This installation manual describes only
for the indoor unit. Refer to the MXZ
type manual for outdoor unit set up.
Phillips screwdriver
Level
Scale
Utility knife or scissors
65 mm hole saw
Torque wrench
Wrench (or spanner)
1. BEFORE INSTALLATION
1-1. THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR SAFETY
• Be sure to read “THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR SAFETY” before installing the air conditioner.
• Be sure to observe the warnings and cautions specified here as they include important items related to safety.
• After reading this manual, be sure to keep it together with the OPERATING INSTRUCTIONS for future reference.
(Could lead to death, serious injury, etc.)
N
N
If refrigerant gas leaks indoors, and comes into contact
N
The pressure of R410A is 1.6 times more than R22.
N
N
If the compressor is started before the refrigerant pipes
N
If fastened too tight, a flare nut may break after a long
N
(Could lead to serious injury in particular environments when operated incorrectly.)
N
If small animals enter and touch the electric parts inside
Note:
It is advisable to make a piping loop near outdoor unit so as
to reduce vibration transmitted from there.
Pipe size
Indoor/outdoor
connecting wire
4-core
1.0 mm
*7
(thickness *3, *4)
Gas / Liquid
ø9.52 / 6.35 mm
2
ø12.7 / 6.35 mm
(0.8 mm)
(0.8 mm)
*8 Insulation material : Heat resisting foam plastic 0.045
*9 Be sure to use the insulation of specified thickness. Exces-
Do not install the unit by yourself (user).
N
Incomplete installation could cause fire or electric
shock, injury due to the unit falling, or leakage of water.
Consult the dealer from whom you purchased the unit
or a qualified installer.
Perform the installation securely referring to the
N
installation manual.
Incomplete installation could cause fire, electric shock,
or injury due to the unit falling, or leakage of water.
When installing the unit, use appropriate protective
N
equipment and tools for safety.
Failure to do so could cause injury.
Install the unit securely in a place which can bear
N
the weight of the unit.
If the installation location cannot bear the weight of the
unit, the unit could fall causing injury.
Electrical work should be performed by a qualified,
N
experienced electrician, according to the installation
manual. Be sure to use an exclusive circuit. Do not
connect other electrical appliances to the circuit.
If the capacity of the power circuit is insufficient or there
is incomplete electrical work, it could result in a fire or
an electric shock.
Earth the unit correctly.
N
Do not connect the earth to a gas pipe, water pipe, light-
ning rod or telephone earth. Defective earthing could
cause electric shock.
Do not damage the wires by applying excessive
N
pressure with parts or screws.
Damaged wires could cause fire or electric shock.
Be sure to cut off the main power in case of setting
N
up the indoor P.C. board or wiring works.
Failure to do so could cause electric shock.
Use the specified wires to connect the indoor and
N
outdoor units securely and attach the wires firmly to
the terminal block connecting sections so the stress
Install an earth leakage breaker depending on the
N
installation place.
If an earth leakage breaker is not installed, it could
cause electric shock.
Perform the drainage/piping work securely accord-
N
ing to the installation manual.
of the wires is not applied to the sections. Do not extend the wires, or use intermediate connection.
Incomplete connecting and securing could cause fire.
Do not install the unit in a place where inflammable gas may leak.
N
If gas leaks and accumulates in the area around the
unit, it could cause an explosion.
Do not use intermediate connection of the power
N
cord or the extension cord and do not connect
many devices to one AC outlet.
It could cause a fire or an electric shock due to defective contact, defective insulation, exceeding the permissible current, etc.
Be sure to use the parts provided or specified parts
N
for the installation work.
The use of defective parts could cause an injury or leakage
of water due to a fire, an electric shock, the unit falling, etc.
When plugging the power supply plug into the outlet,
N
make sure that there is no dust, clogging, or loose
parts in both the outlet and the plug. Make sure that the
power supply plug is pushed completely into the outlet.
If there is dust, clogging, or loose parts on the power sup-
ply plug or the outlet, it could cause electric shock or fire. If
loose parts are found on the power supply plug, replace it.
Attach the electrical cover to the indoor unit and the
N
service panel to the outdoor unit securely.
If the electrical cover of the indoor unit and/or the service
panel of the outdoor unit are not attached securely, it could
result in a fire or an electric shock due to dust, water, etc.
When installing, relocating, or servicing the unit,
N
make sure that no substance other than the specified refrigerant (R410A) enters the refrigerant circuit.
Any presence of foreign substance such as air can
cause abnormal pressure rise and may result in explosion or injury. The use of any refrigerant other than that
specified for the system will cause mechanical failure,
system malfunction, or unit breakdown. In the worst
If there is defect in the drainage/piping work, water
could drop from the unit, soaking and damaging household goods.
Do not touch the air inlet or the aluminum fins of
N
the outdoor unit.
This could cause injury.
1-2. SELECTING THE INSTALLATION LOCATION
INDOOR UNIT
• Where airflow is not blocked.
•
Where cool air spreads over the entire room.
• Rigid wall without vibration.
• Where it is not exposed to direct sunshine.
• Where easily drained.
• At a distance 1 m or more away from your TV and radio.
Operation of the air conditioner may interfere with radio
or TV reception. An amplifier may be required for the affected device.
• In a place as far away as possible from fluorescent and
incandescent lights (so the infrared remote control can
operate the air conditioner normally).
• Where the air filter can be removed and replaced easily.
REMOTE CONTROLLER
• Where it is easy to operate and easily visible.
•
Where children cannot touch it.
• Select a position about 1.2 m above the floor and check
that signals from the remote controller are surely received by the indoor unit from that position (‘beep’ or
‘beep beep’ receiving tone sounds). After that, attach remote controller holder to a pillar or wall and install wireless remote controller.
Note:
In rooms where inverter type fluorescent lamps are used,
the signal from the wireless remote controller may not be
received.
OUTDOOR UNIT
• Where it is not exposed to strong wind.
•
Where airflow is good and dustless.
• Where rain or direct sunlight can be avoided as much as
possible.
• Where neighbours are not annoyed by operation sound
or hot air.
• Where rigid wall or support is available to prevent the
increase of operation sound or vibration.
• Where there is no risk of combustible gas leakage.
• When installing the unit at a high level, be sure to secure
the unit legs.
• Where it is at least 3 m away from the antenna of TV set
or radio. Operation of the air conditioner may interfere with
radio or TV reception in areas where reception is weak.
An amplifier may be required for the affected device.
• Install the unit horizontally.
• Please install it in an area not affected by snowfall or
blowing snow. In areas with heavy snow, please install a
canopy, a pedestal and/or some baffle boards.
*1 Connect to the power switch which has a gap of 3 mm or
more when open to interrupt the source power phase. (When
the power switch is shut off, it must interrupt all phases.)
*2 Use wires in conformity with design 60245 IEC 57.
*3 Never use pipes with thickness less than specified. The
pressure resistance will be insufficient.
*4 Use a copper pipe or a copper-alloy seamless pipe.
–
Rated
Voltage
*7
Frequency
230 V50 Hz–
Breaker
capacity
*5 Be careful not to crush or bend the pipe during pipe bending.
*6 Refrigerant pipe bending radius must be 100 mm or more.
*7 Refer to the installation manual of the multi-type outdoor
units.
*7
WARNING
CAUTION
Power supply
–
Required Tools for Installation
case, this could lead to a serious impediment to securing product safety.
Do not discharge the refrigerant into the atmosphere. If
refrigerant leaks during installation, ventilate the room.
If refrigerant comes in contact with a fire, harmful gas
could be generated.
Check that the refrigerant gas does not leak after
installation has been completed.
with the flame of a fan heater, space heater, stove, etc.,
harmful substances will be generated.
Use appropriate tools and piping materials for installation.
Not using appropriate tools or materials and incomplete
installation could cause the pipes to burst or injury.
When pumping down the refrigerant, stop the compressor before disconnecting the refrigerant pipes.
If the refrigerant pipes are disconnected while the compressor is running and the stop valve is open, air could be drawn
in and the pressure in the refrigeration cycle could become
abnormally high. This could cause the pipes to burst or injury.
When installing the unit, securely connect the refrigerant pipes before starting the compressor.
are connected and when the stop valve is open, air
could be drawn in and the pressure in the refrigeration
cycle could become abnormally high. This could cause
the pipes to burst or injury.
Fasten a flare nut with a torque wrench as specified
in this manual.
period and cause refrigerant leakage.
The unit shall be installed in accordance with national wiring regulations.
Do not install the outdoor unit where small animals
may live.
the unit, it could cause a malfunction, smoke emission,
or fire. Also, advise user to keep the area around the
unit clean.
Note:
When operating the air conditioner in low outside temperature, be sure to follow the instructions described below.
• Never install the outdoor unit in a place where its air
inlet/outlet side may be exposed directly to wind.
• To prevent exposure to wind, install the outdoor unit
with its air inlet side facing the wall.
•
To prevent exposure to wind, it is recommended to install a baffle board on the air outlet side of the outdoor
unit.
Avoid the following places for installation where air conditioner trouble is liable to occur.
• Where flammable gas could leak.
• Where there is much machine oil.
• Salty places such as the seaside.
• Where sulfide gas is generated such as a hot spring.
• Where there is high-frequency or wireless equipment.
• Where there is emission of high levels of VOCs, including phthalate compounds, formaldehyde, etc., which
may cause chemical cracking.
specific gravity
sive thickness may cause incorrect installation of the indoor
unit and insufficient thickness may cause dew drippage.
4 mm hexagonal wrench
Flare tool for R410A
Gauge manifold for R410A
Vacuum pump for R410A
Charge hose for R410A
Pipe cutter with reamer
1-4. INSTALLATION DIAGRAM
Indoor unit
Wall hole
sleeve (C)
Cut off the
extra length.
Pipe fixing band
(E)
Be sure to use wall hole
sleeve (C) to prevent indoor/outdoor connecting
wire (A) from contacting
metal parts in the wall and
to prevent damage by
rodents in case the wall is
hollow.
Wall hole cover (D)
Seal the wall hole
gap with putty (H).
Fix the pipe to wall
with pipe fixing
band (E).
Fixing screw
(F)
ACCESSORIES
Check the following parts before installation.
<Indoor unit>
(1) Installation plate1
Installation plate fixing screw
(2)
4 × 25 mm
(3) Remote controller holder1
Fixing screw for (3) 3.5 × 16 mm
(4)
(Black)
(5) Battery (AAA) for (6)2
(6) Wireless remote controller1
Felt tape
(7)
(For left or left-rear piping)
(8) Soft drycloth (VAB type only)1
PARTS TO BE PROVIDED
AT YOUR SITE
(A) Indoor/outdoor unit connecting wire*1
(B) Extension pipe1
(C) Wall hole sleeve1
(D) Wall hole cover1
(E) Pipe fixing band2 to 5
(F) Fixing screw for (E) 4 × 20 mm2 to 5
(G) Piping tape1
(H) Putty1
Drain hose
(I)
(or soft PVC hose, 15 mm inner
diameter or hard PVC pipe VP16)
(J) Refrigeration oil1
(K) Power supply cord*1
* Note:
Place indoor/outdoor unit connecting wire (A)
and power supply cord (K) at least 1 m away
from the TV antenna wire.
Units should be installed by licensed contractor according to local code requirements.
5
2
1
1 or 2
mm or
128
mm or
72
more/
left back piping
more for left and
107.5 mm
or more
(using spacer)
more
7 mm or
117.5
mm
or more
After the leak test, apply
insulating material tightly
so that there is no gap.
When the piping is to be attached to a wall containing
metals (tin plated) or metal
netting, use a chemically
treated wooden piece 20
mm or thicker between the
wall and the piping or wrap
7 to 8 turns of insulation vinyl tape around the piping.
To use existing piping, perform COOL operation for
30 minutes and pump down
before removing the old air
conditioner. Remake flare
according to the dimension
for new refrigerant.
IMPORTANT NOTES
To comply with the requirements of Australian standard AS/NZS 3000 electrical installations (wiring rules), the electrical wiring required between the
indoor and outdoor units must be installed by a licenced electrical contractor.
2. INDOOR UNIT INSTALLATION
CAUTION
Protective film covers the front panel of some indoor units. When installing
those indoor units, leave the film on it to prevent scratching until installation
completes.
2-1. FIXING OF INSTALLATION PLATE
• Find a structural material (such as a stud) in the wall and fix installation plate (1) horizontally with fixing screws (2).
• To prevent installation plate (1) from vibrating, be sure to install the fixing screws in
the holes indicated in the illustration. For added support, fixing screws may also be
installed in other holes.
• When the knockout is removed, apply vinyl tape to the knockout edges to prevent
damaging the wires.
• When bolts recessed in the concrete wall are to be utilized, secure installation plate (1)
using 11 × 20 · 11 × 26 oval hole (450 mm pitch).
• If the recessed bolt is too long, change it for a shorter one available in the market.
2-2. WALL HOLE DRILLING
1) Determine the wall hole position.
2) Drill a ø65 mm hole. The outdoor side should be
5 to 7 mm lower than the indoor side.
3) Insert wall hole sleeve (C).
Ceiling
Installation plate (1)
107.5
mm
or more
WallWall
Fixing screw (2)
2-3. CONNECTING WIRES FOR INDOOR UNIT
Level
You can connect indoor/outdoor lead wire without removing the front panel.
1) Open the front panel.
2) Remove VA clamp.
ø65 mm
72
mm or more
128
mm or more for left and left
back piping (using spacer)
Insert
the
scale. *
Align the
scale with
the line. *
Wall
117.5
or more
100 mm
* Same for left hole.
5-7 mm
Outdoor
side
mm
Center of
ø65 mm hole
3) Pass indoor/outdoor unit connecting wire (A) from the back of the indoor unit and process the end of the wire.
4) Loosen terminal screw, and connect first the earth wire, then indoor/outdoor unit connecting wire (A) to the terminal block. Be careful not to make mis-wiring. Fix the wire
to the terminal block securely so that no part of its core is appeared, and no external
force is conveyed to the connecting section of the terminal block.
5) Firmly tighten the terminal screws to prevent them from loosening. After tightening, pull
the wires lightly to confirm that they do not move.
6) Secure indoor/outdoor unit connecting wire (A) and the earth wire with the VA clamp.
Never fail to hook the left claw of the VA clamp. Attach the VA clamp securely.
Terminal block
VA clamp
Fixing screw
15 mm
35 mm
Lead wire
• For future servicing, give extra length to the
connecting wires.
• Make earth wire a little longer than others.
(More than 60 mm)
• Do not fold the excess wire, or cram it into
small space. Take caution not to damage
the wires.
• Be sure to attach each screw to its correspondent terminal when securing the cord
and/or the wire to the terminal block.
Note: Do not place the wires between the
indoor unit and the installation plate (1).
Damaged wire could cause heat generation
or fire.
Earth wire
(green/yellow)
Indoor/outdoor unit
connecting wire (A)
2-4. PIPE FORMING AND DRAIN PIPING
Pipe Forming
• Place the drain hose below the refrigerant piping.
• Make sure that the drain hose is not heaved or snaked.
• Do not pull the hose when applying the tape.
• When the drain hose passes the room, be sure to wrap
insulation material (obtainable at a store) around it.
Indoor/outdoor unit
connecting wire (A)
Indoor terminal block
Outdoor terminal block
Liquid pipe
Gas pipe
Indoor/outdoor unit
connecting wire (A)
Felt tape (7)
Piping tape (G)
Rear, right, or downward piping
Drain cap
Drain cap
Drain hose
Cut off in case of left
piping.
Drain cap
Piping tape (G)
Drain hose
Fig. 1
Fig. 2
Fig. 3
Fig. 4
Fig. 5
Felt tape (7)
1) Put the refrigerant piping and the drain hose
together, then firmly apply piping tape (G)
from the end.
2) Insert the piping and the drain hose into the
wall hole sleeve (C), and hook the upper part
Cut off in case of
right piping.
Cut off in case of
downward piping.
of the indoor unit on the installation plate (1).
3) Check if the indoor unit is hooked securely on the installation plate (1) by moving
the unit to left and right.
4) Thrust the lower part of the indoor unit into the installation plate (1).
Drain Piping
• If the extension drain hose has to pass through a room, be sure to wrap it with commercially sold insulation.
• The drain hose should point downward for easy drain flow. (Fig. 1)
• If the drain hose provided with the indoor unit is too short, connect it with drain hose (I)
that should be provided at your site. (Fig. 2)
• When connecting the drain hose to the hard vinyl chloride pipe, be sure to insert it
securely into the pipe. (Fig. 3)
Drain hose
Hard vinyl chloride
pipe I.D. 30 mm
Insert
securely
Downward
slope
Drain
hose
Soft hose
I.D. 15 mm
70 cm or
more
Different
diameter joint
Fig. 1Fig. 2Fig. 3
Do not make drain piping as shown below.
Accumulated
drain water
Air
Waving
Water
leakage
Tip of drain
hose dipped
in water
Ditch
At least
50 mm
gap
Water
leakage
Do not raise
Water
leakage
Left or left-rear piping
Note:
Be sure to reattach the drain
hose and the drain cap in case
of left or left-rear piping.
Otherwise, it could cause drops
of water to drip down from the
drain hose.
1) Put the refrigerant piping and the drain hose together,
then firmly apply felt tape (7) from the end.
Felt tape (7) overlap width should be 1/3 the tape width.
Use a bandage stopper at the end of felt tape (7).
2) Pull out the drain cap at the rear right of the indoor unit.
(Fig. 1)
• Hold the convex section at the end and pull the drain
cap.
3) Pull out the drain hose at the rear left of the indoor unit.
(Fig. 2)
• Hold the claw marked by the arrows and pull out the
drain hose forward.
4) Put the drain cap into the section to which the drain
hose is to be attached at the rear of the indoor unit.
(Fig. 3)
• Insert not sharp-edged tools such as screwdrivers
into the hole at the end of the cap and insert the cap
fully into the drain pan.
5) Insert the drain hose fully into the drain pan at the rear
right of the indoor unit. (Fig. 4)
• Check if the hose is hooked securely to the projection
of its inserting part at the drain pan.
6) Insert the drain hose into wall hole sleeve (C), and hook
the upper part of indoor unit on installation plate (1).
Then, move the indoor unit completely to the left in order to make placing the piping in the back space of the
unit easier.
7) Cut out a piece of cardboard from the shipping box, roll
it up, hook it onto the back rib, and use it as a spacer to
lift the indoor unit. (Fig. 5)
8) Connect the refrigerant piping with the extension pipe (B).
9) Thrust the lower part of the indoor unit into the installation plate (1).
2-5. FLARING WORK
1) Cut the copper pipe correctly with pipe cutter.
(Fig. 1, 2)
2) Completely remove all burrs from the cut cross section of pipe. (Fig. 3)
• Put the end of the copper pipe to downward direc-
tion as you remove burrs in order to avoid to let
burrs drop in the piping.
3) Remove flare nuts attached to indoor and outdoor
units, then put them on pipe having completed burr
removal. (Not possible to put them on after flaring
work.)
4) Flaring work (Fig. 4, 5). Firmly hold copper pipe in the
dimension shown in the table. Select A mm from the
table according to the tool you use.
5) Check
• Compare the flared work with Fig. 6.
• If flare is noted to be defective, cut off the flared
section and do flaring work again.
Burr
Die
Flare nut
Copper pipe
Spare reamer
Pipe cutter
Copper pipe
Fig. 5
Even length
all around
Smooth all
around
Good
Flaring tool
Clutch type
Inside is shining without any
scratches.
Copper
pipe
Fig. 1
No good
Tilted Uneven Burred
Fig. 2
Wing nut type
Fig. 4Fig. 3
Fig. 6
2-6. PIPE CONNECTION
• Fasten flare nut with a torque wrench as specified in the table.
• When fastened too tight, flare nut may break after a long period and cause refrigerant
leakage.
• Be sure to wrap insulation around the piping. Direct contact with the bare piping may result in burns or frostbite.
Indoor unit connection
Connect both liquid and gas pipings to indoor unit.
• Apply a thin coat of refrigeration oil (J) on the seat surface of pipe.
• For connection, first align the center, then tighten the first 3 to 4 turns of flare nut.
• Use tightening torque table above as a guideline for indoor unit side union joint section,
and tighten using two wrenches. Excessive tightening damages the flare section.
Outdoor unit connection
Connect pipes to stop valve pipe joint of the outdoor unit in the
same manner applied for indoor unit.
• For tightening, use a torque wrench or spanner and use the
same tightening torque applied for indoor unit.
WARNING
When installing the unit, securely connect the refrigerant
pipes before starting the compressor.
2-7. INSULATION AND TAPING
1) Cover piping joints with pipe cover.
2) For outdoor unit side, surely insulate every piping including valves.
3) Using piping tape (G), apply taping starting from the entry of outdoor unit.
• Stop the end of piping tape (G) with tape (with adhesive agent attached).
• When piping have to be arranged through above ceiling, closet or where the tempera-
ture and humidity are high, wind additional commercially sold insulation to prevent condensation.
Pipe diameter
(mm)
ø 6.35 (1/4”)
ø 9.52 (3/8”)2234.3 to 41.2 350 to 420
ø12.7 (1/2”)26
ø15.88 (5/8”)2973.5 to 78.4 750 to 800
Nut
(mm)
17
Clutch type
for R410A
Clutch type
tool
tool
for R22
0 to 0.51.0 to 1.5
Wing nut
type tool
for R22
1.5 to 2.0
2.0 to 2.5
N•mkgf•cm
13.7 to 17.7 140 to 180
49.0 to 56.4 500 to 575
A (mm)Tightening torque
)p
3. PURGING PROCEDURES, LEAK TEST, AND TEST RUN
3-1. PURGING PROCEDURES AND LEAK TEST
Refer to the procedures indicated in the installation manual of the outdoor unit.
3-2. TEST RUN
1) Insert power supply plug into the power outlet and/or turn on
the breaker.
2) Press the E.O. SW once for COOL, and twice for HEAT
operation. Test run will be performed for 30 minutes. If the
left lamp of the operation indicator blinks every 0.5 seconds,
inspect the indoor/outdoor unit connecting wire (A) for miswiring. After the test run, emergency mode (set temperature
24°C) will start.
3) To stop operation, press the E.O. SW several times until all
LED lamps turn off. Refer to operating instructions for details.
Checking the remote (infrared) signal reception
Press the ON/OFF button on the remote controller (6) and check that an electronic sound
is heard from the indoor unit. Press the ON/OFF button again to turn the air conditioner off.
• Once the compressor stops, the restart preventive device operates so the compressor
will not operate for 3 minutes to protect the air conditioner.
Emergency
operation switch
(E.O. SW)
4. RELOCATION AND MAINTENANCE
4-1. REMOVING AND INSTALLING THE PANEL ASSEMBLY
Removal procedure
) Unlock the upper and lower vanes as
1
shown in
Then, remove the horizontal vanes.
2) Remove the 2 screws which fix the panel
assembly.
3) Remove the panel assembly. Be sure to
remove its bottom right end first.
Installation procedure
1) Install the panel assembly following the removal
procedure in reverse.
2) Be sure to press the positions as indicated by the
arrows in order to attach the assembly completely to
the unit.
3) Install the horizontal vanes.
and using a thin instrument.
3333
Unlock
Upper and
lower vanes
3-3. AUTO RESTART FUNCTION
This product is equipped with an auto restart function. When the power supply is stopped
during operation, such as during blackouts, the function automatically starts operation in
the previous setting once the power supply is resumed. (Refer to the operating instructions for details.)
Caution:
• After test run or remote signal reception check, turn off the unit with the E.O. SW or
the remote controller before turning off the power supply. Not doing so will cause the
unit to start operation automatically when power supply is resumed.
To the user
• After installing the unit, make sure to explain the user about auto restart function.
• If auto restart function is unnecessary, it can be deactivated. Consult the service
representative to deactivate the function. Refer to the service manual for details.
3-4. EXPLANATION TO THE USER
• Using the OPERATING INSTRUCTIONS, explain to the user how to use the air conditioner (how to use the remote controller, how to remove the air filters, how to remove
or put the remote controller in the remote controller holder, how to clean, precautions
for operation, etc.).
• Recommend the user to read the OPERATING INSTRUCTIONS carefully.
4-3. PUMPING DOWN
When relocating or disposing of the air conditioner, pump down the system following the
procedure below so that no refrigerant is released into the atmosphere.
1) Connect the gauge manifold valve to the service port of the stop valve on the gas pipe
side of the outdoor unit.
2) Fully close the stop valve on the liquid pipe side of the outdoor unit.
3) Close the stop valve on the gas pipe side of the outdoor unit almost completely so that
it can be easily closed fully when the pressure gauge shows 0 MPa [Gauge] (0 kgf/
2
).
cm
4) Start the emergency COOL operation.
To start the emergency operation in COOL mode, disconnect the power supply plug
and/or turn off the breaker. After 15 seconds, connect the power supply plug and/or
turn on the breaker, and then press the E.O. SW once. (The emergency COOL
operation can be performed continuously for up to 30 minutes.)
5) Fully close the stop valve on the gas pipe side of the outdoor unit when the pressure
gauge shows 0.05 to 0 MPa [Gauge] (approx. 0.5 to 0 kgf/cm
6) Stop the emergency COOL operation.
Press the E.O. SW several times until all LED lamps turn off. Refer to operating in-
structions for details.
WARNING
When pumping down the refrigerant, stop the compressor before disconnecting
the refrigerant pipes. The compressor may burst if air etc. get into it.
2
).
4-2. REMOVING THE INDOOR UNIT
Remove the bottom of the indoor unit from the installation
plate.
When releasing the corner part, release both left and right
bottom corner part of indoor unit and pull it downward and
forward as shown in the figure on the right.
HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO
100-8310, JAPAN
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.