Before installing the unit, make sure you read all the “Safety
Precautions”.
The “Safety Precautions” provide very important points re-
garding safety. Make sure you follow them.
Please report to or take consent by the supply authority be-
fore connection to the system.
Warning:
• For appliances not accessible to the general public.
• The unit must not be installed by the user. Ask the dealer or an
authorized company to install the unit. If the unit is installed improperly, water leakage, electric shock or fi re may result.
• Do not stand on, or place any items on the unit.
• Do not splash water over the unit and do not touch the unit with
wet hands. An electric shock may result.
• Do not spray combustible gas close to the unit. Fire may result.
• Do not place a gas heater or any other open-flame appliance
where it will be exposed to the air discharged from the unit. Incomplete combustion may result.
• Do not remove the front panel or the fan guard from the outdoor
unit when it is running.
Warning:
Describes precautions that should be observed to prevent danger
of injury or death to the user.
Caution:
Describes precautions that should be observed to prevent damage
to the unit.
Symbols used in the illustrations
: Indicates a part which must be grounded.
• When you notice exceptionally abnormal noise or vibration, stop
operation, turn off the power switch, and contact your dealer.
• Never insert fi ngers, sticks etc. into the intakes or outlets.
• If you detect odd smells, stop using the unit, turn off the power
switch and consult your dealer. Otherwise, a breakdown, electric
shock or fi re may result.
• This air conditioner is NOT intended for use by children or infi rm
persons without supervision.
• Young children must be supervised to ensure that they do not
play with the air conditioner.
• If the refrigeration gas blows out or leaks, stop the operation of
the air conditioner, thoroughly ventilate the room, and contact
your dealer.
Caution:
• Do not use any sharp object to push the buttons, as this may
damage the remote controller.
• Never block or cover the indoor or outdoor unit’s intakes or outlets.
2. Parts Names
Indoor Unit
PLA-A.BA
Fan steps4 steps
VaneAuto with swing
Louver–
FilterLong-life
Filter cleaning indication2,500 hr
Disposing of the unit
When you need to dispose of the unit, consult your dealer.
Air outlet
Vane
Filter
Air intake
2
2. Parts Names
Wired Remote-Controller
Display Section
For purposes of this explanation,
all parts of the display are shown.
During actual operation, only the
relevant items will be displayed.
Identifi es the current operation
Shows the operating mode, etc.
* Multi language display is sup-
ported.
“Centrally Controlled” indicator
Indicates that operation of the remote controller has been prohibited
by a master controller.
“Timer is Off” indicator
Indicates that the timer is off.
Temperature Setting
Shows the target temperature.
Operation Section
Day-of-Week
Shows the current day of the week.
Time/Timer Display
Shows the current time, unless the simple or Auto Off
timer is set.
If the simple or Auto Off timer is set, shows the time remaining.
TIME SUN MON TUE WED THU FRI SAT
TIMER
AFTER
ERROR CODE
˚F˚C
Hr
AFTER
˚F˚C
ONLY1Hr.
Room Temperature display
Up/Down Air Direction indicator
The indicator shows the direction of the outcoming airfl ow.
“One Hour Only” indicator
Displayed if the airflow is set to
Low and downward during COOL
or DRY mode. (Operation varies
according to model.)
The indicator goes off after one
hour when the airflow direction
also changes.
Shows the room temperature. The room
temperature display range is 8–39 °C,
46–102 °F.
The display blinks if the temperature is
less than 8 °C, 46 °F or 39 °C, 102 °F or
more.
Louver display
Indicates the action of the swing louver.
Does not appear if the louver is stationary.
(Power On indicator)
Indicates that the power is on.
ON
OFF
FUNCTION
FILTER
WEEKLY
SIMPLE
AUTO OFF
“Sensor” indication
Displayed when the remote controller
sensor is used.
“Locked” indicator
Indicates that remote controller buttons have been locked.
“Clean The Filter” indicator
Comes on when it is time to clean the
fi lter.
Timer indicators
The indicator comes on if the corresponding timer is set.
Fan Speed indicator
Shows the selected fan speed.
Ventilation indicator
Appears when the unit is running in
Ventilation mode.
Set Temperature buttons
ON/OFF button
Down
Up
Fan Speed button
Timer Menu button
(Monitor/Set button)
Mode button (Return button)
Set Time buttons
Back
Ahead
Timer On/Off button
(Set Day button)
TEMP.
MENU
BACKDAY
MONITOR/SET
PAR-21MAA
CLOCK
ON/OFF
OPERATION
ON/OFF
FILTER
CHECK
CLEAR
TEST
Filter button
(<Enter> button)
Test Run button
Check button (Clear button)
Airfl ow Up/Down button
Louver button
Operation button)
(
To return operation
Opening the
door
Built-in temperature sensor
number
Ventilation button
Operation button)
(
To go to next opera-
tion number
Note:
“PLEASE WAIT” message
This message is displayed for approximately 3 minutes when power is supplied to the indoor unit or when the unit is recovering from a power fail-
ure.
“NOT AVAILABLE” message
This message is displayed if a button is pressed to operate a function that the indoor unit does not have.
If a single remote controller is used to simultaneously operate multiple indoor units that are different models, this message will not be displayed if
any of the indoor units is equipped with the function.
When using the wireless remote controller, point it towards the receiver on the indoor unit.
If the remote controller is operated within approximately two minutes after power is supplied
to the indoor unit, the indoor unit may beep twice as the unit is performing the initial automatic
check.
The indoor unit beeps to confirm that the signal transmitted from the remote controller has
been received. Signals can be received up to approximately 7 meters in a direct line from the
indoor unit in an area 45° to the left and right of the unit. However, illumination such as fl uores
cent lights and strong light can affect the ability of the indoor unit to receive signals.
If the operation lamp near the receiver on the indoor unit is blinking, the unit needs to be in
spected. Consult your dealer for service.
Handle the remote controller carefully! Do not drop the remote controller or subject it to strong
shocks. In addition, do not get the remote controller wet or leave it in a location with high hu
midity.
To avoid misplacing the remote controller, install the holder included with the remote controller
on a wall and be sure to always place the remote controller in the holder after use.
Outdoor unit
Po w e r
Ref. Pipes
Indoor-Outdoor
Connection wire
Battery installation/replacement
1. Remove the top cover, insert two AAA batteries, and then install the top cover.
1
2
Top cover
2. Press the Reset button.
3
Two AAA batteries
Insert the negative (–)
end of each battery fi rst.
Install the batteries in
the correct directions
(+, –)!
Press the Reset button
with an object that has
a narrow end.
Ear th
Service P anel
4
3. Screen Confi guration
Function Selection of remote
controller
Set Day/Time
TIME SUN
Standard Control Screens
˚F
˚F˚C
˚C
OFFON
Timer MonitorTimer Setup
MON
TIMER
OFF
˚F˚C
WEEKLY
SUN MON TUE WED THU FRI SAT
4. Setting the Day of the Week and Time
1
Day of the Week &
TIME SUN
˚F
˚C
˚F
˚C
TEMP.
MENU
MONITOR/SET
BACKDAY
PAR-21MAA
ON/OFF
CLOCK
OPERATION
ON/OFF
FILTER
CHECK
CLEAR
TEST
Note:
The day and time will not appear if clock use has been disabled at Function Selection of remote controller.
Time display
WEEKLY
<Screen Types>
For details on setting the language for the remote controller display, refer
to section 8. Function Selection.
The initial language setting is English.
Function Selection of remote controller:
Set the functions and ranges available to the
remote controller (timer functions, operating
restrictions, etc.)
Set Day/Time:
Set the current day of the week or time.
Standard Control Screens:
View and set the air conditioning system’s operating status
Timer Monitor:
View the currently set timer (weekly timer,
simple timer, or Auto Off timer)
Timer Setup:
Set the operation of any of the timers (weekly
timer, simple timer, or Auto Off timer).
<How to change the screen>
: Hold down both the Mode button and the Timer On/Off button for 2
seconds.
: Press the Timer Menu button.
: Press the Mode (Return) button.
: Press either of the Set Time buttons ( or ).
Day of the Week Setting
3
2
TIME SUN
4
Time Setting
1. Press the or Set Time button to show display 2.
2. Press the Timer On/Off (Set Day) button to set the day.
* Each press advances the day shown at 3 :
Sun Mon ... Fri Sat.
Press the appropriate Set Time button as necessary to set the time.
3.
* As you hold the button down, the time (at 4) will increment fi rst in
one-minute intervals, then in ten-minute intervals, and then in onehour intervals.
4. After making the appropriate settings at Steps 2 and 3, press the Filter
button
to lock in the values.
5. Operation
2
˚C˚F
3
PAR-21MAA
5.1. Turning ON/OFF
<To Start Operation>
Press the ON/OFF button .
• The ON lamp 1 and the display area come on.
Note:
When the unit is restarted, initial settings are as follows.
ModeLast operation mode
Temperature settingLast set temperature
Fan speedLast set fan speed
Airfl ow up/downLast setting
˚C˚F
TEMP.
MENU
MONITOR/SET
CLOCK
ON/OFF
OPERATION
BACKDAY
Remote Controller settings
ON/OFF
FILTER
CHECK
CLEAR
TEST
6
4
5
8
7
1
2
5
6
F
3
7
5
5. Operation
<To Stop Operation>
Press the ON/OFF button again.
1
• The ON lamp
Note:
Even if you press the ON/OFF button immediately after shutting down the operation is progress, the air conditioner will not start for about three minutes.
This is to prevent the internal components from being damaged.
and the display area go dark.
5.2. Mode select
Press the operation mode () button and select the opera-
Only indicated on the following condition
Wired remote controller used
LOSSNAY connected
Information for multi system air conditioner (Outdoor
unit: MXZ series)
Multi system air conditioner (Outdoor unit: MXZ series) can
connect two or more indoor units with one outdoor unit. Accord
ing to the capacity, two or more units can operate simultaneously.
• When you try to operate two or more indoor units with one outdoor
unit simultaneously, one for the cooling and the other for heating, the
operation mode of the indoor unit that operates earlier is selected. The
other indoor units that will start the operation later cannot operate, indicating an operation state in blinking.
In this case, please set all the indoor units to the same operation mode.
• There might be a case that the indoor unit, which is operating in (AUTO)
mode. Cannot change over to the operating mode (COOL HEAT) and
becomes a state of standby.
• When indoor unit starts the operation while the defrosting of outdoor
unit is being done, it takes a few minutes (max. about 15 minutes) to
blow out the warm air.
• In the heating operation, though indoor unit that does not operate may
get warm or the sound of refrigerant fl owing may be heard, they are
not malfunction. The reason is that the refrigerant continuously fl ows
into it.
Automatic operation
According to a set temperature, cooling operation starts if the room
temperature is too hot and heating operation starts if the room temperature is too cold.
During automatic operation, if the room temperature changes and re-
mains 2 °C, 4 °F or more above the set temperature for 15 minutes,
the air conditioner switches to cooling mode. In the same way, if the
room temperature remains 2 °C, 4 °F or more below the set temperature for 15 minutes, the air conditioner switches to heating mode.
Cooling mode15 minu tes (switches
from heating to cooling)
5.3. Temperature setting
To decrease the room temperature:
Press button to set the desired temperature.
The selected temperature is displayed 3.
To increase the room temperature:
Press button to set the desired temperature.
The selected temperature is displayed 3.
• Available temperature ranges are as follows:
Cooling/Drying: 19 - 30 °C, 67 - 87 °F
Heating: 17 - 28 °C, 63 - 83 °F
Automatic: 19 - 28 °C, 67 - 83 °F
•
The display blinks either 8 °C - 39 °C, 46 °F - 102 °F to inform you if the
room temperature is lower or higher than the displayed temperature.
(This display does not appear on the wireless remote controller.)
5.4. Fan speed setting
Press the Fan Speed button as many times as necessary while the
system is running.
• Each press changes the force. The currently selected speed is
shown at 5.
• The change sequence, and the available settings, are as follows.
FAN SPEEDDisplay
4-speed
+
Auto
Note:
The number of available fan speeds depends on the type of unit connected.
In the following cases, the actual fan speed generated by the unit will differ
from the speed shown the remote controller display.
1. While the display is showing “STAND BY” or “DEFROST”.
2. When the temperature of the heat exchanger is low in the heating mode.
(e.g. immediately after heating operation starts)
3. In HEAT mode, when room temperature is higher than the temperature
setting.
4. When the unit is in DRY mode.
Speed 1 Speed 2 Speed 3 Speed 4
Auto
5.5. Airfl ow direction setting
<To Change the Airfl ow’s Up/Down Direction>
With the unit running, press the Airfl ow Up/Down button as necessary.
•
Each press changes the direction. The current direction is shown at 6.
• The change sequence and the available settings are as follows.
Remote controllerDisplay
Wired type
Wireless type
Swing
Swing
Auto 12
1
3
2
5
4
3
4
Set temperature +2 °C, +4 °F
Set temperature
Set temperature -2 °C, -4 °F
15 minutes (switches
from cooling to heating)
Because the room temperature is automatically adjusted in order to
maintain a fi xed effective temperature, cooling operation is performed
a few degrees warmer and heating operation is performed a few degrees cooler than the set room temperature once the temperature is
reached (automatic energy-saving operation).
6
* Note that during swing operation, the directional indication on the
screen does not change in sync with the directional vanes on the
unit.
Note:
Available directions depend on the type of unit connected. In the following cases, the actual air direction will differ from the direction
indicated on the remote controller display.
1. While the display is showing “STAND BY” or “DEFROST”.
2. Immediately after starting heater mode (while the system is waiting for
the mode change to take effect).
3. In heat mode, when room temperature is higher than the temperature
setting.
5. Operation
< How to set the fixed up/down air direction (Only for
wired remote controller) >
Note:
This function cannot be set depending on the outdoor unit to be connected.
• For PLA-A.BA, only the particular outlet can be fi xed to certain direction
with the procedures below. Once fi xed, only the set outlet is fi xed every
time air conditioner is turned on. (Other outlets follow UP/DOWN air
direction setting of remote controller.)
Horizontal airflow
Remote controller setting
The airflow direction of
this outlet is controlled by
the airflow direction setting of
remote contoller.
Downward
Fixing
The airflow direction of
this outlet is fixed
in particular direction.
When it is cold because of direct airflow,
the airflow direction can be fixed
horizontally to avoid direct airflow.
Explanation of word
• "Refrigerant address No." and "Unit No." are the numbers given to
each air conditioner.
• "Outlet No." is the number given to each outlet of air conditioner.
(Refer to the right.)
• "Up/Down air direction" is the direction (angle) to fi x.
Reset1
horizontal
2345
Operation buttons (During the fi xed airfl ow direction mode)
ON/OFF button
Resets the fixed airflow direction mode.
TEMP.
MENU
ON/OFF
MONITOR/SET
BACKDAY
PAR-21MAA
CLOCK
OPERATION
Mode button (Return button)
Moves between the selected(blinking)
parts.
Unit No.Outlet No.
ON/OFF
FILTER
CHECK
TEST
CLEAR
Up/Down air direction
Fan Speed button
Filter button
(<Enter> button)
Sends the information on
remote controller display.
Check button (Clear button)
·Refer to the next page for details.
Refrigerant addres No.
Press for 2
seconds to
change / cancel
"Fixed airflow
direction mode".
Outlet No.3
Outlet No.2
Outlet No.4
Outlet No.1
Note: "0" indicates all outlets.
Pressing the button with either refrigerant
address No., unit no. or outlet No. blinking, ...
Only the air conditioner with the No. on remote
controller and its outlet are set to the setting 5.
(Other outlets are closed.)
It is used to identify the air conditioner and
outlet to set.
Pressing the button with
Up/Down air direction indicater blinking
Attention
Only the air conditioner with the No. on Remote controller
and its outlet are fixed at "Up/Down air direction"
blinking.
This is used only to decide direction conclusively.
Attention: Be careful not to set wrong air conditioner.
MITSUBISHI
ELECTRIC
label
Set temperature buttons
Changes the selection(No.).
Unit No.
Outlet No.
"1-4"or "0"
Up/Down air direction
"1-4"
Down
5 steps or
cancel
Up
Refrigerant address No.
"00-15"
7
5. Operation
< Process for setting >
[1] To turn off air conditioner and change the remote
controller to "Fixed airfl ow direction mode"
1.Press ON/OFF button to turn off the air conditioner.
2.Press Fan Speed button and Filter button for more than 2
seconds simultaneously and it becomes the fi xed airfl ow direction
mode after a while.
"Fixed airflow direction mode" display
Air blows downward after it becomes
"fixed airflow direction mode"
[2] To select and identify the outlet to set
1.Press Set Temperature button to change number with the outlet No.
blinking. Select outlet No. to set.
[4] To cancel "Fixed airfl ow direction mode"
1.Press ON/OFF button to cancel "Fixed airfl ow direction mode".
It is also canceled by pressing Fan Speed button and Filter button
for more than 2 seconds simultaneously.
2.Do not operate remote controller for 30 seconds after the "Fixed airfl ow
direction mode" is canceled. It does not accept even if it is operated.
Unit No.
Outlet No.3
2.Press Filter
Outlet No.
Outlet No.2
button
Up/Down air direction
to send the information on remote controller.
Refrigerant addres No.
Outlet No.4
Outlet No.1
MITSUBISHI
ELECTRIC
label
Note: "0" indicates
all outlets.
3. Wait for 15 seconds . How does the air conditioner run?
Only the air from the selected outlet blows downward.
Go to step[3].
Air from the wrong outlet blows downward.
Repeat 1 and set again.
All outlets are closed.
The numbers of the air conditioner (refrigerant address No.,
Unit No.) are wrong. Refer to How to fi nd air conditioner No..
[3] To fi x air direction
1.Press Mode button (Return button) to blink Up/Down air direction
indicater.
2.Press Set Temperature button until the direction to set is chosen.
3.Press Filter button to send the information on remote controller to
air conditioner.
4.Wait for 15 seconds . How does the air conditioner run?
Airfl ow direction is set in the selected direction.
The fi xed setting completed (Go to step [4].)
Airfl ow direction is set in the wrong direction.
Repeat 2. and set again.
Unit No. Outlet No.
Air direction changes
This indicates NO FIXED SETTING(canceled)
Up/Down air direction
Refrigerant addres No.
8
5. Operation
How to fi nd air conditioner No.
Each air conditioner has its own refrigerant address No. and unit No.
(Example below).
To fi nd air conditioner No. to set, refer to the procedures below.
Air conditioner No. is found by its airflow direction with the unit No.
changed one after the other.
Refrigerant
address
No.”00”
Unit No.”1” Unit No.”2”Unit No.”1”
As for this air conditioner,
air conditioner No. is “Unit No.1”
of refrigerant address “0”.
Check from refrigerant address 00 at first.
Change to unit No.1 and check
Change to unit No.2 and check
Change to unit No.3 and check
Change to unit No.4 and check
Change to unit No.1 and check
Change to unit No.2 and check
Change to unit No.3 and check
Change to unit No.4 and check
Remote controller
Refrigerant
address
No.”01”
Unit No.”2”
[2] To check by changing unit No. one after the other
(Maximum unit No. is 4)
1.Press Mode button (Return button) and unit No. blinks.
Unit No.
Outlet No.
Up/Down air direction
Refrigerant addres No.
Adjust to the next unit No.with Set Temperature button .
(refrigerant address No.00 is remained.)
2. Press Filter button to send the information on remote controller.
3. Wait for 15 seconds . How does the air conditioner run?
Only air from the outlet which No. displayed on remote controller blows
downward.
No. displayed in remote controller is air conditioner No. (Checking
completed)
All outlets are closed.
Repeat [1] and check. (If all the numbers are checked up to No.4
and is not found, go to [3].)
"Err" is displayed on remote controller.
The refrigerant address does not have further unit No.. (Go to [3].)
Err
[3] To check Unit No. of following refrigerant address No.(Maxmum
refrigerant address No. is 15)
1.Press Mode button (Return button) to blink refrigerant address No..
Adjust refrigerant No. with Set Temperature button .
* By changing refrigerant address, unit No. and outlet No. turn to initial
display.
2.Go back to [2] and check Unit No. again from Unit No. 1 in order.
Change to unit No.1 and check
Change to unit No.2 and check
Change to unit No.3 and check
Change to unit No.4 and check
When "Err" is displayed, refrigerant address
does not heve further "unit No.".
Change to the next "refrigerant address No..
(Refrigerant No "00"~max. No."15")
Change to unit No.1 and check
Change to unit No.2 and check
Change to unit No.3 and check
Change to unit No.4 and check
<Process to fi nd air conditioner No.>
[1] To check refrigerant address No. and unit No.
1.Press Mode button (Return button) and unit No. or refrigerant
address No. blinks.
Adjust refrigerant address No.to "00" and unit No."1" with Set
Temperature button .
Unit No.
Outlet No.
2.Press Filter button to send the information on remote controller.
3. Wait for 15 seconds . How does the air conditioner run?
Only air from the outlet which No. displayed on remote controller
blows downward.
Refrigerant address No.00 and unit No.1 are the air conditioner No..
All outlets are closed.
Go to step [2].
Up/Down air direction
Refrigerant addres No.
Unit No.
Outlet No.
Up/Down air direction
Refrigerant addres No.
To clear fi xed setting
To clear all fi xed setting(reset to factory default), press check button(clear
botton) for more than 3 seconds in fi xed airfl ow direction mode.
Display of remote controller blinks and the set information is cleared.
Note:
This operation clears the fixed setting information of all air
conditioner connected to the remote controller.
5.6. Ventillation
For LOSSNAY combination
5.6.1. For Wired Remote-controller
To run the ventilator together with the indoor unit:
Press the ON/OFF button .
• The Vent indication appears on the screen (at 8). The ventilator
will now automatically operate whenever the indoor unit is running.
To run the ventilator independently:
Press the Mode button until appears on the display. This
will cause the ventilatoPr to start.
To change the ventilator force:
Press the Ventilation button as necessary.
• Each press toggles the setting, as shown below.
Low
5.6.2. For Wireless Remote-controller
The ventillator will automatically operate when the indoor unit turns on.
No indication on the wireless remote controller.
High
9
6. Timer
6.1. For Wired Remote-controller
You can use Function Selection of remote controller to select which of
three types of timer to use: Weekly timer, Simple timer, or Auto
Off timer.
6.1.1. Weekly Timer
The weekly timer can be used to set up to eight operations for each
day of the week.
• Each operation may consist of any of the following: ON/OFF time
together with a temperature setting, or ON/OFF time only, or temperature setting only.
• When the current time reaches a time set at this timer, the air conditioner carries out the action set by the timer.
Time setting resolution for this timer is one minute.
Note:
*1. Weekly Timer/Simple Timer/Auto Off Timer cannot be used at the same
time.
*2. The weekly timer will not operate when any of the following conditions is
in effect.
The timer feature is off; the system is in an malfunction state; a test run
is in progress; the remote controller is undergoing self-check or remote
controller check; the user is in the process of setting a function; the user
is in the process of setting the timer; the user is in the process of setting
the current day of the week or time; the system is under central control.
(Specifi cally, the system will not carry out operations (unit on, unit off or
temperature setting) that are prohibited during these conditions.)
Operation No.
4
BAC KDAY
PAR-21MAA
TEMP.
MENU
MONITOR/SET
CLOCK
32
SUN
ON/OFF
Day Setting
ON
C
˚F
OPERATION
WEEKLY
ON/OFF
FILTER
CHECK
CLEAR
1
TEST
<Setting the Weekly Timer>
Shows the time
setting
SUN
C
˚F
Shows the selected operation (ON or OFF)
65
* Does not appear if operation is not set.
ON
WEEKLY
Shows the temperature setting
* Does not appear if temperature
7
is not set.
5. Press the appropriate Set Time button as necessary to set the desired time (at 5).
* As you hold the button down, the time fi rst increments in minute in-
tervals, then in ten-minute intervals, and then in one-hour intervals.
6. Press the ON/OFF button to select the desired operation (ON or
OFF), at 6.
* Each press changes the next setting, in the following sequence: No
display (no setting)
“ON” “OFF”
7. Press the appropriate Set Temperature button to set the desired
temperature (at 7).
* Each press changes the setting, in the following sequence: No dis-
play (no setting) 75 77 ... 84 87 53 ... 73
No display.
(Available range: The range for the setting is 12 °C, 53 °F to 30 °C,
87 °F. The actual range over which the temperature can be controlled,
however, will vary according to the type of the connected unit.)
8. After making the appropriate settings at Steps 5, 6 and 7, press the
button to lock in the values.
Filter
To clear the currently set values for the selected operation, press and
quickly release the Check (Clear) button
once.
* The displayed time setting will change to “—:—”, and the On/Off
and temperature settings will all disappear.
(To clear all weekly timer settings at once, hold down the Check
(Clear) button for two seconds or more. The display will begin
blinking, indicating that all settings have been cleared.)
Note:
Your new entries will be cancelled if you press the Mode (Return) button
before pressing the Filter button .
If you have set two or more different operations for exactly the same time,
only the operation with the highest Operation No. will be carried out.
<How to Set the Weekly Timer>
1. Be sure that you are at a standard control screen, and that the weekly
1
timer indicator
is shown in the display.
2. Press the Timer Menu button , so that the “Set Up” appears on the
screen (at 2). (Note that each press of the button toggles the display
between “Set Up” and “Monitor”.)
3. Press the Timer On/Off (Set Day) button to set the day. Each press
advances the display at
quence: “Sun Mon Tues Wed Thurs Fri Sat”
3
to the next setting, in the following se-
“Sun” ... “Fri”
“Sat” “Sun Mon Tues Wed Thurs Fri Sat”...
4. Press the
the appropriate operation number (1 to 8)
or Operation button ( or ) as necessary to select
4
.
* Your inputs at Steps 3 and 4 will select one of the cells from the ma-
trix illustrated below.
(The remote-controller display at left shows how the display would
appear when setting Operation 1 for Sunday to the values indicated
below.)
Setup Matrix
Op No.SundayMonday...Saturday
• 8:30
No. 1
• ON
• 73 °F
• 10:00
No. 2
• OFF
...
No. 8
<Operation 1 settings for Sunday>
Start the air conditioner at 8:30, with
the temperature set to 73 °F.
Note:
By setting the day to “Sun Mon Tues Wed Thurs Fri Sat”, you can set the
same operation to be carried out at the same time every day.
(Example: Operation 2 above, which is the same for all days of the week.)
• 10:00
• OFF
• 10:00
• OFF
<Operation 2 settings for every day>
Turn off the air conditioner at 10:00.
• 10:00
• OFF
9. Repeat Steps 3 to 8 as necessary to fi ll as many of the available cells
as you wish.
10. Press the mode (Return) button
to return to the standard control
screen and complete the setting procedure.
11. To activate the timer, press the Timer On/Off button , so that the
“Timer Off” indication disappears from the screen. Be sure that the
“Timer Off” indication is no longer displayed.
* If there are no timer settings, the “Timer Off” indication will blink on
the screen.
<How to View the Weekly Timer Settings>
SUN
Timer Settings
9
˚F
C
ON
OFF
WEEKLY
1
8
TIMER
1. Be sure that the weekly timer indicator is visible on the screen (at 1).
2. Press the Timer Menu button so that “Monitor” is indicated on the
screen (at 8).
3. Press the Timer On/Off (Set Day) button as necessary to select the
day you wish to view.
4. Press the or Operation button (
the timer operation shown on the display (at
or ) as necessary to change
9
).
* Each press will advance to the next timer operation, in order of time
setting.
5. To close the monitor and return to the standard control screen, press
the Mode (Return) button
.
<To Turn Off the Weekly Timer>
Press the Timer On/Off button so that “Timer Off” appears at 10.
TIME SUN
C
10
CF
˚F
WEEKLY
10
6. Timer
<To Turn On the Weekly Timer>
Press the Timer On/Off button so that the “Timer Off” indication (at
10
goes dark.
TIME SUN
C
˚F
WEEKLY
10
C
F
6.1.2. Simple Timer
You can set the simple timer in any of three ways.
• Start time only:
The air conditioner starts when the set time has elapsed.
• Stop time only:
The air conditioner stops when the set time has elapsed.
• Start & stop times:
The air conditioner starts and stops at the respective elapsed times.
The simple timer (start and stop) can be set only once within a 72-hour
period.
The time setting is made in hour increments.
Note:
*1. Weekly Timer/Simple Timer/Auto Off Timer cannot be used at the same
time.
*2. The simple timer will not operate when any of the following conditions
is in effect.
The timer is off; the system is in malfunction state; a test run is in prog-
ress; the remote controller is undergoing self-check or remote controller check; the user is in the process of selecting a function; the user is
in the process of setting the timer; the system is under central control.
(Under these conditions, On/Off operation is prohibited.)
4. With “ON” or “OFF” showing at 3: Press the appropriate Set Time but-
)
as necessary to set the hours to ON (if “ON” is displayed) or the
ton
hours to OFF (if “OFF” is displayed) at
4
.
• Available Range: 1 to 72 hours
5. To set both the ON and OFF times, repeat Steps 3 and 4.
* Note that ON and OFF times cannot be set to the same value.
6. To clear the current ON or OFF setting: Display the ON or OFF
setting(see step 3) and then press the Check (Clear) button so that
the time setting clears to “—” at
4
. (If you want to use only an ON setting or only an OFF setting, be sure that the setting you do not wish to
use is shown as “—”.)
7. After completing steps 3 to 6 above, press the Filter
button to lock
in the value.
Note:
Your new settings will be cancelled if you press the Mode (Return) button
before pressing the Filter
button .
8. Press the Mode (Return) button to return to the standard control
screen.
9. Press the Timer On/Off button to start the timer countdown. When
the timer is running, the timer value is visible on the display. Be sure
that the timer value is visible and appropriate.
<Viewing the Current Simple Timer Settings>
56
TIMERON
Timer Setting
OFFHrAFTER
SIMPLE
1
ONHr
AFTER
SIMPLE
TEMP.
MENU
BAC KDAY
MONITOR/SET
PAR-21MAA
CLOCK
ON/OFF
OPERATION
ON/OFF
FILTER
CHECK
CLEAR
TEST
<How to Set the Simple Timer>
Timer Setting
2
4
AFTER
ONHr
SIMPLE
Action (On or Off)
3
* “— —” is displayed if there is no
setting.
1
1. Be sure that you are at a standard control screen, and that the simple
timer indicator is visible in the display (at 1).
When something other than the Simple Timer is displayed, set it to
SIMPLE TIMER using the function selection of remote controller (see
8.[3] (3)) timer function setting.
2. Press the Timer Menu button , so that the “Set Up” appears on the
screen (at 2). (Note that each press of the button toggles the display
between “Set Up” and “Monitor”.)
3. Press the ON/OFF button to display the current ON or OFF simple
timer setting. Press the button once to display the time remaining to
ON, and then again to display the time remaining to OFF. (The ON/
OFF indication appears at 3).
• “ON” timer:
The air conditioner will start operation when the specifi ed number of
hours has elapsed.
• “OFF” timer:
The air conditioner will stop operation when the specifi ed number of
hours has elapsed.
1. Be sure that the simple timer indicator is visible on the screen (at 1).
2. Press the Timer Menu button , so that the “Monitor” appears on the
screen (at 5).
• If the ON or OFF simple timer is running, the current timer value will
appear at 6.
• If ON and OFF values have both been set, the two values appear
alternately.
3. Press the Mode (Return) button to close the monitor display and
return to the standard control screen.
<To Turn Off the Simple Timer...>
Press the Timer On/Off button so that the timer setting no longer appears on the screen (at 7).
7
˚C
F
˚C
˚F
SIMPLE
<To Turn On the Simple Timer...>
Press the Timer On/Off button so that the timer setting becomes
visible at 7.
˚C
F
7
ONHr
AFTER
˚C
˚F
SIMPLE
11
6. Timer
Examples
If ON and OFF times have both been set at the simple timer, operation
and display are as indicated below.
Example 1:
Start the timer with ON time set earlier than OFF time
ON Setting: 3 hours
OFF Setting: 7 hours
ONHr
AFTER
OFFHrAFTER
˚F
F
˚C
˚C
At Timer Start
Display shows the timer’s ON setting (hours
SIMPLE
remaining to ON).
At 3 hours after timer start
Display changes to show the timer’s OFF set-
SIMPLE
ting (hours remaining to OFF).
The time displayed is OFF setting (7 hours) –
ON setting (3 hours) = 4 hours.
At 7 hours after timer start
The air conditioner goes off, and will remain
SIMPLE
off until it is restarted.
Example 2:
Start the timer with OFF time set earlier than ON time
ON Setting: 5 hours
OFF Setting: 2 hours
OFFHrAFTER
˚F
F
˚C
˚C
At Timer Start
Display shows the timer’s OFF setting (hours
SIMPLE
remaining to OFF).
<How to Set the Auto Off Timer>
2
AFTEROFF
Timer Setting
3
AUTO OFF
1
1. Be sure that you are at a standard control screen, and that the Auto
Off timer indicator is visible in the display (at 1).
When something other than the Auto Off Timer is displayed, set it to
AUTO OFF TIMER using the function selection of remote controller
(see 8.[4]-3 (3)) timer function setting.
2. Hold down the Timer Menu button for 3 seconds so that the “Set
Up” appears on the screen (at 2).
(Note that each press of the button toggles the display between “Set
Up” and “Monitor”.)
3. Press the appropriate Set Time button as necessary to set the OFF
time (at 3).
4. Press the Filter button to lock in the setting.
Note:
Your entry will be cancelled if you press the Mode (Return) button
pressing the Filter
button .
before
5. Press the Mode (Return) button to complete the setting procedure
and return to the standard control screen.
6. If the air conditioner is already running, the timer starts countdown
immediately. Be sure to check that the timer setting appears cor-
rectly on the display.
<Checking the Current Auto Off Timer Setting>
45
Timer Setting
ONHr
AFTER
˚C
˚C
F
˚F
At 2 hours after timer start
Display changes to show the timer’s ON set-
SIMPLE
ting (hours remaining to ON).
The time displayed is ON setting (5 hours) –
OFF setting (2 hours) = 3 hours.
At 5 hours after timer start
The air conditioner comes on and will con-
SIMPLE
tinue to run until it is turned off.
6.1.3. Auto Off Timer
This timer begins countdown when the air conditioner starts and shuts
the air conditioner off when the set time has elapsed.
Available settings run from 30 minutes to 4 hours in 30-minute intervals.
Note:
*1. Weekly Timer/Simple Timer/Auto Off Timer cannot be used at the same
time.
*2. The Auto Off timer will not operate when any of the following conditions
is in effect.
The timer is off; the system is in malfunction state; a test run is in prog-
ress; the remote controller is undergoing self-check or remote controller check; the user is in the process of selecting a function; the user is
in the process of setting the timer; the system is under central control.
(Under these conditions, On/Off operation is prohibited.)
AFTEROFF
TEMP.
AUTO OFF
ON/OFF
TIMER
AFTER
OFF
1
AUTO OFF
1. Be sure that the “Auto Off” is visible on the screen (at 1).
2. Hold down the Timer Menu button for 3 seconds so that “Monitor”
4
is indicated on the screen (at
).
• The timer remaining to shutdown appears at 5.
3. To close the monitor and return to the standard control screen, press
the Mode (Return) button .
<To Turn Off the Auto Off Timer...>
Hold down the Timer On/Off button for 3 seconds so that “Timer
6
Off” appears (at
6
Alternatively, turn off the air conditioner itself. The timer value (at
) and the timer value (at 7) disappears.
7
˚C
F
˚C
˚F
AUTO OFF
7
will disappear from the screen.
7
AUTO OFF
<To Turn On the Auto Off Timer...>
Hold down the Timer On/Off button for 3 seconds. The “Timer Off”
indication disappears (at 6), and the timer setting comes on the dis-
7
play (at
).
Alternatively, turn on the air conditioner. The timer value will appear at
7
.
)
12
MENU
BACKDAY
MONITOR/SET
PAR-21MAA
CLOCK
ON/OFF
OPERATION
FILTER
CHECK
CLEAR
TEST
7
AFTEROFF
˚C
F
6
˚C
˚F
AUTO OFF
6. Timer
6.2. For Wireless Remote-controller
F
7. Other Functions
7.1. Locking the Remote Controller Buttons (Operation function limit controller)
If you wish, you can lock the remote controller buttons. You can use
the Function Selection of remote controller to select which type of lock
to use.
(For information about selecting the lock type, see section 8, item [2]
(1)). Specifi cally, you can use either of the following two lock types.
Press the
AUTO STOP
or
AUTO START
button (TIMER SET).
• Time can be set while the following symbol is blinking.
OFF timer : is blinking.
ON timer : is blinking.
Use the h and
Canceling the timer.
To cancel the OFF timer, press the
To cancel the ON timer, press the
min
buttons to set the desired time.
AUTO STOP
button.
AUTO START
button.
• It is possible to combine both OFF and ON timers.
• Pressing the ON/OFF button of the remote controller during timer
mode to stop the unit will cancel the timers.
• If the current time has not been set, the timer operation cannot be
used.
<How to Lock the Buttons>
1. While holding down the Filter button , press and hold down the ON/
OFF button for 2 seconds. The “Locked” indication appears on the
screen (at 1), indicating that the lock is now engaged.
* If locking has been disabled in Function Selection of remote control-
ler, the screen will display the “Not Available” message when you
press the buttons as described above.
Lock All Buttons:
Locks all of the buttons on the remote controller.
Lock All Except ON/OFF:
Locks all buttons other than the ON/OFF button.
Note:
The “Locked” indicator appears on the screen to indicate that buttons are
currently locked.
1
Lock Indicator
TIME SUN
FUNCTION
˚C
˚F
˚C
F
TEMP.
MENU
BACKDAY
MONITOR/SET
PAR-21MAA
ON/OFF
CLOCK
OPERATION
ON/OFF
FILTER
CHECK
CLEAR
TEST
1
F
˚C
˚F
FUNCTION
˚C
• If you press a locked button, the “Locked” indication (at 1) will blink
on the display.
˚C
F
˚F
1
FUNCTION
˚C
<How to Unlock the Buttons>
1. While holding down the Filter button , press and hold down the ON/
OFF button for 2 seconds—so that the “Locked” indication disappears from the screen (at 1).
˚C
˚C
F
˚F
1
13
7. Other Functions
7.2. Error Codes indication
ERROR CODE
ON/OFF
ON lamp
(Blinking)
Error CodeIndoor Unit No.
Alternating Display
If you have entered contact number to be called in the event of a problem, the screen displays this number.
(You can set this up under Function Selection of remote controller. For information, refer to section 8.)
Indoor Unit’s Refrigerant Address
If the ON lamp and error code are both blinking: This means that the air conditioner is out of order and operation has been stopped (and cannot re-
sume). Take note of the indicated unit number and error code, then switch off the power to the air conditioner and call your dealer or servicer.
When the Check button is pressed:
CALL:XXXX
XXX:XXX
ON/OFF
F
˚C
ERROR CODE
Error Code
˚C
˚F
ON/OFF
If only the error code is blinking (while the ON lamp remains lit): Operation is continuing, but there may be a problem with the system. In this case,
you should note down the error code and then call your dealer or servicer for advice.
* If you have entered contact number to be called in the event of a problem, push the Check button to display it on the screen. (You can set this up
under Function Selection of remote controller. For information, refer to section 8.)
8. Function Selection
Function selection of remote controller
The setting of the following remote controller functions can be changed using the remote controller function selection mode. Change the setting when
needed.
Item 1Item 2Item 3 (Setting content)
1. Change Language
(“CHANGE LAN-
GUAGE”)
2. Function limit
(“FUNCTION SELEC-
TION”)
3. Mode selection
(“MODE SELECTION”)
4. Display change
(“DISP MODE SET-
TING”)
Language setting to display• Display in multiple languages is possible
(1) Operation function limit setting (operation lock) (“LOCKING
FUNCTION”)
(2) Use of automatic mode setting (“SELECT AUTO MODE”)• Setting the use or non-use of “automatic” operation mode
(3) Temperature range limit setting (“LIMIT TEMP FUNCTION”) • Setting the temperature adjustable range (maximum, minimum)
(1) Remote controller main/sub setting (“CONTROLLER MAIN/
SUB”)
(2) Use of clock setting (“CLOCK”)• Setting the use or non-use of clock function
(3) Timer function setting (“WEEKLY TIMER”)• Setting the timer type
(4) Contact number setting for error situation (“CALL.”)• Contact number display in case of error
(1) Temperature display °C/°F setting (“TEMP MODE °C/°F”)• Setting the temperature unit (°C or °F) to display
(2) Room air temperature display setting (“ROOM TEMP DISP
Not necessary to set this mode. Refer to OPERATION MANUAL of
Optional Parts (Panel) for details on operation.
Fixed airfl ow direction mode
Not necessary to set this mode. Refer to OPERATION MANUAL of
indoor unit for details on operation.
The remote controller will be the main controller. (Initial setting value)
The remote controller will be the sub controller.
The clock function can be used. (Initial setting value)
The clock function can not be used.
Weekly timer can be used. (Initial setting value)
Auto off timer can be used.
Simple timer can be used.
Timer mode can not be used.
The set contact numbers are not displayed in case of error.
(Initial setting value)
The set contact numbers are displayed in case of error.
Display
mode setting
˚C
˚F
ON
OFF
ON
The temperature unit °C is used. (Initial setting value)
The temperature unit °F is used.
Room air temperature is displayed. (Initial setting value)
Room air temperature is not displayed.
One of “Automatic cooling” and “Automatic heating” is displayed
under the automatic mode is running. (Initial setting value)
OFF
Only “Automatic” is displayed under the automatic mode.
15
8. Function Selection
[Detailed setting]
[4]-1 CHANGE LANGUAGE setting
The language that appears on the dot display can be selected.
• Press the [
Italian (I), Chinese (CH), French (F), Japanese (JP)
Refer to the dot display table.
[4]-2 Function limit
(1) Operation function limit setting (operation lock)
• To switch the setting, press the [
no2: Operation lock setting is made on all buttons.
OFF (Initial setting value): Operation lock setting is not made.
* To make the operation lock setting valid on the normal screen, it
(2) Use of automatic mode setting
When the remote controller is connected to the unit that has auto-
• To switch the setting, press the [ ON/OFF] button .
The automatic mode is displayed when the operation mode is
OFF:
The automatic mode is not displayed when the operation mode
.
(3) Temperature range limit setting
After this setting is made, the temperature can be changed within
• To switch the setting, press the [
LIMIT TEMP COOL MODE:
The temperature range can be changed on cooling/dry mode.
LIMIT TEMP HEAT MODE:
The temperature range can be changed on heating mode.
The temperature range can be changed on automatic mode.
* When the setting other than OFF is made, the temperature
• To increase or decrease the temperature, press the [ TEMP.
(
• To switch the upper limit setting and the lower limit setting, press
English (GB), German (D), Spanish (E), Russian (RU),
no1: Operation lock setting is made on all buttons other than
is necessary to press buttons (Press and hold down the [FILTER]
and [ ON/OFF] buttons at the same time for two seconds.) on
the normal screen after the above setting is made.
matic operation mode, the following settings can be made.
ON (Initial setting value):
selected.
is selected
the set range.
LIMIT TEMP AUTO MODE:
OFF (initial setting): The temperature range limit is not active.
range limit setting on cooling, heating and automatic mode is
made at the same time. However, the range cannot be limited
when the set temperature range has not changed.
) or ( )] button .
the [
perature can be set.
MENU] button to change the language.
ON/OFF] button .
the [
ON/OFF] button.
ON/OFF] button .
] button . The selected setting will blink and the tem-
– 30°C, 67°F – 87°F
– 19°C, 87°F – 67°F
– 28°C, 63°F – 83°F
– 17°C, 83°F – 63°F
– 28°C, 67°F – 83°F
– 19°C, 83°F – 67°F
[4]-3 Mode selection setting
(1) Remote controller main/sub setting
• To switch the setting, press the [
(2) Use of clock setting
• To switch the setting, press the [ ON/OFF] button .
ON: The clock function can be used.
(3) Timer function setting
• To switch the setting, press the [ ON/OFF] button (Choose
WEEKLY TIMER (initial setting value):
The weekly timer can be used.
AUTO OFF TIMER:
The auto off timer can be used.
The simple timer can be used.
The timer mode cannot be used.
* When the use of clock setting is OFF, the “WEEKLY TIMER” can-
(4) Contact number setting for error situation
• To switch the setting, press the [ ON/OFF] button .
The set contact numbers are not displayed in case of error.
The set contact numbers are displayed in case of error.
CALL_:
The contact number can be set when the display is as shown
• Setting the contact numbers
To set the contact numbers, follow the following procedures.
Move the blinking cursor to set numbers. Press the [ TEMP.
[4]-4 Display change setting
(1) Temperature display °C/°F setting
• To switch the setting, press the [ ON/OFF] button .
°F: The temperature unit °F is used.
(2) Room air temperature display setting
• To switch the setting, press the [
ON: The room air temperature is displayed.
(3) Automatic cooling/heating display setting
• To switch the setting, press the [ ON/OFF] button .
One of “Automatic cooling” and “Automatic heating” is dis-
OFF:
Only “Automatic” is displayed under the automatic mode.
Main: The controller will be the main controller.
Sub: The controller will be the sub controller.
OFF: The clock function cannot be used.
one of the followings.).
SIMPLE TIMER:
TIMER MODE OFF:
not be used.
CALL OFF:
CALL **** *** ****:
above.
( ) and ( )] button to move the cursor to the right (left).
Press the [ CLOCK ( ) and ( )] button to set the numbers.
9. Emergency Operation for Wireless Remote-controller
When the remote controller cannot be used
When the batteries of the remote controller run out or the remote controller malfunctions, the emergency operation can be done using the emergency buttons on the grille.
Operation modeCOOLHEAT
Set temperature24°C, 75°F24°C, 75°F
Fan speedHighHigh
Airfl ow directionHorizontalDownward 5
Stopping operation
• To stop operation, press the
for more than 2
button
for more than 2
means the start of operation.
button or the button .
10. Care and Cleaning
C
C
F
˚F
TEMP.
Indicates that the fi lter needs cleaning.
Ask authorized people to clean the fi lter.
When resetting “FILTER” display
When the [FILTER] button is pressed two times successively after
cleaning the fi lter, the display goes off and is reset.
Note:
When two or more different types of indoor unit are controlled, the clean-
ing period differs with the type of filter. When the master unit cleaning
period arrives, “FILTER” is displayed. When the fi lter display goes off, the
cumulative time is reset.
“FILTER” indicates the cleaning period when the air conditioner was used
under general indoor air conditions by criteria time. Since the degree of
dirtiness depends on the environmental conditions, clean the fi lter accordingly.
The fi lter cleaning period cumulative time differs with the model.This indication is not available for wireless remote controller.
FILTER
ON/OFF
Filter removal
Caution:
• In removing the fi lter, precautions must be taken to protect your
eyes from dust. Also, if you have to climb up on a stool to do the
job, be careful not to fall.
• When the fi lter is removed, do not touch the metallic parts inside
the indoor unit, otherwise injury may result.
.
PLA-A
BA
Cleaning the fi lters
• Clean the filters using a vacuum cleaner. If you do not have a vacuum
cleaner, tap the fi lters against a solid object to knock off dirt and dust.
• If the fi lters are especially dirty, wash them in lukewarm water. Take care to
rinse off any detergent thoroughly and allow the fi lters to dry completely
before putting them back into the unit.
Caution:
• Do not dry the fi lters in direct sunlight or by using a heat source, such as
an electric heater: this may warp them.
• Do not wash the fi lters in hot water (above 50°C, 122°F), as this may warp
them.
• Make sure that the air fi lters are always installed. Operating the unit without
air fi lters can cause malfunction.
Caution:
• Before you start cleaning, stop operation and turn OFF the power supply.
• Indoor units are equipped with fi lters to remove the dust of sucked-in air.
Clean the fi lters using the methods shown in the following sketches.
18
Pull the knob on the intake grille in the direction indicated by
the arrow and it should open.
Open the intake grille.
Release the knob on the center edge of the intake grille and
pull the fi lter forward to remove the fi lter.
Knob Grille Intake grille Filter
11. Trouble Shooting
Having trouble?Here is the solution. (Unit is operating normally.)
Air conditioner does not heat or cool well.
When heating operation starts, warm air does not blow from the indoor
unit soon.
Clean the fi lter. (Airfl ow is reduced when the fi lter is dirty or clogged.)Check the temperature adjustment and adjust the set temperature.Make sure that there is plenty of space around the outdoor unit. Is the
indoor unit air intake or outlet blocked?
Has a door or window been left open?Warm air does not blow until the indoor unit has suffi ciently warmed up.
During heating mode, the air conditioner stops before the set room temperature is reached.
Airfl ow direction changes during operation or airfl ow direction cannot be
set.
When the airflow direction is changed, the vanes always move up and
down past the set position before fi nally stopping at the position.
A fl owing water sound or occasional hissing sound is heard. These sounds can be heard when refrigerant is fl owing in the air condi-
A cracking or creaking sound is heard.
The room has an unpleasant odor.
A white mist or vapor is emitted from the indoor unit.
Water or vapor is emitted from the outdoor unit.
The operation indicator does not appear in the remote controller display. Turn on the power switch. “
“
” appears in the remote controller display. During central control, “” appears in the remote controller display and
When restarting the air conditioner soon after stopping it, it does not operate even though the ON/OFF button is pressed.
Air conditioner operates without the ON/OFF button being pressed.
Air conditioner stops without the ON/OFF button being pressed.
Remote controller timer operation cannot be set. Are timer settings invalid?
“PLEASE WAIT” appears in the remote controller display.
An error code appears in the remote controller display.
Draining water or motor rotation sound is heard. When cooling operation stops, the drain pump operates and then stops.
When the outdoor temperature is low and the humidity is high, frost
may form on the outdoor unit. If this occurs, the outdoor unit performs a
defrosting operation. Normal operation should begin after approximately
10 minutes.
During cooling mode, the vanes automatically move to the horizontal
(down) position after 1 hour when the down (horizontal) airfl ow direction
is selected. This is to prevent water from forming and dripping from the
vanes.
During heating mode, the vanes automatically move to the horizontal
airfl ow direction when the airfl ow temperature is low or during defrosting
mode.
When the airfl ow direction is changed, the vanes move to the set posi-
tion after detecting the base position.
tioner or when the refrigerant fl ow is changing.
These sounds can be heard when parts rub against each due to expan-
sion and contraction from temperature changes.
The indoor unit draws in air that contains gases produced from the
walls, carpeting, and furniture as well as odors trapped in clothing, and
then blows this air back into the room.
If the indoor temperature and the humidity are high, this condition may
occur when operation starts.
During defrosting mode, cool airfl ow may blow down and appear like a
mist.
During cooling mode, water may form and drip from the cool pipes and
joints.
During heating mode, water may form and drip from the heat exchang-
er.
During defrosting mode, water on the heat exchanger evaporates and
water vapor may be emitted.
” will appear in the remote controller dis-
play.
air conditioner operation cannot be started or stopped using the remote
controller.
Wait approximately three minutes. (Operation has stopped to protect
the air conditioner.)
Is the on timer set?
Press the ON/OFF button to stop operation.
Is the air conditioner connected to a central remote controller?
Consult the concerned people who control the air conditioner.
Does “” appear in the remote controller display?
Consult the concerned people who control the air conditioner.
Has the auto recovery feature from power failures been set?
Press the ON/OFF button to stop operation.
Is the off timer set?
Press the ON/OFF button to restart operation.
Is the air conditioner connected to a central remote controller?
Consult the concerned people who control the air conditioner.
Does “” appear in the remote controller display?
Consult the concerned people who control the air conditioner.
If the timer can be set,
the remote controller display.
The initial settings are being performed. Wait approximately 3 minutes.The protection devices have operated to protect the air conditioner. Do not attempt to repair this equipment by yourself.
Turn off the power switch immediately and consult your dealer. Be sure
to provide the dealer with the model name and information that appeared in the remote controller display.
Wait approximately 3 minutes.
WEEKLY
,
SIMPLE
, or
AUTO OFF
appears in
19
11. Trouble Shooting
Having trouble?Here is the solution. (Unit is operating normally.)
Noise is louder than specifi cations.
The indoor operation sound level is affected by the acoustics of the par-
ticular room as shown in the following table and will be higher than the
noise specifi cation, which was measured in anechoic room.
Low sound
absorbing rooms
Offi ce, hotel
room
Nothing appears in the wireless remote controller display, the display is
faint, or signals are not received by the indoor unit unless the remote controller is close.
The operation lamp near the receiver for the wireless remote controller on
the indoor unit is blinking.
High sound
absorbing rooms
Location
examples
Noise levels3 to 7 dB6 to 10 dB9 to 13 dB
The batteries are low.
Replace the batteries and press the Reset button.
If nothing appears even after the batteries are replaced, make sure that
the batteries are installed in the correct directions (+, –).
The self diagnosis function has operated to protect the air conditioner. Do not attempt to repair this equipment by yourself.
Turn off the power switch immediately and consult your dealer. Be sure
to provide the dealer with the model name.
Broadcasting
studio, music
room, etc.
Normal rooms
Reception room,
hotel lobby, etc.
12. Specifi cations
ModelPLA-A12BAPLA-A18BAPLA-A24BAPLA-A30BAPLA-A36BAPLA-A42BA
Power source (Phase, Voltage<V>)
Frequency <Hz>
Fan motor <FLA>0.220.360.360.510.941.00
MCA <A>111122
MOCP <A>151515151515
Dimension (Height) <inch>10-3/16 (1-3/8)11-3/4 (1-3/8)
Dimension (Width) <inch>33-1/16 (37-3/8)
Dimension (Depth) <inch>33-1/16 (37-3/8)
Airfl owDRY <CFM>
(Low-Middle2-Middle1-High)WET <CFM>
Noise level (Low-Middle2-Middle1-High) <dB>27-28-29-3128-29-31-3228-29-31-3228-30-32-3432-34-37-4034-36-39-41
Net weight <lbs>49 (13)51 (13)55 (13)