Mitsubishi MUZ-FD25VA-E1, MUZ-FD25VAH-E1, MUZ-FD35VA-E1, MUZ-FD35VAH-E1, MUZ-FD50VA-E1 Service Manual

Page 1
SPLIT-TYPE AIR CONDITIONERS
OUTDOOR UNIT
Revision B:
• MUZ-FD50VA- E1 has been added.
Please void OBH489 REVISED EDITION-A.
SERVICE MANUAL
Models
MUZ-FD25VA ­MUZ-FD25VAH ­MUZ-FD35VA ­MUZ-FD35VAH ­MUZ-FD50VA -
E1
E1,E2
E1
E1
E1
HFC
utilized
R410A
No. OBH489
REVISED EDITION-B
MUZ-FD25/35
Indoor unit service manual MSZ-FD•VA Series (OBH488)
CONTENTS
1. TECHNICAL CHANGES ··································· 3
2. PART NAMES AND FUNCTIONS ····················· 4
3. SPECIFICATION ················································ 5
4. NOISE CRITERIA CURVES ······························ 8
5. OUTLINES AND DIMENSIONS ························ 9
6. WIRING DIAGRAM ·········································· 10
8. PERFORMANCE CURVES ····························· 15
9. ACTUATOR CONTROL ··································· 29
10. SERVICE FUNCTIONS ···································· 30
11. TROUBLESHOOTING ····································· 31
12. DISASSEMBLY INSTRUCTIONS ···················· 55
PARTS CATALOG (OBB489)
NOTE:
RoHS compliant products have <G> mark on the spec name plate.
Page 2
Revision A:
• MUZ-FD25VAH- E2 has been added.
• Power outlet has been corrected.
Revision B:
• MUZ-FD50VA- E1 has been added.
2
Page 3
1
TECHNICAL CHANGES
MUZ-FD25VA ­MUZ-FD25VAH ­MUZ-FD35VA ­MUZ-FD35VAH ­MUZ-FD50VA -
1. New model
MUZ-FD25VAH -
1. Power outlet
E1
E1
E1
E1
E1
E1
E1
:
12 A,
MUZ-FD25VAH -
E2
: 10 A
E2
3
Page 4
2
PART NAMES AND FUNCTIONS
MUZ-FD25VA MUZ-FD25VAH MUZ-FD35VA MUZ-FD35VAH
Air inlet
(back and side)
Piping
Drain hose
Air outlet
Drain outlet
MUZ-FD50VA
Air inlet
(back and side)
Piping
Drain hose
Air outlet
Drain outlet
ACCESSORIES
MUZ-FD25/35VA MUZ-FD50VA
Drain socket 1 1 Drain cap - 2
4
Page 5
3
Capacity Rated frequency (Min.-Max.)
Breaker Capacity A 10
Electrical data
Coeffi cient of performance (COP)
Compressor
Fan motor
Dimensions W × H × D mm 800 × 550 × 285 Weight kg 36
Special remarks
NOTE: Test conditions are based on ISO 5151. Cooling: Indoor Dry-bulb temperature 27°C Wet-bulb temperature 19°C Outdoor Dry-bulb temperature 35°C Heating: Indoor Dry-bulb temperature 20°C Outdoor Dry-bulb temperature 7°C Wet-bulb temperature 6°C Refrigerant piping length (one way): 5 m
SPECIFICATION
Outdoor model MUZ-FD25VA MUZ-FD25VAH MUZ-FD35VA MUZ-FD35VAH
Power supply Single phase, 230 V, 50 Hz
Cooling Heating 3.2 (1.5-5.5) 3.2 (1.5-6.3) 4.0 (1.5-6.3) 4.0 (1.3-7.7)
Power input 1 (Total)
Running current 1 (Total)
Power factor 1 (Total)
Starting current 1 (Total) A 2.9 4.0 3.9
1 (Total)
Model SNB130FGBH Output W 900
Current 1
Refrigeration oil (Model) cc 450 (NEO22)
Model RC0J50-EA
Current
Dehumidifi cation Cooling /h 1.4 2.0
Cooling
Air fl ow 1
Heating
Sound level 1
Cooling
Fan speed
Heating
Fan speed regulator 3 Refrigerant fi lling capacity (R410A) kg 1.15
1 Measured under rated operating frequency.
Cooling Heating 610 865 850 Cooling Heating 2.9 4.0 3.9 Cooling Heating 91 94 95
Cooling 5.15 4.12 4.19 Heating 5.25 4.62 4.71
Cooling Heating 2.30 3.33 3.23
Cooling
1
Heating 0.30 0.35
High
Low 1,086
High 2,016
Med. 1,776
Low 1,386 Cooling Heating 50
High
Low 490
High 870
Med. 770
Low 610
kW
W
A
%
A
A
3
/h
m
dB(A) 46
rpm
2.5 (1.1-3.5) 3.5 (1.1-4.0) 3.5 (0.8-4.0)
E1
: 12
E2
: 10
485 850 835
2.4 3.9 3.8
88 95 96
1.88 3.31 3.21
0.27 0.32
1,872
810
10 12
47
5
Page 6
Outdoor model MUZ-FD50VA
Power supply Single phase, 230 V, 50 Hz
Capacity Rated frequency (Min.-Max.)
Cooling Heating 5.8 (1.5-7.8)
kW
5.0 (1.5-5.8)
Breaker Capacity A 16
Power input 1 (Total)
Running current
Power factor 1 (Total)
Electrical data
1 (Total)
Cooling Heating 1,550 Cooling Heating 6.9 Cooling Heating 98
W
A
%
1,500
6.7
98
Starting current 1 (Total) A 6.9
Coeffi cient of performance (COP) 1 (Total)
Cooling 3.33
Heating 3.74 Model SNB172FDGH Output W 1,200
Compressor
Current
Cooling
1
Heating 5.62
A
5.40
Refrigeration oil (Model) cc 450 (NEO22) Model RC0J60-AA
Fan motor
Current 1
Cooling Heating
A 0.72
Dimensions W × H × D mm 840 × 850 × 330 Weight kg 55
Dehumidifi cation Cooling /h 1.7
Air fl ow 1
Cooling
Heating
High
Med. 2,940
Low 1,680
High 2,940
3
m
/h
Med. 2,940
Low 2,100
Sound level 1
Special remarks
Fan speed
Cooling
Heating
Cooling Heating 56
dB(A)
High
Med. 800
Low 480
High 800
rpm
Med. 800
54
Low 580 Fan speed regulator 2 Refrigerant fi lling capacity (R410A) kg 1.55
NOTE: Test conditions are based on ISO 5151. Cooling: Indoor Dry-bulb temperature 27°C Wet-bulb temperature 19°C Outdoor Dry-bulb temperature 35°C Heating: Indoor Dry-bulb temperature 20°C Outdoor Dry-bulb temperature 7°C Wet-bulb temperature 6°C Refrigerant piping length (one way): 5 m
1 Measured under rated operating frequency.
6
Page 7
Specifi cations and rating conditions of main electric parts
Item
Current transformer
Smoothing capacitor (C61, C62, C63) 620 F 420 V
Diode module
Fuse
Defrost heater (H) 230 V 130 W 230 V 130 W Intelligent power module (IPM) 20 A 600 V Expansion valve coil (LEV) DC 12 V Reactor (L61) 23.0 mH
Current-detecting resistor
Current-limiting PTC thermistor (PTC64, PTC65) 33 Terminal block (TB1, TB2) 3 P
Relay
R.V.coil (21S4) AC 220 - 240 V Heater protector (26H) Open 45°C Open 45°C IGBT (TR821) 30 A 600 V
(CT761, CT781) 15 A
(F701, F801, F901) T3.15AL250V
(R937, R938, R939) 430 m 2 W
Model
(DB61) 15 A 600 V (DB65) 25 A 600 V
(F61) T20AL250V
(R61, R62) 180 m 5 W (2 elements)
(R825) 25 m 5 W
(X63) 3 A 250 V (X64) 20 A 250 V (X66) 3 A 250 V 3 A 250 V
MUZ-FD25VA MUZ-FD25VAH MUZ-FD35VA MUZ-FD35VAH
(CT) 20 A
Model
Item
Current transformer
Smoothing capacitor (CB1, CB2, CB3) 560 F 450 V
Fuse
Expansion valve coil (LEV) DC 12 V
Intelligent power module
High pressure switch (HPS) ACB-DB156 Reactor (L) 600 H 20 A Power factor correct module (PFC) 20 A 600 V Current-limiting PTC thermistor (PTC64, PTC65) 33
Current-detecting resistor
Solenoid coil relay (SSR61) 0.5 A 600 V Terminal block (TB1, TB2) 3 P Relay (X64) 20 A 250 V R.V. coil (21S4) AC 220 - 240 V
(RS1, RS2, RS3, RS4)
(CT1, CT2) 20 A
(CT61) 20 A
(F64) T2.0AL250V
(F801) T3.15AL250V
(IPM) 15 A 600 V
(HC930) 3 A 600 V
(R937A, R937B) 1.1 2 W
MUZ-FD50VA
40 m 7 W (2 elements)
7
Page 8
4
NOISE CRITERIA CURVES
MUZ-FD25VA MUZ-FD25VAH
FUNCTION
COOLING HEATING
90
80
70
60
50
40
30
20
OCTAVE BAND SOUND PRESSURE LEVEL, 0dB re 0.0002 MICRO BAR
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
SPL(dB(A)) LINE
46
NC-10
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
MUZ-FD35VA MUZ-FD35VAH
FUNCTION
COOLING
HEATING
90
80
70
60
50
40
30
20
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
SPL(dB(A))
47 50
NC-10
LINE
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
MUZ-FD50VA
FUNCTION
COOLING HEATING
90
80
70
60
50
40
30
20
OCTAVE BAND SOUND PRESSURE LEVEL, 0dB re 0.0002 MICRO BAR
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
SPL(dB(A)) LINE
54 56
NC-10
Test conditions Cooling : Dry-bulb temperature 35 °C Heating : Dry-bulb temperature 7 °C Wet-bulb temperature 6 °C
OUTDOOR UNIT
1 m
MICROPHONE
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
8
Page 9
5
OUTLINES AND DIMENSIONS
MUZ-FD25VA MUZ-FD25VAH MUZ-FD35VA MUZ-FD35VAH
REQUIRED SPACE
344.5
285
550
44
Air in
2 holes 10 × 21
22.3
Handle
280
10
400
Air in
Air out
150
302.5 500 Bolt pitch for installation
800
Drain hole ø42 (25/35VA) Drain hole ø33 (25/35VAH)
40
17.5
69
Bolt pitch for
23
164.5
99.5
304-325
installation
Service port
100 mm or more
Open two sides of left, right, or rear side.
Service panel
Liquid refrigerant pipe joint Refrigerant pipe (flared) ø6.35
35°
Gas refrigerant pipe joint Refrigerant pipe (flared) ø9.52
170.5
Unit: mm
Basically open 100 mm or more without any obstruction in front and on both sides of the unit.
100 mm or more
350 mm or more
200 mm or more
43°
MUZ-FD50VA
299
66
51
34
Air in
330
170
850
515
Air in
Air out
121
500 840
Drain holes ø33
40
4 holes 10 × 21
80
REQUIRED SPACE
100 mm or more
360
Open as a rule 500 mm or more if the back, both sides and top are open
Open as a rule 500 mm or more if the front and both sides are open
100 mm or more 200 mm or more if there are obstacles to both sides
350 mm or more
Service panel
Liquid refrigerant pipe joint Refrigerant pipe
ø6.35
(flared)
430
30°
155
90
35°
Gas refrigerant pipe joint Refrigerant pipe
198
(flared)
ø12.7
9
Page 10
6
MUZ-FD25VA MUZ-FD35VA
WIRING DIAGRAM
10
Page 11
MUZ-FD25VAH MUZ-FD35VAH
11
Page 12
MUZ-FD50VA
12
Page 13
7
REFRIGERANT SYSTEM DIAGRAM
MUZ-FD25VA MUZ-FD25VAH MUZ-FD35VA MUZ-FD35VAH
Refrigerant pipe ø9.52 (with heat insulator)
Flared connection
Flared connection
Refrigerant pipe ø6.35 (with heat insulator)
Muffler
Stop valve (with service port)
Capillary tube ø
3.0×ø2.0×240
Stop valve (with strainar)
4-way valve
Discharge temperature thermistor RT62
LEV
Muffler
Compressor
Defrost thermistor RT61
Capillary tube ø
3.0×ø1.8×600(×2)
Outdoor heat exchanger
temperature Outdoor heat exchanger
thermistor
RT68
Ambient
temperature
thermistor
RT65
Strainer #100
R.V. coil heating ON cooling OFF
Refrigerant flow in cooling Refrigerant flow in heating
Unit: mm
MUZ-FD50VA
Refrigerant pipe (with heat insulator)
Flared connection
Flared connection
Refrigerant pipe ø6.35 (with heat insulator)
ø
12.7 4-way valve
Stop valve (with service port)
Receiver
Stop valve
Strainer
#100
Capillary tube
ø
3.6
Muffler
#100
Discharge temperature thermistor RT62
Compressor
×
ø
2.4×50
LEV
High-pressure switch
Defrost thermistor RT61
Strainer
#100
Refrigerant flow in cooling Refrigerant flow in heating
Outdoor heat exchanger
Outdoor heat exchanger temperature thermistor RT68
R.V. coil heating ON cooling OFF
Ambient temperature thermistor RT65
13
Page 14
MAX. REFRIGERANT PIPING LENGTH and MAX. HEIGHT DIFFERENCE
Refrigerant piping: m
MUZ-FD25 MUZ-FD35
Max. Length
A
20 12 9.52
Max. Height difference
B
MUZ-FD50 30 15 12.7
Indoor unit
Max. Height
difference
B
Max. Length A
Outdoor unit
Piping size O.D: mm
Gas Liquid
ADDITIONAL REFRIGERANT CHARGE (R410A: g)
Model
MUZ-FD25 MUZ-FD35
Outdoor unit
precharged
1,150
5 m 6 m 7 m 8 m 9 m 10 m 11 m 12 m 13 m 14 m 15 m 20 m
0 0 0 90 120 150 180 210 240 270 300 450
Refrigerant piping length (one way)
6.35
Calculation: X g = 30 g/m × (Refrigerant piping length (m) - 5)
Model
Outdoor unit
precharged
7 m 10 m 15 m 20 m 25 m 30 m
Refrigerant piping length (one way)
MUZ-FD50 1,550 0 90 240 390 540 690
Calculation: X g = 30 g/m × (Refrigerant piping length (m) – 7)
NOTE: Refrigerant piping exceeding 7 m requires additional refrigerant charge according to the calculation.
14
Page 15
PERFORMANCE CURVES8
MUZ-FD25VA MUZ-FD25VAH MUZ-FD35VA MUZ-FD35VAH MUZ-FD50VA
The standard specifications apply only to the operation of the air conditioner under normal conditions. Since operating condi-
tions vary according to the areas where these units are installed, the following information has been provided to clarify the operating characteristics of the air conditioner under the conditions indicated by the performance curve.
(1) GUARANTEED VOLTAGE
198 ~ 264 V, 50 Hz
(2) AIR FLOW
Air flow should be set at MAX.
(3) MAIN READINGS
(1) Indoor intake air wet-bulb temperature: °C [WB] (2) Indoor outlet air wet-bulb temperature: °C [WB] (3) Outdoor intake air dry-bulb temperature: °C [DB] (4) Total input: W (5) Indoor intake air dry-bulb temperature: °C [DB]
(7) Total input: W Indoor air wet/dry-bulb temperature difference on the left side of the following chart shows the difference between the indoor intake air wet/dry-bulb temperature and the indoor outlet air wet/dry-bulb temperature for your reference at service.
How to measure the indoor air wet-bulb / dry-bulb temperature difference
1. Attach at least 2 sets of wet and dry-bulb thermometers to the indoor air intake as shown in the figure, and at least 2 sets of wet and dry-bulb thermometers to the indoor air outlet. The thermometers must be attached to the position where air speed is high.
2. Attach at least 2 sets of wet and dry-bulb thermometers to the outdoor air intake.
Cover the thermometers to prevent direct rays of the sun.
3. Check that the air filter is cleaned.
4. Open windows and doors of room.
5. Press the EMERGENCY OPERATION switch once (twice) to start the EMERGENCY COOL (HEAT) MODE.
6. When system stabilizes after more than 15 minutes, measure temperature and take an average temperature.
7. 10 minutes later, measure temperature again and check that the temperature does not change.
}
}
Cooling
Heating(6) Outdoor intake air wet-bulb temperature: °C [WB]
INDOOR UNIT
Wet and dry-bulb thermometers FRONT VIEW
8-1. CAPACITY AND INPUT CURVES
6.5
6.0
5.5
5.1
4.6
difference (°C)
4.1
3.7
Indoor air Wet-bulb temperature
9.1
8.4
7.7
7.0
6.3
5.7
5.1
10.1
9.3
8.5
7.7
7.0
6.3
5.6
1.5
1.4
1.3
1.2
1.1
1.0
Capacity correction factors
0.9
-10-5 0 5 1015202530354045
OUTDOOR UNIT
Wet and dry-bulb thermometers BACK VIEW
Cooling capacity
Outdoor intake air Dry-bulb temperature(°C)
(
at Rated frequency)
Indoor intake air Wet-bulb temperature( )
26
24
22 20 18
MUZ-FD25VAH
MUZ-FD35VA
MUZ-FD35VAH
MUZ-FD50VA
MUZ-FD25VA
15
Page 16
9.3
8.0
6.7
5.3
MUZ-FD25VAH
7.7
7.0
6.3
5.7
5.1
4.5
MUZ-FD35VA
8.5
7.7
7.0
6.3
5.6
4.9
MUZ-FD35VAH
20.9
19.3
17.7
16.1
14.5
12.9
11.3
9.7
8.0
6.4
5.5
5.1
4.6
4.1
difference (°C)
3.7
3.3
Indoor air Wet-bulb temperature
MUZ-FD25VA
17.3
16.0
14.6
13.3
12.0
10.6
difference (°C)
Indoor air Dry-bulb temperature
1.3
1.2
1.1
1.0
0.9
Input correction factors
0.8
-10-5 0 5 1015202530354045
MUZ-FD50VA
25.6
23.7
21.7
19.7
17.7
15.8
13.8
11.8
1.3
1.2
1.1
1.0
0.9
0.8
0.7
0.6
9.9
0.5
Capacity correction factor
7.9
0.4
-20 -15 -10 -5 0 5 10 15
Total input (Cooling :
at Rated frequency
)
Indoor intake air Wet-bulb temperature(°C)
Outdoor intake air Dry-bulb temperature (°C)
Heating capacity (
Indoor intake air Dry-bulb te
at Rated frequency)
mperature ( )
Outdoor intake air Wet-bulb temperature (°C)
22
26
24
20 18
15
20 26
MUZ-FD35VA
MUZ-FD25VAH
MUZ-FD25VA
17.3
16.0
14.6
13.3
12.0
10.6
9.3
8.0
difference (°C)
6.7
5.3
Indoor air Dry-bulb temperature
20.9
19.3
17.7
16.1
14.5
12.9
11.3
9.7
8.0
6.4
MUZ-FD35VAH
MUZ-FD50VA
25.6
23.7
21.7
19.7
17.7
15.8
13.8
11.8
1.3
1.2
1.1
1.0
0.9
0.8
0.7
0.6
Input correction factor
9.9
0.5
7.9
0.4
Total input (Heating :
r Dry-
ke ai
inta
Indoor
at Rated frequency
bulb te
)
mperature (
26
)
°C
20 15
-20 -15 -10 -5 0 5 10 15 Outdoor intake air Wet-bulb temperature (°C)
MUZ-FD25VA
MUZ-FD25VAH
MUZ-FD35VAH
MUZ-FD35VA
MUZ-FD50VA
NOTE: The above broken lines are for the heating operation without any frost and defrost operation.
16
Page 17
8-2. CAPACITY AND INPUT CORRECTION BY OPERATIONAL FREQUENCY OF COMPRESSOR
MUZ-FD25VA MUZ-FD25VAH
Correction of Cooling capacity
1.5
1.0
0.5
Capacity correction factors
0.0 0 50 100 150(Hz)
The operational frequency of compressor
MUZ-FD35VA
Correction of Cooling capacity
1.5
1.0
0.5
Capacity correction factors
0.0 0 50 100 150(Hz)
The operational frequency of compressor
Correction of Cooling input
2.5
2.0
1.5
1.0
0.5
Input correction factors
0.0 0 50 100 150(Hz)
The operational frequency of compressor
Correction of Cooling input
1.5
1.0
0.5
Input correction factors
0.0 0 50 100 150(Hz)
The operational frequency of compressor
Correction of Heating capacity
2.0
1.5
1.0
0.5
Capacity correction factors
0.0 0 50 100 150(Hz)
The operational frequency of compressor
Correction of Heating capacity
2.0
1.5
1.0
0.5
Capacity correction factors
0.0 0 50 100 150(Hz)
The operational frequency of compressor
Correction of Heating input
4
3
2
1
Input correction factors
0
0 50 100 150(Hz)
The operational frequency of compressor
Correction of Heating input
3
2
1
Capacity correction factors
0
0 50 100 150(Hz)
The operational frequency of compressor
MUZ-FD35VAH
Correction of Cooling capacity
1.5
1.0
0.5
Capacity correction factors
0.0 0 50 100 150(Hz)
The operational frequency of compressor
MUZ-FD50VA
Correction of Cooling capacity
1.5
1.0
0.5
Capacity correction factors
0.0 0 50 100
The operational frequency of
compressor (Hz)
Correction of Cooling input
1.5
1.0
0.5
Input correction factors
0.0 0 50 100 150(Hz)
The operational frequency of compressor
Correction of Cooling input
2.0
1.5
1.0
0.5
Input correction factors
0.0 0 50 100
The operational frequency of
compressor (Hz)
Correction of Heating capacity
2.0
1.5
1.0
0.5
Capacity correction factors
0.0 0 50 100 150(Hz)
The operational frequency of compressor
Correction of Heating capacity
1.5
1.0
0.5
Capacity correction factors
0.0 0 50 100 150
The operational frequency of
compressor (Hz)
Correction of Heating input
3
2
1
Capacity correction factors
0
0 50 100 150(Hz)
The operational frequency of compressor
Correction of Heating input
2.0
1.5
1.0
0.5
Capacity correction factors
0.0 0 50 100 150
The operational frequency of
compressor (Hz)
17
Page 18
8-3. TEST RUN OPERATION (How to operate fixed-frequency operation)
1. Press EMERGENCY OPERATION switch to start COOL or HEAT mode (COOL: Press once, HEAT: Press twice).
2. Test run operation starts and continues to operate for 30 minutes.
3. Compressor operates at rated frequency in COOL mode or 58 Hz in HEAT mode.
4. Indoor fan operates at High speed.
5. After 30 minutes, test run operation finishes and EMERGENCY OPERATION starts (operation frequency of compressor var­ies).
6. To cancel test run operation (EMERGENCY OPERATION), press EMERGENCY OPERATION switch or any button on remote controller.
8-4. OUTDOOR LOW PRESSURE AND OUTDOOR UNIT CURRENT
COOL operation
Both indoor and outdoor unit are under the same temperature/
humidity condition.
Operation: TEST RUN OPERATION (Refer to 8-3.)
Dry-bulb temperature (°C) Relative humidity (%)
20 50 25 60 30 70
Outdoor low pressure
MUZ-FD25VA MUZ-FD25VAH
1.4
1.2
1.0
MPa [Gauge]
0.8
0.6
0.4
0.2 15 20 25 30 35
50 60 70
Ambient temperature(°C) Ambient humidity(%)
MUZ-FD50VA
1.4
1.2
1.0
MPa [Gauge]
0.8
0.6
0.4
0.2
15 20 25 30 35
50 60 70
Ambient temperature(°C) Ambient humidity(%)
14 12 10 8 6 4
14 12 10 8 6 4
[Gauge]
2
kgf/cm
[Gauge]
2
kgf/cm
MUZ-FD35VA
1.4
1.2
1.0
MPa [Gauge]
0.8
0.6
0.4
0.2 15 20 25 30 35
50 60 70
Ambient temperature(°C) Ambient humidity(%)
14 12 10 8 6 4
[Gauge]
2
kgf/cm
MUZ-FD35VAH
1.4
1.2
1.0
MPa [Gauge]
0.8
0.6
0.4
0.2 15 20 25 30 35
50 60 70
Ambient temperature(°C) Ambient humidity(%)
14 12 10 8 6 4
[Gauge]
2
kgf/cm
NOTE: The unit of pressure has been changed to MPa on the international system of units (SI unit system)
The conversion factor is: 1 (MPa [Gauge]) = 10.2 (kgf/cm
2
[Gauge])
18
Page 19
Outdoor unit current
MUZ-FD25VA MUZ-FD25VAH
(A) (A)
2.4
2.2
2.0
1.8 15 205025
18
MUZ-FD50VA
(A)
6.5
6.0
5.5
5.0
4.5 15 20 25 30 35
60 Ambient temperature(°C) Ambient humidity(%)
50 60 70
Ambient temperature (°C) Ambient humidity (%)
3230
35(°C)
70 (%)
MUZ-FD35VA
4.0
3.5
3.0
2.5 15 205025
18
Ambient temperature(°C) Ambient humidity(%)
60
3230
35(°C)
70 (%)
MUZ-FD35VAH
(A)
4.0
3.5
3.0
2.5 15 205025
18
Ambient temperature(°C) Ambient humidity(%)
60
3230
35(°C)
70 (%)
HEAT operation
Condition:
Dry bulb temperature (°C) 20.0 2 7 15 20.0
Wet bulb temperature (°C) 14.5 1 6 12 14.5
Operation: Test run operation (Refer to 8-3.)
Outdoor unit current
MUZ-FD25VA MUZ-FD25VAH
6.0
(A) (A)
5.5
5.0
4.5
4.0
MUZ-FD50VA
(A)
5 10152025
Ambient temperature(°C)
8.5
8.0
7.5
Indoor Outdoor
MUZ-FD35VA
6.0
5.5
5.0
4.5
4.0 2
510152025
Ambient temperature(°C)
MUZ-FD35VAH
(A)
6.0
5.5
5.0
4.5
4.0 2
5 10152025
Ambient temperature(°C)
7.0
6.5
6.0 02 5 10 15 20 25
Ambient temperature (°C)
19
Page 20
PERFORMANCE DATA COOL operation at Rated frequency
MUZ-FD25VA MUZ-FD25VAH
CAPACITY: 2.5 kW SHF: 0.85 INPUT: 485 W
INDOOR
DB (°C)
INDOOR
WB (°C)
21 18 2.94 1.97 0.67 388 2.81 1.88 0.67 407 2.70 1.81 0.67 427 2.60 1.74 0.67 446
21 20 3.06 1.68 0.55 407 2.94 1.62 0.55 432 2.85 1.57 0.55 441 2.75 1.51 0.55 461
22 18 2.94 2.09 0.71 388 2.81 2.00 0.71 407 2.70 1.92 0.71 427 2.60 1.85 0.71 446
22 20 3.06 1.81 0.59 407 2.94 1.73 0.59 432 2.85 1.68 0.59 441 2.75 1.62 0.59 461
22 22 3.19 1.50 0.47 422 3.08 1.45 0.47 449 3.00 1.41 0.47 461 2.88 1.35 0.47 480
23 18 2.94 2.20 0.75 388 2.81 2.11 0.75 407 2.70 2.03 0.75 427 2.60 1.95 0.75 446
23 20 3.06 1.93 0.63 407 2.94 1.85 0.63 432 2.85 1.80 0.63 441 2.75 1.73 0.63 461
23 22 3.19 1.63 0.51 422 3.08 1.57 0.51 449 3.00 1.53 0.51 461 2.88 1.47 0.51 480
24 18 2.94 2.32 0.79 388 2.81 2.22 0.79 407 2.70 2.13 0.79 427 2.60 2.05 0.79 446
24 20 3.06 2.05 0.67 407 2.94 1.97 0.67 432 2.85 1.91 0.67 441 2.75 1.84 0.67 461
24 22 3.19 1.75 0.55 422 3.08 1.69 0.55 449 3.00 1.65 0.55 461 2.88 1.58 0.55 480
24 24 3.35 1.44 0.43 441 3.23 1.39 0.43 466 3.15 1.35 0.43 480 3.05 1.31 0.43 504
25 18 2.94 2.44 0.83 388 2.81 2.33 0.83 407 2.70 2.24 0.83 427 2.60 2.16 0.83 446
25 20 3.06 2.17 0.71 407 2.94 2.09 0.71 432 2.85 2.02 0.71 441 2.75 1.95 0.71 461
25 22 3.19 1.88 0.59 422 3.08 1.81 0.59 449 3.00 1.77 0.59 461 2.88 1.70 0.59 480
25 24 3.35 1.57 0.47 441 3.23 1.52 0.47 466 3.15 1.48 0.47 480 3.05 1.43 0.47 504
26 18 2.94 2.56 0.87 388 2.81 2.45 0.87 407 2.70 2.35 0.87 427 2.60 2.26 0.87 446
26 20 3.06 2.30 0.75 407 2.94 2.20 0.75 432 2.85 2.14 0.75 441 2.75 2.06 0.75 461
26 22 3.19 2.01 0.63 422 3.08 1.94 0.63 449 3.00 1.89 0.63 461 2.88 1.81 0.63 480
26 24 3.35 1.71 0.51 441 3.23 1.64 0.51 466 3.15 1.61 0.51 480 3.05 1.56 0.51 504
26 26 3.45 1.35 0.39 466 3.35 1.31 0.39 490 3.30 1.29 0.39 504 3.20 1.25 0.39 519
27 18 2.94 2.67 0.91 388 2.81 2.56 0.91 407 2.70 2.46 0.91 427 2.60 2.37 0.91 446
27 20 3.06 2.42 0.79 407 2.94 2.32 0.79 432 2.85 2.25 0.79 441 2.75 2.17 0.79 461
27 22 3.19 2.14 0.67 422 3.08 2.06 0.67 449 3.00 2.01 0.67 461 2.88 1.93 0.67 480
27 24 3.35 1.84 0.55 441 3.23 1.77 0.55 466 3.15 1.73 0.55 480 3.05 1.68 0.55 504
27 26 3.45 1.48 0.43 466 3.35 1.44 0.43 490 3.30 1.42 0.43 504 3.20 1.38 0.43 519
28 18 2.94 2.79 0.95 388 2.81 2.67 0.95 407 2.70 2.57 0.95 427 2.60 2.47 0.95 446
28 20 3.06 2.54 0.83 407 2.94 2.44 0.83 432 2.85 2.37 0.83 441 2.75 2.28 0.83 461
28 22 3.19 2.26 0.71 422 3.08 2.18 0.71 449 3.00 2.13 0.71 461 2.88 2.04 0.71 480
28 24 3.35 1.98 0.59 441 3.23 1.90 0.59 466 3.15 1.86 0.59 480 3.05 1.80 0.59 504
28 26 3.45 1.62 0.47 466 3.35 1.57 0.47 490 3.30 1.55 0.47 504 3.20 1.50 0.47 519
29 18 2.94 2.91 0.99 388 2.81 2.78 0.99 407 2.70 2.67 0.99 427 2.60 2.57 0.99 446
29 20 3.06 2.66 0.87 407 2.94 2.56 0.87 432 2.85 2.48 0.87 441 2.75 2.39 0.87 461
29 22 3.19 2.39 0.75 422 3.08 2.31 0.75 449 3.00 2.25 0.75 461 2.88 2.16 0.75 480
29 24 3.35 2.11 0.63 441 3.23 2.03 0.63 466 3.15 1.98 0.63 480 3.05 1.92 0.63 504
29 26 3.45 1.76 0.51 466 3.35 1.71 0.51 490 3.30 1.68 0.51 504 3.20 1.63 0.51 519
30 18 2.94 2.94 1.00 388 2.81 2.81 1.00 407 2.70 2.70 1.00 427 2.60 2.60 1.00 446
30 20 3.06 2.79 0.91 407 2.94 2.67 0.91 432 2.85 2.59 0.91 441 2.75 2.50 0.91 461
30 22 3.19 2.52 0.79 422 3.08 2.43 0.79 449 3.00 2.37 0.79 461 2.88 2.27 0.79 480
30 24 3.35 2.24 0.67 441 3.23 2.16 0.67 466 3.15 2.11 0.67 480 3.05 2.04 0.67 504
30 26 3.45 1.90 0.55 466 3.35 1.84 0.55 490 3.30 1.82 0.55 504 3.20 1.76 0.55 519
31 18 2.94 2.94 1.00 388 2.81 2.81 1.00 407 2.70 2.70 1.00 427 2.60 2.60 1.00 446
31 20 3.06 2.91 0.95 407 2.94 2.79 0.95 432 2.85 2.71 0.95 441 2.75 2.61 0.95 461
31 22 3.19 2.65 0.83 422 3.08 2.55 0.83 449 3.00 2.49 0.83 461 2.88 2.39 0.83 480
31 24 3.35 2.38 0.71 441 3.23 2.29 0.71 466 3.15 2.24 0.71 480 3.05 2.17 0.71 504
31 26 3.45 2.04 0.59 466 3.35 1.98 0.59 490 3.30 1.95 0.59 504 3.20 1.89 0.59 519
32 18 2.94 2.94 1.00 388 2.81 2.81 1.00 407 2.70 2.70 1.00 427 2.60 2.60 1.00 446
32 20 3.06 3.03 0.99 407 2.94 2.91 0.99 432 2.85 2.82 0.99 441 2.75 2.72 0.99 461
32 22 3.19 2.77 0.87 422 3.08 2.68 0.87 449 3.00 2.61 0.87 461 2.88 2.50 0.87 480
32 24 3.35 2.51 0.75 441 3.23 2.42 0.75 466 3.15 2.36 0.75 480 3.05 2.29 0.75 504
32 26 3.45 2.17 0.63 466 3.35 2.11 0.63 490 3.30 2.08 0.63 504 3.20 2.02 0.63 519
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT
21 25 27 30
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
OUTDOOR DB (°C)
2020
Page 21
PERFORMANCE DATA COOL operation at Rated frequency
MUZ-FD25VA MUZ-FD25VAH
CAPACITY: 2.5 kW SHF: 0.85 INPUT: 485 W
INDOOR
DB (°C)
INDOOR
WB (°C)
21 18 2.45 1.64 0.67 475 2.25 1.51 0.67 504 2.08 1.39 0.67 524
21 20 2.58 1.42 0.55 495 2.40 1.32 0.55 519 2.23 1.22 0.55 548
22 18 2.45 1.74 0.71 475 2.25 1.60 0.71 504 2.08 1.47 0.71 524
22 20 2.58 1.52 0.59 495 2.40 1.42 0.59 519 2.23 1.31 0.59 548
22 22 2.73 1.28 0.47 514 2.55 1.20 0.47 543 2.38 1.12 0.47 563
23 18 2.45 1.84 0.75 475 2.25 1.69 0.75 504 2.08 1.56 0.75 524
23 20 2.58 1.62 0.63 495 2.40 1.51 0.63 519 2.23 1.40 0.63 548
23 22 2.73 1.39 0.51 514 2.55 1.30 0.51 543 2.38 1.21 0.51 563
24 18 2.45 1.94 0.79 475 2.25 1.78 0.79 504 2.08 1.64 0.79 524
24 20 2.58 1.73 0.67 495 2.40 1.61 0.67 519 2.23 1.49 0.67 548
24 22 2.73 1.50 0.55 514 2.55 1.40 0.55 543 2.38 1.31 0.55 563
24 24 2.88 1.24 0.43 534 2.70 1.16 0.43 558 2.55 1.10 0.43 582
25 18 2.45 2.03 0.83 475 2.25 1.87 0.83 504 2.08 1.72 0.83 524
25 20 2.58 1.83 0.71 495 2.40 1.70 0.71 519 2.23 1.58 0.71 548
25 22 2.73 1.61 0.59 514 2.55 1.50 0.59 543 2.38 1.40 0.59 563
25 24 2.88 1.35 0.47 534 2.70 1.27 0.47 558 2.55 1.20 0.47 582
26 18 2.45 2.13 0.87 475 2.25 1.96 0.87 504 2.08 1.81 0.87 524
26 20 2.58 1.93 0.75 495 2.40 1.80 0.75 519 2.23 1.67 0.75 548
26 22 2.73 1.72 0.63 514 2.55 1.61 0.63 543 2.38 1.50 0.63 563
26 24 2.88 1.47 0.51 534 2.70 1.38 0.51 558 2.55 1.30 0.51 582
26 26 3.03 1.18 0.39 553 2.85 1.11 0.39 577 2.68 1.04 0.39 601
27 18 2.45 2.23 0.91 475 2.25 2.05 0.91 504 2.08 1.89 0.91 524
27 20 2.58 2.03 0.79 495 2.40 1.90 0.79 519 2.23 1.76 0.79 548
27 22 2.73 1.83 0.67 514 2.55 1.71 0.67 543 2.38 1.59 0.67 563
27 24 2.88 1.58 0.55 534 2.70 1.49 0.55 558 2.55 1.40 0.55 582
27 26 3.03 1.30 0.43 553 2.85 1.23 0.43 577 2.68 1.15 0.43 601
28 18 2.45 2.33 0.95 475 2.25 2.14 0.95 504 2.08 1.97 0.95 524
28 20 2.58 2.14 0.83 495 2.40 1.99 0.83 519 2.23 1.85 0.83 548
28 22 2.73 1.93 0.71 514 2.55 1.81 0.71 543 2.38 1.69 0.71 563
28 24 2.88 1.70 0.59 534 2.70 1.59 0.59 558 2.55 1.50 0.59 582
28 26 3.03 1.42 0.47 553 2.85 1.34 0.47 577 2.68 1.26 0.47 601
29 18 2.45 2.43 0.99 475 2.25 2.23 0.99 504 2.08 2.05 0.99 524
29 20 2.58 2.24 0.87 495 2.40 2.09 0.87 519 2.23 1.94 0.87 548
29 22 2.73 2.04 0.75 514 2.55 1.91 0.75 543 2.38 1.78 0.75 563
29 24 2.88 1.81 0.63 534 2.70 1.70 0.63 558 2.55 1.61 0.63 582
29 26 3.03 1.54 0.51 553 2.85 1.45 0.51 577 2.68 1.36 0.51 601
30 18 2.45 2.45 1.00 475 2.25 2.25 1.00 504 2.08 2.08 1.00 524
30 20 2.58 2.34 0.91 495 2.40 2.18 0.91 519 2.23 2.02 0.91 548
30 22 2.73 2.15 0.79 514 2.55 2.01 0.79 543 2.38 1.88 0.79 563
30 24 2.88 1.93 0.67 534 2.70 1.81 0.67 558 2.55 1.71 0.67 582
30 26 3.03 1.66 0.55 553 2.85 1.57 0.55 577 2.68 1.47 0.55 601
31 18 2.45 2.45 1.00 475 2.25 2.25 1.00 504 2.08 2.08 1.00 524
31 20 2.58 2.45 0.95 495 2.40 2.28 0.95 519 2.23 2.11 0.95 548
31 22 2.73 2.26 0.83 514 2.55 2.12 0.83 543 2.38 1.97 0.83 563
31 24 2.88 2.04 0.71 534 2.70 1.92 0.71 558 2.55 1.81 0.71 582
31 26 3.03 1.78 0.59 553 2.85 1.68 0.59 577 2.68 1.58 0.59 601
32 18 2.45 2.45 1.00 475 2.25 2.25 1.00 504 2.08 2.08 1.00 524
32 20 2.58 2.55 0.99 495 2.40 2.38 0.99 519 2.23 2.20 0.99 548
32 22 2.73 2.37 0.87 514 2.55 2.22 0.87 543 2.38 2.07 0.87 563
32 24 2.88 2.16 0.75 534 2.70 2.03 0.75 558 2.55 1.91 0.75 582
32 26 3.03 1.91 0.63 553 2.85 1.80 0.63 577 2.68 1.69 0.63 601
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT
35 40 46
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
OUTDOOR DB (°C)
2121
Page 22
PERFORMANCE DATA COOL operation at Rated frequency
MUZ-FD35VA
CAPACITY: 3.5 kW SHF: 0.85 INPUT: 850 W
INDOOR
DB (°C)
INDOOR
WB (°C)
21 18 4.11 2.76 0.67 680 3.94 2.64 0.67 714 3.78 2.53 0.67 748 3.64 2.44 0.67 782
21 20 4.29 2.36 0.55 714 4.11 2.26 0.55 757 3.99 2.19 0.55 774 3.85 2.12 0.55 808
22 18 4.11 2.92 0.71 680 3.94 2.80 0.71 714 3.78 2.68 0.71 748 3.64 2.58 0.71 782
22 20 4.29 2.53 0.59 714 4.11 2.43 0.59 757 3.99 2.35 0.59 774 3.85 2.27 0.59 808
22 22 4.46 2.10 0.47 740 4.31 2.02 0.47 786 4.20 1.97 0.47 808 4.03 1.89 0.47 842
23 18 4.11 3.08 0.75 680 3.94 2.95 0.75 714 3.78 2.84 0.75 748 3.64 2.73 0.75 782
23 20 4.29 2.70 0.63 714 4.11 2.59 0.63 757 3.99 2.51 0.63 774 3.85 2.43 0.63 808
23 22 4.46 2.28 0.51 740 4.31 2.20 0.51 786 4.20 2.14 0.51 808 4.03 2.05 0.51 842
24 18 4.11 3.25 0.79 680 3.94 3.11 0.79 714 3.78 2.99 0.79 748 3.64 2.88 0.79 782
24 20 4.29 2.87 0.67 714 4.11 2.76 0.67 757 3.99 2.67 0.67 774 3.85 2.58 0.67 808
24 22 4.46 2.45 0.55 740 4.31 2.37 0.55 786 4.20 2.31 0.55 808 4.03 2.21 0.55 842
24 24 4.69 2.02 0.43 774 4.52 1.94 0.43 816 4.41 1.90 0.43 842 4.27 1.84 0.43 884
25 18 4.11 3.41 0.83 680 3.94 3.27 0.83 714 3.78 3.14 0.83 748 3.64 3.02 0.83 782
25 20 4.29 3.04 0.71 714 4.11 2.92 0.71 757 3.99 2.83 0.71 774 3.85 2.73 0.71 808
25 22 4.46 2.63 0.59 740 4.31 2.54 0.59 786 4.20 2.48 0.59 808 4.03 2.37 0.59 842
25 24 4.69 2.20 0.47 774 4.52 2.12 0.47 816 4.41 2.07 0.47 842 4.27 2.01 0.47 884
26 18 4.11 3.58 0.87 680 3.94 3.43 0.87 714 3.78 3.29 0.87 748 3.64 3.17 0.87 782
26 20 4.29 3.22 0.75 714 4.11 3.08 0.75 757 3.99 2.99 0.75 774 3.85 2.89 0.75 808
26 22 4.46 2.81 0.63 740 4.31 2.71 0.63 786 4.20 2.65 0.63 808 4.03 2.54 0.63 842
26 24 4.69 2.39 0.51 774 4.52 2.30 0.51 816 4.41 2.25 0.51 842 4.27 2.18 0.51 884
26 26 4.83 1.88 0.39 816 4.69 1.83 0.39 859 4.62 1.80 0.39 884 4.48 1.75 0.39 910
27 18 4.11 3.74 0.91 680 3.94 3.58 0.91 714 3.78 3.44 0.91 748 3.64 3.31 0.91 782
27 20 4.29 3.39 0.79 714 4.11 3.25 0.79 757 3.99 3.15 0.79 774 3.85 3.04 0.79 808
27 22 4.46 2.99 0.67 740 4.31 2.88 0.67 786 4.20 2.81 0.67 808 4.03 2.70 0.67 842
27 24 4.69 2.58 0.55 774 4.52 2.48 0.55 816 4.41 2.43 0.55 842 4.27 2.35 0.55 884
27 26 4.83 2.08 0.43 816 4.69 2.02 0.43 859 4.62 1.99 0.43 884 4.48 1.93 0.43 910
28 18 4.11 3.91 0.95 680 3.94 3.74 0.95 714 3.78 3.59 0.95 748 3.64 3.46 0.95 782
28 20 4.29 3.56 0.83 714 4.11 3.41 0.83 757 3.99 3.31 0.83 774 3.85 3.20 0.83 808
28 22 4.46 3.17 0.71 740 4.31 3.06 0.71 786 4.20 2.98 0.71 808 4.03 2.86 0.71 842
28 24 4.69 2.77 0.59 774 4.52 2.66 0.59 816 4.41 2.60 0.59 842 4.27 2.52 0.59 884
28 26 4.83 2.27 0.47 816 4.69 2.20 0.47 859 4.62 2.17 0.47 884 4.48 2.11 0.47 910
29 18 4.11 4.07 0.99 680 3.94 3.90 0.99 714 3.78 3.74 0.99 748 3.64 3.60 0.99 782
29 20 4.29 3.73 0.87 714 4.11 3.58 0.87 757 3.99 3.47 0.87 774 3.85 3.35 0.87 808
29 22 4.46 3.35 0.75 740 4.31 3.23 0.75 786 4.20 3.15 0.75 808 4.03 3.02 0.75 842
29 24 4.69 2.95 0.63 774 4.52 2.84 0.63 816 4.41 2.78 0.63 842 4.27 2.69 0.63 884
29 26 4.83 2.46 0.51 816 4.69 2.39 0.51 859 4.62 2.36 0.51 884 4.48 2.28 0.51 910
30 18 4.11 4.11 1.00 680 3.94 3.94 1.00 714 3.78 3.78 1.00 748 3.64 3.64 1.00 782
30 20 4.29 3.90 0.91 714 4.11 3.74 0.91 757 3.99 3.63 0.91 774 3.85 3.50 0.91 808
30 22 4.46 3.53 0.79 740 4.31 3.40 0.79 786 4.20 3.32 0.79 808 4.03 3.18 0.79 842
30 24 4.69 3.14 0.67 774 4.52 3.03 0.67 816 4.41 2.95 0.67 842 4.27 2.86 0.67 884
30 26 4.83 2.66 0.55 816 4.69 2.58 0.55 859 4.62 2.54 0.55 884 4.48 2.46 0.55 910
31 18 4.11 4.11 1.00 680 3.94 3.94 1.00 714 3.78 3.78 1.00 748 3.64 3.64 1.00 782
31 20 4.29 4.07 0.95 714 4.11 3.91 0.95 757 3.99 3.79 0.95 774 3.85 3.66 0.95 808
31 22 4.46 3.70 0.83 740 4.31 3.57 0.83 786 4.20 3.49 0.83 808 4.03 3.34 0.83 842
31 24 4.69 3.33 0.71 774 4.52 3.21 0.71 816 4.41 3.13 0.71 842 4.27 3.03 0.71 884
31 26 4.83 2.85 0.59 816 4.69 2.77 0.59 859 4.62 2.73 0.59 884 4.48 2.64 0.59 910
32 18 4.11 4.11 1.00 680 3.94 3.94 1.00 714 3.78 3.78 1.00 748 3.64 3.64 1.00 782
32 20 4.29 4.24 0.99 714 4.11 4.07 0.99 757 3.99 3.95 0.99 774 3.85 3.81 0.99 808
32 22 4.46 3.88 0.87 740 4.31 3.75 0.87 786 4.20 3.65 0.87 808 4.03 3.50 0.87 842
32 24 4.69 3.52 0.75 774 4.52 3.39 0.75 816 4.41 3.31 0.75 842 4.27 3.20 0.75 884
32 26 4.83 3.04 0.63 816 4.69 2.95 0.63 859 4.62 2.91 0.63 884 4.48 2.82 0.63 910
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT
21 25 27 30
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
OUTDOOR DB (°C)
2222
Page 23
PERFORMANCE DATA COOL operation at Rated frequency
MUZ-FD35VA
CAPACITY: 3.5 kW SHF: 0.85 INPUT: 850 W
INDOOR
DB (°C)
INDOOR
WB (°C)
21 18 3.43 2.30 0.67 833 3.15 2.11 0.67 884 2.91 1.95 0.67 918
21 20 3.61 1.98 0.55 867 3.36 1.85 0.55 910 3.12 1.71 0.55 961
22 18 3.43 2.44 0.71 833 3.15 2.24 0.71 884 2.91 2.06 0.71 918
22 20 3.61 2.13 0.59 867 3.36 1.98 0.59 910 3.12 1.84 0.59 961
22 22 3.82 1.79 0.47 901 3.57 1.68 0.47 952 3.33 1.56 0.47 986
23 18 3.43 2.57 0.75 833 3.15 2.36 0.75 884 2.91 2.18 0.75 918
23 20 3.61 2.27 0.63 867 3.36 2.12 0.63 910 3.12 1.96 0.63 961
23 22 3.82 1.95 0.51 901 3.57 1.82 0.51 952 3.33 1.70 0.51 986
24 18 3.43 2.71 0.79 833 3.15 2.49 0.79 884 2.91 2.29 0.79 918
24 20 3.61 2.42 0.67 867 3.36 2.25 0.67 910 3.12 2.09 0.67 961
24 22 3.82 2.10 0.55 901 3.57 1.96 0.55 952 3.33 1.83 0.55 986
24 24 4.03 1.73 0.43 935 3.78 1.63 0.43 978 3.57 1.54 0.43 1020
25 18 3.43 2.85 0.83 833 3.15 2.61 0.83 884 2.91 2.41 0.83 918
25 20 3.61 2.56 0.71 867 3.36 2.39 0.71 910 3.12 2.21 0.71 961
25 22 3.82 2.25 0.59 901 3.57 2.11 0.59 952 3.33 1.96 0.59 986
25 24 4.03 1.89 0.47 935 3.78 1.78 0.47 978 3.57 1.68 0.47 1020
26 18 3.43 2.98 0.87 833 3.15 2.74 0.87 884 2.91 2.53 0.87 918
26 20 3.61 2.70 0.75 867 3.36 2.52 0.75 910 3.12 2.34 0.75 961
26 22 3.82 2.40 0.63 901 3.57 2.25 0.63 952 3.33 2.09 0.63 986
26 24 4.03 2.05 0.51 935 3.78 1.93 0.51 978 3.57 1.82 0.51 1020
26 26 4.24 1.65 0.39 969 3.99 1.56 0.39 1012 3.75 1.46 0.39 1054
27 18 3.43 3.12 0.91 833 3.15 2.87 0.91 884 2.91 2.64 0.91 918
27 20 3.61 2.85 0.79 867 3.36 2.65 0.79 910 3.12 2.46 0.79 961
27 22 3.82 2.56 0.67 901 3.57 2.39 0.67 952 3.33 2.23 0.67 986
27 24 4.03 2.21 0.55 935 3.78 2.08 0.55 978 3.57 1.96 0.55 1020
27 26 4.24 1.82 0.43 969 3.99 1.72 0.43 1012 3.75 1.61 0.43 1054
28 18 3.43 3.26 0.95 833 3.15 2.99 0.95 884 2.91 2.76 0.95 918
28 20 3.61 2.99 0.83 867 3.36 2.79 0.83 910 3.12 2.59 0.83 961
28 22 3.82 2.71 0.71 901 3.57 2.53 0.71 952 3.33 2.36 0.71 986
28 24 4.03 2.37 0.59 935 3.78 2.23 0.59 978 3.57 2.11 0.59 1020
28 26 4.24 1.99 0.47 969 3.99 1.88 0.47 1012 3.75 1.76 0.47 1054
29 18 3.43 3.40 0.99 833 3.15 3.12 0.99 884 2.91 2.88 0.99 918
29 20 3.61 3.14 0.87 867 3.36 2.92 0.87 910 3.12 2.71 0.87 961
29 22 3.82 2.86 0.75 901 3.57 2.68 0.75 952 3.33 2.49 0.75 986
29 24 4.03 2.54 0.63 935 3.78 2.38 0.63 978 3.57 2.25 0.63 1020
29 26 4.24 2.16 0.51 969 3.99 2.03 0.51 1012 3.75 1.91 0.51 1054
30 18 3.43 3.43 1.00 833 3.15 3.15 1.00 884 2.91 2.91 1.00 918
30 20 3.61 3.28 0.91 867 3.36 3.06 0.91 910 3.12 2.83 0.91 961
30 22 3.82 3.01 0.79 901 3.57 2.82 0.79 952 3.33 2.63 0.79 986
30 24 4.03 2.70 0.67 935 3.78 2.53 0.67 978 3.57 2.39 0.67 1020
30 26 4.24 2.33 0.55 969 3.99 2.19 0.55 1012 3.75 2.06 0.55 1054
31 18 3.43 3.43 1.00 833 3.15 3.15 1.00 884 2.91 2.91 1.00 918
31 20 3.61 3.42 0.95 867 3.36 3.19 0.95 910 3.12 2.96 0.95 961
31 22 3.82 3.17 0.83 901 3.57 2.96 0.83 952 3.33 2.76 0.83 986
31 24 4.03 2.86 0.71 935 3.78 2.68 0.71 978 3.57 2.53 0.71 1020
31 26 4.24 2.50 0.59 969 3.99 2.35 0.59 1012 3.75 2.21 0.59 1054
32 18 3.43 3.43 1.00 833 3.15 3.15 1.00 884 2.91 2.91 1.00 918
32 20 3.61 3.57 0.99 867 3.36 3.33 0.99 910 3.12 3.08 0.99 961
32 22 3.82 3.32 0.87 901 3.57 3.11 0.87 952 3.33 2.89 0.87 986
32 24 4.03 3.02 0.75 935 3.78 2.84 0.75 978 3.57 2.68 0.75 1020
32 26 4.24 2.67 0.63 969 3.99 2.51 0.63 1012 3.75 2.36 0.63 1054
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT
35 40 46
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
OUTDOOR DB (°C)
2323
Page 24
PERFORMANCE DATA COOL operation at Rated frequency
MUZ-FD35VAH
CAPACITY: 3.5 kW SHF: 0.85 INPUT: 835 W
INDOOR
DB (°C)
INDOOR
WB (°C)
21 18 4.11 2.76 0.67 668 3.94 2.64 0.67 701 3.78 2.53 0.67 735 3.64 2.44 0.67 768
21 20 4.29 2.36 0.55 701 4.11 2.26 0.55 743 3.99 2.19 0.55 760 3.85 2.12 0.55 793
22 18 4.11 2.92 0.71 668 3.94 2.80 0.71 701 3.78 2.68 0.71 735 3.64 2.58 0.71 768
22 20 4.29 2.53 0.59 701 4.11 2.43 0.59 743 3.99 2.35 0.59 760 3.85 2.27 0.59 793
22 22 4.46 2.10 0.47 726 4.31 2.02 0.47 772 4.20 1.97 0.47 793 4.03 1.89 0.47 827
23 18 4.11 3.08 0.75 668 3.94 2.95 0.75 701 3.78 2.84 0.75 735 3.64 2.73 0.75 768
23 20 4.29 2.70 0.63 701 4.11 2.59 0.63 743 3.99 2.51 0.63 760 3.85 2.43 0.63 793
23 22 4.46 2.28 0.51 726 4.31 2.20 0.51 772 4.20 2.14 0.51 793 4.03 2.05 0.51 827
24 18 4.11 3.25 0.79 668 3.94 3.11 0.79 701 3.78 2.99 0.79 735 3.64 2.88 0.79 768
24 20 4.29 2.87 0.67 701 4.11 2.76 0.67 743 3.99 2.67 0.67 760 3.85 2.58 0.67 793
24 22 4.46 2.45 0.55 726 4.31 2.37 0.55 772 4.20 2.31 0.55 793 4.03 2.21 0.55 827
24 24 4.69 2.02 0.43 760 4.52 1.94 0.43 802 4.41 1.90 0.43 827 4.27 1.84 0.43 868
25 18 4.11 3.41 0.83 668 3.94 3.27 0.83 701 3.78 3.14 0.83 735 3.64 3.02 0.83 768
25 20 4.29 3.04 0.71 701 4.11 2.92 0.71 743 3.99 2.83 0.71 760 3.85 2.73 0.71 793
25 22 4.46 2.63 0.59 726 4.31 2.54 0.59 772 4.20 2.48 0.59 793 4.03 2.37 0.59 827
25 24 4.69 2.20 0.47 760 4.52 2.12 0.47 802 4.41 2.07 0.47 827 4.27 2.01 0.47 868
26 18 4.11 3.58 0.87 668 3.94 3.43 0.87 701 3.78 3.29 0.87 735 3.64 3.17 0.87 768
26 20 4.29 3.22 0.75 701 4.11 3.08 0.75 743 3.99 2.99 0.75 760 3.85 2.89 0.75 793
26 22 4.46 2.81 0.63 726 4.31 2.71 0.63 772 4.20 2.65 0.63 793 4.03 2.54 0.63 827
26 24 4.69 2.39 0.51 760 4.52 2.30 0.51 802 4.41 2.25 0.51 827 4.27 2.18 0.51 868
26 26 4.83 1.88 0.39 802 4.69 1.83 0.39 843 4.62 1.80 0.39 868 4.48 1.75 0.39 893
27 18 4.11 3.74 0.91 668 3.94 3.58 0.91 701 3.78 3.44 0.91 735 3.64 3.31 0.91 768
27 20 4.29 3.39 0.79 701 4.11 3.25 0.79 743 3.99 3.15 0.79 760 3.85 3.04 0.79 793
27 22 4.46 2.99 0.67 726 4.31 2.88 0.67 772 4.20 2.81 0.67 793 4.03 2.70 0.67 827
27 24 4.69 2.58 0.55 760 4.52 2.48 0.55 802 4.41 2.43 0.55 827 4.27 2.35 0.55 868
27 26 4.83 2.08 0.43 802 4.69 2.02 0.43 843 4.62 1.99 0.43 868 4.48 1.93 0.43 893
28 18 4.11 3.91 0.95 668 3.94 3.74 0.95 701 3.78 3.59 0.95 735 3.64 3.46 0.95 768
28 20 4.29 3.56 0.83 701 4.11 3.41 0.83 743 3.99 3.31 0.83 760 3.85 3.20 0.83 793
28 22 4.46 3.17 0.71 726 4.31 3.06 0.71 772 4.20 2.98 0.71 793 4.03 2.86 0.71 827
28 24 4.69 2.77 0.59 760 4.52 2.66 0.59 802 4.41 2.60 0.59 827 4.27 2.52 0.59 868
28 26 4.83 2.27 0.47 802 4.69 2.20 0.47 843 4.62 2.17 0.47 868 4.48 2.11 0.47 893
29 18 4.11 4.07 0.99 668 3.94 3.90 0.99 701 3.78 3.74 0.99 735 3.64 3.60 0.99 768
29 20 4.29 3.73 0.87 701 4.11 3.58 0.87 743 3.99 3.47 0.87 760 3.85 3.35 0.87 793
29 22 4.46 3.35 0.75 726 4.31 3.23 0.75 772 4.20 3.15 0.75 793 4.03 3.02 0.75 827
29 24 4.69 2.95 0.63 760 4.52 2.84 0.63 802 4.41 2.78 0.63 827 4.27 2.69 0.63 868
29 26 4.83 2.46 0.51 802 4.69 2.39 0.51 843 4.62 2.36 0.51 868 4.48 2.28 0.51 893
30 18 4.11 4.11 1.00 668 3.94 3.94 1.00 701 3.78 3.78 1.00 735 3.64 3.64 1.00 768
30 20 4.29 3.90 0.91 701 4.11 3.74 0.91 743 3.99 3.63 0.91 760 3.85 3.50 0.91 793
30 22 4.46 3.53 0.79 726 4.31 3.40 0.79 772 4.20 3.32 0.79 793 4.03 3.18 0.79 827
30 24 4.69 3.14 0.67 760 4.52 3.03 0.67 802 4.41 2.95 0.67 827 4.27 2.86 0.67 868
30 26 4.83 2.66 0.55 802 4.69 2.58 0.55 843 4.62 2.54 0.55 868 4.48 2.46 0.55 893
31 18 4.11 4.11 1.00 668 3.94 3.94 1.00 701 3.78 3.78 1.00 735 3.64 3.64 1.00 768
31 20 4.29 4.07 0.95 701 4.11 3.91 0.95 743 3.99 3.79 0.95 760 3.85 3.66 0.95 793
31 22 4.46 3.70 0.83 726 4.31 3.57 0.83 772 4.20 3.49 0.83 793 4.03 3.34 0.83 827
31 24 4.69 3.33 0.71 760 4.52 3.21 0.71 802 4.41 3.13 0.71 827 4.27 3.03 0.71 868
31 26 4.83 2.85 0.59 802 4.69 2.77 0.59 843 4.62 2.73 0.59 868 4.48 2.64 0.59 893
32 18 4.11 4.11 1.00 668 3.94 3.94 1.00 701 3.78 3.78 1.00 735 3.64 3.64 1.00 768
32 20 4.29 4.24 0.99 701 4.11 4.07 0.99 743 3.99 3.95 0.99 760 3.85 3.81 0.99 793
32 22 4.46 3.88 0.87 726 4.31 3.75 0.87 772 4.20 3.65 0.87 793 4.03 3.50 0.87 827
32 24 4.69 3.52 0.75 760 4.52 3.39 0.75 802 4.41 3.31 0.75 827 4.27 3.20 0.75 868
32 26 4.83 3.04 0.63 802 4.69 2.95 0.63 843 4.62 2.91 0.63 868 4.48 2.82 0.63 893
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT
21 25 27 30
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
OUTDOOR DB (°C)
24
Page 25
PERFORMANCE DATA COOL operation at Rated frequency
MUZ-FD35VAH
CAPACITY: 3.5 kW SHF: 0.85 INPUT: 835 W
INDOOR
DB (°C)
INDOOR
WB (°C)
21 18 3.43 2.30 0.67 818 3.15 2.11 0.67 868 2.91 1.95 0.67 902
21 20 3.61 1.98 0.55 852 3.36 1.85 0.55 893 3.12 1.71 0.55 944
22 18 3.43 2.44 0.71 818 3.15 2.24 0.71 868 2.91 2.06 0.71 902
22 20 3.61 2.13 0.59 852 3.36 1.98 0.59 893 3.12 1.84 0.59 944
22 22 3.82 1.79 0.47 885 3.57 1.68 0.47 935 3.33 1.56 0.47 969
23 18 3.43 2.57 0.75 818 3.15 2.36 0.75 868 2.91 2.18 0.75 902
23 20 3.61 2.27 0.63 852 3.36 2.12 0.63 893 3.12 1.96 0.63 944
23 22 3.82 1.95 0.51 885 3.57 1.82 0.51 935 3.33 1.70 0.51 969
24 18 3.43 2.71 0.79 818 3.15 2.49 0.79 868 2.91 2.29 0.79 902
24 20 3.61 2.42 0.67 852 3.36 2.25 0.67 893 3.12 2.09 0.67 944
24 22 3.82 2.10 0.55 885 3.57 1.96 0.55 935 3.33 1.83 0.55 969
24 24 4.03 1.73 0.43 919 3.78 1.63 0.43 960 3.57 1.54 0.43 1002
25 18 3.43 2.85 0.83 818 3.15 2.61 0.83 868 2.91 2.41 0.83 902
25 20 3.61 2.56 0.71 852 3.36 2.39 0.71 893 3.12 2.21 0.71 944
25 22 3.82 2.25 0.59 885 3.57 2.11 0.59 935 3.33 1.96 0.59 969
25 24 4.03 1.89 0.47 919 3.78 1.78 0.47 960 3.57 1.68 0.47 1002
26 18 3.43 2.98 0.87 818 3.15 2.74 0.87 868 2.91 2.53 0.87 902
26 20 3.61 2.70 0.75 852 3.36 2.52 0.75 893 3.12 2.34 0.75 944
26 22 3.82 2.40 0.63 885 3.57 2.25 0.63 935 3.33 2.09 0.63 969
26 24 4.03 2.05 0.51 919 3.78 1.93 0.51 960 3.57 1.82 0.51 1002
26 26 4.24 1.65 0.39 952 3.99 1.56 0.39 994 3.75 1.46 0.39 1035
27 18 3.43 3.12 0.91 818 3.15 2.87 0.91 868 2.91 2.64 0.91 902
27 20 3.61 2.85 0.79 852 3.36 2.65 0.79 893 3.12 2.46 0.79 944
27 22 3.82 2.56 0.67 885 3.57 2.39 0.67 935 3.33 2.23 0.67 969
27 24 4.03 2.21 0.55 919 3.78 2.08 0.55 960 3.57 1.96 0.55 1002
27 26 4.24 1.82 0.43 952 3.99 1.72 0.43 994 3.75 1.61 0.43 1035
28 18 3.43 3.26 0.95 818 3.15 2.99 0.95 868 2.91 2.76 0.95 902
28 20 3.61 2.99 0.83 852 3.36 2.79 0.83 893 3.12 2.59 0.83 944
28 22 3.82 2.71 0.71 885 3.57 2.53 0.71 935 3.33 2.36 0.71 969
28 24 4.03 2.37 0.59 919 3.78 2.23 0.59 960 3.57 2.11 0.59 1002
28 26 4.24 1.99 0.47 952 3.99 1.88 0.47 994 3.75 1.76 0.47 1035
29 18 3.43 3.40 0.99 818 3.15 3.12 0.99 868 2.91 2.88 0.99 902
29 20 3.61 3.14 0.87 852 3.36 2.92 0.87 893 3.12 2.71 0.87 944
29 22 3.82 2.86 0.75 885 3.57 2.68 0.75 935 3.33 2.49 0.75 969
29 24 4.03 2.54 0.63 919 3.78 2.38 0.63 960 3.57 2.25 0.63 1002
29 26 4.24 2.16 0.51 952 3.99 2.03 0.51 994 3.75 1.91 0.51 1035
30 18 3.43 3.43 1.00 818 3.15 3.15 1.00 868 2.91 2.91 1.00 902
30 20 3.61 3.28 0.91 852 3.36 3.06 0.91 893 3.12 2.83 0.91 944
30 22 3.82 3.01 0.79 885 3.57 2.82 0.79 935 3.33 2.63 0.79 969
30 24 4.03 2.70 0.67 919 3.78 2.53 0.67 960 3.57 2.39 0.67 1002
30 26 4.24 2.33 0.55 952 3.99 2.19 0.55 994 3.75 2.06 0.55 1035
31 18 3.43 3.43 1.00 818 3.15 3.15 1.00 868 2.91 2.91 1.00 902
31 20 3.61 3.42 0.95 852 3.36 3.19 0.95 893 3.12 2.96 0.95 944
31 22 3.82 3.17 0.83 885 3.57 2.96 0.83 935 3.33 2.76 0.83 969
31 24 4.03 2.86 0.71 919 3.78 2.68 0.71 960 3.57 2.53 0.71 1002
31 26 4.24 2.50 0.59 952 3.99 2.35 0.59 994 3.75 2.21 0.59 1035
32 18 3.43 3.43 1.00 818 3.15 3.15 1.00 868 2.91 2.91 1.00 902
32 20 3.61 3.57 0.99 852 3.36 3.33 0.99 893 3.12 3.08 0.99 944
32 22 3.82 3.32 0.87 885 3.57 3.11 0.87 935 3.33 2.89 0.87 969
32 24 4.03 3.02 0.75 919 3.78 2.84 0.75 960 3.57 2.68 0.75 1002
32 26 4.24 2.67 0.63 952 3.99 2.51 0.63 994 3.75 2.36 0.63 1035
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT
35 40 46
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
OUTDOOR DB (°C)
25
Page 26
PERFORMANCE DATA COOL operation at Rated frequency
MUZ-FD50VA
CAPACITY: 5.0 kW SHF: 0.77 INPUT: 1500 W
INDOOR
DB (°C)
INDOOR
WB (°C)
21 18 5.88 3.47 0.59 1200 5.63 3.32 0.59 1260 5.40 3.19 0.59 1320 5.20 3.07 0.59 1380
21 20 6.13 2.88 0.47 1260 5.88 2.76 0.47 1335 5.70 2.68 0.47 1365 5.50 2.59 0.47 1425
22 18 5.88 3.70 0.63 1200 5.63 3.54 0.63 1260 5.40 3.40 0.63 1320 5.20 3.28 0.63 1380
22 20 6.13 3.12 0.51 1260 5.88 3.00 0.51 1335 5.70 2.91 0.51 1365 5.50 2.81 0.51 1425
22 22 6.38 2.49 0.39 1305 6.15 2.40 0.39 1388 6.00 2.34 0.39 1425 5.75 2.24 0.39 1485
23 18 5.88 3.94 0.67 1200 5.63 3.77 0.67 1260 5.40 3.62 0.67 1320 5.20 3.48 0.67 1380
23 20 6.13 3.37 0.55 1260 5.88 3.23 0.55 1335 5.70 3.14 0.55 1365 5.50 3.03 0.55 1425
23 22 6.38 2.74 0.43 1305 6.15 2.64 0.43 1388 6.00 2.58 0.43 1425 5.75 2.47 0.43 1485
24 18 5.88 4.17 0.71 1200 5.63 3.99 0.71 1260 5.40 3.83 0.71 1320 5.20 3.69 0.71 1380
24 20 6.13 3.61 0.59 1260 5.88 3.47 0.59 1335 5.70 3.36 0.59 1365 5.50 3.25 0.59 1425
24 22 6.38 3.00 0.47 1305 6.15 2.89 0.47 1388 6.00 2.82 0.47 1425 5.75 2.70 0.47 1485
24 24 6.70 2.35 0.35 1365 6.45 2.26 0.35 1440 6.30 2.21 0.35 1485 6.10 2.14 0.35 1560
25 18 5.88 4.41 0.75 1200 5.63 4.22 0.75 1260 5.40 4.05 0.75 1320 5.20 3.90 0.75 1380
25 20 6.13 3.86 0.63 1260 5.88 3.70 0.63 1335 5.70 3.59 0.63 1365 5.50 3.47 0.63 1425
25 22 6.38 3.25 0.51 1305 6.15 3.14 0.51 1388 6.00 3.06 0.51 1425 5.75 2.93 0.51 1485
25 24 6.70 2.61 0.39 1365 6.45 2.52 0.39 1440 6.30 2.46 0.39 1485 6.10 2.38 0.39 1560
26 18 5.88 4.64 0.79 1200 5.63 4.44 0.79 1260 5.40 4.27 0.79 1320 5.20 4.11 0.79 1380
26 20 6.13 4.10 0.67 1260 5.88 3.94 0.67 1335 5.70 3.82 0.67 1365 5.50 3.69 0.67 1425
26 22 6.38 3.51 0.55 1305 6.15 3.38 0.55 1388 6.00 3.30 0.55 1425 5.75 3.16 0.55 1485
26 24 6.70 2.88 0.43 1365 6.45 2.77 0.43 1440 6.30 2.71 0.43 1485 6.10 2.62 0.43 1560
26 26 6.90 2.14 0.31 1440 6.70 2.08 0.31 1515 6.60 2.05 0.31 1560 6.40 1.98 0.31 1605
27 18 5.88 4.88 0.83 1200 5.63 4.67 0.83 1260 5.40 4.48 0.83 1320 5.20 4.32 0.83 1380
27 20 6.13 4.35 0.71 1260 5.88 4.17 0.71 1335 5.70 4.05 0.71 1365 5.50 3.91 0.71 1425
27 22 6.38 3.76 0.59 1305 6.15 3.63 0.59 1388 6.00 3.54 0.59 1425 5.75 3.39 0.59 1485
27 24 6.70 3.15 0.47 1365 6.45 3.03 0.47 1440 6.30 2.96 0.47 1485 6.10 2.87 0.47 1560
27 26 6.90 2.42 0.35 1440 6.70 2.35 0.35 1515 6.60 2.31 0.35 1560 6.40 2.24 0.35 1605
28 18 5.88 5.11 0.87 1200 5.63 4.89 0.87 1260 5.40 4.70 0.87 1320 5.20 4.52 0.87 1380
28 20 6.13 4.59 0.75 1260 5.88 4.41 0.75 1335 5.70 4.28 0.75 1365 5.50 4.13 0.75 1425
28 22 6.38 4.02 0.63 1305 6.15 3.87 0.63 1388 6.00 3.78 0.63 1425 5.75 3.62 0.63 1485
28 24 6.70 3.42 0.51 1365 6.45 3.29 0.51 1440 6.30 3.21 0.51 1485 6.10 3.11 0.51 1560
28 26 6.90 2.69 0.39 1440 6.70 2.61 0.39 1515 6.60 2.57 0.39 1560 6.40 2.50 0.39 1605
29 18 5.88 5.35 0.91 1200 5.63 5.12 0.91 1260 5.40 4.91 0.91 1320 5.20 4.73 0.91 1380
29 20 6.13 4.84 0.79 1260 5.88 4.64 0.79 1335 5.70 4.50 0.79 1365 5.50 4.35 0.79 1425
29 22 6.38 4.27 0.67 1305 6.15 4.12 0.67 1388 6.00 4.02 0.67 1425 5.75 3.85 0.67 1485
29 24 6.70 3.69 0.55 1365 6.45 3.55 0.55 1440 6.30 3.47 0.55 1485 6.10 3.36 0.55 1560
29 26 6.90 2.97 0.43 1440 6.70 2.88 0.43 1515 6.60 2.84 0.43 1560 6.40 2.75 0.43 1605
30 18 5.88 5.58 0.95 1200 5.63 5.34 0.95 1260 5.40 5.13 0.95 1320 5.20 4.94 0.95 1380
30 20 6.13 5.08 0.83 1260 5.88 4.88 0.83 1335 5.70 4.73 0.83 1365 5.50 4.57 0.83 1425
30 22 6.38 4.53 0.71 1305 6.15 4.37 0.71 1388 6.00 4.26 0.71 1425 5.75 4.08 0.71 1485
30 24 6.70 3.95 0.59 1365 6.45 3.81 0.59 1440 6.30 3.72 0.59 1485 6.10 3.60 0.59 1560
30 26 6.90 3.24 0.47 1440 6.70 3.15 0.47 1515 6.60 3.10 0.47 1560 6.40 3.01 0.47 1605
31 18 5.88 5.82 0.99 1200 5.63 5.57 0.99 1260 5.40 5.35 0.99 1320 5.20 5.15 0.99 1380
31 20 6.13 5.33 0.87 1260 5.88 5.11 0.87 1335 5.70 4.96 0.87 1365 5.50 4.79 0.87 1425
31 22 6.38 4.78 0.75 1305 6.15 4.61 0.75 1388 6.00 4.50 0.75 1425 5.75 4.31 0.75 1485
31 24 6.70 4.22 0.63 1365 6.45 4.06 0.63 1440 6.30 3.97 0.63 1485 6.10 3.84 0.63 1560
31 26 6.90 3.52 0.51 1440 6.70 3.42 0.51 1515 6.60 3.37 0.51 1560 6.40 3.26 0.51 1605
32 18 5.88 5.88 1.00 1200 5.63 5.63 1.00 1260 5.40 5.40 1.00 1320 5.20 5.20 1.00 1380
32 20 6.13 5.57 0.91 1260 5.88 5.35 0.91 1335 5.70 5.19 0.91 1365 5.50 5.01 0.91 1425
32 22 6.38 5.04 0.79 1305 6.15 4.86 0.79 1388 6.00 4.74 0.79 1425 5.75 4.54 0.79 1485
32 24 6.70 4.49 0.67 1365 6.45 4.32 0.67 1440 6.30 4.22 0.67 1485 6.10 4.09 0.67 1560
32 26 6.90 3.80 0.55 1440 6.70 3.69 0.55 1515 6.60 3.63 0.55 1560 6.40 3.52 0.55 1605
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT
21 25 27 30
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
OUTDOOR DB (°C)
26
Page 27
PERFORMANCE DATA COOL operation at Rated frequency
MUZ-FD50VA
CAPACITY: 5.0 kW SHF: 0.77 INPUT: 1500 W
INDOOR
DB (°C)
INDOOR
WB (°C)
21 18 4.90 2.89 0.59 1470 4.50 2.66 0.59 1560 4.15 2.45 0.59 1620
21 20 5.15 2.42 0.47 1530 4.80 2.26 0.47 1605 4.45 2.09 0.47 1695
22 18 4.90 3.09 0.63 1470 4.50 2.84 0.63 1560 4.15 2.61 0.63 1620
22 20 5.15 2.63 0.51 1530 4.80 2.45 0.51 1605 4.45 2.27 0.51 1695
22 22 5.45 2.13 0.39 1590 5.10 1.99 0.39 1680 4.75 1.85 0.39 1740
23 18 4.90 3.28 0.67 1470 4.50 3.02 0.67 1560 4.15 2.78 0.67 1620
23 20 5.15 2.83 0.55 1530 4.80 2.64 0.55 1605 4.45 2.45 0.55 1695
23 22 5.45 2.34 0.43 1590 5.10 2.19 0.43 1680 4.75 2.04 0.43 1740
24 18 4.90 3.48 0.71 1470 4.50 3.20 0.71 1560 4.15 2.95 0.71 1620
24 20 5.15 3.04 0.59 1530 4.80 2.83 0.59 1605 4.45 2.63 0.59 1695
24 22 5.45 2.56 0.47 1590 5.10 2.40 0.47 1680 4.75 2.23 0.47 1740
24 24 5.75 2.01 0.35 1650 5.40 1.89 0.35 1725 5.10 1.79 0.35 1800
25 18 4.90 3.68 0.75 1470 4.50 3.38 0.75 1560 4.15 3.11 0.75 1620
25 20 5.15 3.24 0.63 1530 4.80 3.02 0.63 1605 4.45 2.80 0.63 1695
25 22 5.45 2.78 0.51 1590 5.10 2.60 0.51 1680 4.75 2.42 0.51 1740
25 24 5.75 2.24 0.39 1650 5.40 2.11 0.39 1725 5.10 1.99 0.39 1800
26 18 4.90 3.87 0.79 1470 4.50 3.56 0.79 1560 4.15 3.28 0.79 1620
26 20 5.15 3.45 0.67 1530 4.80 3.22 0.67 1605 4.45 2.98 0.67 1695
26 22 5.45 3.00 0.55 1590 5.10 2.81 0.55 1680 4.75 2.61 0.55 1740
26 24 5.75 2.47 0.43 1650 5.40 2.32 0.43 1725 5.10 2.19 0.43 1800
26 26 6.05 1.88 0.31 1710 5.70 1.77 0.31 1785 5.35 1.66 0.31 1860
27 18 4.90 4.07 0.83 1470 4.50 3.74 0.83 1560 4.15 3.44 0.83 1620
27 20 5.15 3.66 0.71 1530 4.80 3.41 0.71 1605 4.45 3.16 0.71 1695
27 22 5.45 3.22 0.59 1590 5.10 3.01 0.59 1680 4.75 2.80 0.59 1740
27 24 5.75 2.70 0.47 1650 5.40 2.54 0.47 1725 5.10 2.40 0.47 1800
27 26 6.05 2.12 0.35 1710 5.70 2.00 0.35 1785 5.35 1.87 0.35 1860
28 18 4.90 4.26 0.87 1470 4.50 3.92 0.87 1560 4.15 3.61 0.87 1620
28 20 5.15 3.86 0.75 1530 4.80 3.60 0.75 1605 4.45 3.34 0.75 1695
28 22 5.45 3.43 0.63 1590 5.10 3.21 0.63 1680 4.75 2.99 0.63 1740
28 24 5.75 2.93 0.51 1650 5.40 2.75 0.51 1725 5.10 2.60 0.51 1800
28 26 6.05 2.36 0.39 1710 5.70 2.22 0.39 1785 5.35 2.09 0.39 1860
29 18 4.90 4.46 0.91 1470 4.50 4.10 0.91 1560 4.15 3.78 0.91 1620
29 20 5.15 4.07 0.79 1530 4.80 3.79 0.79 1605 4.45 3.52 0.79 1695
29 22 5.45 3.65 0.67 1590 5.10 3.42 0.67 1680 4.75 3.18 0.67 1740
29 24 5.75 3.16 0.55 1650 5.40 2.97 0.55 1725 5.10 2.81 0.55 1800
29 26 6.05 2.60 0.43 1710 5.70 2.45 0.43 1785 5.35 2.30 0.43 1860
30 18 4.90 4.66 0.95 1470 4.50 4.28 0.95 1560 4.15 3.94 0.95 1620
30 20 5.15 4.27 0.83 1530 4.80 3.98 0.83 1605 4.45 3.69 0.83 1695
30 22 5.45 3.87 0.71 1590 5.10 3.62 0.71 1680 4.75 3.37 0.71 1740
30 24 5.75 3.39 0.59 1650 5.40 3.19 0.59 1725 5.10 3.01 0.59 1800
30 26 6.05 2.84 0.47 1710 5.70 2.68 0.47 1785 5.35 2.51 0.47 1860
31 18 4.90 4.85 0.99 1470 4.50 4.46 0.99 1560 4.15 4.11 0.99 1620
31 20 5.15 4.48 0.87 1530 4.80 4.18 0.87 1605 4.45 3.87 0.87 1695
31 22 5.45 4.09 0.75 1590 5.10 3.83 0.75 1680 4.75 3.56 0.75 1740
31 24 5.75 3.62 0.63 1650 5.40 3.40 0.63 1725 5.10 3.21 0.63 1800
31 26 6.05 3.09 0.51 1710 5.70 2.91 0.51 1785 5.35 2.73 0.51 1860
32 18 4.90 4.90 1.00 1470 4.50 4.50 1.00 1560 4.15 4.15 1.00 1620
32 20 5.15 4.69 0.91 1530 4.80 4.37 0.91 1605 4.45 4.05 0.91 1695
32 22 5.45 4.31 0.79 1590 5.10 4.03 0.79 1680 4.75 3.75 0.79 1740
32 24 5.75 3.85 0.67 1650 5.40 3.62 0.67 1725 5.10 3.42 0.67 1800
32 26 6.05 3.33 0.55 1710 5.70 3.14 0.55 1785 5.35 2.94 0.55 1860
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT
35 40 46
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
OUTDOOR DB (°C)
27
Page 28
PERFORMANCE DATA HEAT operation at Rated frequency
MUZ-FD25VA MUZ-FD25VAH
CAPACITY: 3.2 kW INPUT: 610 W
INDOOR
DB (°C)
15 2.02 397 2.43 476 2.85 537 3.26 580 3.68 616 4.06 634 4.48 647
21 1.92 427 2.30 506 2.72 561 3.10 604 3.52 634 3.90 653 4.30 677
26 1.73 458 2.14 537 2.53 592 2.94 634 3.36 665 3.74 683 4.16 702
-10 -5 0 5 10 15 20
Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT
OUTDOOR WB (°C)
MUZ-FD35VA
CAPACITY: 4.0 kW INPUT: 865 W
INDOOR
DB (°C)
15 2.52 562 3.04 675 3.56 761 4.08 822 4.60 874 5.08 900 5.60 917
21 2.40 606 2.88 718 3.40 796 3.88 856 4.40 900 4.88 926 5.38 960
26 2.16 649 2.68 761 3.16 839 3.68 900 4.20 943 4.68 969 5.20 995
-10 -5 0 5 10 15 20
Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT
OUTDOOR WB (°C)
MUZ-FD35VAH
CAPACITY: 4.0 kW INPUT: 850 W
INDOOR
DB (°C)
15 2.52 553 3.04 663 3.56 748 4.08 808 4.60 859 5.08 884 5.60 901
21 2.40 595 2.88 706 3.40 782 3.88 842 4.40 884 4.88 910 5.38 944
26 2.16 638 2.68 748 3.16 825 3.68 884 4.20 927 4.68 952 5.20 978
-10 -5 0 5 10 15 20
Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT
OUTDOOR WB (°C)
MUZ-FD50VA
CAPACITY: 5.8 kW INPUT: 1550 W
INDOOR
DB (°C)
15 3.65 1008 4.41 1209 5.16 1364 5.92 1473 6.67 1566 7.37 1612 8.12 1643
21 3.48 1085 4.18 1287 4.93 1426 5.63 1535 6.38 1612 7.08 1659 7.80 1721
26 3.13 1163 3.89 1364 4.58 1504 5.34 1612 6.09 1690 6.79 1736 7.54 1783
-10 -5 0 5 10 15 20
Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT
OUTDOOR WB (°C)
NOTE Q : Total capacity (kW) INPUT : Total power input (W) DB: Dry-bulb temperature WB: Wet-bulb temperature
2828
Page 29
9
ACTUATOR CONTROL
MUZ-FD25VA MUZ-FD25VAH MUZ-FD35VA MUZ-FD35VAH MUZ-FD50VA
9-1. OUTDOOR FAN MOTOR CONTROL
The fan motor turns ON/OFF, interlocking with the compressor. [ON] The fan motor turns ON 5 seconds before the compressor starts up. [OFF] The fan motor turns OFF 15 seconds after the compressor has stopped running.
5 seconds 15 seconds
ON
Compressor
OFF
ON
Outdoor fan motor
OFF
9-2. R.V. COIL CONTROL
Heating Cooling Dry
NOTE: The 4-way valve reverses for 5 seconds right before start-up of the compressor.
9-3. RELATION BETWEEN MAIN SENSOR AND ACTUATOR
MUZ-FD25/35
Discharge temperature thermistor
Indoor coil temperature thermistor
Defrost thermistor
Fin temperature thermistor Protection
Ambient temperature thermistor
Outdoor heat exchanger temperature thermistor
. . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
Compressor
R.V.coil
Outdoor fan motor
Sensor Purpose
ON OFF OFF
ON OFF
ON OFF
ON OFF
Protection
Cooling: Coil frost prevention
Heating: High pressure protection
Cooling: High pressure protection
Heating: Defrosting
Cooling: Low ambient temperature operation
Heating: Defrosting (Heater)
Low outside temperature operation
<COOL>
5 seconds
Compressor
LEV
      

<HEAT>
5 seconds
Actuator
Outdoor
fan motor
R.V.coil
Indoor fan
motor
Defrost
heater
29
Page 30
MUZ-FD50
Sensor Purpose
Discharge temperature thermistor
Indoor coil temperature thermistor
Defrost thermistor Heating: Defrosting Fin temperature thermistor Protection Ambient temperature
thermistor
Outdoor heat exchanger temperature thermistor
Protection
Cooling: Coil frost preven­tion
Heating: High pressure protection
Cooling: Low ambient tem­perature operation
Cooling: Low ambient tem­perature operation
Cooling: High pressure protection
Actuator
Compressor
LEV
Outdoor fan
motor
R.V.coil
Indoor fan
motor
 
 
 
 
10
SERVICE FUNCTIONS
MUZ-FD25VA MUZ-FD25VAH MUZ-FD35VA MUZ-FD35VAH MUZ-FD50VA
10-1. CHANGE IN DEFROST SETTING Changing defrost finish temperature
MUZ-FD25/35
<JS> To change the defrost finish temperature, cut/solder the JS wire of the outdoor inverter P.C. board. (Refer to
11-6-1.)
Jumper wire Defrost nish temperature (°C)
Soldered
(Initial setting)
JS
MUZ-FD50
1. Turn OFF the power supply for the air conditioner before making the setting.
2. Set the 4th Dip Switch of SW1 on the outdoor electronic control P.C. board to ON to change the defrost finish temperature. (Refer to 11-6-2.)
4th Dip Switch of SW1 Defrost fi nish temperature (°C)
10-2. PRE-HEAT CONTROL SETTING
PRE-HEAT CONTROL
When moisture gets into the refrigerant cycle, it may interfere the start-up of the compressor at low outside temperature. The pre-heat control prevents this interference. The pre-heat control turns ON when outside temperature is 20°C or below. When pre-heat control is turned ON, compressor is energized. (About 50 W)
None (Cut)
OFF
(Initial setting)
ON 12.2
5
10
ON
1234
8.3
MUZ-FD25/35
<JK> To activate the pre-heat control, cut the JK wire of the inverter P.C. board. (Refer to 11-6.1)
NOTE: When the inverter P.C. board is replaced, check the Jumper wires, and cut/solder them if necessary.
MUZ-FD50
[How to activate pre-heat control]
1. Turn OFF the power supply for the air conditioner before making the setting.
2. Set the 2nd Dip Switch of SW1 on the outdoor electronic control P.C. board to ON to activate pre-heat control function. (Refer to 11-6-2.)
30
ON
1234
Page 31
11
TROUBLESHOOTING
MUZ-FD25VA MUZ-FD25VAH MUZ-FD35VA MUZ-FD35VAH MUZ-FD50VA
11-1. CAUTIONS ON TROUBLESHOOTING
1. Before troubleshooting, check the following
1) Check the power supply voltage.
2) Check the indoor/outdoor connecting wire for miswiring.
2. Take care of the following during servicing
1) Before servicing the air conditioner, be sure to turn OFF the main unit first with the remote controller, and then after confirming the horizontal vane is closed, turn OFF the breaker and/or disconnect the power plug.
2) Be sure to turn OFF the power supply before removing the front panel, the cabinet, the top panel, and the electronic control P.C. board.
3) When removing the electrical parts, be careful of the residual voltage of smoothing capacitor.
4) When removing the electronic control P.C. board, hold the edge of the board with care NOT to apply stress on the components.
5) When connecting or disconnecting the connectors, hold the housing of the connector. DO NOT pull the lead wires.
Lead wiring
3. Troubleshooting procedure
1) First, check if the OPERATION INDICATOR lamp on the indoor unit is flashing on and off to indicate an abnormality.
To make sure, check how many times the abnormality indication is flashing on and off before starting service work.
2) Before servicing, check that the connector and terminal are connected properly.
3) When the electronic control P.C. board seems to be defective, check the copper foil pattern for disconnection and the
components for bursting and discoloration.
4) Refer to 11-2. and 11-3.
Housing point
31
Page 32
11-2. FAILURE MODE RECALL FUNCTION
Outline of the function This air conditioner can memorize the abnormal condition which has occurred once. Even though LED indication listed on the troubleshooting check table (11-3.) disappears, the memorized failure details can be recalled.
1. Flow chart of failure mode recall function for the indoor/outdoor unit
Operational procedure
The cause of abnormality cannot be found because the abnormality does not recur.
Setting up the failure mode recall function
Turn ON the power supply. <Preparation of the remote controller>
While pressing both OPERATION SELECT button and TOO COOL button on the
remote controller at the same time, press RESET button.
First, release RESET button.
And release the other two buttons after all LCD in operation display section of the
remote controller is displayed after 3 seconds.
Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit. 1
1. Regardless of normal or abnormal condition, a short
Does POWER lamp on the indoor unit blink at the interval of
0.5 seconds? Blinks: Either indoor or outdoor unit is abnormal. Beep
is emitted at the same timing as the blinking of POWER lamp. 2
Judgment of indoor/outdoor abnormality
Before blinking, does POWER lamp stay ON for 3 seconds? Stays ON for 3 seconds (without beep): The outdoor unit is abnormal.
The indoor unit is abnormal. Check the blinking pattern, and confi rm the abnormal point with the indoor unit failure mode table. (Refer to indoor unit service manual.) Make sure to check at least two consecutive blinking cycles. 2
Yes (Blinks)
No
No (OFF)
Yes
Indoor unit is normal. But the outdoor unit might be abnormal because there are some abnor­malities that can not be recalled with this way. Confi rm if outdoor unit is abnormal according to the detailed outdoor unit failure mode recall function. (Refer to 11-2.2)
The outdoor unit is abnormal. Check the blinking pattern, and confi rm the abnormal point with the outdoor unit failure mode table. (Refer to 11-2.3) Make sure to check at least two consecutive blinking cycles. 3
beep is emitted once the signal is received.
Releasing the failure mode recall function
Deleting the memorized abnormal condition
Release the failure mode recall function by the following procedures. Turn OFF the power supply and turn it ON again. Press RESET button of the remote controller.
Repair the defective parts.
After repairing the unit, recall the failure mode again according to "Setting up the failure mode recall
function" mentioned above.
Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed)
with the remote controller headed towards the indoor unit. Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted. Release the failure mode recall function according to "Releasing the failure mode recall function"
mentioned above.
NOTE: 1. Make sure to release the failure mode recall function once it is set up, otherwise the unit cannot operate properly.
2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.
2. Blinking pattern when the indoor unit is abnormal:
2.5-second OFF
Blinking at 0.5-
second interval
2.5-second OFF
Blinking at 0.5­second interval
ON
OFF
Repeated cycle Repeated cycle
Beeps
3.Blinking pattern when the outdoor unit is abnormal:
2.5-second OFF 3-second ON
Blinking at 0.5­second interval
Beeps
Repeated cycle
2.5-second OFF 3-second ON
ON
OFF
No beep Beeps
Repeated cycle
No beep Beeps
Repeated cycle
Beeps
Blinking at 0.5­second interval
Repeated cycle
32
Page 33
2. Flow chart of the detailed outdoor unit failure mode recall function
Operational procedure
The outdoor unit might be abnormal. Confi rm if outdoor unit is abnormal according to the following procedures.
Confi rm that the remote controller is in the failure mode recall function.
With the remote controller headed towards the indoor unit, press TOO COOL or TOO WARM button to adjust the set temperature to 25°C. 1
1. Regardless of normal or abnormal condition, 2 short beeps are emitted as the signal is received.
Does POWER lamp on the indoor unit blink at the interval of 0.5 seconds? Blinks: The outdoor unit is abnormal. Beep is emitted
at the same timing as the blinking of POWER lamp. 2
Yes
)
(Blinks
No (OFF)
The outdoor unit is abnormal. Check the blinking pattern, and confi rm the abnormal point with the out- door unit failure mode table (11-2.3.). Make sure to check at least two consecutive blinking cycles.
2
The outdoor unit is normal.
Releasing the failure mode recall function
Release the failure mode recall function by the following procedures. Turn OFF the power supply and turn it ON again. Press RESET button of the remote controller.
Release the failure mode recall function accord­ing to the left mentioned procedure.
Repair the defective parts.
Deleting the memorized abnormal condition
After repairing the unit, recall the failure mode again according to "Setting up the failure mode recall
function" (11-2.1.).
Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed) with
the remote controller headed towards the indoor unit. Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted. Release the failure mode recall function according to "Releasing the failure mode recall function" men-
tioned above.
NOTE: 1. Make sure to release the failure mode recall function once it is set up, otherwise the unit cannot operate properly.
2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.
2. Blinking pattern when outdoor unit is abnormal:
2.5-second OFF 3-second ON
ON
OFF
No beep
Repeated cycle
Blinking at 0.5-
second interval
Beeps
2.5-second OFF 3-second ON
No beep Beeps
Repeated cycle
33
Blinking at 0.5-
second interval
Repeated cycle
Page 34
3. Outdoor unit failure mode table
MUZ-FD25/35
POWER lamp
(Indoor unit)
OFF None (Normal)
2-time fl ash
2.5 seconds OFF
3-time fl ash
2.5 seconds OFF
4-time fl ash
2.5 seconds OFF
5-time fl ash
2.5 seconds OFF
Abnormal point
(Failure mode / protection)
Outdoor power system
Discharge temperature thermistor
Defrost thermistor
Fin temperature thermistor 3-time fl ash
P.C. board temperature thermistor
Ambient temperature thermistor
Overcurrent 11-time fl ash
Compressor synchronous abnormality (Compressor start-up failure protection)
Discharge temperature
"How
Indoor/outdoor
unit failure
mode recall
function


LED indication
(Outdoor P.C. board)
—— —
Overcurrent protection stop is continuously performed 3 times within
1-time fl ash every
2.5 seconds
2.5 seconds OFF
4-time fl ash
2.5 seconds OFF
2-time fl ash
2.5 seconds OFF
2.5 seconds OFF
12-time fl ash
2.5 seconds OFF
1 minute after the compressor gets started.
Thermistor shorts or opens during compressor running.
Large current fl ows into intelligent power module.
Waveform of compressor current is distorted.
Temperature of discharge temperature thermistor exceeds 116°C, compressor stops. Compressor can restart if discharge temperature thermistor reads 100°C or less 3 minutes later.
Condition Correspondence
Reconnect
• connectors. Refer to 11-5. "How
• to check inverter/ compressor". Check stop valve.
• Refer to 11-5.
• "Check of outdoor thermistors". Defective outdoor thermistors can be identifi ed by checking the blinking pattern of LED.
Reconnect
• compressor connector. Refer to 11-5.
• to check inverter/ compressor". Check stop valve.
Reconnect
• compressor connector. Refer to 11-5. "How
• to check inverter/ compressor".
Check refrigerant
• circuit and refrigerant amount. Refer to 11-5. "Check
• of LEV".
Outdoor unit failure mode
recall function
6-time fl ash
2.5 seconds OFF
7-time fl ash
2.5 seconds OFF
8-time fl ash
2.5 seconds OFF
9-time fl ash
2.5 seconds OFF
10-time fl ash
2.5 seconds OFF
11-time fl ash
2.5 seconds OFF
12-time fl ash
2.5 seconds OFF
14-time fl ash
2.5 seconds OFF
High pressure
Fin temperature/ P.C. board temperature
Outdoor fan motor
Nonvolatile memory data 5-time fl ash
Discharge temperature
DC voltage 8-time fl ash
Each phase current of compressor
Overcurrent Compressor open-phase
Stop valve (Closed valve) 14-time fl ash
7-time fl ash
2.5 seconds OFF
2.5 seconds OFF
2.5 seconds OFF
9-time fl ash
2.5 seconds OFF
10-time fl ash
2.5 seconds OFF
2.5 seconds OFF
Temperature indoor coil thermistor exceeds 70°C in HEAT mode. Temperature defrost thermistor exceeds 70°C in COOL mode.
Temperature of fi n temperature thermistor on the inverter P.C. board exceeds 75 ~ 80°C, or temperature of P.C. board temperature thermistor on the inverter P.C. board exceeds 70 ~ 75°C.
Outdoor fan has stopped 3 times in a row within 30 seconds after outdoor fan start-up.
Nonvolatile memory data cannot be read properly.
Temperature of discharge temperature thermistor has been 50°C or less for 20 minutes.
DC voltage of inverter cannot be detected normally.
Each phase current of compressor cannot be detected normally.
Large current fl ows into intelligent power module (IPM). The open-phase operation of compressor is detected. The interphase short out occurs in the output of the intelligent power module (IPM). The compressor winding shorts out.
Closed valve is detected by compressor current.
Check refrigerant
• circuit and refrigerant amount. Check stop valve.
Check around outdoor
• unit. Check outdoor unit air
• passage. Refer to 11-5. "Check
• of outdoor fan motor".
Refer to 11-5. "Check
• of outdoor fan motor". Refer to 11-5. "Check of inverter P.C. board".
Replace the inverter
• P.C. board.
Refer to 11-5. "Check
• of LEV". Check refrigerant
•— circuit and refrigerant amount.
Refer to 11-5. "How
• to check inverter/ compressor".
Reconnect
• compressor connector. Refer to 11-5.
• to check inverter/ compressor".
Check stop valve
NOTE: Blinking patterns of this mode differ from the ones of Troubleshooting check table (11-3.).
"How


34
Page 35
MUZ-FD50VA
LED indication
POWER lamp
(Indoor unit)
OFF None (Normal) Lighting Lighting
2-time fl ash Outdoor power system Lighting Lighting Overcurrent protection stop is continuously
3-time fl ash Discharge temperature
Abnormal point
(Failure mode / protection)
thermistor Defrost thermistor Lighting Once
(Outdoor P.C. board)
LED1 LED2
performed 3 times within 1 minute after the compressor gets started, or when converter protection stop or bus-bar voltage protection stop is continuously performed 3 times within 3 minutes after start-up.
Lighting Once Thermistor shorts or opens during compressor
running.
Condition Correspondence
• Check the connection of the compressor connecting wire.
• Refer to 11-5. "How to check inverter/compressor".
• Check the stop valve.
• Refer to 11-5. "Check of outdoor thermistors".
Indoor/outdoor
unit failure
mode recall
function
Ambient temperature thermistor
Fin temperature thermistor Lighting 3 times
P.C. board temperature thermistor
Outdoor heat exchanger temperature thermistor
4-time fl ash Overcurrent Once Goes out 28 A current fl ows into intelligent power module. • Reconnect compressor
5-time fl ash Discharge temperature Lighting Lighting Discharge temperature exceeds 116°C during
6-time fl ash High pressure Lighting Lighting The outdoor heat exchanger temperature
7-time fl ash Fin temperature 3 times Goes out The fi n temperature exceeds 87°C during
P.C. board temperature 4 times Goes out The P.C. board temperature exceeds 70°C
8-time fl ash Outdoor fan motor Lighting Lighting Failure occurs continuously three times within
9-time fl ash Nonvolatile memory data Lighting 5 times Nonvolatile memory data cannot be read
10-time fl ash Discharge temperature Lighting Lighting The frequency of the compressor is kept 80 Hz
11-time fl ash Communication error between
P.C. boards
Current sensor Lighting 7 times A short or open circuit is detected in the current
Zero cross detecting circuit 5 times Goes out Zero cross signal cannot be detected while the
Converter 5 times Goes out A failure is detected in the operation of the
Bus-bar voltage (1)
Bus-bar voltage (2)
Even if this protection stop
is performed continuously 3 times, it does not mean the abnormality in outdoor power system.
Lighting Twice
Lighting 4 times • Replace the outdoor
Lighting 9 times • Refer to 11-5. "Check of
operation. Compressor can restart if discharge temperature thermistor reads 100°C or less 3 minutes later.
exceeds 70°C during cooling or the indoor gas pipe temperature exceeds 70°C during heating.
operation.
during operation.
30 seconds after the fan gets started.
properly.
or more and the discharge temperature is kept under 39°C for more than 20 minutes.
Lighting 6 times Communication error occurs between the
5 times Goes out The bus-bar voltage exceeds 400 V or falls to
6 times Goes out The bus-bar voltage exceeds 400 V or falls to 50
electronic control P.C. board and power board for more than 10 seconds.
The communication between boards protection stop is continuously performed twice.
sensor during compressor operating.
Current sensor protection stop is continuously performed twice.
compressor is operating.
The protection stop of the zero cross detecting circuit is continuously performed 10 times.
converter during operation.
200 V or below during compressor operating.
V or below during compressor operating.
electronic control P.C. board.
outdoor thermistors".
connector.
• Refer to 11-5. "How to check inverter/compressor.
• Check the stop valve.
• Check refrigerant circuit and refrigerant amount.
• Refer to 11-5. LEV".
• Check refrigerant circuit and refrigerant amount.
• Check the stop valve.
• Check around outdoor unit.
• Check outdoor unit air passage.
• Refer to 11-5. "Check of outdoor fan motor".
• Refer to 11-5. outdoor fan motor".
• Replace the outdoor electronic control P.C. board.
• Check refrigerant circuit and refrigerant amount.
• Refer to 11-5. "Check of LEV".
Check the connecting wire
between outdoor electronic control P.C. board and power board.
Replace the power board.
Check the connecting wire
among electronic control P.C. board, noise fi lter P.C. board and power board.
• Check the voltage of power supply.
Replace the power board.
• Check the voltage of power supply.
• Replace the outdoor electronic control P.C. board.
"Check of
"Check of
NOTE: Blinking patterns of this mode differ from the ones of Troubleshooting check table (11-3.).
35
Page 36
11-3. TROUBLESHOOTING CHECK TABLE
MUZ-FD25/35
No. Symptom LED indication
Outdoor unit does not op-
1
erate.
2
3
4
5
6
'Outdoor unit stops and
7
restarts 3 minutes later' is repeated.
8
9
10
11
12
13
14
Outdoor unit
15
operates.
16
17
Outdoor unit operates.
18
1-time fl ash every
2.5 seconds
6-time fl ash
2.5 seconds OFF 11-time fl ash
2.5 seconds OFF 14-time fl ash
2.5 seconds OFF
2-time fl ash
2.5 seconds OFF
3-time fl ash
2.5 seconds OFF
4-time fl ash
2.5 seconds OFF
5-time fl ash
2.5 seconds OFF
8-time fl ash
2.5 seconds OFF
10-time fl ash
2.5 seconds OFF
12-time fl ash
2.5 seconds OFF 13-time fl ash
2.5 seconds OFF 1-time fl ash
2.5 seconds OFF 3-time fl ash
2.5 seconds OFF
4-time fl ash
2.5 seconds OFF
7-time fl ash
2.5 seconds OFF
Abnormal point/
Condition
Outdoor power sys­tem
Outdoor thermistors Discharge temperature thermistor, fi n temperature thermistor,
Outdoor control sys­tem
Serial signal The communication fails between the indoor and outdoor unit
Stop valve/ Closed valve
Outdoor unit (Other abnormality)
Overcurrent protec­tion
Discharge tempera­ture overheat protec­tion
Fin temperature /P.C. board tem­perature thermistor overheat protection
High pressure pro­tection
Compressor syn­chronous abnormal­ity
Outdoor fan motor Outdoor fan has stopped 3 times in a row within 30 seconds
Each phase current of compressor
DC voltage DC voltage of inverter cannot be detected normally. Refer to 11-5. "How to check in-
Frequency drop by current protection
Frequency drop by high pressure pro­tection
Frequency drop by defrosting in COOL mode
Frequency drop by discharge tempera­ture protection
Low discharge tem­perature protection
Condition Correspondence
Overcurrent protection stop is continuously performed 3 times within 1 minute after the compressor gets started.
defrost thermistor, P.C. board temperature thermistor or ambi­ent temperature thermistor shorts or opens during compressor running.
Nonvolatile memory data cannot be read properly.
(POWER lamp of the indoor unit lights up or fl ashes 7-time.)
for 3 minutes. Closed valve is detected by compressor current. Check stop valve.
Outdoor unit is defective. Refer to 11-2.2. "Flow chart of the
Large current fl ows into intelligent power module. Reconnect connector of compres-
Temperature of discharge temperature thermistor exceeds 116 °C, compressor stops. Compressor can restart if discharge temperature thermistor reads 100°C or less 3 minutes later.
Temperature of fi n temperature thermistor on the heat sink exceeds 75 ~ 80°C or temperature of P.C. board temperature thermistor on the inverter P.C.board exceeds 70 ~ 75°C.
Indoor coil thermistor exceeds 70°C in HEAT mode. Defrost thermistor exceeds 70°C in COOL mode.
The waveform of compressor current is distorted. Reconnect connector of compres-
after outdoor fan start-up.
Each phase current of compressor cannot be detected nor­mally.
Current from power outlet is nearing breaker capacity. The unit is normal, but check the
Temperature of indoor coil thermistor exceeds 55°C in HEAT mode, compressor frequency lowers.
Indoor coil thermistor reads 8°C or less in COOL mode, com­pressor frequency lowers.
Temperature of discharge temperature thermistor exceeds 111 °C, compressor frequency lowers.
Temperature of discharge temperature thermistor has been 50 °C or less for 20 minutes.
Reconnect connector of compres­sor.
Refer to 11-5. verter/compressor". Check stop valve.
Refer to 11-5. thermistors".
Replace inverter P.C. board.
Refer to 11-5. "How to check mis-
• wiring and serial signal error.
• detailed outdoor unit failure mode recall function".
• sor.
Refer to 11-5. verter/compressor". Check stop valve.
• Check refrigerant circuit and refrig-
• erant amount. Refer to 11-5. "Check of LEV".
Check around outdoor unit.
Check outdoor unit air passage.
Refer to 11-5. fan motor".
Check refrigerant circuit and refrig-
• erant amount. Check stop valve.
• sor. Refer to 11-5. "How to check in-
• verter/compressor".
Refer to 11-5.
• fan motor. Refer to 11-5. "Check of inverter
• P.C. board.
Refer to 11-5. verter/compressor".
• verter/compressor".
following. Check if indoor fi lters are clogged.
• Check if refrigerant is short.
• Check if indoor/outdoor unit air cir-
• culation is short cycled.
Check refrigerant circuit and refrig-
• erant amount. Refer to 11-5.
• Refer to 11-5. "Check of outdoor
• thermistors".
Refer to 11-5.
• Check refrigerant circuit and refrig-
• erant amount.
"How to check in-
"Check of outdoor
"How to check in-
"Check of outdoor
"Check of outdoor
"How to check in-
"Check of LEV".
"Check of LEV".
8-time fl ash
2.5 seconds OFF
19
9-time fl ash
20
NOTE: 1. The location of LED is illustrated at the right fi gure. Refer to 11-6.1.
2. LED is lighted during normal operation.
The fl ashing frequency shows the number of times the LED blinks after every 2.5-second OFF. (Example) When the fl ashing frequency is “2”.
ON
2.5-second OFF
OFF
2.5 seconds OFF
PAM protection PAM: Pulse Ampli­tude Modulation
Inverter check mode The connector of compressor is disconnected, inverter check
0.5-second ON
2.5-second OFF
The overcurrent fl ows into IGBT (Insulated Gate Bipolar tran- sistor: TR821) or the bus-bar voltage reaches 320 V or more, PAM stops and restarts.
mode starts.
0.5-second ON
3636
This is not malfunction. PAM pro­tection will be activated in the fol­lowing cases: 1 Instantaneous power voltage
drop. (Short time power failure)
2 When the power supply voltage
is high.
Check if the connector of the com-
• pressor is correctly connected. Refer to 11-5. "How to check inverter/compressor".
Inverter P.C. board (Parts side)
LED
Flashing
Page 37
MUZ-FD50VA
No. Symptom
Outdoor unit does not oper­ate.
1
2
3
4
5
6
7
8
LED indication
LED1(Red)
Lightning
Lightning
Lightning
Lightning
Lightning
Lightning
Lightning
Lightning
Abnormal point/ Con-
LED2(Yellow)
Twice
3 times
4 times
5 times
6 times
7 times
8 times
11 times
dition
Outdoor power system
Discharge temperature thermistor
Fin temperature thermistor
P.C. board tempera­ture thermistor
Ambient temperature thermistor
Outdoor heat exchanger temperature thermistor
Defrost thermistor A short circuit is detected in the thermistor during operation, or
Serial signal The communication fails between the indoor and outdoor unit 3
Nonvolatile memory data
Current sensor Current sensor protection stop is continuously performed twice. • Replace the power board.
Communication error between P.C. boards
Overcurrent protection stop is continuously performed 3 times within 1 minute after the compressor gets started, or when converter protection stop or bus-bar voltage protection stop is continuously performed three times within 3 minutes after start­up.
A short circuit is detected in the thermistor during operation, or when an open circuit is detected in the thermistor after 10 min­utes of compressor start-up.
A short or open circuit is detected in the thermistor during op­eration.
A short or open circuit is detected in the thermistor during op­eration.
A short circuit is detected in the thermistor during operation, or an open circuit is detected in the thermistor after 5 minutes (in cooling) and 10 minutes (in heating) of compressor start-up.
an open circuit is detected in the thermistor after 5 minutes of compressor stat-up.
minutes. The nonvolatile memory data cannot be read properly. • Replace the outdoor electronic
The communication protection stop between boards is continu­ously performed twice.
Condition Correspondence
• Check the connection of the com­pressor connecting wire.
• Refer to 11-5. "How to check in­verter/compressor".
• Check the stop valve.
• Refer to 11-5. "Check of outdoor thermistor".
• Refer to 11-5. thermistor".
• Replace the outdoor electronic control P.C. board.
• Refer to 11-5. "Check of outdoor thermistor".
• Refer to 11-5. miswiring and serial signal error.
control P.C. board.
• Check the connecting wire be­tween outdoor electronic control P.C. board and power board.
"Check of outdoor
"How to check
9
’Outdoor unit stops and restarts 3 min­utes later’ is
10
repeated.
11 3 times
12 4 times
13 5 times
14 8 times
15 9 times
16 13 times
17 Lighting 8 times
18 Lighting 11 times
Lightning
Twice
12 times
Goes
out
Goes
out
Goes
out
Goes
out
Goes
out
Goes
out
Goes
out
Zero cross detecting circuit
lPM protection Overcurrent is detected after 30 minutes of compressor start-
Lock protection Overcurrent is detected within 30 minutes of compressor start-
Discharge tempera­ture protection
Fin temperature pro­tection
P.C. board temperature protection
High-Pressure pro­tection
Converter protection A failure is detected in the operation of the converter during
Bus-bar voltage pro­tection (1).
Bus-bar voltage pro­tection (2)
Outdoor fan motor Failure occurs continuously three times within 30 seconds after
Current sensor pro­tection
Communication be­tween P.C. boards protection
The protection stop of the zero cross detecting circuit is con­tinuously performed 10 times.
up.
up.
Discharge temperature exceeds 116°C during operation and compressor stops. Compressor can restart if discharge tem­perature thermistor reads 100°C or less 3 minutes later.
The fi n temperature exceeds 87°C during operation. • Check around outdoor unit.
The P.C. board temperature exceeds 70°C during operation.
The outdoor heat exchanger temperature exceeds 70°C during cooling or indoor gas pipe temperature exceeds 70°C during heating.
operation. The bus-bar voltage exceeds 400 V or falls to 200 V or below
during compressor operating.
The bus-bar voltage exceeds 400 V or falls to 50 V or below during compressor operating.
the fan gets started. A short or open circuit is detected in the current sensor during
compressor operating. Communication error occurs between the outdoor electronic
control P.C. board and power board for more than 10 seconds
• Check the connecting wire among outdoor electronic control P.C. board, noise fi lter P.C. board and power board.
• Reconnect compressor connector.
• Refer to 11-5. "How to check in­verter/compressor".
• Check the stop valve.
• Check the power module (PAM module).
• Check the amount of gas and re­frigerant circuit.
• Refer to 11-5. "Check of LEV".
• Check outdoor unit air passage.
• Refer to 11-5. fan motor".
• Check the amount of gas and the refrigerant circuit.
• Check the stop valve.
• Replace the power board.
• Check the voltage of power supply.
• Replace the power board or the outdoor electronic control P.C. board.
• Refer to 11-5. "Check of bus-bar voltage".
• Refer to 11-5. "Check of outdoor fan motor".
• Replace the power board.
• Check the connecting wire be­tween outdoor electronic control P.C. board and power board.
"Check of outdoor
Zero cross detecting
19 Lighting 12 times
NOTE: 1. The location of LED is illustrated at the right fi gure. Refer to 11-6.2.
2. LED is lighted during normal operation.
The fl ashing frequency shows the number of times the LED blinks after every 2.5-second OFF. (Example) When the fl ashing frequency is “2”.
ON
2.5-second OFF
OFF
circuit protection
Zero cross signal cannot be detected while the compressor is operating.
0.5-second ON
2.5-second OFF
37
• Check the connecting wire among outdoor electronic control P.C. board, noise fi lter P.C. board and power board.
Outdoor electronic control P.C. board (Parts side)
LED2 LED1
Lighting
0.5-second ON
Page 38
No. Symptom
Outdoor unit operates.
20
21
22
23
LED indication
LED1(Red)
Once
Twice
3 times
4 times
Abnormal point/ Con-
LED2(Yellow)
Primary current pro­tection
Lighting
Secondary current pro­tection
High-Pressure protec­tion
Lighting
Defrosting in cooling
Discharge temperature protection
Lighting
Low discharge tem­perature protection
Lighting
dition
Condition Correspondence
The input current exceeds 15 A. These symptoms do not mean any
The current of the compressor exceeds 13 A.
The indoor gas pipe temperature exceeds 45°C during heating.
The indoor gas pipe temperature falls 3°C or below during cooling.
The discharge temperature exceeds 100°C during operation. • Check refrigerant circuit and refrig-
The frequency of the compressor is kept 80 Hz or more and the discharge temperature is kept under 39°C for more than 20 minutes.
abnormality of the product, but check the following points.
• Check if indoor fi lters are clogged.
• Check if refrigerant is short.
• Check if indoor/outdoor unit aircir­culation is short cycled.
erant amount.
• Refer to 11-5. "Check of LEV".
• Refer to 11-5. "Check of outdoor thermistors’’.
• Refer to 11-5. "Check of LEV".
• Check refrigerant circuit and refrig­erant amount.
24
25
26
Outdoor unit operates
5 times
9 times
Lighting
Cooling high-pressure protection
Lighting
Inverter check mode The unit is operated with emergency operation switch.
Lighting
Normal
Lighting
The outdoor heat exchanger temperature exceeds 58°C during operation.
——
This symptom does not mean any abnormality of the product, but check the following points.
• Check if indoor fi lters are clogged.
• Check if refrigerant is short.
• Check if indoor/outdoor unit air circulation is short cycled.
38
Page 39
11-4. TROUBLE CRITERION OF MAIN PARTS
MUZ-FD25VA MUZ-FD25VAH MUZ-FD35VA MUZ-FD35VAH MUZ-FD50VA
Part name Check method and criterion Figure
Defrost thermistor (RT61)
Ambient temperature thermistor (RT65)
Fin temperature thermistor (RT64)
Outdoor heat exchanger temperature thermistor (RT68)
Discharge temperature thermistor (RT62)
Compressor
Outdoor fan motor
Measure the resistance with a tester.
Refer to 11-6. "Test point diagram and voltage," 1. "Inverter P.C. board", or 2. "Outdoor electronic control P.C. board", the chart of ther­mistor.
Measure the resistance with a tester. Before measurement, hold the thermistor with your hands to warm it up.
Refer to 11-6. "Test point diagram and voltage," 1. "Inverter P.C. board", or 2. "Outdoor electronic control P.C. board", the chart of ther­mistor.
Measure the resistance between terminals using a tester. (Temperature: -10 ~ 40°C)
Normal
U-V
U-W
V-W
25/35 50
0.82 ~ 1.11 0.60 ~ 0.82
Measure the resistance between lead wires using a tester. (Temperature: -10 ~ 40°C)
Color of lead wire Normal
RED – BLK
BLK – WHT
WHT – RED
25/35 50
11 ~ 16 12 ~ 17
WHT
V
WHT
V
RED BLK
W
U
RED BLK
W
U
R. V. coil (21S4)
Expansion valve coil (LEV)
Defrost heater
MUZ-FD•VAH
High pressure switch (HPS) MUZ-FD50
Measure the resistance using a tester. (Temperature: -10 ~ 40°C)
Normal
25/35 50
1.19 ~ 1.78 k 1.15 ~ 1.71 k
Measure the resistance using a tester. (Temperature: -10 ~ 40°C)
Color of lead wire Normal
WHT – RED RED – ORN
YLW – BRN
37 ~ 54
BRN – BLU
Measure the resistance using a tester. (Temperature: -10 ~ 40°C)
Normal
349 ~ 428
Pressure
3.7 ± 0.15 MPa Close
+0.05
4.8
MPa Open
-0.1
WHT
RED ORN
YLW
LEV
BRN
BLU
3939
Page 40
11-5. TROUBLESHOOTING FLOW
A How to check inverter/compressor
MUZ-FD25/35
Disconnect the connector (CN61) between compressor and the intelligent power module (IPM).
Check the voltage between terminals.
Are the voltages balanced?
Yes
Check the compressor.
MUZ-FD50
Disconnect the terminal of the compres­sor. 3 minutes after turning on the power supply, start EMERGENCY OPERATION.
Measure the voltage between each lead wire leading to the compressor. U (BLK) - V (WHT) V (WHT) - W (RED) W (RED) - U (BLK)
Is output balanced?
Yes
Is the input voltage to the outdoor electronic control P.C. board 370 V or more?
Yes
Turn OFF power supply of indoor and outdoor unit, and measure the com­pressor winding resistance between the compressor terminals. Is the resistance between each terminal normal? (Refer to 11-4.)
Yes
Reconnect the lead wire of compressor, and turn ON power supply to indoor and outdoor unit. 3 minutes later, starts EMERGENCY OP­ERATION.
Does the compressor run for 10 seconds or more after it starts?
No
See 11-5. “Check of open phase”.
No
Replace the inverter P.C. board.
See 11-5. “Check of compressor”.
After the outdoor fan starts running, wait for 1 minute or more before measuring the volt-
• age. Output voltage is 50 - 130 V. (The voltage may differ according to the tester.)
No
Replace the power board.
No
<<Judgement>>
0 second
1 second
Compressor starts
Abnormal (IPM failure)
2 seconds
No
Replace the compressor.
(Compressor winding short)
Abnormal (Compressor lock out) (Starting defect)
Abnormal (Poor contact,)
10 seconds
(Outdoor P.C. board defect) (Disconnected connector)
Abnormal (Refrigerant circuit defect) (Closed valve)
10 minutes
Normal
Yes
Refer to <<Judgement>>. Check the refrigerant circuit. Check the stop valve.
After the compressor is heated with a drier, does the compressor start? 1
Yes
Compressor start failure. Activate pre-heat control. (Refer to 10-2. "PRE-HEAT CONTROL SETTING")
No
Refer to <<Judgement>>. Replace the compressor.
4040
1 Heat the compressor with a drier for about 20 minutes. Do not recover refrigerant gas while heating.
Heating part
Page 41
B Check of open phase
MUZ-FD25/35
With the connector between the compressor and the intelligent power module disconnected, activate the inverter and check if
the inverter is normal by measuring the balance of voltage between the terminals.
Output voltage is 50 - 130 V. (The voltage may differ according to the tester.)
<< Operation method>> Start cooling or heating operation by pressing EMERGENCY OPERATION switch on the indoor unit. (TEST RUN OPERA-
TION: Refer to 8-3.) <<Measurement point>> At 3 points BLK (U)-WHT (V) BLK (U)-RED (W) WHT(V)-RED (W)
NOTE: 1. Output voltage varies according to power supply voltage.
2. Measure the voltage by analog type tester.
3. During this check, LED of the inverter P.C. board fl ashes 9 times. (Refer to 11-6.1.)
Measure AC voltage between the lead wires at 3 points.
C Check of compressor
MUZ-FD25/35
Refer to 11-5. “Check of compressor winding”. Is the compressor normal?
Yes
Refer to 11-5. “Check of compressor operation time”. Does the compressor operate continuously?
Yes
OK.
No
No
Replace the compressor.
Refer to 11-5. “Check of compressor start failure”.
41
Page 42
D Check of compressor winding
MUZ-FD25/35
Disconnect the connector (CN61) between the compressor and intelligent power module, and measure the resistance be-
tween the compressor terminals. <<Measurement point>> at 3 points BLK-WHT BLK-RED WHT-RED <<Judgement>> Refer to 11-4. 0 [] ················Abnormal [short] Infinite [] ·······Abnormal [open] NOTE: Be sure to zero the ohmmeter before measurement.
Measure the resistance between the lead wires at 3 points.
E Check of compressor operation time
MUZ-FD25/35
Connect the compressor and activate the inverter. Then measure
the time until the inverter stops due to over current.
<<Operation method>>
Start heating or cooling operation by pressing EMERGENCY
OPERATION switch on the indoor unit.
(TEST RUN OPERATION: Refer to 8-3.)
<<Measurement>>
Measure the time from the start of compressor to the stop of
compressor due to overcurrent.
F Check of compressor start failure
MUZ-FD25/35
Confi rm that ~ is normal.
•Electrical circuit check . Contact of the compressor connector (Including CN61) . Output voltage of inverter P.C. board and balance of them (See 11-5. ) . Direct current voltage between DB61(+) and (-) on the inverter P.C. board . Voltage between outdoor terminal block S1-S2
<<Judgement>>
0 second
1 second
2 seconds
10 seconds
10 minutes
Compressor starts
Abnormal (IPM failure) (Compressor winding short)
Abnormal (Compressor lock out) (Starting defect)
Abnormal (Poor contact) (Outdoor P.C. board defect) (Disconnected connector)
Abnormal (Refrigerant circuit defect) (Closed valve)
Normal
Does the compressor run for 10 seconds or more after it starts?
No
After the compressor is heated with a drier, does the compressor start? 1
Yes
Compressor start failure. Activate pre-heat control. (Refer to 10-2. "PRE-HEAT CONTROL SETTING")
Yes
No
Check the refrigerant circuit. Check the stop valve.
Replace the compressor.
1 Heat the compressor with a drier for about 20 minutes. Do not recover refrigerant gas while heating.
Heating part
42
Page 43
G Check of outdoor thermistors
Disconnect the connector of thermistor in the outdoor P.C. board (see below table), and measure the resistance of thermistor.
Is the resistance of thermistor normal? (Refer to 11-6.1. or 11-6.2.)
Yes
Reconnect the connector of thermistor. Turn ON the power supply and press EMERGENCY OPERATION switch.
Does the unit operate for 10 minutes or more without showing thermistor abnormality?
Yes
OK. (Cause is poor contact.)
No
No
Replace the thermistor except RT64. When RT64 is abnormal, replace the inverter P.C. board or the outdoor power board.
Replace the inverter P.C. board or the outdoor electronic control P.C. board.
MUZ-FD25/35
Thermistor Symbol Connector, Pin No. Board Defrost RT61 Between CN641 pin1 and pin2 Discharge temperature RT62 Between CN641 pin3 and pin4 Fin temperature RT64 Between CN642 pin1 and pin2 Ambient temperature RT65 Between CN643 pin1 and pin2 Outdoor heat exchanger temperature RT68 Between CN644 pin1 and pin3
Inverter P.C. board
MUZ-FD50
Thermistor Symbol Connector, Pin No. Board Defrost RT61 Between CN661 pin 1 and pin 2 Discharge temperature RT62 Between CN661 pin 3 and pin 4 Outdoor heat exchanger temperature RT68 Between CN661 pin 7 and pin 8 Ambient temperature RT65 Between CN663 pin 1 and pin 2 Fin temperature RT64 Between CN3 pin 1 and pin 2 Outdoor power board
Outdoor electronic control P.C. board
H Check of R.V. coil
MUZ-FD25/35
First of all, measure the resistance of R.V. coil to check if the coil is defective. Refer to 11-4. In case CN721 is disconnected or R.V. coil is open, voltage is generated between the terminal pins of the connector
although no signal is being transmitted to R.V. coil.
Check if CN721 is connected.
Unit operates COOL mode even if it is set to HEAT mode.
Disconnect connector (CN61) between the compressor and the intelligent power module. Turn ON the power supply and press EMERGENCY OPERATION switch twice (HEAT mode).
Unit operates HEAT mode even if it is set to COOL mode.
Disconnect connector (CN61) between the compressor and the intelligent power module. Turn ON the power supply and press EMERGENCY OPERATION switch once (COOL mode).
Is there 230 VAC between CN721
on the inverter P.C. board 3 minutes
after the power supply is turned ON?
Yes
Replace the 4-way valve.
Is there 230 VAC between CN721 and
on the inverter P.C. board 3 minutes
after the power supply is turned ON?
No
and
Replace the inverter
No
P.C. board.
Replace the inverter
Yes
P.C. board.
Replace the 4-way valve.
43
Page 44
MUZ-FD50
Heating operation does not work.
Disconnect the lead wire leading to the compressor.
1. 3 minutes after turning on the power supply, start EMERGENCY
2. OPERATION in HEAT mode.
Is there voltage of 230 VAC between pin1 and pin 2 at connector CN912?
Yes
Turn OFF power supply of indoor and outdoor unit.
Disconnect the connec­tor CN912 in noise fi lter P.C. board. Is there normal resistance to R.V. coil?
Yes
Replace the 4-way valve.
Cooling operation does not work.
Disconnect the lead wire leading to the compressor.
1. 3 minutes after turning on the power supply, start EMERGENCY
2. OPERATION in COOL mode.
Is there voltage of 230 VAC between pin1 and pin 2 at connector CN912?
Replace the R.V. coil.
No
No
No
1.
Turn off power supply of indoor and outdoor unit, and discon­nect the connector CN781 in the outdoor electronic control P.C. board.
2.
3 minutes after turning ON the power supply, start EMER­GENCY OPERATION in HEAT mode.
Is there voltage 12 VDC be­tween the connector CN781 pin 5 (+) and pin 3 (-)?
Yes
Replace the noise fi lter P.C. board.
If the connector CN912 is disconnected or
R.V. coil is open, voltage occurs between terminals even when the control is OFF.
Replace the 4-way valve.
Replace the outdoor electronic control P.C.
No
board.
Turn OFF power supply of indoor and outdoor unit, and
1. disconnect the connector CN781 in the outdoor electronic control P.C. board. 3 minutes after turning ON the power supply, start EMER-
2. GENCY OPERATION in COOL mode.
Is there voltage 12 VDC between the connector CN781 pin 5 (+) and pin 3 (-)?
Yes
Replace the outdoor electronic control P.C. board.
No
Replace the noise fi lter P.C. board.
44
Page 45
I Check of outdoor fan motor
MUZ-FD25/35
Disconnect CN932 from the inverter P.C. board, and measure the resistance of the outdoor fan motor.
Is the resistance of outdoor fan motor normal? (Refer to 11-4.)
Yes
Replace the inverter P.C. board.
MUZ-FD50
Disconnect CN932 from the outdoor electronic control P.C. board, and measure the resistance of the outdoor fan motor.
Is the resistance of outdoor fan motor normal? (Refer to 11-4.)
No
(Fixed to either 5 or 0 VDC)
Replace the outdoor fan motor.
Yes
No
Turn on the power supply. Rotate the outdoor fan motor manually and measure the voltage of CN931. Between 1(+) and 5(-) Between 2(+) and 5(-) Between 3(+) and 5(-)
No
No
Replace the outdoor fan motor.
Does the voltage between each terminal become 5 and 0 VDC repeatedly?
Yes
Does the outdoor fan motor rotate smoothly?
Yes
Replace the outdoor electronic control P.C. board.
45
Page 46
J Check of power supply
MUZ-FD25/35
Disconnect the connector (CN61) between compressor and intelligent power module. Turn ON power supply and press EMERGENCY OPERATION switch.
Does POWER lamp on the indoor unit light up?
Yes
No
Rectify indoor/outdoor connecting wire.
Yes
Is there voltage 230 VAC between the indoor terminal block S1 and S2?
Replace the indoor electronic control P.C.
No
board.
Is there voltage 280 ~ 370 VDC between DB61 (+) and DB61 (–) on the inverter P.C. board? (Refer to 11-6.1.)
No
Check the electric parts in main circuit.
MUZ-FD50
Check the connecting of parts of main power supply circuit.
Turn ON power supply.
Is there voltage of 230 VAC in the power sup­ply terminal block?
Yes
Is the output voltage from the noise fi lter P.C. board 230 VAC?
Yes
Yes
Dose LED on the inverter P.C. board light up or fl ash? (Refer to 11-6.1.)
Yes
If light up, OK. If fl ash, refer to 11-3.
No
No
Check the power supply cable.
Is fuse (F64) blown?
Yes
Replace the inverter
No
P.C. board.
DB61
Inverter P.C. board (Solder side)
No
Replace the noise fi lter P.C. board.
280 ~ 370 VDC
Is the input voltage to the power board 230 VAC?
Yes
Is the input voltage to the outdoor electronic control P.C. board 325 VDC?
Yes
Replace the outdoor electronic control P.C. board.
No
No
Replace the fuse.
Replace the reactor.
Replace the power board.
46
Page 47
K Check of LEV (Expansion valve)
Turn ON the power supply. <Preparation of the remote controller>
While pressing both OPERATION SELECT button
and TOO COOL button on the remote controller at the same time, press RESET button.
First, release RESET button.
And release the other two buttons after all LCD ex-
cept the set temperature in operation display section of the remote controller is displayed after 3 seconds.
Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit. 1
Expansion valve operates in full-opening direction.
Do you hear the expansion valve "click, click·······"? Do you feel the expansion valve vibrate on touching it ?
No
Yes
OK
1. Regardless of normal or abnormal condition, a short beep is emitted once the signal is received.
Is LEV coil properly fi xed to the expansion valve?
Yes
Does the resistance of LEV coil have the characteristics? (Refer to 11-4.)
No
Replace the LEV coil.
NOTE: After check of LEV, do the undermentioned operations.
1. Turn OFF the power supply and turn it ON again.
2. Press RESET button on the remote controller.
No
Yes
Properly fi x the LEV coil to the expansion valve.
Measure each voltage between connector pins of CN724 on the inverter P.C. board or CN795 on the outdoor electronic control P.C. board.
1. Pin (-) — Pin (+)
2. Pin (-) — Pin (+)
3. Pin (-) — Pin (+)
4. Pin (-) — Pin (+) Is there about 3 ~ 5 VAC between each? NOTE: Measure the voltage by an analog
tester.
Replace the expansion valve.
Yes
Replace the inverter P.C. board or the outdoor
No
electronic control P.C. board.
47
Page 48
L Check of inverter P.C. board
MUZ-FD25/35
Check the outdoor fan motor. (Refer to 11-5. .)
Is the fuse (F901) blown on the in­verter P.C. board?
No
Check the connection of the connectors (CN932) of the outdoor fan motor. If the connection is poor, make it correct.
Operate the outdoor unit by starting EMERGENCY OPERATION.
Check the LED indication on the in­verter P.C. board. Does the LED fl ash 10 times?
Yes (10-time fl ash)
Replace the inverter P.C. board.
Yes
No
Inverter P.C. board (Solder side)
CN932
Check the corresponding parts following LED indication. (Refer to 11-3.)
48
Page 49
M How to check miswiring and serial signal error
Turn OFF the power supply.
Is there rated voltage in the power supply?
Turn ON the power supply.
Is there rated voltage between outdoor termi­nal block S1 and S2?
Press EMERGENCY OPERATION switch once.
Does AREA-L lamp light up? <Confi rmation of the power to the indoor unit>
Is serial signal error indicated 6 minutes later?
Turn OFF the power supply. Check once more if the indoor/outdoor
B
connecting wire is not miswiring. Short-circuit outdoor terminal block S2 and S3.
1
Turn ON the power supply.
Yes
Yes
Yes
Yes
A
No
Check the power supply.
No
No
No
1. Miswiring may damage indoor electronic control P.C. board during the operation.
Be sure to confi rm the wiring is correct before the operation
starts.
3. Be sure to check this within 3 minutes after turning ON. After 3 minutes, LED blinks 6 times. Even when the inverter P.C. board or the outdoor electronic control P.C. board is normal, LED blinks 6 times after 3 minutes.
Check the wiring.
Is there any miswiring, poor contact, or wire disconnection of the indoor/outdoor connect­ing wire?
No
Yes
Correct them.
A
Turn OFF inverter-controlled lighting
• equipment. Turn OFF the power supply and then
• turn ON again.
Press EMERGENCY OPERATION switch.
Reinstall
• either the unit or the light each other
No
away. Attach a fi lter on remote control receiv­ing section of the indoor unit.
Is serial signal error indicated 6 minutes later?
Yes
B
Does the LED on the inverter P.C. board or the outdoor electronic control P.C. board repeat "3.6-second-OFF and 0.8-second­ON quick blinking"?
Turn OFF the power supply. Remove the short-circuit between outdoor terminal block S2 and S3. Turn ON the power supply. Is there amplitude of 10 to 20 VDC between outdoor terminal block S2 and S3? <Confi rmation of serial signal>
Is there rated voltage between indoor terminal block S1 and S2? <Confi rmation of power voltage>
Replace the indoor electronic control P.C. board.
Be sure to release the failure-mode recall function after checking.
3
Yes
Yes
Yes
No (Lighted or not lighted)
No
No
Replace the inverter P.C. board or the outdoor electronic control P.C. board.
2
2. Be careful of the residual voltage of smoothing capacitor.
Is there any error of the in­door/outdoor connecting wire, such as the damage of the wire, intermediate connection, poor contact to the terminal block?
Is there any error of the in­door/outdoor connecting wire, such as the damage of the wire, intermediate connection, poor contact to the terminal block?
No
No
Replace the indoor/ outdoor connecting
Yes
wire.
Replace the indoor/ outdoor connecting
Yes
wire.
49
Page 50
N Electromagnetic noise enters into TV sets or radios
Is the unit earthed?
Yes
Is the distance between the antennas and the indoor unit within 3 m, or is the distance between the antennas and the outdoor unit within 3 m?
No
Is the distance between the TV sets or radios and the indoor unit within 1 m, or is the distance between the TV sets or radios and the outdoor unit within 3 m?
No
Are the antennas damaged? Is the coaxial cable damaged? Is there any poor contact in the anten­na wiring?
No
Is the indoor/outdoor connecting wire of the air conditioner and the wiring of the antennas close?
No
No
Yes
Yes
Yes
Yes
Earth the unit.
Extend the distance between the antennas and the indoor unit, and/or the antennas and the outdoor unit.
Extend the distance between the TV sets and/or radios and the indoor unit, or the TV sets or radios and the outdoor unit.
Replace or repair the antenna. Replace or repair the coaxial cable.
Extend the distance between the indoor/outdoor connecting wire of the air conditioner and the wir­ing of the antennas.
Even if all of the above conditions are fulfi lled, the electromagnetic noise may enter, depending on the electric fi eld strength or the installation condition (combination of specifi c conditions such as antennas or wiring). Check the following before asking for service.
1. Devices affected by the electromagnetic noise TV sets, radios (FM/AM broadcast, shortwave)
2. Channel, frequency, broadcast station affected by the electromagnetic noise
3. Channel, frequency, broadcast station unaffected by the electromagnetic noise
4. Layout of : indoor/outdoor unit of the air conditioner, indoor/outdoor wiring, earth wire, antennas, wiring from antennas, receiver
5. Electric fi eld intensity of the broadcast station affected by the electromagnetic noise
6. Presence or absence of amplifi er such as booster
7. Operation condition of air conditioner when the electromagnetic noise enters in
1) Turn OFF the power supply once, and then turn ON the power supply. In this situation, check for the electromagnetic noise.
2) Within 3 minutes after turning ON the power supply, press OPERATE/STOP (ON/OFF) button on the remote controller for power ON, and check for the electromagnetic noise.
3) After a short time (3 minutes later after turning ON), the outdoor unit starts running. During operation, check for the electromagnetic noise.
4) Press OPERATE/STOP (ON/OFF) button on the remote controller for power OFF, when the outdoor unit stops but the indoor/outdoor communication still runs on. In this situation, check for the electromagnetic noise.
50
Page 51
O Check of defrost heater
MUZ-FD25VAH MUZ-FD35VAH
Check the following points before checking electric continuity.
1. Does the resistance of ambient temperature thermistor have the characteristics? Refer to 11-6.1.
2. Is the resistance of defrost heater normal? Refer to 11-4.
3. Does the heater protector remain conducted (not open)?
4. Are both ambient temperature thermistor and circuit of defrost heater securely connected to connectors?
In HEAT mode, for more than 5 minutes, let the ambient temperature thermistor continue to read 5°C or below, and let the defrost thermistor continue to read -1°C or below.
NOTE: In case both thermistors are more than the above temperature, cool them with cold
water etc...
Is there 230 VAC between CN722 and on the inverter P.C. board? Refer to 11-6.1.
No
Replace the inverter P.C. board.
P Check of bus-bar voltage
MUZ-FD50
•Check the voltage of power supply.
•Confi rm outdoor unit failure mode recall function. (Refer to 11-2.2)
Confi rm LED1 indication lamp on the outdoor electronic control P.C.
board.
Blink 5 times
Replace the power board.
Yes
Blink 6 times
Replace the outdoor elec­tronic control P.C. board.
Not the problem of the inverter P.C. board.
Lighting
Replace the outdoor elec­tronic control P.C. board.
Turn ON power supply. Start operation.
Confi rm LED1 indication lamp on the outdoor electronic con-
trol P.C. board.
Blink 9 times
Replace the outdoor elec­tronic control P.C. board.
Turn OFF power supply before removing P.C. board.
Lighting Lighting
Normal.
Turn ON power supply. Start operation.
Confi rm LED1 indication lamp on the outdoor electronic con-
trol P.C. board.
Blink 9 times
Replace the power board.
51
Page 52
11-6. TEST POINT DIAGRAM AND VOLTAGE
1. Inverter P.C. board
MUZ-FD25VA MUZ-FD25VAH MUZ-FD35VA MUZ-FD35VAH
Back side of unit
AC 230 V
Fuse (F901) 250 V 3.15 A
Output to drive compressor (LDU, LDV, LDW)
Bus-bar voltage DB61 DC 260 - 300 V
(-)
(+)
Smoothing capacitor (C63)
Smoothing capacitor (C62)
Fuse (F801) 250 V 3.15 A
Smoothing capacitor (C61)
Fuse (F701) 250 V 3.15 A
Heater connector (CN722)
MUZ-FD•VAH
R.V.coil (CN721) 230 VAC
AC 230 V
Front side of unit
Fin temperature
thermistor /RT64
Output to drive outdoor
fan motor (CN932)
Defrost thermistor(RT61) Ambient temperature thermistor(RT65) Outdoor heat exchanger temperature thermistor(RT68)
100
90 80 70 60 50 40 30
Resistance(k )
20 10
0
-20 -10 0 10 20 30 40 Temperature( )
(CN642)
Ambient temperature
Outdoor heat exchanger
temperature thermistor
/RT68 (CN644)
Discharge temperature thermistor(RT62)
700
600
500
400
300
200
Resistance(k )
100
0
0 102030405060708090100110120
Defrost thermistor
/RT61(CN641)
thermistor /RT65
(CN643)
Temperature( )
Discharge temperature
thermistor /RT62
LEV connector (CN724)
(CN641)
Jumper wire for changing defrost setting (JS)
Fin temperature thermistor(RT64)
200 180 160 140 120
100
80 60
Resistance(k )
40 20
0
0 1020304050607080
Temperature( )
Jumper wire for pre-heat control setting (JK)
52
Page 53
2. Outdoor electronic control P.C. board
MUZ-FD50VA
Discharge temperature thermistor (RT62)
700 600 500 400 300 200
Resistance (k )
100
0
0 102030405060708090100110
Temperature (°C)
120
Fin temperature thermistor (RT64)
200 180 160 140 120 100
80
Resistance (k )
60 40 20
0
0 1020304050607080
Temperature (°C)
CN661
Defrost thermistor (RT61) Ambient temperature thermistor (RT65) Outdoor heat exchanger temperature thermistor (RT68)
100
90 80 70 60 50
Resistance (k )
40 30 20 10
0
-20-10 0 10203040
Temperature (°C)
LED 1
LED 2
SW1
CN932
20-90V AC
To fan
motor
5V DC
CN931
pulse wave
5V
GND
Discharge temperature
thermistor (RT62)
Defrost thermistor (RT61)
Ambient temperature
Outdoor heat exchanger
temperature thermistor (RT68)
CN663
CN701
Signal transmission
(To power board)
5V DC pulse wave
(–)
(+)
thermistor (RT65)
CN702
Signal reception
(From power board)
5V DC pulse wave
(–)
(+)
15V
GND
CN781
12 VDC
(+)
Rush current relay
15V
GND (power board)
(–)R.V. coil
(–)
LEV
(+)
CN795
12V DC
pulse wave
(–)
Bus-bar
voltage CN801
325 - 370
VDC
Input
F801
FUSE
250 V 3.15 A
53
CN601
230 VAC Input
CN681 High pressure switch
Serial signal 5 - 10 VDC
Page 54
3. Noise filter P.C. board
MUZ-FD50VA
CN901 To electronic control P.C. board
CN912 R.V. coil 230 VAC
230 VAC Output
CN902 To power board
CN903 To power board
230 VAC Input
CN61 230 VAC Output
4. Outdoor power board
MUZ-FD50VA
325-370 VDC Output
(+)
(–)
(Red)
1
3
(White)
F64 FUSE 250 V 2 A
NR64 VARISTOR
Connect to the compressor Voltage among phases: 5 to 180 V
Connect to the earth
CN2 Connect to the controller board (+)1-5(–): Signal transmission (To electronic control P.C. board) 5 VDC pulse wave (+)2-5(–): Zero cross signal 3-4 : Not used (+)6-5(–): 15 V (+)7-5(–): 15 V
CN3 Fin temperature thermistor RT64
Signal reception (From electronic control P.C. board) 5 VDC pulse wave
54
CN5 Primary current detection (Connect to the noise filter)
Page 55
12
DISASSEMBLY INSTRUCTIONS
<"Terminal with locking mechanism" Detaching points>
The terminal which has the locking mechanism can be detached as shown below. There are two types (refer to (1) and (2)) of the terminal with locking mechanism. The terminal without locking mechanism can be detached by pulling it out. Check the shape of the terminal before detaching.
(1) Slide the sleeve and check if there is a locking lever or not.
Sleeve
Slide the sleeve. Pull the terminal while
Locking lever
pushing the locking lever.
(2) The terminal with this connector has the locking mechanism.
Hold the sleeve, and pull out the terminal slowly.
Connector
12-1. MUZ-FD25VA MUZ-FD25VAH MUZ-FD35VA MUZ-FD35VAH
NOTE: Turn OFF power supply before disassembling.
OPERATING PROCEDURE PHOTOS
1. Removing the cabinet
(1) Remove the screw fixing the service panel. (Photo 2) (2) Pull down the service panel and remove it. (Photo 2) (3) Disconnect the power supply and indoor/outdoor con-
necting wire. (4) Remove the screws fixing the top panel. (Photo 1) (5) Remove the top panel. (Photo 1) (6) Remove the screws fixing the cabinet. (7) Remove the cabinet. (8) Remove the screws fixing the back panel. (9) Remove the back panel.
Photo 1
Screws of the top panel
Screws of the top panel
Photo 2
Screws of the cabinet
Screw of the cabinet
Back panel
Service
panel
Screw of the
service panel
Direction to
remove
55
Screws of the cabinet
Hooks
Page 56
OPERATING PROCEDURE
PHOTOS
2. Removing the inverter assembly, inverter P.C. board
(1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the lead wire to the reactor and the following con-
nectors:
<Inverter P.C. board>
CN721 (R.V. coil) CN722 (Defrost heater) CN932 (Fan motor) CN641 (Defrost thermistor and discharge temperature ther-
mistor) CN643 (Ambient temperature thermistor) CN644 (Outdoor heat exchanger temperature thermistor) CN724 (LEV)
(3) Remove the compressor connector (CN61). (4) Remove the screws fixing the relay panel. (Photo 3) (5) Remove the inverter assembly. (Photo 4) (6) Remove the screw of the earth wire and screw of the
T.B.support. (Photo 4) (7) Remove the relay panel from the inverter assembly. (8) Remove the inverter P.C. board from the relay panel.
3. Removing R.V. coil
(1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the following connectors: <Inverter P.C. board>
CN721 (R.V. coil)
(3) Remove the R.V. coil. (Photo 5)
Photo 3
Screws of the relay panel
Photo 4 (Inverter assembly)
Heat sink
Inverter P.C. board
Screw of the T.B.support
T.B.support
4. Removing the discharge temperature thermistor, defrost thermistor, outdoor heat exchanger tempera­ture thermistor and ambient temperature thermistor
(1) Remove the cabinet and panels. (Refer to 1.)
(2) Disconnect the lead wire to the reactor and the following con-
nectors: <Inverter P.C. board>
CN641 (Defrost thermistor and discharge temperature ther-
mistor) CN643 (Ambient temperature thermistor) CN644 (Outdoor heat exchanger temperature thermistor)
(3) Pull out the discharge temperature thermistor from its holder.
(Photo 5)
(4) Pull out the defrost thermistor from its holder. (Photo 6) (5) Pull out the outdoor heat exchanger temperature thermistor
from its holder. (Photo 6)
(6) Pull out the ambient temperature thermistor from its holder.
Relay panel
Photo 5
Screw of the
earth wire
R.V. coil
Discharge temperature thermistor
56
Page 57
OPERATING PROCEDURE
PHOTOS
5. Removing outdoor fan motor
(1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the following connectors: <Inverter P.C. board>
CN932 (Fan motor) (3) Remove the propeller nut. (See Photo 7) (4) Remove the propeller. (See Photo 7) (5) Remove the screws fixing the fan motor. (See Photo 7) (6) Remove the fan motor.
6. Removing the compressor and 4-way valve
(1) Remove the cabinet and panels. (Refer to 1.) (2) Remove the inverter assembly. (Refer to 2.) (3) Recover gas from the refrigerant circuit.
NOTE: Recover gas from the pipes until the pressure
gauge shows 0 kg/cm2 (0 MPa). (4) Detach the welded part of the suction and the discharge pipe
connected with compressor. (5) Remove the nuts of compressor legs. (6) Remove the compressor. (7) Detach the welded part of pipes connected with 4-way valve.
(See Photo 8)
Photo 6
Photo 7
Outdoor heat exchanger tempera­ture thermistor
Defrost thermistor
Screws of the outdoor fan motor
57
Propeller
Photo 8
Propeller nut
Welded parts of 4-way valve
Page 58
12-2. MUZ-FD50VA
NOTE: Turn OFF power supply before disassembling.
OPERATING PROCEDURE
1. Removing the cabinet
(1) Remove the screws of the service panel. (2) Remove the screws of the top panel. (3) Remove the screw of the valve cover. (4) Remove the service panel. (5) Remove the top panel. (6) Remove the valve cover. (7) Disconnect the power supply and indoor/outdoor connect-
ing wire. (8) Remove the screws of the cabinet. (9) Remove the cabinet. (10)
Remove the screws of the back panel.
(11)
Remove the back panel.
Photo 1
Screw of the top panel
Screws of the back panel
Photo 2
Screw of the top panel
PHOTOS
Screws of the cabinet
Screws of the cabinet
Screws of the cabinet
Screw of the service panel
Screw of the valve cover
Screws of the back panel
58
Page 59
OPERATING PROCEDURE PHOTOS
2. Removing the inverter assembly, outdoor electric control P.C. board, power board, noise filter P.C. board and reactor.
(1) Remove the top panel, cabinet and service panel. (Refer to
1.) (2) Remove the back panel. (Refer to 1.) (3) Disconnect the following connectors:
<Electronic control P.C. board> CN931 and CN932 (Fan motor) CN795 (LEV) CN661 (Discharge temperature thermistor, defrost thermis-
tor and outdoor heat exchanger temperature ther-
mistor) CN663 (Ambient temperature thermistor) <Noise filter P.C. board> CN912 (R.V. coil)
(4) Remove the compressor connector. (5) Remove the screws fixing the relay panel. (6) Remove the inverter assembly. (7) Disconnect all connectors and lead wires on the electronic
control P.C. board.
(8) Remove the outdoor electronic control P.C. board from the
inverter assembly.
(9) Disconnect the reactor lead wire. (
10
) Remove the screws of the reactor, and remove the reactor.
(11)
Remove the screws fixing the power board assembly.
(12)
Disconnect all connectors and lead wires on the power
board.
(13)
Remove the power board from the inverter assembly.
(14)
Disconnect all connectors and lead wires on the noise filter
P.C. board.
(15)
Remove the noise filter P.C. board from the inverter assem-
bly.
Photo 3 (Inverter assembly)
Screws of the power board assembly
Screws of the relay panel
Photo 4
59
Screws of the reactor
Page 60
OPERATING PROCEDURE PHOTOS
3. Removing the defrost thermistor, discharge tempera­ture thermistor, outdoor heat exchanger temperature thermistor and ambient temperature thermistor
(1) Remove the top panel, cabinet and service panel. (Refer to
1.) (2) Remove the back panel. (Refer to 1.) (3) Disconnect the following connectors:
<Electronic control P.C. board> CN661 (Discharge temperature thermistor, defrost thermis-
tor and outdoor heat exchanger temperature ther­mistor)
CN663 (Ambient temperature thermistor) (4) Pull out the defrost thermistor from its holder. (5) Pull out the discharge temperature thermistor from its hold-
er. (Photo 7) (6) Pull out the outdoor heat exchanger temperature thermistor
from its holder. (7) Pull out the ambient temperature thermistor from its holder.
Photo 5
Outdoor heat
exchanger tempera­ture thermistor
Defrost thermistor
Ambient tem­perature thermistor
4. Removing outdoor fan motor
(1) Remove the top panel, cabinet and service panel. (Refer to
1.)
(2) Disconnect the following connectors:
<Electronic control P.C. board>
CN931 and CN932 (Fan motor)
(3) Remove the propeller. (4) Remove the screws fixing the fan motor. (5) Remove the fan motor.
Photo 6
Screws of the outdoor fan motor
60
Page 61
OPERATING PROCEDURE PHOTOS
5. Removing the compressor and 4-way valve
(1) Remove the top panel, cabinet and service panel. (Refer to
1.) (2) Remove the back panel. (Refer to 1.) (3) Remove the inverter assembly. (Refer to 2.) (4) Recover gas from the refrigerant circuit.
NOTE: Recover gas from the pipes until the pressure gauge
shows 0 MPa.
(5) Detach the welded part of the suction and the discharge
pipe connected with compressor.
(6) Remove the compressor nuts.
(7) Remove the compressor.
(8) Detach the welded part of 4-way valve and pipe.
6. Removing R.V. coil
(1) Remove the top panel, cabinet and service panel. (Refer to
1.)
(2) Remove the back panel. (Refer to 1.) (3) Disconnect the following connectors:
<Noise filter P.C. board> CN912 (R.V. coil)
(4) Remove the R.V. coil.
Photo 7
Welded part of the discharge pipe
Photo 8
Discharge temperature thermistor
Welded part of the suction pipe
Welded parts of 4-way valve
R.V. coil
61
Page 62
62
Page 63
63
Page 64
HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
© Copyright 2007 MITSUBISHI ELECTRIC CO.,LTD
Distributed in Nov. 2008. No. OBH489 REVISED EDITION-B 5 Distributed in Oct. 2007. No. OBH489 REVISED EDITION-A 6 Distributed in Aug. 2007. No. OBH489 6 Made in Japan
New publication, effective Nov. 2008 Specifications subject to change without notice.
Loading...