Mitsubishi PE-5GAK, PE-5GAKT, PE-6GAK, PE-6GAKT Service Manual

Page 1
TECHNICAL & SERVICE MANUAL
SPLIT-TYPE, AIR CONDITIONERS
CONTENTS
1.
TYPES OF CONNECTED OUTDOOR UNITS
···2
2. SAFETY FOR USE·································3
4. SPECIFICATIONS ··································7
5. DATA·····················································11
6. OUTLINES AND DIMENSIONS···········18
7. WIRING DIAGRAM·······························20
8.
REFRIGERANT SYSTEM DIAGRAM
········21
9. TROUBLESHOOTING··························22
10. FUNCTION SETTING ···························35
11. SYSTEM CONTROL·····························39
12. SERVICE DATA (PARTS NAME)·········48
13. OPTIONAL PARTS ·······························50
No. HWE07050
Indoor unit
Ceiling Concealed
Series PE
ON/OFF
TEMP.
Remote controller
NOTE:
• This service manual describes technical data of indoor units.
• RoHS compliant products have <G> mark on the spec name plate.
August 2007
[Model names]
PE-5GAK PE-5GAKT PE-6GAK PE-6GAKT
Page 2
2
1
TYPES OF CONNECTED OUTDOOR UNITS
Outdoor Unit List
Indoor unit
PE-5GAK(T)
PE-6GAK(T)
Specification
Model name
PE-5GAK PE-5GAK.TH PE-5GAK.TH-SP PE-5GAK.TH-MF PE-5GAK.TH-SPMF
PE-6GAK PE-6GAK.TH PE-6GAK.TH-SP PE-6GAK.TH-MF PE-6GAK.TH-SPMF
Specification
Model name
PE-5GAKT PE-5GAKT.TH PE-5GAKT.TH-SP
PE-6GAKT PE-6GAKT.TH
Outdoor unit Model name
PU-5YAKD
PU-5YJSA
PU-6YAKD
PU-6YJSA
Standard Model High static pressure motor Steel fan
Standard Model High static pressure motor
PE-6GAKT.TH-SP
High static pressure
motor/steel fan
Page 3
3
SAFETY FOR USE
2
Before conducting installation work, please read this ''SAFETY FOR USE'' carefully
for
correct installation.
Since the caution items shown here contain important description relative to safety, please
observe them without fail.
After reading, please keep it with you together the Instruction Manual, and read it again at the
movement of the unit.
The unit should not be installed by the user.
If the unit is installed improperly, explosion, water leakage, electric shock or fire may be result. Consult your dealer or specialist subcontractor for repair and movement.
For installation, conduct the work correctly by following the Installation Manual.
Improper installation may cause a fire, electrical shock or water leakage.
Install the unit on a spot sufficiently durable against the unit weight.
Insufficient durability can cause an injury by the falling down of unit.
All electric work must be performed by licensed technician, according to local regulations and the instructions given in this manual.
The units should be powered by dedicated power lines. Power lines with insufficient capacity or improper electrical work may result in electric shock or fire.
Use only the specified cables for wiring. The connections must be made secured without tension the terminals.
Improper connection or fastening can cause a fire or electrical shock.
The unit should be installed according to the instructions in order to minimize the risk of damage from earthquakes, typhoons or strong winds.
Improper installation work can cause an injury by the falling down of the unit.
The outdoor unit must be installed on stable, level surface, in a place where there is no accumulation of snow , leaves or rubbish. The outdoor unit should be installed in a location where air and noise emitted by the unit will not disturb the neighbors. The indoor unit should be securely installed.
When installing or relocating the unit, make sure that no substance other than the specified refrigerant enters the refrigerant circuit. Any presence of foreign substance such as air can cause abnormal pressure rise or explosion.
If the unit is loosely mounted, it may fall, and cause injury.
Never repair the unit, remodel or transfer it to another site by yourself.
If they are performed improperly, water leakage, electric shock or fire may result. If you need to have the unit repaired or moved, consult your dealer.
Use only the specified refrigerant (R-22) to charge the refrigerant circuit. Do not mix it with any other refrigerant and do not allow air to remain in the circuit.
Air enclosed in the circuit can cause high pressure resulting in a rupture and other hazards.
Ventilate the room if refrigerant leaks during Installation.
The refrigerant heated generates poisonous gas by decomposition which can cause poisoning.
After completing installation work, make sure that refrigerant gas has not leaked.
If refrigerant gas has leaked and exposed to fan heater, stove, oven and so on, it may generate noxious gases.
Take a proper measure to suppress the critical concentration of refrigerant if leaked when installing the unit in a small room.
The limit density is made not to be exceeded even if the refrigerant leaks by any chance. You are necessary to ventilation measures to prevent the accident. If the refrigerant leaks, hypoxia accident may caused. For the countermeasure to be taken, consult your dealer.
The terminal block cover of unit must be firmly attached to prevent entry of dust and moisture.
Improper mounting of the cover cause electric shock or fire.
Use only optional parts authorised by Mitsubishi Electric.
If the accessories are installed improperly, water leakage, electric shock or fire may result. Ask your dealer or an authorised company to install them.
Erroneous handling gives a high possibility to induce serious results such as
death or heavy injury.
Erroneous handling may induce serious injury depending on the situation.
Warning
Warning
Caution
Page 4
4
Caution
Never install on the place where a combustible gas might leak.
The gas may ignite or explode when the gas leaks and collects in surrounding of the unit.
When the unit is installed at telecommunication centers or hospitals, take a proper provision against noise.
The erroneous operation of air conditioner may be induced by inverter equipment, independent power device, medical equipment or communication equipment. While the erroneous operation of medical equipment or communication equipment may caused by the air conditioner.
For special use as for foods, animals/plants, precision equipment or art objects, the applicability should be confirmed beforehand.
As the use for the applications other than that designed originally may result in the deterioration of the quality. Consult your dealer in this regard.
Do not use the unit under a special atmosphere.
Installing the unit at the following places may cause a trouble, a place where much machine oil, salt sonnet, humidity or dust, spa district, a place full of sulfur gas, volatile gas, or corrosive gas, a place near high frequency processing machine.
Thermal insulation of the drain pipes is necessary prevent dew condensation.
If the drain pipes are not properly insulated, condensation will result and drip on ceiling, floor or other possessions.
The drain piping must process by surely,and insulate the drain piping not to be dewy.
When the room humidity exceeds 80% or when the drain pipe is clogged, water may drip from the indoor unit. The outdoor unit produces condensation during the heating operation. Make sure to provide drainage around the outdoor unit if such condensation is likely to cause damage.
Install drain piping according to this Installation Manual to ensure proper drainage. Place thermal insulation on the pipes to prevent condensation.
Improper drain piping may cause water leakage and damage to furniture or other possessions.
The unit must be properly earth connected.
Do not connect the earth wire to gas pipe, city water pipe, lightning rod or telephone earth wire. Improper earth connection may cause electrical shock.
When installing at a watery place, provide an electric leak breaker.
Failure to mount the electric leak breaker may cause electrical shock.
Use breaker or fuse with proper capacity. Make sure that there is a main power switch.
Using a wire or a copper wire instead of proper capacity of fuse can cause fire or trouble. Other appliances connected to the same line could cause an overload.
For the power lines, use standard cables of sufficient current capacity.
Otherwise, current leakage, overheating or fire may occur.
When installing the power lines, do not apply tension to the cables.
The tighten or loosen the connections may cause generate heat and cause fire.
Remote controller is not pushed with the thing sharpening ahead.
It occasionally causes the electric shock and the breakdown.
Arrange the configuration of wiring not to bring up the panel and terminal cover, and fasten the panel and terminal cover securely.
The poor mounting of the panel or terminal cover may cause the heat generation of the terminal connection, a fire or electrical shock.
Do not wash the unit with water.
If washed with water, electrical shock may be caused.
Do not handle the switch with wet hands.
Otherwise electrical shock can be resulted.
Be very careful on handling the unit.
When carrying in outdoor unit, be sure to support it at four points. Carrying in and lifting with 3-point support may make outdoor unit unstable, resulting in a fall of it. The unit should not be carried by only one person if it is more than 20kg. Some units use PP bands for packing. Do not use any PP band for delivery purpose. Do not touch the heat exchanger fins with your bear hands. Doing so may cut your hands. Be sure to safely dispose the packaging materials. Packaging materials, such as catches and other metal or wooden parts, may cause stabs or other injuries. Tear off and discard plastic packing bags so that children will not play any of them. If children play with a plastic bag which was not torn off, it may cause a risk of suffocation.
Do not leave the mounting base being damaged.
The damaged base may cause the falling down of the unit which may give injury.
Turn on the main power switch more than 6 hours before starting operation.
Do not turn the main power switch OFF during seasons of heavy use, doing so can result in failure.
Do not touch the compressor or refrigerant piping without wearing glove on your hands.
Touching directly such part can cause a burn or frostbite as it becomes high or low temperature according to the refrigerant state.
Do not touch the metal edges inside the unit without wearing glove on your hands.
Touching directly it may injure your hands.
Do not remove the panel or the fan guard from the outdoor unit when it is running.
You could be injured if you touch rotating, hot or high­voltage parts.
Do not operate the air conditioner without the air filter set place.
Dust may accumulate, and cause a failure.
At emergency (if you smell something burning), stop operation and turn the power source switch off.
Continuing the operation without eliminating the emergency state may cause a machine trouble, fire, or electrical shock.
After stopping operation, be sure to wait for five minutes before turning off the main power switch.
Otherwise, water leakage or unit failure may
Remote controller is not installed for the place where direct sunshine strikes.
occur.
Page 5
5
3
PART NAMES AND FUNCTIONS
Indoor (Main) Unit
Air intake duct flange
Air outlet duct flange
Air outlet
Air intake (sucks the air inside the room into the unit)
Remote controller
Once the controls are set, the same operation mode can be repeated by simply pressing the ON/OFF button.
Operation buttons
PAR-21MAA
ON/OFF
FILTER
CHECK
OPERATION
CLEAR
TEST
TEMP.
MENU
BACK DAY
MONITOR/SET
CLOCK
ON/OFF
Set Temperature buttons
Down Up
Timer Menu button (Monitor/Set button)
Mode button (Return button)
Set Time buttons
Back
Ahead
Timer On/Off button (Set Day button)
Opening the door.
ON/OFF button
Fan Speed button
Filter button (<Enter> button)
Test Run button
Check button (Clear button)
Airflow Up/Down button
Louver button (
Operation button)
To preceding operation number.
Ventilation button (
Operation button)
To next operation number.
Page 6
6
Display
For purposes of this explanation, all parts of the display are shown as lit. During actual operation, only the relevant items will be lit.
˚F˚C
˚F˚C
ERROR CODE
AFTER
TIMER
TIME SUN MON TUE WED THU FRI SAT
ON OFF
Hr AFTER
FILTER
FUNCTION
ONLY1Hr.
WEEKLY
SIMPLE
AUTO OFF
Identifies the current operation
Shows the operating mode, etc. * Multilanguage display is sup-
ported.
Centrally Controlled indicator
Indicates that operation of the re­mote controller has been prohib­ited by a master controller.
Timer Is Off indicator
Indicates that the timer is off.
Temperature Setting
Shows the target temperature.
Day-of-Week
Shows the current day of the week.
Time/Timer Display
Shows the current time, unless the simple or Auto Off timer is set. If the simple or Auto Off timer is set, shows the time remaining.
Sensor indication
Displayed when the remote controller sensor is used.
Locked indicator
Indicates that remote controller but­tons have been locked.
Clean The Filter indicator
Comes on when it is time to clean the filter.
Timer indicators
The indicator comes on if the corre­sponding timer is set.
Up/Down Air Direction indica­tor
The indicator shows the direc­tion of the outcoming airflow.
One Hour Only indicator
Displayed if the airflow is set to weak and downward during COOL or DRY mode. (Operation varies according to model.) The indicator goes off after one hour, at which time the airflow di­rection also changes.
Room Temperature display
Shows the room temperature.
Louver display
Indicates the action of the swing louver. Does not appear if the louver is stationary.
(Power On indicator)
Indicates that the power is on.
Fan Speed indicator
Shows the selected fan speed.
Ventilation indicator
Appears when the unit is running in Ventilation mode.
Caution
Only the Power on indicator lights when the unit is stopped and power supplied to the unit.
If you press a button for a feature that is not installed at the indoor unit, the remote controller will display the Not Available
message. If you are using the remote controller to drive multiple indoor units, this message will appear only if he feature is not present at the parent unit.
When power is turned ON for the first time, it is normal that PLEASE WAIT is displayed on the room temperature indication
(For max. 2minutes). Please wait until this PLEASE WAIT indication disappear then start the operation.
Page 7
7
SPECIFICATIONS4
4-1 STANDARD SPECIFICATIONS
Item
Capacity *1
Total input EER COP
Model name
Power supply(phase,cycle,voltage)
Input Running current
Starting current External finish Heat exchanger
Fan(drive) × No.
Fan motor output
Fan
Airflow
INDOOR UNIT
REFRIGERANT PIPING OUTDOOR UNIT
*1 Rating condition
Refrigerant piping length (one way):5m *2 Noise level is measured in an unacoustic room based on JIS conditions. *3 In case of PU-5,6YAKD, guaranteed operating range is;
Outdoor D.B.21-46˚C Indoor W.B.15.5-22.5˚C In case of PU-5,6YJSA, guaranteed operating range is; Outdoor D.B.21-52˚C Indoor W.B.15.5-22.5˚C
*4 Above data based on indicated voltage
External static pressure Operation control & Thermostat Noise level *2 Cond. Drain connection O.D.
Dimensions
Weight
Model name
Power supply(phase,cycle,voltage)
Input
Running current
Starting current External finish Refrigerant control Compressor
Model
Motor output
Starter type
Protection devices
Heat exchanger
Fan(drive) × No.
Fan motor output Fan
Airflow Noise level *2
Dimensions
Weight Refrigerant
Charge
Pipe size O.D.
Connection method Between the indoor &
outdoor unit
Cooling: Indoor unit D.B.27˚C, W.B.19˚C Outdoor unit D.B.35˚C
Indoor unit : 1phase 240V 50Hz Outdoor unit : 3phase 415V 50Hz
Liquid mm Gas mm Indoor side Outdoor side Height difference Piping length
Model name
Btu/h 44,000 41,000 44,000 41,000 54,000 51,000
kW 12.9 12.0 12.9 12.0 15.8 14.9
kcal/h 11,000 10,300 11,000 10,300 13,500 12,800
kW
kcal/h.W 2.17 2.03 1.98 1.86 2.23 2.12
W/W 2.54 2.37 2.33 2.17 2.62 2.47
kW
A A
kW
Hi
Lo
Hi Lo
Hmm
Wmm
Dmm
Hmm
Wmm
Dmm
CMM
L/s
CMM
L/s
Pa
mmAq
dB(A)
kg
lbs
kW
A A
kW
kW
3
/min
m
L/s
dB(A)
kg
lbs
kg
lbs
PE-5GAK(T)
Gross Net Gross Net Gross Net
PE-5GAK(T) PE-6GAK(T)
1PH 50Hz 220-240V 1PH 50Hz 220-240V
Galvanized steel
Cross fin coil
Centrifugal (direct) × 1
Remote control & built in
3PH 4W 50Hz 380-415V
Munsell 3Y 7.8/1.1
Capillary tube
Thermal relay, Thermal switch
HP switch, LP switch,
Anti-phase protector
Cross fin coil
Propeller (direct) × 2
5.06
0.87
4.0
6.1
0.46 0.46 50
833
40
667 100
10
46 42
R1
400
1,180
634
56
123
PU-5YAKD
4.19
6.86 7.63 64
Hermetic
BH82YEHT
3.5
Line start
Thermal relay, Thermal switch
0.100 × 2 100
1,667
55
1,258
970
345+24
119 262
R-22
5.1
11.2
9.52
19.05 Flared Flared
Max. 50m Max. 50m
5.53
PE-5GAK(T)
1PH 50Hz 220-240V
0.87
4.0
6.1 6.1
Galvanized steel
Cross fin coil
Centrifugal (direct) × 1
0.46 50
833
40
667 100
10
Remote control & built in
46 42
R1
400
1,180
634
56
123
PU-5YJSA
3PH 4W 50Hz 380-415V
4.66
66
Munsell 3Y 7.8/1.1
Capillary tube
Hermetic
ZR61KC-TFD
3.5
Line start Line start
Thermal relay, Thermal switch
HP switch,
Anti-phase protector
Cross fin coil
Propeller (direct) × 2
0.100 × 2 100
1,667 1,667
1,258
970
345+24
114 251
R-22
5.1
11.2
9.52
19.05 Flared Flared
Max. 50m Max. 50m Max. 50m
Galvanized steel
Centrifugal (direct) × 1
Remote control & built in
3PH 4W 50Hz 380-415V
Munsell 3Y 7.8/1.1
HP switch, LP switch,
Anti-phase protector
Propeller (direct) × 2
PE-6GAK(T)PE-5GAK(T)
6.03
0.87
4.0
Cross fin coil
55
917
44 733 100
10
49
45
R1
400
1,180
634
59 130
PU-6YAKD
5.16
8.45 68
Capillary tube
Hermetic
BH96YEHT
4.2
Cross fin coil
0.100 × 2 100
5655
1,258
970
345+24
120 265
R-22
5.7
12.6
9.52
19.05 Flared Flared
Max. 50m
Page 8
8
Item
Capacity *1
Total input EER COP
Model name
Power supply(phase,cycle,voltage)
Input Running current
Starting current External finish Heat exchanger
Fan(drive) × No.
Fan motor output
Fan
Airflow
INDOOR UNIT
REFRIGERANT PIPING OUTDOOR UNIT
*1 Rating condition
Refrigerant piping length (one way):5m *2 Noise level is measured in an unacoustic room based on JIS conditions. *3 In case of PU-5,6YAKD, guaranteed operating range is;
Outdoor D.B.21-46˚C Indoor W.B.15.5-22.5˚C In case of PU-5,6YJSA, guaranteed operating range is; Outdoor D.B.21-52˚C Indoor W.B.15.5-22.5˚C
*4 Above data based on indicated voltage
External static pressure Operation control & Thermostat Noise level *2 Cond. Drain connection O.D.
Dimensions
Weight
Model name
Power supply(phase,cycle,voltage)
Input
Running current
Starting current External finish Refrigerant control Compressor
Model
Motor output
Starter type
Protection devices
Heat exchanger
Fan(drive) × No.
Fan motor output Fan
Airflow Noise level *2
Dimensions
Weight Refrigerant
Charge
Pipe size O.D.
Connection method Between the indoor &
outdoor unit
Cooling: Indoor unit D.B.27˚C, W.B.19˚C Outdoor unit D.B.35˚C
Indoor unit : 1phase 240V 50Hz Outdoor unit : 3phase 415V 50Hz
Liquid mm Gas mm Indoor side Outdoor side Height difference Piping length
Model name
Btu/h 54,000 51,000 44,000 41,000 44,000 41,000
kW 15.8 14.9 12.9 12.0 12.9 12.0
kcal/h 13,500 12,800 11,000 10,300 11,000 10,300
kW
kcal/h.W 2.23 2.11 2.17 2.03 1.98 1.86
W/W 2.61 2.46 2.54 2.37 2.33 2.17
kW
A A
kW
Hi
Lo
Hi Lo
Hmm
Wmm
Dmm
Hmm
Wmm
Dmm
CMM
L/s
CMM
L/s
Pa
mmAq
dB(A)
kg
lbs
kW
A A
kW
kW
3
/min
m
L/s
dB(A)
kg
lbs
kg
lbs
PE-6GAK(T)
Gross Net Gross Net Gross Net
PE-6GAK(T)
1PH 50Hz 220-240V
Galvanized steel
Cross fin coil
Centrifugal (direct) × 1
3PH 4W 50Hz 380-415V
Munsell 3Y 7.8/1.1
Capillary tube
ZR72KC-TFD
Thermal relay, Thermal switch
Anti-phase protector
(With a high static pressure motor)
6.05 5.06 5.53
0.87
4.0
6.1
0.46 55
917
44
733 100
10
49
400
59
130
PU-6YJSA
5.18
8.48 74
Hermetic
HP switch,
56
PE-5GAK(T)
PE-5GAK(T) PE-5GAK(T)
~ 50Hz 220-240V ~ 50Hz 220-240V
0.87 0.87
4.0 4.0
7.8
Galvanized steel Galvanized steel
Cross fin coil Cross fin coil
Centrifugal (direct) × 1
833 833
40 667 667 150
15
Remote control & built in Remote control & built inRemote control & built in
48 48
4545
R1R1
400
1,180
634
56 123 123
PU-5YAKD PU-5YJSA
3PH 4W 50Hz 380-415V
4.19 4.66
6.86 7.63 64 66
Munsell 3Y 7.8/1.1 Munsell 3Y 7.8/1.1
Capillary tube
Hermetic Hermetic
BH82YEHT
Thermal relay, Thermal switch
HP switch, LP switch,
Anti-phase protector
Cross fin coilCross fin coil
100100
1,6671,667 1,667
55
1,2581,258
970970
345+24345+24 345+24
119117
5.15.7 5.1
11.212.6
FlaredFlared Flared FlaredFlared
(With a high static pressure motor)
Centrifugal (direct) × 1
3PH 4W 50Hz 380-415V
Capillary tube
ZR61KC-TFD
Thermal relay, Thermal switch
Anti-phase protector
Propeller (direct) × 2Propeller (direct) × 2Propeller (direct) × 2
PE-5GAK(T)
7.8
0.540.54 5050
40
150
15
45
R1
400
1,1801,180
634634
56
3.53.54.2
Line startLine startLine start
HP switch,
Cross fin coil
0.100 × 20.100 × 20.100 × 2 100
55
1,258
970
114 251262258
R-22R-22R-22
11.2
9.529.529.52
19.0519.0519.05
Flared Max. 50mMax. 50mMax. 50m Max. 50mMax. 50mMax. 50m
Page 9
9
Item
Capacity *1
Total input EER COP
Model name
Power supply(phase,cycle,voltage)
Input Running current
Starting current External finish Heat exchanger
Fan
INDOOR UNIT
Operation control & Thermostat Noise level *2 Cond. Drain connection O.D.
Dimensions
Weight
Model name
Power supply(phase,cycle,voltage)
External finish Refrigerant control Compressor
Heat exchanger
Fan
Noise level *2
Dimensions
Weight Refrigerant
Pipe size O.D.
Connection method Between the indoor &
REFRIGERANT PIPING OUTDOOR UNIT
outdoor unit
*1 Rating condition
Cooling: Indoor unit D.B.27˚C, W.B.19˚C
Outdoor unit D.B.35˚C Refrigerant piping length (one way):5m *2 Noise level is measured in an unacoustic room based on JIS conditions. *3 In case of PU-5,6YAKD, guaranteed operating range is;
Outdoor D.B.21-46˚C Indoor W.B.15.5-22.5˚C In case of PU-5,6YJSA, guaranteed operating range is; Outdoor D.B.21-52˚C Indoor W.B.15.5-22.5˚C
*4 Above data based on indicated voltage
Indoor unit : 1phase 240V 50Hz
Outdoor unit : 3phase 415V 50Hz
× No.
Fan(drive) Fan motor output
Airflow
External static pressure
Input Running current Starting current
Model Motor output Starter type
Protection devices
× No.
Fan(drive) Fan motor output
Airflow
Charge
Liquid mm Gas mm Indoor side Outdoor side Height difference Piping length
Model name
Btu/h
kW
kcal/h
kW
kcal/h.W
W/W
kW
A A
kW
Hi
Lo
Hi
Lo
Hmm
Wmm
Dmm
Hmm
Wmm
Dmm
CMM
L/s
CMM
L/s Pa
mmAq
dB(A)
kg
lbs
kW
A A
kW
kW
3
/min
m
L/s
dB(A)
kg
lbs
kg
lbs
(With a high static pressure motor)
Gross
54,000
15.8
13,500
2.23
2.62
PE-6GAK(T)
Net
51,000
14.9
6.03
PE-6GAK(T)
~ 50Hz 220-240V
0.87
4.0
7.8
Galvanized steel
Cross fin coil
Centrifugal (direct) ×
0.54 55
917
44
733 150
15
Remote control & built in
51 48
R1
400
1,180
634
59
130
PU-6YAKD
3PH 4W 50Hz 380-415V
5.16
8.45 68
Munsell 3Y 7.8/1.1
Capillary tube
Hermetic
BH96YEHT
4.2
Line start
Thermal relay, Thermal switch
HP switch, LP switch,
Anti-phase protector
Cross fin coil
Propeller (direct) ×
0.100 100
1,667
56
970
1,258
345+24
120 265
R-22
5.7
12.6
9.52
19.05 Flared Flared
Max. 50m Max. 50m
12,800
2.12
2.47
1
2
× 2
(With a high static pressure motor)
Gross
54,000
15.8
13,500
2.23
2.61
PE-6GAK(T)
51,000
14.9
6.05
PE-6GAK(T)
~ 50Hz 220-240V
0.87
4.0
7.8
Galvanized steel
Cross fin coil
Centrifugal (direct) ×
0.54 55
917
44
733 150
15
Remote control & built in
51 48
R1
400
1,180
634
59
130
PU-6YJSA
3PH 4W 50Hz 380-415V
5.18
8.48 74
Munsell 3Y 7.8/1.1
Capillary tube
Hermetic
ZR72KC-TFD
4.2
Line start
Thermal relay, Thermal switch
HP switch,
Anti-phase protector
Cross fin coil
Propeller (direct) ×
0.100 100
1,667
56
970
1,258
345+24
117 258
R-22
5.7
12.6
9.52
19.05 Flared Flared
Max. 50m Max. 50m
12,800
2.11
2.46
1
2
× 2
Net
Page 10
10
4-2. ELECTRICAL SPECIFICATIONS
Rating conditions
JIS B 8616
Indoor : D.B. 27°C (80°F), W.B. 19°C (66°F) Outdoor : D.B. 35°C (95°F), W.B. 24°C (75°F)
Indoor unit
Input kW 0.87 0.87 0.87 0.87 Current A 4.0 4.0 4.0 4.0 Starting current A 6.1 6.1 7.8 7.8
Outdoor unit
PE-5GAK(T) PE-6GAK(T)
PU-5YAKD
PU-5YJSA
PU-6YAKD
PU-6YJSA
PE-5GAK(T)
(With a high static pressure motor)
PU-5YAKD
PU-5YJSA
PE-6GAK(T)
(With a high static pressure motor)
PU-6YAKD
PU-6YJSA
Page 11
11
DATA5
Cooling capacity correction factors
5-1. PERFORMANCE DATA
Cooling capacity
Notes : CA: Capacity (kW)
P.C.: Power can sweeping (kW)
Model name
PE-5GAK(T)
PU-5YAKD
PE-6GAK(T)
PU-6YAKD
Model name
PE-5GAK(T)
PU-5YJSA
PE-6GAK(T)
PU-6YJSA
Indoor Intake
air W.B.˚C
16 13.0 4.06 12.7 4.23 12.2 4.55 11.7 4.88 11.2 5.21 10.6 5.54 18 13.9 4.14 13.5 4.31 13.0 4.66 12.5 5.00 11.9 5.34 11.4 5.69 20 14.7 4.22 14.4 4.40 13.9 4.76 13.3 5.12 12.8 5.49 12.2 5.86 22 15.6 4.29 15.3 4.49 14.7 4.86 14.2 5.24 13.6 5.64 13.0 6.05 16 13.6 4.83 13.2 5.04 12.8 5.43 12.2 5.82 11.7 6.21 11.1 6.60 18 14.5 4.93 14.1 5.14 13.6 5.55 13.1 5.96 12.5 6.37 11.9 6.78 20 15.4 5.02 15.0 5.24 14.5 5.67 13.9 6.10 13.4 6.54 12.7 6.98 22 16.3 5.12 16.0 5.35 15.4 5.79 14.9 6.25 14.3 6.72 13.6 7.21
Indoor Intake
air W.B.˚C
16 12.9 4.48 12.7 4.65 12.2 4.98 11.7 5.31 11.2 5.70 10.7 6.08 9.5 6.41 8.4 6.58 18 13.8 4.53 13.5 4.70 13.0 5.09 12.5 5.47 11.9 5.86 11.4 6.19 10.2 6.58 9.1 6.75 20 14.6 4.65 14.4 4.81 13.9 5.20 13.3 5.59 12.8 5.97 12.2 6.41 11.0 6.80 9.7 6.97 22 15.6 4.76 15.2 4.92 14.7 5.31 14.2 5.75 13.6 6.14 13.0 6.64 11.3 7.08 10.0 7.24 16 13.5 4.90 13.3 5.08 12.7 5.45 12.3 5.81 11.7 6.23 11.2 6.66 9.9 7.02 8.8 7.20 18 14.4 4.96 14.2 5.14 13.6 5.57 13.1 5.99 12.5 6.41 11.9 6.78 10.7 7.20 9.5 7.38 20 15.3 5.08 15.1 5.26 14.5 5.69 13.9 6.11 13.4 6.53 12.7 7.02 11.5 7.44 10.2 7.62 22 16.3 5.20 16.0 5.38 15.4 5.81 14.8 6.29 14.3 6.72 13.6 7.26 11.8 7.74 10.5 7.93
21 25 30 35 40 45
CA P.C. CA P.C. CA P.C. CA P.C. CA P.C. CA P.C.
CA P.C. CA P.C. CA P.C. CA P.C. CA P.C. CA P.C. CA P.C. CA P.C.
PE-5
5m (16ft)
1.0
10m (33ft)
0.978
15m (49ft)
Outdoor intake air D.B.˚C
20m (66ft)
0.962
Outdoor intake air D.B.˚C
Refrigerant piping length (one way)
35m (115ft)
0.948
25m (82ft)
0.934
30m (98ft)
0.921
0.908
5021 25 30 35 40 45
40m (131ft)
0.896
52
45m (148ft)
0.884
50m (164ft)
0.875
PE-6
1.0
0.971
0.950
0.931
0.912
0.896
0.880
0.864
0.850
0.840
Page 12
12
The unit of pressure has been changed to Mpa based on SI (International System of Units) in accordance with I.S.O. (International Organization for Standardization).
The conversion factor is : 1(Mpa) =10.2 (OOf/FF)
5-2. STANDARD OPERATION DATA
Mode
Capacity (GROSS) Capacity (NET)
Total
Input Indoor unit Phase, Hz
Volts Amperes
Outdoor unit
Phase, Hz
Electrical circuit
Volts Amperes Discharge Pressure Suction Pressure Discharge temp. Suction temp.
Refrigerant circuit
Ref. pipe length
Indoor intake air temp.
Outdoor intake air temp.
Model name
D.B. ˚C27 W.B. ˚C19 19 19 D.B. ˚C35 35 35 W.B. ˚C24 24 24
SHF
BF
PE-5GAK(T) PE-5GAK(T) PE-6GAK(T)
Cooling Cooling Cooling kW 12.9 12.9 15.8 kW 12.0 12.0 14.9 kW 5.06 5.53 6.03
PE-5GAK(T) PE-5GAK(T) PE-6GAK(T)
1, 50 1, 50 1, 50 V 240 240 240 A 4.0 4.0 4.0
PU-5YAKD PU-5YJSA PU-6YAKD
3, 50 3, 50 3, 50 V 415 415 415 A 6.86 7.63 8.45
MPa 1.87 1.90 2.03
2
kgf/cm
MPa 0.40 0.42 0.40
2
kgf/cm
˚C74 73 82 ˚C
m
19.1 19.4 20.7
4.1 4.3 4.1
2 5
0.82 0.82 0.82
0.27 0.27 0.19
9 5
27 27
2 5
Page 13
13
Mode
The unit of pressure has been changed to Mpa based on SI (International System of Units) in accordance with I.S.O. (International Organization for Standardization).
The conversion factor is : 1(Mpa) =10.2 (OOf/FF)
Capacity (GROSS) Capacity (NET)
Total
Input
Indoor unit
Phase, Hz Volts Amperes
Outdoor unit
Phase, Hz
Electrical circuit
Volts Amperes Discharge Pressure Suction Pressure Discharge temp. Suction temp.
Refrigerant circuit
Ref. pipe length
Indoor intake air temp.
Outdoor intake air temp.
Model name
D.B. ˚C27 W.B. ˚C19 D.B. ˚C35 W.B. ˚C24
SHF
BF
PE-6GAK(T)
Cooling kW 15.8 kW 14.9 kW 6.05
PE-6GAK(T)
1, 50 V 240 A 4.0
PU-6YJSA
3, 50 V 415 A 8.48
MPa 1.99
2
kgf/cm
MPa 0.42
2
kgf/cm
˚C79 ˚C11
m5
20.3
4.3
0.82
0.19
PE-5GAK(T)
(With a high static pressure motor)
Cooling
12.9
12.0
5.06
PE-5GAK(T)
(With a high static pressure motor)
1, 50
240
4.0
PU-5YAKD
3, 50
415
6.86
1.87
19.1
0.40
4.1 74
2
5 27 19 35 24
0.82
0.27
Page 14
14
Mode
The unit of pressure has been changed to Mpa based on SI (International System of Units) in accordance with I.S.O. (International Organization for Standardization).
The conversion factor is : 1(Mpa) =10.2 (OOf/FF)
Capacity (GROSS) Capacity (NET)
Total
Input
Indoor unit
Phase, Hz Volts Amperes
Outdoor unit
Phase, Hz
Electrical circuit
Volts Amperes Discharge Pressure Suction Pressure Discharge temp. Suction temp.
Refrigerant circuit
Ref. pipe length
Indoor intake air temp.
Outdoor intake air temp.
Model name
D.B. ˚C27 27 27 W.B. ˚C19 19 19 D.B. ˚C35 35 35 W.B. ˚C24 24 24
SHF
BF
PE-5GAK(T)
(With a high static pressure motor)
Cooling Cooling Cooling kW 12.9 15.8 15.8 kW 12.0 14.9 14.9 kW 5.53 6.03 6.05
PE-5GAK(T)
(With a high static pressure motor)
1, 50 1, 50 1, 50 V 240 240 240 A 4.0 4.0 4.0
PU-5YJSA PU-6YAKD PU-6YJSA
3, 50 3, 50 3, 50 V 415 415 415 A 7.63 8.45 8.48
MPa 1.90 2.03 1.99
2
kgf/cm
MPa 0.42 0.40 0.42
2
kgf/cm
˚C738279 ˚C9 2 11
m5 5 5
19.4 20.7 20.3
4.3 4.1 4.3
0.82 0.82 0.82
0.27 0.19 0.19
PE-6GAK(T)
(With a high static pressure motor)
PE-6GAK(T)
(With a high static pressure motor)
PE-6GAK(T)
(With a high static pressure motor)
PE-6GAK(T)
(With a high static pressure motor)
Page 15
15
Service Ref. : PE-6GAK(T)
5-3. FAN PERFORMANCE AND CORRECTED AIRFLOW
Service Ref. : PE-5GAK(T)
Corrected Air flow
Corrected Air flow
Fan Performance Curve
Fan Performance Curve
300
250
200
150
100
External static pressure (Pa)
50
0
35.0 40.0 45.0 50.0 55.0
Lo
Hi
Air flow
300
250
200
Hi
(CMM)
1.1
1.0
Capacity/ input factor
0.9 35 40 45 50 55
1.1
Capacity input
(CMM)
Air flow
Capacity input
150
100
External static pressure (Pa)
50
0
40.0 45.0 50.0 55.0 60.0
Lo
Air flow
(CMM)
1.0
Capacity/ input factor
0.9
40 45 50 55 60
Air flow
(CMM)
Page 16
16
Service Ref. : PE-5GAK(T) (With a high static pressure motor)
Service Ref. : PE-6GAK(T) (With a high static pressure motor)
Fan Performance Corrected Air flow
Fan Performance Corrected Air flow
300
250
1.1
Capacity input
200
150
100
External static pressure (Pa)
50
Lo
Hi
1.0
Capacity/ input factor
0.9 35 40 45 50 55
0
35.0 40.0 45.0 50.0 55.0
Air flow
(CMM)
300
250
200
150
Hi
1.1
1.0
(CMM)
Air flow
Capacity input
100
External static pressure (Pa)
50
0
40.0 45.0 50.0 55.0 60.0
Lo
Air flow
(CMM)
Capacity/ input factor
0.9 40 45 50 55 60
Air flow
(CMM)
Page 17
17
5-4. SOUND DATA
Indoor units
1) Sound Levels
Model
PE-5
PE-6
PE-5
(High static pressure motor)
PE-6
(High static pressure motor)
SPL
dB(A) 63Hz 125Hz 250Hz 500Hz 1000Hz 2000Hz 4000Hz 8000Hz
46 50 49 46 44 42 38 28 22 42 44 44 41 40 38 34 23 15 49 54 53 51 47 43 34 29 25 45 51 51 47 44 40 31 25 21 48 52 51 48 46 44 40 30 24 45 47 47 44 43 41 37 26 18 51 55 54 51 49 47 43 33 27 48 50 50 47 46 44 40 29 21
Position measurement
Indoor unit
2m
Outlet
PEH-5,6: Upper High/Lower Low
OCTAVE BAND FREQ.Hz
1m
Inlet
Measurement point
1.5m
Page 18
18
6
OUTLINES AND DIMENSIONS
6-1. INDOOR UNIT
PE-5,6 GAK (T)
Unit : mm
199
3 Holes 20-
34124
882
51
6X130(=780)51
Return air
duct flange
10
130
20
1080
200
131
3.1 Holes 14-
12 Holes 4-
For hanging bolt M10
[Field supply]
10
55
130
3X130(=390)
Top view
55
Supply air
duct flange
1180
1120
11 250 95
1064
Front view
361 500 179
42
2pcs.
62
1pc.
20
462
Control box
Remote
Rubber bush
controller wiring
40
70 1295575
Outdoor unit
Rubber bush
Rubber bush
connection wiring
A
Power supply
wiring
<
40 1040 40
54
10
634
530
50
10
Return air
sensor
400
376
2510010025
262 73
130
35
144
22330
Supply air
A
130
145
56539
35
89
Drain R1
Left side view
9.52 (3/8 flare)
Refrigerant pipe
Accessory
Pipe cover
(For dew condensation prevention of
local piping and unit connection.)
Remote controller
19.05 (3/4 flare)
Refrigerant pipe
Return air
Page 19
19
6-2. REMOTE CONTROLLER
130
120
19
Unit : mm
Page 20
20
7
WIRING DIAGRAM
PE-5,6GAK(T)
ROOM TEMP
LIQUID PIPE TEMP
NAME
FERRITE COREFB
SURGE KILLERCR
AUXILIARY RELAY (INDOOR FAN MOTOR<HIGH SPEED>)
OVER CURRENT RELAY (INDOOR FAN MOTOR)
MAGNETIC CONTACTOR (INDOOR FAN MOTOR)
FAN MOTOR (INDOOR)
TERMINAL BLOCK
52F
51F
MF1
SYMBOL NAME
TB2,4,5
INDOOR UNIT
AUXILIARY RELAY (INDOOR FAN MOTOR<LOW SPEED>)
THERMISTOR
FUSE FUSE (T6.3AL250V)
ZNR VARISTOR
C CAPACITOR
TH1
TH2
X2Hi
X1Lo
INDOOR
CONTROLLER
C
5
6
(*1)
MF1
124
C01
X2Hi
X1Lo
RED
BLUE
WHITE
L2L3N
GREEN/YELLOW
REDL1
TB2 52F 51F
INDOOR UNIT
CONNECTOR (DRAIN SENSOR)CN31
CONNECTOR (REMOTE SWITCH)CN32
CONNECTOR (LOSSNAY)CN2L
AUXILIARY RELAYX4-6
SWITCH (MODEL SELECTION)
SWITCH (SYSTEM SELECTION)
SW5
SW1
LED (POWER SUPPLY <REMOTE CONTROLLER>)
SWITCH (EMERGENCY OPERATION)
CONNECTOR (EMERGENCY OPERATION)
LED (POWER SUPPLY)
SW6
SWE
LED1
LED2
BOARD
DSA DSR
ZNR5~7
SNB BOARD 1
BLACK
ARRESTER
CONNECTOR (WIRELESS REMOTE CONTROLLER)
CONNECTOR (CENTRALLY CONTROL)
CONNECTOR (HA TERMINAL-A)
VARISTOR
CN90
CN51
CN41
DSA,DSR
ZNR5~7
SYMBOL
SNB BOARD 1
REMOTE CONTROLLER
TB6 TERMINAL BLOCK
matching wiring and terminal.
2.Color of earth wire is yellow and green twisting.
3.Specification subject to change without notice.
4.Indoor and outdoor connecting wires are made with polarities,make sure
Note:1.The dotted lines show field wiring.
LCD
BOARD
REMOTE CONTROLLER
TB6
REMOTE CONTROLLER
FB
12
LED1
CN2D
2
1
TAB1
DC
INDOOR
13.1V
POWER BOARD
3
1
X1
Hi Lo
X2
CR
52F
CN2S
CNSK
X2
Lo Hi
X1
51F
DC13.1V
CND
FUSE
13 1 3
CNDK
X5 X4
1357
X6
FAN
ZNR
X6 X5 X4
If a trouble occurs with either the remote controller or the indoor microcom-
puter and no other trouble exists, emergency operation for cooling or heating
can be performed by changing the setting of connector (SWE) and switch (SW6)
on the indoor controller board.
SWE : ON / Indoor fan is running high speed.
SW6-1 : ON / Emargency operation of cooling mode.
6. mark is connector. mark is terminal.
5.Emergency operation
7.This motor(*1) includes auto reset type internal thermostat.
Therefore, do not change factory set value of over current relays.
1.To protect fan motor from abnormal current,over current relays is installed.
Caution,
OUTDOOR UNIT
TO OUTDOOR UNIT
CONNECTING WIRES
(POLAR)
TB5
121
1
LED2
CN32 CN31
CN2L
CN41
CN51
21
SW6
ON
OFF
INDOOR
CONTROLLER BOARD
TB4
2
2
123
CN22
CN30
121
2
CN20
CN21
CN90
ON
OFF
5
SW5
3214
ON
OFF
54321 678
SW1
SWE
ON
OFF
TH1
TH2
CIRCUIT BREAKER
(FIELD SUPPLY)
PE-5,6GAK(T) : 15A
POWER SUPPLY
~PE
220/230/240V
50Hz
PE
Page 21
21
REFRIGERANT SYSTEM DIAGRAM8
PE-5GAK(T) / PU-5YJSA PE-6GAK(T) / PU-6YJSA
PE-5GAK(T)/PU-5YAKD PE-6GAK(T)/PU-6YAKD
Unit : mm
INDOOR UNIT
Indoor heat exchanger
Indoor coil thermistor TH2
Distributor
Strainer
Refrigerant pipe 19.05 (3/4") (With insulator)
Flared connection
Refrigerant pipe 9.52 (3/8") (With insulator)
Flared connection
plug
Ball valve
Check plugCharge
High pressure switch
Thermal switch
Accumulator
Capillary tube PU-5YJSA (O.D. 4.0 × I.D. 2.4 – L840) × 2pcs PU-6YJS A (O.D. 4.0 × I.D. 2.4 – L1200) × 2pcs
Compressor
Ball valve (with service port)
Capillary tube PU-5YJSA (O.D. 4.0 × I.D. 2.4 – L400) PU-6YJSA (O.D. 4.0 × I.D. 2.4 – L200)
OUTDOOR UNIT
Outdoor heat exchanger
Strainer
DPR
Refrigerant pipe 19.05 (with insulator)
Indoor heat exchanger
Indoor coil thermistor TH2
Distributor
Refrigerant pipe 9.52 (with insulator)
Flared
Connection
Ball valve
Strainer
Accumulator
Strainer
Flow of refrigerant
Charge plug
Compressor switch
Strainer
Compressor
High pressure switch
Thermal switch
OUTDOOR UNITINDOOR UNIT
Outdoor heat exchanger
Strainer
Capillary tube PU-5YAKD (O.D.4.0×I.D.2.4 PU-6YAKD (O.D.4.0×I.D.2.4
L840)
L1200)
Strainer
Ball valve (with charge plug)
Flow of refrigerant
Page 22
22
9 TROUBLESHOOTING
<Error code display by self-diagnosis and actions to be taken for service (summary)>
Present and past error codes are logged and displayed on the wired remote controller or controller board of outdoor unit. Actions to be taken for service,which depends on whether or not the the inferior phenomenon is reoccurring at service, are summarized in the table below. Check the contents below before investigating details.
9-1. TROUBLESHOOTING
Unit conditions at service
Error code
Actions to be taken for service (summary)
The inferior phenomenon is reoccurring.
Displayed
Not displayed
Judge what is wrong and take a corrective action according to SELF-DIAGNOSIS ACTION TABLE (7-3).
Identify the cause of the inferior phenomenon and take a corrective action according to TROUBLESHOOTING BY INFERIOR PHENOMENA (7-4).
The inferior phenomenon is not reoccurring.
Logged
Not logged
1Consider the temporary defects such as the work of protection devices in the refrigerant circuit including compressor, poor connection of wiring, noise and etc. Re-check the symptom, and check the installation environment, refrigerant amount, weather when the inferior phenomenon occurred, and wiring related. 2Reset error code logs and restart the unit after finishing service. 3There is no abnormality in electrical components, controller boards, and remote controller.
1Recheck the abnormal symptom. 2Identify the cause of the inferior phenomenon and take
a corrective action according to TROUBLESHOOTING BY INFERIOR PHENOMENA (7-4). 3Continue to operate unit for the time being if the cause is not ascertained. 4There is no abnormality in electrical components, controller boards, remote controller etc.
PAR-21MAA
ON/OFF
FILTER
CHECK
OPERATION
CLEAR
TEST
TEMP.
MENU
BACK DAY
MONITOR/SET
CLOCK
ON/OFF
ERROR CODE
ERROR CODE
ERROR CODE
1 Turn on the power. 2 Press the [CHECK] button twice. 3 Set address with [TEMP] button if system control is used. 4 Press the [ON/OFF] button to stop the self-check.
A CHECK button B Address C TEMP. button D IC : Indoor unit
OC: Outdoor unit E Check code
F Unit No. G Timer ON/OFF button
A
F
C
BBEED
G
<To delete check code>
1 Display the error code at the self-check result display screen. 2 The address for self-check will blink when the
G ON/OFF
button is pressed twice within three seconds.
– – – – : No trouble generated in the past. F F F F : No corresponding unit.
9-2. MALFUNCTION-DIAGNOSIS METHOD BY REMOTE CONTROLLER
<In case of trouble during operation>
When a malfunction occurs to air conditioner, both indoor unit and outdoor unit will stop and operation lamp blinks to inform unusual stop.
Wired remote controller
Page 23
23
Errors detected by indoor unit
Wired remote controller
1 Check code
Symptom Remark
P1
Intake sensor error
P2 Pipe (TH2) sensor error P4 Drain sensor error P5 PA
Drain pump error
Forced compressor stop P6 Freezing/ Overheating safeguard operation P8 Pipe temperature error / Outdoor unit error E4, E5 Remote controller signal receiving error
– –
– –
Fb Indoor unit control system error (memory error, etc.) E0, E3
Remote controller transmission error E1, E2 Remote controller control board error
On wired remote controller
1Check code displayed in the LCD.
If the unit cannot be operated properly after test run has been performed, refer to the following table to remove the cause.
Wired remote controller
PLEASE WAIT
Symptom
For about 2 minutes follow­ing power-on
For about 2 minutes following power-on,op­eration of the remote controller is not possible due to system start-up. (Correct operation)
Cause
Connector for the outdoor units protection
PLEASE WAIT → Error code
Display messages do not appear even when operation switch is turned ON (operation lamp does not light up).
After about 2 minutes has expired follow­ing power-on
device is not connected.
Reverse or open phase wiring for the outdoor units power terminal block
Incorrect wiring between indoor and outdoor units
Remote controller wire short
Note: Operation is not possible for about 30 seconds after cancellation of function selection. (Correct operation)
For description of each LED (LED1, 2) provided on the indoor controller, refer to the following table.
LED1 (power for microcomputer) Indicates whether control power is supplied. Make sure that this LED is
always lit.
LED2 (power for wired remote controller)
Indicates whether power is supplied to the wired remote controller. This LED lights only in the case of the main indoor unit.
Page 24
24
9-3. SELF-DIAGNOSIS ACTION TABLE
Error Code
Meaning of error code and detection method
Cause
Countermeasure
P1
Abnormality of room temperature thermistor (TH1)
1 The unit is in three-minute resume
prevention mode if short/open of thermistor is detected. Abnormal if the unit does not reset normally after three minutes. (The unit returns to normal operation, if it has normally reset.)
2 Constantly detected during cooling,
drying, and heating operation. Short: 90
: or more
Open: -40
: or less
1 Defective thermistor
characteristics.
2 Contact failure of connector
(CN20) on the indoor controller board. (Insert failure)
3 Breaking of wire or contact
failure of thermistor wiring.
4 Defective indoor controller
board.
13 Check resistance value of thermistor.
0
: ····15.0k" 10: ······9.6k" 20: ······6.3k" 30: ······4.3k" 40: ······3.0k" If you put force on (draw or bend) the lead wire with measuring resistance value of thermistor breaking of wire or contact failure can be detected. 2 Check contact failure of connector (CN20)
on the indoor controller board. Refer to 9-7.
Turn the power on again and check restart
after inserting connector again. 4 Check room temperature display on remote
controller.
Replace indoor controller board if there is
abnormal difference with actual room
temperature. Turn the power off, and on again to operate
after check.
P2
Abnormality of pipe temperature thermistor/Liquid (TH2)
1 The unit is in three-minute resume
prevention mode if short/open of thermistor is detected. Abnormal if the unit does not reset normally after three minutes. (The unit returns to normal operation, if it has normally reset.)
2 Constantly detected during cooling,
drying, and heating (except defrosting) operation. Short: 90
: or more
Open: -40
: or less
1 Defective thermistor
characteristics.
2 Contact failure of connector
(CN21) on the indoor controller board. (Insert failure)
3 Breaking of wire or contact
failure of thermistor wiring.
4 Defective refrigerant circuit is
causing thermistor temperature of 90
: or more or -40: or
less.
5 Defective indoor controller board.
1–3 Check resistance value of thermistor.
For characteristics, refer to (P1) above. 2 Check contact failure of connector (CN21)
on the indoor controller board. Refer to 9-7. Turn the power on and check restart after inserting connector again.
4 Check pipe <liquid> temperature with remote
controller in test run mode. If pipe <liquid> temperature is exclusively low (in cooling mode) or high (in heating mode), refrigerant circuit may have defective.
5 Check pipe <liquid> temperature with remote
controller in test run mode. If there is exclusive difference with actual pipe <liquid> temperature, replace indoor controller board.
Turn the power off, and on again to operate after check.
P4
Abnormality of drain sensor (DS)
1 Suspensive abnormality, if short/open of
thermistor is detected for 30 seconds continuously. Turn off compressor and indoor fan.
2 Short/open is detected for 30 seconds
continuously during suspensive abnormality. (The unit returns to normal operation,
if it has normally reset.)
3 Detect the following condition.
During cooling and drying operation.
In case that pipe <liquid> temperature
- room temperature <-10deg
(Except defrosting)
When pipe <liquid> temperature or room temperature is short/open temperature.
During drain pump operation.
1 Defective thermistor
characteristics
2 Contact failure of connector
(CN31) on the indoor controller board. (Insert failure).
3 Breaking of wire or contact
failure of drain sensor wiring.
4 Defective indoor controller board.
1–3 Check resistance value of thermistor.
0
: ······6.0k" 10: ····3.9k" 20: ····2.6k" 30: ····1.8k" 40: ····1.3k" 2 Check contact failure of connector (CN31)
on the indoor controller board. Refer to 9-7. Turn the power on again and check restart after inserting connector again.
4 Replace indoor controller board if drain
pump operates with the line of drain sensor connector CN31-
1 and 2 is short-circuited,
and abnormality reappears.
Turn the power off, and on again to operate after check.
P5
Malfunction of drain pump (DP)
1 Suspensive abnormality, if thermistor
of drain sensor is let heat itself and temperature rises slightly. Turn off compressor and indoor fan.
2 Drain pump is abnormal if the condition
above is detected during suspensive abnormality.
3 Constantly detected during drain pump
operation.
1 Malfunction of drain pump 2 Defective drain
Clogged drain pump Clogged drain pipe
3 Attached drop of water at the
drain sensor
Drops of drain trickles from lead wire.
Clogged filter is causing wave of drain.
4 Defective indoor controller board.
1 Check if drain-up machine works. 2 Check drain function. 3 Check the setting of lead wire of drain
sensor and check clogs of the filter.
4 Replace indoor controller board if drain
pump operates with the line of drain sensor connector CN31-1 and 2 is short-circuited and abnormality reappears. Refer to 9-7.
Turn the power off, and on again to operate after check.
Page 25
25
Error Code
Meaning of error code and detection method
Cause
Countermeasure
P6
Freezing/overheating protection is working
1 Freezing protection (Cooling mode)
The unit is in six-minute resume prevention mode if pipe temperature stays under
-15: for three minutes, three minutes after the compressor started. Abnormal if it stays under -15: for three minutes again within 16 minutes after six-minute resume prevention mode. <Frost prevention mode> If pipe temperature is 1: or below when 16 minutes has passed after com­pressor starts operating, unit will start operating in frost prevention mode which stops compressor operation. After that, when pipe temperature stays 10: or more for 3 minutes, frost prevention mode will be released and compressor will restart its operation.
P8
1 Slight temperature difference
between indoor room temperature and pipe tempera­ture thermistor
Shortage of refrigerant
Disconnected holder of pipe
thermistor
Defective refrigerant circuit
2 Converse connection of
extension pipe (on plural units connection)
3 Converse wiring of indoor/
outdoor unit connecting wire (on plural units connection)
4 Defective detection of indoor
room temperature and pipe temperature thermistor
5 Stop valve is not opened
completely.
(Cooling or drying mode)
1 Clogged filter (reduced airflow) 2 Short cycle of air path 3 Low-load (low temperature)
operation beyond the tolerance range
4 Defective indoor fan motor
Fan motor is defective.
Indoor controller board is
defective.
5 Defective outdoor fan control 6 Overcharge of refrigerant 7 Defective refrigerant circuit
(clogs)
(Cooling or drying mode)
1 Check clogs of the filter. 2 Remove shields.
4 Measure the resistance of fan motor's winding.
Measure the output voltage of fan's connector (Relay for FAN) onthe indoor controller board. * The indoor controller board should be
normal when voltage of AC 220~240V is detected while fan motor is connected. Refer to 9-7.
5 Check outdoor fan motor. 67 Check operating condition of refrigerant
circuit.
Abnormality of pipe temperature
<Cooling mode> Detected as abnormal when the pipe tem­perature is not in the cooling range 3 min­utes later of compressor start and 6 min­utes later of the liquid pipe is out of cooling range. Note 1) It takes at least 9 min. to detect. Note 2) Abnormality P8 is not detected in
drying mode. Cooling range : -5 deg ] (TH2-TH1) TH2: Liquid pipe temperature TH1: Intake temperature
1~4 Check pipe temperature with room
temperature display on remote controller.
23Check converse connection of extension
pipe or converse wiring of indoor/outdoor unit connecting wire.
1 Wrong wiring of indoor/outdoor
connecting wire
2 Reversed phase 3 Protection device is working 4 Damaged outdoor coil thermis-
tor
Abnormality in outdoor unit
1 Check the indoor/outdoor connecting wire. 2 Change the connection of electric wiring. 3 Check the protection device. 4 Measure the resistance of the outdoor coil
thermistor. If the resistance is normal, replace the outdoor controller board.
Page 26
26
Error Code
Meaning of error code and detection method
Cause
Countermeasure
E0
or
E4
Remote controller transmission error(E0)/signal receiving error(E4)
1 Abnormal if main or sub remote con-
troller can not receive normally any transmission from indoor unit of refriger­ant address “0” for three minutes. (Error code : E0)
2 Abnormal if sub remote controller could
not receive for any signal for two min­utes. (Error code: E0)
1 Abnormal if indoor controller board can
not receive normally any data from remote controller board or from other indoor controller board for three minutes. (Error code: E4)
2 Indoor controller board cannot receive
any signal from remote controller for two minutes. (Error code: E4)
1 Check disconnection or looseness of indoor
unit or transmission wire of remote controller.
2 Set one of the remote controllers “main.
If there is no problem with the action above.
3 Check wiring of remote controller.
Total wiring length: max.500m (Do not use cable x 3 or more)
The number of connecting indoor units: max.16units
The number of connecting remote con­troller: max.2units
When it is not the above-mentioned problem of
1~3 4 Diagnose remote controllers.
a) When RC OK is displayed,
Remote controllers have no problem. Put the power off, and on again to check. If abnormality generates again, replace indoor controller board.
b) When RC NG is displayed,
Replace remote controller. c) When RC E3 is displayed, d) When ERC 00-06 is displayed, [ c),d)Noise may be causing abnormality. ]
* If the unit is not normal after replacing
indoor controller board in group control, indoor controller board of address “0” may be abnormal.
E3
or
E5
Remote controller transmission error(E3)/signal receiving error(E5)
1 Abnormal if remote controller could not
find blank of transmission path for six seconds and could not transmit. (Error code: E3)
2 Remote controller receives transmitted
data at the same time, compares the data, and when detecting it, judges different data to be abnormal 30 continuous times. (Error code: E3)
1 Abnormal if indoor controller board could
not find blank of transmission path.
(Error code: E5)
2 Indoor controller board receives trans-
mitted data at the same time, compares the data,and when detecting it, judges different data to be abnormal 30 continuous times. (Error code: E5)
1 Set a remote controller to main, and the
other to sub.
2 Remote controller is connected with only one
indoor unit.
3 The address changes to a separate setting. 4~6 Diagnose remote controller.
a) When RC OKis displayed, remote con-
trollers have no problem. Put the power off,and on again to check. When becoming abnormal again, replace indoor controller board.
b) When RC NGis displayed, replace
remote controller.
c)
When RC E3or ERC 00-66is displayed, noise may be causing abnormality.
1 Contact failure at transmission
wire of remote controller
2 All remote controllers are set
as sub remote controller. In this case, E0 is displayed on remote controller, and E4 is displayed at LED (LED1, LED2) on the outdoor controller circuit board.
3 Mis-wiring of remote controller. 4 Defective transmitting receiving
circuit of remote controller
5 Defective transmitting receiving
circuit of indoor controller board of refrigerant address “0”.
6 Noise has entered into the
transmission wire of remote controller.
1 Two remote controller are set
as main. (In case of 2 remote con-
trollers)
2 Remote controller is connected
with two indoor units or more.
3 Repetition of refrigerant
address.
4 Defective transmitting receiving
circuit of remote controller.
5 Defective transmitting receiving
circuit of indoor controller board.
6 Noise has entered into trans-
mission wire of remote con­troller.
Page 27
27
Error Code
Meaning of error code and detection method
Cause
Countermeasure
Fb
Abnormality of indoor controller board
Abnormal if data cannot be normally read from the nonvolatile memory of the indoor controller board.
1 Defective indoor controller
board.
1 Replace indoor controller board.
E1
or
E2
Abnormality of remote controller control board
1 Abnormal if data cannot be normally
read from the nonvolatile memory of the remote controller control board.
(Error code: E1)
2 Abnormal if the clock function of remote
controller cannot be normally operated.
(Error code: E2)
1 Defective remote controller. 1 Replace remote controller.
PA (2502) (2500)
Forced compressor stop (due to water leakage abnormality)
1 When the intake temperature subtracted
with liquid pipe temperature is less than
-10
:, drain sensor is detected whether it is soaked in the water or not at the interval of 90 seconds. (Drain pump will start operating
when the drain sensor is detected to be
soaked in the water.)
2 The unit has a water leakage abnormality
when the following conditions, a and b, are
satisfied while the above-mentioned detection
is performed. a) The drain sensor is detected to be
soaked in the water 10 times in a row.
b) The intake temperature subtracted with
liquid pipe temperature is detected to be less than -10
: for a total of 30 minutes.
(When the drain sensor is detected to
be NOT soaked in the water, the detection
record of a and b will be cleared.)
3 The drain sensor detection is performed
in operations other than cooling. (When the unit stops operating, during heating or fan operation, when the unit stops because of some abnormality)
*Once the water leakage abnormality is
detected, abnormality state will not be released until the main power is reset.
1 Drain pump trouble 2 Drain defective
· Drain pump clogging
· Drain pipe clogging
3 Open circuit of drain sensor
side heater
4 Contact failure of drain sensor
connector
5 Dew condensation on drain
sensor
· Drain water descends along lead wire.
· Drain water waving due to filter clogging.
6 Extension piping connection
difference at twin, triple, quadruple system.
7 Mis-wiring of indoor/ outdoor
connecting at twin, triple, quadruple system.
8 Room temperature thermistor /
liquid pipe temperature thermis­tor detection is defective.
1Check the drain pump.
Performance 2Please confirm whether water can be drained.
3Confirm the resistance of the drain sensor
side heater.
4Check the connector contact failure.
5 Check the drain sensor leadwire mounted.
Check the filter clogging
6Check the piping connection.
7Check the indoor/ outdoor connecting wires.
8Check the room temperature display of
remote controller.
Check the indoor liquid pipe temperature
display of outdoor controller board.
Page 28
28
When LED1 on indoor controller board is also off.
1 Power supply of 220~240V AC is not supplied to
indoor unit.
2 Defective indoor controller board.
3 Defective indoor power board.
9-4. TROUBLESHOOTING BY INFERIOR PHENOMENA
Phenomena
Cause
Countermeasure
(1)LED2 on indoor controller board
is off.
When LED1 on indoor controller board is lit.
1 Mis-setting of main/sub for indoor unit
(There is no unit corresponding to main unit.)
1 Reconfirm the setting of main/sub for
indoor unit
Set the main unit. Set main/sub using SW5-3 on indoor controller board.
1 Check the voltage of indoor power supply
terminal block (L,N).
When AC220~240V is not detected. Check the power supply wiring.
When AC220~240V is detected.
-Check 2 (below).
2 Check voltage output from CNDK on
indoor controller board.
When AC220~240V is not detected. Check the fuse on indoor controller board. Check the wiring connection between indoor power supply terminal block and CND on indoor controller board.
When AC220~240V is detected.
-Check 3 (below).
3 Check voltage output from CN2S on
indoor power board.
When no voltage output. Check the wiring connection between CNDK on indoor controller board and CNSK on indoor power board. If no problem are found,indoor power board is defective.
When DC12.5~13.7V is detected. Check the wiring connection between CN2S on indoor power board and CN2D on indoor power board. If no problem are found,indoor controller board is defective.
(2)LED2 on indoor controller board
is blinking.
When LED1 on indoor controller board is also blinking. Connection failure of indoor/outdoor unit connecting wire
When LED1 is lit.
1 Mis-wiring of remote controller wires
When 2 indoor units are wired in one refrigerant system, each indoor unit sets main unit. (SW5-3)
2 Short-cut of indoor/outdoor unit connecting wire.
3 Short-cut of remote controller wires 4 Defective remote controller
Check indoor/outdoor unit connecting wire for connection failure.
1 Check the connection of remote con-
troller wires in case of twin triple indoor unit system. When 2 or more indoor units are wired in one refrigerant system, connect remote controller wires to one of those units.
2 Remove indoor/outdoor connecting wires
and check LED2 on indoor controller board.
When LED2 is blinking, check the short­cut of indoor/outdoor connecting wires.
When LED2 is lit, connect indoor/outdoor connecting wires again, and; if LED2 is blinking, outdoor units controller board is defective; if LED2 is lit, connection failure of indoor/outdoor terminal block etc. has returned to normal.
34 Remove remote controller wires and
check LED2 on indoor controller board.
When LED2 is blinking, check the
short-cut of remote controller wires.
When LED2 is lit, connect remote
controller wires again and: if LED2 is blinking, remote controller is defective; if LED2 is lit, connection failure of remote controller terminal block etc. has returned to normal.
Page 29
29
(3)Upward/downward vane
performance failure
1 The vane is not downward during defrosting and
heat preparation and when the thermostat is OFF in HEAT mode. (Working of COOLprotection function)
2 Vane motor does not rotate.
Defective vane motor
Breaking of wire or connection failure of connector
Up/down vane setting is No vanes”.
3 Upward/downward vane does not work.
The vane is set to fixed position.
1 Normal operation (The vane is set to hor-
izontal regardless of remote control.)
2 Check 2 (left).
Check the vane motor. (Refer to How to check the parts.)
Check for breaking of wire or connec­tion failure of connector.
Check Up/down vane setting. (Unit function selection by remote controller).
3 Normal operation (Each connector on
vane motor side is disconnected.)
Phenomena
Cause
Countermeasure
9-5. TEST RUN AND EMERGENCY OPERATION
9-5-1. Before test run
9-5-2. Test run (Using wired remote controller)
B
EF
C
H
G
IM
A
D
ûC
ûC
SIMPLE
PAR-21MAA
ON/OFF
FILTER
CHECK
OPERATION
CLEAR
TEST
TEMP.
MENU
BACK DAY
MONITOR/SET
CLOCK
ON/OFF
TEST RUN COOL, HEAT
A ON/OFF button B Test run display C Indoor temperature liquid line
temperature display
D ON/OFF lamp E Power display
F Error code display
Test run remaining time display
G Set temperature button H Mode selection button I Fan speed button M TEST button
1 Turn on the power at least 12 hours before the test run. 2 Press the [TEST] button twice. "TEST RUN" liquid crystal display 3 Press the [Mode selection] button. Make sure that wind is blown out. 4 Press the [Mode selection] button and switch to the cooling mode.
Make sure that cold wind is blown out.
5 Press the [Fan speed] button. Make sure that the wind speed is switched. 6 Check operation of the outdoor unit fan. 7 Release test run by pressing the [ON/OFF] button. Stop 8 Register a telephone number.
The telephone number of the repair shop, sales office, etc., to contact if an error occurs can be registered in the remote controller. The telephone number will be displayed when an error occurs. For registration procedures, refer to the operation manual for the indoor unit.
After completing installation and the wiring and piping of the indoor and outdoor units, check for refrigerant leakage, looseness in the power supply or control wiring, wrong polarity, and no disconnection of one phase in the supply.
Use a 500-volt megohmmeter to check that the resistance between the power supply terminals and ground is at least 1.0M .
Do not carry out this test on the control wiring (low voltage circuit) terminals. Warning:
Do not use the air conditioner if the insulation resistance is less than 1.0M .
Page 30
30
1.When the wired remote control or the indoor unit microcomputer has failed,but all other components work if you set the switch(SWE,SW6) on the indoor control board,the indoor unit will begin properly Emergency Operation.
2.When you activate emergency operation of the cooling, you have to set the connector(SWE) and switch(SW6)on the indoor controller.
SWE:ON Indoor fan is running high speed. SW6-1:ON Emergency operation of cooling mode.
3.Before you activate emergency operation,check the following points: (1)Emergency operation cannot be activated when:
the outdoor unit malfunctions.
the indoor fan malfunctions.
(2)Emergency operation becomes continuous only by switching the power source on/off. ON/OFF on the remote
control or temperature control etc. does not function.
(3)Emergency cooling should be limited to 10 hours maximum
(The indoor unit heat exchanger may freeze).
(4)After emergency operation has been deactivated,set the switches etc. to their original positions.
9-5-3. When wired remote controller or indoor unit micro computer troubles
Page 31
31
9-6. HOW TO CHECK THE PARTS
PE-5GAK(T) PE-6GAK(T)
0
10
20
30
40
50
-20 -10 0 10 20 30 40 50
< Thermistor for lower temperature >
Temperature (:)
Resistance (K")
<Thermistor Characteristic graph>
Room temperature thermistor(TH1) Indoor coil thermistor(TH2)
Thermistor R
0=15k' ±3%
Fixed number of B=3480 ± 2% Rt=15exp { 3480( ) }
0
:: 15k' 10:: 9.6k' 20:: 6.3k' 25:: 5.2k' 30:: 4.3k' 40:: 3.0k'
Thermistor for lower temperature
1
273+t
1
273
Parts name
Room temperature thermistor (TH1)
Disconnect the connector, then measure the resistance using a tester. (Surrounding temperature 10˚C-30˚C)
Indoor coil thermistor (TH2)
Fan motor
Brown
Red Lo 220~240V 50Hz
Hi 220~240V 50Hz
Blue Thermal protector 17AM037E5-4
Operating temperature150˚C
P
Orange
A1
M
A2
White
Measure the resistance between the terminals using a tester. (Surrounding temperature 20˚C)
Check points
Nomal Abnormal
4.3kr -9.6kr Open or short
Red-Orange 7.15
PE-5,6
Brown-White 11.71
Red-Brown 5.12
PE-5,6
(High static pressure motor)
Red-Orange 5.34
Brown-White 10.12
Red-Brown 3.35
Nomal
(Refer to the thermistor)
Abnormal
Open or short
Page 32
32
9-7. TEST POINT DIAGRAM
9-7-1. Power board PE-5GAK(T) PE-6GAK(T)
CNSK Connect to the indoor controller board (CNDK) Between
1 to 3 220-240V AC
CN2S Connect to the indoor controller board (CN2D) Between
1 to 3 12.6-13.7V DC (Pin1 (+))
Page 33
33
9-7-2. Indoor controller board PE-5GAK(T) PE-6GAK(T)
FAN Fan motor output
CNP Drain-pump output (DP) (220~240V AC)
CNC Dew prevention heater (H2) (220~240V AC)
CNDK Connect to the indoor power board (CNSK) (220~240V AC)
FUSE (6.3A 250V)
CND Power supply input (220~240V AC)
SWE Emergency operation
SW1 Model setting
CN2L Connector (LOSSNAY)
CN51 Centrally control
CN6V Vane motor output (MV)
CN90 Connect to the wire­less remote con­troller board (CNB)
CN31 Drain sensor (DS)
CN21 Pipe temperature thermistor/Liquid (TH2)
CN20 Room temperature thermistor (TH1)
CN22 Remote controller connecting wire (10.4~14.6V DC)
LED2 Power supply (R.B)
LED1 Power supply (I.B)
CN2D Connector to the indoor power board (CN2S) (12.5~13.7V DC)
}
}
+
+
SW5 System Setting
CN32 Remote Switch
CN41 Connector (HA terminal-A)
CN105/ CN92 (RED)
SW6 Emergency operation
CN30 Transmission (indoor/outdoor)
Page 34
34
9-8. FUNCTIONS OF DIP SWITCH AND JUMPER WIRE
Each function is controlled by the dip switch and the jumper wire on control p.c. board.
SW1
Setting by the dip switch and jumper wire
Functions
Jumper wire
Model settings
SW5
System settings
Remarks
(Marks in the table below) Jumper wire ( : Short : Open)
SW5-3 Main/Sub setting OFF : Main ON : Sub SW5-4 Rotaion operation setting OFF : Not avairable ON : avairable
8761
SW5
OFF
ON
5432
OFF
ON
54321
SW1
Page 35
35
10-1. UNIT FUNCTION SETTING BY THE REMOTE CONTROLLER
Each function can be set according to necessity using the remote controller. The setting of function for each unit can only be done by the remote controller. Select function available from the table 1. (1) Functions available when setting the unit number to 00 (Select 00 referring to
4 setting the indoor unit number.)
*1 The functions below are available only when the wired remote controller is used.The functions are not available for floor
standing models.
<Table 1> Function selections
(2) Functions available when setting the unit number to 01-02 or AL (07 in case of wireless remote controller)
When setting functions for an indoor unit in an independent system, set the unit number to 01 referring to
4 setting the
indoor unit number.
When setting functions for a simultaneous Twin-indoor unit system, set the unit number to 01 to 02 for each indoor unit in case of selecting different functions for each unit referring to
4 setting the indoor unit number.
When setting the same functions for an entire simultaneous Twin-indoor unit system, set refrigerant address to AL (07 in case of wireless remote controller) referring to
4 setting the indoor unit number.
10
FUNCTION SETTING
Function
Power failure automatic recovery Indoor temperature detecting
LOSSNAY connectivity
Power supply voltage Frost prevention temperature Humidifier control
Rotation
Settings
OFF ON Indoor unit's (Main) internal sensor
Remote controller's internal sensor *1 Not supported Supported (indoor unit not equipped with outdoor air intake) Supported (indoor unit equipped with outdoor air intake) 240V 220V,230V 1
Mode No.
Initial setting
(when sent from the factory)
01
02
03
04 15 16
20
Setting No.
1 2 1 2 3 1 2 3 1 2 1 2 1 2 1 2 3
Remarks
The setting is applied to all the units in the same refrigerant system.
Initial setting (Factory setting
Function Settings
Mode No.
Setting No.
- : Not available PE-GAK(T)
Filter sign 100Hr 1
2500Hr 07 2
No filter sign indicator
3 Air flow Quiet 1 ­(
Fan speed
)
Standard 08 2 ­High ceiling 3 -
No.of air outlets 4 directions 1 -
3 directions 09 2 ­2 directions
Optional high efficiency
Not supported filter Supported Vane setting
No vanes (Vane No.3 setting:PL-AAKonly Vane No.1 setting Vane No.2 setting
Energy saving air Disabled flow (Heating mode Vane differential setting No.1 setting (TH2: 24-28˚C
)
Enabled
)
in heating mode No.2 setting (Standard, TH2:28-32˚C (
cold wind prevention
)
No.3 setting (TH2: 32-38˚C
)
Swing Not available
Available
Fan speed when the
Set fan speed
cooling thermostat is OFF Stop Detection of abnormality of Available the pipe temperature (P8
)
Not available
10
)
11 2 -
12
)
14 2 -
23 27
28
3­1 2
-
-
1-
3­1 2
-
-
1-
3­1 2
-
-
1 2 1 2
)
Page 36
36
[Operating Procedure]
1 Check the setting items provided by function selection.
If settings for a mode are changed by function selection, the functions of that mode will be changed accordingly. Check all the current settings according to steps 2 to 7 , fill in the "Check" column in Table 1, and then change them as necessary. For factory settings, refer to the indoor unit's installation manual.
2 Switch off the remote controller.
A Hold down the
B ( mode 15 or more) and
buttons
simultaneously for at least two seconds.
will start to flash,
and then the remote controller's display content will change as shown below.
3 Set the outdoor address.
C Press the [
CLOCK] buttons ( and ) to select the desired
address. The address changes from "00" to "15".
* If the unit stops after
flashed for two seconds or "88" flashes in the room temperature display area for two seconds, a transmission error may have occurred.
Check to see if there are any sources of noise or interference near the transmission path. Note
If you have made operational mistakes during this procedure, exit function selection (see step 0), and then restart from step 2 .
4 Set the indoor unit number.
D Press the
button so that " - -" flashes in the unit number display
area.
C Press the [
CLOCK] buttons ( and ) to select the unit number
of the indoor unit for which you want to perform function selection. The unit number changes to "00", "01", "02","03",04" and "AL" each time a button is pressed.
* To set modes 01 to 06 or 15 to 22 select unit number "00". * To set modes 07 to 14 or 23 to 28 carry out as follows:
To set each indoor unit individually, select "01" to "04".
To set all the indoor units collectively, select "AL".
5 Confirm the address and unit number.
E Press the
button to confirm the address and unit number. After a while, "- - " will start to flash in the mode number display area.
E When the address and unit number are confirmed by pressing the
button, the corresponding indoor unit will start fan operation. This
helps you find the location of the indoor unit for which you want to perform function selection. However, if "00" or "AL" is selected as the unit number, all the indoor units corresponding to the specified address will start fan operation.
* "88" will flash in the room temperature display area if the selected address
does not exist in the system. Furthermore, if
"F"
appears and flashes in the unit number display area and the address display area also flashes, there are no units that correspond to the selected unit number. In this case, the address and unit number may be incorrect, so repeat steps 2 and 3 to set the correct ones.
* When grouping different systems, if an indoor unit other than the
one to which the address has been set performs fan operation, there may be another address that is the same as the specified one. In this case, check the DIP switch of the outdoor unit to see whether such a address exists.
6 Select the mode number.
F Press the [
TEMP] buttons ( and ) to set the desired mode
number. (Only the selectable mode numbers can be selected.)
7 Select the setting content for the selected mode.
G Press the
button. The currently selected setting number will
flash, so check the currently set content.
F Press the [
TEMP] buttons ( and ) to select the desired setting
number.
8 Register the settings you have made in steps 3 to 7 .
E Press the
button. The mode number and setting number will start
to flash and registration starts.
The mode number and setting number will stop flashing and remain lit, indicating the end of registration.
* If " - - - " is displayed for both the mode number and setting number and "
" flashes in the room temperature display area, a transmission error may have occurred.
Check to see if there are any sources of noise or interference near the transmission path. 9 If you wish to continue to select other functions, repeat steps 3 to 8 . 0 Complete function selection.
A Hold down the
buttons simultaneously for at least two seconds.
After a while, the function selection screen will disappear and the air condi­tioner OFF screen will reappear.
* Do not operate the remote controller for at least 30 seconds after completing
function selection. (No operations will be accepted even if they are made.)
Note If a function of an indoor unit is changed by function selection after installation is complete, make sure that a " " mark, etc., is given in the "Check" column of Table 1 to indicate the change.
Unit number display section
Mode number display section
00 address
Indoor unit
Fan draft
Remote controller
Main Sub
Outdoor unit
Designate operation
Example) When the address is set to 01 and the unit number is 02.
Mode number display section
Mode number 02 = Indoor temperature detection
Setting number display section
Setting number 3 = Remote controller built-in sensor
Setting number 1 = Indoor unit operating average
( mode 15 or more) and
FILTER
Address display section
FUNCTION SELECTION
FUNCTION SELECTION
TEST
ON/OFF
MODE
MODE
MENU
MODE
FILTER TEST
Page 37
37
10-2. FUNCTION SELECTION OF REMOTE CONTROLLER
The setting of the following remote controller functions can be changed using the remote controller function selection mode. Change the setting when needed.
Item 1
1.Change Language ("CHANGE LANGUAGE")
2.Function limit ("FUNCTION SELECTION")
3.Mode selection ("MODE SELECTION")
4.Display change ("DISP MODE SETTING")
Item 3 (Setting content)
Display in multiple languages is possible.
Setting the range of operation limit (operation lock)
Setting the use or non-use of "automatic" operation mode
Setting the temperature adjustable range (maximum, minimum)
Selecting main or sub remote controller
*
When two remote controllers are connected to one group, one controller must be set to sub.
Setting the use or non-use of clock function
Setting the timer type
Contact number display in case of error
Setting the telephone number
Setting the temperature unit (: or °F) to display
Setting the use or non-use of the display of indoor (suction) air temperature
Setting the use or non-use of the display of "Cooling" or "Heating" display during
operation with automatic mode
Item 2
Language setting to display
(1)
Operation function limit setting (operation lock) ("LOCKING FUNCTION")
(2)
Use of automatic mode setting ("SELECT AUTO MODE")
(3)
Temperature range limit setting ("LIMIT TEMP FUNCTION")
(1)
Remote controller main/sub setting ("CONTROLLER MAIN/SUB")
(2) Use of clock setting ("CLOCK") (3) Timer function setting ("WEEKLY TIMER") (4) Contact number setting for error situation ("CALL.")
(1) Temperature display :/°F setting ("TEMP MODE :/°F") (2)
Suction air temperature display setting ("ROOM TEMP DISP SELECT")
(3)
Automatic cooling/heating display setting ("AUTO MODE DISP C/H")
[Function selection flowchart] Refer to next page. [1] Stop the air conditioner to start remote controller function selection mode. [2] Select from item1. [3] Select from item2. [4] Make the setting. (Details are specified in item3) [5] Setting completed. [6] Change the display to the normal one. (End)
➔➔
[Detailed setting] [4] -1. CHANGE LANGUAGE setting
The language that appears on the dot display can be selected.
Press the [
MENU] button to change the language.
1 Japanese (JP), 2 English (GB), 3 German (D), 4 Spanish (E), 5 Russian (RU), 6 Italian (I), 7 Chinese (CH),8 French (F)
[4] -2. Function limit (1) Operation function limit setting (operation lock)
To switch the setting, press the [ ON/OFF] button. 1 no1: Operation lock setting is made on all buttons other than
the [
ON/OFF] button.
2 no2: Operation lock setting is made on all buttons. 3 OFF (Initial setting value) : Operation lock setting is not made
* To make the operation lock setting valid on the normal screen, it is
necessary to press buttons (Press and hold down the [FILTER] and [ ON/OFF] buttons at the same time for two seconds.) on the normal screen after the above setting is made..
(2) Use of automatic mode setting When the remote controller is connected to the unit that has auto­matic operation mode, the following settings can be made.
To switch the setting, press the [ ON/OFF] button. 1 ON (Initial setting value) : The automatic mode is displayed when
the operation mode is selected.
2 OFF : The automatic mode is not display
when the operation mode is selected.
[4] -3. Mode selection setting (1) Remote controller main/sub setting
To switch the setting, press the [ ON/OFF] button.
1 Main : The controller will be the main controller. 2 Sub : The controller will be the sub controller.
(2) Use of clock setting
To switch the setting, press the [ ON/OFF] button.
1 ON : The clock function can be used. 2 OFF:The clock function cannot be used.
(3) Timer function setting
To switch the setting, press the [ ON/OFF] button (Choose one of the followings.).
1 WEEKLY TIMER (initial setting on MA deluxe):
The weekly timer can be used.
2 AUTO OFF TIMER: The auto off timer can be used.
SIMPLE TIMER (Default setting on MA smooth):
The simple timer can be used.
4
3
TIMER MODE OFF: The timer mode cannot be used.
* When the use of clock setting is OFF , the "WEEKLY TIMER" cannot be
used.
(4) Contact number setting for error situation
To switch the setting, press the [ ON/OFF] button.
1 CALL OFF:
The set contact numbers are not displayed in case of error.
2 CALL **** *** **** : The set contact numbers are displayed in case
of error.
(3) Temperature range limit setting After this setting is made, the temperature can be changed within the set range.
To switch the setting, press the [ ON/OFF] button. 1 LIMIT TEMP COOL MODE :
The temperature range can be changed on cooling/dry mode.
2 LIMIT TEMP HEAT MODE :
The temperature range can be changed on heating mode.
3 LIMIT TEMP AUTO MODE :
The temperature range can be changed on automatic mode. 4 OFF (initial setting) : The temperature range limit is not active. *
When the setting, other than OFF, is made, the temperature range limit setting on cooling, heating and automatic mode is made at the same time. However the range cannot be limited when the set temperature range has not changed.
To increase or decrease the temperature, press the [ TEMP ( ) or ( )] button.
To switch the upper limit setting and the lower limit setting, press the
[ ]
button. The selected setting will flash and the temperature can be set.
Settable range
Cooling/Dry mode : Lower limit: 19 : ~ 30: Upper limit: 30 : ~ 19:
Heating mode : Lower limit: 17 : ~ 28: Upper limit: 28 : ~ 17:
Automatic mode : Lower limit: 19 : ~ 28: Upper limit: 28 : ~ 19:
CALL_ : The contact number can be set when the display is as
shown on the left.
Setting the contact numbers To set the contact numbers, follow the following procedures. Move the flashing cursor to set numbers. Press the [
TEMP. ( ) and ( )] button to move the cursor to the right (left). Press the [ CLOCK (
) and ( )] button to set the numbers.
[4] -4. Display change setting (1) Temperature display :/ F setting
To switch the setting, press the [ ON/OFF] button.
1 : : The temperature unit : is used. 2 F: The temperature unit
°
°°
F is used.
(2) Suction air temperature display setting
To switch the setting, press the [ ON/OFF] button.
1 ON : The suction air temperature is displayed. 2 OFF:The suction air temperature is not displayed.
(3) Automatic cooling/heating display setting
To switch the setting, press the [ ON/OFF] button. 1 ON : One of "A utomatic cooling" and "A utomatic heating" is displa yed
under the automatic mode is running.
2 OFF:Only "Automatic" is displayed under the automatic mode.
Page 38
38
Hold down the E button and press the D button for 2 seconds.
Hold down the E button and press the D button for 2 seconds.
Remote controller function selection mode
E Press the operation mode button. G Press the TIMER MENU button. D Press the TIMER ON/OFF button.
Item1 Item2
Dot display
Item3
Room air temperature is not displayed.
One of "Automatic cooling" and "Automatic heating" is displayed under the automatic mode is running. (Initial setting value)
Only "Automatic" is displayed under the automatic mode.
Normal display (Display when the air condition is not running)
Change Language
Function selection
Mode selection
Display mode setting
Operation lock setting is not used. (Initial setting value)
Operation lock setting is except On/Off buttons.
Operation lock setting is All buttons.
The automatic mode is displayed when the operation mode is selected. (Initial setting value)
The automatic mode is not displayed when the operation mode is selected.
The temperature range limit is not active. (Initial setting value)
The temperature range can be changed on cooling/dry mode.
The temperature range can be changed on heating mode.
The temperature range can be changed on automatic mode.
The remote controller will be the main controller. (Initial setting value)
The remote controller will be the sub controller.
The clock function can be used. (Initial setting value)
The clock function can not be used.
Weekly timer can be used. (Initial setting value)
Auto off timer can be used.
Simple timer can be used.
Timer mode can not be used.
The set contact numbers are not displayed in case of error. (Initial setting value)
The set contact numbers are displayed in case of error.
The temperature unit
:
is used. (Initial setting value)
The temperature unit °F is used.
Room air temperature is displayed. (Initial setting value)
Flowchart of Function Setting
Setting language (English)
E
E
G
EN
GE
ES
RU
G
IT
ZH
FR
F
TEMP.
MENU
E
PAR-21MAA
G
MONITOR/SET
BACK DAY
CLOCK
ON/OFF
C
OPERATION
D
ON/OFF
FILTER
CHECK
CLEAR
I A
TEST
B
H
JA
D
OFF
D
on1
D
D
D
D
D
D
on2
ON
D
OFF
OFF
D
G
G
E
G
G
G
D
G
D
D
E
G
D
D
G
G
D
D
D
G
G
D
D
D
G
G
D
D
D
ON
D
OFF
D
OFF
D
CALL-
:
D
°F
ON
D
OFF
ON
D
OFF
Page 39
39
11 SYSTEM CONTROL
11-1. VARIETY OF SYSTEM CONTROL FUNCTIONS
System Name System Diagram Features
A.Remote control-
ler operation
Use of two con­trollers enables operation of the air conditioner both from a distance and nearby.
B.Group control
operation
Use of one remote controller to con­trol multiple air conditioners with the same settings simultaneously.
Indoor unit
Remote Controller
* One of the wired remote con-
trollers must be set as a sub remote controller.
Inter face Indoor
unit Outdoor
Remote Controller
unit
Up to two remote controllers can be connected to one group.
Operation control by the latest command (last en­tered priority)
Wired remote controllers can be combined as a pair.
One group can consist of up to 16 indoor units, and they can be started sequentially by connecting the remote controller to them and assigning an address to each inter face.
All the units belonging to the same group are oper­ated in the same mode, but thermostats can be turned ON/OFF individually for each indoor unit.
Up to two remote controllers can be connected.
Parts Required in Addition to Standard System
Components (Indoor/Outdoor Units, Remote Controller)
Wired remote controller (addi­tional) (PAR-21MAA)
Inter face MAC-397IF-E
Page 40
40
System Nam
e
m
es
y
m
)
n
l
.
y
,
/
-
-
.
:
e
.
e
.
e
n
).
t
f
.
s
.
o
ed.
er
(
)
C. Timer operatio
Enables contro of start and stop
For control b external timer refer to Remote handheld com bined control op eration"
System Diagra
Featur
Weekly timer In addition to ON/OFF, up to eight temperatur patterns can be set for each day of the week Only one timer can be selected; the auto off, simpl and weekly timers cannot be combined Simple timer: Start and stop operations can each b
performed once within 72 hours (ca be set in 1-hour increments
Auto off timer:Operation is stopped when the prese
time elapses following the start o operation The time can be set from 30 minute
to 4 hours in 30-minute increments Only one timer can be selected; the simple and aut off timers cannot be combin
Parts Required in Addition to Standard S
Components (Indoor/Outdoor Units, Remote Controller
MA Remote controll
PAR-21MAA
ste
Page 41
41
11-2. ONE REMOTE CONTROLLER (STANDARD) OPERATION
(1) One Wired Remote Controller
(OC: Outdoor unit IC: Indoor unit R: Remote controller (for wireless type: optical receiver adapter)
(Reference)
Electrical wiring diagram
OC IC
1 2
LN
Power source wiring
1 2
1 2
1 2
R
(No polarity)
Outdoor unit Indoor unit Remote controller
Power source wiring
(Polarity)
Power supply terminal block L, N
Indoor/outdoor connection cable terminal
block 1,2 (Polarity)
Remote controller cable terminal block 1,2 (No polarity)
11-3. TWO-REMOTE CONTROLLER OPERATION
(1) Two Wired Remote Controllers
(Reference)
Set one of the remote controllers as the main controller (factory setting) and the other as the sub controller using the remote controller's function selection.
Slim Air Conditioners System
Remote controller connection circuit (Controller cable)
Outdoor unit OC
Indoor unit IC
Wired remote controller R
Standard 1:1
Indoor/Outdoor connection cable
Remote controller cable
OC
IC-1
R
2
2
(R: Wired remote controller)
Slim Air Conditioner System
Outdoor unit OC
Indoor unit IC
Remote controller connection circuit (Controller cable)
Wired remote controller R
Outdoor unit OC
Indoor unit IC
Wired remote controller R
Standard 1:1
Indoor/outdoor connection cable
Remote controller cable
OC
2
IC
2
R-1 R-2
OC
IC
R-1
2
2
2
R-2
2
Page 42
42
Indoor control board
CN105
or
CN92
2.Connecting the remote control interface with each system
(For details on each system, see the relevant instruction manual.)
Replace the interface unit mounting cord clamp with a supplied mounting cord clamp based on the thickness of the connecting cable used for each system.
The cables connected to the Indoor unit should be mounted on or near the Indoor unit. If the connecting cable is not securely mounted, the connector may detach, break, or malfunction.
Set the interface dip switch (SW500502) settings before turning on the power.
If the interface dip switch (SW500502) settings are not set correctly, the system will not function properly.
Connecting cable for each system
Mounting screws 4 o 16
Electrical wire mounting bracket
Mounting cord clamp
Mounting screws 4 o 10
Mounting cord clamp
Connect the connecting cable that comes with the interface unit to the connector CN105 or CN92 on the indoor control board.
INDOOR
Mounting screws (black) 3.5 o 12
Interface unit mounting cord clamp or mounting cord clamps
11-4. GROUP CONTROL OPERATION
(COLLECTIVE OPERATION AND CONTROL OF MULTIPLE REFRIGERANT SYSTEMS (2 to 16))
Group control can be operated by using MAC-397IF-E.
The setting of wired remote controller is subjected to variation according to the function of the indoor unit. (for mode operation, setting temperature, fan step, air direction) The display of remote controller and operating the indoor unit might be different.
Neither the test run nor the function setting can be done by MA remote controller connected with MAC-397IF-E.
1.Connecting the MA& CONTACT TERMINAL Interface to the Indoor Unit
Connect the interface unit and the indoor control board using the connecting cable that came with the interface.
Extending or shortening the connecting cable that comes out of the interface may cause it to malfunction. Also,
keep the connecting cable as far as possible away from the electrical wires and ground wire. Do not bundle them together.
Page 43
43
Use as a Wired Remote Control (Using the MA Remote Controller)
Note:
1.Be sure the Auto Heating/Cooling Display Setting on the MA remote controller is set to OFF before use.
•For information on how to set the Auto/Heating Cooling Display Setting, see the MA remote controller instruction manual.
•The actual operating status of the unit may differ from what is shown on the remote controller display
2.A test run cannot be initiated using the test run switch on the MA remote controller..
3.The horizontal vanes on the unit cannot be operated using the louver switch.
The range of room temperature indication is between 10 and 38 .
4.
Indoor unit
Interface unit
CN560
TB580 1 2 A B
Remote control cord that came with the MA remote controller (Non polarity)
2
MA remote controller (PAR-21MAA)
PAR-20MAA cannot be used
*
with this interface.
Dip switch settings
SW500 does not have to be set. SW501:
SW501- No. 1-4: Refrigerant address
Set this switch when multiple indoor units (and remote control interfaces) are connected to a single MA remote controller. Always start the refrigerant address at "0". Even when connecting multiple outdoor units, set a different refrigerant address for each indoor unit.
Refrigerant address
0
1
2
15
1
3
4
Refrigerant address "0"
5
21
3
3
44
Refrigerant address "1"
Outdoor unit Outdoor unit Indoor unit Interface MA remote controller
Refrigerant address "2"
ON
1 2 34
ON
2 3 4
1
ON
1 2 34
ON
2 34
1
SW501- No. 5–6
ON
No. 5 should normally be set to OFF. Under the following conditions, No.6 should normally be set to ON.
5 6
When the model of Mr. SLIM exists in the same group, it sets it to turning ON.
Set them to ON only when using the room temperature sensor installed in the MA remote controller. * This can be switched when an accurate room temperature cannot be detected by the air conditioner unit. PE-GAK(T) series do not have a room temperature sensor on their MA remote controllers.
Page 44
44
SW501: Settings to accommodate MA remote controller and settings to accommodate outdoor units
SW No.
No. 1 No. 2 No. 3 No. 4
Functions OFF ON Comments
Only specify these settings when connecting an MA remote controller.
Functions Room temperature detector The model of Mr. SLIM exists in the
same group.
This should normally be set to ON.
ON
1
2 3 4 5 6
ON
1 2 3 4 5 6
ON
1
2 3 4 5 6
ON
1
2 3 4 5 6
ON
1 2 3 4 5 6
ON
1
2 3 4 5 6
ON
1
2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1
2 3 4 5 6
ON
1
2 3 4 5 6
ON
1
2 3 4 5 6
ON
1
2 3 4 5 6
ON
1
2 3 4 5 6
ON
1 2 3 4 5 6
ON
1
2 3 4 5 6
Refrigerant address 0
Refrigerant address 1
Refrigerant address 2
Refrigerant address 3
Refrigerant address 4
Refrigerant address 5
Refrigerant address 6
Refrigerant address 7
Refrigerant address 8
Refrigerant address 9
Refrigerant address 10
Refrigerant address 11
Refrigerant address 12
Refrigerant address 13
Refrigerant address 14
Refrigerant address 15
OFF Indoor unit Not mixed
ON Remote control Mixed
Comments
This should normally be set to OFF.
SW No.
No. 5 No. 6
Page 45
45
SW502 : Air Conditioner Function Settings
Interface unit
Wall mounting brackets
Mounting screws
Mounting screws
Mounting screws
Cord clamp for wiring
SW No.
Cooling only type/ Heat pump type
No. 1
No. 2
Auto mode
No. 3
No. 4
Fan speed
No. 5
Vane
No. 6
Swing
No. 7
Not in use
No. 8
Fan mode
* Fan speed 2 step model : An actual fan speed is 2 step though the display of remote controller becomes 4 step or 3 step.
Functions
OFF
Heat pump type
Not available
(setting No.3 disabled)
Available
(unit)
4 speeds
Available
Available
Not available
ON
Cooling only type
Available
(setting No.3 enabled)
Available
(remote controller)
3 speeds (1-speed and
2-speed models
set ON)
Not available
Not available
Available
Set the mode in accordance with the operation manual for the indoor unit.
Heat pump type : Set to ON. Cooling only type : Set to OFF.
Set to OFF. When operating 2-speed model with the 3-speed
setting (ON), the MA remote controller display will indicate 3 fan speeds. The table below shows the displays and the actual outputs at that time.
Display Meaning Indoor unit output
Medium speed High speed
The Vane function of either of indoor unit : When the function is provided, it is Available (OFF). When the function is not provided, it is Not available (ON).
The Swing function of either of indoor unit : When the function is provided, it is Available (OFF). When the function is not provided, it is Not available (ON).
Permanently set to OFF.
Set to ON.
Comments
High speed
Low speedLow speed
High speed
3. Test Run (Check Operations)
Interface status monitor
You can check the status of the interface by the LED lamp on the interface unit board.
LED lamp no.
LED521
LED522
LED523
Lamp off
DC 12 V is not being supplied from the air conditioner.
Device is not communicating properly with the air conditioner.
Device is not communicating properly with the MA remote controller.
Lamp on
DC 12 V is being supplied from the air conditioner.
Blinking at approx. 1 second intervals: Device is communicating normally with the air conditioner.
Blinking at approx. 8 second intervals: Device is com­municating normally with the MA remote controller.
Blinking
* Use the table above to check the device operations.
4. Mounting the Remote Control Interface Unit
The Interface unit should be placed in a location where the connecting cable from the interface can reach an indoor unit. The device will not function properly if the connecting cable is extended so the connecting cable should not be extended. Mount the interface unit securely to a pillar or wall using 2 or more screws.
When Using Wall Mounting Brackets
2
1
Attach the wall mounting brackets to the interface unit using 2 mounting screws.
Mount the unit to a pillar or wall using 2 mounting screws.
Page 46
46
When Mounting Directly to a Wall
Mount the interface unit case to the wall using the mounting screws.
Interface case mounting screws
Mounting screws
When mounting the interface unit inside a ceiling or wall, install an access door to facilitate mainte­nance.
When the interface unit is mounted above an indoor unit, it should be positioned 40 mm or more away from the unit to ensure that ceiling grills can be removed.
40 mm or more
Attach the interface unit connecting cable here. Store extra connecting cable in the ductwork space behind the indoor unit.
* If there is any slack in the connecting cable, use a
fastener to keep it in place.
* When mounting the interface unit using a cushioning
material , be sure to mount it in a location where it will not fall.
Interface unit
Cushioning material
Page 47
47
11-5. POWER OUTAGE AUTOMATIC RECOVERY OPERATION
Whenever a power outage or switching of the power supply causes the power supply of an operating air conditioner to go from OFF to ON, this function will automatically restore the operation of the air conditioner to its previous operating mode. w If the power is turned from OFF to ON when the air conditioner is not in operation, the air conditioner will not automatically
be turned on. However, the timer operation will be cancelled if the air conditioner is in timer operation (including when the unit is waiting for its start time). Setting for timer operation must be performed once again.
If there is a momentary power outage of less than one second while the air conditioner is in operation, there may not be a clear determination of whether or not there was a power failure. When it has been determined that there has been a power failure, recovery will take approximately four minutes after the power is restored. Please wait. (Once "PLEASE WAIT" has appeared on the display, a protection system will operate to prevent the unit from restarting for three minutes.)
When it has been determined that there has been no power failure, operation will continue as is.
Settings can be made by function selections from the remote controller.
When there is group control, selection of all refrigerants is required.
11-6. INDIVIDUAL CONTROL OPERATION FROM A SEPARATE ROOM
By simply centralizing the remote controllers installed in each room in a separate control room, individual control or central­ized monitoring of the air conditioners in each room can be attained.
Air conditioner control can be performed up to a total of 500 meters away by connecting the indoor units and remote con­trollers with 0.3 to 1.25 mm
2
2-core cable.
If a remote controller is installed in a room and control room, refer to the section on operating with two remote controllers.
Indoor unit Indoor unit Indoor unit
Remote controller
Control room room 1 room 2 room 3
11-7. TIMER OPERATION
Timer operation can be performed by setting the wired timer. Start and stop times can be set in 10-minute increments within
a 24-hour period.
When used in combination with the central control remote controller of the M-NET control system for the outdoor unit, one
program timer can be used for individual timer settings for each group of the central control system. (Each timer setting can be stored in data memory so timer settings for up to 50 groups can be set individually.)
* Please refer to the MELANS catalog or technical information for details about the central control remote controller.
Page 48
48
SERVICE DATA (PARTS NAME)
12
Indoor unit
11
External parts
• PE-5,6GAK(T)
Drain pan
Drain pipe connection (R1)
Control box
Fan motor
Sirocco fan
Suspension bracket
Special washer
Drain pan
Heat exchanger
Liquid pipe
Gas pipe
Inlet thermistor (TH1)
Liquid pipe thermistor (TH2)
Strainer
Page 49
49
22
Control box parts
• PE-5,6GAK(T)
Magnetic contactor (Fan motor)
Capacitor
Power supply board
Ferrite core
Control board
Terminal block for remote controller
Terminal block for outdoor/indoor control wiring connection
Power supply terminal block
TB5
2121
52F
TB4
51F
TB2
L1 L3 NL2
A
FB
I/D POWER BOARD
I/D
CAPACITOR
X1Lo X2Hi
CONTROLLER BOARD
SNB board
Relay
view A
Page 50
50
OPTIONAL PARTS
13
Individual order numberItem
MAC-397IF-E
Group control operation
M-NET operation
1 2
MAC-399IF-E
Page 51
Page 52
HEAD OFFICE : TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU TOKYO 100-8310, JAPAN
CCopyright 2007 MITSUBISHI ELECTRIC ENGINEERING CO., LTD. Distributed in August 2007 No.HWE07050 PDF 5 Printed in Japan.
New publication, effective August 2007. Specifications subject to change without notice.
TM
Loading...