Mitsubishi MSZ-FA35VA, MSZ-FA25VA-E1, MSZ-FA25VA-E1WH, MSZ-FA35VA-E1, MSZ-FA35VA-E1WH Service Manual

Page 1
SERVICE MANUAL
SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
Wireless type Models
E1
E1
(WH)
(WH)
MSZ-FA25VA ­MSZ-FA35VA -
No. OB371
Indication of model name
MSZ-FA25VA ­MSZ-FA35VA -
NOTE:
This service manual describes technical data of the indoor units.
•As for outdoor units MUZ-FA25VA- , MUZ-FA35VA- , MUZ-FA25VAH- and MUZ-FA35VAH- , refer to service manual OB372.
•As for outdoor units MXZ-3A54VA- , MXZ-4A71VA- and MXZ-4A80VA- ,
refer to service manual OB377.
E1
E1
E1
CONTENTS
1. TECHNICAL CHANGES ····································2
2. PART NAMES AND FUNCTIONS······················3
3. SPECIFICATION·················································5
4. NOISE CRITERIA CURVES·······························6
5. OUTLINES AND DIMENSIONS·························7
6. WIRING DIAGRAM ············································8
7. REFRIGERANT SYSTEM DIAGRAM················8
8. SERVICE FUNCTIONS ······································9
9. TROUBLESHOOTING ······································11
10. DISASSEMBLY INSTRUCTIONS·····················31
12. OPTIONAL PARTS ···········································38
E1E1E1
E1E1E1
Page 2
1
TECHNICAL CHANGES
MSZ-A09YV - ➔ MSZ-FA25VA -
MSZ-A12YV - MSZ-FA35VA -
1. Indication of capacity has been changed.(BTU base kW base)
2. Controller method between indoor and outdoor has been changed.
3. Power supply method has been changed (change to supply from outdoor unit).
4. Power supply cord has been removed.
5. Indoor electronic control P.C. board has been changed.
6. Position of terminal block has been changed.
7. Indoor fan motor has been changed. ( AC DC)
8. Indoor heat exchanger has been changed.
9. The horizontal vane motor unit has been changed. An external gear is added to the generalized stepping motor. The unit is structured so that the driving torque and stopping torque would increase.
Generalized stepping motor
NOTE: Do not remove the vane motor from the motor unit.
Do not disassemble the horizontal vane motor unit.
10. The vertical vane motor unit has been added. An external gear is added to the generalized stepping motor. The unit is structured so that the driving torque and stopping torque would increase.
E1E1 E1E1
Generalized stepping motor
NOTE: Do not remove the vane motor from the motor unit.
Do not disassemble the vertical vane motor unit.
11. Front panel driving motor unit which opens and closes the front panel has been added.
Front panel opening/closing
output gear
NOTE: Do not disassemble the front panel driving motor unit.
12. PLASMA DEODORIZING/AIR PURIFYING filter units have been added.
13. i-see Sensor has been added.
(i-see control operation and AREAsetting have been added.)
14. Air cleaning filer has been removed.
15. Signal of remote controller has been changed. (It is not available for the conventional models.)
16. Symbol on terminal block has been changed (to S1/S2/S3).
2
Page 3
2
Line flow fan
Air outlet
Vertical vane
Air inlet
Display section
Front panel
PLASMA DEODORIZING filter
Panel
Heat exchanger
Horizontal vane
Operation section
(When the front panel is opened)
Remote controller
POWER lamp
Remote control receiving section
PLASMA AIR PURIFYING filter
Anti-mold air filter
Fan guard
i-see Sensor
PLASMA/WASH lamp
AREA lamp
Emergency operation switch
WASH reset switch
Auto front panel
When the unit starts operating, the front panel opens automatically to draw in air. When the unit stops operating, the front panel closes automatically.
AREA lamp indicate AREA setting
In AREA setting, the horizontal air flow direction changes automatically according to the detection of i-see Sensor which detects the floor/ wall temperature to air-condition the room evenly.
i-see control operation
i-see sensor constantly measure floor/wall temperature to automatically adjust to the set temperature by estimating the temperature actually perceived by a person inside the room ("sensible temperature").
<Open> <Closed>
Auto front panel
PART NAMES AND FUNCTIONS
INDOOR UNIT
MSZ-FA25VA ­MSZ-FA35VA -
E1
E1
3
Page 4
1 2 3 4 5 6 7
Installation plate Installation plate fixing screw 4 o 25 mm Remote controller holder Fixing screw for 3 3.5 o 1.6 mm (Black) Battery (AAA) for remote controller Wireless remote controller Felt tape (Used for left or left-rear piping)
MSZ-FA25VA -
E1
MSZ-FA35VA -
E1
1 5 1 2 2 1 1
ON-TIMER button
CLOCK SET button
TIME SET buttons FORWARD button BACKWARD button
VANE CONTROL button (Horizontal vane button)
OFF-TIMER button
i-see button
(This diagram shows an overall view.)
Open the front lid.
PLASMA button
AREA button
RESET button
WIDE VANE button (Vertical vane button)
Signal transmitting section
Operation display section
Temperature buttons
OPERATE/STOP (ON/OFF) button
FAN SPEED CONTROL button
OPERATION SELECT button
ECONO COOL button
Indication of remote controller model is on back
MSZ-FA25VA ­MSZ-FA35VA -
E1
E1
ACCESSORIES
REMOTE CONTROLLER
4
Page 5
3
T3.15AL250V
NSEJ001DA1 12V DC 100" (at 25˚C)
MP20Z 12V DC 300" (at 25˚C) MSBPC20M16 12V DC 250" (at 25˚C) MSBPC20M11 12V DC 300" (at 25˚C)
ERZV14D471
A2TPMI334F0V50HSOBA060P5L1J4S 5V DC
3P
INDOOR UNIT
Item
Model
Fuse Front panel driving motor i-see Sensor motor Horizontal vane motor Vertical vane motor Varistor i-see Sensor Terminal block
MSZ-FA25VA -
E1
MSZ-FA35VA -
E1
(F11)
(MP)
(MT) (MV1) (MV2)
(NR11)
(RR)
(TB)
MSZ-FA25VA -
E1
MSZ-FA35VA -
E1
Indoor model
Function
Power supply
Single phase
230V,50Hz
10
0.25 33 — 57
0.25
RC0J40-EB
780O298O198
10
4
42
36W/29W/21
W
4 10 10 10
KM05A
Cooling
594
474W/354W/252
W
1,220
1,010W/800W/610
W
Heating
612
498W/384W/264
W
1,250
1,050W/850W/640
W
Single phase
230V,50Hz
10
0.25 33 — 57
0.25
RC0J40-EB
780O298O198
10
4
42
36W/29W/22
W
4 10 10 10
KM05A
Cooling
594
474W/354W/258
W
1,220
1,010W/800W/630
W
Heating
612
498W/384W/276
W
1,250
1,050W/850W/660
W
Air flow(Super High) Air flow(HighW/Med.W/LowW) Power outlet Running current 1 Power input 1 Auxiliary heater Power factor 1 Fan motor current 1 Model Dimensions WOHOD Weight Air direction Sound level(Super High) Sound level(HighW/Med.W/LowW) Fan speed(Super High) Fan speed(HighW/Med.W/LowW) Fan speed regulator Thermistor RT11(at25:) Thermistor RT12(at25:) Thermistor RT13(at25:) Remote controller model
K /h K /h
A A
W
A(kW)
%
A
mm
kg
dB(A) dB(A)
rpm rpm
k" k" k"
Electrical
data
Fan motor
Special
remarks
Capacity
MSZ-FA25VA -
E1
MSZ-FA35VA -
E1
Indoor model
Function
Cooling
546
450W/348W/252
W
1,130
960W/790W/610
W
Heating
540
420W/372W/264
W
1,120
910W/830W/640
W
Cooling
516W/390W/258
W
1,080W/860W/630
W
Heating
522W/402W/276
W
1,090W/880W/660
W
Air flow(Super High) Air flow(HighW/Med.W/LowW) Sound level(Super High) Sound level(HighW/Med.W/LowW) Fan speed(Super High) Fan speed(HighW/Med.W/LowW)
K /h K /h
dB(A) dB(A)
rpm rpm
Special
remarks
Capacity
42
36W/29W/21
W
642
42
36W/29W/22
W
1,300
SPECIFICATION
When outdoor unit is MXZ type.
NOTE : Test conditions are based on ISO 5151
Cooling : Indoor Dry-bulb temperature 27:Wet-bulb temperature 19: Heating : Indoor Dry-bulb temperature 20:Wet-bulb temperature 15: Refrigerant piping length (one way): 5m
w Reference value
Outdoor Dry-bulb temperature 35:Wet-bulb temperature 24: Outdoor Dry-bulb temperature 7: Wet-bulb temperature 6:
1 Measured under rated operating frequency.
Specifications and rating conditions of main electric parts
5
Page 6
4
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE
COOLING
FUNCTION
42 42
SPL(dB(A))
LINE
Super High
FAN SPEED
HEATING
Test conditions, Cooling : Dry-bulb temperature 27: Wet-bulb temperature 19:
Heating : Dry-bulb temperature 20: Wet-bulb temperature 15:
INDOORUNIT
WALL
MICROPHONE
0.8m
1m
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
Test conditions, Cooling : Dry-bulb temperature 27: Wet-bulb temperature 19:
APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE
COOLING
FUNCTION
42 42
SPL(dB(A))
LINE
Super High
FAN SPEED
HEATING
Heating : Dry-bulb temperature 20: Wet-bulb temperature 15:
NOISE CRITERIA CURVES
MSZ-FA25VA -
E1
MSZ-FA35VA -
E1
6
Page 7
5
OUTLINES AND DIMENSIONS
MSZ-FA25VA ­MSZ-FA35VA -
INDOOR UNIT
298
53.5 102624.5 58
E1 E1
780
19
11o26 Oblong hole
Installation plate
41.5 215
Indoor unit
100
Air out
11o20 Oblong hole
155 155
335 320
Air in
198 5
or more7
106
90
Wall hole
Installation plate
Liquid line [6.35 - 0.5m Gas line [9.52 - 0.43m Insulation [35 O.D
{
[19 I.D
Drain hose [16 (Connected part O.D)
Insulation [28
5555 225 225
214
7055
Unit : mm
14273.5
234
3 287.5
42.5
[65
159
Wireless remote controller
Required space (Indoor unit)
75 or more
10 or more
75 or more
55 or morew
wIn case of left, left back, or
left under piping (using spacer),
113 or more
7
Page 8
6
SYMBOL
DB111
F11
MF
MP MT
MV1
SYMBOL
MV2
NR11 PLASMA_A PLASMA_D
RR
RT11
SYMBOL
RT12 RT13
T111
TB
NAME DIODE STACK FUSE (T3.15AL250V) INDOOR FAN MOTOR FRONT PANEL DRIVING MOTOR i-see Sensor MOTOR VANE MOTOR (HORIZONTAL)
NAME VANE MOTOR (VERTICAL) VARISTOR PLASMA AIR PURIFYING FILTER UNIT PLASMA DEODORIZING FILTER UNIT i-see Sensor ROOM TEMPERATURE THERMISTOR
NAME INDOOR COIL THERMISTOR (MAIN) INDOOR COIL THERMISTOR (SUB) TRANSFORMER TERMINAL BLOCK
WIRING DIAGRAM
MSZ-FA25VA ­MSZ-FA35VA -
INDOOR UNIT
E1
E1
TO OUTDOOR UNIT CONNECTING
GRN
MV1
230V~
12-24V
LD104
CN
151
5
MV2
MODELS WIRING DIAGRAM
TB
S1 S2 S3
CN
1R1
2
5
INTERLOCK SWITCH(FAN)
POWER MONITOR RECEIVER P.C. BOARD
BLK
BLU RED
LD
101(A)
105(T)
8
SW P.C. BOARD
TAB3
2 1
CN201
LD
3
F11
MT
NR11
CN
110
5
DB111
4
RR
INDOOR ELECTRONIC CONTROL P.C. BOARD
T111
CN 1T1
CN
1T2
33
PLASMA_DPLASMA_A
SAFETY DEVICE (PLASMA UNIT)
4 3
CN
112
2 1
CN
111
1 2 3 4 5 6
CN
1U1
CN211
5
2
MP
RED
BLK WHT YLW BLU
RT13 RT12
RT11
5
MF
NOTE:1. About the outdoor side electric wiring refer to the outdoor unit electric wiring diagram for servicing.
2. Use copper conductors only. (For field wiring)
3. Symbols below indicate.
/: Terminal block, : Connector
7
MSZ-FA25VA -
INDOOR UNIT
REFRIGERANT SYSTEM DIAGRAM
E1
Refrigerant pipe [9.52
MSZ-FA35VA -
INDOOR UNIT
(with heat insulator)
Indoor coil
Indoor heat exchanger
thermistor RT12(main)
Flared connection
Indoor heat exchanger
Indoor coil thermistor RT13(sub)
Room temperature thermistor RT11
Room temperature thermistor RT11
E1
Indoor coil thermistor RT12(main)
Indoor coil thermistor RT13(sub)
Unit : mm
Refrigerant pipe [9.52 (with heat insulator)
Flared connection
Flared connection
Refrigerant flow in cooling Refrigerant flow in heating
Refrigerant pipe [6.35 (with heat insulator)
8
Flared connection
Refrigerant pipe [6.35 (with heat insulator)
Page 9
8
SERVICE FUNCTIONS
MSZ-FA25VA ­MSZ-FA35VA -
E1
E1
8-1. TIMER SHORT MODE
For service, set time can be shortened by short circuit of JPG and JPS the electronic control P.C. board. The time will be shortened as follows. (Refer to 9-7.) Set time : 1-minute 1-second Set time : 3-minute 3-second (It takes 3 minutes for the compressor to start operation. However, the starting time is
shortened by short circuit of JPG and JPS.)
8-2. P.C. BOARD MODIFICATION FOR INDIVIDUAL OPERATION
A maximum of 4 indoor units with wireless remote controllers can be used in a room. In this case, to operate each indoor unit individually by each remote controller, P.C. boards of remote controller must be modified according to the number of the indoor unit.
How to modify the remote controller P.C. board
Remove batteries before modification. The board has a print as shown below :
Remote controller model : KM05A
NOTE : For remodelling, take out
the batteries and press the OPERATE/STOP(ON/OFF) button twice or 3 times at first. After finish remodelling, put back the batteries then press the RESET button.
J1
The P.C. board has the print “J1” and “J2”. Solder “J1” and “J2” according to the number of indoor unit as shown in Table 1. After modification, press the RESET button.
J2
Table 1
1 unit operation No. 1 unit No. 2 unit No. 3 unit No. 4 unit
How to set the remote controller exclusively for particular indoor unit.
After you turn the breaker ON, the first remote controller that sends the signal to the indoor unit will be regarded as the remote controller for the indoor unit. The indoor unit will only accepts the signal from the remote controller that has been assigned to the indoor unit once they are set. The setting will be cancelled if the breaker has turned off, or the power supply has shut down. Please conduct the above setting once again after the power has restored.
No modification
– – –
2 units operation
Same as at left
Solder J1
– –
3 units operation
Same as at left Same as at left
Solder J2
4 units operation
Same as at left Same as at left Same as at left
Solder both J1 and J2
8-3. AUTO RESTART FUNCTION
When the indoor unit is controlled with the remote controller, the operation mode, the set temperature, and the fan speed are memorized by the indoor electronic control P.C. board. The “AUTO RESTART FUNCTION” sets to work the moment power has restored after power failure. Then, the unit will restart automatically.
Operation
1 If the main power has been cut, the operation settings remain. 2 After the power is restored, the unit restarts automatically according to the memory.
(However, it takes at least 3 minutes for the compressor to start running.)
9
Page 10
How to release “AUTO RESTART FUNCTION”
JR07
CN151 CN211CN112 CN1R1
CN212
CN1T1CN1T2
CN130
IC156
8-4. Remote controller
Be sure to set the slide switch inside the remote controller to an appropriate position in accordance with the installed position of the indoor unit. If the switch is not set correctly, the air conditioner may not function properly.
Area Left Center Right
Position of
the slide
switch
Display on
the remote
controller
Where is the indoor unit installed in your room?
Installed at left , if the distance is not more than 50 cm.
NOTE:If the indoor unit is installed more than 50 cm away from the side walls, cabinets or other nearby objects, set the slide
switch to the “center” position.
Installed at right, if the distance is not more than 50 cm.
Is the indoor unit in­stalled at right, left or center?
(Left) (Center) (Right)
Side swich
1Turn off the main power for the unit. 2Solder the Jumper wire to JR07 on the indoor electronic control P.C. board. (Refer to 9-7.)
NOTE:
The operation settings are memorized when 10 seconds have passed after the indoor unit was operated with the remote
controller.
If main power is turned OFF or a power failure occurs while AUTO START/STOP timer is active, the timer setting is
cancelled.
If the unit has been off with the remote controller before power failure, the auto restart function does not works as the
power button of the remote controller is off.
To prevent breaker off due to the rush of starting current, systematize other home appliance not to turn on at the same
time.
When some air conditioners are connected to the same supply system, if they are operated before power failure, the
starting current of all the compressors may flow simultaneously at restart. Therefore, the special counter-measures are required to prevent the main voltage-drop or the rush of the starting current by adding to the system that allows the units to start one by one.
10
Page 11
21
Stopper
Lock.
Left
Insert this end first.
9
RESET button
Housing point
TROUBLESHOOTING
MSZ-FA25VA ­MSZ-FA35VA -
E1
E1
9-1. Cautions on troubleshooting
1. Before troubleshooting, check the following:
1) Check the power supply voltage.
2) Check the indoor/outdoor connecting wire for mis-wiring.
2. Take care the following during servicing.
1) Before servicing the air conditioner, be sure to turn off the unit first with the remote controller, and then after confirming the horizontal vane is closed, turn off the breaker and / or disconnect the power plug.
2) Be sure to turn OFF the power supply before removing the front panel, the cabinet, the top panel, and the electronic control P.C. board.
3) When removing the electronic control P.C. board, hold the edge of the board with care NOT to apply stress on the components.
4) When connecting or disconnecting the connectors, hold the housing of the connector. DO NOT pull the lead wires.
3. Troubleshooting procedure
1) First, check if the OPERATION INDICATOR lamp on the indoor unit is flashing on and off to indicate an abnormality. To make sure, check how many times the abnormality indication is flashing on and off before starting service work.
2) Before servicing check that the connector and terminal are connected properly.
3) If the electronic control P.C. board is supposed to be defective, check the copper foil pattern for disconnection and the
components for bursting and discoloration.
4) When troubleshooting, refer to 9-2., 9-3. and 9-4.
4. How to replace batteries
Weak batteries may cause the remote controller malfunction. In this case, replace the batteries to operate the remote controller normally.
1 Remove the front lid and insert batteries.
Then reattach the front lid.
Lead wiring
2 Press RESET button with tip end of ball point pen
or the like, and then use the remote controller.
Insert the negative pole of the batteries first. Check if the polarity of the batteries are correct.
NOTE : 1. If RESET button is not pressed, the remote controller may not operate correctly.
2. This remote controller has a circuit to automatically reset the microcomputer when batteries are replaced. This function is equipped to prevent the microcomputer from malfunctioning due to the voltage drop caused by the battery replacement.
5. How to install the horizontal vane
If horizontal vane is not installed correctly, All of the operation indicator lamps will blink. In this case, install the horizontal vane correctly by following the procedures 1 to 2.
NOTE: Before installation of the horizontal vane, turn OFF the power supply.
22
In procedure
stoppers until they click into place.
11
lock the
Page 12
WASH
reset
E.O.
SW
Plasma element holder
6. How to remove and install PLASMA DEODORIZING / AIR PURIFYING filter units
If PLASMA/WASH lamp on the indoor unit blinks, clean the filters as soon as possible. The lamp will start blinking when accumulated operating time exceeds 330 hours.
<Remove>
Figure 1.
(1) Switch the indoor unit OFF with the remote controller and
disconnect the power supply plug and/ or turn OFF the breaker. NOTE: Otherwise, you may get injured since PLASMA
DEODORIZING/AIR PURIFYING filter units are charged with high voltage.
(2) Hold the knobs on both sides of the front panel and lift the
panel up until its level. (3) Remove the anti-mold air filter.(See Figure 1.) (4) Remove PLASMA DEODORIZING/AIR PURIFYING filter
units. (See Figure 2.)
Figure 2.
<Install>
Install PLASMA DEODORIZING/AIR PURIFYING filter units by following the removal procedure in reverse. (1) Insert the top of PLASMA DEODORIZING/AIR PURIFYING filter
units into the aperture in the plasma element holder.
Figure 3.
(See Figure 3.)
(2) Push in PLASMA DEODORIZING/AIR PURIFYING filter units
until they click into place.
•The front panel does not close if PLASMA DEODORIZING/AIR PURIFYING filter units are not installed properly.
(3) Install the anti-mold air filter. (4) Connect the power supply plug and/ or turn ON the breaker. (5) Press WASH reset switch. A short “beep” is heard and the blinks
of PLASMA/WASH lamp will be cancelled. Make sure PLASMA/ WASH lamp is not blinking at the start of operation next time. (See Figure 4.)
(6) Hold both sides of the front panel and close the front panel.
Figure 4.
(7) Press the 3 positions on the front panel as indicated by the
arrows.(See Figure 5.)
NOTE: Install PLASMA DEODORIZING/AIR PURIFYING filter units only when they are completely dry. If the filter unit remains wet, PLASMA/WASH lamp may blink and the plasma function may be disabled.(When PLASMA DEODORIZING/AIR PURIFYING filter units are cleaned.)
Figure 5.
12
Page 13
INFORMATION FOR MULTI SYSTEM AIR CONDITIONER
Lighted Blinking Not lighted
OUTDOOR UNIT : MXZ series
Multi system air conditioner can connect two or more indoor units with one outdoor unit.
•Unit won’t operate in case the total capacity of indoor units exceeds the capacity of outdoor units. Do not connect indoor units beyond the outdoor unit capacity. Operation indicator lamp flashes as shown in the figure below.
•When you try to operate two or more indoor units with one outdoor unit simultaneously, one for the cooling and the other for heating, the operation mode of the indoor unit that operates earlier is selected. The other indoor units which start the operation later cannot operate, indicating as shown in the figure below. In this case, please set all the indoor units to the same operation mode.
•When indoor units start the operation while the defrosting of outdoor unit is being done, it takes a few minutes (max. 10 minutes) to blow out the warm air.
•In the heating operation, though indoor unit that does not operate may get warm or the sound of refrigerant flowing may be heard, they are not malfunction. The reason is that the refrigerant continuously flows into it.
13
Page 14
9-2. Failure mode recall function
Operational procedure
Yes
(Blinks)
No
(OFF)
Yes
No
Releasing the failure mode recall function
W1. Regardless of normal or abnormal, a short beep is emitted once as the signal is received.
Note1.Make sure to release the failure mode recall function once it's set up, otherwise the unit cannot operate properly.
2.If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.
W2. Blinking pattern when the indoor unit is abnormal:
W3.Blinking pattern when the outdoor unit is abnormal:
ON
OFF
Beeps
Repeated cycle Repeated cycle
ON
OFF
No beep Beeps
Repeated cycle
2.5-second OFF
Blinking at 0.5­second interval
2.5-second OFF 3-second ON
Blinking at 0.5­second interval
Beeps
Repeated cycle
2.5-second OFF
Blinking at 0.5­second interval
No beep Beeps
Repeated cycle
2.5-second OFF 3-second ON
Blinking at 0.5­second interval
Repeated cycle
Beeps
Does POWER lamp on the indoor unit blink at the interval of 0.5 seconds? Blinks: Either indoor or outdoor unit is abnormal. Beep sounds are emitted at the same timing of the blinking of POWER lamp. W2
The cause of abnormality cannot be found because the abnormality doesn't recur.
Setting up the failure mode recall function
Before blinking, does POWER lamp stay ON for 3 seconds? Stays ON for 3 seconds (without beep): The outdoor unit is abnormal.
The indoor unit is abnormal. Check the blinking pattern, and refer to confirm the abnormal point(9-2.4.). Make sure to check at least two consecutive blinking cycles. W2
Turn ON the power supply. 1 While pressing both OPERATION SELECT button and TOO COOL button on the remote controller at the same time, press RESET button. 2 First, release RESET button. And release the other two buttons since all LCD in operation display section of the remote controller is displayed after 3 seconds.
Deleting the abnormal condition
1After repairing the unit, recall the failure mode again according to "Setting up the failure mode recall function" mentioned above. 2Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted. 3Release the failure mode recall function according to "Releasing the failure mode recall function" mentioned above.
Repair the defective parts.
Release the failure mode recall function by the following procedures. 1With the remote controller headed towards the indoor unit, press any button that is not used in this failure mode recall function (e.g. TIMER button) . OR
1Turn OFF the power supply and turn ON it again. 2Press RESET button of the remote controller.
Judgment of indoor/outdoor abnormality
W1 Press OPERATE/STOP(ON/OFF) button of the remote controller (the set temperature is displayed). With the remote controller headed towards the indoor unit, press TOO COOL or TOO WARM button to adjust the set temperature to 24:.
Indoor unit is normal. There is a possibility that the plasma or outdoor unit is abnormal. Confirm the presence of abnormality according to the flow chart of the the prasma unit or detailed outdoor unit failure mode recall function.
The outdoor unit is abnormal. Check the blinking pattern, and refer to confirm the abnormal point. Make sure to check at least two consecutive blinking cycles. W3
1 While pressing both OPERATION SELECT button and TOO COOL button on the
remote controller at the same time, press RESET button. 2 First, release RESET button. And release the other two buttons since all LCD in operation display section of the remote controller is displayed after 3 seconds.
•As for outdoor unit MUZ type, refer to service manual OB372. As for outdoor unit MXZ type, refer to service manual OB377.
Outline of the function This air conditioner can memorize the abnormal condition which has occurred once. Even though LED indication listed on the troubleshooting check table disappears, the memorized failure details can be recalled. This mode is very useful when the unit needs to be repaired for the abnormality which doesn't recur.
1. Flow chart of the indoor/outdoor unit failure mode recall function
14
Page 15
2. Flow chart of PLASMA DEODORIZING/PLASMA AIR PURIFYING power failure mode recall function
Operational procedure
Note1. Make sure to release the failure mode recall function once it's set up, otherwise the unit cannot operate properly.
2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized. W2.Blinking pattern when outdoor unit is abnormal:
Yes
(Blinks)
No
(OFF)
W1. Regardless of normal or abnormal, a short beep is emitted as the signal is received.
Does POWER lamp on the indoor unit blink at the interval of 0.5 seconds? W2 Blinks: The plasma unit is abnormal. Beep sounds are emitted at the same timing of the blinking of POWER lamp.
Deleting the abnormal condition
1After repairing the unit, recall the failure mode again according to "Setting up the failure mode recall function" mentioned above. 2Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted. 3Release the failure mode recall function according to "Releasing the failure mode recall function" mentioned above.
Repair the defective parts.
Confirmation of abnormality presence
W1 With the remote controller headed towards the indoor unit, press TOO COOL or TOO WARM button to adjust the set temperature to 23:.
The plasma unit is normal.
Releasing the failure mode recall function
Release the failure mode recall function by the following procedures. 1With the remote controller headed towards the indoor unit, press any button that is not used in this failure mode recall function (e.g. TIMER button) . OR
1Turn OFF the power supply and turn ON it again. 2Press RESET button of the remote controller.
The plasma unit is abnormal. Check the blinking pattern, and refer to confirm the abnormal point(9-2.5.). Make sure to check at least two consecutive blinking cycles. W2
Release the failure mode recall function according to the left mentioned procedure.
Confirm that the remote controller is in the failure mode recall function.
There is a possibility that the plasma unit is abnormal. Confirm the presence of abnormality according to the following procedures.
ON
OFF
Beeps
Repeated cycle Repeated cycle
2.5-second OFF
Blinking at 0.5­second interval
Beeps
Repeated cycle
2.5-second OFF
Blinking at 0.5­second interval
Beeps
ActionPLASMA/WASH lamp
Continuously flashes
2-time flash
Follow "Check of
PLASMA DEODORIZING
power" or "Check of
PLASMA AIR PURIFYING
power"
to identify the error.(Refer to 9-6.F or G.) PLASMA DEODORIZING power or PLASMA AIR PURIFYING power
control circuit on the indoor
electronic control P.C. board is out of order.(Refer to 9-6.F or G.)
PLASMA DEODORIZING/PLASMA AIR PURIFYING power goes ON when PLASMA button on the remote controller is pressed once while the indoor error indication is being checked or after one short beep sound (signal reception beep) is emitted. PLASMA button is pressed, the power of plasma is changed in sequence: PLASMA DEODORIZING power goes ON PLASMA AIR PURIFYING power goes ON Cancel Check the operation display section of the remote controller to confirm that PLASMA DEODORIZING power or PLASMA AIR PURIFYING power is activated. While PLASMA/WASH lamp stays OFF, and it means normal. Flashing PLASMA/WASH lamp means abnormal, and the plasma power is not being conducted.
3. PLASMA DEODORIZING/PLASMA AIR PURIFYING power operation check
NOTE: Perform the above mentioned check with the front panel closed. Panel open is detected by the SAFETY DEVICE
(PLASMA UNIT).
15
Page 16
4. Indoor unit failure mode table
12-time flash
2.5-second OFF
Replace the indoor electronic control P.C. board.
Indoor control system
When it cannot properly read data in the nonvolatile memory of the indoor electronic control P.C. board.
11-time flash
2.5-second OFF
Refer to 9-6.A "Check of indoor fan motor".
Indoor fan motor
When the rotational frequency feedback signal is not emit during 12-second the indoor fan operation.
2-time flash
2.5-second OFF
Refer to the characteristic of the main indoor coil thermistor, the sub indoor coil thermistor (9-7.).
Indoor coil thermistor
When the indoor coil thermistor short or open circuit is detected every 8 seconds during operation.
3-time flash
2.5-second OFF
Refer to 9-6.D "How to check miswiring and serial signal error".
Serial signal error
When the serial signal from outdoor unit is not received for a maximum of 6 minutes.
1-time flash every 0.5-second
Refer to the characteristics of the room temperature thermistor (9-7.).
Room temperature thermistor
When the room temperature thermistor short or open circuit is detected every 8 seconds during operation.
Not lighted Normal
POWER lamp
Check point
Abnormal point
(Failure mode)
Detection method
5-time flash
Refer to 9-6.F"Check of PLASMA DEODORIZING power" or 9-6.G"Check of PLASMA AIR PURIFYING power".
When the voltage between CN1 1(+) and 2(GND) on the PLASMA POWER P.C. board (PLASMA DEODORIZING or PLASMA AIR PURIFYING) rises above the normal voltage value (3V).
4-time flash
Refer to 9-6.F"Check of PLASMA DEODORIZING power" or 9-6.G"Check of PLASMA AIR PURIFYING power".
PLASMA DEODORIZING/ PLASMA AIR PURIFYING power
When the voltage between CN1 1(+) and 2(GND) on the PLASMA POWER P.C. board (PLASMA DEODORIZING or PLASMA AIR PURIFYING) falls significantly. (0.4V / 0.5ms)
3-time flash
Refer to 9-6.F"Check of PLASMA DEODORIZING power" or 9-6.G"Check of PLASMA AIR PURIFYING power".
Abnormal electric discharge error 1
When the voltage between CN1 1(+) and 2(GND) on the PLASMA POWER P.C. board (PLASMA DEODORIZING or PLASMA AIR PURIFYING) falls 0.9V below the normal range voltage.
2-time flash
Refer to 9-6.F"Check of PLASMA DEODORIZING power" or 9-6.G"Check of PLASMA AIR PURIFYING power".
Replace the indoor electronic control P.C. board.
Spark discharge
1-time flash
PLASMA DEODORIZING/ PLASMA AIR PURIFYING power control
When the voltage between CN1 1(+) and 2(GND) on the PLASMA POWER P.C. board (PLASMA DEODORIZING or PLASMA AIR PURIFYING) falls below 1.6V(spark discharge judgment voltage).
When PLASMA DEODORIZING/PLASMA AIR PURIFYING power cannot be turned OFF.
POWER lamp
Check point
Abnormal point
(Failure mode)
Detection method
Abnormal electric discharge error 2
NOTE: Blinking patterns of this mode differs from the ones of Troubleshooting check table(9-4.).
5. PLASMA DEODORIZING/PLASMA AIR PURIFYING power failure mode table
w As soon as an error is detected, PLASMA DEODORIZING power or PLASMAAIR PURIFYING power goes OFF,
therefore measuring instrument which records the voltage wave is required in order to perform the above men­tioned voltage measurement.
16
Page 17
9-3. Instruction of troubleshooting
Start
w"Test Run operation" means the operation within 30 minutes after EMERGNCY OPERATION switch is pressed.
If blinking of OPERATION INDICATOR lamp cannot be checked, it can be checked with failure mode recall function.
Indoor unit operates. Outdoor unit doesn't operate.
Outdoor unit operates in only Test Run operation. w
Check room temperature thermistor. Refer to 9-7. "Test point diagram and voltage".
Indoor unit operates. Outdoor unit doesn't operate normally.
Outdoor unit doesn't operate even in Test Run operation. w
Refer to "How to check inverter/ compressor".
Unit doesn't operate normal operation in COOL or HEAT mode.
Refer to "Check of R.V. coil".
Indoor unit doesn't receive the signal from remote controller.
Indoor unit operates, when EMERGENCY OPERATION switch is pressed.
Refer to 9-6.B "Check of remote controller and receiver P.C. board".
OPERATION INDICATOR lamp on the indoor unit is flashing on and off.
Indoor unit doesn't operate, when EMERGENCY OPERATION switch is pressed.
1. Check indoor / outdoor connecting wire. (Check if the power is supplied to the indoor unit.)
2. Refer to 9-6.C "Check of indoor electronic control P.C. board and indoor fan motor".
OPERATION INDICATOR lamp on the indoor unit stays off.
PLASMA/WASH lamp 2-time flash cause: Indoor unit
• Trouble of PLASMA DEODORIZNG power control or PLASMA AIR PURIFYING power control
Replace the indoor electronic control P.C. board.
As for outdoor unit MUZ type,
refer to service manual OB372. As for outdoor unit MXZ type, refer to service manual OB377.
All lamps Flash on and off at 0.5-second intervals Cause: Indoor unit
• The horizontal vane is not installed correctly.
Refer to 9-6. E "Check of installation of the horizontal vane".
POWER lamp Flash on and off at 0.5-second intervals Cause: Indoor/ Outdoor unit
• Mis-wiring or trouble of serial signal
Refer to 9-6. D "How to check of mis-wiring and serial signal error (when outdoor unit doesn't work)".
POWER lamp 2-time flash Cause: Indoor unit
• Trouble of room temp­ erature/ indoor coil thermistor
Check room temperature thermistor and indoor coil thermis­tor. Refer to 9-7. "Test point diagram and voltage".
POWER lamp 3-time flash Cause: Indoor unit
• Trouble of indoor fan motor
Refer to 9-6. A "Check of indoor fan motor".
Left lamp of AREA lamp 4-time flash Cause: Indoor unit
• Trouble of indoor unit control system
Replace the indoor electronic control P.C. board.
17
POWER lamp 5-time flash Cause: Outdoor unit
• Outdoor power system abnormality
Refer to "How to check inverter/ compressor".
POWER lamp 6-time flash Cause: Outdoor unit
• Trouble of thermistor in outdoor unit
Refer to "Check of outdoor thermistors".
POWER lamp 7-time flash Cause: Outdoor unit
• Trouble of outdoor control system
Replace the inverter P.C. board or the outdoor electronic control P.C. board.
POWER lamp 14-time flash Cause: Outdoor unit
• Other abnormality
Check "Flow chart of the detailed outdoor unit failure mode recall function."
Page 18
No.
1
3
5
6
SymptomOperation indicator lamp Detection method
Check point
POWER lamp flashes.
0.5-second ON
0.5-second OFF
Mis-Wiring or serial signal
Outdoor power system
Outdoor thermistors
Outdoor control system
Indoor coil thermistor
When the serial signal form the outdoor unit is not received for a maximum of 6 minutes.
When it consecutively occurs 3 times that the compressor stops for overcurrent protection or start-up failure protection witth in 1 minute after start-up.
When the outdoor thermistors short or open circuit during the compressor operation.
When it cannot properly read data in the nonvolatile memory of the inverter P.C. board or the outdoor electronic control P.C. board.
• Refer to "Check of outdoor thermistor".
Refer to service manual OB372 or OB377.
• Refer to "Check of inverter/ compressor".
Refer to service manual OB372 or OB377. Check the stop valve.
• Replace the inverter P.C. board or the outdoor
electronic control P.C. board.
Refer to service manual
OB372 or OB377.
• Refer to 9-6.D "How to check
mis-wiring and serial signal
error".
4
Indoor fan motor
7
Abnormal
point
Outdoor unit does not operate.
Room tempera­ture thermistor
POWER lamp flashes. 2-time flash
2.5-second OFF
When the indoor coil or the room temperature thermistor is short or open circuit.
• Refer to 9-7.the
characteristics of indoor coil thermistor, and the room temperature thermistor.
POWER lamp flashes. 3-time flash
2.5-second OFF
When the rotational frequency feedback signal is not emit during the indoor fan operation.
• Refer to 9-7.A "Check of indoor fan motor".
Indoor unit and outdoor unit do not operate.
POWER lamp flashes. 5-time flash
2.5-second OFF POWER lamp flashes.
6-time flash
2.5-second OFF
Indoor unit and outdoor unit do not operate.
Indoor unit and outdoor unit do not operate.
Indoor unit and outdoor unit do not operate.
Other abnonmality
An abnormality other than above mentioned is deteced.
• Confirm the abnormarity in detail using the failure mode recall function.
Indoor unit and outdoor unit do not operate.
Indoor unit and outdoor unit do not operate.
8
Outdoor control system
When it cannot properly read data in the nonvolatile memory of the inverter P.C. board or the outdoor electronic control P.C. board.
• Check the blinking pattern of the LED on the inverter P.C. board or the outdoor lectronic control P.C. board.
2
Outdoor unit does not operate.
POWER lamp flashes. 7-time flash
2.5-second OFF
POWER lamp flashes. 14-time flash
2.5-second OFF
POWER lamp lights up
9-4. Troubleshooting check table
Lighted Blinking Not lighted
· Flashing of POWER lamp indicates abnormalities.
NOTE : Before taking measures, make sure that the symptom reappears for accurate troubleshooting.
Self check table
NOTE : When the indoor unit has started operation and the above detection method has detected an abnormality (the first
detection after the power ON), the indoor electronic control P.C. board turns OFF the indoor fan motor with OPERATION INDICATOR lamp flashing.
18
Page 19
Lighted
No.
1
SymptomOperation indicator lamp Detection method
Check point
Abnormal
point
Left lamp of AREA lamp flashes. 4-time flash
2.5-second OFF
Indoor control system
When it cannot properly read data in the nonvolatile memory of the indoor electronic control P.C. board.
Indoor unit and outdoor unit do not operate.
• Replace the indoor electronic control P.C. board.
No.
1
SymptomOperation indicator lamp Detection method
Check point
Abnormal
point
0.5-second ON
0.5-second OFF
When the electricity is not conducted to the interlock switch (Fan) of the horizontal vane.
• Refer to 9-6.E "Check of installation of the horizontal vane".
Indoor unit and outdoor unit do not operate.
Attachment of the horizontal vane
All lamps flash at the same time.
No.
SymptomOperation indicator lamp Detection method
Check point
Abnormal
point
1
MXZ type
Operation mode setting
Outdoor unit operates but indoor unit does not operate.
When the operation mode of the each indoor unit is differently set to COOL(includes DRY) and HEAT at the same time, the operation mode of the indoor unit that has operated at first has the priority.
• Unify the operation mode. Refer to service manual OB377.
2.5-second OFF
Both lamps flash
Lighted Blinking Not lighted
No.
1
SymptomOperation indicator lamp Detection method
Check point
Abnormal
point
PLASMA/WASH lamp flashes. 2-time flash
2.5-second OFF
When PLASMA DEODORIZING power or PLASMA AIR PURIFYING power can not be turned OFF.
Indoor unit and outdoor unit do not operate.
PLASMA DEODORIZING/ PLASMA AIR PURIFYING power control
• Replace the indoor electronic control P.C. board.
Blinking Not lighted
· Flashing of AREAlamp(left-hand side lamp) indicates abnormality.
NOTE : Before taking measures, make sure that the symptom reappears for accurate troubleshooting.
Self check table
Lighted Blinking Not lighted
Lighted Blinking Not lighted
· Flashing of All lamps indicate abnormality.
· Flashing of AREAlamp(both lamps) indicates abnormality.
· POWER lamp is lighted.
NOTE : When the indoor unit has started operation and the above detection method has detected an abnormality (the first
detection after the power ON), the indoor electronic control P.C. board turns OFF the indoor fan motor with OPERATION INDICATOR lamp flashing.
· Flashing of PLASMA/WASH lamp indicates abnormality.
19
Page 20
9-5. Trouble criterion of main parts
Part name FigureCheck method and criterion
Measure the resistance with a tester. (Part temperature 10˚C ~ 30˚C)
Normal
8 k" ~ 20 k"
Abnormal
Open or short-circuit
Room temperature thermistor(RT11)
Indoor coil thermistor (RT12(MAIN), RT13(SUB))
Horizontal vane motor(MV1)
Normal
BRN-other one
Abnormal
Open or short-circuit
Measure the resistance between the terminals with a tester. (Part temperature 10°C ~ 30°C)
235 " ~ 255 "
Color of the lead wire
Vertical vane motor(MV2)
i-see Sensor motor(MT)
Normal
Abnormal
Open or short-circuit
Measure the resistance between the terminals with a tester. (Part temperature 10°C ~ 30°C)
Front panel driving motor (MP)
Normal
Abnormal
Open or short-circuit
Measure the resistance between the terminals with a tester. (Part temperature 10°C ~ 30°C)
94 " ~ 102 "
i-see Sensor(RR)
Turn the power ON(i-see Sensor is energized) with the aluminum block part on the i-see Sensor P.C. board (upper part of i-see Sensor) covered with black vinyl tape, then measure the voltage between connector terminals of i-see Sensor using tester. (Part temperature 10 ~ 40°C)
282 " ~ 306 "
Normal range
2(-)
-
4(+)
1(+) - 2(-)
Below 1.874 or above 3.387V DC Below 1.010 or above 1.420V DC
1.874 ~ 3.387V DC
1.010 ~ 1.420V DC
i-see Sensor connector terminals
Abnormal
NOTE: Pay attention to static electricity.
Indoor fan motor(MF)
Check 9-6. A.
PLASMA DEODORIZING/ PLASMA AIR PURIFYING power
Check 9-6. F or G.
Color of the lead wire
BRN-other one
Color of the lead wire
BRN-other one
RED
YLW BRN
ORN
GRN
ROTOR
RED
YLW BRN
ORN
GRN
ROTOR
RED
YLW BRN
ORN
GRN
ROTOR
MSZ-FA25VA - MSZ-FA35VA -
E1E1
Aluminum block
i-see Sensor
w The aluminum block
part is covered with black vinyl tape.
Connector
i-see Sensor P.C. board
Black vinyl tape
20
Page 21
wIf 12 seconds or more passes after EMERGENCY OPERATION switch is pressed, the voltage mentioned above 2 goes 0V DC although the indoor electric control P.C. board is normal.
Indoor electronic control P.C. board
Pay careful attention to the high voltage on the fan motor connector CN211.
Yes
No
No
Changed
Unchanged
Is there any foreign matter that interferes the rotation of the line flow fan?
Turn OFF the power supply. Insert a stick such as a screw driver into the air outlet, and check if there is any catch in the rotation of the line flow fan.
Adjust the line flow fan and remove the foreign matter.
w
Turn ON the power supply, wait 5 seconds or more, and then press EMERGENCY OPERATION switch. Measure the supply voltage as follows within 12 seconds after EMERGENCY OPERATION switch is pressed. If more than 12 seconds passes by, turn OFF the power supply and turn ON it again, then measure the voltage.
1.Measure the voltage between CN211 1(+) and 3(-).
2.Measure the voltage between CN211 5(+) and 3(-).
Is there 311V DC between CN211 1 (+) and 3 (-), and does the voltage between CN211 5(+) and 3(-) rise to the range of 3 to 6V DC within 12 seconds after EMERGENCY OPERATION switch is pressed?
Yes
Replace the indoor fan motor.
CN211
Replace the indoor electronic control P.C. board.
The indoor fan motor error has occurred, and the indoor fan repeats "12-second ON and 30-second OFF" 3 times, and then stops.
Measure the voltage between CN211 6(+) and 3(-) while the fan motor is rotating.
Is it unchanged holding 0V DC or 15V DC?
Replace the indoor fan motor.
Replace the indoor electronic control P.C. board.
The indoor fan motor error has occurred, and the indoor fan doesn't operate.
9-6. Troubleshooting flow
When POWER lamp flashes 3-time. Indoor fan does not operate.
A
Check of indoor fan motor
21
Page 22
Indoor unit operates by pressing EMERGENCY OPERATION switch, but does not operate with the remote controller.
Check of remote controller and receiver P.C. board
B
wCheck if the remote controller is exclusive for this air conditioner.
Switch on the remote controller.
Is LCD display on the the remote controller visible?
Yes
Remove the batteries, then set them back and press RESET button. (Refer to 9-1.4.) Check if the unit operates with the remote controller.
Does the unit operate with the remote controller?
Yes
OK
No (not clear)
No
Replace the batteries. (Refer to 9-1.4.)
Turn on a radio to AM and press switch on the remote controller.
Is noise heard from radio?
Yes
Are there any fluorescent lights of inverter or rapid-start type within the range of 1m?
Replace the indoor electronic control P.C. board.
No
Yes
Replace the remote controller.
Reinstall the unit away from lights.
Attach a filter on receiving part.
22
Page 23
The unit does not operate with the remote controller. Also, POWER lamp does not light up by pressing EMERGENCY OPERATION switch.
Check of indoor electronic control P.C. board and indoor fan motor
C
Turn OFF the power supply. Remove indoor fan motor connector CN211, vane motor connector CN151 front panel driving motor connector connector CN1U1 and i-see Sensor motor connector CN110 from the indoor electronic control P.C. board and turn ON the power supply.
Does the unit operate with the remote controller? Does POWER lamp light up by pressing EMERGENCY OPERATION switch?
No
Turn OFF the power supply. Check both “parts side” and “pattern side” of the indoor electronic control P.C. board visually.
Yes
Measure the resistance of the front panel driving motor coil. Normal value is approx. 100'
Measure the resistance of i-see Sensor motor coil. Normal value is approx. 300'
Measure the resistance between CN211 3 and 4 of the indoor fan motor connector. Normal value is approx. 30k' to 50k'.
Measure the resistance of the horizontal vane motor coil and the vertical vane motor coil. Normal value is approx. 300' or 250'.
Replace the varistor(NR11) and fuse(F11).
Yes
Are the varistor(NR11) burnt and the fuse(F11) blown?
Be sure to check both the fuse and the varistor in any case.
Is the fuse(F11) blown only?
w1,2
Yes
No
No
Short circuit: Replace the front panel driving motor and the indoor electronic control P.C. board.
Short circuit: Replace i-see Sensor motor and the indoor electronic control P.C. board.
Short circuit: Replace the indoor fan motor.
Short circuit: Replace the horizontal vane motor, the vertical vane motor and the indoor electronic control P.C. board.
Indoor electronic control P.C.Board
CN201
Fuse(F11)
w3. Short circuit: The indoor fan motor is abnormal.
Measure the cement resistance R111 on the indoor electronic control P.C. board.
CN211
Varistor(NR11)
Measure the resistance between 1(+) and 3(-) of the indoor fan motor connector (to CN211 on the indoor electronic control P.C. board) .
w3
Is the resistance 1M' or more?
Yes
Replace the fuse (F11).
Replace the indoor electronic control P.C. board.
No
Is the resistance approx. 4'?
23
w1. The fan motor connector's 1 lead wire is red, whereas 3 is black. w2. Connect "+" of the tester to fan motor connector's 1 lead
wire, and "-" to 3 lead wire, otherwise the resistance cannot be measured properly.
Replace the fuse (F11) and the indoor fan motor.
No
Replace the indoor electronic control P.C. board and the indoor fan motor.
Yes
Page 24
When POWER lamp flashes ON and OFF in every 0.5-second.
Is there rated voltage of 230V AC in the power supply?
In 3 minutes after turning ON the power supply of the outdoor unit, does the LED on the inverter P.C. board repeat quick blinking "3.6-second-OFF and 0.8-second-ON"? Be sure to check above in 3 minutes after turning ON. After 3 minutes, LED blinks 6 times. When the inverter P.C. board is normal, LED also blinks 6 times after 3 minutes.
Is there any mis-wiring, poor contact, or wire disconnection of the indoor/outdoor connecting wire?
W1. Mis-wiring may damage indoor electronic control P.C. board during the operation. Be sure to confirm the wiring is correct before the operation starts.
(Lighting)
No
Yes
No
Yes
Yes
No
Yes
No
Yes
No
W2 Be careful to the residual voltage of smoothing capacitor.
Be sure to release the failure-mode recall function after checking.
No
No
Yes
No
Yes
Serial signal error display
Yes
Yes
No
Yes
As for outdoor unit MUZ type,refer to service manual OB372. As for outdoor unit MXZ type,refer to service manual OB377.
Inverter P.C.board (Parts side)
LED
Blinking
Turn OFF the power supply.
Turn ON the power supply.
Is there 230V AC between outdoor terminal block S1 and S2?
Does POWER lamp light up? <Confirmation of the power to the indoor unit>
Press EMERGENCY OPERATION switch.
Check the power supply.
Is the self-check of the indoor unit displayed 6 minutes after?
POWER lamp blinks quickly.
A
Turn OFF the power supply. Check once more if the indoor/outdoor connecting wire is not mis-wiring.
Short-circuit outdoor terminal block S2 and S3. W1
B
Turn ON the power supply of the outdoor unit.
Check the wiring.
Make them sure.
Remove the short-circuit between outdoor terminal block S2 and S3. Is there amplitude of 10 to 20V DC between outdoor terminal block S2 and S3? <Confirmation of serial signal>
Is there 230V AC between outdoor terminal block S1 and S2? <Confirmation of power voltage>
Replace the indoor electronic control P.C. board.
Replace the inverter P.C. board. W2
Is there any error of the indoor/outdoor connecting wire, such as the damage of the wire, intermediate connection, poor contact to the terminal block?
Is there any error of the indoor/outdoor connecting wire, such as the damage of the wire, intermediate connection, poor contact to the terminal block?
Replace the indoor/outdoor connecting.
Replace the indoor/outdoor connecting.
Is serial signal error indicated 6 minutes later?
Yes
No
· Turn OFF inverter-controlled lighting equipment.
· Turn OFF the power supply and then turn ON again.
· Press EMERGENCY OPERATION switch.
B
· Reinstall either the unit or the light each other away.
· Attach a filter on receiving section of the indoor unit.
A
Outdoor unit does not operate.
D
How to check mis-wiring and serial signal error
24
Page 25
Start
Replace the indoor electronic control P.C. board.
Replace the interlock switch(Fan).
Is the stopper of the horizontal vane locked to the indoor unit correctly?
Yes
No
Is there resistance 0 "?
Relock the stopper of the horizontal vane to the indoor unit. Refer to 9-1.5.
Yes
Are all lamp flashing?
Yes
No()
No
OK
Turn ON the power supply.
To check the continuity of the interlock switch (Fan), measure the resistance of connector 1 - 2 connected to CN1R1 on the indoor electronic control P.C. board.
Turn OFF the power supply.
Turn OFF the power supply.
When All lamps flash ON and OFF every 0.5-second. Indoor unit and outdoor unit do not operate.
Check of installation of the horizontal vane
E
25
Page 26
When PLASMA/WASH lamp flashes 2-time.
After performing the check, make sure to release the failure mode recall function.
Make sure that the front panel is firmly closed.
1 During pressing both OPERATION SELECT button and TOO COOL button on the remote controller at the same time, press RESET button. 2 First, release RESET button. And release the other two buttons since all LCD in operation display section of the remote controller is displayed after 3 seconds.
(Failure mode recall function is set.)
3 Press OPERATE/STOP (ON/OFF) button. 4 After a short beep sound is emitted, press
once PLASMA button. PLASMA DEODORIZING operation is selected. wThe plasma power operation check mode is set.(Refer to 9-2.5.)
PLASMA DEODORIZING power supply is normal. The front panel is not firmly closed, therefore the protection by the interlock switch is active.
If the plasma unit is dirty, clean the unit. After cleaning, make sure to attach the unit when it is completely dry. If the air conditioner goes ON with the plasma unit being wet, protection gets active and PLASMA/WASH lamp continuously flashes.
w1 Turn PLASMA DEODORIZING power OFF and ON again. (For turning off PLASMA DEODORIZING power, refer to 9-2.3.) (If it goes normal without turning OFF and ON, PLASMA/WASH lamp doesn't go OFF.
Yes
No
No
Yes
Yes
No
9.5V DC is generated.
Yes
No
Replace the indoor electronic control P.C. board. Check the wiring of CN1T1 on the indoor electronic control P.C. board.
High voltage (approx. -3.9kV) is generated during PLASMA DEODORIZING power operation. Pay careful attention and never touch PLASMA/WASH unit and the high-voltage lead part (red wire).
Yes
No
Stays OFF
PLASMA DEODORIZING operation
Continuously flashes.
Stays OFF
Continuously flashes.
While the operation is being stopped, does PLASMA/WASH lamp flash twice?
Turn ON the power supply.
Replace the indoor electronic control P.C. board is out of order.
Remove the plasma unit, firmly close the front panel, and then perform PLASMA DEODORIZING power operation check (w1). Does PLASMA/WASH lamp stay OFF, or continuously flash?
Does PLASMA/WASH lamp stay OFF, or continuously flash?
Turn OFF the power supply, and check the SAFETY DEVICE(PLASMA UNIT). Is it firmly fixed?
Turn ON and OFF the SAFETY DEVICE (PLASMA UNIT) using something like a screw driver, and measure the resistance value between CN1T2 1 and 3 on the indoor electronic control P.C. board. Does the switch work?
Keep the SAFETY DEVICE(PLASMA UNIT) ON using something like a screw driver. Turn ON the power supply. While the operation is being stopped, is the voltage between CN1 1(+) and 2(GND) on the PLASMA POWER P.C. board (PLASMA DEODORIZING) 0V?
Set the plasma power failure mode recall function.
Replace the PLASMA POWER P.C. board (PLASMA DEODORIZING).
Replace the indoor electronic control P.C. board.
When PLASMA button is pressed, is there voltage of 12.5V DC between CN1 1(+) and 2(GND)?
Replace the SAFETY DEVICE(PLASMA UNIT).
Firmly fix the SAFETY DEVICE.
1 During pressing both OPERATION SELECT button and TOO COOL button on the remote controller at the same time, press RESET button. 2 First, release RESET button. And release the other two buttons since all LCD in operation display section of the remote controller is displayed after 3 seconds.
(Failure mode recall function is set.)
3 Press OPERATE/STOP (ON/OFF) button. 4 After a short beep sound is emitted, press
once PLASMA button. PLASMA DEODORIZING operation is selected.
ww
The power failure mode for PLASMA DEODORIZING power is memorized when the failure mode is called.
F
Check of PLASMA DEODORIZING power
26
Page 27
When PLASMA/WASH lamp flashes 2-time.
PLASMA AIR PURIFYING operation
Make sure that the front panel is firmly closed.
1 During pressing both OPERATION SELECT button and TOO COOL button on the remote controller at the same time, press RESET button. 2 First, release RESET button. And release the other two buttons since all LCD in operation display section of the remote controller is displayed after 3 seconds.
(Failure mode recall function is set.)
3 Press OPERATE/STOP (ON/OFF) button. 4 After a short beep sound is emitted, press
twice PLASMA button. PLASMA AIR PURIFYING operation is selected. wThe plasma power operation check mode is set.(Refer to 9-2.5.)
1 During pressing both OPERATION SELECT button and TOO COOL button on the remote controller at the same time, press RESET button. 2 First, release RESET button. And release the other two buttons since all LCD in operation display section of the remote controller is displayed after 3 seconds.
(Failure mode recall function is set.)
3 Press OPERATE/STOP (ON/OFF) button. 4 After a short beep sound is emitted, press
twice PLASMA button. PLASMA AIR PURIFYING operation is selected.
After performing the check, make sure to release the failure mode recall function.
PLASMA AIR PURIFYING power supply is normal. The front panel is not firmly closed, therefore the protection by the interlock switch is active.
If the plasma unit is dirty, clean the unit. After cleaning, make sure to attach the unit when it is completely dry. If the air conditioner goes ON with the plasma unit being wet, protection gets active and PLASMA/WASH lamp continuously flashes.
w1 Turn PLASMA AIR PURIFYING power OFF and ON again. (For turning off PLASMA AIR PURIFYING power, refer to 9-2.3.) (If it goes normal without turning OFF and ON, PLASMA/WASH lamp doesn't go OFF.
Yes
No
No
Yes
Yes
No
9.5V DC is generated.
Yes
No
Replace the indoor electronic control P.C. board. Check the wiring of CN1T1 on the indoor electronic control P.C. board.
High voltage (approx. -3.9kV) is generated during PLASMA AIR PURIFYING power operation. Pay careful attention and never touch PLASMA/WASH unit and the high-voltage lead part (red wire).
Yes
No
Stays OFF
Continuously flashes.
Stays OFF
Continuously flashes.
While the operation is being stopped, does PLASMA/WASH lamp flash twice?
Turn ON the power supply.
Replace the indoor electronic control P.C. board is out of order.
Remove the plasma unit, firmly close the front panel, and then perform PLASMA AIR PURIFYING power operation check (w1). Does PLASMA/WASH lamp stay OFF, or continuously flash?
Does PLASMA/WASH lamp stay OFF, or continuously flash?
Turn OFF the power supply, and check the SAFETY DEVICE(PLASMA UNIT). Is it firmly fixed?
Turn ON and OFF the SAFETY DEVICE (PLASMA UNIT) using something like a screw driver, and measure the resistance value between CN1T2 1 and 3 on the indoor electronic control P.C. board. Does the switch work?
Keep the SAFETY DEVICE(PLASMA UNIT) ON using something like a screw driver. Turn ON the power supply. While the operation is being stopped, is the voltage between CN1 1(+) and 2(GND) on the PLASMA POWER P.C. board (PLASMA AIR PURIFYING) 0V?
Set the plasma power failure mode recall function.
Replace the PLASMA POWER P.C. board (PLASMA AIR PURIFYING).
Replace the indoor electronic control P.C. board.
When PLASMA button is pressed, is there voltage of 12.5V DC between CN1 1(+) and 2(GND)?
Replace the SAFETY DEVICE(PLASMA UNIT).
Firmly fix the SAFETY DEVICE.
ww
The power failure mode for PLASMA AIR PURIFYING power is memorized when the failure mode is called.
G
Check of PLASMA AIR PURIFYING power
27
Page 28
Is the connector of the front panel driving motor unit or the indoor electric control P.C. board unplugged?
Front panel is normal.
Replace the front panel driving motor unit.
Does the front panel automatically open? (Does it start to move?)
Yes
Is the front panel held 10mm or more upper than the level line of the nozzle top?
Yes
No
Turn the remote controller ON.
Plug in the connector and check from the start again.
Is the resistance value between terminals of the front panel driving motor unit normal?
Replace the indoor electric control P.C. board.
Replace the front panel driving motor unit.
No
No
Yes
Yes
No
Indoor unit and outdoor unit do not operate.
Check of auto front panel
H
10 mm or more
28
Z-Z side view
Page 29
Electromagnetic noise enters into TV sets or radios
Replace the antennas. Replace the coaxial cable.
No
No
No
Yes
Yes
No
No
Yes
Yes
Yes
Is the distance between the antennas and the indoor unit within 3m, or is the distance between the antennas and the outdoor unit within 3m?
Is the distance between the TV sets or radios and the indoor unit within 1m, or is the distance between the TV sets or radios and the outdoor unit within 3m?
Is there any antennas damage by rust or something , coaxial cable damage, or poor contact such as loosing of the connectors or wire disconnection of wiring of the antennas?
Is the indoor/outdoor connecting wire of the air conditioner and the wiring of the antennas in close?
Even if all of the above conditions is fulfilled, the electromagnetic noise may enter, depending on the electric field strength or the installation condition (combination of specific conditions such as antennas or wiring). Check the followings before asking for service.
1.Devices affected by the electromagnetic noise TV sets, radios (FM/AM broadcast, shortwave)
2.Channel, frequency, broadcast station affected by the electromagnetic noise
3.Channel, frequency, broadcast station unaffected by the electromagnetic noise
4.Layout of ; indoor/outdoor unit of the air conditioner, indoor/outdoor wiring, grounding wire, antennas, wiring from antennas, receiver
5.Electric field intensity of the broadcast station affected by the electromagnetic noise
6.Presence or absence of amplifier such as booster
7.Operation condition of air conditioner when the electromagnetic noise enters in.
1)Turn OFF the power supply once, and then turn ON the power supply. In this situation check for the electromagnetic noise.
2)Within 3 minutes after turning ON the power supply, press OPERATE/STOP (ON/OFF) button on the remote controller for power-on, and check for the electromagnetic noise.
3)After a short time (3 minutes later after turning ON), the outdoor unit starts running. During operation, check for the electromagnetic noise.
4)Press OPERATE/STOP (ON/OFF) button on the remote controller for power off, when the outdoor unit stops but the indoor/outdoor communication still runs on. In this situation check for the electromagnetic noise.
After checking the above, consult the service representative.
Is the unit earthed?
Earth the unit.
Extend the distance between the antennas and the indoor unit, or the antennas and the outdoor unit.
Extend the distance between the TV sets or radios and the indoor unit, or the TV sets or radios and the outdoor unit.
Extend the distance between the indoor/outdoor connecting wire of the air conditioner and the wiring of the antennas.
I
29
Page 30
Indoor coil thermistor [RT12 (MAIN), RT13 (SUB)] Room temperature thermistor (RT11)
Temperature (:)
Resistance (k")
9-7. Test point diagram and voltage
MSZ-FA25VA - MSZ-FA35VA -
Indoor electronic control P.C. board
E1E1
Power supply input
SW P.C. Board
WASH reset switch(SW2)
Emergency operation switch(SW1)
230V AC
{
5V DC
12V DC
Cement resistance
(R111)
Indoor fan motor (CN211)
1311V DC
3(-) Fiducial terminal of
cathode side on measur­ing high-voltage DC
415
V DC
5(+)3-6V DC 6(+)0V DC or 15V DC
Interlock switch(Fan) (CN1R1)
Room temperature thermistor (CN111)
Varistor (NR11)
CN2011 (Used for check of con­ducting of thermal fuse)
Indoor coil thermistor RT12(MAIN) RT13(SUB) (CN112)
Plasma deodorizing/air purifying filter units (CN1T1)
Safety device(Plasma unit) (CN1T2)
Horizontal and Vertical vane motor(CN151)
12
34
Power monitor receiver P.C. board.
Plasma power P.C. board
High-voltage lead wire (Red)
Release of Auto restart function Solder the Jumper wire to JR07.
(Refer to 8-3.)
CN1
i-see Sensor (CN110)
1DC 2.5V during PLASMA
AIR PURIFYING/PLASMA DEODORIZING operation
2GND 3DC 12.5V during PLASMA
AIR PURIFYING/PLASMA DEODORIZING operation
Standard lead wire (Green)
30
Fuse (F11)
Front panel driving motor (CN1U1)
Timer short mode point JPG, JPS
}
(Refer to 8-1.)
Page 31
10
(1) Slide the sleeve and check if there is a locking lever or not. (2) The terminal with this connector has the
locking mechanism.
1Slide the sleeve. 2Pull the terminal while
pushing the locking lever.
1Hold the sleeve, and pull out the terminal slowly.
The terminal which has the locking mechanism can be detached as shown below. There are two types ( Refer to (1) and (2)) of the terminal with locking mechanism. The terminal without locking mechanism can be detached by pulling it out. Check the shape of the terminal before detaching.
<"Terminal with locking mechanism" Detaching points>
Connector
Sleeve
Locking lever
DISASSEMBLY INSTRUCTIONS
MSZ-FA25VA - MSZ-FA35VA -
E1E1
INDOOR UNIT
OPERATING PROCEDURE
1. Removing the panel
(1) Press and unlock the knobs on both sides of the front
panel and lift the front panel until it is level, and then pull
the hinges forward to remove the front panel. (2) Remove the horizontal vane. (3) Remove the screw caps of the panel.
Remove the screws. (See Photo 1.) (4) Remove the screw of the front panel driving motor.
(See Photo 2.) (5) Hold the lower part of both ends on the panel and pull it
slightly toward you, and then remove the panel by pushing
it upward.
PHOTOS
Photo 1
Front panel
Screws of the panel
Horizontal vane
Photo 2
31
Screw of the front panel driving motor
Page 32
OPERATING PROCEDURE PHOTOS
2. Removing the electronic control P.C. board, the power monitor receiver P.C. board, i-see Sensor, SW P.C. board and the terminal block
(1) Remove the horizontal vane, the panel (Refer to 1.) and
the corner box.
(2) Remove the screw of the V.A. clamp, and then the
indoor/outdoor connecting wire.(See Photo 3.)
(3) Remove the switch holder from the electrical cover.
(See Photo 4.)
(4) Remove the screw of the electrical cover, and then the
electrical cover. (See Photo 4.)
(5) Remove the ground wire connected to the indoor electronic
control P.C. board from the electrical box. (See Photo 5.)
(6) Unhook the power monitor receiver P.C. board holder from
the catch. (See Photo 5.)
(7) Open the rear cover of the power monitor receiver P.C.
board holder and pull out the power monitor receiver P.C. board.
(8) Remove the screws of the i-see Sensor cover and the i-see
Sensor motor, and then the i-see Sensor motor. (9) Open the i-see Sensor holder and pull out the i-see Sensor. (10)
Open the switch holder and pull out SW P.C. board. (11)
Pull the electronic control P.C. board slightly toward you
from the electrical box, and disconnect TAB3 and all the
connectors on the electronic control P.C. board.
(LD101 and LD105 are direct-mounted to the electronic
control P.C. board.)
(12)
Pull out the electronic control P.C. board from the electrical
box.
(13)
Remove the ground wire connected to the heat exchanger
from the electrical box. (See Photo 5.)
(14)
Unhook the catches of the electrical box, and pull out the
electrical box.
(15)
Remove the screws of the terminal block cover, and then the terminal block cover and the terminal block holder. (See Photo 3.)
(16)
Remove the terminal block by sliding it.
3. Removing the electrical box
(1) Remove the horizontal vane, the panel (Refer to 1.) and the
corner box.
(2) Remove the screw of the V.A. clamp, and then the indoor/
outdoor connecting wire.(See Photo 3.)
(3) Remove the switch holder and the electrical cover.
(See Photo 4.)
(4) Remove the ground wire connected to the heat exchanger
from the electrical box.(See Photo 5.)
(5) Disconnect the following connectors on the electronic
control P.C. board; the fan motor connector <CN211>, the
indoor coil thermistor connector <CN112>, the vane motor
connector <CN151>, the connector of the interlock switch
(Fan) of the horizontal vane <CN1R1>, the connector of
the safety device (plasma unit) <CN1T2>, the connector of
the plasma power P.C. board <CN1T1>, the connector of
the front panel driving motor <CN1U1>.
(6) Unhook the catches of the electrical box, and pull out the
electrical box. (See Photo3.)
Photo 3
Screws of the terminal block cover
Drain hose
Photo 4
Photo 5
Power monitor receiver P.C. board holder
Ground wires
i-see Sensor
Screw of the V.A. clamp
Switch holder
Screw of the electrical cover.
Fan motor connector (CN211)
Connector of the interlock switch(Fan) (CN1R1)
Indoor coil thermistor connector (CN112)
Connector of the plasma power P.C.board(CN1T1)
Connector of the safety device(Plasma unit) (CN1T2)
Vane motor connector (CN151)
Connector of the front panel driving motor (CN1U1)
i-see Sensor cover
32
Page 33
OPERATING PROCEDURE PHOTOS
4. Removing the horizontal vane motor unit
(1) Remove the horizontal vane and the panel. (Refer to 1.) (2) Remove the screws of the horizontal vane motor unit,
and pull out the horizontal vane motor unit. (See Photo 6.)
(3) Disconnect the connector from the horizontal vane motor
unit.
5. Removing the vertical vane motor unit
(1) Remove the horizontal vane, the panel (Refer to 1.) and
the corner box.
(2) Pull out the drain hose from the nozzle assembly, and
remove the nozzle assembly. (See Photo 5.)
(3) Remove the crank of the vertical vane motor unit from the
arm of the vertical vane.(See Photo 7.)
(4) Remove the screws of the vertical vane motor unit, and pull
the vertical vane motor unit. (See Photo 7.)
Photo 6
Screw of the horizontal
vane motor unit
Photo 7
Arm
Crank of the vertical vane motor unit
Screws of the vertical vane motor unit
6. Removing the indoor fan motor and the line flow fan
(1) Remove the horizontal vane, the panel (Refer to 1.) and
the corner box.
(2)
Remove the switch holder and the electrical box. (Refer to 3.)
(3) Pull out the drain hose from the nozzle assembly, and
remove the nozzle assembly. (4) Remove the screws fixing the motor bed. (5) Loosen the screw fixing the line flow fan. (6) Remove the motor bed together with fan motor and motor
band. (7) Release the hooks of the motor band, and remove the
motor band then pull out the indoor fan motor. (8) Remove the screws fixing the left side of the heat
exchanger. (9) Lift the heat exchanger, and pull out the line flow fan to the
lower-left.
(See Photo 10.)
(See Photo 8.)
(See Photo 9.)
Photo 9
Screw of the line flow fan
Photo 8
Screws of the motor bed
Photo 10
Screws of the left side of the heat exchanger
Motor band
33
Page 34
OPERATING PROCEDURE PHOTOS
7. Removing the plasma power P.C. board
(1) Remove the horizontal vane, the panel (Refer to 1.) and
the corner box.
(2) Remove the switch holder and the electrical cover.
(Refer to 3.)
(3) Disconnect the connector of the front panel driving motor
<CN1U1> from the electronic control P.C. board. (4) Remove the front panel driving motor. (5) Remove the screw of the plasma element holder, and remove
the plasma element holder from the heat exchanger.
(See Photo 11.) (6) Unhook all the catches of plasma unit cover and remove
the plasma unit cover. (See Photo 12.) (7) Remove the terminals with locking mechanism connected
to the plasma power P.C. board and the safety device
(Plasma unit). (See Photo 13.) (8) Remove the plasma electrical box from the plasma element
holder. (9) Remove the screw fixing the plasma electrical box, and
open the plasma electrical box then pull out the plasma
power P.C. board from the plasma electrical box.
(See Photo 13.)
Photo 11
Photo 12
Screw of the plasma element holder
Plasma unit cover
Front panel driving motor
Photo 13
Terminal
Safety device (Plasma unit)
Terminal
Screw of the plasma electrical box
Plasma power P.C. board
Terminal
Terminal
34
Page 35
PARTS LIST11
MSZ-FA25VA - (WH) MSZ-FA35VA - (WH)
E1
E1
11-1. INDOOR UNIT STRUCTURAL PARTS
1
2
3
4
5 6
11-2. ACCESSORY AND REMOTE
CONTROLLER
8
9
7
10
11-1. INDOOR UNIT STRUCTURAL PARTS
Symbol
No.
E02 897 234
1
E02 913 000
2
E02 913 067
3
E02 913 010
4
E02 914 100
5
E02 913 100
6
E02 913 975
7
E02 913 970
8
Part No.
Part name
BOX PANEL ASSEMBLY (WH) SCREW CAP FRONT PANEL (WH) AIR FILTER (LEFT) AIR FILTER (RIGHT) CORNER BOX (RIGHT) INSTALLATION PLATE
in Wiring
Diagram
11-2. ACCESSORY AND REMOTE CONTROLLER
E02 913 426
9
E02 527 083
10
REMOTE CONTROLLER REMOTE CONTROLLER HOLDER
Q'ty/unit
MSZ-FA25VA -
(WH)
E1
1 1 2 1 1 1 1 1
1 1
MSZ-FA35VA -
(WH)
E1
1 1 2 1 1 1 1 1
1 1
Remarks
Including No.3,4 2PCS/SET
KM05A
35
Page 36
MSZ-FA25VA - (WH) MSZ-FA35VA - (WH)
E1
E1
11-3. INDOOR UNIT ELECTRICAL PARTS
AND FUNCTIONAL PARTS
SAFETY DEVICE
30
1
(PLASMA UNIT)
29
PLASMA POWER P.C.BOARD
27
26
25
24
20
2
SLEEVE BEARING
3
4
5
INTERLOCK SWITCH (FAN)
8
6
POWER MONITOR RECEIVER P.C. BOARD
31
18
POWER MONITOR RECEIVER P.C. BOARD HOLDER
11
12
i-see Sensor
32
7
28
13
i-see Sensor MOTOR
23
22
21
SW P.C. BOARD
18
17 16
15 14
11-4. INDOOR UNIT HEAT EXCHANGER
34
35
33
36
9
FUSE
10
VARISTOR NR11
18
ROOM TEMPERATURE THERMISTOR
19
Page 37
BEARING MOUNT SLEEVE BEARING DRAIN HOSE NOZZLE ASSEMBLY VANE MOTOR UNIT (HORIZONTAL) INTERLOCK SWITCH(FAN) VANE MOTOR UNIT (VERTICAL) HORIZONTAL VANE FUSE VARISTOR POWER MONITOR RECEIVER P.C. BOARD HOLDER i-see Sensor i-see Sensor MOTOR VA CLAMP TERMINAL BLOCK COVER TERMINAL BLOCK HOLDER TERMINAL BLOCK ELECTRONIC CONTROL P.C. BOARD W1 ELECTRONIC CONTROL P.C. BOARD W1 ROOM TEMPERATURE THERMISTOR INDOOR COIL THERMISTOR INDOOR COIL THERMISTOR SWITCH HOLDER INDOOR FAN MOTOR W2 MOTOR BAND FRONT PANEL DRIVING MOTOR LINE FLOW FAN PLASMA ELEMENT HOLDER PLASMA UNIT COVER PLASMA ELECTRICAL BOX PLASMA POWER P.C. BOARD SAFETY DEVICE (PLASMA UNIT) PLASMA AIR PURIFYING FILTER UNIT PLASMA DEODORIZING FILTER UNIT
UP & DOWN
RIGHT & LEFT
3.15A
AUTO RESTART AUTO RESTART
RC0J40-
MV1
MV2
F11
NR11
RR MT
TB
RT11 RT12, RT13 RT12, RT13
MF
MP
PLASMA_A PLASMA_D
(WH)
(WH)
No. Part No.
Part name
Remarks
Symbol
in Wiring
Diagram
Q'ty/unit
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16 17
18 19 20 21
22 23 24 25 26 27 28 29 30 31 32
MSZ-FA25VA-
E1
MSZ-FA35VA-
E1
33 34
35
INDOOR HEAT EXCHANGER INDOOR HEAT EXCHANGER UNION (GAS) UNION (LIQUID)
{9.52 {6.35
E02 751 509 E02 001 504 E02 897 702 E02 913 235 E02 897 303 E02 897 316 E02 913 303 E02 913 040 E02 127 382 E02 661 385 E02 913 095 E02 913 391 E02 914 303 E02 897 784 E02 897 780 E02 897 779 E02 913 375 E02 913 452 E02 914 452 E02 897 308 E02 913 307 E02 914 307 E02 913 782 E02 897 300 E02 897 333 E02 898 303 E02 897 302 E02 913 775 E02 913 776 E02 913 777 E02 897 440 E02 898 316 E02 913 774 E02 914 774
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
1 1
1 1 1 1 1 1 1 1 2 1 1 1
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
1 1
1 1 1 1 1 1 1 1 1 2 1 1 1
E02 913 620 E02 914 620 E02 815 666 E02 151 667
1
1 1
1 1 1
W1 Including SW P.C. BOARD and POWER MONITOR RECEIVER P.C. BOARD W2 Including FAN MOTOR RUBBER MOUNT (2 PCS/SET)
11-3. INDOOR UNIT ELECTRICAL PARTS AND FUNCTIONAL PARTS
11-4. INDOOR UNIT HEAT EXCHANGER
37
Page 38
12 OPTIONAL PARTS
(1)
(2)
Deodorizing ceramic filter
MAC-305FT-E
Model Part No.
MSZ-FA25VA - MSZ-FA35VA -
E1 E1
DEODORIZING CERAMIC FILTER
Replacement of the deodorizing ceramic filter(about once every 6 years)
Deodorizing ceramic filter is installed inside PLASMA DEODORIZING filter unit. The filter is fragile. Handle it with care. NOTE: PLASMA DEODORIZING filter unit may not operate properly if the deodorizing ceramic filter is not installed.
Be sure to install the deodorizing ceramic filter.
(1) Release the two knobs to open the filter unit. (2) Pull the side knobs to outward and then
forward to remove, as illustrated below.
(3) Pull out the deodorizing ceramic filter from the side of
the filter unit.
(4) Install the deodorizing ceramic filter by following the
removal procedure in reverse.
38
Page 39
39
Page 40
HEAD OFFICE: MITSUBISHI DENKI BLDG., 2-2-3, MARUNOUCHI, CHIYODA-KU, TOKYO100-8310, JAPAN
CC
Copyright 2005 MITSUBISHI ELECTRIC ENGINEERING CO.,LTD Distributed in Jan. 2005. No. OB371 6 Made in Japan
New publication, effective Jan. 2005 Specifications subject to change without notice.
Loading...