Mitsubishi MUZ-A09NA- 1, MUZ-A15NA, MUZ-A12NA- U1, MUZ-A09NA- U1, MUZ-A15NA- U1 Service Manual

...
SERVICE MANUAL
CONTENTS
1. TECHNICAL CHANGES ··································· 3
2. PART NAMES AND FUNCTIONS ····················· 6
3. SPECIFICATION ················································ 7
4. OUTLINES AND DIMENSIONS ·······················11
5. WIRING DIAGRAM ·········································· 12
7. DATA ································································ 23
8. ACTUATOR CONTROL ··································· 37
9. SERVICE FUNCTIONS ··································· 38
10. TROUBLESHOOTING ····································· 38
11. DISASSEMBLY INSTRUCTIONS ···················· 65
12. PARTS LIST ····················································· 72 12-1. PARTS LIST ··········································· 72 12-2. RoHS PARTS LIST ································ 78
13. OPTIONAL PARTS ······················ BACK COVER
Models
MUZ-A09NA,-
1
,-
U1
,-
U2
MUZ-A12NA,-
U1
MUZ-A15NA,-
U1
MUZ-A17NA,-
U1
MUZ-A24NA,-
1
,-
U1
,-
U2
MUY-A15NA MUY-A17NA MUY-A24NA
,-
1
,-
U1
,-
U2
MUZ-GA24NA,-
U1
MUY-GA24NA
SPLIT-TYPE AIR CONDITIONERS
OUTDOOR UNIT
Indoor unit service manual
MSZ-A•NA Series (OB450)
MSZ-GA•NA Series (OB450)
MUZ-A09/12/15/17NA MUY-A15/17NA
NOTE:
RoHS compliant products have <G> mark on the spec name plate. For servicing of RoHS compliant products, refer to the PARTS LIST (RoHS compliant).
TM
HFC
utilized
R410A
No. OB451
REVISED EDITION-E
Revision E:
• MUZ-GA24NA and MUY-GA24NA have been added.
Please void OB451 REVISED EDITION-D.
2
Revision A:
• MUZ-A09NA -U2 and MUZ-A09NA -1 have been added.
Revision B:
• 10-5. ”Check of outdoor thermistors” has been corrected.
Revision C:
• 10-6. ”Test point diagram and voltage” has been corrected. 10-6.3. ”Outdoor electronic control P.C. board”, the chart of thermistor has been corrected.
Revision D:
• MUZ-A24NA - 1, MUZ-A24NA - U2 and MUY-A24NA -
1
have been added.
Revision E:
• MUZ-GA24NA and MUY-GA24NA have been added.
3
MUZ09UN MUZ-A09NA MUZ12UN MUZ-A12NA MUH15TN MUZ-A15NA MUH17TN MUZ-A17NA MUH24WN MUZ-A24NA MU15TN MUY-A15NA MU17TN → MUY-A17NA MU24WN MUY-A24NA
1. Outdoor unit model has been changed.
2. Control method between indoor and outdoor unit has been changed.
3. Refrigerant has been changed. (R22 R410A)
4. Fan motor has been changed. (AC DC)
5. Compressor has been changed. (AC DC)
MUZ-A09NA MUZ-A09NA -
1
MUZ-A09NA - U1 MUZ-A09NA -
U2
1. Refrigerant system diagram has been changed.
MUZ-A24NA MUZ-A24NA -
1
MUZ-A24NA - U1 MUZ-A24NA -
U2
MUY-A24NA MUY-A24NA -
1
1. Wiring diagram has been changed.
MUZ-A24NA - 1 MUZ-GA24NA MUZ-A24NA - U2 MUZ-GA24NA -
U1
MUY-A24NA - 1 MUY-GA24NA
1. Compressor has been changed. (SNB130FPDH SNB130FQBH)
2. Wiring diagram has been changed.
3. Fan motor has been changed.
4. ELECTRONIC CONTROL P.C. Board has been changed.
1
TECHNICAL CHANGES
4
INFORMATION FOR THE AIR CONDITIONER WITH R410A REFRIGERANT
• This room air conditioner adopts HFC refrigerant (R410A) which never destroys the ozone layer.
• Pay particular attention to the following points, though the basic installation procedure is same as that for R22 air condition­ers.
As R410A has working pressure approximate 1.6 times as high as that of R22, some special tools and piping parts/materials
are required. Refer to the table below.
Take sufficient care not to allow water and other contaminations to enter the R410A refrigerant during storage and installa-
tion, since it is more susceptible to contaminations than R22.
For refrigerant piping, use clean, pressure-proof parts/materials specifically designed for R410A. (Refer to 2. Refrigerant pip-
ing.)
Composition change may occur in R410A since it is a mixed refrigerant. When charging, charge liquid refrigerant to prevent
composition change.
New refrigerant Previous refrigerant
Refrigerant
Refrigerant R410A R22 Composition (Ratio) HFC-32: HFC-125 (50%: 50%) R22 (100%) Refrigerant handling Pseudo-azeotropic refrigerant Single refrigerant Chlorine Not included Included Safety group (ASHRAE) A1 / A1 A1 Molecular weight 72.6 86.5 Boiling point (°F) -60.5 -41.4 Steam pressure [77°F] (PSIG) 225.82 136.34 Saturated steam density [77°F] (lb./ft.
3
) 3.995 2.772 Combustibility Non combustible Non combustible ODP
1 0 0.055 GWP 2 1730 1700 Refrigerant charge method From liquid phase in cylinder Gas phase Additional charge on leakage Possible Possible
Refrigeration oil
Kind Incompatible oil Compatible oil Color None Light yellow Smell None None
1: Ozone Depletion Potential: based on CFC-11 2: Global Warming Potential: based on CO2
New Specification Current Specification
Compressor
The incompatible refrigeration oil easily separates from refrigerant and is in the upper layer inside the suction muffl er. Raising position of the oil back hole enables to back the refrigeration oil of the upper layer to flow back to the compressor.
Since refrigerant and refrigeration oil are compatible with each other, refrigeration oil goes back to the compressor through the lower position oil back hole.
Compressor
Suction muffler
Oil back hole
refrigeration oil
Refrigerant
Compressor
Suction muffler
Oil back hole
Refrigeration oil /Refrigerant
5
-22 -4 14 32 50 68
86
104 122 140
-73
0
73
145
218
290
363
435
508
580
(PSIG)
R410A
R22
Conversion chart of refrigerant temperature and pressure
Saturated liquid pressure
(°F)
1. Tools dedicated for the air conditioner with R410A refrigerant
The following tools are required for R410A refrigerant. Some R22 tools can be substituted for R410A tools.
R410A tools
Can R22 tools
be used?
Description
Gauge manifold No
R410A has high pressures beyond the measurement range of existing gaug­es.
Charge hose No Hose material have been changed to improve the pressure resistance.
Gas leak detector No Dedicated for HFC refrigerant.
Torque wrench
Yes 1/4 in. and 3/8 in.
No 1/2 in. and 5/8 in.
Flare tool Yes Clamp bar hole has been enlarged to reinforce the spring strength in the tool.
Flare gauge New Provided for flaring work (to be used with R22 flare tool).
Vacuum pump adapter
New
Provided to prevent the back flow of oil. This adapter enables you to use vac­uum pumps.
Electronic scale for refrigerant charging
New
It is difficult to measure R410A with a charging cylinder because the refriger­ant bubbles due to high pressure and high-speed vaporization
No: Not Substitutable for R410A Yes: Substitutable for R410A
2. Refrigerant piping
Specifications
Use the copper or copper-alloy seamless pipes for refrigerant that meet the following specifications.
Outside diameter (in.) Wall thickness (in.) Insulation material
1/4 0.0315
Heat resisting foam plastic Specific gravity 0.045 Thickness 0.315 in.
3/8 0.0315
1/2 0.0315
5/8 0.0394
Flaring work and flare nut Flaring work for R410A pipe differs from that for R22 pipe. For details of flaring work, refer to Installation manual “FLARING WORK”.
Pipe diameter (in.)
Dimension of flare nut mm (in.)
R410A R22
1/4 17 (11/16) 17 (11/16)
3/8 22 (7/8) 22 (7/8)
1/2 26 (1-1/32) 24 (15/16)
5/8 29 (1-5/32) 27 (1-1/16)
6
3. Refrigerant oil
Apply the special refrigeration oil (accessories: packed with indoor unit) to the flare and the union seat surfaces.
4. Air purge
• Do not discharge the refrigerant into the atmosphere. Take care not to discharge refrigerant into the atmosphere during installation, reinstallation, or repairs to the refrigerant cir-
cuit.
• Use the vacuum pump for air purging for the purpose of environmental protection.
5. Additional charge
For additional charging, charge the refrigerant from liquid phase of the gas cylinder. If the refrigerant is charged from the gas phase, composition change may occur in the refrigerant inside the cylinder and the outdoor unit. In this case, capacity of the refrigeration cycle decreases or normal operation can be impossible. However, charging the liquid refrigerant all at once may cause the compressor to be locked. Thus, charge the refrigerant slowly.
Electronic scale for refrigerant charging
Outdoor unit
Refrigerant gas cylinder operating valve
Refrigerant gas cylinder for R410A with siphon
Refrigerant (liquid)
Service port
Gauge manifold valve (for R410A)
Union
Liquid pipe
Gas pipe
Stop valve
Indoor unit
Charge hose (for R410A)
PART NAMES AND FUNCTIONS
2
Air outlet
Drain outlet
Piping
Drain hose
Air inlet
(back and side)
MUZ-A09NA MUZ-A15NA MUY-A15NA MUZ-A12NA MUZ-A17NA MUY-A17NA
MUZ-A24NA MUY-A24NA MUZ-GA24NA MUY-GA24NA
Piping
Air outlet
Drain hose
Drain outlet
Air inlet
(back and side)
7
Item Model MSZ-A09NA MSZ-A12NA
Capacity Rated (Minimum-Maximum)
Cooling
1 Btu/h 9,000 (5,500-9,000) 12,000 (5,700-12,000)
Heating 47 1 Btu/h 10,900 (5,200-12,600) 13,600 (5,200-13,600)
Capacity Heating 17 2 Btu/h 7,700 8,300
Power consumption Rated (Minimum-Maximum)
Cooling 1 W 690 (390-690) 1,170 (395-1,170) Heating 47 1 W 860 (350-1,100) 1,160 (350-1,160)
Power consumption Heating 17
2 W 880 930 EER 1 [SEER] 3 Cooling 13.0 [17.0] 10.3 [17.0] HSPF IV(V) 4 Heating 8.2 (7.1) 8.2 (7.1) COP Heating 1 3.71 3.44
Outdoor unit model
MUZ-A09NA
MUZ-A09NA -
U1
MUZ-A09NA -
1
MUZ-A09NA - U2
MUZ-A12NA
Power supply V , phase , Hz 208/230, 1, 60 Max. fuse size (time delay) A 15 Min. circuit ampacity A 12 Fan motor F.L.A 0.52
Compressor
Model KNB092FPAH Winding resistance (at 68˚F) Ω
0.49 R.L.A 7.8 L.R.A 9.2
Refrigerant control Liner expansion valve Sound level 1 dB(A) 48 Defrost method Reverse cycle
Dimensions
W in. 31-1/2 D in. 11-1/4 H in. 21-5/8
Weight Ib. 82 75 82 External fi nish Munsell 3Y 7.8/1.1 Remote controller Wireless type Control voltage (by built-in transformer) 12 - 24 VDC Refrigerant piping Not supplied
Refrigerant pipe size (Min. wall thickness)
Liquid in. 1/4 (0.0315) Gas in. 3/8 (0.0315)
Connection method
Indoor Flared Outdoor Flared
Between the indoor & outdoor units
Height difference
ft. 40
Piping length ft. 65
Refrigerant charge (R410A) 2 lb. 5 oz. 2 lb. 2 lb. 5 oz. Refrigeration oil (Model) NEO22
NOTE: Test conditions are based on ARI 210/240.
1: Rating conditions (Cooling) — Indoor: 80˚FDB, 67˚FWB, Outdoor: 95˚FDB, (75˚FWB) Rated frequency (Heating) — Indoor: 70˚FDB, 60˚FWB, Outdoor: 47˚FDB, 43˚FWB Rated frequency 2: (Heating) — Indoor: 70˚FDB, 60˚FWB, Outdoor: 17˚FDB, 15˚FWB Maximum frequency
3
SPECIFICATION
8
Item Model MSZ-A15NA MSY-A15NA MSZ-A17NA MSY-A17NA
Capacity Rated (Minimum-Maximum)
Cooling 1 Btu/h
15,000
(3,100-15,000)
15,000
(3,100-15,000)
16,200
(3,100-16,200)
16,200
(3,100-16,200)
Heating 47
1 Btu/h
18,000
(3,400-20,900)
20,100
(3,400-20,900)
Capacity Rated Heating 17 2 Btu/h 13,000 13,000
Power consumption Rated (Minimum-Maximum)
Cooling 1 W 1,690 (210-1,690) 1,690 (210-1,690) 2,070 (210-2,070) 2,070 (210-2,070) Heating 47
1 W 1,790 (250-2,330) – 2,150 (250-2,330) –
Power consumption Rated
Heating 17 2 W 1,740 1,740
EER
1 [SEER] 3 Cooling 8.9 [16.0] 8.9 [16.0] 7.8 [16.0] 7.8 [16.0] HSPF IV(V) 4 Heating 8.2 (7.1) 8.2 (7.1) – COP Heating 1 2.95 – 2.74 – Outdoor unit model MUZ-A15NA MUY-A15NA MUZ-A17NA MUY-A17NA Power supply V , phase , Hz 208/230, 1, 60 Max. fuse size (time delay) A 15 Min. circuit ampacity A 14 Fan motor F.L.A 0.52
Compressor
Model SNB130FPDH Winding resistance (at 68˚F) Ω
0.45 R.L.A 10.1 L.R.A 12
Refrigerant control Liner expansion valve Sound level 1 dB(A) 50 50 52 52 Defrost method 51 53
Dimensions
W in. 31-1/2 D in. 11-1/4 H in. 21-5/8
Weight Ib. 88 External fi nish Munsell 3Y 7.8/1.1 Remote controller Wireless type Control voltage (by built-in transformer) 12 - 24 VDC Refrigerant piping Not supplied
Refrigerant pipe size (Min. wall thickness)
Liquid in. 1/4 (0.0315) Gas in. 1/2 (0.0315)
Connection method
Indoor Flared Outdoor Flared
Between the indoor & outdoor units
Height difference ft. 40 Piping length ft. 65
Refrigerant charge (R410A) 2 lb. 7 oz. Refrigeration oil (Model) NEO22
NOTE: Test conditions are based on ARI 210/240.
1: Rating conditions (Cooling) — Indoor: 80˚FDB, 67˚FWB, Outdoor: 95˚FDB, (75˚FWB) Rated frequency (Heating) — Indoor: 70˚FDB, 60˚FWB, Outdoor: 47˚FDB, 43˚FWB Rated frequency 2: (Heating) — Indoor: 70˚FDB, 60˚FWB, Outdoor: 17˚FDB, 15˚FWB Maximum frequency
9
Item Model MSZ-A24NA MSY-A24NA MSZ-GA24NA MSY-GA24NA
Capacity Rated Minimum-Maximum)
Cooling 1 Btu/h
22,000
(4,400-22,000)
22,000
(4,400-22,000)
22,000
(4,400-22,000)
22,000
(4,400-22,000)
Heating 47
1 Btu/h
23,200
(3,600-24,400)
23,200
(3,600-24,400)
Capacity Rated Heating 17
2 Btu/h 15,200 — 15,200 —
Power consumption Rated (Minimum-Maximum)
Cooling
1 W 2,880 (290-2,880) 2,880 (290-2,880) 2,500 (270-2,500) 2,500 (270-2,500)
Heating 47 1 W 2,350 (260-2,570) 2,140 (250-2,520)
Power consumption Rated
Heating 17 2 W 1,960 1,870
EER
1 [SEER] 3 Cooling 7.6 [16.0] 7.6 [16.0] 8.8 [17.5] 8.8 [17.5] HSPF IV(V) 4 Heating 8.2 (7.1) 9.5 (7.1) — COP Heating 1 2.89 — 3.17 — Outdoor unit model MUZ-A24NA MUY-A24NA MUZ-GA24NA MUY-GA24NA Power supply V , phase , Hz 208/230, 1, 60 Max. fuse size (time delay) A 20 Min. circuit ampacity A 17 Fan motor F.L.A 0.93
Compressor
Model SNB130FPDH SNB130FQBH Winding resistance (at 68˚F) Ω
0.45 0.98 R.L.A 10.1 12.8 L.R.A 16.0 16.0
Refrigerant control Liner expansion valve Sound level 1 dB(A) 55 Defrost method Reverse cycle
Dimensions
W in. 33-1/16 D in. 13 H in. 33-7/16
Weight Ib. 128 117 External fi nish Munsell 3Y 7.8 1.1 Remote controller Wireless type Control voltage (by built-in transformer) 12 - 24 VDC Refrigerant piping Not supplied
Refrigerant pipe size (Min. wall thickness)
Liquid in. 1/4 (0.0315) Gas in. 5/8 (0.0394)
Connection method
Indoor Flared Outdoor Flared
Between the indoor & outdoor units
Height difference ft. 50 Piping length ft. 100
Refrigerant charge (R410A) 4 lb. Refrigeration oil (Model) NEO22
NOTE: Test conditions are based on ARI 210/240.
1: Rating conditions (Cooling) — Indoor: 80˚FDB, 67˚FWB, Outdoor: 95˚FDB, (75˚FWB) Rated frequency (Heating) — Indoor: 70˚FDB, 60˚FWB, Outdoor: 47˚FDB, 43˚FWB Rated frequency 2: (Heating) — Indoor: 70˚FDB, 60˚FWB, Outdoor: 17˚FDB, 15˚FWB Maximum frequency
10
Test condition
3, 4
Mode Test
Indoor air condition (˚F) Outdoor air condition (˚F)
Dry bulb Wet bulb Dry bulb Wet bulb
ARI
SEER
(Cooling)
"A" Cooling Steady State at rated compres­sor Speed
80 67 95 (75)
"B-2" Cooling Steady State at rated com­pressor Speed
80 67 82 (65)
"B-1" Cooling Steady State at minimum compressor Speed
80 67 82 (65)
Low ambient Cooling Steady State at mini­mum compressor Speed
80 67 67 (53.5)
Intermediate Cooling Steady State At Inter­mediate compressor Speed
5
80 67 87 (69)
HSPF
(Heating)
Standard Rating-Heating at rated compres­sor Speed
70 60 47 43
Low temperature Heating at rated compres­sor Speed
70 60 17 15
Max temperature Heating at minimum com­pressor Speed
70 60 62 56.5
High temperature Heating at minimum com­pressor Speed
70 60 47 43
Frost Accumulation at rated compressor Speed
70 60 35 33
Frost Accumulation at Intermediate com­pressor Speed 5
70 60 35 33
5: At Intermediate compressor Speed = ("Cooling rated compressor speed" - "minimum compressor speed") / 3 + "minimum
compressor speed".
OPERATING RANGE
(1) POWER SUPPLY
Rated voltage Guaranteed Voltage (V)
Outdoor unit
208/230 V
1 phase
60 Hz
Min.187
208 230 Max.253
(2) OPERATION
Mode Condition
Intake air temperature (°F)
Indoor Outdoor
DB WB DB WB
Cooling
Standard temperature 80 67 95 — Maximum temperature 90 73 115 — Minimum temperature 67 57 14 — Maximum humidity 78%
Heating
Standard temperature 70 60 47 43 Maximum temperature 80 67 75 65
Minimum temperature 70 60
14
5 (MUZ-GA24)
13
4 (MUZ-GA24)
Except -
U
model
11
30°
35°
6-1/28
3-17/32
7-25/32
1-9/16
20-9/32
11-25/32
2-19/32
2
14-3/16
33-7/16
16-15/16
19-11/16
3-3/16
4-25/32
33-1/16
Open as a rule 20 inch or more if the front and both sides are open
4 inch or more / 8 inch or more if there are obstacles to both sides
Open as a rule 20 inch or more if the back, both sides and top are open
14 in. or more
4 in. or more
Air in
Air out
13
Service panel
Gas refrigerant pipe joint Refrigerant pipe (flared) ø5/8
Liquid refrigerant pipe joint Refrigerant pipe (flared) ø1/4
Drain hole ø1-5/8
4-3/8 13/16 Oval hole
REQUIRED SPACE
Air in
Liquid pipe :1/4 (flared) Gas pipe :3/8 (flared) ··· MUZ-A09/12NA
:1/2 (flared) ··· MUZ-A15/17NA, MUY-A15/17NA
6-23/32
2
5-7/8
2-23/32
1-3/4
15-3/4
12 ~ 12-3/4
13-9/16
11/ 16
1-9/16
7/8
21-5/8
11-1/32
13/32
31-1/2
19-11/16
5-15/16
11-29/32
17/3229/32 11-1/4
Air in
handle
Air in
Air out
2- 3/8 13/16 Oval hole
Drain hole ø1-5/8
{
REQUIRED SPACE
Basically open 4 inch or more without any obstruction in front and on both sides of the unit.
14 in. or more
8 in. or more
4 in. or more
4 in. or more
Open two sides of left, right, or rear side.
Unit: inch
MUZ-A09NA MUZ-A12NA MUZ-A15NA MUZ-A17NA MUY-A15NA MUY-A17NA
MUZ-A24NA MUY-A24NA MUZ-GA24NA MUY-GA24NA
4
OUTLINES AND DIMENSIONS
12
MUZ-A09NA MUZ-A12NA MUZ-A15NA MUZ-A17NA
5 WIRING DIAGRAM
13
MUY-A15NA MUY-A17NA
14
MUZ-A24NA MUZ-A24NA-
U1
15
MUZ-A24NA-
1
MUZ-A24NA-
U2
16
MUY-A24NA
17
MUY-A24NA-
1
18
MUZ-GA24NA
19
MUY-GA24NA
20
Outdoor heat exchanger
Flared connection
Defrost thermistor RT61
Discharge temperature thermistor RT62
Service port
Service port
Flared connection
Stop valve (with strainer)
Stop valve (with service port)
Refrigerant flow in cooling
Compressor
4-way valve
Refrigerant flow in heating (MUZ)
Refrigerant pipe ø3/8 (MUZ-A09/12) ø1/2 (MUZ-A15/17,MUY-A15/17) (with heat insulator)
Refrigerant pipe ø1/4 (with heat insulator)
R.V. coil heating ON cooling OFF
Strainer #100
Capillary tube
O.D. 0.118 × I.D. 0.071 × 23-5/8 (ø
3.0
×
ø1.8
×
600
)
Expansion valve
Ambient temperature thermistor RT65
Muffler
Muffler
Muffler
Outdoor heat exchanger
Flared connection
Defrost thermistor RT61
Discharge temperature thermistor RT62
Flared connection
Stop valve (with strainer)
Stop valve (with service port)
Refrigerant flow in cooling
Compressor
4-way valve
Refrigerant flow in heating
Refrigerant pipe ø3/8 (with heat insulator)
Refrigerant pipe ø1/4 (with heat insulator)
Capillary tube O.D. 0.118 × I.D. 0.079 × 9-7/16 (ø3.0 × ø2.0 × 240)
Expansion valve
R.V. coil heating ON cooling OFF
Strainer #100
Muffler
Muffler
Ambient temperature thermistor RT65
Muffler
Unit: inch
MUZ-A09NA MUZ-A09NA-
U1
MUZ-A12NA MUZ-A15NA MUZ-A17NA
MUY-A15NA MUY-A17NA
MUZ-A09NA-
1
MUZ-A09NA-
U2
6
REFRIGERANT SYSTEM DIAGRAM
21
MUZ-A24NA MUZ-GA24NA
Outdoor heat exchanger
Flared connection
Defrost thermistor RT61
Service port
Service port
Discharge temperature thermistor RT62
Flared connection
Stop valve
Stop valve (with service port)
Capillary tube
Refrigerant flow in cooling
Compressor
4-way valve
Refrigerant flow in heating
Refrigerant pipe ø5/8 (with heat insulator)
Refrigerant pipe ø1/4 (with heat insulator)
LEV
R.V. coil heating ON cooling OFF
Muffler
#100
Strainer
#100
Receiver
Outdoor heat exchanger temperature thermistor RT68
Ambient temperature thermistor RT65
Strainer
#100
O.D. 0.142 × I.D. 0.094 × 1-31/32 (ø
3.6 × ø2.4 × 50
)
MUY-A24NA MUY-GA24NA
Outdoor heat exchanger
Flared connection
Discharge temperature thermistor RT62
Flared connection
Stop valve
Stop valve (with service port)
Capillary tube
Refrigerant flow in cooling
Compressor
Service port
Service port
4-way valve
Refrigerant pipe ø5/8 (with heat insulator)
Refrigerant pipe ø1/4 (with heat insulator)
LEV
Muffler
#100
Strainer
#100
Receiver
Outdoor heat exchanger temperature thermistor RT68
Ambient temperature thermistor RT65
Strainer
#100
O.D. 0.142 × I.D. 0.094 × 1-31/32 (ø
3.6 × ø2.4 × 50
)
Unit: inch
22
Max. Length A
Max. Height
difference
B
Indoor unit
Outdoor unit
MAX. REFRIGERANT PIPING LENGTH and MAX. HEIGHT DIFFERENCE
Model
Refrigerant piping: ft. Piping size O.D: in.
Max. Length
A
Max. Height difference
B
Gas Liquid
MUZ-A09NA MUZ-A12NA
65 40
3/8 1/4
MUZ-A15NA MUY-A15NA MUZ-A17NA MUY-A17NA
1/2 1/4
MUZ-A24NA
MUY-A24NA MUZ-GA24NA MUY-GA24NA
100 50 5/8 1/4
ADDITIONAL REFRIGERANT CHARGE (R410A: oz.)
Refrigerant piping exceeding 25 ft. requires additional refrigerant charge according to the calculation.
Model
Outdoor unit
precharged
Refrigerant piping length (one way): ft.
25 30 40 50 60 65
MUZ-A09NA MUZ-A09NA -
U1
MUZ-A12NA
2 lb. 5 oz.
0 1.62 4.86 8.10 11.34 12.96
MUZ-A09NA -
1
MUZ-A09NA -
U2
2 lb.
MUZ-A15NA MUY-A15NA MUZ-A17NA MUY-A17NA
2 lb. 7 oz.
Calculation: X oz. = 1.62/5 oz. / ft. × (Refrigerant piping length (ft.) - 25)
Model
Outdoor unit
precharged
Refrigerant piping length (one way): ft.
25 30 40 50 60 70 80 90 100
MUZ-A24NA MUY-A24NA MUZ-GA24NA MUY-GA24NA
4 lb. 0 1.08 3.24 5.40 7.56 9.72 11.88 14.04 16.20
Calculation: X oz. = 1.08/5 oz. / ft. × (Refrigerant piping length (ft.) - 25)
NOTE: Refrigerant piping exceeding 25 ft. requires additional refrigerant charge according to the calculation.
23
MUZ-A09NA MUZ-A12NA MUZ-A15NA MUZ-A17NA MUZ-A24NA MUZ-GA24NA MUY-A15NA MUY-A17NA MUY-A24NA MUY-GA24NA
7-1. PERFORMANCE DATA
1) COOLING CAPACITY
Model
Indoor air Outdoor intake air DB temperature (˚F)
IWB 75 85 95 105 115
(˚F) TC SHC TPC TC SHC TPC TC SHC TPC TC SHC TPC TC SHC TPC
MUZ-A09NA
MUZ-A09NA
-
U1
71 11.0 6.4 0.61 10.3 5.9 0.67 9.7 5.6 0.72 9.0 5.2 0.76 8.3 4.8 0.79 67 10.4 7.4 0.58 9.7 6.9 0.64 9.0 6.4 0.69 8.4 5.9 0.73 7.7 5.5 0.77 63 9.8 8.3 0.55 9.1 7.7 0.61 8.5 7.1 0.66 7.7 6.5 0.70 7.0 5.9 0.73
MUZ-A09NA
-
1
MUZ-A09NA
-
U2
71 11.0 6.4 0.61 10.3 5.9 0.67 9.7 5.6 0.72 9.0 5.2 0.76 8.3 4.8 0.79 67 10.4 7.4 0.58 9.7 6.9 0.64 9.0 6.4 0.69 8.4 5.9 0.73 7.7 5.5 0.77 63 9.8 8.3 0.55 9.1 7.7 0.61 8.5 7.1 0.66 7.7 6.5 0.70 7.0 5.9 0.73
MUZ-A12NA
71 14.7 8.5 1.04 13.7 7.9 1.14 12.9 7.4 1.23 12.0 6.9 1.29 11.0 6.4 1.35 67 13.9 9.9 0.98 13.0 9.2 1.08 12.0 8.5 1.17 11.2 7.9 1.24 10.3 7.3 1.30 63 13.1 11.0 0.94 12.1 10.2 1.04 11.3 9.5 1.12 10.3 8.7 1.19 9.4 7.9 1.24
MUY-A15NA MUZ-A15NA
71 18.4 9.5 1.50 17.2 8.9 1.65 16.1 8.3 1.77 15.0 7.8 1.87 13.8 7.1 1.94 67 17.4 11.3 1.42 16.2 10.5 1.56 15.0 9.8 1.69 14.0 9.1 1.79 12.8 8.3 1.88 63 16.4 12.8 1.35 15.2 11.9 1.50 14.1 11.0 1.61 12.8 10.0 1.72 11.7 9.2 1.79
MUY-A17NA MUZ-A17NA
71 19.8 10.3 1.84 18.5 9.6 2.02 17.4 9.0 2.17 16.2 8.4 2.29 14.9 7.7 2.38 67 18.8 12.2 1.74 17.5 11.4 1.91 16.2 10.5 2.07 15.1 9.8 2.19 13.9 9.0 2.30 63 17.7 13.8 1.66 16.4 12.8 1.83 15.2 11.9 1.98 13.9 10.8 2.11 12.6 9.9 2.19
MUY-A24NA MUZ-A24NA
71 27.0 13.4 2.56 25.2 12.5 2.81 23.7 11.7 3.02 22.0 10.9 3.18 20.2 10.1 3.31 67 25.5 16.1 2.42 23.8 15.0 2.66 22.0 13.9 2.88 20.5 12.9 3.05 18.8 11.9 3.20 63 24.0 18.3 2.30 22.2 17.0 2.55 20.7 15.8 2.75 18.8 14.4 2.94 17.2 13.1 3.05
MUY-GA24NA MUZ-GA24NA
71 27.0 13.4 2.23 25.2 12.5 2.44 23.7 11.7 2.63 22.0 10.9 2.76 20.2 10.1 2.88 67 25.5 16.1 2.10 23.8 15.0 2.31 22.0 13.9 2.50 20.5 12.9 2.65 18.8 11.9 2.78 63 24.0 18.3 2.00 22.2 17.0 2.21 20.7 15.8 2.39 18.8 14.4 2.55 17.2 13.1 2.65
NOTE: 1. IWB: Intake air wet-bulb temperature
TC: Total Capacity (×10
3
Btu/h)
SHC: Sensible Heat Capacity (×10
3
Btu/h)
TPC: Total Power Consumption (kW)
2. SHC is based on 80˚F of indoor Intake air DB temperature.
2) COOLING CAPACITY CORRECTIONS
Model
Refrigerant piping length (one way: ft.)
25 (std.) 40 65 100
MSZ-A09/12/15/17NA MSY-A15/17NA
1.0 0.954 0.878
MSZ-A24NA MSY-A24NA MSZ-GA24NA MSY-GA24NA
1.0 0.95 0.878 0.713
7 DATA
24
3) HEATING CAPACITY
Model
Indoor air Outdoor intake air WB temperature (˚F)
IDB5 152535434555
(˚F) TC TPC TC TPC TC TPC TC TPC TC TPC TC TPC TC TPC
MUZ-A09NA
MUZ-A09NA -
U1
75
——
6.3 0.64 7.9 0.75 9.4 0.84 10.6 0.88 11.0 0.89 12.4 0.93 70 6.7 0.62 8.2 0.74 9.6 0.82 10.9 0.86 11.2 0.88 12.7 0.91 65 6.9 0.59 8.6 0.71 10.0 0.80 11.2 0.84 11.6 0.85 13.0 0.89
MUZ-A09NA -
1
MUZ-A09NA -
U2
75
——
6.3 0.64 7.9 0.75 9.4 0.84 10.6 0.88 11.0 0.89 12.4 0.93 70 6.7 0.62 8.2 0.74 9.6 0.82 10.9 0.86 11.2 0.88 12.7 0.91 65 6.9 0.59 8.6 0.71 10.0 0.80 11.2 0.84 11.6 0.85 13.0 0.89
MUZ-A12NA
75
——
7.9 0.86 9.9 1.02 11.8 1.13 13.3 1.19 13.7 1.21 15.5 1.25 70 8.4 0.84 10.2 0.99 12.0 1.10 13.6 1.16 14.0 1.18 15.8 1.23 65 8.6 0.80 10.7 0.96 12.4 1.07 14.0 1.13 14.4 1.15 16.2 1.21
MUZ-A15NA
75
——
10.4 1.33 13.1 1.57 15.6 1.75 17.6 1.83 18.1 1.86 20.5 1.93 70 11.1 1.29 13.5 1.53 15.9 1.70 18.0 1.79 18.5 1.83 21.0 1.90 65 11.3 1.24 14.1 1.48 16.5 1.66 18.5 1.75 19.1 1.77 21.4 1.86
MUZ-A17NA
75
——
11.7 1.60 14.6 1.88 17.4 2.10 19.6 2.20 20.2 2.24 22.9 2.32 70 12.4 1.55 15.1 1.84 17.8 2.04 20.1 2.15 20.7 2.19 23.4 2.28 65 12.7 1.48 15.8 1.77 18.4 1.99 20.7 2.10 21.3 2.13 23.9 2.24
MUZ-A24NA
75
——
13.5 1.75 16.8 2.06 20.1 2.29 22.6 2.41 23.3 2.44 26.4 2.54 70 14.3 1.69 17.4 2.01 20.5 2.23 23.2 2.35 23.9 2.40 27.0 2.49 65 14.6 1.62 18.2 1.94 21.2 2.17 23.9 2.29 24.6 2.33 27.6 2.44
MUZ-GA24NA
75 10.2 1.26 13.5 1.59 16.8 1.87 20.1 2.09 22.6 2.19 23.3 2.23 26.4 2.31 70 11.0 1.21 14.3 1.54 17.4 1.83 20.5 2.03 23.2 2.14 23.9 2.18 27.0 2.27 65 11.6 1.16 14.6 1.48 18.2 1.77 21.2 1.98 23.9 2.09 24.6 2.12 27.6 2.23
NOTE: 1. IDB: Intake air dry-bulb temperature
TC: Total Capacity (×10
3
Btu/h)
TPC: Total Power Consumption (kW)
2. Above data is for heating operation without any frost.
How to operate with fixed operational frequency of the compressor.
1. Press the EMERGENCY OPERATION switch on the front of the indoor unit, and select either EMERGENCY COOL mode or EMERGENCY HEAT mode before starting to operate the air conditioner.
2. The compressor starts with operational frequency.
3. The fan speed of the indoor unit is High.
4. This operation continues for 30 minutes.
5. In order to release this operation, press the EMERGENCY OPERATION switch twice or once, or press any button on the remote controller.
25
7-2. PERFORMANCE CURVE
65 70 75
75 70 65
Total power consumption
(kW)
Total capacity
(10
3
Btu/h)
Outdoor intake air WB temperature (°F)
= 307 CFM
Airflow
12
14
10
8
9
11
13
15
7
1.0
15 25 35 45 55
0.8
0.6
0.7
0.9
Ind
oor intake air DB temperature (°F)
Indoor intak
e air DB temperature (°F)
65 70 75
75 70 65
20
12
8
16
22
18
10
14
Ind
oor
intake air DB temperature (°F)
= 318 CFM
Airflow
15 25 35 45 55
Outdoor intake air WB temperature (°F)
1.3
0.8
0.9
1.0
1.1
1.2
Indoor intak
e air
DB temperature
(°F)
Total power consumption
(kW)
Total capacity
(10
3
Btu/h)
Cooling
71 67 63
71 67 63
Outdoor intake air DB temperature (°F)
SHF at rating condition = 0.71
= 275 CFM
Airflow
6
8 7
9
10
11
12
0.9
65 75 85 95 105 115
0.7
0.6
0.8
Indoor intake air WB tempe
rat
ure (°F)
Indoor intake air WB temperature (°F)
0.5
0.4
Total power consumption
(kW)
Total capacity
(10
3
Btu/h)
71 67 63
71 67 63
24
22
20
18
12
16
14
2.5
2.3
2.1
1.9
1.7
1.5
Ind
oor intake air WB temperature (°F)
Indoor intake air WB temperature (°F)
SHF at rating condition = 0.65
= 342 CFM
Airflow
65 75 85 95 105 115
Outdoor intake air DB temperature (°F)
Total power consumption
(kW)
Total capacity
(10
3
Btu/h)
71
63
67
71
63
67
27
29
23
19
25
21
17
3.1
2.9
2.7
2.5
2.3
2.1
Indoor intake air WB temperature (°F)
Indoor intake air WB temperature (°F)
SHF at rating condition = 0.63
= 508 CFM
Airflow
65 75 85 95 105 115
Outdoor intake air DB temperature (°F)
Total power consumption
(kW)
Total capacity
(10
3
Btu/h)
71 67 63
71 67 63
15
13
9
11
1.4
1.3
1.2
1.1
1.0
0.9
Indoor
intak
e air WB temperat
ure
(°F)
Indoor intake air WB temperature (°F)
SHF at rating condition = 0.70
= 318 CFM
Airflow
65 75 85 95 105 115
Outdoor intake air DB temperature (°F)
Total power consumption
(kW)
Total capacity
(10
3
Btu/h)
71 67 63
71 67 63
22
18
10
14
2.2
2.0
1.8
1.6
1.4
1.2
Indoor intake air WB temperature (°F)
Indoor intake air WB temperature (°F)
SHF at rating condition = 0.65
= 342 CFM
Airflow
65 75 85 95 105 115
Outdoor intake air DB temperature (°F)
Total power consumption
(kW)
Total capacity
(10
3
Btu/h)
MUZ-A09NA MUZ-A09NA
-
U1
MUZ-A09NA MUZ-A09NA-
U1
MUZ-A12NA
MUZ-A15NA MUY-A15NA
MUZ-A17NA MUY-A17NA
MUZ-A24NA MUY-A24NA
Heating
MUZ-A12NA
MUZ-A09NA-
1
MUZ-A09NA-
U2
MUZ-A09NA-
1
MUZ-A09NA-
U2
71 67 63
71 67 63
Outdoor intake air DB temperature (°F)
SHF at rating condition = 0.71
= 275 CFM
Airflow
6
8 7
9
10
11
12
0.9
65 75 85 95 105 115
0.7
0.6
0.8
Indoor intake air
WB temperature (°F)
Indoor intake air WB temperature (°F
)
0.5
0.4
Total power consumption
(kW)
Total capacity
(10
3
Btu/h)
65 70 75
75 70 65
Total power consumption
(kW)
Total capacity
(10
3
Btu/h)
Outdoor intake air WB temperature (°F)
= 307 CFM
Airflow
12
14
10
8
9
11
13
15
7
1.0
15 25 35 45 55
0.8
0.6
0.7
0.9
Indoor intake air DB temperat
ure
(°F)
Indoor intake air DB temperature (°F)
71
63
67
71
63
67
27
29
23
19
25
21
17
2.9
2.7
2.5
2.3
2.1
1.7
Indoor intake air WB temperature (°F)
Indoor intake air WB tempe
rat
ure (°F)
SHF at rating condition = 0.63
= 508 CFM
Airflow
65 75 85 95 105 115
Outdoor intake air DB temperature (°F)
Total power consumption
(kW)
Total capacity
(10
3
Btu/h)
MUZ-GA24NA MUY-GA24NA
26
65 70 75
75 70 65
Outdoor intake air WB temperature (°F)
Airflow= 381 CFM
18
22
24
14
10
1.8
1.9
1.7
15 25 35 45 55
1.5
1.3
1.4
1.6
Indoor intake air DB temperat
ure
(°F)
Indoor intake air DB temperature (°F
)
Total power consumption
(kW)
Total capacity
(×10
3
Btu/h)
65 70 75
75 70 65
24
20
12
16
Indoor intak
e air DB temperat
ure (°F)
= 381 CFM
Airflow
15 25 35 45 55
Outdoor intake air WB temperature (°F)
2.4
1.4
1.6
1.8
2.0
2.2
Indoor intake air DB temperature (°F)
Total power consumption
(kW)
Total capacity
(10
3
Btu/h)
65 70 75
75 70 65
28
26
24
22
16
14
20
18
2.6
1.6
Indoor intake air DB
temperature (°F
)
= 568 CFM
Airflow
15 25 35 45 55
Outdoor intake air WB temperature (°F)
1.8
2.0
2.2
2.4
Indoor intake air DB temperature (°F)
Total power consumption
(kW)
Total capacity
(10
3
Btu/h)
MUZ-A15NA
MUZ-A17NA
MUZ-A24NA
10
12
14
16
18
20
22
24
26
28
30
32
65 70 75
75 70 65
= 568 CFM
Airflow
15525354555
Outdoor intake air WB temperature (°F)
Indoor intake air DB temperature (°F)
Total power consumption
(kW)
Total capacity
(10
3
Btu/h)
1.0
1.2
1.4
1.6
1.8
2.0
2.2
2.4
Indoor intake air DB temperat
ure
(°F)
MUZ-GA24NA
This value of frequency is not the same as the actual frequency in operating. Refer to 7-5 and 7-6 for the relationships between frequency and capacity.
Data is based on the condition of indoor humidity 50%. Air flow should be set to High speed.
7-3. Condensing pressure
Cooling
68 70 75 80 85 90 95 100 105
(°F)
110
115
120
125
130
135
140
145
150
155
160
165
170
(PSIG)
Condensing pressure
86 80 75 70
Suction pressure
Outdoor ambient temperature
Indoor DB temperature (°F)
(PSIG)
86
80
75
70
68 70 75 80 85 90 95 100 105
(°F)
260
280
300
320
340
360
380
400
420
Indoor DB temperature (°F)
Outdoor ambient temperature
MUZ-A09NA MUZ-A09NA-