Mitsubishi PEFY-P25VMA-E, PEFY-P50VMA-E, PEFY-P40VMA-E, PEFY-P32VMA-E, PEFY-P63VMA-E Installation Manual

...
Air-Conditioners INDOOR UNIT
PEFY-P20,25,32,40,50,63,71,80,100,125,140VMA-E PEFY-P20,25,32,40,50,63,71,80,100,125,140VMAL-E
GBDFEINLP
INSTALLATIONSHANDBUCH
Zum sicheren und ordnungsgemäßen Gebrauch der Klimageräte das Installationshandbuch gründlich durchlesen.
Veuillez lire le manuel d’installation en entier avant d’installer ce climatiseur pour éviter tout accident et vous assurer d’une utilisation correcte.
MANUAL DE INSTALACIÓN
Para un uso seguro y correcto, lea detalladamente este manual de instalación antes de montar la unidad de aire acondicionado.
INSTALLATION MANUAL
For safe and correct use, please read this installation manual thoroughly before installing the air-conditioner unit.
MANUALE DI INSTALLAZIONE
Per un uso sicuro e corretto, leggere attentamente questo manuale di installazione prima di installare il condizionatore d’aria.
INSTALLATIEHANDLEIDING
Voor een veilig en juist gebruik moet u deze installatiehandleiding grondig doorlezen voordat u de airconditioner installeert.
MANUAL DE INSTALAÇÃO
Para segurança e utilização correctas, leia atentamente este manual de instalação antes de instalar a unidade de ar condicionado.
GRRUTR
ΕΓΧΕΙΡΙΔΙΟ ΟΔΗΓΙΩΝ ΕΓΚΑΤΑΣΤΑΣΗΣ
Για ασφάλεια και σωστή χρήση, παρακαλείστε διαβάσετε προσεχτικά αυτό το εγχειρίδιο εγκατάστασης πριν αρχίσετε την εγκατάσταση της μονάδας κλιματισμού.
РУКОВОДСТВО ПО УСТАНОВКЕ
Для осторожного и правильного использования прибора необходимо тщательно ознакомиться с данным руководством по установке до выполнения установки кондиционера.
MONTAJ ELKİTABI
Emniyetli ve doğru biçimde nasıl kullanılacağını öğrenmek için lütfen klima cihazını monte etmeden önce bu elkitabını dikkatle okuyunuz.
SVHGPO CZ
PŘÍRUČKA K INSTALACI
V zájmu bezpečného a správného používání si před instalací klimatizační jednotky důkladně pročtěte tuto příručku k instalaci.
NÁVOD NA INŠTALÁCIU
Pre bezpečné a správne použitie si pred inštalovaním klimatizačnej jednotky, prosím, starostlivo prečítajte tento návod na inštaláciu.
TELEPÍTÉSI KÉZIKÖNYV
A biztonságos és helyes használathoz, kérjük, olvassa el alaposan ezt a telepítési kézikönyvet, mielőtt telepítené a légkondicionáló egységet.
PODRĘCZNIK INSTALACJI
W celu bezpiecznego i poprawnego korzystania należy przed zainstalowaniem klimatyzatora dokładnie zapoznać się z niniejszym podręcznikiem instalacji.
SLSWHRBGRO
PRIROČNIK ZA NAMESTITEV
Za varno in pravilno uporabo pred namestitvijo klimatske naprave skrbno preberite priročnik za namestitev.
INSTALLATIONSHANDBOK
Läs den här installationshandboken noga innan luftkonditioneringsenheten installeras, för säker och korrekt användning.
PRIRUČNIK ZA UGRADNJU
Radi sigurne i ispravne uporabe, temeljito pročitajte ovaj priručnik prije ugradnje unutarnje jedinice.
РЪКОВОДСТВО ЗА МОНТАЖ
За безопасна и правилна употреба, моля, прочетете внимателно това ръководство преди монтажа на климатизатора.
MANUAL CU INSTRUCŢIUNI DE INSTALARE
Pentru o utilizare corectă şi sigură, vă rugăm să citiţi cu atenţie acest manual înainte de a instala unitatea de aer condiţionat.
2
3
3.2
[Fig. 3.2.1]
4
4.1
[Fig. 4.1.1]
A Refrigerant pipe (liquid pipe) B Refrigerant pipe (gas pipe) C Drain pipe (O.D. ø32) D Drain pipe (O.D. ø32, spontaneous draining)
A Unit body B Lifting machine
C Nuts (field supply) D Washers (field supply) E M10 hanging bolt (field supply)
5
5.2
[Fig. 5.1.1] [Fig. 5.1.2] [Fig. 5.2.1]
5.1
6
6.2
[Fig. 6.2.1]
A Center of gravity
A Access door B Electrical parts box C Air inlet D Air outlet E Ceiling surface F Service space (viewed from the side) G Service space (viewed from the direction of arrow)
1 600 mm or more
2 100 mm or more
3 20 mm or more
4 300 mm or more
A Indoor unit’s bottom surface
YX
LW
A
Z
A
C
D
C
E
D
B
C
D
A
F
G
3
4
E
A
50~150 450
450
49
625
777
20
100
23
C B A
D
C
E
250
1
2
B
A
137 67
239
357
122
33
41
217
C
A
B
D
Model PEFY-P20,25,32VMA(L)-E PEFY-P40,50VMA(L)-E PEFY-P63,71,80VMA(L)-E PEFY-P100,125VMA(L)-E PEFY-P140VMA(L)-E
A 700 900
1100 1400 1600
B 754 954
1154 1454 1654
C
800 1000 1200 1500 1700
D 660 860
1060 1360 1560
E
800 1000 1200 1500 1700
(mm)
3
A Cut here B Remove brazed cap
A
A
E
C
F
B
D
A Thermal insulation B Pull out insulation C Wrap with damp cloth D Return to original position E Ensure that there is no gap here F Wrap with insulating tape
7
[Fig. 7.1.1]
7.1
[Fig. 7.1.3]
B
J
O
N
F
Max. 300mm
[Fig. 7.2.1]
Correct piping
Wrong piping
A Insulation (9 mm or more) B Downward slope (1/100 or more) C Support metal K Air bleeder L Raised M Odor trap
Grouped piping
D O. D. ø32 PVC TUBE E Make it as large as possible. About 10 cm. F Indoor unit G Make the piping size large for grouped piping. H Downward slope (1/100 or more) I O. D. ø38 PVC TUBE for grouped piping.
(9 mm or more insulation)
J Up to 550 mm N Drain hose (accessory) O Horizontal or slightly upgradient
7.2
[Fig. 7.2.2]
C
B
A
L
D
D
D
E
K
M
B
H
I
Max. 20m
1.5-2m
G
F
FF
B
CD D
G
F
E
H
A
3235 25
A Indoor unit B Tie band (accessory) C Visible part D Insertion margin E Drain hose (accessory) F Drain pipe (O.D. ø32 PVC TUBE, field supply) G Insulating material (field supply) H Tie band (accessory)
A
[Fig. 7.1.2]
A Cool by a wet cloth
A Indoor unit B Tie band (accessory) C Band fixing part D Insertion margin E Drain hose (accessory) F Drain pipe (O.D. ø32 PVC TUBE, field supply) G Insulating material (field supply)
C
D
G
F
E
B
525
A
[Fig. 7.2.3]
4
8
[Fig. 8.0.1]
9
9.1
[Fig. 9.1.1] [Fig. 9.2.1]
[Fig. 9.2.2]
TB5 TB5
SM1M2 SM1M2
TB3
M1M2
AA
B
CC
TB5 TB15 TB5 TB15
SM1M2 SM1M2
TB3
M1M2 21 21
AA
B
CC
A Ter minal block for indoor
transmission cable
B Terminal block for outdoor
transmission cable
C Remote controller
9.2
[Fig. 7.3.1]
7.3
A Insert pump's end 2 to 4 cm. B Remove the water supply port. C About 2500 cc D Water E Filling port F Screw
[Fig. 8.0.2]
SWE
[Fig. 7.3.2]
[Fig. 8.0.3]
[Fig. 8.0.4]
<Indoor controller board>
A
B
F
C
D
E
A
B
G
F
A
A B C D E F G
CE
Duct
Air inlet
Access door
Canvas duct
Ceiling surface
Air outlet
Leave distance enough to pre­vent short cycle
<A> In case of rear inlet
D
A
B
G
C
E
A
F
<B> In case of bottom inlet
D
A
B
A Filter B Bottom plate
C
D
A Ground-fault interrupter B Local switch/Wiring breaker C Indoor unit
AB
C
PE
~220 -240V