14. PARTS LIST······················································32
15. OPTIONAL PARTS ···········································34
This manual describes technical data of outdoor unit.
For the indoor unit refer to the service manuals No. OB229, OB227 REVISED EDITION-B, OB252 REVISED EDITION-A,OC280 REVISED EDITION-A,OC281 REVISED EDITION-A and OC165 of corresponding models.
Page 2
1
TECHNICAL CHANGES
MXZ-18RV -➔ MXZ-18TV -
1. The combination pattern of indoor unit has increased.
2. Outside dimension of the outdoor unit changed.
3. Ball valve has changed to stop valve.
4. Accumulator has been removed.
5. Hight pressure switch has been removed.
6. Compressor has changed.
7. Refrigerant filling capacity has changed. (1.3kg ➝ 1.55kg)
MXZ-18TV -➔ MXZ-18TV -
1.Combinations of the connectable indoor units have increased.
2. FUSE(F912) and Varistor(NR63) on Noise filter P.C. board has changed.
3. Accordance with the change, the board of E2 can be used for E1.
4. The board of E1 can not be used for E2.
E1E1
E2E1
2
PART NAMES AND FUNCTIONS
OUTDOOR UNIT
MXZ-18TVMXZ-18TV-
E1
E2
Air outlet
Air inlet
(back and side)
Model indication
2
Page 3
3
❈There is no combination other than this table.
MXZ-18TV-
E1
OUTDOOR UNIT
Combination of the
connectable indoor units
07+09
07+12
07+SEH-1.6
09+09
09+12
09+SEH-1.6
12+12
MXZ-18TV-
E2
07+09
07+SLH-1
07+12
07+SEH-1.6
07+SLH-1.6
09+0.9
09+SLH-1
09+12
09+SEH-1.6
09+SLH-1.6
SLH-1+SLH-1
SLH-1+12
SLH-1+SEH-1.6
SLH-1+SLH-1.6
12+12
12+SLH-1.6
SLH-1.6+SLH-1.6
07
09
12
07+09
07+12
09+09
09+12
12+12
90
90
90
90
90
90
90
90
3.88
4.17
6.22
8.79
8.85
8.88
9.00
9.07
2.3
(0.9-2.8)
2.5
(0.9-3.0)
3.4
(0.9-3.8)
4.8
(1.49-5.25)
5.0
(1.51-5.45)
5.0
(1.51-5.45)
5.2
(1.53-5.60)
5.3
(1.55-5.70)
0.850
(0.225-1.055)
0.865
(0.225-1.125)
1.29
(0.220-1.550)
1.82
(0.370-2.11)
1.835
(0.365-2.125)
1.840
(0.370-2.130)
1.865
(0.365-2.145)
1.88
(0.370-2.190)
–
–
–
2.5
2.98
2.5
3.0
2.65
2.3
2.5
3.4
2.3
2.02
2.5
2.2
2.65
Indoor units
combination
Unit AUnit B
Cooling capacity (kW)
Total
Outdoor unit
power consumption
(kW)
Current
(A)
Power
factor
(%)
230V
NOTE: Electrical data is for outdoor unit only.
MXZ-18TV -
E1 , MXZ-18TV - E2
NOTE: Electrical data is for outdoor unit only.
07
09
12
07+09
07+12
09+09
09+12
12+12
90
90
90
90
90
90
90
90
4.85
5.23
6.95
9.27
9.14
9.17
8.81
8.64
3.3
(0.9-4.0)
3.6
(0.9-4.5)
4.0
(0.9-4.7)
6.2
(1.53-6.70)
6.5
(1.55-7.00)
6.5
(1.55-7.0)
6.55
(1.56-7.1)
6.6
(1.58-7.2)
1.005
(0.225-1.115)
1.085
(0.225-1.195)
1.440
(0.220-1.490)
1.92
(0.300-2.030)
1.895
(0.295-2.005)
1.900
(0.300-2.010)
1.825
(0.295-1.925)
1.790
(0.290-1.840)
–
–
–
3.23
3.88
3.25
3.77
3.30
3.3
3.6
4.0
2.97
2.62
3.25
2.78
3.30
Indoor units
combination
Unit AUnit B
Heating capacity (kW)
Total
Outdoor unit
power consumption
(kW)
Current
(A)
Power
factor
(%)
230V
INDOOR / OUTDOOR CORRESPONDENCE TABLE
4
INDOOR UNITS COMBINATION
NOTE: SLH-1AR is equivalent to class 9 (9000BTU).
SEH-1.6AR,SLH-1.6AR is equivalent to class 12 (12000BTU).
3
Page 4
5
Outdoor model
Indoor units number
Indoor units total capacity (Connectable)
indoor units total capacity (Simultaneous operation)
Piping total length
Connecting pipe length
Height difference (Indoor ~ Outdoor)
Height difference (Indoor ~ Indoor)
Function
Capacity
Dehumidification
Outdoor air flow
Power outlet
Running current
Power input
Auxiliary heater
Crankcase heater
Power factor
Starting current
Compressor motor current
Fan motor current
Model
Output
Winding
resistance(at20:)
Model
Winding
resistance(at20:)
Dimensions WOHOD
Weight
Sound level (Hi)
Fan speed (Hi)
Fan speed regulator
Refrigerant filling
capacity(R-22)
Refrigerating oil (Model)
Thermistor RT61
Thermistor RT62
Thermistor RT63
Thermistor RT65,66
Thermistor RT67
m
m
m
m
kW
R/h
K /h
A
A
W
A(kW)
W
%
A
A
A
W
"
"
mm
kg
dB
rpm
kg
cc
k"
k"
k"
k"
k"
Compressor
Electrical
data
Fan
motor
Special
remarks
CapacitySystem
Coefficient of performance(C.O.P)
Outdoor unit power supply
MXZ-18TV -
E1
,
MXZ-18TV -
E2
Single phase
230V,50Hz
2
Total model name 24
Total model name 24
Max. 30 (chargeless 20)
Max. 20
10
10
1,860
20
—
—
90.0
9.08
0.38
SHV-130FEA (ROTARY)
1,400
U-V 0.45
V-W 0.45 W-U 0.45
RA6V35-AA
WHT-BLK 236.2 BLK-YLW 48.1
BLK-RED 224.1
800(+69)o600o300
46
630
2
1.55
350 (MS-56)
13.4 (at 100:)
10.0 (at 25:)
10.0 (at 25:)
10.0 (at 25:)
17.0 (at 50:)
Cooling
5.3 (1.55~5.7)
—
9.08
1,880 (370~2,190)
8.70
2.82
48
Heating
6.6 (1.58~7.2)
—
8.64
1,790 (290~1,840)
8.26
3.69
49
SPECIFICATION
NOTE: Test conditions are based on ISO 5151 (Refrigerant piping length (one way) :5m
✽1 Electrical data is for only outdoor unit.
TEST CONDITIONS COOLING INDOOR DB27.0°C WB19.0°C
HEATING INDOOR DB20.0°C
OUTDOOR DB35.0°C WB24.0°C
OUTDOOR DB 7.0°C WB 6.0°C
4
Page 5
NOISE CRITERIA CURVES6
90
80
70
60
50
40
30
20
10
631252505001000200040008000
APPROXIMATE
TERESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, 0dB = 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
Test conditions.
Cooling :DB 35:WB 24:
Heating :DB 7:WB 6:
Cooling
NOTCH
Heating
48
SPL(dB(A))
49
LINE
MXZ-18TV -
E1
MXZ-18TV -
E2
5
Page 6
7
OUTLINES AND DIMENSIONS
OUTDOOR UNIT
MXZ-18TV MXZ-18TV -
E1
E2
Drainage hole {33
23
Bolt pitch for installation
43.6
152
Air in
45.4
16
Handle
400
347.5
Air in
Air out
113
500
800
Drainage
hole {33
155
Unit: mm
REQUIRED SPACE
Even if the right / left sides or
back side are vacant, the top
has to be at least 100mm
unobstructed.
100mm or more
34
17300
WA
200mm or more
WB
330
However, either the
left / right sides or
back side should
34
40
69
17
Handle
be unobstructed.
WA In case of poorly-ventilated place, the front
or the back has to be at least 200mm
unobstructed.
POWER-FACTOR CAPACITOR
SMOOTHING CAPACITOR
FAN MOTOR CAPACITOR
CURRENT TRANSFORMER
CURRENT TRANSFORMER
DIODE MODULE
FUSE(20A)
FUSE(1A)
FUSE(1A)
POWER TRANSISTOR MODULE
REACTOR
R64A,R64B
R61,R62
LEV A
LEV B
21S4
MC
MF61
RT61
RT62
RT63
RT65
RESISTOR
RESISTOR
EXPANSION VALVE A,COIL
EXPANSION VALVE B,COIL
REVERSING VALVE SOLENOID COIL
COMPRESSOR
FAN MOTOR
DISCHARGE TEMP. THERMISTOR
DEFROST TEMP. THERMISTOR
EVAPORATOR TEMP. THERMISTOR
GAS PIPE TEMP. A THERMISTOR
RT66
RT67
SSR61
T801
TB1
TB2
X61
X62
X64
CN61
F912
GAS PIPE TEMP. B THERMISTOR
FIN TEMP. THERMISTOR
SOLENOID COIL RELAY
TRANSFORMER
TERMINAL BLOCK
TERMINAL BLOCK
FAN MOTOR RELAY
FAN MOTOR RELAY
RELAY
CONNECTOR
FUSE(3.15A)
SG79J657H01
R64A
F912(3.15A)
R61
IPM
FUSE(1A)
T801
CT62
WVU
TAB61
TAB65
C65
SSR61
CN664CN663CN661
66
MF61
CN912CN911
21S4
CN61
R62
TAB62
V
W
U
MC
BLK
WHT
RED RED
WHT
BLK
PE
F911(1A)
BLU
ORN
YLW
TB2
BLK
BREAKER
GRN/YLW
CIRCUIT
POWER
SUPPLY
~/N
230V~
50Hz
TB1
TO INDOOR
UNIT No.B
CONNECTING
12V
TO INDOOR
UNIT No.A
CONNECTING
12V
N
L
N
3
N
3
GROUND
BLK
BLU
BLK
BLU
GRN
RED
X62
X61
X64
R64
CT61
TAB2
TAB1
LDE
CN601CN602
CN851
TAB4
CN901
L
DS62
DS61
C61C62
7
ORN
BLU
RED
YLW
YLW
RED
4
FUSE(20A)
ELECTRONIC CONTROL
P.C. BOARD
2121654321
RT65RT66RT61RT67
LEV ALEV B
CN772CN771
43
RT62RT63
6543213214
123
3214567
1234567
123123
NOISE FILTER
P.C.BOARD
–
++
–
–
+
–
+
NAMESYMBOLNAMESYMBOL
1.About the indoor side electric wiring refer to the indoor unit electric wiring diagram for servicing.
POWER-FACTOR CAPACITOR
SMOOTHING CAPACITOR
FAN MOTOR CAPACITOR
CURRENT TRANSFORMER
CURRENT TRANSFORMER
DIODE MODULE
FUSE(20A)
FUSE(1A)
FUSE(1A)
POWER TRANSISTOR MODULE
REACTOR
R64
R61,R62
LEV A
LEV B
21S4
MC
MF61
RT61
RT62
RT63
RT65
RESISTOR
RESISTOR
EXPANSION VALVE A,COIL
EXPANSION VALVE B,COIL
REVERSING VALVE SOLENOID COIL
COMPRESSOR
FAN MOTOR
DISCHARGE TEMP. THERMISTOR
DEFROST TEMP. THERMISTOR
EVAPORATOR TEMP. THERMISTOR
GAS PIPE TEMP. A THERMISTOR
RT66
RT67
SSR61
T801
TB1
TB2
X61
X62
X64
CN61
GAS PIPE TEMP. B THERMISTOR
FIN TEMP. THERMISTOR
SOLENOID COIL RELAY
TRANSFORMER
TERMINAL BLOCK
TERMINAL BLOCK
FAN MOTOR RELAY
FAN MOTOR RELAY
RELAY
CONNECTOR
SG79J191H01
WIRING DIAGRAM
OUTDOOR UNIT
OUTDOOR UNIT
MODELS MXZ-18TV-
MODELS MXZ-18TV-
E1
E2
7
Page 8
9
a
Outdoor
unit
b
H
H
H
REFRIGERANT SYSTEM DIAGRAM
MXZ-18TV MXZ-18TV -
Stop valve
(with service port)
Indoor
Unit B
Indoor
Unit A
Stop valve
(with service port)
Indoor
Unit A
Indoor
Unit B
E1
E2
Stop valve
Stop valve
Discharge
temperature
thermistor
Gas pipe temperature
B thermistor
Muffler
Gas pipe temperature
A thermistor
Capillary tube
{3.0✕{2.0✕400
{6
Strainer
{6
Strainer
Capillary tube
{3.0✕{2.0✕400
Compressor
Muffler
4-way valve
LEV (A)
LEV (B)
{8
Capillary tube
{2.4✕{0.6✕750
{16
Evaporation
temperatuer
thermistor
R.V. coil
heating ON
cooling OFF
{12
Unit:mm
Refrigerant flow in cooling
Refrigerant flow in heating
Outdoor
heat
exchanger
Defrost
thermistor
Capillary tube
{4.0✕{2.4✕300
MAX REFRIGERANT PIPING LENGTH
-
MXY-18TV
MXY-18TV
Piping length each indoor unit (a, b)20m
Total piping length (a+b)30m
Height difference between units (H)10m
Bending point for each unit15
Total bending point 30
❋It does not matter which unit is higher.
● Refrigerant pipe diameter is different according to indoor unit to be connected. When using extension pipes,refer to the
tables below.
● When diameter of refrigerant pipe is different from that of outdoor unit union, use optional Different-diameter pipe.
For further information on Different-diameter pipe, see page BACK COVER.
classPipe diameter
07/09
12
NOTE: SEH-1.6AR is equivalent to class 12.
E1
-
E2
Indoor unit
Extension pipe diameter
Liquid6.35(1/4)Liquid6.35(1/4)
Gas9.52(3/8)Gas9.52(3/8)
Liquid6.35(1/4)Liquid6.35(1/4)
Gas12.7(1/2)Gas12.7(1/2)
Outdoor unit union diameter
For
Indoor unit A
Indoor unit B
Unit : mm (inch)
Liquid6.35(1/4)
Gas9.52(3/8)
Liquid6.35(1/4)
Gas9.52(3/8)
8
Page 9
10
Wet-and dry-bulb
thermometers
Wet-and dry-bulb
thermometers
07 class
7.7
7.2
6.6
6.1
5.5
5.0
9.3
8.6
7.9
7.3
6.6
6.0
8.4
7.8
7.2
6.6
6.0
5.4
12 class
09 class
25.9
23.9
21.9
19.9
17.9
15.9
13.9
11.9
23.6
21.8
19.9
18.1
16.3
14.5
12.7
10.9
25.7
23.7
21.8
19.8
17.8
15.8
13.8
11.9
07 class
09 class
12 class
PERFORMANCE CURVES
The standard data contained in these specifications apply only to the operation of the air conditioner under normal conditions,
since operating conditions vary according to the areas where these units are installed. The following information has been provided to clarify the operating characteristics of the air conditioner under the conditions indicated by the performance curve.
(1) GUARANTEED VOLTAGE
198 ~ 264V
, 50Hz
(2) AIR FLOW
Air flow should be set at MAX.
(3) MAIN READINGS
(1) Indoor intake air wet-bulb temperature :°CWB
(2) Indoor outlet air wet-bulb temperature :°CWB
(3) Outdoor intake air dry-bulb temperature :°CDB
}
Cooling
(4) Total input:W
(5) Indoor intake air dry-bulb temperature :°CDB
(6) Outdoor intake air wet-bulb temperature :°CWB
(7) Total input :W
Heating
}
Indoor air wet/dry-bulb temperature difference on the left side of the chart on page 10 and 11 shows the difference
between the indoor intake air wet/dry-bulb temperature and the indoor outlet air wet/dry-bulb temperature for your reference at service.
How to measure the indoor air wet-bulb/dry-bulb temperature difference
1. Attach at least 2 sets of wet-and dry-bulb thermometers to the indoor air intake as shown in the figure, and at least 2 sets
of wet-and dry-bulb thermometers to the indoor air outlet. The thermometers must be attached to the position where air
speed is high.
2. Attach at least 2 sets of wet-and dry-bulb thermometers to the outdoor air intake.
Cover the thermometers to prevent direct rays of the sun.
3. Check that the air filter is cleaned.
4. Open windows and doors of room.
5. Press the EMERGENCY OPERATION switch once(twice) to start the EMERGENCY COOL(HEAT) MODE.
6. When system stabilizes after more than 15 minutes, measure temperature and take an average temperature.
7. 10 minutes later, measure temperature again and check that the temperature does not change.
INDOOR UNITOUTDOOR UNIT
10-1. CAPACITY AND THE INPUT CURVES
9
Page 10
10-2. Capacity and input correction by inverter output frequency
050100150
0.5
1.0
1.5
050100150
0.5
1.0
1.5
050100150
0.5
1.0
1.5
050100150
0.5
1.0
1.5
050100150
0.5
1.0
1.5
050100150
0.5
1.0
1.5
050100150
0.5
1.0
1.5
050100150
0.5
1.0
1.5
050100150
0.5
1.0
1.5
050100150
0.5
1.0
1.5
050100150
0.5
1.0
1.5
<COOL>Capacity
Frequency
Hz
Frequency
<COOL>Total input
HzHz
<HEAT>Capacity
Frequency
Frequency
<HEAT>Total input
Hz
<COOL>Capacity
Frequency
Hz
Frequency
<COOL>Total input
Hz
<HEAT>Capacity
Frequency
050100150
0.5
1.0
1.5
Frequency
<HEAT>Total input
Hz
<COOL>Capacity
Frequency
Hz
Frequency
<COOL>Total input
Hz
<HEAT>Capacity
Frequency
Hz
Hz
Frequency
<HEAT>Total input
Hz
1. 07-class unit in single operation
2. 09-class unit in single operation
3. 12-class unit in single operation
NOTE 1 : Inverter output frequency : COOL 55Hz,HEAT 80Hz
(OUTDOOR UNIT:MXZ-18TV)
NOTE 2 : The dotted line on graphs connects the frequency range in normal operation shown by the full line and the frequency
in test run shown by the point.
10
Page 11
10-3. Outdoor low pressure and outdoor unit current
1. 07-class unit in single operation (OUTDOOR UNIT : MXZ-18TV)
NOTE:The unit of pressure has been changed to MPa on the international system of units(SI unit system).
The converted score against the traditional unit system can be gotten according to the formula below.
1(MPa • G) =10.2(kgf/ff• G)
(1) COOL operation
1Both indoor and outdoor units are under the same
temperature/humidity condition.
Dry-bulb temperature(°C)Relative humidity(%)
2050
2560
3070
2Air flow speed : HI
3Inverter output frequency : 55Hz
(kgf/F• Gauge)
Outdoor low pressure
(MPa•Gauge)
8
7
6
5
4
3
2
0.8
0.7
0.6
0.5
0.4
0.3
0.2
Ambient temperature(:)/ Ambient humidity(%)
2025
18
5060
30
70
55Hz
32
<How to work fixed-frequency operation>
1.Set emergency switch to COOL or HEAT.The switch is located on indoor unit.
2.Press emergency run ON/OFF button.
3.Compressor starts running at 55Hz (COOL) or 80Hz (HEAT).
4.Indoor fan runs at HI speed and continues for 30 minutes.
5.To cancel this operation,press emergency run ON/OFF button
or any button on remote controller.
4
55Hz
3.5
3
2.5
2
Outdoor unit current (A)
1.5
(%)
(:)
0.5
Ambient temperature(:)/ Ambient humidity(%)
2025
18
5060
30
70
32
(:)
(%)
(2) HEAT operation
①
IndoorOutdoor
➁
Set air flow to Hi speed.
➂
Inverter output frequency is 80Hz.
DB(°C) 20.0
WB(°C) 14.5
DB(°C) 271520.0
WB(°C) 161214.5
8
7
6
5
4
Outdoor unit current (A)
3
2
2510152025
80Hz
Ambient temperature(:)
11
Page 12
2. 09-class unit in single operation (OUTDOOR UNIT : MXZ-18TV)
NOTE: The unit of pressure has been changed to MPa on the international system of units(SI unit system).
The converted score against the traditional unit system can be gotten according to the formula below.
1(MPa • G) =10.2(kgf/ff• G)
(1) COOL operation
1Both indoor and outdoor units are under the same
temperature/humidity condition.
Dry-bulb temperature(°C)Relative humidity(%)
2050
2560
3070
2Air flow speed : HI
3Inverter output frequency : 55Hz
<How to work fixed-frequency operation>
1.Set emergency switch to COOL or HEAT.The switch is located on indoor unit.
2.Press emergency run ON/OFF button.
3.Compressor starts running at 55Hz (COOL) or 80Hz (HEAT).
4.Indoor fan runs at HI speed and continues for 30 minutes.
5.To cancel this operation,press emergency run ON/OFF button
or any button on remote controller.
(kgf/F• Gauge)
Outdoor low pressure
(2) HEAT operation
①
IndoorOutdoor
➁
Set air flow to Hi speed.
➂
Inverter output frequency is 80Hz.
(MPa•Gauge)
0.8
8
0.7
7
0.6
6
0.5
5
0.4
4
0.3
3
2
0.2
Ambient temperature(:)/ Ambient humidity(%)
DB(°C) 20.0
WB(°C) 14.5
18
2025
5060
4
55Hz
30
32
(:)
70
DB(°C) 271520.0
WB(°C) 161214.5
(%)
3.5
3
2.5
Outdoor unit current (A)
2
1.5
Ambient temperature(:)/ Ambient humidity(%)
18202530
506070
55Hz
32
(:)
(%)
12
8
7
6
5
4
Outdoor unit current (A)
3
2
2510152025
Ambient temperature(:)
80Hz
Page 13
3. 12-class unit in single operation (OUTDOOR UNIT : MXZ-18TV)
NOTE: The unit of pressure has been changed to MPa on the international system of units(SI unit system).
The converted score against the traditional unit system can be gotten according to the formula below.
1(MPa • G) =10.2(kgf/ff• G)
(1) COOL operation
1Both indoor and outdoor units are under the same
temperature/humidity condition.
Dry-bulb temperature(°C)Relative humidity(%)
2050
2560
3070
2Air flow speed : HI
3Inverter output frequency : 55Hz
<How to work fixed-frequency operation>
1.Set emergency switch to COOL or HEAT.The switch is located on indoor unit.
2.Press emergency run ON/OFF button.
3.Compressor starts running at 55Hz (COOL) or 80Hz (HEAT).
4.Indoor fan runs at HI speed and continues for 30 minutes.
5.To cancel this operation,press emergency run ON/OFF button
or any button on remote controller.
(kgf/F• Gauge)
Outdoor low pressure
(2) HEAT operation
①
IndoorOutdoor
➁
Set air flow to Hi speed.
➂
Inverter output frequency is 80Hz.
(MPa•Gauge)
8
7
6
5
4
3
2
0.8
0.7
0.6
0.5
0.4
0.3
0.2
DB(°C) 20.0
WB(°C) 14.5
18
Ambient temperature(:)/ Ambient humidity(%)
2025
5060
4
3.5
55Hz
3
2.5
2
Outdoor unit current (A)
1.5
32
30
70
DB(°C) 271520.0
WB(°C) 161214.5
(:)
(%)
1
Ambient temperature(:)/ Ambient humidity(%)
18202530
506070
55Hz
32
(:)
(%)
13
8
7
6
5
4
Outdoor unit current (A)
3
2
2510152025
Ambient temperature(:)
80Hz
Page 14
11
Compressor
power
factor
Indoor unit
microprocessor
SSR61
Drive
circuit
Transistor
module
Indoor Unit
B
Indoor Unit
B
Comp.
Discharge
temperature
thermistor
RT61
Evaporation
temperature
thermistor
RT63
Gas pipe
temperature
thermistor RT66
Gas pipe
temperature
thermistor RT65
Indoor Unit
A
Indoor Unit
A
Outdoor
fan motor
MF61
x 61
x 62
Defrost
thermistor
RT62
LEV (A)
LEV (B)
Outdoor unit control microprocessor
Compressor
primary
current
Compressor
secondary
current
Fin temperature
thermistor RT67
R. V. coil
21S4
Input signal
Output signal
MICROPROCESSOR CONTROL
INVERTER MULTI SYSTEM CONTROL
MXZ-18TV -
MXZ-18TV -
E1
E2
14
Page 15
11-1.LEV control
Linear expansion valve (LEV) is controlled by "Thermostat ON" commands given from each unit.
Indoor unit status
Stop of all indoor unit
Opening before stop ➝ 500 pulse in 15 minutes
When outdoor unit is operating,
some indoor unit stops and
some operates.
Thermostat OFF in
COOL or DRY mode
When the outdoor unit operation (When the other indoor unit operate): 5 pulse.
When outdoor unit stops. (When the other indoor unit stops or thermo off):
Maintain LEV opening before stop ➝ 500 pulse in 15 minutes
• LEV opening for each indoor unit is determined by adding adjustment in accordance
with the number of operating unit and the capacity class to standard opening, based
on the operation frequency:
Ex.) Opening 130 pulse in standard opening 1 ➝ Minimum 80 pulse, Maximum 205
Thermostat ON in
COOL or DRY mode
pulse. (Capacity code 4 at 1 unit operation) (Capacity code 1 at 4 unit operation)
• After starting operation, adjustment in accordance with intake super heat, discharge
temperature is included in standard opening. w1
Note: LEV opening in each frequency at DRY operation and COOL operation is the
same. However, velocity and compressor operation frequency controls are
different. See 11-2 Operational frequency range
(As far as the indoor unit velocity control goes, refer to DRY operation in
MICROPROCESSOR CONTROL in the indoor unit service manual.)
• When the outdoor unit operates. (When the other indoor unit operates): 59 pulse
Thermostat OFF in HEAT mode
• When the outdoor unit stops. (When the other indoor unit stops or thermo off):
Maintain LEV opening before stop ➝ 500 pulse in 15 minutes.
• LEV opening for each indoor unit is determined by adding adjustment in accordance
with the number of operating unit and the capacity class to standard opening, based
Thermostat ON in HEAT mode
on the operation frequency:
Ex.) Opening 120 pulse in standard opening 1 ➝ Minimum 70 pulse, Maximum 165
pulse. (Capacity code 4 at 1 unit operation) (Capacity code 1 at 4 unit operation)
• After starting operation, opening becomes the one that adjustment in accordance
with discharge temperature was added to basic opening. w1
w1 LEV opening when the outdoor unit operating: Upper limit 500 pulse, Lower limit 59 pulse.
Determination of LEV standard opening in each indoor unit
• The standard opening is on the straight line, which connects an each standard point in the section where divided
into seven according to the operation frequency of compressor as shown in the figure below.
(LEV opening is controlled in proportion to the operation frequency.)
Note: Opening is adjusted at the standard opening according to the indoor unit conditions.
However, inclination of standard opening in each point of opening does not change with the original curve.
• Add opening provided in Difference in Capacity in the table below to the standard opening from 1 to 8,
when capacity of the indoor unit is excluding code 1.
• Add opening provided in Difference in Operation number in the table below to determined LEV opening for
each indoor unit, when 2, 3 or 4 indoor units are operated at the same time.
Note: Even when the adjusted standard opening exceeds the driving range from 59 to 500 pulse, actual
driving output opening is in a range from 59 to 500 pulse.
< Calculation example of LEV opening >
Cool operation: Compressor frequency 70Hz: 2 unit ON: 18class
(170-150)p(80-60)o(70-60)+150+75-30=205 pulse
Standard opening
12345678
220
210
200
190
180
170
160
150
140
LEV opening (Pulse)
130
120
720406080100120140
COOL
HEAT
Operation frequency of compressor (Hz) : F
15
Page 16
(1) LEV opening correction by suction super heat (COOL, DRY)
Suction superheat (S.H.)
LEV opening
correction (pulse)
more than 12
10 to12
8 to 10
6 to 8
6 or less
6
4
3
2
0
Difference of
superheat
LEV opening
correction (pulse)
more than 9
6 to9
3to 6
6 or less
8
6
2
0
1 Suction super heat
(MIN gas pipe temperature thermistor - Evaporation temperature thermistor)
2 Each correction w 1
• (Each gas pipe temperature thermistor - Evaporation temperature thermistor)
• (Main pipe temperature thermistor - sub pipe temperature thermistor)
w 1 Perform this, when number of operation units is 2units or more
w 2 When the correction opening of suction super heat is 0, correct the LEV opening by dischaege temperature.
3 Discharge temperature
COOLDRYHEAT
••
-
•
w 2
•
w 2
•
<Correction>
2
Code3Code2
Standard opening
Difference in
capacity
Difference in
operation number
12345678
COOL
HEAT
150
120
160
130
170
140
180
150
Capacity code
Indoor unit
1
07209312418
190
160
190
170
200
180
200
180
25
20
50
40
-60
-60
(Suction super heat) = (Minimum gas pipe temperature) - (Evaporation temperature)
When COOL and DRY , correct the LEV openings corrected from the table below
(2) Separate correction (COOL,DRY)
(When number of operation unit is 2 units)
(a) Correction by the separate super heat
Correct the LEV separately by temperature difference between each gas pipe temperature thermistor and evaporator
temperature thermistor.
1 Calculate each super heat of the unit from the expression below;
(Super heat) = (Gas pipe temperature thermistor) - (Evaporation temperature thermistor)
2 Select a minimum super heat from among them.
3 Correct an each LEV is corrected opening is corrected by difference between each super heat and minimum super
heat.
16
Page 17
(3) LEV opening correction by discharge temperature
Operation frequency
of compressor
Minimum ~ 20
21 ~ 33
34 ~ 46
47 ~ 59
60 ~ 72
73 ~ 85
86 ~ 98
97 ~ 111
111 ~ Maximum
Single
40
40
45
45
50
55
65
70
75
Double
40
40
45
45
50
55
65
70
75
Single
40
45
50
55
60
65
70
75
75
Double
40
45
50
55
60
65
70
73
73
Number of operating unit.Number of operating unit.
COOL, DRYHEAT
Discharge temperature (;)
LEV opening
correction (pulse)
more than Target discharge temperature+11
Target discharge temperature+11 to Target discharge temperature+8
Target discharge temperature+8 to Target discharge temperature+5
Target discharge temperature+5 to Target discharge temperature+2
Target discharge temperature+2 to Target discharge temperature-2
Target discharge temperature-2 to Target discharge temperature-5
Target discharge temperature-5 to Target discharge temperature-8
Target discharge temperature-8 to Target discharge temperature-11
Target discharge temperature-11 or less
COOL
10
4
2
1
0
-1
-2
-5
-8
HEAT
8
2
1
1
0
-1
-1
-2
-6
DRY
Min. Max. RatedMin. Max.
Defrost
Rated
Note: When the fan speed of indoor unit is total
Lo notch, the maximum frequency is
rated frequency.
COOL
HEAT
Number of
operating
unit
1
2
3
2
3
4
5
6
7
30
30
70
80
100
120
55
61
85
108
30
41
53
723030
100
100
120
120
100
100
100
100
80
85
94
120
1
2
capacity
cord
When LEV correction output is 0 pulse by the suction super heat at cool or dry operation, or dry operating, correct LEV is corrected according to the following table.
The target discharge temperature is determined according to frequency zone and number of operation unit of the
compressor.
Correct the LEV opening according to difference between the target discharge temperature and discharge temperature.
11-2.Operational frequency range
11-3.Heat defrosting control
(1) Conditions to enter defrosting mode
1. When temperature of defrosting thermistor is -3; or less.
2.When specified non-defrosting time, is counted in the control p.c.board is satisfied.
(Total time of compressor operating)
Going to defrosting mode at both condition of 1 and 2.
(2) Defrosting operation
1. Compressor stops for 50 seconds, Indoor fan is off, Defrosting lamp lights
2.4-way valve reverses flow, Compressor operates by the frequency in heat defrosting control.
3. After compressor stops for 35 seconds, 4-way valve reverses flow, then defrosting finishes.
(3) Conditions to finish defrosting mode
1. When the defrosting thermistor temperature is 8; or more.
2. When it has spent 10 minutes for defrosting.
Defrosting finishes at condition of 1 or 2.
17
Page 18
11-5.Discharge temperature protection control
COOL
Fan speed
Up
Down
Up
Down
SingleDouble
Mode
HEAT
Indoor unit operation
<Relation between compressor frequency and fan speed.>
60Hz
50Hz
60Hz
50Hz
60Hz
50Hz
60Hz
50Hz
Up
Down
Fan speed
Hi
Low
Compressor frequencyMin.Max.
Discharge temperature thermistor
Indoor pipe temperature thermistor
Defrost thermistor
Evaporation temperature thermistor
Gas pipe temperature thermistor
Fin temperature thermistor
Capacity code
Purpose
Protection
Defrosting Protection
Defrosting
Control
Control
Protection
Control
CompressorLEV
Outdoor
fan motor
Reversing
valve
Sensor
Actuator
This protection controls the compressor ON/OFF and operation frequency according to temperature of the discharge temp.
thermistor.
(1) Compressor ON/OFF
When temperature of the discharge temp. thermistor exceeds 116;, the control stops the compressor.
When temperature of the discharge temp. thermistor is 80; or less, the controls starts the compressor.
(2) Compressor operation frequency
When temperature of the discharge temp. thermistor is expected to be higher than 116;, the control decreases 12Hz from the
current frequency.
When temperature of the discharge temp. thermistor is expected to be higher than 111; and less than 116;, the control
decreases 6Hz from the current frequency.
When temperature of the discharge temp. thermistor is expected to be higher than 104; and less than 111;, the control is set
at the current frequency.
11-6.Refrigerant recovery control on heating
<Control status>
The control performs when the following status are satisfied everything;
• When there is 1 unit or more not operating indoor unit on heat operation. (Excluding thermo OFF)
• When discharge temperature becomes 107; or more.
• When it passed 60 minutes or more since the operation has started or the last refrigerant recovery has controlled.
<Control details>
LEV opening, which adjusts to not operating indoor unit, is considered to be 80 pulse.
<Control finish status>
The control finishes either as follows. However, the LEV opening is considered to be 59 pulse.
• When it passed 60 seconds since the control has started.
• When the discharge temperature is 90; or less.
11-7.Outdoor fan control
Fan speed is switched according to a number of operating indoor unit and the compressor frequency.
Note
•When operation, fan speed of Hi/ Low mode changes to VHi/ Hi mode by promoting those fan speeds respectively by
1 step after defrosting is operated. This control is cleared, when the compressor off.
•When overheat protection of P.C. board temperature or fin temperature operates, the outdoor fan speed is fixed to VHi
mode regardless of compressor frequency. Also, when the overheat protection is cleared, the fan speed is
back to normal
•When the indoor coil thermistor is 57; or more on HEAT operation, fan speed is fixed to Low notch .
Or, the indoor coil thermistor is 45; or less on HEAT operation, fan speed is back to normal.
11-8.Relation between main sensor and actuator
Relation between main sensor and actuator.
18
Page 19
12TROUBLESHOOTING
Lead wiring
Housing point
Operation start
Check the outdoor unit
LED indicator
A Check of power supply
See page 22.
• Indoor unit
serial signal
error
B Check of
serial signa
See page 22.
• Cool or HEAT
opereation only
C Check of
R.V.coil
See page 23.
• When cooling,
room does not
cool.
E Check of
inverter,
compressor
See page 24.
• When cooling, heat
exchanger of
non-operating indoor
unit frosts.
•When heating, non
operating indoor unit
gets warm.
D Check of LEV
See page 24.
• When cooling,
dew drops in the
non-operating
indoor unit
Check of mispiping.
• When heating,
room doed not get
warm.
E Check of
inverter,compressor
See page 24.
Check mis-piping
Shortage of capacity
Refer to indicator list
See page 20, 21.
OFF
Both LED 1 and
LED 2 lighting
• Check the indoor unit with referring to the indoor unit service manual, and confirm that there is any problem in the indoor unit.
Then, check the outdoor unit with referring to this page.
LED 1 or LED 2
has blinked.
12-1. Cautions on troubleshooting
1. Before troubleshooting, check the following:
1) Check the power supply voltage.
2) Check the indoor/outdoor connecting wire for mis-wiring.
2. Take care the following during servicing.
1) Before servicing the air conditioner, be sure to first turn off the remote controller to stop the unit, and then after confirming the horizontal vane is closed, turn off the breaker and / or disconnect the power plug.
2) Be sure to unplug the power cord before removing the front panel, the cabinet, the top panel, and the electronic control P.C. board.
3) When removing the electronic control P.C. board, hold the edge of the board with care NOT to apply stress on the
components.
4) When connecting or disconnecting the connectors, hold the housing of the connector. DO NOT pull the lead wires.
3. Troubleshooting procedure
1) First, check if the OPERATION INDICATOR lamp on the indoor unit is flashing on and off to indicate an abnormality.
To make sure, check how many times the abnormality indication is flashing on and off before starting service work.
2) If the electronic control P.C. board is supposed to be defective, check the copper foil pattern for disconnection and the
components for bursting and discoloration.
3) When troubleshooting, refer to the flow chart on page 19 and the check table on page 20, 21.
12-2. Instruction of troubleshooting
19
Page 20
Troubleshooting check table <OUTDOOR UNIT>
LED 1 (red)
Lighting
Indication
LED 1
Lighting
Lighting
6 times Goes out
Lighting
LED 1
Lighting
Lighting
(red)
Indication
(red)
LED 2
(Yellow)
Twice
7 times
9 times
LED 2
(Yellow)
3 times
4 times
LED 2 (yellow)
Lighting
Symptom: Outdoor unit does not operate.
Abnormal pointDetecting methodCheck points
Outdoor power system
Outdoor control system
Indoor unit and LEV
DC voltage sensing circuit
Abnormal pointDetecting methodCheck points
Discharge temperature
thermistor
Fin temperature thermistor
When the compressor operation has been interrupted by overcurrent
protection continuously three times within 1 minute after start-up.
When the nonvolatile memory data cannot be read properly on the outdoor electronic control P.C. board.
When the drain abnormality is detected in the indoor unit and the indoor
unit coil temperature is too low, or when any abnormality is detected in
the components of indoor unit.
When DC voltage sensing circuit detects 57V or below or 395V or above
Symptom: Outdoor unit repeats to stop and restart in 3 minutes
When a short or open circuit occurs in the discharge temperature thermistor during compressor running.
When a short or opern circuit occurs in the fin temperature thermistor
during compressor running.
Error mode
Normal
• Check the inverter / compressor.
Refer to “E” on page 24.
• Replace the outdoor electronic control
P.C. board.
• Check the abnormality indication on the
indoor unit.
• Check the LEV.
Refer to “D” on page 24.
• Replace the outdoor electronic control
P.C. board.
• Check the characteristic of the discharge
temperature thermistor.
Refer to “F” on page 25.
• Check the connector. (CN663)
• Check the characteristic of the fin temperature thermistor.
Refer to “F” on page 25.
• Check the connector. (CN664)
Lighting
Lighting
Lighting
Lighting
3 times Goes out
4 times Goes out
4 times Goes out
5 times
10 times
11 times
12 times
Twice Goes out
P.C. board temperature
thermistor
Evaporation temperature thermistor
Gas pipe temperature A
thermistor
Gas pipe temperature B
thermistor
Over current protection When over current is applied to the power module.
Discharge temperature
overheat protection
Fin temperature overheat protection
P.C. board temperature
overheat protection
When a short or open circuit occurs in the P.C. board temperature thermistor during compressor running.
When a short or open circuit occurs in the evaporation temperature thermistor during compressor running.
When a short or open circuit occurs in the gas pipe temperature Athermistor during compressor running.
When a short or open circuit occurs in the gas pipe temperature B thermistor during compressor running.
When the discharge temperature thermistor detects 116: or above.
(Protection will be released at 100: or below.)
When the fin temperature thermistor detects 91: or above.
When the P.C. board temperature thermistor detects 79: or above.
• Replace the outdoor electronic control
P.C. board.
• Check the characteristic of the evaopration temperature thermistor.
Refer to “F” on page 25.
• Check the connector. (CN663)
• Check the characteristic of the gas pipe
temperature A thermistor.
Refer to “F” on page 25.
• Check the connector. (CN661)
• Check the characteristic of the gas pipe
temperature B thermistor.
Refer to “F” on page 25.
• Check the connector. (CN661)
• Check the inverter / compressor.
Refer to “E” on page 24.
• Check the amount of gas.
• Check the indoor / outdoor air flow for
short cycle.
• Check the indoor unit air filter for clogging.
• Check the amount of gas and the refrigerant cycle.
• Check the outdoor unit air passage.
• Check the outdoor unit air passage.
• Check the outdoor fan motor.
Refer to “G” on page 25.
• Check the power module.
• Check the outdoor unit air passage.
• Check the outdoor fan motor.
Refer to “G” on page 25.
• Replace the outdoor electronic control
P.C. board.
20
Page 21
Indication
W
U
V
WHT
RED
BLK
WHT
Protector specification
Short
Open
87I15:
135I5:
YLW
P
ORN
RED
BLK
LEV
WHT
RED
YLW
BRN
ORN
BLU
LED 1
LED 2
(red)
(Yellow)
OnceLighting
Symptom: Oudtoor unit operates (The compressor operates at reduced frequency)
Abnormal pointDetecting methodCheck points
Current protectionWhen the outdoor unit input current exceeds 15.5A.
Overload protectionWhen the compressor load exceed the specified value.Twice
High pressure protec-
tion
Defrosting in cooling
Discharge temperature
protection
Low discharge tempera-
ture protection
LED 2
Defrost thermistor
Power factor detection When the compressor power factor cannot be detected.• Check the compressor wiring.6 times Lighting
When indoor pipe temperature exceeds 55: during heating.
When indoor pipe temperature falls to 6: or below during cooling.
When the discharge temperature exceeds 111:.
When the state with low discharge temperature of which 50.4: or below
in cool and 48.8: or below in heat for 20 minutes.
Abnormal pointDetecting methodCheck points
When a short or open circuit occurs in the defrost thermistor during heating.
3 times
3 times
4 times
7 times
Indication
LED 1
(red)
5 times
Lighting
Lighting
Lighting
Lighting
Lighting
(Yellow)
Lighting
12-4. Trouble criterion of main parts
Part nameCheck method and criterion
Defrost thermistor
Evaporation / Gas pipe
temperature thermistor
Measure the resistance using a tester.
(Part temperature -10°C ~ 40°C)
These symptoms do not mean any abnormality of the product, but check the following points.
• Air filter clogging.
• Amount of gas.
• Short cycle of indoor / outdoor air flow.
Symptom: Outdoor unit operates
• Check the characteristic of the defrost
temperature thermistor.
Refer to “F” on page 25.
• Check the connector. (CN663)
Normalabnormal
5kΩ ~ 55kΩOpened or short-circuited
Discharge temperature
thermistor
Compressor
Outdoor fan motor
R. V. coil
Linear expansion valve
Measure the resistance using a tester, after warming up the thermistor by holding by hand.
(Part temperature : 20°C ~40°C)
Normalabnormal
100kΩ ~ 250kΩOpened or short-circuited
Measure the resistance between terminals using a tester.
(Winding temperature : -10°C ~ 40°C)
Normalabnormal
1Each phase 0.39Ω ~ 0.50ΩOpened or short-circuited
Measure the resistance between lead wires using a tester.
(Part temperature : -10°C ~ 40°C)
WHT - BLK
BLK - YLW
BLK - RED
Normal
208.4Ω ~ 254.8Ω
42.4Ω ~ 51.9Ω
197.7Ω ~ 241.7Ω
abnormal
Opened or
short-circuited
Measure the resistance using a tester. (Part temperature -10°C ~ 40°C)
Normalabnormal
2.6kΩ ~ 3.3kΩOpened or short-circuited
Measure the resistance using a tester.(Part temperature -10°C ~ 40°C)
Lead wire colorNormal
Abnormal
WHT - RED
RED - ORN
YLW - BRN
Opened or short-circuited37.4Ω ~ 53.9Ω
BRN - BLU
P Inner protector
21
Page 22
Outdoor unit does not operate. (LED display: display OFF)
AA
Check of power supply
Start
Check the connecting of main circuit parts .
Turn on power supply
Is there voltage of 230V AC in the
power supply terminal block?
Yes
Is there voltage of 325V DC across the
smoothing capacity?
Yes
Replace the outdoor electronic control
P. C. board.
Outdoor unit does not operate. (LED display: Both LED1 and LED2 lighting)
BB
Check of outdoor unit serial signal
Start
No
No
Check the power supply cable.
Is there voltage of 230V AC across the
input terminal part in the diode module
(DS61)?
Yes
Check the main circuit parts
and replace it.
Replace the noise
No
filter P. C. board
1. Check the indoor unit with referring to the indoor unit service manual.
2. Turn off the power supply of the indoor and outdoor unit and return the indoor/ outdoor unit connecting wire to former
original.
3. Check the connection of indoor/ outdoor unit connecting wire in the outdoor unit terminal block, and check the connection
of the connector (CN601: unit A, CN602: unit B) in the control P. C. board
4. Disconnect the lead wire to the compressor. Turn on the power supply (indoor/ outdoor unit) 3 minutes later,
EMERGENCY OPERATION starts.
Is there voltage from 5V DC - 10V DC between
No. 3 (+) and N (-) in the outdoor terminal block.
Yes
Recheck a connected circumstance of the indoor/ outdoor unit connecting wire.
No
Replace the outdoor electronic control P. C. board.
22
Page 23
The cooling operation or heating operation does not operate. (LED display: Both LED1 and LED2 lighting)
CC
Check of R. V. coil
• When heating operation does not work.
Start
1. Disconnect the lead wire leading to the compressor.
2. Turn on power supply to the indoor and outdoor unit, three minutes later
EMERGENCY OPERATION (HEAT operation) starts.
Is there voltage of 230V AC between pin1 and
pin 2 at connector CN912?
Yes
Turn off power supply of indoor and outdoor unit.
Disconnect the connector
CN912 in noise filter P. C.
board, and measure the
resistance of R. V. coil to
check the integrity.
Yes
Replace the 4-way valve
• When cooling operation does not work.
Start
1. Disconnect the lead wire leading to the compressor.
2. Turn on power supply to the indoor and outdoor unit, three minutes later
EMERGENCY OPERATION (COOL operation) starts.
No
Replace the R. V. coil
No
1. Turn off power supply of indoor and outdoor unit, and
disconnect the connector (CN851) in the outdoor electronic
control P. C. board.
2. Turn on power supply to the indoor and outdoor unit, three
minutes later EMERGENCY OPERATION
(HEAT operation) starts.
Is there voltage 12V DC between
the connector CN851 pin 3 (+)
and pin 4 (-)?
Yes
Replace the noise filter P. C. board.
No
Replace the electronic
control P. C. board.
Is there voltage of 230V AC between pin1 and
pin 2 at connector CN912?
Yes
1. Turn off power supply of indoor and outdoor unit, and
disconnect the connector (CN851) in the outdoor electronic
control P. C. board.
2. Turn on power supply to the indoor and outdoor unit, three
minutes later EMERGENCY OPERATION
(COOL operation) starts.
Is there voltage 12V DC between
the connector CN851 pin 3 (+)
and pin 4 (-)? W1
Yes
Replace the outdoor electronic control P. C. board.
No
Replace the noise filter P. C. board.
W1If the connector CN912 is not connected or R. V. coil is open, voltage
occurs between terminals even when the control is OFF.
No
Replace the 4-way valve
23
Page 24
• When cooling, heat exchanger of non-operating indoor unit frosts.
• When heating, non-operating indoor unit get warm.
DD
Check of LEV
Start
Turn on power supply to the outdoor unit after checking LEV coil is mounted to the
LEV body securely.
LED display:
LED1LED2
LightingLighting
6 timeGoes out
Is "click - click" sound heard?
Or, do you feel vibration of the LEV coil with a hand?
No
Disconnect the connector
(CN771: unit A, CN772: unit B), and measure the
resistance of LEV coil to check the integrity.
No
Replace the LEV coil.
• When heating, room does not get warm.
• When cooling, room does not get cool.
EE
Check of inverter/ compressor
Start
Disconnect the lead wire to the compressor at terminals, and turn on power supply to the indoor
and outdoor unit. Three minutes later, EMERGENCY OPERATION starts.
Measure the voltage between
each leading to the compressor.
U (BLK) - V (WHT)
V (WHT) - W (RED)
W (RED) - U (BLK)
Output voltage
COOL: 100V(58Hz), HEAT: 100V (58Hz)
Is voltage output? W1
Yes
Is output balanced?
Yes
Turn off power supply of indoor and outdoor unit,
and measure the compressor winding resistance
between the compressor terminals.
Is there resistance of 0.53" to 0.66" between
the each terminals?
Yes
No
LED display:
W1 • After the outdoor fan starts running, wait for 1 minutes or more before
measuring the voltage.
•The output voltage values in the above table have the tolerance of i20%.
No
Yes
Yes
Replace the outdoor electronic
control P. C. board
No
Normal
Replace the outdoor electronic
control P. C. board
LED1LED2
LightingLighting
Lighting
Twice
Replace the
compressor.
Twice
Goes out
Return the lead wire of compressor to former, and
turn on power supply to indoor and outdoor unit.
Three minutes later EMERGENCY OPERATION starts.
Clarify the causes by counting time until the inverter stops.
0 to 10 seconds: compressor rare short
10 to 60 seconds: compressor lock
60 seconds to 5minutes: refrigerant circuit defective
5 minutes or more: normal
24
Page 25
• When thermistor is abnormal. (When the LED display is a table below.)
FF
Check of outdoor unit thermistor
Start
Disconnect the connector in the outdoor electronic control P. C. board (see below table),
and measure the resistance of thermistor to check whether the thermistor is normal or not.
Normal
Reconnect the connector (CN661, CN663 and CN664) and disconnect the lead wire leading to the compressor.
Turn on power supply to the indoor and outdoor unit. Three minutes later EMERGENCY OPERATION starts.
Does thermistor operate 10 minutes or more though the
thermistor abnormality is not displayed?
Yes
Normal
Thermistor
Discharge temperature thermistor
Defrost thermistor
Evaporation temperature thermistor
Gas pipe temperature A thermistor
Gas pipe temperature B thermistor
Fin temperature thermistor
• Fan motor does not operate. Or fan motor stops at once after fan motor operate.
GG
Check of outdoor fan motor
Symbol
RT61
RT62
RT63
RT65
RT66
RT67
No
Replace the outdoor electronic
control P. C. board.
Connector, Pin No.
Between CN663 pin3 and pin4
Between CN663 pin1 and pin2
Between CN663 pin5 and pin6
Between CN661 pin1 and pin2
Between CN661 pin3 and pin4
Between CN664 pin1 and pin2
Abnormal
Replace the thermistor
Start
Check the connection of connector (CN851) in the fan motor relay connector and outdoor electronic control P. C. board
at the noise filter P. C. board and connector (CN901) in the noise filter board.
Disconnect the fan motor connector, and measure the resistance of the
fan motor winding to check the winding characteristic.
Normal
1. Disconnect the lead wire leading to the compressor. Turn on power supply to the
indoor and outdoor unit. Three minutes later, EMERGENCY OPERATION starts.
2. Check the voltage between pin 1 and pin 4, pin 1 and pin 5 at the fan motor connector.
Is there voltage of 230V AC?
No
1. Turn off power supply of the indoor and outdoor unit, and disconnect the connector
(CN851).
2. Is the voltage 0V, when the voltage between CN851 pin3 (+), pin7 (-), pin6 (-) are
measured after the power supply is turned on the outdoor unit?
Yes
Is there voltage of 12V DC between CN851 pin3 (+) and pin6 (-), when power supply
turns on the indoor unit and EMERGENCY OPERATION starts in three minutes.
Yes
Replace the noise filter P. C. board
Yes
Abnormal
No
No
Replace the fan motor
Replace the oudtoor
electronic control P. C.
board
25
Page 26
HH
The other cases
Indoor unit dose not operate. (difference modes)
1
• When you try to run two indoor unit simultaneously, one for cooling and the other for heating, the unit which
transmits signal to the outdoor units earlier decides the operation mode. The other unit indicates as shown in
the figure below.
• When the above situation occurs, set all the indoor units to the same mode, turn OFF the indoor units, and
then turn them back ON.
• Though the top of the indoor unit sometimes gets warm, this does not mean malfunction. The reason is that
the refrigerant gas continuously flows into the indoor unit even while it is not operating.
(1) Remove the screws fixing the top panel and remove it.
(Photo 1)
(2) Remove the screw fixing the service panel, next pull down
the service panel and remove it from the cabinet. (Photo 2)
(3) Remove the screws fixing the front cover and remove it.
(4) Remove the inside and outside connection electric wire.
(5) Remove the screws fixing the back panel and remove it.
Photo 2
4 Hooks
2. Removing the inverter assembly
(1) Remove the top panel, front panel, and service panel.
(2) Remove the inside and outside connection electric wire, next
remove the back panel.
(3) Disconnect the connector of outdoor fan motor (CN911),
R.V. coil (CN912) in the noise filter P.C. board.
Disconnect the connector of discharge / defrost / evapora-
tion temperature thermistor (CN663), gas pipe temperature
thermistor (CN661), LEV A(CN771), LEV B (CN772) in the
electronic control P.C. board.
(4) Remove the compressor relay connector. (Photo 3)
(5) Remove the two screws fixing the relay panel, and remove
the inverter assembly. (Photo 3)
Photo 1
Front panel
Photo 3
PHOTOS
Top panel
Back panel
Screw of the
service panel
Service panel
Screw of the
relay panel
3. Removing the inverter P.C. board
(1) Remove the top panel, front panel, and service panel.
(2) Remove all the connectors the lead wire and the earth wire
on the electronic control P.C board.
(3) Remove the compressor relay connector.
(4) Remove the two screws fixing the heat sink, and pull up the
inverter P.C. board.
(5) Remove the screws fixing the transistor module.
(6) Remove the inverter P.C. board.
4. Removing the noise filter
(1) Remove the top panel, front cover, and service panel.
(2) Remove all the connectors the lead wire and earth wire on
the electronic control P.C. board.
(3) Remove the two hooks, then remove the noise filter P.C.
board.
29
Photo 4
Inverter
P.C. board
Compressor connector
Screws of
the heat sink
Noise filter
P.C. board
Hooks
Page 30
OPERATING PROCEDURE
5. Removing the 4-way coil
(1) Remove the top panel, front cover and service panel.
(2) Remove the inside and outside connection electric wire, next
remove the back panel.
(3) Remove 4-way coil and disconnect the noise filter P.C. board
connectors CN912
6. Defrost, Discharge temperature thermistor
(1) Remove the top panel, front cover, service panel.
(2) Remove the inside and outside connection electric wire, next
remove the back panel.
(3) Remove the connector CN663 on inverter P.C. board.
(4) Remove the defrost thermistor and remove the discharge
temperature thermistor on the compressor. (Photo 5, 6)
7. Fin temperature thermistor
(1) Remove the top panel, front cover, service panel.
(2) Remove the inside and outside connection electric wire, next
remove the back panel.
(3) Remove all the connectors the lead wire and the earth wire
on the electronic control P.C. board.
(4) Remove the compressor relay connector. (Photo 3)
(5) Remove the two screws fixing the heat sink, and pull up the
inverter P.C. board. (Photo 4)
(6) Remove the screws fixing the transistor module. (Photo 4)
(7) Remove the screws the fin temperature thermistor, and
remove it. (Photo 7)
PHOTOS
Photo 5
Discharge temperature thermistor
Photo 6
8. Removing the fan motor
(1) Remove the top panel, front cover.
(2) Remove the fan motor connectors (CN911) on the noise fil-
ter P.C. board.
(3) Remove the propeller fan.
(4) Remove the screws fixing the fan motor and remove it.
Photo 7
Photo 8
Fan motor
Defrost thermistor
Inverter board
Fin temperature
thermistor
Screws of fan motor
30
Propeller
fan
Page 31
OPERATING PROCEDUREPHOTOS
9. Remove the compressor
(1) Remove the top panel, front cover, service panel.
(2) Remove the inside and outside connection electric wire,
next remove the back panel.
(3) Remove the inverter assembly.
(4) Can have the service of compression, 4-way and other
refrigerant circuit..
(5) Remove then the part (four places) which welds it when
you leave 4-way. (Photo 9)
Photo 9
Welded part
31
Page 32
14
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
FIN TEMPERATURE THERMISTOR
DIODE STACK
REACTOR
CONNECTOR POST ASSY
NOISE FILTER P.C. BOARD
NOISE FILTER P.C. BOARD
FUSE
THERMISTOR SET
GAS PIPE TEMPERATURE THERMISTOR SET
R.V. COIL
TERMINAL BED
TERMINAL BED
ELECTRONIC CONTROL P.C. BOARD
POWER FACTOR CAPACITOR
SMOOTHING CAPACITOR
FUSE
FUSE&VARISTOR
RT67
DS61, DS62
L
RT61,RT62,RT63
RT66, RT65
21S4
TB2
TB1
C61
C62
F911
F912,NR63
1
2
1
1
1
1
1
1
1
1
1
1
1
1
1
No.Parts Name
Symbol
in Wiring
Diagram
Parts No.
Q'ty / unit
MXZ-18TV-
Remarks
20A
EVAOPRATION
DISCHARGE, DEFROST
GAS PIPE TEMPERATURE
THREMISTOR
14-1. OUTDOOR UNIT FUNCTIONAL PARTS
MXZ-18TV MXZ-18TV -
E1
E2
1314
1
2
12
11
3
4
56
78
10
9
32
Page 33
14-2. OUTDOOR UNIT STRUCTURAL PARTS
MXZ-18TV MXZ-18TV -
E1
E2
14
13
15
1
16
17
2
18
3456789
Part numbers that are circled are not shown in the illustration.
No.Parts Name
Parts No.
T2W E87 232
1
T2W E87 521
2
M21 68N 290
3
T92 501 280
4
T2W E87 646
5
M21 21J 662
6
M21 00A 661
7
T2W E87 531
8
T2W E87 245
9
T2W G04 961
10
T2W E87 293
11
T2W E87 630
12
M21 68K 523
13
M21 68N 297
14
T2W E87 515
15
T2W E87 301
16
M21 68N 501
17
M21 61G 972
18
T2W E87 645
19
M21 PA2 642
20
FRONT PANEL ASSEMBLY
GRILLE
BASE ASSEMBL Y
COMPRESSOR
EXPANSION VALVE
STOP VALVE (LIQUID)
STOP VALVE (GAS)
BACK PANEL
SERVICE PANEL ASSEMBLY
4-WAY VALVE
SEPARATOR
OUTDOOR HEAT EXCHANGER
CONDENSER NET
TOP PANEL
MOTOR SUPPORT
OUTDOOR FAN MOTOR
PROPELLER FAN
PROPELLER FAN NUT
LEV ASSEMBL Y
STRAINER
Symbol
in Wiring
Diagram
LEV
MXZ-18TV-
1
1
1
1
1
2
2
1
1
1
1
1
1
1
1
1
1
1
1
2
12
Q'ty / unit
E1
MXZ-18TV-
11
10
E2
1
1
1
1
1
2
2
1
1
1
1
1
1
1
1
1
1
1
1
2
Remarks
SHV-130FEA
RA6V35-
33
Page 34
B
A
C
15
OPTIONAL PARTS
15-1. Different-diameter pipe
MXZ-18TV
Model name
Model code
Connected pipes
diameter (mm)
Length
A
Length
B
Length
Unit : mm (inch)
C
For differentdiameter
pipes
MAC-454JP
51H-454
{9.52 — {12.7
(3/8) (1/2)
{9.52
(3/8)
{12.7
(1/2)
69
34
Page 35
Page 36
HEAD OFFICE: MITSUBISHI DENKI BLDG.,2-2-3, MARUNOUCHI, CHIYODA-KU, TOKYO100-8310, JAPAN
CC
Copyright 2001 MITSUBISHI ELECTRIC ENGINEERING CO.,LTD.
Distributed in Dec. 2002. No.OB280 REVISED EDITION-A 16
Reprinted in Dec. 2001 No.OB280 5
Reprinted in Dec. 2001 No.OB280 50
Distributed in Mar. 2001. No.OB280 49
Made in Japan
New publication, effective Dec. 2002
Specifications subject to change without notice.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.