Mitsubishi Electronics MSZ-FA25VA User Manual

SERVICE MANUAL
SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
Wireless type Models
E1
E1
(WH)
(WH)
MSZ-FA25VA ­MSZ-FA35VA -
No. OB371
Indication of model name
MSZ-FA25VA ­MSZ-FA35VA -
NOTE:
This service manual describes technical data of the indoor units.
•As for outdoor units MUZ-FA25VA- , MUZ-FA35VA- , MUZ-FA25VAH- and MUZ-FA35VAH- , refer to service manual OB372.
•As for outdoor units MXZ-3A54VA- , MXZ-4A71VA- and MXZ-4A80VA- ,
refer to service manual OB377.
E1
E1
E1
CONTENTS
1. TECHNICAL CHANGES ····································2
2. PART NAMES AND FUNCTIONS······················3
3. SPECIFICATION·················································5
4. NOISE CRITERIA CURVES·······························6
5. OUTLINES AND DIMENSIONS·························7
6. WIRING DIAGRAM ············································8
7. REFRIGERANT SYSTEM DIAGRAM················8
8. SERVICE FUNCTIONS ······································9
9. TROUBLESHOOTING ······································11
10. DISASSEMBLY INSTRUCTIONS·····················31
12. OPTIONAL PARTS ···········································38
E1E1E1
E1E1E1
1
TECHNICAL CHANGES
MSZ-A09YV - ➔ MSZ-FA25VA -
MSZ-A12YV - MSZ-FA35VA -
1. Indication of capacity has been changed.(BTU base kW base)
2. Controller method between indoor and outdoor has been changed.
3. Power supply method has been changed (change to supply from outdoor unit).
4. Power supply cord has been removed.
5. Indoor electronic control P.C. board has been changed.
6. Position of terminal block has been changed.
7. Indoor fan motor has been changed. ( AC DC)
8. Indoor heat exchanger has been changed.
9. The horizontal vane motor unit has been changed. An external gear is added to the generalized stepping motor. The unit is structured so that the driving torque and stopping torque would increase.
Generalized stepping motor
NOTE: Do not remove the vane motor from the motor unit.
Do not disassemble the horizontal vane motor unit.
E1E1 E1E1
10. The vertical vane motor unit has been added. An external gear is added to the generalized stepping motor. The unit is structured so that the driving torque and stopping torque would increase.
Generalized stepping motor
NOTE: Do not remove the vane motor from the motor unit.
Do not disassemble the vertical vane motor unit.
11. Front panel driving motor unit which opens and closes the front panel has been added.
Front panel opening/closing
output gear
NOTE: Do not disassemble the front panel driving motor unit.
12. PLASMA DEODORIZING/AIR PURIFYING filter units have been added.
13. i-see Sensor has been added.
(i-see control operation and AREAsetting have been added.)
14. Air cleaning filer has been removed.
15. Signal of remote controller has been changed. (It is not available for the conventional models.)
16. Symbol on terminal block has been changed (to S1/S2/S3).
2
2
Line flow fan
Air outlet
Vertical vane
Air inlet
Display section
Front panel
PLASMA DEODORIZING filter
Panel
Heat exchanger
Horizontal vane
Operation section
(When the front panel is opened)
Remote controller
POWER lamp
Remote control receiving section
PLASMA AIR PURIFYING filter
Anti-mold air filter
Fan guard
i-see Sensor
PLASMA/WASH lamp
AREA lamp
Emergency operation switch
WASH reset switch
Auto front panel
When the unit starts operating, the front panel opens automatically to draw in air. When the unit stops operating, the front panel closes automatically.
AREA lamp indicate AREA setting
In AREA setting, the horizontal air flow direction changes automatically according to the detection of i-see Sensor which detects the floor/ wall temperature to air-condition the room evenly.
i-see control operation
i-see sensor constantly measure floor/wall temperature to automatically adjust to the set temperature by estimating the temperature actually perceived by a person inside the room ("sensible temperature").
<Open> <Closed>
Auto front panel
PART NAMES AND FUNCTIONS
INDOOR UNIT
MSZ-FA25VA ­MSZ-FA35VA -
E1
E1
3
1 2 3 4 5 6 7
Installation plate Installation plate fixing screw 4 o 25 mm Remote controller holder Fixing screw for 3 3.5 o 1.6 mm (Black) Battery (AAA) for remote controller Wireless remote controller Felt tape (Used for left or left-rear piping)
MSZ-FA25VA -
E1
MSZ-FA35VA -
E1
1 5 1 2 2 1 1
ON-TIMER button
CLOCK SET button
TIME SET buttons FORWARD button BACKWARD button
VANE CONTROL button (Horizontal vane button)
OFF-TIMER button
i-see button
(This diagram shows an overall view.)
Open the front lid.
PLASMA button
AREA button
RESET button
WIDE VANE button (Vertical vane button)
Signal transmitting section
Operation display section
Temperature buttons
OPERATE/STOP (ON/OFF) button
FAN SPEED CONTROL button
OPERATION SELECT button
ECONO COOL button
Indication of remote controller model is on back
MSZ-FA25VA ­MSZ-FA35VA -
E1
E1
ACCESSORIES
REMOTE CONTROLLER
4
3
T3.15AL250V
NSEJ001DA1 12V DC 100" (at 25˚C)
MP20Z 12V DC 300" (at 25˚C) MSBPC20M16 12V DC 250" (at 25˚C) MSBPC20M11 12V DC 300" (at 25˚C)
ERZV14D471
A2TPMI334F0V50HSOBA060P5L1J4S 5V DC
3P
INDOOR UNIT
Item
Model
Fuse Front panel driving motor i-see Sensor motor Horizontal vane motor Vertical vane motor Varistor i-see Sensor Terminal block
MSZ-FA25VA -
E1
MSZ-FA35VA -
E1
(F11)
(MP)
(MT) (MV1) (MV2)
(NR11)
(RR)
(TB)
MSZ-FA25VA -
E1
MSZ-FA35VA -
E1
Indoor model
Function
Power supply
Single phase
230V,50Hz
10
0.25 33 — 57
0.25
RC0J40-EB
780O298O198
10
4
42
36W/29W/21
W
4 10 10 10
KM05A
Cooling
594
474W/354W/252
W
1,220
1,010W/800W/610
W
Heating
612
498W/384W/264
W
1,250
1,050W/850W/640
W
Single phase
230V,50Hz
10
0.25 33 — 57
0.25
RC0J40-EB
780O298O198
10
4
42
36W/29W/22
W
4 10 10 10
KM05A
Cooling
594
474W/354W/258
W
1,220
1,010W/800W/630
W
Heating
612
498W/384W/276
W
1,250
1,050W/850W/660
W
Air flow(Super High) Air flow(HighW/Med.W/LowW) Power outlet Running current 1 Power input 1 Auxiliary heater Power factor 1 Fan motor current 1 Model Dimensions WOHOD Weight Air direction Sound level(Super High) Sound level(HighW/Med.W/LowW) Fan speed(Super High) Fan speed(HighW/Med.W/LowW) Fan speed regulator Thermistor RT11(at25:) Thermistor RT12(at25:) Thermistor RT13(at25:) Remote controller model
K /h K /h
A A
W
A(kW)
%
A
mm
kg
dB(A) dB(A)
rpm rpm
k" k" k"
Electrical
data
Fan motor
Special
remarks
Capacity
MSZ-FA25VA -
E1
MSZ-FA35VA -
E1
Indoor model
Function
Cooling
546
450W/348W/252
W
1,130
960W/790W/610
W
Heating
540
420W/372W/264
W
1,120
910W/830W/640
W
Cooling
516W/390W/258
W
1,080W/860W/630
W
Heating
522W/402W/276
W
1,090W/880W/660
W
Air flow(Super High) Air flow(HighW/Med.W/LowW) Sound level(Super High) Sound level(HighW/Med.W/LowW) Fan speed(Super High) Fan speed(HighW/Med.W/LowW)
K /h K /h
dB(A) dB(A)
rpm rpm
Special
remarks
Capacity
42
36W/29W/21
W
642
42
36W/29W/22
W
1,300
SPECIFICATION
When outdoor unit is MXZ type.
NOTE : Test conditions are based on ISO 5151
Specifications and rating conditions of main electric parts
Cooling : Indoor Dry-bulb temperature 27:Wet-bulb temperature 19: Heating : Indoor Dry-bulb temperature 20:Wet-bulb temperature 15: Refrigerant piping length (one way): 5m
w Reference value
Outdoor Dry-bulb temperature 35:Wet-bulb temperature 24: Outdoor Dry-bulb temperature 7: Wet-bulb temperature 6:
1 Measured under rated operating frequency.
5
4
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE
COOLING
FUNCTION
42 42
SPL(dB(A))
LINE
Super High
FAN SPEED
HEATING
Test conditions, Cooling : Dry-bulb temperature 27: Wet-bulb temperature 19:
Heating : Dry-bulb temperature 20: Wet-bulb temperature 15:
INDOORUNIT
WALL
MICROPHONE
0.8m
1m
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
Test conditions, Cooling : Dry-bulb temperature 27: Wet-bulb temperature 19:
APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE
COOLING
FUNCTION
42 42
SPL(dB(A))
LINE
Super High
FAN SPEED
HEATING
Heating : Dry-bulb temperature 20: Wet-bulb temperature 15:
NOISE CRITERIA CURVES
MSZ-FA25VA -
E1
MSZ-FA35VA -
E1
6
5
OUTLINES AND DIMENSIONS
MSZ-FA25VA ­MSZ-FA35VA -
INDOOR UNIT
298
53.5 102624.5
E1
E1
58
780
19
11o26 Oblong hole
Installation plate
Indoor unit
41.5 215
100
Air out
11o20 Oblong hole
155 155
335 320
Air in
198 5
or more7
106
90
Wall hole
Installation plate
Liquid line [6.35 - 0.5m Gas line [9.52 - 0.43m Insulation [35 O.D
{
[19 I.D
Drain hose [16 (Connected part O.D)
Insulation [28
5555 225 225
214
7055
Unit : mm
14273.5
234
3 287.5
42.5
[65
159
Wireless remote controller
Required space (Indoor unit)
75 or more
10 or more
75 or more
55 or morew
wIn case of left, left back, or
left under piping (using spacer),
113 or more
7
6
SYMBOL
DB111
F11
MF
MP MT
MV1
SYMBOL
MV2
NR11 PLASMA_A PLASMA_D
RR
RT11
SYMBOL
RT12 RT13
T111
TB
NAME DIODE STACK FUSE (T3.15AL250V) INDOOR FAN MOTOR FRONT PANEL DRIVING MOTOR i-see Sensor MOTOR VANE MOTOR (HORIZONTAL)
NAME VANE MOTOR (VERTICAL) VARISTOR PLASMA AIR PURIFYING FILTER UNIT PLASMA DEODORIZING FILTER UNIT i-see Sensor ROOM TEMPERATURE THERMISTOR
NAME INDOOR COIL THERMISTOR (MAIN) INDOOR COIL THERMISTOR (SUB) TRANSFORMER TERMINAL BLOCK
WIRING DIAGRAM
MSZ-FA25VA ­MSZ-FA35VA -
INDOOR UNIT
E1
E1
TO OUTDOOR UNIT CONNECTING
GRN
MV1
230V~
12-24V
LD104
CN
151
5
MV2
MODELS WIRING DIAGRAM
TB
S1 S2 S3
CN
1R1
2
5
INTERLOCK SWITCH(FAN)
POWER MONITOR RECEIVER P.C. BOARD
BLK BLU
RED
LD
101(A)
105(T)
8
SW P.C. BOARD
TAB3
2 1
CN201
LD
3
F11
MT
NR11
CN
110
5
DB111
4
RR
INDOOR ELECTRONIC CONTROL P.C. BOARD
T111
CN
1T1
CN
1T2
33
PLASMA_DPLASMA_A
SAFETY DEVICE (PLASMA UNIT)
2
CN
1U1
MP
CN
112
5
4 3 2 1
CN
111
1 2 3 4 5 6
CN211
RED BLK
WHT YLW BLU
RT13 RT12
RT11
5
MF
NOTE:1. About the outdoor side electric wiring refer to the outdoor unit electric wiring diagram for servicing.
2. Use copper conductors only. (For field wiring)
3. Symbols below indicate.
/: Terminal block, : Connector
7
MSZ-FA25VA -
INDOOR UNIT
REFRIGERANT SYSTEM DIAGRAM
E1
Refrigerant pipe [9.52
MSZ-FA35VA -
INDOOR UNIT
(with heat insulator)
Indoor coil
Indoor heat exchanger
thermistor RT12(main)
Flared connection
Indoor heat exchanger
Indoor coil thermistor RT13(sub)
Room temperature thermistor RT11
Room temperature thermistor RT11
E1
Indoor coil thermistor RT12(main)
Indoor coil thermistor RT13(sub)
Unit : mm
Refrigerant pipe [9.52 (with heat insulator)
Flared connection
Refrigerant flow in cooling Refrigerant flow in heating
Flared connection
Refrigerant pipe [6.35 (with heat insulator)
8
Flared connection
Refrigerant pipe [6.35 (with heat insulator)
8
SERVICE FUNCTIONS
MSZ-FA25VA ­MSZ-FA35VA -
E1
E1
8-1. TIMER SHORT MODE
For service, set time can be shortened by short circuit of JPG and JPS the electronic control P.C. board. The time will be shortened as follows. (Refer to 9-7.) Set time : 1-minute 1-second Set time : 3-minute 3-second (It takes 3 minutes for the compressor to start operation. However, the starting time is
shortened by short circuit of JPG and JPS.)
8-2. P.C. BOARD MODIFICATION FOR INDIVIDUAL OPERATION
A maximum of 4 indoor units with wireless remote controllers can be used in a room. In this case, to operate each indoor unit individually by each remote controller, P.C. boards of remote controller must be modified according to the number of the indoor unit.
How to modify the remote controller P.C. board
Remove batteries before modification. The board has a print as shown below :
Remote controller model : KM05A
NOTE : For remodelling, take out
the batteries and press the OPERATE/STOP(ON/OFF) button twice or 3 times at first. After finish remodelling, put back the batteries then press the RESET button.
J1
The P.C. board has the print “J1” and “J2”. Solder “J1” and “J2” according to the number of indoor unit as shown in Table 1. After modification, press the RESET button.
J2
Table 1
1 unit operation No. 1 unit No. 2 unit No. 3 unit No. 4 unit
How to set the remote controller exclusively for particular indoor unit.
After you turn the breaker ON, the first remote controller that sends the signal to the indoor unit will be regarded as the remote controller for the indoor unit. The indoor unit will only accepts the signal from the remote controller that has been assigned to the indoor unit once they are set. The setting will be cancelled if the breaker has turned off, or the power supply has shut down. Please conduct the above setting once again after the power has restored.
No modification
– – –
2 units operation
Same as at left
Solder J1
– –
3 units operation
Same as at left Same as at left
Solder J2
4 units operation
Same as at left Same as at left Same as at left
Solder both J1 and J2
8-3. AUTO RESTART FUNCTION
When the indoor unit is controlled with the remote controller, the operation mode, the set temperature, and the fan speed are memorized by the indoor electronic control P.C. board. The “AUTO RESTART FUNCTION” sets to work the moment power has restored after power failure. Then, the unit will restart automatically.
Operation
1 If the main power has been cut, the operation settings remain. 2 After the power is restored, the unit restarts automatically according to the memory.
(However, it takes at least 3 minutes for the compressor to start running.)
9
How to release “AUTO RESTART FUNCTION”
JR07
CN151 CN211CN112 CN1R1
CN212
CN1T1CN1T2
CN130
IC156
8-4. Remote controller
Be sure to set the slide switch inside the remote controller to an appropriate position in accordance with the installed position of the indoor unit. If the switch is not set correctly, the air conditioner may not function properly.
Area Left Center Right
Position of
the slide
switch
Display on
the remote
controller
Where is the indoor unit installed in your room?
Installed at left , if the distance is not more than 50 cm.
NOTE:If the indoor unit is installed more than 50 cm away from the side walls, cabinets or other nearby objects, set the slide
switch to the “center” position.
Installed at right, if the distance is not more than 50 cm.
Is the indoor unit in­stalled at right, left or center?
(Left) (Center) (Right)
Side swich
1Turn off the main power for the unit. 2Solder the Jumper wire to JR07 on the indoor electronic control P.C. board. (Refer to 9-7.)
NOTE:
The operation settings are memorized when 10 seconds have passed after the indoor unit was operated with the remote
controller.
If main power is turned OFF or a power failure occurs while AUTO START/STOP timer is active, the timer setting is
cancelled.
If the unit has been off with the remote controller before power failure, the auto restart function does not works as the
power button of the remote controller is off.
To prevent breaker off due to the rush of starting current, systematize other home appliance not to turn on at the same
time.
When some air conditioners are connected to the same supply system, if they are operated before power failure, the
starting current of all the compressors may flow simultaneously at restart. Therefore, the special counter-measures are required to prevent the main voltage-drop or the rush of the starting current by adding to the system that allows the units to start one by one.
10
21
Stopper
Lock.
Left
Insert this end first.
9
RESET button
Housing point
TROUBLESHOOTING
MSZ-FA25VA ­MSZ-FA35VA -
E1
E1
9-1. Cautions on troubleshooting
1. Before troubleshooting, check the following:
1) Check the power supply voltage.
2) Check the indoor/outdoor connecting wire for mis-wiring.
2. Take care the following during servicing.
1) Before servicing the air conditioner, be sure to turn off the unit first with the remote controller, and then after confirming the horizontal vane is closed, turn off the breaker and / or disconnect the power plug.
2) Be sure to turn OFF the power supply before removing the front panel, the cabinet, the top panel, and the electronic control P.C. board.
3) When removing the electronic control P.C. board, hold the edge of the board with care NOT to apply stress on the components.
4) When connecting or disconnecting the connectors, hold the housing of the connector. DO NOT pull the lead wires.
3. Troubleshooting procedure
1) First, check if the OPERATION INDICATOR lamp on the indoor unit is flashing on and off to indicate an abnormality. To make sure, check how many times the abnormality indication is flashing on and off before starting service work.
2) Before servicing check that the connector and terminal are connected properly.
3) If the electronic control P.C. board is supposed to be defective, check the copper foil pattern for disconnection and the
components for bursting and discoloration.
4) When troubleshooting, refer to 9-2., 9-3. and 9-4.
4. How to replace batteries
Weak batteries may cause the remote controller malfunction. In this case, replace the batteries to operate the remote controller normally.
1 Remove the front lid and insert batteries.
Then reattach the front lid.
Lead wiring
2 Press RESET button with tip end of ball point pen
or the like, and then use the remote controller.
Insert the negative pole of the batteries first. Check if the polarity of the batteries are correct.
NOTE : 1. If RESET button is not pressed, the remote controller may not operate correctly.
2. This remote controller has a circuit to automatically reset the microcomputer when batteries are replaced. This function is equipped to prevent the microcomputer from malfunctioning due to the voltage drop caused by
the battery replacement.
5. How to install the horizontal vane
If horizontal vane is not installed correctly, All of the operation indicator lamps will blink. In this case, install the horizontal vane correctly by following the procedures 1 to 2.
NOTE: Before installation of the horizontal vane, turn OFF the power supply.
22
In procedure
stoppers until they click into place.
lock the
11
WASH
reset
E.O. SW
Plasma element holder
6. How to remove and install PLASMA DEODORIZING / AIR PURIFYING filter units
If PLASMA/WASH lamp on the indoor unit blinks, clean the filters as soon as possible. The lamp will start blinking when accumulated operating time exceeds 330 hours.
<Remove>
Figure 1.
(1) Switch the indoor unit OFF with the remote controller and
disconnect the power supply plug and/ or turn OFF the breaker. NOTE: Otherwise, you may get injured since PLASMA
DEODORIZING/AIR PURIFYING filter units are charged with high voltage.
(2) Hold the knobs on both sides of the front panel and lift the
panel up until its level. (3) Remove the anti-mold air filter.(See Figure 1.) (4) Remove PLASMA DEODORIZING/AIR PURIFYING filter
units. (See Figure 2.)
Figure 2.
<Install>
Install PLASMA DEODORIZING/AIR PURIFYING filter units by following the removal procedure in reverse.
(1) Insert the top of PLASMA DEODORIZING/AIR PURIFYING filter
units into the aperture in the plasma element holder.
Figure 3.
(See Figure 3.) (2) Push in PLASMA DEODORIZING/AIR PURIFYING filter units
until they click into place.
•The front panel does not close if PLASMA DEODORIZING/AIR PURIFYING filter units are not installed properly.
(3) Install the anti-mold air filter. (4) Connect the power supply plug and/ or turn ON the breaker. (5) Press WASH reset switch. A short “beep” is heard and the blinks
of PLASMA/WASH lamp will be cancelled. Make sure PLASMA/ WASH lamp is not blinking at the start of operation next time. (See Figure 4.)
(6) Hold both sides of the front panel and close the front panel.
Figure 4.
(7) Press the 3 positions on the front panel as indicated by the
arrows.(See Figure 5.)
NOTE: Install PLASMA DEODORIZING/AIR PURIFYING filter units only when they are completely dry. If the filter unit remains wet, PLASMA/WASH lamp may blink and the plasma function may be disabled.(When PLASMA DEODORIZING/AIR PURIFYING filter units are cleaned.)
12
Figure 5.
Loading...
+ 28 hidden pages