Mitsubishi PE-3EJA2.TH, PE-3EJA3.TH, PE-4EJSA2.TH, PE-5EJSA2.TH, PE-6EJSA2.TH Service Manual

SPLIT-TYPE, AIR CONDITIONERS
MITSUBISHI ELECTRIC
12 11 10
9 8 7 6 5 4 3 2 1
29 28 27 26 25 24 23 22 21 20 19 18
TIMER TEMP
TIMER/TEMP.
UP
DOWN
POWER
COOL
ON/OFF
MODE
SELECT
FAN
SPEED
TIMER
MODE
DRY FAN
HIGH LOW
AUTO STOP
START
TECHNICAL & SERVICE MANUAL
No. OC155
REVISED EDITION-B
Series PE
Ceiling Concealed
<Indoor unit> [Model names] [Service Ref.]
PE-3EJA PE-3EJA
PE-3EJA
PE-4EJSA PE-4EJSA PE-5EJSA PE-5EJSA PE-6EJSA PE-6EJSA
2
.TH
3
.TH
2 2 2
.TH .TH .TH
CONTENTS
PE-3EJA3.TH added in EDITION-B Please destroy
.
OC155 REVISED
REVISED
EDITION-A. This manual does not cover the following outdoor units. When servicing them, please refer to the following service manual and this manual in a set. [Service Ref.] OC152 REVISED EDITION-A
PU-3VJA1.TH, 3YJA1.TH PU-4VLJSA1.TH, 4YJSA1.TH PU-5YJSA.TH PU-6YJSA.TH
OC127 REVISED EDITION-A
PU-3NJA PU-4TJSA
1
2
OC199
PU-5TJSA PU-6TJSA
1 1
OC206
PU-3VJC.TH, 3YJC.TH
Indoor unit
Remote controller
1. COMBINA TION OF AND OUTDOOR UNIT···3
2. TECHNICAL CHANGE ···························3
3. PART NAMES AND FUNCTIONS··········3
4. SPECIFICATIONS ··································5
5. DATA·······················································9
7. WIRING DIAGRAM·······························24
8.
REFRIGERANT SYSTEM DIAGRAM
········25
9. OPERATION FLOW-CHART················27
10. MICROPROCESSOR CONTROL ········30
11. TROUBLE SHOOTING·························36
12. DISASSEMBLY PROCEDURE·············39
13. PARTS LIST··········································41
14. OPTIONAL PARTS ·······························45
1
Air intake duct flange
Air outlet duct flange
Air outlet
Air intake (sucks the air inside the room into the unit)
Change points PE-3EJA2.TH PE-3EJA3.TH
COOLING
CAPACITY
24,600 Btu/h
7,200 W
PU-3VJA
1.TH
PU-3YJA
1.TH
2.2kW(PU-3YJA
1.TH) 2.4kW(PU-3YJC.TH)
25,600 Btu/h
7,500 W
PU-3VJC.TH PU-3YJC.TH
OUTDOOR
UNIT
COMPRESSOR
OUTPUT
Change points
Service Ref. PE-3EJA
2.TH.
PE-3EJA
3.TH.
PE-4EJSA
2.TH.
PE-5EJSA
2.TH.
PE-6EJSA
2.TH.
VJA1.TH
— — — —
YJA1.TH
— — — —
NJA
1
— — —
VLJSA1.TH
— —
— —
YJSA1.TH
— —
— —
TJSA
2
— —
— —
YJSA.TH
— — —
TJSA
1
— — —
YJSA.TH
— — — —
TJSA
1
— — — —
VJC.TH
— — —
YJC.TH
— — —
345
Outdoor unit
6
COMBINATION OF INDOOR AND OUTDOOR UNITS
2
TECHNICAL CHANGE
Differences with PE-3EJA2.TH / PU-3VJA1.TH, PU-3YJA1.TH (OC155 REVISED EDITION-A)
3
PART NAMES AND FUNCTIONS
Indoor (Main) Unit
3
Remote controller
MITSUBISHI ELECTRIC
12 11 10
9 8 7 6 5 4 3 2 1
29 28 27 26 25 24 23 22 21 20 19 18
TIMER TEMP
TIMER/TEMP.
UP
DOWN
POWER
COOL
ON/OFF
MODE
SELECT
FAN
SPEED
TIMER MODE
DRY FAN
HIGH LOW
AUTO STOP
START
Settings remain in effect until changed. Air conditioner can be operated by simply pushing ON /OFF button once settings have been made.
Display Panel Operating Panel
TIMER / TEMP.
This button is used to change between display of room temperature and dis­play of remaining timer dur-
ON / OFF button
Pushing button starts oper­ation. Pushing again stops operation. Green lamp remains lit during operation
ing "AUTO STOP" opera­tion. Green lamps light in selected display mode.
MODE SELECT button
This button is used to
Lamps display remain­ing timer time or room temperature.
Remaining timer time
change between cooling, ventilation and DRY opera­tion modes. One of three green lamps lights to indi­cate mode in effect.
display
Lamps indicate time remaining until timer stops timed operation. Green lamps corresponding to remaining number of hours light.
Room Temperature
FAN SPEED button
This button is used to change between low and high fan speeds. One of two green lamps lights to indicate fan speed in effect.
display
Lamps display temperature settings and actual room temperatures.
Temperature settings; Green lamps light.
Temperature in room; Green lamps flash.
(Example display readings are for explanations only ; actual display readings will differ.)
Attention :
Pushing UP and Down buttons together for more than two seconds will initiate "trial run" or "inspection" mode. Avoid pushing these buttons simultaneously during normal operation. Push ON / OFF button to cancel trial run or inspection mode if initiat­ed by accident.
All green lamps turn off when air conditioner is stopped.
Avoid operation of buttons with fingernails or other sharp objects. Sharp objects may scratch operating panel.
UP and DOWN buttons
Temperature control (While "TEMP" green lamps is lit.) Use UP and DOWN buttons to set desired temperature between 18 and 29°C.
Timed operation (While green "TIMER" lamp is lit.) Use UP and DOWN buttons to set timed operation between one and twelve hours.
TIMER MODE button
Used for selecting timed starting or stopping. Green lamps lights to indicate timer mode selected.
4
SPECIFICATIONS4
W
Btu/h
W
Btu/h
W
Btu/h
kW
kW
m
3
/min
CFM
m
3
/min
CFM Pa (mmAq) Pa (mmAq)
dB dB
in. mm (in.) mm (in.) mm (in.)
kg (lbs)
kW
W
kW
m
3
/min(CFM)
m
3
/min(CFM)
dB mm (in.) mm (in.) mm (in.)
kg (lbs)
PE-3EJA
2.TH
7,200
24,600
8,100
27,600
6,700
23,000
3.41 / 3.76
PE-3EJA
2.TH
0.2
19 - 22
671 - 777
22 - 26
777 - 918
49 (5) 69 (7)
46 - 48 48 - 50
R1
785 (31) 690 (27-1/6) 428 (16-7/8)
46 (101)
W7 PU-3JA type
2.2
32 / 38
0.085 50 (1,765) 50 (1,765)
52 / 53
870 (34-1/4)
850 (33-7/16)
73 (161)
PE-4EJSA
2.TH
9,800 33,400 10,900 37,200
9,400 32,000
3.59 / 4.69
PE-4EJSA
2.TH
0.3
27 - 34
953 - 1,200
27 - 34
953 - 1,200
62 (6.35) 62 (6.35)
54 - 58 54 - 58
R1
1,055 (41-1/2)
690 (27-1/6) 428 (16-7/8)
58 (128)
W7 PU-4JSA type
2.7
32 / 38
0.065 + 0.065 95 (3,352) 95 (3,352)
54 / 55
870 (34-1/4)
1,258 (49-1/2)
94 (207)
50Hz
60Hz
60Hz
50Hz 60Hz
50Hz 60Hz
W
D H
50/60Hz
50Hz 60Hz
50/60Hz
W
D H
Service Ref.
External finish Fan motor output
Airflow Lo - High
Ex. static pressure at Hi - notch Operation control & thermostat
Noise level Low - High W5 Unit drain thread
Dimensions
Weight
Service Ref.
External finish Refrigerant (R-22) control Compressor output Protection devices Crankcase heater W4 Fan motor output
Airflow Noise level W5
Dimensions
Weight
Galvanized sheets
Remote controller & built-in
Munsell 5Y 7/1
Capillary tube
W6
295 + 24 (11-5/8 add 1)
Cooling capacity W1
Cooling capacity W2 Total input (50/60Hz) W3
OUTDOOR UNIT INDOOR UNIT
Service Ref.
Item
50Hz
60Hz
1. STANDARD SPECIFICATIONS
NOTE : W1 Rating conditions (JIS B 8616)
Indoor : D.B. 27°C (80°F), W.B.19°C (86°F) Outdoor : D.B. 35°C (95°F), W.B. 24°C (75°F)
NOTE : W2 Rating conditions (SSA 385, 386)
Indoor : D.B. 29°C (84°F), W.B.19°C (86°F) Outdoor : D.B. 46°C (115°F), W.B. 24°C (75°F)
NOTE : W3 Total input based on indicated voltage.
Service Ref.
50Hz 60Hz
Rating conditions (JIS B 8616) NOTE : W4 Capacity of crankcase heater (W) based on 220 volts. NOTE : W5 Noise level is measured in an unacoustic room based on JIS conditions. NOTE : W6 V , N ···Inner thermostat, HP switch, LP switch
VL ···Inner thermostat, HP switch, LP switch, thermal switch. T, Y···Thermal switch, Reversed - phase protector, HP switch, LPswitch
NOTE : W7 PU-3JA type···PU-3VJA
PU-4JSA type···PU-4VLJSA1.TH, 4YJSA1.TH, 4TJSA2
PE-3EJA
1ph 220V / 1ph 220V 1ph 220V / 1ph 220V 1ph 220V / 3ph 220V
2.TH
PE-4EJSA2.TH
1ph 220V / 3ph 380V
(Indoor / Outdoor)
1.TH, 3YJA1.TH, 3NJA1
5
Item
Cooling capacity W1
Cooling capacity W2 Total input (50/60Hz) W3
Service Ref.
External finish Fan motor output
Airflow Lo - High
Ex. static pressure at Hi - notch Operation control & thermostat
Noise level Low - High W5 Unit drain thread
Dimensions
Weight
Service Ref.
External finish Refrigerant (R-22) control Compressor output Protection devices Crankcase heater Fan motor output
Airflow
OUTDOOR UNIT INDOOR UNIT
Noise level W5
Dimensions
Weight
50Hz
60Hz
60Hz
50Hz 60Hz
50Hz 60Hz
50Hz 60Hz
W
D H
50/60Hz
50Hz 60Hz
50/60Hz
W
D H
Service Ref.
W
Btu/h
W
Btu/h
W
Btu/h
kW
kW
3
m
/min
CFM
3
m
/min
CFM Pa (mmAq) Pa (mmAq)
dB dB
in. mm (in.) mm (in.) mm (in.)
kg (lbs)
kW
W
kW
3
m
/min(CFM)
3
m
/min(CFM)
dB mm (in.) mm (in.) mm (in.)
kg (lbs)
PE-5EJSA
2.TH
12,100 41,300 13,500 46,100 11,000 37,500
5.10 / 6.06
PE-5EJSA
2.TH
0.4
34 - 42
1,200 - 1,482
34 - 42
1,200 - 1,482
62 (6.35) 62 (6.35)
Remote controller & built-in 54 - 58 54 - 58
R1
1,255 (49-7/16)
690 (27-1/6) 428 (16-7/8)
72 (159)
PU-5YJSA.TH, 5TJSA
3.5 W6
0.10 + 0.10 100(3,530) 100(3,530)
55 / 55
970 (38-3/16)
345 + 24 (13-9/16 add 1)
1,258 (49-1/2)
114 (282)
Galvanized sheets
1
Munsell 5Y 7/1
Capillary tube
PE-6EJSA
2.TH
14,000 47,800 15,200 51,900 13,400 45,700
5.65 / 6.58
PE-6EJSA
2.TH
0.4
34 - 42
1,200 - 1,482
34 - 42
1,200 - 1,482
62 (6.35) 62 (6.35)
54 - 58 54 - 58
R1
1,255 (49-7/16)
690 (27-1/6) 428 (16-7/8)
72 (159)
PU-6YJSA.TH, 6TJSA
4.2/4.0 W6
0.10 + 0.10 100(3,530) 100(3,530)
56/56
970 (38-3/16)
1,258 (49-1/2)
117 (313)
1
NOTE : W1 Rating conditions (JIS B 8616)
NOTE : W2 Rating conditions (SSA 385, 386)
NOTE : W3 Total input based on indicated voltage.
Indoor : D.B. 27°C (80°F), W.B. 19°C (86°F) Outdoor : D.B. 35°C (95°F), W.B. 24°C (75°F)
Indoor : D.B. 29°C (84°F), W.B. 19°C (86°F) Outdoor : D.B. 46°C (115°F), W.B. 24°C (75°F)
(Indoor / Outdoor)
Service Ref. PE-5/6EJSA2.TH
50Hz 1 60Hz 1
Rating conditions (JIS B 8616) NOTE : W4 Capacity of crankcase heater (W) based on 220 volts. NOTE : W5 Noise level is measured in an unacoustic room based on JIS conditions. NOTE : W6 Y : Inner thermostat, HP switch, Thermal switch
ph 220V / 3ph 380V ph 220V / 3ph 220V
T : Inner thermostat, HP switch, LP switch, Thermal switch
6
W
Btu/h
W
Btu/h
W
Btu/h
kW
kW
m
3
/min
CFM
m
3
/min
CFM Pa (mmAq) Pa (mmAq)
dB dB
in. mm (in.) mm (in.) mm (in.)
kg (lbs)
kW
W
kW
m
3
/min(CFM)
m
3
/min(CFM)
dB mm (in.) mm (in.) mm (in.)
kg (lbs)
PE-3EJA
3.TH
7,500
25,600
8,100
27,600
6,700
23,000
3.41 / 3.76
PE-3EJA
3.TH
Galvanized sheets
0.2
19 - 22
671 - 777
22 - 26
777 - 918
49 (5) 69 (7)
Remote controller & built-in
46 - 48 48 - 50
R1
785 (31) 690 (27-1/6) 428 (16-7/8)
46 (101)
PU-3VJC.TH, 3YJC.TH, 3NJA
1
Munsell 5Y 7/1
Capillary tube
(V)2.2, (Y)2.4 / (N)2.2
W6
32 / 38
0.085 50 (1,765) 50 (1,765)
52 / 53
870 (34-1/4)
295 + 24 (11-5/8 add 1)
850 (33-7/16)
73 (161)
50Hz
60Hz
60Hz
50Hz 60Hz
50Hz 60Hz
W
D H
50/60Hz
50Hz 60Hz
50/60Hz
W
D H
Service Ref.
External finish Fan motor output
Airflow Lo - High
Ex. static pressure at Hi - notch Operation control & thermostat
Noise level Low - High W5 Unit drain thread
Dimensions
Weight
Service Ref.
External finish Refrigerant (R-22) control Compressor output Protection devices Crankcase heater W4 Fan motor output
Airflow Noise level W5
Dimensions
Weight
Cooling capacity W1
Cooling capacity W2 Total input (50/60Hz) W3
OUTDOOR UNIT INDOOR UNIT
Service Ref.
Item
50Hz
60Hz
PE - 3EJA 3.TH
Service Ref.
1ph 220V / 1ph 220V, 3ph 380V
1ph 220V / 1ph 220V
50Hz 60Hz
NOTE : W1 Rating conditions (JIS B 8616)
NOTE : W2 Rating conditions (SSA 385, 386)
NOTE : W3 Total input based on indicated voltage.
Indoor : D.B. 27°C (80°F), W.B. 19°C (86°F) Outdoor : D.B. 35°C (95°F), W.B. 24°C (75°F)
Indoor : D.B. 29°C (84°F), W.B. 19°C (86°F) Outdoor : D.B. 46°C (115°F), W.B. 24°C (75°F)
Rating conditions (JIS B 8616) NOTE : W4 Capacity of crankcase heater (W) based on 220 volts. NOTE : W5 Noise level is measured in an unacoustic room based on JIS conditions. NOTE : W6 V , N ···Inner thermostat, HP switch, LP switch
Y···Thermal switch, Reversed - phase protector, HP switch, LP switch
(Indoor / Outdoor)
7
2. POWER SUPPLY & MODEL NAMES
1ph. 3ph. 1ph. 3ph.
PE - 3EJA 2.TH
PU-3VJA
1.TH
PU-3YJA
1.TH
PU-3NJA
1
PE - 3EJA
3.TH
PU-3VJC.TH PU-3YJC.TH
PU-3NJA
1
PE - 4EJSA
2.TH
PU-4VLJSA
1.TH
PU-4YJSA
1.TH
PU-4TJSA
2
Service Ref.(Outdoor unit)
Service Ref.(Indoor unit)Power supply
220, 230, 240V 380/220, 400/230, 415/240V 220V 220V
PE - 5EJSA
2.TH
PU-5YJSA.TH
PU-5TJSA
1
PE - 6EJSA 2.TH
PU-6YJSA.TH
PU-6TJSA
1
50Hz
60Hz
Power supply (1 phase)
Current Input Starting current Outdoor unit
PE-3EJA2.TH PE-3EJA
3.TH
1.07
0.23
2.4
PU-3
V : 220V 50Hz V : 230V 50Hz V : 240V 50Hz N : 220V 60Hz
1.41
0.30
2.6
PU-4
PE-4EJSA2.TH
1.07
0.24
2.5
PU-3
PE-3EJA2.TH PE-3EJA
3.TH
1.40
0.31
2.6
PU-4
PE-4EJSA2.TH
1.07
0.25
2.6
PU-3
PE-3EJA2.TH PE-3EJA
3.TH
1.39
0.32
2.6
PU-4
PE-4EJSA2.TH
1.47
0.32
2.1
PU-3
PE-3EJA2.TH PE-3EJA
3.TH
PE-4EJSA2.TH
1.95
0.42
2.6
PU-4
A
kW
A
Power supply (1 phase)
Service Ref.
Current Input Starting current Outdoor unit
PE-5EJSA2.TH
2.50
0.54
4.1
PU-5
Y : 220V 50Hz Y : 230V 50Hz Y : 240V 50Hz T : 220V 60Hz
PE-6EJSA2.TH
2.50
0.54
4.1
PU-6
PE-5EJSA2.TH
2.53
0.57
4.1
PU-5
PE-6EJSA2.TH
2.53
0.57
4.1
PU-6
PE-5EJSA2.TH
2.58
0.60
4.1
PU-5
PE-6EJSA2.TH
2.58
0.60
4.1
PU-6
PE-5EJSA2.TH
1.99
0.43
3.1
PU-5
PE-6EJSA2.TH
1.99
0.43
3.1
PU-6
A
kW
A
Service Ref.
NOTE : 1. Power supply key N ········1ph, 220V, 60Hz
V (L) ···1ph, 220, 230, 240V, 50Hz Y ··· 3ph, 380 / 220, 400 / 230, T ·········3ph, 220V, 60Hz 415 / 240V, 50Hz, 4wires
2. Primary power supplies for all indoor units are single - phase.
3. ELECTRICAL SPECIFICATIONS
Rating conditions
JIS B 8616
Series PE Indoor Unit (Single Phase)
Indoor : D.B. 27°C (80°F), W.B. 19°C (66°F) Outdoor : D.B. 35°C (95°F), W.B. 24°C (75°F)
8
DATA5
PE-3EJA2.TH
22
0.26
0.69
Evaporator airflow (m3/min) Bypass factors S.H.F. at rating conditions
Service Ref.
Temperature Outdoor D.B. Indoor D.B.
34
0.21
0.76
7.2
7.7
7.9
8.0
8.2
8.7
7.1
7.5
7.8
7.9
8.0
8.5
6.8
7.3
7.5
7.6
7.7
8.2
6.7
7.1
7.4
7.5
7.6
8.1
6.5
7.0
7.2
7.3
7.4
7.9
6.2
6.7
6.9
7.0
7.1
7.6
6.2
6.6
6.9
6.9
7.1
7.6
5.9
6.4
6.6
6.7
6.8
7.3
5.9
6.3
6.5
6.6
6.7
7.2
5.6
6.0
6.2
6.3
6.5
6.9
5.5
5.9
6.1
6.2
6.3
6.8
21°C
(69.8°F)
25°C
(77°F)
30°C
(86°F)
32.2°C (90°F)
35°C
(95°F)
40°C
(104°F)
40.6°C
(105°F)
45°C
(113°F)
46°C
(115°F)
50°C
(122°F)
52°C
(125.5°F)
16°C 18°C 19°C
19.4°C 20°C 22°C 16°C 18°C 19°C
19.4°C 20°C 22°C 16°C 18°C 19°C
19.4°C 20°C 22°C 16°C 18°C 19°C
19.4°C 20°C 22°C 16°C 18°C 19°C
19.4°C 20°C 22°C 16°C 18°C 19°C
19.4°C 20°C 22°C 16°C 18°C 19°C
19.4°C 20°C 22°C 16°C 18°C 19°C
19.4°C 20°C 22°C 16°C 18°C 19°C
19.4°C 20°C 22°C 16°C 18°C 19°C
19.4°C 20°C 22°C 16°C 18°C 19°C
19.4°C 20°C 22°C
(60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F)
T.C.
0.81
0.82
0.83
0.83
0.84
0.86
0.84
0.85
0.86
0.86
0.87
0.89
0.90
0.92
0.93
0.93
0.94
0.96
0.93
0.95
0.96
0.97
0.97
0.99
0.96
0.99
1.00
1.00
1.01
1.04
1.03
1.06
1.07
1.08
1.08
1.11
1.04
1.06
1.08
1.08
1.09
1.12
1.10
1.12
1.14
1.15
1.16
1.20
1.11
1.14
1.15
1.16
1.17
1.21
1.16
1.19
1.21
1.22
1.23
1.28
1.19
1.22
1.24
1.25
1.26
1.31
C.F.
(T.I.)
C.F.
(T.I.)
9.8
10.5
10.8
10.9
11.1
11.8
9.6
10.2
10.6
10.7
10.9
11.6
9.3
9.9
10.2
10.3
10.5
11.2
9.1
9.7
10.0
10.2
10.3
11.0
8.9
9.5
9.8
10.1
10.1
10.8
8.5
9.1
9.4
9.5
9.7
10.3
8.4
9.0
9.3
9.5
9.6
10.3
8.1
8.6
8.9
9.1
9.3
9.9
8.0
8.6
8.9
9.0
9.2
9.8
7.6
8.2
8.5
8.6
8.8
9.4
7.4
8.0
8.3
8.4
8.6
9.2
T.C.
0.81
0.82
0.83
0.83
0.84
0.86
0.84
0.85
0.86
0.86
0.87
0.89
0.90
0.92
0.93
0.93
0.94
0.96
0.93
0.95
0.96
0.97
0.97
0.99
0.96
0.99
1.00
1.00
1.01
1.04
1.03
1.06
1.07
1.08
1.08
1.11
1.04
1.06
1.08
1.08
1.09
1.12
1.10
1.12
1.14
1.15
1.16
1.20
1.11
1.14
1.15
1.16
1.17
1.21
1.16
1.19
1.21
1.22
1.23
1.28
1.19
1.22
1.24
1.25
1.26
1.31
PE-4EJSA
2.TH
1. PERFORMANCE DATA
Cooling capacity 50Hz
Notes : 1. T.C : Total capacity ( 103W)
C.F (T.I.) : Correction factors of Total input (Indoor unit input + Outdoor unit input)
2. (°F) = 32 + 9 / 5 (°C)
3. Guaranteed operating range (cooling)
...
(Btu / h)
.
=
. (W) 3.4, (kcal / h) = (W) 0.86
Lower limit ... Indoor : D.B. 21°C (70°F), W.B. 15.5°C (60°F), Outdoor : D.B. 21°C (70°F)
{
Upper limit
...
Indoor : D.B. 35°C (95°F), W.B. 22.5°C (72.5°F), Outdoor : D.B. 52°C (125.5°F)
9
WVL
...
Outdoor : D.B. 46°C (115°F)
Cooling capacity
Service Ref.
Temperature Outdoor D.B. Indoor D.B.
21°C
(69.8°F)
25°C
(77°F)
30°C
(86°F)
32.2°C (90°F)
35°C
(95°F)
40°C
(104°F)
40.6°C
(105°F)
45°C
(113°F)
46°C
(115°F)
50°C
(122°F)
52°C
(125.5°F)
Evaporator airflow (m3/min) Bypass factors S.H.F. at rating conditions
Notes : 1. T.C : Total capacity ( 103W)
C.F (T.I.) : Correction factors of Total input (Indoor unit input + Outdoor unit input)
2. (°F) = 32 + 9 / 5 (°C)
3. Guaranteed operating range (cooling)
16°C 18°C 19°C
19.4°C 20°C 22°C 16°C 18°C 19°C
19.4°C 20°C 22°C 16°C 18°C 19°C
19.4°C 20°C 22°C 16°C 18°C 19°C
19.4°C 20°C 22°C 16°C 18°C 19°C
19.4°C 20°C 22°C 16°C 18°C 19°C
19.4°C 20°C 22°C 16°C 18°C 19°C
19.4°C 20°C 22°C 16°C 18°C 19°C
19.4°C 20°C 22°C 16°C 18°C 19°C
19.4°C 20°C 22°C 16°C 18°C 19°C
19.4°C 20°C 22°C 16°C 18°C 19°C
19.4°C 20°C 22°C
50Hz
(60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F)
PE-3EJA3.TH
T.C.
7.5
8.0
8.3
8.4
8.5
9.0
7.4
7.8
8.1
8.2
8.4
8.9
7.1
7.6
7.8
7.9
8.1
8.6
7.0
7.4
7.7
7.8
7.9
8.4
6.8
7.3
7.5
7.6
7.7
8.3
6.5
6.9
7.2
7.3
7.4
7.9
6.5
6.9
7.1
7.2
7.4
7.9
6.2
6.6
6.8
6.9
7.1
7.6
6.1
6.5
6.8
6.9
7.0
7.5
5.8
6.3
6.5
6.6
6.7
7.2
5.7
6.1
6.4
6.5
6.6
7.1 22
0.26
...
.
=
(Btu / h)
{
. (W) 3.4, (kcal / h) = (W) 0.86
Lower limit ... Indoor : D.B. 21°C (70°F), W.B. 15.5°C (60°F), Outdoor : D.B. 21°C (70°F) Upper limit
...
Indoor : D.B. 35°C (95°F), W.B. 22.5°C (72.5°F), Outdoor : D.B. 52°C (125.5°F)
0.72
C.F.
(T.I.)
0.81
0.82
0.83
0.83
0.84
0.86
0.84
0.85
0.86
0.86
0.87
0.89
0.90
0.92
0.93
0.93
0.94
0.96
0.93
0.95
0.96
0.97
0.97
0.99
0.96
0.99
1.00
1.00
1.01
1.04
1.03
1.06
1.07
1.08
1.08
1.11
1.04
1.06
1.08
1.08
1.09
1.12
1.10
1.12
1.14
1.15
1.16
1.20
1.11
1.14
1.15
1.16
1.17
1.21
1.16
1.19
1.21
1.22
1.23
1.28
1.19
1.22
1.24
1.25
1.26
1.31
10
Cooling capacity
Service Ref.
Temperature Outdoor D.B. Indoor D.B.
21°C
(69.8°F)
25°C
(77°F)
30°C
(86°F)
32.2°C (90°F)
35°C
(95°F)
40°C
(104°F)
40.6°C
(105°F)
45°C
(113°F)
46°C
(115°F)
50°C
(122°F)
52°C
(125.5°F)
Evaporator airflow (m3/min) Bypass factors S.H.F. at rating conditions
Notes : 1. T.C : Total capacity ( 103W)
2. (°F) = 32 + 9 / 5 (°C)
3. Guaranteed operating range (cooling)
16°C 18°C 19°C
19.4°C 20°C 22°C 16°C 18°C 19°C
19.4°C 20°C 22°C 16°C 18°C 19°C
19.4°C 20°C 22°C 16°C 18°C 19°C
19.4°C 20°C 22°C 16°C 18°C 19°C
19.4°C 20°C 22°C 16°C 18°C 19°C
19.4°C 20°C 22°C 16°C 18°C 19°C
19.4°C 20°C 22°C 16°C 18°C 19°C
19.4°C 20°C 22°C 16°C 18°C 19°C
19.4°C 20°C 22°C 16°C 18°C 19°C
19.4°C 20°C 22°C 16°C 18°C 19°C
19.4°C 20°C 22°C
C.F (T.I.) : Correction factors of Total input (Indoor unit input + Outdoor unit input)
50Hz
(60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F)
(66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F)
PE-5EJSA2.TH
T.C.
12.1
12.9
13.3
13.5
13.7
14.6
11.9
12.7
13.1
13.2
13.5
14.3
11.4
12.2
12.6
12.8
13.0
13.8
11.2
12.0
12.4
12.5
12.8
13.6
11.0
11.7
12.1
12.3
12.5
13.3
10.5
11.2
11.6
11.7
12.0
12.8
10.4
11.1
11.5
11.7
11.9
12.7
10.0
10.7
11.0
11.2
11.4
12.2
9.9
10.6
10.9
11.0
11.2
12.1
8.9
9.6
9.9
10.0
10.3
10.6
7.9
8.5
8.8
8.9
9.1
9.4
C.F.
(T.I.)
0.81
0.82
0.83
0.83
0.84
0.86
0.84
0.85
0.86
0.86
0.87
0.89
0.90
0.92
0.93
0.93
0.94
0.96
0.93
0.95
0.96
0.97
0.97
0.99
0.96
0.99
1.00
1.00
1.01
1.04
1.03
1.06
1.07
1.08
1.08
1.11
1.04
1.06
1.08
1.08
1.09
1.12
1.10
1.12
1.14
1.15
1.16
1.20
1.11
1.14
1.15
1.16
1.17
1.21
1.16
1.19
1.21
1.22
1.23
1.28
1.19
1.22
1.24
1.25
1.26
1.31
PE-6EJSA
T.C.
14.1
15.0
15.4
15.6
15.9
16.8
13.7
14.6
15.1
15.3
15.6
16.6
13.2
14.1
14.6
14.8
15.0
16.0
13.0
13.9
14.3
14.5
14.8
15.7
12.7
13.5
14.0
14.2
14.5
15.4
12.1
13.0
13.4
13.6
13.8
14.8
12.1
12.9
13.3
13.5
13.8
14.7
11.5
12.4
12.8
13.0
13.2
14.1
11.4
12.2
12.6
12.7
13.0
14.0
10.3
11.1
11.5
11.6
11.9
12.3
9.1
9.8
10.2
10.3
10.5
10.9
42
0.18
...
{
.
=
(Btu / h)
. (W) 3.4, (kcal / h) = (W) 0.86
Lower limit ... Indoor : D.B. 21°C (70°F), W.B. 15.5°C (60°F), Outdoor : D.B. 21°C (70°F) Upper limit
...
Indoor : D.B. 35°C (95°F), W.B. 22.5°C (72.5°F), Outdoor : D.B. 52°C (125.5°F)
0.82
...
WVL
Outdoor : D.B. 46°C (115°F)
42
0.16
0.77
2.TH
C.F.
(T.I.)
0.81
0.82
0.83
0.83
0.84
0.86
0.84
0.85
0.86
0.86
0.87
0.89
0.90
0.92
0.93
0.93
0.94
0.96
0.93
0.95
0.96
0.97
0.97
0.99
0.96
0.99
1.00
1.00
1.01
1.04
1.03
1.06
1.07
1.08
1.08
1.11
1.04
1.06
1.08
1.08
1.09
1.12
1.10
1.12
1.14
1.15
1.16
1.20
1.11
1.14
1.15
1.16
1.17
1.21
1.16
1.19
1.21
1.22
1.23
1.28
1.19
1.22
1.24
1.25
1.26
1.31
11
Cooling capacity
Service Ref.
Temperature Outdoor D.B. Indoor D.B.
21°C
(69.8°F)
25°C
(77°F)
30°C
(86°F)
32.2°C (90°F)
35°C
(95°F)
40°C
(104°F)
40.6°C
(105°F)
45°C
(113°F)
46°C
(115°F)
50°C
(122°F)
52°C
(125.5°F)
Evaporator airflow (m3/min) Bypass factors S.H.F. at rating conditions
Notes : 1. T.C : Total capacity ( 103W)
16°C 18°C 19°C
19.4°C 20°C 22°C 16°C 18°C 19°C
19.4°C 20°C 22°C 16°C 18°C 19°C
19.4°C 20°C 22°C 16°C 18°C 19°C
19.4°C 20°C 22°C 16°C 18°C 19°C
19.4°C 20°C 22°C 16°C 18°C 19°C
19.4°C 20°C 22°C 16°C 18°C 19°C
19.4°C 20°C 22°C 16°C 18°C 19°C
19.4°C 20°C 22°C 16°C 18°C 19°C
19.4°C 20°C 22°C 16°C 18°C 19°C
19.4°C 20°C 22°C 16°C 18°C 19°C
19.4°C 20°C 22°C
C.F (T.I) : Correction factors of Total input (Indoor unit input + Outdoor unit input)
2. (°F) = 32 + 9 / 5 (°C)
3. Guaranteed operating range (cooling)
60Hz
(60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F)
(66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F)
...
(Btu / h)
PE-3EJA2.TH, PE-3EJA3.TH
T.C.
8.1
8.7
8.9
9.0
9.2
9.7
7.9
8.5
8.7
8.9
9.0
9.6
7.7
8.2
8.4
8.5
8.7
9.3
7.5
8.0
8.3
8.4
8.6
9.1
7.3
7.8
8.1
8.2
8.4
8.9
7.0
7.5
7.8
7.9
8.0
8.5
7.0
7.5
7.8
7.9
8.0
8.5
6.7
7.5
7.4
7.5
8.0
8.2
6.6
7.1
7.3
7.4
7.6
8.1
6.3
6.8
7.0
7.1
7.3
7.8
6.2
6.6
6.9
7.0
7.1
7.6
C.F.
(T.I.)
0.81
0.82
0.83
0.83
0.84
0.86
0.84
0.85
0.86
0.86
0.87
0.89
0.90
0.92
0.93
0.93
0.94
0.96
0.93
0.95
0.96
0.97
0.97
0.99
0.96
0.99
1.00
1.00
1.01
1.04
1.03
1.06
1.07
1.08
1.08
1.11
1.04
1.06
1.08
1.08
1.09
1.12
1.10
1.12
1.14
1.15
1.16
1.20
1.11
1.14
1.15
1.16
1.17
1.21
1.16
1.19
1.21
1.22
1.23
1.28
1.19
1.22
1.24
1.25
1.26
1.31
26
0.35
0.67
.
=
. (W) 3.4, (kcal / h) = (W) 0.86
Lower limit ... Indoor : D.B. 21°C (70°F), W.B. 15.5°C (60°F), Outdoor : D.B. 21°C (70°F)
{
Upper limit
...
Indoor : D.B. 35°C (95°F), W.B. 22.5°C (72.5°F), Outdoor : D.B. 52°C (125.5°F)
PE-4EJSA
T.C.
10.9
11.7
12.0
12.2
12.4
13.1
10.7
11.4
11.8
11.9
12.1
12.9
10.3
11.0
11.3
11.5
11.7
12.5
10.1
10.8
11.2
11.3
11.5
12.3
9.9
10.5
10.9
11.0
11.3
12.0
9.4
10.1
10.4
10.6
10.8
11.5
9.4
10.0
10.4
10.5
10.7
11.4
9.0
9.6
10.0
10.1
10.3
11.0
8.9
9.5
9.9
10.0
10.2
10.9
8.5
9.1
9.5
9.6
9.8
10.5
8.3
8.9
9.2
9.4
9.6
10.3 34
0.23
0.74
2.TH
C.F.
(T.I.)
0.81
0.82
0.83
0.83
0.84
0.86
0.84
0.85
0.86
0.86
0.87
0.89
0.90
0.92
0.93
0.93
0.94
0.96
0.95
0.96
0.97
0.97
1.00
0.99
0.96
0.99
1.00
1.00
1.01
1.04
1.03
1.06
1.07
1.08
1.08
1.11
1.04
1.06
1.08
1.08
1.09
1.12
1.10
1.12
1.14
1.15
1.16
1.20
1.11
1.14
1.15
1.16
1.17
1.21
1.16
1.19
1.21
1.22
1.23
1.28
1.19
1.22
1.24
1.25
1.26
1.31
12
Cooling capacity
Service Ref.
Temperature Outdoor D.B. Indoor D.B.
21°C
(69.8°F)
25°C
(77°F)
30°C
(86°F)
32.2°C (90°F)
35°C
(95°F)
40°C
(104°F)
40.6°C
(105°F)
45°C
(113°F)
46°C
(115°F)
50°C
(122°F)
52°C
(125.5°F)
Evaporator airflow (m3/min) Bypass factors S.H.F. at rating conditions
Notes : 1. T.C : Total capacity ( 103W)
16°C 18°C 19°C
19.4°C 20°C 22°C 16°C 18°C 19°C
19.4°C 20°C 22°C 16°C 18°C 19°C
19.4°C 20°C 22°C 16°C 18°C 19°C
19.4°C 20°C 22°C 16°C 18°C 19°C
19.4°C 20°C 22°C 16°C 18°C 19°C
19.4°C 20°C 22°C 16°C 18°C 19°C
19.4°C 20°C 22°C 16°C 18°C 19°C
19.4°C 20°C 22°C 16°C 18°C 19°C
19.4°C 20°C 22°C 16°C 18°C 19°C
19.4°C 20°C 22°C 16°C 18°C 19°C
19.4°C 20°C 22°C
C.F (T.I) : Correction factors of Total input (Indoor unit input + Outdoor unit input)
2. (°F) = 32 + 9 / 5 (°C)
3. Guaranteed operating range (cooling)
60Hz
(60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F)
(66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F)
...
(Btu / h)
PE-5EJSA2.TH
T.C.
13.6
14.4
14.9
15.1
15.3
16.2
13.2
14.1
14.6
14.8
15.0
16.0
12.8
13.6
14.0
14.2
14.5
15.4
12.5
13.4
13.8
14.0
14.3
15.2
12.2
13.1
13.5
13.7
13.9
14.9
11.7
12.5
12.9
13.1
13.4
14.3
11.6
12.4
12.9
13.0
13.3
14.2
11.1
11.9
12.3
12.5
12.7
13.6
11.0
11.8
12.1
12.3
12.5
13.5
9.9
10.7
11.1
11.2
11.4
11.8
8.8
9.4
9.8
9.9
10.1
10.5
C.F. (T.I.)
0.81
0.82
0.83
0.83
0.84
0.86
0.84
0.85
0.86
0.86
0.87
0.89
0.90
0.92
0.93
0.93
0.94
0.96
0.93
0.95
0.96
0.97
0.97
0.99
0.96
0.99
1.00
1.00
1.01
1.04
1.03
1.06
1.07
1.08
1.08
1.11
1.04
1.06
1.08
1.08
1.09
1.12
1.10
1.12
1.14
1.15
1.16
1.20
1.11
1.14
1.15
1.16
1.17
1.21
1.16
1.19
1.21
1.22
1.23
1.28
1.19
1.22
1.24
1.25
1.26
1.31
PE-6EJSA
T.C.
15.3
16.2
16.8
17.0
17.3
18.3
14.9
15.9
16.4
16.6
16.9
18.0
14.4
15.3
15.8
16.0
16.3
17.4
14.1
15.1
15.5
15.7
16.0
17.1
13.8
14.7
15.2
15.4
15.7
16.7
13.2
14.1
14.6
14.7
15.0
16.0
13.1
14.0
14.5
14.7
15.0
16.0
12.5
13.4
13.9
14.1
14.4
15.3
12.4
13.3
13.7
13.8
14.1
15.2
11.2
12.0
12.4
12.6
12.9
13.3
9.9
10.6
11.0
11.2
11.4
11.8
42
0.19
0.77
.
=
. (W) 3.4, (kcal / h) = (W) 0.86
Lower limit ... Indoor : D.B. 21°C (70°F), W.B. 15.5°C (60°F), Outdoor : D.B. 21°C (70°F)
{
Upper limit
...
Indoor : D.B. 35°C (95°F), W.B. 22.5°C (72.5°F), Outdoor : D.B. 52°C (125.5°F)
2.TH
42
0.19
0.73
C.F.
(T.I.)
0.81
0.82
0.83
0.83
0.84
0.86
0.84
0.85
0.86
0.86
0.87
0.89
0.90
0.92
0.93
0.93
0.94
0.96
0.93
0.95
0.96
0.97
0.97
0.99
0.96
0.99
1.00
1.00
1.01
1.04
1.03
1.06
1.07
1.08
1.08
1.11
1.04
1.06
1.08
1.08
1.09
1.12
1.10
1.12
1.14
1.15
1.16
1.20
1.11
1.14
1.15
1.16
1.17
1.21
1.16
1.19
1.21
1.22
1.23
1.28
1.19
1.22
1.24
1.25
1.26
1.31
13
Cooling capacity correction factors
Service Ref.
PE-3EJA2.TH PE-3EJA
3.TH
PE-4EJSA PE-5EJSA PE-6EJSA
2.TH
2.TH
2.TH
5m (16ft)
1.0
1.0
1.0
1.0
10m (33ft)
0.978
0.984
0.978
0.971
15m (49ft)
50Hz
0.962
0.974
0.962
0.950
Refrigerant piping length (one way)
20m (66ft)
0.948
0.964
0.948
0.931
25m (82ft)
0.934
0.954
0.934
0.912
30m (98ft)
0.921
0.944
0.921
0.896
35m (115ft)
0.935
0.908
0.880
40m (131ft)
0.926
0.896
0.864
45m (148ft)
— —
0.884
0.850
50m (164ft)
— —
0.875
0.840
Cooling capacity correction factors
Service Ref.
PE-3EJA2.TH PE-3EJA
3.TH
PE-4EJSA PE-5EJSA PE-6EJSA
2.TH
2.TH
2.TH
5m (16ft)
1.0
1.0
1.0
1.0
10m (33ft)
0.971
0.980
0.971
0.960
15m (49ft)
60Hz
0.950
0.966
0.950
0.933
Refrigerant piping length (one way)
20m (66ft)
0.931
0.952
0.931
0.908
25m (82ft)
0.913
0.939
0.913
0.885
30m (98ft)
0.896
0.926
0.896
0.894
35m (115ft)
0.914
0.880
0.845
40m (131ft)
0.902
0.864
0.828
45m (148ft)
— —
0.850
0.812
50m (164ft)
— —
0.840
0.800
14
2. STANDARD OPERATION DATA
V A
V A
Capacity Input
Indoor unit Service Ref.
Phase, Hz Volts Amperes
Outdoor unit Service Ref.
Phase, Hz Volts Amperes
Discharge pressure
Suction pressure
Discharge temperature
Condensing temperature
Suction temperature
Ref. pipe length
Discharge air temperature
Service Ref.
Mode
Cooling
7,200
3.41
1, 50
220
1.07
PU-3VJA
1.TH
1, 50
220
15.1
2.04
0.465
64.1
52.4
4.5 5
27 19
13.1 35 24
W
kW
MPa MPa
:
:
:
m
:
:
:
:
:
(kgf/F) (kgf/F)
(20.8)
(4.7)
(22.4)
(4.5)
(19.5)
(5.5)
(21.8)
(5.2)
Cooling
8,100
3.76
1, 60
220
1.41
PU-3NJA
1
1, 60
220
17.6
2.20
0.44
73.2
54.2
1.3 5
27 19
14.2 35 24
Cooling
9,800
3.59
1, 50
220
1.41
PU-4YJSA
1.TH
3, 50
380
5.7
1.91
0.54
77.4
50.3
9.2 5
27 19
14.6 35 24
Cooling
10,900
4.69
1, 60
220
1.95
PU-4TJSA
2
3, 60
220
12.2
2.14
0.51
77.5
54.9
6.7 5
27 19
15.3 35 24
PE-3EJA
2.TH PE-4EJSA 2.TH
PE-3EJA
2.TH PE-4EJSA 2.TH
TotalElectrical CircuitRefrigerant CircuitIndoor side
Outdoor side
Intake air temperature
Intake air temperature
D.B. W.B. D.B. D.B. W.B.
The unit of pressure has been changed to Mpa based on SI (International System of Units) in accordance with I.S.O. (International Organization for Standardization).
The conversion factor is : 1(Mpa) =10.2 (OOf/FF)
15
Capacity Input
Indoor unit Service Ref.
Phase, Hz Volts Amperes
Outdoor unit Service Ref.
Phase, Hz Volts Amperes
Discharge pressure
Suction pressure
Discharge temperature
Condensing temperature
Suction temperature
Ref. pipe length
Discharge air temperature
Service Ref.
Mode
W
kW
V A
V A
MPa MPa
:
:
:
m
:
:
:
:
:
(kgf/F) (kgf/F)
(20.2)
(4.4)
(19.9)
(4.5)
(19.0)
(4.9)
(20.5 )
(4.1)
Cooling
13,500
6.06
1, 60
220
1.99
PU-5TJSA
1
3, 60
220
16.83
1.98
0.43
78.3
51.9
1.6 5
27 19
14.9 35 24
Cooling
14,000
5.65
1, 50
220
2.50
PU-6YJSA.TH
3, 50
380
8.63
1.95
0.44
77.8
50.8
1.7 5
27 19
14.5 35 24
Cooling
12,100
5.10
1, 50
220
2.50
PU-5YJSA.TH
3, 50
380
8.15
1.86
0.48
72.2
49.3
- 0.9 5
27 19
15.5
35 24
Cooling
15,200
6.58
1, 60
220
1.99
PU-6TJSA
1
3, 60
220
18.70
2.01
0.40
81
52.1
- 0.5 5
27 19
14.1
35 24
PE-5EJSA
2.TH PE-6EJSA2.TH
PE-5EJSA
2.TH PE-6EJSA 2.TH
TotalElectrical CircuitRefrigerant CircuitIndoor side
Outdoor side
Intake air temperature
Intake air temperature
D.B. W.B. D.B. D.B. W.B.
The unit of pressure has been changed to Mpa based on SI (International System of Units) in accordance with I.S.O. (International Organization for Standardization).
The conversion factor is : 1(Mpa) =10.2 (OOf/FF)
16
Service Ref.
PE-3EJA
3.TH
Mode
Capacity
TotalElectrical CircuitRefrigerant CircuitIndoor side
Input
Indoor unit Service Ref.
Phase, Hz Volts Amperes
Outdoor unit Service Ref.
Phase, Hz Volts Amperes
Discharge pressure
Suction pressure
Discharge temperature
Condensing temperature
Suction temperature
Ref. pipe length
Intake air temperature
Discharge air temperature
Intake air temperature
Outdoor side
D.B. W.B. D.B. D.B. W.B.
W
kW
V A
V A
MPa
(kgf/F)
MPa
(kgf/F)
:
:
:
m
:
:
:
:
:
Cooling
7,500
3.41
1, 50
220
1.07
PU-3VJC.TH
1, 50
220
15.1
2.04
(20.8)
0.46 (4.7)
88.1
52.4
4.5 5
27 19
15.0 35 24
PE-3EJA
3.TH
Cooling
8,100
3.76
1, 60
220
1.41
PU-3NJA
1, 60
220
17.6
2.20
(22.4)
0.44 (4.5)
73.2
54.2
1.3 5
27 19
14.2 35 24
1
The unit of pressure has been changed to Mpa based on SI (International System of Units) in accordance with I.S.O. (International Organization for Standardization).
The conversion factor is : 1(Mpa) =10.2 (OOf/FF)
17
3. FAN PERFORMANCE AND CORRECTED AIRFLOW
Airflow (m /min)
50Hz
50Hz
Recommended range
150
100
50
Hi
Lo
0
1.0
0.95
1.05
0.9
2022 25 30 3537
20 22 25 30 35 37 40
External static pressure(Pa)
(1Pa = 0.1mmAq)
Correction factor
Airflow (m /min)
Airflow (m /min)
60Hz
Recommended range
150
100
50
Hi
Lo
0
1.0
0.95
1.05
0.9
2022 25 30 3537
20 22 25 30 35 37 40
External static pressure(Pa)
(1Pa = 0.1mmAq)
Correction factor
Airflow (m /min)
60Hz
Capacity
Input
50Hz
50Hz
Recommended range
150
100
50
Hi
Lo
0
1.0
0.95
0.9 16 18 20 22
16 18 20 22
External static pressure(Pa)
(1Pa = 0.1mmAq)
Airflow (m /min) (1m /min = 35.3CFM)
Correction factor
Airflow (m /min)
60Hz
60Hz
Recommended range
150
100
50
Hi
Lo
0
1.0
0.95
0.9 2019 22 24 26
19 20 22 24 26
External static pressure(Pa)
(1Pa = 0.1mmAq)
Correction factor
Airflow (m /min)
Capacity
Input
Service Ref. : PE-3EJA2.TH
PE-3EJA3.TH
Service Ref. : PE-4EJSA 2.TH
18
Service Ref. : PE-5EJSA 2.TH
Recommended range
150
100
50
0
External static pressure(Pa)
(1Pa = 0.1mmAq)
27 30 35 40 45 4850
Airflow (m /min)
1.05
1.0
0.95
Correction factor
0.9
27 30 35 40 45 48
Airflow (m /min)
50Hz
Hi
Lo
50Hz
Capacity
Input
Recommended range
150
100
Lo
50
0
External static pressure(Pa)
(1Pa = 0.1mmAq)
27 30 35 40 45 50
Airflow (m /min)
1.05
1.0
0.95
Correction factor
0.9
27 30 35 40 45
Airflow (m /min)
60Hz
Hi
60Hz
Service Ref. : PE-6EJSA 2.TH
50Hz
Recommended range
150
100
50
0
External static pressure(Pa)
(1Pa = 0.1mmAq)
27 30 35 40 45 48 50
Hi
Lo
Airflow (m /min)
50Hz
1.05
1.0
0.95
Correction factor
0.9
27 30 35 40 45 48
Airflow (m /min)
Capacity
Input
Recommended range
150
100
Lo
50
0
External static pressure(Pa)
(1Pa = 0.1mmAq)
27 30 35 40 45 50
Airflow (m /min)
1.05
1.0
0.95
Correction factor
0.9
27 30 35 40 45
Airflow (m /min)
60Hz
Hi
60Hz
19
6
11
11
105 35
70
44
50
59
75
35
3.2
(2 3/8)
60 265(10 1/2) 40 155 155 155
20(13/16)
10(3/8)
600(24)
100
70 300
900(36)
14524.5 145
22.5
20
672(26 1/ 2)
(4 3/16)
(13/16)
510(20 1/8)
339(13 3/8)
418(16 1/2)
(11 13/16)
530(7 7/8)
(2 3/4)
200(7 7/8) 200(7/8)130
220
128
14
20 20
25 25
15
15
15
11
9017525070
15
25
381(15) 10(3/8)
2585 85
125 125
(2 3/4)
530(20 7/8)
(8 7/16)
(5 1/16)
690(27 3/16)
730(28 3/4)
300(11 13/16)
235(9 1/4)
650(25 5/8)
40 40
(3·9/16)
345(13 5/8)
OUTLINES AND DIMENSIONS
1. INDOOR UNIT PE-3EJA2.TH PE-3EJA3.TH
Unit : mm (inch)
Refrigerant-pipe flared connection [9.52 (3/8)
1
Refrigerant-pipe flared connection [15.88 (5/8)
2
Electrical parts box
3
Drainage pan
4
Drainage pipe connection R1 (male)
5
Service panel (Indoor coil thermistor)
6
Room temperature thermistor
7
Heat insulator t10 (3/8)
8
Air intake duct flange
9
Air intake
10 11
Wiring entry (2-[22 (7/8) holes)
Suspension bolt holes (4-[12 (1/2))
12
14-[3 (1/8) holes
13
For air outlet duct connection (12-[3 (1/8) holes)
14
Air outlet
15
Mounting plate
16
Air outlet duct flange
17
Heat insulator t10 (3/8)
18
Service space (opening) in the ceiling
19
Service panel (Room temperature thermistor)
20
Duct earth
21
20
PE-4EJSA 2.TH
11
90
35
20
(13/16)
980(38 9/16)
(3·9/16)
795(31 5/16)
11 65(=715)
4 65(=260)
3 65(=195)
7 65(=455)
345(13 5/8)
70
40 40
65
200(7 7/8)
200(7/8)
130
20 20
65
22.5
15
15
22.5
530(20 7/8)
960(27 3/16)
44
55
63
85
35
(3 3/8)
70 245
(2 3/4) (9 5/8)
3.2
98
14
250(6 13/16)
(3 7/8)
1000(3 15/16)
500(19 11/16)
210(8 1/4)
920(36 1/4)40 40
20(13/16)
10(3/8)
39.5 65
339(13·3/8)
418(16·1/2)
15
90
11
17525070
15
27.5 27.5 381(15)
10(3/8)
65
(2 3/4)
(3·9/16)
100
70
300
900(36)
(11 13/16)
530(7 7/8)
(2 3/4)
600(24)
11
Unit : mm (inch)
Refrigerant-pipe flared connection [9.52 (3/8)
1
Refrigerant-pipe flared connection [19.05 (3/4)
2 3 4 5 6 7 8 9
10
11
Electrical parts box Drain pan Drain pipe connection R1 (male) Service panel (Indoor coil thermistor) Room temperature thermistor Heat insulator t10 (3/8) Air intake duct flange Air intake Wiring entry (2-[22 (7/8) holes)
Suspension bolt holes (4-[12 (1/2))
12
34-[3 (1/8) holes
13
For air outlet duct connection (24-[3 (1/8) holes)
14
Air outlet
15
Mounting plate
16
Air outlet duct flange
17
Heat insulator t10 (3/8)
18
Service space (opening) in the ceiling
19
Service panel (Room temperature thermistor)
20
Duct earth
21
21
PE-5EJSA 2.TH
11
11
90
35
20
1142(44 15/16)
(13/16)
(3 9/16)
995(39 3/16)
345(13 5/8)
530(20 7/8)
14 65(=910)
13 65(=845)
70
40
40
65
200(7 7/8)
130
20 20
65
27.5
15
15
27.5
200(7 7/8)
1160(15 11/16)
44
55
63
85
35
(3 3/8)
70 245
(2 3/4) (9 5/8)
3.2
98
14
250(6 13/16)
(3 7/8)
1200(47 1/4)
900(35 7/16)
110(4 5/16)
1120(44 1/8)40 40
4 65(=260)
3 65(=195)
20(13/16)
10(3/8)
10(3/8)
39.5 65
339(13 3/8)
418(16 1/2)
15
90
11
17525070
15
27.527.5
381(15)
65
(2 3/4)
(3 9/16)
100
70
300
900(36)
(11 13/16)
530(7 7/8)
600(24)
PE-6EJSA 2.TH
Unit : mm (inch)
Refrigerant-pipe flared connection [9.52 (3/8)
1
Refrigerant-pipe flared connection [19.05 (3/4)
2
Electrical parts box
3
Drain pan
4
Drain pipe connection R1 (male)
5
Service panel (Indoor coil thermistor)
6
Room temperature thermistor
7
Heat insulator t10 (3/8)
8
Air intake duct flange
9
Air intake
10
Wiring entry (2-[22 (7/8) holes)
11
Suspension bolt holes (4-[12 (1/2))
12
40-[3 (1/8) holes
13
For air outlet duct connection (36-[3 (1/8) holes)
14
Air outlet
15
Mounting plate
16
Air outlet duct flange
17
Heat insulator t10 (3/8)
18 19 20 21
Service space (opening) in the ceiling Service panel (Room temperature thermistor) Duct earth
22
2. REMOTE CONTROLLER
MITSUBISHI ELECTRIC
12 11 10
9 8 7 6 5 4 3 2 1
29 28 27 26 25 24 23 22 21 20 19 18
TIMER TEMP
TIMER/TEMP.
UP
DOWN
POWER
COOL
ON/OFF
MODE
SELECT
FAN
SPEED
TIMER MODE
DRY FAN
HIGH LOW
AUTO
STOP START
75
69
108
117
108
96.5
12
90.5
11.6
3.6
33
117
33
Rear side wiring arrangememt opening
Upper side wiring arrangement opening
Fixing hole
83.5
12
86
4.6
46
9.2
MITSUBISHI ELECTRIC
12 11 10
9 8 7 6 5 4 3 2 1
29 28 27 26 25 24 23 22 21 20 19 18
TIMER TEMP
TIMER/TEMP.
UP
DOWN
POWER
COOL
ON/OFF
MODE
SELECT
FAN
SPEED
TIMER
MODE
DRY FAN
HIGH LOW
AUTO STOP
START
Exposed remote controller cable
Cable can be connected only to the top of the remote controller. (Right side, left side, and buttom are not possible.)
Remote controller cable
Conduit tube (local arrangement)
Switch box (local arrangement)
Set screw (match with switch box), local arrangement.
Unit : mm
For exposed remote controller cable installation
Note : The cable for the remote controller has 10m (39ft) length and 12-core with connectors O.D. 5.8.
Remote controller cable installation
For recessed remote controller cable installation
23
7
WIRING DIAGRAM
PE-3EJA2.TH / PE-3EJA3.TH / PE-4EJSA2.TH / PE-5EJSA2.TH / PE-6EJSA2.TH
SYMBOL NAME
C1
CN120<I.B>
CN51<I.B>
CNR120<R.B>
FI,2<I.B> I.B LD1<R.B> LD3<R.B> LD4<R.B> LD5<R.B> LD7<R.B> LD8<R.B> LD9<R.B> LD10<R.B> LD11<R.B> LD12<R.B>
FAN MOTOR CAPACITOR REMOTE CONTROLLER TRANSMISSION WIRE
CONNECTOR REMOTE INDICATOR CONNECTOR REMOTE CONTROLLER TRANSMISSION WIRE
CONNECTOR FUSE (6.3A 250V)
INDOOR CONTROLLER BOARD RUN INDICATOR LED COOLING INDICATOR LED FAN MODE INDICATOR LED FAN HIGH INDICATOR LED INDICATOR MODE TEMPERATURE LED INDICATOR MODE TIMER LED DRY INDICATOR LED FAN LOW INDICATOR LED OFF TIMER INDICATOR LED ON TIMER INDICATOR LED
MF1
6
432
51
RED
BLU
BLK
WHT
ORN
YLW
BLU
C1
7
531
CND 31
POWER
RED
I.B
BLK
FAN1
F2 F1
X5
X6
X6 X5
CN2B
TWIN-2
SW3
ON OFF
321
CN2A
TWIN-1
ZNR
SW1 ON OFF
3213421
JR
01 02 03 04 05 06
NOTES:
1. Since the indoor transformer (T) is connected with 220V wiring, if 230V or 240V power is used, change the wiring connection as shown fig : 1 w. When power supply is
240V 230V
fig w1
240 YELLOW 230 ORANGE 220 RED
Since the indoor fan motor (MF1) is connected with 220V 60Hz power, if 200V~240V 50Hz power is used, change the wiring connection as shown fig : 2 w.
fig w2
LD YELLOW
Indoor fan motor (MF1) for 200V ~ 240V 50Hz.
BLUE
200—220 230—240
LD
2. Be sure to refer the outdoor unit electric wiring diagram before wiring of outdoor side unit.
3. Symbols used in wiring diagram above are.
/ : Terminal block, : Connector.
4. Emergency operation If remote controller or microcomputer fails but there is no other trouble, emergency operation is possible by setting dip switch [SW3<I. B>] on the indoor con­troller board.
[Check items] (1) Compressor and fan. (2) Check the trouble position using self diagnostic function. If the result of self diagnosis indicates protective device such as freeze protection is functioning emer-
gency operation is not possible unless the cause is removed.
(3) In emergency operation, the operation made by only ON / OFF circuit breaker manually [ON / OFF with remote controller is not possible]. [Emergency operation procedure]
(1) Cooling is possible by setting
.
1
2 ON and 3 OFF for the dip switch (SW3<I.B>) at indoor controller board.
(2) Turn on outdoor unit side circuit breaker, then indoor unit side circuit breaker in this order. (3) During emergency operation indoor fan runs at high. (4) Thermostat will not function. (5) Do not cooling for more than 10 hours (the indoor unit heat exchanger can freeze). DWG NO. BG79N636H01
SYMBOL NAME
LD13-24<R.B>
MF1
SW1<I.B> SW2<I.B> SW3<I.B> SW1<R.B> SW2<R.B> SW3<R.B> SW5<R.B>
SW6<R.B>
SW7<R.B>
SW8<R.B>
BLU
SW2
RED
WHT
YLW
CN20
INTAKE
TEMPERATURE / TIMER REMAINING TIME INDICATOR LED
INDOOR FAN MOTOR
FUNCTION SWITCH UNIT SWITCH EMERGENCY OPERATION SWITCH ON / OFF SWITCH OPERATION MODE SWITCH FAN HIGH / LOW SWITCH INDICATOR SWITCH
TEMPERATURE TIMER SETTING UPSWITCH
TEMPERATURE TIMER SETTING DOWN SWITCH
TIMER CONTINUOUS ON / OFF SWITCH
220V 230V 240V
YLW
CNT
CN50
DRAIN
T
35421
ORN
TRANS
12
RT1
220 BLUE
10.6VAC
14.5VAC
CN21 PIPE
RED
RED
BRN
BRN
342131
CN4T
TRANS
CN51
MULTIPLE
CN30
123
OUTDOOR
12
RT2
TB1
RED BLU
GRN/YLW
Indoor unit
CN120
TO.RC
112
CN31
132
HEATER
CN2
TIMER
CN28
L.TEST
TO OUTDOOR UNIT CONNECTING WIRES DC 12V(non-polar)
SYMBOL NAME
R.B T TB1
TB2
RT1
RT2
X5<I.B> X6<I.B> ZNR<I.B>
JR
POWER SUPPLY
L
~ (1 PHASE)
N
220-240V 50Hz
REMOTE CONTROLLER BOARD TRANSFORMER POWER SUPPLYTERMINAL BLOCK
INDOOR / OUTDOOR CONNECTING WIRE TER­MINAL BLOCK
ROOM TEMPERATURE THERMISTOR (0°C / 15k, 25°C / 5.4kΩ DETECT)
INDOOR COIL THERMISTOR ( 0°C / 15k, 25°C / 5.4kΩ DETECT)
FAN MOTOR AUXILIARY RELAY FAN MOTOR AUXILIARY RELAY VARISTOR
FUNCTION SELECTOR JUMPER RESISTORS
220V 60Hz
Remote controller
Remote control transmission line DC 12V with 12 core connector
R.B
LD8
ORN YLW
TB2 21
LD13 LD14 LD15 LD16 LD17 LD18 LD19 LD20 LD21 LD22 LD23 LD24
LD7
SW5
SW6
SW7
CNR120 LD1
LD3 LD9 LD4
LD5
LD10
LD11 LD12
SW1
SW2
SW3
SW8
24
REFRIGERANT SYSTEM DIAGRAM8
PE-3EJA3.TH PU-3C type
PE-3EJA 2.TH PU-3A type
Indoor heat
exchanger
Outdoor heat
exchanger
Indoor coil thermistor RT2
Distributor with strainer
Indoor heat
exchanger
Indoor coil thermistor RT2
Distributor with strainer
Flared connection
Flared connection
Frexible tube
Refrigerant pipe [9.52(3/8") (With insulation) option
Compressor
Accumulator
Ball Valve
Charge plug
Low pressure switch
High pressure switch
Check plug
Ball Valve (With service port)
Capillary tube For injection
Capillary tube
(O.D. 3.2 I.D. 1.8
- L800) 2pcs
Indoor heat exchanger
Refrigerant pipe [9.52(3/8") (with heat insulator) option
Ball valve (with service port)
Flow of refrigerant
Flow of refrigerant
D.P.R. (Discharge pressure regulator)
Capillary tube
Compressor
Accumulator
(O.D. 3.2 oI.D. 1.8 o L800) o2pcs
Ball valve
Low pressure switch
Charge pIug
Check pIug
High pressure switch
Outdoor heat exchanger
strainer
Strainer
Muffier
strainer
Flexible tube
Flared connection
Flared connection
Refrigerant pipe [15.88(5/8") (With insulation) option
Refrigerant pipe [15.88(5/8")
(With insulation) option
PE-3EJA2.TH / PU-3VJA1.TH, PU-3YJA1.TH, PU-3NJA1 PE-3EJA3.TH, / PU-3NJA1
Unit : mm
PE-3EJA3.TH / PU-3VJC.TH, PU-3YJC.TH
25
Indoor heat exchanger
Outdoor heat exchanger
Flared connection
Flexible tube
Compressor
Flared connection
High pressure switch
Low pressure switch (only PU-5,6TJSA
1
)
Refrigerant pipe [
9.52 (3/8")
(With insulator) option
OUTDOOR UNIT
PE-5EJSA
2
.TH
PE-6EJSA
2
.TH
PU-5 type PU-6 type
Ball valve
Check plug
Charge plug
Accumulator
INDOOR UNIT
PE-4EJSA2.TH PU-4 type
Indoor heat
exchanger
Outdoor heat
exchanger
Indoor coil thermistor RT2
Distributor with strainer
Indoor coil thermistor RT2
Distributor with strainer
Flared connection
Flared connection
Flexible tube
Compressor
(Only PU-4TJSA, 4YJSA)
Accumulator
Ball Valve
Charge plug
Low pressure switch
High pressure switch
Check plug
Ball Valve (With service port)
Capillary tube For injection
Capillary tube
(O.D.3.2 I.D.1.8
- L1360) 2pcs
Capillary tube PU-5Y·TJSA (O.D. 4.0 oI.D. 2.4 – L400) PU-6Y·TJSA (O.D. 4.0 oI.D. 2.4 – L200)
Ball valve (with service port)
Capillary tube PU-5Y·TJSA (O.D. 4.0 oI.D. 2.4 – L840)o2pcs PU-6YJSA (O.D. 4.0 oI.D. 2.4 – L1200)o2pcs PU-6TJSA (O.D. 4.0 oI.D. 2.4 – L740)o2pcs
Strainer
DPR
Thermal switch
Refrigerant pipe [
19.05 (3/4")
(With insulator) option
Refrigerant pipe [
9.52(3/8")
(With insulator) option
Refrigerant pipe [
19.05(3/4")
(With insulator) option
Strainer
Muffler
Flow of refrigerant
Flow of refrigerant
PE-4EJSA2.TH / PU-4VLJSA1.TH, PU-4YJSA1.TH, PU-4TJSA2
Unit : mm
PE-5EJSA2.TH / PU-5YJSA.TH, PU-5TJSA1 PE-6EJSA2.TH / PU-6YJSA.TH, PU-6TJSA1
26
OPERATION FLOW-CHART9
FAN OPERATION
FAN
POWER SUPPLY
Live
ON/OFF
button ON
TIMER MODE
button ON
During
operation
AUTO STOP lamp ON AUTO START lamp ON
Auto start timer Press / 1 12Hr up Press / 12 1Hr down
Abnormal
operation mode
MODE SELECT
button
EMERGENCY
ALL STOP
Self-diagnostic function
Indicate & Memory
Protection device
Self hold
Protection device
Self hold reset
COOL OPERATION
DRY OPERATION
POWER lamp ON
NO
NO
NO
NO
NO
NO
NO
DRY
COOL
YES
YES
YES YES
YES
YES
YES
<Note 1>
<Note 3>
<Note 2>
<Note 5>
<Note 4>
Auto stop timer Press / 1 12Hr up Press / 12 1Hr down
Set time ­Elapsed time=0
Set time ­Elapsed time=0
1. Main operation
Note 1. Refer to page 33 for timer mode details. Note 2. The unit starts operation by pressing the ON / OFF switch when unit is OFF.
During operation, the unit stops operation by pressing the ON / OFF switch. In addition, operation can be turned ON / OFF with the centralized remote controller or the remote switch.
Note 3. The factors which cause "abnormal operation mode" are as follows.
Outdoor unit abnormal operation.
Fault of room temperature thermistor (RT1).
Fault of indoor coil thermistor (RT2).
Indoor coil frost protection mode.
Drain water overflow prevention mode.
Note 4. The indoor fan runs on the low speed for 1 minute to eliminate remaining heat. Note 5. The compressor will not start for 3 minutes after the stop to protect the compressor.
27
2. COOL operation
3-minute
time delay
Compressor start
3 minutes elapse
Compressor
start 10 minutes
elapse
Compressor
start 16 minutes
elapse
6-minute
time delay
Coil frost
protection
Coil frost
prevention
Indoor coil
temperature
1°C or below
Indoor coil
temperature 10 °C
or more
3-minute time delay
Coil frost
prevention release
Coil frost
prevention set
Range C
Allowance release
Compressor ON Compressor OFF
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
NO
NO
NO
NO
<Note 6>
<Note 7>
<Note 8>
Compressor
thermostat ON
Allowance release
Allowanse
Allowanse set
6-minute time delay
Coil frost
protection
check mode
Continue 1 minute
Fan speed LOW
Fan speed LOW
5 minutes elapse
Outdoor unit abnor-
mality check mode
Note 6. The thermostat is continuously ON during the test run. Note 7. Refer to page 31 for coil frost protection. Note 8. Range A : Indoor coil temperature is more than 5 degrees above room temperature.
Range B : Indoor coil temperature is within 5 degrees either way of room temperature. Range C : Indoor coil temperature is more than 5 degrees below room temperature.
28
3. DRY operation
Compressor ON
Compressor OFF
10 minutes completed
Compressor ON
3 min.elapse
Compressor
themostat ON
Compressor
thermostat ON
Compressor ON
time completed
Fan stop
Compressor OFF
Compressor ON
time set
Compressor ON
Fan speed LOW
Compressor OFF
10-minute timer start
Room temperature
18 C or below
NO
NO
NO
NO
NO
NO
NO
YES
YES
YES
YES
YES
YES
YES
YES
YES
<Note 6>
<Note 10>
<Note 6>
<Note 11>
<Note 12>
<Note 12>
3-minute
time delay
Note 10. When the room temperature is 18°C or below, the compressor can not turn ON. When the room temperature rises to
19°C or above, the compressor will start operation after a 3-minute time delay. Note 11. Refer to page 32 for the compressor operation time. Note 12. In DRY operation, the indoor fan runs on the low speed during the compressor ON and stops during the compressor
OFF.
29
10 MICROPROCESSOR CONTROL
MITSUBISHI ELECTRIC
12 11 10
9 8 7 6 5 4 3 2 1
29 28 27 26 25 24 23 22 21 20 19 18
TIMER TEMP
TIMER/TEMP.
UP
DOWN
POWER
COOL
ON/OFF
MODE
SELECT
FAN
SPEED
TIMER MODE
DRY FAN
HIGH LOW
AUTO STOP
START
1. OUTLINE OF MICROPROCESSOR CONTROL
INPUT to remote controller
ON-OFF switching.
COOL-FAN selector switching.
HIGH-LOW fan speed switching.
TIMER mode selector switching.
Thermostat setting.
Timer setting.
Self-diagnostic troubleshooting.
Test run switching.
Indoor unit
REMOTE CONTROLLER
Transmits and receives orders.
12
12V DC
OUTPUT to remote controller
Indication lamps lights.
Polar, twelve (12) - core cable Maximum length 50m (164ft)
INPUT from indoor unit
Room temperature thermistor (RT1)
Indoor coil thermistor (RT2)
OUTPUT to indoor unit
Fan : ON-OFF.
Fan speed : HIGH-LOW.
Emergency stop.
INPUT from outdoor unit
Compressor protection device working
INDOOR CONTROLLER BOARD
Receives orders from remote controller and temperature data from indoor unit.
Processes orders and data.
Transmits the power of indication lamp to remote controller.
Controls indoor and outdoor operation.
Self-diagnostic function.
W System control operation.<Optional> W Emergency operation.
Non - polar, two (2) - core cable
Outdoor unit
12V DC
OUTDOOR UNIT
Receives order from indoor controller.
Emergency stop.
OUTPUT to outdoor unit
Compressor motor and outdoor fan motor : ON - OFF
30
2. INDOOR UNIT CONTROL
TIMER
MITSUBISHI ELECTRIC
12 11 10
9 8 7 6 5 4 3 2 1
29 28 27 26 25 24 23 22 21 20 19 18
TIMER TEMP
TIMER/TEMP.
UP
DOWN
POWER
COOL
ON/OFF
MODE
SELECT
FAN
SPEED
TIMER MODE
DRY FAN
HIGH LOW
AUTO
STOP START
2-1 COOL operation
Steady Flash OFF
<COOL operation time chart>
Operation starts by POWER button ON.
ON
Thermostat
Indoor fan
OFF
ON
OFF
<How to operate>
1 Press POWER ON / OFF button. 2 Press MODE SELECT button to set operation mode to COOL. 3 Check lamp is ON and set desired temperature with UP or DOWN but-
TEMP
ton.
NOTES : 1. When lamp is ON, press DISPLA YSELECT button to change
the display to temperature mode.
2. Set temperature changes by 1°C in the range 18 ~ 29°C each time UP or DOWN button is pressed.
3. The lighting lamp shows the set temperature, and the flashing lamp shows the room temperature. When the room temperature is equal to the set temperature, the lamp keeps lighting, 0.5 seconds brightly and 0.5 seconds faintly.
Room temperature becomes equal to set temperature.
Room temperature rises above set temperature.
LOW or HIGHLOW or HIGH
Operation stops by POWER button OFF.
ON
Compressor
OFF
MIN. 3 minutes 1
W1 Even if the room temperature rise above the set temperature during this period, the compressor will not start until this
period has ended.
(1) Compressor control
1 3 minute time delay
To prevent overload, the compressor will not start within 3 minutes after stop.
2 The compressor runs when the room temperature is higher than the set temperature.
The compressor stops when the room temperature is equal to or lower than the set temperature.
3 The compressor stops in check mode or during protective functions. 4 Coil frost prevention
To prevent indoor coil frost, the compressor will stop when the indoor coil thermistor (RT2) reads 1°C or below after the com­pressor has been continuously operated for 16 minutes or more. The coil frost prevention is released under any of the fol­lowing conditions.
The indoor coil thermistor rises to 10°C or above.
The room temperature becomes equal to or lower than the set temperature.
COOL mode is stopped or changed to another mode.
NOTE : By cutting the jumper wire JRO2 on the indoor controller board, the temperature to start coil frost prevention changes
from 1°C to -3°C.
5 Coil frost protection
When indoor coil temperature becomes -15°C or below, coil frost protection will proceed as follows.
<Start condition>
After the compressor has been continuously operated for 3 minutes or more, and the indoor coil temperature has been
-15°C or below for 3 minutes, the coil frost protection will start.
<Coil frost protection>
Compressor stops for 6 minutes, and then restarts. lf the start condition is satisfied again during the first 10 minutes of compressor operation, both the indoor and outdoor units stop, and the remote controller displays this occurrence.
<Termination conditions>
Coil frost protection is released when the start condition is not satisfied again during the allowance, or when the COOL mode stops or changes to another mode.
31
TIMER
(2) Indoor fan control
Indoor fan speed LOW/HIGH depends on the remote controller setting. However, if an outdoor unit abnormality is detected, the indoor fan speed will be LOW, regardless of the remote controller setting.
(3) Detecting abnormalities in the outdoor unit
After the compressor has been continuously operated for 3 minutes, if the difference between the difference between the indoor coil temperature and room temperature is out of RANGE C, for 1 minute, the indoor fan speed will turn to LOW. Five minutes later, if the difference is in RANGE C, the fan speed will return to the set speed. If the dif ference is still out of RANGE C, the outdoor unit is deemed abnormal. Thus, the compressor will stop and the trouble location is indicated on the remote controller. RANGE A: Indoor coil temperature is more than 5 degrees above room temperature. RANGE B : Indoor coil temperature is within 5 degrees either way of room temperature. RANGE C : Indoor coil temperature is more than 5 degrees below room temperature.
2-2 DRY operation
<How to operate>
1 Press POWER ON / OFF button. 2 Press MODE SELECT button to set operation mode to DRY.
TIMER TEMP
TIMER/TEMP.
29
12
28
11
27
10
26
9
25
8
24
7
23
6
22
5
21
4
20
3
19
2
18
1
UP
DOWN
POWER
ON/OFF
COOL
MODE
DRY
SELECT
FAN HIGH
FAN
SPEED
LOW
AUTO STOP
TIMER MODE
START
MITSUBISHI ELECTRIC
Steady Flash OFF
3 Check lamp is ON and set desired temperature with UP or DOWN but-
ton.
NOTES : 1. When lamp is ON, press DISPLA YSELECT button to change
TEMP
the display to temperature mode.
2. Set temperature changes by 1°C in the range 18 ~ 29°C each time UP or DOWN button is pressed.
3. The lighting lamp shows the set temperature, and the flashing lamp shows the room temperature. When the room temperature is equal to the set temperature, the lamp keeps lighting, 0.5 seconds brightly and 0.5 seconds faintly.
(1) Compressor control
1 3-minute time delay
To prevent overload, the compressor will not start within 3 minutes after stop.
2 The compressor runs when the room temperature is higher than the set temperature.
The compressor stops when the room temperature is equal to or lower than the set temperature.
3 The compressor stops in check mode or during protective functions. 4 The compressor will not start when the room temperature is below 18°C.
The compressor starts intermittent operation when the power is turned ON with room temperature above 18°C. The com­pressor ON / OFF time depends on the thermostat ON / OFF and the room temperature as follows. After 3 minute compressor operation,
If the room temperature thermistor reads above 28°C with thermostat ON, the compressor will operate for 6 more minutes and then stop for 3 minutes.
If the room temperature thermistor reads 26 °C ~28 °C with thermostat ON, the compressor will operate for 4 more minutes and then stop for 3 minutes.
If the room temperature thermistor reads 24°C ~26°C with thermostat ON, the compressor will operate for 2 more minutes and then stop for 3 minutes.
If the room temperature thermistor reads below 24°C with thermostat ON, the compressor will stop for 3 minutes.
If the thermostat is OFF, regardless of room temperature, the compressor will stop for 10minutes.
5 Coil frost protection
Coil frost protection in DRY operation is the same as in COOL operation.
(2) Indoor fan control
The indoor fan runs on LOW speed during compressor operation. The fan speed cannot be changed with the remote con­troller. Also, the indoor fan does not run during compressor OFF.
(3) Detecting abnormalities in the outdoor unit
An abnormality in the outdoor unit can not be detected in DRY operation.
32
2-3 FAN operation
TIMER
TIMER
<How to operate>
1 Press POWER ON / OFF button. 2 Press MODE SELECT button to set operation mode to FAN.
TIMER TEMP
TIMER/TEMP.
29
12
28
11
27
10
26
9
25
8
24
7
23
6
22
5
21
4
20
3
19
2
18
1
UP
DOWN
POWER
ON/OFF
COOL
MODE
DRY
SELECT
FAN HIGH
FAN
SPEED
LOW
AUTO
STOP
TIMER MODE
START
MITSUBISHI ELECTRIC
NOTES : Temperature can not be set in FAN operation.
Steady Flash OFF
(1) Indoor fan control
The indoor fan speed LOW / HIGH depends on the remote controller setting.
2-4 TIMER operation
<Timer function>
AUTO STOP ·········Air conditioner stops after the set time lapses. AUTO START ········Air conditioner starts after the set time lapses.
TIMER TEMP
TIMER/TEMP.
29
12
28
11
27
10
26
9
25
8
24
7
23
6
22
5
21
4
20
3
19
2
18
1
UP
DOWN
POWER
ON/OFF
COOL
MODE
DRY
SELECT
FAN HIGH
FAN
SPEED
LOW
AUTO
STOP
TIMER MODE
START
MITSUBISHI ELECTRIC
Steady Flash OFF
<How to operate
1 While lamp is lighting, press TIMER MODE button.
2 Set the time for the AUTO STOP timer with the UP or DOWN button.
NOTE : The time setting is in 1 hour units up to 12 hours.
3 With the lapse of time, the timer lamps turn OFF one by one, showing the remain-
ing time.
4 To cancel the AUTO STOPtimer and continue operation, press the TIMER MODE
button. To cancel the AUTO STOP timer and stop operation, press the POWER ON/OFF button.
<How to operate AUTO START timer>
1 While lamp is OFF, press TIMER MODE button.
AUTO STOP timer>
POWER
POWER
and lamps turn ON.
and lamps turn ON.
TIMER
2 Set the time for the AUTO START timer with the UP or DOWN button.
NOTE : The time setting is in 1 hour units up to 12 hours.
3 With the lapse of time, the timer lamps turn OFF one by one, showing the remain-
ing time.
4 To cancel the AUTO STARTtimer and keep the unit OFF , press the TIMER MODE
button. To cancel the AUTO START timer and start operation, press the POWER ON / OFF button.
2-5 Test run
The unit starts the test run by pressing both the UP and DOWN buttons simultaneously for more than two seconds during
lamp ON or the unit OFF.
The test run automatically stops in 2 hours.
Set temperature is not displayed during test run.
Room temperature is displayed by the flashing green lamp when DISPLAY SELECT button is pressed.
The test run can be released by pressing the POWER ON / OFF or the TIMER MODE button.
<Initial setting>
The units are set as follows by the factory.
1) AUTO START set time : 12hours AUTO STOP set time : 12 hours
2) Initial operation mode : FAN
3) Fan speed : LOW
4) Set temperature : 28°C
33
2-6 Self-diagnostic function
TEMP
! When trouble occurs during operation, the unit stops
and displays the trouble location with the timer lamps on the remote controller. All the other lamps are OFF normally.
@ To activate the self-diagnostic function for service,
press the UP and DOWN buttons simultaneously for more than two
seconds during operation with lamp ON
# The timer lamps show the latest trouble. Trouble data
is memorized until the next trouble occurs, even when the breaker turns OFF.
$ All buttons except the POWER ON/OFF are unavail-
able during the self-diagnostic mode.
% To release the self-diagnostic mode, press the
POWER ON /OFF button.
2-7 Emergency operation
When the remote controller or microprocessor malfunc­tions and no other trouble exists, emergency cooling operation is available by setting the dip switch on the indoor controller board. [Check items] ! Make sure the compressor and the fans are running
normally.
@ Locate the trouble with the self-diagnostic function. If
the self-diagnostic function indicates that the protec­tion device (such as coil frost protection) is functioning, the sources must be removed before attempting emer­gency operation. Emergency operation ON / OFF is activated not with
the remote controller but with the circuit breaker. [Emergency operation procedure] ! Cooling operation is available by setting the dip switch
(SW3<I.B>)
controller board. @ To start emergency operation, turn the outdoor side cir-
cuit breaker ON first, and then the indoor side circuit
breaker ON. # During emergency operation, the indoor fan runs on
HIGH speed, the compressor runs continuously.
$ Thermostat will not function. % Do not use emergency cooling operation for more than
10 hours, as the indoor coil may freeze.
1 and 2 ON and 3 OFF on the indoor
SW3
ON
OFF
1 2 3
34
2-8 Function of jumper wire and dip switch on indoor controller board
1. Jumper wire
2. Dip switch
...
1 JR1 2 JR2 3 JR3
4 JR4 5 JR5 6 JR6
1 SW1 (Function switch)
Jumper wire for the auto vanes.
Cut JR01 for the unit WITHOUT auto vanes.
...
Jumper wire for the temperature to start coil frost prevention
Cutting JR02 changes the temperature from +1°C to -3°C.
...
Jumper wire for set temperature adjustment in HEAT mode. In HEAT operation, heated air stagnates in the upper part of the room. The indoor unit installed in the upper part of the room will detect the air temperature higher than the actual temperature in the living space. This difference is about 4 degrees. Therefore, the temperature detected by the room temperature thermistor should be corrected 4 degrees down. The unit with JR04 attached will make this adjustment.
...
Jumper wire for the indoor fan speed during thermostat OFF in HEAT mode Cutting JR04 changes the speed from Extra-Low to Low.
...
Jumper wire for detecting abnormalities in the outdoor unit Cutting JR05 makes this detection unavailable. (Occurrence of abnormality can not be detected. )
...
Jumper wire for auto restart function Cutting JR06 makes the auto restart function available.
ON OFF
1 2 3
SW1-1) Switch for power supply
ON : 220V OFF : 230V, 240V
SW1-2) Switch for single or twin control
ON : Twin control OFF : Single control
SW1-3) Switch for unit number in twin control
(This switch is valid when SW1-2 is ON. ) ON : Unit No. 2 OFF : Unit No. 1
2 SW2 (Unit switch)
ON OFF
1 2 3 4
3 SW3 (Emergency operation switch)
Normal operation For emergency cooling
1 2 3
ON OFF
SW2-1) Switch for air conditioner with or without electric heater
SW2-2) Switch for air conditioner with or without heat pump
SW2-3) Switch for function code
SW2-4) Switch for function code
ON OFF
ON : Unit with electric heater OFF: Unit without electric heater
ON : Unit with heat pump OFF: Unit without heat pump
ON : 1 OFF: 0
ON : 1 OFF: 0
1 2 3
35
11
TROUBLESHOOTING
1. SELF-DIAGNOSTIC FUNCTION
! When trouble occurs during operation, the unit stops and enters the self-diagnostic mode, and displays the trouble loca-
tion with the timer lamps on the remote controller. All the other lamps are OFF.
@ To activate the self-diagnostic function for service, press the UP and DOWN buttons simultaneously for more than two
TEMP.
seconds during operation with lamp ON.
# The timer lamps show the latest trouble. Trouble data is memorized until the next trouble occurs, even when the breaker
turns OFF. To clear the memory, press the UP and DOWN buttons simultaneously for more than two seconds during the test run.
$ All buttons except the POWER ON/OFF button are unavailable during the self-diagnostic mode. % To release the self-diagnostic mode, press the POWER ON/OFF button.
Unit
Transmission error
12
12
TIMER
TEMP.
29
29
Trouble location
in twin control
Outdoor unit
Cause
Wrong wiring between No. 1 and No. 2 units
Poor connector contact
Wrong wiring between
indoor/outdoor units
Outdoor unit abnormality detection
Malfunction of outdoor coil thermistor
Reversed phase detected
Measures
Check dip switch setting
Check wiring
Check wiring
Check outdoor unit
Check outdoor coil thermistor
11
11
10
10
9
9
8
8
7
7
6
6
5
5
4
4
3
3
2
2
1
1
28
28
27
27
26
26
25
25
24
24
23
23
22
22
21
21
20
20
19
19
18
18
Unit
No.1
Unit
No.2
Unit
No.1
Unit
No.2
Unit
No.1
Unit
No.2
Unit
No.1
Unit
No.2
Unit
No.1
Unit
No.2
Room
temperature
thermistor
(RT1)
Indoor coil
thermistor
(RT2)
Drain sensor
(DS)
Drain
overflow
protection
Coil frost
or overheat
prevention
Poor connector contact
Thermistor malfunction
Poor connector contact
Thermistor malfunction
Poor connector contact
Thermistor malfunction
Drain pump malfunction
Drain sensor improperly
mounted
Air passage short cycle
Air filter clogged
Indoor fan malfunction
Check connector
Check thermistorNo trouble ➔ replace indoor
Check connector
Check thermistorNo trouble ➔ replace indoor
Check connector
Check thermistorNo trouble ➔ replace indoor
Check drain pump
Check drain sensorNo trouble ➔ replace indoor
Remove blockage
Check air filter
Check indoor fan
}
controller board.
}
controller board.
}
controller board.
}
controller board.
(Indicates that the unit is in self-diagnostic mode)
36
2. OTHER TROUBLES AND CAUSES
Power ON/OFF button does not work.
Indoor/outdoor connect­ing wire is connected incorrectly. Indoor/outdoor connect­ing wire shorts. Compressor protector is damaged. Dicer is broken.
Remote controller is damaged. Transmission wire is poorly connected.
Transmission wire is
damaged.
Connector is poorly
connected.
37
3. How to check the parts PE-EJ(S)A.TH
1 2 3
1 2 3 4
CNT T CN4T
RED
BRN
WHT
YLW
BLK
BLU
YLW
RED
ORN
Capacito
WHT
BLK
BLU
Protector
123456
713 5
0
10
20
30
40
50
-20 -10 0 10 20 30 40 50
< Thermistor for lower temperature >
Temperature (:)
Resistance (K")
Parts name Check points
Room temperature thermistor
(RT1)
Indoor coil thermistor
(RT2)
Disconnect the connector, then measure the resistance using a tester. (Surrounding temperature 10°C~30°C)
Normal
4.3k'~9.6k'
Abnormal
Open or short
(Refer to the thermistor)
Trans
Disconnect the connector and measure the resistance using a tester.
CNT(1)-(3) CN4T(1)-(2) CN4T(3)-(4)
Fan motor
Measure the resistance between the terminals using a tester. (Surrounding temperature 20°C)
Motor terminal
or
Relay connector
WHT-BLK
BLK-BLU BLU-YLW YLW-RED
<Thermistor Characteristic graph>
Normal
WHT App. 135' BRN App. 0.5~1.0' RED App. 1.0~2.0'
3EJA2, 3EJA3
46.38'
17.25'
18.37'
(BLU-RED)
Abnormal
Open or short
Normal
PE-EJ(S)A
4EJSA2
20.63'
8.05'
3.18'
16.02'
5EJSA2, 6EJSA2
15.26'
5.118'
2.648'
14.49'
Abnormal
Open or short
Thermistor for lower temperature
Thermistor R0=15k' ±3% Fixed number of B=3480k' ±2%
Rt=15exp { 3480( ) }
0: 15k' 10: 9.6k' 20: 6.3k' 25: 5.2k' 30: 4.3k' 40: 3.0k'
Room temperature thermistor(RT1) Indoor coil thermistor(RT2)
1
273+t
1
273
38
12
DISASSEMBLY PROCEDURE
PE-3EJA2.TH PE-3EJA3.TH
OPERATING PROCEDURE PHOTOS&ILLUSTRATIONS
1. Removing the drain pan
! Unscrew each set screw on the right and left, and remove
the drain pan pushing it toward the back.
(See Photo 1)
2. Removing the electrical parts
! Remove the electrical parts cover.
(set screw 2) and the parts as blow (See Photo 2)
Indoor controller board
Transformer
Run capacitor
Fuse (6.3A)
Terminal block
Room temperature thermistor
(See Photo 3)
Photo 1
Drain pan
Photo 2
Room temperature thermistor
Set screw (for drain pan)
Electrical
parts cover
Set screw
3. Removing the indoor coil thermistor
! Remove the drain pan. @ Remove the electrical parts cover. # Remove the set wire of the indoor coil thermistor.
(See Photo 1)
(See Photo 2 )
(See Photo 4)
Photo 3
Connector
Terminal block
Photo 4
Indoor controller board
Transformer
Run capacitor
Indoor coil thermistor
39
Fan motor
OPERATING PROCEDURE PHOTOS
4. Removing the fan
Note : Perform the following with the indoor unit lowered down
to the floor.
! Remove the drain pan. (See Photo 1) @ Disconnect the connector for the fan motor.
(See Photo 3)
# Take out the fan after removing the 7 set screws of the fan
plate. (See Photo 5 or 6.)
$ Unscrew four set screws of the bell mouth and remove the
bell mouth.
(See Photo 7.)
% Loosen the set screw of the fan to pull out the sirocco fan.
(See Photo 7.)
^ Unscrew the four set screws of the motor fitting, and
remove the fan motor. (See Photo 8.)
Photo 5
Fan plate
Set screw
Photo 6
Fan motor
Bell mouth
Set screw
Fan casing
Fixture set screw
Sirocco fan
Fan plate
Photo 8Photo 7
Fan casing
Fixture set screw
Fittings
Fan plate
Set screw
Fan motor
40
13
1 2 3 4 5 6 7 8
9 10 11 12 13 14
(R300B098F04)
(R302D730G01)
(BA02G745G10) (BG00T021B01) (BA00H896G08) (BB02R503G10) (R302G070G01) (BA02L499G04)
2PCS/SET
MF1
Price
Amount
Unit
Q'ty/set
PE-3
EJA1.TH, EJA2.TH, EJA3.TH
No. Part No. Part Name
Specification
Remarks
(Drawing No.)
Wiring
Diagram
symbol
Recom­mended
Q'ty
E07 027 300
— E07 018 500 E07 018 808
— E07 018 505 E07 018 700 E07 027 620
PA6V205-E8INDOOR FAN MOTOR CASING BELL MOUTH SIROCCO FAN LEG FAN PLATE CABINET ASSY AIR OUTLET DUCT FLANGE AIR INTAKE DUCT FLANGE FAN MOTOR LEG MOTOR BEAM RUBBER MOUNT DRAIN PAN HEAT EXCHANGER
1 1 1 1 2 1 1 1 1 1 1 2 1 1
914 3 4 5 7 2 5 6 8
11
10
13
12
1
PARTS LIST
STRUCTURAL PARTS PE-3EJA 1.TH PE-3EJA 2.TH PE-3EJA 3.TH
41
STRUCTURAL PARTS
12 14 6 3 9 8 7 9 10 11
5
4
13
2
1
1 2 3 4 5 6 7 8
9 10 11 12 13 14
1 2 1 1 1 1 1 1 2 1 1 1 1 1
2PCS/SET
(BB00L212G04) (BB02T248G02)
(R302D730G01) (BA00N328G08) (BG00T022B01)
(BB02G686G05) (BA00H896G09) (BB02G810G05)
MF1
Price
AmountUnit
Q'ty/set
PE-4
EJSA1.TH, EJSA2.TH
No. Part No. Part Name
Specification
Remarks
(Drawing No.)
Wiring
Diagram
symbol
Recom-
mended
Q'ty
E07 028 300 E07 018 505 E07 022 500
— — — — —
E07 018 808
— —
— E07 022 700 E07 028 620
PA6V305-EAINDOOR FAN MOTOR RUBBER MOUNT SIROCCO FAN FAN MOTOR LEG MOTOR BEAM BELL MOUTH CASING CABINET ASSY LEG FAN PLATE AIR OUTLET DUCT FLANGE AIR INTAKE DUCT FLANGE DRAIN PAN HEAT EXCHANGER
PE-4EJSA1.TH PE-4EJSA2.TH
42
STRUCTURAL PARTS
5 6 12 14 8 1 4 2 3 10 9 11
13
5
15
7
16
17
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15
16
17
1 1 1 2 2 1 1 1 1 1 1 1 1 1 1 1
1
1 1 1 2 2 1 1 1 1 1 1 1 1 1 1
1 1
(BB00L212G04) (BB02L182G04)
(R302D730G01)
(R300B098F04)
(R300B098F05) (BA02N472G05) (BA00H898G10)
(BG00T022B04)
(BB02L116G12)
MF1
Price
AmountUnit
Q'ty/set
PE-5
EJSA1.TH EJSA
2.TH
PE-6
EJSA1.TH EJSA
2.TH
No. Part No. Part Name
Specification
Remarks
(Drawing No.)
Wiring
Diagram
symbol
Recom-
mended
Q'ty
E07 029 300
— —
E07 018 505
— E07 018 500 E07 023 500
— E07 018 809 E07 018 808
— E07 023 700 E07 029 620 E07 030 620
PA6V400-ED
INDOOR FAN MOTOR FAN MOTOR LEG MOTOR BEAM RUBBER MOUNT BELL MOUTH SIROCCO FAN SIROCCO FAN CASING CASING FAN PLATE AIR OUTLET DUCT FLANGE LEFT LEG RIGHT LEG CABINET ASSY DRAIN PAN HEAT EXCHANGER HEAT EXCHANGER AIR INTAKE DUCT FLANGE
PE-5EJSA1.TH, 6EJSA1.TH PE-5EJSA2.TH, 6EJSA2.TH
43
ELECTRICAL PARTS
1 2 3 4 5 6 7 8
9 10 11 12
1 1 1 1 1 1 1 1 1 1 1 1
I.B
F1,2<I.B>
C1
T TB1 TB2 RT1 RT2
R.B
w1
w1 : [CONTROLLER CASE] is made together with INDOOR CONTROLLER BOARD.
Price
AmountUnit
Q'ty/set
EJ(S)A1.TH, EJ(S)A2.TH, EJA3.TH
No. Part No. Part Name
Specification
Remarks
(Drawing No.)
Wiring
Diagram
symbol
Recom-
mended
Q'ty
E07 027 447 E07 006 382 E07 018 351 E07 027 339 E07 006 375 E07 007 375 E07 027 308 E07 027 307 E07 027 426 E07 027 088 E07 027 089 E07 027 087
250V 6.3A
8.0+/440VAC
3P (L, N, ;) 2P (1, 2)
10m
0.5m
INDOOR CONTROLLER BOARD FUSE INDOOR FAN CAPACITOR TRANSFORMER TERMINAL BLOCK TERMINAL BLOCK ROOM TEMPERATURE THERMISTOR INDOOR COIL THERMISTOR REMOTE CONTROLLER REMOTE CONTROLLER COVER REMOTE CONTROLLER CABLE CABLE (FOR BOARD)
PE-3,4,5,6
PE-3EJA1.TH, PE-4EJSA1.TH, PE-5EJSA1.TH, PE-6EJSA1.TH PE-3EJA2.TH, PE-4EJSA2.TH, PE-5EJSA2.TH, PE-6EJSA2.TH PE-3EJA3.TH
44
14
28˚C
26
˚C
8:00
Normal
operation
23:00
Setback
operation
8:00
Normal
operation
Part No. Pipe length Pipe size O.D. Connection method
PAC-05FFS-E
5m
PAC-07FFS-E
7m
Liquid : ø9.52 Gas : ø15.88
Indoor unit : Flared Outdoor unit : Flared
PAC-10FFS-E
10m
PAC-15FFS-E
15m
Part No.
Length
PAC-905EC
12m
PAC-906EC
20m
PAC-918EC
30m
PAC-919EC
50m
Part No.
Model Name
PAC-SK65PT (with set back function)
Program timer
Part name Part No. Exterior dimensions Installation Type of clock Clock accuracy Display - Time
- Week
- Timer Program cycle Timer setting unit No. of set points Power rating Set back function
Program timer PAC-SK65PT 120 x 120 x 15mm Wall mount Quartz ±50s / month Liquid crystal display Liquid crystal display Liquid crystal display 24 hours 30 minutes 48 / day 5V DC Provided
Part No. Pipe length Pipe size O.D. Connection method
PAC-SC51PI-E
5m
PAC-SC52PI-E
7m
Liquid : ø9.52 Gas : ø19.05
Indoor unit : Flared Outdoor unit : Flared
PAC-SC53PI-E
10m
PAC-SC54PI-E
15m
OPTIONAL PARTS
1. REFRIGERANT PIPES
Service Ref. : PE-3EJA2.TH / PE-3EJA3.TH
Service Ref. : PE-4EJSA2.TH, PE-5EJSA 2.TH, PE-6EJSA 2.TH
Note 1. How to connect refrigerant pipes.
Factory supplied optional refrigerant piping contains refrigerant at the above atmospheric pressure. As long as connec­tion takes no more than 5 minutes, no air will enter, and there will be no need for air purging. Remove the blind caps and make the connections within 5 minutes. After the connections for the indoor and outdoor units are made, open the stop valve on the outdoor unit to allow refrigerant gas to flow. If piping length exceeds 20m, an additional charge of refrigerant is needed.
Note 2. The following main parts are contained in the optional refrigerant piping kit.
Heat insulating cover, vinyl tapes, nipples, sleeve, flange (for wall hole).
2. REMOTE CONTROLLER EXTENSION CABLE
When installing the remote controller at a distance from the air conditioner, use the designated extension cable with connec­tor.
3. TIMER
When using a program timer, a program timer adapter (PAC-825AD) is also needed.
3-1 Program timer specifications
3-2 Feature of program timer
(1) Daily timer function
Daily timer can be set in 30 minute units up to 24 hours. Each unit can be set for unit ON, unit OFF, or setback operation.
(2) Setback operation. (PAC-SK65PT)
Set back operation is useful for reducing running costs e.g. : At a hotel with a 24-hour system
(3) Weekly timer function
Daily timer function can apply to each day of the week.
8:00~23:00 Cooling operation with set temperature at 26°C
23:00~8:00 Setback operation with 2 degrees of setback As shown in the chart on the right, the set temperature rises 2 degrees automatically during the setback operation. When the set­back operation ends, normal operation will begin.
45
Centralized
Remote
controller
Use 6-wire cable
Connect to indoor unit 2-wire cable
Connect to CN1 Connect to CN1
Program
timer
3-3 How to connect program timer
MITSUBISHI ELECTRIC
SET MONITOR
BACK
ON OFF
ON OFF
AHEAD
BACK
AHEAD
! Install the program timer next to the remote controller the same way as the remote controller is installed. @ Connect the program timer and the remote controller with a 6-wire cable as shown in the figure below
NOTE : While the program timer is connected to the remote
controller, the 24-hour ON / OFF timer on the remote controller will not operate.
3-4 Names and functions <PAC-SK65PT>
Mode display
Current time
display
Current day display
Weekly timer
display
Mode selector button : Use this button to select "MONITOR" or
"SET" mode.
"MONITOR" : Indicates the current timer setting. All buttons except
SET/MONITOR will not work. This is the
normal status.
"SET" : "SET" is used to set the time, change of day of the week, and
program the daily and weekly timer.
Clock adjustment button : Used to adjust the current time. Press AHEAD
button to advance the time. Each time the button is pressed the time advances by 1 minute, and press­ing continuously advances 1 minute at a 0. 5 second interval. When the lower digit of the minutes becomes 0 the indication advances in 10 minute units. BACK button is used for reversing the time. Each time the button is pressed the time reverses by 1 minute, and pressing continuously reverses the time by 1 minute at a 0. 5 second interval. When the lower digit of the minute becomes 0 the indication reverses in 10 minutes units.
Daily timer display
NOTE : display above is
only an example.
Day setting button : Used to set the day of the week.
Pressing button changes the day.
light displays in the order of S ➝ M ➝ T ➝ W.
Weekly timer button : Used to set the weekly timer.
Set back button : Used to set the set back amount.
Set back can be set in the range of 1 to 9°C in 1°C unit.
Daily timer button : Used to set the daily timer in 30 minute units.
46
4. CENTRALIZED REMOTE CONTROLLER
Allows individual or combined control of up to 16 units.
Part No. PAC-805RC
4-1 Dimensions
ENGAGED
GROUP
12345678910
ACTIVE BYPASS
DUAL CENTRAL
GROUP SELECTION
PROGRAM TIMER
CONTROLLER OPERATION
117
POWER ON/OFF
AHEAD
BACK
ACTIVE
BYPASS
DUAL
CENTRAL
MITSUBISHI ELECTRIC
4-2 Names and Functions
"ENGAGED" indicator When this indicator is lit, transmission is in progress and all switches are inoperative.
DUAL/CENTRAL switch This change-over switch controls the oper-
ation of the accessory remote controller. "DUAL"
Instructions from both the accessory remote controller and the centralized remote controller are valid. (Priority is given to the last instruction received.)
117
12
ENGAGED
GROUP
12345678910
ACTIVE BYPASS
DUAL CENTRAL
ENGAGED
GROUP
12345678910
ACTIVE BYPASS
DUAL CENTRAL
GROUP SELECTION
PROGRAM TIMER
CONTROLLER OPERATION
BACK
ACTIVE BYPASS
DUAL
CENTRAL
113
GROUP SELECTION
PROGRAM TIMER
CONTROLLER OPERATION
POWER ON/OFF
AHEAD
23.5
BACK
ACTIVE
BYPASS
DUAL
CENTRAL
10 9 8 7 6 5 4 3 2 1
56.5
Unit : mm
11
POWER ON/OFF
AHEAD
8
113
POWER ON/OFF switch Operation ON/OFF switch.
BACK AHEAD buttons These buttons are used to designate the attached unit(s). (They designate the unit to be centrally controlled.)
When group “00” is designated; col­lective ON/OFF instruction is sent to all units.
When group ¨01¨ - ¨16¨ is designated; ON/OFF instruction is sent only to the designated units.
"CENTRAL" ON/OFF switching by the accessory remote controller is invalidated. Operation is controlled by the centralized remote con­troller only. Initial setting is "DUAL".
MITSUBISHI ELECTRIC
ACTIVE/BYPASS switch This change-over switch for the pro­gram timer. (It selects the timer operation on the program timer.) Use “BYPASS” when a program timer is not connected. “ACTIVE”
LCD Matrix Display This display indicates the operational sta­tus of all connected units either by steady lighting or by flashing.
The switch turns ON / OFF commands given from the program timer automati­cally. “BYPASS” ON / OFF Operation is controlled by the centralized remote controller only. Initial setting is “BYPASS”.
Independent “DUAL / CENTRAL” and “ACTIVE / BYPASS” setting of all the groups is possible. When power supply to the centralized remote controller is cut, due to a power failure, for example all settings return to original “DUAL” and “BYPASS”.
47
TERMINAL-BLOCK FOR TRANSMISSION
TERMINAL-BLOCK OF POWER SUPPLY
Tie-lap
TRANSFORMER
Fuse(5A)
Tle-lap
LNE
Transmission
(W) (BN) (R) (O) (Y)
T
200
220
230
240
5A
L N E
POWER SUPPLY
Wiring has to be change when a 200,230 or 240 power is used.
BACK
ACTIVE BYPASS
POWER ON/OFF
DUAL
CENTRAL
AHEAD
ENGAGED
GROUP
ACTIVE BYPASS
GROUP SELECTION
PROGRAM TIMER
CONTROLLER OPERATION
DUAL CENTRAL
12345678910
10 9 8 7 6 5 4 3 2 1
To adaptor's terminal-block
Centralized remote controller
Non-polar, two-wire cable
To adaptor's terminal-block
Power supply board box
BACK
ACTIVE BYPASS
POWER ON/OFF
DUAL
CENTRAL
AHEAD
ENGAGED
GROUP
ACTIVE BYPASS
GROUP SELECTION
PROGRAM TIMER
CONTROLLER OPERATION
DUAL CENTRAL
12345678910
10 9 8 7 6 5 4 3 2 1
Dip switch SW17
Centralized remote controller
Power supply board
4-3 Connection method
(1) Connections in the power supply cord.
1. Connect the power supply cord to the power supply terminal-block and fix it in-place with a tie-lap. Connect a single phase 200V AC (220, 230, 240V) to LN. As E is the GND terminal, be sure to ground the earth wire.
2. Connect the transmission line to the transmission terminal-block and fix it in-place with a tie-lap. Use a Ø1.6 (AWG 14) or above two-wire cable for the transmission line. CAUTION : Never connect the power supply cord to the transmission terminal-block.
(2) Connection method of centralized remote controller and power supply board.
1. Connect the centralized remote controller and power supply board with a non-polar, two-wire cable.
2. Wiring diagram 3. Set the max. address number with the dip switch SW17
of the centralized remote controller.
48
5. PROGRAM TIMER ADAPTER
This adapter is needed when a program timer (PAC-SK65PT) or the centralized remote controller (PAC-805RC) is used.
Part No. PAC-825AD
5-1 Parts included
ADAPTER ··························1P 3-core cable···························1P
Length : 2m (6' 7") Length : 2m (6' 7")
4-core cable···························1P
Length : 2m (6' 7") Length : 2m (6' 7")
3-core cable···························1P
5-core cable ···························1P
5-2 Connection method
Connection and wiring methods differ with the type of the indoor unit used. Confirm the type before carrying out the work.
(1) Connections in the adapter Box
1. Connect the power supply cord to the terminal-block and fix it in-place with a tie-lap. Connect a single phase 200V AC (220, 230, 240V) to L N. As ; is the GND terminal, be sure to ground the earth wire.
2. Connect the transmission line to the transmission terminal-block and fix it in-place with a tie-lap, when a centralized remote controller is being used.
CAUTION : Never connect the power supply cord to the transmission terminal-block
fig.1 fig.2
TERMINAL BLOCK FOR TRANSMISSION
CN22
Dip switch
TRANS CN1 CN21 CN51 CN30 CN42 CN50 CN40
SW1
(AG)
LNE
Tie-lap
Transmission cord
TRANSFORMER
Fuse(5A)
POWER SUPPLY CORD
TERMINAL BLOCK FOR POWER SUPPLY
Tie-lap
Transmission
CN22
TRANS
(W) (B) (Y)
200
220
-240
SW1
T
5A
POWER SUPLLY
L N
49
Adaptor
200~240V AC
3-core cable 5-core cable
52
To program timer or centralized remote controller
Fig.3
CN30 CN50
CN51CN2
Remote controller Indoor unit Max. length of each calbe is 10m.
65
230
22
15
15
86 70
35
27
15
hole
40 80 40 27 18
Fixing screw hole
4- 5.5
95
220
22
35
120
12
30
200
2 2- 2.9
74
7 8
Fig. 4
10
ORN BRN RED
1 2
3
BRN RED
ORN YLW GRN
BRN
RED ORN
YLW GRN
+
+
-
-
-
JST XHP-3
5
2
5
+
-
<Wiring>
CN51
GREEN
RED
BROWN
YELLOW ORANGE
5
1
connector (5P)
Electrical insulation is needed
Optional multiple display adapter
Local wiring
Power supply
The maximum distance between indoor boared and relay is 10m.
X1
X1 RL
X2 GL
X2
(2) Set the address number (from SW1-1 to SW1-6) in
the dip switch when a centralized remote controller is being used. The address is the control number of each unit in the centralized control system. As the address serves as a time-delay device as well, sequential starts (all units are triggered collec­tively by one single ON instruction)must be set with different address numbers (greater than 0) for each
987654321
ON
SW1
Levers No. 1-6 can set the following addresses respectively with binary notations.
Toggle32No.6 ON16No.5 ON8No.4 ON4No.3 ON2No.2 ON1No.1 ON
Address
adapter.
(Ex.1) 3 = 2 + 1 (Ex.2) 9 = 8 + 1 (Ex.3) 15 = 8 + 4 + 2 + 1
10
987654321
10
987654321
10
987654321
ON
(3) Connection from adaptor
5-3 Dimensions
ON
6. TIMER ADAPTER
This adapter is needed for system control and for operation via external contacts.
Part No. PAC-SA89TA-E
ON
7. REMOTE INDICATION ADAPTER
This adapter is used for remote indication (operation / check).
Part No.
PAC-559AD
50
HEAD OFFICE MITSUBISHI DENKI BLDG.MARUNOUCHI TOKYO100-8310 TELEX J24532 CABLE MELCO TOKYO
CCopyright 1997 MITSUBISHI ELECTRIC ENGINEERING CO., LTD. Issued in Jul. 2000. No. OC155 REVISED EDITION-B 1540 Issued in Dec.1997. No. OC155 REVISED EDITION-A 670 Issued in Sep.1997. No. OC155 860 Printed in Japan.
New publication, effective Jul. 2000. Specifications subject to change without notice.
Loading...