Before obtaining access to terminals, all supply
circuits must be disconnected.
3-2. CAUTIONS RELATED TO NEW REFRIGERANT
Cautions for units utilizing refrigerant R410A
Use new refrigerant pipes.
Make sure that the inside and outside of refrigerant piping is clean and it has no contamination
such as sulfur hazardous for use, oxides, dirt,
shaving particles, etc.
In addition, use pipes with specified thickness.
Contamination inside refrigerant piping can cause deterioration of refrigerant oil etc.
Store the piping to be used indoors during
installation and both ends of the piping sealed
until just before brazing. (Leave elbow joints, etc.
in their packaging.)
If dirt, dust or moisture enters into refrigerant cycle, that
can cause deterioration of refrigerant oil or malfunction of
compressor.
Use ester oil, ether oil or alkylbenzene oil (small
amount) as the refrigerant oil applied to flares
and flange connections.
If large amount of mineral oil enters, that can cause deterioration of refrigerant oil etc.
Do not use refrigerant other than R410A.
If other refrigerant (R22 etc.) is used, chlorine in refrigerant can cause deterioration of refrigerant oil etc.
Use a vacuum pump with a reverse flow check
valve.
Vacuum pump oil may flow back into refrigerant cycle and
that can cause deterioration of refrigerant oil etc.
Use the following tools specifically designed for
use with R410A refrigerant.
The following tools are necessary to use R410A refrigerant.
If dirt, dust or moisture enters into refrigerant cycle, that can
cause deterioration of refrigerant oil or malfunction of compressor.
Charge refrigerant from liquid phase of gas
cylinder.
If the refrigerant is charged from gas phase, composition
change may occur in refrigerant and the efficiency will be
lowered.
[1] Cautions for service
(1) Perform service after recovering the refrigerant left in unit completely.
(2) Do not release refrigerant in the air.
(3) After completing service, charge the cycle with specified amount of refrigerant.
(4) When performing service, install a filter drier simultaneously.
Be sure to use a filter drier for new refrigerant.
Do not use a charging cylinder.
If a charging cylinder is used, the composition of refrigerant will change and the efficiency will be lowered.
Ventilate the room if refrigerant leaks during
operation. If refrigerant comes into contact with
a flame, poisonous gases will be released.
3
[2] Additional refrigerant charge
When charging directly from cylinder
· Check that cylinder for R410A on the market is syphon type.
· Charging should be performed with the cylinder of syphon stood vertically. (Refrigerant is charged from liquid phase.)
Unit
Gravimeter
[3] Service tools
Use the below service tools as exclusive tools for R410A refrigerant.
No. Tool name Specifications
1Gauge manifold · Only for R410A
· Use the existing fitting
· Use high-tension side pressure of 5.3MPa·G or over.
2Charge hose · Only for R410A
· Use pressure performance of 5.09MPa·G or over.
3 Electronic scale
4Gas leak detector · Use the detector for R134a, R407C or R410A.
5Adaptor for reverse flow check · Attach on vacuum pump.
6Refrigerant charge base
7Refrigerant cylinder · Only for R410A · Top of cylinder (Pink)
Airflow can be changed
to horizontally by moving
the guide vane to the left
or right.
Filter
Air outlet
Air intake
Room air is suctioned
here
.
Air outlet
Air intake grille
Auto vane
Filter
Removes dust and dirt
from the intake air.
Air outlet
Air intake grille
Auto vane
Disperse airflow up and
down as well as adjusts the
angle of airflow direction.
5
PAR-21MAA
ON/OFF
FILTER
CHECK
OPERATION
CLEAR
TEST
TEMP.
MENU
BACKDAY
MONITOR/SET
CLOCK
ON/OFF
Temperature setting buttons
Down
Up
Timer Menu button
(Monitor/Set button)
Mode button (Return button)
Set Time buttons
Back
Ahead
Timer On/Off button
(Set Day button)
Opening the
lid
ON/OFF button
Fan Speed button
Filter button
(<Enter> button)
Test Run button
Check button (Clear button)
Airflow Up/Down button
Louver button
( Operation button)
To return operation
number
Ventilation button
( Operation button)
To go to next operation
number
Built-in temperature sensor
Wired remote controller
Once the controllers are set, the same operation mode can be repeated by simply pressing the ON/OFF button.
6
Wired remote controller
Display Section
For purposes of this explanation,
all parts of the display are shown
as lit. During actual operation, only
the relevant items will be lit.
Identifies the current operation
Shows the operating mode, etc.
*Multilanguage display is available.
“Centrally Controlled” indicator
Indicates that operation from the
remote controller has been prohibited by a master controller.
“Timer is Off” indicator
Indicates that the timer is off.
Temperature Setting
Shows the target temperature.
Day-of-Week
Shows the current day of the week.
Time/Timer Display
Shows the current time, unless the simple or Auto Off
timer is set.
If the simple or Auto Off timer is set, the time to be
switched off is shown.
TIME SUN MON TUE WED THU FRI SAT
TIMER
AFTER
ERROR CODE
°F°C
Hr
AFTER
°F°C
ONLY1Hr.
Up/Down Air Direction indicator
The indicator shows the direction of the outcoming airflow.
“One Hour Only” indicator
Displayed if the airflow is set to
low or downward during COOL
or DRY mode. (Operation varies
according to model.)
The indicator goes off in 1 hour,
when the airflow direction
also changes.
Room Temperature display
Shows the room temperature. The room
temperature display range is 46–102°F.
The display blinks if the temperature
is less than 46°
Louver display
Indicates the action of the swing louver.
Does not appear if the louver is not
running.
(Power On indicator)
Indicates that the power is on.
ON
OFF
FUNCTION
FILTER
WEEKLY
SIMPLE
AUTO OFF
F
or 102°F or more.
“Sensor” indication
Displayed when the remote controller
sensor is used.
“Locked” indicator
Indicates that remote controller buttons have been locked.
“Clean The Filter” indicator
To be displayed on when it is time to
clean the filter.
Timer indicators
The indicator comes on if the corresponding timer is set.
Fan Speed indicator
Shows the selected fan speed.
Ventilation indicator
Appears when the unit is running in
Ventilation mode.
Note:
L
“PLEASE WAIT” message
This message is displayed for approximately 3 minutes when power is supplied to the indoor unit or when the unit is recovering from a power failure.
L
“NOT AVAILABLE” message
This message is displayed if an invalid button is pressed (to operate a function that the indoor unit does not have).
If a single remote controller is used to operate multiple indoor units simultaneously that are different types, this message will not be displayed as
far as any of the indoor units is equipped with the function.
7
Wireless remote controller
CHECK
TEST RUN
display
Indicate that the unit is being checked or
test-run.
MODEL SELECT
Blinks when model is selected.
display
display
Lights up while the signal is transmitted to
the indoor unit when the button is pressed.
Temperature setting display
Indicates the desired temperature setting
which is set.
OPERATION MODE display
OPERATION MODE display
Indicates which operation mode is in effect.
display
The vertical direction of airflow is indicated.
display
Displays selected fan speed.
ON/OFF button
The unit is turned ON and OFF alternately
each time the button is pressed.
FAN SPEED SELECT button
Changes the fan speed.
MODE SELECT button
Switches the operation mode between
COOLING/DRY/FAN/HEATING and AUTO
mode.
+In case the outdoor unit is cooling only
type, the heating and auto mode are not
available.
COOL
DRY
AUTO
FAN
HEAT
RUN
MODEL
SELECT
FAN
SWING
NOT AVAILABLE
TEST
CHECK
ON/OFF TEMP
FAN
MODE
CHECK
VAN E
LOUVER
TEST RUN
RESETSETCLOCK
°F
°C
AMPMSTOP
AMPM
START
AUTO STOP
AUTO START
h
min
CLOCK display
Displays the current time.
TIMER display
Displays when in timer operation or when
setting timer.
“” “ ” display
Displays the order of timer operation.
“ ” “ ” display
Displays whether timer is on or off.
button
Sets any desired room temperature.
TIMER CONTROL buttons
AUTO STOP (OFF timer): when this switch
is set, the air conditioner will be
autom at ically stopped at the preset time.
AUTO START (ON timer): when this switch
is set, the air conditioner will be
automatically started at the preset time.
"h" and "min" buttons
Buttons used to set the “hour and minute” of
the current time and timer settings.
CHECK-TEST RUN button
Performs an inspection check or test
operation.
Do not use it for normal operation.
VANE CONTROL button
Changes the air flow direction.
LOUVER button
Changes left / right airflow direction.
(Not available for this model.)
CLOCK button
RESET button
SET button
8
5
SPECIFICATIONS
Service Ref.
Power supply(phase, cycle, voltage)
Max. Fuse Size
Min. Circuit Ampacity
External finish
Heat exchanger
Fan Fan(drive) % No.Fan motor output
Fan motor
Airflow
(Low-Medium2-Medium1-High)
External static pressure
INDOOR UNIT
Operation control & Thermostat
Noise level(
Field drain pipe I.D.
Dimensions
Weight
Service Ref.
Power supply(phase, cycle, voltage)
Max. Fuse Size
Min. Circuit Ampacity
External finish
Heat exchanger
Fan Fan(drive) % No.Fan motor output
Fan motor
External static pressure
INDOOR UNIT
Operation control & Thermostat
Noise level(Low-High)
Field drain pipe I.D.
Dimensions
Power supply (phase, cycle, voltage)
Max. Fuse Size
Min. Circuit Ampacity
External finish
Heat exchanger
Fan Fan (drive) % No.Fan motor output
Fan motor
Low-High
Airflow (
External static pressure
INDOOR UNIT
Operation control & Thermostat
Noise level(Low-High)
Field drain pipe I.D.
Dimensions
Power supply (phase, cycle, voltage)
Max. Fuse Size
Min. Circuit Ampacity
External finish
Heat exchanger
Fan Fan (drive) % No.Fan motor output
Fan motor
Airflow (Low-High)
External static pressure
INDOOR UNIT
Operation control & Thermostat
Noise level (Low-High)
Field drain pipe I.D.
Dimensions
Power supply (phase, cycle, voltage)
Max. Fuse Size
Min. Circuit Ampacity
External finish
Heat exchanger
Fan Fan(drive) % No.Fan motor output
Fan motor
Airflow (Low-High)
External static pressure
INDOOR UNIT
Operation control & Thermostat
Noise level (Low-High)
Field drain pipe I.D.
Dimensions
CAPACITOR<FAN MOTOR>
FAN MOTOR
VANE MOTOR
TERMINAL BLOCK<INDOOR/OUTDOOR
CONNECTING LINE>
TERMINAL BLOCK<REMOTE CONTROLLER
TRANSMISSION LINE >
ROOM TEMP.THERMISTOR
Ω, 77°F/5.2kΩ DETECT>
<32°F/15k
PIPE TEMP.THERMISTOR/LIQUID
Ω, 77°F/5.2kΩ DETECT>
<32°F/15k
COND./EVA.TEMP.THERMISTOR
Ω, 77°F/5.2kΩ DETECT>
<32°F/15k
WIRED REMOTE CONTROLLER BOARD
Please set the voltage
using the remote controller.
For the setting method,
please refer to the indoor
unit Installation Manual.
SYMBOL
W.B
Table 2
MODELS
PKAA12GA(L)
WIRELESS REMOTE CONTROLLER BOARD
RECEIVING UNIT
RU
BZ
BUZZER
LED1
LED<RUN INDICATOR >
LED2
LED<HOT ADJUST>
SW1
SWITCH<HEATING ON/OFF>
SW2
SWITCH<COOLING ON/OFF>
NAME
Table 1
SW1
Service board
1 2 3 4 5
ON
OFF
SW2
Service boardService board
1 2 3 4 5
ON
OFF
MODELS
PKAA18GA(L)
1 2 3 4 5
ON
OFF
YLW
ORN
YLW
ORN
BRN
TB4
S1
S2
S3
+1
TO
OUTDOOR
UNIT
MF
M
1~
1
32
C
BLK
WHT
RED
I.B
FAN
(
)
WHT
5
1
3
BCR
SW2 SW1
SWE
ON
OFF
Refer to tables 1 and 2
for service PCB.
POWER
CNDK
X4
(RED)
WHT
RED
11
3
POWER
CND
(ORN)
ZNR
U
YLW
LED3 LED2 LED1
CN24
(
YLW
INTAKE
CN20
)
(
)
RED
12
1
2121212
ttt
ORN
BLK
1
3
POWER
CN2D
(WHT)
FUSE
CN41
CN51
51
LIQUID
CN21
(
WHT
TH2
PIPE
CN29
)
(
BLK
TH5TH1
WHT
BRN
1
2
A-CONTROL
CN3C
(BLU)
(
)
WHT
14
(
)
WHT
REMOCON
CN22
)
(
BLU
ORN
3
(
CN2L
RED
12
(
CN32
WHT
13
CN30
(
BLK
)
6
VANE
CN6V
(GRN)
)
1
6
1
)
WIRELESS
CN90
(WHT)
)
9
13
1
TRANSMISSION WIRES DC12V
2
TB5
M
MV
99
RU
RECEIVER
For A12/18GAL
CNB
BZ
LED1 LED2 SW2SW1
R.B
1
2
TB6
For A12/18GA
NOTES:
1. Since the outdoor side electric wiring may change be sure to check the outdoor unit electric wiring for servicing.
2. Indoor and outdoor connecting wires are made with polarities, make wiring matching terminal numbers (S1, S2, S3).
3. Symbols used in wiring diagram above are, : Connector, : Terminal (block).
4. This diagram shows the wiring of Indoor and Outdoor connecting wires (specification of 230V), adopting superimposed system of
power and signal.
+1. Use copper supply wires.
Please set the voltage
using the remote controller.
For the setting method,
please refer to the indoor
unit Installation Manual.
MF
M
1~
SYMBOLNAME
POWER SUPPLY<R.B>
LED2
C
MF
MV
TB4
TB5,TB6
TH1
TH2
TH5
R.B
TRANSMISSION<INDOOR-OUTDOOR>LED3
CAPACITOR<FAN MOTOR>
FAN MOTOR
VANE MOTOR
TERMINAL BLOCK<INDOOR/OUTDOOR
CONNECTING LINE>
TERMINAL BLOCK<REMOTE CONTROLLER
TRANSMISSION LINE >
ROOM TEMP.THERMISTOR
<32°F/15k
Ω
, 77°F/5.2kΩ DETECT>
PIPE TEMP.THERMISTOR/LIQUID
Ω
, 77°F/5.2kΩ DETECT>
<32°F/15k
COND./EVA.TEMP.THERMISTOR
<32°F/15k
Ω
, 77°F/5.2kΩ DETECT>
WIRED REMOTE CONTROLLER BOARD
YLW
ORN
YLW
ORN
BRN
TB4
S1
S2
S3
SYMBOL
W.B
+1
TO
OUTDOOR
UNIT
WIRELESS REMOTE CONTROLLER BOARD
RECEIVING UNIT
RU
BZ
BUZZER
LED1
LED<RUN INDICATOR >
LED2
LED<HOT ADJUST>
SW1
SWITCH<HEATING ON/OFF>
SW2
SWITCH<COOLING ON/OFF>
Table 1
SW1
Service board
1 2 3 4 5
Table 2
MODELS
PKAA24FA(L)
MODELS
PKAA30FA(L)
MODELS
PKAA36FA(L)
NAME
ON
OFF
SW2
Service board
1 2 3 4 5
Service board
1 2 3 4 5
Service board
1 2 3 4 5
ON
OFF
ON
OFF
ON
OFF
1
32
C
BLK
WHT
RED
I.B
FAN
(
WHT
BCR
)
SWE
1
3
SW2 SW1
POWER
5
CNDK
(RED)
X4
ON
OFF
Refer to tables 1 and 2
for service PCB.
NOTES:
1. Since the outdoor side electric wiring may change be sure to check the outdoor unit electric wiring for servicing.
WHT
RED
11
3
POWER
CND
(ORN)
ZNR
U
YLW
LED3 LED2 LED1
LIQUID
CN24
(
YLW
INTAKE
CN20
)
(
)
RED
12
1
2121212
ttt
ORN
BLK
WHT
1
3
POWER
CN2D
(WHT)
FUSE
CN41
CN51
51
PIPE
CN21
CN29
(
)
(
WHT
BLK
TH2
TH5TH1
BRN
1
2
A-CONTROL
CN3C
(BLU)
(
)
WHT
14
(
)
WHT
REMOCON
CN22
)
(
)
BLU
ORN
3
(
CN2L
RED
12
(
CN32
WHT
13
CN30
(
BLK
6
)
6
VANE
CN6V
(GRN)
1
1
)
WIRELESS
CN90
(WHT)
)
9
13
1
TRANSMISSION WIRES DC12V
2
TB5
M
MV
99
RU
RECEIVER
For A24/30/36FAL
BZ
LED1 LED2 SW2 SW1
R.B
TB6
For A24/30/36FA
2. Indoor and outdoor connecting wires are made with polarities, make wiring matching terminal numbers (S1, S2, S3).
3. Symbols used in wiring diagram above are, : Connector, : Terminal (block).
4. This diagram shows the wiring of Indoor and Outdoor connecting wires (specification of 230V), adopting superimposed system of
power and signal.
+1. Use copper supply wires.
Refrigerant flow in cooling
Refrigerant flow in heating
1
2
19
10TROUBLESHOOTING
10-1. TROUBLESHOOTING
<Error code display by self-diagnosis and actions to be taken for service (summary)>
Present and past error codes are logged and displayed on the wired remote controller or controller board of outdoor unit.
Actions to be taken for service and the trouble reoccurrence at field are summarized in the table below. Check the contents
below before investigating details.
Unit conditions at service
The trouble is reoccurring.
The trouble is not reoccurring.
Error code
Displayed
Not displayed
Logged
Not logged
Actions to be taken for service (summary)
Judge what is wrong and take a corrective action
according to “SELF-DIAGNOSIS ACTION TABLE” (10-3).
Identify the cause of the trouble and take a corrective
action according to “TROUBLESHOOTING
BY INFERIOR PHENOMENA ” (10-4).
Consider the temporary defects such as the work of
protection devices in the refrigerant circuit including
compressor, poor connection of wiring, noise and etc.
Re-check the symptom, and check the installation
environment, refrigerant amount, weather when the
trouble occurred, and wiring related.
Reset error code logs and restart the unit after finishing
service.
There is no abnormality in electrical components,
controller boards, and remote controller.
Recheck the abnormal symptom.
Identify the cause of the trouble and take a corrective
action according to “TROUBLESHOOTING
BY INFERIOR PHENOMENA ” (10-4).
Continue to operate unit for the time being if the cause
is not ascertained.
There is no abnormality in electrical components,
controller boards, remote controller etc.
20
10-2. MALFUNCTION-DIAGNOSIS METHOD BY REMOTE CONTROLLER
<In case of trouble during operation>
When a malfunction occurs to the air conditioner, both indoor unit and outdoor unit will stop and operation lamp blinks to inform
unusual stop.
<Malfunction-diagnosis method at maintenance service>
[Procedure]
CHECK
display
ON/OFF
button
CHECK
button
ON/OFF
MODE
CHECK
TEST RUN
SET
CHECK
FAN
VAN E
LOUVER
RESET
TEMP
AUTO STOP
AUTO START
CLOCK
min
h
Refrigerant
address
display
Temperature
button
HOUR
button
1. Press the CHECK button twice.
2. Press the temperature
buttons.
3. Point the remote controller at the
sensor on the indoor unit and
press the HOUR button.
• "CHECK" lights, and refrigerant
address "00" blinks.
• Check that the remote controller's
display has stopped before continuing.
• Select the refrigerant address of the
indoor unit for the self-diagnosis.
Note: Set refrigerant address using the
outdoor unit’s DIP switch (SW1).
(For more information, see the
outdoor unit installation manual.)
• If an air conditioner error occurs, the
indoor unit's sensor emits an intermit tent buzzer sound, the operation lamp
blinks, and the error code is
output.
(It takes 3 seconds at most for error
code to appear.)
4. Point the remote controller at the
sensor on the indoor unit and
press the ON/OFF button.
• The check mode is cancelled.
To be continued to the next page.
21
• Refer to the following tables for details on the check codes.
[Output pattern A]
Beeper sounds
OPERATION
INDICATOR
lamp blinking
pattern
Beep
Self-check
starts
(Start signal
received)
Beep Beep BeepBeepBeep Beep
1st2nd3
Off
Approx. 2.5 sec.On0.5 sec.On0.5 sec.On0.5 sec.
Number of blinks/beeps in pattern indicates the check
code in the following table (i.e., n=5 for “P5”)
rd
0.5 sec.
th
n
On
Off
Approx. 2.5 sec.On0.5 sec.On0.5 sec.
Number of blinks/beeps in pattern indicates
the check code in the following table
1st2
nd
· · · Repeated
[Output pattern B] Only A-CONTROL
Beeper sounds
OPERATION
INDICATOR
lamp blinking
pattern
BeepBeep Beep BeepBeep
1st2nd3
Off
Self-check
starts
(Start signal
received)
Approx. 2.5 sec.OnApprox. 3 sec.On0.5 sec.On0.5 sec.On0.5 sec.On0.5 sec.
Number of blinks/beeps in pattern indicates the check
code in the following table (i.e., n=5 for “U2”)
rd
th
n
Off
Approx. 2.5 sec.OnApprox. 3 sec.On0.5 sec.On0.5 sec.
Number of blinks/beeps in pattern indicates
the check code in the following table
Beep Beep
1st2
nd
· · · Repeated
[Output pattern A] Errors detected by indoor unit
Wireless remote controller
Beeper sounds/OPERATION
INDICATOR lamp blinks Check code
Wired remote controller
SymptomRemark
(Number of times)
1P1
2
P2
P9
3E6,E7
4P4
5
P5
PA
6P6
7EE
8P8
9E4, E5
10
11
–
–
12Fb
–
E0, E3
–E1, E2
[Output pattern B]
Wireless remote controller
Errors detected by unit other than indoor unit (outdoor unit, etc.)
Wired remote controller
Beeper sounds/OPERATION
INDICATOR lamp blinks Check code
Intake sensor error
Pipe (TH2) sensor error
Pipe (TH5) sensor error
Indoor/outdoor unit communication error
Drain sensor error
Drain pump error
Forced compressor stop(due to water leakage abnormality)
Freezing/Overheating protection operation
Communication error between indoor and outdoor units
Pipe temperature error
Remote controller signal receiving error
–
–
Indoor unit control system error (memory error, etc.)
Remote controller transmission error
Remote controller control board error
SymptomRemark
(Number of times)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
E9
UP
U3,U4
UF
U2
U1,Ud
U5
U8
U6
U7
U9,UH
–
–
Others
*1 If the beeper does not sound again after the initial
the OPERATION INDICATOR lamp does not come on,
Indoor/outdoor unit communication error
(Transmitting error) (Outdoor unit)
Compressor overcurrent interruption
Open/short of outdoor unit thermistors
Compressor overcurrent interruption (When compressor locked)
Abnormal high discharging temperature/49C worked/
insufficient refrigerant
Abnormal high pressure (63H worked)/Overheating
protection operation
Abnormal temperature of heatsink
Outdoor unit fan protection stop
Compressor overcurrent interruption/Abnormal of power module
Abnormality of superheat due to low discharge temperature
Abnormality such as overvoltage or voltage shortage and
abnormal synchronous signal to main circuit/Current sensor error
–
–
Other errors (Refer to the technical manual for the outdoor unit.)
2 beeps to confirm the self-check start signal was received and
there are no error records.
As for outdoor
unit, refer to
outdoor unit's
service manual.
For details, check
the LED display
of the outdoor
controller board.
*2 If the beeper sounds 3 times continuously “beep, beep, beep (0.4 + 0.4 + 0.4 sec.)” after the initial 2 beeps to confirm
the self-check start signal was received, the specified refrigerant address is incorrect.
22
• On wireless remote controller
The continuous buzzer sounds from receiving section of indoor unit.
Blink of operation lamp
• On wired remote controller
Check code displayed in the LCD.
If the unit cannot be operated properly after the test run has been performed, refer to the following table to find out the cause.
•
Symptom
Wired remote controllerLED 1, 2 (PCB in outdoor unit)
For about 2 minutes after power-on,operation
PLEASE WAIT
PLEASE WAIT → Error code
Display messages do not
appear even when operation
switch is turned ON (operation
lamp does not light up).
On the wireless remote controller with condition above, following phenomena take place.
• No signals from the remote controller can be received.
• Operation lamp is blinking.
• The buzzer makes a short ping sound.
Note:
Operation is not possible for about 30 seconds after cancellation of function selection. (Correct operation)
For description of each LED (LED1, 2, 3) provided on the indoor controller, refer to the following table.
LED1 (power for microcomputer)Indicates whether control power is supplied. Make sure that this LED is
LED2 (power for remote controller)
LED3 (communication between indoor and
outdoor units)
For about 2
minutes after
power-on
Subsequent to
about 2 minutes
after power-on
After LED 1, 2 are lighted, LED 2 is
turned off, then only LED 1 is
lighted.
(Correct operation)
Only LED 1 is lighted. →
Only LED 1 is lighted.
always lit.
Indicates whether power is supplied to the remote controller.
This LED lights only in the case of the indoor unit which is connected to the
outdoor unit refrigerant address “0”.
Indicates state of communication between the indoor and outdoor units.
Make sure that this LED is always blinking.
LED 1, 2 blink.
→
LED 1 blinks twice,
LED 2 blinks once.
•
of the remote controller is not possible
due to system start-up. (Correct operation)
•Connector for the outdoor unit’s protection
device is not connected.
•Reverse or open phase wiring for the outdoor
unit’s power terminal block (L1, L2, GR)
•Incorrect wiring between indoor and outdoor
units (incorrect polarity of S1, S2, S3)
•Remote controller wire short
Cause
23
10-3. SELF-DIAGNOSIS ACTION TABLE
Error Code
P1
P2
P4
P5
Abnormal
Room temperature thermistor (TH1)
1 The unit is in 3-minute resume preven-
tion mode if short/open of thermistor is
detected. Abnormal if the unit does not
reset normally after 3 minutes. (The
unit returns to normal operation, if it
has been reset normally.)
2 Constantly detected during cooling, dry-
ing, and heating operation.
Short: -90:(194˚F) or more
Open: -40:(-40˚F) or less
Pipe temperature thermistor/Liquid
(TH2)
1 The unit is in 3-minute resume
prevention mode if short/open of
thermistor is detected. Abnormal if the
unit does not reset normally after 3 minutes. (The unit returns to normal operation, if it has been reset normally.)
2 Constantly detected during cooling,
drying, and heating (except defrosting)
operation.
Short: 90:(194˚F) or more
Open: -40:(-40˚F) or less
Drain sensor (DS)
1 Suspensive abnormality, if short/open
of thermistor is detected for 30 seconds
continuously.
Turn off compressor and indoor fan.
Short/open is detected for 30 seconds con-
2
tinuously during suspensive abnormality.
(The unit returns to normal operation, if
it has been reset normally.)
3 Detect the following condition.
• During cooling and drying operation
• In case that pipe <liquid> temperature
- room temperature <-10deg
(Except defrosting)
• When pipe <liquid> temperature or
room temperature is short/open temperature.
• During drain pump operation
Malfunction of drain pump (DP)
1 Suspensive abnormality, if thermistor
of drain sensor heats itself and
temperature rises slightly. Turn off
compressor and indoor fan.
2 Drain pump is abnormal if the condition
above is detected during suspensive
abnormality.
3 Constantly detected during drain pump
operation.
point and detection method
1 Defective thermistor
characteristics
2 Contact failure of connector
3 Breaking of wire or contact
failure of thermistor wiring
4 Defective indoor controller
1 Defective thermistor
characteristics
2 Contact failure of connector
3 Breaking of wire or contact
failure of thermistor wiring
4 Defective refrigerant circuit is
-40:(-40˚F) or less.
5 Defective indoor controller board
1 Defective thermistor
characteristics
2 Contact failure of connector
3 Breaking of wire or contact
failure of drain sensor wiring
4 Defective indoor controller board
1 Malfunction of drain pump
2 Defective drain
Clogged drain pump
Clogged drain pipe
3 Attached drop of water at the
4 Defective indoor controller board
Note: Refer to the manual of outdoor unit for the details of display
such as F, U, and other E.
Cause
(CN20) on the indoor controller
board (Insert failure)
board
(CN21) on the indoor controller
board (Insert failure)
causing thermistor temperature
of 90:(194˚F) or more or
(CN31) on the indoor controller
board (Insert failure)
If you put force on (draw or bend) the lead wire
with measuring resistance value of thermistor
breaking of wire or contact failure can be detected.
2 Check contact failure of connector (CN20)
on the indoor controller board. Refer to 10-7.
Turn the power on again and check restart
after inserting connector again.
4 Check room temperature display on remote
controller.
Replace indoor controller board if there is abnor-
mal difference with actual room temperature.
Turn the power off, and on again to operate
after check.
1–3 Check resistance value of thermistor.
For characteristics, refer to (P1) above.
2 Check contact failure of connector (CN21)
on the indoor controller board. Refer to 10-7.
Turn the power on and check restart after
inserting connector again.
4 Check pipe <liquid> temperature with remote
controller in test run mode. If pipe <liquid>
temperature is extremely low (in cooling
mode) or high (in heating mode), refrigerant
circuit may have defect.
5 Check pipe <liquid> temperature with remote
controller in test run mode. If there is extreme
difference with actual pipe <liquid> temperature,
replace indoor controller board.
Turn the power off, and on again to operate
after check.
on the indoor controller board. Refer to 10-7.
Turn the power on again and check restart
after inserting connector again.
4 Replace indoor controller board if drain
pump operates with the line of drain sensor
connector CN31-1 and 2 is short-circuited,
and abnormality reappears.
Turn the power off, and on again to operate
after check.
1 Check if drain pump works.
2 Check drain function.
3 Check the setting of lead wire of drain sensor
and check clogs of the filter.
4 Replace indoor controller board if drain
pump operates with the line of drain sensor
connector CN31-1 and 2 is short-circuited
and abnormality reappears.
Refer to 10-7.
Turn the power off, and on again to operate
after check.
24
Error Code
Abnormal
Freezing/overheating protection is working
1 Freezing protection (Cooling mode)
The unit is in 6-minute resume prevention
mode if pipe <liquid or condenser/evaporator> temperature stays under
-15:(5˚F) for 3 minutes, 3 minutes after
the compressor started. Abnormal if it
stays under -15:(5˚F) for 3 minutes
again within 16 minutes after 6-minute
resume prevention mode.
point and detection method
Cause
(Cooling or drying mode)
1 Clogged filter (reduced airflow)
2 Short cycle of air path
3 Low-load (low temperature)
operation out of the tolerance
range
4 Defective indoor fan motor
• Fan motor is defective.
• Indoor controller board is defective.
5 Defective outdoor fan control
6 Overcharge of refrigerant
7 Defective refrigerant circuit
(clogs)
Countermeasure
(Cooling or drying mode)
1 Check clogs of the filter.
2 Remove shields.
4 Measure the resistance of fan motor's winding.
Measure the output voltage of fan's connector
(FAN) on the indoor controller board.
WThe indoor controller board should be
normal when voltage of AC 208/230V is
detected while fan motor is connected.
Refer to 10-7.
5 Check outdoor fan motor.
67 Check operating condition of refrigerant
circuit.
P6
P8
2 Overheating protection (Heating mode)
The units is in 6-minute resume
prevention mode if pipe <condenser /
evaporator> temperature is detected as
over 70:(158˚F) after the compressor
started. Abnormal if the temperature
of over 70:(158˚F) is detected again
within 10 minutes after 6-minute resume
prevention mode.
Pipe temperature
<Cooling mode>
Detected as abnormal when the pipe temperature is not in the cooling range 3 minutes after compressor start and 6 minutes
after the liquid or condenser/evaporator pipe
is out of cooling range.
Note 1) It takes at least 9 minutes to
detect.
Note 2) Abnormality P8 is not detected in
drying mode.
Cooling range
TH: Lower temperature between liquid pipe
TH1: Intake temperature
<Heating mode>
When 10 seconds have passed after the
compressor starts operation and the hot
adjustment mode has finished, the unit is
detected as abnormal when condenser/
evaporator pipe temperature is not in heating range within 20 minutes.
:-3 deg C[-5.4deg F]]
temperature (TH2) and condenser/
evaporator temperature (TH5)
(TH-TH1)
(Heating mode)
1 Clogged filter (reduced airflow)
2 Short cycle of air path
3 Overload (high temperature)
operation beyond the tolerance
range
4 Defective indoor fan motor
• Fan motor is defective.
• Indoor controller board is defective.
5 Defective outdoor fan control
6 Overcharge of refrigerant
7 Defective refrigerant circuit
(clogs)
8
Bypass circuit of outdoor unit
is defective.
1 Slight temperature difference
between indoor room
temperature and pipe <liquid
or condenser / evaporator>
temperature thermistor
• Shortage of refrigerant
• Disconnected holder of pipe
<liquid or condenser /
evaporator> thermistor
• Defective refrigerant circuit
2 Converse connection of
extension pipe (on plural units
connection)
3 Converse wiring of indoor/
outdoor unit connecting wire
(on plural units connection)
4 Defective detection of indoor
room temperature and pipe
<condenser / evaporator>
temperature thermistor
5 Stop valve is not opened
completely.
(Heating mode)
1 Check clogs of the filter.
2 Remove shields.
4
Measure the resistance of fan motor's winding.
Measure the output voltage of fan's connector
(FAN) on the indoor controller board.
WThe indoor controller board should be
normal when voltage of AC 208/230V is
detected while fan motor is connected.
Refer to 10-7.
5 Check outdoor fan motor.
6~8Check operating condition of refrigerant
circuit.
1~4 Check pipe <liquid or condenser /
evaporator> temperature with room
temperature display on remote controller
and outdoor controller circuit board.
Pipe <liquid or condenser / evaporator>
temperature display is indicated by setting
SW2 of outdoor controller circuit board as
follows.
Conduct temperature check with outdoor
controller circuit board after connecting
(
‘A-Control Service Tool(PAC-SK52ST)’.
23Check converse connection of extension
pipe or converse wiring of indoor/outdoor
unit connecting wire.
)
Note 3) It takes at least 27 minutes to
detect abnormality.
Note 4) It excludes the period of defrosting
(Detection restarts when defrosting
mode is over)
Heating range
:3 deg C[5.4deg F][
(TH5-TH1)
25
Error Code
P9
E0
or
E4
E3
or
E5
Abnormal point and detection method
Pipe temperature thermistor /
Condenser-Evaporator (TH5)
1 The unit is in 3-minute resume protec-
tion mode if short/open of thermistor is
detected. Abnormal if the unit does not
get back to normal within 3 minutes. (The
unit returns to normal operation, if it has
been reset normally.)
2 Constantly detected during cooling,
drying, and heating operation (except
defrosting)
Short: 90:(194˚F) or more
Open: -40:(-40˚F) or less
data, and when detecting it, judges
different data to be abnormal 30
continuous times. (Error code: E3)
1 Abnormal if indoor controller board could
not find blank of transmission path.
(Error code: E5)
2 Indoor controller board receives trans-
mitted data at the same time, compares
the data,and when detecting it, judges
different data to be abnormal 30
continuous times. (Error code: E5)
Cause
1 Defective thermistor
characteristics
2 Contact failure of connector
(CN29) on the indoor controller
board (Insert failure)
3 Breaking of wire or contact
failure of thermistor wiring
4 Temperature of thermistor is
90:(194˚F) or more or -40:
(-40˚F) or less caused by
defective refrigerant circuit.
5 Defective indoor controller
board
1 Contact failure at transmission
wire of remote controller
2 All remote controllers are set
as “sub” remote controller. In
this case, E0 is displayed on
remote controller, and E4 is
displayed at LED (LED1, LED2)
on the outdoor controller circuit
board.
3 Miswiring of remote controller
4 Defective transmitting receiving
circuit of remote controller
5 Defective transmitting receiving
circuit of indoor controller board
of refrigerant address “0”
6 Noise has entered into the
transmission wire of remote
controller.
1 2 remote controller are set as
“main.” (In case of 2 remote
controllers)
2 Remote controller is connected
with 2 indoor units or more.
3 Repetition of refrigerant
address
4 Defective transmitting receiving
circuit of remote controller
5 Defective transmitting receiving
circuit of indoor controller board
6 Noise has entered into trans-
mission wire of remote controller.
Countermeasure
1–3 Check resistance value of thermistor.
For characteristics, refer to (P1) above.
2 Check contact failure of connector (CN29)
on the indoor controller board. Refer to 10-7.
Turn the power on and check restart after
inserting connector again.
Operate in test run mode and check pipe
4
<condenser / evaporator> temperature with
outdoor controller circuit board. If pipe <condenser / evaporator> temperature is extremely low (in cooling mode) or high (in heating
mode), refrigerant circuit may have defect.
5 Operate in test run mode and check pipe
<condenser / evaporator> temperature with
outdoor control circuit board. If there is
exclusive difference with actual pipe
<condenser / evaporator> temperature
replace indoor controller board.
There is no abnormality if none of above
comes within the unit.
Turn the power off and on again to operate.
In case of checking pipe temperature
with outdoor controller circuit board,
be sure to connect A-control service
(
tool (PAC-SK52ST).
1 Check disconnection or looseness of indoor
unit or transmission wire of remote controller.
2 Set one of the remote controllers “main”
if there is no problem with the action above.
3 Check wiring of remote controller.
• Total wiring length: max. 500m
(Do not use cable o 3 or more.)
• The number of connecting indoor units:
max. 16 units
• The number of connecting remote controller: max. 2 units
When the above-mentioned problem 1~3 are not seen.4 Diagnose remote controllers.
a) When “RC OK” is displayed,
remote controllers have no problem.
Turn the power off, and on again to check.
If abnormality generates again, replace
indoor controller board.
b) When “RC NG” is displayed,
replace remote controller.
c) When “RC E3” is displayed,
d) When “ERC 00-06” is displayed,
[ c),d)→Noise may be causing abnormality. ]
* If the unit is not normal after replacing
indoor controller board in group control,
the indoor controller board of address “0”
may be abnormal.
1 Set a remote controller to main, and the
other to sub.
2 Remote controller is connected with only 1
indoor unit.
3 The address changes to a separate setting.
4~6 Diagnose remote controller.
a) When “RC OK” is displayed, remote con-
trollers have no problem.
Turn the power off, and on again to check.
When becoming abnormal again, replace
indoor controller board.
b)When “RC NG” is displayed, replace
remote controller.
c)When “RC E3” or “ERC 00-66” is displayed,
noise may be causing abnormality.
)
26
Error Code
E6
E7
Fb
E1
or
E2
Abnormal point and detection method
Indoor/outdoor unit communication
error (Signal receiving error)
1 Abnormal if indoor controller board
cannot receive any signal normally for 6
minutes after turning the power on.
2 Abnormal if indoor controller board
cannot receive any signal normally for 3
minutes.
3 Consider the unit as abnormal under
the following condition: When 2 or more
indoor units are connected to 1
outdoor unit, indoor controller board
cannot receive a signal for 3 minutes
from outdoor controller circuit board, a
signal which allows outdoor controller
circuit board to transmit signals.
Indoor/outdoor unit communication
error (Transmitting error)
Abnormal if “1” receiving is detected 30
times continuously though indoor controller
board has transmitted “0”.
Indoor controller board
Abnormal if data cannot be read normally
from the nonvolatile memory of the indoor
controller board.
Remote controller control board
1 Abnormal if data cannot be read nor-
mally from the nonvolatile memory of the
remote controller control board.
(Error code: E1)
2 Abnormal if the clock function of remote
controller cannot be operated normally.
(Error code: E2)
Cause
1 Contact failure, short circuit or,
miswiring (converse wiring) of
indoor/outdoor unit connecting
wire
circuit board. (Connect A-control service
tool, PAC-SK52ST.)
For EA-EC item, refer to outdoor unit service
manual.
1 Check disconnection or looseness of indoor/
outdoor unit connecting wire of indoor unit or
outdoor unit.
Check all the units in case of twin indoor
unit system.
2-4 Turn the power off, and on again to check.
If abnormality generates again, replace
indoor controller board or outdoor
controller circuit board.
* Other indoor controller board may have
defect in case of twin indoor unit system.
1-3 Turn the power off, and on again to check.
If abnormality generates again, replace
indoor controller board.
1 Replace indoor controller board.
Countermeasure
PA
(2502)
(2500)
Forced compressor stop
(due to water leakage abnormality)
When the intake temperature subtracted
1
with liquid pipe temperature is less than
-10:(14˚F), drain sensor
er it is soaked in the water or not at the
interval of 90 seconds.
start operating when the drain sensor detects
to be soaked in the water.)
2 The unit has a water leakage abnormality
when the following conditions, a and b,
are satisfied while the above-mentioned
detection is performed.
a) The drain sensor detects to be
soaked in the water 10 times in a row.
b) The intake temperature subtracted
with liquid pipe temperature is detected to be less than -10:(14˚F) for a
total of 30 minutes. (When the drain
sensor detects to be NOT soaked in
the water, the detection record of a
and b will be cleared.)
3 The drain sensor detection is performed
in operations other than cooling. (When
the unit stops operating, during heating
or fan operation, when the unit stops
because of some abnormality)
*Once the water leakage abnormality is
detected, abnormality state will not be
released until the main power is reset.
detects
wheth-
(Drain pump will
1 Drain pump trouble
2 Drain defective
· Drain pump clogging
· Drain pipe clogging
3 Open circuit of drain sensor
side heater
4 Contact failure of drain sensor
connector
5 Dew condensation on drain
sensor
· Drain water trikles along lead
wire.
· Drain water waving due to filter
clogging
6 Extension piping connection
difference at twin system
7 Miswiring of indoor/ outdoor
connecting at twin system
8 Room temperature thermistor /
liquid pipe temperature thermis tor detection is defective.
1 Check the drain pump.
2 Check whether water can be drained.
3 Check the resistance of the drain sensor.
4 Check the connector contact failure.
5 Check the drain sensor leadwire mounted.
Check the filter clogging.
6 Check the piping connection.
7 Check the indoor/ outdoor connecting wires.
8 Check the room temperature display of
remote controller.
Check the indoor liquid pipe temperature
display of outdoor controller board.
27
10-4. TROUBLESHOOTING BY INFERIOR PHENOMENA
Note: Refer to the manual of outdoor unit for the detail of remote controller.
Phenomena
(1)LED2 on indoor controller board
is off.
• When LED1 on indoor controller board is also off.
1 Power supply of rated voltage is not supplied to out-
door unit.
2 Defective outdoor controller circuit board
3 Power supply of 208/230V is not supplied to indoor
unit.
4 Defective indoor power board
5 Defective indoor controller board
(For the separate indoor/outdoor unit power sup-
ply system)
1 Power supply of 208/230V AC is not supplied to
indoor unit.
2 The connectors of the optional replacement kit are
not used.
3 Defective indoor controller board
4 Defective indoor power board
Cause
Countermeasure
1 Check the voltage of outdoor power
supply terminal block (L1,L2).
• When AC 208/230V is not detected,
check the power wiring to outdoor unit
and the breaker.
• When AC 208/230V is detected,
check 2 (below).
2 Check the voltage between outdoor
terminal block S1 and S2.
• When AC 208/230V is not detected,
—check the fuse on outdoor controller
circuit board.
—check the wiring connection.
• When AC 208/230V is detected,
check 3 (below).
3 Check the voltage between indoor terminal
block S1 and S2.
• When AC 208/230V is not detected,
check indoor/outdoor unit connecting
wire for miswiring.
• When AC 208/230V is detected,
check 4 (below).
4 Check voltage output from CN2S on indoor
power board (DC13.1V). Refer to 10-7-1.
• When no voltage is output, check the
wiring connection.
• When output voltage is between
DC12.5V and DC13.7V, check 5
(below).
5 Check the wiring connection between
indoor controller board and indoor power
board. Check the fuse on indoor controller
board. If no problems are found, indoor
controller board is defective.
1 Check the voltage of indoor power supply
terminal block (L1,L2).
• When AC208/230V is not detected,
check the power supply wiring.
• When AC208/230V is detected, check
2 (below).
2 Check that there is no problem in the
method of connecting the connectors.
• When there are problems in the method
of connecting the connectors, connect
the connector correctly referring to installation manual of an optional kit.
• When there is no problem in the meth-
od of connecting the connectors, check
3 (below).
3 Check voltage output from CNDK on
indoor controller board.
• When AC208/230V is not detected,
—check the fuse on indoor controller board.
—check the wiring connection between
indoor power supply terminal block and
CND on indoor controller board.
• When AC208/230V is detected, check
4 (below).
4 Check voltage output from CN2S on
indoor power board.
• When no voltage output, check the
wiring connection between CNDK on
indoor controller board and CNSK on
indoor power board.
If no problem are found, indoor power
board is defective.
• When DC12.5~13.7V is detected, check
the wiring connection between CN2S
on indoor power board and CN2D on
indoor power board.
If no problem are found, indoor control-
ler board is defective.
28
Phenomena
(1)LED2 on indoor controller board
is off.
(2)LED2 on indoor controller board
is blinking.
(3)Upward/downward vane
performance failure
Note: Refer to the manual of the outdoor unit for the detail of remote controller.
Cause
• When LED1 on indoor controller board is lit.
1 Mis-setting of refrigerant address for outdoor unit
(There is no unit corresponding to refrigerant
address “0”.)
•
When LED1 on indoor controller board is also blinking.
Connection failure of indoor/outdoor unit connecting wire
• When LED1 is lit.
1 Miswiring of remote controller wires
Under indoor unit system, 2 indoor
together.
2 Refrigerant address for outdoor unit is wrong or not
set.
Under grouping control system, there are some units
whose refrigerant address is 0.
3 Shortcut of remote controller wires
4 Defective remote controller
1 The vane is not downward during defrosting and heat
preparation and when the thermostat is OFF in HEAT
mode. (Working of COOL protection function)
2 Vane motor does not rotate.
• Defective vane motor
• Breaking of wire or connection failure of connector
• Up/downward vane setting is “No vanes”.
3 Upward/downward vane does not work.
• The vane is set to fixed position.
units are wired
Countermeasure
1 Check again the setting of refrigerant
address for outdoor unit.
Set the refrigerant address to “0”.
(For grouping control system under
which 2 or more outdoor units are
connected, set one of the units to “0”.)
Set refrigerant address using SW1 (3-6)
on outdoor controller circuit board.
Check indoor/outdoor unit connecting wire
for connection failure.
1 Check the connection of remote con troller wires in case of twin indoor unit
system. When 2 or more indoor units are
wired in one refrigerant system, connect
remote controller wires to one of those
units.
2 Check the setting of refrigerant address
in case of grouping control system.
If there are some units whose refrigerant
addresses are 0 in one group, set one of
the units to 0 using SW1 (3-6) on outdoor
controller circuit board
34 Remove remote controller wires and
check LED2 on indoor controller board.
• When LED2 is blinking, check the shortcut of remote controller wires.
• When LED2 is lit, connect remote
controller wires again and:
if LED2 is blinking, remote controller
is defective; if LED2 is lit, connection
failure of remote controller terminal
block etc. has returned to normal.
1 Normal operation (The vane is set to
horizontal regardless of remote control.)
2 Check 2 (left).
• Check the vane motor. (Refer to “How
to check the parts”.)
• Check for breaking of wire or connection failure of connector.
• Check “Up/down vane setting”. (Unit
function selection by remote controller).
3 Normal operation (Each connector on
vane motor side is disconnected.)
.
(4)Receiver for wireless remote
controller
1 Weak batteries of wireless remote controller
2 Contact failure of connector (CNB) on wireless
remote controller board(Insert failure)
3 Contact failure of connector (CN90) on indoor con-
troller board(Insert failure)
4 Contact failure of connector between wireless remote
controller board and indoor controller board
29
1 Replace batteries of the wireless remote
controller.
2~4
Check contact failure of each connector. If no problems are found in connector,
replace indoor controller board.
When the same trouble occurs even if
indoor controller board is replaced,
replace wireless remote controller
board.
10-5. EMERGENCY OPERATION
10-5-1. When wireless remote controller has troubles or its battery is exhausted
1. Emergency operation is available in such a case using emergency operation switch equipped next to the receiver of indoor
unit.
2. To start operation
• Cooling Operation·······Press (Cooling) switch.
• Heating Operation·······Press (Heating) switch.
wWhen the unit starts operating, the operation lamp is lit.
Emergency operation switch (cooling)
Emergency operation switch (heating)
Receiver
Operation lamp
+Emergency operation will be performed as follows.
Mode
Set temperature
Fan speed
Airflow direction
3. To stop operation
• Press either emergency operation switch (cooling/heating).
Cooling
24, 75F
High
Horizontal (30deg)
Heating
24, 75F
High
Downward (70deg)
10-5-2. When wired remote controller or indoor unit microcomputer has troubles
1. If other defects are not found when trouble occurs, emergency operation starts as the indoor controller board switch (SWE)
is set to ON.
During the emergency operation the indoor unit is as follows;
· Indoor fan high speed operation
2. For emergency operation of cooling or heating
When emergency operation for COOL or HEAT, setting of the switch (SWE) in the indoor controller board and outdoor unit
emergency operation are necessary.
3. Check items and notices as the emergency operation
(1) Emergency operation cannot be used as follows;
• When the outdoor unit is something wrong
• When the indoor fan is something wrong
• When drain over flow protection operation is detected during self-diagnosis (Error code : P5)
(2) Emergency operation will be serial operation by the power supply ON/OFF.
ON/OFF or temperature, etc. adjustment is not operated by the remote controller.
(3) Do not operate for a long time as cold air is blown when the outdoor unit starts defrosting operation during heat emer-
gency operation.
(4) Cool emergency operation must be within 10 hours. Otherwise, heat exchanger of indoor unit may get frosted.
(5) After completing the emergency operation, return the switch setting, etc. in former state.
(6) Since vane does not work at emergency operation, position the vane slowly by hand.
30
10-6. HOW TO CHECK THE PARTS
PKA-A12/ 18GA PKA-A24/ 30/ 36FA PKA-A12/ 18GAL PKA-A24/ 30/ 36FAL
PKA-A12/ 18GA
CNSK
Connect to the indoor controller board
(CNDK)
between 1 to 3 208/230V AC
33
10-8. FUNCTIONS OF DIP SWITCH AND JUMPER WIRE
Each function is controlled by the dip switch and the jumper wire on control P.C. board.
SW1 and SW2 are equipped only for service parts.
Model setting and capacity setting are memorized in the nonvolatile memory of the control P.C. board of
the unit.
(Marks in the table below) Jumper wire ( : Short : Open)
Jumper wire
SW1
SW2
J41
J42
Functions
Model
settings
Capacity
settings
Pair number
setting with
wireless
remote
controller
Setting by the dip switch and jumper wire
For service board
PKA-A12,18GA(1)(2)
PKA-A12,18GAL(1)
PKA-A24,30,36FA(1)
PKA-A24,30,36FAL(1)
MODELS
PKA-A12GA
PKA-A12GAL
PKA-A18GA
PKA-A18GAL
PKA-A24FA
PKA-A24FAL
PKA-A30FA
PKA-A30FAL
PKA-A36FA
PKA-A36FAL
Wireless remote
controller setting
0
1
2
3 ~ 9
(1)
(2)
(1)
(1)
(2)
(1)
(1)
(2)
(1)
(2)
(1)
(2)
(1)
(2)
(1)
(2)
(1)
(2)
(2)
(2)
(2)
(2)
(2)
1 2 3 4 5
1 2 3 4 5
Service board
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
Control PCB setting
J41J42
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
Remarks
<Initial setting>
Wireless remote controller: 0
Control PCB: (for both J41 and J42)
Four pair number settings are supported.
The pair number settings of the wireless remote
controller and indoor control PCB (J41/J42) are
given in the table on the left.
(' ' in the table indicates the jumper wire is disconnected.)
JP1
Unit type
setting
Indoor
JP3
controller
board type
setting
Model
Without TH5
With TH5
Indoor controller board type
For product
Service parts
JP1
There is no jumper (JP1) because these models
have the cond./eva. temperature thermistor (TH5).
(1) Rotation function(and Back-up function)
Outline of functions
· Operating the unit of main and sub alternately according to the interval setting. (Rotation function)
wThe setting of main/sub unit depends on the refrigerant address.(The setting of dip switch on the outdoor unit)
Refrigerant address"00" Main unit
Refrigerant address"01" Sub unit
· If an error occurrs to one unit, the other unit starts.(Back-up function)
System constraint
· This function is available only by the grouping control system(INDOOR UNIT : OUTDOOR UNIT=1:1) of 2 refrigerant
group.(Refer to Fig 1)
· It is necessary to connect remote controller crossover wiring to between units(Wireless remote controller is unusable) and
to assign refrigerant address to each unit.(Dip switch on the outdoor unit…Refrigerant address 00/01)
Operation pattern
[Back-up function only]··· Request code number "312"
Start operation
Main
unit
IC-1
Sub
unit
IC-2
[Rotation function] & [Back-up function]··· Request code number "313~318"
Start operation
Main
unit
IC-1
Sub
unit
IC-2
(Ex:When the request code number is "313", each unit operates alternately in daily cycle.)
Run
Stop
Main SubMain SubMain Sub
Run
Stop
1~28 days1~28 days
Error occurred on main unit
Main Sub
Abnormal condition
Run
Error occurred on main unit
Stop
Run
Run
StopRun
Abnormal condition
Fig 1
OC: Outdoor unit
IC: Indoor unit
RC: Wired remote controller
Refrigerant address
"00"
Main
unit
2
(2) 2nd stage cut-in function
Outline of functions
· Quantity of operating units is controlled according to the room temperature and set point.
· When room temperature becomes more than set point, standby unit starts.(2 units running )
· When room temperature falls below set point -4:(7.5°F), standby unit stops.(1 unit running)
System constraint
· This function is available only in rotation operation(or back-up) and cooling mode.
OC-1
IC-1
RC
3(2)
Refrigerant address
"01"
OC-2
Sub
3(2)
unit
IC-2
2
[2nd stage cut-in function]··· Request code number "322~324"
Start operationSub unit start operation
Main
unit
IC-1
Sub
unit
IC-2
Room temp. Set point
Run
StopStopRun
Room temp. < Set point -4(7.5°F)
Sub unit stop
35
11-1-2.How to perform the operation of rotation function(Back-up funcion, 2nd stage cut-in function)
Set by wired remote controller.(Maintenance monitor)
NOTE
It is necessary to set the same content to both main unit and sub unit.
Every time indoor controller board is replaced for servicing, it is necessary to set each function.
Rotation and Back-up OFF (Normal group control operation)
Back-up function only
Rotation ON (Alternating interval = 1day) and back-up function
Rotation ON (Alternating interval = 3days) and back-up function
Rotation ON (Alternating interval = 5days) and back-up function
Rotation ON (Alternating interval = 7days) and back-up function
Rotation ON (Alternating interval = 14days) and back-up function
Rotation ON (Alternating interval = 28days) and back-up function
Initial
setting
2nd stage cut-in setting
Setting No.
(Request code)
No.1
(320)
No.2
(321)
No.3
(322)
No.4
(323)
No.5
(324)
Setting contents
Monitoring the request code of current setting.
Cut-in function OFF
Cut-in function ON (Set point = Set temp. +4(7.2°F))
Cut-in function ON (Set point = Set temp. +6(10.8°F))
Cut-in function ON (Set point = Set temp. +8(14.4°F))
Initial
setting
36
(2) Setting method of each function by wired remote controller
B: Refrigerant address
C: Data display area
D: Request code display area
1. Stop running the air-conditioner(
2. Press the button (
TEST
).
) for 3 seconds so that [Maintenance mode] appears on the screen (at ).
After a while, [00] appears in the refrigerant address number display area.(at
3. Press the button (
CHECK
) for 3 seconds to switch to [Maintenance monitor].
)
Note) It is not possible to switch to [Maintenance monitor] during data request in maintenance mode
(i.e., while“----” is blinking) since no buttons are operative.
[----] appears on the screen (at
(The display (at
) now allows you to set a request code No.)
) when [Maintenance monitor] is activated.
4. Press the [TEMP ( and )] buttons (
[Screen]
5. Press the [CLOCK ( and )] buttons (
) to select the desired refrigerant address.
) to set the desired request code No.(“311~318”, “321~324”,
“331~335”)
6. Press the button (
FILTER
If the above operations are set correctly, request code number will appear in data display area.(at
[Example) When the request code number is "311", [311] appears on the screen.(at
) to perform function setting.
)
)]
[Refererence]
You can check the request code number of current setting by setting the request code number (“310”, “320” or “330”) and
press the button.(
FILTER
[Example) When the current setting is "Setting No.2(Request code 311)", [311] appears on the screen.(at
7. To return to normal mode, press the button (
)
)]
ON/OFF
).
11-2. BACK-UP HEATING FUNCTION(CN24)
11-2-1. Operation
Outline of functions
The back-up heater signal is sent out according to the temperature
difference between indoor room temperature and set temperature.
This function is available only in heating operation.
11-2-2. How to connect
When connecting to the connector CN24 of the indoor unit, use
PAC-SE56RA-E(optional parts).
1. REMOVING THE LOWER SIDE OF THE INDOOR UNIT
FROM THE INSTALLATION PLATE.
(1) Remove the left / right corner box of the indoor unit.
(2) Hold and pull down the lower and both ends of the indoor
unit, and remove the ▼ section from the square hole.
(Refer to the figure 2.1)
Or remove the front panel and push the ▼ section down
by using hexagonal wrench ,etc. from the front side.
(Refer to the figure 2.2).
(3) Unhook the top of the indoor unit from the back plate catch.
Figure 2.2
Down
Square hole
Up
Figure 1
Figure 2.1
Square hole
Hook
Hook
2. REMOVING THE FRONT PANEL.
(1) Open the front grille.
(2) Remove the terminal block cover with a screw.
(3) Remove the 3 screw caps then remove the 3 set screws.
(4) After removing the lower side of the front panel a little,
remove it as pulling toward upper.
3. REMOVING THE INDOOR CONTROLLER BOARD.
(1) Remove the terminal block cover.
(2) Remove the front panel. (see the photo 1)
(3) Remove the electrical parts box(2 screws).
(4) Remove the electrical parts box cover(1 screw).
(5) Disconnect the connector on the controller board and
remove the controller board by pulling up the hook of the
controller case.
wFor smooth works, hang the side hooks of the electrical
parts box on the hook of the motor cover.
(see the photo 3)
Figure 3
Terminal block
cover
Photo 1
Front
panel
Photo 2
Motor cover
Electrical parts
box hook w
Photo 3
Front grille
Set screw
Electrical parts
box
38
Hook
Control board
Controller case
Electrical parts box
OPERATION PROCEDURE
PHOTOS & ILLUSTRATION
4. REMOVING THE POWER BOARD
(1) Remove the front panel. (see the photo 1)
(2) Remove the electrical parts box(2 screws). (see the photo 2)
(3) Disconnect the whole connector in the control board.
(4) After lifting the controller case with pressing its convex
section, remove the controller case and the control board
simultaneously. (see the photo 3)
(5) Disconnect the connector in the power board.
(6) Remove the power board.
5. REMOVING THE VANE MOTOR
(1) Disconnect the connector CN6V on the indoor controller
board.
(2) Remove the 2 screws of the vane motor, disconnect the
lead wire and remove the vane motor from the shaft.
6. REMOVING THE THERMISTOR
(1) Removing the room temperature thermistor TH1.
1Disconnect the connector CN20<red> on the indoor
controller board.
2Remove the room temperature thermistor from the holder.
(2) Removing the pipe temperature thermistor TH2.
1Disconnect the connector CN21<white> on the controller
board.
2Remove the pipe temperature thermistor set to the pipe.
(3) Removing the indoor coil temperature thermistor TH5.
1Disconnect the connector CN29<black> on the indoor con-
troller board.
2Remove the gas pipe thermistor set to the pipe.
Photo 4
Photo 5
Nozzle
assemble
Vane motor
Photo 6
Pipe
temperature
thermistor
(TH2)
Room
temperature
thermistor
(TH1)
Power board
Electrical
parts box
Set screws
Lead wire
Condenser
/evaporator
temperature
thermistor
(TH5)
Electrical
parts box
7. REMOVING THE NOZZLE ASSEMBLE
(1) Disconnect the connector CN6V on the controller board.
(2) Disconnect the lead wire of the vane motor.
(3) Remove the corner cover.
(4) Pull the drain hose out from the nozzle assembly.
(5) Unhook the hook of the lower nozzle assembly and
pull the nozzle assembly toward you, then remove the
nozzle assembly by sliding it down.
8. REMOVING THE ELECTRICAL PARTS BOX
(1) Remove the terminal block cover.
(2) Disconnect the connector <yellow> of the wireless remote
controller board.
(3) Remove the front panel. (see the photo 1)
(4) Disconnect the vane motor connector.
(5) Disconnect the fan motor connector from the fan motor.
(6) Disconnect the connector <yellow> of the heater. (only PKH).
(7) Remove the liquid(TH2) / gas(TH5) pipe thermistors. (see
the photo 6)
(8) Remove the electrical parts box (2screws).
39
Photo 7
Nozzle assemble
Photo 8
Pipe
temperature
thermistor
Hook
Drain hose
Corner cover
Fan motor connector
Vane motor
connector
Electrical
parts box
OPERATION PROCEDUREPHOTOS & ILLUSTRATION
9. REMOVING THE FAN MOTOR
(1) Remove the terminal block cover.
(2) Disconnect the connector <yellow> of the wireless remote
controller board.
(3) Remove the front panel. (see the photo 1)
(4) Remove the electrical parts box. (see the photo 8)
(5) Remove the nozzle assemble. (see the photo 7)
(6) Remove the fan motor leg fixing 3 screws.
(7) Unscrew the set screws by using hexagonal wrench and
remove it by sliding the fan motor to right.
(8) Remove the 4 screws and remove the motor cover from the
fan motor leg.
10. REMOVING THE LINE FLOW FAN
(1) Remove the terminal block cover.
(2) Remove the front panel. (see the photo 1)
(3) Remove the electrical parts box. (see the photo 8)
(4) Remove the nozzle assemble. (see the photo 7)
(5) Remove the fan motor. (see the photo 9)
(6) Remove the pipe fixture with 2 screws. (see the photo12)
(7) Remove the left / right screws of the heat exchanger and
pull the left-hand side up.
(8) Remove the 2 screws by sliding it toward you remove the
fixture(fixing bearing).
w w When resetting the fan to the fan motor. Locate and fix the shaft after installing the fan.
11. REMOVING THE HEAT EXCHANGER
(1) Remove the terminal block cover.
(2) Disconnect the connector <yellow> of the wireless remote
(3) Remove the front panel. (see the photo 1)
(4) Remove the electrical parts box. (see the photo 8)
(5) Remove the corner box.
(6) Remove the nozzle assemble. (see the photo 7)
(7) Remove the 2 screws and the pipe fixture.
(8) Remove the 2 screws and heat exchanger.
12. REMOVING THE SIGNAL RECEIVING P.C. BOARD
FOR (PKA-A12GAL(1), PKA-A18GAL(1))
(1) Remove the terminal block cover.
(2) Disconnect the connector <yellow> for the wireless remote
controller.
(3) Remove the front panel. (see the photo 1)
(4) Remove the 2 screws and signal receiving P.C. board cover.
(5) Remove the signal receiving P.C. board.
The fan motor is removable first,when the fan removing is hard.
1. Removing the lower side of the indoor unit from the
installation plate
(1) Remove the 2 screws.
Hang the indoor unit hangers to the catches on the instal-
lation plate.
Metal fixture
Screws
Figure 1
Hanger of indoor unit
Catch of installation plate
2. Removing the right side panel
(1) Remove the 2 screws of the right side panel:one on the
bottom and the other on the upper right-hand side.
(2) Disconnect the connector from the adaptor case.
(3) Sliding the right side panel to the right, pull it out toward
you.
3. Removing the indoor controller board
(1) Remove the right side panel.
(2) Remove the screw of the electrical parts box cover, and
remove the cover.
(3) Disconnect the connectors on the indoor controller board.
(4) To unhook the catches on the right-hand side of the indoor
controller board, pull the left-hand side toward you and lift
up the cover to the right. Then the indoor controller board
can be removed.
4. Removing the electrical parts box
(1) Remove the right side panel.
(2) Remove the screw of the electrical parts box cover, and
remove the cover.
(3) Remove the room temperature thermistor and the condens-
er / evaporator temperature thermistor.
(4) Disconnect the vane motor connector on the indoor control-
ler board.
(5) Remove the 2 screws of the electrical parts box.
(6) Disconnect the connector of the heater lead wire
connector.
(7) Disconnect the connector of the fan motor lead wire.
(8) Remove the electrical parts box.
Figure 2
Terminal cover
Electrical parts box cover
Photo 1
Indoor controller
board
Photo 2
Room temperature
thermistor
Connector
Indoor controller
board
Right side pan
Connector
Electrical parts
box cover
Catches
Condenser/ evaporator
temperature thermistor
Screws
Electrical parts
box
41
OPERATING PROCEDUREPHOTOS&ILLUSTRATION
(9) Remove the screws of the indoor controller board case,
and pull out the indoor controller board case.
Then the indoor power board, the fan motor capacitor
and the heater relay can be serviced.
5. Removing the vane motor
(1) Remove the right side panel.
(2) Remove the screw of the electrical parts box cover, and
remove the cover.
(3) Remove the 2 screws of the vane motor, and remove the
motor from the shaft.
(4) Disconnect the vane motor connector on the indoor control-
ler board.
Photo 3
Capacitor
Indoor controller
board case
Photo 4
Vane motor
Relay
Indoor
power board
Electrical parts box
Screws
Indoor controller board
6. Removing the intake grilles
(1) Remove the right side panel.
(2) To remove the left side panel, remove the screw on the bot-
tom and the screw on the upper left-hand side. (See Figure
3.)
1. Press up this side of the left side panel to unhook the
catch on the panel from the catch on the unit.
2. Slide the left side panel to the left to remove the panel.
Note: Fix the unit to the metal fixture securely.
(3) Remove the air filters.
(4) Hold and press the centre cover to remove.
(5) Remove the screws of the grills.
(6) Pull the lower side of the grille toward you and slide the
upper side to the right to remove the grilles.
7. Removing the drain pan
(1) Remove the left and right side panels.
(2) Remove the grilles.
(3) Remove the electrical parts box cover.
(4) Loosen the drain hose band to remove.
(5) Remove the 3 screws of the drain pan, and slide the drain
pan toward you to remove.
Figure 3
Photo 5
Left side panel
Photo 6
Catch on the left side panel
Catch on
the unit
Slide to the
right
Screws for grills
Drain pan
Grills
Drain hose
band
Screws
Drain hose
42
OPERATING PROCEDUREPHOTOS
8. Removing the line flow fan and the fan motor
(1) Remove the left and right side panels.
(2) Remove the grills.
(3) Remove the electrical parts box.
(4) Remove the drain pan.
(5) Loosen the screw that fixes the line flow fan to the fan
motor. (See Photo 7. )
(6) Remove the 4 screws of the motor fixture, and remove the
fan motor and the motor fixture at a time (See Photo 8.)
(7) Remove the screws of the left and right motor supports,
and remove the motor supports and the fan motor. (See
Photo 9.)
(8) Remove the 2 screws on the left and right sides of the heat
exchanger, and pull the bearing support toward you. (See
Photo 11.)
(9) Remove the screw of the centre support, and remove the
support. (See Photo 10. )
(10)
Pull the left-hand side of the heat exchanger toward you,
and remove the line flow fan.
Photo 11
Heat exchanger
Bearing support
Photo 7
Photo 8
Fan motor
Photo 9
Screw
Motor support
Line flow fan
Fan motor
Screw
Fan motor
Screw
Motor fixture
Screw
Lineflow fan
Photo 10
Photo 12
Heat exchanger
Line flow fans
ScrewCentre support
Heater element
Motor
support
Heater fixing screws
43
13PARTS LIST (non-RoHS compliant)
ELECTRICAL PARTS
PKA-A12GA PKA-A12GAL
PKA-A18GA PKA-A18GAL
1
4
3
5
2
6
9
10
No.
10
11
12
13
14
15
16
17
Parts No.Parts Name
1
T7W H28 480
2
R01 E22 114
3
R01 07Y 102
4
R01 005 103
5
R01 07Y 106
6
T7W A00 675
7
R01 07Y 524
8
R01 07Y 527
9
R01 07Y 530
R01 09Y 038
R01 07Y 038
R01 07Y 059
R01 E04 223
R01 E03 317
R01 07Y 135
R01 07Y 105
T7W E23 762
12
7
8
11
10
13
Specifications
HEAT EXCHANGER
LINE FLOW FAN
BEARING MOUNT
SLEEVE BEARING
BEARING SUPPORT
FAN GUARD
DRAIN PLUG
DRAIN HOSE
NOZZLE
GUIDE VANE
GUIDE VANE
ARM
VANE MOTOR
WIRERLESS ADAPTER CONTROLLER BOARD
MOTOR COVER
RUBBER MOUNT
FAN MOTOR
PM4V30-K
14
1
17
16
15
12,18GA
Q'ty/set
PKA-A
1
1
1
1
1
1
1
1
1
4
10
2
1
1
2
1
27
25
24
12, 18GAL
1
1
1
1
1
1
1
1
1
4
10
2
1
1
1
2
1
26
23
18
(Drawing No.)
20
19
Remarks
22
21
Wiring
Diagram
Symbol
MV
W.B
MF
Recommended
Q'ty
Continued to the next page
44
From the previous page
No.
18
19
20
21
22
23
24
25
26
27
Parts No.Parts Name
T7W E11 716
R01 E13 246
T7W E11 255
T7W E46 310
T7W E24 313
R01 556 246
R01 E58 202
T7W E05 202
R01 E02 202
T7W E06 130
Specifications
TERMINAL BLOCK
TERMINAL BLOCK
CAPACITOR
3P(L1,L2,GR)
3P(S1, S2, S3)
2.0 × 440V
INDOOR CONTROLLER BOARD
POWER BOARD
TERMINAL BLOCK
2P(1,2)
CONDENSER / EVAPORATOR TEMPERATURE THERMISTOR
ROOM TEMPERATURE THERMISTOR
PIPE TEMPERATURE THERMISTOR
MOTOR SUPPORT
Q'ty/set
PKA-A
12, 18GA 12, 18GAL
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Remarks
(Drawing No.)
Wiring
Diagram
Symbol
TB2
TB4
C
I.B
P. B
TB5
TH5
TH1
TH2
Recommended
Q'ty
45
ELECTRICAL PARTS
PKA-A24FA PKA-A30FA PKA-A24FAL PKA-A30FAL
26
25
1
2
23
24
3
4
22
20
21
5
19
7
18617
14
15
13
16
9
8
10
11
12
No.
1
2
3
4
5
6
7
8
9
10
11
12
Part No.
R01 Z61 102
R01 E23 114
T7W H25 480
T7W H26 480
T7W E13 529
R01 12G 621
R01 12G 063
R01 12G 002
R01 KV5 527
R01 E02 223
R01 E03 317
T7W E03 255
T7W E46 310
BEARING MOUNT
LEFT LINEFLOW FAN
HEAT EXCHANGER
HEAT EXCHANGER
DRAIN PAN
CENTER COVER
JOINT SHAFT
AUTO VANE
DRAIN HOSE
VANE MOTOR
WIRELESS ADAPTER CONTROLLER BOARD
CAPACITOR
INDOOR CONTROLLER BOARD
Part Name
Specification
2.5 440V
24FA 30FA
1
1
1
1
1
1
2
1
1
1
1
46
Q'ty/set
PKA-A
24FAL30FAL
1
1
1
1
1
1
1
1
1
1
1
1
2
2
1
1
1
1
1
1
1
1
1
(Drawing No.)
1
1
1
1
1
1
2
1
1
1
1
1
Remarks
Continued to the next page
Wiring
Diagram
Symbol
MV
W.B
C
I.B
Recom-
mended
Q'ty
From the previous page
No.
13
14
15
16
17
18
19
20
21
22
23
24
25
26
Part No.
T7W E24 313
R01 556 246
R01 E13 246
T7W E11 716
T7W E12 202
R01 E34 202
R01 E02 202
T7W B00 762
R01 12G 105
R01 E04 115
R01 KV5 102
R01 12G 103
T7W B02 675
R01 005 103
Part Name
INDOOR POWER BOARD
TERMINAL BLOCK
TERMINAL BLOCK
TERMINAL BLOCK
ROOM TEMPERATURE THERMISTOR
CONDENSER / EVAPORATOR
TEMPERATURE THERMISTOR
PIPE TEMPERATURE THERMISTOR
FAN MOTOR
RUBBER MOUNT
RIGHT LINEFLOW FAN
BEARING MOUNT
SLEEVE BEARING
FAN GUARD
SLEEVE BEARING
Specification
2P(1, 2)
3P(S1, S2, S3)
3P(L1, L2, GR)
PN4N45-K
24FA
1
1
1
1
1
1
1
1
2
1
1
1
2
1
Q'ty/set
PKA-A
30FA
1
1
1
1
1
1
1
1
2
1
1
1
2
1
24FAL
1
1
1
1
1
1
1
2
1
1
1
2
1
30FAL
1
1
1
1
1
1
1
2
1
1
1
2
1
Remarks
(Drawing No.)
Wiring
Diagram
Symbol
P. B
TB5
TB4
TB2
TH1
TH5
TH2
MF
Recom-
mended
Q'ty
47
ELECTRICAL PARTS
PKA-A36FA PKA-A36FAL
26
1
25
2
23
24
3
4
25
22
20
21
15
14
13
5
6
19
16
18
10
17
11129
7
8
No.
1
2
3
4
5
6
7
8
9
10
11
12
Part No.
R01 Z61 102
R01 16G 114
T7W H27 480
T7W E14 529
R01 12G 621
R01 12G 063
R01 16G 002
R01 KV5 527
R01 E05 223
R01 E03 317
T7W E03 255
T7W E46 310
BEARING MOUNT
LEFT LINEFLOW FAN
HEAT EXCHANGER
DRAIN PAN
CENTER COVER
JOINT SHAFT
AUTO VANE
DRAIN HOSE
VANE MOTOR
WIRELESS ADAPTER CONTROLLER BOARD
CAPACITOR
INDOOR CONTROLLER BOARD
Part Name
Specification
2.5F 440V
48
Q'ty/set
PKA-A
36FA36FAL
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
2
1
1
1
1
1
Remarks
(Drawing No.)
Continued to the next page
Wiring
Diagram
Symbol
MV
W.B
C
I.B
Recom-
mended
Q'ty
From the previous page
No.
13
14
15
16
17
18
19
20
21
22
23
24
25
26
Part No.Part NameSpecification
T7W E24 313
R01 556 246
R01 E13 246
T7W E11 716
T7W E12 202
R01 E34 202
R01 E02 202
T7W B01 762
R01 16G 105
R01 16G 115
R01 KV5 102
R01 12G 103
T7W B03 675
R01 005 103
INDOOR POWER BOARD
TERMINAL BLOCK
TERMINAL BLOCK
TERMINAL BLOCK
ROOM TEMPERATURE THERMISTOR
CONDENSER / EVAPORATOR
TEMPERATURE THERMISTOR
PIPE TEMPERATURE THERMISTOR
FAN MOTOR
RUBBER MOUNT
RIGHT LINEFLOW FAN
BEARING MOUNT
SLEEVE BEARING
FAN GUARD
SLEEVE BEARING
2P(1, 2)
3P(S1, S2, S3)
3P(L1,L2,GR)
PN4N70-K
Q'ty/set
PKA-A
36FA36FAL
1
1
1
1
1
1
1
1
1
2
1
1
1
2
1
1
1
1
1
1
1
2
1
1
1
2
1
Remarks
(Drawing No.)
Wiring
Diagram
Symbol
P. B
TB5
TB4
TB2
TH1
TH5
TH2
MF
Recommended
Q'ty
49
STRUCTURAL PARTS
PKA-A12GA
PKA-A18GA
PKA-A12GAL
PKA-A18GAL
4
5
6
1
2
3
12
11
No.
10
12
13
14
15
16
Parts No.
R01 07Y 808
1
R01 09Y 658
2
R01 07Y 623
3
R01 E05 651
4
R01 07Y 096
5
R01 07Y 092
6
R01 07Y 691
7
R01 A16 500
8
R01 07Y 002
9
R01 24K 658
R01 07Y 658
11
R01 07Y 635
T7W E09 714
R01 E01 049
R01 E00 075
T7W E10 713
13
8
7
Parts NameSpecifications
BACK PLATE
CORNER COVER
UNDER COVER
FRONT PANEL
SCREW CAP
VANE SLEEVE
FRONT GRILLE
AIR FILTER
AUTO VANE
RECEIVING UNIT
CORNER COVER
BOX ASSEMBLY
WIRELESS REMOTE CONTROLLER
WIRELESS REMOTE CONTROLLER DOOR
WIRELESS REMOTE CONTROLLER HOLDER
WIRED REMOTE CONTROLLER
9
10
12, 18GA
1
1
1
1
3
1
1
2
1
1
1
1
Q'ty/set
PKA-A
12, 18GAL
14
15
Remarks
(Drawing No.)
1
1
1
1
3
1
1
2
1
1
1
1
1
1
1
16
TEMP.
Wiring
Diagram
Symbol
RU
R.B
ON/OFF
Recom-
mended
Q'ty
50
STRUCTURAL PARTS
PKA-A24FA PKA-A30FA
PKA-A24FAL PKA-A30FAL
13
12
1
1011
9
2
3
TEMP.
ON/OFF
5
7
8
4
Part number that is circled is not shown in the figure.
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
Part No.
R01 12G 662
R01 E01 812
R01 E00 811
R01 A17 500
R01 12G 691
R01 24K 658
R01 12G 661
T7W E05 661
T7W E10 713
R01 E00 075
R01 E01 049
T7W E08 714
R01 12G 808
R01 E01 641
R01 12G 523
LEFT SIDE PANEL
UNDER PLATE
NOSE
AIR FILTER
INTAKE GRILLE
RECEIVER
RIGHT SIDE PANEL
RIGHT SIDE PANEL
WIRED REMOTE CONTROLLER
WIRELESS REMOTE CONTROLLER HOLDER
WIRELESS REMOTE CONTROLLER DOOR
WIRELESS REMOTE CONTROLLER
BACK PLATE
TOP PLATE
DRAIN SOCKET
Part Name
Specifications
Q'ty/set
PKA-A
24, 30FA
1
1
1
4
2
1
1
1
1
1
6
24, 30FAL
1
1
1
4
2
1
1
1
1
1
1
1
1
Remarks
(Drawing No.)
Wiring
Diagram
Symbol
RU
R.B
Recommended
Q'ty
51
STRUCTURAL PARTS
PKA-A36FA PKA-A36FAL
1
13
12
14
2
3
4
Part number that is circled is not shown in the figure.
11
9
10
TEMP.
ON/OFF
5
6
7
8
Part No.
No.
R01 12G 662
1
R01 E00 812
2
R01 E01 811
3
R01 A17 500
4
R01 12G 691
5
R01 24K 658
6
R01 12G 661
7
T7W E05 661
T7W E10 713
8
R01 E00 075
9
R01 E01 049
10
T7W E08 714
11
R01 16G 808
12
R01 E00 641
13
R01 16G 692
14
R01 12G 523
15
Part Name
Specification
LEFT SIDE PANEL
UNDER PLATE
NOSE
AIR FILTER
INTAKE GRILLE
RECEIVER
RIGHT SIDE PANEL
RIGHT SIDE PANEL
WIRED REMOTE CONTROLLER
WIRELESS REMOTE CONTROLLER HOLDER
WIRELESS REMOTE CONTROLLER DOOR
WIRELESS REMOTE CONTROLLER
BACK PLATE
TOP PLATE
INTAKE GRILLE
DRAIN SOCKET
Q'ty/set
36FA
1
1
1
5
2
1
1
1
1
1
1
PKA-A
36FAL
1
1
1
5
2
1
1
1
1
1
1
1
1
1
Remarks
(Drawing No.)
Wiring
Diagram
Symbol
RU
R.B
Recom-
mended
Q'ty
52
14RoHS PARTS LIST
STRUCTURAL PARTS
PKA-A12GA
PKA-A18GA1 PKA-A18GA2
PKA-A12GAL1 PKA-A12GAL2
PKA-A18GAL1 PKA-A18GAL2
Part number that is circled is not shown in the figure.
9
1011
TEMP.
ON/OFF
5
7
8
6
No.
Part No.
Part Name
RoHS
R01 14G 662
G
1
R01 E02 812
G
2
R01 E00 811
G
3
R01 A17 500
G
4
R01 17G 691
G
5
R01 E18 658
G
6
R01 14G 661
G
7
T7W E18 661
G
T7W E14 713
G
8
R01 E00 075
G
9
R01 E03 049
G
10
T7W E08 714
G
11
R01 E03 808
G
12
R01 E19 641
G
13
R01 E02 523
G
14
LEFT SIDE PANEL
UNDER PLATE
NOSE
AIR FILTER
INTAKE GRILLE
RECEIVER
RIGHT SIDE PANEL
RIGHT SIDE PANEL
WIRED REMOTE CONTROLLER
WIRELESS REMOTE CONTROLLER HOLDER
WIRELESS REMOTE CONTROLLER DOOR
WIRELESS REMOTE CONTROLLER
BACK PLATE
TOP PLATE
DRAIN SOCKET
Specifications
54
Q'ty/set
PKA-A24/30
1/FA2
FAL1/FAL2
FA
1
1
1
4
2
1
1
1
1
1
1
1
1
4
2
1
1
1
1
1
1
1
1
Remarks
(Drawing No.)
Wiring
Diagram
Symbol
RU
R.B
Recom-
mended
Q'ty
STRUCTURAL PARTS
PKA-A36FA
1 PKA-A36FAL1 PKA-A36FA2 PKA-A36FAL2
13
12
1
14
2
3
4
Part number that is circled is not shown in the figure.
11
9
10
TEMP.
ON/OFF
5
6
7
8
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Part No.
RoHS
R01 14G 662
G
R01 E03 812
G
R01 E01 811
G
R01 A17 500
G
R01 17G 691
G
R01 E18 658
G
R01 14G 661
G
T7W E18 661
G
T7W E14 713
G
R01 E00 075
G
R01 E03 049
G
T7W E08 714
G
R01 E04 808
G
R01 E20 641
G
R01 18G 692
G
R01 E02 523
G
Part NameSpecification
FA
LEFT SIDE PANEL
UNDER PLATE
NOSE
AIR FILTER
INTAKE GRILLE
RECEIVER
RIGHT SIDE PANEL
RIGHT SIDE PANEL
WIRED REMOTE CONTROLLER
WIRELESS REMOTE CONTROLLER HOLDER
WIRELESS REMOTE CONTROLLER DOOR
WIRELESS REMOTE CONTROLLER
BACK PLATE
TOP PLATE
INTAKE GRILLE
DRAIN SOCKET
Q'ty/set
PKA-A36
1/FA2
FAL1/FAL2
1
1
1
5
2
1
1
1
1
1
1
1
1
1
5
2
1
1
1
1
1
1
1
1
1
Remarks
(Drawing No.)
Wiring
Diagram
Symbol
RU
R.B
Recommended
Q'ty
55
ELECTRICAL PARTS
PKA-A12GA
1 PKA-A12GAL1 PKA-A12GA2 PKA-A12GAL2
PKA-A18GA1 PKA-A18GAL1 PKA-A18GA2 PKA-A18GAL2
1
4
3
5
2
6
9
7
8
10
11
12
10
13
Part number that is circled is not shown in the figure.
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
Parts No.Parts NameSpecifications
RoHS
G
T7W H28 480
G
R01 E22 114
G
R01 08Y 102
G
R01 E04 103
G
R01 08Y 106
G
T7W A01 675
G
R01 08Y 524
G
R01 08Y 527
G
R01 08Y 530
G
R01 10Y 038
G
R01 08Y 038
G
R01 08Y 059
G
R01 E14 223
G
R01 E06 317
G
R01 08Y 135
G
R01 08Y 105
G
T7W E30 762
HEAT EXCHANGER
LINE FLOW FAN
BEARING MOUNT
SLEEVE BEARING
BEARING SUPPORT
FAN GUARD
DRAIN PLUG
DRAIN HOSE
NOZZLE
GUIDE VANE
GUIDE VANE
ARM
VANE MOTOR
WIRERLESS ADAPTER CONTROLLER BOARD
MOTOR COVER
RUBBER MOUNT
FAN MOTOR
14
PM4V30-K
1
17
16
15
GA1GA2
10
27
24
Q'ty/set
PKA-A12,18
GAL1GAL2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
4
4
4
10
10
2
2
2
1
1
1
1
1
1
1
2
2
2
1
1
1
25
26
23
18
(Drawing No.)
1
1
1
1
1
1
1
1
1
4
10
2
1
1
1
2
1
22
20
19
Remarks
Continued to the next page
21
Wiring
Diagram
Symbol
MV
W.B
MF
Recom-
mended
Q'ty
56
From the previous page
No.
18
19
20
21
22
23
24
25
26
27
28
Parts No.Parts Name
RoHS
T7W E41 716
G
R01 E18 246
G
T7W E17 255
G
T7W E56 310
G
T7W E70 310
G
T7W E35 313
G
R01 E21 246
G
T7W E46 716
G
R01 H11 202
G
R01 H08 202
G
T7W E05 202
G
R01 H05 202
G
T7W E10 130
G
R01 E06 239
G
TERMINAL BLOCK
TERMINAL BLOCK
CAPACITOR
INDOOR CONTROLLER BOARD
INDOOR CONTROLLER BOARD
POWER BOARD
TERMINAL BLOCK
TERMINAL BLOCK
CONDENSER/EVAPORATOR TEMPERATURE THERMISTOR
ROOM TEMPERATURE THERMISTOR
ROOM TEMPERATURE THERMISTOR
PIPE TEMPERATURE THERMISTOR
MOTOR SUPPORT
FUSE
Specifications
3P(L1, L2, GR)
3P(S1, S2, S3)
2.0 × 440V
2P(1,2)
2P(1,2)
6.3A 250V
Q'ty/set
PKA-A12,18
GA1 GAL1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
GA2 GAL2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Remarks
(Drawing No.)
Wiring
Diagram
Symbol
TB2
TB4
C
I.B
I.B
P. B
TB5
TB5
TH5
TH1
TH1
TH2
FUSE
Recommended
Q'ty
57
ELECTRICAL PARTS
PKA-A24FA
1 PKA-A30FA1 PKA-A24FAL1 PKA-A30FAL1
PKA-A24FA2 PKA-A30FA2 PKA-A24FAL2 PKA-A30FAL2
26
1
25
2
3
4
5
7
8
Part number that is circled is not shown in the figure.
No.
1
G
2
G
G
3
G
G
4
G
5
G
6
G
7
G
8
G
9
G
10
G
11
G
12
G
Part No.
RoHS
R01 Z61 102
R01 E23 114
T7W H25 480
T7W H26 480
T7W E24 529
R01 14G 621
R01 13G 063
R01 18G 002
R01 E04 527
R01 E15 223
R01 E06 317
T7W E16 255
T7W E56 310
T7W E70 310
Part Name
BEARING MOUNT
LEFT LINEFLOW FAN
HEAT EXCHANGER
HEAT EXCHANGER
DRAIN PAN
CENTER COVER
JOINT SHAFT
AUTO VANE
DRAIN HOSE
VANE MOTOR
WIRELESS ADAPTER CONTROLLER BOARD
CAPACITOR
INDOOR CONTROLLER BOARD
INDOOR CONTROLLER BOARD
23
24
22
9
Specification
2.5 440V
58
21
14
19
15
18617
16
10
Q'ty/set
PKA-A
24 30 24 30 24 30 24 30
FA
1 FA L1FA2FAL2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
2
2
2
2
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
13
11
12
Remarks
(Drawing No.)
1
1
1
1
1
1
2
1
1
1
1
1
Continued to the next page
Diagram
Symbol
Wiring
MV
W.B
C
I.B
I.B
20
Recom-
mended
Q'ty
From the previous page
No.
Part No.Part Name
RoHS
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
T7W E35 313
G
T7W E46 716
G
R01 E18 246
G
T7W E41 716
G
R01 H06 202
G
R01 H07 202
G
R01 H05 202
G
T7W B05 762
G
R01 12G 105
G
R01 E04 115
G
R01 KV5 102
G
R01 E03 103
G
T7W E15 675
G
R01 E04 103
G
R01 E06 239
G
INDOOR POWER BOARD
TERMINAL BLOCK
TERMINAL BLOCK
TERMINAL BLOCK
ROOM TEMPERATURE THERMISTOR
CONDENSER / EVAPORATOR
TEMPERATURE THERMISTOR
PIPE TEMPERATURE THERMISTOR
FAN MOTOR
RUBBER MOUNT
RIGHT LINEFLOW FAN
BEARING MOUNT
SLEEVE BEARING
FAN GUARD
SLEEVE BEARING
FUSE
Specification
2P(1, 2)
3P(S1, S2, S3)
3P(L1, L2, GR)
PN4N45-K
6.3A 250V
Q'ty/set
PKA-A
24 30 24 30 24 30 24 30
1FAL 1FA2FAL2
FA
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
1
1
1
1
1
1
2
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
1
1
1
1
1
1
2
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
2
1
1
1
1
1
1
1
1
1
2
2
2
1
1
1
1
1
1
Remarks
(Drawing No.)
1
1
1
1
1
1
2
1
1
1
2
1
1
Wiring
Diagram
Symbol
P. B
TB5
TB4
TB2
TH1
TH5
TH2
MF
FUSE
Recom-
mended
Q'ty
59
ELECTRICAL PARTS
PKA-A36FA
1
1 PKA-A36FAL1 PKA-A36FA2 PKA-A36FAL2
26
25
2
23
24
3
4
25
22
20
21
15
14
13
5
6
19
16
18
10
17
11129
7
8
Part number that is circled is not shown in the figure.
No.
G
1
G
2
G
3
G
4
G
5
G
6
G
7
G
8
G
9
G
10
G
11
G
12
G
Part No.
RoHS
R01 Z61 102
R01 19G 114
T7W H27 480
T7W E25 529
R01 14G 621
R01 13G 063
R01 19G 002
R01 E04 527
R01 E15 223
R01 E06 317
T7W E16 255
T7W E56 310
T7W E70 310
BEARING MOUNT
LEFT LINEFLOW FAN
HEAT EXCHANGER
DRAIN PAN
CENTER COVER
JOINT SHAFT
AUTO VANE
DRAIN HOSE
VANE MOTOR
WIRELESS ADAPTER CONTROLLER BOARD
CAPACITOR
INDOOR CONTROLLER BOARD
INDOOR CONTROLLER BOARD
Part Name
Specification
2.5F 440V
60
PKA-A36
1
FA
1
1
1
1
1
1
2
1
1
1
1
Q'ty/set
FA
FAL1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
1
1
1
1
1
1
1
1
1
Remarks
(Drawing No.)
2
FAL2
1
1
1
1
1
1
2
1
1
1
1
1
Continued to the next page
Wiring
Diagram
Symbol
W.B
Recommended
Q'ty
MV
C
I.B
I.B
From the previous page
No.
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
Part No.Part NameSpecification
RoHS
T7W E35 313
G
T7W E46 716
G
R01 E18 246
G
T7W E41 716
G
R01 H06 202
G
R01 H07 202
G
R01 H05 202
G
T7W B06 762
G
R01 16G 105
G
R01 19G 115
G
R01 KV5 102
G
R01 E03 103
G
T7W E16 675
G
R01 E04 103
G
R01 E06 239
G
INDOOR POWER BOARD
TERMINAL BLOCK
TERMINAL BLOCK
TERMINAL BLOCK
ROOM TEMPERATURE THERMISTOR
CONDENSER / EVAPORATOR
TEMPERATURE THERMISTOR
PIPE TEMPERATURE THERMISTOR
FAN MOTOR
RUBBER MOUNT
RIGHT LINEFLOW FAN
BEARING MOUNT
SLEEVE BEARING
FAN GUARD
SLEEVE BEARING
FUSE
2P(1, 2)
3P(S1, S2, S3)
3P(L1,L2,GR)
PN4N70-K
6.3A 250V
PKA-A36
FA
1
1
1
1
1
1
1
1
1
2
1
1
1
2
1
1
Q'ty/set
FA
FAL1
1
1
1
1
1
1
1
2
1
1
1
2
1
1
Remarks
(Drawing No.)
2
FAL2
1
1
1
1
1
Wiring
Diagram
Symbol
P. B
TB5
TB4
Recom-
mended
Q'ty
TB2
1
1
1
1
1
1
1
1
2
2
1
1
1
1
1
1
2
2
1
1
1
1
TH1
TH5
TH2
MF
FUSE
61
62
63
HEAD OFFICE : TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
CCopyright 2006 MITSUBISHI ELECTRIC ENGINEERING CO., LTD.
Distributed in Apr. 2009 No.OC369 REVISED EDITION-D PDF 7
Distributed in Oct. 2007 No.OC369 REVISED EDITION-C PDF 9
Distributed in Jun. 2007 No.OC369 REVISED EDITION-B PDF 9
Distributed in Aug. 2006 No.OC369 REVISED EDITION-A PDF 9
Distributed in Feb. 2006 No.OC369 PDF 10
New publication, effective Apr. 2009
Specifications subject to change without notice.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.