Mitsubishi PEH-5GAK, PEH-6GAK Service Manual

Page 1
TECHNICAL & SERVICE MANUAL
CONTENTS
1.
TYPES OF CONNECTED OUTDOOR UNITS
···2
2. SAFETY FOR USE·······························3
3. SAFETY PRECAUTIONS·····················5
5. SPECIFICATIONS·································9
6. DATA ···················································11
8. WIRING DIAGRAM ·····························20
9.
REFRIGERANT SYSTEM DIAGRAM
······21
10. TROUBLESHOOTING·······················22
11. FUNCTION SETTING·························35
12. SYSTEM CONTROL··························39
13. SERVICE DATA(PARTS NAME)·······47
14. OPTIONAL PARTS····························49
No. HWE07020
Indoor unit
Ceiling Concealed
Series PEH
Remote controller
ON/OFF
TEMP.
SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
[Model name]
PEH-5GAK PEH-6GAK
July 2007
Page 2
2
1
TYPES OF CONNECTED OUTDOOR UNITS
Outdoor Unit List
Indoor unit
PEH-5GAK PUH-5YKSA PEH-6GAK PUH-6YKSA
Outdoor unit Model name
Specification
Standard Model High static pressure motor Steel fan
Model name
PEH-5GAK PEH-6GAK
PEH-5GAK.TH PEH-6GAK.TH
PEH-5GAK.TH-SP PEH-6GAK.TH-SP
PEH-5GAK.TH-MF PEH-6GAK.TH-MF
High static pressure motor/
steel fan
PEH-5GAK.TH-SPMF PEH-6GAK.TH-SPMF
Page 3
3
2
Before conducting installation work, please read this ''SAFETY FOR USE'' carefully
for
correct installation.
Since the caution items shown here contain important description relative to safety, please
observe them without fail.
After reading, please keep it with you together the Instruction Manual, and read it again at the
movement of the unit.
The unit should not be installed by the user.
If the unit is installed improperly, explosion, water leakage, electric shock or fire may be result. Consult your dealer or specialist subcontractor for repair and movement.
For installation, conduct the work correctly by following the Installation Manual.
Improper installation may cause a fire, electrical shock or water leakage.
Install the unit on a spot sufficiently durable against the unit weight.
Insufficient durability can cause an injury by the falling down of unit.
All electric work must be performed by licensed technician, according to local regulations and the instructions given in this manual.
The units should be powered by dedicated power lines. Power lines with insufficient capacity or improper electrical work may result in electric shock or fire.
Use only the specified cables for wiring. The connections must be made secured without tension the terminals.
Improper connection or fastening can cause a fire or electrical shock.
The unit should be installed according to the instructions in order to minimize the risk of damage from earthquakes, typhoons or strong winds.
Improper installation work can cause an injury by the falling down of the unit.
The outdoor unit must be installed on stable, level surface, in a place where there is no accumulation of snow , leaves or rubbish. The outdoor unit should be installed in a location where air and noise emitted by the unit will not disturb the neighbors. The indoor unit should be securely installed.
When installing or relocating the unit, make sure that no substance other than the specified refrigerant enters the refrigerant circuit. Any presence of foreign substance such as air can cause abnormal pressure rise or explosion.
If the unit is loosely mounted, it may fall, and cause injury.
Never repair the unit, remodel or transfer it to another site by yourself.
If they are performed improperly, water leakage, electric shock or fire may result. If you need to have the unit repaired or moved, consult your dealer.
Use only the specified refrigerant (R-22) to charge the refrigerant circuit. Do not mix it with any other refrigerant and do not allow air to remain in the circuit.
Air enclosed in the circuit can cause high pressure resulting in a rupture and other hazards.
Ventilate the room if refrigerant leaks during Installation.
The refrigerant heated generates poisonous gas by decomposition which can cause poisoning.
After completing installation work, make sure that refrigerant gas has not leaked.
If refrigerant gas has leaked and exposed to fan heater, stove, oven and so on, it may generate noxious gases.
Take a proper measure to suppress the critical concentration of refrigerant if leaked when installing the unit in a small room.
The limit density is made not to be exceeded even if the refrigerant leaks by any chance. You are necessary to ventilation measures to prevent the accident. If the refrigerant leaks, hypoxia accident may caused. For the countermeasure to be taken, consult your dealer.
The terminal block cover of unit must be firmly attached to prevent entry of dust and moisture.
Improper mounting of the cover cause electric shock or fire.
Use only optional parts authorised by Mitsubishi Electric.
If the accessories are installed improperly, water leakage, electric shock or fire may result. Ask your dealer or an authorised company to install them.
Erroneous handling gives a high possibility to induce serious results such as
death or heavy injury.
Erroneous handling may induce serious injury depending on the situation.
Warning
Warning
Caution
SAFETY FOR USE
Page 4
4
Caution
Never install on the place where a combustible gas might leak.
The gas may ignite or explode when the gas leaks and collects in surrounding of the unit.
When the unit is installed at telecommunication centers or hospitals, take a proper provision against noise.
The erroneous operation of air conditioner may be induced by inverter equipment, independent power device, medical equipment or communication equipment. While the erroneous operation of medical equipment or communication equipment may caused by the air conditioner.
For special use as for foods, animals/plants, precision equipment or art objects, the applicability should be confirmed beforehand.
As the use for the applications other than that designed originally may result in the deterioration of the quality. Consult your dealer in this regard.
Do not use the unit under a special atmosphere.
Installing the unit at the following places may cause a trouble, a place where much machine oil, salt sonnet, humidity or dust, spa district, a place full of sulfur gas, volatile gas, or corrosive gas, a place near high frequency processing machine.
Thermal insulation of the drain pipes is necessary prevent dew condensation.
If the drain pipes are not properly insulated, condensation will result and drip on ceiling, floor or other possessions.
The drain piping must process by surely,and insulate the drain piping not to be dewy.
When the room humidity exceeds 80% or when the drain pipe is clogged, water may drip from the indoor unit. The outdoor unit produces condensation during the heating operation. Make sure to provide drainage around the outdoor unit if such condensation is likely to cause damage.
Install drain piping according to this Installation Manual to ensure proper drainage. Place thermal insulation on the pipes to prevent condensation.
Improper drain piping may cause water leakage and damage to furniture or other possessions.
The unit must be properly earth connected.
Do not connect the earth wire to gas pipe, city water pipe, lightning rod or telephone earth wire. Improper earth connection may cause electrical shock.
When installing at a watery place, provide an electric leak breaker.
Failure to mount the electric leak breaker may cause electrical shock.
Use breaker or fuse with proper capacity. Make sure that there is a main power switch.
Using a wire or a copper wire instead of proper capacity of fuse can cause fire or trouble. Other appliances connected to the same line could cause an overload.
For the power lines, use standard cables of sufficient current capacity.
Otherwise, current leakage, overheating or fire may occur.
When installing the power lines, do not apply tension to the cables.
The tighten or loosen the connections may cause generate heat and cause fire.
Remote controller is not pushed with the thing sharpening ahead.
It occasionally causes the electric shock and the breakdown.
Arrange the configuration of wiring not to bring up the panel and terminal cover, and fasten the panel and terminal cover securely.
The poor mounting of the panel or terminal cover may cause the heat generation of the terminal connection, a fire or electrical shock.
Do not wash the unit with water.
If washed with water, electrical shock may be caused.
Do not handle the switch with wet hands.
Otherwise electrical shock can be resulted.
Be very careful on handling the unit.
When carrying in outdoor unit, be sure to support it at four points. Carrying in and lifting with 3-point support may make outdoor unit unstable, resulting in a fall of it. The unit should not be carried by only one person if it is more than 20kg. Some units use PP bands for packing. Do not use any PP band for delivery purpose. Do not touch the heat exchanger fins with your bear hands. Doing so may cut your hands. Be sure to safely dispose the packaging materials. Packaging materials, such as catches and other metal or wooden parts, may cause stabs or other injuries. Tear off and discard plastic packing bags so that children will not play any of them. If children play with a plastic bag which was not torn off, it may cause a risk of suffocation.
Do not leave the mounting base being damaged.
The damaged base may cause the falling down of the unit which may give injury.
Turn on the main power switch more than 6 hours before starting operation.
Do not turn the main power switch OFF during seasons of heavy use, doing so can result in failure.
Do not touch the compressor or refrigerant piping without wearing glove on your hands.
Touching directly such part can cause a burn or frostbite as it becomes high or low temperature according to the refrigerant state.
Do not touch the metal edges inside the unit without wearing glove on your hands.
Touching directly it may injure your hands.
Do not remove the panel or the fan guard from the outdoor unit when it is running.
You could be injured if you touch rotating, hot or high­voltage parts.
Do not operate the air conditioner without the air filter set place.
Dust may accumulate, and cause a failure.
At emergency (if you smell something burning), stop operation and turn the power source switch off.
Continuing the operation without eliminating the emergency state may cause a machine trouble, fire, or electrical shock.
After stopping operation, be sure to wait for five minutes before turning off the main power switch.
Otherwise, water leakage or unit failure may occur.
Remote controller is not installed for the place where direct sunshine strikes.
Page 5
5
3
SAFETY PRECAUTIONS
3.1. Before installation and electric work
s Before installing the unit, make sure y ou read all the “Safety
precautions”.
s The “Safety precautions provide very important points re-
garding safety. Make sure you follow them.
Symbols used in the text
Warning:
Describes precautions that should be observed to prevent danger of injury or death to the user.
Caution:
Describes precautions that should be observed to prevent damage to the unit.
Symbols used in the illustrations
: Indicates an action that must be avoided. : Indicates that important instructions must be followed. : Indicates a part which must be grounded. : Beware of electric shock. <Color: yellow>
Warning:
Carefully read the labels affixed to the unit.
Warning:
Ask the dealer or an authorized technician to install the air conditioner.
- Improper installation by the user may result in water leakage, electric shock, or fire.
Install the unit at a place that can withstand its weight.
- Inadequate strength may cause the unit to fall down, resulting in injuries.
Use the specified cables for wiring. Make the connections securely so that the outside force of the cable is not applied to the terminals.
- Inadequate connection and fastening may generate heat and cause a fire.
Prepare for strong winds and earthquakes and install the unit at the speci­fied place.
- Improper installation may cause the unit to topple and result in injury.
Always use an filter and other accessories specified by Mitsubishi Elec­tric.
- Ask an authorized technician to install the accessories. Improper installation
by the user may result in water leakage, electric shock, or fire.
Never repair the unit. If the air conditioner must be repaired, consult the dealer.
- If the unit is repaired improper ly, water leakage, electric shock, or fire may
result.
Do not touch the heat exchanger fins and metal edges.
- Improper handling may result in injury.
If refrigerant gas leaks during installation work, ventilate the room.
- If the refrigerant gas comes into contact with a flame, poisonous gases will
be released.
Install the air conditioner according to this Installation Manual.
- If the unit is installed improper ly, water leakage, electric shock, or fire may
result.
Have all electric work done by a licensed electrician according to Elec- tric Facility Engineering Standard” and Interior Wire Regulations”and the instructions given in this manual and always use a special circuit.
- If the power source capacity is inadequate or electric work is performed im-
properly, electric shock and fire may result.
Securely install the terminal cover (panel).
- If the terminal cover (panel) is not installed properly, dust or water may enter
the outdoor unit and fire or electric shock may result.
When installing and moving the air conditioner to another site, do not charge the it with a refrigerant different from the refrigerant (R22) speci­fied on the unit.
- If a different refrigerant or air is mixed with the original refrigerant, the refrig-
erant cycle may malfunction and the unit may be damaged.
If the air conditioner is installed in a small room, measures must be taken to prevent the refrigerant concentration from exceeding the safety limit even if the refrigerant should leak.
- Consult the dealer regarding the appropriate measures to prev ent the saf ety
limit from being exceeded. Should the refrigerant leak and cause the safety limit to be exceeded, hazards due to lack of oxygen in the room could result.
When moving and reinstalling the air conditioner, consult the dealer or an authorized technician.
- If the air conditioner is installed improperly, water leakage, electric shock, or
fire may result.
After completing installation work, make sure that refrigerant gas is not leaking.
- If the refr igerant gas leaks and is exposed to a fan heater, stove, oven, or
other heat source, it may generate noxious gases.
Do not reconstruct or change the settings of the protection devices.
- If the pressure switch, thermal switch, or other protection device is shorted and operated forcibly, or parts other than those specified by Mitsubishi Elec­tric are used, fire or explosion may result.
To dispose of this product, consult your dealer.
The installer and system specialist shall secure safety against leakage
according to local regulation or standards.
- Following standards may be applicable if local regulation are not available.
Pay a special attention to the place, such as a basement, etc. where re­frigeration gas can stay, since refrigeration is heavier than the air.
The appliance is not intended for use by young children or infirm per­sons without supervision.
Young children should be supervised to ensure that they do not play with the appliance.
Never operate in open phase condition. Control box may be broken.
3.2. Before Installation
Caution:
Do not install the unit where combustible gas may leak.
- If the gas leaks and accumulates around the unit, an explosion may result.
Do not use the air conditioner where food, pets, plants, precision instru­ments, or artwork are kept.
- The quality of the food, etc. may deteriorate.
Do not use the air conditioner in special environments.
- Oil, steam, sulfur ic smoke, etc. can significantly reduce the performance of
the air conditioner or damage its parts.
When installing the unit in a hospital, communication station, or similar place, provide sufficient protection against noise.
- The inverter equipment, pr ivate power generator, high-frequency medical
equipment, or radio communication equipment may cause the air conditioner to operate erroneously, or fail to operate. On the other hand, the air condi­tioner may affect such equipment by creating noise that disturbs medical treatment or image broadcasting.
Do not install the unit on a structure that may cause leakage.
- When the room humidity exceeds 80 % or when the drain pipe is clogged,
condensation may drip from the indoor unit. P erform collective drainage work together with the outdoor unit, as required.
3.3. Before Installation (moved) - electrical
work
Caution:
Ground the unit.
- Do not connect the ground wire to gas or water pipes, lightning rods, or
telephone ground lines. Improper grounding may result in electric shock.
The reverse phase of L lines (L
1, L2, L3) can be detected (Error cord: 4103),
but the reverse phase of L lines and N line can be not be detected.
- Some electr ic par ts should be damaged when power is supplied under the
miss wiring.
Install the power cable so that tension is not applied to the cable.
- Tension may cause the cable to break and generate heat and cause a fire.
Install an leak circuit breaker, as required.
- If an leak circuit breaker is not installed, electric shock may result.
Use power line cables of sufficient current carrying capacity and rating.
- Cables that are too small may leak, generate heat, and cause a fire.
Use only a circuit breaker and fuse of the specified capacity.
- A fuse or circuit breaker of a larger capacity or a steel or copper wire may
result in a general unit failure or fire.
Do not wash the air conditioner units.
- Washing them may cause an electric shock.
Be careful that the installation base is not damaged by long use.
- If the damage is left uncorrected, the unit may fall and cause personal injury
or property damage.
Install the drain piping according to this Installation Manual to ensure proper drainage. Wrap thermal insulation around the pipes to prevent condensation.
- Improper drain piping may cause water leakage and damage to furniture
and other possessions.
Be very careful about product transportation.
- Only one person should not carry the product if it weighs more than 20 kg.
- Some products use PP bands for packaging. Do not use any PP bands for a
means of transportation. It is dangerous.
- Do not touch the heat exchanger fins. Doing so may cut your fingers.
- When transporting the outdoor unit, suspend it at the specified positions on
the unit base. Also support the outdoor unit at four points so that it cannot slip sideways.
Safely dispose of the packing materials.
- Packing materials, such as nails and other metal or wooden parts, may cause
stabs or other injuries.
- Tear apart and throw away plastic packaging bags so that children will not
play with them. If children play with a plastic bag which was not torn apart, they face the risk of suffocation.
Page 6
6
Remote controller is not allowed to install for the place where direct sunshine strikes.
3.4. Before starting the test run
Caution:
Turn on the power at least 12 hours before starting operation.
- Starting operation immediately after turning on the main power switch can
result in severe damage to internal parts. Keep the power switch turned on during the operational season.
Do not touch the switches with wet fingers.
- Touching a switch with wet fingers can cause electric shock.
Do not touch the refrigerant pipes during and immediately after opera­tion.
- During and immediately after operation, the refrigerant pipes are may be
hot and may be cold, depending on the condition of the refrigerant flowing through the refrigerant piping, compressor, and other refrigerant cycle parts. Your hands may suffer burns or frostbite if you touch the refrigerant pipes.
Do not operate the air conditioner with the panels and guards removed.
- Rotating, hot, or high-voltage parts can cause injuries.
Do not turn off the power immediately after stopping operation.
- Always wait at least five minutes before turning off the power. Otherwise,
water leakage and trouble may occur.
Do not operate the air conditioner without the air filter set place.
- Dust may accumulate, and cause a failure.
At emergency (if you smell something burning), stop operation and turn the power source switch off.
- Continuing the operation without eliminating the emergency state may cause
a machine trouble, fire, or electric shock.
Remote controller should be pushed with finger.
- It occasionally causes the electric shock and the breakdown.
Page 7
7
PART NAMES AND FUNCTIONS
4
Indoor (Main) Unit
Air intake duct flange
Air outlet duct flange
Air outlet
Air intake (sucks the air inside the room into the unit)
Remote controller
Once the controls are set, the same operation mode can be repeated by simply pressing the ON/OFF button.
Operation buttons
PAR-21MAA
ON/OFF
FILTER
CHECK
OPERATION
CLEAR
TEST
TEMP.
MENU
BACK DAY
MONITOR/SET
CLOCK
ON/OFF
Set Temperature buttons
Down
Up
Timer Menu button (Monitor/Set button)
Mode button (Return button)
Set Time buttons
Back
Ahead
Timer On/Off button (Set Day button)
Opening the door.
ON/OFF button
Fan Speed button
Filter button (<Enter> button)
Test Run button
Check button (Clear button)
Airflow Up/Down button
Louver button (
Operation button)
To preceding operation number.
Ventilation button (
Operation button)
To next operation number.
Page 8
8
Display
For purposes of this explanation, all parts of the display are shown as lit. During actual operation, only the relevant items will be lit.
˚F˚C
˚F˚C
ERROR CODE
AFTER
TIMER
TIME SUN MON TUE WED THU FRI SAT
ON OFF
Hr AFTER
FILTER
FUNCTION
ONLY1Hr.
WEEKLY
SIMPLE
AUTO OFF
Identifies the current operation
Shows the operating mode, etc. * Multilanguage display is sup-
ported.
Centrally Controlled indicator
Indicates that operation of the re­mote controller has been prohib­ited by a master controller.
Timer Is Off indicator
Indicates that the timer is off.
Temperature Setting
Shows the target temperature.
Day-of-Week
Shows the current day of the week.
Time/Timer Display
Shows the current time, unless the simple or Auto Off timer is set. If the simple or Auto Off timer is set, shows the time remaining.
Sensor indication
Displayed when the remote controller sensor is used.
Locked indicator
Indicates that remote controller but­tons have been locked.
Clean The Filter indicator
Comes on when it is time to clean the filter.
Timer indicators
The indicator comes on if the corre­sponding timer is set.
Up/Down Air Direction indica­tor
The indicator shows the direc­tion of the outcoming airflow.
One Hour Only indicator
Displayed if the airflow is set to weak and downward during COOL or DRY mode. (Operation varies according to model.) The indicator goes off after one hour, at which time the airflow di­rection also changes.
Room Temperature display
Shows the room temperature.
Louver display
Indicates the action of the swing louver. Does not appear if the louver is stationary.
(Power On indicator)
Indicates that the power is on.
Fan Speed indicator
Shows the selected fan speed.
Ventilation indicator
Appears when the unit is running in Ventilation mode.
Caution
Only the Power on indicator lights when the unit is stopped and power supplied to the unit.
If you press a button for a feature that is not installed at the indoor unit, the remote controller will display the Not Available
message. If you are using the remote controller to drive multiple indoor units, this message will appear only if he feature is not present at the parent unit.
When power is turned ON for the first time, it is normal that “PLEASE WAIT is displayed on the room temperature indica- tion (For max. 2minutes). Please wait until this PLEASE WAIT indication disappear then start the operation.
Page 9
9
5 SPECIFICATIONS
Item
Function
Model name
Gross Net Net Gross Net Net
PEH-5GAK
Cooling Cooling
Btu/h 44,000 41,000 46,000 54,000 51,000 62,000
Capacity *1
kW 12.9 12.0 13.5 15.8 14.9 18.2
kcal/h 11,000 10,300 11,600 13,500 12,800 15,600 Total input EER COP
Model name
Power supply(phase,cycle,voltage)
Input Running current
Starting current External finish Heat exchanger
×
Fan(drive)
No.
Fan motor output
Fan
INDOOR UNIT
Airflow
External static pressure Operation control & Thermostat
Cond. Drain connection O.D.
Dimensions
Weight
Model name
Power supply(phase,cycle,voltage)
Input
Running current
Starting current External finish Refrigerant control Compressor
Model
Motor output
Starter type
Protection devices
Heat exchanger
×
No.
Fan
Fan(drive)
Fan motor output
Airflow Defrost method
Noise level
Dimensions
Weight Refrigerant
Charge
Pipe size O.D.
Connection method Between the indoor &
outdoor unit
REFRIGERANT PIPING OUTDOOR UNIT
kW 5.03 5.45
kcal/h.W 2.16 2.02 2.30 2.41 2.28 2.86
W/W 2.53 2.36 2.68 2.82 2.66 3.33
kW
A A
kW
Hi
Lo
CMM
L/s
CMM
L/s Pa
mmAq
Hi Lo
dB(A)Noise level
Hmm
Wmm
Dmm
kg
lbs
kW 4.16 4.58
A 6.81 7.50 A5374
kW
kW
3
m
/min
L/s
dB(A) 55 56
Hmm
Wmm
Dmm
kg
lbs
kg
lbs Liquid mm Gas mm Indoor side Outdoor side Height difference Piping length
5.08
PEH-5GAK PEH-6GAK
~ 50Hz 220-240V ~ 50Hz 220-240V
0.87
4.0
6.1
Galvanized steel
Cross fin coil
Centrifugal (direct)
×
0.46 50
833
40
667 100
10
Remote control & built in
46 42 R1
400
1180
634
56
123
PUH-5YKSA
3PH 4W 50Hz 380-415V
4.21
6.89 53
Munsell 3Y 7.8/1.1
Capillary tube
Hermetic
ZR61KC-TFD
3.5
Line start
Thermal relay, Thermal switch
HP switch, Anti-phase protector
Cross fin coil
Propeller(direct)
0.085
×
2
×
2
95
1,583
Reverse cycle
55
1258
970
345+24
117 257
R-22
5.4
11.9
9.52
19.05 Flared Flared
Max. 50m Max. 50m
*1 Rating condition 2. Guaranteed operating range
Cooling·····Indoor unit D.B. 27˚C, W.B. 19˚C
Outdoor unit D.B. 35˚C
Heating·····Indoor unit D.B. 20˚C
Outdoor unit D.B. 7˚C, W.B. 6˚C
Cooling Heating
Upper limit Lower limit Upper limit Lower limit
Refrigerant piping length (one way): 5m 3. Above data based on indicated voltage
Indoor unit: 1 phase 240V 50Hz Outdoor unit: 3 phase 415V 50Hz
PEH-6GAK
Heating Heating
5.60
0.87
4.0
6.1
Galvanized steel
Cross fin coil
1
Centrifugal (direct) ×1
0.46 55
917
44
733 100
10
Remote control & built in
49 45
R1
400
1180
634
59
130
PUH-6YKSA
3PH 4W 50Hz 380-415V
4.73
7.74 74
Munsell 3Y 7.8/1.1
Capillary tube
Hermetic
ZR68KC-TFD
4.0
Line start
Thermal relay, Thermal switch
HP switch, Anti-phase protector
Cross fin coil
×
Propeller(direct)
0.10
2
×
2
100
1,666
Reverse cycle
56
1258
970
345+24
117 257
R-22
5.0
11.0
9.52
19.05 Flared Flared
Max. 50m Max. 50m
Indoor D.B. 35˚C, W.B. 22.5˚C D.B. 21˚C, W.B. 15.5˚C
D.B. 27˚C D.B. 20˚C
Outdoor D.B. 46˚C D.B. -5˚C
D.B. 21˚C, W.B. 15.5˚C
D.B. -8.5˚C, W.B. -9.5˚C
Page 10
10
Item
Function
Model name
<With a high static pressure motor>
Gross Net Net Gross Net Net
PEH-5GAK
Cooling Cooling
Btu/h 44,000 41,000 46,000 54,000 51,000 62,000
Capacity 1
kW 12.9 12.0 13.5 15.8 14.9 18.2
kcal/h 11,000 10,300 11,600 13,500 12,800 15,600 Total input EER COP
kW 5.03 5.45
kcal/h.W 2.16 2.02 2.30 2.41 2.28 2.86
W/W 2.53 2.36 2.68 2.82 2.66 3.33
Model name
Power supply(phase,cycle,voltage)
Input Running current Starting current
kW
A
A External finish Heat exchanger
Fan(drive)×No. Fan motor output
Fan
INDOOR UNIT
Airflow
External static pressure
Hi
Lo
kW
CMM
L/s
CMM
L/s
Pa
mmAq
Operation control & Thermostat Noise level
Hi Lo
dB(A)
Cond. Drain connection O.D.
Hmm
Dimensions
Wmm
Dmm
Weight
kg
lbs
Model name
Power supply(phase,cycle,voltage)
Input Running current Starting current
kW 4.16 4.58
A 6.81 7.50
A5374 External finish Refrigerant control Compressor
Model Motor output
kW
Starter type Protection devices
Heat exchanger
Fan(drive)×No.
Fan
Fan motor output Airflow
kW
3
m
/min
L/s Defrost method Noise level
dB(A) 55 56
Hmm
Dimensions
Wmm
Dmm
Weight
kg
lbs Refrigerant
Charge
Pipe size O.D.
Connection method Between the indoor &
REFRIGERANT PIPING OUTDOOR UNIT
outdoor unit
*1 Rating condition 2. Guaranteed operating range
Cooling·····Indoor unit D.B. 27˚C, W.B. 19˚C Heating·····Indoor unit D.B. 20˚C Refrigerant piping length (one way): 5m
Outdoor unit D.B. 35˚C Outdoor unit D.B. 7˚C, W.B. 6˚C
Liquid mm Gas mm Indoor side Outdoor side Height difference Piping length
kg
lbs
3. Above data based on indicated voltage Indoor unit: 1 phase 240V 50Hz Outdoor unit: 3 phase 415V 50Hz
5.08 5.60
PEH-5GAK PEH-6GAK
~ 50Hz 220-240V ~ 50Hz 220-240V
0.87 0.87
4.0 4.0
7.8 7.8
Galvanized steel Galvanized steel
Cross fin coil Cross fin coil
Centrifugal (direct) ×1 Centrifugal (direct) ×1
0.54 0.54 50 55
833 917
40 44
667 733 150 150
15 15
Remote control & built in Remote control & built in
48 51 45 48
R1 R1
400 400
1180 1180
634 634
56 59
123 130
PUH-5YKSA PUH-6YKSA
3PH 4W 50Hz 380-415V 3PH 4W 50Hz 380-415V
4.21 4.73
6.89 7.74 53
Munsell 3Y 7.8/1.1 Munsell 3Y 7.8/1.1
Capillary tube Capillary tube
Hermetic Hermetic
ZR61KC-TFD ZR68KC-TFD
3.5 4.0
Line start Line start
Thermal relay, Thermal switch
HP switch, Anti-phase protector
Cross fin coil Cross fin coil
Propeller(direct)×2 Propeller(direct)×2
0.085×20.10×2 95 100
1,583 1,666
Reverse cycle Reverse cycle
55 56
1258 1258
970 970
345+24 345+24
117 117 257 257
R-22 R-22
5.4 5.0
11.9 11.0
9.52 9.52
19.05 19.05 Flared Flared Flared Flared
Max. 50m Max. 50m Max. 50m Max. 50m
Cooling Heating
Upper limit Lower limit Upper limit Lower limit
<With a high static pressure motor>
PEH-6GAK
Heating Heating
74
Thermal relay, Thermal switch
HP switch, Anti-phase protector
Indoor D.B. 35˚C, W.B. 22.5˚C D.B. 21˚C, W.B. 15.5˚C
D.B. 27˚C D.B. 20˚C
Outdoor
D.B. 46˚C
D.B. -5˚C
D.B. 21˚C, W.B. 15.5˚C
D.B. -8.5˚C, W.B. -9.5˚C
Page 11
11
DATA
6
6-1. PERFORMANCE DATA
1) COOLING CAPACITY
Note:C A : Capacity (W)
P.C. : Power consumption (kW)
Cooling capacity correction factors
Indoor
Model name
PEH-5GAK
PEH-6GAK
Intake
air W.B.˚C CA P.C. CA P.C. CA P.C. CA P.C. CA P.C. CA P.C.
16 13,014 4.07 12,658 4.25 12,193 4.57 11,699 4.90 11,176 5.23 10,624 5.56 18 13,857 4.15 13,492 4.33 13,000 4.68 12,485 5.02 11,945 5.36 11,381 5.71 20 14,708 4.23 14,363 4.42 13,850 4.78 13,315 5.14 12,759 5.51 12,180 5.88 22 15,569 4.31 15,270 4.51 14,741 4.88 14,191 5.26 13,618 5.66 13,023 6.07 16 15,940 4.49 15,503 4.68 14,934 5.04 14,329 5.40 13,688 5.77 13,013 6.13 18 16,972 4.58 16,525 4.78 15,923 5.15 15,291 5.53 14,630 5.91 13,939 6.29 20 18,015 4.67 17,591 4.87 16,963 5.27 16,309 5.67 15,627 6.07 14,918 6.48 22 19,069 4.75 18,703 4.97 18,055 5.38 17,381 5.80 16,679 6.24 15,950 6.70
Model name
PEH-5GAK PEH-6GAK
20 25 30 35 40
5m
1.00
1.00
10m
0.981
0.975
15m
0.968
0.955
Outdoor intake air D.B.˚C
Refrigerant piping length (one way)
20m
0.952
0.935
25m
0.940
0.918
30m
0.925
0.99
35m
0.913
0.884
40m
0.900
0.869
45m
0.886
0.855
45
50m
0.874
0.840
Page 12
12
Heating
1.4
1.2
1.0
0.8
0.6
1.4
1.2
1.0
0.8
0.6
0.4
-12-10 -5 0 5 10 15 OUTDOOR W.B.(°C)
INDOOR D.B. (°C)
INDOOR D.B. (°C)
15 20 25
25 20 15
TOTAL INPUT (RATIO) CAPACITY (RATIO)
Cooling
1.4
1.2
1.0
0.8
0.6
1.4
1.2
1.0
0.8
0.6
0.4
-5 5 15 253546 OUTDOOR D.B.(°C)
TOTAL INPUT (RATIO) CAPACITY (RATIO)
INDOOR W.B.(°C)
INDOOR W.B.(°C)
22 20 18 16
22 20 18 16
6-2. PERFORMANCE CURVE
2) HEATING CAPACITY
Note:C A : Capacity (W)
P.C. : Power consumption (kW)
Heating capacity correction factors
Model name
Intake
air D.B.
˚C
-10 -5 0 5 10 15
CA P.C. CA P.C. CA P.C. CA P.C. CA P.C. CA P.C.
15 9,245 3.43 10,596 3.79 12,077 4.18 13,686 4.58 15,421 5.01 17,280 5.47
Indoor
PEH-5GAK
20 8,852 3.70 10,180 4.09 11,621 4.50 13,176 4.94 14,842 5.40 16,617 5.89 25 8,507 3.93 9,766 4.36 11,160 4.81 12,688 5.29 14,349 5.79 16,141 6.31 15 12,464 3.72 14,284 4.11 16,281 4.53 18,451 4.97 20,790 5.43 23,297 5.92
PEH-6GAK
20 11,934 4.01 13,724 4.43 15,667 4.88 17,763 5.35 20,009 5.85 22,403 6.38 25 11,469 4.25 13,166 4.72 15,045 5.21 17,105 5.73 19,344 6.27 21,761 6.84
Service Ref.
PEH-5GAK PEH-6GAK
5m
1.00
1.00
10m
1.00
1.00
15m
1.00
1.00
Outdoor intake air W.B.
Refrigerant piping length (one way)
20m
1.00
1.00
25m
1.00
1.00
30m
1.00
1.00
35m
0.998
0.998
˚C
40m
0.995
0.995
45m
0.993
0.993
50m
0.990
0.990
Page 13
13
6-3. FAN PERFORMANCE AND CORRECTED AIR FLOW
(1) PEH-5GAK
(2) PEH-6GAK
300
250
200
Hi
150
100
External static pressure (Pa)
50
0
35.0 40.0 45.0 50.0 55.0
1.1
1.0
Capacity/ input factor
0.9 35 40 45 50 55
300
Lo
Air flow
Cooling
(CMM)
Capacity input
1.1
Heating
Capacity input
1.0
Capacity/ input factor
0.9
Air flow
(CMM)
35 40 45 50 55
Air flow rate
(CMM)
250
200
150
100
External static pressure (Pa)
50
0
Lo
40.0 45.0 50.0 55.0 60.0
Hi
Air flow
Cooling
1.1
1.0
Capacity/ input factor
0.9 40 45 50 55 60
Air flow
(CMM)
Capacity input
(CMM)
Heating
1.1
1.0
Capacity/ input factor
0.9 40 45 50 55 60
Air flow
Capacity input
(CMM)
Page 14
14
(3) PEH-5GAK (With a high static pressure motor)
(4) PEH-6GAK (With a high static pressure motor)
300
250
200
150
100
External static pressure (Pa)
50
0
35.0 40.0 45.0 50.0 55.0
Lo
Air flow
Hi
Cooling
1.1
1.0
Capacity/ input factor
0.9 35 40 45 50 55
Air flow
(CMM)
Capacity input
(CMM)
Heating
1.1
1.0
Capacity/ input factor
0.9 35 40 45 50 55
Air flow rate
Capacity
input
(CMM)
300
250
200
150
100
External static pressure (Pa)
50
0
40.0 45.0 50.0 55.0 60.0
Lo
Air flow
1.1
1.0
Capacity/ input factor
0.9 40 45 50 55 60
Hi
Cooling
Air flow
(CMM)
Capacity input
(CMM)
Heating
1.1
1.0
Capacity/ input factor
0.9 40 45 50 55 60
Air flow
Capacity input
(CMM)
Page 15
15
6-4. ELECTRICAL DATA
Indoor unit········240V 50Hz 1phase Outdoor unit ·····415V 50Hz 3phase
Indoor unit
Outdoor unit
PEH-5GAK
PUH-5YKSA
PEH-6GAK
PUH-6YKSA
PEH-5GAK
<With a high static pressure motor>
PUH-5YKSA PUH-6YKSA
<With a high static pressure motor>
PEH-6GAK
Mode Capacity (GROSS) Capacity (NET) Total input
Input kW 0.87 0.87 0.87 0.87 0.87 0.87 0.87 0.87 Current A 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 Starting current A 6.1 6.1 6.1 6.1 7.8 7.8 7.8 7.8
Indoor unit
Input kW 4.21 4.16 4.73 4.58 4.21 4.16 4.73 4.58 Current A 6.89 6.81 7.74 7.50 6.89 6.81 7.74 7.50 Starting current A 53 53 74 74 53 53 74 74
Outdoor unit
kW 12.9 - 15.8 - 12.9 - 15.8 ­kW 12.0 13.5 14.9 18.2 12.0 13.5 14.9 18.2 kW 5.08 5.03 5.60 5.45 5.08 5.03 5.60 5.45
Cool Heat Cool Heat Cool Heat Cool Heat
Page 16
16
6-5. STANDARD OPERATION DATA
The unit of pressure has been changed to MPa based on SI (International System of Units) in accordance with I.S.O. (International Organization for Standardization).
The conversion factor is : 1(MPa) =10.2 (OOf/FF)
Mode
Capacity (GROSS) Capacity (NET)
Total
Input
Indoor unit
Phase, Hz Volts Amperes
Outdoor unit
Phase, Hz
Electrical circuit
Volts Amperes Discharge Pressure Suction Pressure Discharge temp. Suction temp.
Refrigerant circuit
Ref. pipe length Indoor intake air temp. Outdoor intake air temp.
Model name
D.B. W.B. D.B. W.B.
SHF
BF
PEH-6GAKPEH-5GAK
Cooling Heating Cooling Heating Cooling Heating Cooling Heating kW 12.9 - 15.8 - 12.9 - 15.8 ­kW 12.0 13.5 14.9 18.2 12.0 13.5 14.9 18.2 kW 5.08 5.03 5.60 5.45 5.08 5.03 5.60 5.45
PEH-5GAK
1, 50 V A 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0
V A 6.89 6.81 7.74 7.50 6.89 6.81 7.74 7.50
MPa 1.91 2.02 1.95 1.92 1.91 2.02 1.95 1.92
2
kgf/cm
MPa 0.43 0.33 0.43 0.34 0.43 0.33 0.43 0.34
2
kgf/cm
˚C ˚C
m 5555 5 5 5 5
˚C ˚C ˚C ˚C
240
PUH-5YKSA PUH-6YKSA
3, 50 3, 50
415
19.5 20.6 19.9 19.6 19.5 20.6 19.9 19.6
4.4 3.4 4.4 3.5 4.4 3.4 4.4 3.5 76 84 77 79 76 84 77 79
4 -2 4 -3 4 -2 4 -3
27 20 27 20 27 20 27 20 19 15 19 15 19 15 19 15 35 7 35 7 35 7 35 7 24 6 24 6 24 6 24 6
0.82 - 0.82 - 0.82 - 0.82 -
0.27 - 0.19 - 0.27 - 0.19 -
PEH-6GAK
1, 50
240
415
PEH-5GAK PEH-6GAK
<With a high static pressure motor> <With a high static pressure motor>
PEH-5GAK PEH-6GAK
<With a high static pressure motor> <With a high static pressure motor>
1, 50 1, 50
240 240
PUH-5YKSA PUH-6YKSA
3, 50 3, 50
415 415
Page 17
17
PEH-5,6: Upper High/Lower Low
SPL
dB(A) 63Hz 125Hz 250Hz 500Hz 1000Hz 2000Hz 4000Hz 8000Hz
46 50 49 46 44 42 38 28 22 42 44 44 41 40 38 34 23 15 49 54 53 51 47 43 34 29 25 45 51 51 47 44 40 31 25 21 48 52 51 48 46 44 40 30 24 45 47 47 44 43 41 37 26 18 51 55 54 51 49 47 43 33 27 48 50 50 47 46 44 40 29 21
1) Sound Levels
PEH-5GAK
PEH-6GAK
PEH-5GAK (High static pressure motor)
PEH-6GAK (High static pressure motor)
6-6. SOUND DATA
Model
Position measurement
Indoor unit
2m
Outlet
OCTAVE BAND FREQ.Hz
1m
Inlet
1.5m
Measurement point
Page 18
18
OUTLINES AND DIMENSIONS
7
7-1. INDOOR UNITS
PEH-5GAK, PEH-6GAK
Unit : mm
Return air
duct flange
34124
51
10
130
3 Holes
882
6X130(=780)51
20-
199
20
1080
200
131
3.1 Holes 14-
12 Holes 4-
For hanging bolt M10
[Field supply]
10
55
130
3X130(=390)
Top view
55
Supply air
duct flange
1180
1120
11 250 95
1064
Front view
361 500 179
42
2pcs.
62
1pc.
20
462
Control box
Remote
Rubber bush
controller wiring
40
70 1295575
Outdoor unit
Rubber bush
connection wiring
Rubber bush
A
Power supply
wiring
<
40 1040 40
54
10
634
530
50
10
Return air
sensor
400
376
2510010025
262 73
35
130
144
22330
Supply air
A
130
145
35
56539
Drain R1
89
Refrigerant pipe
Left side view
9.52 (3/8 flare)
Accessory
Pipe cover
(For dew condensation prevention of
local piping and unit connection.)
Remote controller
19.05 (3/4 flare)
Refrigerant pipe
Return air
Page 19
19
Unit : mm
7-2. REMOTE CONTROLLER
130
120
19
Page 20
20
WIRING DIAGRAM
8
PEH-5GAK, PEH-6GAK
ROOM TEMP
LIQUID PIPE TEMP
OVER CURRENT RELAY (INDOOR FAN MOTOR)
THERMISTOR
MAGNETIC CONTACTOR (INDOOR FAN MOTOR)
TERMINAL BLOCK
52F
51F
TH1
TB2,4,5
TH2
MF1 FAN MOTOR (INDOOR)
SYMBOL NAME
INDOOR UNIT
CONNECTOR (LOSSNAY)
CONNECTOR (REMOTE SWITCH)
CONNECTOR (HA TERMINAL-A)
CONNECTOR (CENTRALLY CONTROL)
AUXILIARY RELAY (INDOOR FAN MOTOR<HIGH SPEED>)
AUXILIARY RELAY (INDOOR FAN MOTOR<LOW SPEED>)
CAPACITOR
C
X1Lo
FUSE (T6.3AL250V)
FERRITE CORE
SURGE KILLER
FUSE
FB
CR
X2Hi
INDOOR
VARISTOR
AUXILIARY RELAY
SWITCH (MODEL SELECTION)
SWITCH (SYSTEM SELECTION)
ZNR
X4-6
SW5
SW1
CONTROLLER
BOARD
LED (POWER SUPPLY <REMOTE CONTROLLER>)
SWITCH (EMERGENCY OPERATION)
CONNECTOR (EMERGENCY OPERATION)
LED (POWER SUPPLY)
CN2L
SWE
LED1
LED2
SW6
CN31 CONNECTOR (DRAIN SENSOR)
CONNECTOR (WIRELESS REMOTE CONTROLLER)
CN32
CN41
CN51
CN90
NAME
ARRESTER
VARISTOR
DSA,DSR
ZNR5~7
SYMBOL
SNB BOARD 1
REMOTE CONTROLLER
TERMINAL BLOCK
TB6
1. The dotted lines show field wiring.
Note:
polarities,make sure matching wiring and terminal.
If a trouble occurs with either the remote controller or the
2. Color of earth wire is yellow and green twisting.
3. Specification subject to change without notice.
4. Indoor and outdoor connecting wires are made with
BOARD
REMOTE CONTROLLER
indoor microcom-puter and no other trouble exists, emergency
5. Emergency operation
LCD
TB6
SWE :ON / Indoor fan is running high speed.
operation for cooling or heating can be performed by changing
the setting of connector (SWE) and switch (SW6) on the indoor
controller board.
REMOTE CONTROLLER
SW6-1 :ON / Emargency operation of cooling mode.
SW6-1,2 :ON / Emargency operation of heating mode.
6. mark is connector. mark is terminal.
is installed.
Therefore, do not change factory set value of over current
relays.
1. To protect fan motor from abnormal current,over current relays
7. This motor(*1) includes auto reset type internal thermostat.
Caution,
OUTDOOR UNIT
C
5
6
MF1
124
C01
X2Hi
X1Lo
51F52F
RED
REDL1
WHITE
TB2
INDOOR UNIT
L2L3N
(*1)
BLACK
BLUE
GREEN/YELLOW
DSA DSR
ZNR5~7
SNB BOARD 1
2
INDOOR
DC
13.1V
POWER BOARD
3
X1
X2
Hi Lo
CR
52F
TO OUTDOOR UNIT
CONNECTING WIRES
(POLAR)
TB5
1
2
FB
1 2
LED1
CN2D
1
CNSK CN2S
1
X2
Lo Hi
X1
DC13.1V
1 3
CND
1 3
CNDK
1 3 5 7
FAN
FUSE
ZNR
X5 X4 X6
LED2
X6 X5 X4
51F
CN2L
CN41
12
OFF
ON
INDOOR
CN51 CN32 CN31
SW6
1
2
CN22
CONTROLLER BOARD
123
123
CN30
1
2
1
2
CN20
CN21
CN90
OFF
ON
8764123
5
SW5
OFF
ON
SW1
12345
SWE
OFF
ON
TB4
TH1
TH2
CIRCUIT BREAKER
(FIELD SUPPLY)
PEH-5,6GAK : 15A
PE
220/230/240V
50Hz
POWER SUPPLY
~
PE
Page 21
21
PEH-5GAK / PUH-5YKSA PEH-6GAK / PUH-6YKSA
Refrigerant flow in cooling
R.V.coil Heating:ON Cooling:OFF
Refrigerant flow in heating
9 REFRIGERANT SYSTEM DIAGRAM
Unit : mm
Indoor unit
Indoor heat exchanger
Strainer
Thermistor TH2
Distributor with strainer
PEH-5,6 (O.D. 4.0 × I.D. 2.4 -L700)
Restrictor
valve
Capillary
tube
Refrigerant pipe (option)
19.05mm( 3/4¨) (With heat insulator)
Flexible tube
Flared connection
Flexible tube
Refrigerant pipe (option)
9.52 mm( 3/8¨) (With heat insulator)
Ball Valve
Strainer
Service port (check)
Accumulator
Ball Valve (with service port)
Oil separator
4-way valve
Service port
Compressor
High pressure control switch
Capillary tube
Thermal switch
Outdoor unit
Outdoor heat exchanger
Bypass valve
Strainer
Thermistor RT Restrictor valve
Capillary tube
PUH-5 (O.D. 4.0 × I.D. 2.4
-
L
840) ×
2pcs
PUH-6 (O.D. 4.0 × I.D. 2.4
-
L
1200) ×
2pcs
Page 22
22
10
TROUBLESHOOTING
<Error code display by self-diagnosis and actions to be taken for service (summary)>
Present and past error codes are logged and displayed on the wired remote controller or controller board of outdoor unit. Actions to be taken for service,which depends on whether or not the the inferior phenomenon is reoccurring at service, are summarized in the table below. Check the contents below before investigating details.
10-1. TROUBLESHOOTING
Unit conditions at service
Error code
Actions to be taken for service (summary)
The inferior phenomenon is reoccurring.
Displayed
Not displayed
Judge what is wrong and take a corrective action according to SELF-DIAGNOSIS ACTION TABLE (10-3).
Identify the cause of the inferior phenomenon and take a corrective action according to TROUBLESHOOTING BY INFERIOR PHENOMENA (10-4).
The inferior phenomenon is not reoccurring.
Logged
Not logged
1Consider the temporary defects such as the work of protection devices in the refrigerant circuit including compressor, poor connection of wiring, noise and etc. Re-check the symptom, and check the installation environment, refrigerant amount, weather when the inferior phenomenon occurred, and wiring related. 2Reset error code logs and restart the unit after finishing service. 3There is no abnormality in electrical components, controller boards, and remote controller.
1Recheck the abnormal symptom. 2Identify the cause of the inferior phenomenon and take
a corrective action according to TROUBLESHOOTING BY INFERIOR PHENOMENA (10-4). 3Continue to operate unit for the time being if the cause is not ascertained. 4There is no abnormality in electrical components, controller boards, remote controller etc.
PAR-21MAA
ON/OFF
FILTER
CHECK
OPERATION
CLEAR
TEST
TEMP.
MENU
BACK DAY
MONITOR/SET
CLOCK
ON/OFF
ERROR CODE
ERROR CODE
ERROR CODE
1 Turn on the power. 2 Press the [CHECK] button twice. 3 Set address with [TEMP] button if system control is used. 4 Press the [ON/OFF] button to stop the self-check.
A CHECK button B Address C TEMP. button D IC : Indoor unit
OC: Outdoor unit E Check code
F Unit No. G Timer ON/OFF button
A
F
C
BBEED
G
<To delete check code>
1 Display the error code at the self-check result display screen. 2 The address for self-check will blink when the
G ON/OFF
button is pressed twice within three seconds.
– – – – : No trouble generated in the past. F F F F : No corresponding unit.
10-2. MALFUNCTION-DIAGNOSIS METHOD BY REMOTE CONTROLLER
<In case of trouble during operation>
When a malfunction occurs to air conditioner, both indoor unit and outdoor unit will stop and operation lamp blinks to inform unusual stop.
Wired remote controller
Page 23
23
Wired remote controller
1 Check code
Symptom Remark
P1 P2 P4 P5 PA P6 P8 E4, E5
– –
Fb E0, E3
E1, E2
Intake sensor error Pipe (TH2) sensor error
Drain sensor error Drain pump error Forced compressor stop Freezing/ Overheating safeguard operation Pipe temperature error / Outdoor unit error Remote controller signal receiving error
– –
Indoor unit control system error (memory error, etc.) Remote controller transmission error
Remote controller control board error
On wired remote controller
1Check code displayed in the LCD.
If the unit cannot be operated properly after the above test run has been performed, refer to the following table to remove the cause.
Wired remote controller
PLEASE WAIT
Symptom
For about 2 minutes follow­ing power-on
For about 2 minutes following power-on,op­eration of the remote controller is not possible due to system start-up. (Correct operation)
Cause
Connector for the outdoor units protection
PLEASE WAIT → Error code
Display messages do not appear even when operation switch is turned ON (operation lamp does not light up).
After about 2 minutes has expired follow­ing power-on
device is not connected.
Reverse or open phase wiring for the outdoor units power terminal block
Incorrect wiring between indoor and outdoor units
Remote controller wire short
On the wireless remote controller with condition above, following phenomena takes place.
No signals from the remote controller are accepted.
Operation lamp is blinking.
The buzzer makes a short piping sound.
Note: Operation is not possible for about 30 seconds after cancellation of function selection. (Correct operation)
For description of each LED (LED1, 2) provided on the indoor controller, refer to the following table.
LED1 (power for microcomputer) Indicates whether control power is supplied. Make sure that this LED is
always lit.
LED2 (power for wired remote controller)
Indicates whether power is supplied to the wired remote controller. This LED lights only in the case of the main indoor unit.
Page 24
24
10-3. SELF-DIAGNOSIS ACTION TABLE
Note: Refer to the manual of outdoor unit for the details of display
such as F, U, and other E.
Error Code
Meaning of error code and detection method
Cause
Countermeasure
P1
Abnormality of room temperature thermistor (TH1)
1 The unit is in three-minute resume
prevention mode if short/open of thermistor is detected. Abnormal if the unit does not reset normally after three minutes. (The unit returns to normal operation, if it has normally reset.)
2 Constantly detected during cooling,
drying, and heating operation. Short: 90
: or more
Open: -40
: or less
1 Defective thermistor
characteristics.
2 Contact failure of connector
(CN20) on the indoor controller board. (Insert failure)
3 Breaking of wire or contact
failure of thermistor wiring.
4 Defective indoor controller
board.
13 Check resistance value of thermistor. 0
: ······15.0k" 10: ····9.6k" 20: ····6.3k" 30: ····4.3k" 40: ····3.0k" If you put force on (draw or bend) the lead wire with measuring resistance value of thermistor breaking of wire or contact failure can be detected. 2 Check contact failure of connector
(CN20)
on the indoor controller board. Refer to 10-7. Turn the power on again and check restart after inserting connector again.
4 Check room temperature display on remote
controller. Replace indoor controller board if there is abnormal difference with actual room temperature.
Turn the power off, and on again to operate after check.
P2
Abnormality of pipe temperature thermistor/Liquid (TH2)
1 The unit is in three-minute resume
prevention mode if short/open of thermistor is detected. Abnormal if the unit does not reset normally after three minutes. (The unit returns to normal operation, if it has normally reset.)
2 Constantly detected during cooling,
drying, and heating (except defrosting) operation. Short: 90
: or more
Open: -40
: or less
1 Defective thermistor
characteristics.
2 Contact failure of connector
(CN21) on the indoor controller board. (Insert failure)
3 Breaking of wire or contact
failure of thermistor wiring.
4 Defective refrigerant circuit is
causing thermistor temperature of 90
: or more or -40: or
less.
5 Defective indoor controller board.
1–3 Check resistance value of thermistor.
For characteristics, refer to (P1) above. 2 Check contact failure of connector
(CN21)
on the indoor controller board. Refer to
10-7
.
Turn
the power on and check restart after
inserting
connector again.
4
Check pipe <liquid> temperature with remote controller in test run mode. If pipe <liquid> temperature is exclusively low (in cooling mode) or high (in heating mode), refrigerant circuit may have defective.
5 Check pipe <liquid> temperature with remote
controller in test run mode. If there is exclusive difference with actual pipe <liquid> temperature
,
replace indoor controller board.
Turn the power off, and on again to operate after check.
P4
Abnormality of drain sensor (DS)
1 Suspensive abnormality, if short/open of
thermistor is detected for 30 seconds continuously. Turn off compressor and indoor fan.
2 Short/open is detected for 30 seconds
continuously during suspensive abnormality. (The unit returns to normal operation,
if it has normally reset.)
3 Detect the following condition.
During cooling and drying operation.
In case that pipe <liquid> temperature
- room temperature <-10deg (Except defrosting)
When pipe <liquid> temperature or room temperature is short/open temperature.
During drain pump operation.
1 Defective thermistor
characteristics
2 Contact failure of connector
(CN31) on the indoor controller board. (Insert failure).
3 Breaking of wire or contact
failure of drain sensor wiring.
4 Defective indoor controller board.
1–3 Check resistance value of thermistor.
0
: ······6.0k" 10: ····3.9k" 20: ····2.6k" 30: ····1.8k" 40: ····1.3k" 2 Check contact failure of connector
(CN31)
on
the indoor controller board. Refer to
10-7
. Turn the power on again and check restart after inserting connector again.
4 Replace indoor controller board if drain
pump operates with the line of drain sensor connector CN31-
1 and 2 is short-circuited,
and abnormality reappears.
Turn the power off, and on again to operate after check.
P5
Malfunction of drain pump (DP)
1 Suspensive abnormality, if thermistor
of drain sensor is let heat itself and temperature rises slightly. Turn off compressor and indoor fan.
2 Drain pump is abnormal if the condition
above is detected during suspensive abnormality.
3 Constantly detected during drain pump
operation.
1 Malfunction of drain pump 2 Defective drain
Clogged drain pump Clogged drain pipe
3 Attached drop of water at the
drain sensor
Drops of drain trickles from lead wire.
Clogged filter is causing wave of drain.
4 Defective indoor controller board.
1 Check if drain-up machine works. 2 Check drain function. 3
Check the setting of lead wire of drain senso
r
and check clogs of the filter.
4 Replace indoor controller board if drain
pump operates with the line of drain sensor connector CN31-1 and 2 is short-circuited and abnormality reappears. Refer to 10-7.
Turn the power off, and on again to operate after check.
Page 25
25
<Heating mode> When 10 seconds have passed after the compressor starts operation and the hot adjustment mode has finished, the unit is detected as abnormal when condenser/evaporator pipe temperature is not in heating range within 20 minutes.
Note 3) It takes at least 27 minutes to
detect abnormality.
Note 4) It excludes the period of defrosting
(Detection restarts when defrosting mode is over)
Heating range : 5 deg [ (TH2-TH1)
Error Code
Meaning of error code and detection method
Cause
Countermeasure
P6
Freezing/overheating protection is working
1 Freezing protection (Cooling mode)
The unit is in six-minute resume prevention mode if pipe temperature stays under
-15: for three minutes, three minutes after the compressor started. Abnormal if it stays under -15: for three minutes again within 16 minutes after six-minute resume prevention mode. <Frost prevention mode> If pipe temperature is 1: or below when 16 minutes has passed after com­pressor starts operating, unit will start operating in frost prevention mode which stops compressor operation. After that, when pipe temperature stays 10: or more for 3 minutes, frost prevention mode will be released and compressor will restart its operation.
2 Overheating protection (Heating mode)
The units is in six-minute resume prevention mode if pipe temperature is detected as over 70: after the com­pressor started. Abnormal if the temper­ature of over 70: is detected again within 10 minutes after six-minute resume prevention mode.
P8
1 Slight temperature difference
between indoor room temperature and pipe tempera­ture thermistor
Shortage of refrigerant
Disconnected holder of pipe
thermistor
Defective refrigerant circuit
2 Converse connection of
extension pipe (on plural units connection)
3 Converse wiring of indoor/
outdoor unit connecting wire (on plural units connection)
4 Defective detection of indoor
room temperature and pipe temperature thermistor
5 Stop valve is not opened
completely.
(Cooling or drying mode)
1 Clogged filter (reduced airflow) 2 Short cycle of air path 3 Low-load (low temperature)
operation beyond the tolerance range
4 Defective indoor fan motor
Fan motor is defective.
Indoor controller board is
defective.
5 Defective outdoor fan control 6 Overcharge of refrigerant 7 Defective refrigerant circuit
(clogs)
(Heating mode)
1 Clogged filter (reduced airflow) 2 Short cycle of air path 3 Over-load (high temperature)
operation beyond the tolerance range
4 Defective indoor fan motor
Fan motor is defective.
Indoor controller board is
defective.
5 Defective outdoor fan control 6 Overcharge of refrigerant 7 Defective refrigerant circuit
(clogs)
8 Bypass circuit of outdoor unit
is defective.
(Cooling or drying mode)
1 Check clogs of the filter. 2 Remove shields.
4 Measure the resistance of fan motor's winding.
Measure the output voltage of fan's connector (Relay for FAN) onthe indoor controller board. * The indoor controller board should be
normal when voltage of AC 220~240V is detected while fan motor is connected. Refer to 10-7.
5 Check outdoor fan motor. 67 Check operating condition of refrigerant
circuit.
(Heating mode)
1 Check clogs of the filter. 2 Remove shields.
4 Measure the resistance of fan motor's
winding. Measure the output voltage of fan's connector (Relay for FAN) onthe indoor controller board. * The indoor controller board should be
normal when voltage of AC 220~240V is detected while fan motor is connected. Refer to 10-7.
5 Check outdoor fan motor. 6~8Check operating condition of refrigerant
circuit.
Abnormality of pipe temperature
<Cooling mode> Detected as abnormal when the pipe tem­perature is not in the cooling range 3 min­utes later of compressor start and 6 min­utes later of the liquid pipe is out of cooling range. Note 1) It takes at least 9 min. to detect. Note 2) Abnormality P8 is not detected in
drying mode. Cooling range : -5 deg ] (TH2-TH1) TH2: Liquid pipe temperature TH1: Intake temperature
1~4 Check pipe temperature with room
temperature display on remote controller.
23Check converse connection of extension
pipe or converse wiring of indoor/outdoor unit connecting wire.
1 Wrong wiring of indoor/outdoor
connecting wire
2 Reversed phase 3 Protection device is working 4 Damaged outdoor coil thermis-
tor
Abnormality in outdoor unit
1 Check the indoor/outdoor connecting wire. 2 Change the connection of electric wiring. 3 Check the protection device. 4 Measure the resistance of the outdoor coil
thermistor. If the resistance is normal, replace the outdoor controller board.
Page 26
26
Error Code
Meaning of error code and detection method
Cause
Countermeasure
E0
or
E4
Remote controller transmission error(E0)/signal receiving error(E4)
1 Abnormal if main or sub remote con-
troller can not receive normally any transmission from indoor unit of refriger­ant address “0” for three minutes. (Error code : E0)
2 Abnormal if sub remote controller could
not receive for any signal for two min­utes. (Error code: E0)
1 Abnormal if indoor controller board can
not receive normally any data from remote controller board or from other indoor controller board for three minutes. (Error code: E4)
2 Indoor controller board cannot receive
any signal from remote controller for two minutes. (Error code: E4)
1 Check disconnection or looseness of indoor
unit or transmission wire of remote controller.
2 Set one of the remote controllers “main.
If there is no problem with the action above.
3 Check wiring of remote controller.
Total wiring length: max.500m (Do not use cable x 3 or more)
The number of connecting indoor units:
max.16units
The number of connecting remote con-
troller: max.2units
When it is not the above-mentioned problem of
1~3 4 Diagnose remote controllers.
a) When RC OK is displayed,
Remote controllers have no problem. Put the power off, and on again to check. If abnormality generates again, replace indoor controller board.
b) When RC NG is displayed,
Replace remote controller. c) When RC E3 is displayed, d) When ERC 00-06 is displayed, [ c),d)Noise may be causing abnormality. ]
* If the unit is not normal after replacing
indoor controller board in group control, indoor controller board of address “0” may be abnormal.
E3
or
E5
Remote controller transmission error(E3)/signal receiving error(E5)
1 Abnormal if remote controller could not
find blank of transmission path for six seconds and could not transmit.
(Error code: E3)
2 Remote controller receives transmitted
data at the same time, compares the data, and when detecting it, judges different data to be abnormal 30 continuous times. (Error code: E3)
1 Abnormal if indoor controller board could
not find blank of transmission path.
(Error code: E5)
2 Indoor controller board receives trans-
mitted data at the same time, compares the data,and when detecting it, judges different data to be abnormal 30 continuous times. (Error code: E5)
1 Set a remote controller to main, and the
other to sub.
2
Remote controller is connected with only one indoor unit.
3 The address changes to a separate setting. 4~6 Diagnose remote controller.
a) When RC OKis displayed, remote con-
trollers have no problem.
Put the power off,and on again to check. When becoming abnormal again, replace
indoor controller board. b)When RC NGis displayed, replace
remote controller. c)When RC E3or ERC 00-66is displayed,
noise may be causing abnormality.
1 Contact failure at transmission
wire of remote controller
2 All remote controllers are set
as sub remote controller. In this case, E0 is displayed on remote controller, and E4 is displayed at LED (LED1, LED2) on the outdoor controller circuit board.
3 Mis-wiring of remote controller. 4 Defective transmitting receiving
circuit of remote controller
5 Defective transmitting receiving
circuit of indoor controller board of refrigerant address “0”.
6 Noise has entered into the
transmission wire of remote controller.
1 Two remote controller are set
as main.
(In case of 2 remote con-
trollers)
2 Remote controller is connected
with two indoor units or more.
3 Repetition of refrigerant
address.
4 Defective transmitting receiving
circuit of remote controller.
5 Defective transmitting receiving
circuit of indoor controller board.
6 Noise has entered into trans-
mission wire of remote con­troller.
Page 27
27
Error Code
Meaning of error code and detection method
Cause
Countermeasure
Fb
Abnormality of indoor controller board
Abnormal if data cannot be normally read from the nonvolatile memory of the indoor controller board.
1 Defective indoor controller
board.
1 Replace indoor controller board.
E1
or
E2
Abnormality of remote controller con­trol board
1 Abnormal if data cannot be normally
read from the nonvolatile memory of the remote controller control board.
(Error code: E1)
2 Abnormal if the clock function of remote
controller cannot be normally operated.
(Error code: E2)
1 Defective remote controller. 1 Replace remote controller.
PA (2502) (2500)
Forced compressor stop (due to water leakage abnormality)
1 When the intake temperature subtracted
with liquid pipe temperature is less than
-10
:, drain sensor is detected whether it is soaked in the water or not at the interval of 90 seconds. (Drain pump will start operating when the drain sensor is detected to be soaked in the water.)
2 The unit has a water leakage abnormality
when the following conditions, a and b, are satisfied while the above-mentioned detection is performed. a) The drain sensor is detected to be
soaked in the water 10 times in a row.
b) The intake temperature subtracted with
liquid pipe temperature is detected to be less than -10
: for a total of 30 minutes.
(When the drain sensor is detected to
be NOT soaked in the water, the detection
record of a and b will be cleared.)
3 The drain sensor detection is performed
in operations other than cooling. (When the unit stops operating, during heating or fan operation, when the unit stops because of some abnormality)
*Once the water leakage abnormality is
detected, abnormality state will not be released until the main power is reset.
1 Drain pump trouble 2 Drain defective
· Drain pump clogging
· Drain pipe clogging
3 Open circuit of drain sensor
side heater
4 Contact failure of drain sensor
connector
5 Dew condensation on drain
sensor
· Drain water descends along lead wire.
· Drain water waving due to filter clogging.
6 Extension piping connection
difference at twin, triple, quadruple system.
7 Mis-wiring of indoor/ outdoor
connecting at twin, triple, quadruple system.
8 Room temperature thermistor /
liquid pipe temperature thermis­tor detection is defective.
1Check the drain pump.
2
Please confirm whether water can be drained.
3Confirm the resistance of the drain sensor.
4Check the connector contact failure.
5 Check the drain sensor leadwire mounted.
Check the filter clogging
6Check the piping connection.
7Check the indoor/ outdoor connecting wires.
8Check the room temperature display of
remote controller. Check the indoor liquid pipe temperature display of outdoor controller board.
Page 28
28
10-4. TROUBLESHOOTING BY INFERIOR PHENOMENA
When LED1 on indoor controller board is also off.
1 Power supply of 220~240V AC is not supplied to
indoor unit.
2 Defective indoor controller board.
3 Defective indoor power board.
Phenomena
Cause
Countermeasure
(1)LED2 on indoor controller board
is off.
When LED1 on indoor controller board is lit.
1 Mis-setting of main/sub for indoor unit
(There is no unit corresponding to main unit.)
1 Reconfirm the setting of main/sub for
indoor unit
Set the main unit. Set main/sub using SW5-3 on indoor controller board.
1 Check the voltage of indoor power supply
terminal block (L,N).
When AC220~240V is not detected. Check the power supply wiring.
When AC220~240V is detected.
-Check 2 (below).
2 Check voltage output from CNDK on
indoor controller board.
When AC220~240V is not detected. Check the fuse on indoor controller board. Check the wiring connection between indoor power supply terminal block and CND on indoor controller board.
When AC220~240V is detected.
-Check 3 (below).
3 Check voltage output from CN2S on
indoor power board.
When no voltage output. Check the wiring connection between CNDK on indoor controller board and CNSK on indoor power board. If no problem are found,indoor power board is defective.
When DC12.5~13.7V is detected. Check the wiring connection between CN2S on indoor power board and CN2D on indoor power board. If no problem are found,indoor con­troller board is defective.
(2)LED2 on indoor controller board
is blinking.
When LED1 on indoor controller board is also blinking. Connection failure of indoor/outdoor unit connecting wire
When LED1 is lit.
1 Mis-wiring of remote controller wires
When 2 indoor units are wired in one refrigerant system, each indoor unit sets main unit. (SW5-3)
2 Short-cut of indoor/outdoor unit connecting wire.
3 Short-cut of remote controller wires 4 Defective remote controller
Check indoor/outdoor unit connecting wire for connection failure.
1 Check the connection of remote con-
troller wires in case of twin triple indoor unit system. When 2 or more indoor units are wired in one refrigerant system, connect remote controller wires to one of those units.
2 Remove indoor/outdoor connecting wires
and check LED2 on indoor controller board.
When LED2 is blinking, check the short­cut of indoor/outdoor connecting wires.
When LED2 is lit, connect indoor/outdoor connecting wires again, and; if LED2 is blinking, outdoor units controller board is defective; if LED2 is lit, connection failure of indoor/outdoor terminal block etc. has returned to normal.
34 Remove remote controller wires and
check LED2 on indoor controller board.
When LED2 is blinking, check the
short-cut of remote controller wires.
When LED2 is lit, connect remote
controller wires again and: if LED2 is blinking, remote controller is defective; if LED2 is lit, connection failure of remote controller terminal block etc. has returned to normal.
Page 29
29
10-5-3. When wired remote controller or indoor unit micro computer troubles
(3)Upward/downward vane
performance failure
1 The vane is not downward during defrosting and
heat preparation and when the thermostat is OFF in HEAT mode. (Working of COOL protection function)
2 Vane motor does not rotate.
Defective vane motor
Breaking of wire or connection failure of connector
Up/down vane setting is No vanes”.
3 Upward/downward vane does not work.
The vane is set to fixed position.
1 Normal operation (The vane is set to hor-
izontal regardless of remote control.)
2 Check 2 (left).
Check the vane motor. (Refer to How to check the parts.)
Check for breaking of wire or connec­tion failure of connector.
Check Up/down vane setting. (Unit function selection by remote controller).
3 Normal operation (Each connector on
vane motor side is disconnected.)
Phenomena
Cause
Countermeasure
10-5. TEST RUN AND EMERGENCY OPERATION
10-5-1. Before test run
10-5-2. Test run (Using wired remote controller)
B
EF
C
H
G
IM
A
D
ûC
ûC
SIMPLE
PAR-21MAA
ON/OFF
FILTER
CHECK
OPERATION
CLEAR
TEST
TEMP.
MENU
BACK DAY
MONITOR/SET
CLOCK
ON/OFF
TEST RUN COOL, HEAT
A ON/OFF button B Test run display C Indoor temperature liquid line
temperature display
D ON/OFF lamp E Power display
F Error code display
Test run remaining time display
G Set temperature button H Mode selection button I Fan speed button M TEST button
1 Turn on the power at least 12 hours before the test run. 2 Press the [TEST] button twice. "TEST RUN" liquid crystal display 3 Press the [Mode selection] button. Make sure that wind is blown out. 4 Press the [Mode selection] button and switch to the cooling (or heating) mode.
Make sure that cold (or warm) wind is blown out.
5 Press the [Fan speed] button. Make sure that the wind speed is switched. 6 Check operation of the outdoor unit fan. 7 Release test run by pressing the [ON/OFF] button. Stop 8 Register a telephone number.
The telephone number of the repair shop, sales office, etc., to contact if an error occurs can be registered in the remote controller. The telephone number will be displayed when an error occurs. For registration procedures, refer to the operation manual for the indoor unit.
[Emergency operation procedure]
1.When the indoor unit microcomputer has failed, but all other components work properly, if you set the switch(SWE,SW6) on the indoor control board, the indoor unit will begin Emergency Operation.
2.When you activate emergency operation of the cooling or heating, you have to set the switch(SWE)and switch(SW6) on indoor controller.
SWE:ON · Indoor fan is running high speed. SW6-1:ON · Emergency operation of cooling mode. SW6-1,2:ON · Emergency operation of heating mode.
3.Before you activate emergency operation, check the following points: (1) Emergency operation cannot be activated when:
· The outdoor unit malfunctions. · The indoor fan malfunctions. (2) Emergency operation becomes continuous only by switching the power source on / off. ON / OFF on the remote control or temperature control etc. does not function. (3)
Avoid operating for a long time when the outdoor unit begins defrosting while emergency operation of the heating is activated, because it will start to blow cold air. (4) Emergency cooling should be limited to 10 hours maximum (The indoor unit heat exchanger may freeze). (5) After emergency operation has been deactivated, set the switches etc. to their original positions.
▲▲▲
After completing installation and the wiring and piping of the indoor and outdoor units, check for refrigerant leakage, looseness in the power supply or control wiring, wrong polarity, and no disconnection of one phase in the supply. Use a 500-volt megohmmeter to check that the resistance between the power supply terminals and ground is at least 1.0M
Do not carry out this test on the control wiring (low voltage circuit) terminals.
Warning: Do not use the air conditioner if the insulation resistance is less than 1.0M .
Page 30
30
10-6. HOW TO CHECK THE PARTS PEH-5GAK PEH-6GAK
0
10
20
30
40
50
-20 -10 0 10 20 30 40 50
< Thermistor for lower temperature >
Temperature (:)
Resistance (K")
<Thermistor Characteristic graph>
Room temperature thermistor(TH1)
Pipe temperature thermistor/liquid(TH2)
Thermistor R
0=15k' ±3%
Fixed number of B=3480 ± 2% Rt=15exp { 3480( ) }
0
: 15k' 10: 9.6k' 20: 6.3k' 25: 5.2k' 30: 4.3k' 40: 3.0k'
Thermistor for lower temperature
1
273+t
1
273
Parts name
Room temperature thermistor (TH1)
Disconnect the connector, then measure the resistance using a tester. (Surrounding temperature 10˚C-30
Indoor coil thermistor (TH2)
Indoor unit Fan motor
PEH-5,6 Thermal protector trip temperature
150 ±5˚C : open 96 ±15˚C : close
Brown
Red
Lo 220∼240V 50Hz
Blue Thermal protector 17AM037E5-4
Operating temperature
P
M
Orange
Measure the resistance value across the terminals with a multimeter. (Winding temperature 20˚C)
PEH-5,6
A1
A2
White
PEH-5,6 (High static pressure motor)
Check points
˚C)
Nomal Abnormal
-9.6k4.3k Open or short
(Refer to the thermistor)
Normal
Red-Orange 7.15 Brown-White Red-Brown
Red-Orange Brown-White Red-Brown
11.71
5.12
5.34
10.12
3.35
Abnormal
Open or short
Page 31
31
10-7. TEST POINT DIAGRAM
10-7-1. Power board PEH-5GAK PEH-6GAK
CNSK Connect to the indoor controller board (CNDK) Between
1 to 3 220-240V AC
CN2S Connect to the indoor controller board (CN2D) Between
1 to 3 12.6-13.7V DC (Pin1 (+))
Page 32
32
10-7-2. Indoor controller board PEH-5GAK PEH-6GAK
FAN Fan motor output
CNP Drain-pump output (DP) (220~240V AC)
CNC Dew prevention heater (H2) (220~240V AC)
CNDK Connect to the indoor power board (CNSK) (220~240V AC)
FUSE (6.3A 250V)
CND Power supply input (220~240V AC)
SWE Emergency operation
SW1 Model setting
CN2L Connector (LOSSNAY)
CN51 Centrally control
CN6V Vane motor output (MV)
CN90 Connect to the wire­less remote con­troller board (CNB)
CN31 Drain sensor (DS)
CN21 Pipe temperature thermistor/Liquid (TH2)
CN20 Room temperature thermistor (TH1)
CN22 Remote controller connecting wire (10.4~14.6V DC)
LED2 Power supply (R.B)
LED1 Power supply (I.B)
CN2D Connector to the indoor power board (CN2S) (12.5~13.7V DC)
}
}
+
+
SW5 System Setting
CN32 Remote Switch
CN41 Connector (HA terminal-A)
CN105/ CN92 (RED)
SW6 Emergency operation
CN30 Transmission (indoor/outdoor)
CNL Louver motor output (ML) (220~240V AC)
Page 33
33
10-8. FUNCTIONS OF DIP SWITCH AND JUMPER WIRE
Each function is controlled by the dip switch and the jumper wire on control p.c. board.
(Marks in the table below) Jumper wire ( : Short : Open)
Jumper wire
SW1
SW5
Functions
Model settings
System settings
Setting by the dip switch and jumper wire
SW1
54321
ON
OFF
SW5
5432
8761
ON OFF
Remarks
SW5-3 Main/Sub setting OFF : Main ON : Sub SW5-4 Rotaion operation setting OFF : Not avairable ON : avairable
Page 34
34
10-9. OUTDOOR UNIT SERVICE FUNCTIONS (OUTDOOR CONTROLLER BOARD)
(1) Compulsory defrosting
1When all of the following conditions are satisfied, pressing SW2 starts the compulsory defrosting.
During HEAT mode
The compressor is ON.
The outdoor coil temperature is being displayed by LED. (Outdoor controller board dip switch SW3-1 : OFF, SW3-2 :
ON)
The outdoor coil thermistor reads 8°C or below.
2The operation state and the termination conditions of the compulsory defrosting are the same as those of the normal
defrosting. As an exception, the defrost interval after the defrosting completion is 50 minutes.
(2) Fixed fan-output
While the compressor is operating (except during defrosting) and the fan output step is indicated by LED, pressing SW2 fixes the fan output. The fixed fan-output can be released when any of the following conditions are satisfied.
1SW2 is pressed again. 2SW3 setting is changed. 3The compressor stops. 4Defrosting operation starts.
(3) Function of switches on the outdoor controller board
SW1: Clears the check code memory (push-button switch) SW2: Switches the output state indication and the check code display (push-button switch) SW3-1,2: Switches the output state indication items (dip switch)
(4) 100% fan output
Fan output is fixed to 100% by shorting the connector CN22. However, the fan stops during compressor OFF or defrosting. Open-circuit of CN22 restarts the normal fan control.
(5) Time shortening
Short circuit of the connector CN21 shortens the time as follows
1Fan control period: 30 seconds 3 seconds 2Three-minutes time delay function : 3 minutes 3 seconds 3Max. time of defrosting : 15 minutes 15 seconds 4Defrost interval : 30 ~ 120 minutes 3 ~ 12 seconds 5Compressor ON/OFF time for bypass valve ON/OFF : 30 minutes 3 seconds 6Compressor ON time to start other functions : x minutes x seconds 7Crankcase heater operation : 1 hour 6 seconds
(6) Crankcase heater control
1With jumper wire J3
The crankcase heater is ON from when the power is turned ON until the compressor starts, and then turns ON one hour
after the compressor stops.
2Without jumper wire J3 The crankcase heater is ON from when the power is turned ON until the compressor starts, and repeats 1-hour ON and 1­hour OFF, after the compressor stops.
Page 35
35
11
FUNCTION SETTING
Function
Settings
Mode No.
Setting No.
Initial setting
(when sent from the factory)
Remarks
Power failure automatic recovery Indoor temperature detecting
LOSSNAY connectivity
Power supply voltage Frost prevention temperature Humidifier control
Rotation
OFF ON Indoor unit's (Main) internal sensor
Remote controller's internal sensor *1 Not supported Supported (indoor unit not equipped with outdoor air intake) Supported (indoor unit equipped with outdoor air intake) 240V 220V,230V 1˚C (Normal)
-3˚C When the compressor operates, the humidifier also operates. When the fan operates, the humidifier also operates. 24h cycle 168h cycle Back up function
1 2 1 2 3 1 2 3 1 2 1 2 1 2 1 2 3
01
02
03
04 15 16
20
The setting is applied to all the units in the same refrigerant system.
11-1. UNIT FUNCTION SETTING BY THE REMOTE CONTROLLER
Each function can be set according to necessity using the remote controller. The setting of function for each unit can only be done by the remote controller. Select function available from the table 1. (1) Functions available when setting the unit number to 00 (Select 00 referring to
4 setting the indoor unit number.)
*1 The functions below are available only when the wired remote controller is used.The functions are not available for floor
standing models.
<Table 1> Function selections
(2) Functions available when setting the unit number to 01-02 or AL (07 in case of wireless remote controller)
When setting functions for an indoor unit in an independent system, set the unit number to 01 referring to
4 setting the
indoor unit number.
When setting functions for a simultaneous- Twin indoor unit system, set the unit number to 01 to 02 for each indoor unit in case of selecting different functions for each unit referring to
4 setting the indoor unit number.
When setting the same functions for an entire simultaneous Twin indoor unit system, set refrigerant address to AL (07 in case of wireless remote controller) referring to
4 setting the indoor unit number.
Filter sign 100Hr 1
Air flow Quiet 1 ­(
Fan speed
No.of air outlets 4 directions 1 -
Optional high efficiency filter Supported Vane setting
Energy saving air Disabled flow (Heating mode Vane differential setting No.1 setting (TH2: 24-28˚C) in heating mode No.2 setting (Standard, TH2:28-32˚C (
cold wind prevention
Swing Not available
Set temperature in heating Available mode (4 deg up
Fan speed when the heating thermostat is OFF
Fan speed when the cooling thermostat is OFF Stop Detection of abnormality of Available the pipe temperature (P8
Function Settings
2500Hr 07 2
No filter sign indicator
)
Standard 08 2 ­High ceiling 3 -
3 directions 09 2 ­2 directions Not supported
No vanes Vane No.1 setting Vane No.2 setting
)
)
)
Enabled
No.3 setting (TH2: 32-38˚C
Available
Not available Extra low Stop Set fan speed
Set fan speed
)
Not available
)
)
Initial setting (Factory setting
Mode
Setting
No.
No.
3
3-
10
1 2 1-
11 2 -
3-
12
1 2 1-
14 2
23 24
25
27
28
3 1 2 1 2
1 2 3 1 2 1 2
- : Not available PEH-GAK
-
-
-
-
-
-
-
-
)
Page 36
36
Operating Procedure
]
.
t
.
d
T
N
N
.
.
(
d
N
N
flashed for two seconds or "
flashes in the room temperature display area for two seconds, a transmission error may have occurred.
F
button so that "
flashes in the unit number display
.
[
r
.
.
".
.
E
t
.
A
E
s
"
is selected as the unit number, all the indoor
will flash in the room temperature display area if the selected address
"
appears and flashes in the unit number display area and the
e
.
e
,
.
.
.
(
e
.
)
button. The currently selected setting number will
.
(
g
.
E
t
e
.
is displayed for both the mode number and setting number and
T
.
A
-
.
g
)
.
A
s
n
e
c
r
n
t
r
n
.
r
n
n
n
r
e
d
heck the setting items provided by function selection
o
, fill in the "Check" column in Table 1, and then change them as necessary. For factory settings, refer to the indoor unit's installation manual
old down the
buttons and then the remote controller's display content will change as shown below
ddres
display sectio
UNCTIO
SELECTIO
an
ES
Set the outdoor address
ress the [LOCK] buttons
current settings according to steps
and
to select the desire
f the unit stops after
Note :
ress the
area
o set modes 01 to 06 or 15 to 22 select unit number "00" o set modes 07 to 14 or 23 to 28 carry out as follows:
o set each indoor unit individually, select " o set all the indoor units collectively, select "
onfirm the address and unit number
ress the
umber
fter a while, "
ode numbe
display sectio
88
urthermore, if
address display area also flashes, there are no units that correspond to th
elected unit number. In this case, the address and unit number may be incorrect, o repeat steps
Select the mode number
ress the [EMP] buttons
umber
Only the selectable mode numbers can be selected.
ress the
lash, so check the currently set content
UNCTIO
SELECTIO
-
ON/OF
nit numb
display se
button to confirm the address and uni
OD
and
to set the correct ones
- -"
and
ENU
1" to "4
"
to set the desired mod
, and then restart from step
ress the
pressed
button, the corresponding indoor unit will start fan operation. Thi
OD
election. However, if "
xample) When the address is set to 01 and the unit number is 02
Indoor unit
esignate operatio
hen grouping different systems, if an indoor unit other than th
ne to which the address has been set performs fan operation
there may be another address that is the same as the specified one
n this case, check the DIP switch of the outdoor unit to see
whether such a address exists
ode numbe
display sectio
ress the [EMP] buttons umber
0" or
00 address Outdoor unit
emote controlle
and
Main Sub
ode number 02 = Indoor temperature detectio
and
to select the unit numbe
an draf
to select the desired settin
Setting number display sectio
egister the settings you have made in steps
ress the
"---"
old down the
buttons simultaneously for at least two seconds
fter a while, the function selection screen will disappear and the air condi
tioner OFF screen will reappear
Note : column of Table 1 to indicate the change
button. The mode number and setting number will star
OD
Setting number 1 = Indoor unit operating averag
to
to
ES
an
Setting number 3 = Remote controller built-in senso
he mode number and setting number will stop flashing and remain lit, indicating th
end of registration
o not operate the remote controller for at least 30 seconds after completin
unction selection. (No operations will be accepted even if they are made.
"Check"
Page 37
37
11-2. FUNCTION SELECTION OF REMOTE CONTROLLER
The setting of the following remote controller functions can be changed using the remote controller function selection mode. Change the setting when needed.
Item 1
1.Change Language ("CHANGE LANGUAGE")
2.Function limit ("FUNCTION SELECTION")
3.Mode selection ("MODE SELECTION")
4.Display change ("DISP MODE SETTING")
Item 3 (Setting content)
Display in multiple languages is possible.
Setting the range of operation limit (operation lock)
Setting the use or non-use of "automatic" operation mode
Setting the temperature adjustable range (maximum, minimum)
Selecting main or sub remote controller
*
When two remote controllers are connected to one group, one controller must be set to sub.
Setting the use or non-use of clock function
Setting the timer type
Contact number display in case of error
Setting the telephone number
Setting the temperature unit (: or °F) to display
Setting the use or non-use of the display of indoor (suction) air temperature
Setting the use or non-use of the display of "Cooling" or "Heating" display during
operation with automatic mode
Item 2
Language setting to display
(1)
Operation function limit setting (operation lock) ("LOCKING FUNCTION")
(2)
Use of automatic mode setting ("SELECT AUTO MODE")
(3)
Temperature range limit setting ("LIMIT TEMP FUNCTION")
(1)
Remote controller main/sub setting ("CONTROLLER MAIN/SUB")
(2) Use of clock setting ("CLOCK") (3) Timer function setting ("WEEKLY TIMER") (4) Contact number setting for error situation ("CALL.")
(1) Temperature display :/°F setting ("TEMP MODE :/°F") (2)
Suction air temperature display setting ("ROOM TEMP DISP SELECT")
(3)
Automatic cooling/heating display setting ("AUTO MODE DISP C/H")
[Function selection flowchart] Refer to next page. [1] Stop the air conditioner to start remote controller function selection mode. [2] Select from item1. [3] Select from item2. [4] Make the setting. (Details are specified in item3) [5] Setting completed. [6] Change the display to the normal one. (End)
➔➔
[Detailed setting] [4] -1. CHANGE LANGUAGE setting
The language that appears on the dot display can be selected.
Press the [
MENU] button to change the language.
1 Japanese (JP), 2English (GB), 3 German (D), 4 Spanish (E), 5 Russian (RU), 6 Italian (I), 7 Chinese (CH), 8 French (F)
[4] -2. Function limit (1) Operation function limit setting (operation lock)
To switch the setting, press the [ ON/OFF] button. 1 no1: Operation lock setting is made on all buttons other than
the [
ON/OFF] button.
2 no2: Operation lock setting is made on all buttons. 3 OFF (Initial setting value) : Operation lock setting is not made
* To make the operation lock setting valid on the normal screen, it is
necessary to press buttons (Press and hold down the [FILTER] and [ ON/OFF] buttons at the same time for two seconds.) on the normal screen after the above setting is made..
(2) Use of automatic mode setting When the remote controller is connected to the unit that has auto­matic operation mode, the following settings can be made.
To switch the setting, press the [ ON/OFF] button. 1 ON (Initial setting value) : The automatic mode is displayed when
the operation mode is selected.
2 OFF : The automatic mode is not display
when the operation mode is selected.
[4] -3. Mode selection setting (1) Remote controller main/sub setting
To switch the setting, press the [ ON/OFF] button.
1 Main : The controller will be the main controller. 2 Sub : The controller will be the sub controller.
(2) Use of clock setting
To switch the setting, press the [ ON/OFF] button.
1 ON : The clock function can be used. 2 OFF:The clock function cannot be used.
(3) Timer function setting
To switch the setting, press the [ ON/OFF] button (Choose one of the followings.).
1 WEEKLY TIMER (initial setting on MA deluxe):
The weekly timer can be used.
2 AUTO OFF TIMER: The auto off timer can be used.
SIMPLE TIMER (Default setting on MA smooth):
The simple timer can be used.
4
3
TIMER MODE OFF: The timer mode cannot be used.
* When the use of clock setting is OFF, the "WEEKLY TIMER" cannot be
used.
(4) Contact number setting for error situation
To switch the setting, press the [ ON/OFF] button.
1 CALL OFF:
The set contact numbers are not displayed in case of error.
2 CALL **** *** **** : The set contact numbers are displayed in case
of error.
(3) Temperature range limit setting After this setting is made, the temperature can be changed within the set range.
To switch the setting, press the [ ON/OFF] button. 1 LIMIT TEMP COOL MODE :
The temperature range can be changed on cooling/dry mode.
2 LIMIT TEMP HEAT MODE :
The temperature range can be changed on heating mode.
3 LIMIT TEMP AUTO MODE :
The temperature range can be changed on automatic mode. 4 OFF (initial setting) : The temperature range limit is not active. *
When the setting, other than OFF, is made, the temperature range limit setting on cooling, heating and automatic mode is made at the same time. However the range cannot be limited when the set temperature range has not changed.
To increase or decrease the temperature, press the [ TEMP ( ) or ( )] button.
To switch the upper limit setting and the lower limit setting, press the
[ ]
button. The selected setting will flash and the temperature can be set.
Settable range
Cooling/Dry mode : Lower limit: 19 : ~ 30: Upper limit: 30 : ~ 19: Heating mode : Lower limit: 17 : ~ 28: Upper limit: 28 : ~ 17: Automatic mode : Lower limit: 19 : ~ 28: Upper limit: 28 : ~ 19:
CALL_ : The contact number can be set when the display is as
shown on the left.
Setting the contact numbers To set the contact numbers, follow the following procedures. Move the flashing cursor to set numbers. Press the [
TEMP. ( ) and ( )] button to move the cursor to the right (left). Press the [ CLOCK (
) and ( )] button to set the numbers.
[4] -4. Display change setting (1) Temperature display :/ F setting
To switch the setting, press the [ ON/OFF] button.
1 : : The temperature unit : is used. 2 F: The temperature unit
°
°°
F is used.
(2) Suction air temperature display setting
To switch the setting, press the [ ON/OFF] button.
1 ON : The suction air temperature is displayed. 2 OFF:The suction air temperature is not displayed.
(3) Automatic cooling/heating display setting
To switch the setting, press the [ ON/OFF] button. 1 ON : One of "Automatic cooling" and "A utomatic heating" is displayed
under the automatic mode is running.
2 OFF:Only "Automatic" is displayed under the automatic mode.
Page 38
38
Hold down the E button and press the D button for 2 seconds.
Hold down the E button and press the D button for 2 seconds.
Remote controller function selection mode
E Press the operation mode button. G Press the TIMER MENU button. D Press the TIMER ON/OFF button.
Item1 Item2
Dot display
Item3
Room air temperature is not displayed.
One of "Automatic cooling" and "Automatic heating" is displayed under the automatic mode is running. (Initial setting value)
Only "Automatic" is displayed under the automatic mode.
Normal display (Display when the air condition is not running)
Change Language
Function selection
Mode selection
Display mode setting
Operation lock setting is not used. (Initial setting value)
Operation lock setting is except On/Off buttons.
Operation lock setting is All buttons.
The automatic mode is displayed when the operation mode is selected. (Initial setting value)
The automatic mode is not displayed when the operation mode is selected.
The temperature range limit is not active. (Initial setting value)
The temperature range can be changed on cooling/dry mode.
The temperature range can be changed on heating mode.
The temperature range can be changed on automatic mode.
The remote controller will be the main controller. (Initial setting value)
The remote controller will be the sub controller.
The clock function can be used. (Initial setting value)
The clock function can not be used.
Weekly timer can be used. (Initial setting value)
Auto off timer can be used.
Simple timer can be used.
Timer mode can not be used.
The set contact numbers are not displayed in case of error. (Initial setting value)
The set contact numbers are displayed in case of error.
The temperature unit
:
is used. (Initial setting value)
The temperature unit °F is used.
Room air temperature is displayed. (Initial setting value)
Flowchart of Function Setting
Setting language (English)
E
G
EN
GE
E
ES
RU
G
IT
ZH
FR
F
TEMP.
MENU
E
PAR-21MAA
G
MONITOR/SET
BACK DAY
CLOCK
ON/OFF
C
OPERATION
D
ON/OFF
FILTER
CHECK
CLEAR
I A
TEST
B
H
JA
D
OFF
D
on1
D
D
D
D
D
on2
ON
D
OFF
OFF
D
G
G
E
G
G
G
G
D
D
D
E
G
D
D
G
G
D
D
D
G
G
D
D
D
G
G
D
D
D
D
ON
D
OFF
D
OFF
D
CALL-
:
D
°F
ON
D
OFF
ON
D
OFF
Page 39
39
SYSTEM CONTROL12
12-1. VARIETY OF SYSTEM CONTROL FUNCTIONS
System Name System Diagram Features
A.Remote control-
ler operation
Use of two con­trollers enables operation of the air conditioner both from a distance and nearby.
B.Group control
operation
Use of one remote controller to con­trol multiple air conditioners with the same settings simultaneously.
Indoor unit
Remote Controller
* One of the wired remote con-
trollers must be set as a sub remote controller.
Inter face Indoor
unit Outdoor
Remote Controller
unit
Up to two remote controllers can be connected to one group.
Operation control by the latest command (last en­tered priority)
Wired remote controllers can be combined as a pair.
One group can consist of up to 16 indoor units, and they can be started sequentially by connecting the remote controller to them and assigning an address to each inter face.
All the units belonging to the same group are oper­ated in the same mode, but thermostats can be turned ON/OFF individually for each indoor unit.
Up to two remote controllers can be connected.
System Name System Diagram Features
Weekly timer: In addition to ON/OFF, up to eight temperature patterns can be set for each day of the week.
C. Timer operation
Enables control of start and stop.
* For control by
external timer, refer to Remote/ handheld com­bined control op­eration".
* Only one timer can be selected; the auto off, simple
and weekly timers cannot be combined.
Simple timer: Start and stop operations can each be
performed once within 72 hours (can be set in 1-hour increments).
Auto off timer:Operation is stopped when the preset
time elapses following the start of operation. The time can be set from 30 minutes to 4 hours in 30-minute increments.
* Only one timer can be selected; the simple and auto
off timers cannot be combined.
Parts Required in Addition to Standard System
Components (Indoor/Outdoor Units, Remote Controller)
Wired remote controller (addi­tional) (PAR-21MAA)
Inter face MAC-397IF-E
Parts Required in Addition to Standard System
Components (Indoor/Outdoor Units, Remote Controller)
MA Remote controller (PAR-21MAA)
Page 40
40
12-2. ONE REMOTE CONTROLLER (STANDARD) OPERATION
(1) One Wired Remote Controller
(OC: Outdoor unit IC: Indoor unit R: Remote controller (for wireless type: optical receiver adapter)
(Reference)
Electrical wiring diagram
OC IC
1 2
LN
Power source wiring
1 2 3
1 2
R
(No polarity)
Outdoor unit Indoor unit Remote controller
Power source wiring
(Polarity)
1 2 3
Power supply terminal block L, N
Indoor/outdoor connection cable terminal
block 1,2 (Polarity)
Remote controller cable terminal block 1,2 (No polarity)
Slim Air Conditioners System
Remote controller connection circuit (Controller cable)
Outdoor unit OC
Indoor unit IC
Wired remote controller R
Standard 1:1
Indoor/Outdoor connection cable
Remote controller cable
OC
IC-1
R
2
2
12-3. TWO-REMOTE CONTROLLER OPERATION
(1) Two Wired Remote Controllers
Slim Air Conditioner System
Outdoor unit OC
Indoor unit IC
Remote controller connection circuit (Controller cable)
[Reference]
Set one of the remote controllers as the main controller (factory setting) and the other as the sub controller using the remote controller's function selection.
Wired remote controller R
Outdoor unit OC
Indoor unit IC
Wired remote controller R
(R: Wired remote controller)
Standard 1:1
Remote controller cable
OC
IC
R-1
OC
3
IC
2
R-1
3
2
2
R-2
Indoor/outdoor connection cable
2
R-2
Page 41
41
Connecting cable for each system
Mounting screws 4 o 16
Electrical wire mounting bracket
Mounting cord clamp
Mounting screws 4
o 10
Mounting cord clamp
Mounting screws (black) 3.5
o 12
Interface unit mounting cord clamp or mounting cord clamps
12-4. GROUP CONTROL OPERATION
))
.
.
)
.
.
t
.
g
.
Indoor control board
CN105
or
CN92
Connect the connecting cable that comes with the interface unit to the connector CN105 or CN92 on the indoor control board.
INDOOR
(COLLECTIVE OPERATION AND CONTROL OF MULTIPLE REFRIGERANTSYSTEMS (2 to 16
Group control can be operated by using MAC-397IF-E
he setting of wired remote controller is subjected to variation according to the function of the indoor unit
for mode operation, setting temperature, fan step, air direction
he display of remote controller and operating the indoor unit might be different
Neither the test run nor the function setting can be done by MA remote controller connected with MAC-397IF-E
1.Connecting the MA& CONTACT TERMINAL Interface to the Indoor Uni
onnect the interface unit and the indoor control board using the connecting cable that came with the interface xtending or shortening the connecting cable that comes out of the interface may cause it to malfunction. Also,
keep the connectin
cable as far as possible away from the electrical wires and ground wire. Do not bundle them together
2.Connecting the remote control interface with each system
(For details on each system, see the relevant instruction manual.)
Replace the interface unit mounting cord clamp with a supplied mounting cord clamp based on the thickness of the connecting cable used for each system.
The cables connected to the Indoor unit should be mounted on or near the Indoor unit. If the connecting cable is not securely mounted, the connector may detach, break, or malfunction.
Set the interface dip switch (SW500502) settings before turning on the power.
If the interface dip switch (SW500502) settings are not set correctly, the system will not function properly.
Page 42
42
se as a Wired Remote Control (Using the MA Remote Controller
)
.
.
C
0
0
B
t
h
)
.
.
.
.
ON
1
ON
1
2 3 4
ON
1
2 3 4
ON
1
2 3 4
t
N
.
.
.
.
.
.
t
t
t
t
r
.
Note:
e sure the Auto Heating/Cooling Display Setting on the MA remote controller is set to OFF before use
For information on how to set the Auto/Heating Cooling Display Setting, see the MA remote controller
manual
.
The range of room temperature indication is between 10°C and 38°
ndoor uni
nterface uni
N56
B58
emote control cord that came wit
the MA remote controller (Non polarity
A remote controlle
AR-21MAA)
AR-20MAA cannot be used
with this interface
ip switch settings
SW500 does not have to be set SW501:
SW501- No. 1-4: Refrigerant address
Set this switch when multiple indoor units (and remote control interfaces) are connected to a single MA remote controller
lways start the refrigerant address at "0" ven when connecting multiple outdoor units, set a different refrigerant address for each indoor unit
efrigeran
address
efrigeran
address "0"
efrigeran
address "1"
efrigeran
address "2"
SW501- No. 5
O
6
No. 5 should normally be set to OFF
nder the following conditions, No.6 should normally be set to ON
hen the model of Mr. SLIM exists in the same group, it sets it to turning ON
Set them to ON only when using the room temperature sensor installed in the MA remote controller
This can be switched when an accurate room temperature cannot be detected by the air conditioner unit
E-GAK series do not have a room temperature sensor on their MA remote controllers
Page 43
43
SW501: Settings to accommodate MA remote controller and settings to accommodate outdoor units
SW No.
No. 1 No. 2 No. 3 No. 4
ON
1
2 3 4 5 6
ON
1
2 3 4 5 6
ON
1
2 3 4 5 6
ON
1
2 3 4 5 6
ON
1
2 3 4 5 6
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
1
2 3 4 5 6
ON
1
2 3 4 5 6
ON
2 3 4 5 6
1
ON
1
2 3 4 5 6
ON
1
2 3 4 5 6
ON
2 3 4 5 6
1
ON
1
2 3 4 5 6
ON
1
2 3 4 5 6
ON
1
2 3 4 5 6
Functions OFF ON Comments
Only specify these settings when connecting an
Refrigerant address 0
MA remote controller.
Refrigerant address 1
Refrigerant address 2
Refrigerant address 3
Refrigerant address 4
Refrigerant address 5
Refrigerant address 6
Refrigerant address 7
Refrigerant address 8
Refrigerant address 9
Refrigerant address 10
Refrigerant address 11
Refrigerant address 12
Refrigerant address 13
Refrigerant address 14
Refrigerant address 15
SW No.
No. 5 No. 6
Functions Room temperature detector The model of Mr. SLIM exists in the
same group.
Indoor unit Not mixed
OFF
ON Remote control Mixed
Comments This should normally be set to OFF. This should normally be set to ON.
Page 44
44
SW502 : Air Conditioner Function Settings
4. Mounting the Remote Control Interface Unit
The Interface unit should be placed in a location where the connecting cable from the interface can reach an indoor unit. The device will not function properly if the connecting cable is extended so the connecting cable should not be extended. Mount the interface unit securely to a pillar or wall using 2 or more screws.
When Using Wall Mounting Brackets
1
Attach the wall mounting brackets to the interface unit using 2 mounting screws.
2
Mount the unit to a pillar or wall using 2 mounting screws.
Interface unit
Wall mounting brackets
Mounting screws
Mounting screws
Mounting screws
Cord clamp for wiring
SW No.
Cooling only type/ Heat pump type
No. 1
No. 2
Auto mode
No. 3
No. 4
Fan speed
No. 5
Vane
No. 6
Swing
No. 7
Not in use
No. 8
Fan mode
* Fan speed 2 step model : An actual fan speed is 2 step though the display of remote controller becomes 4 step or 3 step.
Functions
OFF
Heat pump type
Not available
(setting No.3 disabled)
Available
(unit)
4 speeds
Available
Available
Not available
ON
Cooling only type
Available
(setting No.3 enabled)
Available
(remote controller)
3 speeds (1-speed and
2-speed models
set ON)
Not available
Not available
Available
Set the mode in accordance with the operation manual for the indoor unit.
Heat pump type : Set to ON. Cooling only type : Set to OFF.
Set to OFF. When operating 2-speed model with the 3-speed
setting (ON), the MA remote controller display will indicate 3 fan speeds. The table below shows the displays and the actual outputs at that time.
Display Meaning Indoor unit output
Medium speed High speed
The Vane function of either of indoor unit : When the function is provided, it is Available (OFF). When the function is not provided, it is Not available (ON).
The Swing function of either of indoor unit : When the function is provided, it is Available (OFF). When the function is not provided, it is Not available (ON).
Permanently set to OFF. Set to ON.
3. Test Run (Check Operations)
Comments
High speed
Low speedLow speed
High speed
Interface status monitor
You can check the status of the interface by the LED lamp on the interface unit board.
LED lamp no.
LED521
LED522
LED523
DC 12 V is not being supplied from the air conditioner.
Device is not communicating properly with the air conditioner.
Device is not communicating properly with the MA remote controller.
Lamp off
Lamp on
DC 12 V is being supplied from the air conditioner.
Blinking
Blinking at approx. 1 second intervals: Device is communicating normally with the air conditioner.
Blinking at approx. 8 second intervals: Device is com­municating normally with the MA remote controller.
* Use the table above to check the device operations.
Page 45
45
When Mounting Directly to a Wall
Mount the interface unit case to the wall using the mounting screws.
Interface case mounting screws
Mounting screws
When mounting the interface unit inside a ceiling or wall, install an access door to facilitate mainte­nance.
When the interface unit is mounted above an indoor unit, it should be positioned 40 mm or more away from the unit to ensure that ceiling grills can be removed.
40 mm or more
Attach the interface unit connecting cable here. Store extra connecting cable in the ductwork space behind the indoor unit.
* If there is any slack in the connecting cable, use a
fastener to keep it in place.
* When mounting the interface unit using a cushioning
material , be sure to mount it in a location where it will not fall.
Interface unit
Cushioning material
Page 46
46
12-5. POWER OUTAGE AUTOMATIC RECOVERY OPERATION
Whenever a power outage or switching of the power supply causes the power supply of an operating air conditioner to go from OFF to ON, this function will automatically restore the operation of the air conditioner to its previous operating mode.
* If the power is turned from OFF to ON when the air conditioner is not in operation, the air conditioner will not automatically
be turned on. However, the timer operation will be cancelled if the air conditioner is in timer operation (including when the unit is waiting for its start time). Setting for timer operation must be performed once again.
If there is a momentary power outage of less than one second while the air conditioner is in operation, there may not be a
clear determination of whether or not there was a power failure. When it has been determined that there has been a power failure, recovery will take approximately four minutes after the power is restored. Please wait. (Once "PLEASE WAIT" has appeared on the display, a protection system will operate to prevent the unit from restarting for three minutes.)
When it has been determined that there has been no power failure, operation will continue as is.
Settings can be made by function selections from the remote controller.
When there is group control, selection of all refrigerants is required.
12-6. INDIVIDUAL CONTROL OPERATION FROM A SEPARATE ROOM
By simply centralizing the remote controllers installed in each room in a separate control room, individual control or central-
ized monitoring of the air conditioners in each room can be attained.
Air conditioner control can be performed up to a total of 500 meters away by connecting the indoor units and remote con-
trollers with 0.3 to 1.25 mm
2
2-core cable.
If a remote controller is installed in a room and control room, refer to the section on operating with two remote controllers.
Indoor unit Indoor unit Indoor unit
Remote controller
Control room room 1 room 2 room 3
12-7. TIMER OPERATION
Timer operation can be performed by setting the wired timer. Start and stop times can be set in10-minute increments within a
24-hour period.
When used in combination with the central control remote controller of the M-NET control system for the outdoor unit, one
program timer can be used for individual timer settings for each group of the central control system. (Each timer setting can be stored in data memory so timer settings for up to 50 groups can be set individually.)
* Please refer to the MELANS catalog or technical information for details about the central control remote controller.
Page 47
47
SERVICE DATA (PARTS NAME)
13
Indoor unit
(1) Parts name
11
External parts
PEH-5, 6GAK
Drain pan
Drain pipe connection (R1)
Control box
Fan motor
Sirocco fan
Suspension bracket
Special washer
Check valve
Capillary tube
Strainer
Heat exchanger
Liquid pipe
Gas pipe
Inlet thermistor (TH1)
Strainer
Liquid pipe thermistor (TH2)
Drain Pan
Page 48
48
22
Control box parts
PEH-5, 6GAK
Magnetic contactor (Fan motor)
Capacitor
Power supply board
Ferrite core
Control board
Terminal block for remote controller
Terminal block for outdoor/indoor control wiring connection
Power supply terminal block
TB5
2121
52F
TB4
51F
TB2
L1 L3 NL2
A
FB
I/D POWER BOARD
I/D
CAPACITOR
X1Lo X2Hi
CONTROLLER BOARD
SNB board
Relay
view A
Page 49
49
OPTIONAL PARTS
14
1 MAC-397IF-E
Item Individual order number
Group control operation 2 3 Air filter PAC-KE206AF
M-NET operation MAC-399IF-E
Page 50
HEAD OFFICE : TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU TOKYO 100-8310, JAPAN
CCopyright 2007 MITSUBISHI ELECTRIC ENGINEERING CO., LTD. Distributed in July 2007 No.HWE07020 PDF 5 Printed in Japan.
New publication, effective July 2007. Specifications subject to change without notice.
TM
Loading...