Mitsubishi Electronics PKA-A24KA-TH, PKA-A30KA-TH, PKA-A30KAL-TH, PKA-A36KA-TH, PKA-A24KAL-TH User Manual

SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
3 3 2 2 3
SPLIT-TYPE, AIR CONDITIONERS
SERVICE MANUAL
Indoor unit [Model names] [Service Ref.]
PKA-A24KA
PKA-A30KA
PKA-A36KA
PKA-A24KA.TH PKA-A30KA.TH PKA-A36KA.TH
March 2009
No. OCH457
NOTE:
• This manual describes only service data of the indoor units.
• RoHS compliant products have <G> mark on the spec name plate.
PKA-A24KAL
PKA-A30KAL
PKA-A36KAL
PKA-A24KAL.TH PKA-A30KAL.TH PKA-A36KAL.TH
INDOOR UNIT
COOL
DRY
AUTO
FAN
HEAT
CONTENTS
1. REFERENCE MANUAL
2. SAFETY PRECAUTION
3. PART NAMES AND FUNCTIONS
4. SPECIFICATIONS
5. NOISE CRITERION CURVES
6. OUTLINES AND DIMENSIONS
7. WIRING DIAGRAM
8. REFRIGERANT SYSTEM DIAGRAM
9. TROUBLESHOOTING
10. SPECIAL FUNCTION
11. DISASSEMBLY PROCEDURE
...................................
...................................
...................
............................................
..........................
.......................
.........................................10
....................................
.....................................
.......................
............
2
3 4
7
8 9
11 12 26 29
TEMP.
WIRED REMOTE
CONTROLLER
ON/OFF
PARTS CATALOG (OCB457)
WIRELESS REMOTE
CONTROLLER
1
REFERENCE MANUAL
1-1. OUTDOOR UNIT SERVICE MANUAL
Service Ref. Service Manual No. PUZ-A24/30/36NHA3
PUZ-A24/30/36NHA3-BS PUY-A24/30/36NHA3 PUY-A24/30/36NHA3-BS
PUZ-HA30/36NHA2
OCH458 OCB458
OCH426 OCB426
1-2. TECHNICAL DATA BOOK
Series (Outdoor unit) Data Book No. PUZ-A·NHA3(-BS)
PUY-A·NHA3(-BS) PUZ-HA·NHA2 OCS15
OCS14
2
2
SAFETY PRECAUTION
2-1. ALWAYS OBSERVE FOR SAFETY
Before obtaining access to terminal, all supply circuits must be disconnected.
2-2. CAUTIONS RELATED TO NEW REFRIGERANT
Cautions for units utilising refrigerant R410A
Use new refrigerant pipes.
Make sure that the inside and outside of refrige­rant piping is clean and it has no contamination such as sulfur hazardous for use, oxides, dirt, shaving particles, etc. In addition, use pipes with specified thickness.
Contamination inside refrigerant piping can cause deterio­ration of refrigerant oil etc.
Store the piping to be used indoors during installation, and keep both ends of the piping sealed until just before brazing. (Leave elbow joints, etc. in their packaging.)
If dirt, dust or moisture enters into refrigerant cycle, that can cause deterioration of refrigerant oil or malfunction of com­pressor.
Use ester oil, ether oil or alkylbenzene oil (small amount) as the refrigerant oil applied to flares and flange connections.
If large amount of mineral oil enters, that can cause deterio­ration of refrigerant oil etc.
Do not use refrigerant other than R410A.
If other refrigerant (R22 etc.) is used, chlorine in refrige­rant can cause deterioration of refrigerant oil etc.
Use a vacuum pump with a reverse flow check valve.
Vacuum pump oil may flow back into refrigerant cycle and that can cause deterioration of refrigerant oil etc.
Use the following tools specifically designed for use with R410A refrigerant.
The following tools are necessary to use R410A refrigerant.
Tools for R410A Gauge manifold Charge hose
Gas leak detector
Torque wrench
Flare tool Size adjustment gauge Vacuum pump adaptor
Electronic refrigerant charging scale
Handle tools with care.
If dirt, dust or moisture enters into refrigerant cycle, that can cause deterioration of refrigerant oil or malfunction of com­pressor.
Charge refrigerant from liquid phase of gas cylinder.
If the refrigerant is charged from gas phase, composition change may occur in refrigerant and the efficiency will be lowered.
Do not use a charging cylinder.
If a charging cylinder is used, the composition of refrigera­nt will change and the efficiency will be lowered.
Ventilate the room if refrigerant leaks during operation. If refrigerant comes into contact with a flame, poisonous gases will be released.
[1] Cautions for service
(1) Perform service after recovering the refrigerant left in unit completely. (2) Do not release refrigerant in the air. (3) After completing service, charge the cycle with specified amount of refrigerant. (4) When performing service, install a filter drier simultaneously. Be sure to use a filter drier for new refrigerant.
[2] Additional refrigerant charge
When charging directly from cylinder
· Check that cylinder for R410A on the market is syphon type.
· Charging should be performed with the cylinder of syphon stood vertically. (Refrigerant is charged from liquid phase.)
3
Unit
Gravimeter
[3] Service tools
Use the below service tools as exclusive tools for R410A refrigerant.
No. Tool name Specifications 1 Gauge manifold · Only for R410A
· Use the existing fitting
· Use high-tension side pressure of 5.3MPa·G or over. 2 Charge hose · Only for R410A
· Use pressure performance of 5.09MPa·G or over. 3 Electronic scale 4 Gas leak detector · Use the detector for R134a, R407C or R410A. 5 Adaptor for reverse flow check · Attach on vacuum pump. 6 Refrigerant charge base 7 Refrigerant cylinder · Only for R410A · Top of cylinder (Pink)
· Cylinder with syphon 8 Refrigerant recovery equipment
specifications
. (UNF1/2)
3
PART NAMES AND FUNCTIONS
Indoor unit
Air inlet
Air outlet
Louver
Filter
Vane
Front grille
Emergency switch
operation
4
Wired remote controller
Display Section
For purposes of this explanation, all parts of the display are shown as lit. During actual operation, only the relevant items will be lit.
Identifies the current operation
Shows the operating mode, etc. *Multilanguage display is available.
“Centrally Controlled” indicator
Indicates that operation from the remote controller has been prohib­ited by a master controller.
“Timer is Off” indicator
Indicates that the timer is off.
Temperature Setting
Shows the target temperature.
Day-of-Week
Shows the current day of the week.
Time/Timer Display
Shows the current time, unless the simple or Auto Off timer is set. If the simple or Auto Off timer is set, the time to be switched off is shown.
TIME SUN MON TUE WED THU FRI SAT TIMER AFTER
ERROR CODE
°F°C
Hr AFTER
°F°C
ONLY1Hr.
Up/Down Air Direction indica­tor
The indicator shows the direc­tion of the outcoming airflow.
“One Hour Only” indicator
Displayed if the airflow is set to low or downward during COOL or DRY mode. (Operation varies according to model.) The indicator goes off in 1 hour, when the airflow direction also changes.
Room Temperature display
Shows the room temperature.The room temperature display range is 46–102˚F. The display blinks if the temperature is less than 46˚F or 102˚F or more.
Louver display
Indicates the action of the swing louver. Does not appear if the louver is not running.
(Power On indicator)
Indicates that the power is on.
ON OFF
FUNCTION
FILTER
WEEKLY
SIMPLE
AUTO OFF
“Sensor” indication
Displayed when the remote controller sensor is used.
“Locked” indicator
Indicates that remote controller but­tons have been locked.
“Clean The Filter” indicator
To be displayed on when it is time to clean the filter.
Timer indicators
The indicator comes on if the corre­sponding timer is set.
Fan Speed indicator
Shows the selected fan speed.
Ventilation indicator
Appears when the unit is running in Ventilation mode.
Operation Section
Temperature setting buttons
Down Up
Timer Menu button (Monitor/Set button)
Mode button (Return button)
TEMP.
Set Time buttons
Back
Ahead
Timer On/Off button (Set Day button)
Opening the lid
Note:
“PLEASE WAIT”message
This message is displayed for approximately 3 minutes when power is supplied to the indoorunit or when the unit is recoveringfrom a power failure. “NOT AVAILABLE” message
This message is displayed if an invalid button is pressed (to operate a function that the indoor unit does not have).
BACK DAY
PAR-21MAA
MENU
MONITOR/SET
CLOCK
ON/OFF
OPERATION
ON/OFF
FILTER
CHECK
TEST
CLEAR
Built-in temperature sensor
If a single remote controller is used to operate multiple indoor units simultaneously that are different types, this message will not be displayed as far as any of the indoor units is equipped with the function.
ON/OFF button
Fan Speed button
Filter button (<Enter> button)
Test Run button
Check button (Clear button)
Airflow Up/Down button
Louver button ( Operation button)
To return operation number
Ventilationbutton ( Operation button)
To go to next operation number
5
Wireless remote controller
CHECK
TEST RUN
display
Indicate that the unit is being checked or test-run.
MODEL SELECT
Blinks when model is selected.
display
display
Lights up while the signal is transmitted to the indoor unit when the button is pressed.
Temperature setting display
Indicates the desired temperature setting which is set.
OPERATION MODE display
OPERATION MODE display Indicates which operation mode is in effect.
display
The vertical direction of airflow is indicated.
display
Displaysselected fanspeed.
ON/OFF button
The unit is turned ON and OFF alternately
each time the button is pressed.
FAN SPEED SELECT button
Changes the fan speed.
MODE SELECT button
Switches the operation mode between COOLING/DRY/FAN/HEATING and AUTO mode.
In case the outdoor unit is cooling only type, the heating and auto mode are not available.
COOL
DRY
AUTO
FAN
HEAT
RUN
MODEL SELECT
FAN
SWING
NOTAVAILABLE
TEST
CHECK
ON/OFF TEMP
FAN
MODE
CHECK
VANE
LOUVER
TEST RUN
RESETSET CLOCK
°F °C
AMPMSTOP
AMPM
START
AUTO STOP
AUTO START
h
min
CLOCK display
Displays the current time.
TIMER display
Displays when in timer operation or when setting timer.
“ ” “ ” display
Displays the order of timer operation.
“ ” “ ” display
Displays whether timer is on or off.
button
Sets any desired room temperature.
TIMER CONTROL buttons
AUTO STOP (OFF timer): when this switch is set, the air conditioner will be automatically stopped at the preset time.
AUTO START (ON timer): when this switch is
set, the air conditioner will be automatically
started at the preset time.
"h" and "min" buttons
Buttons used to set the “hour and minute” of the current time and timer settings.
CHECK-TEST RUN button
Performs an inspection check or test operation. Do not use it for normal operation.
VANE CONTROL button
Changes the air flow direction.
LOUVER button
Changes left / right airflow direction.
(Not available for this model.)
CLOCK button
RESET button
SET button
6
4
SPECIFICATIONS
Service Ref.
Power supply(phase, cycle, voltage)
External finish Heat exchanger Fan Fan(drive) % No.
INDOOR UNIT
Operation control & Thermostat Noise level(Low-Middle-High) Field drain pipe I.D. Dimensions
Weight
Service Ref.
Power supply(phase, cycle, voltage)
External finish Heat exchanger Fan Fan(drive) % No.
INDOOR UNIT
Operation control & Thermostat Noise level(Low-Middle-High) Field drain pipe I.D. Dimensions
Weight
Max. Fuse Size Min.Circuit Ampacity
Fan motor output Fan motor
Airflow(Low-Middle-High) External static pressure
Max. Fuse Size Min.Circuit Ampacity
Fan motor output Fan motor
Airflow(Low-Middle-High)
External static pressure
W
D H
W
D H
A A
kW
F.L.A
m3/min(CFM)
Pa(mmAq)
dB mm(in.) mm(in.) mm(in.) mm(in.)
kg(lbs)
A
A
kW
F.L.A
*/min(CFM)
Pa(mmAq)
dB mm(in.) mm(in.) mm(in.) mm(in.)
kg(lbs)
PKA-A24KA.TH, PKA-A24KAL.TH
1 phase, 60Hz, 208/230V
15
1
White Munsell 1.0Y 9.2/0.2
Plate fin coil
Line flow fan (direct) % 1
0.056
0.36
Dry: 18-20-22 (635-705-775)
Wet: 16-18-20 (570-635-700)
0(direct blow)
Remote controller & built-in
39-42-45
16(5/8)
1170 (46-1/16)
295 (11-5/8)
365 (14-3/8)
21 (46)
PKA-A30KA.TH, PKA-A30KAL.TH
1 phase, 60Hz, 208/230V
15
1
White Munsell 1.0Y 9.2/0.2
Plate fin coil
Line flow fan (direct) % 1
0.056
0.36
Dry: 18-20-22 (635-705-775)
Wet: 16-18-20 (570-635-700)
0(direct blow)
Remote controller & built-in
39-42-45
16(5/8)
1170 (46-1/16)
295 (11-5/8)
365 (14-3/8)
21 (46)
Service Ref.
Power supply(phase, cycle, voltage)
External finish Heat exchanger Fan Fan(drive) % No.
INDOOR UNIT
Operation control & Thermostat Noise level(Low-Middle-High) Field drain pipe I.D. Dimensions
Weight
Max. Fuse Size Min.Circuit Ampacity
Fan motor output Fan motor
Airflow(Low-Middle-High) External static pressure
W
D H
A A
kW
F.L.A
3
/min(CFM)
m
Pa(mmAq)
dB mm(in.) mm(in.) mm(in.) mm(in.)
kg(lbs)
PKA-A36KA.TH, PKA-A36KAL.TH
1 phase, 60Hz, 208/230V
15
1
White Munsell 1.0Y 9.2/0.2
Plate fin coil
Line flow fan (direct) % 1
0.056
0.57
Dry: 20-23-26 (705-810-920)
Wet: 18-21-23 (635-730-830)
0(direct blow)
Remote controller & built-in
43-46-49
16(5/8)
1170 (46-1/16)
295 (11-5/8) 365 (14-3/8)
21 (46)
7
5
NOISE CRITERION CURVES
PKA-A24KA.TH
PKA-A24KA PKA-A30KA
PKA-A30KA.TH
PKA-A24KAL
PKA-A24KAL.TH
PKA-A30KAL
PKA-A30KAL.TH
90
80
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF
OCTAVE BAND SOUND PRESSURE LEVEL, dB(0dB=0.0002 μbar)
HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
NOTCH
High
Low
SPL(dB)39LINE
45
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
PKA-A36KA.TH PKA-A36KAL.TH
90
)
80
bar
70
60
50
40
30
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0dB= 0.0002 μ
APPROXIMATE
20
THRESHOLD OF HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
NOTCH
High
Low
SPL(dB)43LINE
49
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
UNIT
3.3ft
3.3ft
MICROPHONE
WALL
8
6
OUTLINES AND DIMENSIONS
PKA-A24KA.TH PKA-A30KA.TH PKA-A36KA.TH PKA-A24KAL.TH PKA-A30KAL.TH PKA-A36KAL.TH
Top side
17(431.7)16-11/16(423.7)
2-9/16(65.2)
5-17/132(140.3)
7/16(11)
Knock out hole for left piping
1-1/4(32)
23/32(18)
2-3/32(53)
Left side
A
1-3/16(30) 1-3/8(35)
2-19/32(66)
14-3/8(365)
Filter hook
33-21/32(855)2-29/32(74)
Front side(Grille open)
Front side
46-1/16(1170)
17-15/32(444)Gas pipe
18-31/32(482)Liquid pipe
23-1/32(585)Drain hose
Under side
9-1/2(241)
Terminal block for Outdoor unit Terminal block for power supply (option)
Terminal block for MA-remote controller (only PKA-A·KA models)
Emergency operation switch (cooling/heating)
4-27/32(123)
6-1/16(154) 5-9/32(134)
Right side
11-5/8(295)
Operation lamp
DEFROST/STAND BY lamp
Receiver
Unit: inch (mm)
Mount board
C
3/16(5)
Knock out hole for right piping
Min.9/32(7)
Sleeve (purchased locally)
:2-15/16 (:75)
Required space(Indoor unit)
Min.2-27/32(72.4)
75-:3/16(:5.1) Tapping screw hole
5/8(15.5)
31/32(25) 1-31/32(50) 2-15/16(75)
3-15/16(100) 4-19/32(117)
4-29/32(125)
5-19/32(142)
7-9/16(192) 9-17/32(242)
11(279.5)
11-1/2(292)
Through hole
:2-15/16~:3-5/32 (:75~:80)
20-3/8(517.4)
0
23-1/32(585)
20-7/8(530.5)
Vane(auto)
4-:11/3 2(:9) Bolt hole
17-9/32(439)
17-7/8(454)
16-3/32(408.5)
15-1/8(384)
14-11/32(364)
12-3/8(314)
15-1/8(384)
16-15/16(430.5)
13-11/32(339)
Wall hole for left rear piping
Air inlet
Air outlet
Min.2(50.5)Min.8-21/32(220)
0
7-7/16(189)
Knockout hole for rear piping 2-15/16×18-29/32(75×480)
Louver(manual) Knockout hole
for lower piping
Center measurement hole :3/32(:2.5)
2-1/8(54)
1/8(3)
0
13/32(10)
4-11/32(110)
2-3/8(60)
13/32(10)
2-3/8(60)
0
Min.1-7/8(48)
Min.9-27/32(250)
Mount board
4-11/32(110)
8-17/32(216.5)
Wall hole for right rear piping
R1-15/
32(R37.5)
14-11/32(364)
12-3/8(314)
13-11/32(339)
17-7/8(454)
15-1/8(384.5)
16-3/32(408.5)
17-9/32(439)
15-1/8(384)
13-3/4(349.2)
C
18-5/16(465.5)
17-11/16(449.2)
Indoor unit outline
Piping connection Liquid pipe
BB
Gas pipe Drain hose
2-5/8(67)
3-1/32(77)
5/16(7.8)
2-9/16(65)
2-1/8(54) 1-1/4(32) 31/32(25)
1/2(12.5) 0 1/2(12.5) 1-15/32(37.5)
2-15/32(62.5)
3-7/16(87.5)
4-1/8(104.5)
5-3/32(129.5)
6-9/16(167)
8-17/32(217)
9-1/32(229.5) 10-13/32(264)
11-1/2(292)
12-5/32(308.5) 12-1/4(311)
23-1/32(585)
Refrigerant pipe: 3/8 O.D(:9.52) Flared connection: 3/8F Refrigerant pipe: 5/8 O.D(:15.88) Flared connection: 5/8F
5/8(:16) O.D
Knockout hole for piping
B
2-9/16(65)
3-1/32(77) 3-7/16(87)
13/32(10.7)
3-1/32(77)
5/16(7.8)
A
2-5/8(67)
2-9/16(65)
9
7
WIRING DIAGRAM
PKA-A24KA.TH PKA-A30KA.TH PKA-A36KA.TH PKA-A24KAL.TH PKA-A30KAL.TH PKA-A36KAL.TH
Notes:
1.SymboIs used in wiring diagram above are, : Connector, : Terminal (block).
2.Indoor and outdoor connecting wires have poIarities, make sure to match terminal numbers (S1, S2, S3)for correct wirings.
3.Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric wiring diagram for servicing.
4.This diagram shows the wiring of indoor and outdoor connecting wires.(specification of 230V), adopting superimposed system for power and signal.
+
1: If indoor and outdoor units have separate power applies, refer to Fig 1.
+
2: For power supply system of this unit, refer to the caution label located near this diagram.
+
3: Use copper supply wires.
10
8
REFRIGERANT SYSTEM DIAGRAM
PKA-A24KA.TH PKA-A30KA.TH PKA-A36KA.TH PKA-A24KAL.TH PKA-A30KAL.TH PKA-A36KAL.TH
Heat exchanger
Strainer (#50)
Refrigerant GAS pipe connection (Flare)
Thermistor TH5 (Cond./ Eva.temperature)
Thermistor TH1 (Room temperature)
Thermistor TH2 Pipe temperature(Liquid)
Distributor with strainer (#50/#100)
Refrigerant flow in cooling Refrigerant flow in heating
Refrigerant LIQUID pipe connection (Flare)
Strainer (#50)
11
9
TROUBLESHOOTING
9-1. TROUBLESHOOTING
<Error code display by self-diagnosis and actions to be taken for service (summary)>
Present and past error codes are logged and displayed on the wired remote controller or controller board of outdoor unit. Actions to be taken for service and the trouble reoccurrence at field are summarized in the table below. Check the contents below before investigating details.
Unit conditions at service
The trouble is reoccurring.
Error code
Displayed
Not displayed
Judge what is wrong and take a corrective action according to “9-3. Self-diagnosis action table”.
Conduct troubleshooting and ascertain the cause of the trouble according to “9-4. Troubleshooting by inferior phenomena”.
Actions to be taken for service (summary)
Consider the temporary defects such as the work of protection devices in the refrigerant circuit including compressor, poor connection of wiring, noise and etc.
Logged
Re-check the symptom, and check the installation environment, refrigerant amount, weather when the trouble occurred, matters related to wiring and etc.
The trouble is not reoccurring.
Reset error code logs and restart the unit after finishing service. There is no abnormality in electrical component, controller board,remote controller and etc.
Re-check the abnormal symptom.
Conduct trouble shooting and ascertain the cause of the trouble
according to “9-4. Troubleshooting by inferior phenomena”.
Not logged
Continue to operate unit for the time being if the cause is not ascertained.
There is no abnormality concerning of parts such as electrical
component, controller board, remote controller and etc.
9-2. MALFUNCTION-DIAGNOSIS METHOD BY REMOTE CONTROLLER
<In case of trouble during operation>
When a malfunction occurs to air conditioner, both indoor unit and outdoor unit will stop and operation lamp blinks to inform unusual stop.
<Malfunction-diagnosis method at maintenance service>
CHECK display
ON/OFF button
CHECK button
ON/OFF
MODE
CHECK
TEST RUN
SET
CHECK
FAN
VANE
LOUVER
RESET
TEMP
CLOCK
AUTO STOP
AUTO START
h
min
Refrigerant address display
Temperature button
HOUR button
[Procedure]
1. Press the CHECK button twice.
2. Press the temperature buttons.
3. Point the remote controller at the sensor on the indoor unit and press the HOUR button.
4. Point the remote controller at the sensor on the indoor unit and press the ON/OFF button.
12
• "CHECK" lights, and refrigerant address "00" blinks.
• Check that the remote controller's display has stopped before continuing.
• Select the refrigerant address of the indoor unit for the self-diagnosis.
Note: Set refrigerant address using the
outdoor unit’s DIP switch (SW1).
(For more information, see the outdoor unit installation manual.)
• If an air conditioner error occurs, the indoor unit's sensor emits an intermit­tent buzzer sound, the operation lamp blinks, and the error code is output.
(It takes 3 seconds at most for error
code to appear.)
• The check mode is cancelled.
• Refer to the following tables for details on the check codes. [Output pattern A]
Beeper sounds OPERATION
INDICATOR lamp blink pattern
Beep
Self-check starts (Start signal received)
Beep Beep Beep Beep Beep Beep
1st2nd3
Off
Approx. 2.5 sec.On0.5 sec.On0.5 sec.On0.5 sec.
Number of blinks/beeps in pattern indicates the check code in the following table (i.e., n=5 for “P5”)
rd
0.5 sec.
th
n
On
[Output pattern B]
Beeper sounds OPERATION
INDICATOR lamp blink pattern
Self-check starts (Start signal received)
Off
Approx. 2.5 sec.OnApprox. 3 sec.On0.5 sec.On0.5 sec.On0.5 sec.
1st2nd3
Number of blinks/beeps in pattern indicates the check code in the following table (i.e., n=5 for “U2”)
[Output pattern A] Errors detected by indoor unit
Wireless remote controller
Wired remote controller
Beeper sounds/OPERATION
INDICATOR lamp blinks
Check code
(Number of times)
1P1 2
P2 Pipe (TH2) sensor error P9 Pipe (TH5) sensor error
3E6,E7
Intake sensor error
Indoor/outdoor unit communication error
4 P4 Float switch connector (CN4F) open 5
P5 PA
Drain pump error
Forced compressor stop(due to water leakage abnormality) 6 P6 Freezing/Overheating protection operation 7 EE Communication error between indoor and outdoor units 8 P8 Pipe temperature error 9 E4, E5 Remote controller signal receiving error
10 11
– –
– –
12 Fb Indoor unit control system error (memory error, etc.)
E0, E3
Remote controller transmission error – E1, E2 Remote controller control board error
nd
1st2
Off
Approx. 2.5 sec.On0.5 sec.On0.5 sec.
Number of blinks/beeps in pattern indicates the check code in the following table
peeBpeeBpeeBpeeBpeeB
rd
th
n
On
0.5 sec.
Approx. 2.5 sec.OnApprox. 3 sec.On0.5 sec.On0.5 sec.
· · · Repeated
Off
Beep Beep
Number of blinks/beeps in pattern indicates the check code in the following table
1st2
nd
· · · Repeated
krameRmotpmyS
[Output pattern B]
Wireless remote controller
Errors detected by unit other than indoor unit (outdoor unit, etc.)
Wired remote controller
Beeper sounds/OPERATION
INDICATOR lamp blinks Check code
(Number of times)
1 2
3 4
5
6 7
8 9
10 11 12
13 14
E9 UP
U3,U4 UF
U2
U1,Ud U5
U8 U6 U7
U9,UH
– –
Others
*1If the beeper does not sound again after the initial
the OPERATION INDICATOR lamp does not come on,
Indoor/outdoor unit communication error (Transmitting error) (Outdoor unit)
Compressor overcurrent interruption Open/short of outdoor unit thermistors Compressor overcurrent interruption (When compressor locked) Abnormal high discharging temperature/49C worked/
insufficient refrigerant Abnormal high pressure (63H worked)/Overheating
protection operation Abnormal temperature of heatsink Outdoor unit fan protection stop
Compressor overcurrent interruption/Abnormal of power module Abnormality of superheat due to low discharge temperature Abnormality such as overvoltage or voltage shortage and
abnormal synchronous signal to main circuit/Current sensor error
– –
Other errors (Refer to the technical manual for the outdoor unit.)
2 beeps to confirm the self-check start signal was received and
there are no error records.
For details, check the LED display of the outdoor controller board. As for outdoor unit, refer to outdoor unit's service manual.
*2If the beeper sounds 3 times continuously “beep, beep, beep (0.4 + 0.4 + 0.4 sec.)” after the initial 2 beeps to confirm
the self-check start signal was received, the specified refrigerant address is incorrect.
krameRmotpmyS
1313
• On wireless remote controller The continuous buzzer sounds from receiving section of indoor unit.
Blink of operation lamp
• On wired remote controller Check code displayed in the LCD. (Refer to the previous page, check code.)
If the unit cannot be operated properly after the test run, refer to the following table to find out the cause.
• Symptom
Wired remote controller LED 1, 2 (PCB in outdoor unit)
PLEASE WAIT
PLEASE WAIT
Display messages do not appear even when operation switch is turned ON (operation lamp does not light up).
On the wireless remote controller with condition above, following phenomena take place.
• No signals from the remote controller can be received.
• OPE lamp is blinking.
• The buzzer makes a short ping sound.
Note: Operation is not possible for about 30 seconds after cancellation of function selection. (Correct operation)
For description of each LED (LED1, 2, 3) provided on the indoor controller, refer to the following table.
LED1 (power for microcomputer) Indicates whether control power is supplied. Make sure that this LED is LED2 (power for remote controller)
LED3 (communication between indoor and outdoor units)
Error code
For about 2 minutes after power-on
Subsequent to about 2 minutes after power-on
After LED 1, 2 are lighted, LED 2 is
turned off, then only LED 1 is lighted.
(Correct operation)
Only LED 1 is lighted.
Only LED 1 is lighted.
always lit. Indicates whether power is supplied to the remote controller.
This LED lights only in the case of the indoor unit which is connected to the outdoor unit refrigerant addresses “0”.
Indicates state of communication between the indoor and outdoor units. Make sure that this LED is always blinking.
LED 1, 2 blink.
LED 1 blinks twice, LED 2 blinks once.
• For about 2 minutes following power-on,op­eration of the remote controller is not possible due to s y s t e m s t a rt- u p. (Correct operation)
•Connector for the outdoor unit’ s protection devi c e i s n o t c o nnected.
•Reverse or open phase wiring for the outdoor unit’s power terminal block (L1, L2, GR)
•Incorrect wiring between indoor and outdoor units (incorrect polarity of S1, S2, S3)
•Remote controller wire short
Cause
14
9-3. SELF-DIAGNOSIS ACTION TABLE
Error Code
P1
P2
Abnormal point and detection method
Room temperature thermistor (TH1)
The unit is in 3-minute resume prevention mode if short/open of thermistor is detected.Abnormal if the unit does not reset normally after 3 min­utes. (The unit returns to normal opera­tion, if it has been reset normally.) Constantly detected during cooling, drying, and heating operation. Short: 90 Open: -40
Pipe temperature thermistor/Liquid (TH2)
The unit is in 3-minute resume prevention mode if short/open of thermistor is detected.Abnormal if the unit does not reset normally after 3 min­utes. (The unit returns to normal opera­tion, if it has been reset normally.) Constantly detected during cooling, drying, and heating (except defrosting) operation. Short: 90 Open: -40
Note: Refer to the manual of outdoor unit for the details of display suchas F,U, and other E.
Cause
Defective thermistor characteristics Contact failure of connector (CN20) on the indoor controller board (Insert failure) Breaking of wire or contact failure of thermistor wiring Defective indoor controller board
Defective thermistor characteristics Contact failure of connector (CN44) on the indoor controller board (Insert failure) Breaking of wire or contact failure of thermistor wiring Defective refrigerant circuit is causing thermistor tempera­ture of 90
-40 Defective indoor controller board
Countermeasure
– Check resistance value of thermistor.
••••••••••
0 10 20 30 40
••••••••••••
••••••••••••
••••••••••••
•••••••••••
15.0k
9.6k
6.3k
4.3k
3.0k If you put force on (draw or bend) the lead wire while measuring resistance value of thermis­tor, breaking of wire or contact failure can be detected.
Check contact failure of connector (CN20) on the indoor controller board. Refer to 9-7. Turn the power on again and check restart after inserting connector again. Check room temperature display on remote controller. Replace indoor controller board if there is abnormal difference with actual room temperature.
Turn the power off, and on again to operate after check.
Check resistance value of thermistor.
For characteristics, refer to (P1) above.
Check contact failure of connector (CN44) on the indoor controller board. Refer to 9-7. Turn the power on and check restart after inserting connector again. Check pipe <liquid> temperature with remote controller in test run mode. If pipe <liquid> temperature is extremely low (in cooling mode) or high (in heating mode), refrigerant circuit may have defect. Check pipe <liquid> temperature with remote controller in test run mode. If there is extremely difference with actual pipe <liquid> temperature, replace indoor controller board.
P4
(5701)
P5
Contact failure of drain float switch (CN4F)
Extract when the connector of drain float switch is disconnected.
and of connector CN4F is not
( short-circuited.) Constantly detected during operation.
Drain overflow protection operation
Suspensive abnormality, if drain float switch is detected to be underwater for 1 minute and 30 seconds continuously with drain pump on. Turn off compressor and indoor fan. Drain pump is abnormal if the condition above is detected during suspensive abnormality. Constantly detected during drain pump operation.
Contact failure of connector (Insert failure)
Defective indoor controller board
Malfunction of drain pump Defective drain Clogged drain pump Clogged drain pipe Defective drain float switch Catch of drain float switch or malfunction of moving parts cause drain float switch to be detected under water (Switch On) Defective indoor-controller board
15
Turn the power off, and on again to operate after check.
Check contact failure of float switch connec­tor. Turn the power on again and check after inserting connector again. Operate with connector (CN4F) short-circuited. Replace indoor controller board if abnormality reappears.
Check if drain-up machine works.
Check drain function.
Remove drain float switch connector CN4F and check if it is short (Switch On) with the moving part of float switch UP, or OPEN with the moving part of float switch down. Replace float switch if it is short with the moving part of float switch down. Replace indoor controller board if it is short­circuited between
- of the drain float switch connector CN4F and abnormality reappears.
It is not abnormal if there is no problem about the above-mentioned
~ Turn the power off, and on again to operate after check.
Error Code
Abnormal point and detection method
Freezing/overheating protection is work­ing
Freezing protection (Cooling mode) The unit is in 6-minute resume prevention mode if pipe <liquid or condenser/evapo­rator> temperature stays under
the compressor started.Abnormal if it again within 16 minutes after 6-minute
resume prevention mode.
Cause
(Cooling or drying mode)
Clogged filter (reduced airflow) Short cycle of air path Low load (low temperature) operation out of the tolerance range Defective indoor fan motor
• Fan motor is defective.
• Indoor controller board is defec­tive. Defective outdoor fan control Overcharge of refrigerant Defective refrigerant circuit (clogs)
Countermeasure
(Cooling or drying mode)
Check clogs of the filter. Remove shields.
Refer to 9-6.
Check outdoor fan motor.
Check operating condition of refrigerant circuit.
P6
P8
Overheating protection (Heating mode) The units is in 6-minute resume prevention mode if pipe <liquid or
condenser/ detected as over 70°C[158°F] after the compressor started. Abnormal if the temperature of over 70°C[158°F] is detected again within 10 minutes after 6 minute resume prevention mode.
Pipe temperature
<Cooling mode> Detected as abnormal when the pipe tem­perature is not in the cooling range 3 min­utes after compressor start and 6 minutes after the liquid or condenser/evaporatorpipe is out of cooling range. Note 1) It takes at least 9 minutes to detect. Note 2) Abnormality P8 is not detected in
Cooling range : - (TH-TH1) TH: Lower temperature between liquid pipe
temperature (TH2) and condenser/ evaporator temperature (TH5)
TH1: Intake temperature <Heating mode>
When 10 seconds have passed after the compressor starts operation and the hot adjustment mode has finished, the unit is detected as abnormal when condenser/ evaporator pipe temperature is not in heat­ing range within 20 minutes. Note 3) It takes at least 27 minutes to
Note 4) It excludes the period of defrosting
Heating range : (TH5-TH1)
evaporator> temperature is
drying mode.
detect abnormality. (Detection restarts when defrosting
mode is over)
(Heating mode)
Clogged filter (reduced airflow) Short cycle of air path Overload (high temperature) operation out of the tolerance range Defective indoor fan motor
• Fan motor is defective.
• Indoor controller board is defec­tive. Defective outdoor fan control Overcharge of refrigerant Defective refrigerant circuit (clogs) Bypass circuit of outdoor unit is defective.
Slight temperature difference between indoor room temperature and pipe <liquid or condenser/evaporator> temperature thermistor
• Shortage of refrigerant
• Disconnected holder of pipe <liquid or condenser/
evaporator> thermistor
• Defective refrigerant circuit
Converse connection of extension pipe (on plural units connection) Converse wiring of indoor/ outdoor unit connecting wire (on plural units connection) Defective detection of indoor room temperature and pipe <condenser/evaporator> temperature thermistor Stop valve is not opened completely.
(Heating mode)
Check clogs of the filter. Remove shields.
Refer to 9-6.
Check outdoor fan motor.
Check operating condition of refrigerant
~
circuit.
~ Check pipe <liquid or condenser/evap-
orator> temperature with room tempera­ture display on remote controller and outdoor controller circuit board. Pipe <liquid or condenser/evaporator> temperature display is indicated by set­ting SW2 of outdoor controller circuit board as follows.
Conduct temperature check with outdoor controller circuit board after connecting
(
‘A-Control Service Tool(PAC-SK52ST)’.
Check converse connection of extension pipe or converse wiring of indoor/outdoor unit connecting wire.
)
16
Error Code
P9
Abnormal point and detection method
Pipe temperature thermistor/ Condenser-Evaporator (TH5)
The unit is in 3-minute resume protec­tion mode if short/open of thermistor is detected. Abnormal if the unit does not get back to normal within 3 minutes. (The unit returns to normal operation, if it has been reset normally.) Constantly detected during cooling, drying, and heating operation (except defrosting)
Cause
Defective thermistor characteristics Contact failure of connector (CN44) on the indoor controller board (Insert failure) Breaking of wire or contact failure of thermistor wiring Temperature of thermistor is
defective refrigerant circuit. Defective indoor controller board
Countermeasure
– Check resistance value of thermistor.
For characteristics, refer to (P1) above. Check contact failure of connector (CN44) on the indoor controller board. Refer to 9-7. Turn the power on and check restart after inserting connector again. Operate in test run mode and check pipe <con­denser/evaporator> temperature with outdoor controller circuit board. If pipe <condenser/evaporator> temperature is exclu­sively low (in cooling mode) or high (in heating mode), refrigerant circuit may have defect. Operate in test run mode and check pipe <con­denser/evaporator> temperature with outdoor control circuit board. If there is extreme difference with actual pipe <condenser/evaporator> temperature, replace indoor controller board. There is no abnormality if none of above comes within the unit. Turn the power off and on again to operate.
In case of checking pipe temperature with outdoor controller circuit board, be sure to connect A-control service
(
tool (PAC-SK52ST).
)
PA
(2500)
E0
or
E4
Forced compressor stop (due to water leakage abnormality)
The unit has a water leakage abnor­mality when the following conditions, a) and b), are satisfied while the above­mentioned detection is performed.
a) The intake temperature subtracted
with liquid pipe temperature detects to be less than -10 [14 30 minutes. (When the drain sensor is detected to be NOT soaked in the water, the detection record of a) and b) will be cleared.)
b) Drain float switch detects to be in the
water for more than 15 minutes.
*Once the water leakage abnormality is
detected, abnormality state will not be released until the main power is reset.
Remote controller transmission error(E0)/signal receiving error(E4)
Abnormal if main or sub remote con-
troller cannot receive any transmission
normally from indoor unit of refrigerant
address “0” for 3 minutes.
(Error code : E0)
Abnormal if sub remote controller could
not receive for any signal for 2 minutes.
(Error code: E0)
Abnormal if indoor controller board
cannot receive any data normally from
remote controller board or from other
indoor controller board for 3 minutes.
(Error code: E4)
Indoor controller board cannot receive
any signal from remote controller for 2
minutes. (Error code: E4)
Drain pump trouble Drain defective
· Drain pump clogging
· Drain pipe clogging Open circuit of float switch Contact failure of float switch connector Dew condensation on float switch
·Drain water descends along lead wire.
·Drain water waving due to filter clogging. Extension piping connection difference at twin, triple, quad­ruple system. Miswiring of indoor/outdoor connecting at twin, triple, quad­ruple system. Room temperature thermistor/ liquid pipe temperature thermis­tor detection is defective.
Contact failure at transmission wire of remote controller All remote controllers are set as “sub” remote controller. In this case, E0 is displayed on remote controller, and E4 is displayed at LED (LED1, LED2) on the outdoor controller circuit board. Miswiring of remote controller Defective transmitting receiving circuit of remote controller Defective transmitting receiving circuit of indoor controller board of refrigerant addresses “0”. Noise has entered into the transmission wire of remote controller.
Check the drain pump. Check whether water can be drained.
Check the resistance of the float switch. Check the connector contact failure.
Check the float switch leadwire mounted.
Check the filter clogging.
Check the piping connection.
Check the indoor/outdoor connecting wires.
Check the room temperature display of
remote controller. Check the indoor liquid pipe temperature dis­play of outdoor controller board.
Check disconnection or looseness of indoor unit or transmission wire of remote controller. Set one of the remote controllers “main” if there is no problem with the action above. Check wiring of remote controller.
(Do not use cable
• The number of connecting indoor units: max. 16 units
• The number of connecting remote control ler: max. 2 units
When the above-mentioned problem of ~ are not applied,
Diagnose remote controllers. a) When “RC OK” is displayed, remote con-
trollers have no problem. Turn the power off, and on again to check. If abnormality generates again, replace indoor controller board.
b) When “RC NG” is displayed, replace
remote controller. c) When “RC E3” or “ERC 00-06” is dis­ played, noise may be causing abnormality.
If the unit is not normal after replacing indoor controller board in group control, indoor controller board of address “0” may be abnormal.
3 or more.)
-
17
Error Code
E3
or
E5
Abnormal point and detection method
Remote controller transmission error(E3)/signal receiving error(E5)
Abnormal if remote controller could not find blank of transmission path for 6 sec­onds and could not transmit.
(Error code: E3)
Remote controller receives transmitted data at the same time, compares the data, and when detecting it, judges different data to be abnormal 30 continuous times. (Error code: E3)
Abnormal if indoor controller board could not find blank of transmission path.
(Error code: E5)
Indoor controller board receives trans­mitted data at the same time, compares the data,and when detecting it, judges different data to be abnormal 30 continuous times. (Error code: E5)
Cause
2 remote controllers are set as
“main.” (In case of 2 remote con­ trollers)
Remote controller is connected
with 2 indoor units or more.
Repetition of refrigerant
address
Defective transmitting receiving
circuit of remote controller
Defective transmitting receiving
circuit of indoor controller board
Noise has entered into trans-
mission wire of remote control-
ler.
Countermeasure
Set a remote controller to main, and the other to sub.
Remote controller is connected with only one indoor unit. The address changes to a separate setting.
~ Diagnose remote controller.
a) When “RC OK” is displayed, remote con-
trollers have no problem. Turn the power off, and on again to check. When becoming abnormal again, replace indoor controller board.
b) When “RC NG” is displayed, replace
remote controller.
c) When “RC E3” or “ERC 00-66” is dis-
played, noise may be causing abnormal­ity.
E6
E7
Fb
Indoor/outdoor unit communication error (Signal receiving error)
Abnormal if indoor controller board cannot receive any signal normally for 6 minutes after turning the power on. Abnormal if indoor controller board cannot receive any signal normally for 3 minutes. Consider the unit as abnormal under the following condition: When 2 or more indoor units are connected to an outdoor unit, indoor controller board cannot receive a signal for 3 minutes from outdoor controller circuit board, a signal which allows outdoor controller circuit board to transmit signals.
Indoor/outdoor unit communication error (Transmitting error)
Abnormal if indoor controller board receives “1” 30 times continuously when indoor controller board transmits “0” signal.
Indoor controller board
Abnormal if data cannot be read normally from the nonvolatile memory of the indoor controller board.
Contact failure, short circuit or, miswiring (converse wiring) of indoor/outdoor unit connecting wire Defective transmitting receiving circuit of outdoor controller circuit board Defective transmitting receiving circuit of indoor controller board Noise has entered into indoor/ outdoor unit connecting wire.
Defective transmitting receiving circuit of indoor controller board Noise has entered into power supply. Noise has entered into outdoor control wire.
Defective indoor controller board
Check LED display on the outdoor control circuit board. (Connect A-control service tool, PAC-SK52ST.) Refer to EA-EC item if LED displays EA-EC.
Check disconnection or looseness of indoor/ outdoor unit connecting wire of indoor unit or
outdoor unit. Check all the units in case of twin indoor unit system.
- Turn the power off, and on again to check. If abnormality generates again, replace indoor controller board or outdoor controller circuit board.
Other indoor controller board may have defect in case of twin indoor unit system.
- Turn the power off, and on again to check. If abnormality generates again, replace indoor controller board.
Replace indoor controller board.
E1
or
E2
Remote controller control board
Abnormal if data cannot be read nor­mally from the nonvolatile memory of the remote controller control board.
(Error code: E1)
Abnormal if the clock function of remote controller cannot be operated normally.
(Error code: E2)
Defective remote controller Replace remote controller.
18
9-4. TROUBLESHOOTING BY INFERIOR PHENOMENA
Note: Refer to the manual of outdoor unit for the detail of remote
controller.
Phenomena
(1)LED2 on indoor controller board is off.
• When LED1 on indoor controller board is also off. Power supply of rated voltage is not supplied to out-
door unit.
Defective outdoor controller circuit board
Power supply of 208/230V is not supplied to indoor
unit.
Defective indoor controller board
Cause
Countermeasure
Check the voltage of outdoor power
supply terminal block (L1, L2).
• When AC 208/230V is not detected, check the power wiring to outdoor unit and the breaker.
• When AC 208/230V is detected, check
(below).
Check the voltage between outdoor
terminal block S1 and S2.
• When AC 208/230V is not detected, —check the fuse on outdoor controller circuit board.
—check the wiring connection.
• When AC 208/230V is detected, check
(below).
Checkthevoltagebetweenindoorterminal
block S1 and S2.
• When AC 208/230V is not detected, check indoor/outdoor unit connecting wire for miswiring.
• When AC 208/230V is detected, check
(below).
Check the fuse on indoor controller board. Check the wiring connection. If no problem are found, indoor controller board is defective.
(For the separate indoor/outdoor unit power sup-
ply system)
Power supply of 208/230V AC is not supplied to indoor unit.
The connectors of the optional replacement kit are not used.
Defective indoor controller board
• When LED1 on indoor controller board is lit. Mis-setting of refrigerant address for outdoor unit
(There is no unit corresponding to refrigerant address “0”.)
Check the voltage of indoor power supply
terminal block (L1,L2).
• When AC208/230V is not detected, check the power supply wiring.
• When AC208/230V is detected, check
(below).
Check that there is no problem in the
method of connecting the connectors.
• When there are problems in the method of connecting the connectors, connect the connector correctly referring to installation manual of an optional kit.
• When there is no problem in the meth­od of connecting the connectors, check
(below).
Check the fuse on indoor controller board. Check the wiring connection. If no problem are found, indoor controller board is defective.
Check again the setting of refrigerant address for outdoor unit.
Set the refrigerant address to “0”.
(For grouping control system under
which 2 or more outdoor units are connected, set one of the units to “0”.) Set refrigerant address using SW1 (3-6) on outdoor controller circuit board.
19
Phenomena
(2)LED2 on indoor controller board is blinking.
Note: Refer to the manual of outdoor unit for the detail of remote
controller.
Cause
• When LED1 on indoor controller board is also blinking. Connection failure of indoor/outdoor unit connecting wire
• When LED1 is lit.
Miswiring of remote controller wires Under twin indoor unit system, 2 indoor
wired together.
Refrigerant address for outdoor unit is wrong or not
set. Under grouping control system, there are some units whose refrigerant address is 0.
Short-cut of remote controller wires
Defective remote controller
units are
Countermeasure
Check indoor/outdoor unit connecting wire for connection failure.
Check the connection of remote con­troller wires in case of twin indoor unit system. When 2 indoor units are wired in one refrigerant system, connect remote controller wires to one of those units. Check the setting of refrigerant address in case of grouping control system.
If there are some units whose refrigerant
addresses are 0 in one group, set one of the units to 0 using SW1 (3-6) on outdoor
controller circuit board.
Remove remote controller wires and
check LED2 on indoor controller board.
• When LED2 is blinking, check the short­circuit of remote controller wires.
• When LED2 is lit, connect remote controller wires again and:
if LED2 is blinking, remote controller is defective; if LED2 is lit, connection failure of remote controller terminal
block etc. has returned to normal.
(3)Upward/downward vane performance failure
(4)Receiver for wireless remote controller
The vane is not downward during defrosting and heat preparation and when the thermostat is OFF in HEAT mode. (Working of COOL protection function) Vane motor does not rotate.
• Defective vane motor
• Breaking of wire or connection failure of connector
Upward/downward vane does not work.
• The vane is set to fixed position.
Weak batteries of wireless remote controller Contact failure of connector (CNB) on wireless
remote controller board
(Insert failure) Contact failure of connector (CN90) on indoor con­troller board (Insert failure) Contact failure of connector between wireless remote controller board and indoor controller board
Normal operation (The vane is set to horizontal regardless of remote control.)
Check
• Check the vane motor. (Refer to “How
• Check for breaking of wire or connec­Normal operation (Each connector on
vane motor side is disconnected or set­ting the fixed vanes by wired remote controller.)
Replace batteries of wireless remote con­troller.
~
When the same trouble occurs even if
(left). to check the parts”.) tion failure of connector.
Check contact failure of each connector.
If no problems are found of connector, replace indoor controller board.
indoor controller board is replaced, replace wireless remote controller board.
20
9-5. EMERGENCY OPERATION
9-5-1. When wireless remote controller fails or its battery is exhausted
When the remote controller cannot be used
When the batteries of the remote controller run out or the remote controller malfunctions, the emergency operation can be done using the emergency buttons.
DEFROST/STAND BY lamp (ORANGE)
Operation lamp (GREEN)
Emergency operation switch (cooling/heating)
Receiver
 
• Each press of the emergency operation switch will toggle the operation mode.
• Check “COOL/HEAT” with the operation monitor display. (The display will appear orange for 5 seconds after pressing the emergency operation switch.)
[Heat pump type]
Cooling Heating Stop
[Cooling Only type]
Cooling Stop
Operation Monitor Display
GREEN ORANGE STOP COOL
HEAT
OFF ON
The orange lamp follows the switch operation as indicated at the left for 5 sedonds, and then it will return to the normal display.
* Details of emergency mode are as shown below.
Operation Mod Set Temperature
Fan Speed
Airflow Direction Up and Down Horizontal
COOL HEAT
24°C, 75°F 24°C, 75°F
High High
Downward
9-5-2. When wired remote controller or indoor unit microcomputer fails
1. When the wired remote control or the indoor unit microcomputer has failed, but all other components work properly, if you set the switch (SWE) on the indoor controller board ON, the indoor unit will begin Emergency Operation. When Emergency Operation is activated, the indoor unit operates as follows: (1) Indoor fan is running at high speed. + Note on the wireless remote control When the remote control does not function, it is possible to activate Emergency Operation by using the indoor unit Emergency Operation switch. However, if the indoor unit microcomputer has failed, it is nesessary to proceed with points 2 and 3 below as in the case of the wired remote control.
2. When you activate Emergency Operation of the cooling or heating, you have to set the switch (SWE) on the indoor controller board and activate Emergency Operation of the outdoor unit. For details on how to activate Emergency Operation of the outdoor unit, refer to the outdoor unit wiring diagram.
3. Before you activate Emergency Operation, check the following points: (1) Emergency operation cannot be activated when:
• the outdoor unit malfunctions. • the indoor fan malfunctions.
• when it has detected the malfunction of drain-up machine during self-diagnosing. (2) Emergency Operation becomes continuous only by switching the power source on/off. ON/OFF on the remote control or temperature control etc. does not function. (3) Avoid operating for a long time when the outdoor unit begins defrosting while Emergency Operation of the heating is activated, because it will start to blow cold air. (4) Emergency cooling should be limited to 10 hours maximum (The indoor unit heat exchanger may freeze). (5) After Emergency Operation has been deactivated, set the switches etc. to their original positions. (6) Movement of the vanes does not work in Emergency operation, therefore you have to slowly set them manually to the appropriate position.
21
9-6. HOW TO CHECK THE PARTS PKA-A24KA.TH PKA-A30KA.TH PKA-A36KA.TH
PKA-A24KAL.TH PKA-A30KAL.TH PKA-A36KAL.TH
Parts name Check points
Room temperature thermistor (TH1) Liquid pipe thermistor (TH2) Condenser/evaporator temperature thermistor (TH5)
Vane motor (MV)
Red
Yellow
Brown
Connect pin No.
Orange
M
Disconnect the connector then measure the resistance using a tester. (At the ambient temperature 50"F~86"F)
Normal
4.3k~9.6k
Measure the resistance between the terminals using a tester. (Coil temperature 68"F)
Green
-
Brown-Red
-
Brown-Orange
Abnormal
Open or short
Normal
Brown-Yellow
250 ± 7%
-
(Refer to the next page for a detail.)
-
Brown-Green
Open or short
Abnormal
Fan motor (MF)
Refer to 9-6-2.
9-6-1. Thermistor
<Thermistor Characteristic graph>
Thermistor for lower temperature
Thermistor R Fixed number of B=3480 ± 2%
t(
)Rt=15exp { 3480( ) }
0 10 20 25 30 40
0=15k ±3%
Room temperature thermistor (TH1) Pipe temperature thermistor/liquid (TH2) Condenser/evaporator temperature thermistor (TH5)
1
273+t1273
273+
1
T-32
1.8
1
273
<Thermistor for lower temperature>
50
40
30
20
Resistance (k )
10
0
-20 -10 0 10 20 30 40 50
-4 -14 32 50 68 86 104122 °F Temperature
°C
22
9-6-2. DC Fan motor (fan motor/indoor controller circuit board)
Check method of DC fan motor (fan motor/indoor controller circuit board)
Notes
· High voltage is applied to the connecter (CNMF) for the fan motor. Pay attention to the service.
· Do not pull out the connector (CNMF) for the motor with the power supply on. (It causes trouble of the indoor controller circuit Self check
Symptom : The indoor fan cannot rotate.
Wiring contact check
Contact of fan motor connector (CNMF)
board and fan motor.)
Is there contact failure?
No
Power supply check (Remove the connector (CNMF))
Measure the voltage in the indoor controller circuit
TEST POINT
: VDC (between 1 (+) and 3 (-) of the fan connector): VDC DC294~325V
Yes
Wiring recovery
board.
TEST POINT  : VCC (between 4 (+) and 3 (-) of the fan connector): VCC DC15V
Is the voltage normal?
Yes
No
Indoor controller board fuse check
Is the fuse normal?
Replace the indoor
controller board.
Check the operation
Replace the fan motor.
Sensor signal check
Measure the voltage between CNMF
and DC 0V
and DC 15V in the indoor controller circuit board.
Yes
NG
NG
No
Replace the fuse.
Check the operation END
OK
END
OK
Does the voltage repeat DC 0V and DC 15V?
Yes
Replace the indoor
controller board.
OK
Check the operation END
NG
Replace the fan motor.
No
Replace the fan motor.
Yes
Check the operation of fan. END
NG
Replace the indoor controller board.
23
OK
9-7. TEST POINT DIAGRAM
Indoor controller board
PKA-A24KA.TH PKA-A30KA.TH PKA-A36KA.TH PKA-A24KAL.TH PKA-A30KAL.TH PKA-A36KAL.TH
SWE
Emergency operation connector
SW1
Model selection
SW2
Capacity setting
CNMF
Connect to the fan motor (MF)
1-3 : DC294~325V 4-3 : DC15V 5-3 : DC0~6.5V 6-3 : DC0
or DC15V
CN01
Connect to the Terminal block (TB4) 1-3 : 208/230VAC
{
FUSE
(3.15A 250V)
LED1:Power supply (I.B) LED2:Power supply (R.B) LED3:Transmission
(Indoor/outdodr)
CN3C
Transmission (Indoor/outdodr) (DC 0~24V)
CN151
Connect to the vane motor (MV)
Jumper wire J41,J42
Pair No. setting for wireless remote controller
CN152 Connector (Back-up heating)
CN44
Pipe temperature thermistor
1-2 : Liquid (TH2) 3-4 :
Condenser/Evaporator
(TH5)
CN20
Room temp. thermistor (TH1)
SWE2
Emergency operation switch
CN2L
Connector (LOSSNAY)
CN41
Connector (HA terminal-A)
Wireless remote controller board
CN22
Connect to the terminal block (TB5) (Remote controller connecting wire) (only PKA-A·KA)
CN30
Connector (LLC)
CN32
Remote switch
CN90
Connect to the remote operation adapter
CN51
Centrally control
24
9-8. FUNCTIONS OF DIP SWITCH AND JUMPER WIRE
Each function is controlled by the dip switch and the jumper wire on control P.C. board.
(Marks in the table below) Jumper wire ( : Short : Open)
Jumper wire
SW1
SW2
J41 J42
Functions
Model settings
Capacity settings
Pair number setting with wireless remote controller
Setting by the dip switch and jumper wire
MODELS
PKA-A·KA(L)
MODELS
A24
A30
A36
Wireless remote controller setting
0 1 2
3 ~ 9
SETTING
12345
SETTING
12345
12345
12345
Control PCB setting
ON OFF
ON OFF
ON OFF
ON OFF
J41 J42
Remarks
<Initial setting> Wireless remote controller: 0 Control PCB: (for both J41 and J42) 4 pair number settings are supported. The pair number settings of the wireless remote controller and indoor control PCB (J41/J42) are given in the table on the left. (' ' in the table indicates the jumper wire is dis­connected.)
JP3
Indoor controller board type setting
Indoor controller board type
For product Spare parts
JP3
: With JP3 : Without JP3
25
10
SPECIAL FUNCTION
10-1. Rotation Function (and back-up function, 2nd stage cut-in function)
Only PKA-A·KA (Wired remote controller use model)
10-1-1. Operation
(1) Rotation function (and Back-up function)
Outline of functions
· Main and sub units operate alternately according to the interval of rotation setting. w Main and sub unit should be set by refrigerant address. (Outdoor Dip switch setting)
Refrigerant address "00" Main unit Refrigerant address "01" Sub unit
· When error occurs to one unit, another unit will start operation. (Back-up function)
System constraint
· This function is available only by the grouping control system (INDOOR UNIT: OUTDOOR UNIT=1:1) of 2 refrigerant groups. (Refer to Fig. 1)
· Main indoor unit should be connected for wired remote controller and the transmission line (TB5) for main and sub unit should also be connected. (Refer to Fig. 1)
(This function cannot be set by wireless remote controller.)
· Set refrigerant address of each unit. (Dip switch on the outdoor unit ··· Refrigerant address 00/01)
Operation pattern
[Back-up function only]··· Request code number "312"
Start operation
Main
unit IC-1
Run
Error occurs on main unit. Main Sub
Abnormal condition
Fig. 1
Main unit
Refrigerant address "00"
OC-1
3(2)
Refrigerant address "01"
OC-2
3(2)
Sub unit
Sub unit IC-2

[Rotation function] & [Back-up function]··· Request code number "313~318"
Start operation
Main
unit IC-1
Sub unit IC-2
(Ex:When the request code number is "313", each unit operates alternately in daily cycle.)
Stop
Main Sub Sub Main Main Sub
Run
Stop
1~28 days 1~28 days
Stop
Run
Run
Error occurs on main unit.
Abnormal condition
Run
Stop Run
IC-1
2
RC
OC : Outdoor unit IC : Indoor unit RC : Wired remote controller
2
IC-2
Note:
· When the uint is restarted to operate after turning off the power or OFF operation, the unit which was operating will start oper­ation.
· To operate the main unit, refer to the 10-1-2. and set the requet code No. which is not the same as the current one, and set again the former request code No.
(2) 2nd stage cut-in function
Outline of functions
· When the 1st unit can NOT supply with sufficient capacity for exceptionally high-demand conditions and the actual room temperature reaches set point *, the 2nd unit starts operation in conjunction with the 1st unit.
· Once the actual room temperature goes down to 4degrees C (7.5 degrees F) below set point*, the 2nd unit stops operation automatically. (* set point = set temperature by R/C (remote controller) + 4, 6, 8:(7.5, 10.8, 14.4°F) (selectable))
· Number of operating units is determined according to the room temperature and set point.
· When room temperature becomes higher than set point, standby unit starts. (2 units operation)
· When room temperature falls below set point -4:(-7.5°F), standby unit stops. (1 unit operation)
26
System constraint
· This function is available only in cooling mode. Ex.) Set temp. by R/C = 20:(68°F)
Set point = 26:(79°F) When request code number is “323”.
26: 2nd unit Cut-in
(79°F)
4 degree C
(7.5 degreeF)
22: 2nd unit Cut-out
(71.5°F)
[2nd stage cut-in function]··· Request code number "322~324"
Start operation Sub unit start operation
Main
unit IC-1
Sub unit IC-2
Room temp. Set point
Run
Stop StopRun
20:
(68°F)
10-1-2. How to set rotation function (Back-up function, 2nd stage cut-in function)
You can set these functions by wired remote controller.(Maintenance monitor)
NOTE
Both main and sub unit should be set in same setting. Every time replacing indoor controller board for servicing, the function should be set again.
(1) Request Code List Rotation setting
Setting No. (Request code)
No.1 (310)
No.2 (311)
No.3 (312)
No.4 (313)
No.5 (314)
No.6 (315)
No.7 (316)
No.8 (317)
No.9 (318)
Setting contents
Monitoring the request code of current setting.
Rotation and Back-up OFF (Normal group control operation)
Back-up function only Rotation ON (Alternating interval = 1day) and back up function Rotation ON (Alternating interval = 3day) and back up function Rotation ON (Alternating interval = 5day) and back up function Rotation ON (Alternating interval = 7day) and back up function Rotation ON (Alternating interval = 14day) and back up function Rotation ON (Alternating interval = 28day) and back up function
Initial setting
Room temp. < Set point -4(-7.5°F)
Sub unit stop
2nd stage cut-in setting
Setting No. (Request code)
No.1 (320)
No.2 (321)
No.3 (322)
No.4 (323)
No.5 (324)
Setting contents
Monitoring the request code of current setting.
Cut-in function OFF
Cut-in Function ON(Set point = Set temp.+ 4°C(7.5°F))
Cut-in Function ON(Set point = Set temp.+ 6°C(10.8°F))
Cut-in Function ON(Set point = Set temp.+ 8°C(14.4°F))
2727
Initial setting
(2) Setting method of each function by wired remote controller
B: Refrigerant address C: Data display area D: Request code display area
1. Stop operation().
2. Press the button () for 3 seconds so that [Maintenance mode] appears on the screen ().
TEST
After a while, [00] appears in the refrigerant address number display area.(at  )
3. Press the button () for 3 seconds to switch to [Maintenance monitor].
CHECK
Note) It is not possible to switch to [Maintenance monitor] during data request in maintenance mode
(i.e., while “----” is blinking) since no buttons are operative.
[----] appears on the screen () when [Maintenance monitor] is activated. (The display () now allows you to set a request code No.)
4. Press the [TEMP ( and )] buttons () to select the desired refrigerant address. [ScreenB]
  
5. Press the [CLOCK ( and )] buttons () to set the desired request code No.(“311~318”, “321~324”)
6. Press the button () to perform function setting.
FILTER
If above setting operations are done correctly, "Request code number" will appear in data display area.() [Example: When the "311" of "Request code number" is set, [311] appears on the screen.()]
[Refererence] You can check current "request code number" setting by setting the "request code number"(“310” or “320”) and pressing the button.()
FILTER
[Example: When the current setting is "Setting No.2(Request code 311)", [311] appears on the screen.()]
7. To return to normal mode, press the button ().
10-2. BACK-UP HEATING FUNCTION (CN152)
10-2-1. Operation
Outline of functions
The back-up heater signal is sent out according to the tempera­ture difference between indoor room temperature and set tem­perature. This function is available only in heating operation.
10-2-2. How to connect
ON/OFF
Temperature difference
(Z=Set temp. - Room temp.)
1 2 3
Z 0˚C(˚F)
0 < Z < 2.5˚C(4.5˚F)
2.5˚C(4.5˚F) Z
Back-up heater
signal output
OFF
Keeping condition
ON
ON
When connecting to the connector CN152 of the indoor unit, use PAC-SE59RA-E(optional parts).
Z0 2.5˚C(4.5˚F)
OFF
28
11
DISASSEMBLY PROCEDURE
PKA-A24KA.TH PKA-A30KA.TH PKA-A36KA.TH PKA-A24KAL.TH PKA-A30KAL.TH PKA-A36KAL.TH
PHOTOS & ILLUSTRATIONSOPERATION PROCEDURE
1. REMOVING THE PANEL
(1) Press and unlock the knobs on both sides of the front grille and lift the front grille until it is level. Pull the hinges
forward to remove the front grille. (See Photo 1) (2) Remove 3 screw caps of the panel. Remove 5 screws. (See Photo 1) (3) Unfix 3 hooks. (See Figure 1) (4) Hold the lower part of both ends of the panel and pull it
slightly toward you, and then remove the panel by pushing
it upward. (5) Remove the screw of the corner box. (See Photo 1) Remove the corner box.
Photo 1
Figure 1
Be careful when removing heavy parts.
Front grille
Screws and screw caps
Screws
Screw of the corner box
Hooks
2. REMOVING THE INDOOR CONTROLLER BOARD AND THE WIRELESS CONTROLLER BOARD
(1) Remove the panel and the corner box. (Refer to 1.) (2) Remove the front and side electrical box covers (each 1
screw). (See Photo 2)
(3) Disconnect the connectors on the indoor controller board.
(See Photo 3) (4) Remove the switch board holder and open the cover. (5)
Pull out the indoor controller board toward you then remove the indoor controller board and switch board. (See Photo 3) (6) Remove the holder of wireless remote controller board. (7)
Disconnect the connector of wireless remote controller
board and remove the wireless remote controller board from the holder.
Photo 2
Screw of electrical box cover (Front)
Photo 3
Connector for ground wire
Electrical box
Water Cut
Holder of wireless remote controller board
Terminal block (TB4)
Screw of electrical box cover (side)
Switch board holder
Indoor controller board (I.B.)
Terminal block (TB2) (option)
Terminal block (TB5) (only PKA-KA)
29
3. REMOVING THE ELECTRICAL BOX
(1) Remove the panel and the corner box. (Refer to 1.) (2) Remove the front and side electrical box covers (each 1
screw).
(3) Remove the indoor / outdoor connecting wire from termi-
nal block (TB4).
(4)
Disconnect the connectors on the indoor controller board. (5) Disconnect the connector for ground wire. (6) Remove the screw on lower side of the electrical box. (See Photo 5) (7) Push up the upper fixture catch to remove the box, then
remove it from the box fixture.
Photo 4
Connector for ground
wire
Electrical box
PHOTOSOPERATION PROCEDURE
Terminal block (TB4)
Indoor controller board (I.B.)
Terminal block (TB2) (option)
Terminal block (TB5) (only PKA-KA)
4. REMOVING THE NOZZLE ASSEMBLY (with VANE and VANE MOTOR) AND DRAIN HOSE
(1) Remove the panel and corner box. (Refer to 1.) (2) Remove the electrical box covers. (Refer to 2.) (3) Disconnect the vane motor connector (CN151) on the indoor controller board.
(4) Pull out the drain hose from the nozzle assembly, and
remove nozzle assembly. (See Photo 5)
5. REMOVING THE VANE MOTOR
(1) Remove the nozzle assembly. (Refer to 4.) (2) Remove 2 screws of the vane motor unit cover, and pull
out the vane motor unit. (3) Remove 2 screws of the vane motor unit. (4) Remove the vane motor from the vane motor unit. (5) Disconnect the connector from the vane motor.
Photo 5
Nozzle assembly
Drain hose
Photo 6
(see the bottom)
Vane motor
Screw of electrical box
Screws of the vane motor unit
Screws of the vane motor unit cover
30
PHOTOSOPERATION PROCEDURE
6. REMOVING THE INDOOR FAN MOTOR AND THE LINE FLOW FAN
(1) Remove the panel and the corner box. (Refer to 1.) (2) Remove the electrical box (Refer to 2.) and the nozzle
assembly (Refer to 3.). (3) Remove the water cut. (See Photo 2) (4) Remove the screw fixing the line flow fan. (See Photo 8) (5) Remove 5 screws fixing the motor bed. (See Photo 7) (6) Remove the lead wire of pipe thermistor from the hook of
motor bed. (See Photo 7) (7) Remove the screw fixing motor band. (See Photo 7) (8) Remove the motor bed together with fan motor and motor
band. (9)
Remove 3 screws fixing the left side of the heat exchanger. (See Photo 9)
(10) Lift the heat exchanger, and pull out the line flow fan to the
lower-left.
Photo 9
Screws of the left side of the heat exchanger
Photo 7
Photo 8
Screw of the motor band
Lead wire of pipe ther­mistor
Screws of the motor bed
Screw of the line flow fan
7. REMOVING THE LIQUID PIPE THERMISTOR AND COND / EVA PIPE THERMISTOR
(1) Remove the panel and the corner box. (Refer to 1) (2) Remove the electrical box covers. (Refer to 2.) (3) Remove the water cut. (See Photo 2) (4)
Remove the liquid pipe thermistor and cond / eva thermis-
tor.
(5) Disconnect the connector (CN44) on the indoor controller
board.
31
Photo 10
Cond / eva thermistor (TH5)
Liquid pipe thermistor (TH2)
PHOTOSOPERATION PROCEDURE
8. REMOVING THE HEAT EXCHANGER
(1) Remove the panel and the corner box. (Refer to 1.) (2) Remove the electrical box (Refer to 3.) and the nozzle assembly (Refer to 4.). (3) Remove the water cut. (4) Remove the pipe thermistors from each holder. (5) Disconnect the connector for ground wire. (6) Remove 3 screws fixing the left side of the heat exchanger. (See Photo 9) (7) Remove the heat exchanger.
Photo 11
Heat exchanger
Photo 12
Heat exchanger
Liquid pipe thermistor (TH2)
Lead wire for TH5
Water Cut
Connector for ground
9. REMOVING THE ROOM TEMPERATURE THERMISTOR
(1) Remove the panel and corner box. (Refer to 1.) (2) Remove the electrical box covers. (3) Remove the room temperature thermistor. (4) Disconnect the connector (CN20) on the indoor controller board.
HEAD OFFICE : TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
CCopyright 2009 MITSUBISHI ELECTRIC ENGINEERING CO., LTD.
Distributed in Mar. 2009 No.OCH457 PDF 6 Made in Japan
Photo 13
Indoor controller board (I.B.)
Room temp. thermistor (TH1)
New publication, effective Mar. 2009 Specifications subject to change without notice
Loading...