Mitsubishi PKA-A12HAL, PKA-A12HA, PKA-A18HAL, PCA-A12KA, PCA-A24KA Operation Manual

...
jf_ MITSUBISHI
ELECTRIC
Air-C n
indoor unit
iti
n
PKA-A.HA/PKA-A. PCA-A.KA
AL
OPERATION MANUAL
For safe and correct use, please read this operation manual thoroughly before operating the air-conditioner unit.
MANUEL D'UTILISATION
Pour une utilisation correcte sans risques, veuillez lire le manuel d'utilisation en entier avant de vous servir du
climatiseur.
MANUAL DE INSTRUCCIONES
Lea este manual de instrucciones hasta el final antes de porter en marcha la unidad de aire acondicionado para
garantizar un uso seguro y correcto.
m
Contents
1. Safety Precautions ............................................................... 2
2. Parts Names ........................................................................ 2
3. Screen Configuration ........................................................... 5
4. Setting the Day of the Week and Time ................................. 5
5. Operation ............................................................................. 5
6. Timer .................................................................................... 7
7. Other Functions .................................................................. 10
8. Function Selection .............................................................. 11
9. Emergency Operation for Wireless Remote-controller ....... 15
10. Care and Cleaning ............................................................. 15
11. Trouble Shooting ................................................................ 15
12. Specifications ..................................................................... 17
1. Safety Precautions
i_ Before installing the unit, make sure you read all the
"Safety Precautions".
i_ The "Safety Precautions" provide very important
points regarding safety. Make sure you follow them.
i_ Please report to or take consent by the supply author-
ity before connection to the system.
Symbols used in the text
Z_ Warning: Describes precautions that should be observed to prevent danger
of injury or death to the user.
z_ Caution: Describes precautions that should be observed to prevent damage
to the unit.
Symbols used in the illustrations (_ - Indicates apart which must be grounded.
Z_ Warning:
The unit must not be installed by the user. Ask the dealer or an authorized company to install the unit. If the unit is installed im-
properly, water leakage, electric shock or fire may result.
Do not stand on, or place any items on the unit.
Do not splash water over the unit and do not touch the unit with wet hands. An electric shock may result.
Do not spray combustible gas close to the unit. Fire may result.
Do not place a gas heater or any other open-flame appliance where it will be exposed to the air discharged from the unit. In- complete combustion may result.
Do not remove the front panel or the fan guard from the outdoor
unit when it is running.
When you notice exceptionally abnormal noise or vibration, stop operation, turn off the power switch, and contact your dealer.
Never insert fingers, sticks etc. into the intakes or outlets.
If you detect odd smells, stop using the unit, turn off the power switch and consult your dealer. Otherwise, a breakdown, electric shock or fire may result.
This air conditioner is NOT intended for use by children or infirm persons without supervision.
Young children must be supervised to ensure that they do not play with the air conditioner.
If the refrigeration gas blows out or leaks, stop the operation of the air conditioner, thoroughly ventilate the room, and contact
your dealer.
Z_ Caution:
Do not use any sharp object to push the buttons, as this may damage the remote controller.
Never block or cover the indoor or outdoor unit's intakes or out-
lets.
Disposing of the unit
When you need to dispose of the unit, consult your dealer.
2. Parts Names
[] Indoor Unit
PKA-A. HA PCA-A. KA
PKA-A. HAL
Fan speed 3 speeds + Auto 4 speeds + Auto
Vane Auto with swing Auto with swing
Louver Manual Manual Filter Normal Long-life
Filter cleaning indication 100 hr 2,500 hr
[] PKA-A.HA/PKA-A.HAL Wall Mounted
Filter Air intake
Louver Air outlet Vane
2
[] PCA-A.KA Ceiling Suspended
Air outlet
Vane
\
Air intake
Louver
Filter
(Inside of Air intake)
2. Parts Names
[] Wired Remote-Controller
I Display Section I
For purposes of this explanation, all parts of the display are shown. During actual operation, only the relevant items will be displayed.
J
/
Identifies the current operation Shows the operating mode, etc. |
Multi language display is sup-| ported. |
of the re- I
Imote controller has been prohibited I Iby a master controller. I
s Off" indicator
that the timer is off. /
Setting et temperature.
[ Operation Section ]
Set Temperature buttons
@ Down
(_Up
Timer Menu button (Monitor!Set button)
_,Returnbutton)
Set Time buttons )--
C_ Back
Ahead
I imer On/Off button _-]
(Set Day button)
Opening the lid
Day=of-Week I
Shows the current day of the week.
Tirne/Timer Display fl
Shows the current time, unless the simple or Auto Of timer is set.
If the simple or Auto Off timer is set, shows the time re- I
|
maining.
m_ MITSUBISHI ELEITRIC
"Sensor" indication contro!ler
Displayed when the remote sensor is used.
"'Locked" indicator but-
Indicates that remote controller tons have been locked.
"Clean The Filter" indicator
1
Comes on when it is time to clean the filter.
aTimer indicators corre-
The indicator comes on if the sponding timer is set.
WEEKLY _ '
SIMPLE
AUTO OFF-J "-_ I
[Fan Speed indicator speed. ]
[Shows the selected fan
Up/Down Air Direction indi- I
____ ----_
or '% shows the direc- I
It!on of the outcoming airflow. !
"One Hour Only" indicator Displayed if the airflow is set to
low and downward during COOL or DRY mode. (Operation varies according to model.) The indicator goes off after 1 hour
when the airflow direction also
changes.
Temperaturedisplay ] indica tthe room temperature. The room I IAppears when the unit is running in
ature display range is 46-102 °F. I IVentilati°n mode.
play blinks if the temperature isI n 46 °F or 102 °F or more. I
display louver, t
the action of the swing
t appear if the louver is station 1
[(_)(Power On indicator) _lndicates that the power is on.
MITSUBISHI ELECTRIC
I
Built-in temperature sensor
button
Speed button
button 1
(<Enter> button)
button
i ( Check button (Clear button)
Aifflow Up/Down button )
-L-'_ L°u(L_Vo rpeb:t_°n but n )1
_To return operation
number
--f Ventilation button !(A Operation button)
(_To go opera-
to next
tion number
Note:
"PLEASE WAIT" message This message is displayed for approximately 3 minutes when power is supplied to the indoor unit or when the unit is recovering from a power fail- ure.
"NOT AVAILABLE" message This message is displayed if a button is pressed to operate a function that the indoor unit does not have. If a single remote controller is used to simultaneously operate multiple indoor units that are different models, this message will not be displayed if any of the indoor units is equipped with the function.
3
2. Parts Names
[] Wireless Remote-Controller
_ Transmission area )
'Remote controller disp(ay)
* For explanation purposes, all of the items
that appear in the display are shown.
* All items are displayed when the Reset
button is pressed.
_ ON!OFF button)
Set Temperature buttons)
_Fan Speed button (Changes fan speed)_
'Airflow button (Changes up/down airflow _ [-
, I
Mode button (Changes operation mode)_
( Check button_)_
Test Run button_ F ):
Transmission indicator Timer indicator
(_Operation areas )
)
button
-- _Minute button ._ "Set Time button (Sets the time) )
Louver button (Changes left/right airflow direction) )
" Reset button )
[] When using the wireless remote controller, point it towards the receiver on the indoor unit. [] If the remote controller is operated within approximately 2 minutes after power is supplied
to the indoor unit, the indoor unit may beep twice as the unit is performing the initial auto-
matic check.
[] The indoor unit beeps to confirm that the signal transmitted from the remote controller has
been received. Signals can be received up to approximately 7 meters in a direct line from the indoor unit in an area 45 ° to the left and right of the unit. However, illumination such as fluorescent lights and strong light can affect the ability of the indoor unit to receive signals.
[] If the operation lamp near the receiver on the indoor unit is blinking, the unit needs to be
inspected. Consult your dealer for service.
[] Handle the remote controller carefully) Do not drop the remote controller or subject it to
strong shocks. In addition, do not get the remote controller wet or leave it in a location with
high humidity.
[] To avoid misplacing the remote controller, install the holder included with the remote con-
troller on a wall and be sure to always place the remote controller in the holder after use.
[] Outdoor unit
iiii)))J))))))))))))....................................................................................................
Power
Ref. Pipes _ Indoor-Outdoor
Connection wire
Battery instal(ationlreplacement
1. Remove the top cover, insert 2 AAA batteries, and then install the top cover.
1
4
Top cover
2. Press the Reset butto
_3
2 AAA batteries
Insert the negative (-) (
end of each battery( first, Install the bat- I teries in the correct I directions (+,-)! (
Press the Reset but-I ton with an object that has a narrow end.
Panel
Earth
///////_///////
4
3. Screen Configuration
FunctionSelectionofremotecontroller Set Day/Time
Standard Control Screens
OFF ON
Timer Monitor TimerSetup
T,_,j,_,..... , I iT,%%,,_i _v_:_':'_........
<Screen Types> For details on setting the language for the remote controller display, refer to section 8. Function Selection. The initial language setting is English.
® Function Selection of remote controller:
Set the functions and ranges available to the remote controller (timer functions, operating restrictions, etc.)
Set Day/Time: Set the current day of the week or time.
Standard Control Screens: View and set the air conditioning system's op- erating status
Timer Monitor: View the currently set timer (weekly timer, sim- ple timer, or Auto Off timer)
Timer Setup: Set the operation of any of the timers (weekly timer, simple timer, orAuto Off timer).
<How to change the screen>
@ : Hold down both the Mode button and the Timer On/Off button for 2
seconds. ® : Press the Timer Menu button. © : Press the Mode (Return) button. ® : Press either of the Set Time buttons (V or/k).
4. Setting the Day of the Week and Time
_ TE_4P (_ ON/OFF
[3 d3-----
[] [] Day of the Week Setting
Day of the Week / & Time display [] Time Setting
@
Note: The day and time will not appear if clock use has been disabled at Function
Selection of remote controller,
1. Press the V or/k Set Time button @ to show display %.
2. Press the Timer On/Off (Set Day) button @ to set the day.
* Each press advances the day shown at %: Sun _ Mon ..... Fri
Sat.
3. Press the appropriate Set Time button @ as necessary to set the time.
*As you hold the button down, the time (at %) will increment first in
minute intervals, then in 10-minute intervals, and then in 1-hour inter-
vals.
4. After making the appropriate settings at Steps 2 and 3, press the Filter button @ to lock in the values.
5. Operation
[] @
[] [] []
[]
5.1. Turning ON/OFF
<To Start Operation>
[] Press the ON/OFF button ®.
The ON lamp [] and the display area come on.
%
.@
<To Stop Operation>
[] Press the ON/OFF button ® again.
The ON lamp [] and the display area go dark.
Note: Even if you press the ON/OFF button immediately after shutting down the op-
eration is progress, the air conditioner will not start for about three minutes, This is to prevent the internal components from being damaged.
5
5. Operation
5.2. Mode select
[] Press the operation mode (I-1_OO6) button ® and select the opera-
tion mode [_.
---__t: (COOL) Cooling mode (DRY) Drying mode
(FAN) Fan mode
.O-(HEAT) Heating mode I--I (AUTO) Automatic (cooling/heating) mode
J _ Ventillation mode
Only indicated on the following condition
Wired remote controller used
LOSSNAY connected
Automatic operation [] According to a set temperature, cooling operation starts if the room
temperature is too hot and heating operation starts if the room tem-
perature is too cold.
[] During automatic operation, if the room temperature changes and
remains 2 °C, 4 °F or more above the set temperature for 15 minutes,
the air conditioner switches to cooling mode. In the same way, if the
room temperature remains 2 °C, 4 °F or more below the set tempera-
ture for 15 minutes, the air conditioner switches to heating mode.
Coolingmode
15minutes (switches
from heatingto cooling)
Set temperature +2°C, +4°F Set temperature
/
*l
_-.-_-.-_ ........ Set temperature -2°C, -4°F
15 minutes (switches
from cooling to heating )
[] Because the room temperature is automatically adjusted in order to
maintain a fixed effective temperature, cooling operation is performed
a few degrees warmer and heating operation is performed a few de- grees cooler than the set room temperature once the temperature is
reached (automatic energy-saving operation).
5.3. Temperature setting
_. To decrease the room temperature:
Press (2D button ® to set the desired temperature.
The selected temperature is displayed [].
_- To increase the room temperature:
Press GD button ® to set the desired temperature.
The selected temperature isdisplayed [].
Available temperature ranges are as follows:
Cooling/Drying: 19 - 30 °C, 67 - 87 °F
Heating: 17 - 28 °C, 63 - 83 °F
Automatic: 19 - 28 °C, 67 - 83 °F
The display [] flashes either 8 °C - 39 °C, 46 °F - 102 °F to inform you
if the room temperature is lower or higher than the displayed tempera-
ture. (This display does not appear on the wireless remote controller.)
5.4. Fan speed setting
[] Press the Fan Speed button @ as many times as necessary while the
system is running.
Each press changes the force. The currently selected speed is shown at %.
The change sequence, and the available settings, are as follows.
FAN SPEED Display
4-speed
+
Auto
3-speed
+
Auto
Speed 1 Speed 2 Speed 3 Speed 4 Auto
"t,. -'_ "t,.t --_ "t,.d -'_ "_,.dl -'_ '_' -
Speed 1 Speed 2 Speed 3 Auto
F--" -" -" "'" " --1
Note:
The number of available fan speeds depends on the type of unit connected. Note also that some units do not provide an "Auto" setting.
In the following cases, the actual fan speed generated by the unit
will differ from the speed shown the remote controller display.
1. While the display is showing "STAND BY" or "DEFROST".
2. When the temperature of the heat exchanger is low in the heat-
ing mode. (e.g. immediately after heating operation starts)
3. In HEAT mode, when room temperature is higher than the tem-
perature setting.
4. When the unit is in DRY mode.
5.5. Airflow direction setting
<To Change the Airflow's Up/Down Direction> [] With the unit running, press the Airflow Up/Down button ® as necessary.
Each press changes the direction. The current direction isshown at [_.
The change sequence, and the available settings, are as follows.
Remote controller Display
Wiled type
(PCA-KA) (PKA-HA)
Wireless type
Swing Auto 1 2 3 4 5
['_7 . D . D_ .D. . ._\ . D, . DI 3
Swing 1 2 3 4
*Note that during swing operation, the directional indication on the screen dose not change in sync with the directional vanes on the unit.
Note:
O Available directions depend on the type of unit connected. Note
also that some units do not provide an "Auto" setting.
O in the following cases, the actual air direction will differ from the
direction indicated on the remote controller display.
1. While the display is showing "STAND BY" or "DEFROST".
2. immediately after starting heater mode (while the system is
waiting for the mode change to take effect).
3. In heat mode, when room temperature is higher than the tempera=
ture setting.
6
5. Operation
<[Manual] To Change the Airflow's Left/Right Direction>
* The louver button G cannot be used.
o Stop the unit operation, hold the lever of the louver,
and adjust to the desired direction.
* Do not set to the inside direction when the unit is
in the cooling or drying mode because there is a
risk of condensation and water dripping.
Z_ Caution: When you operate the process above, be sure to take measures to avoid falls.
5.6. Ventillation
For LOSSNAY combination
5.6.1. For Wired Remote-controller
To run the ventilator together with the indoor unit: [] Press the ON/OFF button @.
The Vent indication appears on the screen (at []). The ventilator will now automatically operate whenever the indoor unit is running.
To run the ventilator only when the indoor unit is off: [] Press the Mode button @ until _ appears on the display. This
will cause the ventilator to start.
To change the ventilator force: [] Press the Ventilation button ® as necessary.
Each press toggles the setting as shown below.
(Low) (High)
Note:
With some model configurations, the fan on the indoor unit may
come on even when you set the ventilator to run independently.
6. Timer
6.1. For Wired Remote=controller
You can use Function Selection of remote controller to select which of three types of timer to use: (_ Weekly timer, _ Simple timer, or (_ Auto
Off timer.
6.1.1. Weekly Timer
[] The weekly timer can be used to set up to eight operations for each
day of the week.
Each operation may consist of any of the following: ON/OFF time together with a temperature setting, or ON/OFF time only, or tem- perature setting only.
When the current time reaches a time set at this timer, the air condi- tioner carries out the action set by the timer.
[] Time setting resolution for this timer is 1 minute.
Note: "1. Weekly Timer/Simple Timer/Auto Off Timer cannot be used at
the same time.
2. The weekly timer will not operate when any of the following con- ditions is in effect.
The timer feature is off; the system is in an malfunction state; a test run is in progress; the remote controller is undergoing self- check or remote controller check; the user is in the process of setting a function; the user is in the process of setting the timer; the user is in the process of setting the current day of the week or time; the system is under central control. (Specifically, the system will not carry out operations (unit on, unit off, or tem- perature setting) that are prohibited during these conditions.)
Operation No.
[] [] [] Day Setting
<How to Set the Weekly Timer>
1. Be sure that you are at a standard control screen, and that the weekly timer indicator [] is shown in the display.
2. Press the Timer Menu button @, so that the "Set Up" appears on the screen (at []). (Note that each press of the button toggles the display
between "Set Up" and "Monitor".)
3. Press the Timer On/Off (Set Day) button @ to set the day. Each press advances the display at [] to the next setting, in the following se-
quence: "Sun Mon Tues Wed Thurs Fri Sat" _ "Sun" _ .... "Fri" _ "Sat"
"Sun Mon Tues Wed Thurs Fri Sat"...
4. Press the V or Z& Operation button ((_ or ®) as necessary to select the appropriate operation number (1 to 8) []. * Your inputs at Steps 3 and 4 will select one of the cells from the
matrix illustrated below. (The remote-controller display at left shows how the display would appear when setting Operation 1 for Sunday to the values indicated below.)
Matrix
Op No. Sunday Monday ... Saturday
No. 1
No. 8
" 8:30 " ON " 73 °F
<Operation 1 settings for Sunday> <Operation 2 settings for every day> I
Start the air conditioner at 8:38, with Turn off the a r cond t oner at 10:00. J the emperature se to 73 °F.
Note: By setting the day to "Sun Mort Tues Wed Tburs Fri Sat", you can set the
same operation to be carried out at the same time every day. (Example: Operation 2 above, which is the same for all days of the week.)
<Setting the Weekly Timer> Shows thetime set- [] [] Shows the selected operation (ON or OFF)
ting i * Does not appear if operation is not set.
l
I
"--_-_( ........"l Shows the temperature setting
""q'" []
/ ",,!_-" ©,,.EE_ * Does not appear if temperature is
_-/_ / ®l i j notset.
5. Press the appropriate Set Time button @ as necessary to set the desired time (at []). * As you hold the button down, the time first increments in minute
intervals, then in 10-minute intervals, and then in 1-hour intervals.
6. Press the ON/OFF button (_ to select the desired operation (ON or OFF), at []. * Each press changes the next setting, in the following sequence:
No display (no setting) _ "ON" _ "OFF"
7
6. Timer
7. Press the appropriate Set Temperature button (_ to set the desired temperature (at []). * Each press changes the setting, in the foNowing sequence: No
display (no setting) <=>75 <=>77 <=>... <=>84 <=>86 <=>54 <=>... <=>
73 <=>No display. (Available range: The range for the setting is 12 °C, 54 °F to 30 °C, 86 °F. The actual range over which the temperature can be con-
trolled, however, will vary according to the type of the connected
unit.)
8. After making the appropriate settings at Steps 5, 6 and 7, press the Filter # button @ to lock in the values. To clear the currently set values for the selected operation, press and quickly release the Check (Clear) button (_ once. * The displayed time setting will change to "--:--", and the On/Off
and temperature settings will all disappear.
(To clear all weekly timer settings at once, hold down the Check (Clear) button (_ for 2 seconds or more. The display will begin
blinking, indicating that all settings have been cleared.)
Note: Your new entries will be cancelled if you press the Mode (Return) but- ton ® before pressing the Filter _.Jbutton Q.
If you have set 2 or more different operations for exactly the same time, only the operation with the highest Operation No. will be carried out.
9. Repeat Steps 3 to 8 as necessary to fill as many of the available ceNs as you wish.
10.Press the mode (Return) button _ to return to the standard control screen and complete the setting procedure.
11.To activate the timer, press the Timer On/Off button @, so that the "Timer Off" indication disappears from the screen. Be sure that the "Timer Off" indication is no lonaer disDlaved_ * if there are no timer settings, the "Timer Off" indication win blink
on the screen.
<How to View the Weekly Timer Settings>
[] [] Timer Settings
1. Be sure that the weekly timer indicator is visible on the screen (at [_).
2. Press the Timer Menu button @ so that "Monitor" is indicated on the screen (at []).
3. Press the Timer On/Off (Set Day) button @ as necessary to select the day you wish to view.
4. Press the V or A Operation button (G or @) as necessary to change the timer operation shown on the display (at _]). * Each press will advance to the next timer operation, in order of
time setting.
5. To close the monitor and return to the standard control screen, press the Mode (Return) button _.
<To Turn Off the Weekly Timer>
Press the Timer On/Off button @ so that "Timer Off" appears at [_.
/_I _l I_I
<To Turn On the Weekly Timer>
Press the Timer On/Off button @ so that the "Timer Off" indication (at _)
goes dark.
I I ILl
6.1.2. Simple Timer [] You can set the simple timer in any of three ways.
Start time only: The air conditioner starts when the set time has elapsed.
Stop time only: The air conditioner stops when the set time has elapsed.
Start & stop times: The air conditioner starts and stops at the respective elapsed times.
[] The simple timer (start and stop) can be set only once within a 72-hour
period. The time setting is made in hour increments.
Note: "1. Weekly Timer/Simple Timer/Auto Off Timer cannot be used at the same
time.
2. The simple timer will not operate when any of the following conditions is
in effect. The timer is off; the system is in malfunction state; a test run is in
progress; the remote controller is undergoing self-check or remote con- troller check; the user is in the process of selecting a function; the user is in the process of setting the timer; the system is under central control. (Under these conditions, On/Off operation Jsprohibited.)
_ MITSUBISHI ELECTRIC
Sk/_ J"Z "
J
@
@
@ ®
<How to Set the Simple Timer>
[] [] Timer Setting
I
i'Zl¢_--Jr.---" "',4;," [] Action (On or Off)
'_[_ * <'-- --" is displayed if there is no
I [] setting.
1. Be sure that you are at a standard control screen, and that the simple timer indicator is visible in the display (at [_).
When something other than the Simple Timer is displayed, set it to SIMPLE TIMER using the function selection of remote controller (see
8.[4]-3 (3)) timer function setting.
2. Press the Timer Menu button @, so that the "Set Up" appears on the screen (at []). (Note that each press of the button toggles the display
between "Set Up" and "Monitor".)
3. Press the ON/OFF button (_ to display the current ON or OFF simple timer setting. Press the button once to display the time remaining to ON, and then again to display the time remaining to OFR (The ON/ OFF indication appears at _).
"ON" timer:
The air conditioner will start operation when the specified number of hours has elapsed.
"OFF" timer:
The air conditioner will stop operation when the specified number of hours has elapsed.
4. With "ON" or "OFF" showing at _]: Press the appropriate Set Time but- ton @ as necessary to set the hours to ON (if "ON" is displayed) or the hours to OFF (if "OFF" is displayed) at [_.
Available Range: 1 to 72 hours
5. To set both the ON and OFF times, repeat Steps 3 and 4.
Note that ON and OFF times cannot be set to the same value.
6. To clear the current ON or OFF setting: Display the ON or OFF setting (see step 3) and then press the Check (Clear) button @ so that the
time setting clears to "--" at [_. (If you want to use only an ON setting or only an OFF setting, be sure that the setting you do not wish to use isshown as "--".)
8
6. Timer
7. After completing steps 3 to 6 above, press the Filter _J button @ to lock in the value.
Note: Your new settings will be cancelled if you press the Mode (Return) button G
before pressing the Filter_J button (_.
8. Press the Mode (Return) button (D to return to the standard control screen.
9. Press the Timer On/Off button @ to start the timer countdown. When the timer is running, the timer value is visible on the display. Be sure that the timer value is visible and a_riate.
<Viewing the Current Simple Timer Settings>
[] [] Timer Setting
1. Be sure that the simple timer indicator is visible on the screen (at []).
2. Press the Timer Menu button @, so that the "Monitor" appears on the screen (at []).
if the ON or OFF simple timer is running, the current timer value will
appear at [].
if ON and OFF values have both been set, the 2 values appear al-
ternately.
3. Press the Mode (Return) button (D to close the monitor display and return to the standard control screen.
<To Turn Off the Simple Timer...> Press the Timer On/Off button @ so that the timer setting no longer appears on the screen (at []).
[]
<To Turn On the Simple Timer...> Press the Timer On/Off button @ so that the timer setting becomes
visible at [].
[]
Examples If ON and OFF times have both been set at the simple timer, operation and display are as indicated below.
Example 1:
Start the timer, with ON time set sooner than OFF time ON Setting: 3 hours OFF Setting: 7 hours
..-%.......p
:, 7 AF,EROFF
qm'_ ......
-At Timer Start Display shows the timer's ON setting (hours remaining to ON).
m _
At 3 hours after timer startj
- Display changes to show the timer's OFF set- ting (hours remaining to OFF). The time displayed is OFF setting (7 hours) - ON setting (3 hours) = 4 hours.
At 7 hours after timer start
The air conditioner goes off, and wUi remain off until someone restarts it.
Example 2:
Start the timer, with OFF time is sooner than ON time ON Setting: 5 hours OFF Setting: 2 hours
iiillliii!!!i!!!!!!!!!!!ii
N J _,TER
-At Timer Start Display shows the timer's OFF setting (hours remaining to OFF).
At 2 hoursafter timer start)
Display changes to show the timer's ON set- ting (hours remaining to ON). The time displayed is ON setting (5 hours) - OFF setting (2 hours) = 3 hours.
.... At 5 hours after timer start
F
_h12' _%11| The air conditioner comes on, and will con-
e _ @ SM_E tinue to run until someone turns it off.
6.1.3. Auto Off Timer [] This timer begins countdown when the air conditioner starts, and shuts
the air conditioner off when the set time has elapsed.
[] Available settings run from 30 minutes to 4 hours, in 30-minute inter-
vals. Note: "1. Weekly Timer/Simple Timer/Auto Off Timer cannot be used at the same
time.
"2. The Auto Off timer will not operate when any of the following conditions
is in effect.
The timer is off; the system is in malfunction state; a test run is in
progress; the remote controller is undergoing serf-check or remote con-
troller check; the user is in the process of selecting a function; the user
is in the process of setting the timer; the system is under central control. (Under these conditions, On/Off operation is prohibited.)
f
MWSUBISHI ELECTRIC
I
_ TEMP ()I0N'OFF
f :z
\ j'
r
CI'_OO6:_ 8MENU (I)ON/OFF "_'.lll 7,' F_LTER
@ @
<How to Set the Auto Off Timer>
[] [] Timer Setting
1. Be sure that you are at a standard control screen, and that the Auto
Off timer indicator is visible in the display (at m).
When something other than the Auto Off Timer is displayed, set it to
AUTO OFF TIMER using the function selection of remote controller (see
8.[4]-3 (3)) timer function setting.
2. Hold down the Timer Menu button @ for 3 seconds, so that the "Set
Up" appears on the screen (at []). (Note that each press of the button toggles the display between "Set Up" and "Monitor".)
3. Press the appropriate Set Time button @ as necessary to set the OFF
time (at _]).
4. Press the Filter 4J button @ to lock in the setting. Note:
Your entry will be cancelled if you press the Mode (Return) button G before
pressing the Filter_ button Q,
5. Press the Mode (Return) button (D to complete the setting procedure
and return to the standard control screen.
6. if the air conditioner is already running, the timer starts countdown
immediately. Be sure to check that the timer settin ag__o__ears cor- rectly on the display_.
9
6. Timer
<Checking the Current Auto Off Timer Setting> 6.2. For wireless remote controller
[] [] Timer Setting
1. Be sure that the "Auto Off" is visible on the screen (at _).
2. Hold clown the Timer Menu button @ for 3 seconds, so that "Monitor" is indicated on the screen (at []).
The timer remaining to shutdown appears at [_.
3. To close the monitor and return to the standard control screen, press
the Mode (Return) button _.
<To Turn Off the Auto Off Timer...> ® Hold down the Timer On/Off button @ for 3 seconds, so that "Timer
Off" appears (at [_) and the timer value (at []) disappears.
[]
® Alternatively, turn off the air conditioner itself. The timer value (at [])
will disappear from the screen.
[]
<To Turn On the Auto Off Timer...> ® Hold down the Timer On/Off button @ for 3 seconds. The "Timer Off"
indication disappears (at %), and the timer setting comes on the display (at
[]).
[] Alternatively, turn on the air conditioner. The timer value will appear at [].
[]
AUT0STOP AUTOSTART
(_ Press the _ or I_ button (TIMER SET). Time can be set while the following symbol is blinking.
OFF timer: A(_-O is blinking. ON timer: AC)=I is blinking.
h •in
Use the CZ and C_ buttons to set the desired time.
(_ Cancelling the timer. To cancel the OFF timer, press the _ button. To cancel the ON timer, press the _ button.
It is possible to combine both OFF and ON timers.
Pressing the (_ ON/OFF button of the remote controller during timer mode to stop the unit will cancel the timers.
if the current time has not been set, the timer operation cannot be used.
7. Other Functions
7.1. Locking the Remote Controller Buttons (Operation
function limit controller)
[] If you wish, you can lock the remote controller buttons. You can use
the Function Selection of remote controller to select which type of lock to use. (For information about selecting the lock type, see section 8,
item [4]-2 (1)). Specifically, you can use either of the following 2 lock types.
Lock All Buttons: Locks all of the buttons on the remote controller.
(D LockAII Except ON/OFF:
Locks all buttons other than the ON/OFF button.
Note: The "Locked" indicator appears on the screen to indicate that buttons are
currently locked.
TEMP _i) ONOFF
[]
[]
Lock Indicator
@ ®
<How to Lock the Buttons>
1. While holding down the Filter button @, press and hold down the ON/ OFF button _ for 2 seconds. The "Locked" indication appears on the screen (at []), indicating that the lock is now engaged. * if locking has been disabled in Function Selection of remote control-
ler, the screen will display the "Not Available" message when you press the buttons as described above.
i
o If you press a locked button, the "Locked" indication (at _) will blink
on the display.
<How to Unlock the Buttons>
1. While holding down the Filter button @, press and hold down the ON/ OFF button (_ for 2 seconds--so that the "Locked" indication disap- pears from the screen (at []).
'w I
t0
7. Other Functions
7.2. Error Codes indication
MITSUBISHI ELECTRIC
iCldi'_/OO,
--:,/ I/ I/_,1 II i/-
mmr-,_/__
I (_)ON/OFF
Indoor Unit's Refrig- Error Code Indoor Unit No.
erantAddress [ J
If you have entered contact number to be called in the event of a problem, the screen displays this Alternating Display number. (You can set this up under Function Selection of remote controller. For information, refer to section 8.)
ON lamp (Flashing)
If the ON lamp and error code are both blinking: This means that the air conditioner is out of order and operation has been stopped (and cannot resume). Take note of the indicated unit number and error code, then switch off the power to the air conditioner and call your dealer or servicer.
....................... M'TS"B'S.;ELEOT"iC.............................................................................................................................................................."
i .........................................................................................................\ # / ,.......
:'_":_ / _T ° , I I
I °F uL'l¢-' ll I
_ONIOFF
Error Code
When the Check button is Dressed:
_ MITSUBISH|ELECTRIC
(_)ON/OFF
o
® If only the error code is blinking (while the ON lamp remains lit): Operation is continuing, but there may be a problem with the system. In this case,
you should note down the error code and then call your dealer or servicer for advice.
* If you have entered contact number to be called in the event of a problem, push the Check button to display it on the screen. (You can set this up
under Function Selection of remote controller. For information, refer to section 8.)
8. Function Selection
Function selection of remote controller
The setting of the following remote controller functions can be changed using the remote controller function selection mode. Change the setting when needed.
Item 1 Item 2 Item 3 (Setting content)
1. Change Language Language setting to display Display in multiple languages is possible ("CHANGE LAN- GUAGE")
2. Function limit (1) Operation function limit setting (operation lock) ("LOCKING Setting the range of operation limit (operation lock) ("FUNCTION SELEC- FUNCTION")
TION")
(2) Use of automatic mode setting ("SELECT AUTO MODE") Setting the use or non-use of "automatic" operation mode
(3) Temperature range limit setting ("LIMIT TEMP FUNCTION") Setting the temperature adjustable range (maximum, minimum)
3. Mode selection (1) Remote controller main/sub setting ("CONTROLLER MAIN/ Selecting main or sub remote controller ("MODE SELEC- SUB") * When 2 remote controllers are connected to one group, one controller
TION") must be set to sub.
(2) Use of clock setting ("CLOCK") Setting the use or non-use of clock function
(3) Timer function setting ("WEEKLY TIMER") Setting the timer type
(4) Contact number setting for error situation ("CALL.") Contact number display in case of error
Setting the telephone number
4. Display change (1) Temperature display °C/°F setting ("TEMP MODE °C/°F '') Setting the temperature unit (°C or °F) to display ("DISP MODE SET-
TING") (2) Suction air temperature display setting ("ROOM TEMP DISP Setting the use or non-use of the display of indoor (suction) air tempera-
SELECT") ture
(3) Automatic cooling/heating display setting ("AUTO MODE Setting the use or non-use of the display of "Cooling" or "Heating" dis-
DISP C/H") ptay during operation with automatic mode
tl
8. Function Selection
[Function selection flowchart] Setting language (English)
Change
Language
Function selection
Mode selection
Display mode setting
Item 1
Remote controller function selection mode
' i i (_ Item2
_ _nglish
I _ German
I _ Spanish
_l _ Russian
(_) _) _ _ Italian
_r_ Chinese
_ French
_[_ _ Japanese
I
I
®
i
I I
i
' G _
i
©
Normal display
IjD sp ay when the a r cond t oner is not running) Hold down the (_) button and press the © button for 2 seconds.
Hold down the (_) button and press the © button for 2 seconds. [ (_)Press the operation mode button.
(_)Press the TIMER MENU button. ©Press the TIMER ON/OFF button.
Dot display
(_
G_
© ©
item 3
)
)
©
Operation lock setting is not used. (Initial setting value)
Operation lock setting is except On/Off button.
Operation lock setting is all buttons.
The automatic mode is displayed when the operation mode is selected. (Initial setting value)
The automatic mode is not displayed when the operation mode
is selected.
The temperature range limit is not active. (Initial setting value)
The temperature range can be changed on cooling/dry mode.
The temperature range can be changed on heating mode.
The temperature range can be changed on automatic mode.
Automatic filter elevation panel up/down operation mode Not necessaryto set this mode.Refer to OPERATION MANUAL of Optionat Parts (Panel) for details on operation.
Fixed airflow direction mode Not necessaryto set this mode.Refer to OPERATION MANUAL of indoor unit for details on operation.
The remotecontroller will be the main controller. (initial setting value)
The remote controller will be the sub controller.
The clock function can be used. (Initial setting value)
The clock function can not be used.
Weekly timer can be used. (Initial setting value)
Auto off timer can be used.
Simple timer can be used.
Timer mode can not be used.
The set contact numbers are not displayed in case of error.
(Initial setting value)
The set contact numbers are displayed in case of error.
The temperature unit °F is used. (Initial setting value)
The temperature unit °C is used.
Room air temperature is displayed. (Initial setting value)
Room air temperature is not displayed.
One of "Automatic cooling" and "Automatic heating" is displayed
under the automatic mode is running. (Initial setting value)
Only "Automatic" is displayed under the automatic mode.
t2
8. Function Selection
[Detailed setting] [4]-1. CHANGE LANGUAGE setting
The language that appears on the dot display can be selected.
Press the [Q MENU] button @ to change the language. (_ English (GB), (_) German (D), (_ Spanish (E), (_ Russian (RU), (_) Italian (I), (_ Chinese (CH), (_ French (F), (_ Japanese (JP)
Refer to the dot display table.
[4]-2. Function limit
(1) Operation function limit settin¢l (operation lock)
To switch the setting, press the [@ ON/OFF] button @. (_ no1 : Operation lock setting ismade on all buttons other
than the [Q ON/OFF] button O. (D no2 : Operation lock setting is made on all buttons. (_ OFF (initial setting value): Operation lock setting is not made.
To make the operation lock setting valid on the normal screen, it is necessary to press buttons (Press and hold down the [FILTER] @ and [_ ON/OFF] O buttons at the same time for 2 seconds.) on the normal screen after the above setting is made.
(2) Use of automatic mode settinq
When the remote controller is connected to the unit that has auto- matic operation mode, the following settings can be made.
To switch the setting, press the [@ ON/OFF] button @. (_ ON (Initial setting value):
The automatic mode is displayed when the operation mode is selected.
(D OFF:
The automatic mode is not displayed when the operation
mode is selected.
(3) Temperature ranqe limit settinq
After this setting is made, the temperature can be changed within
the set range.
To switch the setting, press the [@ ON/OFF] button @. C) LIMITTEMP COOL MODE:
The temperature range can be changed on cooling/dry mode.
LIMIT TEMP HEAT MODE:
The temperature range can be changed on heating mode.
(_ LIMITTEMPAUTO MODE:
The temperature range can be changed on automatic mode.
@ OFF (initial setting): The temperature range limit is not active.
When the setting, other than OFF, is made, the temperature range limit setting on cooling, heating and automatic mode is made at the same time. However, the range cannot be limited when the set temperature range has not changed.
To increase or decrease the temperature, press the [_TEMP. (V) or (A)] button (_.
To switch the upper limit setting and the lower limit setting, press the [¢,d ] button @. The selected setting will flash and the tem- perature can be set.
Set table range Cooling/Dry mode:
Lower limit: 19°C ~ 30°C, 67°F ~ 87°F Upperlimit:30°C~19°C, 87°F~67°F
Heating mode:
Lower limit: 17°C ~ 28°C, 63°F ~ 83°F Upper limit: 28°C ~ 17°C, 83°F ~ 63°F
Automatic mode:
Lower limit: 19°C ~ 28°C, 67°F ~ 83°F Upperlimit:28°C~19°C, 83°F~67°F
[4]-3. Mode selection setting
(1) Remote controller main/sub settinq
To switch the setting, press the [Q ON/OFF] button @. (_ Main: The controller will be the main controller. (D Sub: The controller will be the sub controller.
(2) Use of clock settinq
To switch the setting, press the [@ ON/OFF] button @. (_ ON: The clock function can be used.
OFF: The clock function cannot be used.
(3) Timer function setting
To switch the setting, press the [@ ON/OFF] button @ (Choose one of the followings.). (_ WEEKLY TIMER (initial setting value):
The weekly timer can be used.
(_) AUTO OFF TIMER:
The auto off timer can be used.
(_ SIMPLE TIMER:
The simple timer can be used.
@ TIMER MODE OFF:
The timer mode cannot be used.
When the use of clock setting is OFF, the "WEEKLY TIMER" can- not be used.
(4) Contact number settinq for error situation
To switch the setting, press the [Q ON/OFF] button @. (_ CALL OFF:
The set contact numbers are not displayed in case of error.
(_) CALL ............
The set contact numbers are displayed in case of error.
CALL :
The contact number can be set when the display is as shown on the left.
Setting the contact numbers
To set the contact numbers, follow the following procedures. Move the blinking cursor to set numbers. Press the [,_TEMP.
(V) and (A)] button _ to move the cursor to the right (left). Press the [Q CLOCK (V) and (A)] button © to set the num- bers.
[4]-4. Display change setting
(1) Temperature dis lily °C/°F settinq
To switch the setting, press the [@ ON/OFF] button @. (_ °C: The temperature unit °C is used.
°F: The temperature unit °F is used.
(2) Suction air temperature display settinq
To switch the setting, press the [Q ON/OFF] button @. (_ ON: The suction air temperature is displayed.
OFF: The suction air temperature is not displayed.
f3_ Automatic coolina/heatinq disdispla_q
, To switch the setting, press the [Q ON/OFF] button @.
(_ ON:
One of "Automatic cooling" and "Automatic heating" is dis- played under the automatic mode is running.
(_) OFF:
Only "Automatic" is displayed under the automatic mode.
t3
8. Function Selection
[Dot display table]
Selecting language English German Spanish Russian italian Chinese French Japanese
Waiting for start-up 4--- 4--- _ 4--- <-_ 4-_ <---
Operation mode
DSJHUml;
BESHg
_LNZiONE
_LnT|OH _L_TION
Coo(
Dry Heat
Auto
Auto (Cool)
Auto (Heat)
Fan
Ventilation
Stand by (Hot adiust ) Defrost
Set temperature
Fan speed
i Not use button
Check (Error) Test run
Self check
Unit function selection
Setting of ventilation
Selecting language
CHANGE LANGUAGE
Function selection
Operation function limit setting
Use of automatic mode setting
i i Temperature range limit setting
i I i Limit temperature cooling/day
i mode i Limit temperature heating mode
Limit temperature auto mode
Mode selection
Remote controller setting MAIN
Remote controller setting SUB
Use of clock setting
Setting the day of the week and time Timer set
Timer monitor
Weekly timer
Timer mode off
Auto off timer
Simple timer
Contact number setting of error situation
Display change
Temperature display °C/°F setting
Room air temperature display set- ting Automatic cooling/heating display setting
t4
9. Emergency Operation for Wireless Remote=controller
© ©
® ® ®
Fig. 9-1
(For PKA-A.HA / PKA-A.HAL)
Fig. 9=2
When the remote contro((er cannot be used When the batteries of the remote control(er run out or the remote contro(-
(er malfunctions, the emergency operation can be done using the emer- gency buttons.
[Fig.9-1] @ DEFROST/STAND BY lamp
® Operation lamp © Emergency operation switch (heating) © Emergency operation switch (cooling) ® Receiver
Starting operation
To operate the cooling mode, press the © button @ for more than 2 seconds.
To operate the heating mode, press the O button © for more than 2 seconds.
Stopping operation
To stop operation, press the O button @ or the C_button © for more
than 2 seconds.
[Fig.9-2] @ DEFROST/STAND BY lamp (Orange)
(_ Operation lamp (Green) © Emergency operation switch (cooling/heating) © Receiver
Each press of the emergency operation switch will toggle the operation
mode.
Check "COOL/HEAT" with the operation monitor display. (The orange lamp @ follows this monitor display for 5 seconds after pressing the emergency operation switch.)
[Heat pump type] [Cooling only type]
Operation Monitor Display
GREEN ORANGE
STOP O O The orange lamp follows the
...........................................................................................................................................................................................switch operation as indicated
COOL O O at the left for 5 seconds, and
then it will return to the normal
HEAT O _ display. O: Turning off _: Lighting
Note:
Details of emergency mode are as shown below.
Operation mode COOL Set temperature 24°C, 75°F Fan speed High
Airflow direction Horizontal
HEAT
24°C, 75°F
High
Downward 4 (5)
10. Care and Cleaning
[] indicates that the filter needs cleaning.
Ask authorized people to clean the filter.
[] When resetting "FILTER" display
When the [FILTER] button is pressed 2 times successively after clean- ing the filter, the display goes off and is reset.
Note: ® When 2 or more different types of indoor unit are controlled, the cleaning
period differs with the type of filter. When the master unit cleaning period
arrives, "FILTER" is displayed, When the filter display goes off, the cumu=
lative time is reset.
® "FILTER" indicates the cleaning period when the air conditioner was used
under general indoor air conditions by criteria time, Since the degree of
dirtiness depends on the environmental conditions, clean the filter accord=
ingly.
® The filter cleaning period cumulative time differs with the model, ® This indication is not available for wireless remote controller.
11. Trouble Shooting
Air conditioner does not heat or cool well. [] Clean the filter. (Airflow is reduced when the filter is dirty or clogged.)
[] Check the temperature adjustment and adjust the set temperature. [] Make sure that there is plenty of space around the outdoor unit. Is the
indoor unit air intake or outlet blocked?
[] Has a door or window been left open?
When heating operation starts, warm air does not blow from the indoor [] Warm air does not blow until the indoor unit has sufficiently warmed
unit soon. up. During heating mode, the air conditioner stops before the set room tem- [] When the outdoor temperature is low and the humidity is high, frost
perature is reached, may form on the outdoor unit. If this occurs, the outdoor unit performs
a defrosting operation. Normal operation should begin after approxi- mately 10 minutes.
i5
Loading...
+ 35 hidden pages