Mitsubishi Electric PKA-A18HA6, PKA-A12HA6, PCA, PCA-A24KA6, PCA-A36KA6 Service Manual

...
Page 1
SERVICE MANUAL
Notes:
• This manual describes service data of the indoor units only.
• RoHS compliant products have <G> mark on the spec name plate.
CONTENTS
1. REFERENCE MANUAL
...................................
2
2. SAFETY PRECAUTION
...................................
3
3. PARTS NAMES AND FUNCTIONS
.................
4
4. SPECIFICATIONS
...........................................
10
5. NOISE CRITERION CURVES
.........................11
6. OUTLINES AND DIMENSIONS
...................... 12
7. WIRING DIAGRAM
.........................................13
8. REFRIGERANT SYSTEM DIAGRAM
............
14
9. TROUBLESHOOTING
....................................
15
10. SPECIAL FUNCTION
.....................................
29
11. DISASSEMBLY PROCEDURE
.......................
32
Indoor unit [Model Name] [Service Ref.]
PARTS CATALOG (OCB580)
INDOOR UNIT
PKA-A12HA6
PKA-A12HA6
PKA-A18HA6
PKA-A18HA6
WIRED REMOTE
CONTROLLER
(Option)
IR WIRELESS REMOTE CONTROLLER (Option)
December 2014
No. OCH580
COOL
DRY
AUTO
FAN
HEAT
SPLIT-SYSTEM HEAT PUMP
Page 2
2
1
REFERENCE MANUAL
1-1. OUTDOOR UNIT SERVICE MANUAL
Model Name Service Ref. Service Manual No.
PUZ-A18/24/30/36NHA6 PUZ-A18/24/30/36NHA6-BS
PUZ-A18/24/30/36NHA6 PUZ-A18/24/30/36NHA6-BS
OCH577
OCB577
PUY-A12/18/24/30/36NHA6 PUY-A12/18/24/30/36NHA6-BS
PUY-A12/18/24/30/36NHA6 PUY-A12/18/24/30/36NHA6-BS
Radio frequency interface Wired remote controller IR wireless remote controller
COOL
DRY
AUTO
FAN
HEAT
RF thermostat
Remote controller (Optional parts)
OCH580
Page 3
3
SAFETY PRECAUTION
2
Cautions for units utilising refrigerant R410A
2-2. CAUTIONS RELATED TO NEW REFRIGERANT
2-1. ALWAYS OBSERVE FOR SAFETY
Before obtaining access to terminal, all supply circuits must be disconnected.
Use new refrigerant pipes.
Charge refrigerant from liquid phase of gas cylinder.
If the refrigerant is charged from gas phase, composition change may occur in refrigerant and the efficiency will be lowered.
Use a vacuum pump with a reverse flow check valve.
Vacuum pump oil may flow back into refrigerant cycle and that can cause deterioration of refrigerant oil, etc.
Use the following tools specifically designed for use with R410A refrigerant.
The following tools are necessary to use R410A refrigerant.
Handle tools with care.
If dirt, dust or moisture enters into refrigerant cycle, that can cause deterioration of refrigerant oil or malfunction of com­pressor.
Do not use a charging cylinder.
If a charging cylinder is used, the composition of refrigera­nt will change and the efficiency will be lowered.
Flare tool
Electronic refrigerant charging scale
Vacuum pump adaptor
Size adjustment gauge
Gauge manifold
Torque wrench
Gas leak detector
Charge hose
Tools for R410A
Contamination inside refrigerant piping can cause deterio­ration of refrigerant oil, etc.
If large amount of mineral oil enters, that can cause deterio­ration of refrigerant oil, etc.
The refrigerant oil applied to flare and flange connections must be ester oil, ether oil or alkylbenzene oil in a small amount.
Make sure that the inside and outside of refrige­rant piping is clean and it has no contaminants such as sulfur, oxides, dirt, shaving particles, etc, which are hazards to refrigerant cycle. In addition, use pipes with specified thickness.
Store the piping indoors, and both ends of the piping sealed until just before brazing. (Leave elbow joints, etc. in their packaging.)
If dirt, dust or moisture enters into refrigerant cycle, that can cause deterioration of refrigerant oil or malfunction of compressor.
Do not use refrigerant other than R410A.
If other refrigerant (R22, etc.) is used, chlorine in refrige­rant can cause deterioration of refrigerant oil, etc.
Ventilate the room if refrigerant leaks during operation. If refrigerant comes into contact with a flame, poisonous gases will be released.
Use the specified refrigerant only.
Never use any refrigerant other than that specified.
Doing so may cause a burst, an explosion, or fire when the unit is being used, serviced, or disposed of. Correct refrigerant is specified in the manuals and on the spec labels provided with our products. We will not be held responsible for mechanical failure, system malfunction, unit breakdown or accidents caused by failure to follow the instructions.
[1] Cautions for service
(1) Perform service after recovering the refrigerant left in unit completely. (2) Do not release refrigerant in the air. (3) After completing service, charge the cycle with specified amount of refrigerant. (4) When performing service, install a filter drier simultaneously.
Be sure to use a filter drier for new refrigerant.
OCH580
Page 4
4
Gravimeter
Unit
[3] Service tools
Use the below service tools as exclusive tools for R410A refrigerant.
3
PARTS NAMES AND FUNCTIONS
Indoor unit
Filter
Air intake
Louver
Air outlet
Vane
No. Tool name Specifications
1
Gauge manifold · Only for R410A
· Use the existing fitting
specifications
. (UNF1/2)
· Use high-tension side pressure of 5.3MPa·G or over.
2
Charge hose · Only for R410A
· Use pressure performance of 5.09MPa·G or over.
3
Electronic scale
4
Gas leak detector
· Use the detector for R134a, R407C or R410A.
5
Adaptor for reverse flow check
· Attach on vacuum pump.
6
Refrigerant charge base
7
Refrigerant cylinder · Only for R410A · Top of cylinder (Pink)
· Cylinder with syphon
8
Refrigerant recovery equipment
[2] Additional refrigerant charge
When charging directly from cylinder
· Check that cylinder for R410A on the market is syphon type.
· Charging should be performed with the cylinder of syphon stood vertically. (Refrigerant is charged from liquid phase.)
OCH580
Page 5
5
Wired remote controller (Option)
Function buttons
4 3 2 1
5
6
7 8 9
0
The functions of the function buttons change depending on the screen. Refer to the button function guide that appears at the bottom of the LCD for the functions they serve on a given screen. When the system is centrally controlled, the button function guide that corresponds to the locked button will not appear.
Fri
Room
Set temp.
Mode Temp. Fan
Cool
Main
Main display:
Cursor Page
Main menu
Vane·Louver·Vent. (Lossnay) High power Timer Weekly timer OU silent mode
Main display Main menu
Function guide
1 [ON/OFF] button
Press to turn ON/OFF the indoor unit.
2 [SELECT] button
Press to save the setting.
3 [RETURN] button
Press to return to the previous screen.
4 [MENU] button
Press to bring up the Main menu.
5 Backlit LCD
Operation settings will appear.
When the backlight is off, pressing any button turns the backlight on and it will stay lit for a certain period of time depending on the screen.
When the backlight is off, pressing any button turns the backlight on and does not perform its function. (except for the [ON/OFF] button)
6 ON/OFF lamp
This lamp lights up in green while the unit is in operation. It blinks while the remote controller is starting up or when there is an error.
7 Function button [F1]
Main display: Press to change the operation mode.
Main menu: Press to move the cursor down.
8 Function button [F2]
Main display: Press to decrease temperature.
Main menu: Press to move the cursor up.
9 Function button [F3]
Main display: Press to increase temperature.
Main menu: Press to go to the previous page.
0 Function button [F4]
Main display: Press to change the fan speed.
Main menu: Press to go to the next page.
Controller interface
7 8 9
0
7 8 9
0
OCH580
Page 6
6
The main display can be displayed in two different modes: “Full” and “Basic”. The initial setting is “Full”. To switch to the “Basic” mode, change the setting on the Main display setting. (Refer to operation manual included with remote controller.)
<Basic mode>
3
Appears when the On/Off timer, Night setback, or Auto-off timer func­tion is enabled.
appears when the timer is disabled by the centralized control
system.
4
Appears when the Weekly timer is enabled.
5
Appears while the units are operated in the energy-save mode. (Will not appear on some models of indoor units)
6
Appears while the outdoor units are operated in the silent mode.
7
Appears when the built-in thermistor on the remote controller is acti­vated to monitor the room temperature (1).
appears when the thermistor on the indoor unit is activated to
monitor the room temperature.
8
Indicates the vane setting.
9
Indicates the louver setting.
▌)
Indicates the ventilation setting.
▌!
Appears when the preset temperature range is restricted.
1 Operation mode
Indoor unit operation mode appears here.
2 Preset temperature
Preset temperature appears here.
3 Clock (See the Installation Manual.)
Current time appears here.
4 Fan speed
Fan speed setting appears here.
5 Button function guide
Functions of the corresponding buttons appear here.
6
Appears when the ON/OFF operation is centrally controlled.
7
Appears when the operation mode is centrally controlled.
8
Appears when the preset temperature is centrally controlled.
9
0
1 Room temperature (See the Installation Manual.)
Current room temperature appears here.
2
Appears when the buttons are locked.
<Full mode>
* All icons are displayed for explanation.
Fri
Mode Temp. Fan
Room
Cool
Set temp.
Fri
Cool
Mode Temp. Fan
Set temp.
4
3
2
1
5
6
7
8
9
0
1
3
9
4
)
!
2 3 4 5 6 7 8
2
1
5
Most settings (except ON/OFF, mode, fan speed, temperature) can be made from the Menu screen. (Refer to operation manual included with remote controller.)
Display
Appears
OCH580
Page 7
7
Not all functions are available on all models of indoor units.
Energy saving
Auto return
Schedule
Night setback
Main menu
Press the
MENU
button.
Move the cursor to the desired item with the
F1
and
F2
buttons, and press the
SELECT
button.
Vane · Louver · Vent. (Lossnay)
High power
Weekly timer
Restriction
Maintenance
Initial setting
On / Off timer
Auto-Off timer
Temp. range
Operation lock
Manual vane angle
Main / Sub
Timer
Main display
Contrast
Display details
Auto mode
Administrator password
Language selection
Service
Input maintenance info.
Function setting
Lossnay (City Multi only)
Check
Self check
Maintenance password
Remote controller check
Test run
Clock
Auto descending panel
Menu structure
Filter Information
Error Information
OCH580
Page 8
8
Setting and display items Setting details
Vane · Louver · Vent. (Lossnay) Use to set the vane angle.
• Select a desired vane setting from ve different settings.
Use to turn ON / OFF the louver.
• Select a desired setting from "ON" and "OFF."
Use to set the amount of ventilation.
• Select a desired setting from "Off," "Low," and "High."
High power Use to reach the comfortable room temperature quickly.
• Units can be operated in the High-power mode for up to 30 minutes.
Timer On/Off timer* Use to set the operation On/Off times.
• Time can be set in 5-minute increments.
Auto-Off timer Use to set the Auto-Off time.
• Time can be set to a value from 30 to 240 in 10-minute increments.
Weekly timer* Use to set the weekly operation On / Off times.
• Up to 8 operation patterns can be set for each day. (Not valid when the On/Off timer is enabled.)
Restriction Temp. range Use to restrict the preset temperature range.
• Different temperature ranges can be set for different operation modes.
Operation lock Use to lock selected functions.
• The locked functions cannot be operated.
Energy saving Auto return Use to get the units to operate at the preset temperature after performing energy-save operation for a
specied time period.
• Time can be set to a value from 30 and 120 in 10-minute increments. (This function will not be valid when the preset temperature ranges are restricted.)
Schedule* Set the start/stop times to operate the units in the energy-save mode for each day of the week, and set the
energy-saving rate.
• Up to 4 energy-save operation patterns can be set for each day.
• Time can be set in 5-minute increments.
• Energy-saving rate can be set to a value from 0% or 50 to 90% in 10% increments.
Night setback* Use to make Night setback settings.
• Select "Yes" to enable the setting, and "No" to disable the setting. The temperature range and the start/stop times can be set.
Filter information Use to check the lter status.
• The lter sign can be reset.
Error information Use to check error information when an error occurs.
• Check code, error source, refrigerant address, unit model, manufacturing number, contact information (dealer's
phone number) can be displayed.
(The unit model, manufacturing number, and contact information need to be registered in advance to be displayed.)
Maintenance Auto descending panel Auto descending panel (Optional parts) Up / Down you can do.
Manual vane angle Use to set the vane angle for each vane to a xed position.
Initial setting Main/Sub When connecting two remote controllers, one of them needs to be designated as a sub controller.
Clock Use to set the current time.
Main display Use to switch between "Full" and "Basic" modes for the Main display.
• The initial setting is "Full."
Contrast Use to adjust screen contrast.
Display details Make the settings for the remote controller related items as necessary.
Clock: The initial settings are "Yes" and "24h" format. Temperature: Set either Celsius (°C) or Fahrenheit (°F). Room temp. : Set Show or Hide. Auto mode: Set the Auto mode display or Only Auto display.
Auto mode Whether or not to use the Auto mode can be selected by using the button.
This setting is valid only when indoor units with the Auto mode function are connected.
Administrator password
The administrator password is required to make the settings for the following items.
• Timer setting • Energy-save setting • Weekly timer setting
• Restriction setting • Outdoor unit silent mode setting • Night set back
Language selection Use to select the desired language.
Service Test run Select "Test run" from the Service menu to bring up the Test run menu.
• Test run • Drain pump test run
Input maintenance Select "Input maintenance Info." from the Service menu to bring up the Maintenance information screen.
The following settings can be made from the Maintenance Information screen.
• Model name input • Serial No. input • Dealer information input
Function setting Make the settings for the indoor unit functions via the remote controller as necessary. Check Error history: Display the error history and execute “delete error history”.
Refrigerant leak check: Refrigerant leaks can be judged. Smooth maintenance: The indoor and outdoor maintenance data can be displayed. Request code: Details of the operation data including each thermistor temperature and error history can be checked.
Self check Error history of each unit can be checked via the remote controller. Maintenance password Use to change the maintenance password. Remote controller check
When the remote controller does not work properly, use the remote controller checking function to trou­blushoot the problem.
Main menu list
* Clock setting is required.
OCH580
Page 9
9
IR wireless remote controller (Option)
ON/OFF TEMP
FAN
VANE
TEST RUN
AUTO STOP
AUTO START
h
min
LOUVER
MODE
CHECK
RESETSET CLOCK
MODEL SELECT
NOT AVAILABLE
CHECK
TEST RUN
°C
AMPM
AMPM
VANE CONTROL button
Used to change the air flow direction.
CLOCK button
RESET button
SET button
ON/OFF button
The unit is turned ON and OFF alternately
each time
the button is pressed.
MODE SELECT button
Used to switch the operation mode between cooling, drying, heating, auto and fan mode.
CHECK-TEST RUN buttons
Only press this button to perform an inspection check or test operation. Do not use it for normal operation.
FAN SPEED SELECT button
Used to change the fan speed.
TIMER display
Displays when in timer operation or when setting timer.
buttons
SET TEMPERATURE button sets any desired room temperature.
CLOCK display
Displays the current time.
“ ” “ ” display
Displays the order of timer operation.
“ ” “ ” display
Displays whether timer is on or off.
Buttons used to set the “hour and minute” of the current time and timer settings.
“h” and “min” buttons
display
display
FAN SPEED display indicates which fan speed has been selected.
display
The vertical direction of air flow is indicated.
display
Blinks when model is selected.
display
display
CHECK and TEST RUN display indicate that the unit is being checked or test-run.
display
OPERATION MODE display Operation mode display indicates which operation mode is in effect.
AUTO STOP (OFF timer): when this switch is set, the air conditioner will be automatically stopped at the preset time. AUTO START (ON timer): when this switch is set, the air conditioner will be automatically started at the preset time.
MODEL SELECT
CHECK
TEST RUN
LOUVER button
Changes left/right airflow direction. (Not available for this model.)
SET TEMP. display indicates the desired temperature which is set.
Lights up while the signal is transmitted to the indoor unit when the button is pressed.
TIMER CONTROL buttons
OCH580
Page 10
10
SPECIFICATIONS
4
A A
kW
F.L.A
m
3
/min(CFM)
Pa(mmAq)
dB mm (in) mm (in) mm (in) mm (in)
kg (lb)
Service Ref.
Power supply(phase, cycle, voltage)
Max. Fuse Size
Min.Circuit Ampacity External finish Heat exchanger Fan Fan(drive) o No.
Fan motor output
Fan motor
Airflow(Low-Middle-High)
External static pressure Operation control & Thermostat Noise level(Low-Middle-High) Field drain pipe O.D. Dimensions
Weight
W
D H
INDOOR UNIT
PKA-A12HA6
1 phase, 60 Hz, 208/230 V
15
1
White Munsell 1.0Y 9.2/0.2
Plate fin coil
Line flow fan (direct) o 1
0.030
0.33
Dry: 9-10.5-12 (320-370-425)
Wet: 8-9.5-11 (290-335-380)
0(direct blow)
Remote controller & built-in
36-40-43
16(5/8)
898 (35-3/8)
249 (9-13/16)
295 (11-5/8)
13 (29)
1 phase, 60 Hz, 208/230 V
15
1
Plate fin coil
0(direct blow)
Remote controller & built-in
A A
kW
F.L.A
K/min(CFM)
Pa(mmAq)
dB
mm (in) mm (in) mm (in)
kg (lb)
Service Ref.
Power supply(phase, cycle, voltage)
Max. Fuse Size
Min.Circuit Ampacity
External finish Heat exchanger Fan Fan(drive) o No.
Fan motor output Fan motor
Airflow(Low-Middle-High)
External static pressure Operation control & Thermostat Noise level(Low-Middle-High) Field drain pipe O.D. Dimensions
Weight
W
D H
INDOOR UNIT
PKA-A18HA6
White Munsell 1.0Y 9.2/0.2
0.030
0.33
Dry: 9-10.5-12 (320-370-425)
Wet: 8-9.5-11 (290-335-380)
36-40-43
16(5/8)
898 (35-3/8)
249 (9-13/16)
295 (11-5/8)
13 (29)
Line flow fan (direct) o 1
mm (in)
OCH580
Page 11
11
5
NOISE CRITERION CURVES
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0dB=0.0002 µbar)
BAND CENTER FREQUENCIES, Hz
PKA-A12HA6 PKA-A18HA6
High
NOTCH
Low
43
SPL(dB)
36
LINE
UNIT
WALL
3.3ft
3.3ft
MICROPHONE
OCH580
Page 12
12
OUTLINES AND DIMENSIONS
6
PKA-A12HA6 PKA-A18HA6 Unit: in (mm)
1/2F ([12.7)
1/4F (
[
6.35)
Refrigerant Piping
Drain hose
Gas pipe
Liquid pipe
[2-1/2~[3-1/8 ([65~[80)
[2-1/2~[3-1/8 ([65~[80)
Through hole
Sleeve (purchased locally)
Center measurement hole [3/32([2.5)
5/32(3.8)
2-1/4(58)
0
Wall hole for left rear piping
Knock out hole for left rear piping 2-3/4×12-3/16(70×310)
Wall hole for right rear piping
77-
[
3/16([5.1) Tapping screw hole
4-[5/16([9) Bolt hole
Mount board
Indoor unit outline
0
5/8(16)
9-15/16(253.5)
9-1/8(232.5)
1-1/16(28.5)
1-9/16(41)
3-1/16(78.5)
4-1/16(103.5)
4-9/16(116)
6-1/2(166)
7(178.5)
8(203.5)
3-9/16(91)
13/16(21.8)
9-1/16(231.5)
10-3/4(273.2)
0
1-1/4(32.7)
2-9/16(66)
2-1/16(53.5)
5(128.5) 6(153.5)
3/4(20)
9/16(15)
14-5/8(372.3)
14(356.3)
12-7/8(237.5)
11-7/16(291.5)
10-3/8(265)
9-5/16(238)
8-13/16(225)
7-13/16(200)
4-7/8(125)
2-3/4(70)
9/16(15)
14-5/8(372.3)
14(356.3)
12-7/8(327.5)
10-3/8(265)
11-7/16(291.5)
7-13/16(200)
8-13/16(225)
4-7/8(125)
2-3/4(70)
0
17-5/8(449)
7-9/16(193.5)
7-1/16(180.3)
6-9/16(167)
5-1/2(140)
4-1/2(115)
6-13/16(174)
8-3/8(213)
9-5/16(238)
10-15/16(278.3)
15-1/2(394)
11-1/16(281)
17-5/8(449)
0
Emergency operation switch (cooling/heating)
Terminal block for MA-remote controller
Terminal block for power supply (option)
Front side(Grille open)
Terminal block for indoor/outdoor connecting line
17-15/16(457)Gas pipe
21-3/16(539)Liquid pipe
6-5/8(169) 6-3/16(158)
Drain hose
7-3/16(184)
250mm,9-13/16inch or greater with
optional drain pump installation.
Required space(Indoor unit)
(mm)
Air inlet
Air inlet
Air outlet
Min.1-31/32(50)
Min.9-13/16(250)
Min.5-7/8(150)
Min.8-5/8
(220)
Min.1-31/32(50)
Min.1/4(7)
Knock out hole for piping
D
2-3/16(56)
2-11/16(69)
3/16(6)
1-11/16(43)
C
2-3/16(56)7/16(12.5)
1-11/16(43)
B
1-3/4(46)
2-5/16(60)
2-5/16(59)
1-11/16(43)
A
1-11/16(43)
1-3/4(46)
2-3/16(56)
3/16(6)
A
Knock out hole for right piping
Right side
Mount board
3/16(5)9-13/16(249)
Top side
15-3/16(387)
7-1/2(192)
7-3/4(197)
23-9/16(599)
C
B
Operation lamp
DEFROST/STAND BY lamp
Receiver
Louver(manual)
Vane(auto)
Knock out hole for lower piping
Knock out hole for lower piping
Under side
5/16(8)
24-1/16(612)
D
Knock out hole for left piping
Left side
Front side
6-1/16(155)
2-1/8 (55)
27-1/16(688)
11-5/8(295)
35-3/8(898)
[
5/8 ([16) O.D
Effective length: 15-3/4 (400)
OCH580
Page 13
13
WIRING DIAGRAM
7
PKA-A12HA6 PKA-A18HA6
The black square(■)indicates a switch position.
Notes:
1. SymboIs used in wiring diagram above are, : Connector, :: Terminal (block).
2. Indoor and outdoor connecting wires have poIarities, make sure to match terminal numbers (S1, S2, S3)for correct wirings.
3. Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric wiring diagram for servicing.
4. This diagram shows the wiring of indoor and outdoor connecting wires. (specification of 230V), adopting superimposed system of power and signal. 1 : Use copper supply wires.
Utilisez des fils d,alimentation en cuivre.
Refer to tables 1and 2
CN90
(WHT)
CN2L (RED)
CN151 (WHT)
CN20 (RED)
CN105
(RED)
CN44
(WHT)
CN4F
(WHT)
CN22 (BLU)
CN41
(WHT)
CN51
(WHT)
CN32
(WHT)
CNMF (WHT)
S.W
SWE
R.B
CNP(BLU)
CN3C (BLU)
LDSWE(A)
(BLU)
LDSWE(B) SWE2
CN01 (BLK)
DB1
X1
FUSE
I.B
1
1
1 1 1 54
1 1
1 2
1 4 1 4
1 525
TH1 TH2 TH5
2
11 39
CN152 (WHT)
CN30 (BLK)
11 310
3
3
3
2
2
1
2
1
1
1
5
6
3
M
t
t○t
MS
3~
TB4
TB5
S1 S2 S3
ORN
ORN
ORN
BRN
LED1
LED3
LED2
TB6
ON OFF
TO OUTDOOR UNIT
YLWYLW
BLK
<Table 1> SW1 (MODEL SELECTION)
SETTING
SETTING
ON OFF
1 2 3 4 5
<Table 2> SW2(CAPACITY CODE)
MODELS
PKA­A12HA6
PKA­A18HA6
ON OFF
1 2 3 4 5
ON OFF
1 2 3 4 5
W.B
RFI
CNRU
(WHT)
LD101(B)
REC1
LED1
LED2
6
2
5
RU
Symbol
Name
Symbol
Name
I.B Indoor controller board
FUSE FUSE(T3.15AL250V)
RFI
Radio frequency interface for RF thermostat
CN2L Connector (LOSSNAY) CN30 Connector (LLC)
CN105 Connector (Radio frequency interface) CN152 Connector (Back-up heating)
CN90 Connector (Remote operation adapter)
Connector (Emergency operation)
CN32 Connector ( Remote switch) CN41 Connector (HA terminal-A) CN51 Connector (Centrally control)
LED1 Power supply (I.B) LED2 Power supply (R.B) LED3 Transmission (Indoor-outdoor) SW1 Switch (Model selection) See table 1 SW2 SWE
Switch (Capacity code) See table 2
[Explanation of symbols]
MS Fan motor
W.B Pcb for IR wireless remote controller
Switch board
SWE2 Emergency operation
M Vane motor
LED1 LED (Operation indication : Green)
REC1 Receiving unit
LED2 LED (Preparation for heating: Orange)
TB2 Terminal block(Indoor unit Power (option)) TB4 Terminal block (Indoor/outdoor connecting line) TB5 Terminal block (Remote controller transmission line) TH1 Room temp. Thermistor
Pipe temp. Thermistor/liquid
Cond./eva. temp. Thermistor
(32˚F/15ΚΩ, 77˚F/5.4ΚΩ Detect)
(32˚F/15ΚΩ, 77˚F/5.4ΚΩ Detect)
(32˚F/15ΚΩ, 77˚F/5.4ΚΩ Detect)
TH2
TH5
S.W
R.B
OPTION PART
Wired remote controller board
TB6
Terminal block (Remote controller transmission line)
OCH580
Page 14
14
REFRIGERANT SYSTEM DIAGRAM
8
Thermistor TH2 Pipe temperature(Liquid)
Distributor with strainer (#50/#50)
Thermistor TH5 (Cond./ Eva.temperature)
Thermistor TH1 (Room temperature)
Refrigerant flow in cooling Refrigerant flow in heating
Strainer (#50)
Strainer (#50)
Heat exchanger
Refrigerant GAS pipe connection (Flare)
Refrigerant LIQUID pipe connection (Flare)
PKA-A12HA6 PKA-A18HA6
OCH580
Page 15
15
TROUBLESHOOTING
9
<Check code displayed by self-diagnosis and actions to be taken for service (summary)>
Present and past check codes are logged, and they can be displayed on the wired remote controller and control board of out­doorunit. Actions to be taken for service, which depends on whether or not the trouble is reoccurring in the field, are summa­rized in the table below. Check the contents below before investigating details.
9-1. TROUBLESHOOTING
Unit conditions at service
Check code
Actions to be taken for service (summary)
The trouble is reoccurring.
Displayed
Not displayed
Judge what is wrong and take a corrective action according to “9-3. SELF-DIAGNOSIS ACTION TABLE”.
Conduct troubleshooting and ascertain the cause of the trouble according to “9-4. TROUBLESHOOTING BY INFERIOR PHENOMENA”.
The trouble is not reoccurring.
Logged
Not logged
1Consider the temporary defects such as the work of protection devices in the refrigerant circuit including compressor, poor connection of wiring, noise, etc. Re-check the symptom, and check the installation environment, refrigerant amount, weather when the trouble occurred, matters related to wiring, etc.
2
Reset check code logs and restart the unit after finishing
service. 3There is no abnormality in electrical component, controller board,remote controller, etc.
1Re-check the abnormal symptom. 2Conduct troubleshooting and ascertain the cause of the
trouble according to “9-4. TROUBLESHOOTING BY INFERIOR PHENOMENA”. 3Continue to operate unit for the time being if the cause is not ascertained. 4There is no abnormality concerning of parts such as
electrical component, controller board, remote controller,
etc.
OCH580
Page 16
16
[Procedure]
1. Press the CHECK button twice.
2. Press the TEMP buttons.
3. Point the remote controller at the sensor on the indoor unit and press the HOUR button.
4. Point the remote controller at the sensor on the indoor unit and press the ON/OFF button.
ON/OFF
TEMP
FAN
VANE
MODE
CHECK
LOUVER
TEST RUN
AUTO STOP
AUTO START
h
min
RESET
SET
CLOCK
CHECK
CHECK display
Temperature button
CHECK button
Refrigerant address display
HOUR button
ON/OFF button
<Malfunction-diagnosis method at maintenance service>
9-2. MALFUNCTION-DIAGNOSIS METHOD BY REMOTE CONTROLLER
<In case of trouble during operation>
When a malfunction occurs to air conditioner, both indoor unit and outdoor unit will stop and operation lamp blinks to inform unusual stop.
"CHECK" lights, and refrigerant address "00" blinks.
Check that the remote controller's display has stopped before continuing.
Select the refrigerant address of the indoor unit for the self-diagnosis. Note: Set refrigerant address using the outdoor unit’s DIP switch (SW1).
(For more information, see the outdoor unit installation manual.)
If an air conditioner error occurs, the indoor unit's sensor emits an intermit­ tent buzzer sound, the operation lamp blinks, and the check code is output. (It takes 3 seconds at most for check code to appear.)
The check mode is cancelled.
■IR wireless remote controller
OCH580
Page 17
17
[Output pattern A] Errors detected by indoor unit
[Output pattern B]
E9
1.If the beeper does not sound again after the initial
2 beeps to confirm the self-check start signal was received and
the OPERATION INDICATOR lamp does not come on,
there are no error records.
2.If the beeper sounds 3 times continuously “beep, beep, beep (0.4 + 0.4 + 0.4 seconds)” after the initial 2 beeps to confirm the self-check start signal was received, the specified refrigerant address is incorrect.
OPERATION INDICATOR lamp blink pattern
peeBpeeBpeeBpeeBpeeB
Beep Beep
Off
Approx. 2.5 s
On
Approx. 3 s
On
0.5 sOn0.5 sOn0.5 s
On
0.5 s
Off
Approx. 2.5 s
On
Approx. 3 s
On
0.5 sOn0.5 s
· · · Repeated
Number of blinks/beeps in pattern indicates the check code in the following table (i.e., n=5 for “U2”)
Number of blinks/beeps in pattern indicates the check code in the following table
n
th
1st2nd3
rd
1st2
nd
Self-check starts (Start signal received)
Beeper sounds
[Output pattern B]
OPERATION INDICATOR lamp blink pattern
Beep
Beep Beep Beep Beep Beep Beep
Off
Approx. 2.5 sOn0.5 sOn0.5 sOn0.5 s
On
0.5 s
Off
Approx. 2.5 sOn0.5 sOn0.5 s
· · · Repeated
Number of blinks/beeps in pattern indicates the check code in the following table (i.e., n=5 for “P5”)
Number of blinks/beeps in pattern indicates the check code in the following table
n
th
1st2nd3
rd
1st2
nd
Self-check starts (Start signal received)
Beeper sounds
Refer to the following tables for details on the check codes.
[Output pattern A]
Beeper sounds/OPERATION
INDICATOR lamp blinks
Check code
krameRmotpmyS
(Number of times)
IR wireless remote controller
Wired remote controller
Beeper sounds/OPERATION
INDICATOR lamp blinks
Check code
(Number of times)
IR wireless remote controller
Wired remote controller
1 P1
Intake sensor error
P9 Pipe (TH5) sensor error
2
P2 Pipe (TH2) sensor error
3 E6,E7
Indoor/outdoor unit communication error
4 P4 Float switch connector (CN4F) open
5
P5 PA
Drain pump error
Forced compressor stop(due to water leakage abnormality) 6 P6 Freezing/Overheating protection operation 7 EE Communication error between indoor and outdoor units 8 P8 Pipe temperature error 9 E4, E5 Remote controller signal receiving error
10
11
Errors detected by unit other than indoor unit (outdoor unit, etc.)
krameRmotpmyS
1
Indoor/outdoor unit communication error
2
(Transmitting error) (Outdoor unit)
3
Open/short of outdoor unit thermistors
4
Compressor overcurrent interruption (When compressor locked)
5
Abnormal high discharging temperature/49C operated/ insufficient refrigerant
6
Abnormal high pressure (63H operated)/Overheating protection operation
7
Abnormal temperature of heatsink
8
Outdoor unit fan protection stop
9
Compressor overcurrent interruption/Abnormal of power module
10
Abnormality of superheat due to low discharge temperature
11
Abnormality such as overvoltage or voltage shortage and abnormal synchronous signal to main circuit/Current sensor error
12 13
U2
U5
UP U3,U4 UF
U1,Ud
U8 U6 U7
U9,UH
Others
– –
– –
14
Other errors (Refer to the technical manual for the outdoor unit.)
For details, check the LED display of the outdoor controller board. As for outdoor unit, refer to outdoor unit's service manual.
12 Fb Indoor unit control system error (memory error, etc.)
E0, E3
E1, E2 Remote controller control board error
Remote controller transmission error
Compressor overcurrent interruption
14 PL Abnormality of refrigerant circuit
Notes:
OCH580
Page 18
18
If the unit cannot be operated properly after the test run, refer to the following table to find out the cause.
Symptom
Cause
Wired remote controller LED 1, 2 (PCB in outdoor unit)
On the IR wireless remote controller with condition above, following phenomena take place.
No signals from the remote controller can be received.
OPE lamp is blinking.
The buzzer makes a short ping sound.
PLEASE WAIT
PLEASE WAIT
Check code
Display messages do not appear even when operation switch is turned ON (operation lamp does not light up).
For about 2 minutes after
power-on
Subsequent to about 2 minutes after power-on
After LED 1, 2 are lighted, LED 2 is turned off, then only LED 1 is
Only LED 1 is lighted.
LED 1, 2 blink.
Only LED 1 is lighted.
LED 1 blinks twice,
LED 2 blinks once.
For about 2 minutes following power-on, op-
eration of the remote controller is not possible due to system start-up. (Correct operation)
Connector for the outdoor unit’s protection
device is not connected.
Reverse or open phase wiring for the outdoor
unit’s power terminal block (L1, L2, GR)
Incorrect wiring between indoor and outdoor
units (incorrect polarity of S1, S2, S3)
Remote controller wire short
Note: Operation is not possible for about 30 seconds after cancellation of function selection. (Correct operation)
For description of each LED (LED1, 2, 3) provided on the indoor controller, refer to the following table.
LED1 (power for microprocessor) Indicates whether control power is supplied. Make sure that this LED is
always lit.
LED2 (power for wired remote controller)
Indicates whether power is supplied to the wired remote controller. This LED lights only in the case of the indoor unit which is connected to the outdoor unit refrigerant addresses “0”.
LED3 (communication between indoor and outdoor units)
Indicates state of communication between the indoor and outdoor units. Make sure that this LED is always blinking.
lighted.
(Correct operation)
On IR wireless remote controller
The continuous buzzer sounds from receiving section of indoor unit. Blink of operation lamp
On wired remote controller
Check code displayed in the LCD. (Refer to the previous page, check code.)
OCH580
Page 19
19
9-3. SELF-DIAGNOSIS ACTION TABLE
Note: Errors to be detected in outdoor unit, such as codes starting with F, U or E (excluding E0 to E7), are not covered in this document. Please refer to the outdoor unit service manual for the details.
Check code
Abnormal point and detection method
Cause
Countermeasure
P1
P2
Room temperature thermistor (TH1)
1 The unit is in 3-minute resume prevention mode if short/open of thermistor is detected. Abnormal if the
unit does not reset normally after 3 min­utes. (The unit returns to normal opera­tion, if it has been reset normally.)
2 Constantly detected during cooling, drying, and heating operation. Short: 194°F [90:] or more Open: −40°F [−40:] or less
1 Defective thermistor characteristics 2 Contact failure of connector
(CN20) on the indoor controller board (Insert failure)
3 Breaking of wire or contact failure of thermistor wiring 4 Defective indoor controller
board
13 Check resistance value of thermistor.
32°F [0:] ....15.0 k"
50°F [10:] ......9.6 k"
68°F [20:] ......6.3 k"
86°F [30:] ......4.3 k"
104°F [40:] ......3.0 k"
If you put force on (draw or bend) the lead wire with measuring resistance value of thermis­tor, breaking of wire or contact failure can be detected. 2 Check contact failure of connector (CN20)
on the indoor controller board. Refer to "9-7. TEST POINT DIAGRAM". Turn the power on again and check restart after inserting connector again.
4 Check room temperature display on remote
controller.
Replace indoor controller board if there is
abnormal difference with actual room
temperature.
Turn the power off, and on again to operate after check.
Pipe temperature thermistor/Liquid (TH2)
1 The unit is in 3-minute resume prevention mode if short/open of thermistor is detected. Abnormal if the
unit does not reset normally after 3 min­utes. (The unit returns to normal opera­tion, if it has been reset normally.)
2 Constantly detected during cooling, drying, and heating (except defrosting)
operation
Short: 194°F [90:] or more Open: −40°F [−40:] or less
Note:
When all of the following conditions are sat­isfied, the error is not detected:
1) During cooling operation, or for 3 min­utes after cooling operation is stopped.
2) Up to 16 minutes from 10 seconds after cooling operation is started.
3) Outside temperature < −22°F [−30:]
1 Defective thermistor characteristics 2 Contact failure of connector
(CN44) on the indoor controller board (Insert failure)
3 Breaking of wire or contact failure of thermistor wiring 4 Defective refrigerant circuit is
causing thermistor temperature of 194°F [90:] or more, or
−40°F [−40:] or less.
5 Defective indoor controller
board
13 Check resistance value of thermistor. For characteristics, refer to (P1) above. 2 Check contact failure of connector (CN44)
on the indoor controller board. Refer to "9-7. TEST POINT DIAGRAM". Turn the power on and check restart after inserting connector again.
4 Check pipe <liquid> temperature with remote
controller in test run mode. If pipe <liquid> temperature is extremely low (in cooling mode) or high (in heating mode), refrigerant circuit may have defective.
5 Check pipe <liquid> temperature with
remote controller in test run mode. If there is extremely difference with actual pipe <liquid> temperature, replace indoor controller board.
Turn the power off, and on again to operate after check.
P4
Contact failure of drain float switch (CN4F)
• Extract when the connector of drain float switch is disconnected.
(3 and 4 of connector CN4F is not
short-circuited.)
• Constantly detected during operation
1 Contact failure of connector (Insert failure)
2 Defective indoor controller
board
1 Check contact failure of float switch connector. Turn the power on again and check after insert-
ing connector again.
2 Operate with connector (CN4F) short-circuited. Replace indoor controller board if abnormality
reappears.
P5
Drain over flow protection operation
1 Suspensive abnormality, if drain float
switch is detected to be underwater for 1 minute and 30 seconds continuously with drain pump on.
Compressor and indoor fan will be
turned off.
2 Drain pump is abnormal if the condition
above is detected during suspensive abnormality.
3 Constantly detected during drain pump
operation
1 Malfunction of drain pump 2 Defective drain
Clogged drain pump Clogged drain pipe 3 Defective drain float switch
Catch of drain float switch or malfunction of moving parts cause drain float switch to be detected under water (Switch On)
4 Defective indoor-controller
board
1 Check if drain-up machine works. 2 Check drain function. 3 Remove drain float switch connector CN4F
and check if it is short (Switch On) with the moving part of float switch UP, or OPEN with the moving part of float switch down.
Replace float switch if it is short with the
moving part of float switch down.
4 Replace indoor controller board if it is short-
circuited between 3–4 of the drain float switch connector CN4F and abnormality reappears.
It is not abnormal if there is no problem about the above-mentioned 1–4. Turn the power off, and on again to operate after check.
OCH580
Page 20
20
Check code
Abnormal point and detection method
Cause
Countermeasure
P6
Freezing/overheating protection is work­ing
1 Freezing protection (Cooling mode)
• In case when outside temperature > −4°F [−20:]
The unit is in 6-minute resume preven­tion mode if pipe <liquid or condenser/ evaporator> temperature stays under
−5°F [−15:] for 3 minutes, 3 minutes after the compressor started. Abnormal if it stays under −5°F [−15:] for 3 minutes again within 16 minutes after 6-minute resume prevention mode.
• In case when outside temperature [ −4°F [−20:]
The unit is in 6-minute resume preven­tion mode if pipe <liquid or condenser/ evaporator> temperature stays under
−31°F [−35:] for 3 minutes, 3 minutes after the compressor started. Abnormal if it stays under −31°F [−35:] for 3 minutes again within 16 minutes after 6-minute resume prevention mode.
2 Overheating protection (Heating mode)
The unit is in 6-minute resume prevention mode if pipe <liquid or con­denser/evaporator> temperature is detected as over 158°F [70:] after the compressor started. Abnormal if the tem­perature of over 158°F [70:] is detected again within 30 minutes after 6-minute resume prevention mode.
P8
1 Slight temperature difference
between indoor room temperature and pipe <liquid or condenser/evaporator> temperature thermistor
• Shortage of refrigerant
• Disconnected holder of pipe <liquid or condenser/
evaporator> thermistor
• Defective refrigerant circuit
2 Converse connection of extension pipe (on plural units
connection)
3 Converse wiring of indoor/ outdoor unit connecting wire
(on plural units connection)
4 Defective detection of indoor
room temperature and pipe <condenser/evaporator>
temperature thermistor 5 Stop valve is not opened completely.
(Cooling or drying mode)
1 Clogged filter (reduced airflow) 2 Short cycle of air path 3 Low-load (low temperature)
operation out of the tolerance range
4 Defective indoor fan motor
• Fan motor is defective.
• Indoor controller board is defec­tive.
5 Defective outdoor fan control 6 Overcharge of refrigerant 7 Defective refrigerant circuit
(clogs)
(Heating mode)
1 Clogged filter (reduced airflow) 2 Short cycle of air path 3 Over-load (high temperature)
operation out of the tolerance range
4 Defective indoor fan motor
• Fan motor is defective.
• Indoor controller board is defec­tive.
5 Defective outdoor fan control 6 Overcharge of refrigerant 7 Defective refrigerant circuit
(clogs)
8 Bypass circuit of outdoor unit is
defective.
(Cooling or drying mode)
1 Check clogs of the filter. 2 Remove shields.
4 Refer to "9-6. HOW TO CHECK THE
PARTS".
5 Check outdoor fan motor. 67 Check operating condition of refrigerant
circuit.
(Heating mode)
1 Check clogs of the filter. 2 Remove shields.
4 Refer to "9-6. HOW TO CHECK THE
PARTS".
5 Check outdoor fan motor. 6–8Check operating condition of refrigerant
circuit.
Pipe temperature
<Cooling mode> Detected as abnormal when the pipe tem­perature is not in the cooling range 3 min­utes after compressor start and 6 minutes after the liquid or condenser/evaporator pipe is out of cooling range. Note 1: It takes at least 9 minutes to
detect.
Note 2: Abnormality P8 is not detected in
drying mode.
Cooling range: −5.4°F [−3°C] ] (TH−TH1) TH: Lower temperature between liquid pipe
temperature (TH2) and condenser/ evaporator temperature (TH5)
TH1: Intake temperature
<Heating mode> When 10 seconds have passed after the compressor starts operation and the hot adjustment mode has finished, the unit is detected as abnormal when condenser/ evaporator pipe temperature is not in heat­ing range within 20 minutes.
Note 3: It takes at least 27 minutes to
detect abnormality.
Note 4: It excludes the period of defrosting.
(Detection restarts when defrosting mode is over.)
Heating range: 5.4°F [3°C] [ (TH5−TH1)
14 Check pipe <liquid or condenser/evapora-
tor> temperature with room temperature display on remote controller and outdoor controller circuit board.
Pipe <liquid or condenser/evaporator>
temperature display is indicated by set­ting SW2 of outdoor controller circuit board as follows.
23Check converse connection of extension
pipe or converse wiring of indoor/outdoor unit connecting wire.
Conduct temperature check with outdoor controller circuit board after connecting ‘A-Control Service Tool(PAC-SK52ST)’.
(
)
OCH580
Page 21
21
Check code
Abnormal point and detection method
Cause
Countermeasure
P9
Pipe temperature thermistor/ Condenser-Evaporator (TH5)
1 The unit is in 3-minute resume protec-
tion mode if short/open of thermistor is detected. Abnormal if the unit does not get back to normal within 3 minutes. (The unit returns to normal operation, if it has been reset normally.)
2 Constantly detected during cooling,
drying, and heating operation (except defrosting)
Short: 194°F [90:] or more Open: −40°F [−40:] or less
Note:
When all of the following conditions are satisfied, the error is not detected:
1) During cooling operation, or for 3 min­utes after cooling operation is stopped.
2) Up to 16 minutes from 10 seconds after cooling operation is started.
3) Outside temperature < −22°F [−30:]
1 Defective thermistor characteristics 2 Contact failure of connector
(CN44) on the indoor controller board (Insert failure)
3 Breaking of wire or contact failure of thermistor wiring 4 Temperature of thermistor is
194°F [90:] or more or −40°F [−40:] or less caused by defective refrigerant circuit.
5 Defective indoor controller
board
13 Check resistance value of thermistor. For characteristics, refer to (P1) above. 2 Check contact failure of connector (CN44) on
the indoor controller board.
Refer to "9-7. TEST POINT DIAGRAM". Turn the power on and check restart after
inserting connector again.
4 Operate in test run mode and check pipe
<condenser/evaporator> temperature with outdoor controller circuit board. If pipe
<condenser/evaporator> temperature is
extremely low (in cooling mode) or high (in heating mode), refrigerant circuit may have defect.
5 Operate in test run mode and check pipe
<condenser/evaporator> temperature with
outdoor control circuit board. If there is extreme difference with actual pipe <condenser/evaporator> temperature, replace
indoor controller board. There is no abnormality if none of above
comes within the unit. Turn the power off and on again to operate.
In case of checking pipe temperature with outdoor controller circuit board, be sure to connect A-control service tool (PAC-SK52ST).
(
)
PA
Forced compressor stop (due to water leakage abnormality)
1 The unit has a water leakage abnor-
mality when the following conditions, a) and b), are satisfied while the above­mentioned detection is performed.
a) The intake temperature subtracted with
liquid pipe temperature detects to be less than 14°F [−10°C] for a total of 30 minutes. (When the drain sensor is detected to be NOT soaked in the water, the detection record of a) and b) will be cleared.)
b) Drain float switch detects to be in the
water for more than 15 minutes.
Note:
Once the water leakage abnormality is detected, abnormality state will not be released until the main power is reset.
1 Drain pump trouble 2 Drain defective
· Drain pump clogging
· Drain pipe clogging
3 Open circuit of float switch 4 Contact failure of float switch
connector
5 Dew condensation on float switch
· Drain water descends along lead wire.
· Drain water is waving due to filter clogging. 6 Extension piping connection dif-
ference at twin, triple or quadru­ple system
7 Miswiring of indoor/outdoor con-
necting at twin, triple or quadru­ple system
8 Room temperature thermistor/
liquid pipe temperature thermis­tor detection is defective.
1 Check the drain pump. 2 Check whether water can be drained.
3 Check the resistance of the float switch. 4 Check the connector contact failure.
5 Check the float switch leadwire mounted.
Check the filter clogging.
6 Check the piping connection.
7 Check the indoor/outdoor connecting wires.
8 Check the room temperature display of
remote controller.
Check the indoor liquid pipe temperature dis-
play of outdoor controller board.
E0
or
E4
Remote controller transmission error(E0)/signal receiving error(E4)
1 Abnormal if main or sub remote con-
troller cannot receive any transmission normally from indoor unit of refrigerant address “0” for 3 minutes.
(Check code: E0) 2 Abnormal if sub remote controller could
not receive any signal for 2 minutes. (Check code: E0)
1 Abnormal if indoor controller board can
not receive any data normally from remote controller board or from other indoor controller board for 3 minutes. (Check code: E4)
2 Indoor controller board cannot receive
any signal from remote controller for 2 minutes. (Check code: E4)
1 Check disconnection or looseness of indoor
unit or transmission wire of remote controller.
2 Set one of the remote controllers “main” if there is no problem with the action above. 3 Check wiring of remote controller.
• Total wiring length: max. 500 m
(Do not use cable x 3 or more.)
• The number of connecting indoor units: max. 16 units
• The number of connecting remote controller: max. 2 units
If the cause of trouble is not in above 1–3, 4 Diagnose remote controllers.
a) When “RC OK” is displayed,
Remote controllers have no problem. Turn the power off, and on again to check. If abnormality generates again, replace indoor controller board.
b) When “RC NG” is displayed,
Replace remote controller.
c)When “RC E3” or “ERC 00-66” is displayed,
noise may be causing abnormality.
Note: If the unit is not normal after replacing indoor
controller board in group control, indoor con­troller board of address “0” may be abnormal.
1 Contact failure at transmission
wire of remote controller
2 All remote controllers are set as
“sub” remote controller. In this case, E0 is displayed on remote controller, and E4 is displayed at LED (LED1, LED2) on the outdoor controller circuit board.
3 Miswiring of remote controller 4 Defective transmitting receiving
circuit of remote controller
5 Defective transmitting receiving
circuit of indoor controller board of refrigerant addresses “0”.
6 Noise has entered into the
transmission wire of remote controller.
OCH580
Page 22
22
E6
E7
Check code
Abnormal point and detection method
Cause
Countermeasure
Fb
E1
or
E2
1 Contact failure, short circuit or,
miswiring (converse wiring) of indoor/outdoor unit connecting wire
2 Defective transmitting receiving
circuit of indoor controller board
3 Defective transmitting receiving
circuit of indoor controller board
4 Noise has entered into indoor/
outdoor unit connecting wire.
Check LED display on the outdoor control
circuit board. (Connect A-control service tool, PAC-SK52ST.)
Refer to outdoor unit service manual. 1 Check disconnection or looseness of indoor/
outdoor unit connecting wire of indoor unit or
outdoor unit. Check all the units in case of twin triple indoor unit system. 24 Turn the power off, and on again to check.
If abnormality generates again, replace indoor controller board or outdoor
controller circuit board.
Note: Other indoor controller board may have
defect in the case of twin triple indoor unit system.
Indoor/outdoor unit communication error (Transmitting error)
Abnormal if “1” receiving is detected 30 times continuously though indoor controller board has transmitted “0”.
1 Defective transmitting receiving
circuit of indoor controller board
2 Noise has entered into power
supply.
3 Noise has entered into outdoor
control wire.
13 Turn the power off, and on again to check.
If abnormality generates again, replace indoor controller board.
Indoor/outdoor unit communication error (Signal receiving error)
1 Abnormal if indoor controller board cannot receive any signal normally for 6
minutes after turning the power on.
2 Abnormal if indoor controller board cannot receive any signal normally for 3
minutes.
3 Consider the unit abnormal under the fol-
lowing condition: When 2 or more indoor
units are connected to an outdoor unit, indoor controller board cannot receive a signal for 3 minutes
from outdoor controller circuit board, a
signal which allows outdoor controller cir-
cuit board to transmit signals.
Indoor controller board
Abnormal if data cannot be read normally from the nonvolatile memory of the indoor controller board.
1 Defective indoor controller
board
1 Replace indoor controller board.
Remote controller control board
1 Abnormal if data cannot be read nor-
mally from the nonvolatile memory of the remote controller control board.
(Check code: E1)
2 Abnormal if the clock function of remote
controller cannot be operated normally.
(Check code: E2)
1 Defective remote controller 1 Replace remote controller.
E3
or
E5
Remote controller transmission error(E3)/signal receiving error(E5)
1 Abnormal if remote controller could not
find blank of transmission path for 6 sec-
onds and could not transmit. (Check code: E3)
2 Remote controller receives transmitted
data at the same time and compares the
received and transmitted data. Abnormal
if these data are judged to be different
30 continuous times. (Check code: E3) 1 Abnormal if indoor controller board could
not find blank of transmission path. (Check code: E5)
2
Indoor controller board receives transmitted
data at the same time and compares the
received and transmitted data. Abnormal
if these data are judged to be different 30
continuous times. (Check code: E5)
1 Set a remote controller to main, and the
other to sub.
2 Remote controller is connected with only one
indoor unit.
3 The address changes to a separate setting.
4–6 Diagnose remote controller.
a) When “RC OK” is displayed, remote con-
trollers have no problem. Turn the power off,and on again to check. When becoming abnormal again, replace
indoor controller board. b) When “RC NG” is displayed, replace
remote controller. c)
When “RC E3” or “ERC 00-66” is dis-
played, noise may be causing abnormality.
1 2 remote controllers are set as
“main.” (In case of 2 remote con­ trollers) 2 Remote controller is connected
with 2 indoor units or more. 3 Repetition of refrigerant
address 4 Defective transmitting receiving
circuit of remote controller 5 Defective transmitting receiving
circuit of indoor controller board 6
Noise has entered into transmis-
sion wire of remote controller.
PL
Abnormal refrigerant circuit
During Cooling, Dry, or Auto Cooling
operation, the following conditions are regarded as failures when detected for 1 second.
a) The compressor continues to run for 30
or more seconds.
b) The liquid pipe temperature or the
condense/evaporator temperature is 167°F [75°C] or more.
These detected errors will not be cancelled until the power source is reset.
Abnormal operation of 4-way
valve
Disconnection of or leakage in
refrigerant pipes
Air into refrigerant piping Abnormal operation (no
rotation) of indoor fan
· Defective fan motor
· Defective indoor control board
Defective refrigerant circuit
(clogging)
When this error occurs, be sure to
replace the 4-way valve.
Check refrigerant pipes for disconnection or
leakage.
After the recovery of refrigerant, vacuum
dry the whole refrigerant circuit.
Refer to "9-6-2. DC fan motor (fan motor/
indoor controller circuit board".
Check refrigerant circuit for operation.
To avoid entry of moisture or air into
refrigerant circuit which could cause abnormal high pressure, purge air in refrigerant circuit or replace refrigerant.
OCH580
Page 23
23
Note: Refer to the manual of outdoor unit for the detail of remote controller.
(1)Upward/downward vane performance failure
The vane is not downward during defrosting and heat
preparation and when the thermostat is OFF in HEAT mode. (Working of COOL protection function)
Vane motor does not rotate.
Defective vane motor
Breaking of wire or connection failure of connector
Upward/downward vane does not work.
The vane is set to fixed position.
Normal operation (The vane is set to
horizontal regardless of remote control.)
Check (left).
Check the vane motor. (Refer to “How
to check the parts”.)
Check for breaking of wire or connec-
tion failure of connector.
Normal operation (Each connector on
vane motor side is disconnected or set­ting the fixed vanes by wired remote controller.)
Phenomena
Cause
Countermeasure
(2)Receiver for IR wireless remote controller
Weak batteries of IR wireless remote controller
Contact failure of connector (CNB) on IR wireless
remote controller board (Insert failure)
Contact failure of connector (CN90) on indoor con-
troller board (Insert failure)
Contact failure of connector between IR wireless
remote controller board and indoor controller board
Replace batteries of IR wireless remote
controller.
Check contact failure of each connector. If no problems are found of connector,
replace indoor controller board.
When the same trouble occurs even if
indoor controller board is replaced, replace IR wireless remote controller board.
9-4. TROUBLESHOOTING BY INFERIOR PHENOMENA
OCH580
Page 24
24
9-5. EMERGENCY OPERATION
9-5-1. When IR wireless remote controller fails or its battery is exhausted
9-5-2. When wired remote controller or indoor unit microprocessor fails
When the remote controller cannot be used
A
DEFROST/STAND BY lamp (ORANGE)
B
Operation lamp (GREEN)
C
Emergency operation switch (cooling/heating)
D
Receiver
[Heat pump type]
[Cooling Only type]
Operation Monitor Display
GREEN ORANGE
STOP
COOL
HEAT
OFF ON
Details of emergency mode are as shown below.
Operation Mod Set Temperature
Fan Speed
COOL HEAT
75°F [24°C] 75°F [24°C]
High High
Airflow Direction Up and Down Horizontal
Cooling Heating Stop
Cooling Stop
Each press of the emergency operation switch will toggle the
operation mode.
Check “COOL/HEAT” with the operation monitor display. (The display will
appear orange for 5 seconds after pressing the emergency operation switch.)
Downward
When the batteries of the remote controller run out or the remote controller malfunctions, the emergency operation can be done using the emergency buttons.
The orange lamp follows the switch operation as indicated at the left for 5 sedonds, and then it will return to the normal display.
B A
D
C
E.O. SW
1. When the wired remote control or the indoor unit microprocessor has failed, but all other components work properly, if you set the switch (SWE) on the indoor controller board ON, the indoor unit will begin Emergency Operation. When Emergency Operation is activated, the indoor unit operates as follows: (1) Indoor fan is running at high speed. Note on the IR wireless remote control: when the remote control does not function, it is possible to activate Emergency Operation by using the indoor unit emergency operation switch. However, if the indoor unit microprocessor has failed, it is nesessary to proceed with points 2 and 3 below as in the case of the wired remote control.
2. When you activate Emergency Operation of the cooling or heating, you have to set the switch (SWE) on the indoor controller board and activate Emergency Operation of the outdoor unit. For details on how to activate Emergency Operation of the outdoor unit, refer to the outdoor unit wiring diagram.
3. Before you activate Emergency Operation, check the following points: (1) Emergency Operation cannot be activated when:
• the outdoor unit malfunctions. • the indoor fan malfunctions.
• when it has detected the malfunction of drain pump during self-diagnosing.
(2) Emergency Operation becomes continuous only by switching the power source on/off. ON/OFF on the remote control or temperature control, etc. does not function. (3) Avoid operating for a long time when the outdoor unit begins defrosting while Emergency Operation of the heating is activated, because it will start to blow cold air. (4) Emergency cooling should be limited to 10 hours maximum (The indoor unit heat exchanger may freeze). (5) After Emergency Operation has been deactivated, set the switches etc. to their original positions. (6) Movement of the vanes does not work in Emergency Operation, thereforeyou have to slowly set them manually to the appropriate position.
OCH580
Page 25
25
9-6. HOW TO CHECK THE PARTS
Parts name Check points
Vane motor (MV)
Measure the resistance between the terminals with a tester. (Coil temperature 77_F [25°C])
Normal
350 " ± 7%
Abnormal
1-2
Brown-Red
1-3
Brown-Orange
1-4
Brown-Yellow
1-5
Brown-Green
Open or short
Fan motor (MF)
2
Red
4
Yellow
1
Brown
Orange
3
Green
5
Connect pin No.
M
Refer to “9-6-2. DC Fan motor (fan motor/indoor controller circuit board)”.
Disconnect the connector then measure the resistance with a tester. (At the ambient temperature 50 to 86_F [10 to 30°C])
(Refer to “9-6-1. Thermistor”.)
Room temperature thermistor (TH1) Liquid pipe thermistor (TH2) Condenser/evaporator temperature thermistor (TH5)
Normal
4.3 to 9.6 k"
Abnormal
Open or short
9-6-1. Thermistor
<Thermistor Characteristic graph>
Room temperature thermistor (TH1) Pipe temperature thermistor/liquid (TH2) Condenser/evaporator temperature thermistor (TH5)
Thermistor R
0=15 k ± 3%
Fixed number of B=3480 ± 2%
t(
)Rt=15exp { 3480( ) }
Thermistor for lower temperature
1
273+t1273
0
10
20
30
40
50
-20 -10 0 10 20 30 40 50
-4 -14 32 50 68 86 104122 °F Temperature
Resistance (k )
<Thermistor for lower temperature>
1
273+
1
273
T-32
1.8
°C
"
32°F [0°C] 50°F [10°C] 68°F [20°C] 77°F [25°C] 86°F [30°C] 104°F [40°C]
15 k"
9.6 k"
6.3 k"
5.4 k"
4.3 k"
3.0 k"
PKA-A12HA6 PKA-A18HA6
OCH580
Page 26
26
9-6-2. DC Fan motor (fan motor/indoor controller circuit board)
Notes
· High voltage is applied to the connecter (CNMF) for the fan motor. Pay attention to the service.
· Do not pull out the connector (CNMF) for the motor with the power supply on. (It causes trouble of the indoor controller circuit
board and fan motor.)
Self check Symptom : The indoor fan cannot rotate.
Yes
NG
NG
Wiring contact check
Contact of fan motor connector (CNMF)
Power supply check (Remove the connector (CNMF))
Measure the voltage in the indoor controller circuit
board.
TEST POINT
1 : VDC (between 1 (+) and 3 () of the fan connector): VDC 294–325 V DC
TEST POINT 2 : VCC (between 4 (+) and 3 () of the fan connector): VCC 15 V DC
Wiring recovery
Replace the indoor controller board.
Replace the fan motor.
Replace the indoor
controller board.
Replace the fan motor.
Is the voltage normal?
Is there contact failure?
No
1
2
Yes
No
Check the operation of fan. END
Yes
OK
Check the operation END
OK
Check method of DC fan motor (fan motor/indoor controller circuit board)
Sensor signal check
Measure the voltage between CNMF
6 and 3 0 and
15 V DC in the indoor controller circuit board.
Does the voltage repeat 0 and 15 V DC?
No
Yes
Indoor controller board fuse check
Is the fuse normal?
Replace
the fuse.
Check the operation END
OK
Replace the indoor
controller board.
Check the operation
END
OK
NG
Replace the fan motor.
Yes
No
NG
OCH580
Page 27
27
9-7. TEST POINT DIAGRAM
Indoor controller board
PKA-A12HA6 PKA-A18HA6
{
CN51
Centrally control
12: Control signal
13 V DC pulse input (1: +)
34: Operation indicator
13 V DC (3: +)
35: Malfunction indicator
13 V DC (3: +)
CN44
Pipe temperature thermistor
1–2: Liquid (TH2) 3–4:
Condenser/Evaporator
(TH5)
CN20
Room temp. thermistor (TH1)
CN90
Connect to the remote operation adapter
CNMF
Connect to the fan motor (MF)
1–3: 294–325 V DC 4–3: 15 V DC 5–3: 0–6.5 V DC 6–3: 0
or 15 V DC
FUSE
(3.15 A, 250 V)
SWE
Emergency operation connector
SW1
Model selection
SW2
Capacity setting
CN151
Connect to the vane motor (MV)
Jumper wire J41,J42
Pair No. setting for IR wireless remote controller
CN01
Connect to the Terminal block (TB4) 13: 208/230 V AC
LED1:Power supply (I.B) LED2:Power supply (R.B) LED3:Transmission
(Indoor/outdodr)
CN3C
Transmission (Indoor/outdodr) (DC 0~24V)
CN30
Connector (LLC)
CN22
Connect to the terminal block (TB5) (Remote controller connecting wire)
CN2L
Connector (LOSSNAY)
SWE2
Emergency operation switch
CN41
Connector (HA terminal-A)
IR wireless remote controller board
CN32
Remote switch
CN152 Connector (Back-up heating)
CN105 RFI (Radio frequency interface)
OCH580
Page 28
28
9-8. FUNCTIONS OF DIP SWITCH AND JUMPER WIRE
Each function is controlled by the DIP switch and the jumper wire on indoor controller board.
PKA-A12HA6 PKA-A18HA6
SW1
Setting by the DIP switch and jumper wire
Functions
Jumper wire
Model settings
Capacity settings
Pair number setting with IR wireless remote controller
Remarks
SW2
J41 J42
Indoor controller board type setting
JP3
0 1 2
3–9
Wireless remote controller setting
Control PCB setting
J41 J42
<Initial setting> IR wireless remote controller: 0 Control PCB: (for both J41 and J42) 4 pair number settings are supported. The pair number settings of the wireless remote controller and indoor control PCB (J41/J42) are given in the table on the left. (' ' in the table indicates the jumper wire is dis­connected.)
Jumper wire ( : Short : Open)
For product
Spare parts
Indoor controller board type
JP3
: With JP3 : Without JP3
MODEL
SETTING
PKA-A·HA6
MODEL
SETTING
PKA-A18HA6
ON OFF
1 2 3 4 5
ON OFF
1 2 3 4 5
ON OFF
1 2 3 4 5
PKA-A12HA6
The black square () indicates a switch position.
OCH580
Page 29
29
10
SPECIAL FUNCTION
Note:
· When the uint is restarted to operate after turning off the power or OFF operation, the unit which was operating will start oper­ation.
· To operate the main unit, refer to "10-1-2. How to set rotation function (Back-up function, 2nd stage cut-in function)", and set the request code No. which is not the same as the current one, and set again the former request code No.
(2) 2nd stage cut-in function
Outline of functions
· When the 1st unit can NOT supply with sufficient capacity for exceptionally high-demand conditions and the actual room temperature reaches set point *, the 2nd unit starts operation in conjunction with the 1st unit.
· Once the actual room temperature goes down to 7.5°F [4:] below set point*, the 2nd unit stops operation automatically. (* set point = set temperature by R/C (remote controller) + 7.5, 10.8, 14.4°F [4, 6, 8:] (selectable))
· Number of operating units is determined according to the room temperature and set point.
· When room temperature becomes higher than set point, standby unit starts. (2 units operation)
· When room temperature falls below set point −7.5°F [−4:], standby unit stops. (1 unit operation)
10-1. Rotation Function (and back-up function, 2nd stage cut-in function)
This function is only available when using wired remote controller.
10-1-1. Operation
(1) Rotation function (and Back-up function)
Outline of functions
· Main and sub units operate alternately according to the interval of rotation setting. Note: Main and sub unit should be set by refrigerant address. (Outdoor DIP switch setting)
Refrigerant address "00"
Main unit
Refrigerant address "01"
Sub unit
· When error occurs to one unit, another unit will start operation. (Back-up function)
System constraint
· This function is available only by the grouping control system (INDOOR UNIT: OUTDOOR UNIT=1:1) of 2 refrigerant groups. (Refer to Fig. 1)
· Main indoor unit should be connected for wired remote controller and the transmission line (TB5) for main and sub unit should also be connected. (Refer to Fig. 1)
(This function cannot be set by IR wireless remote controller.)
· Set refrigerant address of each unit. (DIP switch on the outdoor unit ··· Refrigerant address 00/01)
Operation pattern
OC-1
OC-2
IC-1
IC-2
3(2)
3(2)
2
RC
2
Main unit
Sub unit
Refrigerant address "01"
Refrigerant address "00"
Fig. 1
1 [Back-up function only]··· Request code number "312"
2
[Rotation function] & [Back-up function]··· Request code number "313–318"
(Ex:When the request code number is "313", each unit operates alternately in daily cycle.)
Error occurs on main unit.
Start operation
Run
Abnormal condition
Stop
Run
Main
unit
IC-1
Sub
unit
IC-2
Error occurs on main unit.
Start operation
1–28 days 1–28 days
Run
Abnormal condition
Stop
Stop
Run
Run
Stop Run
Main
unit
IC-1
Sub
unit
IC-2
Main Sub
Main Sub Sub Main Main Sub
OC : Outdoor unit IC : Indoor unit RC : Wired remote controller
OCH580
Page 30
30
System constraint
· This function is available only in cooling mode.
Ex.) Set temp. by R/C = 68°F [20:]
Set point = 79°F [26:] When request code number is “323”.
79°F 2nd unit Cut-in
7.5°F
71.5°F 2nd unit Cut-out
68°F
10-1-2. How to set rotation function (Back-up function, 2nd stage cut-in function)
You can set these functions by wired remote controller. (Maintenance monitor)
Both main and sub unit should be set in same setting. Every time replacing indoor controller board for servicing, the function should be set again.
NOTE
Setting No.
(Request code)
Setting contents
Initial
setting
No.1 (310)
Monitoring the request code of current setting
No.2 (311)
Rotation and Back-up OFF (Normal group control operation)
No.3 (312)
Back-up function only
No.4 (313)
Rotation ON (Alternating interval = 1day) and back up function
No.5 (314)
Rotation ON (Alternating interval = 3day) and back up function
No.6 (315)
Rotation ON (Alternating interval = 5day) and back up function
No.7 (316)
Rotation ON (Alternating interval = 7day) and back up function
No.8 (317)
Rotation ON (Alternating interval = 14day) and back up function
No.9 (318)
Rotation ON (Alternating interval = 28day) and back up function
Setting No.
(Request code)
Setting contents
Initial
setting
No.1 (320)
Monitoring the request code of current setting
No.2 (321)
Cut-in function OFF
No.3 (322)
Cut-in Function ON(Set point = Set temp.+ 7.5°F [4°C])
No.4 (323)
Cut-in Function ON(Set point = Set temp.+ 10.8°F [6°C])
No.5 (324)
Cut-in Function ON(Set point = Set temp.+ 14.4°F [8°C])
(1) Request Code List
Rotation setting
2nd stage cut-in setting
[2nd stage cut-in function]··· Request code number "322–324"
Start operation Sub unit start operation
Room temp. ] Set point
Sub unit stop
Run
Stop StopRun
Main
unit IC-1
Sub unit IC-2
Room temp. < Set point 7.5°F [4:]
[20:]
[22:]
[4:]
[26:]
OCH580
Page 31
31
10-2. BACK-UP HEATING FUNCTION (CN152)
10-2-1. Operation
Outline of functions
The back-up heater signal is sent out according to the tempera­ture difference between indoor room temperature and set tem­perature. This function is available only in heating operation.
10-2-2. How to connect
When connecting to the connector CN152 of the indoor unit, use PAC-SE59RA-E(optional parts).
Z [ 0˚C [˚F]
0 < Z < 2.5˚C [4.5˚F]
2.5˚C [4.5˚F] [ Z
OFF
Keeping condition
ON
1
2
3
Temperature difference
[Z=Set temp. - Room temp.]
Back-up heater
signal output
Z 0 2.5˚C [4.5˚F]
OFF
ON
1
Press the button.
2
Select "Service" with the [Cursor] buttons (
F1
andF2) or the [Page] buttons (
F3
andF4), and press the button.
PAR-31MAA
F1 F2 F3 F4
Main menuMain 3/3
Main display:
Cursor Page
Maintenance Initial setting Service
Service menu
Select:
Cursor
Enter maintenance password
9999
Service menu 1/2
Main menu:
Cursor
Test run Input maintenance info. Function setting Check Self check
Check menu 1/1
Service menu:
Cursor
Error history Refrigerant volume check Refrigerant leak check Smooth maintenance Request code
Request code
Request:
Cursor
Ref.address 0 Request code 004
3
Enter the current maintenance password (4 numerical digits).
• Move cursor to the digit you wat to change with the F1orF2 button.
• Set each number (0 through 9) with the
F3
or
F4
button.
(Note: The initial maintenance password is "9999".)
4
Then, press the button.
5
Select "Check" with theF1orF2 button, and press the button.
6
Select "Request code" with theF1orF2 button, and press the button.
7
Set the Refrigerant address and Request code.
• Select the item to be changed with the
F1orF2
button.
• Select the required setting with the
F3
or
F4
button.
8
Press the F3or
F4
button to set the Refrigerant address "0".
9
Press the F3or
F4
button to set the desired request code No.
• Rotation & Back up operation: Enter one request code from 311–318.
• 2nd stage cut-in operation: Enter one request code from 321–324.
0
Press the button. Data will be collected and displayed.
1
Press the F3orF4 button to set the Refrigerant address "1".
Set above
9–0
.
2
To return to the Main menu, press the button.
(2) Rotation and back up operation
OCH580
Page 32
32
DISASSEMBLY PROCEDURE
11
Be careful when removing heavy parts.
Push
Push
Down
Be careful not to damage the airflow adjustment plate with the screw driver.
Corner hole
1. REMOVING THE LOWER SIDE OF THE INDOOR UNIT FROM THE INSTALLATION PLATE
(1) Remove the front panel. (2) Insert the screw driver to the corner hole at both left and
right side as shown in the figure 1. (3) Push it up, then pull down the lower side of indoor unit and remove the hook.
Figure 1
2. REMOVING THE FRONT PANEL
(1) Press and unlock the knobs on both sides of the front
panel and lift the front panel until it is level. Pull the hinges forward to remove the front panel. (See Photo 2)
(2) Move the horizontal vanes in a downward direction. (3) Remove the screw caps of the panel. Remove the screws. (See Photo 1) (4) Hold the lower part of both ends of the panel and pull it
slightly toward you, and then remove the panel by pushing it upward.
Photo 1
Front panel
Screw caps
Vanes
Photo 2
PKA-A12HA6 PKA-A18HA6
PHOTOS & ILLUSTRATIONSOPERATION PROCEDURE
OCH580
Page 33
3333
4. REMOVING THE ELECTRICAL BOX
(1) Remove the front panel. (Refer to step 2)
(2) Remove the electrical box covers. (See Photo 3) (3) Remove the nozzle assembly. (Refer to step 5) (4) Disconnect the connecting wire from terminal block (TB4)
and terminal block for MA-remote controller (TB5). (5) Disconnect the connectors on the indoor controller board. (6) Disconnect the connector for the ground wire. (See Photo 5) (7) Pull the disconnected lead wire out from the electrical box. (8) Remove the screw of electrical box. (See Photo 6) (9) Push up the upper fixture (See Photo 5) catch to remove
the box, then pull the right fixture (See Photo 4) and remove it from the box fixture.
Photo 5
Connector for ground wire
Photo 6
Screw (Electrical box)
Photo 3
3. REMOVING THE INDOOR CONTROLLER BOARD AND IR WIRELESS CONTROLLER BOARD
(1) Remove the front panel. (Refer to step 2) (2) Remove the room temp. thermistor TH1. (see Photo 3) (3) Remove the electrical box covers (screw 4 × 12). (See Photo 3) (4) Disconnect the connectors on the indoor controller board. (5) Remove the switch board cover. (6) Pull out the indoor controller board toward you, then disconnect the rest of connectors. Remove the indoor controller board and switch board. (7) Remove the holder of IR wireless controller board. (8) Disconnect the connector of IR wireless controller board
and remove the IR wireless controller board from the holder.
Indoor controller board (I.B)
Terminal block (TB4)
Photo 4
Fixture (right)
Fixture (upper)
Terminal block (TB5)
Terminal block (TB4)
Electrical box cover (top)
Electrical box cover (side)
Screw (side cover)
Holder of IR wireless controller board
Screw (side cover)
Switch holder
Nozzle assembly
Screw (top cover)
Room temp. thermistor (TH1)
Thermistor holder
PHOTOSOPERATION PROCEDURE
OCH580
Page 34
34
5. REMOVING THE NOZZLE ASSEMBLY (with VANE and VANE MOTOR) AND DRAIN HOSE
(1) Remove the front panel (Refer to step 2). (2) Remove the electrical box cover. (3) Disconnect the vane motor connector (CN151) on the indoor controller board. (4) Remove the corner box. (5) Pull the nozzle assembly and detach. (6) Push the fixture and remove the drain hose.
6. REMOVING THE INDOOR FAN MOTOR AND THE LINE FLOW FAN
(1) Remove the front panel (Refer to step 2) and the corner
box at right lower side.
(2) Remove the electrical box (Refer to step 4) and the nozzle
assembly (Refer to step 5). (3) Remove the screws fixing the motor bed. (See Photo 8) (4) Loosen the screw fixing the line flow fan. (See Photo 9) (5) Remove the motor bed together with fan motor and motor
band. (6) Release the hooks of the motor band. Remove the motor
band. Pull out the indoor fan motor. (7)
Remove the screws fixing the left side of the heat exchanger. (See Photo 10) (8) Lift the heat exchanger, and pull out the line flow fan to the
lower-left.
Photo 8
Photo 9
7. REMOVING THE VANE MOTOR
(1) Remove the nozzle assembly. (Refer to step 5) (2) Remove the screws of the vane motor unit, and pull out
the vane motor unit. (3) Remove the screws of the vane motor unit cover. (4) Remove the vane motor from the vane motor unit. (5) Disconnect the connector from the vane motor.
Photo 7
Screw of the line flow fan
Photo 10
Screws of the left side of the heat exchanger
Electrical box cover (top)
Electrical box cover (side)
Screw (side cover)
Screw (top cover)
Switch board cover
Holder of IR wireless controller board
Nozzle assembly
Screws of the vane motor unit
Screws of the vane motor unit cover
Photo 11
Screw (side cover)
Screws of the motor bed
Heat exchanger
Water cover
Motor band
PHOTOSOPERATION PROCEDURE
OCH580
Page 35
35
8. REMOVING THE LIQUID PIPE THERMISTOR AND COND/EVA TEMP. THERMISTOR
(1) Remove the front panel. (Refer to step 2) (2) Remove the electrical box cover. (3) Remove the motor band. (4) Cut the wiring fixed band. (5)
Remove the liquid pipe thermistor and cond/eva temp. ther-
mistor. (6) Disconnect the connector (CN44) on the indoor controller board.
Photo 12
Liquid pipe thermistor (TH2)
Condenser/evaporator temp. thermistor (TH5)
Heat exchanger
9. REMOVING THE HEAT EXCHANGER
(1) Remove the front panel (Refer to step 2) and the corner
panel at right lower side. (2) Remove the electrical box (Refer to step 4) and the nozzle assembly (Refer to step 5). (3) Remove the motor band. (4) Remove the pipe thermistors (Refer to step 8). (5) Disconnect the connector (CN60) on the indoor controller board and the connector for ground wire. (See Photo 5) (6) Remove the screws fixing the left side of the heat exchanger. (See Photo 9) (7) Remove the heat exchanger.
10. REMOVING THE ROOM TEMPERATURE THERMISTOR
(1) Remove the front panel (Refer to step 2). (2) Remove the electrical box cover. (3) Remove the room temperature thermistor. (4) Disconnect the connector (CN20) on the indoor controller board.
Photo 13
Photo 14
Electrical box cover (top)
Electrical box cover (side)
Screw (side cover)
Screw (top cover)
Switch board cover
Holder of IR wireless controller board
Nozzle assembly
Water cover
Screw (side cover)
Heat exchanger
Electrical box cover (top)
Electrical box cover (side)
Screw (side cover)
Screw (side cover)
Switch holder
Nozzle assembly
Screw (top cover)
Room temp.
thermistor (TH1)
Thermistor holder
Holder of IR wireless controller board
PHOTOSOPERATION PROCEDURE
OCH580
Page 36
HEAD OFFICE : TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
CCopyright 2014 MITSUBISHI ELECTRIC CORPORATION Distributed in Dec. 2014 No. OCH580 Made in Japan
New publication, effective Dec. 2014 Specifications are subject to change without notice.
Loading...