Mitsubishi PL-3AAK, PL-4AAK, PL-5AAK, PL-6AAK Service Manual

SPLIT-TYPE, AIR CONDITIONERS
ON/OFF TEMP
ON/OFF
TEMP.
TECHNICAL & SERVICE MANUAL
March 2006
No. OC378
Indoor unit [Model names] [Service Ref.]
PL-3AAK
PL-4AAK
PL-5AAK
PL-6AAK
PL-3AAK PL-4AAK PL-5AAK PL-6AAK
NOTE:
• This manual does not cover outdoor units. When servicing outdoor units, please refer to the service manual No.OC152,
OC206 and OC353 together with this manual.
CONTENTS
1. PART NAMES AND FUNCTIONS ···················2
2. SPECIFICATIONS············································5
3. DATA ································································9
4. OUTLINES AND DIMENSIONS·····················21
5. WIRING DIAGRAM ········································24
6. REFRIGERANT SYSTEM DIAGRAM············25
7. TROUBLESHOOTING ···································27
8. FUNCTION SETTING·····································42
Model name indication
WIRELESS REMOTE
CONTROLLER
INDOOR UNIT
WIRED REMOTE
CONTROLLER
9. 4-WAY AIR FLOW SYSTEM ··························49
10. SYSTEM CONTROL ·····································55
11. DISASSEMBLY PROCEDURE·······················69
12. PARTS LIST···················································72
13. OPTIONAL PARTS ········································75
PAR-21MAA
ON/OFF
FILTER
CHECK
OPERATION
CLEAR
TEST
TEMP.
MENU
BACK DAY
MONITOR/SET
CLOCK
ON/OFF
Set Temperature buttons
Down
Up
Timer Menu button (Monitor/Set button)
Mode button (Return button)
Set Time buttons
Back
Ahead
Timer On/Off button (Set Day button)
Opening the door.
ON/OFF button
Fan Speed button
Filter button (<Enter> button)
Test Run button
Check button (Clear button)
Airflow Up/Down button
Louver button ( Operation button)
To preceding operation number.
Ventilation button (
Operation button)
To next operation number.
Auto Air Swing Vane Disperses airflow up and down and adjusts the angle of airflow direction.
Grille
Filter Removes dust and pollutants from intake air
Horizontal Air Outlet Sets airflow of horizontal automatically during cooling or dehumidifying.
Air Intake Intakes air from room.
1
PART NAMES AND FUNCTIONS
Indoor Unit
Wired remote controller
On the controls are set, the same operation mode can be repeated by simply pressing the ON/OFF button.
Operation buttons
2
Display
For purposes of this explanation, all parts of the display are shown as lit. During actual operation, only the relevant items will be lit.
˚F˚C
˚F˚C
ERROR CODE
AFTER
TIMER
TIME SUN MON TUE WED THU FRI SAT
ON OFF
Hr AFTER
FILTER
FUNCTION
ONLY1Hr.
WEEKLY
SIMPLE
AUTO OFF
Identifies the current operation
Shows the operating mode, etc. * Multilanguage display is sup-
ported.
“Centrally Controlled” indicator
Indicates that operation of the re­mote controller has been prohib­ited by a master controller.
“Timer Is Off” indicator
Indicates that the timer is off.
Temperature Setting
Shows the target temperature.
Day-of-Week
Shows the current day of the week.
Time/Timer Display
Shows the current time, unless the simple or Auto Off timer is set. If the simple or Auto Off timer is set, shows the time remaining.
“Sensor” indication
Displayed when the remote controller sensor is used.
“Locked” indicator
Indicates that remote controller but­tons have been locked.
“Clean The Filter” indicator
Comes on when it is time to clean the filter.
Timer indicators
The indicator comes on if the corre­sponding timer is set.
Up/Down Air Direction indica­tor
The indicator shows the direc­tion of the outcoming airflow.
“One Hour Only” indicator
Displayed if the airflow is set to weak and downward during COOL or DRY mode. (Operation varies according to model.) The indicator goes off after one hour, at which time the airflow di­rection also changes.
Room Temperature display
Shows the room temperature.
Louver display
Indicates the action of the swing louver. Does not appear if the louver is stationary.
(Power On indicator)
Indicates that the power is on.
Fan Speed indicator
Shows the selected fan speed.
Ventilation indicator
Appears when the unit is running in Ventilation mode.
Caution
Only the Power on indicator lights when the unit is stopped and power supplied to the unit.
If you press a button for a feature that is not installed at the indoor unit, the remote controller will display the “Not Available”
message. If you are using the remote controller to drive multiple indoor units, this message will appear only if he feature is not present at the parent unit.
When power is turned ON for the first time, it is normal that “PLEASE WAIT” is displayed on the room temperature indica­tion (For max. 2minutes). Please wait until this “PLEASE WAIT” indication disappear then start the operation.
3
ON/OFF TEMP
FAN
VANE
TEST RUN
AUTO STOP
AUTO START
h
min
LOUVER
MODE
CHECK
RESETSET CLOCK
MODEL SELECT
NOT AVAILABLE
CHECK
TEST RUN
˚C
AMPM
AMPM
VANE CONTROL button
Used to change the air flow direction.
CLOCK button
RESET button
SET button
ON/OFF button
The unit is turned ON and OFF alternately each time the button is pressed.
LOUVER button
This switch the horizontal fan motion ON and OFF.
(Not available for this model.)
MODE SELECT button
Used to switch the operation mode between cooling, drying, blowing, heating and auto mode.
CHECK-TEST RUN button
Only press this button to perform an inspec­tion check or test operation. Do not use it for normal operation.
FAN SPEED SELECT button
Used to change the fan speed.
TIMER display
Displays when in timer operation or when setting timer.
button
SET TEMPERATURE button sets any desired room temperature.
CLOCK display
Displays the current time.
“ ” “ ” display
Displays the order of timer operation.
“ ” “ ” display
Displays whether timer is on or off.
w In case the outdoor unit is cool only type,
the heating mode is not available.
Buttons used to set the “hour and minute” of the current time and timer settings.
h and min buttons
display
SET TEMP. display indicates desired temper­ature set.
display
FAN SPEED display indicates which fan speed has been selected.
display
The vertical direction of air flow is indicated.
display
Blinks when model is selected.
display
Lights up while transmission to the indoor unit is mode using switches.
display
CHECK&TEST RUN display indicates that the unit is being checked or test-run.
display
OPERATION MODE display Operation mode display indicates which op­eration mode is in effect.
TIMER CONTROL buttons
AUTO STOP (OFF timer): when this switch is set, the air conditioner will be au­tomatically stopped at the preset time. AUTO START (ON timer): when this switch is set, the air conditioner will be automatical­ly started at the preset time.
MODEL SELECT
CHECK
TEST RUN
Wireless remote controller
4
2
PL-3AAK
UNIT : 840(33-1/6) UNIT : 840(33-1/6) UNIT : 258(10-1/8)
UNIT : 24(53)
PANEL : 950(37-3/8) PANEL : 950(37-3/8)
PANEL : 30(1-3/16)
PANEL : 5(11)
27,000
7,900
3.33
PL-3AAK
Single, 50Hz, 220-240V
0.15
0.78
1.00
Grille : Munsell 0.70Y 8.59/0.97
Plate fin coil
Turbo fan (direct) x 1
0.07
15-20(530-705)
0(direct blow)
Remote controller & built-in
28-34
32(1-1/4)
PU-3VJC
1.TH / PU-3YJC.TH
Munsell 3.0Y 7.8/1.1
Capillary tube
2.2 / 2.4 w1
32
0.085
50(1765)
52
870(34-1/4)
295+24 (11-5/8 add 1)
850(33-1/4)
73(161)
W
D H
W
D H
INDOOR UNITOUTDOOR UNIT
Item
Service Ref.
Btu/h
W
kW
kW
A A
kW
K/ min (CFM)
Pa
dB mm(in.) mm(in.) mm(in.) mm(in.)
kg(lbs)
kW
W
kW
K/ min (CFM)
dB mm(in.) mm(in.) mm(in.)
kg(lbs)
Capacity Total input
Service Ref.
Power supply(phase, cycle,voltage)
External finish Heat exchanger Fan
Operation control & Thermostat Noise level(Low-High) Unit drain pipe O.D.
Dimensions
Weight
Service Ref.
External finish Refrigerant control Compressor output Protection devices Crankcase heater Fan
Noise level
Dimensions
Weight
Input Running current Starting current
Fan(drive) x No. Fan motor output Airflow(Low-High) External static pressure
Fan motor output Airflow
SPECIFICATIONS
w1 V …Internal thermostat, HP switch, LP switch
Y…Anti-phase protector, Thermal relay, Thermal switch, HP switch, LP switch
Notes: Rating condition (ISO.T1<JIS B8616>)
Cooling: Indoor : D.B. 27°C, W.B. 19°C Refrigerant piping length(one way):5m(16ft)
Outdoor : D.B. 35°C, W.B. 24°C
5
33,800
9,900
3.59 / 3.53(V / Y)
PL-4AAK
Single, 50Hz, 220-240V
0.24
1.25
2.0
Grille : Munsell 0.70Y 8.59/0.97
Plate fin coil
Turbo fan (direct) x 1
0.12
20-28(705-990)
0(direct blow)
Remote controller & built-in
33-41
32(1-1/4)
PU-4VLJSA
2.TH / PU-4YJSA1.TH
Munsell 3.0Y 7.8/1.1
Capillary tube
2.7 w1 32
0.065+0.065 95(3353)
54
870(34-1/4)
295+24 (11-5/8 add 1)
1258(49-1/2)
94(207)
PL-4AAK
W
D H
W
D H
INDOOR UNITOUTDOOR UNIT
Item
Service Ref.
Btu/h
W
kW
kW
A A
kW
K/ min (CFM)
Pa
dB mm(in.) mm(in.) mm(in.) mm(in.)
kg(lbs)
kW
W
kW
K/ min (CFM)
dB mm(in.) mm(in.) mm(in.)
kg(lbs)
Capacity Total input
Service Ref.
Power supply(phase, cycle,voltage)
External finish Heat exchanger Fan
Operation control & Thermostat Noise level(Low-High) Unit drain pipe O.D.
Dimensions
Weight
Service Ref.
External finish Refrigerant control Compressor output Protection devices Crankcase heater Fan
Noise level
Dimensions
Weight
Input Running current Starting current
Fan(drive) x No. Fan motor output Airflow(Low-High) External static pressure
Fan motor output Airflow
UNIT : 840(33-1/6) UNIT : 840(33-1/6) UNIT : 298(11-3/4)
UNIT : 30(66)
PANEL : 950(37-3/8) PANEL : 950(37-3/8)
PANEL : 30(1-3/16)
PANEL : 5(11)
w1 V …Internal thermostat, HP switch, LP switch
Y…Anti-phase protector, Thermal relay, Thermal switch, HP switch, LP switch
Notes: Rating condition (ISO.T1<JIS B8616>)
Cooling: Indoor : D.B. 27°C, W.B. 19°C
Outdoor : D.B. 35°C, W.B. 24°C
Refrigerant piping length(one way):5m(16ft)
6
Item
Capacity Total input
Service Ref.
Power supply(phase, cycle,voltage)
Input Running current
Starting current External finish Heat exchanger Fan
INDOOR UNITOUTDOOR UNIT
Operation control & Thermostat Noise level(Low-High) Unit drain pipe O.D.
Dimensions
Weight
Service Ref.
External finish Refrigerant control Compressor output Protection devices Crankcase heater Fan
Noise level
Dimensions
Weight
Notes: Rating condition (ISO.T1<JIS B8616>)
Fan(drive) x No.
Fan motor output
Airflow(Low-High)
External static pressure
Fan motor output
Airflow
Cooling: Indoor : D.B. 27°C, W.B. 19°C
Outdoor : D.B. 35°C, W.B. 24°C
Refrigerant piping length(one way):5m(16ft)
W
D H
W
D H
Service Ref.
Btu/h
W
kW
kW
A A
kW
K/ min (CFM)
Pa
dB mm(in.) mm(in.) mm(in.) mm(in.)
kg(lbs)
kW
W
kW
K/ min (CFM)
dB mm(in.) mm(in.) mm(in.)
kg(lbs)
PL-5AAK
42,300 12,400
4.84
PL-5AAK
Single, 50Hz, 220-240V
0.28
1.43
2.0
Grille : Munsell 0.70Y 8.59/0.97
Plate fin coil
Turbo fan (direct) x 1
0.12
22-30(775-1,060)
0(direct blow)
Remote controller & built-in
35-43
32(1-1/4) UNIT : 840(33-1/6) UNIT : 840(33-1/6) UNIT : 298(11-3/4)
UNIT : 30(66)
PU-5YJSA
Munsell 3.0Y 7.8/1.1
Capillary tube
3.5
Internal thermostat, Anti-phase protector, Thermal switch, HP switch
32
0.10 + 0.10 100(3530)
55
970(38-3/16)
345+24 (13-9/16 add 1)
1258(49-1/2)
114(251)
PANEL : 950(37-3/8) PANEL : 950(37-3/8)
PANEL : 30(1-3/16)
PANEL : 5(11)
1.TH
7
48,800 14,300
5.43
PL-6AAK
Single, 50Hz, 220-240V
0.32
1.64
2.0
Grille : Munsell 0.70Y 8.59/0.97
Plate fin coil
Turbo fan (direct) x 1
0.12
22-30(775-1,060)
0(direct blow)
Remote controller & built-in
37-45
32(1-1/4)
PU-6YJSA
1.TH
Munsell 3.0Y 7.8/1.1
Capillary tube
4.2
Internal thermostat, Anti-phase protector, Thermal switch, HP switch
32
0.10+0.10
100(3530)
56
970(38-3/16)
345+24 (13-9/16 add 1)
1258(49-1/2)
117(258)
PL-6AAK
W
D H
W
D H
INDOOR UNITOUTDOOR UNIT
Item
Service Ref.
Btu/h
W
kW
kW
A A
kW
K/ min (CFM)
Pa
dB mm(in.) mm(in.) mm(in.) mm(in.)
kg(lbs)
kW
W
kW
K/ min (CFM)
dB mm(in.) mm(in.) mm(in.)
kg(lbs)
Capacity Total input
Service Ref.
Power supply(phase, cycle,voltage)
External finish Heat exchanger Fan
Operation control & Thermostat Noise level(Low-High) Unit drain pipe O.D.
Dimensions
Weight
Service Ref.
External finish Refrigerant control Compressor output Protection devices Crankcase heater Fan
Noise level
Dimensions
Weight
Input Running current Starting current
Fan(drive) x No. Fan motor output Airflow(Low-High) External static pressure
Fan motor output Airflow
UNIT : 840(33-1/6) UNIT : 840(33-1/6) UNIT : 298(11-3/4)
UNIT : 32(71)
PANEL : 950(37-3/8) PANEL : 950(37-3/8)
PANEL : 30(1-3/16)
PANEL : 5(11)
Notes: Rating condition (ISO.T1<JIS B8616>)
Cooling: Indoor : D.B. 27°C, W.B. 19°C
Outdoor : D.B. 35°C, W.B. 24°C
Refrigerant piping length(one way):5m(16ft)
8
3
Outdoor intake air D.B.(°C)
20 25 30
Indoor
Intake air
D.B.(°C)
Indoor
Intake air
W.B.(°C)
20 20 22 22 22 24 24 24 24 26 26 26 26 27 27 27 27 28 28 28 28 30 30 30 30 32 32 32 32
16 18 16 18 20 16 18 20 22 16 18 20 22 16 18 20 22 16 18 20 22 16 18 20 22 16 18 20 22
7970 8486 7970 8486 9007 7970 8486 9007 9534 7970 8486 9007 9534 7970 8486 9007 9534 7970 8486 9007 9534 7970 8486 9007 9534 7970 8486 9007 9534
CA SHC SHF P.C. CA SHC SHF P.C. CA SHC SHF P.C.
5021 4328 5659 5007 4233 6296 5685 4954 4100 6934 6364 5675 4863 7253 6704 6035 5244 7571 7043 6395 5625 7970 7722 7116 6388 7970 8401 7836 7151
0.63
0.51
0.71
0.59
0.47
0.79
0.67
0.55
0.43
0.87
0.75
0.63
0.51
0.91
0.79
0.67
0.55
0.95
0.83
0.71
0.59
1.00
0.91
0.79
0.67
1.00
0.99
0.87
0.75
0.63
0.51
0.71
0.59
0.47
0.79
0.67
0.55
0.43
0.87
0.75
0.63
0.51
0.91
0.79
0.67
0.55
0.95
0.83
0.71
0.59
1.00
0.91
0.79
0.67
1.00
0.99
0.87
0.75
0.63
0.51
0.71
0.59
0.47
0.79
0.67
0.55
0.43
0.87
0.75
0.63
0.51
0.91
0.79
0.67
0.55
0.95
0.83
0.71
0.59
1.00
0.91
0.79
0.67
1.00
0.99
0.87
0.75
7752 8262 7752 8262 8796 7752 8262 8796 9352 7752 8262 8796 9352 7752 8262 8796 9352 7752 8262 8796 9352 7752 8262 8796 9352 7752 8262 8796 9352
4884 4214 5504 4875 4134 6124 5536 4838 4021 6744 6197 5541 4769 7054 6527 5893 5143 7364 6858 6245 5517 7752 7519 6949 6266 7752 8180 7652 7014
7467 7961 7467 7961 8482 7467 7961 8482 9028 7467 7961 8482 9028 7467 7961 8482 9028 7467 7961 8482 9028 7467 7961 8482 9028 7467 7961 8482 9028
4704 4060 5301 4697 3986 5899 5334 4665 3882 6496 5971 5343 4604 6795 6290 5683 4965 7093 6608 6022 5326 7467 7245 6701 6049 7467 7882 7379 6771
2.67
2.72
2.67
2.72
2.77
2.67
2.72
2.77
2.83
2.67
2.72
2.77
2.83
2.67
2.72
2.77
2.83
2.67
2.72
2.77
2.83
2.67
2.72
2.77
2.83
2.67
2.72
2.77
2.83
2.78
2.84
2.78
2.84
2.90
2.78
2.84
2.90
2.95
2.78
2.84
2.90
2.95
2.78
2.84
2.90
2.95
2.78
2.84
2.90
2.95
2.78
2.84
2.90
2.95
2.78
2.84
2.90
2.95
3.00
3.06
3.00
3.06
3.13
3.00
3.06
3.13
3.20
3.00
3.06
3.13
3.20
3.00
3.06
3.13
3.20
3.00
3.06
3.13
3.20
3.00
3.06
3.13
3.20
3.00
3.06
3.13
3.20
DATA
3-1. PERFORMANCE DATA [50Hz]
1) COOLING CAPACITY(1) PL-3AAK / PU-3VJC1.TH, PU-3YJC.TH
CA : Capacity (W) SHC : Sensible heat capacity (W) P.C. : Power consumption (kW) SHF : Sensible heat factor
9
COOLING CAPACITY(2)
Outdoor intake air D.B.(°C)
35 40 45
Indoor
Intake air
D.B.(°C)
Indoor
Intake air
W.B.(°C)
20 20 22 22 22 24 24 24 24 26 26 26 26 27 27 27 27 28 28 28 28 30 30 30 30 32 32 32 32
16 18 16 18 20 16 18 20 22 16 18 20 22 16 18 20 22 16 18 20 22 16 18 20 22 16 18 20 22
7164 7646 7164 7646 8154 7164 7646 8154 8690 7164 7646 8154 8690 7164 7646 8154 8690 7164 7646 8154 8690 7164 7646 8154 8690 7164 7646 8154 8690
CA SHC SHF P.C. CA SHC SHF P.C. CA SHC SHF P.C.
4514 3899 5087 4511 3833 5660 5123 4485 3737 6233 5734 5137 4432 6520 6040 5463 4780 6806 6346 5790 5127 7164 6958 6442 5823 7164 7569 7094 6518
0.63
0.51
0.71
0.59
0.47
0.79
0.67
0.55
0.43
0.87
0.75
0.63
0.51
0.91
0.79
0.67
0.55
0.95
0.83
0.71
0.59
1.00
0.91
0.79
0.67
1.00
0.99
0.87
0.75
0.63
0.51
0.71
0.59
0.47
0.79
0.67
0.55
0.43
0.87
0.75
0.63
0.51
0.91
0.79
0.67
0.55
0.95
0.83
0.71
0.59
1.00
0.91
0.79
0.67
1.00
0.99
0.87
0.75
0.63
0.51
0.71
0.59
0.47
0.79
0.67
0.55
0.43
0.87
0.75
0.63
0.51
0.91
0.79
0.67
0.55
0.95
0.83
0.71
0.59
1.00
0.91
0.79
0.67
1.00
0.99
0.87
0.75
6844 7315 6844 7315 7813 6844 7315 7813 8339 6844 7315 7813 8339 6844 7315 7813 8339 6844 7315 7813 8339 6844 7315 7813 8339 6844 7315 7813 8339
4312 3731 4859 4316 3672 5407 4901 4297 3586 5954 5486 4922 4253 6228 5779 5235 4587 6502 6071 5548 4920 6844 6657 6173 5587 6844 7242 6798 6255
6506 6970 6506 6970 7459 6506 6970 7459 7975 6506 6970 7459 7975 6506 6970 7459 7975 6506 6970 7459 7975 6506 6970 7459 7975 6506 6970 7459 7975
4099 3554 4619 4112 3506 5140 4670 4103 3429 5660 5227 4699 4067 5921 5506 4998 4386 6181 5785 5296 4705 6506 6342 5893 5343 6506 6900 6489 5981
3.21
3.43
3.65
3.29
3.52
3.74
3.21
3.43
3.65
3.29
3.52
3.74
3.37
3.61
3.85
3.21
3.43
3.65
3.29
3.52
3.74
3.37
3.61
3.85
3.45
3.71
3.98
3.21
3.43
3.65
3.29
3.52
3.74
3.37
3.61
3.85
3.45
3.71
3.98
3.21
3.43
3.65
3.29
3.52
3.74
3.37
3.61
3.85
3.45
3.71
3.98
3.21
3.43
3.65
3.29
3.52
3.74
3.37
3.61
3.85
3.45
3.71
3.98
3.21
3.43
3.65
3.29
3.52
3.74
3.37
3.61
3.85
3.45
3.71
3.98
3.21
3.43
3.65
3.29
3.52
3.74
3.37
3.61
3.85
3.45
3.71
3.98
PL-3AAK / PU-3VJC1.TH, 3YJC.TH
CA : Capacity (W) SHC : Sensible heat capacity (W) P.C. : Power consumption (kW) SHF : Sensible heat factor
10
COOLING CAPACITY(3)
Outdoor intake air D.B.(°C)
20 25 30
Indoor
Intake air
D.B.(°C)
Indoor
Intake air
W.B.(°C)
20 20 22 22 22 24 24 24 24 26 26 26 26 27 27 27 27 28 28 28 28 30 30 30 30 32 32 32 32
16 18 16 18 20 16 18 20 22 16 18 20 22 16 18 20 22 16 18 20 22 16 18 20 22 16 18 20 22
9988
10634
9988 10634 11288
9988 10634 11288 11948
9988 10634 11288 11948
9988 10634 11288 11948
9988 10634 11288 11948
9988 10634 11288 11948
9988 10634 11288 11948
CA SHC SHF P.C. CA SHC SHF P.C. CA SHC SHF P.C.
6792 5955 7591 6806 6870 8390 7657 6773 5735 9189 8507 7676 6691 9588 8933 8127 7169 9988 9358 8579 7647 9988
10209
9482 9603
9988 10634 10385
9559
0.68
0.56
0.76
0.64
0.52
0.84
0.72
0.60
0.48
0.92
0.80
0.68
0.56
0.96
0.84
0.72
0.60
1.00
0.88
0.76
0.64
1.00
0.96
0.84
0.72
1.00
1.00
0.92
0.80
0.68
0.56
0.76
0.64
0.52
0.84
0.72
0.60
0.48
0.92
0.80
0.68
0.56
0.96
0.84
0.72
0.60
1.00
0.88
0.76
0.64
1.00
0.96
0.84
0.72
1.00
1.00
0.92
0.80
0.68
0.56
0.76
0.64
0.52
0.84
0.72
0.60
0.48
0.92
0.80
0.68
0.56
0.96
0.84
0.72
0.60
1.00
0.88
0.76
0.64
1.00
0.96
0.84
0.72
1.00
1.00
0.92
0.80
2.90
2.96
2.90
2.96
3.02
2.90
2.96
3.02
3.07
2.90
2.96
3.02
3.07
2.90
2.96
3.02
3.07
2.90
2.96
3.02
3.07
2.90
2.96
3.02
3.07
2.90
2.96
3.02
3.07
9714
10354
9714 10354 11022
9714 10354 11022 11719
9714 10354 11022 11719
9714 10354 11022 11719
9714 10354 11022 11719
9714 10354 11022 11719
9714 10354 11022 11719
6606 5798 7383 6627 5732 8160 7455 6613 5625 8937 8283 7495 6563 9326 8697 7936 7031 9714 9112 8377 7500 9714 9940 9259 8438
9714 10354 10141
9375
3.03
3.09
3.03
3.09
3.15
3.03
3.09
3.15
3.21
3.03
3.09
3.15
3.21
3.03
3.09
3.15
3.21
3.03
3.09
3.15
3.21
3.03
3.09
3.15
3.21
3.03
3.09
3.15
3.21
9357 9977 9357 9977
10629
9357
9977 10629 11313
9357
9977 10629 11313
9357
9977 10629 11313
9357
9977 10629 11313
9357
9977 10629 11313
9357
9977 10629 11313
6363 5587 7111 6385 5527 7860 7183 6377 5430 8609 7982 7228 6335 8983 8381 7653 6788 9357 8780 8078 7240 9357 9578 8928 8146 9357 9977 9779 9051
3.26
3.33
3.26
3.33
3.40
3.26
3.33
3.40
3.48
3.26
3.33
3.40
3.48
3.26
3.33
3.40
3.48
3.26
3.33
3.40
3.48
3.26
3.33
3.40
3.48
3.26
3.33
3.40
3.48
PL-4AAK / PU-4VJSA2.TH, PU-4YJSA1.TH
CA : Capacity (W) SHC : Sensible heat capacity (W) P.C. : Power consumption (kW) SHF : Sensible heat factor
11
COOLING CAPACITY(4)
Outdoor intake air D.B.(°C)
35 40 45
Indoor
Intake air
D.B.(°C)
Indoor
Intake air
W.B.(°C)
20 20 22 22 22 24 24 24 24 26 26 26 26 27 27 27 27 28 28 28 28 30 30 30 30 32 32 32 32
16 18 16 18 20 16 18 20 22 16 18 20 22 16 18 20 22 16 18 20 22 16 18 20 22 16 18 20 22
CA SHC SHF P.C. CA SHC SHF P.C. CA SHC SHF P.C.
6105 5366 6823 6132 5314 7542 6899 6131 5227 8260 7665 6949 6099 8619 8048 7357 6534 8978 8432 7766 6970 8978 9198 8584 7841 8978 9581 9401 8712
0.68
0.56
0.76
0.64
0.52
0.84
0.72
0.60
0.48
0.92
0.80
0.68
0.56
0.96
0.84
0.72
0.60
1.00
0.88
0.76
0.64
1.00
0.96
0.84
0.72
1.00
1.00
0.92
0.80
0.68
0.56
0.76
0.64
0.52
0.84
0.72
0.60
0.48
0.92
0.80
0.68
0.56
0.96
0.84
0.72
0.60
1.00
0.88
0.76
0.64
1.00
0.96
0.84
0.72
1.00
1.00
0.92
0.80
0.68
0.56
0.76
0.64
0.52
0.84
0.72
0.60
0.48
0.92
0.80
0.68
0.56
0.96
0.84
0.72
0.60
1.00
0.88
0.76
0.64
1.00
0.96
0.84
0.72
1.00
1.00
0.92
0.80
3.49
3.58
3.49
3.58
3.66
3.49
3.58
3.66
3.75
3.49
3.58
3.66
3.75
3.49
3.58
3.66
3.75
3.49
3.58
3.66
3.75
3.49
3.58
3.66
3.75
3.49
3.58
3.66
3.75
8577 9167 8577 9167 9792 8577 9167 9792
10451
8577 9167 9792
10451
8577 9167 9792
10451
8577 9167 9792
10451
8577 9167 9792
10451
8577 9167 9792
10451
8978 9581 8978 9581
10219
8978
9581 10219 10890
8978
9581 10219 10890
8978
9581 10219 10890
8978
9581 10219 10890
8978
9581 10219 10890
8978
9581 10219 10890
5832 5133 6518 5867 5092 7205 6600 5875 5016 7891 7334 6658 5852 8234 7700 7050 6270 8577 8067 7442 6688 8577 8800 8225 7525 8577 9167 9008 8361
3.73
3.82
3.73
3.82
3.92
3.73
3.82
3.92
4.04
3.73
3.82
3.92
4.04
3.73
3.82
3.92
4.04
3.73
3.82
3.92
4.04
3.73
3.82
3.92
4.04
3.73
3.82
3.92
4.04
8153 8734 8153 8734 9348 8153 8734 9348 9994 8153 8734 9348 9994 8153 8734 9348 9994 8153 8734 9348 9994 8153 8734 9348 9994 8153 8734 9348 9994
5544 4891 6197 5590 4861 6849 6288 5609 4797 7501 6987 6356 5597 7827 7337 6730 5997 8153 7686 7104 6396 8153 8385 7852 7196 8153 8734 8600 7995
3.96
4.07
3.96
4.07
4.19
3.96
4.07
4.19
4.33
3.96
4.07
4.19
4.33
3.96
4.07
4.19
4.33
3.96
4.07
4.19
4.33
3.96
4.07
4.19
4.33
3.96
4.07
4.19
4.33
PL-4AAK / PU-4LVJSA2.TH, PU-4YJSA1.TH
CA : Capacity (W) SHC : Sensible heat capacity (W)
P.C. : Power consumption (kW) SHF : Sensible heat factor
12
COOLING CAPACITY(5)
Outdoor intake air D.B.(°C)
20 25 30
Indoor
Intake air
D.B.(°C)
Indoor
Intake air
W.B.(°C)
20 20 22 22 22 24 24 24 24 26 26 26 26 27 27 27 27 28 28 28 28 30 30 30 30 32 32 32 32
16 18 16 18 20 16 18 20 22 16 18 20 22 16 18 20 22 16 18 20 22 16 18 20 22 16 18 20 22
12510 13319 12510 13319 14138 12510 13319 14138 14965 12510 13319 14138 14965 12510 13319 14138 14965 12510 13319 14138 14965 12510 13319 14138 14965 12510 13319 14138 14965
CA SHC SHF P.C. CA SHC SHF P.C. CA SHC SHF P.C.
7881 6793 8882 7858 6645 9883 8924 7776 6435
10883
9990 8907
7632 11384 10522
9472
8231 11884 11055 10038
8830 12510 12121 11169 10027 12510 13186 12300 11224
0.63
0.51
0.71
0.59
0.47
0.79
0.67
0.55
0.43
0.87
0.75
0.63
0.51
0.91
0.79
0.67
0.55
0.95
0.83
0.71
0.59
1.00
0.91
0.79
0.67
1.00
0.99
0.87
0.75
0.63
0.51
0.71
0.59
0.47
0.79
0.67
0.55
0.43
0.87
0.75
0.63
0.51
0.91
0.79
0.67
0.55
0.95
0.83
0.71
0.59
1.00
0.91
0.79
0.67
1.00
0.99
0.87
0.75
0.63
0.51
0.71
0.59
0.47
0.79
0.67
0.55
0.43
0.87
0.75
0.63
0.51
0.91
0.79
0.67
0.55
0.95
0.83
0.71
0.59
1.00
0.91
0.79
0.67
1.00
0.99
0.87
0.75
3.98
4.06
3.98
4.06
4.13
3.98
4.06
4.13
4.21
3.98
4.06
4.13
4.21
3.98
4.06
4.13
4.21
3.98
4.06
4.13
4.21
3.98
4.06
4.13
4.21
3.98
4.06
4.13
4.21
12167 12969 12167 12969 13806 12167 12969 13806 14679 12167 12969 13806 14679 12167 12969 13806 14679 12167 12969 13806 14679 12167 12969 13806 14679 12167 12969 13806 14679
7665 6614 8639 7652 6489 9612 8689 7593 6312
10585
9727 8698
7486 11072 10245
9250
8073 11559 10764
9802
8660 12167 11802 10907
9835 12167 12839 12011 11009
4.15
4.23
4.15
4.23
4.31
4.15
4.23
4.31
4.40
4.15
4.23
4.31
4.40
4.15
4.23
4.31
4.40
4.15
4.23
4.31
4.40
4.15
4.23
4.31
4.40
4.15
4.23
4.31
4.40
11720 12496 11720 12496 13313 11720 12496 13313 14170 11720 12496 13313 14170 11720 12496 13313 14170 11720 12496 13313 14170 11720 12496 13313 14170 11720 12496 13313 14170
7384 6373 8321 7373 6257 9259 8373 7322 6093
10196
9372 8387 7227
10665
9872 8920
7794 11134 10372
9452
8360 11720 11372 10517
9494 11720 12371 11582 10628
446 456 446 456 466 446 456 466 476 446 456 466 476 446 456 466 476 446 456 466 476 446 456 466 476 446 456 466 476
PL-5AAK / PU-5YJSA1.TH
CA : Capacity (W) SHC : Sensible heat capacity (W) P.C. : Power consumption (kW) SHF : Sensible heat factor
13
COOLING CAPACITY(6)
Outdoor intake air D.B.(°C)
35 40 45
Indoor
Intake air
D.B.(°C)
Indoor Intake air W.B.(°C)
20 20 22 22 22 24 24 24 24 26 26 26 26 27 27 27 27 28 28 28 28 30 30 30 30 32 32 32 32
16 18 16 18 20 16 18 20 22 16 18 20 22 16 18 20 22 16 18 20 22 16 18 20 22 16 18 20 22
11245 12001 11245 12001 12799 11245 12001 12799 13640 11245 12001 12799 13640 11245 12001 12799 13640 11245 12001 12799 13640 11245 12001 12799 13640 11245 12001 12799 13640
CA SHC SHF P.C. CA SHC SHF P.C. CA SHC SHF P.C.
7085 6120 7984 7080 6016 8884 8041 7040 5865 9783 9001 8064 6957
10233
9481 8575 7502
10683
9961 9087
8048 11245 10921 10111
9139 11245 11881 11135 10230
0.63
0.51
0.71
0.59
0.47
0.79
0.67
0.55
0.43
0.87
0.75
0.63
0.51
0.91
0.79
0.67
0.55
0.95
0.83
0.71
0.59
1.00
0.91
0.79
0.67
1.00
0.99
0.87
0.75
0.63
0.51
0.71
0.59
0.47
0.79
0.67
0.55
0.43
0.87
0.75
0.63
0.51
0.91
0.79
0.67
0.55
0.95
0.83
0.71
0.59
1.00
0.91
0.79
0.67
1.00
0.99
0.87
0.75
0.63
0.51
0.71
0.59
0.47
0.79
0.67
0.55
0.43
0.87
0.75
0.63
0.51
0.91
0.79
0.67
0.55
0.95
0.83
0.71
0.59
1.00
0.91
0.79
0.67
1.00
0.99
0.87
0.75
4.78
4.90
4.78
4.90
5.02
4.78
4.90
5.02
5.14
4.78
4.90
5.02
5.14
4.78
4.90
5.02
5.14
4.78
4.90
5.02
5.14
4.78
4.90
5.02
5.14
4.78
4.90
5.02
5.14
10743 11482 10743 11482 12264 10743 11482 12264 13090 10743 11482 12264 13090 10743 11482 12264 13090 10743 11482 12264 13090 10743 11482 12264 13090 10743 11482 12264 13090
6768 5856 7627 6774 5764 8487 7693 6745 5629 9346 8611 7726 6676 9776 9071 8217 7199
10206
9530 8708
7723 10743 10448
9689
8770 10743 11367 10670
9817
5.11
5.24
5.11
5.24
5.38
5.11
5.24
5.38
5.53
5.11
5.24
5.38
5.53
5.11
5.24
5.38
5.53
5.11
5.24
5.38
5.53
5.11
5.24
5.38
5.53
5.11
5.24
5.38
5.53
10212 10939 10212 10939 11708 10212 10939 11708 12518 10212 10939 11708 12518 10212 10939 11708 12518 10212 10939 11708 12518 10212 10939 11708 12518 10212 10939 11708 12518
6434 5579 7251 6454 5503 8068 7329 6439 5383 8885 8205 7376 6384 9293 8642 7844 6885 9702 9080 8313 7386
10212
9955 9249
8387 10212 10830 10186
9389
5.43
5.57
5.43
5.57
5.74
5.43
5.57
5.74
5.93
5.43
5.57
5.74
5.93
5.43
5.57
5.74
5.93
5.43
5.57
5.74
5.93
5.43
5.57
5.74
5.93
5.43
5.57
5.74
5.93
PL-5AAK / PU-5YJSA1.TH
CA : Capacity (W) SHC : Sensible heat capacity (W)
P.C. : Power consumption (kW) SHF : Sensible heat factor
14
COOLING CAPACITY(7)
Outdoor intake air D.B.(°C)
20 25 30
Indoor
Intake air
D.B.(°C)
Indoor
Intake air
W.B.(°C)
20 20 22 22 22 24 24 24 24 26 26 26 26 27 27 27 27 28 28 28 28 30 30 30 30 32 32 32 32
16 18 16 18 20 16 18 20 22 16 18 20 22 16 18 20 22 16 18 20 22 16 18 20 22 16 18 20 22
14426 15360 14426 15360 16304 14426 15360 16304 17258 14426 15360 16304 17258 14426 15360 16304 17258 14426 15360 16304 17258 14426 15360 16304 17258 14426 15360 16304 17258
CA SHC SHF P.C. CA SHC SHF P.C. CA SHC SHF P.C.
8656 7373 9810 8602 7174
10964
9831 8478
6903 12118 11059
9783
8284 12695 11674 10435
8974 13272 12288 11087
9665 14426 13517 12391 11045 14426 14746 13696 12426
0.60
0.48
0.68
0.56
0.44
0.76
0.64
0.52
0.40
0.84
0.72
0.60
0.48
0.88
0.76
0.64
0.52
0.92
0.80
0.68
0.56
1.00
0.88
0.76
0.64
1.00
0.96
0.84
0.72
0.60
0.48
0.68
0.56
0.44
0.76
0.64
0.52
0.40
0.84
0.72
0.60
0.48
0.88
0.76
0.64
0.52
0.92
0.80
0.68
0.56
1.00
0.88
0.76
0.64
1.00
0.96
0.84
0.72
0.60
0.48
0.68
0.56
0.44
0.76
0.64
0.52
0.40
0.84
0.72
0.60
0.48
0.88
0.76
0.64
0.52
0.92
0.80
0.68
0.56
1.00
0.88
0.76
0.64
1.00
0.96
0.84
0.72
4.42
4.51
4.42
4.51
4.60
4.42
4.51
4.60
4.68
4.42
4.51
4.60
4.68
4.42
4.51
4.60
4.68
4.42
4.51
4.60
4.68
4.42
4.51
4.60
4.68
4.42
4.51
4.60
4.68
14031 14956 14031 14956 15921 14031 14956 15921 16928 14031 14956 15921 16928 14031 14956 15921 16928 14031 14956 15921 16928 14031 14956 15921 16928 14031 14956 15921 16928
8419 7179 9541 8375 7005
10664
9572 8279
6771 11786 10768
9553
8125 12348 11366 10190
8802 12909 11965 10826
9479 14031 13161 12100 10834 14031 14358 13374 12188
4.61
4.71
4.61
4.71
4.80
4.61
4.71
4.80
4.90
4.61
4.71
4.80
4.90
4.61
4.71
4.80
4.90
4.61
4.71
4.80
4.90
4.61
4.71
4.80
4.90
4.61
4.71
4.80
4.90
13516 14411 13516 14411 15353 13516 14411 15353 16341 13516 14411 15353 16341 13516 14411 15353 16341 13516 14411 15353 16341 13516 14411 15353 16341 13516 14411 15353 16341
8110 6917 9191 8070 6755
10272
9223 7984
6537 11353 10376
9212
7844 11894 10953
9826
8497 12435 11529 10440
9151 13516 12682 11668 10458 13516 13835 12897 11766
4.97
5.08
4.97
5.08
5.19
4.97
5.08
5.19
5.30
4.97
5.08
5.19
5.30
4.97
5.08
5.19
5.30
4.97
5.08
5.19
5.30
4.97
5.08
5.19
5.30
4.97
5.08
5.19
5.30
PL-6AAK / PU-6YJSA1.TH
CA : Capacity (W) SHC : Sensible heat capacity (W) P.C. : Power consumption (kW) SHF : Sensible heat factor
15
COOLING CAPACITY(8)
Outdoor intake air D.B.(°C)
35 40 45
Indoor
Intake air
D.B.(°C)
Indoor
Intake air
W.B.(°C)
20 20 22 22 22 24 24 24 24 26 26 26 26 27 27 27 27 28 28 28 28 30 30 30 30 32 32 32 32
16 18 16 18 20 16 18 20 22 16 18 20 22 16 18 20 22 16 18 20 22 16 18 20 22 16 18 20 22
12968 13840 12968 12840 14760 12968 13840 14760 15731 12968 13840 14760 15731 12968 13840 14760 15731 12968 13840 14760 15731 12968 13840 14760 15731 12968 13840 14760 15731
CA SHC SHF P.C. CA SHC SHF P.C. CA SHC SHF P.C.
7781 6643 8818 7750 6495 9856 8857 7675 6292
10893
9965 8856
7551 11412 10518
9447
8180 11931 11072 10037
8809 12968 12179 11218 10068 12968 13286 12399 11326
0.60
0.48
0.68
0.56
0.44
0.76
0.64
0.52
0.40
0.84
0.72
0.60
0.48
0.88
0.76
0.64
0.52
0.92
0.80
0.68
0.56
1.00
0.88
0.76
0.64
1.00
0.96
0.84
0.72
0.60
0.48
0.68
0.56
0.44
0.76
0.64
0.52
0.40
0.84
0.72
0.60
0.48
0.88
0.76
0.64
0.52
0.92
0.80
0.68
0.56
1.00
0.88
0.76
0.64
1.00
0.96
0.84
0.72
0.60
0.48
0.68
0.56
0.44
0.76
0.64
0.52
0.40
0.84
0.72
0.60
0.48
0.88
0.76
0.64
0.52
0.92
0.80
0.68
0.56
1.00
0.88
0.76
0.64
1.00
0.96
0.84
0.72
5.32
5.45
5.32
5.45
5.59
5.32
5.45
5.59
5.72
5.32
5.45
5.59
5.72
5.32
5.45
5.59
5.72
5.32
5.45
5.59
5.72
5.32
5.45
5.59
5.72
5.32
5.45
5.59
5.72
12389 13241 12389 13241 14143 12389 13241 14143 15096 12389 13241 14143 15096 12389 13241 14143 15096 12389 13241 14143 15096 12389 13241 14143 15096 12389 13241 14143 15096
7433 6356 8424 7415 6223 9415 8474 7355 6038
10407
9534 8486
7246 10902 10063
9052
7850 11398 10593
9618
8453 12389 11652 10749
9661 12389 12711 11880 10869
5.68
5.83
5.68
5.83
5.98
5.68
5.83
5.98
6.15
5.68
5.83
5.98
6.15
5.68
5.83
5.98
6.15
5.68
5.83
5.98
6.15
5.68
5.83
5.98
6.15
5.68
5.83
5.98
6.15
11777 12616 11777 12616 13502 11777 12616 13502 14436 11777 12616 13502 14436 11777 12616 13502 14436 11777 12616 13502 14436 11777 12616 13502 14436 11777 12616 13502 14436
7066 6056 8008 7065 5941 8951 8074 7021 5774 9893 9083 8101 6929
10364
9588 8641
7507 10835 10093
9181
8084 11777 11102 10262
9239 11777 12111 11342 10394
6.04
6.20
6.04
6.20
6.39
6.04
6.20
6.39
6.60
6.04
6.20
6.39
6.60
6.04
6.20
6.39
6.60
6.04
6.20
6.39
6.60
6.04
6.20
6.39
6.60
6.04
6.20
6.39
6.60
PL-6AAK / PU-6YJSA1.TH
CA : Capacity (W) SHC : Sensible heat capacity (W) P.C. : Power consumption (kW) SHF : Sensible heat factor
16
3-2.COOLING CAPACITY CORRECTION FACTORS
Refrigerant piping length(one way)
5m
1.0
1.0
1.0
1.0
10m
0.978
0.984
0.978
0.970
15m
0.962
0.974
0.962
0.950
20m
0.948
0.964
0.948
0.931
25m
0.934
0.954
0.934
0.912
30m
0.921
0.944
0.921
0.896
35m
0.935
0.908
0.880
40m
0.926
0.896
0.864
45m
— —
0.884
0.850
50m
— —
0.875
0.840
Service Ref.
PL-3AAK PL-4AAK PL-5AAK PL-6AAK
1.4
1.2
1.0
0.8
0.6
1.4
1.2
1.0
0.8
0.6
0.4 21 25 35 45 52
OUTDOOR D.B.(°C)
TOTAL INPUT (RATIO) CAPACITY (RATIO)
INDOOR W.B.(°C)
INDOOR W.B.(°C)
22 20 18 16
22 20 18 16
3-3. PERFORMANCE CURVE
PL-3AAK PL-4AAK PL-5AAK PL-6AAK
Cooling
17
3-4. ELECTRICAL SPECIFICATIONS
Power supply (1 Phase) V : 220V 50Hz
Service Ref.
Outdoor unit
Current Input Starting current
A
kW
A
0.15
0.78
1.0
PU-3
V : 230V 50Hz
PL-3AAK
0.24
1.25
2.0
PU-4
PL-4AAK
0.28
1.43
2.0
PU-5
PL-5AAK
0.32
1.64
2.0
PU-6
PL-6AAK
0.16
0.79
1.0
PU-3
PL-3AAK
0.25
1.25
2.0
PU-4
PL-4AAK
0.29
1.43
2.0
PU-5
PL-5AAK
0.33
1.64
2.0
PU-6
PL-6AAK
Power supply (1 Phase) V : 240V 50Hz
Service Ref.
Current Input Starting current Outdoor unit
A
kW
A
0.17
0.81
1.0
PU-3
PL-3AAK
0.26
1.25
2.0
PU-4
PL-4AAK
0.30
1.43
2.0
PU-5
PL-5AAK
0.34
1.64
2.0
PU-6
PL-6AAK
Indoor
unit
{
Capacity Input
Indoor unit Service Ref.
Phase, Hz Volts Amperes
Outdoor unit Service Ref.
Phase,Hz Volts Amperes
Discharge pressure Suction pressure
Discharge temperature
Condensing temperature
Suction temperature Ref. pipe length
Intake air temperature
Discharge air temperature
Intake air temperature
SHF
BF
Total
W
kW
V A
V A
MPa
(kgf/F)
MPa
(kgf/F)
°C °C °C
m
°C °C °C °C °C
PL-3AAK
PL-4AAK PL-5AAK PL-6AAK
Service Ref.
7,900
3.33
PL-3AAK
1, 50
220
0.78
PU-3VJA1.TH
/ PU-3YJA.TH
1 / 3, 50
220 / 380
15.1 / 5.7
2.06
(21.0)
0.45
(4.6)
82 55
3.0 5
27 19
13.0 35 24
0.73
0.12
9,900
3.59/3.53
PL-4AAK
1, 50
220
1.25
PU-4VLJSA2 .TH
/ PU-4YJSA1.TH
1 / 3, 50
220 / 380
16.9 / 5.7
1.84
(18.8)
0.52 (5.3)
67 49
8.1 5
27 19
13.6 35 24
0.78
0.09
12,400
4.84
PL-5AAK
1, 50
220
1.43
PU-5YJSA
1.TH
3, 50
380
8.15
1.85
(18.9)
0.46
(4.78)
73 49
5.1 5
27 19
12.5 35 24
0.73
0.10
14,300
5.43
PL-6AAK
1, 50
220
1.64
PU-6YJSA
1.TH
3, 50
380
8.63
1.94
(19.8)
0.43 (4.4)
76 51
1.7 5
27 19
11.0 35 24
0.70
0.06
Electrical circuitRefrigerant circuit
Indoor
side
Outdoo
r side
D.B.
W.B.
D.B. D.B.
W.B.
(1). Rating conditions — ISO.T1(JIS B8616)
Series PL Indoor unit (Single Phase)
3-5. STANDARD OPERATION DATA
Indoor : D.B. 27°C (80°F),
W.B. 19°C (66°F)
Outdoor : D.B. 35°C (95°F)
FF
The unit of pressure has been changed to Mpa based on the international SI system. The conversion factor is : 1(Mpa)=10.2(kgf/
)
18
3-6. OUTLET AIR SPEED AND COVERAGE RANGE
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
APPROTIMATE TERESHOLD OF REARING FOR CONTINUOUS NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
PL-4AAK
Hi
NOTCH
Lo
41
SPL(dB)
33
LINE
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
APPROTIMATE TERESHOLD OF REARING FOR CONTINUOUS NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
PL-3AAK
Hi Lo
34
SPL(dB)28LINE
NOTCH
PL-4AAK
28(990)
4.9
7.4
PL-5AAK
30(1,060)
5.2
7.9
PL-6AAK
30(1,060)
Standard
Service Ref.
Air flow Air speed Coverage range
K/
mim(CFM)
m/W m
PL-3AAK
20(705)
4.0
5.7
wThe air coverage range is the value up to the position where the air speed is 0.25m/sec.
When air is blown out horizontally from the unit at the Hi notch position. The coverage range should be used only as a general guideline since it varies according to the size of the room and the furniture inside the room.
3-7. NOISE CRITERION CURVES
6.6
8.9
19
UNIT
1.5m
MICROPHONE
CEILING
Ambient temperature 27:
Test conditions are based on JIS Z8731
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
APPROTIMATE TERESHOLD OF REARING FOR CONTINUOUS NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
PL-6AAK
Hi
NOTCH
Lo
45
SPL(dB)
37
LINE
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
APPROTIMATE TERESHOLD OF REARING FOR CONTINUOUS NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
PL-5AAK
Hi
NOTCH
Lo
43
SPL(dB)
35
LINE
20
4
Air outlet hole
Vane motor
Auto vane
Drain hole
Grille
Drain pipe VP-25connection (O.D.{32)
Branch duct hole (Cut out hole)
Ceiling surface
Suspension bolt pitch
Ceiling hole
Branch duct hole
Suspension bolt pitch
Ceiling hole
Air outlet hole
Air intake hole
411
Air intake hole
Air intake grille
Receiver
Operation lamp
Emergency operation switch (cooling)
High efficiency filter & Fresh air intake casement (option)
A (WIRELESS PANEL)
Power line entry
Suspension bolt lower edge
Suspension bolt M10 or W3/8
Control wire entry
Feeding hole (Drain pump)
577
374286
840
197 159
60
17
+5
0
17
+5
0
135
30
190
159
605
159192
170
140
50~70
98
89
C
840
860~91020~45 20~45
20~4520~45
Fresh air intake
Branch duct hole
860~910
810
159
16
105
A
B
77 51
M
M
M
A
1
2
M
950
51 77
950
577
411
Terminal block
Deteil drawing of fresh air intake
{175
{150
14 - {2.8 Burring hole
3 - {2.8 Burring hole
{100 (Cut out hole)
{125
Ceiling surface
PL-3AAK
Models 12
PL-4/5/6AAK
Refrigerant pipe
(9.52mm dia.)
flared connection
3/8F
Refrigerant pipe
(9.52mm dia.)
flared connection
3/8F
Refrigerant pipe
(15.88mm dia.)
flared connection
5/8F
241
281
A
258
298
B
80
84
C
Refrigerant pipe
(19.05mm dia.)
flared connection
3/4F
350
120
_
120
_
158
90
70_
100 100 90
100
130
155
167
OUTLINES AND DIMENSIONS
1. INDOOR UNIT PL-3AAK PL-4AAK PL-5AAK PL-6AAK
Unit : mm
21
WIRED REMOTE CONTROLLER
130
120
19
Unit : mm
22
WIRELESS REMOTE CONTROLLER
159.3
55
58
19
Unit : mm
23
5
321
321
531
MF
FAN
(WHT)
RED
WHT
BLK
BLK
X1
X4
X1X4
C
BCR
31
DP
D.U.M
CNP
(BLU)
YLW
YLW
31 31 3 31
YLW
YLW
D.HEATER CNC(RED)
RED
WHT
WHT
POWER CNDK (RED)
POWER CND (ORN)
21 21
POWER CN2D (WHT)
21
OUTDOOR
CN30 (BLK)
CN41CN51 CN2L
CN32
9
WIRELESS
CN90
(WHT)
BZ
5
VANE CN6V
(GRN)
CN2S
(WHT)
CNSK (RED)
W.B(OPTION)
LED2
CNB
LED1
SW1 SW2
RU
21
2
21
1
REMOCON
CN22 (BLU)
TB5
TRANSMISSION WIRES
DC12V
TB6
R.B
BLU
BLU
321 21 21
D.SENSOR
CN31 (WHT)
INTAKE
CN20 (RED)
LIQUID
CN21
(WHT)
DS
TH2
TH1
LED2 LED1
SW6
ON OFF
SWE
Refer to tables
1. 2 and 3.
SW2SW1 SW5
9 5
10
76321 84
5MV5MV5
5
MV5MV
GRILLE
H2
TB2
POWER SUPPLY ~(1 PHASE) 220-240V 50Hz 220V 60Hz
RED BLU
GRN/YLW
TO OUTDOOR UNIT
L
N
DC
13.1V
1
2
2
3
1
P.B
ZNR
FUSE
I.B
YLW ORN
RED
BLU
1 2 3 4 5
MODELS
Table 1
SW1
Manufacture/Service
PL-AAK
(D/C/T)
PL-AAK
(D/C/T)
1 2 3 4 5
ON OFF
MODELS
Table 2
SW2
Manufacture/Service
PL-2.5AAK
(D/C/T)
PL-3AAK
(D/C/T)
PL-5AAK
(D/C/T)
PL-6AAK
(D/C/T)
1 2 3 4 5
ON OFF
PL-4AAK
(D/C/T)
1 2 3 4 5
ON OFF
1 2 3 4 5
ON OFF
MODELS
Manufacture/Service
1 2 3 4 5
ON OFF
ON OFF
1 2
ON OFF
12345678
ON OFF
MODELS
Table 3
SW5
Manufacture/Service
NOTES:
1.Symbols used in wiring diagram above are, : Connector, : Terminal (block).
2.Indoor and outdoor connecting wires are made with polarities, make wiring matching terminal numbers (1, 2, 3).
3.Since the outdoor side electric wiring may change be sure to check the outdoor unit electric wiring for servicing.
Please set the voltage using the remote controller. For the setting method. please refer to the indoor unit Installation Manual.
2 3
1
TB4
INDOOR POWER BOARD
[LEGEND]
P.B
INDOOR CONTROLLER BOARD
I.B
FUSE(T6.3AL250V)
FUSE
CN2L
VARISTOR
ZNR
CONNECTOR(LOSSNAY)
CN32
FAN CONTROL ELEMENT
BCR
CONNECTOR(REMOTE SWITCH)
CN41
CONNECTOR(HA TERMINAL-A)
CN51
CONNECTOR(CENTRALLY CONTROL)
SW1
SWITCH(MODEL SELECTION)wSee table 1 SWITCH(CAPACITY CORD)wSee table 2
SW2 SW5 SW6
SWITCH(SYSTEM SELECTION)wSee table 3 SWITCH(EMERGENCY OPERATION)
SWE
CONNECTOR(EMERGENCY OPERATION)
X1
RELAY(DRAIN PUMP)
X4
RELAY(FAN MOTOR)
LED1
POWER SUPPLY(I.B)
LED2
POWER SUPPLY(R.B)
SYMBOL NAME SYMBOL NAME SYMBOL NAME
C
CAPACITOR(FAN MOTOR)
MF
FAN MOTOR
MV
VANE MOTOR
DP
DRAIN-UP MACHINE
DS
DRAIN SENSOR
H2
DEW PREVENTION HEATER
TB4
TERMINAL BLOCK (INDOOR/ OUTDOOR CONNECTING LINE)
TB2
TERMINAL BLOCK (POWER SUPPLY)
TB5, TB6
TERMINAL BLOCK(REMOTE CONTROLLER TRANSMISSION LINE)
TH1
ROOM TEMP.THERMISTOR (0:/15k",25:/5.4k" DETECT)
TH2
PIPE TEMP.THERMISTOR/LIQUID (0:/15k",25:/5.4k" DETECT)
R.B
WIRED REMOTE CONTROLLER BOARD
W.B
WIRELESS REMOTE CONTROLLER BOARD
RU
RECEIVING UNIT
BZ
BUZZER
LED1
LED(RUN INDICATOR)
LED2
LED(HOT ADJUST)
SW1
SWITCH(HEATING ON/OFF)
SW2
SWITCH(COOLING ON/OFF)
[Self-diagnosis]
1.For details on how to operate self-diagnosis with the wireless remote control, refer to the technical manuals etc.
2.For the wired remote control:When you quickly press twice the CHECK switch on the remote control, the unit begins self-diagnosis. and Check Codes generated in the past appear on the display. For Check Codes and symptoms refer to the table below.
Check Code
P1 P2 P4 P5
Abnormality of room temperature thermistor (TH1). Abnormality of pipe temperature thermistor/Liquid (TH2). Abnormality of drain sensor (DS). Malfunction of drain-up machine.
Symptom
P6
Freezing / overheating protection is working.
P8
E0-E5
Abnormality in outdoor unit. Refer to outdoor unit wiring diagram. Abnormality of the signal transmission between remote controller and indoor unit.
----
FFFF
No trouble generated in the past. No corresponding unit.
Fb
Abnormality of indoor controller board.
[Emergency operation procedure]
1.When the wired remote control or the indoor unit microcomputer has failed,but all other compornents work if you set the switch (SWE, SW6) on the indoor control board, the indoor unit will begin properly. Emergency Operation. wNote on the wireless remote control: when the remote control does not function, it is possible to activate Emergency Operation by using the indoor unit emergency operation switch (SW1,SW2 of the wireless signal receiver board). However,if the indoor unit microcomputer has failed, it is nesessary to proceed with points 2 and 3 below as in the case of the wired remote controller.
2.When you activate emergency operation of the cooling, you have to set the switch (SWE) and switch (SW6) on the indoor controller. SWE : ON • Indoor fan is running at high speed. • Drain-up machine is working. SW6-1 : ON • Emergency operation of cooling mode.
3.Before you activate emergency operation, check the following points: (1) Emergency operation cannot be activated when:
• the outdoor unit malfunctions. • the indoor fan malfunctions.
• when it has detected the malfunction of drain-up machine during self-diagnosing. (2) Emergency operation becomes continuous only by switching the power source on/off. ON/OFF on the remote control or temperature control etc,dose not function. (3) Avoid operating for a long time when the outdoor unit begins defrosting while emergency operation of the heating is activated, because it will start to blow cold air. (4) Emergency cooling should be limited to 10 hours maximum (The indoor unit heat exchanger may freeze). (5) After emergency operation has been deactivated, set the switches etc.to their original positions. (6) Movement of the vanes does not work in emergency operation, therefore you have to slowly set them manually to the appropriate position.
WIRING DIAGRAM
PL-3AAK PL-4AAK PL-5AAK PL-6AAK
24
6 REFRIGERANT SYSTEM DIAGRAM
Capillary tube
(O.D. 3.2 o I.D. 1.8 o L800) o 2pcs
Indoor heat exchanger
Distributor with strainer
Indoor coil thermistor TH2
strainer
Refrigerant pipe [ 9.52(3/8") (with heat insulator) option
Ball valve (with service port)
flow of refrigerant
D.P.R. (Discharge pressure regulator)
Compressor
Accumulator
Ball valve
Low pressure switch
Charge pIug
Check pIug
High pressure switch
Outdoor heat exchanger
strainer
strainer
Flexible tube
Flared connection
Flared connection
Refrigerant pipe [15.88(5/8") (with insulator) option
Indoor heat exchanger
Distributor with strainer
Indoor coil thermistor TH2
strainer
Refrigerant pipe [ 9.52(3/8") (with heat insulator) option
Ball valve (with service port)
Flow of refrigerant
Compressor
Accumulator
Capillary tube PU-4Y only
O.D. 3.2 o I.D. 1.2 o L500
Capillary tube
(O.D. 3.2 o I.D. 2.0 o L840) o 2pcs
Ball valve
Low pressure switch
Charge pIug
Check pIug
High pressure switch
Thermal switch for PU-4V only
Outdoor heat exchanger
Strainer
Muffier
strainer
Flexible tube
Flared connection
Flared connection
Refrigerant pipe [19.05(3/4") (with insulator) option
PL-3AAK / PU-3VJC1.TH, PU-3YJC.TH
UNIT : mm(inch)
PL-4AAK / PU-4VLJSA2.TH, PU-4YJSA1.TH
UNIT : mm(inch)
25
PL-5AAK / PU-5YJSA1.TH
Capillary tube
PU-5Y (O.D. 4.0 o I.D. 2.4 o L840) o 2pcs PU-6Y (O.D. 4.0 o I.D. 2.4 o L840) o 2pcs
Capillary tube
PU-5Y
(O.D. 4.0 o I.D. 2.4 o L400)
PU-6Y
(O.D. 4.0 o I.D. 2.4 o L200)
Thermal switch
Indoor heat exchanger
Distributor with strainer
Indoor coil thermistor TH2
strainer
Refrigerant pipe [ 9.52(3/8") (with heat insulator) option
Ball valve (with service port)
Flow of refrigerant
D.P.R. (Discharge pressure regulator)
Compressor
Accumulator
Ball valve
Charge pIug
Check pIug
High pressure switch
Outdoor heat exchanger
Strainer
strainer
Flexible tube
Flared connection
Flared connection
Refrigerant pipe [19.05(3/4") (with insulator) option
PL-6AAK / PU-6YJSA1.TH
UNIT : mm(inch)
26
7 TROUBLESHOOTING
Unit conditions at service
Error code
Actions to be taken for service (summary)
The inferior phenomenon is reoccurring.
Displayed
Not displayed
Judge what is wrong and take a corrective action according to “SELF-DIAGNOSIS ACTION TABLE” (7-3).
Identify the cause of the inferior phenomenon and take a corrective action according to “TROUBLESHOOTING BY INFERIOR PHENOMENA ” (7-4).
The inferior phenomenon is not reoccurring.
Logged
Not logged
1Consider the temporary defects such as the work of protection devices in the refrigerant circuit including compressor, poor connection of wiring, noise and etc. Re-check the symptom, and check the installation environment, refrigerant amount, weather when the inferior phenomenon occurred, and wiring related. 2Reset error code logs and restart the unit after finishing service. 3There is no abnormality in electrical components, controller boards, and remote controller.
1Recheck the abnormal symptom. 2Identify the cause of the inferior phenomenon and take
a corrective action according to “TROUBLESHOOTING BY INFERIOR PHENOMENA ” (7-4). 3Continue to operate unit for the time being if the cause is not ascertained. 4There is no abnormality in electrical components, controller boards, remote controller etc.
PAR-21MAA
ON/OFF
FILTER
CHECK
OPERATION
CLEAR
TEST
TEMP.
MENU
BACK DAY
MONITOR/SET
CLOCK
ON/OFF
ERROR CODE
ERROR CODE
ERROR CODE
1 Turn on the power. 2 Press the [CHECK] button twice. 3 Set address with [TEMP] button if system control is used. 4 Press the [ON/OFF] button to stop the self-check.
A CHECK button B Address C TEMP. button D IC : Indoor unit
OC: Outdoor unit E Check code F Unit No.
A
F
C
BBEED
7-1. TROUBLESHOOTING
<Error code display by self-diagnosis and actions to be taken for service (summary)>
Present and past error codes are logged and displayed on the wired remote controller or controller board of outdoor unit. Actions to be taken for service,which depends on whether or not the the inferior phenomenon is reoccurring at service, are summarized in the table below. Check the contents below before investigating details.
7-2. MALFUNCTION-DIAGNOSIS METHOD BY REMOTE CONTROLLER
<In case of trouble during operation>
When a malfunction occurs to air conditioner, both indoor unit and outdoor unit will stop and operation lamp blinks to inform unusual stop.
Wired remote controller
27
<Malfunction-diagnosis method at maintenance service>
ON/OFF
TEMP
FAN
VANE
MODE
CHECK
LOUVER
TEST RUN
AUTO STOP
AUTO START
h
min
RESET
SET
CLOCK
CHECK
CHECK display
Temperature button
CHECK button
Address display
HOUR button
ON/OFF button
[Output pattern A] Errors detected by indoor unit
*1If the beeper does not sound again after the initial
two beeps to confirm the self-check start signal was received and
the OPERATION INDICATOR lamp does not come on,
there are no error records.
*2If the beeper sounds three times continuously “beep, beep, beep (0.4 + 0.4 + 0.4 sec.)” after the initial two beeps to confirm
the self-check start signal was received, the specified refrigerant address is incorrect.
OPERATION INDICATOR lamp flash pattern
Beep
Beep Beep Beep Beep Beep Beep
Off
Approx. 2.5 sec.On0.5 sec.On0.5 sec.On0.5 sec.
On
0.5 sec.
Off
Approx. 2.5 sec.On0.5 sec.On0.5 sec.
· · · Repeated
Number of flashes/beeps in pattern indicates the check code in the following table (i.e., n=5 for “P5”)
Number of flashes/beeps in pattern indicates the check code in the following table
n
th
1st2nd3
rd
1st2
nd
Self-check starts (Start signal received)
Beeper sounds
• Refer to the following tables for details on the check codes. [Output pattern A]
• On wireless remote controller
2The continuous buzzer sounds from receiving section of indoor unit. 3Blink of operation lamp
• On wired remote controller
1Check code displayed in the LCD.
Beeper sounds/OPERATION
INDICATOR lamp flashes 1 Check code
Symptom Remark
(Number of times)
Wireless remote controller
Wired remote controller
1P1
Intake sensor error
2
P2 Pipe (TH2) sensor error
4 P4 Drain sensor error 5
P5 PA
Drain pump error
Forced compressor stop 6 P6 Freezing/ Overheating safeguard operation 8 P8 Pipe temperature error / Outdoor unit error 9 E4, E5 Remote controller signal receiving error
10
11
– –
12 Fb Indoor unit control system error (memory error, etc.)
E0, E3
E1, E2 Remote controller control board error
Remote controller transmission error
Wireless remote controller
[Procedure]
1. Press the CHECK button twice.
• "CHECK" lights, and address "00" flash­es.
• Check that the remote controller's display has stopped before continuing.
2. Press the temperature buttons.
3. Point the remote controller at the
sensor on the indoor unit and press the HOUR button.
4. Point the remote controller at the
sensor on the indoor unit and press the ON/OFF button.
• Select the address of the indoor unit for the self-diagnosis.
Main indoor unit : “00” Sub indoor unit : “01”
• If an air conditioner error occurs, the indoor unit's sensor emits an intermit­tent buzzer sound, the operation light flashes, and the error code is output. (It takes 3 seconds at most for error code to appear.)
• The check mode is cancelled.
28
If the unit cannot be operated properly after the above test run has been performed, refer to the following table to remove the cause.
• Symptom
Wired remote controller
PLEASE WAIT
PLEASE WAIT → Error code
Display messages do not appear even when operation switch is turned ON (operation lamp does not light up).
On the wireless remote controller with condition above, following phenomena takes place.
• No signals from the remote controller are accepted.
• Opration lamp is blinking.
• The buzzer makes a short piping sound.
Note: Operation is not possible for about 30 seconds after cancellation of function selection. (Correct operation)
For description of each LED (LED1, 2) provided on the indoor controller, refer to the following table.
LED1 (power for microcomputer) Indicates whether control power is supplied. Make sure that this LED is LED2 (power for wired remote controller)
For about 2 minutes follow­ing power-on
After about 2 minutes has expired follow­ing power-on
• For about 2 minutes following power-on,op­eration of the remote controller is not possible due to system start-up. (Correct operation)
•Connector for the outdoor unit’s protection device is not connected.
•Reverse or open phase wiring for the outdoor unit’s power terminal block
•Incorrect wiring between indoor and outdoor units
•Remote controller wire short
always lit. Indicates whether power is supplied to the wired remote controller.
This LED lights only in the case of the main indoor unit.
Cause
29
7-3. SELF-DIAGNOSIS ACTION TABLE
Error Code
P1
P2
Meaning of error code and detection method
Abnormality of room temperature thermistor (TH1)
1 The unit is in three-minute resume
prevention mode if short/open of thermistor is detected. Abnormal if the unit does not reset normally after three minutes. (The unit returns to normal operation, if it has normally reset.)
2 Constantly detected during cooling,
drying, and heating operation. Short: 90: or more Open: -40: or less
Abnormality of pipe temperature thermistor/Liquid (TH2)
1 The unit is in three-minute resume
prevention mode if short/open of thermistor is detected. Abnormal if the unit does not reset normally after three minutes. (The unit returns to normal operation, if it has normally reset.)
2 Constantly detected during cooling,
drying, and heating (except defrosting) operation. Short: 90: or more Open: -40: or less
Cause
1 Defective thermistor
characteristics.
2 Contact failure of connector
(CN20) on the indoor controller board. (Insert failure)
3 Breaking of wire or contact
failure of thermistor wiring.
4 Defective indoor controller
board.
1 Defective thermistor
characteristics.
2 Contact failure of connector
(CN21) on the indoor controller board. (Insert failure)
3 Breaking of wire or contact
failure of thermistor wiring.
4 Defective refrigerant circuit is
causing thermistor temperature of 90: or more or -40: or less.
5 Defective indoor controller board.
Countermeasure
13 Check resistance value of thermistor. 0: ······15.0k" 10: ····9.6k" 20: ····6.3k" 30: ····4.3k" 40: ····3.0k" If you put force on (draw or bend) the lead wire with measuring resistance value of thermistor breaking of wire or contact failure can be detected. 2 Check contact failure of connector (CN20) on
the indoor controller board. Refer to 7-7. Turn the power on again and check restart after inserting connector again.
4 Check room temperature display on remote
controller. Replace indoor controller board if there is abnormal difference with actual room temperature.
Turn the power off, and on again to operate after check.
13 Check resistance value of thermistor. For characteristics, refer to (P1) above. 2 Check contact failure of connector (CN21) on
the indoor controller board. Refer to 7-7. Turn the power on and check restart after inserting connector again.
4 Check pipe <liquid> temperature with remote
controller in test run mode. If pipe <liquid> temperature is exclusively low (in cooling mode) or high (in heating mode), refrigerant circuit may have defective.
5 Check pipe <liquid> temperature with remote
controller in test run mode. If there is exclusive difference with actual pipe <liquid> temperature, replace indoor controller board.
P4
P5
Abnormality of drain sensor (DS)
1 Suspensive abnormality, if short/open of
thermistor is detected for 30 seconds continuously. Turn off compressor and indoor fan.
2 Short/open is detected for 30 seconds
continuously during suspensive abnormality. (The unit returns to normal operation,
if it has normally reset.)
3 Detect the following condition.
• During cooling and drying operation.
• In case that pipe <liquid> temperature
- room temperature <-10deg (Except defrosting)
• When pipe <liquid> temperature or room temperature is short/open temperature.
• During drain pump operation.
Malfunction of drain pump (DP)
1 Suspensive abnormality, if thermistor
of drain sensor is let heat itself and temperature rises slightly. Turn off compressor and indoor fan.
2 Drain pump is abnormal if the condition
above is detected during suspensive abnormality.
3 Constantly detected during drain pump
operation.
1 Defective thermistor
characteristics
2 Contact failure of connector
(CN31) on the indoor controller board. (Insert failure).
3 Breaking of wire or contact
failure of drain sensor wiring.
4 Defective indoor controller board.
1 Malfunction of drain pump 2 Defective drain
Clogged drain pump Clogged drain pipe
3 Attached drop of water at the
drain sensor
• Drops of drain trickles from lead wire.
• Clogged filter is causing wave of drain.
4 Defective indoor controller board.
Turn the power off, and on again to operate after check.
13 Check resistance value of thermistor. 0: ······6.0k" 10: ····3.9k" 20: ····2.6k" 30: ····1.8k" 40: ····1.3k" 2 Check contact failure of connector (CN31) on
the indoor controller board. Refer to 7-7. Turn the power on again and check restart after inserting connector again.
4 Replace indoor controller board if drain
pump operates with the line of drain sensor connector CN31-1 and 2 is short-circuited, and abnormality reappears.
Turn the power off, and on again to operate after check.
1 Check if drain-up machine works. 2 Check drain function. 3 Check the setting of lead wire of drain sensor
and check clogs of the filter.
4 Replace indoor controller board if drain
pump operates with the line of drain sensor connector CN31-1 and 2 is short-circuited and abnormality reappears. Refer to 7-7.
Turn the power off, and on again to operate after check.
30
Error Code
P6
Meaning of error code and detection method
Freezing/overheating protection is working
1 Freezing protection (Cooling mode)
The unit is in six-minute resume prevention mode if pipe <liquid or condenser/evap­orator> temperature stays under
-15: for three minutes, three minutes after the compressor started. Abnormal if it stays under -15: for three minutes again within 16 minutes after six-minute resume prevention mode.
<Frost prevention mode> If pipe <liquid or condenser-evaporator> temperature is 1: or below when 16 minutes has passed after compressor starts operating, unit will start operating in frost prevention mode which stops compressor operation. After that, when pipe <liquid or condenser/evaporator> temperature stays 10: or more for 3 minutes, frost prevention mode will be released and compressor will restart its operation.
2 Overheating protection (Heating mode)
The units is in six-minute resume
prevention mode if pipe <condenser / evaporator> temperature is detected as over 70: after the compressor started. Abnormal if the temperature of over 70: is detected again within 10 minutes after six-minute resume prevention mode.
(Cooling or drying mode)
1 Clogged filter (reduced airflow) 2 Short cycle of air path 3 Low-load (low temperature)
4 Defective indoor fan motor
• Fan motor is defective.
• Indoor controller board is
5 Defective outdoor fan control 6 Overcharge of refrigerant 7 Defective refrigerant circuit
(Heating mode)
1 Clogged filter (reduced airflow) 2 Short cycle of air path 3 Over-load (high temperature)
4 Defective indoor fan motor
• Fan motor is defective.
• Indoor controller board is
5 Defective outdoor fan control 6 Overcharge of refrigerant 7 Defective refrigerant circuit
8 Bypass circuit of outdoor unit
Cause
operation beyond the tolerance range
defective.
(clogs)
operation beyond the tolerance range
defective.
(clogs) is defective.
Countermeasure
(Cooling or drying mode)
1 Check clogs of the filter. 2 Remove shields.
4 Measure the resistance of fan motor's winding.
Measure the output voltage of fan's connector (FAN) on the indoor controller board. WThe indoor controller board should be
normal when voltage of AC 220~240V is detected while fan motor is connected. Refer to 7-7.
5 Check outdoor fan motor. 67 Check operating condition of refrigerant
circuit.
(Heating mode)
1 Check clogs of the filter. 2 Remove shields.
4 Measure the resistance of fan motor's
winding. Measure the output voltage of fan's connector (FAN) on the indoor controller board. WThe indoor controller board should be
normal when voltage of AC 220~240V is detected while fan motor is connected. Refer to 7-7.
5 Check outdoor fan motor. 6~8Check operating condition of refrigerant
circuit.
P8
Abnormality of pipe temperature
<Cooling mode> Detected as abnormal when the pipe tem­perature is not in the cooling range 3 min­utes later of compressor start and 6 min­utes later of the liquid pipe is out of cooling range. Note 1) It takes at least 9 min. to detect. Note 2) Abnormality P8 is not detected in
drying mode. Cooling range : -5 deg ] (TH2-TH1) TH2: Liquid pipe temperature TH1: Intake temperature
Abnormality in outdoor unit
1 Slight temperature difference
between indoor room temperature and pipe tempera­ture thermistor
• Shortage of refrigerant
• Disconnected holder of pipe thermistor
• Defective refrigerant circuit
2 Converse connection of
extension pipe (on plural units connection)
3 Converse wiring of indoor/
outdoor unit connecting wire (on plural units connection)
4 Defective detection of indoor
room temperature and pipe temperature thermistor
5 Stop valve is not opened
completely.
1 Wrong wiring of indoor/outdoor
connecting wire
2 Reversed phase 3 Protection device is working 4 Damaged outdoor coil thermis-
tor
1~4 Check pipe temperature with room
temperature display on remote controller.
23Check converse connection of extension
pipe or converse wiring of indoor/outdoor unit connecting wire.
1 Check the indoor/outdoor connecting wire. 2 Change the connection of electric wiring. 3 Check the protection device. 4 Measure the resistance of the outdoor coil
thermistor. If the resistance is normal, replace the outdoor controller board.
31
Error Code
E0
or
E4
E3
or
E5
Meaning of error code and detection method
Remote controller transmission error(E0)/signal receiving error(E4)
1 Abnormal if main or sub remote con-
troller can not receive normally any transmission from indoor unit of refriger­ant address “0” for three minutes. (Error code : E0)
2 Abnormal if sub remote controller could
not receive for any signal for two min­utes. (Error code: E0)
1 Abnormal if indoor controller board can
not receive normally any data from remote controller board or from other indoor controller board for three minutes. (Error code: E4)
2 Indoor controller board cannot receive
any signal from remote controller for two minutes. (Error code: E4)
Remote controller transmission error(E3)/signal receiving error(E5)
1 Abnormal if remote controller could not
find blank of transmission path for six seconds and could not transmit.
(Error code: E3)
2 Remote controller receives transmitted
data at the same time, compares the data, and when detecting it, judges different data to be abnormal 30 continuous times. (Error code: E3)
1 Abnormal if indoor controller board could
not find blank of transmission path.
(Error code: E5)
2 Indoor controller board receives trans-
mitted data at the same time, compares the data,and when detecting it, judges different data to be abnormal 30 continuous times. (Error code: E5)
1 Contact failure at transmission 2 All remote controllers are set
3 Mis-wiring of remote controller. 4 Defective transmitting receiving
5 Defective transmitting receiving
6 Noise has entered into the
1 Two remote controller are set
2 Remote controller is connected 3 Repetition of refrigerant 4 Defective transmitting receiving 5 Defective transmitting receiving
6 Noise has entered into trans-
Cause
wire of remote controller as “sub” remote controller. In
this case, E0 is displayed on remote controller, and E4 is displayed at LED (LED1, LED2) on the outdoor controller circuit board.
circuit of remote controller circuit of indoor controller board
of refrigerant address “0”. transmission wire of remote
controller.
as “main.”
(In case of 2 remote con-
trollers) with two indoor units or more. address. circuit of remote controller. circuit of indoor controller
board. mission wire of remote con-
troller.
Countermeasure
1 Check disconnection or looseness of indoor
unit or transmission wire of remote controller.
2 Set one of the remote controllers “main”.
If there is no problem with the action above.
3 Check wiring of remote controller.
• Total wiring length: max.500m (Do not use cable x 3 or more)
• The number of connecting indoor units:
max.16units
• The number of connecting remote con-
troller: max.2units
When it is not the above-mentioned problem of
1~3 4 Diagnose remote controllers.
a) When “RC OK” is displayed,
Remote controllers have no problem. Put the power off, and on again to check. If abnormality generates again, replace indoor controller board.
b) When “RC NG” is displayed,
Replace remote controller. c) When “RC E3” is displayed, d) When “ERC 00-06” is displayed, [ c),d)Noise may be causing abnormality. ]
If the unit is not normal after replacing
indoor controller board in group control, indoor controller board of address “0” may be abnormal.
1 Set a remote controller to main, and the
other to sub.
2 Remote controller is connected with only one
indoor unit.
3 The address changes to a separate setting. 4~6 Diagnose remote controller.
a) When “RC OK”is displayed, remote con-
trollers have no problem.
Put the power off,and on again to check. When becoming abnormal again, replace
indoor controller board. b)When “RC NG”is displayed, replace
remote controller. c)When “RC E3”or “ERC 00-66”is displayed,
noise may be causing abnormality.
32
Error Code
Fb
E1
or
E2
PA (2502) (2500)
Meaning of error code and detection method Abnormality of indoor controller board
Abnormal if data cannot be normally read from the nonvolatile memory of the indoor controller board.
Abnormality of remote controller con­trol board
1 Abnormal if data cannot be normally
read from the nonvolatile memory of the remote controller control board.
(Error code: E1)
2 Abnormal if the clock function of remote
controller cannot be normally operated.
(Error code: E2)
Forced compressor stop (due to water leakage abnormality)
1 When the intake temperature subtracted
with liquid pipe temperature is less than
-10:, drain sensor is detected whether it is soaked in the water or not at the interval of 90 seconds. (Drain pump will start operating when the drain sensor is detected to be soaked in the water.)
2 The unit has a water leakage abnormality
when the following conditions, a and b, are satisfied while the above-mentioned detection is performed. a) The drain sensor is detected to be
soaked in the water 10 times in a row.
b) The intake temperature subtracted with
liquid pipe temperature is detected to be less than -10: for a total of 30 minutes. (When the drain sensor is detected to
be NOT soaked in the water, the detection record of a and b will be cleared.)
3 The drain sensor detection is performed
in operations other than cooling. (When the unit stops operating, during heating or fan operation, when the unit stops because of some abnormality)
*Once the water leakage abnormality is
detected, abnormality state will not be released until the main power is reset.
1 Defective indoor controller
1 Defective remote controller. 1 Replace remote controller.
1) Drain pump trouble
2) Drain defective
3) Open circuit of drain sensor
4) Contact failure of drain sensor
5) Dew condensation on drain
6) Extension piping connection
7) Mis-wiring of indoor/ outdoor
8) Room temperature thermistor /
Cause
board.
· Drain pump clogging
· Drain pipe clogging
side heater
connector
sensor
· Drain water descends along lead wire.
· Drain water waving due to filter clogging.
difference at twin, triple, quadruple system.
connecting at twin, triple, quadruple system.
liquid pipe temperature thermis­tor detection is defective.
Countermeasure
1 Replace indoor controller board.
Check the drain pump. Performance Please confirm whether water can be drained.
Confirm the resistance of the drain sensor side
heater.
Check the connector contact failure.
1 Check the drain sensor leadwire mounted. 2 Check the filter clogging
Check the piping connection.
Check the indoor/ outdoor connecting wires.
Check the room temperature display of remote controller. Check the indoor liquid pipe temperature dis-
play of outdoor controller board.
33
7-4. TROUBLESHOOTING BY INFERIOR PHENOMENA
Phenomena
(1)LED2 on indoor controller board
is off.
• When LED1 on indoor controller board is also off.
1 Power supply of 220~240V AC is not supplied to
indoor unit.
2 Defective indoor controller board.
3 Defective indoor power board.
Cause
Countermeasure
1 Check the voltage of indoor power supply
terminal block (L,N).
• When AC220~240V is not detected. Check the power supply wiring.
• When AC220~240V is detected.
-Check 2 (below).
2 Check voltage output from CNDK on
indoor controller board.
• When AC220~240V is not detected. Check the fuse on indoor controller board. Check the wiring connection between indoor power supply terminal block and CND on indoor controller board.
• When AC220~240V is detected.
-Check 3 (below).
3 Check voltage output from CN2S on
indoor power board.
• When no voltage output. Check the wiring connection between CNDK on indoor controller board and CNSK on indoor power board. If no problem are found,indoor power board is defective.
• When DC12.5~13.7V is detected. Check the wiring connection between CN2S on indoor power board and CN2D on indoor power board. If no problem are found,indoor con­troller board is defective.
(2)LED2 on indoor controller board
is blinking.
• When LED1 on indoor controller board is lit.
1 Mis-setting of main/sub for indoor unit
(There is no unit corresponding to main unit.)
• When LED1 on indoor controller board is also blinking. Connection failure of indoor/outdoor unit connecting wire
• When LED1 is lit.
1 Mis-wiring of remote controller wires
When 2 indoor units are wired in one refrigerant
system, each indoor unit sets main unit. (SW5-3)
2 Short-cut of indoor/outdoor unit connecting wire.
3 Short-cut of remote controller wires 4 Defective remote controller
1 Reconfirm the setting of main/sub for
indoor unit
Set the main unit. Set main/sub using SW5-3 on indoor controller board.
Check indoor/outdoor unit connecting wire for connection failure.
1 Check the connection of remote con-
troller wires in case of twin triple indoor unit system. When 2 or more indoor units are wired in one refrigerant system, connect remote controller wires to one of those units.
2 Remove indoor/outdoor connecting wires
and check LED2 on indoor controller board.
• When LED2 is blinking, check the short­cut of indoor/outdoor connecting wires.
• When LED2 is lit, connect indoor/outdoor connecting wires again, and; if LED2 is blinking, outdoor unit’s controller board is defective; if LED2 is lit, connection failure of indoor/outdoor terminal block etc. has returned to normal.
34 Remove remote controller wires and
check LED2 on indoor controller board.
• When LED2 is blinking, check the
short-cut of remote controller wires.
• When LED2 is lit, connect remote
controller wires again and: if LED2 is blinking, remote controller is defective; if LED2 is lit, connection failure of remote controller terminal block etc. has returned to normal.
34
Phenomena
• After completing installation and the wiring and piping of the indoor and outdoor units, check for refrigerant leakage, looseness in the power supply or control wiring, wrong polarity, and no disconnection of one phase in the supply.
• Use a 500-volt megohmmeter to check that the resistance between the power supply terminals and ground is at least 1.0M".
• Do not carry out this test on the control wiring (low voltage circuit) terminals.
Warning: Do not use the air conditioner if the insulation resistance is less than 1.0M". Insulation resistance
B
EF
C
H
G
IM
A
D
ûC
ûC
SIMPLE
PAR-21MAA
ON/OFF
FILTER
CHECK
OPERATION
CLEAR
TEST
TEMP.
MENU
BACK DAY
MONITOR/SET
CLOCK
ON/OFF
TEST RUN COOL, HEAT
A ON/OFF button B Test run display C Indoor temperature liquid line
temperature display
D ON/OFF lamp E Power display
F Error code display
Test run remaining time display
G Set temperature button H Mode selection button I Fan speed button M TEST button
1 Turn on the power at least 12 hours before the test run. 2 Press the [TEST] button twice. "TEST RUN" liquid crystal display 3 Press the [Mode selection] button. Make sure that wind is blown out. 4 Press the [Mode selection] button and switch to the cooling mode.
Make sure that cold wind is blown out.
5 Press the [Fan speed] button. Make sure that the wind speed is switched. 6 Check operation of the outdoor unit fan. 7 Release test run by pressing the [ON/OFF] button. Stop 8 Register a telephone number.
The telephone number of the repair shop, sales office, etc., to contact if an error occurs can be registered in the remote controller. The telephone number will be displayed when an error occurs. For registration procedures, refer to the operation manual for the indoor unit.
(3)Upward/downward vane
performance failure
1 The vane is not downward during defrosting and
heat preparation and when the thermostat is OFF in HEAT mode. (Working of COOL protection function)
Cause
2 Vane motor does not rotate.
• Defective vane motor
• Breaking of wire or connection failure of connector
• Up/down vane setting is “No vanes”.
3 Upward/downward vane does not work.
• The vane is set to fixed position.
(4)Receiver for wireless remote
controller
1 Weak batteries of wireless remote controller. 2 Contact failure of connector (CNB) on wireless
remote controller board.
(Insert failure)
3 Contact failure of connector (CN90) on indoor con-
troller board.(Insert failure)
4 Contact failure of connector between wireless
remote controller board and indoor controller board.
7-5. TEST RUN AND EMERGENCY OPERATION
7-5-1. Before test run
Countermeasure
1 Normal operation (The vane is set to hor-
izontal regardless of remote control.)
2 Check 2 (left).
• Check the vane motor. (Refer to “How to check the parts”.)
• Check for breaking of wire or connec­tion failure of connector.
• Check “Up/down vane setting”. (Unit function selection by remote controller).
3 Normal operation (Each connector on
vane motor side is disconnected.)
1 Replace batteries of wireless remote con-
troller.
2~4
Check contact failure of each connector. If no problems are found of connector, replace indoor controller board. When the same trouble occurs even if indoor controller board is replaced, replace wireless remote controller board.
7-5-2. Test run (Using wired remote controller)
35
Receiver
Operation lamp
Emergency operation switch (cooling)
Mode
Cooling
Set temperature
Fan speed
Airflow direction
24: High
Horizontal (30deg)
wEmergency operation will be performed as follows.
7-5-3. Test run (Using wireless remote controller)
1 Turn on the power to the unit at least 12 hours before the test run. 2 Press the button twice continuously.
(Start this operation from the status of remote controller display turned off.) A and current operation mode are displayed.
TEST RUN
TEST RUN
3 Press the button to activate mode, then check whether cool air is blown out from the unit.
MODE
COOL
4 Press the button and check whether fan speed changes.
FAN
5 Press the button and check whether the auto vane operates properly.
VANE
6 Press the ON/OFF button to stop the test run.
Note:
Point the remote controller towards the indoor unit receiver while following steps 2 to 6.
• It is not possible to run the in FAN or DRY mode.
A
TEST RUN
ON/OFF TEMP
6
FAN
AUTO STOP
AUTO START
h
min
4
5
3
2
CHECK
TEST RUN
LOUVER
RESETSET CLOCK
VANE
MODE
7-5-4. When wireless remote controller troubles or its battery is exhausted
1. Emergency operation is available in such a case using emergency operation switch equipped next to the receiver of indoor unit.
2. To start operation
• Cooling Operation·······Press (Cooling) switch.
wWhen the unit starts operating, the operation lamp is lit.
3. To stop operation
• Press either emergency operation switch.
7-5-5. When wired remote controller or indoor unit micro computer troubles
1.When the wired remote control or the indoor unit microcomputer has failed,but all other compornents work if you set the switch (SWE, SW6) on the indoor control board, the indoor unit will begin properly Emergency Operation.
w Note on the wireless remote control: when the remote control does not function, it is possible to activate Emergency
Operation by using the indoor unit emergency operation switch (SW1,SW2 of the wireless signal receiver board). However,if the indoor unit microcomputer has failed, it is nesessary to proceed with points 2 and 3 below as in the case of the wired remote controller.
2.When you activate emergency operation of the cooling, you have to set the switch (SWE) and switch (SW6) on the indoor controller. SWE : ON • Indoor fan is running at high speed. • Drain-up machine is working. SW6-1 : ON • Emergency operation of cooling mode.
3.Before you activate emergency operation, check the following points:
(1) Emergency operation cannot be activated when:
• the outdoor unit malfunctions. • the indoor fan malfunctions.
• when it has detected the malfunction of drain-up machine during self-diagnosing.
(2) Emergency operation becomes continuous only by switching the power source on/off. ON/OFF on the remote control or
temperature control etc,dose not function.
(3) Avoid operating for a long time when the outdoor unit begins defrosting while emergency operation of the heating is
activated, because it will start to blow cold air. (4) Emergency cooling should be limited to 10 hours maximum (The indoor unit heat exchanger may freeze). (5) After emergency operation has been deactivated, set the switches etc.to their original positions. (6) Movement of the vanes does not work in emergency operation, therefore you have to slowly set them manually to the
appropriate position.
36
7-6. HOW TO CHECK THE PARTS
Parts name Check points
Disconnect the connector then measure the resistance using a tester. (Surrounding temperature 10:~30:)
Measure the resistance between the terminals using a tester. (Surrounding temperature20:)
Measure the resistance between the terminals using a tester. (Winding temperature 20:)
Measure the resistance between the terminals using a tester. Measure the resistance after 3 minutes have passed since the power supply was intercepted. (Surrounding temperature 0:~60:)
Vane motor
Drain pump
Drain sensor
(Refer to the thermistor)
(Refer to the thermistor)
Room temperature thermistor (TH1)
Pipe temperature thermistor/liquid(TH2)
1 3
YLW
YLW
1 2 3
Normal
4.3k"~9.6k"
Abnormal
Open or short
Abnormal
Open or short
Normal
0.6k"~6.0k"
Normal Abnormal
15k" Open or short
Normal Abnormal
290" Open or short
Measure the resistance between the terminals using a tester. (Winding temperature 20:)
Fan motor
1
1
2
2
3
3
Red
White
Black
Relay connector
Protector OFF:130: ON :80i20:
Abnormal
Open or short
Red-Black
White-Black
Motor terminal
or
Relay connector
Normal
87.2"
104.1"
PL-3 PL-4/5/6
28.7"
41.6"
PL-3AAK PL-4AAK PL-5AAK PL-6AAK
37
<Thermistor Characteristic graph>
-20 0 20406080
< Thermistor for drain sensor >
Temperature (:)
0
1
2
3
4
5
6
7
8
9
10
Resistance (K")
Thermistor for lower temperature
Room temperature thermistor(TH1) Pipe temperature thermistor/liquid(TH2)
Thermistor R0=15k' ±3%
Fixed number of B=3480 ± 2 %
Rt=15exp { 3480( ) }
1
273+t
1
273
0: 15k'
10: 9.6k'
20: 6.3k'
25: 5.4k'
30: 4.3k'
40: 3.0k'
Thermistor for drain sensor
< Thermistor for lower temperature >
50
40
30
20
Resistance (K")
10
0
-20 -10 0 10 20 30 40 50 Temperature (:)
Thermistor R0=6.0k' ±5% Fixed number of B=3390 ±2%
Rt= 6 exp { 3390( ) }
1
273+t
0: 6.0k' 10: 3.9k' 20: 2.6k' 25: 2.2k' 30: 1.8k' 40: 1.3k' 60: 0.6k'
1
273
38
7-7.TEST POINT DIAGRAM
7-7-1. Power board PL-3AAK PL-4AAK PL-5AAK PL-6AAK
CN2S Connect to the indoor controller board (CN2D) Between 1 to 3 12.6-13.7V DC (Pin1 (+))
CNSK Connect to the indoor controller board (CNDK) Between 1 to 3 220-240V AC
39
7-7-2. Indoor controller board PL-3AAK PL-4AAK PL-5AAK PL-6AAK
CNDK Connect to the indoor power board (CNSK) (220~240V AC)
SW6 Emergency operation
FUSE (6.3 A 250 V)
CND Power supply input (220~240V AC)
CNP Drain-pump output (DP) (220~240V AC)
CNC Dew prevention heater(H2)
CN2D Connect to the indoor power board (CN2S) (12.5~13.7V DC)
LED1 Power supply (I.B)
LED2 Power supply (R.B)
CN22 Connect to the terminal block(TB5) (Remote controller connecting wire) (10.4~14.6V DC)
CN30 Transmission (indoor/outdoor)
CN20 Room temperature thermistor (TH1)
CN21 Pipe temperature thermistor/Liquid (TH2)
CN31 Drain sensor (DS)
CN90 Connect to the wireless remote controller board (CNB)
CN6V Vane motor output (MV)
CN41 Connector (HA terminal-A)
CN105/CN92 (RED)
CN51 Centrally control
CN24 Heater output (12V DC)
SWE Emergency operation
FAN Fan motor output
Jumper wire J41, J42 Pair number setting with wireless remote controller
40
SW2 Capacity setting
CN32 Remote switch
CN2L Connector (LOSSNAY)
SW5 System setting
SW1 Model setting
7-8. FUNCTIONS OF DIP SWITCH AND JUMPER WIRE
Each function is controlled by the dip switch and the jumper wire on control p.c. board.
(Marks in the table below) Jumper wire ( : Short : Open)
Jumper wire
SW1
SW2
Functions
Model settings
Capacity settings
Setting by the dip switch and jumper wire
MODELS SW1
1 2 3 4 5
PL-AAK
MODELS SW2
1 2 3 4 5
PL-3AAK
1 2 3 4 5
PL-4AAK
1 2 3 4 5
PL-5AAK
1 2 3 4 5
PL-6AAK
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
Remarks
SW5
J41 J42
System settings
Pair number setting with wireless remote controller
MODELS SW5
1 2 3 4 5 6 7 8
PL-AAK
Wireless remote
controller setting
0 1 2
3 ~ 9
Control PCB setting
J41 J42
SW5-3 Main/Sub setting OFF : Main ON : Sub
ON
SW5-4 Rotaion operation setting
OFF
OFF : Not avairable ON : avairable <Settings at time of factory shipment>
Wireless remote controller: 0 Control PCB: (for both J41 and J42) Four pair number settings are supported. The pair number settings of the wireless remote controller and indoor control PCB (J41/J42) are given in the table on the left. (' ' in the table indicates the jumper line is disco­nnected.)
41
8 FUNCTION SETTING
8-1. UNIT FUNCTION SETTING BY THE REMOTE CONTROLLER
Each function can be set according to necessity using the remote controller. The setting of function for each unit can only be done by the remote controller. Select function available from the table 1.
<Table 1> Function selections
(1) Functions available when setting the unit number to 00 (Select 00 referring to 4 setting the indoor unit number.)
W1 The functions below are available only when the wired remote controller is used.The functions are not available for floor
standing models.
Function
Power failure automatic recovery Indoor temperature detecting
LOSSNAY connectivity
Power supply voltage Frost prevention temperature Humidifier control
Rotation
Settings
OFF ON Indoor unit's (Main) internal sensor
Remote controller's internal sensor w1 Not supported Supported (indoor unit not equipped with outdoor air intake) Supported (indoor unit equipped with outdoor air intake) 240V 220V,230V 1: (Normal)
-3: When the compressor operates, the humidifier also operates. When the fan operates, the humidifier also operates. 24h cycle 168cycle Back up function
Mode No.
01
02
03
04 15 16
20
Setting No.
1 2 1 2 3 1 2 3 1 2 1 2 1 2 1 2 3
Initial setting
(when sent from the factory)
Remarks
The setting is applied to all the units in the same refrigerant system.
(2) Functions available when setting the unit number to 01-03 or AL (07 in case of wireless remote controller)
• When setting functions for an indoor unit in an independent system, set the unit number to 01 referring to 4 setting the indoor unit number.
• When setting functions for a simultaneous- Twin Triple indoor unit system, set the unit number to 01 to 03 for each indoor
unit in case of selecting different functions for each unit referring to 4 setting the indoor unit number.
• When setting the same functions for an entire simultaneous Twin Triple-indoor unit system, set refrigerant address to AL
(07 in case of wireless remote controller) referring to 4 setting the indoor unit number.
)
Mode
Function Settings
Filter sign 100Hr 1
Air flow Standard 1 (
Fan speed
No.of air outlets 4 directions 1
Optional high efficiency filter Supported Vane setting
Energy saving air Disabled flow (Heating mode Optional humidifier Not supported
Vane differential setting No.1 setting (TH5: 24-28: in heating mode No.2 setting (Standard, TH5:28-32: (
cold wind prevention
Swing Not available Quiet operation mode Disabled (Standard
(
Fan speed Fan speed when the cooling thermostat is OFF Stop Detection of abnormality of Available the pipe temperature (P8)Not available
)
)
)
2500Hr 07 2
No filter sign indicator
High ceiling1 High ceiling2
3 directions 09 2 2 directions Not supported
Vane No.3 setting Vane No.1 setting Vane No.2 setting
Enabled
Supported
)
No.3 setting (TH5: 32-38:
Available
Enabled (Quiet operation mode
Set fan speed
)
)
)
)
)
No.
08 2
10
11 2
12
13
14 2
23 26
27
28
Setting No.
Initial setting (Factory setting
- : Not available
4-Way cassette
PL-AAKC PL-AAKD
3
3
3 1 2
1
3 1 2 1 2
1
3 1 2 1 2 1 2 1 2
42
Rotation setting (Function setting mode No.20
9-1-1. Selecting functions using the wired remote controller
First, try to familiarize yourself with the flow of the function selection procedure. In this section, an example of setting the room temperature detection position is given. For actual operations, refer to steps 1 to 0 .
Setting number
Address Unit number
Mode number
F
E
G
C
D
J
B
A
I
Modes 01 to 13 can be activated by pressing buttons
A
and
B
simultaneously, and modes 15 to 28 by pressing buttons
B
and J.
Function setting Mode No.
Setting No.
19 01
(
24hours cycle
)
Features Indoor controller board
Each system operates alternately for 24hours.
)
SW5-3 setting SW5-4 setting
02
(
168hours
)
cycle
03
(
Back up function
Each system operates alternately for 168hours.
When abnormality occurs while operating
)
and operating continues.
,
it changes as a back up unit
OFF : Main ON : Sub
,
This system can correspond only by the pattern of two refrigerant group by 1 : 1 (indoor and outdoor unit combination) systems.
Example of unit's operation
(Setting No. = 01 or 02)
Operation starts MainSub SubMain
Main indoor unit
Sub indoor unit
(Setting No. = 03)
Main indoor unit
ON
OFF
ON
OFF
Operation starts MainSub
ON
OFF
24h 24h
(Setting No. = 02
• • •
168hours cycle)
Main Unit is abnormal
Main Unit is abnormal
MainSub
Main
ON
Remote Controller
Sub
Outdoor unit
Indoor unit
Sub indoor unit
ON
OFF
43
Selecting functions using the wired remote controller
1
Check the function selection setting.
2
Switch to function setting mode.
(Press
A
and B at the same time
For modes 15 and higher, press
with the remote controller stopped.)
3
Specify address
(Use
C
4
Specify unit No.
and D.)
Refer to address unit No. to the figure below
J
and B at the same time.
5
Enter the setting.
(Press
6
Select mode No. 02
(Specified indoor unit:
E
.)
BLOW operation)
NO
Change refrigerant address unit No.
YES
(room temperature detection position).
7
Select setting No. 03 (remote controller fixed).
(Use
F
and G.)
8
Enter the setting.
(Press
E
.)
Example: Selecting room temperature detection position
9
NO
Finished
YES
0
Ending function display
(Press
1 : 1 system Simultaneous twin system Rotation system
A
and B at the same time.)
The above procedure must be carried out only if changes are necessary.
Outdoor unit
Indoor unit
Remote controller
Indoor unit address = 00 unit No. = 01
Main indoor unit
Main indoor unit address = 00 unit No. = 01
Outdoor unit Outdoor unit Outdoor unit
Sub indoor unit
Remote controller
Sub indoor unit address = 01 unit No. = 02
Main indoor unit
Main indoor unit address = 00 unit No. = 01
Sub indoor unit
Remote controller
Sub indoor unit address = 01 unit No. = 01
44
[Operating Procedure]
1 Check the setting items provided by function selection.
If settings for a mode are changed by function selection, the functions of that mode will be changed accordingly. Check all the current settings according to steps 2 to 7 , fill in the "Check" column in Table 1, and then change them as necessary. For factory settings, refer to the indoor unit's installation manual.
2 Switch off the remote controller.
A Hold down the
buttons and then the remote controller's display content will change as shown below.
* If the unit stops after
Check to see if there are any sources of noise or interference near the transmission path. Note
If you have made operational mistakes during this procedure, exit function selection (see step 0 ), and then restart from step 2 .
4 Set the indoor unit number.
D Press the
area.
FILTER
simultaneously for at least two seconds.
Address display section
FUNCTION
flashed for two seconds or "88" flashes in the room temperature display area for two seconds, a transmission error may have occurred.
SELECTION
ON/OFF
button so that " - -" flashes in the unit number display
Unit number display section
FUNCTION SELECTION
B and ( mode 15 or more)
TEST
will start to flash,
3 Set the outdoor address.
C Press the [ CLOCK] buttons ( and ) to select the desired
address. The address changes from "00" to "15".
C Press the [
of the indoor unit for which you want to perform function selection. The unit number changes to "00", "01", "02","03",04" and "AL" each time a button is pressed.
CLOCK] buttons ( and ) to select the unit number
* To set modes 01 to 06 or 15 to 22 select unit number "00". * To set modes 07 to 14 or 23 to 28 carry out as follows:
• To set each indoor unit individually, select "01" to "04".
• To set all the indoor units collectively, select "AL".
5 Confirm the address and unit number.
E Press the
number. After a while, "- - " will start to flash in the mode number display area.
Mode number display section
* "88" will flash in the room temperature display area if the selected address
does not exist in the system. Furthermore, if address display area also flashes, there are no units that correspond to the selected unit number. In this case, the address and unit number may be incorrect, so repeat steps 2 and 3 to set the correct ones.
6 Select the mode number.
F Press the [
number. (Only the selectable mode numbers can be selected.)
7 Select the setting content for the selected mode.
G Press the
flash, so check the currently set content.
8 Register the settings you have made in steps 3 to 7 .
E Press the
to flash and registration starts.
MODE
button to confirm the address and unit
MODE
"F"
appears and flashes in the unit number display area and the
TEMP] buttons ( and ) to set the desired mode
button. The currently selected setting number will
MENU
Setting number display section
button. The mode number and setting number will start
Setting number 1 = Indoor unit operating average
E When the address and unit number are confirmed by pressing the
button, the corresponding indoor unit will start fan operation. This
MODE
helps you find the location of the indoor unit for which you want to perform function selection. However, if "00" or "AL" is selected as the unit number, all the indoor units corresponding to the specified address will start fan operation.
Example) When the address is set to 01 and the unit number is 02.
00 address
Outdoor unit
Indoor unit
Designate operation
* When grouping different systems, if an indoor unit other than the
one to which the address has been set performs fan operation, there may be another address that is the same as the specified one. In this case, check the DIP switch of the outdoor unit to see whether such a address exists.
Mode number display section
F Press the [
number.
The mode number and setting number will stop flashing and remain lit, indicating the end of registration.
TEMP] buttons ( and ) to select the desired setting
Main Sub
Remote controller
Mode number 02 = Indoor temperature detection
Setting number 3 = Remote controller built-in sensor
Fan draft
* If " - - - " is displayed for both the mode number and setting number and "
Check to see if there are any sources of noise or interference near the transmission path. 9 If you wish to continue to select other functions, repeat steps 3 to 8 . 0 Complete function selection.
A Hold down the
buttons simultaneously for at least
After a while, the function selection screen will disappear and the air condi­tioner OFF screen will reappear.
Note If a function of an indoor unit is changed by function selection after installation is complete, make sure that a " " mark, etc., is given in the "Check" column of Table 1 to indicate the change.
FILTER TEST
and ( mode 15 or more)
two seconds.
" flashes in the room temperature display area, a transmission error may have occurred.
* Do not operate the remote controller for at least 30 seconds after completing
function selection. (No operations will be accepted even if they are made.)
45
ON/OFF
TEMP
FAN
VANE
MODE
CHECK
LOUVER
TEST RUN
AUTO STOP
AUTO START
h
min
CHECK
RESET
SET
CLOCK
h
CHECK
min
h
The flow of the function selection procedure is shown below. This example shows how to turn off the function that raises the set temperature by 4 degrees during HEAT operation . The procedure is given after the flow chart.
1 Check the function selection setting. 2 Switch to function selection mode.
(Enter address "50" in troubleshooting mode, then press the HOUR button.)
Troubleshooting mode is the mode entered when you press the INSPECT button twice to display "INSPECT".
3 Specify unit No. "01" (since the function applies to unit 01).
(Set address "01" while still in troubleshooting mode, then press the MINUTE button.)
Note: You can't specify the refrigerant address.
4
Select mode No. "24" (function that raises set temperature by 4 degrees during HEAT operation).
(Set address "24" while still in troubleshooting mode, then press the HOUR button.)
6
Finished
8 End function selection mode.
(End troubleshooting mode.)
YES
NO
Note: When you switch to function selection mode
on the wireless remote controller's operation area, the unit ends function selection mode automatically if nothing is input for 10 minutes or longer.
5 Select setting No. "02" (OFF).
(Set address "02" while still in troubleshooting mode, then press the HOUR button.)
Change unit No.
YES
NO
7
8-1-2. Selecting functions using the wireless remote controller (Type C)
h
min
Functions can be selected with the wireless remote controller. Function selection using wireless remote controller is available only for refriger­ant system with wireless function. Address cannot be specified by the wireless remote controller.
[Flow of function selection procedure]
[Operating instructions]
1 Check the function settings. 2 Press the button twice continuously. CHECK is lit and “00” blinks.
Press the temp button once to set “50”. Direct the wireless remote controller toward the receiver of the indoor unit and press the button.
3 Set the unit number.
Press the temp button to set the unit number. (Press “01” to specify the indoor unit whose unit number is 01.) Direct the wireless remote controller toward the receiver of the indoor unit and press the button.
By setting unit number with the button, specified indoor unit starts performing fan operation. Detect which unit is assigned to which number using this function. If unit number is set to AL, all the indoor units in same refrigerant system start performing fan operation simultaneously.
* If a unit number that cannot be recognized by the unit is entered, 3 beeps of 0.4 seconds will be heard. Reenter the unit number
setting.
* If the signal was not received by the sensor, you will not hear a beep or a “double beep” may be heard. Reenter the unit number
setting.
4 Select a mode.
Press the temp button to set a mode. Press “24” to turn on the function that raises the set temperature by 4 degree
during heat operation. Direct the wireless remote controller toward the sensor of the indoor unit and press the button.
The sensor-operation indicator will flash and beeps will be heard to indicate the current setting number. Current setting number: 1 = 1 beep (one second)
2 = 2 beeps (one second each)
* If a mode number that cannot be recognized by the unit is entered, 3 beeps of 0.4 seconds will be heard. Reenter the mode
number.
* If the signal was not received by the sensor, you will not hear a beep or a “double beep” may be heard. Reenter the mode
number.
5 Select the setting number.
Press the temp button to select the setting number. (02: Not available) Direct the wireless remote controller toward the receiver of the indoor unit and press the button. The sensor-operation indicator will flash and beeps will be heard to indicate the the setting number.
Setting number: 1 = 2 beeps (0.4 seconds each)
* If a setting number that cannot be recognized by the unit is entered, the setting will turn back to the original setting.
6 Repeat steps 4 and 5 to make an additional setting without changing unit number. 7 Repeat steps 3 to 5 to change unit number and make function settings on it. 8 Complete the function settings
* Do not use the wireless remote controller for 30 seconds after completing the function setting.
* If the signal was not received by the sensor, you will not hear a beep or a “double beep” may be heard. Reenter the setting number.
Press button.
3 = 3 beeps (one second each)
2 = 2 beeps (0.4 seconds each, repeated twice) 3 = 2 beeps (0.4 seconds each, repeated three times)
46
8-2. FUNCTION SELECTION OF REMOTE CONTROLLER
The setting of the following remote controller functions can be changed using the remote controller function selection mode. Change the setting when needed.
Item 1
1.Change Language ("CHANGE LANGUAGE")
2.Function limit ("FUNCTION SELECTION")
3.Mode selection ("MODE SELECTION")
4.Display change ("DISP MODE SETTING")
Item 3 (Setting content)
• Display in multiple languages is possible.
• Setting the range of operation limit (operation lock)
• Setting the use or non-use of "automatic" operation mode
• Setting the temperature adjustable range (maximum, minimum)
• Selecting main or sub remote controller *
When two remote controllers are connected to one group, one controller must be set to sub.
• Setting the use or non-use of clock function
• Setting the timer type
• Contact number display in case of error
• Setting the telephone number
• Setting the temperature unit (: or °F) to display
• Setting the use or non-use of the display of indoor (suction) air temperature
• Setting the use or non-use of the display of "Cooling" or "Heating" display during
operation with automatic mode
Item 2
Language setting to display
(1)
Operation function limit setting (operation lock) ("LOCKING FUNCTION")
(2)
Use of automatic mode setting ("SELECT AUTO MODE")
(3)
Temperature range limit setting ("LIMIT TEMP FUNCTION")
(1)
Remote controller main/sub setting ("CONTROLLER MAIN/SUB")
(2) Use of clock setting ("CLOCK") (3) Timer function setting ("WEEKLY TIMER") (4) Contact number setting for error situation ("CALL.")
(1) Temperature display :/°F setting ("TEMP MODE :/°F") (2)
Suction air temperature display setting ("ROOM TEMP DISP SELECT")
(3)
Automatic cooling/heating display setting ("AUTO MODE DISP C/H")
[Function selection flowchart] Refer to next page. [1] Stop the air conditioner to start remote controller function selection mode. [2] Select from item1. [3] Select from item2. [4] Make the setting. (Details are specified in item3) [5] Setting completed. [6] Change the display to the normal one. (End)
➔➔
[Detailed setting] [4] -1. CHANGE LANGUAGE setting
The language that appears on the dot display can be selected.
• Press the [
MENU] button to change the language.
1 Japanese (JP), 2 English (GB), 3 German (D), 4 Spanish (E), 5 Russian (RU), 6Italian (I), 7Chinese (CH),8 French (F)
[4] -2. Function limit (1) Operation function limit setting (operation lock)
• To switch the setting, press the [ ON/OFF] button. 1 no1: Operation lock setting is made on all buttons other than
the [
ON/OFF] button.
2 no2: Operation lock setting is made on all buttons. 3 OFF (Initial setting value) : Operation lock setting is not made
* To make the operation lock setting valid on the normal screen, it is
necessary to press buttons (Press and hold down the [FILTER] and [ ON/OFF] buttons at the same time for two seconds.) on the normal screen after the above setting is made..
(2) Use of automatic mode setting When the remote controller is connected to the unit that has auto­matic operation mode, the following settings can be made.
• To switch the setting, press the [ ON/OFF] button. 1 ON (Initial setting value) : The automatic mode is displayed when
the operation mode is selected.
2 OFF : The automatic mode is not display
when the operation mode is selected.
[4] -3. Mode selection setting (1) Remote controller main/sub setting
• To switch the setting, press the [ ON/OFF] button.
1 Main : The controller will be the main controller. 2 Sub : The controller will be the sub controller.
(2) Use of clock setting
• To switch the setting, press the [ ON/OFF] button.
1 ON : The clock function can be used. 2 OFF:The clock function cannot be used.
(3) Timer function setting
• To switch the setting, press the [ ON/OFF] button (Choose one of the followings.).
1 WEEKLY TIMER (initial setting on MA deluxe):
The weekly timer can be used.
2 AUTO OFF TIMER: The auto off timer can be used.
SIMPLE TIMER (Default setting on MA smooth):
The simple timer can be used.
4
3
TIMER MODE OFF: The timer mode cannot be used.
* When the use of clock setting is OFF, the "WEEKLY TIMER" cannot be
used.
(4) Contact number setting for error situation
• To switch the setting, press the [ ON/OFF] button.
1 CALL OFF:
The set contact numbers are not displayed in case of error.
2 CALL **** *** **** : The set contact numbers are displayed in case
of error.
(3) Temperature range limit setting After this setting is made, the temperature can be changed within the set range.
• To switch the setting, press the [ ON/OFF] button. 1 LIMIT TEMP COOL MODE :
The temperature range can be changed on cooling/dry mode.
2 LIMIT TEMP HEAT MODE :
The temperature range can be changed on heating mode.
3 LIMIT TEMP AUTO MODE :
The temperature range can be changed on automatic mode. 4 OFF (initial setting) : The temperature range limit is not active. *
When the setting, other than OFF, is made, the temperature range limit setting on cooling, heating and automatic mode is made at the same time. However the range cannot be limited when the set temperature range has not changed.
To increase or decrease the temperature, press the [ TEMP ( ) or ( )] button.
To switch the upper limit setting and the lower limit setting, press the
[ ]
button. The selected setting will flash and the temperature can be set.
• Settable range
Cooling/Dry mode : Lower limit: 19 : ~ 30: Upper limit: 30 : ~ 19: Heating mode : Lower limit: 17 : ~ 28: Upper limit: 28 : ~ 17: Automatic mode : Lower limit: 19 : ~ 28: Upper limit: 28 : ~ 19:
CALL_ : The contact number can be set when the display is as
shown on the left.
• Setting the contact numbers To set the contact numbers, follow the following procedures. Move the flashing cursor to set numbers. Press the [
TEMP. ( ) and
(
)] button to move the cursor to the right (left). Press the [ CLOCK
(
) and ( )] button to set the numbers.
[4] -4. Display change setting (1) Temperature display :/ F setting
• To switch the setting, press the [ ON/OFF] button.
1 : : The temperature unit : is used. 2 F: The temperature unit
°
°°
F is used.
(2) Suction air temperature display setting
• To switch the setting, press the [ ON/OFF] button.
1 ON : The suction air temperature is displayed. 2 OFF:The suction air temperature is not displayed.
(3) Automatic cooling/heating display setting
• To switch the setting, press the [ ON/OFF] button. 1 ON : One of "A utomatic cooling" and "A utomatic heating" is display ed
under the automatic mode is running.
2 OFF:Only "Automatic" is displayed under the automatic mode.
47
Hold down the E button and press the D button for 2 seconds.
Hold down the
E button and press the D button for 2 seconds.
Remote controller function selection mode
E Press the operation mode button. G Press the TIMER MENU button. D Press the TIMER ON/OFF button.
Item1 Item2
Dot display
Item3
Room air temperature is not displayed.
One of "Automatic cooling" and "Automatic heating" is displayed under the automatic mode is running. (Initial setting value)
Only "Automatic" is displayed under the automatic mode.
Normal display (Display when the air condition is not running)
Change Language
Function selection
Mode selection
Display mode setting
Operation lock setting is not used. (Initial setting value)
Operation lock setting is except On/Off buttons.
Operation lock setting is All buttons.
The automatic mode is displayed when the operation mode is selected. (Initial setting value)
The automatic mode is not displayed when the operation mode is selected.
The temperature range limit is not active. (Initial setting value)
The temperature range can be changed on cooling/dry mode.
The temperature range can be changed on heating mode.
The temperature range can be changed on automatic mode.
The remote controller will be the main controller. (Initial setting value)
The remote controller will be the sub controller.
The clock function can be used. (Initial setting value)
The clock function can not be used.
Weekly timer can be used. (Initial setting value)
Auto off timer can be used.
Simple timer can be used.
Timer mode can not be used.
The set contact numbers are not displayed in case of error. (Initial setting value)
The set contact numbers are displayed in case of error.
The temperature unit
:
is used. (Initial setting value)
The temperature unit °F is used.
Room air temperature is displayed. (Initial setting value)
Flowchart of Function Setting
Setting language (English)
E
G
EN
GE
E
ES
RU
G
IT
ZH
FR
F
TEMP.
MENU
E
PAR-21MAA
G
MONITOR/SET
BACK DAY
CLOCK
ON/OFF
C
OPERATION
D
ON/OFF
FILTER
CHECK
CLEAR
I A
TEST
B
H
JA
D
OFF
D
on1
D
D
D
D
D
D
D
D
D
D
D
on2
ON
D
OFF
OFF
D
D
ON
D
OFF
D
G
G
E
G
G
G
G
E
G
G
G
D
D
G
G
D
D
D
G
G
D
D
D
OFF
D
CALL-
:
D
°F
ON
D
OFF
ON
D
OFF
48
9
Blowout direction
pattern
4-direction<Table 1> 3-direction 2-direction Note1.
For 3 and 2-directional, please use the air outlet shutter plate (option).
Pattern 1 Factory setting Pattern 4 One air outlet
fully closed
Pattern 6 Two air outlet
fully closed
Fresh air intake hole
Fresh air intake hole diagram
3 - {2.8 Burring hole
{125 Burring hole pitch
{100 (Cut out hole)
Refrigerant pipe Drain pipe
Ceiling surface
120
_
120_
w158
4-WAY AIR FLOW SYSTEM
9-1. PLACEMENT OF THE AIR OUTLETS
• For this grille, the blowout direction comes in 11 patterns. Also,by unit function setting by the remote controller, you can adjust the air flow and speed. Select the settings from Table according to the location in which you want to install the unit.
1) Decide on the pattern of the airflow direction.
2) According to the number of air outlets and height of the ceiling to install the unit, be sure to set the unit function setting by the remote controller.
Correspondence of ceiling heights to numbers of air outlets.
Ceiling height & discharge direction
(Unit : m)
PL-3AAK
Standard
High ceiling 1
High ceiling 2
4 direction 2.7m 3 direction 2 direction
PL-4, 5, 6AAK
4 direction
3 direction
2 direction
3.0m
3.3m 3.5m
Standard
High ceiling 1
3.2m
3.6m
4.0m 4.2m
3.0m
3.3m
3.6m
4.0m
3.5m
3.5m —
High ceiling 2
4.2m
4.2m —
9-2. FRESH AIR INTAKE (INSTALLATION OF SITE)
• At the time of installation, use the duct holes (cut out) located at the positions shown in following diagram, as and when required.
Note :
Be sure to add135mm to the dimensions in the diagram that are marked with a “w” if installing a multi function casement (Option)
4949
9-3. FIXING OF HORIZONTAL VANE
Standard of
horizontal position
Dimension A (mm)
26 29 33 37
Level 30°
(Min.)
Downward 45° Downward 55°
Downward 70°
(Max.)
w Dimension between 26mm and 37mm can be arbitrarily set.
Caution
Do not set the dimension out of the range.
It could cause dew drips and attain on ceiling, etc. and the unit may be damaged.
<Set range>
Horizontal vane of each air outlet can be fixed according to the environment, which is installed.
Setting procedure
1) Turn off a main power supply (Turn off a breaker).
2) Disconnect the vane motor connector of the direction of the arrow with pressing the unlocking button as shown in figure below.
Electricity insulate the disconnected connector with the vinyl tape.
Vane motor
Vane motor
Connector
Unlocking button
Horizontal vane
3) Set a vertical vane of the air outlet, which tries to fixed by the hand slowly within the range in the table below.
Measured standard
position of the grille
Horizontal vane
50
9-4. FRESH AIR INTAKE AMOUNT & STATIC PRESSURE CHARACTERISTICS
Q
0
B
A
C
1
Curve in the left praphs.
Duct characteristics at site
Q
A
EC
2
Q
Qa
AD
3
PL-3AAK
Multifunction casement + Standard filter
Multifunction casement + High efficiency filter
Static pressure [Pa]
50
0
1 2 3 4 5 6
-50
-100
-150
-200
Taking air into the unit
Static pressure [Pa]
50
0
1 2 3 4 5 6
-50
-100
-150
-200
1 intake
Air flow [m
2 intakes
Air flow [m
3
/min]
3
/min]
Static pressure [Pa]
50
0
-50
-100
-150
-200
How to read curves
1 2 3 4 5 6
1 intake
Q…Planned amount of fresh air intake A…Static pressure loss of fresh air
intake duct system with air flow amount Q
B…Forced static pressure at air condi-
tioner inlet with air flow amount Q
C…Static pressure of booster fan with
air flow amount Q
D…Static pressure loss increase
amount of fresh air intake dust sys­tem for air flow amount Q <Pa>
E…Static pressure of indoor unit with air
flow amount Q
Qa…Estimated amount of fresh air
intake with out D <m3/min>
Air flow [m
2 intakes
3
/min]
<m
3
/min>
<Pa>
<Pa> <Pa>
<Pa>
PL-4 / 5 / 6AAK
Multifunction casement + Standard filter Multifunction casement + High efficiency filter
Static pressure [Pa]
50
0
1 2 3 4 5 6 7 8 9
-50
-100
-150
-200
Taking air into the unit
Static pressure [Pa]
50
0
1 2 3 4 5 6 7 8 9
-50
-100
-150
-200
2 intakes
1 intake
Static pressure [Pa]
Air flow
3
[m
/min]
Air flow [m
3
/min]
50
-50
-100
-150
-200
0
1 2 3 4 5 6 7 8 9
1 intake
Air flow
3
/min]
[m
2 intakes
51
Fresh air intake hole
Refrigerant pipe Drain pipe
Branch duct hole (Cut out hole)
Branch duct hole diagram (view from either side)
Branch duct hole
{175
Burring hole pitch
{150 Cut out hole
14 - {2.8 Burring hole
350
90
70_
100 100 90
100
130
w155
w167
Branch duct hole
Indoor controller board
Be sure to secure insulation material by tape and such
5
Green
Yellow Orange
Connector (5P)
Package side
Multiple remote controller adapter PAC-SA88HA-E
Be sure to secure insulation material by tape and such
Installation at site
CN51 on indoor unit board
Red
Brown
1
MB
~
Multiple remote controller adapter PAC-SA88HA-E
Distance between indoor controller board and relay must be within 10m.
CN51
9-5. INTERLOCKING OPERATION METHOD WITH DUCT FAN (Booster fan)
Whenever the indoor unit is operating, the duct fun operates.
(1)Connect the optional multiple remote controller
adapter(P AC-SA88HA-E) to the connector CN51 on the indoor controller board.
(2)Drive the relay after connecting the 12V DC relay
between the Yellow and Orange connector lines. Use a relay under 1W.
MB: Electromagnetic switch power relay for duct fan.
X: Auxiliary relay (12V DC LY-1F)
9-6. BRANCH DUCT(Installation at site)
Discharge by branch duct becomes possible by installing a branch duce at site. Knockout holes on the wall panel of the indoor unit must be removed.
9-6-1 BRANCH DUCT INSTALLATION PROCEDURE
At the time of installation, use the duct holes (cut out) located at the positions shown in following diagram, as and when required.
Note : The figure marked with wwin the drawing represent the dimensions of the main unit excluding those of the optional
multi function casement. When installing the optional multi function casement, add 135 mm to the dimensions marked on the figure. When installing the branch ducts, be sure to insulate adequately. Otherwise condensation and dripping may occur.
Fig 1. Branch duct mounting position Fig 2. Branch duct connection details
52
9-7. AIR FLOW & STATIC PRESSURE CHARACTERISTICS OF BRANCH DUCT (with SWA at “Standard”)
Static
pressure
[Pa]
Air flow [m
3
/min]
30
20
10
0
123456
Hi
Lo
Static
pressure
[Pa]
Air flow [m
3
/min]
30
20
10
0
123456
Hi
Lo
Static
pressure
[Pa]
Air flow [m
3
/min]
50 40 30 20 10
0
123
Hi
Lo
45678910
Static
pressure
[Pa]
Air flow [m
3
/min]
50 40 30 20 10
0
123
Hi
Lo
45678910
Static
pressure
[Pa]
Air flow [m
3
/min]
50 40 30 20 10
0
123
Hi
Lo
45678910
Static
pressure
[Pa]
Air flow [m
3
/min]
50 40 30 20 10
0
123
Hi
Lo
45678910
Static
pressure
[Pa]
Air flow [m
3
/min]
30
40
50
60
20 10
0
123456789
Hi
Lo
Static
pressure
[Pa]
Air flow [m
3
/min]
50
60
70
80
90
100
40 30 20 10
0
123
Hi
Lo
4567891011121314
Static
pressure
[Pa]
Air flow [m
3
/min]
50
60
70
80
90
100
40 30 20 10
0
123
Hi
Lo
4567891011121314
Static
pressure
[Pa]
Air flow [m
3
/min]
30
40
50
60
20 10
0
123456789
Hi
Lo
Static
pressure
[Pa]
Air flow [m
3
/min]
50
60
70
80
90
100
40 30 20 10
0
123
Hi
Lo
4567891011121314
Static
pressure
[Pa]
Air flow [m
3
/min]
50
60
70
80
90
100
40 30 20 10
0
123
Hi
Lo
4567891011121314
4 direction airflow (Horizontal vane) Angled duct
PL-3AAK
Rounded duct PL-3AAK
PL-4AAK
PL-5, 6AAK
3 direction airflow (Horizontal vane) Angled duct
PL-3AAK
PL-4AAK
PL-5, 6AAK
Rounded duct
PL-3AAK
PL-4AAK
PL-5, 6AAK
PL-4AAK
PL-5, 6AAK
53
2 direction airflow (Horizontal vane) Angled duct
PL-3AAK
100
90 80 70 60
Static
pressure
[Pa]
50 40 30 20 10
0
1234567891011
Lo
Air flow [m
Hi
3
PL-4AAK
120
110
100
90
[Pa]
80 70 60 50 40 30 20 10
0
Hi
Lo
123
4 5 6 7 8 9 101112131415 16
Air flow [m
Static
pressure
/min]
3
/min]
Rounded duct PL-3AAK
Static
pressure
[Pa]
PL-4AAK
Static
pressure
[Pa]
100
90 80 70 60 50 40 30 20 10
0
Lo
1234567
Air flow [m
120
110
100
90 80 70 60 50 40 30 20 10
0
123
Hi
3
/min]
Hi
Lo
4 5 6 7 8 9 101112131415 16
Air flow [m
3
/min]
PL-5, 6AAK
Static
pressure
[Pa]
120 110 100
90 80 70 60 50 40 30 20 10
0
Lo
123
4 5 6 7 8 9 101112131415 16
Air flow [m
PL-5, 6AAK
120
110
100
[Pa]
90 80 70 60 50 40 30 20 10
0
Hi
Lo
123
4 5 6 7 8 9 101112131415 16
Air flow [m
3
/min]
Hi
Static
pressure
3
/min]
54
SYSTEM CONTROL10
System Name System Diagram Features
Parts Required in Addition to Standard System
Components (Indoor/Outdoor Units, Remote Controller)
A.Remote control-
ler operation (Standard)
B.Remote control-
ler operation
Use of two con­trollers enables operation of the air conditioner both from a distance and nearby.
C.Group control
operation
Use of one remote controller to con­trol multiple air conditioners with the same settings simultaneously.
D.
Remote/handheld combined control operation
Allows start/stop of the air condi­tioner from a dis­tance, and prohib­its/permits start/ stop from remote controllers.
E.Operation by
external signal
F.
Control and remote
display by external signal (extraction of monitor signal)
Enables you to display the op­eration state and control start/stop from a distance.
• There are two types of remote controllers: wired type and wireless type.
• Simultaneous twin indoor units are started or stopped simultaneously.
• Up to two remote controllers can be connected to one group.
• Simultaneous twin units are counted as each unit.
• Operation control by the latest command (last en­tered priority)
• Wired and wireless remote controllers can be com­bined as a pair.
• One group can consist of up to 16 indoor units, and they can be started sequentially by connecting the remote controller to them and assigning an address to each inter face.
• Simultaneous twin units are counted as one unit.
• All the units belonging to the same group are oper­ated in the same mode, but thermostats can be turned ON/OFF individually for each indoor unit.
• Up to two remote controllers can be connected.
• All the air conditioners can be turned ON/OFF collectively from a distance.
• Operation can be switched between the remote operat­ing panel and handheld controller.
• Operations (e.g., temperature adjustment, airflow, air­flow direction) except for start/stop operations can be performed even if the remote controller is being oper­ated.
• In the case of simultaneous twin, triple and quad units, connect the controller to one indoor unit only. If con­nected to two or more indoor units, an error (operation stop) may occur.
• Control by an external timer is possible by connecting it.
• Use of optional "remote operation adapter" enables remote control via relay. (Level signal)
Extraction of non-voltage contact output
• Use of optional "remote operation adapter" and "remote display panel" (Part to be provided at your site) pro-vides non-voltage contact outputs of signals (operation, error) and operation/stop input function.
Extraction of DC12 V contact output
• Use of optional "remote display adapter" and "re­mote display panel"
(Part to be provided at your site)
provides
DC12 V
contact outputs of signals (operation
,
error) and operation/stop input function.
* One of the wired remote con-
trollers must be set as a sub remote controller.
Wired remote controller (addi­tional) (PAR-21MAA)
Inter face MAC-397IF-E
Remote ON/OFF adapter (PAC-SE55RA-E) Relay box (Part to be provided at your site) Remote operating panel (Part to be provided at your site)
Remote ON/OFF adapter (PAC–SE55RA-E)
A-control operation display kit (PAC-SF40RM-E) Remote display panel (Part to be provided at your site)
Remote display adapter (PAC-SA88HA) Remote display panel (Part to be provided at your site)
10-1. VARIETY OF SYSTEM CONTROL FUNCTIONS
Indoor unit
Outdoor unit
Remote Controller
Relay box
Indoor unit
Remote Controller
Remote operating panel
Remote Controller
Indoor unit
Remote Controller
Inter face Indoor
unit Outdoor unit
Remote
display kit
Indoor unit
Remote Controller
Remote display (operation, error)
55
System Name System Diagram Features
• Weekly timer: In addition to ON/OFF, up to eight temperature patterns can be set for each day of the week.
G. Timer operation
Enables control of start and stop.
* For control by
external timer, refer to Remote/ handheld com­bined control op­eration".
* Only one timer can be selected; the auto off, simple
and weekly timers cannot be combined.
• Simple timer: Start and stop operations can each be
performed once within 72 hours (can be set in 1-hour increments).
• Auto off timer:Operation is stopped when the preset
time elapses following the start of operation. The time can be set from 30 minutes to 4 hours in 30-minute increments.
* Only one timer can be selected; the simple and auto
off timers cannot be combined.
Parts Required in Addition to Standard System
Components (Indoor/Outdoor Units, Remote Controller)
MA Remote controller (PAR-21MAA)
H.Interlock opera-
tion with periph-
eral equipment
Enables control of Mitsubishi Lossnay ventilator by remote controller.
I.Rotation
Lossnay ventilator
Main
Remote Controller
Sub
Indoor unit
Remote Controller
Indoor unit
Outdoor unit
• Connecting a Lossnay ventilator and an indoor unit enables control of interlock/solo ventilation opera­tion and airflow. (Only the microcomputer type Lossnay ventilator can be used.)
When abnormality occurs while operating, it changes into operating the back up unit, and operating is continued. (Unit function Mode No. 20 setting No.3 , Indoor controller board SW-5-4 ON) Main / Sub setting Main : Indoor controller board SW5-3 : OFF Sub : Indoor controller board SW5-3 : ON
Each system operates alternately for 24 hours or 168 hours. (Unit function Mode No. 20 setting No.1: 24 hours/No.2 : 168 hours, Indoor controller board SW 5­4 ON) Main / Sub setting Main : Indoor controller board SW5-3 : OFF Sub : Indoor controller board SW5-3 : ON
This system can correspond only by the pattern of two refrigerant group by 1 : 1 (indoor and outdoor unit combination) systems.
56
10-2. ONE REMOTE CONTROLLER (STANDARD) OPERATION
Slim Air Conditioners System
Remote controller connection circuit (Controller cable)
Outdoor unit OC
Indoor unit IC
Wired remote controller R
Indoor/Outdoor connection cable
Remote controller cable
OC
IC-1
R
IC-2
2
2
OC
IC-1
R
2
2
Standard 1:1 Simultaneous Twin Indoor controller board switch setting
SW5-3
OFF
ON
Indoor unit IC
IC-1 (Main)
IC-2 (Sub)
OC IC
1 2
LN
Power source wiring
1 2
1 2
1 2
R
(No polarity)
Outdoor unit Indoor unit Remote controller
Power source wiring
(Polarity)
Slim Air Conditioners System
Remote controller optical receiver section connection circuit
Outdoor unit OC
Indoor unit IC
Wireless remote controller receiver section R'
Indoor/Outdoor connection cable
Wireless remote controller cable
Wireless remote controller cable
Remote controller cable
OC
IC-1
R'
IC-2
2
2
9
OC
IC-1
R'
2
9
Standard 1:1 Simultaneous Twin Indoor controller board switch setting
SW5-3
OFF
ON
Indoor unit IC
IC-1 (Main)
IC-2 (Sub)
CN90
Controller board
Indoor unit IC
9
CNB
12
Wireless remote controller
optical receiver section R’
Remote controller cable terminal block
(1) One Wired Remote Controller
(OC: Outdoor unit IC: Indoor unit R: Remote controller (for wireless type: optical receiver adapter)
(Reference)
11
If simultaneous twin connect the remote controller to indoor units. Can control all functions of the indoor unit even if dif-
ferent models (different types) are mixed. Note that there may be some restrictions of the functions.
22
Electrical wiring diagram
• Power supply terminal block L, N
• Indoor/outdoor connection cable terminal block 1,2 (Polarity)
• Remote controller cable terminal block 1,2 (No polarity)
(2) Wireless remote controller
(Reference)
11
If simultaneous twin connect the remote controller to indoor units. Can control all functions of the indoor unit even if dif-
ferent models (different types) are mixed. Note that there may be some restrictions of the functions.
22
Electrical wiring diagram
57
10-3. TWO-REMOTE CONTROLLER OPERATION
(1) Two Wired Remote Controllers
Slim Air Conditioner System
Outdoor unit OC
Indoor unit IC
Remote controller connection circuit (Controller cable)
Wired remote controller R
Outdoor unit OC
Indoor unit IC
Wired remote controller R
[Reference] 1 In the case of free component multi type systems consisting of simultaneous twin units, connect the remote controllers to each indoor unit.
All the functions of the connected indoor units can be controlled even if the system consists of different models. However, some function may be restricted.
2 In the case of free component multi type systems consisting of simultaneous twin units, the indoor units should be connected by crossover wiring. 3 Set one of the remote controllers as the main controller (factory setting) and the other as the sub controller using the remote controller's function
selection.
Standard 1:1 Simultaneous Twin
Remote controller cable
OC
IC
R-1
OC
2
IC
2
2
R-1
2
2
R-2
2
R-2
Indoor/outdoor connection cable
(R: Wired remote controller)
OC
2
IC-1
R-1
OC
2
IC-1
2
R-1
IC-2
2
2
2
R-2
IC-2
2
2
R-2
Indoor controller board switch setting
SW5-3
OFF
ON
Indoor unit IC
IC-1 (Main)
IC-2 (Sub)
(2) Two Wireless Remote Controllers
Slim Air Conditioner System
Outdoor unit
Remote
OC
controller receiver
Indoor unit IC
connection circuit
Wireless remote controller re­ceiver section R'
Standard 1:1 Simultaneous Twin
(R': Wireless remote controller receiver)
Indoor/outdoor connection cable
Receiver connection cable
OC
2
IC-1
9 9
R'-1
Remote controller cable
IC-2
2
Indoor controller board switch setting
SW5-3
OFF
ON
R'-2
Indoor unit IC
IC-1 (Main)
IC-2 (Sub)
* Numbers given in ( ) apply when power is supplied to the indoor and outdoor units separately. [Reference] 1 In the case of free component multi type systems consisting of simultaneous twin units, connect two wireless remote controller receivers
(one each) to any two of the indoor units. All the functions of the connected indoor units can be controlled even if the system consists of different models. However, some functions may be restricted.
2 In the case of free component multi type systems consisting of simultaneous twin units, the indoor units should be connected by crossover wiring.
In the case of "standard 1:1" connection, it is not possible to connect two remote controller receivers to the indoor units. However, with systems
3
consisting of simultaneous twin units, it is possible to connect a remote controller receiver to two indoor units. In this case, all the pair numbers will be "0" (factory setting, no change necessary), and all the units will be turned ON/OFF simultaneously.
4 When using two or more wireless remote controllers, the display contents on the remote controllers may differ from the actual settings, since the
operation made last by any of the remote controllers will be effective.
(3) One Wired and One Wireless Remote Controller
Indoor controller board switch setting
SW5-3
OFF
ON
Indoor unit IC
IC-1 (Main)
IC-2 (Sub)
Slim Air Conditioner System
Outdoor unit
Remote
OC
controller receiver
Indoor unit IC
connection circuit
•Wired remote controller R
•Receiver R'
(R: Wired remote controller, R': Wireless remote controller receiver)
Standard 1:1 Simultaneous Twin
Indoor/outdoor connection cable
Remote controller cable
OC
3(2)
IC
Receiver connection
9
2
cable
R
R'
OC
IC-1
2
IC-2
2
9
2
R
R'
[Reference]
In the case of free component multi type systems consisting of simultaneous twin units, connect both the wired remote controller and wireless
1
remote controller receiver to any one of the indoor units. All the functions of the connected indoor units can be controlled even if the system consists of different models. However, some functions may be restricted. In the case of free component multi type systems consisting of simultaneous twin units, the indoor units should be connected by crossover wiring.
2
When using two or more wireless remote controllers, the display contents on the remote controllers may differ from the actual settings, since the
3
operation made last by any of the wireless remote controllers will be effective.
58
10-4. GROUP CONTROL OPERATION
(COLLECTIVE OPERATION AND CONTROL OF MULTIPLE REFRIGERANT SYSTEMS (2 to 16))
Group control can be operated by using MAC-397IF-E. The setting of wired remote controller is subjected to variation according to the function of the indoor unit. (for mode operation, setting temperature, fan step, air direction) The display of remote controller and operating the indoor unit might be different. Neither the test run nor the function setting can be done by MA remote controller connected with MAC-397IF-E.
1.Connecting the MA& CONTACT TERMINAL Interface to the Indoor Unit
• Connect the interface unit and the indoor control board using the connecting cable that came with the interface.
• Extending or shortening the connecting cable that comes out of the interface may cause it to malfunction. Also, keep the connecting cable as far as possible away from the electrical wires and ground wire. Do not bundle them together.
INDOOR
CN105
or
CN92
Indoor control board
Connect the connecting cable that comes with the interface unit to the connector CN105 or CN92 on the indoor control board.
2.Connecting the remote control interface with each system
(For details on each system, see the relevant instruction manual.)
• Replace the interface unit mounting cord clamp with a supplied mounting cord clamp based on the thickness of the connecting cable used for each system.
Interface unit mounting cord clamp or mounting
Mounting screws (black) 3.5 o 12
Connecting cable for each system
cord clamps
• The cables connected to the Indoor unit should be mounted on or near the Indoor unit. If the connecting cable is not securely mounted, the connector may detach, break, or malfunction.
Mounting screws 4 o 10
Electrical wire mounting
Mounting cord clamp
bracket
Mounting screws 4 o 16
Mounting cord clamp
• Set the interface dip switch (SW500–502) settings before turning on the power.
• If the interface dip switch (SW500–502) settings are not set correctly, the system will not function properly.
59
Use as a Wired Remote Control (Using the MA Remote Controller)
Note:
1. Be sure the Auto Heating/Cooling Display Setting on the MA remote controller is set to OFF before use.
• For information on how to set the Auto/Heating Cooling Display Setting, see the MA remote controller instruction manual.
• The actual operating status of the unit may differ from what is shown on the remote controller display
2. A test run cannot be initiated using the test run switch on the MA remote controller..
3. The horizontal vanes on the unit cannot be operated using the louver switch.
4. The range of room temperature indication is between 10: and 38:.
Indoor unit
Interface unit
CN560
TB580 1 2 A B
Remote control cord that came with the MA remote controller (Non polarity)
2
MA remote controller (PAR-21MAA) * PAR-20MAA cannot be used
with this interface.
Dip switch settings
SW500 does not have to be set.
SW501: SW501- No. 1-4: Refrigerant address
• Set this switch when multiple indoor units (and remote control interfaces) are connected to a single MA remote controller.
• Always start the refrigerant address at "0". Even when connecting multiple outdoor units, set a different refrigerant address for each indoor unit.
Refrigerant address
0
1
2
15
1
112
3333
4
Refrigerant address "0"
5
1Outdoor unit 2Outdoor unit 3Indoor unit 4Interface 5MA remote controller
44
Refrigerant address "1"
Refrigerant address "2"
ON
1
ON
1
ON
1
ON
1
2 3 4
2 3 4
2 3 4
2 3 4
SW501- No. 5–6
ON
No. 5 should normally be set to OFF. Under the following conditions, No.6 should normally be set to ON.
6
5
When the model of Mr. SLIM exists in the same group, it sets it to turning ON.
Set them to ON only when using the room temperature sensor installed in the MA remote controller. * This can be switched when an accurate room temperature cannot be detected by the air conditioner unit. PL-AAK series do not have a room temperature sensor on their MA remote controllers.
60
SW501: Settings to accommodate MA remote controller and settings to accommodate outdoor units
SW No.
No. 1 No. 2 No. 3 No. 4
Functions OFF ON Comments
Only specify these settings when connecting an MA remote controller.
Functions Room temperature detector The model of Mr. SLIM exists in the
same group.
This should normally be set to ON.
ON
1
2 3 4 5 6
ON
1
2 3 4 5 6
ON
1
2 3 4 5 6
ON
1
2 3 4 5 6
ON
1
2 3 4 5 6
ON
1
2 3 4 5 6
ON
1
2 3 4 5 6
ON
1
2 3 4 5 6
ON
1
2 3 4 5 6
ON
1
2 3 4 5 6
ON
1
2 3 4 5 6
ON
1
2 3 4 5 6
ON
1
2 3 4 5 6
ON
1
2 3 4 5 6
ON
1
2 3 4 5 6
ON
1
2 3 4 5 6
Refrigerant address 0
Refrigerant address 1
Refrigerant address 2
Refrigerant address 3
Refrigerant address 4
Refrigerant address 5
Refrigerant address 6
Refrigerant address 7
Refrigerant address 8
Refrigerant address 9
Refrigerant address 10
Refrigerant address 11
Refrigerant address 12
Refrigerant address 13
Refrigerant address 14
Refrigerant address 15
OFF Indoor unit Not mixed
ON Remote control Mixed
Comments
This should normally be set to OFF.
SW No.
No. 5 No. 6
61
SW502 : Air Conditioner Function Settings
SW No.
No. 1
No. 2
No. 3
No. 4
Cooling only type/ Heat pump type
Auto mode
Fan speed
Functions
OFF
Heat pump type
Not available
(setting No.3 disabled)
Available
(unit)
4 speeds
ON
Cooling only type
Available
(setting No.3 enabled)
Available
(remote controller)
3 speeds (2-speed
model set ON)
Comments
Set the mode in accordance with the operation manual for the indoor unit.
Heat pump type : Set to ON. Cooling only type : Set to OFF.
Set to OFF. When operating a 2-speed model with the 3-speed
setting (ON), the MA remote controller display will indicate 3 fan speeds. The table below shows the displays and the actual outputs at that time.
Display Meaning Indoor unit output
Low speedLow speed
Medium speed High speed
High speed
High speed
No. 5
Vane
No. 6
Swing
No. 7
Not in use
No. 8
Fan mode
* Fan speed 2 step model : An actual fan speed is 2 step though the display of remote controller becomes 4 step or 3 step.
Available
Available
Not available
Not available
Not available
Available
The Vane function of either of indoor unit : When the function is provided, it is Available (OFF). When the function is not provided, it is Not available (ON).
The Swing function of either of indoor unit : When the function is provided, it is Available (OFF). When the function is not provided, it is Not available (ON).
Permanently set to OFF. Set to ON.
3. Test Run (Check Operations)
Interface status monitor
You can check the status of the interface by the LED lamp on the interface unit board.
LED lamp no.
LED521
LED522
LED523
DC 12 V is not being supplied from the air conditioner.
Device is not communicating properly with the air conditioner.
Device is not communicating properly with the MA remote controller.
Lamp off
Lamp on
DC 12 V is being supplied from the air conditioner.
Blinking at approx. 1 second intervals: Device is communicating normally with the air conditioner.
Blinking at approx. 8 second intervals: Device is com­municating normally with the MA remote controller.
* Use the table above to check the device operations.
4. Mounting the Remote Control Interface Unit
Blinking
The Interface unit should be placed in a location where the connecting cable from the interface can reach an indoor unit. The device will not function properly if the connecting cable is extended so the connecting cable should not be extended. Mount the interface unit securely to a pillar or wall using 2 or more screws.
When Using Wall Mounting Brackets
2
1
Attach the wall mounting brackets to the interface unit
Mount the unit to a pillar or wall using 2 mounting screws.
using 2 mounting screws.
Interface unit
Wall mounting brackets
Mounting screws
Mounting screws
Cord clamp for wiring
Mounting screws
62
When Mounting Directly to a Wall
Mount the interface unit case to the wall using the mounting screws.
Interface case mounting screws
Mounting screws
* When mounting the interface unit using a cushioning
material , be sure to mount it in a location where it will not fall.
Interface unit
Cushioning material
When mounting the interface unit inside a ceiling or wall, install an access door to facilitate mainte­nance.
When the interface unit is mounted above an indoor unit, it should be positioned 40 mm or more away from the unit to ensure that ceiling grills can be removed.
40 mm or more
Attach the interface unit connecting cable here. Store extra connecting cable in the ductwork space behind the indoor unit.
* If there is any slack in the connecting cable, use a
fastener to keep it in place.
63
10-5. POWER OUTAGE AUTOMATIC RECOVERY OPERATION
Indoor unit Indoor unit Indoor unit
Remote controller
Control room room 1 room 2 room 3
Indoor unit
Relay box Relay box Relay box
Indoor unit
Control circuit power supply
Indoor unit Indoor unit
Remote controller
Remote/Hand-held selection switch
Control room W
room 1 room 2 room 3
Remote controller
Remote controller
Remote controller
• Whenever a power outage or switching of the power supply causes the power supply of an operating air conditioner to go from OFF to ON, this function will automatically restore the operation of the air conditioner to its previous operating mode.
w If the power is turned from OFF to ON when the air conditioner is not in operation, the air conditioner will not automatically
be turned on. However, the timer operation will be cancelled if the air conditioner is in timer operation (including when the unit is waiting for its start time). Setting for timer operation must be performed once again.
• If there is a momentary power outage of less than one second while the air conditioner is in operation, there may not be a clear determination of whether or not there was a power failure. When it has been determined that there has been a power failure, recovery will take approximately four minutes after the power is restored. Please wait. (Once "PLEASE WAIT" has appeared on the display, a protection system will operate to prevent the unit from restarting for three minutes.) When it has been determined that there has been no power failure, operation will continue as is.
• Settings can be made by function selections from the remote controller.
• When there is group control, selection of all refrigerants is required.
10-6. INDIVIDUAL CONTROL OPERATION FROM A SEPARATE ROOM
• By simply centralizing the remote controllers installed in each room in a separate control room, individual control or central­ized monitoring of the air conditioners in each room can be attained.
• Air conditioner control can be performed up to a total of 500 meters away by connecting the indoor units and remote con­trollers with 0.3 to 1.25 mm22-core cable.
• If a remote controller is installed in a room and control room, refer to the section on operating with two remote controllers.
10-7. COMBINED REMOTE/HAND-HELD CONTROL
• Operation/remote controller prohibit/ stop can be controlled from a remote location by routing the remote stop/start adapter (PAC-SE55RA-E sold separately) through the relay box installed on site. When this remote control is cancelled, the hand­held remote controller can be used for operating and stopping the air conditioner.
1. Basic system wiring
• Use the remote start/stop adapter (PAC-SE55RA-E) and connect the "Start/Stop Circuit From Remote Location" that comes from the relay box and remote/hand-held selection switch and connect it to the CN32 connector on the printed circuit board for the indoor unit
<Points of precaution>
11
Match the rated power supply voltage of the remote/hand-held selection switch and relay (X2) with the power supply for the
controller.
22
When performing group control of multiple outdoor unit using a timer, be sure to arrange the timer so that all units do not start
at the same time. If this is not performed, all of the units will start at one time creating an over current that will cause the circuit breaker to operate.
33
An on-delay system is one that includes specifications for operating a limited time when an on signal is received and has a tem-
porary off timer for recovery operations.
44
Use a connecting relay when the wiring length exceeds 10 meters, such as when performing remote wiring. If this is not pro-
vided, abnormal operation will occur.
(1) System diagram
W The AC for the control room is usually disconnected from the remote/hand-held control system.
64
Control circuit power supply
Dedicated short circuit prevention device
Remote/Hand-held selection switch
No.1 unit relay box
No.2 unit relay box
3 Relay box
2
Adapter for
remote start/stop
1
Remote/Hand-held
selection switch
T Timer
(On delay system)
X Relay
Model PAC-SE55RA-E (Sold separately)
(Example) Single polarity single-throw switch (125V rating)
To next unit
T
Brown
Red
X
2 X2
T
One method of easily distinguishing the on/off status of SW1 and SW2 is to use together with a "illuminated switch R" or pilot lamp.
T
X
2
SW1 SW2
T
X
2
Orange Orange
Brown
Red
Starting/stopping with remote controller disabled.
• Starting/stopping by remote operation enabled.
Starting/stopping with remote controller disabled.
• AC is in operation.
• Starting/stopping by remote operation enabled.
Starting/stopping with remote controller disabled.
• Starting/stopping by remote operation enabled.
Starting/stopping with remote controller disabled.
• AC is in operation.
• Starting/stopping by remote operation enabled.
Remote control
OFFON
Description of functions
OFFON
SW1 SW2
OFFON
Remote/Hand-held selection switch
(2) Basic wiring diagram
Indoor unit circuit board
CN32
Orange Red
Brown
On site wiring On site wiring
On site wiring
Timer
Timer
For remote operation
On site wiring
On site wiring
This is not used. Protect exposed wire by wrapping with insulating tape
On site wiring
SW1
Indoor unit circuit board
CN32
Orange Red
Brown
SW1 SW2
Indoor unit circuit board
CN32
Orange Red
Brown
SW2
Indoor unit circuit board
CN32
Orange Red
Brown
SW2
Indoor unit circuit board
CN32
Orange Red
Brown
Indoor unit circuit board
CN32
Orange Red
Brown
SW2
For remote operation
For timer operation
(3) Part specifications
Note: When using group address, connect to refrigerant
address "0" on the inside.
2. Examples of system applications
In any of the following examples, there is a five to six second delay from the time the operating command is issued until the operation begins. 1 This is when starting and stopping is performed by remote operation or external timer and when starting and stopping by
the remote controller is to be prohibited.
2 This is when starting and stopping is performed by remote operation or external timer and when starting and stopping by
the remote controller is to be separated.
3 This is when starting and stopping is performed by remote operation and then allowing starting or stopping by remote con-
trol at any time.
4 This is when permitting or prohibiting operation by remote controller is performed by external circuit.
Use momentary switch for SW2. (Manual operation/automatic recover switch on time is more than one second.) Press SW2 (on time is more than one second) and operation starts. After this has been done, stopping or restarting can be down by remote controller.
65
If SW2 is on, operation by remote controller cannot be performed. If SW2 is off, operation by remote controller is permitted.
10-8. OBTAINING REMOTE DISPLAY
CN90 CN1
CN41
Wireless
3
TB3
External input
TB2
Error
TB1
Operation
2
A control indoor control circuit board A control operating display kit
5
External input
Error output (No voltage momentary "a" contact)
Operating output (No voltage momentary "a" contact)
No voltage (Momentary "a" contact)
HA
Power supply for controller
Timer control
panel (on-site)
Remote controller
Indoor unit
Remote controller
Indoor unit
Remote controller
Indoor unit
Use the Acontrol operating display kit (PAC-SF40RM-E) to provide operation/error non-voltage contact output and on/off input function.
(1) Wiring method
..
Caution
TB3 is a dedicated terminal for contact point input. Never input voltage. It will damage the indoor control circuit board.
<Connections on the indoor unit side>
1 When using external output function
Insert the 9-prong connector (3-core) of the attached cable to CN90 on the indoor control circuit board.
2 When using the external input function
Insert the 4-prong connector (2-core) of the attached cable to CN41 on the indoor control circuit board. W The connector is direction-sensitive. Use care not to make an error when inserting.
Never force the connectors. This will result in damage.
(2) Locally procured parts
Item Name Model and specifications
External output function External output signal wire Use sheathed vinyl coated cord or cable.
Wire type: CV, CVS or equivalent. Wire size: Stranded wire 0.5mm
2
to 1.25mm
Single straged: {0.65mm to 1.25mm
Display lamp, etc. No voltage “a” contact AC200V (DC30V), 1Aor less
External input function External input signal wire Use sheathed vinyl coated cord or cable.
Wire type: CV, CVS or equivalent. Wire size: Stranded wire 0.5mm2to 1.25mm
Single straged: {0.65mm to 1.2mm
Switch No voltage “a” contact
(Start and stop operation is switched by inputting a pulse of 200ms or more)
2
2
10-9. TIMER OPERATION
Timer operation can be performed by setting the wired or wireless remote controller timer. Start and stop times can be set in 10-minute increments within a 24-hour period.
When used in combination with the central control remote controller of the M-NET control system for the outdoor unit, one program timer can be used for individual timer settings for each group of the central control system. (Each timer setting can be stored in data memory so timer settings for up to 50 groups can be set individually.)
W Please refer to the MELANS catalog or technical information for details about the central control remote controller.
1.Operating with on-site timer
(1) Summary of system
If the “Remote ON/OFF adapter” (PAC­SE55RA-E) (sold separately) is used, the on-site timer can be operated to turn each unit on and off.
66
(2) Basic pattern for timer control
Orange
As selected by remote controller operation switch.
From indoor unit
Red Brown
T
SW ON SW OFF
Timer control Remote controller control
SW
Orange
From indoor unit
Red Brown
T
Wiring diagram
Control circuit board
Slim indoor unit
Lossnay
Lossnay linkage
(PAC-SB81VS)
External control
input terminal
block
1 2
3
Connector
(CN2L)
Basic wiring
X: Relay (DC12V) CN25 (Indoor unit circuit board)
System example
Remote controller
Indoor unit
Relay box (On-site tinstallation)
Relay box
(On-site tinstallation)
Remote controller
Humidifier unit
Humidifier
unit
Use a no-voltage contact point output timer (one that has separate circuits for the load side and timer power supply). a) Timer-independent control b) Combined control by timer and remote controller
(3) Basic system
Refer to 10-7 COMBINED CONTROL BY REMOTE / HAND-HELD CONTROL.
10-10. LINKED OPERATION WITH PERIPHERAL AIR CONDITIONERS EQUIPMENT
Lossnay operation
Linked operation with a Lossnay unit can be obtained by connecting Lossnay linkage cable (Model PAC-SB81VS - sold
separately) to the CN2L (Remote kit) on the circuit board of the indoor unit. This function must be selected from the remote controller.
1 Summary of wiring
Connect the Lossnay linkage cable (Model PAC­SB81VS) connector to CN2L on the indoor unit on the circuit board of the indoor unit.
Connect the lead wire of the Lossnay linkage cable to the Lossnay external control input terminal blocks (1) and (2). (At this time, the input terminal blocks (1) and (2) have no polarity.)
2 Precautions when wiring
The Lossnay linkage cable can be extended up to a maximum of 500 meters. When extending the Lossnay linkage cable, be sure to connect securely and take proper steps to ensure insulation. (Extension cable specifications: Sheathed vinyl cord or cable 0.5 to 0.75mm
Lossnay linked cable
Arrange wiring so that there can be no contact between the Lossnay linkage cable and the power supply cord. Contact
may cause malfunctioning. (Separate by 5cm or more.)
2
)
10-11. OBTAINING HUMIDIFIER SIGNAL
10-12. EXTERNAL MOUNTING OF TEMPERATURE SENSOR
The humidifier signal that is linked to the AC heating operation (indoor unit ventilator) can be obtained by connecting the adaptor for the humidifier signal to connector CN25 on the printed circuit for the indoor unit and wiring it to the humidifier unit via the on-site relay box. There is no output when the thermostat is off, during heating preparation and during defrosting.
W Please consult your nearest Mitsubishi Electric
representative for information about obtaining the adapter for humidifier signal.
Temperature control from an alternative external location can be performed by connecting the temperature sensor (Model PAC-SE41TS-E - sold separately) to the CN20 connector on the circuit board for the indoor unit.
The wired remote controller also has an internal temperature sensor. Function selection from the remote controller is required. Refer to “FUNCTION SETTING” for information of installation manual about selecting functions with the remote controller.
67
10-13. MULTIPLE REMOTE CONTROL DISPLAY
CN51
connector(5P)
GREEN
Power supply
Electrical insulation is needed.
Wiring at the actual place
Optional multiple display adapter
The maximum distance between indoor board and relay is 10m.
YELLOW ORANGE
RED
BROWN
5
X2
X2
GL
RL
X1
X1
1
<Wiring >
Power supply
Remote controller cable
Relay box (Field supply)
Remote controller
Remote controller
Remote controller
3wires 3wires 3wires
2wires
No.1 unit No.2 unit No.3 unit
Muitiple remote control ON-OFF display (Field supply)
(Operation check)
<System>
Power supply
RL-1 GL-1
Multiple Remote Control Display
Multiple remote controller adapter
connect to the connector CN51
Relay box
5
X1-1
X2-1
1
<Wiring diagram>
RL-2 GL-2
RL-3
No.1 unit
GL-3
X1-1
X2-1
X1-2
X1-3
X2-3
X2-2
5
1
No.2 unit
5
1
No.3 unit
X1-2
X2-2
X1-3
X2-3
Be sure to secure insulation material by tape and such
5
Green
Yellow
Orange
Connector (5P)
Package side
Multiple remote controller adapter PAC-SA88HA-E
Be sure to secure insulation material by tape and such
Installation at site
CN51 on indoor controller board
Red
Brown
1
~
MB
Indoor controller board
CN51
You can control several units with a multiple remote control display, by wiring an optional multiple display adapter (PAC-SA88HA-E) with relays and lamps on the market.
How to wire
(1) Connect the multiple display adapter to the connector CN51 on the
indoor controller board.
(2) Wire three of the five wires from the multiple display adapter as shown
in the figure below.
Indoor controller board
[Notes on Signs] X1:Relay (for operation lamp) X2:Relay (for check lamp) RL:Operation Lamp GL:Check Lamp
[Field supplied parts] Relays:12V DC with rated coil power
consumption below 0.9W.
Lamps:Matching to power supply voltage.
10-14. INTERLOCKING OPERATION METHOD WITH DUCT FAN (Booster fan)
Whenever the indoor unit is operating, the duct fan operates. (1)Connect the optional multiple remote
controller adapter(PAC-SA88HA-E)to the connector CN51 on the indoor controller board.
(2)Drive the relay after connecting the
12V DC relay between the Yellow and
Orange connector lines. Use a relay under 1W. MB: Electromagnetic switch power relay
for duct fan.
X: Auxiliary relay (12V DC LY-1F)
68
11 DISASSEMBLY PROCEDURE
PL-3/4/5/6AAK
OPERATING PROCEDURE PHOTOS & ILLUSTRATIONS
1. Removing the air intake grille
(1) Slide the knob of air intake grille to the direction of the
arrow 1 to open the air intake grille.
(2) Remove the string hook from the panel to prevent the
grille from dropping.
(3) Slide the shaft in the hinge to the direction of the arrow2
and remove the air intake grille.
2. Removing the room temperature thermistor
(1) Remove the screw(1) in the room temperature thermistor
holder to remove the holder and the room temperature thermistor.
(2) Remove the 1 screw from the bell mouth, and unscrew the
other 2 screws (fix to the oval hole which has a different diameter) to remove the bell mouth.
(3) Hold the holder claw, and remove the room temperature
thermistor and holder.
(4) Disconnect the connector (CN20:red) on the indoor control
board.
Be careful on removing heavy parts.
Figure 1
Air intake grille
Grille
Air intake grille knob
Photo 1
Screws
Bell mouth
Room temperature thermistor
3. Removing the electrical box
(1) Disconnect the lead wire of the vane motor from the clamp,
and disconnect the white connector (10P). (2) Remove the room temperature thermistor with the holder. (3) Remove the bell mouth.(See photo 1) (4) Disconnect the relay connector in the electrical box.
Red (3P) for fan motor.
Disconnect the connector on the indoor controller board.
White (2P) for pipe temperature detecting thermistor.
Blue (3P) for drain pump.
White (3P) for drain sensor. (5) Remove the 3 screws from the electrical box, loosen
another 2 screws to remove the box.
<Electrical parts in the electrical box>
Indoor controller board
Power supply board
Terminal block
Capacitor
Photo 2
Turbo fan
Electrical box
Power supply board
Nut
Indoor controller board
Air intake grille
Capacitor
Terminal
block
Connector
69
OPERATING PROCEDURE
PHOTOS & ILLUSTRATIONS
4. Remove the fan motor
(1) Remove the bell mouth.(See photo 1) (2) Remove the electrical box.(See photo 2) (3) Remove the turbo fan nut. (4) Pull out the turbo fan. (5) Disconnect the connector of the fan motor lead wire. (6) Remove the 4 nuts of the fan motor.
5. Removing the pipe temperature thermistor
(1) Remove the bell mouth.(See photo 1) (2) Remove the electrical box.(See photo 2) (3) Remove the turbo fan. (4) Remove the screw of the service panel. (5) Remove the service panel. (6) Remove the pipe temperature thermistor which is inserted
into the holder installed to the thin copper pipe.
(7) Disconnect the 2-pin white connector.
Photo 3
Photo 4
Fan motor
Nut
Pipe temperature thermistor
Connector
Nut
6. Removing the panel
(1) Remove the air intake grille.(See figure 1)
Corner panel (See figure 2)
(1) Remove the corner screw. (2) Slide the corner panel to the direction of the arrow3, and
remove the corner panel.
Panel (See photo 5)
(1) Disconnect the connector that connects with the unit. (2) Remove the 2 screws from the panel and loosen another
2 screws, which fix to the oval holes, have different diame­ters.
(3) Rotate the panel a little to remove the screws.
7. Removing the drain pan
(1) Remove the panel. (See photo 5) (2) Remove the drain plug (Larger one), drain the remaining
water in the drain pan. (3) Remove the corner cover. (2 screws) (4) Remove the bell mouth (See photo 1) (5) Remove the electrical box. (See photo 2) (6) Remove the lead wire holder. (1 screw) (7) Remove the 4 screws and pull out the drain pan.
w Pull out the left and right of the pan gradually.
Be careful not to crack or damage the pan.
Figure 2
Corner panel
Photo 5
Connector
Screw
Photo 6
Screw
Drain pan
Screw
Service access
Screw
Corner panel
Panel
Screw
Panel
Screw
Screw
70
Lead wire holder
Drain plug(Larger one)
Corner cover
OPERATING PROCEDURE PHOTOS & ILLUSTRATIONS
8. Removing the drain pump and drain sensor
(1) Remove the panel. (See photo 5) (2) Remove the bell mouth. (See photo 1) (3) Remove the electrical box. (See photo 2) (4) Remove the drain pan. (See photo 6) (5) Remove the 3 screws of the drain pump. (6) Cut the drain hose band, pull out the drain hose from the
drain pump. (7) Pull out the drain pump. (8) Remove the drain sensor and the holder.
9. Removing the heat exchanger
(1) Remove the panel. (See photo 5) (2) Remove the bell mouth. (See photo 1) (3) Remove the electrical box. (See photo 2) (4) Remove the drain pan. (See photo 6) (5) Remove the turbo fan. (See photo 3) (6) Remove the 3 screws of the piping cover, and pull out
piping cover. (7) Remove the 4 screws of the outer wall cover, and pull out
the outer wall cover. (8) Remove the screw of the coil support. (9) Remove the 2 screws of the coil.
(10) Pull out the heat exchanger.
Photo 7
Screw
Drain hose
Photo 8
Heat exchanger
Coil
support
Fixing band
Coil support
Drain sensor
Screw
Drain pump
Coil screws
Coil support
Photo 9
Screw
Outer wall cover
Piping cover
Screws of piping cover
71
12 PARTS LIST
ON/OFF TEMP
MODEL SELECT
NOT AVAILABLE
CHECK
TEST RUN
˚C
AMPM
AMPM
ON/OFF
CENTRALLY CONTROLLED
ERROR CODE
CLOCK
ON OFF
˚C
CHECK
CHECK MODE
FILTER
TEST RUN FUNCTION
˚C
1Hr.
NOT AVAILABLE
STAND BY DEFROST
TEMP.
No.
Parts No. Parts Name
Specification
Q'ty / set
WIRELESS
WIRED
Remarks
(Drawing No.)
Wiring
Diagram
Symbol
Recom­mended
Q'ty
Unit
Amount
Price
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16 17
18
AIR OUTLET GRILLE VANE CORNER PANEL (RECEIVER) CORNER PANEL L.L FILTER GRILLE ASSY RECEIVING UNIT WIRELESS REMOTE CONTROLLER BOARD VANE MOTOR VANE BUSH GEAR (VANE) GEAR REMOTE CONTROLLER WIRELESS REMOTE CONTROLLER REMOTE CONTROLLER DOOR REMOCON HOLDER CABLE ASSY SCREW ASSY
1 4
4 1 1
4 8 4 4 1
1 1
1 4 1 3 1 1 1 1 4 8 4 4
1 1 1
1
RU
W.B
MV
R.B
T7W E10 003 R01 E00 002 R01 E02 638 R01 E03 638 R01 E00 500 R01 E00 691 R01 24K 658 R01 E00 317 R01 E00 223 R01 E00 063 R01 E00 040 R01 E01 040 T7W E08 713 T7W E06 714 R01 E01 049 R01 E00 075 T7W E01 305 R01 E00 673
PLP-6AA
PLP-6AAL
Including H2
PANEL PARTS PLP-6AA PLP-6AAL
1
GEAR
12
GEAR
(VANE)
11
VANE
2
BUSH
10
9
VANE
MOTOR
3
8
4
13
14
15 16
Part numbers that is circled is not shown in the figure.
5
6
72
17
7
RECEIVER
FUNCTIONAL AND STRUCTURE PARTS PL-3AAK PL-4AAK PL-5AAK PL-6AAK
1
2
11
10
9
Parts No.
No.
1 2
3
R01 E28 114
4
R01 E29 114
5
R01 08K 097 T7W K25 480
6
T7W K26 480 T7W H31 480
7
T7W E06 202
8 9
T7W E06 762
10
T7W E07 762 R01 A41 105
11
SPL WASHER
— — — —
— — —
3 4
5
6
Parts Name
BASE BASE LEG LEG TURBO FAN TURBO FAN SPL WASHER HEAT EXCHANGER HEAT EXCHANGER HEAT EXCHANGER PIPE TEMPERATURE THERMISTOR INNER COVER INNER COVER LEG FAN MOTOR FAN MOTOR RUBBER MOUNT
Specification
D17B6P70MS D176P120MS
Q'ty / set
PL-AAK
5
3
46
1
1
1
2
2
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
4
4
4
Remarks
(Drawing No.)
(RG00G462G34) (RG00G462G32)
1
(RG02G374H05)
2
(RG02G374H06)
1
1 1
1 1
(RG00G165G45)
1
(RG00G165G47)
1
(RG02G375H01)
1 4
8
7
PIPE TEMPERATURE THERMISTOR
Wiring
Symbol
TH2
MF MF
Recom­mended
Q'ty
Unit
Diagram
Price
Amount
73
No.
Parts No.
Parts Name
Wiring
Diagram
Symbol
Recom­mended
Q'ty
Unit
Amount
Price
1
2
3
4
5
6
7
8
9 10 11 12 13
14 15
16 17
DRAIN PAN DRAIN PAN DRAIN PAN DRAIN SOCKET DRAIN PUMP DRAIN SENSOR SENSOR HOLDER INDOOR POWER BOARD FUSE INDOOR CONTROLLER BOARD CONTROL COVER ASSY ROOM TEMPERATURE THERMISTOR TERMINAL BLOCK TERMINAL BLOCK TERMINAL BLOCK CAPACITOR CAPACITOR CORNER COVER DRAIN PLUG DRAIN PLUG
1
1 1 1 1 1 1 1 1 1 1 1 1 1
1 1 1
1
1 1 1 1 1 1 1 1 1 1 1 1
1 1 1 1
(RG00A239GV5)
(RG00G623G05)
DP DS
P.B
FUSE
I.B
TH1 TB5 TB4 TB2
C C
6.3A 250V
2P
(1, 2)
3P
(1, 2, 3)
3P
(L, N, ;)
3.5+ 440V
7.0+ 440V
R01 E02 529 R01 E00 529 R01 E01 529 R01 A41 523 T7W E08 355 R01 E00 266 R01 31K 241 T7W E24 313 R01 E02 239 T7W E47 310
— R01 E00 202 T7W 512 716 T7W E27 716 T7W A14 716 R01 17T 255 T7W E02 255
— R01 A41 524 R01 A48 524
Q'ty / set
PL-AAK
3
4,5
Specification
Remarks
(Drawing No.)
1 1 1 1 1 1 1 1 1 1 1 1 1
1 1 1 1
6
FUNCTIONAL AND STRUCTURE PARTS PL-3AAK PL-4AAK PL-5AAK PL-6AAK
1 2
DRAIN PLUG
17
FUSE
3
DRAIN PLUG
16
15
4
5
CAPACITOR
14
TERMINAL BLOCK
13
TERMINAL BLOCK
12
6 7
8 9
TERMINAL BLOCK
11
ROOM
10
TEMPERATURE THERMISTOR
74
13
1 2 3 4 5
BRN RED ORN YLW GRN
OPTIONAL PARTS
13-1. REFRIGERANT PIPES
Service Ref. : PL-3AAK
Part No. PAC-05FFS-E PAC-07FFS-E PAC-10FFS-E PAC-15FFS-E Pipe length 5m 7m 10m 15m Pipe size O.D . Connection method Indoor unit: Flared Outdoor unit: Flared
Service Ref. : PL-4AAK, PL-5AAK, PL-6AAK
Part No. PAC-PC51PI-E PAC-SC52PI-E PAC-SC53PI-E PAC-SC54PI-E Pipe length 5m 7m 10m 15m Pipe size O.D. Connection method Indoor unit: Flared Outdoor unit: Flared
Note 1. How to connect refrigerant pipes.
Factory supplied optional refrigerant pipings contain refrigerant at the above atmospheric pressures. As long as the connection takes no more than 5 minutes, no air will enter, and there will be no need for air purging. Remove the blind caps and make the connections within 5 minutes. After the connections for the indoor and outdoor units are made, open the stop valve on the outdoor unit to allow refrigerant gas to flow.
Note 2. The following main parts are contained in the optional refrigerant piping kit.
Heat insulating cover, vinyl tapes, nipples, sleeve and flange (for wall hole).
Liquid:[9.52 Gas:[15.88
Liquid:[9.52 Gas:[19.05
13-2. MULTIPLE REMOTE CONTROLLER ADAPTER
This adapter is needed for remote indication (operation/check).
Part No.
Applicable Service Ref.
PAC-SA88HA-E
PL-3/4/5/6AAK
13-3. REMOTE ON/OFF ADAPTER
Part No.
Applicable Service Ref.
PAC-SE55RA-E
PL-3/4/5/6AAK
13-4. REMOTE SENSOR
Part No.
Applicable Service Ref.
PAC-SE41TS-E
PL-3/4/5/6AAK
13-5. REMOTE OPERATION ADAPTER
Part No.
Applicable Service Ref.
PAC-SF40RM-E
PL-3/4/5/6AAK
75
13-6. MULTI FUNCTION CASEMENT (FOR HIGH EFFICIENCY FILTER AND FRESH AIR INTAKE)
Part No.
Applicable Service Ref.
PAC-SG03TM-E
PL-3/4/5/6AAK
13-7. HIGH EFFICIENCY FILTER ELEMENT (PAC-SG03TM-E is needed)
Part No.
Applicable Service Ref.
PAC-SG01KF
PL-3/4/5/6AAK
13-8. AIR OUTLET SHUTTER PLATE (20set, 2pcs/set)
Part No.
Applicable Service Ref.
PAC-SG06SP-E
PL-3/4/5/6AAK
HEAD OFFICE : TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU TOKYO 100-8310, JAPAN
© Copyright 2006 MITSUBISHI ELECTRIC ENGINEERING CO.,LTD. Distributed in Mar. 2006 No.OC378 PDF 9 Made in Japan
New publication, effective Mar. 2006 Specifications subject to change without notice
Loading...