Radio frequency interfaceWired remote controllerIR wireless remote controller
OCH481
OCB481
COOL
DRY
AUTO
FAN
HEAT
RF thermostat
TEMP.
ON/OFF
2
Page 3
2
SAFETY PRECAUTION
2-1. ALWAYS OBSERVE FOR SAFETY
Before obtaining access to terminal, all supply
circuits must be disconnected.
2-2. CAUTIONS RELATED TO NEW REFRIGERANT
Cautions for units utilising refrigerant R410A
Use new refrigerant pipes.
Make sure that the inside and outside of refrigerant piping is clean and it has no contaminants
such as sulfur, oxides, dirt, shaving particles, etc,
which are hazards to refrigerant cycle.
In addition, use pipes with specified thickness.
Contamination inside refrigerant piping can cause deterioration of refrigerant oil etc.
Store the piping to be used indoors during
installation, and keep both ends of the piping
sealed until just before brazing. (Leave elbow
joints, etc. in their packaging.)
If dirt, dust or moisture enters into refrigerant cycle, that can
cause deterioration of refrigerant oil or malfunction of compressor.
The refrigerant oil applied to flare and flange
connections must be ester oil, ether oil or
alkylbenzene oil in a small amount.
If large amount of mineral oil enters, that can cause deterioration of refrigerant oil etc.
Do not use refrigerant other than R410A.
If other refrigerant (R22 etc.) is used, chlorine in refrigerant can cause deterioration of refrigerant oil etc.
Use a vacuum pump with a reverse flow check
valve.
Vacuum pump oil may flow back into refrigerant cycle and
that can cause deterioration of refrigerant oil etc.
Use the following tools specifically designed for
use with R410A refrigerant.
The following tools are necessary to use R410A refrigerant.
If dirt, dust or moisture enters into refrigerant cycle, that can
cause deterioration of refrigerant oil or malfunction of compressor.
Charge refrigerant from liquid phase of gas
cylinder.
If the refrigerant is charged from gas phase, composition
change may occur in refrigerant and the efficiency will be
lowered.
[1] Cautions for service
(1) Perform service after recovering the refrigerant left in unit completely.
(2) Do not release refrigerant in the air.
(3) After completing service, charge the cycle with specified amount of refrigerant.
(4) When performing service, install a filter drier simultaneously.
Be sure to use a filter drier for new refrigerant.
Do not use a charging cylinder.
If a charging cylinder is used, the composition of refrigerant will change and the efficiency will be lowered.
Ventilate the room if refrigerant leaks during
operation. If refrigerant comes into contact with
a flame, poisonous gases will be released.
3
Page 4
[2] Additional refrigerant charge
When charging directly from cylinder
· Check that cylinder for R410A on the market is syphon type.
· Charging should be performed with the cylinder of syphon stood vertically. (Refrigerant is charged from liquid phase.)
Unit
Gravimeter
[3] Service tools
Use the below service tools as exclusive tools for R407C refrigerant.
No.Tool nameSpecifications
Gauge manifold· Only for R410A
1
· Use the existing fitting
· Use high-tension side pressure of 5.3MPa·G or over.
Charge hose· Only for R410A
2
· Use pressure performance of 5.09MPa·G or over.
Electronic scale
3
Gas leak detector
4
Adaptor for reverse flow check
5
Refrigerant charge base
6
Refrigerant cylinder· Only for R410A · Top of cylinder (Pink)
7
Refrigerant recovery equipment
8
· Use the detector for R134a, R407C or R410A.
· Attach on vacuum pump.
· Cylinder with syphon
specifications
—
—
—
. (UNF1/2)
3
PART NAMES AND FUNCTIONS
Indoor Unit
Air outlet
Vane
4
Louver
Air intake
Filter
(Inside of Air intake)
Page 5
Wiredremote controller (Option)
Display Section
For purposes of this explanation,
all parts of the display are shown
as lit. During actual operation, only
the relevant items will be lit.
Identifies the current operation
Shows the operating mode, etc.
*Multilanguage display is available.
“Centrally Controlled” indicator
Indicates that operation from the
remote controller has been prohibited by a master controller.
“Timer is Off” indicator
Indicates that the timer is off.
Temperature Setting
Shows the target temperature.
Day-of-Week
Shows the current day of the week.
Time/Timer Display
Shows the current time, unless the simple or Auto Off
timer is set.
If the simple or Auto Off timer is set, the time to be
switched off is shown.
Up/Down Air Direction indicator
The indicator shows the direction of the outcoming airflow.
“One Hour Only” indicator
Displays if the airflow is set to
Low or downward during COOL
or DRY mode. (Operation varies
according to model.)
The indicator goes off in one hour,
at which time the airflow direction
also changes.
TIME SUN MON TUE WED THU FRI SAT
TIMER
AFTER
ERROR CODE
°F°C
ONLY1Hr.
ON
Hr
OFF
AFTER
°F°C
FUNCTION
FILTER
WEEKLY
SIMPLE
AUTO OFF
Room Temperature display
Shows the room temperature. The room
temperature display range is 46-102°F.
The display blinks if the temperature
is less than 46°F or 102°F or more.
Louver display
Indicates the action of the swing louver.
Does not appear if the louver is not
running.
(Power On indicator)
Indicates that the power is on.
“Sensor” indication
Displayed when the remote controller
sensor is used.
“Locked” indicator
Indicates that remote controller buttons have been locked.
“Clean The Filter” indicator
To be displays on when it is time to
clean the filter.
Timer indicators
The indicator comes on if the corresponding timer is set.
Fan Speed indicator
Shows the selected fan speed.
Ventilation indicator
Appears when the unit is running in
Ventilation mode.
Operation Section
Temperature setting buttons
Down
Up
Timer Menu button
(Monitor/Set button)
Mode button (Return button)
Set Time buttons
Back
Timer On/Off button
(Set Day button)
Opening the
cover
Note:
●
“PLEASE WAIT” message
Ahead
TEMP.
MENU
BACKDAY
MONITOR/SET
PAR-21MAA
CLOCK
ON/OFF
OPERATION
ON/OFF
FILTER
CHECK
TEST
CLEAR
Built-in temperature sensor
This message is displayed for approximately 3 minutes when power is supplied to the indoor unit or when the unit is recovering from a power failure.
●
“NOT AVAILABLE” message
This message is displayed if an invalid button is pressed (to operate a function that the indoor unit does not have).
If a single remote controller is used to operate multiple indoor units simultaneously that are different types, this message will not be displayed as
far as any of the indoor units is equipped with the function.
ON/OFF button
Fan Speed button
Filter button
(<Enter> button)
Test Run button
Check button (Clear button)
Airflow Up/Down button
Louver button
( Operation button)
To return operation
number
Ventilation button
( Operation button)
To go to next operation
number
5
Page 6
IR wirelessremote controller (Option)
CHECK
TEST RUN
Indicate that the unit is being checked or
test-run.
MODEL SELECT
Blinks when model is selected.
display
display
display
Lights up while the signal is transmitted to
the indoor unit when the button is pressed.
Temperature setting display
Indicates the desired temperature setting
which is set.
OPERATION MODE display
OPERATION MODE display
Indicates which operation mode is in effect.
display
The vertical direction of airflow is indicated.
display
Displays selected fan speed.
ON/OFF button
The unit is turned ON and OFF alternately
each time the button is pressed.
FAN SPEED SELECT button
Changes the fan speed.
MODE SELECT button
Switches the operation mode between
COOLING/DRY/FAN/HEATING and AUTO
mode.
+In case the outdoor unit is cooling only
type, the heating and auto mode are not
available.
COOL
DRY
AUTO
FAN
HEAT
RUN
MODEL
SELECT
FAN
SWING
NOT AVAILABLE
TEST
CHECK
ON/OFF TEMP
FAN
MODE
CHECK
VAN E
LOUVER
TEST RUN
RESETSETCLOCK
°F
°C
AMPMSTOP
AMPM
START
AUTO STOP
AUTO START
min
CLOCK display
Displays the current time.
TIMER display
Displays when in timer operation or when
setting timer.
“” “ ” display
Displays the order of timer operation.
“ ” “ ” display
Displays whether timer is on or off.
button
Sets any desired room temperature.
TIMER CONTROL buttons
h
AUTO STOP (OFF timer): when this switch
is set, the air conditioner will be
autom aticall y stopped at the preset time.
AUTO START (ON timer): when this switch is
set, the air conditioner will be automatically
started at the preset time.
"h" and "min" buttons
Buttons used to set the “hour and minute” of
the current time and timer settings.
CHECK-TEST RUN button
Performs an inspection check or test
operation. Do not use it for normal
operation.
(optional parts),
remove the
jumper
connector
CN4F and fit
the drain float
switch (FS).
2
1
TB6
R.B
Pair No.
CN2L
21
(RED
)
FLOAT SW
CN4F
(WHT
TRANSMISSION
WIRES
DC12V
CN32
J42J41
)
FLOAT SW
)
(WHT
113
CN51 (WHT
)
51
CN41 (WHT
41
SWE
ON OFF
4
When attaching
drain pump
(optional parts)
14
CN4F
(
WHT
FS
)
TB5
CN24
(
YLW
)
2
1
)
12
REMOCON
LIQUID/PIPE
<Table 1> SW1 (MODEL SELECTION)
SW1
Service
12345
ON
OFF
2
3
1
INDOOR/OUTDOOR
COMMUNICATION
CN3C
BLU
(
21
CN22
(
BLU
)
INTAKE
CN20
CN44
(RED
(WHT
)
14
t°t°t
TH2 TH5 TH1
21
°
+
Be sure to turn off the source power
)
CN30
GRN
)
(
)
1
135
OUTDOOR
CN01
BLK
)
(
DC294~325V
RECTIFICATION
FAN
CNMF
(WHT
)
741
MS
3~
MF
331
M
1~
DP
(OPTIONAL PARTS)
X1
D.U.M
(BLU
FUSE
CNP
YLW
ORN
ORN
BRN
)
and then disconnect fan motor connector.
(Failure to do so will cause trouble in Fan motor)
YLW
ORN
TB4
S1
S2
S3
+1
TO OUTDOOR
UNIT
1. SymboIs used in wiring diagram above are, : Connector, :Terminal block.
Notes:
2. Indoor and outdoor connecting wires are made with poIarities, make wiring matching terminal numbers (S1, S2, S3).
3. Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric wiring for servicing.
+
1 : Use copper supply wire.
12
Page 13
REFRIGERANT SYSTEM DIAGRAM8
PCA-A24KA4 PCA-A30KA4 PCA-A36KA4 PCA-A42KA4
Strainer
Heat exchanger
Room temperature
thermistor (TH1)
Condenser/evaporator
temperature thermistor
(TH5)
Pipe temperature
thermistor/liquid
(TH2)
Distributor
with strainer 1/2
#50/#50
#50
Refrigerant GAS pipe connection
(Flare)
Refrigerant LIQUID pipe connection
(Flare)
Strainer
#50
Refrigerant flow in cooling
Refrigerant flow in heating
13
Page 14
TROUBLESHOOTING9
9-1. TROUBLESHOOTING
<Error code display by self-diagnosis and actions to be taken for service (summary)>
Present and past error codes are logged and displayed on the wired remote controller or controller board of outdoor unit.
Actions to be taken for service and the trouble reoccurrence at field are summarized in the table below. Check the contents
below before investigating details.
Unit conditions at service
The trouble is reoccurring.
The trouble is not reoccurring.
Error code
Displayed
Not displayed
Logged
Not logged
Actions to be taken for service (summary)
Judge what is wrong and take a corrective action
according to “9-3. Self-diagnosis action table”.
Conduct troubleshooting and ascertain the cause of the
trouble according to “9-4. Troubleshooting by inferior
phenomena”.
Consider the temporary defects such as the work of
protection devices in the refrigerant circuit including
compressor, poor connection of wiring, noise and etc.
Re-check the symptom, and check the installation
environment, refrigerant amount, weather when the
trouble occurred, matters related to wiring and etc.
Reset error code logs and restart the unit after finishing
service.
There is no abnormality in electrical component,
controller board,remote controller and etc.
Re-check the abnormal symptom.
Conduct trouble shooting and ascertain the cause of the
trouble according to “9-4. Troubleshooting by inferior
phenomena”.
Continue to operate unit for the time being if the cause
is not ascertained.
There is no abnormality concerning of parts such as
electrical component, controller board, remote controller
and etc.
1414
Page 15
9-2. MALFUNCTION-DIAGNOSIS METHOD BY REMOTE CONTROLLER
<In case of trouble during operation>
When a malfunction occurs to air conditioner, both indoor unit and outdoor unit will stop and operation lamp blinks to inform
unusual stop.
<Malfunction-diagnosis method at maintenance service>
■IR wireless remote controller
[Procedure]
CHECK
display
ON/OFF
button
CHECK
button
ON/OFF
MODE
CHECK
TEST RUN
SET
CHECK
FAN
VAN E
LOUVER
RESET
TEMP
AUTO STOP
AUTO START
CLOCK
h
min
Refrigerant
address
display
Temperature
button
HOUR
button
1. Press the CHECK button twice.
2. Press the temperature
buttons.
3. Point the remote controller at the
sensor on the indoor unit and
press the HOUR button.
• "CHECK" lights, and refrigerant
address "00" blinks.
• Check that the remote controller's
display has stopped before continuing.
• Select the refrigerant address of the
indoor unit for the self-diagnosis.
Note: Set refrigerant address using the
outdoor unit’s DIP switch (SW1).
(For more information, see the
outdoor unit installation manual.)
• If an air conditioner error occurs, the
indoor unit's sensor emits an intermit tent buzzer sound, the operation lamp
blinks, and the error code is output.
(It takes 3 seconds at most for error
code to appear.)
■Wired remote controller
ERROR CODE
TEMP.
MENU
MONITOR/SET
BACKDAY
PAR-21MAA
ON/OFF
CLOCK
OPERATION
ON/OFF
CHECK
CLEAR
4. Point the remote controller at the
• The check mode is cancelled.
sensor on the indoor unit and
press the ON/OFF button.
Turn on the power.
Press the [CHECK] button twice.
Set address with [TEMP] button if system control is used.
Press the [ON/OFF] button to stop the self-check.
CHECK button
Address
ERROR CODE
TEMP. button
IC : Indoor unit
OC: Outdoor unit
Check code
FILTER
TEST
ERROR CODE
Unit No.
Timer ON/OFF button
– – – – : No trouble generated in the past.
F F F F : No corresponding unit.
<To delete check code>
Display the error code on the self-check result display screen.
The address for self-check will blink when the ON/OFF
button is pressed twice within 3 seconds.
To be continued to the next page.
1515
Page 16
• Refer to the following tables for details on the check codes.
[Output pattern A]
Beeper sounds
OPERATION
INDICATOR
lamp blink
pattern
Beep
Self-check
starts
(Start signal
received)
Beep Beep BeepBeepBeep Beep
1st2nd3
Off
Approx. 2.5 sec.On0.5 sec.On0.5 sec.On0.5 sec.
Number of blinks/beeps in pattern indicates the check
code in the following table (i.e., n=5 for “P5”)
rd
th
n
On
0.5 sec.
[Output pattern B]
Beeper sounds
OPERATION
INDICATOR
lamp blink
pattern
Self-check
starts
(Start signal
received)
Off
Approx. 2.5 sec.OnApprox. 3 sec.On0.5 sec.On0.5 sec.On0.5 sec.
1st2nd3
Number of blinks/beeps in pattern indicates the check
code in the following table (i.e., n=5 for “U2”)
Forced compressor stop(due to water leakage abnormality)
6P6Freezing/Overheating protection operation
7EECommunication error between indoor and outdoor units
8P8Pipe temperature error
9E4, E5Remote controller signal receiving error
10
11
–
–
–
–
12FbIndoor unit control system error (memory error, etc.)
–
E0, E3
Remote controller transmission error
–E1, E2Remote controller control board error
nd
1st2
Off
Approx. 2.5 sec.On0.5 sec.On0.5 sec.
Number of blinks/beeps in pattern indicates
the check code in the following table
peeBpeeBpeeBpeeBpeeB
rd
th
n
On
0.5 sec.
Approx. 2.5 sec.OnApprox. 3 sec.On0.5 sec.On0.5 sec.
· · · Repeated
Off
Beep Beep
Number of blinks/beeps in pattern indicates
the check code in the following table
1st2
nd
· · · Repeated
krameRmotpmyS
[Output pattern B]
IR wireless remote controller
Errors detected by unit other than indoor unit (outdoor unit, etc.)
Wired remote controller
Beeper sounds/OPERATION
INDICATOR lamp blinks Check code
(Number of times)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
E9
UP
U3,U4
UF
U2
U1,Ud
U5
U8
U6
U7
U9,UH
–
–
Others
*1 If the beeper does not sound again after the initial
the OPERATION INDICATOR lamp does not come on,
Indoor/outdoor unit communication error
(Transmitting error) (Outdoor unit)
Compressor overcurrent interruption
Open/short of outdoor unit thermistors
Compressor overcurrent interruption (When compressor locked)
Abnormal high discharging temperature/49C operated/
insufficient refrigerant
Abnormal high pressure (63H operated)/Overheating
protection operation
Abnormal temperature of heatsink
Outdoor unit fan protection stop
Compressor overcurrent interruption/Abnormal of power module
Abnormality of superheat due to low discharge temperature
Abnormality such as overvoltage or voltage shortage and
abnormal synchronous signal to main circuit/Current sensor error
–
–
Other errors (Refer to the technical manual for the outdoor unit.)
2 beeps to confirm the self-check start signal was received and
there are no error records.
For details, check
the LED display
of the outdoor
controller board.
As for outdoor
unit, refer to
outdoor unit's
service manual.
*2 If the beeper sounds 3 times continuously “beep, beep, beep (0.4 + 0.4 + 0.4 sec.)” after the initial 2 beeps to confirm
the self-check start signal was received, the specified refrigerant address is incorrect.
krameRmotpmyS
16
Page 17
• On IR wireless remote controller
The continuous buzzer sounds from receiving section of indoor unit.
Blink of operation lamp
• On wired remote controller
Check code displayed in the LCD. (Refer to the previous page,check code.)
If the unit cannot be operated properly after the test run, refer to the following table to find out the cause.
•
Symptom
Wired remote controllerLED 1, 2 (PCB in outdoor unit)
PLEASE WAIT
PLEASE WAIT
Display messages do not
appear even when operation
switch is turned ON (operation
lamp does not light up).
On the IR wireless remote controller with condition above, following phenomena take place.
• No signals from the remote controller can be received.
• OPE lamp is blinking.
• The buzzer makes a short ping sound.
Note:
Operation is not possible for about 30 seconds after cancellation of function selection. (Correct operation)
For description of each LED (LED1, 2, 3) provided on the indoor controller, refer to the following table.
LED1 (power for microprocessor)
LED2 (power for wired remote controller)
LED3 (communication between indoor and
outdoor units)
Error code
For about 2
minutes after
power-on
Subsequent to
about 2 minutes
after power-on
After LED 1, 2 are lighted, LED 2 is
turned off, then only LED 1 is
lighted.
(Correct operation)
Only LED 1 is lighted.
Only LED 1 is lighted.
Indicates whether control power is supplied. Make sure that this LED is
always lit.
Indicates whether power is supplied to the wired remote controller.
This LED lights only in the case of the indoor unit which is connected to the
outdoor unit refrigerant addresses “0”.
Indicates state of communication between the indoor and outdoor units.
Make sure that this LED is always blinking.
LED 1, 2 blink.
LED 1 blinks twice,
LED 2 blinks once.
•For about 2 minutes following power-on,operation of the remote controller is not possible
due to system start-up. (Correct operation)
•Connector for the outdoor unit’s protection
device is not connected.
•Reverse or open phase wiring for the outdoor
unit’s power terminal block (L1, L2, GR)
•Incorrect wiring between indoor and outdoor
units (incorrect polarity of S1, S2, S3)
•Remote controller wire short
Cause
17
Page 18
9-3. SELF-DIAGNOSIS ACTION TABLE
Error Code
P1
P2
Abnormal point and detection method
Room temperature thermistor (TH1)
The unit is in 3-minute resume
prevention mode if short/open of
thermistor is detected. Abnormal if the
unit does not reset normally after 3 minutes. (The unit returns to normal operation, if it has been reset normally.)
Constantly detected during cooling,
drying, and heating operation.
Short: 90
Open: -40
Pipe temperature thermistor/Liquid
(TH2)
The unit is in 3-minute resume
prevention mode if short/open of
thermistor is detected. Abnormal if the
unit does not reset normally after 3 minutes. (The unit returns to normal operation, if it has been reset normally.)
Constantly detected during cooling,
drying, and heating (except defrosting)
operation.
Short: 90
Open: -40
Note: Refer to the manual of outdoor unit for the details of display
such as F, U, and other E.
Cause
Defective thermistor
characteristics
Contact failure of connector
(CN20) on the indoor controller
board (Insert failure)
Breaking of wire or contact
failure of thermistor wiring
Defective indoor controller
board
Defective thermistor
characteristics
Contact failure of connector
(CN44) on the indoor controller
board (Insert failure)
Breaking of wire or contact
failure of thermistor wiring
Defective refrigerant circuit is
causing thermistor temperature of 90
-40
Defective indoor controller
board
Countermeasure
– Check resistance value of thermistor.
0
10
20
30
40
••••••••••
••••••••••••
••••••••••••
••••••••••••
•••••••••••
15.0k
9.6k
6.3k
4.3k
3.0k
If you put force on (draw or bend) the lead wire
while measuring resistance value of thermistor, breaking of wire or contact failure can be
detected.
Check contact failure of connector (CN20) on
the indoor controller board. Refer to 9-7.
Turn the power on again and check restart
after inserting connector again.
Check room temperature display on remote
controller.
Replace indoor controller board if there is
abnormal difference with actual room
temperature.
Turn the power off, and on again to operate
after check.
– Check resistance value of thermistor.
For characteristics, refer to (P1) above.
Check contact failure of connector (CN44) on
the indoor controller board. Refer to 9-7.
Turn the power on and check restart after
inserting connector again.
Check pipe <liquid> temperature with remote
controller in test run mode. If pipe <liquid>
temperature is extremely low (in cooling
mode) or high (in heating mode), refrigerant
circuit may have defect.
Check pipe <liquid> temperature with remote
controller in test run mode. If there is extremely
difference with actual pipe <liquid> temperature,
replace indoor controller board.
Contact failure of drain float switch (CN4F)
Extract when the connector of drain float
P4
(5701)
switch is disconnected.
( andof connector CN4F is not
short-circuited.)
Constantly detected during operation.
Drain overflow protection operation
Suspensive abnormality, if drain float
switch is detected to be underwater for
1 minute and 30 seconds continuously
with drain pump on.
Turn off compressor and indoor fan.
Drain pump is abnormal if the condition
above is detected during suspensive
abnormality.
P5
Constantly detected during drain pump
operation.
Contact failure of connector
(Insert failure)
Defective indoor controller
board
Malfunction of drain pump
Defective drain
Clogged drain pump
Clogged drain pipe
Defective drain float switch
Catch of drain float switch or
malfunction of moving parts
cause drain float switch to be
detected under water (Switch
On)
Defective indoor-controller
board
18
Turn the power off, and on again to operate
after check.
Check contact failure of float switch connector.
Turn the power on again and check after
inserting connector again.
Operate with connector (CN4F) short-circuited.
Replace indoor controller board if abnormality
reappears.
Check if drain pump operates.
Check drain function.
Remove drain float switch connector CN4F
and check if it is short (Switch On) with the
moving part of float switch UP, or OPEN with
the moving part of float switch down.
Replace float switch if it is short with the
moving part of float switch down.
Replace indoor controller board if it is shortcircuited between -
of the drain float
switch connector CN4F and abnormality
reappears.
It is not abnormal if there is no problem about
the above-mentioned ~
Turn the power off, and on again to operate
after check.
Page 19
Error Code
Abnormal point and detection method
Freezing/overheating protection is
opearting
Freezing protection (Cooling mode)
The unit is in 6-minute resume prevention
mode if pipe <liquid or condenser/evaporator> temperature stays under
the compressor started. Abnormal if it
again within 16 minutes after 6-minute
resume prevention mode.
Cause
(Cooling or drying mode)
Clogged filter (reduced airflow)
Short cycle of air path
Low load (low temperature)
operation out of the tolerance
range
Defective indoor fan motor
• Fan motor is defective.
• Indoor controller board is defective.
Defective outdoor fan control
Overcharge of refrigerant
Defective refrigerant circuit
(clogs)
Countermeasure
(Cooling or drying mode)
Check clogs of the filter.
Remove blockage.
Refer to 9-6.
Check outdoor fan motor.
Check operating condition of refrigerant
circuit.
P6
P8
Overheating protection (Heating mode)
The units is in 6-minute resume
prevention mode if pipe <liquid or
condenser/
detected as over 70°C[158°F] after the
compressor started. Abnormal if the
temperature of over 70°C[158°F] is
detected again within 10 minutes after
6 minute resume prevention mode.
Pipe temperature
<Cooling mode>
Detected as abnormal when the pipe temperature is not in the cooling range 3 minutes after compressor start and 6 minutes
after the liquid or condenser/evaporator pipe
is out of cooling range.
Note 1) It takes at least 9 minutes to detect.
Note 2) Abnormality P8 is not detected in
Cooling range : -(TH-TH1)
TH: Lower temperature between liquid pipe
temperature (TH2) and condenser/
evaporator temperature (TH5)
TH1: Intake temperature
<Heating mode>
When 10 seconds have passed after the
compressor starts operation and the hot
adjustment mode has finished, the unit is
detected as abnormal when condenser/
evaporator pipe temperature is not in heating range within 20 minutes.
Note 3) It takes at least 27 minutes to
Note 4) It excludes the period of defrosting
Heating range :(TH5-TH1)
evaporator> temperature is
drying mode.
detect abnormality.
(Detection restarts when defrosting
mode is over)
(Heating mode)
Clogged filter (reduced airflow)
Short cycle of air path
Overload (high temperature)
operation out of the tolerance
range
Defective indoor fan motor
• Fan motor is defective.
• Indoor controller board is defective.
Defective outdoor fan control
Overcharge of refrigerant
Defective refrigerant circuit
(clogs)
Bypass circuit of outdoor unit
is defective.
Slight temperature difference
between indoor room
temperature and pipe <liquid
or condenser/evaporator>
temperature thermistor
• Shortage of refrigerant
• Disconnected holder of pipe
<liquid or condenser/
evaporator> thermistor
• Defective refrigerant circuit
Converse connection of
extension pipe (on plural units
connection)
Converse wiring of indoor/
outdoor unit connecting wire
(on plural units connection)
Defective detection of indoor
room temperature and pipe
<condenser/evaporator>
temperature thermistor
Stop valve is not opened
completely.
(Heating mode)
Check clogs of the filter.
Remove blockage.
Refer to 9-6.
Check outdoor fan motor.
Check operating condition of refrigerant
~
circuit.
~ Checkpipe<liquidorcondenser/evap-
orator> temperature with room temperature display on remote controller and
outdoor controller circuit board.
Pipe <liquid or condenser/evaporator>
temperature display is indicated by setting SW2 of outdoor controller circuit
board as follows.
Conduct temperature check with outdoor
controller circuit board after connecting
(
‘A-Control Service Tool (PAC-SK52ST)’.
Check converse connection of extension
pipe or converse wiring of indoor/outdoor
unit connecting wire.
)
19
Page 20
Error Code
P9
Abnormal point and detection method
Pipe temperature thermistor/
Condenser-Evaporator (TH5)
The unit is in 3-minute resume protection mode if short/open of thermistor is
detected. Abnormal if the unit does not
get back to normal within 3 minutes. (The
unit returns to normal operation, if it has
been reset normally.)
Constantly detected during cooling,
drying, and heating operation (except
defrosting)
Cause
Defective thermistor
characteristics
Contact failure of connector
(CN44) on the indoor controller
board (Insert failure)
Breaking of wire or contact
failure of thermistor wiring
Temperature of thermistor is
For characteristics, refer to (P1) above.
Check contact failure of connector (CN44) on
the indoor controller board. Refer to 9-7.
Turn the power on and check restart after
inserting connector again.
Operate in test run mode and check pipe <condenser/evaporator> temperature with outdoor
controller circuit board. If pipe
<condenser/evaporator> temperature is exclusively low (in cooling mode) or high (in heating
mode), refrigerant circuit may have defect.
Operate in test run mode and check pipe <condenser/evaporator> temperature with outdoor
control circuit board. If there is
extreme difference with actual pipe
<condenser/evaporator> temperature, replace
indoor controller board.
There is no abnormality if none of above comes
within the unit.
Turn the power off and on again to operate.
In case of checking pipe temperature
with outdoor controller circuit board,
be sure to connect A-control service
(
tool (PAC-SK52ST).
)
PA
(2500)
E0
or
E4
Forced compressor stop
(due to water leakage abnormality)
The unit has a water leakage abnormality when the following conditions, a)
and b), are satisfied while the abovementioned detection is performed.
a) The intake temperature subtracted
with liquid pipe temperature detects to
be less than -10 [14
30 minutes. (When the drain sensor
is detected to be NOT soaked in the
water, the detection record of a) and b)
will be cleared.)
b) Drain float switch detects to be in the
water for more than 15 minutes.
*Once the water leakage abnormality is
detected, abnormality state will not be
released until the main power is reset.
· Drain pipe clogging
Open circuit of float switch
Contact failure of float switch
connector
Dew condensation on float switch
·Drain water descends along
lead wire.
·Drain water waving due to filter
clogging.
Extension piping connection
difference at twin, triple, quadruple system.
Miswiring of indoor/outdoor
connecting at twin, triple, quadruple system.
Room temperature thermistor/
liquid pipe temperature thermistor detection is defective.
Contact failure at transmission
wire of remote controller
All remote controllers are set
as “sub” remote controller. In
this case, E0 is displayed on
remote controller, and E4 is
displayed at LED (LED1, LED2)
on the outdoor controller circuit
board.
Miswiring of remote controller
Defective transmitting receiving
circuit of remote controller
Defective transmitting receiving
circuit of indoor controller board
of refrigerant addresses “0”.
Noise has entered into the
transmission wire of remote
controller.
Check the drain pump.
Check whether water can be drained.
Check the resistance of the float switch.
Check the connector contact failure.
Check the float switch leadwire mounted.
Check the filter clogging.
Check the piping connection.
Check the indoor/outdoor connecting wires.
Check the room temperature display of
remote controller.
Check the indoor liquid pipe temperature display of outdoor controller board.
Check disconnection or looseness of indoor
unit or transmission wire of remote controller.
Set one of the remote controllers “main”
if there is no problem with the action above.
Check wiring of remote controller.
(Do not use cable3 or more.)
• The number of connecting indoor units:
max. 16 units
• The number of connecting remote control
ler: max. 2 units
When the above-mentioned problem of ~
are not applied,
Diagnose remote controllers.
a) When “RC OK” is displayed, remote con-
trollers have no problem. Turn the power
off, and on again to check. If abnormality
generates again, replace indoor controller
board.
b) When “RC NG” is displayed, replace
remote controller.
c) When “RC E3” or “ERC 00-06” is dis played, noise may be causing abnormality.
If the unit is not normal after replacing
indoor controller board in group control,
indoor controller board of address “0”
may be abnormal.
Abnormal if remote controller could not
find blank of transmission path for 6 seconds and could not transmit.
(Error code: E3)
Remote controller receives transmitted
data at the same time, compares the
data, and when detecting it, judges
different data to be abnormal 30
continuous times. (Error code: E3)
Abnormal if indoor controller board could
not find blank of transmission path.
(Error code: E5)
Indoor controller board receives transmitted data at the same time, compares
the data,and when detecting it, judges
different data to be abnormal 30
continuous times. (Error code: E5)
Cause
2 remote controllers are set as
“main.”
(In case of 2 remote con trollers)
Remote controller is connected
with 2 indoor units or more.
Repetition of refrigerant
address
Defective transmitting receiving
circuit of remote controller
Defective transmitting receiving
circuit of indoor controller board
Noise has entered into trans-
mission wire of remote control-
ler.
Countermeasure
Set a remote controller to main, and the
other to sub.
Remote controller is connected with only one
indoor unit.
The address changes to a separate setting.
~Diagnose remote controller.
a) When “RC OK” is displayed, remote con-
trollers have no problem.
Turn the power off, and on again to check.
When becoming abnormal again, replace
indoor controller board.
b) When “RC NG” is displayed, replace
remote controller.
c) When “RC E3” or “ERC 00-66” is dis-
played, noise may be causing abnormality.
E6
E7
Fb
Indoor/outdoor unit communication
error (Signal receiving error)
Abnormal if indoor controller board
cannot receive any signal normally for 6
minutes after turning the power on.
Abnormal if indoor controller board
cannot receive any signal normally for 3
minutes.
Consider the unit as abnormal under
the following condition: When 2 or more
indoor units are connected to an
outdoor unit, indoor controller board
cannot receive a signal for 3 minutes
from outdoor controller circuit board, a
signal which allows outdoor controller
circuit board to transmit signals.
Indoor/outdoor unit communication
error (Transmitting error)
Abnormal if indoor controller board
receives “1” 30 times continuously when
indoor controller board transmits “0” signal.
Indoor controller board
Abnormal if data cannot be read normally
from the nonvolatile memory of the indoor
controller board.
Contact failure, short circuit or,
miswiring (converse wiring) of
indoor/outdoor unit connecting
wire
Defective transmitting receiving
circuit of outdoor controller
circuit board
Defective transmitting receiving
circuit of indoor controller board
Noise has entered into indoor/
outdoor unit connecting wire.
Defective transmitting receiving
circuit of indoor controller board
Noise has entered into power
supply.
Noise has entered into outdoor
control wire.
Defective indoor controller
board
Check LED display on the outdoor control
circuit board. (Connect A-control service
tool, PAC-SK52ST.)
Refer to EA-EC item if LED displays EA-EC.
Check disconnection or looseness of indoor/
outdoor unit connecting wire of indoor unit or
outdoor unit.
Check all the units in case of twin indoor
unit system.
- Turn the power off, and on again to check.
If abnormality generates again, replace
indoor controller board or outdoor
controller circuit board.
Other indoor controller board may have
defect in case of twin indoor unit system.
- Turn the power off, and on again to check.
If abnormality generates again, replace
indoor controller board.
Replace indoor controller board.
Remote controller control board
Abnormal if data cannot be read normally from the nonvolatile memory of the
remote controller control board.
(Error code: E1)
E1
or
E2
Abnormal if the clock function of remote
controller cannot be operated normally.
Note: Refer to the manual of outdoor unit for the detail of remote
controller.
Phenomena
(1)Upward/downward vane
performance failure
The vane is not downward during defrosting and heat
preparation and when the thermostat is OFF in HEAT
mode. (Working of COOL protection function)
Vane motor does not rotate.
• Defective vane motor
• Breaking of wire or connection failure of connector
Upward/downward vane does not work.
• The vane is set to fixed position.
Cause
Countermeasure
Normal operation (The vane is set to
horizontal regardless of remote control.)
Check(left).
• Check the vane motor. (Refer to “How
to check the parts”.)
• Check for breaking of wire or connection failure of connector.
Normal operation (Each connector on
vane motor side is disconnected or setting the fixed vanes by wired remote
controller.)
(2)Receiver for IR wireless remote
controller
Weak batteries of IR wireless remote controller
Contact failure of connector (CNB) on IR wireless
remote controller board
(Insert failure)
Contact failure of connector (CN90) on indoor controller board (Insert failure)
Contact failure of connector between IR wireless
remote controller board and indoor controller board
Replace batteries of IR wireless remote
controller.
~
Check contact failure of each connector.
If no problems are found of connector,
replace indoor controller board.
When the same trouble occurs even if
indoor controller board is replaced,
replace IR wireless remote controller
board.
22
Page 23
9-5. EMERGENCY OPERATION
9-5-1. When IR wireless remote controller fails or its battery is exhausted
When the remote controller cannot be used
When the batteries of the remote controller run out or the remote controller malfunctions, the emergency operation can be done using the emergency buttons on the grille.
• To operate the heating mode, press thebutton
seconds
* Lighting of the Operation lamp
Note:
• Details of emergency mode are as shown below.
Operation modeCOOLHEAT
Set temperature24°C, 75°F24°C, 75°F
Fan speedHighHigh
Airflow directionHorizontalDownward 5
Stopping operation
• To stop operation, press the
.
.
button
means the start of operation.
button or the button .
for more than 2
for more than 2
9-5-2. When wired remote controller or indoor unit microprocessor fails
1.When the wired remote control or the indoor unit microprocessor has failed, but all other components work properly,
if you set the switch (SWE) on the indoor controller board ON, the indoor unit will begin emergency operation.
When emergency operation is activated, the indoor unit operates as follows:
(1)Indoor fan is running at high speed. (2)Drain pump is working. (option)
+
Note on the IR wireless remote control: when the remote control does not function, it is possible to activate
emergency operation by using the indoor unit emergency operation switch (SW1, SW2 of the IR wireless signal
receiver board).
However, if the indoor unit microprocessor has failed, it is necessary to proceed with points (2) and (3) below as in
the case of the wired remote controller.
2.When you activate emergency operation of the cooling or heating, you have to set the switch (SWE) on the indoor
controller board and activate emergency operation of the outdoor unit.
For details on how to activate emergency operation of the outdoor unit, refer to the outdoor unit wiring diagram.
3.Before you activate emergency operation, check the following points:
(1)Emergency operation cannot be activated when:
• the outdoor unit malfunctions. • the indoor fan malfunctions.
• when it has detected the malfunction of drain pump during self-diagnosing.
(2)Emergency operation becomes continuous only by switching the power source on/off.
ON/OFF on the remote control or temperature control etc. does not function.
(3)Avoid operating for a long time when the outdoor unit begins defrosting while emergency operation
of the heating is activated because it will start to blow cold air.
(4)Emergency cooling should be limited to 10 hours maximum (The indoor unit heat exchanger may freeze).
(5)After emergency operation has been deactivated, set the switches etc. to their original positions.
(6)Movement of the vanes does not work in emergency operation, therefore you have to slowly set them
manually to the appropriate position.
23
Page 24
9-6. HOW TO CHECK THE PARTS
PCA-A24KA4 PCA-A30KA4 PCA-A36KA4 PCA-A42KA4
Parts nameCheck points
Room temperature
thermistor (TH1)
Liquid pipe thermistor
(TH2)
Condenser/evaporator
temperature thermistor
(TH5)
Vane motor (MV)
White
Orange
Red
Blue
Yellow
Disconnect the connector then measure the resistance with a tester.
(At the ambient temperature 50"F~86"F)
Normal
4.3k~9.6k
Abnormal
Open or short
(Refer to the next page for a detail.)
Measure the resistance between the terminals with a tester.
(At the ambient temperature of 68°F~86°F)
Connector
Normal
Red - Yellow
Red - Blue
Red - Orange
300
Open or short
Red - White
Abnormal
Drain pump (DP) (Option)
YLW
1
3
YLW
Drain float switch (FS)
(Option)
Moving part
1
2
3
4
i-see sensor
(Option)
4321
431
2
Black
Pink
Brown
Blue
Vane motor for
i-see sensor (Option)
White
Orange
Red
Blue
Yellow
Measure the resistance between the terminals with a tester.
(Winding temperature 68°F)
NormalAbnormal
290Open or short
Measure the resistance between the terminals with a tester.
State of moving partAbnormal
UP
DOWNOther than open
Normal
ShortOther than short
Open
Turn on the indoor unit with the black plastic tape on the outside of i-see sensor controller board.
i-see sensor rotates then pull out the connector of motor for i-see sensor.
With electricity being turned on, measure the power voltage between connectors with tester.
Black plastic tape
i-see sensor (At the ambient temperature of 50°F~104°F)
i-see sensor connector
(–)—(+)
(+)—(–)Other than the normal
NOTE : Be careful not to discharge static electricity into electronic device.
Measure the resistance between the terminals with a tester.
(At the ambient temperature of 68°F~86°F)
Connector
Normal
Red - Yellow
Red - Blue
Red - Orange
250
Red - White
Normal
DC 1.857V~ 3.132VOther than the normal
DC 0.939V~ 1.506V
Abnormal
Abnormal
Open or short
Switch
Magnet
Moving
Part
24
Page 25
9-6-1. Thermistor
<Thermistor Characteristic graph>
Thermistor for
lower temperature
Room temperature thermistor (TH1)
Pipe temperature thermistor/liquid (TH2)
<Thermistor for lower temperature>
50
Condenser/evaporator temperature
thermistor (TH5)
Thermistor R
0=15k± 3%
Fixed number of B=3480 ± 2%
t( )Rt=15exp { 3480( ) }
1
273+t1273
1
T-32
273+
1.8
273
0
1
40
30
20
Resistance (k )
10
10
20
25
30
40
0
-20 -10 0 10 20 30 40 50
-4 -14 32 50 68 86 104 122 °F
9-6-2. DC Fan motor (fan motor/indoor controller circuit board)
Check method of DC fan motor (fan motor/indoor controller circuit board)
Notes
· High voltage is applied to the connecter (CNMF) for the fan motor. Pay attention to the service.
· Do not pull out the connector (CNMF) for the motor with the power supply on.
(It causes trouble of the indoor controller circuit board and fan motor.
Self check
Symptom : The indoor fan cannot turn around.
)
°C
Temperature
Wiring contact check
Contact of fan motor connector (CNMF)
Is there contact failure?
No
Power supply check (Remove the connector (CNMF))
Measure the voltage in the indoor controller circuit
TEST POINT
TEST POINT : VCC (between 5 (+) and 4 (-) of the fan connector): VCC DC15V
Is the voltage normal?
Replace indoor controller board.
Check the operationEND
Replace the fan motor.
: VDC (between 1 (+) and 4 (-) of the fan connector): VDC DC294~325V
No
NG
Yes
Yes
OK
Wiring recovery
board.
Replace the fan motor
Check the operationEND
NG
Replace indoor controller board.
OK
25
Page 26
9-7. TEST POINT DIAGRAM
Indoor controller board
PCA-A24KA4 PCA-A30KA4 PCA-A36KA4 PCA-A42KA4
CN90
Connect to the IR wireless
remote controller board (CNB)
CN4Y
i-see sensor (option)
CN6Y
sensor motor (option)
CN105
RFI
(Radio frequency interface)
LED2
Power supply (R.B)
CN4F
Drain float switch (FS)
(option)
CN44
Pipe temperature
thermistor
- : Liquid (TH2)
- : Cond./Eva. (TH5)
CN20
Room temperature
thermistor (TH1)
LED1
Power supply (I.B)
CN30
Connector (LLC)
LED3
Transmission
(Indoor/outdoor)
CN2L
Connector (LOSSNAY)
CNV
Vane motor output (MV)
12V pulse output
SW1
Model selection
SW2
Capacity setting
Jumper wire J41,J42
Pair No. setting for IR wireless
remote controller
SWE
Emergency operation
CN51
Centrally control
- : Control signal
13VDC pulse input (: +)
- : Operation indicator
13VDC (: +)
- : Malfunction indicator
13VDC (: +)
CN41
Connector
CN24
Connector (Back-up heating)
CN22
Connect to the terminal block (TB5)
(Remote controller connecting wire)
(10.4~14.6V DC)
(HA terminal-A)
CNMF
Fan motor
-: DC 294~325V
-: DC15V
CNP
Drain-pump output (DP)
(208/230V AC) (option)
26
CN3C
Transmission
(0~24V DC)
VCC: Voltage between pins of
C955 15VDC
(Same as (+)–(-) of CNMF)
CN01
Connect to the Terminal Block
(TB4)
(Indoor/outdoor connecting line)
Between and
208/230V AC
FUSE
6.3A /250V
(Indoor/outdoor)
Page 27
9-8. FUNCTIONS OF DIP SWITCH AND JUMPER WIRE
Each function is controlled by the dip switch and the jumper wire on control P.C. board.
SW1 and SW2 are equipped only for service parts.
Model setting and capacity setting are memorized in the nonvolatile memory of the control P.C. board of
the unit.
The black square (■) indicates a switch position.
Jumper wire ( : Short : Open)
Jumper wire
SW1
SW2
J41
J42
Functions
Model
settings
Capacity
settings
Pair number
setting with
IR wireless
remote
controller
Setting by the dip switch and jumper wire
For service board
12345
MODELS
PCA-A24KA4
ON
OFF
Service board
1 2 3 4 5
ON
OFF
1 2 3 4 5
PCA-A30KA4
ON
OFF
1 2 3 4 5
PCA-A36KA4
ON
OFF
PCA-A42KA4
1 2 3 4 5
ON
OFF
Wireless remote
controller setting
0
1
2
3 ~ 9
Control PCB setting
J41J42
Remarks
<Initial setting>
IR wireless remote controller: 0
Control PCB: (for both J41 and J42)
Four pair number settings are supported.
The pair number settings of the wireless remote
controller and indoor control PCB (J41/J42) are
given in the table on the left.
(' ' in the table indicates the jumper line is disconnected.)
JP1
JP3
Unit type
setting
Indoor
controller
board type
Model
Without TH5
With TH5
Indoor controller board type
setting
For product
Spare parts
JP1
There is no jumper (JP1) because these models
have the cond./eva. temperature thermistor (TH5).
JP3
27
Page 28
10
SPECIAL FUNCTION
10-1. Rotation Function (and back-up function, 2nd stage cut-in function)
This function is only available when using wired remote controller.
10-1-1. Operation
(1) Rotation function (and Back-up function)
Outline of functions
· Main and sub units operate alternately according to the interval of rotation setting.
w Main and sub unit should be set by refrigerant address. (Outdoor Dip switch setting)
Refrigerant address "00"
Refrigerant address "01"Sub unit
· When error occurs to one unit, another unit will start operation. (Back-up function)
System constraint
· This function is available only by the grouping control system (INDOOR UNIT: OUTDOOR UNIT=1:1) of 2 refrigerant
groups. (Refer to Fig. 1)
· Main indoor unit should be connected for wired remote controller and the transmission line (TB5) for main and sub unit
should also be connected. (Refer to Fig. 1)
(This function cannot be set by IR wireless remote controller.)
· Set refrigerant address of each unit. (Dip switch on the outdoor unit ··· Refrigerant address 00/01)
Main unit
Operation pattern
[Back-up function only]··· Request code number "312"
Start operation
Main
unit
IC-1
Sub
unit
IC-2
[Rotation function] & [Back-up function]··· Request code number "313~318"
Start operation
Main
unit
IC-1
Sub
unit
IC-2
(Ex:When the request code number is "313", each unit operates alternately in daily cycle.)
Run
Stop
Main SubSub MainMain Sub
Run
Stop
1~28 days1~28 days
Error occurs on main unit.
Main Sub
Abnormal condition
Run
Stop
Run
Run
StopRun
Error occurs on main unit.
Abnormal condition
Main
unit
2
Refrigerant address
"00"
OC-1
3(2)
IC-1
2
RC
Fig. 1
OC : Outdoor unit
IC : Indoor unit
RC : Wired remote controller
Refrigerant address
"01"
OC-2
Sub
3(2)
unit
IC-2
Note:
· When the unit is restarted to operate after turning off the power or OFF operation, the unit which was operating will start operation.
· To operate the main unit, refer to the 10-1-2. and set the request code No. which is not the same as the current one, and set
again the former request code No.
(2) 2nd stage cut-in function
Outline of functions
· When the 1st unit can NOT supply with sufficient capacity for exceptionally high-demand conditions and the actual room
temperature reaches set point *, the 2nd unit starts operation in conjunction with the 1st unit.
· Once the actual room temperature goes down to 4 degrees C (7.5 degrees F) below set point*, the 2nd unit stops operation
automatically.
(* set point = set temperature by R/C (remote controller) + 4, 6, 8:(7.5, 10.8, 14.4°F) (selectable))
· Number of operating units is determined according to the room temperature and set point.
· When room temperature becomes higher than set point, standby unit starts. (2 units operation)
· When room temperature falls below set point -4:(-7.5°F), standby unit stops. (1 unit operation)
2828
Page 29
System constraint
· This function is available only in cooling mode.
Ex.) Set temp. by R/C = 20:(68°F)
Set point = 26:(79°F)
When request code number is “323”.
26: 2nd unit Cut-in
(79°F)
4 degree C
(7.5 degreeF)
22: 2nd unit Cut-out
(71.5°F)
[2nd stage cut-in function]··· Request code number "322~324"
Start operationSub unit start operation
Main
unit
IC-1
Sub
unit
IC-2
Room temp. Set point
Run
StopStopRun
20:
(68°F)
10-1-2. How to set rotation function (Back-up function, 2nd stage cut-in function)
You can set these functions by wired remote controller.(Maintenance monitor)
NOTE
Both main and sub unit should be set in same setting.
Every time replacing indoor controller board for servicing, the function should be set again.
(1) Request Code List
Rotation setting
Setting No.
(Request code)
No.1
(310)
No.2
(311)
No.3
(312)
No.4
(313)
No.5
(314)
No.6
(315)
No.7
(316)
No.8
(317)
No.9
(318)
Setting contents
Monitoring the request code of current setting.
Rotation and Back-up OFF (Normal group control operation)
Back-up function only
Rotation ON (Alternating interval = 1day) and back up function
Rotation ON (Alternating interval = 3day) and back up function
Rotation ON (Alternating interval = 5day) and back up function
Rotation ON (Alternating interval = 7day) and back up function
Rotation ON (Alternating interval = 14day) and back up function
Rotation ON (Alternating interval = 28day) and back up function
Initial
setting
Room temp. < Set point -4(-7.5°F)
Sub unit stop
2nd stage cut-in setting
Setting No.
(Request code)
No.1
(320)
No.2
(321)
No.3
(322)
No.4
(323)
No.5
(324)
Monitoring the request code of current setting.
Cut-in Function ON(Set point = Set temp.+ 4°C(7.5°F))
Cut-in Function ON(Set point = Set temp.+ 6°C(10.8°F))
Cut-in Function ON(Set point = Set temp.+ 8°C(14.4°F))
Setting contents
Cut-in function OFF
Initial
setting
2929
Page 30
(2) Setting method of each function by wired remote controller
B: Refrigerant address
C: Data display area
D: Request code display area
1. Stop operation().
2. Press the button () for 3 seconds so that [Maintenance mode] appears on the screen ().
TEST
After a while, [00] appears in the refrigerant address number display area.(at )
3. Press the button () for 3 seconds to switch to [Maintenance monitor].
CHECK
Note) It is not possible to switch to [Maintenance monitor] during data request in maintenance mode
(i.e., while “----” is blinking) since no buttons are operative.
[----] appears on the screen () when [Maintenance monitor] is activated.
(The display () now allows you to set a request code No.)
4. Press the [TEMP ( and )] buttons () to select the desired refrigerant address.
[ScreenB]
5. Press the [CLOCK ( and )] buttons () to set the desired request code No.(“311~318”, “321~324”)
6. Press the button () to perform function setting.
FILTER
If above setting operations are done correctly, "Request code number" will appear in data display area.()
[Example: When the "311" of "Request code number" is set, [311] appears on the screen.()]
[Refererence]
You can check current "request code number" setting by setting the "request code number"(“310” or “320”) and
pressing the button.()
FILTER
[Example: When the current setting is "Setting No.2(Request code 311)", [311] appears on the screen.()]
7. To return to normal mode, press the button ().
10-2. BACK-UP HEATING FUNCTION (CN24)
10-2-1. Operation
Outline of functions
The back-up heater signal is sent out according to the temperature difference between indoor room temperature and set temperature. This function is available only in heating operation.
ON/OFF
Temperature difference
(Z=Set temp. - Room temp.)
1
2
3
Z 0˚C(˚F)
0 < Z < 2.5˚C(4.5˚F)
2.5˚C(4.5˚F) Z
Back-up heater
signal output
OFF
Keeping condition
ON
10-2-2. How to connect
When connecting to the connector CN24 of the indoor unit, use
PAC-SE56RA-E(optional parts).
Z0 2.5˚C(4.5˚F)
ON
OFF
30
Page 31
11
DISASSEMBLY PROCEDURE
PCA-A24KA4 PCA-A30KA4
PCA-A36KA4 PCA-A42KA4
OPERATING PROCEDURE
1. Removing the air intake grille
(1)
Slide the air intake grille holding knobs (at 2 or 3 locations) to the rear to open the air intake grille. (See Figure 1)
(2) While the air intake grille left open, push the stoppers
on the rear hinges (at 2 or 3 locations) to pull out the air
intake grille. (See Figure 2)
Figure 2
hinges
Pull out the air intake grille
2.
Removing the indoor controller board and the electrical box
(1) Remove the air intake grille. (See Figure 1,2)
(2) Remove the beam by removing 1 screw (4
Photo 1)
(3) Remove 2 screws from the electrical cover, and remove
the electrical cover.
(4) Remove 2 screws from the electrical box and pull the
electrical box downward.
Temporarily secure the electrical box using 2 hooks in
the back of electrical box.
(5) Disconnect the connectors on the indoor controller
board.
[Removing the electrical box]
(6) Disconnect the wires from the terminal blocks and pull
out the electrical box. (See Photo 2)
× 8 PT) (See
PHOTOS & ILLUSTRATIONS
Figure 1
Air intake grille
Air intake grille
holding knobs
Photo 1
Electrical cover
Photo 2
Be careful when removing heavy parts.
(Photo: PCA-A36KA4)
slide
Beam fixing screw
(4 × 8 PT)
Electrical cover
fixing screws (4 × 8 ST)
Beam
[Removing the indoor controller board]
(6) Remove the 6 supports from the indoor controller board
and remove the indoor controller board. (See Photo 3)
31
Electrical box
Photo 3
Room temperature
thermistor (TH21)
Electrical box fixing screws
Indoor controller
board (I.B.)
Terminal blocks
(TB4) (TB5)
Page 32
OPERATING PROCEDURE
PHOTOS & ILLUSTRATIONS
3. Removing the room temperature thermistor (TH1)
(1) Remove the air intake grille. (See Figure 1,2)
(2) Remove the beam by removing 1 screw (4 × 8 PT) (See
Photo 1)
(3) Remove 2 screws from the electrical cover, and remove
the electrical cover.
(4) Remove 2 screws from the electrical box and pull the
electrical box downward.
Temporarily secure the electrical box using 2 hooks in
the back of electrical box.
(5) Disconnect the connector CN20 (red) from the indoor
controller board.
(6) Remove the sensor holder from the electrical box and
remove the thermistor from the holder.
4. Removing the fan motor and right side fan
(1) Remove the air intake grille. (See Figure 1,2)
(2) Remove the beam by removing 1 screw (4
× 8 PT) (See
Photo 1)
(3) Remove 2 screws from the electrical cover, and remove
the electrical cover.
(4) Remove 2 screws from the electrical box and pull the
electrical box downward.
(5) Temporarily secure the electrical box using 2 hooks in
the back of electrical box.
(6) Remove the lower casing while pressing the 4 catches of
the casing (right side of the fan motor). (See Photo 6)
(7) Loosen the 2 set screws (2 hexagon set screws) of con-
necting joint and slide the fan motor to the left. (See
Photo 5)
(8) Remove the screw for motor earth wire. (See Photo 5)
(9) Remove the motor piece (left and right, each 1 screw).
(See Photo 5)
(
10
) Remove the fan motor and right side fan together.
11
) Loosen the set screw (hexagon set screw) of fan and
(
remove the fan from the shaft. (See Photo 7,8)
Photo 4
Room temperature
thermistor (TH1)
Electrical box
Photo 5
Connecting
joint
Casing
Photo 6
Casing
Catch
Motor piece
fixing screws
Set screws
Casing
Fan motor
Electrical box
Catches
Motor earth wire
fixing screw
Casing
Photo 8
Hexagon set screw
32
Photo 7
Catches
Hole for driver
Page 33
OPERATING PROCEDURE
PHOTOS & ILLUSTRATIONS
5. Removing the fan (3 connection)
(1) Remove the air intake grille. (See Figure 1,2)
(2) Remove the beam by removing 1 screw (4
× 8 PT) (See
Photo 1)
(3) Remove 2 screws from the electrical cover, and remove
the electrical cover.
(4) Remove 2 screws from the electrical box and pull the
electrical box downward.
Temporarily secure the electrical box using 2 hooks in
the back of electrical box.
(5) Remove 2 screws from the left side beam and remove
the beam. (See Photo 9)
(6) Loosen 2 set screws (2 hexagon set screws) of connect-
ing joint. (See Photo 5)
(7) Remove 3 lower casings while pressing each 4 catches
of the casing. (See Photo 6)
(8) Remove the 4 screws from the bearing support. (See
Photo 10)
(9) Slide the connecting joint to the left and remove the fans
and shaft together. (See Photo 11)
(
10
) Remove the fans from the shaft. (See Photo 7,8 )
Photo 11
Fans (3 connection)
Photo 9
Photo 10
Bearing support fixing
screws
Beam
Bearing support
Shaft
Bearing support
Shaft
6. Removing the side panel
(1) Remove the air intake grille. (See Figure 1,2)
(2) Remove the screws from the side panel, and remove
the side panel by sliding the panel to the front.
(3) Unhook the side panel support hanger, and then slide
the side panel forward to remove it.
Figure 3
Side panel
(Left)
Figure 4
Screws
Hole for side panel
support hanger
Side panel
(Right)
Sliding the panel
to the front
Side panel
support hanger
33
Page 34
OPERATING PROCEDURE
7. Removing the vane motor
(1) Remove the air intake. (See Figure 1,2)
(2) Remove the right side panel. (See Figure 3)
(3) Remove the connector of vane motor.
(4) Remove 2 screws of vane motor cover, then remove
vane motor.
PHOTOS & ILLUSTRATIONS
Photo 12
Vane motor and cover
Screws
Connector
8. Removing the under panel
(1) Remove the air intake grille. (See Figure 1,2)
(2) Remove the left and right side panels. (See Figure 3)
(3) Remove the beam. (See Photo 1)
(4) Remove the electrical cover. (See Photo 1)
(5) Pull the electrical box downward. (See Photo 2)
(6) (Wireless remote controller receiver type only)
Disconnect the connector CNB from the PCB for wire-
less remote controller and remove the clamp and strap
for wires.
(7) Remove 8 screws from the under panel.
(8) Move the under panel forward by about 7/16 in. (10 mm)
and remove the under panel.
9. Removing the drain pan
(1) Remove the air intake grille. (See Figure 1,2)
(2) Remove the side panel (right and left). (See Figure 3)
(3) Remove the under panel. (See Photo 13)
Remove the screws of the right and left side drain pan.
(See Photo 14)
(4) Remove 2 insulation in centre of the drain pan, and after
removing 2 screws with washer, remove the drain pan.
(See Photo 15,16)
(Note)
Please be aware that there might be some drainage left in
the drain pan when you remove the drain pan.
Photo 16
Photo 13
Under panel fixing
screws
Photo 14
Drain pan
fixing screws
(left and right
each 1 screw)
Photo 15
Van e
Pipe cover fixing screws
Drain pan
Insulations
Screw with
washer
(2 locations)
34
Page 35
OPERATING PROCEDURE
10. Removing the thermistors/Liquid pipe (TH2) and condenser/evaporator (TH5)
(1) Remove the air intake grille. (See Figure 1, 2)
(2) Remove the left and right side panels. (See Figure 3)
(3) Remove the under panel. (See Photo 14)
(4) Remove the drain pan. (See Photo 15, 16, 17)
(5) Disconnect the connector CN44 (white) from the indoor
controller board.
(6) Remove 6 screws from the pipe cover and remove the
pipe cover. (See Photo 15, 18)
(7)
Remove the fastener for wires and remove the thermistors
(TH2 and TH5) from each holder. (See Photo 19)
(1) Remove the intake grille. (See Figure 1, 2)
(2) Remove the side panel (right and left). (See Figure 3)
(3) Remove the under panel. (See Photo 13)
(4) Remove the drain pan. (See Photo 14, 15, 16)
(5) Remove the screw from the guide vane, then remove
the guide vane.
12. Removing the Auto vane
(1) Remove the intake grille. (See Figure 1, 2)
(2) Remove the right side panel. (See Figure 3)
(3) Remove the vane motor and cover. (See Photo 12)
(4) Slide the auto vane to the vane motor side.
(5) Remove 2 axes from each vane support pushing the
vane support to the vane sleeve side.
Photo 19
Photo 20
Vane sleeve
Screw
Drain pan
Guide vane
Vane supportVane
Vane motor side
35
Page 36
OPERATING PROCEDURE
13. Removing the heat exchanger
(1) Remove the air intake grille. (See Figure 1, 2)
(2) Remove the beam. (See Photo 1)
(3) Remove the electrical cover. (See Photo 1)
(4) Pull the electrical box downward. (See Photo 2)
(5) Remove the left and right side panels. (See Figure 3)
(6) Remove the under panel. (See Photo 14)
(7) Remove the drain pan. (See Photo 15, 16, 17)
(8) Remove the pipe cover. (See Photo 18)
(9) Remove the pipe thermistors (TH2 and TH5) from each
holder. (See Photo 19)
(10) Remove the pipe band fixing screw and remove the
pipe band. (See Photo 22)
(11) Remove 2 screws from the heat exchanger and
remove the heat exchanger.
PHOTOS & ILLUSTRATIONS
Photo 22
Heat exchanger
Pipe band
Pipe band fixing
screw
Photo 23
Heat exchanger
fixing screws
HEAD OFFICE : TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
CCopyright 2010 MITSUBISHI ELECTRIC ENGINEERING CO., LTD.
Distributed in Nov. 2010 No.OCH484
Made in Japan
Heat exchangerVan e
New publication, effective Nov. 2010
Specifications subject to change without notice
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.