Mitsubishi Electric PCA-RP71HA, PCA-RP125HA, PCA-RP125HA,PCA-RP125HA Service Manual

Page 1
SERVICE MANUAL
No. OC329
REVISED EDITION-B
INDOOR UNIT
REMOTE CONTROLLER
Indoor unit [Model names] [Service Ref.]
PCA-RP71HA
PCA-RP71HA#1
PCA-RP125HA
PCA-RP125HA
PCA-RP125HA#1
CONTENTS
1. TECHNICAL CHANGES
..................................
2
2. REFERENCE MANUAL
...................................
2
3. SAFETY PRECAUTION
...................................
3
4. PART NAMES AND FUNCTIONS
....................
7
5. SPECIFICATIONS
............................................
9
6. NOISE CRITERION CURVES
........................
10
7. OUTLINES AND DIMENSIONS
......................
11
8.
WIRING DIAGRAM
................................................
.
13
9.
REFRIGERANT SYSTEM DIAGRAM
....................
14
10. TROUBLESHOOTING
....................................
15
11. SPECIAL FUNCTION
.....................................
26
12. DISASSEMBLY PROCEDURE
.......................
29
13. PARTS LIST
....................................................
33
14. RoHS PARTS LIST
.........................................
36
ON/OFF
TEMP.
SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS SPLIT-TYPE, AIR CONDITIONERS
May 2008
Model name indication
Revision:
PCA-RP71·125HA#1 are added in REVISED EDITION-B.
Some descriptions have been modified.
Note:
This manual describes only service data of the indoor units.
RoHS compliant products have <G> mark on the spec name plate.
For servicing of RoHS com­pliant products, refer to the RoHS Parts List.
Please void OC329
REVISED EDITION-A.
Page 2
2
2-1. OUTDOOR UNIT’S SERVICE MANUAL
2-2. TECHNICAL DATA BOOK
2
REFERENCE MANUAL
TECHNICAL CHANGES
1
Service Ref. Service Manual No. PUHZ-RP35/50/60/71/100/125/140VHA
(1)
PUHZ-RP100/125/140YHA
OC334
PUHZ-RP71/100/125/140VHA
(1)
-A OC337
PUHZ-RP200/250YHA
(1)(2)
OC338
PUHZ-RP200/250YHA
(1)
-A OC339 PU(H)-P • VGAA.UK PU(H)-P • YGAA.UK
OC336
PUHZ-P100/125/140VHA.UK OC359 PUHZ-RP35/50/60/71/100/125/140VHA2
(1)
PUHZ-RP100/125/140YHA2
(1)
PUHZ-RP35/50/60/71/100VHA3 PUHZ-RP100YHA3
OC374
PU(H)-P71/100VHA
(1)
.UK
PU(H)-P100/125/140YHA
(1)
.UK
OC379
PUHZ-P100/125/140VHA2
(1)
.UK OCH415 / OCB415 PUHZ-RP71/100/125/140VHA2-A PUHZ-RP100/125/140YHA2-A
OCH422 / OCB422
PUHZ-BP100/125/140VHA-A PUHZ-BP200/250YHA-A
OCH423 / OCB423
PUHZ-P200/250YHA2 OCH424 / OCB424 PUHZ-HRP71/100VHA PUHZ-HRP100/125YHA
OCH425 / OCB425
PUHZ-RP200/250YHA2 OCH428 / OCB428
Series (Outdoor unit) Manual No. PUHZ-RP • HA(-A) OCS01
PU(H)-P • GAA.UK OCS02 PUHZ-RP • HA2 OCS05 PUHZ-P • HA OCS06 PU(H)-P • HA OCS07 PUHZ-P • VHA2, PUHZ-P • YHA OCS08 PUHZ-RP • HA2-A OCS09 PUHZ-BP • HA OCS10 PUHZ-HRP • HA OCS11
PCA-RP71HA PCA-RP71HA#1 PCA-RP125HA PCA-RP125HA#1
INDOOR CONTROLLER BOARD(I.B.) has been changed.
Page 3
33
SAFETY PRECAUTION
3
Cautions for units utilising refrigerant R407C
3-2. CAUTIONS RELATED TO NEW REFRIGERANT
Do not use the existing refrigerant piping.
The old refrigerant and lubricant in the existing piping contains a large amount of chlorine which may cause the lubricant deterioration of the new unit.
Use “low residual oil piping”
If there is a large amount of residual oil (hydraulic oil, etc.) inside the piping and joints, deterioration of the lubricant will result.
Use ESTER , ETHER or HAB as the lubricant to coat flares and flange connection parts.
If large amount of mineral oil enter, that can cause deterioration of refrigerant oil etc.
Use liquid refrigerant to charge the system.
If gas refrigerant is used to seal the system, the composition of the refrigerant in the cylinder will change and performance may drop.
Do not use a refrigerant other than R407C.
If another refrigerant (R22, etc.) is used, the chlorine in the refrigerant may cause the lubricant deterioration.
Use a vacuum pump with a reverse flow check valve.
The vacuum pump oil may flow back into the refrigerant cycle and cause the lubricant deterioration.
Store the piping to be used during installation indoors with keep both ends sealed until just before brazing. (Store elbows and other joints in a plastic bag.)
If dust, dirt, or water enters the refrigerant cycle, deterioration of the oil and compressor trouble may result.
Ventilate the room if refrigerant leaks during operation. If refrigerant comes into contact with a flame, poisonous gases will be released.
3-1. ALWAYS OBSERVE FOR SAFETY
Before obtaining access to terminal, all supply circuits must be disconnected.
Page 4
4
No. Tool name Specifications 1 Gauge manifold ·Only for R407C.
·Use the existing fitting SPECIFICATIONS. (UNF7/16)
·Use high-tension side pressure of 3.43MPa·G or over. 2 Charge hose ·Only for R407C.
·Use pressure performance of 5.10MPa·G or over. 3 Electronic scale
4 Gas leak detector ·Use the detector for R134a or R407C. 5 Adapter for reverse flow check. ·Attach on vacuum pump. 6 Refrigerant charge base.
7 Refrigerant cylinder. ·For R407C ·Top of cylinder (Brown)
·Cylinder with syphon 8 Refrigerant recovery equipment.
[3] Service tools
Use the below service tools as exclusive tools for R407C refrigerant.
[2] Refrigerant recharging
(1) Refrigerant recharging process
1Direct charging from the cylinder.
·R407C cylinder are available on the market has a syphon pipe.
·Leave the syphon pipe cylinder standing and recharge it. (By liquid refrigerant)
(2) Recharge in refrigerant leakage case
·After recovering the all refrigerant in the unit, proceed to working.
·Do not release the refrigerant in the air.
·After completing the repair service, recharge the cycle with the specified amount of liquid refrigerant.
Gravimeter
Unit
[1] Cautions for service
·After recovering the all refrigerant in the unit, proceed to working.
·Do not release refrigerant in the air.
·After completing the repair service, recharge the cycle with the specified amount of liquid refrigerant.
Page 5
5
Cautions for units utilising refrigerant R410A
CAUTIONS RELATED TO NEW REFRIGERANT
Use new refrigerant pipes.
Make sure that the inside and outside of refrige­rant piping is clean and it has no contamination such as sulfur hazardous for use, oxides, dirt, shaving particles, etc. In addition, use pipes with specified thickness.
Store the piping to be used during installation indoors and keep both ends of the piping sealed until just before brazing. (Leave elbow joints, etc. in their packaging.)
Use ester oil, ether oil or alkylbenzene oil (small amount) as the refrigerant oil applied to flares and flange connections.
In case of using the existing pipes for R22, be careful with the followings.
· For RP71VHA3 and RP125 be sure to perform replacement operation before test run.
· Change flare nut to the one provided with this product. Use a newly flared pipe.
· Avoid using thin pipes.
Charge refrigerant from liquid phase of gas cylinder.
If the refrigerant is charged from gas phase, composition change may occur in refrigerant and the efficiency will be lowered.
Do not use refrigerant other than R410A.
If other refrigerant (R22 etc.) is used, chlorine in refrige­rant can cause deterioration of refrigerant oil etc.
Use a vacuum pump with a reverse flow check valve.
Vacuum pump oil may flow back into refrigerant cycle and that can cause deterioration of refrigerant oil etc.
Use the following tools specifically designed for use with R410A refrigerant.
The following tools are necessary to use R410A refrigerant.
Keep the tools with care.
If dirt, dust or moisture enter into refrigerant cycle, that can cause deterioration of refrigerant oil or malfunction of com­pressor.
Do not use a charging cylinder.
If a charging cylinder is used, the composition of refrigera­nt will change and the efficiency will be lowered.
Flare tool
Electronic refrigerant charging scale
Vacuum pump adaptor
Size adjustment gauge
Gauge manifold
Torque wrench
Gas leak detector
Charge hose
Tools for R410A
Contamination inside refrigerant piping can cause deterio­ration of refrigerant oil etc.
If dirt, dust or moisture enter into refrigerant cycle, that can cause deterioration of refrigerant oil or malfunction of com­pressor.
If large amount of mineral oil enter, that can cause deterio­ration of refrigerant oil etc.
Ventilate the room if refrigerant leaks during operation. If refrigerant comes into contact with a flame, poisonous gases will be released.
[1] Cautions for service
(1) Perform service after collecting the refrigerant left in unit completely. (2) Do not release refrigerant in the air. (3) After completing service, charge the cycle with specified amount of refrigerant. (4) When performing service, install a filter drier simultaneously. Be sure to use a filter drier for new refrigerant.
[2] Additional refrigerant charge
When charging directly from cylinder
· Check that cylinder for R410A on the market is syphon type.
· Charging should be performed with the cylinder of syphon stood vertically. (Refrigerant is charged from liquid phase.)
Page 6
6
[3] Service tools
Use the below service tools as exclusive tools for R410A refrigerant.
No. Tool name Specifications 1 Gauge manifold ·Only for R410A
·Use the existing fitting
specifications
. (UNF1/2)
·Use high-tension side pressure of 5.3MPa·G or over. 2 Charge hose ·Only for R410A
·Use pressure performance of 5.09MPa·G or over. 3 Electronic scale 4 Gas leak detector ·Use the detector for R134a, R407C or R410A. 5 Adaptor for reverse flow check ·Attach on vacuum pump. 6 Refrigerant charge base 7 Refrigerant cylinder ·Only for R410A Top of cylinder (Pink) Cylinder with syphon 8 Refrigerant recovery equipment
Gravimeter
Unit
Page 7
77
4
PART NAMES AND FUNCTIONS
Indoor (Main) Unit
Air outlet
Air intake
Oil filter (Air intake)
+ It prevents oil from getting into the unit.
Left/right guide vanes
Change the direction of airflow from the horizontal blower.
Up/down guide vanes
Change the direction of airflow from the vartical blower.
Remote controller
Once the controls are set, the same operation mode can be repeated by simply pressing the ON/OFF button.
Operation buttons
PAR-21MAA
ON/OFF
FILTER
CHECK
OPERATION
CLEAR
TEST
TEMP.
MENU
BACK DAY
MONITOR/SET
CLOCK
ON/OFF
Set Temperature buttons
Down Up
Timer Menu button (Monitor/Set button)
Mode button (Return button)
Set Time buttons
Back Ahead
Timer On/Off button (Set Day button)
Opening the door.
ON/OFF button
Fan Speed button
Filter button (<Enter> button)
Test Run button
Check button (Clear button)
Airflow Up/Down button
Louver button ( Operation button)
To preceding operation number.
Ventilation button (
Operation button)
To next operation number.
Page 8
8
Display
For purposes of this explanation, all parts of the display are shown as lit. During actual operation, only the relevant items will be lit.
°F°C
°F°C
ERROR CODE
AFTER
TIMER
TIME SUN MON TUE WED THU FRI SAT
ON OFF
Hr AFTER
FILTER
FUNCTION
ONLY1Hr.
WEEKLY
SIMPLE
AUTO OFF
Identifies the current operation
Shows the operating mode, etc. * Multilanguage display is sup-
ported.
“Centrally Controlled” indicator
Indicates that operation of the re­mote controller has been prohib­ited by a master controller.
“Timer Is Off” indicator
Indicates that the timer is off.
Temperature Setting
Shows the target temperature.
Day-of-Week
Shows the current day of the week.
Time/Timer Display
Shows the current time, unless the simple or Auto Off timer is set. If the simple or Auto Off timer is set, shows the time remaining.
“Sensor” indication
Displayed when the remote controller sensor is used.
“Locked” indicator
Indicates that remote controller but­tons have been locked.
“Clean The Filter” indicator
Comes on when it is time to clean the filter.
Timer indicators
The indicator comes on if the corre­sponding timer is set.
Up/Down Air Direction indica­tor
The indicator shows the direc­tion of the outcoming airflow.
“One Hour Only” indicator
Displayed if the airflow is set to low and downward during COOL or DRY mode. (Operation varies according to model.) The indicator goes off after one hour, at which time the airflow di­rection also changes.
Room Temperature display
Shows the room temperature.
Louver display
Indicates the action of the swing louver. Does not appear if the louver is stationary.
(Power On indicator)
Indicates that the power is on.
Fan Speed indicator
Shows the selected fan speed.
Ventilation indicator
Appears when the unit is running in Ventilation mode.
Caution
 Only the Power on indicator lights when the unit is stopped and power supplied to the unit.  If you press a button for a feature that is not installed at the indoor unit, the remote controller will display the “Not Available”
message. If you are using the remote controller to drive multiple indoor units, this message will appear only if he feature is not present at every unit connected.  When power is turned ON for the first time, it is normal that “PLEASE WAIT” is displayed on the room temperature indication
(For max. 2minutes). Please wait until this “PLEASE WAIT” indication disappear then start the operation.
Page 9
99
SPECIFICATIONS
5
kW
A A
kW
*/min(CFM)
Pa(mmAq)
dB mm(in.) mm(in.) mm(in.) mm(in.)
kg(lbs)
Service Ref.
Mode Power supply(phase, cycle, voltage) Input Running current Starting current External finish Heat exchanger Fan Fan(drive) x No. Fan motor output Airflow(Low-High) External static pressure Operation control & Thermostat Noise level(Low-High) Unit drain pipe I.D. Dimensions
Weight
W
D H
INDOOR UNIT
PCA-RP125HA, PCA-RP125HA#1
Cooling
0.26
1.19
2.38
Heating
0.26
1.19
2.38
Single phase, 50Hz, 230V
Stainless steel
Plate fin coil
Sirocco fan (direct) x 4
0.08 + 0.08
30-38(1,060-1,350)
0(direct blow)
Remote controller & built-in
44-50
26(1)
1,520(59-7/8)
650(25-5/8)
280(11) 56(124)
Cooling
0.09
0.43
0.86
Heating
0.09
0.43
0.86
Single phase, 50Hz, 230V
Stainless steel
Plate fin coil
Sirocco fan (direct) x 2
0.04
17-19(600-670)
0(direct blow)
Remote controller & built-in
34-38
26(1)
1,136(44-3/4)
650(25-5/8)
280(11)
41(90)
PCA-RP71HA, PCA-RP71HA#1
kW
A A
kW
*/min(CFM)
Pa(mmAq)
dB mm(in.) mm(in.) mm(in.) mm(in.)
kg(lbs)
Service Ref.
Mode Power supply(phase, cycle, voltage) Input Running current Starting current External finish Heat exchanger Fan Fan(drive) x No. Fan motor output Airflow(Low-High) External static pressure Operation control & Thermostat Noise level(Low-High) Unit drain pipe I.D. Dimensions
Weight
W
D H
INDOOR UNIT
Page 10
10
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB ( 0dB = 0.0002 μbar )
BAND CENTER FREQUENCIES, Hz
PCA-RP71HA PCA-RP71HA#1
NOTCH
High
Low
SPL(dB)
38 34
LINE
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB ( 0dB = 0.0002 μbar )
BAND CENTER FREQUENCIES, Hz
PCA-RP125HA PCA-RP125HA#1
NOTCH
High Low
SPL(dB)
50 44
LINE
1m
1m
unit
about 1.4m
MICROPHONE
ceiling
NOISE CRITERION CURVES
6
Page 11
11
Ceiling
Less than
Less than
or more
Less than
or more
or more
300
<Suspension bolt pitch>
model:PAC-SG38KF-E (12pcs.)
Filter element for the exchange
1.Use M10 or W3/8 screw for anchor bolt.
NOTES.
(122 )
<Filter contour dimension>
16
handle
100
1001136
366
480
176
318
650
<Flexible hose(accessory)>
Terminal block box
78
Inspection port
(pipe sensor)
The half bottom of FAN CASING
can be separated.
Adjustable part
288
360
<Air outlet>
<Suspension bolt pitch>
<Air outlet>
<Air intake>
<Air intake>
Filter (3-pieces)
Terminal block bo
5
2
1
4
3
6
9
2
1
38
105
85
90°
Electrical box
Rear wall
500
250
2 ~ 3
(Gap to ceiling)
Allowing clearances
<gas> <liquid>
Suspension bolt
130
210
45
165
120
1224
1180
75
1136
986
1098
70
243
254
175
197
110
21
130 15
258 110 102
320 80
90
14018
75
70~90
650
13
289
75
280
495
43
295
:222
:200
Refrigerant-pipe connection(gas pipe side/flared connection : 5/8F)
Refrigerant-pipe connection(liquid pipe side/flared connection : 3/8F)
Flexible hose(accessory) Drainage pipe connection(26mm I.D.)
Knockout hole for behind refrigerant-piping arrangement
Knockout hole for upper refrigerant-pipe arrangement
Knockout hole for wiring arrangement : 2- : 27
Terminal block(indoor/outdoor connecting line)
Terminal block(remote controller)
Knockout hole (duct for fresh air intake): 2- : 200
Option parts:duct flange( : 200). model: PAC-SF28OF-E(1 pc.)
PCA-RP71HA PCA-RP71HA#1
OUTLINES AND DIMENSIONS
7
Unit : mm
Page 12
12
Ceiling
Less than
Less than
Less than
or more
or more
or more
Allowing clearances
Rear wall
(Gap to ceiling)
NOTES.
1.Use M10 or W3/8 screw for anchor bolt.
Use the current nuts meeting the pipe size
of the outdoor unit.
model:PAC-SG38KF-E (12pcs.)
Filter element for the exchange
<Suspension bolt pitch>
(122)246
handle
16
<Flexible hose(accessory)>
Terminal block box
78
<Filter contour dimension>
Inspection port
(pipe sensor)
The half bottom of FAN CASING
can be separated.
Adjustable part
288
360
<Air outlet>
<Suspension bolt pitch>
<Air outlet>
<Air intake>
<Air intake>
Filter (4-pieces)
Terminal block box
5
2
1
4
3
6
9
2
1
176
38 210
105
8545
165
:222
:200
440440298
130
90°
650
300
1001520100
Electrical box
500
250
2~3
<gas> <liquid>
Suspension bolt
70
243
254
175
197
110
21
130 15
258
1482
110 102
1370 75
1608
320 801564
1520
90 120
14018
75
70~90
650
13
289
75
280
495
43
295
Refrigerant-pipe connection(gas pipe side/flared connection : 5/8F, 3/4F)
Refrigerant-pipe connection(liquid pipe side/flared connection : 3/8F)
Flexible hose(accessory) Drainage pipe connection(26mm I.D.)
Knockout hole for behind refrigerant-piping arrangement
Knockout hole for upper refrigerant-pipe arrangement
Knockout hole for wiring arrangement : 2- : 27
Terminal block(indoor/outdoor connecting line)
Terminal block(remote controller)
Knockout hole (duct for fresh air intake) : 2- : 200
Option parts:duct flange( : 200). model: PAC-SF28OF-E(1 pc.)
: 9.52
RP125
: 15.88
: 19.05
Available pipe size
LIQUID SIDE
GAS SIDE
: Initial flare nut size
PCA-RP125HA PCA-RP125HA#1
Unit : mm
Page 13
1313
PCA-RP71HA PCA-RP125HA PCA-RP71HA#1 PCA-RP125HA#1
SYMBOL
[ LEGEND ]
NAME SYMBOL NAME INDOOR POWER BOARD INDOOR CONTROLLER BOARD FUSE (T6.3AL250V)
MF1, MF2 C1, C2 H2
FAN MOTOR CAPACITOR(FAN MOTOR)
DEW PREVENTION HEATER VARISTOR CONNECTOR (LOSSNAY) CONNECTOR (REMOTE SWITCH) CONNECTOR (HA TERMINAL-A) CONNECTOR (CENTRALLY CONTROLL) POWER SUPPLY (I. B) POWER SUPPLY (R. B) TRANSMISSION(INDOOR-OUTDOOR) RELAY (DEW PREVENTION HEATER) RELAY(FAN MOTOR) RELAY(FAN MOTOR) RELAY(FAN MOTOR) SWITCH (MODEL SELECTION)
See T able 1. SWITCH (CAPACITY CODE) See Table 2. SWITCH (EMERGENCY OPERATION)
P. B I. B
FUSE ZNR CN2L CN32 CN41 CN51 LED1 LED2 LED3 X1 X4 X5 X6 SW1
TB2
TB4
TB5,TB6
TH1
TH2
TH5
R. B
TERMINAL BLOCK(INDOOR UNIT POWER (OPTION)) TERMINAL BLOCK(INDOOR/OUTDOOR CONNECTING LINE) TERMINAL BLOCK(REMOTE CONTROLLER TRANSMISSION LINE) ROOM TEMP.THERMISTOR (0°C/15k, 25°C/5.4k DETECT) PIPE TEMP.THERMISTOR/LIQUID (0°C/15k, 25°C/5.4k DETECT) COND./ EVA.TEMP.THERMISTOR (0°C/15k, 25°C/5.4k DETECT)
WIRED REMOTE CONTROLLER BOARD SW2 SWE
Service board
SW1
Table 1
1 2 3 4 5
ON OFF
Service board
SW2
Table 2
1 2 3 4 5
MODELS
PCA-RP71HA
ON OFF
Service board
1 2 3 4 5
MODELS
PCA-RP125HA
ON OFF
1357
MF1
BLU
BLK
WHT
YLW
BLU
BLK
WHT
YLW
ORN
ORN
C1
RED
RED
13 13 13 12
1 2
1 2
3
13
11
654321
MF2
BLU
YLW
YLW
ORN
BLK
RED
WHT
WHT
YLW
BLK
WHT
YLW
BLU
BLK
WHT
YLW
ORN
BRN
C2
GRY
RED
654321
D.HEATER CNC (RED)
For PCA-RP125HA, PCA-RP125HA#1
X6 X5 X4
X6 X5 X4
ZNR
FUSE
SWE
FAN
(WHT)
SW2 SW1
LED3 LED2 LED1
H2
OFF
ON
12 12 12
12 13
12
WHT
WHT
REMOCON
CN22 (BLU)
TH1 TH2 TH5
BLU
BLU
BLK
BLK
1
2
2
1
TB5
INTAKE
CN20 (RED)
LIQUID
CN21
(WHT)
PIPE CN29 (BLK)
R.B
TB6
TRANSMISSION WIRES DC12V
CN41 CN2L
CN32CN51
ROWER
CNDK
(RED)
ROWER
CND
(ORN)
DC13.1V
CNDK
(RED)
CN2S
(WHT)
P.B
I.B
BRN
YLW ORN ORN
S1
S2
S3
TB4
TO OUTDOOR UNIT
ROWER
CN2D(WHT)
INDOOR/OUTDOOR
COMMUNICATION
CN3C(BLU)
Refer to tables 1 and 2 for service PCB.
Please set the voltage using the remote controller. For the setting method, please refer to the indoor unit Installation Manual.
3131
POWER
CND
(ORN)
INDOOR/OUTDOOR COMMUNICATION
CN3C (BLU)
TB4
POWER SUPPLY ~(1PHASE) 230V 50Hz
RED
TB2
BLU
TO OUTDOOR UNIT
L
S1 S2
S3
N
I.B
YLW
ORN
ORN ORN
YLW
GRN/YLW
BRN
+1 (Fig.1)
NOTES:
1.Since the outdoor side electric wiring may change be sure to check the outdoor unit electric wiring for servicing.
2.Indoor and outdoor connecting wires are made with polarities, make wiring matching terminal numbers (S1,S2,S3).
3.Symbols used in wiring diagram above are, : Connector, : Terminal (block). 1 ; When work to supply power separately to Indoor and Outdoor unit was applied, refer to Fig1. 2 ; For power supply system of this unit, refer to the caution label located near this diagram.
WIRING DIAGRAM
8
Page 14
14
PCA-RP71HA PCA-RP71HA#1 PCA-RP125HA PCA-RP125HA#1
Pipe temperature thermistor/liquid (TH2)
Distributor with strainer #50
Condenser/evaporator temperature thermistor (TH5)
Room temperature thermistor (TH1)
Refrigerant flow in cooling Refrigerant flow in heating
Strainer #50
Strainer #50
Heat exchanger
Refrigerant GAS pipe connection (Flare)
Refrigerant LIQUID pipe connection (Flare)
REFRIGERANT SYSTEM DIAGRAM
9
Page 15
15
<Error code display by self-diagnosis and actions to be taken for service (summary)>
Present and past error codes are logged and displayed on the wired remote controller or controller board of outdoor unit. Actions to be taken for service and the trouble reoccurrence at field are summarized in the table below. Check the contents below before investigating details. Note : Refer to the manual of outdoor unit for malfunction-diagnosis method by remote controller.
10-1. TROUBLESHOOTING
Unit conditions at service
Error code
Actions to be taken for service (summary)
The trouble is reoccurring.
Displayed
Not displayed
Judge what is wrong and take a corrective action according to “SELF-DIAGNOSIS ACTION TABLE” (10-2).
Conduct troubleshooting and ascertain the cause of the trouble according to “TROUBLESHOOTING BY INFERIOR PHENOMENA ” (10-3).
The trouble is not reoccurring.
Logged
Not logged
Consider the temporary defects such as the work of protection devices in the refrigerant circuit including compressor, poor connection of wiring, noise and etc. Re-check the symptom, and check the installation environment, refrigerant amount, weather when the trouble occurred, and wiring related. Reset error code logs and restart the unit after finishing service. There is no abnormality in electrical components, controller boards, and remote controller.
Recheck the abnormal symptom.Identify the cause of the trouble and take a corrective
action according to “TROUBLESHOOTING BY INFERIOR PHENOMENA ” (10-3). Continue to operate unit for the time being if the cause is not ascertained. There is no abnormality in electrical components, controller boards, remote controller etc.
TROUBLESHOOTING
10
Page 16
16
10-2. SELF-DIAGNOSIS ACTION TABLE
Note: Refer to the manual of outdoor unit for the details of display such as F, U, and other E.
Error Code
Abnormal point and detection method
Cause
Countermeasure
P1
P2
P4
Drain sensor (DS)
1 Suspensive abnormality, if short/open
of thermistor is detected for 30 seconds continuously.Compressor and indoor fan will be turned off
2 Short/open is detected for 30 seconds
continuously during suspensive abnormality. (The unit returns to normal operation, if it has normally reset.) 3 Detect the following condition.
• During cooling and drying operation.
• In case that pipe <liquid> temperature ­room temperature <-10deg
(Except defrosting)
• When pipe <liquid> temperature or room temperature is short/open
temperature.
• During drain pomp operation.
1 Defective thermistor characteristics 2 Contact failure of connector
(CN31) on the indoor controller
board. (Insert failure). 3 Breaking of wire or contact failure of drain sensor wiring.
4 Defective indoor controller board.
1–3 Check resistance value of thermistor.
0:
......
6.0k"
10:
....
3.9k"
20:
....
2.6k"
30:
....
1.8k"
40:
....
1.3k"
2 Check contact failure of connector (CN31)
on the indoor controller board. Refer to 10-6. Turn the power on again and check restart
after inserting connector again. 4 Replace indoor controller board if drain pump operates with the line of drain sensor
connector CN31-1 and 2 is short-circuited,
and abnormality reappears. Turn the power off, and on again to operate
after check.
P5
Malfunction of drain pump (DP)
1 Suspensive abnormality, if thermistor of drain sensor is let heat itself and temperature rises slightly. Compressor
and indoor fan will be turned off.
2 Drain pomp is abnormal if the condition
above is detected during suspensive abnormality.
3 Constantly detected during drain pump
operation.
1 Malfunction of drain pump 2 Defective drain
Clogged drain pump Clogged drain pipe
3
Attached drop of water at the
drain sensor
• Drops of drain trickles from lead wire.
• Clogged filter is causing wave of drain.
4 Defective indoor controller board.
1 Check if drain-up machine works. 2 Check drain function. 3 Check the setting of lead wire of drain sensor
and check clogs of the filter. 4 Replace indoor controller board if drain pump operates with the line of drain sensor
connector CN31-1 and 2 is short-circuited
and abnormality reappears. Refer to 10-6.
Turn the power off, and on again to operate after check.
Room temperature thermistor (TH1)
1 The unit is in 3-minute resume prevention mode if short/open of thermistor is detected. Abnormal if the
unit does not reset normally after 3 min­utes. (The unit returns to normal opera-
tion, if it has been reset normally.) 2 Constantly detected during cooling, drying, and heating operation. Short: -90: or more Open: -40: or less
1 Defective thermistor characteristics 2 Contact failure of connector
(CN20) on the indoor controller
board (Insert failure) 3 Breaking of wire or contact failure of thermistor wiring 4 Defective indoor controller
board
13 Check resistance value of thermistor.
0: 15.0k" 10: 9.6k" 20: 6.3k" 30: 4.3k"
40: 3.0k" If you put force on (draw or bend) the lead wire with measuring resistance value of thermis­tor, breaking of wire or contact failure can be detected. 2 Check contact failure of connector (CN20)
on the indoor controller board. Refer to 10-6. Turn the power on again and check restart after inserting connector again.
4 Check room temperature display on remote
controller.
Replace indoor controller board if there is
abnormal difference with actual room
temperature. Turn the power off, and on again to operate
after check.
Pipe temperature thermistor/Liquid (TH2)
1 The unit is in 3-minute resume prevention mode if short/open of thermistor is detected. Abnormal if the
unit does not reset normally after 3 min­utes. (The unit returns to normal opera-
tion, if it has been reset normally.) 2 Constantly detected during cooling, drying, and heating (except defrosting)
operation Short: 90: or more Open: -40: or less
1 Defective thermistor characteristics 2 Contact failure of connector
(CN44) on the indoor control-
ler board (Insert failure) 3 Breaking of wire or contact failure of thermistor wiring 4 Defective refrigerant circuit is
causing thermistor tempera-
ture of 90: or more or -40:
or less. 5 Defective indoor controller
board
13 Check resistance value of thermistor. For characteristics, refer to (P1) above. 2 Check contact failure of connector (CN44)
on the indoor controller board. Refer to 10-6. Turn the power on and check restart after inserting connector again.
4 Check pipe <liquid> temperature with remote
controller in test run mode. If pipe <liquid> temperature is extremely low (in cooling mode) or high (in heating mode), refrigerant circuit may have defective.
5 Check pipe <liquid> temperature with
remote controller in test run mode. If there is extremely difference with actual pipe <liquid> temperature, replace indoor controller board.
Turn the power off, and on again to operate after check.
Page 17
17
Error Code
Abnormal point and detection method
Cause
Countermeasure
P6
Freezing/overheating protection is work­ing
1 Freezing protection (Cooling mode)
The unit is in 6-minute resume preven­tion mode if pipe <liquid or condenser/ evaporator> temperature stays under
-15: for 3 minutes, 3 minutes after the compressor started. Abnormal if it stays under -15: for 3 minutes again within 16 minutes after 6-minute resume pre­vention mode.
2 Overheating protection (Heating mode)
The units is in 6 minute resume
prevention mode if pipe <condenser / evaporator> temperature is detected as over 70: after the compressor started. Abnormal if the temperature of over 70: is detected again within 30 minutes after 6 minute resume prevention mode.
P8
1 Slight temperature difference
between indoor room temperature and pipe <liquid or condenser / evaporator> temperature thermistor
• Shortage of refrigerant
• Disconnected holder of pipe <liquid or condenser /
evaporator> thermistor
• Defective refrigerant circuit
2 Converse connection of extension pipe (on plural units
connection) 3 Converse wiring of indoor/ outdoor unit connecting wire
(on plural units connection) 4 Defective detection of indoor
room temperature and pipe
<condenser / evaporator> temperature thermistor 5 Stop valve is not opened completely.
(Cooling or drying mode)
1 Clogged filter (reduced airflow) 2 Short cycle of air path 3 Low-load (low temperature)
operation out of the tolerance
range
4 Defective indoor fan motor
• Fan motor is defective.
• Indoor controller board is defec­tive.
5 Defective outdoor fan control 6 Overcharge of refrigerant 7 Defective refrigerant circuit
(clogs)
(Heating mode)
1 Clogged filter (reduced airflow) 2 Short cycle of air path 3 Over-load (high temperature)
operation out of the tolerance range
4 Defective indoor fan motor
• Fan motor is defective.
• Indoor controller board is defec­tive.
5 Defective outdoor fan control 6 Overcharge of refrigerant 7 Defective refrigerant circuit
(clogs)
8 Bypass circuit of outdoor unit
is defective.
(Cooling or drying mode)
1 Check clogs of the filter. 2 Remove shields.
4 Refer to 10-6.
5 Check outdoor fan motor. 67 Check operating condition of refrigerant
circuit.
(Heating mode)
1 Check clogs of the filter. 2 Remove shields.
4 Refer to 10-6.
5 Check outdoor fan motor. 6~8Check operating condition of refrigerant
circuit.
Pipe temperature
<Cooling mode> Detected as abnormal when the pipe tem­perature is not in the cooling range 3 min­utes after compressor start and 6 minutes after the liquid or condenser/evaporator pipe is out of cooling range. Note 1) It takes at least 9 minutes to
detect.
Note 2) Abnormality P8 is not detected in
drying mode. Cooling range : -3 °C ] (TH-TH1) TH: Lower temperature between: liquid
pipe temperature (TH2) and condens­er/evaporator temperature (TH5)
TH1: Intake temperature <Heating mode>
When 10 seconds have passed after the compressor starts operation and the hot adjustment mode has finished, the unit is detected as abnormal when condenser/ evaporator pipe temperature is not in heat­ing range within 20 minutes.
Note 3) It takes at least 27 minutes to
detect abnormality. Note 4) It excludes the period of defrosting.
(Detection restarts when defrosting
mode is over.) Heating range : 3 °C [ (TH5-TH1)
1~4 Check pipe <liquid or condenser / evapo-
rator> temperature with room tempera­ture display on remote controller and outdoor controller circuit board.
Pipe <liquid or condenser / evaporator>
temperature display is indicated by set­ting SW2 of outdoor controller circuit board as follows.
23Check converse connection of extension
pipe or converse wiring of indoor/outdoor unit connecting wire.
Conduct temperature check with outdoor controller circuit board after connecting ‘A-Control Service Tool(PAC-SK52ST)’.
(
)
Page 18
18
Error Code
Abnormal point and detection method
Cause
Countermeasure
P9
Pipe temperature thermistor / Condenser-Evaporator (TH5)
1 The unit is in 3-minute resume protec-
tion mode if short/open of thermistor is detected. Abnormal if the unit does not get back to normal within 3 minutes. (The unit returns to normal operation, if it has been reset normally.)
2 Constantly detected during cooling,
drying, and heating operation (except
defrosting) Short: 90: or more Open: -40: or less
1 Defective thermistor characteristics 2 Contact failure of connector
(CN44) on the indoor controller
board (Insert failure) 3 Breaking of wire or contact failure of thermistor wiring 4 Temperature of thermistor is
90: or more or -40: or less
caused by defective refrigerant
circuit. 5 Defective indoor controller
board
13 Check resistance value of thermistor. For characteristics, refer to (P1) above. 2 Check contact failure of connector (CN44)
on the indoor controller board. Refer to 10-7. Turn the power on and check restart after
inserting connector again. 4 Operate in test run mode and check pipe
<condenser / evaporator> temperature with
outdoor controller circuit board. If pipe <condenser / evaporator> temperature is
extremely low (in cooling mode) or high (in
heating mode), refrigerant circuit may have
defect. 5 Operate in test run mode and check pipe
<condenser / evaporator> temperature with
outdoor control circuit board. If there is extreme difference with actual pipe <condenser / evaporator> temperature,
replace indoor controller board. There is no abnormality if none of above
comes within the unit. Turn the power off and on again to operate.
E0
or
E4
Remote controller transmission error(E0)/signal receiving error(E4)
1 Abnormal if main or sub remote con-
troller cannot receive any transmission normally from indoor unit of refrigerant
address “0” for 3 minutes. (Error code : E0) 2 Abnormal if sub remote controller could
not receive any signal for 2 minutes.
(Error code: E0) 1 Abnormal if indoor controller board can
not receive any data normally from
remote controller board or from other
indoor controller board for 3 minutes.
(Error code: E4) 2 Indoor controller board cannot receive
any signal from remote controller for 2
minutes. (Error code: E4)
1 Check disconnection or looseness of indoor
unit or transmission wire of remote controller. 2 Set one of the remote controllers “main” if there is no problem with the action above. 3 Check wiring of remote controller.
• Total wiring length: max. 500m (Do not use cable x 3 or more.)
• The number of connecting indoor units: max. 16 units
• The number of connecting remote control­ler: max. 2 units
When it is not the above-mentioned problem of
1~3 4 Diagnose remote controllers.
a) When “RC OK” is displayed,
Remote controllers have no problem. Turn the power off, and on again to check. If abnormality generates again, replace indoor controller board.
b) When “RC NG” is displayed,
Replace remote controller.
c)When “RC E3” or “ERC 00-66” is dis-
played, noise may be causing abnormality.
* If the unit is not normal after replacing
indoor controller board in group control, indoor controller board of address “0” may be abnormal.
E3
or
E5
Remote controller transmission error(E3)/signal receiving error(E5)
1 Abnormal if remote controller could not
find blank of transmission path for 6 sec­onds and could not transmit.
(Error code: E3) 2 Remote controller receives transmitted
data at the same time and compares the received and transmitted data. Abnormal if these data are judged to be different 30 continuous times. (Error code: E3)
1 Abnormal if indoor controller board could
not find blank of transmission path.
(Error code: E5) 2 Indoor controller board receives trans-
mitted data at the same time and com­pares the received and transmitted data. Abnormal if these data are judged to be different 30 continuous times. (Error code: E5)
1 Set a remote controller to main, and the
other to sub.
2 Remote controller is connected with only one
indoor unit.
3 The address changes to a separate setting. 4~6 Diagnose remote controller.
a) When “RC OK” is displayed, remote con-
trollers have no problem. Turn the power off,and on again to check. When becoming abnormal again, replace
indoor controller board. b)When “RC NG” is displayed, replace
remote controller. c)When “RC E3” or “ERC 00-66” is dis-
played, noise may be causing abnormal-
ity.
1 Contact failure at transmission
wire of remote controller
2 All remote controllers are set
as “sub” remote controller. In this case, E0 is displayed on remote controller, and E4 is displayed at LED (LED1, LED2) on the outdoor controller circuit board.
3 Miswiring of remote controller 4 Defective transmitting receiving
circuit of remote controller
5 Defective transmitting receiving
circuit of indoor controller board of refrigerant addresses “0”.
6 Noise has entered into the
transmission wire of remote controller.
1 2 remote controllers are set as
“main.” (In case of 2 remote con­ trollers) 2 Remote controller is connected
with 2 indoor units or more. 3 Repetition of refrigerant
address 4 Defective transmitting receiving
circuit of remote controller 5 Defective transmitting receiving
circuit of indoor controller board 6 Noise has entered into trans-
mission wire of remote control-
ler.
In case of checking pipe temperature with outdoor controller circuit board, be sure to connect A-control service tool (PAC-SK52ST).
(
)
Page 19
19
E6
E7
Error Code
Abnornal point and detection method
Cause
Countermeasure
Fb
E1
or
E2
PA
Forced compressor stop (due to water leakage abnormality)
1 When the intake temperature subtracted with liquid pipe temperature is less than
-10:, drain sensor is detected whether it is soaked in the water or not at the interval of 90 seconds. (Drain pump will start operating
when the drain sensor is detected to be soaked in the water.) 2 The unit has a water leakage abnormality
when the following conditions, a and b, are
satisfied while the above-mentioned detection is performed. a) The drain sensor is detected to be soaked in the water 10 times in a row. b) The intake temperature subtracted with
liquid pipe temperature is detected to be less than -10: for a total of 30 minutes. (When the drain sensor is detected to
be NOT soaked in the water, the detection record of a and b will be cleared.) 3 The drain sensor detection is performed in operations other than cooling. (When the unit stops operating, during heating or fan operation, when the unit stops because of some abnormality) *Once the water leakage abnormality is detected, abnormality state will not be released until the main power is reset.
1 Drain pump trouble 2 Drain defective
· Drain pump clogging
· Drain pipe clogging 3 Open circuit of drain sensor
side heater 4 Contact failure of drain sensor
connector 5 Dew condensation on drain
sensor
· Drain water descends along lead wire.
· Drain water waving due to filter clogging.
6 Extension piping connection difference at twin, triple, quadruple system.
7 Mis-wiring of indoor/ outdoor connecting at twin, triple, quadruple system.
8 Room temperature thermistor / liquid pipe temperature thermis­ tor detection is defective.
1 Check the drain pump. 2 Please confirm whether water can be
drained.
3 Confirm the resistance of the drain sensor.
4 Check the connector contact failure.
5 Check the drain sensor leadwire mounted.
Check the filter clogging
6 Check the piping connection.
7 Check the indoor/ outdoor connecting wires.
8 Check the room temperature display of
remote controller. Check the indoor liquid pipe temperature display of outdoor controller board.
1 Contact failure, short circuit or,
miswiring (converse wiring) of indoor/outdoor unit connecting wire
2 Defective transmitting receiving
circuit of indoor controller board
3 Defective transmitting receiving
circuit of indoor controller board
4 Noise has entered into indoor/
outdoor unit connecting wire.
* Check LED display on the outdoor control
circuit board. (Connect A-control service
tool, PAC-SK52ST.) Refer to outdoor unit service manual. 1 Check disconnection or looseness of indoor/
outdoor unit connecting wire of indoor unit or
outdoor unit. Check all the units in case of twin triple indoor unit system. 2-4 Turn the power off, and on again to check.
If abnormality generates again, replace
indoor controller board or outdoor controller circuit board. * Other indoor controller board may have defect in case of twin triple indoor unit system.
Indoor/outdoor unit communication error (Transmitting error)
Abnormal if “1” receiving is detected 30 times continuously though indoor controller board has transmitted “0”.
1 Defective transmitting receiving
circuit of indoor controller board
2 Noise has entered into power
supply.
3 Noise has entered into outdoor
control wire.
1-3 Turn the power off, and on again to check.
If abnormality generates again, replace
indoor controller board.
Indoor/outdoor unit communication error (Signal receiving error)
1 Abnormal if indoor controller board cannot receive any signal normally for 6
minutes after turning the power on. 2 Abnormal if indoor controller board cannot receive any signal normally for 3
minutes. 3 Consider the unit abnormal under the fol-
lowing condition: When 2 or more indoor
units are connected to an outdoor unit, indoor controller board cannot receive a signal for 3 minutes
from outdoor controller circuit board, a
signal which allows outdoor controller
circuit board to transmit signals.
Indoor controller board
Abnormal if data cannot be read normally from the nonvolatile memory of the indoor controller board.
1 Defective indoor controller
board
1 Replace indoor controller board.
Remote controller control board
1 Abnormal if data cannot be read nor-
mally from the nonvolatile memory of the
remote controller control board.
(Error code: E1) 2 Abnormal if the clock function of remote
controller cannot be operated normally.
(Error code: E2)
1 Defective remote controller 1 Replace remote controller.
Page 20
20
(For the separate indoor/outdoor unit power sup-
ply system)
1 Power supply of 220~240V AC is not supplied to
indoor unit.
2 The connectors of the optional replacement kit are
not used.
3 Defective indoor controller board.
4 Defective indoor power board.
10-3. TROUBLESHOOTING BY INFERIOR PHENOMENA
Note: Refer to the manual of outdoor unit for the detail of remote controller.
Phenomena
Cause
Countermeasure (1)LED2 on indoor controller board is off.
• When LED1 on indoor controller board is also off. 1 Power supply of rated voltage is not supplied to out-
door unit.
2 Defective outdoor controller circuit board.
3 Power supply of 220~240V is not supplied to indoor
unit.
4 Defective indoor power board.
5 Defective indoor controller board.
1 Check the voltage of outdoor power
supply terminal block (L, N) or (L3, N).
• When AC 220~240V is not detected. Check the power wiring to outdoor unit and the breaker.
• When AC 220~240V is detected.
—Check 2 (below). 2 Check the voltage between outdoor terminal block S1 and S2.
• When AC 220~240V is not detected.
Check the fuse on outdoor controller cir-
cuit board.
Check the wiring connection.
• When AC 220~240V is detected.
—Check 3 (below). 3 Check the voltage between indoor terminal
block S1 and S2.
• When AC 220~240V is not detected. Check indoor/outdoor unit connecting wire for mis-wiring.
• When AC 220~240V is detected.
—Check 4 (below).
4 Check voltage output from CN2S on indoor
power board (DC13.1V). Refer to 10-6-1.
• When no voltage is output. Check the wiring connection.
• When output voltage is between DC12.5V
and DC13.7V.
—Check 5 (below).
5 Check the wiring connection between indoor
controller board and indoor power board. Check the fuse on indoor controller board. If no problems are found, indoor controller board is defective.
• When LED1 on indoor controller board is lit. 1 Mis-setting of refrigerant address for outdoor unit (There is no unit corresponding to refrigerant address “0”.)
1 Reconfirm the setting of refrigerant address
for outdoor unit Set the refrigerant address to “0”. (For grouping control system under
which 2 or more outdoor units are connected, set one of the units to “0”.) Set refrigerant address using SW1 (3-6) on outdoor controller circuit board.
1 Check the voltage of indoor power supply
terminal block (L,N).
• When AC220~240V is not detected. Check the power supply wiring.
• When AC220~240V is detected.
-Check 2 (below).
2 Check that there is no problem in the meth-
od of connecting the connectors.
• When there are problems in the method of connecting the connectors.
Connect the connector correctly referring
to installation manual of an optional kit.
• When there is no problem in the method of connecting the connectors.
-Check 3 (below).
3 Check voltage output from CNDK on indoor
controller board.
• When AC220~240V is not detected.
Check the fuse on indoor controller board. Check the wiring connection between
indoor power supply terminal block and CND on indoor controller board.
• When AC220~240V is detected.
-Check 4 (below).
4 Check voltage output from CN2S on indoor
power board.
• When no voltage output.
Check the wiring connection between CNDK on indoor controller board and CNSK on indoor power board. If no problem are found,indoor power
board is defective.
• When DC12.5~13.7V is detected.
Check the wiring connection between
CN2S on indoor power board and
CN2D on indoor power board. If no problem are found,indoor controller
board is defective.
Page 21
21
10-4.
WHEN WIRED REMOTE CONTROLLER OR INDOOR UNIT MICRO COMPUTER TROUBLES
1. If there is not any other wrong when trouble occurs, emergency operation starts as the indoor controller board switch (SWE) is set to ON.
During the emergency operation the indoor unit is as follows;
Indoor fan high speed operation
2. When emergency operating for COOL or HEAT, setting of the switch (SWE) on the indoor controller board and outdoor unit emergency operation are necessary.
3. Check items and notices as the emergency operation
(1) Emergency operation cannot be used as follows;
• When the outdoor unit is something wrong.
• When the indoor fan is something wrong.
• When drain over flow protected operation is detected during self-diagnosis. (Error code : P5)
(2) Emergency operation will be serial operation by the power supply ON/OFF.
ON/OFF or temperature, etc. adjustment is not operated by the remote controller.
(3) Do not operate for a long time as cold air is blown when the outdoor unit starts defrosting operation during heat emer-
gency operation. (4) Cool emergency operation must be within 10 hours. Other wire, heat exchanger of indoor unit may get frosted. (5) After completing the emergency operation, return the switch setting, etc. in former state. (6) Since vane does not work at emergency operation, position the vane slowly by hand.
Note: Refer to the manual of outdoor unit for the detail of remote controller.
(3)Upward/downward vane performance failure
1 The vane is not downward during defrosting and heat
preparation and when the thermostat is OFF in HEAT mode. (Working of COOL protection function)
2 Vane motor does not rotate.
• Defective vane motor
• Breaking of wire or connection failure of connector
• Up/down vane setting is “No vanes”.
3 Upward/downward vane does not work.
• The vane is set to fixed position.
1 Normal operation (The vane is set to
horizontal regardless of remote control.)
2 Check 2 (left).
• Check the vane motor. (Refer to “How to check the parts”.)
• Check for breaking of wire or connec­tion failure of connector.
• Check “Up/down vane setting”. (Unit function selection by remote controller).
3 Normal operation (Each connector on
vane motor side is disconnected.)
Phenomena
Cause
Countermeasure
(2)LED2 on indoor controller board is blinking.
• When LED1 on indoor controller board is also blinking. Connection failure of indoor/outdoor unit connecting wire
• When LED1 is lit. 1 Mis-wiring of remote controller wires
Under twin triple indoor unit system, 2 or more indoor
units are wired together.
2 Refrigerant address for outdoor unit is wrong or not
set. Under grouping control system, there are some units whose refrigerant address is 0.
3 Short-cut of remote controller wires 4 Defective remote controller
Check indoor/outdoor unit connecting wire for connection failure.
1 Check the connection of remote con­ troller wires in case of twin triple indoor
unit system. When 2 or more indoor units are wired in one refrigerant system, connect remote controller wires to one of
those units.
2 Check the setting of refrigerant address
in case of grouping control system. If there are some units whose refrigerant addresses are 0 in one group, set one of the units to 0 using SW1 (3-6) on outdoor controller circuit board. 34 Remove remote controller wires and check LED2 on indoor controller board.
• When LED2 is blinking, check the short­cut of remote controller wires.
• When LED2 is lit, connect remote
controller wires again and: if LED2 is blinking, remote controller is defective; if LED2 is lit, connection failure of remote controller terminal block etc. has returned to normal.
(4)Receiver for wireless remote controller
1 Weak batteries of wireless remote controller. 2 Contact failure of connector (CNB) on wireless
remote controller board.
(Insert failure) 3 Contact failure of connector (CN90) on indoor con-
troller board.(Insert failure)
4 Contact failure of connector between wireless remote
controller board and indoor controller board.
1 Replace batteries of wireless remote con-
troller.
2~4 Check contact failure of each connector. If no problems are found of connector,
replace indoor controller board.
When the same trouble occurs even if
indoor controller board is replaced,
replace wireless remote controller
board.
Page 22
22
10-5. HOW TO CHECK THE PARTS
PCA-RP71HA PCA-RP71HA#1 PCA-RP125HA PCA-RP125HA#1
Measure the resistance between the terminals with a tester. (Winding temperature 20)
Fan motor
(MF)
Open or short
Abnormal
White
Orange
Yellow
Blue
Black
Red
Relay connector
Protector
Protector
OPEN : 135±5 CLOSE : 95±15
White–Black
Black–Blue
Blue–Yellow
Yellow–Red
Connector
PCA-RP71
140.5
15.4
28.5
80.4
PCA-RP125
75.6
36.7
23.6
47.8
Normal
Parts name Check points
Disconnect the connector then measure the resistance with a tester. (At the ambient temperature 10~30)
(Refer to <Thermistor Characteristic graph> for a detail.)
Room temperature thermistor (TH1)
Pipe temperature thermistor (TH2)
Condenser/Evaporator temperature thermistor (TH5)
Normal
4.3k~9.6k
Abnormal
Open or short
0
10
20
30
40
50
-20-100 1020304050
< Thermistor for lower temperature >
Temperature ()
Resistance (K)
<Thermistor Characteristic graph>
Room temperature thermistor(TH1) Pipe temperature thermistor(TH2) Condenser/evaporator temperature thermistor(TH5)
Thermistor R0=15k ± 3% Fixed number of B=3480k ± 2%
Rt=15exp { 3480( ) } 0: 15k
10: 9.6k 20: 6.3k 25: 5.4k 30: 4.3k 40: 3.0k
Thermistor for lower temperature
1
273+t
1
273
Page 23
23
10-6. TEST POINT DIAGRAM
10-6-1. Power board PCA-RP71HA PCA-RP71HA#1 PCA-RP125HA PCA-RP125HA#1
CNSK Connect to the indoor controller board (CNDK) Between 1 to 3 220-240V AC
CN2S Connect to the indoor controller board (CN2D) Between 1 to 3 12.6-13.7V DC (Pin1 (+))
Page 24
24
10-6-2. Indoor controller board
PCA-RP71HA PCA-RP71HA#1 PCA-RP125HA PCA-RP125HA#1
FAN Fan motor output
CNP Drain-pump output (DP) (220~240V AC)
CNC Dew prevention heater (H2) (220~240V AC)
CNDK Connect to the indoor power board (CNSK) (220~240V AC)
FUSE (6.3A 250V)
CND Power supply input (220~240V AC)
SWE Emergency operation
SW2 Capacity setting
SW1 Model setting
CN2L Connector (LOSSNAY)
CN51 Centrally control
CN6V Vane motor output (MV)
CN90 Connect to the wire­less remote controller board (CNB)
CN31 Drain sensor (DS)
CN29 Condenser/evaporator temperature thermistor (TH5)
CN21 Pipe temperature thermistor/Liquid (TH2)
CN20 Room temperature thermistor (TH1)
CN22 Remote controller connecting wire (10.4~14.6V DC)
LED3 Transmission (Indoor/outdoor)
LED2 Power supply (R.B)
LED1 Power supply (I.B)
CN2D Connector to the indoor power board (CN2S) (12.5~13.7V DC)
CN3C Transmission (Indoor/outdoor) (0~24V DC)
}
}
+
+
CN41 Connector (HA terminal-A)
Page 25
25
SW1
Setting by the dip switch and jumper wire
Functions
Jumper wire
Model settings
Capacity settings
Pair number setting with wireless remote controller
For service board
Remarks
SW2
J41 J42
Unit type setting
JP1
Indoor controller board type setting
JP3
0 1 2
3 ~ 9
Wireless remote controller setting
Control PCB setting
J41 J42
<Initial setting> Wireless remote controller: 0 Control PCB: (for both J41 and J42) Four pair number settings are supported. The pair number settings of the wireless remote controller and indoor control PCB (J41/J42) are given in the table on the left. (' ' in the table indicates the jumper line is disco­nnected.)
There is no jumper (JP1) because these models have the cond./eva. temperature thermistor (TH5).
(Marks in the table below) Jumper wire ( : Short : Open)
Without TH5
With TH5
Model
JP1
For product
Service parts
Indoor controller board type
JP3
12345
ON
OFF
Service board
MODELS
PCA-RP71HA
1 2 3 4 5
ON OFF
PCA-RP125HA
1 2 3 4 5
ON OFF
10-7. FUNCTIONS OF DIP SWITCH AND JUMPER WIRE
Each function is controlled by the dip switch and the jumper wire on control p.c. board. SW1 and SW2 are equipped only for service parts. Model setting and capacity setting are memorized in the nonvolatile memory of the control p.c. board of the unit.
Page 26
26
SPECIAL FUNCTION
11
Note:
· When the uint is restarted to operate after turning off the power or OFF operation, the unit which was operating will start operation.
· To operate the main unit, refer to the 11-1-2. and set the requet code No. which is not the same as the current one, and set again the former request code No.
(2) 2nd stage cut-in function Outline of functions
· Number of operating units is determined according to the room temperature and set point.
· When room temperature becomes higher than set point, standby unit starts.(2 units operation)
· When room temperature falls below set point -4:, standby unit stops.(1 unit operation)
System constraint
· This function is available only in rota­tion operation and back-up function in cooling mode.
[2nd stage cut-in function]··· Request code number "322~324"
Start operation Sub unit start operation
Room temp. Set point
Sub unit stop
Run
Stop StopRun
Main
unit
IC-1
Sub
unit
IC-2
Room temp. < Set point -4
11-1. ROTATION FUNCTION(AND BACK-UP FUNCTION, 2ND STAGE CUT-IN FUNCTION)
For PCA-RP71/125HA#1 11-1-1. Operation (1) Rotation function (and Back-up function)
• Outline of functions
· Main and sub unit operate alternately according to the interval of rotation setting. w Main and sub unit should be set by refrigerant address.(Outdoor Dip switch setting) Refrigerant address"00" Main unit Refrigerant address"01" Sub unit
· When error occurrs to one unit, another unit will start operation.(Back-up function)
• System constraint
· This function is available only by the grouping control system(INDOOR UNIT : OUTDOOR UNIT=1:1) of 2 refrigerant
groups.(Refer to Fig. 1)
· Main indoor unit should be connected for wired remote controller and the transmission line(TB5) for main and sub unit
should also be connected. (Refer to Fig. 1)
(This function cannot be set by wireless remote controller.)
· Set refrigerant address of each unit.(Dip switch on the outdoor unit···Refrigerant address 00/01)
Operation pattern
OC-1
OC-2
IC-1
IC-2
3(2)
3(2)
2
RC
2
Main unit
Sub unit
Refrigerant address "01"
Refrigerant address "00"
Fig. 1
[Back-up function only]··· Request code number "312"

[Rotation function] & [Back-up function]··· Request code number "313~318"
(Ex:When the request code number is "313", each unit operates alternately in daily cycle.)
Error occurs on main unit.
Start operation
Run
Abnormal condition
Stop
Run
Main
unit
IC-1
Sub
unit
IC-2
Error occurs on main unit.
Start operation
1~28 days 1~28 days
Run
Abnormal condition
Stop
Stop
Run
Run
Stop Run
Main
unit
IC-1
Sub
unit
IC-2
Main Sub
Main Sub Sub Main Main Sub
OC : Outdoor unit IC : Indoor unit RC : Wired remote controller
Page 27
2727
11-1-2. How to set rotation function(Back-up function, 2nd stage cut-in function)
You can set these functions by wired remote controller.(Maintenance monitor)
Both main and sub unit should be set in same setting. Every time replacing indoor controller board for servicing, the function should be set again.
NOTICE
Setting No.
(Request code)
Setting contents
Initial
setting
No.1 (310)
Monitoring the request code of current setting.
No.2 (311)
Rotation and Back-up OFF (Normal group control operation)
No.3 (312)
Back-up function only
No.4 (313)
Rotation ON (Alternating interval = 1day) and back up function
No.5 (314)
Rotation ON (Alternating interval = 3day) and back up function
No.6 (315)
Rotation ON (Alternating interval = 5day) and back up function
No.7 (316)
Rotation ON (Alternating interval = 7day) and back up function
No.8 (317)
Rotation ON (Alternating interval = 14day) and back up function
No.9 (318)
Rotation ON (Alternating interval = 28day) and back up function
Setting No.
(Request code)
Setting contents
Initial
setting
No.1 (320)
Monitoring the request code of current setting.
No.2 (321)
Cut-in function OFF
No.3 (322)
Cut-in Function ON(Set point = Set temp.+ 4°C(7.2°F))
No.4 (323)
Cut-in Function ON(Set point = Set temp.+ 6°C(10.8°F))
No.5 (324)
Cut-in Function ON(Set point = Set temp.+ 8°C(14.4°F))
(1) Request Code List Rotation setting
2
nd stage cut-in setting
Page 28
28
(2) Setting method of each function by wired remote controller
B: Refrigerant address C: Data display area D: Request code display area
TEST
CHECK
FILTER
  
FILTER
ON/OFF
1. Stop operation().
2. Press the button () for 3 seconds so that [Maintenance mode] appears on the screen (). After a while, [00] appears in the refrigerant address number display area.(at  )
3. Press the button () for 3 seconds to switch to [Maintenance monitor]. Note) It is not possible to switch to [Maintenance monitor] during data request in maintenance mode
(i.e., while “----” is blinking) since no buttons are operative.
[----] appears on the screen () when [Maintenance monitor] is activated. (The display () now allows you to set a request code No.)
4. Press the [TEMP ( and )] buttons () to select the desired refrigerant address.
5. Press the [CLOCK ( and )] buttons () to set the desired request code No.(“311~318”, “321~324”)
6. Press the button () to perform function setting.
If above setting operations are done correctly, "Request code number will appear in data display area.() [Example: When the "311" of "Request code number" is set, [311] appears on the screen.()]
[Refererence] You can check current "request code number" setting by setting the "request code number"(“310” or “320”) and pressing the button.() [Example: When the current setting is "Setting No.2(Request code 311)", [311] appears on the screen.()]
7. To return to normal mode, press the button ().
[ScreenB]
Page 29
2929
PCA-RP71HA PCA-RP125HA PCA-RP71HA#1 PCA-RP125HA#1
12
DISASSEMBLY PROCEDURE
1. Removing the oil filter
(1) Slide the oil filter towards you to remove. (See figure 1.)
OPERATING PROCEDURE PHOTOS&ILLUSTRATIONS
Figure 1
Photo 1
Slide
2. Removing the terminal block box cover
(1) Remove the oil filter. (See figure 1.) (2) Remove a screw for terminal block box cover, and remove
the terminal block box cover. (See photo 1.)
Terminal block box cover
Terminal block box
Screw
Clamp for wiring
3. Removing the control box
(1) Remove the oil filter. (See figure 1.) (2) Loosen the screw for control box cover to remove the
control box cover. (See photo 2.) (3) Remove the lead wire from the 2 clips. (4) Remove the 2 white cord heater relay connectors (1P o 2)
and 2 fan motor relay connectors (6P o 2) in the control
box. (5) Remove the 2 screws for control box to slide the control
box downward. Electrical parts in the control box
• Fan motor capacitor
• Indoor controller board
• Power board
Photo 2
Photo 3
Screws for control box
Screw for control box cover
Clip for lead wire
Cord heater relay connectors
Power board
Fan motor capacitor
Fan motor relay connectors
Room temperature thermistor connector (CN20)
Pipe temperature thermistor connector (CN21)
Indoor controller board
Oil filter
Filter rail Fan guard
Page 30
OPERATING PROCEDURE PHOTOS&ILLUSTRATIONS
4. Removing the fan motor
(1) Remove the oil filter. (See figure 1.) (2) Remove the control box cover. (See photo 2.) (3) Remove the room temperature thermistor connector (CN20)
on the indoor controller board. (See photo 3.) (4) Remove a filter rail that is the nearest to the control box. (See photo 4.) (5) Remove the fan guard. (See photo 5.) (6) Remove the room temperature thermistor together with the
holder at the right side of the casing.
5. Removing the fan motor and the sirocco fan
(1) Remove the oil filter. (See figure 1.) (2) Remove the control box cover.
(See photo 2.)
(3) Remove the fan motor relay connectors (6P) in the control
box. (See photo 3.)
(4) Remove the 3 filter rails.
(See photo 1, 4.)
(5) Remove the fan guard.
(See photo 5.)
(6) Remove the lower casing.
(See photo 6.)
(7) Remove the green earth wire from the motor support.
(See photo 7.)
(8) Remove the 2 screws (M5 × 12) for motor support, and
remove the left and right motor supports.
(9) Remove the fan motor together with the sirocco fan.
(10) Remove the 2 set screws (M6) to separate the fan motor
from the sirocco fan.
Photo 4
Photo 6
Fan guard
Screws for Fan guard
Room temperature thermistor
Screws for Fan guard
Control box cover
Screws for casing
Screws for motor support
Motor support
Fan motor
casing
Set screws
Screws for casing
casing
Sirocco fan
Sirocco fan
Photo 7
Earth wire
Screws for filter reil
Filter reil
Room temperature thermistor
Photo 5
Control box cover
30
Page 31
OPERATING PROCEDURE PHOTOS
6. Removing the pipe temperature thermistor
(1) Remove the oil filter. (See figure 1.) (2) Remove the fan guard.
(See photo 1.) (3) Remove the terminal block box cover. (4) Remove the white relay connector (2P) in the terminal
block box. (See photo 8.) (5) Remove the service panel. (See photo 9.) (6) Remove the pipe temperature thermistor from the holder.
(See photo 10.)
8. Removing the drain pan
(1) Remove the oil filter. (See Figure 1) (2) Remove the 3 filter rails. (See photo 1, 4.) (3) Remove the under panel. (See photo 11.) (4) Pull the blue lead wire for cord heater towards you to
slack off. (See photo 12.) (5) Remove the 3 screws at the center of the drain pan, and
remove the drain pan. (Note) Remove the drain pan carefully since the drain could
remain in it.
7. Removing the under panel
(1) Remove the oil filter. (See figure 1.) (2) Remove the 3 filter rails. (See photo 1, 4.) (3) Remove the 12 screws (left: 1, right: 1, Bottom: 10) for
under panel, and remove the under panel. (See photo 11.)
Photo 8
Photo 9
Photo 11
Photo 12
Caution for installation
When installing the pipe temperature thermistor, slack off its lead wire as shown in the photo. Otherwise, water trickled down the lead wire may splash on the connector and this could cause a short circuit of the connector.
Photo 10
Terminal block box
Relay connector
Screw for service panel
Service panel
Inspection port
Pipe temperature thermistor
Slack off
Screws for drain pan
Lead wire for cord heater
Drain pan
Screws for under panel (Bottom:10)
Screw for
under panel
(left:1)
Screw for under panel (right:1)
Under panel
31
Page 32
32
OPERATING PROCEDURE PHOTOS
9. Removing the guide vane
(1) Remove the oil filter. (See figure 1.) (2) Remove the 3 filter rails. (See photo 1, 4.) (3) Remove the under panel. (See photo 11.) (4) Remove the drain pan. (See photo 12.) (5) Remove the 3 screws (4 × 10) for guide vane, and
remove the guide vane. (See photo 13.)
10. Removing the vane
(1) Slide the vane to the center of the unit, and pull it towards
you to remove. (See photo 14.)
11. Removing the heat exchanger
(1) Remove the oil filter. (See figure 1.) (2) Remove the 3 filter rails. (See photo 1, 4.) (3) Remove the under panel. (See photo 11.) (4) Remove the drain pan. (See photo 12.) (5) Remove the 2 screws (4 × 10) for pipe cover, and remove
the pipe cover. (See photo 15.)
(6) Remove the 3 screws (4 × 10, left: 2, right: 1) for heat
exchanger. (See photo 15, 16.)
(7) Remove the 2 screws (4 × 10) for heat exchanger at the
top of the unit, and remove the heat exchanger.
(See photo 17.)
Photo 13
Photo 14
Photo 15
Caution for installation
When installing the vane, check that its projection is on the left-rear side.
Guide vane
Screws for guide vaneDrain pan
Vane
Slide
Slide
Screw for pipe cover
pipe cover
Heat exchanger
Screw for Heat exchanger (right)
Screws for Heat exchanger (left)
Heat exchanger
Photo 16Photo 17
Screws for Heat exchanger (top)
Heat exchanger
Projection
Page 33
33
13
PARTS LIST (non-RoHS compliant)
No.
Parts No. Parts Name
Specifications
PCA-RP
71HA
Wiring
Diagram
Symbol
Recom­mended
Q'ty
Q'ty / set
Remarks
(Drawing No.)
125HA
1 2
3
4
5
7 8 9
10
11
12
13
14 15 16 17 18 19
LEG-L SIDE PLATE-L REAR PANEL REAR PANEL UNDER PANEL UNDER PANEL FILTER RAIL OIL FILTER DRAIN HOSE SUPPORT SIDE COVER LEG-R SERVICE PANEL SIDE PLATE-R FRONT PANEL FRONT PANEL VANE ASSY VANE ASSY GUIDE VANE ASSY-6L GUIDE VANE ASSY-6C GUIDE VANE ASSY-6R VANE HOLDER VANE SUPPORT FRONT SUPPORT
R01 13N 809 R01 13N 662 T7W E02 676 T7W E03 676 R01 12N 669 R01 13N 669 R01 13N 503 R01 E05 500
— R01 13N 667 R01 13N 808 R01 13N 668 R01 13N 661 T7W E02 651 T7W E03 651 R01 12N 002 R01 13N 002 R01 13N 086 R01 13N 087 R01 13N 085 R01 13N 533
2 1 1
1
2 3 1 1 2 1 1 1
2
1
1 1 1 1
2 1
1
1 3 4 1 1 2 1 1
1
3 1 1 1 2 2 2
(BG00K145G02)
(BG00K146G02) (BG00T773G01)
6
STRUCTURAL PART PCA-RP71HA PCA-RP125HA
1 2
3
4 5
6
7
8
9
10
11
13
12
16
15
14
17
18
19
Page 34
34
No.
Parts No. Parts Name
Specifications
PCA-RP
71HA
Wiring
Diagram
Symbol
Recom-
mended
Q'ty
Q'ty / set
Remarks
(Drawing No.)
125HA
TH1
TH2 TH5
MF1 MF1,2
PA6V40-CB PA4V80-CA
1
2
3
4 5
6
7
8
9
10
11 12 13
14
15 16
17
18 19 20 21 22 23
T. CASING ASSY T. CASING ASSY SIROCO FAN SIROCO FAN UNDER CASING-L UNDER CASING-L FAN GUARD-S ROOM TEMPERATUR TERMISTOR FAN GUARD-L FAN GUARD-L UNDER CASING-R UNDER CASING-R FAN GUARD-S DRAINPAN ASSY DRAINPAN ASSY FAN PLATE FAN PLATE PIPE SUPPORT PIPE TEMPERATURE TERMISTOR CONDENSER / EVAPORATOR TEMPERATURE TERMISTOR HEAT EXCHANGER HEAT EXCHANGER FAN PLATE SUPPORT-R FAN PLATE SUPPORT-C FAN MOTOR FAN MOTOR MOTOR LEG PIECE FOR MOTOR FAN PLATE SUPPORT-L PIPE COVER DRAIN HOSE COVER RUBBER MOUNT
(BG00N756G15) (BG00N756G14) (BG02T500H04)
(BG00N893G15) (BG00N893G14)
(BG00N893G13)
R01 12N 110 R01 13N 110 R01 12N 114 R01 13N 114 T7W E02 111 T7W E03 111 T7W E12 675 R01 E51 202 T7W E14 675 T7W E13 675 T7W E00 111 T7W E01 111 T7W E11 675 R01 12N 529 R01 13N 529
— —
— R01 13N 202 R01 E63 202 R01 H04 480 T7W K07 480
— T7W E20 762 T7W E21 762 R01 45K 130 R01 83E 126
— R01 13N 521 R01 13N 072 R01 811 105
2
2
1
1 1 1
1
1 1
1
1 1 1 1
1 1 1
1 1 1 1 1 2
4
4
2 2 1
2
2 2
1
2 1 1 1
1 1 1
2 2 2 1 1 1 4
Part numbers that are circled are not shown in the figure.
1 2 3
4
9
5 6
8
10
11
13
14
12
16
18,19 17
FAN PARTS PCA-RP71HA PCA-RP125HA
7
20 15
4
6
8
Page 35
35
TO REMOTE CONTROLLER
TO OUTDOOR UNIT
21
S3S2S1
ELECTRICAL PARTS PCA-RP71HA PCA-RP125HA
1
ON/OFF
TEMP.
No.
Parts No. Parts Name Specifications
PCA-RP
71HA
Wiring
Diagram
Symbol
Recom­mended
Q'ty
Q'ty / set
Remarks
(Drawing No.)
125HA
(BG02N713H05)
(BG00T759G13)
1
2
3
4
5
6
7
8
9
10
11
SUPPORT
CONTROLLER BOARD
FUSE
POWER BOARD
RUN CAPACITOR
RUN CAPACITOR
CONTROL BOX COVER
CONTROL BOX
TERMINAL BLOCK
TERMINAL BLOCK
REMOTE CONTROLLER
R01 18J 054
T7W E41 310
R01 E02 239
R01 E02 313
R01 A00 255
R01 576 255
T7W E23 716
R01 556 246
T7W E08 713
9
1
1
1
1
1
1
1
1
1
I.B
FUSE
P. B
C1
C1,C2
TB4
TB5
R.B
250V 6.3A
2.5, 440V
3, 440V
3P(S1, S2, S3)
2P(1, 2)
PAR-21MAA
9
1
1
1
2
1
1
1
1
1
2
3
4
1
6
5
9 10
11
7, 8
Page 36
36
14
RoHS PARTS LIST
No.
Parts No. Parts Name
Specifications
PCA-RP
71HA
Wiring
Diagram
Symbol
Recom-
mended
Q'ty
Q'ty / set
Remarks
(Drawing No.)
125HA
7 8 9
10
14 15 16 17 18 19
LEG-L SIDE PLATE-L REAR PANEL REAR PANEL UNDER PANEL UNDER PANEL FILTER RAIL OIL FILTER
DRAIN HOSE SUPPORT SIDE COVER LEG-R SERVICE PANEL SIDE PLATE-R FRONT PANEL FRONT PANEL VANE ASSY VANE ASSY GUIDE VANE ASSY-6L GUIDE VANE ASSY-6C GUIDE VANE ASSY-6R VANE HOLDER VANE SUPPORT FRONT SUPPORT
R01 15N 669 R01 14N 503 R01 14N 500
— R01 14N 667 R01 14N 808 R01 14N 668 R01 14N 661 T7W 14N 651 T7W 15N 651 R01 15N 002 R01 16N 002 R01 14N 086 R01 14N 087 R01 14N 085 R01 14N 533
2 1 1
1
2 3
1 1 2 1 1 1
2
1
1 1 1 1
2 1
1
1 3 4
1 1 2 1 1
1
3 1 1 1 2 2 2
(BG00K145G02)
(BG00K146G02) (BG00T773G02)
RoHS
G G G G G G G G G G G G G G G G G G G G G G
1 2
3
4
5
6
13
G
R01 14N 809
R01 14N 662 T7W 14N 676 T7W 15N 676
R01 14N 669
12
11
G
R01 15N 500
OIL FILTER
71HA#1
125HA#1
2 1 1
1
2
3 1 1 2 1 1 1
2
1
1 1 1 1
2 1
1
1 3
4 1 1 2 1 1
1
3 1 1 1 2 2 2
STRUCTURAL PART PCA-RP71/125HA PCA-RP71/125HA#1
1 2
3 4
5
6
7
8
9
10
11
13
12
16
15
14
17
18
19
Page 37
3737
Part numbers that are circled are not shown in the figure.
RoHS
No.
Parts No. Parts Name
Specifications
PCA-RP
71HA·71HA#1
Wiring
Diagram
Symbol
Recom-
mended
Q'ty
Q'ty / set
Remarks
(Drawing No.)
125HA·125HA#1
TH1
TH2 TH5
MF1 MF1,2
PA6V40-CC PA4V80-CA
1
2
3
4 5
6
7
8
9
10
11 12 13
14
15 16
17
18 19 20
21
22
23
T. CASING ASSY T. CASING ASSY SIROCO FAN SIROCO FAN UNDER CASING-L UNDER CASING-L FAN GUARD-S(L) ROOM TEMPERATUR TERMISTOR FAN GUARD-L FAN GUARD-L UNDER CASING-R UNDER CASING-R FAN GUARD-S(R) DRAINPAN ASSY DRAINPAN ASSY FAN PLATE FAN PLATE PIPE SUPPORT PIPE TEMPERATURE TERMISTOR CONDENSER / EVAPORATOR TEMPERATURE TERMISTOR HEAT EXCHANGER HEAT EXCHANGER FAN PLATE SUPPORT-R FAN PLATE SUPPORT-C FAN MOTOR FAN MOTOR MOTOR LEG PIECE FOR MOTOR FAN PLATE SUPPORT-L PIPE COVER DRAIN HOSE COVER RUBBER MOUNT
(BG00N756G17) (BG00N756G16) (BG02T500H04)
(BG00N893G15) (BG00N893G14)
(BG00N893G13)
R01 14N 110 R01 15N 110 R01 14N 114 R01 15N 114 T7W 16N 111 T7W 17N 111 T7W 18N 675 R01 15N 202 T7W 15N 675 T7W 16N 675 T7W 14N 111 T7W 15N 111 T7W 17N 675 R01 15N 529 R01 16N 529
— —
— R01 16N 202 R01 17N 202 R01 J68 480 T7W H55 480
— T7W 14N 762 T7W 15N 762 R01 14N 130 R01 14N 126
— R01 14N 521 R01 14N 072 R01 14N 105
2
2
1
1 1 1
1
1 1
1
1 1 1 1
1 1 1
1 1 1 1 1 2
4
4
2 2 1
2
2 2
1
2 1 1 1
1 1 1
2 2 2 1 1 1 4
G G G G G G G G G G G G G G G G G G G G G G G G G G G G G G G G
1 2 3
4
9
5 6
8
10
11
13
14
12
16
18,19 17
FAN PARTS PCA-RP71/125HA PCA-RP71/125HA#1
7
20 15
4
6
8
Page 38
38
TO REMOTE CONTROLLER
TO OUTDOOR UNIT
21
S3S2S1
ELECTRICAL PARTS PCA-RP71/125HA PCA-RP71/125HA#1
1
ON/OFF
TEMP.
No.
Parts No. Parts Name
Specifications
PCA-RP
71HA
Wiring
Diagram
Symbol
Recom-
mended
Q'ty
Q'ty / set
Remarks
(Drawing No.)
125HA
(BG02N713H07)
(BG00T759G16)
1
3
4
5
6
7
8
9
10
11
SUPPORT
CONTROLLER BOARD
FUSE
POWER BOARD
RUN CAPACITOR
RUN CAPACITOR
CONTROL BOX COVER
CONTROL BOX
TERMINAL BLOCK
TERMINAL BLOCK
REMOTE CONTROLLER
R01 20J 054
T7W E51 310
R01 E06 239
R01 E38 313
R01 14N 255
R01 E12 255
R01 E20 246
R01 E21 246
T7W E11 713
9
1
1
1
1
1
1
1
1
1
I.B
FUSE
P. B
C1
C1,C2
TB4
TB5
R.B
250V 6.3A
2.5, 440V
3, 440V
3P(S1, S2, S3)
2P(1, 2)
PAR-21MAA
9
1
1
1
2
1
1
1
1
1
G
G
G
G
G
G
G
G
G
G
G
125HA#1
1
1
2
1
1
1
1
71HA#1
1
1
1
1
1
1
1
2
T7W E74 310
1
1
G
CONTROLLER BOARD
9
1
I.B
1
RoHS
9
2
3
4
1
6
5
9 10
11
7, 8
Page 39
39
Page 40
HEAD OFFICE : TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
CCopyright 2005 MITSUBISHI ELECTRIC ENGINEERING CO., LTD. Distributed in May 2008 No.OC329 REVISED EDITION-B PDF 7 Distributed in Jul. 2006 No.OC329 REVISED EDITION-A PDF 8 Distributed in Jun. 2005 No.OC329 PDF 9 Made in Japan.
New publication, effective May 2008. Specifications subject to change without notice.
TM
Loading...