EDITION-A.
This manual does not cover the
following outdoor units.
When servicing them, please refer
to the following service manual and
this manual in a set.
[Service Ref.]
OC152 REVISED EDITION-A
13. PARTS LIST··········································41
14. OPTIONAL PARTS ·······························45
1
Air intake duct flange
Air outlet duct flange
Air outlet
Air intake
(sucks the air inside the room into the unit)
Change pointsPE-3EJA2.THPE-3EJA3.TH
COOLING
CAPACITY
24,600 Btu/h
7,200 W
PU-3VJA
1.TH
PU-3YJA
1.TH
2.2kW(PU-3YJA
1.TH)2.4kW(PU-3YJC.TH)
25,600 Btu/h
7,500 W
PU-3VJC.TH
PU-3YJC.TH
OUTDOOR
UNIT
COMPRESSOR
OUTPUT
Change points
Service Ref.
PE-3EJA
2.TH.
PE-3EJA
3.TH.
PE-4EJSA
2.TH.
PE-5EJSA
2.TH.
PE-6EJSA
2.TH.
VJA1.TH
—
—
—
—
YJA1.TH
—
—
—
—
NJA
1
—
—
—
VLJSA1.TH
—
—
—
—
YJSA1.TH
—
—
—
—
TJSA
2
—
—
—
—
YJSA.TH
—
—
—
—
TJSA
1
—
—
—
—
YJSA.TH
—
—
—
—
TJSA
1
—
—
—
—
VJC.TH
—
—
—
—
YJC.TH
—
—
—
—
345
Outdoor unit
6
COMBINATION OF INDOOR AND OUTDOOR UNITS
2
TECHNICAL CHANGE
Differences with PE-3EJA2.TH / PU-3VJA1.TH, PU-3YJA1.TH (OC155 REVISED EDITION-A)
3
PART NAMES AND FUNCTIONS
● Indoor (Main) Unit
3
● Remote controller
MITSUBISHI ELECTRIC
12
11
10
9
8
7
6
5
4
3
2
1
29
28
27
26
25
24
23
22
21
20
19
18
TIMERTEMP
TIMER/TEMP.
UP
DOWN
POWER
COOL
ON/OFF
MODE
SELECT
FAN
SPEED
TIMER
MODE
DRY
FAN
HIGH
LOW
AUTO
STOP
START
Settings remain in effect until changed. Air conditioner
can be operated by simply pushing ON /OFF button
once settings have been made.
Display PanelOperating Panel
TIMER / TEMP.
This button is used to
change between display of
room temperature and display of remaining timer dur-
ON / OFF button
Pushing button starts operation. Pushing again stops
operation. Green lamp
remains lit during operation
ing "AUTO STOP" operation. Green lamps light in
selected display mode.
MODE SELECT button
This button is used to
Lamps display remaining timer time or room
temperature.
Remaining timer time
change between cooling,
ventilation and DRY operation modes. One of three
green lamps lights to indicate mode in effect.
display
Lamps indicate time
remaining until timer stops
timed operation. Green
lamps corresponding to
remaining number of hours
light.
Room Temperature
FAN SPEED button
This button is used to
change between low and
high fan speeds. One of
two green lamps lights to
indicate fan speed in effect.
display
Lamps display temperature
settings and actual room
temperatures.
● Temperature settings;
Green lamps light.
● Temperature in room;
Green lamps flash.
(Example display readings are for explanations
only ; actual display readings will differ.)
Attention :
● Pushing UP and Down buttons together for more than two seconds will initiate "trial run" or "inspection" mode. Avoid pushing
these buttons simultaneously during normal operation. Push ON / OFF button to cancel trial run or inspection mode if initiated by accident.
● All green lamps turn off when air conditioner is stopped.
● Avoid operation of buttons with fingernails or other sharp objects. Sharp objects may scratch operating panel.
UP and DOWN buttons
● Temperature control (While "TEMP" green
lamps is lit.)
Use UP and DOWN buttons to set desired
temperature between 18 and 29°C.
● Timed operation (While green "TIMER"
lamp is lit.)
Use UP and DOWN buttons to set timed
operation between one and twelve hours.
TIMER MODE button
Used for selecting timed
starting or stopping. Green
lamps lights to indicate
timer mode selected.
4
SPECIFICATIONS4
W
Btu/h
W
Btu/h
W
Btu/h
kW
kW
m
3
/min
CFM
m
3
/min
CFM
Pa (mmAq)
Pa (mmAq)
dB
dB
in.
mm (in.)
mm (in.)
mm (in.)
kg (lbs)
kW
W
kW
m
3
/min(CFM)
m
3
/min(CFM)
dB
mm (in.)
mm (in.)
mm (in.)
kg (lbs)
PE-3EJA
2.TH
7,200
24,600
8,100
27,600
6,700
23,000
3.41 / 3.76
PE-3EJA
2.TH
0.2
19 - 22
671 - 777
22 - 26
777 - 918
49 (5)
69 (7)
46 - 48
48 - 50
R1
785 (31)
690 (27-1/6)
428 (16-7/8)
46 (101)
W7 PU-3JA type
2.2
32 / 38
0.085
50 (1,765)
50 (1,765)
52 / 53
870 (34-1/4)
850 (33-7/16)
73 (161)
PE-4EJSA
2.TH
9,800
33,400
10,900
37,200
9,400
32,000
3.59 / 4.69
PE-4EJSA
2.TH
0.3
27 - 34
953 - 1,200
27 - 34
953 - 1,200
62 (6.35)
62 (6.35)
54 - 58
54 - 58
R1
1,055 (41-1/2)
690 (27-1/6)
428 (16-7/8)
58 (128)
W7 PU-4JSA type
2.7
32 / 38
0.065 + 0.065
95 (3,352)
95 (3,352)
54 / 55
870 (34-1/4)
1,258 (49-1/2)
94 (207)
50Hz
60Hz
60Hz
50Hz
60Hz
50Hz
60Hz
W
D
H
50/60Hz
50Hz
60Hz
50/60Hz
W
D
H
Service Ref.
External finish
Fan motor output
Airflow Lo - High
Ex. static pressure at
Hi - notch
Operation control & thermostat
Noise level Low - High W5
Unit drain thread
Dimensions
Weight
Service Ref.
External finish
Refrigerant (R-22) control
Compressor output
Protection devices
Crankcase heater W4
Fan motor output
Rating conditions (JIS B 8616)
NOTE : W4 Capacity of crankcase heater (W) based on 220 volts.
NOTE : W5 Noise level is measured in an unacoustic room based on JIS conditions.
NOTE : W6 V , N ···Inner thermostat, HP switch, LP switch
VL ···Inner thermostat, HP switch, LP switch, thermal switch.
T, Y···Thermal switch, Reversed - phase protector, HP switch, LPswitch
Rating conditions (JIS B 8616)
NOTE : W4 Capacity of crankcase heater (W) based on 220 volts.
NOTE : W5 Noise level is measured in an unacoustic room based on JIS conditions.
NOTE : W6 Y : Inner thermostat, HP switch, Thermal switch
ph 220V / 3ph 380V
ph 220V / 3ph 220V
T : Inner thermostat, HP switch, LP switch, Thermal switch
6
W
Btu/h
W
Btu/h
W
Btu/h
kW
kW
m
3
/min
CFM
m
3
/min
CFM
Pa (mmAq)
Pa (mmAq)
dB
dB
in.
mm (in.)
mm (in.)
mm (in.)
kg (lbs)
kW
W
kW
m
3
/min(CFM)
m
3
/min(CFM)
dB
mm (in.)
mm (in.)
mm (in.)
kg (lbs)
PE-3EJA
3.TH
7,500
25,600
8,100
27,600
6,700
23,000
3.41 / 3.76
PE-3EJA
3.TH
Galvanized sheets
0.2
19 - 22
671 - 777
22 - 26
777 - 918
49 (5)
69 (7)
Remote controller & built-in
46 - 48
48 - 50
R1
785 (31)
690 (27-1/6)
428 (16-7/8)
46 (101)
PU-3VJC.TH, 3YJC.TH, 3NJA
1
Munsell 5Y 7/1
Capillary tube
(V)2.2, (Y)2.4 / (N)2.2
W6
32 / 38
0.085
50 (1,765)
50 (1,765)
52 / 53
870 (34-1/4)
295 + 24 (11-5/8 add 1)
850 (33-7/16)
73 (161)
50Hz
60Hz
60Hz
50Hz
60Hz
50Hz
60Hz
W
D
H
50/60Hz
50Hz
60Hz
50/60Hz
W
D
H
Service Ref.
External finish
Fan motor output
Airflow Lo - High
Ex. static pressure at
Hi - notch
Operation control & thermostat
Noise level Low - High W5
Unit drain thread
Dimensions
Weight
Service Ref.
External finish
Refrigerant (R-22) control
Compressor output
Protection devices
Crankcase heater W4
Fan motor output
Rating conditions (JIS B 8616)
NOTE : W4 Capacity of crankcase heater (W) based on 220 volts.
NOTE : W5 Noise level is measured in an unacoustic room based on JIS conditions.
NOTE : W6 V , N ···Inner thermostat, HP switch, LP switch
Y···Thermal switch, Reversed - phase protector, HP switch, LP switch
TotalElectrical CircuitRefrigerant CircuitIndoor side
Outdoor side
Intake air
temperature
Intake air
temperature
D.B.
W.B.
D.B.
D.B.
W.B.
The unit of pressure has been changed to Mpa based on SI (International System of Units) in accordance with I.S.O.
(International Organization for Standardization).
The conversion factor is : 1(Mpa) =10.2 (OOf/FF)
15
Capacity
Input
Indoor unit Service Ref.
Phase, Hz
Volts
Amperes
Outdoor unit Service Ref.
Phase, Hz
Volts
Amperes
Discharge
pressure
Suction
pressure
Discharge
temperature
Condensing
temperature
Suction
temperature
Ref. pipe
length
Discharge air
temperature
Service Ref.
Mode
W
kW
V
A
V
A
MPa
MPa
:
:
:
m
:
:
:
:
:
(kgf/F)
(kgf/F)
(20.2)
(4.4)
(19.9)
(4.5)
(19.0)
(4.9)
(20.5 )
(4.1)
Cooling
13,500
6.06
1, 60
220
1.99
PU-5TJSA
1
3, 60
220
16.83
1.98
0.43
78.3
51.9
1.6
5
27
19
14.9
35
24
Cooling
14,000
5.65
1, 50
220
2.50
PU-6YJSA.TH
3, 50
380
8.63
1.95
0.44
77.8
50.8
1.7
5
27
19
14.5
35
24
Cooling
12,100
5.10
1, 50
220
2.50
PU-5YJSA.TH
3, 50
380
8.15
1.86
0.48
72.2
49.3
- 0.9
5
27
19
15.5
35
24
Cooling
15,200
6.58
1, 60
220
1.99
PU-6TJSA
1
3, 60
220
18.70
2.01
0.40
81
52.1
- 0.5
5
27
19
14.1
35
24
PE-5EJSA
2.THPE-6EJSA2.TH
PE-5EJSA
2.THPE-6EJSA 2.TH
TotalElectrical CircuitRefrigerant CircuitIndoor side
Outdoor side
Intake air
temperature
Intake air
temperature
D.B.
W.B.
D.B.
D.B.
W.B.
The unit of pressure has been changed to Mpa based on SI (International System of Units) in accordance with I.S.O.
(International Organization for Standardization).
The conversion factor is : 1(Mpa) =10.2 (OOf/FF)
16