RoHS compliant products have <G> mark on the spec name plate.
MUZ-FH06NAH
MUZ-FH09NAH
MUZ-FH12NAH
PARTS CATALOG (OBB684)
Page 2
Use the specifi ed refrigerant only
OBH684D
Never use any refrigerant other than that specified.
Doing so may cause a burst, an explosion, or fire when the unit is being used, serviced, or disposed of.
Correct refrigerant is specified in the manuals and on the spec labels provided with our products.
We will not be held responsible for mechanical failure, system malfunction, unit breakdown or accidents caused by
failure to follow the instructions.
Revision A:
• 3. SPECIFICATION has been modified.
(The values of COP have been modified.)
• 10. TROUBLESHOOTING has been modified.
Revision B:
• MUZ-FH18NA and MUZ-FH18NAH have been added.
Revision C:
• MUZ-FH06NA, MUZ-FH09/12NA- 1, MUZ-FH18NA2, MUZ-FH06NAH, MUZ-FH09/12NAH- 1 and MUZ-FH18NAH2 have
been added.
Revision D:
• Capacity corrections have been corrected [7-1. 2), 3)].
Indoor air condition (°F)Outdoor air condition (°F)
Dry bulbWet bulbDry bulb Wet bulb
806795(75)
806782(65)
806782(65)
806767(53.5)
806787(69)
70604743
70601715
70606256.5
70604743
70603533
OPERATING RANGE
(1) POWER SUPPLY
Outdoor unit
(2) OPERATION
ModeCondition
Standard temperature806795—
Cooling
Heating
Maximum temperature9073115—
Minimum temperature675714—
Maximum humidity78 %—
Standard temperature70604743
Maximum temperature80677565
Minimum temperature7060-13-14
How to operate with fixed operational frequency of the compressor.
1. Press the EMERGENCY OPERATION switch on the front of the indoor unit, and select either EMERGENCY COOL
mode or EMERGENCY HEAT mode before starting to operate the air conditioner.
2. The compressor starts with operational frequency.
3. The fan speed of the indoor unit is High.
4. This operation continues for 30 minutes.
5. In order to release this operation, press the EMERGENCY OPERATION switch twice or once, or press any button on
the remote controller.
17
Page 18
7-2. PERFORMANCE CURVE
71
67
63
65758595105115
0.1
0.2
0.3
0.4
0.5
Indoor intake air WB temperature (°F)
SHF at rating condition = 0.96
= 381 CFM
Airflow
Outdoor intake air DB temperature (°F)
Total power consumption
(kW)
OBH684D
Cooling
1.5
1.4
1.3
1.2
1.1
difference (°F)
1.0
Capacity correction factors
0.9
Indoor air Wet-bulb temperature
14233241505968778695104 113
Cooling capacity (
Outdoor intake air DB temperature(°F)
MUZ-FH06NA MUZ-FH06NAH
at Rated frequency)
Indoor intake air Wet-bulb
temperature( F)
76
75
72
68
64
MUZ-FH09NA MUZ-FH09NAH
SHF at rating condition = 0.92
0.8
Airflow
= 381 CFM
0.7
0.6
(kW)
0.5
0.4
Total power consumption
Indoor intake air WB temperature (°F)
65758595105115
Outdoor intake air DB temperature (°F)
MUZ-FH12NA MUZ-FH12NAHMUZ-FH15NA MUZ-FH15NAH
SHF at rating condition = 0.83
1.1
1.0
0.9
(kW)
0.8
0.7
0.6
Total power consumption
Indoor intake air WB temperature (°F)
65758595105115
Outdoor intake air DB temperature (°F)
MUZ-FH18NA MUZ-FH18NAH
SHF at rating condition = 0.67
1.8
1.7
1.6
1.5
1.4
(kW)
1.3
1.2
1.1
Total power consumption
This value of frequency is not the same as the actual frequency in operating. Refer to 7-5 and 7-6 for the relationships
between frequency and capacity.
Indoor intake air WB temperature (°F)
65758595105115
Outdoor intake air DB temperature (°F)
= 398 CFM
Airflow
Airflow
= 437 CFM
1.4
71
67
63
1.3
1.2
(kW)
1.1
1.0
0.9
Total power consumption
MUZ-FH18NA2 MUZ-FH18NAH2
1.7
71
67
63
1.6
1.5
1.4
1.3
(kW)
1.2
1.1
1.0
Total power consumption
18
SHF at rating condition = 0.7
65758595105115
Outdoor intake air DB temperature (°F)
SHF at rating condition = 0.67
Indoor intake air WB temperature (°F)
65758595105115
Outdoor intake air DB temperature (°F)
= 411 CFM
Airflow
Indoor intake air WB temperature (°F)
= 437 CFM
Airflow
71
67
63
71
67
63
71
67
63
Page 19
Heating
65
70
75
-5 5 1525354555
65
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
Indoor intake air DB temperature (°F)
= 437 CFM
Airflow
Outdoor intake air WB temperature (°F)
Total power consumption
(kW)
OBH684D
Heating capacity (
1.3
1.2
1.1
1.0
0.9
0.8
0.7
difference (°F)
0.6
0.5
Capacity correction factor
Indoor air Dry-bulb temperature
0.4
-4 5 142332415059
Outdoor intake air WB temperature (°F)
Indoor intake air Dry-bulb temperature ( F)
at Rated frequency)
59
68
79
MUZ-FH06NAMUZ-FH06NAH
= 437 CFM
0.8
Airflow
MUZ-FH09NA
MUZ-FH12NA
MUZ-FH15NA
0.6
(kW)
0.4
Total power consumption
0.2
-5 5 1525354555
0.8
0.6
(kW)
0.4
Total power consumption
0.2
-5 5 1525354555
1.2
0.9
(kW)
0.6
Total power consumption
0.3
-5 5 1525354555
1.50
1.25
1.00
(kW)
0.75
Total power consumption
0.50
-5 5 1525354555
Indoor intake air DB temperature (°F)
Outdoor intake air WB temperature (°F)
Indoor intake air DB temperature (°F)
Outdoor intake air WB temperature (°F)
Indoor intake air DB temperature (°F)
Outdoor intake air WB temperature (°F)
Indoor intake air DB temperature (°F)
Outdoor intake air WB temperature (°F)
Airflow
Airflow
Airflow
= 437 CFM
= 454 CFM
= 454 CFM
75
70
65
65
MUZ-FH09NAH
= 437 CFM
65
70
75
65
1.0
0.9
0.8
0.7
0.6
(kW)
0.5
0.4
Total power consumption
0.3
-5 5 1525354555
Indoor intake air DB temperature (°F)
Outdoor intake air WB temperature (°F)
Airflow
75
70
65
65
MUZ-FH12NAH
= 454 CFM
65
70
75
65
1.1
1.0
0.9
0.8
0.7
(kW)
0.6
0.5
Total power consumption
0.4
-5 5 1525354555
Indoor intake air DB temperature (°F)
Outdoor intake air WB temperature (°F)
Airflow
75
70
65
65
MUZ-FH15NAH
= 497 CFM
65
70
75
65
1.5
1.3
1.1
(kW)
0.9
0.7
Total power consumption
0.5
-5 5 1525354555
Indoor intake air DB temperature (°F)
Outdoor intake air WB temperature (°F)
19
Airflow
75
70
65
65
Page 20
MUZ-FH18NA
OBH684D
2.00
1.75
1.50
1.25
(kW)
1.00
0.75
Total power consumption
0.50
-5 5 1525354555
Airflow
Indoor intake air DB temperature (°F)
Outdoor intake air WB temperature (°F)
= 514 CFM
65
MUZ-FH18NAH
65
70
75
Total power consumption
2.00
1.75
1.50
(kW)
1.25
1.00
0.75
-5 5 1525354555
Indoor intake air DB temperature (°F)
Outdoor intake air WB temperature (°F)
Airflow
= 514 CFM
MUZ-FH18NA2MUZ-FH18NAH2
2.00
1.75
1.50
1.25
(kW)
1.00
0.75
Total power consumption
0.50
-5 5 1525354555
Indoor intake air DB temperature (°F)
Outdoor intake air WB temperature (°F)
Airflow
65
70
75
65
2.00
1.75
1.50
(kW)
1.25
1.00
Total power consumption
0.75
-5 5 1525354555
Indoor intake air DB temperature (°F)
Outdoor intake air WB temperature (°F)
= 514 CFM
This value of frequency is not the same as the actual frequency in operating. Refer to 7-5 and 7-6 for the relationships
between frequency and capacity.
Airflow
= 514 CFM
75
70
65
65
75
70
65
65
7-3. CONDENSING PRESSURE
Cooling
Data are based on the condition of indoor humidity 50 %.
Air flow should be set to High speed.
MUZ-FH06NA MUZ-FH06NAH
(PSIG)
500
450
400
350
Indoor DB temperature (°F)
300
Condensing pressure
250
200
65707580859095 100 105
Outdoor ambient temperature
(PSIG)
190
86
80
75
70
170
150
130
Suction pressure
110
90
(°F)(°F)
Indoor DB temperature (°F)
60 65 70 75 80 85 90 95 100 105
Outdoor ambient temperature
MUZ-FH09NA MUZ-FH09NAH
(PSIG)
500
450
400
350
Indoor DB temperature (°F)
300
Condensing pressure
250
200
65707580859095 100 105
Outdoor ambient temperature
(PSIG)
190
86
80
75
70
170
150
130
Suction pressure
110
90
(°F)(°F)
Indoor DB temperature (°F)
60 65 70 75 80 85 90 95 100 105
Outdoor ambient temperature
20
86
80
75
70
86
80
75
70
Page 21
MUZ-FH12NA MUZ-FH12NAH
OBH684D
(PSIG)
500
450
400
Indoor DB temperature (°F)
350
300
Condensing pressure
250
200
65707580859095 100 105
Outdoor ambient temperature
MUZ-FH15NA MUZ-FH15NAH
(PSIG)
500
450
400
Indoor DB temperature (°F)
350
300
Condensing pressure
250
200
65707580859095 100 105
Outdoor ambient temperature
MUZ-FH18NA MUZ-FH18NAH
(PSIG)
500
(PSIG)
86
80
180
75
70
160
140
120
Suction pressure
100
80
(°F)(°F)
(PSIG)
86
80
180
75
70
160
140
120
Suction pressure
100
80
(°F)(°F)
Indoor DB temperature (°F)
65707580859095 100 105
65707580859095 100 105
Outdoor ambient temperature
Indoor DB temperature (°F)
Outdoor ambient temperature
86
80
75
70
86
80
75
70
450
400
Indoor DB temperature (°F)
350
300
Condensing pressure
250
200
65707580859095 100 105
Outdoor ambient temperature
MUZ-FH18NA2 MUZ-FH18NAH2
(PSIG)
500
450
400
350
300
Condensing pressure
250
200
65707580859095 100 105
Indoor DB temperature (°F)
Outdoor ambient temperature
86
(PSIG)
80
180
75
70
160
140
120
Suction pressure
100
80
(°F)(°F)
(PSIG)
86
80
180
75
70
160
140
120
Suction pressure
100
80
(°F)(°F)
Indoor DB temperature (°F)
65707580859095 100 105
65707580859095 100 105
Outdoor ambient temperature
Indoor DB temperature (°F)
Outdoor ambient temperature
86
80
75
70
86
80
75
70
21
Page 22
Heating
OBH684D
Data are based on the condition of outdoor humidity 75%.
Air flow should be set to High speed.
Data are for heating operation without any frost.
The fan motor turns ON/OFF, interlocking with the compressor.
[ON] The fan motor turns ON 5 seconds before the compressor starts up.
[OFF] The fan motor turns OFF 15 seconds after the compressor has stopped running.
5 seconds15 seconds
ON
Compressor
OFF
ON
Outdoor fan
motor
OFF
8-2. R.V. COIL CONTROL
Heating
Cooling
Dry
NOTE: The 4-way valve reverses for 5 seconds right before start-up of the compressor.
<JS> To change the defrost finish temperature, cut/solder the JS wire of the outdoor inverter P.C. board (Refer to 10-6.1.).
Defrost fi nish temperature
Jumper
MUZ-FH06/09/12NA
MUZ-FH06/09/12NAH
MUZ-FH15/18NA MUZ-FH18NA2
MUZ-FH15/18NAH MUZ-18NAH2
Soldered
(Initial setting)
JS
None
(Cut)
41°F (5°C)50°F (10°C)
50°F (10°C)64°F (18°C)
9-2. PRE-HEAT CONTROL SETTING
MUZ-FH06/09/12
When moisture gets into the refrigerant cycle, it may interfere with the start-up of the compressor at low outside temperature. The pre-heat control prevents this interference. The pre-heat control turns ON when the discharge temperature thermistor is 68°F (20°C) or below. When the pre-heat control turns ON, the compressor is energized. (About 50 W)
MUZ-FH15/18
Prolonged low load operation, in which the thermostat is OFF for a long time, at low outside temperature [32°F (0°C) or
less] may cause the following troubles. To prevent those troubles, activate the pre-heat control.
1) If moisture gets into the refrigerant cycle and freezes, it may interfer the start-up of the compressor.
2) If liquid refrigerant collects in the compressor, a failure in the compressor may occur.
The pre-heat control turns ON when the compressor temperature is 68°F (20°C) or below. When the pre-heat control
turns ON, the compressor is energized. (About 70 W)
Pre-heat control setting
<JK>
ON: To activate the pre-heat control, cut JK wire of the inverter P.C. board.
OFF: To deactivate the pre-heat control, solder JK wire of the inverter P.C. board.
(Refer to 10-6.1)
Pre-heat control setting
Jumper
MUZ-FH06/09/12NA
MUZ-FH06/09/12NAH
MUZ-FH15/18NA MUZ-FH18NA2
MUZ-FH15/18NAH MUZ-18NAH2
Soldered
JK
CutActivated
NOTE: When the inverter P.C. board is replaced, check the jumper wires, and cut/solder them if necessary.
2) Check the indoor/outdoor connecting wire for miswiring.
2. Take care of the following during servicing
1) Before servicing the air conditioner, be sure to turn OFF the main unit first with the remote controller, then after confirming the horizontal vane is closed, turn off the breaker and/or disconnect the power plug.
2) Be sure to turn OFF the power supply before removing the front panel, the cabinet, the top panel, and the electronic
control P.C. board.
3) When removing the electrical parts, be careful of the residual voltage of smoothing capacitor.
4) When removing the electronic control P.C. board, hold the edge of the board with care NOT to apply stress on the
components.
5) When connecting or disconnecting the connectors, hold the connector housing. DO NOT pull the lead wires.
3. Troubleshooting procedure
1)
Check if the OPERATION INDICATOR lamp on the indoor unit is flashing on and off to indicate an abnormality. To make
sure, check how many times the OPERATION INDICATOR lamp is flashing on and off before starting service work.
2) Before servicing, check that the connector and terminal are connected properly.
3) When the electronic control P.C. board seems to be defective, check the copper foil pattern for disconnection and the
components for bursting and discoloration.
4) Refer to 10-2 and 10-3.
29
Page 30
10-2. FAILURE MODE RECALL FUNCTION
OBH684D
Outline of the function
This air conditioner can memorize the abnormal condition which has occurred once.
Even though LED indication listed on the troubleshooting check table (10-3.) disappears, the memorized failure details can be recalled.
1. Flow chart of failure mode recall function for the indoor/outdoor unit
Operational procedure
Setting up the failure mode recall function
Judgment of indoor/outdoor abnormality
The cause of abnormality cannot be found because the abnormality does not recur.
Turn ON the power supply.
<Preparation of the remote controller>
While pressing OPERATION SELECT button and TEMP
controller at the same time, press RESET button.
First, release RESET button.
Hold down the other 2 buttons for another 3 seconds. Make sure that the indicators on
the LCD screen shown in the right fi gure are all displayed. Then release the buttons.
Press STOP/OPERATE (OFF/ON) button of the remote controller (the set temperature
is displayed) with the remote controller headed towards the indoor unit.
Does the left lamp of the OPERATION INDICATOR lamp on
the indoor unit blink at the interval of 0.5 seconds?
Blinks: Either indoor or outdoor unit is abnormal. Beep is emit-
ted at the same timing as the blinking of the left lamp of
the OPERATION INDICATOR lamp.
Before blinking, does the left lamp of the OPERATION INDICATOR lamp stay ON for 3 seconds?
When it stays ON for 3 seconds (without beep): The outdoor unit
The indoor unit is abnormal.
Check the blinking pattern, and identify the abnormal point by referring to the
indoor unit failure mode table. (Refer to indoor unit service manual.)
Make sure to check at least 2 consecutive blinking cycles.
button on the remote
1
1. Regardless of normal or abnormal condition,
a short beep is emitted once the signal is
received.
No
(OFF)
Yes
(Blinks)
No
2
is abnormal.
2
Indoor unit is normal.
But the outdoor unit might be abnormal because there are some abnormalities that cannot be recalled with this way.
Check if outdoor unit is abnormal according to the detailed outdoor unit
failure mode recall function. (Refer to 10-2.2)
Yes
The outdoor unit is abnormal.
Check the blinking pattern, and identify the abnormal point by referring
to the outdoor unit failure mode table. (Refer to 10-2.3)
Make sure to check at least 2 consecutive blinking cycles.
3
Releasing the failure mode recall function
Deleting the memorized abnormal condition
Release the failure mode recall function by the following procedures.
Turn OFF the power supply and turn it ON again.
Press RESET button of the remote controller.
Repair the failure parts.
After repairing the unit, recall the failure mode again according to "Setting up the failure mode recall
function" mentioned above.
Press STOP/OPERATE (OFF/ON) button of the remote controller (the set temperature is displayed)
with the remote controller headed towards the indoor unit.
Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted.
Release the failure mode recall function according to "Releasing the failure mode recall function" men-
tioned above.
NOTE: 1. Make sure to release the failure mode recall function after it is set up, otherwise the unit cannot operate properly.
2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.
2. Blinking pattern when the indoor unit is abnormal:
2.5-second OFF
Blinking at 0.5second interval
2.5-second OFF
Blinking at 0.5second interval
ON
OFF
Repeated cycleRepeated cycle
Beeps
3.Blinking pattern when the outdoor unit is abnormal:
2.5-second OFF3-second ON
Blinking at 0.5second interval
Beeps
Repeated cycle
2.5-second OFF3-second ON
ON
OFF
No beepBeeps
Repeated cycle
No beepBeeps
Repeated cycle
30
Beeps
Blinking at 0.5second interval
Repeated cycle
Page 31
2. Flow chart of the detailed outdoor unit failure mode recall function
OBH684D
Operational procedure
The outdoor unit might be abnormal.
Check if outdoor unit is abnormal according to the following procedures.
Make sure that the remote controller is set to the failure mode recall function.
With the remote controller headed towards the indoor unit, press TEMP
button to adjust the set temperature to 77°F (25°C). 1
Does the left lamp of the OPERATION INDICATOR lamp
on the indoor unit blink at the interval of 0.5 seconds?
Blinks: The outdoor unit is abnormal. Beep is emitted
at the same timing as the blinking of the left
lamp of the OPERATION INDICATOR lamp.
2
The outdoor unit is abnormal.
Check the blinking pattern, and identify the abnormal point by referring to
the outdoor unit failure mode table (10-2.3.).
Make sure to check at least 2 consecutive blinking cycles.
Releasing the failure mode recall function
Release the failure mode recall function by the following procedures.
Turn OFF the power supply and turn it ON again.
Press RESET button of the remote controller.
Repair the failure parts.
Deleting the memorized abnormal condition
After repairing the unit, recall the failure mode again according to "Setting up the failure mode recall
function" (10-2.1.).
Press STOP/OPERATE (OFF/ON) button of the remote controller (the set temperature is displayed) with
the remote controller headed towards the indoor unit.
Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted.
Release the failure mode recall function according to "Releasing the failure mode recall function" men-
tioned above.
Yes
(Blinks
1. Regardless of normal or abnormal condition, 2 short
beeps are emitted as the signal is received.
No
(OFF)
)
The outdoor unit is normal.
2
Release the failure mode recall function according to the left mentioned procedure.
NOTE: 1. Make sure to release the failure mode recall function after it is set up, otherwise the unit cannot operate properly.
2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.
Power module (IC700)
(FH09/12)
IGBT module (IC700)
(FH15/18)
LED indication
(Outdoor P.C. board)
—
—
—
1-time fl ash every
2.5 seconds
2.5 seconds OFF
4-time fl ash
2.5 seconds OFF
2-time fl ash
2.5 seconds OFF
—
2.5 seconds OFF
12-time fl ash
2.5 seconds OFF
—
—
7-time fl ash
2.5 seconds OFF
—
2.5 seconds OFF
6-time fl ash
2.5 seconds OFF
Condition Remedy
Any signals from the inverter P.C.
board cannot be received normally for
3 minutes.
Although the inverter P.C. board
sends signal "0", signal "1" has been
received 30 consecutive times.
Overcurrent protection cut-out
operates 3 consecutive times within
1 minute after the compressor gets
started.
Thermistor shorts or opens during
compressor running.
Large current fl ows into the power
module (IC700) (FH06/09/12)/ IGBT
module (IC700) (FH15/18).
Waveform of compressor current is
distorted.
Temperature of discharge temperature
thermistor exceeds 241°F (116°C),
compressor stops.
Compressor can restart if discharge
temperature thermistor reads
212°F (100°C) or less 3 minutes later.
Temperature indoor coil thermistor
exceeds 158°F (70°C) in HEAT
mode. Temperature defrost thermistor
exceeds 158°F (70°C) in COOL mode.
Temperature of the fi n temperature
thermistor on the inverter P.C. board
exceeds 167 - 187°F (75 - 86°C)
(FH06/09/12)/167 - 176°F (75 - 80°C)
(FH15/18), or temperature of P.C.
board temperature thermistor on the
inverter P.C. board exceeds 162 185°F (72 - 85°C) (FH06/09/12)/158 167°F (70 - 75°C) (FH15/18).
Outdoor fan has stopped 3 times in a
row within 30 seconds after outdoor
fan start-up.
Nonvolatile memory data cannot be
read properly.
The interface short circuit occurs in the
output of the power module (IC700)
(FH06/09/12)/IGBT module (IC700)
(FH15/18).
The compressor winding shorts circuit.
•Refer to 10-5.
to check miswiring and
serial signal error.
•Refer to 10-5.
to check miswiring and
serial signal error.
Reconnect
•
connectors.
Refer to 10-5.
•
to check inverter/
compressor".
Check stop valve.
•
Refer to 10-5.
•
"Check of outdoor
thermistors".
Defective outdoor
thermistors can be
identifi ed by checking
the blinking pattern of
LED.
Reconnect
•
compressor connector.
Refer to 10-5.
•
to check inverter/
compressor".
Check stop valve.
•
Reconnect
•
compressor connector.
Refer to 10-5.
•
to check inverter/
compressor".
Check refrigerant
•
circuit and refrigerant
amount.
Refer to 10-5.
•
of LEV".
Check refrigerant
•
circuit and refrigerant
amount.
Check stop valve.
•
Check around outdoor
•
unit.
Check outdoor unit air
•
passage.
Refer to 10-5.
•
of outdoor fan motor".
Refer to 10-5.
•
of outdoor fan motor".
Refer to 10-5.
of inverter P.C. board".
Replace the inverter
•
P.C. board.
Refer to 10-5.
•
to check inverter/
compressor".
How
How
"How
"How
"How
"Check
"Check
"Check
"Check
"How
Indoor/outdoor
unit failure
mode recall
function
Outdoor unit
failure mode
recall function
○○
○○
○○
—
—
—
—
—
—
○○
NOTE: Blinking patterns of this mode differ from the ones of TROUBLESHOOTING CHECK TABLE (10-3.).
○
○
○
○
○
○
32
Page 33
The left
OBH684D
lamp of the
OPERATION
INDICATOR
lamp
(Indoor unit)
10-time fl ash
2.5 seconds
OFF
11-time fl ash
2.5 seconds
OFF
14-time fl ash
or more
2.5 seconds
OFF
Abnormal point
(Failure mode/protection)
Discharge temperature
DC voltage8-time fl ash
Each phase current of
compressor
Stop valve (Closed valve) 14-time fl ash
4-way valve/
Pipe temperature
Outdoor refrigerant system
abnormality
LED indication
(Outdoor P.C. board)
—
2.5 seconds OFF
9-time fl ash
2.5 seconds OFF
2.5 seconds OFF
16-time fl ash
2.5 seconds OFF
17-time fl ash
2.5 seconds OFF
Condition Remedy
Temperature of discharge temperature
thermistor has been 122°F (50°C) or
less for 20 minutes.
DC voltage of inverter cannot be
detected normally.
Each phase current of compressor
cannot be detected normally.
Closed valve is detected by
compressor current.
The 4-way valve does not work
properly.
The indoor coil thermistor detects an
abnormal temperature.
A closed valve and air trapped in the
refrigerant circuit are detected based
on the temperature sensed by the
indoor and outdoor thermistors and the
current of the compressor.
Refer to 10-5.
•
of LEV".
Check refrigerant
•
circuit and refrigerant
amount.
Refer to 10-5.
•
to check inverter/
compressor".
Check stop valve.
•
Check the 4-way
•
valve.
Replace the inverter
•
P.C. board.
Check for a gas leak
•
in a connecting piping
etc.
Check the stop valve.
•
Refer to 10-5.
•
“Check of outdoor
refrigerant circuit”.
Indoor/outdoor
mode recall
"Check
"How
NOTE: Blinking patterns of this mode differ from the ones of TROUBLESHOOTING CHECK TABLE (10-3.).
unit failure
function
—
—
Outdoor unit
failure mode
recall function
○
○
○○
○○
33
Page 34
10-3. TROUBLESHOOTING CHECK TABLE
OBH684D
No. Symptom LED indication
Outdoor unit
does not operate.
1
2
3
4
5
6
7
'Outdoor unit
stops and
8
restarts 3
minutes later'
is repeated.
9
10
11
12
13
14
15
NOTE: 1. The location of LED is illustrated at the right fi gure. Refer to 10-6.1.
2. LED is lighted during normal operation.
The fl ashing frequency shows the number of times the LED blinks after every 2.5-second OFF.
(Example) When the fl ashing frequency is “2”.
ON
2.5-second OFF
OFF
1-time fl ash every
2.5 seconds
6-time fl ash
2.5 seconds OFF
11-time fl ash
2.5 seconds OFF
16-time fl ash
2.5 seconds OFF
17-time fl ash
2.5 seconds OFF
2-time fl ash
2.5 seconds OFF
3-time fl ash
2.5 seconds OFF
4-time fl ash
2.5 seconds OFF
5-time fl ash
2.5 seconds OFF
8-time fl ash
2.5 seconds OFF
10-time fl ash
2.5 seconds OFF
12-time fl ash
2.5 seconds OFF
13-time fl ash
2.5 seconds OFF
Abnormal point/
Condition
Outdoor power system
Outdoor thermistors Discharge temperature thermistor, fi n temperature thermistor,
Outdoor control system
Serial signal The communication fails between the indoor and outdoor unit
Stop valve/
Closed valve
4-way valve/
Pipe temperature
Outdoor refrigerant
system abnormality
Overcurrent protection
Discharge temperature overheat
protection
Fin temperature
/P.C. board temperature thermistor
overheat protection
High pressure protection
Compressor synchronous abnormality
Outdoor fan motor Outdoor fan has stopped 3 times in a row within 30 seconds
Each phase current
of compressor
DC voltageDC voltage of inverter cannot be detected normally.
0.5-second ON
2.5-second OFF
Overcurrent protection cut-out operates 3 consecutive times
within 1 minute after the compressor gets started.
defrost thermistor, P.C. board temperature thermistor, outdoor
heat exchanger temperature thermistor or ambient temperature thermistor shorts or opens during compressor running.
Nonvolatile memory data cannot be read properly.
(The left lamp of the OPERATION INDICATOR lamp on the
indoor unit lights up or fl ashes 7-time.)
for 3 minutes.
Closed valve is detected by compressor current.
The 4-way valve does not work properly.
The indoor coil thermistor detects an abnormal temperature.
A closed valve and air trapped in the refrigerant circuit are
detected based on the temperature sensed by the indoor and
outdoor thermistors and the current of the compressor.
Large current fl ows into the power module (IC700)
(FH06/09/12)/ IGBT module (IC700) (FH15/18).
Temperature of discharge temperature thermistor exceeds
241°F (116°C), compressor stops. Compressor can restart if
discharge temperature thermistor reads 212°F (100°C) or less
3 minutes later.
Temperature of the fi n temperature thermistor on the heat sink
exceeds 167 - 187°F (75 - 86°C) (FH06/09/12)/167 - 176°F
(75 - 80°C) (FH15/18) or temperature of P.C. board temperature thermistor on the inverter P.C.board exceeds 162 - 185°F
(72 - 85°C) (FH06/09/12)/158 - 167°F (70 - 75°C) (FH15/18).
Indoor coil thermistor exceeds 158°F (70°C) in HEAT mode.
Defrost thermistor exceeds 158°F (70°C) in COOL mode.
The waveform of compressor current is distorted.
after outdoor fan start-up.
Each phase current of compressor cannot be detected normally.
Condition Remedy
0.5-second ON
Reconnect connector of compres-
•
sor.
Refer to 10-5.
•
inverter/compressor".
Check stop valve.
•
Refer to 10-5.
•
thermistors".
Replace inverter P.C. board.
•
Check connection between the in-
•
verter P.C. board and the relay P.C.
board. (FH15/18)
Refer to 10-5.
•
miswiring and serial signal error.
Check stop valve.
•
Refer to 10-5.
•
coil".
Replace the inverter P.C. board.
•
Check for a gas leak in a
•
connecting piping etc.
Check the stop valve.
•
Refer to 10-5.
•
refrigerant circuit”.
Reconnect connector of compressor.
•
Refer to 10-5.
•
inverter/compressor".
Check stop valve.
•
Check refrigerant circuit and refrig-
•
erant amount.
Refer to 10-5.
•
Check around outdoor unit.
•
Check outdoor unit air passage.
•
Refer to 10-5.
•
fan motor".
Check refrigerant circuit and refrig-
•
erant amount.
Check stop valve.
•
Reconnect connector of compressor.
•
Refer to 10-5.
•
inverter/compressor".
Refer to 10-5.
•
fan motor.
Refer to 10-5.
•
P.C. board.
Refer to 10-5.
•
inverter/compressor".
It occurs with following case.
•
Instantaneous power voltage
drop. (Short time power failure)
(FH15/18)
Refer to 10-5.
•
supply". (FH15/18)
Refer to 10-5.
•
verter/compressor".
Inverter P.C. board
MUZ-FH06/09/12NA(H)
Flashing →
MUZ-FH15/18NA(H)
Flashing
"How to check
"Check of outdoor
"How to check
"Check of R.V.
“Check of outdoor
"How to check
"Check of LEV".
"Check of outdoor
"How to check
"Check of outdoor
"Check of inverter
"How to check
"Check of power
"How to check in-
LED
→
LED
34
Page 35
No. Symptom LED indication
OBH684D
Outdoor unit
operates.
16
17
18
19
Outdoor unit
operates.
20
21
22
NOTE: 1. The location of LED is illustrated at the right fi gure. Refer to 10-6.1.
2. LED is lighted during normal operation.
The fl ashing frequency shows the number of times the LED blinks after every 2.5-second OFF.
(Example) When the fl ashing frequency is “2”.
ON
2.5-second OFF
OFF
1-time fl ash
2.5 seconds OFF
3-time fl ash
2.5 seconds OFF
4-time fl ash
2.5 seconds OFF
MUZ-FH06/09/12
5-time fl ash
2.5 seconds OFF
7-time fl ash
2.5 seconds OFF
8-time fl ash
2.5 seconds OFF
9-time fl ash
2.5 seconds OFF
Abnormal point/
Condition
Frequency drop by
current protection
Frequency drop by
high pressure protection
Frequency drop by
defrosting in COOL
mode
Frequency drop by
discharge temperature protection
Outside temperature
thermistor protection
Low discharge temperature protection
MUZ-FH06/09/12
PAM protection
PAM: Pulse Amplitude Modulation
MUZ-FH15/18
Zero cross detecting
circuit
Inverter check mode The connector of compressor is disconnected, inverter check
0.5-second ON
2.5-second OFF
FH06/09/12
FH15/18Current from power outlet is nearing breaker ca-
Temperature of indoor coil thermistor exceeds 131 °F (55°C)
in HEAT mode, compressor frequency lowers.
Indoor coil thermistor reads 46°F (8°C) or less in COOL mode,
compressor frequency lowers.
Temperature of discharge temperature thermistor exceeds
232°F (111°C), compressor frequency lowers.
When the outside temperature thermistor shorts or opens,
protective operation without that thermistor is performed.
Temperature of discharge temperature thermistor has been
122°F (50°C) or less for 20 minutes.
The overcurrent fl ows into PFC (Power factor correction
:IC820) or the DC voltage reaches 394 V or more, PAM stops
and restarts.
Zero cross signal cannot be detected.
mode starts.
When the input current exceeds approximately
10A (FH06/09)/10.5A (FH12), compressor frequency lowers.
pacity.
Condition Remedy
0.5-second ON
The unit is normal, but check the
following.
Check if indoor fi lters are clogged.
•
Check if refrigerant is short.
•
Check if indoor/outdoor unit air
•
circulation is short cycled.
Check refrigerant circuit and refrig-
•
erant amount.
Refer to 10-5.
•
Refer to 10-5.
•
thermistors".
Refer to 10-5.
•
thermistors.
Refer to 10-5.
•
Check refrigerant circuit and refrig-
•
erant amount.
This is not malfunction. PAM protection will be activated in the following cases:
Outdoor heat exchanger
temperature thermistor
(RT68)
Discharge temperature
thermistor (RT62)
Compressor
Measure the resistance with a tester.
Refer to 10-6. “Test point diagram and voltage”, 1. “Inverter P.C.
board”, for the chart of thermistor.
Measure the resistance with a tester. Before measurement, hold the
thermistor with your hands to warm it up.
Refer to 10-6. “Test point diagram and voltage”, 1. “Inverter P.C.
board”, for the chart of thermistor.
Measure the resistance between terminals using a tester.
[Temperature: 14 - 104°F (-10 - 40°C)]
Normal (Ω)
MUZ-FH06/09MUZ-FH12MUZ-FH15/18
U-V
U-W
1.60 - 2.171.66 - 2.260.87 - 1.18
V-W
WHT
V
RED BLK
W
U
Outdoor fan motor
R. V. coil (21S4)
Expansion valve coil
(LEV)
Measure the resistance between lead wires using a tester.
[Temperature: 14 - 104°F (-10 - 40°C)]
Color of lead wire
MUZ-FH06/09/12MUZ-FH15/18
Normal (Ω)
RED – BLK
BLK – WHT
29 - 4012 - 16
WHT – RED
Measure the resistance using a tester.
[Temperature: 14 - 104°F (-10 - 40°C)]
Normal (kΩ)
0.97 - 1.38
Measure the resistance using a tester.
[Temperature: 14 - 104°F (-10 - 40°C)]
Color of lead wire Normal (Ω)
RED – ORN
RED – WHT
RED – BLU
37 - 54
RED – YLW
Measure the resistance using a tester.
[Temperature: 14 - 104°F (-10 - 40°C)]
WHT
V
WHT
ORN
RED
(+12V)
RED BLK
W
U
LEV
YLW
BLU
Defrost heater
Normal (Ω)
MUZ-FH06/09/12NAH
349 - 428376 - 461
36
MUZ-FH15/18NAH
MUZ-FH18NAH2
Page 37
10-5. TROUBLESHOOTING FLOW
OBH684D
A How to check inverter/compressor
Disconnect the connector between the compressor
and the power module (IC700) (MUZ-FH06/09/12)/
IGBT module (IC700) (MUZ-FH15/18).
Check the voltage between terminals.
Are the voltages balanced?
Yes
Check the compressor.
No
See 10-5. “Check of open phase”.
Replace the inverter P.C. board.
See 10-5. “Check of compressor”.
B Check of open phase
● With the connector between the compressor and the power module (IC700) (MUZ-FH06/09/12)/IGBT module (IC700) (MUZ-
FH15/18) disconnected, activate the inverter and check if the inverter is normal by measuring the voltage balance between
the terminals.
Output voltage is 50 - 130 V. (The voltage may differ according to the tester.)
<< Operation method>>
Start cooling or heating operation by pressing EMERGENCY OPERATION switch on the indoor unit. (TEST RUN OPERA-
TION: Refer to 7-6.)
<<Measurement point>>
At 3 points
BLK (U)-WHT (V)
BLK (U)-RED (W)
WHT(V)-RED (W)
Measure AC voltage between the lead wires at 3 points.
NOTE: 1. Output voltage varies according to power supply voltage.
2. Measure the voltage by analog type tester.
3. During this check, LED of the inverter P.C. board fl ashes 9 times. (Refer to 10-6.1.)
C Check of compressor
Refer to 10-5. “Check of compressor
winding”.
Is the compressor normal?
Yes
Refer to 10-5. “Check of compressor
operation time”.
Does the compressor operate continuously?
Yes
OK
No
No
Replace the compressor.
Refer to 10-5. “Check of compressor start failure”.
37
Page 38
D Check of compressor winding
OBH684D
●Disconnect the connector between the compressor and the power module (IC700) (MUZ-FH06/09/12)/IGBT module (IC700)
(MUZ-FH15/18), and measure the resistance between the compressor terminals.
<<Measurement point>>
At 3 points
BLK-WHT
BLK-RED
WHT-RED
<<Judgement>>
Refer to 10-4.
0 [Ω] ················Abnormal [short]
Infinite [Ω] ·······Abnormal [open]
NOTE: Be sure to zero the ohmmeter before measurement.
Measure the resistance between the lead wires at 3 points.
E Check of compressor operation time
<<Judgement>>
● Connect the compressor and activate the inverter. Then measure
the time until the inverter stops due to overcurrent.
<<Operation method>>
Start heating or cooling operation by pressing EMERGENCY
OPERATION switch on the indoor unit. (TEST RUN OPERATION:
Refer to 7-6.)
<<Measurement>>
Measure the time from the start of compressor to the stop of
compressor due to overcurrent.
1
Heat the compressor with
a drier for about 20 minutes.
Do not recover refrigerant
gas while heating.
Heating part
38
Page 39
G Check of outdoor thermistors
OBH684D
Disconnect the connector of thermistor in the inverter P.C. board (see
below table), and measure the resistance of thermistor.
Is the resistance of thermistor normal?
(Refer to 10-6.1.)
Yes
Reconnect the connector of thermistor.
Turn ON the power supply and press EMERGENCY OPERATION switch.
Does the unit operate for 10 minutes or more
without showing thermistor abnormality?
Yes
OK
(Cause is poor contact.)
No
No
Replace the thermistor except RT64.
When RT64 is abnormal, replace the inverter P.C.
board.
Replace the inverter P.C. board.
MUZ-FH06/09/12
Thermistor Symbol Connector, Pin No. Board
DefrostRT61 Between CN641 pin1 and pin2
Discharge temperature RT62 Between CN641 pin3 and pin4
Fin temperature RT64 Between CN642 pin1 and pin2
Ambient temperature RT65 Between CN643 pin1 and pin2
Outdoor heat exchanger temperature RT68 Between CN644 pin1 and pin3
MUZ-FH15/18
Thermistor Symbol Connector, Pin No. Board
DefrostRT61 Between CN671 pin1 and pin2
Discharge temperature RT62 Between CN671 pin3 and pin4
Fin temperature RT64 Between CN673 pin1 and pin2
Ambient temperature RT65 Between CN672 pin1 and pin2
Outdoor heat exchanger temperature RT68 Between CN671 pin5 and pin6
Inverter P.C. board
Inverter P.C. board
39
Page 40
H Check of R.V. coil
OBH684D
MUZ-FH06/09/12
First of all, measure the resistance of R.V. coil to check if the coil is defective. Refer to 10-4.
In case CN721 is disconnected or R.V. coil is open, voltage is generated between the terminal pins of the connector
although no signal is being transmitted to R.V. coil.
Check if CN721 is connected.
Unit operates COOL mode even if it is set to HEAT mode.
Disconnect connector between the
compressor and the power module
(IC700).
Turn ON the power supply and press
EMERGENCY OPERATION switch
twice (HEAT mode).
Is there 208/230 VAC between CN721
and
on the inverter P.C. board
3 minutes after the power supply is turned
ON?
Yes
Replace the 4-way valve.
Replace the inverter
No
P.C. board.
Unit operates HEAT mode even if it is set to COOL mode.
Disconnect connector between the
compressor and the power module
(IC700).
Turn ON the power supply and
press EMERGENCY OPERATION
switch once (COOL mode).
Is there 208/230 VAC between CN721
and
on the inverter P.C. board
3 minutes after the power supply is turned
ON?
No
Replace the inverter
Yes
P.C. board.
Replace the 4-way valve.
MUZ-FH15/18
First of all, measure the resistance of R.V. coil to check if the coil is defective. Refer to 10-4.
In case CN602 is disconnected or R.V. coil is open, voltage is generated between the terminal pins of the connector
although no signal is being transmitted to R.V. coil.
Check if CN602 is connected.
Unit operates COOL mode even if it is set to HEAT mode.
Disconnect connector between the
compressor and the IGBT module
(IC700).
Turn ON the power supply and press
EMERGENCY OPERATION switch
twice (HEAT mode).
Is there 208/230 VAC between CN602
and
on the inverter P.C. board
3 minutes after the power supply is turned
ON?
Yes
Replace the 4-way valve.
Replace the inverter
No
P.C. board.
Unit operates HEAT mode even if it is set to COOL mode.
Disconnect connector between the
compressor and the IGBT module
(IC700).
Turn ON the power supply and
press EMERGENCY OPERATION
switch once (COOL mode).
Is there 208/230 VAC between CN602
and
on the inverter P.C. board
3 minutes after the power supply is turned
ON?
No
Replace the inverter
Yes
P.C. board.
Replace the 4-way valve.
40
Page 41
I Check of outdoor fan motor
OBH684D
Disconnect the connectors CN931
and CN932 from the inverter P.C.
board.
Check the connection between the
connector CN931 and CN932.
Is the resistance between each terminal of outdoor fan motor normal?
(Refer to 10-4.)
No
Yes
Disconnect CN932 from the inverter P.C. board, and turn on the
power supply.
Rotate the outdoor fan motor manually and measure the voltage
of CN931.
Between 1(+) and 5(-)
Between 2(+) and 5(-)
Between 3(+) and 5(-)
(Fixed to either 5 or 0 VDC)
Replace the outdoor fan motor.
Does the voltage between each terminal become 5 and 0
No
VDC repeatedly?
Yes
Does the outdoor fan motor rotate smoothly?
No
Replace the inverter P.C. board.
Yes
41
Page 42
J Check of power supply
OBH684D
Disconnect the connector between the
compressor and the power module
Turn ON power supply and press
EMERGENCY OPERATION switch.
Does the left lamp of the
OPERATION INDICATOR lamp on
the indoor unit light up?
Yes
Is there DC voltage 260 - 370 VDC
between DB61 (+) and DB61 (–)
(MUZ-FH06/09/12)/294 - 370 VDC
between JP715 (+) and JP30 (–)
(MUZ-FH15/18) on the inverter P.C.
board? (Refer to 10-6.1.)
No
Check the electric parts in main circuit.
No
Yes
Rectify indoor/outdoor
connecting wire.
Yes
Is there voltage 208/230 VAC
between the indoor terminal
block S1 and S2?
Does LED on the inverter P.C.
board light up or fl ash?
(Refer to 10-6.1.)
Yes
If lights up, OK.
If fl ashes, refer to 10-3.
Replace the indoor
electronic control P.C.
No
board.
Replace the inverter
No
P.C. board.
DB61
Inverter P.C. board
(Solder side)
260 - 370 VDC
294 -370 VDC
MUZ-FH06/09/12
JP30
JP715
MUZ-FH15/18
42
Page 43
K Check of LEV (Expansion valve)
OBH684D
Turn ON the power supply.
<Preparation of the remote controller>
While pressing both OPERATION SELECT button
and TEMP button on the remote controller at the
same time, press RESET button.
First, release RESET button.
Hold down the other 2 buttons for another 3 seconds.
Make sure that the indicators on the LCD screen
shown in the right fi gure are all displayed. Then re-
lease the buttons.
Press STOP/OPERATE (OFF/ON) button of the remote
controller (the set temperature is displayed) with the
remote controller headed towards the indoor unit.
Expansion valve operates in full-opening direction.
Do you hear the expansion valve "click,
click·······"?
Do you feel the expansion valve vibrate
when touching it ?
No
Yes
1
OK
1. Regardless of normal or abnormal condition, a short beep
is emitted once the signal is received.
Is LEV coil properly fi xed to
the expansion valve?
Yes
Does the resistance of LEV
coil have the characteristics?
(Refer to 10-4.)
No
Replace the LEV coil.
NOTE: After check of LEV, do the undermentioned operations.
1. Turn OFF the power supply and turn it ON again.
2. Press RESET button on the remote controller.
No
Yes
Properly fi x the LEV coil to the expansion valve.
Measure each voltage between connector
pins of CN724 on the inverter P.C. board.
1. Pin (-) — Pin (+)
2. Pin (-) — Pin (+)
3. Pin (-) — Pin (+)
4. Pin (-) — Pin (+)
Is there about 3 - 5 VAC between each?
NOTE: Measure the voltage by an analog
tester.
Replace the expansion valve.
Yes
Replace the inverter P.C.
No
board.
43
Page 44
L Check of inverter P.C. board
OBH684D
Check the outdoor fan motor.
(Refer to 10-5.
.)
Is the fuse (F901) blown on the inverter P.C. board?
No
Check the connection of the connectors
(CN931, CN932) of the outdoor fan motor.
If the connection is poor, make it correct.
Operate the outdoor unit by starting
EMERGENCY OPERATION.
Check the LED indication on the inverter P.C. board.
Does the LED fl ash 10 times?
Yes
(10-time fl ash)
Replace the inverter P.C. board.
Yes
No
Check the corresponding parts
following LED indication.
(Refer to 10-3.)
44
Page 45
M How to check miswiring and serial signal error
OBH684D
Turn OFF the power supply.
NOTE: Refer to the indoor unit service manual.
Is there rated voltage in the power supply?
Turn ON the power supply.
Is there rated voltage between the outdoor terminal block S1 and S2?
Press EMERGENCY OPERATION switch once.
Does the left lamp of OPERATION INDICATOR
lamp light up? <Confi rmation of the power to
the indoor unit>
Is serial signal error indicated 6 minutes later?
Turn OFF the power supply.
Check once more if the indoor/outdoor
B
connecting wire is not miswiring.
Bridge the outdoor terminal block S2 and
1
S3.
Turn ON the power supply.
Is the bus-bar voltage of the inverter P.C. board normal?
(Refer to "TEST POINT DIAGRAM AND VOLTAGE" in the outdoor service manual.)
Yes
Yes
Yes
Yes
A
Yes
No
No
No
1. Miswiring may damage indoor electronic control P.C.
3. Be sure to check this within 3 minutes after turning ON.
Check the power supply.
No
Check the wiring.
Is there any miswiring,
poor contact, or wire
disconnection of the
indoor/outdoor connecting wire?
board during the operation.
Be sure to confi rm the wiring is correct before the opera-
tion starts.
After 3 minutes, LED blinks 6 times. Even when the
inverter P.C. board is normal, LED blinks 6 times after 3
minutes.
No
No
Check of power supply.
(Refer to the outdoor
service manual.)
Yes
Correct them.
Does the LED on the inverter P.C. board repeat
"3.6-second-OFF and 0.8-second-ON quick blinking"?
Turn OFF the power supply.
Remove the bridge between the outdoor terminal block S2 and S3.
Turn ON the power supply.
Is there rated voltage between the indoor terminal block S1 and S2?
<Confi rmation of power voltage>
Is there amplitude of 10 to 20 VDC between the indoor terminal block
S2 and S3? <Confi rmation of serial signal>
Yes
A
• Reinstall
• Attach a fi lter
No
either the unit
or the light
away from
each other.
on remote
control receiving section
of the indoor
unit.
• Turn OFF inverter-controlled lighting
equipment.
• Turn OFF the power supply and then
turn ON again.
• Press EMERGENCY OPERATION
switch.
Is serial signal
error indicated 6
minutes later?
B
3
Yes
Yes
Yes
Is there 2 VDC or less between CN202 (+)
and JPG (GND)(-) on the indoor electronic
control P.C. board?
Yes
Is there 2 VDC or less between
CN202A (+) and JPG (GND)(-)
on the indoor electronic control P.C.
board?
Replace the indoor power
P.C. board.
No
NoYesNo
No
(Lighted
or not
lighted)
No
No
Replace the indoor electronic control P.C. board.
45
Replace the inverter P.C. board . 2
2. Be careful of the residual voltage of
smoothing capacitor.
Check the wiring
If there are any error of the indoor/outdoor connecting wire:
such as the damage of the wire, intermediate connection,
and/or poor contact to the terminal block, replace the indoor/
outdoor connecting wire.
Is there 2 VDC or less between
CN202 (+) and JPG (GND)(-) on
the indoor electronic control P.C.
board?
Check the following points before checking electric continuity.
1. Does the resistance of ambient temperature thermistor have the characteristics? Refer to 10-6.1.
2. Is the resistance of defrost heater normal? Refer to 10-4.
3. Does the heater protector remain conducted (not open)?
4. Are both ambient temperature thermistor and circuit of defrost heater securely connected to connectors?
In HEAT mode, for more than 5 minutes, let the ambient temperature thermistor continue to read
32°F (0°C) or below, and let the defrost thermistor continue to read 30°F (-1°C) or below.
NOTE: In case both thermistors are more than the above temperature, cool them with cold
water etc...
Is there 208/230 VAC between CN722 and
(MUZ-FH06/09/12)/CN601 and (MUZ-
FH15/18) on the inverter P.C. board? Refer to
10-6.1.
No
Replace the inverter P.C. board.
Yes
Not the problem of the inverter P.C. board.
O Check of outdoor refrigerant circuit
Has the operation stopped
during pump down?
Yes
The operation has stopped to prevent the diesel explosion caused by
air trapped in the refrigerant circuit.
Close the stop valve, and disconnect
the power plug or turn the breaker
OFF.
CAUTION : Do not start the opera-
tion again to prevent
hazards.
Was the operation started with
No
the stop valve closed, and was
it opened during operation?
No
The refrigerant gas amount may be
60% or less than the normal amount.
Identify where the gas is leaking from,
and fi x the leak.
The unit occasionally stops when the
stop valve is opened or closed during
operation. Open the stop valve and
Yes
start the cooling operation again.
46
Page 47
P Electromagnetic noise enters into TV sets or radios
OBH684D
Is the unit grounded?
Yes
Is the distance between the antennas
and the indoor unit within 9.91 ft.
or is the distance between the antennas
and the outdoor unit within 9.91 ft.
No
Is the distance between the TV sets or radios and the indoor unit within 3.28 ft.
or is the distance between the TV sets or
radios and the outdoor unit within
9.91 ft.
(3m)
?
No
Are the antennas damaged?
Is the coaxial cable damaged?
Is there any poor contact in the antenna wiring?
No
Is the indoor/outdoor connecting wire
of the air conditioner and the wiring of
the antennas close?
No
(3m)
(3m)
(1m)
No
,
Yes
?
,
Yes
Yes
Yes
Ground the unit.
Extend the distance between the antennas and
the indoor unit, and/or the antennas and the
outdoor unit.
Extend the distance between the TV sets and/or
radios and the indoor unit, or the TV sets or
radios and the outdoor unit.
Replace or repair the antenna.
Replace or repair the coaxial cable.
Extend the distance between the indoor/outdoor
connecting wire of the air conditioner and the wiring of the antennas.
Even if all of the above conditions are fulfi lled, the electromagnetic noise may enter, depending on the electric fi eld strength
or the installation condition (combination of specifi c conditions such as antennas or wiring).
Check the following before asking for service.
1. Devices affected by the electromagnetic noise
TV sets, radios (FM/AM broadcast, shortwave)
2. Channel, frequency, broadcast station affected by the electromagnetic noise
3. Channel, frequency, broadcast station unaffected by the electromagnetic noise
4. Layout of:
indoor/outdoor unit of the air conditioner, indoor/outdoor wiring, ground wire, antennas, wiring from antennas, receiver
5. Electric fi eld intensity of the broadcast station affected by the electromagnetic noise
6. Presence or absence of amplifi er such as booster
7. Operation condition of air conditioner when the electromagnetic noise enters in
1) Turn OFF the power supply once, and then turn ON the power supply. In this situation, check for the electromagnetic
noise.
2) Within 3 minutes after turning ON the power supply, press STOP/OPERATE (OFF/ON) button on the remote controller
for power ON, and check for the electromagnetic noise.
3) After a short time (3 minutes later after turning ON), the outdoor unit starts running. During operation, check for the
electromagnetic noise.
4) Press STOP/OPERATE (OFF/ON) button on the remote controller for power OFF, when the outdoor unit stops but the
indoor/outdoor communication still runs on. In this situation, check for the electromagnetic noise.
47
Page 48
10-6. TEST POINT DIAGRAM AND VOLTAGE
OBH684D
1. Inverter P.C. board
MUZ-FH06NA MUZ-FH06NAH MUZ-FH09NA
(+)
1
-
Smoothing
capacitor (C62)
Fuse (F801)
T3.15AL250V
MUZ-FH12NA
Back side of unit
208/230 VAC
Fuse (F901)
T3.15AL250V
Output to
drive outdoor
fan motor
(CN932)
Output to
drive
compressor
(LDU,
LDV,
LDW)
-1 MUZ-FH12NAH
DB61
260 - 370 VDC
(-)
-1 MUZ-FH09NAH
R.V.coil
Smoothing
capacitor (C61)
(CN721)
208/230 VAC
-1
Heater connector
(CN722)
(MUZ-FH06NAH
MUZ-FH09/12NAH-
Fuse (F701)
T3.15AL250V
208/230
VAC
1
)
LED
Front side of unit
Fin temperature
thermistor/RT64
(CN642)
Signal of outdoor
fan motor (CN931)
Defrost thermistor(RT61)
Ambient temperature thermistor(RT65)
Outdoor heat exchanger temperature thermistor(RT68)
100
90
80
70
60
50
40
30
5HVLVWDQFHN
20
10
0
-414 32506886 104
Temperature(°F)
Defrost thermistor
/RT61(CN641)
Ambient temperature
thermistor/RT65
(CN643)
Discharge temperature thermistor (RT62)
800
700
600
500
400
300
5HVLVWDQFHN
200
100
0
32 50 68 86 104 122 140 158 176 194 212 230 248
Discharge temperature
thermistor/RT62
(CN641)
Outdoor heat exchanger
temperature thermistor
Temperature (°F)
48
/RT68 (CN644)
LEV connector
(CN724)
Jumper wire for
changing defrost
setting (JS)
Jumper wire
for pre-heat
control setting
(JK)
Fin temperature thermistor(RT64)
200
180
160
140
120
100
80
60
5HVLVWDQFHN
40
20
0
32 50 68 86 104 122 140 158 176
Temperature(°F)
Page 49
MUZ-FH09NA MUZ-FH09NAH MUZ-FH12NA MUZ-FH12NAH
OBH684D
Back side of unit
208/230 VAC
Fuse (F901)
T3.15AL250V
Output to
drive outdoor
fan motor
(CN932)
Output to
drive
compressor
(LDU,
LDV,
LDW)
DB61
260 - 370 VDC
(-)
(+)
Smoothing
capacitor
(C62)
Fuse (F801)
T3.15AL250V
Smoothing
capacitor
(C61)
R.V.coil
(CN721)
208/230 VAC
Heater connector
(CN722) (MUZ-FH09/12NAH)
Fuse (F701)
T3.15AL250V
208/230
VAC
LED
Front side of unit
Fin temperature
thermistor/RT64
(CN642)
Signal of outdoor
fan motor (CN931)
Defrost thermistor(RT61)
Ambient temperature thermistor(RT65)
Outdoor heat exchanger temperature thermistor(RT68)
100
90
80
70
60
50
40
30
5HVLVWDQFHN
20
10
0
-414 32506886 104
Temperature(°F)
Defrost thermistor
/RT61(CN641)
Ambient temperature
thermistor/RT65
(CN643)
Discharge temperature thermistor (RT62)
800
700
600
500
400
300
5HVLVWDQFHN
200
100
0
32 50 68 86 104 122 140 158 176 194 212 230 248
Discharge temperature
thermistor/RT62
(CN641)
Outdoor heat exchanger
temperature thermistor
Temperature (°F)
49
/RT68 (CN644)
LEV connector
(CN724)
Jumper wire for
changing defrost
setting (JS)
Jumper wire
for pre-heat
control setting
(JK)
Fin temperature thermistor(RT64)
200
180
160
140
120
100
80
60
5HVLVWDQFHN
40
20
0
32 50 68 86 104 122 140 158 176
Temperature(°F)
Page 50
MUZ-FH15NA
-414 32506886 104
0
10
20
30
40
50
60
70
80
90
100
Temperature(°F)
Defrost thermistor(RT61)
Ambient temperature thermistor(RT65)
Outdoor heat exchanger temperature thermistor(RT68)
Outdoor heat exchanger
temperature thermistor
/RT68 (CN671)
Ambient temperature
thermistor/RT65
(CN672)
Fin temperature
thermistor/RT64
(CN673)
Jumper wire for
changing defrost
setting (JS)
Jumper wire for
pre-heat control
setting (JK)
50
Page 51
11
OBH684D
DISASSEMBLY INSTRUCTIONS
<"Terminal with locking mechanism" Detaching points>
The terminal which has the locking mechanism can be detached as shown below.
There are 2 types (refer to (1) and (2)) of the terminal with locking mechanism.
The terminal without locking mechanism can be detached by pulling it out.
Check the shape of the terminal before detaching.
(1) Slide the sleeve and check if there is a locking lever or not.(2) The terminal with this connector has the
Sleeve
locking mechanism.
Locking lever
Slide the sleeve.
Pull the terminal while
pushing the locking
lever.
Hold the sleeve, and
pull out the terminal
slowly.
NOTE: Turn OFF the power supply before disassembly.
OPERATING PROCEDUREPHOTOS
1. Removing the cabinet
(1) Remove the screw fixing the service panel.
(2) Pull down the service panel and remove it.
(3) Remove the screws fixing the conduit cover.
(4) Remove the conduit cover. (Photo 4)
(5) Remove the screw fixing the conduit plate. (Photo 5)
(6) Remove the conduit plate.
(7) Disconnect the power supply wire and indoor/outdoor
connecting wire.
(8) Remove the screws fixing the top panel.
(9) Remove the top panel.
(
10
) Remove the screws fixing the cabinet.
(
11
) Remove the cabinet.
(
12
) Remove the screws fixing the back panel.
(
13
) Remove the back panel.
Photo 1
Screws of
the top panel
Back
panel
Screws
of the
back
panel
Photo 2
Screws of the
top panel
Screws of the
cabinet
Photo 3
51
Screws of
the cabinet
Screws of
the cabinet
Screw of the
cabinet
Service
panel
Screws of
the terminal block
support and the
back panel
Direction
to remove
Hooks
Page 52
OPERATING PROCEDUREPHOTOS
OBH684D
Photo 4Photo 5
Screws of the
conduit cover
Screw of the
conduit plate
2. Removing the inverter assembly, inverter P.C. board
(1) Remove the cabinet and panels. (Refer to 1.)
(2) Disconnect the lead wire to the reactor and the following
connectors:
<Inverter P.C. board>
CN721 (R.V. coil)
CN722 (Defrost heater and heater protector) (MUZ-
FH06/09/12NAH)
CN931, CN932 (Fan motor)
CN641 (Defrost thermistor and discharge temperature ther-
mistor)
CN643 (Ambient temperature thermistor)
CN644 (Outdoor heat exchanger temperature thermistor)
CN724 (LEV)
(3) Remove the compressor connector (CN61).
(4) Remove the screws fixing the heat sink support and the
separator.
(5) Remove the fixing screws of the terminal block support and
the back panel.
(6) Remove the inverter assembly.
(7) Remove the screw of the ground wire and screw of the ter-
minal block support.
(8) Remove the heat sink support from the P.C. board support.
(9) Remove the screw of the inverter P.C. board and remove the
inverter P.C. board from the P.C. board support.
3. Removing R.V. coil
(1) Remove the cabinet and panels. (Refer to 1.)
(2) Disconnect the following connectors:
<Inverter P.C. board>
CN721 (R.V. coil)
(3) Remove the R.V. coil.
Photo 6
Screws of the heat sink
support and the separator
Photo 7
Heat sink
Heat sink support
P.C. board
support
Screws of the terminal block
support and the back panel
Screw of the
Terminal block
support
52
Screw of the
inverter P.C. board
Terminal
block
support
Screw of the
ground wire
Page 53
OPERATING PROCEDUREPHOTOS
OBH684D
4. Removing the discharge temperature thermistor,
defrost thermistor, outdoor heat exchanger temperature thermistor and ambient temperature thermistor
(1) Remove the cabinet and panels. (Refer to 1.)
(2) Disconnect the lead wire to the reactor and the following con-
nectors:
<Inverter P.C. board>
CN641 (Defrost thermistor and discharge temperature ther-
mistor)
CN643 (Ambient temperature thermistor)
CN644 (Outdoor heat exchanger temperature thermistor)
(3) Pull out the discharge temperature thermistor from its holder.
(4) Pull out the defrost thermistor from its holder. (Photo 6)
(5) Pull out the outdoor heat exchanger temperature thermistor
from its holder. (Photo 6)
(6) Pull out the ambient temperature thermistor from its holder.
Photo 8
Discharge temperature thermistor
Screw of the
R.V. coil
Photo 9
Photo 10
Outdoor heat
exchanger temperature thermistor
Defrost thermistor
Ambient temperature
thermistor
53
Page 54
OPERATING PROCEDURE
OBH684D
5. Removing outdoor fan motor
(1) Remove the cabinet and panels. (Refer to 1.)
(2) Disconnect the following connectors:
<Inverter P.C. board>
CN931, CN932 (Fan motor)
(3) Remove the propeller fan nut.
(4) Remove the propeller fan.
(5) Remove the screws fixing the fan motor.
(6) Remove the fan motor.
PHOTOS
Photo 11
Screws of the outdoor fan motor
6. Removing the compressor and 4-way valve
(1) Remove the cabinet and panels. (Refer to 1.)
(2) Remove the inverter assembly. (Refer to 2.)
(3) Remove the screws fixing the reactor.
(4) Remove the reactor.
(5) Remove the soundproof felt.
(6) Recover gas from the refrigerant circuit.
NOTE: Recover gas from the pipes until the pressure gauge
shows 0 PSIG.
(7) Detach the brazed part of the suction and the discharge pipe
connected with compressor.
(8) Remove the nuts fixing the compressor.
(9) Remove the compressor.
(
10
) Detach the brazed part of pipes connected with 4-way valve.
NOTE: Turn OFF the power supply before disassembly.
OPERATING PROCEDURE
1. Removing the cabinet
(1) Remove the screws of the service panel.
(2) Remove the screws of the top panel.
(3) Remove the screw of the valve cover.
(4) Remove the service panel.
(5) Remove the screws fixing the conduit cover.
(6) Remove the conduit cover.
(7) Remove the screw of fixing the conduit plate.
(8) Remove the conduit plate.
(9) Remove the top panel.
(10)
Remove the valve cover.
(11)
Disconnect the power supply and indoor/outdoor connect-
ing wire.
(12)
Remove the screws of the cabinet.
(13)
Remove the cabinet.
(14)
Remove the screws of the back panel.
(15)
Remove the back panel.
Photo 2
Screws of the top panel
Screw of the back panel
Screws of the
cabinet
Photo 1
Screws of the top panel
Screws of the
cabinet
Photo 3
Screws of the conduit cover
PHOTOS
Screws of the
cabinet
Screws of
the cabinet
Screw of the
valve cover
Screws of the
service panel
Photo 4
Screw of the conduit plate
Screws of the
back panel
55
Page 56
OPERATING PROCEDURE
OBH684D
PHOTOS
2. Removing the inverter assembly, inverter P.C. board
and relay P.C. board
(1) Remove the cabinet and panels. (Refer to 1.)
(2) Disconnect the lead wire to the reactor and the following con-
and outdoor heat exchanger temperature thermistor)
CN672 (Ambient temperature thermistor)
CN724 (LEV)
CN601 (Defrost heater and heater protector)
(MUZ-FH15/18NAH/18NAH2)
(3) Remove the compressor connector.
(4) Remove the screws fixing the relay panel.
(5) Remove the relay panel.
(6) Remove the ground wires and the lead wires of the inverter
P.C. board.
(7) Remove the screws of the P.B. support.
(8) Remove the inverter P.C. board from the P.B. support.
Photo 5
Inverter P.C.
board
Screws of
the P.B.
support
Screw of the
relay panel
Screw of the
relay panel
Ground wires
Screw of the
relay panel
Screws of the
P.B. support
3. Removing R.V. coil
(1) Remove the cabinet and panels. (Refer to 1.)
(2) Disconnect the following connector:
<Inverter P.C. board>
CN602 (R.V. coil)
(3) Remove the R.V. coil.
Photo 6
Screw of the
R.V. coil
Brazed parts of
4-way valve
56
Page 57
OPERATING PROCEDUREPHOTOS
OBH684D
4. Removing the discharge temperature thermistor,
defrost thermistor, outdoor heat exchanger temperature thermistor and ambient temperature thermistor
(1) Remove the cabinet and panels. (Refer to 1.)
(2) Disconnect the lead wire to the reactor and the following
connectors:
<Inverter P.C. board>
CN671 (Defrost thermistor, discharge temperature thermis-
tor and outdoor heart exchanger temperature thermistor)
CN672 (Ambient temperature thermistor)
(3)
Pull out the discharge temperature thermistor from its holder.
(4) Pull out the defrost thermistor from its holder.
(5) Pull out the outdoor heat exchanger temperature thermistor
from its holder.
(6) Pull out the ambient temperature thermistor from its holder.
5. Removing outdoor fan motor
(1)
Remove the top panel, cabinet and service panel. (Refer to 1.)
(2) Disconnect the following connectors:
<Inverter P.C. board>
CN931 and CN932 (Fan motor)
(3) Remove the propeller fan.
(4) Remove the screws fixing the fan motor.
(5) Remove the fan motor.
Photo 7
Outdoor heat exchanger
temperature thermistor
Photo 8
Ambient temperature
thermistor
Defrost thermistor
6. Removing the compressor and 4-way valve
(1)
Remove the top panel, cabinet and service panel. (Refer to 1.)
(2) Remove the back panel. (Refer to 1.)
(3) Remove the inverter assembly. (Refer to 2.)
(4) Remove the soundproof felt.
(5) Recover gas from the refrigerant circuit.
NOTE: Recover gas from the pipes until the pressure gauge
shows 0 PSIG.
(6) Detach the brazed part of the suction and the discharge
pipe connected with compressor.
(7) Remove the nuts fixing the compressor.
(8) Remove the compressor.
(9) Detach the brazed parts of 4-way valve and pipe. (Photo 4)
57
Photo 9
Brazed part of the
suction pipe
Screws of the
outdoor fan motor
Discharge temperature
thermistor
Soundproof felt
Brazed part of the
discharge pipe
Page 58
HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN