The PKH series models have been downsized and now require such minimal wall space that they can even be installed
above windows.
2. LCD WIRELESS REMOTE CONTROLLER
The new wireless remote controller has a larger easy-to-read temperature display, and executes ON/OFF commands
and temperature settings with a press of the button.
3. AUTO FLAP SHUTTER
With a simple flick of the OFF switch the air outlet can be closed off with a shutter. The shutter also functions as a flap
during operation to adjust the air flow angle, with “Auto Angle 1” securing a comfortable air flow.
4. INSTALLATION : FAST AND EASILY ADAPTABLE
(1) Multi-directional piping
Multi directional drain and refrigerant piping radically improves flexibility in selecting installation layouts.
PKH18/24/30/36FL models boast refrigerant piping in 4 directions and drain piping in 2 directions.
(2) Back plate installation guide
The back plate installation guide gives clear instructions on installation positions. The enlarged back plate secures the
unit firmly to the wall, while the support piece which lifts the unit makes left side piping work much easier.
(3) Easily removable filter and convenient wireless remote controller
The presence of thumb screws on the filters means that the filters can be quickly and smoothly removed.
5. HIGH RELIABILITY AND EASY SERVICING
In addition to the self-diagnostic function, units are also equipped with a 3-minute time delay mechanism (cooling), an auto
restart function, an emergency operation function, a test run switch, etc., to assure high reliability and easy servicing.
6. NITROGEN GAS IS CHARGED TO INDOOR UNIT
Indoor unit and refrigerant pipes are charged with nitrogen gas (N2) instead of R22 before shipment from the factory.
2
PART NAMES AND FUNCTIONS2
ON/OFF TEMP
FAN
VANE
TEST RUN
AUTO STOP
AUTO START
h
min
LOUVER
MODE
CHECK
RESETSETCLOCK
MODEL
SELECT
NOT AVAILABLE
SWING
CHECK
FAN
TEST
RUN
˚F
˚C
AMPMSTOP
START
AMPM
COOL
DRY
AUTO
FAN
HEAT
VANE CONTROL button
Used to change the air flow direction.
CLOCK button
RESET button
SET button
ON/OFF button
The unit is turned ON and OFF alternately
each time the button is pressed.
LOUVER button
This switch the horizontal fan motion ON
and OFF.
(Not available for this model.)
MODE SELECT button
Used to switch the operation mode between
cooling, drying, fan.
CHECK-TEST RUN button
Only press this button to perform an inspection check or test operation.
Do not use it for normal operation.
FAN SPEED SELECT button
Used to change the fan speed.
TIMER display
Displays when in timer operation or when
setting timer.
button
SET TEMPERATURE button sets any desired
room temperature.
CLOCK display
Displays the current time.
“ ” “ ” display
Displays the order of timer operation.
“ ” “ ” display
Displays whether timer is on or off.
Buttons used to set the “hour and minute” of
the current time and timer settings.
h and min buttons
88°F display
SET TEMP. display indicates desired temperature set.
display
FAN SPEED display indicates which fan
speed has been selected.
display
The vertical direction of air flow is indicated.
display
Blinks when model is selected.
display
Lights up while transmission to the indoor
unit is mode using switches.
display
CHECK&TEST RUN display indicates that
the unit is being checked or test-run.
OPERATION MODE display
OPERATION MODE display
Operation mode display indicates which operation mode is in effect.
TIMER CONTROL buttons
AUTO STOP (OFF timer): when this switch
is set, the air conditioner will be automatically stopped at the preset time.
AUTO START (ON timer): when this switch
is set, the air conditioner will be automatically started at the preset time.
MODEL SELECT
CHECK
TEST RUN
●Wireless remote controller
● When cover is open.
3
3SPECIFICATIONS
FK1:48 -41
Capacity
Moisture removal
Power
Consumption
EER
SEER
HSPF
COP
INDOOR UNIT MODELS
External finish
Power supply
Max.fuse size (time delay)
Min.ampacity
Fan motor
Booster heater
Airflow Hi-Lo
Sound level Hi-Lo
Unit drain pipe O.D.
Dimensions
Weight
OUTDOOR UNIT MODELS
External finish
Power supply
Max.fuse size (time delay)
Min.ampacity
Fan motor
Compressor
Crankcase heater
Refrigerant control
Defrost method
Sound level
Dimensions
Weight
REMOTE CONTROLLER
Control voltage (by built-in transformer)
REFRIGERANT
REFRIGERANT PIPING
Pipe size
Connection
method
Between the indoor
& outdoor units
Cooling *1
Heating *1
Heating *2
Cooling *1
Heating *1
Heating *2
*1
*1
*2
Dry
Wet
W
D
H
Model (type)
W
D
H
Name
Charge
Oil <Model>
Liquid
Gas
Indoors
Outdoors
Height difference
Piping length
Air flow should be set at HI.
A point on the curve shows the reference point.
<PKH36FL>
COOLING MODE
Data is based on the condition under outdoor humidity 75%.
A point on the curve shows the reference point.
HEATING MODE
12
4. STANDARD OPERATION DATA
Models
Item
Electrical circuitRefrigerant circuitIndoor sideOutdoor side
Voltage
Frequency
Total input
Indoor fan current
Booster heater current
Outdoor fan current
Comp. current
Condensing pressure
Suction pressure
Discharge temperature
Condensing temperature
Suction temperature
Comp.shell bottom temperature
Ref. pipe length
Refrigerant charge
Fan speed
Airflow (High)
Fan speed upper/lower
Airflow
Unit
V
Hz
kW
A
A
A
A
psi.G
psi.G
˚F
˚F
˚F
˚F
ft
˚F
˚F
˚F
˚F
r.p.m.
CFM
˚F
˚F
r.p.m.
CFM
Btu/h
208/230
1.79
0.5
0.75
7.4/6.9
255
81
182
118
66
171
80
67
61
59
95
75
18,000
0.82
60
Cooling
208/230
1.56
0.5
7.6/8.4
0.75
6.1/5.9
202
61
126
102
34
111
70
60
96
68
47
43
18,600
Heating
PKH18FL
208/230
2.36
0.5
0.65+0.65
9.3/8.7
240
75
158
115
46
141
80
67
58
56
95
75
24,000
0.71
60
Cooling
208/230
2.37
0.5
7.6/8.4
0.65+0.65
9.5/8.7
243
63
149
115
35
126
70
60
105
70
47
43
25,000
Heating
PKH24FL
208/230
3.12
0.6
0.75+0.75
12.6/11.8
245
80
158
115
49
138
80
67
59
58
95
75
30,000
0.75
60
Cooling
208/230
3.02
0.6
8.7/9.6
0.75+0.75
12.2/11.4
236
60
159
113
32
130
70
60
103
70
47
43
33,000
Heating
PKH30FL
208/230
3.44
0.6
0.75+0.75
14.3/13.2
243
74
160
115
45
142
80
67
58
56
95
75
34,200
0.71
60
25
5 lbs 8 oz
1,310
710
1,310
710
1,400
990
1,400
990
790
1,590
750/750
3,170
760/760
3,350
760/760
3,350
25
9 lbs 15 oz
25
10 lbs 2 oz
25
10 lbs 9 oz
Cooling
208/230
3.54
0.6
8.7/9.6
0.75+0.75
14.7/13.7
263
60
170
120
33
148
70
60
109
71
47
43
38,000
Heating
PKH36FL
Intake
air temperature
Discharge
air temperature
Intake
air temperature
Capacity
SHF
DB
WB
DB
WB
DB
WB
13
5. OPERATING RANGE
1) POWER SUPPLY
1 Phase 60Hz 208/230V
Guaranteed voltage range
2) OPERATION
Min.Max.
198V208V230V253V
Function
Cooling
Heating
Air intake temperature
Condition
Standard temperature
Maximum temperature
Minimum temperature
Maximum humidity
Standard temperature
Maximum temperature
Minimum temperature
DB(˚F
80
95
67
80
70
80
70
Indoor
)
WB(˚F
6. OUTLET AIR SPEED AND COVERAGE RANGE
Model
PKH18FL
PKH24FL
PKH30FL
Airflow
(
CFM
710
710
990
)
Air speed
(
ft/sec
16.1
16.1
17.7
)
Coverage
range(ft
41
41
50
)
Outdoor
)
67
71
57
75
60
67
60
* With wind baffle D.B. 23°F if no wind baffle.
The air coverage range is the value up to the position
where the air speed is 0.8ft/sec. when air is blown out
horizontally from the unit at the High notch position.
The coverage range should be used only as a general
guideline since it varies according to the size of the
room and furniture installed inside the room.
DB(˚F
95
115
*0
80
47
75
17
)
WB(˚F
75
—
—
75
43
65
15
)
PKH36FL
990
17.7
50
7. ADDITIONAL REFRIGERANT CHARGE (R22(oz))
Refrigerant piping length (one way)
100ft
85ft
70ft
55ft
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Model
PKH18FL
PKH24FL
PKH30FL
PKH36FL
Outdoor unit
precharged
(
up to 100ft
5 lbs 8 oz
9 lbs 15 oz
10 lbs 2 oz
10 lbs 9 oz
)
25ft
0
0
0
0
40ft
0
0
0
0
14
115ft
2
2
5
5
130ft
4
4
10
10
150ft
7
16
16
164ft
9
20
20
6. NOISE CRITERION CURVES
90
80
70
60
50
40
30
20
10
63125250500 1000 2000 4000 8000
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
Hi
NOTCH
Lo
49
SPL(dB)44LINE
90
80
70
60
50
40
30
20
10
63125250500 1000 2000 4000 8000
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
Hi
NOTCH
Lo
48
SPL(dB)41LINE
Wall
Unit
3.3ft
3.3ft
PKH18FL
PKH24FL
Ambient temperature 80˚F
Test conditions are based on JIS Z8731
PKH30FL
PKH36FL
15
5
9-1/4
1-25/32
9-1/4
1-25/32
9-1/49-1/4
1-25/32
1/2
13-3/8
7-3/4
1-21/32
2-9/32
Top
Front
Right side
Left side
55-1/8
42-15/16
Air intake
9-1/4
C
Knock out hole for right piping
Refrigerant pipe. Drain pipe
Knock out hole for
left piping
Drain hose for
left-hand side piping
Drain hose
Lower side
Auto vane
(Gas pipe)
Drain hose O.D.1-1/16(or 7/8)
Bolt
Gas pipe
19/32
Terminal block for power supply
Terminal block for control
(Liquid pipe)
Liquid pipe 3/8F
Gas pipe 5/8F
Liquid pipe
A
1-3/16
1-15/32
1-17/32
3-27/322-9/16
2-29/32
5/32
3-15/16
1-17/32
1-3/16
1-15/32
2-29/32
5/32
1-5/32
11-1/32
1-3/16
7-1/4
1-3/16
3-5/32
1-3/18
2-3/8
13/32
1-17/32
1-15/32
2-9/16
3-15/16
A
B
C
Knock out hole for piping
31/32
43-11/16
7-7/32
9-7/16
B
44-3/32
21-23/32
4-23/32
2-5/32
4-7/32
4-3/8
Air outlet
21-23/32
Air outlet
Change vane (manual)
Under panel
Removable at left-hand
side piping
Knock out hole for under-piping
Refrigerant pipe. Drain pipe
Rear piping opening
Range for left rear piping opening
12-{1/4 Hole for
tapping screw
66-{1/4 hole for
tapping screw
Wall fixture
Unit center
32-{15/32
hole for bolt
23/32
3-19/32
35-7/16
38-31/32
17-29/32
11-7/32
9-21/32
3/4
9-7/1611-1/3212-3/8
24
Drainage range
on left-hand side
Drainage range
on right-hand side
10x3-19/32=(35-13/16)
7-3/32
2-15/32
8-27/32
3-17/32
23/32
OUTLINES AND DIMENSIONS
Indoor Unit
PKH18FL
PKH24FL
Unit : inch
16
PKH30FL
PKH36FL
Unit : inch
3/4F
Through hole
on the market.
3-1/2 3-1/2~ 4
>< 1 Sleeves are available
B
9-1/4
Right side
7-3/4
C
19/32
or less
Drain hose O.D.1-1/16(or 7/8)
Bolt
4-3/8
4-1/32
Gas pipe
Liquid pipe1/2F
1
2
Sleeve >< 1
2-9/32
2-15/32
1/2
9-1/4
Knock out hole
1-25/32
for right piping
2
1-21/32
2-5/32(Gas pipe)
9-7/16
4-23/32(Liquid pipe)
7-7/32
1
9-1/4
1-25/32
Front
Top
9-1/4
9-1/4
1-25/32
1-25/32
66-5/32
53-15/16 Air Intake
Terminal block for control
Terminal block for power supply
Lower side
55-1/8
Drain hose
43-11/16 (Drain hose)
27-5/16 Air outlet27-5/16 Air outlet
9-1/4
13-3/8
louvers(manual)
Under panel (Removable at
left-hand piping)
Knock out hole for under-piping
Auto vanes
11-1/32
1-5/32
3-5/32
1-3/16
1-3/16
7-1/413/32
1-3/16
Refrigerant pipe .Drain pipe
2-3/8
7-17/32
12- 1/4 hole
for tapping screw
Front
Air
intake
or more
1-3/16
Air
outlet
5-/15/16 or less
Left side
10 or more
Knock out hole for wiring
2 or more10 or more
C
A
A
1-3/161-3/16
B
3-15/16
1-17/32
3-15/16
Knock out hole
for left piping
5/32
1-17/32
1-15/32
2-29/32
2-9/16
1-15/32
1-17/32
2-29/32
5/32
17
1-15/32
2-9/16
3-27/32
Drain hose for
left-hand side piping
31/32
Unit center
Drainage range on
9-21/32
Drainage range on
11-7/32
right-hand side
23-7/16
13x3-19/32=(7-3/16)
50
Wall fixture
Unit out line
Left hand side
3/4
3-19/32
35-7/16
23/32
23/32
84-{1/4 hole
for tapping
screw
12-3/8
29-17/32
11-1/32
7-3/32
9-7/16
Range for left
rear piping hole
8-27/32
11-5/8
41- 15/32 hole
Rear piping hole
Range for left rear piping hole
for bolt
Remote controller
Pipe temperature
thermistor / Liquid
(RT2)
Distributor
Restrictor
valve
Capillary tube
PKH18FL : ({0.126x{0.071x19.7)
PKH24FL : ({0.157x{0.079x19.7) w
1.Since the indoor fan motor(MF)is connected with 230V power,if 208V power is used,change the dip switch(SW8)on
the indoor controller board as shown in fig:*1.
fig:*1
Indoor fan motor(MF)for 208V.
2.Since the outdoor side electric wiring may change be sure to check the outdoor unit electric wiring for servicing.
3.Indoor and outdoor connecting wires are made with polarities, make wiring matching terminal numbers.
4.Symbols used in wiring diagram above are, :Connector, :Terminal block.
5.Emergency operation
If remote controller or microcomputer fails but there is no other trouble emergency operation is possible by setting
dip switch(SW3<I.B>) on the indoor controller board.
[Check items]
(1) Make sure that no other trouble exist in the outdoor unit.Trouble with the outdoor unit prevents emergency operation.
(2) Make sure that there is no trouble with the indoor fan.
Emergency operation will be continuous run with the power ON/OFF(ON/OFF with the remote controller is not possible).
[Emergency operation procedure]
(1) Set the dip switch(SW3<I.B>)on the indoor controller board to 1 on and 2 off for cooling and 1 • 2 on for heating.
(2) Turn on outdoor unit side circuit breaker,then indoor unit side circuit breaker.
(3) During emergency operation indoor fan runs at high speed but auto-vane does not work.
(4) Thermostat will not function.Cold air blows out for defrosting during heating thus do not operate defrosting for a long time.
(5) Emergency cooling should be limited to 10 hours maximum
(the indoor unit heat exchanger may freeze).
(6) After every emergency operation,set all dip switches(SW3<I.B>) to OFF.
(7) Movement of the vanes does not work in emergency operation,therefore you have to slowly set them manually to the
appropriate position.
SW8
SW8
H
FS1FS2
88H
TB2
26H
BWN
YLW
8
88H
5
6
GRY
7
GRY
RED
BLUBLU
64
35
RED
2
1
12
HEATER
CN24
(YLW)
6
[LEGEND]
2
1
3
2
1
3
2
1
2
1
31212
12
4
3
2
1
213131
SW3SW9
SW7
SW6
SW1
SW8
SW5
RT2
RT1
F2
F1
SW2
CN51
CENTRALLY
CONTROL
(WHT)
CN40
REMOCON
POWER
LED1 LED2
CN2L
LOSSNAY
ZNR
OUT
DOOR
CN30
WHT
BLK
CN2D
(WHT)
GRN/YLW
RED
BLU
RED
BLU
P.B
TRANS
(DC13.1V)
CN2S (WHT)
CNSK(RED)
I.B
MF
C
135
FC
MV
X4
X4
WHT
RED
BLK
WHT
BLK
FAN
(WHT)
INTAKE
CN20
(RED)
POWER
CNDK
(WHT)
POWER
CND
(RED)
WIRELESS
CN90
(WHT)
REMOCON
CN22
(BLU)
PIPE
CN21
(WHT)
VANE
CN6V
(WHT)
DRAIN
CN31
(WHT)
243˚F ,10A(18,24FL)/16A(30,36FL)
FUSE(6A/250V)
(32˚F /15kΩ, 77˚F /5.4kΩ DETECT)
(32˚F /15kΩ, 77˚F /5.4kΩ DETECT)
(AC208/230V)
(BLU)
WIRING DIAGRAM
MODELS PKH18FL, PKH24FL, PKH30FL, PKH36FL
19
WIRING DIAGRAM
The drawing has been revised as some errors in
WIRING DIAGRAM have been modified.
The former drawing number is RG79J693H01.
8OPERATION FLOW-CHART
START
Power circuit
breaker
Check SW
ON twice
Operation SW
ON
“OFF” timer
“ON” timer
STOP
Set time
complete
Set time
complete
1
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
w 1
w 2
w 3
w 4
w 5
w 7
w 6
PROTECTION DEVICE
SELF HOLD RELEASE
Remote controller
indicator lamp OFF
Trouble STOP
Remote controller
operation display
Operating mode
(COOL)
Operating mode
(DRY)
Operating mode
(HEAT)
Operating mode
(FAN)
Auto COOL/HEAT
operation
COOL operation
DRY operation
HEAT operation
FAN operation
Trouble
PROTECTION DEVICE
SELF HOLD
Remote controller
trouble display
Indoor side
Outdoor side
Fan STOP
Auxiliary heater OFF
Compressor OFF
Fan STOP
Four-way valve OFF
MAIN OPERATION
w1 In addition, the centralised control and remote control can be operated.
w2 The modes which indicate the sources of trouble are listed below.
● E0-Signal transmitting/receiving error
● P1-Room temperature thermistor malfunction
● P2-Indoor coil thermistor malfunction
● P4-Drain sensor malfunction
● P5-Drain overflow
● P6-Coil frost/overheat protection
● P7-System error
● P8-Outdoor unit trouble
w3 The CHECK switch will show if an error has occurred in the past.
w4 Fan runs on low speed for 1 minute in order to remove overheat air.
w5 The 3-minute (6 minutes …heating mode) time-delay functions after compressor stops.
w6 FAN or AUTO mode is selected by the indoor dip switch setting.
w7 In FAN mode, fan speed and vane operation depend on the remote controller setting. (Compressor is OFF.)
20
COOLING OPERATION
COOL operation
Four-way valve/OFF
NO
NO
NO
Vane setting notch
Initial
COOLING
w 8
55 deg downward angle
70 deg downward angle
NO
Downward discharge
Vane horizontal
w 9
YES
Vane initial
setting
Vane
YES
Fan speed
LOW
YES
1 hour
YES
airflow
Compressor
thermostat ON
Allowance
cancel
NO
YES
NO
YES
YES
NO
compressor operation
w 10
w 11
NO
compressor operation
Allowance cancel
NO
compressor operation
temperature is 34˚F
3-minute
time delay
NO
6-minute
time delay
NO
3-minute
YES
Coil frost
protection
NO
Cooling area
YES
10-minute
YES
Coil frost
prevention
NO
16-minute
YES
Indoor pipe
or lower
NO
YES
YES
YES
NO
Coil frost
prevention
Indoor coil
temperature is 50˚F
or higher
YES
Defrosting
protection detection
temperature 30˚F
or lower
YES
6-minute
time delay
Coil frost
prevention release
NO
NO
3-minute
time delay
Allowance
period
NO
6 minute
time delay
Allowance set
YES
NO
1 min continue
FAN speed
LOW 5 min elapse
YES
LOW
FAN speed
NO
Coil frost protection
YES
Outdoor unit
trouble
Compressor ON
1
Compressor OFF
w8 When operation stops or changes to cooling or dry mode, the auto vane turns to a horizontal angle. If operation changes
during auto vane SWING, the auto vane will continue to swing.
w9 When operating TEST RUN, the thermostat will be continuously ON.
w10 After 3 minute compressor operation, if the indoor coil thermistor reads 5°F or below for 3 minutes, the compressor will
stop for 6 minutes.
w11Heating area : Indoor coil temperature is more than 9 degrees above the room temperature.
Cooling area : Indoor coil temperature is more than 9 degrees below the room temperature.
FAN area : Indoor coil temperature is within 9 degrees either way of the room temperature.
21
DRY OPERATION
DRY
operation
Four-way valve / OFF
Initial dry
operation
Room temperature is
64°F or lower
During
compressor ON
Compressor &
thermostat ON
Vane initial setting
Vane
setting notch
10-minute compressor
OFF timer start
Compressor OFF
Fan STOP
3-minute
time delay
10-minute
compressor
OFF
Compressor ON
time set
Compressor ON
Fan speed LOW
1
Compressor &
thermostat
ON
3-minute
compressor
operation
Compressor ON
time completes
NO
YES
NO
NO
YES
w14
w14
w13
YES
YES
NO
YES
NO
NO
w9
YES
YES
w9
NO
NO
w12
YES
NO
YES
w8
w8—9 Refer to page OC276-21.
w12When room temperature is 64°F or below, the compressor cannot operate.
When room temperature rises over 64°F the compressor starts after a 3-minute time delay.
w13Compressor ON time is decided by room temperature. Refer to page OC276-30.
w14In dry operation, compressor ON makes the fan speed LOW. Also, when the compressor OFF and the pipe temperature
is 79°F or less, the fan stops, or when the compressor OFF and the pipe temperature is below 43°F the fan speed
changes to LOW mode.
It is not possible to set the fan speed with the remote controller
22
HEATING OPERATION
Heat operation
initial
YES
setting
NO
NO
NO
NO
Compressor
NO
trouble
1
operation
YES
>
T
1 To
=
YES
w 15
YES
YES
YES
YES
YES
YES
6 min. restart
2
Hot adjust start
FAN SPEED
Compressor ON
w 16
NO
3 min.restart
prevention
prevention
very low
HEAT mode
NO
HEATING
Vane setting
notch
Vane initial
defrosting
Four-way
valve ON
Hot adjust
in process
Compressor ON
w 9
thermostat ON
Allowance cancel
NO
Indoor piping
5°F or lower
YES
Outdoor unit
FAN SPEED
Very low airflow
Compressor OFF
AUTOMATIC COOLING/HEATING OPERATION
Auto COOL/HEAT
NO
Initial mode
w 17
COOL mode
NO
NO
10-minute
NO
compressor
operation
YES
Allowance cancel
w 11
Heating
area
FAN STOP
w 11
Fan area
20 min.elaspe
YES
Fan area
Heating area
w 11
Fan area
Cooling area
YES
Defrost operation
START
Four-way valve
OFF
NO
NO
NO
w 11
YES
YES
w 10
NO
Heating area
NO
Defrost
30 min. elapse
YES
Outdoor unit
trouble
1
A
Outdoor unit
trouble
YES
Defrost release
NO
Indoor piping
131°F or lower
NO
Auxiliary
heater ON
NO
Indoor piping
140°F or higher
YES
Auxiliary heater
Overheat remote
NO
Indoor Coil. temp.
150°F or higher
Allowance
period
Overload protect
2
B
NO
YES
OFF
START
YES
YES
1
YES
NO
Auxiliary heater
thermostat ON
Auxiliary heater
NO
6-minute restart
prevention
Allowance set
Compressor OFF
ON
YES
YES
FAN SPEED
FAN SPEED
setting notch
Auxiliary heater
thermistor is 140°F
FAN speed
Airflow 10% up
Indoor piping
95°F or higher
NO
HOT adjust
5 min. elapse
YES
Low
FAN SPEED
Low 2 min.
elapse
YES
Hot adjust
release
A
3-minute
OFF
YES
Indoor coil
or higher
YES
Low notch
YES
B
NO
NO
NO
NO
NO
FAN setting
notch
YES
YES
NO
NO
YES
NO
T
1] (To + 4)
YES
NO
YES
Cool mode
set
After 15min.
T
1] (To + 4)
HEAT operation
11
HEAT operation
COOL mode
NO
T
1[ (To - 4)
After 15min.
1[ (To-4)
T
COOL operation
w15 ( i ) Until Low airflow is set while in hot adjustment
(ii )While defrosting (FAN STOP)
(iii)When thermostat is OFF
In the case of( i ), (ii) and (iii) above, airflow is horizontal regardless the VANE setting.
w16 When AUTO operation is started, COOLor HEAT mode is selected automatically.
w17 T1 : Room temperature.
To : Set temperature
23
9MICROPROCESSOR CONTROL
ON/OFF TEMP
MODEL
SELECT
NOT AVAILABLE
SWING
CHECK
FAN
TEST
RUN
˚F
˚C
AMPMSTOP
START
AMPM
COOL
DRY
AUTO
FAN
HEAT
1.OUTLINE OF MICROPROCESSOR CONTROL
INPUT to remote controller
● OFF-ON switching.
● COOL/DRY-AUTO-HEAT selector switching.
● Thermostat setting.
● TIMER mode selector-switching and Timer
setting.
● HIGH-LOW fan speed switching.
● AUTO Vane selector (AIR DISCHARGE)
switching.
● TEST RUN switching.
● CHECK mode switching.
(Self diagnostic trouble shooting)
Indoor
unit
INPUT from indoor unit
Remote controller board
● Processes and transmits
orders.
Indoor controller board
OUTPUT to remote controller
● Indication LCD lights.
● Room temperature thermistor (RT1)
● Pipe temperature thermistor (RT2)
OUTPUT to indoor unit
● Auto vane’s angle setting.
● Booster heater ON-OFF Control.
● Emergency stop.
Independent Control of
Outdoor Unit
● Compressor protection
device working
● Defrosting
START-STOP
● Fan speed control.
● Crankcase heater control
ON-OFF.
● Self diagnostic function
● Receives orders from remote controller and tem-
perature data from indoor unit.
● Processes orders and data.
● Controls indoor and outdoor operation.
● Self diagnostic function.
w System control operation.
w Emergency operation.
w Set by dip switch on indoor controller board.
123
Polar three-wire cable
Outdoor unit
OUTPUT to outdoor unit
12VDC
1
2
3
● Compressor and
outdoor fan : ONOFF
● Operation mode
change :COOLHEAT.
24
2. INDOOR UNIT CONTROL
Minimum 3 minutes w1
ON
Thermostat
Indoor fan
Auto vane
Booster heater
Compressor
ON
LOW or HIGHLOW or HIGH
ON
ON
OFF
OFF
ON
OFF
OFF
OFF
OFF
Operation starts by
POWER button
ON.
Operation stops by
POWER button
OFF.
Room temperature
becomes equal to
set temperature.
Room temperature
rises above set
temperature.
ON/OFF TEMP
FAN
VANE
TEST RUN
AUTO STOP
AUTO START
h
min
LOUVER
MODE
CHECK
RESETSETCLOCK
FAN
˚F
COOL
AM
2-1 COOL operation
<COOL operation time chart>
<How to operate>
1 Press POWER ON/OFF button.
2 Press the MODE button to display COOL.
3 Press the TEMP( or ) button to set the desired temperature.
NOTE:
Set temperature changes 2°F when the TEMP( or )
button is pressed one time.
Cooling 65 to 87°F.
w1 Even if the room temperature rise above the set temperature during this period, the compressor will not start until this peri-
od has ended.
25
(1) Compressor control
5 minutes
SET
low
5 minutes
SET
low
OFF
1 3-minute time delay
To prevent overload, the compressor will not start within 3 minutes after stop.
2 The compressor runs when room temperature is higher than set temperature.
The compressor stops when room temperature is equal to or lower than the set temperature.
The compressor maintains the previous state when the room temperature minus the set temperature is 0 degrees or more,
or lower than 2 degrees.
3 The compressor stops in check mode or during protective functions.
4 Coil frost prevention
To prevent indoor coil frost, the compressor will stop when the indoor coil thermistor (RT2) reads 34°F or below after the
compressor has been continuously operated for at least 16 minutes or more. When the indoor coil temperature rises to
50°F or above, the compressor will start in a 3-minute(w2) time delay.
w2 When the indoor coil temperature is 30°F or less, the compressor starts in 6 minutes.
NOTE : By turning OFF the dip switch SW1-3 on indoor controller board, the start temperature of coil frost prevention changes
from 34°F to 36°F.
5 Coil frost protection
When indoor coil temperature becomes 5°F or below,coil frost protection will proceed as follows.
<Start condition>
After the compressor has been continuously operated for 3 minutes or more,and the indoor coil temperature has been 5°F
or below for 3 minutes,the coil frost protection will start.
<Coil frost protection>
Compressor stops for 6 minutes,and then restarts.
lf the start condition is satisfied again during the first 10 minutes of compressor operation,both the indoor and outdoor units
stop,displaying a check code of“P6”on the remote controller.
<Termination conditions>
Coil frost protection is released when the start condition is not satisfied again during the allowance, or when the COOL
mode stops or changes to another mode.
(2) Indoor fan control
Indoor fan speed depends on the remote controller setting.
However, if an outdoor unit abnormality is detected, the indoor fan speed will be low, regardless of the remote controller
setting.
When the outdoor unit abnormality detection is released and the fan speed returns to the set speed, the quiet cycle control
will work.
(a) Normal control
(i ) Fan speed depends on the remote controller setting regardless of the thermostat on/off.
(ii) Fan speed will remain on low if an abnormality in outdoor unit is detected. (5 minutes)
1 Start-up of outdoor unit abnormality detec-
tion.
2 Release of outdoor unit abnormality detec-
tion.
3 Unit stop due to outdoor unit abnormality
with P8 indication.
NOTE 1 : Fan stops immediately if the unit stops or the check mode is started.
26
(3) Auto vane control
10°
1
30° downward
2
60° downward
3
70° downward
4
SWING5
Auto vane position is set to 10 degrees airflow at the start-up of COOL operation. It can then be changed by the remote
controller.
(a) Vane position set mode & swing mode.
( i ) Every time AIR DISCHARGE button is pressed, setting will be changed .
(ii) Airflow direction can be changed with AIR DISCHARGE button.
1 Fan speed : LOW
10°
60°
70°
SWING
2 Fan speed : HIGH
10°
30°
60°
70°
SWING
<AUTO RETURN>
When discharge 60° or 70° continues for 1 hour with the fan speed at LOW, the discharge direction turns to the horizontal
discharge automatically.
After that, 60° or 70° is available by setting with the remote controller, and it continues for 1 hour.
If the discharge direction changes from 60° or 70°, the direction returns to the horizontal discharge when 1 hour has
passed since the discharge 60° started.
If the discharge direction changes from 60° (or 70°) to the horizontal discharge, the 1-hour timer to return the horizontal
discharge is cancelled.
<Remote controller display>
Changes by pressing the AIR DISCHARGE button.
27
(4) Detecting abnormalities in the outdoor unit
After the compressor has been continuously operated for 3 minutes, if the difference between the indoor coil temperature
and room temperature is out of RANGE C for 1 minute, the indoor fan speed will turn to LOW. Five minutes later, if the difference is still out of RANGE C,the outdoor unit is functioning abnormally. Thus, the compressor stops and check code
“P8” appears on remote controller.
RANGE A: Indoor coil temperature is more than 9 degrees above room temperature.
RANGE B : Indoor coil temperature is within 9 degrees either way of room temperature.
RANGE C : Indoor coil temperature is more than 9 degrees below room temperature.
Indoor coil temperature
minus room temperature
(degree)
+9
-9
RANGE A
0
RANGE B
RANGE C
28
Minimum 3 minutes w1
ON
Thermostat
Indoor fan
Auto vane
Booster heater
Compressor
ON
DRY MODE
DRY MODE
ON
ON
OFF
OFF
ON
OFF
OFF
OFF
OFF
Operation starts by
POWER button
ON.
Operation stops by
POWER button
OFF.
Room temperature
becomes equal to
set temperature.
Room temperature
rises above set
temperature.
2-2 DRY operation
ON/OFF TEMP
FAN
VANE
TEST RUN
AUTO STOP
AUTO START
h
min
LOUVER
MODE
CHECK
RESETSETCLOCK
FAN
˚F
DRY
AM
<DRY operation time chart>
<How to operate>
1 Press POWER ON/OFF button.
2 Press the MODE button to display “DRY”
3 Press the TEMP( or ) button to set the desired temperature.
NOTE: The set temperature changes 2°F when the TEMP( or )
button is pressed one time.
Dry 65 to 87°F
w1 Even if the room temperature rises above the set temperature during this period, the compressor will not start until this
period has ended.
29
1) Compressor control
Compressor OFF
43°F or more
Below 43°F
STOP
Pipe temp.Fan
LOW
AllLOW
Compressor ON
1 3-minute time delay
To prevent overload, the compressor will not start within 3 minutes after stop.
2 The compressor runs when room temperature is higher than set temperature.
The compressor stops when room temperature is equal to or lower than the set temperature.
The compressor maintains the previous state when the room temperature minus the set temperature is 0°F or more, or
lower than 2°F.
3 The compressor stops in check mode or during protective functions.
4 The compressor will not start when the room temperature is 64°F or below.
The compressor starts intermittent operation when the power is turned ON with room temperature above 64°F. The compressor ON/OFF time depends on the thermostat ON/OFF and the following room temperatures.After 3-minute compressor
operation,
● If the room temperature thermistor reads above 82°F with thermostat ON, the compressor will operate for 6 more minutes
and then stop for 3 minutes.
● If the room temperature thermistor reads 79°F to 82°F with thermostat ON, the compressor will operate for 4 more minutes and then stop for 3 minutes.
● If the room temperature thermistor reads 75°F to 79°F with thermostat ON, the compressor will operate for 2 more minutes and then stop for 3 minutes.
● If the room temperature thermistor reads below 75°F with thermostat ON, the compressor will stop for 3 minutes.
● If the thermostat is OFF regardless of room temperature, the compressor will stop for 10 minutes.
5Coil frost protection
Coil frost protection in DRY operation is the same as in COOL operation.
6Coil frost prevention
Coil frost prevention does not operate in DRY operation.
(2) Indoor fan control
The indoor fan runs on LOW speed during compressor operation. The fan speed cannot be changed with the remote controller. Also, the fan runs on LOW speed when the pipe temperature is 43°F or more, or the compressor is OFF and the
pipe temperature is below 43°F.
(a)During compressor OFF
● When the indoor coil temperature is 43°F or above, the indoor fan will stop.
● When the indoor coil temperature is below 43°F, the indoor fan will run on LOW speed.
(b)During compressor ON
● The indoor fan runs on LOW speed.
<Dry mode>
The fan notch is controlled by the indoor coil temperature every 30 seconds.
Fan control in DRY operation.
(3) Auto vane control
Same as in COOL operation
(4) Detecting abnormalities in the outdoor unit
An abnormality in the outdoor unit can not be detected in DRY operation.
30
2-3 HEAT operation
Minimum 3 minutes w2
ON
Thermostat
Indoor fan
Auto vane
Booster heater
Compressor
Power ON lamp
STAND BY lamp
ON
ON
LOW or HIGHLOW or HIGH
ON
OFF
OFF
OFF
HorizontalHorizontal
OFF
ON
OFF
ON
OFF
ON
OFF
LOW
w
1
LOW
w
1
Hot adjustment
From POWER ON until
warm begins to blow
Hot adjustment
Depends on remote
controller setting
Depends on remote
controller setting
w
1 Changeable LOW or HIGH
by indoor dip switch SW1-6 .
OFF during thermostat OFF
hot adjustment
defrosting
Operation starts by
POWER button
ON.
Operation stops by
POWER button
OFF.
Room temperature
becomes equal to
set temperature.
Room temperature
falls below set temperature.
ON/OFF TEMP
FAN
VANE
TEST RUN
AUTO STOP
AUTO START
h
min
LOUVER
MODE
CHECK
RESETSETCLOCK
FAN
˚F
HEAT
AM
<HEAT operation time chart>
<How to operate>
1 Press POWER ON/OFF button.
2 Press the MODE button to display “HEAT”
3 Press the TEMP( or ) button to set the desired temperature.
NOTE: The set temperature changes 2°F when the TEMP( or ).
button is pressed one time.
Heating 63 to 83°F.
<Display in HEAT operation>
[DEFROST]
The [DEFROST] symbol is only displayed during the defrost operation.
[STANDBY]
The [STANDBY] symbol is only displayed from the time the heating
operation starts until the heated air begins to blow.
w2 Even if the room temperature falls below the set temperature during this period, the compressor will not start until this peri-
od has ended.
31
(1) Compressor control
13-minute time delay
To prevent overload, the compressor will not start within 3 minutes after stop.
2The compressor runs when the room temperature is lower than the set temperature.
The compressor stops when the room temperature is equal to or higher than the set temperature.
3The compressor stops in check mode or during protective functions.
4Overheat protection
<Start condition>
When the indoor coil thermistor reads 158°F or above, the overheat protection will start.
<Overheat protection>
The compressor stops for 6 minutes, and then restarts.
If the start condition is satisfied again within 10 minutes of compressor operation, both the indoor and outdoor units stop,
displaying a check code of “P6” on the remote controller.
<Termination conditions>
Overheat protection is terminated when the start condition is not satisfied again during the allowance (10-minute compressor operation), when operation mode changes to other mode, or when thermostat turns OFF.
(2) Indoor fan control
(a) Normal control
( i )The indoor fan runs on LOW speed during the thermostat OFF.
LOW speed can be changed to HIGH speed by setting the dip switch SW1-6.
If the indoor coil temperature becomes more than 5 degrees below the room temperature during the thermostat
OFF, the indoor fan will stop. After, when the indoor coil temperature becomes within 5 degrees of room temperature, the indoor fan will run on LOW speed.
(ii)Hot adjustment
Hot adjustment is a warm-up for HEAT operation
<Start conditions>
The hot adjustment works under any of the following conditions.
● HEAT operation starts.
● Defrosting ends.
● Thermostat turns ON.
[Hot adjustment]
Initially, the indoor fan runs on LOW speed. When 5 minutes have passed or the indoor coil temperature exceeds
95°F, the fan speed will not be changed. 2 minutes later, the hot adjustment ends. Then, the fan speed depends on
the remote controller setting.
(iii)The indoor fan stops when the indoor coil temperature is within 9 degrees either way of room temperature.
(iv)To eliminate the remaining heat, the indoor fan runs for the first 1 minute after the booster heater is turned OFF.
(3) Auto vane control
Auto vane position is set to 70 degrees airflow at the start-up of HEAT operation.
(a) Vane position set mode & swing mode.
( i ) Every time AIR DISCHARGE button is pressed, setting will be changed .
(ii) Airflow direction can be changed with AIR DISCHARGE button.
10°
NOTE : In the following cases, the discharge direction is 30° regardless of the remote controller setting.
1 During the hot adjustment with fan speed at LOW
2 During defrosting with indoor fan OFF
3 During thermostat OFF
(4) Booster heater control
When the room temperature is 6 degrees below the set temperature, the booster heater will turn ON.
When the room temperature is equal to the set temperature, booster heater will turn OFF.
During the hot adjustment, the booster heater will not work.
<Overheat prevention>
When the indoor coil thermistor rises to 140°F or above, the booster heater cannot work.
When the indoor coil thermistor falls to 131°F or below, the booster heater can work.
30°60°
70°SWING
32
(5) Detecting abnormalities in the outdoor unit
When the outdoor unit is determined to be abnormal by the following causes, the compressor will stop and the check code
“ P8 ” will appear on the remote controller display.
( i ) During compressor ON while hot adjustment is set.
1 If the difference between the indoor coil temperature and room temperature is in the RANGE B, the indoor fan will
stop.
2 Within 20 minutes after entering RANGE B (except for the first 10 seconds),
a) If the temperature difference enters RANGE A, the hot adjustment starts,
b) If the temperature difference is still in RANGE B, the outdoor unit is deemed abnormal.
c) If the temperature difference enters RANGE C, defrosting starts.
3 Within 20 minutes after entering RANGE C, if the temperature difference does not return to RANGE B,the outdoor
unit is deemed abnormal.
4 If the temperature difference returns to RANGE B, the next 20 minutes is an allowance period. If the difference enter
RANGE Aduring the allowance, defrosting ends and the hot adjustment starts. If the difference does not enter
RANGE Aduring the allowance, the outdoor unit is deemed abnormal.
( ii ) During compressor ON in defrosting
After 30 minutes of defrosting in hot adjustment, if the temperature difference is still in RANGE C, the outdoor unit is
determined to be abnormal.
When RANGE B does not change to RANGE Aafter 20 minutes have passed since RANGE C had outdoor unit is
determined to be abnormal.
( iii ) During compressor OFF
Not detecting abnormalities.
(6) Indoor coil temperature abnormality detection
An abnormality can be detected during compressor ON, except for the following.
●For the first 30 minutes after the temperature difference between the indoor coil temperature and room temperature
enters the RANGE C.
●When the temperature difference enters the RANGE C until it moves to the RANGE B.
(7) Defrosting operation
After the outdoor unit starts the defrosting operation, when the temperature difference between the indoor coil temperature
and room temperature gets out of RANGE Aand into RANGE B, the indoor unit starts the defrosting mode. After the outdoor unit stops the defrosting operation, when the temperature difference returns to the RANGE A, the indoor unit stops
the defrosting mode. While the indoor unit is in the defrosting mode, the indoor fan and the booster heater stop.
w1 RANGE A: Indoor coil temperature is more than 9 degrees above room temperature.
RANGE B : Indoor coil temperature is within 9 degrees either way of room temperature.
RANGE C : Indoor coil temperature is more than 9 degrees below room temperature
Indoor coil temperature
minus room temperature
(degree)
+9
0
-9
RANGE A
RANGE B
RANGE C
33
2-4 AUTO operation (Automatic COOL/HEAT change over operation)
Mode change (HEAT COOL)
When room temperature becomes 4 degrees above the set temperature,the operation mode can not be changed
for 15 minutes.
(degree)
To+4
To:Set temperature (65~83°F)
To+2
To
To- 2
To- 4
Compressor
Start
HEAT modeHEAT mode
Mode change
15 minutes
15 minutes
Minimum 3 minutes
COOL mode
(COOL HEAT)
ON
OFF
102030405060708090100110120
COOLING
0°F
115°F
HEATING
75°F17°F
(°F)
0
*
In case of the wind baffle installed.
*
ON/OFF TEMP
FAN
VANE
TEST RUN
AUTO STOP
AUTO START
h
min
LOUVER
MODE
CHECK
RESETSETCLOCK
FAN
˚F
AUTO
AM
<How to operate>
1 Press POWER ON/OFF button.
2
Press the MODE button to display “AUTO”
3 Press the TEMP( or ) button to set the desired temperature.
NOTE: The set temperature changes 2°F when the TEMP( or )
button is pressed one time.
Automatic 65 to 83°F.
●“AUTOMATIC” works to change by itself the operation
mode either to cooling or heating according to the room
temperature.
(1) Initial mode
1 When AUTO operation starts after unit OFF.
● If the room temperature is higher than the set temperature, operation starts in COOL mode.
● If the room temperature is equal to or lower than the set temperature, operation starts HEAT mode.
2 When AUTO operation starts after COOL or HEAT operation, the previous mode continues.
(2 ) Mode change
1 HEAT mode changes to COOL mode when 15 minutes have passed since the room temperature became 4 degrees
above the set temperature.
2 COOL mode changes to HEAT mode when 15 minutes have passed since the room temperature became 4 degrees
below the set temperature.
(3) Temperature range
AUTO operation is available under the outside air temperatures as follows.
34
10°
1
30° downward
2
60° downward
3
70° downward
4
SWING5
2-5 Auto vane control
12
3
4
5
10˚
30˚
60˚
70˚
SWING
ON/OFF TEMP
FAN
VANE
TEST RUN
AUTO STOP
AUTO START
h
min
LOUVER
MODE
CHECK
RESETSETCLOCK
SWING
FAN
˚F
AM
AUTO
<Remote controller display>
<How to operate>
To change the air flow direction, press VANE ( ) button.
Available in COOL operation with fan speed on HIGH or
in HEAT operation.
Unavailable in DRY operation.
If fan speed changes from LOW to HIGH during 30°
downward discharge in COOL mode, the direction automatically changes to 10°.
Changes by pressing the AIR DISCHARGE button.
(1) COOL/DRY operation
At the start-up of COOL or DRY operation, the discharge direction in automatically set to 10°. After, it can be changed to
another direction with VANE ( ) button on the remote controller.
<Auto return>
When discharge 60° or 70° continues for 1 hour with the fan speed at LOW, the discharge direction turns to the horizontal
discharge automatically.
After that, 60° or 70° is available by setting with the remote controller, and it continues for 1 hour.
If the discharge direction changes from 60° or 70°, the direction returns to the horizontal discharge when 1 hour has
passed since the discharge 60° started.
If the discharge direction changes from 60° (or 70°) to the horizontal discharge, the 1-hour timer to return the horizontal
discharge is cancelled.
(2) HEAT operation
At the start-up of HEAT operation, discharge direction depends on the setting of the last operation.
After, it can be changed to another direction with VANE ( ) button. The discharge direction shifts to 10° regardless of
the remote controller settings under any of the following conditions.
● Thermostat OFF
● Defrosting
● Indoor fan speed LOW in hot adjustment
35
2-6 TIMER operation
ON/OFF TEMP
FAN
VANE
TEST RUN
AUTO STOP
AUTO START
h
min
LOUVER
MODE
CHECK
RESETSETCLOCK
SWING
FAN
˚F
PMSTOP
START
AM
COOL
MODE
TEST RUN
FAN
VANE
TEST RUN
ON/OFF TEMP
FAN
VANE
TEST RUN
AUTO STOP
AUTO START
h
min
LOUVER
MODE
CHECK
RESETSETCLOCK
FAN
TEST
RUN
COOL
A
4
6
3
2
5
2-7 Test run
<Timer function>
AUTO STOP ·········The air conditioner stops after the set time lapses.
AUTO START ········The air conditioner starts after the set time lapses.
AUTO OFF ············Timer is not active.
<How to operate>
1 Push POWER ON/OFF button.
2 Check if or not the current time is correct.
3 Push the or button and select the desired time.
4 Set the timer time using HR and MIN buttons.
Test run
Measure an impedance between the power supply terminal block on
the outdoor unit and ground with a 500V Megger and check that it is
equal to or greater than 1.0M
1 Turn on the main power to the unit.
2 Press the button twice continuously.
(Start this operation from the status of remote controller display
turned off.)
Aand current operation mode are displayed.
3 Press the ( ) button to activate COOL mode, then
check whether cool air is blown out from the unit.
4 Press the button and check whether strong air is blown out
from the unit.
5 Press the button and check whether the auto vane operates
properly.
6 Press the ON/OFF button to stop the test run.
".
Note:
• Point the remote controller towards the indoor unit receiver
while following steps 22to 66.
• It is not possible to run the in FAN, DRY or AUTO mode.
36
(1) Indoor coil temperature code
1 ON
1
2
1.2 ON
1
2
1.2 OFF
SW3
1
2
During the test run, the indoor coil temperature code from 1 to 15 is displayed on the remote controller instead of room
temperature. The code should fall with the lapse of time in normal COOL operation, and should rise in normal HEAT
operation.
Code
Indoor coil temperature
Code
Indoor coil temperature
1
~34(36)°F
9
~113°F
2
36(37)°F~50°F
10
~122°F
3
~59°F
11
~131°F
4
~68°F
12
~140°F
5
~77°F
13
~158°F
6
~86°F
14
~191°F
7
~95°F
15
Thermistor abnormality
(2) Trouble during test run
● If the unit malfunctions during the test run, refer to section 10 in this manual entitled “TROUBLESHOOTING.”
● When the optional program timer is connected to the conditioner, refer to its operating instructions.
2-8 Emergency operation
When the remote controller or microprocessor malfunctions but all other parts are normal, emergency operation is started
by setting the dip switch SW3 on the indoor controller board.
<Before emergency operation>
1. Make sure the compressor and the indoor fan are operating normally.
2. Locate the defect with the self-diagnostic function. When the self-diagnostic function indicates “protective function is
working”, release the protective function before starting the emergency operation.
CAUTION: When the self-diagnostic function indicates a check code of “P5” (drain pump malfunction), do not start the
emergency operation because the drain may overflow.
<How to operate>
1. For emergency cooling, set the dip switch SW3-1 to ON and SW3-2 to OFF.
For emergency heating, set the dip switch SW3-1,2 to ON.
Emergency
cooling
Emergency
heating
Normal
operation
8
~104°F
Indoor controller board
2. Turn ON the outdoor unit breaker and then ON the indoor unit breaker.
Emergency operation will now start.
3. During emergency operation, the indoor fan operates on high speed, the auto vanes do not operate.
4. To stop emergency operation, turn OFF the indoor unit breaker.
5. Movements of the vanes do not work in emergency operation, therefore you have to slowly set them manually to the
appropriate position.
NOTE: The remote controller POWER ON/OFF button can not start/stop emergency operations.
CAUTION: Do not use emergency cooling for more than 10 hours, as the indoor coil may freeze.
37
2-9 Dip switch and jumper connector functions.
Each figure shows the initial factory setting.
2-9-1 On remote controller board
(1). On indoor controller board
1. SW1 (Mode selector)
1 2 3 4 5 6 7 8 9
ON
OFF
SW1-1) Switch that changes between FAN mode and AUTO mode
OFF:AUTO mode for models with heat pump
ON:Fan mode for models without heat pump
SW1-2) Switch for drain pump
OFF:The drain pump works in COOL and DRY operation.
ON:The drain pump works in both COOL and DRY and HEAT operation.
SW1-3) Switch to change the temperature to start coil frost prevention
OFF:34°F
ON:36°F
SW1-4) Switch for set temperature adjustment in HEAT mode
During HEAT operation,warm air collects near the ceiling.When the indoor unit is installed near the ceiling,the
temperature read by room temperature thermistor differs from the actual living-space temperature by about 7
degrees. Therefore,the room temperature read by room temperature thermistor must be lowered by 7 degrees.
OFF:7-degree adjustment
ON:NO adjustment
SW1-5) Not for use.
SW1-6) Switch for fan speed during thermostat OFF in HEAT operation
OFF:LOW
ON:LOW or HIGH(set with remote controller)
SW1-7) Switch for detecting abnormalities in the outdoor unit abnormality detection
OFF:When an abnormality occurs,it is detected.
ON:Even if an abnormality occurs,it can not be detected.
SW1-8) Switch for auto restart function
OFF:This function does not work
ON:This function works.
SW1-9, 10) Not for use.
10
2. SW2 (Address selector)
1 2 3 4 5 6
ON
OFF
3. SW3 (Emergency operation switch)
Normal operation
1 2
ON
OFF
4. SW5 (Model selector)
1 2 3 4
ON
OFF
SW5-1) Not for use.
SW5-2) Leave this switch as it is.
SW5-3) Not for use.
SW5-4) Not for use.
SW2-1~6) Not for use.
For emergency cooling
1 2
ON
OFF
For emergency heating
1 2
ON
OFF
38
5. SW6 (Address selector)
1 2 3 4
ON
OFF
6. SW7 (Model selector)
Switch to set the output of phase-controlled indoor fan motor.
Address setting is available at any time.
The initial factory setting by is based on each capacity.
This switch is not available for series PKH.
Service Ref.
SW7
7. SW8 (Option)
1 2 3 4
ON
OFF
SW8-1~2) Not for use.
SW8-3~4) Not for use.
SW8-5) Not for use.
SW8-6) OFF:For 230V power supply
ON: For 208V power supply
8. SW9 (Model selector)
1 2 3 4
ON
OFF
SW9-1~5) Keep this switch.
PKH18FL
ON
OFF
1 2 3
56
5
2-10 INDOOR FAN CONTROL
Indoor fan relay output.
(a) During fan ON
The indoor fan relay turns ON. One second later, the phase control will start.
(b) During fan OFF
The phase control turns OFF. One second later, the indoor fan relay will turn OFF.
PKH24FL
ON
OFF
1 2 3
PKH30FLPKH36FL
ON
OFF
1 2 3
ON
OFF
1 2 3
39
2-11 Wireless remote controller pair number setting operation
ON/OFF
TEMP
FAN
VANE
MODE
CHECK
LOUVER
TEST RUN
AUTO STOP
AUTO START
h
min
RESET
SET
CLOCK
MODEL SELECT
4
A
Model No.
3
2,5
MODEL SELECT
min
A Pair No. of wireless
remote controller
Indoor PC board
0
1
2
3~9
Factory setting
Cut J41
Cut J42
Cut J41, J42
1 Turn on the main power to the unit.
2 Press the SET button with the point of a ball-point pen or the like.
Start this operation from the status of remote controller display turned off.
blinks and Model No. is lighted.
3 Press the button twice continuously.
A Pair No. “0” blinks.
4 Press the temp button to set the pair number you want to set.
5 Press the SET button with the point of a ball-point pen or the like.
Set pair number is lighted for three seconds then turned off.
40
10
CHECK
h
CHECK
ON/OFF
TEMP
FAN
VANE
MODE
CHECK
LOUVER
TEST RUN
AUTO STOP
AUTO START
h
min
RESET
SET
CLOCK
4
AB
3
2
1
2
3
4
5
6
7
8
9
Check CodeAlarmBuzzer sound
Suction sensor alarm
Pipe sensor alarm
Transmission alarm
Drain sensor alarm
Drain pump alarm
Anti-freezing on
Anti-overheat on
System error
Outdoor unit alarm
No alarm (no error)
Single beep O 1
Single beep O 2
Single beep O 3
Single beep O 4
Single beep O 5
Single beep O 6
Single beep O 6
Single beep O 7
Single beep O 8
Receiving signal only
(no error alarm)
TROUBLESHOOTING
1. Self-diagnostic function
Self-check
1 Turn on the main power to the unit.
2 Press the button twice continuously.
(Start this operation from the status of remote controller display
turned off.)
Abegins to light.
B “00” begins to blink.
3 While pointing the remote controller toward the unit’s receiver,
press the button. The check code will be indicated by the
number of times that the buzzer sounds from the receiver section
and the number of blinks of the operation lamp.
4 Press the ON/OFF button to stop the self-check.
41
2. OTHER TROUBLES AND CAUSES
Auto vanes do not work.
Unit stops after 5 to
20 seconds operation
Power ON/OFF button
is not available.
Check
code
1
2
Diagnosis of malfunctionCauseCheck points
Abnormality of room temperature thermistor (RT1)
Abnormality of indoor coil
thermistor (RT2)
Auto vane motor does not work.
Connector is poorly connected.
Auto vane motor is poorly assembled.
Indoor controller board is damaged.
Protection function is working.
Indoor/outdoor connecting wire is connected
incorrectly.
Indoor/outdoor connecting wire shorts.
Compressor protector is damaged.
Defroster is broken.
Remote controller is damaged.
Transmission wire is poorly connected
1) Bad contact of thermistor
2) Damaged thermistor
Auto vane motor is damaged.
Auto vane motor relay is damaged.
Refer to check code on remote controller display.
Transmission wire is damaged.
Connector is poorly connected.
1) Check the thermistor.
2) Measure the resistance of the thermistor.
Normal resistance should be as follows.
32°F····15kΩ86°F·····4.3kΩ
50°F······9.6kΩ 104°F·····3.0kΩ
68°F······6.3kΩ
If the resistance is normal, replace the indoor
controller board.
Abnormality of drain sensor1) Bad contact of transmission
4
Malfunction of drain pump1) Malfunction of drain pump
5
Coil frost protection is work-
6
ing.
Abnormality in outdoor unit
8
❈ The number of check code shows times of Buzzer sound.
wire
2) Damaged thermistor
2) Damaged drain sensor
1) Short cycle of air cycle
2) Dirty air filter
3) Damaged fan
4) Abnormal refrigerant
1) Wrong wiring of indoor/outdoor
connecting wire
2) Reversed phase
3) Protection device is working
4) Damaged outdoor coil thermistor
1) Check the connector.
2) Measure the resistance of the thermistor
(between ➃ - ➄of CN50).
As for the normal resistance, refer to the case
of 1.
If the resistance is normal, replace the indoor controller board.
1) Check the drain pump.
2) ● Check the drain sensor.
● Check the drain sensor heater. Normal resis-
tance should be 82Ω. (between 1 - 3of
CN50).
If the resistance is normal, replace the indoor controller board.
1) Clear obstructions from the air cycle.
2) Clean the air filter
3) Check the fan.
4) Check the refrigerant temperature.
1) Check the indoor/outdoor connecting wire.
2) Change the connection of electric wiring.
3) Check the protection device.
4) Measure the resistance of the outdoor coil thermistor. If the resistance is normal, replace the
outdoor controller board.
42
3. WRONG WIRING ON SITE
OutdoorIndoor
1
2
3
1
2
3
OutdoorIndoor
1
2
3
1
2
3
OutdoorIndoor
1
2
3
1
2
3
OutdoorIndoor
1
2
3
1
2
3
OutdoorIndoor
1
2
3
1
2
3
3-1 Between remote controller and indoor unit
If the wire is disconnected between the remote controller and the indoor unit, nothing is displayed on the remote controller
when the POWER button is pressed. The beep sound will also not be heard.
3-2 Phenomenon due to wrong wiring between indoor and outdoor units
1. Removing the lower side of the indoor unit from the installation plate
(1) Remove the 2 screws.
Hang the indoor unit hangers to the catches on the installation plate.
Figure 1
2. Removing the right side panel
(1) Remove the 2 screws of the right side panel:one on the
bottom and the other on the upper right-hand side.
(2) Disconnect the connector from the adapter case.
(3) Sliding the right side panel to the right, pull it out toward
you.
3. Removing the indoor controller board
(1) Remove the right side panel.
(2) Remove the screw of the electrical box cover, and remove
the cover.
(3) Disconnect the connectors on the indoor controller board.
(4) To unhook the catches on the right-hand side of the indoor
controller board, pull the left-hand side toward you and lift
up the cover to the right. Then the indoor controller board
can be removed.
Figure 2
Photo 1
Indoor controller
board
Electrical box
cover
Catches
4. Removing the electrical box
(1) Remove the right side panel.
(2) Remove the screw of the electrical box cover, and remove
the cover.
(3) Remove the room temperature thermistor and the pipe
temperature thermistor.
(4) Disconnect the vane motor connector on the indoor con-
(5) Remove the 2 screws of the electrical box.
(6) Disconnect the connector of the heater lead wire connec-
(7) Disconnect the connector of the fan motor lead wire.
(8) Remove the electrical box.
troller board.
tor.
45
Photo 2
Room temperature thermistor
Pipe temperature thermistor
Screws
Electrical box
OPERATING PROCEDUREPHOTOS&ILLUSTRATION
Catch on the left side panel
Catch on
the unit
(8) Remove the screws of the indoor controller board case,
and pull out the indoor controller board case.
Then the transformer and the capacitor and relay can be
serviced.
5. Removing the vane motor
(1) Remove the right side panel.
(2) Remove the screw of the electrical box cover, and remove
the cover.
(3) Remove the 2 screws of the vane motor, and remove the
motor from the shaft.
(4) Disconnect the vane motor connector on the indoor con-
troller board.
Photo 3
Capacitor
Indoor controller
board case
Photo 4
Vane motor
Relay
Power board
Electrical box
Screws
Indoor controller board
6 Removing the intake grilles
(1) Remove the right side panel.
(2) To remove the left side panel, remove the screw on the
bottom and the screw on the upper left-hand side. (See
Figure 3.)
1. Press up this side of the left side panel to unhook the
catch on the panel from the catch on the unit.
2. Slide the left side panel to the left to remove the panel.
Note: Fix the unit to the metal fixture securely
(3) Remove the air filters.
(4) Hold and press the center cover to remove.
(5) Remove the screws of the grilles.
(6) Pull the lower side of the grille toward you and slide the
upper to the right to remove the grilles.
7. Removing the drain pan
(1) Remove the left and right side panels.
(2) Remove the grilles.
(3) Remove the electrical box cover.
(4) Loosen the drain hose band to remove.
(5) Remove the 3 screws of the drain pan, and slide the drain
pan toward you to remove.
Figure 3
Photo 5
Left side panel
Photo 6
Slide to the
right
Screws for grilles
Drain pan
Screws
Grilles
Drain hose
band
Drain hose
46
OPERATING PROCEDUREPHOTOS
8. Removing the line flow fan and the fan motor
(1) Remove the left and right side panels.
(2) Remove the grilles.
(3) Remove the electrical box.
(4) Remove the drain pan.
(5) Loosen the screw that fixes the line flow fan to the fan
motor. (See Photo 7. )
(6) Remove the 4 screws of the motor fixture, and remove the
fan motor and the motor fixture at a time (See Photo 8.)
(7) Remove the screws of the left and right motor supports,
and remove the motor supports and the fan motor. (See
Photo 9.)
(8) Remove the 2 screws on the left and right sides of the heat
exchanger, and pull the bearing support toward you. (See
Photo 11.)
(9) Remove the screw of the center support, and remove the
support. (See Photo 10. )
(10) Pull the left-hand side of the heat exchanger toward you,
and remove the line flow fan.
Photo 11
Heat exchanger
Bearing support
Photo 7
Photo 8
Photo 9
Screw
Motor support
Line flow fan
Fan motor
Screw
Fan motor
Screws
Fan motor
Motor fixture
Screw
Line flow fan
9. Removing the electrical heater.
(1) Remove the left and right side panels.
(2) Remove the grilles.
(3) Remove the drain pan.
(4) Loosen the screw that fixes the line flow fan to the fan
motor.(See Photo 7.)
(5) Remove the screw of the center support, and remove the
support. (See Photo 10.)
(6) Remove the 2 screws on the left and right sides of the heat
exchanger, and pull the bearing support toward you. (See
Photo 11.)
(7) Pull the left-hard side of the heat exchanger toward you,
and remove the line flow fan.
(8) Remove the heater fixing screws (1 screw each on right
and left sides), and slide the heater element to the left to
remove the heater.
Photo 10
Photo 12
Heat exchanger
Line flow fan
Heater element
Motor
support
ScrewCenter support
Heater fixing screw
47
12PARTS LIST
No.
Parts No.Parts NameSpecifications
Remarks
(Drawing No.)
Wiring
Diagram
Symbol
Q'ty / set
PKH
FLFL
FL
1
2
3
4
5
SLEEVE BEARING
BEARING MOUNT
LEFT LINE FLOW FAN
LEFT LINE FLOW FAN
RIGHT LINE FLOW FAN
RIGHT LINE FLOW FAN
HEAT EXCHANGER
HEAT EXCHANGER
HEAT EXCHANGER
HEAT EXCHANGER
w Restrictor valve and capillary tube have been
added to "Specifications" of heat exchanger.
ELECTRICAL PARTS
PKH18FL
PKH24FL
PKH30FL
PKH36FL
32·33
1
31
30
2
3
5
27
26
29
28
25
24
23
4
6
22
21
7
8
15
20
19
14
9
12 13
10
w
48
16 171811
No.
Parts No.Parts NameSpecifications
T7W E13 529
6
T7W E14 529
7
R01 12G 621
8
R01 12G 063
R01 12G 002
9
R01 16G 002
10
R01 KV5 527
11
R01 12G 223
12
T7W E12 202
13
R01 E02 202
14
R01 377 246
15
R01 998 246
16
T7W E03 255
17
T7W E24 310
18
T7W 410 239
19
R01 E02 313
R01 479 215
20
R01 673 215
R01 12G 105
21
R01 16G 105
T7W B00 762
22
T7W B01 762
23
R01 E00 075
24
T7W E07 714
25
R01 E01 049
26
R01 12G 103
27
R01 KV5 102
R01 12G 706
28
T7W 589 706
29
R01 20J 303
30
T7W B00 700
T7W 587 300
31
T7W 589 300
32
T7W B02 675
33
T7W B03 675
DRAIN PAN
DRAIN PAN
CENTER COVER
JOINT SHAFT
AUTO VANE
AUTO VANE
DRAIN HOSE
VANE MOTOR
ROOM TEMPERATURE THERMISTOR
PIPE TEMPERATURE THERMISTOR
TERMINAL BLOCK
TERMINAL BLOCK
FAN MOTOR CAPACITOR
CONTROLLER BOARD
FUSE
POWER BOARD
RELAY
RELAY
RUBBER MOUNT
RUBBER MOUNT
FAN MOTOR
FAN MOTOR
WIRELESS REMOTE CONTROLLER HOLDER
WIRELESS REMOTE CONTROLLER
REMOTE CONTROLLER DOOR
SLEEVE BEARING
BEARING MOUNT
THERMAL FUSE
THERMAL FUSE
INSULATOR
THERMAL SWITCH
HEATER ELEMENT
HEATER ELEMENT
FAN GUARD
FAN GUARD
Q'ty / set
24
18
FL
FL
1
1
1
1
1
1
2
2
1
1
1
1
ROOM TEMPERATURE
PIPE TEMPERATURE (INDOOR COIL)
3P(L1, L2, GR)
3P(1, 2, 3)
2.5µF 440V
250V 6A
LY1F DC12V
LY2F DC12V
PN4N45-K
PN4N70-K
243°F 10A 250V
243°F 16A 250V
240V 700W
240V 800W
1
1
1
1
1
1
1
1
1
1
1
1
2
2
1
1
1
1
2
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
3
3
2
2
PKH
3036
FLFL
1
1
1
1
1
1
2
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
1
1
2
2
2
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
3
3
2
2
Remarks
(Drawing No.)
Wiring
Diagram
Symbol
MV
RT1
RT2
TB2
TB4
C
I.B
F1.2<I.B>
P.B
88H
88H
MF
MF
W.R
FS1.2
FS1.2
26H
H
H
49
STRUCTURAL PARTS
PKH18FL
PKH24FL
PKH30FL
1
PKH36FL
2
3
10
9
8
8
7
4
Part number that is circled is not shown in the figure.
No.
Parts No.Parts NameSpecifications
R01 12G 662
1
R01 E01 812
2
R01 E00 812
R01 E00 811
3
R01 E01 811
R01 A17 500
4
R01 50J 317
5
R01 24K 658
6
T7W E00 661
7
R01 12G 691
8
R01 12G 808
9
R01 16G 808
R01 E01 641
10
R01 E00 641
R01 16G 692
11
R01 12G 523
12
LEFT SIDE PANEL
UNDER PLATE
UNDER PLATE
NOSE
NOSE
FILTER
W.A. CONT (A)
RECEIVER
RIGHT SIDE PANEL
INTAKE GRILLE
BACK PLATE
BACK PLATE
TOP PLATE
TOP PLATE
INTAKE GRILLE
DRAIN SOCKET
18
FL
1
1
1
4
1
1
1
2
1
1
1
Q'ty / set
PKH
2430
FL
1
1
1
4
1
1
1
2
1
1
1
FL
1
1
1
5
1
1
1
2
1
1
1
1
6
5
Wiring
Diagram
Symbol
36
(Drawing No.)
FL
1
1
1
5
1
1
1
2
1
1
1
1
Remarks
50
TM
cCopyright 2001 MITSUBISHI ELECTRIC ENGINEERING CO., LTD.
Distributed in Nov. 2003 No.OC276 REVISED EDITON-APDF 9
Distributed in Dec. 2001 No.OC276
.
New publication, effective Nov. 2003
Specifications subject to change without notice.