Mitsubishi MUH-A07YV - E1, MUH-A09YV - E1, MUH-A12YV - E1 Service Manual

Page 1
SERVICE MANUAL
HFC
utilized
R410A
SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
Revision A:
MUH-A12YV - can be connected to MCFH-A12WV - .
Please void OB331.
E1
E1
No. OB331
REVISED EDITION-A
MUH-A07YV ­MUH-A09YV ­MUH-A12YV -
Indication of model name
MUH-A07YV ­MUH-A09YV ­MUH-A12YV -
E1
E1
E1
CONTENTS
1. TECHNICAL CHANGES ····································2
2. PART NAMES AND FUNCTIONS······················5
3. SPECIFICATION·················································5
4. NOISE CRITERIA CURVES·······························6
5. OUTLINES AND DIMENSIONS·························7
6. WIRING DIAGRAM ············································7
E1
7. REFRIGERANT SYSTEM DIAGRAM················8
E1
8. PERFORMANCE CURVES································9
E1
9. MICROPROCESSOR CONTROL ····················22
10. SERVICE FUNCTIONS·····································24
11. TROUBLESHOOTING ······································24
12. DISASSEMBLY INSTRUCTIONS·····················31
13. PARTS LIST······················································34
NOTE:
•This manual describes technical data of outdoor units.
•As for indoor units MSC-A07/A09/A12YV - , refer to the service manual OB329.
•As for indoor unit MCFH-A12WV - , refer to the service manual OB336.
E1
E1
Page 2
Refrigerating
oil
Refrigerant
New refrigerant
R410A
HFC-32: HFC-125 (50%:50%)
Pseudo-azeotropic refrigerant
Not included
A1/A1
72.6
-51.4
1.557 64
Non combustible
0
1730
From liquid phase in cylinder
Possible
Incompatible oil
Non Non
Previous refrigerant
R22
R22 (100%)
Single refrigerant
Included
A1
86.5
-40.8
0.94
44.4
Non combustible
0.055 1700
Gas phase
Possible
Compatible oil
Light yellow
Non
Refrigerant Composition (Ratio) Refrigerant handling Chlorine Safety group (ASHRAE) Molecular weight Boiling point (:) Steam pressure [25:](Mpa) Saturated steam density [25:](Kg/K) Combustibility ODP w1 GWP w2 Refrigerant charge method Additional charge on leakage Kind Color Smell
w1:Ozone Destruction Parameter : based on CFC-11 w2 :Global Warmth Parameter : based on CO
2
Revision A:
•MUH-A12YV - can be connected to MCFH-A12WV - . SPECIFICATION, PERFORMANCE CURVES and TROUBLESHOOTING have been added.
E1E1
1
MUH-A07WV- ➔MUH-A07YV-
1. Outdoor heat exchanger has changed.
2. Outdoor fan motor has changed. (RA6V23-FB➔RC6V20-AB)
MUH-A09WV- MUH-A09YV­MUH-A12WV- MUH-A12YV-
1. Outdoor heat exchanger has changed.
2. Outdoor fan motor has changed. (RA6V33-DB➔RA6V33-FB)
TECHNICAL CHANGES
E1E1
E1E1
E1E1
INFORMATION FOR THE AIR CONDITIONER WITH R410A REFRIGERANT
• This room air conditioner adopts an HFC refrigerant (R410A) which never destroys the ozone layer.
• Pay particular attention to the following points, though the basic installation procedure is same as that for R22 conditioners. 1 As R410A has working pressure approximate 1.6 times as high as that of R22, some special tools and piping parts/
materials are required. Refer to the table below.
2 Take sufficient care not to allow water and other contaminations to enter the R410Arefrigerant during storage and
installation, since it is more susceptible to contaminations than R22.
3 For refrigerant piping, use clean, pressure-proof parts/materials specifically designed for R410A. (Refer to 2. Refrigerant
piping.)
4 Composition change may occur in R410A since it is a mixed refrigerant. When charging, charge liquid refrigerant to prevent
composition change.
2
Page 3
R410A tools Can R22 tools be used?
Gas leak detector
R410A has high pressures beyond the measurement range of existing gauges. Port diameters have been changed to prevent any other refrigerant from being charged into the unit.
Hose material and cap size have been changed to improve the pressure resistance.
Dedicated for HFC refrigerant.
6.35 mm and 9.52 mm
Description
Clamp bar hole has been enlarged to reinforce the spring strength in the tool. Provided for flaring work (to be used with R22 flare tool).
Provided to prevent the back flow of oil. This adapter enables you to use vacuum pumps.
It is difficult to measure R410A with a charging cylinder because the refrigerant bubbles due to high pressure and high-speed vaporization
No
No
No
Yes
Yes
New
New
New
Gauge manifold
Charge hose
Torque wrench
Flare tool Flare gauge
Vacuum pump adapter
Electronic scale for refrigerant charging
No : Not Substitutable for R410A Yes : Substitutable for R410A
No 12.7 mm
NOTE : The unit of pressure has been changed to MPa on the international system of units(SI unit system).
New Specification Current Specification
The incompatible refrigerating oil easily separates from refrigerant and is in the upper layer inside the suction muffler. Raising position of the oil back hole enables to back the refrigerating oil of the upper layer to flow back to the compressor.
Since refrigerant and refrigerating oil are compatible each, refrigerating oil backs to the compressor through the lower position oil back hole.
Compressor
Suction muffler
Oil back hole
Refrigerating oil
Refrigerant
Compressor
Suction muffler
Oil back hole
Refrigerating oil /Refrigerant
Compressor
The conversion factor is: 1(MPa [Gauge]) =10.2(kgf/ff[Gauge])
Conversion chart of refrigerant temperature and pressure
(MPa [Gauge])
4.0
3.5
3.0
2.5
2.0
1.5
1.0
0.5
Saturated liquid pressure
0.0
-0.5
-30 -20 -10 0 10 20
R410A R22
30
40 50 60
1.Tools dedicated for the air conditioner with R410A refrigerant
The following tools are required for R410A refrigerant. Some R22 tools can be substituted for R410A tools. The diameter of the service port on the stop valve in outdoor unit has been changed to prevent any other refrigerant being charged into the unit. Cap size has been changed from 7/16 UNF with 20 threads to 1/2 UNF with 20 threads.
NOTE : The unit of pressure has been changed to MPa on the
international system of units(SI unit system).
The conversion factor is: 1(MPa [Gauge]) =10.2(kgf/
(:)
3
ff
[Gauge])
Page 4
R410A
Pipe diameter
mm
6.35
9.52
12.7
17 22 26
Dimension of flare nut
R22
17 22 24
Electronic scale for refrigerant charging
Outdoor unit
Refrigerant gas cylinder operating valve
Refrigerant gas cylinder for R410A with siphon
Refrigerant (liquid)
Service port
Gauge manifold valve (for R410A)
Union
Liquid pipe Gas pipe
Stop valve
Indoor unit
Charge hose (for R410A)
2.Refrigerant piping
Wall thickness
Outside diameter
Pipe
mm
For liquid For gas
6.35
9.52
12.7
0.8 mm
0.8 mm
0.8 mm
Heat resisting foam plastic Specific gravity 0.045 Thickness 8 mm
Insulation material
1 Specifications
Use the refrigerant pipes that meet the following specifications.
• Use a copper pipe or a copper-alloy seamless pipe with a thickness of 0.8 mm. Never use any pipe with a thickness less than 0.8mm, as the pressure resistance is insufficient.
2 Flaring work and flare nut
Flaring work for R410A pipe differs from that for R22 pipe. For details of flaring work, refer to Installation manual “FLARING WORK”.
3.Refrigerant oil
Apply the special refrigeration oil (accessories: packed with indoor unit) to the flare and the union seat surfaces.
4.Air purge
• Do not discharge the refrigerant into the atmosphere. Take care not to discharge refrigerant into the atmosphere during installation, reinstallation, or repairs to the refrigerant
circuit.
• Use the vacuum pump for air purging for the purpose of environmental protection.
5.Additional charge
For additional charging, charge the refrigerant from liquid phase of the gas cylinder. If the refrigerant is charged from the gas phase, composition change may occur in the refrigerant inside the cylinder and the outdoor unit. In this case, ability of the refrigerating cycle decreases or normal operation can be impossible. However, charging the liquid refrigerant all at once may cause the compressor to be locked. Thus, charge the refrigerant slowly.
4
Page 5
2
Air inlet
Piping
Drain hose
Air outlet
Drain outlet
(back and side)
Drain socket Drain cap
1 2
<Outdoor unit: MUH type>
1
2
Capacity Dehumidification Outdoor air flow Power outlet Running current Power input Auxiliary heater Power factor Starting current Compressor motor current Fan motor current
Model Output Winding resistance (at 20:) Model Winding resistance (at 20:) Dimensions WOHOD Weight Sound level Fan speed Fan speed regulator Refrigerant filling capacity (R410A) Refrigerating oil (Model) Thermistor RT61 (at 0:)
kW
R/h
K /h
A A
W
A(kW)
%
A A A
W
"
"
mm
kg
dB
rpm
kg cc
k"
MUH-A07YV -
E1
Single phase
230V,50Hz
1,686
10
23
0.22
RN092VHSHT
600 C-R 3.87 C-S 6.14
RC6V20-AB
WHT-BLK 410
BLK-RED 433 780o540o255
35 47
735
1
0.62
350 (NEO22)
33.18
Cooling
2.3
0.9
3.00 680
98
2.78
3.22
Heating
2.5 —
2.86 655
99
2.64
3.62
MUH-A09YV - E1
Single phase
230V,50Hz
1,710
10
24
0.31
RN104VHSHT
700 C-R 3.40 C-S 4.56
RA6V33-FB
WHT-BLK 223
BLK-RED 228 780o540o255
38 49
825
1
1.00
350 (NEO22)
33.18
Cooling
2.55
1.1
3.32 760
99
3.01
3.21
Heating
3.05 —
3.52
805
99
3.21
3.69
MUH-A12YV -
E1
Indoor model
MSC-A12YV -
E1
Single phase
230V,50Hz
1,710
10
29
0.31
RN135VHSHT
900 C-R 2.79 C-S 3.36
RA6V33-FB
WHT-BLK 223
BLK-RED 228 780o540o255
40 49
825
1
1.00
620 (NEO22)
33.18
Cooling
3.5
1.7
4.65
1,050
98
4.34
3.21
Heating
3.9 —
4.60
1,040
98
4.29
3.61
Compressor
Electrical
data
Fan
motor
Special
remarks
Capacity
Coefficient of performance (C.O.P)
Outdoor unit power supply
Function
Outdoor model
MUH-A12YV -
E1
Indoor model
MCFH-A12WV -
E1
Single phase
230V,50Hz
1,710
10
29
0.31
RN135VHSHT
900 C-R 2.79 C-S 3.36
RA6V33-FB
WHT-BLK 223
BLK-RED 228 780o540o255
40 49
825
1
1.00
620 (NEO22)
33.18
Cooling
3.5
1.5
4.85
1,094
98
4.54
3.02
Heating
3.7 —
4.23 954
98
3.92
3.63
PART NAMES AND FUNCTIONS
OUTDOOR UNIT
MUH-A07YV ­MUH-A09YV ­MUH-A12YV -
3
SPECIFICATION
E1
E1
E1
ACCESSORIES
MUH-A07YV­MUH-A09YV­MUH-A12YV-
E1
E1
E1
NOTE: Test conditions are based on ISO 5151.
Cooling : Indoor DB27°C WB19°C Heating : Indoor DB20°C Indoor-Outdoor piping length : 5m
5
Outdoor DB35°C WB24°C Outdoor DB 7°C/WB 6°C
Page 6
4
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
APPROXIMATE TERESHOLD OF HEARING FOR CONTINUOUS NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
Test conditions, Cooling :DB35: WB24:
Heating :DB 7: WB 6:
MUH-A09YV- E1 MUH-A12YV- E1
COOL
FUNCTION
49
HEAT
SPL(dB
(A)) LINE
OUTDOORUNIT
MICROPHONE
1m
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
APPROXIMATE TERESHOLD OF HEARING FOR CONTINUOUS NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
Test conditions,
Cooling :DB35: WB24: Heating :DB 7: WB 6:
MUH-A07YV- E1
COOL
FUNCTION
47
HEAT
SPL(dB
(A)) LINE
NOISE CRITERIA CURVES
6
Page 7
5
SYMBOL
T61
TB1,TB2
21S4
52C
SYMBOL
MF
NR61 RT61
SR61,SR62
SYMBOL
C1
C65
DSAR
F61
MC
NAME
NAME NAME COMPRESSOR CAPACITOR OUTDOOR FAN CAPACITOR SURGE ABSORBER FUSE(2A) COMPRESSOR(INNER PROTECTOR)
VARISTOR DEFROST THERMISTOR SOLID STATE RELAY
TRANS FORMER TERMINAL BLOCK R.V. COIL COMPRESSOR CONTACTOR
OUTDOOR FAN MOTOR (INNER FUSE/INNER PROTECTOR)
OUTLINES AND DIMENSIONS
MUH-A07YV - MUH-A09YV - MUH-A12YV -
OUTDOOR UNIT
32
109
Air in
Drainage 3holes [33
540
260
40
10
320
Air in
147
122
110
Air out
500 780
74
255
285
155
320
25
90
E1E1E1
REQUIRED SPACE
100mm or more
104
100mm or more
400mm or more
Service panel
Liquid refrigerant pipe joint Refrigerant pipe (flared) [6.35
35-
43-
Gas refrigerant pipe joint Refrigerant pipe (flared) [9.52 (MUH-A07/A09YV [12.7 (MUH-A12YV
Unit: mm
100mm or more
350mm or more
)
)
6
WIRING DIAGRAM
MUH-A07YV ­MUH-A09YV ­MUH-A12YV -
OUTDOOR UNIT
E1
E1
E1
TO INDOOR UNIT CONNECTING 12V
CIRCUIT BREAKER
POWER SUPPLY ~/N
50Hz
230V
MODELS WIRING DIAGRAM
DSAR
RT61
1 2 3
TAB20
CN661
CN730
F61
PE
TB2
3 N
TB1
L
N
GRN/YLW
RED BLK
BRN
BRN
BLU
BLU
T61
4
21S4
CN721
NR61
52C
3
DEICER P.C.BOARD
C1
RED BLK
SR62
SR61
WHT
S
CN711
1 2 3
C65
C
MC
MF
WHT BLK RED
R
NOTE:1. About the indoor side electric wiring refer to the indoor unit electric wiring diagram for servicing.
2. Use copper conductors only. (For field wiring)
3. Symbols below indicate.
/: Terminal block, : Connector
7
Page 8
7
REFRIGERANT SYSTEM DIAGRAM
MUH-A07YV ­MUH-A09YV -
E1
E1
OUTDOOR UNIT
Refrigerant pipe [ 9.52
(with heat insulator)
Flared connection
Flared connection
Refrigerant pipe [6.35
(with heat insulator)
Stop valve (with service port)
Strainer #100
Stop valve
4-way valve
Defrost thermistor RT61
Muffler
Compressor
Capillary tube
[3.0x[1.4x500(MUH-A07YV) [3.0x[1.4x600(MUH-A09YV)
Check valve
Capillary tube
[3.0x[1.4x600(MUH-A07YV) [3.0x[1.4x1000(MUH-A09YV)
Refrigerant flow in cooling Refrigerant flow in heating
Unit:mm
Outdoor heat exchanger
Capillary tube [3.0x[1.4x800(2 pcs)
(MUH-A07YV) [3.0x[1.4x500(2 pcs)
(MUH-A09YV)
R.V. coil heating ON cooling OFF
MUH-A12YV -
E1
OUTDOOR UNIT
Refrigerant pipe [12.7
(with heat insulator)
Flared connection
Flared connection
Refrigerant pipe [6.35
(with heat insulator)
4-way valve
Stop valve (with service port)
Strainer #100
Stop valve
Muffler
Compressor
Capillary tube [3.0x[1.6x1050
Check valve
Defrost thermistor RT61
Unit:mm
Outdoor heat exchanger
Capillary tube [3.0x[1.4x500(2pcs)
Capillary tube [3.0x[1.6x600
R.V. coil heating ON cooling OFF
Refrigerant flow in cooling Refrigerant flow in heating
8
Page 9
MAX. REFRIGERANT PIPING LENGTH
Refrigerant piping
Model
Max. length : m
A
Piping size O.D : mm Length of connecting pipe : m Gas
Liquid
Indoor unit
Outdoor unit
MUH-A07YV - E1 MUH-A09YV - E1
MUH-A12YV - E1
20
25
9.52
12.7
MAX. HEIGHT DIFFERENCE
Indoor unit
Height difference should be within 10m regardless of which unit, indoor or outdoor position is high.
w Max. Height difference 10m
ADDITIONAL REFRIGERANT CHARGE(R410A : g)
Model
MUH-A07YV - E1
Outdoor unit precharged
7m
620
Gas 0.43
6.35 Liquid 0.5
Refrigerant Piping
Max.length
A
Refrigerant piping length (one way)
10m
15m
20m
Gas 0
Liquid 0
Outdoor unit
25m
MUH-A09YV - E1 MUH-A12YV - E1
8
PERFORMANCE CURVES
1000
0
MUH-A07YV - MUH-A09YV - MUH-A12YV -
The standard data contained in these specifications apply only to the operation of the air conditioner under normal conditions, since operating conditions vary according to the areas where these units are installed. The following information has been pro­vided to clarify the operating characteristics of the air conditioner under the conditions indicated by the performance curve.
60
E1E1E1
160
Calculation : Xg=20g/m 5 x(A-7)m
260
360
(1) GUARANTEED VOLTAGE
198~264V
(2) AIR FLOW
Air flow should be set at MAX.
(3) MAIN READINGS
(1) Indoor intake air wet-bulb temperature : °CWB (2) Indoor outlet air wet-bulb temperature : °CWB (3) Outdoor intake air dry-bulb temperature : °CDB (4) Total input: W (5) Indoor intake air dry-bulb temperature : °CDB (6) Outdoor intake air wet-bulb temperature : °CWB (7) Total input : W Indoor air wet/dry-bulb temperature difference on the left side of the chart on page 10 shows the difference between the indoor intake air wet/dry-bulb temperature and the indoor outlet air wet/dry-bulb temperature for your reference at service.
}
}
Cooling
Heating
9
Page 10
MSC-A07YV - E1
MUH-A07YV - E1
MUH-A12YV - E1
MSC-A12YV - E1
MUH-A09YV - E1
MSC-A09YV - E1
8.5
7.8
7.1
6.4
5.8
5.1
9.6
8.8
8.0
7.2
6.5
5.7
11.0
10.0
9.1
8.2
7.4
6.5
8.7
8.0
7.3
6.6
5.9
5.3
MUH-A12YV - E1
MCFH-A12WV - E1
20.4
18.8
17.2
15.7
14.1
12.5
11.0
9.4
19.2
17.8
16.3
14.8
13.3
11.8
10.4
8.9
MSC-A07YV - E1
MUH-A07YV - E1
MUH-A09YV - E1
MSC-A09YV - E1
MUH-A12YV - E1
MSC-A12YV - E1
25.2
23.3
21.4
19.4
17.5
15.5
13.6
11.7
MUH-A12YV - E1
MCFH-A12WV - E1
18.6
17.2
15.7
14.3
12.9
11.5
10.0
8.6
How to measure the indoor air wet-bulb/dry-bulb temperature difference
1. Attach at least 2 sets of wet-and dry-bulb thermometers to the indoor air intake as shown in the figure, and at least 2 sets of wet-and dry-bulb thermometers to the indoor air outlet. The thermometers must be attached to the position where air speed is high.
2. Attach at least 2 sets of wet-and dry-bulb thermometers to the outdoor air intake. Cover the thermometers to prevent direct rays of the sun.
3. Check that the air filter is cleaned.
4. Open windows and doors of room.
5. Press the EMERGENCY OPERATION switch once(twice) to start the EMERGENCY COOL
(HEAT) MODE.
6. When system stabilizes after more than 15 minutes, measure temperature and take an average temperature.
7. 10 minutes later, measure temperature again and check that the temperature does not change.
INDOOR UNIT
Wet-and dry-bulb thermometers
8-1.CAPACITY AND THE INPUT CURVES
OUTDOOR UNIT
Wet-and dry-bulb thermometers
NOTE:The above curves are for the heating operation without any frost.
10
Page 11
8-2.OUTDOOR LOW PRESSURE AND OUTDOOR UNIT CURRENT
18 32
230V
15 20
50
25 60
30
70(%)
35(:)
0.7
0.8
0.9
1.0
1.1
1.2
1.3
7
8
9
10
11
12
13
15 20
50
25 60
30 70(%)
35(:)
1
2
4
3
18 32
230V
18 32
230V
15 20
50
25 6030 70(%)
35(:)
0.7
0.8
0.9
1.0
1.1
1.2
1.3
7
8
9
10
11
12
13
15 20
50
25 60
30 70(%)
35(:)
1
2
4
3
18 32
230V
18 32
230V
15 20
50
25 60
30
70(%)
35(:)
0.7
0.8
0.9
1.0
1.1
1.2
1.3
7
8
9
10
11
12
13
15 20
50
25 60
30 70(%)
35(:)
2
3
5
4
18 32
230V
COOL operation
Both indoor and outdoor unit are under the same temperature/humidity condition.
Dry-bulb temperature
20 25
Relative humidity(%)
50 60
30 70
Air flow should be set at MAX.
The unit of pressure has been changed to MPa on the international system of units(SI unit system).
The conversion factor is : 1(MPa[Gauge]) =10.2(kgf/ff[Gauge] )
(kgf/F[Gauge])(MPa[Gauge])
Outdoor low pressure
(kgf/F[Gauge])(MPa[Gauge])
MUH-A07YV -
Ambient temperature(˚C) Ambient humidity(%)
MUH-A09YV -
E1
MUH-A07YV -
Outdoor unit current (A)
Ambient temperature(˚C) Ambient humidity(%)
E1
MUH-A09YV -
E1
E1
(kgf/F[Gauge])(MPa[Gauge])
Outdoor low pressure
Ambient temperature(˚C) Ambient humidity(%)
MUH-A12YV ­( Indoor unit : MSC-A12YV - )
Outdoor low pressure
Ambient temperature(˚C) Ambient humidity(%)
Outdoor unit current (A)
Ambient temperature(˚C) Ambient humidity(%)
E1
E1
MUH-A12YV ­( Indoor unit : MSC-A12YV - )
E1
E1
Outdoor unit current (A)
Ambient temperature(˚C) Ambient humidity(%)
11
Page 12
7
21
230V
(:)
5 10152025
3
4
5
6
7
21
230V
(:)
5 10152025
2
3
4
5
7
21
230V
(:)
5 10152025
2
3
4
5
18 32
230V
15 20
50
25 6030 70(%)
35(:)
3
4
5
6
(kgf/F[Gauge])(MPa[Gauge])
7
21
230V
(:)
5 10152025
3
4
5
6
1.3
13
1.2
12
1.1
11
1.0
10
0.9
9
Outdoor low pressure
0.8
8
0.7
7
15 20
HEAT operation
Condition indoor:Dry bulb temperature 20.0°C
MUH-A12YV -
E1
( Indoor unit : MCFH-A12WV - )
230V
18 32
50
Ambient temperature(˚C) Ambient humidity(%)
Wet bulb temperature 14.5°C
25 6030 70
35(:)
(%)
MUH-A12YV -
E1
( Indoor unit : MCFH-A12WV - )
E1
Outdoor unit current (A)
Ambient temperature(˚C) Ambient humidity(%)
Outdoor:Dry bulb temperature 7,15,20°C
Wet bulb temperature 6,12,14.5°C
E1
MUH-A07YV -
E1
MUH-A09YV -
E1
Outdoor unit current (A)
Ambient temperature(˚C)
MUH-A12YV ­( Indoor unit : MSC-A12YV - )
Outdoor unit current (A) Outdoor unit current (A)
E1
E1
Outdoor unit current (A)
Ambient temperature(˚C)
Ambient temperature(˚C)
MUH-A12YV ­( Indoor unit : MCFH-A12WV - )
E1
E1
Ambient temperature(˚C)
12
Page 13
PERFORMANCE DATA
21 18 2.70 1.51 0.56 572 2.59 1.45 0.56 601 2.48 1.39 0.56 629 2.39 1.34 0.56 658 21 20 2.82 1.24 0.44 601 2.70 1.19 0.44 636 2.62 1.15 0.44 651 2.53 1.11 0.44 679 22 18 2.70 1.62 0.60 572 2.59 1.55 0.60 601 2.48 1.49 0.60 629 2.39 1.44 0.60 658 22 20 2.82 1.35 0.48 601 2.70 1.30 0.48 636 2.62 1.26 0.48 651 2.53 1.21 0.48 679 22 22 2.93 1.06 0.36 622 2.83 1.02 0.36 661 2.76 0.99 0.36 679 2.65 0.95 0.36 708 23 18 2.70 1.73 0.64 572 2.59 1.66 0.64 601 2.48 1.59 0.64 629 2.39 1.53 0.64 658 23 20 2.82 1.47 0.52 601 2.70 1.41 0.52 636 2.62 1.36 0.52 651 2.53 1.32 0.52 679 23 22 2.93 1.17 0.40 622 2.83 1.13 0.40 661 2.76 1.10 0.40 679 2.65 1.06 0.40 708 24 18 2.70 1.84 0.68 572 2.59 1.76 0.68 601 2.48 1.69 0.68 629 2.39 1.63 0.68 658 24 20 2.82 1.58 0.56 601 2.70 1.51 0.56 636 2.62 1.47 0.56 651 2.53 1.42 0.56 679 24 22 2.93 1.29 0.44 622 2.83 1.24 0.44 661 2.76 1.21 0.44 679 2.65 1.16 0.44 708 24 24 3.08 0.99 0.32 651 2.97 0.95 0.32 686 2.90 0.93 0.32 708 2.81 0.90 0.32 744 25 18 2.70 1.95 0.72 572 2.59 1.86 0.72 601 2.48 1.79 0.72 629 2.39 1.72 0.72 658 25 20 2.82 1.69 0.60 601 2.70 1.62 0.60 636 2.62 1.57 0.60 651 2.53 1.52 0.60 679 25 22 2.93 1.41 0.48 622 2.83 1.36 0.48 661 2.76 1.32 0.48 679 2.65 1.27 0.48 708 25 24 3.08 1.11 0.36 651 2.97 1.07 0.36 686 2.90 1.04 0.36 708 2.81 1.01 0.36 744 26 18 2.70 2.05 0.76 572 2.59 1.97 0.76 601 2.48 1.89 0.76 629 2.39 1.82 0.76 658 26 20 2.82 1.80 0.64 601 2.70 1.73 0.64 636 2.62 1.68 0.64 651 2.53 1.62 0.64 679 26 22 2.93 1.52 0.52 622 2.83 1.47 0.52 661 2.76 1.44 0.52 679 2.65 1.38 0.52 708 26 24 3.08 1.23 0.40 651 2.97 1.19 0.40 686 2.90 1.16 0.40 708 2.81 1.12 0.40 744 26 26 3.17 0.89 0.28 686 3.08 0.86 0.28 722 3.04 0.85 0.28 744 2.94 0.82 0.28 765 27 18 2.70 2.16 0.80 572 2.59 2.07 0.80 601 2.48 1.99 0.80 629 2.39 1.91 0.80 658 27 20 2.82 1.92 0.68 601 2.70 1.84 0.68 636 2.62 1.78 0.68 651 2.53 1.72 0.68 679 27 22 2.93 1.64 0.56 622 2.83 1.58 0.56 661 2.76 1.55 0.56 679 2.65 1.48 0.56 708 27 24 3.08 1.36 0.44 651 2.97 1.31 0.44 686 2.90 1.28 0.44 708 2.81 1.23 0.44 744 27 26 3.17 1.02 0.32 686 3.08 0.99 0.32 722 3.04 0.97 0.32 744 2.94 0.94 0.32 765 28 18 2.70 2.27 0.84 572 2.59 2.17 0.84 601 2.48 2.09 0.84 629 2.39 2.01 0.84 658 28 20 2.82 2.03 0.72 601 2.70 1.95 0.72 636 2.62 1.89 0.72 651 2.53 1.82 0.72 679 28 22 2.93 1.76 0.60 622 2.83 1.70 0.60 661 2.76 1.66 0.60 679 2.65 1.59 0.60 708 28 24 3.08 1.48 0.48 651 2.97 1.42 0.48 686 2.90 1.39 0.48 708 2.81 1.35 0.48 744 28 26 3.17 1.14 0.36 686 3.08 1.11 0.36 722 3.04 1.09 0.36 744 2.94 1.06 0.36 765 29 18 2.70 2.38 0.88 572 2.59 2.28 0.88 601 2.48 2.19 0.88 629 2.39 2.10 0.88 658 29 20 2.82 2.14 0.76 601 2.70 2.05 0.76 636 2.62 1.99 0.76 651 2.53 1.92 0.76 679 29 22 2.93 1.88 0.64 622 2.83 1.81 0.64 661 2.76 1.77 0.64 679 2.65 1.69 0.64 708 29 24 3.08 1.60 0.52 651 2.97 1.54 0.52 686 2.90 1.51 0.52 708 2.81 1.46 0.52 744 29 26 3.17 1.27 0.40 686 3.08 1.23 0.40 722 3.04 1.21 0.40 744 2.94 1.18 0.40 765 30 18 2.70 2.49 0.92 572 2.59 2.38 0.92 601 2.48 2.29 0.92 629 2.39 2.20 0.92 658 30 20 2.82 2.25 0.80 601 2.70 2.16 0.80 636 2.62 2.10 0.80 651 2.53 2.02 0.80 679 30 22 2.93 1.99 0.68 622 2.83 1.92 0.68 661 2.76 1.88 0.68 679 2.65 1.80 0.68 708 30 24 3.08 1.73 0.56 651 2.97 1.66 0.56 686 2.90 1.62 0.56 708 2.81 1.57 0.56 744 30 26 3.17 1.40 0.44 686 3.08 1.36 0.44 722 3.04 1.34 0.44 744 2.94 1.30 0.44 765 31 18 2.70 2.59 0.96 572 2.59 2.48 0.96 601 2.48 2.38 0.96 629 2.39 2.30 0.96 658 31 20 2.82 2.37 0.84 601 2.70 2.27 0.84 636 2.62 2.20 0.84 651 2.53 2.13 0.84 679 31 22 2.93 2.11 0.72 622 2.83 2.04 0.72 661 2.76 1.99 0.72 679 2.65 1.90 0.72 708 31 24 3.08 1.85 0.60 651 2.97 1.78 0.60 686 2.90 1.74 0.60 708 2.81 1.68 0.60 744 31 26 3.17 1.52 0.48 686 3.08 1.48 0.48 722 3.04 1.46 0.48 744 2.94 1.41 0.48 765 32 18 2.70 2.70 1.00 572 2.59 2.59 1.00 601 2.48 2.48 1.00 629 2.39 2.39 1.00 658 32 20 2.82 2.48 0.88 601 2.70 2.38 0.88 636 2.62 2.31 0.88 651 2.53 2.23 0.88 679 32 22 2.93 2.23 0.76 622 2.83 2.15 0.76 661 2.76 2.10 0.76 679 2.65 2.01 0.76 708 32 24 3.08 1.97 0.64 651 2.97 1.90 0.64 686 2.90 1.85 0.64 708 2.81 1.80 0.64 744 32 26 3.17 1.65 0.52 686 3.08 1.60 0.52 722 3.04 1.58 0.52 744 2.94 1.53 0.52 765
INDOOR
DB(:)
INDOOR
WB(:)
OUTDOOR DB(:)
21 2725
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT30Q SHC SHF INPUT
CAPACITY : 2.3(KW) SHF : 0.74 INPUT : 715(W)
COOL operation (230V)
MSC-A07YV - : MUH-A07YV -
E1E1
NOTE Q :Total capacity (kW) SHF :Sensible heat factor DB :Dry-bulb temperature
SHC :Sensible heat capacity (kW) INPUT :Total power input (W) WB :Wet-bulb temperature
13
Page 14
PERFORMANCE DATA
21 18 2.25 1.26 0.56 701 2.07 1.16 0.56 744 1.99 1.11 0.56 758 21 20 2.37 1.04 0.44 729 2.21 0.97 0.44 765 2.13 0.94 0.44 787 22 18 2.25 1.35 0.60 701 2.07 1.24 0.60 744 1.99 1.19 0.60 758 22 20 2.37 1.14 0.48 729 2.21 1.06 0.48 765 2.13 1.02 0.48 787 22 22 2.51 0.90 0.36 758 2.35 0.84 0.36 801 2.27 0.82 0.36 815 23 18 2.25 1.44 0.64 701 2.07 1.32 0.64 744 1.99 1.27 0.64 758 23 20 2.37 1.23 0.52 729 2.21 1.15 0.52 765 2.13 1.11 0.52 787 23 22 2.51 1.00 0.40 758 2.35 0.94 0.40 801 2.27 0.91 0.40 815 24 18 2.25 1.53 0.68 701 2.07 1.41 0.68 744 1.99 1.35 0.68 758 24 20 2.37 1.33 0.56 729 2.21 1.24 0.56 765 2.13 1.19 0.56 787 24 22 2.51 1.10 0.44 758 2.35 1.03 0.44 801 2.27 1.00 0.44 815 24 24 2.65 0.85 0.32 787 2.48 0.79 0.32 822 2.42 0.77 0.32 840 25 18 2.25 1.62 0.72 701 2.07 1.49 0.72 744 1.99 1.43 0.72 758 25 20 2.37 1.42 0.60 729 2.21 1.32 0.60 765 2.13 1.28 0.60 787 25 22 2.51 1.20 0.48 758 2.35 1.13 0.48 801 2.27 1.09 0.48 815 25 24 2.65 0.95 0.36 787 2.48 0.89 0.36 822 2.42 0.87 0.36 840 26 18 2.25 1.71 0.76 701 2.07 1.57 0.76 744 1.99 1.51 0.76 758 26 20 2.37 1.52 0.64 729 2.21 1.41 0.64 765 2.13 1.36 0.64 787 26 22 2.51 1.30 0.52 758 2.35 1.22 0.52 801 2.27 1.18 0.52 815 26 24 2.65 1.06 0.40 787 2.48 0.99 0.40 822 2.42 0.97 0.40 840 26 26 2.78 0.78 0.28 815 2.62 0.73 0.28 851 2.54 0.71 0.28 869 27 18 2.25 1.80 0.80 701 2.07 1.66 0.80 744 1.99 1.59 0.80 758 27 20 2.37 1.61 0.68 729 2.21 1.50 0.68 765 2.13 1.45 0.68 787 27 22 2.51 1.40 0.56 758 2.35 1.31 0.56 801 2.27 1.27 0.56 815 27 24 2.65 1.16 0.44 787 2.48 1.09 0.44 822 2.42 1.06 0.44 840 27 26 2.78 0.89 0.32 815 2.62 0.84 0.32 851 2.54 0.81 0.32 869 28 18 2.25 1.89 0.84 701 2.07 1.74 0.84 744 1.99 1.67 0.84 758 28 20 2.37 1.71 0.72 729 2.21 1.59 0.72 765 2.13 1.53 0.72 787 28 22 2.51 1.50 0.60 758 2.35 1.41 0.60 801 2.27 1.36 0.60 815 28 24 2.65 1.27 0.48 787 2.48 1.19 0.48 822 2.42 1.16 0.48 840 28 26 2.78 1.00 0.36 815 2.62 0.94 0.36 851 2.54 0.91 0.36 869 29 18 2.25 1.98 0.88 701 2.07 1.82 0.88 744 1.99 1.75 0.88 758 29 20 2.37 1.80 0.76 729 2.21 1.68 0.76 765 2.13 1.62 0.76 787 29 22 2.51 1.60 0.64 758 2.35 1.50 0.64 801 2.27 1.45 0.64 815 29 24 2.65 1.38 0.52 787 2.48 1.29 0.52 822 2.42 1.26 0.52 840 29 26 2.78 1.11 0.40 815 2.62 1.05 0.40 851 2.54 1.02 0.40 869 30 18 2.25 2.07 0.92 701 2.07 1.90 0.92 744 1.99 1.83 0.92 758 30 20 2.37 1.90 0.80 729 2.21 1.77 0.80 765 2.13 1.70 0.80 787 30 22 2.51 1.70 0.68 758 2.35 1.60 0.68 801 2.27 1.54 0.68 815 30 24 2.65 1.48 0.56 787 2.48 1.39 0.56 822 2.42 1.35 0.56 840 30 26 2.78 1.22 0.44 815 2.62 1.15 0.44 851 2.54 1.12 0.44 869 31 18 2.25 2.16 0.96 701 2.07 1.99 0.96 744 1.99 1.91 0.96 758 31 20 2.37 1.99 0.84 729 2.21 1.85 0.84 765 2.13 1.79 0.84 787 31 22 2.51 1.81 0.72 758 2.35 1.69 0.72 801 2.27 1.63 0.72 815 31 24 2.65 1.59 0.60 787 2.48 1.49 0.60 822 2.42 1.45 0.60 840 31 26 2.78 1.34 0.48 815 2.62 1.26 0.48 851 2.54 1.22 0.48 869 32 18 2.25 2.25 1.00 701 2.07 2.07 1.00 744 1.99 1.99 1.00 758 32 20 2.37 2.08 0.88 729 2.21 1.94 0.88 765 2.13 1.87 0.88 787 32 22 2.51 1.91 0.76 758 2.35 1.78 0.76 801 2.27 1.72 0.76 815 32 24 2.65 1.69 0.64 787 2.48 1.59 0.64 822 2.42 1.55 0.64 840 32 26 2.78 1.45 0.52 815 2.62 1.36 0.52 851 2.54 1.32 0.52 869
INDOOR
DB(:)
INDOOR
WB(:)
OUTDOOR DB(:)
35 4340
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT
CAPACITY : 2.3(KW) SHF : 0.74 INPUT : 715(W)
COOL operation (230V)
MSC-A07YV - : MUH-A07YV -
E1E1
NOTE Q :Total capacity (kW) SHF :Sensible heat factor DB :Dry-bulb temperature
SHC :Sensible heat capacity (kW) INPUT :Total power input (W) WB :Wet-bulb temperature
14
Page 15
PERFORMANCE DATA
21 18 3.00 1.56 0.52 636 2.87 1.49 0.52 668 2.75 1.43 0.52 700 2.65 1.38 0.52 731 21 20 3.12 1.25 0.40 668 3.00 1.20 0.40 708 2.91 1.16 0.40 723 2.81 1.12 0.40 755 22 18 3.00 1.68 0.56 636 2.87 1.61 0.56 668 2.75 1.54 0.56 700 2.65 1.49 0.56 731 22 20 3.12 1.37 0.44 668 3.00 1.32 0.44 708 2.91 1.28 0.44 723 2.81 1.23 0.44 755 22 22 3.25 1.04 0.32 692 3.14 1.00 0.32 735 3.06 0.98 0.32 755 2.93 0.94 0.32 787 23 18 3.00 1.80 0.60 636 2.87 1.72 0.60 668 2.75 1.65 0.60 700 2.65 1.59 0.60 731 23 20 3.12 1.50 0.48 668 3.00 1.44 0.48 708 2.91 1.40 0.48 723 2.81 1.35 0.48 755 23 22 3.25 1.17 0.36 692 3.14 1.13 0.36 735 3.06 1.10 0.36 755 2.93 1.06 0.36 787 24 18 3.00 1.92 0.64 636 2.87 1.84 0.64 668 2.75 1.76 0.64 700 2.65 1.70 0.64 731 24 20 3.12 1.62 0.52 668 3.00 1.56 0.52 708 2.91 1.51 0.52 723 2.81 1.46 0.52 755 24 22 3.25 1.30 0.40 692 3.14 1.25 0.40 735 3.06 1.22 0.40 755 2.93 1.17 0.40 787 24 24 3.42 0.96 0.28 723 3.29 0.92 0.28 763 3.21 0.90 0.28 787 3.11 0.87 0.28 827 25 18 3.00 2.04 0.68 636 2.87 1.95 0.68 668 2.75 1.87 0.68 700 2.65 1.80 0.68 731 25 20 3.12 1.75 0.56 668 3.00 1.68 0.56 708 2.91 1.63 0.56 723 2.81 1.57 0.56 755 25 22 3.25 1.43 0.44 692 3.14 1.38 0.44 735 3.06 1.35 0.44 755 2.93 1.29 0.44 787 25 24 3.42 1.09 0.32 723 3.29 1.05 0.32 763 3.21 1.03 0.32 787 3.11 1.00 0.32 827 26 18 3.00 2.16 0.72 636 2.87 2.07 0.72 668 2.75 1.98 0.72 700 2.65 1.91 0.72 731 26 20 3.12 1.87 0.60 668 3.00 1.80 0.60 708 2.91 1.74 0.60 723 2.81 1.68 0.60 755 26 22 3.25 1.56 0.48 692 3.14 1.51 0.48 735 3.06 1.47 0.48 755 2.93 1.41 0.48 787 26 24 3.42 1.23 0.36 723 3.29 1.18 0.36 763 3.21 1.16 0.36 787 3.11 1.12 0.36 827 26 26 3.52 0.84 0.24 763 3.42 0.82 0.24 803 3.37 0.81 0.24 827 3.26 0.78 0.24 851 27 18 3.00 2.28 0.76 636 2.87 2.18 0.76 668 2.75 2.09 0.76 700 2.65 2.02 0.76 731 27 20 3.12 2.00 0.64 668 3.00 1.92 0.64 708 2.91 1.86 0.64 723 2.81 1.80 0.64 755 27 22 3.25 1.69 0.52 692 3.14 1.63 0.52 735 3.06 1.59 0.52 755 2.93 1.52 0.52 787 27 24 3.42 1.37 0.40 723 3.29 1.32 0.40 763 3.21 1.29 0.40 787 3.11 1.24 0.40 827 27 26 3.52 0.99 0.28 763 3.42 0.96 0.28 803 3.37 0.94 0.28 827 3.26 0.91 0.28 851 28 18 3.00 2.40 0.80 636 2.87 2.30 0.80 668 2.75 2.20 0.80 700 2.65 2.12 0.80 731 28 20 3.12 2.12 0.68 668 3.00 2.04 0.68 708 2.91 1.98 0.68 723 2.81 1.91 0.68 755 28 22 3.25 1.82 0.56 692 3.14 1.76 0.56 735 3.06 1.71 0.56 755 2.93 1.64 0.56 787 28 24 3.42 1.50 0.44 723 3.29 1.45 0.44 763 3.21 1.41 0.44 787 3.11 1.37 0.44 827 28 26 3.52 1.13 0.32 763 3.42 1.09 0.32 803 3.37 1.08 0.32 827 3.26 1.04 0.32 851 29 18 3.00 2.52 0.84 636 2.87 2.41 0.84 668 2.75 2.31 0.84 700 2.65 2.23 0.84 731 29 20 3.12 2.25 0.72 668 3.00 2.16 0.72 708 2.91 2.09 0.72 723 2.81 2.02 0.72 755 29 22 3.25 1.95 0.60 692 3.14 1.88 0.60 735 3.06 1.84 0.60 755 2.93 1.76 0.60 787 29 24 3.42 1.64 0.48 723 3.29 1.58 0.48 763 3.21 1.54 0.48 787 3.11 1.49 0.48 827 29 26 3.52 1.27 0.36 763 3.42 1.23 0.36 803 3.37 1.21 0.36 827 3.26 1.18 0.36 851 30 18 3.00 2.64 0.88 636 2.87 2.52 0.88 668 2.75 2.42 0.88 700 2.65 2.33 0.88 731 30 20 3.12 2.37 0.76 668 3.00 2.28 0.76 708 2.91 2.21 0.76 723 2.81 2.13 0.76 755 30 22 3.25 2.08 0.64 692 3.14 2.01 0.64 735 3.06 1.96 0.64 755 2.93 1.88 0.64 787 30 24 3.42 1.78 0.52 723 3.29 1.71 0.52 763 3.21 1.67 0.52 787 3.11 1.62 0.52 827 30 26 3.52 1.41 0.40 763 3.42 1.37 0.40 803 3.37 1.35 0.40 827 3.26 1.31 0.40 851 31 18 3.00 2.76 0.92 636 2.87 2.64 0.92 668 2.75 2.53 0.92 700 2.65 2.44 0.92 731 31 20 3.12 2.50 0.80 668 3.00 2.40 0.80 708 2.91 2.33 0.80 723 2.81 2.24 0.80 755 31 22 3.25 2.21 0.68 692 3.14 2.13 0.68 735 3.06 2.08 0.68 755 2.93 1.99 0.68 787 31 24 3.42 1.91 0.56 723 3.29 1.84 0.56 763 3.21 1.80 0.56 787 3.11 1.74 0.56 827 31 26 3.52 1.55 0.44 763 3.42 1.50 0.44 803 3.37 1.48 0.44 827 3.26 1.44 0.44 851 32 18 3.00 2.88 0.96 636 2.87 2.75 0.96 668 2.75 2.64 0.96 700 2.65 2.55 0.96 731 32 20 3.12 2.62 0.84 668 3.00 2.52 0.84 708 2.91 2.44 0.84 723 2.81 2.36 0.84 755 32 22 3.25 2.34 0.72 692 3.14 2.26 0.72 735 3.06 2.20 0.72 755 2.93 2.11 0.72 787 32 24 3.42 2.05 0.60 723 3.29 1.97 0.60 763 3.21 1.93 0.60 787 3.11 1.87 0.60 827 32 26 3.52 1.69 0.48 763 3.42 1.64 0.48 803 3.37 1.62 0.48 827 3.26 1.57 0.48 851
INDOOR
DB(:)
INDOOR
WB(:)
OUTDOOR DB(:)
21 2725
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT30Q SHC SHF INPUT
CAPACITY : 2.55(KW) SHF : 0.70 INPUT : 795(W)
COOL operation (230V)
MSC-A09YV - : MUH-A09YV -
NOTE Q :Total capacity (kW) SHF :Sensible heat factor DB :Dry-bulb temperature
SHC :Sensible heat capacity (kW) INPUT :Total power input (W) WB :Wet-bulb temperature
E1E1
15
Page 16
PERFORMANCE DATA
21 18 2.50 1.30 0.52 779 2.30 1.19 0.52 827 2.21 1.15 0.52 843 21 20 2.63 1.05 0.40 811 2.45 0.98 0.40 851 2.36 0.94 0.40 875 22 18 2.50 1.40 0.56 779 2.30 1.29 0.56 827 2.21 1.24 0.56 843 22 20 2.63 1.16 0.44 811 2.45 1.08 0.44 851 2.36 1.04 0.44 875 22 22 2.78 0.89 0.32 843 2.60 0.83 0.32 890 2.51 0.80 0.32 906 23 18 2.50 1.50 0.60 779 2.30 1.38 0.60 827 2.21 1.32 0.60 843 23 20 2.63 1.26 0.48 811 2.45 1.18 0.48 851 2.36 1.13 0.48 875 23 22 2.78 1.00 0.36 843 2.60 0.94 0.36 890 2.51 0.90 0.36 906 24 18 2.50 1.60 0.64 779 2.30 1.47 0.64 827 2.21 1.41 0.64 843 24 20 2.63 1.37 0.52 811 2.45 1.27 0.52 851 2.36 1.23 0.52 875 24 22 2.78 1.11 0.40 843 2.60 1.04 0.40 890 2.51 1.00 0.40 906 24 24 2.93 0.82 0.28 875 2.75 0.77 0.28 914 2.68 0.75 0.28 934 25 18 2.50 1.70 0.68 779 2.30 1.56 0.68 827 2.21 1.50 0.68 843 25 20 2.63 1.47 0.56 811 2.45 1.37 0.56 851 2.36 1.32 0.56 875 25 22 2.78 1.22 0.44 843 2.60 1.14 0.44 890 2.51 1.11 0.44 906 25 24 2.93 0.94 0.32 875 2.75 0.88 0.32 914 2.68 0.86 0.32 934 26 18 2.50 1.80 0.72 779 2.30 1.65 0.72 827 2.21 1.59 0.72 843 26 20 2.63 1.58 0.60 811 2.45 1.47 0.60 851 2.36 1.42 0.60 875 26 22 2.78 1.33 0.48 843 2.60 1.25 0.48 890 2.51 1.21 0.48 906 26 24 2.93 1.06 0.36 875 2.75 0.99 0.36 914 2.68 0.96 0.36 934 26 26 3.09 0.74 0.24 906 2.91 0.70 0.24 946 2.82 0.68 0.24 966 27 18 2.50 1.90 0.76 779 2.30 1.74 0.76 827 2.21 1.68 0.76 843 27 20 2.63 1.68 0.64 811 2.45 1.57 0.64 851 2.36 1.51 0.64 875 27 22 2.78 1.45 0.52 843 2.60 1.35 0.52 890 2.51 1.31 0.52 906 27 24 2.93 1.17 0.40 875 2.75 1.10 0.40 914 2.68 1.07 0.40 934 27 26 3.09 0.86 0.28 906 2.91 0.81 0.28 946 2.82 0.79 0.28 966 28 18 2.50 2.00 0.80 779 2.30 1.84 0.80 827 2.21 1.76 0.80 843 28 20 2.63 1.79 0.68 811 2.45 1.66 0.68 851 2.36 1.60 0.68 875 28 22 2.78 1.56 0.56 843 2.60 1.46 0.56 890 2.51 1.41 0.56 906 28 24 2.93 1.29 0.44 875 2.75 1.21 0.44 914 2.68 1.18 0.44 934 28 26 3.09 0.99 0.32 906 2.91 0.93 0.32 946 2.82 0.90 0.32 966 29 18 2.50 2.10 0.84 779 2.30 1.93 0.84 827 2.21 1.85 0.84 843 29 20 2.63 1.89 0.72 811 2.45 1.76 0.72 851 2.36 1.70 0.72 875 29 22 2.78 1.67 0.60 843 2.60 1.56 0.60 890 2.51 1.51 0.60 906 29 24 2.93 1.41 0.48 875 2.75 1.32 0.48 914 2.68 1.29 0.48 934 29 26 3.09 1.11 0.36 906 2.91 1.05 0.36 946 2.82 1.01 0.36 966 30 18 2.50 2.20 0.88 779 2.30 2.02 0.88 827 2.21 1.94 0.88 843 30 20 2.63 2.00 0.76 811 2.45 1.86 0.76 851 2.36 1.79 0.76 875 30 22 2.78 1.78 0.64 843 2.60 1.66 0.64 890 2.51 1.61 0.64 906 30 24 2.93 1.52 0.52 875 2.75 1.43 0.52 914 2.68 1.39 0.52 934 30 26 3.09 1.23 0.40 906 2.91 1.16 0.40 946 2.82 1.13 0.40 966 31 18 2.50 2.30 0.92 779 2.30 2.11 0.92 827 2.21 2.03 0.92 843 31 20 2.63 2.10 0.80 811 2.45 1.96 0.80 851 2.36 1.89 0.80 875 31 22 2.78 1.89 0.68 843 2.60 1.77 0.68 890 2.51 1.71 0.68 906 31 24 2.93 1.64 0.56 875 2.75 1.54 0.56 914 2.68 1.50 0.56 934 31 26 3.09 1.36 0.44 906 2.91 1.28 0.44 946 2.82 1.24 0.44 966 32 18 2.50 2.40 0.96 779 2.30 2.20 0.96 827 2.21 2.12 0.96 843 32 20 2.63 2.21 0.84 811 2.45 2.06 0.84 851 2.36 1.98 0.84 875 32 22 2.78 2.00 0.72 843 2.60 1.87 0.72 890 2.51 1.81 0.72 906 32 24 2.93 1.76 0.60 875 2.75 1.65 0.60 914 2.68 1.61 0.60 934 32 26 3.09 1.48 0.48 906 2.91 1.40 0.48 946 2.82 1.35 0.48 966
INDOOR
DB(:)
INDOOR
WB(:)
OUTDOOR DB(:)
35 4340
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT
CAPACITY : 2.55(KW) SHF : 0.70 INPUT : 795(W)
COOL operation (230V)
MSC-A09YV - : MUH-A09YV -
E1E1
NOTE Q :Total capacity (kW) SHF :Sensible heat factor DB :Dry-bulb temperature
SHC :Sensible heat capacity (kW) INPUT :Total power input (W) WB :Wet-bulb temperature
16
Page 17
PERFORMANCE DATA
21 18 4.11 1.97 0.48 872 3.94 1.89 0.48 916 3.78 1.81 0.48 959 3.64 1.75 0.48 1003 21 20 4.29 1.54 0.36 916 4.11 1.48 0.36 970 3.99 1.44 0.36 992 3.85 1.39 0.36 1036 22 18 4.11 2.14 0.52 872 3.94 2.05 0.52 916 3.78 1.97 0.52 959 3.64 1.89 0.52 1003 22 20 4.29 1.72 0.40 916 4.11 1.65 0.40 970 3.99 1.60 0.40 992 3.85 1.54 0.40 1036 22 22 4.46 1.25 0.28 948 4.31 1.21 0.28 1008 4.20 1.18 0.28 1036 4.03 1.13 0.28 1079 23 18 4.11 2.30 0.56 872 3.94 2.21 0.56 916 3.78 2.12 0.56 959 3.64 2.04 0.56 1003 23 20 4.29 1.89 0.44 916 4.11 1.81 0.44 970 3.99 1.76 0.44 992 3.85 1.69 0.44 1036 23 22 4.46 1.43 0.32 948 4.31 1.38 0.32 1008 4.20 1.34 0.32 1036 4.03 1.29 0.32 1079 24 18 4.11 2.47 0.60 872 3.94 2.36 0.60 916 3.78 2.27 0.60 959 3.64 2.18 0.60 1003 24 20 4.29 2.06 0.48 916 4.11 1.97 0.48 970 3.99 1.92 0.48 992 3.85 1.85 0.48 1036 24 22 4.46 1.61 0.36 948 4.31 1.55 0.36 1008 4.20 1.51 0.36 1036 4.03 1.45 0.36 1079 24 24 4.69 1.13 0.24 992 4.52 1.08 0.24 1046 4.41 1.06 0.24 1079 4.27 1.02 0.24 1134 25 18 4.11 2.63 0.64 872 3.94 2.52 0.64 916 3.78 2.42 0.64 959 3.64 2.33 0.64 1003 25 20 4.29 2.23 0.52 916 4.11 2.14 0.52 970 3.99 2.07 0.52 992 3.85 2.00 0.52 1036 25 22 4.46 1.79 0.40 948 4.31 1.72 0.40 1008 4.20 1.68 0.40 1036 4.03 1.61 0.40 1079 25 24 4.69 1.31 0.28 992 4.52 1.26 0.28 1046 4.41 1.23 0.28 1079 4.27 1.20 0.28 1134 26 18 4.11 2.80 0.68 872 3.94 2.68 0.68 916 3.78 2.57 0.68 959 3.64 2.48 0.68 1003 26 20 4.29 2.40 0.56 916 4.11 2.30 0.56 970 3.99 2.23 0.56 992 3.85 2.16 0.56 1036 26 22 4.46 1.96 0.44 948 4.31 1.89 0.44 1008 4.20 1.85 0.44 1036 4.03 1.77 0.44 1079 26 24 4.69 1.50 0.32 992 4.52 1.44 0.32 1046 4.41 1.41 0.32 1079 4.27 1.37 0.32 1134 26 26 4.83 0.97 0.20 1046 4.69 0.94 0.20 1101 4.62 0.92 0.20 1134 4.48 0.90 0.20 1166 27 18 4.11 2.96 0.72 872 3.94 2.84 0.72 916 3.78 2.72 0.72 959 3.64 2.62 0.72 1003 27 20 4.29 2.57 0.60 916 4.11 2.47 0.60 970 3.99 2.39 0.60 992 3.85 2.31 0.60 1036 27 22 4.46 2.14 0.48 948 4.31 2.07 0.48 1008 4.20 2.02 0.48 1036 4.03 1.93 0.48 1079 27 24 4.69 1.69 0.36 992 4.52 1.63 0.36 1046 4.41 1.59 0.36 1079 4.27 1.54 0.36 1134 27 26 4.83 1.16 0.24 1046 4.69 1.13 0.24 1101 4.62 1.11 0.24 1134 4.48 1.08 0.24 1166 28 18 4.11 3.13 0.76 872 3.94 2.99 0.76 916 3.78 2.87 0.76 959 3.64 2.77 0.76 1003 28 20 4.29 2.74 0.64 916 4.11 2.63 0.64 970 3.99 2.55 0.64 992 3.85 2.46 0.64 1036 28 22 4.46 2.32 0.52 948 4.31 2.24 0.52 1008 4.20 2.18 0.52 1036 4.03 2.09 0.52 1079 28 24 4.69 1.88 0.40 992 4.52 1.81 0.40 1046 4.41 1.76 0.40 1079 4.27 1.71 0.40 1134 28 26 4.83 1.35 0.28 1046 4.69 1.31 0.28 1101 4.62 1.29 0.28 1134 4.48 1.25 0.28 1166 29 18 4.11 3.29 0.80 872 3.94 3.15 0.80 916 3.78 3.02 0.80 959 3.64 2.91 0.80 1003 29 20 4.29 2.92 0.68 916 4.11 2.80 0.68 970 3.99 2.71 0.68 992 3.85 2.62 0.68 1036 29 22 4.46 2.50 0.56 948 4.31 2.41 0.56 1008 4.20 2.35 0.56 1036 4.03 2.25 0.56 1079 29 24 4.69 2.06 0.44 992 4.52 1.99 0.44 1046 4.41 1.94 0.44 1079 4.27 1.88 0.44 1134 29 26 4.83 1.55 0.32 1046 4.69 1.50 0.32 1101 4.62 1.48 0.32 1134 4.48 1.43 0.32 1166 30 18 4.11 3.45 0.84 872 3.94 3.31 0.84 916 3.78 3.18 0.84 959 3.64 3.06 0.84 1003 30 20 4.29 3.09 0.72 916 4.11 2.96 0.72 970 3.99 2.87 0.72 992 3.85 2.77 0.72 1036 30 22 4.46 2.68 0.60 948 4.31 2.58 0.60 1008 4.20 2.52 0.60 1036 4.03 2.42 0.60 1079 30 24 4.69 2.25 0.48 992 4.52 2.17 0.48 1046 4.41 2.12 0.48 1079 4.27 2.05 0.48 1134 30 26 4.83 1.74 0.36 1046 4.69 1.69 0.36 1101 4.62 1.66 0.36 1134 4.48 1.61 0.36 1166 31 18 4.11 3.62 0.88 872 3.94 3.47 0.88 916 3.78 3.33 0.88 959 3.64 3.20 0.88 1003 31 20 4.29 3.26 0.76 916 4.11 3.13 0.76 970 3.99 3.03 0.76 992 3.85 2.93 0.76 1036 31 22 4.46 2.86 0.64 948 4.31 2.76 0.64 1008 4.20 2.69 0.64 1036 4.03 2.58 0.64 1079 31 24 4.69 2.44 0.52 992 4.52 2.35 0.52 1046 4.41 2.29 0.52 1079 4.27 2.22 0.52 1134 31 26 4.83 1.93 0.40 1046 4.69 1.88 0.40 1101 4.62 1.85 0.40 1134 4.48 1.79 0.40 1166 32 18 4.11 3.78 0.92 872 3.94 3.62 0.92 916 3.78 3.48 0.92 959 3.64 3.35 0.92 1003 32 20 4.29 3.43 0.80 916 4.11 3.29 0.80 970 3.99 3.19 0.80 992 3.85 3.08 0.80 1036 32 22 4.46 3.03 0.68 948 4.31 2.93 0.68 1008 4.20 2.86 0.68 1036 4.03 2.74 0.68 1079 32 24 4.69 2.63 0.56 992 4.52 2.53 0.56 1046 4.41 2.47 0.56 1079 4.27 2.39 0.56 1134 32 26 4.83 2.13 0.44 1046 4.69 2.06 0.44 1101 4.62 2.03 0.44 1134 4.48 1.97 0.44 1166
INDOOR
DB(:)
INDOOR
WB(:)
OUTDOOR DB(:)
21 2725
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT30Q SHC SHF INPUT
CAPACITY : 3.5(KW) SHF : 0.66 INPUT : 1090(W)
COOL operation (230V)
MSC-A12YV - : MUH-A12YV -
E1E1
NOTE Q :Total capacity (kW) SHF :Sensible heat factor DB :Dry-bulb temperature
SHC :Sensible heat capacity (kW) INPUT :Total power input (W) WB :Wet-bulb temperature
17
Page 18
PERFORMANCE DATA
21 18 3.43 1.65 0.48 1068 3.15 1.51 0.48 1134 3.03 1.45 0.48 1155 21 20 3.61 1.30 0.36 1112 3.36 1.21 0.36 1166 3.24 1.17 0.36 1199 22 18 3.43 1.78 0.52 1068 3.15 1.64 0.52 1134 3.03 1.57 0.52 1155 22 20 3.61 1.44 0.40 1112 3.36 1.34 0.40 1166 3.24 1.30 0.40 1199 22 22 3.82 1.07 0.28 1155 3.57 1.00 0.28 1221 3.45 0.97 0.28 1243 23 18 3.43 1.92 0.56 1068 3.15 1.76 0.56 1134 3.03 1.70 0.56 1155 23 20 3.61 1.59 0.44 1112 3.36 1.48 0.44 1166 3.24 1.42 0.44 1199 23 22 3.82 1.22 0.32 1155 3.57 1.14 0.32 1221 3.45 1.10 0.32 1243 24 18 3.43 2.06 0.60 1068 3.15 1.89 0.60 1134 3.03 1.82 0.60 1155 24 20 3.61 1.73 0.48 1112 3.36 1.61 0.48 1166 3.24 1.55 0.48 1199 24 22 3.82 1.37 0.36 1155 3.57 1.29 0.36 1221 3.45 1.24 0.36 1243 24 24 4.03 0.97 0.24 1199 3.78 0.91 0.24 1254 3.68 0.88 0.24 1281 25 18 3.43 2.20 0.64 1068 3.15 2.02 0.64 1134 3.03 1.94 0.64 1155 25 20 3.61 1.87 0.52 1112 3.36 1.75 0.52 1166 3.24 1.68 0.52 1199 25 22 3.82 1.53 0.40 1155 3.57 1.43 0.40 1221 3.45 1.38 0.40 1243 25 24 4.03 1.13 0.28 1199 3.78 1.06 0.28 1254 3.68 1.03 0.28 1281 26 18 3.43 2.33 0.68 1068 3.15 2.14 0.68 1134 3.03 2.06 0.68 1155 26 20 3.61 2.02 0.56 1112 3.36 1.88 0.56 1166 3.24 1.81 0.56 1199 26 22 3.82 1.68 0.44 1155 3.57 1.57 0.44 1221 3.45 1.52 0.44 1243 26 24 4.03 1.29 0.32 1199 3.78 1.21 0.32 1254 3.68 1.18 0.32 1281 26 26 4.24 0.85 0.20 1243 3.99 0.80 0.20 1297 3.87 0.77 0.20 1324 27 18 3.43 2.47 0.72 1068 3.15 2.27 0.72 1134 3.03 2.18 0.72 1155 27 20 3.61 2.16 0.60 1112 3.36 2.02 0.60 1166 3.24 1.94 0.60 1199 27 22 3.82 1.83 0.48 1155 3.57 1.71 0.48 1221 3.45 1.65 0.48 1243 27 24 4.03 1.45 0.36 1199 3.78 1.36 0.36 1254 3.68 1.32 0.36 1281 27 26 4.24 1.02 0.24 1243 3.99 0.96 0.24 1297 3.87 0.93 0.24 1324 28 18 3.43 2.61 0.76 1068 3.15 2.39 0.76 1134 3.03 2.30 0.76 1155 28 20 3.61 2.31 0.64 1112 3.36 2.15 0.64 1166 3.24 2.07 0.64 1199 28 22 3.82 1.98 0.52 1155 3.57 1.86 0.52 1221 3.45 1.79 0.52 1243 28 24 4.03 1.61 0.40 1199 3.78 1.51 0.40 1254 3.68 1.47 0.40 1281 28 26 4.24 1.19 0.28 1243 3.99 1.12 0.28 1297 3.87 1.08 0.28 1324 29 18 3.43 2.74 0.80 1068 3.15 2.52 0.80 1134 3.03 2.42 0.80 1155 29 20 3.61 2.45 0.68 1112 3.36 2.28 0.68 1166 3.24 2.20 0.68 1199 29 22 3.82 2.14 0.56 1155 3.57 2.00 0.56 1221 3.45 1.93 0.56 1243 29 24 4.03 1.77 0.44 1199 3.78 1.66 0.44 1254 3.68 1.62 0.44 1281 29 26 4.24 1.36 0.32 1243 3.99 1.28 0.32 1297 3.87 1.24 0.32 1324 30 18 3.43 2.88 0.84 1068 3.15 2.65 0.84 1134 3.03 2.54 0.84 1155 30 20 3.61 2.60 0.72 1112 3.36 2.42 0.72 1166 3.24 2.33 0.72 1199 30 22 3.82 2.29 0.60 1155 3.57 2.14 0.60 1221 3.45 2.07 0.60 1243 30 24 4.03 1.93 0.48 1199 3.78 1.81 0.48 1254 3.68 1.76 0.48 1281 30 26 4.24 1.52 0.36 1243 3.99 1.44 0.36 1297 3.87 1.39 0.36 1324 31 18 3.43 3.02 0.88 1068 3.15 2.77 0.88 1134 3.03 2.66 0.88 1155 31 20 3.61 2.74 0.76 1112 3.36 2.55 0.76 1166 3.24 2.46 0.76 1199 31 22 3.82 2.44 0.64 1155 3.57 2.28 0.64 1221 3.45 2.21 0.64 1243 31 24 4.03 2.09 0.52 1199 3.78 1.97 0.52 1254 3.68 1.91 0.52 1281 31 26 4.24 1.69 0.40 1243 3.99 1.60 0.40 1297 3.87 1.55 0.40 1324 32 18 3.43 3.16 0.92 1068 3.15 2.90 0.92 1134 3.03 2.79 0.92 1155 32 20 3.61 2.88 0.80 1112 3.36 2.69 0.80 1166 3.24 2.59 0.80 1199 32 22 3.82 2.59 0.68 1155 3.57 2.43 0.68 1221 3.45 2.34 0.68 1243 32 24 4.03 2.25 0.56 1199 3.78 2.12 0.56 1254 3.68 2.06 0.56 1281 32 26 4.24 1.86 0.44 1243 3.99 1.76 0.44 1297 3.87 1.70 0.44 1324
INDOOR
DB(:)
INDOOR
WB(:)
OUTDOOR DB(:)
35 4340
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT
CAPACITY : 3.5(KW) SHF : 0.66 INPUT : 1090(W)
COOL operation (230V)
MSC-A12YV - : MUH-A12YV -
E1E1
NOTE Q :Total capacity (kW) SHF :Sensible heat factor DB :Dry-bulb temperature
SHC :Sensible heat capacity (kW) INPUT :Total power input (W) WB :Wet-bulb temperature
18
Page 19
PERFORMANCE DATA
21 18 4.11 2.14 0.52 928 3.94 2.05 0.52 974 3.78 1.97 0.52 1021 3.64 1.89 0.52 1067 21 20 4.29 1.72 0.40 974 4.11 1.65 0.40 1032 3.99 1.60 0.40 1056 3.85 1.54 0.40 1102 22 18 4.11 2.30 0.56 928 3.94 2.21 0.56 974 3.78 2.12 0.56 1021 3.64 2.04 0.56 1067 22 20 4.29 1.89 0.44 974 4.11 1.81 0.44 1032 3.99 1.76 0.44 1056 3.85 1.69 0.44 1102 22 22 4.46 1.43 0.32 1009 4.31 1.38 0.32 1073 4.20 1.34 0.32 1102 4.03 1.29 0.32 1148 23 18 4.11 2.47 0.60 928 3.94 2.36 0.60 974 3.78 2.27 0.60 1021 3.64 2.18 0.60 1067 23 20 4.29 2.06 0.48 974 4.11 1.97 0.48 1032 3.99 1.92 0.48 1056 3.85 1.85 0.48 1102 23 22 4.46 1.61 0.36 1009 4.31 1.55 0.36 1073 4.20 1.51 0.36 1102 4.03 1.45 0.36 1148 24 18 4.11 2.63 0.64 928 3.94 2.52 0.64 974 3.78 2.42 0.64 1021 3.64 2.33 0.64 1067 24 20 4.29 2.23 0.52 974 4.11 2.14 0.52 1032 3.99 2.07 0.52 1056 3.85 2.00 0.52 1102 24 22 4.46 1.79 0.40 1009 4.31 1.72 0.40 1073 4.20 1.68 0.40 1102 4.03 1.61 0.40 1148 24 24 4.69 1.31 0.28 1056 4.52 1.26 0.28 1114 4.41 1.23 0.28 1148 4.27 1.20 0.28 1206 25 18 4.11 2.80 0.68 928 3.94 2.68 0.68 974 3.78 2.57 0.68 1021 3.64 2.48 0.68 1067 25 20 4.29 2.40 0.56 974 4.11 2.30 0.56 1032 3.99 2.23 0.56 1056 3.85 2.16 0.56 1102 25 22 4.46 1.96 0.44 1009 4.31 1.89 0.44 1073 4.20 1.85 0.44 1102 4.03 1.77 0.44 1148 25 24 4.69 1.50 0.32 1056 4.52 1.44 0.32 1114 4.41 1.41 0.32 1148 4.27 1.37 0.32 1206 26 18 4.11 2.96 0.72 928 3.94 2.84 0.72 974 3.78 2.72 0.72 1021 3.64 2.62 0.72 1067 26 20 4.29 2.57 0.60 974 4.11 2.47 0.60 1032 3.99 2.39 0.60 1056 3.85 2.31 0.60 1102 26 22 4.46 2.14 0.48 1009 4.31 2.07 0.48 1073 4.20 2.02 0.48 1102 4.03 1.93 0.48 1148 26 24 4.69 1.69 0.36 1056 4.52 1.63 0.36 1114 4.41 1.59 0.36 1148 4.27 1.54 0.36 1206 26 26 4.83 1.16 0.24 1114 4.69 1.13 0.24 1172 4.62 1.11 0.24 1206 4.48 1.08 0.24 1241 27 18 4.11 3.13 0.76 928 3.94 2.99 0.76 974 3.78 2.87 0.76 1021 3.64 2.77 0.76 1067 27 20 4.29 2.74 0.64 974 4.11 2.63 0.64 1032 3.99 2.55 0.64 1056 3.85 2.46 0.64 1102 27 22 4.46 2.32 0.52 1009 4.31 2.24 0.52 1073 4.20 2.18 0.52 1102 4.03 2.09 0.52 1148 27 24 4.69 1.88 0.40 1056 4.52 1.81 0.40 1114 4.41 1.76 0.40 1148 4.27 1.71 0.40 1206 27 26 4.83 1.35 0.28 1114 4.69 1.31 0.28 1172 4.62 1.29 0.28 1206 4.48 1.25 0.28 1241 28 18 4.11 3.29 0.80 928 3.94 3.15 0.80 974 3.78 3.02 0.80 1021 3.64 2.91 0.80 1067 28 20 4.29 2.92 0.68 974 4.11 2.80 0.68 1032 3.99 2.71 0.68 1056 3.85 2.62 0.68 1102 28 22 4.46 2.50 0.56 1009 4.31 2.41 0.56 1073 4.20 2.35 0.56 1102 4.03 2.25 0.56 1148 28 24 4.69 2.06 0.44 1056 4.52 1.99 0.44 1114 4.41 1.94 0.44 1148 4.27 1.88 0.44 1206 28 26 4.83 1.55 0.32 1114 4.69 1.50 0.32 1172 4.62 1.48 0.32 1206 4.48 1.43 0.32 1241 29 18 4.11 3.45 0.84 928 3.94 3.31 0.84 974 3.78 3.18 0.84 1021 3.64 3.06 0.84 1067 29 20 4.29 3.09 0.72 974 4.11 2.96 0.72 1032 3.99 2.87 0.72 1056 3.85 2.77 0.72 1102 29 22 4.46 2.68 0.60 1009 4.31 2.58 0.60 1073 4.20 2.52 0.60 1102 4.03 2.42 0.60 1148 29 24 4.69 2.25 0.48 1056 4.52 2.17 0.48 1114 4.41 2.12 0.48 1148 4.27 2.05 0.48 1206 29 26 4.83 1.74 0.36 1114 4.69 1.69 0.36 1172 4.62 1.66 0.36 1206 4.48 1.61 0.36 1241 30 18 4.11 3.62 0.88 928 3.94 3.47 0.88 974 3.78 3.33 0.88 1021 3.64 3.20 0.88 1067 30 20 4.29 3.26 0.76 974 4.11 3.13 0.76 1032 3.99 3.03 0.76 1056 3.85 2.93 0.76 1102 30 22 4.46 2.86 0.64 1009 4.31 2.76 0.64 1073 4.20 2.69 0.64 1102 4.03 2.58 0.64 1148 30 24 4.69 2.44 0.52 1056 4.52 2.35 0.52 1114 4.41 2.29 0.52 1148 4.27 2.22 0.52 1206 30 26 4.83 1.93 0.40 1114 4.69 1.88 0.40 1172 4.62 1.85 0.40 1206 4.48 1.79 0.40 1241 31 18 4.11 3.78 0.92 928 3.94 3.62 0.92 974 3.78 3.48 0.92 1021 3.64 3.35 0.92 1067 31 20 4.29 3.43 0.80 974 4.11 3.29 0.80 1032 3.99 3.19 0.80 1056 3.85 3.08 0.80 1102 31 22 4.46 3.03 0.68 1009 4.31 2.93 0.68 1073 4.20 2.86 0.68 1102 4.03 2.74 0.68 1148 31 24 4.69 2.63 0.56 1056 4.52 2.53 0.56 1114 4.41 2.47 0.56 1148 4.27 2.39 0.56 1206 31 26 4.83 2.13 0.44 1114 4.69 2.06 0.44 1172 4.62 2.03 0.44 1206 4.48 1.97 0.44 1241 32 18 4.11 3.95 0.96 928 3.94 3.78 0.96 974 3.78 3.63 0.96 1021 3.64 3.49 0.96 1067 32 20 4.29 3.60 0.84 974 4.11 3.45 0.84 1032 3.99 3.35 0.84 1056 3.85 3.23 0.84 1102 32 22 4.46 3.21 0.72 1009 4.31 3.10 0.72 1073 4.20 3.02 0.72 1102 4.03 2.90 0.72 1148 32 24 4.69 2.81 0.60 1056 4.52 2.71 0.60 1114 4.41 2.65 0.60 1148 4.27 2.56 0.60 1206 32 26 4.83 2.32 0.48 1114 4.69 2.25 0.48 1172 4.62 2.22 0.48 1206 4.48 2.15 0.48 1241
CAPACITY :3.5(KW) SHF :0.70 INPUT :1160(W)
OUTDOOR DB(:)
INDOOR INDOOR
21 25 27 30
DB(:) WB(:)
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT
COOL operation (230V)
MCFH-A12WV - : MUH-A12YV -
NOTE Q :Total capacity (kW) SHF :Sensible heat factor DB :Dry-bulb temperature
SHC :Sensible heat capacity (kW) INPUT :Total power input (W) WB :Wet-bulb temperature
E1E1
19
Page 20
PERFORMANCE DATA
21 18 3.43 1.78 0.52 1137 3.15 1.64 0.52 1206 3.03 1.57 0.52 1230 21 20 3.61 1.44 0.40 1183 3.36 1.34 0.40 1241 3.24 1.30 0.40 1276 22 18 3.43 1.92 0.56 1137 3.15 1.76 0.56 1206 3.03 1.70 0.56 1230 22 20 3.61 1.59 0.44 1183 3.36 1.48 0.44 1241 3.24 1.42 0.44 1276 22 22 3.82 1.22 0.32 1230 3.57 1.14 0.32 1299 3.45 1.10 0.32 1322 23 18 3.43 2.06 0.60 1137 3.15 1.89 0.60 1206 3.03 1.82 0.60 1230 23 20 3.61 1.73 0.48 1183 3.36 1.61 0.48 1241 3.24 1.55 0.48 1276 23 22 3.82 1.37 0.36 1230 3.57 1.29 0.36 1299 3.45 1.24 0.36 1322 24 18 3.43 2.20 0.64 1137 3.15 2.02 0.64 1206 3.03 1.94 0.64 1230 24 20 3.61 1.87 0.52 1183 3.36 1.75 0.52 1241 3.24 1.68 0.52 1276 24 22 3.82 1.53 0.40 1230 3.57 1.43 0.40 1299 3.45 1.38 0.40 1322 24 24 4.03 1.13 0.28 1276 3.78 1.06 0.28 1334 3.68 1.03 0.28 1363 25 18 3.43 2.33 0.68 1137 3.15 2.14 0.68 1206 3.03 2.06 0.68 1230 25 20 3.61 2.02 0.56 1183 3.36 1.88 0.56 1241 3.24 1.81 0.56 1276 25 22 3.82 1.68 0.44 1230 3.57 1.57 0.44 1299 3.45 1.52 0.44 1322 25 24 4.03 1.29 0.32 1276 3.78 1.21 0.32 1334 3.68 1.18 0.32 1363 26 18 3.43 2.47 0.72 1137 3.15 2.27 0.72 1206 3.03 2.18 0.72 1230 26 20 3.61 2.16 0.60 1183 3.36 2.02 0.60 1241 3.24 1.94 0.60 1276 26 22 3.82 1.83 0.48 1230 3.57 1.71 0.48 1299 3.45 1.65 0.48 1322 26 24 4.03 1.45 0.36 1276 3.78 1.36 0.36 1334 3.68 1.32 0.36 1363 26 26 4.24 1.02 0.24 1322 3.99 0.96 0.24 1380 3.87 0.93 0.24 1409 27 18 3.43 2.61 0.76 1137 3.15 2.39 0.76 1206 3.03 2.30 0.76 1230 27 20 3.61 2.31 0.64 1183 3.36 2.15 0.64 1241 3.24 2.07 0.64 1276 27 22 3.82 1.98 0.52 1230 3.57 1.86 0.52 1299 3.45 1.79 0.52 1322 27 24 4.03 1.61 0.40 1276 3.78 1.51 0.40 1334 3.68 1.47 0.40 1363 27 26 4.24 1.19 0.28 1322 3.99 1.12 0.28 1380 3.87 1.08 0.28 1409 28 18 3.43 2.74 0.80 1137 3.15 2.52 0.80 1206 3.03 2.42 0.80 1230 28 20 3.61 2.45 0.68 1183 3.36 2.28 0.68 1241 3.24 2.20 0.68 1276 28 22 3.82 2.14 0.56 1230 3.57 2.00 0.56 1299 3.45 1.93 0.56 1322 28 24 4.03 1.77 0.44 1276 3.78 1.66 0.44 1334 3.68 1.62 0.44 1363 28 26 4.24 1.36 0.32 1322 3.99 1.28 0.32 1380 3.87 1.24 0.32 1409 29 18 3.43 2.88 0.84 1137 3.15 2.65 0.84 1206 3.03 2.54 0.84 1230 29 20 3.61 2.60 0.72 1183 3.36 2.42 0.72 1241 3.24 2.33 0.72 1276 29 22 3.82 2.29 0.60 1230 3.57 2.14 0.60 1299 3.45 2.07 0.60 1322 29 24 4.03 1.93 0.48 1276 3.78 1.81 0.48 1334 3.68 1.76 0.48 1363 29 26 4.24 1.52 0.36 1322 3.99 1.44 0.36 1380 3.87 1.39 0.36 1409 30 18 3.43 3.02 0.88 1137 3.15 2.77 0.88 1206 3.03 2.66 0.88 1230 30 20 3.61 2.74 0.76 1183 3.36 2.55 0.76 1241 3.24 2.46 0.76 1276 30 22 3.82 2.44 0.64 1230 3.57 2.28 0.64 1299 3.45 2.21 0.64 1322 30 24 4.03 2.09 0.52 1276 3.78 1.97 0.52 1334 3.68 1.91 0.52 1363 30 26 4.24 1.69 0.40 1322 3.99 1.60 0.40 1380 3.87 1.55 0.40 1409 31 18 3.43 3.16 0.92 1137 3.15 2.90 0.92 1206 3.03 2.79 0.92 1230 31 20 3.61 2.88 0.80 1183 3.36 2.69 0.80 1241 3.24 2.59 0.80 1276 31 22 3.82 2.59 0.68 1230 3.57 2.43 0.68 1299 3.45 2.34 0.68 1322 31 24 4.03 2.25 0.56 1276 3.78 2.12 0.56 1334 3.68 2.06 0.56 1363 31 26 4.24 1.86 0.44 1322 3.99 1.76 0.44 1380 3.87 1.70 0.44 1409 32 18 3.43 3.29 0.96 1137 3.15 3.02 0.96 1206 3.03 2.91 0.96 1230 32 20 3.61 3.03 0.84 1183 3.36 2.82 0.84 1241 3.24 2.72 0.84 1276 32 22 3.82 2.75 0.72 1230 3.57 2.57 0.72 1299 3.45 2.48 0.72 1322 32 24 4.03 2.42 0.60 1276 3.78 2.27 0.60 1334 3.68 2.21 0.60 1363 32 26 4.24 2.03 0.48 1322 3.99 1.92 0.48 1380 3.87 1.86 0.48 1409
CAPACITY :3.5(KW) SHF :0.70 INPUT :1160(W)
OUTDOOR DB(:)
INDOOR INDOOR
35 40 43
DB(:) WB(:)
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT
COOL operation (230V)
MCFH-A12WV - : MUH-A12YV -
NOTE Q :Total capacity (kW) SHF :Sensible heat factor DB :Dry-bulb temperature
SHC :Sensible heat capacity (kW) INPUT :Total power input (W) WB :Wet-bulb temperature
E1E1
20
Page 21
PERFORMANCE DATA HEAT operation (230V)
MSC-A07YV - : MUH-A07YV -
CAPACITY : 2.5(KW)
INDOOR
DB(:)
15 21 26
Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT
1.58
1.50
1.35
INPUT : 690(W)
-10 -5 0 5 10 15 20
449 483 518
1.90
1.80
1.68
538 573 607
E1E1
2.23
2.13
1.98
OUTDOOR WB(:)
607 635 669
2.55
2.43
2.30
656 683 718
2.88
2.75
2.63
697 718 752
3.18
3.05
2.93
718 738 773
3.50
3.36
3.25
731 766 794
MSC-A09YV - : MUH-A09YV -
CAPACITY : 3.05(KW)
INDOOR
DB(:)
15 21 26
-10 -5 0 5 10 15 20
Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT
1.92
1.83
1.65
INPUT : 840(W)
2.32
546
2.20
588
2.04
630
655 697 739
MSC-A12YV - : MUH-A12YV -
CAPACITY : 3.9(KW)
INDOOR
DB(:)
15 21 26
Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT
2.46
2.34
2.11
INPUT : 1080(W)
-10 -5 0 5 10 15 20
702 756 810
2.96
2.81
2.61
842 896 950
E1E1
2.71
2.59
2.41
E1E1
3.47
3.32
3.08
MCFH-A12WV - : MUH-A12YV -
CAPACITY : 3.7(KW)
INDOOR
DB(:)
15 21 26
Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT
2.33
2.22
2.00
INPUT : 1020(W)
-10 -5 0 5 10 15 20
3.29
663 714 765
2.81
2.66
2.48
796 847 898
3.15
2.92
OUTDOOR WB(:)
3.11
739
2.96
773
2.81
815
OUTDOOR WB(:)
1026
3.98
950
1069
3.78
994
1123
1048
E1E1
3.59
OUTDOOR WB(:)
3.77
898
1010
3.59
938
1061
3.40
989
798 832 874
969
3.51
3.36
3.20
4.49
4.29
4.10
4.26
4.07
3.89
848 874 916
1091 1123 1177
1030 1061
1112
3.87
3.72
3.57
4.95
4.76
4.56
4.70
4.51
4.33
874 899 941
1123 1156 1210
1061 1091
1142
4.27
4.10
3.97
5.46
5.25
5.07
5.18
4.98
4.81
890 932 966
1145 1199 1242
1081 1132 1173
NOTE Q:Total capacity (kW) INPUT:Total power input (W) DB:Dry-bulb temperature WB:Wet-bulb temperature
21
Page 22
High pressure protection
Released
48: 52:
Outdoor fan
OFF ON
9
MICROPROCESSOR CONTROL
MUH-A07YV ­MUH-A09YV ­MUH-A12YV -
E1
E1
E1
9-1. HEAT ( ) OPERATION
1. High pressure protection
During heating operation, the outdoor fan motor is controlled by the temperature of indoor coil thermistor RT12 for excess rise protection of compressor discharge pressure. Outdoor fan OFF: 52: Outdoor fan ON: 48:
Operation chart Example
Indoor coil thermistor
RT12 temperature
52˚C
48˚C
Outdoor fan motor
ON
OFF
ON
OFF
Outdoor fan motor turn OFF
Outdoor fan motor turn ON
NOTE : During high pressure protection and for 4 min. and 15 sec. after high pressure protection, defrosting of outdoor heat
exchanger is not detected by the defrost thermistor RT61.(Refer to 9-1.2. Defrosting.)
2. Defrosting
Defrosting of outdoor heat exchanger is controlled by DEICER P.C. board, with detection by the defrost thermistor RT61. (1) Starting conditions of defrost
When all conditions of a) ~ c) are satisfied, the defrosting operation starts. a) The compressor cumulative operation time exceeds 40 minutes without the defrosting operation working. b) RT61 reads - 3°C or less. c) After releasing the high pressure protection 4 minutes and 15 seconds have elapsed.
(2) Releasing conditions of defrost
When the condition d) or e) is satisfied, the defrosting operation stops. d) RT61 reads 10.1°C or more. e) The defrosting time exceeds 10 minutes.
22
Page 23
Operation time chart Example
Defrost thermistor RT61
10.1: or more
-3: or less
Outdoor 52C contactor (Compressor)
ON OFF
X62 (R.V. coil)
ON OFF
30 sec.
15 sec.
30 sec.
5 sec.
SR61 Outdoor fan
Defrost counter
Indoor fan
ON OFF
ON OFF
ON
Very Low
Max 10 min.
NOTE
OFF
Indoor
Horizontal
Horizontal vane
Set position
NOTE When the indoor coil thermistor RT12 reads above 0°C, indoor fan operates at Very Low for 30 seconds.
When the indoor coil thermistor RT12 reads 0°C or less, the indoor fan stops.
3. R.V. coil control
Heating · · · · · ON Cooling · · · · · OFF Dry · · · · · · · · OFF
When operation starts, the 4-way valve reverses for 5 seconds right before start-up of the compressor.
Operation time chart
(COOL/DRY)
5 sec.
(HEAT)
5 sec.
Compressor
ON OFF
ON
R.V. coil
OFF
ON
Outdoor fan
OFF
9-2. “I FEEL CONTROL” ( ) OPERATION
1. HEAT mode of “I FEEL CONTROL”
1. High pressure protection
High pressure protection is as same as HEAT OPERATION.(9-1.1.)
2. Defrosting
Defrosting is as same as HEAT OPERATION.(9-1.2.)
3. R.V. coil control
R.V. coil control is as same as HEAT OPERATION.(9-1.3.)
ON OFF
ON OFF
ON OFF
23
Page 24
Lead wiring
Housing point
10
Jumper wire
JRF
JRG
MODEL Change point
Defrost interval time changes from 40 minutes to 15 minutes.
Deforst start temperature changes from -3: to 0:.
MUH-A07YV ­ MUH-A09YV ­ MUH-A12YV -
E1
E1
E1
SERVICE FUNCTIONS
MUH-A07YV ­MUH-A09YV ­MUH-A12YV -
E1
E1
E1
10-1. COMPULSORY DEFROSTING MODE FOR SERVICE
By short circuit of the connector JPDS and JPSG on the outdoor deicer P.C. board, defrosting mode can be accom­plished regardless of the defrost interval restriction. (Refer to page 30.) Defrost thermistor RT61 must read below -3°C.
10-2. CHANGE IN DEFROST SETTING
<JRF> When the JRF wire of the deicer P.C. board is cut, the defrost interval time will be changed. <JRG> When the JRG wire of the deicer P.C. board is cut, the defrost temperature will be changed.(Refer to page 30.)
11
TROUBLESHOOTING
MUH-A07YV ­MUH-A09YV ­MUH-A12YV -
E1
E1
E1
11-1. Cautions on troubleshooting
1. Before troubleshooting, check the following:
1) Check the power supply voltage.
2) Check the indoor/outdoor connecting wire for mis-wiring.
2. Take care the following during servicing.
1) Before servicing the air conditioner, be sure to first turn off the remote controller to stop the unit, and then after con­firming the horizontal vane is closed, turn off the breaker and/or disconnect the power plug.
2) Be sure to turn OFF the power supply before removing the front panel, the cabinet, the top panel, and the electronic control P.C. board.
3) When removing the electronic control P.C. board, hold the edge of the board with care NOT to apply stress on the components.
4) When connecting or disconnecting the connectors, hold the housing of the connector. DO NOT pull the lead wires.
3. Troubleshooting procedure
1) First, check if the OPERATION INDICATOR lamp on the indoor unit is flashing on and off to indicate an abnormality. To make sure, check how many times the abnormality indication is flashing on and off before starting service work.
2) If the electronic control P.C. board is supposed to be defective, check the copper foil pattern for disconnection and the components for bursting and discoloration.
3) When troubleshooting, refer to the flow chart on page 25 and the check table on page 26.
24
Page 25
11-2. Instruction of troubleshooting
Start
Indoor unit operates. Outdoor unit doesn't operate.
Indoor unit doesn't receive the signal from remote controller.
Indoor unit operates. Outdoor unit doesn't operate normally.
OPERATION INDICATOR lamp on the indoor unit is flashing on and off.
Outdoor unit operates in only Test Run operation.
Outdoor unit doesn't operate even in Test Run operation.
Indoor unit operates, when the EMERGENCY OPERATION switch is pressed.
Indoor unit doesn't operate, when the EMERGENCY OPERATION switch is pressed.
Check room temperature thermistor. Refer to "Test point diagram and voltage".
Refer to A "Check of outdoor unit" on page 26.
Refer to "Check of remote controller and receiver P.C. board".
MSC type
Cause: Indoor/ Outdoor unit
• Mis-wiring
2-time flash Cause: Indoor unit
• Trouble of room temp­ erature/ indoor coil thermistor
MSC type
3-time flash Cause: Indoor unit
• Trouble of indoor fan motor
6-time flash Cause: Outdoor unit
• Trouble of thermistor in outdoor unit
7-time flash Cause: Outdoor unit
• Trouble of outdoor control system
Check room temperature thermistor and indoor coil thermis­tor. Refer to "Test point diagram and voltage".
Refer to "Check of indoor fan motor".
Refer to E "Check of outdoor thermistor" on page 29.
Replace the deicer P.C. board.
MSC type
1-time flash Cause: Outdoor / Indoor unit
• Trouble of serial signal
Refer to D "How to check mis-wiring and serial signal error (When outdoor unit doesn't work)" on page 28. W1
1. Check indoor / outdoor connecting wire.
2. Refer to "Check of indoor electronic control P.C. board".
Outdoor unit doesn't stop even if indoor unit stops.
Unit doesn't operate normal operation in COOL or HEAT mode.
Refer to B "Check of outdoor unit" on page 27.
Refer to C "Check of R.V. coil" on page 27.
W1.<The case of the trouble of the serial signal> When the power is turned off and then turned on again, the indication shows “the trouble of mis-wiring”.
As for indoor unit MSC type, refer to service manual OB329.
As for indoor unit MCFH type, refer to service manual OB336.
MCFH type
4-time flash Cause: Indoor unit
• Trouble of indoor electric P.C. board
Refer to "Check of indoor electronic control P.C. board".
Flash on and off at
0.5-second intervals
MCFH type
Cause: Indoor/ Outdoor unit
• Mis-wiring or trouble of serial signal
MUH-A07YV ­MUH-A09YV ­MUH-A12YV -
E1
E1
E1
25
Page 26
Yes
Compressor doesn't operate.
Yes
Yes
Is there 230V AC between 3 on the compressor contactor (52C) and N on the outdoor terminal block (TB1)?
Operate the unit in COOL or HEAT mode by pressing the EMERGENCY OPERATION switch. 3-minute time delay works. Test run operation operates for 30 minutes.
Outdoor fan motor doesn't operate.
No
Rectify the indoor and outdoor connecting wire.
Rectify the connecting wire.
Check the compressor and compressor capacitor, and rectify the connecting wire.
Start
Yes
Is there 230V AC between 4 on the compressor contactor (52C) and TAB20 on the deicer P.C. board?
Is there 230V AC between LN on the outdoor terminal block (TB1)?
Replace the deicer P.C. board.
Replace the deicer P.C. board.
No
No
Yes
Yes
No
Check the outdoor fan motor and rectify the connecting wire.
Is there 230V AC between 4 on the compressor contactor (52C) and TAB 20 on the deicer P.C. board?
Replace the deicer P.C. board.
No
Yes
Rectify the indoor and outdoor connecting wire.
Rectify the connecting wire.
Is there 230V AC between LN on the outdoor terminal block (TB1)?
No
No
Is the switch SW2-2 on the indoor electronic control P.C. board set to MUH type?
No
Change the switch SW-2-2 on the indoor electronic control P.C. board to MUH type.
Yes
+
Is there 5V DC between J205 –J101 on the deicer P.C. board?
+
Is there 5V DC between J205 –J101 on the deicer P.C. board?
Indoor unit MSC type
Indoor unit MCFH type
P
R
C
S
RED
BLK
WHT
MAINAUX.
WHTRED
BLK
MAIN
AUX.
FUSE
11-3. Trouble criterion of main parts
WHTRED
BLK
MAIN
AUX.
P
MUH-A07YV - MUH-A09YV - MUH-A12YV -
Part name
Defrost thermistor (RT63)
Measure the resistance with a tester. (Part temperature –10°C ~ 40°C)
Normal
5k~ 60k
Check method and criterion
Abnormal
Open or short-circuit
E1E1E1
Figure
Compressor (MC) INNER PROTECTOR
MUH-A07/A09YV
150i 5°C OPEN
90i10°C CLOSE
MUH-A12YV
155i 5°C OPEN
90i10°C CLOSE
Measure the resistance between the terminals with a tester. (Coil wiring temperature –10°C ~ 40°C)
Normal
MUH-A12YV
2.46~3.01
2.96~3.63
C-R
C-S
MUH-A07YV
3.41~4.18
5.41~6.63
MUH-A09YV
2.99~3.67
4.02~4.92
Outdoor fan motor (MF) INNER PROTECTOR
MUH-A07YV
130i 5°C OPEN
83i15°C CLOSE
INNER FUSE
MUH-A09/A12YV
Measure the resistance between the terminals with a tester. (Coil wiring temperature –10°C ~ 40°C)
Color of
lead wire
WHT-BLK BLK-RED
MUH-A07YV
361 ~ 443 381 ~ 468
Normal
MUH-A09/A12YV
Ω Ω
145i 2°C CUT OFF
Compressor and/or outdoor fan motor doesn’t operate.
196 ~ 241 201 ~ 246
Abnormal
Open or short-circuit
Abnormal
Open or short-circuit
MUH-A07YV
MUH-A09/A12YV
P INNER PROTECTOR
AA
Check of outdoor unit
26
Page 27
Compressor and/or outdoor fan motor doesn’t stop.
After 3 minutes, does the unit operate in HEAT mode?
Ok
No
Is there 230V AC between CN72112 on the deicer P.C. board?
Replace the deicer P.C. board.
Yes
Yes
Yes
No
Replace the R.V. coil.
Turn ON the power supply and operate the indoor unit in COOL mode by pressing the EMERGENCY OPERATION switch.
BB
Check of outdoor unit
Start
Turn OFF the power supply. After 1 minute, turn ON power supply again.
Is there 230V AC between 3 on the
Does compressor stop?
Yes
OK
No
compressor contactor (52C) and N on the outdoor terminal block (TB1)?
Yes
Replace the deicer P.C. board.
No
Rectify the connecting wire.
Does outdoor fan motor stop?
Yes
OK
No
Replace the deicer P.C. board.
Unit operates COOL mode even if it is set to HEAT mode.
w First, measure the resistance of R.V. coil to confirm it is disconnected or is not short-circuit.
CC
Check of R.V. coil
Turn ON the power supply and operate the indoor unit in HEAT mode by pressing the EMERGENCY OPERATION switch.
After 3 minutes, does the unit operate in COOL mode?
Yes
Is there 230V AC between CN72112 on the deicer P.C. board?
Yes
Replace the R.V. coil.
No
OK
No
Replace the deicer P.C. board
Unit operates HEAT mode even if it is set to COOL mode.
w First, measure the resistance of R.V. coil to confirm it is disconnected or is not short-circuit.
CC
Check of R.V. coil
27
Page 28
When OPERATION INDICATOR lamp flashes 0.5-second intervals or 1-time. Outdoor unit does not operate.
DD
How to check mis-wiring and serial signal error
Example Indoor unit MSC type
Start
Turn OFF the power supply(indoor/outdoor unit).
Is the outdoor unit "MUH" type?
Yes
•Turn ON the power supply(indoor/outdoor unit).
•Press once EMERGENCY OPERATION switch.
3 min. later, what self-check result is displayed on OPERATION INDICATOR lamp on indoor unit?
w 2
Mis-wiring is indicated.
w 1 Set the switch(SW2-2) on indoor electronic control P.C. board to
MU or MUX type, when the outdoor unit is MU or MUX type. If the setting is MUH or MXZ type, the unit does not work.
w 2 Short circuit of JPG and JPS on the indoor electronic control P.C. board enables self-check to be displayed in 3 seconds.
No
Serial signal error is indicated. (0.5-sec. ON, 2.5-sec. OFF)
Set the switch(SW2-2) on the indoor electronic control P.C. board to MU or MUX type.
Does the unit operate?
Refer to the "Instruction of troubleshooting."
(0.5-sec. ON, 0.5-sec. OFF)
Make them sure.
Yes
Is this mis-wiring, poor contact, or disconnection of wire?
No
1. Turn OFF the power supply(indoor/outdoor unit) and disconnect indoor and outdoor connecting wire on indoor side.
2. Short-circuit between indoor terminal block N and 3.
3. Turn ON the power supply(indoor unit) and press once EMERGENCY OPERATION switch.
Is there 20V DC between both ends of R132 on indoor electronic control P.C. board ? ( By tester, the stylus is between 0 ~ 20V. )
Yes
•Turn OFF the power supply(indoor unit).
•Connect ON indoor and outdoor connecting wire.
No
Replace the indoor electronic control P.C. board.
No
Yes
w1
OK
Turn ON the power supply(outdoor unit).
Is there 230V AC between outdoor terminal block L-N (TB1)?
Yes
Is there 5V DC between J205 + –J101 - on the deicer P.C. board?
Yes
Turn ON the power supply(indoor unit).
During EMERGENCY OPERATION, is there 10V DC between both ends of R601? (By tester, the stylus is between 5 ~10V)
Yes
Replace the deicer P.C. board.
As for indoor unit MSC type, refer to service manual OB329. As for indoor unit MCFH type, refer to service manual OB336.
28
Check the outdoor power supply,
No
power supply cord and connection.
No
Replace the deicer P.C. board.
Make the wiring between CN730
No
on the deicer P.C. board and outdoor terminal block correct.
Page 29
When OPERATION INDICATOR lamp flashes 6-time. Thermistors in the outdoor unit are abnormal.
EE
Check of outdoor thermistor
Start
Turn OFF the power supply.
Defrost thermistor (RT61)
Measure resistance between CN 661 1 and 2.
Is the resistance of thermistor normal?
No
Replace the thermistor.
Reconnect CN661. Turn ON the power
Yes
supply and press the EMERGENCY OPERATION switch.
Replace the deicer P.C.
board.
No
Does the unit operate 10 minutes or more?
Yes
OK
Defective contact of the connector is considered.
29
Page 30
MUH-A07YV ­MUH-A09YV ­MUH-A12YV -
E1 E1 E1
Outdoor deicer P.C. board
CN711 Outdoor fan motor
230V AC
}
CN721 R.V. coil
230V AC
}
5V DC J205 J101
Power supply input
230V AC
}
NR61 Varistor
F61 Fuse
2A/250V
R601
+
5~10VDC
}
--
Defrost interval time short pin (JPDS, JPSG) (Refer to page 24.)
Jumper wire for change in
}
}
CN661 1-2 Defrost thermistor RT61
+
--
defrost setting (JRF,JRG) (Refer to page
24.)
12V DC J204
+
J101
--
30
Page 31
12
(1) Slide the sleeve and check if there is a locking lever or not. (2) The terminal with this connector is a terminal
with lock mechanism
1Slide the sleeve. 2Pull the terminal while
pushing the locking lever.
1Hold the sleeve, and pull out the terminal slowly.
In case of terminal with lock mechanism, detach the terminal as shown below. There are two types ( Refer to (1) and (2)) of the terminal with lock mechanism. The terminal with no lock mechanism can be removed by pulling it out. Check the shape of the terminal and work.
<"Terminal with lock mechanism" Detaching points>
Connector
Sleeve
Locking lever
DISASSEMBLY INSTRUCTIONS
MUH-A07YV - MUH-A09YV - MUH-A12YV -
OUTDOOR UNIT
OPERATING PROCEDURE PHOTOS
1. Removing the cabinet
(1) Remove the screws of the top panel. (2) Remove the screw of the service panel. (3) Remove the screws of the cabinet. (4) Remove the screws of the front panel and motor support. (5) Remove the service panel, and remove the screw from
the insides. (6) Remove the top panel. (7) Remove the cabinet.
Photo 3
Screws of the service panel
Screws of the top panel
E1E1E1
Photo 1
Screws of the front panel and motor support
Screws of the cabinet
Screws of the cabinet
Photo 2
Service panel
31
Screw of the top panel
Screws of the cabinet
Page 32
OPERATING PROCEDURE PHOTOS
2. Removing the deicer P.C. board
(1) Remove the service panel and the cabinet. (2) Disconnect all the connectors and the terminals on the
deicer P.C. board.
(3) Remove the deicer P.C. board.
3. Removing the propeller and the outdoor fan motor
(1) Remove the cabinet. (Refer to 1.) (2) Remove the propeller nut. (3) Remove the propeller.
NOTE : Loose the propeller in the rotating direction for
removal.
When attaching the propeller, align the mark on the propeller and the motor shaft cut section. Set the propeller in position by using the cut on the shaft and the mark on the propeller.
(4) Remove lead clamps and disconnect the outdoor fan motor
connector. (5) Remove screws fixing the fan motor. (6) Remove the outdoor fan motor.
Photo 4
Screw
Photo 5
Propeller
nut
Deicer P.C. board
Screws of the outdoor fan motor
Propeller
Screws
Relay panel
Hook
Terminal block
Lead clamps
Outdoor fan motor connector
32
Screws of the outdoor fan motor
Page 33
OPERATING PROCEDURE PHOTOS
4. Removing the compressor
(1) Remove the cabinet. (Refer to 1.) (2) Remove the relay panel. (3) Remove the soundproof felt. (4) Remove the terminal cover on the compressor. (5) Disconnect lead wires from the glass terminal of the com-
pressor. (6) Recover gas from the refrigerant circuit. (7) Disconnect the welded part of the discharge pipe. (8) Disconnect the welded part of the suction pipe. (9) Remove nuts fixing the compressor.
)
(
Remove the compressor.
10
NOTE
Before using a burner, reclaim gas from the pipes until the pressure gauge shows 0 kg/cm
Use the burner under the condition that gas can be recovered even when the inner pressure rises by heat.
2
(0 MPa).
Photo 6
Glass terminal
Compressor
Discharge pipe
Suction pipe
Compressor set nuts
Terminal cover
33
Page 34
13
No.
Part No.
Remarks
1
2 3
4
5 6
7 8
9 10 11
12 13
14
15
E02 835 630 E02 836 630 E02 837 630 E02 815 232 E02 815 521 E02 742 900 E02 753 900 E02 754 900 E02 075 506 E02 832 290 E02 742 661 E02 747 661 E02 745 662 E02 745 961 E02 815 245 E02 836 233 E02 336 515 E02 442 515 E02 815 297 E02 159 936 E02 156 936 E02 339 936 E02 024 936 E02 726 936 E02 837 936 E02 154 642
OUTDOOR HEAT EXCHANGER OUTDOOR HEAT EXCHANGER OUTDOOR HEAT EXCHANGER CABINET GRILLE(OUT) COMPRESSOR COMPRESSOR COMPRESSOR COMPRESSOR RUBBER SET BASE STOP VALVE(GAS) STOP VALVE(GAS) STOP VALVE(LIQUID) 4-WAY VALVE SERVICE PANEL BACK PANEL MOTOR SUPPORT MOTOR SUPPORT TOP PANEL CAPILLARY TUBE CAPILLARY TUBE CAPILLARY TUBE CAPILLARY TUBE CAPILLARY TUBE CAPILLARY TUBE CHECK VALVE
RN092VHSHT RN104VHSHT RN135VHSHT 3RUBBERS/SET
{9.52 {12.7 {6.35
{3.0x{1.4x800 {3.0x{1.4x500 {3.0x{1.4x600 {3.0x{1.4x1000 {3.0x{1.6x600 {3.0x{1.6x1050
MC MC MC
1
1 1
1
3 1 1
1 1 1 1
1 1
2 1 1
1
1
1 1 1
3 1 1
1 1 1 1 1
1 2 1 1
1
1 1 1
1 3 1
1 1 1 1 1
1 1
2
1 1 1
Symbol in Wiring Diagram
Part name
Q'ty/unit
MUH-A07YV-
E1
MUH-A09YV-
E1
MUH-A12YV-
E1
PARTS LIST
MUH-A07YV - MUH-A09YV - MUH-A12YV -
13-1. OUTDOOR UNIT STRUCTURAL PARTS
1
2
3
13
E1E1E1
12
11
Part numbers that are circled are not shown in the illustration.
34
46
5
7
10
8
9
Page 35
MUH-A07YV - MUH-A09YV - MUH-A12YV -
E1E1E1
13-2. OUTDOOR UNIT
13-3. ACCESSORY ELECTRICAL PARTS AND FUNCTIONAL PARTS
8
1
2
3
7
4
6
5
12
13-2. OUTDOOR UNIT ELECTRICAL PARTS AND FUNCTIONAL PARTS
Part numbers that are circled are not shown in the illustration.
Q'ty/unit
MUH-A09YV-
1
1
1
1 1 1 1 1 1 1 1
E1
MUH-A12YV-
No.
1
E02 665 501 E02 835 301
2
E02 672 301 E02 752 353
3
E02 694 353 E02 696 353 E02 835 451
4
E02 836 451
5
E02 128 383
6
E02 817 374
7
E02 836 374
8
E02 699 310
9
E02 440 490
10
E02 095 382
11
E02 820 385
Part No.
Part name
PROPELLER OUTDOOR FAN MOTOR OUTDOOR FAN MOTOR COMPRESSOR CAPACITOR COMPRESSOR CAPACITOR COMPRESSOR CAPACITOR DEICER P.C. BOARD DEICER P.C. BOARD SURGE ABSORBER TERMINAL BLOCK TERMINAL BLOCK DEFROST THERMISTOR R. V. COIL FUSE VARISTOR
in Wiring
Symbol
Diagram
MF MF C1 C1 C1
DSAR
TB1
TB2 RT61 21S4
F61
NR61
MUH-A07YV-
1 1
1
1
1 1 1 1 1 1 1
E1
13
1
1
1
1 1 1 1 1 1 1 1
Remarks
E1
RC6V20­RA6V33­20+ /440V AC 25+ /440V AC 30+ /440V AC
3P 2P
250V 2A
13-3. ACCESSORY
12
E02 817 704
13
E02 440 705
DRAIN SOCKET DRAIN CAP
35
1 2
1 2
1 2
2PCS/SET
Page 36
HEAD OFFICE: MITSUBISHI DENKI BLDG.,2-2-3, MARUNOUCHI, CHIYODA-KU, TOKYO100-8310, JAPAN
CC
Copyright 2003 MITSUBISHI ELECTRIC ENGINEERING CO.,LTD Distributed in Feb. 2004. No.OB331 REVISED EDITION-A 6 Distributed in Dec. 2003. No.OB331 6 Made in Japan
New publication, effective Feb. 2004 Specifications subject to change without notice.
Loading...