Mitsubishi Electric PLA-A12BA4, PLA-A30BA4, PLA-A36BA4, PLA-A42BA4, PLA-A18BA4 Installation Manual

...
Air-Conditioners
PLA-A·BA4
English
INSTALLATION MANUAL
For safe and correct use, read this manual and the outdoor unit installation manual thoroughly before installing the air-conditioner unit.
FOR INSTALLER
MANUAL DE INSTALACIÓN
Para un uso seguro y correcto, lea detalladamente este manual de instalación antes de montar la unidad de aire acondicionado.
PARA EL INSTALADOR
Français
MANUEL D’INSTALLATION
Avant d’installer le climatiseur, lire attentivement ce manuel, ainsi que le manuel d’installation de l’appareil exté­rieur pour une utilisation sûre et correct.
POUR L’INSTALLATEUR
2
Contents
1. Safety precautions .....................................................................................2
2. Installation location ....................................................................................3
3. Installing the indoor unit ............................................................................3
4. Installing the refrigerant piping ..................................................................5
5. Drainage piping work .................................................................................6
6. Electrical work ...........................................................................................7
7. Test run ....................................................................................................10
8. System control ........................................................................................13
9. Installing the grille ....................................................................................13
10. Easy maintenance function .....................................................................15
1. Safety precautions
Before installing the unit, make sure you read all the “Safety precautions”. Please report to your supply authority or obtain their consent before connecting this equipment to the power supply system.
Warning: Describes precautions that must be observed to prevent danger of injury or death to the user.
Caution: Describes precautions that must be observed to prevent damage to the unit.
After installation work has been completed, explain the “Safety Precautions,” use, and maintenance of the unit to the customer according to the information in the Operation Manual and perform the test run to ensure normal operation. Both the Installation Manual and Operation Manual must be given to the user for keeping. These manuals must be passed on to subsequent users.
: Indicates a part which must be grounded.
Warning:
Carefully read the labels affi xed to the main unit.
Caution: Appliances not accessible to the general public. Install the indoor unit at least 2.4 m (94-1/2 inch) above fl oor or grade level.
Warning:
• Ask a dealer or an authorized technician to install the unit.
• For installation work, follow the instructions in the Installation Manual and use tools and pipe components specifi cally made for use with refrigerant specifi ed in the outdoor unit installation manual.
• The unit must be installed according to the instructions in order to minimize the risk of damage from earthquakes, typhoons, or strong winds. An incorrectly installed unit may fall down and cause damage or injuries.
The unit must be securely installed on a structure that can sustain its weight.
• If the air conditioner is installed in a small room, measures must be taken to prevent the refrigerant concentration in the room from exceeding the safety limit in the event of refrigerant leakage. Should the refrigerant leak and cause the concentration limit to be exceeded, hazards due to lack of oxygen in the room may result.
• Ventilate the room if refrigerant leaks during operation. If refrigerant comes into contact with a fl ame, poisonous gases will be released.
• All electric work must be performed by a qualifi ed technician according to local regulations and the instructions given in this manual.
• Use only specifi ed cables for wiring.
• The terminal block cover panel of the unit must be fi rmly attached.
• Use only accessories authorized by Mitsubishi Electric and ask a dealer or an authorized technician to install them.
• The user should never attempt to repair the unit or transfer it to another location.
• After installation has been completed, check for refrigerant leaks. If refrigerant leaks into the room and comes into contact with the fl ame of a heater or portable cooking range, poisonous gases will be released.
• When installing or relocating, or servicing the air conditioner, use only the specifi ed refrigerant (R410A) to charge the refrigerant lines. Do not mix it with any other refrigerant and do not allow air to remain in the lines. If air is mixed with the refrigerant, then it can be the cause of abnormal high pressure in the refrigerant line, and may result in an explosion and other hazards. The use of any refrigerant other than that specifi ed for the system will cause mechanical failure or system malfunction or unit breakdown. In the worst case, this could lead to a serious impediment to securing product safety.
1.1. Before installation (Environment)
Caution:
Do not use the unit in an unusual environment. If the air conditioner is installed in areas exposed to steam, volatile oil (including machine oil), or sulfuric gas, areas exposed to high salt content such as the seaside, the performance can be signifi cantly reduced and the internal parts can be damaged.
• Do not install the unit where combustible gases may leak, be produced, ow, or accumulate. If combustible gas accumulates around the unit, fi re or explosion may result.
• Do not keep food, plants, caged pets, artwork, or precision instruments in the direct airfl ow of the indoor unit or too close to the unit, as these items can be damaged by temperature changes or dripping water.
• When the room humidity exceeds 80% or when the drainpipe is clogged, water may drip from the indoor unit. Do not install the indoor unit where such dripping can cause damage.
• When installing the unit in a hospital or communications office, be pre­pared for noise and electronic interference. Inverters, home appliances, high-frequency medical equipment, and radio communications equipment can cause the air conditioner to malfunction or breakdown. The air con­ditioner may also affect medical equipment, disturbing medical care, and communications equipment, harming the screen display quality.
1.2. Before installation or relocation
Caution:
• Be extremely careful when transporting the units. Two or more persons are needed to handle the unit, as it weighs 20 kg, 40 lbs or more. Do not grasp the packaging bands. Wear protective gloves as you can injure your hands on the fi ns or other parts.
• Be sure to safely dispose of the packaging materials. Packaging materials, such as nails and other metal or wooden parts may cause stabs or other injuries.
Thermal insulation of the refrigerant pipe is necessary to prevent condensation. If the refrigerant pipe is not properly insulated, condensation will be formed.
• Place thermal insulation on the pipes to prevent condensation. If the drainpipe is installed incorrectly, water leakage and damage to the ceiling, oor, furniture, or other possessions may result.
• Do not clean the air conditioner unit with water. Electric shock may result.
• Tighten all fl are nuts to specifi cation using a torque wrench. If tightened too much, the fl are nut can break after an extended period.
1.3. Before electric work
Caution:
• Be sure to install circuit breakers. If not installed, electric shock may result.
• For the power lines, use standard cables of suffi cient capacity. Otherwise, a short circuit, overheating, or fi re may result.
• When installing the power lines, do not apply tension to the cables.
Be sure to ground the unit. If the unit is not properly grounded, electric shock may result.
Use circuit breakers (ground fault interrupter, isolating switch (+B fuse), and molded case circuit breaker) with the specifi ed capacity. If the circuit breaker capacity is larger than the specifi ed capacity, breakdown or fi re may result.
1.4. Before starting the test run
Caution:
• Turn on the main power switch more than 12 hours before starting opera­tion. Starting operation just after turning on the power switch can severely damage the internal parts.
• Before starting operation, check that all panels, guards and other protec­tive parts are correctly installed. Rotating, hot, or high voltage parts can cause injuries.
• Do not operate the air conditioner without the air fi lter set in place. If the air lter is not installed, dust may accumulate and breakdown may result.
• Do not touch any switch with wet hands. Electric shock may result.
• Do not touch the refrigerant pipes with bare hands during operation.
After stopping operation, be sure to wait at least fi ve minutes before turning off the main power switch. Otherwise, water leakage or breakdown may result.
3
2. Installation location
Refer to the outdoor unit installation manual.
3. Installing the indoor unit
Fig. 3-1
Fig. 3-2
Fig. 3-3
5-29/32
6-5/16
6-5/16
6-5/16
6-5/16
3-17/32
33-27/32 to 35-13/16
(5/16)(5/16)
25/32 to 1-25/32 25/32 to 1-25/32
(inch)
25/32 to
1-25/32
25/32 to
1-25/32
31-7/8
37-3/8
33-1/16
7-3/8
33-1/16
5-5/16
11/16
+3/16
0
11/16
+3/16
0
*
1-15/16
to 2-3/4
*
4-1/8
1-3/8
C
D
Min. 98-7/16
Min. 19-11/16
(mm, inch)
Models
A A12, A18, A24, A30 80, 3-5/32 A36, A42 85, 3-11/32
B 74, 2-29/32 77, 3-1/32
15/16
3-17/32
A
B
*
6-11/16
*
5-1/2
*
7-15/32
2-3/8
11-3/16 14-27/32
23-13/16
-3/16
+1-3/8
33-27/32 to 35-13/16
37-3/8
24-13/32
3.1. Check the indoor unit accessories (Fig. 3-1)
The indoor unit should be supplied with the following accessories.
Accessory name Q'ty Installation template 1 Washers (with insulation)
Washers (without insulation)
4
4 Pipe cover (for refrigerant piping joint) Small diameter Large diameter
1
1 Band 8 Screw with washer (M5 × 25) for mounting grille 4 Drain socket 1 Insulation 1
3.2. Ceiling openings and suspension bolt installation locations (Fig. 3-2)
Caution:
Install the indoor unit at least 2.4m (94-1/2inch) above fl oor or grade level.
• Using the installation template (top of the package) and the gauge (supplied as
an accessory with the grille), make an opening in the ceiling so that the main unit can be installed as shown in the diagram. (The method for using the template and the gauge is shown.)
* Before using, check the dimensions of template and gauge, because they
change due to fl uctuations of temperature and humidity.
* The dimensions of ceiling opening can be regulated within the range shown
in Fig.3-2; so center the main unit against the opening of ceiling, ensuring that the respective opposite sides on all sides of the clearance between them becomes identical.
• Use M10 (3/8") suspension bolts.
* Suspension bolts are to be procured at the fi eld.
• Install securely, ensuring that there is no clearance between the ceiling panel &
grille, and between the main unit & grille.
A
Outer side of main unit
E
Grille
B
Bolt pitch
F
Ceiling
C
Ceiling opening
G
Multi function casement (option)
D
Outer side of Grille
H
Entire periphery
* Note that the space between ceiling panel of the unit and ceiling slab, etc. must be 10 to 15 mm,
25/64 to 19/32 inch.
*
When the optional multi-functional casement is installed, add 135 mm,
5-5/16 inch to the dimensions marked on the fi gure.
(mm, inch)
Models C D
A12, A18, A24, A30 241, 9-1/2" 258, 10-3/16"
A36, A42 281, 11-1/16" 298, 11-3/4"
3.3. Refrigerant and drainage piping locations of
indoor unit
The fi gure marked with * in the drawing represent the dimensions of the main unit excluding those of the optional multi function casement. (Fig. 3-3)
A
Drain pipe
B
Ceiling
C
Grille
D
Refrigerant pipe (liquid)
E
Refrigerant pipe (gas)
F
Water supply inlet
G
Main unit
*
When the optional multi-functional casement is installed, add 135 mm, 5-5/16inch
to the dimensions marked on the fi gure.
4
3. Installing the indoor unit
3.5. Suspension structure (Give site of suspension strong structure) (Fig. 3-5)
• The ceiling work differs according to the construction of the building. Building constructors and interior decorators should be consulted for details.
(1) Extent of ceiling removal: The ceiling must be kept completely horizontal and
the ceiling foundation (framework: wooden slats and slat holders) must be rein-
forced in order to protect the ceiling from vibration. (2) Cut and remove the ceiling foundation. (3) Reinforce the ends of the ceiling foundation where it has been cut and add ceil-
ing foundation for securing the ends of the ceiling board. (4) When installing the indoor unit on a slanted ceiling, attach a pillar between the
ceiling and the grille and set so that the unit is installed horizontally.
Wooden structures
• Use tie beams (single storied houses) or second fl oor beams (two story houses)
as reinforcing members.
• Wooden beams for suspending air conditioners must be sturdy and their sides
must be at least 6 cm, 2-3/8 inch long if the beams are separated by not more than 90 cm, 35-7/16 inch and their sides must be at least 9 cm, 3-9/16 inch long if the beams are separated by as much as 180 cm, 70-7/18 inch. The size of the suspension bolts should be ø10 (3/8"). (The bolts do not come with the unit.)
Ferro-concrete structures Secure the suspension bolts using the method shown, or use steel or wooden hangers, etc. to install the suspension bolts.
3.6. Unit suspension procedures (Fig. 3-6)
Suspend the main unit as shown in the diagram. Figures given in parentheses represent the dimensions in case of installing optional multi function casement.
1. In advance, set the parts onto the suspension bolts in the order of the washers
(with insulation), washers (without insulation) and nuts (double).
• Fit the washer with cushion so that the insulation faces downward.
• In case of using upper washers to suspend the main unit, the lower washers (with insulation) and nuts (double) are to be set later.
2. Lift the unit to the proper height of the suspension bolts to insert the mounting plate between washers and then fasten it securely.
3. When the main unit can not be aligned against the mounting hole on the ceiling, it is adjustable owing to a slot provided on the mounting plate.
• Make sure that A is performed within 17-22 mm, 11/16 to 7/8 inch. Damage could result by failing to adhere to this range. (Fig. 3-7)
Caution: Use the top half of the box as a protective cover to prevent dust or debris from getting inside the unit prior to installation of the decorative cover or when applying ceiling materials.
3.7. Confi rming the position of main unit and
tightening the suspension bolts (Fig. 3-8)
• Using the gauge attached to the grille, ensure that the bottom of the main unit is
properly aligned with the opening of the ceiling. Be sure to confi rm this, otherwise condensation may form and drip due to air leakage, etc.
• Confi rm that the main unit is horizontally levelled, using a level or a vinyl tube
lled with water.
• After checking the position of the main unit, tighten the nuts of the suspension
bolts securely to fasten the main unit.
The installation template (top of the package) can be used as a protective sheet to pre­vent dust from entering the main unit when the grilles are left unattached for a while or when the ceiling materials are to be lined after installation of the unit is fi nished.
*
As for the details of fi tting, refer to the instructions given on the Installation template.
3.4.
Branch duct hole and fresh air intake hole (Fig. 3-4)
At the time of installation, use the duct holes (cut out) located at the positions shown in Fig3-4, as and when required.
• A fresh air intake hole for the optional multi function casement can also be made.
Note: The fi gure marked with * in the drawing represent the dimensions of the main unit excluding those of the optional multi function casement. When installing the optional multi function casement, add 135 mm, 5-5/16 inch to the dimensions marked on the fi gure. When installing the branch ducts, be sure to insulate adequately. Otherwise condensation and dripping may occur. When installing the fresh air intake hole, be sure to remove the insulator
P
that is pasted on the indoor unit.
A
Branch duct hole
H
ø150 mm, ø5-29/32 inch cut out hole
B
Indoor unit
I
ø175 mm, ø6-7/8 inch burring hole pitch
C
Fresh air intake hole
J
Fresh air intake hole diagram
D
Drain pipe
K
3-ø2.8 mm, ø1/8 inch burring hole
E
Refrigerant pipe
L
ø125 mm, ø4-29/32 inch burring hole pitch
F
Branch duct hole diagramM ø100 mm, ø3-15/16 inch cut out hole
(view from either side)
N
Ceiling
G
14-ø2.8 mm, ø1/8 inch burring
hole
O
Detailed fi gure of removing the insulator
P
Insulator
Unit Grille Pillar
Ceiling Rafter Beam Roof beam
Use inserts rated at 100-150 kg, 220-331 lbs each (procure locally) Suspension bolts M10 (3/8") (procure locally) Steel reinforcing rod
23-13/16
31-57/64
Fig. 3-5
Suspension bolt Ceiling Nut Washer (with insulation) Mounting plate Washer (without insulation) Check using the Installation gauge
A=11/16
+3/16
0
11/16
4-1/8 (9-29/64)
+3/16
0
Main unit Ceiling Installation template (top of the package) Screwwith washer(Accessory)
Main unit Ceiling Gauge Ceiling opening dimensions
Fig. 3-6
Fig. 3-7
Fig. 3-8
(inch)
(inch)
(inch)
Min. 1-3/16
Fig. 3-4
#
"
13-25/32
3-17/32
70°
3-15/16 3-15/16 3-17/32
3-15/16
5-1/8
*6-3/32
*6-9/16
*6-7/32
120°
120°
!
5
4. Installing the refrigerant piping
4.1. Precautions
For devices that use R410A refrigerant
• Use ester oil, ether oil or alkylbenzene oil (small amount) as the refrigeration oil applied to the fl ared sections.
• Use C1220 copper phosphorus for copper and copper alloy seamless pipes, to connect the refrigerant pipes. Use refrigerant pipes with the thicknesses specifi ed in the table below. Make sure the insides of the pipes are clean and do not contain any harmful contaminants such as sulfuric compounds, oxidants, debris, or dust.
Warning: When installing or relocating, or servicing the air conditioner, use only the specifi ed refrigerant (R410A) to charge the refrigerant lines. Do not mix it with any other refrigerant and do not allow air to remain in the lines. If air is mixed with the refrigerant, then it can be the cause of abnormal high pressure in the refrigerant line, and may result in an explosion and other hazards. The use of any refrigerant other than that specifi ed for the system will cause mechanical failure or system malfunction or unit breakdown. In the worst case, this could lead to a serious impediment to securing product safety.
A12, A18 A24, A30, A36, A42
Liquid pipe
ø6.35 mm, ø1/4 inch
thickness 0.8mm, 1/32 inch
ø9.52 mm, ø3/8 inch
thickness 0.8mm, 1/32 inch
Gas pipe
ø12.7 mm, ø1/2 inch
thickness 0.8mm, 1/32 inch
ø15.88 mm, ø5/8 inch
thickness 1.0mm, 3/64 inch
• Do not use pipes thinner than those specifi ed above.
4.2. Connecting pipes (Fig. 4-1)
• When commercially available copper pipes are used, wrap liquid and gas pipes
with commercially available insulation materials (heat-resistant to 100 °C, 212 °F or more, thickness of 12 mm, 1/2 inch or more).
• The indoor parts of the drain pipe should be wrapped with polyethylene foam
insulation materials (specifi c gravity of 0.03, thickness of 9 mm, 23/64 inch or more).
• Apply thin layer of refrigerant oil to pipe and joint seating surface before
tightening fl are nut.
• Use two wrenches to tighten piping connections.
• Use refrigerant piping insulation provided to insulate indoor unit connections.
Insulate carefully.
B
Flare nut tightening torque
Copper pipe O.D.
(mm, inch)
Flare nut O.D.
(mm, inch)
Tightening torque
(N-m, ftlbs) ø6.35, 1/4 17, 43/64 14-18, 10-13 ø6.35, 1/4 22, 7/8 34-42, 25-30 ø9.52, 3/8 22, 7/8 34-42, 25-30 ø12.7, 1/2 26, 1-3/64 49-61, 35-44 ø12.7, 1/2 29, 1-9/64 68-82, 49-59
ø15.88, 5/8 29, 1-9/64 68-82, 49-59 ø15.88, 5/8 36, 1-27/64 100-120, 71-86 ø19.05, 3/4 36, 1-27/64 100-120, 71-86
C
Apply refrigerating machine oil over the entire fl are seat surface.
D
Use correct fl are nuts meeting the pipe size of the outdoor unit.
Available pipe size
A12, A18 A24, A30, A36, A42
Liquid side ø6.35
ø9.52
Gas side
ø12.7
ø15.88
: Factory fl are nut attachment to the heat exchanger.
90 0.5
A
R0.4~R0.8
45 2
Fig. 4-1
Die Copper pipe
B
Fig. 4-2
Flare cutting dimensions
Copper pipe O.D. Flaredimensions
(mm, inch) A dimensions (mm, inch)
6.35, 1/4 8.7 - 9.1, 11/32 - 23/64
9.52, 3/8 12.8 - 13.2, 1/2 - 33/64
12.7, 1/2 16.2 - 16.6, 41/64 - 21/32
15.88, 5/8 19.3 - 19.7, 49/64 - 25/32
19.05, 3/4 23.6 - 24.0, 15/16 - 61/64
Copper pipe O.D.
B (mm, inch)
mm (inch)
Flare tool for R410A
Clutch type
6.35 (1/4")
1.0 - 1.5, 3/64 - 1/16
9.52 (3/8")
1.0 - 1.5, 3/64 - 1/16
12.7 (1/2")
1.0 - 1.5, 3/64 - 1/16
15.88 (5/8")
1.0 - 1.5, 3/64 - 1/16
19.05 (3/4")
1.0 - 1.5, 3/64 - 1/16
6
4.3. Indoor unit (Fig. 4-3)
Heat insulation for refrigerant pipes:
1 Wrap the enclosed large-sized pipe cover around the gas pipe, making sure that
the end of the pipe cover touches the side of the unit.
2 Wrap the enclosed small-sized pipe cover around the liquid pipe, making sure
that the end of the pipe cover touches the side of the unit.
3 Secure both ends of each pipe cover with the enclosed bands. (Attach the
bands 20 mm, 25/32 inch from the ends of the pipe cover.)
• After connecting the refrigerant piping to the indoor unit, be sure to test the pipe connections for gas leakage with nitrogen gas. (Check that there is no refrigerant leakage from the refrigerant piping to the indoor unit.)
4.4. For twin/triple combination
Refer to the outdoor unit installation manual.
4. Installing the refrigerant piping
5. Drainage piping work
5.1. Drainage piping work (Fig. 5-1)
• Use VP25 (O.D. ø32 mm, 1-1/4 inch PVC TUBE) for drain piping and provide 1/100 or more downward slope.
• Be sure to connect the piping joints using a polyvinyl type adhesive.
• Observe the fi gure for piping work.
• Use the included drain hose to change the extraction direction.
1
Correct piping
C
Support metal
2
Wrong piping
K
Air bleeder
A
Insulation (9 mm, 23/64 inch or more)L Raised
B
Downward slope (1/100 or more)
M
Odor trap
Grouped piping
D
O.D. ø32 mm, 1-1/4 inch PVC TUBEH Downward slope (1/100 or more)
E
Make it as large as possible
I
O.D. ø38 mm, 1-1/2 inch PVC TUBE for
grouped piping. (9 mm, 23/64 inch or more insulation)
F
Indoor unit
G
Make the piping size large for grouped
piping.
J
Up to 850 mm, 33-7/16 inch
1. Connect the drain socket (supplied with the unit) to the drain port. (Fig. 5-2)
(Fix the tube using PVC adhesive then secure it with a band.)
2. Install a locally purchased drain pipe (PVC pipe, O.D. ø32mm, 1-1/4 inch).
(Fix the pipe using PVC adhesive then secure it with a band.)
3. Insulate the tube and pipe. (PVC pipe, O.D. ø32mm, 1-1/4 inch and socket)
4. Check that drain fl ows smoothly.
5. Insulate the drain port with insulating material, then secure the material with a
band. (Both insulating material and band are supplied with the unit.)
A
Unit
G
Drain pipe (O.D. ø32mm, 1-1/4inch PVC
TUBE)
B
Insulating material
H
Insulating material (purchased locally)
C
Band
I
Transparent PVC pipe
D
Drain port (transparent)
J
O.D. ø32 mm, 1-1/4 inch PVC TUBE
(Slope 1/100 or more)
E
Insertion margin
K
Drain socket
F
Matching
Fig. 4-3
Refrigerant pipe and insulating material
Pipe cover (large) Pipe cover (small) Refrigerant pipe (gas) Refrigerant pipe (liquid) Band Cross-sectional view of connection Pipe Insulating material Squeeze
,
Max. 65 ft
5 to 7 ft
Max. 6 inch
Fig. 5-1
Fig. 5-2
(inch)
7/16
11
1
7
6. Electrical work
6.1. Indoor unit (Fig. 6-1)
1. Remove the electrical wiring service panel.
2. Remove the electrical box cover.
3. For radio frequency interface. Connect the electric wires securely to CN105 (RED) of indoor controller board.
(Fig. 6-2) For wired remote controller. Wire the power cable and control cable separately through the respective wiring
entries given in the diagram.
• Do not allow slackening of the terminal screws.
• Leave excess cable so that the electrical box cover can be suspended below the
unit during servicing. (Approx. 50 to 100 mm, 2 to 4 inch)
A
Entry for control cable
B
Entry for power
C
Clamp
D
Electrical box cover
E
Service panel for electrical wiring
F
Temporary hook for electrical box cover
G
Indoor / Outdoor unit connecting terminals
H
Wired remote controller connector
I
Secure with the clamp
J
Earth terminal
K
Electrical box
L
Indoor controller board
6.1.1. Indoor unit power supplied from outdoor unit
The following connection patterns are available. The outdoor unit power supply patterns vary on models.
S1 S2
L N
1 2
S1 S2 S3
S3
ABC
D
E
F
G
I
H
CN105
RED
S1 S2
L N
1 2
S1 S2 S3
1
2
S1 S2 S3
S3
ABC
D
E
F
G
G
E
* Affi x label A that is included with the manuals near each wiring diagram for the indoor and outdoor units.
A Outdoor unit power supply
B Earth leakage breaker
C Wiring circuit breaker or isolating switch
D Outdoor unit
E Indoor earth
F Wired remote controller
G Indoor controller board
H Radio frequency interface for RF thermostat
I Indoor unit
* Affi x label A that is included with the manuals near each wiring diagram for the indoor and outdoor units.
Only for wired remote controller
A Outdoor unit power supply
B Earth leakage breaker
C Wiring circuit breaker or isolating switch
D Outdoor unit
E Indoor earth
F Wired remote controller
G Indoor unit
Fig. 6-1
Simultaneous twin system
1:1 System
12
TO REMOTE
CONTROLLER
TO OUTDOOR
UNIT
CN105 (RED)

Fig. 6-2
8
6. Electrical work
6.2. Remote controller
6.2.1. For wired remote controller
1) Two wired remote controllers setting
If two wired remote controllers are connected, set one to “Main” and the other to “Sub”. For setting procedures, refer to “Function selection of remote controller” in the operation manual for the indoor unit.
6.2.2. For IR wireless remote controller
1) Setting (Fig. 6-3)
Insert batteries. Press the SET button with something sharp at the end.
MODEL SELECT
blinks and Model No. is lighted.
Press the temp
buttons to set the Model No.
If you mistook the operation, press the ON/OFF
button and operate again
from procedure
.
Press the SET button with something sharp at the end.
MODEL SELECT
and Model No. are lighted for three seconds, then turned off.
Indoor Outdoor Model No.
PLA
heat pump models 001
cooling only models 033
2)Automatic fan speed setting (For IR wireless remote controller) (Fig. 6-4)
It is necessary to set for IR wireless remote controller only when automatic fan speed is not set at default setting. It is not necessary to set for wired remote controller with automatic fan speed at default setting.
Press the SET button with something sharp at the end.
Operate when display of remote controller is off.
MODEL SELECT
blinks and Model No. is lighted .
Press the AUTO STOP
button.
blinks and setting No. is lighted .
(Setting No.01: without automatic fan speed )
Press the temp.
buttons to set the setting No.02.
(Setting No.02:with automatic fan speed )
If you mistook the operation, press the ON/OFF
button and operate again
from procedure .
Press the SET button with something sharp at the end.
MODEL SELECT
and Model No. are lighted for 3 seconds, then turned off.
Fig. 6-3
Fig. 6-4
3) Assigning a IR wireless remote controller to each unit (Fig. 6-5)
Each unit can be operated only by the assigned remote controller. Make sure each pair of an indoor unit PC board and a IR wireless remote controller is assigned to the same pair No.
4) IR wireless remote controller pair number setting operation (Fig. 6-5)
Press the SET button with something sharp at the end.
Start this operation from the status of IR wireless remote controller display
turned off.
MODEL SELECT
blinks and Model No. is lighted.
Press the
min
button twice continuously.
Pair No. “0” blinks.
Press the temp buttons to set the pair number you want to set.
If you mistook the operation, press the ON/OFF
button and operate again
from procedure 2.
Press the SET button with something sharp at the end.
Set pair number is lighted for three seconds then turned off.
Pair No. of IR wireless remote controller
Indoor PC board 0 Factory setting 1 Cut J41 2 Cut J42
3-9 Cut J41, J42
Fig. 6-5
ON/OFF TEMP
FAN
VANE
TEST RUN
AUTO STOP
AUTO START
h
min
LOUVER
MODE
CHECK
RESETSET CLOCK
MODEL SELECT
*1. Max. 50 m, 165 ft *2. The 10m, 30 ft wire is attached in the wired remote controller accessory. Max. 500 m, 1500ft *3. The fi gures are NOT always against the ground. S3 terminal has DC 24 V against S2 terminal. However between S3 and S1, these terminals are not electrically insulated by the transformer or other device.
Notes: 1. Wiring size must comply with the applicable local and national code.
2.
Use copper supply wires.
3. Use wires rated 300V or more for the power supply cables and the indoor unit/outdoor unit connecting cables.
4. Install an earth longer than other cables.
Indoor unit model PLA-A12, 18, 24, 30 PLA-A36, 42 Minimum circuit ampacity 1A 2A Maximum rating of overcurrent protective device 15A 15A
Wiring
Wire No. × size
Indoor unit-Outdoor unit *1 3 × AWG16 (polar) 3 × AWG16 (polar)
Indoor unit earth 1 × Min. AWG16 1 × Min. AWG16
Wired remote contoroller-Indoor unit *2
2 × AWG22
(Non-polar, unshielded)
2 × AWG22
(Non-polar, unshielded)
Circuit
rating
Indoor unit-Outdoor unit S1-S2 *3 AC 208/230 V AC 208/230 V Indoor unit-Outdoor unit S2-S3 *3 DC24 V DC24 V Wired remote controller-Indoor unit *3 DC12 V DC12 V
9
6. Electrical work
6.3. Function settings
6.3.1. Function setting on the unit (Selecting the unit functions)
1) For wired remote controller (Fig. 6-6)
Changing the power voltage setting
• Be sure to change the power voltage setting depending on the voltage used. Go to the function setting mode.
Switch OFF the wired remote controller. Press the FILTER
and TEST RUN buttons simultaneously and hold
them for at least 2 seconds. FUNCTION will start to blink. Use the buttons to set the refrigerant address (3) to 00. Press button and [--] will start to blink in the unit number (4) display. Use the
buttons to set the unit number (4) to 00.
Press the MODE button
to designate the refrigerant address/unit number. [--]
will blink in the mode number (1) display momentarily. Press the buttons to set the mode number (1) to 04. Press the
button and the current set setting number (2) will blink.
Use the button to switch the setting number in response to the power supply
voltage to be used.
Power supply voltage 230 V : setting number = 1 208 V : setting number = 2
Press the MODE button
and mode and the setting number (1) and (2) will
change to being on constantly and the contents of the setting can be confi rmed. Press the FILTER and TEST RUN buttons simultaneously for at least two
seconds. The function selection screen will disappear momentarily and the air
conditioner OFF display will appear.
2) For IR wireless remote controller (Fig. 6-7)
Changing the power voltage setting
• Be sure to change the power voltage setting depending on the voltage used. Going to the function select mode
Press the
CHECK
button twice continuously. (Start this operation from the status of IR wireless remote controller display turned off.)
CHECK
is lighted and “00” blinks.
Press the
temp button once to set “50”. Direct the IR wireless remote control-
ler toward the receiver of the indoor unit and press the
h
button .
Setting the unit number
Press the
temp buttons and to set the unit number “00”. Direct the IR
wireless remote controller toward the receiver of the indoor unit and press the
min
button .
Selecting a mode
Enter 04 to change the power voltage setting using the
temp buttons and
. Direct the IR wireless remote controller toward the receiver of the indoor unit
and press the
h
button . Current setting number: 1 = 1 beep (one second) 2 = 2 beeps (one second each) 3 = 3 beeps (one second each)
Selecting the setting number
Use the
temp buttons and to change the power voltage setting to 01 (240
V). Direct the IR wireless remote controller toward the sensor of the indoor unit and press the
h
button .
To select multiple functions continuously
Repeat steps
and to change multiple function settings continuously.
Complete function selection Direct the IR wireless remote controller toward the sensor of the indoor unit and press the
button .
Note: Whenever changes are made to the function settings after installation or maintenance, be sure to record the changes with a mark in the “Setting” column of the Function table.
6.3.2. Function setting on the remote controller
Refer to the appropriate operation manual included with each remote controller.
Fig. 6-6
CHECK
CHECK
ON/OFF TEMP
FAN
VANE
TEST RUN
AUTO STOP
AUTO START
h
min
LOUVER
MODE
CHECK
RESETSET CLOCK
CHECK
Fig. 6-7
CHECKCHECK
Mode number
Setting number
Refrigerant address
Unit number
PAR-21MAA
ON/OFF
FILTER
CHECK
OPERATION
CLEAR
TEST
TEMP.
MENU
BACK DAY
MONITOR/SET
CLOCK
ON/OFF
10
6. Electrical work
7. Test run
Function table
Select unit number 00
Mode Settings
Mode No.
Setting no.
Initial setting
setting
Wired remote controller
(RF thermostat)
Power failure automatic recovery
Not available
01
(101)
1
Available *1 2
Indoor temperature detecting
Indoor unit operating average
02 (–)
1 Set by indoor unit’s remote controller 2 Wired remote controller’s internal sensor 3
LOSSNAY connectivity
Not Supported
03
(103)
1 Supported (indoor unit is not equipped with outdoor-air intake)
2 Supported (indoor unit is equipped with outdoor-air intake) 3
Power voltage
230 V
04
(104)
1 208 V 2
Select unit numbers 01 to 03 or all units (AL [wired remote controller]/07 [wireless remote controller])
Mode Settings
Mode No.
Setting no.
Initial setting
setting
Wired remote controller
(RF thermostat)
Filter sign
100Hr
07
(107)
1 2500Hr 2 No fi lter sign indicator 3
Fan speed
Silent
08
(108)
1 Standard 2 High ceiling 3
No. of air outlets
4 directions
09
(109)
1 3 directions 2 2 directions 3
Installed options (high-perform­ance fi lter)
Not supported
10
(110)
1 Supported 2
Up/down vane setting
Equipped with vanes (vanes angle setup
3
)
11
(111)
1 Equipped with vanes (vanes angle setup
1
)2
Equipped with vanes (vanes angle setup2)3
*1 When the power supply returns, the air conditioner will start 3 minutes later. *2 Power failure automatic recovery initial setting depends on the connecting outdoor unit.
7.1. Before test run
After completing installation and the wiring and piping of the indoor and out-
door units, check for refrigerant leakage, looseness in the power supply or control wiring, wrong polarity, and no disconnection of one phase in the supply.
Use a 500-volt megohmmeter to check that the resistance between the
power supply terminals and ground is at least 1.0 M .
Do not carry out this test on the control wiring (low voltage circuit)
terminals.
Warning:
Do not use the air conditioner if the insulation resistance is less than 1.0 M .
7.2. Test run
Refer to the installation manual that comes with each remote controller for de­tails.
7.3. Self-check
Refer to the installation manual that comes with each remote controller for de­tails.
RF thermostat is not established.
11
7. Test run
OPERATION INDICATOR lamp blinking pattern
Beep Beep Beep Beep Beep Beep Beep
Off
Approx. 2.5 sec.OnApprox. 3 sec.On0.5 sec.On0.5 sec.On0.5 sec.
On
0.5 sec.
Off
Approx. 2.5 sec.OnApprox. 3 sec.On0.5 sec.On0.5 sec.
· · · Repeated
Number of blinks/beeps in pattern indicates the check code in the following table (i.e., n=5 for “U2”)
Number of blinks/beeps in pattern indicates
the check code in the following table
n
th
1st2nd3
rd
1st2
nd
Self-check starts (Start signal received)
Beeper sounds
[Output pattern B]
OPERATION INDICATOR lamp blinking pattern
Beep
Beep Beep Beep Beep Beep Beep
Off
Approx. 2.5 sec.On0.5 sec.On0.5 sec.On0.5 sec.
On
0.5 sec.
Off
Approx. 2.5 sec.On0.5 sec.On0.5 sec.
· · · Repeated
Number of blinks/beeps in pattern indicates the check code in the following table (i.e., n=5 for “P5”)
Number of blinks/beeps in pattern indicates the check code in the following table
n
th
1st2nd3
rd
1st2
nd
Self-check starts (Start signal received)
Beeper sounds
• Refer to the following tables for details on the check codes. (IR wireless remote controller) [Output pattern A]
[Output pattern A] Errors detected by indoor unit
IR wireless remote controller
Wired remote
controller
RF thermostat
Symptom Remark
Beeper sounds/OPERATION
INDICATOR lamp blinks
(Number of times)
Check code
1 P1 Intake sensor error 2
P2 Pipe (TH2) sensor error
P9 Pipe (TH5) sensor error 3 E6, E7 Indoor/outdoor unit communication error 4 P4 Drain sensor error / Float switch connector open
5
P5 Drain pump error
PA Forced compressor error 6 P6 Freezing/Overheating protection operation 7 EE Communication error between indoor and outdoor units 8 P8 Pipe temperature error 9 E4 Remote controller signal receiving error
10 — 11
12 Fb Indoor unit control system error (memory error, etc.) No sound E0, E3 Remote controller transmission error No sound E1, E2 Remote controller control board error No sound — — No corresponding
[Output pattern B] Errors detected by unit other than indoor unit (outdoor unit, etc.)
IR wireless remote controller
Wired remote
controller
RF thermostat
Symptom Remark
Beeper sounds/OPERATION
INDICATOR lamp blinks
(Number of times)
Check code
1 E9 Indoor/outdoor unit communication error (Transmitting error) (Outdoor unit)
For details, check the LED display of the outdoor controller board.
2 UP Compressor overcurrent interruption 3 U3, U4 Open/short of outdoor unit thermistors 4 UF Compressor overcurrent interruption (When compressor locked) 5 U2 Abnormal high discharging temperature/49C worked/insuffi cient refrigerant 6 U1, Ud Abnormal high pressure (63H worked)/Overheating protection operation 7 U5 Abnormal temperature of heat sink 8 U8 Outdoor unit fan protection stop 9 U6 Compressor overcurrent interruption/Abnormal of power module
10 U7 Abnormality of super heat due to low discharge temperature
11 U9, UH
Abnormality such as overvoltage or voltage shortage and abnormal
synchronous signal to main circuit/Current sensor error 12 — 13 — 14 Others Other errors (Refer to the technical manual for the outdoor unit.)
*1 If the beeper does not sound again after the initial two beeps to confi rm the self-check start signal was received and the OPERATION INDICATOR lamp does not
come on, there are no error records.
*2 If the beeper sounds three times continuously “beep, beep, beep (0.4 + 0.4 + 0.4 sec.)” after the initial two beeps to confi rm the self-check start signal was received,
the specifi ed refrigerant address is incorrect.
• On IR wireless remote controller The continuous buzzer sounds from receiving section of indoor unit. Blink of operation lamp
• On wired remote controller Check code displayed in the LCD.
12
7. Test run
Water supply pump Water (about 1000cc, 1/4 gal) Drain plug Pour water through outlet
.
Be carefule not to spray water
into the drain pump mechanism.
7.4. Check of drainage (Fig. 7-5)
• Ensure that the water is being properly drained out and that no water is leaking from joints.
When electric work is completed.
.
Pour water during cooling operation and check.
When electric work is not completed.
.
Pour water during emergency operation and check.
* Drain pan and fan are activated simultaneously when single phase 220-240V is
turned on to S1 and S2 on terminal block after the connecter (SWE) on controller board in the electrical branch box is set to ON.
Be sure to turn it back to the former state after work.
• If the unit cannot be operated properly after the test run has been performed, refer to the following table to remove the cause. Symptom
Cause
Wired remote controller LED 1, 2 (PCB in outdoor unit
PLEASE WAIT
For about 2 minutes after power-on
After LED 1, 2 are lighted, LED 2 is turned off, then only LED 1 is lighted. (Correct operation)
•For about 2 minutes after power-on, operation of the remote controller is not possible due to system start-up. (Correct operation)
PLEASE WAIT
Error code
Subsequent to about 2 minutes after power­on
Only LED 1 is lighted.
LED 1, 2 blink.
•Connector for the outdoor unit’s protection device is not connected.
•Reverse or open phase wiring for the outdoor unit’s power terminal block (L1, L2, GR)
Display messages do not appear even when operation switch is turned ON (operation lamp does not light up).
Only LED 1 is lighted. LED 1 blinks twice, LED 2 blinks once.
•Incorrect wiring between indoor and outdoor units (incorrect polarity of S1, S2, S3)
•Remote controller wire short
On the IR wireless remote controller with condition above, following phenomena take place.
• No signals from the remote controller are accepted.
• Operation lamp is blinking.
• The buzzer makes a short ping sound.
Note: Operation is not possible for about 30 seconds after cancellation of function selection. (Correct operation)
For description of each LED (LED1, 2, 3) provided on the indoor controller, refer to the following table.
LED 1 (power for microcomputer) Indicates whether control power is supplied. Make sure that this LED is always lit. LED 2 (power for remote controller) Indicates whether power is supplied to the remote controller. This LED lights only in the case of
the indoor unit which is connected to the outdoor unit refrigerant address “0”.
LED 3 (communication between indoor and outdoor units) Indicates state of communication between the indoor and outdoor units. Make sure that this LED
is always blinking.
13
9.1. Checking the contents (Fig. 9-1)
• This kit contains this manual and the following parts. Accessory name Q’ty Remarks
Grille 1
950 × 950 (mm), 37-3/8 × 37-3/8 (inch) Screw with captive washer 4 M5 × 0.8 × 25 Gauge 1 (Divided into four parts) Fastener 3 Screw 4 4 × 8 Screw 1 4 × 12
9.2. Preparing to attach the grille (Fig. 9-2)
• With the gauge supplied with this kit, adjust and check the positioning of the unit relative to the ceiling. If the unit is not properly positioned relative to the ceil­ing, it may allow air leaks or cause condensation to collect.
• Make sure that the opening in the ceiling is within the following tolerances:
860×860 - 910×910 mm, 33-7/8×33-7/8 to 35-13/16×35-13/16 inch.
• Make sure that A is performed within 17-22 mm, 11/16-7/8 inch. Damage could result by failing to adhere to this range.
Main unit Ceiling Gauge (inserted into the unit) Ceiling opening dimensions
9.2.1. Removing the intake grille (Fig. 9-3)
• Slide the levers in the direction indicated by the arrows to open the intake grille.
• Unlatch the hook that secures the grille.
* Do not unlatch the hook for the intake grille.
• With the intake grille in the “open” position, remove the hinge of the intake grille from the grille as indicated by the arrows .
9.2.2. Removing the corner panel (Fig. 9-4)
• Remove the screw from the corner of the corner panel. Slide the corner panel as indicated by the arrow to remove the corner panel.
[Fig.9-3] [Fig.9-4]
Intake grille Grille Intake grille levers Grille hook Hole for the grille’s hook Corner panel Screw
Detail
9.3. Selection of the air outlets
For this grille the discharge direction is available in 11 patterns. Also, by setting the wired remote controller to the appropriate settings, you can adjust the air-fl ow and speed. Select the required settings from the Table 1 according to the location in which you want to install the unit.
1) Decide on the discharge direction pattern.
2) Be sure to set the wired remote controller to the appropriate settings according
to the number of air outlets and the height of the ceiling on which the unit will be installed.
Note: For 3 and 2-directional, please use the air outlet shutter plate (option).
9.4. Installing the grille
9.4.1. Preparations (Fig. 9-5)
• Install the two enclosed screws with washer in the main unit (at the corner drain pipe area and at the opposite corner) as shown in the diagram.
9. Installing the grille
8. System control
Refer to the outdoor unit installation manual.
Fig. 9-5
19/32 to 25/32
4-directional 3-directional
(inch)
One pattern: 4 patterns: Factory setting One air outlet fully closed
2-directional
6 patterns: Two air outlet fully closed
Blowout direction patterns
Blowout direction patterns
20
Fig. 9-1
Fig. 9-2
A=11/16
+3/16
0
Fig. 9-3
Fig. 9-4
Main unit
Screw with captive washer
(inch)
Table 1
14
9. Installing the grille
Fig. 9-6
Ceiling
Main unit
Grille
Make sure that there are no gaps
Adjust the nut of the main unit using a wrench, etc.
Fig. 9-7
Fig. 9-8
Clamp of the main unit
Electrical box
Indoor controler board
Catch for bell mouth
Lead wire of grille
Fig. 9-9
Button
Vane motor
Up/down vanes
Connector
Main unit Corner drain pipe area Screw with washer (for temporary use) Grille Screw with washer Socket Bell shaped hole
9.4.2. Temporary installation of the grille (Fig. 9-6)
• Temporarily secure the grille using the bell shaped holes by putting the socket of the grille marked on the corner drain pipe area of the main unit.
* Make sure that the lead wiring of the grille does not get pinched between the
grille and the main unit.
9.4.3. Securing the grille (Fig. 9-7)
• Secure the grille to the main unit by tightening the previously installed two screws (with captive washer) as well as the two remaining screws (with captive washer).
* Make sure that there are no gaps between the main unit and the grille or the
grille and the ceiling.
Fixing gaps between the grille and the ceiling
With the grille attached, adjust the height of the main unit to close the gap.
9.4.4. Wire connection (Fig. 9-8)
• Remove the 2 screws fixing the cover of electrical branch box of the unit and open the cover.
• Be sure to connect the connector(white, 20-pole) for vane motor of the grille to CNV connector of contoller board of the unit.
• As for PLP-42BALM, the connector of wireless sensor cable is also connected to connecor CN90 on indoor controller board.
The lead wire of grille is passed through the catch of bell mouth of the unit perfectly.
The remaining lead wire is tied with clamp of the unit and put the cover of the unit again with 2 screws.
Note: Do not put the remaining lead wire in electrical branch box of the unit.
9.5. Locking the up/down airfl ow direction (Fig. 9-9)
The vanes of the unit can be set and locked in up or down orientations depending upon the environment of use.
• Set according to the preference of the customer.
The operation of the fi xed up/down vanes and all automatic controls cannot be
performed using the wired remote controller. In addition, the actual position of the vanes may differ from the position indicated on the wired remote controller.
Turn off the main power switch.
Injuries or an electrical shock may occur while the fan of the unit is rotating.
Disconnect the connector for the vane motor of the vent that you want to lock.
(While pressing the button, remove the connector in the direction indicated by
the arrow as shown in the diagram.) After removing the connector, insulate it with tape.
It also can be set by wired remote controller. Refer to operation manual.
9.6. Check
• Make sure that there is no gap between the unit and the grille, or between the grille and the surface of the ceiling. If there is any gap between the unit and the grille, or between the grille and the surface of the ceiling, it may cause dew to collect.
• Make sure that the wires have been securely connected.
Loading...
+ 30 hidden pages