Mitsubishi PLH18AK, PL12AK, PCH24GK, PKH18FL, PK18FL3 Operation Manual

...
Page 1
Air-Conditioners
PLH18, 24, 30, 36, 42AK PL12, 18, 24, 30, 36, 42AK PCH24, 30, 36, 42GK PC24, 30, 36, 42GK PKH18, 24, 30, 36FK3 PK12, 18, 24, 30, 36FK3 PKH18, 24, 30, 36FL PK18, 24, 30, 36FL3
OPERATION MANUAL
For safe and correct use, please read this operation manual thoroughly before operating the air-conditioner unit.
FOR USER
Page 2
2
s Before installing the unit, make sure you read all the “Safety precautions”. s The “Safety precautions” provide very important points regarding safety.
Make sure you follow them.
s If none of the above apply, turn the main switch off and contact the
dealer from whom you bought the air-conditioner, telling him the model name and the nature of the problem. Do not try to fix the unit yourself.
Symbols used in the text
Warning: Describes precautions that should be observed to prevent danger of injury or death to the user.
Caution: Describes precautions that should be observed to prevent damage to the unit.
1. Safety PrecautionsContents
1. Safety Precautions .................................................................................... 2
2. Operation ................................................................................................... 3
2.1. Switching the unit on/off .............................................................. 3
2.2. Mode select ................................................................................. 3
2.3. Selecting a temperature .............................................................. 3
2.4. Selecting a fan speed .................................................................. 3
2.5. Adjusting airflow direction............................................................ 4
2.6. Using the timer ............................................................................ 4
3. Care and cleaning ..................................................................................... 5
3.1. Cleaning the filters and the indoor unit ........................................ 5
3.2. Care and cleaning ....................................................................... 6
4. Troubleshooting ......................................................................................... 6
5. Specifications ............................................................................................ 7
Symbols used in the illustrations
: Indicates an action that must be avoided.
: Indicates that important instructions must be followed.
: Indicates a part which must be grounded.
Warning: Carefully read the labels affixed to the main unit.
Warning:
• The unit should not be installed by the user. Ask the dealer or an authorized
company to install the unit. If the unit is installed improperly, water leakage, electric shock or fire may result.
• Do not stand on, or place any items on the unit.
• Do not splash water over the unit and do not touch the unit with wet hands.
An electric shock may result.
• Do not spray combustible gas close to the unit. Fire may result.
• Do not place a gas heater or any other open-flame appliance where it will be
exposed to the air discharged from the unit. Incomplete combustion may result.
Caution:
• Do not use any sharp object to push the buttons, as this may damage the
remote controller.
• Never block or cover the indoor or outdoor unit’s intakes or outlets.
Warning:
• Do not remove the front panel or the fan guard from the outdoor unit when it
is running. You could be injured if you touch rotating, hot or high-voltage parts.
• Never insert fingers, sticks etc. into the intakes or outlets, otherwise injury
may result, since the fan inside the unit rotates at high speed.
• If you detect odd smells, stop using the unit, turn off the power switch and
consult your dealer.
• This air conditioner is NOT intended for use by children or infirm persons
without supervisions.
• Young children should be supervised to ensure that they do not play with
the air conditioner.
Disposing of the unit
When you need to dispose of the unit, consult your dealer. If pipes are removed incorrectly, refrigerant (fluorocarbon gas) may blow out and come into contact with your skin, causing injury. Releasing refrigerant into the atmosphere also damages the environment.
O
N
/ O
F F
S T A
N D
B
Y D E F
R O S
T
D
R Y
C
O O
L A U
T O
F A
N
H
E A
T
C
E
N
T
R A
L L
Y C O
N T R
O L
L E
D
˚ F
S W
I N G
F A N S P E
E D
A U
T
O R E T U
R
N
N O
T A
V A
IL A
B L
E
˚ F
C H
E C K
M O D
E
F IL
T E R
T I
M E
R
T E
S T
R U
N
T I M
E R O
F F
C
L O C K
A U
T O A
U T O
C H
E C K
S E T T E
M P
.
S T A
R T S T
O P
Page 3
3
ON/OFF
TIMER SETSET TEMP.
REMOTE CONTROLLER
MODE TIMER ON/OFF CLOCK/TIMER FAN SPEED AIR DISCHARGE FILTER
AIR SWEEP CHECK
TEST RUN
STAND BY DEFROST
DRY COOL
AUTO FAN
HEAT
CENTRALLY CONTROLLED
˚F
SWING
FAN SPEED
AUTO
RETURN
NOT AVAILABLE
˚F
CHECK MODE
FILTER
TIMER
TEST RUN
TIMER OFF CLOCK AUTO AUTO
CHECK SET TEMP. START STOP
A
1
2. Operation
Operating range
Indoor air intake temperature Outdoor air intake temperature
Cooling
Maximum 95 °F DB, 71 °F WB 115 °F DB Minimum 67 °F DB, 57 °F WB 0 °F DB*
Heating
Maximum 80 °F DB, 67 °F WB 75 °F DB, 65 °F WB Minimum 70 °F DB, 60 °F WB 17 °F DB, 15 °F WB
* With wind baffle installed. Without wind baffle, the minumum temperature will be
23 °F DB.
2.1. Switching the unit on/off
• The power supply should not be turned off while the air conditioner is in use. This can cause the unit to break down. 1 Press the ON/OFF button.
A The ON indicator should light up.
• Even if you press the ON/OFF button immediately after shutting down the opera­tion in progress, the air conditioner will not start for about three minutes. This is to prevent the internal components from being damaged.
• If the operation stops due to a power failure, the unit will not automatically restart until the power has been restored. Press the ON/OFF button to restart.
2.2. Mode select
1 If the unit is off, press the ON/OFF button to turn it on.
A The ON indicator should light up.
2
Press the operation mode button C and select the operation mode.
B
COOL Cooling mode AUTO Automatic (cooling/heating) mode
(For PLH/PCH/PKH)
DRY Drying mode HEAT Heating mode
(For PLH/PCH/PKH)
FAN Fan mode
(For PL/PC/PK)
Note: The heating display and the automatic display does not appear in models that operate exclusively as cooling only air-conditioner.
2.3. Selecting a temperature
ss
ss
s To decrease the room temperature:
1 Press set temperature button to set the desired temperature.
A The selected temperature is displayed.
• Each time you press the button, the temperature value decreases by 2 °F.
ss
ss
s To increase the room temperature:
1 Press set temperature button to set the desired temperature.
A The selected temperature is displayed.
• Each time you press the button, the temperature value increases by 2 °F.
• Available temperature ranges are as follows:
Cooling & Drying: 65 - 87 °F Heating: 61 - 83 °F Automatic: 65 - 83 °F
• The display flashes either 47 °F or 97 °F to inform you if the room temperture is lower or higher than the displayed temperature.
2.4. Selecting a fan speed
1 Press fan speed button to select a desired fan speed.
• Each time you press the button, available options change with the display A on the remote controller, as shown below.
Wireless type Wired type
Display
FAN SPEED
FAN SPEED
Available Option (Fan Speed Switch)
Low-High Low-High
The display and the fan speed of the unit will differ in the following situations:
• When STAND BY and DEFROST are displayed.
• Just after the heating mode (while waiting to change to another mode).
• When the temperature of the room is higher than the temperature setting of the unit operating in the heating mode.
• In Dry mode, where the speed is set automatically and cannot be changed. Only the display on the remote controller changes.
ON/OFF
TIMER SETSET TEMP.
REMOTE CONTROLLER
MODE TIMER ON/OFF CLOCK/TIMER FAN SPEED AIR DISCHARGE FILTER
AIR SWEEP CHECK
TEST RUN
STAND BY DEFROST
DRY COOL
AUTO FAN
HEAT
CENTRALLY CONTROLLED
˚F
SWING
FAN SPEED
AUTO
RETURN
NOT AVAILABLE
˚F
CHECK MODE
FILTER
TIMER
TEST RUN
TIMER OFF CLOCK AUTO AUTO
CHECK SET TEMP. START STOP
A
1
ON/OFF TEMP
FAN
VANE
TEST RUN
AUTO STOP
AUTO START
h
min
LOUVER
MODE
CHECK
RESETSET CLOCK
MODEL SELECT
NOT AVAILABLE
SWING
CHECK
FAN
TEST RUN
˚F ˚C
AMPMSTOP
START
AMPM
COOL
DRY
AUTO
FAN
HEAT
1
ON/OFF TEMP
FAN
VANE
TEST RUN
AUTO STOP
AUTO START
h
min
LOUVER
MODE
CHECK
RESETSET CLOCK
MODEL SELECT
NOT AVAILABLE
SWING
CHECK
FAN
TEST RUN
˚F ˚C
AMPMSTOP
START
AMPM
COOL
DRY
AUTO
FAN
HEAT
B
C
ON/OFF TEMP
FAN
VANE
TEST RUN
AUTO STOP
AUTO START
h
min
LOUVER
MODE
CHECK
RESETSET CLOCK
MODEL SELECT
NOT AVAILABLE
SWING
CHECK
FAN
TEST
RUN
˚F ˚C
AMPMSTOP
START
AMPM
COOL
DRY
AUTO
FAN
HEAT
A
1
ON/OFF
TIMER SETSET TEMP.
REMOTE CONTROLLER
MODE TIMER ON/OFF CLOCK/TIMER FAN SPEED AIR DISCHARGE FILTER
AIR SWEEP CHECK
TEST RUN
STAND BY DEFROST
DRY COOL
AUTO FAN
HEAT
CENTRALLY CONTROLLED
˚F
SWING
FAN SPEED
AUTO
RETURN
NOT AVAILABLE
˚F
CHECK MODE
FILTER
TIMER
TEST RUN
TIMER OFF CLOCK AUTO AUTO
CHECK SET TEMP. START STOP
A
1
ON/OFF
TIMER SETSET TEMP.
REMOTE CONTROLLER
MODE TIMER ON/OFF CLOCK/TIMER FAN SPEED AIR DISCHARGE FILTER
AIR SWEEP CHECK
TEST RUN
STAND BY DEFROST
DRY COOL
AUTO FAN
HEAT
CENTRALLY CONTROLLED
˚F
SWING
FAN SPEED
AUTO
RETURN
NOT AVAILABLE
˚F
CHECK MODE
FILTER
TIMER
TEST RUN
TIMER OFF CLOCK AUTO AUTO
CHECK SET TEMP. START STOP
A
1
BC
ON/OFF TEMP
FAN
VANE
TEST RUN
AUTO STOP
AUTO START
h
min
LOUVER
MODE
CHECK
RESETSET CLOCK
MODEL
SELECT
NOT AVAILABLE
SWING
CHECK
FAN
TEST RUN
˚F ˚C
AMPMSTOP
START
AMPM
COOL
DRY
AUTO
FAN
HEAT
A
1
FAN
FAN
Page 4
4
ON/OFF
TIMER SETSET TEMP.
REMOTE CONTROLLER
MODE TIMER ON/OFF CLOCK/TIMER FAN SPEED AIR DISCHARGE FILTER
AIR SWEEP CHECK
TEST RUN
STAND BY DEFROST
DRY COOL
AUTO FAN
HEAT
CENTRALLY CONTROLLED
˚F
SWING
FAN SPEED
AUTO
RETURN
NOT AVAILABLE
˚F
CHECK MODE
FILTER
TIMER
TEST RUN
TIMER OFF CLOCK AUTO AUTO
CHECK SET TEMP. START STOP
F
1
2. Operation
2.5. Adjusting airflow direction
The vertical air vane helps select the vertical direction of the airflow. 1 Press AIR DISCHARGE button to select the vertical airflow direction.
Each time you press the button, the option changes are displayed on the remote controller, as shown below.
A (swing) B C D E A
In cooling/drying mode with the fan speed set to LOW, every press on the button will change the direction in the order of A, B, D, A. (C can not be set)
If D or E is set, the angle will automatically revert to B after one hour of operation. (Do not use D and E too often in cooling/drying mode with the fan speed set to LOW, or condensation or dripping can occur.) F AUTO RETURN” should be displayed.
When the angle setting is C in cooling mode, switching the fan speed from HIGH to LOW will cause the angle to revert to B automatically.
The airflow direction can not be set with UP/DOWN while the SWING setting is being used.
The arrow indicators are alternately displayed when the air sweep is in operation,
however they are not displayed when the air sweep is not in operation.
The left/right guide vanes of PC(H) series and the guide vane of the PK(H) serises can be changed manually.
2.6. Using the timer
1) Set the current time
1 Press clock/timer button to display the “CLOCK B.
Remote
CLOCK
AUTO
START
AUTO
STOP
No Display
controller display A
2 Each time you press
TIMER SET
button, the time increases in increments of one minute.
Each time you press
TIMER SET
button, the time decreases in increments of one minute.
Press and hold the button to rapidly change the time.
The time changes in increments of one minute ten minutes in units of hour; in
this order.
Approximately ten seconds after pressing the button, the display on the remote controller will turn off.
(For Wireless Remote Controller)
1 Press the CLOCK button using a thin stick and blink the time A. 2 Press the h and
min
button to set the current time.
3 Press the CLOCK button using a thin stick.
2) Set the time to start the unit as follows
1 Press clock/timer button to display B
AUTO
START
.
2 Press
TIMER SET
button to set the time that you want the unit to start.
The start time is displayed at A.
(For Wireless Remote Controller)
1 Press the
AUTO START
button.
Time can be set while the following symbol is blinking. ON time : B START is blinking.
2 Use the
h
and
min
buttons to set the desired time.
3 To cancel the ON timer, press the
AUTO START
button.
3) Set the time to stop the unit as follows
1 Press clock/timer button to display C
AUTO
STOP
.
2 Press
TIMER SET
button to set the time that you want the unit to stop.
The stop time is displayed at A.
(For Wireless Remote Controller)
1 Press the
AUTO STOP
button.
Time can be set while the following symbol is blinking. OFF time : C STOP is blinking.
2 Use the
h
and
min
buttons to set the desired time.
3 To cancel the OFF timer, press the
AUTO STOP
button.
4) Changing the set times
1 Press clock/timer button to display the time (CURRENT, START, STOP) you want
to change.
2 Press
TIMER SET
button to set the desired time.
When change is made to either one of a pair, e.g., AUTO START or AUTO STOP, set the time you need not to change to
. This display is available following
23:50.
(For Wireless Remote Controller)
Press the
AUTO START
or
AUTO STOP
to cancel the timer and repeat from 2) or 3).
ABCDE
ABCDE
PL(H) Swing 30° 45° 55° 70° PK(H)* Swing 10° 30° 60° 70° PK12FK3 10° 30° 60° 70° PC(H) Swing
100% Horizontal
20° 40° 60°
* Except PK12FK3
ON/OFF TEMP
FAN
VANE
TEST RUN
AUTO STOP
AUTO START
h
min
LOUVER
MODE
CHECK
RESETSET CLOCK
MODEL SELECT
NOT AVAILABLE
SWING
CHECK
FAN
TEST RUN
˚F ˚C
AMPMSTOP
START
AMPM
COOL
DRY
AUTO
FAN
HEAT
1
ON/OFF
TIMER SETSET TEMP.
REMOTE CONTROLLER
MODE TIMER ON/OFF CLOCK/TIMER FAN SPEED AIR DISCHARGE FILTER
AIR SWEEP CHECK
TEST RUN
STAND BY DEFROST
DRY COOL
AUTO FAN
HEAT
CENTRALLY CONTROLLED
˚F
SWING
FAN SPEED
AUTO
RETURN
NOT AVAILABLE
˚F
CHECK MODE
FILTER
TIMER
TEST RUN
TIMER OFF CLOCK AUTO AUTO
CHECK SET TEMP. START STOP
B
1
2
A
ON/OFF TEMP
FAN
VANE
TEST RUN
AUTO STOP
AUTO START
h
min
LOUVER
MODE
CHECK
RESETSET CLOCK
MODEL
SELECT
NOT AVAILABLE
SWING
CHECK
FAN
TEST
RUN
˚F ˚C
AMPMSTOP
START
AMPM
COOL
DRY
AUTO
FAN
HEAT
A
2
13
ON/OFF
TIMER SETSET TEMP.
REMOTE CONTROLLER
MODE TIMER ON/OFF CLOCK/TIMER FAN SPEED AIR DISCHARGE FILTER
AIR SWEEP CHECK
TEST RUN
STAND BY DEFROST
DRY COOL
AUTO FAN
HEAT
CENTRALLY CONTROLLED
˚F
SWING
FAN SPEED
AUTO
RETURN
NOT AVAILABLE
˚F
CHECK MODE
FILTER
TIMER
TEST RUN
TIMER OFF CLOCK AUTO AUTO
CHECK SET TEMP. START STOP
ABC
1
2
ON/OFF TEMP
FAN
VANE
TEST RUN
AUTO STOP
AUTO START
h
min
LOUVER
MODE
CHECK
RESETSET CLOCK
MODEL SELECT
NOT AVAILABLE
SWING
CHECK
FAN
TEST RUN
˚F ˚C
AMPMSTOP
START
AMPM
COOL
DRY
AUTO
FAN
HEAT
C
13
A B
2
Page 5
5
C
B
D
A
ON/OFF
STAND BY
DEFROST
DRYCOOL
AUTOFAN
HEAT
CENTRALLY CONTROLLED
˚F
SWING
FAN SPEED
AUTO RETURN
NOT AVAILABLE
˚F
CHECK MODE
FILTER
TIMER
TEST RUN
TIMER OFF CLOCKAUTO AUTO
CHECKSET TEMP. STARTSTOP
B
A
D
C
3. Care and cleaning
Caution:
Always turn off the power, first on the remote controller and then the main
switch, before cleaning or servicing the unit.
When installing or removing the filter or the intake grille, do not stand on an
unsteady surface. You may fall and injure yourself. Be also careful not to let dust fall into your eyes.
Dirty or clogged filters block the airflow and reduce efficiency. Very dirty filters can damage the air-conditioner itself.
PLH/PL Series
Intake grille removal
Pull the knob on the intake grille in the direction indicated by the arrow and it
should open.
Unhook the hinges to remove the intake grille from the grille.
Filter removal
Open the intake grille.
Release the knob on the center edge of the intake grille and pull the filter forward
to remove the filter.
A Knob B Grille C Intake grille D Filter
PCH/PC Series
Open the intake grille.
Hold the knob on the filter then pull the filter up in the direction of an arrow. To
replace the filter after cleaning, be sure to insert the filter far enough until it fits into the stopper.
A Filter B Intake Grille C Knob D Stopper
PKH/PK Series
Hold the filter lug (located at the bottom of the intake grill) and pull it out downward.
To install the filters, push the filter lug upward.
A Filter B Lug
3.1. Cleaning the filters and the indoor unit
Cleaning the filters
Clean the filters using a vacuum cleaner. If you do not have a vacuum cleaner, tap
the filters against a solid object to knock off dirt and dust.
If the filters are especially dir ty, wash them in lukewarm water. Take care to rinse
off any detergent thoroughly and allow the filters to dry completely before putting them back into the unit.
Caution:
Do not dry the filters in direct sunlight or by using a heat source, such as an
electric heater: this may warp them.
Do not wash the filters in hot water (above 120°F), as this may warp them.
Make sure that the air filters are always installed. Operating the unit without
air filters can cause malfunction.
Cleaning the indoor unit
Wipe the outside of the unit with a clean, dry, soft cloth.
Clean off any oil stains or finger marks using a neutral household detergent (such
as dishwashing liquid or laundry detergent).
Caution: Never use gasoline, benzene, thinner, scouring powder or any type of non­neutral detergent, as these substances may damage the unit’s case.
PLH/PL Series
PCH/PC Series
PKH/PK Series
B
A
Page 6
6
4. Troubleshooting
NOTE: After a power cut, the unit will not restart automatically. You will have to restart it by pressing the POWER - ON/OFF button on the remote controller.
Wired remote controllers
In any of the following cases, turn off the main power switch and contact your local dealer for service:
•“CHECK” followed by “P1”, “P2”, “P3”, “P4”, “P5”, “P7” or “CENTRALLY CONTROLLED” is displayed on the control panel.
The switches do not work properly.
The circuit breaker trips frequently (or the fuse blows frequently).
Water has accidentally been splashed into the unit.
Water leaks from the unit.
Something is accidentally dropped into the air-conditioner.
An unusual noise is heard during operation.
Warning: If the air conditioner operates but does not cool or heat (depending on model) the room, consult your dealer since there may be a refrigerant leak. Be sure to ask the service representative whether there is refrigerant leakage or not when repairs are carried out. The refrigerant charged in the air conditioner is safe. Refrigerant normally does not leak, however, if refrigerant gas leaks indoors, and comes into contact with the fire of a fan heater, space heater, stove, etc., harmful substances will be generated.
Problem
Unit will not start.
Unit discharges air well, but fails to cool or heat the room well.
Unit does not start immediately.
Unit stops soon after starting.
Cause
Main power switch is turned off.
Main power fuse has blown.
Outdoor units ground fault breaker is open.
A power cut has occurred (see NOTE be­low).
Improper temperature setting - e.g. you have selected COOL mode, but the desired temperature setting is higher than the cur­rent room temperature.
Filters are clogged.
Outdoor units intake or outlet is obstructed.
A door or window has been left open.
Unit is waiting three minutes before restart­ing.
Indoor or outdoor units intake or outlet is obstructed.
Filters are clogged.
Solution
Turn main power on. Then press the POWER ON/OFF button to turn the unit on.
Replace the fuse.
Reset the ground fault breaker.
Wait until power is restored, then press the POWER ON/OFF button to turn the unit on.
Check the set temperature on the remote controller and the actual intake air tem­perature. Use the COOLER and WARMER buttons to set the temperature as described in Selecting a temperature on page 3.
Clean the filter and resume operation. See Cleaning the filters and the indoor unit on page 5.
Remove the obstruction.
Shut door or window.
Wait until the unit restarts automatically. The compressor may hesitate resuming because a three-minute resume preven­tion circuit is incorporated in the outdoor unit for protection of the compressor.
Remove obstruction and restart the unit.
Remove the obstruction. Clean the filter and resume operation.
Display reading
Pilot lamp does not turn on even when the POWER ON/OFF button is pressed.
Remote controller shows that the unit is operating.
Remote controller shows that the unit is operating.
Remote controller check display reads CHECK P6 or CHECK P8.
4. Troubleshooting
Before you call out a repair man, check the following table to see whether there is a simple solution to your problem.
ON/OFF
TIMER SETSET TEMP.
REMOTE CONTROLLER
MODE TIMER ON/OFF CLOCK/TIMER FAN SPEED AIR DISCHARGE FILTER
AIR SWEEP CHECK
TEST RUN
STAND BY DEFROST
DRY COOL
AUTO FAN
HEAT
CENTRALLY CONTROLLED
˚F
SWING
FAN SPEED
AUTO
RETURN
NOT AVAILABLE
˚F
CHECK MODE
FILTER
TIMER
TEST RUN
TIMER OFF CLOCK AUTO AUTO
CHECK SET TEMP. START STOP
A
1
3.2. Care and cleaning
Clean the filter
When the A FILTER” indicator blinks on the remote controller to alert you to the necessity of cleaning of the filter. As a guideline for typical office environment, the long-life filter must be cleaned
every 2,500 (PL(H))/100 (PC(H), PK(H)) operating hours.
Reset the FILTER indicator
1 Press the FILTER button twice after cleaning.
s When you press the FILTER button twice, the “FILTER” indicator A will be
turned off and reset.
s The FILTER indicator provides you with a guideline for the necessity of
filter cleaning based on total operating hours in typical indoor air condi­tions. Depending on different operating environments, more or less fre­quent cleaning may be necessary.
Not available for wireless remote controller.
3. Care and cleaning
Page 7
7
PLH18AK PLH24AK PLH30AK PLH36AK PLH42AK
18,000 24,000 30,000 35,400 42,000 19,000 [24,500/25,500] 26,000 [31,500/32,500] 33,000 [39,500/41,200] 38,000 [45,900/47,600] 44,300 [52,200/53,900] 11,000 [16,500/17,500] 16,500 [22,000/23,000] 18,500 [25,000/26,700] 23,000 [30,900/32,600] 26,800 [34,700/36,400]
1.75 2.57 3.17 3.63 3.98
1.59 [3.19/3.49] 2.51 [4.11/4.41] 3.04 [4.94/5.44] 3.45 [5.75/6.25] 3.82 [6.12/6.62]
1.32 [2.92/3.22] 2.15 [3.75/4.05] 2.55 [4.45/4.95] 2.93 [5.23/5.73] 3.24 [5.54/6.04]
10.5 10.3 10.4 10.0 10.7
7.2 7.0 6.9 7.1 7.0
PLH18AK PLH24AK PLH30AK PLH36AK PLH42AK
Munsell 0.7Y 8.59/0.97
208/230, 1, 60 20 25 15 17
0.7 1.2 1.4
7.7/8.3 [1.6/1.9] 9.1/10.4 [1.9/2.4] 11.1/12.2 [2.3/2.8] 530-710 710-990 780-1060 490-670 670-950 740-1020
33-1/16 33-1/16
10-3/16 11-3/4
37-3/8 37-3/8 1-3/16
57 71 75
11
PUH18EK PUH24EK PUH30EK PUH36EK PUH42EK7
Munsell 5Y 7/1
208/230, 1, 60 20 30 40 16 20 22 28
0.75 0.65+0.65 0.75+0.75 0.8+0.8
RH247NAB NH33NBD NH41NAD NH47NAD ZR42K3-PFV
12.0 11.5 14.0 17.5 20.4 37 54 73 87 109
0.11/0.17 (23/28) 0.16/0.17 (33/39) Capillary tube
Reverse cycle 34-1/4 38-3/16 11-5/8 13-9/16
33-1/2 49-9/16
131 202 245 246 246
With grille
Indoor unit-remote controller DC12V, Indoor unit- outdoor unit DC12V
Cooling *1 BTU/h
Capacity Heating *1,*3 BTU/h
Heating *2,*3 BTU/h Cooling *1 kW Heating *1,*3 kW
Heating *2,*3 kW SEER HSPF
INDOOR UNIT MODELS
External finish Power supply V, Phase, Hz Max. fuse size (time delay) A Min. ampacity A Fan motor F. L. A. Auxiliary heater A (kW) Airflow Dry CFM Lo-Hi Wet CFM
Win Dimensions D in
Hin
Win Dimensions
Din (GRILLE)
Hin Weight lbs Weight (GRILLE) lbs
OUTDOOR UNIT MODELS
External finish Power supply V, Phase, Hz Max. fuse size (time delay) A Min. ampacity A Fan motor F. L. A.
Models Compressor
R. L. A.
L. R. A. Crankcase heater A (W) Refrigerant control Defrost method
Win
Dimensions D in
Hin
Weight lbs
REMOTE CONTROLLER
Control voltage (by built-in transformer)
Item
Models
Power consumption
NOTES: *1 Rating conditions (cooling) – indoor: 80°F DB. 67°F WB outdoor: 95°F DB. 75°F WB
(heating) – indoor: 70°F DB. 60°F WB outdoor: 47°F DB. 43°F WB *2 Rating conditions (heating) – indoor: 70°F DB. 60°F WB outdoor: 17°F DB. 15°F WB *3 Heating capacity and power consumption in [ ] include auxiliary electric heater operation at 208/230V.
Units should be installed by licensed electric contractor accordingly to local code requirement. * Specifications subject to change without notice.
5. Specifications
Page 8
8
PL12AK PL18AK PL24AK PL30AK PL36AK PL42AK
12,500 18,400 24,000 31,000 36,500 42,500
1.26 1.85 2.65 3.17 3.64 4.08
10.1 10.2 10.0 10.6 10.5 10.8
PL12AK PL18AK PL24AK PL30AK PL36AK PL42AK
Galvanized sheets with gray heat insulation
Munsell 0.7Y 8.59/0.97
115, 1, 60
15
2.0 3.0
1.2 2.6 420-560 530-710 710-990 780-1060 390-530 490-670 670-950 740-1020
33-1/16 33-1/16
10-3/16 11-3/4
37-3/8 37-3/8 1-3/16
49 53 66 71
11
PU12EK PU18EK PU24EK PU30EK PU36EK PU42EK7
Munsell 5Y 7/1
208/230, 1, 60 15 20 30 40 11 16 20 22 28
0.65 0.75 0.65+0.65 0.75+0.75 0.8+0.8
RH167NAB RH247NAB NH33NBD NH41NAD NH47NAD ZR42K3-PFV
8.9 12.0 11.5 14.0 17.5 20.4 29 37 54 73 87 109
0.11/0.12 (23/28) 0.16/0.17 (33/39) Capillary tube
34-1/4 38-3/16 11-5/8 13-9/16
25-9/16 33-1/2 49-9/16
105 154 207 220 220
With grille
Indoor unit-remote controller DC12V, Indoor unit- outdoor unit DC12V
Cooling capacity *1 BTU/h Power consumption *1 kW SEER
INDOOR UNIT MODELS
External finish External finish (GRILLE) Power supply V, Phase, Hz Max. fuse size (time delay) A Min. ampacity A Fan motor F. L. A. Airflow Dry CFM Lo-Hi Wet CFM
Win
Dimensions D in
Hin Win
Dimensions
Din
(GRILLE)
Hin Weight lbs Weight (GRILLE) lbs
OUTDOOR UNIT MODELS
External finish Power supply V, Phase, Hz Max. fuse size (time delay) A Min. ampacity A Fan motor F. L. A.
Model Compressor
R. L. A.
L. R. A. Crankcase heater A (W) Refrigerant control
Win
Dimensions D in
Hin
Weight lbs
REMOTE CONTROLLER
Control voltage (by built-in transformer)
Item
Models
NOTES: *1 Rating conditions (cooling) – indoor: 80°F DB. 67°F WB outdoor: 95°F DB. 75°F WB
Units should be installed by licensed electric contractor accordingly to local code requirement. * Specifications subject to change without notice.
5. Specifications
Page 9
9
PCH24GK PCH30GK PCH36GK PCH42GK
24,000 30,000 35,400 42,000 27,000 [34,000/35,500] 33,000 [40,500/42,500] 38,000 [45,500/47,500] 45,000 [52,500/54,500] 14,800 [21,800/23,300] 20,000 [27,500/29,500] 21,000 [28,500/30,500] 23,800 [31,300/33,200]
2.51 3.23 3.60 4.10
2.46 [4.49/4.94] 3.00 [5.25/5.76] 3.32 [5.57/6.08] 3.76 [6.03/6.52]
1.95 [3.98/4.43] 2.58 [4.83/5.34] 2.63 [4.88/5.39] 3.00 [5.25/5.76]
10.3 10.0 10.3 10.3
6.8 7.0 7.0 7.2
PCH24GK PCH30GK PCH36GK PCH42GK
Munsell 0.7Y 8.59 / 0.97
208 / 230, 1, 60 20 25 15 17
1.1 1.3
9.8/10.8 [2.0/2.5] 10.8/12.0 [2.2/2.8] 710-880 990-1,240 640-810 880-1,130
51-9/16 63-3/4
26-3/4 10-5/8
87 101 106
PUH24EK PUH30EK PUH36EK PUH42EK7
Munsell 5Y 7/1
208/230, 1, 60 20 30 40 16 20 22 28
0.65+0.65 0.75+0.75 0.8+0.8 NH33NBD NH41NAD NH47NAD ZR42K3-PFV
11.5 14.0 17.5 20.4 54 73 87 109
0.16/0.17 (33/39) Capillary tube Reverse cycle
34-1/4 38-3/16 11-5/8 13-9/16
49-9/16
202 245 246 246
With indoor unit
Indoor unit-remote controller DC12V, Indoor unit- outdoor unit DC12V
Cooling *1 BTU/h
Capacity Heating *1,*3 BTU/h
Heating *2,*3 BTU/h Cooling *1 kW Heating *1,*3 kW
Heating *2,*3 kW SEER HSPF
INDOOR UNIT MODELS
External finish Power supply V, Phase, Hz Max. fuse size (time delay) A Min. ampacity A Fan motor F. L. A. Auxiliary heater A (kW) Airflow Dry CFM Lo-Hi Wet CFM
Win Dimensions D in
Hin Weight lbs
OUTDOOR UNIT MODELS
External finish Power supply V, Phase, Hz Max. fuse size (time delay) A Min. ampacity A Fan motor F. L. A.
Models Compressor
R. L. A.
L. R. A. Crankcase heater A (W) Refrigerant control Defrost method
Win
Dimensions D in
Hin
Weight lbs
REMOTE CONTROLLER
Control voltage (by built-in transformer)
Item
Models
Power consumption
NOTES: *1 Rating conditions (cooling) – indoor: 80°F DB. 67°F WB outdoor: 95°F DB. 75°F WB
(heating) – indoor: 70°F DB. 60°F WB outdoor: 47°F DB. 43°F WB *2 Rating conditions (heating) – indoor: 70°F DB. 60°F WB outdoor: 17°F DB. 15°F WB *3 Heating capacity and power consumption in [ ] include auxiliary electric heater operation at 208/230V.
Units should be installed by licensed electric contractor accordingly to local code requirement. * Specifications subject to change without notice.
5. Specifications
Page 10
10
PC24GK PC30GK PC36GK PC42GK
25,000 31,000 36,500 42,500
2.61 3.18 3.62 4.10
10.4 10.0 10.3 10.8
PC24GK PC30GK PC36GK PC42GK
Munsell 0.7Y 8.59 / 0.97
115, 1, 60
15
2.0 3.0
1.9 2.4 710-880 990-1,240 640-810 880-1,130
51-9/16 63-3/4
26-3/4 10-5/8
82 95 99
PU24EK PU30EK PU36EK PU42EK7
Munsell 5Y 7/1
208/230, 1, 60 20 30 40 16 20 22 28
0.65+0.65 0.75+0.75 0.8+0.8
NH33NBD NH41NAD NH47NAD ZR42K3-PFV
11.5 14.0 17.5 20.4 54 73 87 109
0.16/0.17 (33/39) Capillary tube
34-1/4 38-3/16 11-5/8 13-9/16
49-9/16
207 208 220 220
With indoor unit
Indoor unit-remote controller DC12V, Indoor unit- outdoor unit DC12V
Cooling capacity *1 BTU/h Power consumption *1 kW SEER
INDOOR UNIT MODELS
External finish Power supply V, Phase, Hz Max. fuse size (time delay) A Min. ampacity A Fan motor F. L. A. Airflow Dry CFM Lo-Hi Wet CFM
Win
Dimensions D in
Hin
Weight lbs
OUTDOOR UNIT MODELS
External finish Power supply V, Phase, Hz Max. fuse size (time delay) A Min. ampacity A Fan motor F. L. A.
Model
Compressor
R. L. A.
L. R. A. Crankcase heater A (W) Refrigerant control
Win
Dimensions D in
Hin
Weight lbs
REMOTE CONTROLLER
Control voltage (by built-in transformer)
Item
Models
NOTES: *1 Rating conditions (cooling) – indoor: 80°F DB. 67°F WB outdoor: 95°F DB. 75°F WB
Units should be installed by licensed electric contractor accordingly to local code requirement. * Specifications subject to change without notice.
5. Specifications
Page 11
11
5. Specifications
Cooling *1 BTU/h
Capacity Heating *1,*3 BTU/h
Heating *2,*3 BTU/h Cooling *1 kW Heating *1,*3 kW
Heating *2,*3 kW SEER HSPF
INDOOR UNIT MODELS
External finish Power supply V, Phase, Hz Max. fuse size (time delay) A Min. ampacity A Fan motor F. L. A. Auxiliary heater A (kW) Airflow Dry CFM Lo-Hi Wet CFM
Win Dimensions D in
Hin Weight lbs
OUTDOOR UNIT MODELS
External finish Power supply V, Phase, Hz Max. fuse size (time delay) A Min. ampacity A Fan motor F. L. A.
Models Compressor
R. L. A.
L. R. A. Crankcase heater A (W) Refrigerant control Defrost method
Win
Dimensions D in
Hin
Weight lbs
REMOTE CONTROLLER
Control voltage (by built-in transformer)
Item
Models
Powe r consumption
NOTES: *1 Rating conditions (cooling) – indoor: 80°F DB. 67°F WB outdoor: 95°F DB. 75°F WB
(heating) – indoor: 70°F DB. 60°F WB outdoor: 47°F DB. 43°F WB *2 Rating conditions (heating) – indoor: 70°F DB. 60°F WB outdoor: 17°F DB. 15°F WB *3 Heating capacity and power consumption in [ ] include auxiliary electric heater operation at 208/230V.
Units should be installed by licensed electric contractor accordingly to local code requirement. * Specifications subject to change without notice.
PKH18FK3/PKH18FL PKH24FK3/PKH24FL PKH30FK3/PKH30FL PKH36FK3/PKH36FL
18,000 24,000 30,000 34,200 18,600 [24,100/25,100] 25,000 [30,500/31,500] 33,000 [39,100/40,500] 38,000 [44,100/45,500] 10,700 [16,200/17,200] 14,700 [20,200/21,200] 19,000 [25,100/26,500] 19,600 [25,700/27,100]
1.79 2.36 3.12 3.44
1.56 [3.16/3.46] 2.37 [3.97/4.27] 3.02 [4.82/5.22] 3.54 [5.34/5.74]
1.34 [2.94/3.24] 1.92 [3.52/3.82] 2.48 [4.28/4.68] 2.65 [4.45/4.85]
11.1 10.2 10.6 10.5
7.2 6.8 7.1 6.9
PKH18FK3/PKH18FL PKH24FK3/PKH24FL PKH30FK3/PKH30FL PKH36FK3/PKH36FL
Munsell 3.4Y 7.7/0.8
208/230, 1, 60
15
12 13
0.5 0.6
7.6/8.4 [1.6/1.9] 8.7/9.6 [1.8/2.2] 710-530 990-780 640-480 890-700
55-1/8 66-5/32
9-1/4
13-3/8
57 66
PKH18FK3 / PLH18FL PKH24FK3 / PKH24FL PKH30FK3 / PKH30FL PKH36FK3 / PKH36FL
Munsell 5Y 7/1
208/230, 1, 60 20 30 16 20 22
0.75 0.65+0.65 0.75+0.75
RH247NAB NH33NBD NH41NAD NH47NAD
12.0 11.5 14.0 17.5 37 54 73 87
0.11/0.12 (23/28) 0.16/0.17 (33/39) Capillary tube Reverse cycle
34-1/4 38-3/16 11-5/8 13-9/16
33-1/2 49-9/16
131 202 245 246
With indoor unit
Indoor unit-remote controller DC12V, Indoor unit- outdoor unit DC12V
Page 12
12
Printed in Japan
BG79P948H04
HEAD OFFICE: MITSUBISHI DENKI BLDG., 2-2-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
5. Specifications
Cooling capacity *1 BTU/h Power consumption *1 kW SEER
INDOOR UNIT MODELS
External finish Power supply V, Phase, Hz Max. fuse size (time delay) A Min. ampacity A Fan motor F. L. A. Airflow Dry CFM Lo-Hi Wet CFM
Win
Dimensions D in
Hin
Weight lbs
OUTDOOR UNIT MODELS
External finish Power supply V, Phase, Hz Max. fuse size (time delay) A Min. ampacity A Fan motor F. L. A.
Model
Compressor
R. L. A.
L. R. A. Crankcase heater A (W) Refrigerant control
Win
Dimensions D in
Hin
Weight lbs
REMOTE CONTROLLER
Control voltage (by built-in transformer)
Item
Models
NOTES: *1 Rating conditions (cooling) – indoor: 80°F DB. 67°F WB outdoor: 95°F DB. 75°F WB
Units should be installed by licensed electric contractor accordingly to local code requirement. * Specifications subject to change without notice.
PK12FK3 PK18FK3/PK18FL3 PK24FK3/PK24FL3 PK30FK3/PK30FL3 PK36FK3/PK36FL3
12,500 18,500 24,000 30,000 34,200
1.21 1.75 2.34 3.06 3.47
11.5 11.3 10.6 10.7 10.2
PK12FK3 PK18FK3/PK18FL3 PK24FK3/PK24FL3 PK30FK3/PK30FL3 PK36FK3/PK36FL3
Munsell 3.4Y 7.7/0.8
115, 1, 60
15
12
0.7 1.0 490-350 710-530 990-780 440-320 640-480 890-700
49-7/32 55-1/8 66-5/32
7-7/8 9-1/4
11-13/16 13-3/8
37 53 62
PU12EK PU18EK PU24EK PU30EK PU36EK
Munsell 5Y 7/1
208/230, 1, 60 15 20 30 11 16 20 22
0.65 0.75 0.65+0.65 0.75+0.75
RH167NAB RH247NAB NH33NBD NH41NAD NH47NAD
8.9 12.0 11.5 14.0 17.5 29 37 54 73 87
0.11/0.12 (23/28) 0.16/0.17 (33/39) Capillary tube
34-1/4 38-3/16 11-5/8 13-9/16
25-9/16 33-1/2 49-9/16
105 154 207 208 220
With indoor unit
Indoor unit-remote controller DC12V, Indoor unit- outdoor unit DC12V
Loading...