Mitsubishi MUZ-SF35VE-E2, MUZ-SF25VE, MUZ-SF25VEH, MUZ-SF35VE, MUZ-SF35VEH Service Manual

...
SERVICE MANUAL
CONTENTS
1. TECHNICAL CHANGES ··································· 3
2. PART NAMES AND FUNCTIONS ····················· 4
3. SPECIFICATION ················································ 5
4. NOISE CRITERIA CURVES ······························ 6
5. OUTLINES AND DIMENSIONS ························ 8
6. WIRING DIAGRAM ············································ 9
8. PERFORMANCE CURVES ····························· 13
9. ACTUA TOR CONTROL ··································· 27
10. SERVICE FUNCTIONS ···································· 28
11. TROUBLESHOOTING ····································· 28
12. DISASSEMBLY INSTRUCTIONS ···················· 45
Models
SPLIT-TYPE AIR CONDITIONERS
NOTE: RoHS compliant products have <G> mark on the spec name plate.
HFC
utilized
R410A
No. OBH629
REVISED EDITION-A
OUTDOOR UNIT
Indoor unit service manual MSZ-SF•VE Series (OBH600)
PARTS CATALOG (OBB629)
MUZ-SF25VE MUZ-SF25VEH MUZ-SF35VE MUZ-SF35VEH MUZ-SF42VE MUZ-SF42VEH
MUZ-SF25VE
-
E1
MUZ-SF42VE
-
E1
MUZ-SF25VE
-
E2
MUZ-SF42VE
-
E2
MUZ-SF25VEH
-
E1
MUZ-SF42VEH
-
E1
MUZ-SF35VE
-
E1
MUZ-SF50VE
-
E1
MUZ-SF35VE
-
E2
MUZ-SF50VEH
-
E1
MUZ-SF35VEH
-
E1
Revision A:
• MUZ-SF25/35/42VE - E2 have been added. Please void OBH629.
2
<Preparation before the repair service>
Prepare the proper tools. Prepare the proper protectors. Provide adequate ventilation. After stopping the operation of the air conditioner, turn off the power-supply breaker and remove the power plug. Discharge the capacitor before the work involving the electric parts.
<Precautions during the repair service>
Do not perform the work involving the electric parts with wet hands. Do not pour water into the electric parts. Do not touch the refrigerant. Do not touch the hot or cold areas in the refrigeration cycle. When the repair or the inspection of the circuit needs to be done without turning off the power, exercise great caution not to
touch the live parts.
Use the specifi ed refrigerant only
Never use any refrigerant other than that specified.
Doing so may cause a burst, an explosion, or fire when the unit is being used, serviced, or disposed of. Correct refrigerant is specified in the manuals and on the spec labels provided with our products. We will not be held responsible for mechanical failure, system malfunction, unit breakdown or accidents caused by failure to follow the instructions.
Revision A:
• MUZ-SF25/35/42VE - E2 have been added.
OBH629A
3
MUZ-SF25VE -
E1
MUZ-SF25VEH -
E1
MUZ-SF35VE -
E1
MUZ-SF35VEH -
E1
MUZ-SF42VE -
E1
MUZ-SF42VEH -
E1
MUZ-SF50VE -
E1
MUZ-SF50VEH -
E1
1. New model
MUZ-SF25VE -
E1
MUZ-SF25VE -
E2
MUZ-SF35VE -
E1
MUZ-SF35VE -
E2
MUZ-SF42VE -
E1
MUZ-SF42VE -
E2
1. Condenser net has been changed. (Material: Plastic Steel wire)
TECHNICAL CHANGES
1
OBH629A
4
Air outlet
Drain outlet
Piping
Drain hose
Air inlet
(back and side)
MUZ-SF25VE MUZ-SF25VEH MUZ-SF35VE MUZ-SF35VEH MUZ-SF42VE MUZ-SF42VEH
PART NAMES AND FUNCTIONS
2
ACCESSORIES
MODELS
MUZ-SF25VE MUZ-SF35VE MUZ-SF42VE MUZ-SF50VE
Drain socket 1
MUZ-SF50VE MUZ-SF50VEH
Piping
Air outlet
Drain outlet
Air inlet
(back and side)
Drain hose
OBH629A
5
Outdoor model
MUZ-SF25VE
MUZ-SF25VEH
MUZ-SF35VE
MUZ-SF35VEH
MUZ-SF42VE
MUZ-SF42VEH
MUZ-SF50VE
MUZ-SF50VEH
Power supply Single phase, 230 V, 50 Hz
Capacity Rated frequency (Min.-Max.)
Cooling
kW
2.5 (0.9 - 3.4) 3.5 (1.1 - 3.8) 4.2 (0.8 - 4.5) 5.0 (1.4 - 5.4)
Heating 3.2 (1.0 - 4.1) 4.0 (1.3 - 4.6) 5.4 (1.3 - 6.0) 5.8 (1.6 - 7.3)
Breaker Capacity A 10 16
Electrical data
Power input 1 (Total)
Cooling
W
600 1,080 1,340 1,660
Heating 780 1,030 1,580 1,700
Running current
1
(Total)
Cooling
A
3.2 4.9 6.0 7.4
Heating 3.9 4.7 7.0 7.6
Power factor
1 (Total)
Cooling
%
81 95 97 97
Heating 86 95 98 97
Starting current
1 (Total) A 3.9 4.9 7.0 7.6
Coeffi cient of performance (COP) 1 (Total)
Cooling 4.17 3.24 3.13 3.01 Heating 4.10 3.88 3.42 3.41
Compressor
Model KNB073FKVMC KNB092FNDMC SNB130FGAMT SNB130FGBMT Output W 550 650 900 900
Current
1
Cooling
A
3.04 4.74 5.84 7.22
Heating 3.70 4.48 6.78 7.33
Refrigeration oil (Model) L 0.32 (FV50S) 0.27 (FV50S) 0.35 (FV50S)
Fan motor
Model RC0J50-FA RC0J60-BD Current
1
Cooling
A
0.20 0.24 0.30 0.84
Heating 0.29 0.30 0.28 0.93 Dimensions W × H × D mm 800 × 550 × 285 840 × 880 × 330 Weight kg 31 31 35 55
Special remarks
Dehumidifi cation Cooling L/h 0.3 1.0 1.7 2.2
Air fl ow 1
Cooling
High
m3/h
1,698 1,956 1,806 2,868
Low 1,698 1,806 1,038 1,602
Heating
High 2,064 2,178 2,016 2,778 Med. 1,698 1,932 1,770 2,778
Low 1,350 1,476 1,326 2,124
Sound level 1
Cooling
dB(A)
47 49 50 52
Heating 48 50 51 52
Fan speed
Cooling
High
rpm
740 800 810 840
Low 740 740 490 480
Heating
High 890 890 900 810 Med. 740 790 770 810
Low 600 610 610 620 Fan speed regulator 3 Refrigerant fi lling capacity (R410A) kg 0.7 0.8 1.15 1.55
NOTE: Test conditions are based on ISO 5151. Cooling: Indoor Dry-bulb temperature 27°C Wet-bulb temperature 19°C Outdoor Dry-bulb temperature 35°C Heating: Indoor Dry-bulb temperature 20°C Outdoor Dry-bulb temperature 7°C Wet-bulb temperature 6°C Refrigerant piping length (one way): 5 m 1 Measured under rated operating frequency.
SPECIFICATION
3
OBH629A
6
Speci
cations and rated conditions of main electric parts
Model
Item
MUZ-SF25VE MUZ-SF25VEH MUZ-SF35VE MUZ-SF35VEH MUZ-SF42VE MUZ-SF42VEH MUZ-SF50VE MUZ-SF50VEH
Smoothing capacitor
(C61, C62) 600 μF/ 620 μF 420 V
(C63) — 600 μF/ 620 μF 420 V
Diode module (DB61) 15 A 600 V 25 A 600 V Fuse
(F61) T20AL250V
(F701, F801, F901)
T3.15AL250V
Defrost heater (H)
230 V
130 W
230 V
130 W
230V
130W
230V
130W
Power module
(IC700) 15 A 600 V 20 A 600 V (IC932) 8A600V
Expansion valve coil
(LEV) 12 V DC
Reactor (L61) 18 mH 23 mH Power factor
controller
(IC820) 20A 600V
Current-limiting PTC thermistor
(PTC64, PTC65)
33 Ω
Terminal block (TB) 5 P
Relay
(X63) 3 A 250 V (X64) 20 A 250 V (X66) 3 A 250 V 3 A 250 V 3 A 250 V 3 A 250 V
(X69) 10A 230V R.V.coil (21S4) 220 - 240 V AC Heater protector (26H) Open 45°C Open 45°C Open 45°C Open 45°C
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, 0dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
COOLING
FUNCTION
SPL(dB(A)) LINE
HEATING
47 48
NC-10
MUZ-SF25VE MUZ-SF25VEH
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
COOLING
FUNCTION
SPL(dB(A))
LINE
HEATING
49 50
NC-10
MUZ-SF35VE MUZ-SF35VEH
NOISE CRITERIA CURVES
4
OBH629A
7
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, 0dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
COOLING
FUNCTION
SPL(dB(A)) LINE
HEATING
50
NC-10
51
MUZ-SF42VE MUZ-SF42VEH
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
COOLING
FUNCTION
SPL(dB(A)) LINE
HEATING
52
NC-10
52
MUZ-SF50VE MUZ-SF50VEH
Test conditions Cooling: Dry-bulb temperature 35°C Heating: Dry-bulb temperature 7°C Wet-bulb temperature 6°C
OUTDOOR UNIT
MICROPHONE
1 m
OBH629A
8
Unit: mm
MUZ-SF25VE MUZ-SF25VEH MUZ-SF35VE MUZ-SF35VEH MUZ-SF42VE MUZ-SF42VEH
10
69
800
302.5 500 Bolt pitch for installation
150
22.3
Handle
550
280
164.5
99.5
170.5
23
Service panel
Service port
285
344.5
44
400
Air in
Air out
Air in
17.5
Bolt pitch for
installation
304~325
40
Liquid refrigerant pipe joint Refrigerant pipe (flared) ø6.35
Gas refrigerant pipe joint Refrigerant pipe (flared) ø9.52
43
35
2 holes 10 X 21
REQUIRED SPACE
100 mm or more
350 mm or more
200 mm or more
100 mm or more
100 mm or more
Drain hole ø42 (MUZ-SF25/35/42VE) Drain hole ø33 (MUZ-SF25/35/42VEH)
MUZ-SF50VE MUZ-SF50VEH
OUTLINES AND DIMENSIONS
5
417.5
40
42
Drain hole
175
500
330
50
Air in
Air out
2-holes 10 21
360
840
109
81
880
452
Service panel
99.5
164.5 195
35
44
Liquid refrigerant pipe joint Refrigerant pipe (flared) Ø6.35
Gas refrigerant pipe joint Refrigerant pipe (flared) Ø 12.7
350 mm or more
100 mm or more
REQUIRED SPACE
500 mm or more
100 mm or more
500 mm or more
OBH629A
9
WIRING DIAGRAM
6
MUZ-SF25VE MUZ-SF35VE
MUZ-SF25VEH MUZ-SF35VEH
OBH629A
10
MUZ-SF42VE MUZ-SF50VE
MUZ-SF42VEH MUZ-SF50VEH
OBH629A
11
Unit: mm
MUZ-SF25VE MUZ-SF25VEH MUZ-SF35VE MUZ-SF35VEH
Outdoor heat exchanger
Flared connection
Defrost thermistor RT61
Discharge temperature thermistor RT62
Flared connection
Stop valve (with strainar)
Stop valve
Refrigerant flow in cooling
Compressor
4-way valve
Refrigerant flow in heating
Refrigerant pipe ø9.52 (with heat insulator)
Refrigerant pipe ø6.35 (with heat insulator)
R.V. coil heating ON cooling OFF
Strainer #100
LEV
Ambient temperature thermistor RT65
Muffler
Capillary tube ø3.0×ø2.0×240
Outdoor heat exchanger temperature thermistor RT68
Muffler
REFRIGERANT SYSTEM DIAGRAM
7
Unit: mm
MUZ-SF42VE MUZ-SF42VEH
Outdoor heat exchanger
Flared connection
Defrost thermistor RT61
Discharge temperature thermistor RT62
Flared connection
Stop valve (with strainar)
Stop valve
Refrigerant flow in cooling
Compressor
4-way valve
Refrigerant flow in heating
Refrigerant pipe ø9.52 (with heat insulator)
Refrigerant pipe ø6.35 (with heat insulator)
R.V. coil heating ON cooling OFF
Strainer #100
Capillary tube ø3.0×ø1.8×600(×2)
LEV
Ambient temperature thermistor RT65
Muffler
Capillary tube ø3.0×ø2.0×240
Outdoor heat exchanger temperature thermistor RT68
Muffler
OBH629A
12
MUZ-SF50VE MUZ-SF50VEH
Unit: mm
Outdoor heat exchanger
Flared connection
Defrost thermistor RT61
Discharge temperature thermistor RT62
Flared connection
Stop valve
Stop valve (with service port)
Capillary tube ø
4.0×ø
2.4×100
Capillary tube ø
4.0×ø
2.4×200
Refrigerant flow in cooling
Compressor
4-way valve
Refrigerant flow in heating
Refrigerant pipe
ø
12.7
(with heat insulator)
Refrigerant pipe ø6.35 (with heat insulator)
LEV
R.V. coil heating ON cooling OFF
Muffler
#100
Strainer
#100
Outdoor heat exchanger temperature thermistor RT68
Ambient temperature thermistor RT65
Strainer
#100
Muffler
Capillary tube ø3.0×ø2.0×200(×4)
Max. Length A
Max. Height
difference
B
Indoor unit
Outdoor unit
MAX. REFRIGERANT PIPING LENGTH and MAX. HEIGHT DIFEFRENCE
Refrigerant piping: m Piping size O.D: mm
Max. Length A Max. Height difference B Gas Liquid
MUZ-SF25/35/42 20 12 9.52
6.35
MUZ-SF50 30 15 12.7
ADDITIONAL REFRIGERANT CHARGE (R410A: g)
Model
Outdoor unit
precharged
7 m 8 m 9 m 10 m 11 m 12 m 13 m 14 m 15 m 20 m
MUZ-SF25 700
0 30 60 90 120 150 180 210 240 390
MUZ-SF35 800 MUZ-SF42 1,150
Calculation: X g = 30 g/m × (Refrigerant piping length (m) - 7)
Model
Outdoor unit
precharged
Refrigerant piping length (one way)
7 m 10 m 15 m 20 m 25 m 30 m
MUZ-SF50 1,550 0 60 160 260 360 460
Calculation: X g = 20 g/m × (Refrigerant piping length (m) – 7) NOTE: Refrigerant piping exceeding 7 m requires additional refrigerant charge according to the calculation.
OBH629A
13
The standard specifications apply only to the operation of the air conditioner under normal conditions. Since operating condi­tions vary according to the areas where these units are installed, the following information has been provided to clarify the operating characteristics of the air conditioner under the conditions indicated by the performance curve.
(1) GUARANTEED VOLTAGE
198 ~ 264 V, 50 Hz
(2) AIR FLOW
Air flow should be set at MAX.
(3) MAIN READINGS
(1) Indoor intake air wet-bulb temperature: °C [WB]
}
Cooling
(2) Indoor outlet air wet-bulb temperature: °C [WB] (3) Outdoor intake air dry-bulb temperature: °C [DB] (4) Total input: W (5) Indoor intake air dry-bulb temperature: °C [DB]
}
Heating(6) Outdoor intake air wet-bulb temperature: °C [WB] (7) Total input: W Indoor air wet and dry bulb temperature difference on the left side of the following chart shows the difference between the indoor intake air wet and dry bulb temperature and the indoor outlet air wet and dry bulb temperature for your reference at service.
How to measure the indoor air wet and dry bulb temperature difference
1. Attach at least 2 sets of wet and dry bulb thermometers to the indoor air intake as shown in the figure, and at least 2 sets of wet and dry bulb thermometers to the indoor air outlet. The thermometers must be attached to the position where air speed is high.
2. Attach at least 2 sets of wet and dry bulb thermometers to the outdoor air intake.
Cover the thermometers to prevent direct rays of the sun.
3. Check that the air filter is cleaned.
4. Open windows and doors of room.
5. Press the EMERGENCY OPERATION switch once (twice) to start the EMERGENCY COOL (HEAT) MODE.
6. When system stabilizes after more than 15 minutes, measure temperature and take an average temperature.
7. 10 minutes later, measure temperature again and check that the temperature does not change.
MUZ-SF25VE MUZ-SF25VEH MUZ-SF35VE MUZ-SF35VEH MUZ-SF42VE MUZ-SF42VEH MUZ-SF50VE MUZ-SF50VEH
INDOOR UNIT OUTDOOR UNIT
Wet and dry bulb thermometers FRONT VIEW
Wet and dry bulb thermometers BACK VIEW
Cooling capacity (
at Rated frequency)
0.9
1.0
1.1
1.2
1.3
1.4
1.5
-10-5 0 5 1015202530354045 Outdoor intake air Dry-bulb temperature(°C)
Capacity correction factors
26
24
20 18
22
Indoor intake air Wet-bulb temperature( )
14.2
13.0
11.8
10.7
9.7
8.6
7.6
MUZ-SF50VE
MUZ-SF50VEH
MUZ-SF42VE
MUZ-SF42VEH
MUZ-SF35VE
MUZ-SF35VEH
MUZ-SF25VE
MUZ-SF25VEH
Indoor air Wet-bulb temperature
difference (°C)
7.6
7.0
6.4
5.9
5.3
4.8
4.3
11.3
10.4
9.5
8.6
7.8
7.0
6.2
16.0
14.6
13.3
12.0
10.8
9.6
8.5
8-1. CAPACITY AND INPUT CURVES
PERFORMANCE CURVES8
OBH629A
14
NOTE:
The above broken lines are for the heating operation without any frost and defrost operation.
0.8
0.9
1.0
1.1
1.2
1.3
-10-5 0 5 1015202530354045 Outdoor intake air Dry-bulb temperature (°C)
Input correction factors
26
24
22 20 18
Indoor intake air Wet-bulb temperature( )
Indoor air Wet-bulb temperature
difference (°C)
6.4
5.9
5.3
4.8
4.3
3.8
9.5
8.6
7.8
7.0
6.2
5.4
11.8
10.7
9.7
8.6
7.6
6.7
13.3
12.0
10.8
9.6
8.5
7.4
MUZ-SF50VE
MUZ-SF50VEH
MUZ-SF42VE
MUZ-SF42VEH
MUZ-SF35VE
MUZ-SF35VEH
MUZ-SF25VE
MUZ-SF25VEH
Total input (Cooling :
at Rated frequency
)
Indoor air Dry-bulb temperature
difference (°C)
20.3
18.8
17.2
15.6
14.1
12.5
10.9
9.4
7.8
6.3
32.1
29.6
27.2
24.7
22.2
19.8
17.3
14.8
12.3
9.9
31.6
29.2
26.7
24.3
21.9
19.4
17.0
14.6
12.2
9.7
MUZ-SF50VE
MUZ-SF50VEH
MUZ-SF42VE
MUZ-SF42VEH
MUZ-SF25VEH
MUZ-SF35VE
23.8
21.9
20.1
18.3
16.5
14.6
12.8
11.0
9.1
7.3
MUZ-SF35VEH
MUZ-SF25VE
Outdoor intake air Wet-bulb temperature (°C)
-20 -15 -10 -5 0 5 10 15
0.4
0.5
0.6
0.7
0.8
0.9
1.0
1.1
1.2
1.3
Heating capacity (
at Rated frequency)
Capacity correction factor
15
20 26
Indoor intake air Dry-bulb temperature ( )
Indoor air Dry-bulb temperature
difference (°C)
20.3
18.8
17.2
15.6
14.1
12.5
10.9
9.4
7.8
6.3
MUZ-SF50VE
MUZ-SF50VEH
MUZ-SF42VE
MUZ-SF42VEH
MUZ-SF25VEH
MUZ-SF25VE
23.8
21.9
20.1
18.3
16.5
14.6
12.8
11.0
9.1
7.3
MUZ-SF35VEH
MUZ-SF35VE
32.1
29.6
27.2
24.7
22.2
19.8
17.3
14.8
12.3
9.9
31.6
29.2
26.7
24.3
21.9
19.4
17.0
14.6
12.2
9.7
Outdoor intake air Wet-bulb temperature (°C)
-20 -15 -10 -5 0 5 10 15
0.4
0.5
0.6
0.7
0.8
0.9
1.0
1.1
1.2
1.3
Total input (Heating :
at Rated frequency
)
Input correction factor
15
20
26
Indoor intake air Dry-bulb temperature ( )
Lower limit of guaranteed oerating range in heating MUZ-SF25/35/42/50VE: -15°C MUZ-SF25/35/42/50VEH: -20°C
OBH629A
15
8-2. CAPACITY AND INPUT CORRECTION BY OPERATIONAL FREQUENCY OF COMPRESSOR
0 50 100
0.0
0.5
1.0
1.5
0 50 100
0.0
0.5
1.0
1.5
0 50 100
0.0
0.5
1.0
1.5
0 50 100
0.0
0.5
1.0
1.5
2.0
0 50 100
150
0.0
0.5
1.0
1.5
050100
150
0.0
0.5
1.0
1.5
050100
150
0.0
0.5
1.0
1.5
050100
150
0.0
0.5
1.0
1.5
2.0
0 50 100
0.0
0.5
1.0
1.5
0 50 100
0.0
0.5
1.0
1.5
2.0
0 50 100
0.0
0.5
1.0
1.5
0 50 100
0.0
0.5
1.0
1.5
2.0
050100
150
0.0
0.5
1.0
1.5
0 50 100
150
0.0
0.5
1.0
1.5
2.0
0 50 100
150
0.0
0.5
1.0
1.5
0 50 100
150
0.0
0.5
1.0
1.5
2.0
MUZ-SF25VE MUZ-SF25VEH
MUZ-SF35VE MUZ-SF35VEH
Correction of Cooling capacity
Capacity correction factors
Correction of Cooling input
Input correction factors
Correction of Heating capacity
Capacity correction factors
MUZ-SF42VE MUZ-SF42VEH
Correction of Heating input
Capacity correction factors
Correction of Cooling capacity
Capacity correction factors
Correction of Cooling input
Input correction factors
Correction of Heating capacity
Capacity correction factors
MUZ-SF50VE MUZ-SF50VEH
Correction of Heating input
Capacity correction factors
The operational frequency of compressor (Hz)
The operational frequency of compressor (Hz)
The operational frequency of compressor (Hz)
The operational frequency of compressor (Hz)
The operational frequency of compressor (Hz)
The operational frequency of compressor (Hz)
The operational frequency of compressor (Hz)
The operationalfrequency of compressor (Hz)
Correction of Cooling capacity
The operational frequency of compressor (Hz)
Capacity correction factors
Correction of Cooling input
The operationalfrequency of compressor(Hz)
Input correction factors
Correction of Heating capacity
The operationalfrequency of compressor (Hz)
Capacity correction factors
Correction of Heating input
The operational frequency of compressor (Hz)
Input correction factors
Correction of Cooling capacity
The operational frequency of compressor (Hz)
Capacity correction factors
Correction of Cooling input
The operational frequency of compressor (Hz)
Input correction factors
Correction of Heatingcapacity
The operational frequency of compressor (Hz)
Capacity correction factors
Correction of Heatinginput
The operational frequency of compressor (Hz)
Input correction factors
OBH629A
16
15 20 25 30 35
0.4
0.5
0.6
0.7
0.8
0.9
15 20 25 30 35
0.3
0.4
0.5
0.6
15 20 25 30 35
0.3
0.4
0.5
0.6
0.7
0.8
15 20 25 30 35
0.3
0.4
0.5
0.6
0.7
(kgf/cm2[Gauge])(MPa[Gauge])
6
5
4
7
8
9
(kgf/cm2[Gauge])(MPa[Gauge])
4
3
5
6
(kgf/cm2[Gauge])(MPa[Gauge])
3
5
6
4
7
8
(kgf/cm2[Gauge])(MPa [Gauge])
4
3
5
6
7
50 60 70
Ambient temperature(°C) Ambient humidity(%)
50 60 70
Ambient temperature(°C) Ambient humidity(%)
50 60 70
Ambient temperature(°C) Ambient humidity(%)
50 60 70
Ambient temperature(°C) Ambient humidity(%)
Outdoor low pressure
MUZ-SF25VE MUZ-SF25VEH
MUZ-SF35VE MUZ-SF35VEH
MUZ-SF42VE MUZ-SF42VEH
MUZ-SF50VE MUZ-SF50VEH
COOL operation
Both indoor and outdoor unit are under the same temperature/
humidity condition.
Operation: TEST RUN OPERATION (Refer to 8-3.)
8-4. OUTDOOR LOW PRESSURE AND OUTDOOR UNIT CURRENT
Dry-bulb temperature (°C) Relative humidity (%)
20 50 25 60 30 70
8-3. HOW TO OPERATE FIXED-FREQUENCY OPERATION
<Test run operation>
1. Press EMERGENCY OPERATION switch to start COOL or HEAT mode (COOL: Press once, HEAT: Press twice).
2. Test run operation starts and continues to operate for 30 minutes.
3. Compressor operates at rated frequency in COOL mode or 58 Hz in HEAT mode.
4. Indoor fan operates at High speed.
5.
After 30 minutes, test run operation finishes and EMERGENCY OPERATION starts (operation frequency of compressor varies).
6. To cancel test run operation (EMERGENCY OPERATION), press EMERGENCY OPERATION switch or any button on remote controller.
NOTE: The unit of pressure has been changed to MPa on the international system of units (SI unit system) The conversion factor is: 1 (MPa [Gauge]) = 10.2 (kgf/cm
2
[Gauge])
OBH629A
17
15 20 25 30 35
1.5
2.0
2.5
3.0
15 20 25 30 35
4
5
6
7
8
15 20 25 30 35
3.0
3.5
4.0
4.5
5.0
15 20 25 30 35
3.5
4.0
4.5
5.0
5.5
6.0
Ambient temperature(°C) Ambient humidity(%)
Ambient temperature (°C) Ambient humidity(%)
Ambient temperature (°C) Ambient humidity(%)
Outdoor current (A)Outdoor current (A)
Ambient temperature (°C) Ambient humidity(%)
Outdoor current (A)
Outdoor current (A)
MUZ-SF35VE MUZ-SF35VEHMUZ-SF25VE MUZ-SF25VEH
Outdoor unit current
MUZ-SF42VE MUZ-SF42VEH
MUZ-SF50VE MUZ-SF50VEH
0510
15 20 25
1.5
2.0
2.5
3.0
0510
15
20 25
4.0
4.5
5.0
5.5
6.0
0510
15 20 25
2.5
3.0
3.5
4.0
0510
15
20
25
4.0
4.5
5.0
5.5
6.0
Ambient temperature (°C)
Outdoor current (A)
Ambient temperature (°C)
Outdoor current (A)
Ambient temperature (°C)
Outdoor current (A)
Ambient temperature (°C)
Outdoor current (A)
MUZ-SF35VE MUZ-SF35VEHMUZ-SF25VE MUZ-SF25VEH
Outdoor unit current
MUZ-SF42VE MUZ-SF42VEH
MUZ-SF50VE MUZ-SF50VEH
Condition:
Operation: Test run operation (Refer to 8-3.)
HEAT operation
Indoor Outdoor
Dry bulb temperature (°C) 20.0 2 7 15 20.0
Wet bulb temperature (°C) 14.5 1 6 12 14.5
OBH629A
18
PERFORMANCE DATA COOL operation at Rated frequency
MUZ-SF25VE MUZ-SF25VEH
CAPACITY: 2.5 kW SHF: 0.92 INPUT: 600 W
INDOOR
DB (°C)
INDOOR
WB (°C)
OUTDOOR DB (°C)
21 25 27 30
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT 21 18 2.94 2.17 0.74 480 2.81 2.08 0.74 504 2.70 2.00 0.74 528 2.60 1.92 0.74 552 21 20 3.06 1.90 0.62 504 2.94 1.82 0.62 534 2.85 1.77 0.62 546 2.75 1.71 0.62 570 22 18 2.94 2.29 0.78 480 2.81 2.19 0.78 504 2.70 2.11 0.78 528 2.60 2.03 0.78 552 22 20 3.06 2.02 0.66 504 2.94 1.94 0.66 534 2.85 1.88 0.66 546 2.75 1.82 0.66 570 22 22 3.19 1.72 0.54 522 3.08 1.66 0.54 555 3.00 1.62 0.54 570 2.88 1.55 0.54 594 23 18 2.94 2.41 0.82 480 2.81 2.31 0.82 504 2.70 2.21 0.82 528 2.60 2.13 0.82 552 23 20 3.06 2.14 0.70 504 2.94 2.06 0.70 534 2.85 2.00 0.70 546 2.75 1.93 0.70 570 23 22 3.19 1.85 0.58 522 3.08 1.78 0.58 555 3.00 1.74 0.58 570 2.88 1.67 0.58 594 24 18 2.94 2.53 0.86 480 2.81 2.42 0.86 504 2.70 2.32 0.86 528 2.60 2.24 0.86 552 24 20 3.06 2.27 0.74 504 2.94 2.17 0.74 534 2.85 2.11 0.74 546 2.75 2.04 0.74 570 24 22 3.19 1.98 0.62 522 3.08 1.91 0.62 555 3.00 1.86 0.62 570 2.88 1.78 0.62 594 24 24 3.35 1.68 0.50 546 3.23 1.61 0.50 576 3.15 1.58 0.50 594 3.05 1.53 0.50 624 25 18 2.94 2.64 0.90 480 2.81 2.53 0.90 504 2.70 2.43 0.90 528 2.60 2.34 0.90 552 25 20 3.06 2.39 0.78 504 2.94 2.29 0.78 534 2.85 2.22 0.78 546 2.75 2.15 0.78 570 25 22 3.19 2.10 0.66 522 3.08 2.03 0.66 555 3.00 1.98 0.66 570 2.88 1.90 0.66 594 25 24 3.35 1.81 0.54 546 3.23 1.74 0.54 576 3.15 1.70 0.54 594 3.05 1.65 0.54 624 26 18 2.94 2.76 0.94 480 2.81 2.64 0.94 504 2.70 2.54 0.94 528 2.60 2.44 0.94 552 26 20 3.06 2.51 0.82 504 2.94 2.41 0.82 534 2.85 2.34 0.82 546 2.75 2.26 0.82 570 26 22 3.19 2.23 0.70 522 3.08 2.15 0.70 555 3.00 2.10 0.70 570 2.88 2.01 0.70 594 26 24 3.35 1.94 0.58 546 3.23 1.87 0.58 576 3.15 1.83 0.58 594 3.05 1.77 0.58 624 26 26 3.45 1.59 0.46 576 3.35 1.54 0.46 606 3.30 1.52 0.46 624 3.20 1.47 0.46 642 27 18 2.94 2.88 0.98 480 2.81 2.76 0.98 504 2.70 2.65 0.98 528 2.60 2.55 0.98 552 27 20 3.06 2.63 0.86 504 2.94 2.53 0.86 534 2.85 2.45 0.86 546 2.75 2.37 0.86 570 27 22 3.19 2.36 0.74 522 3.08 2.28 0.74 555 3.00 2.22 0.74 570 2.88 2.13 0.74 594 27 24 3.35 2.08 0.62 546 3.23 2.00 0.62 576 3.15 1.95 0.62 594 3.05 1.89 0.62 624 27 26 3.45 1.73 0.50 576 3.35 1.68 0.50 606 3.30 1.65 0.50 624 3.20 1.60 0.50 642 28 18 2.94 2.94 1.00 480 2.81 2.81 1.00 504 2.70 2.70 1.00 528 2.60 2.60 1.00 552 28 20 3.06 2.76 0.90 504 2.94 2.64 0.90 534 2.85 2.57 0.90 546 2.75 2.48 0.90 570 28 22 3.19 2.49 0.78 522 3.08 2.40 0.78 555 3.00 2.34 0.78 570 2.88 2.24 0.78 594 28 24 3.35 2.21 0.66 546 3.23 2.13 0.66 576 3.15 2.08 0.66 594 3.05 2.01 0.66 624 28 26 3.45 1.86 0.54 576 3.35 1.81 0.54 606 3.30 1.78 0.54 624 3.20 1.73 0.54 642 29 18 2.94 2.94 1.00 480 2.81 2.81 1.00 504 2.70 2.70 1.00 528 2.60 2.60 1.00 552 29 20 3.06 2.88 0.94 504 2.94 2.76 0.94 534 2.85 2.68 0.94 546 2.75 2.59 0.94 570 29 22 3.19 2.61 0.82 522 3.08 2.52 0.82 555 3.00 2.46 0.82 570 2.88 2.36 0.82 594 29 24 3.35 2.35 0.70 546 3.23 2.26 0.70 576 3.15 2.21 0.70 594 3.05 2.14 0.70 624 29 26 3.45 2.00 0.58 576 3.35 1.94 0.58 606 3.30 1.91 0.58 624 3.20 1.86 0.58 642 30 18 2.94 2.94 1.00 480 2.81 2.81 1.00 504 2.70 2.70 1.00 528 2.60 2.60 1.00 552 30 20 3.06 3.00 0.98 504 2.94 2.88 0.98 534 2.85 2.79 0.98 546 2.75 2.70 0.98 570 30 22 3.19 2.74 0.86 522 3.08 2.64 0.86 555 3.00 2.58 0.86 570 2.88 2.47 0.86 594 30 24 3.35 2.48 0.74 546 3.23 2.39 0.74 576 3.15 2.33 0.74 594 3.05 2.26 0.74 624 30 26 3.45 2.14 0.62 576 3.35 2.08 0.62 606 3.30 2.05 0.62 624 3.20 1.98 0.62 642 31 18 2.94 2.94 1.00 480 2.81 2.81 1.00 504 2.70 2.70 1.00 528 2.60 2.60 1.00 552 31 20 3.06 3.06 1.00 504 2.94 2.94 1.00 534 2.85 2.85 1.00 546 2.75 2.75 1.00 570 31 22 3.19 2.87 0.90 522 3.08 2.77 0.90 555 3.00 2.70 0.90 570 2.88 2.59 0.90 594 31 24 3.35 2.61 0.78 546 3.23 2.52 0.78 576 3.15 2.46 0.78 594 3.05 2.38 0.78 624 31 26 3.45 2.28 0.66 576 3.35 2.21 0.66 606 3.30 2.18 0.66 624 3.20 2.11 0.66 642 32 18 2.94 2.94 1.00 480 2.81 2.81 1.00 504 2.70 2.70 1.00 528 2.60 2.60 1.00 552 32 20 3.06 3.06 1.00 504 2.94 2.94 1.00 534 2.85 2.85 1.00 546 2.75 2.75 1.00 570 32 22 3.19 3.00 0.94 522 3.08 2.89 0.94 555 3.00 2.82 0.94 570 2.88 2.70 0.94 594 32 24 3.35 2.75 0.82 546 3.23 2.64 0.82 576 3.15 2.58 0.82 594 3.05 2.50 0.82 624 32 26 3.45 2.42 0.70 576 3.35 2.35 0.70 606 3.30 2.31 0.70 624 3.20 2.24 0.70 642
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
OBH629A
19
PERFORMANCE DATA COOL operation at Rated frequency
MUZ-SF25VE MUZ-SF25VEH
CAPACITY: 2.5 kW SHF: 0.92 INPUT: 600 W
INDOOR
DB (°C)
INDOOR
WB (°C)
OUTDOOR DB (°C)
35 40 46
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT 21 18 2.45 1.81 0.74 588 2.25 1.67 0.74 624 2.08 1.54 0.74 648 21 20 2.58 1.60 0.62 612 2.40 1.49 0.62 642 2.23 1.38 0.62 678 22 18 2.45 1.91 0.78 588 2.25 1.76 0.78 624 2.08 1.62 0.78 648 22 20 2.58 1.70 0.66 612 2.40 1.58 0.66 642 2.23 1.47 0.66 678 22 22 2.73 1.47 0.54 636 2.55 1.38 0.54 672 2.38 1.28 0.54 696 23 18 2.45 2.01 0.82 588 2.25 1.85 0.82 624 2.08 1.70 0.82 648 23 20 2.58 1.80 0.70 612 2.40 1.68 0.70 642 2.23 1.56 0.70 678 23 22 2.73 1.58 0.58 636 2.55 1.48 0.58 672 2.38 1.38 0.58 696 24 18 2.45 2.11 0.86 588 2.25 1.94 0.86 624 2.08 1.78 0.86 648 24 20 2.58 1.91 0.74 612 2.40 1.78 0.74 642 2.23 1.65 0.74 678 24 22 2.73 1.69 0.62 636 2.55 1.58 0.62 672 2.38 1.47 0.62 696 24 24 2.88 1.44 0.50 660 2.70 1.35 0.50 690 2.55 1.28 0.50 720 25 18 2.45 2.21 0.90 588 2.25 2.03 0.90 624 2.08 1.87 0.9 648 25 20 2.58 2.01 0.78 612 2.40 1.87 0.78 642 2.23 1.74 0.78 678 25 22 2.73 1.80 0.66 636 2.55 1.68 0.66 672 2.38 1.57 0.66 696 25 24 2.88 1.55 0.54 660 2.70 1.46 0.54 690 2.55 1.38 0.54 720 26 18 2.45 2.30 0.94 588 2.25 2.12 0.94 624 2.08 1.95 0.94 648 26 20 2.58 2.11 0.82 612 2.40 1.97 0.82 642 2.23 1.82 0.82 678 26 22 2.73 1.91 0.70 636 2.55 1.79 0.70 672 2.38 1.66 0.70 696 26 24 2.88 1.67 0.58 660 2.70 1.57 0.58 690 2.55 1.48 0.58 720 26 26 3.03 1.39 0.46 684 2.85 1.31 0.46 714 2.68 1.23 0.46 744 27 18 2.45 2.40 0.98 588 2.25 2.21 0.98 624 2.08 2.03 0.98 648 27 20 2.58 2.21 0.86 612 2.40 2.06 0.86 642 2.23 1.91 0.86 678 27 22 2.73 2.02 0.74 636 2.55 1.89 0.74 672 2.38 1.76 0.74 696 27 24 2.88 1.78 0.62 660 2.70 1.67 0.62 690 2.55 1.58 0.62 720 27 26 3.03 1.51 0.50 684 2.85 1.43 0.50 714 2.68 1.34 0.50 744 28 18 2.45 2.45 1.00 588 2.25 2.25 1.00 624 2.08 2.08 1.00 648 28 20 2.58 2.32 0.90 612 2.40 2.16 0.90 642 2.23 2.00 0.90 678 28 22 2.73 2.13 0.78 636 2.55 1.99 0.78 672 2.38 1.85 0.78 696 28 24 2.88 1.90 0.66 660 2.70 1.78 0.66 690 2.55 1.68 0.66 720 28 26 3.03 1.63 0.54 684 2.85 1.54 0.54 714 2.68 1.44 0.54 744 29 18 2.45 2.45 1.00 588 2.25 2.25 1.00 624 2.08 2.08 1.00 648 29 20 2.58 2.42 0.94 612 2.40 2.26 0.94 642 2.23 2.09 0.94 678 29 22 2.73 2.23 0.82 636 2.55 2.09 0.82 672 2.38 1.95 0.82 696 29 24 2.88 2.01 0.70 660 2.70 1.89 0.70 690 2.55 1.79 0.70 720 29 26 3.03 1.75 0.58 684 2.85 1.65 0.58 714 2.68 1.55 0.58 744 30 18 2.45 2.45 1.00 588 2.25 2.25 1.00 624 2.08 2.08 1.00 648 30 20 2.58 2.52 0.98 612 2.40 2.35 0.98 642 2.23 2.18 0.98 678 30 22 2.73 2.34 0.86 636 2.55 2.19 0.86 672 2.38 2.04 0.86 696 30 24 2.88 2.13 0.74 660 2.70 2.00 0.74 690 2.55 1.89 0.74 720 30 26 3.03 1.88 0.62 684 2.85 1.77 0.62 714 2.68 1.66 0.62 744 31 18 2.45 2.45 1.00 588 2.25 2.25 1.00 624 2.08 2.08 1.00 648 31 20 2.58 2.58 1.00 612 2.40 2.40 1.00 642 2.23 2.23 1.00 678 31 22 2.73 2.45 0.90 636 2.55 2.30 0.90 672 2.38 2.14 0.90 696 31 24 2.88 2.24 0.78 660 2.70 2.11 0.78 690 2.55 1.99 0.78 720 31 26 3.03 2.00 0.66 684 2.85 1.88 0.66 714 2.68 1.77 0.66 744 32 18 2.45 2.45 1.00 588 2.25 2.25 1.00 624 2.08 2.08 1.00 648 32 20 2.58 2.58 1.00 612 2.40 2.40 1.00 642 2.23 2.23 1.00 678 32 22 2.73 2.56 0.94 636 2.55 2.40 0.94 672 2.38 2.23 0.94 696 32 24 2.88 2.36 0.82 660 2.70 2.21 0.82 690 2.55 2.09 0.82 720 32 26 3.03 2.12 0.70 684 2.85 2.00 0.70 714 2.68 1.87 0.70 744
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
OBH629A
20
PERFORMANCE DATA COOL operation at Rated frequency
MUZ-SF35VE MUZ-SF35VEH
CAPACITY: 3.5 kW SHF: 0.80 INPUT: 1080 W
INDOOR
DB (°C)
INDOOR
WB (°C)
OUTDOOR DB (°C)
21 25 27 30
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT 21 18 4.11 2.55 0.62 864 3.94 2.44 0.62 907 3.78 2.34 0.62 950 3.64 2.26 0.62 994 21 20 4.29 2.14 0.50 907 4.11 2.06 0.50 961 3.99 2.00 0.50 983 3.85 1.93 0.50 1026 22 18 4.11 2.71 0.66 864 3.94 2.60 0.66 907 3.78 2.49 0.66 950 3.64 2.40 0.66 994 22 20 4.29 2.32 0.54 907 4.11 2.22 0.54 961 3.99 2.15 0.54 983 3.85 2.08 0.54 1026 22 22 4.46 1.87 0.42 940 4.31 1.81 0.42 999 4.20 1.76 0.42 1026 4.03 1.69 0.42 1069 23 18 4.11 2.88 0.70 864 3.94 2.76 0.70 907 3.78 2.65 0.70 950 3.64 2.55 0.70 994 23 20 4.29 2.49 0.58 907 4.11 2.39 0.58 961 3.99 2.31 0.58 983 3.85 2.23 0.58 1026 23 22 4.46 2.05 0.46 940 4.31 1.98 0.46 999 4.20 1.93 0.46 1026 4.03 1.85 0.46 1069 24 18 4.11 3.04 0.74 864 3.94 2.91 0.74 907 3.78 2.80 0.74 950 3.64 2.69 0.74 994 24 20 4.29 2.66 0.62 907 4.11 2.55 0.62 961 3.99 2.47 0.62 983 3.85 2.39 0.62 1026 24 22 4.46 2.23 0.50 940 4.31 2.15 0.50 999 4.20 2.10 0.50 1026 4.03 2.01 0.50 1069 24 24 4.69 1.78 0.38 983 4.52 1.72 0.38 1037 4.41 1.68 0.38 1069 4.27 1.62 0.38 1123 25 18 4.11 3.21 0.78 864 3.94 3.07 0.78 907 3.78 2.95 0.78 950 3.64 2.84 0.78 994 25 20 4.29 2.83 0.66 907 4.11 2.71 0.66 961 3.99 2.63 0.66 983 3.85 2.54 0.66 1026 25 22 4.46 2.41 0.54 940 4.31 2.32 0.54 999 4.20 2.27 0.54 1026 4.03 2.17 0.54 1069 25 24 4.69 1.97 0.42 983 4.52 1.90 0.42 1037 4.41 1.85 0.42 1069 4.27 1.79 0.42 1123 26 18 4.11 3.37 0.82 864 3.94 3.23 0.82 907 3.78 3.10 0.82 950 3.64 2.98 0.82 994 26 20 4.29 3.00 0.70 907 4.11 2.88 0.70 961 3.99 2.79 0.70 983 3.85 2.70 0.70 1026 26 22 4.46 2.59 0.58 940 4.31 2.50 0.58 999 4.20 2.44 0.58 1026 4.03 2.33 0.58 1069 26 24 4.69 2.16 0.46 983 4.52 2.08 0.46 1037 4.41 2.03 0.46 1069 4.27 1.96 0.46 1123 26 26 4.83 1.64 0.34 1037 4.69 1.59 0.34 1091 4.62 1.57 0.34 1123 4.48 1.52 0.34 1156 27 18 4.11 3.54 0.86 864 3.94 3.39 0.86 907 3.78 3.25 0.86 950 3.64 3.13 0.86 994 27 20 4.29 3.17 0.74 907 4.11 3.04 0.74 961 3.99 2.95 0.74 983 3.85 2.85 0.74 1026 27 22 4.46 2.77 0.62 940 4.31 2.67 0.62 999 4.20 2.60 0.62 1026 4.03 2.50 0.62 1069 27 24 4.69 2.35 0.50 983 4.52 2.26 0.50 1037 4.41 2.21 0.50 1069 4.27 2.14 0.50 1123 27 26 4.83 1.84 0.38 1037 4.69 1.78 0.38 1091 4.62 1.76 0.38 1123 4.48 1.70 0.38 1156 28 18 4.11 3.70 0.90 864 3.94 3.54 0.90 907 3.78 3.40 0.90 950 3.64 3.28 0.90 994 28 20 4.29 3.34 0.78 907 4.11 3.21 0.78 961 3.99 3.11 0.78 983 3.85 3.00 0.78 1026 28 22 4.46 2.95 0.66 940 4.31 2.84 0.66 999 4.20 2.77 0.66 1026 4.03 2.66 0.66 1069 28 24 4.69 2.53 0.54 983 4.52 2.44 0.54 1037 4.41 2.38 0.54 1069 4.27 2.31 0.54 1123 28 26 4.83 2.03 0.42 1037 4.69 1.97 0.42 1091 4.62 1.94 0.42 1123 4.48 1.88 0.42 1156 29 18 4.11 3.87 0.94 864 3.94 3.70 0.94 907 3.78 3.55 0.94 950 3.64 3.42 0.94 994 29 20 4.29 3.52 0.82 907 4.11 3.37 0.82 961 3.99 3.27 0.82 983 3.85 3.16 0.82 1026 29 22 4.46 3.12 0.70 940 4.31 3.01 0.70 999 4.20 2.94 0.70 1026 4.03 2.82 0.70 1069 29 24 4.69 2.72 0.58 983 4.52 2.62 0.58 1037 4.41 2.56 0.58 1069 4.27 2.48 0.58 1123 29 26 4.83 2.22 0.46 1037 4.69 2.16 0.46 1091 4.62 2.13 0.46 1123 4.48 2.06 0.46 1156 30 18 4.11 4.03 0.98 864 3.94 3.86 0.98 907 3.78 3.70 0.98 950 3.64 3.57 0.98 994 30 20 4.29 3.69 0.86 907 4.11 3.54 0.86 961 3.99 3.43 0.86 983 3.85 3.31 0.86 1026 30 22 4.46 3.30 0.74 940 4.31 3.19 0.74 999 4.20 3.11 0.74 1026 4.03 2.98 0.74 1069 30 24 4.69 2.91 0.62 983 4.52 2.80 0.62 1037 4.41 2.73 0.62 1069 4.27 2.65 0.62 1123 30 26 4.83 2.42 0.50 1037 4.69 2.35 0.50 1091 4.62 2.31 0.50 1123 4.48 2.24 0.50 1156 31 18 4.11 4.11 1.00 864 3.94 3.94 1.00 907 3.78 3.78 1.00 950 3.64 3.64 1.00 994 31 20 4.29 3.86 0.90 907 4.11 3.70 0.90 961 3.99 3.59 0.90 983 3.85 3.47 0.90 1026 31 22 4.46 3.48 0.78 940 4.31 3.36 0.78 999 4.20 3.28 0.78 1026 4.03 3.14 0.78 1069 31 24 4.69 3.10 0.66 983 4.52 2.98 0.66 1037 4.41 2.91 0.66 1069 4.27 2.82 0.66 1123 31 26 4.83 2.61 0.54 1037 4.69 2.53 0.54 1091 4.62 2.49 0.54 1123 4.48 2.42 0.54 1156 32 18 4.11 4.11 1.00 864 3.94 3.94 1.00 907 3.78 3.78 1.00 950 3.64 3.64 1.00 994 32 20 4.29 4.03 0.94 907 4.11 3.87 0.94 961 3.99 3.75 0.94 983 3.85 3.62 0.94 1026 32 22 4.46 3.66 0.82 940 4.31 3.53 0.82 999 4.20 3.44 0.82 1026 4.03 3.30 0.82 1069 32 24 4.69 3.28 0.70 983 4.52 3.16 0.70 1037 4.41 3.09 0.70 1069 4.27 2.99 0.70 1123 32 26 4.83 2.80 0.58 1037 4.69 2.72 0.58 1091 4.62 2.68 0.58 1123 4.48 2.60 0.58 1156
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
OBH629A
21
PERFORMANCE DATA COOL operation at Rated frequency
MUZ-SF35VE MUZ-SF35VEH
CAPACITY: 3.5 kW SHF: 0.80 INPUT: 1080 W
INDOOR
DB (°C)
INDOOR
WB (°C)
OUTDOOR DB (°C)
35 40 46
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT 21 18 3.43 2.13 0.62 1058 3.15 1.95 0.62 1123 2.91 1.80 0.62 1166 21 20 3.61 1.80 0.50 1102 3.36 1.68 0.50 1156 3.12 1.56 0.50 1220 22 18 3.43 2.26 0.66 1058 3.15 2.08 0.66 1123 2.91 1.92 0.66 1166 22 20 3.61 1.95 0.54 1102 3.36 1.81 0.54 1156 3.12 1.68 0.54 1220 22 22 3.82 1.60 0.42 1145 3.57 1.50 0.42 1210 3.33 1.40 0.42 1253 23 18 3.43 2.40 0.70 1058 3.15 2.21 0.70 1123 2.91 2.03 0.70 1166 23 20 3.61 2.09 0.58 1102 3.36 1.95 0.58 1156 3.12 1.81 0.58 1220 23 22 3.82 1.75 0.46 1145 3.57 1.64 0.46 1210 3.33 1.53 0.46 1253 24 18 3.43 2.54 0.74 1058 3.15 2.33 0.74 1123 2.91 2.15 0.74 1166 24 20 3.61 2.24 0.62 1102 3.36 2.08 0.62 1156 3.12 1.93 0.62 1220 24 22 3.82 1.91 0.50 1145 3.57 1.79 0.50 1210 3.33 1.66 0.50 1253 24 24 4.03 1.53 0.38 1188 3.78 1.44 0.38 1242 3.57 1.36 0.38 1296 25 18 3.43 2.68 0.78 1058 3.15 2.46 0.78 1123 2.91 2.27 0.78 1166 25 20 3.61 2.38 0.66 1102 3.36 2.22 0.66 1156 3.12 2.06 0.66 1220 25 22 3.82 2.06 0.54 1145 3.57 1.93 0.54 1210 3.33 1.80 0.54 1253 25 24 4.03 1.69 0.42 1188 3.78 1.59 0.42 1242 3.57 1.50 0.42 1296 26 18 3.43 2.81 0.82 1058 3.15 2.58 0.82 1123 2.91 2.38 0.82 1166 26 20 3.61 2.52 0.70 1102 3.36 2.35 0.70 1156 3.12 2.18 0.70 1220 26 22 3.82 2.21 0.58 1145 3.57 2.07 0.58 1210 3.33 1.93 0.58 1253 26 24 4.03 1.85 0.46 1188 3.78 1.74 0.46 1242 3.57 1.64 0.46 1296 26 26 4.24 1.44 0.34 1231 3.99 1.36 0.34 1285 3.75 1.27 0.34 1339 27 18 3.43 2.95 0.86 1058 3.15 2.71 0.86 1123 2.91 2.50 0.86 1166 27 20 3.61 2.67 0.74 1102 3.36 2.49 0.74 1156 3.12 2.31 0.74 1220 27 22 3.82 2.37 0.62 1145 3.57 2.21 0.62 1210 3.33 2.06 0.62 1253 27 24 4.03 2.01 0.50 1188 3.78 1.89 0.50 1242 3.57 1.79 0.50 1296 27 26 4.24 1.61 0.38 1231 3.99 1.52 0.38 1285 3.75 1.42 0.38 1339 28 18 3.43 3.09 0.90 1058 3.15 2.84 0.90 1123 2.91 2.61 0.90 1166 28 20 3.61 2.81 0.78 1102 3.36 2.62 0.78 1156 3.12 2.43 0.78 1220 28 22 3.82 2.52 0.66 1145 3.57 2.36 0.66 1210 3.33 2.19 0.66 1253 28 24 4.03 2.17 0.54 1188 3.78 2.04 0.54 1242 3.57 1.93 0.54 1296 28 26 4.24 1.78 0.42 1231 3.99 1.68 0.42 1285 3.75 1.57 0.42 1339 29 18 3.43 3.22 0.94 1058 3.15 2.96 0.94 1123 2.91 2.73 0.94 1166 29 20 3.61 2.96 0.82 1102 3.36 2.76 0.82 1156 3.12 2.55 0.82 1220 29 22 3.82 2.67 0.70 1145 3.57 2.50 0.70 1210 3.33 2.33 0.70 1253 29 24 4.03 2.33 0.58 1188 3.78 2.19 0.58 1242 3.57 2.07 0.58 1296 29 26 4.24 1.95 0.46 1231 3.99 1.84 0.46 1285 3.75 1.72 0.46 1339 30 18 3.43 3.36 0.98 1058 3.15 3.09 0.98 1123 2.91 2.85 0.98 1166 30 20 3.61 3.10 0.86 1102 3.36 2.89 0.86 1156 3.12 2.68 0.86 1220 30 22 3.82 2.82 0.74 1145 3.57 2.64 0.74 1210 3.33 2.46 0.74 1253 30 24 4.03 2.50 0.62 1188 3.78 2.34 0.62 1242 3.57 2.21 0.62 1296 30 26 4.24 2.12 0.50 1231 3.99 2.00 0.50 1285 3.75 1.87 0.50 1339 31 18 3.43 3.43 1.00 1058 3.15 3.15 1.00 1123 2.91 2.91 1.00 1166 31 20 3.61 3.24 0.90 1102 3.36 3.02 0.90 1156 3.12 2.80 0.90 1220 31 22 3.82 2.98 0.78 1145 3.57 2.78 0.78 1210 3.33 2.59 0.78 1253 31 24 4.03 2.66 0.66 1188 3.78 2.49 0.66 1242 3.57 2.36 0.66 1296 31 26 4.24 2.29 0.54 1231 3.99 2.15 0.54 1285 3.75 2.02 0.54 1339 32 18 3.43 3.43 1.00 1058 3.15 3.15 1.00 1123 2.91 2.91 1.00 1166 32 20 3.61 3.39 0.94 1102 3.36 3.16 0.94 1156 3.12 2.93 0.94 1220 32 22 3.82 3.13 0.82 1145 3.57 2.93 0.82 1210 3.33 2.73 0.82 1253 32 24 4.03 2.82 0.70 1188 3.78 2.65 0.70 1242 3.57 2.50 0.70 1296 32 26 4.24 2.46 0.58 1231 3.99 2.31 0.58 1285 3.75 2.17 0.58 1339
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
OBH629A
22
PERFORMANCE DATA COOL operation at Rated frequency
MUZ-SF42VE MUZ-SF42VEH
CAPACITY: 4.2 kW SHF: 0.72 INPUT: 1340 W
INDOOR
DB (°C)
INDOOR
WB (°C)
OUTDOOR DB (°C)
21 25 27 30
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT 21 18 4.94 2.66 0.54 1072 4.73 2.55 0.54 1126 4.54 2.45 0.54 1179 4.37 2.36 0.54 1233 21 20 5.15 2.16 0.42 1126 4.94 2.07 0.42 1193 4.79 2.01 0.42 1219 4.62 1.94 0.42 1273 22 18 4.94 2.86 0.58 1072 4.73 2.74 0.58 1126 4.54 2.63 0.58 1179 4.37 2.53 0.58 1233 22 20 5.15 2.37 0.46 1126 4.94 2.27 0.46 1193 4.79 2.20 0.46 1219 4.62 2.13 0.46 1273 22 22 5.36 1.82 0.34 1166 5.17 1.76 0.34 1240 5.04 1.71 0.34 1273 4.83 1.64 0.34 1327 23 18 4.94 3.06 0.62 1072 4.73 2.93 0.62 1126 4.54 2.81 0.62 1179 4.37 2.71 0.62 1233 23 20 5.15 2.57 0.50 1126 4.94 2.47 0.50 1193 4.79 2.39 0.50 1219 4.62 2.31 0.50 1273 23 22 5.36 2.03 0.38 1166 5.17 1.96 0.38 1240 5.04 1.92 0.38 1273 4.83 1.84 0.38 1327 24 18 4.94 3.26 0.66 1072 4.73 3.12 0.66 1126 4.54 2.99 0.66 1179 4.37 2.88 0.66 1233 24 20 5.15 2.78 0.54 1126 4.94 2.66 0.54 1193 4.79 2.59 0.54 1219 4.62 2.49 0.54 1273 24 22 5.36 2.25 0.42 1166 5.17 2.17 0.42 1240 5.04 2.12 0.42 1273 4.83 2.03 0.42 1327 24 24 5.63 1.69 0.30 1219 5.42 1.63 0.30 1286 5.29 1.59 0.30 1327 5.12 1.54 0.30 1394 25 18 4.94 3.45 0.70 1072 4.73 3.31 0.70 1126 4.54 3.18 0.70 1179 4.37 3.06 0.70 1233 25 20 5.15 2.98 0.58 1126 4.94 2.86 0.58 1193 4.79 2.78 0.58 1219 4.62 2.68 0.58 1273 25 22 5.36 2.46 0.46 1166 5.17 2.38 0.46 1240 5.04 2.32 0.46 1273 4.83 2.22 0.46 1327 25 24 5.63 1.91 0.34 1219 5.42 1.84 0.34 1286 5.29 1.80 0.34 1327 5.12 1.74 0.34 1394 26 18 4.94 3.65 0.74 1072 4.73 3.50 0.74 1126 4.54 3.36 0.74 1179 4.37 3.23 0.74 1233 26 20 5.15 3.19 0.62 1126 4.94 3.06 0.62 1193 4.79 2.97 0.62 1219 4.62 2.86 0.62 1273 26 22 5.36 2.68 0.50 1166 5.17 2.58 0.50 1240 5.04 2.52 0.50 1273 4.83 2.42 0.50 1327 26 24 5.63 2.14 0.38 1219 5.42 2.06 0.38 1286 5.29 2.01 0.38 1327 5.12 1.95 0.38 1394 26 26 5.80 1.51 0.26 1286 5.63 1.46 0.26 1353 5.54 1.44 0.26 1394 5.38 1.40 0.26 1434 27 18 4.94 3.85 0.78 1072 4.73 3.69 0.78 1126 4.54 3.54 0.78 1179 4.37 3.41 0.78 1233 27 20 5.15 3.40 0.66 1126 4.94 3.26 0.66 1193 4.79 3.16 0.66 1219 4.62 3.05 0.66 1273 27 22 5.36 2.89 0.54 1166 5.17 2.79 0.54 1240 5.04 2.72 0.54 1273 4.83 2.61 0.54 1327 27 24 5.63 2.36 0.42 1219 5.42 2.28 0.42 1286 5.29 2.22 0.42 1327 5.12 2.15 0.42 1394 27 26 5.80 1.74 0.30 1286 5.63 1.69 0.30 1353 5.54 1.66 0.30 1394 5.38 1.61 0.30 1434 28 18 4.94 4.05 0.82 1072 4.73 3.87 0.82 1126 4.54 3.72 0.82 1179 4.37 3.58 0.82 1233 28 20 5.15 3.60 0.70 1126 4.94 3.45 0.70 1193 4.79 3.35 0.70 1219 4.62 3.23 0.70 1273 28 22 5.36 3.11 0.58 1166 5.17 3.00 0.58 1240 5.04 2.92 0.58 1273 4.83 2.80 0.58 1327 28 24 5.63 2.59 0.46 1219 5.42 2.49 0.46 1286 5.29 2.43 0.46 1327 5.12 2.36 0.46 1394 28 26 5.80 1.97 0.34 1286 5.63 1.91 0.34 1353 5.54 1.88 0.34 1394 5.38 1.83 0.34 1434 29 18 4.94 4.24 0.86 1072 4.73 4.06 0.86 1126 4.54 3.90 0.86 1179 4.37 3.76 0.86 1233 29 20 5.15 3.81 0.74 1126 4.94 3.65 0.74 1193 4.79 3.54 0.74 1219 4.62 3.42 0.74 1273 29 22 5.36 3.32 0.62 1166 5.17 3.20 0.62 1240 5.04 3.12 0.62 1273 4.83 2.99 0.62 1327 29 24 5.63 2.81 0.50 1219 5.42 2.71 0.50 1286 5.29 2.65 0.50 1327 5.12 2.56 0.50 1394 29 26 5.80 2.20 0.38 1286 5.63 2.14 0.38 1353 5.54 2.11 0.38 1394 5.38 2.04 0.38 1434 30 18 4.94 4.44 0.90 1072 4.73 4.25 0.90 1126 4.54 4.08 0.90 1179 4.37 3.93 0.90 1233 30 20 5.15 4.01 0.78 1126 4.94 3.85 0.78 1193 4.79 3.73 0.78 1219 4.62 3.60 0.78 1273 30 22 5.36 3.53 0.66 1166 5.17 3.41 0.66 1240 5.04 3.33 0.66 1273 4.83 3.19 0.66 1327 30 24 5.63 3.04 0.54 1219 5.42 2.93 0.54 1286 5.29 2.86 0.54 1327 5.12 2.77 0.54 1394 30 26 5.80 2.43 0.42 1286 5.63 2.36 0.42 1353 5.54 2.33 0.42 1394 5.38 2.26 0.42 1434 31 18 4.94 4.64 0.94 1072 4.73 4.44 0.94 1126 4.54 4.26 0.94 1179 4.37 4.11 0.94 1233 31 20 5.15 4.22 0.82 1126 4.94 4.05 0.82 1193 4.79 3.93 0.82 1219 4.62 3.79 0.82 1273 31 22 5.36 3.75 0.70 1166 5.17 3.62 0.70 1240 5.04 3.53 0.70 1273 4.83 3.38 0.70 1327 31 24 5.63 3.26 0.58 1219 5.42 3.14 0.58 1286 5.29 3.07 0.58 1327 5.12 2.97 0.58 1394 31 26 5.80 2.67 0.46 1286 5.63 2.59 0.46 1353 5.54 2.55 0.46 1394 5.38 2.47 0.46 1434 32 18 4.94 4.84 0.98 1072 4.73 4.63 0.98 1126 4.54 4.45 0.98 1179 4.37 4.28 0.98 1233 32 20 5.15 4.42 0.86 1126 4.94 4.24 0.86 1193 4.79 4.12 0.86 1219 4.62 3.97 0.86 1273 32 22 5.36 3.96 0.74 1166 5.17 3.82 0.74 1240 5.04 3.73 0.74 1273 4.83 3.57 0.74 1327 32 24 5.63 3.49 0.62 1219 5.42 3.36 0.62 1286 5.29 3.28 0.62 1327 5.12 3.18 0.62 1394 32 26 5.80 2.90 0.50 1286 5.63 2.81 0.50 1353 5.54 2.77 0.50 1394 5.38 2.69 0.50 1434
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
OBH629A
23
PERFORMANCE DATA COOL operation at Rated frequency
MUZ-SF42VE MUZ-SF42VEH
CAPACITY: 4.2 kW SHF: 0.72 INPUT: 1340 W
INDOOR
DB (°C)
INDOOR
WB (°C)
OUTDOOR DB (°C)
35 40 46
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT 21 18 4.12 2.22 0.54 1313 3.78 2.04 0.54 1394 3.49 1.88 0.54 1447 21 20 4.33 1.82 0.42 1367 4.03 1.69 0.42 1434 3.74 1.57 0.42 1514 22 18 4.12 2.39 0.58 1313 3.78 2.19 0.58 1394 3.49 2.02 0.58 1447 22 20 4.33 1.99 0.46 1367 4.03 1.85 0.46 1434 3.74 1.72 0.46 1514 22 22 4.58 1.56 0.34 1420 4.28 1.46 0.34 1501 3.99 1.36 0.34 1554 23 18 4.12 2.55 0.62 1313 3.78 2.34 0.62 1394 3.49 2.16 0.62 1447 23 20 4.33 2.16 0.50 1367 4.03 2.02 0.50 1434 3.74 1.87 0.50 1514 23 22 4.58 1.74 0.38 1420 4.28 1.63 0.38 1501 3.99 1.52 0.38 1554 24 18 4.12 2.72 0.66 1313 3.78 2.49 0.66 1394 3.49 2.30 0.66 1447 24 20 4.33 2.34 0.54 1367 4.03 2.18 0.54 1434 3.74 2.02 0.54 1514 24 22 4.58 1.92 0.42 1420 4.28 1.80 0.42 1501 3.99 1.68 0.42 1554 24 24 4.83 1.45 0.30 1474 4.54 1.36 0.30 1541 4.28 1.29 0.30 1608 25 18 4.12 2.88 0.70 1313 3.78 2.65 0.70 1394 3.49 2.44 0.7 1447 25 20 4.33 2.51 0.58 1367 4.03 2.34 0.58 1434 3.74 2.17 0.58 1514 25 22 4.58 2.11 0.46 1420 4.28 1.97 0.46 1501 3.99 1.84 0.46 1554 25 24 4.83 1.64 0.34 1474 4.54 1.54 0.34 1541 4.28 1.46 0.34 1608 26 18 4.12 3.05 0.74 1313 3.78 2.80 0.74 1394 3.49 2.58 0.74 1447 26 20 4.33 2.68 0.62 1367 4.03 2.50 0.62 1434 3.74 2.32 0.62 1514 26 22 4.58 2.29 0.50 1420 4.28 2.14 0.50 1501 3.99 2.00 0.50 1554 26 24 4.83 1.84 0.38 1474 4.54 1.72 0.38 1541 4.28 1.63 0.38 1608 26 26 5.08 1.32 0.26 1528 4.79 1.24 0.26 1595 4.49 1.17 0.26 1662 27 18 4.12 3.21 0.78 1313 3.78 2.95 0.78 1394 3.49 2.72 0.78 1447 27 20 4.33 2.86 0.66 1367 4.03 2.66 0.66 1434 3.74 2.47 0.66 1514 27 22 4.58 2.47 0.54 1420 4.28 2.31 0.54 1501 3.99 2.15 0.54 1554 27 24 4.83 2.03 0.42 1474 4.54 1.91 0.42 1541 4.28 1.80 0.42 1608 27 26 5.08 1.52 0.30 1528 4.79 1.44 0.30 1595 4.49 1.35 0.30 1662 28 18 4.12 3.38 0.82 1313 3.78 3.10 0.82 1394 3.49 2.86 0.82 1447 28 20 4.33 3.03 0.70 1367 4.03 2.82 0.70 1434 3.74 2.62 0.70 1514 28 22 4.58 2.66 0.58 1420 4.28 2.48 0.58 1501 3.99 2.31 0.58 1554 28 24 4.83 2.22 0.46 1474 4.54 2.09 0.46 1541 4.28 1.97 0.46 1608 28 26 5.08 1.73 0.34 1528 4.79 1.63 0.34 1595 4.49 1.53 0.34 1662 29 18 4.12 3.54 0.86 1313 3.78 3.25 0.86 1394 3.49 3.00 0.86 1447 29 20 4.33 3.20 0.74 1367 4.03 2.98 0.74 1434 3.74 2.77 0.74 1514 29 22 4.58 2.84 0.62 1420 4.28 2.66 0.62 1501 3.99 2.47 0.62 1554 29 24 4.83 2.42 0.50 1474 4.54 2.27 0.50 1541 4.28 2.14 0.50 1608 29 26 5.08 1.93 0.38 1528 4.79 1.82 0.38 1595 4.49 1.71 0.38 1662 30 18 4.12 3.70 0.90 1313 3.78 3.40 0.90 1394 3.49 3.14 0.90 1447 30 20 4.33 3.37 0.78 1367 4.03 3.14 0.78 1434 3.74 2.92 0.78 1514 30 22 4.58 3.02 0.66 1420 4.28 2.83 0.66 1501 3.99 2.63 0.66 1554 30 24 4.83 2.61 0.54 1474 4.54 2.45 0.54 1541 4.28 2.31 0.54 1608 30 26 5.08 2.13 0.42 1528 4.79 2.01 0.42 1595 4.49 1.89 0.42 1662 31 18 4.12 3.87 0.94 1313 3.78 3.55 0.94 1394 3.49 3.28 0.94 1447 31 20 4.33 3.55 0.82 1367 4.03 3.31 0.82 1434 3.74 3.07 0.82 1514 31 22 4.58 3.20 0.70 1420 4.28 3.00 0.70 1501 3.99 2.79 0.70 1554 31 24 4.83 2.80 0.58 1474 4.54 2.63 0.58 1541 4.28 2.48 0.58 1608 31 26 5.08 2.34 0.46 1528 4.79 2.20 0.46 1595 4.49 2.07 0.46 1662 32 18 4.12 4.03 0.98 1313 3.78 3.70 0.98 1394 3.49 3.42 0.98 1447 32 20 4.33 3.72 0.86 1367 4.03 3.47 0.86 1434 3.74 3.21 0.86 1514 32 22 4.58 3.39 0.74 1420 4.28 3.17 0.74 1501 3.99 2.95 0.74 1554 32 24 4.83 2.99 0.62 1474 4.54 2.81 0.62 1541 4.28 2.66 0.62 1608 32 26 5.08 2.54 0.50 1528 4.79 2.39 0.50 1595 4.49 2.25 0.50 1662
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
OBH629A
24
PERFORMANCE DATA COOL operation at Rated frequency
MUZ-SF50VE MUZ-SF50VEH
CAPACITY: 5.0 kW SHF: 0.70 INPUT: 1660 W
INDOOR
DB (°C)
INDOOR
WB (°C)
OUTDOOR DB (°C)
21 25 27 30
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT 21 18 5.88 3.06 0.52 1328 5.63 2.93 0.52 1394 5.40 2.81 0.52 1461 5.20 2.70 0.52 1527 21 20 6.13 2.45 0.40 1394 5.88 2.35 0.40 1477 5.70 2.28 0.40 1511 5.50 2.20 0.40 1577 22 18 5.88 3.29 0.56 1328 5.63 3.15 0.56 1394 5.40 3.02 0.56 1461 5.20 2.91 0.56 1527 22 20 6.13 2.70 0.44 1394 5.88 2.59 0.44 1477 5.70 2.51 0.44 1511 5.50 2.42 0.44 1577 22 22 6.38 2.04 0.32 1444 6.15 1.97 0.32 1536 6.00 1.92 0.32 1577 5.75 1.84 0.32 1643 23 18 5.88 3.53 0.60 1328 5.63 3.38 0.60 1394 5.40 3.24 0.60 1461 5.20 3.12 0.60 1527 23 20 6.13 2.94 0.48 1394 5.88 2.82 0.48 1477 5.70 2.74 0.48 1511 5.50 2.64 0.48 1577 23 22 6.38 2.30 0.36 1444 6.15 2.21 0.36 1536 6.00 2.16 0.36 1577 5.75 2.07 0.36 1643 24 18 5.88 3.76 0.64 1328 5.63 3.60 0.64 1394 5.40 3.46 0.64 1461 5.20 3.33 0.64 1527 24 20 6.13 3.19 0.52 1394 5.88 3.06 0.52 1477 5.70 2.96 0.52 1511 5.50 2.86 0.52 1577 24 22 6.38 2.55 0.40 1444 6.15 2.46 0.40 1536 6.00 2.40 0.40 1577 5.75 2.30 0.40 1643 24 24 6.70 1.88 0.28 1511 6.45 1.81 0.28 1594 6.30 1.76 0.28 1643 6.10 1.71 0.28 1726 25 18 5.88 4.00 0.68 1328 5.63 3.83 0.68 1394 5.40 3.67 0.68 1461 5.20 3.54 0.68 1527 25 20 6.13 3.43 0.56 1394 5.88 3.29 0.56 1477 5.70 3.19 0.56 1511 5.50 3.08 0.56 1577 25 22 6.38 2.81 0.44 1444 6.15 2.71 0.44 1536 6.00 2.64 0.44 1577 5.75 2.53 0.44 1643 25 24 6.70 2.14 0.32 1511 6.45 2.06 0.32 1594 6.30 2.02 0.32 1643 6.10 1.95 0.32 1726 26 18 5.88 4.23 0.72 1328 5.63 4.05 0.72 1394 5.40 3.89 0.72 1461 5.20 3.74 0.72 1527 26 20 6.13 3.68 0.60 1394 5.88 3.53 0.60 1477 5.70 3.42 0.60 1511 5.50 3.30 0.60 1577 26 22 6.38 3.06 0.48 1444 6.15 2.95 0.48 1536 6.00 2.88 0.48 1577 5.75 2.76 0.48 1643 26 24 6.70 2.41 0.36 1511 6.45 2.32 0.36 1594 6.30 2.27 0.36 1643 6.10 2.20 0.36 1726 26 26 6.90 1.66 0.24 1594 6.70 1.61 0.24 1677 6.60 1.58 0.24 1726 6.40 1.54 0.24 1776 27 18 5.88 4.47 0.76 1328 5.63 4.28 0.76 1394 5.40 4.10 0.76 1461 5.20 3.95 0.76 1527 27 20 6.13 3.92 0.64 1394 5.88 3.76 0.64 1477 5.70 3.65 0.64 1511 5.50 3.52 0.64 1577 27 22 6.38 3.32 0.52 1444 6.15 3.20 0.52 1536 6.00 3.12 0.52 1577 5.75 2.99 0.52 1643 27 24 6.70 2.68 0.40 1511 6.45 2.58 0.40 1594 6.30 2.52 0.40 1643 6.10 2.44 0.40 1726 27 26 6.90 1.93 0.28 1594 6.70 1.88 0.28 1677 6.60 1.85 0.28 1726 6.40 1.79 0.28 1776 28 18 5.88 4.70 0.80 1328 5.63 4.50 0.80 1394 5.40 4.32 0.80 1461 5.20 4.16 0.80 1527 28 20 6.13 4.17 0.68 1394 5.88 4.00 0.68 1477 5.70 3.88 0.68 1511 5.50 3.74 0.68 1577 28 22 6.38 3.57 0.56 1444 6.15 3.44 0.56 1536 6.00 3.36 0.56 1577 5.75 3.22 0.56 1643 28 24 6.70 2.95 0.44 1511 6.45 2.84 0.44 1594 6.30 2.77 0.44 1643 6.10 2.68 0.44 1726 28 26 6.90 2.21 0.32 1594 6.70 2.14 0.32 1677 6.60 2.11 0.32 1726 6.40 2.05 0.32 1776 29 18 5.88 4.94 0.84 1328 5.63 4.73 0.84 1394 5.40 4.54 0.84 1461 5.20 4.37 0.84 1527 29 20 6.13 4.41 0.72 1394 5.88 4.23 0.72 1477 5.70 4.10 0.72 1511 5.50 3.96 0.72 1577 29 22 6.38 3.83 0.60 1444 6.15 3.69 0.60 1536 6.00 3.60 0.60 1577 5.75 3.45 0.60 1643 29 24 6.70 3.22 0.48 1511 6.45 3.10 0.48 1594 6.30 3.02 0.48 1643 6.10 2.93 0.48 1726 29 26 6.90 2.48 0.36 1594 6.70 2.41 0.36 1677 6.60 2.38 0.36 1726 6.40 2.30 0.36 1776 30 18 5.88 5.17 0.88 1328 5.63 4.95 0.88 1394 5.40 4.75 0.88 1461 5.20 4.58 0.88 1527 30 20 6.13 4.66 0.76 1394 5.88 4.47 0.76 1477 5.70 4.33 0.76 1511 5.50 4.18 0.76 1577 30 22 6.38 4.08 0.64 1444 6.15 3.94 0.64 1536 6.00 3.84 0.64 1577 5.75 3.68 0.64 1643 30 24 6.70 3.48 0.52 1511 6.45 3.35 0.52 1594 6.30 3.28 0.52 1643 6.10 3.17 0.52 1726 30 26 6.90 2.76 0.40 1594 6.70 2.68 0.40 1677 6.60 2.64 0.40 1726 6.40 2.56 0.40 1776 31 18 5.88 5.41 0.92 1328 5.63 5.18 0.92 1394 5.40 4.97 0.92 1461 5.20 4.78 0.92 1527 31 20 6.13 4.90 0.80 1394 5.88 4.70 0.80 1477 5.70 4.56 0.80 1511 5.50 4.40 0.80 1577 31 22 6.38 4.34 0.68 1444 6.15 4.18 0.68 1536 6.00 4.08 0.68 1577 5.75 3.91 0.68 1643 31 24 6.70 3.75 0.56 1511 6.45 3.61 0.56 1594 6.30 3.53 0.56 1643 6.10 3.42 0.56 1726 31 26 6.90 3.04 0.44 1594 6.70 2.95 0.44 1677 6.60 2.90 0.44 1726 6.40 2.82 0.44 1776 32 18 5.88 5.64 0.96 1328 5.63 5.40 0.96 1394 5.40 5.18 0.96 1461 5.20 4.99 0.96 1527 32 20 6.13 5.15 0.84 1394 5.88 4.94 0.84 1477 5.70 4.79 0.84 1511 5.50 4.62 0.84 1577 32 22 6.38 4.59 0.72 1444 6.15 4.43 0.72 1536 6.00 4.32 0.72 1577 5.75 4.14 0.72 1643 32 24 6.70 4.02 0.60 1511 6.45 3.87 0.60 1594 6.30 3.78 0.60 1643 6.10 3.66 0.60 1726 32 26 6.90 3.31 0.48 1594 6.70 3.22 0.48 1677 6.60 3.17 0.48 1726 6.40 3.07 0.48 1776
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
OBH629A
25
PERFORMANCE DATA COOL operation at Rated frequency
MUZ-SF50VE MUZ-SF50VEH
CAPACITY: 5.0 kW SHF: 0.70 INPUT: 1660 W
INDOOR
DB (°C)
INDOOR
WB (°C)
OUTDOOR DB (°C)
35 40 46
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT 21 18 4.90 2.55 0.52 1627 4.50 2.34 0.52 1726 4.15 2.16 0.52 1793 21 20 5.15 2.06 0.40 1693 4.80 1.92 0.40 1776 4.45 1.78 0.40 1876 22 18 4.90 2.74 0.56 1627 4.50 2.52 0.56 1726 4.15 2.32 0.56 1793 22 20 5.15 2.27 0.44 1693 4.80 2.11 0.44 1776 4.45 1.96 0.44 1876 22 22 5.45 1.74 0.32 1760 5.10 1.63 0.32 1859 4.75 1.52 0.32 1926 23 18 4.90 2.94 0.60 1627 4.50 2.70 0.60 1726 4.15 2.49 0.60 1793 23 20 5.15 2.47 0.48 1693 4.80 2.30 0.48 1776 4.45 2.14 0.48 1876 23 22 5.45 1.96 0.36 1760 5.10 1.84 0.36 1859 4.75 1.71 0.36 1926 24 18 4.90 3.14 0.64 1627 4.50 2.88 0.64 1726 4.15 2.66 0.64 1793 24 20 5.15 2.68 0.52 1693 4.80 2.50 0.52 1776 4.45 2.31 0.52 1876 24 22 5.45 2.18 0.40 1760 5.10 2.04 0.40 1859 4.75 1.90 0.40 1926 24 24 5.75 1.61 0.28 1826 5.40 1.51 0.28 1909 5.10 1.43 0.28 1992 25 18 4.90 3.33 0.68 1627 4.50 3.06 0.68 1726 4.15 2.82 0.68 1793 25 20 5.15 2.88 0.56 1693 4.80 2.69 0.56 1776 4.45 2.49 0.56 1876 25 22 5.45 2.40 0.44 1760 5.10 2.24 0.44 1859 4.75 2.09 0.44 1926 25 24 5.75 1.84 0.32 1826 5.40 1.73 0.32 1909 5.10 1.63 0.32 1992 26 18 4.90 3.53 0.72 1627 4.50 3.24 0.72 1726 4.15 2.99 0.72 1793 26 20 5.15 3.09 0.60 1693 4.80 2.88 0.60 1776 4.45 2.67 0.60 1876 26 22 5.45 2.62 0.48 1760 5.10 2.45 0.48 1859 4.75 2.28 0.48 1926 26 24 5.75 2.07 0.36 1826 5.40 1.94 0.36 1909 5.10 1.84 0.36 1992 26 26 6.05 1.45 0.24 1892 5.70 1.37 0.24 1975 5.35 1.28 0.24 2058 27 18 4.90 3.72 0.76 1627 4.50 3.42 0.76 1726 4.15 3.15 0.76 1793 27 20 5.15 3.30 0.64 1693 4.80 3.07 0.64 1776 4.45 2.85 0.64 1876 27 22 5.45 2.83 0.52 1760 5.10 2.65 0.52 1859 4.75 2.47 0.52 1926 27 24 5.75 2.30 0.40 1826 5.40 2.16 0.40 1909 5.10 2.04 0.40 1992 27 26 6.05 1.69 0.28 1892 5.70 1.60 0.28 1975 5.35 1.50 0.28 2058 28 18 4.90 3.92 0.80 1627 4.50 3.60 0.80 1726 4.15 3.32 0.80 1793 28 20 5.15 3.50 0.68 1693 4.80 3.26 0.68 1776 4.45 3.03 0.68 1876 28 22 5.45 3.05 0.56 1760 5.10 2.86 0.56 1859 4.75 2.66 0.56 1926 28 24 5.75 2.53 0.44 1826 5.40 2.38 0.44 1909 5.10 2.24 0.44 1992 28 26 6.05 1.94 0.32 1892 5.70 1.82 0.32 1975 5.35 1.71 0.32 2058 29 18 4.90 4.12 0.84 1627 4.50 3.78 0.84 1726 4.15 3.49 0.84 1793 29 20 5.15 3.71 0.72 1693 4.80 3.46 0.72 1776 4.45 3.20 0.72 1876 29 22 5.45 3.27 0.60 1760 5.10 3.06 0.60 1859 4.75 2.85 0.60 1926 29 24 5.75 2.76 0.48 1826 5.40 2.59 0.48 1909 5.10 2.45 0.48 1992 29 26 6.05 2.18 0.36 1892 5.70 2.05 0.36 1975 5.35 1.93 0.36 2058 30 18 4.90 4.31 0.88 1627 4.50 3.96 0.88 1726 4.15 3.65 0.88 1793 30 20 5.15 3.91 0.76 1693 4.80 3.65 0.76 1776 4.45 3.38 0.76 1876 30 22 5.45 3.49 0.64 1760 5.10 3.26 0.64 1859 4.75 3.04 0.64 1926 30 24 5.75 2.99 0.52 1826 5.40 2.81 0.52 1909 5.10 2.65 0.52 1992 30 26 6.05 2.42 0.40 1892 5.70 2.28 0.40 1975 5.35 2.14 0.40 2058 31 18 4.90 4.51 0.92 1627 4.50 4.14 0.92 1726 4.15 3.82 0.92 1793 31 20 5.15 4.12 0.80 1693 4.80 3.84 0.80 1776 4.45 3.56 0.80 1876 31 22 5.45 3.71 0.68 1760 5.10 3.47 0.68 1859 4.75 3.23 0.68 1926 31 24 5.75 3.22 0.56 1826 5.40 3.02 0.56 1909 5.10 2.86 0.56 1992 31 26 6.05 2.66 0.44 1892 5.70 2.51 0.44 1975 5.35 2.35 0.44 2058 32 18 4.90 4.70 0.96 1627 4.50 4.32 0.96 1726 4.15 3.98 0.96 1793 32 20 5.15 4.33 0.84 1693 4.80 4.03 0.84 1776 4.45 3.74 0.84 1876 32 22 5.45 3.92 0.72 1760 5.10 3.67 0.72 1859 4.75 3.42 0.72 1926 32 24 5.75 3.45 0.60 1826 5.40 3.24 0.60 1909 5.10 3.06 0.60 1992 32 26 6.05 2.90 0.48 1892 5.70 2.74 0.48 1975 5.35 2.57 0.48 2058
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
OBH629A
26
PERFORMANCE DATA HEAT operation at Rated frequency
MUZ-SF25VE MUZ-SF25VEH
CAPACITY: 3.2 kW INPUT: 780 W
INDOOR
DB (°C)
OUTDOOR WB (°C)
-10 -5 0 5 10 15 20
Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT 15 2.02 507 2.43 608 2.85 686 3.26 741 3.68 788 4.06 811 4.48 827 21 1.92 546 2.30 647 2.72 718 3.10 772 3.52 811 3.90 835 4.30 866 26 1.73 585 2.14 686 2.53 757 2.94 811 3.36 850 3.74 874 4.16 897
MUZ-SF35VE MUZ-SF35VEH
CAPACITY: 4.0 kW INPUT: 1030 W
INDOOR
DB (°C)
OUTDOOR WB (°C)
-10 -5 0 5 10 15 20
Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT 15 2.52 670 3.04 803 3.56 906 4.08 979 4.60 1040 5.08 1071 5.60 1092 21 2.40 721 2.88 855 3.40 948 3.88 1020 4.40 1071 4.88 1102 5.38 1143 26 2.16 773 2.68 906 3.16 999 3.68 1071 4.20 1123 4.68 1154 5.20 1185
MUZ-SF42VE MUZ-SF42VEH
CAPACITY: 5.4 kW INPUT: 1580 W
INDOOR
DB (°C)
OUTDOOR WB (°C)
-10 -5 0 5 10 15 20
Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT 15 3.40 1027 4.10 1232 4.81 1390 5.51 1501 6.21 1596 6.86 1643 7.56 1675 21 3.24 1106 3.89 1311 4.59 1454 5.24 1564 5.94 1643 6.59 1691 7.26 1754 26 2.92 1185 3.62 1390 4.27 1533 4.97 1643 5.67 1722 6.32 1770 7.02 1817
MUZ-SF50VE MUZ-SF50VEH
CAPACITY: 5.8 kW INPUT: 1700 W
INDOOR
DB (°C)
OUTDOOR WB (°C)
-10 -5 0 5 10 15 20
Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT 15 3.65 1105 4.41 1326 5.16 1496 5.92 1615 6.67 1717 7.37 1768 8.12 1802 21 3.48 1190 4.18 1411 4.93 1564 5.63 1683 6.38 1768 7.08 1819 7.80 1887 26 3.13 1275 3.89 1496 4.58 1649 5.34 1768 6.09 1853 6.79 1904 7.54 1955
NOTE: Q : Total capacity (kW) INPUT : Total power input (W) DB: Dry-bulb temperature WB: Wet-bulb temperature
OBH629A
27
MUZ-SF25VE MUZ-SF25VEH MUZ-SF35VE MUZ-SF35VEH MUZ-SF42VE MUZ-SF42VEH MUZ-SF50VE MUZ-SF50VEH
9-2. R.V. COIL CONTROL
Heating
. . . . . . . . . . . . . . . . .
ON
Cooling
. . . . . . . . . . . . . . . . .
OFF
Dry
. . . . . . . . . . . . . . . . . . . .
OFF
NOTE: The 4-way valve reverses for 5 seconds right before start-up of the compressor.
ON
OFF
ON
OFF
Outdoor fan motor
Compressor
5 seconds 15 seconds
ON OFF
Compressor
Outdoor fan motor
R.V.coil
ON OFF
ON OFF
<COOL>
5 seconds
<HEAT>
5 seconds
9-1. OUTDOOR FAN MOTOR CONTROL
The fan motor turns ON/OFF, interlocking with the compressor. [ON] The fan motor turns ON 5 seconds before the compressor starts up. [OFF] The fan motor turns OFF 15 seconds after the compressor has stopped running.
9-3. RELATION BETWEEN MAIN SENSOR AND ACTUATOR
Sensor Purpose
Actuator
Compressor
LEV
Outdoor fan
motor
R.V.coil
Indoor fan
motor
Defrost
heater
Discharge temperature thermistor
Protection
○○
Indoor coil temperature thermistor
Cooling: Coil frost prevention
Heating: High pressure protec­tion
○○
Defrost thermistor Heating: Defrosting
○○○○○
Fin temperature thermistor Protection
○○
Ambient temperature thermistor
Cooling: Low ambient tempera­ture operation
○○○
Heating: Defrosting (Heater)
Outdoor heat exchanger tem­perature thermistor
Cooling: Low ambient tempera­ture operation
○○○
Cooling: High pressure protec­tion
○○○
ACTUATOR CONTROL
9
OBH629A
28
10-1. CHANGE IN DEFROST SETTING Changing defrost finish temperature
<JS> To change the defrost finish temperature, cut/solder the JS wire of the outdoor inverter P.C. board. (Refer to
11-6-1.)
Jumper wire
Defrost fi nish temperature (°C)
MUZ-SF25/35/42 MUZ-SF50
JS
Soldered (Initial setting) 5 9
None (Cut) 10 18
10-2. PRE-HEAT CONTROL SETTING
PRE-HEAT CONTROL
When moisture gets into the refrigerant cycle, it may interfere the start-up of the compressor at low outside temperature. The pre-heat control prevents this interference. The pre-heat control turns ON when the discharge temperature thermis­tor is 20°C or below. When the pre-heat control turns ON, the compressor is energized. (About 50 W)
<JK> To activate the pre-heat control, cut JK wire of the inverter P.C. board. (Refer to 11-6.1)
NOTE: When the inverter P.C. board is replaced, check the Jumper wires, and cut/solder them if necessary.
MUZ-SF25VE MUZ-SF25VEH MUZ-SF35VE MUZ-SF35VEH MUZ-SF42VE MUZ-SF42VEH MUZ-SF50VE MUZ-SF50VEH
SERVICE FUNCTIONS
10
11-1. CAUTIONS ON TROUBLESHOOTING
1. Before troubleshooting, check the following
1) Check the power supply voltage.
2) Check the indoor/outdoor connecting wire for miswiring.
2. Take care of the following during servicing
1) Before servicing the air conditioner, be sure to turn OFF the main unit first with the remote controller, and then after confirming the horizontal vane is closed, turn OFF the breaker and/or disconnect the power plug.
2) Be sure to turn OFF the power supply before removing the front panel, the cabinet, the top panel, and the electronic control P.C. board.
3) When removing the electrical parts, be careful of the residual voltage of smoothing capacitor.
4) When removing the electronic control P.C. board, hold the edge of the board with care NOT to apply stress on the components.
5) When connecting or disconnecting the connectors, hold the housing of the connector. DO NOT pull the lead wires.
MUZ-SF25VE MUZ-SF25VEH MUZ-SF35VE MUZ-SF35VEH MUZ-SF42VE MUZ-SF42VEH MUZ-SF50VE MUZ-SF50VEH
TROUBLESHOOTING
11
3. Troubleshooting procedure
1) Check if the OPERATION INDICATOR lamp on the indoor unit is flashing on and off to indicate an abnormality. To make sure, check how many times the OPERATION INDICATOR lamp is flashing on and off before starting service work.
2) Before servicing, check that the connector and terminal are connected properly.
3) When the electronic control P.C. board seems to be defective, check the copper foil pattern for disconnection and the components for bursting and discoloration.
4) Refer to 11-2 and 11-3.
Lead wiring
Housing point
<Incorrect>
<Correct>
OBH629A
29
Outline of the function This air conditioner can memorize the abnormal condition which has occurred once. Even though LED indication listed on the troubleshooting check table (11-3.) disappears, the memorized failure details can be recalled.
11-2. FAILURE MODE RECALL FUNCTION
1. Flow chart of failure mode recall function for the indoor/outdoor unit
NOTE: 1. Make sure to release the failure mode recall function after it is set up, otherwise the unit cannot operate properly.
2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.
Does the left lamp of OPERATION INDICATOR lamp on the indoor unit blink at the interval of 0.5 seconds? Blinks: Either indoor or outdoor unit is abnormal. Beep is emit-
ted at the same timing as the blinking of the left lamp of OPERATION INDICATOR lamp. 2
Indoor unit is normal. But the outdoor unit might be abnormal because there are some abnor­malities that can not be recalled with this way. Confi rm if outdoor unit is abnormal according to the detailed outdoor unit failure mode recall function. (Refer to 11-2.2)
No
Yes
The cause of abnormality cannot be found because the abnormality does not recur.
Setting up the failure mode recall function
Turn ON the power supply. <Preparation of the remote controller>
While pressing OPERATION SELECT button and TEMP
button on the remote
controller at the same time, press RESET button.
First, release RESET button.
Hold down the other two buttons for another 3 seconds. Make sure that the indicators
on the LCD screen shown in the right fi gure are all displayed. Then release the but- tons.
Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit.
1
Judgment of indoor/outdoor abnormality
Before blinking, does the left lamp of OPERATION INDICA­TOR lamp stay ON for 3 seconds? Stays ON for 3 seconds (without beep): The outdoor unit is abnormal.
The indoor unit is abnormal. Check the blinking pattern, and confi rm the abnormal point with the indoor unit failure mode table. (Refer to indoor unit service manual.) Make sure to check at least two consecutive blinking cycles.
2
Releasing the failure mode recall function
Release the failure mode recall function by the following procedures. Turn OFF the power supply and turn it ON again. Press RESET button of the remote controller.
The outdoor unit is abnormal. Check the blinking pattern, and identify the abnormal point by reffering to the outdoor unit failure mode table. (Refer to 11-2.3) Make sure to check at least two consecutive blinking cycles.
3
Repair the failure parts.
Deleting the memorized abnormal condition
After repairing the unit, recall the failure mode again according to "Setting up the failure mode recall
function" mentioned above.
Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed)
with the remote controller headed towards the indoor unit. Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted. Release the failure mode recall function according to "Releasing the failure mode recall function"
mentioned above.
Operational procedure
Yes (Blinks)
No (OFF)
1. Regardless of normal or abnormal condition, a short beep is emitted once the signal is received.
2. Blinking pattern when the indoor unit is abnormal:
3.Blinking pattern when the outdoor unit is abnormal:
ON
OFF
Beeps
Repeated cycle Repeated cycle
ON
OFF
No beep Beeps
Repeated cycle
2.5-second OFF
Blinking at 0.5­second interval
2.5-second OFF 3-second ON
Blinking at 0.5­second interval
Beeps
Repeated cycle
2.5-second OFF
Blinking at 0.5­second interval
No beep Beeps
Repeated cycle
2.5-second OFF 3-second ON
Blinking at 0.5­second interval
Repeated cycle
Beeps
OBH629A
30
2. Flow chart of the detailed outdoor unit failure mode recall function
2.Blinking pattern when outdoor unit is abnormal:
ON
OFF
No beep
Beeps
Repeated cycle
2.5-second OFF 3-second ON
Blinking at 0.5­second interval
No beep Beeps
Repeated cycle
2.5-second OFF 3-second ON
Blinking at 0.5-
second interval
Repeated cycle
Does the left lamp of OPERATION INDICATOR lamp on the indoor unit blink at the interval of 0.5 seconds? Blinks: The outdoor unit is abnormal. Beep is emitted
at the same timing as the blinking of the left lamp of OPERATION INDICATOR lamp. 2
Yes (Blinks
)
No (OFF)
The outdoor unit might be abnormal. Check if outdoor unit is abnormal according to the following procedures.
Operational procedure
Make sure that the remote controller is set to the failure mode recall func-
With the remote controller headed towards the indoor unit, press TEMP
button to adjust the set temperature to 25°C. 1
1. Regardless of normal or abnormal condition, 2 short beeps are emitted as the signal is received.
The outdoor unit is abnormal. Check the blinking pattern, and identify the abnormal point by reffering to the outdoor unit failure mode table (11-2.3.). Make sure to check at least two consecutive blinking cycles.
2
Releasing the failure mode recall function
Release the failure mode recall function by the following procedures. Turn OFF the power supply and turn it ON again. Press RESET button of the remote controller.
Repair the failure parts.
The outdoor unit is normal.
Release the failure mode recall function accord­ing to the left mentioned procedure.
Deleting the memorized abnormal condition
After repairing the unit, recall the failure mode again according to "Setting up the failure mode recall
function" (11-2.1.).
Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed) with
the remote controller headed towards the indoor unit.
Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted.
4
Release the failure mode recall function according to "Releasing the failure mode recall function" men-
tioned above.
NOTE: 1. Make sure to release the failure mode recall function after it is set up, otherwise the unit cannot operate properly.
2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.
4
The information regarding whether the
connected outdoor unit is a low-standby-
power model or a non-low-standby-power model will also be initialized.
(Default= compatible with a low-standby-
power model)
NOTE: It takes up to 1 minute to indicate the outdoor unit
abnormality.
Even if the OPERATION INDICATOR lamp is not
lighting, keep checking at least 1 minute or longer.
OBH629A
31
3. Outdoor unit failure mode table
The left lamp of
OPERATION
INDICATOR
lamp
(Indoor unit)
Abnormal point
(Failure mode/protection)
LED indication
(Outdoor P.C. board)
Condition Remedy
Indoor/outdoor
unit failure
mode recall
function
Outdoor unit failure mode
recall function
OFF None (Normal)
—— —
1-time fl ash
2.5 seconds OFF
Indoor/outdoor communication, receiving error
Any signals from the inverter P.C. board cannot be received normally for 3 minutes.
•Refer to 11-5.
How to check miswiring and serial signal error.
○○
Indoor/outdoor communication, receiving error
Although the inverter P.C. board sends signal "0", signal "1" has been received 30 consecutive times.
•Refer to 11-5.
How to check miswiring and serial signal error.
2-time fl ash
2.5 seconds OFF
Outdoor power system
Overcurrent protection cut-out operates 3 consecutive times within 1 minute after the compressor gets started.
Reconnect connectors. Refer to 11-5. "How to check inverter/ compressor". Check the stop valve.
○○
3-time fl ash
2.5 seconds OFF
Discharge temperature thermistor
1-time fl ash every
2.5 seconds
Thermistor shorts or opens during compressor running.
Refer to 11-5. "Check of outdoor thermistors". Defective outdoor thermistors can be identifi ed by checking the blinking pattern of LED.
○○
Defrost thermistor Fin temperature thermistor 3-time fl ash
2.5 seconds OFF
P.C. board temperature thermistor
4-time fl ash
2.5 seconds OFF
Ambient temperature thermistor
2-time fl ash
2.5 seconds OFF
Outdoor heat exchanger temperature thermistor
4-time fl ash
2.5 seconds OFF
Overcurrent 11-time fl ash
2.5 seconds OFF
Large current fl ows into power module. Reconnect
compressor connector. Refer to 11-5. "How to check inverter/ compressor". Check the stop valve.
Compressor synchronous abnormality (Compressor start-up failure protection)
12-time fl ash
2.5 seconds OFF
Waveform of compressor current is distorted.
Reconnect compressor connector. Refer to 11-5. "How to check inverter/ compressor".
5-time fl ash
2.5 seconds OFF
Discharge temperature
Temperature of discharge temperature thermistor exceeds 116°C, compressor stops. Compressor can restart if discharge temperature thermistor reads 100°C or less 3 minutes later.
Check the refrigerant circuit and refrigerant amount. Refer to 11-5. "Check of LEV".
6-time fl ash
2.5 seconds OFF
High pressure
Temperature indoor coil thermistor exceeds 70°C in HEAT mode. Temperature defrost thermistor exceeds 70°C in COOL mode.
Check the refrigerant circuit and refrigerant amount. Check the stop valve.
7-time fl ash
2.5 seconds OFF
Fin temperature/ P.C. board temperature
7-time fl ash
2.5 seconds OFF
Temperature of fi n temperature thermistor on the inverter P.C. board exceeds 75 ~ 86°C, or temperature of P.C. board temperature thermistor on the inverter P.C. board exceeds 72 ~ 85°C.
Check around outdoor unit. Check outdoor unit air passage. Refer to 11-5. "Check of outdoor fan motor".
8-time fl ash
2.5 seconds OFF
Outdoor fan motor
Outdoor fan has stopped 3 times in a row within 30 seconds after outdoor fan start-up.
Refer to 11-5. "Check of outdoor fan motor". Refer to 11-5. "Check of inverter P.C. board".
• —
9-time fl ash
2.5 seconds OFF
Nonvolatile memory data 5-time fl ash
2.5 seconds OFF
Nonvolatile memory data cannot be read properly.
Replace the inverter P.C. board.
○○
Power module 6-time fl ash
2.5 seconds OFF
The interface short circuit occurs in the output of the power module (IC700). The compressor winding shorts circuit.
Refer to 11-5. "How to check inverter/ compressor".
10-time fl ash
2.5 seconds OFF
Discharge temperature
Temperature of discharge temperature thermistor has been 50°C or less for 20 minutes.
Refer to 11-5. "Check of LEV". Check the refrigerant circuit and refrigerant amount.
11-time fl ash
2.5 seconds OFF
DC voltage 8-time fl ash
2.5 seconds OFF
DC voltage of inverter cannot be detected normally.
Refer to 11-5. "How to check inverter/ compressor".
• —
Each phase current of compressor
9-time fl ash
2.5 seconds OFF
Each phase current of compressor cannot be detected normally.
14-time fl ash
2.5 seconds OFF
Stop valve (Closed valve) 14-time fl ash
2.5 seconds OFF
Closed valve is detected by compressor current.
Check the stop valve.
○○
4-way valve/ Pipe temperature
16-time fl ash
2.5 seconds OFF
The 4-way valve does not work properly. The indoor coil thermistor detects an abnormal temperature.
Check 4-way valve. Replace inverter P.C. board.
NOTE: Blinking patterns of this mode differ from the ones of Troubleshooting check table (11-3.).
OBH629A
32
11-3. TROUBLESHOOTING CHECK TABLE
No. Symptom LED indication
Abnormal point/
Condition
Condition Remedy
1
Outdoor unit does not op­erate.
1-time fl ash every
2.5 seconds
Outdoor power sys­tem
Overcurrent protection cut-out operates 3 consecutive times within 1 minute after the compressor gets started.
Reconnect connector of compres­sor. Refer to 11-5. "How to check in­verter/compressor". Check the stop valve.
2
Outdoor thermistors Discharge temperature thermistor, fi n temperature thermistor,
defrost thermistor, P.C. board temperature thermistor, outdoor heat exchanger temperature thermistor or ambient tempera­ture thermistor shorts or opens during compressor running.
Refer to 11-5. "Check of outdoor thermistors".
3
Outdoor control sys­tem
Nonvolatile memory data cannot be read properly. (The left lamp of OPERATION INDICATOR lamp of the indoor
unit lights up or fl ashes 7-time.)
Replace inverter P.C. board.
4
6-time fl ash
2.5 seconds OFF
Serial signal The communication fails between the indoor and outdoor unit
for 3 minutes.
Refer to 11-5. "How to check miswiring and serial signal error.
5
11-time fl ash
2.5 seconds OFF
Stop valve/ Closed valve
Closed valve is detected by compressor current. Check the stop valve.
6
14-time fl ash
2.5 seconds OFF
Outdoor unit (Other abnormality)
Outdoor unit is defective. Refer to 11-2.2. "Flow chart of the
detailed outdoor unit failure mode recall function".
7
16-time fl ash
2.5 seconds OFF
4-way valve/
Pipe temperature
The 4-way valve does not work properly. The indoor coil thermistor detects an abnormal temperature.
Refer to 11-5. "Check of R.V. coil". Replace inverter P.C. board.
8
'Outdoor unit stops and restarts 3 minutes later' is repeated.
2-time fl ash
2.5 seconds OFF
Overcurrent protec­tion
Large current fl ows into power module.
Reconnect connector of compressor. Refer to 11-5. "How to check in­verter/compressor". Check the stop valve.
9
3-time fl ash
2.5 seconds OFF
Discharge tempera­ture overheat pro­tection
Temperature of discharge temperature thermistor exceeds 116°C, compressor stops. Compressor can restart if discharge temperature thermistor reads 100°C or less 3 minutes later.
Check the refrigerant circuit and refrigerant amount. Refer to 11-5. "Check of LEV".
10
4-time fl ash
2.5 seconds OFF
Fin temperature /P.C. board tem­perature thermistor overheat protection
Temperature of fi n temperature thermistor on the heat sink exceeds 75 ~ 86°C or temperature of P.C. board temperature thermistor on the inverter P.C.board exceeds 72 ~ 85°C.
Check around outdoor unit. Check outdoor unit air passage. Refer to 11-5. "Check of outdoor fan motor".
11
5-time fl ash
2.5 seconds OFF
High pressure pro­tection
Indoor coil thermistor exceeds 70°C in HEAT mode. Defrost thermistor exceeds 70°C in COOL mode.
Check the refrigerant circuit and refrigerant amount. Check the stop valve.
12
8-time fl ash
2.5 seconds OFF
Compressor syn­chronous abnormal­ity
The waveform of compressor current is distorted.
Reconnect connector of compressor. Refer to 11-5. "How to check in­verter/compressor".
13
10-time fl ash
2.5 seconds OFF
Outdoor fan motor Outdoor fan has stopped 3 times in a row within 30 seconds
after outdoor fan start-up.
Refer to 11-5. "Check of outdoor fan motor. Refer to 11-5. "Check of inverter P.C. board.
14
12-time fl ash
2.5 seconds OFF
Each phase current of compressor
Each phase current of compressor cannot be detected nor­mally.
Refer to 11-5. "How to check in­verter/compressor".
15
13-time fl ash
2.5 seconds OFF
DC voltage DC voltage of inverter cannot be detected normally. Refer to 11-5. "How to check in-
verter/compressor".
16
Outdoor unit operates.
1-time fl ash
2.5 seconds OFF
Frequency drop by current protection
When the input current exceeds approximately 7A(EF25)/ 8A(EF35)/9A(EF42)/12A(EF50), compressor frequency lowers.
The unit is normal, but check the following. Check if the indoor fi lters are clogged. Check if the refrigerant is short. Check if the indoor/outdoor unit air circulation is short cycled.
17
3-time fl ash
2.5 seconds OFF
Frequency drop by high pressure pro­tection
Temperature of indoor coil thermistor exceeds 55°C in HEAT mode, compressor frequency lowers.
Frequency drop by defrosting in COOL mode
Indoor coil thermistor reads 8°C or less in COOL mode, com­pressor frequency lowers.
18
4-time fl ash
2.5 seconds OFF
Frequency drop by discharge tempera­ture protection
Temperature of discharge temperature thermistor exceeds 111°C, compressor frequency lowers.
Check the refrigerant circuit and refrigerant amount. Refer to 11-5.
"Check of LEV". Refer to 11-5. "Check of outdoor thermistors".
19
5-time fl ash
2.5 seconds OFF
Outside temperature thermistor protec­tion
When the outside temperature thermistor shorts or opens, protective operation without that thermistor is performed.
Refer to 11-5. Check of outdoor thermistors.
20
Outdoor unit operates.
7-time fl ash
2.5 seconds OFF
Low discharge tem­perature protection
Temperature of discharge temperature thermistor has been 50°C or less for 20 minutes.
Refer to 11-5. "Check of LEV". Check the refrigerant circuit and the refrigerant amount.
21
8-time fl ash
2.5 seconds OFF
PAM protection PAM: Pulse Ampli­tude Modulation
The overcurrent fl ows into PFC (Power factor correction : IC820) or the bus-bar voltage reaches 394 V or more, PAM stops and restarts.
This is not malfunction. PAM pro­tection will be activated in the fol­lowing cases:
1 Instantaneous power voltage
drop. (Short time power failure)
2 When the power supply voltage
is high.
22
9-time fl ash
2.5 seconds OFF
Inverter check mode The connector of compressor is disconnected, inverter check
mode starts.
Check if the connector of the com­pressor is correctly connected. Refer to 11-5. "How to check inverter/compressor".
NOTE: 1. The location of LED is illustrated at the right fi gure. Refer to 11-6.1.
2. LED is lighted during normal operation. The fl ashing frequency shows the number of times the LED blinks after every 2.5-second OFF.
(Example) When the fl ashing frequency is “2”.
ON OFF
2.5-second OFF
2.5-second OFF
0.5-second ON
0.5-second ON LED
Flashing
Inverter P.C. board
OBH629A
33
11-4. TROUBLE CRITERION OF MAIN PARTS
MUZ-SF25VE MUZ-SF25VEH MUZ-SF35VE MUZ-SF35VEH MUZ-SF42VE MUZ-SF42VEH MUZ-SF50VE MUZ-SF50VEH
Part name Check method and criterion Figure
Defrost thermistor (RT61) Fin temperature
thermistor (RT64) Ambient temperature
thermistor (RT65) Outdoor heat exchanger
temperature thermistor (RT68)
Measure the resistance with a tester. Refer to 11-6. “Test point diagram and voltage”, 1. “Inverter P.C.
board”, for the chart of thermistor.
Discharge temperature thermistor (RT62)
Measure the resistance with a tester. Before measurement, hold the thermistor with your hands to warm it up.
Refer to 11-6. “Test point diagram and voltage”, 1. “Inverter P.C. board”, for the chart of thermistor.
Compressor
Measure the resistance between terminals using a tester. (Temperature: -10 ~ 40°C)
Normal (Ω)
MUZ-SF25 MUZ-SF35 MUZ-SF42 MUZ-SF50
U-V U-W V-W
1.20 ~ 1.72 1.36 ~ 1.93 1.52 ~ 2.17 0.78 ~ 1.11
Outdoor fan motor
Measure the resistance between lead wires using a tester. (Temperature: -10 ~ 40°C)
Color of lead wire
Normal (Ω)
MUZ-SF25/35/42 MUZ-SF50
RED – BLK BLK – WHT WHT – RED
29 ~ 42 12 ~ 17
R. V. coil (21S4)
Measure the resistance using a tester. (Temperature: -10 ~ 40°C)
Normal (kΩ)
1.19 ~ 1.78
Expansion valve coil (LEV)
Measure the resistance using a tester. (Temperature: -10 ~ 40°C)
MUZ-SF25/35/42
Color of lead wire Normal (Ω)
WHT – RED
37 ~ 54
RED – ORN YLW – BRN
BRN – BLU
Measure the resistance using a tester. (Temperature: -10 ~ 40°C)
MUZ-SF50
Color of lead wire Normal (Ω)
RED – ORN
37 ~ 54
RED – WHT
RED – BLU
RED – YLW
Defrost heater
MUZ-SF•VEH
Measure the resistance using a tester. (Temperature: -10 ~ 40°C)
Normal (Ω)
349 ~ 428
W
U
V
WHT
RED BLK
W
U
V
WHT
RED BLK
LEV
WHT
RED ORN
YLW
BRN
BLU
RED
(+12V)
YLW
BLU
WHT ORN
LEV
OBH629A
34
11-5. TROUBLESHOOTING FLOW
Are the voltages balanced?
Disconnect the connector between compressor and the power module (IC700).
Replace the inverter P.C. board.
Check the voltage between terminals.
Check the compressor.
See 11-5. “Check of compressor”.
No
Yes
See 11-5. “Check of open phase”.
A How to check inverter/compressor
Refer to 11-5. “Check of compressor operation time”. Does the compressor operate continuously?
Refer to 11-5. “Check of compressor start failure”.
OK.
No
Yes
Refer to 11-5. “Check of compressor winding”. Is the compressor normal?
Replace the compressor.
No
Yes
B Check of open phase
C Check of compressor
With the connector between the compressor and the power module disconnected, activate the inverter and check if the in­verter is normal by measuring the voltage balance between the terminals.
Output voltage is 50 - 130 V. (The voltage may differ according to the tester.) << Operation method>>
Start cooling or heating operation by pressing EMERGENCY OPERATION switch on the indoor unit. (TEST RUN OPERA-
TION: Refer to 8-3.) <<Measurement point>> At 3 points BLK (U)-WHT (V) BLK (U)-RED (W) WHT(V)-RED (W)
NOTE: 1. Output voltage varies according to power supply voltage.
2. Measure the voltage by analog type tester.
3. During this check, LED of the inverter P.C. board fl ashes 9 times. (Refer to 11-6.1.)
Measure AC voltage between the lead wires at 3 points.
OBH629A
35
F Check of compressor start failure
D Check of compressor winding
E Check of compressor operation time
Disconnect the connector between the compressor and power module, and measure the resistance between the compressor terminals.
<<Measurement point>> at 3 points BLK-WHT BLK-RED WHT-RED <<Judgement>> Refer to 11-4. 0 [Ω] ················Abnormal [short] Infinite [Ω] ·······Abnormal [open] NOTE: Be sure to zero the ohmmeter before measurement.
Measure the resistance between the lead wires at 3 points.
After the compressor is heated with a drier, does the compressor start? 1
Replace the compressor.
Compressor start failure. Activate pre-heat control. (Refer to 10-2. "PRE-HEAT CONTROL SETTING".)
No
Yes
Does the compressor run for 10 seconds or more after it starts?
Check the refrigerant circuit. Check the stop valve.
Yes
No
1 Heat the compressor with a drier for about 20 minutes. Do not recover refrigerant gas while heating.
Heating part
Connect the compressor and activate the inverter. Then measure
the time until the inverter stops due to over current. <<Operation method>> Start heating or cooling operation by pressing EMERGENCY OPERATION switch on the indoor unit. (TEST RUN OPERATION: Refer to 8-3.) <<Measurement>> Measure the time from the start of compressor to the stop of compressor due to overcurrent.
Compressor starts
Abnormal (IC700 failure) (Compressor winding short)
Abnormal (Compressor lock out) (Starting defect)
Abnormal (Poor contact,) (Inverter P.C. board defect) (Disconnected connector)
Abnormal (Refrigerant circuit defect) (Closed valve)
Normal
0 second 1 second
2 seconds
10 seconds
10 minutes
<<Judgement>>
Confi rm that ~ is normal.
•Electrical circuit check . Contact of the compressor connector . Output voltage of inverter P.C. board and balance of them (See 11-5. .) . Direct current voltage between DB61(+) and (-) on the inverter P.C. board . Voltage between outdoor terminal block S1-S2
OBH629A
36
G Check of outdoor thermistors
H Check of R.V. coil
Thermistor Symbol Connector, Pin No. Board
Defrost RT61 Between CN641 pin1 and pin2
Inverter P.C. board
Discharge temperature RT62 Between CN641 pin3 and pin4 Fin temperature RT64 Between CN642 pin1 and pin2 Ambient temperature RT65 Between CN643 pin1 and pin2 Outdoor heat exchanger temperature RT68 Between CN644 pin1 and pin3
Replace the thermistor except RT64. When RT64 is abnormal, replace the inverter P.C. board.
Replace the inverter P.C. board.
No
No
Is the resistance of thermistor normal? (Refer to 11-6.1.)
Reconnect the connector of thermistor. Turn ON the power supply and press EMERGENCY OPERATION switch.
Does the unit operate for 10 minutes or more without showing thermistor abnormality?
OK. (Cause is poor contact.)
Yes
Yes
Disconnect the connector of thermistor in the inverter P.C. board (see below table), and measure the resistance of thermistor.
First of all, measure the resistance of R.V. coil to check if the coil is defective. Refer to 11-4. In case CN721 is disconnected or R.V. coil is open, voltage is generated between the terminal pins of the connector
although no signal is being transmitted to R.V. coil.
Check if CN721 is connected.
Is there 230 VAC between CN721 and
on the inverter P.C. board 3 minutes
after the power supply is turned ON?
No
Yes
Replace the inverter P.C. board.
Replace the 4-way valve.
Unit operates COOL mode even if it is set to HEAT mode.
Is there 230 VAC between CN721 and
on the inverter P.C. board 3 minutes
after the power supply is turned ON?
Yes
No
Replace the inverter P.C. board.
Replace the 4-way valve.
Unit operates HEAT mode even if it is set to COOL mode.
Disconnect connector between the compressor and the power module. Turn ON the power supply and press EMERGENCY OPERATION switch twice (HEAT mode).
Disconnect connector between the compressor and the power module. Turn ON the power supply and press EMERGENCY OPERATION switch once (COOL mode).
OBH629A
37
I Check of outdoor fan motor
Is the resistance between each ter­minal of outdoor fan motor normal? (Refer to 11-4.)
Disconnect CN932 from the inverter P.C. board, and turn on the power supply.
Rotate the outdoor fan motor manually and measure the voltage of CN931. Between 1(+) and 5(-) Between 2(+) and 5(-) Between 3(+) and 5(-)
Does the voltage between each terminal become 5 and 0 VDC repeatedly?
Does the outdoor fan motor rotate smoothly?
Replace the outdoor fan motor.
Replace the inverter P.C. board.
Yes
Yes
No
(Fixed to either 5 or 0 VDC)
No
No
Yes
Disconnect the connectors CN931 and CN932 from the inverter P.C. board. Check the connection between the connector CN931 and CN932.
OBH629A
38
J Check of power supply
Is there voltage 230 VAC between the indoor terminal block S1 and S2?
No
Yes
Replace the indoor electronic control P.C. board.
Rectify indoor/outdoor connecting wire.
Yes
If light up, OK. If fl ash, refer to 11-3.
Does The left lamp of OPERATION INDICATOR lamp on the indoor unit light up?
Dose LED on the inverter P.C. board light up or fl ash? (Refer to 11-6.1.)
No
Replace the inverter P.C. board.
Is there voltage 260 - 370 VDC between DB61 (+) and DB61 (–) on the inverter P.C. board? (Refer to 11-6.1.)
No
Check the electric parts in main circuit.
Yes
Yes
No
Disconnect the connector between compressor and power module. Turn ON power supply and press EMERGENCY OPERATION switch.
Inverter P.C. board (Solder side)
DB61
260 - 370 VDC
OBH629A
39
Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit. 1
Expansion valve operates in full-opening direction.
OK
NOTE: After check of LEV, do the undermentioned operations.
1. Turn OFF the power supply and turn it ON again.
2. Press RESET button on the remote controller.
1. Regardless of normal or abnormal condition, a short beep is emitted once the signal is received.
Measure each voltage between connector pins of CN724 on the inverter P.C. board.
1. Pin (-) — Pin (+)
2. Pin (-) — Pin (+)
3. Pin (-) — Pin (+)
4. Pin (-) — Pin (+) Is there about 3 - 5 VAC between each?
NOTE: Measure the voltage by an analog
tester.
Properly fi x the LEV coil to the expansion valve.
Replace the inverter P.C. board.
Replace the LEV coil.
Replace the expansion valve.
Is LEV coil properly fi xed to the expansion valve?
Does the resistance of LEV coil have the characteristics? (Refer to 11-4.)
Do you hear the expansion valve "click, click·······"? Do you feel the expansion valve vibrate on touching it ?
Turn ON the power supply. <Preparation of the remote controller>
While pressing both OPERATION SELECT button
and TEMP
button on the remote controller at the
same time, press RESET button.
First, release RESET button.
Hold down the other two buttons for another 3 sec-
onds. Confi rm that the indicators on the LCD screen shown in the right fi gure are all displayed.
Then release the buttons.
Yes
No
No
Yes
No
Yes
No
Yes
K Check of LEV (Expansion valve)
OBH629A
40
Check the outdoor fan motor. (Refer to 11-5. .)
Is the fuse (F901) blown on the in­verter P.C. board?
Check the connection of the connectors (CN931, CN932) of the outdoor fan motor. If the connection is poor, make it correct.
Operate the outdoor unit by starting EMERGENCY OPERATION.
Check the LED indication on the in­verter P.C. board. Does the LED fl ash 10 times?
Replace the inverter P.C. board.
Check the corresponding parts following LED indication. (Refer to 11-3.)
Yes
No
Yes (10-time fl ash)
No
L Check of inverter P.C. board
OBH629A
41
M How to check miswiring and serial signal error
Turn OFF inverter-controlled lighting equipment. Turn OFF the power supply and then turn ON again. Press EMERGENCY OPERATION switch.
A
Is serial signal error indicated 6 minutes later?
B
Yes
Reinstall either the unit or the light away from each other. Attach a fi lter on remote control receiving section of the indoor unit.
No
Turn the main power supply OFF.
Is there rated voltage in the power supply?
Yes
No
Check for incorrect indoor-outdoor connecting wiring.
Check the power supply.
A
Is there rated voltage between outdoor terminal block S1 and S2?
No
Yes
Check for miswiring, broken wires, and loose wire connection between the main power supply and outdoor terminal block S1 and between the main power supply and outdoor terminal block S2.
Wait for 2 or more minutes after the main power supply is turned on. Touch S2 and S3 with tester probes and start the emergency operation.
When the emergency operation starts, does the rated voltage occur for 2 seconds between indoor terminal block S2 and S3?
Yes
Turn the main power supply OFF.
Turn the main power supply ON.
Wait for 2 or more minutes after the main power sup­ply is turned ON. Touch CN202
and JPG with tester
probes and start the emergency operation.
During the emergency operation, does DC (2V or more) occur for 2 seconds between CN202
and JPG on the indoor electronic control P.C. board?
No
Does the indoor OPERATION INDICATOR lamp (left) blink continuously 6 minutes after the emergency operation starts?
No
Does the outdoor LED light up?
Replace the indoor electronic control P.C. board.
Replace the indoor power P.C. board.
Yes
Yes
Does the outdoor LED blink 6 times?
Yes
Confi rm that the thermostat is OFF and wiring is not loose.
No
Does DC (6V or more) occur between indoor terminal block S2 and S3?
Yes
Replace the outdoor inverter P.C. board. 1
No
Turn the main power supply OFF. Replace the indoor power P.C. board.
Start the emergency operation.
No
Yes
Repair completed.
Does DC (20V or more) occur between indoor terminal block S2 and S3 ?
No
Yes
Replace the outdoor inverter P.C. board. 1
Replace the indoor electronic control P.C. board.
1. Electric charge may remain immediately after the main power supply is turned OFF. Perform the procedure after 3 minutes.
Replace the outdoor inverter P.C. board. 1
Turn the main power supply ON.
Does the indoor OPERATION INDICATOR lamp (left) blink continuously 6 minutes after the emergency operation starts?
Yes
No
Turn the main power supply ON.
B
No
No
Was the indoor unit ever connected to the Multi (MXZ) series and operated (turned on)?
The connection information to the Multi series is stored in the indoor unit. Refer to “Deleting the memorized abnormal condition” described in 11-2.1 to clear the error history. When the error history is being cleared, the con­nection information also will be initialized. The indoor unit will be compatible with a low-standby-power model after initialization.
OK
Yes
OBH629A
42
N Electromagnetic noise enters into TV sets or radios
Yes
Is the unit earthed?
No
Earth the unit.
Yes
Is the distance between the antennas and the indoor unit within 3 m, or is the distance between the antennas and the outdoor unit within 3 m?
No
Extend the distance between the antennas and the indoor unit, and/or the antennas and the outdoor unit.
Is the distance between the TV sets or radios and the indoor unit within 1 m, or is the distance between the TV sets or radios and the outdoor unit within 3 m?
Yes
Extend the distance between the TV sets and/or radios and the indoor unit, or the TV sets or radios and the outdoor unit.
Are the antennas damaged? Is the coaxial cable damaged? Is there any poor contact in the anten­na wiring?
Yes
No
No
Replace or repair the antenna. Replace or repair the coaxial cable.
Is the indoor/outdoor connecting wire of the air conditioner and the wiring of the antennas close?
Yes
Extend the distance between the indoor/outdoor connecting wire of the air conditioner and the wir­ing of the antennas.
No
Even if all of the above conditions are fulfi lled, the electromagnetic noise may enter, depending on the electric fi eld strength or the installation condition (combination of specifi c conditions such as antennas or wiring). Check the following before asking for service.
1. Devices affected by the electromagnetic noise TV sets, radios (FM/AM broadcast, shortwave)
2. Channel, frequency, broadcast station affected by the electromagnetic noise
3. Channel, frequency, broadcast station unaffected by the electromagnetic noise
4. Layout of: indoor/outdoor unit of the air conditioner, indoor/outdoor wiring, earth wire, antennas, wiring from antennas, receiver
5. Electric fi eld intensity of the broadcast station affected by the electromagnetic noise
6. Presence or absence of amplifi er such as booster
7. Operation condition of air conditioner when the electromagnetic noise enters in
1) Turn OFF the power supply once, and then turn ON the power supply. In this situation, check for the electromagnetic noise.
2) Within 3 minutes after turning ON the power supply, press OPERATE/STOP (ON/OFF) button on the remote controller for power ON, and check for the electromagnetic noise.
3) After a short time (3 minutes later after turning ON), the outdoor unit starts running. During operation, check for the electromagnetic noise.
4) Press OPERATE/STOP (ON/OFF) button on the remote controller for power OFF, when the outdoor unit stops but the indoor/outdoor communication still runs on. In this situation, check for the electromagnetic noise.
OBH629A
43
O Check of defrost heater
Check the following points before checking electric continuity.
1. Does the resistance of ambient temperature thermistor have the characteristics? Refer to 11-6.1.
2. Is the resistance of defrost heater normal? Refer to 11-4.
3. Does the heater protector remain conducted (not open)?
4. Are both ambient temperature thermistor and circuit of defrost heater securely connected to connectors?
Is there 230 VAC between CN722 and on the inverter P.C. board? Refer to 11-6.1.
Not the problem of the inverter P.C. board.
Replace the inverter P.C. board.
No
Yes
In HEAT mode, for more than 5 minutes, let the ambient temperature thermistor continue to read 5°C or below, and let the defrost thermistor continue to read -1°C or below.
NOTE: In case both thermistors are more than the above temperature, cool them with cold
water etc...
MUZ-SF•VEH
OBH629A
44
-20 -10 0 10 20 30 40
0
10
20
30
40
50
60
70
80
90
100
Temperature( )
Defrost thermistor(RT61) Ambient temperature thermistor(RT65) Outdoor heat exchanger temperature thermistor(RT68)
Temperature( )
Discharge temperature thermistor(RT62)
0 102030405060708090100110120
0
100
200
300
400
500
600
700
0 1020304050607080
0
20
40
60
80
100
120
140
160
180
200
Temperature( )
Fin temperature thermistor(RT64)
Resistance(k )
Resistance(k )
Resistance(k )
1. Inverter P.C. board
MUZ-SF25VE MUZ-SF25VEH MUZ-SF35VE MUZ-SF35VEH MUZ-SF42VE MUZ-SF42VEH MUZ-SF50VE MUZ-SF50VEH
11-6. TEST POINT DIAGRAM AND VOLTAGE
Fin temperature
thermistor/RT64
(CN642)
Ambient temperature
thermistor/RT65
(CN643)
Discharge temperature
thermistor/RT62
(CN641)
Defrost thermistor
/RT61(CN641)
DB61 260 - 370 VDC
Front side of unit
230 VAC
Smoothing capacitor (C62)
Output to drive compressor (LDU, LDV, LDW)
(+)
(-)
Fuse (F701) T3.15AL250V
Smoothing capacitor (C61)
Smoothing capacitor (C63)
MUZ-SF42/50
Fuse (F901) T3.15AL250V
R.V.coil (CN721) 230 VAC
Jumper wire for changing defrost setting (JS)
Signal of outdoor
fan motor (CN931)
230 VAC
Outdoor heat exchanger
temperature thermistor
/RT68 (CN644)
Jumper wire for pre-heat control setting (JK)
Heater connector (CN722)
MUZ-SF25/35VEH MUZ-SF42/50VEH
Fuse (F801) T3.15AL250V
Back side of unit
LEV connector
(CN724)
Output to drive outdoor fan motor (CN932)
LED
OBH629A
45
12-1. MUZ-SF25VE MUZ-SF25VEH MUZ-SF35VE MUZ-SF35VEH MUZ-SF42VE MUZ-SF42VEH
NOTE: Turn OFF power supply before disassembly.
OPERATING PROCEDURE PHOTOS
1. Removing the cabinet
(1) Remove the screw fixing the service panel. (2) Pull down the service panel and remove it. (3) Disconnect the power supply and indoor/outdoor con-
necting wire. (4) Remove the screws fixing the top panel. (5) Remove the top panel. (6) Remove the screws fixing the cabinet. (7) Remove the cabinet. (8) Remove the screws fixing the back panel. (9) Remove the back panel.
Photo 1
Photo 2
(1) Slide the sleeve and check if there is a locking lever or not. (2) The terminal with this connector has the
locking mechanism.
Slide the sleeve. Pull the terminal while pushing the locking lever.
Hold the sleeve, and pull out the terminal slowly.
Connector
Sleeve
Locking lever
Back panel
Service
panel
Screws of the top panel
Screws of the cabinet
Screws of the top panel
Screw of the service panel
Direction to remove
Screws of
the cabinet
Hooks
<"Terminal with locking mechanism" Detaching points>
The terminal which has the locking mechanism can be detached as shown below. There are two types (refer to (1) and (2)) of the terminal with locking mechanism. The terminal without locking mechanism can be detached by pulling it out. Check the shape of the terminal before detaching.
DISASSEMBLY INSTRUCTIONS
12
Screw of the
cabinet
Screw of the back panel
Screws of the terminal block support and the back panel
OBH629A
OPERATING PROCEDURE
PHOTOS
2. Removing the inverter assembly, inverter P.C. board
(1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the lead wire to the reactor and the following con-
nectors:
<Inverter P.C. board>
CN721 (R.V. coil) CN722 (Defrost heater) MUZ-SF25/35/42VEH CN931, CN932 (Fan motor) CN641 (Defrost thermistor and discharge temperature ther-
mistor) CN643 (Ambient temperature thermistor) CN644 (Outdoor heat exchanger temperature thermistor) CN724 (LEV)
(3) Remove the compressor connector (CN61). (4) Remove the screws fixing the heat sink support and the sep-
arator.
(5) Remove the fixing screws of the terminal block support and
the back panel. (6) Remove the inverter assembly. (7) Remove the screw of the earth wire and screw of the termi-
nal block support. (8) Remove the heat sink support from the P.C. board support. (9) Remove the screw of the inverter P.C. board and remove the
inverter P.C. board from the P.C. board support.
Photo 3
Photo 4 (Inverter assembly)
Photo 5
3. Removing R.V. coil
(1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the following connectors: <Inverter P.C. board>
CN721 (R.V. coil)
(3) Remove the R.V. coil.
4. Removing the discharge temperature thermistor, defrost thermistor, outdoor heat exchanger tempera­ture thermistor and ambient temperature thermistor
(1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the lead wire to the reactor and the following con-
nectors: <Inverter P.C. board>
CN641 (Defrost thermistor and discharge temperature ther-
mistor) CN643 (Ambient temperature thermistor) CN644 (Outdoor heat exchanger temperature thermistor)
(3) Pull out the discharge temperature thermistor from its holder. (4) Pull out the defrost thermistor from its holder. (Photo 6) (5) Pull out the outdoor heat exchanger temperature thermistor
from its holder. (Photo 6)
(6) Pull out the ambient temperature thermistor from its holder.
Discharge temperature thermistor
Screw of the R.V. coil
Screws of the heat sink support and the separator
46
Screws of the terminal block support and the back panel
Heat sink
Screw of the earth wire
Screw of the Terminal block support
Screw of the inverter P.C. board
Heat sink support
P.C. board support
Terminal block support
Note: As for MUZ-SF25VE(H), the shape of the out-
door heat exchanger is a flat type.
OBH629A
47
OPERATING PROCEDURE
PHOTOS
5. Removing outdoor fan motor
(1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the following connectors: <Inverter P.C. board>
CN931, CN932 (Fan motor) (3) Remove the propeller nut. (4) Remove the propeller. (5) Remove the screws fixing the fan motor. (6) Remove the fan motor.
Photo 6
Photo 7
Photo 8
6. Removing the compressor and 4-way valve
(1) Remove the cabinet and panels. (Refer to 1.) (2) Remove the inverter assembly. (Refer to 2.) (3) Recover gas from the refrigerant circuit.
NOTE: Recover gas from the pipes until the pressure gauge
shows 0 kg/cm2 (0 MPa).
(4) Detach the brazed part of the suction and the discharge pipe
connected with compressor. (5) Remove the nuts of compressor legs. (6) Remove the compressor. (7) Detach the brazed part of pipes connected with 4-way valve.
Defrost thermistor
Outdoor heat exchanger tempera­ture thermistor
Propeller nut
Screws of the outdoor fan motor
Propeller
Brazed parts of 4-way valve
Ambient temperature thermistor
OBH629A
48
12-2. MUZ-SF50VE MUZ-SF50VEH
NOTE: Turn OFF power supply before disassembly.
OPERATING PROCEDURE
PHOTOS
1. Removing the cabinet
(1) Remove the screws of the service panel. (2) Remove the screws of the top panel. (3) Remove the screw of the valve cover. (4) Remove the service panel. (5) Remove the top panel. (6) Remove the valve cover. (7) Disconnect the power supply and indoor/outdoor connect-
ing wire. (8) Remove the screws of the cabinet. (9) Remove the cabinet. (10)
Remove the screws of the back panel.
(11)
Remove the back panel.
Photo 1
Photo 2
Screws of the cabinet
Screws of the top panel
Screws of the top panel
Screw of the back panel
Screws of the cabinet
Screws of the cabinet
Screws of the service panel
Screw of the valve cover
Screws of the cabinet
Screws of the back panel
Screws of the cabinet
OBH629A
49
OPERATING PROCEDURE
PHOTOS
2. Removing the inverter assembly, inverter P.C. board
(1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the lead wire to the reactor and the following con-
nectors: <Inverter P.C. board> CN721 (R.V. coil)
CN722 (Defrost heater) MUZ-SF50VEH CN931, CN932 (Fan motor) CN641 (Defrost thermistor and discharge temperature ther-
mistor) CN643 (Ambient temperature thermistor) CN644 (Outdoor heat exchanger temperature thermistor) CN724 (LEV)
(3) Remove the compressor connector. (4) Remove the screws fixing the heat sink support and the sep-
arator.
(5) Remove the fixing screws of the terminal block support and
the back panel.
(6) Remove the inverter assembly. (7) Remove the screw of the earth wire, screw of the P.C. board
cover and screws of the terminal block support.
(8) Remove the heat sink support from the P.C. board support. (9) Remove the screw of the inverter P.C. board and the inverter
P.C. board from the P.C. board support.
Photo 3
Photo 4
Photo 5
3. Removing R.V. coil
(1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the following connector: <Inverter P.C. board>
CN721 (R.V. coil)
(3) Remove the R.V. coil.
Screw of the heat sink support and the separator
Brazed parts of 4-way valve
Screw of the R.V. coil
Heat sink
Screw of the inverter P.C. board
Screw of the earth wire
Screws of the terminal block support
Screw of the P.C. board cover
Screw of the terminal block support and the back panel
P.C. board support
Heat sink support
OBH629A
OPERATING PROCEDURE PHOTOS
4. Removing the discharge temperature thermistor, defrost thermistor, outdoor heat exchanger tempera­ture thermistor and ambient temperature thermistor
(1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the lead wire to the reactor and the following
connectors: <Inverter P.C. board>
CN641 (Defrost thermistor and discharge temperature ther-
mistor) CN643 (Ambient temperature thermistor) CN644 (Outdoor heat exchanger temperature thermistor)
(3) Pull out the discharge temperature thermistor from its hold-
er.
(4) Pull out the defrost thermistor from its holder. (5) Pull out the outdoor heat exchanger temperature thermistor
from its holder.
(6) Pull out the ambient temperature thermistor from its holder.
Photo 6
Photo 7
Photo 8
5. Removing outdoor fan motor
(1)
Remove the top panel, cabinet and service panel. (Refer to 1.)
(2) Disconnect the following connectors:
<Inverter P.C. board> CN931 and CN932 (Fan motor)
(3) Remove the propeller nut. (4) Remove the propeller. (5) Remove the screws fixing the fan motor. (6) Remove the fan motor.
6. Removing the compressor and 4-way valve
(1)
Remove the top panel, cabinet and service panel. (Refer to 1.) (2) Remove the back panel. (Refer to 1.) (3) Remove the inverter assembly. (Refer to 2.) (4) Recover gas from the refrigerant circuit.
NOTE: Recover gas from the pipes until the pressure gauge
shows 0 kg/cm2 (0 MPa).
(5) Detach the brazed part of the suction and the discharge
pipe connected with compressor. (6) Remove the compressor nuts. (7) Remove the compressor. (8) Detach the brazed part of 4-way valve and pipe. (Photo 5)
Screws of the outdoor fan motor
Brazed part of the
discharge pipe
Brazed part of the suction pipe
Discharge temperature thermistor
Outdoor heat exchanger tempera­ture thermistor
Ambient tem­perature thermistor
Defrost thermistor
Propeller nut
50
OBH629A
51
OBH629A
HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
© Copyright 2012 MITSUBISHI ELECTRIC CORPORATION
Distributed in Aug. 2013. No. OBH629 REVISED EDITION-A Distributed in Nov. 2012. No. OBH629 Made in Japan
New publication, effective Aug. 2013 Specifications are subject to change without notice.