Mitsubishi PEAD-RP35JA(L), PEAD-RP50JA(L), PEAD-RP60JA(L), PEAD-RP71JA(L), PEAD-RP100JA(L) Service Manual

...
SERVICE MANUAL
<indoor unit> Service ref.
Models
PEAD-RP35JA(L) PEAD-RP50JA(L) PEAD-RP60JA(L) PEAD-RP71JA(L) PEAD-RP100JA(L) PEAD-RP125JA(L) PEAD-RP140JA(L)
TM
1. REFERENCE MANUAL ····························· 2
3. PART NAMES AND FUNCTIONS ·············· 4
4. SPECIFICATION ········································ 6
5. FAN PERFORMANCE AND CORRECTED AIR FLOW ·························· 9
6. SOUND PRESSURE LEVELS ···················16
7. OUTLINES & DIMENSIONS ······················23
8. WIRING DIAGRAM ····································25
10
. TROUBLESHOOTING ·······························27
11
. DISASSEMBLY PROCEDURE ··················41
CONTENTS
INDOOR UNIT
REMOTE CONTROLLER
ON/OFF
TEMP.
Series PEAD
R410A
2009
SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
NOTE:
• This manual describes only service data of the indoor units.
2
REFERENCE MANUAL
1
Service Ref.
PUHZ-RP35/50/60/71/100/125/140VHA PUHZ-RP100/125/140YHA
PUHZ-RP71/100/125/140VHA-A
PUHZ-RP200/250YHA
PUHZ-RP200/250YHA-A
PU(H)-P·VGAA.UK PU(H)-P·YGAA.UK
PUHZ-RP35/50/60/71VHA4 PUHZ-RP100/125/140VKA PUHZ-RP100/125/140/200/250YKA
PUH-P71/100VHA PUH-P71/100/125/140YHA PU-P71/100VHA PU-P71/100/125/140YHA
SUZ-KA·VA.TH
SUZ-KA35/50/60VAR2.TH SUZ-KA71VA
1
MXZ-8A140VA3
Service Manual No.
OC334
OC337
OC338
OC339
PUHZ-P100/125/140VHA.UK
PUHZ-P100/125/140VHA3.UK
OC359
OC336
OC322
OC322
OC379
OC316
OCB451
OCH451
OCH415/OCB415
PUHZ-P200/250YHA3
OCH424/OCB424
PUHZ-HRP71/100VHA2
PUHZ-HRP100/125YHA2
OCH425/OCB425
1-1. OUTDOOR UNIT’S SERVICE MANUAL
3
SAFETY PRECAUTION
2
2-1. ALWAYS OBSERVE FOR SAFETY
2-2. CAUTIONS RELATED TO NEW REFRIGERANT
Before obtaining access to terminal, all supply circuits must be disconnected.
Cautions for units utilising refrigerant R410A
Use new refrigerant pipes.
In case of using the existing pipes for R22, be careful with the followings.
· For RP100, 125 and 140, be sure to perform replace-
ment operation before test run.
· Change flare nut to the one provided with this product.
Use a newly flared pipe.
· Avoid using thin pipes.
Make sure that the inside and outside of refrige­rant piping is clean and it has no contamination such as sulfur hazardous for use, oxides, dirt, shaving particles, etc. In addition, use pipes with specified thickness.
Contamination inside refrigerant piping can cause deterio­ration of refrigerant oil etc.
Store the piping to be used indoors during installation and both ends of the piping sealed until just before brazing. (Leave elbow joints, etc. in their packaging.)
If dirt, dust or moisture enters into refrigerant cycle, that can cause deterioration of refrigerant oil or malfunction of com­pressor.
Do not use refrigerant other than R410A.
If other refrigerant (R22 etc.) is used, chlorine in refrige­rant can cause deterioration of refrigerant oil etc.
Use a vacuum pump with a reverse flow check valve.
Vacuum pump oil may flow back into refrigerant cycle and that can cause deterioration of refrigerant oil etc.
Use the following tools specifically designed for use with R410A refrigerant.
The following tools are necessary to use R410A refrigerant.
Tools for R410A Gauge manifold Charge hose
Gas leak detector
To rque wrench
Flare tool Size adjustment gauge Vacuum pump adaptor
Electronic refrigerant charging scale
Handle tools with care.
If dirt, dust or moisture enters into refrigerant cycle, that can cause deterioration of refrigerant oil or malfunction of com­pressor.
Use ester oil, ether oil or alkylbenzene oil (small amount) as the refrigerant oil applied to flares and flange connections.
If large amount of mineral oil enters, that can cause deterio­ration of refrigerant oil etc.
Do not use a charging cylinder.
If a charging cylinder is used, the composition of refrigera­nt will change and the efficiency will be lowered.
Ventilate the room if refrigerant leaks during
Charge refrigerant from liquid phase of gas cylinder.
If the refrigerant is charged from gas phase, composition change may occur in refrigerant and the efficiency will be lowered.
operation. If refrigerant comes into contact with a flame, poisonous gases will be released.
[1] Cautions for service
(1) Perform service after recovering the refrigerant left in unit completely. (2) Do not release refrigerant in the air. (3) After completing service, charge the cycle with specified amount of refrigerant. (4) When performing service, install a filter drier simultaneously. Be sure to use a filter drier for new refrigerant.
[2] Additional refrigerant charge
When charging directly from cylinder
· Check that cylinder for R410A on the market is syphon type.
· Charging should be performed with the cylinder of syphon stood vertically. (Refrigerant is charged from liquid phase.)
4
Unit
PART NAMES AND FUNCTIONS
3
Indoor Unit
Air intake (sucks the air inside the room into the unit)
In case of rear inlet
Air outlet
In case of bottom inlet
Gravimeter
[3] Service tools
Use the below service tools as exclusive tools for R410A refrigerant.
No. Tool name Specifications
1 Gauge manifold · Only for R410A
· Use the existing fitting specifications. (UNF1/2)
· Use high-tension side pressure of 5.3MPa·G or over.
2 Charge hose · Only for R410A
· Use pressure performance of 5.09MPa·G or over.
3 Electronic scale
4 Gas leak detector · Use the detector for R134a, R407C or R410A.
5 Adaptor for reverse flow check · Attach on vacuum pump.
6 Refrigerant charge base
7 Refrigerant cylinder · Only for R410A · To p of cylinder (Pink)
· Cylinder with syphon
8 Refrigerant recovery equipment
5
Wired remote controller
Display Section
For purposes of this explanation, all parts of the display are shown as lit. During actual operation, only the relevant items will be lit.
Identifies the current operation
Shows the operating mode, etc. *Multilanguage display is available.
“Centrally Controlled” indicator
Indicates that operation from the remote controller has been prohib­ited by a master controller.
“Timer is Off” indicator
Indicates that the timer is off.
Temperature Setting
Shows the target temperature.
Day-of-Week
Shows the current day of the week.
Time/Timer Display
Shows the current time, unless the simple or Auto Off timer is set. If the simple or Auto Off timer is set, the time to be switched off is shown.
TIME SUN MON TUE WED THU FRI SAT TIMER AFTER
ERROR CODE
°F°C
Hr AFTER
°F°C
ONLY1Hr.
Up/Down Air Direction indica­tor
The indicator shows the direc­tion of the outcoming airflow.
“One Hour Only” indicator
Displayed if the airflow is set to low or downward during COOL or DRY mode. (Operation varies according to model.) The indicator goes off in 1 hour, when the airflow direction also changes.
Room Temperature display
Shows the room temperature. The room temperature display range is 8–39 The display blinks if the temperature is less than 8
Louver display
Indicates the action of the swing louver. Does not appear if the louver is not running.
(Power On indicator)
Indicates that the power is on.
ON OFF
FUNCTION
FILTER
WEEKLY
SIMPLE
AUTO OFF
˚C or 39˚C or more.
“Sensor” indication
Displayed when the remote controller sensor is used.
“Locked” indicator
Indicates that remote controller but­tons have been locked.
“Clean The Filter” indicator
To be displayed on when it is time to clean the filter.
Timer indicators
The indicator comes on if the corre­sponding timer is set.
Fan Speed indicator
Shows the selected fan speed.
Ventilation indicator
Appears when the unit is running in
˚C.
Ventilation mode.
Operation Section
Te mperature setting buttons
Down
Up
Timer Menu button (Monitor/Set button)
Mode button (Return button)
TEMP.
ON/OFF
Set Time buttons
Back
Ahead
Timer On/Off button
BACK DAY
PAR-21MAA
MENU
MONITOR/SET
CLOCK
ON/OFF
OPERATION
FILTER
CHECK
CLEAR
TEST
(Set Day button)
Opening the lid
Built-in temperature sensor
Note:
“PLEASE WAIT” message This message is displayed for approximately 3 minutes when power is supplied to the indoor unit or when the unit is recovering from a power failure. “NOT AVAILABLE” message This message is displayed if an invalid button is pressed (to operate a function that the indoor unit does not have). If a single remote controller is used to operate multiple indoor units simultaneously that are different types, this message will not be displayed as far as any of the indoor units is equipped with the function.
ON/OFF button
Fan Speed button
Filter button (<Enter> button)
Te st Run button
Check button (Clear button)
Airflow Up/Down button
Louver button ( Operation button)
To return operation number
Ventilation button ( Operation button)
To go to next operation number
6
Service Ref. Mode
Power supply
Input kW Running Current
1
1
1
A External finish Heat exchanger
Fan
Fan (drive) × No. Fan motor output kW Airflow (Low-Mid-High)
m
3
/min (CFM)
External static pressure Pa Booster heater kW Operation control & Thermostat Sound pressure level (Low-Mid-High)
dB (A)
Field drain pipe O.D mm (in.) Dimensions W mm (in.)
D mm (in.) H mm (in.)
kg lbs
1 Figures in the parentheses indicate drainpump-less Model (L).
INDOOR UNIT
Weight
35Pa 50Pa
70Pa 100Pa 150Pa
Service Ref. Mode
Power supply
Input kW Running Current
1
1
1
A External finish Heat exchanger
Fan
Fan (drive) × No. Fan motor output kW Airflow (Low-Mid-High)
m
3
/min (CFM)
External static pressure Pa Booster heater kW Operation control & Thermostat Sound pressure level (Low-Mid-High)
dB (A)
Field drain pipe O.D mm (in.) Dimensions W mm (in.)
D mm (in.) H mm (in.)
kg lbs
INDOOR UNIT
Weight
35Pa 50Pa
70Pa 100Pa 150Pa
Service Ref. Mode
Power supply
Input kW Running Current
1
1
1
A External finish Heat exchanger
Fan
Fan (drive) × No. Fan motor output kW Airflow (Low-Mid-High)
m
3
/min (CFM)
External static pressure Pa Booster heater kW Operation control & Thermostat Sound pressure level (Low-Mid-High)
dB (A)
Field drain pipe O.D mm (in.) Dimensions W mm (in.)
D mm (in.) H mm (in.)
kg lbs
INDOOR UNIT
Weight
35Pa 50Pa
70Pa 100Pa 150Pa
PEAD-RP35JA(L)
Cooling
0.09 (0.07
)
0.64 (0.53
)
Heating
0.07
0.53
Single phase, 50, 60Hz, 220-240V
Galvanized sheets
Plate fin coil
Sirocco fan
× 1
0.085
10.0-12.0-14.0 (353-424-494) 35-50-70-100-150
-
Remote controller & built-in
23-26-29 23-27-30 24-28-31 26-29-33 29-33-37
32 (1-1/4)
900 (35-7/16)
732 (28-7/8)
250 (9-7/8)
26 (25) 58 (56)
PEAD-RP50JA(L)
Cooling
0.11 (0.09
)
0.90 (0.79
)
Heating
0.09
0.79
Single phase, 50, 60Hz, 220-240V
Galvanized sheets
Plate fin coil
Sirocco fan
× 1
0.085
12.0-14.5-17.0 (424-512-600) 35-50-70-100-150
-
Remote controller & built-in
25-30-34 26-31-35 28-32-36 29-33-37 31-35-39
32 (1-1/4)
900 (35-7/16)
732 (28-7/8)
250 (9-7/8)
28 (27) 62 (60)
PEAD-RP60JA(L)
Cooling
0.12 (0.10
)
1.00 (0.89
)
Heating
0.10
0.89
Single phase, 50, 60Hz, 220-240V
Galvanized sheets
Plate fin coil
Sirocco fan
× 2
0.121
14.5-18.0-21.0 (512-636-742) 35-50-70-100-150
-
Remote controller & built-in
25-28-32 25-29-33 26-30-34 27-31-35 29-34-38
32 (1-1/4)
1100 (43-5/16)
732 (28-7/8)
250 (9-7/8)
28 (27) 62 (60)
SPECIFICATION
4
7
1 Figures in the parentheses indicate drainpump-less Model (L).
Service Ref. Mode
Power supply
Input kW Running Current
1
1
1
A External finish Heat exchanger
Fan
Fan (drive) × No. Fan motor output kW Airflow (Low-Mid-High)
m
3
/min (CFM)
External static pressure Pa Booster heater kW Operation control & Thermostat Sound pressure level (Low-Mid-High)
dB (A)
Field drain pipe O.D mm (in.) Dimensions W mm (in.)
D mm (in.) H mm (in.)
kg lbs
INDOOR UNIT
Weight
35Pa 50Pa
70Pa 100Pa 150Pa
Service Ref. Mode
Power supply
Input kW Running Current
1
1
1
A External finish Heat exchanger
Fan
Fan (drive) × No. Fan motor output kW Airflow (Low-Mid-High)
m
3
/min (CFM)
External static pressure Pa Booster heater kW Operation control & Thermostat Sound pressure level (Low-Mid-High)
dB (A)
Field drain pipe O.D mm (in.) Dimensions W mm (in.)
D mm (in.) H mm (in.)
kg lbs
INDOOR UNIT
Weight
35Pa 50Pa
70Pa 100Pa 150Pa
Service Ref. Mode
Power supply
Input kW Running Current
1
1
1
A External finish Heat exchanger
Fan
Fan (drive) × No. Fan motor output kW Airflow (Low-Mid-High)
m
3
/min (CFM)
External static pressure Pa Booster heater kW Operation control & Thermostat Sound pressure level (Low-Mid-High)
dB (A)
Field drain pipe O.D mm (in.) Dimensions W mm (in.)
D mm (in.) H mm (in.)
kg lbs
INDOOR UNIT
Weight
35Pa 50Pa
70Pa 100Pa 150Pa
PEAD-RP70JA(L)
Cooling
0.17 (0.15
)
1.28 (1.17
)
Heating
0.15
1.17
Single phase, 50, 60Hz, 220-240V
Galvanized sheets
Plate fin coil
Sirocco fan
× 2
0.121
17.5-21.0-25.0 (618-742-883) 35-50-70-100-150
-
Remote controller & built-in
25-29-34 26-30-34 27-31-35 28-32-36 30-35-39
32 (1-1/4)
1100 (43-5/16)
732 (28-7/8)
250 (9-7/8)
33 (32) 73 (71)
PEAD-RP100JA(L)
Cooling
0.25 (0.23
)
1.68 (1.57
)
Heating
0.23
1.57
Single phase, 50, 60Hz, 220-240V
Galvanized sheets
Plate fin coil
Sirocco fan
× 2
0.244
24.0-29.0-34.0 (847-1024-1201) 35-50-70-100-150
-
Remote controller & built-in
28-33-38 29-34-38 30-35-39 31-36-40 34-40-43
32 (1-1/4)
1400 (55-1/8)
732 (28-7/8)
250 (9-7/8)
41 (40) 91 (89)
PEAD-RP125JA(L)
Cooling
0.36 (0.34
)
2.40 (2.29
)
Heating
0.34
2.29
Single phase, 50, 60Hz, 220-240V
Galvanized sheets
Plate fin coil
Sirocco fan
× 2
0.244
29.5-35.5-42.0 (1042-4254-1483) 35-50-70-100-150
-
Remote controller & built-in
31-36-40 33-36-40 33-37-41 34-39-42 37-41-45
32 (1-1/4)
1400 (55-1/8)
732 (28-7/8)
250 (9-7/8)
43 (42) 95 (93)
8
1 Figures in the parentheses indicate drainpump-less Model (L).
Service Ref. Mode
Power supply
Input kW Running Current
1
1
1
A External finish Heat exchanger
Fan
Fan (drive) × No. Fan motor output kW Airflow (Low-Mid-High)
m
3
/min (CFM)
External static pressure Pa Booster heater kW Operation control & Thermostat Sound pressure level (Low-Mid-High)
dB (A)
Field drain pipe O.D mm (in.) Dimensions W mm (in.)
D mm (in.) H mm (in.)
kg lbs
INDOOR UNIT
Weight
35Pa 50Pa
70Pa 100Pa 150Pa
PEAD-RP140JA(L)
Cooling
0.39 (0.37
)
2.60 (2.49
)
Heating
0.37
2.49
Single phase, 50, 60Hz, 220-240V
Galvanized sheets
Plate fin coil
Sirocco fan
× 2
0.244
32.0-39.0-46.0 (1130-1377-1624) 35-50-70-100-150
-
Remote controller & built-in
33-37-43 34-38-43 34-39-44 36-40-45
38-42-46 32 (1-1/4) 1600 (63)
732 (28-7/8)
250 (9-7/8)
47 (46)
104 (102)
9
FAN PERFORMANCE AND CORRECTED AIR FLOW
5
PEAD-RP35JA(L)
(External static pressure 35Pa) 220-240V 50/60Hz
60
50
Limit
40
Rated point
Middle
3
High
/min)
30
External static pressure (Pa)
20
Low
10
0
79111315 17 19 21
Airflow rate(m
PEAD-RP35JA(L)
(External static pressure 50Pa) 220-240V 50/60Hz
70
60
Limit
Airflow rate(m
Rated point
Middle
3
/min)
High
50
40
30
External static pressure (Pa)
20
10
0
79111315 17 19 21
Low
PEAD-RP35JA(L)
(External static pressure 100Pa) 220-240V 50/60Hz
120
110
Low
Airflow rate(m
Rated point
Middle
3
/min)
Limit
100
90
80
70
60
50
External static pressure (Pa)
40
30
20
10
0
791113 15 17 19 21
PEAD-RP35JA(L)
(External static pressure 150Pa) 220-240V 50/60Hz
170
160
150
140
Limit
130
120
110
100
90
80
70
60
External static pressure (Pa)
50
40
30
20
10
0
791113 15 17 19 21
Airflow rate(m
Rated point
Low
3
/min)
Middle
High
High
PEAD-RP35JA(L)
(External static pressure 70Pa) 220-240V 50/60Hz
90
80
Limit
70
60
50
40
External static pressure (Pa)
30
20
10
0
791113 15 17 19 21
Airflow rate(m
Low
Rated point
Middle
3
/min)
High
10
PEAD-RP50JA(L)
(External static pressure 35Pa) 220-240V 50/60Hz
70
60
Limit
50
40
Middle
30
External static pressure (Pa)
20
10
0
10 15 20
Low
Airflow rate(m
3
High
Rated point
/min)
PEAD-RP50JA(L)
(External static pressure 100Pa) 220-240V 50/60Hz
130
120
110
100
External static pressure (Pa)
91419
Limit
90
80
70
60
50
40
30
20
10
0
10 15 20
Airflow rate(m
3
Low
/min)
Rated point
High
Middle
91419
PEAD-RP50JA(L)
(External static pressure 50Pa) 220-240V 50/60Hz
80
70
Limit
60
50
40
30
External static pressure (Pa)
20
10
0
10 15 20
Middle
Low
Airflow rate(m
3
High
Rated point
/min)
PEAD-RP50JA(L)
(External static pressure 70Pa) 220-240V 50/60Hz
100
90
PEAD-RP50JA(L)
(External static pressure 150Pa) 220-240V 50/60Hz
180
170
160
150
140
Limit
130
120
110
100
90
80
70
External static pressure (Pa)
60
50
40
30
20
10
0
91419
10 15 20
Airflow rate(m
3
/min)
Rated point
High
Middle
Low
91419
80
Limit
70
60
50
40
External static pressure (Pa)
30
20
10
0
10 15 20
Low
Airflow rate(m
3
Rated point
Middle
/min)
High
91419
11
PEAD-RP60JA(L)
(External static pressure 35Pa) 220-240V 50/60Hz
60
50
Limit
40
Rated point
30
External static pressure (Pa)
20
10
0
10 15 20 25 30
Low
Airflow rate(m
Middle
3
/min)
High
PEAD-RP60JA(L)
(External static pressure 100Pa) 220-240V 50/60Hz
120
110
100
Limit
90
80
70
60
50
External static pressure (Pa)
40
30
20
10
0
10 15 20 25 30
Airflow rate(m
Low
Rated point
3
/min)
Middle
High
PEAD-RP60JA(L)
(External static pressure 50Pa) 220-240V 50/60Hz
70
60
Limit Rated point
50
40
30
External static pressure (Pa)
20
High
Middle
Low
10
0
10 15 20 25 30
Airflow rate(m
3
/min)
PEAD-RP60JA(L)
(External static pressure 70Pa) 220-240V 50/60Hz
90
80
70
Limit
60
50
40
External static pressure (Pa)
30
Low
Rated point
Middle
High
PEAD-RP60JA(L)
(External static pressure 150Pa) 220-240V 50/60Hz
170
160
150
140
130
120
110
100
External static pressure (Pa)
Limit
90
80
70
60
50
40
30
20
10
0
10 15 20 25 30
Airflow rate(m
3
Low
/min)
Rated point
Middle
High
20
10
0
10 15 20 25 30
Airflow rate(m
3
/min)
12
PEAD-RP71JA(L)
(External static pressure 35Pa) 220-240V 50/60Hz
70
60
50
40
30
External static pressure (Pa)
20
10
0
Limit
High
Middle
Low
10 15 20 25 30
Airflow rate(m
3
/min)
Rated point
PEAD-RP71JA(L)
(External static pressure 100Pa) 220-240V 50/60Hz
130
120
110
100
90
80
70
60
50
External static pressure (Pa)
40
30
20
10
0
Limit
Low
10 15 20 25 30
Airflow rate(m
Middle
3
/min)
High
Rated point
PEAD-RP71JA(L)
(External static pressure 50Pa) 220-240V 50/60Hz
90
80
70
60
50
40
External static pressure (Pa)
30
20
10
0
10 15 20 25 30
Limit
Low
Airflow rate(m
Middle
3
High
/min)
PEAD-RP71JA(L)
(External static pressure 70Pa) 220-240V 50/60Hz
100
90
80
Limit
70
High
Rated point
Rated point
PEAD-RP71JA(L)
(External static pressure 150Pa) 220-240V 50/60Hz
180
170
160
150
140
130
Limit
120
110
100
90
80
70
External static pressure (Pa)
60
50
40
30
20
10
0
10 15 20 25 30
Airflow rate(m
Low
Middle
3
/min)
High
Rated point
60
50
40
External static pressure (Pa)
30
20
10
0
10 15 20 25 30
Low
Airflow rate(m
Middle
3
/min)
13
PEAD-RP100JA(L)
(External static pressure 35Pa) 220-240V 50/60Hz
70
Limit
60
50
40
30
External static pressure (Pa)
20
10
0
10 15 20 25 30 35 40 45
Low
Airflow rate(m
3
/min)
Rated point
Middle
High
PEAD-RP100JA(L)
(External static pressure 100Pa) 220-240V 50/60Hz
150
140
130
120
Limit
110
100
90
80
70
60
External static pressure (Pa)
50
40
30
20
10
0
10 15 20 25 30 35 40 45
Low
Airflow rate(m
Middle
3
High
Rated point
/min)
PEAD-RP100JA(L)
(External static pressure 50Pa) 220-240V 50/60Hz
100
90
80
Limit
70
60
50
40
External static pressure (Pa)
30
20
10
0
10 15 20 25 30 35 40 45
Low
Airflow rate(m
Middle
3
High
/min)
PEAD-RP100JA(L)
(External static pressure 70Pa) 220-240V 50/60Hz
120
110
100
Limit
90
80
70
60
50
External static pressure (Pa)
40
30
20
10
0
10 15 20 25 30 35 40 45
Middle
Low
Airflow rate(m
3
High
/min)
Rated point
Rated point
PEAD-RP100JA(L)
(External static pressure 150Pa) 220-240V 50/60Hz
200
190
180
170
160
150
Limit
140
130
120
110
100
90
80
External static pressure (Pa)
70
60
50
40
30
20
10
0
10 15 20 25 30 35 40 45
Low
Airflow rate(m
Middle
High
3
/min)
Rated point
14
PEAD-RP125JA(L)
(External static pressure 35Pa) 220-240V 50/60Hz
70
Limit
60
Middle
50
40
30
External static pressure (Pa)
20
10
0
15 20 25 30 35 40 45
Low
Airflow rate(m
3
Rated point
/min)
High
PEAD-RP125JA(L)
(External static pressure 100Pa) 220-240V 50/60Hz
180
170
160
150
140
130
120
110
100
External static pressure (Pa)
Limit
High
Middle
Rated point
90
80
70
60
50
40
30
20
10
0
15 20 25 30 35 40 45
Low
Airflow rate(m
3
/min)
PEAD-RP125JA(L)
(External static pressure 50Pa) 220-240V 50/60Hz
100
90
80
70
60
50
40
External static pressure (Pa)
30
20
10
0
15 20 25 30 35 40 45
Limit
Low
Airflow rate(m
Middle
3
/min)
Rated point
PEAD-RP125JA(L)
(External static pressure 70Pa) 220-240V 50/60Hz
150
140
130
Limit
120
110
100
90
80
70
60
External static pressure (Pa)
50
40
30
20
10
0
15 20 25 30 35 40 45
Low
Airflow rate(m
Middle
3
/min)
High
Rated point
High
PEAD-RP125JA(L)
(External static pressure 150Pa) 220-240V 50/60Hz
230
220
210
200
190
180
Limit
170
160
150
140
130
120
110
100
90
External static pressure (Pa)
80
70
60
50
40
30
20
10
0
15 20 25 30 35 40 45
Low
Airflow rate(m
Middle
3
/min)
High
Rated point
Loading...