,_ MITSUBISHI
ELECTRIC
$LIII
Air-Co "
PKA-A.GA
PKA-A.GAL
e
iNSTALLATiON MANUAL
For safe and correct use, read this manual and the outdoor unit installation manual thoroughly before installing
the air-conditioner unit.
MANUAL DE INSTALACION
Para un uso correcto y seguro, lea detalladamente este manual y el manual de instalaci6n de la unidad exterior
antes de instalar la unidad de aire acondicionado.
Contents
1. Safety precautions ................................................................................... 2 5. Drainage piping work ............................................................................... 6
2. Installation location .................................................................................. 3 6. Electrical work .......................................................................................... 7
3. Installing the indoor unit ........................................................................... 3 7. Test run .................................................................................................. 12
4. Installing the refrigerant piping ................................................................. 5 8. Easy maintenance function (Option) ...................................................... 15
1. Safety precautions
Before installing the unit, make sure you read all the "Safety precau-
tions".
Please report to your supply authority or obtain their consent before
connecting this equipment to the power suppmysystem.
Warning:
Describes precautions that must be observed to prevent danger of injury or
death to the user.
Z_ Caution:
Describes precautions that must be observed to prevent damage to the unit.
Warning:
,, Ask a dealer or an authorized technician to install the unit.
,, For installation work, follow the instructions in the Installation Manual and use
tools and pipe components specifically made for use with refrigerant specified
in the outdoor unit installation manual
, The unit must be installed according to the instructions in order to minimize
the risk of damage from earthquakes, typhoons, or strong winds. An incor-
rectly installed unit may fall down and cause damage or injuries.
,, The unit must be securely installed on a structure that can sustain its weight.
,, if the air conditioner is installed in a small room, measures must be taken to
prevent the refrigerant concentration in the room from exceeding the safety
limit in the event of refrigerant leakage. Should the refrigerant leak and cause
the concentration limit to be exceeded, hazards due to lack of oxygen in the
room may result.
1.1. Before installation (Environment)
Caution:
,, Do not use the unit in an unusuam environment, if the air conditioner is in-
stalmedin areas exposed to steam, vomatimeoim(incmuding machine oim),or sulfuric
gas, areas exposed to high salt content such as the seaside, the performance
can be significantmy reduced and the internam parts can be damaged.
,, Do not install the unit where combustible gases may leak, be produced, flow,
or accumulate. If combustible gas accumulates around the unit, fire or explo-
sion may resumt.
,, Do not keep food, plants, caged pets, artwork, or precision instruments in the
direct airflow of the indoor unit or too close to the unit as these items can be
damaged by temperature changes or dripping water.
1.2. Before installation or relocation
Caution:
,, Be extremely carefum when transporting the units.Two or mote persons are
needed to handle the unit as it weighs 20 kg, 44 Ibe or more. Do not grasp the
packaging bands. Wear protective gloves as you can injure your hands on
the fins or other parts.
,, Be sure to safely dispose of the packaging materials. Packaging materiame,
such as naimsand other metam or wooden parts may cause stabs or other
injuries.
1.3. Before electric work
Caution:
,, Be sure to install circuit breakers, if not installed, electric shock may result.
,, For the power lines, use standard cables of sufficient capacity. Otherwise, a
short circuit, overheating, or fire may result.
,, When installing the power lines, do not apply tension to the cables.
After installation work has been completed, explain the "Safety precautions;' use, and
maintenance of the unit to the customer according to the information in the Operation
Manual and perform the test run to ensure normal operation. Both the Installation
Manual and Operation Manual must be given to the user for keeping. These manuals
must be passed on to subsequent users.
(_: Indicates which must be
Warning:
Carefully read the labels affixed to the main unit.
o Ventilate the room if refrigerant leaks during operation, if refrigerant comes
into contact with a flame, poisonous gases will be released.
, All electric work must be performed by a qualified technician according to
local regulations and the instructions given in this manual.
, Use only specified cables for wiring.
, The terminal block cover panel of the unit must be firmly attached.
o Use only accessories authorized by Mitsubishi Electric and ask a dealer or
an authorized technician to instammthem.
, The user shoumd never attempt to repair the unit or transfer it to another moca-
tion.
o After installation has been completed, check for refrigerant leaks, if refriger-
ant leaks into the room and comes into contact with the flame of a heater or
portabme cooking range, poisonous gases will be released.
o When the room humidity exceeds 80% or when the drainpipe is cmogged, wa-
ter may drip from the indoor unit. Do not install the indoor unit where such
dripping can cause damage.
, When installing the unit in a hospital or communications office, be prepared
for noise and electronic interference. Inverters, home appliances, high-fre-
quency medical equipment, and radio communications equipment can cause
the air conditioner to malfunction or breakdown.The air conditioner may also
affect medical equipment, disturbing medical care, and communications equip-
ment, harming the screen display quality.
o Thermal insulation of the refrigerant pipe is necessary to prevent condensa-
tion. if the refrigerant pipe isnot properly insulated, condensation will be formed.
o Place thermal insulation on the pipes to prevent condensation, if the drain-
pipe is installed incorrectly, water leakage and damage to the ceiling, floor,
furniture, or other possessions may result.
, Do not clean the air conditioner unit with water. Electric shock may result.
, Tighten all flare nuts to specification using a torque wrench. If tightened too
much, the flare nut can break after an extended period.
o Be sure to ground the unit. if the unit is not properly grounded, electric shock
may result.
, Use circuit breakers (ground fault interrupter, isolating switch (+B fuse), and
molded case circuit breaker) with the specified capacity. If the circuit breaker
capacity is larger than the specified capacity, breakdown or fire may result.
a
part grounded.
1.4. Before starting the test run
/_ Caution:
,, Turn on the main power switch more than 12 hours before starting operation.
Starting operation just after turning on the power switch can severely dam-
age the internal parts.
, Before starting operation, check that all panels, guards and other protective
parts are correctly installed. Rotating, hot, or high voltage parts can cause
injuries.
2
o Do not operate the air conditioner without the air filter set in place, if the air
filter is not installed, dust may accumulate and breakdown may result.
, Do not touch any switch with wet hands. Electric shock may result.
, Do not touch the refrigerant pipes with bare hands during operation.
, After stopping operation, be sure to wait at least five minutes before turning off
the main power switch. Otherwise, water meakage or breakdown may resumt.
2. Installation location
®T
©
®
Fig. 2-1
3. Installing the indoor unit
2.1. Outline dimensions (indoor unit) (Fig. 2-1)
Select a proper position allowing the following clearances for installation and mainte-
nance. (mm)
Models W B H (_) _ _F_ _G_ (_
A12, A18 39 9-1/4 13-3/8 Min.l-13/16 Max.5 Max.7-3/32Min.l-31/32Min.5-29/32
Mount the indoor unit on a ceiling strong enough to withstand the weight of the
unit.
990 235 340 Mn 30 Max 130 Mn 180 Mn 50 Mn 160
_ Ceiling
© Wall
@ Furnishing, etc
Warning:
(inch)
2.2. Outline dimensions (Outdoor unit)
Refer to the outdoor unit installation manual.
@
®
®
®
®
®
®
®
3.1. Check the indoor unit accessories (Fig. 3-1)
The indoor unit should be supplied with the following accessories.
PARTNUMBER
d_
®
®
®
®
®
®
®
®
®
(_) - ® are stored in a cut-out section of the packing material (styrofoam).
ACCESSORY
Mount board
Tapping screw 4 × 35
Pipe cover
Band
Felt tape
Wireless remote controller
Remocon holder
Alkali batteries (size AAA)
Mount piece (Package)
Wired remote controller
Drain adaptor
QUANTITY
1
12
1
5
3
1
1
2
1
1
1
LOCATIONOFSETTING
Fixatthe backofthe unit
Set inside the unit
for PKA-A,GAL
for PKA-A,GA
Fig. 3-1
(inch)
3.2. installing the wall mounting fixture (Fig. 3-2)
3.2.1. Setting the wall mounting fixture and piping positions
Using the wall mounting fixture, determine the unit's installation position
and the locations of the piping holes to be drilled.
z_ Warning:
Before drilling a hole in the wall, you must consult the building contractor.
Supporting piece
_ Mount board
© Main body
@ Slot (6-11 x 20,
©
8P-7/16 x 25/32 inch)
Unit center
CF}Bolt hole (14-o14 ram,
14P-9/16 inch)
_) Tapping hole (49-o5 ram,
49P-3/16 inch)
CH}Bottom left pipe slot
(o90 mm, 3-9/18 inch)
Bottom left pipe slot knockout hole
(_) Bottom right pipe slot (o90 ram, 3-9/16 inch)
Bottom right pipe slot knockout hole
_L_Liquid pipe flare connection position
@ Gas pipe flare connection position
(_) Level setting standard
_) Insert scale.
Hole centre
(_) Align the scale with the line.
®®
Fig. 3-2
3.2.2. Drilling the piping hole (Fig. 3-3)
Use a core drill to make a hole of 90-100 ram, 3-9/16 to 4 inch diameter in the
wail in the piping direction, at the position shown in the diagram to the left.
The hole should incline so that the outside opening is lower than the inside
opening.
Sleeve
_ Hole
©
@
®
© (Indoors)
@ Wall
_} (Outdoors)
I_ Insert a sleeve (with a 90 ram, 3-9/16 inch diameter and purchased locally)
through the hole.
Note:
The purpose of the hole's inclination is to promote drain flow.
Fig. 3-3
3
3. Installing the indoor unit
Fig. 3-4
©
Fig. 3-5
@ Min. 140 ram,
5-1/2 inch
_) Min. 300 ram,
11-13/16 inch
© Min. 55 mm,
2-3/16 inch
@ Mount board
3.2.3. Installing the wall mounting fixture
II_ Since the indoor unit weighs near 30 kg, 66 Ibs selection of the mounting
location requires thorough consideration. If the wall does not seem to be
strong enough, reinforce it with boards or beams before installation.
II_ The mounting fixture must be secured at both ends and at the centre, if
possible. Never fix it at a single spot or in any nonsymetrical way.
(If possible, secure the fixture at all the positions marked with a bold arrow.)
(Fig. 3-4)
z_ Warning:
If possible, secure the fixture at all positions indicated with a bold arrow.
z_ Caution:
o The unit body must be mounted horizontally.
o Fasten at the holes marked with A as shown by the arrows.
_) Fasten athread to the hole.
_ The levelcan be easily obtained by hanging a weight fromthestring andaligningthe string
with the mark.
3.3. When embedding pipes into the wall (Fig. 3-5)
• The pipes are on the bottom left.
• When the cooling pipe, drain pipes internal/external connection lines etc are to be
embedded into the wall in advance, the extruding pipes etc, may have to be bent
and have their length modified to suit the unit.
• Use marking on the mount board as a reference when adjusting the length of the
embedded cooling pipe.
• During construction, give the length of the extruding pipes etc some leeway.
(_)Mount board
(_)Reference marking forflare connection
C-C)Through hole
(_)On-site piping
3.4. Preparing the indoor unit
Rear, right and lower piping (Fig. 3-6)
1. Bind the cooling pipe and drain pipe together.
• Bind the pipes together with vinyl tape at three or more points. This will facilitate
passing the pipes through the wall.
Fig. 3-6
®
®
2. Remove the corner box and knock out the knockout holes as necessary.
• Remove the corner box by pushing in a downward direction (_), while at the same
time, pressing in the upper side part of the corner box (_.
(_)Corner box
(_)Under cover
Left and left rear piping (Fig. 3-7)
1. Remove the under cover.
• Remove the under cover by sliding it towards the rear of the unit @, while at the
same time, pressing the two points marked by arrow heads (_.
2. Remove the corner box and knock out the knockout holes as necessary.
®
Fig. 3-7
_ _....
_o_)
3.5. Mounting the indoor unit
1. Affix the mounting plate to the wall.
2. Hang the indoor unit on the two hooks positioned on the upper part of the mount-
ing plate.
Rear, right and lower piping (Fig. 3-8)
3. Affix the indoor unit.
4. After connecting the pipes, put the corner box back to where it was (follow the
removal steps backwards).
(_)Square hole
(_)Hooks
Fig. 3-8
®
/
(inch)
Fig. 3-9
Left and left rear piping (Fig. 3-9)
3. Cut out a mounting piece from the packaging material.
4. Pull the indoor unit up towards yourself as shown in the figure below and slide the
mounting piece in to the mounting plate using the mounting piece setting marks
as reference.
5. After connecting the pipes and wiring, put the under cover back to where it was,
and remove the mounting piece and affix the indoor unit as shown in the left
figure.
6. Put the corner box back to where it was.
(_)Mounting piece
(_)Ceiling
© Rib
4
4. Installing the refrigerant piping
®
@ Flare cutting dimensions
45o_+2°
Copper pipe O.D. Flare dimensions
(mm, inch) sA dimensions (mm, inch)
06.35, 1/4" 8.7 - 9.1,11/32-23/64
09.52, 3/8" 12.8- 13.2, 1/2-33/64
o12.7, 1/2" 16.2 - 16.6, 41/64-21/32
el 5.88, 5/8" 19.3 - 19.7, 49/64-25/32
®
Fig. 44
(inch)
4.1. Precautions
4.1.1. For devices that use R410A refrigerant
. Use ester oil, ether oil, a(kyibenzene oil (small amount) as the refrigeration oil
applied to the flared sections.
. Use Cl 220 copper phosphorus, for copper and copper alloy seamless pipes,
to connect the refrigerant pipes. Use refrigerant pipes with the thicknesses
specified in the tab(e to the be(ow. Make sure the insides of the pipes are
clean and do not contain any harmful contaminants such as sulfuric com-
pounds, oxidants, debris, or dust.
Z_ Warning:
When installing or moving the air conditioner, use only the specified refriger-
ant (R410A) to charge the refrigerant lines. Do not mix it with any other refriger-
ant and do not a((ow air to remain in the (ines. Air enclosed in the (ines can
cause pressure peaks resulting in a rupture and other hazards.
Liquid pipe e6.35mm, 1/4 inch thickness 0.8 mm, 1/32 inch
I A12, A18
Gas pipe e12.7mm, 1/2 inch thickness 0.8 mm, 1/32 inch
Do not use pipes thinner than those specified above.
4.2. Connecting pipes (Fig. 4-1)
= When commercially available copper pipes are used, wrap liquid and gas pipes
with commercially available insulation materials (heat-resistant to 100 °C, 212 °F or
more, thickness of 12 ram, 1/2 inch or more).
= The indoor parts of the drain pipe should be wrapped with polyethylene foam insu-
lation materials (specific gravity of 0.03, thickness of 9 ram, 23/64 inch or more).
= Apply thin layer of refrigerant oil to pipe and joint seating surface before tightening
flare nut.
= Use two wrenches to tighten piping connections.
= Use refrigerant piping insulation provided to insulate indoor unit connections. Insu-
late carefully.
(_) Flare nut tightening torque
Copper pipe O.D.
(mm, inch)
06.35, 1/4"
e9.52, 3/8"
o12.7, 1/2"
o15.88, 5/8"
© Apply refrigerating machine oil over the entire flare seat surface.
@ Use correct flare nuts meeting the pipe size of the outdoor unit.
Flare nut O.D. Tightening torque
(mm, inch) (N.m, ft4bs!
17, 43/64 14 - 18, 10-13
22, 7/8 34 - 42, 25-30
26, 1-3/64 49 - 61, 35-44
29, 1-9/64 68 - 82, 49-59
Avaimabmepipe size
A12, A18
Liquid side
Gas side
O : Factory flare nut attachment to the heat-exchanger.
06.35
o12.7
5
4. Installing the refrigerant piping
_'_ #............................................................................................................................................................................1_ (inch)
..................................................................................................;;
U_ ........ _ '_)
@2......@
Fig. 4=2
4.3. Positioning refrigerant and drain piping
(_) Position of refrigerant and drain piping (Fig. 4-2)
• The drain pipe can be cut midway to meet the on-site conditions.
(_)(Totallength offlexible hose) @ Drain hose
(_)Liquid pipe _E}Left-side piping
© Gas pipe _} Right-side piping
® Determine the position o1 the knockout holes on the unit body. (Fig. 4-8)
II_ Cut the knockout holes using a saw blade or an adequate knife.
Take care not to damage other parts of the unit.
® ® ® Remove the corner box and drill a knockout hole. If a hole is made without remov-
ing the box, the drain hose could be damaged.
(_) Left-side piping _D}Remote controller cable through hole
(_) Lower piping (E} Corner box
_C)Right-side piping
Fig. 4=3
\
Fig. 4=4
4.4. Refrigerant piping (Fig. 4=4)
1. Remove the flare nut and cap of the indoor unit.
2. Make a flare for the liquid pipe and gas pipe and apply refrigerating machine oil
(available from your local supplier) to the flare sheet surface.
3. Quickly connect the on site cooling pipes to the unit.
4. Wrap the pipe cover ® that is attached to the gas pipe and make sure that the
connection join is not visible.
5. Wrap the pipe cover of the unit's liquid pipe and make sure that it covers the
insulation material of the on site liquid pipe.
6. Use the bands that are provided _') to tighten both ends (15-20mm, 19/32 to
25/32 inch) o1each pipe cover ®.
(_)Cooling pipe and insulation (availablefrom local supplier)
(_)Unit'sgas pipe _} Bands (_0
_c)Unit'sliquid pipe (_F_On site gas pipe
(_)Pipecover _ _) On site liquid pipe
5. Drainage piping work
@ ®
\
©
Fig. 5=1
@
®
@
,',._:3_#ia ,;J,
@bx:_.... .....................,
Fig. 5=2
6
4.5. For twin combination
Refer to the outdoor unit unstallation manual.
5.1. Drainage piping work (Fig. 5-1)
• Use a PVC pipe (I.D. o20mm, 13/16 inch) for drain piping and provide 1/100 or
more downward slope.
• Other PVC pipe sizes are available with the drain adaptor supplied.
• Make sure that there is no water leakage from the connections.
• If the drain pipe passes indoors it must be covered with insulating material (foamed
polyethylene: specific gravity: 0.03, thickness: 9 mm, 23/64 inch or more) available on the
market.
• Do not put the drain piping directly in a drainage ditch where sulphuric gas may be
®
/
generated.
• When piping has been completed, check that water flows from the end of the drain
pipe.
(_)Drain connectionsocket © Indoor unit's drain hose
(_)Field drain pipe
Caution:
The drain pipe should be installed according to this Installation Manual to en-
sure correct drainage. Thermal insulation of the drain pipes is necessary to
prevent condensation. If the drain pipes are not properly installed and insu-
lated, condensation may drip on the ceiling, floor or other possessions.
Preparing left and left rear piping (Fig. 5-2)
(_) Remove the drain cap.
• Remove the drain cap by holding the bit that sticks out at the end of the pipe and
pulling.
(_)Drain cap
® Remove the drain hose.
• Remove the drain hose by holding on to the base of the hose (_ (shown by arrow)
and pulling towards yourself (_).
® Insert the drain cap.
• Insert a screwdriver etc into the hole at the end of the pipe and be sure to push to
the base of the drain cap.
_) Insert the drain hose.
• Push the drain hose until it is at the base of the drain box connection outlet.
• Please make sure the drain hose hook is fastened properly over the extruding drain
box connection outlet.
(_)Hooks
Remove the side panel of the indoor unit on the drain side. Pour water in the drain
pan and check that it comes out the drain pipe end. After confirmation, reinstall the
side panel.
6. Electrical work
\
®
Fig. 6-1
6.1.1. indoor unit power supplied from outdoor unit (A-control application)
The following connection patterns are available.
The outdoor unit power supply patterns vary on models.
6.1. Indoor unit (Fig. 6-1)
1. Remove the corner box.
2. install each wire into the unit.
3. Open the front grill, remove 1 tapping screw and remove the terminal block cover.
@ Terminal block cover
4. Connect each wire properly to the terminal block.
o In consideration of future servicing, please leave some leeway for the wiring length.
5. Put all the parts back the way they were.
6. Use a clamp from the bottom of the electric parts box to fasten each wire.
I_ Fix power source wiring to control box using buffer bushing for tensile force.
(PG connection or the like.)
A means for the disconnection of the supply with an isolation switch, or similar de-
vice, in all active conductors shall be incorporated in the fixed wiring.
_p Terminal block for Indoor/outdoor connecting
© Terminal block for power supply (separate indoor/outdoor unit power supplies, K-control ap-
plication)
@ Earth point
Clamp
CF_Terminal block for remote controller (Only for PKA-A.GA)
_) Conduit plate
CH_Bush (Purchased locally)
Ci_Lock nut (Purchased locally)
_3_Connector (Purchased locally)
(K_Conduit (Purchased locally)
(_ (_ _ Wiring circuit breaker or isolating switch
®
(_ IIi _ Remote controller (Only for PKA-A.GA)
LCJ _/-_/
@
[-ql © Outdoor unit
i I _D)Indoor unit/outdoor unit connecting cords
i_! CF)Indoor unit
_! _) Indoor unit earth
* Affix a label A that is included with the manuals near each wiring diagram for the indoor and outdoor units.
(_ (_ (_ _ Wiring circuit breaker or isolating switch
®
@ I , I I ®Remotecontroller(Only for PKA-A.GA)
[-ql [-ql © Outdoor unit
i I i @ Indoor unit/outdoor unit connecting cords
H! CF_Indoor unit
L¢i _O_, I _) Indoor unit earth
* Affix a label A that is included with the manuals near each wiring diagram for the indoor and outdoor units.
Indoor unit model
Indoor unit power supply
Minimum circuit ampacity
Maximum rating of overcurrent protective device
Indoor unit power supply
u_ _ Indoor unit power supply earth
•__o
•- z Indoor unit-Outdoor unit 41
_ Indoor unit earth
_: Remote controller-Indoor unit 42
Indoor unit L1-L2 43
,_, ._ Indoor unit-Outdoor unit $1-$2 43
"_ Indoor unit-Outdoor unit $2-S3 43
Remote controller-Indoor unit 43
"1. Max. 50 m, 168ft
*2. The 10 m, 30 ft wire is attached in the remote controller accessory. Max. 800 m, 1800 ft <Only for PKA-A.GA>
*3. The figures are NOT always against the ground.
$3 terminal has DC 24 V against $2 terminal. However between $3 and $1, these terminals are not electrically insulataed by the transformer or other device.
Notes:
1. Wiring size must comply with the applicable local and national code.
2. Use copper supply wires.
3. Use wires rated 300V or more for the power supply cables and the indoor unit/outdoor unit connecting cables.
4. Install an earth longer than other cables.
PKA
1A
15A
3 x AWGf6 (polar)
t x Min. AWG16
2 x AWG22 (Non-polar)
AC 208/230 V
DC24 V
DCf2V
@ Outdoor unit power supply
@ Outdoor unit power supply
7
6. Electrical work
6.1.2. Separate indoor unit/outdoor unit power suppJies (A-controJ appJication)
The following connection patterns are available.
The outdoor unit power supply patterns vary on models.
© ®
®
@
* Affix a label B that is included with the manuals near each wiring diagram for the indoor and outdoor units.
©
._._ ® ®
(_) Outdoor unit power supply
© Wiring circuit breaker or isolating switch
© Outdoor unit
© Indoor unit/outdoor unit connecting cords
© Remote controller (Only for PKA-A.GA)
(_ Indoor unit
(G'_Indoor unit power supply
(_) Outdoor unit power supply
© Wiring circuit breaker or isolating switch
© Outdoor unit
© Indoor unit/outdoor unit connecting cords
© Remote controller (Only for PKA-A.GA)
(_ Indoor unit
(G'_Indoor unit power supply
@ I
I '
* Affix a label B that is included with the manuals near each wiring diagram for the indoor and outdoor units.
If the indoor and outdoor units have separate power supplies, refer to the table at the
below. Change the indoor unit electrical box wiring refering to the figure in the right
and the DIP switch settings of the outdoor unit control board.
Indoor unit specifications
Indoor unit electrical box connector con-
nection change Required
Label affixed near each wiring diagram Required
for the indoor and outdoor units
Outdoor unit DIP switch settings (when
using separate indoor unit/outdoor unit L£3__
power supplies only) _ (SW8)
Ao, _
Indoor unit power supplied from outdoor unit
(when shipped from factory)
There are three types of labels (labels A, B, and C). Affix the appropriate labels to
the units according to the wiring method.
Indoor unit model
Indoor unit power supply
Minimum circuit ampacity
Maximum rating of overcurrent protective device
,_ Indoor unit power supply
Indoor unit power supply earth
×
;_ Indoor unit-Outdoor unit "1
'_ Indoor unit earth
_: Remote controller-Indoor unit *2
Indoor unit L1-L2 *3
R ._ Indoor unit-Outdoor unit $1-$2 *3
_- _ Indoor unit-Outdoor unit $2-$3 *3
Remote controller-Indoor unit *3
41. Max. 80m, 165ft
42. The 10 m, 30 ft wire is attached in the remote controller accessory. Max. 800 m, 1800 ft
43. The figures are NOT always against the ground.
Notes:
1. Wiring size must comply with the applicable local and national code.
PKA
Single 208/230 V, 60 Hz
1A
18A
2x Min. AWG16
1 x Min. AWG16
2 x AWG22 (polar)
2 x AWG22 (Non-polar)
AC 208/230 V
DC24 V
DC12 V
2. Use copper supply wires.
3. Use wires rated 300V or more for the power supply cables.
4. mnstaNman earth monger than other cabmes.
Connectors (connections when shipped
from the factory are for indoor unit power
supplied from outdoor unit)
Separate indoor unit/outdoor unit power
supplies
If the indoor and
outdoor units have
separate power
supplies, change the
connections of the
connectors as shown
in the following
figure.
Connectors
8
6. Electrical work
6.1.3. K-control application
The following connection patterns are available.
The outdoor unit power supply patterns vary on models.
<For cooming onmymodems><For heat pump modems>
© ® © @
® ®
@
Set the DIP switch of the indoor
unit control board.
SW5 1 2 3
SW5-1 :ON SW5-2, 3 : OFF
@
Set the DIP switch of the indoor
unit control board.
SW5 1 2 3
SW5-1,2 :ON SW5-3 : OFF
(_) Outdoor unit power supply
(_) Wiring circuit breaker or isolating switch
C-C}Outdoor unit
(_) Indoor unit/outdoor unit connecting cords
Remote controller (Only for PKA-A.GA)
(_ Indoor unit <For heat pump models>
(G'_Indoor unit <For cooling only models>
(_ Indoor unit power supply
* Affix a label B that is included with the manuals near each wiring diagram for the indoor and outdoor units.
<For heat pump models> <For cooling only models> _) Outdoor unit power supply
© @ @ © @ @
.
@
Set the DIP switch of the indoor
unit control board.
© Main indoor (_) Sub indoor
@
Set the DIP switch of the indoor
unit control board.
(_ Main indoor (_ Sub indoor
(_) Wiring circuit breaker or isolating switch
C-C}Outdoor unit
(_) Indoor unit/outdoor unit connecting cords
_E_Remote controller (Only for PKA-A.GA)
(_ Main indoor unit <For heat pump models>
(G'_Sub indoor unit <For heat pump models>
(_ Indoor unit power supply
(_) Main indoor unit <For cooling only models>
Sub indoor unit <For cooling only models>
123 1123 I
SW5
SW5-1 : ON SW5-1 : ON
SW5-2 : OFF SW5-2 :OFF
SW5-3 : OFF SW5-3 :ON
1 23 1 23 I
SW5
SW5-1 : ON SW5-1 : ON
SW5-2 : ON SW5-2 : ON
SW5-3 : OFF SW5-3 : ON
* Affix a label B that is included with the manuals near each wiring diagram for the indoor and outdoor units.
To change to K-control, set the DIP switch (SW5) of the indoor unit control board as
shown in the above figure and change the electric wiring of the indoor unit as shown
in the right figure.
Set up Dip switch after turning off Power supply switch.
Be careful that setting the DIP switch (SW5) of the indoor unit control board varies
between the heat pump models and cooling models of the outdoor unit.
DIP switch (SW5)
SW5-1 A_CONTROL K-CONTROL
SW5-2 heat pump models cooling only models _ Dip switch SW5-2 and SW5-3 is effective only
OFF ON
sw5-3 MAIN SUB _Jwhen Dip switch SW5-1 (K-CONTROL) is ON.
* There are three types of labels (labels A, B, and C). Affix the appropriate labels to
the units according to the wiring method.
Indoor unit model PKA
Indoor unit power supply Single 208/230 V, 60 Hz
Minimum circuit ampacity 1 A
Maximum rating of overcurrent protective device 15A
Indoor unit power supply 2 x Min. AWG16
-_ Indoor unit power supply earth 1 x Min. AWG16
× H/P: 3 x AWG22 (polar)
Indoor unit-Outdoor unit "1
_;_ C/O: 2 x AWG22 (polar)
Indoor unit earth
Remote controller-Indoor unit *2 2 x AWG22 (Non-polar)
Indoor unit L1-L2 *3 AC 208/230 V
# _ Indoor unit-Outdoor unit $1-$2 *3 DC12 V
E "_ Indoor unit-Outdoor unit $1 -$3 *3 D012 V
_5
Remote controller-Indoor unit *3 DC12 V
41. Max. 50 m, 185 ft
42. The 10 m, 30 ft wire is attached in the remote controller accessory. Max. 500 m, 1500 ft
43. The figures are NOT always against the ground.
Notes:
1. Wiring size must comply with the applicable local and national code.
2. Use copper supply wires.
3. Use wires rated 300V or more for the power supply cables.
4. mnstamman earth monger than other cabmes.
Connectors
INDOOR UNIT
CONTROL BOARD
To change to the K-control,
make sure to change the
INDOOR UNIT
CONTROL BOARD
9