Mitsubishi PCA-RP71HAQ, PCA-RP71HAQ-ER, PCA-RP125HAQ Service Manual

SERVICE MANUAL
No. OCH492
REVISED EDITION-A
INDOOR UNIT
REMOTE CONTROLLER
(Option)
[Service Ref.]
CONTENTS
1. REFERENCE MANUAL
...................................
2
2. SAFETY PRECAUTION
...................................
3
3. PARTS NAMES AND FUNCTIONS
.................
6
4. SPECIFICATIONS
...........................................
10
5. NOISE CRITERION CURVES
........................
11
6. OUTLINES AND DIMENSIONS
......................
12
7. WIRING DIAGRAM
.............................................
14
8. REFRIGERANT SYSTEM DIAGRAM
.............
15
9. TROUBLESHOOTING
....................................
16
10. SPECIAL FUNCTION
.....................................
27
11. DISASSEMBLY PROCEDURE
.......................
32
ON/OFF
TEMP.
July 2014
Model name indication
Indoor unit [Model Name]
PCA-RP71HAQ
PCA-RP125HAQ
PARTS CATALOG (OCB492)
Notes:
• This manual describes service data of the indoor units only.
• RoHS compliant products have <G> mark on the spec name plate.
• Please void OCH492.
Revision:
Added
PCA-RP71HAQR-ER in
REVISED EDITION-A.
• Some descriptions have been modified.
SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS SPLIT-TYPE, AIR CONDITIONERS
2
1-1. OUTDOOR UNIT’S SERVICE MANUAL
1-2. TECHNICAL DATA BOOK
1
REFERENCE MANUAL
Model Name Service Ref. Service Manual No.
PUHZ-RP71VHA4 PUHZ-RP125/140VKA PUHZ-RP125/140/250YKA
PUHZ-RP71VHA4 PUHZ-RP125/140VKA PUHZ-RP125/140/250YKA
OCH451 OCB451
PU(H)-P71VHAR3 PU(H)-P71/125/140YHAR3
PU(H)-P71VHAR3.UK PU(H)-P71/125/140YHAR3.UK
OC379
PUHZ-P125/140VHA3R2 PUHZ-P125/140YHAR1
PUHZ-P125/140VHA3R2.UK PUHZ-P125/140YHAR1.UK
OCH415/OCB415
PUHZ-P250YHA3R2 PUHZ-P250YHA3R2 OCH424/OCB424
PUHZ-ZRP71VHA PUHZ-ZRP71VHAR1(-ER)
OCH527 OCB527
Series (Outdoor unit) Manual No.
PUHZ-RP • HA4 PUHZ-RP • KA
OCS16
PUHZ-P • VHA3 PUHZ-P • YHAR3
OCS17
PUHZ-ZRP • VKA OCS24
OCH492A
33
SAFETY PRECAUTION
2
Cautions for units utilising refrigerant R407C
2-2. CAUTIONS RELATED TO NEW REFRIGERANT
Do not use the existing refrigerant piping.
The old refrigerant and lubricant in the existing piping contains a large amount of chlorine which may cause the lubricant deterioration of the new unit.
Use “low residual oil piping”
If there is a large amount of residual oil (hydraulic oil, etc.) inside the piping and joints, deterioration of the lubricant will result.
If large amount of mineral oil enter, that can cause deterioration of refrigerant oil, etc.
Use liquid refrigerant to charge the system.
If gas refrigerant is used to seal the system, the composition of the refrigerant in the cylinder will change and performance may drop.
Do not use a refrigerant other than R407C.
If another refrigerant (R22, etc.) is used, the chlorine in the refrigerant may cause the lubricant deterioration.
Use a vacuum pump with a reverse flow check valve.
The vacuum pump oil may flow back into the refrigerant cycle and cause the lubricant deterioration.
If dust, dirt, or water enters the refrigerant cycle, deterioration of the oil and compressor trouble may result.
Ventilate the room if refrigerant leaks during operation. If refrigerant comes into contact with a flame, poisonous gases will be released.
Store the piping to be used indoors during installation, and keep both ends of the piping sealed until just before brazing. (Leave elbow joints, etc. in their packaging.)
The refrigerant oil applied to flare and flange connections must be ester oil, ether oil or alkylbenzene oil in a small amount.
2-1. ALWAYS OBSERVE FOR SAFETY
Before obtaining access to terminal, all supply circuits must be disconnected.
OCH492A
4
[3] Service tools
Use the below service tools as exclusive tools for R407C refrigerant.
[2] Refrigerant recharging
(1) Refrigerant recharging process
1Direct charging from the cylinder.
· R407C cylinder available on the market has a syphon pipe.
· Leave the syphon pipe cylinder standing and recharge it. (By liquid refrigerant)
(2) Recharge in refrigerant leakage case
· After recovering the all refrigerant in the unit, proceed to working.
· Do not release the refrigerant in the air.
· After completing the repair service, recharge the cycle with the specified amount of liquid refrigerant.
Gravimeter
Unit
[1] Cautions for service
· After recovering the all refrigerant in the unit, proceed to working.
· Do not release refrigerant in the air.
· After completing the repair service, recharge the cycle with the specified amount of liquid refrigerant.
No. Tool name Specifications
1
Gauge manifold · Only for R407C
· Use the existing fitting SPECIFICATIONS. (UNF7/16)
· Use high-tension side pressure of 3.43MPa·G or over.
2
Charge hose · Only for R407C
· Use pressure performance of 5.10MPa·G or over.
3
Electronic scale
4
Gas leak detector
· Use the detector for R134a or R407C.
5
Adaptor for reverse flow check
· Attach on vacuum pump.
6
Refrigerant charge base
7
Refrigerant cylinder · For R407C · Top of cylinder (Brown)
· Cylinder with syphon
8
Refrigerant recovery equipment
OCH492A
5
Cautions for units utilising refrigerant R410A
CAUTIONS RELATED TO NEW REFRIGERANT
Use new refrigerant pipes.
Store the piping to be used during installation indoors, and keep both ends of the piping sealed until just before brazing. (Leave elbow joints, etc. in their packaging.)
In case of using the existing pipes for R22, be careful with the followings.
· For RP71VHA3 and RP125 be sure to perform replacement operation before test run.
· Change flare nut to the one provided with this product. Use a newly flared pipe.
· Avoid using thin pipes.
Charge refrigerant from liquid phase of gas cylinder.
If the refrigerant is charged from gas phase, composition change may occur in refrigerant and the efficiency will be lowered.
Do not use refrigerant other than R410A.
If other refrigerant (R22, etc.) is used, chlorine in refrige­rant can cause deterioration of refrigerant oil, etc.
Use a vacuum pump with a reverse flow check valve.
Vacuum pump oil may flow back into refrigerant cycle and that can cause deterioration of refrigerant oil, etc.
Use the following tools specifically designed for use with R410A refrigerant.
The following tools are necessary to use R410A refrigerant.
Keep the tools with care.
If dirt, dust or moisture enter into refrigerant cycle, that can cause deterioration of refrigerant oil or malfunction of com­pressor.
Do not use a charging cylinder.
If a charging cylinder is used, the composition of refrigera­nt will change and the efficiency will be lowered.
Flare tool
Electronic refrigerant charging scale
Vacuum pump adaptor
Size adjustment gauge
Gauge manifold
Torque wrench
Gas leak detector
Charge hose
Tools for R410A
Contamination inside refrigerant piping can cause deterio­ration of refrigerant oil, etc.
If dirt, dust or moisture enter into refrigerant cycle, that can cause deterioration of refrigerant oil or malfunction of com­pressor.
If large amount of mineral oil enter, that can cause deterio­ration of refrigerant oil, etc.
The refrigerant oil applied to flare and flange connections must be ester oil, ether oil or alkylbenzene oil in a small amount.
Make sure that the inside and outside of refrige­rant piping is clean and it has no contaminants such as sulfur, oxides, dirt, shaving particles, etc, which are hazards to refrigerant cycle. In addition, use pipes with specified thickness.
Ventilate the room if refrigerant leaks during operation. If refrigerant comes into contact with a flame, poisonous gases will be released.
Never use any refrigerant other than that specified.
Doing so may cause a burst, an explosion, or fire when the unit is being used, serviced, or disposed of. Correct refrigerant is specified in the manuals and on the spec labels provided with our products. We will not be held responsible for mechanical failure, system malfunction, unit breakdown or accidents caused by failure to follow the instructions.
Use the specified refrigerant only.
[1] Cautions for service
(1) Perform service after collecting the refrigerant left in unit completely. (2) Do not release refrigerant in the air. (3) After completing service, charge the cycle with specified amount of refrigerant. (4) When performing service, install a filter drier simultaneously.
Be sure to use a filter drier for new refrigerant.
[2] Additional refrigerant charge
When charging directly from cylinder
· Check that cylinder for R410A on the market is syphon type.
· Charging should be performed with the cylinder of syphon stood vertically. (Refrigerant is charged from liquid phase.)
OCH492A
6
3
PARTS NAMES AND FUNCTIONS
3-1. Indoor (Main) Unit
Air outlet
Air intake
Oil filter (Air intake)
It prevents oil from getting into the unit.
Left/right guide vanes
Change the direction of airflow from the horizontal blower.
Up/down guide vanes
Change the direction of airflow from the vartical blower.
[3] Service tools
Use the below service tools as exclusive tools for R410A refrigerant.
Gravimeter
Unit
No. Tool name Specifications
1
Gauge manifold · Only for R410A
· Use the existing fitting
specifications
. (UNF1/2)
· Use high-tension side pressure of 5.3MPa·G or over.
2
Charge hose · Only for R410A
· Use pressure performance of 5.09MPa·G or over.
3
Electronic scale
4
Gas leak detector
· Use the detector for R134a, R407C or R410A.
5
Adaptor for reverse flow check
· Attach on vacuum pump.
6
Refrigerant charge base
7
Refrigerant cylinder · Only for R410A · Top of cylinder (Pink)
· Cylinder with syphon
8
Refrigerant recovery equipment
OCH492A
7
3-2. WIRED REMOTE CONTROLLER (OPTION) <PAR-30MAA><PAR-31MAA>
The functions which can be used are restricted according to each model.
The main display can be displayed in two different modes: "Full" and "Basic." The initial setting is "Full."
Fri
Mode Temp. Fan
Room
Cool Auto
Set temp.
Fri
Cool
Mode Temp. Fan
AutoSet temp.
1
2
3
4
5
20
19
4
3
181716
15
14
13
12
6
8
10
1
11
7
9
21
5
2
Fan speed setting appears here.
4 Fan speed
Appears while the units are operated in the energy-save mode.
Appears while the outdoor units are operated in the silent mode.
Preset temperature appears here.
Appears when the ON/OFF operation is centrally controlled.
Current time appears here.
Appears when the buttons are locked.
Indoor unit operation mode appears here.
Appears when the operation mode is centrally controlled.
15
16
2 Preset temperature
6
12
1 Operation mode
7
Indicates the vane setting.
18
Indicates the louver setting.
Indicates the ventilation setting.
Appears when the On/Off timer or Night setback function is enabled.
19
20
13
Appears
when filter needs maintenance .
Appears when the filter reset function is centrally controlled.
Appears when the preset temperature is centrally controlled.
10
9
8
Appears when the Weekly timer is enabled.
14
Appears when the preset temperature range is restricted.
21
Functions of the corresponding buttons appear here.
5 Button function guide
Appears when the built-in thermistor on the remote controller is activated to monitor the room temperature.
appears when the thermistor on the indoor unit is activated to monitor the room temperature.
17
3 Clock
(See the Installation Manual.)
Current room temperature appears here.
11 Room temperature
(See the Installation Manual.)
All icons are displayed for explanation.
5
6
1234
Press to turn ON/OFF the indoor unit.
1 ON/OFF button
This lamp lights up in green while the unit is in operation. It blinks while the remote controller is starting up or when there is an error.
Press to save the setting.
Main display: Press to change the operation mode. Main menu: Press to move the cursor down.
Press to return to the previous screen.
Main
display
: Press to decrease temperature.
Main menu: Press to move the cursor up.
Press to bring up the Main menu.
Main
display
: Press to increase temperature.
Main menu: Press to go to the previous page.
Operation settings will appear. When the backlight is off, pressing any button turns the backlight on and it will stay lit for a certain period of time depending on the screen.
Main
display
: Press to change the fan speed.
Main menu: Press to go to the next page.
6 ON/OFF lamp
2 SELECT button
7 Function button F1
3 RETURN button
8 Function button F2
4 MENU button
9 Function button F3
5 Backlit LCD
10 Function button F4
Fri
Room
Set temp.
Mode Temp. Fan
Cool Auto
Main
Main display:
Cursor Page
Main menu
Vane·Louver·Vent. (Lossnay) High power Timer Weekly timer OU silent mode
The functions of the function buttons change depending on the screen. Refer to the button function guide that appears at the bottom of the LCD for the functions they serve on a given screen. When the system is centrally controlled, the button function guide that corresponds to the locked button will not appear.
Main display Main menu
Function guide
7 8 9 10 107 8 9
When the backlight is off, pressing any button turns the backlight on and
does not perform its function. (except for the ON/OFF button)
Most settings (except ON/OFF, mode, fan speed, temperature) can be
made from the Menu screen.
Display
Full mode
Basic mode
Controller interface
Function buttons
10987
OCH492A
8
Setting and display items Setting details
Vane · Louver · Vent. (Lossnay)
Use to set the vane angle.
• Select a desired vane setting from ve different settings.
Use to turn ON / OFF the louver.
• Select a desired setting from "ON" and "OFF."
Use to set the amount of ventilation.
• Select a desired setting from "Off," "Low," and "High."
High power Use to reach the comfortable room temperature quickly.
• Units can be operated in the High-power mode for up to 30 minutes.
Timer On/Off timer* Use to set the operation On/Off times.
• Time can be set in 5-minute increments.
Auto-Off timer Use to set the Auto-Off time.
• Time can be set to a value from 30 to 240 in 10-minute increments.
Weekly timer* Use to set the weekly operation On / Off times.
• Up to eight operation patterns can be set for each day. (Not valid when the On/Off timer is enabled.)
Restriction Temp. range Use to restrict the preset temperature range.
• Different temperature ranges can be set for different operation modes.
Operation lock Use to lock selected functions.
• The locked functions cannot be operated.
Energy saving Auto return Use to get the units to operate at the preset temperature after performing energy-save operation for a specied
time period.
• Time can be set to a value from 30 and 120 in 10-minute increments. (This function will not be valid when the preset temperature ranges are restricted.)
Schedule* Set the start/stop times to operate the units in the energy-save mode for each day of the week, and set the
energy-saving rate.
• Up to four energy-save operation patterns can be set for each day.
• Time can be set in 5-minute increments.
• Energy-saving rate can be set to a value from 0% or 50 to 90% in 10% increments.
Night setback* Use to make Night setback settings.
Select "Yes" to enable the setting, and "No" to disable the setting. The temperature range and the start/stop times can be set.
Filter information Use to check the lter status.
• The lter sign can be reset.
Error information Use to check error information when an error occurs.
• Check code, error source, refrigerant address, unit model, manufacturing number, contact information (dealer's phone
number) can be displayed.
(The unit model, manufacturing number, and contact information need to be registered in advance to be displayed.)
Maintenance
Auto descending panel
Auto descending panel (Optional parts) Up / Down you can do.
Manual vane angle Use to set the vane angle for each vane to a xed position.
Initial setting Main/Sub When connecting two remote controllers, one of them needs to be designated as a sub controller.
Clock Use to set the current time.
Main display Use to swich between "Full" and "Basic" modes for the Main display.
• The initial setting is "Full."
Contrast Use to adjust screen contrast.
Display details Make the settings for the remote controller related items as necessary.
Clock: The initial settings are "Yes" and "24h" format. Temperature: Set either Celsius (°C) or Fahrenheit (°F). Room temp. : Set Show or Hide. Auto mode: Set the Auto mode display or Only Auto display.
Auto mode Whether or not to use the Auto mode can be selected by using the button.
This setting is valid only when indoor units with the Auto mode function are connected.
Administrator
password
The administrator password is required to make the settings for the following items.
• Timer setting • Energy-save setting • Weekly timer setting
• Restriction setting • Outdoor unit silent mode setting • Night set back
Language selection Use to select the desired language.
Service Test run Select "Test run" from the Service menu to bring up the Test run menu.
• Test run • Drain pump test run
Input maintenance Select "Input maintenance Info." from the Service menu to bring up the Maintenance information screen.
The following settings can be made from the Maintenance Information screen.
• Model name input • Serial No. input • Dealer information input
Function setting Make the settings for the indoor unit functions via the remote controller as necessary. Check Error history: Display the error history and execute "delete error history".
Refrigerant leak check: Refrigerant leaks can be judged. Smooth maintenance: The indoor and outdoor maintenance data can be displayed. Request code: Details of the operation data including each thermistor temperature and error history can be checked.
Self check Error history of each unit can be checked via the remote controller. Maintenance password Take the following steps to change the maintenance password. Remote controller check When the remote controller does not work properly, use the remote controller checking function to trouble-
shoot the problem.
*Clock setting is required.
Main menu list
OCH492A
9
Caution:
Only the Power on indicator lights when the unit is stopped and power supplied to the unit. If you press a button for a feature that is not installed at the indoor unit, the remote controller will display the “Not Available”
message. If you are using the remote controller to drive multiple indoor units, this message will appear only if the feature is not present at every unit connected.
When power is turned ON for the first time, it is normal that “PLEASE WAIT” is displayed on the room temperature indication (For
max. 2 minutes). Please wait until this “PLEASE WAIT” indication disappear then start the operation.
3-3. WIRED REMOTE CONTROLLER (OPTION) <PAR-21MAA>
°F°C
°F°C
ERROR CODE
AFTER
TIMER
TIME SUN MON TUE WED THU FRI SAT
ON
OFF
Hr
AFTER
FILTER
FUNCTION
ONLY1Hr.
WEEKLY
SIMPLE
AUTO OFF
PAR-21MAA
ON/OFF
FILTER
CHECK
OPERATION
CLEAR
TEST
TEMP.
MENU
BACK DAY
MONITOR/SET
CLOCK
ON/OFF
Display Section
For the purposes of explanation, all parts of the display are shown. During actual operation, only the relevant items will be lit.
Identifies the current operation
Shows the operating mode, etc. Multilanguage display is available.
“Centrally Controlled” indicator
Indicates that operation from the remote controller has been prohib­ited by a master controller.
“Timer is Off” indicator
Indicates that the timer is off.
Temperature Setting
Shows the target temperature.
Day-of-Week
Shows the current day of the week.
Time/Timer Display
Shows the current time, unless the simple or Auto Off timer is set. If the simple or Auto Off timer is set, the time to be switched off is shown.
“Sensor” indication
Displays when the remote controller sensor is used.
“Locked” indicator
Indicates that remote controller but­tons have been locked.
“Clean The Filter” indicator
To be displayed on when it is time to clean the filter.
Timer indicators
The indicator comes on if the corre­sponding timer is set.
Up/Down Air Direction indica­tor
The indicator shows the direc­tion of the outcoming airflow.
“One Hour Only” indicator
Room Temperature display
Shows the room temperature. The room temperature display range is 8 to 39°C. The display blinks if the temperature is less than 8°C or 39°C or more.
Louver display
Indicates the action of the swing louver. Does not appear if the louver is not running.
(Power On indicator)
Indicates that the power is on.
Fan Speed indicator
Shows the selected fan speed.
Ventilation indicator
Appears when the unit is running in Ventilation mode.
Operation Section
Temperature setting buttons
Down
Up
Timer Menu button (Monitor/Set button)
Mode button (Return button)
Set Time buttons
Back
Ahead
Timer On/Off button (Set Day button)
Opening the cover
ON/OFF button
Fan Speed button
Filter button (<Enter> button)
Test Run button
Check button (Clear button)
Airflow Up/Down button
Louver button ( Operation button)
To return operation number
Ventilation button ( Operation button)
To go to next operation number
Built-in temperature sensor
Displays if the airflow is set to low or downward during COOL or DRY mode. (Operation varies according to model.) The indicator goes off in 1 hour, when the airflow direction also changes.
The functions which can be used are restricted according to each model.
OCH492A
10
SPECIFICATIONS
4
kW
A A
kW
K/min (CFM)
Pa(mmAq)
dB mm (in) mm (in) mm (in) mm (in)
kg (lb)
Service Ref.
Mode Power supply (phase, cycle, voltage) Input Running current Starting current External finish Heat exchanger Fan Fan (drive) × No. Fan motor output Airflow (Low-High) External static pressure Operation control & Thermostat Noise level (Low-High) Unit drain pipe I.D. Dimensions
Weight
W
D H
INDOOR UNIT
PCA-RP125HAQ
Cooling
0.26
1.19
2.38
Heating
0.26
1.19
2.38
Single phase, 50Hz, 230V
Stainless steel
Plate fin coil
Sirocco fan (direct) × 4
0.08 + 0.08
30-38 (1,060-1,350)
0 (direct blow)
Remote controller & built-in
44-50 26 (1)
1,520 (59-7/8)
650 (25-5/8)
280 (11) 56 (124)
Cooling
0.09
0.43
0.86
Heating
0.09
0.43
0.86
Single phase, 50Hz, 230V
Stainless steel
Plate fin coil
Sirocco fan (direct) × 2
0.04
17-19 (600-670)
0 (direct blow)
Remote controller & built-in
34-38 26 (1)
1,136 (44-3/4)
650 (25-5/8)
280 (11)
41 (90)
PCA-RP71HAQ
PCA-RP71HAQ-ER
kW
A A
kW
K/min (CFM)
Pa (mmAq)
dB mm (in) mm (in) mm (in) mm (in)
kg (lb)
Service Ref.
Mode Power supply (phase, cycle, voltage) Input Running current Starting current External finish Heat exchanger Fan Fan (drive) × No. Fan motor output Airflow (Low-High) External static pressure Operation control & Thermostat Noise level (Low-High) Unit drain pipe I.D. Dimensions
Weight
W
D H
INDOOR UNIT
OCH492A
11
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB ( 0dB = 0.0002 µbar )
BAND CENTER FREQUENCIES, Hz
PCA-RP71HAQ PCA-RP71HAQ-ER
NOTCH
High
Low
SPL(dB)
38 34
LINE
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB ( 0dB = 0.0002 µbar )
BAND CENTER FREQUENCIES, Hz
PCA-RP125HAQ
NOTCH
High
Low
SPL(dB)
50 44
LINE
1m
1m
unit
about 1.4m
MICROPHONE
ceiling
NOISE CRITERION CURVES
5
OCH492A
Loading...
+ 25 hidden pages