Mitsubishi PEFY-P63VMH-E2, PEFY-P40VMH-E2, PEFY-P100VMH-E2, PEFY-P80VMH-E2, PEFY-P125VMH-E2 Installation Manual

...
1
Air Conditioning For Building Application
Drain Water Lift-Up Kit PAC-DRP10DP-E
Installation Manual
This installation manual contains only the description of how to install the Drain water Lift-Up Kit PAC-DRP10DP-E. For information about how to wire and how to install air conditioning units, see the installation manual for them. For your safety, first be sure to read section 1. "Safety Precautions" below thoroughly and then install the Drain water Lift-Up Kit PAC-DRP10DP-E correctly.
1. Safety precautions
• The following two symbols are used to denote dangers that may be caused by incorrect use and their degree:
WARNING
This symbol denotes what could lead to serious injury or death if you misuse the PAC-DRP10DP-E.
CAUTION
This symbol denotes what could lead to a personal injury or damage to your property if you misuse the PAC-DRP10DP-E.
• After reading this installation manual, keep it in a place where the final user can see it anytime he or she wants to it. When someone moves, repairs, or uses the PAC-DRP10DP-E, make sure that this manual is forwarded to the final user.
WARNING
Always have the unit installed by Authorized Mitsubishi Representative or similar professional.
Improper installation by the user could result in problems such as
water leakage, electric shock or fire.
Always use the designated cables and connect them properly. When connecting the terminals, make sure that external forces from the cable is not being conveyed to the terminal and then tighten it securely.
Improper or loose connections could cause excessive heat or fire.
Only use Mitsubishi-approved accessories, such as an air cleaner, humidifier or electric heater.
Always have such accessories installed by an Authorized Mitsubishi Representative or similar professional. Improper installation by the
user may result in water leakage, electric shock or fire.
Install the unit according to this Installation Manual.
If the unit is installed improperly, water leakage, electric shock or fire
may result.
Have all electric work performed by a properly licensed electrician. Electric work should be performed in strict adherence to procedures to this Installation Manual. Always provide a dedicated power supply.
If the capacity of the power supply is inadequate, it could result in
problems such as electric shock or fire.
Never modify the unit and always have repairs performed by an Authorized Mitsubishi Representative.
Improper repair could result in problems such as water leakage, electric shock or fire.
CAUTION
PRECAUTIONS BEFORE INSTALLATION
Never use for special applications such as storing food, plants, precision equipment or art.
The quality of these items may deteriorate.
Never use the unit in special environments.
Special environments with high concentrations of oil, steam or sulfuric gases will reduce the performance of the air condition and cause its parts to deteriorate.
Never install the unit where run-off could result in damage.
If the humidity in the room exceeds 80% or if the drain becomes clogged, water may drain off of the indoor unit. When the unit is used for heating, there may be drainage from the outdoor unit. If required, provide collector drain for the outdoor unit.
Always provide adequate signal noise protection when installing in facilities such as hospitals and communication stations.
Equipment at these facilities, such as inverters, in-house generators, high-frequency medical equipment, two-way communication equipment, may cause the air conditioner to operate improperly. Conversely, the signal noise from the air conditioner may affect the operation of medical equipment and two-way communication equipment and this could interfere with the medical treatment being given a patient or cause disturbances or interference in video broadcasting equipment.
2
PRECAUTIONS BEFORE REMOVE AND ELECTRIC WORK
Route wiring so that there is no tension.
Tension could cause the wire to break and this could result in
excessive heat or fire.
Dispose of packing materials properly.
Use care when transporting the unit.
• Always use two or more people for lifting a product weight 20 kg or
more.
• Some products are packaged with plastic wrapping bands. Never use
these for lifting or transporting the product.
• Never touch the fins on the heat exchanger. They are sharp and
could cause cuts.
• Never allow children to play with the plastic bags used for packaging.
Always tear them up when disposing. A child could suffocate in these bags.
PRECAUTIONS BEFORE TEST RUN
Never touch the switch with wet hands.
Electric shock could occur.
Never operate the air conditioner with the panel or guard removed.
The hand could come in contact with rotating, hot or high-pressure
components. They could cause electrical shock or entanglement.
Never operate the air conditioner with the air filter removed.
Particles will enter into the air conditioner and cause damage.
Never turn off the power supply immediately after stopping the unit.
Wait five minutes or more before turning off the power supply. Turning
off the power supply before that time could result in water leakage or
damage.
2. Confirming the Supplied Parts
1. Model names and applicable models
Model name Applicable types
PAC-DRP10DP-E
PEFY-P40VMH-E2, PEFY-P50VMH-E2, PEFY-P63VMH-E2, PEFY-P71VMH-E2 PEFY-P80VMH-E2, PEFY-P100VMH-E2, PEFY-P125VMH-E2, PEFY-P140VMH-E2
2. Provided parts
Check that the packet includes the following parts in addition to this installation manual.
PARTS
1 DRAIN PUMP ASSY. 2 RUBBER PLUG 3 BAND 4 PTT SCREW 4×10
SHAPE
Q'TY 1 1 2 2 + 1 (spare)
Drain socket
Drain sensor
3
3. Attach the Drain Pump
The drain pump must be attached before installation of the indoor unit.
3-1. Preparation for the indoor unit
(1) Remove the fixing screws (2 locations) shown in Fig. 3-1, and remove the
control box cover.
Fig. 3-1
(2) Remove the fixing screws (5 locations) shown in Fig. 3-2, and remove the
maintenance cover.
Fig. 3-2
(3) Remove the fixing screws (2 locations) shown in Fig. 3-3, and remove the
Drain socket hole cover.
* These screws will be reused to fix the drain socket. Keep them in a safe
place.
Fig. 3-3
3-2. Attach the drain pump
(1) Attach the drain pump assy 1 and drain socket as shown in Fig. 3-4 using
four PTT screws 4.
* When attaching the drain socket, make sure that drain hose is straight.
(2) Attach the Rubber Plug 2.
Fig. 3-4
Control box cover
Fixing screw
Fixing screw
Maintenance cover
Fixing screws
Fixing screws
Drain socket hole cover
Drain socket
Drain pump assy 1
Rubber Plug 2
Loading...