Mitsubishi Electronics MUZ-FH06NA, MUZ-FH09NA, MUZ-FH12NA, MUZ-FH15NA, MUZ-FH18NA User Manual

...
Page 1
HFC
utilized
R410A
OUTDOOR UNIT
SERVICE MANUAL
Models
Revision D:
• Capacity corrections have been corrected [7-1. 2), 3)].
OBH684 REVISED EDITION-C is void.
No. OBH684
REVISED EDITION-D
MUZ-FH06NA MUZ-FH09NA
MUZ-FH09NA
-
MUZ-FH12NA MUZ-FH12NA
-
MUZ-FH15NA MUZ-FH18NA MUZ-FH18NA2
MUZ-FH06NAH MUZ-FH09NAH
1
MUZ-FH09NAH
-
1
MUZ-FH12NAH
1
MUZ-FH12NAH
-
1
MUZ-FH15NAH MUZ-FH18NAH MUZ-FH18NAH2
Indoor unit service manual MSZ-FH•NA Series (OBH683)
CONTENTS
1. TECHNICAL CHANGES ······························2
2. PART NAMES AND FUNCTIONS ··················3
4. OUTLINES AND DIMENSIONS ·····················6
5. WIRING DIAGRAM ·····································8
6. REFRIGERANT SYSTEM DIAGRAM ···········14
7. DATA······················································16
8. ACTUA TOR CONTROL ·····························27
9. SERVICE FUNCTIONS ······························28
10. TROUBLESHOOTING ······························· 29
11. DISASSEMBLY INSTRUCTIONS ·················51
MUZ-FH06NA MUZ-FH09NA MUZ-FH12NA
NOTE:
RoHS compliant products have <G> mark on the spec name plate.
MUZ-FH06NAH MUZ-FH09NAH MUZ-FH12NAH
PARTS CATALOG (OBB684)
Page 2
Use the specifi ed refrigerant only
OBH684D
Never use any refrigerant other than that specified.
Doing so may cause a burst, an explosion, or fire when the unit is being used, serviced, or disposed of. Correct refrigerant is specified in the manuals and on the spec labels provided with our products. We will not be held responsible for mechanical failure, system malfunction, unit breakdown or accidents caused by failure to follow the instructions.
Revision A:
• 3. SPECIFICATION has been modified. (The values of COP have been modified.)
• 10. TROUBLESHOOTING has been modified.
Revision B:
• MUZ-FH18NA and MUZ-FH18NAH have been added.
Revision C:
• MUZ-FH06NA, MUZ-FH09/12NA- 1, MUZ-FH18NA2, MUZ-FH06NAH, MUZ-FH09/12NAH- 1 and MUZ-FH18NAH2 have been added.
Revision D:
• Capacity corrections have been corrected [7-1. 2), 3)].
1
TECHNICAL CHANGES
MUZ-FH09NA MUZ-FH09NAH MUZ-FH12NA MUZ-FH12NAH MUZ-FH15NA MUZ-FH15NAH
1. New model
MUZ-FH18NA MUZ-FH18NAH
1. New model
MUZ-FH06NA MUZ-FH06NAH
1. New model
MUZ-FH09NA MUZ-FH12NA
1. Model name has been changed.
2. New service part numbers have been set. (Refer to OBB684, 1-2.)
MUZ-FH18NA
1. Model name has been changed.
MUZ-FH09NA ­MUZ-FH12NA -
MUZ-FH18NA2
1
MUZ-FH09NAH
1
MUZ-FH12NAH
MUZ-FH18NAH
MUZ-FH09NAH ­MUZ-FH12NAH -
MUZ-FH18NAH2
1
1
2
Page 3
2
OBH684D
PART NAMES AND FUNCTIONS
MUZ-FH06NA MUZ-FH06NAH MUZ-FH09NA MUZ-FH09NAH MUZ-FH12NA MUZ-FH12NAH
(back and side)
Air inlet
Piping
Air outlet
Drain hose
Drain outlet
MUZ-FH15NA MUZ-FH15NAH MUZ-FH18NA MUZ-FH18NAH MUZ-FH18NA2 MUZ-FH18NAH2
(back and side)
Drain hose
Air outlet
Drain outlet
Air inlet
Piping
3
Page 4
3
OBH684D
SPECIFICATION
Outdoor unit model
Capacity
Cooling 1
Rated (Minimum~Maximum)
Capacity
Rated (Maximum)
Power consumption
Rated (Minimum~Maximum)
Power consumption
Rated (Maximum)
1
EER
HSPF IV
[SEER] 3 Cooling 19.1 [33.1] 16.1 [30.5] 13.8 [26.1] 12.5 [22.0] 12.0 [21.0] 12.5 [21.0]
4
Heating 47 1
Heating 17 2
Cooling 1
Heating 47 1
Heating 17 2
Heating
COP Heating
MUZ-FH06NA
MUZ-FH06NAH
Btu/h
Btu/h
Btu/h
W
W
W
6,000
(1,700 ~ 9,000)
8,700
(1,600 ~ 14,000)
5,900 (10,700) 6,700 (12,200) 8,000(13,600) 11,000 (18,000) 13,700 (20,300)
315
(100 ~ 560)
545
(110 ~ 1,270)
500
(1,000) 600 (1,440) 720 (1,900) 1,020 (2,480) 1,320 (2,800)
NA: 13.5 NA: 13.5 NA: 12.5 NA: 12.0 NA: 12.0 NA2: 12.0
NAH: 12.5 NAH: 12.5 NAH: 11.5 NAH: 11.0 NAH: 11.0 NAH2: 11.0
1 4.68 4.50 4.20 4.06 3.46
MUZ-FH09NA
MUZ-FH09NAH
MUZ-FH12NAH
9,000
(1,700 ~ 12,000)
(2,500 ~ 13,600)
10,900
(1,600 ~ 18,000)
(3,700 ~ 21,000)
560
(100 ~ 1,000)
710
(110 ~ 1,470)
MUZ-FH12NA
12,000
13,600
870
(170 ~ 1,150)
950
(280 ~ 2,300)
MUZ-FH15NA
MUZ-FH15NAH
MUZ-FH18NAH
15,000
(6,450 ~ 19,000)
18,000
(5,150 ~ 24,000)
1,200
(410 ~ 2,200)
1,300
(430 ~ 3,360)
MUZ-FH18NA
(6,450 ~ 21,000)
(5,150 ~ 30,000)
1,430
(410 ~ 2,220)
(430 ~ 3,390)
Power supply V , phase , Hz 208/230, 1 , 60 Max. fuse size (time delay) A 15 20 Min. circuit ampacity A 11 16 Fan motor F.L.A 0.50 0.93
Compressor
Model
R.L.A 8.2 12.0 L.R.A 10.3 15.0
Refrigeration oil L (Model)
SNB092FQAMT SNB140FQUMT
SNB172FQKMT
0.35 (FV50S) 0.35 (FV50S) 0.40 (FV50S)
Refrigerant control Linear expansion valve
Sound level
Cooling dB(A) 47 48 49 51 52
1
Heating dB(A) 48 49 51 55 55
Defrost method Reverse cycle
W in. 31-1/2 33-1/16
Dimensions
D in. 11-1/4 13 H in. 21-5/8 34-5/8
Weight Ib. 81 83 124 External fi nish Munsell 3Y 7.8/1.1 Remote controller Wireless type Control voltage (by built-in transformer) VDC 12 - 24 Refrigerant piping Not supplied
Refrigerant pipe size (Min. wall thickness)
Connection meth­od
Between the indoor & outdoor units
Liquid in. 1/4 (0.0315) Gas in. 3/8 (0.0315) 1/2 (0.0315) Indoor Flared Outdoor Flared Height difference
ft. 40 50
Piping length ft. 65 100
Refrigerant charge (R410A) 2 lb. 9 oz. 3 lb. 7 oz.
NOTE: Test conditions are based on AHRI 210/240.
1: Rating conditions (Cooling) — Indoor: 80˚FDB, 67˚FWB, Outdoor: 95˚FDB, (75˚FWB) (Heating) — Indoor: 70˚FDB, 60˚FWB, Outdoor: 47˚FDB, 43˚FWB 2: (Heating) — Indoor: 70˚FDB, 60˚FWB, Outdoor: 17˚FDB, 15˚FWB
MUZ-FH18NA2
MUZ-FH18NAH2
17,200
20,300
1,375
(410 ~ 2,220)
1,720
4
Page 5
Test condition
OBH684D
3, 4
Mode Test
ARI
"A-2" Cooling Steady State at rated compressor Speed
"B-2" Cooling Steady State at rated compressor Speed
SEER
(Cooling)
HSPF
(Heating)
5
: At Intermediate compressor Speed
"B-1" Cooling Steady State at minimum compressor Speed
"F-1" Cooling Steady State at minimum compressor Speed
"E-V" Cooling Steady State at Intermediate compressor Speed
"H1-2" Heating Steady State at rated compressor Speed
"H3-2" Heating at rated compressor Speed
"H0-1" Heating Steady State at minimum compressor Speed
"H1-1" Heating Steady State at minimum compressor Speed
"H2-V" Heating at Intermediate compressor Speed
5
5
= ("Rated compressor speed" - "minimum compressor speed") / 3 + "minimum compressor speed".
Indoor air condition (°F) Outdoor air condition (°F)
Dry bulb Wet bulb Dry bulb Wet bulb
80 67 95 (75)
80 67 82 (65)
80 67 82 (65)
80 67 67 (53.5)
80 67 87 (69)
70 60 47 43
70 60 17 15
70 60 62 56.5
70 60 47 43
70 60 35 33
OPERATING RANGE
(1) POWER SUPPLY
Outdoor unit
(2) OPERATION
Mode Condition
Standard temperature 80 67 95
Cooling
Heating
Maximum temperature 90 73 115 — Minimum temperature 67 57 14 — Maximum humidity 78 % — Standard temperature 70 60 47 43 Maximum temperature 80 67 75 65 Minimum temperature 70 60 -13 -14
Rated voltage Guaranteed voltage (V)
208/230 V
1 phase
60 Hz
Min. 187
Indoor Outdoor
DB WB DB WB
208 230 Max. 253
Intake air temperature (°F)
5
Page 6
4
OBH684D
OUTLINES AND DIMENSIONS
MUZ-FH06NA MUZ-FH06NAH MUZ-FH09NA MUZ-FH09NAH MUZ-FH12NA MUZ-FH12NAH
Unit: inch
REQUIRED SPACE
*1
4 in. (100 mm) or more when
front and sides of the unit are clear
clear *1
(MUZ-FH06/09/12NA)
(MUZ-FH06/09/12NAH)
2 x hole 3/8 x 13/16
4 in. (100 mm)
or more
8 in. (200 mm)
or more *2
*2
When any 2 sides of left, right
and rear of the unit are clear
14 in. (350 mm)
or more
4 in. (100 mm)
or more
Liquid refrigerant pipe joint Refrigerant pipe (flared) Ø 1/4
Gas refrigerant pipe joint Refrigerant pipe (flared)
Ø 3/8
6
Page 7
MUZ-FH15NA MUZ-FH15NAH MUZ-FH18NA MUZ-FH18NAH MUZ-FH18NA2 MUZ-FH18NAH2
OBH684D
Unit: inch
REQUIRED SPACE
Air in
13
34-5/8
2
17-25/32
6-7/8
16-7/16
Air in
19-11/16
4-5/16
Air out
33-1/16
*1 20 in. (500 mm) or more when front and sides of the unit are clear
Drain hole
1-9/16
1-5/8
14-3/16
2 x hole 13/32 x 13/16
3-3/16
4 in. (100 mm)
or more
Clear *1
20 in. (500 mm)
or more *2
*2 When any 2 sides of left, right and rear of the unit are clear
Service panel
Liquid refrigerant pipe joint Refrigerant pipe (flared)
35
44
4 in. (100 mm)
or more
14in. (350 mm)
or more
Ø 1/4
6-1/2
3-29/32
7-11/16
Gas refrigerant pipe joint Refrigerant pipe (flared)
Ø 1/2
7
Page 8
5
OBH684D
WIRING DIAGRAM
MUZ-FH06NA MUZ-FH09NA-1 MUZ-FH12NA-
1
MUZ-FH06NAH MUZ-FH09NAH-1 MUZ-FH12NAH-
1
8
Page 9
MUZ-FH09NA MUZ-FH12NA
OBH684D
MUZ-FH09NAH MUZ-FH12NAH
9
Page 10
MUZ-FH15NA MUZ-FH18NA
OBH684D
10
Page 11
MUZ-FH18NA2
OBH684D
11
Page 12
MUZ-FH15NAH MUZ-FH18NAH
OBH684D
12
Page 13
MUZ-FH18NAH2
OBH684D
13
Page 14
6
Outdoor heat exchanger
Flared connection
Defrost thermistor RT61
Discharge temperature thermistor RT62
Flared connection
Stop valve (with strainar)
Stop valve
Refrigerant flow in cooling
Compressor
4-way valve
Refrigerant flow in heating
Refrigerant pipe ø3/8 (with heat insulator)
Refrigerant pipe ø1/4 (with heat insulator)
R.V. coil heating ON cooling OFF
Strainer #100
LEV
Ambient temperature thermistor RT65
Muffler
Capillary tube
O.D. 0.157 × I.D. 0.094 × 9-7/16 (
ø4.0 × ø2.4 × 240
)
Outdoor heat exchanger temperature thermistor RT68
Capillary tube O.D. 0.118 × I.D. 0.079 × 8-9/32 (ø3.0 × ø2.0 × 210)
Service port
Service port
Muffler
OBH684D
REFRIGERANT SYSTEM DIAGRAM
MUZ-FH06NA MUZ-FH06NAH MUZ-FH09NA MUZ-FH09NAH MUZ-FH12NA MUZ-FH12NAH
Unit: inch
MUZ-FH15NA MUZ-FH15NAH MUZ-FH18NA MUZ-FH18NAH MUZ-FH18NA2 MUZ-FH18NAH2
Muffler
#100
Discharge temperature thermistor RT62
Capillary tube O.D. 0.157 × I.D. 0.094× 3-15/16 (ø4.0×ø2.4×100)
Compressor
14
Service port
LEV
Strainer
#100
Outdoor heat
Defrost thermistor RT61
Refrigerant flow in cooling Refrigerant flow in heating
exchanger
Outdoor heat exchanger temperature thermistor RT68
R.V. coil heating ON cooling OFF
Ambient temperature thermistor RT65
Refrigerant pipe (with heat insulator)
Flared connection
ø
Flared connection
Refrigerant pipe ø1/4 (with heat insulator)
1/2
Stop valve
Stop valve
Strainer
#100
4-way valve
Service port
Muffler
Page 15
Max. Length A
Max. Height
difference
B
Indoor unit
Outdoor unit
MAX. REFRIGERANT PIPING LENGTH and MAX. HEIGHT DIFFERENCE
OBH684D
Refrigerant piping: ft. Piping size O.D: in.
Model
MUZ-FH06NA MUZ-FH06NAH MUZ-FH09NA MUZ-FH09NAH MUZ-FH12NA MUZ-FH12NAH
MUZ-FH15NA MUZ-FH15NAH MUZ-FH18NA MUZ-FH18NAH MUZ-FH18NA2 MUZ-FH18NAH2
Max. Length
A
Max. Height difference
B
Gas Liquid
65 40 3/8 1/4
100 50 1/2 1/4
ADDITIONAL REFRIGERANT CHARGE (R410A: oz.)
NOTE: Refrigerant piping exceeding 25 ft. requires additional refrigerant charge according to the calculation.
NOTE: Refrigerant piping exceeding 25 ft. requires additional refrigerant charge according to the calculation.
NOTE: Refrigerant piping exceeding 25 ft. requires additional refrigerant charge according to the calculation.
Model
MUZ-FH06NA MUZ-FH06NAH MUZ-FH09NA MUZ-FH09NAH
Model
MUZ-FH12NA MUZ-FH12NAH
Model
MUZ-FH15NA MUZ-FH15NAH MUZ-FH18NA MUZ-FH18NAH MUZ-FH18NA2 MUZ-FH18NAH2
Outdoor unit
precharged
25 30 40 50 60 65
Refrigerant piping length (one way): ft.
2 lb. 9 oz. 0 1.08 3.24 5.40 7.56 8.64
Calculation: X oz. = 1.08/5 oz./ft. × (Refrigerant piping length (ft.) - 25)
Outdoor unit
precharged
25 30 40 50 60 65
Refrigerant piping length (one way): ft.
2 lb. 9 oz. 0 1.62 4.86 8.10 11.34 12.96
Calculation: X oz. = 1.62/5 oz./ft. × (Refrigerant piping length (ft.) - 25)
Outdoor unit
precharged
25 30 40 50 60 70 80 90 100
Refrigerant piping length (one way): ft.
3 lb. 7 oz. 0 1.08 3.24 5.40 7.56 9.72 11.88 14.04 16.20
Calculation: X oz. = 1.08/5 oz./ft. × (Refrigerant piping length (ft.) - 25)
15
Page 16
DATA7
OBH684D
MUZ-FH06NA MUZ-FH06NAH MUZ-FH09NA MUZ-FH09NAH MUZ-FH12NA MUZ-FH12NAH MUZ-FH15NA MUZ-FH15NAH MUZ-FH18NA MUZ-FH18NAH MUZ-FH18NA2 MUZ-FH18NAH2
7-1. PERFORMANCE DATA
1) COOLING CAPACITY
Indoor air Outdoor intake air DB temperature (˚F)
Model
MUZ-FH06NA MUZ-FH06NAH
MUZ-FH09NA MUZ-FH09NAH
MUZ-FH12NA MUZ-FH12NAH
MUZ-FH15NA MUZ-FH15NAH
MUZ-FH18NA MUZ-FH18NAH
MUZ-FH18NA2 MUZ-FH18NAH2
NOTE: 1. IWB : Intake air wet-bulb temperature TC : Total Capacity (x10
2. SHC is based on 80˚F of indoor Intake air DB temperature.
IWB (˚F)
71 7.4 6.1 0.28 6.9 5.7 0.31 6.5 5.3 0.33 6.0 5.0 0.35 5.5 4.6 0.36 67 7.0 6.7 0.26 6.5 6.2 0.29 6.0 5.8 0.32 5.6 5.4 0.33 5.1 4.9 0.35 63 6.5 7.2 0.25 6.1 6.6 0.28 5.6 6.2 0.30 5.1 5.6 0.32 4.7 5.1 0.33 71 11.0 8.7 0.50 10.3 8.1 0.55 9.7 7.6 0.59 9.0 7.1 0.62 8.3 6.5 0.64 67 10.4 9.6 0.47 9.7 8.9 0.52 9.0 8.3 0.56 8.4 7.7 0.59 7.7 7.1 0.62 63 9.8 10.3 0.45 9.1 9.6 0.50 8.5 8.9 0.53 7.7 8.1 0.57 7.0 7.4 0.59 71 14.7 10.2 0.77 13.7 9.6 0.85 12.9 9.0 0.91 12.0 8.4 0.96 11.0 7.7 1.00 67 13.9 11.6 0.73 13.0 10.8 0.80 12.0 10.0 0.87 11.2 9.3 0.92 10.3 8.5 0.97 63 13.1 12.6 0.70 12.1 11.7 0.77 11.3 10.9 0.83 10.3 9.9 0.89 9.4 9.0 0.92 71 18.4 10.4 1.07 17.2 9.7 1.17 16.1 9.1 1.26 15.0 8.5 1.33 13.8 7.8 1.38 67 17.4 12.2 1.01 16.2 11.3 1.11 15.0 10.5 1.20 14.0 9.8 1.27 12.8 9.0 1.33 63 16.4 13.6 0.96 15.2 12.6 1.06 14.1 11.8 1.15 12.8 10.7 1.22 11.7 9.8 1.27 71 21.1 11.3 1.27 19.7 10.6 1.39 18.5 9.9 1.50 17.2 9.2 1.58 15.8 8.5 1.64 67 20.0 13.4 1.20 18.6 12.4 1.32 17.2 11.5 1.43 16.0 10.7 1.52 14.7 9.9 1.59 63 18.7 15.1 1.14 17.4 14.0 1.27 16.2 13.0 1.37 14.7 11.8 1.46 13.4 10.8 1.52 71 21.1 11.3 1.22 19.7 10.6 1.34 18.5 9.9 1.44 17.2 9.2 1.52 15.8 8.5 1.58 67 20.0 13.4 1.16 18.6 12.4 1.27 17.2 11.5 1.38 16.0 10.7 1.46 14.7 9.9 1.53 63
SHC : Sensible Heat Capacity (x10
75 85 95 105 115
TC SHC TPC TC SHC TPC TC SHC TPC TC SHC TPC TC SHC TPC
18.7 15.1 1.10 17.4 14.0 1.22 16.2 13.0 1.31 14.7 11.8 1.40 13.4 10.8 1.46
3
Btu/h) TPC : Total Power Consumption (kW)
3
Btu/h)
2) COOLING CAPACITY CORRECTIONS
Refrigerant piping length (one way: ft.)
25 (std.) 40 65 100
MUZ-FH06NA MUZ-FH06NAH MUZ-FH09NA MUZ-FH09NAH MUZ-FH12NA MUZ-FH12NAH
MUZ-FH15NA MUZ-FH15NAH MUZ-FH18NA MUZ-FH18NAH MUZ-FH18NA2 MUZ-FH18NAH2
3) HEATING CAPACITY CORRECTIONS
MUZ-FH06NA MUZ-FH06NAH MUZ-FH09NA MUZ-FH09NAH MUZ-FH12NA MUZ-FH12NAH
MUZ-FH15NA MUZ-FH15NAH MUZ-FH18NA MUZ-FH18NAH MUZ-FH18NA2 MUZ-FH18NAH2
1.0 0.988 0.967 -
1.0 0.985 0.963 0.933
Refrigerant piping length (one way: ft.)
25 (std.) 40 65 100
1.0 0.977 0.993 -
1.0 0.977 0.993 0.987
16
Page 17
4) HEATING CAPACITY
OBH684D
Indoor air Outdoor intake air WB temperature (˚F)
Model
MUZ-FH06NA
MUZ-FH06NAH
MUZ-FH09NA
MUZ-FH09NAH
MUZ-FH12NA
MUZ-FH12NAH
MUZ-FH15NA
MUZ-FH15NAH
MUZ-FH18NA
MUZ-FH18NAH
MUZ-FH18NA2
MUZ-FH18NAH2
NOTE: 1. IDB : Intake air dry-bulb temperature
2. Above data is for heating operation without any frost.
IDB (˚F)
75 3.8 0.32 5.0 0.41 6.3 0.48 7.5 0.53 8.5 0.56 8.7 0.57 9.9 0.59 70 4.1 0.31 5.4 0.39 6.5 0.47 7.7 0.52 8.7 0.55 9.0 0.56 10.1 0.58 65 4.4 0.29 5.5 0.38 6.8 0.45 8.0 0.50 9.0 0.53 9.2 0.54 10.4 0.57 75 3.8 0.45 5.0 0.53 6.3 0.60 7.5 0.53 8.5 0.55 8.7 0.56 9.9 0.58 70 4.1 0.44 5.4 0.52 6.5 0.59 7.7 0.51 8.7 0.54 9.0 0.55 10.1 0.57 65 4.4 0.42 5.5 0.50 6.8 0.58 8.0 0.50 9.0 0.53 9.2 0.53 10.4 0.56 75 4.8 0.42 6.3 0.53 7.9 0.62 9.4 0.69 10.6 0.73 11.0 0.74 12.4 0.77 70 5.2 0.40 6.7 0.51 8.2 0.61 9.6 0.67 10.9 0.71 11.2 0.72 12.7 0.75 65 5.5 0.38 6.9 0.49 8.6 0.59 10.0 0.66 11.2 0.69 11.6 0.70 13.0 0.74 75 4.8 0.55 6.3 0.66 7.9 0.75 9.4 0.69 10.6 0.73 11.0 0.74 12.4 0.77 70 5.2 0.53 6.7 0.64 8.2 0.74 9.6 0.67 10.9 0.71 11.2 0.72 12.7 0.75 65 5.5 0.51 6.9 0.62 8.6 0.72 10.0 0.66 11.2 0.69 11.6 0.70 13.0 0.74 75 6.0 0.56 7.9 0.71 9.9 0.83 11.8 0.93 13.3 0.97 13.7 0.99 15.5 1.03 70 6.5 0.54 8.4 0.68 10.2 0.81 12.0 0.90 13.6 0.95 14.0 0.97 15.8 1.01 65 6.8 0.51 8.6 0.66 10.7 0.78 12.4 0.88 14.0 0.93 14.4 0.94 16.2 0.99 75 6.0 0.69 7.9 0.84 9.9 0.96 11.8 0.93 13.3 0.97 13.7 0.99 15.5 1.03 70 6.5 0.67 8.4 0.81 10.2 0.94 12.0 0.90 13.6 0.95 14.0 0.97 15.8 1.01 65 6.8 0.64 8.6 0.79 10.7 0.91 12.4 0.88 14.0 0.93 14.4 0.94 16.2 0.99 75 7.9 0.77 10.4 0.97 13.1 1.14 15.6 1.27 17.6 1.33 18.1 1.35 20.5 1.40 70 8.6 0.73 11.1 0.94 13.5 1.11 15.9 1.24 18.0 1.30 18.5 1.33 21.0 1.38 65 9.0 0.70 11.3 0.90 14.1 1.07 16.5 1.20 18.5 1.27 19.1 1.29 21.4 1.35 75 7.9 0.90 10.4 1.10 13.1 1.27 15.6 1.27 17.6 1.33 18.1 1.35 20.5 1.40 70 8.6 0.86 11.1 1.07 13.5 1.24 15.9 1.24 18.0 1.30 18.5 1.33 21.0 1.38 65 9.0 0.83 11.3 1.03 14.1 1.20 16.5 1.20 18.5 1.27 19.1 1.29 21.4 1.35 75 8.9 1.01 11.8 1.28 14.7 1.51 17.6 1.68 19.8 1.76 20.4 1.79 23.1 1.86 70 9.6 0.97 12.5 1.24 15.2 1.47 18.0 1.63 20.3 1.72 20.9 1.75 23.6 1.82 65 10.2 0.93 12.8 1.19 15.9 1.42 18.6 1.59 20.9 1.68 21.5 1.70 24.2 1.79 75 8.9 1.14 11.8 1.41 14.7 1.64 17.6 1.68 19.8 1.76 20.4 1.79 23.1 1.86 70 9.6 1.10 12.5 1.37 15.2 1.60 18.0 1.63 20.3 1.72 20.9 1.75 23.6 1.82 65 10.2 1.06 12.8 1.32 15.9 1.55 18.6 1.59 20.9 1.68 21.5 1.70 24.2 1.79 75 8.9 1.01 11.8 1.28 14.7 1.51 17.6 1.68 19.8 1.76 20.4 1.79 23.1 1.86 70 9.6 0.97 12.5 1.24 15.2 1.47 18.0 1.63 20.3 1.72 20.9 1.75 23.6 1.82 65 10.2 0.93 12.8 1.19 15.9 1.42 18.6 1.59 20.9 1.68 21.5 1.70 24.2 1.79 75 8.9 1.14 11.8 1.41 14.7 1.64 17.6 1.68 19.8 1.76 20.4 1.79 23.1 1.86 70 9.6 1.10 12.5 1.37 15.2 1.60 18.0 1.63 20.3 1.72 20.9 1.75 23.6 1.82 65 10.2 1.06 12.8 1.32 15.9 1.55 18.6 1.59 20.9 1.68 21.5 1.70 24.2 1.79
TC : Total Capacity (x10
5 152535434555
TC TPC TC TPC TC TPC TC TPC TC TPC TC TPC TC TPC
3
Btu/h) TPC : Total Power Consumption (kW)
How to operate with fixed operational frequency of the compressor.
1. Press the EMERGENCY OPERATION switch on the front of the indoor unit, and select either EMERGENCY COOL mode or EMERGENCY HEAT mode before starting to operate the air conditioner.
2. The compressor starts with operational frequency.
3. The fan speed of the indoor unit is High.
4. This operation continues for 30 minutes.
5. In order to release this operation, press the EMERGENCY OPERATION switch twice or once, or press any button on the remote controller.
17
Page 18
7-2. PERFORMANCE CURVE
71 67 63
65 75 85 95 105 115
0.1
0.2
0.3
0.4
0.5
Indoor intake air WB temperature (°F)
SHF at rating condition = 0.96
= 381 CFM
Airflow
Outdoor intake air DB temperature (°F)
Total power consumption
(kW)
OBH684D
Cooling
1.5
1.4
1.3
1.2
1.1
difference (°F)
1.0
Capacity correction factors
0.9
Indoor air Wet-bulb temperature
14 23 32 41 50 59 68 77 86 95 104 113
Cooling capacity (
Outdoor intake air DB temperature(°F)
MUZ-FH06NA MUZ-FH06NAH
at Rated frequency)
Indoor intake air Wet-bulb temperature( F)
76
75
72 68 64
MUZ-FH09NA MUZ-FH09NAH
SHF at rating condition = 0.92
0.8
Airflow
= 381 CFM
0.7
0.6
(kW)
0.5
0.4
Total power consumption
Indoor intake air WB temperature (°F)
65 75 85 95 105 115
Outdoor intake air DB temperature (°F)
MUZ-FH12NA MUZ-FH12NAH MUZ-FH15NA MUZ-FH15NAH
SHF at rating condition = 0.83
1.1
1.0
0.9
(kW)
0.8
0.7
0.6
Total power consumption
Indoor intake air WB temperature (°F)
65 75 85 95 105 115
Outdoor intake air DB temperature (°F)
MUZ-FH18NA MUZ-FH18NAH
SHF at rating condition = 0.67
1.8
1.7
1.6
1.5
1.4
(kW)
1.3
1.2
1.1
Total power consumption
This value of frequency is not the same as the actual frequency in operating. Refer to 7-5 and 7-6 for the relationships between frequency and capacity.
Indoor intake air WB temperature (°F)
65 75 85 95 105 115
Outdoor intake air DB temperature (°F)
= 398 CFM
Airflow
Airflow
= 437 CFM
1.4
71 67 63
1.3
1.2
(kW)
1.1
1.0
0.9
Total power consumption
MUZ-FH18NA2 MUZ-FH18NAH2
1.7
71 67 63
1.6
1.5
1.4
1.3
(kW)
1.2
1.1
1.0
Total power consumption
18
SHF at rating condition = 0.7
65 75 85 95 105 115
Outdoor intake air DB temperature (°F)
SHF at rating condition = 0.67
Indoor intake air WB temperature (°F)
65 75 85 95 105 115
Outdoor intake air DB temperature (°F)
= 411 CFM
Airflow
Indoor intake air WB temperature (°F)
= 437 CFM
Airflow
71 67 63
71 67 63
71 67 63
Page 19
Heating
65
70
75
-5 5 1525354555
65
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
Indoor intake air DB temperature (°F)
= 437 CFM
Airflow
Outdoor intake air WB temperature (°F)
Total power consumption
(kW)
OBH684D
Heating capacity (
1.3
1.2
1.1
1.0
0.9
0.8
0.7
difference (°F)
0.6
0.5
Capacity correction factor
Indoor air Dry-bulb temperature
0.4
-4 5 142332415059 Outdoor intake air WB temperature (°F)
Indoor intake air Dry-bulb temperature ( F)
at Rated frequency)
59 68 79
MUZ-FH06NA MUZ-FH06NAH
= 437 CFM
0.8
Airflow
MUZ-FH09NA
MUZ-FH12NA
MUZ-FH15NA
0.6
(kW)
0.4
Total power consumption
0.2
-5 5 1525354555
0.8
0.6
(kW)
0.4
Total power consumption
0.2
-5 5 1525354555
1.2
0.9
(kW)
0.6
Total power consumption
0.3
-5 5 1525354555
1.50
1.25
1.00
(kW)
0.75
Total power consumption
0.50
-5 5 1525354555
Indoor intake air DB temperature (°F)
Outdoor intake air WB temperature (°F)
Indoor intake air DB temperature (°F)
Outdoor intake air WB temperature (°F)
Indoor intake air DB temperature (°F)
Outdoor intake air WB temperature (°F)
Indoor intake air DB temperature (°F)
Outdoor intake air WB temperature (°F)
Airflow
Airflow
Airflow
= 437 CFM
= 454 CFM
= 454 CFM
75 70 65
65
MUZ-FH09NAH
= 437 CFM
65 70 75
65
1.0
0.9
0.8
0.7
0.6
(kW)
0.5
0.4
Total power consumption
0.3
-5 5 1525354555
Indoor intake air DB temperature (°F)
Outdoor intake air WB temperature (°F)
Airflow
75 70 65
65
MUZ-FH12NAH
= 454 CFM
65 70 75
65
1.1
1.0
0.9
0.8
0.7
(kW)
0.6
0.5
Total power consumption
0.4
-5 5 1525354555
Indoor intake air DB temperature (°F)
Outdoor intake air WB temperature (°F)
Airflow
75 70 65
65
MUZ-FH15NAH
= 497 CFM
65 70 75
65
1.5
1.3
1.1
(kW)
0.9
0.7
Total power consumption
0.5
-5 5 1525354555
Indoor intake air DB temperature (°F)
Outdoor intake air WB temperature (°F)
19
Airflow
75 70 65
65
Page 20
MUZ-FH18NA
OBH684D
2.00
1.75
1.50
1.25
(kW)
1.00
0.75
Total power consumption
0.50
-5 5 1525354555
Airflow
Indoor intake air DB temperature (°F)
Outdoor intake air WB temperature (°F)
= 514 CFM
65
MUZ-FH18NAH
65 70 75
Total power consumption
2.00
1.75
1.50
(kW)
1.25
1.00
0.75
-5 5 1525354555
Indoor intake air DB temperature (°F)
Outdoor intake air WB temperature (°F)
Airflow
= 514 CFM
MUZ-FH18NA2 MUZ-FH18NAH2
2.00
1.75
1.50
1.25
(kW)
1.00
0.75
Total power consumption
0.50
-5 5 1525354555
Indoor intake air DB temperature (°F)
Outdoor intake air WB temperature (°F)
Airflow
65 70 75
65
2.00
1.75
1.50
(kW)
1.25
1.00
Total power consumption
0.75
-5 5 1525354555
Indoor intake air DB temperature (°F)
Outdoor intake air WB temperature (°F)
= 514 CFM
This value of frequency is not the same as the actual frequency in operating. Refer to 7-5 and 7-6 for the relationships between frequency and capacity.
Airflow
= 514 CFM
75 70 65
65
75 70 65
65
7-3. CONDENSING PRESSURE Cooling
Data are based on the condition of indoor humidity 50 %. Air flow should be set to High speed.
MUZ-FH06NA MUZ-FH06NAH
(PSIG)
500
450
400
350
Indoor DB temperature (°F)
300
Condensing pressure
250
200
65 70 75 80 85 90 95 100 105
Outdoor ambient temperature
(PSIG)
190
86 80 75 70
170
150
130
Suction pressure
110
90
(°F) (°F)
Indoor DB temperature (°F)
60 65 70 75 80 85 90 95 100 105
Outdoor ambient temperature
MUZ-FH09NA MUZ-FH09NAH
(PSIG)
500
450
400
350
Indoor DB temperature (°F)
300
Condensing pressure
250
200
65 70 75 80 85 90 95 100 105
Outdoor ambient temperature
(PSIG)
190
86 80 75 70
170
150
130
Suction pressure
110
90
(°F) (°F)
Indoor DB temperature (°F)
60 65 70 75 80 85 90 95 100 105
Outdoor ambient temperature
20
86 80
75 70
86 80
75 70
Page 21
MUZ-FH12NA MUZ-FH12NAH
OBH684D
(PSIG)
500
450
400
Indoor DB temperature (°F)
350
300
Condensing pressure
250
200
65 70 75 80 85 90 95 100 105
Outdoor ambient temperature
MUZ-FH15NA MUZ-FH15NAH
(PSIG)
500
450
400
Indoor DB temperature (°F)
350
300
Condensing pressure
250
200
65 70 75 80 85 90 95 100 105
Outdoor ambient temperature
MUZ-FH18NA MUZ-FH18NAH
(PSIG)
500
(PSIG)
86 80
180
75 70
160
140
120
Suction pressure
100
80
(°F) (°F)
(PSIG)
86 80
180
75 70
160
140
120
Suction pressure
100
80
(°F) (°F)
Indoor DB temperature (°F)
65 70 75 80 85 90 95 100 105
65 70 75 80 85 90 95 100 105
Outdoor ambient temperature
Indoor DB temperature (°F)
Outdoor ambient temperature
86 80
75 70
86 80
75 70
450
400
Indoor DB temperature (°F)
350
300
Condensing pressure
250
200
65 70 75 80 85 90 95 100 105
Outdoor ambient temperature
MUZ-FH18NA2 MUZ-FH18NAH2
(PSIG)
500
450
400
350
300
Condensing pressure
250
200
65 70 75 80 85 90 95 100 105
Indoor DB temperature (°F)
Outdoor ambient temperature
86
(PSIG)
80
180
75 70
160
140
120
Suction pressure
100
80
(°F) (°F)
(PSIG)
86 80
180
75 70
160
140
120
Suction pressure
100
80
(°F) (°F)
Indoor DB temperature (°F)
65 70 75 80 85 90 95 100 105
65 70 75 80 85 90 95 100 105
Outdoor ambient temperature
Indoor DB temperature (°F)
Outdoor ambient temperature
86 80
75 70
86 80
75 70
21
Page 22
Heating
OBH684D
Data are based on the condition of outdoor humidity 75%. Air flow should be set to High speed. Data are for heating operation without any frost.
MUZ-FH06NA MUZ-FH06NAH
(PSIG)
450
410
370
330
Condensing pressure
290
250
5 15253545556575
Indoor DB temperature (°F)
Outdoor ambient temperature
(PSIG)
210
75
190
70
170
65
150
130
110
Suction pressure
90
70
50
5 15253545556575
(°F) (°F)
Indoor DB temperature (°F)
Outdoor ambient temperature
MUZ-FH09NA MUZ-FH09NAH
(PSIG)
450
410
370
330
Condensing pressure
290
250
5 15253545556575
Indoor DB temperature (°F)
Outdoor ambient temperature
(PSIG)
210
75
190
70
170
65
150
130
110
Suction pressure
90
70
50
5 15253545556575
(°F) (°F)
Indoor DB temperature (°F)
Outdoor ambient temperature
MUZ-FH12NA MUZ-FH12NAH
(PSIG)
450
410
(PSIG)
200
75 70
65
175
75 70 65
75 70 65
75 70 65
370
330
Condensing pressure
290
250
5 15253545556575
Indoor DB temperature (°F)
Outdoor ambient temperature
MUZ-FH15NA MUZ-FH15NAH
(PSIG)
550
500
450
400
350
Condensing pressure
300
250
5 15253545556575
Indoor DB temperature (°F)
Outdoor ambient temperature
150
125
Suction pressure
100
75
50
5 15253545556575
(°F) (°F)
(PSIG)
200
75 70
175
65
150
125
Suction pressure
100
75
50
5 15253545556575
(°F) (°F)
Indoor DB temperature (°F)
Outdoor ambient temperature
Indoor DB temperature (°F)
Outdoor ambient temperature
22
75 70 65
Page 23
MUZ-FH18NA MUZ-FH18NAH
OBH684D
(PSIG)
600
550
500
450
400
Condensing pressure
350
Indoor DB temperature (°F)
(PSIG)
75 70 65
Suction pressure
200
175
150
125
100
75 70 65
Indoor DB temperature (°F)
75
300
5 15253545556575
Outdoor ambient temperature
MUZ-FH18NA2 MUZ-FH18NAH2
(PSIG)
600
550
500
450
400
Condensing pressure
350
300
5 15253545556575
Indoor DB temperature (°F)
Outdoor ambient temperature
50
5 15253545556575
(°F) (°F)
(PSIG)
200 75 70 65
175
150
125
Suction pressure
100
75
50
5 15253545556575
(°F) (°F)
Outdoor ambient temperature
Indoor DB temperature (°F)
Outdoor ambient temperature
75 70 65
23
Page 24
7-4. STANDARD OPERATION DATA
OBH684D
Model
Item Unit
Capacity Btu/h 6,000 8,700 9,000 10,900 12,000 13,600 15,000 18,000 17,200 20,300 17,200 20,300
SHF 0.96 — 0.92 — 0.83 — 0.70 — 0.67 — 0.69 —
Total
Input kW 0.315 0.545 0.560 0.710 0.870 0.950 1.200 1.300 1.430 1.720 1.375 1.72
Rated frequency Hz 28 50 47 58.5 46 49 50.5 50 59.5 61 57.0 61
Indoor unit
Power supply
Input kW 0.029 0.029 0.029 0.031 0.033 0.033
Fan motor current A 0.30/0.27 0.30/0.27 0.30/0.27 0.31/0.28 0.34/0.31 0.34/0.31
Outdoor unit
Electrical circuit
Power supply
Input kW 0.243 0.475 0.531 0.681 0.841 0.921 1.169 1.269 1.397 1.687 1.342 1.687
Comp. current A
Fan motor current A
Condensing pressure
Suction pressure
Discharge temperature
Condensing temperature
Suction temperature
Refrigerant circuit
Comp. shell bottom temperature
Ref. pipe length ft. 25
Refrigerant charge (R410A) 2 lb. 9 oz. 3 lb 7 oz.
Intake air temperature
Discharge air temperature
Fan speed (High) rpm 1,150 1,280 1,150 1,280 1,190 1,320 1,220 1,420 1,280 1,460 1,330 1,460
Indoor unit
Airfl ow (High) CFM
Intake air temperature
Fan speed rpm 810 900 810 900 810 900 840 810 840 810 840 810
Airfl ow CFM 1,074 1,202 1,074 1,202 1,074 1,202 1,692 1,634 1,692 1,634 1,692 1,634
Outdoor unit
phase,
phase,
PSIG 332 297 352 323 374 340 361 391 370 445 367 445
PSIG 174 112 153 110 135 106 131 108 125 107 128 107
DB ˚F807080708070807080708070
WB ˚F676067606760676067606760
DB ˚F 64 94 58 99 56 101 52 111 50 119 52 119
WB ˚F60— 55—54—51—49—51—
DB ˚F954795479547954795479547
WB ˚F — 43 — 43 — 43 — 43 — 43 — 43
MSZ-FH06NA MSZ-FH09NA MSZ-FH12NA MSZ-FH15NA MSZ-FH18NA MSZ-FH18NA2
Cooling Heating Cooling Heating Cooling Heating Cooling Heating Cooling Heating Cooling Heating
MSZ-FH06NA MSZ-FH09NA MSZ-FH12NA MSZ-FH15NA MSZ-FH18NA MSZ-FH18NA2
V,
Hz
MUZ-FH06NA
MUZ-FH06NAH
V,
Hz
1.22/1.10 2.23/2.02 2.32/2.10 3.01/2.72 3.60/3.26 4.06/3.67 4.46/4.03 4.87/4.40 5.64/5.10 7.04/6.37 5.53/5.00 7.04/6.37
0.36/0.33 0.34/0.31 0.36/0.33 0.34/0.31 0.41/0.37 0.40/0.36 1.21/1.09 1.24/1.12 1.21/1.09 1.24/1.12 1.21/1.09 1.24/1.12
˚F 136 140 148 145 156 148 152 170 153 189 164 189
˚F 104 96 107 101 112 105 109 115 111 123 109 123
˚F694464415636524543345934
˚F 120 120 129 125 137 128 135 147 141 167 154 167
328
(Wet)
MUZ-FH09NA
MUZ-FH09NAH
437
(Wet)
328
MUZ-FH12NAH
437
208/230, 1, 60
MUZ-FH12NA
208/230, 1, 60
342
(Wet)
454
MUZ-FH15NA
MUZ-FH15NAH
354
(Wet)
497
MUZ-FH18NA
MUZ-FH18NAH
376
(Wet)
514
MUZ-FH18NA2
MUZ-FH18NAH2
395
(Wet)
514
24
Page 25
7-5. CAPACITY AND INPUT CORRECTION BY INVERTER OUTPUT FREQUENCY
OBH684D
MUZ-FH06NA MUZ-FH06NAH
Correction of Cooling capacity
2.0
Correction of Cooling total input
2.0
Correction of Heating capacity
2.0
Correction of Heating total input
2.5
1.5
1.0
0.5
Capacity correction factors
0.0 0 255075100
The operational frequency of compressor
1.5
1.0
0.5
Input correction factors
0.0
(Hz) (Hz)
The operational frequency of compressor
MUZ-FH09NA MUZ-FH09NAH
Correction of Cooling capacity
2.0
1.5
1.0
0.5
Capacity correction factors
0.0 0 255075100
The operational frequency of compressor
2.0
1.5
1.0
0.5
Input correction factors
0.0
(Hz) (Hz)
The operational frequency of compressor
MUZ-FH12NA MUZ-FH12NAH
Correction of Cooling capacity
2.0
1.5
1.0
0.5
Capacity correction factors
0.0 0 255075100
The operational frequency of compressor
2.0
1.5
1.0
0.5
Input correction factors
0.0
(Hz) (Hz)
The operational frequency of compressor
0 25 50 75 100
Correction of Cooling total input
0 25 50 75 100
Correction of Cooling total input
0 25 50 75 100
1.5
1.0
0.5
Capacity correction factors
0.0 0 255075100
(Hz) (Hz)
The operational frequency of compressor
Correction of Heating capacity
2.0
1.5
1.0
0.5
Capacity correction factors
0.0 0 255075100
(Hz) (Hz)
The operational frequency of compressor
Correction of Heating capacity
2.0
1.5
1.0
0.5
Capacity correction factors
0.0 0 255075100
The operational frequency of compressor
(Hz) (Hz)
2.0
1.5
1.0
0.5
Input correction factors
0.0 0 255075100
The operational frequency of compressor
Correction of Heating total input
2.5
2.0
1.5
1.0
0.5
Input correction factors
0.0 0 255075100
The operational frequency of compressor
Correction of Heating total input
2.5
2.0
1.5
1.0
0.5
Input correction factors
0.0 0 255075100
The operational frequency of compressor
MUZ-FH15NA MUZ-FH15NAH
Capacity correction factors
Correction of Cooling capacity
2.0
1.5
1.0
0.5
0.0 0 255075100
The operational frequency of compressor
(Hz) (Hz)
Correction of Cooling total input
2.0
1.5
1.0
0.5
Input correction factors
0.0 0 25 50 75 100
The operational frequency of compressor
Correction of Heating capacity
2.0
1.5
1.0
0.5
Capacity correction factors
0.0 0 255075100
The operational frequency of compressor
25
Correction of Heating total input
3.0
2.5
2.0
1.5
1.0
0.5
Input correction factors
0.0
(Hz) (Hz)
0 255075100
The operational frequency of compressor
Page 26
MUZ-FH18NA MUZ-FH18NAH
OBH684D
Correction of Cooling capacity
2.0
2.0
Correction of Cooling total input
Correction of Heating capacity
2.0
Correction of Heating total input
2.5
1.5
1.0
0.5
Capacity correction factors
0.0 0 255075100
The operational frequency of compressor
1.5
1.0
0.5
Input correction factors
0.0
(Hz) (Hz)
0 255075100
The operational frequency of compressor
1.5
1.0
0.5
Capacity correction factors
0.0 0 255075100
The operational frequency of compressor
2.0
1.5
1.0
0.5
Input correction factors
0.0
(Hz) (Hz)
0 255075100
The operational frequency of compressor
MUZ-FH18NA2 MUZ-FH18NAH2
Correction of Cooling capacity
2.0
1.5
1.0
0.5
Capacity correction factors
0.0 0 255075100
The operational frequency of compressor
Correction of Cooling total input
2.0
1.5
1.0
0.5
Input correction factors
0.0
(Hz) (Hz)
0 255075100
The operational frequency of compressor
Correction of Heating capacity
2.0
1.5
1.0
0.5
Capacity correction factors
0.0 0 255075100
The operational frequency of compressor
(Hz) (Hz)
Correction of Heating total input
2.5
2.0
1.5
1.0
0.5
Input correction factors
0.0 0 255075100
The operational frequency of compressor
7-6. HOW TO OPERATE FIXED-FREQUENCY OPERATION (Test run operation)
1. Press EMERGENCY OPERATION switch to start COOL or HEAT mode (COOL: Press once, HEAT: Press twice).
2. Test run operation starts and continues to operate for 30 minutes.
3. Compressor operates at rated frequency in COOL mode or 58 Hz in HEAT mode.
4. Indoor fan operates at High speed.
5. After 30 minutes, test run operation finishes and EMERGENCY OPERATION starts (operation frequency of compressor var­ies).
6. To cancel test run operation (EMERGENCY OPERATION), press EMERGENCY OPERATION switch or any button on remote controller.
26
Page 27
8
OBH684D
ACTUATOR CONTROL
MUZ-FH06NA MUZ-FH06NAH MUZ-FH09NA MUZ-FH09NAH MUZ-FH12NA MUZ-FH12NAH MUZ-FH15NA MUZ-FH15NAH MUZ-FH18NA MUZ-FH18NAH MUZ-FH18NA2 MUZ-FH18NAH2
8-1. OUTDOOR FAN MOTOR CONTROL
The fan motor turns ON/OFF, interlocking with the compressor. [ON] The fan motor turns ON 5 seconds before the compressor starts up. [OFF] The fan motor turns OFF 15 seconds after the compressor has stopped running.
5 seconds 15 seconds
ON
Compressor
OFF
ON
Outdoor fan motor
OFF
8-2. R.V. COIL CONTROL
Heating Cooling Dry
NOTE: The 4-way valve reverses for 5 seconds right before start-up of the compressor.
8-3. RELATION BETWEEN MAIN SENSOR AND ACTUATOR
Discharge temperature thermistor
Indoor coil temperature thermistor
Defrost thermistor Heating: Defrosting
Fin temperature thermistor Protection
Ambient temperature thermistor
Outdoor heat exchanger tem­perature thermistor
*. MUZ-FH•NAH only.
. . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
Compressor
R.V.coil
Outdoor fan motor
Sensor Purpose
ON OFF OFF
<COOL>
ON OFF
ON OFF
ON OFF
Protection
Cooling: Coil frost prevention
Heating: High pressure protec­tion
Cooling: Low ambient tempera­ture operation
Heating: Defrosting (Heater)
Cooling: Low ambient tempera­ture operation
Cooling: High pressure protec­tion
5 seconds
<HEAT>
5 seconds
Compressor
LEV
○○ ○
○○ ○○○○○
○○ ○○○
○○○ ○○○
Actuator
Outdoor fan
motor
R.V.coil
Indoor fan
motor
Defrost
heater *
27
Page 28
9
OBH684D
SERVICE FUNCTIONS
MUZ-FH06NA MUZ-FH06NAH MUZ-FH09NA MUZ-FH09NAH MUZ-FH12NA MUZ-FH12NAH MUZ-FH15NA MUZ-FH15NAH MUZ-FH18NA MUZ-FH18NAH MUZ-FH18NA2 MUZ-FH18NAH2
9-1. CHANGE IN DEFROST SETTING
Changing defrost finish temperature
<JS> To change the defrost finish temperature, cut/solder the JS wire of the outdoor inverter P.C. board (Refer to 10-6.1.).
Defrost fi nish temperature
Jumper
MUZ-FH06/09/12NA
MUZ-FH06/09/12NAH
MUZ-FH15/18NA MUZ-FH18NA2
MUZ-FH15/18NAH MUZ-18NAH2
Soldered
(Initial setting)
JS
None
(Cut)
41°F (5°C) 50°F (10°C)
50°F (10°C) 64°F (18°C)
9-2. PRE-HEAT CONTROL SETTING
MUZ-FH06/09/12
When moisture gets into the refrigerant cycle, it may interfere with the start-up of the compressor at low outside tempera­ture. The pre-heat control prevents this interference. The pre-heat control turns ON when the discharge temperature ther­mistor is 68°F (20°C) or below. When the pre-heat control turns ON, the compressor is energized. (About 50 W)
MUZ-FH15/18
Prolonged low load operation, in which the thermostat is OFF for a long time, at low outside temperature [32°F (0°C) or less] may cause the following troubles. To prevent those troubles, activate the pre-heat control.
1) If moisture gets into the refrigerant cycle and freezes, it may interfer the start-up of the compressor.
2) If liquid refrigerant collects in the compressor, a failure in the compressor may occur.
The pre-heat control turns ON when the compressor temperature is 68°F (20°C) or below. When the pre-heat control turns ON, the compressor is energized. (About 70 W)
Pre-heat control setting
<JK> ON: To activate the pre-heat control, cut JK wire of the inverter P.C. board. OFF: To deactivate the pre-heat control, solder JK wire of the inverter P.C. board. (Refer to 10-6.1)
Pre-heat control setting
Jumper
MUZ-FH06/09/12NA
MUZ-FH06/09/12NAH
MUZ-FH15/18NA MUZ-FH18NA2
MUZ-FH15/18NAH MUZ-18NAH2
Soldered
JK
Cut Activated
NOTE: When the inverter P.C. board is replaced, check the jumper wires, and cut/solder them if necessary.
Deactivated
(Initial setting)
Deactivated
Activated
(Initial setting)
28
Page 29
10
Lead wiring
<Incorrect>
Connector housing
<Correct>
OBH684D
TROUBLESHOOTING
MUZ-FH06NA MUZ-FH06NAH MUZ-FH09NA MUZ-FH09NAH MUZ-FH12NA MUZ-FH12NAH MUZ-FH15NA MUZ-FH15NAH MUZ-FH18NA MUZ-FH18NAH MUZ-FH18NA2 MUZ-FH18NAH2
10-1. CAUTIONS ON TROUBLESHOOTING
1. Before troubleshooting, check the following
1) Check the power supply voltage.
2) Check the indoor/outdoor connecting wire for miswiring.
2. Take care of the following during servicing
1) Before servicing the air conditioner, be sure to turn OFF the main unit first with the remote controller, then after con­firming the horizontal vane is closed, turn off the breaker and/or disconnect the power plug.
2) Be sure to turn OFF the power supply before removing the front panel, the cabinet, the top panel, and the electronic control P.C. board.
3) When removing the electrical parts, be careful of the residual voltage of smoothing capacitor.
4) When removing the electronic control P.C. board, hold the edge of the board with care NOT to apply stress on the components.
5) When connecting or disconnecting the connectors, hold the connector housing. DO NOT pull the lead wires.
3. Troubleshooting procedure
1)
Check if the OPERATION INDICATOR lamp on the indoor unit is flashing on and off to indicate an abnormality. To make
sure, check how many times the OPERATION INDICATOR lamp is flashing on and off before starting service work.
2) Before servicing, check that the connector and terminal are connected properly.
3) When the electronic control P.C. board seems to be defective, check the copper foil pattern for disconnection and the
components for bursting and discoloration.
4) Refer to 10-2 and 10-3.
29
Page 30
10-2. FAILURE MODE RECALL FUNCTION
OBH684D
Outline of the function This air conditioner can memorize the abnormal condition which has occurred once. Even though LED indication listed on the troubleshooting check table (10-3.) disappears, the memorized failure details can be recalled.
1. Flow chart of failure mode recall function for the indoor/outdoor unit
Operational procedure
Setting up the failure mode recall function
Judgment of indoor/outdoor abnormality
The cause of abnormality cannot be found because the abnormality does not recur.
Turn ON the power supply. <Preparation of the remote controller>
While pressing OPERATION SELECT button and TEMP
controller at the same time, press RESET button.
First, release RESET button.
Hold down the other 2 buttons for another 3 seconds. Make sure that the indicators on
the LCD screen shown in the right fi gure are all displayed. Then release the buttons.
Press STOP/OPERATE (OFF/ON) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit.
Does the left lamp of the OPERATION INDICATOR lamp on the indoor unit blink at the interval of 0.5 seconds? Blinks: Either indoor or outdoor unit is abnormal. Beep is emit-
ted at the same timing as the blinking of the left lamp of the OPERATION INDICATOR lamp.
Before blinking, does the left lamp of the OPERATION INDI­CATOR lamp stay ON for 3 seconds? When it stays ON for 3 seconds (without beep): The outdoor unit
The indoor unit is abnormal. Check the blinking pattern, and identify the abnormal point by referring to the indoor unit failure mode table. (Refer to indoor unit service manual.) Make sure to check at least 2 consecutive blinking cycles.
button on the remote
1
1. Regardless of normal or abnormal condition, a short beep is emitted once the signal is received.
No (OFF)
Yes (Blinks)
No
2
is abnormal.
2
Indoor unit is normal. But the outdoor unit might be abnormal because there are some abnor­malities that cannot be recalled with this way. Check if outdoor unit is abnormal according to the detailed outdoor unit failure mode recall function. (Refer to 10-2.2)
Yes
The outdoor unit is abnormal. Check the blinking pattern, and identify the abnormal point by referring to the outdoor unit failure mode table. (Refer to 10-2.3) Make sure to check at least 2 consecutive blinking cycles.
3
Releasing the failure mode recall function
Deleting the memorized abnormal condition
Release the failure mode recall function by the following procedures. Turn OFF the power supply and turn it ON again. Press RESET button of the remote controller.
Repair the failure parts.
After repairing the unit, recall the failure mode again according to "Setting up the failure mode recall
function" mentioned above.
Press STOP/OPERATE (OFF/ON) button of the remote controller (the set temperature is displayed)
with the remote controller headed towards the indoor unit. Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted. Release the failure mode recall function according to "Releasing the failure mode recall function" men-
tioned above.
NOTE: 1. Make sure to release the failure mode recall function after it is set up, otherwise the unit cannot operate properly.
2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.
2. Blinking pattern when the indoor unit is abnormal:
2.5-second OFF
Blinking at 0.5­second interval
2.5-second OFF
Blinking at 0.5­second interval
ON
OFF
Repeated cycle Repeated cycle
Beeps
3.Blinking pattern when the outdoor unit is abnormal:
2.5-second OFF 3-second ON
Blinking at 0.5­second interval
Beeps
Repeated cycle
2.5-second OFF 3-second ON
ON
OFF
No beep Beeps
Repeated cycle
No beep Beeps
Repeated cycle
30
Beeps
Blinking at 0.5­second interval
Repeated cycle
Page 31
2. Flow chart of the detailed outdoor unit failure mode recall function
OBH684D
Operational procedure
The outdoor unit might be abnormal. Check if outdoor unit is abnormal according to the following procedures.
Make sure that the remote controller is set to the failure mode recall function.
With the remote controller headed towards the indoor unit, press TEMP
button to adjust the set temperature to 77°F (25°C). 1
Does the left lamp of the OPERATION INDICATOR lamp on the indoor unit blink at the interval of 0.5 seconds? Blinks: The outdoor unit is abnormal. Beep is emitted
at the same timing as the blinking of the left lamp of the OPERATION INDICATOR lamp.
2
The outdoor unit is abnormal. Check the blinking pattern, and identify the abnormal point by referring to the outdoor unit failure mode table (10-2.3.). Make sure to check at least 2 consecutive blinking cycles.
Releasing the failure mode recall function
Release the failure mode recall function by the following procedures. Turn OFF the power supply and turn it ON again. Press RESET button of the remote controller.
Repair the failure parts.
Deleting the memorized abnormal condition
After repairing the unit, recall the failure mode again according to "Setting up the failure mode recall
function" (10-2.1.).
Press STOP/OPERATE (OFF/ON) button of the remote controller (the set temperature is displayed) with
the remote controller headed towards the indoor unit. Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted. Release the failure mode recall function according to "Releasing the failure mode recall function" men-
tioned above.
Yes (Blinks
1. Regardless of normal or abnormal condition, 2 short beeps are emitted as the signal is received.
No (OFF)
)
The outdoor unit is normal.
2
Release the failure mode recall function accord­ing to the left mentioned procedure.
NOTE: 1. Make sure to release the failure mode recall function after it is set up, otherwise the unit cannot operate properly.
2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.
2.Blinking pattern when outdoor unit is abnormal:
2.5-second OFF 3-second ON
ON
OFF
No beep
Repeated cycle
Blinking at 0.5­second interval
Beeps
2.5-second OFF 3-second ON
No beep Beeps
Repeated cycle
Blinking at 0.5-
second interval
31
Repeated cycle
Page 32
3. Outdoor unit failure mode table
OBH684D
The left
lamp of the
OPERATION
INDICATOR
lamp
(Indoor unit)
OFF None (Normal) — 1-time fl ash
2.5 seconds OFF
2-time fl ash
2.5 seconds OFF
3-time fl ash
2.5 seconds OFF
4-time fl ash
2.5 seconds OFF
5-time fl ash
2.5 seconds OFF
6-time fl ash
2.5 seconds OFF
7-time fl ash
2.5 seconds OFF
8-time fl ash
2.5 seconds OFF
9-time fl ash
2.5 seconds OFF
Abnormal point
(Failure mode/protection)
Indoor/outdoor communication, receiving error
Indoor/outdoor communication, receiving error
Outdoor power system
Discharge temperature thermistor
Defrost thermistor
Fin temperature thermistor 3-time fl ash
P.C. board temperature thermistor
Ambient temperature thermistor
Outdoor heat exchanger temperature thermistor
Overcurrent 11-time fl ash
Compressor synchronous abnormality (Compressor start-up failure protection)
Discharge temperature
High pressure
Fin temperature/ P.C. board temperature
Outdoor fan motor
Nonvolatile memory data 5-time fl ash
Power module (IC700) (FH09/12) IGBT module (IC700) (FH15/18)
LED indication
(Outdoor P.C. board)
1-time fl ash every
2.5 seconds
2.5 seconds OFF 4-time fl ash
2.5 seconds OFF 2-time fl ash
2.5 seconds OFF
2.5 seconds OFF
12-time fl ash
2.5 seconds OFF
7-time fl ash
2.5 seconds OFF
2.5 seconds OFF 6-time fl ash
2.5 seconds OFF
Condition Remedy
Any signals from the inverter P.C. board cannot be received normally for 3 minutes.
Although the inverter P.C. board sends signal "0", signal "1" has been received 30 consecutive times.
Overcurrent protection cut-out operates 3 consecutive times within 1 minute after the compressor gets started.
Thermistor shorts or opens during compressor running.
Large current fl ows into the power module (IC700) (FH06/09/12)/ IGBT module (IC700) (FH15/18).
Waveform of compressor current is distorted.
Temperature of discharge temperature thermistor exceeds 241°F (116°C), compressor stops. Compressor can restart if discharge temperature thermistor reads 212°F (100°C) or less 3 minutes later.
Temperature indoor coil thermistor exceeds 158°F (70°C) in HEAT mode. Temperature defrost thermistor exceeds 158°F (70°C) in COOL mode.
Temperature of the fi n temperature thermistor on the inverter P.C. board exceeds 167 - 187°F (75 - 86°C) (FH06/09/12)/167 - 176°F (75 - 80°C) (FH15/18), or temperature of P.C. board temperature thermistor on the inverter P.C. board exceeds 162 ­185°F (72 - 85°C) (FH06/09/12)/158 ­167°F (70 - 75°C) (FH15/18).
Outdoor fan has stopped 3 times in a row within 30 seconds after outdoor fan start-up.
Nonvolatile memory data cannot be read properly.
The interface short circuit occurs in the output of the power module (IC700) (FH06/09/12)/IGBT module (IC700) (FH15/18). The compressor winding shorts circuit.
•Refer to 10-5. to check miswiring and serial signal error.
•Refer to 10-5. to check miswiring and serial signal error.
Reconnect
• connectors.
Refer to 10-5.
• to check inverter/ compressor". Check stop valve.
• Refer to 10-5.
• "Check of outdoor thermistors". Defective outdoor thermistors can be identifi ed by checking the blinking pattern of LED.
Reconnect
• compressor connector.
Refer to 10-5.
• to check inverter/ compressor". Check stop valve.
• Reconnect
• compressor connector.
Refer to 10-5.
• to check inverter/ compressor".
Check refrigerant
• circuit and refrigerant
amount. Refer to 10-5.
• of LEV".
Check refrigerant
• circuit and refrigerant
amount. Check stop valve.
• Check around outdoor
• unit.
Check outdoor unit air
• passage.
Refer to 10-5.
• of outdoor fan motor".
Refer to 10-5.
• of outdoor fan motor". Refer to 10-5. of inverter P.C. board".
Replace the inverter
• P.C. board.
Refer to 10-5.
• to check inverter/ compressor".
How
How
"How
"How
"How
"Check
"Check
"Check
"Check
"How
Indoor/outdoor
unit failure
mode recall
function
Outdoor unit failure mode
recall function
○○
○○
○○
○○
NOTE: Blinking patterns of this mode differ from the ones of TROUBLESHOOTING CHECK TABLE (10-3.).
32
Page 33
The left
OBH684D
lamp of the
OPERATION
INDICATOR
lamp
(Indoor unit)
10-time fl ash
2.5 seconds OFF
11-time fl ash
2.5 seconds OFF
14-time fl ash or more
2.5 seconds OFF
Abnormal point
(Failure mode/protection)
Discharge temperature
DC voltage 8-time fl ash
Each phase current of compressor
Stop valve (Closed valve) 14-time fl ash
4-way valve/ Pipe temperature
Outdoor refrigerant system abnormality
LED indication
(Outdoor P.C. board)
2.5 seconds OFF 9-time fl ash
2.5 seconds OFF
2.5 seconds OFF
16-time fl ash
2.5 seconds OFF
17-time fl ash
2.5 seconds OFF
Condition Remedy
Temperature of discharge temperature thermistor has been 122°F (50°C) or less for 20 minutes.
DC voltage of inverter cannot be detected normally.
Each phase current of compressor cannot be detected normally.
Closed valve is detected by compressor current.
The 4-way valve does not work properly. The indoor coil thermistor detects an abnormal temperature.
A closed valve and air trapped in the refrigerant circuit are detected based on the temperature sensed by the indoor and outdoor thermistors and the current of the compressor.
Refer to 10-5.
• of LEV". Check refrigerant
• circuit and refrigerant
amount. Refer to 10-5.
• to check inverter/ compressor".
Check stop valve.
Check the 4-way
• valve.
Replace the inverter
• P.C. board.
Check for a gas leak
• in a connecting piping etc. Check the stop valve.
• Refer to 10-5.
• “Check of outdoor refrigerant circuit”.
Indoor/outdoor
mode recall
"Check
"How
NOTE: Blinking patterns of this mode differ from the ones of TROUBLESHOOTING CHECK TABLE (10-3.).
unit failure
function
Outdoor unit failure mode
recall function
○○
○○
33
Page 34
10-3. TROUBLESHOOTING CHECK TABLE
OBH684D
No. Symptom LED indication
Outdoor unit does not op­erate.
1
2
3
4
5
6
7
'Outdoor unit stops and
8
restarts 3 minutes later' is repeated.
9
10
11
12
13
14
15
NOTE: 1. The location of LED is illustrated at the right fi gure. Refer to 10-6.1.
2. LED is lighted during normal operation.
The fl ashing frequency shows the number of times the LED blinks after every 2.5-second OFF. (Example) When the fl ashing frequency is “2”.
ON
2.5-second OFF
OFF
1-time fl ash every
2.5 seconds
6-time fl ash
2.5 seconds OFF
11-time fl ash
2.5 seconds OFF
16-time fl ash
2.5 seconds OFF
17-time fl ash
2.5 seconds OFF
2-time fl ash
2.5 seconds OFF
3-time fl ash
2.5 seconds OFF
4-time fl ash
2.5 seconds OFF
5-time fl ash
2.5 seconds OFF
8-time fl ash
2.5 seconds OFF
10-time fl ash
2.5 seconds OFF
12-time fl ash
2.5 seconds OFF 13-time fl ash
2.5 seconds OFF
Abnormal point/
Condition
Outdoor power sys­tem
Outdoor thermistors Discharge temperature thermistor, fi n temperature thermistor,
Outdoor control sys­tem
Serial signal The communication fails between the indoor and outdoor unit
Stop valve/ Closed valve
4-way valve/
Pipe temperature
Outdoor refrigerant system abnormality
Overcurrent protec­tion
Discharge tem­perature overheat protection
Fin temperature /P.C. board tem­perature thermistor overheat protection
High pressure pro­tection
Compressor syn­chronous abnormal­ity
Outdoor fan motor Outdoor fan has stopped 3 times in a row within 30 seconds
Each phase current of compressor
DC voltage DC voltage of inverter cannot be detected normally.
0.5-second ON
2.5-second OFF
Overcurrent protection cut-out operates 3 consecutive times within 1 minute after the compressor gets started.
defrost thermistor, P.C. board temperature thermistor, outdoor heat exchanger temperature thermistor or ambient tempera­ture thermistor shorts or opens during compressor running.
Nonvolatile memory data cannot be read properly.
(The left lamp of the OPERATION INDICATOR lamp on the indoor unit lights up or fl ashes 7-time.)
for 3 minutes.
Closed valve is detected by compressor current.
The 4-way valve does not work properly. The indoor coil thermistor detects an abnormal temperature.
A closed valve and air trapped in the refrigerant circuit are detected based on the temperature sensed by the indoor and outdoor thermistors and the current of the compressor.
Large current fl ows into the power module (IC700) (FH06/09/12)/ IGBT module (IC700) (FH15/18).
Temperature of discharge temperature thermistor exceeds 241°F (116°C), compressor stops. Compressor can restart if discharge temperature thermistor reads 212°F (100°C) or less 3 minutes later.
Temperature of the fi n temperature thermistor on the heat sink exceeds 167 - 187°F (75 - 86°C) (FH06/09/12)/167 - 176°F (75 - 80°C) (FH15/18) or temperature of P.C. board tempera­ture thermistor on the inverter P.C.board exceeds 162 - 185°F (72 - 85°C) (FH06/09/12)/158 - 167°F (70 - 75°C) (FH15/18).
Indoor coil thermistor exceeds 158°F (70°C) in HEAT mode. Defrost thermistor exceeds 158°F (70°C) in COOL mode.
The waveform of compressor current is distorted.
after outdoor fan start-up.
Each phase current of compressor cannot be detected nor­mally.
Condition Remedy
0.5-second ON
Reconnect connector of compres-
• sor.
Refer to 10-5.
• inverter/compressor". Check stop valve.
• Refer to 10-5.
• thermistors".
Replace inverter P.C. board.
Check connection between the in-
• verter P.C. board and the relay P.C.
board. (FH15/18) Refer to 10-5.
• miswiring and serial signal error.
Check stop valve.
Refer to 10-5.
• coil". Replace the inverter P.C. board.
Check for a gas leak in a
• connecting piping etc. Check the stop valve.
• Refer to 10-5.
• refrigerant circuit”.
Reconnect connector of compressor.
• Refer to 10-5.
• inverter/compressor". Check stop valve.
Check refrigerant circuit and refrig-
• erant amount.
Refer to 10-5.
Check around outdoor unit.
• Check outdoor unit air passage.
• Refer to 10-5.
• fan motor".
Check refrigerant circuit and refrig-
• erant amount.
Check stop valve.
• Reconnect connector of compressor.
• Refer to 10-5.
• inverter/compressor".
Refer to 10-5.
• fan motor. Refer to 10-5.
• P.C. board.
Refer to 10-5.
• inverter/compressor".
It occurs with following case.
• Instantaneous power voltage
drop. (Short time power failure) (FH15/18) Refer to 10-5.
• supply". (FH15/18) Refer to 10-5.
• verter/compressor".
Inverter P.C. board
MUZ-FH06/09/12NA(H)
Flashing
MUZ-FH15/18NA(H)
Flashing
"How to check
"Check of outdoor
"How to check
"Check of R.V.
“Check of outdoor
"How to check
"Check of LEV".
"Check of outdoor
"How to check
"Check of outdoor
"Check of inverter
"How to check
"Check of power
"How to check in-
LED
LED
34
Page 35
No. Symptom LED indication
OBH684D
Outdoor unit operates.
16
17
18
19
Outdoor unit operates.
20
21
22
NOTE: 1. The location of LED is illustrated at the right fi gure. Refer to 10-6.1.
2. LED is lighted during normal operation.
The fl ashing frequency shows the number of times the LED blinks after every 2.5-second OFF. (Example) When the fl ashing frequency is “2”.
ON
2.5-second OFF
OFF
1-time fl ash
2.5 seconds OFF
3-time fl ash
2.5 seconds OFF
4-time fl ash
2.5 seconds OFF
MUZ-FH06/09/12
5-time fl ash
2.5 seconds OFF
7-time fl ash
2.5 seconds OFF
8-time fl ash
2.5 seconds OFF
9-time fl ash
2.5 seconds OFF
Abnormal point/
Condition
Frequency drop by current protection
Frequency drop by high pressure pro­tection
Frequency drop by defrosting in COOL mode
Frequency drop by discharge tempera­ture protection
Outside temperature thermistor protec­tion
Low discharge tem­perature protection
MUZ-FH06/09/12
PAM protection PAM: Pulse Ampli­tude Modulation
MUZ-FH15/18
Zero cross detecting circuit
Inverter check mode The connector of compressor is disconnected, inverter check
0.5-second ON
2.5-second OFF
FH06/09/12
FH15/18 Current from power outlet is nearing breaker ca-
Temperature of indoor coil thermistor exceeds 131 °F (55°C) in HEAT mode, compressor frequency lowers.
Indoor coil thermistor reads 46°F (8°C) or less in COOL mode, compressor frequency lowers.
Temperature of discharge temperature thermistor exceeds 232°F (111°C), compressor frequency lowers.
When the outside temperature thermistor shorts or opens, protective operation without that thermistor is performed.
Temperature of discharge temperature thermistor has been 122°F (50°C) or less for 20 minutes.
The overcurrent fl ows into PFC (Power factor correction :IC820) or the DC voltage reaches 394 V or more, PAM stops and restarts.
Zero cross signal cannot be detected.
mode starts.
When the input current exceeds approximately 10A (FH06/09)/10.5A (FH12), compressor fre­quency lowers.
pacity.
Condition Remedy
0.5-second ON
The unit is normal, but check the following. Check if indoor fi lters are clogged.
• Check if refrigerant is short.
• Check if indoor/outdoor unit air
• circulation is short cycled.
Check refrigerant circuit and refrig-
• erant amount.
Refer to 10-5.
• Refer to 10-5.
• thermistors".
Refer to 10-5.
• thermistors.
Refer to 10-5.
• Check refrigerant circuit and refrig-
• erant amount.
This is not malfunction. PAM pro­tection will be activated in the fol­lowing cases:
1 Instantaneous power voltage
drop. (Short time power failure)
2 When the power supply voltage
is high.
It occurs with following cases.
1 Instantaneous power voltage
drop. (Short time power failure)
2 Distortion of primary voltage
Refer to 10-5.
• supply".
Check if the connector of the com-
• pressor is correctly connected.
Refer to 10-5. inverter/compressor".
Inverter P.C. board
MUZ-FH06/09/12
Flashing
MUZ-FH15/18
Flashing
LED
"Check of LEV". "Check of outdoor
Check of outdoor
"Check of LEV".
"Check of power
"How to check
LED
35
Page 36
10-4. TROUBLE CRITERION OF MAIN PARTS
OBH684D
MUZ-FH06NA MUZ-FH06NAH MUZ-FH09NA MUZ-FH09NAH MUZ-FH12NA MUZ-FH12NAH MUZ-FH15NA MUZ-FH15NAH MUZ-FH18NA MUZ-FH18NAH MUZ-FH18NA2 MUZ-FH18NAH2
Part name Check method and criterion Figure
Defrost thermistor (RT61)
Fin temperature thermistor (RT64)
Ambient temperature thermistor (RT65)
Outdoor heat exchanger temperature thermistor (RT68)
Discharge temperature thermistor (RT62)
Compressor
Measure the resistance with a tester.
Refer to 10-6. “Test point diagram and voltage”, 1. “Inverter P.C. board”, for the chart of thermistor.
Measure the resistance with a tester. Before measurement, hold the thermistor with your hands to warm it up.
Refer to 10-6. “Test point diagram and voltage”, 1. “Inverter P.C. board”, for the chart of thermistor.
Measure the resistance between terminals using a tester. [Temperature: 14 - 104°F (-10 - 40°C)]
Normal (Ω)
MUZ-FH06/09 MUZ-FH12 MUZ-FH15/18
U-V
U-W
1.60 - 2.17 1.66 - 2.26 0.87 - 1.18
V-W
WHT
V
RED BLK
W
U
Outdoor fan motor
R. V. coil (21S4)
Expansion valve coil (LEV)
Measure the resistance between lead wires using a tester. [Temperature: 14 - 104°F (-10 - 40°C)]
Color of lead wire
MUZ-FH06/09/12 MUZ-FH15/18
Normal (Ω)
RED – BLK
BLK – WHT
29 - 40 12 - 16
WHT – RED
Measure the resistance using a tester. [Temperature: 14 - 104°F (-10 - 40°C)]
Normal (kΩ)
0.97 - 1.38
Measure the resistance using a tester. [Temperature: 14 - 104°F (-10 - 40°C)]
Color of lead wire Normal (Ω)
RED – ORN RED – WHT
RED – BLU
37 - 54
RED – YLW
Measure the resistance using a tester. [Temperature: 14 - 104°F (-10 - 40°C)]
WHT
V
WHT ORN
RED
(+12V)
RED BLK
W
U
LEV
YLW
BLU
Defrost heater
Normal (Ω)
MUZ-FH06/09/12NAH
349 - 428 376 - 461
36
MUZ-FH15/18NAH
MUZ-FH18NAH2
Page 37
10-5. TROUBLESHOOTING FLOW
OBH684D
A How to check inverter/compressor
Disconnect the connector between the compressor
and the power module (IC700) (MUZ-FH06/09/12)/ IGBT module (IC700) (MUZ-FH15/18).
Check the voltage between terminals.
Are the voltages balanced?
Yes
Check the compressor.
No
See 10-5. “Check of open phase”.
Replace the inverter P.C. board.
See 10-5. “Check of compressor”.
B Check of open phase
With the connector between the compressor and the power module (IC700) (MUZ-FH06/09/12)/IGBT module (IC700) (MUZ- FH15/18) disconnected, activate the inverter and check if the inverter is normal by measuring the voltage balance between
the terminals.
Output voltage is 50 - 130 V. (The voltage may differ according to the tester.)
<< Operation method>> Start cooling or heating operation by pressing EMERGENCY OPERATION switch on the indoor unit. (TEST RUN OPERA-
TION: Refer to 7-6.) <<Measurement point>> At 3 points BLK (U)-WHT (V) BLK (U)-RED (W) WHT(V)-RED (W)
Measure AC voltage between the lead wires at 3 points.
NOTE: 1. Output voltage varies according to power supply voltage.
2. Measure the voltage by analog type tester.
3. During this check, LED of the inverter P.C. board fl ashes 9 times. (Refer to 10-6.1.)
C Check of compressor
Refer to 10-5. “Check of compressor winding”. Is the compressor normal?
Yes
Refer to 10-5. “Check of compressor operation time”. Does the compressor operate continuously?
Yes
OK
No
No
Replace the compressor.
Refer to 10-5. “Check of compressor start failure”.
37
Page 38
D Check of compressor winding
OBH684D
Disconnect the connector between the compressor and the power module (IC700) (MUZ-FH06/09/12)/IGBT module (IC700) (MUZ-FH15/18), and measure the resistance between the compressor terminals.
<<Measurement point>> At 3 points BLK-WHT BLK-RED WHT-RED <<Judgement>> Refer to 10-4. 0 [Ω] ················Abnormal [short] Infinite [Ω] ·······Abnormal [open]
NOTE: Be sure to zero the ohmmeter before measurement.
Measure the resistance between the lead wires at 3 points.
E Check of compressor operation time
<<Judgement>>
Connect the compressor and activate the inverter. Then measure
the time until the inverter stops due to overcurrent. <<Operation method>> Start heating or cooling operation by pressing EMERGENCY OPERATION switch on the indoor unit. (TEST RUN OPERATION: Refer to 7-6.) <<Measurement>> Measure the time from the start of compressor to the stop of compressor due to overcurrent.
0 second
1 second
2 seconds
10 seconds
Compressor starts
Abnormal (IC700 failure) (Compressor winding short)
Abnormal (Compressor lock out) (Starting defect)
Abnormal (Poor contact) (Inverter P.C. board defect) (Disconnected connector)
F Check of compressor start failure
Confi rm that ~ is normal.
•Electrical circuit check . Contact of the compressor connector . Output voltage of inverter P.C. board and balance of them (See 10-5. )
. Direct current voltage between DB61(+) and (-) (MUZ-FH06/09/12)/
JP715(+) and JP30(-) (MUZ-FH15/18) on the inverter P.C. board
. Voltage between outdoor terminal block S1-S2
Does the compressor run for 10 seconds or more after it starts?
No
After the compressor is heated with a drier, does the compressor start?
Yes
Compressor start failure. Activate pre-heat control. (Refer to 9-2. "PRE-HEAT CONTROL SETTING")
1
Yes
No
Check the refrigerant circuit. Check the stop valve.
Replace the compressor.
Abnormal (Refrigerant circuit defect) (Closed valve)
10 minutes
Normal
1 Heat the compressor with a drier for about 20 minutes. Do not recover refrigerant gas while heating.
Heating part
38
Page 39
G Check of outdoor thermistors
OBH684D
Disconnect the connector of thermistor in the inverter P.C. board (see below table), and measure the resistance of thermistor.
Is the resistance of thermistor normal? (Refer to 10-6.1.)
Yes
Reconnect the connector of thermistor. Turn ON the power supply and press EMERGENCY OPERATION switch.
Does the unit operate for 10 minutes or more without showing thermistor abnormality?
Yes
OK (Cause is poor contact.)
No
No
Replace the thermistor except RT64. When RT64 is abnormal, replace the inverter P.C. board.
Replace the inverter P.C. board.
MUZ-FH06/09/12
Thermistor Symbol Connector, Pin No. Board Defrost RT61 Between CN641 pin1 and pin2 Discharge temperature RT62 Between CN641 pin3 and pin4 Fin temperature RT64 Between CN642 pin1 and pin2 Ambient temperature RT65 Between CN643 pin1 and pin2 Outdoor heat exchanger temperature RT68 Between CN644 pin1 and pin3
MUZ-FH15/18
Thermistor Symbol Connector, Pin No. Board Defrost RT61 Between CN671 pin1 and pin2 Discharge temperature RT62 Between CN671 pin3 and pin4 Fin temperature RT64 Between CN673 pin1 and pin2 Ambient temperature RT65 Between CN672 pin1 and pin2 Outdoor heat exchanger temperature RT68 Between CN671 pin5 and pin6
Inverter P.C. board
Inverter P.C. board
39
Page 40
H Check of R.V. coil
OBH684D
MUZ-FH06/09/12
First of all, measure the resistance of R.V. coil to check if the coil is defective. Refer to 10-4. In case CN721 is disconnected or R.V. coil is open, voltage is generated between the terminal pins of the connector
although no signal is being transmitted to R.V. coil.
Check if CN721 is connected.
Unit operates COOL mode even if it is set to HEAT mode.
Disconnect connector between the compressor and the power module (IC700). Turn ON the power supply and press EMERGENCY OPERATION switch twice (HEAT mode).
Is there 208/230 VAC between CN721 and
on the inverter P.C. board 3 minutes after the power supply is turned ON?
Yes
Replace the 4-way valve.
Replace the inverter
No
P.C. board.
Unit operates HEAT mode even if it is set to COOL mode.
Disconnect connector between the compressor and the power module (IC700). Turn ON the power supply and press EMERGENCY OPERATION switch once (COOL mode).
Is there 208/230 VAC between CN721 and
on the inverter P.C. board 3 minutes after the power supply is turned ON?
No
Replace the inverter
Yes
P.C. board.
Replace the 4-way valve.
MUZ-FH15/18
First of all, measure the resistance of R.V. coil to check if the coil is defective. Refer to 10-4. In case CN602 is disconnected or R.V. coil is open, voltage is generated between the terminal pins of the connector
although no signal is being transmitted to R.V. coil.
Check if CN602 is connected.
Unit operates COOL mode even if it is set to HEAT mode.
Disconnect connector between the compressor and the IGBT module (IC700). Turn ON the power supply and press EMERGENCY OPERATION switch twice (HEAT mode).
Is there 208/230 VAC between CN602 and
on the inverter P.C. board 3 minutes after the power supply is turned ON?
Yes
Replace the 4-way valve.
Replace the inverter
No
P.C. board.
Unit operates HEAT mode even if it is set to COOL mode.
Disconnect connector between the compressor and the IGBT module (IC700). Turn ON the power supply and press EMERGENCY OPERATION switch once (COOL mode).
Is there 208/230 VAC between CN602 and
on the inverter P.C. board 3 minutes after the power supply is turned ON?
No
Replace the inverter
Yes
P.C. board.
Replace the 4-way valve.
40
Page 41
I Check of outdoor fan motor
OBH684D
Disconnect the connectors CN931 and CN932 from the inverter P.C. board. Check the connection between the connector CN931 and CN932.
Is the resistance between each ter­minal of outdoor fan motor normal? (Refer to 10-4.)
No
Yes
Disconnect CN932 from the inverter P.C. board, and turn on the power supply.
Rotate the outdoor fan motor manually and measure the voltage of CN931. Between 1(+) and 5(-) Between 2(+) and 5(-) Between 3(+) and 5(-)
(Fixed to either 5 or 0 VDC)
Replace the outdoor fan motor.
Does the voltage between each terminal become 5 and 0
No
VDC repeatedly?
Yes
Does the outdoor fan motor rotate smoothly?
No
Replace the inverter P.C. board.
Yes
41
Page 42
J Check of power supply
OBH684D
Disconnect the connector between the compressor and the power module
(IC700) (MUZ-FH06/09/12)/IGBT module (IC700) (MUZ-FH15/18).
Turn ON power supply and press EMERGENCY OPERATION switch.
Does the left lamp of the OPERATION INDICATOR lamp on the indoor unit light up?
Yes
Is there DC voltage 260 - 370 VDC between DB61 (+) and DB61 (–)
(MUZ-FH06/09/12)/294 - 370 VDC
between JP715 (+) and JP30 (–)
(MUZ-FH15/18) on the inverter P.C.
board? (Refer to 10-6.1.)
No
Check the electric parts in main circuit.
No
Yes
Rectify indoor/outdoor connecting wire.
Yes
Is there voltage 208/230 VAC between the indoor terminal block S1 and S2?
Does LED on the inverter P.C. board light up or fl ash? (Refer to 10-6.1.)
Yes
If lights up, OK. If fl ashes, refer to 10-3.
Replace the indoor electronic control P.C.
No
board.
Replace the inverter
No
P.C. board.
DB61
Inverter P.C. board (Solder side)
260 - 370 VDC
294 -370 VDC
MUZ-FH06/09/12
JP30
JP715
MUZ-FH15/18
42
Page 43
K Check of LEV (Expansion valve)
OBH684D
Turn ON the power supply. <Preparation of the remote controller>
While pressing both OPERATION SELECT button and TEMP button on the remote controller at the same time, press RESET button. First, release RESET button.
Hold down the other 2 buttons for another 3 seconds.
Make sure that the indicators on the LCD screen shown in the right fi gure are all displayed. Then re- lease the buttons.
Press STOP/OPERATE (OFF/ON) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit.
Expansion valve operates in full-opening direction.
Do you hear the expansion valve "click, click·······"? Do you feel the expansion valve vibrate when touching it ?
No
Yes
1
OK
1. Regardless of normal or abnormal condition, a short beep is emitted once the signal is received.
Is LEV coil properly fi xed to the expansion valve?
Yes
Does the resistance of LEV coil have the characteristics? (Refer to 10-4.)
No
Replace the LEV coil.
NOTE: After check of LEV, do the undermentioned operations.
1. Turn OFF the power supply and turn it ON again.
2. Press RESET button on the remote controller.
No
Yes
Properly fi x the LEV coil to the expansion valve.
Measure each voltage between connector pins of CN724 on the inverter P.C. board.
1. Pin (-) — Pin (+)
2. Pin (-) — Pin (+)
3. Pin (-) — Pin (+)
4. Pin (-) — Pin (+) Is there about 3 - 5 VAC between each?
NOTE: Measure the voltage by an analog
tester.
Replace the expansion valve.
Yes
Replace the inverter P.C.
No
board.
43
Page 44
L Check of inverter P.C. board
OBH684D
Check the outdoor fan motor. (Refer to 10-5.
.)
Is the fuse (F901) blown on the in­verter P.C. board?
No
Check the connection of the connectors (CN931, CN932) of the outdoor fan motor. If the connection is poor, make it correct.
Operate the outdoor unit by starting EMERGENCY OPERATION.
Check the LED indication on the in­verter P.C. board. Does the LED fl ash 10 times?
Yes (10-time fl ash)
Replace the inverter P.C. board.
Yes
No
Check the corresponding parts following LED indication. (Refer to 10-3.)
44
Page 45
M How to check miswiring and serial signal error
OBH684D
Turn OFF the power supply.
NOTE: Refer to the indoor unit service manual.
Is there rated voltage in the power supply?
Turn ON the power supply.
Is there rated voltage between the outdoor terminal block S1 and S2?
Press EMERGENCY OPERATION switch once.
Does the left lamp of OPERATION INDICATOR lamp light up? <Confi rmation of the power to the indoor unit>
Is serial signal error indicated 6 minutes later?
Turn OFF the power supply. Check once more if the indoor/outdoor
B
connecting wire is not miswiring. Bridge the outdoor terminal block S2 and
1
S3.
Turn ON the power supply.
Is the bus-bar voltage of the inverter P.C. board normal? (Refer to "TEST POINT DIAGRAM AND VOLTAGE" in the outdoor service manual.)
Yes
Yes
Yes
Yes
A
Yes
No
No
No
1. Miswiring may damage indoor electronic control P.C.
3. Be sure to check this within 3 minutes after turning ON.
Check the power supply.
No
Check the wiring.
Is there any miswiring, poor contact, or wire disconnection of the indoor/outdoor connect­ing wire?
board during the operation. Be sure to confi rm the wiring is correct before the opera- tion starts.
After 3 minutes, LED blinks 6 times. Even when the inverter P.C. board is normal, LED blinks 6 times after 3 minutes.
No
No
Check of power supply. (Refer to the outdoor service manual.)
Yes
Correct them.
Does the LED on the inverter P.C. board repeat "3.6-second-OFF and 0.8-second-ON quick blinking"?
Turn OFF the power supply. Remove the bridge between the outdoor terminal block S2 and S3. Turn ON the power supply.
Is there rated voltage between the indoor terminal block S1 and S2? <Confi rmation of power voltage>
Is there amplitude of 10 to 20 VDC between the indoor terminal block S2 and S3? <Confi rmation of serial signal>
Yes
A
• Reinstall
• Attach a fi lter
No
either the unit or the light away from each other.
on remote control receiv­ing section of the indoor unit.
• Turn OFF inverter-controlled lighting equipment.
• Turn OFF the power supply and then turn ON again.
• Press EMERGENCY OPERATION switch.
Is serial signal error indicated 6 minutes later?
B
3
Yes
Yes
Yes
Is there 2 VDC or less between CN202 (+) and JPG (GND)(-) on the indoor electronic control P.C. board?
Yes
Is there 2 VDC or less between CN202A (+) and JPG (GND)(-) on the indoor electronic control P.C. board?
Replace the indoor power P.C. board.
No
No Yes No
No (Lighted or not lighted)
No
No
Replace the indoor elec­tronic control P.C. board.
45
Replace the inverter P.C. board . 2
2. Be careful of the residual voltage of
smoothing capacitor.
Check the wiring If there are any error of the indoor/outdoor connecting wire: such as the damage of the wire, intermediate connection, and/or poor contact to the terminal block, replace the indoor/ outdoor connecting wire.
Is there 2 VDC or less between CN202 (+) and JPG (GND)(-) on the indoor electronic control P.C. board?
Yes
Page 46
N Check of defrost heater
OBH684D
MUZ-FH06NAH MUZ-FH09NAH MUZ-FH12NAH MUZ-FH15NAH MUZ-FH18NAH MUZ-FH18NAH2
Check the following points before checking electric continuity.
1. Does the resistance of ambient temperature thermistor have the characteristics? Refer to 10-6.1.
2. Is the resistance of defrost heater normal? Refer to 10-4.
3. Does the heater protector remain conducted (not open)?
4. Are both ambient temperature thermistor and circuit of defrost heater securely connected to connectors?
In HEAT mode, for more than 5 minutes, let the ambient temperature thermistor continue to read 32°F (0°C) or below, and let the defrost thermistor continue to read 30°F (-1°C) or below.
NOTE: In case both thermistors are more than the above temperature, cool them with cold
water etc...
Is there 208/230 VAC between CN722 and
(MUZ-FH06/09/12)/CN601 and (MUZ-
FH15/18) on the inverter P.C. board? Refer to
10-6.1.
No
Replace the inverter P.C. board.
Yes
Not the problem of the inverter P.C. board.
O Check of outdoor refrigerant circuit
Has the operation stopped during pump down?
Yes
The operation has stopped to pre­vent the diesel explosion caused by air trapped in the refrigerant circuit. Close the stop valve, and disconnect the power plug or turn the breaker OFF.
CAUTION : Do not start the opera-
tion again to prevent hazards.
Was the operation started with
No
the stop valve closed, and was it opened during operation?
No
The refrigerant gas amount may be 60% or less than the normal amount. Identify where the gas is leaking from, and fi x the leak.
The unit occasionally stops when the stop valve is opened or closed during operation. Open the stop valve and
Yes
start the cooling operation again.
46
Page 47
P Electromagnetic noise enters into TV sets or radios
OBH684D
Is the unit grounded?
Yes
Is the distance between the antennas and the indoor unit within 9.91 ft. or is the distance between the antennas and the outdoor unit within 9.91 ft.
No
Is the distance between the TV sets or ra­dios and the indoor unit within 3.28 ft. or is the distance between the TV sets or radios and the outdoor unit within
9.91 ft.
(3m)
?
No
Are the antennas damaged? Is the coaxial cable damaged? Is there any poor contact in the anten­na wiring?
No
Is the indoor/outdoor connecting wire of the air conditioner and the wiring of the antennas close?
No
(3m)
(3m)
(1m)
No
,
Yes
?
,
Yes
Yes
Yes
Ground the unit.
Extend the distance between the antennas and the indoor unit, and/or the antennas and the outdoor unit.
Extend the distance between the TV sets and/or radios and the indoor unit, or the TV sets or radios and the outdoor unit.
Replace or repair the antenna. Replace or repair the coaxial cable.
Extend the distance between the indoor/outdoor connecting wire of the air conditioner and the wir­ing of the antennas.
Even if all of the above conditions are fulfi lled, the electromagnetic noise may enter, depending on the electric fi eld strength or the installation condition (combination of specifi c conditions such as antennas or wiring). Check the following before asking for service.
1. Devices affected by the electromagnetic noise TV sets, radios (FM/AM broadcast, shortwave)
2. Channel, frequency, broadcast station affected by the electromagnetic noise
3. Channel, frequency, broadcast station unaffected by the electromagnetic noise
4. Layout of: indoor/outdoor unit of the air conditioner, indoor/outdoor wiring, ground wire, antennas, wiring from antennas, receiver
5. Electric fi eld intensity of the broadcast station affected by the electromagnetic noise
6. Presence or absence of amplifi er such as booster
7. Operation condition of air conditioner when the electromagnetic noise enters in
1) Turn OFF the power supply once, and then turn ON the power supply. In this situation, check for the electromagnetic noise.
2) Within 3 minutes after turning ON the power supply, press STOP/OPERATE (OFF/ON) button on the remote controller for power ON, and check for the electromagnetic noise.
3) After a short time (3 minutes later after turning ON), the outdoor unit starts running. During operation, check for the electromagnetic noise.
4) Press STOP/OPERATE (OFF/ON) button on the remote controller for power OFF, when the outdoor unit stops but the indoor/outdoor communication still runs on. In this situation, check for the electromagnetic noise.
47
Page 48
10-6. TEST POINT DIAGRAM AND VOLTAGE
OBH684D
1. Inverter P.C. board
MUZ-FH06NA MUZ-FH06NAH MUZ-FH09NA
(+)
1
-
Smoothing capacitor (C62)
Fuse (F801) T3.15AL250V
MUZ-FH12NA
Back side of unit
208/230 VAC
Fuse (F901) T3.15AL250V
Output to drive outdoor fan motor (CN932)
Output to drive compressor (LDU, LDV, LDW)
-1 MUZ-FH12NAH
DB61 260 - 370 VDC
(-)
-1 MUZ-FH09NAH
R.V.coil Smoothing capacitor (C61)
(CN721)
208/230 VAC
-1
Heater connector (CN722)
(MUZ-FH06NAH
MUZ-FH09/12NAH-
Fuse (F701) T3.15AL250V
208/230 VAC
1
)
LED
Front side of unit
Fin temperature
thermistor/RT64
(CN642)
Signal of outdoor
fan motor (CN931)
Defrost thermistor(RT61) Ambient temperature thermistor(RT65) Outdoor heat exchanger temperature thermistor(RT68)
100
90 80 70 60 50 40 30
5HVLVWDQFHN
20 10
0
-4 14 32 50 68 86 104 Temperature(°F)
Defrost thermistor
/RT61(CN641)
Ambient temperature
thermistor/RT65
(CN643)
Discharge temperature thermistor (RT62)
800 700 600 500 400 300
5HVLVWDQFHN
200 100
0
32 50 68 86 104 122 140 158 176 194 212 230 248
Discharge temperature
thermistor/RT62
(CN641)
Outdoor heat exchanger
temperature thermistor
Temperature (°F)
48
/RT68 (CN644)
LEV connector
(CN724)
Jumper wire for changing defrost setting (JS)
Jumper wire for pre-heat control setting (JK)
Fin temperature thermistor(RT64)
200 180 160 140 120 100
80 60
5HVLVWDQFHN
40 20
0
32 50 68 86 104 122 140 158 176
Temperature(°F)
Page 49
MUZ-FH09NA MUZ-FH09NAH MUZ-FH12NA MUZ-FH12NAH
OBH684D
Back side of unit
208/230 VAC
Fuse (F901) T3.15AL250V
Output to drive outdoor fan motor (CN932)
Output to drive compressor (LDU, LDV, LDW)
DB61 260 - 370 VDC
(-)
(+)
Smoothing capacitor (C62)
Fuse (F801) T3.15AL250V
Smoothing capacitor (C61)
R.V.coil (CN721) 208/230 VAC
Heater connector
(CN722) (MUZ- FH09/12NAH)
Fuse (F701) T3.15AL250V
208/230 VAC
LED
Front side of unit
Fin temperature
thermistor/RT64
(CN642)
Signal of outdoor
fan motor (CN931)
Defrost thermistor(RT61) Ambient temperature thermistor(RT65) Outdoor heat exchanger temperature thermistor(RT68)
100
90 80 70 60 50 40 30
5HVLVWDQFHN
20 10
0
-4 14 32 50 68 86 104 Temperature(°F)
Defrost thermistor
/RT61(CN641)
Ambient temperature
thermistor/RT65
(CN643)
Discharge temperature thermistor (RT62)
800 700 600 500 400 300
5HVLVWDQFHN
200 100
0
32 50 68 86 104 122 140 158 176 194 212 230 248
Discharge temperature
thermistor/RT62
(CN641)
Outdoor heat exchanger
temperature thermistor
Temperature (°F)
49
/RT68 (CN644)
LEV connector
(CN724)
Jumper wire for changing defrost setting (JS)
Jumper wire for pre-heat control setting (JK)
Fin temperature thermistor(RT64)
200 180 160 140 120 100
80 60
5HVLVWDQFHN
40 20
0
32 50 68 86 104 122 140 158 176
Temperature(°F)
Page 50
MUZ-FH15NA
-4 14 32 50 68 86 104
0
10
20
30
40
50
60
70
80
90
100
Temperature(°F)
Defrost thermistor(RT61) Ambient temperature thermistor(RT65) Outdoor heat exchanger temperature thermistor(RT68)
32 50 68 86 104 122 140 158 176
0
20
40
60
80
100
120
140
160
180
200
Temperature(°F)
Fin temperature thermistor(RT64)
Resistance(k )
Resistance(k )
Temperature (°F)
Discharge temperature thermistor (RT62)
5HVLVWDQFHN
0
100
200
300
400
500
600
700
800
32 50 68 86 104 122 140 158 176 194 212 230 248
OBH684D
MUZ-FH15NAH MUZ-FH18NA MUZ-FH18NA2 MUZ-FH18NAH MUZ-FH18NAH2
Heater connector (CN601)
208/230 VAC
(MUZ-FH15NAH MUZ-FH18NAH(2))
Signal of out­door fan motor (CN931)
Output to drive outdoor fan motor (CN932)
Fuse (F901)
T3.15AL250V
Fuse (F880)
T3.15AL250V
JP715 (+)
294 - 370 VDC
JP30 (-)
Fuse (F601)
T3.15AL250V
R.V. coil (CN602)
208/230 VAC
LEV connector (CN724)
LED
Defrost thermistor /RT61 (CN671)
Discharge temperature thermistor/RT62 (CN671)
Outdoor heat exchanger temperature thermistor /RT68 (CN671)
Ambient temperature thermistor/RT65 (CN672)
Fin temperature thermistor/RT64 (CN673)
Jumper wire for changing defrost setting (JS)
Jumper wire for pre-heat control setting (JK)
50
Page 51
11
OBH684D
DISASSEMBLY INSTRUCTIONS
<"Terminal with locking mechanism" Detaching points>
The terminal which has the locking mechanism can be detached as shown below. There are 2 types (refer to (1) and (2)) of the terminal with locking mechanism. The terminal without locking mechanism can be detached by pulling it out. Check the shape of the terminal before detaching.
(1) Slide the sleeve and check if there is a locking lever or not. (2) The terminal with this connector has the
Sleeve
locking mechanism.
Locking lever
Slide the sleeve. Pull the terminal while pushing the locking lever.
Hold the sleeve, and pull out the terminal slowly.
Connector
11-1. MUZ-FH06NA MUZ-FH06NAH MUZ-FH09NA MUZ-FH09NAH MUZ-FH12NA MUZ-FH12NAH
NOTE: Turn OFF the power supply before disassembly.
OPERATING PROCEDURE PHOTOS
1. Removing the cabinet
(1) Remove the screw fixing the service panel. (2) Pull down the service panel and remove it. (3) Remove the screws fixing the conduit cover. (4) Remove the conduit cover. (Photo 4) (5) Remove the screw fixing the conduit plate. (Photo 5) (6) Remove the conduit plate. (7) Disconnect the power supply wire and indoor/outdoor
connecting wire. (8) Remove the screws fixing the top panel. (9) Remove the top panel. (
10
) Remove the screws fixing the cabinet.
(
11
) Remove the cabinet.
(
12
) Remove the screws fixing the back panel.
(
13
) Remove the back panel.
Photo 1
Screws of the top panel
Back panel
Screws of the back panel
Photo 2
Screws of the top panel
Screws of the cabinet
Photo 3
51
Screws of the cabinet
Screws of the cabinet
Screw of the cabinet
Service panel
Screws of the terminal block support and the back panel
Direction to remove
Hooks
Page 52
OPERATING PROCEDURE PHOTOS
OBH684D
Photo 4 Photo 5
Screws of the
conduit cover
Screw of the conduit plate
2. Removing the inverter assembly, inverter P.C. board
(1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the lead wire to the reactor and the following
connectors:
<Inverter P.C. board>
CN721 (R.V. coil)
CN722 (Defrost heater and heater protector) (MUZ-
FH06/09/12NAH)
CN931, CN932 (Fan motor) CN641 (Defrost thermistor and discharge temperature ther-
mistor) CN643 (Ambient temperature thermistor) CN644 (Outdoor heat exchanger temperature thermistor) CN724 (LEV)
(3) Remove the compressor connector (CN61). (4) Remove the screws fixing the heat sink support and the
separator.
(5) Remove the fixing screws of the terminal block support and
the back panel. (6) Remove the inverter assembly. (7) Remove the screw of the ground wire and screw of the ter-
minal block support. (8) Remove the heat sink support from the P.C. board support. (9) Remove the screw of the inverter P.C. board and remove the
inverter P.C. board from the P.C. board support.
3. Removing R.V. coil
(1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the following connectors: <Inverter P.C. board>
CN721 (R.V. coil)
(3) Remove the R.V. coil.
Photo 6
Screws of the heat sink support and the separator
Photo 7
Heat sink
Heat sink support
P.C. board support
Screws of the terminal block support and the back panel
Screw of the Terminal block support
52
Screw of the
inverter P.C. board
Terminal block support
Screw of the ground wire
Page 53
OPERATING PROCEDURE PHOTOS
OBH684D
4. Removing the discharge temperature thermistor, defrost thermistor, outdoor heat exchanger tempera­ture thermistor and ambient temperature thermistor
(1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the lead wire to the reactor and the following con-
nectors: <Inverter P.C. board>
CN641 (Defrost thermistor and discharge temperature ther-
mistor) CN643 (Ambient temperature thermistor) CN644 (Outdoor heat exchanger temperature thermistor)
(3) Pull out the discharge temperature thermistor from its holder. (4) Pull out the defrost thermistor from its holder. (Photo 6) (5) Pull out the outdoor heat exchanger temperature thermistor
from its holder. (Photo 6)
(6) Pull out the ambient temperature thermistor from its holder.
Photo 8
Discharge temperature thermistor
Screw of the R.V. coil
Photo 9
Photo 10
Outdoor heat exchanger tempera­ture thermistor
Defrost thermistor
Ambient temperature thermistor
53
Page 54
OPERATING PROCEDURE
OBH684D
5. Removing outdoor fan motor
(1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the following connectors: <Inverter P.C. board>
CN931, CN932 (Fan motor) (3) Remove the propeller fan nut. (4) Remove the propeller fan. (5) Remove the screws fixing the fan motor. (6) Remove the fan motor.
PHOTOS
Photo 11
Screws of the outdoor fan motor
6. Removing the compressor and 4-way valve
(1) Remove the cabinet and panels. (Refer to 1.) (2) Remove the inverter assembly. (Refer to 2.) (3) Remove the screws fixing the reactor. (4) Remove the reactor. (5) Remove the soundproof felt. (6) Recover gas from the refrigerant circuit.
NOTE: Recover gas from the pipes until the pressure gauge
shows 0 PSIG.
(7) Detach the brazed part of the suction and the discharge pipe
connected with compressor. (8) Remove the nuts fixing the compressor. (9) Remove the compressor. (
10
) Detach the brazed part of pipes connected with 4-way valve.
Photo 13
Propeller fan
Photo 12
Propeller fan nut
Screws of the reactor
Discharge pipe brazed part
Brazed parts of 4-way valve
54
Soundproof felt
Suction pipe
brazed part
Page 55
11-2. MUZ-FH15NA MUZ-FH15NAH MUZ-FH18NA MUZ-FH18NAH
OBH684D
MUZ-FH18NA2 MUZ-FH18NAH2
NOTE: Turn OFF the power supply before disassembly.
OPERATING PROCEDURE
1. Removing the cabinet
(1) Remove the screws of the service panel. (2) Remove the screws of the top panel. (3) Remove the screw of the valve cover. (4) Remove the service panel. (5) Remove the screws fixing the conduit cover. (6) Remove the conduit cover. (7) Remove the screw of fixing the conduit plate. (8) Remove the conduit plate. (9) Remove the top panel. (10)
Remove the valve cover.
(11)
Disconnect the power supply and indoor/outdoor connect-
ing wire.
(12)
Remove the screws of the cabinet.
(13)
Remove the cabinet.
(14)
Remove the screws of the back panel.
(15)
Remove the back panel.
Photo 2
Screws of the top panel
Screw of the back panel
Screws of the cabinet
Photo 1
Screws of the top panel
Screws of the cabinet
Photo 3
Screws of the conduit cover
PHOTOS
Screws of the cabinet
Screws of the cabinet
Screw of the valve cover
Screws of the service panel
Photo 4
Screw of the conduit plate
Screws of the back panel
55
Page 56
OPERATING PROCEDURE
OBH684D
PHOTOS
2. Removing the inverter assembly, inverter P.C. board and relay P.C. board
(1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the lead wire to the reactor and the following con-
nectors: <Inverter P.C. board> CN602 (R.V. coil) CN931, CN932 (Fan motor) CN671 (Defrost thermistor, discharge temperature thermistor
and outdoor heat exchanger temperature thermistor) CN672 (Ambient temperature thermistor) CN724 (LEV) CN601 (Defrost heater and heater protector)
(MUZ-FH15/18NAH/18NAH2)
(3) Remove the compressor connector. (4) Remove the screws fixing the relay panel. (5) Remove the relay panel. (6) Remove the ground wires and the lead wires of the inverter
P.C. board.
(7) Remove the screws of the P.B. support. (8) Remove the inverter P.C. board from the P.B. support.
Photo 5
Inverter P.C. board
Screws of the P.B. support
Screw of the relay panel
Screw of the relay panel
Ground wires
Screw of the relay panel
Screws of the P.B. support
3. Removing R.V. coil
(1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the following connector: <Inverter P.C. board>
CN602 (R.V. coil)
(3) Remove the R.V. coil.
Photo 6
Screw of the R.V. coil
Brazed parts of 4-way valve
56
Page 57
OPERATING PROCEDURE PHOTOS
OBH684D
4. Removing the discharge temperature thermistor, defrost thermistor, outdoor heat exchanger tempera­ture thermistor and ambient temperature thermistor
(1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the lead wire to the reactor and the following
connectors: <Inverter P.C. board>
CN671 (Defrost thermistor, discharge temperature thermis-
tor and outdoor heart exchanger temperature ther­mistor)
CN672 (Ambient temperature thermistor)
(3)
Pull out the discharge temperature thermistor from its holder. (4) Pull out the defrost thermistor from its holder. (5) Pull out the outdoor heat exchanger temperature thermistor
from its holder.
(6) Pull out the ambient temperature thermistor from its holder.
5. Removing outdoor fan motor
(1)
Remove the top panel, cabinet and service panel. (Refer to 1.)
(2) Disconnect the following connectors:
<Inverter P.C. board>
CN931 and CN932 (Fan motor) (3) Remove the propeller fan. (4) Remove the screws fixing the fan motor. (5) Remove the fan motor.
Photo 7
Outdoor heat exchanger temperature thermistor
Photo 8
Ambient temperature thermistor
Defrost thermistor
6. Removing the compressor and 4-way valve
(1)
Remove the top panel, cabinet and service panel. (Refer to 1.) (2) Remove the back panel. (Refer to 1.) (3) Remove the inverter assembly. (Refer to 2.) (4) Remove the soundproof felt. (5) Recover gas from the refrigerant circuit.
NOTE: Recover gas from the pipes until the pressure gauge
shows 0 PSIG.
(6) Detach the brazed part of the suction and the discharge
pipe connected with compressor. (7) Remove the nuts fixing the compressor. (8) Remove the compressor. (9) Detach the brazed parts of 4-way valve and pipe. (Photo 4)
57
Photo 9
Brazed part of the suction pipe
Screws of the outdoor fan motor
Discharge temperature thermistor
Soundproof felt
Brazed part of the discharge pipe
Page 58
HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
© Copyright 2014 MITSUBISHI ELECTRIC CORPORATION
Issued: Jul. 2017. No. OBH684 REVISED EDITION-D Issued: Oct. 2015. No. OBH684 REVISED EDITION-C Issued: Dec. 2014. No. OBH684 REVISED EDITION-B Issued: Apr. 2014. No. OBH684 REVISED EDITION-A Published: Feb. 2014. No. OBH684 Made in Japan
Specifications are subject to change without notice.
Loading...