Before obtaining access to terminal, all supply
circuits must be disconnected.
3-2. CAUTIONS RELATED TO NEW REFRIGERANT
Cautions for units utilising refrigerant R407C
Do not use the existing refrigerant piping.
The old refrigerant and lubricant in the existing piping
contains a large amount of chlorine which may cause the
lubricant deterioration of the new unit.
Use “low residual oil piping”
If there is a large amount of residual oil (hydraulic oil, etc.)
inside the piping and joints, deterioration of the lubricant
will result.
Store the piping to be used during installation
indoors with keep both ends sealed until just
before brazing.
(Store elbows and other joints in a plastic bag.)
If dust, dirt, or water enters the refrigerant cycle,
deterioration of the oil and compressor trouble may result.
Use ESTER , ETHER or HAB as the lubricant to
coat flares and flange connection parts.
If large amount of mineral oil enter, that can cause
deterioration of refrigerant oil etc.
Use liquid refrigerant to charge the system.
If gas refrigerant is used to seal the system, the composition
of the refrigerant in the cylinder will change and performance
may drop.
Do not use a refrigerant other than R407C.
If another refrigerant (R22, etc.) is used, the chlorine in the
refrigerant may cause the lubricant deterioration.
Use a vacuum pump with a reverse flow check valve.
The vacuum pump oil may flow back into the refrigerant
cycle and cause the lubricant deterioration.
Ventilate the room if refrigerant leaks during
operation. If refrigerant comes into contact with
a flame, poisonous gases will be released.
3
[1] Cautions for service
·After recovering the all refrigerant in the unit, proceed to working.
·Do not release refrigerant in the air.
·After completing the repair service, recharge the cycle with the specified amount of
liquid refrigerant.
[2] Refrigerant recharging
(1) Refrigerant recharging process
1Direct charging from the cylinder.
·R407C cylinder are available on the market has a syphon pipe.
·Leave the syphon pipe cylinder standing and recharge it.
(By liquid refrigerant)
Unit
Gravimeter
(2) Recharge in refrigerant leakage case
·After recovering the all refrigerant in the unit, proceed to working.
·Do not release the refrigerant in the air.
·After completing the repair service, recharge the cycle with the specified amount of
liquid refrigerant.
[3] Service tools
Use the below service tools as exclusive tools for R407C refrigerant.
No. Tool name Specifications
1Gauge manifold ·Only for R407C.
·Use the existing fitting SPECIFICATIONS. (UNF7/16)
·Use high-tension side pressure of 3.43MPa·G or over.
2Charge hose ·Only for R407C.
·Use pressure performance of 5.10MPa·G or over.
3 Electronic scale
4Gas leak detector ·Use the detector for R134a or R407C.
5Adapter for reverse flow check. ·Attach on vacuum pump.
6Refrigerant charge base.
7Refrigerant cylinder. ·For R407C ·Top of cylinder (Brown)
·Cylinder with syphon
8Refrigerant recovery equipment.
—
—
—
4
CAUTIONS RELATED TO NEW REFRIGERANT
Cautions for units utilising refrigerant R410A
Use new refrigerant pipes.
In case of using the existing pipes for R22, be careful with
the followings.
· For RP60/71VHA3 and RP100/125/140, be sure to
perform replacement operation before test run.
· Change flare nut to the one provided with this product.
Use a newly flared pipe.
· Avoid using thin pipes.
Make sure that the inside and outside of refrigerant piping is clean and it has no contamination
such as sulfur hazardous for use, oxides, dirt,
shaving particles, etc.
In addition, use pipes with specified thickness.
Contamination inside refrigerant piping can cause deterioration of refrigerant oil etc.
Store the piping to be used during installation
indoors and keep both ends of the piping sealed
until just before brazing. (Leave elbow joints, etc.
in their packaging.)
If dirt, dust or moisture enter into refrigerant cycle, that can
cause deterioration of refrigerant oil or malfunction of compressor.
Do not use refrigerant other than R410A.
If other refrigerant (R22 etc.) is used, chlorine in refrigerant can cause deterioration of refrigerant oil etc.
Use a vacuum pump with a reverse flow check
valve.
Vacuum pump oil may flow back into refrigerant cycle and
that can cause deterioration of refrigerant oil etc.
Use the following tools specifically designed for
use with R410A refrigerant.
The following tools are necessary to use R410A refrigerant.
If dirt, dust or moisture enter into refrigerant cycle, that can
cause deterioration of refrigerant oil or malfunction of compressor.
Use ester oil, ether oil or alkylbenzene oil (small
amount) as the refrigerant oil applied to flares
and flange connections.
If large amount of mineral oil enter, that can cause deterioration of refrigerant oil etc.
Do not use a charging cylinder.
If a charging cylinder is used, the composition of refrigerant will change and the efficiency will be lowered.
Ventilate the room if refrigerant leaks during
Charge refrigerant from liquid phase of gas
cylinder.
If the refrigerant is charged from gas phase, composition
change may occur in refrigerant and the efficiency will be
lowered.
operation. If refrigerant comes into contact with
a flame, poisonous gases will be released.
[1] Cautions for service
(1) Perform service after collecting the refrigerant left in unit completely.
(2) Do not release refrigerant in the air.
(3) After completing service, charge the cycle with specified amount of refrigerant.
(4) When performing service, install a filter drier simultaneously.
Be sure to use a filter drier for new refrigerant.
[2] Additional refrigerant charge
When charging directly from cylinder
· Check that cylinder for R410A on the market is syphon type.
· Charging should be performed with the cylinder of syphon stood vertically. (Refrigerant is charged from liquid phase.)
5
Unit
Gravimeter
[3] Service tools
Use the below service tools as exclusive tools for R410A refrigerant.
No. Specifications
1Gauge manifold ·Only for R410A
·Use the existing fitting
·Use high-tension side pressure of 5.3MPa·G or over.
2Charge hose ·Only for R410A
·Use pressure performance of 5.09MPa·G or over.
3 Electronic scale
4Gas leak detector ·Use the detector for R134a, R407C or R410A.
5Adaptor for reverse flow check ·Attach on vacuum pump.
6Refrigerant charge base
7Refrigerant cylinder ·Only for R410A Top of cylinder (Pink)
Cylinder with syphon
8Refrigerant recovery equipment
specifications
. (UNF1/2)
6
4
PAR-21MAA
ON/OFF
FILTER
CHECK
OPERATION
CLEAR
TEST
TEMP.
MENU
BACKDAY
MONITOR/SET
CLOCK
ON/OFF
Set T emperature buttons
Down
Up
Timer Menu button
(Monitor/Set button)
Mode button (Return button)
Set Time buttons
Back
Ahead
Timer On/Off button
(Set Day button)
Opening the
door.
ON/OFF button
Fan Speed button
Filter button
(<Enter> button)
Test Run button
Check button (Clear button)
Airflow Up/Down button
Louver button
( Operation button)
To preceding operation
number.
Ventilation button
(
Operation button)
To next operation number.
PART NAMES AND FUNCTIONS
Indoor Unit
Air outlet
Left/right guide vanes
Change the direction of airflow
from the horizontal blower.
Long-life filter
Removes dust and foreign matter from air coming in
through the grille (Recommended cleaning interval :
Approx, every 2,500 operating hours)
Up/down guide vanes
Change the direction of airflow from the
vertical blower.
Remote controller
Once the controls are set, the same operation mode can be repeated by simply pressing the ON/OFF button.
Operation buttons
Intake grille
Air intake
77
Display
For purposes of this explanation,
all parts of the display are shown
as lit. During actual operation, only
the relevant items will be lit.
Identifies the current operation
Shows the operating mode, etc.
* Multilanguage display is sup-
ported.
“Centrally Controlled” indicator
Indicates that operation of the remote controller has been prohibited by a master controller.
“Timer Is Off” indicator
Indicates that the timer is off.
Temperature Setting
Shows the target temperature.
Day-of-Week
Shows the current day of the week.
Time/Timer Display
Shows the current time, unless the simple or Auto Off
timer is set.
If the simple or Auto Off timer is set, shows the time
remaining.
TIME SUN MON TUE WED THU FRI SAT
TIMER
AFTER
ERROR CODE
°F°C
Hr
AFTER
°F°C
ONLY1Hr.
Up/Down Air Direction indicator
The indicator shows the direction of the outcoming airflow.
“One Hour Only” indicator
Displayed if the airflow is set to
weak and downward during COOL
or DRY mode. (Operation varies
according to model.)
The indicator goes off after one
hour, at which time the airflow direction also changes.
Room Temperature display
Shows the room temperature.
Louver display
Indicates the action of the swing
louver. Does not appear if the
louver is stationary.
(Power On indicator)
Indicates that the power is on.
ON
OFF
FUNCTION
FILTER
WEEKLY
SIMPLE
AUTO OFF
“Sensor” indication
Displayed when the remote controller
sensor is used.
“Locked” indicator
Indicates that remote controller buttons have been locked.
“Clean The Filter” indicator
Comes on when it is time to clean the
filter.
Timer indicators
The indicator comes on if the corresponding timer is set.
Fan Speed indicator
Shows the selected fan speed.
Ventilation indicator
Appears when the unit is running in
Ventilation mode.
Caution
Only the Power on indicator lights when the unit is stopped and power supplied to the unit.
If you press a button for a feature that is not installed at the indoor unit, the remote controller will display the “Not Available”
message.
If you are using the remote controller to drive multiple indoor units, this message will appear only if he feature is not
present at the parent unit.
When power is turned ON for the first time, it is normal that “PLEASE WAIT” is displayed on the room temperature indication
(For max. 2minutes). Please wait until this “PLEASE WAIT” indication disappear then start the operation.
8
5
SPECIFICATIONS
Service Ref.
Mode
Power supply(phase, cycle, voltage)
Input
Running current
Starting current
External finish
Heat exchanger
Fan Fan(drive) x No.
Fan motor output
External static pressure
INDOOR UNIT
Operation control & Thermostat
Noise level(Low-Medium2-Medium1-High)
Unit drain pipe I.D.
Dimensions
Weight
Service Ref.
Mode
Power supply(phase, cycle, voltage)
Input
Running current
Starting current
External finish
Heat exchanger
Fan Fan(drive) x No.
Fan motor output
External static pressure
INDOOR UNIT
Operation control & Thermostat
Noise level(Low-Medium2-Medium1-High)
Unit drain pipe I.D.
Dimensions
Weight
Service Ref.
Mode
Power supply(phase, cycle, voltage)
Input
Running current
Starting current
External finish
Heat exchanger
Fan Fan(drive) x No.
Fan motor output
External static pressure
INDOOR UNIT
Operation control & Thermostat
Noise level(Low-Medium2-Medium1-High)
Unit drain pipe I.D.
Dimensions
Weight
Service Ref.
Mode
Power supply(phase, cycle, voltage)
Input
Running current
Starting current
External finish
Heat exchanger
Fan Fan(drive) x No.
Fan motor output
External static pressure
Operation control & Thermostat
INDOOR UNIT
Noise level(Low-Medium2-Medium1-High)
Unit drain pipe I.D.
Dimensions
Weight
Airflow(Low-Medium2-Medium1-High)
Airflow(Low-Medium2-Medium1-High)
Airflow(Low-Medium2-Medium1-High)
Airflow(Low-Medium2-Medium1-High)
W
D
H
W
D
H
W
D
H
W
D
H
kW
A
A
kW
*/min(CFM)
Pa(mmAq)
dB
mm(in.)
mm(in.)
mm(in.)
mm(in.)
kg(lbs)
kW
A
A
kW
*/min(CFM)
Pa(mmAq)
dB
mm(in.)
mm(in.)
mm(in.)
mm(in.)
kg(lbs)
kW
A
A
kW
*/min(CFM)
Pa(mmAq)
dB
mm(in.)
mm(in.)
mm(in.)
mm(in.)
kg(lbs)
kW
A
A
kW
*/min(CFM)
Pa(mmAq)
dB
mm(in.)
mm(in.)
mm(in.)
mm(in.)
kg(lbs)
PCA-RP50GA, PCA-RP50GA#1
Cooling
Single phase, 50Hz, 230V
0.09
0.41
1.20
Munsell 0.70Y 8.59/0.97
Plate fin coil
Sirocco fan (direct) x 2
0.054
10-11-12-13(355-390-425-460)
0(direct blow)
Remote controller & built-in
37-38-40-42
26(1)
1,000(39-3/8)
680(26-3/4)
210(8-1/4)
27(60)
PCA-RP50GA2, PCA-RP50GA2#1
Cooling
Single phase, 50Hz, 230V
0.12
0.53
1.27
Munsell 0.70Y 8.59/0.97
Plate fin coil
Sirocco fan (direct) x 3
0.070
14-15-16-18(495-530-565-635)
0(direct blow)
Remote controller & built-in
37-39-41-43
26(1)
1,310(51-9/16)
680(26-3/4)
210(8-1/4)
34(75)
PCA-RP60GA, PCA-RP60GA#1
Cooling
Single phase, 50Hz, 230V
0.12
0.53
1.27
Munsell 0.70Y 8.59/0.97
Plate fin coil
Sirocco fan (direct) x 3
0.070
14-15-16-18(495-530-565-635)
0(direct blow)
Remote controller & built-in
37-39-41-43
26(1)
1,310(51-9/16)
680(26-3/4)
210(8-1/4)
34(75)
PCA-RP71GA, PCA-RP71GA#1
Cooling
Single phase, 50Hz, 230V
0.12
0.53
1.27
Munsell 0.70Y 8.59/0.97
Plate fin coil
Sirocco fan (direct) x 3
0.070
14-15-16-18(495-530-565-635)
0(direct blow)
Remote controller & built-in
37-39-41-43
26(1)
1,310(51-9/16)
680(26-3/4)
210(8-1/4)
34(75)
Heating
0.09
0.41
1.20
Heating
0.12
0.53
1.27
Heating
0.12
0.53
1.27
Heating
0.12
0.53
1.27
99
Service Ref.
Mode
Power supply(phase, cycle, voltage)
Input
Running current
Starting current
External finish
Heat exchanger
Fan Fan(drive) x No.
Fan motor output
External static pressure
INDOOR UNIT
Operation control & Thermostat
Noise level(Low-Medium2-Medium1-High)
Unit drain pipe I.D.
Dimensions
Weight
Airflow(Low-Medium2-Medium1-High)
W
D
H
kW
A
A
kW
*/min(CFM)
Pa(mmAq)
dB
mm(in.)
mm(in.)
mm(in.)
mm(in.)
kg(lbs)
PCA-RP100GA, PCA-RP100GA#1
Cooling
Single phase, 50Hz, 230V
0.15
0.69
1.48
Munsell 0.70Y 8.59/0.97
Plate fin coil
Sirocco fan (direct) x 3
0.090
20-21-23-25(705-740-810-885)
0(direct blow)
Remote controller & built-in
40-41-43-45
26(1)
1,310(51-9/16)
680(26-3/4)
270(10-5/8)
37(82)
Heating
0.15
0.69
1.48
Service Ref.
Mode
Power supply(phase, cycle, voltage)
Input
Running current
Starting current
External finish
Heat exchanger
Fan Fan(drive) x No.
Fan motor output
Airflow(Low-Medium2-Medium1-High)
External static pressure
INDOOR UNIT
Operation control & Thermostat
Noise level(Low-Medium2-Medium1-High)
Unit drain pipe I.D.
Dimensions
W
D
H
Weight
Service Ref.
Mode
Power supply(phase, cycle, voltage)
Input
Running current
Starting current
External finish
Heat exchanger
Fan Fan(drive) x No.
Fan motor output
External static pressure
INDOOR UNIT
Operation control & Thermostat
Noise level(Low-Medium2-Medium1-High)
Unit drain pipe I.D.
Dimensions
Weight
Airflow(Low-Medium2-Medium1-High)
W
D
H
kW
A
A
kW
*/min(CFM)
Pa(mmAq)
dB
mm(in.)
mm(in.)
mm(in.)
mm(in.)
kg(lbs)
kW
A
A
kW
*/min(CFM)
Pa(mmAq)
dB
mm(in.)
mm(in.)
mm(in.)
mm(in.)
kg(lbs)
PCA-RP125GA, PCA-RP125GA#1
Cooling
Single phase, 50Hz, 230V
0.22
1.01
2.20
Munsell 0.70Y 8.59/0.97
Plate fin coil
Sirocco fan (direct) x 4
0.150
27-30-32-34(955-1,060-1,130-1,200)
0(direct blow)
Remote controller & built-in
41-43-45-46
26(1)
1,620(63-3/4)
680(26-3/4)
270(10-5/8)
43(95)
PCA-RP140GA, PCA-RP140GA#1
Cooling
Single phase, 50Hz, 230V
0.22
1.01
2.20
Munsell 0.70Y 8.59/0.97
Plate fin coil
Sirocco fan (direct) x 4
0.150
27-30-32-34(955-1,060-1,130-1,200)
0(direct blow)
Remote controller & built-in
42-44-46-48
26(1)
1,620(63-3/4)
680(26-3/4)
270(10-5/8)
45(99)
Heating
0.22
1.01
2.20
Heating
0.22
1.01
2.20
10
Service Ref.
Mode
Power supply(phase, cycle, voltage)
Input +1
Running current +1
Starting current +1
External finish
Heat exchanger
Fan Fan(drive) x No.
Fan motor output
External static pressure
INDOOR UNIT
Booster heater +1
Operation control & Thermostat
Noise level(Low-Medium2-Medium1-High)
Unit drain pipe I.D.
Dimensions
Weight
Airflow(Low-Medium2-Medium1-High)
W
D
H
kW
A
A
kW
*/min(CFM)
Pa(mmAq)
kW
dB
mm(in.)
mm(in.)
mm(in.)
mm(in.)
kg(lbs)
Cooling
0.09
0.41
1.20
PCH-P50GAH
Heating
Single phase, 50Hz, 230V
0.09<1.29>
0.41<5.61>
1.20<5.61>
Munsell 0.70Y 8.59/0.97
Plate fin coil
Sirocco fan (direct) x 2
0.054
10-11-12-13(355-390-425-460)
0(direct blow)
<1.29>
Remote controller & built-in
37-38-40-42
26(1)
1,000(39-3/8)
680(26-3/4)
210(8-1/4)
28.5(63)
Service Ref.
Mode
Power supply(phase, cycle, voltage)
Input +1
Running current +1
Starting current +1
External finish
Heat exchanger
Fan Fan(drive) x No.
Fan motor output
External static pressure
INDOOR UNIT
Booster heater +1
Operation control & Thermostat
Noise level(Low-Medium2-Medium1-High)
Unit drain pipe I.D.
Dimensions
Weight
Service Ref.
Mode
Power supply(phase, cycle, voltage)
Input +1
Running current +1
Starting current +1
External finish
Heat exchanger
Fan Fan(drive) x No.
Fan motor output
External static pressure
INDOOR UNIT
Booster heater +1
Operation control & Thermostat
Noise level(Low-Medium2-Medium1-High)
Unit drain pipe I.D.
Dimensions
Weight
+1 : < > Shows the only booster heater rating.
Airflow(Low-Medium2-Medium1-High)
W
D
H
Airflow(Low-Medium2-Medium1-High)
W
D
H
kW
A
A
kW
*/min(CFM)
Pa(mmAq)
kW
dB
mm(in.)
mm(in.)
mm(in.)
mm(in.)
kg(lbs)
kW
A
A
kW
*/min(CFM)
Pa(mmAq)
kW
dB
mm(in.)
mm(in.)
mm(in.)
mm(in.)
kg(lbs)
Cooling
0.12
0.53
1.27
Cooling
0.12
0.53
1.27
PCH-P60GAH
Heating
Single phase, 50Hz, 230V
0.12<1.93>
0.53<8.39>
1.27<8.39>
Munsell 0.70Y 8.59/0.97
Plate fin coil
Sirocco fan (direct) x 3
0.070
14-15-16-18(495-530-565-635)
0(direct blow)
<1.93>
Remote controller & built-in
37-39-41-43
26(1)
1,310(51-9/16)
680(26-3/4)
210(8-1/4)
36(79)
PCH-P71GAH
Heating
Single phase, 50Hz, 230V
0.12<1.93>
0.53<8.39>
1.27<8.39>
Munsell 0.70Y 8.59/0.97
Plate fin coil
Sirocco fan (direct) x 3
0.070
14-15-16-18(495-530-565-635)
0(direct blow)
<1.93>
Remote controller & built-in
37-39-41-43
26(1)
1,310(51-9/16)
680(26-3/4)
210(8-1/4)
36(79)
11
Service Ref.
Mode
Power supply(phase, cycle, voltage)
Input +1
Running current +1
Starting current +1
External finish
Heat exchanger
Fan Fan(drive) x No.
Fan motor output
External static pressure
INDOOR UNIT
Booster heater +1
Operation control & Thermostat
Noise level(Low-Medium2-Medium1-High)
Unit drain pipe I.D.
Dimensions
Weight
Airflow(Low-Medium2-Medium1-High)
W
D
H
kW
A
A
kW
*/min(CFM)
Pa(mmAq)
kW
dB
mm(in.)
mm(in.)
mm(in.)
mm(in.)
kg(lbs)
Cooling
0.15
0.69
1.48
PCH-P100GAH
Heating
Single phase, 50Hz, 230V
0.15<2.48>
0.69<10.78>
1.48<10.78>
Munsell 0.70Y 8.59/0.97
Plate fin coil
Sirocco fan (direct) x 3
0.090
20-21-23-25(705-740-810-885)
0(direct blow)
<2.48>
Remote controller & built-in
40-41-43-45
26(1)
1,310(51-9/16)
680(26-3/4)
270(10-5/8)
39.5(87)
Service Ref.
Mode
Power supply(phase, cycle, voltage)
Input +1
Running current +1
Starting current +1
External finish
Heat exchanger
Fan Fan(drive) x No.
Fan motor output
External static pressure
INDOOR UNIT
Booster heater +1
Operation control & Thermostat
Noise level(Low-Medium2-Medium1-High)
Unit drain pipe I.D.
Dimensions
Weight
Service Ref.
Mode
Power supply(phase, cycle, voltage)
Input +1
Running current +1
Starting current +1
External finish
Heat exchanger
Fan Fan(drive) x No.
Fan motor output
External static pressure
INDOOR UNIT
Booster heater +1
Operation control & Thermostat
Noise level(Low-Medium2-Medium1-High)
Unit drain pipe I.D.
Dimensions
Weight
+1 : < > Shows the only booster heater rating.
Airflow(Low-Medium2-Medium1-High)
W
D
H
Airflow(Low-Medium2-Medium1-High)
W
D
H
kW
A
A
kW
*/min(CFM)
Pa(mmAq)
kW
dB
mm(in.)
mm(in.)
mm(in.)
mm(in.)
kg(lbs)
kW
A
A
kW
*/min(CFM)
Pa(mmAq)
kW
dB
mm(in.)
mm(in.)
mm(in.)
mm(in.)
kg(lbs)
Cooling
PCH-P125GAH
Single phase, 50Hz, 230V
0.22
1.01
2.20
Munsell 0.70Y 8.59/0.97
Plate fin coil
Sirocco fan (direct) x 4
0.150
27-30-32-34(955-1,060-1,130-1,200)
0(direct blow)
<2.76>
Remote controller & built-in
41-43-45-46
26(1)
1,620(63-3/4)
680(26-3/4)
270(10-5/8)
46(101)
PCH-P140GAH
Cooling
Single phase, 50Hz, 230V
0.22
1.01
2.20
Munsell 0.70Y 8.59/0.97
Plate fin coil
Sirocco fan (direct) x 4
0.150
27-30-32-34(955-1,060-1,130-1,200)
0(direct blow)
<2.76>
Remote controller & built-in
42-44-46-48
26(1)
1,620(63-3/4)
680(26-3/4)
270(10-5/8)
48(106)
Heating
0.22<2.76>
1.01<12.00>
2.20<12.00>
Heating
0.22<2.76>
1.01<12.00>
2.20<12.00>
12
NOISE CRITERION CURVES6
PCA-RP50GA
PCA-RP50GA#1
PCH-P50GAH
90
80
70
60
50
40
30
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)
When installing optional
drain-up machine disconnect
the CN31 jumper connector
and replace it with the
drain sensor (DS).
When installing drain-up
machine (Optional part).
DS
PCH-P50~P140GAH
models only
1. When work to supply power separately to
Indoor and Outdoor unit was applied, refer to Fig 1.
2. For power supply system of this unit,
refer to the caution label located near this diagram.
H1
FS1
SYMBOLNAME
MF
MV
DP
DS
TB2
TB4
TB5,TB6
TH1
TH2
TH5
R.B
P.B
CNDK
(RED)
1
DC13.1V
2
3
WHT
RED
POWER
CND
(ORN)
D.SENSOR
CN31
(
)
WHT
FS2
WHT
YLW
ZNR
INTAKE
CN20
(
RED
1 21 2 3
[Servicing]
Fasten terminal of the terminal board "TB4"equips lock system.
To remove the fastened terminal, pull it while pressing the protruding
portion (locking lever) of the terminal. The fastened terminal protruding
portion should face upward.
1
2
FAN MOTOR
VANE MOTOR
DRAIN-UP MACHINE (OPTION)
DRAIN SENSOR (OPTION)
TERMINAL BLOCK (HEATER) PCH-P.GAH
models only or option for PCA RP.GA(2) models.
TERMINAL BLOCK(INDOOR/OUTDOOR CONNECTING LINE)
TERMINAL BLOCK(REMOTE CONTROLLER
TRANSMISSION LINE )
ROOM TEMP.THERMIST OR
(0/15k, 25/5.4k DETECT)
PIPE TEMP.THERMIST OR/LIQUID
(0/15k, 25/5.4k DETECT)
COND./EVA.TEMP.THERMISTOR
(0/15k, 25/5.4k DETECT)
WIRED REMOTE CONTROLLER BOARD
Refrigerant flow in cooling
Refrigerant flow in heating
Refrigerant LIQUID pipe connection
(Flare)
Strainer
#50
Unit : mm
20
TROUBLESHOOTING10
10-1. TROUBLESHOOTING
<Error code display by self-diagnosis and actions to be taken for service (summary)>
Present and past error codes are logged and displayed on the wired remote controller or controller board of outdoor unit.
Actions to be taken for service and the trouble reoccurrence at field are summarized in the table below. Check the contents
below before investigating details.
Unit conditions at service
The trouble is reoccurring.
The trouble is not reoccurring.
Error code
Displayed
Not displayed
Logged
Not logged
Actions to be taken for service (summary)
Judge what is wrong and take a corrective action
according to “SELF-DIAGNOSIS ACTION TABLE” (10-2).
Conduct troubleshooting and ascertain the cause of the
trouble according to “TROUBLESHOOTING
BY INFERIOR PHENOMENA ” (10-3).
Consider the temporary defects such as the work of
protection devices in the refrigerant circuit including
compressor, poor connection of wiring, noise and etc.
Re-check the symptom, and check the installation
environment, refrigerant amount, weather when the
trouble occurred, and wiring related.
Reset error code logs and restart the unit after finishing
service.
There is no abnormality in electrical components,
controller boards, and remote controller.
Recheck the abnormal symptom.
Identify the cause of the trouble and take a corrective
action according to “TROUBLESHOOTING
BY INFERIOR PHENOMENA ” (10-3).
Continue to operate unit for the time being if the cause
is not ascertained.
There is no abnormality in electrical components,
controller boards, remote controller etc.
21
10-2. SELF-DIAGNOSIS ACTION TABLE
Error Code
P1
P2
Abnormal point and detection method
Room temperature thermistor (TH1)
1 The unit is in 3-minute resume
prevention mode if short/open of
thermistor is detected. Abnormal if the
unit does not reset normally after 3 minutes. (The unit returns to normal opera-
tion, if it has been reset normally.)
2 Constantly detected during cooling,
drying, and heating operation.
Short: -90: or more
Open: -40: or less
Pipe temperature thermistor/Liquid
(TH2)
1 The unit is in 3-minute resume
prevention mode if short/open of
thermistor is detected. Abnormal if the
unit does not reset normally after 3 min-
utes. (The unit returns to normal opera-
tion, if it has been reset normally.)
2 Constantly detected during cooling,
drying, and heating (except defrosting)
operation
Short: 90: or more
Open: -40: or less
1 Defective thermistor
characteristics
2 Contact failure of connector
3 Breaking of wire or contact
failure of thermistor wiring
4 Defective indoor controller
1 Defective thermistor
characteristics
2 Contact failure of connector
3 Breaking of wire or contact
failure of thermistor wiring
4 Defective refrigerant circuit is
5 Defective indoor controller
Note: Refer to the manual of outdoor unit for the details of display
such as F, U, and other E.
Cause
(CN20) on the indoor controller
board (Insert failure)
board
(CN44) on the indoor controller board (Insert failure)
causing thermistor temperature of 90: or more or -40:
or less.
board
Countermeasure
1–3 Check resistance value of thermistor.
0: 15.0k"
10: 9.6k"
20: 6.3k"
30: 4.3k"
40: 3.0k"
If you put force on (draw or bend) the lead wire
with measuring resistance value of thermistor, breaking of wire or contact failure can be
detected.
2 Check contact failure of connector (CN20)
on the indoor controller board. Refer to 10-6.
Turn the power on again and check restart
after inserting connector again.
4 Check room temperature display on remote
controller.
Replace indoor controller board if there is
abnormal difference with actual room
temperature.
Turn the power off, and on again to operate
after check.
1–3 Check resistance value of thermistor.
For characteristics, refer to (P1) above.
2 Check contact failure of connector (CN44)
on the indoor controller board. Refer to 10-6.
Turn the power on and check restart after
inserting connector again.
4 Check pipe <liquid> temperature with remote
controller in test run mode. If pipe <liquid>
temperature is extremely low (in cooling
mode) or high (in heating mode), refrigerant
circuit may have defective.
5 Check pipe <liquid> temperature with
remote controller in test run mode. If there is
extremely difference with actual pipe <liquid>
temperature, replace indoor controller board.
P4
P5
Drain sensor (DS)
1 Suspensive abnormality, if short/open
of thermistor is detected for 30 seconds
continuously.Compressor and indoor fan
will be turned off
2 Short/open is detected for 30 seconds
continuously during suspensive
abnormality.
(The unit returns to normal operation,
if it has normally reset.)
3 Detect the following condition.
• During cooling and drying operation.
• In case that pipe <liquid> temperature room temperature <-10deg
(Except defrosting)
• When pipe <liquid> temperature or
room temperature is short/open
temperature.
• During drain pomp operation.
Malfunction of drain pump (DP)
1 Suspensive abnormality, if thermistor
of drain sensor is let heat itself and
temperature rises slightly. Compressor
and indoor fan will be turned off.
2 Drain pomp is abnormal if the condition
above is detected during suspensive
abnormality.
3 Constantly detected during drain pump
operation.
1 Defective thermistor
characteristics
2 Contact failure of connector
(CN31) on the indoor controller
board. (Insert failure).
3 Breaking of wire or contact
failure of drain sensor wiring.
4 Defective indoor controller board.
1 Malfunction of drain pump
2 Defective drain
Clogged drain pump
Clogged drain pipe
Attached drop of water at the
3
drain sensor
• Drops of drain trickles from
lead wire.
• Clogged filter is causing
wave of drain.
4 Defective indoor controller board.
Turn the power off, and on again to operate
after check.
1–3 Check resistance value of thermistor.
......
0:
6.0k"
....
10:
3.9k"
....
20:
2.6k"
....
30:
1.8k"
....
40:
1.3k"
2 Check contact failure of connector (CN31)
on the indoor controller board. Refer to 10-6.
Turn the power on again and check restart
after inserting connector again.
4 Replace indoor controller board if drain
pump operates with the line of drain sensor
connector CN31-1 and 2 is short-circuited,
and abnormality reappears.
Turn the power off, and on again to operate
after check.
1 Check if drain-up machine works.
2 Check drain function.
3 Check the setting of lead wire of drain sensor
and check clogs of the filter.
4 Replace indoor controller board if drain
pump operates with the line of drain sensor
connector CN31-1 and 2 is short-circuited
and abnormality reappears.
Refer to 10-6.
Turn the power off, and on again to operate
after check.
22
Error Code
Abnormal point and detection method
Freezing/overheating protection is working
1 Freezing protection (Cooling mode)
The unit is in 6-minute resume prevention mode if pipe <liquid or condenser/
evaporator> temperature stays under
-15: for 3 minutes, 3 minutes after the
compressor started. Abnormal if it stays
under -15: for 3 minutes again within
16 minutes after 6-minute resume prevention mode.
Cause
(Cooling or drying mode)
1 Clogged filter (reduced airflow)
2 Short cycle of air path
3 Low-load (low temperature)
operation out of the tolerance
range
4 Defective indoor fan motor
• Fan motor is defective.
• Indoor controller board is defective.
Countermeasure
(Cooling or drying mode)
1 Check clogs of the filter.
2 Remove shields.
4 Refer to 10-6.
P6
P8
2 Overheating protection (Heating mode)
The units is in 6 minute resume
prevention mode if pipe <condenser /
evaporator> temperature is detected as
over 70: after the compressor started.
Abnormal if the temperature of over
70: is detected again within 30 minutes
after 6 minute resume prevention mode.
Pipe temperature
<Cooling mode>
Detected as abnormal when the pipe temperature is not in the cooling range 3 minutes after compressor start and 6 minutes
after the liquid or condenser/evaporator
pipe is out of cooling range.
Note 1) It takes at least 9 minutes to
detect.
Note 2) Abnormality P8 is not detected in
drying mode.
Cooling range : -3 °C ] (TH-TH1)
TH: Lower temperature between: liquid
pipe temperature (TH2) and condenser/evaporator temperature (TH5)
TH1: Intake temperature
<Heating mode>
When 10 seconds have passed after the
compressor starts operation and the hot
adjustment mode has finished, the unit is
detected as abnormal when condenser/
evaporator pipe temperature is not in heating range within 20 minutes.
5 Defective outdoor fan control
6 Overcharge of refrigerant
7 Defective refrigerant circuit
(clogs)
(Heating mode)
1 Clogged filter (reduced airflow)
2 Short cycle of air path
3 Over-load (high temperature)
operation out of the tolerance
range
4 Defective indoor fan motor
• Fan motor is defective.
• Indoor controller board is defective.
5 Defective outdoor fan control
6 Overcharge of refrigerant
7 Defective refrigerant circuit
(clogs)
8 Bypass circuit of outdoor unit
is defective.
1 Slight temperature difference
between indoor room
temperature and pipe <liquid
or condenser / evaporator>
temperature thermistor
• Shortage of refrigerant
• Disconnected holder of pipe
<liquid or condenser /
evaporator> thermistor
• Defective refrigerant circuit
2 Converse connection of
extension pipe (on plural units
connection)
3 Converse wiring of indoor/
outdoor unit connecting wire
(on plural units connection)
4 Defective detection of indoor
room temperature and pipe
<condenser / evaporator>
temperature thermistor
5 Stop valve is not opened
completely.
5 Check outdoor fan motor.
67 Check operating condition of refrigerant
circuit.
(Heating mode)
1 Check clogs of the filter.
2 Remove shields.
4 Refer to 10-6.
5 Check outdoor fan motor.
6~8Check operating condition of refrigerant
circuit.
1~4 Check pipe <liquid or condenser / evapo-
rator> temperature with room temperature display on remote controller and
outdoor controller circuit board.
Pipe <liquid or condenser / evaporator>
temperature display is indicated by setting SW2 of outdoor controller circuit
board as follows.
Conduct temperature check with outdoor
controller circuit board after connecting
(
‘A-Control Service Tool(PAC-SK52ST)’.
23Check converse connection of extension
pipe or converse wiring of indoor/outdoor
unit connecting wire.
)
Note 3) It takes at least 27 minutes to
detect abnormality.
Note 4) It excludes the period of defrosting.
(Detection restarts when defrosting
mode is over.)
Heating range : 3 °C [ (TH5-TH1)
23
Error Code
P9
Abnormal point and detection method
Pipe temperature thermistor /
Condenser-Evaporator (TH5)
1 The unit is in 3-minute resume protec-
tion mode if short/open of thermistor is
detected. Abnormal if the unit does not
get back to normal within 3 minutes. (The
unit returns to normal operation, if it has
been reset normally.)
2 Constantly detected during cooling,
drying, and heating operation (except
defrosting)
Short: 90: or more
Open: -40: or less
Cause
1 Defective thermistor
characteristics
2 Contact failure of connector
(CN44) on the indoor controller
board (Insert failure)
3 Breaking of wire or contact
failure of thermistor wiring
4 Temperature of thermistor is
90: or more or -40: or less
caused by defective refrigerant
circuit.
5 Defective indoor controller
board
Countermeasure
1–3 Check resistance value of thermistor.
For characteristics, refer to (P1) above.
2 Check contact failure of connector (CN44)
on the indoor controller board.
Refer to 10-7.
Turn the power on and check restart after
inserting connector again.
4 Operate in test run mode and check pipe
<condenser / evaporator> temperature with
outdoor controller circuit board. If pipe
<condenser / evaporator> temperature is
extremely low (in cooling mode) or high (in
heating mode), refrigerant circuit may have
defect.
5 Operate in test run mode and check pipe
<condenser / evaporator> temperature with
outdoor control circuit board. If there is
extreme difference with actual pipe
<condenser / evaporator> temperature,
replace indoor controller board.
There is no abnormality if none of above
comes within the unit.
Turn the power off and on again to operate.
In case of checking pipe temperature
with outdoor controller circuit board,
be sure to connect A-control service
30 continuous times. (Error code: E3)
1 Abnormal if indoor controller board could
not find blank of transmission path.
(Error code: E5)
2 Indoor controller board receives trans-
mitted data at the same time and com-
pares the received and transmitted data.
Abnormal if these data are judged to
be different 30 continuous times. (Error
code: E5)
1 Contact failure at transmission
wire of remote controller
2 All remote controllers are set
as “sub” remote controller.
In this case, E0 is displayed
on remote controller, and E4
is displayed at LED (LED1,
LED2) on the outdoor controller
circuit board.
3 Miswiring of remote controller
4 Defective transmitting receiving
circuit of remote controller
5 Defective transmitting receiving
circuit of indoor controller board
of refrigerant addresses “0”.
6 Noise has entered into the
transmission wire of remote
controller.
1 2 remote controllers are set as
“main.”
(In case of 2 remote con trollers)
2 Remote controller is connected
with 2 indoor units or more.
3 Repetition of refrigerant
address
4 Defective transmitting receiving
circuit of remote controller
5 Defective transmitting receiving
circuit of indoor controller board
6 Noise has entered into trans-
mission wire of remote control-
ler.
1 Check disconnection or looseness of indoor
unit or transmission wire of remote controller.
2 Set one of the remote controllers “main”
if there is no problem with the action above.
3 Check wiring of remote controller.
• Total wiring length: max. 500m
(Do not use cable x 3 or more.)
• The number of connecting indoor units:
max. 16 units
• The number of connecting remote controller: max. 2 units
When it is not the above-mentioned problem of
1~3
4 Diagnose remote controllers.
a) When “RC OK” is displayed,
Remote controllers have no problem.
Turn the power off, and on again to check.
If abnormality generates again, replace
indoor controller board.
b) When “RC NG” is displayed,
Replace remote controller.
c)When “RC E3” or “ERC 00-66” is dis-
played, noise may be causing abnormality.
* If the unit is not normal after replacing
indoor controller board in group control,
indoor controller board of address “0” may
be abnormal.
1 Set a remote controller to main, and the
other to sub.
2 Remote controller is connected with only one
indoor unit.
3 The address changes to a separate setting.
4~6 Diagnose remote controller.
a) When “RC OK” is displayed, remote con-
trollers have no problem.
Turn the power off,and on again to check.
When becoming abnormal again, replace
indoor controller board.
b)When “RC NG” is displayed, replace
remote controller.
c)When “RC E3” or “ERC 00-66” is dis-
played, noise may be causing abnormal-
ity.
24
Error Code
E6
Abnornal point and detection method
Indoor/outdoor unit communication
error (Signal receiving error)
1 Abnormal if indoor controller board
cannot receive any signal normally for 6
minutes after turning the power on.
2 Abnormal if indoor controller board
cannot receive any signal normally for 3
minutes.
3 Consider the unit abnormal under the fol-
lowing condition: When 2 or more indoor
units are connected to an
outdoor unit, indoor controller board
cannot receive a signal for 3 minutes
from outdoor controller circuit board, a
signal which allows outdoor controller
circuit board to transmit signals.
Cause
1 Contact failure, short circuit or,
miswiring (converse wiring) of
indoor/outdoor unit connecting
wire
2 Defective transmitting receiving
circuit of indoor controller board
3 Defective transmitting receiving
circuit of indoor controller board
4 Noise has entered into indoor/
outdoor unit connecting wire.
Countermeasure
* Check LED display on the outdoor control
circuit board. (Connect A-control service
tool, PAC-SK52ST.)
Refer to outdoor unit service manual.
1 Check disconnection or looseness of indoor/
outdoor unit connecting wire of indoor unit or
outdoor unit.
Check all the units in case of twin triple
indoor unit system.
2-4 Turn the power off, and on again to check.
If abnormality generates again, replace
indoor controller board or outdoor
controller circuit board.
* Other indoor controller board may have
defect in case of twin triple indoor unit
system.
E7
Fb
E1
E2
PA
Indoor/outdoor unit communication
error (Transmitting error)
Abnormal if “1” receiving is detected 30
times continuously though indoor controller
board has transmitted “0”.
Indoor controller board
Abnormal if data cannot be read normally
from the nonvolatile memory of the indoor
controller board.
Remote controller control board
1 Abnormal if data cannot be read nor-
mally from the nonvolatile memory of the
remote controller control board.
(Error code: E1)
or
2 Abnormal if the clock function of remote
controller cannot be operated normally.
(Error code: E2)
Forced compressor stop
(due to water leakage abnormality)
1 When the intake temperature subtracted
with liquid pipe temperature is less than
-10:, drain sensor is detected whether
it is soaked in the water or not at the interval
of 90 seconds. (Drain pump will start operating
when the drain sensor is detected to be
soaked in the water.)
2 The unit has a water leakage abnormality
when the following conditions, a and b, are
satisfied while the above-mentioned detection
is performed.
a) The drain sensor is detected to be
soaked in the water 10 times in a row.
b) The intake temperature subtracted with
liquid pipe temperature is detected to be
less than -10: for a total of 30 minutes.
(When the drain sensor is detected to
be NOT soaked in the water, the detection
record of a and b will be cleared.)
3 The drain sensor detection is performed
in operations other than cooling. (When
the unit stops operating, during heating
or fan operation, when the unit stops
because of some abnormality)
*Once the water leakage abnormality is
detected, abnormality state will not be
released until the main power is reset.
· Drain pipe clogging
3 Open circuit of drain sensor
side heater
4 Contact failure of drain sensor
connector
5 Dew condensation on drain
sensor
· Drain water descends along
lead wire.
· Drain water waving due to filter
clogging.
6 Extension piping connection
difference at twin, triple,
quadruple system.
7 Mis-wiring of indoor/ outdoor
connecting at twin, triple,
quadruple system.
8 Room temperature thermistor /
liquid pipe temperature thermis tor detection is defective.
1-3 Turn the power off, and on again to check.
If abnormality generates again, replace
indoor controller board.
1 Replace indoor controller board.
1 Check the drain pump.
2 Please confirm whether water can be
drained.
3 Confirm the resistance of the drain sensor.
4 Check the connector contact failure.
5 Check the drain sensor leadwire mounted.
Check the filter clogging
6 Check the piping connection.
7 Check the indoor/ outdoor connecting wires.
8 Check the room temperature display of
remote controller.
Check the indoor liquid pipe temperature
display of outdoor controller board.
25
10-3. TROUBLESHOOTING BY INFERIOR PHENOMENA
Note: Refer to the manual of outdoor unit for the detail of remote
controller.
Phenomena
(1)LED2 on indoor controller board
is off.
• When LED1 on indoor controller board is also off.
1 Power supply of rated voltage is not supplied to out-
door unit.
2 Defective outdoor controller circuit board.
3 Power supply of 220~240V is not supplied to indoor
unit.
4 Defective indoor power board.
5 Defective indoor controller board.
(For the separate indoor/outdoor unit power sup-
ply system)
1 Power supply of 220~240V AC is not supplied to
indoor unit.
2 The connectors of the optional replacement kit are
not used.
3 Defective indoor controller board.
4 Defective indoor power board.
• When LED1 on indoor controller board is lit.
1 Mis-setting of refrigerant address for outdoor unit
(There is no unit corresponding to refrigerant
address “0”.)
Cause
Countermeasure
1 Check the voltage of outdoor power
supply terminal block (L, N) or (L3, N).
• When AC 220~240V is not detected.
Check the power wiring to outdoor unit
and the breaker.
• When AC 220~240V is detected.
—Check 2 (below).2 Check the voltage between outdoor
terminal block S1 and S2.
• When AC 220~240V is not detected.
Check the fuse on outdoor controller cir-
cuit board.
Check the wiring connection.
• When AC 220~240V is detected.
—Check 3 (below).3 Check the voltage between indoor terminal
block S1 and S2.
• When AC 220~240V is not detected.
Check indoor/outdoor unit connecting
wire for mis-wiring.
• When AC 220~240V is detected.
—Check 4 (below).
4 Check voltage output from CN2S on indoor
power board (DC13.1V). Refer to 10-6-1.
• When no voltage is output.
Check the wiring connection.
• When output voltage is between DC12.5V
and DC13.7V.
—Check 5 (below).
5 Check the wiring connection between indoor
controller board and indoor power board.
Check the fuse on indoor controller board.
1 Check the voltage of indoor power supply
terminal block (L,N).
• When AC220~240V is not detected.
Check the power supply wiring.
• When AC220~240V is detected.
-Check 2 (below).
2 Check that there is no problem in the meth-
od of connecting the connectors.
• When there are problems in the method of
connecting the connectors.
Connect the connector correctly referring
to installation manual of an optional kit.
• When there is no problem in the method
of connecting the connectors.
-Check 3 (below).
3 Check voltage output from CNDK on indoor
controller board.
• When AC220~240V is not detected.
Check the fuse on indoor controller board.
Check the wiring connection between
indoor power supply terminal block and
CND on indoor controller board.
• When AC220~240V is detected.
-Check 4 (below).
4 Check voltage output from CN2S on indoor
power board.
• When no voltage output.
Check the wiring connection between
CNDK on indoor controller board and
CNSK on indoor power board.
If no problem are found,indoor power
board is defective.
• When DC12.5~13.7V is detected.
Check the wiring connection between
CN2S on indoor power board and
CN2D on indoor power board.
If no problem are found,indoor controller
1 Reconfirm the setting of refrigerant address
for outdoor unit
Set the refrigerant address to “0”.
(For grouping control system under
which 2 or more outdoor units are
connected, set one of the units to “0”.)
Set refrigerant address using SW1 (3-6)
on outdoor controller circuit board.
26
Phenomena
(2)LED2 on indoor controller board
is blinking.
(3)Upward/downward vane
performance failure
(4)Receiver for wireless remote
controller
Note: Refer to the manual of outdoor unit for the detail of remote
controller.
Cause
• When LED1 on indoor controller board is also blinking.
Connection failure of indoor/outdoor unit connecting
wire
• When LED1 is lit.
1 Mis-wiring of remote controller wires
Under twin triple indoor unit system, 2 or more indoor
units are wired together.
2 Refrigerant address for outdoor unit is wrong or not
set.
Under grouping control system, there are some units
whose refrigerant address is 0.
3 Short-cut of remote controller wires
4 Defective remote controller
1 The vane is not downward during defrosting and heat
preparation and when the thermostat is OFF in HEAT
mode. (Working of COOL protection function)
2 Vane motor does not rotate.
• Defective vane motor
• Breaking of wire or connection failure of connector
• Up/down vane setting is “No vanes”.
3 Upward/downward vane does not work.
• The vane is set to fixed position.
1 Weak batteries of wireless remote controller.
2 Contact failure of connector (CNB) on wireless
remote controller board.
(Insert failure)
3 Contact failure of connector (CN90) on indoor con-
troller board.(Insert failure)
4 Contact failure of connector between wireless remote
controller board and indoor controller board.
Countermeasure
Check indoor/outdoor unit connecting wire
for connection failure.
1 Check the connection of remote con troller wires in case of twin triple indoor
unit system. When 2 or more indoor units
are wired in one refrigerant system,
connect remote controller wires to one of
those units.
2 Check the setting of refrigerant address
in case of grouping control system.
If there are some units whose refrigerant
addresses are 0 in one group, set one of
the units to 0 using SW1 (3-6) on outdoor
controller circuit board.
34 Remove remote controller wires and
check LED2 on indoor controller board.
• When LED2 is blinking, check the shortcut of remote controller wires.
• When LED2 is lit, connect remote
controller wires again and:
if LED2 is blinking, remote controller
is defective; if LED2 is lit, connection
failure of remote controller terminal
block etc. has returned to normal.
1 Normal operation (The vane is set to
horizontal regardless of remote control.)
2 Check 2 (left).
• Check the vane motor. (Refer to “How
to check the parts”.)
• Check for breaking of wire or connection failure of connector.
• Check “Up/down vane setting”. (Unit
function selection by remote controller).
3 Normal operation (Each connector on
vane motor side is disconnected.)
1 Replace batteries of wireless remote con-
troller.
2~4
Check contact failure of each connector. If no problems are found of connector,
replace indoor controller board.
When the same trouble occurs even if
indoor controller board is replaced,
replace wireless remote controller
board.
27
10-4. When wired remote controller or indoor unit micro computer troubles
1. If there is not any other wrong when trouble occurs, emergency operation starts as the indoor controller board switch (SWE)
is set to ON.
During the emergency operation the indoor unit is as follows;
(1) Indoor fan high speed operation (2) Drain-up machine operation(Option)
2. When emergency operating for COOL or HEAT, setting of the switch (SWE) in the indoor controller board and outdoor unit
emergency operation are necessary.
3. Check items and notices as the emergency operation
(1) Emergency operation cannot be used as follows;
• When the outdoor unit is something wrong.
• When the indoor fan is something wrong.
• When drain over flow protected operation is detected during self-diagnosis. (Error code : P5)
(2) Emergency operation will be serial operation by the power supply ON/OFF.
ON/OFF or temperature, etc. adjustment is not operated by the remote controller.
(3) Do not operate for a long time as cold air is blown when the outdoor unit starts defrosting operation during heat emer-
gency operation.
(4) Cool emergency operation must be within 10 hours at most. It may cause heat exchanger frosting in the indoor unit.
(5) After completing the emergency operation, return the switch setting, etc. in former state.
(6) Since vane does not work at emergency operation, position the vane manually and slowly.
CN22
Connect to the terminal
block(TB5)
(Remote controller connecting
wire)
(10.4~14.6V DC)
CNDK
Connect to the indoor
power board (CNSK)
(220~240V AC)
FUSE
(6.3 A 250 V)
CND
Power supply input
(220~240V AC)
CNP
Drain-pump output
(DP)
(220~240V AC)
CN20
Room temperature
thermistor (TH1)
CN21
Pipe temperature
thermistor/Liquid (TH2)
CN29
Condenser/evaporator
temperature thermistor (TH5)
CN31
Drain sensor (DS)
CN90
Connect to the wireless
remote controller board
(CNB)
CN6V
Vane motor output
(MV)
CN41
Connector (HA terminal-A)
CN51
Centrally control
SWE
Emergency operation
FAN
Fan motor output
Jumper wire J41, J42
Pair number setting with
wireless remote controller
31
SW2
Capacity setting
CN24
Heater output
(12V DC)
CN2L
Connector
(LOSSNAY)
SW1
Model setting
10-7. FUNCTIONS OF DIP SWITCH AND JUMPER WIRE
Each function is controlled by the dip switch and the jumper wire on control p.c. board.
SW1 and SW2 are equipped only for service parts.
Model setting and capacity setting are memorized in the nonvolatile memory of the control p.c. board of
the unit.
(Marks in the table below) Jumper wire ( : Short : Open)
Jumper wire
SW1
SW2
Functions
Model
settings
Capacity
settings
Setting by the dip switch and jumper wire
For service board
12345
MODELS
PCA-RP50GA
PCH-P50GAH
PCA-RP50GA2
PCA-RP60GA
PCH-P60GAH
PCA-RP71GA
PCH-P71GAH
PCA-RP100GA
PCH-P100GAH
PCA-RP125GA
PCH-P125GAH
PCA-RP140GA
PCH-P140GAH
ON
OFF
Service board
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
Remarks
J41
J42
JP1
JP3
Pair number
setting with
wireless
remote
controller
Unit type
setting
Indoor
controller
board type
setting
Wireless remote
controller setting
0
1
2
3 ~ 9
Model
Without TH5
With TH5
Indoor controller board type
Service parts
Control PCB setting
J41J42
JP1
For product
<Initial setting>
Wireless remote controller: 0
Control PCB: (for both J41 and J42)
Four pair number settings are supported.
The pair number settings of the wireless remote
controller and indoor control PCB (J41/J42) are
given in the table on the left.
(' ' in the table indicates the jumper line is disconnected.)
There is no jumper (JP1) because these models
have the cond./eva. temperature thermistor (TH5).
For PCA-RP50/60/71/100/125/140GA#1,PCA-RP50GA2#1
11-1-1. Operation
(1) Rotation function (and Back-up function)
• Outline of functions
· Main and sub unit operate alternately according to the interval of rotation setting.
w Main and sub unit should be set by refrigerant address.(Outdoor Dip switch setting)
Refrigerant address"00" Main unit
Refrigerant address"01" Sub unit
· When error occurrs to one unit, another unit will start operation.(Back-up function)
• System constraint
· This function is available only by the grouping control system(INDOOR UNIT : OUTDOOR UNIT=1:1) of 2 refrigerant
groups.(Refer to Fig. 1)
· Main indoor unit should be connected for wired remote controller and the transmission line(TB5) for main and sub unit
should also be connected. (Refer to Fig. 1)
(This function cannot be set by wireless remote controller.)
· Set refrigerant address of each unit.(Dip switch on the outdoor unit···Refrigerant address 00/01)
Operation pattern
[Back-up function only]··· Request code number "312"
Start operation
Main
unit
IC-1
Sub
unit
IC-2
[Rotation function] & [Back-up function]··· Request code number "313~318"
Start operation
Main
unit
IC-1
Sub
unit
IC-2
(Ex:When the request code number is "313", each unit operates alternately in daily cycle.)
Run
Stop
Main SubSub MainMain Sub
Run
Stop
1~28 days1~28 days
Error occurs on main unit.
Main Sub
Abnormal condition
Run
Stop
Run
Run
StopRun
Error occurs on main unit.
Abnormal condition
Fig. 1
OC : Outdoor unit
IC : Indoor unit
RC : Wired remote controller
Refrigerant address
"00"
Main
unit
2
OC-1
3(2)
IC-1
2
RC
Refrigerant address
"01"
OC-2
Sub
3(2)
unit
IC-2
Note:
· When the uint is restarted to operate after turning off the power or OFF operation, the unit which was operating will start
operation.
· To operate the main unit, refer to the 11-1-2. and set the requet code No. which is not the same as the current one, and set
again the former request code No.
(2) 2nd stage cut-in function
Outline of functions
· Number of operating units is determined according to the room temperature and set point.
· When room temperature becomes higher than set point, standby unit starts.(2 units operation)
· When room temperature falls below set point -4:, standby unit stops.(1 unit operation)
System constraint
· This function is available only in rotation operation and back-up function in
cooling mode.
[2nd stage cut-in function]··· Request code number "322~324"
Start operationSub unit start operation
Main
unit
IC-1
Room temp. Set point
Run
Room temp. < Set point -4
Sub unit stop
Sub
unit
IC-2
StopStopRun
3333
11-1-2. How to set rotation function(Back-up function, 2nd stage cut-in function)
You can set these functions by wired remote controller.(Maintenance monitor)
NOTICE
Both main and sub unit should be set in same setting.
Every time replacing indoor controller board for servicing, the function should be set again.
(1) Request Code List
Rotation setting
Setting No.
(Request code)
No.1
(310)
No.2
(311)
No.3
(312)
No.4
(313)
No.5
(314)
No.6
(315)
No.7
(316)
No.8
(317)
No.9
(318)
Setting contents
Monitoring the request code of current setting.
Rotation and Back-up OFF (Normal group control operation)
Back-up function only
Rotation ON (Alternating interval = 1day) and back up function
Rotation ON (Alternating interval = 3day) and back up function
Rotation ON (Alternating interval = 5day) and back up function
Rotation ON (Alternating interval = 7day) and back up function
Rotation ON (Alternating interval = 14day) and back up function
Rotation ON (Alternating interval = 28day) and back up function
Initial
setting
nd stage cut-in setting
2
Setting No.
(Request code)
No.1
(320)
No.2
(321)
No.3
(322)
No.4
(323)
No.5
(324)
Setting contents
Monitoring the request code of current setting.
Cut-in function OFF
Cut-in Function ON(Set point = Set temp.+ 4°C(7.2°F))
Cut-in Function ON(Set point = Set temp.+ 6°C(10.8°F))
Cut-in Function ON(Set point = Set temp.+ 8°C(14.4°F))
Initial
setting
34
(2) Setting method of each function by wired remote controller
1. Stop operation().
2. Press the button () for 3 seconds so that [Maintenance mode] appears on the screen ().
After a while, [00] appears in the refrigerant address number display area.(at )
3. Press the button () for 3 seconds to switch to [Maintenance monitor].
Note) It is not possible to switch to [Maintenance monitor] during data request in maintenance mode
[----] appears on the screen () when [Maintenance monitor] is activated.
(The display () now allows you to set a request code No.)
TEST
CHECK
(i.e., while “----” is blinking) since no buttons are operative.
B: Refrigerant address
C: Data display area
D: Request code display area
4. Press the [TEMP ( and )] buttons () to select the desired refrigerant address.
[ScreenB]
5. Press the [CLOCK ( and )] buttons () to set the desired request code No.(“311~318”, “321~324”)
6. Press the button () to perform function setting.
If above setting operations are done correctly, "Request code number will appear in data display area.()
[Example: When the "311" of "Request code number" is set, [311] appears on the screen.()]
[Refererence]
You can check current "request code number" setting by setting the "request code number"(“310” or “320”) and
pressing the button.()
[Example: When the current setting is "Setting No.2(Request code 311)", [311] appears on the screen.()]
7. To return to normal mode, press the button ().
(1) Slide the intake grille holding 2 knobs backward to open
the intake grill.
(2) When the intake grille left open, push the stoppers on the
rear 2 hinges to pull out the intake grille.
2. Removing the electrical box
(1) Remove the air intake grille. (See the figure 1)
(2) Remove the screw from the beam and remove the beam.
(3) Remove the screws from the electrical cover, and remove
the electrical cover.
(4) Disconnect CN6V, CN21 and CN29.
(5) Remove the screws from the electrical box and pull out
the electrical box.
Figure 1
Intake grill
Intake grill
Holding knobs
Figure 2
slide
Hinges
Pull out the intake grill
Beam
Slide to the left
<Electrical parts in the electrical box>
Terminal block (for indoor / outdoor connecting line)
Terminal block (for electric heater : PCH only)
Terminal block (for remote controller)
Fan motor capacitor
Indoor control board
Relay (PCH only)
Power board
Power board
36
Screw(electrical cover)
Electrical cover
Photo 1
Fan motor
capacitor
Indoor
control
board
Screw(electrical box)
Relay (PCH only)
Terminal
Terminal
block
(Electric heater)
block
(Indoor / outdoor
connecting line)
Clamp
Terminal
block
(remote control)
OPERATING PROCEDUREPHOTOS&ILLUSTRATIONS
3. Removing the fan motor
(1) Remove the intake grille. (See the figure 1)
(2) Disconnect the fan motor connector.
(3) Remove screws for removing the motor guard.
(4) Remove screws for removing the fan guard.
(5) Remove the screw for removing the motor support at both
left and right side.
(6) Loosen the set screws at the fan motor side of the con-
necting joint.
(7) Slide the fan motor to the left side and pull it out.
4. Removing the sirocco fan
(1) Remove the air intake grille. (See the figure 1)
(2) Remove 1 beam.
(3) Remove screws for removing the motor guard.
(4) Remove screws for removing the fan guard.
(5) Remove the lower casing while pressing the stoppers at
upper side of the casing.
(6) Loosen the set screws at the connecting joint.
(7) Remove the sirocco fan and shaft together by sliding the
shaft to the left.
Photo 2
Photo 3
Screws
Motor support
Motor guard
Motor guard
Motor
Set screws
Connecting joint
Fan guard
(Note)
Make sure that the upper side casing is snapped to the fan
plate securely with catch.
5. Removing the side panel
(1) Remove the air intake grille. (See the figure 1)
(2) Remove the screw from the side panel, and remove the
side panel by sliding the panel to the front.
Figure 3
Motor
Sirocco fan
Connecting joint
Screw
Casing
Bearing
Side panel
Sliding the panel
to the front
3737
OPERATING PROCEDUREPHOTOS
6. Removing the vane motor
(1) Remove the air intake grille. (See the figure 1)
(2) Remove the left side panel. (See the figure 3)
(3) Remove the relay connector of vane motor.
(4) Remove the electrical box.
(5) Remove the screws of vane motor, then remove vane
motor.
(Note)
Connect the lead wires and connectors properly and place
them in the proper position so that the wires are not pinched
by other parts.
7. Removing the Indoor coil thermistor
(1) Remove the air intake grille. (See the figure 1)
(2) Remove the right side panel. (See the figure 3)
(3) Remove the relay connector of the pipe thermistor.
(4) Remove the screw, and remove the check panel.
(5) Extract the indoor coil thermistor from the holder.
<Caution for the installation>
There is a possibility for the short circuit when connector gets
wet by water through the thermistor lead wire.
Therefore, lead wire of the indoor coil thermistor should be
tied as shown in the photo 6.
Photo 4
Relay connector of the
vane motor
Photo 5
Left side
panel
Screw
Check
panel
Screw
Vane motor
Relay connector of
the pipe thermistor
8. Removing the Under panel
(1) Remove the air intake grille. (See the figure 1)
(2) Remove the beam.
(3) Remove the side panel (right and left). (See the figure 3)
(4) Remove the 9 screws of the under panel, then remove the
under panel.
w Weight of the under panel : approx. 2kg.
Photo 6
HoldIndoor coil thermistorClamp
Photo 7
Screws
38
Under panel
OPERATING PROCEDUREPHOTOS
9. Removing the drain pan
(1) Remove the air intake grille. (See the figure 1)
(2) Remove the beam.
(3)
Remove the side panels of right and left. (See the figure 3)
(4) Remove the under panel. Remove the screws of the right
and left side drain pan.
(5) Remove the 2 insulations in centre of the drain pan, and
after removing the 2 screws, remove the drain pan.
(Note)
Please aware that there might be drain left in the drain pan
when you remove the drain pump (option).
10. Removing the guide vane
(1) Remove the intake grille. (See the figure 1)
(2) Remove the beam.
Remove the side panels on right and left. (See the figure 3)
(3)
(4) Remove the under panel. (See the photo 7)
(5) Remove the drain pan. (See the photo 8)
(6) Remove the screw from the guide vane, then remove the
guide vane.
Photo 8
Screw
Photo 9
Drain pan
Screw
(Insulation)
Screw
11. Removing the Auto vane
(1) Remove the intake grille. (See the figure 1)
(2) Remove the left side panel. (See the figure 3)
(3) Remove the left side box.
(4) Remove the under panel.
(5) Remove the screw from the auto vane.
(6) Slide the auto vane to the right side and pull the auto
vane out.
Drain pan
Photo 10
Guide vane
Auto vane
Screw
Screw
39
OPERATING PROCEDUREPHOTOS
12. Removing the electric heater. (PCH only)
(1) Remove the air intake grille. (See the figure 1)
(2) Remove the beam.
(3) Remove the electrical box cover and disconnect the con-
nector (6P red) of the heater.
(4) Loosen 2 clamps for the heater lead wires.
(5) Remove the side panel (right and left). (See the figure 3)
(6) Remove the under panel. (See the photo 7)
(7) Remove the drain pan. (See the photo 8)
(8) Remove the 3 screws from the service panel.
(9) Pull out the heater with the service panel.
Photo 11
Clamp
Screws
Connector
(heater)
Service
panel
Electrical
box
13. Removing the heat exchanger.
(1) Remove the air intake grille. (See the figure 1)
(2) Remove the beam.
(3) Remove the side panel (right and left). (See the figure 3)
(4) Disconnect the relay connector of the pipe thermistor.
(5) Remove the under panel. (See the photo 7)
(6) Remove the drain pan. (See the photo 8)
(7) Unscrew the screw of the pipe cover, and remove the pipe
cover.
(8) Unscrew the screw of the pipe support, and remove the
pipe support.
(9) Unscrew the screw of the heat exchanger, and remove
the heat exchanger.
Remove the heat exchanger with care. Since this is quite
heavy, removing work should be done with more than 2
people.
wWeight of heat exchanger : approx. 5.3kg
Photo 12
Pipe
support
Screws
Pipe cover
Screws
Heat
exchanger
40
13
PARTS LIST(non-RoHS compliant)
FAN AND HEATER PARTS
PCH-P50GAH
PCA-RP50GA
2
3
4
5
18
17
1
14
13
2
12
3
16
15
6
7
8
9
No.
Parts No.Parts NameSpecifications
R01 17J 130
1
R01 17J 110
2
R01 17J 114
3
T7W 19J 675
4
R01 E26 202
5
R01 43E 126
6
R01 17J 220
7
R01 17J 524
8
T7W 17J 675
9
R01 A14 529
10
T7W 18J 675
11
R01 46K 700
12
R01 18J 303
13
R01 20J 303
T7W 23J 300
14
R01 17J 202
15
R01 E27 202
16
R01 E38 480
17
T7W K00 480
R01 P02 706
18
MOTOR LEG
CASING
SIROCCO FAN
FAN GUARD
ROOM TEMPERATURE THERMISTOR
PIECE (MOTOR)
FAN MOTOR
DRAIN PLUG
FAN GUARD
DRAIN PAN ASSY
FAN GUARD
THERMAL SWITCH
INSULATOR
INSULATOR
HEATER ELEMENT
PIPE TEMPERATURE THERMISTOR
CONDENSER / EVAPORATOR TEMPERATURE THERMISTOR
HEAT EXCHANGER
HEAT EXCHANGER
THERMAL FUSE
D09B4P54MS
OFF:50 ON:35
80V 466W
250V 98 10A
10
11
Q'ty / set
PCH-
P50GAH
1
2
2
1
1
1
1
1
1
1
1
1
3
1
3
1
1
1
1
PCA-
RP50GA
1
2
2
1
1
1
1
1
1
1
1
1
1
1
Remarks
(Drawing No.)
Wiring
Diagram
Symbol
TH1
MF
26H
H1
TH2
TH5
FS1,2
Recommended
Q'ty
4141
No.Parts No.Parts NameSpecifications
PCH-
PCA-
P60
GAH
RP60
GA
Wiring
Diagram
Symbol
Recom-
mended
Q'ty
Q'ty / set
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
MOTOR LEG
FAN MOTOR
SHAFT JOINT
PIECE (MOTOR)
SIROCCO FAN
FAN GUARD
ROOM TEMPERATURE THERMISTOR
SHAFT (FAN)
FAN GUARD
SLEEVE BEARING
BEARING SUPPORT
DRAIN PLUG
DRAIN PAN ASSY
FAN GUARD
CASING
SIROCCO FAN
INSULATOR
INSULATOR
HEATER ELEMENT
PIPE TEMPERATURE THERMISTOR
CONDENSER / EVAPORATOR TEMPERATURE THERMISTOR
HEAT EXCHANGER
HEAT EXCHANGER
THERMAL FUSE
THERMAL SWITCH
1
1
1
1
2
1
1
1
2
1
1
1
1
1
3
1
1
3
3
1
1
1
1
1
1
1
1
1
2
1
1
1
2
1
1
1
1
1
3
1
1
1
1
MF
TH1
H1
TH2
TH5
FS1,2
26H
Remarks
(Drawing No.)
R01 29J 130
T7W 30J 762
R01 700 116
R01 43E 126
R01 29J 114
T7W 20J 675
R01 E26 202
R01 29J 100
T7W 21J 675
R01 E00 103
R01 29J 145
R01 17J 524
R01 A15 529
T7W 18J 675
R01 17J 110
R01 33J 114
R01 20J 303
R01 30J 303
T7W 30J 300
R01 17J 202
R01 E27 202
R01 H00 480
T7W K01 480
T7W 23J 706
R01 46K 700
DO9C4P70MS
80V 700W
110 16A 250V
OFF:50 ON:35
RP71
GA
1
1
1
1
2
1
1
1
2
1
1
1
1
1
3
1
1
1
1
P71
GAH
1
1
1
1
2
1
1
1
2
1
1
1
1
1
3
1
1
3
3
1
1
1
1
1
FAN AND HEATER PARTS
PCH-P60GAH, PCA-RP60GA
PCH-P71GAH, PCA-RP71GA
1
2
3
23
22
21
20
19
18
17
4
5
6
7
5
8
9
10·11
12
42
13
14
16
15
No.Parts No.Parts NameSpecifications
PCA-PCH-
Wiring
Diagram
Symbol
Recom-
mended
Q'ty
Q'ty / set
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
PIECE (MOTOR)
MOTOR LEG
FAN MOTOR
SHAFT JOINT
SIROCCO FAN
FAN GUARD
ROOM TEMPERATURE THERMISTOR
SHAFT
FAN GUARD
SLEEVE BEARING
BEARING SUPPORT
DRAIN PLUG
DRAIN PAN ASSY
FAN GUARD
CASING
SIROCCO FAN
INSULATOR
INSULATOR
HEATER ELEMENT
PIPE TEMPERATURE THERMISTOR
CONDENSER / EVAPORATOR TEMPERATURE THERMISTOR
HEAT EXCHANGER
HEAT EXCHANGER
THERMAL FUSE
THERMAL SWITCH
P100GAH
1
1
1
1
2
1
1
1
2
1
1
1
1
1
3
1
1
3
3
1
1
1
1
1
RP100GA
1
1
1
1
2
1
1
1
2
1
1
1
1
1
3
1
1
1
1
MF
TH1
H1
TH2
TH5
FS1,2
26H
Remarks
(Drawing No.)
R01 43E 126
R01 35J 130
R01 35J 220
R01 700 116
R01 35J 114
T7W 22J 675
R01 E26 202
R01 29J 100
T7W 23J 675
R01 E00 103
R01 35J 145
R01 17J 524
R01 A16 529
T7W 24J 675
R01 35J 110
R01 39J 114
R01 20J 303
R01 36J 303
T7W 39J 300
R01 17J 202
R01 E27 202
R01 E33 480
T7W K02 480
T7W 589 706
R01 46K 700
D10B4P90MS
80V 900W
117 16A 250V
OFF:50 ON:35
FAN AND HEATER PARTS
PCH-P100GAH
PCA-RP100GA
1
2
3
4
5
6
7
8
23
5
9
10·11
22
14
13
12
21
20
19
18
17
16
15
43
No.
Parts No.Parts NameSpecifications
Wiring
Diagram
Symbol
Recom-
mended
Q'ty
Q'ty / set
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
SHAFT
MOTOR LEG
FAN MOTOR
PIECE (MOTOR)
SIROCCO FAN
FAN GUARD
ROOM TEMPERATURE THERMISTOR
FAN GUARD
SIROCCO FAN
SHAFT JOINT
DRAIN PAN ASSY
FAN GUARD
SIROCCO FAN
DRAIN PLUG
FAN GUARD
CASING
SLEEVE BEARING
BEARING SUPPORT
INSULATOR
INSULATOR
HEATER ELEMENT
PIPE TEMPERATURE THERMISTOR
CONDENSER / EVAPORATOR TEMPERATURE THERMISTOR
HEAT EXCHANGER
HEAT EXCHANGER
HEAT EXCHANGER
HEAT EXCHANGER
THERMAL FUSE
THERMAL SWITCH
MF
TH1
H1
TH2
TH5
FS1,2
26H
Remarks
(Drawing No.)
R01 29J 100
R01 41J 130
R01 41J 220
R01 43E 126
R01 41J 114
T7W 26J 675
R01 E26 202
T7W 25J 675
R01 35J 114
R01 700 116
R01 A17 529
T7W 23J 675
R01 39J 114
R01 17J 524
T7W 24J 675
R01 35J 110
R01 E00 103
R01 35J 145
R01 20J 303
R01 36J 303
T7W 43J 300
R01 17J 202
R01 E27 202
T7W K03 480
T7W K04 480
T7W K05 480
T7W K06 480
T7W 23J 706
R01 46K 700
D10B4P150MS
80V 1000W
110 16A 250V
OFF:50 ON:35
PCH-PCA-
1
1
1
1
1
1
1
1
2
1
1
2
1
1
1
4
1
1
1
6
3
1
1
1
1
1
P125
GAH
1
1
1
1
1
1
1
1
2
1
1
2
1
1
1
4
1
1
1
1
1
RP125
GA
Q'ty / set
1
1
1
1
1
1
1
1
2
1
1
2
1
1
1
4
1
1
1
6
3
1
1
1
1
1
P140
GAH
1
1
1
1
1
1
1
1
2
1
1
2
1
1
1
4
1
1
1
1
1
RP140
GA
FAN AND HEATER PARTS
PCH-P125GAH, PCA-RP125GA
PCH-P140GAH, PCA-RP140GA
S.PLATE-L
L.L FILTER
GRILLE HINGE
GRILLE ASSY
GRILLE ASSY
GRILLE CATCH
L.L FILTER
REAR SUPPORT
UNDER PANEL
BEAM(GA)
W.BOARD CASE
S.PLATE-R
RIGHT LEG (R)
SERVICE PANEL
RIGHT SIDE PANEL
RIGHT SIDE BOX
G.V ASSY-6R
VANE SUPPORT
FRONT PANEL
AUTO VANE
G.V ASSY-6L
REAR PANEL
LEFT SIDE BOX
VANE MOTOR
LEFT LEG (L)
LEFT SIDE PANEL
JOINT SOCKET
DRAIN HOSE COVER
Part numbers that are circled are not shown in the figure.
45
STRUCTURAL PART
PCA-RP60GA
PCA-RP71GA
PCA-RP100GA
PCH-P60GAH
PCH-P71GAH
PCH-P100GAH
Part numbers that are circled are not show in the figure.
1
2
3
4
5
67 891011 12 13
23
2425
2122
20
19
18
17
16
15
14
No.
Parts No.Parts Name
R01 17J 662
1
R01 35J 662
2
R01 17J 809
R01 57N 666
3
R01 35J 666
R01 A15 676
4
R01 A16 676
5
R01 17J 061
6
R01 17J 054
7
R01 17J 691
8
R01 A14 500
9
R01 29J 669
10
T7W E01 070
11
12
R01 18J 665
13
R01 E00 665
R01 17J 661
14
R01 35J 661
15
R01 17J 808
R01 17J 668
16
R01 18J 668
R01 17J 067
17
R01 35J 067
R01 29J 651
18
R01 36J 651
R01 29J 002
19
R01 E03 002
R01 E00 033
20
R01 E01 033
21
R01 37J 085
22
R01 37J 087
23
R01 37J 086
R01 17J 068
24
R01 E00 068
R01 29J 223
25
R01 35J 223
26
R01 17J 523
27
T7W E00 072
—
—
LEFT SIDE PANEL
LEFT SIDE PANEL
LEFT LEG
S.PLATE-L
S.PLATE-L
REAR PANEL
REAR PANEL
GRILLE HINGE
GRILLE CATCH
GRILLE ASSY
L.L FILTER
UNDER PANEL
W.BOARD CASE
REAR SUPPORT
BEAM (GA)
S.PLATE-R
S.PLATE-R
RIGHT SIDE PANEL
RIGHT SIDE PANEL
RIGHT LEG
SERVICE PANEL
SERVICE PANEL
RIGHT SIDE BOX
RIGHT SIDE BOX
FRONT PANEL
FRONT PANEL
AUTO VANE
AUTO VANE
VANE SUPPORT
VANE SUPPORT
G.V ASSY-6R
G.V ASSY-6C
G.V ASSY-6L
LEFT SIDE BOX
LEFT SIDE BOX
VANE MOTOR
VANE MOTOR
JOINT SOCKET
DRAIN HOSE COVER
LEFT SIDE PANEL
S.PLATE-L
REAR PANEL
L.L FILTER
GRILLE HINGE
GRILLE ASSY
GRILLE CATCH
GRILLE ASSY
L.L FILTER
UNDER PANEL
W.BOARD CASE
REAR SUPPORT
BEAM(GA)
RIGHT SIDE PANEL
RIGHT LEG
SERVICE PANEL
RIGHT SIDE BOX
S.PLATE-R
FRONT PANEL
AUTO VANE
G.V ASSY-5R
G.V ASSY-5C
VANE SUPPORT
G.V ASSY-5L
LEFT SIDE BOX
VANE MOTOR
LEFT LEG
JOINT SOCKET
DRAIN HOSE COVER
PCA-RP125/140GA
PCH-P125/140GAH
Q,ty/set
PCA-RP125GA
PCA-RP140GA
PCH-P125GAH
PCH-P140GAH
27
262524
23
1
22
21
2
3
4
5
6
7
Part numbers that are circled are not shown in the figure.
8
9
47
10
11
13
12
20
19
18
17
16
15
14
ELECTRICAL PARTS
PCA-RP50GA
PCA-RP60GA
PCA-RP71GA
PCA-RP100GA
PCA-RP125GA
PCA-RP140GA
1
7
6
2
3
4
5
No.
Parts No.Parts NameSpecifications
R01 30L 255
1
T7W 39J 255
R01 A13 255
2
R01 E02 239
3
T7W E40 310
4
T7W E23 716
5
T7W 512 716
6
7
R01 E02 313
8
9
T7W A00 305
10
T7W E08 713
—
—
—
—
CAPACITOR
CAPACITOR
CAPACITOR
FUSE
INDOOR CONTROLLER BOARD
TERMINAL BLOCK
TERMINAL BLOCK
CONTROL BOX
POWER BOARD
CONTROL COVER
CONTROL COVER
CONTROL COVER
REMOTE CONTROLLER CORD
REMOTE CONTROLLER
8
3 440V
4
440V
6
440V
250V 6.3A
3P(S1,S2,S3)
2P(1,2)
PAR-21MAA
50
1
1
1
1
1
1
1
1
1
1
Q,ty
PCA-RP
60/71 100
GA
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
9
125/140
1
1
1
1
1
(BG00N015G31)
1
1
(BG02A804G27)
(BG02A804G28)
1
(BG02A804G29)
1
1
10
Remarks
(Drawing No.)
TEMP.
Wiring
Diagram
Symbol
C
C
C
FUSE
I.B
TB4
TB5
P. B
R.B
ON/OFF
Recommended
Q'ty
48
ELECTRICAL PARTS
PCH-P50GAH, PCH-P100GAH
PCH-P60GAH, PCH-P125GAH
PCH-P71GAH, PCH-P140GAH
9
8
1
7
2
3
4
5
6
TEMP.
ON/OFF
12
10
11
No.
Parts No.Parts Name
R01 30L 255
T7W 39J 255
1
R01 A13 255
R01 E02 239
2
T7W E40 310
3
T7W A14 716
4
T7W E23 716
5
T7W 512 716
6
7
R01 E02 313
8
R01 71G 215
9
10
T7W A00 305
11
T7W E08 713
12
—
—
—
—
CAPACITOR
CAPACITOR
CAPACITOR
FUSE
INDOOR CONTROLLER BOARD
TERMINAL BLOCK
TERMINAL BLOCK
TERMINAL BLOCK
CONTROL BOX
POWER BOARD
RELAY
CONTROL COVER
CONTROL COVER
CONTROL COVER
REMOTE CONTROLLER CORD
REMOTE CONTROLLER
Specifications
3 440V
4 440V
6 440V
250V 6.3A
3P (L,N, )
3P (S1,S2,S3)
2P (1,2)
JC-1A DC12V
10m
PAR-21MAA
Q'ty / set
PCH-P
50100
60/71
GAH
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
125/140
1
1
1
1
1
1
1
(BG00N015G32)
1
1
(BG02A804G27)
(BG02A804G28)
1
(BG02A804G29)
1
1
Remarks
(Drawing No.)
Wiring
Diagram
Symbol
C
C
C
FUSE
I.B
TB2
TB4
TB5
P. B
88H
R.B
Recom-
mended
Q'ty
49
RoHS PARTS LIST14
FAN AND HEATER PARTS
PCH-P50GAH
PCA-RP50GA
PCA-RP50GA#1
2
3
4
5
18
17
1
14
13
2
12
3
16
15
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
6
7
8
9
Parts No.Parts Name
RoHS
R01 31J 130
G
R01 18J 110
G
R01 E16 114
G
T7W 31J 675
G
R01 H08 202
G
R01 45E 126
G
R01 18J 220
G
R01 18J 524
G
T7W 30J 675
G
R01 E27 529
G
T7W 29J 675
G
R01 E13 700
G
R01 21J 303
G
R01 31J 303
G
T7W E21 300
G
R01 H10 202
G
R01 H09 202
G
R01 N08 480
G
T7W H41 480
G
R01 P03 706
G
MOTOR LEG
CASING
SIROCCO FAN
FAN GUARD
ROOM TEMPERATURE THERMISTOR
PIECE (MOTOR)
FAN MOTOR
DRAIN PLUG
FAN GUARD
DRAIN PAN ASSY
FAN GUARD
THERMAL SWITCH
INSULATOR
INSULATOR
HEATER ELEMENT
PIPE TEMPERATURE THERMISTOR
CONDENSER / EVAPORATOR TEMPERATURE THERMISTOR
HEAT EXCHANGER
HEAT EXCHANGER
THERMAL FUSE
10
Specifications
D09B4P54MS
OFF:50 ON:35
80V 467W
250V 98 10A
11
Q'ty / set
PCH-PPCA-RP
50GAH 50GA
1
2
2
1
1
1
1
1
1
1
1
1
3
1
3
1
1
1
1
50GA#1
1
2
2
1
1
1
1
1
1
1
1
1
1
1
1
2
2
1
1
1
1
1
1
1
1
1
1
1
Remarks
(Drawing No.)
Wiring
Diagram
Symbol
TH1
MF
26H
H1
TH2
TH5
FS1,2
Recom-
mended
Q'ty
50
FAN AND HEATER PARTS
PCA-RP50GA2
PCA-RP50GA2#1
PCA-RP60GA
PCA-RP71GA
PCA-RP60GA#1
PCA-RP71GA#1
PCH-P60GAH
PCH-P71GAH
1
2
3
23
22
21
20
19
18
17
4
5
6
7
No.Parts No.Parts Name
RoHS
MOTOR LEG
FAN MOTOR
SHAFT JOINT
PIECE (MOTOR)
SIROCCO FAN
FAN GUARD
ROOM TEMPERATURE THERMISTOR
SHAFT (FAN)
FAN GUARD
SLEEVE BEARING
BEARING SUPPORT
DRAIN PLUG
DRAIN PAN ASSY
FAN GUARD
CASING
SIROCCO FAN
INSULATOR
INSULATOR
HEATER ELEMENT
PIPE TEMPERATURE THERMISTOR
CONDENSER / EVAPORATOR TEMPERATURE THERMISTOR
HEAT EXCHANGER
HEAT EXCHANGER
HEAT EXCHANGER
THERMAL FUSE
THERMAL SWITCH
10
11
12
13
14
15
16
17
18
19
20
21
22
23
1
G
2
G
3
G
4
G
5
G
6
G
7
G
8
G
9
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
R01 30J 130
T7W 40J 762
R01 800 116
R01 45E 126
R01 E17 114
T7W 29J 675
R01 H08 202
R01 30J 100
T7W 28J 675
R01 E02 103
R01 30J 145
R01 18J 524
R01 A18 529
T7W 27J 675
R01 18J 110
R01 E15 114
R01 31J 303
R01 40J 303
T7W E11 300
R01 H10 202
R01 H09 202
R01 J66 480
T7W H42 480
T7W H37 480
T7W 25J 706
R01 E13 700
16
15
14
13
5
8
9
10·11
Specifications
DO9C4P70MS
80V 700W
110 16A 250V
OFF:50 ON:35
12
Q'ty / set
PCH- PPCA- RP
1
1
1
1
2
1
1
1
2
1
1
1
1
1
3
1
1
3
3
1
1
1
1
1
50GA2
50GA2#1
1
1
1
1
2
1
1
1
2
1
1
1
1
1
3
1
1
1
1
60GAH
1
1
1
1
2
1
1
1
2
1
1
1
1
1
3
1
1
3
3
1
1
1
1
1
71GAH
60GA
60GA#1
1
1
1
1
2
1
1
1
2
1
1
1
1
1
3
1
1
1
1
71GA
71GA#1
1
1
1
1
2
1
1
1
2
1
1
1
1
1
3
1
1
1
1
Remarks
(Drawing No.)
Wiring
Diagram
Symbol
MF
TH1
H1
TH2
TH5
FS1,2
26H
Recommended
Q'ty
5151
No.Parts No.Parts Name
Specifications
PCA-RPPCH-P
Wiring
Diagram
Symbol
Recom-
mended
Q'ty
Q'ty / set
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
RoHS
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
PIECE (MOTOR)
MOTOR LEG
FAN MOTOR
SHAFT JOINT
SIROCCO FAN
FAN GUARD
ROOM TEMPERATURE THERMISTOR
SHAFT
FAN GUARD
SLEEVE BEARING
BEARING SUPPORT
DRAIN PLUG
DRAIN PAN ASSY
FAN GUARD
CASING
SIROCCO FAN
INSULATOR
INSULATOR
HEATER ELEMENT
PIPE TEMPERATURE THERMISTOR
CONDENSER / EVAPORATOR TEMPERATURE THERMISTOR
HEAT EXCHANGER
HEAT EXCHANGER
THERMAL FUSE
THERMAL SWITCH
100GAH
1
1
1
1
2
1
1
1
2
1
1
1
1
1
3
1
1
3
3
1
1
1
1
1
100GA
1
1
1
1
2
1
1
1
2
1
1
1
1
1
3
1
1
1
1
MF
TH1
H1
TH2
TH5
FS1,2
26H
Remarks
(Drawing No.)
R01 45E 126
R01 32J 130
R01 19J 220
R01 800 116
R01 E19 114
T7W 35J 675
R01 H08 202
R01 30J 100
T7W 34J 675
R01 E02 103
R01 36J 145
R01 18J 524
R01 E28 529
T7W 32J 675
R01 19J 110
R01 E20 114
R01 31J 303
R01 41J 303
T7W E22 300
R01 H10 202
R01 H09 202
R01 N09 480
T7W H43 480
T7W 11G 706
R01 E13 700
D10B4P90MS
80V 900W
117 16A 250V
OFF:50 ON:35
100GA#1
1
1
1
1
2
1
1
1
2
1
1
1
1
1
3
1
1
1
1
FAN AND HEATER PARTS
PCH-P100GAH
PCA-RP100GA
PCA-RP100GA#1
1
2
3
4
5
6
7
8
23
22
21
20
19
18
17
16
15
14
5
9
13
12
10·11
52
FAN AND HEATER PARTS
PCA-RP125GA
PCA-RP140GA
PCA-RP125GA#1
PCA-RP140GA#1
PCH-P125GAH
PCH-P140GAH
6
7
8
1
2
3
25
23
4
22
21
5
20
19
24
9
10
11
9
12
13
14
17·18
16
15
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
Parts No.Parts Name
RoHS
G
R01 30J 100
G
R01 33J 130
G
R01 20J 220
G
R01 45E 126
G
R01 E18 114
G
T7W 35J 675
G
R01 H08 202
G
T7W 33J 675
G
R01 E19 114
G
R01 800 116
G
R01 E29 529
G
T7W 34J 675
G
R01 E20 114
G
R01 18J 524
G
T7W 36J 675
G
R01 19J 110
G
R01 E02 103
G
R01 36J 145
G
R01 31J 303
G
R01 41J 303
G
T7W E12 300
G
R01 H10 202
G
R01 H09 202
G
T7W H44 480
G
T7W H45 480
G
T7W H46 480
G
T7W H47 480
G
T7W 25J 706
G
R01 E13 700
SHAFT
MOTOR LEG
FAN MOTOR
PIECE (MOTOR)
SIROCCO FAN
FAN GUARD
ROOM TEMPERATURE THERMISTOR
FAN GUARD
SIROCCO FAN
SHAFT JOINT
DRAIN PAN ASSY
FAN GUARD
SIROCCO FAN
DRAIN PLUG
FAN GUARD
CASING
SLEEVE BEARING
BEARING SUPPORT
INSULATOR
INSULATOR
HEATER ELEMENT
PIPE TEMPERATURE THERMISTOR
CONDENSER / EVAPORATOR TEMPERATURE THERMISTOR
HEAT EXCHANGER
HEAT EXCHANGER
HEAT EXCHANGER
HEAT EXCHANGER
THERMAL FUSE
THERMAL SWITCH
Specifications
D10B4P150MS
80V 1000W
110 16A 250V
OFF:50 ON:35
PCH- P
125GAH
1
1
1
1
1
1
1
1
2
1
1
2
1
1
1
4
1
1
1
6
3
1
1
1
1
1
Q'ty / set
140GAH
1
1
1
1
1
1
1
1
2
1
1
2
1
1
1
4
1
1
1
6
3
1
1
1
1
1
PCA- RP
125GA
125GA#1
1
1
1
1
1
1
1
1
2
1
1
2
1
1
1
4
1
1
1
1
1
140
GA
140GA#1
1
1
1
1
1
1
1
1
2
1
1
2
1
1
1
4
1
1
1
1
1
Remarks
(Drawing No.)
Wiring
Diagram
Symbol
MF
TH1
H1
TH2
TH5
FS1,2
26H
Recom-
mended
Q'ty
53
STRUCTURAL PART
PCA-RP50GA
PCA-RP50GA#1
PCH-P50GAH
1
2
3
4
5
212223242526
6
7
10
8
9
11
12
13
20
19
18
17
16
15
14
Part numbers that are circled are not shown in the figure.
S.PLATE-L
L.L FILTER
GRILLE HINGE
GRILLE ASSY
GRILLE ASSY
GRILLE CATCH
L.L FILTER
REAR SUPPORT
UNDER PANEL
BEAM(GA)
W.BOARD CASE
S.PLATE-R
RIGHT LEG (R)
SERVICE PANEL
RIGHT SIDE PANEL
RIGHT SIDE BOX
G.V ASSY-6R
VANE SUPPORT
FRONT PANEL
AUTO VANE
G.V ASSY-6L
REAR PANEL
LEFT SIDE BOX
VANE MOTOR
LEFT LEG (L)
LEFT SIDE PANEL
JOINT SOCKET
DRAIN HOSE COVER
STRUCTURAL PART
PCA-RP50GA2
PCA-RP50GA2#1
PCA-RP60GA
PCA-RP71GA
PCA-RP100GA
PCA-RP60GA#1
PCA-RP71GA#1
1
2
3
4
5
PCA-RP100GA#1
PCH-P60GAH
PCH-P71GAH
PCH-P100GAH
678910 11 1213
Part numbers that are circled are not show in the figure.
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
Parts No.Parts Name
RoHS
G
R01 18J 662
G
R01 36J 662
G
R01 18J 809
G
R01 E00 666
G
R01 E01 666
G
R01 30J 676
G
R01 A21 676
G
R01 18J 061
G
R01 19J 054
G
R01 19J 691
G
R01 A29 500
G
R01 30J 669
G
T7W E02 070
G
G
G
R01 19J 665
G
R01 E01 665
G
R01 18J 661
G
R01 36J 661
G
R01 18J 808
G
R01 19J 668
G
R01 20J 668
G
R01 18J 067
G
R01 36J 067
G
R01 30J 651
G
R01 38J 651
G
R01 30J 002
G
R01 E14 002
G
R01 E02 033
G
R01 E03 033
G
R01 38J 085
G
R01 38J 087
G
R01 38J 086
G
R01 18J 068
G
R01 E01 068
G
R01 E10 223
G
R01 E12 223
G
R01 18J 523
G
T7W E01 072
R01 18J 072
G
—
—
LEFT SIDE PANEL
LEFT SIDE PANEL
LEFT LEG
S.PLATE-L
S.PLATE-L
REAR PANEL
REAR PANEL
GRILLE HINGE
GRILLE CATCH
GRILLE ASSY
L.L FILTER
UNDER PANEL
W.BOARD CASE
REAR SUPPORT
BEAM (GA)
S.PLATE-R
S.PLATE-R
RIGHT SIDE PANEL
RIGHT SIDE PANEL
RIGHT LEG
SERVICE PANEL
SERVICE PANEL
RIGHT SIDE BOX
RIGHT SIDE BOX
FRONT PANEL
FRONT PANEL
AUTO VANE
AUTO VANE
VANE SUPPORT
VANE SUPPORT
G.V ASSY-6R
G.V ASSY-6C
G.V ASSY-6L
LEFT SIDE BOX
LEFT SIDE BOX
VANE MOTOR
VANE MOTOR
JOINT SOCKET
DRAIN HOSE COVER
DRAIN HOSE COVER
Specifi-
cations
GA2
1
1
1
1
4
4
2
2
1
1
1
2
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
2425
PCA-RP/PCH-P
50
GA2#1
GA/GAH
1
1
1
1
4
4
2
2
1
1
1
2
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
22
23
Q,ty/set
60/71
GA#1GA#1
GA/GAH
1
1
1
1
1
1
1
1
4
4
4
4
2
2
2
2
1
1
1
1
1
1
2
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
21
20
19
18
17
16
15
14
Wiring
100
1
1
1
1
1
1
1
1
4
4
4
4
2
2
2
2
1
1
1
1
1
1
2
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Remarks
(Drawing No.)
(BG02H454K01)
(BG17H464H08)
Diagram
Symbol
MV
MV
Recommended
Q'ty
55
STRUCTURAL PART
PCA-RP125GA
PCA-RP140GA
PCA-RP125GA#1
PCA-RP140GA#1
PCH-P125GAH
PCH-P140GAH
1
27
26 2524
23
22
21
2
3
4
5
6
7
Part numbers that are circled are not shown in the figure.
LEFT SIDE PANEL
S.PLATE-L
REAR PANEL
L.L FILTER
GRILLE HINGE
GRILLE ASSY
GRILLE CATCH
GRILLE ASSY
L.L FILTER
UNDER PANEL
W.BOARD CASE
REAR SUPPORT
BEAM (GA)
RIGHT SIDE PANEL
RIGHT LEG
SERVICE PANEL
RIGHT SIDE BOX
S.PLATE-R
FRONT PANEL
AUTO VANE
G.V ASSY-5R
G.V ASSY-5C
VANE SUPPORT
G.V ASSY-5L
LEFT SIDE BOX
VANE MOTOR
LEFT LEG
JOINT SOCKET
DRAIN HOSE COVER
ELECTRICAL PARTS
PCA-RP50/60/71/100/125/140GA
PCA-RP50/60/71/100/125/140GA#1
PCA-RP50GA2
PCA-RP50GA2#1
1
2
7
6
3
4
5
No.
1
2
3
4
5
6
7
8
9
10
Parts No.Parts Name
RoHS
G
R01 A15 255
G
T7W E13 255
R01 A14 255
G
R01 E06 239
G
T7W E50 310
G
T7W E73 310
G
R01 E20 246
G
T7W E33 716
G
G
G
G
G
G
G
G
—
R01 E38 313
—
—
—
T7W A01 305
T7W E11 713
CAPACITOR
CAPACITOR
CAPACITOR
FUSE
INDOOR CONTROLLER BOARD
INDOOR CONTROLLER BOARD
TERMINAL BLOCK
TERMINAL BLOCK
CONTROL BOX
POWER BOARD
CONTROL COVER
CONTROL COVER
CONTROL COVER
REMOTE CONTROLLER CORD
REMOTE CONTROLLER
Specifications
3440V
4
440V
6
440V
250V 6.3A
3P(S1,S2,S3)
2P(1,2)
10m
PAR-21MAA
50
8
1
1
1
1
1
1
1
1
1
1
60/71
GA
1
1
1
1
1
1
1
1
1
1
100
1
1
1
1
1
1
1
1
1
1
PCA-RP
50
125/140
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
60/71
GA#1
1
1
1
1
1
1
1
1
1
1
100
1
1
1
1
1
1
1
1
1
1
9
125/140
GA2
1
1
1
1
1
1
1
1
1
1
1
1
1
11
1
1
1
1
1
1
10
(Drawing No.)
50
GA2#1
1
1
1
1
1
(BG00N015G40)
1
(BG02A804G38)
(BG02A804G39)
1
(BG02A804G40)
1
1
Remarks
TEMP.
ON/OFF
Wiring
Diagram
Symbol
Recommended
Q'ty
C
C
C
FUSE
I.B
I.B
TB4
TB5
P. B
R.B
57
No.
Parts No.Parts Name
Specifications
Wiring
Diagram
Symbol
Recom-
mended
Q'ty
(BG00N015G42)
Q'ty / set
GAH
1
2
3
4
5
6
7
8
9
10
11
12
RoHS
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
CAPACITOR
CAPACITOR
CAPACITOR
FUSE
INDOOR CONTROLLER BOARD
TERMINAL BLOCK
TERMINAL BLOCK
TERMINAL BLOCK
CONTROL BOX
POWER BOARD
RELAY
CONTROL COVER
CONTROL COVER
CONTROL COVER
REMOTE CONTROLLER CORD
REMOTE CONTROLLER
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
C
C
C
FUSE
I.B
TB2
TB4
TB5
P. B
88H
R.B
3 440V
4 440V
6 440V
250V 6.3A
3P (L,N, )
3P (S1,S2,S3)
2P (1,2)
JC-1A DC12V
10m
PAR-21MAA
Remarks
(Drawing No.)
R01 A15 255
T7W E13 255
R01 A14 255
R01 E06 239
T7W E50 310
T7W E32 716
R01 E20 246
T7W E33 716
—
R01 E38 313
R01 E03 215
—
—
—
T7W A01 305
T7W E11 713
50100
PCH-P
(BG02A804G38)
(BG02A804G39)
(BG02A804G40)
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
60/71
125/140
ELECTRICAL PARTS
PCH-P50GAH, PCH-P100GAH
PCH-P60GAH, PCH-P125GAH
PCH-P71GAH, PCH-P140GAH
9
8
1
7
2
3
4
5
6
TEMP.
ON/OFF
12
10
11
58
59
HEAD OFFICE : TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
CCopyright 2007 MITSUBISHI ELECTRIC ENGINEERING CO., LTD.
Distributed in May 2008 No.OC328 REVISED EDITION-B PDF 7
Distributed in Jun . 2006 No.OC328 REVISED EDITION-A PDF 8
Distributed in May. 2005 No.OC328 PDF 9
Made in Japan
New publication, effective May 2008
Specifications subject to change without notice
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.