Auto Air Swing Vane
Disperses airflow up and
down and adjusts the angle
of airflow direction.
Grille
Filter
Remove dust and pollutants
from inhaled air
Horizontal Air Outlet
Sets airflow horizontal automatically
during cooling or dehumidifying.
Air Intake
Inhales air from room.
PART NAMES AND FUNCTIONS
● Indoor (Main) Unit
● Remote controller
On the controls are set, the same operation mode can be repeated by simply pressing the ON/OFF button.
● Operation buttons
button
This switches between continuous
operation and the timer operation.
button
Press this button to switch the cooler,
electronic dry (dehumidify), and Fan
modes.
TEMP. button
This sets the room temperature, The
temperature setting can be performed
in 1°C units
Setting range
Cooler 19°C to 30°C
button
This sets the current time. start
time and stop time.
button
This sets the ventilation fan
speed.
ON/OFF button
This switches between the operation
and stop modes each time it is
pressed. The lamp on this button
lights during operation.
button
This adjusts the vertical angle of the
ventilation.
FILTER button
This resets the filter cleaning indica-
tion display.
button
This switches the horizontal fan
motion ON and OFF.
(This button does not operate in this
model)
3
CHECK-TEST RUN button
Only press this button to per-
form an inspection check or test
operation, Do not use it for normal operation.
This figure shows the remoto controller for PL-AK.
Page 4
FILTER
CHECK MODE
TEST RUN
● Display
CENTRALLY
CONTROLLED display
This indicates when the unit is controlled by optional features such as
central control type remote controller.
CHECK display
This indicates when a malfunction
has occurred in the unit which should
be checked.
OPERATION MODE display
This indicates the operation mode.
display
The current time , start time and stop
time can be displayed in ten second
intervals by pressing the time setting
button. The start time or stop time is
always displayed during the timer
operation.
display
This displays the air
direction.
In this display example on the bottom left, a condition where all display lamps light is shown for explanation purposes although this differs
from actual operation.
display
The selected fan speed is displayed.
display
The temperature of the suction air is
displayed during operation. The display range is 8° to 39°C. The display
flashes 8°C when the actual temperature is less than 8° and flashes
39°C when the actual temperature is
greater than 39°C.
Operation lamp
This lamp lights during operation,
goes off when the unit stops and
flashes when a malfunction occurs.
CHECK MODE
TEST RUN
This display lights in the check mode
or when a test operation is performed.
display
display
This indicates when the continuous
operation and time operation modes
are set.
It also display the time for the timer
operation at the same time as when
it is set.
display
This displays the selected setting
temperature.
display
This lamp lights when electricity is
supplied to the unit.
This figure shows the remoto controller for PL-AK.
Caution
● Only the display lights when the unit is stopped and power supplied to the unit.
● When power is turned ON for the first time the (CENTRAL CTRL) display appears to go off momentarily but this is not a
malfunction.
● When the central control remote control unit, which is sold separately, is used the ON-OFF button, button and
TEMP. button do not operate.
● “NOT AVAILABLE” is displayed when the button are pressed.This indicates that this room unit is not equipped with
the fan direction adjustment function and the louver function.
FILTER
This lamp lights when the filter need
to be cleaned.
display
4
Page 5
●Wireless remote controller
● When cover is open.
display
Lights up while transmission to the indoor unit
is mode using switches.
display
OPERATION MODE display
Operation mode display indicates which oper-
ation mode is in effect.
• FUNCTION
Lights up when function are set.
display
• TEST RUN • CHECK display
CHECK&TEST RUN display indicates that the
unit is being checked or test-run.
display
Displays when batteries are dead.
display
The vertical direction of airflow is indicated.
display
FAN SPEED display indicates which fan
speed has been selected.
ADDRESS display
Displays the refrigerant address.
UNIT NO. display
Displays the number of unit..
FUNCTION NO. display
Displays the mode.
SELECTION NO. display
Displays the selection number..
ADDRESS
UNIT No.
FUNCTION No.
SELECTION No.
FUNCTION
TEST RUN
CHECK
ON/OFF
MODEFAN
RESET
VANE
AM
PM
AM
PM
TEMP.
˚C
START
STOP
HR.
MIN.
display
SET TEMP. display indicates desired temperature set.
CLOCK display
DIsplays the current time.
“ ”display
Flashes when the current time is displayed.
TIMER display
Displays when in timer operation or when setting timer.
➡
“ ” “ ” display
➡
Displays the order of timer operation.
“ ” “ ” display
Displays whether timer is on or off.
▼
“ ” “ ” display
Displays when the current time and the timer
time can be changed.
▼
TEMP. button
display
The unit is turned ON and OFF alternately
each time the button is pressed.
● When cover is open.
MODE SELECT button
Used to switch the operation mode between
cooling , drying , blowing , heating and auto
mode.
FAN SPEED SELECT button
Used to change the fan speed.
VANE CONTROL button
Used to change the airflow direction.
ON/OFF
MODEFAN
RESET
VANE
TEMP.
START
STOP
HR.
MIN.
SET TEMPERATURE button sets any desired
room temperature.
TIMER CONTROL buttons
STOP (OFF timer): when this switch is set,
the air conditioner will be automatically
stopped at the preset time.
START(ON timer): when this switch is set, the
air conditioner will be automatically started at
the preset time.
HR. and MIN.buttons
Buttons used to set the “hour and minute” of
the current time and timer settings.
button
RESET button
5
Page 6
3
PL-3AK
PL-3AK-E
UNIT : 840(33-1/6)
UNIT : 840(33-1/6)
UNIT : 258(10-1/8)
UNIT : 24(53)
PANEL : 950(37-3/8)
PANEL : 950(37-3/8)
PANEL : 30(1-3/16)
PANEL : 5(11)
27,000
7,900
3.33
PL-3AK
PL-3AK-E
Single, 50Hz, 220-240V
0.15
0.78
1.00
Grille : Munsell 0.70Y 8.59/0.97
Plate fin coil
Turbo fan (direct) x 1
0.07
15-20(530-705)
0(direct blow)
Remote controller & built-in
28-34
32(1-1/4)
PU-3VJC , PU-3VJC.UK / PU-3YJC , PU-3YJC.UK
Munsell 5Y 7/1
Capillary tube
2.2 / 2.4
w1
32
0.085
50(1765)
52
870(34-1/4)
295+24 (11-5/8 add 1)
850(33-1/4)
73(161)
W
D
H
W
D
H
INDOOR UNITOUTDOOR UNIT
Item
Service Ref.
Btu/h
W
kW
kW
A
A
kW
K/ min (CFM)
Pa
dB
mm(in.)
mm(in.)
mm(in.)
mm(in.)
kg(lbs)
kW
W
kW
K/ min (CFM)
dB
mm(in.)
mm(in.)
mm(in.)
kg(lbs)
Capacity
Total input
Service Ref.
Power supply(phase, cycle,voltage)
External finish
Heat exchanger
Fan
Operation control & Thermostat
Noise level(Low-High)
Unit drain pipe O.D.
Dimensions
Weight
Service Ref.
External finish
Refrigerant control
Compressor output
Protection devices
Cranckcase heater
Fan
Noise level
Dimensions
Weight
Input
Running current
Starting current
Fan(drive) x No.
Fan motor output
Airflow(Low-High)
External static pressure
Fan motor output
Airflow
SPECIFICATIONS
w1 V …Internal thermostat, HP switch, LP switch
Y…Anti-phase protector, Thermal relay, Thermal switch, HP switch, LP switch
Notes:Rating condition (ISO.T1<JIS B8616>)
Cooling: Indoor : D.B. 27°C, W.B. 19°C
Outdoor : D.B. 35°C, W.B. 24°C
Refrigerant piping length(one way):5m(16ft)
6
Page 7
W
D
H
W
D
H
Service Ref.
Btu/h
W
kW
kW
A
A
kW
K/ min (CFM)
Pa
dB
mm(in.)
mm(in.)
mm(in.)
mm(in.)
kg(lbs)
kW
W
kW
K/ min (CFM)
dB
mm(in.)
mm(in.)
mm(in.)
kg(lbs)
Item
Capacity
Total input
Service Ref.
Power supply(phase, cycle,voltage)
Input
Running current
Starting current
External finish
Heat exchanger
Fan
INDOOR UNITOUTDOOR UNIT
Operation control & Thermostat
Noise level(Low-High)
Unit drain pipe O.D.
Dimensions
Weight
Service Ref.
External finish
Refrigerant control
Compressor output
Protection devices
Cranckcase heater
Fan
Noise level
Dimensions
Weight
w1. V ··· Internal thermostat , HPswitch , LPswtch
The unit of pressure has been changed to Mpa based on the international SI system.
The conversion factor is : 1(Mpa)=10.2(kgf/
FF
)
22
Page 23
5. OUTLET AIR SPEED AND COVERAGE RANGE
90
80
70
60
50
40
30
20
10
631252505001000200040008000
APPROTIMATE
TERESHOLD OF
REARING FOR
CONTINUOUS
NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
PL-4AKS
PL-4AKS-E
Hi
NOTCH
Lo
41
SPL(dB)
33
LINE
90
80
70
60
50
40
30
20
10
631252505001000200040008000
APPROTIMATE
TERESHOLD OF
REARING FOR
CONTINUOUS
NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
PL-3AK
PL-3AK-E
Hi
Lo
34
SPL(dB)28LINE
NOTCH
PL-4AKS
PL-4AKS-E
28(990)
4.9
7.4
PL-5AKS
PL-5AKS-E
30(1,060)
5.2
7.9
PL-6AKS
PL-6AKS-E
30(1,060)
Standard
Service Ref.
Air flow
Air speed
Coverage range
K/
mim(CFM)
m/W
m
PL-3AK
PL-3AK-E
20(705)
4.0
5.7
wThe air coverage range is the value up to the position where the air speed is 0.25m/sec.
When air is blown out horizontally from the unit at the Hi notch position.
The coverage range should be used only as a general guideline since it varies according to the size of the room and the
furniture inside the room.
6. NOISE CRITERION CURVES
6.6
8.9
23
Page 24
UNIT
1.5m
MICROPHONE
CEILING
Ambient temperature 27:
Test conditions are based on JIS Z8731
90
80
70
60
50
40
30
20
10
631252505001000200040008000
APPROTIMATE
TERESHOLD OF
REARING FOR
CONTINUOUS
NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
PL-6AKS
PL-6AKS-E
Hi
NOTCH
Lo
45
SPL(dB)
37
LINE
90
80
70
60
50
40
30
20
10
631252505001000200040008000
APPROTIMATE
TERESHOLD OF
REARING FOR
CONTINUOUS
NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
PL-5AKS
PL-5AKS-E
Hi
NOTCH
Lo
43
SPL(dB)
35
LINE
24
Page 25
5
Air outlet hole
Vane motor
Auto vane
Drain hole
Grille
Drain pipe
VP-25connection
(O.D.{32)
Branch duct hole
(Cut out hole)
Ceiling surface
Suspension bolt pitch
Ceiling hole
Branch
duct hole
Suspension bolt pitch
Ceiling hole
Air outlet hole
Air intake hole
411
Air intake hole
Air intake grille
Receiver
Operation lamp
Emergency operation switch (cooling)
High efficiency filter
& Fresh air intake casement (option)
1. Since the indoor fan motor (MF) is connected with 230, 240V power. If 220V
power is used, change the dip switch (SW8) on the indoor controller board
as shown in fig : w2.
fig w2
Indoor fan motor (MF)for 220V.
ON
OFF
1
SW8
2 3 4
56
ON
OFF
2. Since the outdoor side electric wiring may change be sure to check the outdoor unit electric wiring for servicing.
3. Symbols used in wiring diagram above are,
: Connector, : Terminal block.
4. Emergency operation
If remote controller or microcomputer fails but there is no other trouble ,
emergency operation is possible by setting dip switch (SW3<I.B>) on the
indoor controller board.
1
SW8
2 3 4
[Check items]
(1)Make sure that no other trouble exist the outdoor unit. Trouble with the out-
door unit prevents emergency operation.
(If any trouble exists the outdoor unit error code “P8”will be displayed on the
remote controller and the trouble position will be shown on the outdoor controller LED. See electric wiring diagram of the outdoor unit for details.)
(2)Make sure that there is no trouble with the indoor fan.
56
Emergency operation will be continuous run with power ON/OFF (ON/OFF
with the remote controller is not possible).
[Emergency operation procedure]
(1)Set the dip switch (SW3<I.B>) on the indoor controller board to 1 on and 2
off for cooling.
(2)Turn on the outdoor unit side circuit breaker, then the indoor unit side circuit
breaker.
(3)During emergency operation indoor fan runs at High speed but auto-vane
does not work.
(4)Thermostat will not function. Cold air blows out for defrosting during heating
thus do not operate defrosting for a long time.
(5)Emergency cooling should be limited to 10 hours maximum.
(The indoor unit heat exchanger may freeze).
(6)After every emergency operation, set all dip switches (SW3<I.B>) to OFF.
(7)Movement of the vanes does not work in emergency operation, therefore you
have to slowly set them manually to the appropriate position.
NOTE: If the drain water lift up mechanism is identified to be defective with the
microcomputer doctor during cooling, do not use emergency operation
(it causes drain overflow)
w1 In addition, the centralized control and remote control can be operated.
w2 The modes which indicate the sources of trouble are listed below.
● EO-Signal transmitting/receiving error
● P1-Room temperature thermistor malfunction
● P2-Indoor coil thermistor malfunction
● P4-Drain sensor malfunction
● P5-Drain overflow
● P6-Coil frost/overheat protection
● P7-System error
● P8-Outdoor unit trouble
w3 The CHECK switch will show if an error has occurred in the past.
w4 Fan runs on low speed for 1 minute in order to remove overheat air.
w5 The 3-minute (6 minutes …heating mode) time-delay functions after compressor stops.
w6 In FAN mode, fan speed and vane operation depend on the remote controller setting. (Compressor is OFF.)
31
Page 32
COOL operation
Initial
COOLING
NO
NO
NO
NO
NO
YES
YES
YES
YES
YES
YES
NO
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
NO
NO
NO
NO
YES
NO
NO
NO
NO
NO
NO
NO
NO
NO
w 8
w 9
Vane initial
setting
Vane
55 deg downward angle
70 deg downward angle
Fan speed
LOW
Downward
discharge
1 hour
Vane setting notch
Vane horizontal
airflow
Compressor
thermostat
ON
Allowance
cancel
3-minute
time delay
6-minute
time delay
3-minute
compressor
operation
Coil frost
protection
Cooling area
10-minute
compressor
operation
Allowance cancel
Coil frost
prevention
16-minute
compressor
operation
Indoor pipe
temperature is
1°C or lower
Compressor ON
1
w 10
w 11
Coil frost
prevention
Compressor OFF
Indoor coil
temperature is
10°C or higher
Defrosting protection
detection temperature
-1°C or lower
YES
NO
6-minute
time delay
3-minute
time delay
Coil frost
prevention release
Allowance
period
6 minute
time delay
Allowance set
1 min continue
Coil frost protection
FAN speed
LOW
FAN speed
LOW 5 min
elapse
Outdoor unit
trouble
COOLING OPERATION
w8 When operation stops or changes to cooling or dry mode, the auto vane turns to a horizontal angle. If operation changes
during auto vane SWING, the auto vane will continue to swing.
w9 When operating TEST RUN, the thermostat will be continuously ON.
w10After 3 minute compressor operation, if the indoor coil thermistor reads -15°C or below for 3 minutes, the compressor will
stop for 6 minutes.
w11Heating area : Indoor coil temperature is more than 5 degrees above the room temperature.
Cooling area : Indoor coil temperature is more than 5 degrees below the room temperature.
FAN area : Indoor coil temperature is within 5 degrees either way of the room temperature.
32
Page 33
DRY OPERATION
DRY
operation
Vane
setting notch
NO
YES
NO
Initial dry
operation
YES
Vane initial setting
w12
Room temperature is
18°C or lower
NO
During
compressor ON
YES
3-minute
compressor
operation
YES
Compressor &
thermostat ON
YES
w8
w9
NO
NO
YES
3-minute
time delay
NO
Compressor &
thermostat
ON
NO
YES
w9
Compressor ON
time completes
YES
10-minute compressor
OFF timer start
Compressor OFF
Fan STOP
1
w8—9 Refer to page 38~39.
w12When room temperature is 18°C or below, the compressor cannot operate.
When room temperature rises over 18°C, the compressor starts after a 3-minute time delay.
w13Compressor ON time is decided by room temperature. Refer to page 36~37.
w14In dry operation, compressor ON makes the fan speed LOW. Also, when the compressor OFF and the pipe temperature
is 26°C or less, the fan stops, or when the compressor OFF and the pipe temperature is below 6°C, the fan speed
changes to LOW mode.
It is not possible to set the fan speed with the remote controller
NO
w14
10-minute
compressor
OFF
YES
Compressor ON
time set
Compressor ON
Fan speed LOW
NO
w13
w14
33
Page 34
9
FILTER
CHECK MODE
TEST RUN
ON/OFF
CHECK
ADDRESS
UNIT No.
FUNCTION No.
SELECTION No.
AM
PM
AM
PM
TEST RUN
FUNCTION
˚C
TEMP.
MICROPROCESSOR CONTROL
1. OUTLINE OF MICROPROCESSOR CONTROL
INPUT to remote controller
● OFF-ON switching.
● COOL/DRY-FAN selector switching.
● Thermostat setting.
● TIMER mode selector-switching and Timer
setting.
● HIGH-LOW fan speed switching.
● AUTO Vane selector (AIR DISCHARGE)
switching.
● TEST RUN switching.
● CHECK mode switching.
(Self diagnostic trouble shooting)
Indoor
unit
Remote controller board
● Processes and transmits
orders.
Non-polar, two-wire
cable maximum
length 500 meters
(WIRED only)
Signal
12VDC
OUTPUT to remote controller
Remote controller
● LCD indicator
This figure shows the remote con-
troller for PL-AK.
WIRED REMOTE
CONTROLLER
INPUT from indoor unit
● Room temperature thermistor (RT1)
● Indoor coil thermistor (RT2)
● Drain sensor
OUTPUT to indoor unit
● Auto vane’s angle setting.
● Drain pump : ON-OFF.
● Emergency stop.
INPUT from outdoor unit
● Compressor protection device
working.
OUTPUT to outdoor unit
● Compressor motor and outdoor fan motor ON-OFF.
Indoor controller board
● Receives orders from remote controller and
temperature data from indoor unit.
● Processes orders and data.
● Controls indoor and outdoor operation.
● Self diagnostic function.
w System control operation.
w Emergency operation.
w Set by dip switch on indoor controller board.
● Transmits the power to remote controller.
Non-polar two (2)-core cable
12VDC
OUTDOOR UNIT
● Receives order from indoor
controller.
● Emergency stop.
WIRELESS
REMOTE
CONTROLLER
Outdoor unit
34
Page 35
2. INDOOR UNIT CONTROL
Minimum 3 minutes w1
ON
Thermostat
Indoor fan
Auto vane
Drain pump
Compressor
ON
ON
LOW or HIGHLOW or HIGH
ON
OFF
OFF
ON
OFF
3 minutes
OFF
OFF
Operation starts by
POWER button
ON.
Operation stops by
POWER button
OFF.
Room temperature
becomes equal to
set temperature.
Room temperature
rises above set
temperature.
FILTER
CHECK MODE
TEST RUN
ON/OFF
CHECK
ADDRESS
UNIT No.
FUNCTION No.
SELECTION No.
AM
PM
AM
PM
TEST RUN
FUNCTION
˚C
TEMP.
2-1 COOL operation
WIRED REMOTE
CONTROLLER
[This figure shows the remote
controller for PL-AK.]
<COOL operation time chart>
WIRELESS REMOTE
<How to operate>
1 Press POWER ON/OFF button.
2 Press the button to display
3 Press the TEMP. button to set the desired temperature.
NOTE: Set temperature changes 1°C when the or
button is pressed one time.
Cooling 19 to 30°C
CONTROLLER
w1 Even if the room temperature rise above the set temperature during this period, the compressor will not start until this period has ended.
(1) Compressor control
1 3-minute time delay
To prevent overload, the compressor will not start within 3 minutes after stop.
2 The compressor runs when room temperature is higher than set temperature.
The compressor stops when room temperature is equal to or lower than the set temperature.
The compressor maintains the previous state when the discharge temperature minus the set temperature is 0°C or
more, or lower than 1°C.
3 The compressor stops in check mode or during protective functions.
4 Coil frost prevention
To prevent indoor coil frost, the compressor will stop when the indoor coil thermistor (RT2) reads 1°C or below after the
compressor has been continuously operated for at least 16 minutes or more. When the indoor coil temperature rises to
10°C or above, the compressor will start in a 3-minute(w2) time delay.
w2 When the indoor coil temperature is -1°C or less, the compressor starts in 6 minutes.
NOTE : By turning OFF the dip switch SW1-3 on indoor controller board, the start temperature of coil frost prevention changes
from 1°C to -3°C.
35
Page 36
5 Coil frost protection
305570
30
45
55
70
AUTO RETURN
When indoor coil temperature becomes -15°C or below,coil frost protection will proceed as follows.
<Start condition>
After the compressor has been continuously operated for 3 minutes or more,and the indoor coil temperature has been
-15°C or below for 3 minutes,the coil frost protection will start.
<Coil frost protection>
Compressor stops for 6 minutes,and then restarts.
lf the start condition is satisfied again during the first 10 minutes of compressor operation,both the indoor and outdoor
units stop, displaying a check code of “P6” on the remote controller.
<Termination conditions>
Coil frost protection is released when the start condition is not satisfied again during the allowance, or when the COOL
mode stops or changes to another mode.
(2) Indoor fan control
Indoor fan speed LOW/HIGH depends on the remote controller setting.
However, if an outdoor unit abnormality is detected, the indoor fan speed will be LOW, regardless of the remote controller
setting.
(i ) Fan speed LOW/HIGH depends on the remote controller setting regardless of the thermostat ON/OFF.
(ii) Fan speed will remain on LOW if an abnormality in outdoor unit is detected. (5 minutes)
NOTE : Fan stops immediately if the unit stops or the check mode is started.
(3) Auto vane control
Auto vane position is set to 30 degrees airflow at the start-up of COOL operation.
(a) Vane position set mode & swing mode.
( i ) Every time button is pressed, setting will be changed .
(ii) Airflow direction can be changed with button.
1 Fan speed : LOW
30°
55°
70°
SWING
2 Fan speed : HIGH
30°
45°
55°
70°
SWING
<VANE POSITION>
1 Fan speed : LOW
2 Fan speed : HIGH
When 55 degrees or 70 degrees airflow is selected with the LOW fan speed in COOL operation, “1Hr” will appear right side
of the air direction display. One hour later, the airflow direction returns to 30 degrees automatically and “1Hr” will disappear. If the airflow direction is set to 30 degrees during “1Hr” indication, the time counting for AUTO RETURN is cancelled.
36
Page 37
(4) Detecting abnormalities in the outdoor unit
After the compressor has been continuously operated for 3 minutes, if the difference between the indoor coil temperature
and room temperature is out of RANGE C for 1 minute, the indoor fan speed will turn to LOW. Five minutes later, if the difference is still out of RANGE C,the outdoor unit is functioning abnormally. Thus, the compressor stops and check code
“P8” appears on remote controller.
RANGE A: Indoor coil temperature is more than 5 degrees above room temperature.
RANGE B : Indoor coil temperature is within 5 degrees either way of room temperature.
RANGE C : Indoor coil temperature is more than 5 degrees below room temperature.
Indoor coil temperature
minus room temperature
(degree)
+5
0
-5
(5) Drain pump control
The drain pump works in COOL or DRY operation.
The drain pump does not work in check mode.
<Drain sensor>
When both the drain pump and unit are operating, the drain sensor detects the temperature. This temperature tells
whether the drain water level is above or under the drain sensor. If the drain water level rises above the drain sensor due
to a drain pump malfunction, the unit will stop operating in order to prevent drain from overflowing. The check code “P5” on
the remote controller will display this occurrence.
(6) Dew prevention heater
To prevent dew from accumulating on the grille, the dew prevention heater is continuously ON during COOL operation.
It is independent of the thermostat ON/OFF.
RANGE A
RANGE B
RANGE C
37
Page 38
Minimum 3 minutes w1
ON
Thermostat
Indoor fan
Auto vane
Drain pump
Compressor
ON
ON
DRY MODE
DRY MODE
ON
OFF
OFF
ON
OFF
3 minutes
OFF
OFF
Operation starts by
POWER button
ON.
Operation stops by
POWER button
OFF.
Room temperature
becomes equal to
set temperature.
Room temperature
rises above set
temperature.
2-2 DRY operation
FILTER
CHECK MODE
TEST RUN
ON/OFF
CHECK
ADDRESS
UNIT No.
FUNCTION No.
SELECTION No.
AM
PM
AM
PM
TEST RUN
FUNCTION
˚C
TEMP.
WIRED REMOTE
CONTROLLER
[This figure shows the remote
controller for PL-AK.]
<DRY operation time chart>
<How to operate>
1 Press POWER ON/OFF button.
2 Press thebutton to display “”
3 Press the TEMP button to set the desired temperature.
NOTE: The set temperature changes 1°C when the or
button is pressed one time.
Dry 19 to 30°C
WIRELESS REMOTE
CONTROLLER
w1 Even if the room temperature rises above the set temperature during this period, the compressor will not start until this
(1) Compressor control
13-minute time delay
To prevent overload, the compressor will not start within 3 minutes after stop.
2The compressor stops in check mode or during protective functions.
period has ended.
38
Page 39
4The compressor will not start when the room temperature is below 18°C.
Compressor OFF
6°C or more
Below 6°C
STOP
Indoor coil
temperature
Fan
LOW
AllLOW
Compressor ON
The compressor starts intermittent operation when the power is turned ON with room temperature above 18°C. The compressor ON/OFF time depends on the thermostat ON/OFF and the following room temperatures.After 3-minute compressor operation,
● If the room temperature thermistor reads above 28°C with thermostat ON, the compressor will operate for 6 more minutes and then stop for 3 minutes.
● If the room temperature thermistor reads 26°C~28°C with thermostat ON, the compressor will operate for 4 more minutes and then stop for 3 minutes.
● If the room temperature thermistor reads 24°C~26°C with thermostat ON, the compressor will operate for 2 more minutes and then stop for 3 minutes.
● If the room temperature thermistor reads below 24°C with thermostat ON, the compressor will stop for 3 minutes.
● If the thermostat is OFF regardless of room temperature, the compressor will stop for 10 minutes.
5Coil frost protection
Coil frost protection in DRY operation is the same as in COOL operation.
6Coil frost prevention
Coil frost prevention does not operate in DRY operation.
(2) Indoor fan control
The indoor fan runs on LOW speed during compressor operation. The fan speed cannot be changed with the remote controller. Also, the fan runs on LOW speed when the pipe temperature is 6°C or more, or the compressor is OFF and the pipe
temperature is below 6°C.
(a)During compressor OFF
● When the indoor coil temperature is 6°C or above, the indoor fan will stop.
● When the indoor coil temperature is below 6°C, the indoor fan will run on LOW speed.
(b)During compressor ON
● The indoor fan runs on LOW speed.
<Dry mode>
The fan notch is controlled by the indoor coil temperature every 30 seconds.
Fan control in DRY operation.
(3) Auto vane & drain pump controls
Same as in COOL operation
(4) Detecting abnormalities in the outdoor unit
An abnormality in the outdoor unit can not be detected in DRY operation.
39
Page 40
30°
1
45° downward
2
55° downward
3
70° downward
4
swing
5
2-3 Auto vane control
FILTER
CHECK MODE
TEST RUN
ON/OFF
CHECK
ADDRESS
UNIT No.
FUNCTION No.
SELECTION No.
AM
PM
AM
PM
TEST RUN
FUNCTION
˚C
TEMP.
<How to operate>
To change the air flow direction, press button.
WIRED REMOTE
CONTROLLER
[This figure shows the remote
controller for PL-AK.]
WIRELESS REMOTE
CONTROLLER
1
30°
2
45°
3
55°
4
70°
Available in COOL operation with fan speed on HIGH .
Unavailable in DRY operation.
If fan speed changes from HIGH to LOW during 45°
downward airflow in COOL mode, the direction automatically changes to 30°.
Changes by pressing the button.
(1) COOL/DRY operation
At the start-up of COOL or DRY operation, the airflow direction in automatically set to 30°. After, it can be changed to
another direction with button on the remote controller.
<Auto return>
When 55° or 70° airflow is set with fan speed in LOW, “1Hr” appears right side of the air direction. One hour later the
direction changes to 30 degrees, automatically and “1Hr” disappears.
40
Page 41
2-4 TIMER operation
OFF
ON/OFF
CHECK
ADDRESS
UNIT No.
FUNCTION No.
SELECTION No.
AM
PM
RESET
AM
PM
TEST RUN
FUNCTION
˚C
MODEFAN
VANE
TEMP.
START
STOP
HR.
MIN.
(1) WIRED REMOTE CONTROLLER
FILTER
CHECK MODE
TEST RUN
[This figure shows the remote controller for PL-AK.]
<Timer setting example>
This setting will stop the air conditioner in 8 hours.
With the lapse of time, time display changes in 1 hour units, showing remaining time.
<Timer function>
AUTO STOP ·········The air conditioner stops after the set time lapses.
AUTO START ········The air conditioner starts after the set time lapses.
AUTO OFF ············Timer is not active.
<How to operate>
1. Press POWER ON/OFF button.
2. Press “” button to select AUTO STOP or AUTO START.
3. Press “” button to set desired time.
Time setting is in 1 hour units for up to 24 hours.
Each time HOURS button is pressed, set time increases by 1 hour.
When HOURS button is pressed and held, the set time increases
by 1 hour every 0.5 seconds.
4. To cancel the timer operation, press POWER ON/OFF button.
(2) WIRELESS REMOTE CONTROLLER
B
A
1
24
3
<How to operate>
1 Press the ON/OFF button to turn it ON.
2 Press the STOP or START button (TIMER SET).
·Time can be set while the following symbol is displayed.
OFF timer : A, Bis displayed.
ON timer : A, Bis displayed.
3 Use the HR. and MIN. buttons to set the desired time.
4 Cancelling the timer.
To cancel the OFF timer, press the STOP button.
To cancel the ON timer, press the START button.
▼
▼
·It is possible to combine both OFF and ON timers.
·Pressing the ON/OFF button of the remote controller during
timer mode to stop the unit will cancel the timers.
41
Page 42
TEST RUN
2-5 Test run
ON/OFF
CHECK
ADDRESS
UNIT No.
FUNCTION No.
SELECTION No.
AM
PM
RESET
AM
PM
TEST RUN
FUNCTION
˚C
MODEFAN
VANE
TEMP.
START
STOP
HR.
MIN.
(1) WIRED REMOTE CONTROLLER
<Before test run>
● After installing, wiring, and piping the indoor and outdoor units, check for refrigerant leakage, looseness in power supply or
control wiring, and mistaken polarity.
● Use a 500-volt mega to check the resistance between the power supply terminal block and ground to make sure that it is at
least 1.0MΩ.
Attention:
Do not use the air conditioner if resistance is less than 1.0MΩ.
Remote controller
This figure shows the remote controller
for PL-AK.
TEST RUN button
TEST RUN
Indoor coil temperature code
Display
Display
Turn on main switch.12 hours before proceeding to step 2 to allow
1
for crankcase heater operation.
Push the TEST RUN button twice and indication of TEST RUN will
2
be shown on the liquid crystal display.
Press the button, COOL/DRY to confirm that cool (or warm)
3
air is blown out.
Push button LOW/HIGH to check that the fan speed changes
4
properly.
Check the operation of outdoor unit fans.This unit controls the rota-
tion speed and performance capacity of fans. ln some cases,it may
rotate at low speed as the condition of outside air requires and the
speed will be kept unless the performance has become deficient.
5
Therefore,when the condition of outside air demands,there may be
such cases as the fan stops or rotates reversely.
Please note that these symptoms are not malfunction.
After the check is finished leave the test run mode, push the power
ON/OFF button.
6
It can also be stopped by pushing the timer MODE button.
*The above figure shows the state of TEST
RUN at cooling operation.
●When a TEST RUN is started,the timer shall be set to 2 hours. The unit will automatically turn off after 2 hours.
(2) WIRELESS REMOTE CONTROLLER
82
<Before test run>
Measure an impedance between the power supply terminal block
on the outdoor unit and the ground with a 500 V Megger and
check that it is equal or greater than 1.0M
""
.
1 Turn on the main power to the unit..
2 Set the Nrm/Set selector switch (on the back of the controller)to <Set>.
AThe FUNCTION , TEST RUN and CHECK begin to blink.
3 Press the MIN. button.
B TEST RUN and current operation mode are displayed.
4 Press the MODE button to activate COOLmode, then check
whether cool air in blown out from the unit.
5 Press the
FANbutton and check whether strong air is blown
out from the unit.
5 Press the
VANEbutton and check whether the auto vane
operates properly.
7 Press the ON/OFF button to stop the test run.
8
After trial run is complete, set the Nrm/Set selector switch to <Nrm.>
Note :
·Point the remote controller toward the inside unit’s receiver
while steps 33though 77.
·It is not possible to run the unit in FAN or DRY mode.
BA
7
5
4
6
3
42
Page 43
(1) Indoor coil temperature code
1 ON
1
2
1.2 OFF
SW3
1
2
During the test run, the indoor coil temperature code from 1 to 15 is displayed on the remote controller instead of room
temperature. The code should fall with the lapse of time in normal COOL operation, and should rise in normal HEAT
operation.
Code
Indoor coil temperature
Code
Indoor coil temperature
1
-39~2(1)°C
9
~45°C
2
3(2)~10°C
10
~50°C
3
~15°C
11
~55°C
4
~20°C
12
~60°C
5
~25°C
13
~70°C
6
~30°C
14
~88.5°C
7
~35°C
15
Thermistor abnormality
(2) Trouble during test run
● If the unit malfunctions during the test run, refer to section 10 in this manual entitled “TROUBLESHOOTING.”
● When the optional program timer is connected to the conditioner, refer to its operating instructions.
2-6 Emergency operation
When the remote controller or microprocessor malfunctions but all other parts are normal, emergency operation is started
by setting the dip switch SW3 on the indoor controller board.
<Before emergency operation>
1. Make sure the compressor and the indoor fan are operating normally.
2. Locate the defect with the self-diagnostic function. When the self-diagnostic function indicates “protective function is
working”, release the protective function before starting the emergency operation.
CAUTION: When the self-diagnostic function indicates a check code of “P5” (drain pump malfunction), DO NOT start
the emergency operation because the drain may overflow.
<How to operate>
1. For emergency cooling, set the dip switch SW3-1 to ON and SW3-2 to OFF.
For emergency heating, set the dip switch SW3-1, 2 to ON.
Emergency
cooling
Normal
operation
8
~40°C
Microprocessor board
2. Turn ON the outdoor unit breaker and then ON the indoor unit breaker.
Emergency operation will now start.
3. During emergency operation, the indoor fan operates on high speed, the auto vanes do not operate.
4. To stop emergency operation, turn OFF the indoor unit breaker.
5. Movements of the vanes do not work in emergency operation, therefore you have to slowly set them manually to the
appropriate position.
NOTE: The remote controller POWER ON/OFF button can not start/stop emergency operations.
CAUTION: Do not use emergency cooling for more than 10 hours, as the indoor coil may freeze.
43
Page 44
2-7 Interlock with ventilation system (LOSSNAY)
Relay box
Relay box (PZ-12RB-E)
LOSSNAY
LOSSNAY
LOSSNAY control switch (PZ-05SLB
2-E)LOSSNAY control switch
(PZ-05SLB
2-E)
Mr. SLIM
Mr. SLIM
Remote
controller
Remote
controller
Remote display
adapter
(PAC-SA88HA-E)
Power
supply
Power supply
Mr. SLIM/LOSSNAY interlock operation is available by using the optional parts listed below.
(1) System organization
(2) LOSSNAY models connectable to Mr. SLIM are: LGH-15RS-E, LGH-50RS-E
LGH-25RS-E, LGH-80RS-E
LGH-35RS-E, LGH-100RS-E
(3) Required parts are:
● Relay box (PZ-12RB-E)…Contact capacity 10A
● Remote display adapter (PAC-SA88HA-E)…An optional part for Mr. SLIM
● LOSSNAY control switch (PZ-05SLB2-E)…For LOSSNAY individual operation
(4) Operation
1LOSSNAY turns ON/OFF according to Mr. SLIM ON/OFF
2While Mr. SLIM is OFF, LOSSNAY individual operation is available by using the LOSSNAY control switch.
When Mr. SLIM turns OFF with the LOSSNAY control switch at ON, LOSSNAY will continue to operate.
(5) Wiring.
Mr. SLIM
Indoor controller
N
L
DAMPER
2-E)
LOW
board
Connector
CN51
ORN
RED
BRN
Remote
controller
Power
supply
50Hz
220 240V
10m
Connecting wire
0.13mm or over
Connecting wire
solid wire,
1.6 or 2.0
(field supplied)
Circuit breaker
(field supplied)
L
N
PL
HIGH
N
LOSSNAY control switch
(PZ-05SLB
Insulation
is needed
2
Power supply
for Mr. SLIM
220 240V AC
GRN
YLW
Relay box
(PZ-12RB-E)
YLW
Junction box
(field supplied)
A
B
L
N
HIGH
N
Terminal
block
LOW
HIGH
N
DAMPER
DAMPER
ORN
RED
WHT
RED
WHT
LOSSNAY
ORN
RED
WHT
RED
ORN
WHT
8
7
4
6
2
5
3
1
44
2When the LOSSNAY control switch is not used:1When the LOSSNAY control switch is used
Relay box
(PZ-12RB-E)
Terminal block
ABLN HIGH N
Mr.SLIM
CN51
12V DC
L
Power supply
220 240V AC
NOTE: For further information, refer to the
LOSSNAY technical & service manual.
Circuit
breaker
N
LOSSNAY
Terminal block
ORN
LOW
RED
HIGH
WHT
N
RED
DAMPER
ORN
DAMPER
WHT
Page 45
2-8 Dip switch functions
Each figure shows the initial factory setting.
1. On remote controller board
(1) SW17(Address selector)
1 2 3 4 5 6 7 8
ON
OFF
SW17-1~6) For address setting
SW17-7) When two remote controllers are used,this switch sets the controller function.
OFF:The remote controller is set as a main controller.
ON :The remote controller is set as a sub controller.
SW17-8) Switch for system back-up.
OFF:Without back-up
ON :With back-up
(2) SW18(Function selector)
1 2 3 4
ON
OFF
SW18-1) Switch for timer
OFF:Single day ON:timer every day
SW18-2) Switch for filter sign
OFF:filter sign absent
ON :filter sign present
SW18-3) Switch for filter sign time setting.
OFF:100Hr ON:2500Hr
SW18-4) Not yet used.
SW18-5) OFF:Switch for models with heat pump.
ON:Switch for models with cooling only.
wSince SW18-5 is OFF(settinng for Heat pump) in the remote controller for PL-AK-E , be sure to switch setting
SW18-6~8) Not yet used.
2. On indoor controller board
(1) SW1 (Mode selector)
1 2 3 4 5 6 7 8 9
ON
OFF
SW1-1) Switch that changes between FAN mode and AUTO mode
OFF:AUTO mode for models with heat pump
ON :Fan mode for models with heat pump
SW1-2) Switch for drain pump
OFF:The drain pump works in COOL and DRY operation.
ON :The drain pump works in both COOL and DRY and HEAT operation.
SW1-3) Switch to change the temperature to start coil frost prevention
OFF:1°C
ON :-3°C
SW1-4) Switch for set temperature adjustment in HEAT mode
During HEAT operation,warm air collects near the ceiling.When the indoor unit is installed near the ceiling,the
temperature read by room temperature thermistor differs from the actual living-space temperature by about 4
degrees. Therefore,the room temperature read by room temperature thermistor must be lowered by 4 degrees.
OFF:4-degree adjustment
ON :NO adjustment
SW1-5) Switch for fan speed during thermostat OFF in HEAT operation
OFF:EXTRA LOW
ON :LOW
SW1-6) Switch for fan speed during thermostat OFF in HEAT operation
OFF:EXTRA LOW or LOW(set with SW1-5)
ON :LOW or HIGH(set with remote controller)
SW1-7) Switch for detecting abnormalities in the outdoor unit abnormality detection
OFF:When an abnormality occurs,it is detected.
ON :Even if an abnormality occurs,it can not be detected.
SW1-8) Switch for auto restart function
OFF:This function does not work
ON :This function works.
SW1-9, 10) Not yet used.
5678
ON(setting for cooling only.).
10
45
Page 46
(2) SW2 (Address selector)
1 2 3 4 5 6
ON
OFF
Used in setting the unit-address for group control.
For further information, refer to page 62.
(3) SW3 (Emergency operation switch)
Normal operation
1 2
ON
OFF
For emergency cooling
1 2
ON
OFF
(4) SW5 (Model selector)
1 2 3 4
ON
OFF
SW5-1) Not yet used
SW5-2) OFF:For models with heat pump
ON :For models with cooling only
SW5-3) OFF:Auto vane angle 30˚→45˚→55˚→70˚
ON :Auto vane angle 25˚→40˚→55˚→70˚
SW5-4) Fresh air intake OFF:Fresh air in not taken in
ON :Fresh air is taken in
(5) SW6 (Address selector)
1 2 3 4
ON
OFF
Single controlTwin control
SW6-1OFFON(Twin NO.1)
SW6-2OFFON(Twin NO.2)
SW6-3OFFOFF
SW6-4OFFOFF
(6) SW7 (Model selector)
Switch to set the output of phase-controlled indoor fan motor.
Address setting is available at any time.
The initial factory setting by is based on each capacity.
Service Ref.
SW7
PL-3AK
PL-3AK-E
ON
OFF
1 2 3
PL-4AKS
PL-4AKS-E
ON
OFF
1 2 3
PL-5AKS
PL-5AKS-E
ON
OFF
1 2 3
PL-6AKS
PL-6AKS-E
ON
OFF
1 2 3
46
Page 47
(7) SW8
1 2 3 4
56
ON
OFF
SW8-1~2) High ceiling type switch
SW8-3~4) Discharge outlet number selector
SW8-5) Option selector
The display “CENTRALLY
CONTROLLED” on remote
controller dose not disappear.
When remote controller
POWER button is turned
ON, the check code
“EO”appears.
CauseCheck points
1) Wrong address setting of remote controller/indoor controller board.
2) Timer adapter is connected to the
remote controller.
3) Signal transmission error between
indoor unit and remote controller.
1) Signal transmission error between
indoor unit and remote controller
1) Check the address setting of remote controller
and indoor controller.
2) Make sure the timer adapter is used correctly.
3) 1 Turn another remote controller’s DIP SW17-
7 ON to make it sub controller.
2 Connect the sub controller to the unit, and
turn circuit breaker ON.
● If the display “centrally controlled” disappears, replace the original remote controller.
● If the display remains the same, replace the
indoor controller board.
1) 1 Connect a sub remote controller.
2 Turn circuit breaker ON.
If the display “centrally controlled” remains,
replace the indoor controller board.
3 If the display disappears, turn the remote
controller POWER button ON and check as
follows.
Remote controller
1
Operating Display
2
Operating Display
3
No Display
4
No Display
Sub remote controller
EO Display
Operating Display
EO Display
Operating Display
Malfunction of
indoor Unit
Malfunction of
Remote controller
Malfunction of
indoor Unit and
Remote Controller
Malfunction of
Remote controller
Malfunction
When remote controller
POWER button is turned
ON, operating display
appears, but disappears
soon.
Despite turning POWER
button ON, the remote
controller display does not
appear.
1) Short circuit of indoor/outdoor connecting wire
2) Short circuit of transmission wire.
3) Wrong operation of remote controller
due to noise wave emitted by other
appliances.
1) Damaged remote controller.
2) Short circuit of transmission wire.
3) Bad contact of indoor CN40.
4) CN40 is attached to a sub unit.
5) Damaged power board.
6) Bad contact of CN2D.
7) Blown fuse.
8) Circuit breaker OFF.
1), 2) Check the wire
3) Turn the circuit breaker OFF, and then turn
ON.
If the remote controller remains abnormal,
despite the above measures, replace the indoor
controller board.
1) Measure the voltage between terminals of
remote controller. If no voltage, remove the
terminals and measure the voltage between
wires. If the voltage is between 6VDC and
12V, replace the remote controller.
2) ~ 8) Check each point.
If it is not defective, replace the indoor
controller board.
48
Page 49
2. SELF DIAGNOSTIC FUNCTION WITH REMOTE CONTROLLER
(WIRED REMOTE CONTROLLER)
2-1 When malfunction occurs during operation
When a malfunction occurs, the indoor and outdoor units stop and the malfunction is displayed on the LCD of the remote
controller.
(1) ON the set temperature display part, “CHECK” appears, and the unit
address and the check code are displayed alternately at one-second
intervals. (Check mode)
Example
CHECK mode
Check
code
(2) When one remote controller controls several units in the group con-
trol, the LCD shows the unit address and check code of the first malfunctioning unit.
(3) To cancel the check mode, press the ON/OFF button. In remote
ON/OFF control, press the remote ON/OFF switch. In centralized
control, turn OFF the ON/OFF button of centralized controller.
NOTE: The latest check code is memorized, even if the check mode is cancelled by the way mentioned above. It takes
60 seconds maximum to display the memorized check code.
Unit
address
Check button
[This figure shows the remote controller for PL-AK.]
2-2 How to use the self diagnostic function for service
A. For normal control with one unit and one remote controller
(1) Pressing the CHECK button on the remote controller twice starts the self diagnostic function.
(2) During the self diagnostic function, “CHECK MODE” appears at two positions on the remote controller display. Then, at
least 10 seconds later, the unit address and the check code is alternately displayed at one-second intervals.
(3) Check and repair the unit according to the check code. (Refer to page 51.)
B. For group control using one remote controller
(1) Pressing the CHECK button on the remote controller twice starts the self diagnostic function.
(2) Press the TEMP. button or TEMP. button on the remote controller to advance or go back to the unit address.
Each time TEMP. button is pressed, the unit address advances by one. Each time TEMP. button is pressed,
the unit address goes back by one.
The check code and the unit address, appear alternately.
(3) The check code “U8” means no malfunction has occurred since installation.
The check code “EO” means the following conditions:
● The unit address displayed on the remote controller does not apply to any unit.
● power is not supplied to the unit.
● Signal transmitting/receiving circuit is abnormal.
(4) Check and repair the unit according to the check code. (Refer to page 51.)
▲
▲▼
▼
49
Page 50
(WIRELESS REMOTE CONTROLLER)
(1) Turn on the main power of the unit.
(2) Turn the adjusting switch on the back of the
wireless remote controller to “SET” CHECK
TEST RUN will start flashing.
★(3) Push the HR. button CHECK will start
flashing.
★(4) While pointing the transmitter to the receiver,
push the HR. button. At this point, you will
hear an intermittent buzzer sound, and oper
ating flash will show check codes.
Intermittent buzzer sound
Operating lamp flashing time
1 second (0.5 second interval)
Repeats as often as the number
of the check code
Remove the battery cover on the back side of
the wireless remote controller, display will start
flashing when the “SET” switch is tured on.
For operations marked “
★”, point the transmit-
ter to the wireless receiver, and make sure that
you will hear a short beep from the receiver.
Turn the adjusting switch to “SET”
˚C
AM
PM
AM
PM
TEMP.
START
STOP
HR.
MIN.
Display will start flashing
ADDRESS
UNIT No.
FUNCTION No.
SELECTION No.
AM
FUNCTION
TEST RUN
CHECK
ON/OFF
PM
AM
PM
TEMP.
˚C
★(5) Push the POWER ON/OFF button and can
cel the test run.
(6) After completing a test run, be sure to turn
the adjusting switch back to “Nrm”.
For operations marked “
less receiver, and make sure that you will hear a short beep
from the receiver.
When the other than main unit is operated by the wireless
remote controller, the receiver beeps an ineffectual beep
3-times.
★”, point the transmitter to the wire-
50
Page 51
Check
code
EOSignal transmitting/receiving
Diagnosis of malfunctionCauseCheck points
error
(Indoor controller does not
respond to remote controller
signal.)
During individual unit control
1) Bad contact of transmission
wire
2) Signal transmitting/receiving circuit is abnormal.
1) Check the transmission wire.
2) Check with another remote controller. If “EO” is
still indicated, replace the indoor controller
board.
If other check code appears. replace the original remote controller.
P1P2Abnormality of room temper-
ature thermistor (RT1)
Abnormality of indoor coil
thermistor (RT2)
P3Signal transmission error
(Remote controller does not
respond to indoor controller
signal.)
P4Abnormality of drain sensor1) Bad contact of transmission
P5Malfunction of drain pump1) Malfunction of drain pump
1) Bad contact of thermistor
2) Damaged thermistor
1) Bad contact of transmission
wire
2) Signal transmitting/receiving circuit is abnormal.
3) Wrong operation due to noise
wave emitted by other appliances
wire
2) Damaged thermistor
2) Damaged drain sensor
1) Check the thermistor.
2) Measure the resistance of the thermistor.
Normal resistance should be as follows.
0: ···15kΩ30:·····4.3kΩ
10:······9.6kΩ 40: ·····3.0kΩ
20:······6.3kΩ
If the resistance is normal, replace the indoor
controller board.
1) Check the transmission wire.
2) Check with another remote controller.
If “P3” is still indicated, replace the indoor
board.
If other check code appears, replace the original remote controller.
3) Short-circuit between
attach CN40 to the following units.
● Second unit in twin control
● Sub units in group control
1) Check the connector.
2) Disconnect CN31, and check the resistance
valve of drain sensor. (1 - 3)
If the resistance is normal, replace the indoor
controller board.
1) Check the drain pump.
2) ● Check the drain sensor.
(Check the drop of water is on.)
If the resistance is normal, replace the indoor
controller board.
1 and 2 of CN40 and
P6Freezing protection/
overheating protection
is working.
P7System error1) Wrong address-setting
P8Abnormality in outdoor unit1) Wrong wiring of indoor/outdoor
1) Short cycle of air cycle
2) Dirty air filter
3) Damaged fan
4) Abnormal refrigerant
2) Signal transmitting/receiving circuit of remote controller is
abnormal.
3) Wrong SW6-setting
connecting wire
2) Reversed phase
3) Protection device is working
51
1) Clear obstructions from the air cycle.
2) Clean the air filter
3) Check the fan.
4) Check the refrigerant temperature.
1) Check the address-setting.
2) Check with another remote controller. If check
code other than “P7” appears, replace the original remote controller.
3) Check SW6 setting.
1) Check the indoor/outdoor connecting wire.
2) Change the connection of electric wiring.
3) Check the protection device.
Page 52
3. OTHER TROUBLES AND CAUSES
Vanes do not work.
Unit stops after 5 to
20 seconds operation
Air discharge display
is OFF and button
does not operate.
In this case, remote
controller is normal.
Power ON/OFF button
is not available.
Vane motor does not work.
Connector is poorly connected.
Vane motor is poorly assembled.
Indoor controller board is damaged.
Protection function is working.
Indoor controller board
deems the auto vanes
are not attached to the
unit.
Horizontal angle can
not be detected.
Beep sound is heard,
but display is turned
OFF.
Beep sound is not heard,
and display remains OFF.
“CENTRALLY CONTROLLED” is displayed.
Indoor controller is
damaged.
Dip switch setting is
wrong.
Indoor controller is
damaged.
Vane motor is damaged.
Auto vane is wired after
power is turned to ON.
Indoor/outdoor connecting wire is connected
incorrectly.
Indoor/outdoor connecting wire shorts.
Compressor protector
is damaged.
Outdoor controller
board is defective.
Remote controller is
damaged.
Transmission wire is
poorly connected
Vane motor is damaged.
Vane motor relay is damaged.
Refer to check code on remote controller display.
See page 51.
Vane motor is damaged.
Transmission wire is
damaged.
Connector is poorly
connected.
Indoor terminal block is
poorly connected.
Remote controller terminal block is poorly
connected.
4. MR. SLIM/LOSSNAY INTERLOCK OPERATION
<Symptoms that are not malfunctions>
If any of the following symptoms occur, they are not malfunctions.
Symptom
LOSSNAY control switch can not work during interlock opera-
LOSSNAY control switch does not work.
LOSSNAY air speed can not be controlled in interlock opera-
tion.
For LOSSNAY, troubleshooting refer to the LOSSNAY technical & service manual.
tion.
LOSSNAY control switch is effective only while Mr. SLIM is not
operating.
LOSSNAY fan speed is fixed to HIGH during interlock operation.
LOSSNAY fan speed LOW/HIGH can be switched only during
LOSSNAY individual operation with the LOSSNAY control
switch.
52
Cause
Page 53
5. How to check the parts PL-3AK / PL-4AKS / PL-5AKS / PL-6AKS
Parts nameCheck points
Disconnect the connector then measure the resistance using a tester.
(Surrounding temperature 10:~30:)
Measure the resistance between the terminals using a tester.
(Surrounding temperature 20:~30:)
Measure the resistance between the terminals using a tester.
(Surrounding temperature 20:~30:)
Measure the resistance between the terminals using a tester.
(Surrounding temperature 10:~30:)
Vane motor
Drain pump
Drain sensor
(Refer to the thermistor)
(Refer to the thermistor)
Room temperature
thermistor (RT1)
Liquid pipe
thermistor (RT2)
1
2
Yellow
Yellow
1
2
3
Normal
4.3k"~9.6k"
Abnormal
Open or short
Abnormal
Open or short
Normal
0.6k"~6.0k"
NormalConnectorAbnormal
300"Open or short
NormalAbnormal
290"Open or short
Orange
Red
White
Red — Yellow
Red — Blue
Red — Orange
Red — White
Blue
Yellow
35
1
2
4
Measure the resistance between the terminals using a tester.
Fan motor
1
1
2
2
3
3
Red
White
Black
Relay connector
Protector
3AK
87.2"
104.1"
Abnormal
Open or short
4,5,6AKS
28.7"
41.6"
Red-Black
White-Black
Motor terminal
or
Relay connector
Normal
PL-
M
53
Page 54
<Thermistor Characteristic graph>
-20 0 20406080
< Thermistor for drain sensor >
Temperature (:)
0
1
2
3
4
5
6
7
8
9
10
Resistance (K")
Thermistor for
lower temperature
Room temperature thermistor(RT1)
Liquid pipe thermistor(RT2)
Thermistor R0=15k' ±3%
Fixed number of B=3480k' ±2%
For 3 and 2-directional,
please use the air outlet
shutter plate (option).
Pattern 1 Factory settingPattern 4 One air outlet
fully closed
Pattern 6 Two air outlet
fully closed
Fresh air intake hole
Fresh air intake hole diagram
3 - {2.8
Burring hole
{125
Burring hole pitch
{100
(Cut out hole)
Refrigerant pipeDrain pipe
Ceiling surface
120_
120_
w158
SW8
4-WAY AIR FLOW SYSTEM
1. Placement of the air outlets
For this grille, the blowout direction comes in 11 patterns.
Also, by setting the dip switches (SW8-3, SW8-4) on the indoor board to the appropriate settings, you can adjust the air flow
and speed. Select the settings from Table according to the location in which you want to install the unit.
1) Decide on the pattern of the airflow direction.
2) According to the number of air outlets and height of the ceiling to install the unit, be sure to set the up switches
(SW8-3, SW8-4) on the indoor board to the appropriate setting.
Correspondence of ceiling heights to numbers of air outlets.
Ceiling height & discharge direction
(Unit : m)
SW8-1 ON
SW8-2 ON
3.5m
3.5m
—
SW8-1 ON
SW8-2 ON
4.2m
4.2m
—
I.B
PL-3AK
PL-3AK-E
SW8-3, 4
4 direction2.7m
3 direction
2 direction
PL-4, 5, 6AKS
PL-4, 5, 6AKS-E
SW8-3, 4
4 direction3.2m
3 direction
2 direction
SW8-1, 2
SW8-3 OFF
SW8-4 OFF
SW8-3 ON
SW8-4 OFF
SW8-3 ON
SW8-4 ON
SW8-1, 2
SW8-3 OFF
SW8-4 OFF
SW8-3 ON
SW8-4 OFF
SW8-3 ON
SW8-4 ON
Standard
SW8-1 OFF
SW8-2 OFF
3.0m
3.3m3.5m
Standard
SW8-1 OFF
SW8-2 OFF
3.6m
4.0m4.2m
High ceiling 1 High ceiling 2
SW8-1 ON
SW8-2 OFF
3.0m
3.3m
High ceiling 1 High ceiling 2
SW8-1 ON
SW8-2 OFF
3.6m
4.0m
2. Fresh air intake (Installation of site)
• At the time of installation, use the duct holes (cut out) located at the positions shown in following diagram, as and when
required.
Note :
Be sure to add135mm to the dimensions in the diagram that are marked with a “w” if installing a multi function casement
(Option)
55
Page 56
3. Fixing of horizontal vane
Standard of
horizontal position
Dimension A (mm)
26293337
Level 30°
(Min.)
Downward 45°Downward 55°
Downward 70°
(Max.)
w Dimension between 26mm and 37mm can be arbitrarily set.
Caution
Do not set the dimension out of the range.
It could cause dew drips and attain on ceiling, etc. and the unit may be damaged.
<Set range>
Horizontal vane of each air outlet can be fixed according to the environment, which is installed.
Setting procedure
1) Turn off a main power supply (Turn off a breaker).
2) Disconnect the vane motor connector of the direction of the arrow with pressing the unlocking button as shown in figure
below.
Electricity insulate the disconnected connector with the vinyl tape.
Vane motor
Vane motor
Connector
Unlocking button
Horizontal vane
3) Set a vertical vane of the air outlet, which tries to fixed by the hand slowly within the range in the table below.
Measured standard
position of the grille
Horizontal vane
56
Page 57
4. Fresh air intake amount & static pressure characteristics
Q
0
B
A
C
1
Curve in the
left praphs.
Duct characteristics
at site
Q
A
EC
2
Q
Qa
AD
3
ll
PL-3AK, PL-3AK-E
Multifunction casement + Standard filter
Multifunction casement + High efficiency filter
Static pressure [Pa]
50
0
123456
-50
-100
-150
-200
Taking air into the unit
Static pressure [Pa]
50
0
123456
-50
-100
-150
-200
1 intake
Air flow [m
2 intakes
Air flow [m
3
/min]
3
/min]
Static pressure [Pa]
50
0
-50
-100
-150
-200
How to read curves
123456
1 intake
Q…Planned amount of fresh air intake
A…Static pressure loss of fresh air
intake duct system with air flow
amount Q
B…Forced static pressure at air condi-
tioner inlet with air flow amount Q
C…Static pressure of booster fan with
air flow amount Q
D…Static pressure loss increase
amount of fresh air intake dust system for air flow amount Q <Pa>
E…Static pressure of indoor unit with air
flow amount Q
Qa…Estimated amount of fresh air
intake with out D<m3/min>
Air flow [m
2 intakes
3
/min]
<m
3
/min>
<Pa>
<Pa>
<Pa>
<Pa>
22
PL-4 · 5 · 6AKS, PL-4 · 5 · 6AKS-E
Multifunction casement + Standard filterMultifunction casement + High efficiency filter
Static pressure [Pa]
50
0
-50
-100
-150
-200
123456789
2 intakes
1 intake
Static pressure [Pa]
Air flow
3
[m
/min]
-50
-100
-150
-200
50
0
123456789
1 intake
Air flow
3
/min]
[m
2 intakes
Taking air into the unit
Static pressure [Pa]
50
0
123456789
Air flow [m
3
/min]
-50
-100
-150
-200
57
Page 58
Fresh air intake hole
Refrigerant pipeDrain pipe
Branch duct hole
(Cut out hole)
Branch duct hole diagram
(view from either side)
Branch
duct hole
{175
Burring hole pitch
{150
Cut out hole
14 - {2.8
Burring hole
350
90
70_
100 100 90
100
130
w155
w167
Branch
duct hole
CN51
Multiple remote
controller adapter
PAC-SA88HA-E
Indoor controller board
Distance between indoor
controller board and relay
must be within 10m.
Be sure to secure insulation
material by tape and such
5
Green
Yellow
Orange
Connector (5P)
Package side
Multiplr remote
controller adapter
PAC-SA88HA-E
Be sure to secure insulation
material by tape and such
Installation at site
CN51
on
indoor unit
board
Red
Brown
1
MB
~
CN51
5. Interlocking operation method with duct fan (Booster fan)
●Whenever the indoor unit is operating, the duct fun operates.
(1)Connect the optional multiple remote controller
adapter(PAC-SA88HA-E)to the connector CN51 on the
indoor controller board.
(2)Drive the relay after connecting the 12V DC relay
between the Yellow and Orange connector lines.
Use a relay under 1W.
MB: Electromagnetic switch power relay for duct fan.
X: Auxiliary relay (12V DC LY-1F)
6. BRANCH DUCT(Installation at site)
Discharge by branch duct becomes possible by installing a branch duce at site. Knockout holes on the wall panel of the indoor
unit must be removed.
6-1 Branch Duct Installation Procedure
At the time of installation, use the duct holes (cut out) located at the positions shown in following diagram, as and when
required.
Note :
The figure marked with wwin the drawing represent the dimensions of the main unit excluding those of the optional
multi function casement.
When installing the optional multi function casement, add 135 mm to the dimensions marked on the figure.
When installing the branch ducts, be sure to insulate adequately. Otherwise condensation and dripping may occur.
7. Air flow & Static pressure characteristics of Branch Duct (with SWA at “Standard”)
Static
pressure
[Pa]
Air flow [m
3
/min]
30
20
10
0
123456
Hi
Lo
Static
pressure
[Pa]
Air flow [m
3
/min]
30
20
10
0
123456
Hi
Lo
Static
pressure
[Pa]
Air flow [m
3
/min]
50
40
30
20
10
0
123
Hi
Lo
45678910
Static
pressure
[Pa]
Air flow [m
3
/min]
50
40
30
20
10
0
123
Hi
Lo
45678910
Static
pressure
[Pa]
Air flow [m
3
/min]
50
40
30
20
10
0
123
Hi
Lo
45678910
Static
pressure
[Pa]
Air flow [m
3
/min]
50
40
30
20
10
0
123
Hi
Lo
45678910
Static
pressure
[Pa]
Air flow [m
3
/min]
30
40
50
60
20
10
0
123456789
Hi
Lo
Static
pressure
[Pa]
Air flow [m
3
/min]
50
60
70
80
90
100
40
30
20
10
0
123
Hi
Lo
4567891011121314
Static
pressure
[Pa]
Air flow [m
3
/min]
50
60
70
80
90
100
40
30
20
10
0
123
Hi
Lo
4567891011121314
Static
pressure
[Pa]
Air flow [m
3
/min]
30
40
50
60
20
10
0
123456789
Hi
Lo
Static
pressure
[Pa]
Air flow [m
3
/min]
50
60
70
80
90
100
40
30
20
10
0
123
Hi
Lo
4567891011121314
Static
pressure
[Pa]
Air flow [m
3
/min]
50
60
70
80
90
100
40
30
20
10
0
123
Hi
Lo
4567891011121314
4 direction airflow (Horizontal vane)
Angled duct
PL-3AK, PL-3AK-E
Rounded duct
PL-3AK, PL-3AK-E
PL-4AKS, PL-4AKS-E
PL-5, 6AKS, PL-5, 6AKS-E
3 direction airflow (Horizontal vane)
Angled duct
PL-3AK, PL-3AK-E
PL-4AKS, PL-4AKS-E
PL-5, 6AKS, PL-5, 6AKS-E
Rounded duct
PL-3AK, PL-3AK-E
PL-4AKS, PL-4AKS-E
PL-5, 6AKS, PL-5, 6AKS-E
PL-4AKS, PL-4AKS-E
PL-5, 6AKS, PL-5, 6AKS-E
59
Page 60
2 direction airflow (Horizontal vane)
Angled duct
Rounded duct
PL-3AK, PL-3AK-EPL-3AK, PL-3AK-E
Static
pressure
[Pa]
100
90
80
70
60
50
40
30
20
10
0
1234567891011
Lo
Air flow [m
Hi
3
/min]
Static
pressure
[Pa]
100
90
80
70
60
50
40
30
20
10
0
1234567
Air flow [m
PL-4AKS, PL-4AKS-EPL-4AKS, PL-4AKS-E
Static
pressure
[Pa]
120
110
100
90
80
70
60
50
40
30
20
10
0
Hi
Lo
123
4 5 6 7 8 9 10 1112 131415 16
Air flow [m
3
/min]
pressure
Static
[Pa]
120
110
100
90
80
70
60
50
40
30
20
10
0
123
Hi
Lo
3
/min]
Hi
Lo
4 5 6 7 8 9 10 1112 131415 16
Air flow [m
3
/min]
PL-5, 6AKS, PL-5, 6AKS-EPL-5, 6AKS, PL-5, 6AKS-E
Static
pressure
[Pa]
120
110
100
90
80
70
60
50
40
30
20
10
0
Lo
123
4 5 6 7 8 9 10 1112 131415 16
Air flow [m
Hi
pressure
3
/min]
Static
[Pa]
120
110
100
90
80
70
60
50
40
30
20
10
0
Lo
123
4 5 6 7 8 9 10 1112 131415 16
Hi
Air flow [m
3
/min]
60
Page 61
Unit
Remote
controller
UnitUnit
Unit
Remote
controller
UnitUnit
Optional
adapter
Remote
ON/OFF
switch
Remote
controller
Relay box
Unit
Unit
Remote
controller
UnitUnit
Unit
Remote controll
display board
Remote
controller
UnitUnit
Circuit breaker
Remote
controller
12
SYSTEM CONTROL
1. VARIETY OF SYSTEM CONTROL FUNCTIONS
1 Group control with
a single remote
controller
(See page 62.)
2 Control using two
remote controllers
(See page 63.)
3 Both remote
ON/OFF and individual controls
(See page 63.)
w Timer adapter
(PAC-SA89TA-E)
is needed.
4 Individual control
by grouping
remote controllers
(See page 64.)
Many units, installed at different locations, can be started
and controlled with a single remote controller. The remote
controller can be mounted in a different location using a
non-polar two-wire cable, which can be extended up to
500m. Amaximum of 50 units can be controlled with a
single remote controller. All units operate in the same
mode.
Two remote controllers can be used to control either one
unit or a group of units. Units can then be controlled from
a distance or at close range. Units operate according to
the latest command from either remote controller.
All units can be turned on or off simultaneously using a
remote ON-OFF switch. Also, each unit can be controlled
individually by each remote controller. Dunning remote
ON-OFF control, a message of “CENTRALLY CONTROLLED” is displayed on the LCD of the remote controller.
This is available for both one unit control and several units
control.
By grouping the remote controllers in one place, several
units installed at different locations can be controlled individually, and operation conditions of all units are visible
without a special control board. The control method is the
same as that of the single unit with a single remote controller.
5 Multiple remote
control display
(See page 65.)
w Multiple display
adapter
(PAC-SA88HA-E)
is needed.
6 Auto restart
function
(See page 65.)
Several units can be controlled with a remote control display board. Operation conditions of all the units are visible with the remote control display board.
Individual control by each remote controller is also possible.
A unit can be started or stopped with the circuit breaker
on or off.
Remote controller is also available.
With this function, when the power is restored after power
failure, the unit will restart automatically. (However, when
the remote controller POWER ON/OFF button is OFF, the
unit will not start.)
61
Page 62
2. GROUP CONTROL WITH A SINGLE REMOTE CONTROLLER
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
To remote
controller
To next
unit
To next unit
The last unit
dose not have
this wire.
Next unit
electrical box
Master unit
electrical box
123LN
PE
LN
PE
123
Master
unit
No.1 unitNo.2 unitLast unit
2-wire cable
SW2
CN40
CN40
SW2
Should be removed
from all units other
than unitNo.0:
(Master Unit).
1
2
3
4
5
6
ON
A maximum of 50 units can be started in order according to the dip switch settings
2-1 How to wire
(1) Connect the remote controller to the double terminal block
on the indoor controller board of the master unit (No.0 unit).
(See Figure 1.)
(2) Connect the double terminal block of the master unit to the
double terminal block of No.1 unit.
(3) Connect the double terminal block of No.1 unit to the dou-
ble terminal block of No.2 unit.
(4) Continue the process until all the units are connected with
two-wire cables. (See Figure 2.)
(5) Remove the connector CN40 from the indoor controller
board of each unit except the master unit. (See Figure 3.)
(6) Set the unit-address of each unit with SW2 on the indoor
controller board following the instructions below.
2-2 How to set unit-address
The unit-address also serves as a successive-start timer which
starts each unit at intervals of 1 second. If two or more units
have the same unit-address in a group control, operation stops
due to system error. Be sure to set SW2 correctly following the
instructions below.
(1) Each lever of SW2 shows the number as follows.
(2) Total number of levers turned to ON shows the address of
the unit.
For example, to set No.3 unit, turn ON SW2-1 and SW2-2.
(3) In this way, set from the master unit to the last unit.
Do not forget to set the master (No. 0) unit.
Figure 1
Figure 2
Figure 3
Indoor controller board ▼
Setting examples
SW2
Unit address & start
delay in seconds.
2-3 Unit control
The remote controller can control all units ON/OFF, temperature, air flow, and swing louver. However, the thermostat in
each unit turns ON or OFF individually to adjust to the room temperature.
Master (No. 0) unit
ALL OFF
No. 1 unit
1 ON
0
1
No. 2 unit
2 ON
2
No. 4 unit
3 ON
4
No. 8 unit
4 ON
8
No. 16 unit
5 ON
16
No. 32 unit
6 ON
32
62
Page 63
3.
Figure 4
Individual
operation
Remote
controller
Remote
controller
Remote
controller
Remote
controller
Multiple operation
SW17
SW18-5 ON
Remote controller
(Set to cool only)
Figure 5
Remote
controller
power supply of
control circuit
Remote
ON/OFF
switch
2-wire
remote
controller
cable
Figure 6
Relay box
Timer adapter cables
Timer adapter
PAC-SA89TA-E
8
7
6
5
4
3
2
OFF
1
Main remote controllerSub remote controller
Turn SW17-7 ON.
8
7
6
5
4
3
2
OFF
1
CONTROL USING TWO REMOTE CONTROLLERS : OPTIONAL REMOTE CONTROLLER
(PAR-JA240KA)
Two remote controllers can be used to control either one unit or a group of units. Units operate according to the latest com-
mand from either of the two remote controllers.
Before operation, be sure to set one remote controller as the “main controller” and the other as the “sub controller”, using dip
switch SW17-7 of the remote controller.
3-1 How to set SW17-7 (See Figure 5.)
(1) For the main remote controller, turn SW17-7 OFF.
(2) For the sub remote controller, turn SW17-7 ON.
3-2 Remote controller LCD indication
(1) The same indications always appear on both the
main and sub remote controllers, except during the
timer operations.
(2) Timer operations can be set with either of the two
remote controllers. However, LCD indication appears
only on the remote controller used for timer-settings.
(3)If both remote controllers are set for timer operation
with different time-settings, the timer operation with
the shorter remaining-time is effective.
(4) Self-diagnostic function is available with either of the
two remote controllers. If one of the remote controllers is used for the self-diagnostic function, the
other remote controller displays the check mode.
If the self-diagnostic function is reset by either of the
two remote controllers, both remote controllers are
reset.
4. REMOTE ON-OFF AND INDIVIDUAL REMOTE CONTROLS
This method is available to control one unit or any number of units.
The following operations are available by connecting a relay, a timer adapter (PAC-SA89TA-E), and a remote ON/OFF switch
to the system. Timer adapter is an optional part. Other parts are available on the market.
(A) To start all units in order by remote ON-OFF switch
(B) To stop all units simultaneously by remote ON-OFF switch
(C) To switch between the remote ON-OFF control and the individual remote control
4-1 System
Figure 6 shows the case of three units. The same is the case with any number of units.
63
Page 64
NOTE1 : Install the relay box where you can be serviced it easily.
Power
supply
Remote
ON/OFF
switch
No.1 unit
relay box
No.2 unit
relay box
Next unit
T
X2X2
T
Glow switch or pilot lamp can be
combined to easily identify the
on-off mode of SW1 and SW2.
To
No.1
unit
To
No.2
unit
Timer adapter cables
Remote controller
T
X2
SW
1
SW2
T
X2
Remote
controller cable (2-core)
Remote controller
NOTE2 : For control circuit wiring, use a wire of No. 14 AWG or a control cable according to the power supply of control
circuit.
NOTE3 : When the power supply of the control circuit is 220/240V AC,
● Do not connect the control circuit wire to the remote controller cable directly.
● Do not place the control circuit wire and the remote controller cable into the same conduit tube.
4-2 Basic wiring
Note : Before starting all units simultaneously by the remote ON-OFF switch, be sure to connect a sequence-start timer
into the remote ON-OFF circuit. Otherwise, a rush of starting current may damage the power supply.
4-3 Switch function of remote ON-OFF switch
SW2
(Switches between remote control and individual control)
SW1
(Switches between
remote ON and OFF.)
ON
(Start)
OFF
(Stop)
ON
(Remote ON-OFF control)
All units start together.
w1
Individual control is not available.
All units stop together.
w2
Individual control is not available.
Each unit can be controlled by each
remote controller.
Remote ON-OFF switch is not available.
OFF
(Individual control)
w1 After all units start at once, if SW2 is turned OFF, each unit can be individually stopped by each remote controller.
w2 After all units stop at once, if SW2 is turned OFF, each unit can be individually started by each remote controller.
5. INDIVIDUAL CONTROL BY GROUPING THE
REMOTE CONTROLLERS
● Grouping the remote controllers allows individual control and cen-
tralized monitoring of units installed in different places without a
special control board.
● Remote control cables are extendible up to 500m. When the cable
length exceeds 12m, use the double-insulated two-care cable such
as Belden 9407. Also, the cable thickness must be No. 22 AWG or
above.
● When gathering the power ON/OFF switches of air conditioners
near the remote controllers, you should also install the power
ON/OFF switch near each unit to prevent electric trouble during
servicing.
64
Page 65
6. MULTIPLE REMOTE CONTROL DISPLAY
CN51
connector(5P)
GREEN
Power
supply
Electrical insulation is needed.
Wiring at the actual place
Optional multiple display
adapter
The maximum distance between
indoor board and relay is 10m.
YELLOW
ORANGE
RED
BROWN
5
X2
X2
GL
RL
X1
X1
1
<Wiring >
CN51
Indoor controller board
CN51
Power
supply
Remote
controller
cable
Relay box
(Field supply)
Remote
controller
Remote
controller
Remote
controller
3wires
3wires
3wires
2wires
No.1 unitNo.2 unitNo.3 unit
Muitiple remote control
ON-OFF display
(Field supply)
(Operation check)
<System>
Power
supply
RL-1
GL-1
Multiple Remote Control Display
Multiple remote
controller adapter
connect to
the connector CN51
Relay box
5
X1-1
X2-1
1
<Wiring diagram>
RL-2
GL-2
RL-3
No.1 unit
GL-3
X1-1
X2-1
X1-2
X1-3
X2-3
X2-2
5
1
No.2 unit
5
1
No.3 unit
X1-2
X2-2
X1-3
X2-3
Remote controller
A
B
Brown
Red
Orange
Remote controller
A
B
Brown
Red
Orange
You can control several units with a multiple remote control display, by
wiring an optional multiple display adapter (PAC-SA88HA-E) with relays
and lamps on the market.
6-1 How to wire
(1) Connect the multiple display adapter to the connector CN51 on the
indoor controller board.
(2) Wire three of the five wires from the multiple display adapter as shown
By setting the dip switch SW1-8 to ON, the air conditioner can be started/stopped by power supply ON/OFF.
If the air conditioner is OFF before the power failure, it will not start operation by power restore.
•This function is mainly to emergency performance when the power supply stops temporarily. Therefore, since the protection function (for example, clank case heater and prevention from restarting in 3 minutes, etc.) of the device is not operated, this function should not be used mostly.
8. TIMER OPERATION OR THE OPERATION BY AN EXTERNAL SIGNAL
<Wiring>
For remote control, connect the optional timer adapter (PAC-SA89TA-E)
65
A : an optional timer adapter
B : a single-throw switch
Page 66
13DISASSEMBLY PROCEDURE
PL-AK Series
OPERATING PROCEDUREPHOTOS & ILLUSTRATIONS
1. Removing the air intake grille
(1) Slide the knob of air intake grille to the direction of the
arrow
1 to open the air intake grille.
(2) Remove the string hook from the panel to pretend the
grille from dropping.
(3) Slide the shaft in the hinge to the direction of the arrow2
and remove the air intake grille.
2. Removing the fan guard
(1) Open the air intake grille.
(2) Remove the 3 screws of fan guard.
Be careful on removing heavy parts.
Figure 1
Air intake grille
Grille
Air intake grille knob
Photo 1
Screws
Fan guard
Air intake grille
3. Removing the room temperature thermistor
(1)Remove the fan guard.(See photo 1)
(2) Remove the screw(✕1) in the room temperature thermistor
holder to remove the holder and the room temperature
thermistor.
(3) Remove the 1 screw from the bell mouth, and unscrew the
another 2 screws (fixed to the oval hole which has different
diameter) to remove the bell mouth.
(4) Hold the holder claw, and remove the room temperature
thermistor and holder.
(5) Disconnect the connector (red) in the indoor control board.
4. Removing the electrical box
(1) Disconnect the lead wire of the vane motor from the clamp,
and disconnect the white connector (10P).
(2) Remove the room temperature thermistor with the holder.
(3) Remove the bell mouth.(See photo 2)
(4) Disconnect the relay connector in the electrical box.
Red (3P) for ran motor power supply
White (2P) for pipe temperature detecting thermistor
Blue (2P) for drain pump
White (3P) for drain sensor
(5) Remove the 3 screws from the electrical box, loosen
another 2 screws to remove the box.
<Electrical parts in the electrical box>
Indoor controller board
Power supply board
Terminal block
Capacitor
Photo 2
Bell mouth
Photo 3
Turbo fan
Electrical
box
Power
supply
board
Nut
Screws
Room
temperature
thermistor
Air intake grille
Capacitor
Terminal
block
66
Connector
Indoor controller board
Connector
Page 67
OPERATING PROCEDURE
PHOTOS & ILLUSTRATIONS
5. Remove the fan motor
(1) Remove the fan guard.(See photo 1)
(2) Remove the bell mouth.(See photo 2)
(3) Remove the electrical box.(See photo 3)
(4) Remove the turbo fan nut.
(5) Pull out the turbo fan.
(6) Disconnect the connector of the fan motor lead wire.
(7) Remove the 4 nuts of the fan motor.
6. Removing the pipe temperature thermistor
(1) Remove the fan guard.(See photo 1)
(2) Remove the bell mouth.(See photo 2)
(3) Remove the electrical box.(See photo 3)
(4) Remove the turbo fan.
(5) Remove the screw of the service panel.
(6) Remove the service panel.
(7) Remove the pipe temperature thermistor which is inserted
into the holder installed to the thin copper pipe.
(8) Disconnect the 2-pin white connector.
Photo 4
Photo 5
Fan motor
Nut
Pipe temperature thermistor
Connector
Nut
7. Removing the panel
(1) Remove the air intake grille.(See figure 1)
Corner panel (See figure 2)
(1) Remove the screw of the corner.
(2) Slide the corner panel to the direction of the arrow3, and
remove the corner panel.
Panel (See photo 6)
(1) Disconnect the connector that connects with the unit.
(2) Remove the 2 screws from the panel and loose another 2
screws, which fixed to the oval hole, have different diameter.
(3) Rotate the panel a little to remove the screws.(Slide the
panel so that the screw comes to a large diameter of the
oval hole, which has two different diameters.)
8. Removing the drain pan
(1) Remove the panel. (See photo 6)
(2) Remove the drain plug (Larger one), drain the remaining
water in the drain pan.
(3) Remove the corner cover. (2 screws)
(4) Remove the bell mouth (See photo 2)
(5) Remove the electrical box. (See photo 3)
(6) Remove the lead wire holder. (1 screw)
(7) Remove the 4 screws and pull out the drain pan.
w Pull out the left and right of the pan gradually.
Be careful not to crack or damage the pan.
Figure 2
Corner
panel
Photo 6
Connector
Screw
Photo 7
Screw
Drain pan
Screw
Service entrance
Screw
Corner
panel
Panel
Screw
Panel
Screw
Screw
67
Lead
wire
holder
Drain plug(Larger one)
Corner cover
Page 68
OPERATING PROCEDUREPHOTOS & ILLUSTRATIONS
9. Removing the drain pump and drain sensor
(1) Remove the panel. (See photo 6)
(2) Remove the fan guard. (See photo 1)
(3) Remove the bell mouth. (See photo 2)
(4) Remove the electrical box. (See photo 3)
(5) Remove the drain pan. (See photo 7)
(6) Remove the 3 screws of the drain pump.
(7) Cut the drain hose band, pull out the drain hose from the
drain pump.
(8) Pull out the drain pump.
(9) Remove the drain sensor and the holder.
10. Removing the heat exchanger
(1) Remove the panel. (See photo 6)
(2) Remove the fan guard. (See photo 1)
(3) Remove the bell mouth. (See photo 2)
(4) Remove the electrical box. (See photo 3)
(5) Remove the drain pan. (See photo 7)
(6) Remove the turbo fan. (See photo 4)
(7) Remove the 3 screws of the piping cover, and pull out
piping cover.
(8) Remove the 4 screws of the outer wall cover, and pull out
the outer wall cover.
(9) Remove the screw of the coil support.
(10) Remove the 2 screws of the coil.
(11) Pull out the heat exchanger.
Part numbers that is circled is not shown in the figure.
14
13
3
8
7
4
5
6
69
Page 70
FUNCTIONAL PARTS
PL-3AK / PL-4AKS
PL-3AK-E / PL-4AKS-E
7
31
10
8
8
11
9
2
4
6
5
No.
Parts No.
T7W E06 762
1
T7W E07 762
R01 E00 114
2
R01 E01 114
R01 A41 105
3
R01 08K 097
4
T7W E06 202
5
T7W E36 480
6
T7W E37 480
7
8
9
10
11
—
—
—
—
—
—
—
Parts Name
FAN MOTOR
FAN MOTOR
TURBO FAN
TURBO FAN
RUBBER MOUNT
SPL WASHER
PIPE TEMPERATURE THERMISTOR
HEAT EXCHANGER
HEAT EXCHANGER
BASE
BASE
LEG
LEG
LEG
INNER ASSY
INNER ASSY
Factory supplied optional refrigerant pipings contain refrigerant at the above atmospheric pressures. As long as the
connection takes no more than 5 minutes, no air will enter, and there will be no need for air purging.
Remove the blind caps and make the connections within 5 minutes. After the connections for the indoor and outdoor
units are made, open the stop valve on the outdoor unit to allow refrigerant gas to flow.
Note 2. The following main parts are contained in the optional refrigerant piping kit.
When using a program timer, a program timer adapter (PAC-825AD) is also needed.
Part No.PAC-SC32PTA(with set back function)
Model NameProgram timer
2-1 Program timer specifications
Parts nameProgram timer
Parts No.PAC-SC32PTA
Exterior dimensions (inch)5-4/32x4-23/32x23/32 (130x120x18mm)
InstallationWall mount
Type of clockQuartz
Clock accuracy±50 second / month at 25°C
Display-Time
-Week
-Timer setting unit
Program cycle24 hours
Timer setting unit30 minutes
No. of set points48 / day
Power rating5V DC ±5% (Supplied by Remote Controller)
2-2 Feature of program timer
(1) Daily timer function
Daily timer can be set in 30 minutes units for up to 24 hours.
Each unit can be set for unit ON, unit OFF, or setback operation.
(2) Setback operation (PAC-SC32PT)
Set back operation is useful for reducing running costs
e.g. At a hotel with a 24-hour system
8:00~23:00 Cooling operation with set temperature at 26°C
23:00~8:00 Setback operation with 2 degrees of setback
As shown in the chart on the night, the set temperature rises 2 degrees
automatically during the setback operation. When the setback operation
ends, normal operation will begin.
(3) Weekly timer function
Daily timer function can apply to each day of the week.
(1) Install the program timer next to the remote controller the same way as the remote controller is installed.
(2) Connect the program timer and the remote controller with a 5-wire cable as shown in the figure below
NOTE:While the program timer is connected to the remote controller, the
24hour ON/OFF timer on the remote controller will not operate.
2-4 Names and functions
<PAC-SC32PTA>
WEEKLY TIMER SETTING DISPLAY
CURRENT TIME DISPLAY
SET BACK DISPLAY
DAILY TIMER SETTING DISPLAY
Used for selection of if or not the day operation pattern set by PATTERN SETTING is to
be applied in weekly day unit, setting.
During MONITOR status,current
time is display.
During Daily timer setting, a
time desire for timer setting is
Indicates the setting set
back range.
24 hours is divided into 48 blocks and each
block express 30 minutes.
The block display consists of 3 pattern.
displayed.
Set back can be done in the range of 1,2,4,6
and 8°C.
SET BACK SETTING SW
SET/MONITOR DISPLAY
During SET is display, clock adjustment,
change of weekly day, daily and weekly timer
setting can be performed.
During MONITOR is display, all switches
except SET/MONITOR SW are invalidated.
This is normal status.
Used for set back setting.
ON/SET BACK/OFF SW
Used to specify the time setting pattern.
WEEK DAY SETTING SW
DAILY TIMER SW
Used for week day setting.
MODE SELECTOR SW
Using this switch select “MONITOR” or “SET”
Mode.
“MONITOR” :Indicates the current timer set-
ting. All switch expect MODE
SELECTOR SW are invalidated
then.This is the normal status.
“SET” :Set to “SET” mode for clock
adjustment, charge of week day,
daily and weekly timer setting.
CLOCK ADJUSTMENT SW
Used for adjustment of the current time.
Push SW to advance the time. Each time the button is
pushed the time advance by 1 minute, pushing continuously
advances by 1 minute at 0.5 second interval, and when the
lower digit of minute becomes 0 indication advances in 10 minutes unit.
SW is used for reversing the time. Each time the button is
pushed the time reverses by 1 minute, pushing continuously
reverses the time by 1 minute at 0.5 second interval, and when
the lower digit of minute becomes 0 indication reverses in 10
minutes unit.
3. TIMER ADAPTER
This adapter is needed for system control and for operation via external contacts. Adapter connection is described on page 65.
Used for timer setting in 30 minutes unit.
WEEKLY TIMER SW
Used for setting timer in day of week unit.
Pushing SW moves the week day light
display in order of
S → M → T → W
enabling to set the week day.
…
Part No.PAC-SA89TA-E
ORN1
BRN
RED
2
3
75
Page 76
4. MULTIPLE REMOTE CONTROLLER ADAPTER
This adapter is needed for remote indication (operation/check). Adapter connection is described on page 65.
Part No.PAC-SA88HA-E
1
2
3
4
5
BRN
RED
ORN
YLW
GRN
5. CENTRALIZED REMOTE CONTROLLER
Allows individual or combined control of up to 16 units. When using the PAC-805RC, the program timer adapter (PAC825AD)is also needed. See page 65.
Part No.PAC-805RC
Unit : mm
5-1 Dimensions
113
12
23.5
56.5
11
ENGAGED
GROUP
12345678910
GROUP
SELECTION
PROGRAM
ACTIVE BYPASS
TIMER
CONTROLLER
DUAL CENTRAL
OPERATION
117
5-2 Functions
"ENGAGED" indicator
When this indicator is lit, transmission is in
progress and all switches are inoperative.
POWER
ON/OFF
AHEAD
BACK
ACTIVE
BYPASS
DUAL
CENTRAL
MITSUBISHI ELECTRIC
117
ENGAGED
GROUP
12345678910
ACTIVE BYPASS
DUAL CENTRAL
GROUP
SELECTION
PROGRAM
TIMER
CONTROLLER
OPERATION
BACK
ACTIVE
BYPASS
DUAL
CENTRAL
10 9 8 7 6 5 4 3 2 1
POWER
ON/OFF
AHEAD
8
113
POWER ON/OFF switch
Operation ON/OFF switch.
▲BACK ▼AHEAD buttons
These buttons are used to designate
DUAL/CENTRAL switch
This change-over switch governing the
operation of the accessory remote controller.
"DUAL"
Instructions from both the accessory
remote controller and the centralized
remote controller are valid. (Priority given
to the last instruction received.)
"CENTRAL"
ON/OFF switching by the accessory
remote controller is invalidated. Control is
by the centralized remote controller only.
Initial setting is "DUAL".
ENGAGED
GROUP
12345678910
ACTIVE BYPASS
DUAL CENTRAL
GROUP
SELECTION
PROGRAM
TIMER
CONTROLLER
OPERATION
POWER
ON/OFF
AHEAD
BACK
ACTIVE
BYPASS
DUAL
CENTRAL
MITSUBISHI ELECTRIC
the attached unit(s). (They designate
the unit to be centrally controlled.)
●When group “00” is designated; collective ON/OFF instruction is sent to all
units.
●When group “01”-“16“ is designated;
ON/OFF instruction is sent to the designated units only.
ACTIVE/BYPASS switch
This is a change-over switch for the
program timer.
(It selects timer operation on the program timer.)
Use “BYPASS” when a program timer
is not connected.
LCD Matrix Display
This display indicates the operational sta-
tus of all connected units either by steady
lighting or by flashing.
“ACTIVE”
The switch turns ON/OFF operational
instructions from the program timer
automatically.
“BYPASS”
ON/OFF Operation is by the centralized remote controller only.
Initial setting is “BYPASS”.
Independent “DUAL / CENTRAL” and “ACTIVE / BYPASS” setting of all the groups is possible. When the power supply to the
centralized remote controller is cut due to power failure, all settings will return to original “DUAL” and “BYPASS”.
76
Page 77
5-3 Connection method
(1) Connections in the power supply cord.
1. Connect the power supply cord to the power supply terminal-block and fix it in-place with a tie-wrap.
Connect a single phase 200V AV (220, 230, 240V) to .
As is the GND terminal, be sure to ground the earth wire.
E
2. Connect the transmission line to the transmission terminal-block and fix it in-place with a tie-wrap.
Use a Ω1.6 (AWG 14) or above two-wire cable for the transmission line.
CAUTION : Never connect the power supply cord to the transmission terminal-block.
L N
TERMINAL-BLOCK
FOR TRANSMISSION
TERMINAL-BLOCK
OF POWER SUPPLY
Transmission
Tie-wrap
TRANSFORMER
ANE
Fuse(5A)
Tie-wrap
(W)(R) (O)
(BR)
200
220
230
T
(Y)
240
5A
L
N
Wiring has to be changed when
a 200,230 or 240V power is used.
(2) Connection method of centralized remote controller and power supply board.
1. Connect the centralized remote controller and power supply board with a non-polar, two-wire cable.
To adaptor's
terminal-block
Power supply board box
POWER
SUPPLY
GROUP
SELECTION
PROGRAM
TIMER
CONTROLLER
OPERATION
BACK
ACTIVE
BYPASS
DUAL
CENTRAL
10 9 8 7 6 5 4 3 2 1
POWER
ON/OFF
AHEAD
To adaptor's
Non-polar,
two-wire cable
terminal-block
ENGAGED
GROUP
12345678910
ACTIVE BYPASS
DUAL CENTRAL
Centralized remote
controller
2. Wiring diagram3. Be sure to set the maximum address number with the
dip switch SW17 on the centralized remote controller.
BACK
ACTIVE
BYPASS
DUAL
CENTRAL
10 9 8 7 6 5 4 3 2 1
POWER
ON/OFF
AHEAD
Dip switch
SW17
Centralized
remote controller
Power supply
board
ENGAGED
GROUP
12345678910
ACTIVE BYPASS
DUAL CENTRAL
GROUP
SELECTION
PROGRAM
TIMER
CONTROLLER
OPERATION
77
Page 78
ANE
Dip switch
Fig.-1Fig.-2
CN22
TRANS
T
(Y)
SW1
Terminal block for
transmission to
program timer or
centralized remote
controller
(B)
(W)
200
5A
L
POWER
SUPPLY
N
;
POWER SUPPLY CORD
Fuse(5A)
Tie-wrap
Wiring has to be changed when 200V power supply is used.
Tie-wrap
Transmission cord
TRANSFORMER
TERMINAL-BLOCK
FOR POWER
SUPPLY
TERMINAL-BLOCK
FOR
TRANSMISSION
SW1
CN22
CN1 CN21 CN51 CN30CN42 CN50 CN40
(AG)
TRANS
220
240
6. PROGRAM TIMER ADAPTER
Length : 2m (6' 7")
Length : 2m (6' 7")
Length : 2m (6' 7")
This adapter is needed when a program timer(PAC-SC32PTA)or a centralized remote controller(PAC-805RC)is used.
Connection and wiring methods differ with the type of the indoor unit used. Confirm the type before carrying out the work.
(1) Connections in the adapter box
1. Connect the power supply cord to the terminal-block and fix it in-place with a tie-wrap.
Connect a single phase 200V (220, 230, 240V) AV to .
As is the GND terminal, be sure to ground the earth wire.
E
L N
2. Connect the transmission line to the transmission terminal-block and fix it in-place with a tie-wrap (when a
centralized remote controller is being used).
CAUTION : Never connect the power supply cord to the transmission terminal-block
(2) When the centralized remote controller is used, set the address number with the dip switch SW1 of the
program timer adapter.
78
Page 79
(3) Connections from adaptor
Fig.3
To program timer or
centralized remote
controller
Adaptor
CN30 CN50
200~240V AC
6-3 Dimensions
Fig.4
35
3-core cable 5-core cable
CN51
Remote controller Indoor unit
Max. length of each calbe is 10m.
408040 27 18
220
Fixing screw hole
95
4- 5.5
22
12
74
7
8
120
2 2- 2.9
30
200
8670
22
27
65
52
15
hole
35
15
230
15
7. MULTI FUNCTION CASEMENT (For HIGH EFFICIENCY FILTER AND FRESH AIR INTAKE)
• The gas pipe 2 and liquid pipe 3 are specified as shown below.
2 Gas pipe3 Liquid pipe
SDD-50S-E
Indoor unit : PL-3AK, PL-3AK-E
Outdoor unit : PU-6 type
After cutting the pipe with the pipe cutter,
deburr the pipe and clean off dirt and foreign
materials.
The following items must be obtain locally in
addition to the packed parts.
Combination of indoor/outdoor unit
Distributor pipe model
Outdoor unit
SDD-50S-E
Indoor unit
PU-6JSA
a Heat insulating sealing tape.
b Extension pipe for refrigerant pipe.
11-2 Pipe size and refrigerant pipe limits.
Outdoor unit
Gas side
Outdoor unit side Indoor unit side Outdoor unit side Indoor unit side
PU(H)-4S~6S Type
{19.05<3/4> {15.88<5/8> {9.52<3/8>{9.52<3/8> A+B=
Note1. The number of bendsin the refrigerant pipe is respectively 8 or less in the range of <A+B> <A+C>
Pipe size (mm)Actual piping leng <m>
Liquid side
Indoor ~
Outdoor
A+C=
30m or less
Indoor ~
Indoor
|B+|C=
80m or less
Indoor ~
Outdoor
H=20m
3 + 3
Height deffence <m>
Indoor ~
Indoor
h=1m
or less
or less less than 8
(Note 1)
No. of bend
80
Page 81
11-3 Pipe connection
Control cablePrepared by site
0.8mm or more
Enclosed with
opeional distribu-
tor pipe. (12m)
DC12V
Not designated
0.3mm
2
or more
Enclosed with
the indoor unit.
Control circuit voltage
Cable thickness
Polarity
A6C
(1) Note the following during work:
• Be sure to recheck the combination <Table1> and pipe size
<Table2> of the outdoor/indoor units.
• Observe the refrigerant pipe length limits and no of bend limits
<Table2>.
• Insert the refrigerant pipe (obtain locally) into the flared end of the
distributior pipe (packed) until the former pipe stops.
Use oxidization-free solder for connection when possible.
• The installation of the distributor pipe (packed) is not regulated.
• Take care to prevent dirt, foreign materials, etc., from entering the
pipe when connecting the pipe.
• After checking remove the tag from the liquid pipe 3.
(2) Piping connection
• When welding the piping, use the exclusive joint 7 as the diameters of the pipe on the outdoor unit side and the joint section differ.
(Refer to the table on the right.)
11-4 Heat insulating work
Gas pipeLiquid pipe
Do not bend or expend any distributor pipe
(Liquid pipe)
Gas side
•Outdoor unit PU-6JSA
Joint pipe B
ID {19.05
Liquid side
•Outdoor unit PU-6JSA
ID {9.52
Joint pipe C
• Install the gas pipe 2 while aligning it with the pipe cover
4. Seal the joint area of the pipe cover 4 with heat insulating sealing tape (obtain locally).
Note:
1. Cover the entire refrigerant pipe (obtain locally) with heat insulating material If connercial heat insulating meterial is used,
it must be 12mm or thicker.
2. As the pipe covers 4 and 5 will shrink slightly due to the high temperature, allow a lap when installing the heat insulating material.
11-5 Control wiring for indoor unit
• Connect the control cables of the indoor units Nos. 1 and 2 with the enclosed 2-core cable (12m) 6.
• Connect the 2-core cable 6 to the remote controller terminal in the electrical box of each indoor unit and tighten the screws.
(The polarity is not designated.)
Specifications of each control cable
A
Indoor unit No.1
Terminal
Terminal block
block for
control
121212
12
Terminal
block for
control
for remote
controller
Outdoor unit
Indoor unit No.2
Terminal block
for remote
controller
6
Remote
controller
c
81
• Install the liquid pipe 3 while aligning it with the pipe cover
5. Seal the joint area of the pipe cover 5 with heat insulating sealing tape (obtain locally).
Twin Setting
1 Set DIP switch SW6.
2 Remove the short-circuit connector CN40. (Leave it con-
nected to the No.1 unit.)
No.1 unit
SW6 Twin type
CN40 connectorLeave it connected.Remove.
OFF
ON
4
3214
No.2 unit
OFF
ON
321
Note 1: SW6 default settings are all OFF.
Note 2: The short-circuit connector CN40 is connected by
factory.
Page 82
HEAD OFFICE MITSUBISHI DENKI BLDG.MARUNOUCHI TOKYO100-8310 TELEX J24532 CABLE MELCO TOKYO