Mitsubishi PCA-P3HA, PCA-P5HA Service Manual

Page 1
ON/OFF
CENTRALLY CONTROLLED
ERROR CODE
CLOCK
ON OFF
˚C
CHECK
CHECK MODE
FILTER
TEST RUN FUNCTION
˚C
1Hr.
NOT AVAILABLE
STAND BY DEFROST
TEMP.
SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS SPLIT-TYPE, AIR CONDITIONERS
TECHNICAL & SERVICE MANUAL
2003
No. OC289
Series PCA
Ceiling Suspended
Indoor unit [Model names] [Service Ref.]
PCA-P3HA PCA-P3HA PCA-P5HA PCA-P5HA
INDOOR UNIT
R407C
• Refer to the OCT03 REVISED EDITION-E as regarding control relation.
• This manual does not cover outdoor units.When serving them, please refer to the service manual No.OC261 REVISED EDITION-B and this manual in a set.
CONTENTS
1. SAFETY PRECAUTION···································2
2. PART NAMES AND FUNCTIONS····················4
3. SPECIFICATIONS············································6
4. DATA·······························································10
5. OUTLINES AND DIMENSIONS·····················21
6.
WIRING DIAGRAM
7.
REFRIGERANT SYSTEM DIAGRAM
8. TROUBLESHOOTING ···································25
9. DISASSEMBLY PROCEDURE······················26
10. PARTS LIST···················································30
11. OPTIONAL PARTS·········································33
············································23
··················24
REMOTE CONTROLLER
Page 2
1
SAFETY PRECAUTION
Cautions for using with the outdoor unit which adopts R407C refrigerant.
· Do not use the existing refrigerant piping.
-The old refrigerant and refrigerant oil in the existing piping contains a large amount of chlorine which may cause the refriger­ant oil of the new unit to deteriorate.
· Do not use copper pipes which are broken, deformed or discolour .
In addition, be sure that the inner surfaces of the pipes are clean, free of hazardous sulphur and oxides, or have no dust /
dirt, shaving particles, oils, moisture or any other contamination.
-If there is a large amount of residual oil (hydraulic oil, etc.) inside the piping and joints, deterioration of the refrigerant oil will result.
· Store the piping to be used during installation indoors and keep both ends of the piping sealed until just before brazing. (Store elbows and other joints in a plastic bag.)
-If dust, dirt, or water enters the refrigerant cycle, deterioration of the oil and compressor trouble may result.
· Use ester oil, ether oil or alkyl benzene (small amount) as the refrigerant oil to coat flares and flange connections.
-The refrigerant oil will degrade if it is mixed with a large amount of mineral oil.
Use liquid refrigerant to fill the system.
-If gas refrigerant is used to fill the system, the composition of the refrigerant in the cylinder will change and performance
may drop.
· Do not use a refrigerant other than R407C.
-If another refrigerant (R22, etc.) is used, the chlorine in the refrigerant may cause the refrigerant oil to deteriorate.
· Use a vacuum pump with a reverse flow check valve.
-The vacuum pump oil may flow back into the refrigerant cycle and cause the refrigerant oil to deteriorate.
· Do not use the following tools that are used with conventional refrigerant. (Gauge manifold , charge hose, gas leak detector, reverse flow check valve, refrigerant charge base, vacuum gauge,
refrigerant recovery equipment)
-If the conventional refrigerant and refrigerant oil are mixed in the R407C, the refrigerant may deteriorated.
-If water is mixed in the R407C, the refrigerant oil may deteriorate.
-Since R407C does not contain any chlorine, gas leak detectors for conventional refrigerant will not react to it.
· Do not use a charging cylinder.
-Using a charging cylinder may cause the refrigerant to deteriorate.
· Be especially careful when managing the tools.
-if dust, dirt, or water gets in the refrigerant cycle, the refrigerant may deteriorate.
· Do not use the drier which is sold in the field.
-The drier for R407C refrigerant is per-attached to outdoor unit refrigerant circuit.
-Some drier in the field are not in conformity with R407C refrigerant .
2
Page 3
Gravimeter
Unit
[1] Service tools
Use the below service tools as exclusive tools for R407C refrigerant.
No. Tool name Specifications
1 Gauge manifold ·Only for R407C.
·Use the existing fitting SPECIFICATIONS. (UNF7/16)
·Use high-tension side pressure of 3.43MPa or over.
2 Charge hose ·Only for R407C.
·Use pressure performance of 5.10MPa or over.
3 Electronic scale 4 Gas leak detector ·Use the detector for R407C. 5 Adapter for reverse flow check. ·Attach on vacuum pump. 6 Refrigerant charge base. 7 Refrigerant cylinder. ·For R407C ·Top of cylinder (Brown)
·Cylinder with syphon
8 Refrigerant recovery equipment.
[2] Notice on repair service
·After recovering the all refrigerant in the unit, proceed to working.
·Do not release refrigerant in the air.
·After completing the repair service, recharge the cycle with the specified amount of liquid refrigerant.
[3] Refrigerant recharging
(1) Refrigerant recharging process
1Direct charging from the cylinder.
·R407C cylinder are available on the market has a syphon pipe.
·Leave the syphon pipe cylinder standing and recharge it. (By liquid refrigerant)
(2) Recharge in refrigerant leakage case
·After recovering the all refrigerant in the unit, proceed to working.
·Do not release the refrigerant in the air.
·After completing the repair service, recharge the cycle with the specified amount of liquid refrigerant.
3
Page 4
2
Air outlet
Air intake
Oil filter (Air intake)
w It prevents oil from getting into the unit.
Left/right guide vanes
Change the direction of airflow from the horizontal blower.
Up/down guide vanes
Change the direction of airflow from the vartical blower.
PAR-20MAA
ON/OFF
CENTRALLY CONTROLLED
ERROR CODE
CLOCK
ON OFF
˚C
CHECK
CHECK MODE
FILTER
TEST RUN FUNCTION
˚C
1Hr.
NOT AVAILABLE
STAND BY DEFROST
FILTER
CHECK TEST
TEMP.
TIMER SET
Press this button to switch the cooler, electronic dry (dehumidify), automatic and heater modes.
OPERATION SWITCH button
This sets the room temperature. The temperature setting can be performed in 1: units Setting range Cooler 19: to 30: Heater 17: to 28:
TEMP. ADJUSTMENT button
This switches between continuous operation and the timer operation.
TIMER button
This switches between the operation and stop modes each time it is pressed. The lamp on this button lights during operation.
ON/OFF button
Only press this button to perform an inspection check or test operation. Do not use it for normal operation.
CHECK-TEST RUN button
This switch the horizontal fan motion ON and OFF.
(Not available for this model.)
LOUVER button
This sets the ventilation fan speed.
VENTILATION button
This adjusts the vertical angle of the ventilation.
AIR DIRECTION button
This resets the filter service indication display
FILTER button
This sets the current time, start time and stop time.
TIME SETTING button
This sets the ventilation fan speed.
AIR SPEED button
PART NAMES AND FUNCTIONS
Indoor (Main) Unit
Remote controller
Once the controls are set, the same operation mode can be repeated by simply pressing the ON/OFF button.
Operation buttons
4
Page 5
PAR-20MAA
ON/OFF
CENTRALLY CONTROLLED
ERROR CODE
CLOCK
ON OFF
˚C
CHECK
CHECK MODE
FILTER
TEST RUN FUNCTION
˚C
1Hr.
NOT AVAILABLE
STAND BY DEFROST
FILTER
CHECK TEST
TEMP.
TIMER SET
Display
CENTRALLY CONTROLLED display
This indicates when the unit is con­trolled by optional features such as central control type remote controller.
TIMER display
This indicates when the continuous operation and time operation modes are set. It also display the time for the timer operation at the same time as when it is set.
OPERATION MODE display
This indicates the operation mode.
STANDBY display
This indicates when the standby mode is set from the time the sleep operation starts until the heating air is discharged.
DEFROST display
This indicates when the defrost oper­ation is performed.
CLOCK display
The current time , start time and stop time can be displayed in ten second intervals by pressing the time switch button. The start time or stop time is always displayed during the timer operation.
In this display example on the bot­tom left, a condition where all dis­play lamps light is shown for expla­nation purposes although this differs from actual operation.
AIR DIRECTION display
This displays the air direction.
FAN SPEED display
The selected fan speed is displayed.
ROOM TEMPERATURE display
The temperature of the suction air is displayed during operation. The dis­play range is 8° to 39°C. The display flashes 8°C when the actual temper­ature is less than 8° and flashes 39°C when the actual temperature is greater than 39°C.
Operation lamp
This lamp lights during operation, goes off when the unit stops and flashes when a malfunction occurs.
CHECK MODE
TEST RUN
This display lights in the check mode or when a test operation is per­formed.
display
CHECK display
This indicates when a malfunction has occurred in the unit which should be checked.
SET TEMPERATURE display
This displays the selected setting temperature.
FILTER
This lamp lights when the filter need to be cleaned.
POWER display
This lamp lights when electricity is supplied to the unit.
display
Caution
Only the Power display lights when the unit is stopped and power supplied to the unit.
When power is turned ON for the first time the (CENTRAL CTRL) display appears to go off momentarily but this is not a
malfunction.
When the central control remote control unit, which is sold separately, is used the ON-OFF button, operation switch button and TEMP. adjustment button do not operate.
“NOT AVAILABLE” is displayed when the Air speed button are pressed.This indicates that this room unit is not equipped with the fan direction adjustment function and the louver function.
When power is turned ON for the first time, it is normal that “H0” is displayed on the room temperature indication (For max. 2minutes). Please wait until this “H0” indication disappear then start the operation.
5
Page 6
3
Service Ref.
Item
Btu/h
W
kW
kW
A A
kW
K/min(CFM)
Pa(mmAq)
dB mm(in.) mm(in.) mm(in.) mm(in.)
kg(lbs)
A A
kW
W
kW
K
/min(CFM
)
dB
dB mm(in.) mm(in.) mm(in.)
kg(lbs) kg(lbs)
L mm(in.) mm(in.)
Function Capacity
Total input
Service Ref.
Power supply
Input Running current
Starting current External finish Heat exchanger Fan Fan(drive) x No.
Fan motor output
Airflow(Lo-Hi)
External static pressure Operation control & Thermostat Noise level(Lo-Hi) Unit drain pipe I.D. Dimensions
Weight
Service Ref.
Power supply
Running current
Starting current External finish Refrigerant control Compressor
Model
Motor output
Starter type
Protection devices Crankcase heater
Heat exchanger Fan Fan(drive) x No.
Fan motor output
Airflow Defrost method Noise level
Dimensions
Weight Refrigerant
Charge
Oil (Model) Pipe size O.D.
Connection method Between the indoor &
outdoor unit
PCA-P3HA
Cooling
25,600
7,500
3.36
0.09
0.43
0.86
14.83 / 4.96
Heating
31,400
9,200
3.41
0.09
0.43
0.86
14.85/ 5.04
W
D H
Cooling Heating
W
D H
Liquid
Gas Indoor side Outdoor side Height difference Piping length
PCA-P3HA
Single phase, 50Hz, 220-230-240V
Stainless steel
Plate fin coil
Sirocco (direct) x 2
0.04
17-19 <600-670>
0 (direct blow)
Remote controller & built-in
34-38
26(1)
1,136(44-3/4)
650(25-5/8)
280(11)
41(90)
PUH-P3VGAA
1.UK / PUH-P3YGAA1.UK
Single phase, 50Hz, 220-230-240V / 3 phase, 50Hz, 380-400-415V (4wires)
93 / 47
Munsell 5Y 7/1
Linear Expansion Valve
Hermetic
NE52VNJMT / NE52YDKMT
2.5
Line start
38
Plate fin coil
Propeller (direct) x 1
0.070
50(1,770)
Reverse cycle
49 51
900(35-7/16)
330+20(13+3/4)
855(33-5/8)
79(174)
R407C
3.3(7.3)
1.3 (Ester) MEL56
9.52(3/8)
15.88(5/8) Flared Flared
Max. 50m Max. 50m
Inner thermostat,
HP switch, Discharge thermo.
Anti-phase protector, Thermal relay,
HP switch, Discharge thermo.
Notes1. Rating Conditions (ISO T1)
Cooling : Indoor : D.B. 27˚C(80˚F), W.B. 19˚C (66˚F) Outdoor : D.B. 35˚C(95˚F), W.B. 24˚C (75˚F) Heating : Indoor : D.B. 20˚C(68˚F) Outdoor : D.B. 7˚C(45˚F), W.B. 6˚C (43˚F) Refrigerant piping length (one way) : 5m (16ft)
2. Guaranteed operating range
3. Above data based on indicated voltage Indoor Unit Single phase 230V 50Hz Outdoor Unit Single phase 230V 50Hz / 3 phase 400V 50Hz
Upper limit Lower limit Upper limit Lower limit
Indoor D.B. 35˚C, W.B. 22.5˚C D.B. 19˚C, W.B. 15˚C
D.B. 28˚C D.B. 17˚C
Outdoor
D.B. 46˚C
D.B. -5˚C
D.B. 24˚C, W.B. 18˚C
D.B. -11˚C, W.B. -12˚C
Cooling
Heating
OUTDOOR UNIT INDOOR UNIT
REFRIGERANT PIPING
SPECIFICATIONS
1. Heat pump type Rating Conditions (ISO T1)
6
Page 7
Rating Conditions (ISO T1)
Service Ref.
Item
Btu/h
W
kW
kW
A A
kW
K/min(CFM)
Pa(mmAq)
dB mm(in.) mm(in.) mm(in.) mm(in.)
kg(lbs)
A A
kW
W
kW
K
/min(CFM
)
dB
dB mm(in.) mm(in.) mm(in.)
kg(lbs) kg(lbs)
L mm(in.) mm(in.)
Function Capacity
Total input
Service Ref.
Power supply
Input Running current
Starting current External finish Heat exchanger Fan Fan(drive) x No.
Fan motor output
Airflow(Lo-Hi)
External static pressure Operation control & Thermostat Noise level(Lo-Hi) Unit drain pipe I.D. Dimensions
Weight
Service Ref.
Power supply
Running current
Starting current External finish Refrigerant control Compressor
Model
Motor output
Starter type
Protection devices Crankcase heater Heat exchanger Fan Fan(drive) x No.
Fan motor output
Airflow Defrost method Noise level
Dimensions
Weight Refrigerant
Charge
Oil (Model) Pipe size O.D.
Connection method Between the indoor &
outdoor unit
PCA-P5HA
Cooling
44,400 13,000
4.90
0.26
1.19
2.38
6.85
Heating
54,600 16,000
4,98
0.26
1.19
2.38
7.07
W
D H
Cooling Heating
W
D H
Liquid
Gas Indoor side Outdoor side Height difference Piping length
PCA-P5HA
Single phase, 50Hz, 220-230-240V
Stainless steel
Plate fin coil
Sirocco (direct) x 4
0.08+0.08
30-38 <1,060-1,350>
0 (direct blow)
Remote controller & built-in
44-50
26(1)
1,520(59-7/8)
650(25-5/8)
280(11) 56(124)
PUH-P5YGAA
1.UK
3 phase, 50Hz, 380-400-415V (4wires)
65.5
Munsell 5Y 7/1
Linear Expansion Valve
Hermetic
ZR61KCW-TFD
3.5
Line start
Anti-phase protector, Internal thermostat, HP switch,Thermal relay, Discharge thermo
38
Plate fin coil
Propeller (direct) x 2
0.070+0.070 95(3,360)
Reverse cycle
55 56
1,050(41-5/16)
330+20(13+3/4)
1,260(49-5/8)
112(247)
R407C
4.6(10.1)
1.690 (Ester) 3MAW-POE
9.52(3/8)
19.05(3/4) Flared Flared
Max. 50m Max. 50m
Notes1. Rating Conditions (ISO T1)
Cooling : Indoor : D.B. 27˚C(80˚F), W.B. 19˚C (66˚F) Outdoor : D.B. 35˚C(95˚F), W.B. 24˚C (75˚F) Heating : Indoor : D.B. 20˚C(68˚F) Outdoor : D.B. 7˚C(45˚F), W.B. 6˚C (43˚F) Refrigerant piping length (one way) : 5m (16ft)
2. Guaranteed operating range
3. Above data based on indicated voltage Indoor Unit Single phase 230V 50Hz Outdoor Unit 3 phase 400V 50Hz
Upper limit Lower limit Upper limit Lower limit
Indoor D.B. 35˚C, W.B. 22.5˚C D.B. 19˚C, W.B. 15˚C
D.B. 28˚C D.B. 17˚C
Outdoor D.B. 46˚C D.B. -5˚C
D.B. 24˚C, W.B. 18˚C D.B. -11˚C, W.B. -12˚C
Cooling
Heating
OUTDOOR UNIT INDOOR UNIT
REFRIGERANT PIPING
7
Page 8
OUTDOOR UNIT
REFRIGERANT
PIPING
Service Ref.
Power supply
External finish Heat exchanger Fan
Operation control & Thermostat Noise level(Lo-Hi) Unit drain pipe I.D. Dimensions
Weight
Service Ref.
Power supply
External finish Refrigerant control Compressor
Crankcase heater Heat exchanger Fan
Defrost method Noise level Dimensions
Weight Refrigerant
Pipe size O.D.
Connection method
Between the indoor & outdoor unit
Indoor side Outdoor side Height difference Piping length
Liquid
Gas
Cooling
W
D H
Input Running current Starting current
Fan(drive))No. Fan motor output Airflow(Lo-Hi) External static pressure
Running current Starting current
Model Motor output Starter type Protection devices
Fan(drive))No. Fan motor output Airflow
Charge Compressor oil (Model)
W
D H
Item
Service Ref.
PCA-P3HA
Function
Total input
2. Guaranteed operating range Upper limit Lower limit
Indoor
D.B. 35:, D.B. 22.5:
D.B. 19:, D.B. 15:
Outdoor
D.B. 46:
D.B. -5:
Cooling
INDOOR UNIT
Cooling
25,600
7,500
3.36
PCA-P3HA
Single phase, 50Hz, 220-230-240V
0.09
0.41
0.86
Stainless steel
Plate fin coil
Sirocco (direct) 2
0.04
17-19 <600-670>
0 (direct blow)
Remote controller & built-in
34-38
26(1)
1,136(44-3/4)
650(25-5/8)
280(11)
41(90)
PU-P3VGAA
1.UK / PU-P3YGAA1.UK
Single-phase, 50Hz, 220-230-240V / 3-phase, 50Hz, 380-400-415V (4wires)
14.02 / 4.78 93 / 47
Munsell 5Y 7/1
Linear Expansion Valve
Hermetic
NE52VNJMT / NE52YDKMT
2.5
Line start
38
Plate fin coil
Propeller (direct) 1
0.070
50(1,770)
— 49
900(35-7/16)
330+20(13+3/4)
855(33-5/8)
79(174)
R407C
3.3(7.3)
1.3 (Ester) MEL56
9.52(3/8)
15.88(5/8) Flared Flared
Max. 50m Max. 50m
Btu/h
W
kW
kW
A A
kW
K/min <CFM>
Pa(mmAq)
dB mm(in.) mm(in.) mm(in.) mm(in.)
kg(lbs)
A A
KW
W
kW
K/min <CFM>
dB mm(in.) mm(in.) mm(in.)
kg(lbs)
kg(lbs)
L mm(in.) mm(in.)
Anti-phase protector, Thermal relay,
HP switch, Discharge thermo
Inner thermostat,
HP switch, Discharge thermo
Capacity
Rating Conditions (ISO T1)
Notes1. Rating Conditions (ISO T1)
Cooling : Indoor : D.B. 27:(80°F), W.B. 19:(66°F)
Outdoor : D.B. 35:(95°F), W.B. 24:(75°F)
Refrigerant piping length (one way) : 5m(16ft)
3. Above data based on indicated voltage Indoor Unit Single phase 230V 50Hz Outdoor Unit Single phase 230V 50Hz / 3 phase 400V 50Hz
8
Page 9
Rating Conditions (ISO T1)
OUTDOOR UNIT
REFRIGERANT
PIPING
Service Ref.
Power supply
External finish Heat exchanger Fan
Operation control & Thermostat Noise level(Lo-Hi) Unit drain pipe I.D. Dimensions
Weight
Service Ref.
Power supply
External finish Refrigerant control Compressor
Crankcase heater Heat exchanger Fan
Defrost method Noise level Dimensions
Weight Refrigerant
Pipe size O.D.
Connection method
Between the indoor & outdoor unit
Indoor side Outdoor side Height difference Piping length
Liquid
Gas
Cooling
W
D H
Input Running current Starting current
Fan(drive))No. Fan motor output Airflow(Lo-Hi) External static pressure
Running current Starting current
Model Motor output Starter type Protection devices
Fan(drive))No. Fan motor output Airflow
Charge Compressor oil (Model)
W
D H
Item
Service Ref.
PCA-P5HA
Function
Total input
Upper limit Lower limit
Indoor
D.B. 35:, D.B. 22.5:
D.B. 19:, D.B. 15:
Outdoor
D.B. 46:
D.B. -5:
Cooling
INDOOR UNIT
Cooling
44,400 13,000
4.90
PCA-P5HA
Single phase, 50Hz, 220-230-240V
0.26
1.19
2.38
Stainless steel
Plate fin coil
Sirocco (direct) 4
0.08+0.08
30-38 <1,060-1,350>
0 (direct blow)
Remote controller & built-in
44-50 26(1)
1,520(59-7/8)
650(25-5/8)
280(11) 56(124)
PU-P5YGAA
1.UK
3-phase, 50Hz, 380-400-415V (4wires)
6.85
65.5
Munsell 5Y 7/1
Linear Expansion Valve
Hermetic
ZR61KCW-TFD
3.5
Line start
Anti-phase protector, Internal thermostat, HP switch, Thermal relay, Discharge thermo
38
Plate fin coil
Propeller (direct) 2
0.070+0.070 95(3,360)
— 55
1,050(41-5/16)
330+20(13+3/4)
1,260(49-5/8)
112(247)
R407C
4.6(10.1)
1.690 (Ester) 3MAW-POE
9.52(3/8)
19.05(3/4) Flared Flared
Max. 50m Max. 50m
Btu/h
W
kW
kW
A A
kW
K/min <CFM>
Pa(mmAq)
dB mm(in.) mm(in.) mm(in.) mm(in.)
kg(lbs)
A A
KW
W
kW
K/min <CFM>
dB mm(in.) mm(in.) mm(in.)
kg(lbs)
kg(lbs)
L mm(in.) mm(in.)
2. Guaranteed operating range
Capacity
Notes1. Rating Conditions (ISO T1)
Cooling : Indoor : D.B. 27:(80°F), W.B. 19:(66°F) Refrigerant piping length (one way) : 5m(16ft)
3. Above data based on indicated voltage Indoor Unit Single phase 230V 50Hz Outdoor Unit 3 phase 400V 50Hz
Outdoor : D.B. 35:(95°F), W.B. 24:(75°F)
9
Page 10
4 DATA
Outdoor intake air D.B.(°C)
20 25 30
Indoor
Intake air
D.B.(°C)
Indoor
Intake air
W.B.(°C) 20 20 20 22 22 22 24 24 24 26 26 26 28 28 28 30 30 30 32 32 32 34 34 34
16 18 20 16 18 20 16 18 20 16 18 20 16 18 20 16 18 20 16 18 20 16 18 20
CA 7,425 7,950 8,550 7,425 7,950 8,550 7,425 7,950 8,550 7,425 7,950 8,550 7,425 7,950 8,550 7,425 7,950 8,550 7,425 7,950 8,550 7,425 7,950 8,550
SHC(W)
4,604 3,975 3,249 5,198 4,611 3,933 5,792 5,247 4,617 6,386 5,883 5,301 6,980 6,519 5,985 7,425 7,155 6,669 7,425 7,791 7,353 7,425 7,950 8,037
SHF
0.62
0.50
0.38
0.70
0.58
0.46
0.78
0.66
0.54
0.86
0.74
0.62
0.94
0.82
0.70
1.00
0.90
0.78
1.00
0.98
0.86
1.00
1.00
0.94
P.C.
2.69
2.74
2.82
2.69
2.74
2.82
2.69
2.74
2.82
2.69
2.74
2.82
2.69
2.74
2.82
2.69
2.74
2.82
2.69
2.74
2.82
2.69
2.74
2.82
CA 7,200 7,725 8,363 7,200 7,725 8,363 7,200 7,725 8,363 7,200 7,725 8,363 7,200 7,725 8,363 7,200 7,725 8,363 7,200 7,725 8,363 7,200 7,725 8,363
SHC(W)
4,464 3,863 3,178 5,040 4,481 3,847 5,616 5,099 4,516 6,192 5,717 5,185 6,768 6,335 5,854 7,200 6,953 6,523 7,200 7,571 7,192 7,200 7,725 7,861
SHF
0.62
0.50
0.38
0.70
0.58
0.46
0.78
0.66
0.54
0.86
0.74
0.62
0.94
0.82
0.70
1.00
0.90
0.78
1.00
0.98
0.86
1.00
1.00
0.94
P.C.
2.84
2.89
2.96
2.84
2.89
2.96
2.84
2.89
2.96
2.84
2.89
2.96
2.84
2.89
2.96
2.84
2.89
2.96
2.84
2.89
2.96
2.84
2.89
2.96
CA 6,975 7,463 8,138 6,975 7,463 8,138 6,975 7,463 8,138 6,975 7,463 8,138 6,975 7,463 8,138 6,975 7,463 8,138 6,975 7,463 8,138 6,975 7,463 8,138
SHC(W)
4,325 3,731 3,092 4,883 4,328 3,743 5,441 4,925 4,394 5,999 5,522 5,045 6,557 6,119 5,696 6,975 6,716 6,347 6,975 7,313 6,998 6,975 7,463 7,649
SHF
0.62
0.50
0.38
0.70
0.58
0.46
0.78
0.66
0.54
0.86
0.74
0.62
0.94
0.82
0.70
1.00
0.90
0.78
1.00
0.98
0.86
1.00
1.00
0.94
P.C.
3.01
3.09
3.16
3.01
3.09
3.16
3.01
3.09
3.16
3.01
3.09
3.16
3.01
3.09
3.16
3.01
3.09
3.16
3.01
3.09
3.16
3.01
3.09
3.16
1. PERFORMANCE DATA (240V)
1) COOLING CAPACITY<1> PCA-P3HA
Notes CA : Capacity (W) SHC(W) : Sensible heat capacity
P.C. : Power consumption (kW) SHF : Sensible heat factor
10
Page 11
COOLING CAPACITY<2> PCA-P3HA
Indoor
Intake air
D.B.(°C)
20 20 20 22 22 22 24 24 24 26 26 26 28 28 28 30 30 30 32 32 32 34 34 34
Indoor
Intake air
W.B.(°C)
16 18 20 16 18 20 16 18 20 16 18 20 16 18 20 16 18 20 16 18 20 16 18 20
CA 6,675 7,200 7,800 6,675 7,200 7,800 6,675 7,200 7,800 6,675 7,200 7,800 6,675 7,200 7,800 6,675 7,200 7,800 6,675 7,200 7,800 6,675 7,200 7,800
Outdoor intake air D.B.(°C)
35 40 45
SHC(W)
4,139 3,600 2,964 4,673 4,176 3,588 5,207 4,752 4,212 5,741 5,328 4,836 6,275 5,904 5,460 6,675 6,480 6,084 6,675 7,056 6,708 6,675 7,200 7,332
SHF
0.62
0.50
0.38
0.70
0.58
0.46
0.78
0.66
0.54
0.86
0.74
0.62
0.94
0.82
0.70
1.00
0.90
0.78
1.00
0.98
0.86
1.00
1.00
0.94
P.C.
3.23
3.31
3.39
3.23
3.31
3.39
3.23
3.31
3.39
3.23
3.31
3.39
3.23
3.31
3.39
3.23
3.31
3.39
3.23
3.31
3.39
3.23
3.31
3.39
CA 6,375 6,975 7,500 6,375 6,975 7,500 6,375 6,975 7,500 6,375 6,975 7,500 6,375 6,975 7,500 6,375 6,975 7,500 6,375 6,975 7,500 6,375 6,975 7,500
SHC(W)
3,953 3,488 2,850 4,463 4,046 3,450 4,973 4,604 4,050 5,483 5,162 4,650 5,993 5,720 5,250 6,375 6,278 5,850 6,375 6,836 6,450 6,375 6,975 7,050
SHF
0.62
0.50
0.38
0.70
0.58
0.46
0.78
0.66
0.54
0.86
0.74
0.62
0.94
0.82
0.70
1.00
0.90
0.78
1.00
0.98
0.86
1.00
1.00
0.94
P.C.
3.46
3.56
3.63
3.46
3.56
3.63
3.46
3.56
3.63
3.46
3.56
3.63
3.46
3.56
3.63
3.46
3.56
3.63
3.46
3.56
3.63
3.46
3.56
3.63
6,075 6,525 7,050 6,075 6,525 7,050 6,075 6,525 7,050 6,075 6,525 7,050 6,075 6,525 7,050 6,075 6,525 7,050 6,075 6,525 7,050 6,075 6,525 7,050
CA
SHC(W)
3,767 3,263 2,679 4,253 3,785 3,243 4,739 4,307 3,807 5,225 4,829 4,371 5,711 5,351 4,935 6,075 5,873 5,499 6,075 6,395 6,063 6,075 6,525 6,627
SHF
0.62
0.50
0.38
0.70
0.58
0.46
0.78
0.66
0.54
0.86
0.74
0.62
0.94
0.82
0.70
1.00
0.90
0.78
1.00
0.98
0.86
1.00
1.00
0.94
P.C.
3.75
3.83
3.90
3.75
3.83
3.90
3.75
3.83
3.90
3.75
3.83
3.90
3.75
3.83
3.90
3.75
3.83
3.90
3.75
3.83
3.90
3.75
3.83
3.90
Notes CA : Capacity (W) SHC(W) : Sensible heat capacity
P.C. : Power consumption (kW) SHF : Sensible heat factor
11
Page 12
Outdoor intake air D.B.(°C)
20 25 30
Indoor
Intake air
D.B.(°C)
Indoor
Intake air
W.B.(°C) 20 20 20 22 22 22 24 24 24 26 26 26 28 28 28 30 30 30 32 32 32 34 34 34
16 18 20 16 18 20 16 18 20 16 18 20 16 18 20 16 18 20 16 18 20 16 18 20
CA 12,870 13,780 14,820 12,870 13,780 14,820 12,870 13,780 14,820 12,870 13,780 14,820 12,870 13,780 14,820 12,870 13,780 14,820 12,870 13,780 14,820 12,870 13,780 14,820
SHC(W)
8,366 7,303 6,076 9,395 8,406 7,262
10,425
9,508
8,447 11,454 10,611
9,633 12,484 11,713 10,819 12,870 12,815 12,004 12,870 13,780 13,190 12,870 13,780 14,375
SHF
0.65
0.53
0.41
0.73
0.61
0.49
0.81
0.69
0.57
0.89
0.77
0.65
0.97
0.85
0.73
1.00
0.93
0.81
1.00
1.00
0.89
1.00
1.00
0.97
P.C.
3.92
3.99
4.12
3.92
3.99
4.12
3.92
3.99
4.12
3.92
3.99
4.12
3.92
3.99
4.12
3.92
3.99
4.12
3.92
3.99
4.12
3.92
3.99
4.12
CA 12,480 13,390 14,495 12,480 13,390 14,495 12,480 13,390 14,495 12,480 13,390 14,495 12,480 13,390 14,495 12,480 13,390 14,495 12,480 13,390 14,495 12,480 13,390 14,495
SHC(W)
8,112 7,097 5,943 9,110 8,168 7,103
10,109
9,239
8,262 11,107 10,310
9,422 12,106 11,382 10,581 12,480 12,453 11,741 12,480 13,390 12,901 12,480 13,390 14,060
SHF
0.65
0.53
0.41
0.73
0.61
0.49
0.81
0.69
0.57
0.89
0.77
0.65
0.97
0.85
0.73
1.00
0.93
0.81
1.00
1.00
0.89
1.00
1.00
0.97
P.C.
4.14
4.21
4.31
4.14
4.21
4.31
4.14
4.21
4.31
4.14
4.21
4.31
4.14
4.21
4.31
4.14
4.21
4.31
4.14
4.21
4.31
4.14
4.21
4.31
CA 12,090 12,935 14,105 12,090 12,935 14,105 12,090 12,935 14,105 12,090 12,935 14,105 12,090 12,935 14,105 12,090 12,935 14,105 12,090 12,935 14,105 12,090 12,935 14,105
SHC(W)
7,859 6,856 5,783 8,826 7,890 6,911 9,793 8,925 8,040
10,760
9,960
9,168 11,727 10,995 10,297 12,090 12,030 11,425 12,090 12,935 12,553 12,090 12,935 13,682
SHF
0.65
0.53
0.41
0.73
0.61
0.49
0.81
0.69
0.57
0.89
0.77
0.65
0.97
0.85
0.73
1.00
0.93
0.81
1.00
1.00
0.89
1.00
1.00
0.97
P.C.
4.39
4.51
4.61
4.39
4.51
4.61
4.39
4.51
4.61
4.39
4.51
4.61
4.39
4.51
4.61
4.39
4.51
4.61
4.39
4.51
4.61
4.39
4.51
4.61
COOLING CAPACITY<3> PCA-P5HA
Notes CA : Capacity (W) SHC(W) : Sensible heat capacity
P.C. : Power consumption (kW) SHF : Sensible heat factor
12
Page 13
COOLING CAPACITY<4> PCA-P5HA
Indoor
Intake air
D.B.(°C)
20 20 20 22 22 22 24 24 24 26 26 26 28 28 28 30 30 30 32 32 32 34 34 34
Indoor Intake air W.B.(°C)
16 18 20 16 18 20 16 18 20 16 18 20 16 18 20 16 18 20 16 18 20 16 18 20
CA 11,570 12,480 13,520 11,570 12,480 13,520 11,570 12,480 13,520 11,570 12,480 13,520 11,570 12,480 13,520 11,570 12,480 13,520 11,570 12,480 13,520 11,570 12,480 13,520
Outdoor intake air D.B.(°C)
35 40 45
SHC(W)
7,521 6,614 5,543 8,446 7,613 6,625 9,372 8,611 7,706
10,297
9,610
8,788 11,223 10,608
9,870 11,570 11,606 10,951 11,570 12,480 12,033 11,570 12,480 13,114
SHF
0.65
0.53
0.41
0.73
0.61
0.49
0.81
0.69
0.57
0.89
0.77
0.65
0.97
0.85
0.73
1.00
0.93
0.81
1.00
1.00
0.89
1.00
1.00
0.97
P.C.
4.70
4.83
4.95
4.70
4.83
4.95
4.70
4.83
4.95
4.70
4.83
4.95
4.70
4.83
4.95
4.70
4.83
4.95
4.70
4.83
4.95
4.70
4.83
4.95
CA 11,050 12,090 13,000 11,050 12,090 13,000 11,050 12,090 13,000 11,050 12,090 13,000 11,050 12,090 13,000 11,050 12,090 13,000 11,050 12,090 13,000 11,050 12,090 13,000
SHC(W)
7,183 6,408 5,330 8,067 7,375 6,370 8,951 8,342 7,410 9,835 9,309
8,450 10,719 10,277
9,490 11,050 11,244 10,530 11,050 12,090 11,570 11,050 12,090 12,610
SHF
0.65
0.53
0.41
0.73
0.61
0.49
0.81
0.69
0.57
0.89
0.77
0.65
0.97
0.85
0.73
1.00
0.93
0.81
1.00
1.00
0.89
1.00
1.00
0.97
P.C.
5.05
5.19
5.29
5.05
5.19
5.29
5.05
5.19
5.29
5.05
5.19
5.29
5.05
5.19
5.29
5.05
5.19
5.29
5.05
5.19
5.29
5.05
5.19
5.29
10,530 11,310 12,220 10,530 11,310 12,220 10,530 11,310 12,220 10,530 11,310 12,220 10,530 11,310 12,220 10,530 11,310 12,220 10,530 11,310 12,220 10,530 11,310 12,220
CA
SHC(W)
6,845 5,994 5,010 7,687 6,899 5,988 8,529 7,804 6,965 9,372 8,709 7,943
10,214
9,614
8,921 10,530 10,518
9,898 10,530 11,310 10,876 10,530 11,310 11,853
SHF
0.65
0.53
0.41
0.73
0.61
0.49
0.81
0.69
0.57
0.89
0.77
0.65
0.97
0.85
0.73
1.00
0.93
0.81
1.00
1.00
0.89
1.00
1.00
0.97
P.C.
5.46
5.59
5.68
5.46
5.59
5.68
5.46
5.59
5.68
5.46
5.59
5.68
5.46
5.59
5.68
5.46
5.59
5.68
5.46
5.59
5.68
5.46
5.59
5.68
Notes CA : Capacity (W) SHC(W) : Sensible heat capacity
P.C. : Power consumption (kW) SHF : Sensible heat factor
13
Page 14
Refrigerant piping length (one way)
Service Ref.
5m 10m 15m 20m 25m 30m 35m 40m 45m 50m
PCA-P3HA PCA-P5HA
1.00
1.00
0.981
0.981
0.968
0.968
0.952
0.952
0.940
0.940
0.925
0.925
0.913
0.913
0.900
0.900
0.886
0.886
0.874
0.874
Cooling capacity correction factors
OUTDOOR D.B.(°C)
TOTAL INPUT (RATIO) CAPACITY (RATIO)
INDOOR W.B.(°C)
INDOOR W.B.(°C)
1.4
1.2
1.0
0.8
10
22 20 18 16
22
20 18
16
20 30 46400-5
1.2
1.0
0.8
0.6
0.4
Cooling
14
Page 15
Refrigerant piping length (one way)
Service Ref.
5m 10m 15m 20m 25m 30m 35m 40m 45m 50m
PCA-P3HA PCA-P5HA
1.00
1.00
0.998
0.998
0.995
0.995
0.993
0.993
0.990
0.990
0.988
0.988
0.985
0.985
0.983
0.983
0.980
0.980
0.978
0.978
2) HEATING CAPACITY
Service Ref.
15 20 25 15 20 25
CA
-10 -5 0 5 10 15
Outdoor intake air W.B.(°C)Indoor
Intake
air
D.B.(°C)
P.C.
2.01
2.18
2.32
2.94
3.19
3.39
CA P.C. CA P.C. CA P.C. CA P.C. CA P.C. 5,842 5,612 5,428
10,160
9,760 9,440
2.22
2.39
2.59
3.24
3.49
3.78
6,348 6,072
5,888 11,040 10,560 10,240
2.56
2.76
3.00
3.74
4.03
4.38
7,084 6,716
6,440 12,320 11,680 11,200
3.07
3.31
3.51
4.48
4.83
5.13
9,292 8,970
8,464 16,160 15,600 14,720
3.41
3.68
3.94
4.98
5.38
5.75
10,488 10,120
9,752 18,240 17,600 16,960
3.68
3.96
4.25
5.38
5.78
6.20
11,684 11,270 10,856 20,320 19,600 18,880
PCA-P3HA
PCA-P5HA
Notes CA : Capacity (W)
P.C. : Power consumption (kW)
Heating capacity correction factors
Heating
Correcting the capacity line influenced by frosting. Not correcting the capacity line influenced by frosting.
1.4
1.2
15 20
INDOOR D.B. (°C)
25
1.0
0.8
0.6
0.4
1.4
1.2
1.0
0.8
0.6
TOTAL INPUT (RATIO) CAPACITY (RATIO)
0.4
-12 -10 -5 0 5 10 15
OUTDOOR W.B. (°C)
INDOOR D.B. (°C)
25 20
15
15
Page 16
2. ELECTRICAL DATA
Indoor
Outdoor
Input (kW) Current (A) Current (A) Starting current (A)
Mode Capacity (W) Total Input (kW) (In + Out)
Service
Ref.
Indoor unit Outdoor unit
Cooling
7,500
3.36
0.09
0.44
15.31 85
Heating
9,200
3.41
0.09
0.44
15.54 85
Cooling
7,500
3.36
0.09
0.44
5.23 43
Heating
9,200
3.41
0.09
0.44
5.32 43
Cooling
13,000
4.90
0.26
1.24
7.22
65.5
Heating
16,000
4.98
0.26
1.24
7.46
65.5
PUH-P3VGAA1.UK PUH-P3YGAA1.UK PUH-P5YGAA1.UK
PCA-P3HA PCA-P5HA
Cooling
13,000
4.90
0.26
1.19
6.85
65.5
Heating
16,000
4.98
0.26
1.19
7.07
65.5
PUH-P5YGAA1.UK
PCA-P5HA
Cooling
13,000
4.90
0.27
1.14
6.61
65.5
Heating
16,000
4.98
0.27
1.14
6.82
65.5
PUH-P5YGAA1.UK
PCA-P5HA
Indoor
Outdoor
Input (kW) Current (A) Current (A) Starting current (A)
Mode Capacity (W) Total Input (kW) (In + Out)
Service
Ref.
Indoor unit Outdoor unit
Cooling
7,500
3.36
0.09
0.43
14.63 89
Heating
9,200
3.41
0.09
0.43
14.85 89
Cooling
7,500
3.36
0.09
0.43
4.96 45
Heating
9,200
3.41
0.09
0.43
5.04 45
PUH-P3VGAA1.UK PUH-P3YGAA1.UK
PCA-P3HA
Indoor
Outdoor
Input (kW) Current (A) Current (A) Starting current (A)
Mode Capacity (W) Total Input (kW) (In + Out)
Service
Ref.
Indoor unit Outdoor unit
Cooling
7,500
3.36
0.09
0.41
14.02 93
Heating
9,200
3.41
0.09
0.41
14.24 93
Cooling
7,500
3.36
0.09
0.41
4.78 47
Heating
9,200
3.41
0.09
0.41
4.86 47
PUH-P3VGAA1.UK PUH-P3YGAA1.UK
PCA-P3HA
Indoor·······220V 50Hz Single phase Outdoor····220V 50Hz Singel phase / 380V 50Hz 3 phase
Indoor·······230V 50Hz Single phase Outdoor····230V 50Hz Singel phase / 400V 50Hz 3 phase
Indoor·······240V 50Hz Single phase Outdoor····240V 50Hz Singel phase / 415V 50Hz 3 phase
2.1. Heat pump type Rating Conditions (ISO T1)
16
Page 17
2.2. Cooling only type
Indoor
Outdoor
Input (kW) Current (A) Current (A) Starting current (A)
Mode Capacity (W) Total Input (kW) (In + Out)
Service
Ref.
Indoor unit Outdoor unit
Cooling
7,500
3.36
0.09
0.44
15.31 85
Cooling
7,500
3.36
0.09
0.44
5.23 43
Cooling
13,000
4.90
0.26
1.24
7.22
65.5
PU-P3VGAA1.UK PU-P3YGAA1.UK PU-P5YGAA1.UK
PCA-P3HA PCA-P5HA
Indoor
Outdoor
Input (kW) Current (A) Current (A) Starting current (A)
Mode Capacity (W) Total Input (kW) (In + Out)
Service
Ref.
Indoor unit Outdoor unit
Cooling
7,500
3.36
0.09
0.43
14.63 89
Cooling
7,500
3.36
0.09
0.43
4.96 45
Cooling
13,000
4.90
0.26
1.19
6.85
65.5
PU-P3VGAA1.UK PU-P3YGAA1.UK PU-P5YGAA1.UK
PCA-P3HA PCA-P5HA
Indoor
Outdoor
Input (kW) Current (A) Current (A) Starting current (A)
Mode Capacity (W) Total Input (kW) (In + Out)
Service
Ref.
Indoor unit Outdoor unit
Cooling
7,500
3.36
0.09
0.41
14.02 93
Cooling
7,500
3.36
0.09
0.41
4.78 47
Cooling
13,000
4.90
0.26
1.14
6.61
65.5
PU-P3VGAA1.UK PU-P3YGAA1.UK PU-P5YGAA1.UK
PCA-P3HA PCA-P5HA
Indoor·······220V 50Hz Single phase Outdoor····220V 50Hz Singel phase / 380V 50Hz 3 phase
Indoor·······230V 50Hz Single phase Outdoor····230V 50Hz Singel phase / 400V 50Hz 3 phase
Indoor·······240V 50Hz Single phase Outdoor····240V 50Hz Singel phase / 415V 50Hz 3 phase
Rating Conditions (ISO T1)
17
Page 18
3. STANDARD OPERATION DATA
Electrical circuit Total Refrigerant circuitIndoor side
Outdoor
side
Capacity Input
Indoor unit Service Ref.
Phase, Hz Volts Amperes
Outdoor unit Service Ref.
Phase, Hz Volts Amperes Discharge pressure Suction pressure Discharge temperature Condensing temperature Suction temperature Ref. pipe length
Intake air temperature
Discharge air temperature
Intake air temperature
Mode
Service Ref.
SHF
BF
W
KW
V A
V A
°C °C °C
m
°C °C °C °C °C
Cooling
7,500
3.36
0.43
14.63/4.96
84 59
2.9 5
27 19 13 35 24
0.72
0.14
Heating
9,200
3.41
0.43
14.85/5.04
89 62
-0.7 5
20 15 47
7 6
— —
PCA-P3HA
1, 50
230
PUH-P3VGAA
1.UK
/PUH-P3YGAA
1.UK
1, 50/3, 50
230/400
2.31
(23.5)
0.45 (4.6)
2.43
(24.8)
0.39
(4.0)
MPa
(Of/F)
MPa
(Of/F)
D.B.
W.B.
D.B. D.B.
W.B.
PCA-P3HA
Cooling
13,000
4.90
1.19
6.85
73 54
4.8 5
27 19 15 35 24
0.72
0.19
Heating
16,000
4.98
1.19
7.07
73 55
-0.3 5
20 15 43
7 6
— —
PCA-P5HA
1, 50
230
PUH-P5YGAA
1.UK
3, 50
400
2.01
(20.5)
0.46 (4.6)
2.07
(21.1)
0.38 (3.8)
PCA-P5HA
3.1 Heat pump type Rating Conditions (ISO T1)
The unit of pressure has been changed to Mpa on the international system of unit (SI unit system). The converted score against the traditional unit system can be gotten according to the formula below.
1(Mpa)=10.2(
OOf/FF
)
18
Page 19
3.2 Cooling only type
Electrical circuit Total Refrigerant circuitIndoor side
Outdoor
side
Capacity Input
Indoor unit Service Ref.
Phase, Hz Volts Amperes
Outdoor unit Service Ref.
Phase, Hz Volts Amperes Discharge pressure Suction pressure Discharge temperature Condensing temperature Suction temperature Ref. pipe length
Intake air temperature
Discharge air temperature
Intake air temperature
Mode
Service Ref.
SHF
BF
W
KW
V A
V A
°C °C °C
m
°C °C °C °C °C
Cooling
7,500
3.36
PCA-P3HA
1, 50
230
0.43
PU-P3VGAA
1.UK
/PU-P3YGAA
1.UK
1, 50/3, 50
230/400
14.63/4.96
84 59
2.9 5
27 19 13 35 24
0.72
0.14
2.31
(23.5)
0.45 (4.6)
MPa
(Of/F)
MPa
(Of/F)
D.B.
W.B.
D.B. D.B.
W.B.
PCA-P3HA
Cooling
13,000
4.90
PCA-P5HA
1, 50
230
1.19
PU-P5YGAA
1.UK
3, 50
400
6.85
73 54
4.8 5
27 19 15 35 24
0.75
0.19
2.01
(20.5)
0.46
(4.6)
PCA-P5HA
Rating Conditions (ISO T1)
The unit of pressure has been changed to Mpa on the international system of unit (SI unit system). The converted score against the traditional unit system can be gotten according to the formula below.
1(Mpa)=10.2(OOf/FF)
4. OUTLET AIR SPEED AND COVERAGE RANGE
Air flow Air speed Coverage range
m3/min
m/sec
m
PCA-P3HA PCA-P5HA
19
2.9
7.9
13.2
38
4.2
19
Page 20
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
APPROXIMATE TERESHOLD OF HEARING FOR CONTINUOUS NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
PCA-P3HA
NOTCH
Hi
Lo
SPL(dB)
38 34
LINE
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
APPROXIMATE TERESHOLD OF HEARING FOR CONTINUOUS NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
PCA-P5HA
NOTCH
Hi
Lo
SPL(dB)
50 44
LINE
5. NOISE CRITERION CURVES
1m
1m
unit
about 1.4m
MICROPHONE
ceiling
20
Page 21
5
Ceiling
Less than
Less than
or more
Less than
or more
or more
300
<Suspension bolt pitch>
model:PAC-SG38KF-E (12pcs.)
Filter element for the exchange
1.Use M10 or W3/8 screw for anchor bolt.
NOTES.
Option parts:duct flange( [ 200). model: PAC-SF28OF-E(1 pcs.)
Knock out hole for wiring arrangement : 2- [ 27
(122)
<Filter contour dimension>
16
handle
100
1001136
366
480
176
318
650
<Flexible hose(accessory)>
Terminal block
9
Terminal block(remote controller)
8
Terminal block(indoor/outdoor connecting line)
78
Inspection port
(pipe sensor)
The half bottom of FAN CASING
can be separated.
Adjustable part
288
360
<Air outlet>
<Suspension bolt pitch>
<Air outlet>
<Air intake>
<Air intake>
Filter
Terminal block
5
2
1
4
3
Knock out hole for upper Refrigerant-pipe arrangement
6
9
2
1
Flexible hose(accessory)Drainage pipe connection(VP-25:pipe outside diameter [ 32)
2
Refrigerant-pipe connection(gas pipe side/flared connection : 5/8F)
38
105
85
90˚
Electrical box
Rear wall
500
250
2 ~ 3
(Gap to ceiling)
Allowing clearances
<gas> <liquid>
7
Knock out hole (duct for fresh air intake): 2- [ 200
6
5
1
3
4
Knock out hole for left Refrigerant-pipe arrangement
Refrigerant-pipe connection(liquid pipe side/flared connection : 3/8F)
Suspension bolt
130
210
45
165
120
1224
1180
75
1136
986
1098
70
243
254
175
197
110
21
130 15
258 110 102
320 80
90
14018
75
70~90
650
13
289
75
280
495
43
295
[222
[200
OUTLINES AND DIMENSIONS
PCA-P3HA
Unit : mm
21
Page 22
Ceiling
Less than
Less than
Less than
or more
or more
or more
4
3156728
9
Refrigerant-pipe connection(gas pipe side/flared connection : 5/8F)
Knock out hole (duct for fresh air intake) : 2- [ 200
Option parts:duct flange( [ 200). model: PAC-SF28OF-E(1 pcs.)
Flexible hose(accessory)Drainage pipe connection(VP-25 : pipe outside diameter [ 32)
Terminal block(indoor/outdoor connecting line)
Terminal block(remote controller)
Refrigerant-pipe connection(liquid pipe side/flared connection : 3/8F)
Knock out hole for left Refrigerant-pipe arrangement
Knock out hole for upper Refrigerant-pipe arrangement
Knock out hole for wiring arrangement : 2- [ 27
Allowing clearances
Rear wall
(Gap to ceiling)
NOTES.
1.Use M10 or W3/8 screw for anchor bolt.
model:PAC-SG38KF-E (12pcs.)
Filter element for the exchange
<Suspension bolt pitch>
(122)246
handle
16
<Flexible hose(accessory)>
Terminal block
78
<Filter contour dimension>
Inspection port
(pipe sensor)
The half bottom of FAN CASING
can be separated.
Adjustable part
288
360
<Air outlet>
<Suspension bolt pitch>
<Air outlet>
<Air intake>
<Air intake>
Filter
Terminal block
5
2
1
4
3
6
9
2
1
176
38 210
105
8545
165
[222
[200
440440298
130
90˚
650
300
1001520100
Electrical box
500
250
2~3
<gas> <liquid>
Suspension bolt
70
243
254
175
197
110
21
130 15
258
1482
110 102
1370 75
1608
320 801564
1520
90 120
14018
75
70~90
650
13
289
75
280
495
43
295
PCA-P5HA
Unit : mm
22
Page 23
6
J15
Service board
SW1
Manufacture
J14J13J12J11
4
OFF
ON
5321
PCA-P5HA
PCA-P3HA
1234
ON
OFF
Service board
MODELS
SW2
Manufacture
1234
ON
OFF
J24J23J22J21
J24J23J22J21
N
L
LEGEND
NAME
WHT
WHT
BLK
BLK
BLU
Symptom
Check code
Abnormality of room temperature thermistor(TH1). Abnormality of pipe temperature thermistor/Liquid(TH2). Freezing /overheating protection is working. Abnormality of pipe temperature. Abnormality of pipe temperature thermistor/ Condenser/Evaporator(TH5). Abnormality of the signal transmission between remote controller and indoor unit. Abnormality of the signal transmission between indoor unit and outdoor unit("EE" indicates abnormality of combination). Abnormality in outdoor unit. Refer to outdoor unit wiring diagram. Abnormality in outdoor unit. Refer to outdoor unit wiring diagram. No trouble generated in the past. No corresponding unit.
FFFF
----
F
U
E6—EF
E0—E5
P9
P8
P6
P2
P1
CONNECTING LINE)
SYMBOL
C1,C2
MF1,MF2 FAN MOTOR
CAPACITOR(FAN MOTOR)
CN2 TB6
TRANSMISSION LINE)
TERMINAL BLOCK(REMOTE CONTROLLER
CONNECTOR(PROGRAM TIMER)
REMOTE CONTROLLER BOARDR.B
(0˚C/15k, 25˚C/5.4k DETECT)
CONDENSER / EVAPORATOR TEMPERATUR THERMISTOR
TH5
(0˚C/15k, 25˚C/5.4k DETECT)
PIPE TEMPERATUR THERMISTOR/LIQUID
TH2
(0˚C/15k, 25˚C/5.4k DETECT)
ROOM TEMPERATUR THERMISTOR
TH1
TRANSMISSION LINE)
TB5
TERMINAL BLOCK(INDOOR/OUTDOOR
TB4
DEW PREVENTION HEATERH2
TERMINAL BLOCK(REMOTE CONTROLLER
SYMBOL NAME
X1 X4 X5 X6 RELAY(FAN MOTOR)
RELAY(FAN MOTOR)
RELAY(FAN MOTOR)
RELAY(DEW PREVENTION HEATER)
JUMPER WIRE(MODEL SELECTION) JUMPER WIRE(CAPACITY CODE) SWITCH(EMERGENCY OPERATION)
SWE
SW2
SW1
POWER SUPPLY(I.B) POWER SUPPLY(R.B) TRANSMISSION(INDOOR-OUTDOOR)
LED3
LED2
LED1
CONNECTOR(HA TERMINAL-A)CN41
CONNECTOR(REMOTE SWITCH)
CN32
CONNECTOR(LOSSNAY)CN2L
INDOOR CONTROLLER BOARDI.B
INDOOR POWER BOARD FUSE(4A) VARISTORZNR
F1
P.B
[Servicing]
Fasten terminal of the terminal board "TB4" equips lock system. To remove the fastened terminal,pull it while pressing the protruding portion(locking lever)of the terminal.The fastened terminal protruding portion should face upward.
Please set the voltage using the remote controller. For the setting method,please refer to the indoor unit installation Manual.
S1
S3
S2
TB1
TB1
S1 S2 S3
L1 L2 L3
N
POWER SUPPLY 3N~(3PHASE 4WIRES) 380-400-415V 50Hz
<PU(H)-P3/5YGAA
1.UK>
POWER SUPPLY ~(1PHASE) 220-230-240V 50Hz
<PU(H)-P3VGAA
1.UK>
OUTDOOR UNIT
WHT
BLK
BRN
ORN
YLW
BLU
BLU
YLW
WHT
BLK
BLU
YLW
WHT
YLW
YLW
BLK
RED
ORN
RED
BLK
BLU
YLW
WHT
WHT
YLW
BLU
BLK
RED
ORN
X4
CN32
CN2LCN41
1231X15
TH1
I.B
2
TB5
1
12
TB6
CN2
TH2
1
2
3 2 1
DC14V
CN2S(WHT)
CONT.BOARD CN02(WHT)
1 2
3 OUTDOOR CN01(BLU)
F1
TB4
S1 S2 S3
YLW ORN BRN
POWER CN03 (RED)
POWER CN2D(WHT)
REMOCON CN22 (BLU)
LIQUID CN21 (WHT)
INTAKE
CN20 (RED)
12
SW2
SWE
ON OFF
J23
NOTES:
TRANSMISSION WIRES DC12V
2121
INDOOR UNIT
R.B
LED1LED2LED3
FAN (WHT)
1.Since the outdoor side electric wiring may change be sure to check the outdoor unit electric wiring for servicing.
2.Indoor and outdoor connecting wires are made with polarities,make wiring matching terminal numbers(S1,S2,S3).
3.Symbols used in wiring diagram above are, :Connector, :Terminal (block).
MF1
ORN
C1
23514
7531
6
X6
X5X6
31
X5 X4
D.HEATER CNC (RED)
H2
ZNR
P.B
J24
X1
11
MF2
123456
C2
BRN
GRY
For PCA-P5HA
J22
J21
SW1
J11
J12
J13
J14
J15
TH5
12
PIPE CN29 (BLK)
12 13
WIRING DIAGRAM
PCA-P3HA PCA-P5HA
23
Page 24
7 REFRIGERANT SYSTEM DIAGRAM
Indoor unit
Outdoor unit
Thermistor (TH1)
Strainer
(#50)
Flared connection
Flexible tube
Service port
Accumulator
Ball valve
Compressor
Refrigerant pipe
15.88A({5/8") (with heat insulator)
Refrigerant pipe
9.52A({3/8") (with heat insulator)
Stop valve (with service port)
4-way valve
Service port
High pressure protect switch
Outdoor heat exchanger
Thermistor (TH3)
Distributor with strainer
Thermistor (TH6)
Distributor with strainer
Indoor coil thermistor (TH2)
Thermistor (TH5)
Muffler
Thermistor(TH4)
Linear expansion valve
Refrigerant flow in cooling Refrigerant flow in heating
(#50)
Strainer
(#100)
Strainer
(#100)
Strainer
Indoor unit
Outdoor unit
Thermistor (TH2)
Flexible tube
Service port
Accumulator
Compressor
Refrigerant pipe
19.05A({3/4") (with heat insulator)
Refrigerant pipe
9.52A({3/8") (with heat insulator)
Stop valve (with service port)
4-way valve
Service port
High pressure protect switch
Thermistor (TH3)
Capillary tube (O.D.4.0I.D.3.0-L200)2pcs
Distributor with strainer
Flared connection
Drier
Liner expansion valve
Bypass valve
Thermistor (TH5)
Thermistor (TH1)
Muffler
Thermistor (TH4)
Thermistor (TH6)
Distributor with strainer
Capillary tube w1
Refrigerant flow in cooling Refrigerant flow in heating
w1 : O.D.4.0I.D.2.0-L400(PUH-P5YGAA
1.UK)
O.D.4.0I.D.3.0-L450(PUH-P6YGAA
1.UK)
Ball valve
(#50)
Strainer
Strainer
(#100)
Strainer
(#100)
Strainer
(#50)
Strainer
(#50)
Indoor unit
Outdoor unit
Thermistor (TH1)
Flared connection
Flexible tube
Service port
Accumulator
Compressor
Refrigerant pipe
15.88A({5/8") (with heat insulator)
Refrigerant pipe
9.52A({3/8") (with heat insulator)
Stop valve (with service port)
Service port
High pressure protect switch
Outdoor heat exchanger
Thermistor (TH3)
Distributor with strainer
Thermistor (TH6)
Distributor with strainer
Indoor coil thermistor (TH2)
Thermistor (TH5)
Thermistor(TH4)
Linear expansion valve
Refrigerant flow in cooling
Ball valve
(#50)
Strainer
(#100)
Strainer
(#100)
Strainer
Strainer
(#50)
Indoor unit
Outdoor unit
Thermistor (TH2)
Flexible tube
Service port
Accumulator
Compressor
Refrigerant pipe
19.05A({3/4") (with heat insulator)
Refrigerant pipe
9.52A({3/8") (with heat insulator)
Service port
High pressure protect switch
Thermistor (TH3)
Capillary tube (O.D.4.0I.D.3.0-L200)2pcs
Distributor with strainer
Flared connection
Drier
Thermistor (TH5)
Thermistor (TH1)
Thermistor (TH4)
Thermistor (TH6)
Distributor with strainer
Refrigerant flow in cooling
Stop valve (with service port)
Liner expansion valve
Ball valve
(#50)
Strainer
Strainer
(#100)
Strainer
(#100)
(#50)
Strainer
Strainer
(#50)
PCA-P3HA / PUH-3VGAA1.UK, PUH-3YGAA1.UK
PCA-P5HA / PUH-5YGAA1.UK
Unit : mm
<4-way valve solenoid coil>
Heating : ON Cooling : OFF
PCA-P3HA / PU-3VGAA1.UK, PU-3YGAA1.UK
PCA-P5HA / PU-5YGAA1.UK
24
Page 25
8
Measure the resistance between the terminals using a tester. (Winding temperature 20:)
Fan motor
Open or short
Abnormal
White
Orange
Yellow
Blue
Black
Red
Relay connector
Protector
Protector
OPEN : 135i 5: CLOSE: 95i 15:
White–Black
Brown–Blue
Blue–Yellow
Yellow–Red
Connector
PCH-P3HA
140.5"
15.4"
28.5"
80.4"
PCH-P5HA
75.6"
36.7"
23.6"
47.8"
Normal
Parts name Check points
Disconnect the connector then measure the resistance using a tester. (Surrounding temperature 10:~30:)
(Refer to the next pege for a detail.)
Room temperature thermistor (TH1)
Pipe temperature thermistor (TH2)
Condenser/Evaporator temperature thermistor (TH5)
Normal
4.3k"~9.6k"
Abnormal
Open or short
TROUBLESHOOTING
HOW TO CHECK THE PARTS
PCA-P3HA PCA-P5HA
<Thermistor Characteristic graph>
Thermistor for lower temperature
Room temperature thermistor(TH1) Pipe temperature thermistor(TH2) Condenser/evaporator temperature thermistor(TH5)
Thermistor R0=15k±3% Fixed number of B=3480kΩ ±2%
Rt=15exp { 3480( ) }
0: 15k 10: 9.6k 20: 6.3k 25: 5.4k 30: 4.3k 40: 3.0k
1
273+t
1
273
25
< Thermistor for lower temperature >
50
40
30
20
Resistance (K")
10
0
-20 -10 0 10 20 30 40 50 Temperature (:)
Page 26
9
Slide
DISASSEMBLY PROCEDURE
PCA-P5HA
OPERATING PROCEDURE PHOTOS&ILLUSTRATIONS
1. Removing the oil filter
(1) Slide the oil filter towards you to remove. (See figure 1.)
2. Removing the terminal block box cover
(1) Remove the oil filter. (See figure 1.) (2) Remove a screw for terminal block box cover, and remove
the terminal block box cover. (See photo 1.)
Figure 1
Oil filter
Photo 1
Filter rail Fan guard
Terminal block box
Screw
Terminal block box cover
Clamp for wiring
3. Removing the control box
(1) Remove the oil filter. (See figure 1.) (2) Loosen a screw for control box cover to remove the con-
trol box cover. (See photo 2.) (3) Remove the lead wire from the 2 clips. (4) Remove the 2 white cord heater relay connectors (1P✕2)
and 2 fan motor relay connectors (6P2) in the control
box. (5) Remove the 2 screws for control box to slide the control
box downward. Electrical parts in the control box
• Fan motor capacitor
• Indoor controller board
• Power board
Photo 2
Screws for control box
Screw for control box cover
Photo 3
Cord heater relay connectors
Power board
Fan motor relay connectors
Clip for lead wire
Pipe temperature thermistor connector (CN21)
Room temperature thermistor connector (CN20)
26
Fan motor capacitor
Indoor controller board
Page 27
OPERATING PROCEDURE PHOTOS&ILLUSTRATIONS
4. Removing the fan motor
(1) Remove the oil filter. (See figure 1.) (2) Remove the control box cover. (See photo 2.) (3) Remove the room temperature thermistor connector
(CN20) on the indoor controller board. (See photo 3.)
(4) Remove a filter rail that is the nearest to the control box.
(See photo 4.) (5) Remove the fan guard. (See photo 5.) (6) Remove the room temperature thermistor together with the
holder at the right side of the casing.
Photo 4
Screws for filter reil
Photo 5
Control box cover
Screws for Fan guard
Room temperature thermistor
Filter reil
Room temperature thermistor
Fan guard
Screws for Fan guard
5. Removing the fan motor and the sirocco fan
(1) Remove the oil filter. (See figure 1.) (2) Remove the control box cover.
(See photo 2.)
(3) Remove the fan motor relay connectors (6P) in the control
box. (See photo 3.) (4) Remove the 3 filter rails. (5) Remove the fan guard. (6) Remove the lower casing.
(See photo 1, 4.)
(See photo 5.)
(See photo 6.)
(7) Remove the green earth wire from the motor support.
(See photo 7.) (8) Remove the 2 screws (M5 12) for motor support, and
remove the left and right motor supports. (9) Remove the fan motor together with the sirocco fan.
(10) Remove the 2 set screws (M6) to separate the fan motor
from the sirocco fan.
Photo 6
Screws for casing
Control box cover
Photo 7
casing
Earth wire
Fan motor
Set screw
Screws for casing
casing
27
Sirocco fan
Screws for motor support
Motor support
Sirocco fan
Page 28
OPERATING PROCEDURE PHOTOS
6. Removing the pipe temperature thermistor
(1) Remove the oil filter. (See figure 1.) (2) Remove the fan guard.
(See photo 1.) (3) Remove the terminal block box cover. (4) Remove the white relay connector (2P) in the terminal
block box. (See photo 8.) (5) Remove the service panel. (See photo 9.) (6) Remove the pipe temperature thermistor from the holder.
(See photo 10.)
Caution for installation
When installing the pipe temperature thermistor, slack off its lead wire as shown in the photo. Otherwise, water trickled down the lead wire may splash on the connector and this could cause a short circuit of the connector.
Photo 8
Photo 9
Photo 10
Relay connector
Terminal block box
Service panel
Screw for service panel
Inspection port
7. Removing the under panel
(1) Remove the oil filter. (See figure 1.) (2) Remove the 3 filter rails. (See photo 1, 4.) (3) Remove the 12 screws (left: 1, right: 1, Bottom: 10) for
under panel, and remove the under panel.
(See photo 11.)
8. Removing the drain pan
(1) Remove the oil filter. (See Figure 1) (2) Remove the 3 filter rails. (See photo 1, 4.) (3) Remove the under panel. (See photo 11.) (4) Pull the blue lead wire for cord heater towards you to
slack off. (See photo 12.) (5) Remove the 3 screws at the center of the drain pan, and
remove the drain pan.
Photo 11
Screw for
under panel
(left:1)
Photo 12
Pipe temperature thermistor
Under panel
Slack off
Screw for under panel (right:1)
Screws for under panel (Bottom:10)
Lead wire for cord heater
(Note) Remove the drain pan carefully since the drain could
remain in it.
Screws for drain pan
Drain pan
28
Page 29
OPERATING PROCEDURE PHOTOS
9. Removing the guide vane
(1) Remove the oil filter. (See figure 1.) (2) Remove the 3 filter rails. (See photo 1, 4.) (3) Remove the under panel. (See photo 11.) (4) Remove the drain pan. (See photo 12.) (5) Remove the 3 screws (4 10) for guide vane, and
remove the guide vane. (See photo 13.)
10. Removing the vane
(1) Slide the vane to the center of the unit, and pull it towards
you to remove. (See photo 14.)
Caution for installation
When installing the vane, check that its projection is on the left-rear side.
Projection
11. Removing the heat exchanger
(1) Remove the oil filter. (See figure 1.) (2) Remove the 3 filter rails. (See photo 1, 4.) (3) Remove the under panel. (See photo 11.) (4) Remove the drain pan. (See photo 12.) (5) Remove the 2 screws (4 10) for pipe cover, and
remove the pipe cover. (See photo 15.)
(6) Remove the 3 screws (4 10, left: 2, right: 1) for heat
exchanger. (See photo 15, 16.)
(7) Remove the 2 screws (4 10) for heat exchanger at the
top of the unit, and remove the heat exchanger. (See photo 17.)
Photo 13
Photo 14
Slide
Photo 15
Heat exchanger
Guide vane
Screws for guide vaneDrain pan
Vane
Slide
pipe cover
Screw for Heat exchanger (right)
Screw for pipe cover
Screws for Heat exchanger (top)
Photo 16Photo 17
Heat exchanger
Heat exchanger
Screws for Heat exchanger (left)
29
Page 30
10
No.
Parts No. Parts Name
Specifications
PCA-
P3HA
Wiring
Diagram
Symbol
Recom­mended
Q'ty
Unit
Amount
Q'ty / set
Price
Remarks
(Drawing No.)
P5HA
1 2
3
4 5
6 7 8
9 10 11
12
13 14
15 16 17 18 19
LEG-L SIDE PLATE-L REAR PANER REAR PANER UNDER PANEL UNDER PANEL FILTER RAIL OIL FILTER DRAIN HOSE SUPPORT SIDE COVER LEG-R SERVICE PANEL SIDE PLATE-R FRONT PANEL FRONT PANEL VANE ASSY VANE ASSY GUIDE VANE ASSY-6L GUIDE VANE ASSY-6C GUIDE VANE ASSY-6R VANE HOLDER VANE SUPPORT FRONT SUPPORT
R01 13N 809 R01 13N 662 T7W E02 676 T7W E03 676 R01 12N 669 R01 13N 669 R01 13N 503 R01 E05 500
— R01 13N 667 R01 13N 808 R01 13N 668 R01 13N 661 T7W E02 651 T7W E03 651 R01 12N 002 R01 13N 002 R01 13N 086 R01 13N 087 R01 13N 085 R01 13N 533
2 1 1
1
2 3 1 1 2 1 1 1
2
1
1 1 1 1
2 1
1
1 3 4 1 1 2 1 1
1
3 1 1 1 1 2 2
(BG00K145G02)
(BG00K146G02) (BG00T773G01)
PARTS LIST
STRUCTURAL PART PCA-P3HA PCA-P5HA
1 2
3 4
5
6
19
18
17
16
15
14
13
12
11 10
9
30
7
8
Page 31
No.
Parts No. Parts Name
Specifications
PCA-
P3HA
Wiring
Diagram
Symbol
Recom-
mended
Q'ty
Unit
Amount
Q'ty / set
Price
Remarks
(Drawing No.)
P5HA
TH1
TH2 TH5
MF1 MF1,2
PA6V40-CB PA4V80-CA
1
2
3 4
5 6
7 8 9
10 11
12 13
14 15
16 17 18
19 20 21 22 23
T. CASING ASSY T. CASING ASSY SIROCO FAN SIROCO FAN UNDER CASING-L UNDER CASING-L FAN GUARD-S ROOM TEMPERATUR TERMISTOR FAN GUARD-L FAN GUARD-L UNDER CASING-R UNDER CASING-R FAN GUARD-S DRAINPAN ASSY DRAINPAN ASSY FAN PLATE FAN PLATE PIPE SUPPORT PIPE TEMPERATURE TERMISTOR CONDENSER / EVAPORATOR TEMPERATURE TERMISTOR HEAT EXCHANGER HEAT EXCHANGER FAN PLATE SUPPORT-R FAN PLATE SUPPORT-C FAN MOTOR FAN MOTOR MOTOR LEG PIECE FOR MOTOR FAN PLATE SUPPORT-L PIPE COVER DRAIN HOSE COVER RUBBER MOUNT
(BG00N756G15) (BG00N756G14) (BG02T500H04)
(BG00N893G15) (BG00N893G14)
(BG00N893G13)
R01 12N 110 R01 13N 110 R01 12N 114 R01 13N 114 T7W E02 111 T7W E03 111 T7W E12 675 R01 E51 202 T7W E14 675 T7W E13 675 T7W E00 111 T7W E01 111 T7W E11 675 R01 12N 529 R01 13N 529
— —
— R01 13N 202 R01 E63 202 R01 H04 480 R01 E75 480
— T7W E20 762 T7W E21 762 R01 45K 130 R01 83E 126
— R01 13N 521 R01 13N 072 R01 811 105
2
2
1
1 1 1
1
1 1
1
1 1 1 1
1 1 1
1 1 1 1 1 2
4
4
2 2 1
2
2 2
1
2 1 1 1
1 1 1
2 2 2 1 1 1 4
20 15
18,19 17
FAN AND HEATER PARTS PCA-P3HA PCA-P5HA
1 2 3
4 5
4
6
7
8
Part numbers that are circled are not shown in the figure.
9
16
14
13
6
12
8
11
10
31
Page 32
TO REMOTE CONTROLLER
TO OUTDOOR UNIT
21
S3S2S1
CN29
CNC
CN21
CN2D
CN22
CN20
CN03
FAN
CN2S
CN02
CN01
ELECTRICAL PARTS
ON/OFF
CENTRALLY CONTROLLED
ERROR CODE
CLOCK
ON OFF
˚C
CHECK
CHECK MODE
FILTER
TEST RUN FUNCTION
˚C
1Hr.
NOT AVAILABLE
STAND BY DEFROST
TEMP.
No.
Parts No. Parts Name
Specifications
PCA-
P3HA
Wiring
Diagram
Symbol
Recom­mended
Q'ty
Unit
Amount
Q'ty / set
Price
Remarks
(Drawing No.)
P5HA
(BG02N713H05) (BG00T759G12)
1 2 3 4 5 6 7 8
9 10 11
SUPPORT CONTROLLER BOARD FUSE P0WER BOARD RUN CAPACITOR RUN CAPACITOR CONTROL BOX COVER CONTROL BOX TERMINAL BLOCK TERMINAL BLOCK REMOTE CONTROLLER
R01 18J 054 T7W E30 310 R01 E00 239 T7W E01 313 R01 A00 255 R01 576 255
— R01 17J 246 R01 556 246
9 1 1 1 1
1 1 1 1 1
I.B
P.B C1 C1,C2
TB4 TB5 R.B
250V 4A
3P(S1, S2, S3) 2P(1, 2)
9 1 1 1
2 1 1 1 1 1
PCA-P3HA PCA-P5HA
7, 8
1
6
5
2
3
1
11
4
9 10
32
Page 33
11
28˚C
26
˚C
8:00
Normal
operation
23:00
Setback
operation
8:00
Normal
operation
1. TIMER
OPTIONAL PARTS
Part No.
Model Name
1-1. Program timer specifications
Part name Parts No. Exterior dimensions (inch) Installation Type of clock Clock accuracy Display-Time
-Week
-Timer setting unit Program cycle Timer setting unit No. of set points Power rating
1-2. Feature of program timer
(1) Daily timer function
Daily timer can be set in 30 minutes units for up to 24 hours. Each unit can be set for unit ON, unit OFF, or setback operation.
(2) Setback operation
Set back operation is useful for reducing running costs e.g. At a hotel with a 24-hour system
8:00~23:00 Cooling operation with set temperature at 26°C
23:00~8:00 Setback operation with 2 degrees of setback As shown in the chart on the right, the set temperature rises 2 degrees automatically during the setback operation. When the setback operation ends, normal operation will begin.
(3) Weekly timer function
Daily timer function can apply to each day of the week.
+
_
PAC-SC32PTA(with set back function)
Program timer PAC-SC32PTA 5-4/32
4-23/3223/32 (13012018mm) Wall mount Quartz
50 second / month at 25: Liquid crystal display Liquid crystal display Liquid crystal display 24 hours 30 minutes 48 / day
+
_
5V DC 5% (Supplied by Remote Controller)
Program timer
33
Page 34
SET/MONITOR
SET
SMTWTF S
MONITOR
PROERAN TIMER
PAC-SC32PTA
TODAY
ON
WEEKLY SETTING
OFF
ON
SET BACK
OFF
CLOCK DAILY TIMER
SET BACK
SET BACK
DAILY
SETTING
12 15 18 21 24
0361215
FILTER CHECK MODE TEST RUN
Connect to indoor unit with 2-wire cable.
Use 5-wire cable
Connect to CN1 Connect to CN1
4
1-3. How to connect program timer
SET/MONITOR
SET
SMTWT FS
MONITOR
PROERAN TIMER
PAC-SC32PTA
TODAY
ON
WEEKLY SETTING
OFF
ON
SET BACK
OFF
CLOCK DAILY TIMER
SET BACK
SET BACK
DAILY
SETTING
12 15 18 21 24
0361215
(1) Install the program timer next to the remote controller the same way as the remote controller is installed. (2) Connect the program timer and the remote controller with a 5-wire cable as shown in the figure below
NOTE:While the program timer is connected to the remote controller, the
24hour ON/OFF timer on the remote controller will not operate.
1-4. Names and functions
<PAC-SC32PTA>
WEEKLY TIMER SETTING DISPLAY
CURRENT TIME DISPLAY
SET BACK DISPLAY
DAILY TIMER SETTING DISPLAY
Used for selection of if or not the day opera­tion pattern set by PATTERN SETTING is to be applied in weekly day unit, setting.
SET/MONITOR DISPLAY
During SET is display, clock adjustment, change of weekly day, daily and weekly timer setting can be performed. During MONITOR is display, all switches except SET/MONITOR SW are invalidated. This is normal status.
WEEK DAY SETTING SW
Used for week day setting.
MODE SELECTOR SW
Using this switch select “MONITOR” or “SET” Mode.
“MONITOR” :Indicates the current timer set-
“SET”: Set to “SET” mode for clock adjust-
ting. All switch expect MODE SELECTOR SW are invalidated then.This is the normal status.
ment, charge of week day, daily and weekly timer setting.
During MONITOR status,current time is display. During Daily timer setting, a
Indicates the setting set back range.
time desire for timer setting is displayed.
CLOCK ADJUSTMENT SW
Used for adjustment of the current time.
Push SW to advance the time. Each time the button is pushed the time advance by 1 minute, pushing continuously advances by 1 minute at 0.5 second interval, and when the lower digit of minute becomes 0 indication advances in 10 min­utes unit.
SW is used for reversing the time. Each time the button is pushed the time reverses by 1 minute, pushing continuously reverses the time by 1 minute at 0.5 second interval, and when the lower digit of minute becomes 0 indication reverses in 10 minutes unit.
24 hours is divided into 48 blocks and each block express 30 minutes. The block display consists of 3 pattern.
Set back can be done in the range of 1,2,4,6 and 8°C.
SET BACK SETTING SW
Used for set back setting.
ON/SET BACK/OFF SW
Used to specify the time setting pattern.
DAILY TIMER SW
Used for timer setting in 30 minutes unit.
WEEKLY TIMER SW
Used for setting timer in day of week unit.
Pushing SW moves the week day light display in order of S → M → T → W enabling to set the week day.
34
Page 35
2. Duct flange for frech air
Part No. PAC-SF28OF-E
Applied Service Ref.
PCA-P3HA, PCA-P5HA
3. Filter element
Part No. PAC-SG38KF-E
Applied Service Ref.
PCA-P3HA, PCA-P5HA
4. Decoration cover (Front + Susupending bracket cover)
Part No. PAC-SF81KC-E PAC-SF82KC-E
Applied Service Ref.
PCA-P3HA PCA-P5HA
5. Remote sensor
Part No. PAC-SE41TS-E
Applied Service Ref.
PCA-P3HA, PCA-P5HA
6. Remote operation adapter
Part No. PAC-SF40RM-E
Applied Service Ref.
PCA-P3HA, PCA-P5HA
7. Remote ON/OFF adapter
Part No. PAC-SF55RA-E
Applied Service Ref.
PCA-P3HA, PCA-P5HA
35
Page 36
HEAD OFFICE : MITSUBISHI DENKI BLDG., 2-2-3, MARUNOUCHI, CHIYODA-KU TOKYO 100-8310, JAPAN
TM
cCopyright 2003 MITSUBISHI ELECTRIC ENGINEERING CO.,LTD. Distribted in Mar. 2003. No. CO289 41 Made in Japan
New publication, effective Mar. 2003. Specifications subject to change without notice.
Loading...