15. SYSTEM CONTROL·······························································121
1
PLA-RP·AA
PLA-RP·AA
1
PLA-RP·AA.UK
PLA-RP·AA
1.UK
PEAD-RP·EA.UK
PEAD-RP·EA
1
.UK
OC293
REVISED EDITION-A
OC297
REVISED EDITION-A
—
RP3VHARP4VHARP5VHARP6VHA
Indoor unit
Outdoor unit [PUHZ]
OC294
PEA–RP·EA.TH-A
OC299
REVISED EDITION-A
RP3VHA-ARP4VHA-ARP5VHA-ARP6VHA-A
Indoor unit
Outdoor unit [PUHZ]
OC300 REVISED EDITION-A
PAIRING TABLE OF THE INDOOR AND OUTDOOR UNITS
2
2
Outdoor unit
Power supply
Phase
Frequency & Voltage
Indoor unit(A)
Outdoor unit(A)
Wire No.
—
25/25
3
—
32/32
3
—
32/32
3
—
40/40
3
Models (Outdoor unit)
~ / N (Single)
50Hz, 220-230-240V
Outdoor unit
Power supply
Input capacity
Main switch/Fuse
Indoor unit/Outdoor unit connecting
Wire No. o size (e)
Remote controller-indoor unit connecting
Wire No. o size (e)
Indoor unit power supply
~ / N (Single), 50Hz, 220-230-240V
Control circuit rating
Wiring
3 o 2.5 cable (Polar)
Cable 2C o 0.69
This wire is accessory of remote controller (Wire length: 10m, Non-polar)
Indoor unit-Outdoor unit: S1-S2 AC220V-230V-240V
S2-S3 DC24V
Remote controller-Indoor unit: DC14V
RP3VRP4VRP5VRP6V
1
2
S1
S2
S3
S1
S2
S3
Indoor/outdoor
unit connection
cable
Indoor
unit
Unit
power
supply
Outdoor
unit
Remote
controller
L
N
Grounding
L
N
1
2
1
2
S1
Indoor
unit
S2
S3
S1
S2
S3
S1
S2
S3
Unit
power
supply
Indoor/outdoor
unit connection
cable
Indoor
unit
Outdoor
unit
Remote
controller
Grounding
1
2
1
2
1
2
S1
S2
S3
S1
S2
S3
S1
S2
S3
S1
S2
S3
Indoor/outdoor
connection cable
Indoor
unit
Unit
power
supply
Indoor
unit
Indoor
unit
Outdoor
unit
Remote
controller
L
N
Grounding
SPECIFICATIONS FOR ELECTRICAL WORK
2-1. Field electrical wiring(power wiring specifications)
PUHZ-RP•VHA
PUHZ-RP•VHA-A
Check items
1. Wiring size must comply with the applicable local and national code.
2. Be careful about choosing the installation location for the earth leakage breaker and how it is installed as the initial electric
current may cause it to malfunction.
3. Power supply cords and indoor unit / Outdoor unit connecting cords shall not be lighter than polychloroprene sheathed flexible cord. (design 254 IEC 57)
1:1 systemSynchronized twin and triple system Electrical wiring
• Synchronized twin
• Synchronized triple
3
2-2. M-NET wiring method
Group
remote
controller
Refrigerant
address 00
M-NET
address 01
A-control
remote
controller
A-control
remote
controller
A-control
remote
controller
Refrigerant
address 00
M-NET
address 02
Refrigerant
address 00
M-NET
address 03
Power
supply
unit for
transmission
wire
Central
remote
controller
M-NET transmission wire
✕ Bad example (Multi spot grounding of shield wire)
Good example 1 (Single spot grounding of shield wire)
Power
supply
appliance
M-NET type
outdoor unit
Central
remote
controller
Power
supply
appliance
M-NET type
outdoor unit
M-NET type
outdoor unit
M-NET type
outdoor unit
M-NET transmission wire
M-NET type
outdoor unit
M-NET type
outdoor unit
Central
remote
controller
Power
supply
appliance
M-NET type
outdoor unit
M-NET transmission wire
M-NET type
outdoor unit
M-NET type
outdoor unit
Good example 2 (Single spot grounding of shield wire)
(Points to notice)
(1) Outside the unit, transmission wires should stay away from electric wires in order to prevent electromagnetic noise from
making an influence on the signal communication. Place them at intervals of more than 5cm. Do not put them in the same
conduit tube.
(2) Terminal block (TB7) for transmission wires should never be connected to 220~240V power supply. If it is connected,
electronic parts on M-NET p.c. board may be burn out.
(3) Use 2-core x 1.25mm2shield wire (CVVS, CPEVS) for the transmission wire. Transmission signals may not be sent or
received normally if different types of transmission wires are put together in the same multi-conductor cable. Never do this
because this may cause a malfunction.
It would be ok if M-NET wire (non-polar, 2-cores) is arranged in addition to the wiring for A-control.
(4) Ground only one of any appliances through M-NET transmission wire (shield wire). Communication error may occur due to
the influence of electromagnetic noise.
“Ed” error will appear on the LED display of outdoor unit.
“0403” error will appear on the central-control remote controller.
If there are more than two grounding spots on the shield wire, noise may enter into the shield wire because the ground wire
and shield wire form one circuit and the electric potential difference occurs due to the impedance difference among grounding spots. In case of single spot grounding, noise does not enter into the shield wire because the ground wire and shield
wire do not form one circuit.
To avoid communication errors caused by noise, make sure to observe the single spot grounding method described in the
installation manual.
4
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
12
~
50
M-NET Address No.
<Setting example>
Switng
setting
SW11
ones
digit
SW12
tens
digit
OFF
ON
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
0
Refuigrant
address
OFF
ON
8
OFF
ON
1
OFF
ON
9
OFF
ON
10
OFF
ON
11
OFF
ON
12
OFF
ON
13
OFF
ON
14
OFF
ON
15
OFF
ON
2
OFF
ON
3
OFF
ON
4
OFF
ON
5
OFF
ON
6
OFF
ON
7
System
controller
A-control
remote
controller
Group AGroup BGroup C
A-control
remote
controller
TB5
A-control
remote
controller
Refrigerant
address 00
M-NET
address 01
Refrigerant
address 00
M-NET
address 02
Refrigerant
address 01
M-NET
address 03
Refrigerant
address 00
M-NET
address 04
Power
supply
unit for
transmission
wire
A-control
remote
controller
A-control
remote
controller
TB5
Group AGroup B
Refrigerant
address 00
M-NET
address 01
Refrigerant
address 01
M-NET
address 02
Refrigerant
address 00
M-NET
address 04
Refrigerant
address 01
M-NET
address 03
Refrigerant
address 02
M-NET
address 05
System
controller
Power
supply
unit for
transmission
wire
● M-NET wiring
(1) Use 2-core x 1.25mm
2
shield wire for electric wires.
(Excluding the case connecting to system controller.)
(2) Connect the wire to the M-NET terminal block.Connect one core of the
transmission wire (non-polar) to Aterminal and the other to B. Peel the
shield wire, twist the shield part to a string and connect it to S terminal.
(3) In the system which several outdoor units are being connected, the terminal
(A, B, S) on M-NET terminal block should be individually wired to the other
M-NET
terminal
block
ABS
Transmission
wire
Ground
wire
Shield
part
outdoor unit’s terminal, i.e. Ato A, B to B and S to S.In this case, choose one of those outdoor units and drive a screw
to fix an ground wire on the plate as shown on the right figure.
2-2-1. M-NET address setting
In A-control models, M-NET address and refrigerant address should be set only for the outdoor unit. Similar to Free Combo
system, there is no need to set the address of outdoor unit and remote controller. To construct a central control system, the
setting of M-NET address should be conducted only upon the outdoor unit. The setting range should be 1 to 50 (the same as
that of the indoor unit in Free Combo system), and the address number should be consecutively set in a same group.
Address number can be set by using rotary switches
(SW11 for ones digit and SW12 for tens digit), which
is located on the M-NET p.c. board of outdoor unit.
(Factory setting: all addresses are set to “0”.)
2-2-2. Refrigerant address setting
In case of multiple grouping system (multiple refrigerant circuits in one group), indoor units should be connected by remote
controller wiring (TB5) and the refrigerant address needs to be set. Leave the refrigerant addresses to “00” if the group setting is not conducted. Set the refrigerant address by using DIP SW1-3 to -6 on the outdoor controller board. [Factory setting:
all switches are OFF. (All refrigerant addresses are “00”.)]
2-2-3. Regulations in address settings
In case of multiple grouping system, M-NET and refrigerant address settings should be done as explained in the above section. Set the lowest number in the group for the outdoor unit whose refrigerant address is “00” as its M-NET address.
w Refrigerant addresses can be overlapped if they are in the different group.
w In group B, M-NET address of the outdoor unit whose refrigerant address is “00” is not set to the minimum in the group. As
“3” is right for this situation, the setting is wrong. Taking group A as a good sample, set the minimum M-NET address in
the group for the outdoor unit whose refrigerant address is “00”.
5
3WIRING DIAGRAM
[Servicing]
Fasten terminal of the terminal board "TB4" equips lock system.
To remove the fastened terminal, pull it while pressing the protruding portion (locking lever) of
the terminal. The fastened terminal protruding portion should face upward.
NOTES:
1.Since the outdoor side electric wiring may change be sure to
check the outdoor unit electric wiring for servicing.
2.Indoor and outdoor connecting wires are made with polarities, make
wiring matching terminal numbers (S1,S2,S3).
3.Symbols used in wiring diagram above are, :Connector, :Terminal (block).
Please set the voltage using
the remote controller.
For the setting method, please
refer to the indoor unit Installation
Manual.
TO OUTDOOR UNIT
C
TB4
H2
5
GRILLE
MV
MV
MV
MV
5
5
5
5
TRANSMISSION
WIRES DC12V
MODELS
Manufacture
Service board
MODELS
Manufacture
Service board
SW1
BLK
BLK
BLK
BLK
BLK
BLK
BLU
BLU
TH5
12
PIPE
CN29
(BLK)
REMOCON
CN22
(BLU)
WIRELESS
CN90
(WHT)
SW1
SW2
SWE
VANE
CN6V
(WHT)
POWER
CN03
(RED)
POWER
CN2D
(WHT)
LIQUID
CN21
(WHT)
INTAKE
CN20
(RED)
D.SENSOR
CN31
(WHT)
D.HEATER
CNC (RED)
D.U.M
CNP
(BLU)
FAN
(WHT)
BRN
ORN
YLW
CONTROLLER BOARD
CN02 (WHT)
OUTDOOR UNIT
CN01 (BLU)
CN2S(WHT)
BLK
WHT
YLW
ORN
BRN
YLW
YLW
YLW
YLW
BLK
RED
WHT
CNB
W.B
LED1
LED2
BZ
RU
SW1 SW2
X4
X4
J15
J22J21J24J23
OFF
ON
OFF
ON
4321
4321
J21J22J23J24
PLA-RP3AA
PLA-RP3AA
1
PLA-RP4AA
PLA-RP4AA
1
PLA-RP5AA
1
PLA-RP6AA
PLA-RP6AA
1
R.B
9
X1
X1
5
31
CN32
CN2LCN41
123
12315
TH1
2
TB5
1
12
TB6
CN2
TH2
DS
3
2
1
DC14V
1
2
3
12
J11
J12
J13
J14
2
121
LED1LED2LED3
ZNR
DP
3
FC
531
1
1
2
ON
OFF
J21
J22
J23
J24
C
MF
I.B
321
P.B
F1
TB4
S1
S2
S3
PLA-RP3,4,5,6AA
PLA-RP3,4,5,6AA
1
1
J11J12J13J142J15
345
ON
OFF
SW2
MODELS
Manufacture
Service board
J22J21J24J23
OFF
ON
OFF
ON
4321
4321
J21J22J23J24
PLA-RP5AA
10
5
9
8
4
7
6321
123
CONNECTOR (PROGRAM TIMER)
TRANSMISSION LINE)
TERMINAL BLOCK (REMOTE CONTROLLER
REMOTE CONTROLLER BOARD
(0:/15kΩ, 25:/5.4kΩ DETECT)
COND./EVA. TEMPERATURE THERMISTOR
(0:/15kΩ, 25:/5.4kΩ DETECT)
PIPE TEMPERATURE THERMISTOR/LIQUID
(0:/15kΩ, 25:/5.4kΩ DETECT)
ROOM TEMPERATURE THERMISTOR
TRANSMISSION LINE)
TERMINAL BLOCK (REMOTE CONTROLLER
TERMINAL BLOCK (INDOOR/OUTDOOR CONNECTING LINE)
CN2
TB6
R.B
TH5
TH2
TH1
TB5
TB4
DEW PREVENTION HEATERH2
W.B
SYMBOLNAME
WIRELESS REMOTE CONTROLLER BOARD
RECEIVING UNIT
BUZZER
LED (HOT ADJUST)
SWITCH (HEATING ON/OFF)
LED (RUN INDICATOR)
BZ
LED1
RU
LED2
SW1
SW2
SWITCH (COOLING ON/OFF)
SYMBOL
SYMBOL
NAME
NAME
I.B
INDOOR POWER BOARD
FUSE (4A)
VARISTOR
INDOOR CONTROLLER BOARD
CN2L
CN32
CN41
SW1
SW2
SWE
X1
X4
FC
1.Since the outdoor side electric wiring may change be sure to check the
outdoor unit electric wiring for servicing.
2.Indoor and outdoor connecting wires are made with polarities,make wiring
matching terminal numbers(S1,S2,S3).
3.Symbols used in wiring diagram above are, :Connector, :Terminal (block).
FAN
(WHT)
1.When pressing the CHECK switch twice on the remote controller,the unit
changes to the self-diagnosis mode and will display the check code by
LED(light Emitting Diode)
Refer to the right table for the check codes and abnormarities.
Connect the pressure gauge to the high-pressure check valve.
Connect the pressure gauge to the low-pressure check valve.
Measured with piping surface thermometer.
Measured with piping surface thermometer.
Can be displayed on remote controller.
Measured with piping surface thermometer.
Measured with piping surface thermometer.
High pressure (MPa)
Low pressure (MPa)
Discharge pipe temperature (:)
Suction pipe temperature (:)
Indoor intake temperature (:)
Indoor outlet temperature (:)
Outdoor intake temperature (:)
Outdoor outlet temperature (:)
Pressure/temperature near JIS
standard operating conditions
A
B
C
D
E
F
G
H
Notes : The operation statuses vary depending on the compressor's operating frequency because units are inverter-type.
Outdoor
heat exchanger
Stop valve
(with service port)
Power
receiver
Linear
expansion
valve BLinear
expansion
valve A
4-way valve
Compressor
Ball valve
Indoor heat
exchanger
A
B
C
D
Overload operation
Standard operation
Permissible operation range
Normal operation range
00.20.40.60.811.2
Suction pressure (MPa)
Discharge pressure (MPa)
4.5
4
3.5
3
2.5
2
1.5
1
0.5
0
REFRIGERANT SYSTEM DIAGRAM
4-1. Checking operation statuses PUHZ-RP • HA
4-1-1. Measurement points and items
•The table and diagrams below show the measurement item for each measurement point, and the pressure and temperature
near the ISO T1 standard operating conditions.
•Measure the temperature and pressure of each part by following the descriptions in the table.
•Measurement time: Be sure to wait until the refrigerant circuit has stabilized (30 minutes to 1 hour) before taking
measurements.
4-1-2. Operation pressure ranges
11
4-2. Refrigerant System Diagram
Pipe temperature
thermistor/liquid
(TH2)
Distributor
with strainer
#50
Condenser/evaporator
temperature thermistor
(TH5)
Room temperature
thermistor (TH1)
Refrigerant flow in cooling
Refrigerant flow in heating
Additional refrigerant charging amount for liquid pipe which is one size larger than
standard diameter
[12.7
[12.7
RP3
RP4 — RP6
Liquid pipe dia
Chargeless
30m
50m
100 g addition per 1 m when pipe length exceeds 20 m
100 g addition per 1 m when pipe length exceeds 20 m
20m
20m
Max. pipe length
Additional refrigerant charging amount
15
30m or
above
31 — 40m
0.6Kg
0.6kg
10m or below
41 — 50m
1.2Kg
1.2kg
51 — 60m
—
1.8kg
61 — 75m
—
2.4kg
<Table 2> Additional refrigerant charging amount for pipe of standard diameter
<Table 3>
Outdoor unit
Permitted
pipe length
Additional refrigerant charging amount for pipe
length exceeding 30 m (kg)
PUHZ-RP3
PUHZ-RP4 — RP6
Outdoor unit
PUHZ-RP3
PUHZ-RP4 — RP6
Number of
bends
Height
difference
50m or below
75m or below
Permitted
pipe length
50m or below
75m or below
3.1
5.1
11 — 20m 21 — 30m
3.3
5.3
3.5
5.5
31 — 40m
4.1
0.6
6.1
0.6
4.7
1.2
6.7
1.2
—
—
7.3
1.8
—
—
7.9
2.4
41 — 50m 51 — 60m 61 — 75m
Additional refrigerant charging amount for recharging (above) and pipe length exceeding 30m (below) (kg)
Liquid
pipe
(mm)
Gas
pipe
(mm)
[6.35
[9.52[12.7
[9.52
OD
Thick-
ness
OD
Thick-
ness
RP3
RP4
RP5
RP6
t0.8
t0.8
[12.7
t0.8
[15.88
t1.0
[12.7
t0.8
[15.88
t1.0
[19.05
t1.0
[15.88
t1.0
[19.05
t1.0
t0.8
t0.8
: Normal piping
: It can be used, however, additional refrigerant charge is required when the pipe length exceeds 20m. Refer to table 4.
: It cannot be used.
: It can be used.
: It can be used, however, the capacity is lowered. Refer to (C) Capacity correction.
<Table 1> Pipe length for 1:1 system
*1: Set DIP SW8-1 on outdoor unit controller board to ON.
*2: The maximum length is 50 m in case of using existing pipes.
*3: The height difference between indoor and outdoor unit should be kept within 30 m for all models.
[Marks in the table above]
10m30m30m
50m
50m
50m
10m
50m
(*1)
75m
(*2)
50m
75m
(*2)
75m
(*2)
50m
(*1)
50m
(*1)
50m
(*1)
50m
(*1)
50m
(*1)
4-3-1. 1:1 system
(a) Pipe length
(b) Adjusting the amount of refrigerant
• Additional refrigerant charge is not necessary for the pipe length up to 30 m. When the pipe length exceeds 30 m or service
(refrigerant replacement) is performed, charge proper amount of refrigerant for each pipe length referring to table below.
Use refrigerant R410A. Use charge hose exclusive for R410A.
• When charging additional refrigerant, charge the refrigerant from low-pressure side of the port valve using a safety charger.
• Make sure that air purge for this unit at refrigerant replacement is performed from both high-pressure check valve and ser-
vice port. (If air purge is performed only from one of them, air in not purged enough.)
• When replacing refrigerant, charge the refrigerant from service port. When charged refrigerant is less than specified amount,
charge the refrigerant again from low pressure side of the port valve using a safety charger.
• Tighten the service port cap (nut) of stop valve firmly. The tightening torque is 12 to 16 N·m. (For the prevention of slow-leak)
• Check additional refrigerant charging amount referring to table 4 when liquid pipe is one size larger than standard diameter,
and table 2 when the pipe is standard diameter.
14
100
95
90
85
80
75
70
5 101520253035404550556065707580
Note: The permitted pipe length is up to 55m for RP3 model.
RP3 model
RP4 model
Heating RP3, 4, 5
and 6 models
(Up to 55m for
RP3 model)
RP5 model
RP6 model
Cooling
Capacity ratio [%]
Corrected pipe length
(c) Capacity correction
5 10152025303540455055
80
Capacity ratio [%]
Corrected pipe length
85
90
95
100
Heating RP3
Cooling RP3
Cooling
Heating
Cooling and heating capacity is lowered according to pipe length. Capacity can be obtained by referring to the capacity
curves below. When the diameter of gas pipe is one size smaller than standard diameter, cooling capacity is lowered comparing to the standard diameter. The lowered capacity can be obtained by referring to capacity curves for gas pipe which is
one size smaller than standard size.
Corrected pipe length (m) = actual pipe length (m) + number of bends x 0.3 (m)
11
Capacity curves for PUHZ-RP • HA model <Standard size>
22
Capacity curve for PUHZ-RP3 model
<When gas pipe is one size smaller than standard size>
33
When gas pipe is one size larger than standard size for PUHZ-RP4, 5 and 6.
1 Capacity can be obtained by referring to capacity curves of standard size.
15
4-3-2. Synchronized twin and triple
(a) Pipe length
Please note that refrigerant piping length, bend number and height difference of indoor units are specified for each unit
combination.
Note: Be sure to use our Multi-distributor for distributing pipe to use existing piping.
<Table 5>
Synchronized twin
Outdoor
unit
<Table 6>
Outdoor
unit
Note 1: If total piping length exceeds charge-less piping length of 30 m, charge additional refrigerant according to the table 7.
PUHZ-RP3VHA
PUHZ-RP4~6VHA
Synchronized twin
PUHZ-RP6VHA30 m or less70 m or less
Permitted total piping
length A + B + C
50 m or less
75 m or less
Permitted total piping
length A + B + C + D
Chargeless piping
length A + B + C
30 m or less
Charge-less piping
length A + B + C + D
Indoor unit’s height
difference [B and C]
8 m or less
Indoor unit’s height difference
[B and C] [C and D] [B and D]
8 m or less
Bend number
w 2
15 at most
Bend number
w 2
15 at most
<Table 7>
A + B + C (+D)
Outdoor unit
30 m or less
PUHZ-RP3VHA
PUHZ-RP4~6VHA
Note 2: Bends number (w 2) should be within 8 for each combination, A + B, A +C and A + D, and 15 in all.
Note 3: Height difference between indoor and outdoor unit is referred to no matter which unit is located higher or lower.
<Table 8> Pipe length for twin of RP 3 - 6 (Piping length: A + B + C)
RP3 Twin (RP1.6✕2)
Liquid [6.35
Gas [12.7
Branch pipe
diameter
[B and C]
<Table 9> Pipe length for triple of RP6 (Piping length: A + B + C + D)
Branch pipe
diameter
[B,C and D]
Liquid [6.35
Gas [12.7
Liquid [9.52
Gas [15.88
Liquid [12.7
Gas [19.05
Liquid [6.35
Gas [12.7
Liquid [9.52
Gas [15.88
Liquid [12.7
Gas [19.05
✕
✕
✕
Main pipe diameter [A]
Liquid [9.52
Gas [15.88
75 m(✽2)
50 m
✕
Not required
Liquid [9.52
Gas [15.88
50 m
50 m
Liquid [12.7
Gas [19.05
50 m(✽1)
50 m(✽1)
Additional refrigerant to be charged (kg)
31 - 40 m41 - 50 m51 - 60 m61 - 75 m
0.6
RP4 Twin (RP2✕2)RP5 T win (RP2.5✕2)RP6 Twin (RP3✕2)
Liquid [9.52
Gas [15.88
75 m(✽2)
50 m
✕
✕
✕
✽1 ··· Set DIP SW8-1 on outdoor unit control circuit board to ON.
✽2 ··· When using existing piping, pipe length should be 50 m at most.
✽3 ··· Height difference between indoor and outdoor unit should be
kept within 30 m in every case.
[Marks in table]
··· Normal piping
··· It can be used with some changes of piping length and the
amount of refrigerant to be charged.
✕ ··· It cannot be used.
1.2
Main pipe diameter [A]
Liquid [12.7
Gas [19.05
50 m(✽1)
50 m(✽1)
✕
1.82.4
Liquid [9.52
Gas [15.88
✕
75 m(✽2)
✕
Liquid [12.7
Gas [19.05
✕
50 m(✽1)
✕
w Charge additional
refrigerant from
the check valve
connected to the
pipe of low-pressure
side in indoor unit.
Liquid [9.52
Gas [15.88
✕
75 m(✽2)
✕
Liquid [12.7
Gas [19.05
50 m(✽1)
✕
✕
16
Synchronized twin
Synchronized triple
Indoor
unit
Optional
distributing pipe
1 m or less
Multi-distributor
30 m or less
Branch
pipe B
Branch
pipe C
Main
pipe A
Indoor
unit
Outdoor
unit
Indoor
unit
Optional
distributing pipe
1 m or less
Multi-distributor
30 m or less
Branch
pipe B
Branch
pipe C
Branch
pipe D
Main
pipe A
Indoor
unit
Indoor
unit
Outdoor
unit
1. Keep Stop valve in outdoor unit fully closed (as it is shipped), and after completing refrigerant piping connection, conduct air
purge from service port of stop valve at outdoor unit.
2. After air purging, make the valve rod of stop valve at outdoor unit fully open.
Now refrigerating cycle is complete between indoor and outdoor unit.
Handle stop valve following the indication on outdoor unit.
Caution:
• Be sure to apply refrigerating oil to flare sheet face. Never apply it to screws. (As it causes flare nut loosening.)
• Use double spanner for piping connection.
• Be sure to check gas leak by using leak detector or soapy water.
• Use attached parts for refrigerant piping to provide correct insulation to the connection of indoor unit side in accordance with
attached explanation sheet.
• Be sure to provide anoxidized brazing.
(b) Adjusting the amount of refrigerant oil
(i) In case of RP 3 twin
Check the additional refrigerant oil to be charged referring to table 2 when using pipe of size referred in table 8.
(ii) In case of RP4 - 6 twin or RP6 triple
When using liquid pipe one size larger than standard diameter for main pipe A, calculate the amount of additional
refrigerant oil referring to 2 below.
1 When using piping of standard diameter or gas pipe one size larger than standard diameter for main pipe A.
Check the additional refrigerant oil to be charged referring to table 2 like 1:1 system.
2 When using liquid pipe one size larger than standard diameter for main pipe A.
[In case of RP4-6 using liquid pipe of [12.7]
• When total length of extension pipe (main pipe and branch pipe) is less than 20 m.
No adjustment is required for refrigerant oil. (Chargeless)
• When total length of extension pipe (main pipe and branch pipe) is more than 20 m.
Calculate the amount of additional refrigerant oil, referred to as W (g) in the following, using the equation below and add
proper amount of refrigerant oil. If W is less than or equal to 0, no additional charge is required. (Chargeless)
Note: Put “0” in L1-3 if it is not used. L1: Liquid pipe length of [12.7 (m)
L2: Liquid pipe length of [9.52 (m)
L3: Liquid pipe length of [6.35 (m)
(c) Capacity correction
Apply pipe length between indoor and outdoor unit which is the longest of all for the calculation of capacity lowering according
to each pipe length.
17
5
Parts nameCheck points
Disconnect the connector then measure the resistance using a tester.
(Surrounding temperature 10:~30:)
Drain sensor
(Refer to below for a detail.)
(Refer to below for a detail.)
Room temperature
thermistor (TH1)
Pipe temperature
thermistor (TH2)
Condenser/evaporator
temperature thermistor
(TH5)
1
2
3
Normal
4.3k"~9.6k"
Abnormal
Open or short
Abnormal
Open or short
Normal
0.6k"~6.0k"
Measure the resistance between the terminals using a tester.
Measure the resistance after 3 minutes have passed since the power supply was intercepted.
(Surrounding temperature 0:~60:)
-200 20406080
< Thermistor for drain sensor >
Temperature (:)
0
1
2
3
4
5
6
7
8
9
10
Resistance (K")
HOW TO CHECK THE PARTS
5-1. INDOOR UNIT
• Common parts
<Thermistor Characteristic graph>
Thermistor for
lower temperature
Room temperature thermistor(TH1)
Pipe temperature thermistor(TH2)
Condenser/evaporator temperature
thermistor(TH5)
Thermistor R0=15kΩ ±3%
Fixed number of B=3480kΩ ±2%
(1) Operation summary of the linear expansion valve.
• Linear expansion valve open/close through stepping motor after receiving the pulse signal from the outdoor controller board.
• Valve position can be changed in proportion to the number of pulse signal.
<Connection between the outdoor controller board and the linear expansion valve>
The output pulse shifts in above order.
❈ 1. When linear expansion valve operation stops, all output phase
become OFF.
❈ When the switch is turned on, 700 pulse closing valve signal will
be sent till it goes to
A point in order to define the valve position.
(The pulse signal is being sent for about 20 seconds.)
When the valve moves smoothly, there is no noise or vibration
occurring from the linear expansion valve : however, when the
pulse number moves from B to A or when the valve is locked,
more noise can be heard than normal situation.
No noise is heard when the pulse number moves from B to A in
case coil is burn out or motor is locked by open-phase.
❈ Noise can be detected by placing the ear against the screw dri-
ver handle while putting the screw driver to the linear expansion
valve.
22
(3) How to attach and detach the coil of linear expansion valve
<Composition>
Linear expansion valve is separable into the main body and the coil as shown in the diagram below.
Coil
Lead wire
<How to detach the coil>
Hold the lower part of the main body (shown as A) firmly so that
the main body does not move and detach the coil by pulling it
upward.
Be sure to detach the coil holding main body firmly. Otherwise
pipes can bend due to pressure.
Stopper
Main body
<How to attach the coil>
Hold the lower part of the main body (shown as A) firmly so that
the main body does not move and attach the coil by inserting it
downward into the main body. Then securely attach the coil stopper to pipe B. (At this time, be careful that stress is not added to
lead wire and main body is not wound by lead wire.) If the stopper is not firmly attached to pipe B, coil may be detached from
the main body and that can cause defective operation of linear
expansion valve.
To prevent piping stress, be sure to attach the coil holding the
main body of linear expansion valve firmly. Otherwise pipe may
break.
B
A
A
Be sure to attach the
stopper to pipe B.
23
6MICROPROCESSOR CONTROL
Standard 1:1Synchronized twin. Triple
1Unit (indoor/outdoor) power supply L/N
2Connecting line between the indoor and
outdoor; S1/S2/S3, Polarized 3-wire
3Remote controller transmission line; Non
polarezed 2-wire
4Auxiliary heater exclusive power supply; L/N
1Unit (indoor/outdoor) power supply L/N
2Connecting line between the indoor and outdoor; S1/S2/S3, Polarized 3-wire
3Remote controller transmission line; Non polarezed 2-wire
4Auxiliary heater exclusive power supply; L/N
1Unit (indoor/outdoor) power supply L/N
2Connecting line between the indoor and
outdoor; S1/S2/S3, Polarized 3-wire
3Remote controller transmission line; Non
polarezed 2-wire
4Auxiliary heater exclusive power supply; L/N
Remote control main/sub setting necessity
(In case of 2 remote controllers)
No setting (initial setting)
Refrigerant address setting; SW1; 3~6
Various setting
Remote controller
Main Sub
Indoor unit
Outdoor unit
Remarks
Group control
1
4
2
3
Main
(00)
Outdoor unit; (00)...Refrigerant address
(SW1; 3~6)
Indoor unit; (00)–w
Indoor unit number
(auto setting)
Refrigerant address
(receiving from the
outdoor unit)
Outdoor unit; (00)...Refrigerant address
(SW1; 3~6)
Indoor unit; (00)–w
Indoor unit number
(auto setting)
Refrigerant address
(receiving from the
outdoor unit)
(00)-1(00)-2(00)-3
Sub
1
44
222
4
3
Main
(00)
(00)-1(00)-2(01)-1
1
(01)
1
(02)
1
44
222
4
(02)-1(02)-2
4
2
2
4
3
333
(1) Indoor unit number is set automatically
(2) When the refrigerant address of the unit is "00", Remote controller is supplied.
Remote control main/sub setting necessity
(In case of 2 remote controllers)
No setting
No setting
Remote control main/sub setting necessity
(In case of 2 remote controllers)
No setting (initial setting)
No setting (initial setting)
Various setting
Remote controller
System construction
System construction
Indoor unit
Outdoor unit
Remarks(1) Indoor unit number is set automatically
6-1. System construction
(1) System construction
A-control model which just wires the connecting line between the indoor and outdoor unit and supply the power is applicable to
any models of standard (1:1), twin and triple. (Refer to 2 Start-up system.)
24
(2) The transmitting specification for “A” control
Cross section
of cable
Round
2.5
2.5
1.5
2.5
3
3
4
4
(50)
✽2
(45)
✽3
60
✽4
Not
applicable
✽5
Flat
✽1 : Power supply cords of appliances shall not be lighter than design 245 IEC or 227 IEC.
✽2 : In case that cable with stripe of yellow and green is available.
✽3 : In case of regular polarity connection (S1-S2-S3), wire size is 1.5mm
2
.
✽4 : In case of regular polarity connection (S1-S2-S3).
✽5 : In the flat cables are connected as this picture, they can be used up to 80m.
✽6 : Mentioned cable length is just a reference value.
It may be different depending on the condition of installation, Humidity or materials, etc.
Flat
Round
Wire size
(mm
2
)
Number
of wires
Clockwise : S1-S2-S3
w Pay attention to stripe of yellow and green
Clockwise : S1-S2-S3-Open
w Connect S1 and S3 to the opposite angle
Not applicable
(Because center wire has no cover finish)
From left to right : S1-Open-S2-S3
Polarity
L(m)
✽6
(3C Flat cable ✕ 2)
S1 S2 S3
1Wiring regulations
SectionCommunications from remote controllers
The maximum length of
500m80m (Including the wiring among indoor units
total wiring
The maximum numbers
for connection
One remote controller can connect and operate
up to 16 indoor units by grouping them.
One group can connect up to two remote controllers.
❋1 Remote controller considers multiplex units as
a single group.
Communications between indoor and outdoor units
in addition to the wiring between indoor and
outdoor units)
1
❋
One outdoor unit can connect up to three
indoor units.
The cables applicable0.3mm
2
to 1.25mm
2
Use either flat-type cable (3 cores: {1.6mm or
more) or wires in the table below.
❋2 The diameter of the cables depends on
each unit.
OthersThe wirings as follows are not allowed:
• The wiring that the indoor units of the same
The core wire connected to terminal S2 shall be
placed at the center of flat-type cable.
refrigerant system are connected through TB5.
• The wiring which directly connects the terminals
for remote controllers.
2Transmitting specification
SectionCommunications from remote controllers
Communications between indoor and outdoor units
Transmitting speed83.3 bit/sec. (1 bit = 12ms)83.3 bit/sec. (1 bit = 12ms)
Normal transmissionThe terminal for remote controller transmits sig-
nals every 7.5 seconds; the indoor unit whose
Outdoor unit transmits signals every 3 seconds;
all the connected indoor units respond them.
refrigerant address is “0” responds them.
ModulationThe waveform modulates at 50kHz.There is no modulation.
Detection of abnormal
communication
When transmitting error is detected for three con-
secutive minutes.
When transmitting error is detected for three
consecutive minute.
WIRING SPECIFICATIONS FOR 220~240V 50Hz
(INDOOR-OUTDOOR CONNECTING CABLE)
25
(3) The waveforms of from remote controller communications
The following graphs are the examples for measuring waveforms on the wirings of remote controlled transmission at the
terminal block for remote controller.
a) Ameasuring example in the sequence of startupb) Ameasuring example during normal stop
• During normal operation, the remote controller interactively exchanges signals with the indoor unit of refrigerant address “0”.
When the remote controller cannot receive signals from the indoor unit of refrigerant address “0” for 3 minutes, it is considered
as abnormal. E0 is displayed on the remote controller as an error.
26
(4) The waveforms of communications between indoor and outdoor units
The following graphs are the examples for measuring waveforms on the wirings of connecting indoor and outdoor units at
between S2 and S3 of the outdoor terminal block TB1.
a) Ameasuring example the sequence of startup: 1b) A measuring example in the sequence of startup: 2
Transmission
from
indoor unit
Transmission
from
outdoor unit
10V/div, 500msec/div:10V/div, 500msec/div:
c) Ameasuring example during normal stop
(When one outdoor unit connects one indoor unit)
Transmission
from
indoor unit
Transmission
from
outdoor unit
Transmission
from
indoor unit
Transmission
from
outdoor unit
d) Ameasuring example during normal stop
(When one outdoor unit connects two indoor units)
Transmission
from
indoor unit
Transmission
from
one indoor unit
Transmission
from
another
indoor unit
10V/div, 500msec/div:10V/div, 500msec/div:
c) Expanded waveform
10V/div, 50msec/div:
• During normal operation, outdoor unit interactively exchanges signals with all the connected indoor units.
• When outdoor unit cannot receive signals for three minutes from an indoor unit due to any trouble like cable disconnection, it
is considered as abnormal and the outdoor unit stops. E8 is displayed on the remote controller. This is to avoid independent
operation of indoor units.
27
(5) Start-up system
Power ON
YES
NO
1 Refrigerant address
transmitting
Power supply control
to remote controller
3 Set number of the
connected unit
4 Set number of the
indoor unit
6 Collecting the unit
information
7 Collecting the
operation data
Set up finish
2 Refrigerant
address "0"?
YES
NO
5 Duplication
detection
Example
2 blinking2 blinkingNot lighted
3 seconds
A control unit is applicable to any models of standard (1:1), twin and triple without switch setting according to carrying out the
below process automatically when the power is supplied.
When the power is supplied, following processes of 1 Refrigerant address transmitting, 2 Power supply control to remote
controller, 3 Set number of the connected unit, 4 Set number of the indoor unit, 5 Duplication detection, 6 Collecting the unit
information and 7 Collecting the operation data are carried out as shown on the figure.
Also when detecting the duplicated setting in the step 5, back to the first step and reset it.
; Transmitting the switch setting
contents on the outdoor unit
remote controller
(SW1-3~6)
; Feeding control to remote
controller
Feeding the indoor unit of the
refrigerant address “0”
EA error if 4 minutes have
passed since the power is
supplied.
; If there are 2 or more speci-
fied indoor unit, back to the
first step.
<<Feature>>
A. Start-up time from the second time will be shorter since setting of the number of connected units is memorized once set.
Start-up time can be estimated as following;
•When installing ... 1~2 minutes (Depending the number of connecting units)
•Since the second time .... 20 seconds ~ 1 minute (Depending the number of connecting units)
w When the above processing does not finish, even if 4 minutes have passed, consider the processing an error and
Ea, Eb or Ec will be displayed.
However if power is not supplied to the indoor unit due to miss-wiring or looseness of the connecting lines
between the indoor and outdoor unit, there will be no display on the remote controller. Also when the data can not
be received from the outdoor unit, E6 is displayed on the remote controller after 6 minutes.
B. When replacing the p.c.board, only the unit number which has had it`s p.c.board replaced is reset.
Even if the power supply is reset, the unit number which has not had it`s replaced does not change.
C. Automatic set unit is possible to confirm by blinking the frequency of LED3 in the indoor controller board.
At intervals of approx. 3 seconds, the number of the unit-number blinks.(Example:The unit(unit number:2) blinks twice at
3-second intervals.
; Collecting the vane, louver
information and transmittance
to the remote controller.
; Collecting the preceding oper-
ation setting information and
transmittance to the remote
controller.
EB error if 4 minutes have
passed since the power is
supplied.
EC error if 4 minutes have
passed since the power is
supplied.
28
Function/control specifications
Item
Fan
Up/down
auto vane
Left/right
Function / specification
swing louver
Drain pump
Number of fan speed
Drive method
Provided
Swing function
Shutter mechanism
Moter type
Provided
Moter type
4-way ceiling cassette
PLA-RP•AA
4
Pulsation
(AC motor)
Stepping
(12V DC)
—
—
Ceiling concealed
PEA-RP•EA
2
Tap-changing
(AC motor)
—
—
—
—
—
—
—
Note: The parts marked are optional.
PEAD-RP•EA
2
Tap-changing
(AC motor)
—
—
—
—
—
—
29
7
Control modes
Control details
1-1. Thermoregulating function (Function to prevent restarting for 3 minutes)
• Room temperature ] desired temperature +1:···Compressor ON
• Room temperature [ desired temperature ···Compressor OFF
Crankcase heater: OFF when compressor operates
ON when compressor stopped
(including when thermo is OFF)
Crankcase heater switches ON when 220-240V AC current is applied between
connectors CH 1 and 2 on the outdoor control board.
1-2. Anti-freezing control
Detected condition : When the liquid pipe temperature (TH2 ) or Condenser/
Evaporator temperature (TH5 ) (w3) is 2: or less (w4) in 16
minutes from compressors start up, anti-freezing control
starts and the compressor will be suspended.
Released condition : The timer which prevents reactivating is set for 3 minutes,
and anti- freezing control is cancelled when any one of the
following conditions is satisfied.
1
Liquid pipe temperature (TH2) and Condenser / Evaporator
temperature (TH5) turn 10: or above.
2 The condition of the compressor stop has become
complete by thermoregulating, etc.
3 The operation modes became mode other than COOL.
4 The operation stopped.
1-3. Frozen protection
Detected condition : 1 When the indoor pipe temperature (TH2 ) or Condenser/
Evaporator temperature (TH5 ) continues -15: for 3 minutes
since 3 minutes has passed after the compressor start, the
compressor stops and then the mode changes to prevent
restarting for 6 minutes. After restarting of 6 minutes, when
the indoor pipe temp. (TH2) or Condenser / Evaporator
temperature (TH5) continues -15 or less for three minutes again
by the time 16 minutes have passed, the frozen protection
operates. (P6)
Detected condition : 2
In case the indoor unit continues to be under the anti-freezing
control for 9 minutes or more, the unit will be in a state of the
suspensive abnormality. Restart the compressor after releasing
the anti-freezing control. The suspensive abnormality will be
cancelled if the compressor keeps operating for 20 minutes.
However, the suspensive abnormality will turn into the
abnormality if the anti-freezing control works again for 9
minutes during that period. On the other hand, the suspensive
abnormality will be cancelled if the anti-freezing control
works for less than 9 minutes
Released condition : When the operation stops by the remote controller operation.
By the remote controller setting (switch of 4 speeds or 2 speeds)
When determining the abnormality of the pipe temp. low speed fan is fixed.
2. Fan
1. Compressor
Remarks
Type
Fan speed notch
[Low] [Mid2] [Mid1] [High]
[Low] [High]
4 speeds type
2 speeds type
Refer to w2.
Refer to w3.
w1 The thermoregulating
function is provided in the
outdoor unit.
The indoor unit transmits
the indoor room
temperature and set
temperature data to
outdoor unit, then the
outdoor unit controls
thermoregulation.
INDOOR UNIT CONTROL
7-1. COOL operation
w2 Compare liquid pipe temperature to Condenser/ Evaporator temperature, and the lower one is applied to anti-freezing control.
• Liquid pipe temperature [ Condenser/ Evaporator temperature····· Liquid pipe
• Liquid pipe temperature > Condenser/ Evaporator temperature····· Condenser/ Evaporator pipe
w3 The function of remote controller can change the temperature to start anti-freezing control.
30
Loading...
+ 100 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.