The old refrigerant and lubricant in the existing piping
contains a large amount of chlorine which may cause the
lubricant deterioration of the new unit.
Use “low residual oil piping”
If there is a large amount of residual oil (hydraulic oil, etc.)
inside the piping and joints, deterioration of the lubricant
will result.
Store the piping to be used indoors during
installation and both ends sealed until just
before brazing.
(Store elbows and other joints in a plastic bag.)
If dust, dirt, or water enters the refrigerant cycle,
deterioration of the oil and compressor trouble may result.
Use ESTR , ETHER or HAB as the lubricant to
coat flares and flange connection parts.
If large amount of mineral oil enter, that can cause
deterioration of refrigerant oil etc.
Use liquid refrigerant to seal the system.
If gas refrigerant is used to seal the system, the composition
of the refrigerant in the cylinder will change and performance
may drop.
Do not use a refrigerant other than R407C.
If another refrigerant (R22, etc.) is used, the chlorine in the
refrigerant may cause the lubricant deterioration.
Use a vacuum pump with a reverse flow check valve.
The vacuum pump oil may flow back into the refrigerant
cycle and cause the lubricant deterioration.
Ventilate the room if refrigerant leaks during
operation. If refrigerant comes into contact with
a flame, poisonous gases will be released.
2
[1] Cautions for service
·After recovering the all refrigerant in the unit, proceed to working.
·Do not release refrigerant in the air.
·After completing the repair service, recharge the cycle with the specified amount of
liquid refrigerant.
[2] Refrigerant recharging
(1) Refrigerant recharging process
1Direct charging from the cylinder.
·R407C cylinder are available on the market has a syphon pipe.
·Leave the syphon pipe cylinder standing and recharge it.
(By liquid refrigerant)
Unit
Gravimeter
(2) Recharge in refrigerant leakage case
·After recovering the all refrigerant in the unit, proceed to working.
·Do not release the refrigerant in the air.
·After completing the repair service, recharge the cycle with the specified amount of
liquid refrigerant.
[3] Service tools
Use the below service tools as exclusive tools for R407C refrigerant.
No. Tool name Specifications
1Gauge manifold ·Only for R407C.
·Use the existing fitting SPECIFICATIONS. (UNF7/16)
·Use high-tension side pressure of 3.43MPa·G or over.
2Charge hose ·Only for R407C.
·Use pressure performance of 5.10MPa·G or over.
3 Electronic scale
4Gas leak detector ·Use the detector for R134a or R407C.
5Adapter for reverse flow check. ·Attach on vacuum pump.
6Refrigerant charge base.
7Refrigerant cylinder. ·For R407C ·Top of cylinder (Brown)
·Cylinder with syphon
8Refrigerant recovery equipment.
33
Cautions for units utilizing refrigerant R410A
Do not use the existing refrigerant piping.
The old refrigerant and lubricant in the existing piping
contains a large amount of chlorine which may cause the
lubricant deterioration of the new unit.
Use “low residual oil piping”
If there is a large amount of residual oil (hydraulic oil, etc.)
inside the piping and joints, deterioration of the lubricant
will result.
Store the piping to be used indoors during
installation and both ends of the piping sealed
until just before brazing. (Leave elbow joints, etc.
in their packaging.)
If dirt, dust or moisture enter into refrigerant cycle, that can
cause deterioration of refrigerant oil or malfunction of compressor.
Use ester oil, ether oil or alkylbenzene oil (small
amount) as the refrigerant oil applied to flares
and flange connections.
If large amount of mineral oil enter, that can cause deterioration of refrigerant oil etc.
Use a vacuum pump with a reverse flow check
valve.
Vacuum pump oil may flow back into refrigerant cycle and
that can cause deterioration of refrigerant oil etc.
Use the following tools specifically designed for
use with R410A refrigerant.
The following tools are necessary to use R410A refrigerant.
If dirt, dust or moisture enter into refrigerant cycle, that can
cause deterioration of refrigerant oil or malfunction of compressor.
Do not use a charging cylinder.
If a charging cylinder is used, the composition of refrigerant will change and the efficiency will be lowered.
Charge refrigerant from liquid phase of gas
cylinder.
If the refrigerant is charged from gas phase, composition
change may occur in refrigerant and the efficiency will be
lowered.
Do not use refrigerant other than R410A.
If other refrigerant (R22 etc.) is used, chlorine in refrigerant can cause deterioration of refrigerant oil etc.
Ventilate the room if refrigerant leaks during
operation. If refrigerant comes into contact with
a flame, poisonous gases will be released.
4
[1] Cautions for service
(1) Perform service after collecting the refrigerant left in unit completely.
(2) Do not release refrigerant in the air.
(3) After completing service, charge the cycle with specified amount of refrigerant.
(4) When performing service, install a filter drier simultaneously.
Be sure to use a filter drier for new refrigerant.
[2] Additional refrigerant charge
When charging directly from cylinder
· Check that cylinder for R410A on the market is syphon type.
· Charging should be performed with the cylinder of syphon stood vertically. (Refrigerant is charged from liquid phase.)
Unit
Gravimeter
[3] Service tools
Use the below service tools as exclusive tools for R410A refrigerant.
No. Tool name Specifications
1Gauge manifold ·Only for R410A
·Use the existing fitting
·Use high-tension side pressure of 5.3MPa·G or over.
2Charge hose ·Only for R410A
·Use pressure performance of 5.09MPa·G or over.
3 Electronic scale
4Gas leak detector ·Use the detector for R134a, R407C or R410A.
5Adaptor for reverse flow check ·Attach on vacuum pump.
6Refrigerant charge base
7Refrigerant cylinder ·Only for R410A Top of cylinder (Pink)
Cylinder with syphon
8Refrigerant recovery equipment
specifications
. (UNF1/2)
5
3
PAR-21MAA
ON/OFF
FILTER
CHECK
OPERATION
CLEAR
TEST
TEMP.
MENU
BACKDAY
MONITOR/SET
CLOCK
ON/OFF
Set Temperature buttons
Down
Up
Timer Menu button
(Monitor/Set button)
Mode button (Return button)
Set Time buttons
Back
Ahead
Timer On/Off button
(Set Day button)
Opening the
door.
ON/OFF button
Fan Speed button
Filter button
(<Enter> button)
Test Run button
Check button (Clear button)
Airflow Up/Down button
Louver button
(
Operation button)
To preceding operation
number.
Ventilation button
(
Operation button)
To next operation number.
PART NAMES AND FUNCTIONS
Indoor Unit
Louver
Air outlet
Air inlet
Vane
Filter
Damper
Air outlet
Louver
Wired remote controller
Once the controls are set, the same operation mode can be repeated by simply pressing the ON/OFF button.
Operation buttons
6
Display
For purposes of this explanation,
all parts of the display are shown
as lit. During actual operation, only
the relevant items will be lit.
Identifies the current operation
Shows the operating mode, etc.
* Multilanguage display is sup-
ported.
“Centrally Controlled” indicator
Indicates that operation of the remote controller has been prohibited by a master controller.
“Timer Is Off” indicator
Indicates that the timer is off.
Temperature Setting
Shows the target temperature.
Day-of-Week
Shows the current day of the week.
Time/Timer Display
Shows the current time, unless the simple or Auto Off
timer is set.
If the simple or Auto Off timer is set, shows the time
remaining.
TIME SUN MON TUE WED THU FRI SAT
TIMER
AFTER
ERROR CODE
°F°C
Hr
AFTER
°F°C
ONLY1Hr.
Up/Down Air Direction indicator
The indicator shows the direction of the outcoming airflow.
“One Hour Only” indicator
Displayed if the airflow is set to
Low and downward during COOL
or DRY mode. (Operation varies
according to model.)
The indicator goes off after one
hour, at which time the airflow direction also changes.
Room Temperature display
Shows the room temperature.
Louver display
Indicates the action of the swing
louver. Does not appear if the
louver is stationary.
(Power On indicator)
Indicates that the power is on.
ON
OFF
FUNCTION
FILTER
WEEKLY
SIMPLE
AUTO OFF
“Sensor” indication
Displayed when the remote controller
sensor is used.
“Locked” indicator
Indicates that remote controller buttons have been locked.
“Clean The Filter” indicator
Comes on when it is time to clean the
filter.
Timer indicators
The indicator comes on if the corresponding timer is set.
Fan Speed indicator
Shows the selected fan speed.
Ventilation indicator
Appears when the unit is running in
Ventilation mode.
Caution
Only the Power on indicator lights when the unit is stopped and power supplied to the unit.
If you press a button for a feature that is not installed at the indoor unit, the remote controller will display the “Not Available”
message.
If you are using the remote controller to drive multiple indoor units, this message will appear only if he feature is not
present at every unit connected.
When power is turned ON for the first time, it is normal that “PLEASE WAIT” is displayed on the room temperature indication
(For max. 2minutes). Please wait until this “PLEASE WAIT” indication disappear then start the operation.
For the PFFY-P VKM series, the airflow direction displayed on the remote controller is different from the actual airflow direc-
tion. Refer to the following table.
123 4
(Horiz.)Swing
Display
1234
(Horiz.)Swing
Actual
The airflow direction for the lower air outlet damper cannot be set. The airflow direction is automatically controlled by a com-
puter.
77
4
SPECIFICATION
4-1. Specification
Item
Power source1-phase 220-240V 50Hz
Cooling capacitykW2.22.83.64.5
Heating capacitykW2.53.24.05.0
PowerCoolingkW0.0250.0250.0250.028
consumptionHeatingkW0.0250.0250.0250.028
Current
DimensionWidthmm700700700700
Weightkg15151515
Heat exchangerCross fin (Aluminum plate fin and copper tube
Fan
Motor
Air filterPP honeycomb fabric (Catechin air filter)
Refrigerant
pipe dimension
Field drain pipe size:mmI.D.16(PVC pipe VP-16 connectable
Test conditions,
Cooling : Dry-bulb temperature 27Wet-bulb temperature 19
Heating : Dry-bulb temperature 20Wet-bulb temperature 15
90
80
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF
HEARING FOR
CONTINUOUS
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
NOISE
10
631252505001000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
FUNCTION
COOLING
HEATING
SPL(dB(A))
38
38
LINE
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
PFFY-P40VKM-E PFFY-P40VKM-ER1
FAN SPEED
High
Test conditions,
Cooling : Dry-bulb temperature 27Wet-bulb temperature 19
Heating : Dry-bulb temperature 20Wet-bulb temperature 15
90
80
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF
HEARING FOR
CONTINUOUS
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
NOISE
10
631252505001000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
FUNCTION
COOLING
HEATING
SPL(dB(A))
44
44
LINE
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
INDOOR UNIT
MICROPHONE
1m
1m
WALL
10
AIR OUTLET SELECTION6
ON
OFF
12345678910
SW12
0
1
9
2
8
3
7
4
6
5
(10ths DIGIT)
SW1
SW11
0
1
9
8
7
4
6
5
(1s DIGIT)
CN43
SWC
CN82
SW14
2
3
SWC
0
1
F
2
E
D
C
B
7
A
8
9
./
(BRANCH No.)
With this function, air comes out simultaneously from the upper and
lower air outlets so that the room can be cooled or heated effectively.
This function is set using the switch SWC on the address board.
3
4
5
6
.
Fig. 4-1
SWC
How to set to blow out air from the upper and lower air outlets:
Set the SWC to lower side (" "). (Initial setting)
Air blows out automatically from the upper and lower air outlet as
shown in the table below.
SWC
Note:
Be sure to operate with the main power turned off.
How to set to blow out air from the upper air outlet only:
Set the SWC to upper side (" ").
Description of operation
Operation
COOL
Air flow
Conditions
Upper and lower air flow
Room temperature and
set temperature are different. +1
Upper air flow
Room temperature is
close to set temperature
or thermo-off.+1
• Be sure to keep the area around the damper of the lower air outlet free of any objects.
+1
Upper air flow
2deg
+2
DIP SW3-2 (on indoor controller board) : OFF (Initial Setting)
If the air conditioner has operated for 2hours with upper and lower air flow,
it changes to 8deg for next 30minutes. After 30minutes it changes back to 4deg.
DIP SW3-2 (on indoor controller board) : ON
Remains to be 4deg.
DRY
Upper air flow only
—
Upper and lower air flow
4deg +2
Upper and lower air flow
(Normal condition (in
heating))
HEATFAN
Upper air flow
During defrosting operation, start of operation, thermo-off
1. At servicing for outdoor unit, always follow the wiring diagram of outdoor unit.
2. In case of connecting MA-Remote controller, please connect MA remote controller cable
in an accessory to the connecter . (Remote controller wire is non-polar.)
3. In case of using M-NET, please connect to TB5. (Transmission line is non-polar.)
4. Symbol [S] of TB5 is the shield wire connection.
5. Symbols used in wiring diagram above are, : terminal block, : connector.
6. The setting of the SW2 dip switches differs in the capacity. For the detail, refer to fig.
LED on indoor board for service
MARK
Main power supply
LED1
Power supply for
LED2
MA-Remote controller
NAMESYMBOLNAME
MF1
MF2
MV1
MV2
LS
LEV
TB2
TB5
TH21
TH22
1 2
MEANING
FUNCTION
Main power supply (Indoor unit: 220-240V)
power on → Iamp is Iit
Power supply for MA-remote controller
on → Iamp is lit
FAN MOTOR (UPPER)
TH23
FAN MOTOR (LOWER)
SYMBOL
VANE MOTOR
A. B
DAMPER MOTOR
DAMPER LIMIT SWITCH (CLOSE)
LINEAR EXPANSION VALVE
POWER SUPPLY
Disconnect the connector then measure the resistance using a tester.
(Surrounding temperature 10~30)
Normal
4.3k~9.6k
Abnormal
Open or short
(Refer to the next page for a detail.)
Check 10-2.
Disconnect the connector then measure the resistance valve using a tester.
(Surrounding temperature 20)
Abnormal
Open or short
(1)-(5)
White-Red
Normal
(2)-(6)
Yellow-Brown
(3)-(5)
Orange-Red
(4)-(6)
Blue-Brown
200 $10%
Measure the resistance between the terminals using a tester.
(Surrounding temperature 20~30)
NormalConnectorAbnormal
Brown — Red
Brown — Orange
Brown — Yellow
282~306Open or short
Brown — Blue
(Refer to the next
page for a detail.)
Damper motor (MV2)
Orange
Red
Pink
M
BlueYellow Brown
Measure the resistance between the terminals using a tester.
(Surrounding temperature 20~30)
NormalConnectorAbnormal
Brown — Yellow
Brown — Blue
Red — Orange
186~214Open or short
Red — Pink
15
<Thermistor Characteristic graph>
Thermistor for
lower temperature
Room temperature thermistor (TH21)
Liquid pipe temperature thermistor (TH22)
Gas pipe temperature thermistor (TH23)
< Thermistor for lower temperature >
50
40
Thermistor R
0=15k' ± 3%
Fixed number of B=3480 ± 2%
Rt=15exp { 3480( ) }
1
273+t
1
273
0: 15k'
30
Resistance (K)
20
10: 9.6k'
20: 6.3k'
25: 5.2k'
30: 4.3k'
10
40: 3.0k'
0
-20-10 0 1020 304050
Temperature ()
Linear expansion valve
1 Operation summary of the linear expansion valve.
• Linear expansion valve open/close through stepping motor after receiving the pulse signal from the indoor controller board.
• Valve position can be changed in proportion to the number of pulse signal.
<Connection between the indoor controller board and the linear expansion valve>
Linear expansion valve
4
M
6
2
5
White
1
Red
3
Orange
Blue
Brown
Yellow
:4
:3
:2
:1
Brown
Red
Blue
Orange
Yellow
White
Connector (CN60)
Controller board
DC12V
6
5
4
3
2
1
Drive circuit
:4
:3
:2
:1
16
<Output pulse signal and the valve operation>
2
OFF
Output
3
OFF
Output
(Phase)
{1
1
ON
4
ON
Closing a valve : 1 → 2 → 3 → 4 → 1
Opening a valve : 4 → 3 → 2 → 1 → 4
The output pulse shifts in above order.
{2
{3
{4
ON
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
OFF
ON
2 Linear expansion valve operation
C
Outdoor unit
R410A model: 1400 pulse
R22 model : 2000 pulse
Opening a valve
all the way
Close
Valve position (capacity)
A
E
B
Extra tightning (80~100pulse)
D
Open
Pulse number
• When linear expansion valve operation stops, all output phase
become OFF.
• At phase interruption or when phase does not shift in order,
motor does not rotate smoothly and motor locks and vibrates.
• When the switch is turned on, 2200 pulse closing valve signal
will be send till it goes to
A point in order to define the valve
position.
• When the valve move smoothly, there is no noise or vibration
occurring from the linear expansion valve : however, when the
pulse number moves from
E to A or when the valve is locked,
more noise can be heard than normal situation.
• Noise can be detected by placing the ear against the screw driver handle while putting the screw driver to the linear expansion
valve.
3 Trouble shooting
Symptom
Operation circuit
failure of the
micro processor.
Linear expansion
valve mechanism
is locked.
Short or breakage
the motor coil of
the linear expansion valve.
Valve does not
close completely.
Wrong connection
of the connector
or contact failure.
Check points
Disconnect the connector on the controller board,
then connect LED for checking.
Pulse signal will be sent out for 10 seconds as soon as
the main switch is turned on. If there is LED with lights
on or lights off, it means the operation circuit is abnormal.
Motor will idle and make ticking noise when motor is
operated while the linear expansion valve is locked. This
ticking sound is the sign of the abnormality.
of
Measure the resistance between the each coil (red-white,
red-orange, brown-yellow, brown-blue) using a tester. It
is normal if the resistance is in the range of 150'±10%.
To check the linear expansion valve, operate the indoor unit
in fan mode and at the same time operate other indoor units
in cooling mode, then check the pipe temperature <liquid
Liquid pipe
thermistor
Linear
expansion
valve
It is not necessary to exchange the linear expansion valve, if
the leakage is small and not making any trouble.
Check the color of lead wire and missing terminal of
the connector.
LED1
pipe temperature> of the indoor unit by the
outdoor multi controller board operation
monitor. During fan operation, linear expansion valve is closed completely and if there
are some leaking, detecting temperature of
the thermistor will go lower. If the detected
temperature is much lower than the temperature indicated in the remote controller,
it means the valve is not closed all the way.
6
5
4
3
2
1
Countermeasures
Exchange the indoor
controller board at drive
circuit failure.
Exchange the linear
expansion vale.
Exchange the linear
expansion valve.
If large amount of
refrigerant is leaked,
exchange the linear
expansion valve.
Disconnect the connector at the controller
board, then check the
continuity.
17
10-2. FAN MOTOR
Check method of indoor fan motor (fan motor/control P.C.board)
Notes
· High voltage is applied to the connecter (CNMF1) for the fan motor. Pay attention to the service.
· Do not pull out the connector (CNMF1,2) for the motor with the power supply on.
(It causes trouble of the control
Self check
Conditions : The indoor fan cannot turn around.
Wiring contact check
Contact of fan motor connector (CNMF1,2)
P.C.board)
Was contact caused good?
N0
Wiring recovery
Yes
Power supply check
Check the voltage in the indoor control P.C.board
TEST POINT
FAN MOTOR (upper)
CNMF1 CNMF2 : DC310 ~ 340V
CNMF2 : DC15V
CNMF2 : DC0 ~ 6.5V
FAN MOTOR (lower)
CNMF1 CNMF2 : DC310 ~ 340V
CNMF2 : DC15V
CNMF2 : DC0 ~ 6.5V
The voltage between CNMF2 and are values during the
fan motor operation. In the case that the fan motor off, the voltage is 0V.
Is the voltage normal?
Yes
No
Indoor controller board fuse check
Is the fuse normal?
Replace the indoor
controller board.
Yes
No
NG
Check the operationEND
Replace
the fuse.
OK
Fan motor position sensor signal check
Turn around the fan motor more than one revolution slowly,
and check the voltage between the connecter
FAN MOTOR (upper)
CNMF2 /FAN MOTOR (lower) CNMF2
Does the voltage repeat
DC 0V and DC 15V?
Yes
Replace the indoor
controller board.
OK
Check the operationEND
NG
Replace the fan motor.
No
OK
Check the operation
NG
Replace the fan motor.
Replace the fan motor.
Yes
Check the operation of fan.END
NG
Replace the indoor controller board.
18
END
OK
10-3. FUNCTION OF DIP SWITCH
SwitchFunctionRemarks
Pole
ONOFF
Thermistor <Room temperature
Operation by switch
SW1
Function
setting
1
detection> position
2
Filter clogging detection
3
Filter cleaning
4
Fresh air intake
Switching remote
5
controller display
6
Humidifier control
7
Air flow set in case of
Heat thermostat OFF
8
9
Auto restart function
10
Power ON/OFF by breaker
Built-in remote controller
Provided
2,500hr
Effective
Indicating if the
thermostat is ON
Always operated while the heat in ON +1
Low +3
Setting air flow +3
Effective
Effective
Indoor unit
Not provided
100hr
Not effective
Indicating fan operation
ON/OFF
Operated depends on the condition +2
Extra low +3
Depends on SW1-7
Not effective
Not effective
Effective
timing
Under
suspension
Address board
<Initial setting>
ON
OFF
1234 5678 9
Note :
+1
Fan operation at Heating
mode.
+2
Thermo ON operation at
heating mode.
+3
SW 1-7=OFF, SW 1-8=ON
→ Setting air flow.
SW 1-7=ON, SW 1-8=ON
→ Indoor fan stop.
Indoor controller board
Set while the unit is off.
<Initial setting>
Set for each capacity.
SW2
Capacity
code
setting
1~6
Capacity
P20P32
P25P40
SW 2CapacitySW 2
ON
OFF
123456
ON
OFF
123456
ON
OFF
123456
ON
OFF
123456
Before
power
supply
ON
10
SW3
Function
setting
SW4
Model
Selection
(Setting
for
PFFY
series)
Heat pump/Cooling only
1
Limitation at time of damper
2
open operation + 4
Van e
3
Vane swing function
4
Vane horizontal angle
5
Vane cooling limit angle setting +5
6
Changing the opening of linear
7
expansion valve during thermo OFF
Heat 4degrees up
8
Superheat setting temperature
9
Sub cool setting temperature +6
10
In case replacing the indoor controller board, make sure to set the switch to the
factory-preset status, which is shown below.
1~5
ON
OFF
Cooling only
Not effective
Available
Available
Second setting +7
Horizontal angle
Effective
Not effective
+6
—
—
12345
Heat pump
Effective
Not available
Not available
First setting
Down B, C
Not effective
Effective
—
—
Under
suspension
Note :
+4
SELECTION"
+5
can be used only 1 hour.
+6
SW3-9,10.
+7
as first setting.
Before
power
supply
ON
Indoor controller board
Set while the unit is off.
<Initial setting>
ON
OFF
1234 5678 9
Refer to "6. AIR OUTLET
At cooling mode, each angle
Please do not use
Second setting is the same
Indoor controller board
10
19
Switch
Pole
Operation by switch
Effective
timing
Remarks
Address board
SWC
Air
outlet
selector
SW11
1s digit
address
setting
SW12
10ths digit
address
setting
SW14
Branch
No.
setting
Connector
2
(Standard)
SW1210SW11
9
8
7
6
Rotary switchRotary switch
(Option)
0
1
2
3
4
5
SW14
0
1
F
E
D
C
B
A
8
9
Refer to 6. AIR OUTLET SELECTION.
0
9
8
7
6
5
1
2
3
4
5
6
7
How to set address
1
Example : If address is "3", remain SW12
2
3
4
(for over 10) at "0", and match SW11 (for 1 to 9)
with "3".
How to set branch number SW14 (Series R2 only)
Match the indoor unit’s refrigerant pipe with the BC
contoller’s end connection number
Remain other than series R2 at "0".
(1) Push both sides of the upper part of the front grille and
pull the front grille open, and then remove the front grille
from the panel. (See Photo 1.)
(2) Remove the screws of the panel. (See Photo 2.)
(3) Open the horizontal vane and push the left, right and
middle of the upper part of the panel, and pull the panel
toward you. (See Photo 2.)
(4) Lift up the panel and remove it from the box.
Photo 1
Push
Grille
Photo 2
PHOTOS
Horizontal
vane
Push
Screws of the panel
Push
Push
Push
2323
OPERATING PROCEDUREPHOTOS
2. Removing the indoor controller board and
address board
(1) Remove the panel. (Refer to 1.)
(2) Remove the screw of the electrical cover, and then the
electrical cover. (See Photo 3.)
(3) Remove the screw of the ground wires connected to the
indoor fan motor (lower), and then the ground wires. (See
Photo 4.)
(4) Remove the screw of the ground wires connected to the
indoor heat exchanger, and then the ground wires. (See
Photo 4.)
(5) Disconnect all the connectors on the address board and
remove the screw of the address board case.
(6) Remove the screw of the ground wire connected to the
indoor controller board, and then the ground wire.
(See Photo 4.)
(7) Pull the indoor controller board case slightly toward you
from the electrical box, and disconnect all the connectors
on the indoor controller board.
(8) Pull out the indoor controller board case from the electrical
box.
Photo 3
Hair pin cover
Photo 4
Address
board (A.B)
Water cover
Screw of the
ground wire (I.B)
Screw of the
electrical cover
3. Removing the electrical box
(1) Remove the panel. (Refer to 1.)
(2) Remove the electrical cover. (Refer to 2.)
(3) Remove the ground wires from the electrical box.
(Refer to 2.)
(4) Remove the ground wires connected to the indoor fan
motor and ones connected to the indoor heat exchanger.
(See Photo 4.)
(5) Remove the screw of the electrical box. (See Photo 4.)
(6) Disconnect the following connectors on the indoor
controller board.
• Fan motor connectors <CNMF1, 2>
• Vane motor connector <CN6V1>
• Damper motor connector <CN6V2>
• Pipe temperature thermistor connector <CN44>
• Damper limit switch connector <CN36>
(7) Unhook the electrical box from the upper catch and pull out
the electrical box from the box.
Terminal block
(TB2)
Terminal block(TB5)
Screw of the
ground wire
(Heat exchanger)
Indoor
controller
board (I.B)
Screw of the
ground wire
(Fan motor)
24
OPERATING PROCEDUREPHOTOS
4. Removing the vane motor (MV1)
(1) Remove the panel. (Refer to 1.)
(2) Remove the screws of the vane motor and pull out the
vane motor. (See Photo 5.)
(3) Disconnect the connector from the vane motor.
5. Removing the indoor fan motor (upper)
(1) Remove the panel. (Refer to 1.) (2) Remove the electrical box. (Refer to 3.)
(3) Remove the nozzle (upper). (See Photo 6.)
(4) Unhook the water cover from the catches and remove the
water cover. (See Photo 6.)
(5) Removing the screw of the motor band, and then the motor
band.
(See Photo 7.)
(6) Remove the line flow fan and the indoor fan motor (upper)
from the box.
Photo 5
Screw of vane motor
Photo 6
Nozzle <Upper>
Photo 7
Water cover
Screw of motor band
25
OPERATING PROCEDUREPHOTOS
6. Removing the damper motor and the damper
limit switch
(1) Remove the panel. (Refer to 1.)
(2) Remove the screws of the nozzle assembly (lower).
(See Photo 8.)
(3) Remove the drain hose from the nozzle assembly (lower)
and pull out the nozzle assembly (lower) toward you.
(4) Remove the tape fixing the lead wires of the damper motor
from the nozzle assembly <lower>. (See Photo 9.)
(5) Remove the screws of the damper motor support, and
then the damper motor support.
(6) Remove the screws of the damper motor, and then the
damper motor from the damper motor support.
(7) Disconnect the connector from the damper motor.
(8) Remove the damper limit switch. (LS).
7. Removing the indoor fan motor
(1) Remove the panel. (Refer to 1.)
(2) Remove the nozzle assembly (lower) and the drain hose.
(Refer to 6.)
(3) Remove the screw of the ground wire of the indoor fan
motor (lower), and then the ground wire. (See Photo 11.)
(4) Remove the screw of the motor band, and then the motor
band. (See Photo11.)
(5) Remove the line flow fan and the indoor fan motor (lower)
from the box.
Photo 8
Screw of
the nozzle
Photo 9
Lead wires of the damper motor
Photo 10
Screw of
the nozzle
Drain
hose
Screw of the damper
motor support
Photo 11
26
Screw of
the motor band
Screw of the
damper motor
Screw of the
ground wire
OPERATING PROCEDUREPHOTOS
8. Removing the pipe temperature detection
(liquid and gas) thermistors and room temperature
thermistor
(1) Remove the panel. (Refer to 1.)
(2) Remove the screw of the electrical cover, and then the
electrical cover. (See photo 3)
(3) Remove the pipe temperature detection (liquid and gas)
thermistors from the holders.
(4) Disconnect the connector CN44 on the indoor controller
board.
(5) Loosen the room temperature thermistor wire clamp under
the electrical box.
(6) Disconnect the connector CN20 on the indoor controller
board.
9. Removing the heat exchanger and linear expansion
valve
(1) Remove the panel. (Refer to 1.)
(2) Remove the hair pin cover and water cover (See Photo 3.)
(3) Remove the 2 screws of the heat exchanger.
(See Photo 14.)
(4) Unhook the heat exchanger from 2 catches (electrical box
side).
(5) Pull out the heat exchanger and linear expansion valve.
Photo 12
Thermistor
(Gas/TH23)
Photo 13
Thermistor
(Liquid/TH22)
Room temperature
thermistor (TH21)
27
Heat exchanger
Photo 14
Screws of the
heat exchanger
Hair pin cover
12RoHS PARTS LIST
12-1. INDOOR UNIT ELECTRICAL PARTS AND FUNCTIONAL PARTS
12-1. INDOOR UNIT ELECTRICAL PARTS AND FUNCTIONAL PARTS
Part number that is circled is not shown in the illustration.
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
Part No.
RoHS
G
T7W E00 530
G
T7W E07 002
G
T7W E06 002
G
T7W E01 103
G
T7W E00 103
G
T7W E01 530
G
T7W E08 223
G
T7W E09 130
G
T7W E00 170
G
T7W E00 272
G
T7W E03 527
G
R01 E09 527
G
T7W E08 002
G
T7W E04 114
G
T7W E26 762
G
T7W E00 105
G
T7W E08 130
G
T7W E25 762
G
R01 E27 246
G
R01 H18 202
G
R01 H08 202
G
T7W E37 716
G
T7W E55 310
G
T7W E80 310
G
T7W E01 294
G
T7W E07 223
G
T7W E03 114
G
R01 E06 239
G
T7W E04 304
Part name
NOZZLE ASSEMBL Y (UPPER)
HORIZONTAL VANE (UPPER)
HORIZONTAL VANE (LOWER)
VANE SLEEVE
BEARING ASSEMBL Y
NOZZLE ASSEMBL Y (LOWER)
DAMPER MOTOR
VANE MOTOR SUPPORT
SM SHAFT
DAMPER LIMIT SWITCH (CLOSE)
DRAIN HOSE
DRAIN HOSE
VANE UNDER
LINE FLOW FAN (LOWER)
INDOOR FAN MOTOR (LOWER)
RUBBER MOUNT (L,R)
MOTOR BAND
INDOOR FAN MOTOR (UPPER)
TERMINAL BLOCK
ROOM TEMPERATURE THERMISTOR
ROOM TEMPERATURE THERMISTOR
TERMINAL BLOCK
INDOOR CONTROLLER BOARD
INDOOR CONTROLLER BOARD
ADDRESS BOARD
VANE MOTOR (SET)
LINE FLOW FAN (UPPER)
FUSE
ADDRESS CABLE
Symbol
in Wiring
Diagram
MV2
LS
MF2
MF1
TB5
TH21
TH21
TB2
I.B
I.B
A.B
MV1
FUSE
Q'ty/unit
PFFY-P20/25/32/40
VKM-E
1
1
1
3
2
1
1
1
1
1
1
1
1
1
2
2
1
1
1
1
1
1
1
1
1
1
VKM-ER1
1
1
1
3
2
1
1
1
1
1
1
1
1
1
2
2
1
1
1
1
1
1
1
1
1
1
Remarks
UP & DOWN
ARW40Y8P30MS
ARW40Z8P30MS
3P (M1, M2, S)
3P (L, N, )
UP&DOWN
6.3A
2929
12-2. STRUCTURAL PARTS
PFFY-P20VKM-E PFFY-P20VKM-ER1
HAIR PIN COVER
INDOOR HEAT EXCHANGER
WATER COVER
PIPE TEMPERATURE THERMISTOR
EXPANSION VALVE
EXPANSION VALVE
Part name
Symbol
in Wiring
Diagram
TH22,TH23
LEV
LEV
Q'ty/unit
PFFY-P20/25/32/40
VKM-EVKM-ER1
1
1
1
1
1
1
1
1
1
1
Remarks
31
TM
HEAD OFFICE : TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
C Copyright 2006 MITSUBISHI ELECTRIC ENGINEERING CO.,LTD
Distributed in Nov. 2008 No. OC404 REVISED EDITION-A PDF 7
Distributed in Jul. 2006 No. OC404 PDF 8
Made in Japan
New publication, effective Nov. 2008
Specifications subject to change without notice.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.