Mitsubishi PEFY-P72NMHSU-E, PEFY-P96NMHSU-E Service Manual

Page 1
TECHNICAL & SERVICE MANUAL
Model nameModel name
PEFY-P72NMHSU-E PEFY-P96NMHSU-E
2011
AIR CONDITIONERS
Page 2
Page 3
HWE10170 GB
Safety Precautions
Read before installation and performing electrical work
Symbol explanations
Thoroughly read the following safety precautions prior to installation.Observe these safety precautions for your safety.This equipment may have adverse effects on the equipment on the same power supply system.Contact the local power authority before connecting to the system.
WARNING
This symbol indicates that failure to follow the instructions exactly as stated poses the risk of serious injury or death.
CAUTION
This symbol indicates that failure to follow the instructions exactly as stated poses the risk of serious injury or dam-
age to the unit.
Indicates an action that must be avoided.
Indicates important instructions.
Indicates a parts that requires grounding.
Indicates that caution must be taken with rotating parts. (This symbol is on the main unit label.) <Color: Yellow>
Indicates that the parts that are marked with this symbol pose a risk of electric shock. (This symbol is on the main unit label.) <Color: Yellow>
WARNING
Carefully read the labels affixed to the main unit.
WARNING
Ask your dealer or a qualified technician to install the unit.
Improper installation by the user may result in water leak­age, electric shock, or fire.
Properly install the unit on a surface that can withstand its weight.
Unit installed on an unstable surface may fall and cause in­jury.
Only use specified cables. Securely connect each cable so that the terminals do not carry the weight of the cable.
Improperly connected cables may produce heat and start a fire.
Take appropriate safety measures against wind gusts and earthquakes to prevent the unit from toppling over.
Improper installation may cause the unit to topple over and cause injury or damage to the unit.
Only use accessories (i.e., air cleaners, humidifiers, electric heaters) recommended by Mitsubishi Electric.
Do not make any modifications or alterations to the unit. Consult your dealer for repair.
Improper repair may result in water leakage, electric shock, or fire.
Do not touch the heat exchanger fins with bare hands.
The fins are sharp and pose a risk of cuts.
In the event of a refrigerant leak, thoroughly ventilate the room.
If gaseous refrigerant leaks out and comes in contact with an open flame, toxic gases will be generated.
Properly install the unit according to the instructions in the Installation Manual.
Improper installation may result in water leakage, electric shock, or fire.
Have all electrical work performed by an authorized electri­cian according to the local regulations and the instructions in this manual. Use a dedicated circuit.
Insufficient power supply capacity or improper installation of the unit may result in malfunctions of the unit, electric shock, or fire.
Page 4
ii
HWE10170 GB
Precautions for handling units for use with R410A
WARNING
Keep electrical parts away from water.
Wet electrical parts pose a risk of electric shock, smoke, or fire.
Securely attach the control box cover.
If the cover is not installed properly, dust or water may infil­trate and pose a risk of electric shock, smoke, or fire.
Only use the type of refrigerant that is indicated on the unit when installing or relocating the unit.
Infiltration of any other types of refrigerant or air into the unit may adversely affect the refrigerant cycle and may cause the pipes to burst or explode.
When installing the unit in a small space, take appropriate precautions to prevent leaked refrigerant from reaching the limiting concentration.
Leaked refrigerant gas will displace oxygen and may cause oxygen starvation. Consult your dealer before installing the unit.
Consult your dealer or a qualified technician when moving or reinstalling the unit.
Improper installation may result in water leakage, electric shock, or fire.
After completing the service work, check for a refrigerant leak.
If leaked refrigerant is exposed to a heat source, such as a fan heater, stove, or electric grill, toxic gases will be gener­ated.
Do not try to defeat the safety features of the unit.
Forced operation of the pressure switch or the temperature switch by defeating the safety features for these devices, or the use of accessories other than the ones that are recom­mended by Mitsubishi Electric may result in smoke, fire, or explosion.
Consult your dealer for proper disposal method.
Do not use a leak detection additive.
CAUTION
Do not use the existing refrigerant piping.
A large amount of chlorine that may be contained in the re­sidual refrigerant and refrigerator oil in the existing piping may cause the refrigerator oil in the new unit to deteriorate.
Use refrigerant piping materials made of phosphorus deox­idized copper. Keep the inner and outer surfaces of the pipes clean and free of such contaminants as sulfur, oxides, dust, dirt, shaving particles, oil, and moisture.
Contaminants in the refrigerant piping may cause the refrig­erator oil to deteriorate.
Store the piping materials indoors, and keep both ends of the pipes sealed until immediately before brazing. (Keep el­bows and other joints wrapped in plastic.)
Infiltration of dust, dirt, or water into the refrigerant system may cause the refrigerator oil to deteriorate or cause the compressor to malfunction.
Use a small amount of ester oil, ether oil, or alkyl benzene to coat flares and flanges.
Infiltration of a large amount of mineral oil may cause the re­frigerator oil to deteriorate.
Charge the system with refrigerant in the liquid phase.
If gaseous refrigerant is drawn out of the cylinder first, the composition of the remaining refrigerant in the cylinder will change and become unsuitable for use.
Only use R410A.
The use of other types of refrigerant that contain chloride may cause the refrigerator oil to deteriorate.
Use a vacuum pump with a check valve.
If a vacuum pump that is not equipped with a check valve is used, the vacuum pump oil may flow into the refrigerant cy­cle and cause the refrigerator oil to deteriorate.
Prepare tools for exclusive use with R 410A. Do not use the following tools if they have been used with the conventional refrigerant: gauge manifold, charging hose, gas leak detec­tor, check valve, refrigerant charge base, vacuum gauge, and refrigerant recovery equipment.
If the refrigerant or the refrigerator oil that may be left on these tools are mixed in with R410A, it may cause the refrigerator oil in the new system to deteriorate. Infiltration of water may cause the refrigerator oil to deteriorate. Leak detectors for conventional refrigerants will not detect an R410A leak because R410A is free of chlorine.
Do not use a charging cylinder.
If a charging cylinder is used, the composition of the refrigerant in the cylinder will change and become unsuitable for use.
Exercise special care when handling tools for use with R410A.
Infiltration of dust, dirt, or water into the refrigerant system may cause the refrigerator oil to deteriorate.
Page 5
CONTENTS
HWE10170 GB
[1] Components and Functions...................................................................................................... 1
[2] Specifications............................................................................................................................ 3
[3] Sound pressure levels .............................................................................................................. 5
[4] Fan performance and corrected air flow ................................................................................... 8
[5] Outlines and Dimensions........................................................................................................ 10
[6] Wiring Diagram ....................................................................................................................... 11
[7] Refrigerant system diagram.................................................................................................... 12
[8] Troubleshooting ...................................................................................................................... 13
[9] Disassembly Procedure.......................................................................................................... 60
[10] Optional parts ....................................................................................................................... 67
Page 6
HWE10170 GB
Page 7
1- 1 -
HWE10170 GB
XI Indoor Unit
[1] Components and Functions
1. Indoor Unit
2. Remote Controller
[PAR-21MAA] Once the operation mode is selected, the unit will remain in the selected mode until changed.
(1) Remote Controller Buttons
Keep the remote controller out of direct sunlight to ensure accurate measurement of room temperature.The thermistor at the lower right-hand section of the remote controller must be free from obstructions to ensure accurate mea-
surement of room temperature.
(1) In case of rear inlet
1 [Set Temperature] Button 7 [Vane Control] Button 2 [Timer Menu] Button 8 [Ventilation] Button
[Monitor/Set] Button [Operation] Button
3 [Mode] Button 9 [Check/Clear] Button
[Back] Button 10 [Test Run] Button
4 [Timer On/Off] Button 11 [Filter] Button
[Set Day] Button [ ] Button
5 [Louver] Button 12 [ON/OFF] Button
[Operation] Button 13 Position of built-in room thermistor
6 [Fan Speed] Button 14 [Set Time] Button
Air inlet
Air outlet
Page 8
2- 2 -
HWE10170 GB
(2) Remote Controller Display
A Current time/Timer time I Louver swing
B Centralized control indicator J Ventilation
C Timer OFF indicator K Filter sign
D Timer mode indicator L Sensor position
E Operation mode display: COOL, DRY, AUTO,
FAN, HEAT
M Room temperature
F Function mode indicator N Vane setting
G Preset temperature O Fan speed
H Power indicator P Operation lamp
Page 9
3- 3 -
HWE10170 GB
[2] Specifications
1. Specifications
*1 <Cooling> Indoor temperature: 80°FD.B./67°FW.B. (26.7°CD.B./19.4°CW.B.) Outdoor temperature: 95°FD.B.(35°CD.B.)
<Heating> Indoor temperature: 70°FD.B.(21.1°CD.B.) Outdoor temperature: 47°FD.B./43°FW.B. (8.3°CD.B./6.1°CW.B.)
*2 Measured at a power supply voltage of 230 V
Model PEFY-P72NMHSU-E PEFY-P96NMHSU-E
Power supply
Voltage V 1-phase 208-230
Frequency Hz 50/60
Capacity*1 Cooling kW[BTU/h] 21.1 (72,000) 28.1 (96,000)
Heating kW[BTU/h] 23.4 (80,000) 31.7 (108,000)
Power consumption
50Pa
[0.20in.WG]
Cooling kW
0.43 0.59
Heating kW
100Pa
[0.40in.WG]
Cooling kW
0.52 0.70
Heating kW
150Pa
[0.60in.WG]
Cooling kW
0.63 0.82
Heating kW
200Pa
[0.80in.WG]
Cooling kW
0.75 0.95
Heating kW
250Pa
[1.00in.WG]
Cooling kW
0.89 0.97
Heating kW
Current consumption *2
50Pa
[0.20in.WG]
Cooling A
2.31 3.08
Heating A
100Pa
[0.40in.WG]
Cooling A
2.79 3.75
Heating A
150Pa
[0.60in.WG]
Cooling A
3.32 4.43
Heating A
200Pa
[0.80in.WG]
Cooling A
3.95 5.10
Heating A
250Pa
[1.00in.WG]
Cooling A
4.81 5.29
Heating A
External finish Galvanized
Dimensions Height mm[in.] 470 (18-9/16)
Width mm[in.] 1250 (49-1/4)
Depth mm[in.] 1120 (44-1/8)
Net weight 97 100
Heat exchanger Cross fin (Alminium fin and copper tube)
Fan Type Sirocco fan x 2
Airflow rate (H-M-L)
m
3
/min
[cfm]
72-61-50
2542-2154-1766
84-71-58
2966-2507-2048
External static pressure
Pa
[in.WG]
(50)/(100)/150/(200)/(250)
(0.20)/(0.40)/0.60/(0.80)/(1.00)
Motor Output kW 0.87
Air filter Option
Refriferant pipe dimensions Gas
(Brazed connection)
mm ø19.05 ø22.2
[in.] ø3/4 ø7/8
Liquid (Brazed connection)
mm ø9.52
[in.] ø3/8
Drain pipe dimensions mm O.D.32
[in.] 1-1/4
Operating noise (H-M-L) 50Pa [0.20in.WG] dB(A) 39-35-32 42-38-35
100Pa [0.40in.WG] 41-37-34 44-40-37
150Pa [0.60in.WG] 43-39-36 46-42-39
200Pa [0.80in.WG] 45-41-38 48-44-41
250Pa [1.00in.WG] 47-43-40 50-46-43
*
Measured in anechoic room.
2m
1m
Aux. duct
1.5m
Measurement location 2
Page 10
4- 4 -
HWE10170 GB
2. Electrical component specifications
Component Symbol
Room temperature thermistor
TH21 Resistance 32°F (0°C)/15k, 50°F (10°C)/9.6k, 68°F (20°C)/6.3k,
77°F (25°C)/5.4k, 86°F (30°C)/4.3k, 104°F (40°C)/3.0k
Liquid pipe thermistor TH22 Resistance 32°F (0°C)/15k, 50°F (10°C)/9.6k, 68°F (20°C)/6.3k,
77°F (25°C)/5.4k, 86°F (30°C)/4.3k, 104°F (40°C)/3.0k
Gas pipe thermistor TH23 Resistance 32°F (0°C)/15k, 50°F (10°C)/9.6k, 68°F (20°C)/6.3k,
77°F (25°C)/5.4k, 86°F (30°C)/4.3k, 104°F (40°C)/3.0k
Fuse (INV board) F01 250V 15A
Fuse (NF board) F001 250V 10A
Fuse (NF board) F100 250V 3.15A
Fan motor MF 8-pole, Output 870W ERC8801AB
Linear expansion valve
LEV1 LEV2
12VDC Stepping motor drive port diameter ø3.2 (0~2000 pulse)
Power supply terminal block
TB2
(L, N, ) 450V 30A
Page 11
5- 5 -
HWE10170 GB
[3] Sound pressure levels
1. Sound pressure level
Ceiling concealed
2. NC curves
PEFY-P72NMHSU-E
Measurement point
Inlet
Outlet
1.5m
2m
1m
Approximate minimum audible limit on continuous noise
High Middle Low
10.0
15.0
20.0
25.0
30.0
35.0
40.0
45.0
50.0
55.0
60.0
65.0
70.0
63 125 250 500 1k 2k 4k 8k
NC-60
NC-50
Octave band pressure level (dB) 0dB=20μPa
NC-40
NC-30
NC-20
Octave band center frequencies (Hz)
External Static Pressure:50Pa, 0.20[in.WG] Power Source: 208, 230V, 50Hz/60Hz
Approximate minimum audible limit on continuous noise
High Middle Low
10.0
15.0
20.0
25.0
30.0
35.0
40.0
45.0
50.0
55.0
60.0
65.0
70.0
63 125 250 500 1k 2k 4k 8k
NC-60
NC-50
Octave band pressure level (dB) 0dB=20μPa
NC-40
NC-30
NC-20
Octave band center frequencies (Hz)
External Static Pressure:100Pa, 0.40[in.WG] Power Source: 208, 230V, 50Hz/60Hz
Approximate minimum audible limit on continuous noise
High Middle Low
10.0
15.0
20.0
25.0
30.0
35.0
40.0
45.0
50.0
55.0
60.0
65.0
70.0
63 125 250 500 1k 2k 4k 8k
NC-60
NC-50
Octave band pressure level (dB) 0dB=20μPa
NC-40
NC-30
NC-20
Octave band center frequencies (Hz)
External Static Pressure:150Pa, 0.60[in.WG] Power Source: 208, 230V, 50Hz/60Hz
Approximate minimum audible limit on continuous noise
High Middle Low
10.0
15.0
20.0
25.0
30.0
35.0
40.0
45.0
50.0
55.0
60.0
65.0
70.0
63 125 250 500 1k 2k 4k 8k
NC-60
NC-50
Octave band pressure level (dB) 0dB=20μPa
NC-40
NC-30
NC-20
Octave band center frequencies (Hz)
External Static Pressure:200Pa, 0.80[in.WG] Power Source: 208, 230V, 50Hz/60Hz
Page 12
6- 6 -
HWE10170 GB
PEFY-P96NMHSU-E
Approximate minimum audible limit on continuous noise
High Middle Low
10.0
15.0
20.0
25.0
30.0
35.0
40.0
45.0
50.0
55.0
60.0
65.0
70.0
63 125 250 500 1k 2k 4k 8k
NC-60
NC-50
Octave band pressure level (dB) 0dB=20μPa
NC-40
NC-30
NC-20
Octave band center frequencies (Hz)
External Static Pressure:250Pa, 1.00[in.WG] Power Source: 208, 230V, 50Hz/60Hz
Approximate minimum audible limit on continuous noise
High Middle Low
10.0
15.0
20.0
25.0
30.0
35.0
40.0
45.0
50.0
55.0
60.0
65.0
70.0
63 125 250 500 1k 2k 4k 8k
NC-60
NC-50
Octave band pressure level (dB) 0dB=20μPa
NC-40
NC-30
NC-20
Octave band center frequencies (Hz)
External Static Pressure:50Pa, 0.20[in.WG] Power Source: 208, 230V, 50Hz/60Hz
Approximate minimum audible limit on continuous noise
High Middle Low
10.0
15.0
20.0
25.0
30.0
35.0
40.0
45.0
50.0
55.0
60.0
65.0
70.0
63 125 250 500 1k 2k 4k 8k
NC-60
NC-50
Octave band pressure level (dB) 0dB=20μPa
NC-40
NC-30
NC-20
Octave band center frequencies (Hz)
External Static Pressure:100Pa, 0.40[in.WG] Power Source: 208, 230V, 50Hz/60Hz
Approximate minimum audible limit on continuous noise
High Middle Low
10.0
15.0
20.0
25.0
30.0
35.0
40.0
45.0
50.0
55.0
60.0
65.0
70.0
63 125 250 500 1k 2k 4k 8k
NC-60
NC-50
Octave band pressure level (dB) 0dB=20μPa
NC-40
NC-30
NC-20
Octave band center frequencies (Hz)
External Static Pressure:150Pa, 0.60[in.WG] Power Source: 208, 230V, 50Hz/60Hz
Approximate minimum audible limit on continuous noise
High Middle Low
10.0
15.0
20.0
25.0
30.0
35.0
40.0
45.0
50.0
55.0
60.0
65.0
70.0
63 125 250 500 1k 2k 4k 8k
NC-60
NC-50
Octave band pressure level (dB) 0dB=20μPa
NC-40
NC-30
NC-20
Octave band center frequencies (Hz)
External Static Pressure:200Pa, 0.80[in.WG] Power Source: 208, 230V, 50Hz/60Hz
Page 13
7- 7 -
HWE10170 GB
Approximate minimum audible limit on continuous noise
High Middle Low
10.0
15.0
20.0
25.0
30.0
35.0
40.0
45.0
50.0
55.0
60.0
65.0
70.0
63 125 250 500 1k 2k 4k 8k
NC-60
NC-50
Octave band pressure level (dB) 0dB=20μPa
NC-40
NC-30
NC-20
Octave band center frequencies (Hz)
External Static Pressure:250Pa, 1.00[in.WG] Power Source: 208, 230V, 50Hz/60Hz
Page 14
8- 8 -
HWE10170 GB
[4] Fan performance and corrected air flow
PEFY-P72NMHSU-E
Static pressure (Pa)
[in.WG]
Airflow rate (m3/min)
[cfm]
External static pressure :50Pa, 0.20[in.WG] Power source:208, 230V, 50Hz/60Hz
Middle
High
Low
Limit
[2825]
80
[2648]
75
[2472]
70
[2295]
65
[2119]
60
[1942]
55
[1412]
40
[1766]
50
[1589]
45
10
[0.04]
20
[0.08]
30
[0.12]
40
[0.16]
50
[0.20]
60
[0.24]
70
[0.28]
80
[0.32]
0
[0]
Static pressure (Pa)
[in.WG]
Airflow rate (m3/min)
[cfm]
[2825]
80
[2648]
75
[2472]
70
[2295]
65
[2119]
60
[1942]
55
[1412]
40
[1766]
50
[1589]
45
30
[0.12]
40
[0.16]
50
[0.20]
60
[0.24]
70
[0.28]
80
[0.32]
90
[0.36]
100
[0.40]
110
[0.44]
120
[0.48]
130
[0.52]
External static pressure :100Pa, 0.40[in.WG] Power source:208, 230V, 50Hz/60Hz
Middle
High
Low
Limit
External static pressure :150Pa, 0.60[in.WG] Power source:208, 230V, 50Hz/60Hz
Middle
High
Low
Limit
Static pressure (Pa)
[in.WG]
Airflow rate (m3/min)
[cfm]
[2825]
80
[2648]
75
[2472]
70
[2295]
65
[2119]
60
[1942]
55
[1412]
40
[1766]
50
[1589]
45
60
[0.24]
70
[0.28]
80
[0.32]
90
[0.36]
100
[0.40]
110
[0.44]
120
[0.48]
130
[0.52]
140
[0.56]
150
[0.60]
160
[0.64]
170
[0.68]
180
[0.72]
External static pressure :200Pa, 0.80[in.WG] Power source:208, 230V, 50Hz/60Hz
Middle
High
Low
Limit
Static pressure (Pa)
[in.WG]
Airflow rate (m3/min)
[cfm]
[2825]
80
[2648]
75
[2472]
70
[2295]
65
[2119]
60
[1942]
55
[1412]
40
[1766]
50
[1589]
45
80
[0.32]
90
[0.36]
100
[0.40]
110
[0.44]
120
[0.48]
130
[0.52]
140
[0.56]
150
[0.60]
160
[0.64]
170
[0.68]
180
[0.72]
190
[0.76]
200
[0.80]
210
[0.84]
220
[0.88]
230
[0.92]
External static pressure :250Pa, 1.00[in.WG] Power source:208, 230V, 50Hz/60Hz
Middle
High
Low
Limit
Static pressure (Pa)
[in.WG]
Airflow rate (m3/min)
[cfm]
[2825]
80
[2648]
75
[2472]
70
[2295]
65
[2119]
60
[1942]
55
[1412]
40
[1766]
50
[1589]
45
100
[0.40]
110
[0.44]
120
[0.48]
130
[0.52]
140
[0.56]
150
[0.60]
160
[0.64]
170
[0.68]
180
[0.72]
190
[0.76]
200
[0.80]
210
[0.84]
220
[0.88]
230
[0.92]
240
[0.96]
250
[1.00]
260
[1.04]
270
[1.09]
Page 15
9- 9 -
HWE10170 GB
PEFY-P96NMHSU-E
Middle
High
Low
Limit
Static pressure (Pa)
[in.WG]
Airflow rate (m3/min)
[cfm]
External static pressure :50Pa, 0.20[in.WG] Power source:208, 230V, 50Hz/60Hz
[3178]
90
[3001]
85
[2825]
80
[2648]
75
[2472]
70
[2295]
65
[1766]
50
[2119]
60
[1942]
55
10
[0.04]
20
[0.08]
30
[0.12]
40
[0.16]
50
[0.20]
60
[0.24]
70
[0.28]
80
[0.32]
90
[0.36]
100
[0.40]
0
[0]
Middle
High
Low
Limit
Static pressure (Pa)
[in.WG]
Airflow rate (m3/min)
[cfm]
30
[0.12]
40
[0.16]
50
[0.20]
60
[0.24]
70
[0.28]
80
[0.32]
90
[0.36]
100
[0.40]
110
[0.44]
120
[0.48]
130
[0.52]
140
[0.56]
External static pressure :100Pa, 0.40[in.WG] Power source:208, 230V, 50Hz/60Hz
[3178]
90
[3001]
85
[2825]
80
[2648]
75
[2472]
70
[2295]
65
[1766]
50
[2119]
60
[1942]
55
External static pressure :150Pa, 0.60[in.WG] Power source:208, 230V, 50Hz/60Hz
Static pressure (Pa)
[in.WG]
60
[0.24]
70
[0.28]
80
[0.32]
90
[0.36]
100
[0.40]
110
[0.44]
120
[0.48]
130
[0.52]
140
[0.56]
150
[0.60]
160
[0.64]
170
[0.68]
180
[0.72]
190
[0.76]
Middle
High
Low
Limit
Airflow rate (m3/min)
[cfm]
[3178]
90
[3001]
85
[2825]
80
[2648]
75
[2472]
70
[2295]
65
[1766]
50
[2119]
60
[1942]
55
Middle
High
Low
Limit
Airflow rate (m3/min)
[cfm]
External static pressure :200Pa, 0.80[in.WG] Power source:208, 230V, 50Hz/60Hz
Static pressure (Pa)
[in.WG]
80
[0.32]
90
[0.36]
100
[0.40]
110
[0.44]
120
[0.48]
130
[0.52]
140
[0.56]
150
[0.60]
160
[0.64]
170
[0.68]
180
[0.72]
190
[0.76]
200
[0.80]
210
[0.84]
220
[0.88]
230
[0.92]
240
[0.96]
[3178]
90
[3001]
85
[2825]
80
[2648]
75
[2472]
70
[2295]
65
[1766]
50
[2119]
60
[1942]
55
Middle
High
Low
Limit
Airflow rate (m3/min)
[cfm]
External static pressure :250Pa, 1.00[in.WG] Power source:208, 230V, 50Hz/60Hz
Static pressure (Pa)
[in.WG]
100
[0.40]
110
[0.44]
120
[0.48]
130
[0.52]
140
[0.56]
150
[0.60]
160
[0.64]
170
[0.68]
180
[0.72]
190
[0.76]
200
[0.80]
210
[0.84]
220
[0.88]
230
[0.92]
240
[0.96]
250
[1.00]
260
[1.04]
270
[1.09]
280
[1.13]
290
[1.17]
[3178]
90
[3001]
85
[2825]
80
[2648]
75
[2472]
70
[2295]
65
[1766]
50
[2119]
60
[1942]
55
Page 16
10- 10 -
HWE10170 GB
[5] Outlines and Dimensions
Air inlet Air outlet
(DUCT)
(7/16)
(2-3/8)
(3-3/16)
(2-3/8)
(3-15/16x3=11-13/16)
(3-15/16x3=11-13/16)
(1-3/4)
(9-13/16)
(DUCT)
(7/16)
(5/8)
(3-15/16)
(3-15/16)
(15/16)
(3-15/16)
(Actual length)
Drain Piping.
(21-11/16)
(7-7/8~11-13/16)
(17-3/4)
(5-15/16~7-7/8)
(17-3/4)
2X4-ø3(1/8) holes
2X11-ø3(1/8) holes
Drain hole
Drain hole
Control box
(Power source)
Terminal block
(MA remocon)
(Transmission wiring)
(Power souse wiring)
(Normal type)
(Option)
(Transmission)
Suspension bolt hole
Terminal blockKnockout hole ø22.2(7/8)
Knockout hole ø22.2(7/8)
Terminal block
4-14X30(9/16x3/16) Slot
2X4-ø3(1/8) holes
2X11-ø3(1/8) holes
Make the access door
at the appointed position properly
for service maintenance.
Access door Ceiling surface
Access door
Note2
Note3
Required space for service and maintenance.
MODEL
PEFY-P72NMHSU-E
PEFY-P96NMHSU-E
ø
19.05(3/4)
ø
22.2(7/8)
ø
9.52(3/8)
Drain hose 32mm
(1-1/4inch)
<flexible joint>
<accessory>
Note 1.Use M10 screw for the suspension bolt (field supply).
2.Keep the service space for the maintenance from the bottom
when the heat exchanger is cleaned.
3.Keep the service space for the maintenance from the bottom
when the fan motor is changed.
4.Make sure to install the air filter (field supply) on the air intake side.
In case field supplied air filter is used, attach it
where the filter service is easily done.
Unit:mm(in.)
Unit:mm(in.)
249
95(3-4/3)
342(13-1/2)
80
170(6-3/4±1/4)
23
100
470(18-9/16)
20(13/16)
102(4-1/16)
105(4-3/16)
420(16-9/16)
1100(43-5/16)(DUCT)
1250(49-1/4)
1372(54-1/16)
1124(44-5/16)
15
10
100x10=1000(3-15/16x10=39-3/8)
100(3-15/16)
50(2)
60
1326(52-1/4)(Suspension bolt pitch)
1034(40-3/4)(Suspension bolt pitch)
340(13-7/16)
1100(43-5/16)(DUCT)
100
100
29(1-3/16)
41(1-5/8)
1067(42-1/16)
24(1)
1120(44-1/8)
489(19-5/16)
327(12-7/8)
44
164(6-1/2)
30(1-3/16)
15(5/8)
100X3(=300)
100(3-15/16)
20(13/16)
100(3-15/16)
10
100x3=300
60
100x10=1000(3-15/16x10=39-3/8)
50(2)
100(3-15/16)
More than 20(13/16)
More than 20(13/16)
550
50(2)
150~200
50(2)
50(2)
450
800(31-1/2)
450
200~300
1350(53-3/16)
730(28-3/4)
PEFY-P72,96NMHSU-E
Gas pipe
Liquid pipe
Gas pipe
Liquid pipe
Drain hose
Drain hose
Page 17
11- 11 -
HWE10170 GB
[6] Wiring Diagram
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
F
E
D
C
B
A
9
8
7
6
5
4
3
2
1
642
1
3
1
2
2
2
1
1
25431
21
85431
2131442331
4321
6
6
5
5
5
4
4
3
3
3
2
2
1
1
1
54321
12345
1
2
76543213
3
1
1
1
2
3
4
5
3
3
1
1
1
3
8
7
1
6
6
5
3
43
5
3
2
1
1
3
3
1
1
CN25
F01
IPM
(BLUE)
CNCT2
CNFAN
CNP
X010
X100
CNR1
(RED)
(RED)
CNACL
ZNR
003
C015
C016
ZNR
002
DSA
001
ZNR
001
F001
F100
CNPW1
CNRSC
CNRSP
CNXC1
CNXB1
CNDB
CNPW2
CN18V
(GREEN)
CNTH
(RED)
CNCT1
CNRS2
CN15V
CNVDC
CNDP
CNINV
NF
CNXC2
CN100
CN41
CN90
LED2
LED1
CN3A
(BLUE)
CN2M
(BLUE)
CN7V
CN60
CN44
CN4F CN4F
CN20
(RED)
CN32
SW3
SWC
SW5
SWA
SWE
ONOFF
SW2SW1
SW4
SW11SW12SW14
1s
DIGIT DIGIT
( ) ( ) ( )
10ths
BRANCH
No.
CNXB2
POWER SUPPLY
AC208-230V
60Hz
Note 1
Note 1
ACL
2 2
1 1
INSIDE SECTION OF CONTROL BOX
TO MA REMOTE
CONTROLLER
TO OUTDOOR UNIT
BC CONTROLLER
REMOTE CONTROLLER
MF
DP
MS
3
~
M
1
~
UVW
R
NF.B.
INV.B.
I.B.
P.B .
TB2
DB01
ACCT
TB5
TB15
LEV1
LEV2
THHS
TH21
TH22FSTH23
L1
3 4
2
1
33112
2
M1M2S(SHIELD)
L2
G
1
2
DB01 RNF.B.
TB2
TB5
TB15
P. B .
I.B.
ACCT
INV.B.
PARTS LOCATION
Inside < > is the optional parts.
NOTE:1.The part of thin dotted line indicates the circuit for optional parts.
2.To perform a drainage test for the drain pump turn on the SWE
on the control board while the indoor unit is being powerd.
*Be sure to turn off the SWE after completing a drainage test or test run.
3.The wirings to TB2,TB5,TB15 shown in dotted line are field work.
4.Mark indicates terminal block, connector.
5.Use copper supply wire.
SYMBOL NAME
SYMBOL EXPLANATION
Aux. relay
X010,X100
Var ist or
Arrester
Intelligent power module
Fuse(AC250V 15A)
DSA001
IPM
F01
Electronic linear expan.valve
LEV1,LEV2
F001
F100
NF
Fuse(AC250V 10A)
Fuse(3.15A)
Noise filter
Switch (for mode selection)
Switch (for capacity code)
Switch (for mode selection)
Switch (for model selection)
Switch (for mode selection)
Switch (1s digit address set)
Switch (10ths digit address set)
Switch (BRANCH No.)
Switch (for static pressure selection)
Switch (for static pressure selection)
TB2
TB5
TB15
CN25
I.B.
NF.B.
INV.B.
P. B.
TH21
TH22
TH23
THHS
<FS>
Connector
Indoor controller board
Noise filter board
Inverter board
Power supply board
Power source terminal block
Transmission terminal block
Transmission terminal block
Float switch
Thermistor(piping temp.detection/liquid)
Thermistor(piping temp.detection/gas)
Thermistor(heatsink)
Thermistor(inlet air temp.detection)
MF
Fan motor
AC reactor (Power factor improvement)
Resistor
Diode bridge
LED (Power supply)
Current Sensor (AC)
LED (Remote controller supply)
ACL
R
DB01
LED1
ACCT
LED2
Connector (emergency operation)
Connector (Remote switch)
CN32
Connector (HA terminal-A)
CN41
Connector (Wireless)
CN90
SW1
SW2
SW3
SW4
SW5
SW11
SW12
SW14
SWA
SWC
SWE
ZNR01~
ZNR03
Drain pump
<DP>
U
UU
M
M
PEFY-P72,96NMHSU-E
Page 18
12- 12 -
HWE10170 GB
[7] Refrigerant system diagram
(A) Gas pipe thermistor TH23
(B) Gas pipe
(C) Liquid pipe
(D) Brazed connections
(E) Strainer (#100 mesh)
(F) Linear expansion valve
(G) Liquid pipe thermistor TH22
(H) Heat exchanger
(I) Room temperature thermistor TH21
(H)
(I)
(F)
(E)
(E)
(C)
(G)
(A)
(D)
(B)
Page 19
13- 13 -
HWE10170 GB
[8] Troubleshooting
1. Check methods
1. Component and check points (1) Thermistor
Room temperature thermistor (TH21)Liquid pipe thermistor (TH22)Gas pipe thermistor (TH23)
Disconnect the connector and measure the resistance between terminals with a tester. (Ambient temperature 50°F (10°C) - 86°F (30°C))
1) Thermistor characteristic graph
(2) Fan motor
Refer to the page on "DC fan motor (fan motor/INV board)."(page 47)
(3) Linear expansion valve
Refer to the page on "LEV". ([8] 4)(page 51)
Normal Abnormal
4.3k - 9.6k Open or short
(Refer to the thermistor characteristic graph below.)
Low-temperature thermistor
Room temperature thermistor (TH21)Liquid pipe thermistor (TH22)Gas pipe thermistor (TH23)
Thermistor R
0
= 15 kΩ 3%
Multiplier of B = 3480 kΩ 2%
32°F (0°C) 15k 50°F (10°C) 9.6k 68°F (20°C) 6.3k 77°F (25°C) 5.2k 86°F (30°C) 4.3k 104°F (40°C) 3.0k
(A) Temperature °F (°C)
(B) Resistance (kΩ)
Rt = 15 exp { 3480( ) }
1
273+t
1
273
0
10
20
30
40
50
-20 -10 0 10 20 30 40 50
(A)
(B)
Page 20
14- 14 -
HWE10170 GB
2. Error Code Lists
Error Code
Prelimi-
nary error code
Error
(prelim-
inary) detail
code
Error code definition
Searched unit
Notes
0403
4300 4305
01 05
(Note)
Serial communication error O O
0900 - - Test run O
1102 1202 - Discharge temperature fault O
1301 - - Low pressure fault O
1302 1402 - High pressure fault O
1500 1600 - Refrigerant overcharge O
- 1605 - Preliminary suction pressure fault O
2500 - - Drain sensor submergence O
2502 - - Drain pump fault O
2503 - - Drain sensor (Thd) fault O O
2600 - - Water leakage O
2601 - - Water supply cutoff O
4102 4152 - Open phase O
4106 - - Transmission power supply fault O
4109 - - Fan operation status detection error O
4115 - - Power supply signal sync error O
4116 - - RPM error/Motor error O O
4220 4225
(Note)
4320 4325
(Note)
[108] Abnormal bus voltage drop O O
[109] Abnormal bus voltage rise O O
[111] Logic error O O
[131] Low bus voltage at startup O
4230 4235
4330 4335
- Heatsink overheat protection O O
4240 4340 - Overload protection O
4250 4255
(Note)
4350 4355
(Note)
[101] IPM error O O
[104] Short-circuited IPM/Ground fault O O
[105] Overcurrent error due to short-circuited motor O O
[106] Instantaneous overcurrent (S/W detection) O O
[107] Overcurrent (effective value) (S/W detection) O O
[121] Position detection error at startup O
[122] Position detection error during operation O
4260 - - Heatsink overheat protection at startup O
5101 1202 -
Temperature sensor fault
Return air temperature (TH21)
O
OA processing unit inlet temperature (TH4)
O
Outdoor unit
Indoor unit
LOSSNAY
Remote controller
Page 21
15- 15 -
HWE10170 GB
5102 1217 -
Temperature sensor fault
Indoor unit pipe tempera­ture (TH22)
O
OA processing unit pipe temperature (TH2)
O
HIC bypass circuit outlet temperature (TH2)
O
5103 1205 00
Temperature sensor fault
Indoor unit gas-side pipe temperature (TH23)
O
OA processing unit gas­side pipe temperature (TH3)
O
Pipe temperature at heatexchanger outlet (TH3)
O
5104 1202 -
Temperature sensor fault
OA processing unit intake air temperature (TH1)
O
Outside temperature (TH24)
O
Detectable only by the All­Fresh type in­door units
Outdoor unit discharge temperature (TH4)
O
5105 1204 -
Temperature sensor fault
Accumulator inlet tempera­ture (TH5)
O
5106 1216 -
Temperature sensor fault
HIC circuit outlet tempera­ture (TH6)
O
5107 1221 -
Temperature sensor fault
Outside temperature (TH7) O
5110 1214 01
Temperature sensor fault
Heatsink temperature (THHS)
OO
5201 - - High-pressure sensor fault (63HS1) O
5301 5305
4300 4305
[115] ACCT sensor fault O
[117] ACCT sensor circuit fault O O
[119] Open-circuited IPM/Loose ACCT connector O O
[120] Faulty ACCT wiring O
5701 - - Loose float switch connector O
6201 - -
Remote controller board fault (nonvolatile memory error)
O
6202 - - Remote controller board fault (clock IC error) O
6600 - - Address overlap OOOO
6601 - - Polarity setting error O
6602 - - Transmission processor hardware error OOOO
6603 - - Transmission line bus busy error OOOO
6606 - -
Communication error between device and trans­mission processors
OOOO
6607 - - No ACK error OOOO
Error Code
Prelimi-
nary error code
Error
(prelim-
inary) detail
code
Error code definition
Searched unit
Notes
Outdoor unit
Indoor unit
LOSSNAY
Remote controller
Page 22
16- 16 -
HWE10170 GB
The last digit in the check error codes in the 4000's and 5000's and two-digit detail codes indicate if the codes apply to
compressor inverter on fan inverter. Example Code 4225 (detail code 108): Bus voltage drop in the fan inverter system Code 4230 : Heatsink overheat protection in the compressor inverter system
There are no preliminary error codes or detail codes for indoor units.
XII
6608 - - No response error OOOO
6831 - -
MA controller signal reception error (No signal re­ception)
OO
6832 - -
MA remote controller signal transmission error (Synchronization error)
OO
6833 - -
MA remote controller signal transmission error (Hardware error)
OO
6834 - -
MA controller signal reception error (Start bit de­tection error)
OO
7100 - - Total capacity error O
7101 - - Capacity code setting error O O O
7102 - - Wrong number of connected units O
7105 - - Address setting error O
7106 - - Attribute setting error O
7110 - -
Connection information signal transmission/recep­tion error
O
7111 - - Remote controller sensor fault O O
7113 - - Function setting error O
7117 - - Model setting error O
7130 - - Incompatible unit combination O
The last digit Inverter system
0 or 1 Compressor inverter system
5 Fan inverter system
Error Code
Prelimi-
nary error code
Error
(prelim-
inary) detail
code
Error code definition
Searched unit
Notes
Outdoor unit
Indoor unit
LOSSNAY
Remote controller
Page 23
17- 17 -
HWE10170 GB
1. Error Code
Serial communication error (Indoor unit)
2. Error definition and error detection method
Serial communication cannot be established between the Indoor controller board and the INV board.
3. Cause, check method and remedy (1) Faulty wiring
Check the following wiring connections.
1) Between Indoor controller board and Power supply board
2) Between Power supply board and INV board
(2) INV board failure or Indoor controller board failure or Power supply board failure
If the error persists after a power reset, replace the INV board, the Indoor controller board, or the Power supply board.
Refer to section [8] Troubleshooting, item 3. DC fan motor (fan motor/INV board) for error codes related to the inverter. (page 47)
1. Error Code
Drain sensor submergence (Models with a drain sensor)
2. Error definition and error detection method
1) If an immersion of the drain sensor in the water is detected while the unit is in any mode other than the Cool/Dry mode and when the drain pump goes from OFF to ON, this condition is considered preliminary water leakage. While this error is being detected, humidifier output cannot be turned on.(Applicable to the units manufactured in or after October 2006)
2) If the immersion of the sensor in the water is detected four consecutive times at an hour interval, this is considered water leak­age, and "2500" appears on the monitor.
3) Detection of water leakage is also performed while the unit is stopped.
4) Preliminary water leakage is cancelled when the following conditions are met:
One hour after the preliminary water leakage was detected, it is not detected that the drain pump goes from OFF to ON.The operation mode is changed to Cool/Dry.The liquid pipe temperature minus the inlet temperature is -10°C [-18°F] or less.
3. Cause, check method and remedy
0403
2500
CN100 CNRSC
Indoor controller board Power supply board
CNRSP CNRS2
Power supply board INV board
Cause Check method and remedy
(1) Drain water drainage problem
Clogged drain pumpClogged drain pipingBackflow of drain water from other units
Check for proper drainage.
(2) Adhesion of water drops to the drain sensor
Trickling of water along the lead wireRippling of drain water caused by filter clogging
1) Check for proper lead wire installation.
2) Check for clogged filter.
(3) Failure of the relay circuit for the solenoid valve Replace the relay.
(4) Indoor controller board failure
Drain sensor circuit failure
If the above item checks out OK, replace the indoor control­ler board.
Page 24
18- 18 -
HWE10170 GB
1. Error Code
Drain sensor submergence (Models with a float switch)
2. Error definition and error detection method
1) If an immersion of the float switch in the water is detected while the unit is in any mode other than the Cool/Dry mode and when the drain pump goes from OFF to ON, this condition is considered preliminary water leakage. While this error is being detected, humidifier output cannot be turned on.
2) If the drain pump turns on within one hour after preliminary water leakage is detected and the above-mentioned condition is detected two consecutive times, water leakage error water leakage is detected, and "2500" appears on the monitor.
3) Detection of water leakage is also performed while the unit is stopped.
4) Preliminary water leakage is cancelled when the following conditions are met:
One hour after the preliminary water leakage was detected, it is not detected that the drain pump goes from OFF to ON.The operation mode is changed to Cool/Dry.The liquid pipe temperature minus the inlet temperature is - 10°C [ -18°F] or less.
3. Cause, check method and remedy
<Reference>
2500
Cause Check method and remedy
(1) Drain water drainage problem
Clogged drain pumpClogged drain pipingBackflow of drain water from other units
Check for proper drainage.
(2) Stuck float switch
Check for slime in the moving parts of the float switch.
Check for normal operation of the float switch.
(3) Float switch failure Check the resistance with the float switch turned on and
turned off.
6 minutes6 minutes
15
seconds
15
seconds
15
seconds
15
seconds
15
seconds
ON
OFF
ON
OFF
Drain pump operation triggered by a submergence of the liquid level sensor (except during the Cooing/Dry mode)
Drain pump output
Float switch input
Submergence of the sensor
Submergence of the sensor Preliminary water leakage
Submergence of the sensor
Water leakage
Sensor in the airSensor in the air
Within 1-hour periodWithin 1-hour period
Page 25
19- 19 -
HWE10170 GB
1. Error Code
Drain pump fault (Models with a drain sensor)
2. Error definition and error detection method
1) Make the drain sensor thermistor self-heat. If the temperature rise is small, it is interpreted that the sensor is immersed in water. This condition is considered to be a preliminary error, and the unit goes into the 3-minute restart delay mode.
2) If another episode of the above condition is detected during the preliminary error, this is considered a drain pump error, and "2502" appears on the monitor.
3) This error is always detected while the drain pump is in operation.
4) The following criteria are met when the criteria for the forced stoppage of outdoor unit (system stoppage) are met.
"Liquid pipe temperature - inlet temperature -10°C [ -18 °F] " has been detected for 30 minutes.The immersion of drain sensor is detected 10 consecutive times.The conditions that are listed under items 1) through 3) above are always met before the criteria for the forced stoppage
of the outdoor unit.
5) The indoor unit that detected the conditions that are listed in item 4) above brings the outdoor unit in the same refrigerant circuit to an error stop (compressor operation prohibited), and the outdoor unit brings all the indoor units in the same refrigerant circuit that are in any mode other than Fan or Stop to an error stop. "2502" appears on the monitor of the units that came to an error stop.
6) Forced stoppage of the outdoor unit Detection timing: The error is detected whether the unit is in operation or stopped.
7) Ending criteria for the forced stoppage of outdoor unit Power reset the indoor unit that was identified as the error source and the outdoor unit that is connected to the same refrig­erant circuit. Forced stoppage of the outdoor unit cannot be cancelled by stopping the unit via the remote controller. (Note) Items 1) - 3) and 4) - 7) are detected independently from each other.
The address and attribute that appear on the remote controller are those of the indoor unit that caused the error.
3. Cause, check method and remedy
2502
Cause Check method and remedy
(1) Drain pump failure Check for proper functioning of the drain pump.
(2) Drain water drainage problem
Clogged drain pumpClogged drain piping
Check for proper drainage.
(3) Adhesion of water drops to the drain sensor
Trickling of water along the lead wireRippling of drain water caused by filter clogging
1) Check for proper lead wire installation.
2) Check for clogged filter.
(4) Indoor controller board failure
Drain pump drive circuit failureDrain heater output circuit failure
If the above item checks out OK, replace the indoor con­troller board.
(5) Items (1) through (4) above and an indoor unit elec-
tronic valve closure failure (leaky valve) occurred si­multaneously.
Check the solenoid valves on the indoor unit for leaks.
Page 26
20- 20 -
HWE10170 GB
1. Error Code
Drain pump fault (Models with a float switch)
2. Error definition and error detection method
1) The immersion of sensor tip in water is detected by the ON/OFF signal from the float switch.
Submergence of the sensor
When it is detected that the float switch has been ON for 15 seconds, it is interpreted that the sensor tip is immersed in water.
Sensor in the air
When it is detected that the float switch has been OFF for 15 seconds, it is interpreted that the sensor tip is not immersed in water.
2) If it is detected that the float switch has been ON for 3 minutes after the immersion of the sensor tip was detected, this is con­sidered a drain pump failure, and "2502" appears on the monitor.
The total time it takes for this error to be detected is 3 minutes and 15 seconds, including the time it takes for the first im-
mersion of the sensor tip to be detected.
3) Detection of drain pump failure is performed while the unit is stopped.
4) The following criteria are met when the criteria for the forced stoppage of outdoor unit (system stoppage) are met.
"Liquid pipe temperature - inlet temperature - 10°C [ -18°F] " has been detected for 30 minutes.It is detected by the float switch that the sensor tip has been immersed in water for 15 minutes or more.The conditions that are listed under items 1) through 3) above are always met before the criteria for the forced stoppage
of the outdoor unit.
5) The indoor unit that detected the conditions that are listed in item 4) above brings the outdoor unit in the same refrigerant circuit to an error stop (compressor operation prohibited), and the outdoor unit brings all the indoor units in the same refrigerant circuit that are in any mode other than Fan or Stop to an error stop.
6) Forced stoppage of the outdoor unit Detection timing: The error is detected whether the unit is in operation or stopped. This error is detected whether the unit is in operation or stopped.
7) Ending criteria for the forced stoppage of outdoor unit Power reset the indoor unit that was identified as the error source and the outdoor unit that is connected to the same refrig­erant circuit. Forced stoppage of the outdoor unit cannot be cancelled by stopping the unit via the remote controller. (Note) Items 1) - 3) and 4) - 7) are detected independently from each other.
The address and attribute that appear on the remote controller are those of the indoor unit that caused the error.
3. Cause, check method and remedy
2502
Cause Check method and remedy
(1) Drain pump failure Check for proper functioning of the drain pump
mechanism
(2) Drain water drainage problem
Clogged drain pumpClogged drain piping
Check for proper drainage.
(3) Stuck float switch
Check for slime in the moving parts of the float switch.
Check for normal operation of the float switch.
(4) Float switch failure Check the resistance with the float switch turned
on and turned off.
(5) Indoor controller board failure
Drain pump drive circuit failureFloat switch input circuit failure
Replace indoor controller board.
(6) Items (1) through (5) above and an indoor unit electronic
valve closure failure (leaky valve) occurred simultane­ously.
Check the solenoid valves on the indoor unit for leaks.
Page 27
21- 21 -
HWE10170 GB
1. Error Code
Drain sensor (Thd) fault
2. Error definition and error detection method
If the open or short circuit of the thermistor has been detected for 30 seconds, this condition is considered to be a preliminary
error, and the unit goes into the 3-minute restart delay mode.
If another episode of the above condition is detected during the preliminary error, this is considered a drain sensor error.(If
the short or open circuit of the thermistor is no longer detected, normal operation will be restored in 3 minutes.)
This error is detected when one of the following conditions are met.
During Cool/Dry operationLiquid pipe temperature minus inlet temperature is equal to or smaller than - 10°C [ -18°F] (except during the defrost cycle)When the liquid temperature thermistor or suction temperature thermistor or short or open circuited.Drain pump is in operation.One hour has elapsed since the drain sensor went off.
Short: 90°C [194 °F] or above Open: - 20°C [-4 °F] or below
3. Cause, check method and remedy
1. Error Code
Indoor unit fan operation error
2. Error definition and error detection method
1) Connector CN28 has remained open-circuited for 100 consecutive secondsduring operation.
3. Cause, check method and remedy
2503
Cause Check method and remedy
(1) Faulty connector (CN31) insertion. 1) Check for connector connection failure.
Reinsert the connector, restart the operation, and check for proper operation.
(2) Broken or semi-broken thermistor wire 2) Check for a broken thermistor wire.
(3) Thermistor failure 3) Check the resistance of the thermistor.
0°C[32 °F]:6.0k 10°C[50 °F]:3.9k 20°C[68°F]:2.6k 30°C[86°F]:1.8k 40°C[104 °F]:1.3k
(4) Indoor controller board (error detection circuit)
failure
4) Replace the indoor controller board if the problem recurs when the unit is operated with the No.-1 and No.-2 pins on the drain sensor connector (CN31) being short-circuited. If the above item checks out OK, there are no problems with the drain sensor. Turn off the power and turn it back on.
4109
Cause Check method and remedy
(1) Auxiliary relay (X13) fault The coil or the wiring of the auxiliary relay connected to
CN28 is faulty.
(2) Connector (CN28) is disconnected. Check the connector for proper connection.
(3) Blown fuse Check the fuse on the control circuit board.
(4) Motor error (thermistor error inside the motor) Check the unit fan for proper operation in the test run
mode. If no problems are found with items 1 through 3 above and the fan does not operate, replace the motor.
Page 28
22- 22 -
HWE10170 GB
1. Error Code
RPM error/Motor error
2. Error definition and error detection method
LOSSNAY
The motor keep running even if the power is OFF.The thermal overload relay is ON. (Only for the three-phase model)
Indoor unit
If detected less than 180rpm or more than 2000rpm, the indoor unit will restart and keep running for 3 minutes.If detected again, the display will appear.
3. Cause, check method and remedy
1. Error Code
Abnormal bus voltage drop (Indoor unit)
2. Error definition and error detection method
If Vdc 130V or less is detected during Inverter operation. (S/W detection)
3. Cause, check method and remedy (1) Power supply environment
Check whether the unit makes an instantaneous stop when the detection result is abnormal or a power failure occurs. Check whether the power voltage is 198V or above across all phases.
(2) Voltage drop detected
Check the voltage at CNVDC (between pins 1 and 3(+)) on the INV board while the inverter is stopped and if it is less than 220V, check the following items.
1) Check the wiring between TB2 and NF board, NF board and ACL, NF board and inrush current resistor, NF board and DB01, NF board and INV board, NF board and indoor controller board.
2) Check the inrush current resistance.
Measure the interphase resistance of the resistor (R). 22 10%
3) Check ACL for broken wires.
Check that the resistance between pins 1 and 3 (housing side) of the CNACL connector is not infinite ( ).
4) Check the diode bridge (DB01) for problem.
Refer to section 5. "Troubleshooting the diode bridge".(page 50)
5) If no problems were found with items 1) through 4) above, replace the NF board.
(3) Indoor controller board failure
Confirm that DC12V is applied to the connector CNXB2 (between pins 4 and 5(+)) on the Indoor controller board while the inverter is operating. If not, replace the Indoor controller board.
(4) NF board failure
If the unit stops within 10 seconds after resuming operation and the same error is detected, replace the NF board.
(5) INV board failure
If no problems were found with items (1) through (4) above, replace the INV board.
Refer to section [8] Troubleshooting, item 3. DC fan motor (fan motor/INV board) for error codes related to the inverter. (page 47)
4116
Cause Check method and remedy
(1) Board failure Replace the board.
(2) Motor malfunction Check for the motor and the solenoid switch.
(3) Solenoid switch malfunction
4225
Page 29
23- 23 -
HWE10170 GB
1. Error Code
Abnormal bus voltage rise (Indoor unit)
2. Error definition and error detection method
If Vdc 425V is detected during inverter operation.
3. Cause, check method and remedy (1) Different voltage connection
Check the power supply voltage on the power supply terminal block (TB2).
(2) INV board failure
If the problem recurs, replace the INV board.
Refer to section [8] Troubleshooting, item 3. DC fan motor (fan motor/INV board) for error codes related to the inverter. (page 47)
1. Error Code
Logic error (Indoor unit)
2. Error definition and error detection method
H/W error If only the H/W error logic circuit operates, and no identifiable error is detected.
3. Cause, Check method and remedy
Refer to section [8] Troubleshooting, item 3. DC fan motor (fan motor/INV board) for error codes related to the inverter. (page 47)
1. Error Code
Heatsink overheat protection (Indoor unit)
2. Error definition and error detection method
When the heat sink temperature (THHS) remains at or above 85°C [185°F] is detected.
3. Cause, check method and remedy
Refer to section [8] Troubleshooting, item 3. DC fan motor (fan motor/INV board) for error codes related to the inverter. (page 47)
4225
4225
Cause Check method and remedy
(1) External noise If the problem recurs when the unit is put into opera-
tion, replace the INV board.
(2) INV board failure
4235
Cause Check method and remedy
(1) Air passage blockage Check that the heat sink cooling air passage is not blocked
(2) Fan motor error Check the fan motor for proper operation (sound, vibration, and rotation).
If any problems were found, check the items listed in sections 2 [3] and [4].
->Refer to [8] 3.2[3][4].(page 49)
(3) THHS failure If the problem persists after resuming operation, replace the THHS sensor.
(4) INV board fault If no problems were found with items (1) through (3) and the same error is de-
tected after resuming operation, replace the INV board.
Page 30
24- 24 -
HWE10170 GB
1. Error Code
IPM error (Indoor unit)
2. Error definition and error detection method
IPM error signal is detected.
3. Cause, check method and remedy
Refer to section [8] Troubleshooting, item 3. DC fan motor (fan motor/INV board) for error codes related to the inverter. (page 47)
1. Error Code
Instantaneous overcurrent (Indoor unit) Overcurrent (Indoor unit)
2. Error definition and error detection method
Overcurrent 18 Arms and above is detected by the current sensor.
3. Cause, check method and remedy
Refer to section [8] Troubleshooting, item 3. DC fan motor (fan motor/INV board) for error codes related to the inverter. (page 47)
4255
Cause Check method and remedy
(1) Power supply environment Check the power supply voltage.
Check whether the power voltage is 176V or above across all phases.
(2) Static pressure setting error Check that the static pressure setting and the design static pressure
are correct.
(3) Inverter failure or fan motor error 1) Refer to [8] 3.2.[1].(page 48)
2) Refer to [8] 3.2.[2].(page 48)
3) Refer to [8] 3.2.[3].(page 49)
4) Refer to [8] 3.2.[4].(page 49)
4255
Cause Check method and remedy
(1) Power supply environment Check the power supply voltage.
Check whether the power voltage is 176V or above across all phases.
(2) Static pressure setting error Check that the static pressure setting and the design static pres-
sure are correct.
(3) Inverter failure or fan motor error 1) Refer to [8] 3.2.[1].(page 48)
2) Refer to [8] 3.2.[2].(page 48)
3) Refer to [8] 3.2.[3].(page 49)
4) Refer to [8] 3.2.[4].(page 49)
Page 31
25- 25 -
HWE10170 GB
1. Error Code
Short-circuited IPM/Ground fault (Indoor unit)
2. Error definition and error detection method
When IPM/IGBT short damage or grounding on the load side is detected just before starting the inverter.
3. Cause, check method and remedy
Refer to section [8] Troubleshooting, item 3. DC fan motor (fan motor/INV board) for error codes related to the inverter. (page 47)
1. Error Code
Overcurrent error due to short-circuited motor (Indoor unit)
2. Error definition and error detection method
When a short is detected on the load side just before starting the inverter operation.
3. Cause, Check method and remedy
Refer to section [8] Troubleshooting, item 3. DC fan motor (fan motor/INV board) for error codes related to the inverter. (page 47)
4255
Cause Check method and remedy
(1) Ground fault of the fan motor Refer to [8] 3.2.[4].(page 49)
(2) Inverter failure 1) Refer to [8] 3.2.[1].(page 48)
2) Refer to [8] 3.2.[2].(page 48)
4255
Cause Check method and remedy
(1) Short-circuited fan motor coil or inverter failure 1) Refer to [8] 3.2.[1].(page 48)
2) Refer to [8] 3.2.[2].(page 48)
3) Refer to [8] 3.2.[3].(page 49)
(2) Output wiring Check for a short circuit
Page 32
26- 26 -
HWE10170 GB
1. Error Code
Position detection error at startup (Indoor unit)
2. Error definition and error detection method
Position error is detected by the hall sensor at inverter startup.
3. Cause, Check method and remedy
Refer to section [8] Troubleshooting, item 3. DC fan motor (fan motor/INV board) for error codes related to the inverter. (page 47)
1. Error Code
Position detection error during operation (Indoor unit)
2. Error definition and error detection method
Position error is detected by the hall sensor during operation.
3. Cause, Check method and remedy
Refer to section [8] Troubleshooting, item 3. DC fan motor (fan motor/INV board) for error codes related to the inverter. (page 47)
4255
Cause Check method and remedy
(1) Loose connector Check the CNCT1 and CNINV connectors on the
INV board for proper connection.
(2) Inverter failure or fan motor error 1) Refer to [8] 3.2.[2].(page 48)
2) Refer to [8] 3.2.[3].(page 49)
4255
Cause Check method and remedy
(1) Loose connector Check the CNCT1 and CNINV connectors on the
INV board for proper connection.
(2) Inverter failure or fan motor error 1) Refer to [8] 3.2.[2].(page 48)
2) Refer to [8] 3.2.[3].(page 49)
Page 33
27- 27 -
HWE10170 GB
1. Error Code
Return air temperature sensor (TH21) fault (Indoor unit) Return air temperature sensor (TH4) fault (OA processing unit)
Pipe temperature sensor (TH22) fault (Indoor unit) Pipe temperature sensor (TH2) fault (OA processing unit)
Gas-side pipe temperature sensor (TH23) fault (Indoor unit) Gas-side pipe temperature sensor (TH3) fault (OA processing unit)
Intake air temperature sensor (TH1) fault (OA processing unit) Intake air temperature sensor (TH24) fault (All-fresh (100% outdoor air) type indoor unit)
2. Error definition and error detection method
If a short or an open is detected during thermostat ON, the outdoor unit turns to anti-restart mode for 3 minutes. When the
error is not restored after 3 minutes (if restored, the outdoor unit runs normally), the outdoor unit makes an error stop. Short: detectable at 90°C [194°F] or higher
Open: detectable at -40°C [-40°F] or lower
Sensor error at gas-side cannot be detected under the following conditions.
During heating operationDuring cooling operation for 3 minutes after the compressor turns on.
3. Cause, check method and remedy
5101
5102
5103
5104
Cause Check method and remedy
(1) Thermistor failure Check the thermistor resistor.
0°C [32°F]: 15 kohm 10°C [50°F]: 9.7 kohm 20°C [68°F] : 6.4 kohm 30°C [86°F] : 4.3 kohm 40°C [104°F] : 3.1 kohm
(2) Connector contact failure
(3) Disconnected wire or partial disconnected
thermistor wire
(4) Unattached thermistor or contact failure
(5) Indoor board (detection circuit) failure Check the connector contact.
When no fault is found, the indoor board is a failure.
Page 34
28- 28 -
HWE10170 GB
1. Error Code
Heatsink temperature sensor (THHS) fault (Indoor unit)
2. Error definition and error detection method
When a short or an open of THHS is detected just before or during the inverter operation.
3. Cause, check method and remedy
Refer to section [8] Troubleshooting, item 3. DC fan motor (fan motor/INV board) for error codes related to the inverter. (page 47)
1. Error Code
ACCT sensor circuit fault (Indoor unit)
2. Error definition and error detection method
When abnormal value is detected by the ACCT detection circuit immediately before the inverter starts
3. Cause, check method and remedy
Refer to section [8] Troubleshooting, item 3. DC fan motor (fan motor/INV board) for error codes related to the inverter. (page 47)
5110
Cause Check method and remedy
(1) Loose connector Check the CNTH on the INV board for proper connection.
(2) THHS sensor fault If the problem persists after resuming operation, replace the THHS sensor.
(3) INV board failure If no problems were found with items (1) and (2) above and the problem per-
sists after resuming operation, replace the INV board.
5305
Cause Check method and remedy
(1) INV board failure Refer to [8] 3.2.[1].(page 48)
(2) Fan motor error Refer to [8] 3.2.[4].(page 49)
Page 35
29- 29 -
HWE10170 GB
1. Error Code
Open-circuited IPM/Loose ACCT connector (Indoor unit)
2. Error definition and error detection method
ACCT sensor detected that not enough current is available.
3. Cause, check method and remedy
Refer to section [8] Troubleshooting, item 3. DC fan motor (fan motor/INV board) for error codes related to the inverter. (page 47)
1. Error Code
Loose float switch connector
2. Error definition and error detection method
Detection of the disconnected float switch (open-phase condition) during operation
3. Cause, check method and remedy (1) CN4F disconnection or contact failure
Check for disconnection of the connector (CN4F) on the indoor controller board.
5305
Cause Check method and remedy
(1) Disconnected ACCT sensor Check CNCT2 on the INV board for proper connection.
(2) ACCT sensor fault Disconnect the CNCT2 connector, and check the resistance between
the terminals. Refer to [8] 3.4.(page 50)
(3) Inverter failure or fan motor error 1) Refer to [8] 3.2.[2].(page 48)
2) Refer to [8] 3.2.[4].(page 49)
3) If no problems were found with items 1) and 2) above and the prob­lem persists after resuming operation, replace the INV board and the ACCT sensor.
4) If the problem persists after taking step 3) above, replace the fan mo­tor.
5701
Page 36
30- 30 -
HWE10170 GB
1. Error Code
Address overlap
2. Error definition and error detection method
An error in which signals from more than one indoor units with the same address are received
The address and attribute that appear on the remote controller indicate the controller that detected the error.
3. Cause, check method and remedy
6600
Cause Check method and remedy
(1) Two or more of the following have the same address:
Outdoor units, indoor units, LOSSNAY units, control­lers such as ME remote controllers. <Example> 6600 "01" appears on the remote controller Unit #01 detected the error. Two or more units in the system have 01 as their ad­dress.
Find the unit that has the same address as that of the error
source.Once the unit is found, correct the address.
Then, turn off the outdoor units, indoor units, and LOSSNAY units, keep them all turned off for at least five minutes, and turn them back on.
When air conditioning units are operating normally despite
the address overlap error Check the transmission wave shape and noise on the transmission line. Refer to the service handbook that came with the outdoor unit.
(2) Signals are distorted by the noise on the transmission
line.
Page 37
31- 31 -
HWE10170 GB
1. Error Code
Transmission processor hardware error
2. Error definition and error detection method
Although "0" was surely transmitted by the transmission processor, "1" is displayed on the transmission line.
The address/attribute appeared on the display on the remote controller indicates the controller where an error oc­curred.
3. Cause
1) When the wiring work of or the polarity of either the indoor or outdoor transmission line is performed or is changed while the power is on, the transmitted data will collide, the wave shape will be changed, and an error will be detected.
2) Grounding fault of the transmission line
3) When grouping the indoor units that are connected to different outdoor units, the male power supply connectors on the multiple outdoor units are connected to the female power supply switch connector (CN40).
4) When the power supply unit for transmission lines is used in the system connected with MELANS, the male power supply connector is connected to the female power supply switch connector (CN40) on the outdoor unit.
5) Controller failure of the source of the error
6) When the transmission data is changed due to the noise on the transmission line
7) Voltage is not applied on the transmission line for centralized control (in case of grouped indoor units connected to different outdoor units or in case of the system connected with MELANS)
4. Check method and remedy
6602
NO
Tightly reconnect the male power supply connector to the female power supply switch connector (CN40).
YES
YES
YES
YES
YES
YES
NO
NO
NO
NO
Is the transmission line work performed while the power is on?
Check the power source of the indoor unit.
198 / 264V?
Check the transmission line work is performed and the shielded wire is treated properly.
Grounding fault or does the shielded wire contact with the transmission line?
System ?
Faulty power source work
Improper transmission line work
Turn off the power source of outdoor/indoor units, and turn them on again.
NO
Investigation into the transmission line noise
Noise exist?
Controller failure of the source of the error
*For the investigation method, follow <Investigation method of transmission wave shape/noise>
Investigation into the cause of the noise
Correct the error.
System with the power supply unit for transmission lines
Is the male power supply connector connected to the female power supply switch connector (CN40) on only one of the outdoor unit?
Is the male power supply connector connected to the female power supply switch connector (CN40) ?
Confirm that the power supply connector on the outdoor unit is not plugged into CN40.
Confirm that the power supply connector on the outdoor unit is not plugged into CN40.
Disconnect the male power supply on CN40 and connect it to CN41
Single-outdoor-unit system
Multiple-outdoor-unit system
Page 38
32- 32 -
HWE10170 GB
1. Error Code
Transmission line bus busy error
2. Error definition and error detection method
Generated error when the command cannot be transmitted for 4-10 minutes in a row due to bus-busyGenerated error when the command cannot be transmitted to the transmission line for 4-10 minutes in a row due to noise
The address/attribute appeared on the display on the remote controller indicates the controller where an error oc­curred.
3. Cause, check method and remedy
1. Error Code
Communication error between device and transmission processors
2. Error definition and error detection method
Communication error between the main microcomputer on the indoor unit board and the microcomputer for transmission
The address/attribute appeared on the display on the remote controller indicates the controller where an error oc­curred.
3. Cause, check method and remedy
6603
Cause Check method and remedy
(1) The transmission processor cannot be transmit-
ted as the short-wavelength voltage like noise ex­ists consecutively on the transmission line.
Check the transmission wave shape and noise on the transmission line. Refer to the service handbook that came with the outdoor unit.
-> No noise indicates that the error source controller is a failure.
-> If noise exists, investigate the noise.
(2) Error source controller failure
6606
Cause Check method and remedy
(1) Data is not properly transmitted due to accidental
erroneous operation of the controller of the error source.
Turn off the power source of the outdoor and the indoor units.(When the power source is turned off separately, the microcomputer will not be reset, and the error will not be corrected.)
-> If the same error occurs, the error source controller is a failure.
(2) Error source controller failure
Page 39
33- 33 -
HWE10170 GB
1. Error Code
No ACK error
2. Error definition and error detection method
The error is detected when no acknowledgement (ACK signal) is received after the transmission. (eg. When the data is trans­mitted six times in a row with 30 seconds interval, the error is detected on the transmission side.)
The address/attribute appeared on the display on the remote controller indicates the controller which did not provide the response (ACK).
3. System configuration (1) System with one outdoor unit
6607
Error
source ad-
dress
Error display
Detection
method
Cause Check method and remedy
Outdoor unit (OC)
ME remote controller (RC) MA remote controller (MA)
No acknowl­edgement (ACK) at IC transmis­sion to OC
(1) Contact failure of transmission
line of OC or IC
Turn off the power source of the outdoor unit, and turn it on again. If the error is accidental, it will run normally. If not, check the causes (1) - (4).
(2) Decrease of transmission line
voltage/signal by exceeding ac­ceptable range of transmission wiring. Farthest:200 m [656ft] or less Remote controller wiring: 10m [32ft] or less
(3) Erroneous sizing of transmission
line (Not within the range below). Wire diameter:
1.25mm2 [AWG16] or more
(4) Indoor unit control board failure
Indoor unit (IC)
ME remote controller (RC) MA remote controller (MA)
No acknowl­edgement (ACK) at RC transmis­sion to IC
(1) When IC unit address is changed
or modified during operation.
Turn off the outdoor/indoor units for 5 or more minutes, and turn them on again. If the error is accidental, they will run normally. If not, check the causes (1) - (5).
(2) Faulty or disconnected IC trans-
mission wiring
(3) Disconnected IC connector
(CN2M)
(4) Indoor unit controller failure
(5) ME remote controller failure
LOSSNAY (LC)
ME remote controller (RC) MA remote controller (MA)
No acknowl­edgement (ACK) at IC transmis­sion to LC
(1) The power source of LOSSNAY
has been shut off.
Turn off the power source of LOSSNAY and turn it on again. If the error is accidental, it will run normally. If not, check the causes (1) - (5).
(2) When the address of LOSSNAY
is changed in the middle of the operation
(3) Faulty or disconnected transmis-
sion wiring of LOSSNAY
(4) Disconnected connector (CN1)
on LOSSNAY
(5) Controller failure of LOSSNAY
ME remote controller (RC)
ME remote controller (RC) MA remote controller (MA)
No acknowl­edgement (ACK) at IC transmis­sion to RC
(1) Faulty transmission wiring at IC
unit side.
Turn off the power source of the outdoor unit for 5 minutes or more, and turn it on again. If the error is accidental, it will run normally. If not, check the causes (1) - (4).
(2) Faulty wiring of the transmission
line for ME remote controller
(3) When the address of ME remote
controller is changed in the mid­dle of the operation
(4) ME remote controller failure
Page 40
34- 34 -
HWE10170 GB
1. Error Code
No ACK error
2. Error definition and error detection method
The error is detected when no acknowledgement (ACK signal) is received after the transmission. (eg. When the data is trans­mitted six times in a row with 30 seconds interval, the error is detected on the transmission side.)
The address/attribute appeared on the display on the remote controller indicates the controller which did not provide the response (ACK).
3. System configuration (2) Grouping of units in a system with multiple outdoor units
6607
Error
source
address
Error display
Detection
method
Cause Check method and remedy
Outdoor unit (OC)
ME remote controller (RC) MA remote controller (MA)
No acknowl­edgement (ACK) at IC transmission to OC
Same cause as that for sys­tem with one outdoor unit
Same remedy as that for sys­tem with one outdoor unit
Indoor unit (IC)
ME remote controller (RC) MA remote controller (MA)
No acknowl­edgement (ACK) at RC transmission to IC
(1) Same causes as (1) - (5) for
system with one outdoor unit
1) Turn off the power sources of the outdoor and indoor units for 5 or more minutes, and turn them on again. If the error is accidental, the will run normal­ly.If not, check the cause 2).
(2) Disconnection or short circuit
of the transmission line for the outdoor unit on the termi­nal block for centralized con­trol line connection (TB7)
2) Check the causes of (1) - (5). If the cause is found, correct it. If no cause is found, check 3).
(3) When multiple outdoor units
are connected and the pow­er source of one of the out­door units has been shut off.
3) Check the LED displays for troubleshooting on other re­mote controllers whether an error occurs.
(4) The male power supply con-
nector of the outdoor unit is not connected to the female power supply switch connec­tor (CN40).
If an error is found,
-> If an error is found, check the check code definition, and correct the error. If no error is found,
-> Indoor unit board failure
(5) The male power supply con-
nectors on 2 or more outdoor units are connected to the fe­male power supply switch connector (CN40) for cen­tralized control.
If an error occurs, after the unit runs normally once, the following causes may be considered.
Total capacity error
(7100)
Capacity code error
(7101)
Error in the number of
connected units (7102)
Address setting error
(7105)
Page 41
35- 35 -
HWE10170 GB
1. Error Code
No ACK error
2. Error definition and error detection method
The error is detected when no acknowledgement (ACK signal) is received after the transmission. (eg. When the data is trans­mitted six times in a row with 30 seconds interval, the error is detected on the transmission side.)
The address/attribute appeared on the display on the remote controller indicates the controller which did not provide the response (ACK).
3. System configuration (2) Grouping of units in a system with multiple outdoor units
6607
Error
source
address
Error display
Detection
method
Cause Check method and remedy
LOSS­NAY (LC)
ME remote controller (RC) MA remote controller (MA)
No acknowl­edgement (ACK) at IC transmission to LC
(1) Factors (1) through (5) in the
"Factors in system with one outdoor unit" (When perform­ing an interlocked operation of the LOSSNAY unit and the indoor units that are connect­ed to different outdoor units.)
1) Turn off the power source of LOSSNAY for 5 or more min­utes, and turn it on again. If the error is accidental, it will run normally.If not, check the cause 2).
(2) Disconnection or short circuit
of the transmission line for the outdoor unit on the termi­nal block for centralized con­trol line connection (TB7)
2) Check the causes of (1) - (5). If the cause is found, correct it. If no cause is found, check 3).
(3) When multiple outdoor units
are connected and the power source of one of the outdoor units has been shut off.
3) Same cause as that for indoor unit described in 3)
(4) The male power supply con-
nector of the outdoor unit is not connected to the female power supply switch connec­tor (CN40).
(5) The male power supply con-
nectors on 2 or more outdoor units are connected to the fe­male power supply switch connector (CN40) for central­ized control.
If an error occurs, after the unit runs normally once, the following causes may be con­sidered.
Total capacity error
(7100)
Capacity code error
(7101)
Error in the number of
connected units (7102)
Address setting error
(7105)
Page 42
36- 36 -
HWE10170 GB
1. Error Code
No ACK error
2. Error definition and error detection method
The error is detected when no acknowledgement (ACK signal) is received after the transmission. (eg. When the data is trans­mitted six times in a row with 30 seconds interval, the error is detected on the transmission side.)
The address/attribute appeared on the display on the remote controller indicates the controller which did not provide the response (ACK).
3. System configuration (2) Grouping of units in a system with multiple outdoor units
6607
Error
source
address
Error display
Detection
method
Cause Check method and remedy
ME re­mote con­troller (RC)
ME remote controller (RC) MA remote controller (MA)
No acknowl­edgement (ACK) at IC transmission to RC
(1) Same causes as (1) - (4) for
system with one outdoor unit
1) Turn off the power source of LOSSNAY for 5 or more min­utes, and turn it on again. If the error is accidental, it will run normally.If not, check the cause 2).
(2) Disconnection or short circuit
of the transmission line for the outdoor unit on the termi­nal block for centralized con­trol line connection (TB7)
2) Check the causes of (1) - (5). If the cause is found, correct it. If no cause is found, check 3).
(3) When multiple outdoor units
are connected and the power source of one of the outdoor units has been shut off.
3) Same cause as that for indoor unit described in 3)
(4) The male power supply con-
nector of the outdoor unit is not connected to the female power supply switch connec­tor (CN40).
(5) The male power supply con-
nectors on 2 or more outdoor units are connected to the fe­male power supply switch connector (CN40) for central­ized control.
If the problem recurs after normal operation is restored, the problem is caused by one of the following factors:
Total capacity error
(7100)
Capacity code setting
error (7101)
Error in the number of
connected units (7102)
Address setting error
(7105)
Page 43
37- 37 -
HWE10170 GB
1. Error Code
No ACK error
2. Error definition and error detection method
The error is detected when no acknowledgement (ACK signal) is received after the transmission. (eg. When the data is trans­mitted six times in a row with 30 seconds interval, the error is detected on the transmission side.)
The address/attribute appeared on the display on the remote controller indicates the controller which did not provide the response (ACK).
3. System configuration (3) System connected to the system controllers (MELANS)
6607
Error
source
address
Error display
Detection
method
Cause Check method and remedy
Out­door unit (OC)
ME remote controller (RC) System control­ler (SC) MA remote controller (MA)
No acknowl­edgement (ACK) at IC transmis­sion to OC
Same cause as that for system with one outdoor unit
Same remedy as that for system with one outdoor unit
Indoor unit (IC)
ME remote controller (RC) MA remote controller (MA)
No acknowl­edgement (ACK) at RC transmis­sion to IC
Same as grouping of units in a system with multiple outdoor units
Same remedy as that for grouping of units in a sys­tem with multiple outdoor units
System control­ler (SC)
No acknowl­edgement (ACK) at SC transmis­sion to IC
1. Error occurrence on some IC Same remedy as that for system with one outdoor unit
(1) Same cause as that for system with one
outdoor unit
2. Error occurrence on all IC in the system
with one outdoor unit
1) Check the LED display for troubleshooting on the outdoor unit.
(1) Total capacity error (7100) If an error is found,
check the check code definition, and correct the error.
If no error is found,
check 2).
(2) Capacity code error (7101)
(3) Error in the number of connected units
(7102)
(4) Address setting error (7105)
(5) Disconnection or short circuit of the trans-
mission line for the outdoor unit on the ter­minal block for centralized control line connection (TB7)
2) Check (5) - (7) on the left.
(6) Turn off the power source of the outdoor
unit
(7) Malfunction of electrical system for the
outdoor unit
3. Error occurrence on all IC Check voltage of the transmission line for cen­tralized control.
20V or more: Check (1)
and (2) on the left.
Less than 20V: Check
(3) on the left.
(1) Same causes as (1) - (7) described in 2.
(2) The male power supply connectors on 2
or more outdoor units are connected to the female power supply switch connector (CN40) for the transmission line for cen­tralized control.
(3) Disconnection or shutdown of the power
source of the power supply unit for trans­mission line
(4) System controller (MELANS) malfunction
Page 44
38- 38 -
HWE10170 GB
1. Error Code
No ACK error
2. Error definition and error detection method
The error is detected when no acknowledgement (ACK signal) is received after the transmission. (eg. When the data is trans­mitted six times in a row with 30 seconds interval, the error is detected on the transmission side.)
The address/attribute appeared on the display on the remote controller indicates the controller which did not provide the response (ACK).
3. System configuration (3) System connected to the system controllers (MELANS)
6607
Error
source
address
Error display
Detection
method
Cause Check method and remedy
ME re­mote con­troller (RC)
ME remote controller (RC) System con­troller (SC) MA remote controller (MA)
No acknowl­edgement (ACK) at IC transmission to RC
Same as grouping of units in a sys­tem with multiple outdoor units
Same remedy as that for grouping of units in a system with multiple outdoor units
System con­troller (SC)
No acknowl­edgement (ACK) at MELANS transmission to RC
1. Error occurrence on some IC Same remedy as that for system with one outdoor unit
(1) Same cause as that for system
with one outdoor unit
2. Error occurrence on all IC in the
system with one outdoor unit
1) Check the LED display for troubleshooting on the out­door unit.
(1) An error is found by the outdoor
unit. Total capacity error (7100) Capacity code error (7101) Error in the number of connected units (7102) Address setting error (7105)
If an error is found, check
the check code definition, and correct the error.
If no error is found, check
the cause 2).
(2) Disconnection or short circuit of the
transmission line for the outdoor unit on the terminal block for cen­tralized control line connection (TB7)
2) Check (2) - (4) on the left.
(3) Turn off the power source of the
outdoor unit
(4) Malfunction of electrical system for
the outdoor unit
3. Error occurrence on all IC Check (1) - (4) on the left.
(1) Same causes as (1) - (4) described
in 2.
(2) When the power supply unit for
transmission lines is used and the male power supply connector is connected to the female power supply switch connector (CN40) for the transmission line for central­ized control
(3) Disconnection or shutdown of the
power source of the power supply unit for transmission line
(4) System controller (MELANS) mal-
function
Page 45
39- 39 -
HWE10170 GB
1. Error Code
No ACK error
2. Error definition and error detection method
The error is detected when no acknowledgement (ACK signal) is received after the transmission. (eg. When the data is trans­mitted six times in a row with 30 seconds interval, the error is detected on the transmission side.)
The address/attribute appeared on the display on the remote controller indicates the controller which did not provide the response (ACK).
3. System configuration (3) System connected to the system controllers (MELANS)
6607
Error
source
address
Error display
Detection
method
Cause Check method and remedy
System controller (SC)
ME remote controller (RC) MA remote controller (MA)
No acknowl­edgement (ACK) at IC transmission to SC
1. Error display on some displays on ME remote controllers
Check (1) - (3) on the left.
(1) Faulty wiring of the transmission
line for ME remote controller
(2) Disconnection or contact failure of
the transmission connector for ME remote controller
(3) ME remote controller failure
2. Error occurrence on all IC in the system with one outdoor unit
1) Check the LED display for troubleshooting on the out­door unit.
(1) An error is found by the outdoor
unit. Total capacity error (7100) Capacity code error (7101) Error in the number of connected units (7102) Address setting error (7105)
If an error is found, check
the check code definition, and correct the error.
If no error is found, check
the cause 2)
(2) Disconnection or short circuit of the
transmission line for the outdoor unit on the terminal block for cen­tralized control line connection (TB7)
2) Check (2) - (4) on the left.
(3) Turn off the power source of the
outdoor unit
(4) Malfunction of electrical system for
the outdoor unit
3. Error display on all displays on ME remote controllers
Check (1) - (4) on the left
(1) Same causes as (1) - (4) described
in 2.
(2) When the power supply unit for
transmission lines is used and the male power supply connector is connected to the female power sup­ply switch connector (CN40) for the transmission line for centralized control
(3) Disconnection or shutdown of the
power source of the power supply unit for transmission line
(4) System controller (MELANS) mal-
function
Page 46
40- 40 -
HWE10170 GB
1. Error Code
No ACK error
2. Error definition and error detection method
The error is detected when no acknowledgement (ACK signal) is received after the transmission. (eg. When the data is trans­mitted six times in a row with 30 seconds interval, the error is detected on the transmission side.)
The address/attribute appeared on the display on the remote controller indicates the controller which did not provide the response (ACK).
3. System configuration (4) Errors that are not limited to a particular system
6607
Error
source ad-
dress
Error dis-
play
Detection
method
Cause Check method and remedy
Address which should not be existed
- - (1) Although the address of ME remote controller has been changed after the group is set using ME remote controller, the indoor unit is keeping the memory of the previous ad­dress. The same symptom will appear for the registration with SC.
Delete unnecessary informa­tion of non-existing address which some indoor units have. Use either of the following two methods for deletion.
(2) Although the address of
LOSSNAY has been changed after the interlock registration of LOSSNAY is made using ME remote controller, the in­door unit is keeping the mem­ory of the previous address.
1) Address deletion by ME remote controller Delete unnecessary address in­formation using the manual set­ting function of ME remote controller. Refer to Outdoor ser­vice handbook.
2) Deletion of connection informa­tion of the outdoor unit by the deleting switch
Note that the above method will delete all the group set­tings set via the ME remote controller and all the inter­lock settings between LOSS­NAY units and indoor units.
Turn off the power source of
the outdoor unit, and wait for 5 minutes.
Turn on the dip switch (SW2-
2) on the outdoor unit control board.
Turn on the power source of
the outdoor unit, and wait for 5 minutes.
Turn off the power source of
the outdoor unit, and wait for 5 minutes.
Turn off the dip switch (SW2-
2) on the outdoor unit control board.
Turn on the power source of
the outdoor unit.
Page 47
41- 41 -
HWE10170 GB
1. Error Code
No response error
2. Error definition and error detection method
When no response command is returned although acknowledgement (ACK) is received after transmission, an error is detect-
ed.
When the data is transmitted 10 times in a row with 3 seconds interval, an error is detected on the transmission side.
The address/attribute appeared on the display on the remote controller indicates the controller where an error oc­curred.
3. Cause
1) The transmission line work is performed while the power is on, the transmitted data will collide, and the wave shape will be changed.
2) The transmission is sent and received repeatedly due to noise.
3) Decrease of transmission line voltage/signal by exceeding acceptable range of transmission wiring. Farthest:200m [656ft] or less
Remote controller wiring:12m [39ft] or less
4) The transmission line voltage/signal is decreased due to erroneous sizing of transmission line. Wire diameter: 1.25mm
2
[AWG16] or more
4. Check method and remedy
1) When an error occurs during commissioning, turn off the power sources for the outdoor unit, indoor unit, and LOSSNAY for 5 or more minutes, and then turn them on again.
When they return to normal operation, the cause of the error is the transmission line work performed with the power on.If an error occurs again, check the cause 2).
2) Check 3) and 4) above.
If the cause is found, correct it. If no cause is found, check 3).
3) Check transmission wave shape/ noise on trans-mission line by following the instructions detailed in the Outdoor service handbook.
Noise is the most possible cause of the error "6608".
6608
Page 48
42- 42 -
HWE10170 GB
1. Error Code
MA controller signal reception error (No signal reception)
2. Error definition and error detection method
Communication between the MA remote controller and the indoor unit is not done properly. No proper data has been received for 3 minutes.
3. Cause
1) Contact failure of the remote controller lines of MA remote controller or the indoor unit.
2) All the remote controllers are set to SUB.
3) Failure to meet wiring regulations
Wire lengthWire sizeNumber of remote controllersNumber of indoor units
4) The remote controller is removed after the installation without turning the power source off.
5) Noise interference on the remote controller transmission lines
6) Faulty circuit that is on the indoor board and performs transmission/ reception of the signal from the remote controller
7) Problems with the circuit on the remote controller that sends or receives the signals from the remote controller
4. Check method and remedy
1) Check for disconnected or loose transmission lines for the indoor units or MA remote controllers.
2) Confirm that the power is supplied to the main power source and the remote controller line.
3) Confirm that MA remote controller's capacity limit is not exceeded.
4) Check the sub/main setting of the MA remote controllers.One of them must be set to MAIN.
5) Diagnose the remote controller (described in the remote controller installation manual). [OK]: no problems with the remote controller (check the wiring regulations)
[NG]: Replace the MA remote controller. [6832, 6833, ERC]: Due to noise interference <Go to 6)>
6) Check wave shape/noise on MA remote controller line by following the instructions detailed in the Outdoor service handbook.
7) When no problems are found with items 1) through 6), replace the indoor unit board or the MA remote controller. The following status can be confirmed on LED1 and 2 on the indoor unit board.
If LED1 is lit, the main power source of the indoor unit is turned on.If LED2 is lit, the MA remote controller line is being powered.
6831
Page 49
43- 43 -
HWE10170 GB
1. Error Code
MA remote controller signal transmission error (Synchronization error)
2. Error definition and error detection method
MA remote controller and the indoor unit is not done properly.Failure to detect opening in the transmission path and unable to send signals
Indoor unit : 3 minutesRemote controller : 6 seconds
3. Cause
1) Contact failure of the remote controller lines of MA remote controller or the indoor unit
2) 2 or more remote controllers are set to MAIN
3) Overlapped indoor unit address
4) Noise interference on the remote controller lines
5) Failure to meet wiring regulations
Wire lengthWire sizeNumber of remote controllersNumber of indoor units
6) Problems with the circuit on the remote controller that sends or receives the signals from the remote controller
4. Check method and remedy
1) Check for disconnected or loose transmission lines for the indoor units or MA remote controllers.
2) Confirm that the power is supplied to the main power source and the remote controller line.
3) Confirm that MA remote controller's capacity limit is not exceeded.
4) Check the sub/main setting of the MA remote controllers.One of them must be set to MAIN.
5) Diagnose the remote controller (described in the remote controller installation manual). [OK]: no problems with the remote controller (check the wiring regulations)
[NG]: Replace the MA remote controller. [6832, 6833, ERC]: Due to noise interference <Go to 6)>
6) Check wave shape/noise on MA remote controller line by following the instructions detailed in the Outdoor service handbook.
7) When no problems are found with items 1) through 6), replace the indoor unit board or the MA remote controller. The following status can be confirmed on LED1 and 2 on the indoor unit board.
If LED1 is lit, the main power source of the indoor unit is turned on.If LED2 is lit, the MA remote controller line is being powered.
6832
Page 50
44- 44 -
HWE10170 GB
1. Error Code
MA remote controller signal transmission error (Hardware error)
2. Error definition and error detection method
Communication between the MA remote controller and the indoor unit is not done properly.An error occurs when the transmitted data and the received data differ for 30 times in a row.
3. Cause
1) Contact failure of the remote controller lines of MA remote controller or the indoor unit
2) 2 or more remote controllers are set to MAIN
3) Overlapped indoor unit address
4) Noise interference on the remote controller lines
5) Failure to meet wiring regulations
Wire lengthWire sizeNumber of remote controllersNumber of indoor units
6) Problems with the circuit on the remote controller that sends or receives the signals from the remote controller
4. Check method and remedy
1) Check for disconnected or loose transmission lines for the indoor units or MA remote controllers.
2) Confirm that the power is supplied to the main power source and the remote controller line.
3) Confirm that MA remote controller's capacity limit is not exceeded.
4) Check the sub/main setting of the MA remote controllers.One of them must be set to MAIN.
5) Diagnose the remote controller (described in the remote controller installation manual). [OK]: no problems with the remote controller (check the wiring regulations)
[NG]: Replace the MA remote controller. [6832, 6833, ERC]: Due to noise interference <Go to 6)>
6) Check wave shape/noise on MA remote controller line by following the instructions detailed in the Outdoor service handbook.
7) When no problems are found with items 1) through 6), replace the indoor unit board or the MA remote controller. The following status can be confirmed on LED1 and 2 on the indoor unit board.
If LED1 is lit, the main power source of the indoor unit is turned on.If LED2 is lit, the MA remote controller line is being powered.
6833
Page 51
45- 45 -
HWE10170 GB
1. Error Code
MA controller signal reception error (Start bit detection error)
2. Error definition and error detection method
Communication between the MA remote controller and the indoor unit is not done properly.No proper data has been received for 2 minutes.
3. Cause
1) Contact failure of the remote controller lines of MA remote controller or the indoor unit.
2) All the remote controllers are set to SUB.
3) Failure to meet wiring regulations
Wire lengthWire sizeNumber of remote controllersNumber of indoor units
4) The remote controller is removed after the installation without turning the power source off.
5) Noise interference on the remote controller transmission lines
6) Faulty circuit that is on the indoor board and performs transmission/ reception of the signal from the remote controller
7) Problems with the circuit on the remote controller that sends or receives the signals from the remote controller
4. Check method and remedy
1) Check for disconnected or loose transmission lines for the indoor units or MA remote controllers.
2) Confirm that the power is supplied to the main power source and the remote controller line.
3) Confirm that MA remote controller's capacity limit is not exceeded.
4) Check the sub/main setting of the MA remote controllers.One of them must be set to MAIN.
5) Diagnose the remote controller (described in the remote controller installation manual). [OK]: no problems with the remote controller (check the wiring regulations)
[NG]: Replace the MA remote controller. [6832, 6833, ERC]: Due to noise interference <Go to 6)>
6) Check wave shape/noise on MA remote controller line by following the instructions detailed in the Outdoor service handbook.
7) When no problems are found with items 1) through 6), replace the indoor unit board or the MA remote controller. The following status can be confirmed on LED1 and 2 on the indoor unit board.
If LED1 is lit, the main power source of the indoor unit is turned onIf LED2 is lit, the MA remote controller line is being powered.
6834
Page 52
46- 46 -
HWE10170 GB
1. Error Code
Capacity code setting error
2. Error definition and error detection method
Connection of incompatible (wrong capacity code) indoor unit or outdoor unit
3. Error source, cause, check method and remedy
1. Error Code
Remote controller sensor fault
2. Error definition and error detection method
This error occurs when the temperature data is not sent although the remote controller sensor is specified.
3. Error source, cause, check method and remedy
7101
Error source Cause Check method and remedy
Outdoor unit Indoor unit
(1) The model name (capacity code) set by
the switch (SW2) is wrong.
1) Check the model name (capacity code) of the in­door unit which has the error source address set by the switch (SW2 on indoor unit board). When the model name set by the switch is different from that of the unit connected, turn off the power source of the outdoor and the indoor units, and change the setting of the capacity code.
*The capacity of the indoor unit can be confirmed by the self-diagnosis function (SW1 operation) of the outdoor unit.
Outdoor unit (2) The model selection switches (SW5-1 -
5-4) on the outdoor unit are set incor­rectly.
Check the setting for the model selection switch on the outdoor unit (Dipswitches SW5-1 - 5-4 on the outdoor unit control board).
7111
Error source Cause Check method and remedy
Indoor unit OA process­ing unit
The remote controller without the temperature sensor (the wireless remote controller or the ME compact remote controller (mounted type)) is used and the remote controller sen­sor for the indoor unit is specified. (SW1-1 is ON.)
Replace the remote controller with the one with built-in temperature sensor.
72 model
96 model
120 model
144 model
SW5
OFF
ON
OFF
OFF
ON
ON
OFF
ON
OFF
OFF
ON
ON
OFF
OFF
OFF
OFF
1 2 3 4
Model
Page 53
47- 47 -
HWE10170 GB
3. DC fan motor (fan motor/INV board)
If there are problems only with the fan motor, replace the fan motor only
. (Fan motor failure will cause an overcurrent to pass through the inverter, but the inverter is protected from damage with the protection function that will stop the inverter when an overcurrent is detected.)
If the inverter fails, replace the failed components on the inverter.If both the fan motor and inverter fail, replace the fan motor and all applicable parts on the inverter.
1. Troubleshooting the inverter-related problems
1) Inside the inverter is a large capacity electrolytic capacitor, and the residual voltage that remains after the main power is turned off presents a risk of electric shock. Before checking the inverter-related parts, turn off the main power, keep it turned off for at least 10 minutes, and check that the voltage at both ends of the main capacitor (C015, C016) has dropped to a safe level.
Measure the voltage at both ends of the electrolytic capacitor at the check point where "CHECK VOLTAGE" is written in the
left top area of the NF board.
2) The IPM on the inverter becomes damaged if there are loose screws or connectors. When a problem occurs after replacing components, faulty wiring is often the cause of the problem. Check the wiring, screws, connectors, and Fasten terminals for proper connection.
3) Do not plug or unplug the inverter connectors while the main power is turned on, as this will result in damage to the circuit board.
4) Electric current sensor will break if a current is passed through the sensor without it being connected to the circuit board. Con­nect the current sensor to the appropriate connectors on the circuit board before operating the inverter.
Error codes and symptoms Check items
[1] Inverter-related errors
4255, 4225, 4235, 5110, 5305
Check the error history on the outdoor unit circuit board LED.
[2] Main power breaker is tripped. 1) Check the breaker capacity.
2) Check the electric circuits other than the inverter circuits for short-circuit and ground fault.
3) If no problems are found with items 1) and 2), see 3.-[1].
[3] The main earth leakage breaker
is tripped.
1) Check the capacity and the sensitivity current of the earth leakage breaker.
2) Insulation resistance failure of the electrical components other than the in­verter
3) If no problems are found with items 1) and 2), see 3.-[1].
[4] Only the fan motor is inoperative. Check the display on the remote controller. If the fan is in operation, proceed to
section 2.-[2] and 2.-[3].
[5] The fan motor vibrates excessive-
ly or makes abnormal sounds.
See 2.-[2] and 2.-[3].
[6] Peripheral devices pick up electri-
cal noise.
1) Check that the power wire to the peripheral devices are not routed adjacent to the power wire to the indoor unit.
2) Check that the inverter output wiring is not routed adjacent to the power wire or transmission line.
3) Check that a shielded cable is used if required. Check that the shield is prop­erly grounded.
4) Insulation resistance failure of the electrical components other than the in­verter
5) Connect the unit to a different power supply circuit.
6) If the problem appeared suddenly, there is a possibility that the inverter output line had a ground fault. See section 2.-[2] and 2.-[3].
For problems other than the ones listed above, consult your dealer.
[7] Accidental malfunction (due to
external noise)
1) Check that the unit is properly grounded.
2) Check that a shielded cable is used if required. Check that the shield is prop­erly grounded.
3) Check that the transmission line or wiring to external devices are not routed adjacent to the power wires or are placed in the same conduit with them.
For problems other than the ones listed above, consult your dealer.
Page 54
48- 48 -
HWE10170 GB
2. Troubleshooting the inverter output-related problems
Check items Symptoms Actions to take
[1] Check the INV board error detec­tion circuit. (unloaded)
(1) Turn off the breaker.
Be sure to turn off the
breaker.
1) Overcurrent errors Error code:4255
Replace the INV board.
(2) Disconnect the connec-
tor CNINV from the INV board.
2) Logic error Error code:4225
Replace the INV board.
(3) Turn on the breaker. 3) ACCT sensor circuit failure
Error code:5305
Replace the INV board.
(4) Operate the indoor
units.
4) Position detection error Error code:4255
If the problem described at left happens when the power is turned on for the first time, replace the INV board.
Removing the connector CNINV while
the power is turned on can cause the problem described at left. Be sure to turn off the power before disconnecting the connector CNINV.
5) Open-circuited IPM or dis­connected ACCT sensor Error code:5305
Normal
[2] Check the inverter for damage. (unloaded)
(1) Turn off the breaker.
Be sure to turn off the
breaker.
1) An error is detected in less than 30 seconds of startup. (LED2 on the INV board lights up.)
Replace the INV board.
(2) Disconnect the connec-
tor CNINV from the INV board.
2) The line voltage imbalance is 5V or greater.
Replace the INV board.
(3) Turn SW2-1 on the INV
board to ON.
3) There is no line voltage im­balance. An error is detected after 30 seconds of startup (LED2 on the INV board lights up.), and the units will stop.
Normal Reconnect the CNINV connector, and
set the SW2 back to its original setting after checking.
(4) Turn on the breaker.
(5) Operate the indoor
units. The units will operate for approximately 30 sec­onds unloaded and then stop. Error code:4255 During the unloaded op­eration, a constant line voltage of approximately 20V will be output.
Page 55
49- 49 -
HWE10170 GB
3. Troubleshooting when the main power breaker trips
Check items Symptoms Actions to take
[3] Check for inverter damage. (loaded)
(1) Turn off the breaker. 1) The units stop within 10 sec-
onds of startup, and a posi­tion detection error or an overcurrent error is detect­ed. Error code:4255
Check to see if the fan motor is locked.
Replace the fan motor if it is locked. If the problem persists after replacing the fan motor, replace the INV board.
If the fan motor is not locked, go to item [4]. If no problems were found with item [4], replace the INV board. If the problem persists after replacing the INV board, replace the fan motor.
(2) Turn on the breaker. 2) An overcurrent error is de-
tected after approximately 10 seconds of operation. Error code:4255
a)Replace the INV board. b)If the problem persists after replacing
the INV board, replace the fan motor.
(3) Operate the indoor
units.
3) Overcurrent error due to short-circuited motor Error code:4255
a)If no problems were found with items
[1] and [2], check for short-circuited mo­tor wiring.
b)If no problems were found with item a),
replace the fan motor.
c)If the problem persists after replacing
the fan motor, replace the INV board.
4) A line voltage imbalance ex­ceeds the greater of the fol­lowing after the rotation speed has been stabilized: 5% or 5V.
a)If a voltage imbalance is detected, go to
item [4].
b)If no problems were found with item [4],
replace the INV board.
c)If the problem persists after replacing
the INV board, replace the fan motor.
[4] Check the fan motor for a ground fault and check the coil for problems.
Disconnect the indoor unit fan motor wiring, and check the resistance and the wire­wound resistance of the fan motor.
1) Insulation resistance failure of the fan motor Insulation resistance of be­low 1 M is considered ab­normal.
Replace the fan motor.
2) Broken fan motor wire Reference value: Normal wirewound resistance is several ohms. (Varies with the tempera­ture)
Replace the fan motor.
Check items Symptoms Actions to take
[1] Check the resistance between the
terminals of power supply terminal block TB2 with an ohmmeter.
1) 0 to several ohms, or insula­tion resistance failure
Check the components in the main invert­er circuit. *Refer to "4. Simple check on the main in­verter circuit components".(page 50)
a) Diode bridge b) Inrush current limiting resistor c) AC reactor (ACL) d) Current sensor (ACCT)
[2] Turn the power back on and check
again.
1) Main power breaker is tripped.
2) Nothing appears on the re­mote controller.
[3] Check the indoor unit for normal
operation.
1) The indoor unit operates nor­mally without tripping the main breaker.
a) Look for a possible short-circuit, and if
found, repair.
b) If no problems are found with item "a)"
there may be problems with the fan motor.
2) Main power breaker is tripped. The fan motor may have had a ground
fault. See section 2.-[1].
Page 56
50- 50 -
HWE10170 GB
4. Simple check on the main inverter circuit components
Turn off the power supply, take the following components out of the control box, and then check the components.
5. Troubleshooting the diode bridge Measure the resistance between terminals of the diode bridge with a tester, and use the measured value for troubleshooting.
1) Read before taking measurements.
Check the polarity before taking measurements. Black is positive on a regular multimeter when it is used to measure resis-
tance.
Check that the circuit is not completely open ( ) or short-circuited (- 0 ).These resistance measurement values are provided only as a guide, and small deviations from these values are allowed.If the resistance between a given terminal and other terminals all fall within a range of minus 50% and plus 100%, the resis-
tance is normal.
2) Tester restrictions
Use a tester that has an internal voltage supply of 1.5 V or greater.Use a dry-battery-powered tester.
(An accurate diode resistance measurement cannot be obtained with a button-battery-operated card tester because of its low applied voltage.)
Use a tester that can measure in small increments.
It will allow for more accurate measurement.
3) External view
4) Internal circuit diagram
6. Precautions for inverter parts replacement
1) Check for faulty or loose wiring. To avoid damage to the IPM, thoroughly check the wiring to the main circuit components in the diode bridge.
2) Securely attach the diode bridge with mounting screws.
Parts name Evaluation criteria
Diode bridge Refer to "5. Troubleshooting the diode bridge".
Inrush current limiting resistor R Measure the resistance between terminals : 22  10%
AC reactor (ACL)
Measure the resistance between terminals. : 1 or less Measure the resistance between terminals and the chassis:
Current sensor ACCT
Disconnect the CNCT2 connector, and check the resistance between the terminals. 580 30
THHS sensor Disconnect the connector CNTH, and measure the resistance between connector ter-
minals. Check that the terminals are not short-circuited (0 ) or open-circuited ( ).
<Reference values for resistance check>
Black ( + )
+ - ~(L) ~(N)
Red (-)
+ - - 5 - 200 5 - 200
-- -
~(L) 5 - 200 --
~(N) 5 - 200 --
~(N)
-
+
~(L)
L
+
-
N
Page 57
51- 51 -
HWE10170 GB
4. LEV LEV operation
An LEV (Indoor unit: Linear expansion valve), is a stepping-motor-driven valve that operates by receiving the pulse signals from the indoor and outdoor unit control boards.
1. Indoor LEV The valve opening changes according to the number of pulses.
(1) Indoor controller board and LEV connection.
(2) Pulse signal output and valve operation
(3) LEV valve closing and opening operation
(A) Brown (F) White
(B) Red (G) Control board
(C) Blue (H) Connection (CN60,CN7V)
(D) Orange (I) Drive circuit
(E) Yellow (J) Linear expansion valve
4
3
6
5
2
1
(G)
(H)
(I)
(J)
(A)
(A)
(B)
(B)
(C)
(C)
(D)
(D)
(E)
(E)
(F)
(F)
12VDC
M
4
6
2
3
5
1
Output state
Output
(phase)
number
1234
1 ON OFF OFF ON
2 ON ON OFF OFF
3 OFF ON ON OFF
4 OFF OFF ON ON
Output pulses change in the following orders when the Valve is closed; 1 2 3 4 1 Valve is open;
4 3 2 1 4
*1. When the LEV opening angle does not change, all the output phases will be off. *2. When the output is open phase or remains ON, the motor cannot run smoothly, and rattles and vibrates.
*When the power is turned on, the valve closing signal of 2200 pulses will be output from the indoor board to LEV to fix the valve position. It must be fixed at point A .
When the valve operates smoothly, no sound from LEV or no vibration occurs, however, when the pulses change from E to A in the chart or the valve is locked, a big sound occurs.
*Whether a sound is generated or not can be determined by holding a screwdriver against it, then placing your ear against the handle.
Valve opening (refrigerant flow rate)
Valve closed
Valve open
E
B
80 - 100 pulses
Pulses
Fully open: 2000 pulses
A
C
D
Page 58
52- 52 -
HWE10170 GB
2. Judgment methods and possible failure mode
Malfunction
mode
Judgment method Remedy
Microcomputer driver circuit fail­ure
Disconnect the control board connector and connect the check LED as shown in the figure below.
resistance : 0.25W 1k LED : DC15V 20mA or more When the main power is turned on, the indoor controller board outputs pulse signals to the indoor unit LEV for 10 seconds, and the outdoor unit circuit board outputs pulse signals to the outdoor unit LEV for 17 seconds. If any of the LED remains lit or unlit, the drive circuit is faulty.
When the drive circuit has a problem, replace the control board.
LEV mechanism is locked
If the LEV is locked, the drive motor runs idle, and makes a small clicking sound. When the valve makes a closing and opening sound, the valve has a problem.
Replace the LEV.
Disconnected or short-circuited LEV motor coil
Measure resistance between the coils (red - white, red
-orange, brown - yellow, brown - blue) using a tester. They are normal if resistance is 150ohm 10%.
Replace the LEV coils.
Incomple sealing (leak from the valve)
When checking the refrigerant leak from the indoor LEV, run the target indoor unit in the fan mode, and the other indoor units in the cooling mode. Then, check the liquid temperature (TH22) with the self-diagnosis LED. When the unit is running in the fan mode, the LEV is ful­ly closed, and the temperature detected by the thermis­tor is not low. If there is a leak, however, the temperature will be low. If the temperature is extremely low compared with the inlet temperature displayed on the remote controller, the LEV is not properly sealed, however, if there is a little leak, it is not necessary to re­place the LEV when there are no effects to other parts.
If there is a large amount of leakage, replace the LEV.
Faulty wire con­nections in the connector or faulty contact
1. Check for loose pins on the connector and check the colors of the lead wires visually
Check the continuity at the points where an error occurs.
2. Disconnect the control board's connector and conduct a continuity check using a tester.
6
5
4
3
2
1
1 k
LED
Thermistor (liquid piping temperature detection)
Linear Expansion Valve
Page 59
53- 53 -
HWE10170 GB
5. Address switch setting Make sure that power to the unit is turned off.
Indoor controller board
1. Address is set with a combination of SW12 (10's digit) and SW11 (1's digit). To set the address to "3," set SW12 to "0" and SW11 to "3."
To set the address to "25," set SW 12 to "2" and SW 11 to "5."
SW1
SW4
SW2 SW3
SWA
SW5
SWC
SW14 SW12 SW11
Page 60
54- 54 -
HWE10170 GB
6. Test point diagram
1. Indoor controller board
2. Noise filter board (NF board)
CN2M For M-NET transmission cable con-
nection (24 - 30VDC)
SWE Emergency operation
SW2 Capacity setting
SW4 Function setting
SW3 Function setting
CN32 Remote start/stop adapter
CN3A For MA remote controller cable con-
nection (10 - 13 VDC (Between 1 and 3.))
CN52 Remote display
CN51 Centralized control
CN41 JAMA standard HA terminal A
CN44 Thermistor (liquid/gas temperature)
CN4F Connector for float switch
CN20 Thermistor (Inlet temperature)
CN100 Connect to the Power supply board
CNDP Power supply voltage (220-240VAC)
CNACL Connect to the AC reactor
CNR1 Connect to the Resistor
CNDB Connect to the Diode bridge
CNPW1 Connect to the Power supply board
CNFAN Connect to the INV board
CNXB1 Connect to the indoor controller
board
TP001, TP002
CNP
Measure the charged voltage of the inverter electrolytic capacitor here. TP001···Anode TP002···Cathode
Connect to the drain pump (Optional parts)
CN3A
CN2M
SW4
CN32
SW3
CN41
CN51 CN52
CN20
CN4F
CN44
SWE
SW2
CN100
CNXB1
CNP
CNFAN
CNPW1
TP002
CNDP
CNDB
CNR1
CNACL
TP001
Page 61
55- 55 -
HWE10170 GB
3. Power supply board
4. INV board
CNPW2 Connect to the NF board
CNCX1 Connect to the indoor controller
board
CNRSC Connect to the indoor controller
board
CNRSP Connect to the INV board
CN18V Connect to the INV board
SW2 Inverter function setting
CNVDC Connect to the NF board
CNINV Connect to the FAN motor
(Power line)
CN15V Connect to the Power supply board
CNRS2 Connect to the Power supply board
CNCT1 Connect to the FAN motor
(Rotor position sensor input)
CNCT2 Connect to the Current sensor
CNTH Connect to the Thermistor (heat sink)
CN3A
CN2M
SW4
CN32
SW3
CN41
CN51 CN52
CN20
CN4F
CN44
SWE
SW2
CN100
CN18V
CNPW2
CNRSP
CNRSC
CNXC1
CN3A
CN2M
SW4
CN32
SW3
CN41
CN51 CN52
CN20
CN4F
CN44
SWE
SW2
CN100
CN15V
CNRS2
CNINV
CNVDC
SW2 CNTH CNCT1 CNCT2
Page 62
56- 56 -
HWE10170 GB
7. Dipswitch setting (Factory setting)
1. Function setting
(1) SW1
(2) SW3
Dipswitch settings must be made while the unit is stopped.
Switch position Function Switch setting
ON OFF
1 Active Thermistor
(Intake air thermistor)
Built-in thermistor on the remote controller
Indoor unit
2 Filter clogging detection Available Unavailable
3 Filter life 2500 hr 100 hr
4 Outdoor air intake Enabled Disabled
5 Remote display Thermo-ON signal Fan output
6 Humidifier operation During heating mode During heating operation
7 Fan speed Low Very low
8 Fan speed at heating Thermo-OFF Preset fan speed Follows the setting of SW1-7
9 Auto restart after power failure Enabled Disabled
10 Power start/stop Enabled Disabled
Factory setting
Switch position Function Switch setting
ON OFF
1 Unit type Cooling only Heat pump
2- - -
3- - -
4- - -
5- - -
6- - -
7- - -
8 Heating 4-deg up Disabled Enabled
9- - -
10 - - -
Factory setting
Page 63
57- 57 -
HWE10170 GB
2. Capacity code setting
(1) SW2
Dipswitch settings must be made while the unit is stopped. Factory setting The switches are set to correspond to the unit capacity.
3. Model setting
(1) SW4
1) Indoor controller board Dipswitch settings must be made while the unit is stopped.
Note: Changes made to the dipswitches SW1, SW2, and SW3 will become effective when the unit comes to a stop (remote controller off). There is no need to power cycle the unit.
4. Power voltage setting
(1) SW5
1) Indoor controller board Dipswitch settings must be operated with the main power turned OFF.
5. External static pressure
(1) SWA, SWC
1) Indoor controller board
Note: Changes that are made to the dipswitches SWA and SWC immediately become effective regardless of the unit's operation status (RUN/STOP) or the remote controller status (ON/OFF).
CAUTION
If the static pressure setting for the duct is lower than that for the unit, the fan of the unit may repeat start/stop, and the static pressure setting may automatically be lowered. Check the static pressure setting, and then match the static pressure setting for the unit to that for the duct. When the static pressure setting is lowered, reset the power supply of the system or change the static pressure setting, and then the static pressure setting that has been automatically lowered will be reset.
PEFY-P72 PEFY-P96
Factory setting
Factory setting Set SW5 to 240V side when the power supply is 230 volts.
When the power supply is 208 volts, set SW5 to 220V side.
All models Factory
setting
220V
(208V)
240V
(230V)
External static pressure
SWA SWC
50Pa
100Pa
150Pa
200Pa
250Pa
3 2 1
3 2 1
3 2 1
3 2 1
3 2 1
1
2
3
SWA SWC
1
2
Page 64
58- 58 -
HWE10170 GB
When using PAR-30MAA remote controller, the static pressure settings can be made from the remote controller.
To set the external static pressure from the function selection screen on the remote controller (Only PAR-30MAA)
Follow the instructions below and the instructions detailed in the remote controller manual for how to set the switches.
1. Set the function setting No. 32 (Switch setting/Function selection) to “2”.
2. Set the function setting No. 8 and No. 10 to appropriate values, according to the external static pressure.
[Important]
Be sure to write down the settings for all functions in the “Current setting” row if any of the initial settings has been
changed.
2) Selecting a function *The steps below explain how to set the settings on the MA Smart Remote Controller.
To change the settings
To confirm the setting
Notes:
The actual static pressure setting and the Dip switch setting may not match if the setting was set from the remote
controller.
To check the static pressure setting, check it on the remote controller, not on the dip switch.
Selection
Function
setting
No.
Initial
setting
Current
setting
External static
pressure setting
Function setting No.
Initial
setting
Current
setting
No. 32 No. 8 No. 10
Switch setting 1 O 50Pa 1 1
Function selection 2 100Pa 2 1
150Pa 3 1 O
200Pa 2 2
250Pa 3 2
1. Select Function setting from the Service menu to bring up the Function setting screen. (Refer to the remote controller manual for how to set the items in the service menu.)
2. Using the F1 through F4 buttons, set the settings for the M-NET address, Function No., and Data, select “Set”, and press the Enter button. The settings signals will be sent from the remote controller to the indoor units.
3. “Sending data” will appear on the screen, and when signal transmission is successfully completed, “Setting completed” will appear. Press the BACK button to return to the Function setting screen.
1. Select Function setting from the Service menu to bring up the Function setting screen. (Refer to the remote controller manual for how to set the items in the service menu.)
2. Using the F1 through F4 buttons, set the settings for the M-NET address, Function No., and Data, select “Conf”, and press the Enter button.
3. “Checking” will appear on the screen, and when signal transmission is successfully completed, the current settings values will be displayed.
Function setting
Cursor Address
Select:
M-NET address Function No. Data Function
Set / Conf
Function setting
Sending data
M-NET address Function No. Data
Function setting
Setting completed
M-NET address Function No. Data
Return:
Function setting
Checking
M-NET address Function No. Data
Page 65
59- 59 -
HWE10170 GB
6. 1s and 10ths digits (1) SW11, SW12 (Rotary switch)
The use of a network remote controller (PAR-F27MEA) requires address setting.
1) Indoor control board Address settings must be made while the unit is stopped.
7. Connection No. setting
(1) SW14 (Rotary switch)
This switch is used when the unit connected to an R2 series of outdoor unit.
1) Indoor control board
Changes to the dipswitches SW11, SW12, SW14, and SW15 must be made while the unit is stopped and the remote controller is OFF.
Factory setting
Factory setting
Page 66
60- 60 -
HWE10170 GB
[9] Disassembly Procedure
1. Control box
Exercise caution when removing heavy parts.
1. Removing the control box cover (1) Remove the two fixing screws on the cover (A) to re-
move it.
Fig.1
Fig.2
(A)
Page 67
61- 61 -
HWE10170 GB
2. Thermistor (Intake air)
Exercise caution when removing heavy parts.
1. Remove the control box cover according to the proce­dure in section 1. Control box.
2. Disconnect the connector (CN20) from the Indoor con­troller board.
3. Pull out the thermistor holder (B) and thermistor (C) on the control box.
Fig.3
(B),(C)
Indoor controller board
Page 68
62- 62 -
HWE10170 GB
3. Thermistor (Gas pipe) (Liquid pipe) · LEV
Exercise caution when removing heavy parts.
1. Remove the control box cover according to the proce­dure in section 1. Control box.
2. Removing the maintenance cover
(1) Remove the ten fixing screws on the cover (D) , cover
(E) , and cover (F) to remove the maintenance cover.
Fig.4
3. Removing the thermistor
(1) Disconnect the connector (CN44) from the Indoor con-
troller board.
(2) Remove the thermistor (G) from the thermistor holder
(H)on the copper tube.
Thermistor size Liquid pipe: ø8mm Gas pipe: ø6mm
4. Removing the LEV
(1) Disconnect the connectors (CN60 and CN7V) from the
Indoor controller board.
(2) Remove the drive motor (J) using two spanners. (3) When replacing the valve body (K), protect the sur-
rounding parts (e.g., insulation and wires) from brazing torch flame.
Fig.5
(F)
(E)
(D)
(G),(H)
(J)
(K)
Indoor controller board
Page 69
63- 63 -
HWE10170 GB
4. Drainpan
Exercise caution when removing heavy parts.
1. Removing the bottom plate
(1) Remove the twelve fixing screws on the bottom plate
(L) to remove it.
Fig.6
2. Removing the drainpan
(1) Pull out the drain pan (M) in the direction of the arrow.
Fig.7
Note
Drain the water out of the drain pan before
removing it.
(L)
(M)
Page 70
64- 64 -
HWE10170 GB
5. Heat exchanger
Exercise caution when removing heavy parts.
1. Remove the control box cover according to the proce­dure in section 1. Control box.
2. Remove the maintenance cover according to the pro­cedure in section 3. Thermistor (Gas pipe) (Liquid pipe) · LEV.
3. Remove the thermistor and disconnect LEV connector according to the procedure in section 3. Thermistor (Gas pipe) (Liquid pipe) · LEV.
4. Remove the drainpan according to the procedure in section 4. Drainpan.
Fig.8
5. Removing the Heat exchanger
(1) Remove the four fixing screws on the heat exchanger
(N) to remove it.
Fig.9
(N)
Page 71
65- 65 -
HWE10170 GB
6. Reactor, fan, and fan motor
Exercise caution when removing heavy parts.
1. Remove the control box cover according to the proce­dure in section 1. Control box.
2. Removing the fan motor and ACL cable
(1) Disconnect the connector (CNCT1) from the INV
board and connector (CNACL) from the noise filter board. Then, disconnect the relay connector.
(2) Remove the ground wire on the motor from the white
connector.
(3) Remove the cable through the rubber bush.
3. Removing the bottom plate
(1) Remove the ten fixing screws on the bottom plate (T)
to remove it.
Fig.10
4. Removing the wiring
(1) Remove a screw that is used to connect the wiring.
Fig.11
5. Removing the reactor
(1) Remove the two fixing screws on the reactor base (U)
to remove it.
Fig.12
6. Removing the fan case
(1) Remove the eight fixing screws on the fan case (V) to
remove it.
Fig.13
(T)
Noise filter board
INV board
Connector (WHITE)
(U)
(V)
Page 72
66- 66 -
HWE10170 GB
Exercise caution when removing heavy parts.
7. Removing the fan and fan motor
(1) Remove the two fixing screws and attachment on the
fan motor (W).
(2) Pull out the fan motor in the direction of the arrow.
Fig.14
(W)
Page 73
67- 67 -
HWE10170 GB
[10] Optional parts
Drain pump PAC-KE05DM-F
Long-life filter PAC-KE85LAF
Filter box PAC-KE250TB-F
External heater adaptor PAC-YU25HT
Page 74
Page 75
Page 76
http://Global.MitsubishiElectric.com
HWE10170 Printed in Japan
New publication effective July 2011
Specifications subject to change without notice
Loading...