Mitsubishi PLFY-P20VLMD-E, PLFY-P25VLMD-E, PLFY-P32VLMD-E, PLFY-P40VLMD-E, PLFY-P50VLMD-E Service Manual

...
TECHNICAL & SERVICE MANUAL
Air-Conditioners For Building Application
<Indoor unit>
2004
Models
Ceiling Cassettes
Series PLFY
PLFY-P20VLMD-E,PLFY-P63VLMD-E PLFY-P25VLMD-E,PLFY-P80VLMD-E PLFY-P32VLMD-E,PLFY-P100VLMD-E PLFY-P40VLMD-E,PLFY-P125VLMD-E PLFY-P50VLMD-E
INDOOR UNIT
CONTENTS
SAFETY PRECAUTIONS ·························1
1. FEATURES ···········································3
2. PART NAMES AND FUNCTIONS········4
3. SPECIFICATION ···································6
4. OUTLINES AND DIMENSIONS············8
5. WIRING DIAGRAM ·····························11
6.
REFRIGERANT SYSTEM DIAGRAM
13····
7. TROUBLE SHOOTING ·······················14
8. DISASSEMBLY PROCEDURE···········
20
SAFETY PRECAUTIONS
1. Before installation and electric work
Keep the electric parts away from water (washing water etc.).
- It might result in electric shock, catching fire or smoke.
To dispose of this product, consult your dealer.
Do not use a leak detection additive.
1
s Before installing the unit, make sure you read all the
Safety precautions”.
s The “Safety precautions provide very important
points regarding safety. Make sure you follow them.
s This equipment may cause the adverse effect on the
same supply system.
s Please report to or take consent by the supply au-
thority before connection to the system.
Symbols used in the text
Warning:
Describes precautions that should be observed to prevent danger of injury or death to the user.
Never repair the unit. If the air conditioner must be repaired, consult the dealer.
- If the unit is repaired improperly, water leakage, electric shock, or
fire may result.
Do not touch the heat exchanger fins.
- Improper handling may result in injury.
If refrigerant gas leaks during installation work, ventilate the room.
- If the refrigerant gas comes into contact with a flame, poisonous
gases will be released.
Install the air conditioner according to this Installation Manual.
- If the unit is installed improperly, water leakage, electric shock, or
fire may result.
Have all electric work done by a licensed electrician according to Electric Facility Engineering Standard and “Interior Wire Regulationsand the instructions given in this manual and al­ways use a special circuit.
- If the power source capacity is inadequate or electric work is per-
formed improperly, electric shock and fire may result.
Caution:
Describes precautions that should be observed to prevent damage to the unit.
Symbols used in the illustrations
: Indicates an action that must be avoided.
: Indicates that impor tant instructions must be followed.
: Indicates a part which must be grounded.
: Indicates that caution should be taken with rotating parts. (This
symbol is displayed on the main unit label.) <Color: Yellow>
: Beware of electric shock (This symbol is displayed on the main
unit label.) <Color: Yellow>
Warning:
Carefully read the labels affixed to the main unit.
Warning:
Ask the dealer or an authorized technician to install the air con­ditioner.
- Improper installation by the user may result in water leakage, elec-
tric shock, or fire.
Install the air unit at a place that can withstand its weight.
- Inadequate strength may cause the unit to fall down, resulting in
injuries.
Use the specified cables for wiring. Make the connections se­curely so that the outside force of the cable is not applied to the terminals.
- Inadequate connection and fastening may generate heat and cause
a fire.
Prepare for typhoons and other strong winds and earthquakes and install the unit at the specified place.
- Improper installation may cause the unit to topple and result in
injury.
Always use an air cleaner, humidifier, electric heater, and other accessories specified by Mitsubishi Electric.
- Ask an authorized technician to install the accessories. Improper
installation by the user may result in water leakage, electric shock, or fire.
Securely install the cover of control box and the panel.
- If the cover and panel are not installed properly,dust or water may enter the outdoor unit and fire or electric shock may result.
When installing and moving the air conditioner to another site, do not charge the it with a refrigerant different from the refrig­erant specified on the unit.
- If a different refrigerant or air is mixed with the original refrigerant,
the refrigerant cycle may malfunction and the unit may be dam­aged.
If the air conditioner is installed in a small room, measures must be taken to prevent the refrigerant concentration from exceeding the safety limit even if the refrigerant should leak.
- Consult the dealer regarding the appropriate measures to pre-
vent the safety limit from being exceeded. Should the refrigerant leak and cause the safety limit to be exceeded, hazards due to lack of oxygen in the room could result.
When moving and reinstalling the air conditioner, consult the dealer or an authorized technician.
- If the air conditioner is installed improperly, water leakage, elec-
tric shock, or fire may result.
After completing installation work, make sure that refrigerant gas is not leaking.
- If the refrigerant gas leaks and is exposed to a fan heater, stove,
oven, or other heat source, it may generate noxious gases.
Do not reconstruct or change the settings of the protection devices.
- If the pressure switch, thermal switch, or other protection device
is shorted and operated forcibly, or parts other than those specified by Mitsubishi Electric are used, fire or explosion may result.
2. Precautions for devices that use
Caution:
Do not use the existing refrigerant piping.
- The old refrigerant and refrigerator oil in the existing piping con­tains a large amount of chlorine which may cause the refrigerator oil of the new unit to deteriorate.
Use refrigerant piping made of C1220 (Cu-DHP) phosphorus deoxidized copper as specified in the *JIS H3300 “Copper and copper alloy seamless pipes and tubes. In addition, be sure that the inner and outer surfaces of the pipes are clean and free of hazardous sulphur, oxides, dust/dirt, shaving particles, oils, moisture, or any other contaminant.
- Contaminants on the inside of the refrigerant piping may cause
the refrigerant residual oil to deteriorate.
*JIS: Japanese Industrial Standard
Store the piping to be used during installation indoors and keep both ends of the piping sealed until just before brazing. (Store elbows and other joints in a plastic bag.)
- If dust, dirt, or water enters the refrigerant cycle, deterioration of
the oil and compressor trouble may result.
Use ester oil, ether oil or alkylbenzene (small amount) as the refrigerator oil to coat flares and flange connections.
- The refrigerator oil will degrade if it is mixed with a large amount of
mineral oil.
Use liquid refrigerant to fill the system.
- If gas refrigerant is used to seal the system, the composition of
the refrigerant in the cylinder will change and performance may drop.
Do not use a refrig
- If another refrigerant (R22, etc.) is used, the chlorine in the refrig-
erant may cause the refrigerator oil to deteriorate.
Use a vacuum pump with a reverse flow check valve..
- The vacuum pump oil may flow back into the refrigerant cycle and
cause the refrigerator oil to deteriorate.
Do not use the following tools that are used with conventional refrigerants. (Gauge manifold, charge hose, gas leak detector, reverse flow check valve, refrigerant charge base, vacuum gauge, refriger­ant recovery equipment)
- If the conventional refrigerant and refrigerator oil are mixed in the
Do not use a charging cylinder.
- Using a charging cylinder may cause the refrigerant to deteriorate.
Be especially careful when managing the tools.
- If dust, dirt, or water gets in the refrigerant cycle, the refrigerant
may deteriorate.
R410A or R407C refrigerant
erant other than R410A or R407C.
R410A or R407C, the refrigerant may deteriorated.
- If deteriorate.
water is mixed in the R410A or R407C, the refrigerator oil may
- Since R410A or R4 07C does not contain any chlorine, gas leak detectors for conventional refrigerants will not react to it.
2
PLFY-P20VLMD-E
PLFY-P25VLMD-E
PLFY-P32VLMD-E
PLFY-P40VLMD-E
PLFY-P50VLMD-E
PLFY-P63VLMD-E
2.2 / 2.5
2.8 / 3.2
3.6 / 4.0
4.5 / 5.0
5.6 / 6.3
PLFY-P80VLMD-E
9.0 / 10.0
PLFY-P100VLMD-E
11.2 / 12.5
PLFY-P125VLMD-E
14.0 / 16.0
7.1 / 8.0
FEATURES
1
Indoor unit
Ceiling Cassettes
Series PLFY
Models
Cooling capacity/Heating capacity
kW
3
PART NAMES AND FUNCTIONS
2
Indoor (Main) Unit
Air inlet
Sucks the ambient air in.
Long-life filter
Removes the sucked-in dust and dirt. Since the long-life filter is used as an air filter, it should be cleaned at the begin­ning of air-cooling and heating seasons. (During seasons with large amounts of dust and dirt, more frequent cleaning are recommended.)
Autovane
Disperses the airflow up and down and adjusts the angle of the airflow.
Remote controller
[Operation buttons]
[PAR-20MAA]
Once the controls are set, the same operation mode can
be repeated by simply pressing the ON/OFF button.
PAR-20MAA
ON/OFF
CENTRALLY CONTROLLED
ERROR CODE
CLOCK
ON OFF
˚C
CHECK
CHECK MODE
FILTER
TEST RUN FUNCTION
˚C
1Hr.
NOT AVAILABLE
STAND BY DEFROST
FILTER
CHECK TEST
TEMP.
TIMER SET
1
2
3
4 56879
0
C
A
B
1 [Room temperature adjustment] Button 2 [Timer/continuous] Button 3 [Selecting operation] Button 4 [Time selection] Button
[Time-setting] Button
5 [Louver] Button 6 [Fan speed adjustment] Button
7 [Up/down airflow direction] Button 8 [Ventilation] Button 9 [Checking/built-in] Button 0 [Test run] Button A [Filter] Button B [ON/OFF] Button C Position of built-in room temperature
•Never expose the remote controller to direct sunlight. Doing so can result in the erroneous measure­ment of room temperature.
•Never place any obstacle around the lower right-hand section of the remote controller. Doing so can result in the erroneous measurement of room temperature.
4
[Display]
A
Current time/Timer
B
Centralized control
C
Timer ON
D
Abnormality occurs
E
Operation mode: COOL, DRY, AUTO, FAN, HEAT
F
Preparing for Heating mode
G
Defrost mode
H
Set temperature
I
Power ON
J
Louver
K
Not available function
L
Ventilation
M
Function setting mode
N
Test run mode
O
Error check mode
P
Filter sign
Q
Set effective for 1 hr.
R
Sensor position
S
Room temperature
T
Airflow
U
Fan speed
5
ABCD
SQTU
CENTRALLY CONTROLLED
STAND BY DEFROST
G
CHECK
TEMP.
HIKLJ
E
F
˚C
ON OFF
CLOCK
ERROR CODE
1Hr.
NOT AVAILABLE
˚C
FILTER
CHECK MODE
TEST RUN FUNCTION
ON/OFF
R P
O N M
3
SPECIFICATION
3-1. Specification
6
Note:
3 The figure in < > indicates panel's
1 Cooling/Heating capacity indicates the maximum value at operation under the following condition.
Cooling : Indoor 27˚CDB/19˚CWB,Outdoor 35˚CDB Heating : Indoor 20˚CDB,Outdoor 7˚CDB/6˚CWB
2 Cooling capacity indicates the maximum value at operation under the following condition.
Cooling : Indoor 27˚CDB/19.5˚CWB,Outdoor 35˚CDB (WR2: water 30˚C)
4 It is measured in anechoic room.
PLFY-P20VLMD-E PLFY-P25VLMD-E PLFY-P32VLMD-E PLFY-P40VLMD-E
~ 220-240V 50Hz / ~ 220-230V 60Hz
Power source
kcal/h
kW
Cooling capacity
1
2
1
3
kW
kWCooling Heating Cooling Heating
kW
A A
mm mm mm
kg
m
3
/min
Pa
kW
mm mm
dB(A) dB(A)
Heating capacity
Powe r consumption
Current
External finish(Munsel No.)
Dimension ❇3
Height Width Depth
Net weight Heat exchanger
Fan
Type
External static pressure
Motor
Output
Type
Air filter Refrigerant
pipe dimension
Gas(Flare)
Liquid(Flare)
Drain pipe dimension
Unit: Galvanizing Decoration Panel: ABS (0.7Y 8.59/0.97) Service Panel: Galvanizing (0.7Y 8.59/0.97)
290 <20>
776 <1080>
634 <710>
23 <6.5>
Cross fin
Turbo fan1
Single phase induction motor
PP honeycomb fabric (long life filter)
ø 12.7
ø 6.35
Unit drain pipe I.D.32 (1-1/4inch)
6.5-8.0-9.5 7.0-8.5-10.5 0
0.015
24 <6.5>
Airflow rate (Lo-Mid-Hi)
Noise level (Lo-Mid-Hi) 4
220V,240V
230V
2.2
2,000
2.5
0.072 / 0.075
0.065 / 0.069
0.36 / 0.37
0.30 / 0.32
2.8
2,500
3.2
0.072 / 0.075
0.065 / 0.069
0.36 / 0.37
0.30 / 0.32
3.6
3,150
4.0
0.072 / 0.075
0.065 / 0.069
0.36 / 0.37
0.30 / 0.32
4.5
4,000
5.0
0.081 / 0.085
0.074 / 0.079
0.40 / 0.42
0.34 / 0.37
27-30-33 28-31-34 30-34-37
PLFY-P63VLMD-E PLFY-P80VLMD-E
PLFY-P100VLMD-E PLFY-P125VLMD-E
~ 220-240V 50Hz / ~ 220-230V 60Hz
Power source
kcal/h
kW
Cooling capacity
1
2
1
3
kW
kWCooling Heating Cooling Heating
kW
A A
mm mm mm
kg
m
3
/min
Pa
kW
mm
mm
dB(A) dB(A)
Heating capacity
Powe r consumption
Current
External finish(Munsel No.)
Dimension ❇3
Height Width Depth
Net weight
Heat exchanger
Fan
Type
External static pressure
Motor
Output
Type
Air filter
Refrigerant pipe dimension
Gas(Flare)
Liquid(Flare)
Drain pipe dimension
Unit: Galvanizing Decoration Panel: ABS (0.7Y 8.59/0.97) Service Panel: Galvanizing (0.7Y 8.59/0.97)
634 <710>
290 <20>
1446 <1750> 1708 <2010>
606 <710>
28 <7.5> 44 <12.5> 47 <12.5> 56 <13.0>
Cross fin
Turbo fan1 Turbo fan2 Sirocco fan4
Single phase induction motor
Synthetic fiber unwoven
cloth filter (long life)
ø
15.88
ø
9.52
Unit drain pipe I.D.32 (1-1/4inch)
10.0-13.0-15.5
24.0-27.0-30.0-33.0 (Lo-Mid2-Mid1-Hi)
17.5-21.0-25.015.5-18.5-22.0
0
0.020 0.020 (at 240V) 0.030 (at 240V) 0.0782(at 240V)
Airflow rate (Lo-Mid-Hi)
Noise level (Lo-Mid-Hi) 4
220V,240V
230V
7.1
6,300
8.0
0.101 / 0.105
0.094 / 0.099
0.49 / 0.51
0.43 / 0.46
9.0
8,000
10.0
0.147 / 0.156
0.140 / 0.150
0.72 / 0.74
0.66 / 0.69
11.2
10,000
12.5
0.157 / 0.186
0.150 / 0.180
0.75 / 0.88
0.69 / 0.83
14.0
12,500
16.0
0.28 / 0.28
0.27 / 0.27
1.35 / 1.35
1.33 / 1.33
33-36-39
34-37-40
PLFY-P50VLMD-E
946 <1250>
27 <7.5>
PP honeycomb fabric (long life filter)
9.0-11.0-12.5
5.6
5,000
6.3
0.082 / 0.086
0.075 / 0.080
0.41 / 0.43
0.35 / 0.38
31-34-37 32-35-38
32-37-39 33-38-40 37-41-43
40-42-44-46
(Lo-Mid2-Mid1-Hi)
ø 15.88 (R410A)
ø 19.05 (R22,R407C)
29-33-36
ø 12.7 (R410A)
ø 15.88 (R22,R407C)
ø 6.35 (R410A)
ø 9.52 (R22,R407C)
36-39-42
1.7µF
x 440V
1.5µF
x 440V
2.2µF
x 440V
1.5µF
x 440V
2.0µF
x 440V
5.0µF
x 440V
LEV
C1
1.3µF x 440V
MF1
-
PLFY-P20
VLMD-E
PLFY-P25
VLMD-E
PLFY-P32
VLMD-E
PLFY-P40
VLMD-E
PLFY-P50
VLMD-E
PLFY-P63
VLMD-E
3-2. Electrical parts specifications
Model
Parts
name
Tranrsformer T
(Primary) 220-240V 50Hz, 220-230V 60Hz (Secondry) 23.2V 1.1A
(Primary)
50/60Hz
220-240V
(Secondry)
18.4V 1.7A
Resistance 0°C/15k, 10°C/9.6k, 20°C/6.3k,25°C/5.4k, 30°C/4.3k, 40°C/3.0k
Resistance 0°C/15k, 10°C/9.6k, 20°C/6.3k,25°C/5.4k, 30°C/4.3k, 40°C/3.0k
Resistance 0°C/15k, 10°C/9.6k, 20°C/6.3k,25°C/5.4k, 30°C/4.3k, 40°C/3.0k
TH21
TH22
Gas pipe thermistor
F901 250V 6.3A
MV
DP
Drain sensor DS
TB2
TB5
TB15
Fuse
(Indoor
controller board)
Power supply terminal bed
Transmission terminal bed
PLFY-P80
VLMD-E
PLFY-P100
VLMD-E
PLFY-P125
VLMD-E
OFF 145±8°C ON 88±15°C
DC12V Stepping motor
INPUT 6.4/5.5W
400cm
3
/min
INPUT 8/7.5W
400cm
3
/min
Resistance 0°C/6.0k, 10°C/3.9k, 20°C/2.6k,25°C/2.2k, 30°C/1.8k, 40°C/1.3k
DC12V Stepping motor drive port dimension ø 3.2 (0~2000pulse)
(L,N, ) 330V 30A
(M1,M2,S),(1,2) 300V 10A
Room temperature thermistor
Fan motor
(with Inner-
thermostat)
6-pole
OUTPUT 15W
6-pole
OUTPUT
30W
4-pole
OUTPUT
78W
6-pole
OUTPUT 20W
Symbol
TH23
Inner­thermostat
(Fan motor)
Liquid pipe thermistor
Fan motor capacitor
Drain-up mechanism
Linear expansion valve
Vane motor
OFF
130˚C±5˚C
ON
90˚C±20˚C
DC12V Stepping motor drive
port dimension
ø 5.2
0~1800pulse <at R410A outdoor unit> 0~2000pulse <at the other outdoor unit>
0~1800pulse <at R410A outdoor unit> 0~2000pulse <at the other outdoor unit>
7
4
OUTLINES AND DIMENSIONS
PLFY-P20·25·32·40·50·63·80·100VLMD-E
Unit :
mm
8
170mm ± 5mm(Actual Length)
300mm or less
583mmMAX
73 202
222190
4-ø2.9 Mounting hole
Fresh air intake 240x45 knock out hole
240 197
45 216
710
A
Standard center panel
Terminal bed(Transmission)
Terminal bed(Power source)
48
670
48
70 146
507
634
574
108
D(Lifting Bolt Pitch)
108
B
Terminal box
Air filter
Water filling port
Drain hole
3
2
1
290
45
20
68
20
20
68
More Than 350
670
190
146
497
634
122
266
60
574
(Lifting Bolt Pitch)
70
3
36
22
29
27
H
(Gas)
22
H
(Liquid)
17
CMP-63VLW-B
CMP-40VLW-B
388776 82410401080
47399494612101250
E
D
C
B
A
PLFY-P63VLMD-E
PLFY-P50VLMD-E
PLFY-P40VLMD-E
PLFY-P32VLMD-E
PLFY-P25VLMD-E
PLFY-P20VLMD-E
Model
217.52
=435
F
6
G
PLFY-P100VLMD-E
PLFY-P80VLMD-E
10
188.54
=754
1494 723144617101750
CMP-100VLW-B
H
Note: 1.Use M10 screw for the lifing bolt (field supply).
2.It is available to connect the branch duct on right and left side both.
3.On Model :50, 100, you would use flare nut packed with the Indoor
Unit, when connnecting the Outdoor Unit for R407C, R22.
4.In order to increase the strength of the flare nut, the size of some
of them has been increased.
<flare>
Model Gas pipe:LP ø12.7
20·25·32·40 Liquid pipe:HP ø6.35
Model Gas pipe:LP ø12.7<R410A outdoor unit>
50 ø15.88<The other outdoor unit>
Liquid pipe:HP ø6.35<R410A outdoor unit>
ø9.52<The other outdoor unit>
Model Gas pipe:LP ø15.88
63·80 Liquid pipe:HP ø9.52 Model Gas pipe:LP ø15.88<R410A outdoor unit>
100 ø19.05<The other outdoor unit>
Liquid pipe:HP ø9.52
Drain hose VP-25<flexible joint> (accessory)
········ 1
········ 2
········ 1
········ 2
········ 1
········ 2
········ 1
········ 2
········ 3
G-ø2.9 Mounting hole
Branch duct Fx110 knock out hole
(both side)(Note:2)
Control box
2020 B
E
C
D(Lifting bolt pitch)
221
34159
52110
F
PLFY-P125VLMD-E
Unit :
mm
A
3
3
1
2
Water filling port
2
1
3
Air filter
20 338~353
4-ø2.8Mounting hole
Standard center panel
(CMP-125VLW-B)
Branch duct ø200 knock out hole (both side)
4-ø2.9Mounting hole
Fresh air intake ø150 knock out hole
90
˚
ø224
45
˚
90
˚
ø172
90
˚
303
170mm±5mm(Actual length)
600mm Max
300mm or less
45
More than 350
155
255
127127
107
574
1970
670
4848
107 1756
6868 574(Lifting bolt pitch)
192
1970(Ceiling opening)
670(Ceiling opening)20 20
710
2010
2020
290
606
145
856
1708
1756
(Lifting bolt pitch)
181
235
Drain hole
222
Control box
Terminal box
Terminal bed
(Power source)
70 333
38
106
476
70 178
606
Terminal bed
(Transmission)
Note: 1.Use M10 screw for the lifting bolt (field supply).
2.On this model, you would use flare nut packed
with the Indoor Unit, when connnectingthe
Outdoor Unit for R407C, R22.
3.In order to increase the strength of theflare nut,
the size of some of them has been increased.
36
A
(Gas)
A
(Liquid)
22PLFY-P125VLMD-E
Model
<flare>
Gas pipe:LP ø15.88<R410A outdoor unit>
ø19.05<The other outdoor unit>
Liquid pipe:HP ø9.52 Drain hose VP-25<flexible joint> (accessory)
········ 1
········ 2 ········ 3
9
10
PLFY-P20·25·32·40·50·63·80·100VLMD-E with OA duct flange
Unit : mm
5234110
159
E
20
221
Control Box
G-ø 2.9 Mounting hole
both side
206
241
138
243
103
D(Lifting Bolt Pitch)
C
B20
F
Branch duct Fx110 knock out hole
(both side)(Note:2)
45˚
Fresh air intake knock out dimension
Fresh air intake ø150 knock out hole
4-ø2.9 Mounting hole
ø
172
ø
150
90˚
103
128
B
108
D(Lifting Bolt Pitch)
108
574
634
507
14670
48
670
48
Terminal bed(Power source)
Terminal bed(Transmission)
128
241
256 189
Terminal box
Air filter
Water filling port
Drain hole
3
2
1
290
45
20
68
20
20
68
More Than 350
670
190
146
497
634
122
266
60
574
(Lifting Bolt Pitch)
70
170mm 5mm(Actual Length)
300mm or less
583mmMAX
710
A
Standard center panel
3
36
22
29
27
H
(Gas)
22
H
(Liquid)
17
CMP-63VLW-B
CMP-40VLW-B
388776 82410401080
47399494612101250
E
D
C
B
A
PLFY-P63VLMD-E
PLFY-P50VLMD-E
PLFY-P40VLMD-E
PLFY-P32VLMD-E
PLFY-P25VLMD-E
PLFY-P20VLMD-E
Model
217.52
=435
F
6
G
PLFY-P100VLMD-E
PLFY-P80VLMD-E
10
188.54
=754
1494 723144617101750
CMP-100VLW-B
H
Note: 1.Use M10 screw for the lifing bolt (field supply).
2.It is available to connect the branch duct on right and left side both.
3.On Model :50, 100, you would use flare nut packed with the Indoor
Unit, when connnecting the Outdoor Unit for R407C, R22.
4.In order to increase the strength of the flare nut, the size of some
of them has been increased.
<flare>
Model Gas pipe:LP ø12.7
20·25·32·40 Liquid pipe:HP ø6.35
Model Gas pipe:LP ø12.7<R410A outdoor unit>
50 ø15.88<The other outdoor unit>
Liquid pipe:HP ø6.35<R410A outdoor unit>
ø9.52<The other outdoor unit>
Model Gas pipe:LP ø15.88
63·80 Liquid pipe:HP ø9.52 Model Gas pipe:LP ø15.88<R410A outdoor unit>
100 ø19.05<The other outdoor unit>
Liquid pipe:HP ø9.52
Drain hose VP-25<flexible joint> (accessory)
········ 1
········ 2
········ 1
········ 2
········ 1
········ 2
········ 1
········ 2
········ 3