Mitsubishi Electronics PLFY-P36, PLFY-P30, PLFY-P24, PLFY-P18, PLFY-P15 User Manual

...
SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
TECHNICAL & SERVICE MANUAL
R410A / R22
Indoor unit [Model names] [Service Ref.]
PLFY-P12NBMU-E
PLFY-P15NBMU-E
PLFY-P18NBMU-E
PLFY-P24NBMU-E
PLFY-P30NBMU-E
PLFY-P36NBMU-E
PLFY-P PLFY-P PLFY-P PLFY-P PLFY-P PLFY-P PLFY-P PLFY-P PLFY-P PLFY-P PLFY-P
12NBMU-E 12NBMU-ER1 15NBMU-E 15NBMU-ER1 18NBMU-E 18NBMU-ER1 24NBMU-E 24NBMU-ER1 30NBMU-E 30NBMU-ER1 36NBMU-E
November 2008
No. OCH421
REVISED EDITION-A
Revision:
PLFY-P12/15/18/24/30/36
NBMU-ER1 are added in REVISED EDITION-A.
Some descriptions have
been modified.
Plase void OCH421.
Note:
• This manual does not cover outdoor units.
When servicing them, please refer to the outdoor unit’s service manual.
• RoHS compliant products
have <G> mark on the spec name plate.
Model name indication
PLFY-P
INDOOR UNIT
36NBMU-ER1
CONTENTS
1. TECHNICAL CHANGES
2. FEATURES
3. PART NAMES AND FUNCTIONS
4. SPECIFICATIONS
5. 4-WAY AIR FLOW SYSTEM
6. OUTLINES AND DIMENSIONS
7. WIRING DIAGRAM REFRIGERANT SYSTEM DIAGRAM
8.
9. MICROPROCESSOR CONTROL
10. TROUBLESHOOTING
11. DISASSEMBLY PROCEDURE
PARTS CATALOG (OCB421)
.............................................
...................................
...................
...............................
..........
............
......
.........
.............
2 2
3
5
9 12 13 14 15
22
31
1
TECHNICAL CHANGES
PLFY-P12NBMU-E PLFY-P12NBMU-ER1 PLFY-P15NBMU-E PLFY-P15NBMU-ER1 PLFY-P18NBMU-E PLFY-P18NBMU-ER1 PKFY-P24NBMU-E PLFY-P24NBMU-ER1 PKFY-P30NBMU-E PLFY-P30NBMU-ER1 PKFY-P36NBMU-E PLFY-P36NBMU-ER1
INDOOR CONTROLLER BOARD (I.B.) has been changed.
2
FEATURES
Indoor Unit
Models
PLFY-P12NBMU-E 12,000 / 13,500 Btu/h PLFY-P15NBMU-E 15,000 / 17,000 Btu/h PLFY-P18NBMU-E 18,000 / 20,000 Btu/h PLFY-P24NBMU-E 24,000 / 27,000 Btu/h PLFY-P30NBMU-E 30,000 / 34,000 Btu/h PLFY-P36NBMU-E 36,000 / 40,000 Btu/h
Cooling capacity / Heating capacity
1. WIDE AIRFLOW
The new wide shape vane capable of wide angle air supply provides comfort even at the corners of a room regardless of cooling and heating operation. A reduction in the air speed by 20% compared to the conventional product eliminates uncomfortable draft sensation for friendly air conditioning.
2. WAVE AIRFLOW SYSTEM (HEATING MODE)
The wave airflow system has 4 vanes where each vane runs independently. Repeating of horizontal and down blows with a time lag allows the conditioned warm air to be distributed even to room corners thus preventing uneven room temperature distribution.
Operation image of "Wave Airflow"
3. AUTOMATIC AIR SPEED ADJUSTMENT MODE
The automatic air speed adjustment mode is provided in addition to the 4 air speed stages of "High/Medium 1/Medium 2/ Low." Air speed can be changed freely in accordance with a difference between the set temperature and the room tempera­ture. The automatic air speed adjustment mode presents quick cooling of a room with the high mode, such as at the start­ing up of cooling operation, for example. After the room temperature is stabilized, the low mode will be applied by automatic switching to keep your comfort.
Medium 2
Medium 1
HighLow
Automatic air
speed adjustment
4. i-see Sensor (OPTIONAL CORNER PANEL)
The i see sensor is a radiation temperature sensor originated from Mitsubishi’s new technology. In order to create a really comfortable space in shops and offices, it is essential to control the temperature near the floor where occupants/visitors gather. The i see sensor measures the infrared rays generated from the surrounding wall and floor surface at an angle of 360° and the infrared ray energy is computed to convert it into the value of temperature. In addition, the floor temperature at distant spots (radiation temperature) is also measured to supply the optimum airflow to realize comfort which was never experienced in the past.
2
3
PART NAMES AND FUNCTIONS
Indoor unit
Air outlet
Liquid pipe
Gas pipe
i-see sensor (option)
Vane
Wired remote controller
Drain pipe
Filter
Air intake (Intake grille)
Operation Section
Temperature setting buttons
Down
Up
Timer Menu button (Monitor/Set button)
Mode button (Return button)
Set Time buttons
Back
Ahead
Timer On/Off button (Set Day button)
Opening the lid
TEMP.
MENU
BACK DAY
MONITOR/SET
PAR-21MAA
CLOCK
ON/OFF
ON/OFF
FILTER
CHECK
OPERATION
Built-in temperature sensor
CLEAR
TEST
ON/OFF button
Fan Speed button
Filter button (<Enter> button)
Test Run button
Check button (Clear button)
Airflow Up/Down button
Louver button ( Operation button)
To return operation number
Ventilation button ( Operation button)
To go to next operation number
3
Wired remote controller
Display Section
For purposes of this explanation, all parts of the display are shown as lit. During actual operation, only the relevant items will be lit.
Identifies the current operation
Shows the operating mode, etc. *Multilanguage display is available.
“Centrally Controlled” indicator
Indicates that operation from the remote controller has been prohib­ited by a master controller.
“Timer is Off” indicator
Indicates that the timer is off.
Temperature Setting
Shows the target temperature.
Day-of-Week
Shows the current day of the week.
Time/Timer Display
Shows the current time, unless the simple or Auto Off timer is set. If the simple or Auto Off timer is set, the time to be switched off is shown.
TIME SUN MON TUE WED THU FRI SAT TIMER
AFTER
ERROR CODE
°F°C
Hr
AFTER
°F°C
ONLY1Hr.
Up/Down Air Direction indica­tor
The indicator shows the direc­tion of the outcoming airflow.
“One Hour Only” indicator
Displayed if the airflow is set to Low or downward during COOL or DRY mode. (Operation varies according to model.) The indicator goes off in one hour, at which time the airflow direction also changes.
Room Temperature display
Shows the room temperature. The room temperature display range is 46–102F. The display blinks if the temperature is less than 46
Louver display
Indicates the action of the swing louver. Does not appear if the louver is not running.
(Power On indicator)
Indicates that the power is on.
ON
OFF
FUNCTION
FILTER
WEEKLY
SIMPLE
AUTO OFF
F
or 102F or more.
“Sensor” indication
Displayed when the remote controller sensor is used.
“Locked” indicator
Indicates that remote controller but­tons have been locked.
“Clean The Filter” indicator
To be displayed on when it is time to clean the filter.
Timer indicators
The indicator comes on if the corre­sponding timer is set.
Fan Speed indicator
Shows the selected fan speed.
Ventilation indicator
Appears when the unit is running in Ventilation mode.
Note:
“PLEASE WAIT” message This message is displayed for approximately 3 minutes when power is supplied to the indoor unit or when the unit is recovering from a power failure. “NOT AVAILABLE” message
This message is displayed if an invalid button is pressed (to operate a function that the indoor unit does not have). If a single remote controller is used to operate multiple indoor units simultaneously that are different types, this message will not be displayed as far as any of the indoor units is equipped with the function.
4
4
SPECIFICATIONS
4-1. SPECIFICATIONS
Model
Power source Cooling capacity (Nominal)
Heating capacity (Nominal )
External finish External dimension H
Net weight Decoration panel
Heat exchanger FAN
Noise level (Low-Mid2-Mid1-High) (measured in anechoic room)
Insulation material Air filter Protection device Refrigerant control device Connectable outdoor unit Diameter of
refrigerant pipe (O.D.)
Field drain pipe size
Standard attachment
Optional parts
Remark
Power input Current input
Power input Current input
×
W × D
Model External finish Dimension
×
W × D
H Net weight
Type x Quantity External static press.
Motor type Motor output Driving mechanism Airflow rate (Low-Mid2-
Mid1-High)
Liquid
Gas
Document Accessory
Air outlet shutter plate High efficiency filterelement Multi-function casement
*1
*1
*2
*2
(R410A)
(R22)
(R410A)
(R22)
BTU/h
kW kW A Btu/h kcal/h kW A
in. mm Ibs (kg)
in. mm
Ibs (kg)
in.WG Pa
in.WG Pa
kW
cfm
3
m
/min L / s
dB <A> dB <A> dB <A>
in. (mm)
in. (mm)
in. (mm)
PLFY-P12NBMU-E
PLFY-P12NBMU-ER1
12,000
3.5
0.03
0.22
13,500
4.0
0.02
0.14
10-3/16 × 33-3/32 × 33-3/32 10-3/16 × 33-3/32 × 33-3/32 10-3/16 × 33-3/32 × 33-3/32
258
×
840 × 840
49 (22) 49 (22) 51 (23)
PLP-40BAU PLP-40BAU PLP-40BAU
1-3/8 × 37-13/32 × 37-13/32
35
×
950 × 950
13 (6) 13 (6) 13 (6)
0.000 (208V) 0.000 (208V) 0.000 (208V) 0
0.000 (230V) 0
0.050
388 - 424 - 459 - 494
11.0 - 12.0 - 13.0 - 14.0 183 - 200 - 217 - 233
27 - 28 - 29 - 31 (208-230V)
— —
PP honeycomb (long life filter, anti-bacterial type)
1/4 (6.35) Flare 1/4 (6.35) Flare
1/2 (12.7) Flare 1/2 (12.7) Flare
O.D. 1-1/4 (32) O.D. 1-1/4 (32) O.D. 1-1/4 (32)
PAC-SH51SP-E PAC-SH59KF-E PAC-SH53TM-E
PLFY-P15NBMU-E
PLFY-P15NBMU-ER1
1-phase 208-230V 60Hz
15,000
4.4
0.04
0.29
17,000
5.0
0.03
0.22
Galvanized steel sheet
258× 840 × 840 258× 840 × 840
MUNSELL (6.4Y 8.9/0.4)
1-3/8 × 37-13/32 × 37-13/32
35× 950 × 950
Cross fin
Turbo fan
0.000 (230V)
424 - 459 - 494 - 565
12.0 - 13.0 - 14.0 - 16.0 200 - 217 - 233 - 267
27 - 28 - 30 - 31 (208-230V)
R410A, R22 CITY MULTI
1/4 (6.35) Flare 1/4 (6.35) Flare
1/2 (12.7) Flare 1/2 (12.7) Flare
Installation Manual, Instruction Book
PAC-SH51SP-E PAC-SH59KF-E PAC-SH53TM-E
0
0
DC motor
0.050
Direct-drive
— —
PS
Fuse
LEV
×
1Turbo fan × 1 Turbo fan × 1
PLFY-P18NBMU-E
PLFY-P18NBMU-ER1
18,000
5.3
0.05
0.36
20,000
5.9
0.04
0.29
1-3/8 × 37-13/32 × 37-13/32
35× 950 × 950
0
0.000 (230V) 0
0.050
494 - 530 - 565 - 636
14.0 - 15.0 - 16.0 - 18.0 233 - 250 - 267 - 300
28 - 29 - 30- 32 (208-230V)
— —
1/4 (6.35) Flare 3/8 (9.52) Flare
1/2 (12.7) Flare 5/8 (15.88) Flare
PAC-SH51SP-E
PAC-SH59KF-E
PAC-SH53TM-E
Installation
*1 Nominal cooling conditions Note: *2 Nominal heating conditions
Indoor : 80degF D.B. / 67degF W.B.
(26.7degC D.B. / 19.4degC W.B.)
Outdoor : 95degF D.B. 47degF D.B. / 43degF W.B.
(35degC D.B.) (8.3degC D.B. / 6.1degC W.B.)
Pipe length : 25 ft. (7.6 m) 25 ft. (7.6 m)
Level difference : 0 ft. (0 m) 0 ft. (0 m)
*Due to continuing improvement, above specification may be subject to change without notice.
Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the Installation Manual.
70degF D.B. (21.1degC D.B.)
5
Unit converter
kcal/h = kW × 860 BTU/h = kW × 3,412
3
cfm = m
/min × 35.31
lbs = kg/0.4536
*Above specification data is subject to rounding variation.
Model
Power source Cooling capacity (Nominal)
Power input Current input
Heating capacity (Nominal )
Power input Current input
External finish External dimension H × W × D
Net weight Decoration panel
Model External finish Dimension H × W × D
Net weight Heat exchanger FAN
Type × Quantity
External
static press.
Motor type
Motor output
Driving mechanism
Airflow rate
(Low-Mid2-
Mid1-High)
Noise level (Low-Mid2-Mid1-High) (measured in anechoic room)
Insulation material Air filter Protection device Refrigerant control device Connectable outdoor unit Diameter of
Liquid
(R410A) refrigerant pipe (O.D.)
Gas
(R410A)
Field drain pipe size
Standard attachment
Optional parts
Document Accessory
Air outlet shutter plate High efficiency filterelement Multi-function casement
Remark
(R22)
(R22)
*1
*1
*2
*2
BTU/h
kW kW A
Btu/h
kcal/h kW A
in. mm Ibs (kg)
in. mm
Ibs (kg)
in.WG Pa
in.WG Pa
kW
cfm
3
/min
m L/s
dB <A> dB <A> dB <A>
in. (mm)
in. (mm)
in. (mm)
PLFY-P24NBMU-E
PLFY-P24NBMU-ER1
24,000
7.0
0.06
0.43
27,000
7.9
0.05
0.36
10-3/16× 33-3/32 × 33-3/32
258 × 840 × 840
51 (23)
PLP-40BAU
1-3/8× 37-13/32 × 37-13/32
35 × 950 × 950
13 (6)
0.000 (208V) 0
0.000 (230V) 0
0.050
530 - 565 - 636 - 706
15.0 - 16.0 - 18.0 -20.0 250 - 267 - 300 - 333
28 - 30 - 32 - 34 (208-230V)
— —
3/8 (9.52) Flare 3/8 (9.52) Flare
5/8 (15.88) Flare 5/8 (15.88) Flare
O.D. 1-1/4 (32)
PAC-SH51SP-E
PAC-SH59KF-E
PAC-SH53TM-E
PLFY-P30NBMU-E
PLFY-P30NBMU-ER1
1-phase 208-230V 60Hz
30,000
8.8
0.07
0.51
34,000
10.0
0.06
0.43
Galvanized steel sheet
10-3/16× 33-3/32 × 33-3/32
258 × 840 × 840
51 (23)
PLP-40BAU
MUNSELL (6.4Y 8.9/0.4)
1-3/8× 37-13/32 × 37-13/32
35 × 950 × 950
13 (6)
Cross fin
0.000 (208V) 0
0.000 (230V) 0
DC motor
0.050
Direct-drive
565 - 636 - 706 - 777
16.0 - 18.0 - 20.0 - 22.0 267 - 300 - 333 - 367
30 - 32 - 35 - 37 (208-230V)
— —
PS
PP honeycomb (long life filter, anti-bacterial type)
Fuse
LEV
R410A, R22 CITY MULTI
3/8 (9.52) Flare 3/8 (9.52) Flare
5/8 (15.88) Flare 5/8 (15.88) Flare
O.D. 1-1/4 (32)
Installation Manual, Instruction Book
PAC-SH51SP-E PAC-SH59KF-E PAC-SH53TM-E
PLFY-P36NBMU-E
PLFY-P36NBMU-ER1
36,000
10.5
0.16
1.07
40,000
11. 7
0.15
1.00
11-3/4 × 33-3/32 × 33-3/32
298 × 840 × 840
60 (27)
PLP-40BAU
1-3/8× 37-13/32 × 37-13/32
35 × 950 × 950
13 (6)
Turbo fan × 1 Turbo fan × 1 Turbo fan × 1
0.000 (208V) 0
0.000 (230V) 0
0.120
777 - 883 - 989 - 1,059
22.0 - 25.0 - 28.0 - 30.0 367 - 417 - 467 - 500
35 - 38 - 41 - 43 (208-230V)
— —
3/8 (9.52) Flare 3/8 (9.52) Flare
5/8 (15.88) Flare 3/4 (19.05) Flare
O.D. 1-1/4 (32)
PAC-SH51SP-E
PAC-SH59KF-E
PAC-SH53TM-E
Installation
Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the Installation Manual.
*1 Nominal cooling conditions Note: *2 Nominal heating conditions
Indoor : 80degF D.B. / 67degF W.B.
(26.7degC D.B. / 19.4degC W.B.)
70degF D.B. (21.1degC D.B.)
Outdoor : 95degF D.B. 47degF D.B. / 43degF W.B.
(35degC D.B.) (8.3degC D.B. / 6.1degC W.B.)
Pipe length : 25 ft. (7.6 m) 25 ft. (7.6 m)
Level difference : 0 ft. (0 m) 0 ft. (0 m)
*Due to continuing improvement, above specification may be subject to change without notice.
6
Unit converter
kcal/h = kW × 860 BTU/h = kW × 3,412
3
cfm = m
/min × 35.31
lbs = kg/0.4536
*Above specification data is subject to rounding variation.
4-2. SOUND LEVEL
PLFY-P-NBMU-E
* Measured in anechoic room.
4-3. NC CURVES
5 ft (1.5m)
Measurement location
PLFY-P12NBMU-E PLFY-P12NBMU-ER1
PLFY-P15NBMU-E PLFY-P15NBMU-ER1
PLFY-P18NBMU-E PLFY-P18NBMU-ER1
PLFY-P24NBMU-E PLFY-P24NBMU-ER1
PLFY-P30NBMU-E PLFY-P30NBMU-ER1
PLFY-P36NBMU-E PLFY-P36NBMU-ER1
Sound level at anechoic room : Low-
Sound level dB (A)
27-28-29-31
27-28-30-31
28-29-30-32
28-30-32-34
30-32-35-37
35-38-41-43
Mid2-Mid1-High
PLFY-P12NBMU-E PLFY-P12NBMU-ER1
External static pressure : 0Pa
PLFY-P15NBMU-E PLFY-P15NBMU-ER1
External static pressure : 0Pa
PLFY-P18NBMU-E PLFY-P18NBMU-ER1
External static pressure : 0Pa
Power source : 208,230V, 60Hz Power source : 208,230V, 60Hz Power source : 208,230V, 60Hz
High 60Hz
70.0
65.0
60.0
55.0
50.0
45.0
40.0
35.0
30.0
25.0
20.0 Approximate minimum
audible limit on
15.0 continuous noise
Octave band pressure level (dB) 0dB=20Pa
10.0
63 125 250 500 1k 2k 4k 8k
Octave band center frequencies (Hz)
Low 60Hz
PLFY-P24NBMU-E PLFY-P24NBMU-ER1
External static pressure : 0Pa Power source : 208,230V, 60Hz Power source : 208,230V, 60Hz
High 60Hz
70.0
65.0
60.0
55.0
50.0
45.0
40.0
35.0
30.0
25.0
20.0
Approximate minimum audible limit on
15.0
continuous noise
Octave band pressure level (dB) 0dB=20Pa
10.0
63 125 250 500 1k 2k 4k 8k
Octave band center frequencies (Hz)
Low 60Hz
Middle1 60Hz Middle2 60Hz
Middle1 60Hz Middle2 60Hz
70.0
65.0
NC-60
NC-50
NC-40
NC-30
NC-20
60.0
55.0
50.0
45.0
40.0
35.0
30.0
25.0
20.0 Approximate minimum
audible limit on
15.0 continuous noise
Octave band pressure level (dB) 0dB=20Pa
10.0
63 125 250 500 1k 2k 4k 8k
Octave band center frequencies (Hz)
PLFY-P30NBMU-E PLFY-P30NBMU-ER1
External static pressure : 0Pa Power source : 208,230V, 60Hz
70.0
65.0
NC-60
NC-50
NC-40
NC-30
NC-20
60.0
55.0
50.0
45.0
40.0
35.0
30.0
25.0
20.0
Approximate minimum audible limit on
15.0
continuous noise
Octave band pressure level (dB) 0dB=20Pa
10.0
63 125 250 500 1k 2k 4k 8k
Octave band center frequencies (Hz)
High 60Hz Low 60Hz
High 60Hz Low 60Hz
Middle1 60Hz Middle2 60Hz
Middle1 60Hz Middle2 60Hz
70.0
65.0
NC-60
NC-50
NC-40
NC-30
NC-20
60.0
55.0
50.0
45.0
40.0
35.0
30.0
25.0
20.0 Approximate minimum
audible limit on
15.0 continuous noise
Octave band pressure level (dB) 0dB=20Pa
10.0
63 125 250 500 1k 2k 4k 8k
Octave band center frequencies (Hz)
PLFY-P36NBMU-E PLFY-P36NBMU-ER1
External static pressure : 0Pa
70.0
65.0
NC-60
NC-50
NC-40
NC-30
NC-20
60.0
55.0
50.0
45.0
40.0
35.0
30.0
25.0
20.0 Approximate minimum audible limit on
15.0 continuous noise
Octave band pressure level (dB) 0dB=20Pa
10.0
63 125 250 500 1k 2k 4k 8k
Octave band center frequencies (Hz)
High 60Hz Low 60Hz
High 60Hz Low 60Hz
Middle1 60Hz Middle2 60Hz
Middle1 60Hz Middle2 60Hz
NC-60
NC-50
NC-40
NC-30
NC-20
NC-60
NC-50
NC-40
NC-30
NC-20
7
4-4. ELECTRICAL PARTS SPECIFICATIONS
Service Ref.
Parts name
Room temperature thermistor
Liquid pipe thermistor
Gas pipe thermistor
Fuse (Indoor controller board)
Fan motor
Vane motor
Drain-up mechanism
Drain float swich
Linear expansion valve
Power supply terminal block
Transmission terminal block
MA remote controller terminal block
Symbol
TH21
TH22
TH23
FUSE
MF
MV
DP
FS
LEV
TB2
TB5
TB15
PLFY-P12NBMU-E
PLFY-P12NBMU-ER1
DC12V Stepping motor drive port dimension :3.2 (0~2000pulse)
PLFY-P15NBMU-E
PLFY-P15NBMU-ER1
Resistance 30"F/15.8k, 50"F/9.6k, 70"F/6.0k, 80"F/4.8k, 90"F/3.9k, 100"F/3.2k
Resistance 30"F/15.8k, 50"F/9.6k, 70"F/6.0k, 80"F/4.8k, 90"F/3.9k, 100"F/3.2k
Resistance 30"F/15.8k, 50"F/9.6k, 70"F/6.0k, 80"F/4.8k, 90"F/3.9k, 100"F/3.2k
PLFY-P18NBMU-E
PLFY-P18NBMU-ER1
8-pole OUTPUT 50W
EDM-40YGME
PLFY-P24NBMU-E
PLFY-P24NBMU-ER1
250V 6.3A
MSBPC20M04
DC12V 300
PLD-12230ME-1
INPUT 12/10.8W 241/Hr
Open/short detection
(L1, L2, GR) 330V 30A
(M1, M2, S) 250V 20A
(1, 2) 250V 10A
/phase
PLFY-P30NBMU-E
PLFY-P30NBMU-ER1
DC12V Stepping motor drive port
dimension :
PLFY-P36NBMU-E PLFY-P36NBMU-ER1
8-pole OUTPUT,
5.2
(0~2000pulse)
EDM-80YGME
120W
8
5
4-WAY AIR FLOW SYSTEM
5-1. PLACEMENT OF THE AIR OUTLETS
• For this grille, the blowout direction comes in 11 patterns. Also, by setting the remote controller to the appropriate settings, you can adjust the air flow and speed. Select the settings from Table1 according to the location in which you want to install the unit.
1) Decide on the pattern of the airflow direction.
4-direction<Table 1> 3-direction 2-direction
Pattern 1 Initial setting Pattern 4 One air outlet
fully closed
Pattern 6 2 air outlet
fully closed
pattern
Blowout direction
Note: For 3 and 2-direction settings, please use the air outlet shutter plate (option).
2) According to the number of air outlets and height of the ceiling to install the unit, be sure to set up the switches (SWA, SWB) on the address board to the appropriate setting.
• Correspondence of ceiling heights to numbers of air outlets
SWB
SWA
2
3
3
ON OFF
12345678910
SW12
0
1
9
2
8
3
7
4
6
5
(10ths DIGIT)
SW1
SW11
0
9
8
7
6
(1s DIGIT)
2 1
1
5
SWC
2
3
4
4
CN82
SW14
E
D
C
B
(BRANCH No.)
CN43
0
1
F
A
9
2
3
4
5
6
7
8
./
.
PLFY-P12·P15·P18·P24·P30NBMU-E(R1)
Silent
2.5m, 8.2ft
2.7m, 8.9ft
3.0m, 9.8ft
Standard
2.7m, 8.9ft
3.0m, 9.8ft
3.3m, 10.8ft
SWB
4 direction
3 direction
2 direction
SWA
PLFY-P36NBMU-E(R1)
Silent
2.7m, 8.9ft
3.0m, 9.8ft
3.3m, 10.8ft
Standard
3.2m, 10.5ft
3.6m, 11.8ft
4.0m, 13.1ft
SWB
4 direction
3 direction
2 direction
SWA
High ceiling
3.5m, 11.5ft
3.5m, 11.5ft
3.5m, 11.5ft
High ceiling
4.5m, 14.8ft
4.5m, 14.8ft
4.5m, 14.8ft
9
5-2. BRANCH DUCT HOLE AND FRESH AIR INTAKE HOLE
At the time of installation, use the duct holes (cut out) located at the positions shown in following diagram, as and when required.
• A fresh air intake hole for the optional multi function casement can also be made.
Note: The figures marked with * in the drawing below represent the dimensions of the main unit excluding those of the optional multi function casement. When installing the optional multi function casement, add 5-5/16” (135 mm) to the dimensions marked on the figure. When installing the branch ducts, be sure to insulate adequately. Otherwise, condensation and dripping may occur.
Unit : inch(mm)
Fresh air intake hole
Refrigerant pipe
Indoor unit
Branch duct hole
Drain pipe
:6-7/8 (:175) burring hole pitch
Branch duct hole diagram (view from either side)
Fresh air intake hole diagram
3-:1/8 (:2.8) burring hole
120
(*158)
6-7/32
3-17/32
3-15/16
3-15/16
(90)
3-17/32
(90)
70
(90)
(100)
13-25/32 (350)
:4-29/32 (:125) burring hole pitch
120
3-:15/16 (:100) cut out hole
Ceiling
3-15/16 (100)
5-1/8 (130)
*6-3/32 (155)
*6-9/16 (167)
14-:1/8 (:2.8) burring hole
:5-29/32 (:150) cut out hole
5-3. OPERATION IN CONJUNCTION WITH
DUCT FAN (Booster fan)
• Whenever the indoor unit is operating, the duct fan also operates.
(1) Connect the optional multiple remote controller adapter
(PAC-SA88HA-E) to the connector CN51 on the indoor controller board.
(2) Drive the relay after connecting the 12V DC relay
between the Yellow and Orange connector lines.
MB: Electromagnetic switch power relay for duct fan.
X: Auxiliary relay (For DC 12V, coil rating: 1.0W or smaller)
CN51 on indoor controller board
Indoor controller board
Multiple remote controller adapter PAC-SA88HA-E
Connector (5P)
Indoor unit side
10
5
1
CN51
Be sure to secure insulation
Green
CN51
material by tape, etc.
Red
Brown
Multiple remote controller adapter PAC-SA88HA-E
Yellow
Orange
~
MB
Installation at site
Be sure to secure insulation material by tape, etc.
Distance between indoor controller board and relay must be within 10m (33ft).
5-4. FRESH AIR INTAKE AMOUNT & STATIC PRESSURE CHARACTERISTICS 1 PLFY-P12 · P18 · P24 · P30NBMU-E(R1)
Multifunction casement + High efficiency filter Multifunction casement + Standard filter
50(20)
)]
-2
0
-50(-20)
-100(-40)
-150(-60)
Static pressure [Pa(in.W.G.%10
-200(-80) 012
Taking air into the unit
50(20)
)]
-2
0
-50(-20)
-100(-40)
-150(-60)
Static pressure [Pa(in.W.G.%10
-200(-80) 012
50 100 150 200
50 100 150 200
Air flow rate
Air flow rate
2 PLFY-P36NBMU-E(R1)
2 - inlet
1 - inlet
[CMM]
345
3456
6
[CFM]
[CMM]
[CFM]
50(20)
)]
-2
0
-50(-20)
-100(-40)
-150(-60)
Static pressure [Pa(in.W.G.%10
-200(-80) 012
How to read curves
Curve in the
1
graphs.
0
Q
2
Q
3
Q
Qa
2 - inlet
1 - inlet
50 100 150 200
Duct characteristics at site
A
C
B
345
Q…Designed amount of fresh air intake
A…Static pressure loss of fresh air
intake duct system with air flow amount Q <Pa (in.W.G.o10-2)>
B…Forced static pressure at air condi-
tioner inlet with air flow amount Q
<Pa (in.W.G.o10
A
EC
C…Static pressure of booster fan with air
flow amount Q <Pa (in.W.G.o10
D…Static pressure loss increase amount
of fresh air intake duct system for air flow amount Q <Pa (in.W.G.o10
E…Static pressure of indoor unit with air
flow amount Q <Pa (in.W.G.o10
AD
Qa…Estimated amount of fresh air
intake without D <CMM (CFM)>
<CMM (CFM)>
Multifunction casement + Standard filter Multifunction casement + High efficiency filter
6
[CMM]
[CFM]
-2
)>
-2
)>
-2
)>
-2
)>
50(20)
)]
-2
0 0
-50(-20)
-100(-40)
-150(-60)
Static pressure [Pa(in.W.G.%10
-200(-80) 02
50 100 150 200 250
Taking air into the unit
50(20)
)]
-2
0
-50(-20)
-100(-40)
-150(-60)
Static pressure [Pa(in.W.G.%10
-200(-80) 02
50 100 150 200 250
50(20)
)]
-2
-50(-20)
2 - inlet
1 - inlet
48
Air flow rate
48
Air flow rate
6
6
[CMM]
[CFM]
[CMM]
[CFM]
-100(-40)
-150(-60)
Static pressure [Pa(in.W.G.%10
-200(-80)
1 - inlet
02
50 100 150 200 250
48
Air flow rate
2 - inlet
6
[CMM]
[CFM]
11
6
OUTLINES AND DIMENSIONS
PLFY-P12NBMU-E(R1) PLFY-P15NBMU-E(R1) PLFY-P18NBMU-E(R1) Unit : inch (mm) PLFY-P24NBMU-E(R1) PLFY-P30NBMU-E(R1) PLFY-P36NBMU-E(R1)
25/32~1-25/32(20~45)
Fresh air intake hole
(160)
6-5/16
Branch duct hole
33-1/16(840)
(90)
3-17/32
(150)
C
5-29/32
Suspension bolt M10 or W3/8
1
6-16/5
(160)
For MA-Remote controller terminal block
D
7-3/8
(187.5)
(60)
2-3/8
Ceiling hole
33-27/32 to 35-13/16(860~910) 25/32 to 1-25/32(20~45)
31-7/8(810)
Suspension bolt pitch
Indoor unit/Outdoor unit connecting terminal block
For wiring replacement kit terminal block
(840)
33-1/16
(284)
14-27/3211-3/16
(377)
6-5/16
(160)
Suspension bolt pitch
(160)
(24)
15/16
6-5/16
Drain pipe connected to VP-25
(7.5)
(5/16)(5/16)
+35
-5
(605 )
-3/16
+1-3/8
24-13/32
23-13/16
(7.5)
(620)
1-25/32
25/32 to
Ceiling hole
33-27/32 to 35-13/16(860~910)25/32
to 1-25/32
Detail connecting of branch duct (Both aspects)
(20~45)
Branch duct hole
(20~45)
Connected the attached flexible pipe or socket.
3-17/32
13-25/32
(350)
3-15/16
(100)
3-17/32
Cut out hole
ø5-29/32(ø150)
Cut out hole
(90)
(100)
3-15/16
14-ø1/8(14-ø2.8)
Burring hole
(130)
5-1/8
3-15/16 (90)
70
(ø175)
6-7/8
Burring hole pitch
(100)
Detail drawing of fresh air intake hole
Burring hole 3-ø1/8(3-ø2.8)
)(
120
Burring hole pitch
ø4-29/32(ø125)
+6-9/16(167)
+6-3/32(155)
2
(170)
+5-1/2
+6-11/16
Suspension bolt lower edge
(950)
37-3/8
Air intake grille
Ceiling
Grille
Entire periphery
(140)
1-31/32 to 2-3/4
(500)
19-11/16
Air outlet hole
(83)
3-17/64
(36)
Corner pocket
1-27/64
Min.19-11/16(500)
(50~70)
M
M
Indoor unit
23-1/2
Air intake hole
19-11/16 Air outlet hole
37-3/8
Min.94-1/2(2400) from floor
Floor
(597)
(500)
(950)
M
3-17/64
+4-1/8(105)
Ceiling
Grille
Drain hole Drain pump clean hole and Drain emergency drainage hole
M
1-27/64
(83)
A
+B
(190)
(156)
+7-15/32
+6-9/64
+3/16
0
+5
0
1-3/8
(17 )
11/16
Auto vane (Air outlet)
(597)
23-1/2
Air intake hole
Vane motor
(36)
Models
PLFY-P12NBMU-E PLFY-P15NBMU-E PLFY-P18NBMU-ER1
PLFY-P18NBMU-E
PLFY-P24NBMU-E PLFY-P30NBMU-E
PLFY-P36NBMU-E
PLFY-P36NBMU-ER1
Keep 25/64(10) to 19/32(15) between unit ceiling and ceiling slab.
In case of standard grille
(35)
Note:
1. Please choose the Grille from a standard grille.
2. As for drain pipe, please use VP-25 (O.D. :1-1/4(:32) PVC TUBE.) Drain pump is included. Max. lifting height is 70-7/18 (850mm) from the ceiling.
3. As for suspension bolt, please use M10 or W3/8. (Procured at local site)
4. Electrical box may be removed for the service purpose. Make sure to slack the electrical wire little bit for control/power wires connection.
5. The height of the indoor unit is able to be adjusted with the grille attached.
6. For the installation of the optional high efficiency filter or optional multi-functional casement.
1) Add 5-5/16"(135mm) to the dimensions marked on the figure.
2) The optional high efficiency filter becomes optional multi-functional casement and concomitant use.
7. When installing the branch ducts, be sure to insulate adequately. Otherwise condensation and dripping may occur. (It becomes the cause of dew drops/water dew.)
8. As for necessary installation/service space, please refer to the left figure.

Refrigerant pipe
···ø6.35 Flared connection
···1/4F Refrigerant pipe
ø6.35 / ø9.52 Flared connection 1/4F / 3/8F (compatible)
Refrigerant pipe
···ø9.52 Flared connection
···3/8F
Refrigerant pipe ···ø12.7 Flared connection ···1/2F
Refrigerant pipe ø12.7 / ø15.88 Flared connection 1/2F / 5/8F (compatible)
Refrigerant pipe ···ø15.88 Flared connection ···5/8F
Refrigerant pipe ø15.88 / ø19.05 Flared connection 5/8F / 3/4F (compatible)
Refrigerant pipe ···ø15.88 Flared connection ···5/8F
6-7/32
(+158)
In case of wireless remote controller
Emergency operation switch <Cooling> and Emergency Up/Down switch <Up>
Receiver
Operation lamp
9-1/2
11-1/16
(281)
Cut out hole
120
ø3-15/16(ø100)
Ceiling
Emergency operation switch <Heating> and Emegency Up/Down switch <Down>
DEFROST/STAND BY lamp
DCBA
3-5/32
3-11/32
(85)
2-29/32
(74)(80)(258)(241)
3-1/32
(77)
10-3/16
11-3/4
(298)
12
7
WIRING DIAGRAM
PLFY-P12NBMU-E(R1) PLFY-P15NBMU-E(R1) PLFY-P18NBMU-E(R1) PLFY-P24NBMU-E(R1) PLFY-P30NBMU-E(R1) PLFY-P36NBMU-E(R1)
<+1>
MODELS
P12
P15
P18
4
81 41
ADDRESS
CN42 (RED)
91
LIQUID/PIPE
CN44
(WHT)
194
BZ
LED2
LED1
RU
SW2 SW2
ON
OFF
123456
ON
OFF
123456
ON
OFF
123456
SW3
ON
OFF
12345678910 12345612345
CN24
(YLW)
12 12
FLOAT SW
CN4F
(WHT)
14FS12
tt
TH23TH22
SWE
ONOFF
13
CN3G
(BLK)
MODELS
ON
P24
OFF
123456
ON
P30
OFF
123456
ON
P36
OFF
123456
See fig:+1
SW4
SW2
ON OFF
DC311~339V RECTIFICATION
CN25
(WHT)
LED1
INTAKE
CN27
CN20
(RED)
(RED)
12
t
+Be sure to turn off the source power and then disconnect fan motor connector.
TH21
(Failure to do so will cause trouble in Fan motor)
(WHT)
714
FAN
CNMF
MS
3~
MF
GRILLE
MV
MVMVMV
MMMM
5555
I-SEE SENSOR MOTOR
CN6Y (RED)
16
I-SEE SENSOR
CN4Y
(WHT)
14
16
CN52
(GRN)
54
I-SEE
M
SENSOR
I-SEE SENSOR CORNER PANEL (OPTION PART)
MT
WHT
A.B
1011121314151617181920
MA REMOCON
1
LEV CN60 (WHT)
6
BLU
RED
YLW
ORN
M
LEV
ON
OFF
12345678910
10ths DIGIT 1s DIGIT
VANE
(WHT)
CN3A (BLU)
3
CN51
(WHT)
BRN
SW1
SW12 SW11
0
0
1
9
9
2
8
8
3
7
7
4
6
6
5
CN32
(WHT)
13
123456789
CNV
LED2
CN41
(WHT)
141515
TB15
BLU BLU
3 2 1
SWC
1
2
3
4
5
Pair No.
TO MA-REMOTE
1
CONTROLLER
2
DC8.7-13V
(RED)
ADDRESS
CN43
SWBSWA
2 3 4
SW14
F
E
D
C
B
A
BRANCH
No.
J41J42
4
1
ADDRESS
0
1
2
3
4
5
6
7
8
9
8
W.B
8
(RED)
CN82
1
ADDRESS
CN81
(RED)
WIRELESS
CN90 (WHT)
CNB
SW1
SW2
NOTES:
1.At servicing for outdoor unit, always follow the wiring diagram of outdoor unit.
2.In case of using MA-Remote controller, please connect to TB15. (Remote controller wire is non-polar.)
3.In case of using M-NET, please connect to TB5. (Transmission line is non-polar.)
4.Symbol [S] of TB5 is the shield wire connection.
5.Symbols used in wiring diagram above are, : terminal block, : connecter.
6.The setting of the SW2 dip switches differs in the capacity. For the detail, refer to fig.<+1>. +2.Use copper supply wires.
21
M-NET CN2M (BLU)
BLU BLU
ZNR01
D.U.M
CNP
(BLU)
TB5
TO OUTDOOR UNIT BC CONTROLLER
M1
REMOTE CONTROLLER
M2
DC24-30V
S
(SHIELD)
ZNR02
FUSE
U
X1
31
M
1~
DP
DSA
135
U
RED
BLU
GRN/YLW
CND
CNAC
(WHT)
31
POWER SUPPLY ~/N 208-230V 60Hz
+2
TB2
L1 L2
GR
I.B
BREAKER (16A)
FUSE(16A)
PULL BOX
TO NEXT INDOOR UNIT
[LEGEND]
SYMBOL
I. B
INDOOR CONTROLLER BOARD
CN27
CONNECTOR DAMPER CN32 CN51 CN52
SURGE ABSORBER
DSA FUSE
FUSE (T6.3AL250V)
POWER SUPPLY (I. B)
LED1 LED2
POWER SUPPLY (I. B) SW2
SWITCH SW3 SW4 SWE
AUX. RELAY
X1
VARISTOR
ZNR01,02
REMOTE SWITCH CENTRALLY CONTROL REMOTE INDICATION
CAPACITY CODE MODE SELECTION MODEL SELECTION DRAIN-UP MACHINE (TEST MODE) DRAIN WATER LIFTING-UP MACH.
LED on indoor board for service
Mark
LED1
LED2
Meaning Function
Main power supply
Power supply for MA-Remote controller
Main Power supply (Indoor unit:208-230V) power on lamp is lit.
Power supply for MA-Remote controller on lamp is lit.
DP FS LEV MF MV TB2 TB5 TB15 TH21
TH22
TH23
DRAIN-UP MACHINE DRAIN FLOAT SWITCH LINEAR EXPANSION VALVE FAN MOTOR VANE MOTOR TERMINAL BLOCK
THERMISTOR
POWER SUPPLY TRANSMISSION MA-REMOTE CONTROLLER ROOM TEMP. DETECTION (0/15k, 25/5.4k) PIPE TEMP. DETECTION / LIQUID (0/15k, 25/5.4k) PIPE TEMP. DETECTION / GAS (0/15k, 25/5.4k)
SYMBOLNAME SYMBOL NAME NAME
A. B
OPTION PART
ADDRESS BOARD
SWA
SWITCH
SWB
SWC SW1 SW11 SW12 SW14
PCB FOR WIRELESS REMOTE CONTROLLER
W.B
BZ
BUZZER
LED1
LED (OPERATION INDICATION: GREEN)
LED2
LED (PREPARATION FOR HEATING: ORANGE) RECEIVING UNIT
RU SW1
EMERGENCY OPERATION (HEAT/DOWN)
SW2
EMERGENCY OPERATION (COOL/UP)
CEILING HEIGHT SELECTOR DISCHARGE OUTLET NUMBER SELECTOR OPTION SELECTOR MODE SELECTION ADDRESS SETTING 1s DIGIT ADDRESS SETTING 10ths DIGIT BRANCH NO.
13
8 REFRIGERANT SYSTEM DIAGRAM
PLFY-P12NBMU-E(R1) PLFY-P15NBMU-E(R1) PLFY-P18NBMU-E(R1) PLFY-P24NBMU-E(R1) PLFY-P30NBMU-E(R1) PLFY-P36NBMU-E(R1)
Refrigerant flow in cooling Refrigerant flow in heating
Item
Gas pipe
Liquid pipe
Heat exchanger
Room temparature thermistor TH21
Model
PLFY-P12/P15NBMU-E
PLFY-P12/P15NBMU-ER1
:12.7 (1/2'')
:6.35 (1/4'')
Gas pipe thermistor TH23
Liquid pipe thermistor TH22
Linear expansion valve
Strainer1 (#50mesh) Strainer2 (#100mesh)
PLFY-P18NBMU-E
PLFY-P18NBMU-ER1
:12.7 (1/2'')/:15.88 (5/8'')
:6.35 (1/4'')/:9.52 (3/8'')
Strainer (#100mesh)
Gas pipe
Flare connection
Liquid pipe
Strainer (#100mesh)
PLFY-P24/P30NBMU-E
PLFY-P24/P30NBMU-ER1
:15.88 (5/8'')
:9.52 (3/8'')
Unit : mm (inch)
PLFY-P36NBMU-E
PLFY-P36NBMU-ER1
:15.88 (5/8'')/:19.05 (3/4'')
:9.52 (3/8'')
14
MICROPROCESSOR CONTROL9
INDOOR UNIT CONTROL 9-1. COOL OPERATION
TIME SUN MON TUE WED THU FRI SAT TIMER
AFTER
ûF ûC
ONLY1Hr.
TEMP.
MENU
ON/OFF
MONITOR/SET
BACK DAY
PAR-21MAA
CLOCK
Control modes
1. Thermoregulating function
<How to operate>
ERROR CODE
ûF ûC
ON
OFFHrAFTER
FUNCTION
FILTER
WEEKLY
SIMPLE
AUTO OFF
ON/OFF
1 Press POWER ON/OFF button. 2 Press the operation MODE button to display COOL. 3 Press the TEMP. button to set the desired temperature.
NOTE: The set temperature changes 2°F when the or button is
pressed one time. Cooling 67 to 87°F
FILTER
CHECK
TEST
OPERATION
CLEAR
Control details
1-1. Thermoregulating function (Function to prevent restarting for 3 minutes)
• Room temperature desired temperature + 2°F
• Room temperature desired temperature
···Thermo ON
···Thermo OFF
1-2. Anti-freezing control
Detected condition : When the liquid pipe temp. (TH22) is 32°F or less in 16
minutes from compressors start up, anti-freezing control
starts and the thermo OFF.
Released condition : The timer which prevents reactivating is set for 3 minutes,
and anti-freezing control is cancelled when any one of the
following conditions is satisfied.
 Liquid pipe temp. (TH22) turns 50°F or above.
 The condition of the thermo OFF has become complete
by thermoregulating, etc.
 The operation modes became mode other than COOL.
The operation stopped.
Remarks
2. Fan
By the remote controller setting (switch of 4 speeds+Auto)
Type
4 speeds + Auto type
[Low], [Med2], [Med1], [High], [Auto]
Fan speed notch
When [Auto] is set, fan speed is changed depending on the value of:
Room temperature - Desired temperature
To be continued on the next page.
15
From the preceding page.
Control modes
3. Drain pump
Control details
3-1. Drain pump control
•Always drain pump ON during the COOL and DRY mode operation. (Regardless of the thermo ON/OFF)
•When the operation mode has changed from the COOL or DRY to the others (including Stop), OFF the control after the drain pump ON for 3 minutes.
Float switch control
• Float switch control judges whether the sensor is in the air or in the water by turning the float switch ON/OFF. In the water: Detected that the float switch is ON for 15 seconds. In the air : Detected that the float switch is OFF for 15 seconds.
Float SW
ON
OFF
15sec. 15sec. 15sec. 1min.30sec. 1min.30sec.
In the water In the air In the water Error
postponement
Drain pump
abnormal
Remarks
4. Vane
(up/down vane change)
(1) Initial setting: Start at COOL mode and horizontal vane. (2) Vane position:
Horizontal Downward A Downward B Downward CDownward DSwingAuto
(3) Restriction of the downward vane setting
When setting the downward vane A, B, C or D in [Med1], [Med2] or [Low] of the
fan speed notch, the vane changes to horizontal position after 1 hour have passed.
· "ONLY 1 Hr" appears on the wired remote controller.
16
9-2. DRY OPERATION
TIME SUN MON TUE WED THU FRI SAT TIMER
AFTER
ûF ûC
ONLY1Hr.
TEMP.
MENU
ON/OFF
BACK DAY
MONITOR/SET
PAR-21MAA
CLOCK
Control modes
1. Thermo regulating function
<How to operate>
ERROR CODE
ON
OFFHrAFTER
ûF ûC
FUNCTION
FILTER
WEEKLY
SIMPLE
AUTO OFF
ON/OFF
1 Press POWER ON/OFF button. 2 Press the operation MODE button to display DRY. 3 Press the TEMP. button to set the desired temperature.
NOTE: The set temperature changes 2°F when the or button is
pressed one time. Dry 67 to 87°F
FILTER
CHECK
TEST
OPERATION
CLEAR
Control details
1-1. Thermo regulating function (Function to prevent restarting for 3 minutes) Setting the Dry thermo by the thermo regulating signal and the room temperature (TH21). Dry thermo ON Room temperature  desired temperature + 2°F Dry thermo OFF Room temperature desired temperature
Room temperature
Over 64F
Less than 64F
3 min. passed since starting operation
Thermo regulating signal
ON
Room temperature (T1)
83°F > T1 79°F
79°F > T1 75°F
75°F > T1
OFF
Unconditional
Dry thermo OFF
T1 83°F
Dry thermo
ON
time (min)
93
7
5
33
3
Remarks
Dry thermo
OFF
time (min)
3
3
10
2. Fan
3. Drain pump
4. Vane (up/down vane change)
1-2. Frozen prevention control No control function
Indoor fan operation controlled depends on the compressor conditions.
Dry thermo
ON
OFF
Excluding the following
Room temp. < 64°F
Fan speed notch
[Low]
Stop
[Low]
Note: Remote controller setting is not acceptable.
Same control as COOL operation
Same control as COOL operation
17
9-3. FAN OPERATION
TIME SUN MON TUE WED THU FRI SAT
ûF ûC
TEMP.
MENU
MONITOR/SET
BACK DAY
PAR-21MAA
CLOCK
TIMER
AFTER
ONLY1Hr.
ON/OFF
ERROR CODE
ûF ûC
OPERATION
ON
OFFHrAFTER
FUNCTION
FILTER
WEEKLY
SIMPLE
AUTO OFF
ON/OFF
FILTER
CHECK
CLEAR
<How to operate>
1 Press POWER ON/OFF button. 2 Press the operation MODE button to display FAN.
TEST
Control modes
1. Fan
2. Drain pump
Control details
Set by remote controller.
Type
4 speeds + Auto type [Low], [Med2], [Med1], [High], [Auto]
Fan speed notch
When [Auto] is set, fan speed becomes [Low].
2-1. Drain pump control The drain pump turns ON for the specified amount of time when any of the following conditions is met: ON for 3 minutes after the operation mode is switched from COOL or DRY to another operation mode (FAN). ON for 6 minutes after the float switch is submerged in the water when the float swich control judges the sensor is in the water.
2-2. Float switch control
• Float switch control judges whether the sensor is in the air or in the water by turning the float switch ON/OFF. In the water : Detected that the float switch is ON for 15 seconds. In the air : Detected that the float switch is OFF for 15 seconds.
Remarks
· Same control as COOL operation
3. Vane (up/down vane change)
Same as the control performed during the COOL operation, but with no restriction on the vane's downward blow setting
18
9-4. HEAT OPERATION
TIME SUN MON TUE WED THU FRI SAT
ûF ûC
TEMP.
MENU
BACK DAY
MONITOR/SET
PAR-21MAA
CLOCK
TIMER
AFTER
ONLY1Hr.
ON/OFF
ERROR CODE
ûF ûC
OPERATION
ON
OFFHrAFTER
ON/OFF
FUNCTION
FILTER
WEEKLY
SIMPLE
AUTO OFF
FILTER
CHECK
CLEAR
TEST
<How to operate>
1 Press POWER ON/OFF button. 2 Press the operation MODE button to display HEAT. 3 Press the TEMP. button to set the desired temperature.
NOTE: The set temperature changes 2°F when the or button is
pressed one time. Heating 63 to 83°F.
<Display in HEAT operation> [DEFROST]
The [DEFROST] symbol is only displayed during the defrost operation.
[STANDBY]
The [STANDBY] symbol is only displayed during the hot adjust mode.
Control modes
1.
Thermoregulating
function
2. Fan
Control details
1-1. Thermoregulating function (Function to prevent restarting for 3 minutes)
Room temperature desired temperature -2°F ···Thermo ON
Room temperature  desired temperature ···Thermo OFF
By the remote controller setting (switch of 4 speeds+Auto)
Type
4 speeds + Auto type
[Low], [Med2], [Med1], [High], [Auto]
Fan speed notch
When [Auto] is set, fan speed is changed depending on the value of:
Desired temperature - Room temperature Give priority to under-mentioned controlled mode 2-1. Hot adjust mode 2-2. Preheating exclusion mode 2-3. Thermo OFF mode (When the compressor off by the thermoregulating) 2-4. Cool air prevention mode (Defrosting mode)
2-1. Hot adjust mode The fan controller becomes the hot adjuster mode for the following conditions.
When starting the HEAT operation
When the thermoregulating function changes from OFF to ON.
When release the HEAT defrosting operation
Hot adjust mode *1
Set fan speed by the remote controller
[Low]
[Extra Low]
Remarks
*1
"STAND BY" will be displayed during the hot adjust mode.
ACB
A: Hot adjust mode starts. B: 5 minutes have passed since the condition A or the indoor liquid pipe temperature turned 95°F or more. C: 2 minutes have passed since the condition A. (Terminating the hot adjust mode)
2-2. Preheating exclusion mode When the condition changes the auxiliary heater ON to OFF (thermoregulating or operation stop, etc), the indoor fan operates in [Low] mode for 1 minute.
To be continued on the next page.
19
· This control is same for the model without auxiliary heater.
From the preceding page
Control modes
2. Fan
3. Drain pump
Control details
2-3. Thermo OFF mode When the thermoregulating function changes to OFF, the indoor fan operates in [Extra low].
2-4. Heat defrosting mode The indoor fan stops.
3-1. Drain pump control The drain pump turns ON for the specified amount of time when any of the following conditions is met: ON for 3 minutes after the operation mode is switched from COOL or DRY to another operation mode (FAN). ON for 6 minutes after the float switch is submerged in the water when the float swich control judges the sensor is in the water.
3-2. Float switch control
• Float switch control judges whether the sensor is in the air or in the water by turning the float switch ON/OFF. In the water: Detected that the float switch is ON for 15 seconds. In the air : Detected that the float switch is OFF for 15 seconds.
Remarks
· Same control as COOL operation
4. Vane control (Up/down vane change)
(1) Initial setting: OFF HEAT···[last setting] When the last setting is [Swing] ··· [Downward D] When changing the mode from exception of HEAT to HEAT operation
···[Downward D] (2) Vane position:
Horizontal Downward A Downward B Downward CDownward DSwingAuto
(3) Restriction of vane position  The vane is horizontally fixed for the following modes. (The control by the remote controller is temporally invalidated and control by the unit.)
•Thermo OFF
•Hot adjust [Extra low] mode
•Heat defrost mode
20
9-5. AUTO OPERATION [AUTOMATIC COOL/HEAT CHANGE OVER OPERATION]
<How to operate>
1 Press POWER ON/OFF button. 2 Press the operation MODE button to display AUTO. 3 Press the TEMP. button to set the desired temperature.
NOTE: The set temperature changes 2°F when the or button is
pressed one time. Automatic 67 to 83°F
ûF ûC
TEMP.
MENU
MONITOR/SET
BACK DAY
PAR-21MAA
TIME SUN MON TUE WED THU FRI SAT TIMER
AFTER
ERROR CODE
ûF ûC
ONLY1Hr.
ON/OFF
CLOCK
OPERATION
ON
OFFHrAFTER
FUNCTION
FILTER
WEEKLY
SIMPLE
AUTO OFF
ON/OFF
FILTER
CHECK
CLEAR
TEST
Control modes
1. Initial value of operation mode
2. Mode change
HEAT mode for room temperature < Desired temperature COOL mode for room temperature Desired temperature
(1) HEAT mode COOL mode
Control details
Room temperature Desired temperature + 3°F. or 3 min. has passed (2) COOL mode HEAT mode Room temperature  Desired temperature - 3°F. or 3 min. has passed
3. COOL mode
4. HEAT mode
Same control as cool operation
Same control as heat operation
9-6. WHEN UNIT IS STOPPED CONTROL MODE
Control modes
1. Drain pump
1-1. Drain pump control The drain pump turns ON for the specified amount of time when any of the following conditions is met: ON for 3 minutes after the operation mode is switched from COOL or DRY to another operation mode (FAN). ON for 6 minutes after the float switch is submerged in the water when the float swich control judges the sensor is in the water.
Control details
Remarks
Remarks
1-2. Float switch control
• Float switch control judges whether the sensor is in the air or in the water by turning the float switch ON/OFF. In the water : Detected that the float switch is ON for 15 seconds. In the air : Detected that the float switch is OFF for 15 seconds.
21
· Same control as COOL operation
10
TROUBLESHOOTING
10-1. HOW TO CHECK THE PARTS PLFY-P12/15/18/24/30/36NBMU-E PLFY-P12/15/18/24/30/36NBMU-ER1
Parts name Check points
Room temperature thermistor (TH21) Liquid pipe thermistor (TH22) Gas pipe thermistor (TH23)
Disconnect the connector then measure the resistance using a tester. (At the ambient temperature 50"F~86"F)
Normal
4.3k~9.6k
Abnormal
Open or short
(Refer to the next page for a detail.)
Vane motor (MV)
White
Orange
Red
Blue
Yellow
Drain pump (DP)
YLW
1
3
YLW
Drain float switch (FS)
Moving part
1
2
3
4
i-see sensor (Option)
Measure the resistance between the terminals using a tester. (At the ambient temperature of 68°F~86°F)
Connector
Normal
Red - Yellow (-, -, -, -) Red - Blue (-, -, -, -) Red - Orange (-, -, -, -)
300
Red - White (-, -, -, -)
Measure the resistance between the terminals using a tester. (Winding temperature 68°F)
Normal Abnormal
290 Open or short
Measure the resistance between the terminals using a tester.
State of moving part Abnormal
UP
DOWN Other than open
Normal
Short Other than short
Open
Turn on the indoor unit with the black plastic tape on the outside of i-see sensor controller board. With electricity being turned on, measure the power voltage between connectors with tester. i-see sensor rotates then pull out the connector of motor for i-see sensor.
Black plastic tape
Do not disassemble corner panel with i-see sensor.
Abnormal
Open or short
Switch
Magnet
Moving Part
4321
43 1
2
Blue
Black
Pink
Brown
Vane motor for i-see sensor (Option)
White
Orange
Red
Blue
Linear expansion valve (LEV)
M
White
Red
Orange
Yellow
Blue
Brown
Yellow
i-see sensor (At the ambient temperature of 50°F~104°F)
i-see sensor connector
(–)—(+)
(+)—(–) Other than the normal
Normal DC 1.857V~ 3.132V Other than the normal
DC 0.939V~ 1.506V
NOTE : Be careful of handing such a static electricity.
Measure the resistance between the terminals using a tester. (At the ambient temperature of 68°F~86°F)
Connector
Normal
Abnormal Red - Yellow Red - Blue Red - Orange
250
Open or short
Red - White
Disconnect the connector then measure the resistance valve using a tester.
Normal
White-Red Yellow-Brown Orange-Red Blue-Brown
150k$10%
22
Abnormal
Abnormal
Open or short
Refer to 8-1-2.
10-1-1. Thermistor
<Thermistor characteristic graph>
Thermistor for lower temperature
Room temperature thermistor (TH21) Liquid pipe temperature thermistor (TH22) Gas pipe temperature thermistor (TH23)
Thermistor R0=15k' ± 3%
< Thermistor for lower temperature >
50
40
30
Fixed number of B=3480 ± 2%
Rt=15exp { 3480( ) }
1
273+(t-32)/1.8
1
273
Resistance (k)
20
30_F 15.8k' 50_F 9.6k'
10
70_F 6.0k' 80_F 4.8k' 90_F 3.9k' 100_F 3.2k'
10-1-2.
1 Operation summary of the linear expansion valve
• Linear expansion valve open/close through stepping motor after receiving the pulse signal from the indoor controller board.
• Valve position can be changed in proportion to the number of pulse signals. <Connection between the indoor controller board and the linear expansion valve>
Linear expansion valve
0
0-20 20 40 60 80 100 120
Temperature (°F)
Controller board
DC12V
Linear expansion valve
4
M
6
2
5
White
1
Red
3
Orange
Blue
Brown
Yellow
Brown
Red
:4
:3
:2
:1
Blue
Orange
Yellow
White
Connector(CN60)
6
5
4
3
2
1
Drive circuit
:4
:3
:2
:1
Note : Since the number of the connector at the controller board side and the relay connector are different, follow the color of
the lead wire.
23
<Output pulse signal and the valve operation>
2
OFF
ON ON
OFF
Output
3 OFF OFF
ON ON
D
4
ON OFF OFF
ON
C
Output
(Phase)
{1 {2 {3 {4
1 ON ON
OFF OFF
2 Linear expansion valve operation
Open
Close
Closing a valve : 1 2 3 4 → 1 Opening a valve : 4 3 2 1 → 4 The output pulse shifts in above order.
Note:
• When linear expansion valve operation stops, all output phase become OFF.
• At phase interruption or when phase does not shift in order, motor does not rotate smoothly and motor will lock and vibrate.
• When the switch is turned on, 2200 pulse closing valve signal will be sent till it goes to point
A in order to define the valve position.
• When the valve moves smoothly, there is no sound or vibration occurring from the linear expansion valves, however, when the pulse number moves from
E to A or when the valve is locked,
more sound can be heard than in a normal situation.
• Sound can be detected by placing the ear against the screw driver handle while putting the screw driver tip to the linear expansion valve.
Valve position (capacity)
A
E
Close
Extra tightening (200~800 pulse)
3 Trouble shooting
Open
B
Pulse number
Operation circuit failure of the micro processor
Linear expansion valve mechanism is locked.
Short or breakage of the motor coil of the linear expansion valve
Valve does not close completely.
Wrong connection of the connector or contact failure
Outdoor unit R410A model : 1400 pulse Outdoor unit R22 model : 2000 pulse Opening a valve all the way
Symptom
Disconnect the connector on the controller board, then con-
nect LED for checking.
When power is turned on, pulse signals will output for 10
seconds. There must be some defects in the operation circuit if the LED does not light while the signals are output or keeps lighting even after the signals stop.
Motor will idle and make a ticking noise when the motor is
operated while the linear expansion valve is locked. This tick­ing sound is the sign of the abnormality.
Measure the resistance between each coil (white-red, yellow-
brown, orange-red, blue-brown) using a tester. It is normal if the resistance is in the range of 150' ±10%.
To check the linear expansion valve, operate the indoor unit
in fan mode and at the same time operate other indoor units in cooling mode, then check the pipe temperature <liquid
Thermistor (Liquid pipe)
Linear expansion valve
It is not necessary to exchange the linear expansion valve, if the leakage is small and not affecting normal operation.
Check the color of lead wire and missing terminal of the con-
nector.
Check points
6 5 4 3 2
LED1k
pipe temperature> of the indoor unit by the outdoor multi controller board operation monitor. During fan operation, linear expan­sion valve is closed completely and if there is any leaking, detecting temperature of the thermistor will go lower. If the detected temperature is much lower than the tem­perature indicated in the remote controller, it means the valve is not closed all the way.
1
Countermeasures
Exchange the indoor con­troller board at drive circuit failure.
Exchange the linear expan­sion vale.
Exchange the linear expan­sion valve.
If large amount of refriger­ant is leaked, exchange the linear expansion valve.
Disconnect the connector at the controller board, then check the continuity.
24
10-1-3. DC Fan motor (fan motor/indoor controller board)
Check method of indoor fan motor (fan motor/indoor controller board)
Notes
· High voltage is applied to the connecter (CNMF) for the fan motor. Pay attention to the service.
· Do not pull out the connector (CNMF) for the motor with the power supply on. (It causes trouble of the indoor controller board and fan motor) Self check
Conditions : The indoor fan cannot turn around.
Wiring contact check
Contact of fan motor connector (CNMF) Contact of power supply cable
Is there contact failure ?
No
Power supply check (Remove the connector (CNMF))
Measure the voltage in the indoor controller circuit
TEST POINT
: VDC (between 1 (+) and 4 (-) of the fan connector): VDC DC294~325V
Yes
Wiring recovery
board.
TEST POINT  : VCC (between 5 (+) and 4 (-) of the fan connector): VCC DC15V
Is the voltage normal?
Yes
Fan motor position sensor signal check
Turn around the fan motor more than one revolution slowly, and check the voltage TEST POINT V
FG (between 7(+) and 4(-)).
No
Does the voltage repeat DC0V and DC15V?
Yes
Replace the indoor controller board.
OK
Check the operation of fan.
NG
END
Trouble of the indoor controller board Replace the indoor controller board.
No
Trouble of the fan motor Replace the fan motor.
Yes
Check the operation of fan.
NG
Replace the indoor controller board
Replace the fan motor.
Yes
Check the operation of fan.
NG
Replace the fan motor.
OK
END
OK
END
25
10-2. FUNCTION OF DIP SWITCH
Switch Function Remarks
Pole
Operation by switch
ON OFF
Thermistor <Room temperature
SW1
Function
setting
1
detection> position
2
Filter clogging detection
3
Filter cleaning
4
Fresh air intake
Switching remote
5
display
6
Humidifier control
7
Air flow set in case of Heat thermo OFF
8
9
Auto restart function
10
Power ON/OFF by breaker
Built-in remote controller
Provided
2,500hr
Effective
Thermo ON signal display
Always operated while the heat in ON +1
Low +3
Setting air flow +3
Effective
Effective
Indoor unit
Not provided
100hr
Not effective
Indicating fan operation ON/OFF
Operated depends on the condition +2
Extra low +3
Depends on SW1-7
Not effective
Not effective
Effective
timing
Note :
+1
mode
Under suspension
+2
operating.
Address board
<Initial setting>
ON
OFF
1234 56789
Fan operation at Heating
Heating thermo ON is
+3
SW1-7
SW1-8 OFF
ON
OFF
ON
OFF Extra low
OFF
ON
ON
10
Low
Setting air flow
Stop
SW2
Capacity
code
setting
SW3
Function
setting
MODELS
P12
P15
1~6
P18
Heat pump/Cooling only
1
Louver/Humidifier
2
Vane
3
Vane swing function in heating
4
(wave-flow)
Vane horizontal angle
5
Vane horizontal angle
6
Changing the opening of
7
linear expansion valve
Sensible temperatre correction
8
Superheat setting temperature
9
Sub cool setting temperature
10
SW2 SW2
ON
OFF
123456
ON
OFF
123456
ON
OFF
123456
MODELS
P24
P30
P36
Cooling only
Available
Available
Available
Second setting
Third setting
Effective
Not effective
+5
+5
ON
OFF
123456
ON
OFF
123456
ON
OFF
123456
+4
+4
Heat pump
Not available
Not available
Not available
First setting
+4
Depends on SW3-5
Not effective
Effective
Before power supply ON
Under suspension
Indoor controller board
<Initial setting>
Set for each capacity.
Indoor controller board
<Initial setting>
ON
OFF
1234 56789
Note : +4
SW3-5,6
+5
Please do not use SW-3-9,10 as trouble might be caused by the usage condition.
10
SW4
Model Selection (Setting
for
PLFY
series)
1~5
ON
OFF
12345
Before power supply ON
Indoor controller board
Note : +4 SW3-5,6
SW3-5
SW3-6 Vane setting
Initial setting●Setting Vane position
OFF OFF Set up Standard Standard ON OFF Set up Less draft * Upward position than the standard OFF ON Set up Less smudging Downward position than the standard
ON ON unused
* Be careful of the smudge on ceiling.
26
Switch
Pole
Operation by switch
Effective
timing
Remarks
SWA
Ceiling
height
selector
SWB
Discharge
outlet
number
selector
SWC
Option
selector
(High ceiling)
1~3
(Standard)
(Silent)
3
2
(2
direction)
direction)
(3
(4 direction)
(Option)
(Standard)
* Ceiling height can be changed depending on
3
2
1
2
3
4
SWB setting.
PLFY-P12·P15·P18·P24·P30NBMU-E(R1)
SWA
SWB
4 direction
3 direction
2 direction
PLFY-P36NBMU-E(R1)
SWA
SWB
4 direction
3 direction
2 direction
Silent
2.5m, 8.2ft
2.7m, 8.9ft
3.0m, 9.8ft
Silent
2.7m, 8.9ft
3.0m, 9.8ft
3.3m, 10.8ft
Standard
2.7m, 8.9ft
3.0m, 9.8ft
3.3m, 10.8ft
Standard
3.2m, 10.5ft
3.6m, 11.8ft
4.0m, 13.1ft
High ceiling
3.5m, 11.5ft
3.5m, 11.5ft
3.5m, 11.5ft
High ceiling
4.5m, 14.8ft
4.5m, 14.8ft
4.5m, 14.8ft
Under operation or suspension
Address board
<Initial setting>
3 2 1
Address board
<Initial setting>
2 3 4
Address board
When attaching the optional high performance filter elements (multi function casement) to
<Initial setting>
the unit, be sure to attach it to the option side in order to prevent the airflow reducing.
 
SW11
1s digit
address
setting
SW12
10ths digit
address
setting
SW14
Branch
No.
setting
SW1210SW11
0
1
9
2
8
3
7
4
6
5
Rotary switchRotary switch
SW14
F
E
D
C
B
A
Address board
0
9
8
7
6
5
1
How to set address
1
2
Example : If address is "3", remain SW12
3
4
(for over 10) at "0", and match SW11 (for 1 to 9) with "3".
<Initial setting>
SW12 SW11
0
0
1
9
8
7
6
5
1
9
2
4
2
8
3
3
7
4
6
5
Before power supply
Address board
ON
0
1
2
3
4
5
6
7
8
9
How to set branch number SW14 (Series R2 only) Match the indoor unit’s refrigerant pipe with the BC contoller’s end connection number Remain other than series R2 at "0".
<Initial setting>
SW14
0
1
2
F
3
E
4
D
5
C
6
B
7
A
8
9
27
Switch Pole Operation by switch Remarks
Effective
timing
J41, J42
Wireless
remote
controller
Pair No.
• To operate each indoor unit by each remote controller when installed 2 indoor units or more are near, Pair No. setting is necessary.
Pair No. setting is available with the 4 patterns (Setting patters A to D). Make setting for J41, J42 of indoor controller board and the Pair No. of
wireless remote controller.
• You may not set it when operating it by one remote controller.
Setting for indoor unit
Jumper wire J41, J42 on the indoor controller board are cut according to the table below.
Wireless remote controller Pair No.:
Setting operation
1. Press the SET button (using a pointed implement). Check that the remote controller's display has stopped before continuing.
MODEL SELECT
blinks, and the model No. (3 digits) appears (steadily-lit).
2. Press the MINUTE button twice. The pair number appears flashing.
3. Press the temperature buttons to select the pair number to set.
4. Press the SET button (using a pointed implement). The set Pair No. is displayed (steadily-lit) for 3 seconds, then disappears.
Indoor controller
Setting pattern
Jumper wire
J41 J42
A
B
C
D
Cut
Cut
Cut
Cut
+Pair No.4-9 of wireless remote controller is setting pattern D.
Pair No. of wireless remote controller +
0
1
2
3
Initial setting
Under operation or suspension
Indoor controller board
<Initial setting>
Pattern A
MODEL SELECT
TEMP
ON/OFF
AUTO STOP
FAN
AUTO START
MODE
VANE
h
LOUVER
CHECK
TEST RUN
SET button
min
RESET
CLOCK
SET
Pair No.
Model No.
Temperature button
Minute button
SWE
Test run
for Drain pump
Drain pump and fan are activated simultaneously after the connector SWE is set to ON and turn ON the power.
SWE SWE
OFF ON
Connector Jumper
The connector SWE is set to OFF after test run.
OFF ON
Under operation
Indoor controller board
<Initial setting>
SWE
OFF ON
28
10-3. TEST POINT DIAGRAM
10-3-1. Indoor controller board PLFY-P12/15/18/24/30/36NBMU-E PLFY-P12/15/18/24/30/36NBMU-ER1
CN60
Linear expansion valve (LEV) output 12VDC pulse output
CN4Y
i-See sensor
CN52
Remote indicator
CN51
Centrally controlled
CN44
Pipe temperature thermistor
1-2 : Liquid (TH22) 3-4 : Gas (TH23)
CN4F
Drain float switch (FS)
CN20
Room temperature thermistor (TH21)
CN27
Damper signal output 12VDC(1 : +)
CN90 Connect to the wireless remote controller board (W.B)
CN6Y
i-see sensor motor output 12VDC pulse output
CN3A
Connect to the terminal block (TB15) (MA-Remote controller connecting wire) 1 - 3 : 8.7-13V DC (Pin1 (+))
CNV
Vane motor output 12VDC pulse
CN32
Remote switch
Jumper wire J41, J42
Pair No.setting for wireless remote controller
LED2
Power supply for MA-Remote controller
SW3
Function setting
SW4
Model selection
SWE
Test run(Drain pump)
SW2
Capacity setting
LED1 Main power supply (Indoor unit : 208-230V)
CNMF Connect to the fan motor (MF)
1-4 : DC310~340V 5-4 : DC15V 6-4 : DC0~6V
DC0 or DC15V (Stop)
7-4 :
DC7.5V (Operation) (12VDC pulse)
CNP Drain pump output (DP)
1-3 : 208-230VAC
CN2M
Connect to the terminal block (TB5) (M-NET transmission connecting wire) 24-30VDC (non-polar)
CND
Power supply for indoor controller board 3 - 5 : 208-230VAC
FUSE
6.3A 250V
29
10-3-2. Circuit board
PLFY-P12NBMU-E(R1) PLFY-P15NBMU-E(R1) PLFY-P18NBMU-E(R1) PLFY-P24NBMU-E(R1) PLFY-P30NBMU-E(R1) PLFY-P36NBMU-E(R1)
SW1
Function setting
SW12
Address setting 2nd digit
SWA
Ceiling height selector
SW11
Address setting 1st digit
SWB
Discharge outlet
number selector
SWC
Option selector
30
11
DISASSEMBLY PROCEDURE
PLFY-P12NBMU-E(R1) PLFY-P15NBMU-E(R1) PLFY-P18NBMU-E(R1) PLFY-P24NBMU-E(R1) PLFY-P30NBMU-E(R1) PLFY-P36NBMU-E(R1)
Be careful when removing heavy parts.
OPERATING PROCEDURE
1. Removing the air intake grille
(1) Slide the knob of air intake grille toward the arrow 1 to
open the air intake grille.
(2) Remove drop prevention hook from the panel. (3) Slide the shaft in the hinge to the direction of the arrow 2
and remove the air intake grille.
2. Removing the room temperature thermistor (TH21)
(1) Remove the air intake grille and the filter. (See Figure 1) (2) Remove the 2 screws from the electrical box. (3) Disconnect the connector CN20 (Red) from the indoor con­ troller board. (4) Remove the room temperature thermistor.
3. Removing the address board (A.B)
(1) Remove the air intake grille and the filter. (See Figure 1) (2) Remove the 2 screws from the address board cover. (3) Disconnect the connectors CN43 (RED/4P) and CN82
(RED/8P).
(4) Slide and remove the address board.
Figure 1
Photo 1
MA remote controller terminal cover
Terminal
cover fixing
screw
PHOTOS & ILLUSTRATIONS
Filter
Address board cover fixing screw
Address board
Address board fixing screw
Electrical box cover
fixing screws
Electrical box cover
cover
4. Removing the indoor controller board (I.B)
(1) Remove the air intake grille and the filter. (See Figure 1) (2) Remove the 2 screws from the electrical box cover. (3) Disconnect the connectors : CNMF (White/7P) for fan motor CN44 (White/4P) for thermistor (TH22/TH23) CNP (Blue/3P) for drain pump CN4F (White/4P) for float switch CN01 (Black/5P) for earth and TB2 CNV (White/20P) for vane motor CN81, CN42 (Red/8P, 4P) for address board CN2M (Blue/2P) for TB5 CN3A (Blue/3P) for TB15 (4) Remove the 6 supports from indoor controller board. (5) Remove the indoor controller board.
5. Removing the electrical box
(1) Remove the air intake grille and the filter. (See Figure 1) (2) Remove the 2 screws from the electrical box cover. (3) Disconnect the connectors. (Refer to 4.)
Remove 4 electrical box fixing screws and remove 2 hooks.
(4) (5) Pull the electrical box.
<Electrical parts in the electrical box>
Indoor controller board Terminal block (TB2) (TB5)
Photo 2
Room temp. thermistor (TH22)
Electrical box fixing screw
Electrical box
Indoor controller board
Bell mouth
Turbo fan
Nut
Electrical box fixing screw
Support for Indoor controller board
31
OPERATING PROCEDURE
PHOTOS & ILLUSTRATIONS
6. Removing the fan and fan motor (MF)
(1) Remove the electrical box. (See Photo 2) (2) Remove the bell mouth (3 screws). (See Photo 2) (3) Remove the turbo fan nut. (4) Pull out the turbo fan. (5) Remove the wire cover (3 screws). (6) Remove 2 wiring clamps. (7) Disconnect the connector of the fan motor (CNMF). (8) Remove the 3 nuts and washers and rubber mounts of the
fan motor.
7. Removing the panel
(1) Remove the air intake grille and the filter. (See Figure 1) (2) Disconnect the connector CNV (White/20P).
Corner panel (See Figure 2)
(3) Remove the corner screw. (4) Slide the corner panel to the direction of the arrow 1, and
remove the corner panel.
Panel (See Photo 4, 5)
(5) Remove the 2 screws from the panel which fixes to the oval
holes.
(6) Rotate the panel a little to come to the bell shaped hole
where the screw is large and remove the panel.
Photo 3
Figure 2
Corner panel
Photo 4
Fan motor
Screw
Detail
Coil plate
Screw
Corner panel
Bell shaped hole
Clamp
Wire cover fixing screw
Nut Washer Rubber mount
Panel
Photo 5
8. Removing the drain pan
(1) Remove the air intake grille and the filter. (See Figure 1) (2) Remove the 2 screws from the electrical box cover. (3) Disconnect the connectors. (Refer to 4.) (4) Remove the panel. (See Photo 4, 5) (5) Remove the electrical wiring service panel (3 screws). (6) Remove the drain pump wire cover (1 screw). (7) Remove the electrical box. (See Photo 2) (8) Remove the bell mouth. (See Photo 2) (9) Remove the 4 screws and pull out the drain pan. w Pull out the left and right of the pan gradually. Be careful not to crack or damage the pan.
Photo 6
Drain pan fixing screw
Electrical wiring service panel
Drain pan fixing screw
Oval hole
Drain pump wire cover
Electrical wiring ser­vice panel fixing screw
Drain pan fixing screw
Drain pan
32
OPERATING PROCEDURE
PHOTOS & ILLUSTRATIONS
9. Removing the liquid pipe temperature thermistor (TH22) and gas pipe temperature thermistor (TH23)
(1) Remove the drain pan. (See Photo 6) (2) Remove the turbo fan. (Refer to 6) (3) Remove the 2 wiring clamps. (See Photo 3) (4) Remove the coil plate (2 screws). (5) Remove the thermistors which are inserted into the holders
installed to the thin copper pipe.
(6) Disconnect the 4-pin white connector (CN44).
10 Removing the drain pump (DP) and float switch (FS)
(1) Remove the drain pan. (See Photo 6) (2) Cut the hose band and remove the hose. (3) Remove the drain pump assembly (3 screws and 2 hooks). (4) Remove the drain pump (3 screws). (5) Remove the float switch (2 screws).
Photo 7
Gas pipe temp. thermistor (TH23)
Liquid pipe temp. thermistor (TH22)
Photo 8
Float switch
Hose band
Drain pump
33
Photo 9
Drain pump fixing screw
Drain pump assembly fixing screw
Float switch fixing screw
OPERATING PROCEDURE
11. Removing the heat exchanger
(1) Remove the drain pan. (See Photo 6) (2) Remove the 3 screws of the piping cover, and pull out
piping cover. (3) Remove the 2 screws of coil plate. (4) Remove the 2 screws of the coil. (5) Remove the screw of the coil support. (6) Pull out the heat exchanger.
PHOTOS & ILLUSTRATIONS
Photo 10
Heat exchanger
Coil support
Linear expansion valve
Piping cover
Heat exchanger fixing screw
34
35
TM
HEAD OFFICE : TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU TOKYO 100-8310, JAPAN
cCopyright 2007 MITSUBISHI ELECTRIC ENGINEERING CO., LTD. Distributed in Nov. 2008 No. OCH421 REVISED EDITION-A PDF 7 Distributed in Jul. 2007 No. OCH421 PDF 9 Made in Japan
New publication, effective Nov. 2008 Specifications subject to change without notice
Loading...