Mitsubishi PCH-2GKHA1, PCH-2.5GKHA1, PCH-3GKHA1, PCH-4GKHSA1, PCH-5GKHSA1 Service Manual

...
Page 1
TECHNICAL & SERVICE MANUAL
SPLIT-TYPE,HEAT PUMP AIR CONDITIONERS
CONTENTS
1. FEATURES ···········································3
2. PART NAMES AND FUNCTIONS········7
3. SPECIFICATIONS·································8
4. DATA ···················································11
6. WIRING DIAGRAM·····························20
7.
REFRIGERANT SYSTEM DIAGRAM
······21
8. OPERATION FLOW-CHART··············22
9. MICROPROCESSOR CONTROL·······26
10. TROUBLESHOOTING ························49
11. DISASSEMBLY PROCEDURE ···········57
12. PARTS LIST········································62
13. OPTIONAL PARTS·····························73
Indoor unit
PCH-2GKHA PCH-2GKHA1 PCH-2.5GKHA PCH-2.5GKHA1 PCH-3GKHA PCH-3GKHA1 PCH-4GKHSA PCH-4GKHSA1 PCH-5GKHSA PCH-5GKHSA1 PCH-6GKHSA PCH-6GKHSA1
No. OC135
1997
[Models names] [Service Ref.]
This manual does not cover the following outdoor units. When serving them, please refer to the service manual No.OC128 and this manual in a set. [Service Ref.] PUH-2VKA
2
PUH-2.5VKA2 PUH-3VKA2 PUH-3YKA2 PUH-4YKSA3 PUH-5YKSA3 PUH-6YKSA2
INDOOR UNIT
Ceiling Suspended
Series PCH
REMOTE CONTROLLER
The Slim Line. From Mitsubishi Electric.
FILTER
CHECK MODE
TEST RUN
Page 2
Page 3
3
Operation buttons
Once the operation of the unit is set, subsequent operation can
only be performed by pressing the ON/OFF button repeatedly.
FILTER
CHECK MODE
TEST RUN
4
This switches between continuous operation and the timer operation.
button
This sets the ventilation fan speed.
button
button
This sets or switches the current time. start time and stop time.
button
This switches the horizontal fan motion ON and OFF.
button
Press this button to switch
the cooler electronic dry (dehumidify) automatic and heater modes.
button
This resets the filter service indication display.
FILTER button
This switches between the operation and stop modes each time it is pressed. The lamp on this butoon lights during operation.
ON/OFF button
This sets the room temparature The temparature setting can be performed in 1°C units
Setting range
Cooler 19°C to 30°C Heater 17°C to 28°C
TEMP button
This model name of the remote controller is indicated.
1
FEATURES
1. ADVANCED REMOTE CONTROLLER
Indoor unit
Ceiling Suspended
Series PCH
Remote controller
FILTER
CHECK MODE
TEST RUN
w Rating Conditions (JIS B 8616)
Cooling : Indoor : 27: (80
o
F)DB, 19: (66oF)WB.
Outdoor : 35: (95
o
F)DB, 24: (75oF)WB.
Heating : Indoor : 20: (68
o
F)DB.
Outdoor : 7: (45
o
F)DB, 6:(43oF)WB.
This adjusts the vertical angle of the ventilation.
(This button dose not operate in this model)
CHECK-TEST RUN button
Only press this button to perform an inspection check or test operation. Do not use it for normal operation.
Cooling capacity/Heating capacity
W Btu/h
Service Ref.
PCH-2GKHA1 PCH-2.5GKHA1 PCH-3GKHA1 PCH-4GKHSA1 PCH-5GKHSA1 PCH-6GKHSA1
5,400 / 6,200 (7,600) 7,000 / 7,100 (9,200)
7,500 / 8,500 (10,600)
10,000 / 10,450 (13,150)
12,400 /13,900 (16,900)
14,500 / 15,000 (18,000)
18,400 / 21,200 (25,900) 23,900 / 24,200 (31,400) 25,600 / 29,000 (36,200) 34,100 / 35,700 (44,900) 42,300 / 47,400 (57,700) 49,500 / 51,200 (61,400)
Page 4
4
Caution
Only the display lights when the unit is stopped and power supplied to the unit.
When power is turned ON for the first time the (CENTRAL CTRL) display appears to go off momentarily but this is not a
malfunction.
When the central control remote control unit, which is sold separately, is used the ON-OFF button, button and TEMP button do not operate.
“NOT AVAILABLE” is displayed when the
k button are pressed.This indicates that this room unit is not equipped with the
fan direction adjustment function and the louver function.
FILTER
CHECK MODE
TEST RUN
4
CENTRALLY CONTROLLED display
This indicates when the unit is
controlled by optional features such as central control type remote controller.
display
This indicates when the continous
operation and time operation modes are set.
It also display the time for the timer
operation at the same time as when it is set.
OPERATION MODE display
This indicates the operation mode.
STANDBY display
This indicates when the standby
mode is set from the time the sleep operation starts until the heating air is discharged.
DEFROST display
This indicates when the defrost
operation is performed.
CHECK display
This indicates when a malfunction
has occurred in the unit which should be checked.
display
The current time , start time and stop time can be displayed in tensecond intervals by pressing the time switch button. The start time or stop time is always displayed during the timer operation.
Display
Operation lamp
This lamp lights during operation, goes off when the unit stops and flashes when a malfunction occurs.
display
This lamp lights when electricity is supplied to the unit.
display
This displays the selected setting temperature.
display
This displays the air direction.
display
The temperature of the suction air is displayed during operation. The display range is 8° to 39°C. The display flashes 8°C when the actual temperature is less than 8° and flashes 39°C when the actual temperature is greater than 39°C.
display
This display lights in the check mode or when a test operation is performed.
CHECK MODE
TEST RUN
display
This lamp lights when the filter need to be cleaned.
FILTER
display
The selected fan speed is displayed.
Page 5
5
1. AIR OUTLET
New PCH series models have 1 air outlet (auto vane switching of horizontal air flow / down flow by switched by auto vane) instead of 2 (horizontal,and down flows).
2. EASY TO CLEAN ; FLOCKLESS VANE
With our original air current control mechanism, a flockless vane is newly adapted. The flockless vane prevents the condensation on the vane. By changing the vane to the flockless type, the unit can be cleaned much easier with mild household detergent.
3. NEW MATERIALS FOR BETTER OIL RESISTANCE
We have changed the materials of grill, filer, fan and fan casing from ABS to P.P. (polypropylene) for better oil resistance. As a result, oil crazing is cut in haif.
4. SIMPLIFIED INSTALLATION WORK (DIRECT SUSPENDING METHOD)
Simplified the installation work by changing the suspending method to the direct suspending method (suspending the unit directly from the suspension fixture).
In this way, the unit can be attached to the suspension fixture without removing the installation parts off (Only the
side cover is removed). This method is much simpler than the “One-time installation method”.
5. IMPROVING EFFICIENCY OF PIPING WORK
1
Removed the knockout work by separating the piping space from the air outlet for efficiency of the piping work.
w Knockout work is needed for the top part. When
optional drain-up machine is installed, the refrigerant pipe exits out from the top.
w Please move the rubber plug for the unit to the right joint
when drainage pipe exits from the left side.
2
Improved the flexbility by making it possible for drainage pipe to exit not only from the right side back but also from the left side back.
Unifies the air speed with the vane.
Sending the air to the upper area of the vane
Prevents the air comes from cntering from outside the unit
Protruding portion A
Protruding portion B
Flockless vane
Air outlet
B
A
L G D
Side panel
open
L : Liquid pipe G : Gas pipe D : Drain pipe
Back panel
L
U-cut
G
open
D
Rubber plug
Insulation cover (attached)
Drain pipe (purchased locally)
Joint coupliy (attached)
Drain pan
Insulation cover
Band (attached)
Page 6
6
6. QUITENESS ; 43dB (HIGH NOTCH)
New PCH series has No.1 quietness by changing the air course and the adapting the new shape air outlet.
7. EASY MAINTENANCE ; NO MAINTENANCE NECESSARY FOR 2500 HOURS
The new longlife air filter can be used continuously 2500 hours without maintenance (at general office situation).
8. CHOICE OF FILTER
High performance filter can be purchaced optionally for the special needs.
Auto vane
Swing
Locations Appropriate filter Capability Filter life Maintenance How to attach to the unit
Busy shops etc...
Regular office, shops
High performance filter
Standard longlife filter
2500 hour
2500 hour
The filter can be used again after cleaning.
The filter can be used again
after cleaning.
Remove the standard long life filter before attach this optional parts.
It is attached to the unit.
Weighing method 70%
Weighing method 30%
Page 7
7
PART NAMES AND FUNCTION
2
Indoor (Main) Unit
Air outlet
Intake grille
Air intake
Left/right guide vanes
Change the direction of airflow from the horizontal blower.
Long-life fillter
Removes dust and foreigh matter from air coming in through the grille (Recommended cleaning interval : Approx, every 2,500 operating hours)
Up/down guide vanes
Change the direction of airflow from the vartical blower.
Page 8
Service Ref.
Power supply
External finish Heat exchanger
Booster heater Operation control & Thermostat Noise level(Low-High) Cond. drain connection O.D.
Dimensions
Weight
Service Ref.
Power supply
External finish Refrigerant control Compressor
Heat exchanger
Defrost method Crankcase heater Noise level
Dimensions
Weight Refrigerant
Pipe size O.D.
Connection method
Between the indoor & outdoor unit
Indoor side Outdoor side Height difference Piping length
Input Running current Starting current
Fan(drive))No. Fan motor output Airflow(Low-High) External static pressure
Input Running current Starting current
Model Motor output Starter type Protection devices
Fan(drive))No. Fan motor output Airflow
Charge
dB(A) mm,(in) mm,(in) mm,(in) mm,(in) kg,(lbs)
W
D H
Function
Total input
Capacity
Cooling
Heating
Upper limit Lower limit Upper limit Lower limit
Indoor 35: DB, 22.5: WB 21: DB, 15.5: WB
27: DB 20: DB
Outdoor
46: DB
-5: DB
21: DB, 15.5: WB
-8.5: DB, -9.5: WB
2. Guaranteed operating range
W
dB(A) mm,(in) mm,(in) mm,(in) kg,(lbs)
W
D H
INDOOR UNITOUTDOOR UNIT
REFRIGERANT
PIPING
Item
Service Ref.
Btu/h
W
kW
kW
A A
kW
A A
kW
kg,(lbs)
kW
K/min <CFM>
kW
K/min <CFM>
Pa(mmAq)
kW
mm,(in) mm,(in)
Liquid Gas
PCH-2GKHA1 PCH-2.5GKHA1
Cooling
18,400
5,400
2.30
0.10
0.43
1.20
0.10 (1.50)
0.43(6.21)
1.20 (6.98)
0.13
0.55
1.27
0.13 (2.23)
0.55 (9.30)
1.27 (10.02)
Heating
21,200 (25,900)
6,200 (7,600)
2.32 (3.72)
Cooling
23,900
7,000
2.59
Heating
24,200 (31,400)
7,100 (9,200)
2.36 (4.46)
PCH-2GKHA
1
Single phase. 50Hz. 220-240V
Munsell 0.70Y 8.59 / 0.97
Plate fin coil
PCH-2.5GKHA
1
Sirocco (direct))2
0.054
10 -13 <353-459>
Sirocco (direct))3
0.07
14 -18 <494-635>
0 (direct blow)
(1.4) (2.1)
Remote controller & built-in
37 - 42 37 - 43
26(1)
1,000 (39-3/8) 1,310 (51-9/16)
680 (26-3/4)
210 (8-1/4)
28.5 (63)
PUH-2VKA
2
36 (79)
PUH-2.5VKA
2
NH38VMD
1.7
NH41VMD
2.0
0.065
45 (1,590)
0.085
50 (1,764)
650 (25-5/8)
64 (141)
850 (33-7/16)
68 (150)
Max. 40m Max. 40m
Max. 50m Max. 50m
49 52
2.2 (4.9) 2.8 (6.2)
Single phase. 50Hz. 220-240V
Reverse cycle
38
R-22
870 (34-1/4)
295 + 24 (11-5/8 add 1)
Munsell 5Y 7/1
Capillary tube
Hermetic
Line start
Internal thermostat. High-pressure switch
Plate fin coil
Propeller (direct)1
2.20
9.86 45
2.22
9.95 45
2.46
10.68 52
2.23
9.78 52
9.52 (3/8)
15.88 (5/8) Flared Flared
8
SPECIFICATIONS
3
Rating Conditions (JIS B8616)
Notes1. Rating Conditions (JIS B8616)
Cooling : Indoor : 27:(80
o
F)DB. 19:(66oF)WB
Outdoor : 35:(95
o
F)DB. 24:(75oF)WB
Heating : Indoor : 20:(68
o
F)DB.
Outdoor : 7:(45
o
F)DB. 6:(43oF)WB
Refrigerant piping length (one way) : 5m(16ft)
3. Above data based on indicated voltage Indoor Unit 1 phase 240V 50Hz Outdoor Unit 1 phase 240V 50Hz
Page 9
9
Rating Conditions (JIS B8616)
Service Ref.
Power supply
External finish Heat exchanger
Booster heater Operation control & Thermostat Noise level(Low-High) Cond. drain connection O.D.
Dimensions
Weight
Service Ref.
Power supply
External finish Refrigerant control Compressor
Heat exchanger
Defrost method Crankcase heater Noise level
Dimensions
Weight Refrigerant
Pipe size O.D.
Connection method
Between the indoor & outdoor unit
Indoor side Outdoor side Height difference Piping length
Input Running current Starting current
Fan(drive))No. Fan motor output Airflow(Low-High) External static pressure
Input Running current Starting current
Model Motor output Starter type Protection devices
Fan(drive))No. Fan motor output Airflow
Charge
dB(A) mm,(in) mm,(in) mm,(in) mm,(in) kg,(lbs)
W
D H
Function
Total input
Capacity
Cooling
Heating
Upper limit Lower limit Upper limit Lower limit
Indoor 35: DB, 22.5: WB 21: DB, 15.5: WB
27: DB 20: DB
Outdoor
46: DB
-5: DB
21: DB, 15.5: WB
-8.5: DB, -9.5: WB
2. Guaranteed operating range
W
dB(A) mm,(in) mm,(in) mm,(in) kg,(lbs)
W
D H
INDOOR UNITOUTDOOR UNIT
REFRIGERANT
PIPING
Item
Service Ref.
Btu/h
W
kW
kW
A A
kW
A A
kW
kg,(lbs)
kW
K/min <CFM>
kW
K/min <CFM>
Pa(mmAq)
kW
mm,(in) mm,(in)
Liquid Gas
PCH-3GKHA1 PCH-4GKHSA1
Cooling
25,600
7,500
3.28
0.13
0.55
1.27
0.13 (2.23)
0.55 (9.30)
1.27 (10.02)
0.16
0.70
1.48
0.16 (2.86)
0.70 (11.95)
1.48 (12.73)
Heating
29,000 (36,200)
8,500 (10,600)
3.07 (5.17)
Cooling
34,100 10,000
3.36
Heating 35,700 (44,900) 10,450 (13,150)
3.35(6.05)
PCH-3GKHA
1
Single phase. 50Hz. 220-240V
Munsell 0.70Y 8.59 / 0.97
Plate fin coil
Sirocco (direct) 3
PCH-4GKHSA
1
0.07
14 -18 <494-635>
0.09
20 -25 <706-883>
0 (direct blow)
(2.1)
210 (8-1/4) 270 (10-5/8)
(2.7)
Remote controller & built-in
37 - 43 40 - 45
26 (1)
1,310 ( 51-9/16 )
680 (26-3/4)
36 (79)
PUH-3VKA
2,PUH-3YKA2
39.5 (87)
PUH-4YKSA
3
NH52VND(PUH-3VKA),NH52YDA(PUH-3YKA)
2.2 / 2.4
NH56YDA
2.7
Propeller (direct) 1
0.085
50 (1,764)
Propeller (direct) 2
0.065 + 0.065 95 (3,350)
850 (33-7/16)
75 (165)
1,258 (49-1/2)
94 (207)
Max. 50m Max. 50m
38 52
38 54
3.2 (7.1)
9.52 (3/8)
15.88 (5/8)
4.2 (9.2)
9.52 (3/8)
19.05 (3/4)
VKA...1phase, 50Hz, 220-240V / YK(S)A...3phase, 50-380Hz, 415V, 4wires
Reverse cycle
R-22
870 <34-1/4>
295 + 24 <11-5/8 add 1>
Munsell 5Y 7/1
Capillary tube
Hermetic
Line start
VKA...Inner thermostat. High-pressure switch YKA...Anti-phase protector, Thermal relay, Thermal switch, High-pressute switch
Plate fin coil
3.15
13.82 / 5.16 58 / 37
2.94
12.89 / 4.81 58 / 37
3.20
5.24 40
3.19
5.22 40
Flared Flared
Notes1. Rating Conditions (JIS B8616)
Cooling : Indoor : 27:(80
o
F)DB. 19:(66oF)WB
Outdoor : 35:(95
o
F)DB. 24:(75oF)WB
Heating : Indoor : 20:(68
o
F)
Outdoor : 7:(45
o
F)DB. 6:(43oF)WB.
Refrigerant piping length (one way) : 5m(16ft)
3. Above data based on indicated voltage Indoor Unit 1 phase 240V 50Hz Outdoor Unit 1 phase 240V 50Hz / 3 phase 415V 50Hz
Page 10
10
Rating Conditions (JIS B8616)
Service Ref.
Power supply
External finish Heat exchanger
Booster heater Operation control & Thermostat Noise level(Low-High) Cond. drain connection O.D.
Dimensions
Weight
Service Ref.
Power supply
External finish Refrigerant control Compressor
Heat exchanger
Defrost method Crankcase heater Noise level
Dimensions
Weight Refrigerant
Pipe size O.D.
Connection method
Between the indoor & outdoor unit
Indoor side Outdoor side Height difference Piping length
Input Running current Starting current
Fan(drive))No. Fan motor output Airflow(Low-High) External static pressure
Input Running current Starting current
Model Motor output Starter type Protection devices
Fan(drive))No. Fan motor output Airflow
Charge
dB(A) mm,(in) mm,(in) mm,(in) mm,(in)
kg,(lbs)
W
D H
Function
Total input
Capacity
Cooling
Heating
Upper limit Lower limit Upper limit Lower limit
Indoor 35: DB, 22.5: WB 21: DB, 15.5: WB
27: DB 20: DB
Outdoor
46: DB
-5: DB
21: DB, 15.5: WB
-8.5: DB, -9.5: WB
2. Guaranteed operating range
W
dB(A) mm,(in) mm,(in) mm,(in)
kg,(lbs)
W
D H
INDOOR UNITOUTDOOR UNIT
REFRIGERANT
PIPING
Item
Service Ref.
Btu/h
W
kW
kW
A A
kW
A A
kW
kg,(lbs)
kW
K/min <CFM>
kW
K/min <CFM>
Pa(mmAq)
kW
mm,(in) mm,(in)
Liquid Gas
PCH-5GKHSA1 PCH-6GKHSA1
Cooling
42,300 12,400
4.45
0.24
1.06
2.20
0.24 (3.24)
1.06 (13.56)
2.20 (14.70)
0.24
1.06
2.20
0.24 (3.24)
1.06 (13.56)
2.20 (14.70)
Heating 47,400 (57,700) 13,900 (16,900)
4.40 (7.40)
Cooling
49,500 14,500
4.97
Heating 51,200 (61,400) 15,000 (18,000)
4.82 (7.82)
PCH-5GKHSA
1
Single phase. 50Hz. 220-240V
PCH-6GKHSA
1
Munsell 0.70Y 8.59 / 0.97
Plate fin coil
Sirocco (direct)4
0.15
27 -34 <953-1,200>
0 (direct blow)
(3.0)
Remote controller & built-in
41-46 42-48
26 (1)
1,620 (63-3/4)
680 (26-3/4) 270 (10-5/8)
46 (101)
PUH-5YKSA
3
48 (106)
PUH-6YKSA
2
ZR61KC-TFD
3.5
ZR68KC-TFD
4.0
0.085 + 0.085 95 (3,350)
0.10 + 0.10
100 (3,530)
114 (251) 117 (258)
55 56
5.4 (11.9) 5.0 (11.0)
3 phases. 50Hz. 380-415V (4 wires)
Reverse cycle
38
R-22
970 (38-3/16)
345 + 24 (13-9/16 add 1)
1,258 (49-1/2)
Munsell 5Y 7/1
Capillary tube
Hermetic
Line start
Anti-phase protector, Internal thermostat, Thermal switch, High-pressure switch
Plate fin coil
Propeller (direct)2
4.21
6.89 53
4.16
6.81 53
4.73
7.74 74
4.58
7.50 74
9.52 (3/8)
19.05 (3/4) Flared Flared
Max. 50m Max. 50m
Notes1. Rating Conditions (JIS B8616)
Cooling : Indoor : 27:(80
o
F)DB. 19:(66oF)WB
Outdoor : 35:(95
o
F)DB. 24:(75oF)WB
Heating : Indoor : 20:(68
o
F)DB.
Outdoor : 7:(45
o
F)DB. 6:(43oF)WB.
Refrigerant piping length (one way) : 5m(16ft)
3. Above data based on indicated voltage Indoor Unit 1 phase 240V 50Hz Outdoor Unit 3 phase 415V 50Hz
Page 11
11
4
DATA
1. PERFORMANCE DATA
1) COOLING CAPACITY
5448 5800 6157 6517 7062 7519 7981 8448 7566 8056 8551
9052 10088 10741 11402 12069 12510 13319 14138 14965 14628 15575 16532 17500
5299 5648 6012 6392 6869 7321 7794 8286 7359 7844 8350 8878
9812 10459 11134 11838 12167 12969 13806 14679 14228 15165 16144 17164
5104 5442 5798 6171 6616 7054 7515 7999 7089 7558 8052 8571
9452 10078 10736 11427 11720 12496 13313 14170 13705 14613 15568 16570
4897 5226 5574 5940 6348 6775 7225 7700 6802 7259 7741 8250 9069
9678 10322 11000 11245 12001 12799 13640 13150 14033 14967 15951
4678 5000 5341 5700 6064 6482 6923 7389 6515 6954 7419 7910 8686 9272
9892 10547 10771 11497 12266 13078 12595 13445 14344 15293
4447 4764 5099 5451 5765 6176 6609 7067 6199 6632 7089 7570 8266 8842
9451 10094 10249 10964 11720 12516 11985 12821 13705 14636
Service Ref.
PCH-2GKHA
1
PCH-2.5GKHA1
PCH-3GKHA1
PCH-4GKHSA1
PCH-5GKHSA1
PCH-6GKHSA1
16 18 20 22 16 18 20 22 16 18 20 22 16 18 20 22 16 18 20 22 16 18 20 22
CA
20 25 30 35 40 45
Outdoor intake air DB!C
Refrigerant piping length (one way)
PCH-2GKHA
1
PCH-2.5GKHA1 PCH-3GKHA1 PCH-4GKHSA1 PCH-5GKHSA1 PCH-6GKHSA1
Service Ref.
5m
1.00
1.00
1.00
1.00
1.00
1.00
10m
0.992
0.989
0.981
0.989
0.981
0.975
15m
0.983
0.980
0.968
0.980
0.968
0.955
20m
0.978
0.970
0.952
0.970
0.952
0.935
25m
0.966
0.960
0.940
0.960
0.940
0.918
30m
0.959
0.950
0.925
0.950
0.925
0.900
35m
0.950
0.940
0.913
0.940
0.913
0.884
40m
0.945
0.930
0.900
0.930
0.900
0.869
45m
0.920
0.886
0.920
0.886
0.855
50m
0.910
0.874
0.910
0.874
0.840
Indoor Intake
air
WB!C
P.C.
1.84
1.88
1.92
1.95
2.08
2.12
2.16
2.20
2.63
2.68
2.73
2.78
2.69
2.75
2.80
2.85
3.57
3.64
3.71
3.78
3.98
4.06
4.14
4.22
1.92
1.96
2.00
2.04
2.16
2.21
2.25
2.30
2.74
2.80
2.85
2.91
2.81
2.87
2.92
2.98
3.72
3.79
3.87
3.95
4.15
4.24
4.32
4.41
2.07
2.12
2.16
2.21
2.33
2.38
2.44
2.49
2.95
3.02
3.08
3.15
3.02
3.09
3.16
3.23
4.00
4.10
4.19
4.27
4.47
4.57
4.67
4.77
2.22
2.27
2.33
2.38
2.50
2.56
2.62
2.68
3.16
3.24
3.32
3.40
3.24
3.32
3.40
3.48
4.29
4.40
4.50
4.61
4.79
4.91
5.03
5.15
2.37
2.43
2.49
2.56
2.67
2.73
2.81
2.89
3.38
3.46
3.55
3.65
3.46
3.55
3.64
3.74
4.58
4.70
4.82
4.96
5.12
5.25
5.39
5.54
2.52
2.58
2.66
2.75
2.84
2.91
3.00
3.10
3.59
3.68
3.79
3.92
3.68
3.77
3.89
4.01
4.87
5.00
5.15
5.32
5.44
5.58
5.75
5.94
CA P.C. CA P.C. CA P.C. CA P.C. CA P.C.
Notes CA : Capacity (W)
P.C. : Power consumption (kW)
Cooling cpapacity correction factors
Page 12
12
2. HEATING CAPACITY
Service Ref.
PCH-2GKHA
1
PCH-2.5GKHA1
PCH-3GKHA1
PCH-4GKHSA1
PCH-5GKHSA1
PCH-6GKHSA1
15 20 25 15 20 25 15 20 25 15 20 25 15 20 25 15 20 25
CA
-10 -5 0 5 10 15
Outdoor intake air WB!C
Refrigerant piping length (one way)
PCH-2GKHA
1
PCH-2.5GKHA1 PCH-3GKHA1 PCH-4GKHSA1 PCH-5GKHSA1 PCH-6GKHSA1
Service Ref.
5m
1.00
1.00
1.00
1.00
1.00
1.00
10m
1.00
1.00
1.00
1.00
1.00
1.00
15m
1.00
1.00
1.00
1.00
1.00
1.00
20m
1.00
1.00
1.00
1.00
1.00
1.00
25m
1.00
1.00
1.00
1.00
1.00
1.00
30m
1.00
1.00
1.00
1.00
1.00
1.00
35m
0.998
0.998
0.998
0.998
0.998
0.998
40m
0.995
0.995
0.995
0.995
0.995
0.995
45m
0.993
0.993
0.993
0.993
0.993
50m
0.990
0.990
0.990
0.990
0.990
Indoor Intake
air
DB!C
P.C.
1.58
1.71
1.81
1.61
1.73
1.84
2.09
2.26
2.40
2.29
2.46
2.61
3.00
3.23
3.43
3.29
3.54
3.76
CA P.C. CA P.C. CA P.C. CA P.C. CA P.C. 4246 4066 3907 4862 4656 4474 5821 5574 5356 7156 6852 6585 9519 9115 8759
10272
9836 9453
1.75
1.89
2.01
1.78
1.92
2.04
2.31
2.49
2.66
2.53
2.72
2.90
3.32
3.58
3.81
3.63
3.92
4.17
4866 4675 4485 5573 5354 5136 6671 6409 6149 8202 7880
7560 10910 10481 10056 11773 11311 10851
1.93
2.08
2.22
1.96
2.11
2.26
2.55
2.75
2.94
2.78
3.00
3.20
3.65
3.94
4.21
4.00
4.31
4.61
5546 5337 5125 6351 6112 5869 7604 7317 7027 9348 8996
8639 12434 11966 11491 13418 12912 12400
2.11
2.28
2.44
2.15
2.32
2.48
2.80
3.01
3.23
3.05
3.29
3.52
4.01
4.32
4.63
4.39
4.73
5.07
6285 6051 5827 7198 6929 6673 8617 8296
7989 10594 10199
9821 14091 13566 13064 15206 14640 14098
2.31
2.49
2.67
2.35
2.53
2.72
3.06
3.30
3.53
3.34
3.60
3.86
4.39
4.72
5.07
4.81
5.18
5.55
7082 6816 6590 8110 7806 7546 9710 9345
9034 11937 11488 11107 15878 15281 14774 17135 16491 15943
2.52
2.71
2.91
2.57
2.76
2.96
3.34
3.59
3.85
3.64
3.92
4.21
4.78
5.15
5.52
5.24
5.64
6.05
7936 7632 7413 9088 8740
8489 10880 10463 10163 13376 12863 12495 17792 17110 16620 19200 18464 17935
Notes CA : Capacity (W)
P.C. : Power consumption (kW)
Heating capacity correction factors
Page 13
13
3. ELECTRICAL DATA
Rating Conditions (JIS B8616) Indoor
……
220V 50Hz 1phase
Outdoor… 220V 50Hz 1phase / 380V 50Hz 3phase
IndoorOutdoor
Input (kW) Current (A) Starting current (A) Input (kW) Current (A) Starting current (A)
Mode Capacity (W) Total Input (kW)
Service Ref.
Cooling
5,300
2.20
0.08
0.38
1.10
2.12
9.83 43
Heating
6,100
2.22
0.08
0.38
1.10
2.14
9.93 43
PCH-2GKHA
1
Cooling
6,900
2.52
0.11
0.51
1.17
2.41
11.18 52
Heating
7,000
2.27
0.11
0.51
1.17
2.16
10.02 52
PCH-2.5GKHA
1
Cooling
7,400
3.24
0.11
0.51
1.17
3.13
14.67/5.23 54 / 34
Heating
8,400
3.03
0.11
0.51
1.17
2.92
13.68/4.88 54 / 34
PCH-3GKHA
1
Cooling
9,900
3.31
0.14
0.68
1.36
3.17
5.29 37
Heating
10,350
3.30
0.14
0.68
1.36
3.16
5.28 37
PCH-4GKHSA
1
Cooling
12,200
4.39
0.20
0.96
2.0
4.19
7.32 49
Heating
13,700
4.33
0.20
0.96
2.0
4.13
7.21 49
PCH-5GKHSA
1
Cooling
14,400
4.84
0.20
0.96
2.0
4.64
8.10 68
Heating
14,800
4.76
0.20
0.96
2.0
4.56
7.96 68
PCH-6GKHSA
1
IndoorOutdoor
Input (kW) Current (A) Starting current (A) Input (kW) Current (A) Starting current (A)
Mode Capacity (W) Total Input (kW)
Service Ref.
Cooling
5,350
2.25
0.09
0.41
1.15
2.16
9.78 44
Heating
6,150
2.27
0.09
0.41
1.15
2.18
9.87 44
PCH-2GKHA
1
Cooling
6,950
2.56
0.12
0.53
1.22
2.44
10.94 52
Heating
7050
2.32
0.12
0.53
1.22
2.20
9.86 52
PCH-2.5GKHA
1
Cooling
7,450
3.26
0.12
0.53
1.22
3.14
14.22 / 5.21 56 / 36
Heating
8,450
3.05
0.12
0.53
1.22
2.93
13.27 /4.86 56 / 36
PCH-3GKHA
1
Cooling
9,950
3.34
0.15
0.69
1.42
3.19
5.23 39
Heating
10,400
3.33
0.15
0.69
1.42
3.18
5.22 39
PCH-4GKHSA
1
Cooling
12,300
4.42
0.22
1.01
2.10
4.20
7.05 51
Heating
13,800
4.37
0.22
1.01
2.10
4.15
6.97 51
PCH-5GKHSA
1
Cooling
14,450
4.91
0.22
1.01
2.10
4.69
7.87 71
Heating
14,900
4.79
0.22
1.01
2.10
4.57
7.67 71
PCH-6GKHSA
1
IndoorOutdoor
Input (kW) Current (A) Starting current (A) Input (kW) Current (A) Starting current (A)
Mode Capacity (W) Total Input (kW)
Service Ref.
Cooling
5,400
2.30
0.10
0.43
1.20
2.20
9.86 45
Heating
6,200
2.32
0.10
0.43
1.20
2.22
9.95 45
PCH-2GKHA
1
Cooling
7,000
2.59
0.13
0.55
1.27
2.46
10.68 52
Heating
7,100
2.36
0.13
0.55
1.27
2.23
9.78 52
PCH-2.5GKHA
1
Cooling
7,500
3.28
0.13
0.55
1.27
3.15
13.82 / 5.16 58 / 37
Heating
8,500
3.07
0.13
0.55
1.27
2.94
12.89 / 4.81 58 / 37
PCH-3GKHA
1
Cooling
10,000
3.36
0.16
0.70
1.48
3.20
5.24 40
Heating
10,450
3.35
0.16
0.70
1.48
3.19
5.22 40
PCH-4GKHSA
1
Cooling
12,400
4.45
0.24
1.06
2.20
4.21
6.89 53
Heating
13,900
4.40
0.24
1.06
2.20
4.16
6.81 53
PCH-5GKHSA
1
Cooling
14,500
4.97
0.24
1.06
2.20
4.73
7.74 74
Heating
15,000
4.82
0.24
1.06
2.20
4.58
7.50 74
PCH-6GKHSA
1
[7,280]
[3.40]
[8,760]
[4.03]
[10,160]
[4.79]
[12,620]
[5.57]
[16,220]
[6.85]
[17,320]
[7.28]
[7,440]
[3.56]
[7,600]
[3.72]
[9,200]
[4.46]
[10,600]
[5.17]
[13,150]
[6.05]
[16,900]
[7.40]
[18,000]
[7.82]
[8,980]
[4.25]
[10,380]
[4.98]
[12,880]
[5.81]
[16,560]
[7.13]
[17,660]
[7.55]
Indoor
……
230V 50Hz 1phase
Outdoor… 230V 50Hz 1phase / 400V 50Hz 3phase
Indoor
……
240V 50Hz 1phase
Outdoor… 240V 50Hz 1phase / 415V 50Hz 3phase
Page 14
14
4. STANDARD OPERATION DATA
Rating Conditions (JIS B8616)
Electrical circuit Total Refrigerant circuit
Indoor side
Outdoor
side
Capacity Input
Indoor unit Service Ref.
Phase, Hz Volts Amperes
Outdoor unit
Service Ref.
Phase, Hz Volts Amperes Discharge pressure Suction pressure Discharge temperature Condensing temperature Suction temperature Ref. pipe length
Intake air temperature
Discharge air temperature
Intake air temperature
Mode
Service Ref.
SHF
BF
W
KW
V A
V A
Mpa·G(Of/F·G) Mpa·G(Of/F·G)
!C !C !C
m DB !C WB !C DB !C DB !C WB !C
Cooling
5,400
2.30
0.43
9.86
1.92
0.47
87 50
3.8 5
27 19
11.5 35 24
0.68
0.11
Heating
6,200
2.32
0.43
9.95
1.90
0.37
89 —
-2.7 5
20 15
44.8 7 6
— —
PCH-2GKHA
1
PCH-2GKHA
1
1, 50
240
PUH-2VKA
2
1, 50
240
Cooling
7,000
2.59
0.55
10.68
2.05
0.53
85 53
6.9 5
27 19
12.4 35 24
0.69
0.14
Heating
7,100
2.36
0.55
9.78
1.73
0.38
77
-2.1 5
20 15
40.4 7 6
— —
PCH-2.5GKHA
1
PCH-2.5GKHA
1
1, 50
240
PUH-2.5VKA2
1, 50
240
Cooling
7,500
3.28
0.55
13.82/ 5.16
2.04
0.43
87 53
1.6 5
27 19
11.1 35 24
0.66
0.15
Heating
8,500
3.07
0.55
12.89/ 4.81
1.94
0.36
83 —
-2.9 5
20 15
44.8 7 6
— —
PCH-3GKHA
1
PCH-3GKHA
1
1, 50
240
PUH-3VKA
2
PUH-3YKA2
1/3, 50
240 / 415
Cooling
10,000
3.36
0.70
5.24
1.83
0.50
78 48
6.7 5
27 19
11.1 35 24
0.68
0.12
Heating
10,450
3.35
0.70
5.22
1.72
0.39
75 —
-1.0 5
20 15
42.1 7 6
— —
PCH-4GKHSA
1
PCH-4GKHSA
1
1, 50
240
PUH-4YKSA3
3, 50
415
Cooling
12,400
4.45
1.06
6.89
1.92
0.48
75 50
4.4 5
27 19
12.4 35 24
0.73
0.07
Heating
13,900
4.40
1.06
6.81
1.78
0.37
70 —
-2.8 5
20 15
42.4 7 6
— —
PCH-5GKHSA
1
PCH-5GKHSA
1
1, 50
240
PUH-5YKSA3
3, 50
415
Cooling
14,500
4.97
1.06
7.74
1.97
0.45
74 51
2.6 5
27 19
10.0 35 24
0.65
0.14
Heating
15,000
4.82
1.06
7.50
1.80
0.38
69 —
-1.8 5
20 15
44.9 7 6
— —
PCH-6GKHSA
1
PCH-6GKHSA
1
1, 50
240
PUH-6YKSA2
3, 50
415
[7,600]
[3.72]
[9,200]
[4.46]
[10,600]
[5.17]
[13,150]
[6.05]
[16,900]
[7.40]
[18,000]
[7.82]
(19.6)
(4.8)
(19.4)
(3.77)
(20.9)
(5.4)
(17.6)
(3.87)
(20.8)
(4.39)
(19.8)
(3.67)
(18.7)
(5.1)
(17.5)
(3.98)
(19.6)
(4.90)
(18.1)
(3.77)
(20.1)
(4.59)
(18.4)
(3.88)
The unit of pressure has been changed to Mpa on the international system of unit (SI unit system). The converted score against the traditional unit system can be gotten according to the formula below.
1(Mpa·G)=10.2(
O
Of/F
·G)
Page 15
15
5
1. INDOOR UNIT PCH-2GKHA
1
180
210
157
15
85
182 (3/8F) liquid
201 (5/8F) gas
241 (Drainage)
Air intake
918
254
680
Electrical box
226
70
525
928
352
263
171
138
86
46 175
131
38
3879
161
32
179
42
6~7
Celling
Electrical box
[Front view]
When electrical
box is pulled
down
3
2
8
5
1
4
6
2
7
17
150
140
70
320
80
933 (suspension bolt pitch)
983
1000
Air outlet
81
904
76
1 Drainage pipe connection (26mm I.D.) 5 Refrigerant-pipe connection (liquid pipe side/flared connection)
2 Drainage pipe connection (for the left arrangement) 6 Knock out hole for upper drain pipe arrangement
3 Knock out hole for left drain-piping arrangement 7 Knock out hole for left drain pipe arrangement
4 Refrigerant-pipe connection (gas pipe side/flared connection) 8 Knock out hole for wining arrangement
NOTES:
1. Use M10 or W3/8 screws for anchor bolt.
2. Please be sure when installing the drain-up machine (option parts).
refrigerant pipe will be only upper drain pipe arrangement.
OUTLINES AND DIMENSIONS
Page 16
16
PCH-2.5GKHA1 PCH-3GKHA1
1240 (suspension bolt pitch)
140
150
320 80
17
70
6
1290
1214
210 180
81 76
1310
Air outlet
1228
680
254
Air intake
85
182
201
241
15
157
(3/8F liquid)
(5/8F gas)
(Drainage)
3
2
8
5
1
4
Electrical box
When electrical
box is pulled
down
[ Front view ]
Celling
32
179
161
38
3879
42
6~7
525
1235
416
263
171
138
86
131
175 1
46
7
2
Electrical box
70
226
1 Drainage pipe connection (26mm I.D.) 5 Refrigerant-pipe connection (liquid pipe side/flared connection)
2 Drainage pipe connection (for the left arrangement) 6 Knock out hole for upper drain pipe arrangement
3 Knock out hole for left drain-piping arrangement 7 Knock out hole for left drain pipe arrangement
4 Refrigerant-pipe connection (gas pipe side/flared connection) 8 Knock out hole for wining arrangement
NOTES:
1. Use M10 or W3/8 screws for anchor bolt.
2. Please be sure when installing the drain-up machine (option parts).
refrigerant pipe will be only upper drain pipe arrangement.
Page 17
17
PCH-4GKHSA1
1 Drainage pipe connection (26mm I.D.) 5 Refrigerant-pipe connection (liquid pipe side/flared connection)
2 Drainage pipe connection (for the left arrangement) 6 Knock out hole for upper drain pipe arrangement
3 Knock out hole for left drain-piping arrangement 7 Knock out hole for left drain pipe arrangement
4 Refrigerant-pipe connection (gas pipe side/flared connection) 8 Knock out hole for wining arrangement
NOTES:
1. Use M10 or W3/8 screws for anchor bolt.
2. Please be sure when installing the drain-up machine (option parts).
refrigerant pipe will be only upper drain pipe arrangement.
6
(3/8F liquid)
(5/8F-gas)
(Drainage)
182
245
87
16
320 80
70
140
150
17
217
270
207
680
81 96
254
1
4
1
5
8
Celling
[ Front view ]
93
Electrical box
236
192
38 140
160
1310
1214
1240 (suspension bolt pitch)
45
Air outlet
86
138
171
263
38
687
1235
70
2
229
1228
Air intake
7
525
6~7
Electrical box
2
3
42 239
When electrical
box is pulled
down
Page 18
18
1535
680
254
Air intake
1524
270
207
81 96
1620
Air outlet
1547(suspension bolt pitch)
140
150
320 80
18
70
6
87
182
198
245
16
217
(3/8F liquid)
(3/4F gas)
(Drainage)
3
2
8
5
1
4
Electrical box
When electrical
box is pulled
down
[ Front view ]
Celling
93
160
38
38 140
42 239
6~7
525
1545
687
263
171
138
86
192
236
1
45
7
2
Electrical box
70
229
PCH-5GKHSA1 PCH-6GKHSA1
1 Drainage pipe connection (26mm I.D.) 5 Refrigerant-pipe connection (liquid pipe side/flared connection)
2 Drainage pipe connection (for the left arrangement) 6 Knock out hole for upper drain pipe arrangement
3 Knock out hole for left drain-piping arrangement 7 Knock out hole for left drain pipe arrangement
4 Refrigerant-pipe connection (gas pipe side/flared connection) 8 Knock out hole for wining arrangement
NOTES:
1. Use M10 or W3/8 screws for anchor bolt.
2. Please be sure when installing the drain-up machine (option parts).
refrigerant pipe will be only upper drain pipe arrangement.
Page 19
19
2. REMOTE CONTROLLER Unit : mm(inch)
18
130
Rear side wiring arrangement opening.
120
FILTER
CHECK MODE
TEST RUN
FILTER
CHECK MODE
TEST RUN
46
83.5
SW18
SW17
CAUTION
Page 20
20
WIRING DIAGRAM
6
PCH-2GKHA1/PCH-2.5GKHA1/PCH-3GKHA1 PCH-4GKHSA1/PCH-5GKHSA1/PCH-6GKHSA1
240V
230V
220V
230V
220V
YELLOW ORANGE RED
1
ON OFF
2
3 4
1
ON OFF
2
3 4
[Emergency operation procedure] (2) Turn on the outdoor unit side circuit breaker, then indoor unit side circuit breaker in this order. (3) During emergency operation indoor fan runs at high speed but automatic vane remains stop. (4) If vane closed, open the vane by hand slowly. (5) Thermostat will not function. Cold air belows out for defrosting during heating thus do not operate defrosting for a long time. (6) Emergency cooling should be limited to 10 hours maximum.
(The indoor unit heat exchanger may freeze).
(7) If the microcomputer doctor detects the abnormality of the drain-up machine during cooling mode, do not execute emergency
operation.(If causes drain overflow)
NOTES :
1. Since the indoor fan motor (MF 1.2) is connected with 230~240V power. IF 220V power is used. change the dip switch (SWS<1.B>)on the indoor controller board showing fig:w1.
2. Since the indoor transformer (T)is connected with 240Vpower.if 220.230V power is used. Change the wiring connection showing fig:w2.
3. Since the outdoor side electric wiring may change be sure to check the outdoor unit electric wiring for servicing.
4. Indoor and outdoor connecting wires are made with polarities. make wiring matching terminal numbers.
5. Symbols used in wiring diagram above are. : Connector,
/
/
: Terminal block.
6. Emergency operation
If remote controller or microcomputer fails but there is no other truble. emergency operation is possible by setting dip switch (SW3<I.B>) on the indoor controller board.
[Check items] (1)Make sure that no other trouble exist the outdoor unit. Trouble with the outdoor unit prevents emergency operation.
(If any trouble exists the outdoor unit error code “P8”will be displayed on the remote controller and the trouble position will be shown on the outdoor controller LED. See electric wiring diagram of the outdoor unit for details.)
(2)Make sure that there is no trouble with the indoor fan.
Emergency operation will be continuous operation mode due to power ON/OFF (ON/OFF with the remote controller is not possible).
[Emergency operation procedure] (1)Set the dip switch (SW3<I.B>) on the indoor controller board to on and off for cooling and - on for heating.
2121
fig:w1
Indoor fan motor (MF) for
fig:w2
When power supply is
SYMBOL
C
NAME
FAN MOTOR CAPACITOR
CN1<R.B>
PROGRAM TIMER CONNECTOR
CN2<R.B>
REMOTE SWITCH CONNECTOR
CN2L<I.B>
LOSSNAY CONNECTOR
CNP<I.B>
DRAIN-UP MACHINE CONNECTOR
CN50<I.B>
DRAIN SENSOR CONNECTOR
CN51<I.B>
CENTRALLY CONTROL CONNECTOR
F1,2<I.B>
FUSE(6.3A 250V)
FS1,2
H
HEATER I.B J1<I.B> J5<I.B>
INDOOR CONTROLLER BOARD
FUNCTION SELECTOR JUMPER RESISTORS
MODEL SELECTOR JUMPER RESISTORS
SYMBOL
J9<I.B>
NAME
MODEL SELECTOR JUMPER RESISTORS
LED1<I.B>
DC 12V POWER LED
LED2<I.B>
DC 5V POWER LED
MF
FAN MOTOR VANE MOTOR
REMOTE CONTROLLER BOARD ROOM TEMPERATURE THERMISTOR
(0
:/15k", 25:/5.4k" DETECT)
INDOOR COIL THERMISTOR (0:/15k", 25:/5.4k" DETECT) ADDRESS SELECTOR EMERGENCY OPERATION SWITCH TWIN/TRIPLE SELECTOR MODEL SELECTOR
SYMBOL
SW17<R.B>
NAME
ADDRESS SELECTOR
SW18<R.B>
FUNCTION SELECTOR
T
TRANSFORMER
TB2
POWER SUPPLY TERMINAL BLOCK INDOOR/OUTDOOR CONNECTING WIRE TERMINAL BLOCK
REMOTE CONTROLLER
TERMINAL BLOCK
LINE TRANSMISSION FAN MOTOR RELAY
VARISTOR HEATER THERMAL SWITCH HEATER CONTACTOR OPTION DRAIN-UP MACHINE OPTION DRAIN-UP SENSOR
THERMAL FUSE(98:10A:2GKHA / 117:16A: 4GKHA110
:16A:2.5,3GKHA.5.6GKHSA)
MV R.B RT1
RT2
SW2<I.B> SW3<I.B> SW6<I.B> SW7<I.B>
TB4 TB5,6
X4<I.B> ZNR 26H 88H DP DS
I.B
OFF
MF
C
WHT
BLK
RED
FAN1
135
X4
X4
SW2
123456
J5
2
42
ON
DP
CNP
D.U.M
ZNR
J9
13
(OPTION)
31
POWER
SW6
1234
CND
F2 F1
1234
BLU
RED
3
LED1 12V POWER
SW3SW7
ON
OFF
12
J1
456 97108
RED
YLW
WHT
13
ORN
CNT
TRANS
LED2 5V POWER
HEATER
220V 230V 240V
YLW
CN24
T
6
CN6V
VAN E
1
POWER
CENTRALLY
CONTROL
CN51
DRAIN
CN50
10VAC
14.3VAC 6
RED
RED
43211
REMOCON
CN40
1234
CN21
CN20
5
INTAKE
1234
BRN
BRN
TO
REMOCON
OUTDOOR
PIPE
LOSSNAY
GRN/YLW
CN4T
TRANS
CN22
CN30
12
12
CN2L
TB2
6
MV
BLU BLU
12
BRN ORN YLW
123
BLK BLK
12
RT1
L
POWER SUPPLY
N
~
(1 PHASE) AC220-240V 50Hz AC220V 60Hz
INDOOR UNIT
REMOTE CONTROLLER
TRANSMISSION WIRES
TB5
DC12V
2 1
OUTDOOR UNIT
TB4
3
TO OUTDOOR UNIT
2
CONNECTING WIRES
1
DC12V
RT2
54
GRY
DRAIN
CN50
3
BLK
2 1
DS(OPTION)
MODELS
SW7
MODELS
SW7
L N
ON OFF
1234
OFF
1234
RED
RED BLU
TB2
I.B
HEATER
CN24
2 1
PCH-2~6GKH(S)A (with heater)
3GK(H)
2.5GK(H)2GK(H) ON
OFF
1234
1234
6GK(H)5GK(H)4GK(H)
ONON OFF
1234
1234
88H
RED
35
BLU
YLW YLW
6
88H
R.B
SW17
ON OFF
87654321
ON OFF
FS2
FS1
21
RED
6
GRY
5
1
RED
SW18
TB6
OFF ON
OFF ON
CN1
54 12
CN2
312
4321
BG79Y189H03-A
H
26H
B.2A.1
3
Page 21
21
7
REFRIGERANT SYSTEM DIAGRAM
Indoor unit
Indoor heat exchanger
Refrigerant pipe (option)
15.88
mm( 5/8")
(with heat insulator)
Flexible tube
Ball valve
Strainer
4-way valve
Oil separator
Service port
Service port
High pressure control switch
Outdoor unit
Outdoor heat exchanger
Outdoor coil thermistor
(RT)
Capillary tube
Restrictor valve
Strainer
Bypass valve
Compressor
Accumulator
Ball valve (with service port)
Refrigerant pipe (option)
9.52
mm( 3/8")
(with heat insulator)
Capillary tube
Restrictor valve
Distributor with strainer
Indoor coil thermistor RT2
Indoor coil thermistor RT2
Indoor coil thermistor RT2
Strainer
Flared connection
<R.V.coil> Heating ON Cooling OFF
PCH-2(O.D.3.2 I.D.1.6-R230) PCH-2.5(O.D.3.2 I.D.1.8-R430) PCH-3(O.D.4.0 I.D.2.0-R280)
Indoor unit
Indoor heat exchanger
Refrigerant pipe (option)
19.05
mm( 3/4)
(with heat insulator)
Flexible tube
Ball valve
Strainer
4-way valve
Oil separator
Service port
Service port
High pressure control switch
Outdoor unit
Outdoor heat exchanger
Capillary tube
Restrictor valve
Strainer
Bypass valve
Compressor
Accumulator
Ball valve (with service port)
Refrigerant pipe (option)
9.52
mm( 3/8")
(with heat insulator)
Capillary tube
Restrictor valve
Distributor with strainer
Strainer
Flared connection
(O.D.3.2 ✕ I.D.2.0-R820) ✕ 2
(O.D.4.0 I.D.2.0-R350)
Thermal switch
Indoor unit
Indoor heat exchanger
Refrigerant pipe (option)
19.05
mm( 3/4")
(with heat insulator)
Flexible tube
Ball valve
Strainer
4-way valve
Oil separator
Service port
Service port
High pressure control switch
Outdoor unit
Outdoor heat exchanger
Capillary tube
Restrictor valve
Strainer
Bypass valve
Compressor
Accumulator
Ball valve (with service port)
Refrigerant pipe (option)
9.52
mm( 3/8")
(with heat insulator)
Capillary tube
Distributor with strainer
Strainer
Flared connection
PCH-5 O.D.4.0 I.D.2.4-R270
Capillary tube
PUH-5 (O.D.4.0 I.D.2.4-R840) 2 PUH-6 (O.D.4.0 I.D.2.4-R1200) 2
PCH-6 O.D.4.0 I.D.3.0-R300
Restrictor valve
Refrigerant flow in cooling Refrigerant flow in heating
Unit : mm
PCH-2(O.D.4.0 I.D.2.0-R430) PCH-2.5(O.D.4.0 I.D.2.4-R1550) PCH-3(O.D.4.0 I.D.2.4-R1070)
Outdoor coil thermistor
(RT)
Outdoor coil thermistor
(RT)
PCH-2GKHA1/PUH-2VKA2 PCH-2.5GKHA1/PUH-2.5VKA2 PCH-3GKHA1/PUH-3VKA2,PUH-3YKA2
PCH-4GKHSA1/PUH-4YKSA3
PCH-5GKHSA1/PUH-5YKSA3 PCH-6GKHSA1/PUH-6YKSA2
Page 22
22
OPERATION FLOW-CHART
8
START
Power circuit
breaker
Check SW
ON twice
Operation SW
ON
“OFF” timer
“ON” timer
STOP
Set time complete
Set time
complete
1
NO
NO
NO NO
NO
NO
NO
NO
NO
NO
NO
NO
YES
w1
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
PROTECTION DEVICE
SELF HOLD RELEASE
Remote controller
indicator lamp OFF
Trouble STOP
Remote controller
operation display
Operating mode
(COOL)
Operating mode
(DRY)
Operating mode
(HEAT)
Operating mode
(FAN)
Auto COOL/HEAT
operation
COOL operation
DRY operation
HEAT operation
FAN operation
Trouble
PROTECTION DEVICE
SELF HOLD
Remote controller
trouble display
Indoor side
Outdoor side
Fan STOP
Auxiliary heater OFF
Compressor OFF
Fan STOP
Four-way valve OFF
w2
w3
w6
w4
w5
w7
MAIN OPERATION
w1 In addition, the centralized control and remote control can be operated. w2 The modes which indicate the sources of trouble are listed below.
EO-Signal transmitting/receiving error
P1-Room temperature thermistor malfunction
P2-Indoor coil thermistor malfanction
P4-Drain sensor malfunction
P5-Drain overflow
P6-Coil frost/overheat protection
P7-System error
P8-Outdoor unit trouble
w3 The CHECK swich will show if an error has occurred in the past. w4 Fan runs on low speed for 1 minute in order to remove overheat air. w5 The 3-minute (6 minutes …heating mode) time-delay functions after compressor stops. w6 FAN or AUTO mode is selected by the indoor dipswitch setting. w7 In FAN mode, fan speed and vane operation depend on the remote controller setting. (Compressor is OFF.)
Page 23
23
COOLING OPERATION
w8 When operation stops or changes to cooling or dry mode, the auto vane turns to a horizontal angle. If operation
changes during auto vane SWING, the auto vane will continue to swing.
w9 When operating TEST RUN, the thermostat will be continuously ON.
w10 After 3 minute compressor operation, if the indoor coil thermistor reads -15°C or below for 3 minutes, the compressor
will stop for 6 minutes.
w11 Cooling area : Indoor coil temperature is more than 5 degrees above the room temperature.
Heating area : Indoor coil temperature is more than 5 degrees below the room temperature. FAN area : Indoor coil temperature is within 5 degrees either way of the room temperature.
COOL operation
Four-way valve/OFF
NO
NO
NO
NO
Vane setting notch
Initial
COOLING
w8
Downward discharge
Vane horizontal
w9
YES
Vane intial
setting
Vane 40 deg downward angle 60 deg downward angle
YES
Fan speed
LOW
YES
1 hour
YES
airflow
NO
Compressor
thermostat
ON
Allowance
cancel
NO
YES
NO
YES
YES
NO
w10
w11
3-minute time delay
NO
6-minute
time delay
NO
3-minute
compressor operation
YES
Coil frost
prevention
NO
Cooling area
YES
NO
Allowance
period
NO
6 minute
time delay
Allowance set
YES
Coil frost protection
YES
NO
NO
10-minute
compressor operation
YES
Allowance cancel
Coil frost protection
NO
16-minute
compressor operation
YES
Indoor pipe
temperature is
1!C or lower
NO
Compressor ON
1
YES
YES
Coil frost
prevention
Compressor OFF
Indoor coil tempreature is 10!C or higher
3-minute
time delay
Coil frost
prevention release
NO
YES
NO
1 min continue
FAN speed
YES
LOW
FAN speed LOW 5 min
elapse
NO
YES
Outdoor unit
trouble
Page 24
24
Heat operation
Initial
HEATING
Vane setting notch
Vane initial setting
Defrosting
Heating area
Defrost release
Defrost
30 min. elapse
Outdoor unit trouble
Four-way valve ON
Hor adjust in process
Compressor ON
Compressor
thermostat ON
Allowance cancel
Indoor piping
-15!C or lower
Outdoor unit
trouble
FAN SPEED
Very low airflow
Compressor OFF
1
3 min.restart
prevention
6 min. restart
prevention
2
A
B
B
A
1
2
1
Hot adjust start
FAN SPEED very low
Compressor ON
10-minute compressor
operation
Allowance cancel
Heating
area
FAN STOP
Airflow area
20 min.elaspe
Airflow area
Heating area
Outdoor unit
trouble
Airflow area Cooling area
Defrost operation
START
Four-way valve
OFF
Indoor piping 55!C or lower
Auxiliary heater
ON
Indoor piping 60!C or higher
Auxiliary heater OFF
Overheat remote
START
Indoor unit
70!C or higher
Allowance
period
Overload protect
Auxiliary heater
thermostat ON
Auxiliary heater ON
6-minute restart
prevention
Allowance set
Compressor OFF
Indoor piping 35!C or higher
HOT adjust
6 min. elapse
FAN SPEED
Low
FAN SPEED
Low 2 min.
elapse
FAN SPEED
setting nitch
Hot adjust
release
PCH-GKH(S)A
Type
3-minute
Auxiliary heater
OFF
Indoor coil
thermistor is 60!C
or higher
FAN speed
Low notti
Airflow 10% up
FAN setting notch
Auto COOL/HEAT
operation
Initial mode
T
1 T0
> =
COOL mode HEAT mode
COOL mode
T
1 < (T0 - 2)
After 15min.
T
1
<(T0-2)
COOL operation HEAT operation
11
T
1>(T0 + 2)
After 15min.
T
1
>(T0 + 2)
HEAT operation
Cool mode
set
NO
NO
NO
NO
NO
NO
NO
YES YES
YES
YES
YES
YES
YES
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
NO
NO
NO
NO
w17
w16
w11
w10
w11
w11
w9
w15
11
HEATING OPERATION
AUTOMATIC COOLING/HEATING OPERATION
w15 ( i ) Until Low airflow is set while in hot adjustment
(ii)While defrosting (FAN STOP) (iii)When thermostat is OFF
In the case of( i ), (ii) and (iii) above, airflow is horizontal regardless the VANE setting.
w16 When AUTO operation is started, COOL or HEAT mode is selected automatically. w17 T1 : Room temperature.
To : Set temperature
Page 25
25
w8—9 Refer to page 31~32. w12 When room temperature is 18°C or below, the compressor cannot operate.
When room temperature rises over 18°C, the compressor starts after a 3-minute time delay.
w13 Compressor ON time is decided by room temperature. Refer to page 31~32. w14 In dry operation, compressor ON makes the fan speed LOW and compressor OFF stops the fan.
It is not possible to set the fan speed with the remote controller.
DRY OPERATION
DRY
operation
Four-way valve / OFF
Initial dry operation
Room tempereature is
18°C or lower
During
compressor ON
Compressor & thermostat ON
Vane initial setting
Vane
setting notch
10-minute compressor
OFF timer start
Compressor OFF
Fan STOP
3-minute
time delay
10-minute
compressor
OFF
Compressor ON
time set
Compressor ON
Fan speed LOW
1
Compressor &
thermostat
ON
3-minute
compressor
operation
Compressor ON
time completes
NO
YES
NO
NO
YES
w14
w14
w13
YES
YES
NO
YES
NO
NO
w9
YES
YES
w9
NO
NO
w12
YES
NO
YES
w8
Page 26
26
MICROPROCESSOR CONTROL
9
Compressor and outdoor fan : ON­OFF
Operation mode change :COOL­HEAT.
1.OUTLINE OF MICROPROCESSOR CONTROL
OFF-ON switching.
COOL/DRY-AUTO-HEAT selector switching.
Thermostat setting.
TIMER mode selector-switching and Timer
setting.
HIGH-LOW fan speed switching.
AUTO Vane selector (AIR DISCHARGE)
switching.
TEST RUN switching.
CHECK mode switching.
(Self diagnostic trouble shooting)
Room temperature thermistor (RT1)
Indoor coil thermistor (RT2)
Drain sensor
Autovane’s angle setting.
Booster heater ON-OFF Control.
Drain pump : ON-OFF.
Emergency stop.
Compressor protection
device working
Defrosting START-STOP
Fan speed control.
Crankcase heater control
ON-OFF.
Self diagnostic function
Independent Control of Outdoor Unit
OUTPUT to indoor unit
INPUT from indoor unit
INPUT to remote controller
Remote controller board
Processes and transmits orders.orders.
OUTPUT to remote controller
Indoor controller board
Receives orders from remote controller and temperature data from indoor unit.
Processes orders and data.
Controls indoor and outdoor operation.
Self diagnostic function.
w System control operation. w Emergency operation. w Set by dipswitch on indoor controller board.
Transmits the power to remote controller.
OUTPUT to outdoor unit
12VDC
Non-polar, two-wire cable maximum length 500 meters
Signal
Remote controller
LCD indicator
Polar three-wire cable
12VDC
123
1 2 3
Indoor unit
Outdoor unit
FILTER
CHECK MODE
TEST RUN
4
Page 27
27
2. INDOOR UNIT CONTROL
2-1COOL operation
(1) Compressor control
1 3-minute time delay
To prevent overload, the compressor will not start within 3 minutes after stop.
2 The compressor runs when room temperature is higher than set temperature.
The compressor stops when room temperature is equal to or lower than the set temperature.
3 The compressor stops in check mode or during protective functions. 4 Coil frost prevention
To prevent indoor coil frost, the compressor will stop when the indoor coil thermistor (RT2) reads 1°C or below after the compressor has been continuously operated for at least 16 minutes or more. When the indoor coil temperature rises to 10°C or above, the compressor will start after a 3-minute time delay. NOTE : By cut off the J-5 (Jumper resistance)on indoor controller board, the start temperature of coil frost prevention
changes from 1°C to -3°C.
<How to operate>
1 Press POWER ON/OFF button. 2
Press the a button to display “f”.
3
Press the i TEMP button to set the desired temperature. NOTE: Set temperature changes 1°C when the or
button is pressed one time. Cooling 19°C to 30°C
Minimum 3 minutes w1
ON
Thermostat
Indoor fan
Auto vane
Booster heater
Drain pump (OPTIONAL)
Compressor
ON
ON
LOW or HIGH
Initially horizontal
(Changeable by remote controller setting)
LOW or HIGH
ON
OFF
OFF
30! discharge position
3 minutes
OFF
OFF
ON
OFF
OFF
Operation starts by POWER button ON.
Operation stops by POWER button OFF.
Room temperature becomes equal to set temperature.
Room temperature rises above set temperature.
discharge position
30!
<COOL operation time chart>
w1 Even if the room temperature rise above the set temperature during this period, the compressor will not start until this period has ended.
FILTER
CHECK MODE
TEST RUN
4
Page 28
28
5 Coil frost protection
When indoor coil temperatuer becomes -15°C or below,coil frost protection will proceed as follows.
<Start condition>
After the compressor has been continuously operated for 3 minutes or more,and the indoor coil temperature has been ­15° or below for 3 minutes,the coil frost protection will start.
<Coil frost protection>
Compressor stops for 6 minutes,and then restarts. lf the start condition is satisfied again during the first 10 minutes of compressor operation, both the indoor and outdoor units stop,displaying a check code of“P6”on the remote controller.
<Termination conditions>
Coil frost protection is released when the start condition is not satisfied again during the allowance, or when the COOL mode stops or changes to another mode.
(2) Indoor fan control
Indoor fan speed LOW/HIGH depends on the remote controller setting. However, if an outdoor unit abnormality is detected, the indoor fan speed will be LOW, regardless of the remote controller
setting.
When the outdoor unit abnormality detection is released and the fan speed returns to the set speed, the quiet cycle control
will work.
(a) Normal control
( i ) Fan speed LOW/HIGH depends on the remote controller setting regardless of the thermostat ON/OFF. (ii) Fan speed will remain on LOW if an abnormality in outdoor unit is detected. (5 minutes)
When the abnormality detection is released, the fan speed returns to the set speed.
1 Start-up of outdoor unit abnormality
detection.
2 Release of outdoor unit abnormality
detection.
3 Unit stop due to outdoor unit abnormality
with P8 indication.
NOTE 1 : Fan stops immediately if the unit stops or the check mode is started.
5 minutes
SET
LOW
5 minutes
SET
LOW
OFF
Page 29
29
(3) Auto vane control
Auto vane position is set to horizontal airflow at the start-up of COOL operation. It can then be changed by the remote controller.
(a) Stop mode (fixed operation) ( i ) At start-up of COOL operation, the auto vane is set to 30 degrees airflow direction. ( ii ) Discharge direction can be changed with botton.
w Vane angle can be change to upper angle by cutting off the J5-3.(Jumper resistance of indoor units)
(b) SWING mode.
( i ) The vane motor turns ON when the SWING mode is selected.
The vane motor is continuously ON during SWING mode.
When 40° degrees or 60° degrees airflow is selected with the LOW fan speed in COOL operation, “AUTO RETURN” will appear below the temperature display. One hour later, the airflow direction returns to horizontal automatically and “AUTO RETURN” will disappear. If the airflow direction is set to horizontal during “AUTO RETURN” indication, the time counting for AUTO RETURN is cancelled.
1 Fan speed : LOW
2 Fan speed : HIGH
Horizontal
40°
60°
Horizontal
40°
60°
SWING
SWING
20°
holizontal
holizontal
40
20
60
AUTO RETURN AUTO RETURN
40
60
<AUTO RETURN>
1 Fan speed : LOW
2 Fan speed : HIGH
Page 30
30
<Auto vane drive> (a) The auto vane is driven by DC12V motor. (b) Airflow direction is selected depends on the number of pulse were sended.
(c) Before start driving the auto vane, detect the standard position first, output the number of pulse to each airflow. (d) The speed of the auto vane drive for both open and close are setted at 200 pulse/sec. (d) Method of driving the auto vane.
1 Detecting the standard position :
Output 1448 (PCH-2~3),1498 (PCH-4~6)
2 Position setting :
Output the number of pulse indicated no below chart to the closing direction.
(4) Detecting abnormalities in the outdoor unit
After the compressor has been continuously operated for 3 minutes, if the difference between the indoor coil temperature and room temperature is out of RANGE C for 1 minute, the indoor fan speed will turn to LOW. Five minutes later, if the difference is still out of RANGE C,the outdoor unit is functioning abnormally. Thus, the compressor stops and check code “P8” appears on remote controler. RANGE A : Indoor coil temperature is more than 5 degrees above room temperature. RANGE B : Indoor coil temperature is within 5 degrees either way of room temperature. RANGE C : Indoor coil temperature is more than 5 degrees below room tempetature.
Indoor coil temperature minus room temperature.
+5
0
-5
RANGE A
RANGE B
RANGE C
(degree)
(5) Drain pump control (OPTION)
The drain pump works in COOL or DRY operation. When operation stops or changes to HEAT mode, the drain pump
continues to operate for 3 more minutes. The drain pump does not work in check mode.
<Drain sensor>
When both the drain pump and unit are operating, the drain sensor detects the temperature. This temperature tells
whether the drain water level is above or under the drain sensor. If the drain water level rises above the drain sensor due
to a drain pump malfunction, the unit will stop operating in order to prevent drain from overflowing. The check code “P5” on
the remote controller will display this occurrence. When either of the following conditions are satisfied, the drain sensor is
determined to be under water.
Though the drain sensor has been heated by the drain sensor heater for more than 40 seconds, its temperature rise is
less than 20 degrees.
The drain sensor temperature is below 63°C.
The number of pulse outputed after
directing the standard position
Close
Horizontal Downward A Downward B
Downward C
PCH-2~3
1448
247 435 624 813
PCH-4~6
1498
318 511 693 817
Page 31
31
<DRY operation time chart>
ON
Thermostat
Indoor fan
Auto vane
Drain pump (OPTIONAL)
Compressor
ON
ON
Low speed
LOW speed
ON
OFF
OFF
3 minutes
OFF
OFF
Booster heater
ON
OFF
OFF
Operation starts by POWER button ON.
Operation stops by POWER button OFF.
Room temperature becomes equal to set temperature.
Room temperature rises above set temperature.
Initally 35degrees (SW5-3:OFF) or 20degrees (SW5-3:ON) discharge
(Changeable by remote controller setting)
close
close
Minimum 3 minutes w1
w1 Even if the room temperature rises above the set temperature during this period, the compressor will not start until this period has ended.
2-2 DRY operation
(1) Compressor control
13-minute time delay
To prevent overload, the compressor will not start within 3 minutes after stop.
2The compressor runs when the room temperature is higher than the set temperature.
The compressor stops when the room temperature is equal to or lower than the set temperature.
3The compressor stops in check mode or during protective functions.
FILTER
CHECK MODE
TEST RUN
4
<How to operate>
1 Press POWER ON/OFF button. 2 Press the a button to display “ e ”. 3 Press the i TEMP button to set the desired temperature.
NOTE: The set temperature changes 1°C when the or
button is pressed one time. Dry 19°C to 30°C.
Page 32
32
4The compressor will not start when the room temperature is below 18:.
The compressor start intermittent operation when the power is turned ON with room temperature above 18;. The compres sor ON/OFF time depends on the themostat ON/OFF and the following room temperature.
After 3-minute compressor operation.
If the room temperature thermistor reads above 28: with themostat ON, the compressor will operate for 6 more minutes and then stop for 3 minutes.
If the room temperature thermistor reads above 26: ~ 28: with themostat ON, the compressor will operate for 4 more min utes and then stop for 3 minutes.
If the room temperature thermistor reads above 24: ~ 26: with themostat ON, the compressor will operate for 2 more min
utes and then stop for 3 minutes.
If the room temperature thermistor reads below 24: with themostat ON, the compressor will stop for 3 minutes.
If the thermistat is OFF regaedless of room temperatere, the compressor will stop for 10 minutes.
5Coil frost protection
Coil frost protection in DRY operation is the same as in COOL operation.
6Coil frost protection
Coil frost protection does not operate in DRY operation.
(2) Indoor fan control
The indoor fan runs on LOW speed during compressor operation. The fan speed cannot be changed with the remote controller. Also, the indoor fan does not run during compressor OFF.
(3) Auto vane & drain pump controls
Same as in COOL operation.
(4) Detecting abnormalities in the outdoor unit
An abnormality in the outdoor unit can not be detected in DRY operation.
Page 33
33
<HEAT operation time chart>
ON
Thermostat
Indoor fan
Auto vane
Drain pump (OPTINAL)
Compressor
ON
ON
LOW or HIGH
LOW
or HIGH
ON
OFF
OFF
OFF
OFF
OFF
Power ON lamp
ON
OFF
STAND BY lamp
ON
OFF
Booster heater
ON
OFF
Operation starts by POWER button ON.
Operation stops by POWER button OFF.
Room temperature becomes equal to set temperature.
Room temperature rises above set temperature.
close
close
Horizontal
Hot adjustment
OFF
during themostat OFF hot adjustment defrosting
{
1 Changeable by indoor Jamper resistance J1-7 and J1-8
w
w
w
From POWER ON until
warm begins to blow
Depends on remote controller setting
Depends on remote controller setting
Extra LOW 1Extra LOW 1 LOW
Minimum 3 minutes 2
Hot adjustment
Horizontal
w2 Even if the room temperature rises above the set temperature during this period, the compressor will not start until this period has ended.
2-3 HEAT operation
FILTER
CHECK MODE
TEST RUN
4
<How to operate>
1 Press POWER ON/OFF button. 2 Press the a button to display “ g ”. 3 Press the i TEMP button to set the desired temperature.
NOTE: The set temperature changes 1°C when the or
button is pressed one time.
Heating 17°C to 28°C
<Display in HEAT operation>
[DEFROST] The [DEFROST] symbol is only displayed during the defrost operation. [STANDBY] The [STANDBY] symbol is displayed from the heating operation starts until the heated air begins to blow.
Page 34
34
(1) Compressor control
13-minute time delay
To prevent overload, the compressor will not start within 3 minutes after stop.
2The compressor runs when the room temperature is higher than the set temperature.
The compressor stops when the room temperature is equal to or lower than the set temperature.
3The compressor stops in check mode or during protective functions. 4Overheat protection.
<Start condition>
When the indoor coil thermistor reads 70: or above, the overheat protection will start.
<Overheat protection>
The compressor stops for 6 minutes, and then restarts. If the start condition is satisfied again within 10 minutes of compressor operation, both the indoor and outdoor units stop, displaying a check coe of “P6” on the remote controller.
<Termination conditions>
Overheat protection is terminated when the start condition is not satisfied again during the allowance (10-minute compressor operation), when operation mode changes to other mode, or when thermostat turns OFF.
(2) Indoor fan control
(a) Normal control
(!)The indoor fan runs on EXTRA-LOW speed during the thermostat OFF.
EXTRA-LOW speed can be changed to LOW or HIGH speed by setting the Jumper resistance J1 and J1-8. If the indoor coil temperature becomes more than 5 degrees below the room temperature during the thermostat OFF, the indoor fan will stop. After, when the indoor coil temperature becomes within 5 degrees of room temperature, the indoor fan will run on EXTRA-LOW speed.
(@)Hot adjustment
Hot adjustment is a warm-up for HEAT operation. <Start conditions> The hot adjustment works under any of the following conditions.
HEAT operation starts.
Defrosting ends.
Thermostat turns ON.
<Hot adjustment> Initially, the indoor fan runs on EXTRA-LOW speed. When 5 minutes have passed or the indoor coil temperature exceeds 35:, the fan speed changes to LOW. Two minutes later, the hot adjustment ends. Then, the fan speed
depends on the remote controller setting. (#)The indoor fan stops when the indoor coil temperature is within 5 degrees either way of room temperature. ($)To eliminate the remaining heat, the indoor fan runs for the first 1 minute after the booster is turned OFF.
Page 35
35
(3) Auto vane control
(a) STOP mode (fixed operation)
( i ) The airflow direction at the start-up of HEAT operation is the same as that of the previous operation. ( ii ) The airflow direction can be charged by the remote controller setting.
In the following cases, airflow direction becomes horizontal regardless of the remote controller setting.
1 During the hot adjustment with fan speed at EXTRA-LOW 2 During defrosting with indoor fan OFF 3 During the thermostat OFF
(b) SWING mode
( i ) The vane motor turns ON when the SWING mode is selected.
The vane motor is continuously ON during SWING mode.
( ii ) In the following cases, the airflow direction is horizontal regardless of the remote controller setting.
1 During the hot adjustment with fan speed at EXTRA-LOW 2 During defrosting with indoor fan OFF 3 During thermostat OFF
(4) Booster heater control
When the room temperature is 3 degrees below from the set temperature, the booster heater will turn ON. When the room temperature is equal to the set temperature, booster heater will turn OFF. During the hot adjustment, the booster heater will not work.
< Overheat prevention >
When the indoor coil thermistor rises to 60: or above, the booster heater cannot work. When the indoor coil thermistor falls to 55: or below, the booster heater can work.
(5) Detecting abnormalities in the outdoor unit
When the outdoor unit is determined to be abnormal by the following causes, the compressor will stop and the check code “ P8 ” will appear on the remote controller display.
1 During compressor ON after hot adjustment
1 If the difference between the indoor coil temperature and room temperature is in the RANGE B, the indoor fan will
stop. 2 Within 20 minutes after entering RANGE B (except for the first 10 seconds), a) If the temperature difference enters RANGE A, the hot adjustment stasrts, b) If the temperature difference is still in RANGE B, the outdoor unit is deemed abnormal. c) If the temperature difference enters RANGE C, defrosting starts.
Within 20 minutes after entering RANGE C,
If the temperature difference does not return to RANGE B,the outdoor unit is deemed abnormal.
If the temperature difference returns to RANGE B, the next 20 minutes is an allowance period. If the difference enter
RANGE A during the allowance, defrosting ends and the hot adjustment starts. If the difference does not enter RANGE A during the allowance, the outdoor unit is deemed abnormal.
2 During compressor ON in hot adjustment
After 30 minutes of defrosting in hot adjustment, if the temperature difference is still in RANGE C, the outdoor unit is determined to be abnormal.
3 During compressor OFF
After 20 minutes of thermostat OFF, if the indoor coil thermistor reads -25°C or below, the outdoor unit is determined to be abnormal.
horizontal
20° 40°
60°
SWING
w1 (See the next page)
Page 36
36
(6) Indoor coil thermistor abnormality detection
An abnormality can be detected during compressor ON, except for the following.
For the first 30 minutes after the temperature difference between the indoor coil temperature and room temperature enters the RANGE C.
When the temperature difference enters the RANGE C until it moves to the RANGE B.
(7) Defrosting operation
After the outdoor unit starts the defrosting operation, when the temperature difference beetween the indoor coil temperature and room temperature gets out of RANGE A and into RANGE B, the indoor unit starts the defrosting mode. After the outdoor unit stops the defrosting operation, when the temperature difference returns to the RANGE A, the indoor unit stops the defrosting mode. While the indoor unit is in the defrosting mode, the indoor fan and the booster heater stop.
w1 RANGE A : Indoor coil temperature is more than 5 degrees above room temperataure.
RANGE B : Indoor coil temperature is within 5 degrees either way of room temperature. RANGE C : Indoor coil temperature is more than 5 degrees below room temperature
Indoor coil temperature minus room temperature
+5
0
-5
RANGE A
RANGE B
RANGE C
(degree)
Page 37
37
2-4 AUTO operation (Automatic COOL/HEAT change over operation)
(1) Initial mode
1 When AUTO operation starts after unit OFF.
If the room temperature is higher than the set temperature, operation starts in COOL mode.
If the room temperature is equal to or lower than the set temperature, operation starts HEAT mode.
2 When AUTO operation starts after COOL or HEAT operation, the previous mode continues.
(2) Mode change
1 HEAT mode changes to cool mode when 15 minutes have passed since the room temperature became 2 degrees
above the set temperature.
2 COOL mode changes to HEAT mode when 15 minutes have passed since the room temperature became 2 degrees
below the set temperature.
(3) Temperature range
AUTO operation is available under the outside air temperatures as follows.
Mode change (HEAT COOL)
When room temperature becomes 2 degrees above the set temperature,the operation mode can not be changed for 15 minutes.
(degree)
To+2
To:Set temperature (19 28 )
To+1
To
To - 1
To - 2
Compressor
Start
HEAT mode HEAT mode
Mode change
15 minutes
Minimum 3 minutes
15 minutes
Minimum 3 minutes
COOL mode
(COOL HEAT)
ON OFF
-9 0 1020304046
-8.5
Cooling range
(Outside air temperature)
Heating range
-5
FILTER
CHECK MODE
TEST RUN
4
<How to operate>
1 Press POWER ON/OFF button. 2 Press the button to display “
3 Press the TEMP button to set the desired temperature.
NOTE: The set temperature changes 1°C when the or
button is pressed one time. Automatic 19 to 28°C
“AUTOMATIC” works to change by itself the operation mode either to cooling or heating according to the room temperature.
Page 38
38
<How to operate>
To change the air flow direction, press button.
NOTE: Vane angle can be change to upper angle by cutting off the J5-3.
(Jamper resistance of indoor units)
(1) COOL/DRY operation
At the start-up of COOL or DRY operation, the airflow direction in automatically set to horizontal. After, it can be changed
to another direction with button on the remote controller.
<Auto return>
When 40° or 60° airflow is set with fan speed in LOW, “AUTO RETURN” appears below the room temperature display.
One hour later the direction changes to horizontal degrees, automatically and “AUTO RETURN” disappears.
(2) HEAT operation
At the start-up of HEAT operation, airflow direction depends on the setting of the last operation. After, it can be changed to another direction with button. The airflow direction shifts to horizontal regardless of the
remote controller settings under any of the following conditions.
Thermostat OFF
Defrosting
Indoor fan speed EXTRA-LOW in hot adjustment
Available in COOL operation with fan speed on HIGH or in HEAT operation. Unavailable in DRY operation. If fan speed changes from LOW to HIGH during 20° downward airflow in COOL mode, the direction automatically changes to horizontal.
Horizontal
1
20˚
2
40˚
3
60˚
4
swing
5
2-5 Auto vane control
FILTER
CHECK MODE
TEST RUN
4
Changes by pressing the button.
Page 39
39
<Timer function>
AUTO STOP ·········The air conditioner stops after the set time lapses. AUTO START ········The air conditioner starts after the set time lapses. TIMER OFF ··········Timer is not active.
<How to operate>
1. Press POWER ON/OFF button.
2. Press “ ” button to select AUTO STOP or AUTO START.
3. Press “ ” button to set desired time. Time setting is in 1 hour units for up to 24 hours. Each time HOURS button is pressed, set time increases by 1 hour. When HOURS button is pressed and held, the set time increases
by 1 hour every 0.5 seconds.
4. To cancel the timer operation, press POWER ON/OFF button.
2-7 Test run <Before test run>
After installing, wiring, and piping the indoor and outdoor units, check for refrigerant leakage, looseness in power supply or contorol wiring, and mistaken polarity.
Use a 500-volt megger to check the resistance between the power supply terminal block and ground to make sure that it is at least 1.0MΩ.
Attention: Do not use the air conditioner if resistance is less than 1.0MΩ.
This setting will stop the air conditioner in 8 hours. With the lapse of time, time display changes in 1 hour units, showing remaining time.
2-6 TIMER operation
OFF
TEST RUN button
TEST RUN
Indoor coil temperature code
Display
Display
FILTER
CHECK MODE
TEST RUN
4
Remote controller
1
Turn on main switch,12 hours before proceeding to step 2 to allow
for crankcase heater operation.
2
Push the TEST RUN button twice and indication of TEST RUN will
be shown on the liquid crystal display.
4
Push button LOW/HIGH to check that the fan speed changes
properly.
6
After the check is finished leave the test run mode, push the power
ON/OFF button.
It can also be stopped by pushing the timer MODE button.
5
Check the operation of outdoor unit fans.This unit controls the
rotation speed and performance capacity of fans.ln some cases,it may rotate at low speed as the condition of outside air requires and the speed will be kept unless the performance has become deficient.
Therefore,when the condition of outside air demands,there may be
such cases as the fan stops or rotates reversely.
Please note that these symptoms are not mulfunction.
3
Press the button to display , COOL/DRY(or HEAT)to
confirm that cool (or warm) air is blown out.
(At heating operation, there may be a short delay before warm air
begins to blow out.)
*The above figure shows the state of TEST
RUN at cooling operation.
When a TEST RUN is started,the timer shall be set to 2 hours. The unit will automatically turn off after 2 hours.
<Timer setting example>
FILTER
CHECK MODE
TEST RUN
4
Page 40
40
(1) Indoor coil temperature code
During the test run, the indoor coil temperature code from 1 to 15 is displayed on the remote controller instead of room temperature. The code should fall with the lapse of time in normal COOL operation, and should rise in normal HEAT operation.
(2) Trouble during test run
If the unit malfunctions during the test run, refer to section 10 in this manual entitled “TROUBLESHOOTING.”
When the optional program timer is connected to the conditioner, refer to its operating instructions.
2-8 Emergency operation
When the remote controller or microprocessor malfunctions but all other parts are normal, emergency operation is started by setting the dipswitch SW3 on the indoor controller board.
<Before emergency operation>
1. Make sure the compressor and the indoor fan are operating normally.
2. Locate the defect with the self-diagnostic function. When the self-diagnostic function indicates “protective function is working”, release the protective function before starting the emergency operation. CAUTION: When the self-diagnostic function indicates a check code of “P5” (drain pump malfunction), DO NOT start
the emergency operation because the drain may overflow.
<How to operate>
1. For emergency cooling, set the dipswitch SW3-1 to ON and SW3-2 to OFF. For emergency heating, set the dipswitch SW3-1,2 to ON.
2. Turn ON the outdoor unit breaker and then ON the indoor unit breaker.
Emergency operation will now start.
3. During emergency operation, the indoor fan operates on high speed, but the swing louvers and the auto vanes do not operate.
4. To stop emergency operation, turn OFF the indoor unit breaker.
NOTE: The remote controller POWER ON/OFF button can not start/stop emergency operations.
CAUTION: Do not use emergency cooling for more than 10 hours, as the indoor coil may freeze.
1 ON
1
2
1.2 ON
1
2
1-2 OFF
1
2
Emergency cooling
Emergency heating
Normal operation
Microcessor board
Code 1 2 3 4 5 6 7 8
Code 9 10 11 12 13 14 15
Indoor coil temperature
Indoor coil temperature
-40~1: ~10: ~15: ~20: ~25: ~30: ~35: ~40:
~45: ~50: ~55: ~60: ~70: ~90:
Thermistor abnormality
Page 41
2-9 Interlock with ventilation system (LOSSNAY)
Mr. SLIM/LOSSNAY interlock operation is available by using the optional parts listed below.
(1) System organization
Relay box (PZ-12RB-E)
Relay box
LOSSNAY
Mr. SLIM
Remote controller
Power supply
LOSSNAY
Mr. SLIM
Remote controller
LOSSNAY control switch (PZ-05SLB
Power supply
2-E) LOSSNAY control switch
(PZ-05SLB
Remote display adapter (PAC-SA88HA-E)
2-E)
(2) LOSSNAY models connectable to Mr. SLIM are : LGH-15RS-E, LGH-50RS-E
LGH-25RS-E, LGH-80RS-E LGH-35RS-E, LGH-100RS-E
(3) Reqired parts are:
Relay box (PZ-12RB-E)…Contact capacity 10A
Remote display adapter (PAC-SA88HA-E)…An optional part for Mr. SLIM
2-E)
LOSSNAY control switch (PZ-05SLB
For LOSSNAY individual operation
(4) Operation
1LOSSNAY turns ON/OFF according to Mr. SLIM ON/OFF 2While Mr. SLIM is OFF, LOSSNAY individual operation is available by using the LOSSNAY control switch.
When Mr. SLIM turns OFF with the LOSSNAY control switch at ON, LOSSNAY will continue to operate.
(5) Wiring.
2When the LOSSNAY control switch is not used:1When the LOSSNAY control switch is used
Remote controller
Power supply 50Hz 220 240V
10m
Connecting wire
0.13mm or over
Connecting wire solid wire,
1.6 or 2.0 (field supplied)
Circuit breaker
(field supplied) L N
PL
HIGH
N
LOSSNAY control switch (PZ-05SLB
Insulation is needed
2
Indoor controller
N L
LOW
DAMPER
2-E)
Mr. SLIM
board
Connector
CN51
ORN
RED
BRN
GRN
YLW
Junction box (field supplied)
Power supply for Mr. SLIM 220 240V AC
Relay box
(PZ-12RB-E)
YLW
A
ORN
B
RED
L
WHT
N
RED
HIGH
N
WHT
LOSSNAY
Terminal block
ORN
LOW
RED
HIGH
WHT
N
RED
DAMPER
ORN
DAMPER
WHT
Relay box
(PZ-12RB-E)
Terminal block
A B L N HIGH N
Mr.SLIM CN51
8
7
4
6 2
5
3
1
12V DC
L
Power supply 220 240V AC
Circuit breaker
N
NOTE: For further information, refer to the
LOSSNAY technical & service manual.
LOSSNAY
Terminal block
ORN
LOW
RED
HIGH
WHT
N
RED
DAMPER
ORN
DAMPER
WHT
41
Page 42
42
2-10 Dip switch functions
Each figure shows the initial factory setting.
1 On remote controller board
(1) SW17(Address selector)
SW17-1~6) For address setting SW17-7) When two remote controllers are used,this switch sets the controller function.
OFF:The remote controller is set as a main controller. ON:The remote controller is set as a sub controller.
SW17-8) Switch for system back-up (This switch is unavailable for PLH-GKHA.Keep this switch at OFF.)
OFF:Without back-up ON:With back-up
(2) SW18 (Function selector)
SW18-1) Switch for timer
OFF:Single day ON:Timer every day
SW18-2) Switch for filter sign
OFF:Filter sign absent ON:Filter sign present
SW18-3) Switch for filter sign time setting.
OFF:100Hr ON:2500Hr
SW18-4) Not yet used.
1 2 3 4 5 6 7 8
ON OFF
1 2 3 4
ON OFF
J1-4) Switch for drain pump
Provided :The drain pump works in only COOL operation. Not Provided :The drain pump works in both COOL and HEAT operation.
J1-5) Switch to change the temperature to start coil frost prevention
Provided :1°(For all current models) Not Provided :-3°(For previous special models)
J1-6) Switch for set temperature adjustment in HEAT mode
During HEAT operation,warm air collects near the ceiling.When the indoor unit is installed near the ceiling,the temperature read by room temperature thermistor differs from the actual living-space temperature by about 4 degrees. Therefore,the room temperature read by room temperature thermistor must be lowered by 4 degrees. Provided :4-degree adjustment Not Provided :No adjustment
J1-7) Switch for fan speed during thermostat OFF in HEAT operation
Provided :EXTRA LOW Not Provided :LOW
J1-8) Switch for fan speed during thermostat OFF in HEAT operation
Provided :EXTRA LOW or LOW(set with SW1-7) Not Provided :LOW or HIGH(set with remote controller)
J1-9) Switch for detecting abnormalities in the outdoor unit abnoamality detection
Provided :When an abnormality occurs,it is detected. Not Provided :Even if an abnormality occurs,it can not be detected.
J1-10) Switch for auto restart function
Provided :This function does not work Not Provided :This function works.
2 On indoor controller board
PCH-2,2.5,3,4,5,6,GKH(S)A
1
(1) J1 (Function selector Jumper resistors)
145678910
Page 43
43
(2) SW2 (Address selector)
Used insetting the unit-address for group control. For further information, refer to page 40.
(3) SW3 (Emergency operation switch)
Normal operation For emergency cooling For emergency heating
(4) J5 (Model selector emergency heating)
J5-2) Provided : For models with heat pump.
Not provided : For models without heat pump.
J5-3) Available : Vane horizontal angle
......
Normal
Not available : Vane horizontal angle
......
Upper angle
J5-4) This jumper is unavailable for PCH-GKA, keep this.
(5) SW6 (Model selector)
(6) SW7 (Model selector)
SW7-1,7-3,7-4) : Capacity setting
(7) J9 (Model selector)
123456 ON OFF
12 ON OFF
12 ON OFF
12 ON OFF
234
1234 ON OFF
SW6-1 OFF ON (Twin No.1) ON (Triple No.1) SW6-2 OFF ON (Twin No.2) ON (Triple No.2) SW6-3 OFF OFF ON (Triple No.3) SW6-4 OFF OFF ON
Single control Twin control Triple control
1234
ON OFF
PCH-2
ON OFF
PCH-2.5
ON OFF
PCH-3
ON OFF
PCH-4
ON OFF
PCH-5
ON OFF
PCH-6
SW7-2) Voltage change
ON : 240V OFF : 220V
23
J9-1) Provided
J9-2) Provided
}
PCH-GKHA
1234
Page 44
44
2-11 INDOOR FAN CONTROL
Each figure shows the initial factory setting.
(1) Fan motor max. rotational frequncy for PCH-GKHA
(2) Indoor fan relay output
(a) During fan ON
The indoor fan relay turns ON. One second later, the phase control will start.
(a) During fan OFF
The phase control turns OFF. One second later, the indoor fan relay will turn OFF.
Service Ref.
Voltage
(V)
100% rotational
frequency (rpm)
220 230 240 220 230 240 220 230 240 220 250 240 220 230 240 220 230 240
15Hz 1370 1380 1390 1350 1360 1370 1350 1360 1370 1150 1160 1170 1150 1170 1190 1160 1180 1200
PCH-2GKHA1
PCH-2.5GKHA1
PCH-3GKHA1
PCH-4GKHSA1
PCH-5GKHSA1
PCH-6GKHSA1
Page 45
45
3. OUTDOOR UNIT CONTROL
3-1 Outdoor fan control
The rotational frequency of outdoor fan is phase-controlled according to the outdoor coil temperature. This control allows the cooling operation even with the low outside-air temperature and the heating operation even with the high outside-air temperature.
3-2 Outdoor unit control
The outdoor unit turns ON/OFF the cooling/heating operation according to orders given from the indoor unit.
3-3 Protective functions
1 If an reversed-phase, an open phase, or an indoor controller abnormality is detected, the outdoor unit will stop operation
and the check mode will start. (For the check mode details, see page 52.)
2 If a protective function works, the compressor will stop running. Three minutes later, the compressor will restart. If the
protective function works again, the compressor will stop running and the check mode will start.
3 The protective function is memorized. 4 The memory is cleared when the POWER ON/OFF button on the remote controller is turned OFF. However, the check
mode dispaly continues until the outdoor unit receives the “operation ON” command from the indoor unit.
3-4 COOL/HEAT operation time chart
w1 If compressor restarts within 10 minutes, 4-way valve remains ON.
Thermostat
Compressor
Crankcase heater (with jumper wire J3)
Crankcase heater (without jumper wire J3)
4-way valve (COOL)
4-way valve (HEAT)
Bypass valve
Operation starts by POWER button ON.
ON
OFF
ON
OFF
ON OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
Room temperature becomes equal to set temperature.
60 minutes
60 minutes 60 minutes 60 minutes 60 minutes 60 minutes
10 minutes
3 minutes
Room temperature becomes different from set temperature.
Operation stops by POWER button OFF.
60 minutes
Repeats 60-minute ON/OFF
10 minutes 1
3 minutes
Outdoor fan
ON
OFF
Page 46
46
(1) Start conditions
A. When all of the following conditions are satisfied, defrosting will start. However, when the bypass valve turns OFF,
defrosting starts 10 minutes later. (a) More than seven minutes have passed since the compressor start-up. (b) The outdoor coil thermistor reads -5°C or below. (c) The outdoor fan motor output step is 100% (d) Total time of compressor operation exceeds 30 minutes, and the outdoor coil temperature has fallen by 8 degrees or
more in comparison with that of 10 minutes after the compressor start-up.
NOTE: The outdoor coil temperature of 10 minutes after the compressor start-up is memorized until the defrosting
operation has ended.
B. When all of the following conditions are satisfied, defrosting will start.
(a) ~ (c) The same as above (a) ~ (c) in item A (d) Total time of compressor operation exceeds “defrost interval”.
Further information on the defrost interval is described in (3).
C. After the total time of compressor operation exceeds the defrost interval, the thermostat repeats ON/OFF three times.
Two minutes after the fourth “ON” of the thermostat, if the outdoor coil thermistor reads -5°C or below and the fan output output is 100%, defrosting will start.
NOTE: The count of the thermostat ON/OFF is cleared by the compressor-OFF command or defrosting start-up.
(2) During defrosting
Even if the thermostat turns OFF, defrosting continues.
The 4-way valve, bypass valve, outdoor fan, and indoor fan are OFF.
ON
Outdoor fan
Compressor
4-way valve
Bypass valve
Auto vane
Indoor fan
35degrees(SW5-3 OFF)or 20degrees(SW5-3:ON)discharge direction
(Remote controller still displays set direction.)
Outdoor unit
Indoor unit
ON
Set direction
ON
OFF
OFF
OFF
ON OFF
ON
OFF
ON OFF
Set direction
Defrosting starts.
Defrosting stops.
3-5 Defrosting in HEAT mode <Defrosting time chart>
Page 47
47
(3) Defrost interval
The defrost interval time is determined as follows.
Initial defrost interval is 50 minutes.
The defrost interval after defrosting depends on the preceding defrosting time as shown below.
NOTE1:If the unit stops during defrosting , the next defrost interval will be 50 minutes. NOTE2:If a protection function works for the first time during defrosting, the compressor will stop.
After a 3-minute time delay, defrosting will restart. In this case, a 3-minute time delay is included with the defrosting time. If the protection function works for the second time, the unit stops operation and displays the check code. The next defrost interval will be 30 mimutes.
NOTE3:When the defrosting has ended, the total time of the compressor operation is cleard.
(4) Termination conditions
Defrosting finishes when any of the following conditions are satisfied.
1Defrosting has continued for 15 munites. 2Outdoor coil thermistor reads 22°C or above for the first 75 seconds after defrosting start-up. 3Outdoor coil thermistor reads 8°C or above after the 75-second defrosting. 4Power ON/OFF button is turned OFF during defrosting.
3-6 Actuators (1) Bypass valve control
<Cooling mode> 1When the unit stops due to the coil frost prevention, the bypass valve turns ON. When one hour ahs passed since the
compressor stopped, the bypass valve returns to OFF.
2When the compressor operates with the bypass valve at ON for more than 30 minutes, the bypass valve turns OFF. 3When the compressor stops with the bypass valve at OFF, the bypass valve turns ON and remains ON for three
minutes.
<Heating mode> 1When the unit starts for the first time after the circuit breaker has been turned ON, or when it starts after the
compressor OFF of 30 minutes or more, if the outdoor coil thermistor reads 12°C or more, the bypass valve turns ON.
2When the high pressure switch (63H1) works, the bypass valve turns ON. 3When the bypass has been ON for 30 minutes:
If the high pressure switch has already returned, the bypass valve turns to OFF.
If not, the fan output step keeps 70 for three minutes. Meanwhile, if the high pressure switch returns, the bypass
valve turns OFF. Otherwise the normal fan control starts.
4When the operation mode changes or stops, the bypass valve turns ON and remains ON for three minutes. <Defrosting operation>
1The bypass valve is OFF.
(2) Crankcase heater control
1With jumper wire J3
The crankcase heater is ON from when the power is turned ON until the compressor starts, and then turns ON one hour after the compressor stops.
2Without jumper wire J3
The crankcase heater is ON from when the power is turned ON until the compressor starts, and repeats 1-hour ON and 1-hour OFF.
Defrosting operation time Next defrost interval 3 minutes or below 120 minutes 3 to 7 minutes 80 minutes 7 to 10 minutes 60 minutes 10 to 15 minutes 40 minutes 15 minutes (Maximum) 30 minutes
Page 48
48
3-7 Service functions (1) Compulsory defrositng
1When all of the following conditions are satisfied, pressing SW2 starts the compulsory defrosting.
During HEAT mode
The compressor is ON.
The outdoor coil temperature is being displayed by LED. (Outdoor controller board dip switch SW3-1 : OFF, SW3-2 :
ON)
The outdoor coil thermistor reads 8°C or below.
2The operation state and the termination conditions of the compulsory defrosting are the same as those of the normal
defrosting. As an exception, the defrost interval after the defrosting completion is 50 minutes.
(2) Fixed fan-output
While the compressor is operating (exept during defrosting) and the fan output step is indicated by LED, pressing SW2 fixes the fan output. The fixed fan-output can be released when any of the following conditions are satisfied.
1SW2 is pressed again. 2SW3 setting is changed. 3The compressor stops. 4Defrosting operation starts.
(3) Function of switches on the outdoor controller board
SW1: Clears the check code memory (push-button switch) SW2: Switches the output state indication and the check code display (push-button switch) SW3-1,2: Switches the output state indication items (dip swtich) For further information, refer to page 47.
(4) 100% fan output
Fan output is fixed to 100% by shorting the connector CN22. However, the fan stops during compressor OFF or defrosting. Open-circuit of CN22 restarts the normal fan control.
(5) Time shorterning
Short circuit of the connector CN21 shortens the time as follows
1Fan control period: 30 seconds 3 seconds 2Three-minutes time delay function : 3 minites 3 seconds 3Max. time of defrosting : 15 minites 15 seconds 4Defrost interval : 30 ~ 120 minutes 3 ~ 12 seconds 5Compressor ON/OFF time for bypass valve ON/OFF : 30 minutes 3 seconds 6Compressor ON time to start other functions : x minutes x seconds 7Crankcase heater operation : 1 hour 6 seconds
Page 49
49
10
TROUBLESHOOTING
Symptom Cause Check points
The display “CENTRALLY CONTROLLED” on remote controller dose not disappear.
1) Wrong address setting of remote controller/indoor controller board.
2) Timer adapter is connected to the remote controller.
3) Singnal transmission error between indoor unit and remote controller.
1) Check the address setting of remote controller and indoor controller.
2) Make sure the timer adapter is used correctly.
3) 1 Turn another remote controller’s DIP SW17-
7 ON to make it sub controller.
2 Connect the sub controller to the unit, and
turn circuit breaker ON.
If the display “centrally controlled”
disappears, replace the original remote controller.
If the display remains the same, replace the
When remote controller POWER button is turned ON, the check code “EO”appears.
1) Signal transmission error between indoor unit and remote controller
1) 1 Connect a sub remote controller. 2 Turn circuit breaker ON.
If the display “centrally controlled” remains, replace the indoor controller board.
3 If the display disappears, turn the remote
controller POWER button ON and check as follows.
When remote controller POWER button is turned ON, operating display appears, but disappears soon.
1) Short circuit of indoor/outdoor connecting wire
2) Short circuit of transmission wire.
3) Short circuit of drain sensor heater circuit.
4) Wrong operation of remote controller due to noise wave emitted by other appliances.
1), 2) Check the wire
3) Measure the resistance of the drain sensor connector CN50 1 ~ 3. Normal resistance should be 82Ω.
4) Turn the circuit breaker OFF, and then turn ON.
If the remote controller remains abnormal, despite the above measures, replace the indoor controller board.
Despite turning POWER button ON, the remote controller display does not appear.
1) Damaged remote controller.
2) Short circuit of transmission wire.
3) Bad contact of indoor CN40.
4) CN40 is attached to a sub unit.
5) Damaged transformer.
6) Bad contact of CN40.
7) Blown fuse.
8) Circuit breaker OFF.
1) Measure the voltage between terminals of remote controller. If no voltage, remove the terminals and measure the voltage between wires. If the voltage is between 6VDC and 12V, replace the remote controller.
2) ~ 8) Check each point.
If it is not defective, replace the indoor controller board.
1.TROUBLES IN TEST RUN
1
2
3
4
Remote controller
Operating Display
Operating Display
No Display
No Display
Sub remote controller
EO Display
Operating Display
EO Display
Operating Display
Malfunction
Malfunction of indoor Unit
Malfunction of Remote controller
Malfunction of indoor Unit and Remote Controller
Malfunction of Remote controller
Page 50
50
2. SELF DIAGNOSTIC FUNCTION WITH REMOTE CONTROLLER
2-1 When malfunction occurs during operation
When a malfunction occurs, the indoor and outdoor units stop and the malfunction is displayed on the LCD of the remote controller. (1) ON the set temperature display part, “CHECK” appears, and the unit
address and the check code are diplayed alternately at one-second intervals. (Check mode)
2-2 How to use the self diagnostic function for service A. For normal control with one unit and one remote controller
(1) Pressing the CHECK. button on the remote controller twice starts the self diagnostic function. (2) During the self diagnostic function, “CHECK” appears at two positions on the remote controller display. Then, at least
10 seconds later, the unit address and the check code is alternately displayed at one-second intervals.
(3) Check and repair the unit according to the check code. (Refer to the next page.)
2-3 For group control using one remote controller
(1) Press the TEMP. or TEMP. button on the remote controller to advance or go back to the unit address.
Each time TEMP. button is pressed, the unit address advances by one. Each time TEMP. button is pressed, the unit address goes back by one. The check code and the unit address, appear alternately.
(2) The check code “U8” means no malfunction has occurred since installation.
The check code “EO” means the following conditions:
The unit address displayed on the remote controller does not apply to any unit.
Power is not supplied to the unit.
Signal transmitting/receiving circuit is abnormal.
(3) Check and repair the unit according to the check code. (Refer to the next page.)
CHECK
°C
CHECK
°C
Example
Altenately
displayed
Unit address Check code
(2) When one remote controller controls several units in the group
control, the LCD shows the unit address and check code of the first malfunctioning unit.
(3) To cancel the check mode, press the ON/OFF button. In remote
ON/OFF control, press the remote ON/OFF switch. In centralized control, turn OFF the ON/OFF button of centralized controller.
NOTE: The latest check code is memorized, even if the check mode is cancelled by the way mentioned above. It takes
60 seconds maximum to display the memorized check code.
FILTER
CHECK MODE
TEST RUN
4
CHECK mode
Page 51
51
Check
code
Diagnosis of malfunction Cause Check points
EO Signal transmitting/receiving
error
(Indoor controller does not
respond to remote controller signal.)
During individual unit control
1) Bad contact of transmission wire
2) Signal transmitting/receiving circuit is abnormal.
1) Check the transmission wire.
2) Check with another remote controller. If “EO” is still indicated, replace the indoor controller board. If other check code appears. replace the original remote controller.
P3 Signal transmission error
(Remote controller does not
respond to indoor controller signal.)
1) Bad contact of transmission wire
2) Signal transmitting/receiving circuit is abnormal.
3) Wrong operation due to noise wave emitted by other appliances
1) Check the transmission wire.
2) Check with another remote controller. If “P3” is still indicated, replace the indoor board. If other check code appears, replace the original remote controller.
3) Short-circuit between 1 and 2 of CN40 and attach CN40 to the following units.
Second unit in twin control
Second and third units in triple control
Sub units in group control
P4 Abnormality of drain sensor 1) Bad contact of transmission
wire
2) Damaged thermistor
1) Check the connector.
2) Measure the resistance of the thermistor 4 ~
5. As for the normal resistance, refer to the case of P1.
If the resistance is normal, replace the indoor
controller board.
P5 Malfunction of drain pump 1) Malfunction of drain pump
2) Damaged drain sensor
1) Check the drain pump.
2) Check the drain sensor.
Check the drain sensor heater. Normal
resistance should be 82Ω.
If the resistance is normal, replace the indoor
controller board.
P6 Coil frost protection is
working.
1) Short cycle of air cycle
2) Dirty air filter
3) Damaged fan
4) Abnormal refrigerant
1) Clear obstructions from the air cycle.
2) Clean the air filter
3) Check the fan.
4) Check the refrigerant temperature.
P7 System error 1) Wrong address-setting
2) Signal transmitting/receiving circuit of remote controller is abnormal.
3) Wrong SW6-setting
1) Check the address-setting.
2) Check with another remote controller. If check code other than “P7” appears, replace the original remote controller.
3) Check SW6 setting.
P8 Abnormality in outdoor unit 1) Wrong wiring of indoor/outdoor
connecting wire
2) Reversed phase
3) Protection device is working
4) Damaged outdoor coil thermistor
1) Check the indoor/outdoor connecting wire.
2) Change the connection of electric wiring.
3) Check the protection device.
4) Measure the resistance of the outdoor coil thermistor. If the resistance is normal, replace the outdoor controller board.
P1P2Abnormality of room
temperature thermistor (RT1)
Abnormality of indoor coil
thermistor (RT2)
1) Bad contact of thermistor
2) Damaged thermistor
1) Check the thermistor.
2) Measure the resistance of the thermistor. Normal resistance should be as follows.
0 C ···15k 30 C·····4.3k 10 C······9.6k40 C ·····3.0k 20 C······6.3k If the resistance is normal, replace the indoor controller board.
Page 52
52
3. SERVICE DATA INDICATION BY SWITCHES ON OUTDOOR CONTROLLER BOARD
Setting dip switchs SW2 and SW3 on the outdoor controller board enables LED to show the output state and check code. Output state is shown by LED lighting, and check code by blinking. SW1 : Turning SW1 ON clears the check code. If SW1 is turned ON while the check code is blinking , the indication
changes to output state indication.
NOTE : SW1 is usually available independant of SW3 setting. As an exception, when the check code shows a
reversed phase or an open phase during the power-on-reset state, SW1 is not available.
SW2 : SW2 is turned ON by pressing, and OFF by releasing.
When SW3-1 and SW3-2 are OFF, pressing SW2 changes indication between output state and check code alternately. When SW2 is turned On with SW3-1 OFF and SW3-2 ON, the compulsory defrosting starts.
SW3 : Output state indication items depend on the combination of SW3-1 ON/OFF and SW3-2 ON/OFF.
Changed alternately by pressing SW2.
Check code Output state
Outdoor coil temperature
(bit)
Fan Output
step
(bit)
Total time of
compressor
operation(Hr)
SW3-1 OFF OFF OFF ON ON
SW3-2 OFF OFF OFF ON ON
LED
LD1
LD2
LD3
LD4
LD5
LD6
LD7
LD8
Blinking
Reversed phase
Open phase
63H2 function
51C function
26C function
Overheat protection
Outdoor coil thermistor is abnormal
Input circuit on controller board is abnormal
Compressor ON command from indoor controller
Heating operation command from indoor controller
During 63H1 function
Compressor ON
Outdoor fan ON
4-way valve ON
Bypass valve ON
Crankcase heater ON
1
2
4
8
16
32
64
128
1
2
4
8
16
32
64
128
256
512
1024
2048
4096
8192
16384
32768
Lighting
Page 53
53
3-1 Outdoor coil temperature
To obtain data on the outdoor coil temperature, add the number of bits of lighting LEDs, and see the graph below to find the temperature.
3-2 Fan output step
To obtain data on the fan output step, add the number of bits of lighting LEDs, and see the graph below to find the fan rotational frequency.
3-3 Total time of compressor operation
Compressor operation time is indicated in 256 hour units. To obtain the compressor operation time, add the hours of lighting LEDs. During the compressor operation time indication, SW2 is not available.
3-4 Check code indication
When a protection function works for the first time during operation, the operation stops and restarts after the 3-minutes time delay mode. When the protection function works again, the operation stops. (Check mode) When both SW3-1 and SW3-2 are OFF, the check code is indicated.
If the outdoor controller board receives the compressor ON command from the indoor controller board during check mode the indication changes to output state indication.
By pressing SW2 duirng normal operation. operation will continue.
The latest check code is indicated.
50
Fan output step (bit)
Fan rotational frequency (rpm)
100 150 200 250
800
600
400
200
0
50
Fan output step (bit)
Type
Fan rotational frequency (rpm)
100 150 200 250
800
600
400
200
0
Type
100
C
Temperature
80
60
40
20
0
0
(Open 8 bits)(Open 8 bits)
(Short 238 bits)(Short 238 bits)
Number of bits
50 100 150 200 255
-20
-40
1PUH-2/4K type
<50Hz>
2PUH-2.5/3/5/6K type
<50Hz>
Page 54
54
Blinking
LED
Diagnosis of malfunction Cause Check point
LD1 Reversed phase Phases L1, L2, and L3are
connected improperly.
Check the power supply connection.
LD2
Open phase Phase L2is open.
Contact of protector, such as thermal switch, opened when power was turned on.
Check the power supply.
Check each protector.
LD3 Outdoor coil thermistor is
abnormal. (Open circuit or short circuit)
Outdoor coil thermistor is broken.
Thermistor was connected incorrectly.
Measure the resistance of the thermistor.
Check the thermistor. If normal, replace the
outdoor controller board.
LD4 High pressure switch (63H2)
function
62H2 was badly connected.
63H2 was working.
Check 63H2 and the outdoor fan motor.
Check if refrigerant supply is low.
Check if air cycle is short-cycled.
LD5 Thermal relay (51C) function 51C was connected
incorrectly.
51C was working.
Check 51C, the compressor, and power supply.
LD6 Thermal switch (26C) function. 26C was connected
incorrectly.
26C is working.
Check 26C.
Check if refrigerant supply is low.
Check if the capillary tube is clogged.
LD7 Over heat protection The thermistor is broken.
Coil temperature is over
67°C.
Measure the resistance of the thermistor.
Check the outdoor fan motor.
Check if air cycle is short-cycled.
LD8 Input circuit of outdoor
controller board is abnormal.
Pulse input is abnormal. Replace the outdoor controller board.
Cause
1) Indoor/outdoor connecting wires are poorly connected. (Refer to next page.)
2) Power supply is poorly connected.
3) Connector or transformer is broken.
4) Fuse (6A) in the outdoor controller board is blown.
Check points
1) Check the connecting wires.
2) Check the power supply.
3) Check connectors and transformers.
4) Check the fuse.
4. TROUBLESHOOTING ACCORDING TO CHECK CODE
5. WHEN OUTDOOR UNIT DOES NOT WORK
Page 55
55
6. WRONG WIRING ON SITE
6-1 Between remote controller and indoor unit
If the wire is disconnected between the remote controller and the indoor unit, nothing is displayed on the remote controller when the POWER button is pressed. The beep sound will also not be heard.
6-2 Phenomenon due to wrong wiring between indoor and outdoor units
Wrong wiring Mode
Thermostat
Phenomenon
OutdoorIndoor
1 2 3
1 2 3
COOL
OFF
Operation stops.
ON
4-Way valve turns ON. 9 minutes later, check code “P8” appears on remote controller display.
HEAT
OFF
Cooling operation. Several minutes later, check code “P8” appears on remote controller display.
ON
Normal operation.
OutdoorIndoor
1 2 3
1 2 3
COOL
OFF
Outdoor unit stops.
ON
Operation stops. 9 minutes later, check code “P8” appears on remote controller display.
HEAT
OFF
Operation stops.
ON
Operation stops. 27 minutes later, check code “P8” appears on remote controller display.
OutdoorIndoor
1 2 3
1 2 3
COOL
OFF
Outdoor unit stops.
ON
Operation stops. 9 minutes later, check code “P8” appears on remote controller display.
HEAT
OFF
Operation stops.
ON
Operation stops. 27 minutes later, check code “P8” appears on remote controller display.
OutdoorIndoor
1 2 3
1 2 3
COOL
OFF
Outdoor unit stops.
ON
Operation stops. 9 minutes later, check code “P8” appears on remote controller display.
HEAT
OFF
Operation stops.
ON
Operation stops, 27 minutes later, check code “P8” appears on remote controller display.
OutdoorIndoor
1 2 3
1 2 3
COOL
OFF
Outdoor unit stops.
ON
Operation stops. 9 minutes later, check code “P8” appears on remote controller display.
HEAT
OFF
Operation stops.
ON
Operation stops. 27 minutes later, check “P8” appears on remote controller display.
Disconnection between 1 and 1 or 2
and 2.
COOL
OFF
Operation stops.
ON
Operation stops. 9 minutes later, check code “P8” appears on remote controller display.
HEAT
OFF
Operation stops. 4-way valve turns OFF.
ON
27 minutes later, check code “P8” appears on remote controller display.
Disconnection between 3 and 3.
COOL
Normal operation.
HEAT
OFF
Operation stops. 4-way valve turns ON.
ON
Operation stops. 27 minutes later check code “P8” appears on remote controller display.
Page 56
56
LOSSNAY control switch does not work.
LOSSNAY control switch can not work during interlock operation. LOSSNAY control switch is effective only while Mr. SLIM is not operating.
Symptom
LOSSNAY air speed can not be controlled in interlock operation.
LOSSNAY fan speed is fixed to HIGH during interlock operation. LOSSNAY fan speed LOW/HIGH can be switched only during LOSSNAY individual operation with the LOSSNAY contorl switch.
Cause
For LOSSNAY, troubleshooting refer to the LOSSNAY technical & service manual.
8. MR. SLIM/LOSSNAY INTERLOCK OPERATION
<Symptoms that are not malfunctions>
If any of the following symptoms occur, they are not malfunctions.
Vanes do not work.
Vane motor does not work. Connector is poorly connected. Vane motor is poorly assembled. Indoor controller board is damaged.
Unit stops after 5 to
20 seconds operation
Protection function is working.
Air discharge display
is OFF and button
does not operate.
Indoor controller board deems the auto vanes are not attached to the unit. Horizontal anlgle can not be detected.
In this case, remote controller is normal.
Power ON/OFF button is not available.
Beep sound is heard, but display is turned OFF.
Beep sound is not heard, and display remains OFF.
Indoor/outdoor connecting wire is connected incorrectly. Indoor/outdoor connecting wire shorts. Compressor protector is damaged. Deicer is broken.
Remote controller is damaged. Transmission wire is poorly connected
Transmission wire is damaged. Connector is poorly connected. Indoor terminal block is poorly connected. Remote controller terminal block is poorly connected.
Vane motor is damaged.
Refer to check code on remote controller display. See page 51.
Indoor controller is damaged. Dip switch setting is wrong.
Indoor controller is damaged.
Vane motor is damaged.
Auto vane is wired after power is turned to ON.
Poorly connected Disconnected
7. OTHER TROUBLES AND CAUSES
Vane motor is damaged.
“CENTRALLY CONTROLLED” is displayed.
Page 57
1. Removing the air intake grill
(1) Slide the intake grill holding knobs (at two locations)
backward to open the intake grill.
(2) When the intake grill left open, push the stoppers on the
rear hinges (at two locations) to pull out the intake grill.
57
11
DISASSEMBLY PROCEDURE
OPERATING PROCEDURE PHOTOS&ILLUSTRATIONS
2. Removing the electrical box
(1) Remove the air intake grill. (2) Remove the screw from the beam and remove the beam. (3) Remove the screws from the electrical cover, and
remove the electrical cover. (4) Disconnectors including CN6V and CN21. (5) Remove the screws from the electrical box and pull out
the electrical box.
<Electrical parts in the electrical box> Terminal block (for power supply) Terminal block (for in/outdoor connecting wire) Terminal block (for remote controller) Fan motor capacitor Indoor control board Relay Transformer
Figure 1
Figure 2
Photo 1
slide
Intake grill
Intake grill Holding knobs
Hinges
Pull out the intake grill
Electrical cover
Screw(electrical cover)
Screw(electrical box)
Slide to the left
Beam
Clamp
PCH-3GKHA1
Fan motor capacitor
Transformer
Relay
Indoor control board
Terminal block (in/out conncting)
Terminal block (power suppy)
Terminal block (remote control)
Page 58
58
Figure 2
OPERATING PROCEDURE PHOTOS&ILLUSTRATIONS
3. Removing the fan motor
(1) Remove the intake grill. (2) Disconnect the fan motor connector. (3) Unscrew screws for removing the motor guard. (4) Unscrew screws for removing the fan guard. (5) Remove the screw for removing the motor support at both
left and right side.
(6) Loosen the set screws at the fan motor side of the
connecting joint.
(7) Slide the fan motor to the left side and pull it out.
4. Removing the sirocco fan
(1) Remove the air intake grill. (2) Remove 1 beam. (3) Unscrew screws for removing the motor guard. (4) Unscrew screws for removing the fan guard. (5) Remove the lower casing while pressing the stoppers at
upper side of the casing. (6) Loosen the set screws at the connecting joint. (7) Remove the sirocco fan and shaft together by sliding the
shaft to the left.
(Note)
Make sure that the upper side casing is snaped to the fan plate securely with catch.
5. Removing the side panel
(1) Remove the air intake grill. (2) Remove the screw from the side panel, and remove the
side panel by sliding the panel to the front.
Screw
Side panel
Sliding the pare to the front
Photo 2
Photo 3
Screws
Motor
Set screws
Motor support
Connecting joint
Motor guard
Fan guard
Motor
Connecting joint
Sirocco fan
Casing
Bearing
Motor gurd
Page 59
59
OPERATING PROCEDURE PHOTOS
6. Removing the vane motor
(1) Remove the air intake grill. (2) Remove the left side panel. (3) Remove the relay connector of vane motor. (4) Remove the electrical box. (5) Remove the screws of vane motor, then remove vane
motor.
(Note)
Connect the lead wires and connectors properly and place them in the proper position so that the wires are not pinched by other parts.
7. Removing the Under panel
(1) Remove the air intake grill. (2) Remove the beam. (3) Remove the side panel (right and left). (4) Unscrew the screws of the under panel, then remove the
under panel.
w Weight of the under panel : app. 2kg.
7. Removing the Indoor coil thermistor
(1) Remove the air intake grill. (2) Remove the right side panel. (3) Remove the relay connector of the pipe thermistor. (4) Remove the screw, and remove the check panel. (5) Extract the indoor coil thermistor from the holder. <Caution for the installation>
There is a possibility for the short circuit when connector gets wet by water through the thermistor lead wire. Therefore, lead wire of the indoor coil thermistor should be traped as shown in the photo 5.
Photo 4
Photo 5
Photo 6
Photo 7
Screw
Screw
Screw
Hold Indoor coil thermistor Trap
Check panel
Relay connector of the vane motor
Vane motor
Under panel
Relay connector of the pipe thermistor
Left side panel
Page 60
60
OPERATING PROCEDURE PHOTOS
9. Removing the drain pan (option)
(1) Remove the air intake grill. (2) Remove the beam. (3) Remove the side panel (right and left). (4) Remove the under panel. Remove the screws of the right
and left side drain pan. (5) Remove the insulation in center of the drain pan, and
after removing the screw, remove the drain pan.
(Note)
Please aware that there might be drain left in the drain pan when you remove the drain pump (option).
10. Removing the guide vane
(1) Remove the intake grill. (2) Remove the beam. (3) Remove the side panel (right and left). (4) Remove the under panel. (5) Remove the drain pan. (6) Remove the screw from the guide vane, then remove the
guide vane.
11. Removing the Auto vane
(1) Remove the intake grill. (2) Remove the left side panel. (3) Remove the left side box. (4) Remove the under panel. (5) Remove the screw from the auto vane. (6) Slide the auto vane to the right side and pull the auto vane
out.
Photo 8
Screw
Screw
Screw
Guide vane
Auto vane
Drain pan
Screw
Drain pan
Screw
(Insulation)
Photo 9
Photo 10
Page 61
61
OPERATING PROCEDURE PHOTOS
13. Removing the heat exchanger.
(1) Remove the air intake grill. (2) Remove the beam. (3) Remove the side panel (right and left). (4) Disconnect the relay connector. (5) Remove the under panel. (6) Remove the drain pan. (7) Unscrew the screw of the pipe cover, and remove the
pipe cover.
(8) Unscrew the screw of the pipe support, and remove the
pipe support.
(9) Unscrew the screw of the heat exchanger, and remove
the heat exchanger. Remove the heat exchanger with care. Since this is quite heavy, removing work should be done with more than 2 people. wWeight of heat exchanger : App. 5.3kg
Photo 11
Clamp
Connector (heater)
Screws
12. Removing the support heater.
(1) Remove the air intake grill. (2) Remove the beam. (3) Remove the side panel (right and left). (4) Remove the relay connector for the pipe thermistor. (5) Remove the under panel. (6) Remove the drain pan. (7) Remove the screw from the pipe cover, and remove the
pipe cover.
(8) Remove the screw from the pipe support, and remove the
pipe fixed support.
Photo 12
Pipe support
Pipe cover
Heat exchanger
Screws
Screws
Electrical box
Service panel
Page 62
62
12
PARTS LIST
STRUCTURAL PART PCH-2GKHA PCH-2GKHA
1
2
19 13 15
412 16
28 10
11
23
14
18
1
25
26
2032769
8
7
17
5
24
Page 63
63
Part numbers that are circled are not shown in the figure
No.
Parts No. Parts Name
R01 17J 661
1
R01 17J 662
2
R01 17J 669
3
R01 17J 676
4
R01 17J 500
5
R01 18J 500
6
R01 17J 691
7
R01 18J 691
8
R01 17J 054
9
R01 17J 651
10
R01 17J 085
11
R01 18J 086
12
R01 29J 223
13
R01 17J 067
14
R01 17J 068
15
R01 17J 002
16
R01 17J 061
17
R01 17J 808
18
R01 17J 809
19
R01 17J 070
20
R01 17J 523
21
R01 17J 072
22
R01 18J 665
23
R01 17J 666
24
R01 17J 668
25 26 27 28
– – –
RIGHT SIDE PANEL LEFT SIDE PANEL UNDER PANEL REAR PANEL L.L. FILTER L.L. FILTER GRILLE ASSY GRILLE ASSY GRILLE CATCH FRONT PANEL GUIDE VANE ASSY-6R. GUIDE VANE ASSY-6L. VANE MOTOR RIGHT SIDE BOX LEFT SIDE BOX AUTO VANE GRILLE HINGE RIGHT LEG LEFT LEG WIRELESS BOARD CASE JOINT SOCKET DRAIN HOSE COVER SIDE PLATE-R. SIDE PLATE-L. SERVICE PANEL BEAM (GA) REAR SUPPORT VANE SUPPORT
Specifications
Q'ty / set Price
PCH-2
GKHA, GKHA
Remarks
(Drawing No.)
1
Wiring Diagram Symbol
Recom-
mended
Q'ty
Unit
1 1 1 1 1 1 1 1 4 1 1 1 1
MV 1 1 1 4 1 1 1 1 1 1 1 1 2 1 1
(BG17H464H08) (BG02H454H04)
(BG02R321G06)
Amount
Page 64
64
STRUCTURAL PART PCH-2.5GKHA/PCH-3GKHA PCH-4GKHSA PCH-2.5GKHA
1/PCH-3GKHA1
PCH-4GKHSA1
16
11
13
14 12
27
15
10
24
17
1
5
22252619
7
369
4
23
18
2
8
Page 65
65
No.
Parts No. Parts Name
Specifications
PCH-2.5/3
PCH-4
Wiring
Diagram
Symbol
Recom­mended
Q'ty
Unit
Amount
Q'ty / set Price
1
2
3
4
5
6 7 8 9
10
11
12 13 14
15
16
17 18 19 20 21
22
23
24 25 26
27
RIGHT SIDE PANEL RIGHT SIDE PANEL LEFT SIDE PANEL LEFT SIDE PANEL L.L. FILTER REAR PANEL REAR PANEL FRONT PANEL FRONT PANEL GRILLE ASSY UNDER PANEL GRILLE HINGE GRILLE CATCH RIGHT SIDE BOX RIGHT SIDE BOX LEFT SIDE BOX LEFT SIDE BOX GUIDE VANE ASSY-6R. GUIDE VANE ASSY-6L. GUIDE VANE ASSY-6C. AUTO VANE AUTO VANE VANE MOTOR VANE MOTOR RIGHT LEG LEFT LEG WIRELESS BOARD CASE JOINT SOCKET DRAIN HOSECOVER SIDE PLATE-R. SIDE PLATE-R. SIDE PLATE-L. SIDE PLATE-L. SERVICE PANEL BEAM(GA) REAR SUPPORT VANE SUPPORT VANE SUPPORT
1
1
2 1
1
2 1 4 4 1
1
1 1 1 1
1
1 1 1 1 1 1
1
1 2 1 2
1
1 2
1
1 2 1 4 4
1
1 1 1 1
1
1 1 1 1 1 1
1
1 1 2 1
2
(BG02H454H08)
(BG02H454H04) (BG02R321G06) (BG02R805G04)
MV MV
Remarks
(Drawing No.)
R01 17J 661 R01 35J 661 R01 17J 662 R01 35J 662 R01 17J 500 R01 29J 676 R01 35J 676 R01 29J 651 R01 36J 651 R01 17J 691 R01 29J 669 R01 17J 061 R01 17J 054 R01 17J 067 R01 35J 067 R01 17J 068 R01 35J 068 R01 17J 085 R01 18J 086 R01 29J 087 R01 29J 002 R01 35J 002 R01 29J 223 R01 35J 223 R01 17J 808 R01 17J 809 R01 17J 070 R01 17J 523 R01 17J 072 R01 18J 665 R01 35J 665 R01 18J 666 R01 35J 666 R01 17J 668
— — —
GKHA
GKHA
1
GKHSA
GKHSA
1
Page 66
66
STRUCTURAL PART PCH-5GKHSA
PCH-6GKHSA PCH-5GKHSA
1
PCH-6GKHSA1
20
14 16 12 29 13 11
17
10 24
15
26
1
27
28
21
3
5
79
8
18
4
25
2
6
19
Page 67
67
No.
Parts No. Parts Name
R01 35J 661
1
R01 35J 662
2
R01 41J 669
3
R01 41J 676
4
R01 17J 500
5
R01 18J 500
6
R01 17J 691
7
R01 18J 691
8
R01 17J 054
9
R01 41J 651
10
R01 41J 085
11
R01 42J 086
12
R01 43J 087
13
R01 35J 223
14
R01 35J 067
15
R01 35J 068
16
R01 41J 002
17
R01 17J 061
18
R01 17J 808
19
R01 17J 809
20
R01 17J 070
21
R01 17J 523
22
R01 17J 072
23
R01 35J 665
24
R01 35J 666
25
R01 17J 668
26 27 28 29
— — —
RIGHT SIDE PANEL LEFT SIDE PANEL UNDER PANEL REAR PANEL L.L. FILTER L.L. FILTER GRILLE ASSY GRILLE ASSY GRILLE CATCH FRONT PANEL GUIDE VANE ASSY-5R. GUIDE VANE ASSY-5L. GUIDE VANE ASSY-5C. VANE MOTOR RIGHT SIDE BOX LEFT SIDE BOX AUTO VANE GRILLE HINGE RIGHT LEG LEFT LEG WIRELESS BOARD CASE JOINT SOCKET DRAIN HOSE COVER SIDE PLATE-R. SIDE PLATE-L. SERVICE PANEL BEAM(GA) REAR SUPPORT VANE SUPPORT
Specifications
Q'ty / set Price
PCH-5/6
Remarks
(Drawing No.)
GKHSA, GKHSA1
Wiring
Diagram
Symbol
Recom-
mended
Q'ty
1 1 1 1 2 1 2 1 4 1 1 1 2 1
MV
1 1 1 4 1 1 1 1 1 1 1 1 3 1 3
(BG17H464H08) (BG02H454H04) (BG02R805G04)
Unit
Amount
Page 68
68
No.
Parts No. Parts Name Specifications
PCH-2
GKHA, GKHA
1
Wiring
Diagram
Symbol
Recom­mended
Q'ty
Unit
Amount
Q'ty / set Price
1 2 3 4 5 6 7 8
9
10 11 12 13 14 15 16 17
FAN MOTOR MOTOR LEG PIECE (MOTOR) CASING SIROCCO FAN INDOOR COIL THERMISTOR HEATER ELEMENT THERMAL SWITCH INSULATOR INSULATOR THERMAL FUSE DRAIN PAN ASSY ROOM TEMPERATURE THERMISTOR HEAT EXCHANGER DRAIN PLUG FAN GUARD FAN GUARD FAN GUARD
1 1 1 2 2 1 3 1 3 1 1 1 1 1 1 1 1 1
MF
RT2
26H
FS1,2
RT1
Remarks
(Drawing No.)
T7W 23J 762 R01 17J 130 R01 43E 126 R01 17J 110 R01 17J 114 R01 17J 202 T7W 23J 300 R01 46K 700 R01 18J 303 R01 20J 303 R01 P02 706 R01 17J 529 R01 18J 202 R01 26J 480 R01 17J 524 T7W 17J 675 T7W 18J 675 T7J 19J 675
DO9B4P54MS
80V 467W OFF:50: ON:35:
250V 96: 10A
13
6
10
7
9
8
4
16
5
15
11
2
1
3
17
12
5
4
14
FAN AND HEATER PARTS PCH-2GKHA PCH-2GKHA
1
Page 69
69
No. Parts No. Parts Name Specifications
PCH-2.5 PCH-3
GKHA,GKHA1GKHA,GKHA
1
Wiring
Diagram
Symbol
Recom-
mended
Q'ty
Unit
Amount
Q'ty / set Price
1 2 3 4 5 6 7 8
9 10 11
12
13 14
15
16 17 18 19 20 21 22
FAN MOTOR FAN JOINT SHAFT (FAN) SLEEVE BEARING MOTOR LEG SIROCCO FAN SIROCCO FAN CASING HEATER ELEMENT THERMAL SWITCH THERMAL FUSE INSULATOR INSULATOR INDOOR COIL THERMISTOR ROOM TEMPERATURE
THERMISTOR
HEAT EXCHANGER HEAT EXCHANGER DRAIN PAN ASSY DRAIN PLUG BEARING SUPPORT FAN GUARD FAN GUARD FAN GUARD PIECE (MOTOR)
1 1 1 1 1 2 1 3 3 1 1 1 3 1 1 1
1 1 1 1 2 1 1
1 1 1 1 1 2 1 3 3 1 1 1 3 1 1
1 1 1 1 1 2 1 1
MF
H
26H
FS1,2
RT2 RT1
Remarks
(Drawing No.)
T7W 30J 762 R01 29J 116 R01 29J 100 R01 705 103 R01 29J 130 R01 29J 114 R01 33J 114 R01 17J 110 T7W 30J 300 R01 46K 700 T7W 23J 706 R01 20J 303 R01 30J 303 R01 17J 202 R01 18J 202 R01 29J 480 R01 33J 480 R01 29J 529 R01 17J 524 R01 29J 145 T7W 20J 675 T7W 21J 675 T7W 18J 675 R01 43E 126
DC9C4P70MS
80V 700W OFF:50: ON:35: 110! 15A 250V
9
13
15
11
10
6
8
21
16
20
3
19
7
17
4·18
14
2
1
5
22
12
FAN AND HEATER PARTS PCH-2.5GKHA PCH-2.5GKHA
1
PCH-3GKHA PCH-3GKHA
1
Page 70
70
No. Parts No. Parts Name Specifications
PCH-4
GKHSA, GKHSA1
Wiring
Diagram
Symbol
Recom-
mended
Q'ty
Unit
Amount
Q'ty / set Price
1 2 3 4 5 6 7 8
9 10 11 12 13
14
15 16 17 18 19 20 21 22
FAN MOTOR FAN JOINT SHAFT SLEEVE BEARING MOTOR LEG SIROCCO FAN SIROCCO FAN CASING INDOOR COIL THERMISTOR ROOM TEMPERATURE THERMISTOR HEATER ELEMENT THERMAL SWITCH THERMAL FUSE INSULATOR INSULATOR HEAT EXCHANGER DRAIN PAN ASSY DRAIN PLUG BEARING SUPPORT FAN GUARD FAN GUARD FAN GUARD PIECE (MOTOR)
1 1 1 1 1 2 1 3 1 1 3 1 1 1 3 1 1 1 1 1 2 1 1
MF
RT2 RT1
H
26H
FS1,2
Remarks
(Drawing No.)
T7W 39J 762 R01 29J 116 R01 29J 100 R01 705 103
R01 35J 130 R01 35J 114 R01 39J 114 R01 35J 110 R01 17J 202 R01 18J 202 T7W 39J 300 R01 46K 700 T7W 23J 706 R01 20J 303 R01 36J 303 R01 37J 480 R01 35J 529 R01 17J 524 R01 35J 145 T7W 22J 675 T7W 23J 675 T7W 24J 675 R01 43E 126
D10B4P90MS
80V 900W OFF:50: ON:35: 110! 15A 250V
6
8
21
16
20
3
19
7
17
11
2
1
5
22
12
13
15
9
4·18
10
FAN AND HEATER PARTS
PCH-4GKHSA
PCH-4GKHSA
1
14
Page 71
71
17
10
12
4·20
9
23
8
22
18
7
21
19
24
11
6
25
2
3
1
5
16
13
14
15
FAN AND HEATER PARTS PCH-5GKHSA PCH-5GKHSA
1
PCH-6GKHSA PCH-6GKHSA
1
No.
Parts No. Parts Name Specifications
1
T7W 43J 762
2
R01 29J 116
3
R01 29J 100
4
R01 705 103
5
R01 41J 130
6
R01 41J 114
7
R01 39J 114
8
R01 35J 114
9
R01 35J 110
10
R01 17J 202
11
R01 18J 202
12
T7W 43J 300
13
R01 46K 700
14
T7W 23J 706
15
R01 20J 303
16
R01 36J 303 R01 41J 480
17
R01 45J 480
18
R01 41J 529
19
R01 17J 524
20
R01 35J 145
21
T7W 25J 675
22
T7W 23J 675
23
T7W 24J 675
24
T7W 26J 675
25
R01 43E 126
FAN MOTOR FAN JOINT SHAFT SLEEVE BEARING MOTOR LEG SIROCCO FAN SIROCCO FAN SIROCCO FAN CASING INDOOR COIL THERMISTOR ROOM TEMPERATURE THERMISTOR HEATER ELEMENT THERMAL SWITCH THERMAL FUSE INSULATOR INSULATOR HEAT EXCHANGER HEAT EXCHANGER DRAIN PAN ASSY DRAIN PLUG BEARING SUPPORT FAN GUARD FAN GUARD FAN GUARD FAN GUARD PIECE (MOTOR)
D10B4P150MS
80V 1000W OFF:50: ON:35: 110! 15A 250V
Q'ty / set Price
PCH-5 PCH-6
GKHSA
GKHSA
GKHSA
GKHSA
1
1 1 1 1 1 1 1 2 4 1 1 3 1 1 1 6
1 1 1 1 1 1 1 2 4 1 1 3 1 1 1 6
Remarks
(Drawing No.)
1
Wiring
Diagram
Symbol
MF
RT2 RT1
H 26H FS1
Recom-
mended
Q'ty
Unit
1
1 1 1 1 1 2 1 1 1
1
1
1
1
2
1
1
1
Amount
Page 72
72
No.
Parts No. Parts Name
Specifications
Wiring
Diagram
Symbol
Recom­mended
Q'ty
Unit
Amount
Q'ty / set Price
1 2 3 4
5
6 7 8
9
10 11 12
CONTROLLER BOARD FUSE TRANSFORMER CONTROL BOX CAPACITOR RUN CAPACITOR RUN CAPACITOR TERMINAL BLOCK TERMINAL BLOCK TERMINAL BLOCK
BOX COVER
REMOTE CONTROLLER REMOTE CONTROLLER CORD RELAY
(BG00N015G14)
(BG02A804G12) (BG02A804G13) (BG02A804G14)
2
1 1 1 1 1
1 1 1 1
1 1 1
2.5/3
1 1 1 1
1
1 1 1
1
1 1 1
5/6
1 1 1 1
1 1 1 1
1
1 1 1
4
1 1 1 1
1
1 1 1
1 1 1 1
I.B
F1,2
T
C C
C TB2 TB4 TB5
R.B
250V 6.3A
3MF. 440V 4MF. 440V 6MF. 440V 3P (L,N, ) 3P (1,2,3) 2P (1,2)
10m
JC-1A DC12V
Remarks
(Drawing No.)
T7W 71J 310 T7W 520 239
T7W 23J 260
­R01 30L 255 T7W 39J 255 T7W 43J 255 T7W 521 716 T7W 517 716 T7W 512 716
-
-
­T7W 14K 200 R01 08K 305 R01 71G 215
GKHA
GKHA
1
GKHA
GKHA
1
GKHSA
GKHSA
1
GKHSA GKHSA
1
5
12
3
2
1
6
7
8
4
10
11
9
ELECTRICAL PARTS PCH-2GKHA PCH-2GKHA
1
PCH-2.5GKHA PCH-2.5GKHA
1
PCH-3GKHA PCH-3GKHA
1
PCH-4GKHSA PCH-4GKHSA
1
PCH-5GKHSA PCH-5GKHSA
1
PCH-6GKHSA PCH-6GKHSA
1
Page 73
73
13
OPTIONAL PARTS
Note 1. How to connect refrigerant pipes.
Factory supplied optional refrigerant pipings contain refrigerant at the above atmospheric pressures. As long as connection takes no more than 5 minutes, no air will enter, and there will be no need for air purging. Remove the blind caps and make the connections within 5 minutes. After the connections for the indoor and outdoor units are made, open the stop valve on the outdoor unit to allow refrigerant gas to flow. If piping length exceeds 5m, an additional charge of refrigerant in needed.
Note 2. The following main parts are cntained in the optional refrigerant piping kit.
Heat insulating cover, vinyl tapes, nipples, sleeve and flange (for wall hole), connecting cables.
1. REFRIGERANT PIPES
Service Ref. : PCH-2GKHA1/PCH-2.5GKHA1/PCH-3GKHA1
Service Ref. : PCH-4GKHSA1/PCH-5GKHSA1/PCH-6GKHSA1
2. TIMER
Part No.
PAC-SC32PTA
3. CENTRALIZED REMOTE CONTROLLER
Allows individual or combined control of up to 16 units. When using this controller, a program timer adapter (PAC-
825AD) is also needed.
Part No. PAC-805RC
4. PROGRAM TIMER ADAPTER
This part is needed when a centralized remote controller (PAC-805RC) is used.
Part No. PAC-825AD
5. TIMER ADAPTER
This adapter is needed for system control and for operation via external contacts.
Part No. PAC-SA89TA-E
6. MULTIPLE REMOTE CONTROLLER ADAPTER
This adapter is needed for remote indication (operation/check).
Part No. PAC-SA88HA-E
Optional parts connection is described in the service technical guide No.OCT01.
Model name Program timer (when set back function)
Part No. Pipe length Pipe size O.D. Connection method
PAC-05FFS-E
5m
PAC-07FFS-E
7m
PAC-10FFS-E
10m
PAC-15FFS-E
15m
Liquid : {9.52 Gas : {15.88
Indoor unit : Flared Outdoor unit : Flared
Part No. Pipe length Pipe size O.D. Connection method
PAC-SC51PI-E
5m
PAC-SC52PI-E
7m
PAC-SC53PI-E
10m
PAC-SC54PI-E
15m
Liquid : {9.52 Gas : {19.05
Indoor unit : Flared Outdoor unit : Flared
Page 74
74
7.DRAIN PUMP
Part No.
PAC-SE85DM-E
Applied Service Ref.
PCH-2/2.5/3GKHA1
PAC-SE86DM-E
PCH-4/5/6GKHSA1
8.HIGH PERFORMANCE FILTER
Part No. PAC-SE80KF-E PAC-SE81KF-E PAC-SE82KF-E
Applicable Service Ref. PCH-2GKHA
1
PCH-2.5/3/4GK(H)SA
1
PCH-5/6GKHSA
1
Motor
Casing (Inverted corn shape)
Drain water
Suction port
Flow of drain water
Rotating blabe (Inverted triangle plate)
Page 75
Page 76
HEAD OFFICE MITSUBISHI DENKI BLDG.MARUNOUCHI TOKYO100 TELEX J24532 CABLE MELCO TOKYO
cCopyright 1997 MITSUBISHI ELECTRIC ENGINEERING CO.,LTD. Issued in Jun. 1997. No. OC135 140
New publication, effective Jun. 1997 Specifications subject to change without notice.
Loading...