Series (Outdoor unit)Data Book No.
PUZ-A·NHA3(-BS)
PUY-A·NHA3(-BS)
PUZ-HA·NHA2OCS15
OCS14
2
2
SAFETY PRECAUTION
2-1. ALWAYS OBSERVE FOR SAFETY
Before obtaining access to terminal, all supply
circuits must be disconnected.
2-2. CAUTIONS RELATED TO NEW REFRIGERANT
Cautions for units utilising refrigerant R410A
Use new refrigerant pipes.
Make sure that the inside and outside of refrigerant piping is clean and it has no contamination
such as sulfur hazardous for use, oxides, dirt,
shaving particles, etc.
In addition, use pipes with specified thickness.
Contamination inside refrigerant piping can cause deterioration of refrigerant oil etc.
Store the piping to be used indoors during
installation, and keep both ends of the piping
sealed until just before brazing. (Leave elbow
joints, etc. in their packaging.)
If dirt, dust or moisture enters into refrigerant cycle, that can
cause deterioration of refrigerant oil or malfunction of compressor.
Use ester oil, ether oil or alkylbenzene oil (small
amount) as the refrigerant oil applied to flares
and flange connections.
If large amount of mineral oil enters, that can cause deterioration of refrigerant oil etc.
Do not use refrigerant other than R410A.
If other refrigerant (R22 etc.) is used, chlorine in refrigerant can cause deterioration of refrigerant oil etc.
Use a vacuum pump with a reverse flow check
valve.
Vacuum pump oil may flow back into refrigerant cycle and
that can cause deterioration of refrigerant oil etc.
Use the following tools specifically designed for
use with R410A refrigerant.
The following tools are necessary to use R410A refrigerant.
If dirt, dust or moisture enters into refrigerant cycle, that can
cause deterioration of refrigerant oil or malfunction of compressor.
Charge refrigerant from liquid phase of gas
cylinder.
If the refrigerant is charged from gas phase, composition
change may occur in refrigerant and the efficiency will be
lowered.
Do not use a charging cylinder.
If a charging cylinder is used, the composition of refrigerant will change and the efficiency will be lowered.
Ventilate the room if refrigerant leaks during
operation. If refrigerant comes into contact with
a flame, poisonous gases will be released.
[1] Cautions for service
(1) Perform service after recovering the refrigerant left in unit completely.
(2) Do not release refrigerant in the air.
(3) After completing service, charge the cycle with specified amount of refrigerant.
(4) When performing service, install a filter drier simultaneously.
Be sure to use a filter drier for new refrigerant.
[2] Additional refrigerant charge
When charging directly from cylinder
· Check that cylinder for R410A on the market is syphon type.
· Charging should be performed with the cylinder of syphon stood vertically. (Refrigerant is charged from liquid phase.)
3
Unit
Gravimeter
[3] Service tools
Use the below service tools as exclusive tools for R410A refrigerant.
No. Tool name Specifications
1Gauge manifold · Only for R410A
· Use the existing fitting
· Use high-tension side pressure of 5.3MPa·G or over.
2Charge hose · Only for R410A
· Use pressure performance of 5.09MPa·G or over.
3 Electronic scale
4Gas leak detector · Use the detector for R134a, R407C or R410A.
5Adaptor for reverse flow check · Attach on vacuum pump.
6Refrigerant charge base
7Refrigerant cylinder · Only for R410A · Top of cylinder (Pink)
· Cylinder with syphon
8Refrigerant recovery equipment
specifications
. (UNF1/2)
3
PART NAMES AND FUNCTIONS
Indoor unit
Air inlet
Air outlet
Louver
Filter
Vane
Front grille
Emergency
switch
operation
4
Wiredremote controller
Display Section
For purposes of this explanation,
all parts of the display are shown
as lit. During actual operation, only
the relevant items will be lit.
Identifies the current operation
Shows the operating mode, etc.
*Multilanguage display is available.
“Centrally Controlled” indicator
Indicates that operation from the
remote controller has been prohibited by a master controller.
“Timer is Off” indicator
Indicates that the timer is off.
Temperature Setting
Shows the target temperature.
Day-of-Week
Shows the current day of the week.
Time/Timer Display
Shows the current time, unless the simple or Auto Off
timer is set.
If the simple or Auto Off timer is set, the time to be
switched off is shown.
TIME SUN MON TUE WED THU FRI SAT
TIMER
AFTER
ERROR CODE
°F°C
Hr
AFTER
°F°C
ONLY1Hr.
Up/Down Air Direction indicator
The indicator shows the direction of the outcoming airflow.
“One Hour Only” indicator
Displayed if the airflow is set to
low or downward during COOL
or DRY mode. (Operation varies
according to model.)
The indicator goes off in 1 hour,
when the airflow direction
also changes.
Room Temperature display
Shows the room temperature.The room
temperature display range is 46–102˚F.
The display blinks if the temperature
is less than 46˚F or 102˚F or more.
Louver display
Indicates the action of the swing louver.
Does not appear if the louver is not
running.
(Power On indicator)
Indicates that the power is on.
ON
OFF
FUNCTION
FILTER
WEEKLY
SIMPLE
AUTO OFF
“Sensor” indication
Displayed when the remote controller
sensor is used.
“Locked” indicator
Indicates that remote controller buttons have been locked.
“Clean The Filter” indicator
To be displayed on when it is time to
clean the filter.
Timer indicators
The indicator comes on if the corresponding timer is set.
Fan Speed indicator
Shows the selected fan speed.
Ventilation indicator
Appears when the unit is running in
Ventilation mode.
Operation Section
Temperature setting buttons
Down
Up
Timer Menu button
(Monitor/Set button)
Mode button (Return button)
TEMP.
Set Time buttons
Back
Ahead
Timer On/Off button
(Set Day button)
Opening the
lid
Note:
“PLEASE WAIT”message
•
This message is displayed for approximately 3 minutes when power is supplied to the indoorunit or when the unit is recoveringfrom a power failure.
“NOT AVAILABLE” message
•
This message is displayed if an invalid button is pressed (to operate a function that the indoor unit does not have).
BACKDAY
PAR-21MAA
MENU
MONITOR/SET
CLOCK
ON/OFF
OPERATION
ON/OFF
FILTER
CHECK
TEST
CLEAR
Built-in temperature sensor
If a single remote controller is used to operate multiple indoor units simultaneously that are different types, this message will not be displayed as
far as any of the indoor units is equipped with the function.
ON/OFF button
Fan Speed button
Filterbutton
(<Enter> button)
Test Run button
Check button (Clear button)
Airflow Up/Down button
Louver button
( Operation button)
To return operation
number
Ventilationbutton
( Operation button)
To go to next operation
number
5
Wirelessremote controller
CHECK
TEST RUN
display
Indicate that the unit is being checked or
test-run.
MODEL SELECT
Blinks when model is selected.
display
display
Lights up while the signal is transmitted to
the indoor unit when the button is pressed.
Temperature setting display
Indicates the desired temperature setting
which is set.
OPERATION MODE display
OPERATION MODE display
Indicates which operation mode is in effect.
display
The vertical direction of airflow is indicated.
display
Displaysselected fanspeed.
ON/OFF button
The unit is turned ON and OFF alternately
each time the button is pressed.
FAN SPEED SELECT button
Changes the fan speed.
MODE SELECT button
Switches the operation mode between
COOLING/DRY/FAN/HEATING and AUTO
mode.
In case the outdoor unit is cooling only
type, the heating and auto mode are not
available.
COOL
DRY
AUTO
FAN
HEAT
RUN
MODEL
SELECT
FAN
SWING
NOTAVAILABLE
TEST
CHECK
ON/OFFTEMP
FAN
MODE
CHECK
VANE
LOUVER
TEST RUN
RESETSETCLOCK
°F
°C
AMPMSTOP
AMPM
START
AUTO STOP
AUTO START
h
min
CLOCK display
Displays the current time.
TIMER display
Displays when in timer operation or when
setting timer.
“ ” “ ” display
Displays the order of timer operation.
“ ” “ ” display
Displays whether timer is on or off.
button
Sets any desired room temperature.
TIMER CONTROL buttons
AUTO STOP (OFF timer): when this switch
is set, the air conditioner will be
automatically stopped at the preset time.
AUTO START (ON timer): when this switch is
set, the air conditioner will be automatically
started at the preset time.
"h" and "min" buttons
Buttons used to set the “hour and minute” of
the current time and timer settings.
CHECK-TEST RUN button
Performs an inspectioncheck or test
operation. Do not use it for normal
operation.
Refrigerant flow in cooling
Refrigerant flow in heating
Refrigerant LIQUID pipe connection
(Flare)
Strainer (#50)
11
9
TROUBLESHOOTING
9-1. TROUBLESHOOTING
<Error code display by self-diagnosis and actions to be taken for service (summary)>
Present and past error codes are logged and displayed on the wired remote controller or controller board of outdoor unit.
Actions to be taken for service and the trouble reoccurrence at field are summarized in the table below. Check the contents
below before investigating details.
Unit conditions at service
The trouble is reoccurring.
Error code
Displayed
Not displayed
Judge what is wrong and take a corrective action
according to “9-3. Self-diagnosis action table”.
Conduct troubleshooting and ascertain the cause of the trouble
according to “9-4. Troubleshooting by inferior phenomena”.
Actions to be taken for service (summary)
Consider the temporary defects such as the work of
protection devices in the refrigerant circuit including
compressor, poor connection of wiring, noise and etc.
Logged
Re-check the symptom, and check the installation
environment, refrigerant amount, weather when the
trouble occurred, matters related to wiring and etc.
The trouble is not reoccurring.
Reset error code logs and restart the unit after finishing service.
There is no abnormality in electrical component,
controller board,remote controller and etc.
Re-check the abnormal symptom.
Conduct trouble shooting and ascertain the cause of the trouble
according to “9-4. Troubleshooting by inferior phenomena”.
Not logged
Continue to operate unit for the time being if the cause
is not ascertained.
There is no abnormality concerning of parts such as electrical
component, controller board, remote controller and etc.
9-2. MALFUNCTION-DIAGNOSIS METHOD BY REMOTE CONTROLLER
<In case of trouble during operation>
When a malfunction occurs to air conditioner, both indoor unit and outdoor unit will stop and operation lamp blinks to inform
unusual stop.
<Malfunction-diagnosis method at maintenance service>
CHECK
display
ON/OFF
button
CHECK
button
ON/OFF
MODE
CHECK
TEST RUN
SET
CHECK
FAN
VANE
LOUVER
RESET
TEMP
CLOCK
AUTO STOP
AUTO START
h
min
Refrigerant
address
display
Temperature
button
HOUR
button
[Procedure]
1. Press the CHECK button twice.
2. Press the temperature
buttons.
3. Point the remote controller at the
sensor on the indoor unit and
press the HOUR button.
4. Point the remote controller at the
sensor on the indoor unit and
press the ON/OFF button.
12
• "CHECK" lights, and refrigerant
address "00" blinks.
• Check that the remote controller's
display has stopped before continuing.
• Select the refrigerant address of the
indoor unit for the self-diagnosis.
Note: Set refrigerant address using the
outdoor unit’s DIP switch (SW1).
(For more information, see the
outdoor unit installation manual.)
• If an air conditioner error occurs, the
indoor unit's sensor emits an intermittent buzzer sound, the operation lamp
blinks, and the error code is
output.
(It takes 3 seconds at most for error
code to appear.)
• The check mode is cancelled.
• Refer to the following tables for details on the check codes.
[Output pattern A]
Beeper sounds
OPERATION
INDICATOR
lamp blink
pattern
Beep
Self-check
starts
(Start signal
received)
Beep Beep BeepBeepBeep Beep
1st2nd3
Off
Approx. 2.5 sec.On0.5 sec.On0.5 sec.On0.5 sec.
Number of blinks/beeps in pattern indicates the check
code in the following table (i.e., n=5 for “P5”)
rd
0.5 sec.
th
n
On
[Output pattern B]
Beeper sounds
OPERATION
INDICATOR
lamp blink
pattern
Self-check
starts
(Start signal
received)
Off
Approx. 2.5 sec.OnApprox. 3 sec.On0.5 sec.On0.5 sec.On0.5 sec.
1st2nd3
Number of blinks/beeps in pattern indicates the check
code in the following table (i.e., n=5 for “U2”)
Forced compressor stop(due to water leakage abnormality)
6P6Freezing/Overheating protection operation
7EECommunication error between indoor and outdoor units
8P8Pipe temperature error
9E4, E5Remote controller signal receiving error
10
11
–
–
–
–
12FbIndoor unit control system error (memory error, etc.)
–
E0, E3
Remote controller transmission error
–E1, E2Remote controller control board error
nd
1st2
Off
Approx. 2.5 sec.On0.5 sec.On0.5 sec.
Number of blinks/beeps in pattern indicates
the check code in the following table
peeBpeeBpeeBpeeBpeeB
rd
th
n
On
0.5 sec.
Approx. 2.5 sec.OnApprox. 3 sec.On0.5 sec.On0.5 sec.
· · · Repeated
Off
Beep Beep
Number of blinks/beeps in pattern indicates
the check code in the following table
1st2
nd
· · · Repeated
krameRmotpmyS
[Output pattern B]
Wireless remote controller
Errors detected by unit other than indoor unit (outdoor unit, etc.)
Wired remote controller
Beeper sounds/OPERATION
INDICATOR lamp blinks Check code
(Number of times)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
E9
UP
U3,U4
UF
U2
U1,Ud
U5
U8
U6
U7
U9,UH
–
–
Others
*1If the beeper does not sound again after the initial
the OPERATION INDICATOR lamp does not come on,
Indoor/outdoor unit communication error
(Transmitting error) (Outdoor unit)
Compressor overcurrent interruption
Open/short of outdoor unit thermistors
Compressor overcurrent interruption (When compressor locked)
Abnormal high discharging temperature/49C worked/
insufficient refrigerant
Abnormal high pressure (63H worked)/Overheating
protection operation
Abnormal temperature of heatsink
Outdoor unit fan protection stop
Compressor overcurrent interruption/Abnormal of power module
Abnormality of superheat due to low discharge temperature
Abnormality such as overvoltage or voltage shortage and
abnormal synchronous signal to main circuit/Current sensor error
–
–
Other errors (Refer to the technical manual for the outdoor unit.)
2 beeps to confirm the self-check start signal was received and
there are no error records.
For details, check
the LED display
of the outdoor
controller board.
As for outdoor
unit, refer to
outdoor unit's
service manual.
*2If the beeper sounds 3 times continuously “beep, beep, beep (0.4 + 0.4 + 0.4 sec.)” after the initial 2 beeps to confirm
the self-check start signal was received, the specified refrigerant address is incorrect.
krameRmotpmyS
1313
• On wireless remote controller
The continuous buzzer sounds from receiving section of indoor unit.
Blink of operation lamp
• On wired remote controller
Check code displayed in the LCD. (Refer to the previous page,check code.)
If the unit cannot be operated properly after the test run, refer to the following table to find out the cause.
•
Symptom
Wired remote controllerLED 1, 2 (PCB in outdoor unit)
PLEASE WAIT
PLEASE WAIT
Display messages do not
appear even when operation
switch is turned ON (operation
lamp does not light up).
On the wireless remote controller with condition above, following phenomena take place.
• No signals from the remote controller can be received.
• OPE lamp is blinking.
• The buzzer makes a short ping sound.
Note:
Operation is not possible for about 30 seconds after cancellation of function selection. (Correct operation)
For description of each LED (LED1, 2, 3) provided on the indoor controller, refer to the following table.
LED1 (power for microcomputer)Indicates whether control power is supplied. Make sure that this LED is
LED2 (power for remote controller)
LED3 (communication between indoor and
outdoor units)
Error code
For about 2
minutes after
power-on
Subsequent to
about 2 minutes
after power-on
After LED 1, 2 are lighted, LED 2 is
turned off, then only LED 1 is
lighted.
(Correct operation)
Only LED 1 is lighted.
Only LED 1 is lighted.
always lit.
Indicates whether power is supplied to the remote controller.
This LED lights only in the case of the indoor unit which is connected to the
outdoor unit refrigerant addresses “0”.
Indicates state of communication between the indoor and outdoor units.
Make sure that this LED is always blinking.
LED 1, 2 blink.
LED 1 blinks twice,
LED 2 blinks once.
• For about 2 minutes following power-on,operation of the remote controller is not possible
due to s y s t e m s t a rt- u p. (Correct operation)
•Connector for the outdoor unit’ s protection
devi c e i s n o t c o nnected.
•Reverse or open phase wiring for the outdoor
unit’s power terminal block (L1, L2, GR)
•Incorrect wiring between indoor and outdoor
units (incorrect polarity of S1, S2, S3)
•Remote controller wire short
Cause
14
9-3. SELF-DIAGNOSIS ACTION TABLE
Error Code
P1
P2
Abnormal point and detection method
Room temperature thermistor (TH1)
The unit is in 3-minute resume
prevention mode if short/open of
thermistor is detected.Abnormal if the
unit does not reset normally after 3 minutes. (The unit returns to normal operation, if it has been reset normally.)
Constantly detected during cooling,
drying, and heating operation.
Short: 90
Open: -40
Pipe temperature thermistor/Liquid
(TH2)
The unit is in 3-minute resume
prevention mode if short/open of
thermistor is detected.Abnormal if the
unit does not reset normally after 3 minutes. (The unit returns to normal operation, if it has been reset normally.)
Constantly detected during cooling,
drying, and heating (except defrosting)
operation.
Short: 90
Open: -40
Note: Refer to the manual of outdoor unit for the details of display
suchas F,U, and other E.
Cause
Defective thermistor
characteristics
Contact failure of connector
(CN20) on the indoor controller
board (Insert failure)
Breaking of wire or contact
failure of thermistor wiring
Defective indoor controller
board
Defective thermistor
characteristics
Contact failure of connector
(CN44) on the indoor controller
board (Insert failure)
Breaking of wire or contact
failure of thermistor wiring
Defective refrigerant circuit is
causing thermistor temperature of 90
-40
Defective indoor controller
board
Countermeasure
– Check resistance value of thermistor.
••••••••••
0
10
20
30
40
••••••••••••
••••••••••••
••••••••••••
•••••••••••
15.0k
9.6k
6.3k
4.3k
3.0k
If you put force on (draw or bend) the lead wire
while measuring resistance value of thermistor, breaking of wire or contact failure can be
detected.
Check contact failure of connector (CN20) on
the indoor controller board. Refer to 9-7.
Turn the power on again and check restart
after inserting connector again.
Check room temperature display on remote
controller.
Replace indoor controller board if there is
abnormal difference with actual room
temperature.
Turn the power off, and on again to operate
after check.
–
Check resistance value of thermistor.
For characteristics, refer to (P1) above.
Check contact failure of connector (CN44) on
the indoor controller board. Refer to 9-7.
Turn the power on and check restart after
inserting connector again.
Check pipe <liquid> temperature with remote
controller in test run mode. If pipe <liquid>
temperature is extremely low (in cooling
mode) or high (in heating mode), refrigerant
circuit may have defect.
Check pipe <liquid> temperature with remote
controller in test run mode. If there is extremely
difference with actual pipe <liquid> temperature,
replace indoor controller board.
P4
(5701)
P5
Contact failure of drain float switch (CN4F)
Extract when the connector of drain float
switch is disconnected.
andof connector CN4F is not
(
short-circuited.)
Constantly detected during operation.
Drain overflow protection operation
Suspensive abnormality, if drain float
switch is detected to be underwater for
1 minute and 30 seconds continuously
with drain pump on.
Turn off compressor and indoor fan.
Drain pump is abnormal if the condition
above is detected during suspensive
abnormality.
Constantly detected during drain pump
operation.
Contact failure of connector
(Insert failure)
Defective indoor controller
board
Malfunction of drain pump
Defective drain
Clogged drain pump
Clogged drain pipe
Defective drain float switch
Catch of drain float switch or
malfunction of moving parts
cause drain float switch to be
detected under water (Switch
On)
Defective indoor-controller
board
15
Turn the power off, and on again to operate
after check.
Check contact failure of float switch connector.
Turn the power on again and check after
inserting connector again.
Operate with connector (CN4F) short-circuited.
Replace indoor controller board if abnormality
reappears.
Check if drain-up machine works.
Check drain function.
Remove drain float switch connector CN4F
and check if it is short (Switch On) with the
moving part of float switch UP, or OPEN with
the moving part of float switch down.
Replace float switch if it is short with the
moving part of float switch down.
Replace indoor controller board if it is shortcircuited between
- of the drain float
switch connector CN4F and abnormality
reappears.
It is not abnormal if there is no problem about
the above-mentioned
~
Turn the power off, and on again to operate
after check.
Error Code
Abnormal point and detection method
Freezing/overheating protection is working
Freezing protection (Cooling mode)
The unit is in 6-minute resume prevention
mode if pipe <liquid or condenser/evaporator> temperature stays under
the compressor started.Abnormal if it
again within 16 minutes after 6-minute
resume prevention mode.
Cause
(Cooling or drying mode)
Clogged filter (reduced airflow)
Short cycle of air path
Low load (low temperature)
operation out of the tolerance
range
Defective indoor fan motor
• Fan motor is defective.
• Indoor controller board is defective.
Defective outdoor fan control
Overcharge of refrigerant
Defective refrigerant circuit
(clogs)
Countermeasure
(Cooling or drying mode)
Check clogs of the filter.
Remove shields.
Refer to 9-6.
Check outdoor fan motor.
Check operating condition of refrigerant
circuit.
P6
P8
Overheating protection (Heating mode)
The units is in 6-minute resume
prevention mode if pipe <liquid or
condenser/
detected as over 70°C[158°F] after the
compressor started. Abnormal if the
temperature of over 70°C[158°F] is
detected again within 10 minutes after
6 minute resume prevention mode.
Pipe temperature
<Cooling mode>
Detected as abnormal when the pipe temperature is not in the cooling range 3 minutes after compressor start and 6 minutes
after the liquid or condenser/evaporatorpipe
is out of cooling range.
Note 1) It takes at least 9 minutes to detect.
Note 2) Abnormality P8 is not detected in
Cooling range : -(TH-TH1)
TH: Lower temperature between liquid pipe
temperature (TH2) and condenser/
evaporator temperature (TH5)
TH1: Intake temperature
<Heating mode>
When 10 seconds have passed after the
compressor starts operation and the hot
adjustment mode has finished, the unit is
detected as abnormal when condenser/
evaporator pipe temperature is not in heating range within 20 minutes.
Note 3) It takes at least 27 minutes to
Note 4) It excludes the period of defrosting
Heating range :(TH5-TH1)
evaporator> temperature is
drying mode.
detect abnormality.
(Detection restarts when defrosting
mode is over)
(Heating mode)
Clogged filter (reduced airflow)
Short cycle of air path
Overload (high temperature)
operation out of the tolerance
range
Defective indoor fan motor
• Fan motor is defective.
• Indoor controller board is defective.
Defective outdoor fan control
Overcharge of refrigerant
Defective refrigerant circuit
(clogs)
Bypass circuit of outdoor unit
is defective.
Slight temperature difference
between indoor room
temperature and pipe <liquid
or condenser/evaporator>
temperature thermistor
• Shortage of refrigerant
• Disconnected holder of pipe
<liquid or condenser/
evaporator> thermistor
• Defective refrigerant circuit
Converse connection of
extension pipe (on plural units
connection)
Converse wiring of indoor/
outdoor unit connecting wire
(on plural units connection)
Defective detection of indoor
room temperature and pipe
<condenser/evaporator>
temperature thermistor
Stop valve is not opened
completely.
(Heating mode)
Check clogs of the filter.
Remove shields.
Refer to 9-6.
Check outdoor fan motor.
Check operating condition of refrigerant
~
circuit.
~ Check pipe <liquid or condenser/evap-
orator> temperature with room temperature display on remote controller and
outdoor controller circuit board.
Pipe <liquid or condenser/evaporator>
temperature display is indicated by setting SW2 of outdoor controller circuit
board as follows.
Conduct temperature check with outdoor
controller circuit board after connecting
(
‘A-Control Service Tool(PAC-SK52ST)’.
Check converse connection of extension
pipe or converse wiring of indoor/outdoor
unit connecting wire.
)
16
Error Code
P9
Abnormal point and detection method
Pipe temperature thermistor/
Condenser-Evaporator (TH5)
The unit is in 3-minute resume protection mode if short/open of thermistor is
detected. Abnormal if the unit does not
get back to normal within 3 minutes. (The
unit returns to normal operation, if it has
been reset normally.)
Constantly detected during cooling,
drying, and heating operation (except
defrosting)
Cause
Defective thermistor
characteristics
Contact failure of connector
(CN44) on the indoor controller
board (Insert failure)
Breaking of wire or contact
failure of thermistor wiring
Temperature of thermistor is
For characteristics, refer to (P1) above.
Check contact failure of connector (CN44) on
the indoor controller board. Refer to 9-7.
Turn the power on and check restart after
inserting connector again.
Operate in test run mode and check pipe <condenser/evaporator> temperature with outdoor
controller circuit board. If pipe
<condenser/evaporator> temperature is exclusively low (in cooling mode) or high (in heating
mode), refrigerant circuit may have defect.
Operate in test run mode and check pipe <condenser/evaporator> temperature with outdoor
control circuit board. If there is
extreme difference with actual pipe
<condenser/evaporator> temperature, replace
indoor controller board.
There is no abnormality if none of above comes
within the unit.
Turn the power off and on again to operate.
In case of checking pipe temperature
with outdoor controller circuit board,
be sure to connect A-control service
(
tool (PAC-SK52ST).
)
PA
(2500)
E0
or
E4
Forced compressor stop
(due to water leakage abnormality)
The unit has a water leakage abnormality when the following conditions, a)
and b), are satisfied while the abovementioned detection is performed.
a) The intake temperature subtracted
with liquid pipe temperature detects to
be less than -10 [14
30 minutes. (When the drain sensor
is detected to be NOT soaked in the
water, the detection record of a) and b)
will be cleared.)
b) Drain float switch detects to be in the
water for more than 15 minutes.
*Once the water leakage abnormality is
detected, abnormality state will not be
released until the main power is reset.
· Drain pipe clogging
Open circuit of float switch
Contact failure of float switch
connector
Dew condensation on float switch
·Drain water descends along
lead wire.
·Drain water waving due to filter
clogging.
Extension piping connection
difference at twin, triple, quadruple system.
Miswiring of indoor/outdoor
connecting at twin, triple, quadruple system.
Room temperature thermistor/
liquid pipe temperature thermistor detection is defective.
Contact failure at transmission
wire of remote controller
All remote controllers are set
as “sub” remote controller. In
this case, E0 is displayed on
remote controller, and E4 is
displayed at LED (LED1, LED2)
on the outdoor controller circuit
board.
Miswiring of remote controller
Defective transmitting receiving
circuit of remote controller
Defective transmitting receiving
circuit of indoor controller board
of refrigerant addresses “0”.
Noise has entered into the
transmission wire of remote
controller.
Check the drain pump.
Check whether water can be drained.
Check the resistance of the float switch.
Check the connector contact failure.
Check the float switch leadwire mounted.
Check the filter clogging.
Check the piping connection.
Check the indoor/outdoor connecting wires.
Check the room temperature display of
remote controller.
Check the indoor liquid pipe temperature display of outdoor controller board.
Check disconnection or looseness of indoor
unit or transmission wire of remote controller.
Set one of the remote controllers “main”
if there is no problem with the action above.
Check wiring of remote controller.
(Do not use cable
• The number of connecting indoor units:
max. 16 units
• The number of connecting remote control
ler: max. 2 units
When the above-mentioned problem of ~
are not applied,
Diagnose remote controllers.
a) When “RC OK” is displayed, remote con-
trollers have no problem. Turn the power
off, and on again to check. If abnormality
generates again, replace indoor controller
board.
b) When “RC NG” is displayed, replace
remote controller.
c) When “RC E3” or “ERC 00-06” is dis played, noise may be causing abnormality.
If the unit is not normal after replacing
indoor controller board in group control,
indoor controller board of address “0”
may be abnormal.
Abnormal if remote controller could not
find blank of transmission path for 6 seconds and could not transmit.
(Error code: E3)
Remote controller receives transmitted
data at the same time, compares the
data, and when detecting it, judges
different data to be abnormal 30
continuous times. (Error code: E3)
Abnormal if indoor controller board could
not find blank of transmission path.
(Error code: E5)
Indoor controller board receives transmitted data at the same time, compares
the data,and when detecting it, judges
different data to be abnormal 30
continuous times. (Error code: E5)
Cause
2 remote controllers are set as
“main.”
(In case of 2 remote con trollers)
Remote controller is connected
with 2 indoor units or more.
Repetition of refrigerant
address
Defective transmitting receiving
circuit of remote controller
Defective transmitting receiving
circuit of indoor controller board
Noise has entered into trans-
mission wire of remote control-
ler.
Countermeasure
Set a remote controller to main, and the
other to sub.
Remote controller is connected with only one
indoor unit.
The address changes to a separate setting.
~Diagnose remote controller.
a) When “RC OK” is displayed, remote con-
trollers have no problem.
Turn the power off, and on again to check.
When becoming abnormal again, replace
indoor controller board.
b) When “RC NG” is displayed, replace
remote controller.
c) When “RC E3” or “ERC 00-66” is dis-
played, noise may be causing abnormality.
E6
E7
Fb
Indoor/outdoor unit communication
error (Signal receiving error)
Abnormal if indoor controller board
cannot receive any signal normally for 6
minutes after turning the power on.
Abnormal if indoor controller board
cannot receive any signal normally for 3
minutes.
Consider the unit as abnormal under
the following condition: When 2 or more
indoor units are connected to an
outdoor unit, indoor controller board
cannot receive a signal for 3 minutes
from outdoor controller circuit board, a
signal which allows outdoor controller
circuit board to transmit signals.
Indoor/outdoor unit communication
error (Transmitting error)
Abnormal if indoor controller board
receives “1” 30 times continuously when
indoor controller board transmits “0” signal.
Indoor controller board
Abnormal if data cannot be read normally
from the nonvolatile memory of the indoor
controller board.
Contact failure, short circuit or,
miswiring (converse wiring) of
indoor/outdoor unit connecting
wire
Defective transmitting receiving
circuit of outdoor controller
circuit board
Defective transmitting receiving
circuit of indoor controller board
Noise has entered into indoor/
outdoor unit connecting wire.
Defective transmitting receiving
circuit of indoor controller board
Noise has entered into power
supply.
Noise has entered into outdoor
control wire.
Defective indoor controller
board
Check LED display on the outdoor control
circuit board. (Connect A-control service
tool, PAC-SK52ST.)
Refer to EA-EC item if LED displays EA-EC.
Check disconnection or looseness of indoor/
outdoor unit connecting wire of indoor unit or
outdoor unit.
Check all the units in case of twin indoor
unit system.
- Turn the power off, and on again to check.
If abnormality generates again, replace
indoor controller board or outdoor
controller circuit board.
Other indoor controller board may have
defect in case of twin indoor unit system.
- Turn the power off, and on again to check.
If abnormality generates again, replace
indoor controller board.
Replace indoor controller board.
E1
or
E2
Remote controller control board
Abnormal if data cannot be read normally from the nonvolatile memory of the
remote controller control board.
(Error code: E1)
Abnormal if the clock function of remote
controller cannot be operated normally.
Note: Refer to the manual of outdoor unit for the detail of remote
controller.
Phenomena
(1)LED2 on indoor controller board
is off.
• When LED1 on indoor controller board is also off.
Power supply of rated voltage is not supplied to out-
door unit.
Defective outdoor controller circuit board
Power supply of 208/230V is not supplied to indoor
unit.
Defective indoor controller board
Cause
Countermeasure
Check the voltage of outdoor power
supply terminal block (L1, L2).
• When AC 208/230V is not detected,
check the power wiring to outdoor unit
and the breaker.
• When AC 208/230V is detected, check
(below).
Check the voltage between outdoor
terminal block S1 and S2.
• When AC 208/230V is not detected,
—check the fuse on outdoor controller
circuit board.
—check the wiring connection.
• When AC 208/230V is detected, check
(below).
Checkthevoltagebetweenindoorterminal
block S1 and S2.
• When AC 208/230V is not detected,
check indoor/outdoor unit connecting
wire for miswiring.
• When AC 208/230V is detected, check
(below).
Check the fuse on indoor controller board.
Check the wiring connection.
If no problem are found, indoor controller
board is defective.
(For the separate indoor/outdoor unit power sup-
ply system)
Power supply of 208/230V AC is not supplied to
indoor unit.
The connectors of the optional replacement kit are
not used.
Defective indoor controller board
• When LED1 on indoor controller board is lit.
Mis-setting of refrigerant address for outdoor unit
(There is no unit corresponding to refrigerant
address “0”.)
Check the voltage of indoor power supply
terminal block (L1,L2).
• When AC208/230V is not detected,
check the power supply wiring.
• When AC208/230V is detected, check
(below).
Check that there is no problem in the
method of connecting the connectors.
• When there are problems in the method
of connecting the connectors, connect
the connector correctly referring to
installation manual of an optional kit.
• When there is no problem in the method of connecting the connectors, check
(below).
Check the fuse on indoor controller board.
Check the wiring connection.
If no problem are found, indoor controller
board is defective.
Check again the setting of refrigerant
address for outdoor unit.
Set the refrigerant address to “0”.
(For grouping control system under
which 2 or more outdoor units are
connected, set one of the units to “0”.)
Set refrigerant address using SW1 (3-6)
on outdoor controller circuit board.
19
Phenomena
(2)LED2 on indoor controller board
is blinking.
Note: Refer to the manual of outdoor unit for the detail of remote
controller.
Cause
• When LED1 on indoor controller board is also blinking.
Connection failure of indoor/outdoor unit connecting
wire
• When LED1 is lit.
Miswiring of remote controller wires
Under twin indoor unit system, 2 indoor
wired together.
Refrigerant address for outdoor unit is wrong or not
set.
Under grouping control system, there are some units
whose refrigerant address is 0.
Short-cut of remote controller wires
Defective remote controller
units are
Countermeasure
Check indoor/outdoor unit connecting wire
for connection failure.
Check the connection of remote controller wires in case of twin indoor unit
system. When 2 indoor units are wired in
one refrigerant system,
connect remote controller wires to one of
those units.
Check the setting of refrigerant address
in case of grouping control system.
If there are some units whose refrigerant
addresses are 0 in one group, set one of
the units to 0 using SW1 (3-6) on outdoor
controller circuit board.
Remove remote controller wires and
check LED2 on indoor controller board.
• When LED2 is blinking, check the shortcircuit of remote controller wires.
• When LED2 is lit, connect remote
controller wires again and:
if LED2 is blinking, remote controller
is defective; if LED2 is lit, connection
failure of remote controller terminal
block etc. has returned to normal.
(3)Upward/downward vane
performance failure
(4)Receiver for wireless remote
controller
The vane is not downward during defrosting and heat
preparation and when the thermostat is OFF in HEAT
mode. (Working of COOL protection function)
Vane motor does not rotate.
• Defective vane motor
• Breaking of wire or connection failure of connector
Upward/downward vane does not work.
• The vane is set to fixed position.
Weak batteries of wireless remote controller
Contact failure of connector (CNB) on wireless
remote controller board
(Insert failure)
Contact failure of connector (CN90) on indoor controller board (Insert failure)
Contact failure of connector between wireless remote
controller board and indoor controller board
Normal operation (The vane is set to
horizontal regardless of remote control.)
Check
• Check the vane motor. (Refer to “How
• Check for breaking of wire or connecNormal operation (Each connector on
vane motor side is disconnected or setting the fixed vanes by wired remote
controller.)
Replace batteries of wireless remote controller.
~
When the same trouble occurs even if
(left).
to check the parts”.)
tion failure of connector.
Check contact failure of each connector.
If no problems are found of connector,
replace indoor controller board.
indoor controller board is replaced,
replace wireless remote controller
board.
20
9-5. EMERGENCY OPERATION
9-5-1. When wireless remote controller fails or its battery is exhausted
When the remote controller cannot be used
When the batteries of the remote controller run out or the remote controller
malfunctions, the emergency operation can be done using the emergency
buttons.
DEFROST/STAND BY lamp (ORANGE)
Operation lamp (GREEN)
Emergency operation switch (cooling/heating)
Receiver
• Each press of the emergency operation switch will toggle the
operation mode.
• Check “COOL/HEAT” with the operation monitor display. (The display will
appear orange for 5 seconds after pressing the emergency operation switch.)
[Heat pump type]
CoolingHeatingStop
[Cooling Only type]
CoolingStop
Operation Monitor Display
GREENORANGE
STOP
COOL
HEAT
OFF ON
The orange lamp follows the switch operation
as indicated at the left for 5 sedonds, and
then it will return to the normal display.
* Details of emergency mode are as shown below.
Operation Mod
Set Temperature
Fan Speed
Airflow Direction Up and DownHorizontal
COOLHEAT
24°C, 75°F24°C, 75°F
HighHigh
Downward
9-5-2. When wired remote controller or indoor unit microcomputer fails
1. When the wired remote control or the indoor unit microcomputer has failed, but all other components work properly,
if you set the switch (SWE) on the indoor controller board ON, the indoor unit will begin Emergency Operation.
When Emergency Operation is activated, the indoor unit operates as follows:
(1) Indoor fan is running at high speed.
+ Note on the wireless remote control
When the remote control does not function, it is possible to activate
Emergency Operation by using the indoor unit Emergency Operation switch.
However, if the indoor unit microcomputer has failed, it is nesessary to proceed with points 2 and 3 below as in the
case of the wired remote control.
2. When you activate Emergency Operation of the cooling or heating, you have to set the switch (SWE) on the indoor
controller board and activate Emergency Operation of the outdoor unit.
For details on how to activate Emergency Operation of the outdoor unit, refer to the outdoor unit wiring diagram.
3. Before you activate Emergency Operation, check the following points:
(1) Emergency operation cannot be activated when:
• the outdoor unit malfunctions. • the indoor fan malfunctions.
• when it has detected the malfunction of drain-up machine during self-diagnosing.
(2) Emergency Operation becomes continuous only by switching the power source on/off.
ON/OFF on the remote control or temperature control etc. does not function.
(3) Avoid operating for a long time when the outdoor unit begins defrosting
while Emergency Operation of the heating is activated, because it will start to blow cold air.
(4) Emergency cooling should be limited to 10 hours maximum (The indoor unit heat exchanger may freeze).
(5) After Emergency Operation has been deactivated, set the switches etc. to their original positions.
(6) Movement of the vanes does not work in Emergency operation, therefore
you have to slowly set them manually to the appropriate position.
21
9-6. HOW TO CHECK THE PARTS
PKA-A24KA.TH PKA-A30KA.TH PKA-A36KA.TH
PKA-A24KAL.TH PKA-A30KAL.TH PKA-A36KAL.TH
Parts nameCheck points
Room temperature
thermistor (TH1)
Liquid pipe thermistor
(TH2)
Condenser/evaporator
temperature thermistor
(TH5)
Vane motor (MV)
Red
Yellow
Brown
Connect pin No.
Orange
M
Disconnect the connector then measure the resistance using a tester.
(At the ambient temperature 50"F~86"F)
Normal
4.3k~9.6k
Measure the resistance between the terminals using a tester. (Coil temperature 68"F)
Green
-
Brown-Red
-
Brown-Orange
Abnormal
Open or short
Normal
Brown-Yellow
250 ± 7%
-
(Refer to the next page for a detail.)
-
Brown-Green
Open or short
Abnormal
Fan motor (MF)
Refer to 9-6-2.
9-6-1. Thermistor
<Thermistor Characteristic graph>
Thermistor for
lower temperature
Thermistor R
Fixed number of B=3480 ± 2%
t(
)Rt=15exp { 3480( ) }
0
10
20
25
30
40
0=15k±3%
Room temperature thermistor (TH1)
Pipe temperature thermistor/liquid (TH2)
Condenser/evaporator temperature
thermistor (TH5)
1
273+t1273
273+
1
T-32
1.8
1
273
<Thermistor for lower temperature>
50
40
30
20
Resistance (k )
10
0
-20 -10 0 10 20 30 40 50
-4 -14 32 50 68 86 104122 °F
Temperature
°C
22
9-6-2. DC Fan motor (fan motor/indoor controller circuit board)
Check method of DC fan motor (fan motor/indoor controller circuit board)
Notes
· High voltage is applied to the connecter (CNMF) for the fan motor. Pay attention to the service.
· Do not pull out the connector (CNMF) for the motor with the power supply on.
(It causes trouble of the indoor controller circuit
Self check
Symptom : The indoor fan cannot rotate.
Wiring contact check
Contact of fan motor connector (CNMF)
board and fan motor.)
Is there contact failure?
No
Power supply check (Remove the connector (CNMF))
Measure the voltage in the indoor controller circuit
TEST POINT
: VDC (between 1 (+) and 3 (-) of the fan connector): VDC DC294~325V
Yes
Wiring recovery
board.
TEST POINT : VCC (between 4 (+) and 3 (-) of the fan connector): VCC DC15V
Is the voltage normal?
Yes
No
Indoor controller board fuse check
Is the fuse normal?
Replace the indoor
controller board.
Check the operation
Replace the fan motor.
Sensor signal check
Measure the voltage between CNMF
and DC 0V
and DC 15V in the indoor controller circuit board.
Connect to the terminal
block (TB5) (Remote
controller connecting
wire) (only PKA-A·KA)
CN30
Connector (LLC)
CN32
Remote switch
CN90
Connect to the remote
operation adapter
CN51
Centrally control
24
9-8. FUNCTIONS OF DIP SWITCH AND JUMPER WIRE
Each function is controlled by the dip switch and the jumper wire on control P.C. board.
(Marks in the table below) Jumper wire ( : Short : Open)
Jumper wire
SW1
SW2
J41
J42
Functions
Model
settings
Capacity
settings
Pair number
setting with
wireless
remote
controller
Setting by the dip switch and jumper wire
MODELS
PKA-A·KA(L)
MODELS
A24
A30
A36
Wireless remote
controller setting
0
1
2
3 ~ 9
SETTING
12345
SETTING
12345
12345
12345
Control PCB setting
ON
OFF
ON
OFF
ON
OFF
ON
OFF
J41J42
Remarks
<Initial setting>
Wireless remote controller: 0
Control PCB: (for both J41 and J42)
4 pair number settings are supported.
The pair number settings of the wireless remote
controller and indoor control PCB (J41/J42) are
given in the table on the left.
(' ' in the table indicates the jumper wire is disconnected.)
JP3
Indoor
controller
board type
setting
Indoor controller board type
For product
Spare parts
JP3
: With JP3
: Without JP3
25
10
SPECIAL FUNCTION
10-1. Rotation Function (and back-up function, 2nd stage cut-in function)
Only PKA-A·KA (Wired remote controller use model)
10-1-1. Operation
(1) Rotation function (and Back-up function)
Outline of functions
· Main and sub units operate alternately according to the interval of rotation setting.
w Main and sub unit should be set by refrigerant address. (Outdoor Dip switch setting)
Refrigerant address "00"Main unit
Refrigerant address "01"Sub unit
· When error occurs to one unit, another unit will start operation. (Back-up function)
System constraint
· This function is available only by the grouping control system (INDOOR UNIT: OUTDOOR UNIT=1:1) of 2 refrigerant
groups. (Refer to Fig. 1)
· Main indoor unit should be connected for wired remote controller and the transmission line (TB5) for main and sub unit
should also be connected. (Refer to Fig. 1)
(This function cannot be set by wireless remote controller.)
· Set refrigerant address of each unit. (Dip switch on the outdoor unit ··· Refrigerant address 00/01)
Operation pattern
[Back-up function only]··· Request code number "312"
Start operation
Main
unit
IC-1
Run
Error occurs on main unit.
Main Sub
Abnormal condition
Fig. 1
Main
unit
Refrigerant address
"00"
OC-1
3(2)
Refrigerant address
"01"
OC-2
3(2)
Sub
unit
Sub
unit
IC-2
[Rotation function] & [Back-up function]··· Request code number "313~318"
Start operation
Main
unit
IC-1
Sub
unit
IC-2
(Ex:When the request code number is "313", each unit operates alternately in daily cycle.)
Stop
Main SubSub Main Main Sub
Run
Stop
1~28 days1~28 days
Stop
Run
Run
Error occurs on main unit.
Abnormal condition
Run
StopRun
IC-1
2
RC
OC : Outdoor unit
IC : Indoor unit
RC : Wired remote controller
2
IC-2
Note:
· When the uint is restarted to operate after turning off the power or OFF operation, the unit which was operating will start operation.
· To operate the main unit, refer to the 10-1-2. and set the requet code No. which is not the same as the current one, and set
again the former request code No.
(2) 2nd stage cut-in function
Outline of functions
· When the 1st unit can NOT supply with sufficient capacity for exceptionally high-demand conditions and the actual room
temperature reaches set point *, the 2nd unit starts operation in conjunction with the 1st unit.
· Once the actual room temperature goes down to 4degrees C (7.5 degrees F) below set point*, the 2nd unit stops operation
automatically.
(* set point = set temperature by R/C (remote controller) + 4, 6, 8:(7.5, 10.8, 14.4°F) (selectable))
· Number of operating units is determined according to the room temperature and set point.
· When room temperature becomes higher than set point, standby unit starts. (2 units operation)
· When room temperature falls below set point -4:(-7.5°F), standby unit stops. (1 unit operation)
26
System constraint
· This function is available only in cooling mode.
Ex.) Set temp. by R/C = 20:(68°F)
Set point = 26:(79°F)
When request code number is “323”.
26: 2nd unit Cut-in
(79°F)
4 degree C
(7.5 degreeF)
22: 2nd unit Cut-out
(71.5°F)
[2nd stage cut-in function]··· Request code number "322~324"
Start operationSub unit start operation
Main
unit
IC-1
Sub
unit
IC-2
Room temp. Set point
Run
StopStopRun
20:
(68°F)
10-1-2. How to set rotation function (Back-up function, 2nd stage cut-in function)
You can set these functions by wired remote controller.(Maintenance monitor)
NOTE
Both main and sub unit should be set in same setting.
Every time replacing indoor controller board for servicing, the function should be set again.
(1) Request Code List
Rotation setting
Setting No.
(Request code)
No.1
(310)
No.2
(311)
No.3
(312)
No.4
(313)
No.5
(314)
No.6
(315)
No.7
(316)
No.8
(317)
No.9
(318)
Setting contents
Monitoring the request code of current setting.
Rotation and Back-up OFF (Normal group control operation)
Back-up function only
Rotation ON (Alternating interval = 1day) and back up function
Rotation ON (Alternating interval = 3day) and back up function
Rotation ON (Alternating interval = 5day) and back up function
Rotation ON (Alternating interval = 7day) and back up function
Rotation ON (Alternating interval = 14day) and back up function
Rotation ON (Alternating interval = 28day) and back up function
Initial
setting
Room temp. < Set point -4(-7.5°F)
Sub unit stop
2nd stage cut-in setting
Setting No.
(Request code)
No.1
(320)
No.2
(321)
No.3
(322)
No.4
(323)
No.5
(324)
Setting contents
Monitoring the request code of current setting.
Cut-in function OFF
Cut-in Function ON(Set point = Set temp.+ 4°C(7.5°F))
Cut-in Function ON(Set point = Set temp.+ 6°C(10.8°F))
Cut-in Function ON(Set point = Set temp.+ 8°C(14.4°F))
2727
Initial
setting
(2) Setting method of each function by wired remote controller
B: Refrigerant address
C: Data display area
D: Request code display area
1. Stop operation().
2. Press the button () for 3 seconds so that [Maintenance mode] appears on the screen ().
TEST
After a while, [00] appears in the refrigerant address number display area.(at )
3. Press the button () for 3 seconds to switch to [Maintenance monitor].
CHECK
Note) It is not possible to switch to [Maintenance monitor] during data request in maintenance mode
(i.e., while “----” is blinking) since no buttons are operative.
[----] appears on the screen () when [Maintenance monitor] is activated.
(The display () now allows you to set a request code No.)
4. Press the [TEMP ( and )] buttons () to select the desired refrigerant address.
[ScreenB]
5. Press the [CLOCK ( and )] buttons () to set the desired request code No.(“311~318”, “321~324”)
6. Press the button () to perform function setting.
FILTER
If above setting operations are done correctly, "Request code number" will appear in data display area.()
[Example: When the "311" of "Request code number" is set, [311] appears on the screen.()]
[Refererence]
You can check current "request code number" setting by setting the "request code number"(“310” or “320”) and
pressing the button.()
FILTER
[Example: When the current setting is "Setting No.2(Request code 311)", [311] appears on the screen.()]
7. To return to normal mode, press the button ().
10-2. BACK-UP HEATING FUNCTION (CN152)
10-2-1. Operation
Outline of functions
The back-up heater signal is sent out according to the temperature difference between indoor room temperature and set temperature. This function is available only in heating operation.
10-2-2. How to connect
ON/OFF
Temperature difference
(Z=Set temp. - Room temp.)
1
2
3
Z 0˚C(˚F)
0 < Z < 2.5˚C(4.5˚F)
2.5˚C(4.5˚F) Z
Back-up heater
signal output
OFF
Keeping condition
ON
ON
When connecting to the connector CN152 of the indoor unit, use
PAC-SE59RA-E(optional parts).
(1) Press and unlock the knobs on both sides of the front
grille and lift the front grille until it is level. Pull the hinges
forward to remove the front grille. (See Photo 1)
(2) Remove 3 screw caps of the panel. Remove 5 screws.
(See Photo 1)
(3) Unfix 3 hooks. (See Figure 1)
(4) Hold the lower part of both ends of the panel and pull it
slightly toward you, and then remove the panel by pushing
it upward.
(5) Remove the screw of the corner box. (See Photo 1)
Remove the corner box.
Photo 1
Figure 1
Be careful when removing heavy parts.
Front grille
Screws and screw caps
Screws
Screw of the
corner box
Hooks
2. REMOVING THE INDOOR CONTROLLER BOARD
AND THE WIRELESS CONTROLLER BOARD
(1) Remove the panel and the corner box. (Refer to 1.)
(2) Remove the front and side electrical box covers (each 1
screw). (See Photo 2)
(3) Disconnect the connectors on the indoor controller board.
(See Photo 3)
(4) Remove the switch board holder and open the cover.
(5)
Pull out the indoor controller board toward you then remove
the indoor controller board and switch board. (See Photo 3)
(6) Remove the holder of wireless remote controller board.
(7)
Disconnect the connector of wireless remote controller
board and remove the wireless remote controller board
from the holder.
Photo 2
Screw of electrical
box cover (Front)
Photo 3
Connector
for ground
wire
Electrical
box
Water Cut
Holder of wireless
remote controller board
Terminal block (TB4)
Screw of electrical
box cover (side)
Switch board
holder
Indoor controller
board (I.B.)
Terminal block
(TB2) (option)
Terminal block
(TB5) (only PKA-KA)
29
3. REMOVING THE ELECTRICAL BOX
(1) Remove the panel and the corner box. (Refer to 1.)
(2) Remove the front and side electrical box covers (each 1
screw).
(3) Remove the indoor / outdoor connecting wire from termi-
nal block (TB4).
(4)
Disconnect the connectors on the indoor controller board.
(5) Disconnect the connector for ground wire.
(6) Remove the screw on lower side of the electrical box.
(See Photo 5)
(7) Push up the upper fixture catch to remove the box, then
remove it from the box fixture.
Photo 4
Connector
for ground
wire
Electrical
box
PHOTOSOPERATION PROCEDURE
Terminal block (TB4)
Indoor controller
board (I.B.)
Terminal block
(TB2) (option)
Terminal block
(TB5) (only PKA-KA)
4. REMOVING THE NOZZLE ASSEMBLY (with VANE
and VANE MOTOR) AND DRAIN HOSE
(1) Remove the panel and corner box. (Refer to 1.)
(2) Remove the electrical box covers. (Refer to 2.)
(3) Disconnect the vane motor connector (CN151) on the
indoor controller board.
(4) Pull out the drain hose from the nozzle assembly, and
remove nozzle assembly. (See Photo 5)
5. REMOVING THE VANE MOTOR
(1) Remove the nozzle assembly. (Refer to 4.)
(2) Remove 2 screws of the vane motor unit cover, and pull
out the vane motor unit.
(3) Remove 2 screws of the vane motor unit.
(4) Remove the vane motor from the vane motor unit.
(5) Disconnect the connector from the vane motor.
Photo 5
Nozzle assembly
Drain hose
Photo 6
(see the bottom)
Vane motor
Screw of electrical box
Screws of the vane
motor unit
Screws of the vane motor unit cover
30
PHOTOSOPERATION PROCEDURE
6. REMOVING THE INDOOR FAN MOTOR AND THE
LINE FLOW FAN
(1) Remove the panel and the corner box. (Refer to 1.)
(2) Remove the electrical box (Refer to 2.) and the nozzle
assembly (Refer to 3.).
(3) Remove the water cut. (See Photo 2)
(4) Remove the screw fixing the line flow fan. (See Photo 8)
(5) Remove 5 screws fixing the motor bed. (See Photo 7)
(6) Remove the lead wire of pipe thermistor from the hook of
motor bed. (See Photo 7)
(7) Remove the screw fixing motor band. (See Photo 7)
(8) Remove the motor bed together with fan motor and motor
band.
(9)
Remove 3 screws fixing the left side of the heat exchanger.
(See Photo 9)
(10) Lift the heat exchanger, and pull out the line flow fan to the
lower-left.
Photo 9
Screws of the
left side of the
heat exchanger
Photo 7
Photo 8
Screw of the motor band
Lead wire of pipe thermistor
Screws of the motor
bed
Screw of the line flow
fan
7. REMOVING THE LIQUID PIPE THERMISTOR AND
COND / EVA PIPE THERMISTOR
(1) Remove the panel and the corner box. (Refer to 1)
(2) Remove the electrical box covers. (Refer to 2.)
(3) Remove the water cut. (See Photo 2)
(4)
Remove the liquid pipe thermistor and cond / eva thermis-
tor.
(5) Disconnect the connector (CN44) on the indoor controller
board.
31
Photo 10
Cond / eva
thermistor (TH5)
Liquid pipe
thermistor (TH2)
PHOTOSOPERATION PROCEDURE
8. REMOVING THE HEAT EXCHANGER
(1) Remove the panel and the corner box. (Refer to 1.)
(2) Remove the electrical box (Refer to 3.) and the nozzle
assembly (Refer to 4.).
(3) Remove the water cut.
(4) Remove the pipe thermistors from each holder.
(5) Disconnect the connector for ground wire.
(6) Remove 3 screws fixing the left side of the heat
exchanger. (See Photo 9)
(7) Remove the heat exchanger.
Photo 11
Heat exchanger
Photo 12
Heat exchanger
Liquid pipe
thermistor (TH2)
Lead wire for TH5
Water Cut
Connector for
ground
9. REMOVING THE ROOM TEMPERATURE THERMISTOR
(1) Remove the panel and corner box. (Refer to 1.)
(2) Remove the electrical box covers.
(3) Remove the room temperature thermistor.
(4) Disconnect the connector (CN20) on the indoor controller
board.
HEAD OFFICE : TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
CCopyright 2009 MITSUBISHI ELECTRIC ENGINEERING CO., LTD.
Distributed in Mar. 2009 No.OCH457 PDF 6
Made in Japan
Photo 13
Indoor controller
board (I.B.)
Room temp.
thermistor (TH1)
New publication, effective Mar. 2009
Specifications subject to change without notice
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.