Mitsubishi Electric Mr. Slim PCA-RP-GA Installation Manual

Page 1
Air-Conditioners
PCA-RP·GA
INSTALLATION MANUAL
For safe and correct use, please read this installation manual thoroughly before installing the air-conditioner unit.
INSTALLATIONSHANDBUCH
Zum sicheren und ordnungsgemäßen Gebrauch der Klimaanlage das Installationshandbuch gründlich durchlesen.
MANUEL D’INSTALLATION
Veuillez lire le manuel d’installation en entier avant d’installer ce climatiseur pour éviter tout accident et vous assurer d’une utilisation correcte.
INSTALLATIEHANDLEIDING
Voor een veilig en juist gebruik moet u deze installatiehandleiding grondig doorlezen voordat u de airconditioner installeert.
MANUAL DE INSTALACIÓN
Para un uso seguro y correcto, lea detalladamente este manual de instalación antes de montar la unidad de aire acondicionado.
MANUALE DI INSTALLAZIONE
Per un uso sicuro e corretto, leggere attentamente questo manuale di installazione prima di installare il condizionatore d’aria.
E°XEIPI¢IO O¢H°IøN E°KATA™TA™H™
°И· ·ЫК¿ПВИ· О·И ЫˆЫЩ‹ ¯Ъ‹ЫЛ, ·Ъ·О·ПВ›ЫЩВ ‰И·‚¿ЫВЩВ ЪФЫВ¯ЩИО¿ ·˘Щfi ЩФ ВБ¯ВИЪ›‰ИФ ВБО·Щ¿ЫЩ·ЫЛ˜ ЪИУ ·Ъ¯›ЫВЩВ ЩЛУ ВБО·Щ¿ЫЩ·ЫЛ ЩЛ˜ МФУ¿‰·˜ ОПИМ·ЩИЫМФ‡.
MANUAL DE INSTALAÇÃO
Para segurança e utilização correctas, leia atentamente este manual de instalação antes de instalar a unidade de ar condicionado.
FOR INSTALLER
FÜR INSTALLATEURE
POUR L’INSTALLATEUR
VOOR DE INSTALLATEUR
PARA EL INSTALADOR
PER L’INSTALLATORE
°π∞ ∞À∆√¡ ¶√À ∫∞¡∂π ∆∏¡ ∂°∫∞∆∞™∆∞™∏
PARA O INSTALADOR
English
Deutsch
Français
Nederlands
Español
Italiano
Português
INSTALLATIONSMANUAL
Læs venligst denne installationsmanual grundigt, før De installerer airconditionanlægget, af hensyn til sikker og korrekt anvendelse.
INSTALLATIONSMANUAL
Läs denna installationsmanual noga för säkert och korrekt bruk innan luftkonditioneringen installeras.
MONTAJ ELK‹TABI
Emniyetli ve do¤ru biçimde nas›l kullan›laca¤›n› ö¤renmek için lütfen klima cihaz›n› monte etmeden önce bu elkitab›n› dikkatle okuyunuz.
РУКОВОДСТВО ПО УСТАНОВКЕ
Для осторожного и правильного использования прибора необходимо тщательно ознакомиться с данным руководством по установке до выполнения установки кондиционера.
TIL INSTALLATØREN
Dansk
FÖR INSTALLATÖREN
Svenska
MONTÖR ‹Ç‹N
Türkçe
ДЛЯ УСТАНОВИТЕЛЯ
Русский
Page 2
Contents
ELV
1. Safety precautions ................................................................................... 2
2. Installation location .................................................................................. 3
3. Installing the indoor unit ........................................................................... 3
4. Installing the refrigerant piping ................................................................. 5
1. Safety precautions
s Before installing the unit, make sure you read all the “Safety precau-
tions”.
s Please report to your supply authority or obtain their consent before
connecting this equipment to the power supply system.
Warning: Describes precautions that must be observed to prevent danger of injury or death to the user.
Caution: Describes precautions that must be observed to prevent damage to the unit.
After installation work has been completed, explain the “Safety Precautions,” use, and maintenance of the unit to the customer according to the information in the Op­eration Manual and perform the test run to ensure normal operation. Both the Instal­lation Manual and Operation Manual must be given to the user for keeping. These manuals must be passed on to subsequent users.
Warning:
• Ask a dealer or an authorized technician to install the unit.
• For installation work, follow the instructions in the Installation Manual and use
tools and pipe components specifically made for use with refrigerant specified in the outdoor unit installation manual.
• The unit must be installed according to the instructions in order to minimize
the risk of damage from earthquakes, typhoons, or strong winds. An incor­rectly installed unit may fall down and cause damage or injuries.
• The unit must be securely installed on a structure that can sustain its weight.
• If the air conditioner is installed in a small room, measures must be taken to
prevent the refrigerant concentration in the room from exceeding the safety limit in the event of refrigerant leakage. Should the refrigerant leak and cause the concentration limit to be exceeded, hazards due to lack of oxygen in the room may result.
5. Drainage piping work ............................................................................... 5
6. Electrical work .......................................................................................... 6
7. Test run .................................................................................................... 8
: Indicates an action that must be avoided.
: Indicates that important instructions must be followed.
: Indicates a part which must be grounded.
: Indicates that caution should be taken with rotating parts.
: Indicates that the main switch must be turned off before servicing.
: Beware of electric shock.
: Beware of hot surface.
: At servicing, please shut down the power supply for both the Indoor and
Outdoor Unit.
Warning:
Carefully read the labels affixed to the main unit.
• Ventilate the room if refrigerant leaks during operation. If refrigerant comes into contact with a flame, poisonous gases will be released.
• All electric work must be performed by a qualified technician according to local regulations and the instructions given in this manual.
• Use only specified cables for wiring.
• The terminal block cover panel of the unit must be firmly attached.
• Use only accessories authorized by Mitsubishi Electric and ask a dealer or an authorized technician to install them.
• The user should never attempt to repair the unit or transfer it to another loca­tion.
• After installation has been completed, check for refrigerant leaks. If refriger­ant leaks into the room and comes into contact with the flame of a heater or portable cooking range, poisonous gases will be released.
1.1. Before installation (Environment)
Caution:
• Do not use the unit in an unusual environment. If the air conditioner is in­stalled in areas exposed to steam, volatile oil (including machine oil), or sulfuric gas, areas exposed to high salt content such as the seaside, the performance can be significantly reduced and the internal parts can be damaged.
• Do not install the unit where combustible gases may leak, be produced, flow, or accumulate. If combustible gas accumulates around the unit, fire or explo­sion may result.
• Do not keep food, plants, caged pets, artwork, or precision instruments in the direct airflow of the indoor unit or too close to the unit, as these items can be damaged by temperature changes or dripping water.
1.2. Before installation or relocation
Caution:
• Be extremely careful when transporting the units. Two or more persons are needed to handle the unit, as it weighs 20 kg or more. Do not grasp the packaging bands. Wear protective gloves as you can injure your hands on the fins or other parts.
• Be sure to safely dispose of the packaging materials. Packaging materials, such as nails and other metal or wooden parts may cause stabs or other injuries.
1.3. Before electric work
Caution:
• Be sure to install circuit breakers. If not installed, electric shock may result.
• For the power lines, use standard cables of sufficient capacity. Otherwise, a short circuit, overheating, or fire may result.
• When installing the power lines, do not apply tension to the cables.
1.4. Before starting the test run
Caution:
Turn on the main power switch more than 12 hours before starting operation. Starting operation just after turning on the power switch can severely dam­age the internal parts.
Before starting operation, check that all panels, guards and other protective parts are correctly installed. Rotating, hot, or high voltage parts can cause injuries.
• When the room humidity exceeds 80% or when the drainpipe is clogged, wa­ter may drip from the indoor unit. Do not install the indoor unit where such dripping can cause damage.
• When installing the unit in a hospital or communications office, be prepared for noise and electronic interference. Inverters, home appliances, high-fre­quency medical equipment, and radio communications equipment can cause the air conditioner to malfunction or breakdown. The air conditioner may also affect medical equipment, disturbing medical care, and communications equip­ment, harming the screen display quality.
• Thermal insulation of the refrigerant pipe is necessary to prevent condensa­tion. If the refrigerant pipe is not properly insulated, condensation will be formed.
• Place thermal insulation on the pipes to prevent condensation. If the drain­pipe is installed incorrectly, water leakage and damage to the ceiling, floor, furniture, or other possessions may result.
• Do not clean the air conditioner unit with water. Electric shock may result.
• Tighten all flare nuts to specification using a torque wrench. If tightened too much, the flare nut can break after an extended period.
• Be sure to ground the unit. If the unit is not properly grounded, electric shock may result.
• Use circuit breakers (ground fault interrupter, isolating switch (+B fuse), and molded case circuit breaker) with the specified capacity. If the circuit breaker capacity is larger than the specified capacity, breakdown or fire may result.
Do not operate the air conditioner without the air filter set in place. If the air
filter is not installed, dust may accumulate and breakdown may result.
Do not touch any switch with wet hands. Electric shock may result.
Do not touch the refrigerant pipes with bare hands during operation.
After stopping operation, be sure to wait at least five minutes before turning off
the main power switch. Otherwise, water leakage or breakdown may result.
2
Page 3
2. Installation location
E
D
H
C
W
A
B
UNIT
A
C
B
680
320 80
13775
8685
11
D
E
46
F
43
A
F
H D
G
E
226
F
B
C
180
200
241
H G
E
GH
A
B
A
C
B
125
151(211)170(230)
70
80 Ø65 Ø100
2.1. Outline dimensions (Indoor unit) (Fig. 2-1)
Select a proper position allowing the following clearances for installation and mainte­nance.
Models W D H ABCE
RP2 1000 680 221 Min. 270 Min. 300 Min. 500 Max. 250
RP2.5, 3 1310 680 221 Min. 270 Min. 300 Min. 500 Max. 250
RP4 1310 680 281 Min. 270 Min. 300 Min. 500 Max. 250
RP5, 6 1620 680 281 Min. 270 Min. 300 Min. 500 Max. 250
Warning: Mount the indoor unit on a ceiling strong enough to withstand the weight of the unit.
(mm)
Fig. 2-1
3. Installing the indoor unit
1
4
7
2
5
Fig. 3-1
2.2. Outline dimensions (Outdoor unit)
Refer to the outdoor unit installation manual.
3
3.1. Check the indoor unit accessories (Fig. 3-1)
The indoor unit should be supplied with the following accessories (contained in the inside of the intake grille).
Accessory name Q’ty
6
1 Washer 4 pcs 2 Pipe cover 1 pc Large size (For gas tubing) 3 Pipe cover 1 pc Small size (For liquid tubing) 4 Band 4 pcs 5 Joint socket 1 pc Marked with UNIT 6 Socket cover 1 pc 7 Drain tubing cover 1 pc
3.2. Preparation for installation (Fig. 3-2)
3.2.1. Suspension bolt installing spacing
Models A B C RP2 933 1000 221 RP2.5, 3 1240 1310 221 RP4 1240 1310 281 RP5, 6 1547 1620 281
3.2.2. Refrigerant and drain tubing location
Models D E F G H J K L RP2, 2.5, 3 131 175 178 90 82 159 156 90 RP4, 5, 6 191 235 238 150 142 219 216 150
A Front side outlet E Right drain tubing
B Left side outlet F Left drain tubing
C Right side outlet G Gas tubing
D Independent piece (Removable) H Liquid tubing
(mm)
(mm)
Fig. 3-2
Fig. 3-3
(mm)
3.2.3. Selection of suspension bolts and tubing positions (Fig. 3-3)
Using the pattern paper provided for installation, select proper positions for suspen­sion bolts and tubing and prepare relative holes.
A Pattern paper
B Suspension bolt hole
C Indoor unit width
Secure the suspension bolts or use angle stock braces or square timbers for bolt installation.
A Use inserts of 100 kg to 150 kg each.
B Use suspension bolts of W3/8 or M10 in size
3
Page 4
3. Installing the indoor unit
B
A
C
1
a
b
10–20
C
D
A
7–12
B
E
F
G
H
C
Fig. 3-4
Fig. 3-5
Fig. 3-6
(mm)
3.2.4. Indoor unit preparation (Fig. 3-4)
1. Install the suspending bolts. (Procure the W3/8 or M10 bolts locally.) Predetermine the length from the ceiling (1 within 100 mm).
A Ceiling surface B Suspending bolt C Suspending bracket
2. Remove the intake grille. Slide the intake grille holding knobs (at two locations) backward to open the intake grille.
3. Remove the side panel. Remove the side panel holding screws (one in each side, right and left) then slide the side panel forward for removal.
3.3. Installing the indoor unit
Use a proper suspending method depending on the presence or absence of ceiling materials as follows. (Fig. 3-5) In the absence of ceiling materials
a Suspending bracket b Unit
1) Directly suspending the unit (Fig. 3-6)
Installing procedures
1. Install the washer 1 (supplied with the unit) and the nut (to be locally procured).
2. Set (hook) the unit through the suspending bolts.
3. Tighten the nuts. Check the unit installing condition.
Check that the unit is horizontal between the right and left sides.
Check that the unit slopes continuously downward from the front to the rear.
When embedding pipes, into the wall
2) Installing the suspending bracket first onto the ceiling (Fig. 3-7)
Installing procedures
1. Remove the suspending brackets, U-shaped washers, and suspending bracket holding screws from the unit.
2. Adjust the suspending bracket holding bolts on the unit.
3. Attach the suspending brackets to the suspending bolts.
4. Set (hook) the unit to the suspending brackets.
Be sure to install the U-shaped washers.
A Bolt B Unit C Washer D Suspending bracket holding screw E Bolt F Washer 1 G Double nuts
H RP2 900 - 905
RP2.5, 3, 4 1207 - 1212 RP5, 6
(mm)
1514 - 1519
Fig. 3-7
4
Page 5
90° ±0.5°
øA
R0.4~R0.8
A
45°±2°
B
C
D
4. Installing the refrigerant piping
G
C
DE
A
B
D
E
F
C
B
A
Fig. 4-1
A Flare cutting dimensions
Copper pipe O.D. Flare dimensions
(mm) øA dimensions (mm)
ø6.35 8.7 - 9.1 ø9.52 12.8 - 13.2
ø12.7 16.2 - 16.6 ø15.88 19.3 - 19.7 ø19.05 23.6 - 24.0
4.1. Connecting pipes (Fig. 4-1)
When commercially available copper pipes are used, wrap liquid and gas pipes with commercially available insulation materials (heat-resistant to 100 °C or more, thickness of 12 mm or more).
The indoor parts of the drain pipe should be wrapped with polyethylene foam insu­lation materials (specific gravity of 0.03, thickness of 9 mm or more).
Apply thin layer of refrigerant oil to pipe and joint seating surface before tightening flare nut.
Use two wrenches to tighten piping connections.
Use refrigerant piping insulation provided to insulate indoor unit connections. Insu-
late carefully.
B Flare nut tightening torque
Copper pipe O.D. Flare nut O.D. Tightening torque
(mm) (mm) (N·m)
ø6.35 17 14 - 18 ø6.35 22 34 - 42 ø9.52 22 34 - 42 ø12.7 26 49 - 61
ø12.7 29 68 - 82 ø15.88 29 68 - 82 ø15.88 36 100 - 120 ø19.05 36 100 - 120
C Apply refrigerating machine oil over the entire flare seat surface. D Use the flare nuts as follows.
*1: The flare nut is attached to its pipe. *2: The flare nut is in the outdoor unit accessory.
Refer to the outdoor unit installation manual for the specification of connecting pipes.
Indoor unit RP1.6, 2 RP2.5, 3 RP4-6
Refrigerant R407C
Joint outdoor unit PU(H)-P1.6/2 PU(H)-P2.5/3 PU(H)-P4/5/6
Gas side Pipe size (mm) ø15.88 ø15.88 ø19.05
Liquid side Pipe size (mm) ø9.52 ø9.52 ø9.52
Joint outdoor unit
Gas side Pipe size (mm) ø12.7 ø15.88 ø15.88
Liquid side Pipe size (mm) ø6.35 ø9.52 ø9.52
Do not use the flare nut attached. If it is used, a gas leakage or even a pipe extraction may occur.
Indoor nut *1 *1 *1
Outdoor nut *1 *1 *1
Indoor nut *1 *1 *1
Outdoor nut *1 *1 *1
Indoor unit RP1.6, 2 RP2.5, 3 RP4-6
Refrigerant R410A
PUHZ-RP1.6/2 PUHZ-RP2.5/3 PUHZ-RP4/5/6
Indoor nut *2 *1 *2
Outdoor nut *1 *1 *1
Indoor nut *2 *1 *1
Outdoor nut *1 *1 *1
Fig. 4-2
5. Drainage piping work
Fig. 5-1
A Drain pan B Plug
4.2. Indoor unit (Fig. 4-2)
Installing procedures
1. Slide the supplied pipe cover 2 over the gas tubing until it is pressed against the sheet metal inside the unit.
2. Slide the provided pipe cover 3 over the liquid tubing until it is pressed against the sheet metal inside the unit.
3. Tighten the pipe covers 2 and 3 at the both ends (15 - 20 mm) with the supplied bands 4.
A Gas tubing E Pipe cover 3 B Liquid tubing F Press the pipe cover against the sheet metal. C Band 4 G Refrigerant tubing heat insulating material D Pipe cover 2
4.3. For twin/triple combination
Refer to the outdoor unit installation manual.
5.1. Preparation for left side tubing installation (Fig. 5-1)
For left side tubing, be sure to insert the rubber plug into the right drain port.
Install the drain tubing as it slopes continuously downward.
After completion of work, check that correct drain is available from the outflow port
of the drain tubing.
5
Page 6
L
1
N
2
S1 S2 S3
5. Drainage piping work
3.B
1.D
2.C
4.E
B
C
D
A
E
F
1
2 3
L
1
N
2
G
K
F
J
I
H
E
D
C
B
A
A Drain pan B Drain tubing C Socket cover 6 D Joint socket 5 E Drain tubing cover 7
Fig. 5-2
Fig. 5-3
6. Electrical work
F Drain tubing sensor
Installing procedures (Fig. 5-2)
1. Attach the joint socket 5 supplied with the unit to the drain port on the unit with a vinyl chloride adhesive.
2. Fasten the socket cover 6 supplied with the unit to the joint socket 5.
3. Attach the field drain tubing (VP20) to the joint socket 5 with a vinyl chloride adhesive.
4. Wrap the drain tubing cover 7 supplied with the unit. (Seam taping)
5. Check for correct drainage. (Fig. 5-3)
Fill the drain pan with water of about 1 L from the tubing sensor access port.After checking for correct drainage, replace the tubing sensor access port cover.
6-1. Electric wiring (Fig. 6-1)
Wiring procedures
1. Remove the (two) tapping screws then remove the electric part cover.
2. Connect the electric wires securely to the corresponding terminals.
3. Replace the removed parts.
4. Tie the electric wires with the local wiring clamp located in the right side of the junction box.
A Cover B Set screws C Beam D Wiring clamp E Power supply board F Control board G Wire service entrance H Terminal block for indoor and outdoor units connection I Terminal block for electric heater power supply (for only PCH models) J Terminal block for remote controller K Grounding cable connector
Fig. 6-1
Indoor unit model Indoor unit power supply (Heater) Indoor unit input capacity (Heater) Main switch (Breaker)
Indoor unit power supply (Heater) Indoor unit power supply (Heater) earth
)
2
Indoor unit-Outdoor unit
(mm
Wiring
Indoor unit-Outdoor unit Remote controller-Indoor unit *2
Wire No. × size
Indoor unit (Heater) L-N *3 Indoor unit-Outdoor unit S1-S2 *3 Indoor unit-Outdoor unit S2-S3 *3
rating
Circuit
Remote controller-Indoor unit *3
*1. A breaker with at least 3 mm contact separation in each pole shall be provided. Use non-fuse breaker (NF) or earth leakage breaker (NV). *2. A 10 m wire is attached in the remote controller accessory. *3. The figures are NOT always against the ground.
Notes: 1. Wiring size must comply with the applicable local and national code.
S3 terminal has DC 24 V against S2 terminal. However between S3 and S1, these terminals are not electrically insulataed by the transformer or other device.
6
2. Power supply cords and Indoor unit/Outdoor unit connecting cords shall not be lighter than polychloroprene sheathed flexible cord. (Design 245 IEC 57)
3. Install an earth longer and thicker than other cables.
earth
PCA PCH
~/N (single), 50Hz, 220-230-240V
*1
2 × Min. 1.5 1 × Min. 1.5
3 × 2.5 (Polar) 3 × 2.5 (Polar)
1 × Min. 2.5 1 × Min. 2.5
2 × 0.69 (Non-polar) 2 × 0.69 (Non-polar)
AC 220-230-240V
AC 220-230-240V AC 220-230-240V
DC24V DC24V DC14V DC14V
16A
Page 7
6. Electrical work
30
46
30
30120
83.5
A
B
C
F
A
H
C
D
E
G
I
I
I
H
B
J
H
A
AB TB6
B
1
234
ON
1
234
ON
C
ON/OFF
CENTRALLY CONTROLLED
ERROR CODE
CLOCK
ON OFF
˚C
CHECK
CHECK MODE
FILTER
TEST RUN FUNCTION
˚C
1Hr.
NOT AVAILABLE
STAND BY DEFROST
FILTER
CHECK TEST
TEMP.
TIMER SET
F G E
CD
B
A
4321
STAND BY DEFROST
INDOOR UNIT ADDRESS NO
CLOCK
ON OFF
˚C
1Hr.
˚C
CHECK MODE
FILTER
CLOCK
FUNCTION
4
1
STAND BY DEFROST
INDOOR UNIT ADDRESS NO
CLOCK
ON OFF
˚C
1Hr.
˚C
CHECK MODE
FILTER
CLOCK
FUNCTION
STAND BY DEFROST
INDOOR UNIT ADDRESS NO
CLOCK
ON OFF
˚C
1Hr.
˚C
CHECK MODE
FILTER
CLOCK
FUNCTION
STAND BY DEFROST
INDOOR UNIT ADDRESS NO
CLOCK
ON OFF
˚C
1Hr.
˚C
CHECK MODE
FILTER
CLOCK
FUNCTION
21
Fig. 6-2
B-1. B-2.
Fig. 6-3
Fig. 6-4
6.2. Remote controller
6.2.1. For wired remote controller
1) Installing procedures
(1) Select an installing position for the remote controller. (Fig. 6-2) The temperature sensors are located on both remote controller and indoor unit.
s Procure the following parts locally:
Two piece switch box Thin copper conduit tube Lock nuts and bushings
A Remote controller profile B Required clearances surrounding the remote controller C Installation pitch
(2) Seal the service entrance for the remote controller cord with putty to prevent pos-
sible invasion of dew drops, water, cockroaches or worms. (Fig. 6-3)
A For installation in the switch box: B For direct installation on the wall select one of the following:
Prepare a hole through the wall to pass the remote controller cord (in order to run the remote controller cord from the back), then seal the hole with putty.
Run the remote controller cord through the cut-out upper case, then seal the cut­out notch with putty similarly as above.
B-1. To lead the remote controller cord from the back of the controller: B-2. To run the remote controller cord through the upper portion:
(3) For direct installation on the wall
C Wall D Conduit E Lock nut F Bushing G Switch box H Remote controller cord I Seal with putty J Wood screw
2) Connecting procedures (Fig. 6-4)
1 Connect the remote controller cord to the terminal block.
A To TB5 on the indoor unit B TB6 (No polarity)
2 Set the dip switch No.1 shown below when using two remote controller’s for the
same group.
C Dip switches
Setting the dip switches
The dip switches are at the bottom of the remote controller. Remote controller Main/ Sub and other function settings are performed using these switches. Ordinarily, only change the Main/Sub setting of SW No.1. (The factory settings are all “ON”.)
<SW No. 1>
SW contents Main Remote controller Main/Sub setting
ON/OFF
Main/Sub
Comment Set one of the two remote controllers at one group to “Main”
<SW No. 2>
SW contents Main When remote controller power turned on
ON/OFF
Comment
Normally on/Timer mode on When you want to return to the timer mode when the power is restored after a power failure when a Program timer is connected, select Timer mode”.
Fig. 6-5
1
Mode number
2
Setting number
3
Refrigerant address
4
Unit number
<SW No. 3>
SW contents Main Cooling/heating display in AUTO mode
ON/OFF
Comment
Yes/No When you do not want to display “Cooling” and “Heating” in the Auto mode, set to “No”.
<SW No. 4>
SW contents Main Intake temperature display
ON/OFF
Yes/No
Comment When you do not want to display the intake temperature, set to “No”.
6.3. Function settings
6.3.1. For wired remote controller (Fig. 6-5)
Changing the power voltage setting
Be sure to change the power voltage setting depending on the voltage used.
1 Go to the function setting mode.
Switch OFF the remote controller. Press the A and B buttons simultaneously and hold them for at least 2 seconds. FUNCTION will start to flash.
2 Use the C button to set the refrigerant address (3) to 00. 3 Press D and [--] will start to flash in the unit number (4) display. 4 Use the C button to set the unit number (4) to 00. 5 Press the E MODE button to designate the refrigerant address/unit number. [--]
will flash in the mode number (1) display momentarily.
6 Press the F buttons to set the mode number (1) to 04. 7 Press the G button and the current set setting number (2) will flash.
Use the F button to switch the setting number in response to the power supply voltage to be used. Power supply voltage
8 Press the MODE button E and mode and the setting number (1) and (2) will
change to being on constantly and the contents of the setting can be confirmed.
9 Press the FILTER A and TEST RUN B buttons simultaneously for at least two
seconds. The function selection screen will disappear momentarily and the air conditioner OFF display will appear.
240 V : Setting number = 1 220 V, 230 V : Setting number = 2
7
Page 8
6. Electrical work
ON/OFF
CENTRALLY CONTROLLED
ERROR CODE
CLOCK
ON OFF
˚C
CHECK
CHECK MODE
FILTER
TEST RUN FUNCTION
˚C
1Hr.
NOT AVAILABLE
STAND BY DEFROST
FILTER
CHECK TEST
TEMP.
TIMER SET
DEF
HIJKLMG
CB A
ON/OFF
CHECK
FILTER
CHECK TEST
TEMP.
TIMER SET
B
C
A
STAND BY DEFROST
INDOOR UNIT ADDRESS NO
ERROR CODE OA UNIT ADDRESS NO
CENTRALLY CONTROLLED
CLOCK
ON OFF
˚C
1Hr.
NOT AVAILABLE
˚C
CHECK MODE
FILTER
CHECK
FUNCTION
STAND BY DEFROST
INDOOR UNIT ADDRESS NO
ERROR CODE OA UNIT ADDRESS NO
CENTRALLY CONTROLLED
CLOCK
ON OFF
˚C
1Hr.
NOT AVAILABLE
˚C
CHECK MODE
FILTER
CHECK
FUNCTION
a)
D
E
F
Function table
Select unit number 00
Mode Power failure automatic recovery
Indoor temperature detecting
LOSSNAY connectivity
Power voltage
Auto mode (only for PUHZ)
Select unit numbers 01 to 03 or all units (AL [wired remote controller]/07 [wireless remote controller])
Mode Filter sign
Fan speed
No. of air outlets
Installed options (high-performance filter)
Up/down vane setting
Energy saving air flow (Heating mode)
Settings Not available Available Indoor unit operating average Set by indoor units remote controller Remote controllers internal sensor Not Supported Supported (indoor unit is not equipped with outdoor-air intake) Supported (indoor unit is equipped with outdoor-air intake) 240 V 220 V, 230 V Energy saving cycle automatically enabled Energy saving cycle automatically disabled
Settings 100 Hr 2500 Hr No filter sign indicator Standard (PLH/PLA)/Silent (PCH/PCA) High ceiling 1 (PLH/PLA)/Standard (PCH/PCA) High ceiling 2 (PLH/PLA)/High ceiling (PCH/PCA) 4 directions 3 directions 2 directions Not supported Supported No vanes Equipped with vanes (vanes angle setup 1) Equipped with vanes (vanes angle setup 2) Disabled Enabled
Mode no. Setting no.
01
1 2 1
02 2
3 1
03 2
3
04
05
1 2 1 2
Mode no. Setting no.
1
07 2
3 1
08 2
3 1
09 2
3
10
1 2 1
11
2 3
12
1 2
Initial setting
Initial setting
Setting
Setting
7. Test run
7.1. Before test run
s After completing installation and the wiring and piping of the indoor and outdoor
units, check for refrigerant leakage, looseness in the power supply or control wiring, wrong polarity, and no disconnection of one phase in the supply.
s Use a 500-volt megohmmeter to check that the resistance between the power
supply terminals and ground is at least 1.0 M
Fig. 7-1
8
Fig. 7-2
s Do not carry out this test on the control wiring (low voltage circuit) termi-
nals. Warning:
ΩΩ
Insulation resistance
ΩΩ
Do not use the air conditioner if the insulation resistance is less than 1.0 M
Ω.
ΩΩ
Ω.
ΩΩ
7.2. Test run
The following 3 methods are available.
7.2.1. Using wired remote controller (Fig. 7-1)
1 Turn on the power at least 12 hours before the test run. 2 Press the [TEST] button twice. TEST RUN liquid crystal display 3 Press the [Mode selection] button. Make sure that wind is blown out. 4 Press the [Mode selection] button and switch to the cooling (or heating) mode.
Make sure that cold (or warm) wind is blown out.
5 Press the [Fan speed] button. Make sure that the wind speed is switched. 6 Switch the wind direction by pressing the [Airflow] or [Louver] button.
Make sure that horizontal outlet, downward outlet, and other wind direction
adjustments are possible.
Check operation of the outdoor unit fan.
7 Release test run by pressing the [ON/OFF] button. Stop 8 After the checks, always turn off the power.
7.2.2. Using SW4 in outdoor unit
Refer to the outdoor unit installation manual.
7.3. Self-check
7.3.1. Wired remote controller (Fig. 7-2)
1 Turn on the power. 2 Press the [CHECK] button twice. 3 Set refrigerant address with [TEMP] button if system control is used. 4 Press the [ON/OFF] button to stop the self-check.
A CHECK button B Refrigerant address C TEMP. button D IC: Indoor unit
OC: Outdoor unit
E Check code F Unit address
Page 9
7. Test run
For description of each check code, refer to the following table.
1 Check code Symptom 2 Buzzer sound 3 OPE LED P1 Intake sensor error Single beep × 1 Lit for 1 sec. × 1 P2 Pipe sensor error Single beep × 2 Lit for 1 sec. × 2 P4 Drain sensor error Single beep × 4 Lit for 1 sec. × 4 P5 Drain pump error Single beep × 5 Lit for 1 sec. × 5 P6 Freezing/Overheating safeguard operation Single beep × 6 Lit for 1 sec. × 6 P8 Pipe temperature error Single beep × 8 Lit for 1 sec. × 8 P9 TH5 sensor error Single beep × 2 Lit for 1 sec. × 2 U0–UP Outdoor unit error Double beep × 1 Lit for 0.4 sec. + 0.4 sec. × 1 F1–FA Outdoor unit error Double beep × 1 Lit for 0.4 sec. + 0.4 sec. × 1 E0–E5 Signal error between remote controller and indoor units Sounds other than above Lights other than above E6–EF Communication error between indoor and outdoor units Sounds other than above Lights other than above – – No alarm history No sound Not lit F F F F No unit Triple beep Not lit
On wireless remote controller
2 The continuous buzzer sounds from receiving section of indoor unit. 3 Blink of operation lamp
On wired remote controller
1 Check code displayed in the LCD.
If the unit cannot be operated properly after the above test run has been performed, refer to the following table to remove the cause.
Wired remote controller LED 1, 2 (PCB in outdoor unit)
H0
H0 Error code
Display messages do not appear even when operation switch is turned ON (operation lamp does not light up).
Symptom
For about 2 minutes following power-on
After about 2 minutes has expired following power-on
After LED 1, 2 are lighted, LED 2 is turned off, then only LED 1 is lighted. (Correct operation)
Only LED 1 is lighted. LED 1, 2 blink.
Only LED 1 is lighted. LED 1 blinks twice, LED 2 blinks once.
For about 2 minutes following power-on, operation of the remote controller is not possible due to system start-up. (Cor­rect operation)
Connector for the outdoor units protection device is not con­nected.
Reverse or open phase wiring for the outdoor units power terminal block (L1, L2, L3)
Incorrect wiring between indoor and outdoor units (incorrect polarity of S1, S2, S3)
Remote controller wire short
Cause
On the wireless remote controller with condition above, following phenomena takes place.
No signals from the remote controller are accepted.
OPE lamp is blinking.
The buzzer makes a short piping sound.
Note: Operation is not possible for about 30 seconds after cancellation of function selection. (Correct operation)
For description of each LED (LED1, 2, 3) provided on the indoor controller, refer to the following table.
LED1 (power for microcomputer) Indicates whether control power is supplied. Make sure that this LED is always lit.
LED2 (power for remote controller) Indicates whether power is supplied to the remote controller. This LED lights only in the case of the
LED3 (communication between indoor and outdoor units) Indicates state of communication between the indoor and outdoor units. Make sure that this LED is
indoor unit which is connected to the outdoor unit refrigerant address “0”.
always blinking.
9
Page 10
This product is designed and intended for use in the residential,
commercial and light-industrial environment.
The product at hand is based on the following EU regulations:
Low Voltage Directive 73/23/ EEC
Electromagnetic Compatibility Directive 89/
336/ EEC
Please be sure to put the contact address/telephone number on
this manual before handing it to the customer.
HEAD OFFICE: MITSUBISHI DENKI BLDG., 2-2-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
BG79U334H01
Printed in Japan
Loading...