Mitsubishi MXZ-18TV-E1, MXZ-18TV-E2 Service Manual

Page 1
SPLIT-TYPE, HEAT PUMP AIR CONDITIONER
SERVICE MANUAL
Inverter-controlled multi system Model
Revision:
• MXZ-18TV - has been added.
• Please void OB280.
E2
No. OB280
REVISED EDITION-A
MXZ-18TV ­MXZ-18TV -
Model indication
E1
E2
CONTENTS
1. TECHNICAL CHANGES ····································2
2. PART NAMES AND FUNCTIONS······················2
3. INDOOR/OUTDOOR CORRESPONDENCE TABLE ···························3
4. INDOOR UNITS COMBINATION ·······················3
5. SPECIFICATION·················································4
6. NOISE CRITERIA CURVES······························ 5
7. OUTLINES AND DIMENSIONS························ 6
9. REFRIGERANT SYSTEM DIAGRAM················8
10. PERFORMANCE CURVES································9
11. MICROPROCESSOR CONTROL·····················14
12. TROUBLESHOOTING ······································19
13. DISASSEMBLY INSTRUCTIONS·····················29
14. PARTS LIST······················································32
15. OPTIONAL PARTS ···········································34
This manual describes technical data of outdoor unit. For the indoor unit refer to the service manuals No. OB229, OB227 REVISED EDITION-B, OB252 REVISED EDI­TION-A,OC280 REVISED EDITION-A,OC281 REVISED EDITION-A and OC165 of corresponding models.
Page 2
1
TECHNICAL CHANGES
MXZ-18RV - MXZ-18TV -
1. The combination pattern of indoor unit has increased.
2. Outside dimension of the outdoor unit changed.
3. Ball valve has changed to stop valve.
4. Accumulator has been removed.
5. Hight pressure switch has been removed.
6. Compressor has changed.
7. Refrigerant filling capacity has changed. (1.3kg ➝ 1.55kg)
MXZ-18TV - MXZ-18TV -
1.Combinations of the connectable indoor units have increased.
2. FUSE(F912) and Varistor(NR63) on Noise filter P.C. board has changed.
3. Accordance with the change, the board of E2 can be used for E1.
4. The board of E1 can not be used for E2.
E1E1
E2E1
2
PART NAMES AND FUNCTIONS
OUTDOOR UNIT
MXZ-18TV­MXZ-18TV-
E1 E2
Air outlet
Air inlet
(back and side)
Model indication
2
Page 3
3
There is no combination other than this table.
MXZ-18TV-
E1
OUTDOOR UNIT
Combination of the
connectable indoor units
07+09 07+12
07+SEH-1.6
09+09 09+12
09+SEH-1.6
12+12
MXZ-18TV-
E2
07+09
07+SLH-1
07+12 07+SEH-1.6 07+SLH-1.6
09+0.9
09+SLH-1
09+12 09+SEH-1.6 09+SLH-1.6
SLH-1+SLH-1
SLH-1+12
SLH-1+SEH-1.6
SLH-1+SLH-1.6
12+12
12+SLH-1.6
SLH-1.6+SLH-1.6
07 09
12 07+09 07+12 09+09 09+12 12+12
90 90 90 90 90 90 90 90
3.88
4.17
6.22
8.79
8.85
8.88
9.00
9.07
2.3
(0.9-2.8)
2.5
(0.9-3.0)
3.4
(0.9-3.8)
4.8
(1.49-5.25)
5.0
(1.51-5.45)
5.0
(1.51-5.45)
5.2
(1.53-5.60)
5.3
(1.55-5.70)
0.850
(0.225-1.055)
0.865
(0.225-1.125)
1.29
(0.220-1.550)
1.82
(0.370-2.11)
1.835
(0.365-2.125)
1.840
(0.370-2.130)
1.865
(0.365-2.145)
1.88
(0.370-2.190)
– – –
2.5
2.98
2.5
3.0
2.65
2.3
2.5
3.4
2.3
2.02
2.5
2.2
2.65
Indoor units combination
Unit A Unit B
Cooling capacity (kW)
Total
Outdoor unit
power consumption
(kW)
Current
(A)
Power
factor
(%)
230V
NOTE: Electrical data is for outdoor unit only.
MXZ-18TV -
E1 , MXZ-18TV - E2
NOTE: Electrical data is for outdoor unit only.
07 09
12 07+09 07+12 09+09 09+12 12+12
90 90 90 90 90 90 90 90
4.85
5.23
6.95
9.27
9.14
9.17
8.81
8.64
3.3
(0.9-4.0)
3.6
(0.9-4.5)
4.0
(0.9-4.7)
6.2
(1.53-6.70)
6.5
(1.55-7.00)
6.5
(1.55-7.0)
6.55
(1.56-7.1)
6.6
(1.58-7.2)
1.005
(0.225-1.115)
1.085
(0.225-1.195)
1.440
(0.220-1.490)
1.92
(0.300-2.030)
1.895
(0.295-2.005)
1.900
(0.300-2.010)
1.825
(0.295-1.925)
1.790
(0.290-1.840)
– – –
3.23
3.88
3.25
3.77
3.30
3.3
3.6
4.0
2.97
2.62
3.25
2.78
3.30
Indoor units combination
Unit A Unit B
Heating capacity (kW)
Total
Outdoor unit
power consumption
(kW)
Current
(A)
Power
factor
(%)
230V
INDOOR / OUTDOOR CORRESPONDENCE TABLE
4
INDOOR UNITS COMBINATION
NOTE: SLH-1AR is equivalent to class 9 (9000BTU).
SEH-1.6AR,SLH-1.6AR is equivalent to class 12 (12000BTU).
3
Page 4
5
Outdoor model
Indoor units number Indoor units total capacity (Connectable) indoor units total capacity (Simultaneous operation) Piping total length Connecting pipe length Height difference (Indoor ~ Outdoor) Height difference (Indoor ~ Indoor) Function Capacity Dehumidification Outdoor air flow Power outlet Running current Power input Auxiliary heater Crankcase heater Power factor Starting current Compressor motor current Fan motor current
Model Output Winding resistance(at20:) Model Winding resistance(at20:) Dimensions WOHOD Weight Sound level (Hi) Fan speed (Hi) Fan speed regulator Refrigerant filling capacity(R-22) Refrigerating oil (Model) Thermistor RT61 Thermistor RT62 Thermistor RT63 Thermistor RT65,66 Thermistor RT67
m m m m
kW
R/h
K /h
A A
W
A(kW)
W %
A A A
W
"
  
"
mm
kg
dB
rpm
kg
cc k" k" k" k" k"
Compressor
Electrical
data
Fan
motor
Special
remarks
Capacity System
Coefficient of performance(C.O.P)
Outdoor unit power supply
MXZ-18TV -
E1
,
MXZ-18TV -
E2
Single phase
230V,50Hz
2 Total model name 24 Total model name 24
Max. 30 (chargeless 20)
Max. 20
10 10
1,860
20
— —
90.0
9.08
0.38
SHV-130FEA (ROTARY)
1,400
U-V 0.45
V-W 0.45 W-U 0.45
RA6V35-AA
WHT-BLK 236.2 BLK-YLW 48.1
BLK-RED 224.1
800(+69)o600o300
46
630
2
1.55
350 (MS-56)
13.4 (at 100:)
10.0 (at 25:)
10.0 (at 25:)
10.0 (at 25:)
17.0 (at 50:)
Cooling
5.3 (1.55~5.7) —
9.08
1,880 (370~2,190)
8.70
2.82
48
Heating
6.6 (1.58~7.2) —
8.64
1,790 (290~1,840)
8.26
3.69
49
SPECIFICATION
NOTE: Test conditions are based on ISO 5151 (Refrigerant piping length (one way) :5m
1 Electrical data is for only outdoor unit. TEST CONDITIONS COOLING INDOOR DB27.0°C WB19.0°C
HEATING INDOOR DB20.0°C
OUTDOOR DB35.0°C WB24.0°C OUTDOOR DB 7.0°C WB 6.0°C
4
Page 5
NOISE CRITERIA CURVES6
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
APPROXIMATE TERESHOLD OF HEARING FOR CONTINUOUS NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, 0dB = 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
Test conditions.
Cooling :DB 35: WB 24: Heating :DB 7: WB 6:
Cooling
NOTCH
Heating
48
SPL(dB(A))
49
LINE
MXZ-18TV -
E1
MXZ-18TV -
E2
5
Page 6
7
OUTLINES AND DIMENSIONS
OUTDOOR UNIT
MXZ-18TV ­MXZ-18TV -
E1 E2
Drainage hole {33
23
Bolt pitch for installation
43.6
152 Air in
45.4
16
Handle
400
347.5 Air in
Air out
113
500
800
Drainage hole {33
155
Unit: mm
REQUIRED SPACE
Even if the right / left sides or back side are vacant, the top has to be at least 100mm unobstructed.
100mm or more
34
17300
WA
200mm or more
WB
330
However, either the
left / right sides or
back side should
34
40
69
17
Handle
be unobstructed.
WA In case of poorly-ventilated place, the front
or the back has to be at least 200mm unobstructed.
WB The wall may get dirty in case the air is
discharged toward it.
Liquid refrigerant pipe joint Refrigerant pipe (flared) {6.35
WA
Basically
unobstructed
100mm or more
350mm or more
300
600
Service port
165
90 65 65 65
Gas refrigerant pipe joint Refrigerant pipe (flared) {9.52
6
Page 7
8
R61
IPM
FUSE(1A)
T801
CT62
WVU
TAB61
TAB65
C65
SSR61
CN664 CN663 CN661
66
MF61
CN912CN911
21S4
CN61
R62
TAB62
V
W
U
MC
BLK
WHT
RED RED
WHT
BLK
PE
F911(1A)
BLU
ORN
YLW
TB2
BLK
BREAKER
GRN/YLW
CIRCUIT
POWER SUPPLY ~/N 230V~ 50Hz
TB1
TO INDOOR UNIT No.B CONNECTING 12V
TO INDOOR UNIT No.A CONNECTING 12V
N
L
N
3
N
3
GROUND
BLK
BLU
BLK
BLU
GRN
RED
X62
X61
X64
R64B
CT61
TAB2
TAB1
LDE
CN601CN602
CN851
TAB4
CN901
L
DS62
DS61
C61 C62
7
ORN
BLU
RED
YLW
YLW
RED
4
FUSE(20A)
ELECTRONIC CONTROL P.C. BOARD
21 2165 4321
RT65RT66RT61RT67
LEV ALEV B
CN772 CN771
43
RT62RT63
654321 3214
123
3214567
1234567
123123
NOISE FILTER P.C.BOARD
++
+
+
NAMESYMBOLNAMESYMBOL
1.About the indoor side electric wiring refer to the indoor unit electric wiring diagram for servicing.
2.Use copper conductors only (For field wiring).
3.Symbols below indicate. :Terminal block :Connector
NAMESYMBOL
NOTES:
C61 C62
C65 CT61 CT62
DS61,DS62
FUSE FUSE
F911
IPM
L
POWER-FACTOR CAPACITOR SMOOTHING CAPACITOR FAN MOTOR CAPACITOR CURRENT TRANSFORMER CURRENT TRANSFORMER DIODE MODULE FUSE(20A) FUSE(1A) FUSE(1A) POWER TRANSISTOR MODULE REACTOR
R64A,R64B
R61,R62
LEV A LEV B
21S4
MC
MF61
RT61 RT62 RT63 RT65
RESISTOR RESISTOR EXPANSION VALVE A,COIL EXPANSION VALVE B,COIL REVERSING VALVE SOLENOID COIL COMPRESSOR FAN MOTOR DISCHARGE TEMP. THERMISTOR DEFROST TEMP. THERMISTOR EVAPORATOR TEMP. THERMISTOR GAS PIPE TEMP. A THERMISTOR
RT66 RT67
SSR61
T801
TB1 TB2 X61 X62
X64 CN61 F912
GAS PIPE TEMP. B THERMISTOR FIN TEMP. THERMISTOR SOLENOID COIL RELAY TRANSFORMER TERMINAL BLOCK TERMINAL BLOCK FAN MOTOR RELAY FAN MOTOR RELAY RELAY CONNECTOR FUSE(3.15A)
SG79J657H01
R64A
F912(3.15A)
R61
IPM
FUSE(1A)
T801
CT62
WVU
TAB61
TAB65
C65
SSR61
CN664 CN663 CN661
66
MF61
CN912CN911
21S4
CN61
R62
TAB62
V
W
U
MC
BLK
WHT
RED RED
WHT
BLK
PE
F911(1A)
BLU
ORN
YLW
TB2
BLK
BREAKER
GRN/YLW
CIRCUIT
POWER SUPPLY ~/N 230V~ 50Hz
TB1
TO INDOOR UNIT No.B CONNECTING 12V
TO INDOOR UNIT No.A CONNECTING 12V
N
L
N
3
N
3
GROUND
BLK
BLU
BLK
BLU
GRN
RED
X62
X61
X64
R64
CT61
TAB2
TAB1
LDE
CN601CN602
CN851
TAB4
CN901
L
DS62
DS61
C61 C62
7
ORN
BLU
RED
YLW
YLW
RED
4
FUSE(20A)
ELECTRONIC CONTROL P.C. BOARD
21 2165 4321
RT65RT66RT61RT67
LEV ALEV B
CN772 CN771
43
RT62RT63
654321 3214
123
3214567
1234567
123123
NOISE FILTER P.C.BOARD
++
+
+
NAMESYMBOLNAMESYMBOL
1.About the indoor side electric wiring refer to the indoor unit electric wiring diagram for servicing.
2.Use copper conductors only (For field wiring).
3.Symbols below indicate. :Terminal block :Connector
NAMESYMBOL
NOTES:
C61 C62
C65 CT61 CT62
DS61,DS62
FUSE FUSE
F911
IPM
L
POWER-FACTOR CAPACITOR SMOOTHING CAPACITOR FAN MOTOR CAPACITOR CURRENT TRANSFORMER CURRENT TRANSFORMER DIODE MODULE FUSE(20A) FUSE(1A) FUSE(1A) POWER TRANSISTOR MODULE REACTOR
R64
R61,R62
LEV A LEV B 21S4
MC MF61 RT61 RT62 RT63 RT65
RESISTOR RESISTOR EXPANSION VALVE A,COIL EXPANSION VALVE B,COIL REVERSING VALVE SOLENOID COIL COMPRESSOR FAN MOTOR DISCHARGE TEMP. THERMISTOR DEFROST TEMP. THERMISTOR EVAPORATOR TEMP. THERMISTOR GAS PIPE TEMP. A THERMISTOR
RT66 RT67
SSR61
T801
TB1 TB2 X61 X62 X64
CN61
GAS PIPE TEMP. B THERMISTOR FIN TEMP. THERMISTOR SOLENOID COIL RELAY TRANSFORMER TERMINAL BLOCK TERMINAL BLOCK FAN MOTOR RELAY FAN MOTOR RELAY RELAY CONNECTOR
SG79J191H01
WIRING DIAGRAM
OUTDOOR UNIT
OUTDOOR UNIT
MODELS MXZ-18TV-
MODELS MXZ-18TV-
E1
E2
7
Page 8
9
a
Outdoor unit
b
H
H
H
REFRIGERANT SYSTEM DIAGRAM
MXZ-18TV ­MXZ-18TV -
Stop valve (with service port)
Indoor Unit B
Indoor Unit A
Stop valve (with service port)
Indoor Unit A
Indoor Unit B
E1 E2
Stop valve
Stop valve
Discharge temperature thermistor
Gas pipe temperature B thermistor
Muffler
Gas pipe temperature A thermistor
Capillary tube
{3.0{2.0400
{6
Strainer
{6
Strainer
Capillary tube {3.0{2.0400
Compressor
Muffler
4-way valve
LEV (A)
LEV (B)
{8
Capillary tube
{2.4{0.6750
{16
Evaporation temperatuer thermistor
R.V. coil heating ON cooling OFF
{12
Unit:mm
Refrigerant flow in cooling Refrigerant flow in heating
Outdoor
heat
exchanger
Defrost thermistor
Capillary tube {4.0{2.4300
MAX REFRIGERANT PIPING LENGTH
-
MXY-18TV MXY-18TV
Piping length each indoor unit (a, b) 20m Total piping length (a+b) 30m Height difference between units (H) 10m Bending point for each unit 15 Total bending point 30
It does not matter which unit is higher.
Refrigerant pipe diameter is different according to indoor unit to be connected. When using extension pipes,refer to the
tables below.
When diameter of refrigerant pipe is different from that of outdoor unit union, use optional Different-diameter pipe. For further information on Different-diameter pipe, see page BACK COVER.
class Pipe diameter
07/09
12
NOTE: SEH-1.6AR is equivalent to class 12.
E1
-
E2
Indoor unit
Extension pipe diameter
Liquid 6.35(1/4) Liquid 6.35(1/4)
Gas 9.52(3/8) Gas 9.52(3/8)
Liquid 6.35(1/4) Liquid 6.35(1/4)
Gas 12.7(1/2) Gas 12.7(1/2)
Outdoor unit union diameter
For
Indoor unit A
Indoor unit B
Unit : mm (inch)
Liquid 6.35(1/4)
Gas 9.52(3/8)
Liquid 6.35(1/4)
Gas 9.52(3/8)
8
Page 9
10
Wet-and dry-bulb thermometers
Wet-and dry-bulb thermometers
07 class
7.7
7.2
6.6
6.1
5.5
5.0
9.3
8.6
7.9
7.3
6.6
6.0
8.4
7.8
7.2
6.6
6.0
5.4
12 class
09 class
25.9
23.9
21.9
19.9
17.9
15.9
13.9
11.9
23.6
21.8
19.9
18.1
16.3
14.5
12.7
10.9
25.7
23.7
21.8
19.8
17.8
15.8
13.8
11.9
07 class
09 class
12 class
PERFORMANCE CURVES
The standard data contained in these specifications apply only to the operation of the air conditioner under normal conditions, since operating conditions vary according to the areas where these units are installed. The following information has been pro­vided to clarify the operating characteristics of the air conditioner under the conditions indicated by the performance curve.
(1) GUARANTEED VOLTAGE
198 ~ 264V
, 50Hz
(2) AIR FLOW
Air flow should be set at MAX.
(3) MAIN READINGS
(1) Indoor intake air wet-bulb temperature : °CWB (2) Indoor outlet air wet-bulb temperature : °CWB (3) Outdoor intake air dry-bulb temperature : °CDB
}
Cooling
(4) Total input: W (5) Indoor intake air dry-bulb temperature : °CDB (6) Outdoor intake air wet-bulb temperature : °CWB (7) Total input : W
Heating
}
Indoor air wet/dry-bulb temperature difference on the left side of the chart on page 10 and 11 shows the difference between the indoor intake air wet/dry-bulb temperature and the indoor outlet air wet/dry-bulb temperature for your refer­ence at service.
How to measure the indoor air wet-bulb/dry-bulb temperature difference
1. Attach at least 2 sets of wet-and dry-bulb thermometers to the indoor air intake as shown in the figure, and at least 2 sets of wet-and dry-bulb thermometers to the indoor air outlet. The thermometers must be attached to the position where air speed is high.
2. Attach at least 2 sets of wet-and dry-bulb thermometers to the outdoor air intake. Cover the thermometers to prevent direct rays of the sun.
3. Check that the air filter is cleaned.
4. Open windows and doors of room.
5. Press the EMERGENCY OPERATION switch once(twice) to start the EMERGENCY COOL(HEAT) MODE.
6. When system stabilizes after more than 15 minutes, measure temperature and take an average temperature.
7. 10 minutes later, measure temperature again and check that the temperature does not change.
INDOOR UNIT OUTDOOR UNIT
10-1. CAPACITY AND THE INPUT CURVES
9
Page 10
10-2. Capacity and input correction by inverter output frequency
0 50 100 150
0.5
1.0
1.5
0 50 100 150
0.5
1.0
1.5
0 50 100 150
0.5
1.0
1.5
0 50 100 150
0.5
1.0
1.5
0 50 100 150
0.5
1.0
1.5
0 50 100 150
0.5
1.0
1.5
0 50 100 150
0.5
1.0
1.5
0 50 100 150
0.5
1.0
1.5
0 50 100 150
0.5
1.0
1.5
0 50 100 150
0.5
1.0
1.5
0 50 100 150
0.5
1.0
1.5
<COOL>Capacity
Frequency
Hz
Frequency
<COOL>Total input
Hz Hz
<HEAT>Capacity
Frequency
Frequency
<HEAT>Total input
Hz
<COOL>Capacity
Frequency
Hz
Frequency
<COOL>Total input
Hz
<HEAT>Capacity
Frequency
0 50 100 150
0.5
1.0
1.5
Frequency
<HEAT>Total input
Hz
<COOL>Capacity
Frequency
Hz
Frequency
<COOL>Total input
Hz
<HEAT>Capacity
Frequency
Hz
Hz
Frequency
<HEAT>Total input
Hz
1. 07-class unit in single operation
2. 09-class unit in single operation
3. 12-class unit in single operation
NOTE 1 : Inverter output frequency : COOL 55Hz,HEAT 80Hz
(OUTDOOR UNIT:MXZ-18TV)
NOTE 2 : The dotted line on graphs connects the frequency range in normal operation shown by the full line and the frequency
in test run shown by the point.
10
Page 11
10-3. Outdoor low pressure and outdoor unit current
1. 07-class unit in single operation (OUTDOOR UNIT : MXZ-18TV)
NOTE:The unit of pressure has been changed to MPa on the international system of units(SI unit system).
The converted score against the traditional unit system can be gotten according to the formula below.
1(MPa • G) =10.2(kgf/ff• G)
(1) COOL operation
1Both indoor and outdoor units are under the same temperature/humidity condition.
Dry-bulb temperature(°C) Relative humidity(%)
20 50 25 60 30 70
2Air flow speed : HI 3Inverter output frequency : 55Hz
(kgf/F• Gauge)
Outdoor low pressure
(MPa•Gauge)
8
7
6
5
4
3
2
0.8
0.7
0.6
0.5
0.4
0.3
0.2
Ambient temperature(:)/ Ambient humidity(%)
20 25
18
50 60
30 70
55Hz
32
<How to work fixed-frequency operation>
1.Set emergency switch to COOL or HEAT.The switch is locat­ed on indoor unit.
2.Press emergency run ON/OFF button.
3.Compressor starts running at 55Hz (COOL) or 80Hz (HEAT).
4.Indoor fan runs at HI speed and continues for 30 minutes.
5.To cancel this operation,press emergency run ON/OFF button or any button on remote controller.
4
55Hz
3.5
3
2.5
2
Outdoor unit current (A)
1.5
(%)
(:)
0.5
Ambient temperature(:)/ Ambient humidity(%)
20 25
18
50 60
30 70
32
(:)
(%)
(2) HEAT operation
Indoor Outdoor
Set air flow to Hi speed.
Inverter output frequency is 80Hz.
DB(°C) 20.0
WB(°C) 14.5
DB(°C) 2 7 15 20.0
WB(°C) 1 6 12 14.5
8
7
6
5
4
Outdoor unit current (A)
3
2
2 5 10 15 20 25
80Hz
Ambient temperature(:)
11
Page 12
2. 09-class unit in single operation (OUTDOOR UNIT : MXZ-18TV)
NOTE: The unit of pressure has been changed to MPa on the international system of units(SI unit system).
The converted score against the traditional unit system can be gotten according to the formula below.
1(MPa • G) =10.2(kgf/ff• G)
(1) COOL operation
1Both indoor and outdoor units are under the same
temperature/humidity condition.
Dry-bulb temperature(°C) Relative humidity(%)
20 50 25 60 30 70
2Air flow speed : HI 3Inverter output frequency : 55Hz
<How to work fixed-frequency operation>
1.Set emergency switch to COOL or HEAT.The switch is locat­ed on indoor unit.
2.Press emergency run ON/OFF button.
3.Compressor starts running at 55Hz (COOL) or 80Hz (HEAT).
4.Indoor fan runs at HI speed and continues for 30 minutes.
5.To cancel this operation,press emergency run ON/OFF button or any button on remote controller.
(kgf/F• Gauge)
Outdoor low pressure
(2) HEAT operation
Indoor Outdoor
Set air flow to Hi speed.
Inverter output frequency is 80Hz.
(MPa•Gauge)
0.8
8
0.7
7
0.6
6
0.5
5
0.4
4
0.3
3
2
0.2
Ambient temperature(:)/ Ambient humidity(%)
DB(°C) 20.0
WB(°C) 14.5
18
20 25 50 60
4
55Hz
30
32
(:)
70
DB(°C) 2 7 15 20.0
WB(°C) 1 6 12 14.5
(%)
3.5
3
2.5
Outdoor unit current (A)
2
1.5
Ambient temperature(:)/ Ambient humidity(%)
18 20 25 30
50 60 70
55Hz
32
(:)
(%)
12
8
7
6
5
4
Outdoor unit current (A)
3
2
2 5 10 15 20 25
Ambient temperature(:)
80Hz
Page 13
3. 12-class unit in single operation (OUTDOOR UNIT : MXZ-18TV)
NOTE: The unit of pressure has been changed to MPa on the international system of units(SI unit system).
The converted score against the traditional unit system can be gotten according to the formula below.
1(MPa • G) =10.2(kgf/ff• G)
(1) COOL operation
1Both indoor and outdoor units are under the same
temperature/humidity condition.
Dry-bulb temperature(°C) Relative humidity(%)
20 50 25 60 30 70
2Air flow speed : HI 3Inverter output frequency : 55Hz
<How to work fixed-frequency operation>
1.Set emergency switch to COOL or HEAT.The switch is locat­ed on indoor unit.
2.Press emergency run ON/OFF button.
3.Compressor starts running at 55Hz (COOL) or 80Hz (HEAT).
4.Indoor fan runs at HI speed and continues for 30 minutes.
5.To cancel this operation,press emergency run ON/OFF button or any button on remote controller.
(kgf/F• Gauge)
Outdoor low pressure
(2) HEAT operation
Indoor Outdoor
Set air flow to Hi speed.
Inverter output frequency is 80Hz.
(MPa•Gauge)
8
7
6
5
4
3
2
0.8
0.7
0.6
0.5
0.4
0.3
0.2
DB(°C) 20.0
WB(°C) 14.5
18
Ambient temperature(:)/ Ambient humidity(%)
20 25 50 60
4
3.5
55Hz
3
2.5
2
Outdoor unit current (A)
1.5
32
30 70
DB(°C) 2 7 15 20.0
WB(°C) 1 6 12 14.5
(:)
(%)
1
Ambient temperature(:)/ Ambient humidity(%)
18 20 25 30
50 60 70
55Hz
32
(:)
(%)
13
8
7
6
5
4
Outdoor unit current (A)
3
2
2 5 10 15 20 25
Ambient temperature(:)
80Hz
Page 14
11
Compressor power factor
Indoor unit microprocessor
SSR61
Drive
circuit
Transistor
module
Indoor Unit
B
Indoor Unit
B
Comp.
Discharge temperature thermistor RT61
Evaporation temperature thermistor RT63
Gas pipe temperature thermistor RT66
Gas pipe temperature thermistor RT65
Indoor Unit
A
Indoor Unit
A
Outdoor fan motor MF61
x 61 x 62
Defrost thermistor RT62
LEV (A)
LEV (B)
Outdoor unit control microprocessor
Compressor primary current
Compressor secondary current
Fin temperature thermistor RT67
R. V. coil 21S4
Input signal
Output signal
MICROPROCESSOR CONTROL
INVERTER MULTI SYSTEM CONTROL MXZ-18TV -
MXZ-18TV -
E1 E2
14
Page 15
11-1.LEV control
Linear expansion valve (LEV) is controlled by "Thermostat ON" commands given from each unit.
Indoor unit status Stop of all indoor unit
Opening before stop 500 pulse in 15 minutes
When outdoor unit is operating, some indoor unit stops and some operates.
Thermostat OFF in
COOL or DRY mode
When the outdoor unit operation (When the other indoor unit operate): 5 pulse. When outdoor unit stops. (When the other indoor unit stops or thermo off): Maintain LEV opening before stop 500 pulse in 15 minutes
• LEV opening for each indoor unit is determined by adding adjustment in accordance with the number of operating unit and the capacity class to standard opening, based on the operation frequency: Ex.) Opening 130 pulse in standard opening 1 Minimum 80 pulse, Maximum 205
Thermostat ON in
COOL or DRY mode
pulse. (Capacity code 4 at 1 unit operation) (Capacity code 1 at 4 unit operation)
• After starting operation, adjustment in accordance with intake super heat, discharge temperature is included in standard opening. w1
Note: LEV opening in each frequency at DRY operation and COOL operation is the
same. However, velocity and compressor operation frequency controls are different. See 11-2 Operational frequency range (As far as the indoor unit velocity control goes, refer to DRY operation in MICROPROCESSOR CONTROL in the indoor unit service manual.)
• When the outdoor unit operates. (When the other indoor unit operates): 59 pulse
Thermostat OFF in HEAT mode
• When the outdoor unit stops. (When the other indoor unit stops or thermo off): Maintain LEV opening before stop 500 pulse in 15 minutes.
• LEV opening for each indoor unit is determined by adding adjustment in accordance with the number of operating unit and the capacity class to standard opening, based
Thermostat ON in HEAT mode
on the operation frequency: Ex.) Opening 120 pulse in standard opening 1 Minimum 70 pulse, Maximum 165 pulse. (Capacity code 4 at 1 unit operation) (Capacity code 1 at 4 unit operation)
• After starting operation, opening becomes the one that adjustment in accordance with discharge temperature was added to basic opening. w1
w1 LEV opening when the outdoor unit operating: Upper limit 500 pulse, Lower limit 59 pulse.
LEV opening
COOL : 5 pulse (full closed) HEAT : 59 pulse (slightly opened)
Determination of LEV standard opening in each indoor unit
• The standard opening is on the straight line, which connects an each standard point in the section where divided into seven according to the operation frequency of compressor as shown in the figure below. (LEV opening is controlled in proportion to the operation frequency.)
Note: Opening is adjusted at the standard opening according to the indoor unit conditions.
However, inclination of standard opening in each point of opening does not change with the original curve.
• Add opening provided in Difference in Capacity in the table below to the standard opening from 1 to 8, when capacity of the indoor unit is excluding code 1.
• Add opening provided in Difference in Operation number in the table below to determined LEV opening for each indoor unit, when 2, 3 or 4 indoor units are operated at the same time.
Note: Even when the adjusted standard opening exceeds the driving range from 59 to 500 pulse, actual
driving output opening is in a range from 59 to 500 pulse. < Calculation example of LEV opening > Cool operation: Compressor frequency 70Hz: 2 unit ON: 18class (170-150)p(80-60)o(70-60)+150+75-30=205 pulse
Standard opening
12345678
220 210 200 190 180 170 160 150 140
LEV opening (Pulse)
130 120
7 20 40 60 80 100 120 140
COOL
HEAT
Operation frequency of compressor (Hz) : F
15
Page 16
(1) LEV opening correction by suction super heat (COOL, DRY)
Suction superheat (S.H.)
LEV opening correction (pulse)
more than 12
10 to12
8 to 10
6 to 8
6 or less
6 4 3 2 0
Difference of superheat
LEV opening correction (pulse)
more than 9
6 to9 3to 6
6 or less
8 6 2 0
1 Suction super heat
(MIN gas pipe temperature thermistor - Evaporation temperature thermistor)
2 Each correction w 1
• (Each gas pipe temperature thermistor - Evaporation temperature thermistor)
• (Main pipe temperature thermistor - sub pipe temperature thermistor)
w 1 Perform this, when number of operation units is 2units or more w 2 When the correction opening of suction super heat is 0, correct the LEV opening by dischaege temperature.
3 Discharge temperature
COOL DRY HEAT
••
-
w 2
w 2
<Correction>
2
Code3Code2
Standard opening
Difference in capacity
Difference in operation number
12345678
COOL
HEAT
150 120
160 130
170 140
180 150
Capacity code
Indoor unit
1
07209312418
190 160
190 170
200 180
200 180
25 20
50 40
-60
-60
(Suction super heat) = (Minimum gas pipe temperature) - (Evaporation temperature)
When COOL and DRY , correct the LEV openings corrected from the table below
(2) Separate correction (COOL,DRY)
(When number of operation unit is 2 units) (a) Correction by the separate super heat
Correct the LEV separately by temperature difference between each gas pipe temperature thermistor and evaporator temperature thermistor. 1 Calculate each super heat of the unit from the expression below;
(Super heat) = (Gas pipe temperature thermistor) - (Evaporation temperature thermistor)
2 Select a minimum super heat from among them. 3 Correct an each LEV is corrected opening is corrected by difference between each super heat and minimum super
heat.
16
Page 17
(3) LEV opening correction by discharge temperature
Operation frequency of compressor
Minimum ~ 20
21 ~ 33 34 ~ 46 47 ~ 59 60 ~ 72 73 ~ 85 86 ~ 98
97 ~ 111
111 ~ Maximum
Single
40 40 45 45 50 55 65 70 75
Double
40 40 45 45 50 55 65 70 75
Single
40 45 50 55 60 65 70 75 75
Double
40 45 50 55 60 65 70 73 73
Number of operating unit. Number of operating unit.
COOL, DRY HEAT
Discharge temperature (;)
LEV opening correction (pulse)
more than Target discharge temperature+11 Target discharge temperature+11 to Target discharge temperature+8 Target discharge temperature+8 to Target discharge temperature+5 Target discharge temperature+5 to Target discharge temperature+2 Target discharge temperature+2 to Target discharge temperature-2 Target discharge temperature-2 to Target discharge temperature-5 Target discharge temperature-5 to Target discharge temperature-8 Target discharge temperature-8 to Target discharge temperature-11 Target discharge temperature-11 or less
COOL
10
4 2 1 0
-1
-2
-5
-8
HEAT
8 2 1 1 0
-1
-1
-2
-6
DRY
Min. Max. Rated Min. Max.
Defrost
Rated
Note: When the fan speed of indoor unit is total Lo notch, the maximum frequency is rated frequency.
COOL
HEAT
Number of
operating
unit
1 2 3 2 3 4 5 6 7
30
30
70 80
100
120
55 61 85
108
30 41 53
723030
100 100 120
120
100 100 100
100
80 85 94
120
1
2
capacity
cord
When LEV correction output is 0 pulse by the suction super heat at cool or dry operation, or dry operating, correct LEV is cor­rected according to the following table.
The target discharge temperature is determined according to frequency zone and number of operation unit of the compressor.
Correct the LEV opening according to difference between the target discharge temperature and discharge temperature.
11-2.Operational frequency range
11-3.Heat defrosting control
(1) Conditions to enter defrosting mode
1. When temperature of defrosting thermistor is -3; or less.
2.When specified non-defrosting time, is counted in the control p.c.board is satisfied.
(Total time of compressor operating) Going to defrosting mode at both condition of 1 and 2.
(2) Defrosting operation
1. Compressor stops for 50 seconds, Indoor fan is off, Defrosting lamp lights
2.4-way valve reverses flow, Compressor operates by the frequency in heat defrosting control.
3. After compressor stops for 35 seconds, 4-way valve reverses flow, then defrosting finishes.
(3) Conditions to finish defrosting mode
1. When the defrosting thermistor temperature is 8; or more.
2. When it has spent 10 minutes for defrosting.
Defrosting finishes at condition of 1 or 2.
17
Page 18
11-5.Discharge temperature protection control
COOL
Fan speed
Up
Down
Up
Down
Single Double
Mode
HEAT
Indoor unit operation
<Relation between compressor frequency and fan speed.>
60Hz 50Hz 60Hz 50Hz
60Hz 50Hz 60Hz 50Hz
Up
Down
Fan speed
Hi
Low
Compressor frequencyMin. Max.
Discharge temperature thermistor Indoor pipe temperature thermistor Defrost thermistor Evaporation temperature thermistor Gas pipe temperature thermistor Fin temperature thermistor Capacity code
Purpose
Protection
Defrosting Protection
Defrosting
Control Control
Protection
Control
Compressor LEV
Outdoor fan motor
Reversing
valve
Sensor
Actuator
This protection controls the compressor ON/OFF and operation frequency according to temperature of the discharge temp. thermistor.
(1) Compressor ON/OFF When temperature of the discharge temp. thermistor exceeds 116;, the control stops the compressor. When temperature of the discharge temp. thermistor is 80; or less, the controls starts the compressor.
(2) Compressor operation frequency When temperature of the discharge temp. thermistor is expected to be higher than 116;, the control decreases 12Hz from the
current frequency.
When temperature of the discharge temp. thermistor is expected to be higher than 111; and less than 116;, the control
decreases 6Hz from the current frequency.
When temperature of the discharge temp. thermistor is expected to be higher than 104; and less than 111;, the control is set
at the current frequency.
11-6.Refrigerant recovery control on heating
<Control status>
The control performs when the following status are satisfied everything;
• When there is 1 unit or more not operating indoor unit on heat operation. (Excluding thermo OFF)
• When discharge temperature becomes 107; or more.
• When it passed 60 minutes or more since the operation has started or the last refrigerant recovery has controlled.
<Control details>
LEV opening, which adjusts to not operating indoor unit, is considered to be 80 pulse.
<Control finish status>
The control finishes either as follows. However, the LEV opening is considered to be 59 pulse.
• When it passed 60 seconds since the control has started.
• When the discharge temperature is 90; or less.
11-7.Outdoor fan control
Fan speed is switched according to a number of operating indoor unit and the compressor frequency.
Note
•When operation, fan speed of Hi/ Low mode changes to VHi/ Hi mode by promoting those fan speeds respectively by 1 step after defrosting is operated. This control is cleared, when the compressor off.
•When overheat protection of P.C. board temperature or fin temperature operates, the outdoor fan speed is fixed to VHi mode regardless of compressor frequency. Also, when the overheat protection is cleared, the fan speed is back to normal
•When the indoor coil thermistor is 57; or more on HEAT operation, fan speed is fixed to Low notch . Or, the indoor coil thermistor is 45; or less on HEAT operation, fan speed is back to normal.
11-8.Relation between main sensor and actuator
Relation between main sensor and actuator.
18
Page 19
12 TROUBLESHOOTING
Lead wiring
Housing point
Operation start
Check the outdoor unit LED indicator
A Check of power supply See page 22.
• Indoor unit serial signal error B Check of serial signa See page 22.
• Cool or HEAT opereation only C Check of R.V.coil See page 23.
• When cooling, room does not cool. E Check of inverter, compressor See page 24.
• When cooling, heat exchanger of non-operating indoor unit frosts.
•When heating, non operating indoor unit gets warm. D Check of LEV See page 24.
• When cooling, dew drops in the non-operating indoor unit Check of mis­piping.
• When heating, room doed not get warm. E Check of inverter,compressor See page 24. Check mis-piping Shortage of capacity
Refer to indicator list See page 20, 21.
OFF
Both LED 1 and LED 2 lighting
• Check the indoor unit with referring to the indoor unit service manual, and confirm that there is any problem in the indoor unit. Then, check the outdoor unit with referring to this page.
LED 1 or LED 2 has blinked.
12-1. Cautions on troubleshooting
1. Before troubleshooting, check the following:
1) Check the power supply voltage.
2) Check the indoor/outdoor connecting wire for mis-wiring.
2. Take care the following during servicing.
1) Before servicing the air conditioner, be sure to first turn off the remote controller to stop the unit, and then after con­firming the horizontal vane is closed, turn off the breaker and / or disconnect the power plug.
2) Be sure to unplug the power cord before removing the front panel, the cabinet, the top panel, and the electronic con­trol P.C. board.
3) When removing the electronic control P.C. board, hold the edge of the board with care NOT to apply stress on the components.
4) When connecting or disconnecting the connectors, hold the housing of the connector. DO NOT pull the lead wires.
3. Troubleshooting procedure
1) First, check if the OPERATION INDICATOR lamp on the indoor unit is flashing on and off to indicate an abnormality.
To make sure, check how many times the abnormality indication is flashing on and off before starting service work.
2) If the electronic control P.C. board is supposed to be defective, check the copper foil pattern for disconnection and the
components for bursting and discoloration.
3) When troubleshooting, refer to the flow chart on page 19 and the check table on page 20, 21.
12-2. Instruction of troubleshooting
19
Page 20
Troubleshooting check table <OUTDOOR UNIT>
LED 1 (red)
Lighting
Indication
LED 1
Lighting
Lighting
6 times Goes out
Lighting
LED 1
Lighting
Lighting
(red)
Indication
(red)
LED 2
(Yellow)
Twice
7 times
9 times
LED 2
(Yellow)
3 times
4 times
LED 2 (yellow)
Lighting
Symptom: Outdoor unit does not operate.
Abnormal point Detecting method Check points
Outdoor power system
Outdoor control system
Indoor unit and LEV
DC voltage sensing cir­cuit
Abnormal point Detecting method Check points
Discharge temperature thermistor
Fin temperature ther­mistor
When the compressor operation has been interrupted by overcurrent protection continuously three times within 1 minute after start-up.
When the nonvolatile memory data cannot be read properly on the out­door electronic control P.C. board.
When the drain abnormality is detected in the indoor unit and the indoor unit coil temperature is too low, or when any abnormality is detected in the components of indoor unit.
When DC voltage sensing circuit detects 57V or below or 395V or above
Symptom: Outdoor unit repeats to stop and restart in 3 minutes
When a short or open circuit occurs in the discharge temperature ther­mistor during compressor running.
When a short or opern circuit occurs in the fin temperature thermistor during compressor running.
Error mode
Normal
• Check the inverter / compressor. Refer to “E” on page 24.
• Replace the outdoor electronic control P.C. board.
• Check the abnormality indication on the indoor unit.
• Check the LEV.
Refer to “D” on page 24.
• Replace the outdoor electronic control P.C. board.
• Check the characteristic of the discharge temperature thermistor.
Refer to “F” on page 25.
• Check the connector. (CN663)
• Check the characteristic of the fin temper­ature thermistor.
Refer to “F” on page 25.
• Check the connector. (CN664)
Lighting
Lighting
Lighting
Lighting
3 times Goes out
4 times Goes out
4 times Goes out
5 times
10 times
11 times
12 times
Twice Goes out
P.C. board temperature thermistor
Evaporation tempera­ture thermistor
Gas pipe temperature A thermistor
Gas pipe temperature B thermistor
Over current protection When over current is applied to the power module.
Discharge temperature overheat protection
Fin temperature over­heat protection
P.C. board temperature overheat protection
When a short or open circuit occurs in the P.C. board temperature ther­mistor during compressor running.
When a short or open circuit occurs in the evaporation temperature ther­mistor during compressor running.
When a short or open circuit occurs in the gas pipe temperature Ather­mistor during compressor running.
When a short or open circuit occurs in the gas pipe temperature B ther­mistor during compressor running.
When the discharge temperature thermistor detects 116: or above. (Protection will be released at 100: or below.)
When the fin temperature thermistor detects 91: or above.
When the P.C. board temperature thermistor detects 79: or above.
• Replace the outdoor electronic control P.C. board.
• Check the characteristic of the evaopra­tion temperature thermistor.
Refer to “F” on page 25.
• Check the connector. (CN663)
• Check the characteristic of the gas pipe temperature A thermistor.
Refer to “F” on page 25.
• Check the connector. (CN661)
• Check the characteristic of the gas pipe temperature B thermistor.
Refer to “F” on page 25.
• Check the connector. (CN661)
• Check the inverter / compressor.
Refer to “E” on page 24.
• Check the amount of gas.
• Check the indoor / outdoor air flow for short cycle.
• Check the indoor unit air filter for clogging.
• Check the amount of gas and the refriger­ant cycle.
• Check the outdoor unit air passage.
• Check the outdoor unit air passage.
• Check the outdoor fan motor.
Refer to “G” on page 25.
• Check the power module.
• Check the outdoor unit air passage.
• Check the outdoor fan motor.
Refer to “G” on page 25.
• Replace the outdoor electronic control P.C. board.
20
Page 21
Indication
W
U
V
WHT
RED
BLK
WHT
Protector specification
Short Open
87I15: 135I5:
YLW
P
ORN RED
BLK
LEV
WHT
RED
YLW
BRN
ORN
BLU
LED 1
LED 2
(red)
(Yellow)
Once Lighting
Symptom: Oudtoor unit operates (The compressor operates at reduced frequency)
Abnormal point Detecting method Check points
Current protection When the outdoor unit input current exceeds 15.5A.
Overload protection When the compressor load exceed the specified value.Twice High pressure protec-
tion Defrosting in cooling Discharge temperature
protection Low discharge tempera-
ture protection
LED 2
Defrost thermistor
Power factor detection When the compressor power factor cannot be detected. • Check the compressor wiring.6 times Lighting
When indoor pipe temperature exceeds 55: during heating.
When indoor pipe temperature falls to 6: or below during cooling.
When the discharge temperature exceeds 111:. When the state with low discharge temperature of which 50.4: or below
in cool and 48.8: or below in heat for 20 minutes.
Abnormal point Detecting method Check points
When a short or open circuit occurs in the defrost thermistor during heat­ing.
3 times
3 times
4 times
7 times
Indication
LED 1
(red)
5 times
Lighting
Lighting
Lighting
Lighting
Lighting
(Yellow)
Lighting
12-4. Trouble criterion of main parts
Part name Check method and criterion
Defrost thermistor Evaporation / Gas pipe temperature thermistor
Measure the resistance using a tester. (Part temperature -10°C ~ 40°C)
These symptoms do not mean any abnor­mality of the product, but check the follow­ing points.
• Air filter clogging.
• Amount of gas.
• Short cycle of indoor / outdoor air flow.
Symptom: Outdoor unit operates
• Check the characteristic of the defrost temperature thermistor.
Refer to “F” on page 25.
• Check the connector. (CN663)
Normal abnormal
5k~ 55k Opened or short-circuited
Discharge temperature thermistor
Compressor
Outdoor fan motor
R. V. coil
Linear expansion valve
Measure the resistance using a tester, after warming up the thermistor by holding by hand. (Part temperature : 20°C ~40°C)
Normal abnormal
100k~ 250k Opened or short-circuited
Measure the resistance between terminals using a tester. (Winding temperature : -10°C ~ 40°C)
Normal abnormal
1Each phase 0.39~ 0.50 Opened or short-circuited
Measure the resistance between lead wires using a tester. (Part temperature : -10°C ~ 40°C)
WHT - BLK
BLK - YLW BLK - RED
Normal
208.4~ 254.8
42.4~ 51.9
197.7~ 241.7
abnormal
Opened or
short-circuited
Measure the resistance using a tester. (Part temperature -10°C ~ 40°C)
Normal abnormal
2.6k~ 3.3k Opened or short-circuited
Measure the resistance using a tester.(Part temperature -10°C ~ 40°C)
Lead wire color Normal
Abnormal WHT - RED RED - ORN YLW - BRN
Opened or short-circuited37.4~ 53.9
BRN - BLU
P Inner protector
21
Page 22
Outdoor unit does not operate. (LED display: display OFF)
AA
Check of power supply
Start
Check the connecting of main circuit parts .
Turn on power supply
Is there voltage of 230V AC in the power supply terminal block?
Yes
Is there voltage of 325V DC across the smoothing capacity?
Yes
Replace the outdoor electronic control P. C. board.
Outdoor unit does not operate. (LED display: Both LED1 and LED2 lighting)
BB
Check of outdoor unit serial signal
Start
No
No
Check the power supply cable.
Is there voltage of 230V AC across the input terminal part in the diode module (DS61)?
Yes
Check the main circuit parts and replace it.
Replace the noise
No
filter P. C. board
1. Check the indoor unit with referring to the indoor unit service manual.
2. Turn off the power supply of the indoor and outdoor unit and return the indoor/ outdoor unit connecting wire to former original.
3. Check the connection of indoor/ outdoor unit connecting wire in the outdoor unit terminal block, and check the connection of the connector (CN601: unit A, CN602: unit B) in the control P. C. board
4. Disconnect the lead wire to the compressor. Turn on the power supply (indoor/ outdoor unit) 3 minutes later, EMERGENCY OPERATION starts.
Is there voltage from 5V DC - 10V DC between No. 3 (+) and N (-) in the outdoor terminal block.
Yes
Recheck a connected circumstance of the indoor/ outdoor unit connecting wire.
No
Replace the outdoor electronic control P. C. board.
22
Page 23
The cooling operation or heating operation does not operate. (LED display: Both LED1 and LED2 lighting)
CC
Check of R. V. coil
• When heating operation does not work.
Start
1. Disconnect the lead wire leading to the compressor.
2. Turn on power supply to the indoor and outdoor unit, three minutes later EMERGENCY OPERATION (HEAT operation) starts.
Is there voltage of 230V AC between pin1 and pin 2 at connector CN912?
Yes
Turn off power supply of indoor and outdoor unit.
Disconnect the connector CN912 in noise filter P. C. board, and measure the resistance of R. V. coil to check the integrity.
Yes
Replace the 4-way valve
• When cooling operation does not work.
Start
1. Disconnect the lead wire leading to the compressor.
2. Turn on power supply to the indoor and outdoor unit, three minutes later EMERGENCY OPERATION (COOL operation) starts.
No
Replace the R. V. coil
No
1. Turn off power supply of indoor and outdoor unit, and disconnect the connector (CN851) in the outdoor electronic control P. C. board.
2. Turn on power supply to the indoor and outdoor unit, three minutes later EMERGENCY OPERATION (HEAT operation) starts.
Is there voltage 12V DC between the connector CN851 pin 3 (+) and pin 4 (-)?
Yes
Replace the noise filter P. C. board.
No
Replace the electronic control P. C. board.
Is there voltage of 230V AC between pin1 and pin 2 at connector CN912?
Yes
1. Turn off power supply of indoor and outdoor unit, and disconnect the connector (CN851) in the outdoor electronic control P. C. board.
2. Turn on power supply to the indoor and outdoor unit, three minutes later EMERGENCY OPERATION (COOL operation) starts.
Is there voltage 12V DC between the connector CN851 pin 3 (+) and pin 4 (-)? W1
Yes
Replace the outdoor electronic control P. C. board.
No
Replace the noise filter P. C. board.
W1If the connector CN912 is not connected or R. V. coil is open, voltage
occurs between terminals even when the control is OFF.
No
Replace the 4-way valve
23
Page 24
• When cooling, heat exchanger of non-operating indoor unit frosts.
• When heating, non-operating indoor unit get warm.
DD
Check of LEV
Start
Turn on power supply to the outdoor unit after checking LEV coil is mounted to the LEV body securely.
LED display:
LED1 LED2
Lighting Lighting
6 time Goes out
Is "click - click" sound heard? Or, do you feel vibration of the LEV coil with a hand?
No
Disconnect the connector (CN771: unit A, CN772: unit B), and measure the resistance of LEV coil to check the integrity.
No
Replace the LEV coil.
• When heating, room does not get warm.
• When cooling, room does not get cool.
EE
Check of inverter/ compressor
Start
Disconnect the lead wire to the compressor at terminals, and turn on power supply to the indoor and outdoor unit. Three minutes later, EMERGENCY OPERATION starts.
Measure the voltage between each leading to the compressor. U (BLK) - V (WHT) V (WHT) - W (RED) W (RED) - U (BLK) Output voltage COOL: 100V(58Hz), HEAT: 100V (58Hz) Is voltage output? W1
Yes
Is output balanced?
Yes
Turn off power supply of indoor and outdoor unit, and measure the compressor winding resistance between the compressor terminals. Is there resistance of 0.53" to 0.66" between the each terminals?
Yes
No
LED display:
W1 • After the outdoor fan starts running, wait for 1 minutes or more before
measuring the voltage.
•The output voltage values in the above table have the tolerance of i20%.
No
Yes
Yes
Replace the outdoor electronic control P. C. board
No
Normal
Replace the outdoor electronic control P. C. board
LED1 LED2 Lighting Lighting Lighting
Twice
Replace the compressor.
Twice
Goes out
Return the lead wire of compressor to former, and turn on power supply to indoor and outdoor unit. Three minutes later EMERGENCY OPERATION starts.
Clarify the causes by counting time until the inverter stops. 0 to 10 seconds: compressor rare short 10 to 60 seconds: compressor lock 60 seconds to 5minutes: refrigerant circuit defective 5 minutes or more: normal
24
Page 25
• When thermistor is abnormal. (When the LED display is a table below.)
FF
Check of outdoor unit thermistor
Start
Disconnect the connector in the outdoor electronic control P. C. board (see below table), and measure the resistance of thermistor to check whether the thermistor is normal or not.
Normal
Reconnect the connector (CN661, CN663 and CN664) and disconnect the lead wire leading to the compressor. Turn on power supply to the indoor and outdoor unit. Three minutes later EMERGENCY OPERATION starts.
Does thermistor operate 10 minutes or more though the thermistor abnormality is not displayed?
Yes
Normal
Thermistor Discharge temperature thermistor Defrost thermistor Evaporation temperature thermistor Gas pipe temperature A thermistor Gas pipe temperature B thermistor Fin temperature thermistor
• Fan motor does not operate. Or fan motor stops at once after fan motor operate.
GG
Check of outdoor fan motor
Symbol
RT61 RT62 RT63 RT65 RT66 RT67
No
Replace the outdoor electronic control P. C. board.
Connector, Pin No. Between CN663 pin3 and pin4 Between CN663 pin1 and pin2 Between CN663 pin5 and pin6 Between CN661 pin1 and pin2 Between CN661 pin3 and pin4 Between CN664 pin1 and pin2
Abnormal
Replace the thermistor
Start
Check the connection of connector (CN851) in the fan motor relay connector and outdoor electronic control P. C. board at the noise filter P. C. board and connector (CN901) in the noise filter board.
Disconnect the fan motor connector, and measure the resistance of the fan motor winding to check the winding characteristic.
Normal
1. Disconnect the lead wire leading to the compressor. Turn on power supply to the indoor and outdoor unit. Three minutes later, EMERGENCY OPERATION starts.
2. Check the voltage between pin 1 and pin 4, pin 1 and pin 5 at the fan motor connector.
Is there voltage of 230V AC?
No
1. Turn off power supply of the indoor and outdoor unit, and disconnect the connector (CN851).
2. Is the voltage 0V, when the voltage between CN851 pin3 (+), pin7 (-), pin6 (-) are
measured after the power supply is turned on the outdoor unit?
Yes
Is there voltage of 12V DC between CN851 pin3 (+) and pin6 (-), when power supply turns on the indoor unit and EMERGENCY OPERATION starts in three minutes.
Yes
Replace the noise filter P. C. board
Yes
Abnormal
No
No
Replace the fan motor
Replace the oudtoor electronic control P. C. board
25
Page 26
HH
The other cases
Indoor unit dose not operate. (difference modes)
1
• When you try to run two indoor unit simultaneously, one for cooling and the other for heating, the unit which transmits signal to the outdoor units earlier decides the operation mode. The other unit indicates as shown in the figure below.
• When the above situation occurs, set all the indoor units to the same mode, turn OFF the indoor units, and then turn them back ON.
• Though the top of the indoor unit sometimes gets warm, this does not mean malfunction. The reason is that the refrigerant gas continuously flows into the indoor unit even while it is not operating.
OPERATION INDICATOR
Lighting Flashing
26
Page 27
-20 -10 0 10 20 30 40
0
10
20
30
40
50
60
70
80
90
100
Temperature(:)
Gas pipe temperature thermistor (RT65,66)
Evaporation temperature thermistor (RT63)
Temperature(:)
Discharge temperature thermistor (RT61)
0 102030405060708090100110120
0
100
200
300
400
500
600
700
0 1020304050607080
0
20
40
60
80
100
120
140
160
180
200
Temperature(:)
Fin temperature thermistor (RT67)
Resistance(k")
Resistance(k")
Resistance(k")
TEST POINT DIAGRAM AND VOLTAGE MXZ-18TV
-
MXZ-18TV -
,
E2E1
Outdoor Electronic control P.C.board
Linear expansion valve (LEV)
12V DC pulse wave
Linear expansion valve (LEV)
12V DC pulse wave
325V DC
(
Gas pipe temperature Athermistor (RT65)
(
Gas pipe temperature B thermistor (RT66)
Defrost temperature thermistor (RT62)
(((
Discharge temperature thermistor (RT61)
Evaporation temperature thermistor (RT63)
(
Fin temperature thermistor (RT67)
R.V. coil 12V DC
Current Limit Relay 12V DC
Outdoor fan Hi 12V DC
Outdoor fan Lo 12V DC
Room A
(
Room B
(
LED monitor indication (LED 1)
LED monitor indication (LED 2)
Serial signal Room B 5 ~ 10V DC
Serial signal Room A 5 ~ 10V DC
27
Page 28
Noise filter P.C.board
E1
MXZ-18TV
230V AC 50Hz Input
Outdoor Fan Fan speed “Hi” 230V AC
-
Outdoor Fan Fan speed “Lo” 230V AC
230V AC 50Hz Output
Reversing valve 230V AC
MXZ-18TV -
230V AC 50Hz Input
Outdoor Fan Fan speed “Lo” 230V AC
E2
230V AC 50Hz Output
Outdoor Fan Fan speed “Hi” 230V AC
FUSE(F911)AC250V 1A R.V.coil 230V AC FUSE(F912)AC250V 3.15A
28
Page 29
13
DISASSEMBLY INSTRUCTIONS
MXZ-18TV - ,MXZ-18TV -
E2E1
OUTDOOR UNIT
OPERATING PROCEDURE
1. Removing the top panel ~ back panel
(1) Remove the screws fixing the top panel and remove it.
(Photo 1)
(2) Remove the screw fixing the service panel, next pull down
the service panel and remove it from the cabinet. (Photo 2) (3) Remove the screws fixing the front cover and remove it. (4) Remove the inside and outside connection electric wire. (5) Remove the screws fixing the back panel and remove it.
Photo 2
4 Hooks
2. Removing the inverter assembly
(1) Remove the top panel, front panel, and service panel. (2) Remove the inside and outside connection electric wire, next
remove the back panel. (3) Disconnect the connector of outdoor fan motor (CN911),
R.V. coil (CN912) in the noise filter P.C. board.
Disconnect the connector of discharge / defrost / evapora-
tion temperature thermistor (CN663), gas pipe temperature
thermistor (CN661), LEV A(CN771), LEV B (CN772) in the
electronic control P.C. board. (4) Remove the compressor relay connector. (Photo 3) (5) Remove the two screws fixing the relay panel, and remove
the inverter assembly. (Photo 3)
Photo 1
Front panel
Photo 3
PHOTOS
Top panel
Back panel
Screw of the service panel
Service panel
Screw of the
relay panel
3. Removing the inverter P.C. board
(1) Remove the top panel, front panel, and service panel. (2) Remove all the connectors the lead wire and the earth wire
on the electronic control P.C board. (3) Remove the compressor relay connector. (4) Remove the two screws fixing the heat sink, and pull up the
inverter P.C. board. (5) Remove the screws fixing the transistor module. (6) Remove the inverter P.C. board.
4. Removing the noise filter
(1) Remove the top panel, front cover, and service panel. (2) Remove all the connectors the lead wire and earth wire on
the electronic control P.C. board. (3) Remove the two hooks, then remove the noise filter P.C.
board.
29
Photo 4
Inverter P.C. board
Compressor connector
Screws of the heat sink
Noise filter P.C. board
Hooks
Page 30
OPERATING PROCEDURE
5. Removing the 4-way coil
(1) Remove the top panel, front cover and service panel. (2) Remove the inside and outside connection electric wire, next
remove the back panel.
(3) Remove 4-way coil and disconnect the noise filter P.C. board
connectors CN912
6. Defrost, Discharge temperature thermistor
(1) Remove the top panel, front cover, service panel. (2) Remove the inside and outside connection electric wire, next
remove the back panel. (3) Remove the connector CN663 on inverter P.C. board. (4) Remove the defrost thermistor and remove the discharge
temperature thermistor on the compressor. (Photo 5, 6)
7. Fin temperature thermistor
(1) Remove the top panel, front cover, service panel. (2) Remove the inside and outside connection electric wire, next
remove the back panel. (3) Remove all the connectors the lead wire and the earth wire
on the electronic control P.C. board. (4) Remove the compressor relay connector. (Photo 3) (5) Remove the two screws fixing the heat sink, and pull up the
inverter P.C. board. (Photo 4) (6) Remove the screws fixing the transistor module. (Photo 4) (7) Remove the screws the fin temperature thermistor, and
remove it. (Photo 7)
PHOTOS
Photo 5
Discharge temperature thermistor
Photo 6
8. Removing the fan motor
(1) Remove the top panel, front cover. (2) Remove the fan motor connectors (CN911) on the noise fil-
ter P.C. board. (3) Remove the propeller fan. (4) Remove the screws fixing the fan motor and remove it.
Photo 7
Photo 8
Fan motor
Defrost thermistor
Inverter board
Fin temperature thermistor
Screws of fan motor
30
Propeller fan
Page 31
OPERATING PROCEDURE PHOTOS
9. Remove the compressor
(1) Remove the top panel, front cover, service panel. (2) Remove the inside and outside connection electric wire,
next remove the back panel. (3) Remove the inverter assembly. (4) Can have the service of compression, 4-way and other
refrigerant circuit..
(5) Remove then the part (four places) which welds it when
you leave 4-way. (Photo 9)
Photo 9
Welded part
31
Page 32
14
1 2 3 4 5
6 7 8
9 10 11 12 13 14 15 16
FIN TEMPERATURE THERMISTOR DIODE STACK REACTOR CONNECTOR POST ASSY NOISE FILTER P.C. BOARD NOISE FILTER P.C. BOARD FUSE THERMISTOR SET GAS PIPE TEMPERATURE THERMISTOR SET R.V. COIL TERMINAL BED TERMINAL BED ELECTRONIC CONTROL P.C. BOARD POWER FACTOR CAPACITOR SMOOTHING CAPACITOR FUSE FUSE&VARISTOR
RT67
DS61, DS62
L
RT61,RT62,RT63
RT66, RT65
21S4
TB2 TB1
C61 C62
F911
F912,NR63
1 2 1 1 1
1 1 1 1 1 1 1 1 1 1
No. Parts Name
Symbol
in Wiring
Diagram
Parts No.
Q'ty / unit
MXZ-18TV-
Remarks
20A
EVAOPRATION DISCHARGE, DEFROST GAS PIPE TEMPERATURE THREMISTOR
1A 250V
3.15A 250V
E1
T2W E87 308 T2W E45 447 M21 68K 337 T2W E87 471 T2W E87 424 T2W G04 424 T2W E99 382 T2W E87 309 T2W E87 306 T2W E87 389 T2W E64 376 T2W E75 375 T2W E87 451 T2W E45 357 T2W E75 356 T2W E66 382 T2W E99 313
MXZ-18TV-
E2
1 2 1 1
1 1 1 1 1 1 1 1 1 1 1 1
PARTS LIST
14-1. OUTDOOR UNIT FUNCTIONAL PARTS MXZ-18TV ­MXZ-18TV -
E1 E2
1314
1
2
12
11
3
4
5 6
7 8
10
9
32
Page 33
14-2. OUTDOOR UNIT STRUCTURAL PARTS MXZ-18TV ­MXZ-18TV -
E1 E2
14
13
15
1
16 17
2
18
3 4 5 6 7 8 9
Part numbers that are circled are not shown in the illustration.
No. Parts Name
Parts No.
T2W E87 232
1
T2W E87 521
2
M21 68N 290
3
T92 501 280
4
T2W E87 646
5
M21 21J 662
6
M21 00A 661
7
T2W E87 531
8
T2W E87 245
9
T2W G04 961
10
T2W E87 293
11
T2W E87 630
12
M21 68K 523
13
M21 68N 297
14
T2W E87 515
15
T2W E87 301
16
M21 68N 501
17
M21 61G 972
18
T2W E87 645
19
M21 PA2 642
20
FRONT PANEL ASSEMBLY GRILLE BASE ASSEMBL Y COMPRESSOR EXPANSION VALVE STOP VALVE (LIQUID) STOP VALVE (GAS) BACK PANEL SERVICE PANEL ASSEMBLY 4-WAY VALVE SEPARATOR OUTDOOR HEAT EXCHANGER CONDENSER NET TOP PANEL MOTOR SUPPORT OUTDOOR FAN MOTOR PROPELLER FAN PROPELLER FAN NUT LEV ASSEMBL Y STRAINER
Symbol
in Wiring
Diagram
LEV
MXZ-18TV-
1 1 1 1 1 2 2 1 1 1 1 1 1 1 1 1 1 1 1 2
12
Q'ty / unit
E1
MXZ-18TV-
11
10
E2
1 1 1 1 1 2 2 1 1 1 1 1 1 1 1 1 1 1 1 2
Remarks
SHV-130FEA
RA6V35-
33
Page 34
B
A
C
15
OPTIONAL PARTS
15-1. Different-diameter pipe
MXZ-18TV
Model name
Model code
Connected pipes
diameter (mm)
Length
A
Length
B
Length
Unit : mm (inch)
C
For different­diameter pipes
MAC-454JP
51H-454
{9.52 — {12.7 (3/8) (1/2)
{9.52
(3/8)
{12.7
(1/2)
69
34
Page 35
Page 36
HEAD OFFICE: MITSUBISHI DENKI BLDG.,2-2-3, MARUNOUCHI, CHIYODA-KU, TOKYO100-8310, JAPAN
CC
Copyright 2001 MITSUBISHI ELECTRIC ENGINEERING CO.,LTD. Distributed in Dec. 2002. No.OB280 REVISED EDITION-A 16 Reprinted in Dec. 2001 No.OB280 5 Reprinted in Dec. 2001 No.OB280 50 Distributed in Mar. 2001. No.OB280 49 Made in Japan
New publication, effective Dec. 2002 Specifications subject to change without notice.
Loading...