Mitsubishi Electronics MUZ-A09-A12YV-H, MSZ-A09-A12YV User Manual

SG79Y281H07
English
SPLIT-TYPE AIR CONDITIONERS Models
MSZ-A09/A12YV MUZ-A09/A12YV(H)
INSTALLATION MANUAL
[FLARE CONNECTION TYPE]
1. THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR SAFETY
Please provide an exclusive circuit for the air conditioner and do not connect other
electrical appliances to it. Be sure to read THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR
SAFETY before installing the air conditioner. Be sure to observe the cautions specified here as they include important items
related to safety. The indications and meanings are as follows.
WARNING
Could lead to death, serious injury, etc.
CAUTION
Could lead to serious injury in particular environments when operated incorrectly.
After reading this manual, be sure to keep it together with the OPERATING
INSTRUCTIONS in a handy place on the customers site.
WARNING
Do not install the unit by yourself (customer).
Incomplete installation could cause injury due to fire, electric shock, the unit falling or leakage of water. Consult the dealer from whom you purchased the unit or special installer.
Install the unit securely in a place which can bear the weight of the unit.
When installed in an insufficient strong place, the unit could fall causing injury.
Use the specified wires to connect the indoor and outdoor units securely
and attach the wires firmly to the terminal block connecting sections so the stress of the wires is not applied to the sections.
Incomplete connecting and fixing could cause fire.
Do not use intermediate connection of the power cord or the extension
cord and do not connect many devices to one AC outlet.
It could cause a fire or an electric shock due to defective contact, defective insulation, exceeding the permissible current, etc.
Check that the refrigerant gas do not leak after installation has com-
pleted.
If refrigerant gas leaks indoors, and comes into contact with the fire of a fan heater, space heater, stove, etc., harmful substances will be generated.
Perform the installation securely referring to the installation manual.
Incomplete installation could cause a personal injury due to fire, electric shock, the unit falling or leakage of water.
Perform electrical work according to the installation manual and be sure
to use an exclusive circuit.
If the capacity of the power circuit is insufficient or there is incomplete electrical work, it could result in a fire or an electric shock.
Attach the electrical cover to the indoor unit and the service panel to the
outdoor unit securely.
If the electrical cover in the indoor unit and/or the service panel in the outdoor unit are not attached securely, it could result in a fire or an electric shock due to dust, water, etc.
Be sure to use the part provided or specified parts for the installation
work.
The use of defective parts could cause an injury or leakage of water due to a fire, an electric shock, the unit falling, etc.
Be sure to cut off the main power in case of setting up the indoor
electronic control P.C. board or wiring works.
It could cause an electric shock.
The appliance shall be installed in accordance with national wiring
regulations.
1
HFC
utilized
R410A
Series
When installing an MXZ series outdoor unit, refer to the MXZ type manual for outdoor unit set up.
CAUTION
Earth the unit.
Do not connect the earth to a gas pipe, water pipe, lightning rod or telephone earth. Defective earthing could cause an electric shock.
Do not install the unit in a place where an inflammable gas leaks.
If gas leak and accumulate in the area surrounding the unit, it could cause an explosion.
Install an earth leakage breaker depending on the installation place (Where it is humid).
If an earth leakage breaker is not installed, it could cause an electric shock.
Perform the drainage/piping work securely according to the installation manual.
If there is a defect in the drainage/piping work, water could drop from the unit and household goods could be wet and damaged.
Fasten a flare nut with a torque wrench as specified in this manual.
When fastened too tight, a flare nut may broken after a long period and cause a leakage of refrigerant.
2. SELECTING THE INSTALLATION LOCATION
2-1 INDOOR UNIT
Where airflow is not blocked.
Where cool air spreads over the entire room.
Maximum refrigerant piping length between indoor unit and outdoor unit is 20 m
and the difference of height of both units is 12 m. Rigid wall without vibration.
Where it is not exposed to direct sunshine.
Where easily drained.
At a distance 1 m or more away from your TV and radio. Operation of the air
conditioner may interfere with radio or TV reception in areas where reception is weak. An amplifier may be required for the affected device. In a place as far away as possible from fluorescent and incandescent lights (so
the infrared remote control can operate the air conditioner normally). Where the air filter can be removed and replaced easily.
2-2 OUTDOOR UNIT
Where it is not exposed to strong wind.
Where airflow is good and dustless.
Where it is not exposed to rain and direct sunshine.
Where neighbours are not annoyed by operation sound or hot air.
Where rigid wall or support is available to prevent the increase of operation sound
or vibration. Where there is no risk of combustible gas leakage.
When installing the unit at a high level, be sure to fix the unit legs.
Where it is at least 3 m away from the antenna of TV set or radio. Operation of the
air conditioner may interfere with radio or TV reception in areas where reception is weak. An amplifier may be required for the affected device. Install the unit horizontally.
Note:
It is advisable to make a piping loop near outdoor unit so as to reduce vibration transmitted from there.
CAUTION
Avoid the following places for installation where air conditioner trouble is liable to occur.
Where flammable gas could leak.
Where there is much machine oil.
Salty places such as the seaside.
Where sulfide gas is generated such as a hot spring.
Where there is high-frequency or wireless equipment.
2-3 WIRELESS REMOTE CONTROLLER MOUNTING
Place of mounting
Where it is easy to operate and easily visible.
Where children can not touch.
Mounting
Select a position about 1.2 m above the floor, check that signals from the remote controller are surely received by the indoor unit from that position (‘beep’ or ‘beep- beep receiving tone sounds). After that, attach remote controller holder 3 to a pillar or wall and set the wireless remote controller 6.
In rooms where inverter type fluorescent lamps are used, the signal from the wireless remote controller may not be received.
4. INDOOR UNIT INSTALLATION
4-1 FIXING OF INSTALLATION PLATE
Find a structural material (such as a stud) in the wall and fix installation plate
horizontally.
A09YV
102 mm or more
(off the wall)
A12YV
182 mm or more
(off the wall)
To prevent the installation plate from vibrating, be sure to fix the holes as indicated by the arrows c.
When bolts recessed in the concrete wall are to be utilized, secure the installation plate 1 using 11 × 20 · 11 × 26 oval hole (450 mm pitch). If the recessed bolt is too long, change it for a shorter one available in the market.
4-2 WALL HOLE DRILLING
1 Determine the wall hole position. 2 Drill a 75 mm hole so that outside can be lower than inside. 3 Insert the wall hole sleeve C.
Positioning of the holes on the wall
Be sure to use wall hole sleeve C to prevent the outdoor connecting wires from contacting with metal part in the wall and to prevent damage by rat in case the wall is hollow.
Wall hole sealing and fixing pipe to wall
Indoor unit
Wall hole sleeve C
Bind the line to the center hole.
Installation plate fixing screw 2 4 × 25 mm
Bind the line to the center hole.
Installation plate fixing screw 2 4 × 25 mm
Installation plate 1
Insert the scale.
Align the scale with the line.
Repeat the same procedure for the left hole.
Wall hole
75 mm dia.
(Indoor side)
(Wall hole cross section)
Wall hole cover D
Installation plate 1
Installation plate 1
Fix the pipe to wall with pipe fixing band E.
Plumb
Plumb
100 mm
Seal the wall hole gap with putty H.
79 mm or more 109 mm or more for left and left back piping (using spacer)
190 mm or more
(off the wall)
Align the plumb line with the mark
79 mm or more 109 mm or more for left and left back piping (using spacer)
182 mm or more
(off the wall)
Align the plumb line with the mark
Hole of dia. 75 mm
Wall thickness
One scale
Cut with 1 extra scale length.
Wall hole sleeve C
Cut off the extra length. Pipe fixing
Fixing screw F
.
.
band E
4-3 POWER SUPPLY AND CONNECTING WIRE SPECIFI-
CATIONS
Use special room air conditioning circuit.
Power supply cord length (Lead to left/Lead to right)
Indoor/outdoor unit connecting Cable 4-core 1.0 mm wire Specification with Design 245 IEC 57.
Take out power supply cord from the left or right bottom corner of the indoor unit.
Connect to the power switch which has a gap of 3 mm or more when open to interrupt the source power phase. (When the power switch is shut off, it must interrupt all phases.) (Rated Voltage/Frequency : 230 V/50 Hz) (Input capacity Main switch/Fuse:10 A) (This plug has to be the one meets the Standards.) Power supply cord
Never cut the indoor and outdoor unit connecting wire and connect it to other wires. It may cause a fire.
Do not bundle the spare wire, but put it as shown below.
Green/Yellow : Ground Blue : N Brown : L
WARNING
0.3 m/1 m
2
, in conformity
4-4 INDOOR AND OUTDOOR CONNECTING WIRE CON-
NECTION
You can connect indoor/outdoor lead wire without removing the front panel.
1 Open the front panel. 2 Remove one screw holding the electrical cover, then remove the cover. 3 Remove the VA clamp. 4 Pass the indoor/outdoor unit connecting wire from the back of the indoor unit and
process the end of the wire, then connect it to the terminal block.
5 Replace the fixture and electrical cover securely.
Indoor terminal block
Indoor/outdoor unit connecting wire A
Use the indoor/outdoor unit connecting wire that meets the Standards to connect
the indoor and outdoor units and fix the wire to the terminal block securely so that no external force is conveyed to the connecting section of the terminal block. Incomplete connection or fixing of the wire could result in a fire. Attach the electrical cover securely. If it is attached incorrectly, it could result in a
fire or an electric shock due to dust, water, etc.
Loosen terminal screw.
Terminal block
<Connection details>
VA clamp
Securely push the wire into the terminal block until no part of its core is appeared.
WARNING
15 mm
35 mm
Lead wire
Never fail to hook the left claw on the wire fixture to secure indoor/ outdoor unit connecting wire A.
MSZ
MUZ
L
23
N
N
3
2
ELECTRICAL COVER
Fixing screws
Power supply cord
Indoor terminal block
Earth wire (green/yellow)
Indoor/outdoor unit connecting wire A 4-core 1.0 mm
Outdoor terminal block
2
CAUTION
Be careful not to make mis-wiring.
Firmly tighten the terminal screws to prevent them from loosening.
After tightening, pull the wires lightly to confirm that they do not move.
If the connecting wire is incorrectly connected to the terminal block, the unit does
not operate normally. If an earth is incorrect, it may cause an electric shock.
4-5 AUTO RESTART FUNCTION
These models are equipped with an auto restart function. If you do not want to use
this function, please consult the service representative because the setting of the unit needs to be changed. When the indoor unit is controlled with the remote controller, the operation mode, the
set temperature, and the fan speed are memorized by the indoor electronic control P.C. board. The auto restart function sets to work the moment the power has restored after power failure, then, the unit will restart automatically. If the unit is operated in “I FEEL... or AUTO mode before power failure, the operation mode (COOL, DRY or HEAT) is not stored in the memory. When the main power is turned on, the unit decides the operation mode by the initial room temperature at restart and starts operation again.
Operation
1 If the main power has been cut, the operation settings remain. 2 When three minutes have passed after power was restored, the unit will restart
automatically according to the memory.
Notes:
The operation settings are memorized when 10 seconds have passed after the remote controller was operated.
If the main power is turned off or a power failure occurs while AUTO START/STOP timer is active, the timer setting is cancelled. As these models are equipped with an auto restart function, the air conditioner starts operating with timer cancelled at the same time that power is restored.
If the unit has been off with the remote controller before power failure, the auto restart function does not work as the power button of the remote controller is off.
To prevent breaker off due to the rush of starting current, systematize other home appliances not to turn on at the same time.
4-6 PIPE FORMING
Place the drain hose below the refrigerant piping.
Make sure that the drain hose is not heaved or snaked.
Do not pull the hose to apply the tape.
When the drain hose passes the room, be sure to wrap insulation material (obtain-
able at a store) around it. Wrap the felt tape 7 around the pipe and the drain hose, then put the pipe in the
back space of the indoor unit.
Drain hose
Felt tape 7
FOR REAR, RIGHT OR DOWNWARD PIPING
Pipe arrangement
Put the refrigerant piping and the drain hose together, then apply piping tape G to them.
Be careful drain hose is not heaved.
Cut off in case of right piping.
Insert the piping and the drain hose into the wall hole sleeve C, and hook the upper
part of the indoor unit on the installation plate 1. Check if the indoor unit is hooked securely on the installation plate 1 by moving the
unit to left and right. Thrust the lower part of the indoor unit into the installation plate 1.
Liquid pipe
Gas pipe
Indoor/outdoor unit connecting wire A
Firmly apply piping tape G from the end.
Cut off in case of downward piping.
FOR LEFT OR LEFT-REAR PIPING
Pipe arrangement
Put the refrigerant piping and the drain hose together, then apply felt tape 7 to them.
Be careful drain hose is not heaved.
Felt tape 7
Firmly apply felt tape 7 from the end. (Felt tape 7 overlap width should be 1/3 the tape width.)
REATTACHING DRAIN HOSE
Be sure to reattach the drain hose and the drain cap in case of left or left-rear piping. Otherwise, it could cause drops of water to drip down from the drain hose.
1
Pull out the drain cap at the rear right of the indoor unit.
Hold the convex section at the end and pull the drain cap.
2
Pull out the drain hose at the rear left of the indoor unit.
Hold the claw marked by the arrow and pull out the drain hose forward.
3
Put the drain cap into the section to which the drain hose is to be
Cut off in case of left piping.
Use a bandage stopper at the end of felt tape 7.
Drain cap
Drain hose
Drain cap
attached at the rear of the indoor unit.
Insert the screwdriver, etc. (not sharp-edged tool) into the hole at the end of the cap and insert the cap fully into the drain pan.
Drain cap
4
Insert the drain hose into the section to which the drain hose is to be attached at the rear right of the indoor unit.
Insert the drain hose fully into the drain pan. Check if the hose is hooked securely to the projection of its inserting part at the drain pan.
Drain hose
INDOOR UNIT INSTALLATION
Insert the drain hose into the wall hole sleeve C, and hook the upper part of
indoor unit on the installation plate 1. Then, move the unit to the very edge of the left side for putting the piping easily in the back space of the indoor unit. After that, cut a part of packing material, then roll it as shown below and use it as a spacer to hook on the back rib and lift the indoor unit.
Indoor unit packing cardboard
Cut the cardboard using
Fix the end with masking tape or tape affixed on the lower side of indoor unit.
Connect the refrigerant piping with the extension pipe B.
Thrust the lower part of the indoor unit into the installation plate 1.
Roll the cutting piece as shown in the right.
scissors or cutters.
Securely attach the spacer assembly in the concave part of the rib, taking care its direction is correct as shown in the figure right.
Spacer
4-7 DRAIN PIPING
The drain hose should point downward for easy drain flow. (Fig. 1)
Do not make drain piping as shown in Fig. 2 to 5.
Accumulated Downward slope
Water leakage
(Fig. 1) (Fig. 2) (Fig. 3)
Tip of drain hose dipped in water.
Water leakage
(Fig. 4) (Fig. 5)
If the drain hose provided with the indoor unit is too short, connect it with drain
hose I that should be provided at your site. If the extension drain hose has to pass through a room, be sure to wrap it with
commercially sold insulation.
Ditch
Do not raise.
Less than 50 mm gap
Water leakage
drain water
Waving
Drain hose
5. OUTDOOR UNIT INSTALLATION
5-1 INDOOR/OUTDOOR UNIT CONNECTING WIRE
CONNECTION
Connect the indoor/outdoor unit connecting wire A from the indoor unit correctly
on the terminal block. For future servicing, give extra length to connecting wire.
Peel off both ends of connecting wire (extension wire).
Be careful not to contact connecting wire with piping.
Make earth wire a little longer than the others.
(more than 35 mm)
For the indoor/outdoor unit connecting wires, be sure to use the ones in compli-
ance with the standards. Be sure to push the core until it is hidden and pull each cable to make sure that it
is not pulled up incomplete insertion may cause a risk of burning the terminal blocks.
Indoor and Outdoor connecting wire Specification
Cable 4-core 1.0 mm2, in conformity with Design 245 IEC 57.
35 mm
Air
Soft hose I.D. 15 mm or hard vinyl chloride
15 mm
WARNING
A means for disconnection of the supply with an isolation switch, or similar
device, in all active conductors shall be incorporated in the fixed wiring. Never cut the power cord and connect it to other wires.
It may cause a fire.
Power supply cord
Loosen terminal screw.
Lead wire
Terminal block
<Connection details>
Use care not to make mis-wiring.
Firmly tighten the terminal screws to prevent them from loosening.
After tightening, pull the wires lightly to confirm that they do not move.
If the connecting wire is incorrectly connected to the terminal block, the unit
does not operate normally.
Be sure to fix the indoor/outdoor unit connecting wire A using this cord clamp.
Be sure to attach the service panel of the outdoor unit securely. If it is not attached correctly, it could result in a fire or an electric shock due to dust, water, etc.
L
MSZ
MUZ
3
CAUTION
WARNING
N
N
2
Earth wire (green/yellow)
Indoor/outdoor unit connecting wire A 4-core 1.0 mm
Outdoor terminal block
Service panel
2
Remove one fixing screw to open the service panel.
Indoor terminal block
23
5-2 DRAIN PIPING FOR OUTDOOR UNIT
Provide drain piping before indoor and outdoor piping connection. (It will be hard to
install drain socket 9 if indoor and outdoor piping connection is conducted prior to drain piping as outdoor unit becomes immovable.) Connect the drain hose I (obtainable at a store, inside diameter: 15 mm) as
shown in the figure for drainage. Make sure to provide drain piping with a downhill grade for easy drain flow.
Drain hose I
Drain socket 9 (For YV type only)
Note:
Do not use the drain socket 9 in the cold region. Drain may freeze and it makes the fan stop.
3. INSTALLATION DIAGRAM & ACCESSORIES
FLARED CONNECTIONS
This unit has flared connections on both indoor and outdoor sides.
Remove the outdoor units valve cover, then connect the pipe.
Refrigerant pipes are used to connect the indoor and outdoor units.
Be careful not to crush or bend the pipe in pipe bending.
Limits
Pipe length 20 m max.
Height difference 12 m max.
No. of bends 10 max.
Refrigerant adjustment ... If pipe length exceeds 7 m, additional refrigerant
(R410A) charge is required. (The outdoor unit is charged with refrigerant for pipe length up to 7 m.)
Up to 7 m No additional charge is required.
Pipe length
Refrigerant to be added
Exceeding 7 m
ACCESSORIES
Check the following parts before installation. <Indoor unit>
1 Installation plate 1
2 Installation plate fixing screw 4 × 25 mm 7
3 Remote controller holder 1
4 Fixing screw for 3 3.5 × 16 mm (Black) 2
5 Battery (AAA) for remote controller 2
6 Wireless remote controller 1
7 Felt tape (Used for left or left-rear piping) 1
8 Air cleaning filter 2
<Outdoor unit: For YV type only>
9 Drain socket 1
PART TO BE PROVIDED AT YOUR SITE
Optional extension pipe
Indoor/outdoor unit connecting wire
A
(4-core 1.0 mm
B Extension pipe 1 C Wall hole sleeve 1 D Wall hole cover 1
Pipe fixing band (The quantity depends
E
on the pipe length.) Fixing screw for E 4 × 20 mm (The
F
quantity depends on the pipe length.)
G Piping tape 1 H Putty 1
Drain hose (or soft PVC. hose, 15 mm
I
inner dia. or hard PVC pipe VP16)
J Refrigeration oil 1
285 mm
344.5 mm
2-10 mm × 21 mm slot
Note:
When operating the air conditioner in low outside temperature, be sure to follow the instructions described below.
Never install the outdoor unit in a place where its air inlet/ outlet side may be exposed directly to wind.
To prevent exposure to wind, install the outdoor unit with its air inlet side facing the wall.
To prevent exposure to wind, it is recommended to install a baffle board on the air outlet side of the outdoor unit.
150 mm
2
)
800 mm
500 mm
Air inlet
Air outlet
Additional charge is required.
(Refer to the table below.)
30 g/m × (refrigerant piping length (m) -5)
79 mm or more
109 mm or more for left and left
79 mm or more
109 mm or more for left and left
1
2 to 5
2 to 5
1 or 2
304 - 325 mm
40 mm
8
100 mm
or more
PIPING PREPARATION
1 Specifications
Use the refrigerant pipes that meet the following specifications.
Pipe
For liquid 6.35 8
For gas 9.52 8
Use a copper pipe or a copper-alloy seamless pipe with a thickness of 0.8 mm. Never use any pipe with a thickness less than 0.8 mm, as the pressure resistance is insufficient.
2 Ensure that the 2 refrigerant pipes are insulated to prevent condensation. 3 Refrigerant pipe bending radius must be 100 mm or more.
Be sure to use the insulation of specified thickness. Excessive thickness may cause incorrect installation of the indoor unit and lack of thickness may cause dew drippage.
182 m
o
m
r m
ore
back piping (using spacer)
1
2
1
02 m
or m
m
ore
back piping (using spacer)
2
5
200 mm or more
Open two sides of left, right, or rear side.
1
8
Basically open 100 mm or more without any obstruction in front and on both sides of the unit.
(A12YV)
(A09YV)
6
7 mm or more
Outside diameter Insulation thickness
mm mm
Heat resisting foam plastic
0.045 specific gravity
CAUTION
Decide the installation position using mark on the installation plate indicating the indoor unit size as reference.
The figure refers to A09 YV.
182 m
m
or m
ore
Piping can be directed towards rear, right, downward, left or left-rear directions.
Rear side Right
190 m
m
or m
ore
D
H
7
C
3
G
4
F
100 mm or more
A
350 m
m
Units should be installed by licensed contractor according to local code requirement.
or m
E
I
B
ore
Rear
Downward
Separate the 2 connecting pipes and apply insulation individually.
8 mm thickness thermal insulation plastic
When the piping is to be attached to a wall containing metals (tin plated) or metal netting, use a chemically treated wooden piece 20 mm or thicker between the wall and the piping or wrap 7 to 8 turns of insulation vinyl tape around the piping.
Insulation material
Be careful the drain hose is not raised.
Front
Left-rear
Lock the catch.
Left
6. INDOOR/OUTDOOR UNIT CONNECTION FINISHING AND TEST RUN
INSTALLATION INFORMATION FOR THE AIR CONDI­TIONER WITH R410A REFRIGERANT
This room air conditioner adopts an HFC refrigerant (R410A) which will never destroy
the ozone layer. Pay particular attention to the following points, though the basic installation procedure
is same as that for R22 air conditioners.
1 As R410A has a working pressure approx. 1.6 times as high as that of R22, some
special tools and piping parts / materials are required. (Refer to the table below.)
2 Take sufficient care not to allow water and other contaminations to enter the
R410A refrigerant during storage and installation, since it is more susceptible to contaminations than R22.
3 For refrigerant piping, use clean, pressure-proof parts / materials specifically
designed for R410A. (Refer to 2. Refrigerant piping.)
4 Composition change may occur in R410A since it is a mixed refrigerant. When
charging, charge liquid refrigerant to prevent composition change.
6-1 Tools dedicated for the air conditioner with R410A
refrigerant
The following tools are required for R410A refrigerant. Some R22 tools can be substituted for R410A tools. The diameter of the service port on the stop valve in outdoor unit has been changed to prevent any other refrigerant being charged into the unit. (Cap size has been changed from 7/16 UNF with 20 threads to 1/2 UNF with 20 threads.)
R410A tools Can R22 tools be used? Description
R410A has high pressures beyond the meas-
Gauge manifold No Port diameters have been changed to prevent
Charge hose No
Gas leak detector No Dedicated for HFC refrigerant.
Torque wrench Yes 1/4 and 3/8
Flare tool Yes
Flare gauge New
Vacuum pump adaptor
Electronic scale for refrigerant charging
New
New
No: Not substitutable for R410A Yes: Substitutable for R410A
6-2 FLARING WORK
Main cause of gas leakage is defect in flaring work.
Carry out correct flaring work in the following procedure.
1
Pipe cutting
Cut the copper pipe correctly with pipe cutter.
Copper pipe
2
Burrs removal
Completely remove all burrs from the cut cross section of pipe.
Put the end of the copper pipe to downward direction as you remove burrs in order to
avoid to let burrs drop in the piping.
Burr
urement range of existing gauges.
any other refrigerant from being charged into the unit.
Hose material and cap size have been changed to improve the pressure resistance.
Clamp bar hole has been enlarged to reinforce the spring strength in the tool.
Provided for flaring work (to be used with R22 flare tool).
Provided to prevent the back flow of oil. This adapter enables you to use existing vacuum pumps.
It is difficult to measure R410A with a charging cylinder because the refrigerant bubbles due to high pressure and high-speed vaporization.
90°
Copper pipe
Good
Spare reamer
Pipe cutter
Tilted
No good
Uneven
Burred
3
Putting nut on
Remove flare nuts attached to indoor and outdoor units, then put them on pipe having completed burr removal. (not possible to put them on after flaring work)
Flare nut for R410A pipe differs from R22 pipe. Refer to the following table for detail.
mm inch R410A R22
ø6.35 1/4 17 17
ø9.52 3/8 22 22
4
Flaring work
Carry out flaring work using flaring tool as shown below.
Flaring tool
Die
Clutch type
Outside diameter Conventional flare tool
ø6.35 mm 0 to 0.5 1.0 to 1.5 1.5 to 2.0
ø9.52 mm 0 to 0.5 1.0 to 1.5 1.5 to 2.0
Firmly hold copper pipe in a die in the dimension shown in the table above.
5
Check
Compare the flared work with figure below.
If flare is noted to be defective, cut off the flared section and do flaring work again.
Wing nut type
Flare tool for R410A
clutch type
Smooth all around
Even length all around
Copper pipe
Flare nut
Copper pipe
A
York
Die
Flare nut
A (mm)
Clutch type Wing nut type
Inside is shining without any scratches.
Copper pipe
6-3 PIPE CONNECTION
Note:
Fasten a flare nut with a torque wrench as specified in the table below. When fastened too tight, a flare nut may broken after a long period and cause a leakage of refrigerant. 1 Indoor unit connection Connect both liquid and gas pipings to indoor unit.
Apply a thin coat of refrigeration oil J on the seat surface of pipe.
For connection first align the center, then tighten the first 3 to 4 turns of flare nut.
Use tightening torque table below as a guideline for indoor unit side union joint
section, and tighten using two wrenches. Excessive tightening damages the flare section.
Pipe diameter Tightening torque
mm N·m kgf·cm
ø6.35 13.7 to 17.7 140 to 180 ø9.52 34.3 to 41.2 350 to 420
2 Outdoor unit connection Connect pipes to stop valve pipe joint of the outdoor unit in the same manner applied for indoor unit.
For tightening, use a torque wrench or spanner and use the same tightening torque
applied for indoor unit.
INSULATION AND TAPING
1 Cover piping joints with pipe cover. 2 For outdoor unit side, surely insulate every piping including valves. 3 Using piping tape G, apply taping starting from the entry of outdoor unit.
Stop the end of piping tape G with tape (with adhesive agent attached).
When piping have to be arranged through above ceiling, closet or where the
temperature and humidity are high, wind additional commercially sold insulation for prevention of condensation.
6-4 PURGING PROCEDURES·LEAK TEST
PURGING PROCEDURES
Connect the refrigerant pipes (both liquid pipe and the gas pipe) between the indoor and the outdoor unit.
Remove the service port cap of the stop valve on the side of the outdoor unit gas pipe. (The stop valve will not work in it initial state fresh out of the factory (totally closed with cap on).)
Connect the gauge manifold valve and the vacuum pump to the service port of the stop valve on the gas pipe side of the outdoor unit.
Run the vacuum pump. (Vacuumize for more than 15 minutes.)
Check the vacuum with the gauge manifold valve, then close the gauge manifold valve, and stop the vacuum pump.
Leave as it is for one or two minutes. Make sure the pointer gauge manifold valve remains in the same position. Confirm that the pressure gauge shows–0.101 Mpa [Gauge] (–760 mmHg).
Handle Low
Window
Adapter for preventing the back flow
Compound pressure gauge (for R410A)
Pressure gauge (for R410A)
Gauge manifold valve (for R410A)
Handle High
Charge hose (for R410A)
Vacuum
(or the vacuum
pump
pump with the function to prevent the back flow)
Stop valve
*Close
*Open
Hexagonal wrench
*4 to 5 turns
Remove the gauge manifold valve quickly from the service port of the stop valve.
After refrigerant pipes are connected and evacuated, fully open all stop valves on both sides of gas pipe and liquid pipe. Operating without fully opening lowers the performance and this causes trouble.
Pipe length up to 7 m No gas charge is needed.
Cap for service port 13.7 to 17.7 140 to 180
Cap for stop valve 19.6 to 29.4 200 to 300
Stop valve
Service port
Tighten the cap to the service port to obtain the initial status.
Retighten the cap.
Leak test
N·m kgf·cm
-0.101MPa (-760 mmHg)
Stop valve
Charge hose (for R410A)
Pipe length exceeding 7 m Charge the prescribed amount of gas. (refer to 3)
Tightening torque
6-5 TEST RUN
Before performing the test run, recheck for any wrong wiring.
Wrong wiring prevents normal operation or results in blown fuse disabling operation. The test run can be started by pressing EMERGENCY OPERATION switch. When
the EMERGENCY OPERATION switch is once pressed, the unit will start the test run (continuous operation) for 30 minutes. A thermostat does not work during this time. After 30 minutes the unit will start the EMERGENCY OPERATION at a fixed temperature setting of 24 °C in COOL MODE. Perform test run in the following procedure.
Note:
Insert the power supply plug into the power outlet and/or turn on the breaker. Check that both of the operation indicator lamps are not lit. If they are blinking, the horizontal vanes are not installed correctly. In this case, disconnect the power supply plug and/or turn off the breaker, and then reinstall the horizontal vanes. (See the OPERATING INSTRUCTIONS page 11.)
Click.
Horizontal vanes
PROCEDURE
Press the EMERGENCY OPERATION switch.
1 Press it once, and after test run for 30 minutes the EMERGENCY COOL MODE starts.
If the left side lamp of the operation indicator blinks every 0.5 seconds, inspect the indoor/outdoor unit connecting wire A for mis-wiring.
2 Press it once more, and the EMERGENCY HEAT MODE starts. 3 Press it once more, and the operation stops.
(The operation mode changes in order of 1 ~ 3 every time the EMERGENCY OPERATION switch is pressed.)
Mode
Operation Indicator lamp
1
COOL
2
HEAT
STOP
3
In starting the heating operation, indoor unit fan may not operate to prevent blowing
cool air. Please wait for a few minutes until the temperature of heat exchanger rises and warm air blows out.
(Light) (Off)
(Off) (Light)
(Off) (Off)
EMERGENCY OPERATION switch
Checking the remote (infrared) signal reception
Press the ON/OFF button on the remote controller and check that an electronic sound is heard from the indoor unit. Press the ON/OFF button again to turn the air conditioner off.
If the indoor unit is operated with the remote controller, both the test run and the emergency operation are released by commands from the remote controller.
Once the compressor stops, the restart preventive device operates so the compressor
will not operate for three minutes to protect the air conditioner.
6-6 EXPLANATION TO THE CUSTOMER
Using the OPERATING INSTRUCTIONS, explain the following to the customer, how to
control temperature, how to remove the air filters, how to remove or put the remote controller in the remote controller holder, how to clean, precautions for operation, etc. Recommend the customer to read the OPERATING INSTRUCTIONS carefully.
7. FOR MOVEMENT AND MAINTENANCE
7-1 HOW TO INSTALL THE FRONT PANEL
1 Before installing the front panel, set the horizontal vane to the position as shown
below.
2 Insert the bottom of the front panel under the horizontal vane. 3 Set the top of the front panel. 4 Push as the arrow mark on the front panel to fix it to the air conditioner.
1 Horizontal vane
Slightly downward
Horizontal vane
7-2 REMOVING THE INDOOR UNIT
Remove the bottom of the indoor unit from the installation plate.
When releasing the corner part
Release both left and right bottom corner part of indoor unit and pull it downward and forward as below to release the hooks.
If the above method cannot be used
Remove the front panel and insert hexagonal wrenches into the square holes on the left and right as shown in the figure below, then push them up; the bottom of the indoor unit is lowered and the hooks are released.
Push
Square hole
3
2
Lower
7-3 GAS CHARGE
1 Connect gas cylinder to the service port of stop valve (3-way). 2 Execute air purge of the pipe (or hose) coming from refrigerant gas cylinder. 3 Replenish specified amount of the refrigerant, while operating the air conditioner
for cooling.
Note:
In case of adding refrigerant, comply with the quantity specified for the refrigerating cycle.
CAUTION
Do not discharge the refrigerant into the atmosphere.
Take care not to discharge refrigerant into the atmosphere during installation, reinstallation, or repairs to the refrigerant circuit.
For additional charging, charge the refrigerant from liquid phase of the
gas cylinder.
If the refrigerant is charged from the gas phase, composition change may occur in the refrigerant inside the cylinder and the outdoor unit. In this case, ability of the refrigerating cycle decreases or normal operation can be impossible. However, charging the liquid refrigerant all at once may cause the compressor to be locked. Thus, charge the refrigerant slowly.
To maintain the high pressure of the gas cylinder, warm the gas cylinder with warm water (under 40°C) during cold season. But never use naked fire or steam.
Union
Indoor unit
Refrigerant gas cylinder operating valve
This product is designed and intended for use in the residential, commercial and light-industrial environment.
The product at hand is based on the following EU regulations:
HEAD OFFICE: MITSUBISHI DENKI BLDG., 2-2-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
Liquid pipe
Gas pipe
Gauge manifold valve (for R410A)
Charge hose (for R410A)
Refrigerant gas cylinder for R410A with siphon
Refrigerant (liquid)
Electronic scale for refrigerant charging
• Low Voltage Directive 73/23/ EEC
• Electromagnetic Compatibility Directive 89/336/ EEC
Stop valve
Outdoor unit
Service port
Loading...