Mitsubishi PLFY-P32VKM.UK, PLFY-P40VKM.UK, PLFY-P50VKM.UK, PLFY-P63VKM.UK Service Manual

Page 1
TECHNICAL & SERVICE MANUAL
SPLIT-TYPE,HEAT PUMP AIR CONDITIONERS
Indoor unit
PLFY-P32VKM
PLFY-P32VKM.UK
PLFY-P40VKM
PLFY-P40VKM.UK
PLFY-P50VKM
PLFY-P50VKM.UK
PLFY-P63VKM
PLFY-P63VKM.UK
No. OC204
[Model names]
Ceiling Cassettes
Series PLFY
CONTENTS
1. SAFETY PRECAUTION ·······················3
2. PART NAMES AND FUNCTIONS········4
3. SPECIFICATIONS·································6
4. OUTLINES AND DIMENSIONS············8
5. WIRING DIAGRAM·······························9
6.
REFRIGERANT SYSTEM DIAGRAM
···10
7. TROUBLE SHOOTING ·······················11
8. DISASSEMBLY PROCEDURE···········16
9. PARTS LIST········································19
R407C
[Service Ref.]
R22
Page 2
Page 3
3
SAFETY PRECAUTION
1
Cautions for using with the outdoor unit which adopts R407C refrigerant.
· Do not use the existing refrigerant piping.
-The old refrigerant and refrigerator oil in the existing piping contains a large amount of chlorine which may cause the refrigerator oil of the new unit to deteriorate.
· Do not use crushed, misshapen, or discoloured tubing. The inside of the tubing should be clean and free from harmful sulfuric compounds, oxidants, dirt, debris, oils and
moisture(or any other contaminants).
-Contaminants on the inside of the refrigerant piping may cause the refrigerant residual oil deteriorate.
· Store the piping to be used during installation indoors and keep both ends of the piping sealed until just before brazing. (Store elbows and other joints in a plastic bag.)
-If dust, dirt, or water enters the refrigerant cycle, deterioration of the oil and compressor trouble may result.
· Use liquid refrigerant to fill the system.
-If gas refrigerant is used to seal the system, the composition of the refrigerant in the cylinder will change and performance
may drop.
· Do not use a refrigerant other than R407C.
-If another refrigerant (R22, etc.) is used, the chlorine in the refrigerant may cause the refrigerator oil to deteriorate.
· Use a vacuum pump with a reverse flow check valve.
-The vacuum pump oil may flow back into the refrigerant cycle and cause the refrigerator oil to deteriorate.
· Use ester oil, ether oil or alkyl benzene(small amount) as the refrigerator oil to coat flares and flange connections.
-The refrigerator oil will degrade if it is mixed with a large amount of mineral oil.
· Do not used the following tools that are used with conventional refrigerants. (Gauge manifold, charge hose, charging cylinder, gas leak detector, reverse flow check valve, refrigerant charge
base, vacuum gauge, refrigerant recovery equipment)
-If the conventional refrigerant and refrigerator oil are mixed in the R407C , the refrigerant may deteriorated.
-If water is mixed in the R407C, the refrigerator oil may deteriorate.
-Since R407C dose not contain any chlorine, gas leak detectors for conventional refrigerants will not react to it.
· Be especially careful when managing the tools.
-If dust, dirt, or water gets in the refrigerant cycle, the refrigerant may deteriorate.
· Do not use a charging cylinder.
-Using a charging cylinder may cause the refrigerant to deteriorate.
Page 4
4
2
PART NAMES AND FUNCTIONS
Indoor (Main) Unit
Remote controller
Operation buttons
[PAR-F25MA]
Once the controls are set, the same operation mode can be repeated by simply pressing the ON/OFF button.
Auto Air Swing Vane Disperses airflow up and down and adjusts the angle of airflow direction.
Grille
Filters Removes dust and pollutants from intake air
Horizontal Air Outlet Sets horizontal air flow automatically during cooling or dehumidifying.
Air Intake Intakes air from room.
Press this button to switch the cool, electronic dry (dehumidify), automatic and heater modes.
OPERATION SWITCH button
This sets the room temperature. The temperature setting can be performed in 1: units Setting range Cooler 19: to 30: Heater 17: to 28:
TEMP. ADJUSTMENT button
This switches between continuous operation and the timer operation.
TIMER button
This switches between the operation and stop modes each time it is pressed. The lamp on this button lights during operation.
ON/OFF button
Only press this button to perform an inspection check or test operation. Do not use it for normal operation.
CHECK-TEST RUN button
This sets the ventilation fan speed.
VENTILATION button
This switches the horizontal fan motion ON and OFF.
(This button does not operate in this model)
(When the only LOSSNAY is connected.)
LOUVER button
This adjusts the vertical angle of the ventilation.
AIR DIRECTION button
This resets the filter service indication display
FILTER button
This sets the current time,
start time
and stop time.
TIME SETTING button
This sets the ventilation fan speed.
AIR SPEED button
Page 5
5
Caution
Only the Power display lights when the unit is stopped and power is supplied to the unit.
When power is turned ON for the first time the (CENTRAL CTRL) display appears to go off momentarily but this is not a
malfunction.
When the central control remote control unit, which is sold separately, is used the ON-OFF button, operation switch button and TEMP. adjustment button do not operate.
“NOT AVAILABLE” is displayed when the Air speed button is pressed.This indicates that this room unit is not equipped with the fan direction adjustment function and the louver function.
When power is turned ON for the first time, it is normal that “H0” is displayed on the room temperature indication (For max. 2minutes). Please wait until this “H0” indication has disappeared then start the operation.
4
CENTRALLY CONTROLLED display
This indicates when the unit is controlled by optional features such as central control type remote controller.
TIMER display
This indicates when the continuous operation and time operation modes are set. It also displays the time for the timer operation at the same time as when it is set.
OPERATION MODE display
This indicates the operation mode.
STANDBY display
This indicates when the standby mode is set from the time the sleep operation starts until the heating air is discharged.
DEFROST display
This indicates when the defrost operation is performed.
CHECK display
This indicates when a malfunction has occurred in the unit which should be checked.
CLOCK display
The current time , start time and stop time can be displayed in ten second intervals by pressing the time switch button. The start time or stop time is always displayed during the timer operation.
Display
In this display example on the bottom left, a condition where all display lamps light is shown for explanation purposes although this differs from actual operation.
Operation lamp
This lamp lights during operation, goes off when the unit stops and flashes when a malfunction occurs.
POWER display
This lamp lights when electricity is supplied to the unit.
SET TEMPERATURE display
This displays the selected setting temperature.
FAN SPEED display
This displays the air direction.
ROOM TEMPERATURE display
The temperature of the suction air is displayed during operation. The display range is 8° to 39°C. The display flashes 8°C when the actual temperature is less than 8° and flashes 39°C when the actual temperature is greater than 39°C.
display
This display lights in the check mode or when a test operation is performed.
CHECK MODE
TEST RUN
FILTER display
This lamp lights when the filter need to be cleaned.
AIR DIRECTION display
The selected fan speed is displayed.
Page 6
3
SPECIFICATIONS
3-1. Specification
Item
Power
Cooling
capacity
Heating
capacity
Cooling
Power supply
Heating
Cooling
Starting
current
Heating
Cooling
Power
factor
Electric characteristic
(munsell symbol)
Dimensions
Heating
Exterior
Height
Width
Depth
Heat exchanger
Fan No
F
Air flow #3
a
External
n
static pressure
Fan motor
output
Insulator
Air filter
Pipe
dimensions
Gas side
Liquid
side
Unit drain pipe size
Noise level
Product weight
V·Hz
kcal/h
BTU/h
kW
kcal/h
BTU/h
kW
kW
kW
A
A
%
%
mm
mm
mm
3
m
/min
Pa
kW
ømm
ømm
mm
dB
kg
PLFY-P32VKM.UK PLFY-P40VKM.UK PLFY-P50VKM.UK PLFY-P63VKM.UK
Single phase 220V-240V 50 Hz
3,150
12,500
3.7
3,550
14,100
4.1
0.13
0.13
0.60
0.60
90
90
4,000
15,900
4.7
4,500
17,900
5.2
0.13
0.13
0.60
0.60
90
90
5,000
19,800
5.8
5,600
22,200
6.6
0.14
0.14
0.64
0.64
91
91
6,300
25,000
7.3
7,100
28,200
8.3
0.15
0.15
0.68
0.68
92
92
-Unit : Galvanized sheets · Standard grill : ABS resin acrylic coating Munsell<0.70y 8.59/0.97>
298<30>
660<760>
660<760>
Cross fin
Turbo fan ✕ 1
15-14.5-14-13
16-15-14-13
17-16-15-14
0
0.030
Polyethylene sheet
PP honeycomb fabric
12.7(1/2")
6.35(1/4")
15.88(5/8")
9.52(3/8")
ID32 (PVC pipe VP-25 connectable)
35-34-32.5-31
19<3.7>
37-35.5-34-32
39-38-36.5-35
20<3.7>
Note 1. Rating conditions (JIS B 8615)
Cooling: Indoor: D.B. 27°C, W.B. 19.5°C
outdoor: D.B. 35°C
Heating: Indoor: D.B. 21°C
outdoor: D.B. 7°C, W.B. 6°C Note 2. The number indicated in < > is just for the grill. Note 3. Air flow and the noise level are indicated as High-Medium 1-Medium 2-Low.
6
Page 7
3-2. Electrical parts specifications
Model
Symbol
Parts name
PLFY-P32VKM.UK PLFY-P40VKM.UK PLFY-P50VKM.UK PLFY-P63VKM.UK
Transformer
Room temperature thermistor
Liquid pipe thermistor
Gas pipe thermistor
Fuse (Indoor controller board)
Fan motor (with inner-thermostat)
inner-thermostat (Fan motor)
Fan motor capacitor
T
TH21
TH22
TH23
FUSE
MF
C1
(Primary) 50/60Hz 220-240V (Secondary) (18.4V 1.7A)
Resistance 0°C/15k, 10°C/9.6k, 20°C/6.3k, 25°C/5.4k, 30°C/4.3k, 40°C/3.0k
Resistance 0°C/15k, 10°C/9.6k, 20°C/6.3k, 25°C/5.4k, 30°C/4.3k, 40°C/3.0k
Resistance 0°C/15k, 10°C/9.6k, 20°C/6.3k, 25°C/5.4k, 30°C/4.3k, 40°C/3.0k
250V 6.3A
6-pole OUTPUT 30W
PAI-V30F
OFF 125°C ± 5°C
ON 85°C ± 20°C
2.5µF 400V
Vane motor (with limit switch)
Drain-up mechanism
Drain sensor
Linear expansion valve
Electric heater (Dew prevention)
Power supply terminal block
Transmission terminal block
MV
DP
DS
LEV
H2
TB2
TB5
Heater resistance 82/25°C Thermistor resistance
0°C/15kΩ, 10°C/9.6kΩ, 20°C/6.3kΩ, 25°C/5.4kΩ, 30°C/4.3kΩ, 40°C/3.0kΩ
MC8 200V-240V
2.5/2W 5/6R.P.M
PJV-1002
INPUT 8/7.5W 24L/Hr
DC12V Stepping motor drive port
dimension 3.2 (0~2000pulse)
EDM-402ME
240V 28.8W
(L, N, Earth) 330V 30A
(M1, M2, S) 330V 30A
7
Page 8
8
4
OUTLINES AND DIMENSIONS
PLFY-P32VKM.UK, PLFY-P40VKM.UK PLFY-P50VKM.UK, PLFY-P63VKM.UK
Unit : mm
Models
PLFY-P32VKM.UK PLFY-P40VKM.UK
Refrigerant pipe
(6.35mmdia)
flared connection
1/4F
Refrigerant pipe
(12.7mmdia)
flared connection
1/2F
Refrigerant pipe
(9.52mmdia)
flared connection
3/8F
Refrigerant pipe
(15.88mmdia)
flared connection
5/8F
PLFY-P50VKM.UK PLFY-P63VKM.UK
12
Ceiling hole
Suspension bolt pitch
Suspension bolt M10 or
Air intake hole
Air outlet hole
Air intake grille
690~710 25~3525~35
640
660
466
460
66 35
760
117 117
117
435
13554
117
Ceiling hole
Suspension bolt pitch
Suspension bolt lower edge
Air outlet hole
Air outlet hole
690~710
25~35
25~35
65~80
760
460
466
6635
115
243
253
29830
54
+3
- 2
507
660
54
53
Terminal block for powersupply
Terminal block for control
Drain hole
Drain hole ID32 VP-25 connection
W3/8
Feeding hole (Drain pump)
Leave space of 10~15mm between the top surface of the unit and the ceiling slab.
Ceiling surface
4-Auto vanes
Intake grille opening /closing side
Vane motor
Decorative panel
Control wire entry
Refrigerant piping side electric wire entry side
Power line entry
41 25
Liquid pipe
Gas pipe
Optional high-efficiency filter
+3
-2
NOTE 1.The electrical parts box may be removed during servic­ ing. When connecting the power line and the control
wire,provide enough length to the electric wires. NOTE 2.When installing the optional high-efficiency filter,the
dimension between the transom and ceiling shall be more than 440mm. Also,when installing the optional
fresh air intake casement or the multi-functional case­ ment,the dimension between the transom and ceiling shall be more than 440mm. (The optional high­ efficiency filter can also be installed.)
Page 9
9
WIRING DIAGRAM
5
PLFY-P32VKM.UK, PLFY-P40VKM.UK PLFY-P50VKM.UK, PLFY-P63VKM.UK
}
PE
GRY
GRY
BLK
BLK
BLK
BLK
BLK
BLK
RED
RED
WHT
RED
YLW
ORN
BRN
BLU
M1
TO OUTDOOR UNIT
BC CONTROLLER REMOTE CONTROLLER
DC24-30V
M2
TB5
(SHIELD)
AC18.4V
AC220-240V
BLU
RED
BLU
BLU
BRN
BRN
YLW
YLW
YLW
YLW
WHT
RED
RED
WHT
BLK
(WHT)
FAN1
CNT
(WHT)
TRANS
(GRN)
CNV
(BLU)
CNP
6.3A
250V
FUSE
(RED)
CND
CN3T TRANS (RED)
BLU
BLU
M-NET
(BLU)
CN2M
BRN
BRN
CN23
(GRN) VANE POSITION
4
1
CN41
(WHT)
HA
1
CN32
3
(WHT) REMOTE SWITCH
CN50
DRAIN
(RED)
CN20
(RED)
INTAKE
CN21
LIQUID
(WHT)
CN29
(BLK)
GAS
CN60
LEV
(WHT)
5
(WHT)
CENTRALLY
CONTROL
1
CN51
1
5
(WHT)
REMOTE
INDICATION
CN52
CN42
(RED)
ADDRESS
CN81
(RED)
ADDRESS
12
HUMIDIFIER
CN25
A.B
SW5
240V
220V
SWA
3 2 1
SWB
2 3 4
1
2
3
4
CN43
ADDRESS
(RED)
1
2
3
4
5
6
7
8
ADDRESS
CN82
(RED)
CONNECTION
No.
SW14
0
SWC
SW1
87654321
OFF
ON
109
00
SW11
SW12
1ST.DIGIT
2ND.DIGIT
3RD.DIGIT
6
BLU
RED
GRN/YLW
L N
TB2
TO NEXT INDOOR UNIT
PULL BOX
FUSE(15A)
BREAKER (15A)
POWER SUPPLY ~/N 220-240V 50Hz
SR3
SR1
ZNR
DS
4
I.B
8
TH21
SW2
SEE
fig1
SEE
fig2
10
LEV
TH22
TH23
T
32
SW4
1
10N12345678923456
SW3
0FF
LED4
LED3
LED5LED2
LED1
4
0N 0FF
27 510 61
H2
GRILLE
MV
LS
1
53
X4
X4
87 23456
F.C
1
1 2
4
3
65 1234211342
MF
1432
13
13
13
13
64523
DP
21
C
321
123
31
14532122112
1
1 2
1 2
LEGEND
SYMBOL
NAME
I.B
SYMBOL
T TRANSFORMER
DRAIN SENSOR DRAIN WATER LIFTING-UP MACH. FAN MOTOR (WITH INNER THERMO.) FAN MOTOR CAPACITOR VANE MOTOR LIMIT SWITCH DEW PREVENTION HEATER POWER SUPPLY TERMINAL BLOCK TRANSMISSION TERMINAL BLOCK LINEAR EXPANSION VALVE ADDRESS BOARD MODE SELECTOR
DS DP MF C MV LS H2 TB2 TB5 LEV A.B SW1(A.B) SW5(A.B) SW11(A.B) SW12(A.B) SW14(A.B) SWA(A.B) SWB(A.B)
SWC(A.B)
INDOOR CONTROLLER BOARD
CN25 HUMIDIFIER CONNECTOR
REMOTE SWITCH CONNECTOR HA TERMINAL-A CONNECTOR CENTRALLY CONTROL CONNECTOR REMOTE INDICATION CONNECTOR CAPACITY CORD SWITCH FUNCTION SELECTOR UNIT SELECTOR DRAIN UP MECH RELAY DEW PREVENTION HEATER RELAY VANE RELAY FAN MOTOR RELAY
CN32 CN41 CN51 CN52 SW2 SW3 SW4 SR1
SR3 X4 ZNR FUSE F. C
VARISTOR FUSE(6.3A) FAN PHASE CONTROL
TH21
TH22
TH23
ROOM TEMPERATURE THERMISTOR (0:/15k',25:/5.4k')
LIQUID PIPE THERMISTOR (0:/15k',25:/5.4k')
GAS PIPE THERMISTOR (0:/15k',25:/5.4k')
VOLTAGE SELECTOR 1ST DIGIT ADDRESS SETTING 2ND DIGIT ADDRESS SETTING CONNECTION NO. CEILING HEIGHT SELECTOR
DISCHARGE AIR DIRECTION
OPTION SELECTOR
NAME
NOTE
1.At servicing for outdoor unit,always follow the wiring diagram of outdoor unit.
2.Symbol(S) of TB5 is the shield wire connection.
3.Symbols used in wiring diagram above are, :Terminal block, :Connector.
4.The setting of the SW2 dip switches differs for the capacity. For the detail,see the table below.
5.Please set the switch SW5 according to the power supply voltage. Set SW5 to 240V side when the power supply is 230 and 240 volts. When the power supply is 220 volts,set SW5 to 220V side.
PLFY-P32VKM.UK
MODELS SW2
ON
OFF
1234
ON
OFF
1234
56
56
ON
OFF
123456
ON
OFF
123456
SW2
<fig1> <fig2>
MODELS
PLFY-P40VKM.UK
PLFY-P50VKM.UK
PLFY-P63VKM.UK
PLFY-P32VKM.UK PLFY-P40VKM.UK
PLFY-P50VKM.UK PLFY-P63VKM.UK
MODELS SW3
ON
OFF
1234
ON
OFF
1234
56789
10
6789
10
5
Page 10
10
6 REFRIGERANT SYSTEM DIAGRAM
Strainer (#50mesh)
Strainer (#100mesh)
Strainer (#100mesh)
Heat exchanger
Room temparature thermistor TH21
Gas pipe thermistor TH23
Liquid pipe thermistor TH22
Linear expansion valve
Gas pipe
Flare connection
PLFY-P32VKM.UK, PLFY-P40VKM.UK PLFY-P50VKM.UK, PLFY-P63VKM.UK
Gas pipe
Liquid pipe
PLFY-P32,P40VKM.UK
[12.7<1/2F>
[6.35<1/4F>
PLFY-P50,P63VKM.UK
[15.88<5/8F>
[9.52<3/8F>
Item
Service Ref.
Page 11
7
TROUBLE SHOOTING
7-1. How to check the parts PLFY-P•VKM.UK
Parts name Check points
Room temperature thermistor (TH21) Liquid pipe thermistor (TH22) Gas pipe thermistor (TH23)
Disconnect the connector then measure the resistance using a tester. (Surrounding temperature 10°W~30°C)
Normal
4.3k~9.6k
Abnormal
Open or short
(Refer to the thermistor)
Trans
CNT T CN3T
Red Blue
1 2 3
White
Blue
Vane motor
Fan motor
Relay connector
1
Red
White
2
3
Black
Protector
Linear expansion valve
1
White
M
5
Red
4
6
2
3
Orange
Drain-up mechanism
Gray
1
2
Gray
1 2 3
1
2
3
Blue
Brown
Yellow
Disconnect the connector and measure the resistance using a tester.
Abnormal
Open or short
CNT(1)~(3)
CN3T(1)~(3)
Normal
Approx. 45
Approx. 1
Measure the resistance between the terminals using a tester. (Surrounding temperature 20°C~30°C)
Normal Abnormal
Approx. 14k Open or short
Measure the resistance between the terminals using a tester.
Motor terminal
or
Relay connector
Red-Black
White-Black
Normal
PLFY-P·VKM.UK
P32, P40, P50, P63
136.2k
197.5k
Abnormal
Open or short
Disconnect the connector then measure the resistance using a tester. Refer to the next page for a detail.
Abnormal
Open or short
(1)-(5)
White-Red
Normal
(2)-(6)
Yellow-Blown
(3)-(5)
Orange-Red
(4)-(6)
Blue-Brown
150ki10%
Measure the resistance between the terminals using a tester. (Surrounding temperature 20°C~30°C)
Normal Abnormal
327 Open or short
Drain sensor
Measure the resistance between the terminals using a tester.
1 2 3 4 5
(1)-(3) (4)-(5)
Normal
82
4.3k~9.6k
Abnormal
Open or short
(Refer to the thermistor)
11
Page 12
12
Output
(Phase)
Output
{1
1
ON
{2
ON
{3
OFF
{4
OFF
2
OFF
ON ON
OFF
3 OFF OFF
ON ON
4
ON OFF OFF
ON
<Output pulse signal and the valve operation>
Linear expansion valve operation
Trouble shooting
D
A
E
B
C
Open
Extra tightning (80~100pulse)
Pulse number
2000 pulse Opening a valve all the way
Close
Valve position (capacity)
6 5 4 3 2 1
LED1S
Symptom
Check points
Operation circuit failure of the micro processor.
Disconnect the connector on the controller board, then connect LED for checking.
Pulse signal will be sent out for 10 seconds as soon as the main switch is turned on. If there is flashing LED it means the operation circuit is abnormal.
Countermeasures
Exchange the indoor controller board at drive circuit failure.
Linear expansion valve mechanism is locked.
Valve doesn't close completely (thermistor leaking).
Wrong connection of the connector or contact failure.
To check the linear expansion valve, operate the indoor unit in fan mode and at the same time operate other indoor units in cooling mode, then check the pipe temperature <liquid
pipe temperature> of the indoor unit by the outdoor multi controller board operation monitor. During fan operation, linear expansion valve is closed completely and if there is some leaking, detecting temperature of the thermistor will decrease. If the detected temperature is much lower
than the temperature indicated in the remote controller, it means the valve is not closed all the way. It is not necessary to exchange the linear expansion valve, if the leakage is small and not making any trouble.
Liquid pipe thermistor
Linear expansion valve
Motor will idle and make ticking noise when motor is operated while the linear expansion valve is locked. This ticking sound is the sign of the abnormality.
Check the color of lead wire and missing terminal of the connector.
Exchange the linear expansion valve.
Exchange the linear expansion valve.
If large amount of thermistor is leaked, exchange the linear expansion valve.
Disconnect the connector at the controller board, then check the continuity.
Measure the resistance between each coil (red-white, red­orange, brown-yellow, brown-blue) using a tester. It is normal if the resistance is in the range of 150" i 10%.
Short or breakage of the motor coil of the linear expansion valve.
Closing a valve : 1 2 3 4 1 Opening a valve : 4 3 2 1 4
The output pulse shifts in the above order. 1. When linear expansion valve operation stops, all output phases
become OFF.
2. At phase interruption or when the phase does not shift in order, the motor does not rotate smoothly and will lock and vibrate.
When the switch is turned on, a 2200 pulse opening valve signal
will be sent until point
A is reached in order to define the valve
position.
When the valve moves smoothly, there is no noise or vibration occurring from the linear expansion valve : however, when the pulse number moves from
E to A or when the valve is locked,
more noise can be heard than in normal situations.
Noise can be detected by placing the ear against the screw
driver handle while putting the screw driver to the linear expansion valve.
Page 13
13
0
10
20
30
40
50
-20 -10 0 10 20 30 40 50
< Thermistor for lower temperature >
Temperature (:)
Resistance (k")
4
[4
3
62
5
[3
2
[2
1
[1
[4
[3
[2
[1
Controller board
Drive circuit
Relay connector
Connector(CN60)
DC12V
Brown
Red
Blue
Orange
Yellow
White
5
1
3
4
6
M
4
6
2 3
5
1
Blue
Brown
Yellow
Orange
Red
White
Linear expansion valve
<Thermistor Characteristic graph>
Room temperature thermistor(TH21) Liquid pipe thermistor(TH22) Gas pipe temperature thermistor(TH23) Drain sensor(THD)
Thermistor R
0=15k' ±3%
Fixed number of B=3480k' ±2%
Rt=15exp { 3480( ) }
0: 15k' 10: 9.6k' 20: 6.3k' 25: 5.2k' 30: 4.3k' 40: 3.0k'
Thermistor for lower temperature
Linear expansion valve
Operation summary of the linear expansion valve.
• Linear expansion valve opens/closes through a stepping motor after receiving the pulse signal from the indoor controller board.
• Valve position can be changed in proportion to the number of pulse signals. <Connection between the indoor controller board and the linear expansion valve>
1
273+t
1
273
Note : Since the number of the connector at the controller board side and the relay connector are different, follow the color of
the lead wire.
Page 14
14
7-2. FUNCTION OF DIP SWITCHES
Switch Function Remarks
<At delivery>
ON
OFF
123456789
10
Address board
Operation by switch
ON OFF
(Note1) Fan operation at Heating mode.
(Note1) Heater thermo ON is operating.
(Note1) SW 1-7=OFF, SW 1-8=ON Setting air flow. SW 1-7=ON, SW 1-8=ON → Indoor fan stop.
Pole
Built-in remote controller
Provided
2,500hr
Effective
Thermostat ON signal indication
Always operated while in heating mode
Low
Setting air flow
Effective
Effective
Filter clogging detection
Filter cleaning sign
Air intake
Remote indication switching
Humidifier control
Auto reset function
Power ON/OFF
Indoor unit
Not provided
100hr
Not effective
Fan output indication
Operated depending on the condition
Extra low
Depends on SW1-7
Not effective
Not effective
Cooling only
Available
Available
Available
Second setting
Horizontal angle
Effective
Not effective
5deg.(R-22)/9deg.(R407C)
15deg.
Heat pump / Cool only
Louver
Vane
Vane swing function
Vane horizontal angle
Vane cooling limit angle setting
Heater 4deg. up
Superheat setting temperature
Superheat setting temperature
Heat pump
Not available
Not available
Not available
First setting
Down B, C
Not effective
Effective
2deg.(R-22)/6deg.(R407C)
10deg.
1 2 3 4 5 6 7 8 9
10
1 2 3 4 5 6 7 8 9
10
SW1
Mode
Selection
SW2
Capacity
code
setting
1~6
1~3
SW3
Function
Selection
SW4
Unit
Selection
Indoor linear expansion valve opening
Thermistor <intake temperature detection> position
Air flow set in case of heat thermostat OFF
<At delivery>
ON
OFF
123456789
10
Indoor controller board
(Note1) At cooling mode, each angle can be used only for 1 hour.
<At delivery>
ON
OFF
1234
Indoor controller board
<At delivery>
Set while the unit is off.
Set while the unit is off.
Set while the unit is off.
Set for each capacity.
Indoor controller board
(SW 3-9) PLFY-P32, P40VKM.UK=ON PLFY-P50, P63VKM.UK=OFF
ON
OFF
1234
ON
OFF
MODELS
PLFY-
P32VKM.UK
PLFY-
P50VKM.UK
PLFY-
P40VKM.UK
PLFY-
P63VKM.UK
SW 2 MODELS SW 2
123456
ON
OFF
123456
ON
OFF
123456
ON
OFF
123456
Page 15
15
0
5
9
4
8
3
7
2
6
1
0
5
9
4
8
3
7
2
6
1
0
5
9
4
8
3
7
2
6
1
0
5
9
4
8
3
7
2
6
1
0
8
F
7
E
6
D
5
C
4
B
3
A
2
9
1
0
8
F
7
E
6
D
5
C
4
B
3
A
2
9
1
220V 240V
Switch
SWA
Set the
Ceiling
height
SWB
Discharge
Air
Direction
SWC
Option
Rotary switchRotary switch
SW14
Connection
No.
setting
SW5
Voltage
Selection
SW11
1st digit
address
setting
SW12
2st digit
address
setting
Pole
(High ceiling) (Standard) (Silent)
3 2 1
Not used
3 way 4 way
Option
Standard
Option
Standard
1~3
3
SWB
3 way 4 way
2.7m
2.4m
3.0m
2.7m
3.3m
3.0m
2
2
Operation by switch
Ceiling height can be changed depending on SWB setting.
Address setting should be done when network remote controller (PAR-F25MA) is being used.
When attaching the optional high performance filter elements (filter casement) to the unit, be sure to attach it to the option side in order to prevent the air flow reducing.
This is the switch to be used when the indoor unit is operated with R2, R3, series outdoor unit as a set.
If the unit is used at the 230V or 240V area, set the voltage to 240V. If the unit is used at the 220V, set the voltage to 220V.
Remarks
<At delivery>
Address board
<At delivery>
Address board
<At delivery>
Address board
Address can be set while the unit is stopped.
Address board
<At delivery>
Address board
<At delivery>
Address board
3 2 1
2 3 4
SW1210SW11
1
SW12 SW11
SW14
SW14
<At delivery>
220V 240V
SWA
123
Page 16
16
8
DISASSEMBLY PROCEDURE
OPERATING PROCEDURE PHOTOS&ILLUSTRATIONS
1. Removing the air intake grille
(1) Press the button. (2) Open the intake grille 90°. (3) Remove the clip. (4) Slide the shaft in the hinge to the left and remove the
intake grille.
PUSH
4. Removing the fan motor
(1) Remove the fan guard. (2) Remove the turbo-fan nut and radiator aluminum cap. (3) Pull out the turbo fan. (4) Disconnect the connector of the fan motor lead wire. (5) Remove the 3nuts of fan motor.
3. Removing the electrical parts box
(1) Remove the fan grand. (2) Disconnect the lead wire of the vane motor from the clamp,
and disconnect the red connector (8P). (3) Remove 2 of 4 screws from the electrical parts cover. (4) Remove the electrical parts cover. (5) Disconnect the following connectors from the box.
Red (3P) for the fan motor White (2P) for the indoor coil thermistor Blue (2P) for the drain pump White (4P) for the drain sensor
(6) Disconnect the green anti-falling wire of the electrical parts
box. (7) Remove 3 of 4 screws from the electrical parts box, and
loosen the other screw. (8) Pull out the electrical parts box.
Electrical parts inside the box
Terminal block
Transformer
Indoor fan capacitor
Room temperature thermistor
Indoor controller board
2. Removing the fan guard.
(1) Open the intake grille. (2) Remove the 4 screws of the fan guard.
1. INDOOR UNIT
Be careful on removing heavy parts.
Photo 1
Photo 2
Photo 3
Figure 1
Photo 4
nut
Fan motorConnector
Fan guard screws
Lead wire for vane motor
ConnectorTerminal blockAnti-falling wire
Radiator aluminum cap
Capacitor
Nut
Screws
Box cover
Clamp
Fan guard
Electrical box
Connector
Room temperature thermistor
Screws
Transformer
Indoor controller board
PLFY-P63VKM.UK
PUSH button
Shaft
Intake grille
Page 17
17
OPERATING PROCEDURE PHOTOS&ILLUSTRATIONS
5. Removing the room temperature thermistor
(1) Remove the fan guard. (2) Remove the electrical box cover (3) Remove the holder and the room temperature thermistor
by pulling the catch.
(4) Disconnect the red connector, CN20, on the indoor
controller board.
6. Removing the liquid pipe thermistor
(1) Remove the fan guard. (2) Remove the electrical box cover. (3) Remove the electrical box. (4) Remove the turbo fan. (5) Remove the screw of the service panel. (6) Remove the service panel. (7) Remove the liquid pipe thermistor(TH22) from the holder
attached to the copper pipe.
(8) Disconnect the 2-pin white connector.
7. Removing the panel
(1) Open the intake grille. (2) Disconnect the connector the vane motor. (3) Remove 4 screws of the panel. (4) Pulling the temporary handing hook, remove the panel.
8. Removing the drain pan
(1) Remove the panel. (2) Remove the fan guard. (3) Remove the rubber bushing. (4) Drain the remaining water in the drain pan. (5) Remove the electrical box cover. (6) Remove the electrical box. (7) Remove the screw of the V.A. cover, and remove the V.A.
cover.
(8) Remove each screw of the corner supports 1,2, and 3,
and remove the corner supports 1,2 and 3.
(9) Pull out the drain pan.
wPull the left and right of the pan gradually.
Be careful not to crack or damage the pan.
Photo 8
Photo 7
Photo 6
Photo 5
Indoor controller board
Room temperature thermistor
Mounting hole
Corner support 1
Corner support 3
VA cover
Rubber bush
Corner support 2
Screws
screws
screws
Panel
Fan guard
Temporary hanging hook
Temporary hanging hook
Liquid pipe thermistor(TH22)
Page 18
18
OPERATING PROCEDURE PHOTOS&ILLUSTRATIONS
9. Removing the drain pump and drain sensor
(1) Remove the panel. (2) Remove the fan guard. (3) Remove the electrical parts cover. (4) Remove the electrical parts box. (5) Remove the drain pan. (6) Remove 4 screws of the drain pump. (7) Pulling the clip of the drain hose, pull out the drain hose
from the drain pump. (8) Remove the drain sensor and the holder. (9) Pull out the drain pump.
11. Removing the heat exchanger
(1) Remove the panel. (2) Remove the fan guard. (3) Remove the electrical parts cover. (4) Remove the electrical parts box. (5) Remove the drain pan. (6) Remove the turbo fan. (7) Remove the screw of the coil support A. (8) Remove 2 screws of the coil support B. (9) Remove 2 screws of the coil.
(10) Remove 4 screws of the piping cover of the outer wall,
and pull out the piping cover.
Photo 9
Drain hose
Drain pump
Drain sensor holder
Screw
Clip
Photo 10
Photo 11
Heat exchanger
Coil support B
Coil support A
Coil screw
Screws of piping cover
Piping
cover
Gas pipe thermistor(TH23)
10. Removing the gas pipe thermistor
(1) Remove the panel. (2) Remove the fan guard. (3) Remove the electrical parts cover. (4) Remove the electrical parts box. (5) Remove the drain pan. (6) Remove the turbo fan. (7) Remove the gas pipe thermistor(TH23) from the holder
attached to the copper pipe. (8) Disconnect the 4-pin connector.
Page 19
19
PARTS LIST
9
1 2 3 4 5 6 7
S70 29H 003 S70 29H 500 S70 29H 691 S70 29H 061 S70 29H 098 S70 B00 713 S70 A00 305
1 1 1 2 1 1 1
R.B
AIR OUTLET GRILLE AIR FILTER INTAKE GRILLE HINGE GRILLE HANGER REMOTE CONTROLLER REMOTE CONTROLLER CABLE
10m
No. Part No. Part Name Specification
Q'ty/set
Price
Unit
Amount
Remarks
(Drawing No.)
Wiring
Diagram
Symbol
Recom-
mended
Q'ty
PLFY-P32/P40/
P50/P63
VKM.UK
PANEL PARTS PLFY-P32VKM.UK PLFY-P40VKM.UK PLFY-P50VKM.UK PLFY-P63VKM.UK
7
6
Page 20
20
10
11
12
35
19
28
2931
32
39
30
24
27
26
25
15
14
7
6
3
4
33
8
9
5
1
2
34
23
22
13
36
38
37
16
21
17
18
20
21
FUNCTIONAL PARTS PLFY-P32VKM.UK PLFY-P40VKM.UK PLFY-P50VKM.UK PLFY-P63VKM.UK
Page 21
Part No. Part Name Specification
No.
1
S70 002 687
2
S70 101 130
3
S70 100 130
4
S70 101 130
5
S70 100 130
6
S70 E00 762
7
S70 001 133
8
S70 001 659
9
S70 41N 114 S70 12B 202
10
11
S70 29H 523
12
S70 55K 355
13
S70 001 266 S70 12B 480
14
S70 14B 480 S70 15B 480
15
S70 A00 529
16
S70 001 660
17
S70 002 660
18
S70 003 660
19
S70 004 660
20
S70 001 657
21
S70 001 099
22
S70 521 716
23
S70 B02 716
24
S70 29H 255
25
S70 001 656 S70 030 310 S70 040 310
26
S70 050 310 S70 060 310 S70 001 239
27
S70 B02 799
28
S70 050 202
29
S70 003 501
30
S70 002 502
31
S70 A00 675
32
S70 001 097
33
S70 A48 524
34
S70 006 533
35
S70 060 202
36
S70 12A 401
37
S70 B02 304
38
S70 05B 294
39
BASE LEG LEG LEG LEG FAN MOTOR MOTOR MOUNT INNER COVER TURBO FAN LIQUID PIPE THERMISTOR DRAIN SOCKET DRAIN PUMP DRAIN SENSOR HEAT EXCHANGER HEAT EXCHANGER HEAT EXCHANGER DRAIN PAN CORNER SUPPORT(1) CORNER SUPPORT(2) CORNER SUPPORT(3) CORNER SUPPORT(4) VA COVER ASSY PANEL HOOKS POWER SUPPLY TERMINAL BLOCK TRANSMISSION TERMINAL BLOCK FAN MOTOR CAPACITOR B.BOX PLATE ASSY INDOOR CONTROLLER BOARD INDOOR CONTROLLER BOARD INDOOR CONTROLLER BOARD INDOOR CONTROLLER BOARD FUSE TRANSFORMER ROOM TEMPERATURE THERMISTOR ELECTRICAL PARTS COVER BELL MOUTH FAN GUARD NUT/WASHER/CAP DRAIN PLUG SENSOR HOLDER GAS PIPE THERMISTOR LINEAR EXPANSION VALVE ADDRESS CABLE ADDRESS BOARD
PAI-V30F
(L, N, GND) (M1, M2, S)
2.5µF 400V
250V 6.3A
Q'ty/set Price
PLFY-P·VKM.UK
P32 P40 P50
1
1 1 1 1 1 1 3 1 1 1 1 1 1 1
1 1 1 1 1 1 2 1 1 1 1 1
1 1 1 1 1 1 1 1 1 1 1 1 1
1
1
1
1
1
1
1
1
1
1
1
3
3
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Remarks
(Drawing No.)
P63
1 1 1 1 1 1 3 1 1 1 1 1 1
1 1 1 1 1 1 1
(PART OF GRILLE)
2 1 1 1 1
1
(PART OF THE BOARD)
1 1 1 1 1 1 1 1 1 1 1 1 1
Wiring
Diagram
Symbol
MF
TH22
DP DS
TB2 TB5
C
I.B I.B I.B I.B
FUSE
T
TH21
TH23
LEV
A.B
Recom-
mended
Q'ty
Unit
Amount
21
Page 22
22
1 2 3 4 5 6 7 8 9
S70 29H 002 S70 29H 085 S70 29H 223 S70 29H 063 S70 31H 063 S70 29H 056 S70 29H 040 S70 29H 041 S70 29H 049
4 1 1 1 1 1 1 1 1
MV
<3/SET>
AUTO VANE AIR GUIDE VANE MOTOR SPRING JOINT 1 SPRING JOINT 2 PUSH BUTTON GRILLE GEAR RIGHT GRILLE GEAR LEFT LID (UP)
No. Part No. Part Name Specification
Q'ty/set
Price
Unit
Amount
Remarks
(Drawing No.)
Wiring
Diagram
Symbol
Recom­mended
Q'ty
PLFY-P32/P40 /P50/P63
VKM.UK
PANEL PARTS PLFY-P32VKM.UK PLFY-P40VKM.UK PLFY-P50VKM.UK PLFY-P63VKM.UK
Page 23
Page 24
HEAD OFFICE MITSUBISHI DENKI BLDG.MARUNOUCHI TOKYO100-8310 TELEX J24532 CABLE MELCO TOKYO
cCopyright 1999 MITSUBISHI ELECTRIC ENGINEERING CO., LTD. Issued in Dec. 1999. No. OC204 300 Issued in Dec. 1999. No. OC204 242 Printed in Japan
New publication, effective Dec. 1999 Specifications subject to change without notice
TM
Loading...