SUBMITTAL DATA: MXZ-2C20NA2
ON MULTI-ZONE INVERTER HEAT-PUMP SYSTEM
1.5-T
Job Name:
System Reference: Date:
GENERAL FEATURES
Variable speed INVERTER-driven compressor
•
• Energy Star® certified (non-ducted)
• M-NET connection through outdoor unit
• Quiet outdoor unit operation as low as 50 dB(A)
• New Intelligent Power Module (IPM) for reduced power loss
• Selectable thermal lockout/restart function
• Optional base pan heater
• High pressure switch for additional protection
• Thermal differential of +/-1° F from setpoint
Specifications are subject to change without notice. Copyright © 2017 Mitsubishi Electric US, Inc.

Model number
SPECIFICATIONS: MXZ-2C20NA2
Outdoor unit MXZ-2C20NA2
Indoor unit type Non-
Ducted
Maximum Capacity Btu/h 20,000
Rated Capacity Btu/h 18,000 19,000 20,000
Mix Ducted
Cooling*1
Heating at 47° F*2
Heating at 17° F *3
Heating at 5° F *4
Minimum Capacity Btu/h 5,700
Maximum Power Input W 2,245
Rated Power Input W 1,417 1,709 2,000
Power Factor % 98.7 99.3 99.9
Maximum Capacity Btu/h 25,000
Rated Capacity Btu/h 22,000
Minimum Capacity Btu/h 7,400
Maximum Power Input W 2,455
Rated Power Input W 1,641 1,706 1,771
Power Factor % 96.2 97.9 99.6
Maximum Capacity Btu/h 15,500 15,000 14,500
Rated Capacity Btu/h 12,500 13,000 13,500
Maximum Power Input W 1,750 1,780 1,810
Rated Power Input W 1,300 1,325 1,350
Maximum Capacity Btu/h 11,100 11,000 10,900
Maximum Power Input W 1,600 1,625 1,650
Efficiency
Electrical
Outdoor unit
SEER 20.00 18.00 16.00
EER *1 12.70 11.35 10.00
HSPF (IV) 10.00 9.65 9.30
COP at 47° F *2 3.93 3.78 3.64
COP at 17° F *3 2.82 2.87 2.93
ENERGY STAR® Certified YES NO NO
Voltage, Phase, Frequency 208 / 230V, 1-phase, 60 Hz
Guaranteed Voltage Range V AC 187 - 253
Voltage: Indoor - Outdoor, S1-S2 V AC 208V / 230
Voltage: Indoor - Outdoor, S2-S3 V DC 12-24
Voltage: Indoor - Remote controller V DC 24
Recommended Fuse/Breaker Size A 20
Recommended Wire Size
(Indoor - Outdoor)
MCA A 17.2
AWG AWG14
Specifications are subject to change without notice. Copyright © 2017 Mitsubishi Electric US, Inc.

Model number
SPECIFICATIONS: MXZ-2C20NA2
Outdoor unit MXZ-2C20NA2
Indoor unit type Non-
Ducted
Fan Motor Full Load Amperage A 1.77
Fan Motor Output W 64
Airflow Rate CFM 1,342 / 1,458
Refrigerant Control Liner Expansion Valve
Defrost Method Reverse Cycle
Heat Exchanger Type Plate fin coil
Sound Pressure Level, Cooling*1 dB(A) 50
Sound Pressure Level, Heating*2 dB(A) 54
Compressor Type Twin Rotary type
Compressor Model SNB140FQUH2T
Compressor Motor Output kW 1.5
Mix Ducted
Outdoor unit operating
temperature range
Compressor Rated Load Amps A 10.7
Compressor Locked Rotor Amps A 15.5
Compressor Oil Type // Charge oz. NEO22 / 20.3
External Finish Color Munsell 3.0Y 7.8/1.1
Base Pan Heater Optional
W: In. [mm] 33-1/16 [840]
Unit Dimensions
Package Dimensions
Unit Weight Lbs.[kg] 126 [57]
Package Weight Lbs.[kg] 147 [67]
Cooling Intake Air Temp
(Maximum / Minimum)
Heating Intake Air Temp
(Maximum / Minimum)
D: In. [mm] 13 [330]
H: In. [mm] 27-15/16 [710]
W: In. [mm] 40 [1,010]
D: In. [mm] 18-1/2 [470]
H: In. [mm] 33-1/2 [850]
°F 14 to 115
°F 5 to 75
Thermal Lock-out / Re-start Temperatures °F Cooling: 10.4 / 14 Heating: 1.5 / 5
Refrigerant
Indoor unit connection
Specifications are subject to change without notice. Copyright © 2017 Mitsubishi Electric US, Inc.
Type R410A
Charge Lbs., Oz. 3, 15
Maximum Number of Connected IDU 2
Minimum Number of Connected IDU 2
Maximum connected capacity Btu/h 24,000

Model number
SPECIFICATIONS: MXZ-2C20NA2
Outdoor unit MXZ-2C20NA2
Indoor unit type Non-
Ducted
Minimum connected capacity Btu/h 12,000
Gas Pipe Size O.D. (Flared) In.[mm] 3/8 [9.52]
Liquid Pipe Size O.D. (Flared) In.[mm] 1/4 [6.35]
Total Piping Length Ft. [m] 164 [50]
Mix Ducted
Maximum Height Difference,
Piping
AHRI Rated
Conditions (Rated
data is determined
at a fixed
compressor
speed)
Conditions *4 Heating at 5°F (Indoor // Outdoor) °F 70°F DB, 60°F WB // -4°F DB, -5°F WB
For reference to connected capacity charts, please refer MXZ-2C20NA2-U1 Operational Performance.
Notes:
ODU above IDU
Maximum Height Difference,
ODU below IDU
Farthest Piping Length from ODU to IDU Ft. [m] 82 [25]
Maximum Number of Bends 50
*1 Cooling (Indoor // Outdoor) °F 80°F DB, 67°F WB // 95°F DB, 75°F WB
*2 Heating at 47°F (Indoor // Outdoor) °F 70°F DB, 60°F WB // 47°F DB, 43°F WB
*3 Heating at 17°F (Indoor // Outdoor) °F 70°F DB, 60°F WB // 17°F DB, 15°F WB
Ft. [m] 33 [10]
Ft. [m] 49 [15]
Specifications are subject to change without notice. Copyright © 2017 Mitsubishi Electric US, Inc.

ACCESSORIES: MXZ-2C20NA2
Unit φ9.52 → Pipeφ15.88 □ PAC-SG76RJ-E
Unit φ6.35 → Pipeφ9.52 □ PAC-493PI
Joint Pipe
Unit φ9.52 → Pipeφ12.7 □ MAC-A454JP-E
Unit φ12.7 → Pipeφ9.52 □ MAC-A455JP-E
Unit φ12.7 → Pipeφ15.88 □ MAC-A456JP-E
Air Discharge Guide □ MAC-856SG
Base Pan Heater □ PAC-646BH-E
Control Cable □ CW162S
3-pole Disconnect □ TAZ-MS303
M-NET Adapter □ PAC-IF01MNT-E
Wall Mounting Bracket (Powder-coated Steel) □ QSWB2000M-1
Wall Mounting Bracket (316 Series Stainless Steel) □ QSWBSS
Outdoor Unit Mounting Pad 24" x 42" x 3" □ ULTRILITE2
MiniSplit Mounting Stand-Dual Fan models - 12" □ QSMS1202M
MiniSplit Mounting Stand-Dual Fan models - 18" □ QSMS1802M
MiniSplit Mounting Stand-Dual Fan models - 24" □ QSMS2402M
1/4 x 1/2 x 15' / 1/2" Lineset (Twin-Tube Insulation) □ MLS141212T-15
1/4 x 1/2 x 30' / 1/2" Lineset (Twin-Tube Insulation) □ MLS141212T-30
1/4 x 1/2 x 50' / 1/2" Lineset (Twin-Tube Insulation) □ MLS141212T-50
1/4 x 1/2 x 65' / 1/2" Lineset (Twin-Tube Insulation) □ MLS141212T-65
1/4 x 1/2 x 100' / 1/2" Lineset (Twin-Tube Insulation) □ MLS141212T-100
Diamondback
Linesets
*1
3/8 x 5/8 x 10' / 1/2" Lineset (Twin-Tube Insulation) □ MPLS385812T-10
3/8 x 5/8 x 15' / 1/2" Lineset (Twin-Tube Insulation) □ MPLS385812T-15
3/8 x 5/8 x 30' / 1/2" Lineset (Twin-Tube Insulation) □ MPLS385812T-30
3/8 x 5/8 x 50' / 1/2" Lineset (Twin-Tube Insulation) □ MPLS385812T-50
3/8 x 5/8 x 65' / 1/2" Lineset (Twin-Tube Insulation) □ MPLS385812T-65
3/8 x 5/8 x 100' / 1/2" Lineset (Twin-Tube Insulation) □ MPLS385812T-100
*1
Linesets are indoor unit specific and will be listed in the IDU information - the Joint Pipe adaptors are used in this application
Specifications are subject to change without notice. Copyright © 2017 Mitsubishi Electric US, Inc.

Connecting
wire hole
1-25/32”
18-1/8
29/32”
3-5/16”
5-5/16”
11-25/32”
14-3/16”
27-15/16”
9-7/16”
7-7/8”
1-3/16”33-1/16”
Unit A
GAS
GAS
LIQ
LIQ
LIQ 1/4”(ø6.35)FLARE
GAS 3/8”(ø9.52)FLARE
Unit B
Connecting
wire hole
1-1/32” 13”
2-19/32”
1/2”
(Bolt Pitch)
(Foundation Bolt M8)
4-(13/32”×13/16”) Oval Hole
3-ø(1-5/16”) Drain hole
Air
Inlet
Air Inlet
Air
Outlet
14-3/16”
15/32” 23/32”
21/32”
1-11/32”
2-9/16” 12-3/8”8-5/32”
6-21/32” 6-23/32”19-11/16”
11/16”11/16”
15-19/32”
Handle
Unit: inch (mm)
OUTLINES AND DIMENSIONS
5
Lock nut
Connector
Grounding terminal
Conduit
cover
DIMENSIONS: MXZ-2C20NA2
1340 Satellite Boulevard, Suwanee, GA 30024
oll Free: 800-433-4822 www.mehvac.com
T
FORM# MXZ-2C20NA2 - 201706
Specifications are subject to change without notice. Copyright © 2017 Mitsubishi Electric US, Inc.