Make sure that the inside and outside of refrigerant piping is clean and it has no contamination
such as sulfur hazardous for use, oxides, dirt,
shaving particles, etc.
In addition, use pipes with specified thickness.
Store the piping to be used during installation
indoors and keep both ends of the piping sealed
until just before brazing. (Leave elbow joints, etc.
in their packaging.)
Use ester oil, ether oil or alkylbenzene oil (small
amount) as the refrigerant oil applied to flares
and flange connections.
Charge refrigerant from liquid phase of gas
cylinder.
If the refrigerant is charged from gas phase, composition
change may occur in refrigerant and the efficiency will be
lowered.
Do not use refrigerant other than R410A.
If other refrigerant (R22 etc.) is used, chlorine in refrigerant can cause deterioration of refrigerant oil etc.
Use a vacuum pump with a reverse flow check
valve.
Vacuum pump oil may flow back into refrigerant cycle and
that can cause deterioration of refrigerant oil etc.
Use the following tools specifically designed for
use with R410A refrigerant.
The following tools are necessary to use R410A refrigerant.
Keep the tools with care.
If dirt, dust or moisture enters into refrigerant cycle, that can
cause deterioration of refrigerant oil or malfunction of compressor.
Do not use a charging cylinder.
If a charging cylinder is used, the composition of refrigerant will change and the efficiency will be lowered.
Flare tool
Electronic refrigerant
charging scale
Vacuum pump adaptor
Size adjustment gauge
Gauge manifold
Torque wrench
Gas leak detector
Charge hose
Tools for R410A
Contamination inside refrigerant piping can cause deterioration of refrigerant oil etc.
If dirt, dust or moisture enters into refrigerant cycle, that can
cause deterioration of refrigerant oil or malfunction of compressor.
If large amount of mineral oil enters, that can cause deterio
-
ration of refrigerant oil etc.
Ventilate the room if refrigerant leaks during
operation. If refrigerant comes into contact with
a flame, poisonous gases will be released.
SAFETY PRECAUTION
3-1. ALWAYS OBSERVE FOR SAFETY
Before obtaining access to terminals, all supply
circuits must be disconnected.
3-2. CAUTIONS RELATED TO NEW REFRIGERANT
Cautions for units utilising refrigerant R410A
[1] Cautions for service
(1) Perform service after collecting the refrigerant left in the unit completely.
(2) Do not release refrigerant in the air.
(3) After completing service, charge the cycle with specified amount of refrigerant.
(4) When performing service, install a filter drier simultaneously.
Be sure to use a filter drier for new refrigerant.
3
Gravimeter
Unit
[2] Additional refrigerant charge
When charging directly from cylinder
· Check that cylinder for R410A on the market is syphon type.
· Charging should be performed with the cylinder of syphon stood vertically. (Refrigerant is charged from liquid phase.)
[3] Service tools
Use the below service tools as exclusive tools for R410A refrigerant.
No.Specifications
1Gauge manifold·Only for R410A
·Use the existing fitting
·Use high-tension side pressure of 5.3MPa·G or over.
2Charge hose·Only for R410A
·Use pressure performance of 5.09MPa·G or over.
3Electronic scale
4Gas leak detector·Use the detector for R134a, R407C or R410A.
5Adaptor for reverse flow check·Attach on vacuum pump.
6Refrigerant charge base
7Refrigerant cylinder·Only for R410ATop of cylinder (Pink)
8Refrigerant recovery equipment
specifications
Cylinder with syphon
. (UNF1/2)
4
4
Auto Air Swing Vane
Disperses airflow up and
down and adjusts the angle
of airflow direction.
Grille
Filter
Removes dust and pollutants
from intake air.
Horizontal Air Outlet
Sets horizontal airflow automatically
during cooling or dehumidifying.
Air Intake
Intakes air from room.
Operation Section
Temperature setting buttons
Down
Up
Timer Menu button
(Monitor/Set button)
Mode button (Return button)
Set Time buttons
Back
Ahead
Timer On/Off button
(Set Day button)
Opening the
lid
ON/OFF button
Fan Speed button
Filter button
(<Enter> button)
Test Run button
Check button (Clear button)
Airflow Up/Down button
Louver button
( Operation button)
T o return operation
number
Ventilation button
( Operation button)
To go to next operation
number
Built-in temperature sensor
PART NAMES AND FUNCTIONS
● Indoor Unit
● Wired remote controller
TEMP.
MENU
MONITOR/SET
BACKDAY
PAR-21MAA
ON/OFF
ON/OFF
CLOCK
OPERATION
5
FILTER
CHECK
CLEAR
TEST
● Wired remote controller
●
●
˚F˚C
˚F˚C
ERROR CODE
AFTER
TIMER
TIME SUN MON TUE WED THU FRI SAT
ON
OFF
Hr
AFTER
FILTER
FUNCTION
ONLY1Hr.
WEEKLY
SIMPLE
AUTO OFF
Note:
“PLEASE WAIT” message
This message is displayed for approximately 3 minutes when power is supplied to the indoor unit or when the unit is recovering from a power failure.
“NOT A V AILABLE” message
This message is displayed if an invalid button is pressed (to operate a function that the indoor unit does not have).
If a single remote controller is used to operate multiple indoor units simultaneously that are different types, this message will not be displayed as
far as any of the indoor units is equipped with the function.
Display Section
For purposes of this explanation,
all parts of the display are shown
as lit. During actual operation, only
the relevant items will be lit.
Identifies the current operation
Shows the operating mode, etc.
*Multilanguage display is available.
“Centrally Controlled” indicator
Indicates that operation from the
remote controller has been prohibited by a master controller.
“Timer is Off” indicator
Indicates that the timer is off.
Temperature Setting
Shows the target temperature.
Day-of-Week
Shows the current day of the week.
Time/Timer Display
Shows the current time, unless the simple or Auto Off
timer is set.
If the simple or Auto Off timer is set, the time to be
switched off is shown.
“Sensor” indication
Displayed when the remote controller
sensor is used.
“Locked” indicator
Indicates that remote controller buttons have been locked.
“Clean The Filter” indicator
To be displayed on when it is time to
clean the filter.
Timer indicators
The indicator comes on if the corresponding timer is set.
Up/Down Air Direction indicator
Shows the direction of the
outcoming airflow.
“One Hour Only” indicator
Room Temperature display
Shows the room temperature. The room
temperature display range is 46–102°F.
The display blinks if the temperature
is less than 46
°
F
or 102°F
or more.
Louver display
Indicates the action of the swing louver.
Does not appear if the louver is not
running.
(Power On indicator)
Indicates that the power is on.
Fan Speed indicator
Shows the selected fan speed.
Ventilation indicator
Appears when the unit is running in
Ventilation mode.
Displayed if the airflow is set to
Low or downward during COOL
or DRY mode. (Operation varies
according to model.)
The indicator goes off in one hour,
at which time the airflow direction
also changes.
6
ON/OFF TEMP
FAN
VANE
TEST RUN
AUTO STOP
AUTO START
h
min
LOUVER
MODE
CHECK
RESETSETCLOCK
MODEL
SELECT
NOT AVAILABLE
SWING
CHECK
FAN
TEST
RUN
˚F
˚C
AMPMSTOP
START
AMPM
COOL
DRY
AUTO
FAN
HEAT
VANE CONTROL button
Changes the air flow direction.
CLOCK button
RESET button
SET button
ON/OFF button
The unit is turned ON and OFF alternately
each time the button is pressed.
LOUVER button
Changes left / right airflow direction.
(Not available for this model.)
MODE SELECT button
Switches the operation mode between
COOLING/DRY/FAN/HEATING and AUTO
mode.
wIn case the outdoor unit is cooling only
type, the heating and auto mode are not
available.
CHECK-TEST RUN button
Performs an inspection check or test operation.
Do not use it for normal operation.
FAN SPEED SELECT button
Changes the fan speed.
TIMER display
Displays when in timer operation or when
setting timer.
button
Sets any desired room temperature.
CLOCK display
Displays the current time.
“ ” “ ” display
Displays the order of timer operation.
“ ” “ ” display
Displays whether timer is on or off.
Buttons used to set the “hour and minute” of
the current time and timer settings.
"h" and "min" buttons
Temperature setting display
indicates the desired temperature setting
which is set.
display
Displays selected fan speed.
display
The vertical direction of air flow is indicated.
display
Blinks when model is selected.
display
Lights up while the signal is transmitted to
the indoor unit when the button is pressed.
display
Indicate that the unit is being checked or
test-run.
OPERATION MODE display
OPERATION MODE display
Indicates which operation mode is in effect.
TIMER CONTROL buttons
AUTO STOP (OFF timer): when this switch
is set, the air conditioner will be automatically stopped at the preset time.
AUTO START (ON timer): when this switch
is set, the air conditioner will be automatically started at the preset time.
Please set the voltage using the
remote controller.
For the setting method, please refer to
the indoor unit Installation Manual.
SW1
SW2
Table 1
Table 2
Service board
Service board
MODELS
PLA-A,AA
1 2 3 4 5
ON
OFF
1 2 3 4 5
ON
OFF
MODELS
PLA-A12AA
Service board
1 2 3 4 5
ON
OFF
MODELS
PLA-A30AA
1 2 3 4 5
ON
OFF
PLA-A18AA
1 2 3 4 5
ON
OFF
PLA-A36AA
1 2 3 4 5
ON
OFF
PLA-A24AA
1 2 3 4 5
ON
OFF
PLA-A42AA
w1
NOTES:
1. Symbols used in wiring diagram above are, : Connector, : Terminal (block).
2. Indoor and outdoor connecting wires have polarities, make sure to match
terminal numbers (S1, S2, S3) for correct wirings.
3. Since the outdoor side electric wiring may change, be sure to check the outdoor
unit electric wiring diagram for servicing.
4. This diagram shows the wiring of Indoor and Outdoor connecting wires
(specification of 230V), adopting superimposed system of power and signal.
w1. Use copper supply wires.
Check code
Symptom
Check code
Symptom
P1Abnormality of room temperature thermistor(TH1)
Fb
Abnormality of indoor controller board
U*, F*
Abnormality in outdoor unit. Refer to outdoor unit wiring diagram.
FFFF
No corresponding unit
————
No trouble generated in the past
P2Abnormality of pipe temperature thermistor / Liquid(TH2)
P4Abnormality of drain sensor(DS)
P5Malfunction of drain-up machine
P6Freezing / overheating protection is working.
P8Abnormality of pipe temperature
P9Abnormality of pipe temperature thermistor / Cond. / Eva.(TH5)
E0-E5
Abnormality of the signal transmission between remote
controller and indoor unit
E6-EF
Abnormality of the signal transmission between indoor unit and outdoor unit
[Self-diagnosis]
1. For details on how to operate self-diagnosis with the wireless remote control, refer to the technical manuals etc.
2. For the wired remote control : When you quickly press twice the CHECK switch on the remote control,
the unit begins self-diagnosis, and Check Codes generated in the past appear on the display.
For check Codes and Symptoms refer to the table below.
[LEGEND]
P.B
INDOOR POWER BOARD
SYMBOLNAME
I.B
INDOOR CONTROLLER BOARD
FUSEFUSE (6.3A/250V)
ZNRVARISTOR
CN2LCONNECTOR<LOSSNAY>
BCRFAN CONTROL ELEMENT
CN32CONNECTOR<REMOTE SWITCH>
Judge what is wrong and take a corrective action
according to “SELF-DIAGNOSIS ACTION TABLE” (10-3).
Identify the cause of the inferior phenomenon and take
a corrective action according to “TROUBLESHOOTING
BY INFERIOR PHENOMENA ” (10-4).
The inferior phenomenon is
not reoccurring.
Logged
Not logged
1Consider the temporary defects such as the work of
protection devices in the refrigerant circuit including
compressor, poor connection of wiring, noise and etc.
Re-check the symptom, and check the installation
environment, refrigerant amount, weather when the
inferior phenomenon occurred, and wiring related.
2Reset error code logs and restart the unit after finishing
service.
3There is no abnormality in electrical components,
controller boards, and remote controller.
1Recheck the abnormal symptom.
2Identify the cause of the inferior phenomenon and take
a corrective action according to “TROUBLESHOOTING
BY INFERIOR PHENOMENA ” (10-4).
3Continue to operate unit for the time being if the cause
is not ascertained.
4There is no abnormality in electrical components,
controller boards, remote controller etc.
10-1. TROUBLESHOOTING
<Error code display by self-diagnosis and actions to be taken for service (summary)>
Present and past error codes are logged and displayed on the wired remote controller or controller board of outdoor unit.
Actions to be taken for service and the inferior phenomenon reoccurrence at field are summarized in the table below. Check
the contents below before investigating details.
14
10-2. MALFUNCTION-DIAGNOSIS METHOD BY REMOTE CONTROLLER
ON/OFF
TEMP
FAN
VANE
MODE
CHECK
LOUVER
TEST RUN
AUTO STOP
AUTO START
h
min
RESET
SET
CLOCK
CHECK
CHECK
display
Temperature
button
CHECK
button
Refrigerant
address
display
HOUR
button
ON/OFF
button
<In case of trouble during operation>
When a malfunction occurs to the air conditioner, both indoor unit and outdoor unit will stop and operation lamp blinks to
inform unusual stop.
<Malfunction-diagnosis method at maintenance service>
[Procedure]
1. Press the CHECK button twice.
• "CHECK" lights, and refrigerant
address "00" blinks.
• Check that the remote controller's
display has stopped before continuing.
2. Press the temperature
buttons.
3. Point the remote controller at the
sensor on the indoor unit and
press the HOUR button.
4. Point the remote controller at the
sensor on the indoor unit and
press the ON/OFF button.
• Select the refrigerant address of the
indoor unit for the self-diagnosis.
Note: Set refrigerant address using the
outdoor unit’s DIP switch (SW1).
(For more information, see the
outdoor unit installation manual.)
• If an air conditioner error occurs, the
indoor unit's sensor emits an intermittent buzzer sound, the operation light
flashes, and the error code is
output.
(It takes 3 seconds at most for error
code to appear.)
• The check mode is cancelled.
To be continued to the next page.
15
[Output pattern A] Errors detected by indoor unit
[Output pattern B]
E9
*1If the beeper does not sound again after the initial
2 beeps to confirm the self-check start signal was received and
the OPERATION INDICATOR lamp does not come on,
there are no error records.
*2If the beeper sounds 3 times continuously “beep, beep, beep (0.4 + 0.4 + 0.4 sec.)” after the initial 2 beeps to confirm
the self-check start signal was received, the specified refrigerant address is incorrect.
OPERATION
INDICATOR
lamp blinking
pattern
BeepBeep Beep BeepBeep
Beep Beep
Off
Approx. 2.5 sec.OnApprox. 3 sec.On0.5 sec.On0.5 sec.On0.5 sec.
On
0.5 sec.
Off
Approx. 2.5 sec.OnApprox. 3 sec.On0.5 sec.On0.5 sec.
· · · Repeated
Number of blinks/beeps in pattern indicates the check
code in the following table (i.e., n=5 for “U2”)
Number of blinks/beeps in pattern indicates
the check code in the following table
n
th
1st2nd3
rd
1st2
nd
Self-check
starts
(Start signal
received)
Beeper sounds
[Output pattern B] Only A-CONTROL
OPERATION
INDICATOR
lamp blinking
pattern
Beep
Beep Beep BeepBeepBeep Beep
Off
Approx. 2.5 sec.On0.5 sec.On0.5 sec.On0.5 sec.
On
0.5 sec.
Off
Approx. 2.5 sec.On0.5 sec.On0.5 sec.
· · · Repeated
Number of blinks/beeps in pattern indicates the check
code in the following table (i.e., n=5 for “P5”)
Number of blinks/beeps in pattern indicates
the check code in the following table
n
th
1st2nd3
rd
1st2
nd
Self-check
starts
(Start signal
received)
Beeper sounds
• Refer to the following tables for details on the check codes.
[Output pattern A]
Beeper sounds/OPERATION
INDICATOR lamp blinks1 Check code
SymptomRemark
(Number of times)
Wireless remote controller
Wired remote controller
Beeper sounds/OPERATION
INDICATOR lamp blinks1 Check code
(Number of times)
Wireless remote controller
Wired remote controller
1P1
Intake sensor error
P9
Pipe (TH5) sensor error
2
P2
Pipe (TH2) sensor error
3E6,E7
Indoor/outdoor unit communication error
4P4
Drain sensor error
5
P5
PA
Drain pump error
Forced compressor stop
6P6
Freezing/Overheating protection operation
7EE
Communication error between indoor and outdoor units
8P8
Pipe temperature error
9E4, E5
Remote controller signal receiving error
10
–
11
–
–
–
Errors detected by unit other than indoor unit (outdoor unit, etc.)
Abnormal high discharging temperature/49C worked/
insufficient refrigerant
6
Abnormal high pressure (63H worked)/Overheating
protection
operation
7
Abnormal temperature of heatsink
8
Outdoor unit fan
protection
stop
9
Compressor overcurrent interruption/Abnormal of power module
10
Abnormality of superheat due to low discharge temperature
11
Abnormality such as overvoltage or voltage shortage and
abnormal synchronous signal to main circuit/Current sensor error
12
13
U2
U5
UP
U3,U4
UF
U1,Ud
U8
U6
U7
U9,UH
Others
–
–
–
–
14
Other errors (Refer to the technical manual for the outdoor unit.)
As for outdoor
unit, refer to
outdoor unit's
service manual.
For details, check
the LED display
of the outdoor
controller board.
12Fb
Indoor unit control system error (memory error, etc.)
–
E0, E3
–E1, E2
Remote controller control board error
Remote controller transmission error
Compressor overcurrent interruption
16
•
If the unit cannot be operated properly after the test run has been performed, refer to the following table to find out the cause.
Symptom
Cause
Wired remote controllerLED 1, 2 (PCB in outdoor unit)
On the wireless remote controller with condition above, following phenomena take place.
• No signals from the remote controller can be received.
• Operation lamp is blinking.
• The buzzer makes a short ping sound.
PLEASE WAIT
PLEASE WAIT → Error code
Display messages do not
appear even when operation
switch is turned ON (operation
lamp does not light up).
For about 2
minutes after
power-on
Subsequent to
about 2 minutes
after power-on
After LED 1, 2 are lighted, LED 2 is
turned off, then only LED 1 is
Only LED 1 is lighted. →
LED 1, 2 blink.
Only LED 1 is lighted.
→
LED 1 blinks twice,
LED 2 blinks once.
•
For about 2 minutes after power-on,operation
of the remote controller is not possible
due to system start-up. (Correct operation)
•Connector for the outdoor unit’s protection
device is not connected.
•Reverse or open phase wiring for the outdoor
unit’s power terminal block (L1, L2, GR)
•Incorrect wiring between indoor and outdoor
units (incorrect polarity of S1, S2, S3)
•Remote controller wire short
Note:
Operation is not possible for about 30 seconds after cancellation of function selection. (Correct operation)
For description of each LED (LED1, 2, 3) provided on the indoor controller, refer to the following table.
LED1 (power for microcomputer)Indicates whether control power is supplied. Make sure that this LED is
always lit.
LED2 (power for remote controller)
Indicates whether power is supplied to the remote controller.
This LED lights only in the case of the indoor unit which is connected to the
outdoor unit refrigerant address “0”.
LED3 (communication between indoor and
outdoor units)
Indicates state of communication between the indoor and outdoor units.
Make sure that this LED is always blinking.
lighted.
(Correct operation)
• On wireless remote controller
The continuous buzzer sounds from receiving section of indoor unit.
Blink of operation lamp
• On wired remote controller
1Check code displayed in the LCD.
17
10-3. SELF-DIAGNOSIS ACTION TABLE
Error Code
P1
P2
P4
P5
Abnormal
Room temperature thermistor (TH1)
1 The unit is in 3-minute resume preven-
tion mode if short/open of thermistor is
detected. Abnormal if the unit does not
reset normally after 3 minutes. (The
unit returns to normal operation, if it
has been reset normally.)
2 Constantly detected during cooling,
drying, and heating operation.
Short: 90:(194˚F) or more
Open: -40:(-40˚F) or less
Pipe temperature thermistor/Liquid
(TH2)
1 The unit is in 3-minute resume
prevention mode if short/open of
thermistor is detected. Abnormal if the
unit does not reset normally after 3 minutes. (The unit returns to normal operation, if it has been reset normally.)
2 Constantly detected during cooling,
drying, and heating (except defrosting)
operation.
Short: 90:(194˚F) or more
Open: -40:(-40˚F) or less
Drain sensor (DS)
1 Suspensive abnormality, if short/open of
thermistor is detected for 30 seconds
continuously.
Turn off compressor and indoor fan.
Short/open is detected for 30 seconds con-
2
tinuously during suspensive abnormality.
(The unit returns to normal operation, if
it has been reset normally.)
3 Detect the following condition.
• During cooling and drying operation
• In case that pipe <liquid> temperature
- room temperature <-10deg
(Except defrosting)
• When pipe <liquid> temperature or
room temperature is short/open temperature.
• During drain pump operation
Malfunction of drain pump (DP)
1 Suspensive abnormality, if thermistor
of drain sensor heats itself and
temperature rises slightly. Turn off
compressor and indoor fan.
2 Drain pump is abnormal if the condition
above is detected during suspensive
abnormality.
3 Constantly detected during drain pump
operation.
point and detection method
1 Defective thermistor
2 Contact failure of connector
3 Breaking of wire or contact
4 Defective indoor controller
1 Defective thermistor
2 Contact failure of connector
3 Breaking of wire or contact
4 Defective refrigerant circuit is
5 Defective indoor controller board
1 Defective thermistor
2 Contact failure of connector
3 Breaking of wire or contact
4 Defective indoor controller board
1 Malfunction of drain pump
2 Defective drain
3 Attached drop of water at the
4 Defective indoor controller board
Note: Refer to the manual of outdoor unit for the details of display
such as F, U, and other E.
Cause
characteristics
(CN20) on the indoor controller
board (Insert failure)
failure of thermistor wiring
board
characteristics
(CN21) on the indoor controller
board (Insert failure)
failure of thermistor wiring
causing thermistor temperature
of 90:(194˚F) or more or
-40:(-40˚F) or less.
characteristics
(CN31) on the indoor controller
board (Insert failure)
failure of drain sensor wiring
3.0k"
If you put force on (draw or bend) the lead wire
with measuring resistance value of thermistor
breaking of wire or contact failure can be detected.
2 Check contact failure of connector (CN20) on
the indoor controller board. Refer to 10-7.
Turn the power on again and check restart
after inserting connector again.
4 Check room temperature display on remote
controller.
Replace indoor controller board if there is abnormal difference with actual room temperature.
Turn the power off, and on again to operate
after check.
1–3 Check resistance value of thermistor.
For characteristics, refer to (P1) above.
2 Check contact failure of connector (CN21) on
the indoor controller board. Refer to 10-7.
Turn the power on and check restart after
inserting connector again.
4 Check pipe <liquid> temperature with remote
controller in test run mode. If pipe <liquid>
temperature is extremely low (in cooling
mode) or high (in heating mode), refrigerant
circuit may have defect.
5 Check pipe <liquid> temperature with remote
controller in test run mode. If there is extreme
difference with actual pipe <liquid> temperature,
replace indoor controller board.
Turn the power off, and on again to operate
after check.
the indoor controller board. Refer to 10-7.
Turn the power on again and check restart
after inserting connector again.
4 Replace indoor controller board if drain
pump operates with the line of drain sensor
connector CN31-1 and 2 is short-circuited,
and abnormality reappears.
Turn the power off, and on again to operate
after check.
1 Check if drain pump works.
2 Check drain function.
3 Check the setting of lead wire of drain sensor
and check clogs of the filter.
4 Replace indoor controller board if drain
pump operates with the line of drain sensor
connector CN31-1 and 2 is short-circuited
and abnormality reappears.
Refer to 10-7.
Turn the power off, and on again to operate
after check.
18
Error Code
Abnormal
Freezing/overheating protection is
working
1 Freezing protection (Cooling mode)
The unit is in 6-minute resume prevention
mode if pipe <liquid or condenser/evaporator> temperature stays under
-15:(5˚F) for 3 minutes, 3 minutes after
the compressor started. Abnormal if it
stays under -15:(5˚F) for 3 minutes
again within 16 minutes after 6-minute
resume prevention mode.
point and detection method
Cause
(Cooling or drying mode)
1 Clogged filter (reduced airflow)
2 Short cycle of air path
3 Low-load (low temperature)
operation out of the tolerance
range
4 Defective indoor fan motor
• Fan motor is defective.
• Indoor controller board is
defective.
5 Defective outdoor fan control
6 Overcharge of refrigerant
7 Defective refrigerant circuit
(clogs)
Countermeasure
(Cooling or drying mode)
1 Check clogs of the filter.
2 Remove shields.
4 Measure the resistance of fan motor's winding.
Measure the output voltage of fan's connector
(FAN) on the indoor controller board.
WThe indoor controller board should be
normal when voltage of AC 208/230V is
detected while fan motor is connected.
Refer to 10-7.
5 Check outdoor fan motor.
67 Check operating condition of refrigerant
circuit.
P6
P8
2 Overheating protection (Heating mode)
The units is in 6-minute resume
prevention mode if pipe <condenser /
evaporator> temperature is detected as
over 70:(158˚F) after the compressor
started. Abnormal if the temperature of
over 70:(158˚F) is detected again within 10 minutes after 6-minute resume
prevention mode.
Pipe temperature
<Cooling mode>
Detected as abnormal when the pipe temperature is not in the cooling range 3 minutes after compressor start and 6 minutes
after the liquid or condenser/evaporator pipe
is out of cooling range.
Note 1) It takes at least 9 minutes to
detect.
Note 2) Abnormality P8 is not detected in
drying mode.
Cooling range
TH: Lower temperature between liquid pipe
TH1: Intake temperature
<Heating mode>
When 10 seconds have passed after the
compressor starts operation and the hot
adjustment mode has finished, the unit is
detected as abnormal when
condenser/evaporator pipe temperature is
not in heating range within 20 minutes.
:-3 deg C[-5.4deg F]]
temperature (TH2) and
condenser/evaporator temperature
(TH5)
(TH-TH1)
(Heating mode)
1 Clogged filter (reduced airflow)
2 Short cycle of air path
3 Overload (high temperature)
operation beyond the tolerance
range
4 Defective indoor fan motor
• Fan motor is defective.
• Indoor controller board is
defective.
5 Defective outdoor fan control
6 Overcharge of refrigerant
7 Defective refrigerant circuit
(clogs)
8 Bypass circuit of outdoor unit
is defective.
1 Slight temperature difference
between indoor room
temperature and pipe <liquid
or condenser / evaporator>
temperature thermistor
• Shortage of refrigerant
• Disconnected holder of pipe
<liquid or condenser /
evaporator> thermistor
• Defective refrigerant circuit
2 Converse connection of
extension pipe (on plural units
connection)
3 Converse wiring of indoor/
outdoor unit connecting wire
(on plural units connection)
4 Defective detection of indoor
room temperature and pipe
<condenser / evaporator>
temperature thermistor
5 Stop valve is not opened
completely.
(Heating mode)
1 Check clogs of the filter.
2 Remove shields.
4
Measure the resistance of fan motor's winding.
Measure the output voltage of fan's connector
(FAN) on the indoor controller board.
WThe indoor controller board should be
normal when voltage of AC 208/230V is
detected while fan motor is connected.
Refer to 10-7.
5 Check outdoor fan motor.
6~8Check operating condition of refrigerant
circuit.
1~4 Check pipe <liquid or condenser /
evaporator> temperature with room
temperature display on remote controller
and outdoor controller circuit board.
Pipe <liquid or condenser / evaporator>
temperature display is indicated by setting
SW2 of outdoor controller circuit board as
follows.
Conduct temperature check with outdoor
controller circuit board after connecting
(
‘A-Control Service Tool(PAC-SK52ST)’.
23Check converse connection of extension
pipe or converse wiring of indoor/outdoor
unit connecting wire.
)
Note 3) It takes at least 27 minutes to
detect abnormality.
Note 4) It excludes the period of defrosting
(Detection restarts when defrosting
mode is over)
Heating range
:3 deg C[5.4deg F][
(TH5-TH1)
19
Error Code
P9
E0
or
E4
E3
or
E5
Abnormal point and detection method
Pipe temperature thermistor /
Condenser-Evaporator (TH5)
1 The unit is in 3-minute resume protec-
tion mode if short/open of thermistor is
detected. Abnormal if the unit does not
get back to normal within 3 minutes.
(The unit returns to normal operation, if
it has been reset normally.)
2 Constantly detected during cooling, dry-
ing, and heating operation (except
defrosting)
Short: 90:(194˚F) or more
Open: -40:(-40˚F) or less
find blank of transmission path for 6 seconds and could not transmit.
(Error code: E3)
2 Remote controller receives transmitted
data at the same time, compares the
data, and when detecting it, judges
different data to be abnormal 30
continuous times. (Error code: E3)
1 Abnormal if indoor controller board could
not find blank of transmission path.
(Error code: E5)
2 Indoor controller board receives trans-
mitted data at the same time, compares
the data,and when detecting it, judges
different data to be abnormal 30
continuous times. (Error code: E5)
Cause
1 Defective thermistor
characteristics
2 Contact failure of connector
(CN29) on the indoor controller
board (Insert failure)
3 Breaking of wire or contact
failure of thermistor wiring
4 Temperature of thermistor is
90:(194˚F) or more or -40:
(-40˚F) or less caused by
defective refrigerant circuit.
5 Defective indoor controller
board
1 Contact failure at transmission
wire of remote controller
2 All remote controllers are set
as “sub” remote controller. In
this case, E0 is displayed on
remote controller, and E4 is
displayed at LED (LED1, LED2)
on the outdoor controller circuit
board.
3 Miswiring of remote controller
4 Defective transmitting receiving
circuit of remote controller
5 Defective transmitting receiving
circuit of indoor controller board
of refrigerant address “0”
6 Noise has entered into the
transmission wire of remote
controller.
1 2 remote controller are set as
“main.” (In case of 2 remote
controllers)
2 Remote controller is connected
with 2 indoor units or more.
3 Repetition of refrigerant
address
4 Defective transmitting receiving
circuit of remote controller
5 Defective transmitting receiving
circuit of indoor controller board
6 Noise has entered into trans-
mission wire of remote controller.
Countermeasure
1–3 Check resistance value of thermistor.
For characteristics, refer to (P1) above.
2 Check contact failure of connector (CN29)
on the indoor controller board. Refer to 10-7.
Turn the power on and check restart after
inserting connector again.
4 Operate in test run mode and check pipe
<condenser / evaporator> temperature with
outdoor controller circuit board. If pipe
<condenser / evaporator> temperature is
extremely low (in cooling mode) or high (in
heating mode), refrigerant circuit may have
defect.
5 Operate in test run mode and check pipe
<condenser / evaporator> temperature with
outdoor control circuit board. If there is
exclusive difference with actual pipe
<condenser / evaporator> temperature
replace indoor controller board.
There is no abnormality if none of above
comes within the unit.
Turn the power off and on again to operate.
In case of checking pipe temperature
with outdoor controller circuit board,
be sure to connect A-control service
(
tool (PAC-SK52ST).
1 Check disconnection or looseness of indoor
unit or transmission wire of remote controller.
2 Set one of the remote controllers “main”
if there is no problem with the action above.
3 Check wiring of remote controller.
• Total wiring length: max. 500m
(Do not use cable o 3 or more)
• The number of connecting indoor units:
max. 16 units
• The number of connecting remote controller: max. 2 units
When the above-mentioned problem 1~3 are not seen.4 Diagnose remote controllers.
a) When “RC OK” is displayed,
remote controllers have no problem.
Turn the power off, and on again to
check. If abnormality generates again,
replace indoor controller board.
b) When “RC NG” is displayed,
replace remote controller.
c) When “RC E3” is displayed,
d) When “ERC 00-06” is displayed,
[ c),d)→Noise may be causing abnormality. ]
∗ If the unit is not normal after replacing
indoor controller board in group control,
the indoor controller board of address
“0” may be abnormal.
1 Set a remote controller to main, and the
other to sub.
2 Remote controller is connected with only 1
indoor unit.
3 The address changes to a separate setting.
4~6 Diagnose remote controller.
a) When “RC OK” is displayed, remote con-
trollers have no problem.
Turn the power off, and on again to check.
When becoming abnormal again, replace
indoor controller board.
b)When “RC NG” is displayed, replace
remote controller.
c)When “RC E3” or “ERC 00-66” is displayed,
noise may be causing abnormality.
)
20
Error Code
E6
E7
Fb
E1
or
E2
Abnormal point and detection method
Indoor/outdoor unit communication
error (Signal receiving error)
1 Abnormal if indoor controller board
cannot receive any signal normally for 6
minutes after turning the power on.
2 Abnormal if indoor controller board
cannot receive any signal normally for 3
minutes.
3 Consider the unit as abnormal under the
following condition: When 2 or more
indoor units are connected to 1
outdoor unit, indoor controller board
cannot receive a signal for 3 minutes
from outdoor controller circuit board, a
signal which allows outdoor controller
circuit board to transmit signals.
Indoor/outdoor unit communication
error (Transmitting error)
Abnormal if “1” receiving is detected 30
times continuously though indoor controller
board has transmitted “0”.
Indoor controller board
Abnormal if data cannot be normally read
from the nonvolatile memory of the indoor
controller board.
Remote controller control board
1 Abnormal if data cannot be normally
read from the nonvolatile memory of the
remote controller control board.
(Error code: E1)
2 Abnormal if the clock function of remote
controller cannot be normally operated.
(Error code: E2)
Cause
1 Contact failure, short circuit or,
miswiring (converse wiring) of
indoor/outdoor unit connecting
wire
cuit board. (Connect A-control service tool,
PAC-SK52ST.)
Refer to EA-EC item if LED displays EA-EC.
1 Check disconnection or looseness of indoor/
outdoor unit connecting wire of indoor unit or
outdoor unit.
Check all the units in case of twin indoor
unit system.
2-4 Turn the power off, and on again to
check. If abnormality generates again,
replace indoor controller board or outdoor
controller circuit board.
∗ Other indoor controller board may have
defect in case of twin indoor unit system.
1-3 Turn the power off, and on again to
check. If abnormality generates again,
replace indoor controller board.
1 Replace indoor controller board.
Countermeasure
PA
(2502)
(2500)
Forced compressor stop
(due to water leakage abnormality)
When the intake temperature subtracted
1
with liquid pipe temperature is less than
-10:(14˚F), drain sensor detects
whether it is soaked in the water or not
at the interval of 90 seconds.
pump will start operating when the drain
sensor detects to be soaked in the
water.)
2 The unit has a water leakage abnormality
when the following conditions, a and b,
are satisfied while the above-mentioned
detection is performed.
a) The drain sensor detects to be
soaked in the water 10 times in a row.
b) The intake temperature subtracted
with liquid pipe temperature is detected to be less than -10:(14˚F) for a
total of 30 minutes. (When the drain
sensor detects to be NOT soaked in
the water, the detection record of a
and b will be cleared.)
3 The drain sensor detection is performed
in operations other than cooling. (When
the unit stops operating, during heating
or fan operation, when the unit stops
because of some abnormality)
*Once the water leakage abnormality is
detected, abnormality state will not be
released until the main power is reset.
(Drain
1 Drain pump trouble
2 Drain defective
· Drain pump clogging
· Drain pipe clogging
3 Open circuit of drain sensor
side heater
4 Contact failure of drain sensor
connector
5 Dew condensation on drain
sensor
· Drain water trickles along
lead wire.
· Drain water waving due to filter
clogging
6 Extension piping connection
difference at twin system
7 Miswiring of indoor/ outdoor
connecting at twin system
8 Room temperature thermistor /
liquid pipe temperature thermistor detection is defective.
1 Check the drain pump.
2 Please confirm whether water can be
drained.
3 Confirm the resistance of the drain sensor.
4 Check the connector contact failure.
5 Check the drain sensor leadwire mounted.
Check the filter clogging.
6 Check the piping connection.
7 Check the indoor/ outdoor connecting wires.
8 Check the room temperature display of
remote controller.
Check the indoor liquid pipe temperature
display of outdoor controller board.
21
10-4. TROUBLESHOOTING BY INFERIOR PHENOMENA
Note: Refer to the manual of outdoor unit for the detail of remote controller.
Phenomena
(1)LED2 on indoor controller board
is off.
• When LED1 on indoor controller board is also off.
1 Power supply of rated voltage is not supplied to out-
door unit.
2 Defective outdoor controller circuit board
3 Power supply of 208/230V is not supplied to indoor
unit.
4 Defective indoor power board
5 Defective indoor controller board
(For the separate indoor/outdoor unit power sup-
ply system)
1 Power supply of 208/230V AC is not supplied to
indoor unit.
2 The connectors of the optional replacement kit are
not used.
3 Defective indoor controller board
4 Defective indoor power board
Cause
Countermeasure
1 Check the voltage of outdoor power
supply terminal block (L1,L2).
• When AC 208/230V is not detected,
check the power wiring to outdoor unit
and the breaker.
• When AC 208/230V is detected,
check 2 (below).
2 Check the voltage between outdoor
terminal block S1 and S2.
• When AC 208/230V is not detected.
—Check the fuse on outdoor controller
circuit board.
—Check the wiring connection.
• When AC 208/230V is detected,
check 3 (below).
3 Check the voltage between indoor terminal
block S1 and S2.
• When AC 208/230V is not detected,
check indoor/outdoor unit connecting
wire for miswiring.
• When AC 208/230V is detected,
check 4 (below).
4 Check voltage output from CN2S on indoor
power board (DC13.1V). Refer to 10-7-1.
• When no voltage is output, check the
wiring connection.
• When output voltage is between
DC12.5V and DC13.7V, check 5
(below).
5 Check the wiring connection between
indoor controller board and indoor power
board. Check the fuse on indoor controller
board. If no problems are found, indoor
controller board is defective.
1 Check the voltage of indoor power supply
terminal block (L1,L2).
• When AC208/230V is not detected,
check the power supply wiring.
• When AC208/230V is detected, check
2 (below).
2 Check that there is no problem in the
method of connecting the connectors.
• When there are problems in the method
of connecting the connectors, connect
the connector correctly referring to installation manual of an optional kit.
• When there is no problem in the
method of connecting the connectors,
check 3 (below).
3 Check voltage output from CNDK on
indoor controller board.
• When AC208/230V is not detected.
—Check the fuse on indoor controller board.
—Check the wiring connection between
indoor power supply terminal block and
CND on indoor controller board.
• When AC208/230V is detected, check
4 (below).
4 Check voltage output from CN2S on
indoor power board.
• When no voltage output, check the
wiring connection between CNDK on
indoor controller board and CNSK on
indoor power board.
If no problem are found, indoor power
board is defective.
• When DC12.5~13.7V is detected,
check the wiring connection between
CN2S on indoor power board and
CN2D on indoor power board.
If no problem are found, indoor con-
troller board is defective.
22
Phenomena
(1)LED2 on indoor controller board
is off.
Note: Refer to the manual of outdoor unit for the detail of remote
controller.
Cause
• When LED1 on indoor controller board is lit.
1 Mis-setting of refrigerant address for outdoor unit
(There is no unit corresponding to refrigerant
address “0”.)
Countermeasure
1 Check the setting of refrigerant address
for outdoor unit.
Set the refrigerant address to “0”.
(For grouping control system under
which 2 or more outdoor units are
connected, set one of the units to “0”.)
Set refrigerant address using SW1 (3-6)
on outdoor controller circuit board.
(2)LED2 on indoor controller board
is blinking.
(3)Upward/downward vane
performance failure
• When LED1 on indoor controller board is also blinking.
Connection failure of indoor/outdoor unit connecting
wire
• When LED1 is lit.
1 Miswiring of remote controller wires
Under twin indoor unit system, 2 indoor
wired together.
2 Refrigerant address for outdoor unit is wrong or not
set.
Under grouping control system, there are some units
whose refrigerant address is 0.
3 Shortcut of remote controller wires
4 Defective remote controller
1 The vane is not downward during defrosting and
heat preparation and when the thermostat is OFF in
HEAT mode. (Working of COOL protection function)
2 Vane motor does not rotate.
• Defective vane motor
• Breaking of wire or connection failure of connector
3 Upward/downward vane does not work.
• The vane is set to fixed position.
units are
Check indoor/outdoor unit connecting wire
for connection failure.
1 Check the connection of remote con-
troller wires in case of twin indoor unit
system. When 2 indoor units are wired in
one refrigerant system, connect remote
controller wires to one of those units.
2 Check the setting of refrigerant address
in case of grouping control system.
If there are some units whose refrigerant
addresses are 0 in one group, set one of
the units to 0 using SW1 (3-6) on outdoor
controller circuit board.
34 Remove remote controller wires and
check LED2 on indoor controller board.
• When LED2 is blinking, check the
shortcut of remote controller wires.
• When LED2 is lit, connect remote controller wires again and:
if LED2 is blinking, remote controller is
defective; if LED2 is lit, connection failure of remote controller terminal block
etc. has returned to normal.
1 Normal operation (The vane is set to hor-
izontal regardless of remote control.)
2 Check 2 (left).
• Check the vane motor. (Refer to “How
to check the parts”.)
• Check for breaking of wire or connection failure of connector.
3 Normal operation (Each connector on
vane motor side is disconnected.)
(4)Receiver for wireless remote
controller
1 Weak batteries of wireless remote controller
2 Contact failure of connector (CNB) on wireless
remote controller board
(Insert failure)
3 Contact failure of connector (CN90) on indoor con-
troller board (Insert failure)
4 Contact failure of connector between wireless
remote controller board and indoor controller board
23
1 Replace batteries of wireless remote con-
troller.
2~4
Check contact failure of each connector.
If no problems are found of connector,
replace indoor controller board. When
the same trouble occurs even if indoor
controller board is replaced, replace
wireless remote controller board.
10-5. EMERGENCY OPERATION
Receiver
Operation lamp
Emergency operation switch (cooling)
Emergency operation switch (heating)
Mode
Cooling
Heating
Set temperature
Fan speed
Airflow direction
24:, 75-F
High
Downward (70deg)
24:, 75-F
High
Horizontal (30deg)
wEmergency operation will be performed as follows.
10-5-1. When wireless remote controller has troubles or its battery is exhausted
1. Emergency operation is available in such a case using emergency operation switch equipped on the grille.
2. To start operation
• Cooling Operation·······Press (Cooling) switch.
• Heating Operation·······Press (Heating) switch.
wWhen the unit starts operating, the operation lamp is lit.
3. To stop operation
• Press either emergency operation switch (cooling/heating).
10-5-2. When wired remote controller or indoor unit microcomputer has troubles
1. If other defects are not found when trouble occurs, emergency operation starts as the indoor controller board switch (SWE)
is set to ON.
During the emergency operation, the indoor unit is as follows;
(1) Indoor fan high speed operation(2) Drain pump operation
2. For emergency operation of cooling or heating
When emergency operation for COOL or HEAT, setting of the switch (SWE) in the indoor controller board and outdoor unit
emergency operation are necessary.
3. Check items and notices as the emergency operation
(1) Emergency operation cannot be used as follows;
• When the outdoor unit is something wrong.
• When the indoor fan is something wrong.
• When drain overflow protection operation is detected during self-diagnosis. (Error code : P5)
(2) Emergency operation will be serial operation by the power supply ON/OFF.
ON/OFF or temperature, etc. adjustment is not operated by the remote controller.
(3) Do not operate for a long time as cold air is blown when the outdoor unit starts defrosting operation during heat emer-
gency operation.
(4) Cool emergency operation must be within 10 hours. Otherwise, heat exchanger of indoor unit may get frosted.
(5) After completing the emergency operation, return the switch setting, etc. in former state.
(6) Since vane does not work at emergency operation, position the vane slowly by hand.
24
10-6. HOW TO CHECK THE PARTS
PLA-A12AAPLA-A18AAPLA-A24AAPLA-A30AAPLA-A36AAPLA-A42AA
PLA-A12AA1PLA-A18AA1PLA-A24AA1PLA-A30AA1PLA-A36AA1PLA-A42AA1
Parts nameCheck points
Room temperature
thermistor (TH1)
Pipe temperature
thermistor/liquid(TH2)
Condenser/Evaporator
temperature thermistor
(TH5)
Disconnect the connector then measure the resistance using a tester.
(At the ambient temperature 10:(50˚F)~30:(86˚F))
Normal
4.3k"~9.6k"
Abnormal
Open or short
(Refer to the thermistor characteristic graph.)
Vane motor (MV)
Fan motor (MF)
Relay connector
1
Red
White
2
3
Black
Protector
OFF:130:
ON :80i20:
Drain pump (DP)
YLW
1
3
YLW
Drain sensor (DS)
1
2
3
Measure the resistance between the terminals using a tester.
(At the ambient temperature20:(68˚F))
NormalAbnormal
15k"Open or short
Measure the resistance between the terminals using a tester.
(Winding temperature 20:(68˚F))
Motor terminal
1
2
3
or
Relay connector
Red-Black
White-Black
PLA-A12/18/24/30AA
PLA-A12/18/24/30AA
87.2"
104.1"
Normal
1
PLA-A36/42AA
PLA-A36/42AA
32.6"
40.7"
1
Open or short
Measure the resistance between the terminals using a tester.
(Winding temperature 20:(68˚F))
NormalAbnormal
319"Open or short
Measure the resistance between the terminals using a tester.
Measure the resistance after 3 minutes have passed since the power supply was intercepted.
(At the ambient temperature 0:(32˚F)~60:(140˚F))
Normal
0.6k"~6.0k"
Abnormal
Open or short
(Refer to the thermistor characteristic graph.)
Abnormal
25
<Thermistor Characteristic graph>
< Thermistor for drain sensor >
0
1
2
3
4
5
6
7
8
9
10
Resistance (k")
6080
140
176
-2002040
-43268 104
:
°F
Temperature
Thermistor for
lower temperature
Room temperature thermistor(TH1)
Pipe temperature thermistor/liquid(TH2)
Condenser/evaporator temperature
thermistor(TH5)
Thermistor R0=15k' ±3%
Fixed number of B=3480 ± 2%
CN2D
Connect to the indoor power board
(CN2S)
(12.5~13.7V DC)
CN3C
Transmission
(Indoor/outdoor)
(0~24V DC)
CNDK
Connect to the indoor
power board (CNSK)
(208/230V AC)
FUSE
(6.3 A 250 V)
CND
Power supply input
(208/230V AC)
LED1
Power supply (I.B)
LED2
Power supply (R.B)
LED3
Transmission (Indoor/outdoor)
CN22
Connect to the terminal
block(TB5)
(Remote controller connecting
wire)
(10.4~14.6V DC)
CN20
Room temperature
thermistor (TH1)
CN21
Pipe temperature
thermistor/Liquid (TH2)
CN29
Condenser/evaporator
temperature thermistor (TH5)
CN31
Drain sensor (DS)
CN90
Connect to the wireless
remote controller board
(CNB)
CNP
Drain-pump output
(DP)
(208/230V AC)
CNC
Dew prevention
heater (H2)
(208/230V AC)
SWE
Emergency operation
FAN
Fan motor output
CN6V
Vane motor output
(MV)
CN41
Connector (HA terminal-A)
CN51
Centrally control
CN24
Heater output
(12V DC)
CN32
Remote switch
CN2L
Connector
(LOSSNAY)
Jumper wire J41, J42
Pair number setting with
wireless remote controller
SW2
Capacity setting
SW1
Model setting
28
10-8. FUNCTIONS OF DIP SWITCH AND JUMPER WIRE
Each function is controlled by the dip switch and the jumper wire on control P.C. board.
SW1 and SW2 are equipped only for service parts.
Model setting and capacity setting are memorized in the nonvolatile memory of the control P.C. board of
the unit.
(Marks in the table below) Jumper wire ( : Short : Open)
Jumper wire
SW1
SW2
J41
J42
Functions
Model
settings
Capacity
settings
Pair number
setting with
wireless
remote
controller
Setting by the dip switch and jumper wire
1
0
1
2
3 ~ 9
Service board
1 2 3 4 5
ON
OFF
Service board
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
Control PCB setting
J41J42
MODELS
PLA-A·AA
PLA-A·AA
MODELS
PLA-A12AA
PLA-A12AA1
PLA-A18AA
PLA-A18AA1
PLA-A24AA
PLA-A24AA1
PLA-A30AA
PLA-A30AA1
PLA-A36AA
PLA-A36AA1
PLA-A42AA
PLA-A42AA1
Wireless remote
controller setting
Remarks
<Initial setting>
Wireless remote controller: 0
Control PCB: (for both J41 and J42)
4 pair number settings are supported.
The pair number settings of the wireless remote
controller and indoor control PCB (J41/J42) are
given in the table on the left.
(' ' in the table indicates the jumper wire is disconnected.)
JP1
JP3
Unit type
setting
Indoor
controller
board type
setting
Model
Without TH5
With TH5
Indoor controller board type
For product
Service parts
JP1
There is no jumper (JP1) because these models
have the cond./eva. temperature thermistor (TH5).
(1) Slide the knob of air intake grille to the direction of the
arrow 1 to open the air intake grille.
(2) Remove the string hook from the panel to prevent the
grille from dropping.
(3) Slide the shaft in the hinge to the direction of the arrow2
and remove the air intake grille.
2. Removing the room temperature thermistor
(1) Remove the screw(✕1) in the room temperature thermistor
holder to remove the holder and the room temperature
thermistor.
(2) Remove the 1 screw from the bell mouth, and unscrew the
other 2 screws (fix to the oval hole which has a different
diameter) to remove the bell mouth.
(3) Hold the holder claw, and remove the room temperature
thermistor and holder.
(4) Disconnect the connector (CN20:red) on the indoor control
board.
Figure 1
Air intake grille
Grille
Air intake grille knob
Photo 1
Screws
Bell mouth
Room
temperature
thermistor
Air intake grille
3. Removing the electrical box
(1) Disconnect the lead wire of the vane motor from the clamp,
and disconnect the white connector (10P).
(2) Remove the room temperature thermistor with the holder.
(3) Remove the bell mouth.(See photo 1)
(4) Disconnect the relay connector in the electrical box.
Red (3P) for fan motor
Disconnect the connector on the indoor controller board.
White (2P) for pipe temperature detecting thermistor
Blue (3P) for drain pump
White (3P) for drain sensor
(5) Remove the 3 screws from the electrical box, loosen
another 2 screws to remove the box.
<Electrical parts in the electrical box>
Indoor controller board
Power board
Terminal block
Capacitor
30
Photo 2
Turbo fan
Electrical
box
Power
board
Nut
Indoor controller board
Capacitor
Terminal
block
Connector
OPERATING PROCEDURE
PHOTOS & ILLUSTRATIONS
4. Removing the fan motor
(1) Remove the bell mouth.(See photo 1)
(2) Remove the electrical box.(See photo 2)
(3) Remove the turbo fan nut.
(4) Pull out the turbo fan.
(5) Disconnect the connector of the fan motor lead wire.
(6) Remove the 4 nuts of the fan motor.
5. Removing the pipe temperature thermistor
and condenser evaporator temperature thermistor
(1) Remove the bell mouth.(See photo 1)
(2) Remove the electrical box.(See photo 2)
(3) Remove the turbo fan.
(4) Remove the screw of the service panel.
(5) Remove the service panel.
(6) Remove the pipe temperature thermistor which is inserted
into the holder installed to the thin copper pipe.
(7) Disconnect the 2-pin white connector.(CN21)
[Condenser/ evaporator temperature thermistor]
(8) Remove the drain pan. (See Photo 6)
(9) Remove the thermistor which is installed into the holder to
the indoor coil.
(10) Disconnect the 2-pin black connector. (CN29)
6. Removing the panel
(1) Remove the air intake grille.(See figure 1)
Corner panel (See figure 2)
(1) Remove the corner screw.
(2) Slide the corner panel to the direction of the arrow3, and
remove the corner panel.
Panel (See photo 5)
(1) Disconnect the connector that connects with the unit.
(2) Remove the 2 screws from the panel and loosen another
2 screws, which fix to the oval holes, have different diameters.
(3) Rotate the panel a little to remove the screws.
Photo 3
Photo 4
Figure 2
Corner
panel
Photo 5
Connector
Screw
Fan motor
Nut
Pipe temperature thermistor
Service access
Screw
Connector
Corner
panel
Nut
Panel
Screw
Panel
7. Removing the drain pan
(1) Remove the panel. (See photo 5)
(2) Remove the drain plug (Larger one), drain the remaining
water in the drain pan.
(3) Remove the corner cover. (2 screws)
(4) Remove the bell mouth (See photo 1)
(5) Remove the electrical box. (See photo 2)
(6) Remove the lead wire holder. (1 screw)
(7) Remove the 4 screws and pull out the drain pan.
w Pull out the left and right of the pan gradually.
Be careful not to crack or damage the pan.
31
Photo 6
Drain pan
Screw
Lead
wire
holder
Screw
Drain plug(Larger one)Corner cover
Screw
Screw
OPERATING PROCEDUREPHOTOS & ILLUSTRATIONS
8. Removing the drain pump and drain sensor
(1) Remove the panel. (See photo 5)
(2) Remove the bell mouth. (See photo 1)
(3) Remove the electrical box. (See photo 2)
(4) Remove the drain pan. (See photo 6)
(5) Remove the 3 screws of the drain pump.
(6) Cut the drain hose band, pull out the drain hose from the
drain pump.
(7) Pull out the drain pump.
(8) Remove the drain sensor and the holder.
9. Removing the heat exchanger
(1) Remove the panel. (See photo 5)
(2) Remove the bell mouth. (See photo 1)
(3) Remove the electrical box. (See photo 2)
(4) Remove the drain pan. (See photo 6)
(5) Remove the turbo fan. (See photo 3)
(6) Remove the 3 screws of the piping cover, and pull out
piping cover.
(7) Remove the 4 screws of the outer wall cover, and pull out
the outer wall cover.
(8) Remove the screw of the coil support.
(9) Remove the 2 screws of the coil.
(10) Pull out the heat exchanger.
Photo 7
Screw
Drain hose
Photo 8
Heat exchanger
Coil
support
Fixing band
Coil support
Drain sensor
Screw
Drain pump
Coil screws
Coil
support
32
Photo 9
Screw
Outer wall cover
Piping cover
Screws of
piping cover
12PARTS LIST (non-RoHS compliant)
ON/OFF
CENTRALLY CONTROLLED
ERROR CODE
CLOCK
ON OFF
˚C
CHECK
CHECK MODE
FILTER
TEST RUN
FUNCTION
˚C
1Hr.
NOT AVAILABLE
STAND BY
DEFROST
TEMP.
No.
Parts No.Parts Name
Specification
Q'ty / set
Remarks
(Drawing No.)
Wiring
Diagram
Symbol
Recom-
mended
Q'ty
1
2
3
4
5
6
7
8
9
10
11
12
AIR OUTLET GRILLE
VANE
CORNER PANEL
L.L FILTER
GRILLE ASSY
VANE MOTOR
VANE BUSH
GEAR (VANE)
GEAR
REMOTE CONTROLLER
CABLE ASSY
SCREW ASSY
PANEL PARTS
PLA-A12AAPLA-A18AAPLA-A24AA
PLA-A30AAPLA-A36AAPLA-A42AA
2
3
1
GEAR
9
GEAR
(VANE)
8
VANE
BUSH
7
6
VANE
MOTOR
10
Part number that is circled is not shown in the figure.
3
4
5
11
33
3
No.
Parts No.
Parts Name
Q'ty / set
PLA-A·AA
1218
24, 30
Wiring
Diagram
Symbol
Recommended
Q'ty
1
2
3
4
5
6
7
8
9
TURBO FAN
SPL WASHER
HEAT EXCHANGER
HEAT EXCHANGER
HEAT EXCHANGER
PIPE TEMPERATURE THERMISTOR
CONDENSER / EVAPORATOR TEMPERATURE THERMISTOR
MOTOR CAP
LEAD ASSY(F/M)
FAN MOTOR
RUBBER MOUNT
PANEL PARTS
PLA-A12AA1PLA-A18AA1PLA-A24AA1
PLA-A30AA1PLA-A36AA1PLA-A42AA1
1
GEAR
9
GEAR
(VANE)
8
VANE
2
BUSH
7
6
VANE
MOTOR
3
3
3
10
Part number that is circled is not shown in the figure.
4
5
11
38
FUNCTIONAL AND STRUCTURAL PARTS
PLA-A12AA1
PLA-A18AA1
PLA-A24AA1
PLA-A30AA1
1
98
7
MOTOR CAP
6
No.
RoHS
R01 E28 114
1
G
R01 09K 097
2
G
T7W H20 480
G
T7W H34 480
3
G
T7W H21 480
G
R01 H05 202
4
G
R01 H15 202
5
G
R01 E03 122
6
G
T7W E05 304
7
G
T7W E27 762
8
G
R01 A51 105
9
G
SPL WASHER
Parts No.
2
3
Q'ty / set
Parts Name
TURBO FAN
SPL WASHER
HEAT EXCHANGER
HEAT EXCHANGER
HEAT EXCHANGER
PIPE TEMPERATURE THERMISTOR
CONDENSER / EVAPORATOR TEMPERATURE THERMISTOR
MOTOR CAP
LEAD ASSY (F/M)
FAN MOTOR
RUBBER MOUNT
Specification
D17D6P70MS
PLA-A·AA1
1218
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
4
4
24, 30
1
1
1
1
1
1
1
1
4
5
CONDENSER
EVAPORATOR
TEMPERATURE
THERMISTOR
4
PIPE TEMPERATURE
THERMISTOR
Remarks
(Drawing No.)
Wiring
Diagram
Symbol
TH2
TH5
MF
Recom-
mended
Q'ty
39
Q'ty / set
36, 42
Specification
Remarks
(Drawing No.)
No.
Parts No.
Parts Name
Wiring
Diagram
Symbol
Recom-
mended
Q'ty
1
2
3
4
5
6
7
8
9
RoHS
G
G
G
G
G
G
G
G
G
TURBO FAN
SPL WASHER
HEAT EXCHANGER
PIPE TEMPERATURE THERMISTOR
FUNCTIONAL AND STRUCTURAL PARTS
PLA-A36AA1
PLA-A42AA1
1
2
DRAIN PLUG
14
3
4
5
DRAIN PLUG
13
CAPACITOR
12
TERMINAL BLOCK
11
TERMINAL BLOCK
10
6
TERMINAL BLOCK
9
7
ROOM
8
TEMPERATURE
THERMISTOR
42
43
TM
HEAD OFFICE : TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
CCopyright 2006 MITSUBISHI ELECTRIC ENGINEERING CO., LTD.
Distributed in Jun. 2007 No.OC370 REVISED EDITION-B PDF 9
Distributed in Aug. 2006 No.OC370 REVISED EDITION-APDF 9
Distributed in Feb. 2006 No.OC370 PDF 10
Made in Japan
New publication, effective Jun. 2007
Specifications subject to change without notice.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.