Mitsubishi MUZ-HM18NA2-U1, MUZ-HM18NA-U1, MUZ-HM24NA-U1, MUZ-HM24NA2-U1 Service Manual

HFC
utilized
R410A
INDOOR UNIT
OUTDOOR UNIT
SERVICE MANUAL
Models
Revision C:
U1
• MUZ-HM09/12NA
have been added.
OBH747 REVISED EDITION-B is void.
-
, MUZ-HM09/12NA2
No. OBH747
REVISED EDITION-C
U1
-
MUZ-HM09NA
-
MUZ-HM09NA2 MUZ-HM12NA
-
MUZ-HM12NA2 MUZ-HM15NA
-
MUZ-HM15NA2
MUZ-HM24NA
U1
,
U1,U8
-
U1,U8
U1,U8
-
U1
U1
-
U8
MUZ-HM18NA MUZ-HM18NA2 MUZ-HM24NA MUZ-HM24NA2
Indoor unit service manual MSZ-HM•NA Series (OBH746)
CONTENTS
1. TECHNICAL CHANGES ··································· 3
2. PART NAMES AND FUNCTIONS ····················· 4
3. SPECIFICATION ················································ 5
4. OUTLINES AND DIMENSIONS ······················ 10
5. WIRING DIAGRAM ·········································· 12
6. REFRIGERANT SYSTEM DIAGRAM ·············15
7. DATA ································································ 19
8. ACTUA TOR CONTROL ··································· 32
9. SERVICE FUNCTIONS ··································· 33
10. TROUBLESHOOTING ····································· 34
11. DISASSEMBLY INSTRUCTIONS ···················· 59
PARTS CATALOG (OBB747)
U1
-
U1
-
U1
-
U1
-
NOTE:
RoHS compliant products have <G> mark on the spec name plate.
Use the specifi ed refrigerant only
OBH747C
Never use any refrigerant other than that specified.
Doing so may cause a burst, an explosion, or fire when the unit is being used, serviced, or disposed of. Correct refrigerant is specified in the manuals and on the spec labels provided with our products. We will not be held responsible for mechanical failure, system malfunction, unit breakdown or accidents caused by failure to follow the instructions.
Revision A:
• MUZ-HM09/12NA-U8, MUZ-HM09/12NA2-U8, MUZ-HM15/18NA-U1, MUZ-HM15/18NA2-U1 and MUZ-HM24NA2-U1 have been added.
Revision B:
• 3. SPECIFICATION has been modified.
Revision C:
• MUZ-HM09/12NA
U1
-
, MUZ-HM09/12NA2
U1
-
have been added.
2
1
OBH747C
TECHNICAL CHANGES
MUZ-HM24NA
1. New model
MUZ-HM09NA MUZ-HM09NA2 MUZ-HM12NA MUZ-HM12NA2 MUZ-HM15NA MUZ-HM15NA2 MUZ-HM18NA MUZ-HM18NA2 MUZ-HM24NA2
1. New model
MUZ-HM09NA MUZ-HM09NA2 MUZ-HM12NA MUZ-HM12NA2
1. New model
U1
-
U8
-
U8
-
U8
-
U8
-
U1
-
U1
-
U1
-
U1
-
U1
-
U1
-
U1
-
U1
-
U1
-
3
Piping
Air outlet
Drain outlet
Air inlet
(back and side)
Drain hose
2
OBH747C
PART NAMES AND FUNCTIONS
MUZ-HM09NA MUZ-HM09NA2 MUZ-HM12NA MUZ-HM12NA2 MUZ-HM15NA MUZ-HM15NA2 MUZ-HM18NA MUZ-HM18NA2
Air inlet
(back and side)
Piping
Air outlet
Drain hose
Drain outlet
MUZ-HM24NA MUZ-HM24NA2
4
3
OBH747C
SPECIFICATION
Outdoor unit model Capacity
Rated (Minimum~Maximum)
Capacity
Rated (Maximum)
Power consumption
Rated (Minimum~Maximum)
Power consumption
Rated (Maximum)
1
EER HSPF IV
[SEER]
4
Cooling 1 Heating 47 1
Heating 17 2 Cooling 1
Heating 47 1 Heating 17 2
3
Cooling 12.0 [ 18.0 ] Heating 10.0 [NA] / 8.5 [NA2]
COP Heating Power factor
Cooling (208/230) % 87/87 84/84 Heating (208/230) % 90/90 90/89
1
MUZ-HM09NA
MUZ-HM09NA2
U1
-
U1
­Btu/h 9,000 ( 3,800 ~ 10,000 ) Btu/h 10,900 ( 4,500 ~ 11,800 )
Btu/h 6,700 (7,200) W 750 (240 - 850) 750 (205 - 850)
W 900 (240 - 1,000) 900 (255 - 1,000) W 700 (780)
3.55
MUZ-HM09NA
MUZ-HM09NA2
Power supply V , phase , Hz 208/230 , 1 , 60 Max. fuse size (time delay) A 15 Min. circuit ampacity A 9 12 Fan motor F.L.A A 0.50
Model KNB073FRVMC KNB073FQDHC
Compressor
R.L.A A 6.2 6.6 L.R.A A 7.7 8.2 Refrigeration oil
oz. (L) (Model)
9.1 (0.27) (FV50S) 10.8 (0.32) (NEO22)
Refrigerant control Linear expansion valve Sound level
1
Airfl ow High - Med. - Low
Fan speed High - Med. - Low
Cooling dB(A) 46 Heating
dB(A) 50
Cooling CFM 1,063 Heating
CFM 1,282 - 1,105 1,240 - 1,105
Cooling rpm 740 Heating rpm 890 - 770 860 - 770
Defrost method Reverse cycle
W in. 31-1/2
Dimensions
D in. 11-1/4
H in. 21-5/8 Weight Ib. 73 External fi nish Munsell 3Y 7.8/1.1 Refrigerant piping Not supplied
Refrigerant pipe size (Min. wall thickness)
Connection method Between the indoor &
outdoor units Refrigerant charge (R410A)
Liquid in. 1/4 (0.0315)
Gas in. 3/8 (0.0315)
Indoor Flared
Outdoor Flared
Height difference ft. 40
Piping length ft. 65
1 lb. 12 oz.
NOTE: Test conditions are based on AHRI 210/240.
1: Rating conditions (Cooling) — Indoor: 80˚FDB, 67˚FWB, Outdoor: 95˚FDB, (75˚FWB) (Heating) — Indoor: 70˚FDB, 60˚FWB, Outdoor: 47˚FDB, 43˚FWB 2: (Heating) Indoor: 70˚FDB, 60˚FWB, Outdoor: 17˚FDB, 15˚FWB 3: Test condition (Refer to page 9.) 4: Test condition (Refer to page 9.)
U8
-
U8
-
5
Outdoor unit model
OBH747C
Capacity
Rated (Minimum~Maximum)
Capacity
Rated (Maximum)
Power consumption
Rated (Minimum~Maximum)
Power consumption
Rated (Maximum)
1
EER HSPF IV
[SEER]
4
Cooling 1 Heating 47 1
Heating 17 2 Cooling 1
Heating 47 1 Heating 17 2
3
Cooling 9.9 [ 18.0 ] Heating 10.0 [NA] / 8.5 [NA2]
COP Heating Power factor
Cooling (208/230) % 95/95 94/94 Heating (208/230) % 93/93 95/96
MUZ-HM12NA
MUZ-HM12NA2
Btu/h 12,000 ( 3,800 ~ 12,200 ) Btu/h 12,200 ( 4,500 ~ 14,500 ) 12,200 ( 5,500 ~ 14,500 )
Btu/h 7,600 (9,000) W 1,210 (240 - 1,300) 1,210 (205 - 1,300)
W 990 (240 - 1,220) 990 (340 - 1,660) W 800 (990)
1
U1
-
U1
-
MUZ-HM12NA
MUZ-HM12NA2
3.61
Power supply V , phase , Hz 208/230 , 1 , 60 Max. fuse size (time delay) A 15 Min. circuit ampacity A 9 12 Fan motor F.L.A A 0.50
Compressor
Model R.L.A A 6.2 6.6 L.R.A A 7.7 8.2 Refrigeration oil
oz. (L) (Model)
KNB073FRVMC KNB092FQAHC
9.1 (0.27) (FV50S) 10.8 (0.32) (NEO22)
Refrigerant control Linear expansion valve Sound level
1
Airfl ow High - Med. - Low
Fan speed High - Med. - Low
Cooling dB(A) 49 Heating
dB(A) 51 Cooling CFM 1,063 1,102 - 639 Heating
CFM 1,282 - 1,105 1,186 - 1,116 - 1,045 Cooling rpm 740 810 - 490 Heating rpm 890 - 770 870 - 820 - 770
Defrost method Reverse cycle
W in. 31-1/2
Dimensions
D in. 11-1/4 H in. 21-5/8
Weight Ib. 73 External fi nish Munsell 3Y 7.8/1.1 Refrigerant piping Not supplied
Refrigerant pipe size (Min. wall thickness)
Connection method Between the indoor &
outdoor units Refrigerant charge (R410A)
Liquid in. 1/4 (0.0315) Gas in. 3/8 (0.0315) Indoor Flared Outdoor Flared Height difference ft. 40 Piping length ft. 65
1 lb. 12 oz. 2 lb. 9 oz.
NOTE: Test conditions are based on AHRI 210/240.
1: Rating conditions (Cooling) — Indoor: 80˚FDB, 67˚FWB, Outdoor: 95˚FDB, (75˚FWB) (Heating) — Indoor: 70˚FDB, 60˚FWB, Outdoor: 47˚FDB, 43˚FWB 2: (Heating) Indoor: 70˚FDB, 60˚FWB, Outdoor: 17˚FDB, 15˚FWB 3: Test condition (Refer to page 9.) 4: Test condition (Refer to page 9.)
U8
-
U8
-
6
Outdoor unit model
OBH747C
Capacity
Rated (Minimum~Maximum)
Capacity
Rated (Maximum)
Power consumption
Rated (Minimum~Maximum)
Power consumption
Rated (Maximum)
1
EER HSPF IV
[SEER]
4
Cooling 1 Heating 47 1
Heating 17 2 Cooling 1
Heating 47 1 Heating 17 2
3
Cooling 12.0 [18.0] 10.5 [18.0] Heating 10.0 [NA] / 8.5 [NA2] 10.0 [NA] / 8.5 [NA2]
COP Heating Power factor
Cooling (208/230) % 98/98 98/98 Heating (208/230) % 98/98 97/97
1
MUZ-HM15NA
MUZ-HM15NA2
Btu/h 14,000 (3,100 - 16,000) 17,200 (5,800 - 18,000) Btu/h 18,000 (4,800 - 18,500) 18,000 (5,400 - 20,900)
Btu/h 11,500 (14,000) 11,500 (15,000) W 1,127 (187 - 1,957) 1,598 (308 - 2,028)
W 1,570 (190 - 1,980) 1,548 (288 - 2,208) W 1,290 (1,820) 1,258 (1,908)
3.30 3.32
MUZ-HM18NA
MUZ-HM18NA2
Power supply V , phase , Hz 208/230, 1 , 60 208/230, 1 , 60 Max. fuse size (time delay) A 15 15 Min. circuit ampacity A 10 10 Fan motor F.L.A A 0.50 0.50
Model SNB130FQBMT SNB130FQBMT
Compressor
R.L.A A 7.4 7.4 L.R.A A 9.3 9.3 Refrigeration oil
oz. (L) (Model)
11.8 (0.35) (FV50S) 11.8 (0.35) (FV50S)
Refrigerant control Linear expansion valve Sound level
1
Airfl ow High - Med. - Low
Fan speed High - Med. - Low
Cooling dB(A) 49 49 Heating
dB(A) 51 51 Cooling CFM 1,102 - 639 1,102 - 639 Heating
CFM 1,186 - 1,045 - 1,045 1,186 - 1,045 - 1,045 Cooling rpm 810 - 490 810 - 490 Heating rpm 870 - 770 - 770 870 - 770 - 770
Defrost method Reverse cycle
W in. 31-1/2 31-1/2
Dimensions
D in. 11-1/4 11-1/4 H in. 21-5/8 21-5/8
Weight Ib. 81 81 External fi nish Munsell 3Y 7.8/1.1 Refrigerant piping Not supplied
Refrigerant pipe size (Min. wall thickness)
Connection method Between the indoor &
outdoor units
Liquid in. 1/4 (0.0315) 1/4 (0.0315) Gas in. 1/2 (0.0315) 1/2 (0.0315) Indoor Flared Flared Outdoor Flared Flared Height difference ft. 40 40 Piping length ft. 65 65
Refrigerant charge (R410A) 2 lb. 9 oz. 2 lb. 10 oz.
NOTE: Test conditions are based on AHRI 210/240.
1: Rating conditions (Cooling) — Indoor: 80˚FDB, 67˚FWB, Outdoor: 95˚FDB, (75˚FWB) (Heating) — Indoor: 70˚FDB, 60˚FWB, Outdoor: 47˚FDB, 43˚FWB 2: (Heating) Indoor: 70˚FDB, 60˚FWB, Outdoor: 17˚FDB, 15˚FWB 3: Test condition (Refer to page 9.) 4: Test condition (Refer to page 9.)
7
Outdoor unit model
OBH747C
Capacity
Rated (Minimum~Maximum)
Capacity
Rated (Maximum)
Power consumption
Rated (Minimum~Maximum)
Power consumption
Rated (Maximum)
Cooling 1 Btu/h 22,500 (5,800 ~ 22,500) Heating 47
1 Btu/h 26,000 (5,400 ~ 26,000) Heating 17 2 Btu/h 18,500 (18,500) Cooling 1 W 2,575 (275 ~ 2,575)
Heating 47
1 W 2,445 (265 ~ 2,445) Heating 17 2 W 2,245 (2,245)
MUZ-HM24NA
MUZ-HM24NA2
EER 1 [SEER] 3 Cooling 8.6 [18.0] HSPF IV COP Heating
Power factor
4 Heating 9.5 [NA] / 8.5 [NA2]
1 3.05 Cooling (208/230) % 99/99 Heating (208/230) % 99/99
Power supply V , phase , Hz 208/230, 1 , 60 Max. fuse size (time delay) A 15 Min. circuit ampacity A 14 Fan motor F.L.A 0.93
Model SNB130FQBMT
Compressor
Refrigeration oil
R.L.A 10 L.R.A 12.5 oz. (L) (Model)
11.8 (0.35) (FV50S)
Refrigerant control Linear expansion valve Sound level
1
Airfl ow High - Med. - Low
Fan speed High - Med. - Low
Cooling dB(A) 54 Heating dB(A) 55 COOL CFM 1,742 - 922 HEAT CFM 1,691 - 1,691 - 1,372 Cooling rpm 840 - 450 Heating rpm 810 - 810 - 650
Defrost method Reverse cycle
W in. 33-1/16
Dimensions
D in. 13 H in. 34-5/8
Weight Ib. 121 External fi nish Munsell 3Y 7.8/1.1 Refrigerant piping Not supplied Refrigerant pipe size
(Min. wall thickness) Connection method Between the indoor &
outdoor units
Liquid in. 3/8 (0.0315) Gas in. 5/8 (0.0315) Indoor Flared Outdoor Flared Height difference ft. 50 Piping length ft. 100
Refrigerant charge (R410A) 3 lb. 9 oz.
NOTE: Test conditions are based on AHRI 210/240.
1: Rating conditions (Cooling) — Indoor: 80˚FDB, 67˚FWB, Outdoor: 95˚FDB, (75˚FWB) (Heating) — Indoor: 70˚FDB, 60˚FWB, Outdoor: 47˚FDB, 43˚FWB
2: (Heating) Indoor: 70˚FDB, 60˚FWB, Outdoor: 17˚FDB, 15˚FWB
8
Test condition
OBH747C
3, 4
Mode Test
ARI
"A-2" Cooling Steady State at rated compressor Speed
"B-2" Cooling Steady State at rated compressor Speed
SEER
(Cooling)
HSPF
(Heating)
5
: At Intermediate compressor Speed
"B-1" Cooling Steady State at minimum compressor Speed
"F-1" Cooling Steady State at minimum compressor Speed
"E-V" Cooling Steady State at Intermediate compressor Speed
"H1-2" Heating Steady State at rated compressor Speed
"H3-2" Heating at rated compressor Speed
"H0-1" Heating Steady State at minimum compressor Speed
"H1-1" Heating Steady State at minimum compressor Speed
"H2-V" Heating at Intermediate compressor Speed
5
5
= ("Rated compressor speed" - "minimum compressor speed") / 3 + "minimum compressor speed".
Indoor air condition (°F) Outdoor air condition (°F)
Dry bulb Wet bulb Dry bulb Wet bulb
80 67 95 (75)
80 67 82 (65)
80 67 82 (65)
80 67 67 (53.5)
80 67 87 (69)
70 60 47 43
70 60 17 15
70 60 62 56.5
70 60 47 43
70 60 35 33
OPERATING RANGE
(1) POWER SUPPLY
Outdoor unit
(2) OPERATION
Mode Condition
Standard temperature 80 67 95
Cooling
Heating
Maximum temperature 90 73 115 — Minimum temperature 67 57 14 — Maximum humidity 78 % — Standard temperature 70 60 47 43 Maximum temperature 80 67 75 65 Minimum temperature 70 60 -4 (NA), 5(NA2) -5 (NA), 4 (NA2)
Rated voltage Guaranteed voltage (V)
208/230 V
1 phase
60 Hz
Min. 187
DB WB DB WB
208 230 Max. 253
Intake air temperature (°F)
Indoor Outdoor
9
4
OBH747C
OUTLINES AND DIMENSIONS
MUZ-HM09NA MUZ-HM09NA2 MUZ-HM12NA MUZ-HM12NA2 MUZ-HM15NA MUZ-HM15NA2 MUZ-HM18NA MUZ-HM18NA2
REQUIRED SPACE
*1
4 in. (100 mm) or more when
front and sides of the unit are clear
4 in. (100 mm)
or more
8 in. (200 mm)
or more *2
*2
When any 2 sides of left, right
and rear of the unit are clear
holes
Liquid refrigerant pipe joint Refrigerant pipe (flared)
Gas refrigerant pipe joint Refrigerant pipe (flared)
Ø 1/2 (HM15/18)
clear *1
4 in. (100 mm)
14 in. (350 mm)
or more
Ø 1/4
Ø 3/8 (HM09/12)
Unit: inch
or more
10
MUZ-HM24NA MUZ-HM24NA2
OBH747C
Unit: inch
REQUIRED SPACE
Air in
13
34-5/8
2
17-25/32
6-7/8
16-7/16
Air in
4-5/16
Air out
19-11/16
33-1/16
*1 20 in. (500 mm) or more when front and sides of the unit are clear
Drain hole
1-9/16
1-5/8
14-3/16
2-holes 13/32 13/16
3-3/16
4 in. (100 mm)
or more
Clear *1
20 in. (500 mm)
or more *2
*2 When any 2 sides of left, right and rear of the unit are clear
Service panel
Liquid refrigerant pipe joint Refrigerant pipe (flared)
35
44
4 in. (100 mm)
or more
14 in. (350 mm)
or more
Ø 3/8
6-1/2
3-29/32
7-11/16
Gas refrigerant pipe joint Refrigerant pipe (flared)
Ø 5/8
11
5
OBH747C
WIRING DIAGRAM
MUZ-HM09NA
U1
-
MUZ-HM09NA2
U1
-
MUZ-HM12NA
U1
-
MUZ-HM12NA2
U1
-
MUZ-HM09NA
U8
-
MUZ-HM09NA2
U8
-
MUZ-HM12NA
U8
-
MUZ-HM12NA2
U8
-
12
MUZ-HM15NA
OBH747C
U1
-
MUZ-HM15NA2
U1
-
MUZ-HM18NA
U1
-
MUZ-HM18NA2
U1
-
13
MUZ-HM24NA
OBH747C
U1
-
MUZ-HM24NA2
U1
-
14
6
OBH747C
REFRIGERANT SYSTEM DIAGRAM
MUZ-HM09NA
Refrigerant pipe ø3/8 (ø9.52) (with heat insulator)
Flared connection
Flared connection
Refrigerant pipe ø1/4 (ø6.35) (with heat insulator)
U1
-
MUZ-HM09NA2
Stop valve (with service port)
Stop valve (with strainer)
U1
-
MUZ-HM12NA
4-way valve
Muffler
Discharge temperature thermistor RT62
Service port
Capillary tube
O.D. 0.118 × I.D. 0.055 × 10-1/4 (ø3.0 × ø1.4
×
260)
LEV
-
Muffler
Service port
Compressor
Defrost thermistor RT61
U1
MUZ-HM12NA2
Outdoor heat exchanger temperature
Outdoor heat exchanger
Refrigerant flow in cooling Refrigerant flow in heating
thermistor RT68
Ambient temperature thermistor RT65
Strainer #100
R.V. coil heating ON cooling OFF
U1
-
Unit: Inch (mm)
MUZ-HM09NA
Refrigerant pipe ø3/8 (ø9.52) (with heat insulator)
Flared connection
Flared connection
Refrigerant pipe ø1/4 (ø6.35) (with heat insulator)
U8
-
MUZ-HM09NA2
Stop valve (with service port)
Stop valve (with strainer)
U8
-
4-way valve
Muffler
Discharge temperature thermistor RT62
Service port
Capillary tube
O.D. 0.118 × I.D. 0.079 × 9-7/16 (ø3.0 × ø2.0
×
240)
LEV
Muffler
Service port
Compressor
Defrost thermistor RT61
Outdoor heat exchanger temperature
Outdoor heat exchanger
Refrigerant flow in cooling Refrigerant flow in heating
thermistor RT68
Ambient temperature thermistor RT65
Strainer #100
R.V. coil heating ON cooling OFF
15
Outdoor heat exchanger
Flared connection
Defrost thermistor RT61
Discharge temperature thermistor RT62
Flared connection
Stop valve (with strainer)
Refrigerant flow in cooling
Compressor
4-way valve
Refrigerant flow in heating
Refrigerant pipe ø1/4 (ø6.35) (with heat insulator)
R.V. coil heating ON cooling OFF
Strainer #100
LEV
Ambient temperature thermistor RT65
Muffler
Capillary tube O.D. 0.157 × I.D. 0.094 × 9-7/16 (
ø4.0 × ø2.4 × 240
)
Outdoor heat exchanger temperature thermistor RT68
Capillary tube
O.D. 0.118 × I.D. 0.079 × 8-9/32 (ø3.0 × ø2.0 × 210)
Service port
Service port
Refrigerant pipe ø1/2 (ø12.7) (with heat insulator)
Stop valve (with service port)
Muffler
MUZ-HM12NA
OBH747C
U8
-
MUZ-HM12NA2
U8
-
Unit: Inch (mm)
Refrigerant pipe ø3/8 (ø9.52) (with heat insulator)
Stop valve (with service port)
Flared connection
Flared connection
Stop valve (with strainer)
Refrigerant pipe ø1/4 (ø6.35) (with heat insulator)
4-way valve
Muffler
Discharge temperature thermistor RT62
Service port
Capillary tube
O.D. 0.118 × I.D. 0.079 × 9-7/16
×
(ø3.0 × ø2.0
240)
Muffler
Service port
Compressor
Defrost thermistor RT61
Capillary tube
O.D. 0.118 × I.D. 0.071 × 23-5/8
3.0
× ø
1.8
LEV
Outdoor heat exchanger
×
600
)
(×2)
Strainer #100
R.V. coil heating ON cooling OFF
Refrigerant flow in cooling Refrigerant flow in heating
Outdoor heat exchanger temperature thermistor RT68
Ambient temperature thermistor RT65
MUZ-HM15NA MUZ-HM15NA2 MUZ-HM18NA MUZ-HM18NA2
16
MUZ-HM24NA MUZ-HM24NA2
OBH747C
Unit: Inch (mm)
Refrigerant pipe (with heat insulator)
Flared connection
Flared connection
Refrigerant pipe (with heat insulator)
ø5/8 (ø
ø3/8 (ø
15.88)
Stop valve (with service port)
Strainer
#100
Stop valve
9.52)
4-way valve
Service port
Muffler
Discharge temperature thermistor RT62
Compressor
Capillary tube
O.D. 0.118× I.D. 0.079× 7-7/8
(ø3.0×ø2.0×200(×4))
Capillary tube
O.D. 0.157× I.D. 0.094× 3-15/16
4.0×ø
2.4×100)
Muffler with #100 mesh strainer
Service port
LEV
Capillary tube
Strainer
O.D. 0.157× I.D. 0.094×7-7/8
4.0×ø
2.4×200)
#100
Outdoor
Defrost thermistor RT61
Refrigerant flow in cooling Refrigerant flow in heating
heat exchanger
Outdoor heat exchanger temperature thermistor RT68
R.V. coil heating ON cooling OFF
17
MAX. REFRIGERANT PIPING LENGTH and MAX. HEIGHT DIFFERENCE
OBH747C
Refrigerant piping: ft. Piping size O.D: in.
Model
MUZ-HM09NA MUZ-HM09NA2 MUZ-HM12NA MUZ-HM12NA2
MUZ-HM15NA MUZ-HM15NA2 MUZ-HM18NA MUZ-HM18NA2
MUZ-HM24NA MUZ-HM24NA2
Max. Length
A
Max. Height difference
B
Gas Liquid
3/8
65 40
1/2
100 50 5/8 3/8
Indoor unit
Max. Height
difference
B
Max. Length A
Outdoor unit
1/4
ADDITIONAL REFRIGERANT CHARGE (R410A: oz.)
NOTE: Refrigerant piping exceeding 25 ft. requires additional refrigerant charge according to the calculation.
Model
MUZ-HM09NA MUZ-HM09NA2
MUZ-HM12NA MUZ-HM12NA2
MUZ-HM12NA MUZ-HM12NA2
MUZ-HM15NA MUZ-HM15NA2
MUZ-HM18NA MUZ-HM18NA2
Model
MUZ-HM24NA MUZ-HM24NA2
U1
-
U1
-
U8
-
U8
-
Outdoor unit
precharged
25 30 40 50 60 65
1 lb. 12 oz.
0 1.08 3.24 5.40 7.56 8.64
2 lb. 9 oz.
2 lb. 10 oz.
Outdoor unit
precharged
25 30 40 50 60 70 80 90 100
3 lb. 9 oz. 0 1.08 3.24 5.40 7.56 9.72 11.88 14.04 16.20
Refrigerant piping length (one way): ft.
Calculation: X oz. = 1.08/5 oz./ft. × (Refrigerant piping length (ft.) - 25)
Refrigerant piping length (one way): ft.
Calculation: X oz. = 1.08/5 oz./ft. × (Refrigerant piping length (ft.) - 25)
18
DATA7
OBH747C
MUZ-HM09NA MUZ-HM09NA2 MUZ-HM12NA MUZ-HM12NA2 MUZ-HM15NA MUZ-HM15NA2 MUZ-HM18NA MUZ-HM18NA2 MUZ-HM24NA MUZ-HM24NA2
7-1. PERFORMANCE DATA
1) COOLING CAPACITY
Indoor air Outdoor intake air DB temperature (˚F)
Model
MUZ-HM09NA MUZ-HM09NA2
MUZ-HM12NA MUZ-HM12NA2
MUZ-HM15NA MUZ-HM15NA2
MUZ-HM18NA MUZ-HM18NA2
MUZ-HM24NA MUZ-HM24NA2
NOTE: 1. IWB : Intake air wet-bulb temperature TC : Total Capacity (x10
2. SHC is based on 80˚F of indoor Intake air DB temperature.
IWB (˚F)
71 11.0 7.6 0.67 10.3 7.1 0.73 9.7 6.6 0.79 9.0 6.2 0.83 8.3 5.7 0.86 67 10.4 8.6 0.63 9.7 8.0 0.69 9.0 7.4 0.75 8.4 6.9 0.80 7.7 6.3 0.83 63 9.8 9.4 0.60 9.1 8.7 0.66 8.5 8.1 0.72 7.7 7.3 0.77 7.0 6.7 0.80 71 14.7 9.4 1.08 13.7 8.7 1.18 12.9 8.2 1.27 12.0 7.6 1.34 11.0 7.0 1.39 67 13.9 10.7 1.02 13.0 10.0 1.12 12.0 9.2 1.21 11.2 8.6 1.28 10.3 7.9 1.34 63 13.1 11.8 0.97 12.1 10.9 1.07 11.3 10.2 1.16 10.3 9.3 1.23 9.4 8.5 1.28 71 17.2 11.1 1.04 16.0 10.4 1.14 15.1 9.7 1.23 14.0 9.1 1.29 12.9 8.3 1.35 67 16.2 12.7 0.98 15.1 11.8 1.08 14.0 10.9 1.17 13.0 10.2 1.24 12.0 9.3 1.30 63 15.3 13.9 0.94 14.1 12.9 1.04 13.2 12.0 1.12 12.0 10.9 1.19 10.9 10.0 1.24 71 21.1 15.3 1.46 19.7 14.3 1.60 18.5 13.4 1.72 17.2 12.5 1.81 15.8 11.5 1.89 67 20.0 17.2 1.38 18.6 16.0 1.52 17.2 14.8 1.64 16.0 13.8 1.74 14.7 12.6 1.82 63 18.7 18.6 1.31 17.4 17.3 1.45 16.2 16.1 1.57 14.7 14.6 1.67 13.4 13.3 1.74 71 27.6 20.9 2.34 25.8 19.5 2.56 24.2 18.3 2.76 22.5 17.0 2.91 20.7 15.7 3.02 67 26.1 23.2 2.21 24.3 21.6 2.43 22.5 20.0 2.63 20.9 18.6 2.79 19.2 17.1 2.92
63 24.5 25.1 2.10 22.7 23.3 2.33 21.2 21.6 2.51 19.2 19.7 2.68 17.6 18.0 2.79
SHC : Sensible Heat Capacity (x10
75 85 95 105 115
TC SHC TPC TC SHC TPC TC SHC TPC TC SHC TPC TC SHC TPC
3
3
Btu/h) TPC : Total Power Consumption (kW)
Btu/h)
2) COOLING CAPACITY CORRECTIONS
Refrigerant piping length (one way: ft.)
Model 25 (std.) 40 65 100
MUZ-HM09NA MUZ-HM09NA2 MUZ-HM12NA MUZ-HM12NA2 MUZ-HM15NA MUZ-HM15NA2
MUZ-HM18NA MUZ-HM18NA2 MUZ-HM24NA MUZ-HM24NA2
1.0 0.954 0.878
1.0 0.954 0.878 0.771
19
3) HEATING CAPACITY
OBH747C
Indoor air Outdoor intake air WB temperature (˚F)
Model
MUZ-HM09NA MUZ-HM09NA2
MUZ-HM12NA MUZ-HM12NA2
MUZ-HM15NA MUZ-HM15NA2
MUZ-HM18NA MUZ-HM18NA2
MUZ-HM24NA MUZ-HM24NA2
NOTE: 1. IDB : Intake air dry-bulb temperature
2. Above data is for heating operation without any frost.
How to operate with fixed operational frequency of the compressor.
1. Press the EMERGENCY OPERATION switch on the front of the indoor unit, and select either EMERGENCY COOL mode or EMERGENCY HEAT mode before starting to operate the air conditioner.
2. The compressor starts with operational frequency.
3. The fan speed of the indoor unit is High.
4. This operation continues for 30 minutes.
5. In order to release this operation, press the EMERGENCY OPERATION switch or press any button on the remote con­troller.
IDB (˚F)
75 4.8 0.53 6.3 0.67 7.9 0.79 9.4 0.88 10.6 0.92 11.0 0.94 12.4 0.97 70 5.2 0.51 6.7 0.65 8.2 0.77 9.6 0.86 10.9 0.90 11.2 0.92 12.7 0.95 65 5.5 0.49 6.9 0.62 8.6 0.74 10.0 0.83 11.2 0.88 11.6 0.89 13.0 0.94 75 5.4 0.58 7.1 0.74 8.8 0.87 10.6 0.97 11.9 1.01 12.3 1.03 13.9 1.07 70 5.8 0.56 7.5 0.71 9.2 0.85 10.8 0.94 12.2 0.99 12.6 1.01 14.2 1.05 65 6.1 0.53 7.7 0.68 9.6 0.82 11.2 0.92 12.6 0.97 12.9 0.98 14.5 1.03 75 7.9 0.94 10.4 1.19 13.1 1.40 15.6 1.56 17.6 1.64 18.1 1.66 20.5 1.73 70 8.6 0.90 11.1 1.15 13.5 1.37 15.9 1.52 18.0 1.60 18.5 1.63 21.0 1.70 65 9.0 0.86 11.3 1.10 14.1 1.32 16.5 1.48 18.5 1.56 19.1 1.58 21.4 1.66 75 7.9 0.94 10.4 1.18 13.1 1.39 15.6 1.55 17.6 1.63 18.1 1.65 20.5 1.72 70 8.6 0.90 11.1 1.14 13.5 1.36 15.9 1.51 18.0 1.59 18.5 1.62 21.0 1.69 65 9.0 0.86 11.3 1.10 14.1 1.31 16.5 1.47 18.5 1.55 19.1 1.57 21.4 1.65 75 11.4 1.48 15.1 1.86 18.9 2.19 22.5 2.44 25.4 2.56 26.1 2.60 29.6 2.70 70 12.4 1.41 16.0 1.80 19.5 2.14 23.0 2.38 26.0 2.50 26.8 2.55 30.3 2.65 65 13.0 1.35 16.4 1.73 20.4 2.06 23.8 2.31 26.8 2.44 27.6 2.48 30.9 2.60
TC : Total Capacity (x10
5 152535434555
TC TPC TC TPC TC TPC TC TPC TC TPC TC TPC TC TPC
3
Btu/h) TPC : Total Power Consumption (kW)
20
7-2. PERFORMANCE CURVE
Cooling capacity (
at Rated frequency)
0.9
1.0
1.1
1.2
1.3
1.4
1.5
14 23 32 41 50 59 68 77 86 95 104 113
Outdoor intake air DB temperature(°F)
Capacity correction factors
79
75
68 64
72
Indoor intake air Wet-bulb temperature( F)
Indoor air Wet-bulb temperature
difference (°F)
71 67 63
65 75 85 95 105 115
0.4
0.5
0.6
0.7
0.8
0.9
1.0
Indoor intake air WB temperature (°F)
SHF at rating condition = 0.82
= 399 CFM
Airflow
Outdoor intake air DB temperature (°F)
Total power consumption
(kW)
71 67 63
65 75 85 95 105 115
0.9
1.0
1.1
1.2
1.3
1.4
1.5
Indoor intake air WB temperature (°F)
SHF at rating condition = 0.77
= 399 CFM
Airflow
Outdoor intake air DB temperature (°F)
Total power consumption
(kW)
OBH747C
Cooling
MUZ-HM09NA MUZ-HM09NA2 MUZ-HM12NA MUZ-HM12NA2
MUZ-HM15NA MUZ-HM15NA2
SHF at rating condition = 0.78
1.5
1.4
1.3
1.2
1.1
(kW)
1.0
0.9
0.8
0.7 65 75 85 95 105 115
Total power consumption
Indoor intake air WB temperature (°F)
Outdoor intake air DB temperature (°F)
Airflow
MUZ-HM24NA MUZ-HM24NA2
SHF at rating condition = 0.89
3.2
3.0
2.8
2.6
2.4
(kW)
2.2
2.0
1.8 65 75 85 95 105 115
Total power consumption
This value of frequency is not the same as the actual frequency in operating. Refer to 7-5 and 7-6 for the relationships between frequency and capacity.
Indoor intake air WB temperature (°F)
Outdoor intake air DB temperature (°F)
Airflow
= 533 CFM
= 702 CFM
MUZ-HM18NA MUZ-HM18NA2
SHF at rating condition = 0.86
71 67 63
2.0
1.8
1.6
(kW)
1.4
1.2
Total power consumption
65 75 85 95 105 115
Indoor intake air WB temperature (°F)
Outdoor intake air DB temperature (°F)
71 67 63
21
Airflow
= 625 CFM
71 67 63
Heating
p
)
OBH747C
Heating capacity (
1.3
1.2
1.1
1.0
0.9
0.8
0.7
difference (°F)
0.6
0.5
Capacity correction factor
Indoor air Dry-bulb temperature
0.4
-4 5 142332415059 Outdoor intake air WB temperature (°F)
Indoor intake air Dry-bulb temperature ( F)
at Rated frequency)
59 68 79
MUZ-HM09NA MUZ-HM09NA2 MUZ-HM12NA MUZ-HM12NA2
= 406 CFM
1.1
0.9
0.7
(kW)
0.5
Total power consumption
0.3 0 10203040506070
Indoor intake air DB temperature (°F)
Outdoor intake air WB temperature (°F)
Airflow
75 70 65
1.2
1.1
1.0
0.9
0.8
(kW)
0.7
0.6
0.5
Total power consumption
0.4 0 10203040506070
Indoor intake air DB temperature (°F)
Outdoor intake air WB temperature (°F)
Airflow
= 406 CFM
MUZ-HM15NA MUZ-HM15NA2 MUZ-HM18NA MUZ-HM18NA2
2.0
1.7
1.4
(kW)
1.1
0.8
Total power consumption
0.5
-5 5 1525354555
Indoor intake air DB temperature (°F)
Outdoor intake air WB temperature (°F)
Airflow
= 463 CFM
75 70 65
65
2.0
1.7
1.4
(kW)
1.1
0.8
Total power consumption
0.5
-5 5 1525354555
Indoor intake air DB temperature (°F)
Outdoor intake air WB temperature (°F)
Airflow
= 625 CFM
MUZ-HM24NA MUZ-HM24NA2
= 702 CFM
3.2
2.9
2.6
2.3
2.0
(kW)
1.7
1.4
1.1
Total power consumption
0.8
-5 5 1525354555
Indoor intake air DB temperature (°F)
Outdoor intake air WB tem
This value of frequency is not the same as the actual frequency in operating. Refer to 7-5 and 7-6 for the relationships between frequency and capacity.
Airflow
erature (°F
75 70 65
65
75 70 65
75 70 65
65
22
7-3. CONDENSING PRESSURE
(PSIG)
6870 75 80 85 90
95
100 105
(°F)
260
300
340
380
420
(PSIG)
6870 75 80 85 90
95
100 105
(°F)
110
130
150
170
190
Condensing pressure
86 80 75 70
Suction pressure
Indoor DB temperature (°F)
Outdoor ambient temperature
86
80 75
70
Indoor DB temperature (°F)
Outdoor ambient temperature
4
86
807570
Indoor DB temperature (°F)
e
OBH747C
Cooling
Data are based on the condition of indoor humidity 50 %. Air flow should be set to High speed.
MUZ-HM09NA MUZ-HM09NA2
440
400
360
86 80 75 70
(PSIG)(PSIG)
200
180
160
Indoor DB temperature (°F)
86
80 75
70
Condensing pressure
320
280
6870 75 80 85 90
MUZ-HM12NA
500
445
390
335
280
70 75 80 85 90 95 100 105
MUZ-HM12NA
Indoor DB temperature (°F)
Outdoor ambient temperature
U1
-
MUZ-HM12NA2
Outdoor ambient temperature
U8
-
MUZ-HM12NA2
95
100 105
U1
-
U8
-
(°F)
Suction pressure
140
120
6870 75 80 85 90 95 100 105
(PSIG)(PSIG)
180
160
140
Suction pressure
120
100
Outdoor ambient temperature
Indoor DB temperature (°F)
70 75 80 85 90 95 100 105
Outdoor ambient temperature
(°F)
86 80
75 70
23
70 75 80 85 90 95 100 105
270
310
350
390
430
470
510
(°F) (°F)
70 75 80 85 90 95 100 105
90
105
120
135
150
165
180
(PSIG)
Condensing pressure
Suction pressure
Outdoor ambient temperature
Indoor DB temperature (°F)
(PSIG)
Indoor DB temperature (°F)
Outdoor ambient temperature
86 80 75 70
86 80
75 70
65 70 75 80 85 90 95 100 105
250
300
350
400
450
500
550
(°F) (°F)
65 70 75 80 85 90 95 100 105
80
100
120
140
160
180
200
(PSIG)
Condensing pressure
Suction pressure
Outdoor ambient temperature
Indoor DB temperature (°F)
(PSIG)
Indoor DB temperature (°F)
Outdoor ambient temperature
86 80 75 70
86 80 75 70
65 70 75 80 85 90 95 100 105
200
250
300
350
400
450
500
(°F) (°F)
65 70 75 80 85 90 95 100 105
60
80
100
120
140
160
180
(PSIG)
Condensing pressure
Suction pressure
Outdoor ambient temperature
Indoor DB temperature (°F)
(PSIG)
Indoor DB temperature (°F)
Outdoor ambient temperature
86 80 75 70
86 80 75 70
MUZ-HM15NA MUZ-HM15NA2
OBH747C
MUZ-HM18NA MUZ-HM18NA2
MUZ-HM24NA MUZ-HM24NA2
Heating
Data are based on the condition of outdoor humidity 75%. Air flow should be set to High speed. Data are for heating operation without any frost.
24
MUZ-HM09NA MUZ-HM09NA2 MUZ-HM12NA
75 70
65
75 70 65
(PSIG)
Condensing pressure
Outdoor ambient temperature
(°F) (°F)
(PSIG)
Suction pressure
Outdoor ambient temperature
5 15253545556575
250
300
350
400
450
500
58Hz
Indoor DB temperature (°F)
5 15253545556575
40
65
90
115
140
165
190
Indoor DB temperature (°F)
58Hz
OBH747C
(PSIG) (PSIG)
370
345
75 70 65
U1
-
MUZ-HM12NA2
210
185
U1
-
75 70 65
320
295
270
Condensing pressure
245
220
MUZ-HM12NA
(PSIG) (PSIG)
460
420
380
340
Condensing pressure
300
Indoor DB temperature (°F)
58Hz
5 15253545556575(°F) 5 15253545556575(°F)
Outdoor ambient temperature
U8
-
MUZ-HM12NA2
Indoor DB temperature (°F)
58Hz
U8
-
75 70 65
160
135
110
Suction pressure
85
60
210
185
160
135
110
Suction pressure
85
Indoor DB temperature (°F)
Outdoor ambient temperature
Indoor DB temperature (°F)
58Hz
58Hz
75 70
65
260
5 15253545556575(°F) 5 15253545556575(°F)
Outdoor ambient temperature
MUZ-HM15NA MUZ-HM15NA2
60
Outdoor ambient temperature
25
75 70 65
75 70 65
(PSIG)
Condensing pressure
Outdoor ambient temperature
(°F) (°F)
(PSIG)
Suction pressure
Outdoor ambient temperature
5 15253545556575
250
300
350
400
450
500
550
81Hz
Indoor DB temperature (°F)
5 15253545556575
50
75
100
125
150
175
200
Indoor DB temperature (°F)
81Hz
75 70
65
75 70 65
(PSIG)
Condensing pressure
Outdoor ambient temperature
(°F) (°F)
(PSIG)
Suction pressure
Outdoor ambient temperature
5 15253545556575
250
300
350
400
450
500
58Hz
Indoor DB temperature (°F)
5 15253545556575
50
75
100
125
150
175
200
Indoor DB temperature (°F)
58Hz
MUZ-HM18NA MUZ-HM18NA2
OBH747C
MUZ-HM24NA MUZ-HM24NA2
26
7-4. STANDARD OPERATION DATA
OBH747C
Model MSZ-HM09NA
U1
-
MSZ-HM09NA
U8
-
Item Unit Cooling Heating Cooling Heating Capacity Btu/h 9,000 10,900 9,000 10,900 SHF 0.82 0.82
Total
Input kW 0.750 0.900 0.750 0.900 Rated frequency Hz 59.5 79.0 59.5 77.5 Indoor unit MSZ-HM09NA MSZ-HM09NA
V,
Power supply
phase,
208/230, 1, 60
Hz Input kW 0.022 0.023 0.022 0.023 Fan motor current A 0.24/0.22 0.25/0.23 0.24/0.22 0.25/0.23
Outdoor unit
Electrical circuit
Power supply
V,
phase,
MUZ-HM09NA
MUZ-HM09NA2
U1
-
U1
-
208/230, 1, 60
MUZ-HM09NA
MUZ-HM09NA2
U8
-
U8
-
Hz Input kW 0.728 0.877 0.728 0.877 Comp. current A 3.64/3.29 4.25/3.85 3.32/3.00 3.66/3.31 Fan motor current A 0.27/0.24 0.30/0.27 0.27/0.24 0.30/0.27 Condensing pressure PSIG 384 331 389 331 Suction pressure PSIG 152 102 151 103 Discharge temperature ˚F 151 155 154 152 Condensing temperature ˚F 113 101 115 103 Suction temperature ˚F58415939 Comp. shell bottom temperature ˚F 146 149 151 149
Refrigerant circuit
Ref. pipe length ft. 25 Refrigerant charge (R410A) 1 lb. 12 oz.
Intake air temperature
Discharge air temperature
Indoor unit
Fan speed (High) rpm 1,020 1,040 1,020 1,040
DB ˚F80708070
WB ˚F67606760
DB ˚F60976097
WB ˚F58—58—
Airfl ow (High) CFM 367 (Wet) 413 367 (Wet) 413 Intake air temperature
DB ˚F95479547
WB ˚F—43—43 Fan speed rpm 800 850 800 850 Airfl ow CFM 1 151 1225 1151 1225
Outdoor unit
27
7-4. STANDARD OPERATION DATA
OBH747C
Model MSZ-HM12NA
U1
-
MSZ-HM12NA
U8
-
Item Unit Cooling Heating Cooling Heating Capacity Btu/h 12,000 12,200 12,000 14,400 SHF 0.77 0.77
Total
Input kW 1.210 0.990 1.210 0.990 Rated frequency Hz 89.0 90.0 69.0 77.0 Indoor unit MSZ-HM12NA MSZ-HM12NA
V,
Power supply
phase,
208/230, 1, 60
Hz Input kW 0.022 0.023 0.022 0.023 Fan motor current A 0.24/0.22 0.25/0.23 0.24/0.22 0.25/0.23
Outdoor unit
Electrical circuit
Power supply
V,
phase,
MUZ-HM12NA
MUZ-HM12NA2
U1
-
U1
-
208/230, 1, 60
MUZ-HM12NA
MUZ-HM12NA2
U8
-
U8
-
Hz Input kW 1.188 0.967 1.188 0.967 Comp. current A 5.61/5.08 4.56/4.13 4.39/3.97 5.41/4.89 Fan motor current A 0.27/0.24 0.30/0.27 0.34/0.31 0.31/0.28 Condensing pressure PSIG 429 347 389 397 Suction pressure PSIG 135 99 133 104 Discharge temperature ˚F 180 165 163 162 Condensing temperature ˚F 120 104 115 116 Suction temperature ˚F60415635 Comp. shell bottom temperature ˚F 174 157 158 158
Refrigerant circuit
Ref. pipe length ft. 25 Refrigerant charge (R410A) 1 lb. 12 oz. 2 lb. 9 oz.
Intake air temperature
Discharge air temperature
Indoor unit
Fan speed (High) rpm 1,020 1,040 1,020 1,040
DB ˚F80708070
WB ˚F67606760
DB ˚F 56 108 56 108
WB ˚F 55 55
Airfl ow (High) CFM 367 (Wet) 413 367 (Wet) 413 Intake air temperature
DB ˚F95479547
WB ˚F—43—43 Fan speed rpm 800 850 900 860 Airfl ow CFM 1 151 1225 1229 1172
Outdoor unit
28
7-4. STANDARD OPERATION DATA
OBH747C
Model MSZ-HM15NA MSZ-HM18NA MSZ-HM24NA
Item Unit Cooling Heating Cooling Heating Cooling Heating Capacity Btu/h 14,000 18,000 17,200 18,000 22,500 26,000 SHF 0.78 0.86 0.89
Total
Input kW 1.17 1.60 1.64 1.59 2.63 2.5 Rated frequency Hz 56.5 74 68 74 98 108 Indoor unit MSZ-HM15NA MSZ-HM18NA MSZ-HM24NA
Power supply
Input kW 0.043 0.030 0.042 0.042 0.055 Fan motor current A 0.43/0.39 0.34/0.31 0.44/0.40 0.44/0.40 0.55/0.50
Outdoor unit
Electrical circuit
Power supply
Input kW 1.127 1.570 1.598 1.548 2.575 2.445 Comp. current A 4.91/4.44 7.11/6.43 7.22/6.53 7.11/6.43 11.11/10.05 10.56/9.55 Fan motor current A 0.41/0.37 0.40/0.36 0.41/0.37 0.40/0.36 1.05/0.95 1.05/0.95 Condensing pressure PSIG 396 427 423 361 404 403 Suction pressure PSIG 138 98 144 99 127 94 Discharge temperature ˚F 168 178 165 161 174 194 Condensing temperature ˚F 115 120 120 108 116 116 Suction temperature ˚F613154355444 Comp. shell bottom temperature ˚F 152 158 149 143 173 192
Refrigerant circuit
Ref. pipe length ft. 25 Refrigerant charge (R410A) 2 lb. 9 oz. 2 lb. 10 oz. 3 lb 9 oz.
Intake air temperature
Discharge air temperature
Indoor unit
Fan speed (High) rpm 1,280 1,140 1,140 1,140 1,250 1,250 Airfl ow (High) CFM 498 (Wet) 463 562 (Wet) 625 632 (Wet) 702
Intake air temperature Fan speed rpm 910 900 910 900 810 810
Airfl ow CFM 1,243 1,229 1,243 1,229 1,691 1,691
Outdoor unit
V,
phase,
Hz
MUZ-HM15NA
MUZ-HM15NA2
V,
phase,
Hz
DB ˚F807080708070
WB ˚F676067606760
DB ˚F 58 114 58 114 57 108
WB ˚F56—56—56—
DB ˚F954795479547
WB ˚F 43 43 43
208/230, 1, 60
MUZ-HM18NA
MUZ-HM18NA2
208/230, 1, 60
MUZ-HM24NA
MUZ-HM24NA2
29
7-5. CAPACITY AND INPUT CORRECTION BY INVERTER OUTPUT FREQUENCY
OBH747C
MUZ-HM09NA - U1 MUZ-HM09NA2 - U1
Correction of Cooling capacity
1.5
1.0
0.5
Capacity correction factors
0.0 0 50 100
The operational frequency of compressor
MUZ-HM09NA - U8 MUZ-HM09NA2 - U8
Correction of Cooling capacity
1.5
1.0
0.5
Capacity correction factors
0 50 100(Hz)
The operational frequency of compressor
Correction of Cooling total input
1.5
1.0
0.5
0.0 050100
The operational frequency of compressor
Correction of Cooling total input
1.5
1.0
0.5
0 50 100(Hz)
The operational frequency of compressor
Correction of Heating capacity
1.5
1.0
0.5
0.0 0 50 100 150
The operational frequency of compressor
Correction of Heating capacity
1.5
1.0
0.5
0 50 100 150(Hz)
The operational frequency of compressor
Correction of Heating total input
2.0
1.5
1.0
0.5
0.0 0 50 100 150
The operational frequency of compressor
Correction of Heating total input
2.0
1.5
1.0
0.5
0 50 100 150(Hz)
The operational frequency of compressor
MUZ-HM12NA - U1 MUZ-HM12NA2 - U1
Correction of Cooling capacity
1.5
1.0
0.5
Capacity correction factors
0.0 0 50 100
The operational frequency of compressor
MUZ-HM12NA - U8 MUZ-HM12NA2 - U8
Correction of Cooling capacity
1.5
1.0
0.5
Capacity correction factors
0 50 100(Hz)
The operational frequency of compressor
Correction of Cooling total input
1.5
1.0
0.5
0.0 050100
The operational frequency of compressor
Correction of Cooling total input
1.5
1.0
0.5
0 50 100(Hz)
The operational frequency of compressor
Correction of Heating capacity
1.5
1.0
0.5
0.0 0 50 100 150
The operational frequency of compressor
Correction of Heating capacity
1.5
1.0
0.5
0 50 100 150(Hz)
The operational frequency of compressor
Correction of Heating total input
2.0
1.5
1.0
0.5
0.0 0 50 100 150
The operational frequency of compressor
Correction of Heating total input
2.0
1.5
1.0
0.5
0 50 100 150(Hz)
The operational frequency of compressor
30
MUZ-HM15NA MUZ-HM15NA2
OBH747C
Correction of Cooling capacity
2.0
Correction of Cooling total input
2.0
Correction of Heating capacity
2.0
Correction of Heating total input
2.0
1.5
1.0
0.5
Capacity correction factors
0 25 50 75 100
The operational frequency of compressor
1.5
1.0
0.5
Input correction factors
(Hz) (Hz)
The operational frequency of compressor
MUZ-HM18NA MUZ-HM18NA2
Correction of Cooling capacity
2.0
1.5
1.0
0.5
Capacity correction factors
0 25 50 75 100
The operational frequency of compressor
2.0
1.5
1.0
0.5
Input correction factors
(Hz) (Hz)
The operational frequency of compressor
MUZ-HM24NA MUZ-HM24NA2
Correction of Cooling capacity
2.0
2.0
0 25 50 75 100
Correction of Cooling total input
0 25 50 75 100
Correction of Cooling total input
1.5
1.0
0.5
Capacity correction factors
0 50 100
The operational frequency of compressor
Correction of Heating capacity
2.0
1.5
1.0
0.5
150
Capacity correction factors
0 50 100
The operational frequency of compressor
Correction of Heating capacity
2.0
150
1.5
1.0
0.5
Input correction factors
(Hz) (Hz)
0 50 100
The operational frequency of compressor
Correction of Heating total input
2.0
1.5
1.0
0.5
150
Input correction factors
(Hz) (Hz)
0 50 100
The operational frequency of compressor
Correction of Heating total input
2.0
150
1.5
1.0
0.5
Capacity correction factors
30 60 90 120 150
0
The operational frequency of compressor
1.5
1.0
0.5
Input correction factors
(Hz) (Hz)
30 60 90 120 150
0
The operational frequency of compressor
1.5
1.0
0.5
Capacity correction factors
30 60 90 120 150
0
The operational frequency of compressor
(Hz) (Hz)
1.5
1.0
0.5
Input correction factors
30 60 90 120 150
0
The operational frequency of compressor
7-6. HOW TO OPERATE FIXED-FREQUENCY OPERATION (Test run operation)
1. Press EMERGENCY OPERATION switch to start COOL or HEAT mode (COOL: Press once, HEAT: Press twice).
2. Test run operation starts and continues to operate for 30 minutes.
3. Compressor operates at rated frequency in COOL mode or 58 Hz in HEAT mode.
4. Indoor fan operates at High speed.
5. After 30 minutes, test run operation finishes and EMERGENCY OPERATION starts (operation frequency of compressor var­ies).
6. To cancel test run operation (EMERGENCY OPERATION), press EMERGENCY OPERATION switch or any button on remote controller.
31
8
OBH747C
ACTUATOR CONTROL
MUZ-HM09NA MUZ-HM09NA2 MUZ-HM12NA MUZ-HM12NA2 MUZ-HM15NA MUZ-HM15NA2 MUZ-HM18NA MUZ-HM18NA2 MUZ-HM24NA MUZ-HM24NA2
8-1. OUTDOOR FAN MOTOR CONTROL
The fan motor turns ON/OFF, interlocking with the compressor. [ON] The fan motor turns ON 5 seconds before the compressor starts up. [OFF] The fan motor turns OFF 15 seconds after the compressor has stopped running.
5 seconds 15 seconds
ON
Compressor
OFF
ON
Outdoor fan motor
OFF
8-2. R.V. COIL CONTROL
Heating Cooling
Dry
NOTE: The 4-way valve reverses for 5 seconds right before start-up of the compressor.
8-3. RELATION BETWEEN MAIN SENSOR AND ACTUATOR
Discharge temperature thermistor
Indoor coil temperature thermistor
Defrost thermistor Heating: Defrosting Fin temperature thermistor Protection
Ambient temperature thermistor
Outdoor heat exchanger tem­perature thermistor
Optional parts
. . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
Compressor
R.V.coil
Outdoor fan motor
Sensor Purpose
ON OFF OFF
<COOL>
ON OFF
ON OFF
ON OFF
Protection Cooling: Coil frost prevention
Heating: High pressure protec­tion
Cooling: Low ambient tempera­ture operation
Heating: Defrosting (Heater)
Cooling: Low ambient tempera­ture operation
Cooling: High pressure protec­tion
5 seconds
<HEAT>
5 seconds
Compressor
LEV
○○ ○
○○ ○○○○○
○○ ○○○
○○○ ○○○
Actuator
Outdoor fan
motor
R.V. coil
Indoor fan
motor
Defrost
heater
32
9
OBH747C
SERVICE FUNCTIONS
MUZ-HM09NA MUZ-HM09NA2 MUZ-HM12NA MUZ-HM12NA2 MUZ-HM15NA MUZ-HM15NA2 MUZ-HM18NA MUZ-HM18NA2 MUZ-HM24NA MUZ-HM24NA2
9-1. CHANGE IN DEFROST SETTING
Changing defrost finish temperature
<JS> To change the defrost finish temperature, cut/solder the JS wire of the outdoor inverter P.C. board (Refer to 10-6.1.).
Jumper
(Initial setting)
JS
Soldered
None
(Cut)
MUZ-HM09/12
52°F (11°C) 41°F (5°C) 50°F (10°C) 41°F (5°C) 50°F (10°C)
52°F (11°C) 46°F (8°C) 55°F (13°C) 50°F (10°C) 64°F (18°C)
-
U1
MUZ-HM09
9-2. PRE-HEAT CONTROL SETTING
When moisture gets into the refrigerant cycle, it may interfere with the start-up of the compressor at low outside tempera­ture. The pre-heat control prevents this interference. The pre-heat control turns ON when the discharge temperature ther­mistor is 68°F (20°C) or below. When the pre-heat control turns ON, the compressor is energized. (About 50 W)
Pre-heat control setting
<JK> ON: To activate the pre-heat control, cut JK wire of the inverter P.C. board. OFF: To deactivate the pre-heat control, solder JK wire of the inverter P.C. board. (Refer to 10-6.1)
Defrost fi nish temperature
U8
-
MUZ-HM12
-
U8
MUZ-HM15/18 MUZ-HM24
Jumper Pre-heat control setting
Soldered
JK
Cut Activated
NOTE: When the inverter P.C. board is replaced, check the jumper wires, and cut/solder them if necessary.
Deactivated
(Factory setting)
33
10
Lead wiring
<Incorrect>
Connector housing
<Correct>
OBH747C
TROUBLESHOOTING
MUZ-HM09NA MUZ-HM09NA2 MUZ-HM12NA MUZ-HM12NA2 MUZ-HM15NA MUZ-HM15NA2 MUZ-HM18NA MUZ-HM18NA2 MUZ-HM24NA MUZ-HM24NA2
10-1. CAUTIONS ON TROUBLESHOOTING
1. Before troubleshooting, check the following
1) Check the power supply voltage.
2) Check the indoor/outdoor connecting wire for miswiring.
2. Take care of the following during servicing
1) Before servicing the air conditioner, be sure to turn OFF the main unit first with the remote controller, then after con­firming the horizontal vane is closed, turn off the breaker and/or disconnect the power plug.
2) Be sure to turn OFF the power supply before removing the front panel, the cabinet, the top panel, and the electronic control P.C. board.
3) When removing the electrical parts, be careful of the residual voltage of smoothing capacitor.
4) When removing the electronic control P.C. board, hold the edge of the board with care NOT to apply stress on the components.
5) When connecting or disconnecting the connectors, hold the connector housing. DO NOT pull the lead wires.
3. Troubleshooting procedure
1)
Check if the OPERATION INDICATOR lamp on the indoor unit is flashing on and off to indicate an abnormality. To make
sure, check how many times the OPERATION INDICATOR lamp is flashing on and off before starting service work. (See the service manual of the indoor unit for a description of those failure codes.)
2) Before servicing, check that the connector and terminal are connected properly.
3) When the electronic control P.C. board seems to be defective, check the copper foil pattern for disconnection and the
components for bursting and discoloration.
4) Refer to 10-2 and 10-3.
34
10-2. FAILURE MODE RECALL FUNCTION
OBH747C
Outline of the function This air conditioner can memorize the abnormal condition which has occurred once. Even though LED indication listed on the troubleshooting check table (10-3.) disappears, the memorized failure details can be recalled.
1. Flow chart of failure mode recall function for the indoor/outdoor unit
Operational procedure
Setting up the failure mode recall function
Judgment of indoor/outdoor abnormality
The cause of abnormality cannot be found because the abnormality does not recur.
Turn ON the power supply. <Preparation of the remote controller>
While pressing OPERATION SELECT button and TOO COOL button on the remote
controller at the same time, press RESET button.
First, release RESET button.
Hold down the other 2 buttons for another 3 seconds. Make sure that the indicators on
the LCD screen shown in the right fi gure are all displayed. Then release the buttons.
Press STOP/OPERATE (OFF/ON) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit.
Does the upper lamp of the OPERATION INDICATOR lamp on the indoor unit blink at the interval of 0.5 seconds? Blinks: Either indoor or outdoor unit is abnormal. Beep is
emitted at the same timing as the blinking of the upper lamp of the OPERATION INDICATOR lamp.
Before blinking, does the upper lamp of the OPERATION INDICATOR lamp stay ON for 3 seconds? When it stays ON for 3 seconds (without beep): The outdoor unit
The indoor unit is abnormal. Check the blinking pattern, and identify the abnormal point by referring to the table of indoor unit failure mode recall function. (Refer to indoor unit service manual.) Make sure to check at least 2 consecutive blinking cycles.
1
1. Regardless of normal or abnormal condition, a short beep is emitted once the signal is received.
No (OFF)
Yes (Blinks)
No
2
is abnormal.
2
Indoor unit is normal. But the outdoor unit might be abnormal because there are some abnor­malities that cannot be recalled with this way. Check if outdoor unit is abnormal according to the detailed outdoor unit failure mode recall function. (Refer to 10-2.2)
Yes
The outdoor unit is abnormal. Check the blinking pattern, and identify the abnormal point by referring to the outdoor unit failure recall mode table. (Refer to 10-2.3) Make sure to check at least 2 consecutive blinking cycles.
3
Releasing the failure mode recall function
Deleting the memorized abnormal condition
Release the failure mode recall function by the following procedures. Turn OFF the power supply and turn it ON again. Press RESET button of the remote controller.
Repair the failure parts.
After repairing the unit, recall the failure mode again according to "Setting up the failure mode recall
function" mentioned above.
Press STOP/OPERATE (OFF/ON) button of the remote controller (the set temperature is displayed)
with the remote controller headed towards the indoor unit. Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted. Release the failure mode recall function according to "Releasing the failure mode recall function"
mentioned above.
NOTE: 1. Make sure to release the failure mode recall function after it is set up, otherwise the unit cannot operate properly.
2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.
2. Blinking pattern when the indoor unit is abnormal:
2.5-second OFF
Blinking at 0.5­second interval
2.5-second OFF
Blinking at 0.5-
second interval
ON
OFF
Repeated cycle Repeated cycle
Beeps
3.Blinking pattern when the outdoor unit is abnormal:
2.5-second OFF 3-second ON
Blinking at 0.5­second interval
Beeps
Repeated cycle
2.5-second OFF 3-second ON
ON
OFF
No beep Beeps
Repeated cycle
No beep Beeps
Repeated cycle
35
Beeps
Blinking at 0.5­second interval
Repeated cycle
2. Flow chart of the detailed outdoor unit failure mode recall function
OBH747C
Operational procedure
The outdoor unit might be abnormal. Check if outdoor unit is abnormal according to the following procedures.
Make sure that the remote controller is set to the failure mode recall function.
With the remote controller headed towards the indoor unit, press TOO COOL button to adjust the set temperature to 77°F (25°C).
Does the upper lamp of the OPERATION INDICATOR lamp on the indoor unit blink at the interval of 0.5 seconds? Blinks: The outdoor unit is abnormal. Beep is emitted at
the same timing as the blinking of the upper lamp of the OPERATION INDICATOR lamp.
Yes (Blinks
The outdoor unit is abnormal. Check the blinking pattern, and identify the abnormal point by referring to the table of outdoor unit failure mode recall function (10-2.3.). Make sure to check at least 2 consecutive blinking cycles.
Releasing the failure mode recall function
Release the failure mode recall function by the following procedures. Turn OFF the power supply and turn it ON again. Press RESET button of the remote controller.
Repair the failure parts.
Deleting the memorized abnormal condition
After repairing the unit, recall the failure mode again according to "Setting up the failure mode recall
function" (10-2.1.).
Press STOP/OPERATE (OFF/ON) button of the remote controller (the set temperature is displayed) with
the remote controller headed towards the indoor unit. Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted. Release the failure mode recall function according to "Releasing the failure mode recall function" men-
tioned above.
NOTE: 1. Make sure to release the failure mode recall function after it is set up, otherwise the unit cannot operate properly.
2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.
)
1
No
2
(OFF)
2
1. Regardless of normal or abnormal condition, 2 short beeps are emitted as the signal is received.
The outdoor unit is normal.
Release the failure mode recall function accord­ing to the left mentioned procedure.
2.Blinking pattern when outdoor unit is abnormal:
2.5-second OFF 3-second ON
ON
OFF
No beep
Repeated cycle
Blinking at 0.5­second interval
Beeps
2.5-second OFF 3-second ON
No beep Beeps
Repeated cycle
36
Blinking at 0.5­second interval
Repeated cycle
3. Table of outdoor unit failure mode recall function
OBH747C
NOTE: Blinking patterns of this mode differ from the ones of TROUBLESHOOTING CHECK TABLE (10-3.).
MUZ-HM09NA MUZ-HM09NA2 MUZ-HM12NA MUZ-HM12NA2
OPERATION
INDICATOR
upper lamp
(Indoor unit) OFF None (Normal) — 2-time fl ash
2.5 seconds OFF
3-time fl ash
2.5 seconds OFF
4-time fl ash
2.5 seconds OFF
5-time fl ash
2.5 seconds OFF
6-time fl ash
2.5 seconds OFF
7-time fl ash
2.5 seconds OFF
8-time fl ash
2.5 seconds OFF
9-time fl ash
2.5 seconds OFF
10-time fl ash
2.5 seconds OFF
Abnormal point
(Failure mode / protection)
Outdoor power system
Discharge temperature thermistor
Defrost thermistor Fin temperature thermistor 3-time fl ash
P.C. board temperature thermistor
Ambient temperature thermistor
Overcurrent 11-time fl ash
Compressor synchronous abnormality (Compressor start­up failure protection)
Discharge temperature
High pressure
Fin temperature/ P.C. board temperature
Outdoor fan motor
Nonvolatile memory data 5-time fl ash
Discharge temperature
LED indication
(Outdoor P.C. board)
1-time fl ash every
2.5 seconds
2.5 seconds OFF 4-time fl ash
2.5 seconds OFF 2-time fl ash
2.5 seconds OFF
2.5 seconds OFF
12-time fl ash
2.5 seconds OFF
7-time fl ash
2.5 seconds OFF
2.5 seconds OFF
Condition Remedy
Overcurrent protection cut-out operates 3 consecutive times within 1 minute after the compressor gets started.
Thermistor shorts or opens during compressor running.
Large current fl ows into intelligent power module/ power module
Waveform of compressor current is distorted.
Temperature of discharge temperature thermistor exceeds 241°F (116°C), compressor stops. Compressor can restart if discharge temperature thermistor reads 212°F (100°C) or less 3 minutes later.
Temperature of indoor coil thermistor exceeds 158°F (70°C) in HEAT mode. Temperature of outdoor heat exchanger temperature thermistor exceeds 158°F (70°C) in COOL mode.
Temperature of fi n temperature thermistor on the inverter P.C. board exceeds 167 - 176°F (75 - 80°C), or temperature of P.C. board temperature thermistor on the inverter P.C. board exceeds 158 - 167°F (70 - 75°C).
Outdoor fan has stopped 3 times in a row within 30 seconds after outdoor fan start-up.
Nonvolatile memory data cannot be read properly.
Temperature of discharge temperature thermistor has been 122°F (50°C) or less for 20 minutes.
Reconnect connectors.
• Refer to 10-5.
• to check inverter/ compressor". Check the stop valve.
• Refer to 10-5. "Check
• of outdoor thermistors". Defective outdoor thermistors can be identifi ed by checking the blinking pattern of LED.
Reconnect compressor
• connector. Refer to 10-5.
• to check inverter/ compressor". Check the stop valve.
• Reconnect compressor
• connector. Refer to 10-5.
• to check inverter/ compressor".
Check the refrigerant
• circuit and the refrigerant amount. Refer to 10-5.
• of LEV".
Check the refrigerant
• circuit and the refrigerant amount. Check the stop valve.
Check around the
• outdoor unit. Check the outdoor unit
• air passage. Refer to 10-5.
• of outdoor fan motor".
Refer to 10-5. "Check
• of outdoor fan motor". Refer to 10-5. of inverter P.C. board".
Replace the inverter
• P.C. board.
Refer to 10-5. "Check
• of LEV". Check the refrigerant
• circuit and the refrigerant amount.
"How
"How
"How
"Check
"Check
"Check
Indoor/
outdoor unit
failure mode
recall function
Outdoor unit failure mode
recall function
○○
○○
○○
37
OPERATION
OBH747C
INDICATOR
upper lamp
(Indoor unit)
11-time fl ash
2.5 seconds OFF
12-time fl ash
2.5 seconds OFF
14-time fl ash
2.5 seconds OFF
Abnormal point
(Failure mode / protection) DC voltage 8-time fl ash Each phase current of
compressor Overcurrent Compressor open-
phase
Stop valve (Closed valve) 14-time fl ash
4-way valve/ Pipe temperature
Outdoor refrigerant system abnormality (MUZ-
HM09/12NA(2)
U1
-
)
LED indication
(Outdoor P.C. board)
2.5 seconds OFF 9-time fl ash
2.5 seconds OFF 10-time fl ash
2.5 seconds OFF
2.5 seconds OFF
16-time fl ash
2.5 seconds OFF
1-time fl ash
2.5 seconds OFF
NOTE: Blinking patterns of this mode differ from the ones of TROUBLESHOOTING CHECK TABLE (10-3.).
Condition Remedy
DC voltage of inverter cannot be detected normally. Each phase current of compressor cannot be detected normally.
Large current fl ows into intelligent power module (IPM)/power module
(IPM) The open-phase operation of compressor is detected. The interphase short circuit occurs in the output of the intelligent power module (IPM)/power module (IPM) The compressor winding shorts circuit.
Closed valve is detected by compressor current.
The 4-way valve does not work properly. The indoor coil thermistor detects an abnormal temperature.
A closed valve and air trapped in the refrigerant circuit are detected based on the temperature sensed by the indoor and outdoor thermistors and the current of the compressor.
Refer to 10-5.
• to check inverter/
compressor".
Reconnect compressor
• connector. Refer to 10-5.
• to check inverter/ compressor".
Check the stop valve
Check the 4-way valve.
Replace the inverter
P.C. board.
Check for a gas leak
in a connecting piping etc. Check the stop valve.
Refer to 10-5.
“Check of outdoor refrigerant circuit”.
"How
"How
Indoor/
outdoor unit
failure mode
recall function
Outdoor unit failure mode
recall function
○○
○○
38
MUZ-HM15NA MUZ-HM15NA2
OBH747C
MUZ-HM18NA MUZ-HM18NA2 MUZ-HM24NA MUZ-HM24NA2
The upper
lamp of the
OPERATION
INDICATOR
lamp
(Indoor unit)
OFF None (Normal) — 1-time fl ash
2.5 seconds OFF
2-time fl ash
2.5 seconds OFF
3-time fl ash
2.5 seconds OFF
4-time fl ash
2.5 seconds OFF
5-time fl ash
2.5 seconds OFF
6-time fl ash
2.5 seconds OFF
7-time fl ash
2.5 seconds OFF
8-time fl ash
2.5 seconds OFF
9-time fl ash
2.5 seconds OFF
Abnormal point
(Failure mode/protection)
Indoor/outdoor communication, receiving error
Indoor/outdoor communication, receiving error
Outdoor power system
Discharge temperature thermistor
Defrost thermistor Fin temperature thermistor 3-time fl ash
P.C. board temperature thermistor
Ambient temperature thermistor
Outdoor heat exchanger temperature thermistor
Overcurrent 11-time fl ash
Compressor synchronous abnormality (Compressor start­up failure protection)
Discharge temperature
High pressure
Fin temperature/ P.C. board temperature
Outdoor fan motor
Nonvolatile memory data 5-time fl ash Power module (IPM) (MUZ-
HM09/12NA(2) (MUZ-HM09/12/15/18/24NA(2)
U1
-
)
-
U8
)/(IC700)
LED indication
(Outdoor P.C. board)
1-time fl ash every
2.5 seconds
2.5 seconds OFF 4-time fl ash
2.5 seconds OFF 2-time fl ash
2.5 seconds OFF —
2.5 seconds OFF
12-time fl ash
2.5 seconds OFF
7-time fl ash
2.5 seconds OFF
2.5 seconds OFF
6-time fl ash
2.5 seconds OFF
Any signals from the inverter P.C. board cannot be received normally for 3 minutes.
Although the inverter P.C. board sends signal "0", signal "1" has been received 30 consecutive times. Overcurrent protection cut-out operates 3 consecutive times within 1 minute after the compressor gets started.
Thermistor shorts or opens during compressor running.
Large current fl ows into the power module (IPM) (MUZ-
HM09/12NA(2) HM09/12/15/18/24NA(2)
Waveform of compressor current is distorted.
Temperature of discharge temperature thermistor exceeds 241°F (116°C), compressor stops. Compressor can restart if discharge temperature thermistor reads 212°F (100°C) or less 3 minutes later.
Temperature indoor coil thermistor exceeds 158°F (70°C) in HEAT mode. Temperature defrost thermistor exceeds 158°F (70°C) in COOL mode.
Temperature of the fi n temperature thermistor on the inverter P.C. board exceeds 167 - 187°F (75 - 86°C), or temperature of P.C. board temperature thermistor on the inverter P.C. board exceeds 162 - 185°F (72 - 85°C).
Outdoor fan has stopped 3 times in a row within 30 seconds after outdoor fan start-up.
Nonvolatile memory data cannot be read properly.
The interface short circuit occurs in the output of the power module (IPM)
(MUZ-HM09/12NA(2) (MUZ-HM09/12/15/18/24NA(2) The compressor winding shorts circuit.
NOTE: Blinking patterns of this mode differ from the ones of TROUBLESHOOTING CHECK TABLE (10-3.).
Indoor/outdoor
Condition Remedy
How
How
"How
"How
"How
"Check
"Check
"Check
"How
U8
-
)/(IC700) (MUZ-
-
U1
-
U8
)/(IC700)
•Refer to 10-5. to check miswiring and serial signal error.
•Refer to 10-5. to check miswiring and serial signal error. Reconnect
• connectors. Refer to 10-5.
• to check inverter/
compressor". Check stop valve.
• Refer to 10-5.
• "Check of outdoor thermistors". Defective outdoor thermistors can be identifi ed by checking the blinking pattern of LED.
Reconnect
• compressor connector. Refer to 10-5.
).
to check inverter/ compressor". Check stop valve.
• Reconnect
• compressor connector. Refer to 10-5.
• to check inverter/ compressor".
Check refrigerant
• circuit and refrigerant amount. Refer to 10-5.
• of LEV".
Check refrigerant
• circuit and refrigerant amount. Check stop valve.
• Check around outdoor
• unit. Check outdoor unit air
• passage. Refer to 10-5.
• of outdoor fan motor".
Refer to 10-5. "Check
• of outdoor fan motor". Refer to 10-5. of inverter P.C. board".
Replace the inverter
• P.C. board.
Refer to 10-5.
• to check inverter/ compressor".
U1
-
).
unit failure
mode recall
function
○○
○○
○○
○○
Outdoor unit failure mode
recall function
39
The upper
OBH747C
lamp of the
OPERATION
INDICATOR
lamp
(Indoor unit)
10-time fl ash
2.5 seconds OFF
11-time fl ash
2.5 seconds OFF
14-time fl ash or more
2.5 seconds OFF
Abnormal point
(Failure mode/protection)
Discharge temperature
DC voltage 8-time fl ash
Each phase current of compressor
Stop valve (Closed valve) 14-time fl ash
4-way valve/ Pipe temperature
Outdoor refrigerant system abnormality
LED indication
(Outdoor P.C. board)
2.5 seconds OFF 9-time fl ash
2.5 seconds OFF
2.5 seconds OFF
16-time fl ash
2.5 seconds OFF
1-time fl ash
2.5 seconds OFF
NOTE: Blinking patterns of this mode differ from the ones of TROUBLESHOOTING CHECK TABLE (10-3.).
Condition Remedy
Temperature of discharge temperature thermistor has been 122°F (50°C) or less for 20 minutes.
DC voltage of inverter cannot be detected normally.
Each phase current of compressor cannot be detected normally.
Closed valve is detected by compressor current.
The 4-way valve does not work properly. The indoor coil thermistor detects an abnormal temperature.
A closed valve and air trapped in the refrigerant circuit are detected based on the temperature sensed by the indoor and outdoor thermistors and the current of the compressor.
Refer to 10-5.
• of LEV".
Check refrigerant
• circuit and refrigerant amount.
Refer to 10-5. "How
• to check inverter/ compressor".
Check stop valve.
Check the 4-way
• valve. Replace the inverter
• P.C. board.
Check for a gas leak
• in a connecting piping etc. Check the stop valve.
• Refer to 10-5.
• “Check of outdoor
refrigerant circuit”.
"Check
Indoor/outdoor
unit failure
mode recall
function
Outdoor unit failure mode
recall function
○○
○○
40
10-3. TROUBLESHOOTING CHECK TABLE
OBH747C
No. Symptom LED indication
Outdoor unit does not op­erate.
1
2
3
4 5
6
7
'Outdoor unit stops and restarts 3
8
minutes later' is repeated.
9
11
NOTE: 1. The location of LED is illustrated at the right fi gure. Refer to 10-6.1.
2. LED is lighted during normal operation.
3. Blinking patterns of this mode differ from the ones of the failure recall mode. The fl ashing frequency shows the number of times the LED blinks after every 2.5-second OFF.
(Example) When the fl ashing frequency is “2”.
ON
2.5-second OFF
OFF
1-time fl ash every
2.5 seconds
6-time fl ash
2.5 seconds OFF 11-time fl ash
2.5 seconds OFF
16-time fl ash
2.5 seconds OFF
17-time fl ash
2.5 seconds OFF (MUZ-
HM09/12/15/18/ 24NA(2)
2-time fl ash
2.5 seconds OFF
3-time fl ash
2.5 seconds OFF
4-time fl ash
2.5 seconds OFF
5-time fl ash
2.5 seconds OFF
8-time fl ash
2.5 seconds OFF
10-time fl ash
2.5 seconds OFF
12-time fl ash
2.5 seconds OFF 13-time fl ash
2.5 seconds OFF
U1
-
Abnormal point/
Condition Outdoor power sys­tem
Outdoor thermistors Discharge temperature thermistor, fi n temperature thermistor,
Outdoor control sys­tem
Serial signal The communication fails between the indoor and outdoor unit Stop valve/
Closed valve 4-way valve/
Pipe temperature
Outdoor refrigerant system abnormality
)
Overcurrent protec­tion
Discharge tem­perature overheat protection
Fin temperature / P.C. board tem­perature thermistor overheat protection
High pressure pro­tection
Compressor syn­chronous abnormal­ity
Outdoor fan motor Outdoor fan has stopped 3 times in a row within 30 seconds
Each phase current of compressor
DC voltage DC voltage of inverter cannot be detected normally.
0.5-second ON
2.5-second OFF
Overcurrent protection cut-out operates 3 consecutive times within 1 minute after the compressor gets started.
defrost thermistor, P.C. board temperature thermistor, outdoor heat exchanger temperature thermistor or ambient tempera­ture thermistor shorts or opens during compressor running.
Nonvolatile memory data cannot be read properly. (The upper lamp of the OPERATION INDICATOR lamp on the
indoor unit lights up or fl ashes 7-time.)
for 3 minutes. Closed valve is detected by compressor current.
The 4-way valve does not work properly. The indoor coil thermistor detects an abnormal temperature.
A closed valve and air trapped in the refrigerant circuit are detected based on the temperature sensed by the indoor and outdoor thermistors and the current of the compressor.
Large current fl ows into the power module (IPM) (MUZ-
HM09/12NA(2)
U1
-
).
When overcurrent protection occurs within 10 seconds after
compressor starts, compressor restarts after 15 seconds (MUZ-HM09/12NA).
Temperature of discharge temperature thermistor exceeds 241°F (116°C), compressor stops. Compressor can restart if discharge temperature thermistor reads 212°F (100°C) or less 3 minutes later.
Temperature of the fi n temperature thermistor on the heat sink exceeds 167 - 176°F (75 - 80°C) (MUZ-HM09/12NA(2))/167 ­187°F (75 - 86°C) (MUZ-HM15/18/24NA(2)) or temperature of P.C. board temperature thermistor on the inverter P.C. board ex­ceeds 158 - 167°F (70 - 75°C) (MUZ-HM09/12NA(2))/162 ­185°F (72 - 85°C) (MUZ-HM15/18/24NA(2)). Indoor coil thermistor exceeds 158°F (70°C) in HEAT mode. Defrost thermistor exceeds 158°F (70°C) in COOL mode.
The waveform of compressor current is distorted.
after outdoor fan start-up.
Each phase current of compressor cannot be detected nor­mally.
-
Condition Remedy
U8
)/(IC700) (MUZ-HM09/12/15/18/24NA(2)
0.5-second ON
Reconnect connector of compres-
• sor. Refer to 10-5.
• inverter/compressor".
Check stop valve.
• Refer to 10-5.
• thermistors".
Replace inverter P.C. board.
Refer to 10-5.
• miswiring and serial signal error.
Check stop valve.
• Refer to 10-5.
• coil". Replace the inverter P.C. board.
• Check for a gas leak in a
• connecting piping etc. Check the stop valve.
• Refer to 10-5.
• refrigerant circuit”.
Reconnect connector of compressor.
• Refer to 10-5. "How to check
• inverter/compressor". Check stop valve.
Check refrigerant circuit and refrig-
• erant amount. Refer to 10-5.
• Check around outdoor unit.
• Check outdoor unit air passage.
• Refer to 10-5.
• fan motor".
Check refrigerant circuit and refrig-
• erant amount. Check stop valve.
• Reconnect connector of compressor.
• Refer to 10-5.
• inverter/compressor".
Refer to 10-5.
• fan motor. Refer to 10-5.
• P.C. board.
Refer to 10-5.
• inverter/compressor".
Refer to 10-5.
• verter/compressor".
Inverter P.C. board
MUZ-HM09/12NA(2)
MUZ-HM15/18/24NA(2)
Flashing
"How to check
"Check of outdoor
"How to check
"Check of R.V.
“Check of outdoor
"Check of LEV".
"Check of outdoor
"How to check
"Check of outdoor "Check of inverter
"How to check "How to check in-
LED
Flashing
LED
41
No. Symptom LED indication
OBH747C
Outdoor unit operates.
Outdoor unit operates.
NOTE: 1. The location of LED is illustrated at the right fi gure. Refer to 10-6.1.
2. LED is lighted during normal operation.
3. Blinking patterns of this mode differ from the ones of the failure recall mode. The fl ashing frequency shows the number of times the LED blinks after every 2.5-second OFF.
(Example) When the fl ashing frequency is “2”.
ON
2.5-second OFF
OFF
1-time fl ash
2.5 seconds OFF
3-time fl ash
2.5 seconds OFF
4-time fl ash
2.5 seconds OFF
5-time fl ash
2.5 seconds OFF
7-time fl ash
2.5 seconds OFF
8-time fl ash
2.5 seconds OFF
9-time fl ash
2.5 seconds OFF
Abnormal point/
Condition Frequency drop by current protection
Frequency drop by high pressure pro­tection
Frequency drop by defrosting in COOL mode
Frequency drop by discharge tempera­ture protection
Outside temperature thermistor protec­tion
Low discharge tem­perature protection
PAM protection PAM: Pulse Ampli­tude Modulation
Zero cross detecting circuit (MUZ-HM09/12NA(2))
Inverter check mode The connector of compressor is disconnected, inverter check
0.5-second ON
2.5-second OFF
MUZ-HM 09/12NA(2)
MUZ-HM15/ 18/24NA(2)
Temperature of indoor coil thermistor exceeds 131 °F (55°C) in HEAT mode, compressor frequency lowers.
Indoor coil thermistor reads 46°F (8°C) or less in COOL mode, compressor frequency lowers.
Temperature of discharge temperature thermistor exceeds 232°F (111°C), compressor frequency lowers.
When the outside temperature thermistor shorts or opens, protective operation without that thermistor is performed.
Temperature of discharge temperature thermistor has been 122°F (50°C) or less for 20 minutes.
The overcurrent fl ows into IGBT (Insulated Gate Bipolar tran- sistor: TR821) (MUZ-HM09/12NA(2)
correction: IC820) (MUZ-HM09/12/15/18/24NA(2) DC voltage reaches 320 V (MUZ-HM09/12NA(2) (MUZ-HM09/12/15/18/24NA(2)
restarts.
Zero cross signal for PAM control cannot be detected.
mode starts.
Current from power outlet is nearing Max. fuse size.
When the input current exceeds approximately
10.5 A, compressor frequency lowers.
Condition Remedy
U8
-
)/PFC (Power factor
U1
-
) or more, PAM stops and
0.5-second ON
-
-
U8
U1
) or the
)/394 V
The unit is normal, but check the following. Check if indoor fi lters are clogged.
• Check if refrigerant is short.
• Check if indoor/outdoor unit air
• circulation is short cycled.
Check refrigerant circuit and refrig-
• erant amount. Refer to 10-5.
• Refer to 10-5.
• thermistors".
Refer to 10-5.
• thermistors.
Refer to 10-5.
• Check refrigerant circuit and refrig-
• erant amount.
This is not malfunction. PAM pro­tection will be activated in the fol­lowing cases:
1 Instantaneous power voltage
drop. (Short time power failure)
2 When the power supply voltage
is high.
Check if the connector of the com-
• pressor is correctly connected. Refer to 10-5. inverter/compressor".
Inverter P.C. board
MUZ-HM09/12NA(2)
MUZ-HM15/18/24NA(2)
Flashing
"Check of LEV". "Check of outdoor
Check of outdoor
"Check of LEV".
"How to check
Flashing
LED
LED
42
10-4. TROUBLE CRITERION OF MAIN PARTS
OBH747C
MUZ-HM09NA MUZ-HM09NA2 MUZ-HM12NA MUZ-HM12NA2 MUZ-HM15NA MUZ-HM15NA2 MUZ-HM18NA MUZ-HM18NA2 MUZ-HM24NA MUZ-HM24NA2
Part name Check method and criterion Figure
Defrost thermistor (RT61) Fin temperature
thermistor (RT64)
Measure the resistance with a tester.
Ambient temperature thermis­tor (RT65)
Outdoor heat exchanger tem­perature thermistor (RT68)
Discharge temperature ther­mistor (RT62)
Compressor
Outdoor fan motor
R. V. coil (21S4)
Refer to 10-6. “Test point diagram and voltage”, 1. “Inverter P.C. board”, for the chart of thermistor.
Measure the resistance with a tester. Before measurement, hold the thermistor with your hands to warm it up.
Refer to 10-6. “Test point diagram and voltage”, 1. “Inverter P.C. board”, for the chart of thermistor.
Measure the resistance between terminals using a tester. [Temperature: 14 - 104°F (-10 - 40°C)]
Normal (Ω)
HM09/12
-
U1
HM09
-
U8
HM12
-
U8
HM15/18/24
U-V
U-W
1.26 - 1.72 1.36 - 1.93 1.52 - 2.17 0.82 - 1.11
V-W
Measure the resistance between lead wires using a tester. [Temperature: 14 - 104°F (-10 - 40°C)]
Color of lead wire
HM09/12/15/18 HM24
Normal (Ω)
RED – BLK
BLK – WHT
29 - 40 12 - 16
WHT – RED
Measure the resistance using a tester. [Temperature: 14 - 104°F (-10 - 40°C)]
Normal (kΩ)
0.97 - 1.38
WHT
V
WHT
V
RED BLK
W
U
RED BLK
W
U
Measure the resistance using a tester. [Temperature: 14 - 104°F (-10 - 40°C)]
Expansion valve coil (LEV)
Measure the resistance using a tester.
Defrost heater
[Temperature: 14 - 104°F (-10 - 40°C)]
(Optional parts)
Color of lead wire Normal (Ω)
RED – ORN RED – WHT
RED – BLU
37 - 54
RED – YLW
Normal (Ω)
349 - 428
43
WHT ORN
RED
(+12V)
LEV
YLW
BLU
10-5. TROUBLESHOOTING FLOW
OBH747C
A How to check inverter/compressor
Disconnect the connector between the compressor and the
-
power module (IPM) (MUZ-HM09/12NA(2)
-
(MUZ-HM09/12NA(2)
U1
, MUZ-HM
Check the voltage between terminals.
Are the voltages balanced?
Yes
Check the compressor.
U8
)/(IC700)
15/18/24NA(2))
No
See 10-5. “Check of open phase”.
Replace the inverter P.C. board.
See 10-5. “Check of compressor”.
B Check of open phase
-
With the connector between the compressor and the power module (IPM) (MUZ-HM09/12NA(2)
-
U1
HM09/12NA(2)
, MUZ-HM15/18/24NA(2)) disconnected, activate the inverter and check if the inverter is normal by meas-
uring the voltage balance between the terminals. Output voltage is 50 - 130 V. (The voltage may differ according to the tester.) << Operation method>>
Start cooling or heating operation by pressing EMERGENCY OPERATION switch on the indoor unit. (TEST RUN OPERA-
TION: Refer to 7-6.) <<Measurement point>> At 3 points BLK (U)-WHT (V)
Measure AC voltage between the lead wires at 3 points.
BLK (U)-RED (W) WHT(V)-RED (W)
U8
)/(IC700) (
MUZ-
NOTE: 1. Output voltage varies according to power supply voltage.
2. Measure the voltage by analog type tester.
3. During this check, LED of the inverter P.C. board fl ashes 9 times. (Refer to 10-6.1.)
C Check of compressor
Refer to 10-5. “Check of compressor winding”. Is the compressor normal?
Yes
Refer to 10-5. “Check of compressor operation time”. Does the compressor operate continuously?
Yes
OK
No
No
Replace the compressor.
Refer to 10-5.
“Check of compressor start failure”.
44
D Check of compressor winding
OBH747C
Disconnect the connector between the compressor and the power module (IPM) (MUZ-HM09/12NA(2)
HM09/12NA(2)
<<Measurement point>> At 3 points BLK-WHT BLK-RED WHT-RED <<Judgement>> Refer to 10-4. 0 [Ω] ················Abnormal [short] Infinite [Ω] ·······Abnormal [open] NOTE: Be sure to zero the ohmmeter before measurement.
-
U1
, MUZ-HM15/18/24NA(2)), and measure the resistance between the compressor terminals.
Measure the resistance between the lead wires at 3 points.
E Check of compressor operation time
<<Judgement>>
-
U8
)/(IC700) (
MUZ-
Connect the compressor and activate the inverter. Then measure the time until the inverter stops due to overcurrent. <<Operation method>> Start heating or cooling operation by pressing EMERGENCY OPERATION switch on the indoor unit. (TEST RUN OPERATION: Refer to 7-6.) <<Measurement>> Measure the time from the start of compressor to the stop of compressor due to overcurrent.
F Check of compressor start failure
Confi rm that ~ is normal.
•Electrical circuit check . Contact of the compressor connector . Output voltage of inverter P.C. board and balance of them (See 10-5. ) . Direct current voltage between DB61(+) and (-) on the inverter P.C. board . Voltage between outdoor terminal block S1-S2
0 second 1 second
2 seconds
10 seconds
10 minutes
Compressor starts Abnormal
((IPM) (MUZ-HM09/12NA(2) (IC700) ( MUZ-HM15/18/24NA(2)) failure) (Compressor winding short)
Abnormal (Compressor lock out) (Starting defect)
Abnormal (Poor contact) (Inverter P.C. board defect) (Disconnected connector)
Abnormal (Refrigerant circuit defect) (Closed valve)
Normal
MUZ-HM09/12NA(2)
-
-
U8
)/
U1
,
Does the compressor run for 10 seconds or more after it starts?
No
After the compressor is heated with a drier, does the compressor start?
1
Yes
Compressor start failure. Activate pre-heat control. (Refer to 9-2. "PRE-HEAT CONTROL SETTING")
Yes
No
Check the refrigerant circuit. Check the stop valve.
Replace the compressor.
1 Heat the compressor with a drier for about 20 minutes. Do not recover refrigerant gas while heating.
Heating part
45
G Check of outdoor thermistors
OBH747C
Disconnect the connector of thermistor in the inverter P.C. board (see below table), and measure the resistance of thermistor.
Is the resistance of thermistor normal? (Refer to 10-6.1.)
Yes
No
Replace the thermistor except RT64. When RT64 is abnormal, replace the inverter P.C. board.
Reconnect the connector of thermistor. Turn ON the power supply and press EMERGENCY OPERATION switch.
Does the unit operate for 10 minutes or more without showing thermistor abnormality?
No
Replace the inverter P.C. board.
Yes
OK (Cause is poor contact.)
Thermistor Symbol Connector, Pin No. Board Defrost RT61 Between CN641 pin1 and pin2 Discharge temperature RT62 Between CN641 pin3 and pin4 Fin temperature RT64 Between CN642 pin1 and pin2
Inverter P.C. board Ambient temperature RT65 Between CN643 pin1 and pin2 Outdoor heat exchanger temperature RT68 Between CN644 pin1 and pin3
H Check of R.V. coil
First of all, measure the resistance of R.V. coil to check if the coil is defective. Refer to 10-4. Check if there is 208/230 VAC at L1 - L2. In case CN721 is disconnected or R.V. coil is open, voltage is generated between the terminal pins of the connector
although no signal is being transmitted to R.V. coil.
Check if CN721 is connected.
Unit operates COOL mode even if it is set to HEAT mode.
Disconnect connector between the compressor and the power module
-
(IPM) (MUZ-HM09/12NA(2) (IC700) (
MUZ-HM09/12NA(2)
U8
)/
-
U1
, MUZ-
HM15/18/24NA(2)).
Turn ON the power supply and press EMERGENCY OPERATION switch twice (HEAT mode).
Unit operates HEAT mode even if it is set to COOL mode.
Disconnect connector between the compressor and the power module (IPM) (MUZ-HM09/12NA(2) (IC700) (
MUZ-HM09/12NA(2)
HM15/18/24NA(2)).
Turn ON the power supply and press EMERGENCY OPERATION switch once (COOL mode).
-
U8
)/
-
U1
, MUZ-
Is there 208/230 VAC between CN721 and
on the inverter P.C. board 3 minutes after the power supply is turned ON?
Yes
Replace the 4-way valve.
Is there 208/230 VAC between CN721 and
on the inverter P.C. board 3 minutes after the power supply is turned ON?
No
Replace the 4-way valve.
46
Replace the inverter P.C. board.
No
Replace the inverter P.C. board.
Yes
I Check of outdoor fan motor
OBH747C
Check the connection between the connector CN931 and CN932. Disconnect the connectors CN931 and CN932 from the inverter P.C. board.
Is the resistance between each ter­minal of outdoor fan motor normal? (Refer to 10-4.)
No
Yes
Disconnect CN932 from the inverter P.C. board, and turn on the power supply.
Rotate the outdoor fan motor manually and measure the voltage of CN931. Between 1(+) and 5(-) Between 2(+) and 5(-) Between 3(+) and 5(-)
(Fixed to either 5 or 0 VDC)
Replace the outdoor fan motor.
Does the voltage between each terminal become 5 and 0
No
VDC repeatedly?
Yes
Does the outdoor fan motor rotate smoothly?
No
Replace the inverter P.C. board.
Yes
47
J Check of power supply
OBH747C
Disconnect the connector between the compressor and the power module (IPM) (MUZ-HM09/12NA(2)
HM09/12NA(2)
Turn ON power supply and press EMERGENCY OPERATION switch.
Does the upper lamp of the OPERATION INDICATOR lamp on the indoor unit light up?
-
U8
-
U1
)/(IC700) (
, MUZ-HM15/18/24NA(2)).
Yes
MUZ-
No
Rectify indoor/outdoor connecting wire.
No
Is there voltage 208/230 VAC between the indoor terminal block S1 and S2?
Replace the indoor electronic control P.C.
Yes
board.
Is there DC voltage 260 - 325 VDC
-
(MUZ-HM09/12NA(2) 370 VDC (
MUZ-HM09/12NA(2)
U8
)/260 -
-
U1
, MUZ-HM15/18/24NA(2)) between
DB61 (+) and DB61 (–) on the inverter P.C. board? (Refer to 10-6.1.)
No
Check the electric parts in main circuit.
260 - 325 VDC (MUZ-HM09/12NA(2) 260 - 370 VDC (MUZ-HM09/12NA(2)
DB61
Inverter P.C. board (Solder side)
Yes
Does LED on the inverter P.C. board light up or fl ash? (Refer to 10-6.1.)
Yes
If lights up, OK. If fl ashes, refer to 10-3.
-
U8
)
-
U1
, MUZ-HM15/18/24NA(2))
Replace the inverter
No
P.C. board.
48
K Check of LEV (Expansion valve)
OBH747C
Turn ON the power supply. <Preparation of the remote controller>
While pressing both OPERATION SELECT button and TOO COOL button on the remote controller at the same time, press RESET button. First, release RESET button.
Hold down the other 2 buttons for another 3 seconds.
Make sure that the indicators on the LCD screen shown in the right fi gure are all displayed. Then re- lease the buttons.
Press STOP/OPERATE (OFF/ON) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit. 1
Expansion valve operates in full-opening direction.
Do you hear the expansion valve "click, click·······"? Do you feel the expansion valve vibrate when touching it ?
No
Yes
OK
1. Regardless of normal or abnormal condition, a short beep is emitted once the signal is received.
Is LEV coil properly fi xed to the expansion valve?
Yes
Does the resistance of LEV coil have the characteristics? (Refer to 10-4.)
No
Replace the LEV coil.
NOTE: After check of LEV, do the undermentioned operations.
1. Turn OFF the power supply and turn it ON again.
2. Press RESET button on the remote controller.
No
Yes
Properly fi x the LEV coil to the expansion valve.
Measure each voltage between connector pins of CN724 on the inverter P.C. board.
1. Pin (-) — Pin (+)
2. Pin (-) — Pin (+)
3. Pin (-) — Pin (+)
4. Pin (-) — Pin (+) Is there about 3 - 5 VAC between each?
NOTE: Measure the voltage by an analog
tester.
Replace the expansion valve.
Yes
Replace the inverter P.C.
No
board.
49
L Check of inverter P.C. board
OBH747C
Check the outdoor fan motor. (Refer to 10-5.
.)
Is the fuse (F901) blown on the in­verter P.C. board?
No
Check the connection of the connectors (CN931, CN932) of the outdoor fan motor. If the connection is poor, make it correct.
Operate the outdoor unit by starting EMERGENCY OPERATION.
Check the LED indication on the in­verter P.C. board. Does the LED fl ash 10 times?
Yes (10-time fl ash)
Replace the inverter P.C. board.
Yes
No
Check the corresponding parts following LED indication. (Refer to 10-3.)
50
M How to check miswiring and serial signal error
OBH747C
MUZ-HM09/12NA(2)
Is the bus-bar voltage of the inverter P.C. board normal? (Refer to "TEST POINT DIAGRAM AND VOLTAGE" in the outdoor service manual.)
Turn OFF the power supply.
Is there rated voltage in the power supply?
Turn ON the power supply.
Is there rated voltage between outdoor terminal block S1 and S2?
Press EMERGENCY OPERATION switch once.
Does the OPERATION INDICATOR lamp light up? <Confi rmation of the power to the indoor unit>
Is serial signal error indicated 6 minutes later?
Turn OFF the power supply. Check once more if the indoor/outdoor
B
connecting wire is not miswiring. Bridge the outdoor terminal block S2 and
1
S3.
Turn ON the power supply.
Yes
Yes
Yes
Yes
A
Yes
No
No
No
1. Miswiring may damage indoor electronic control P.C.
3. Be sure to check this within 3 minutes after turning ON.
Check the power supply.
Is there any miswiring, poor contact, or wire disconnec­tion of the indoor/outdoor connecting wire?
board during the operation. Be sure to confi rm the wiring is correct before the opera- tion starts.
After 3 minutes, LED blinks 6 times. Even when the inverter P.C. board is normal, LED blinks 6 times after 3 minutes.
No
No
Check the wiring.
Correct them.
Yes
Check of power supply. (Refer to 10-5. .)
No
Does the LED on the inverter P.C. board repeat "3.6-second-OFF and 0.8-sec­ond-ON quick blinking"?
Turn OFF the power supply. Remove the bidge between the outdoor terminal block S2 and S3. Turn ON the power supply.
Is there rated voltage between the indoor terminal block S1 and S2? <Confi rmation of power voltage>
Is there amplitude of 10 to 20 VDC between the indoor terminal block S2 and S3? <Confi rmation of serial signal>
A
• Turn OFF inverter-controlled lighting equipment.
• Turn OFF the power supply and then turn ON again.
• Press EMERGENCY OPERATION switch.
• Reinstall either the unit or the light away from
Is serial signal error indicated 6 minutes later?
Yes
B
each other.
• Attach a fi lter
No
on remote control receiv­ing section of the indoor unit.
3
Yes
Yes
Yes
Is there 2 VDC or less between CN10A (+) and JPG (GND)(-) on the indoor electronic control P.C. board?
Yes
Is there 2 VDC or less between CN10A (+) and JPG (GND)(-) on the indoor electronic control P.C. board?
Replace the indoor power P.C. board and the indoor terminal P.C. board
No
No Yes No
No (Lighted or not lighted)
Check the wiring If there are any error of the indoor/outdoor connecting wire: such as the damage of the wire, intermediate connection,
No
and/or poor contact to the terminal block, replace the indoor/ outdoor connecting wire.
No
Replace the indoor elec­tronic control P.C. board.
Replace the inverter P.C. board. 2
2. Be careful of the residual voltage of smoothing capacitor.
Is there 2 VDC or less between CN10A (+) and JPG (GND)(-) on the indoor electronic control P.C. board?
Yes
51
MUZ-HM15/18/24NA(2)
OBH747C
Turn OFF the power supply.
NOTE: Refer to the indoor unit service manual.
Is there rated voltage in the power supply?
Turn ON the power supply.
Is there rated voltage between outdoor terminal block S1 and S2?
Press EMERGENCY OPERATION switch once.
Does the OPERATION INDICATOR lamp light up? <Confi rmation of the power to the indoor unit>
Is serial signal error indicated 6 minutes later?
Turn OFF the power supply. Check once more if the indoor/outdoor
B
connecting wire is not miswiring. Bridge the outdoor terminal block S2 and
1
S3.
Turn ON the power supply.
Is the bus-bar voltage of the inverter P.C. board normal? (Refer to "TEST POINT DIAGRAM AND VOLTAGE" in the outdoor service manual.)
Yes
Yes
Yes
Yes
A
Yes
No
No
No
1. Miswiring may damage indoor electronic control P.C.
3. Be sure to check this within 3 minutes after turning ON.
(Except for outdoor unit of multi system type)
Check the power supply.
Is there any miswiring, poor contact, or wire disconnection of the indoor/outdoor connect­ing wire?
board during the operation. Be sure to confi rm the wiring is correct before the opera- tion starts.
After 3 minutes, LED blinks 6 times. Even when the inverter P.C. board or the outdoor electronic control P.C. board is normal, LED blinks 6 times after 3 minutes.
No
No
Check the wiring.
Correct them.
Yes
No
Does the LED on the inverter P.C. board repeat "3.6-second-OFF and 0.8-sec­ond-ON quick blinking"?
Is there amplitude of 10 to 20 VDC between the indoor terminal block S2 and S3? <Confi rmation of serial signal>
A
• Turn OFF inverter-controlled lighting equipment.
• Turn OFF the power supply and then turn ON again.
• Press EMERGENCY OPERATION switch.
• Reinstall either the unit or the light away from
Is serial signal error indicated 6 minutes later?
Yes
B
each other.
• Attach a fi lter
No
on remote control receiv­ing section of the indoor unit.
3
Yes
Turn OFF the power supply. Remove the bridge between outdoor terminal block S2 and S3.
Turn on the power supply.
No
Yes
Is there 2 VDC or less between CN10A (+) and GND (-) on the indoor electronic control P.C. board?
Yes
Is there 2 VDC or less between CN10A the indoor electronic control P.C. board?
Replace the indoor power P.C. board.
No
(+) and GND (-) on
No Yes No
Replace the indoor elec­tronic control P.C. board.
52
No (Lighted or not lighted)
Replace the inverter P.C. board. 2
2. Be careful of the residual voltage of smoothing capacitor.
Is there 2 VDC or less between CN10A the indoor electronic control P.C. board?
(+) and GND (-) on
Yes
N Check of defrost heater
OBH747C
Check the following points before checking electric continuity.
1. Does the resistance of ambient temperature thermistor have the characteristics? Refer to 10-6.1.
2. Is the resistance of defrost heater normal? Refer to 10-4.
3. Does the heater protector remain conducted (not open)?
4. Are both ambient temperature thermistor and circuit of defrost heater securely connected to connectors? In HEAT mode, for more than 5 minutes, let the ambient temperature thermistor continue to read
32°F (0°C) or below, and let the defrost thermistor continue to read 30°F (-1°C) or below.
NOTE: In case both thermistors are more than the above temperature, cool them with cold
(Optional parts)
water etc...
Is there 208/230 VAC between CN722 and on the inverter P.C. board? Refer to 10-6.1.
No
Replace the inverter P.C. board.
O Check of outdoor refrigerant circuit
Has the operation stopped during pump down?
Yes
The operation has stopped to pre­vent the diesel explosion caused by air trapped in the refrigerant circuit. Close the stop valve, and disconnect the power plug or turn the breaker OFF.
No
Was the operation started with the stop valve closed, and was it opened during operation?
The refrigerant gas amount may be 60% or less than the normal amount. Identify where the gas is leaking from, and fi x the leak.
Yes
Not the problem of the inverter P.C. board.
(MUZ-HM09/12/15/18/24NA(2)
Yes
No
-
U1
)
The unit occasionally stops when the stop valve is opened or closed during operation. Open the stop valve and start the cooling operation again.
CAUTION : Do not start the opera-
tion again to prevent hazards.
53
P Electromagnetic noise enters into TV sets or radios
OBH747C
Is the unit grounded?
Yes
Is the distance between the antennas and the indoor unit within 9.91 ft. or is the distance between the antennas and the outdoor unit within 9.91 ft.
No
Is the distance between the TV sets or ra­dios and the indoor unit within 3.28 ft. or is the distance between the TV sets or radios and the outdoor unit within
9.91 ft.
(3m)
?
No
Are the antennas damaged? Is the coaxial cable damaged? Is there any poor contact in the anten­na wiring?
No
Is the indoor/outdoor connecting wire of the air conditioner and the wiring of the antennas close?
No
(3m)
(3m)
(1m)
No
,
Yes
?
,
Yes
Yes
Yes
Ground the unit.
Extend the distance between the antennas and the indoor unit, and/or the antennas and the outdoor unit.
Extend the distance between the TV sets and/or radios and the indoor unit, or the TV sets or radios and the outdoor unit.
Replace or repair the antenna. Replace or repair the coaxial cable.
Extend the distance between the indoor/outdoor connecting wire of the air conditioner and the wir­ing of the antennas.
Even if all of the above conditions are fulfi lled, the electromagnetic noise may enter, depending on the electric fi eld strength or the installation condition (combination of specifi c conditions such as antennas or wiring). Check the following before asking for service.
1. Devices affected by the electromagnetic noise TV sets, radios (FM/AM broadcast, shortwave)
2. Channel, frequency, broadcast station affected by the electromagnetic noise
3. Channel, frequency, broadcast station unaffected by the electromagnetic noise
4. Layout of: indoor/outdoor unit of the air conditioner, indoor/outdoor wiring, ground wire, antennas, wiring from antennas, receiver
5. Electric fi eld intensity of the broadcast station affected by the electromagnetic noise
6. Presence or absence of amplifi er such as booster
7. Operation condition of air conditioner when the electromagnetic noise enters in
1) Turn OFF the power supply once, and then turn ON the power supply. In this situation, check for the electromagnetic noise.
2) Within 3 minutes after turning ON the power supply, press STOP/OPERATE (OFF/ON) button on the remote controller for power ON, and check for the electromagnetic noise.
3) After a short time (3 minutes later after turning ON), the outdoor unit starts running. During operation, check for the electromagnetic noise.
4) Press STOP/OPERATE (OFF/ON) button on the remote controller for power OFF, when the outdoor unit stops but the indoor/outdoor communication still runs on. In this situation, check for the electromagnetic noise.
54
10-6. TEST POINT DIAGRAM AND VOLTAGE
-4 14 32 50 68 86 104
0
10
20
30
40
50
60
70
80
90
100
Temperature(°F)
Defrost thermistor(RT61) Ambient temperature thermistor(RT65) Outdoor heat exchanger temperature thermistor(RT68)
32 50 68 86 104 122 140 158 176
0
20
40
60
80
100
120
140
160
180
200
Temperature(°F)
Fin temperature thermistor(RT64)
5HVLVWDQFHN
5HVLVWDQFHN
Temperature (°F)
Discharge temperature thermistor (RT62)
5HVLVWDQFHN
0
100
200
300
400
500
600
700
800
32 50 68 86 104 122 140 158 176 194 212 230 248
OBH747C
1. Inverter P.C. board
U1
MUZ-HM09NA MUZ-HM09NA2
Back side of unit
208/230 VAC
Fuse (F901) T3.15AL250V
Output to drive outdoor fan motor (CN932)
Output to drive compressor (LDU, LDV, LDW)
-
MUZ-HM12NA
U1
-
MUZ-HM12NA2
DB61 260 - 370 VDC
-
(+)(-)
U1
U1
-
Smoothing capacitor (C62)
Smoothing capacitor (C61)
Fuse (F801) T3.15AL250V
R.V.coil (CN721) 208/230 VAC
Fuse (F701) T3.15AL250V
LED
Front side of unit
Fin temperature
thermistor/RT64
(CN642)
Signal of outdoor
fan motor (CN931)
Defrost thermistor
Ambient temperature
thermistor/RT65
/RT61(CN641)
(CN643)
55
Discharge temperature
thermistor/RT62
(CN641)
Outdoor heat exchanger
temperature thermistor
/RT68 (CN644)
LEV connector
(CN724)
208/230 VAC
Jumper wire for pre­heat control setting (JK)
Jumper wire for changing defrost setting (JS)
-4 14 32 50 68 86 104
0
10
20
30
40
50
60
70
80
90
100
Temperature(°F)
Defrost thermistor(RT61) Ambient temperature thermistor(RT65) Outdoor heat exchanger temperature thermistor(RT68)
32 50 68 86 104 122 140 158 176
0
20
40
60
80
100
120
140
160
180
200
Temperature(°F)
Fin temperature thermistor(RT64)
5HVLVWDQFHN
5HVLVWDQFHN
Temperature (°F)
Discharge temperature thermistor (RT62)
5HVLVWDQFHN
0
100
200
300
400
500
600
700
800
32 50 68 86 104 122 140 158 176 194 212 230 248
1. Inverter P.C. board
OBH747C
U8
MUZ-HM09NA MUZ-HM09NA2
-
-
MUZ-HM12NA
U8
MUZ-HM12NA2
U8
-
U8
-
Back side of unit
208/230 VAC
Fuse (F901) T3.15AL250V
Output to drive compressor (LDU, LDV, LDW)
Bus-bar voltage DB61 260-325 VDC
(-)
(+)
Smoothing capacitor (C63)
Smoothing capacitor (C62)
Fuse (F801) T3.15AL250V
Fuse (F701) T3.15AL250V
R.V.coil (CN721) 208/230 VAC
Signal of outdoor fan motor (CN931)
208/230 VAC
Front side of unit
Output to drive outdoor fan motor (CN932)
Fin temperature thermistor/RT64 (CN642)
Outdoor heat exchanger temperature thermistor /RT68 (CN644)
Discharge temperature thermistor/RT62 (CN641)
Defrost thermistor /RT61(CN641)
Ambient temperature thermistor/RT65 (CN643)
56
LEV
LED
connector (CN724)
Jumper wire for changing defrost setting (JS)
Jumper wire for pre-heat control setting (JK)
1. Inverter P.C. board
OBH747C
MUZ-HM15NA MUZ-HM18NA MUZ-HM15NA2 MUZ-HM18NA2
Back side of unit
208/230 VAC
Fuse (F901) T3.15AL250V
Output to drive outdoor fan motor (CN932)
Output to drive compressor (LDU, LDV, LDW)
DB61 260 - 370 VDC
Smoothing capacitor (C63)
Smoothing capacitor (C62)
(+)(-)
Fuse (F801) T3.15AL250V
Smoothing capacitor (C61)
R.V.coil (CN721) 208/230 VAC
Fuse (F701) T3.15AL250V
LED
Front side of unit
Fin temperature
thermistor/RT64
Defrost thermistor(RT61) Ambient temperature thermistor(RT65) Outdoor heat exchanger temperature thermistor(RT68)
100
90 80 70 60 50 40 30
5HVLVWDQFHN
20 10
0
-4 14 32 50 68 86 104 Temperature(°F)
(CN642)
Signal of outdoor
fan motor (CN931)
Defrost thermistor
Ambient temperature
thermistor/RT65
Discharge temperature thermistor (RT62)
800 700 600 500 400 300
5HVLVWDQFHN
200 100
0
32 50 68 86 104 122 140 158 176 194 212 230 248
/RT61(CN641)
(CN643)
Temperature (°F)
Discharge temperature
57
thermistor/RT62
(CN641)
Outdoor heat exchanger
temperature thermistor
/RT68 (CN644)
200 180 160 140 120 100
5HVLVWDQFHN
208/230 VAC
Jumper wire for pre­heat control setting (JK)
Jumper wire for changing defrost setting (JS)
LEV connector
(CN724)
Fin temperature thermistor(RT64)
80 60 40 20
0
32 50 68 86 104 122 140 158 176
Temperature(°F)
1. Inverter P.C. board
OBH747C
MUZ-HM24NA MUZ-HM24NA2
Back side of unit
208/230 VAC
Fuse (F901) T3.15AL250V
Output to drive outdoor fan motor (CN932)
Output to drive compressor (LDU, LDV, LDW)
Smoothing capacitor (C63)
DB61 260 - 370 VDC
(+)(-)
Smoothing capacitor (C62)
Fuse (F801) T3.15AL250V
Smoothing capacitor (C61)
R.V.coil (CN721) 208/230 VAC
Heater connector (CN722) (Optional parts)
Fuse (F701) T3.15AL250V
Front side of unit
Defrost thermistor(RT61) Ambient temperature thermistor(RT65) Outdoor heat exchanger temperature thermistor(RT68)
100
90 80 70 60 50 40 30
5HVLVWDQFHN
20 10
0
-4 14 32 50 68 86 104 Temperature(°F)
LED
Fin temperature
thermistor/RT64
(CN642)
Signal of outdoor
fan motor (CN931)
Discharge temperature thermistor (RT62)
800 700 600 500 400 300
5HVLVWDQFHN
200 100
0
32 50 68 86 104 122 140 158 176 194 212 230 248
Defrost thermistor
Ambient temperature
thermistor/RT65
/RT61(CN641)
(CN643)
Temperature (°F)
Discharge temperature
thermistor/RT62
58
(CN641)
Outdoor heat exchanger
temperature thermistor
/RT68 (CN644)
LEV connector
(CN724)
Fin temperature thermistor(RT64)
200 180 160 140 120 100
80 60
5HVLVWDQFHN
40 20
0
32 50 68 86 104 122 140 158 176
208/230 VAC
Jumper wire for pre­heat control setting (JK)
Jumper wire for changing defrost setting (JS)
Temperature(°F)
11
(1) Slide the sleeve and check if there is a locking lever or not. (2) The terminal with this connector has the
locking mechanism.
Slide the sleeve. Pull the terminal while pushing the locking lever.
Hold the sleeve, and pull out the terminal slowly.
Connector
Sleeve
Locking lever
OBH747C
DISASSEMBLY INSTRUCTIONS
<"Terminal with locking mechanism" Detaching points>
The terminal which has the locking mechanism can be detached as shown below. There are 2 types (refer to (1) and (2)) of the terminal with locking mechanism. The terminal without locking mechanism can be detached by pulling it out. Check the shape of the terminal before detaching.
11-1. MUZ-HM09NA MUZ-HM12NA MUZ-HM09NA2 MUZ-HM12NA MUZ-HM15NA MUZ-HM18NA MUZ-HM15NA2 MUZ-HM18NA2
NOTE: Turn OFF the power supply before disassembly.
OPERATING PROCEDURE PHOTOS
1. Removing the cabinet
(1) Remove the screw fixing the service panel. (2) Pull down the service panel and remove it. (3) Remove the screws fixing the conduit cover. (4) Remove the conduit cover. (Photo 4) (5) Remove the screw fixing the conduit plate. (Photo 5) (6) Remove the conduit plate. (7) Disconnect the power supply wire and indoor/outdoor
connecting wire. (8) Remove the screws fixing the top panel. (9) Remove the top panel. (
10
) Remove the screws fixing the cabinet.
(
11
) Remove the cabinet.
(
12
) Remove the screws fixing the back panel.
(
13
) Remove the back panel.
Photo 2
Screws of the top panel
Photo 1
Screws of the cabinet
Photo 3
Screws of the top panel
Screw of the cabinet
Back panel
Screws of the back panel
Service panel
Screws of the terminal block support and the back panel
Screws of the cabinet
Screws of the cabinet
59
Direction to remove
Hooks
OPERATING PROCEDURE PHOTOS
OBH747C
Photo 4 Photo 5
Screws of the conduit cover
Screw of the
conduit plate
2. Removing the inverter assembly, inverter P.C. board
(1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the lead wire to the reactor and the following
connectors:
<Inverter P.C. board>
CN721 (R.V. coil) CN931, CN932 (Fan motor) CN641 (Defrost thermistor and discharge temperature ther-
mistor) CN643 (Ambient temperature thermistor) CN644 (Outdoor heat exchanger temperature thermistor) CN724 (LEV)
(3) Remove the compressor connector (CN61). (4) Remove the screws fixing the heat sink support and the
separator.
(5) Remove the fixing screws of the terminal block support and
the back panel. (6) Remove the inverter assembly. (7) Remove the screw of the ground wire and screw of the ter-
minal block support. (8) Remove the heat sink support from the P.C. board support. (9) Remove the screw of the inverter P.C. board and remove the
inverter P.C. board from the P.C. board support.
3. Removing R.V. coil
(1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the following connectors: <Inverter P.C. board>
CN721 (R.V. coil)
(3) Remove the R.V. coil.
Photo 6
Screws of the heat sink support and the separator
Soundproof felt
Photo 7
Heat sink
Heat sink support
P.C. board support
Screws of the terminal block support and the back panel
Screw of the Terminal block support
60
Screw of the inverter P.C. board
Terminal block support
Screw of the ground wire
OPERATING PROCEDURE PHOTOS
OBH747C
4. Removing the discharge temperature thermistor, defrost thermistor, outdoor heat exchanger tempera­ture thermistor and ambient temperature thermistor
(1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the lead wire to the reactor and the following
connectors: <Inverter P.C. board>
CN641 (Defrost thermistor and discharge temperature ther-
mistor) CN643 (Ambient temperature thermistor) CN644 (Outdoor heat exchanger temperature thermistor)
(3)
Pull out the discharge temperature thermistor from its holder. (4) Pull out the defrost thermistor from its holder. (5) Pull out the outdoor heat exchanger temperature thermistor
from its holder.
(6) Pull out the ambient temperature thermistor from its holder.
Photo 8
Discharge temperature thermistor
Photo 9
Ambient temperature thermistor
Outdoor heat exchanger tempera­ture thermistor
Defrost thermistor
61
OPERATING PROCEDURE
OBH747C
5. Removing outdoor fan motor
(1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the following connectors: <Inverter P.C. board>
CN931, CN932 (Fan motor) (3) Remove the propeller fan nut. (4) Remove the propeller fan. (5) Remove the screws fixing the fan motor. (6) Remove the fan motor.
NOTE: The propeller fan nut is a revers thread.
PHOTOS
Photo 10
Screws of the outdoor fan motor
6. Removing the compressor and 4-way valve
(1) Remove the cabinet and panels. (Refer to 1.) (2) Remove the inverter assembly. (Refer to 2.) (3) Remove the screws fixing the reactor. (4) Remove the reactor. (5) Remove the soundproof felt. (6) Recover gas from the refrigerant circuit.
NOTE: Recover gas from the pipes until the pressure gauge
shows 0 PSIG.
(7) Detach the brazed part of the suction and the discharge pipe
connected with compressor. (8) Remove the nuts fixing the compressor. (9) Remove the compressor. (
10
) Detach the brazed part of pipes connected with 4-way valve.
Photo 12
Propeller fan
Photo 11
Discharge pipe brazed part
Propeller fan nut
Screws of the reactor
Suction pipe brazed part
Brazed parts of 4-way valve
Screw of the R.V. coil
62
11-2. MUZ-HM24NA MUZ-HM24NA2
OBH747C
OPERATING PROCEDURE PHOTOS
NOTE: Turn OFF the power supply before disassembly.
1. Removing the cabinet
(1) Remove the screws of the service panel. (2) Remove the screws of the top panel. (3) Remove the screw of the valve cover. (4) Remove the service panel. (5) Remove the screws fixing the conduit cover. (6) Remove the conduit cover. (7) Remove the screw of fixing the conduit plate. (8) Remove the conduit plate. (9) Remove the top panel. (10)
Remove the valve cover.
(11)
Disconnect the power supply and indoor/outdoor connect-
ing wire.
(12)
Remove the screws of the cabinet.
(13)
Remove the cabinet.
(14)
Remove the screws of the back panel.
(15)
Remove the back panel.
Photo 3
Screws of the conduit cover
Photo 1
Screws of the cabinet
Screws of the cabinet
Photo 2
Screws of the top panel
Screw of the valve cover
Screw of the back panel
Screws of the top panel
Screws of the cabinet
Screws of the cabinet
Photo 4
Screw of the conduit plate
63
Screws of the cabinet
Screws of the back panel
Screws of the service panel
OPERATING PROCEDURE
OBH747C
PHOTOS
2. Removing the inverter assembly, inverter P.C. board
(1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the lead wire to the reactor and the following con-
nectors:
<Inverter P.C. board> CN721 (R.V. coil) CN931, CN932 (Fan motor) CN641 (Defrost thermistor and discharge temperature ther-
mistor) CN643 (Ambient temperature thermistor) CN644 (Outdoor heat exchanger temperature thermistor) CN724 (LEV)
(3) Remove the compressor connector. (4) Remove the screw fixing the heat sink support and the sepa-
rator.
(5) Remove the fixing screws of the terminal block support and
the back panel. (6) Remove the inverter assembly. (7) Remove the screw of the ground wire, screw of the P.C.
board cover and screws of the terminal block support. (8) Remove the heat sink support from the P.C. board support. (9) Remove the screw of the inverter P.C. board and the inverter
P.C. board from the P.C. board support.
3. Removing R.V. coil
(1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the following connector: <Inverter P.C. board>
CN721 (R.V. coil)
(3) Remove the R.V. coil.
Photo 7
Screw of the R.V. coil
Photo 5
Screw of the heat sink support and the separator
Photo 6
Heat sink
P.C. board support
Screw of the inverter P.C. board
Screw of the ground wire
Screws of the terminal block support and the back panel
Heat sink support
Screw of the P.C. board cover
Screws of the terminal block support
Brazed parts of 4-way valve
64
OPERATING PROCEDURE PHOTOS
OBH747C
4. Removing the discharge temperature thermistor, defrost thermistor, outdoor heat exchanger tempera­ture thermistor and ambient temperature thermistor
(1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the lead wire to the reactor and the following
connectors: <Inverter P.C. board>
CN641 (Defrost thermistor and discharge temperature ther-
mistor) CN643 (Ambient temperature thermistor) CN644 (Outdoor heat exchanger temperature thermistor)
(3)
Pull out the discharge temperature thermistor from its holder. (4) Pull out the defrost thermistor from its holder. (5) Pull out the outdoor heat exchanger temperature thermistor
from its holder.
(6) Pull out the ambient temperature thermistor from its holder.
5. Removing outdoor fan motor
(1)
Remove the top panel, cabinet and service panel. (Refer to 1.)
(2) Disconnect the following connectors:
<Inverter P.C. board>
CN931 and CN932 (Fan motor) (3) Remove the propeller fan nut. (4) Remove the propeller fan. (5) Remove the screws fixing the fan motor. (6) Remove the fan motor.
NOTE: The propeller fan nut is a reverse thread.
Photo 8
Photo 9
Outdoor heat exchanger tempera­ture thermistor
Defrost thermistor
Propeller fan nut
Ambient tem-
perature
thermistor
6. Removing the compressor and 4-way valve
(1)
Remove the top panel, cabinet and service panel. (Refer to 1.) (2) Remove the back panel. (Refer to 1.) (3) Remove the inverter assembly. (Refer to 2.) (4) Recover gas from the refrigerant circuit.
NOTE: Recover gas from the pipes until the pressure gauge
shows 0 PSIG.
(5) Detach the brazed part of the suction and the discharge
pipe connected with compressor. (6) Remove the compressor nuts. (7) Remove the compressor. (8) Detach the brazed part of 4-way valve and pipe. (Photo 7)
65
Photo 10
Brazed part of the discharge pipe
Screws of the outdoor fan motor
Discharge temperature thermistor
Brazed part of the suction pipe
HEAD OFFICE: TOKYO BUILDING, 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
© Copyright 2015 MITSUBISHI ELECTRIC CORPORATION
Issued: Feb. 2017. No. OBH747 REVISED EDITION-C Issued: Mar. 2016. No. OBH747 REVISED EDITION-B Issued: Feb. 2016. No. OBH747 REVISED EDITION-A Published: Dec. 2015. No. OBH747 Made in Japan
Specifications are subject to change without notice.
Loading...