13. PARTS LIST······················································38
NOTE:
This service manual describes technical data of the outdoor units.
•As for indoor units MSZ-A09YV-and MSZ-A12YV-, refer to the service manual OB327.
•As for indoor unit MCFZ-A12WV-, refer to the service manual OB344.
E1
E1E1
Page 2
Refrigerating
oil
Refrigerant
New refrigerant
R410A
HFC-32: HFC-125 (50%:50%)
Pseudo-azeotropic refrigerant
Not included
A1/A1
72.6
-51.4
1.557
64
Non combustible
0
1730
From liquid phase in cylinder
Possible
Incompatible oil
Non
Non
Previous refrigerant
R22
R22 (100%)
Single refrigerant
Included
A1
86.5
-40.8
0.94
44.4
Non combustible
0.055
1700
Gas phase
Possible
Compatible oil
Light yellow
Non
Refrigerant
Composition (Ratio)
Refrigerant handling
Chlorine
Safety group (ASHRAE)
Molecular weight
Boiling point (:)
Steam pressure [25:](Mpa)
Saturated steam density [25:](Kg/K)
Combustibility
ODP w1
GWP w2
Refrigerant charge method
Additional charge on leakage
Kind
Color
Smell
w1:Ozone Destruction Parameter : based on CFC-11
w2 :Global Warmth Parameter : based on CO
2
New SpecificationCurrent Specification
The incompatible refrigerating oil easily separates from
refrigerant and is in the upper layer inside the suction muffler.
Raising position of the oil back hole enables to back the
refrigerating oil of the upper layer to flow back to the
compressor.
Since refrigerant and refrigerating oil are compatible each,
refrigerating oil backs to the compressor through the lower
position oil back hole.
Compressor
Suction muffler
Oil back hole
Refrigerating oil
Refrigerant
Compressor
Suction muffler
Oil back hole
Refrigerating oil /Refrigerant
Compressor
Revision A:
•MUZ-A12YV-and MUZ-A12YVH-can be connected to MCFZ-A12WV-.
•Some mistakes were corrected.
E1E1E1
1
TECHNICAL CHANGES
INFORMATION FOR THE AIR CONDITIONER WITH R410A REFRIGERANT
• This room air conditioner adopts an HFC refrigerant (R410A) which never destroys the ozone layer.
• Pay particular attention to the following points, though the basic installation procedure is same as that for R22 air
conditioners.
1 As R410A has working pressure approximate 1.6 times as high as that of R22, some special tools and piping parts/
materials are required. Refer to the table below.
2 Take sufficient care not to allow water and other contaminations to enter the R410Arefrigerant during storage and
installation, since it is more susceptible to contaminations than R22.
3 For refrigerant piping, use clean, pressure-proof parts/materials specifically designed for R410A. (Refer to 2. Refrigerant
piping.)
4 Composition change may occur in R410A since it is a mixed refrigerant. When charging, charge liquid refrigerant to prevent
composition change.
NOTE : The unit of pressure has been changed to MPa on the international system of units(SI unit system).
The conversion factor is: 1(MPa [Gauge]) =10.2(kgf/ff[Gauge])
2
Page 3
Conversion chart of refrigerant temperature and pressure
R410A toolsCan R22 tools be used?
Gas leak detector
R410A has high pressures beyond the measurement range of existing
gauges. Port diameters have been changed to prevent any other refrigerant
from being charged into the unit.
Hose material and cap size have been changed to improve the pressure
resistance.
Dedicated for HFC refrigerant.
6.35 mm and 9.52 mm
Description
Clamp bar hole has been enlarged to reinforce the spring strength in the tool.
Provided for flaring work (to be used with R22 flare tool).
Provided to prevent the back flow of oil. This adapter enables you to use
vacuum pumps.
It is difficult to measure R410A with a charging cylinder because the
refrigerant bubbles due to high pressure and high-speed vaporization
No
No
No
Yes
Yes
New
New
New
Gauge manifold
Charge hose
Torque wrench
Flare tool
Flare gauge
Vacuum pump
adapter
Electronic scale for
refrigerant charging
No : Not Substitutable for R410A Yes : Substitutable for R410A
No12.7 mm
Wall
thickness
Outside diameter
Pipe
mm
For liquid
For gas
6.35
9.52
12.7
0.8 mm
0.8 mm
0.8 mm
Heat resisting foam plastic
Specific gravity 0.045 Thickness 8 mm
Insulation material
(MPa [Gauge])
4.0
3.5
3.0
2.5
2.0
1.5
R410A
R22
NOTE : The unit of pressure has been changed to MPa on the
international system of units(SI unit system).
1.0
0.5
Saturated liquid pressure
0.0
-0.5
-30 -20 -1001020
30
405060
The conversion factor is: 1(MPa [Gauge]) =10.2(kgf/ff[Gauge])
(:)
1.Tools dedicated for the air conditioner with R410A refrigerant
The following tools are required for R410A refrigerant. Some R22 tools can be substituted for R410A tools.
The diameter of the service port on the stop valve in outdoor unit has been changed to prevent any other refrigerant being
charged into the unit. Cap size has been changed from 7/16 UNF with 20 threads to 1/2 UNF with 20 threads.
2.Refrigerant piping
1 Specifications
Use the refrigerant pipes that meet the following specifications.
• Use a copper pipe or a copper-alloy seamless pipe with a thickness of 0.8 mm. Never use any pipe with a thickness less
than 0.8mm, as the pressure resistance is insufficient.
3
Page 4
Electronic scale for refrigerant charging
Outdoor unit
Refrigerant gas
cylinder
operating valve
Refrigerant gas cylinder
for R410A with siphon
Refrigerant (liquid)
Service port
Gauge manifold
valve (for R410A)
Union
Liquid pipe
Gas pipe
Stop valve
Indoor unit
Charge hose (for R410A)
R410A
Pipe diameter
mm
6.35
9.52
12.7
17
22
26
Dimension of flare nut
R22
17
22
24
2 Flaring work and flare nut
Flaring work for R410A pipe differs from that for R22 pipe.
For details of flaring work, refer to Installation manual “FLARING WORK”.
3.Refrigerant oil
Apply the special refrigeration oil (accessories: packed with indoor unit) to the flare and the union seat surfaces.
4.Air purge
• Do not discharge the refrigerant into the atmosphere.
Take care not to discharge refrigerant into the atmosphere during installation, reinstallation, or repairs to the refrigerant
circuit.
• Use the vacuum pump for air purging for the purpose of environmental protection.
5.Additional charge
For additional charging, charge the refrigerant from liquid phase of the gas cylinder.
If the refrigerant is charged from the gas phase, composition change may occur in the refrigerant inside the cylinder and the
outdoor unit. In this case, ability of the refrigerating cycle decreases or normal operation can be impossible. However,
charging the liquid refrigerant all at once may cause the compressor to be locked. Thus, charge the refrigerant slowly.
4
Page 5
2
PART NAMES AND FUNCTIONS
MUZ-A09YV -MUZ-A12YV MUZ-A09YVH -MUZ-A12YVH -
OUTDOOR UNIT
Air inlet
(back and side)
Piping
Drain hose
Air outlet
Drain outlet
3
Capacity
Electrical
Coefficient of performance(C.O.P)
Compressor
Fan
Special
NOTE : Test conditions are based on ISO 5151
SPECIFICATION
MUZ-A09YV -
Outdoor model
Function
Power supply
Capacity Rated frequency(Min.~Max.)
Dehumidification
Air flow
Starting current ✽1
Compressor motor current ✽1
Fan motor current
data
kW
r/h
K /h
A
A
A
✽1
Model
Output
Winding
resistance(at 20:)
W
"
Model
Winding
motor
resistance(at 20:)
Dimensions WOHOD
Weight
Sound level
Fan speed
"
mm
kg
dB(A)
rpm
Fan speed regulator
Refrigerant filling
capacity(R410A)
Refrigerating oil (Model)
The standard data contained in these specifications apply only to the operation of the air conditioner under normal conditions.
Since operating conditions vary according to the areas where these units are installed. The following information has been
provided to clarify the operating characteristics of the air conditioner under the conditions indicated by the performance curve.
(1) GUARANTEED VOLTAGE
198 ~ 264V, 50Hz
(2) AIR FLOW
Air flow should be set at MAX.
(3) MAIN READINGS
(1) Indoor intake air wet-bulb temperature :°C WB
(2) Indoor outlet air wet-bulb temperature :°C WB
(3) Outdoor intake air dry-bulb temperature :°C DB
(4) Total input:W
(5) Indoor intake air dry-bulb temperature :°C DB
(6) Outdoor intake air wet-bulb temperature :°C WB
(7) Total input :W
Indoor air wet/dry-bulb temperature difference on the left side of the chart on next page shows the difference between the
indoor intake air wet/dry-bulb temperature and the indoor outlet air wet/dry-bulb temperature for your reference at service.
E1E1
E1E1
Cooling
}
Heating
}
How to measure the indoor air wet-bulb / dry-bulb temperature difference
1. Attach at least 2 sets of wet and dry-bulb thermometers to the indoor air intake as shown in the figure, and at least 2 sets
of wet and dry-bulb thermometers to the indoor air outlet. The thermometers must be attached to the position where air
speed is high.
2. Attach at least 2 sets of wet and dry-bulb thermometers to the outdoor air intake.
Cover the thermometers to prevent direct rays of the sun.
3. Check that the air filter is cleaned.
4. Open windows and doors of room.
5. Press the EMERGENCY OPERATION switch once (twice) to start the EMERGENCY COOL (HEAT) MODE.
6. When system stabilizes after more than 15 minutes, measure temperature and take an average temperature.
7. 10 minutes later, measure temperature again and check that the temperature does not change.
12
Page 13
INDOOR UNIT
OUTDOOR UNIT
MSZ typeMCFZ type
Air out
Air in
Wet and dry-bulb
thermometers
7.3
6.8
6.3
5.7
5.2
difference (degree)
4.7
Indoor air Wet-bulb temperature
8.2
7.6
7.0
6.4
5.8
5.3
8.7
8.0
7.3
6.6
5.9
5.3
Indoor intake air Wet-bulb temperature (:)
Outdoor intake air Dry-bulb temperature (:)
Wet and dry-bulb
thermometers
Wet and dry-bulb
thermometers
:)
Indoor intake air Wet-bulb temperature (
Outdoor intake air Dry-bulb temperature (:)
MSZ-A09YV -E1
23.1
21.3
19.5
17.8
16.0
14.2
difference (degree)
12.4
10.7
Indoor air Dry-bulb temperature
MSZ-A09YV -E1
MUZ-A09YV -E1
MSZ-A12YV -E1
MUZ-A09YV -E1
MUZ-A09YVH -E1
MUZ-A12YV -E1
MUZ-A09YVH -E1
Rated frequency 57Hz
Rated frequency 75Hz
MUZ-A12YVH -E1
25.4
23.4
21.5
19.5
17.6
15.6
13.7
11.7
MSZ-A12YV -E1
MUZ-A12YV -E1
MUZ-A12YVH -E1
Rated frequency 69Hz
Rated frequency 76Hz
MCFZ-A12WV -E1
MUZ-A12YV -E1
MUZ-A12YVH -E1
Rated frequency 69Hz
19.6
18.1
16.6
15.1
13.6
12.1
10.6
9.1
MUZ-A12YV -E1
MCFZ-A12WV -E1
MUZ-A12YVH -E1
Rated frequency 76Hz
:)
Indoor intake air Dry-bulb temperature (:)
Indoor intake air Dry-bulb temperature (
Outdoor intake air Wet-bulb temperature (:)
Outdoor intake air Wet-bulb temperature (:)
NOTE:The above curves are for the heating operation without any frost.
13
Page 14
Correction of Cooling total input
Input correction factors
The operational frequency of compressor
050100150(Hz)
0.0
0.5
1.0
1.5
050100150(Hz)
0.0
0.5
1.0
1.5
Correction of Cooling capacity
Capacity correction factors
The operational frequency of compressor
050100150(Hz)
0.0
0.5
1.0
1.5
Correction of Cooling capacity
Capacity correction factors
The operational frequency of compressor
Correction of Cooling total input
Input correction factors
The operational frequency of compressor
050100150(Hz)
0.0
0.5
1.0
1.5
Correction of Heating total input
The operational frequency of compressor
050100150(Hz)
2.0
1.5
1.0
0.5
0.0
2.0
1.5
1.0
0.5
0.0
2.0
1.5
1.0
0.5
0.0
2.0
1.5
1.0
0.5
0.0
050100150(Hz)
Correction of Heating capacity
Capacity correction factors
The operational frequency of compressor
Correction of Heating total input
Input correction factors
The operational frequency of compressor
050100150(Hz)
050100150(Hz)
Correction of Heating capacity
Capacity correction factors
The operational frequency of compressor
Input correction factors
MUZ-A09YV MUZ-A09YVH -
E1
E1
MUZ-A09YV MUZ-A09YVH -
E1
E1
MUZ-A09YV MUZ-A09YVH -
E1
E1
MUZ-A09YV MUZ-A09YVH -
E1
E1
050100150(Hz)
0.0
0.5
1.0
1.5
Correction of Cooling capacity
Capacity correction factors
The operational frequency of compressor
Correction of Cooling total input
Input correction factors
The operational frequency of compressor
050100150(Hz)
0.0
0.5
1.0
1.5
2.0
1.5
1.0
0.5
0.0
2.0
1.5
1.0
0.5
0.0
Correction of
Heating total input
Input correction factors
The operational frequency of compressor
050100150(Hz)
050100150(Hz)
Correction of Heating capacity
Capacity correction factors
The operational frequency of compressor
MUZ-A12YV MUZ-A12YVH -
E1
E1
Indoor unit :
MSZ-A12YV -
E1
MUZ-A12YV MUZ-A12YVH -
E1
E1
( )
MUZ-A12YV MUZ-A12YVH -
E1
E1
Indoor unit :
MSZ-A12YV -
E1
MUZ-A12YV MUZ-A12YVH -
E1
E1
( )
MUZ-A12YV MUZ-A12YVH -
E1
E1
Indoor unit :
MSZ-A12YV -
E1
MUZ-A12YV MUZ-A12YVH -
E1
E1
( )
MUZ-A12YV MUZ-A12YVH -
E1
E1
Indoor unit :
MSZ-A12YV -
E1
MUZ-A12YV MUZ-A12YVH -
E1
E1
( )
MUZ-A12YV MUZ-A12YVH -
E1
E1
Indoor unit :
MCFZ-A12WV -
E1
MUZ-A12YV MUZ-A12YVH -
E1
E1
( )
MUZ-A12YV MUZ-A12YVH -
E1
E1
Indoor unit :
MCFZ-A12WV -
MUZ-A12YV MUZ-A12YVH -
E1
E1
E1
( )
MUZ-A12YV MUZ-A12YVH -
E1
E1
Indoor unit :
MCFZ-A12WV -
MUZ-A12YV MUZ-A12YVH -
E1
E1
E1E1
( )
MUZ-A12YV MUZ-A12YVH -
E1
E1
Indoor unit :
MCFZ-A12WV -
MUZ-A12YV MUZ-A12YVH -
E1
E1
E1
( )
OUTDOOR LOW PRESSURE AND OUTDOOR UNIT CURRENT
<How to operate fixed-frequency operation (Test run operation)>
1. Press the EMERGENCY OPERATION switch to COOL or HEAT mode (COOL : Press once, HEAT : Press twice).
2. Test run operation starts and continue to operate for 30 minutes.
3. Compressor operates at rated frequency in COOL mode or 58Hz in HEAT mode.
4. Indoor fan operates at High speed.
5. After 30 minutes, test run operation finishes and EMERGENCY OPERATION starts (Operation frequency of compressor
varies).
6. To cancel test run operation (EMERGENCY OPERATION), press the EMERGENCY OPERATION switch or any button on
remote controller.
NOTE : The unit of pressure has been changed to MPa on the international system of units (SI unit system).
The conversion factor is: 1(MPa [Gauge]) =10.2(kgf/ff[Gauge])
14
Page 15
(kgf/F [Gauge]) (MPa [Gauge])
1832
152050256030
70 (%)
35(˚C)
0.2
0.4
0.6
0.8
1.0
1.2
57Hz
2
4
6
8
10
12
14
1.4
Ambient temperature(˚C) Ambient humidity(%)
Outdoor low pressure
MUZ-A09YV MUZ-A09YVH -
E1
E1
152050256030
70 (%)
35(˚C)
2
2.5
3
3.5
4
57Hz
32
18
Outdoor unit current(A)
Ambient temperature(˚C) Ambient humidity(%)
(kgf/F [Gauge]) (MPa [Gauge])
Ambient temperature(˚C) Ambient humidity(%)
Ambient temperature(˚C) Ambient humidity(%)
(kgf/F [Gauge]) (MPa [Gauge])
Ambient temperature(˚C) Ambient humidity(%)
Ambient temperature(˚C) Ambient humidity(%)
1832
152050256030
70 (%)
35(˚C)
0.2
0.4
0.6
0.8
1.0
1.2
69Hz
1.4
15205025
60
30
70 (%)
35(˚C)
2
3
4
5
6
69Hz
32
18
Outdoor low pressure
Outdoor unit current(A)
MUZ-A09YV MUZ-A09YVH -
E1
E1
2
4
6
8
10
12
14
MUZ-A12YV MUZ-A12YVH -
E1
E1
Indoor unit :
MSZ-A12YV -
E1
MUZ-A12YV MUZ-A12YVH -
E1
E1
( )
MUZ-A12YV MUZ-A12YVH -
E1
E1
Indoor unit :
MSZ-A12YV -
E1
MUZ-A12YV MUZ-A12YVH -
E1
E1
( )
1832
152050256030
70 (%)
35(˚C)
0.2
0.4
0.6
0.8
1.0
1.2
69Hz
1.4
15205025
60
30
70 (%)
35(˚C)
2
3
4
5
6
69Hz
32
18
Outdoor low pressure
Outdoor unit current(A)
2
4
6
8
10
12
14
MUZ-A12YV MUZ-A12YVH -
E1
E1
Indoor unit :
MCFZ-A12WV -
E1
MUZ-A12YV MUZ-A12YVH -
E1
E1
( )
MUZ-A12YV MUZ-A12YVH -
E1
E1
Indoor unit :
MCFZ-A12WV -
E1
MUZ-A12YV MUZ-A12YVH -
E1
E1
( )
OUTDOOR LOW PRESSURE AND OUTDOOR UNIT CURRENT
Outdoor unit current (A)
Outdoor unit current (A)
Ambient temperature(˚C)
Ambient temperature(˚C)
MUZ-A09YV MUZ-A09YVH -
E1
E1
Outdoor unit current (A)
Ambient temperature(˚C)
MUZ-A12YV MUZ-A12YVH -
E1
E1
Indoor unit :
MSZ-A12YV -
E1
MUZ-A12YV MUZ-A12YVH -
E1
E1
( )
MUZ-A12YV MUZ-A12YVH -
E1
E1
Indoor unit :
MCFZ-A12WV -
E1
MUZ-A12YV MUZ-A12YVH -
E1
E1
( )
3.0
2.5
2.0
1.5
1.0
0.5
0.0
2 5101520 25(:)
58Hz
4.0
3.5
3.0
2.5
2.0
1.5
1.0
2 5101520 25(:)
58Hz
4.0
3.5
3.0
2.5
2.0
1.5
1.0
2 5101520 25(:)
58Hz
COOL operation
1 Both indoor and outdoor unit are under the
same temperature/humidity condition.
2 Air flow : High speed
3 Operational frequency : 57Hz(MUZ-A09YV, MUZ-A09YVH)
69Hz(MUZ-A12YV, MUZ-A12YVH)
Dry-bulb temperature
20
25
3070
Relative humidity(%)
50
60
HEAT operation
Condition indoor: Dry bulb temperature 20.0°C
Condition outdoor: Dry bulb temperature 2,7,15,20.0°C
Wet bulb temperature 14.5°C
Wet bulb temperature 1,6,12,14.5°C
15
Page 16
PERFORMANCE DATA COOL operation Rated frequency 57Hz
MSZ-A09YV -: MUZ-A09YV -MUZ-A09YVH -Rated frequency 75Hz
NOTE Q:Total capacity (kW) INPUT:Total power input (W) DB : Dry-bulb temperature WB : Wet-bulb temperature
MSZ-A12YV -: MUZ-A12YV -MUZ-A12YVH -Rated frequency 76Hz
NOTE Q:Total capacity (kW) INPUT:Total power input (W) DB : Dry-bulb temperature WB : Wet-bulb temperature
E1E1E1
E1E1E1
MCFZ-A12WV -: MUZ-A12YV -MUZ-A12YVH -Rated frequency 76Hz
NOTE Q:Total capacity (kW) INPUT:Total power input (W) DB : Dry-bulb temperature WB : Wet-bulb temperature
E1E1E1
20
Page 21
9
ON
OFF
ON
OFF
Outdoor fan
motor
Compressor
5 seconds15 seconds
ON
OFF
Compressor
Outdoor fan
motor
R.V.coil
ON
OFF
ON
OFF
<COOL>
5 seconds
<HEAT>
5 seconds
ACTUATOR CONTROL
MUZ-A09YV -MUZ-A12YV MUZ-A09YVH -MUZ-A12YVH -
E1E1
E1E1
9-1. Outdoor fan motor control
The AC fan motor turns ON/OFF, interlocking with the compressor.
[ON] The AC fan motor turns ON 5 seconds before the compressor starts up.
[OFF] The AC fan motor turns OFF 15 seconds after the compressor has stopped running.
9-2. R.V. coil control
Heating
Cooling . . . . . . . . . . . . . . . . . OFF
Dry
NOTE: The 4-way valve reverses for 5 seconds right before start-up of the compressor.
. . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
ON
OFF
9-3. Relation between main sensor and actuator
Sensor
Discharge temperature thermistor
Indoor coil temperature thermistor
Defrost thermistor
Fin temperature thermistor
Ambient temperature thermistor
Cooling : Coil frost prevention
Heating : High pressure protection
Cooling : High pressure protection
Heating : Defrosting
Cooling : Low ambient temperature operation
Heating : Defrosting (Heater)
Purpose
Protection
Protection
Compressor
21
LEV
Actuator
Outdoor
fan motor
R.V.coil
Indoor
fan motor
Defrost
heater
Page 22
10
Jumper wire
Defrost finish temperature
(Initial setting)
JS
none
(cut)
Model
soldered
MUZ-A09YVH -
E1
E1
MUZ-A12YVH -
(Serial number 4000531~)
(Serial number 4000211~)
MUZ-A09YV -
E1
E1
MUZ-A12YV MUZ-A09YVH -
E1
E1
MUZ-A12YVH -
(Serial number ~4000530)
(Serial number ~4000210)
8:
5:
Housing point
SERVICE FUNCTIONS
MUZ-A09YV -MUZ-A12YV MUZ-A09YVH -MUZ-A12YVH -
E1E1
E1E1
CHANGE IN DEFROST SETTING
<JS> When the JS wire of the outdoor Inverter P.C. board is cut/ soldered, the defrost finish temperature is changed.
(Refer to page 32.)
11
TROUBLESHOOTING
MUZ-A09YV -MUZ-A12YV MUZ-A09YVH -MUZ-A12YVH -
11-1. Cautions on troubleshooting
1. Before troubleshooting, check the following:
1) Check the power supply voltage.
2) Check the indoor/outdoor connecting wire for mis-wiring.
2. Take care the following during servicing.
1) Before servicing the air conditioner, be sure to first turn off the remote controller to stop the main unit, and then after
confirming the horizontal vane is closed, turn off the breaker and / or disconnect the power plug.
2) Be sure to turn OFF the power supply before removing the front panel, the cabinet, the top panel, and the
electronic control P.C. board.
3) When removing the electrical parts, be careful to the residual voltage of smoothing capacitor.
4) When removing the electronic control P.C. board, hold the edge of the board with care NOT to apply stress on the
components.
5) When connecting or disconnecting the connectors, hold the housing of the connector. DO NOT pull the lead wires.
Lead wiring
3. Troubleshooting procedure
1) First, check if the OPERATION INDICATOR lamp on the indoor unit is flashing on and off to indicate an abnormality.
To make sure, check how many times the abnormality indication is flashing on and off before starting service work.
2) Before servicing check that the connector and terminal are connected properly.
3) If the electronic control P.C. board is supposed to be defective, check the copper foil pattern for disconnection and
4) When troubleshooting, refer to the flow chart on page 23 and check table on page 24.
the components for bursting and discoloration.
E1E1
E1E1
22
Page 23
11-2. Instruction of troubleshooting
Start
Indoor unit
operates.
Outdoor unit
doesn't
operate.
Outdoor unit
operates in
only Test Run
operation.
Check room
temperature
thermistor.
Refer to
"Test point
diagram and
voltage".
Outdoor unit
doesn't
operate
even in
Test Run
operation.
Refer to A
"Check of
inverter/
compressor"
on page 26.
Indoor unit operates.
Outdoor unit doesn't
operate normally.
Unit doesn't
operate
normal
operation in
COOL or
HEAT mode.
Refer to H
"Check of
R.V. coil"
on page 28.
Indoor unit
operates, when
the EMERGENCY
OPERATION
switch is pressed.
Refer to
"Check of
remote controller
and receiver
P.C. board".
Indoor unit
doesn't receive
the signal from
remote controller.
Indoor unit
doesn't operate,
when the
EMERGENCY
OPERATION
switch is pressed.
1. Check indoor / outdoor
connecting wire.
(Check if the power
is supplied to the
indoor unit.)
2. Refer to
"Check of indoor
electronic control
P.C. board".
OPERATION INDICATOR
lamp on the indoor unit is
flashing on and off.
As for indoor unit MSZ type,
refer to service manual OB327.
As for indoor unit MCFZ type,
refer to service manual OB344.
MSZ type
Both lamps
(Left and right)
Flash on and off
at 0.5-second
intervals
Cause:
Indoor unit
• The horizontal
vanes are not
installed
correctly.
Refer to
"Check of
installation of
the horizontal
vanes".
Left lamp
Flash on and
off at
0.5-second
intervals
Cause:
Indoor/
Outdoor unit
• Mis-wiring or
trouble of
serial signal.
Refer to N
"How to check
of mis-wiring
and serial
signal error
(When
outdoor unit
doesn't work)"
on page 31.
Left lamp
2-time flash
Cause:
Indoor unit
• Trouble of
room temp erature/
indoor coil
thermistor
Check room
temperature
thermistor
and indoor
coil thermistor.
Refer to
"Test point
diagram and
voltage".
MSZ type
Left lamp
3-time flash
Cause:
Indoor unit
• Trouble of
indoor fan
motor
Refer to
"Check of
indoor fan
motor".
Left lamp
4-time flash
Cause:
Indoor unit
• Trouble of
indoor unit
control
system
Replace the
indoor
electronic
control
P.C. board.
Left lamp
5-time flash
Cause:
Outdoor unit
• Outdoor
power
system
abnormality
Refer to A
"Check of
inverter/
compressor"
on page 26.
Left lamp
6-time flash
Cause:
Outdoor unit
• Trouble of
thermistor
in outdoor
unit
Refer to G
"Check of
outdoor
thermistors"
on page 28.
Left lamp
7-time flash
Cause:
Outdoor unit
• Trouble of
outdoor
control
system
Replace the
inverter P.C.
board.
23
Page 24
Abnormal point/ Condition
When compressor has stopped by overcurrent protection within
1 minute 3 times in a row after compressor start-up, unit stops.
When discharge temperature thermistor, fin temperature
thermistor or defrost thermistor shorts or opens during
compressor running, compressor stops and restarts 3 minutes
later.
When nonvolatile memory data cannot be read properly,
compressor stops and restarts 3 minutes later.
When 12A(MUZ-A09YV, MUZ-A09YVH)/ 20A(MUZ-A12YV,
MUZ-A12YVH) current flows into power transistor module,
compressor stops and restarts 3 minutes later.
When discharge temperature thermistor exceeds 116:,
compressor stops. Compressor can restart if discharge
temperature thermistor reads 100: or less 3 minutes later.
When temperature at heat sink exceeds 83: or temperature of
inverter P.C. board exceeds 79:, compressor stops and
restarts 3 minutes later.
When indoor coil thermistor exceeds 70:.
When the defrost thermistor exceeds 70: in COOL mode.
When current from power outlet exceeds 7A(MUZ-A09YV,
MUZ-A09YVH)/ 9A(MUZ-A12YV, MUZ-A12YVH), compressor
frequency lowers.
When indoor coil thermistor exceeds 55: in HEAT mode,
compressor frequency lowers.
When indoor coil thermistor reads 6: or less in COOL mode,
compressor frequency lowers.
When discharge temperature thermistor exceeds 110:,
compressor frequency lowers.
When discharge temperature has been 40: or less for 20
minutes.
No.
1
2
3
5
6
7
8
10
11
12
14
15
Symptom
LED indication
Detection method
Checkpoint
Outdoor unit
does not
operate
'Outdoor unit
stops and
restarts 3
minutes later'
is repeated
Outdoor unit
operates (at
low
frequency)
Outdoor unit
operates
1-time flash every
2.5 seconds
NOTE:
For abnormality
location, refer to
'Indoor
troubleshooting
check table'.
Refer to service
manual OB327.
2-time flash
2.5 seconds OFF
3-time flash
2.5 seconds OFF
4-time flash
2.5 seconds OFF
5-time flash
2.5 seconds OFF
1-time flash
2.5 seconds OFF
3-time flash
2.5 seconds OFF
4-time flash
2.5 seconds OFF
7-time flash
2.5 seconds OFF
Outdoor power
system
Outdoor
thermistors
Outdoor control
system
Overcurrent
protection
Discharge
temperature
overheat
protection
Fin temperature
thermistor overheat
protection
High pressure
protection
Frequency drop by
current protection
Frequency drop by
high pressure
protection
Frequency drop by
defrosting in COOL
mode
Frequency drop by
discharge
temperature
protection
Low discharge
temperature
protection
· Check stop valve.
· Reconnect connectors.
· Refer to A "How to check inverter/
compressor" on page 26.
· Refer to G "Check of outdoor
thermistors" on page 28.
· Check stop valve.
· Reconnect connectors.
· Refer to A "How to check inverter/
compressor" on page 26.
Replace inverter P.C. board after
check of A "How to check inverter/
compressor" on page 26 and G
"Check of outdoor thermistors" on
page 28.
· Check refrigerant circuit and
refrigerant amount.
· Refer to G "Check of outdoor
thermistors" on page 28.
· Refer to L "Check of LEV" on page
30.
· Check around outdoor unit.
· Check outdoor unit air passage.
· Refer to I "Check of outdoor fan
motor" on page 29.
· Check refrigerant circuit and
refrigerant amount.
· Check stop valve.
The unit is normal, but check the
following.
· Check if indoor filters are clogged.
· Check if refrigerant is short.
· Check if indoor/outdoor unit air
circulation is short cycled.
· Refer to L "Check of LEV" on
page 30.
· Check refrigerant circuit and
refrigerant amount.
<Inverter P.C. board>
LED
Flashing
Refer to A "How to check inverter/
compressor" on page 26.
When the bus-bar voltage of inverter cannot be detected
normally.
Bus-bar voltage
8-time flash
2.5 seconds OFF
Compressor
sinusoidal current
When the waveform of compressor current is distorted.
· Check stop valve.
· Reconnect connector.
· Refer to A "How to check inverter/
compressor" on page 26.
8-time flash
2.5 seconds OFF
PAM protection
PAM:
Pulse
Amplitude
Modulation
When the overcurrent flows into IGBT(Insulated Gate Bipolar
transistor : TR821) or when the bus-bar voltage reaches 300V
or more, PAM stops and restarts.
This is not malfunction.
PAM protection will be activated in
the following cases;
1Instantaneous power voltage drop
(Short time power failure)
2When the power supply voltage is
high.
9-time flash
2.5 seconds OFF
Inverter check
mode
When the connector of compressor is disconnected, inverter
check mode starts.
Check if the connector is correctly
connected.
Refer to A "How to check inverter/
compressor" on page 26.
4
9
16
13
When ambient temperature thermistor shorts or opens during
compressor running.
5-time flash
2.5 seconds OFF
Outdoor
thermistors
· Refer to G "Check of outdoor
thermistors" on page 28.
1. Troubleshooting check table
NOTE 1. The location of LED is illustrated at the right figure. Refer to page 32.
2. LED lights up during normal operation.
The flashing frequency shows the number of times the LED blinks after every 2.5-second OFF.
(Example) When the flashing frequency is “2”.
ON
2.5-second OFF
OFF
0.5-second ON
2.5-second OFF
24
0.5-second ON
Page 25
2. Trouble criterion of main parts
Part nameFigureCheck method and criterion
Outdoor fan motor(MF)
INNER FUSE
152i : CUT OFF
0
5
R.V. coil(21S4)
LEV(Expansion valve)
Measure the resistance between the terminals with a tester.
(Part temperature –15˚C ~ 40˚C)
WHT – BLK
BLK – RED
Abnormal
Open or
short-circuit
Normal
Measure the resistance between the terminals with a tester.
(Part temperature –15˚C ~ 40˚C)
Normal
1.90 k" ~ 2.39 k"
Abnormal
Open or short-circuit
WHT – RED
RED – ORN
YLW – BRN
BRN – BLU
Abnormal
Open or
short-circuit
Normal
39 " ~ 50 "
Measure the resistance with a tester.
(Part temperature : –15˚C ~ 40˚C)
Measure the resistance with a tester. (Part temperature –15˚C ~ 40˚C)
Color of lead wire
Color of lead wire
Discharge temperature
thermistor(RT62)
Measure the resistance with a tester.
Before measurement, hold the thermistor with your hands to warm it up.
(Part temperature 0˚C ~ 40˚C)
Normal
150 k" ~ 600 k"
30 k" ~ 180 k"
Abnormal
Open or short-circuit
Normal
5 k" ~ 65 k"
Abnormal
Open or short-circuit
Defrost thermistor
(RT61)
Fin temperature
thermistor(RT64)
Measure the resistance with a tester.
Before measurement, hold the thermistor with your hands to warm it up.
(Part temperature 0˚C ~ 40˚C)
NormalAbnormal
Open or short-circuit
Ambient temperature
thermistor(RT65)
WHT
RED
BLK
299 " ~ 374 "
242 " ~ 304 "
Measure the resistance between the terminals with a tester.
(Part temperature –15˚C ~ 40˚C)
Compressor(MC)
Defrost heater(H)
Measure the resistance with a tester.
(Part temperature -15˚C ~ 40˚C)
Normal
341 " ~ 427 "
Abnormal
Open or short-circuit
U-V
U-W
V-W
Abnormal
Open or
short-circuit
Normal
MUZ-A12YV
MUZ-A12YVH
0.42 " ~ 0.53 "
MUZ-A09YV
MUZ-A09YVH
1.31 " ~ 1.66"
23
W
U
V
1
WHT
RED BLK
FUSE
LEV
WHT
6
RED1
ORN4
YLW5
BRN2
BLU3
MUZ-A09YV -MUZ-A12YV MUZ-A09YVH -MUZ-A12YVH -
E1E1
E1E1
25
Page 26
When OPERATION INDICATOR lamp flashes 5-time.
Outdoor unit does not operate.
A
How to check inverter/ compressor
Disconnect the connector (CN61)
between compressor and power
transistor module (IPM).
Check the voltage
between terminals.
Are the voltages
balanced?
See B “Check of open phase” on page 26.
No
Check the resistance of power transistor
module.
Yes
Check the
compressor.
B
Check of open phase
See D “Check of compressor” on page 27.
Is the resistance
infinite?
●With the connector between compressor and power transistor
module disconnected, activate the inverter and check if the inverter
is normal by measuring the balance of voltage between terminals.
Output voltage [V]
115V
<< Operation method>>
Start cooling or heating operation by pressing the EMERGENCY OPERATION
switch on the indoor unit. (test-run mode : refer to page 14)
w Measure AC voltage between
the lead wires at 3 points.
See C 'Check of power transistor module' on page 26.
Yes
Replace the inverter P.C.
board.
No
(0~several
")
Replace the inverter P.C.
board and compressor.
Inverter P.C. board
LED
Flashing
NOTE 1. Output voltage varies according to power supply voltage.
2. Measure the voltage by analog type tester.
3. During this check, LED of inverter P.C. board flashes 9 times.
C
Check of power transistor module
●Disconnect the connector (CN61) between compressor and
power transistor module, and measure the resistance between
terminals on the power transistor module.
<<Measurement point>>
at 6 points
BLK-WHT, WHT-BLK
BLK-RED, RED-BLK
WHT-RED, RED-WHT
<<Judgement>>
Infinite ["]···········Normal
0~dozens of ······Abnormal (short)
26
9-time flash
ohmmeter indication
"
X1
"
X1
Normal
(infinite)
Abnormal
(0~dozens of ")
2.5-second OFF
Page 27
D
Check of compressor
Start
E "Check of compressor
winding" on page 27.
No
Replace the compressor.
Is the compressor normal?
Yes
F "Check of compressor
operation time" on page
27. Does the compressor
operate continuously?
No
Is the compressor
operation time more than
10 seconds?
Yes
Ok
E
Check of compressor winding
Check the refrigerant circuit.
● Disconnect the connector (CN61) between compressor and power
transistor module, and measure the resistance between the
compressor terminals.
<<Measurement point>>
at 3 points
BLK-WHT
BLK-RED
WHT-RED
w Measure the resistance between the
lead wires at 3 points.
<<Judgement>>
Refer to page 25.
0["] ···············Abnormal [short]
Infinite["] ·······Abnormal [open]
NOTE 1. Be sure to zero the ohmmeter before measurement.
2. Winding resistance for each phase at 20:.
Refer to page 5.
No
Yes
Ohmmeter indication
"
X1
"
X1
"
X1
Replace the compressor.
WHT
23
Normal
V
(1~several ")
Compressor motor
Abnormal
(0" ····· short)
Abnormal
(infinite····· open)
RED BLK
1
W
U
Check of compressor operation time
F
●Connect the compressor and activate the inverter. Then measure
the time until the inverter stops due to over current.
<<Operation method>>
Start heating or cooling operation by pressing the EMERGENCY
OPERATION switch on the indoor unit. (Test-run mode)
<<Measurement>>
Measure the time from the start of outdoor fan running to the
stop of compressor due to over current.
<<Judgement>>
For reference
0~10 seconds·····················Abnormal (compressor short)
10~60 seconds···················Abnormal (compressor lock-out)
60 seconds~5 minutes·······Abnormal (refrigerant circuit defect)
more than 5 minutes···········Normal
27
0 second
10 seconds
60 seconds
5 minutes
Outdoor fan starts
Abnormal
(Compressor winding short or layer short)
Abnormal
(Compressor lock-out)
Abnormal
(Refrigerant circuit defect, etc.)
Normal
Page 28
When OPERATION INDICATOR lamp flashes 6-time.
Measure the
resistance
between CN641
1 and 2.
Measure the
resistance
between CN642
1 and 2.
No
Yes
Replace the
thermistor
except RT64.
In case of RT64,
replace the
inverter P.C.
board.
Since RT64 is
combined with
inverter P.C.
board.
Replace the inverter
P.C. board.
Disconnect the connectors CN641, CN642 and CN643 from the inverter P.C. board.
(Check the characteristics of each thermistor.)
1 Reconnect the
connectors CN641,
CN642 and CN643.
2 Disconnect the
connector between
the compressor and
power transistor
module.
Defrost thermistor RT61
Measure the
resistance
between CN641
3 and 4.
Turn ON the
power supply and
press the
EMERGENCY
OPERATION
switch.
Discharge
temperature
thermistor RT62
Fin temperature
thermistor RT64
Does the
resistance of the
thermistor have the
characteristics on
page 32?
No
Yes
Does the unit
operate 10 minutes
or more?
Is LED of the
inverter P.C. board
flashes 5 times?
Reconnect the
connector or
connecting wire.
Yes
No
Measure the
resistance
between CN643
1 and 2.
Ambient
temperature
thermistor RT65
The thermistors in the outdoor unit are abnormal.
G
Check of outdoor thermistors
Check of R.V. coil
H
w First of all, measure the resistance of R.V. coil to check if the coil is defective (refer to page 25).
w In case CN721 is not connected or R.V. coil is open, voltage is generated between the
terminal pins of the connector although any signal is not being transmitted to R.V. coil.
Check if CN721 is connected.
Unit operates COOL mode even if it is set to HEAT mode.
Disconnect connector (CN61) between
compressor and power transistor
module.
Turn ON the power supply and press the
EMERGENCY OPERATION switch
twice (HEAT mode).
Unit operates HEAT mode even if it is set to COOL mode.
Disconnect connector (CN61) between
compressor and power transistor
module.
Turn ON the power supply and press the
EMERGENCY OPERATION switch once
(COOL mode).
Is there 230V AC between CN7211 and
2 on the power P.C.board 3 minutes after
the power supply is turned ON?
Replace the 4-way valve.
Is there 230V AC between CN7211 and
2 on the power P.C.board 3 minutes after
the power supply is turned ON?
•Defective R.V. coil
•Defective 4-way valve
28
Yes
No
No
Power P.C. board
(soldered side)
Yes
Replace the
power P.C. board.
CN721
Replace the
power P.C. board.
Page 29
Outdoor fan motor does not operate.
Is there voltage 230V
AC between indoor
terminal block 2 and
N?
Replace the
outdoor fan motor.
3 minutes after
power ON, is there voltage
230V AC between outdoor
terminal block 2 and N?
Is the resistance of fan
motor normal?
Is there voltage 230V
AC between CN771 2
and 3 on the power
P.C. board?
Disconnect the connector CN771 on the power P.C.
board.
Disconnect the connector (CN61) between
compressor and power transistor module.
Turn ON the power supply and press the
EMERGENCY OPERATION switch.
Yes
Yes
Yes
No
No
CN771
Power P.C. board
1
2
3
Fan
motor
Outdoor terminal block
3
N
2
Check the resistance of fan motor. (Refer to page 25.)
Replace the
power P.C. board.
Rectify indoor/ outdoor
connecting wire.
No
Replace the indoor
electronic control
P.C. board.
Replace the outdoor
fan motor.
No
Yes
Indoor/ outdoor
connecting
wire
Disconnect the connector
(CN61) between compressor and
power transistor module.
Turn ON power supply and press
the EMERGENCY OPERATION
switch.
Check the electric
parts in main circuit.
Ok.
If flash, refer to
page 24.
3 minutes after power
ON, is there voltage of
230V AC between
outdoor terminal block 2
and N?
Is there voltage
280V ~ 370V DC
between LD61A (+)
and LD66A (–) on the
inverter P.C. board?
(Refer to page 32.)
Dose LED on the inverter
P.C. board light up or
flash? (Refer to page 32.)
Outdoor terminal block
3
N
2
Yes
Yes
Yes
No
No
Replace the indoor
electronic control
P.C. board.
No
Yes
No
Indoor/ outdoor
connecting
wire
Replace the inverter
P.C. board.
LD66A
LD61A
(–)
(+)
280V~370V DC
Inverter P.C. board
(Pattern side)
Is there voltage 230V AC
between indoor terminal
block 2 and N?
Rectify indoor/ outdoor
connecting wire.
I
Check of outdoor fan motor
Inverter does not operate.
Check of power supply
J
29
Page 30
Outdoor unit does not operate at all or stops immediately due to over current.
Replace the power P.C. board.
When the current-limiting resistor is open, the rush current limiting relay (X64) may not work properly.
Does current-limiting resistor (R64) detect 10"?
No ∞
Yes
Ok
Start
Replace the LEV.
With remote controller set toward the indoor unit, press
the OPERATE/ STOP(ON/ OFF) button and confirm one
beep tone.
LEV operates in full-opening
direction.
Is LEV properly fixed to the
expansion valve?
Ok
Do you hear the expansion
valve "click, click·······"?
Do you feel the expansion
valve vibrate on touching it ?
Does the resistance of LEV
have the characteristics on
page 25?
Measure each voltage between connector pins
of CN724 on the inverter P.C. board.
1.Pin3(-) Pin1(+)
2.Pin4(-) Pin1(+)
3.Pin5(-) Pin1(+)
4.Pin6(-) Pin1(+)
Is there about 3~5V AC between each?
NOTE: Measure the voltage by an analog tester.
No
Yes
Yes
Yes
No
Replace the
expansion valve.
Yes
No
No
Properly fix the LEV to the
expansion valve.
Replace the
inverter P.C. board.
NOTE : After check of LEV, do the undermentioned
operations.
1. Turn OFF the power supply and
turn ON again.
2. Press the RESET button on the remote
controller.
Turn ON the power supply.
1 During pressing both the OPERATION SELECT
button and the TOO COOL button on the
remote controller at the same time,
press the RESET button.
2 First, release the RESET button.
And release the other two buttons since all LCD
in operation display section of the remote controller
is displayed after 3 seconds.
1 During pressing both the OPERATION SELECT
button and the TOO COOL button on the
remote controller at the same time,
press the RESET button.
2 First, release the RESET button.
And release the other two buttons since all LCD
in operation display section of the remote controller
is displayed after 3 seconds.
AMPM
CLOCK
:
AMPM
Replace the inverter P.C. board.
Is there 230V AC between CN722 1 and 3 on the
power P.C. board?
Yes
No
No problem of the
power P.C. board.
Is the voltage between CN726 6(+)-3(-) on the
power P.C. board 0V DC? (Refer to page 33.)
Yes
No
Replace the power
P.C. board.
NOTE: In case both thermistors are more than the above
temperature, cool them with cold water etc...
In HEAT mode, for more than 5 minutes, let the ambient temperature thermistor continue to read 5: or less, and let the
defrost thermistor continue to read -1: or less.
3
2
1
230V AC
Check the following points before checking electric continuity.
1) Does the resistance of ambient temperature thermistor have the characteristics? (Refer to page 32.)
2) Is the resistance of defrost heater normal? (Refer to page 25.)
3) Does the heater protector remain conducted (not open)?
4) Are both ambient temperature thermistor and circuit of defrost heater securely connected to connectors?
26H
CN726
CN722
H
2
1
2
1
36
Check of current-limiting resistor
K
Heating/Cooling does not work sufficiently.
Check of LEV (Expansion valve)
L
Outdoor base gets frozen.
Check of defrost heater
M
<MUZ-A09YVH MUZ-A12YVH>
30
Page 31
When OPERATION INDICATOR lamp flashes ON and OFF in every 0.5-second.
No
Replace the
indoor/ outdoor
connecting wire.
Is there voltage approximate 280V DC between
LD61A (+) and LD66A (–) on the inverter P.C.
board arter 3 minutes?
Turn OFF the power supply and then turn ON
again.
Press EMERGENCY OPERATION switch.
After 3 minutes, is there approximate 230V AC
between outdoor terminal block 2 and N?
w4 Replace the inverter P.C.
board.
Does the right side of OPERATION INDICATOR
lamp blink quickly?
w2 Mis-wiring may damage indoor electronic
control P.C. board during the operation.
Be sure to confirm the wiring is correct
before the operation starts.
Replace the indoor
electronic control
P.C. board.
No
Replace the indoor/ outdoor connecting wire.
Release the failure mode. w3
Yes
Yes
A
B
Turn OFF the power supply.
Disconnect the indoor/ outdoor connecting wire.
Short-circuit indoor terminal block N and 3.
Turn ON the power supply.
During pressing both the OPERATION SELECT button
and TOO COOL button on the remote controller at the
same time, press the RESET button.
At first, release the RESET button.
And release the other two buttons since all LCD in
operation display section of the remote controller is
displayed after 3 seconds.
Transmit the signal of remote controller, pressing
OPERATE/STOP (ON/OFF) button on the remote
controller.
(The above procedure allows OPERATION INDICATOR
lamp to indicate the failure-mode.)
Remove the short-circuit between indoor terminal block N
and 3.
Reconnect the indoor/ outdoor connecting wire.
Turn ON the power supply.
Press the EMERGENCY OPERATION switch.
Is there amplitude of 5 to 10V DC between outdoor
terminal block N and 3 after 3 minutes (for confirmation of
serial signal)?
1. Turn OFF the power supply.
2. Disconnect the connector (CN61) between the
compressor and the power transistor module.
3. Turn ON the power supply.
4. Press the EMERGENCY OPERATION switch.
No
Yes
No
Yes
(light up or OFF)
Is mis-wiring
indicated when
the contactor
(52C) on the
indoor electronic
control P.C.
board turns ON
3 minutes later?
Yes
No
· Turn OFF inverter-controlled lighting
equipment.
· Turn OFF the power supply and then
turn ON again.
· Press the EMERGENCY
OPERATION switch.
B
· Reinstall
either the
unit or the
light each
other away.
· Attach a filter
on receiving
section of
the indoor
unit.
w3 Be sure to release the failure-mode
recall function after checking.
w4 Be careful to the residual voltage of smoothing capacitor.
Procedure of release of failure-mode.
1 Press the EMERGENCY
OPERATION switch.
2 Turn OFF the power supply.
3 Press the RESET button on the
remote controller.
Start
No
• Turn ON the power supply.
•
Press once EMERGENCY OPERATION switch.
Is there any mis-wiring, poor contact,
or wire disconnection? w2
Make them sure.
Yes
After 3 minutes, mis-wiring is indicated
(0.5-second ON, 0.5-second OFF)
on OPERATION INDICATOR
lamp on indoor unit.w
w Short circuit of JPG and JPS on the indoor
electronic control P.C. board enables
self-check to be displayed in 3 seconds.
Yes
Is there 230V AC between outdoor terminal
block 2 and N?
No
Replace the
indoor/ outdoor
connecting wire.
A
•The following indication
applies regardless of shape
of the indicator.
Blinking
Operation Indicator
As for indoor unit MSZ type, refer to service manual OB327.
As for indoor unit MCFZ type, refer to service manual OB344.
AMPM
CLOCK
:
AMPM
Outdoor unit doesn’t operate.
How to check mis-wiring and serial signal error (when outdoor unit does not work)
N
31
Page 32
MUZ-A09YV -MUZ-A12YV -
-20 -10010203040
0
10
20
30
40
50
60
70
80
90
100
Temperature(:)
Ambient temperature thermistor(RT65)
Defrost thermistor(RT61)
Temperature(:)
Discharge temperature thermistor(RT62)
0 102030405060708090100110120
0
100
200
300
400
500
600
700
0 1020304050607080
0
20
40
60
80
100
120
140
160
180
200
Temperature(:)
Fin temperature thermistor(RT64)
Resistance(k")
Resistance(k")
Resistance(k")
MUZ-A09YVH -MUZ-A12YVH -
Inverter P.C. board
Back side of unit
(Refer to page 29.)
LD66A
LD61A
280V ~ 370V DC
E1E1
E1E1
230V AC
Jumper wire for change in defrost setting (JS)
(Refer to page 22.)
LED monitor
lamp
Output to drive
compressor
(LDU,LDV,LDW)
Front side of unit
Discharge temperature
thermistor (RT62)
Connecting
Defrost thermistor (RT61)
(CN641)
wire with
power P.C.
board
(CN725)
32
(CN642)
thermistor (RT65)
Fin temperature
thermistor (RT64)
(CN643)
Ambient temperature
LEV
connector
(CN724)
Connector
for indoor/
outdoor
communi-
Zero cross
signal
connector
(CN800)
cation
(CN601)
Page 33
MUZ-A09YV -MUZ-A12YV MUZ-A09YVH -MUZ-A12YVH -
Power P.C. board
Back side of unit
E1E1
E1E1
Connecting wire with
inverter P.C. board
(CN726)
(Refer to page 30.)
R.V. coil
(CN721)
Front side of unit
230V AC
Output to drive
outdoor fan
motor (CN771)
230V AC
Heater connector
(CN722)
}
MUZ-A09YVH
MUZ-A12YVH
230V AC
230V AC
33
Page 34
12
DISASSEMBLY INSTRUCTIONS
<"Terminal with lock mechanism" Detaching points>
In case of terminal with lock mechanism, detach the terminal as shown below.
There are two types ( Refer to (1) and (2)) of the terminal with lock mechanism.
The terminal with no lock mechanism can be removed by pulling it out.
Check the shape of the terminal and work.
(1) Slide the sleeve and check if there is a locking lever or not.(2) The terminal with this connector is a terminal
Sleeve
with lock mechanism
1Slide the sleeve.
2Pull the terminal while
Locking lever
MUZ-A09YV -MUZ-A12YV -
pushing the locking
lever.
E1E1
MUZ-A09YVH -MUZ-A12YVH OUTDOOR UNIT
OPERATING PROCEDURE
1. Removing the cabinet.
(1) Remove the screws fixing the top panel. (Photo 1)
(2) Remove the top panel. (Photo 1)
(3) Remove the screw fixing the service panel. (Photo 2)
(4) Pull down the service panel and remove it. (Photo 2)
(5) Remove the screws fixing the cabinet.
(6) Remove the cabinet.
(7) Disconnect the indoor/outdoor connecting wire.
(8) Remove the screws fixing the back panel.
(9) Remove the back panel.
1Hold the sleeve, and
pull out the terminal
slowly.
Connector
E1E1
PHOTOS
Photo 1
Screws of
the top panel
Screws of
the top panel
Photo 2
Screws of
the cabinet
Screw of the
service panel
Direction to
remove
Hooks
Screws of
the cabinet
Back
panel
Service
panel
34
Page 35
OPERATING PROCEDURE
PHOTOS
2. Removing the inverter assembly, inverter P.C. board
and power P.C. board
(1) Remove the top panel, cabinet and service panel.
(Refer to 1.)
(2) Disconnect the indoor/outdoor connecting wire and remove
the back panel. (Refer to 1.)
(3) Disconnect the ground wire, the lead wire to the reactor
and the following connectors;
<Power P.C. board>
CN721 (4-way valve)
CN722 (Defrost heater) MUZ-A09/A12YVHCN771 (Fan motor)
<Inverter P.C. board>
CN641 (Defrost thermistor and discharge temperature
thermistor)
CN643 (Ambient temperature thermistor)
CN724 (LEV)
(4) Remove the compressor connector (CN61).
(5) Remove the screws fixing the relay panel. (Photo 3)
(6) Remove the inverter assembly. (Photo 3)
(7) Disconnect all connectors and lead wires on the inverter
P.C. board. (Photo 4)
(8) Remove the inverter P.C. board from the inverter assembly.
(9) Remove the screw fixing the power P.C. board. (Photo 4)
(10)
Disconnect all connectors and lead wires on the power P.C.
board.
(11)
Remove the power P.C. board from the inverter assembly.
E1
Photo 3
Photo 4
Heat sink
Screws of the relay panel
Inverter
P.C. board
Screw of
the ground
wire
Power
P.C. board
3. Removing R.V. coil
(1) Remove the top panel, cabinet and service panel.
(Refer to 1.)
(2) Disconnect the indoor/outdoor connecting wire and remove
the back panel. (Refer to 1.)
(3) Remove the inverter assembly. (Refer to 2.)
(4) Remove the R.V. coil. (Photo 5)
Screw of the power
P.C. board
35
Page 36
OPERATING PROCEDURE
PHOTOS
4. Removing the defrost thermistor and discharge temperature thermistor
(1) Remove the top panel, cabinet and service panel.
(Refer to 1.)
(2) Disconnect the indoor/outdoor connecting wire and remove
the back panel. (Refer to 1.)
(3) Remove the inverter assembly. (Refer to 2.)
(4) Pull out the defrost thermistor from its holder. (Photo 6)
(5) Pull out the discharge temperature thermistor from its
holder. (Photo 5)
Photo 5
Photo 6
R.V. coil
Discharge temperature thermistor
36
Defrost
thermistor
Page 37
OPERATING PROCEDURE
PHOTOS
5. Removing outdoor fan motor
(1) Remove the top panel, cabinet and service panel.
(Refer to 1.)
(2) Disconnect the indoor/outdoor connecting wire and remove
the back panel. (Refer to 1.)
(3) Remove the inverter assembly. (Refer to 2.)
(4) Remove the propeller.
(5) Remove the screws fixing the fan motor. (Photo 7)
(6) Remove the fan motor. (Photo 7)
6. Removing the compressor and 4-way valve
(1) Remove the top panel, cabinet and service panel.
(Refer to 1.)
(2) Disconnect the indoor/outdoor connecting wire and remove
the back panel. (Refer to 1.)
(3) Remove the inverter assembly. (Refer to 2.)
(4) Recover gas from the refrigerant circuit.
(5) Detach the welded part of the suction and the discharge
pipe connected with compressor.
(6) Remove the nuts of compressor legs.
(7) Remove the compressor.
(8) Detach the welded part of pipes conneced with 4-way
valve. (Photo 8)
Photo 7
Photo 8
Propeller
Screws of
outdoor
fan motor
NOTE
● Before using a burner, reclaim gas from the pipes until the
pressure gauge shows 0 kg/cm
● Use the burner under the condition that gas can be recovered
even when the inner pressure rises by heat.
2
(0MPa).
Welded parts of 4-way valve
37
Page 38
13
CABINET
GRILLE
PROPELLER
BASE
BASE
COMPRESSOR
COMPRESSOR
COMPRESSOR RUBBER SET
STOP VALVE (GAS)
STOP VALVE (LIQUID)
SERVICE PANEL
BACK PANEL
EXPANSION VALVE
EXPANSION VALVE COIL
4-WAY VALVE
SEPARATOR
SEPARATOR
MOTOR SUPPORT
CONDENSER NET
TOP PANEL
OUTDOOR HEAT EXCHANGER
OUTDOOR HEAT EXCHANGER
OUTDOOR FAN MOTOR
DEFROST HEATER
HEATER PROTECTOR
CAPILLARY TUBE
250V/20A
3P
Including heat sink and RT64
Including heat sink and RT64
Remarks
Part No.
No.
Part Name
L61
21S4
RT61,RT62
RT65
F61
TB
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
MUZ-
A09YV-
E1
MUZ-
A09YVH-
E1
MUZ-
A12YV-
E1
MUZ-
A12YVH-
E1
MUZ-A09YV -MUZ-A12YV MUZ-A09YVH -MUZ-A12YVH -
13-2. OUTDOOR UNIT
ELECTRICAL PARTS
E1E1
E1E1
9
8
7
6
1
2
3
4
5
39
Page 40
MUZ-A09YV MUZ-A12YV -
E1
E1
13-3. DRAIN SOCKET
Outdoor unit {42 drain hole
1
Soft vinyl chloride hose of
25mm inside diameter.
Parts No.Parts Name
No.
1
E02 838 704
DRAIN SOCKET
Symbol
in Wiring
Diagram
Q'ty/unit
MUZ-A09YV-
E1
MUZ-A12YV-
11
E1
Remarks
HEAD OFFICE: MITSUBISHI DENKI BLDG., 2-2-3, MARUNOUCHI, CHIYODA-KU, TOKYO100-8310, JAPAN
CC
Copyright 2004 MITSUBISHI ELECTRIC ENGINEERING CO.,LTD
Distributed in Apr. 2004. No. OB328 REVISED EDITION-A 6
Distributed in Jan. 2004. No. OB328 6
Made in Japan
New publication, effective Apr. 2004
Specifications subject to change without notice.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.