Mitsubishi PLA-RP_AA(1), PLA-RP_AA(1).UK, PEA-RP_EA, PEAD-RP_EA, PEAD-RP_EA.UK TECHNICAL MANUAL

...
SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
No. OCT04
SERVICE TECHNICAL GUIDE
<Indoor unit> [Model names] [Service Ref]
PLA-RP·AA PLA-RP·AA
PLA-RP·AA
R410A
1
PLA-RP·AA.UK PLA-RP·AA
PEA-RP·EA PEA-RP·EA.TH-A PEAD-RP·EA PEAD-RP·EA.UK
PEAD-RP·EA
<Outdoor unit> [Model names] [Service Ref]
PUHZ-RP·VHA PUHZ-RP·VHA
1.UK
1.UK
PUHZ-RP·VHA-A
CONTENTS
1. PAIRING TABLE OF THE INDOOR AND OUTDOOR UNIT·····2
2. SPECIFICATIONS FOR ELECTRICAL WORK ·························3
3. WIRING DIAGRAM·····································································6
4. REFRIGERANT SYSTEM DIAGRAM ······································11
5. HOW TO CHECK THE PARTS ················································18
6. MICROPROCESSOR CONTROL·············································24
8. OUTDOOR UNIT CONTROL····················································38
10. FUNCTION SETTING ·······························································67
11. TEST RUN • REPLACEMENT OPERATION & EMERGENCY OPERATION···················································77
12. SELF-DIAGNOSIS····································································83
13. TEST POINT DIAGRAM·························································109
14. TROUBLESHOOTING····························································117
15. SYSTEM CONTROL·······························································121
1
PLA-RP·AA PLA-RP·AA
1
PLA-RP·AA.UK PLA-RP·AA
1.UK
PEAD-RP·EA.UK PEAD-RP·EA
1
.UK
OC293
REVISED EDITION-A
OC297
REVISED EDITION-A
RP3VHA RP4VHA RP5VHA RP6VHA
Indoor unit
Outdoor unit [PUHZ]
OC294
PEA–RP·EA.TH-A
OC299
REVISED EDITION-A
RP3VHA-A RP4VHA-A RP5VHA-A RP6VHA-A
Indoor unit
Outdoor unit [PUHZ]
OC300 REVISED EDITION-A
PAIRING TABLE OF THE INDOOR AND OUTDOOR UNITS
2
2
Outdoor unit Power supply
Phase Frequency & Voltage Indoor unit(A) Outdoor unit(A)
Wire No.
25/25
3
32/32
3
32/32
3
40/40
3
Models (Outdoor unit)
~ / N (Single)
50Hz, 220-230-240V
Outdoor unit Power supply Input capacity Main switch/Fuse
Indoor unit/Outdoor unit connecting Wire No. o size (e) Remote controller-indoor unit connecting Wire No. o size (e)
Indoor unit power supply
~ / N (Single), 50Hz, 220-230-240V
Control circuit rating
Wiring
3 o 2.5 cable (Polar)
Cable 2C o 0.69
This wire is accessory of remote controller (Wire length: 10m, Non-polar)
Indoor unit-Outdoor unit: S1-S2 AC220V-230V-240V
S2-S3 DC24V
Remote controller-Indoor unit: DC14V
RP3V RP4V RP5V RP6V
1 2
S1 S2 S3
S1 S2 S3
Indoor/outdoor unit connection cable
Indoor unit
Unit power supply
Outdoor unit
Remote controller
L
N
Grounding
L N
1 2
1 2
S1
Indoor unit
S2 S3
S1 S2 S3
S1 S2 S3
Unit power supply
Indoor/outdoor unit connection cable
Indoor unit
Outdoor unit
Remote controller
Grounding
1 2
1 2
1 2
S1 S2 S3
S1 S2 S3
S1 S2 S3
S1 S2 S3
Indoor/outdoor connection cable
Indoor unit
Unit power supply
Indoor unit
Indoor unit
Outdoor unit
Remote controller
L N
Grounding
SPECIFICATIONS FOR ELECTRICAL WORK
2-1. Field electrical wiring(power wiring specifications) PUHZ-RP•VHA PUHZ-RP•VHA-A
Check items
1. Wiring size must comply with the applicable local and national code.
2. Be careful about choosing the installation location for the earth leakage breaker and how it is installed as the initial electric current may cause it to malfunction.
3. Power supply cords and indoor unit / Outdoor unit connecting cords shall not be lighter than polychloroprene sheathed flex­ible cord. (design 254 IEC 57)
1:1 system Synchronized twin and triple system Electrical wiring
• Synchronized twin
• Synchronized triple
3
2-2. M-NET wiring method
Group remote controller
Refrigerant address 00
M-NET address 01
A-control remote controller
A-control remote controller
A-control remote controller
Refrigerant address 00
M-NET address 02
Refrigerant address 00
M-NET address 03
Power supply unit for transmission wire
Central remote controller
M-NET transmission wire
Bad example (Multi spot grounding of shield wire)
Good example 1 (Single spot grounding of shield wire)
Power supply appliance
M-NET type outdoor unit
Central remote controller
Power supply appliance
M-NET type outdoor unit
M-NET type outdoor unit
M-NET type outdoor unit
M-NET transmission wire
M-NET type outdoor unit
M-NET type outdoor unit
Central remote controller
Power supply appliance
M-NET type outdoor unit
M-NET transmission wire
M-NET type outdoor unit
M-NET type outdoor unit
Good example 2 (Single spot grounding of shield wire)
(Points to notice) (1) Outside the unit, transmission wires should stay away from electric wires in order to prevent electromagnetic noise from
making an influence on the signal communication. Place them at intervals of more than 5cm. Do not put them in the same conduit tube.
(2) Terminal block (TB7) for transmission wires should never be connected to 220~240V power supply. If it is connected,
electronic parts on M-NET p.c. board may be burn out.
(3) Use 2-core x 1.25mm2shield wire (CVVS, CPEVS) for the transmission wire. Transmission signals may not be sent or
received normally if different types of transmission wires are put together in the same multi-conductor cable. Never do this because this may cause a malfunction.
It would be ok if M-NET wire (non-polar, 2-cores) is arranged in addition to the wiring for A-control.
(4) Ground only one of any appliances through M-NET transmission wire (shield wire). Communication error may occur due to
the influence of electromagnetic noise.
“Ed” error will appear on the LED display of outdoor unit. “0403” error will appear on the central-control remote controller.
If there are more than two grounding spots on the shield wire, noise may enter into the shield wire because the ground wire
and shield wire form one circuit and the electric potential difference occurs due to the impedance difference among ground­ing spots. In case of single spot grounding, noise does not enter into the shield wire because the ground wire and shield wire do not form one circuit.
To avoid communication errors caused by noise, make sure to observe the single spot grounding method described in the
installation manual.
4
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
12
~
50
M-NET Address No.
<Setting example>
Switng setting
SW11 ones digit
SW12 tens digit
OFF
ON
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
0
Refuigrant address
OFF
ON
8
OFF
ON
1
OFF
ON
9
OFF
ON
10
OFF
ON
11
OFF
ON
12
OFF
ON
13
OFF
ON
14
OFF
ON
15
OFF
ON
2
OFF
ON
3
OFF
ON
4
OFF
ON
5
OFF
ON
6
OFF
ON
7
System controller
A-control remote controller
Group A Group B Group C
A-control remote controller
TB5
A-control remote controller
Refrigerant address 00
M-NET address 01
Refrigerant address 00
M-NET address 02
Refrigerant address 01
M-NET address 03
Refrigerant address 00
M-NET address 04
Power supply unit for transmission wire
A-control remote controller
A-control remote controller
TB5
Group A Group B
Refrigerant address 00
M-NET address 01
Refrigerant address 01
M-NET address 02
Refrigerant address 00
M-NET address 04
Refrigerant address 01
M-NET address 03
Refrigerant address 02
M-NET address 05
System controller
Power supply unit for transmission wire
M-NET wiring
(1) Use 2-core x 1.25mm
2
shield wire for electric wires.
(Excluding the case connecting to system controller.)
(2) Connect the wire to the M-NET terminal block.Connect one core of the
transmission wire (non-polar) to Aterminal and the other to B. Peel the shield wire, twist the shield part to a string and connect it to S terminal.
(3) In the system which several outdoor units are being connected, the terminal
(A, B, S) on M-NET terminal block should be individually wired to the other
M-NET terminal block
ABS
Transmission
wire
Ground wire
Shield part
outdoor unit’s terminal, i.e. Ato A, B to B and S to S.In this case, choose one of those outdoor units and drive a screw to fix an ground wire on the plate as shown on the right figure.
2-2-1. M-NET address setting
In A-control models, M-NET address and refrigerant address should be set only for the outdoor unit. Similar to Free Combo system, there is no need to set the address of outdoor unit and remote controller. To construct a central control system, the setting of M-NET address should be conducted only upon the outdoor unit. The setting range should be 1 to 50 (the same as that of the indoor unit in Free Combo system), and the address number should be consecutively set in a same group.
Address number can be set by using rotary switches (SW11 for ones digit and SW12 for tens digit), which is located on the M-NET p.c. board of outdoor unit. (Factory setting: all addresses are set to “0”.)
2-2-2. Refrigerant address setting
In case of multiple grouping system (multiple refrigerant circuits in one group), indoor units should be connected by remote controller wiring (TB5) and the refrigerant address needs to be set. Leave the refrigerant addresses to “00” if the group set­ting is not conducted. Set the refrigerant address by using DIP SW1-3 to -6 on the outdoor controller board. [Factory setting: all switches are OFF. (All refrigerant addresses are “00”.)]
2-2-3. Regulations in address settings
In case of multiple grouping system, M-NET and refrigerant address settings should be done as explained in the above sec­tion. Set the lowest number in the group for the outdoor unit whose refrigerant address is “00” as its M-NET address.
w Refrigerant addresses can be overlapped if they are in the different group.
w In group B, M-NET address of the outdoor unit whose refrigerant address is “00” is not set to the minimum in the group. As
“3” is right for this situation, the setting is wrong. Taking group A as a good sample, set the minimum M-NET address in the group for the outdoor unit whose refrigerant address is “00”.
5
3 WIRING DIAGRAM
[Servicing] Fasten terminal of the terminal board "TB4" equips lock system.
To remove the fastened terminal, pull it while pressing the protruding portion (locking lever) of the terminal. The fastened terminal protruding portion should face upward.
NOTES:
1.Since the outdoor side electric wiring may change be sure to check the outdoor unit electric wiring for servicing.
2.Indoor and outdoor connecting wires are made with polarities, make wiring matching terminal numbers (S1,S2,S3).
3.Symbols used in wiring diagram above are, :Connector, :Terminal (block).
Please set the voltage using the remote controller. For the setting method, please refer to the indoor unit Installation Manual.
TO OUTDOOR UNIT
C
TB4
H2
5
GRILLE
MV
MV
MV
MV
5
5
5
5
TRANSMISSION WIRES DC12V
MODELS
Manufacture
Service board
MODELS
Manufacture
Service board
SW1
BLK
BLK
BLK
BLK
BLK
BLK
BLU
BLU
TH5
12
PIPE CN29 (BLK)
REMOCON CN22 (BLU)
WIRELESS CN90 (WHT)
SW1
SW2
SWE
VANE CN6V (WHT)
POWER CN03 (RED)
POWER CN2D (WHT)
LIQUID CN21 (WHT)
INTAKE CN20 (RED)
D.SENSOR CN31 (WHT)
D.HEATER CNC (RED)
D.U.M CNP (BLU)
FAN (WHT)
BRN
ORN
YLW
CONTROLLER BOARD CN02 (WHT)
OUTDOOR UNIT CN01 (BLU)
CN2S(WHT)
BLK
WHT
YLW
ORN
BRN
YLW
YLW
YLW
YLW
BLK
RED
WHT
CNB
W.B
LED1
LED2
BZ
RU
SW1 SW2
X4
X4
J15
J22J21 J24J23
OFF
ON
OFF
ON
4321
4321
J21J22J23J24
PLA-RP3AA PLA-RP3AA
1
PLA-RP4AA PLA-RP4AA
1
PLA-RP5AA
1
PLA-RP6AA PLA-RP6AA
1
R.B
9
X1
X1
5
31
CN32
CN2LCN41
123
12315
TH1
2
TB5
1
12 TB6
CN2
TH2
DS
3 2 1
DC14V
1 2 3
12
J11
J12
J13
J14
2
121
LED1LED2LED3
ZNR
DP
3
FC
531
1
1
2
ON OFF
J21
J22
J23
J24
C
MF
I.B
321
P.B
F1
TB4
S1 S2 S3
PLA-RP3,4,5,6AA PLA-RP3,4,5,6AA
1
1
J11J12J13J142J15
345
ON
OFF
SW2
MODELS
Manufacture
Service board
J22J21 J24J23
OFF
ON
OFF
ON
4321
4321
J21J22J23J24
PLA-RP5AA
10
5
9
8
4
7
6321
123
CONNECTOR (PROGRAM TIMER) TRANSMISSION LINE)
TERMINAL BLOCK (REMOTE CONTROLLER
REMOTE CONTROLLER BOARD
(0:/15k, 25:/5.4k DETECT)
COND./EVA. TEMPERATURE THERMISTOR
(0:/15k, 25:/5.4k DETECT)
PIPE TEMPERATURE THERMISTOR/LIQUID
(0:/15k, 25:/5.4k DETECT)
ROOM TEMPERATURE THERMISTOR
TRANSMISSION LINE)
TERMINAL BLOCK (REMOTE CONTROLLER
TERMINAL BLOCK (INDOOR/OUTDOOR CONNECTING LINE)
CN2 TB6
R.B
TH5
TH2
TH1
TB5
TB4
DEW PREVENTION HEATERH2
W.B
SYMBOL NAME
WIRELESS REMOTE CONTROLLER BOARD RECEIVING UNIT BUZZER
LED (HOT ADJUST) SWITCH (HEATING ON/OFF)
LED (RUN INDICATOR)
BZ LED1
RU
LED2 SW1 SW2
SWITCH (COOLING ON/OFF)
SYMBOL
SYMBOL
NAME
NAME
I.B
INDOOR POWER BOARD FUSE (4A) VARISTOR
INDOOR CONTROLLER BOARD CN2L CN32 CN41 SW1 SW2 SWE X1 X4 FC
CONNECTOR (LOSSNAY)
CONNECTOR (REMOTE SWITCH)
CONNECTOR (HA TERMINAL-A)
JUMPER WIRE (MODEL SELECTION)
JUMPER WIRE (CAPACITY CORD)
SWITCH (EMERGENCY OPERATION)
RELAY (DRAIN PUMP)
RELAY (FAN MOTOR)
FAN PHASE CONTROL
C
CAPACITOR (FAN MOTOR)
MF
FAN MOTOR
DP DS DRAIN SENSOR
P.B
ZNR
F1
DRAIN-UP MACHINE
LED1 LED2
POWER SUPPLY (I.B)
POWER SUPPLY (I.B)
MV
VANE MOTOR
LED3
TRANSMISSION (INDOOR-OUTDOOR)
[LEGEND]
PLA-RP3AA PLA-RP4AA PLA-RP5AA PLA-RP6AA PLA-RP3AA1 PLA-RP4AA1 PLA-RP5AA1 PLA-RP6AA1 PLA-RP3AA.UK PLA-RP4AA.UK PLA-RP5AA.UK PLA-RP6AA.UK PLA-RP3AA1.UK PLA-RP4AA1.UK PLA-RP5AA1.UK PLA-RP6AA1.UK
6
PEA-RP3EA.TH-A PEA-RP5EA.TH-A
TO OUTDOOR UNIT
12
TB6
R.B
562341
PIPE TEMPERATURE THERMISTOR/LIQUID (0˚C/15k, 25˚C/5.4k DETECT)
COND./EVA. TEMPERATURE THERMISTOR (0˚C/15k, 25˚C/5.4k DETECT)
ROOM TEMPERATURE THERMISTOR (0˚C/15k, 25˚C/5.4k DETECT)
TH5
TH2
TH1
CN24
NAME
SYMBOL
NAME
SYMBOL SYMBOL
NAME
CN2
R.B
CONNECTOR(PROGRAM TIMER)
REMOTE CONTROLLER BOARD
TERMINAL BLOCK(REMOTE CONTROLLER TRANSMISSON LINE)
TB6
RELAY(FAN MOTOR)
X6
X5
X4
SWE
SW2
SW1
JUMPER WIRE(MODEL SELECTION) JUMPER WIRE(CAPACITY CORD) SWITCH(EMERGENCY OPERATION) RELAY(FAN MOTOR) RELAY(FAN MOTOR)
LED3
LED2
POWER SUPPLY(R.B) TRANSMISSOION(INDOOR • OUTDOOR)
I.B
CN2L
CN41
CN32
LED1
INDOOR CONTROLLER BOARD CONNECTOR(LOSSNAY)
CONNECTOR(HA TERMINAL-A)
CONNECTOR(REMOTE SWITCH))
POWER SUPPLY(I.B)
FUSE(4A)
INDOOR POWER BOARD
VARISTOR
P.B
F1 ZNR
CAPACITOR(FAN MOTOR) FAN MOTOR
MF
TB4
TERMINAL BLOCK (INDOOR/OUTDOOR CONNECTING LINE)
C
J21J22J23J24
J21J22J23J24
J21J22J23J24
J24J23J22
1
BLU
2
3 2 1
CN31
2 1
2 1
1
2
1 2
J24
J23
J22
P.B
ZNR
X4X5
X6 X5
X6
1357
RED
C
ORN
MF
1.Since the outdoor side electric wiring may change be sure to check the outdoor unit electric wiring for servicing.
2.Indoor and outdoor connecting wires are made with polarities,make wiring matching terminal numbers(S1,S2,S3).
3.Symbols used in wiring diagram above are, :Connector, :Terminal (block).
FAN (WHT)
1.When pressing the CHECK switch twice on the remote controller,the unit changes to the self-diagnosis mode and will display the check code by LED(light Emitting Diode) Refer to the right table for the check codes and abnormarities.
LED3 LED2 LED1
INDOOR UNIT
TRANSMISSION WIRE DC12V
OFF
ON
4321
Manufacture
<For manufacture>
SW1
[Self diagnosis]
[NOTES]
J21
OFF
ON
SWE
SW2
WIRELESS
INTAKE CN20 (RED)
LIQUID CN21 (WHT)
REMOCON CN22 (BLU)
CN90 (WHT)
POWER CN2D (WHT)
POWER CN03 (RED)
S3
S2
S1
F1
OUTDOOR CN01(BLU)
3
2
1
CONT.BOARD CN02(WHT)
CN2S(WHT)
DC14V
1
2
3
2 1
TH1
CN2
TB5
I.B
TH2
513
CN41
CN2L
CN32
X4
BLK
BLU
BRN
WHT
YLW
ORN
BRN
WHT
BLK
YLW ORN BRN
SW1
J11
J12
J13
J14
J15
TB4
TH5
1
2
PIPE CN29 (BLK)
BLU
SW2
MODELS
J14J13J12J11 J15
Service board
OFF
ON
4321
OFF
ON
4321
J21
OFF
ON
4321
3EA
4EA
5EA
6EA
123 5
ON
OFF
4
<For service board>
PEA-RP4EA.TH-A PEA-RP6EA.TH-A
7
PEAD-RP3EA.UK PEAD-RP4EA.UK PEAD-RP5EA.UK PEAD-RP6EA.UK PEAD-RP3EA1.UK PEAD-RP4EA1.UK PEAD-RP5EA1.UK PEAD-RP6EA1.UK
8
PUHZ-RP3VHA PUHZ-RP3VHA-A
9
PUHZ-RP4VHA PUHZ-RP5VHA PUHZ-RP6VHA PUHZ-RP4VHA-A PUHZ-RP5VHA-A PUHZ-RP6VHA-A
10
4
Measurement item
COOL: 2.3 ~ 3.0 HEAT: 2.0 ~ 3.2
0.55 ~ 1.0 50 ~ 100
-2 ~ +18
COOL: 27: HEAT: 20:
COOL: 8 ~ 20
HEAT: 30 ~ 50
COOL: 35 HEAT: 7
COOL: 40 ~ 50 HEAT: 0 ~ 5
Measurement method, remarks
Connect the pressure gauge to the high-pressure check valve.
Connect the pressure gauge to the low-pressure check valve.
Measured with piping surface thermometer. Measured with piping surface thermometer.
Can be displayed on remote controller.
Measured with piping surface thermometer. Measured with piping surface thermometer.
High pressure (MPa) Low pressure (MPa) Discharge pipe temperature (:) Suction pipe temperature (:) Indoor intake temperature (:) Indoor outlet temperature (:)
Outdoor intake temperature (:) Outdoor outlet temperature (:)
Pressure/temperature near JIS standard operating conditions
A
B
C
D
E
F
G
H
Notes : The operation statuses vary depending on the compressor's operating frequency because units are inverter-type.
Outdoor heat exchanger
Stop valve (with service port)
Power receiver
Linear expansion valve B Linear
expansion valve A
4-way valve
Compressor
Ball valve
Indoor heat
exchanger
A
B
C
D
Overload operation
Standard operation
Permissible operation range Normal operation range
0 0.2 0.4 0.6 0.8 1 1.2
Suction pressure (MPa)
Discharge pressure (MPa)
4.5 4
3.5 3
2.5 2
1.5 1
0.5 0
REFRIGERANT SYSTEM DIAGRAM
4-1. Checking operation statuses PUHZ-RP • HA
4-1-1. Measurement points and items
•The table and diagrams below show the measurement item for each measurement point, and the pressure and temperature near the ISO T1 standard operating conditions.
•Measure the temperature and pressure of each part by following the descriptions in the table.
•Measurement time: Be sure to wait until the refrigerant circuit has stabilized (30 minutes to 1 hour) before taking measurements.
4-1-2. Operation pressure ranges
11
4-2. Refrigerant System Diagram
Pipe temperature thermistor/liquid (TH2)
Distributor with strainer #50
Condenser/evaporator temperature thermistor (TH5)
Room temperature thermistor (TH1)
Refrigerant flow in cooling Refrigerant flow in heating
Strainer #50
Strainer #50
Heat exchanger
Refrigerant GAS pipe connection (Flare)
Refrigerant LIQUID pipe connection (Flare)
PLA-RP3AA PLA-RP4AA PLA-RP5AA PLA-RP6AA PLA-RP3AA1 PLA-RP4AA1 PLA-RP5AA1 PLA-RP6AA1 PLA-RP3AA.UK PLA-RP4AA.UK PLA-RP5AA.UK PLA-RP6AA.UK PLA-RP3AA1.UK PLA-RP4AA1.UK PLA-RP5AA1.UK PLA-RP6AA1.UK PEA-RP3EA.TH-A PEA-RP4EA.TH-A PEA-RP5EA.TH-A PEA-RP6EA.TH-A PEAD-RP3EA.UK PEAD-RP4EA.UK PEAD-RP5EA.UK PEAD-RP6EA.UK PEAD-RP3EA1.UK PEAD-RP4EA1.UK PEAD-RP5EA1.UK PEAD-RP6EA1.UK
12
Distributor
Thermistor TH7 (Outdoor)
Heat exchanger
Refrigerant GAS pipe connection(5/8F)
Refrigerant LIQUID pipe connection(3/8F)
Stop valve (with service port)
Strainer #100
Power receiver
Linear expansion valve B
Linear expansion valve A
Strainer #100
Strainer #100
Strainer #100
Thermistor TH6 (Outdoor 2-phase pipe)
Thermistor TH3 (Outdoor pipe)
Service port (Low pressure)
Service port (High pressure)
High pressure switch 63H
Bypass valve
Replace filter
Thermistor TH4 (Discharge)
Compressor
Strainer #50
4-way valve
Capillary tube (O.D.4.0OI.D.3.0OL200)O2pcs
Strainer #100
Strainer #100
Low pressure switch 63L
Muffler
Ball valve
Restrictor valve
PUHZ-RP3VHA
Distributor
Thermistor TH7 (Outdoor)
Heat exchanger
Refrigerant GAS pipe connection(5/8F)
Refrigerant LIQUID pipe connection(3/8F)
Stop valve (with service port)
Strainer #100
Power receiver
Linear expansion valve B
Linear expansion valve A
Strainer #100
Strainer #100
Strainer #100
Thermistor TH6 (Outdoor 2-phase pipe)
Thermistor TH3 (Outdoor pipe)
Service port (Low pressure)
Service port (High pressure)
High pressure switch 63H
Bypass valve
Oil separator
Thermistor TH4 (Discharge)
Muffler
Strainer #50
4-way valve
Compressor
Ball valve
Capillary tube O.D.4.0OI.D.2.4OL500
Capillary tube O.D.2.5OI.D.0.6OL1000
PUHZ-RP3VHA-A
PUHZ-RP4VHA PUHZ-RP5VHA PUHZ-RP6VHA PUHZ-RP4VHA-A PUHZ-RP5VHA-A PUHZ-RP6VHA-A
13
4-3. Applicable extension pipe for each model
<Table 4>
Additional refrigerant charging amount for liquid pipe which is one size larger than
standard diameter
[12.7 [12.7
RP3
RP4 — RP6
Liquid pipe dia
Chargeless
30m 50m
100 g addition per 1 m when pipe length exceeds 20 m 100 g addition per 1 m when pipe length exceeds 20 m
20m 20m
Max. pipe length
Additional refrigerant charging amount
15
30m or
above
31 — 40m
0.6Kg
0.6kg
10m or below
41 — 50m
1.2Kg
1.2kg
51 — 60m
1.8kg
61 — 75m
2.4kg
<Table 2> Additional refrigerant charging amount for pipe of standard diameter
<Table 3>
Outdoor unit
Permitted
pipe length
Additional refrigerant charging amount for pipe
length exceeding 30 m (kg)
PUHZ-RP3
PUHZ-RP4 — RP6
Outdoor unit
PUHZ-RP3
PUHZ-RP4 — RP6
Number of
bends
Height
difference
50m or below 75m or below
Permitted
pipe length
50m or below
75m or below
3.1
5.1
11 — 20m 21 — 30m
3.3
5.3
3.5
5.5
31 — 40m
4.1
0.6
6.1
0.6
4.7
1.2
6.7
1.2
— —
7.3
1.8
— —
7.9
2.4
41 — 50m 51 — 60m 61 — 75m
Additional refrigerant charging amount for recharging (above) and pipe length exceeding 30m (below) (kg)
Liquid
pipe
(mm)
Gas pipe
(mm)
[6.35
[9.52 [12.7
[9.52
OD
Thick-
ness
OD
Thick-
ness
RP3 RP4 RP5 RP6
t0.8
t0.8
[12.7
t0.8
[15.88
t1.0
[12.7
t0.8
[15.88
t1.0
[19.05
t1.0
[15.88
t1.0
[19.05
t1.0
t0.8
t0.8
: Normal piping : It can be used, however, additional refrigerant charge is required when the pipe length exceeds 20m. Refer to table 4. : It cannot be used. : It can be used. : It can be used, however, the capacity is lowered. Refer to (C) Capacity correction.
<Table 1> Pipe length for 1:1 system
*1: Set DIP SW8-1 on outdoor unit controller board to ON. *2: The maximum length is 50 m in case of using existing pipes. *3: The height difference between indoor and outdoor unit should be kept within 30 m for all models.
[Marks in the table above]
10m 30m 30m
50m 50m 50m
10m
50m
(*1)
75m
(*2)
50m
75m
(*2)
75m
(*2)
50m
(*1)
50m
(*1)
50m
(*1)
50m
(*1)
50m
(*1)
4-3-1. 1:1 system (a) Pipe length
(b) Adjusting the amount of refrigerant
Additional refrigerant charge is not necessary for the pipe length up to 30 m. When the pipe length exceeds 30 m or service
(refrigerant replacement) is performed, charge proper amount of refrigerant for each pipe length referring to table below. Use refrigerant R410A. Use charge hose exclusive for R410A.
When charging additional refrigerant, charge the refrigerant from low-pressure side of the port valve using a safety charger.
Make sure that air purge for this unit at refrigerant replacement is performed from both high-pressure check valve and ser-
vice port. (If air purge is performed only from one of them, air in not purged enough.)
When replacing refrigerant, charge the refrigerant from service port. When charged refrigerant is less than specified amount, charge the refrigerant again from low pressure side of the port valve using a safety charger.
Tighten the service port cap (nut) of stop valve firmly. The tightening torque is 12 to 16 N·m. (For the prevention of slow-leak)
Check additional refrigerant charging amount referring to table 4 when liquid pipe is one size larger than standard diameter,
and table 2 when the pipe is standard diameter.
14
100
95
90
85
80
75
70
5 101520253035404550556065707580
Note: The permitted pipe length is up to 55m for RP3 model.
RP3 model
RP4 model
Heating RP3, 4, 5 and 6 models (Up to 55m for RP3 model)
RP5 model
RP6 model
Cooling
Capacity ratio [%]
Corrected pipe length
(c) Capacity correction
5 10152025303540455055
80
Capacity ratio [%]
Corrected pipe length
85
90
95
100
Heating RP3
Cooling RP3
Cooling Heating
Cooling and heating capacity is lowered according to pipe length. Capacity can be obtained by referring to the capacity curves below. When the diameter of gas pipe is one size smaller than standard diameter, cooling capacity is lowered com­paring to the standard diameter. The lowered capacity can be obtained by referring to capacity curves for gas pipe which is one size smaller than standard size.
Corrected pipe length (m) = actual pipe length (m) + number of bends x 0.3 (m)
11
Capacity curves for PUHZ-RP • HA model <Standard size>
22
Capacity curve for PUHZ-RP3 model
<When gas pipe is one size smaller than standard size>
33
When gas pipe is one size larger than standard size for PUHZ-RP4, 5 and 6.
1 Capacity can be obtained by referring to capacity curves of standard size.
15
4-3-2. Synchronized twin and triple
(a) Pipe length
Please note that refrigerant piping length, bend number and height difference of indoor units are specified for each unit combination. Note: Be sure to use our Multi-distributor for distributing pipe to use existing piping.
<Table 5>
Synchronized twin
Outdoor
unit
<Table 6>
Outdoor
unit
Note 1: If total piping length exceeds charge-less piping length of 30 m, charge additional refrigerant according to the table 7.
PUHZ-RP3VHA PUHZ-RP4~6VHA
Synchronized twin
PUHZ-RP6VHA 30 m or less70 m or less
Permitted total piping length A + B + C
50 m or less 75 m or less
Permitted total piping length A + B + C + D
Chargeless piping length A + B + C
30 m or less
Charge-less piping length A + B + C + D
Indoor unit’s height difference [B and C]
8 m or less
Indoor unit’s height difference
[B and C] [C and D] [B and D]
8 m or less
Bend number
w 2
15 at most
Bend number
w 2
15 at most
<Table 7>
A + B + C (+D)
Outdoor unit
30 m or less PUHZ-RP3VHA PUHZ-RP4~6VHA
Note 2: Bends number (w 2) should be within 8 for each combination, A + B, A +C and A + D, and 15 in all. Note 3: Height difference between indoor and outdoor unit is referred to no matter which unit is located higher or lower.
<Table 8> Pipe length for twin of RP 3 - 6 (Piping length: A + B + C)
RP3 Twin (RP1.6✕2)
Liquid [6.35
Gas [12.7 Branch pipe diameter [B and C]
<Table 9> Pipe length for triple of RP6 (Piping length: A + B + C + D)
Branch pipe diameter [B,C and D]
Liquid [6.35 Gas [12.7
Liquid [9.52 Gas [15.88
Liquid [12.7 Gas [19.05
Liquid [6.35 Gas [12.7
Liquid [9.52 Gas [15.88
Liquid [12.7 Gas [19.05
Main pipe diameter [A]
Liquid [9.52
Gas [15.88
75 m(2)
50 m
Not required
Liquid [9.52 Gas [15.88
50 m
50 m
Liquid [12.7 Gas [19.05
50 m(1)
50 m(1)
Additional refrigerant to be charged (kg)
31 - 40 m 41 - 50 m 51 - 60 m 61 - 75 m
0.6
RP4 Twin (RP22) RP5 T win (RP2.52) RP6 Twin (RP3✕2)
Liquid [9.52 Gas [15.88
75 m(2)
50 m
1 ··· Set DIP SW8-1 on outdoor unit control circuit board to ON.2 ··· When using existing piping, pipe length should be 50 m at most.3 ··· Height difference between indoor and outdoor unit should be
kept within 30 m in every case. [Marks in table]
··· Normal piping
··· It can be used with some changes of piping length and the amount of refrigerant to be charged. ··· It cannot be used.
1.2
Main pipe diameter [A]
Liquid [12.7 Gas [19.05
50 m(1)
50 m(1)
1.8 2.4
Liquid [9.52 Gas [15.88
75 m(2)
Liquid [12.7 Gas [19.05
50 m(1)
w Charge additional refrigerant from the check valve connected to the pipe of low-pressure side in indoor unit.
Liquid [9.52 Gas [15.88
75 m(2)
Liquid [12.7 Gas [19.05
50 m(1)
16
Synchronized twin
Synchronized triple
Indoor unit
Optional distributing pipe
1 m or less
Multi-distributor
30 m or less
Branch pipe B
Branch pipe C
Main pipe A
Indoor unit
Outdoor unit
Indoor unit
Optional distributing pipe
1 m or less
Multi-distributor
30 m or less
Branch pipe B
Branch pipe C
Branch pipe D
Main pipe A
Indoor unit
Indoor unit
Outdoor unit
1. Keep Stop valve in outdoor unit fully closed (as it is shipped), and after completing refrigerant piping connection, conduct air purge from service port of stop valve at outdoor unit.
2. After air purging, make the valve rod of stop valve at outdoor unit fully open. Now refrigerating cycle is complete between indoor and outdoor unit. Handle stop valve following the indication on outdoor unit.
Caution:
• Be sure to apply refrigerating oil to flare sheet face. Never apply it to screws. (As it causes flare nut loosening.)
• Use double spanner for piping connection.
• Be sure to check gas leak by using leak detector or soapy water.
• Use attached parts for refrigerant piping to provide correct insulation to the connection of indoor unit side in accordance with attached explanation sheet.
• Be sure to provide anoxidized brazing.
(b) Adjusting the amount of refrigerant oil
(i) In case of RP 3 twin
Check the additional refrigerant oil to be charged referring to table 2 when using pipe of size referred in table 8.
(ii) In case of RP4 - 6 twin or RP6 triple
When using liquid pipe one size larger than standard diameter for main pipe A, calculate the amount of additional refrigerant oil referring to 2 below.
1 When using piping of standard diameter or gas pipe one size larger than standard diameter for main pipe A.
Check the additional refrigerant oil to be charged referring to table 2 like 1:1 system.
2 When using liquid pipe one size larger than standard diameter for main pipe A.
[In case of RP4-6 using liquid pipe of [12.7]
• When total length of extension pipe (main pipe and branch pipe) is less than 20 m. No adjustment is required for refrigerant oil. (Chargeless)
• When total length of extension pipe (main pipe and branch pipe) is more than 20 m. Calculate the amount of additional refrigerant oil, referred to as W (g) in the following, using the equation below and add proper amount of refrigerant oil. If W is less than or equal to 0, no additional charge is required. (Chargeless)
[Additional refrigerant oil] W (g) = {100(g) L1} + {60(g) L2} + {30(g) L3} - 2000(g)
Note: Put “0” in L1-3 if it is not used. L1: Liquid pipe length of [12.7 (m)
L2: Liquid pipe length of [9.52 (m) L3: Liquid pipe length of [6.35 (m)
(c) Capacity correction
Apply pipe length between indoor and outdoor unit which is the longest of all for the calculation of capacity lowering according to each pipe length.
17
5
Parts name Check points
Disconnect the connector then measure the resistance using a tester. (Surrounding temperature 10:~30:)
Drain sensor
(Refer to below for a detail.)
(Refer to below for a detail.)
Room temperature thermistor (TH1)
Pipe temperature thermistor (TH2)
Condenser/evaporator temperature thermistor (TH5)
1 2 3
Normal
4.3k"~9.6k"
Abnormal
Open or short
Abnormal
Open or short
Normal
0.6k"~6.0k"
Measure the resistance between the terminals using a tester. Measure the resistance after 3 minutes have passed since the power supply was intercepted. (Surrounding temperature 0:~60:)
-200 20406080
< Thermistor for drain sensor >
Temperature (:)
0
1
2
3
4
5
6
7
8
9
10
Resistance (K")
HOW TO CHECK THE PARTS
5-1. INDOOR UNIT
• Common parts
<Thermistor Characteristic graph>
Thermistor for lower temperature
Room temperature thermistor(TH1) Pipe temperature thermistor(TH2) Condenser/evaporator temperature thermistor(TH5)
Thermistor R0=15k±3% Fixed number of B=3480kΩ ±2%
Rt=15exp { 3480( ) }
1
273+t
0: 15k 10: 9.6k 20: 6.3k 25: 5.2k 30: 4.3k 40: 3.0k
Drain sensor
1
273
< Thermistor for lower temperature >
50
40
30
20
Resistance (K")
10
0
-20 -10 0 10 20 30 40 50 Temperature (:)
Thermistor R0=6.0k±5% Fixed number of B=3390kΩ ±2%
Rt=6exp { 3390( ) }
0: 6.0k 10: 3.9k 20: 2.6k 25: 2.2k 30: 1.8k 40: 1.3k
1
273+t
1
273
18
Parts name Check points
Measure the resistance between the terminals using a tester. (Winding temperature 20:)
Fan motor (MF)
Brown
White
Blue
Red
Orange
Black
Protector (PEA-RP3,4,5EA) OPEN :135: CLOSE:86i15:
(PEA-RP6EA) OPEN :150: CLOSE:96i15:
Abnormal
Open or short
White-Black
Black-Blue
Blue-Brown
Brown-Red
Motor terminal
or
Relay connector
Normal
PEA-
RP3EA.TH-A RP4EA.TH-A RP5EA.TH-A RP6EA.TH-A
28.6"
12.5"
4.3"
23.6"
20.6"
8.1"
3.2"
16.0"
15.3"
5.1"
2.7"
14.5"
10.2"
5.2"
3.1"
12.1"
Parts name Check points
Measure the resistance between the terminals using a tester. (Winding temperature 20:)
Fan motor (MF)
PEAD-RP4,5,6EA
(1)
.UK
PEAD-RP3EA(1).UK
White
Blue
Red
Gray
Black
Protector OPEN :135: CLOSE:86i15:
Blue
WhiteRed
Gray
Black
Protector OPEN :150: CLOSE:96i15:
Abnormal
Open or short
Gray-Black
(White or Red open)
Blue-Black Black-Red
(White or Red open)
Gray-Red
(White or Red open)
Motor terminal
or
Relay connector
Normal PEAD-
RP4EA
(1).UK
RP5EA
(1)
.UK RP6EA
(1)
.UK
24.76"
4.78"
18.99"
36.63"
10.27"
2.11"
20.75"
25.44"
Abnormal
Open or short
Gray-Black
(White or Red open)
Black-Blue
(White or Red open)
Blue-Red
(White or Red open)
Motor terminal
or
Relay connector
Normal
PEAD-RP3EA
(1).UK
43.5"
14.74"
57.5"
PLA-RP3AA PLA-RP4AA PLA-RP5AA PLA-RP6AA PLA-RP3AA
1 PLA-RP4AA1 PLA-RP5AA1 PLA-RP6AA1
PLA-RP3AA.UK PLA-RP4AA.UK PLA-RP5AA.UK PLA-RP6AA.UK PLA-RP3AA
Parts name Check points
Vane motor
Fan motor
Relay connector
1
2
3
Protector OPEN :130: CLOSE:80i20:
Drain pump
Red
Red
1.UK PLA-RP4AA1.UK PLA-RP5AA1.UK PLA-RP6AA1.UK
Measure the resistance between the terminals using a tester. (Surrounding temperature20:)
Normal Abnormal
15k" Open or short
Measure the resistance between the terminals using a tester. (Winding temperature 20:)
Red
White
Black
1 2 3
Motor terminal
or
Relay connector
Red-Black
White-Black
PLA-RP3AA PLA-RP4,5,6AA
87.2"
104.1"
Normal
28.7"
41.6"
Abnormal
Open or short
Measure the resistance between the terminals using a tester. (Winding temperature 20:)
1 2
Normal Abnormal
290" Open or short
PEA-RP3EA.TH-A PEA-RP4EA.TH-A PEA-RP5EA.TH-A PEA-RP6EA.TH-A
PEAD-RP3EA.UK PEAD-RP4EA.UK PEAD-RP5EA.UK PEAD-RP6EA.UK PEAD-RP3EA1.UK PEAD-RP4EA1.UK PEAD-RP5EA1.UK PEAD-RP6EA1.UK
19
U-V
U-W
W-V
Unit
Compressor model
Winding
Resistance
( " )
ANV33FDAMT
(at 20°C)
0.266
0.266
0.266
TNB220FMBH
0.865 ~ 0.895
0.865 ~ 0.895
0.865 ~ 0.895
PUHZ-RP4,5,6VHA
PUHZ-RP3VHA
5-2. OUTDOOR UNIT
4
6
2
3
1 2 3 4 5 6
5
1
M
Blue
Brown
Yellow
Orange
Red
White
Parts name
Check points
Disconnect the connector then measure the resistance using a tester. (Surrounding temperature 10:~30:)
Disconnect the connector then measure the resistance using a tester. (
Winding temperature 20
:)
Thermistor (TH3) <Outdoor pipe>
Thermistor (TH4) <Discharge>
Thermistor (TH6) <Outdoor 2-phase pipe>
Thermistor (TH7) <Outdoor>
Thermistor (TH8) <Heat sink>
Normal
160k"~410k"
4.3k"~9.6k"
39k"~105k"
TH4 TH3 TH6 TH7 TH8
Abnormal
Open or short
Normal
(1) - (6)
Red - White
(1) - (4)
Red - Orange
(2) - (5)
Brown - Yellow
(2) - (3)
Brown - Blue
Abnormal
46±4"
Measure the resistance between the terminals using a tester. (Surrounding temperature 20
:
)
Solenoid valve coil <Four-way valve> (21S4)
Pin number of relay connector is different from that motor connector
Motor for compressor (MC)
Linear expansion valve ( LEV(A),LEV(B) )
Normal
Abnormal
Open or short
PUHZ-RP3VHA PUHZ-RP4, 5, 6VHA
Open or short
Measure the resistance between the terminals using a tester. (Surrounding temperature 20
:
)
Normal
1197±10"
Abnormal
Open or short
Solenoid valve coil <Bypass valve> (SV)
Measure the resistance between the terminals using a tester. (Winding temperature 20:)
Fan motor(MF1,MF2)
Normal
15.1±0.5"
2350±170" 1370±100"
PUHZ-RP3VHA PUHZ-RP4, 5, 6VHA
0.865"~0.895" 0.266"
Measure the resistance between the terminals using a tester. (Winding temperature 20
:
)
Normal
Abnormal
Open or short
Relay connector
Abnormal
Open or short
Red — Black Black — White White — Red
Red
W
V U
W
V
U
White Black
PUHZ-RP3VHA PUHZ-RP4VHA PUHZ-RP5VHA PUHZ-RP6VHA PUHZ-RP3VHA-A PUHZ-RP4VHA-A PUHZ-RP5VHA-A PUHZ-RP6VHA-A
5-3. COMPRESSOR TECHNICAL DATA
20
HOW TO CHECK THE COMPONENTS
0
10
20
30
40
50
-20 -10 0 10 20 30 40 50 Temperature (:)
Resistance (K")
200
150
100
50
0
25 50 75 100 125
Temperature (:)
Resistance (K")
500
400
300
200
100
0
25
50 75 100 120
Temperature (:)
Resistance (K")
<Thermistor feature chart>
Low temperature thermistors
• Thermistor <Outdoor pipe> (TH3)
• Thermistor <Outdoor 2-phase pipe> (TH6)
• Thermistor <Outdoor> (TH7) Thermistor R0 = 15k' ±3%
B constant = 3480k' ±2%
1
R
t =15exp{3480(
0: 15k' 10: 9.6k' 20: 6.3k' 25: 5.2k'
Medium temperature thermistor
• Thermistor <Heat sink> (TH8)
1
273+t – 273
30: 4.3k' 40: 3.0k'
)}
Thermistor R50 = 17k' ±2% B constant = 4150k' ±3%
1
t =17exp{4150(
R
1
273+t – 323
)}
0: 180k' 25: 50k' 50: 17k' 70: 8k' 90: 4k'
High temperature thermistor
• Thermistor <Discharge> (TH4) Thermistor R120 = 7.465k' ±2%
B constant = 4057k' ±2%
1
t =7.465exp{4057(
R 20: 250k'
30: 160k' 40: 104k' 50: 70k' 60: 48k'
1
273+t – 393
70: 34k' 80: 24k' 90: 17.5k' 100: 13.0k' 110: 9.8k'
)}
21
A
B
C
Open
Extra tightning (about 32 pulse)
Pulse number
500 pulse Opening a valve all the way
Close
Valve position (capacity)
LEV
M
1
6
[4
[4
[3
[2
[1
2
1
Red
Brown
Blue
Orange
Yellow
White
3
4
5
6
Connector LEV-A
LEV-B
DC12V
Outdoor controller board
Drive circuit
[3
[2
[1
3
2
5
4
Linear expansion valve
1
ON OFF OFF OFF
ON
ON OFF OFF
OFF
ON OFF OFF
OFF
ON ON
OFF
[1
Output
(Phase)
Output
[2 [3
[4
234
5678
OFF OFF
ON
OFF
OFF OFF
ON ON
OFF OFF OFF
ON
ON OFF OFF
ON
(1) Operation summary of the linear expansion valve.
• Linear expansion valve open/close through stepping motor after receiving the pulse signal from the outdoor controller board.
• Valve position can be changed in proportion to the number of pulse signal. <Connection between the outdoor controller board and the linear expansion valve>
<Output pulse signal and the valve operation>
(2) Linear expansion valve operation
Opening a valve : 8 7 6 5 4 3 2 1 8 Closing a valve : 1 2 3 4 5 6 7 8 1
The output pulse shifts in above order. 1. When linear expansion valve operation stops, all output phase
become OFF.
When the switch is turned on, 700 pulse closing valve signal will
be sent till it goes to
A point in order to define the valve position.
(The pulse signal is being sent for about 20 seconds.) When the valve moves smoothly, there is no noise or vibration
occurring from the linear expansion valve : however, when the pulse number moves from B to A or when the valve is locked, more noise can be heard than normal situation. No noise is heard when the pulse number moves from B to A in case coil is burn out or motor is locked by open-phase.
Noise can be detected by placing the ear against the screw dri-
ver handle while putting the screw driver to the linear expansion valve.
22
(3) How to attach and detach the coil of linear expansion valve
<Composition> Linear expansion valve is separable into the main body and the coil as shown in the diagram below.
Coil
Lead wire
<How to detach the coil>
Hold the lower part of the main body (shown as A) firmly so that the main body does not move and detach the coil by pulling it upward. Be sure to detach the coil holding main body firmly. Otherwise pipes can bend due to pressure.
Stopper
Main body
<How to attach the coil>
Hold the lower part of the main body (shown as A) firmly so that the main body does not move and attach the coil by inserting it downward into the main body. Then securely attach the coil stop­per to pipe B. (At this time, be careful that stress is not added to lead wire and main body is not wound by lead wire.) If the stop­per is not firmly attached to pipe B, coil may be detached from the main body and that can cause defective operation of linear expansion valve. To prevent piping stress, be sure to attach the coil holding the main body of linear expansion valve firmly. Otherwise pipe may break.
B
A
A
Be sure to attach the stopper to pipe B.
23
6 MICROPROCESSOR CONTROL
Standard 1:1 Synchronized twin. Triple
1Unit (indoor/outdoor) power supply L/N 2Connecting line between the indoor and
outdoor; S1/S2/S3, Polarized 3-wire
3Remote controller transmission line; Non
polarezed 2-wire
4Auxiliary heater exclusive power supply; L/N
1Unit (indoor/outdoor) power supply L/N 2Connecting line between the indoor and outdoor; S1/S2/S3, Polarized 3-wire 3Remote controller transmission line; Non polarezed 2-wire 4Auxiliary heater exclusive power supply; L/N
1Unit (indoor/outdoor) power supply L/N 2Connecting line between the indoor and
outdoor; S1/S2/S3, Polarized 3-wire
3Remote controller transmission line; Non
polarezed 2-wire
4Auxiliary heater exclusive power supply; L/N
Remote control main/sub setting necessity (In case of 2 remote controllers)
No setting (initial setting) Refrigerant address setting; SW1; 3~6
Various setting
Remote controller
Main Sub
Indoor unit
Outdoor unit
Remarks
Group control
1
4
2
3
Main
(00)
Outdoor unit; (00)...Refrigerant address
(SW1; 3~6)
Indoor unit; (00)–w
Indoor unit number (auto setting)
Refrigerant address (receiving from the outdoor unit)
Outdoor unit; (00)...Refrigerant address
(SW1; 3~6)
Indoor unit; (00)–w
Indoor unit number (auto setting)
Refrigerant address (receiving from the outdoor unit)
(00)-1 (00)-2 (00)-3
Sub
1
44
222
4
3
Main
(00)
(00)-1 (00)-2 (01)-1
1
(01)
1
(02)
1
44
222
4
(02)-1 (02)-2
4
2
2
4
3
333
(1) Indoor unit number is set automatically (2) When the refrigerant address of the unit is "00", Remote controller is supplied.
Remote control main/sub setting necessity (In case of 2 remote controllers)
No setting No setting
Remote control main/sub setting necessity (In case of 2 remote controllers)
No setting (initial setting) No setting (initial setting)
Various setting
Remote controller
System construction
System construction
Indoor unit
Outdoor unit
Remarks (1) Indoor unit number is set automatically
6-1. System construction
(1) System construction A-control model which just wires the connecting line between the indoor and outdoor unit and supply the power is applicable to any models of standard (1:1), twin and triple. (Refer to 2 Start-up system.)
24
(2) The transmitting specification for “A” control
Cross section
of cable
Round
2.5
2.5
1.5
2.5
3
3
4
4
(50)
2
(45)
3
60 4
Not
applicable
5
Flat
1 : Power supply cords of appliances shall not be lighter than design 245 IEC or 227 IEC.2 : In case that cable with stripe of yellow and green is available.3 : In case of regular polarity connection (S1-S2-S3), wire size is 1.5mm
2
.
4 : In case of regular polarity connection (S1-S2-S3). 5 : In the flat cables are connected as this picture, they can be used up to 80m.
6 : Mentioned cable length is just a reference value.
It may be different depending on the condition of installation, Humidity or materials, etc.
Flat
Round
Wire size
(mm
2
)
Number
of wires
Clockwise : S1-S2-S3 w Pay attention to stripe of yellow and green
Clockwise : S1-S2-S3-Open w Connect S1 and S3 to the opposite angle
Not applicable (Because center wire has no cover finish)
From left to right : S1-Open-S2-S3
Polarity
L(m)
6
(3C Flat cable 2)
S1 S2 S3
1Wiring regulations
Section Communications from remote controllers
The maximum length of
500m 80m (Including the wiring among indoor units
total wiring
The maximum numbers for connection
One remote controller can connect and operate up to 16 indoor units by grouping them. One group can connect up to two remote controllers. 1 Remote controller considers multiplex units as
a single group.
Communications between indoor and outdoor units
in addition to the wiring between indoor and outdoor units)
1
One outdoor unit can connect up to three indoor units.
The cables applicable 0.3mm
2
to 1.25mm
2
Use either flat-type cable (3 cores: {1.6mm or more) or wires in the table below. 2 The diameter of the cables depends on
each unit.
Others The wirings as follows are not allowed:
• The wiring that the indoor units of the same
The core wire connected to terminal S2 shall be placed at the center of flat-type cable.
refrigerant system are connected through TB5.
• The wiring which directly connects the terminals for remote controllers.
2Transmitting specification
Section Communications from remote controllers
Communications between indoor and outdoor units Transmitting speed 83.3 bit/sec. (1 bit = 12ms) 83.3 bit/sec. (1 bit = 12ms) Normal transmission The terminal for remote controller transmits sig-
nals every 7.5 seconds; the indoor unit whose
Outdoor unit transmits signals every 3 seconds; all the connected indoor units respond them.
refrigerant address is “0” responds them. Modulation The waveform modulates at 50kHz. There is no modulation. Detection of abnormal
communication
When transmitting error is detected for three con-
secutive minutes.
When transmitting error is detected for three consecutive minute.
WIRING SPECIFICATIONS FOR 220~240V 50Hz (INDOOR-OUTDOOR CONNECTING CABLE)
25
(3) The waveforms of from remote controller communications
The following graphs are the examples for measuring waveforms on the wirings of remote controlled transmission at the terminal block for remote controller.
a) Ameasuring example in the sequence of startup b) Ameasuring example during normal stop
Transmission from remote controller
Transmission from indoor unit
7.5 seconds
Transmission from remote controller
Transmission from indoor unit
7.5 seconds
5V/div, 1sec/div: 5V/div, 1sec/div:
c) Expanded waveform 1 (signal 111000....) d) Expanded waveform 2 (50Hz carrier)
5V/div, 10msec/div: 5V/div, 2µsec/div:
• During normal operation, the remote controller interactively exchanges signals with the indoor unit of refrigerant address “0”. When the remote controller cannot receive signals from the indoor unit of refrigerant address “0” for 3 minutes, it is considered as abnormal. E0 is displayed on the remote controller as an error.
26
(4) The waveforms of communications between indoor and outdoor units
The following graphs are the examples for measuring waveforms on the wirings of connecting indoor and outdoor units at between S2 and S3 of the outdoor terminal block TB1.
a) Ameasuring example the sequence of startup: 1 b) A measuring example in the sequence of startup: 2
Transmission from indoor unit
Transmission from outdoor unit
10V/div, 500msec/div: 10V/div, 500msec/div:
c) Ameasuring example during normal stop
(When one outdoor unit connects one indoor unit)
Transmission from indoor unit
Transmission from outdoor unit
Transmission from indoor unit
Transmission from outdoor unit
d) Ameasuring example during normal stop
(When one outdoor unit connects two indoor units)
Transmission from indoor unit
Transmission from one indoor unit
Transmission from another indoor unit
10V/div, 500msec/div: 10V/div, 500msec/div:
c) Expanded waveform
10V/div, 50msec/div:
• During normal operation, outdoor unit interactively exchanges signals with all the connected indoor units.
• When outdoor unit cannot receive signals for three minutes from an indoor unit due to any trouble like cable disconnection, it is considered as abnormal and the outdoor unit stops. E8 is displayed on the remote controller. This is to avoid independent operation of indoor units.
27
(5) Start-up system
Power ON
YES
NO
1 Refrigerant address
transmitting
Power supply control
to remote controller
3 Set number of the
connected unit
4 Set number of the
indoor unit
6 Collecting the unit
information
7 Collecting the
operation data
Set up finish
2 Refrigerant
address "0"?
YES
NO
5 Duplication
detection
Example
2 blinking 2 blinkingNot lighted
3 seconds
A control unit is applicable to any models of standard (1:1), twin and triple without switch setting according to carrying out the below process automatically when the power is supplied. When the power is supplied, following processes of 1 Refrigerant address transmitting, 2 Power supply control to remote controller, 3 Set number of the connected unit, 4 Set number of the indoor unit, 5 Duplication detection, 6 Collecting the unit information and 7 Collecting the operation data are carried out as shown on the figure. Also when detecting the duplicated setting in the step 5, back to the first step and reset it.
; Transmitting the switch setting
contents on the outdoor unit remote controller (SW1-3~6)
; Feeding control to remote
controller Feeding the indoor unit of the refrigerant address “0”
EA error if 4 minutes have passed since the power is supplied.
; If there are 2 or more speci-
fied indoor unit, back to the first step.
<<Feature>> A. Start-up time from the second time will be shorter since setting of the number of connected units is memorized once set.
Start-up time can be estimated as following;
•When installing ... 1~2 minutes (Depending the number of connecting units)
•Since the second time .... 20 seconds ~ 1 minute (Depending the number of connecting units)
w When the above processing does not finish, even if 4 minutes have passed, consider the processing an error and
Ea, Eb or Ec will be displayed. However if power is not supplied to the indoor unit due to miss-wiring or looseness of the connecting lines between the indoor and outdoor unit, there will be no display on the remote controller. Also when the data can not be received from the outdoor unit, E6 is displayed on the remote controller after 6 minutes.
B. When replacing the p.c.board, only the unit number which has had it`s p.c.board replaced is reset.
Even if the power supply is reset, the unit number which has not had it`s replaced does not change.
C. Automatic set unit is possible to confirm by blinking the frequency of LED3 in the indoor controller board.
At intervals of approx. 3 seconds, the number of the unit-number blinks.(Example:The unit(unit number:2) blinks twice at 3-second intervals.
; Collecting the vane, louver
information and transmittance to the remote controller.
; Collecting the preceding oper-
ation setting information and transmittance to the remote controller.
EB error if 4 minutes have passed since the power is supplied.
EC error if 4 minutes have passed since the power is supplied.
28
Function/control specifications
Item
Fan
Up/down auto vane
Left/right
Function / specification
swing louver
Drain pump
Number of fan speed Drive method
Provided Swing function Shutter mechanism Moter type
Provided Moter type
4-way ceiling cassette
PLA-RP•AA
4
Pulsation
(AC motor)
Stepping
(12V DC)
— —
Ceiling concealed
PEA-RP•EA
2
Tap-changing
(AC motor)
— — —
— —
Note: The parts marked are optional.
PEAD-RP•EA
2
Tap-changing
(AC motor)
— — —
— —
29
7
Control modes
Control details
1-1. Thermoregulating function (Function to prevent restarting for 3 minutes)
• Room temperature ] desired temperature +1:···Compressor ON
• Room temperature [ desired temperature ···Compressor OFF Crankcase heater: OFF when compressor operates
ON when compressor stopped
(including when thermo is OFF) Crankcase heater switches ON when 220-240V AC current is applied between connectors CH 1 and 2 on the outdoor control board.
1-2. Anti-freezing control Detected condition : When the liquid pipe temperature (TH2 ) or Condenser/ Evaporator temperature (TH5 ) (w3) is 2: or less (w4) in 16
minutes from compressors start up, anti-freezing control starts and the compressor will be suspended.
Released condition : The timer which prevents reactivating is set for 3 minutes, and anti- freezing control is cancelled when any one of the following conditions is satisfied.
1
Liquid pipe temperature (TH2) and Condenser / Evaporator temperature (TH5) turn 10: or above.
2 The condition of the compressor stop has become
complete by thermoregulating, etc.
3 The operation modes became mode other than COOL. 4 The operation stopped.
1-3. Frozen protection Detected condition : 1 When the indoor pipe temperature (TH2 ) or Condenser/
Evaporator temperature (TH5 ) continues -15: for 3 minutes since 3 minutes has passed after the compressor start, the compressor stops and then the mode changes to prevent restarting for 6 minutes. After restarting of 6 minutes, when the indoor pipe temp. (TH2) or Condenser / Evaporator temperature (TH5) continues -15 or less for three minutes again by the time 16 minutes have passed, the frozen protection operates. (P6)
Detected condition : 2
In case the indoor unit continues to be under the anti-freezing control for 9 minutes or more, the unit will be in a state of the suspensive abnormality. Restart the compressor after releasing
the anti-freezing control. The suspensive abnormality will be cancelled if the compressor keeps operating for 20 minutes. However, the suspensive abnormality will turn into the abnormality if the anti-freezing control works again for 9
minutes during that period. On the other hand, the suspensive abnormality will be cancelled if the anti-freezing control works for less than 9 minutes
Released condition : When the operation stops by the remote controller operation.
By the remote controller setting (switch of 4 speeds or 2 speeds) When determining the abnormality of the pipe temp. low speed fan is fixed.
2. Fan
1. Compressor
Remarks
Type
Fan speed notch
[Low] [Mid2] [Mid1] [High]
[Low] [High]
4 speeds type 2 speeds type
Refer to w2. Refer to w3.
w1 The thermoregulating function is provided in the outdoor unit.
The indoor unit transmits the indoor room temperature and set temperature data to outdoor unit, then the outdoor unit controls thermoregulation.
INDOOR UNIT CONTROL
7-1. COOL operation
w2 Compare liquid pipe temperature to Condenser/ Evaporator temperature, and the lower one is applied to anti-freezing control.
• Liquid pipe temperature [ Condenser/ Evaporator temperature····· Liquid pipe
• Liquid pipe temperature > Condenser/ Evaporator temperature····· Condenser/ Evaporator pipe w3 The function of remote controller can change the temperature to start anti-freezing control.
30
Loading...
+ 100 hidden pages