RoHS compliant products have <G> mark on the spec name plate.
Use the specifi ed refrigerant only
OBH747C
Never use any refrigerant other than that specified.
Doing so may cause a burst, an explosion, or fire when the unit is being used, serviced, or disposed of.
Correct refrigerant is specified in the manuals and on the spec labels provided with our products.
We will not be held responsible for mechanical failure, system malfunction, unit breakdown or accidents caused by
failure to follow the instructions.
Revision A:
• MUZ-HM09/12NA-U8, MUZ-HM09/12NA2-U8, MUZ-HM15/18NA-U1, MUZ-HM15/18NA2-U1 and MUZ-HM24NA2-U1 have
been added.
Indoor air condition (°F)Outdoor air condition (°F)
Dry bulbWet bulbDry bulb Wet bulb
806795(75)
806782(65)
806782(65)
806767(53.5)
806787(69)
70604743
70601715
70606256.5
70604743
70603533
OPERATING RANGE
(1) POWER SUPPLY
Outdoor unit
(2) OPERATION
ModeCondition
Standard temperature806795—
Cooling
Heating
Maximum temperature9073115—
Minimum temperature675714—
Maximum humidity78 %—
Standard temperature70604743
Maximum temperature80677565
Minimum temperature7060-4 (NA), 5(NA2)-5 (NA), 4 (NA2)
2. Above data is for heating operation without any frost.
How to operate with fixed operational frequency of the compressor.
1. Press the EMERGENCY OPERATION switch on the front of the indoor unit, and select either EMERGENCY COOL
mode or EMERGENCY HEAT mode before starting to operate the air conditioner.
2. The compressor starts with operational frequency.
3. The fan speed of the indoor unit is High.
4. This operation continues for 30 minutes.
5. In order to release this operation, press the EMERGENCY OPERATION switch or press any button on the remote controller.
This value of frequency is not the same as the actual frequency in operating. Refer to 7-5 and 7-6 for the relationships
between frequency and capacity.
Indoor intake air WB temperature (°F)
Outdoor intake air DB temperature (°F)
Airflow
= 533 CFM
= 702 CFM
MUZ-HM18NA MUZ-HM18NA2
SHF at rating condition = 0.86
71
67
63
2.0
1.8
1.6
(kW)
1.4
1.2
Total power consumption
65758595105115
Indoor intake air WB temperature (°F)
Outdoor intake air DB temperature (°F)
71
67
63
21
Airflow
= 625 CFM
71
67
63
Heating
p
)
OBH747C
Heating capacity (
1.3
1.2
1.1
1.0
0.9
0.8
0.7
difference (°F)
0.6
0.5
Capacity correction factor
Indoor air Dry-bulb temperature
0.4
-4 5 142332415059
Outdoor intake air WB temperature (°F)
Indoor intake air Dry-bulb temperature ( F)
at Rated frequency)
59
68
79
MUZ-HM09NA MUZ-HM09NA2MUZ-HM12NA MUZ-HM12NA2
= 406 CFM
1.1
0.9
0.7
(kW)
0.5
Total power consumption
0.3
0 10203040506070
Indoor intake air DB temperature (°F)
Outdoor intake air WB temperature (°F)
Airflow
75
70
65
1.2
1.1
1.0
0.9
0.8
(kW)
0.7
0.6
0.5
Total power consumption
0.4
0 10203040506070
Indoor intake air DB temperature (°F)
Outdoor intake air WB temperature (°F)
Airflow
= 406 CFM
MUZ-HM15NA MUZ-HM15NA2MUZ-HM18NA MUZ-HM18NA2
2.0
1.7
1.4
(kW)
1.1
0.8
Total power consumption
0.5
-5 5 1525354555
Indoor intake air DB temperature (°F)
Outdoor intake air WB temperature (°F)
Airflow
= 463 CFM
75
70
65
65
2.0
1.7
1.4
(kW)
1.1
0.8
Total power consumption
0.5
-5 5 1525354555
Indoor intake air DB temperature (°F)
Outdoor intake air WB temperature (°F)
Airflow
= 625 CFM
MUZ-HM24NA MUZ-HM24NA2
= 702 CFM
3.2
2.9
2.6
2.3
2.0
(kW)
1.7
1.4
1.1
Total power consumption
0.8
-5 5 1525354555
Indoor intake air DB temperature (°F)
Outdoor intake air WB tem
This value of frequency is not the same as the actual frequency in operating. Refer to 7-5 and 7-6 for the relationships
between frequency and capacity.
Airflow
erature (°F
75
70
65
65
75
70
65
75
70
65
65
22
7-3. CONDENSING PRESSURE
(PSIG)
687075808590
95
100 105
(°F)
260
300
340
380
420
(PSIG)
687075808590
95
100 105
(°F)
110
130
150
170
190
Condensing pressure
86
80
75
70
Suction pressure
Indoor DB temperature (°F)
Outdoor ambient temperature
86
80
75
70
Indoor DB temperature (°F)
Outdoor ambient temperature
4
86
807570
Indoor DB temperature (°F)
e
OBH747C
Cooling
Data are based on the condition of indoor humidity 50 %.
Air flow should be set to High speed.
MUZ-HM09NA MUZ-HM09NA2
440
400
360
86
80
75
70
(PSIG)(PSIG)
200
180
160
Indoor DB temperature (°F)
86
80
75
70
Condensing pressure
320
280
687075808590
MUZ-HM12NA
500
445
390
335
280
707580859095100105
MUZ-HM12NA
Indoor DB temperature (°F)
Outdoor ambient temperature
U1
-
MUZ-HM12NA2
Outdoor ambient temperature
U8
-
MUZ-HM12NA2
95
100 105
U1
-
U8
-
(°F)
Suction pressure
140
120
68707580859095100 105
(PSIG)(PSIG)
180
160
140
Suction pressure
120
100
Outdoor ambient temperature
Indoor DB temperature (°F)
707580859095100105
Outdoor ambient temperature
(°F)
86
80
75
70
23
707580859095100105
270
310
350
390
430
470
510
(°F)(°F)
707580859095100105
90
105
120
135
150
165
180
(PSIG)
Condensing pressure
Suction pressure
Outdoor ambient temperature
Indoor DB temperature (°F)
(PSIG)
Indoor DB temperature (°F)
Outdoor ambient temperature
86
80
75
70
86
80
75
70
65707580859095100 105
250
300
350
400
450
500
550
(°F)(°F)
65707580859095100105
80
100
120
140
160
180
200
(PSIG)
Condensing pressure
Suction pressure
Outdoor ambient temperature
Indoor DB temperature (°F)
(PSIG)
Indoor DB temperature (°F)
Outdoor ambient temperature
86
80
75
70
86
80
75
70
65707580859095100 105
200
250
300
350
400
450
500
(°F)(°F)
65707580859095100105
60
80
100
120
140
160
180
(PSIG)
Condensing pressure
Suction pressure
Outdoor ambient temperature
Indoor DB temperature (°F)
(PSIG)
Indoor DB temperature (°F)
Outdoor ambient temperature
86
80
75
70
86
80
75
70
MUZ-HM15NA MUZ-HM15NA2
OBH747C
MUZ-HM18NA MUZ-HM18NA2
MUZ-HM24NA MUZ-HM24NA2
Heating
Data are based on the condition of outdoor humidity 75%.
Air flow should be set to High speed.
Data are for heating operation without any frost.
The fan motor turns ON/OFF, interlocking with the compressor.
[ON] The fan motor turns ON 5 seconds before the compressor starts up.
[OFF] The fan motor turns OFF 15 seconds after the compressor has stopped running.
5 seconds15 seconds
ON
Compressor
OFF
ON
Outdoor fan
motor
OFF
8-2. R.V. COIL CONTROL
Heating
Cooling
Dry
NOTE: The 4-way valve reverses for 5 seconds right before start-up of the compressor.
8-3. RELATION BETWEEN MAIN SENSOR AND ACTUATOR
Discharge temperature
thermistor
Indoor coil temperature
thermistor
Defrost thermistorHeating: Defrosting
Fin temperature thermistorProtection
When moisture gets into the refrigerant cycle, it may interfere with the start-up of the compressor at low outside temperature. The pre-heat control prevents this interference. The pre-heat control turns ON when the discharge temperature thermistor is 68°F (20°C) or below. When the pre-heat control turns ON, the compressor is energized. (About 50 W)
Pre-heat control setting
<JK>
ON: To activate the pre-heat control, cut JK wire of the inverter P.C. board.
OFF: To deactivate the pre-heat control, solder JK wire of the inverter P.C. board.
(Refer to 10-6.1)
Defrost fi nish temperature
U8
-
MUZ-HM12
-
U8
MUZ-HM15/18MUZ-HM24
JumperPre-heat control setting
Soldered
JK
CutActivated
NOTE: When the inverter P.C. board is replaced, check the jumper wires, and cut/solder them if necessary.
2) Check the indoor/outdoor connecting wire for miswiring.
2. Take care of the following during servicing
1) Before servicing the air conditioner, be sure to turn OFF the main unit first with the remote controller, then after confirming the horizontal vane is closed, turn off the breaker and/or disconnect the power plug.
2) Be sure to turn OFF the power supply before removing the front panel, the cabinet, the top panel, and the electronic
control P.C. board.
3) When removing the electrical parts, be careful of the residual voltage of smoothing capacitor.
4) When removing the electronic control P.C. board, hold the edge of the board with care NOT to apply stress on the
components.
5) When connecting or disconnecting the connectors, hold the connector housing. DO NOT pull the lead wires.
3. Troubleshooting procedure
1)
Check if the OPERATION INDICATOR lamp on the indoor unit is flashing on and off to indicate an abnormality. To make
sure, check how many times the OPERATION INDICATOR lamp is flashing on and off before starting service work. (See
the service manual of the indoor unit for a description of those failure codes.)
2) Before servicing, check that the connector and terminal are connected properly.
3) When the electronic control P.C. board seems to be defective, check the copper foil pattern for disconnection and the
components for bursting and discoloration.
4) Refer to 10-2 and 10-3.
34
10-2. FAILURE MODE RECALL FUNCTION
OBH747C
Outline of the function
This air conditioner can memorize the abnormal condition which has occurred once.
Even though LED indication listed on the troubleshooting check table (10-3.) disappears, the memorized failure details can be recalled.
1. Flow chart of failure mode recall function
for the indoor/outdoor unit
Operational procedure
Setting up the failure mode recall function
Judgment of indoor/outdoor abnormality
The cause of abnormality cannot be found because the abnormality does not recur.
Turn ON the power supply.
<Preparation of the remote controller>
While pressing OPERATION SELECT button and TOO COOL button on the remote
controller at the same time, press RESET button.
First, release RESET button.
Hold down the other 2 buttons for another 3 seconds. Make sure that the indicators on
the LCD screen shown in the right fi gure are all displayed. Then release the buttons.
Press STOP/OPERATE (OFF/ON) button of the remote controller (the set temperature
is displayed) with the remote controller headed towards the indoor unit.
Does the upper lamp of the OPERATION INDICATOR lamp on
the indoor unit blink at the interval of 0.5 seconds?
Blinks: Either indoor or outdoor unit is abnormal. Beep is
emitted at the same timing as the blinking of the upper
lamp of the OPERATION INDICATOR lamp.
Before blinking, does the upper lamp of the OPERATION
INDICATOR lamp stay ON for 3 seconds?
When it stays ON for 3 seconds (without beep): The outdoor unit
The indoor unit is abnormal.
Check the blinking pattern, and identify the abnormal point by referring to the table
of indoor unit failure mode recall function. (Refer to indoor unit service manual.)
Make sure to check at least 2 consecutive blinking cycles.
1
1. Regardless of normal or abnormal condition,
a short beep is emitted once the signal is
received.
No
(OFF)
Yes
(Blinks)
No
2
is abnormal.
2
Indoor unit is normal.
But the outdoor unit might be abnormal because there are some abnormalities that cannot be recalled with this way.
Check if outdoor unit is abnormal according to the detailed outdoor unit
failure mode recall function. (Refer to 10-2.2)
Yes
The outdoor unit is abnormal.
Check the blinking pattern, and identify the abnormal point by referring
to the outdoor unit failure recall mode table. (Refer to 10-2.3)
Make sure to check at least 2 consecutive blinking cycles.
3
Releasing the failure mode recall function
Deleting the memorized abnormal condition
Release the failure mode recall function by the following procedures.
Turn OFF the power supply and turn it ON again.
Press RESET button of the remote controller.
Repair the failure parts.
After repairing the unit, recall the failure mode again according to "Setting up the failure mode recall
function" mentioned above.
Press STOP/OPERATE (OFF/ON) button of the remote controller (the set temperature is displayed)
with the remote controller headed towards the indoor unit.
Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted.
Release the failure mode recall function according to "Releasing the failure mode recall function"
mentioned above.
NOTE: 1. Make sure to release the failure mode recall function after it is set up, otherwise the unit cannot operate properly.
2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.
2. Blinking pattern when the indoor unit is abnormal:
2.5-second OFF
Blinking at 0.5second interval
2.5-second OFF
Blinking at 0.5-
second interval
ON
OFF
Repeated cycleRepeated cycle
Beeps
3.Blinking pattern when the outdoor unit is abnormal:
2.5-second OFF3-second ON
Blinking at 0.5second interval
Beeps
Repeated cycle
2.5-second OFF3-second ON
ON
OFF
No beepBeeps
Repeated cycle
No beepBeeps
Repeated cycle
35
Beeps
Blinking at 0.5second interval
Repeated cycle
2. Flow chart of the detailed outdoor unit failure mode recall function
OBH747C
Operational procedure
The outdoor unit might be abnormal.
Check if outdoor unit is abnormal according to the following procedures.
Make sure that the remote controller is set to the failure mode recall function.
With the remote controller headed towards the indoor unit, press TOO
COOL button to adjust the set temperature to 77°F (25°C).
Does the upper lamp of the OPERATION INDICATOR
lamp on the indoor unit blink at the interval of 0.5 seconds?
Blinks: The outdoor unit is abnormal. Beep is emitted at
the same timing as the blinking of the upper lamp
of the OPERATION INDICATOR lamp.
Yes
(Blinks
The outdoor unit is abnormal.
Check the blinking pattern, and identify the abnormal point by referring to
the table of outdoor unit failure mode recall function (10-2.3.).
Make sure to check at least 2 consecutive blinking cycles.
Releasing the failure mode recall function
Release the failure mode recall function by the following procedures.
Turn OFF the power supply and turn it ON again.
Press RESET button of the remote controller.
Repair the failure parts.
Deleting the memorized abnormal condition
After repairing the unit, recall the failure mode again according to "Setting up the failure mode recall
function" (10-2.1.).
Press STOP/OPERATE (OFF/ON) button of the remote controller (the set temperature is displayed) with
the remote controller headed towards the indoor unit.
Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted.
Release the failure mode recall function according to "Releasing the failure mode recall function" men-
tioned above.
NOTE: 1. Make sure to release the failure mode recall function after it is set up, otherwise the unit cannot operate properly.
2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.
)
1
No
2
(OFF)
2
1. Regardless of normal or abnormal condition, 2 short
beeps are emitted as the signal is received.
The outdoor unit is normal.
Release the failure mode recall function according to the left mentioned procedure.
2.Blinking pattern when outdoor unit is abnormal:
2.5-second OFF3-second ON
ON
OFF
No beep
Repeated cycle
Blinking at 0.5second interval
Beeps
2.5-second OFF3-second ON
No beepBeeps
Repeated cycle
36
Blinking at 0.5second interval
Repeated cycle
3. Table of outdoor unit failure mode recall function
OBH747C
NOTE: Blinking patterns of this mode differ from the ones of
TROUBLESHOOTING CHECK TABLE (10-3.).
MUZ-HM09NA MUZ-HM09NA2 MUZ-HM12NA MUZ-HM12NA2
OPERATION
INDICATOR
upper lamp
(Indoor unit)
OFF None (Normal) —————
2-time fl ash
2.5 seconds
OFF
3-time fl ash
2.5 seconds
OFF
4-time fl ash
2.5 seconds
OFF
5-time fl ash
2.5 seconds
OFF
6-time fl ash
2.5 seconds
OFF
7-time fl ash
2.5 seconds
OFF
8-time fl ash
2.5 seconds
OFF
9-time fl ash
2.5 seconds
OFF
10-time fl ash
2.5 seconds
OFF
Abnormal point
(Failure mode / protection)
Outdoor power system
Discharge temperature
thermistor
Defrost thermistor
Fin temperature thermistor 3-time fl ash
Overcurrent protection cut-out operates
3 consecutive times within 1 minute
after the compressor gets started.
Thermistor shorts or opens during
compressor running.
Large current fl ows into intelligent
power module/ power module
Waveform of compressor current is
distorted.
Temperature of discharge temperature
thermistor exceeds 241°F (116°C),
compressor stops.
Compressor can restart if discharge
temperature thermistor reads 212°F
(100°C) or less 3 minutes later.
Temperature of indoor coil thermistor
exceeds 158°F (70°C) in HEAT mode.
Temperature of outdoor heat exchanger
temperature thermistor exceeds 158°F
(70°C) in COOL mode.
Temperature of fi n temperature
thermistor on the inverter P.C. board
exceeds 167 - 176°F (75 - 80°C), or
temperature of P.C. board temperature
thermistor on the inverter P.C. board
exceeds 158 - 167°F (70 - 75°C).
Outdoor fan has stopped 3 times in a
row within 30 seconds after outdoor fan
start-up.
Nonvolatile memory data cannot be
read properly.
Temperature of discharge temperature
thermistor has been 122°F (50°C) or
less for 20 minutes.
1.
Reconnect connectors.
•
Refer to 10-5.
•
to check inverter/
compressor".
Check the stop valve.
•
Refer to 10-5. "Check
•
of outdoor thermistors".
Defective outdoor
thermistors can be
identifi ed by checking
the blinking pattern of
LED.
Reconnect compressor
•
connector.
Refer to 10-5.
•
to check inverter/
compressor".
Check the stop valve.
•
Reconnect compressor
•
connector.
Refer to 10-5.
•
to check inverter/
compressor".
Check the refrigerant
•
circuit and the
refrigerant amount.
Refer to 10-5.
•
of LEV".
Check the refrigerant
•
circuit and the
refrigerant amount.
Check the stop valve.
•
Check around the
•
outdoor unit.
Check the outdoor unit
•
air passage.
Refer to 10-5.
•
of outdoor fan motor".
Refer to 10-5. "Check
•
of outdoor fan motor".
Refer to 10-5.
of inverter P.C. board".
Replace the inverter
•
P.C. board.
Refer to 10-5. "Check
•
of LEV".
Check the refrigerant
•
circuit and the
refrigerant amount.
"How
"How
"How
"Check
"Check
"Check
Indoor/
outdoor unit
failure mode
recall function
Outdoor unit
failure mode
recall function
○○
○○
—
—
—
—
—
—
○○
—
○
○
○
○
○
○
○
37
OPERATION
OBH747C
INDICATOR
upper lamp
(Indoor unit)
11-time fl ash
2.5 seconds
OFF
12-time fl ash
2.5 seconds
OFF
14-time fl ash
2.5 seconds
OFF
Abnormal point
(Failure mode / protection)
DC voltage 8-time fl ash
Each phase current of
compressor
Overcurrent Compressor open-
phase
Stop valve (Closed valve) 14-time fl ash
4-way valve/
Pipe temperature
Outdoor refrigerant
system abnormality (MUZ-
HM09/12NA(2)
U1
-
)
LED indication
(Outdoor P.C. board)
2.5 seconds OFF
9-time fl ash
2.5 seconds OFF
10-time fl ash
2.5 seconds OFF
2.5 seconds OFF
16-time fl ash
2.5 seconds OFF
1-time fl ash
2.5 seconds OFF
NOTE: Blinking patterns of this mode differ from the ones of
TROUBLESHOOTING CHECK TABLE (10-3.).
Condition Remedy
DC voltage of inverter cannot be
detected normally.
Each phase current of compressor
cannot be detected normally.
Large current fl ows into intelligent
power module (IPM)/power module
1.
(IPM)
The open-phase operation of
compressor is detected.
The interphase short circuit occurs
in the output of the intelligent power
module (IPM)/power module (IPM)
The compressor winding shorts circuit.
Closed valve is detected by compressor
current.
The 4-way valve does not work
properly.
The indoor coil thermistor detects an
abnormal temperature.
A closed valve and air trapped in the
refrigerant circuit are detected based on
the temperature sensed by the indoor
and outdoor thermistors and the current
of the compressor.
1.
Refer to 10-5.
•
to check inverter/
compressor".
Reconnect compressor
•
connector.
Refer to 10-5.
•
to check inverter/
compressor".
Check the stop valve
•
Check the 4-way valve.
•
Replace the inverter
•
P.C. board.
Check for a gas leak
•
in a connecting piping
etc.
Check the stop valve.
•
Refer to 10-5.
•
“Check of outdoor
refrigerant circuit”.
"How
"How
Indoor/
outdoor unit
failure mode
recall function
—
—
Outdoor unit
failure mode
recall function
○
○
○○
○○
38
MUZ-HM15NA MUZ-HM15NA2
OBH747C
MUZ-HM18NA MUZ-HM18NA2
MUZ-HM24NA MUZ-HM24NA2
The upper
lamp of the
OPERATION
INDICATOR
lamp
(Indoor unit)
OFF None (Normal) —————
1-time fl ash
2.5 seconds
OFF
2-time fl ash
2.5 seconds
OFF
3-time fl ash
2.5 seconds
OFF
4-time fl ash
2.5 seconds
OFF
5-time fl ash
2.5 seconds
OFF
6-time fl ash
2.5 seconds
OFF
7-time fl ash
2.5 seconds
OFF
8-time fl ash
2.5 seconds
OFF
9-time fl ash
2.5 seconds
OFF
Abnormal point
(Failure mode/protection)
Indoor/outdoor communication,
receiving error
Indoor/outdoor communication,
receiving error
Outdoor power system
Discharge temperature
thermistor
Defrost thermistor
Fin temperature thermistor 3-time fl ash
Nonvolatile memory data 5-time fl ash
Power module (IPM) (MUZ-
HM09/12NA(2)
(MUZ-HM09/12/15/18/24NA(2)
U1
-
)
-
U8
)/(IC700)
LED indication
(Outdoor P.C. board)
—
—
—
1-time fl ash every
2.5 seconds
2.5 seconds OFF
4-time fl ash
2.5 seconds OFF
2-time fl ash
2.5 seconds OFF
—
2.5 seconds OFF
12-time fl ash
2.5 seconds OFF
—
—
7-time fl ash
2.5 seconds OFF
—
2.5 seconds OFF
6-time fl ash
2.5 seconds OFF
Any signals from the inverter P.C.
board cannot be received normally for
3 minutes.
Although the inverter P.C. board
sends signal "0", signal "1" has been
received 30 consecutive times.
Overcurrent protection cut-out
operates 3 consecutive times within
1 minute after the compressor gets
started.
Thermistor shorts or opens during
compressor running.
Large current fl ows into the
power module (IPM) (MUZ-
HM09/12NA(2)
HM09/12/15/18/24NA(2)
Waveform of compressor current is
distorted.
Temperature of discharge temperature
thermistor exceeds 241°F (116°C),
compressor stops.
Compressor can restart if discharge
temperature thermistor reads
212°F (100°C) or less 3 minutes later.
Temperature indoor coil thermistor
exceeds 158°F (70°C) in HEAT
mode. Temperature defrost thermistor
exceeds 158°F (70°C) in COOL mode.
Temperature of the fi n temperature
thermistor on the inverter P.C. board
exceeds 167 - 187°F (75 - 86°C), or
temperature of P.C. board temperature
thermistor on the inverter P.C. board
exceeds 162 - 185°F (72 - 85°C).
Outdoor fan has stopped 3 times in a
row within 30 seconds after outdoor
fan start-up.
Nonvolatile memory data cannot be
read properly.
The interface short circuit occurs in
the output of the power module (IPM)
(MUZ-HM09/12NA(2)
(MUZ-HM09/12/15/18/24NA(2)
The compressor winding shorts circuit.
NOTE: Blinking patterns of this mode differ from the ones of
TROUBLESHOOTING CHECK TABLE (10-3.).
Indoor/outdoor
Condition Remedy
How
How
"How
"How
"How
"Check
"Check
"Check
"How
U8
-
)/(IC700) (MUZ-
-
U1
-
U8
)/(IC700)
•Refer to 10-5.
to check miswiring and
serial signal error.
•Refer to 10-5.
to check miswiring and
serial signal error.
Reconnect
•
connectors.
Refer to 10-5.
•
to check inverter/
compressor".
Check stop valve.
•
Refer to 10-5.
•
"Check of outdoor
thermistors".
Defective outdoor
thermistors can be
identifi ed by checking
the blinking pattern of
LED.
Reconnect
•
compressor connector.
Refer to 10-5.
•
).
to check inverter/
compressor".
Check stop valve.
•
Reconnect
•
compressor connector.
Refer to 10-5.
•
to check inverter/
compressor".
Check refrigerant
•
circuit and refrigerant
amount.
Refer to 10-5.
•
of LEV".
Check refrigerant
•
circuit and refrigerant
amount.
Check stop valve.
•
Check around outdoor
•
unit.
Check outdoor unit air
•
passage.
Refer to 10-5.
•
of outdoor fan motor".
Refer to 10-5. "Check
•
of outdoor fan motor".
Refer to 10-5.
of inverter P.C. board".
Replace the inverter
•
P.C. board.
Refer to 10-5.
•
to check inverter/
compressor".
U1
-
).
unit failure
mode recall
function
○○
○○
○○
—
—
—
—
—
—
○○
Outdoor unit
failure mode
recall function
○
○
○
○
○
○
39
The upper
OBH747C
lamp of the
OPERATION
INDICATOR
lamp
(Indoor unit)
10-time fl ash
2.5 seconds
OFF
11-time fl ash
2.5 seconds
OFF
14-time fl ash
or more
2.5 seconds
OFF
Abnormal point
(Failure mode/protection)
Discharge temperature
DC voltage8-time fl ash
Each phase current of
compressor
Stop valve (Closed valve) 14-time fl ash
4-way valve/
Pipe temperature
Outdoor refrigerant system
abnormality
LED indication
(Outdoor P.C. board)
—
2.5 seconds OFF
9-time fl ash
2.5 seconds OFF
2.5 seconds OFF
16-time fl ash
2.5 seconds OFF
1-time fl ash
2.5 seconds OFF
NOTE: Blinking patterns of this mode differ from the ones of
TROUBLESHOOTING CHECK TABLE (10-3.).
Condition Remedy
Temperature of discharge temperature
thermistor has been 122°F (50°C) or
less for 20 minutes.
DC voltage of inverter cannot be
detected normally.
Each phase current of compressor
cannot be detected normally.
Closed valve is detected by
compressor current.
The 4-way valve does not work
properly.
The indoor coil thermistor detects an
abnormal temperature.
A closed valve and air trapped in the
refrigerant circuit are detected based
on the temperature sensed by the
indoor and outdoor thermistors and the
current of the compressor.
Refer to 10-5.
•
of LEV".
Check refrigerant
•
circuit and refrigerant
amount.
Refer to 10-5. "How
•
to check inverter/
compressor".
Check stop valve.
•
Check the 4-way
•
valve.
Replace the inverter
•
P.C. board.
Check for a gas leak
•
in a connecting piping
etc.
Check the stop valve.
•
Refer to 10-5.
•
“Check of outdoor
refrigerant circuit”.
"Check
Indoor/outdoor
unit failure
mode recall
function
—
—
Outdoor unit
failure mode
recall function
○
○
○○
○○
40
10-3. TROUBLESHOOTING CHECK TABLE
OBH747C
No. Symptom LED indication
Outdoor unit
does not operate.
1
2
3
4
5
6
7
'Outdoor unit
stops and
restarts 3
8
minutes later'
is repeated.
9
10
11
12
13
14
15
NOTE: 1. The location of LED is illustrated at the right fi gure. Refer to 10-6.1.
2. LED is lighted during normal operation.
3. Blinking patterns of this mode differ from the ones of the failure recall mode.
The fl ashing frequency shows the number of times the LED blinks after every 2.5-second OFF.
(Example) When the fl ashing frequency is “2”.
ON
2.5-second OFF
OFF
1-time fl ash every
2.5 seconds
6-time fl ash
2.5 seconds OFF
11-time fl ash
2.5 seconds OFF
16-time fl ash
2.5 seconds OFF
17-time fl ash
2.5 seconds OFF
(MUZ-
HM09/12/15/18/
24NA(2)
2-time fl ash
2.5 seconds OFF
3-time fl ash
2.5 seconds OFF
4-time fl ash
2.5 seconds OFF
5-time fl ash
2.5 seconds OFF
8-time fl ash
2.5 seconds OFF
10-time fl ash
2.5 seconds OFF
12-time fl ash
2.5 seconds OFF
13-time fl ash
2.5 seconds OFF
U1
-
Abnormal point/
Condition
Outdoor power system
Outdoor thermistors Discharge temperature thermistor, fi n temperature thermistor,
Outdoor control system
Serial signal The communication fails between the indoor and outdoor unit
Stop valve/
Closed valve
4-way valve/
Pipe temperature
Outdoor refrigerant
system abnormality
)
Overcurrent protection
Discharge temperature overheat
protection
Fin temperature /
P.C. board temperature thermistor
overheat protection
High pressure protection
Compressor synchronous abnormality
Outdoor fan motor Outdoor fan has stopped 3 times in a row within 30 seconds
Each phase current
of compressor
DC voltageDC voltage of inverter cannot be detected normally.
0.5-second ON
2.5-second OFF
Overcurrent protection cut-out operates 3 consecutive times
within 1 minute after the compressor gets started.
defrost thermistor, P.C. board temperature thermistor, outdoor
heat exchanger temperature thermistor or ambient temperature thermistor shorts or opens during compressor running.
Nonvolatile memory data cannot be read properly.
(The upper lamp of the OPERATION INDICATOR lamp on the
indoor unit lights up or fl ashes 7-time.)
for 3 minutes.
Closed valve is detected by compressor current.
The 4-way valve does not work properly.
The indoor coil thermistor detects an abnormal temperature.
A closed valve and air trapped in the refrigerant circuit are
detected based on the temperature sensed by the indoor and
outdoor thermistors and the current of the compressor.
Large current fl ows into the power module (IPM) (MUZ-
HM09/12NA(2)
U1
-
).
When overcurrent protection occurs within 10 seconds after
compressor starts, compressor restarts after 15 seconds
(MUZ-HM09/12NA).
Temperature of discharge temperature thermistor exceeds
241°F (116°C), compressor stops. Compressor can restart if
discharge temperature thermistor reads 212°F (100°C) or less
3 minutes later.
Temperature of the fi n temperature thermistor on the heat sink
exceeds 167 - 176°F (75 - 80°C) (MUZ-HM09/12NA(2))/167 187°F
(75 - 86°C) (MUZ-HM15/18/24NA(2)) or temperature of P.C.
board temperature thermistor on the inverter P.C. board exceeds 158 - 167°F (70 - 75°C) (MUZ-HM09/12NA(2))/162 185°F (72 - 85°C) (MUZ-HM15/18/24NA(2)).
Indoor coil thermistor exceeds 158°F (70°C) in HEAT mode.
Defrost thermistor exceeds 158°F (70°C) in COOL mode.
The waveform of compressor current is distorted.
after outdoor fan start-up.
Each phase current of compressor cannot be detected normally.
-
Condition Remedy
U8
)/(IC700) (MUZ-HM09/12/15/18/24NA(2)
0.5-second ON
Reconnect connector of compres-
•
sor.
Refer to 10-5.
•
inverter/compressor".
Check stop valve.
•
Refer to 10-5.
•
thermistors".
Replace inverter P.C. board.
•
Refer to 10-5.
•
miswiring and serial signal error.
Check stop valve.
•
Refer to 10-5.
•
coil".
Replace the inverter P.C. board.
•
Check for a gas leak in a
•
connecting piping etc.
Check the stop valve.
•
Refer to 10-5.
•
refrigerant circuit”.
Reconnect connector of compressor.
•
Refer to 10-5. "How to check
•
inverter/compressor".
Check stop valve.
•
Check refrigerant circuit and refrig-
•
erant amount.
Refer to 10-5.
•
Check around outdoor unit.
•
Check outdoor unit air passage.
•
Refer to 10-5.
•
fan motor".
Check refrigerant circuit and refrig-
•
erant amount.
Check stop valve.
•
Reconnect connector of compressor.
•
Refer to 10-5.
•
inverter/compressor".
Refer to 10-5.
•
fan motor.
Refer to 10-5.
•
P.C. board.
Refer to 10-5.
•
inverter/compressor".
Refer to 10-5.
•
verter/compressor".
Inverter P.C. board
MUZ-HM09/12NA(2)
MUZ-HM15/18/24NA(2)
Flashing →
"How to check
"Check of outdoor
"How to check
"Check of R.V.
“Check of outdoor
"Check of LEV".
"Check of outdoor
"How to check
"Check of outdoor
"Check of inverter
"How to check
"How to check in-
LED
Flashing →
LED
41
No. Symptom LED indication
OBH747C
Outdoor unit
operates.
16
16
18
19
Outdoor unit
operates.
20
21
22
NOTE: 1. The location of LED is illustrated at the right fi gure. Refer to 10-6.1.
2. LED is lighted during normal operation.
3. Blinking patterns of this mode differ from the ones of the failure recall mode.
The fl ashing frequency shows the number of times the LED blinks after every 2.5-second OFF.
(Example) When the fl ashing frequency is “2”.
ON
2.5-second OFF
OFF
1-time fl ash
2.5 seconds OFF
3-time fl ash
2.5 seconds OFF
4-time fl ash
2.5 seconds OFF
5-time fl ash
2.5 seconds OFF
7-time fl ash
2.5 seconds OFF
8-time fl ash
2.5 seconds OFF
9-time fl ash
2.5 seconds OFF
Abnormal point/
Condition
Frequency drop by
current protection
Frequency drop by
high pressure protection
Frequency drop by
defrosting in COOL
mode
Frequency drop by
discharge temperature protection
Outside temperature
thermistor protection
Low discharge temperature protection
PAM protection
PAM: Pulse Amplitude Modulation
Zero cross detecting
circuit
(MUZ-HM09/12NA(2))
Inverter check mode The connector of compressor is disconnected, inverter check
0.5-second ON
2.5-second OFF
MUZ-HM
09/12NA(2)
MUZ-HM15/
18/24NA(2)
Temperature of indoor coil thermistor exceeds 131 °F (55°C)
in HEAT mode, compressor frequency lowers.
Indoor coil thermistor reads 46°F (8°C) or less in COOL mode,
compressor frequency lowers.
Temperature of discharge temperature thermistor exceeds
232°F (111°C), compressor frequency lowers.
When the outside temperature thermistor shorts or opens,
protective operation without that thermistor is performed.
Temperature of discharge temperature thermistor has been
122°F (50°C) or less for 20 minutes.
The overcurrent fl ows into IGBT (Insulated Gate Bipolar tran-
sistor: TR821) (MUZ-HM09/12NA(2)
correction: IC820) (MUZ-HM09/12/15/18/24NA(2)
DC voltage reaches 320 V (MUZ-HM09/12NA(2)
(MUZ-HM09/12/15/18/24NA(2)
restarts.
Zero cross signal for PAM control cannot be detected.
mode starts.
Current from power outlet is nearing Max. fuse
size.
When the input current exceeds approximately
10.5 A, compressor frequency lowers.
Condition Remedy
U8
-
)/PFC (Power factor
U1
-
) or more, PAM stops and
0.5-second ON
-
-
U8
U1
) or the
)/394 V
The unit is normal, but check the
following.
Check if indoor fi lters are clogged.
•
Check if refrigerant is short.
•
Check if indoor/outdoor unit air
•
circulation is short cycled.
Check refrigerant circuit and refrig-
•
erant amount.
Refer to 10-5.
•
Refer to 10-5.
•
thermistors".
Refer to 10-5.
•
thermistors.
Refer to 10-5.
•
Check refrigerant circuit and refrig-
•
erant amount.
This is not malfunction. PAM protection will be activated in the following cases:
1 Instantaneous power voltage
drop. (Short time power failure)
2 When the power supply voltage
is high.
Check if the connector of the com-
•
pressor is correctly connected.
Refer to 10-5.
inverter/compressor".
Refer to 10-6. “Test point diagram and voltage”, 1. “Inverter P.C.
board”, for the chart of thermistor.
Measure the resistance with a tester. Before measurement, hold the
thermistor with your hands to warm it up.
Refer to 10-6. “Test point diagram and voltage”, 1. “Inverter P.C.
board”, for the chart of thermistor.
Measure the resistance between terminals using a tester.
[Temperature: 14 - 104°F (-10 - 40°C)]
Normal (Ω)
HM09/12
-
U1
HM09
-
U8
HM12
-
U8
HM15/18/24
U-V
U-W
1.26 - 1.721.36 - 1.931.52 - 2.170.82 - 1.11
V-W
Measure the resistance between lead wires using a tester.
[Temperature: 14 - 104°F (-10 - 40°C)]
Color of lead wire
HM09/12/15/18HM24
Normal (Ω)
RED – BLK
BLK – WHT
29 - 4012 - 16
WHT – RED
Measure the resistance using a tester.
[Temperature: 14 - 104°F (-10 - 40°C)]
Normal (kΩ)
0.97 - 1.38
WHT
V
WHT
V
RED BLK
W
U
RED BLK
W
U
Measure the resistance using a tester.
[Temperature: 14 - 104°F (-10 - 40°C)]
Expansion valve coil (LEV)
Measure the resistance using a tester.
Defrost heater
[Temperature: 14 - 104°F (-10 - 40°C)]
(Optional parts)
Color of lead wire Normal (Ω)
RED – ORN
RED – WHT
RED – BLU
37 - 54
RED – YLW
Normal (Ω)
349 - 428
43
WHT
ORN
RED
(+12V)
LEV
YLW
BLU
10-5. TROUBLESHOOTING FLOW
OBH747C
A How to check inverter/compressor
Disconnect the connector between the compressor and the
-
power module (IPM) (MUZ-HM09/12NA(2)
-
(MUZ-HM09/12NA(2)
U1
, MUZ-HM
Check the voltage between terminals.
Are the voltages balanced?
Yes
Check the compressor.
U8
)/(IC700)
15/18/24NA(2))
No
See 10-5. “Check of open phase”.
Replace the inverter P.C. board.
See 10-5. “Check of compressor”.
B Check of open phase
-
● With the connector between the compressor and the power module (IPM) (MUZ-HM09/12NA(2)
-
U1
HM09/12NA(2)
, MUZ-HM15/18/24NA(2)) disconnected, activate the inverter and check if the inverter is normal by meas-
uring the voltage balance between the terminals.
Output voltage is 50 - 130 V. (The voltage may differ according to the tester.)
<< Operation method>>
Start cooling or heating operation by pressing EMERGENCY OPERATION switch on the indoor unit. (TEST RUN OPERA-
TION: Refer to 7-6.)
<<Measurement point>>
At 3 points
BLK (U)-WHT (V)
Measure AC voltage between the lead wires at 3 points.
BLK (U)-RED (W)
WHT(V)-RED (W)
U8
)/(IC700) (
MUZ-
NOTE: 1. Output voltage varies according to power supply voltage.
2. Measure the voltage by analog type tester.
3. During this check, LED of the inverter P.C. board fl ashes 9 times. (Refer to 10-6.1.)
C Check of compressor
Refer to 10-5. “Check of compressor
winding”.
Is the compressor normal?
Yes
Refer to 10-5. “Check of compressor
operation time”.
Does the compressor operate continuously?
Yes
OK
No
No
Replace the compressor.
Refer to 10-5.
“Check of compressor start failure”.
44
D Check of compressor winding
OBH747C
●Disconnect the connector between the compressor and the power module (IPM) (MUZ-HM09/12NA(2)
HM09/12NA(2)
<<Measurement point>>
At 3 points
BLK-WHT
BLK-RED
WHT-RED
<<Judgement>>
Refer to 10-4.
0 [Ω] ················Abnormal [short]
Infinite [Ω] ·······Abnormal [open]NOTE: Be sure to zero the ohmmeter before measurement.
-
U1
, MUZ-HM15/18/24NA(2)), and measure the resistance between the compressor terminals.
Measure the resistance between the lead wires at 3 points.
E Check of compressor operation time
<<Judgement>>
-
U8
)/(IC700) (
MUZ-
● Connect the compressor and activate the inverter. Then measure
the time until the inverter stops due to overcurrent.
<<Operation method>>
Start heating or cooling operation by pressing EMERGENCY
OPERATION switch on the indoor unit. (TEST RUN OPERATION:
Refer to 7-6.)
<<Measurement>>
Measure the time from the start of compressor to the stop of
compressor due to overcurrent.
F Check of compressor start failure
Confi rm that ~ is normal.
•Electrical circuit check
. Contact of the compressor connector
. Output voltage of inverter P.C. board and balance of them (See 10-5. )
. Direct current voltage between DB61(+) and (-) on the inverter P.C. board
. Voltage between outdoor terminal block S1-S2
Does the compressor run for 10 seconds or
more after it starts?
No
After the compressor is heated with a drier,
does the compressor start?
1
Yes
Compressor start failure. Activate pre-heat control.
(Refer to 9-2. "PRE-HEAT CONTROL SETTING")
Yes
No
Check the refrigerant circuit.
Check the stop valve.
Replace the compressor.
1
Heat the compressor with
a drier for about 20 minutes.
Do not recover refrigerant
gas while heating.
Heating part
45
G Check of outdoor thermistors
OBH747C
Disconnect the connector of thermistor in the inverter P.C. board (see
below table), and measure the resistance of thermistor.
Is the resistance of thermistor normal?
(Refer to 10-6.1.)
Yes
No
Replace the thermistor except RT64.
When RT64 is abnormal, replace the inverter P.C.
board.
Reconnect the connector of thermistor.
Turn ON the power supply and press EMERGENCY OPERATION switch.
Does the unit operate for 10 minutes or more
without showing thermistor abnormality?
No
Replace the inverter P.C. board.
Yes
OK
(Cause is poor contact.)
Thermistor Symbol Connector, Pin No. Board
DefrostRT61Between CN641 pin1 and pin2
Discharge temperature RT62Between CN641 pin3 and pin4
Fin temperature RT64Between CN642 pin1 and pin2
Inverter P.C. board
Ambient temperature RT65Between CN643 pin1 and pin2
Outdoor heat exchanger temperature RT68Between CN644 pin1 and pin3
H Check of R.V. coil
First of all, measure the resistance of R.V. coil to check if the coil is defective. Refer to 10-4.
Check if there is 208/230 VAC at L1 - L2.
In case CN721 is disconnected or R.V. coil is open, voltage is generated between the terminal pins of the connector
although no signal is being transmitted to R.V. coil.
Check if CN721 is connected.
Unit operates COOL mode even if it is set to HEAT mode.
Disconnect connector between the
compressor and the power module
-
(IPM) (MUZ-HM09/12NA(2)
(IC700) (
MUZ-HM09/12NA(2)
U8
)/
-
U1
, MUZ-
HM15/18/24NA(2)).
Turn ON the power supply and press
EMERGENCY OPERATION switch twice
(HEAT mode).
Unit operates HEAT mode even if it is set to COOL mode.
Disconnect connector between the
compressor and the power module
(IPM) (MUZ-HM09/12NA(2)
(IC700) (
MUZ-HM09/12NA(2)
HM15/18/24NA(2)).
Turn ON the power supply and press
EMERGENCY OPERATION switch once
(COOL mode).
-
U8
)/
-
U1
, MUZ-
Is there 208/230 VAC between CN721
and
on the inverter P.C. board
3 minutes after the power supply is turned
ON?
Yes
Replace the 4-way valve.
Is there 208/230 VAC between CN721
and
on the inverter P.C. board
3 minutes after the power supply is turned
ON?
No
Replace the 4-way valve.
46
Replace the inverter
P.C. board.
No
Replace the inverter
P.C. board.
Yes
I Check of outdoor fan motor
OBH747C
Check the connection between the
connector CN931 and CN932.
Disconnect the connectors CN931
and CN932 from the inverter P.C.
board.
Is the resistance between each terminal of outdoor fan motor normal?
(Refer to 10-4.)
No
Yes
Disconnect CN932 from the inverter P.C. board, and turn on the
power supply.
Rotate the outdoor fan motor manually and measure the voltage
of CN931.
Between 1(+) and 5(-)
Between 2(+) and 5(-)
Between 3(+) and 5(-)
(Fixed to either 5 or 0 VDC)
Replace the outdoor fan motor.
Does the voltage between each terminal become 5 and 0
No
VDC repeatedly?
Yes
Does the outdoor fan motor rotate smoothly?
No
Replace the inverter P.C. board.
Yes
47
J Check of power supply
OBH747C
Disconnect the connector between the
compressor and the power module (IPM)
(MUZ-HM09/12NA(2)
HM09/12NA(2)
Turn ON power supply and press
EMERGENCY OPERATION switch.
Does the upper lamp of the
OPERATION INDICATOR lamp on
the indoor unit light up?
-
U8
-
U1
)/(IC700) (
, MUZ-HM15/18/24NA(2)).
Yes
MUZ-
No
Rectify indoor/outdoor
connecting wire.
No
Is there voltage 208/230 VAC
between the indoor terminal
block S1 and S2?
Replace the indoor
electronic control P.C.
Yes
board.
Is there DC voltage 260 - 325 VDC
-
(MUZ-HM09/12NA(2)
370 VDC (
MUZ-HM09/12NA(2)
U8
)/260 -
-
U1
, MUZ-HM15/18/24NA(2)) between
DB61 (+) and DB61 (–) on the
inverter P.C. board?
(Refer to 10-6.1.)
Does LED on the inverter P.C.
board light up or fl ash?
(Refer to 10-6.1.)
Yes
If lights up, OK.
If fl ashes, refer to 10-3.
-
U8
)
-
U1
, MUZ-HM15/18/24NA(2))
Replace the inverter
No
P.C. board.
48
K Check of LEV (Expansion valve)
OBH747C
Turn ON the power supply.
<Preparation of the remote controller>
While pressing both OPERATION SELECT button
and TOO COOL button on the remote controller at the
same time, press RESET button.
First, release RESET button.
Hold down the other 2 buttons for another 3 seconds.
Make sure that the indicators on the LCD screen
shown in the right fi gure are all displayed. Then re-
lease the buttons.
Press STOP/OPERATE (OFF/ON) button of the remote
controller (the set temperature is displayed) with the
remote controller headed towards the indoor unit. 1
Expansion valve operates in full-opening direction.
Do you hear the expansion valve "click,
click·······"?
Do you feel the expansion valve vibrate
when touching it ?
No
Yes
OK
1. Regardless of normal or abnormal condition, a short beep
is emitted once the signal is received.
Is LEV coil properly fi xed to
the expansion valve?
Yes
Does the resistance of LEV
coil have the characteristics?
(Refer to 10-4.)
No
Replace the LEV coil.
NOTE: After check of LEV, do the undermentioned operations.
1. Turn OFF the power supply and turn it ON again.
2. Press RESET button on the remote controller.
No
Yes
Properly fi x the LEV coil to the expansion valve.
Measure each voltage between connector
pins of CN724 on the inverter P.C. board.
1. Pin (-) — Pin (+)
2. Pin (-) — Pin (+)
3. Pin (-) — Pin (+)
4. Pin (-) — Pin (+)
Is there about 3 - 5 VAC between each?
NOTE: Measure the voltage by an analog
tester.
Replace the expansion valve.
Yes
Replace the inverter P.C.
No
board.
49
L Check of inverter P.C. board
OBH747C
Check the outdoor fan motor.
(Refer to 10-5.
.)
Is the fuse (F901) blown on the inverter P.C. board?
No
Check the connection of the connectors
(CN931, CN932) of the outdoor fan motor.
If the connection is poor, make it correct.
Operate the outdoor unit by starting
EMERGENCY OPERATION.
Check the LED indication on the inverter P.C. board.
Does the LED fl ash 10 times?
Yes
(10-time fl ash)
Replace the inverter P.C. board.
Yes
No
Check the corresponding parts
following LED indication.
(Refer to 10-3.)
50
M How to check miswiring and serial signal error
OBH747C
MUZ-HM09/12NA(2)
Is the bus-bar voltage of the inverter P.C. board normal? (Refer to "TEST POINT DIAGRAM AND
VOLTAGE" in the outdoor service manual.)
Turn OFF the power supply.
Is there rated voltage in the power supply?
Turn ON the power supply.
Is there rated voltage between outdoor terminal block S1 and S2?
Press EMERGENCY OPERATION switch once.
Does the OPERATION INDICATOR lamp light
up? <Confi rmation of the power to the indoor
unit>
Is serial signal error indicated 6 minutes later?
Turn OFF the power supply.
Check once more if the indoor/outdoor
B
connecting wire is not miswiring.
Bridge the outdoor terminal block S2 and
1
S3.
Turn ON the power supply.
Yes
Yes
Yes
Yes
A
Yes
No
No
No
1. Miswiring may damage indoor electronic control P.C.
3. Be sure to check this within 3 minutes after turning ON.
Check the power supply.
Is there any miswiring, poor
contact, or wire disconnection of the indoor/outdoor
connecting wire?
board during the operation.
Be sure to confi rm the wiring is correct before the opera-
tion starts.
After 3 minutes, LED blinks 6 times. Even when the
inverter P.C. board is normal, LED blinks 6 times after 3
minutes.
No
No
Check the wiring.
Correct them.
Yes
Check of power supply.
(Refer to 10-5. .)
No
Does the LED on the inverter P.C. board repeat "3.6-second-OFF and 0.8-second-ON quick blinking"?
Turn OFF the power supply.
Remove the bidge between the outdoor terminal block S2 and S3.
Turn ON the power supply.
Is there rated voltage between the indoor terminal block S1 and S2?
<Confi rmation of power voltage>
Is there amplitude of 10 to 20 VDC between the indoor terminal block
S2 and S3? <Confi rmation of serial signal>
A
• Turn OFF inverter-controlled lighting
equipment.
• Turn OFF the power supply and then
turn ON again.
• Press EMERGENCY OPERATION
switch.
• Reinstall
either the unit
or the light
away from
Is serial signal
error indicated 6
minutes later?
Yes
B
each other.
• Attach a fi lter
No
on remote
control receiving section
of the indoor
unit.
3
Yes
Yes
Yes
Is there 2 VDC or less between CN10A (+)
and JPG (GND)(-) on the indoor electronic
control P.C. board?
Yes
Is there 2 VDC or less between
CN10A (+) and JPG (GND)(-) on
the indoor electronic control P.C.
board?
Replace the indoor power
P.C. board and the indoor
terminal P.C. board
No
NoYesNo
No
(Lighted
or not
lighted)
Check the wiring
If there are any error of the indoor/outdoor connecting wire:
such as the damage of the wire, intermediate connection,
No
and/or poor contact to the terminal block, replace the indoor/
outdoor connecting wire.
No
Replace the indoor electronic control P.C. board.
Replace the inverter P.C. board. 2
2. Be careful of the residual voltage of smoothing
capacitor.
Is there 2 VDC or less between
CN10A (+) and JPG (GND)(-) on
the indoor electronic control P.C.
board?
Yes
51
MUZ-HM15/18/24NA(2)
OBH747C
Turn OFF the power supply.
NOTE: Refer to the indoor unit service manual.
Is there rated voltage in the power supply?
Turn ON the power supply.
Is there rated voltage between outdoor terminal block S1 and S2?
Press EMERGENCY OPERATION switch once.
Does the OPERATION INDICATOR lamp light
up? <Confi rmation of the power to the indoor
unit>
Is serial signal error indicated 6 minutes
later?
Turn OFF the power supply.
Check once more if the indoor/outdoor
B
connecting wire is not miswiring.
Bridge the outdoor terminal block S2 and
1
S3.
Turn ON the power supply.
Is the bus-bar voltage of the inverter P.C. board normal? (Refer to "TEST POINT DIAGRAM AND
VOLTAGE" in the outdoor service manual.)
Yes
Yes
Yes
Yes
A
Yes
No
No
No
1. Miswiring may damage indoor electronic control P.C.
3. Be sure to check this within 3 minutes after turning ON.
(Except for outdoor unit of multi system type)
Check the power supply.
Is there any miswiring,
poor contact, or wire
disconnection of the
indoor/outdoor connecting wire?
board during the operation.
Be sure to confi rm the wiring is correct before the opera-
tion starts.
After 3 minutes, LED blinks 6 times. Even when the
inverter P.C. board or the outdoor electronic control P.C.
board is normal, LED blinks 6 times after 3 minutes.
No
No
Check the wiring.
Correct them.
Yes
No
Does the LED on the inverter P.C. board repeat "3.6-second-OFF and 0.8-second-ON quick blinking"?
Is there amplitude of 10 to 20 VDC between the indoor terminal block
S2 and S3? <Confi rmation of serial signal>
A
• Turn OFF inverter-controlled lighting
equipment.
• Turn OFF the power supply and then
turn ON again.
• Press EMERGENCY OPERATION
switch.
• Reinstall
either the unit
or the light
away from
Is serial signal
error indicated 6
minutes later?
Yes
B
each other.
• Attach a fi lter
No
on remote
control receiving section
of the indoor
unit.
3
Yes
Turn OFF the power supply.
Remove the bridge between outdoor terminal block S2 and S3.
Turn on the power supply.
No
Yes
Is there 2 VDC or less between CN10A (+)
and GND (-) on the indoor electronic control
P.C. board?
Yes
Is there 2 VDC or less between
CN10A
the indoor electronic control P.C.
board?
Replace the indoor power
P.C. board.
No
(+) and GND (-) on
NoYesNo
Replace the indoor electronic control P.C. board.
52
No
(Lighted
or not
lighted)
Replace the inverter P.C. board. 2
2. Be careful of the residual voltage of smoothing
capacitor.
Is there 2 VDC or less between
CN10A
the indoor electronic control P.C.
board?
(+) and GND (-) on
Yes
N Check of defrost heater
OBH747C
Check the following points before checking electric continuity.
1. Does the resistance of ambient temperature thermistor have the characteristics? Refer to 10-6.1.
2. Is the resistance of defrost heater normal? Refer to 10-4.
3. Does the heater protector remain conducted (not open)?
4. Are both ambient temperature thermistor and circuit of defrost heater securely connected to connectors?
In HEAT mode, for more than 5 minutes, let the ambient temperature thermistor continue to read
32°F (0°C) or below, and let the defrost thermistor continue to read 30°F (-1°C) or below.
NOTE: In case both thermistors are more than the above temperature, cool them with cold
(Optional parts)
water etc...
Is there 208/230 VAC between CN722 and
on the inverter P.C. board? Refer to 10-6.1.
No
Replace the inverter P.C. board.
O Check of outdoor refrigerant circuit
Has the operation stopped
during pump down?
Yes
The operation has stopped to prevent the diesel explosion caused by
air trapped in the refrigerant circuit.
Close the stop valve, and disconnect
the power plug or turn the breaker
OFF.
No
Was the operation started with
the stop valve closed, and was
it opened during operation?
The refrigerant gas amount may be
60% or less than the normal amount.
Identify where the gas is leaking from,
and fi x the leak.
Yes
Not the problem of the inverter P.C. board.
(MUZ-HM09/12/15/18/24NA(2)
Yes
No
-
U1
)
The unit occasionally stops when the
stop valve is opened or closed during
operation. Open the stop valve and
start the cooling operation again.
CAUTION : Do not start the opera-
tion again to prevent
hazards.
53
P Electromagnetic noise enters into TV sets or radios
OBH747C
Is the unit grounded?
Yes
Is the distance between the antennas
and the indoor unit within 9.91 ft.
or is the distance between the antennas
and the outdoor unit within 9.91 ft.
No
Is the distance between the TV sets or radios and the indoor unit within 3.28 ft.
or is the distance between the TV sets or
radios and the outdoor unit within
9.91 ft.
(3m)
?
No
Are the antennas damaged?
Is the coaxial cable damaged?
Is there any poor contact in the antenna wiring?
No
Is the indoor/outdoor connecting wire
of the air conditioner and the wiring of
the antennas close?
No
(3m)
(3m)
(1m)
No
,
Yes
?
,
Yes
Yes
Yes
Ground the unit.
Extend the distance between the antennas and
the indoor unit, and/or the antennas and the
outdoor unit.
Extend the distance between the TV sets and/or
radios and the indoor unit, or the TV sets or
radios and the outdoor unit.
Replace or repair the antenna.
Replace or repair the coaxial cable.
Extend the distance between the indoor/outdoor
connecting wire of the air conditioner and the wiring of the antennas.
Even if all of the above conditions are fulfi lled, the electromagnetic noise may enter, depending on the electric fi eld strength
or the installation condition (combination of specifi c conditions such as antennas or wiring).
Check the following before asking for service.
1. Devices affected by the electromagnetic noise
TV sets, radios (FM/AM broadcast, shortwave)
2. Channel, frequency, broadcast station affected by the electromagnetic noise
3. Channel, frequency, broadcast station unaffected by the electromagnetic noise
4. Layout of:
indoor/outdoor unit of the air conditioner, indoor/outdoor wiring, ground wire, antennas, wiring from antennas, receiver
5. Electric fi eld intensity of the broadcast station affected by the electromagnetic noise
6. Presence or absence of amplifi er such as booster
7. Operation condition of air conditioner when the electromagnetic noise enters in
1) Turn OFF the power supply once, and then turn ON the power supply. In this situation, check for the electromagnetic
noise.
2) Within 3 minutes after turning ON the power supply, press STOP/OPERATE (OFF/ON) button on the remote controller
for power ON, and check for the electromagnetic noise.
3) After a short time (3 minutes later after turning ON), the outdoor unit starts running. During operation, check for the
electromagnetic noise.
4) Press STOP/OPERATE (OFF/ON) button on the remote controller for power OFF, when the outdoor unit stops but the
indoor/outdoor communication still runs on. In this situation, check for the electromagnetic noise.
54
10-6. TEST POINT DIAGRAM AND VOLTAGE
-41432506886 104
0
10
20
30
40
50
60
70
80
90
100
Temperature(°F)
Defrost thermistor(RT61)
Ambient temperature thermistor(RT65)
Outdoor heat exchanger temperature thermistor(RT68)
32 50 68 86 104 122 140 158 176
0
20
40
60
80
100
120
140
160
180
200
Temperature(°F)
Fin temperature thermistor(RT64)
5HVLVWDQFHN
5HVLVWDQFHN
Temperature (°F)
Discharge temperature thermistor (RT62)
5HVLVWDQFHN
0
100
200
300
400
500
600
700
800
32 50 68 86 104 122 140 158 176 194 212 230 248
OBH747C
1. Inverter P.C. board
U1
MUZ-HM09NA
MUZ-HM09NA2
Back side of unit
208/230 VAC
Fuse (F901)
T3.15AL250V
Output to
drive outdoor
fan motor
(CN932)
Output to
drive
compressor
(LDU,
LDV,
LDW)
-
MUZ-HM12NA
U1
-
MUZ-HM12NA2
DB61
260 - 370 VDC
-
(+)(-)
U1
U1
-
Smoothing
capacitor (C62)
Smoothing
capacitor (C61)
Fuse (F801)
T3.15AL250V
R.V.coil
(CN721)
208/230 VAC
Fuse (F701)
T3.15AL250V
LED
Front side of unit
Fin temperature
thermistor/RT64
(CN642)
Signal of outdoor
fan motor (CN931)
Defrost thermistor
Ambient temperature
thermistor/RT65
/RT61(CN641)
(CN643)
55
Discharge temperature
thermistor/RT62
(CN641)
Outdoor heat exchanger
temperature thermistor
/RT68 (CN644)
LEV connector
(CN724)
208/230 VAC
Jumper wire for preheat control setting
(JK)
Jumper wire for
changing defrost
setting (JS)
-41432506886 104
0
10
20
30
40
50
60
70
80
90
100
Temperature(°F)
Defrost thermistor(RT61)
Ambient temperature thermistor(RT65)
Outdoor heat exchanger temperature thermistor(RT68)
32 50 68 86 104 122 140 158 176
0
20
40
60
80
100
120
140
160
180
200
Temperature(°F)
Fin temperature thermistor(RT64)
5HVLVWDQFHN
5HVLVWDQFHN
Temperature (°F)
Discharge temperature thermistor (RT62)
5HVLVWDQFHN
0
100
200
300
400
500
600
700
800
32 50 68 86 104 122 140 158 176 194 212 230 248
1. Inverter P.C. board
OBH747C
U8
MUZ-HM09NA
MUZ-HM09NA2
-
-
MUZ-HM12NA
U8
MUZ-HM12NA2
U8
-
U8
-
Back side of unit
208/230 VAC
Fuse (F901)
T3.15AL250V
Output to
drive
compressor
(LDU,
LDV,
LDW)
Bus-bar voltage
DB61
260-325 VDC
(-)
(+)
Smoothing
capacitor
(C63)
Smoothing
capacitor
(C62)
Fuse (F801)
T3.15AL250V
Fuse (F701)
T3.15AL250V
R.V.coil
(CN721)
208/230
VAC
Signal of
outdoor
fan motor
(CN931)
208/230
VAC
Front side of unit
Output to drive outdoor
fan motor (CN932)
Fin temperature
thermistor/RT64 (CN642)
Outdoor heat exchanger
temperature thermistor
/RT68 (CN644)
Discharge temperature
thermistor/RT62
(CN641)
Defrost thermistor
/RT61(CN641)
Ambient temperature
thermistor/RT65 (CN643)
56
LEV
LED
connector
(CN724)
Jumper wire for
changing defrost
setting (JS)
Jumper wire
for pre-heat
control setting
(JK)
1. Inverter P.C. board
OBH747C
MUZ-HM15NA MUZ-HM18NA
MUZ-HM15NA2 MUZ-HM18NA2
Back side of unit
208/230 VAC
Fuse (F901)
T3.15AL250V
Output to
drive outdoor
fan motor
(CN932)
Output to
drive
compressor
(LDU,
LDV,
LDW)
DB61
260 - 370 VDC
Smoothing
capacitor (C63)
Smoothing
capacitor (C62)
(+)(-)
Fuse (F801)
T3.15AL250V
Smoothing
capacitor (C61)
R.V.coil
(CN721)
208/230 VAC
Fuse (F701)
T3.15AL250V
LED
Front side of unit
Fin temperature
thermistor/RT64
Defrost thermistor(RT61)
Ambient temperature thermistor(RT65)
Outdoor heat exchanger temperature thermistor(RT68)
100
90
80
70
60
50
40
30
5HVLVWDQFHN
20
10
0
-41432506886 104
Temperature(°F)
(CN642)
Signal of outdoor
fan motor (CN931)
Defrost thermistor
Ambient temperature
thermistor/RT65
Discharge temperature thermistor (RT62)
800
700
600
500
400
300
5HVLVWDQFHN
200
100
0
32 50 68 86 104 122 140 158 176 194 212 230 248
/RT61(CN641)
(CN643)
Temperature (°F)
Discharge temperature
57
thermistor/RT62
(CN641)
Outdoor heat exchanger
temperature thermistor
/RT68 (CN644)
200
180
160
140
120
100
5HVLVWDQFHN
208/230 VAC
Jumper wire for preheat control setting
(JK)
Jumper wire for
changing defrost
setting (JS)
LEV connector
(CN724)
Fin temperature thermistor(RT64)
80
60
40
20
0
32 50 68 86 104 122 140 158 176
Temperature(°F)
1. Inverter P.C. board
OBH747C
MUZ-HM24NA
MUZ-HM24NA2
Back side of unit
208/230 VAC
Fuse (F901)
T3.15AL250V
Output to
drive outdoor
fan motor
(CN932)
Output to
drive
compressor
(LDU,
LDV,
LDW)
Smoothing
capacitor (C63)
DB61
260 - 370 VDC
(+)(-)
Smoothing
capacitor (C62)
Fuse (F801)
T3.15AL250V
Smoothing
capacitor (C61)
R.V.coil
(CN721)
208/230 VAC
Heater connector
(CN722) (Optional parts)
Fuse (F701)
T3.15AL250V
Front side of unit
Defrost thermistor(RT61)
Ambient temperature thermistor(RT65)
Outdoor heat exchanger temperature thermistor(RT68)
100
90
80
70
60
50
40
30
5HVLVWDQFHN
20
10
0
-41432506886 104
Temperature(°F)
LED
Fin temperature
thermistor/RT64
(CN642)
Signal of outdoor
fan motor (CN931)
Discharge temperature thermistor (RT62)
800
700
600
500
400
300
5HVLVWDQFHN
200
100
0
32 50 68 86 104 122 140 158 176 194 212 230 248
Defrost thermistor
Ambient temperature
thermistor/RT65
/RT61(CN641)
(CN643)
Temperature (°F)
Discharge temperature
thermistor/RT62
58
(CN641)
Outdoor heat exchanger
temperature thermistor
/RT68 (CN644)
LEV connector
(CN724)
Fin temperature thermistor(RT64)
200
180
160
140
120
100
80
60
5HVLVWDQFHN
40
20
0
32 50 68 86 104 122 140 158 176
208/230 VAC
Jumper wire for preheat control setting
(JK)
Jumper wire for
changing defrost
setting (JS)
Temperature(°F)
11
(1) Slide the sleeve and check if there is a locking lever or not.(2) The terminal with this connector has the
locking mechanism.
Slide the sleeve.
Pull the terminal while
pushing the locking
lever.
Hold the sleeve, and
pull out the terminal
slowly.
Connector
Sleeve
Locking lever
OBH747C
DISASSEMBLY INSTRUCTIONS
<"Terminal with locking mechanism" Detaching points>
The terminal which has the locking mechanism can be detached as shown below.
There are 2 types (refer to (1) and (2)) of the terminal with locking mechanism.
The terminal without locking mechanism can be detached by pulling it out.
Check the shape of the terminal before detaching.
NOTE: Turn OFF the power supply before disassembly.
OPERATING PROCEDUREPHOTOS
1. Removing the cabinet
(1) Remove the screw fixing the service panel.
(2) Pull down the service panel and remove it.
(3) Remove the screws fixing the conduit cover.
(4) Remove the conduit cover. (Photo 4)
(5) Remove the screw fixing the conduit plate. (Photo 5)
(6) Remove the conduit plate.
(7) Disconnect the power supply wire and indoor/outdoor
connecting wire.
(8) Remove the screws fixing the top panel.
(9) Remove the top panel.
(
10
) Remove the screws fixing the cabinet.
(
11
) Remove the cabinet.
(
12
) Remove the screws fixing the back panel.
(
13
) Remove the back panel.
Photo 2
Screws of the
top panel
Photo 1
Screws of
the cabinet
Photo 3
Screws of
the top panel
Screw of the
cabinet
Back
panel
Screws
of the
back
panel
Service
panel
Screws of
the terminal block
support and the
back panel
Screws of the
cabinet
Screws of
the cabinet
59
Direction
to remove
Hooks
OPERATING PROCEDUREPHOTOS
OBH747C
Photo 4Photo 5
Screws of the
conduit cover
Screw of the
conduit plate
2. Removing the inverter assembly, inverter P.C. board
(1) Remove the cabinet and panels. (Refer to 1.)
(2) Disconnect the lead wire to the reactor and the following
connectors:
<Inverter P.C. board>
CN721 (R.V. coil)
CN931, CN932 (Fan motor)
CN641 (Defrost thermistor and discharge temperature ther-
mistor)
CN643 (Ambient temperature thermistor)
CN644 (Outdoor heat exchanger temperature thermistor)
CN724 (LEV)
(3) Remove the compressor connector (CN61).
(4) Remove the screws fixing the heat sink support and the
separator.
(5) Remove the fixing screws of the terminal block support and
the back panel.
(6) Remove the inverter assembly.
(7) Remove the screw of the ground wire and screw of the ter-
minal block support.
(8) Remove the heat sink support from the P.C. board support.
(9) Remove the screw of the inverter P.C. board and remove the
inverter P.C. board from the P.C. board support.
3. Removing R.V. coil
(1) Remove the cabinet and panels. (Refer to 1.)
(2) Disconnect the following connectors:
<Inverter P.C. board>
CN721 (R.V. coil)
(3) Remove the R.V. coil.
Photo 6
Screws of the heat sink
support and the separator
Soundproof
felt
Photo 7
Heat sink
Heat sink support
P.C. board
support
Screws of the terminal block
support and the back panel
Screw of the
Terminal block
support
60
Screw of the
inverter P.C. board
Terminal
block
support
Screw of the
ground wire
OPERATING PROCEDUREPHOTOS
OBH747C
4. Removing the discharge temperature thermistor,
defrost thermistor, outdoor heat exchanger temperature thermistor and ambient temperature thermistor
(1) Remove the cabinet and panels. (Refer to 1.)
(2) Disconnect the lead wire to the reactor and the following
connectors:
<Inverter P.C. board>
CN641 (Defrost thermistor and discharge temperature ther-
mistor)
CN643 (Ambient temperature thermistor)
CN644 (Outdoor heat exchanger temperature thermistor)
(3)
Pull out the discharge temperature thermistor from its holder.
(4) Pull out the defrost thermistor from its holder.
(5) Pull out the outdoor heat exchanger temperature thermistor
from its holder.
(6) Pull out the ambient temperature thermistor from its holder.
Photo 8
Discharge temperature thermistor
Photo 9
Ambient temperature
thermistor
Outdoor heat
exchanger temperature thermistor
Defrost thermistor
61
OPERATING PROCEDURE
OBH747C
5. Removing outdoor fan motor
(1) Remove the cabinet and panels. (Refer to 1.)
(2) Disconnect the following connectors:
<Inverter P.C. board>
CN931, CN932 (Fan motor)
(3) Remove the propeller fan nut.
(4) Remove the propeller fan.
(5) Remove the screws fixing the fan motor.
(6) Remove the fan motor.
NOTE: The propeller fan nut is a revers thread.
PHOTOS
Photo 10
Screws of the outdoor fan motor
6. Removing the compressor and 4-way valve
(1) Remove the cabinet and panels. (Refer to 1.)
(2) Remove the inverter assembly. (Refer to 2.)
(3) Remove the screws fixing the reactor.
(4) Remove the reactor.
(5) Remove the soundproof felt.
(6) Recover gas from the refrigerant circuit.
NOTE: Recover gas from the pipes until the pressure gauge
shows 0 PSIG.
(7) Detach the brazed part of the suction and the discharge pipe
connected with compressor.
(8) Remove the nuts fixing the compressor.
(9) Remove the compressor.
(
10
) Detach the brazed part of pipes connected with 4-way valve.
Photo 12
Propeller fan
Photo 11
Discharge pipe
brazed part
Propeller fan nut
Screws of
the reactor
Suction pipe
brazed part
Brazed parts of
4-way valve
Screw of the
R.V. coil
62
11-2. MUZ-HM24NA MUZ-HM24NA2
OBH747C
OPERATING PROCEDUREPHOTOS
NOTE: Turn OFF the power supply before disassembly.
1. Removing the cabinet
(1) Remove the screws of the service panel.
(2) Remove the screws of the top panel.
(3) Remove the screw of the valve cover.
(4) Remove the service panel.
(5) Remove the screws fixing the conduit cover.
(6) Remove the conduit cover.
(7) Remove the screw of fixing the conduit plate.
(8) Remove the conduit plate.
(9) Remove the top panel.
(10)
Remove the valve cover.
(11)
Disconnect the power supply and indoor/outdoor connect-
ing wire.
(12)
Remove the screws of the cabinet.
(13)
Remove the cabinet.
(14)
Remove the screws of the back panel.
(15)
Remove the back panel.
Photo 3
Screws of the conduit cover
Photo 1
Screws
of the
cabinet
Screws of the cabinet
Photo 2
Screws of the top panel
Screw of
the valve
cover
Screw of the back panel
Screws of the top panel
Screws of the cabinet
Screws of
the cabinet
Photo 4
Screw of the conduit plate
63
Screws of
the cabinet
Screws of
the back panel
Screws of the service panel
OPERATING PROCEDURE
OBH747C
PHOTOS
2. Removing the inverter assembly, inverter P.C. board
(1) Remove the cabinet and panels. (Refer to 1.)
(2) Disconnect the lead wire to the reactor and the following con-
nectors:
<Inverter P.C. board>
CN721 (R.V. coil)
CN931, CN932 (Fan motor)
CN641 (Defrost thermistor and discharge temperature ther-
mistor)
CN643 (Ambient temperature thermistor)
CN644 (Outdoor heat exchanger temperature thermistor)
CN724 (LEV)
(3) Remove the compressor connector.
(4) Remove the screw fixing the heat sink support and the sepa-
rator.
(5) Remove the fixing screws of the terminal block support and
the back panel.
(6) Remove the inverter assembly.
(7) Remove the screw of the ground wire, screw of the P.C.
board cover and screws of the terminal block support.
(8) Remove the heat sink support from the P.C. board support.
(9) Remove the screw of the inverter P.C. board and the inverter
P.C. board from the P.C. board support.
3. Removing R.V. coil
(1) Remove the cabinet and panels. (Refer to 1.)
(2) Disconnect the following connector:
<Inverter P.C. board>
CN721 (R.V. coil)
(3) Remove the R.V. coil.
Photo 7
Screw of
the R.V. coil
Photo 5
Screw of the heat sink
support and the separator
Photo 6
Heat sink
P.C. board
support
Screw of
the inverter
P.C. board
Screw of the
ground wire
Screws of the terminal
block support and the
back panel
Heat sink
support
Screw of the
P.C. board
cover
Screws of the
terminal block
support
Brazed parts of
4-way valve
64
OPERATING PROCEDUREPHOTOS
OBH747C
4. Removing the discharge temperature thermistor,
defrost thermistor, outdoor heat exchanger temperature thermistor and ambient temperature thermistor
(1) Remove the cabinet and panels. (Refer to 1.)
(2) Disconnect the lead wire to the reactor and the following
connectors:
<Inverter P.C. board>
CN641 (Defrost thermistor and discharge temperature ther-
mistor)
CN643 (Ambient temperature thermistor)
CN644 (Outdoor heat exchanger temperature thermistor)
(3)
Pull out the discharge temperature thermistor from its holder.
(4) Pull out the defrost thermistor from its holder.
(5) Pull out the outdoor heat exchanger temperature thermistor
from its holder.
(6) Pull out the ambient temperature thermistor from its holder.
5. Removing outdoor fan motor
(1)
Remove the top panel, cabinet and service panel. (Refer to 1.)
(2) Disconnect the following connectors:
<Inverter P.C. board>
CN931 and CN932 (Fan motor)
(3) Remove the propeller fan nut.
(4) Remove the propeller fan.
(5) Remove the screws fixing the fan motor.
(6) Remove the fan motor.
NOTE: The propeller fan nut is a reverse thread.
Photo 8
Photo 9
Outdoor heat
exchanger temperature thermistor
Defrost thermistor
Propeller fan nut
Ambient tem-
perature
thermistor
6. Removing the compressor and 4-way valve
(1)
Remove the top panel, cabinet and service panel. (Refer to 1.)
(2) Remove the back panel. (Refer to 1.)
(3) Remove the inverter assembly. (Refer to 2.)
(4) Recover gas from the refrigerant circuit.
NOTE: Recover gas from the pipes until the pressure gauge
shows 0 PSIG.
(5) Detach the brazed part of the suction and the discharge
pipe connected with compressor.
(6) Remove the compressor nuts.
(7) Remove the compressor.
(8) Detach the brazed part of 4-way valve and pipe. (Photo 7)
65
Photo 10
Brazed part of the
discharge pipe
Screws of the
outdoor fan motor
Discharge temperature
thermistor
Brazed part of the suction pipe
HEAD OFFICE: TOKYO BUILDING, 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN