Indicates that incorrect handling may cause hazardous conditions, resulting in
death or severe injury.
CAUTION
Indicates that incorrect handling may cause hazardous conditions, resulting in
minor or moderate injury or property damage.
Indicates what must not be done. For example, "No Fire" is indicated by .
Indicates what must be done. For example, grounding is indicated by .
(Please read the instructions carefully before using the equipment.)
To use the equipment correctly, do not attempt to install, operate, maintain, or inspect the equipment until you have read
through this Instruction Manual, Installation guide, and appended documents carefully. Do not use the equipment until you
have a full knowledge of the equipment, safety information and instructions.
In this Instruction Manual, the safety instruction levels are classified into "WARNING" and "CAUTION".
Note that the CAUTION level may lead to a serious consequence according to conditions.
Please follow the instructions of both levels because they are important to personnel safety.
What must not be done and what must be done are indicated by the following diagrammatic symbols.
In this Instruction Manual, instructions at a lower level than the above, instructions for other functions, and so on are classified
into "POINT".
After reading this Instruction Manual, keep it accessible to the operator.
1
[To prevent electric shock, note the following]
WARNING
● Before wiring and inspections, turn off the power and wait for 15 minutes or more until the charge
lamp turns off. Then, confirm that the voltage between P+ and N- is safe with a voltage tester and
others. Otherwise, an electric shock may occur. In addition, when confirming whether the charge lamp
is off or not, always confirm it from the front of the servo amplifier.
● Ground the servo amplifier and servo motor securely.
● Any person who is involved in wiring and inspection should be fully competent to do the work.
● Do not attempt to wire the servo amplifier and servo motor until they have been installed. Otherwise, it
may cause an electric shock.
● Do not operate switches with wet hands. Otherwise, it may cause an electric shock.
● The cables should not be damaged, stressed, loaded, or pinched. Otherwise, it may cause an electric
shock.
● During power-on or operation, do not open the front cover of the servo amplifier. Otherwise, it may
cause an electric shock.
● Do not operate the servo amplifier with the front cover removed. High-voltage terminals and charging
area are exposed and you may get an electric shock.
● Except for wiring and periodic inspection, do not remove the front cover of the servo amplifier even if
the power is off. The servo amplifier is charged and you may get an electric shock.
● To prevent an electric shock, always connect the protective earth (PE) terminal (marked ) of the
servo amplifier to the protective earth (PE) of the cabinet.
● To avoid an electric shock, insulate the connections of the power supply terminals.
[To prevent fire, note the following]
CAUTION
● Install the servo amplifier, servo motor, and regenerative resistor on incombustible material. Installing
them directly or close to combustibles will lead to smoke or a fire.
● Always connect a magnetic contactor between the power supply and the main circuit power supply
(L1/L2/L3) of the servo amplifier, in order to configure a circuit that shuts down the power supply on
the side of the servo amplifier’s power supply. If a magnetic contactor is not connected, continuous
flow of a large current may cause smoke or a fire when the servo amplifier malfunctions.
● Always connect a molded-case circuit breaker, or a fuse to each servo amplifier between the power
supply and the main circuit power supply (L1/L2/L3) of the servo amplifier, in order to configure a
circuit that shuts down the power supply on the side of the servo amplifier’s power supply. If a moldedcase circuit breaker or fuse is not connected, continuous flow of a large current may cause smoke or
a fire when the servo amplifier malfunctions.
● When using the regenerative resistor, switch power off with the alarm signal. Otherwise, a
regenerative transistor malfunction or the like may overheat the regenerative resistor, causing smoke
or a fire.
● Provide adequate protection to prevent screws and other conductive matter, oil and other combustible
matter from entering the servo amplifier and servo motor.
2
[To prevent injury, note the following]
CAUTION
● Only the power/signal specified in the Instruction Manual should be applied to each terminal.
Otherwise, it may cause an electric shock, fire, injury, etc.
● Connect cables to the correct terminals. Otherwise, a burst, damage, etc., may occur.
● Ensure that polarity (+/-) is correct. Otherwise, a burst, damage, etc., may occur.
● The servo amplifier heat sink, regenerative resistor, servo motor, etc., may be hot while the power is
on and for some time after power-off. Take safety measures such as providing covers to avoid
accidentally touching them by hands and parts such as cables.
3
[Additional instructions]
The following instructions should also be fully noted. Incorrect handling may cause a malfunction, injury, electric shock, fire,
etc.
[Transportation and installation]
CAUTION
● Transport the products correctly according to their mass.
● Stacking in excess of the specified number of product packages is not allowed.
● Do not hold the front cover, cables, or connectors when carrying the servo amplifier. Otherwise, it may
drop.
● Install the servo amplifier and the servo motor in a load-bearing place in accordance with the
Instruction Manual.
● Do not get on or put heavy load on the equipment. Otherwise, it may cause injury.
● The equipment must be installed in the specified direction.
● Maintain specified clearances between the servo amplifier and the inner surfaces of a control cabinet
or other equipment.
● Do not install or operate the servo amplifier and servo motor which have been damaged or have any
parts missing.
● Do not block the intake and exhaust areas of the servo amplifier. Otherwise, it may cause a
malfunction.
● Do not drop or apply heavy impact on the servo amplifiers and the servo motors. Otherwise, it may
cause injury, malfunction, etc.
● Do not strike the connector. Otherwise, it may cause a connection failure, malfunction, etc.
● When you keep or use the equipment, please fulfill the following environment.
ItemEnvironment
Ambient
temperature
Ambient
humidity
Vibration resistance
Operation
Storage
Operation
Storage
Ambience
Altitude
Indoors (no direct sunlight), free from corrosive gas, flammable gas, oil mist, dust, and dirt
2000 m or less above sea level (Contact your local sales office for the altitude for options.)
0 °C to 55 °C (non-freezing)
-20 °C to 65 °C (non-freezing)
5 %RH to 90 %RH (non-condensing)
2
, at 10 Hz to 55 Hz (X, Y, Z axes)
5.9 m/s
● When the product has been stored for an extended period of time, contact your local sales office.
● When handling the servo motor, be careful with the sharp edges of the servo motor.
● The servo amplifier must be installed in a metal cabinet.
● When fumigants that contain halogen materials, such as fluorine, chlorine, bromine, and iodine, are
used for disinfecting and protecting wooden packaging from insects, they cause a malfunction when
entering our products. Please take necessary precautions to ensure that remaining materials from
fumigant do not enter our products, or treat packaging with methods other than fumigation, such as
heat treatment. Additionally, disinfect and protect wood from insects before packing the products.
● To prevent a fire or injury in case of an earthquake or other natural disasters, securely install, mount,
and wire the servo motor in accordance with the Instruction Manual.
4
[Wiring]
24 V DC
RA
DOCOM
Control output
signal
Servo amplifier
For sink output interface
24 V DC
RA
DOCOM
Control output
signal
Servo amplifier
For source output interface
CAUTION
● Wire the equipment correctly and securely. Otherwise, the servo motor may operate unexpectedly.
● Make sure to connect the cables and connectors by using the fixing screws and the locking
mechanism. Otherwise, the cables and connectors may be disconnected during operation.
● Do not install a power capacitor, surge killer, or radio noise filter (optional FR-BIF(-H)) on the servo
amplifier output side.
● To avoid a malfunction, connect the wires to the correct phase terminals (U/V/W) of the servo amplifier
and servo motor.
● Connect the servo amplifier power output (U/V/W) to the servo motor power input (U/V/W) directly. Do
not connect a magnetic contactor and others between them. Otherwise, it may cause a malfunction.
Servo amplifier
U
V
W
● The connection diagrams in this Instruction Manual are shown for sink interfaces, unless stated
otherwise.
● The surge absorbing diode installed to the DC relay for control output should be fitted in the specified
direction. Otherwise, the converter unit and the drive unit will malfunction and will not output signals,
disabling the emergency stop and other protective circuits.
Servo motor
U
V
W
Servo motorServo amplifier
U
M
V
W
U
V
M
W
● When the wires are not tightened enough to the terminal block, the wires or terminal block may
generate heat because of the poor contact. Be sure to tighten the wires with specified torque.
● Connecting a servo motor of the wrong axis to U, V, W, or CN2 of the servo amplifier may cause a
malfunction.
● Configure a circuit to turn off EM2 or EM1 when the main circuit power supply is turned off to prevent
an unexpected restart of the servo amplifier.
● To prevent malfunction, avoid bundling power lines (input/output) and signal cables together or
running them in parallel to each other. Separate the power lines from the signal cables.
[Test run and adjustment]
CAUTION
● When executing a test run, follow the notice and procedures in this instruction manual. Otherwise, it
may cause a malfunction, damage to the machine, or injury.
● Before operation, check and adjust the parameter settings. Improper settings may cause some
machines to operate unexpectedly.
● Never make a drastic adjustment or change to the parameter values as doing so will make the
operation unstable.
● Do not get close to moving parts during the servo-on status.
5
[Usage]
CAUTION
● Provide an external emergency stop circuit to stop the operation and shut the power off immediately.
● For equipment in which the moving part of the machine may collide against the load side, install a limit
switch or stopper to the end of the moving part. The machine may be damaged due to a collision.
● Do not disassemble, repair, or modify the product. Otherwise, it may cause an electric shock, fire,
injury, etc. Disassembled, repaired, and/or modified products are not covered under warranty.
● Before resetting an alarm, make sure that the run signal of the servo amplifier is off in order to prevent
a sudden restart. Otherwise, it may cause an accident.
● Use a noise filter, etc., to minimize the influence of electromagnetic interference. Electromagnetic
interference may affect the electronic equipment used near the servo amplifier.
● Do not burn or destroy the servo amplifier. Doing so may generate a toxic gas.
● Use the servo amplifier with the specified servo motor.
● Wire options and peripheral equipment, etc. correctly in the specified combination. Otherwise, it may
cause an electric shock, fire, injury, etc.
● The electromagnetic brake on the servo motor is designed to hold the motor shaft and should not be
used for ordinary braking.
● For such reasons as incorrect wiring, service life, and mechanical structure (e.g. where a ball screw
and the servo motor are coupled via a timing belt), the electromagnetic brake may not hold the motor
shaft. To ensure safety, install a stopper on the machine side.
● If the dynamic brake is activated at power-off, alarm occurrence, etc., do not rotate the servo motor by
an external force. Otherwise, it may cause a fire.
6
[Corrective actions]
Servo motor
Electromagnetic brake
B
U
RA
Contacts must be opened with
the emergency stop switch.
Contacts must be opened when ALM
(Malfunction) or MBR (Electromagnetic
brake interlock) turns off.
24 V DC
CAUTION
● Ensure safety by confirming the power off, etc. before performing corrective actions. Otherwise, it may
cause an accident.
● If it is assumed that a power failure, machine stoppage, or product malfunction may result in a
hazardous situation, use a servo motor with an electromagnetic brake or provide an external brake
system for holding purpose to prevent such hazard.
● Configure an electromagnetic brake circuit which is interlocked with an external emergency stop
switch.
● When an alarm occurs, eliminate its cause, ensure safety, and deactivate the alarm to restart
operation.
● If the molded-case circuit breaker or fuse is activated, be sure to remove the cause and secure safety
before switching the power on. If necessary, replace the servo amplifier and recheck the wiring.
Otherwise, it may cause smoke, fire, or an electric shock.
● Provide an adequate protection to prevent unexpected restart after an instantaneous power failure.
● After an earthquake or other natural disasters, ensure safety by checking the conditions of the
installation, mounting, wiring, and equipment before switching the power on to prevent an electric
shock, injury, or fire.
[Maintenance, inspection and parts replacement]
CAUTION
● Make sure that the emergency stop circuit operates properly such that an operation can be stopped
immediately and a power is shut off by the emergency stop switch.
● It is recommended that the servo amplifier be replaced every 10 years when it is used in general
environment.
● When using the servo amplifier that has not been energized for an extended period of time, contact
your local sales office.
[General instruction]
● To illustrate details, the equipment in the diagrams of this Instruction Manual may have been drawn
without covers and safety guards. When the equipment is operated, the covers and safety guards
must be installed as specified. Operation must be performed in accordance with this Instruction
Manual.
7
DISPOSAL OF WASTE
• Please dispose a servo amplifier, battery (primary battery) and other options according to your local laws and regulations.
EEP-ROM LIFE
The number of write times to the EEP-ROM, which stores parameter settings, etc., is limited to 100,000. If the total number of
the following operations exceeds 100,000, the servo amplifier may malfunction when the EEP-ROM reaches the end of its
useful life.
• Write to the EEP-ROM due to parameter setting changes
• Write to the EEP-ROM due to device changes
STO FUNCTION OF THE SERVO AMPLIFIER
When using the STO function of the servo amplifier, refer to the following.
Page 453 USING STO FUNCTION
For the MR-J3-D05 safety logic unit, refer to the following.
Page 586 MR-J3-D05 Safety logic unit
COMPLIANCE WITH GLOBAL STANDARDS
For the compliance with global standards, refer to the following.
Page 572 Compliance with global standards
8
ABOUT THE MANUALS
You must have this Instruction Manual and the following manuals to use this servo. Ensure to prepare them to use the servo
*1 It is necessary for using an MR-D30 functional safety unit.
*2 It is necessary for using a rotary servo motor.
*3 It is necessary for using a linear servo motor.
*4 It is necessary for using a direct drive motor.
*5 It is necessary for using a fully closed loop system.
*1
*2
*3
*4
*3*5
SH(NA)030132ENG
SH(NA)030113ENG
SH(NA)030110ENG
SH(NA)030112ENG
SH(NA)030111ENG
WIRING
Wires mentioned in this Instruction Manual are selected based on the ambient temperature of 40 .
U.S. CUSTOMARY UNITS
U.S. customary units are not shown in this manual. Convert the values if necessary according to the following table.
The Mitsubishi Electric general-purpose AC servo MELSERVO-J4 series have further higher performance and higher
functions compared to the previous MELSERVO-J3 series.
MR-J4-_GF_ servo amplifier can be connected to controllers, such as a simple motion module on CC-Link IE Field Network.
CC-Link IE Field Network is an open network using Ethernet (1000BASE-T), allowing high-speed and large-capacity
communication. A communication speed of 1 Gbps achieves high-speed control of field devices and high-speed
communication between facilities, thus shortening operating cycle.
MELSERVO-J4 series compatible rotary servo motor is equipped with 22-bit (4194304 pulses/rev) high-resolution absolute
encoder. In addition, speed frequency response is increased to 2.5 kHz. Thus, faster and more accurate control is enabled as
compared to MELSERVO-J3 series.
MR-J4-_GF_ servo amplifier operates MELSERVO-J4 series compatible rotary servo motors, linear servo motors, and direct
drive motors as standard.
With one-touch tuning and real-time auto tuning, you can easily adjust the servo gains according to the machine.
The tough drive function and the drive recorder function, which are well-received in the MELSERVO-JN series, have been
improved. The MR-J4 servo amplifier supports the improved functions. Additionally, the preventive maintenance support
function detects an error in the machine parts. This function provides strong support for the machine maintenance and
inspection.
MR-J4-_GF_ servo amplifier supports the Safe Torque Off (STO) function. By combining with optional MR-J3-D05, the servo
amplifier supports Safe stop 1 (SS1) function.
The servo amplifier has a USB communication interface. Therefore, you can connect the servo amplifier to the personal
computer with MR Configurator2 installed to perform the parameter setting, test operation, gain adjustment, and others.
In the MELSERVO-J4 series, servo amplifiers with the CN2L connector are also available as MR-J4-_GF_-RJ.
By using the CN2L connector, an A/B/Z-phase differential output type external encoder can be connected to the servo
amplifier. In a fully closed loop system, a four-wire type external encoder is connectable as well. The following table indicates
the communication method of the external encoder compatible with MR-J4-_GF_ and MR-J4-_GF_-RJ servo amplifiers.
Operation modeExternal encoder
communication method
Linear servo motor system
Fully closed loop system
Scale measurement function
*5
*5
*5
Two-wire typeCN2
Four-wire type
A/B/Z-phase differential output
method
Two-wire typeCN2
Four-wire type
A/B/Z-phase differential output
method
Two-wire typeCN2
Four-wire type
A/B/Z-phase differential output
method
Connector
MR-J4-_GF_MR-J4-_GF_-RJ
*1
CN2L
*2*3
*2*3
CN2
CN2L
CN2L
*1
*4
*1 The MR-J4THCBL03M branch cable is necessary.
*2 The MR-J4FCCBL03M branch cable is necessary.
*3 When the communication method of the servo motor encoder is four-wire type, MR-J4-_GF_ cannot be used. Use an MR-J4-_GF_-RJ.
*4 Connect a thermistor to CN2.
*5 This is used with servo amplifiers with software version A1 or later.
18
1 FUNCTIONS AND CONFIGURATION
1.1 Summary
1.2Function block diagram
The function block diagram of this servo is shown below.
The diagram shows for MR-J4-_GF_-RJ as an example. MR-J4-_GF_ servo amplifier does not have CN2L
connector.
1
1 FUNCTIONS AND CONFIGURATION
1.2 Function block diagram
19
200 V class
Model position
Current
control
Actual
position
control
Actual
speed
control
Virtual
motor
Virtual
encoder
L11
L21
Cooling fan
*3
Encoder
N-CD
L3
L2
L1
Dynamic
brake
circuit
Power factor improving
DC reactor
*6
Current
detection
Overcurrent
protection
Voltage
detection
Power
supply
*2
MCMCCB
Base
amplifier
STO
circuit
CN5
USB
USB
Personal
computer
Controller or
servo amplifier
Controller or
servo amplifier
CN1A
CN1B
D/A
Analog monitor
(2 channels)
Position
command
input
CN3
Servo amplifier
U
V
W
U
V
W
P3
P4
*4
Diode
stack
Relay
P+
+
+
B
RA
24 V DC
B1
B2
Battery
(For absolute position
detection system)
CN4
STO
switch
Model speed Model torque
M
CN2
CN8
Control
circuit
power
supply
Model
position
control
Model
speed
control
I/F Control
Servo motor
CHARGE
lamp
Regenerative
TR
Current
detector
Digital I/O
control
Regenerative
option
UU
U
Stepdown
circuit
Electromagnetic
brake
*1
*5
External encoder
CN2L
■MR-J4-500GF(-RJ) or less
20
1 FUNCTIONS AND CONFIGURATION
1.2 Function block diagram
*1 The built-in regenerative resistor is not provided for MR-J4-10GF(-RJ).
*2 For 1-phase 200 V AC to 240 V AC, connect the power supply to L1 and L3. Leave L2 open. Refer to the following for the power supply
specifications.
Page 30 Servo amplifier standard specifications
*3 Servo amplifiers MR-J4-70GF(-RJ) or more have a cooling fan.
*4 MR-J4 servo amplifier has P3 and P4 in the upstream of the inrush current suppression circuit. They are different from P1 and P2 of MR-
J3 servo amplifiers.
*5 This is for MR-J4-_GF-RJ servo amplifier. MR-J4-_GF servo amplifier does not have CN2L connector.
*6 The power factor improving AC reactor can also be used. In this case, the power factor improving DC reactor cannot be used. When not
using the power factor improving DC reactor, short P3 and P4.
1
1 FUNCTIONS AND CONFIGURATION
1.2 Function block diagram
21
■MR-J4-700GF(-RJ)
L11
L21
Cooling fan
N-C
MCMCCB
STO
circuit
CN5
USB
USB
CN1A
CN1B
D/A
CN3
Servo amplifier
U
V
W
U
V
W
P3
P4
*2
Relay
P+
+
+
B
RA
B1
CN4
M
CN2
CN8
Control
circuit
power
supply
CHARGE
lamp
Regenerative
TR
Regenerative
option
L3
L2
L1
U U
U
Current
detection
Overcurrent
protection
Voltage
detection
Base
amplifier
STO
switch
Servo motor
24 V DC
Encoder
Model position
Current
control
Actual
position
control
Actual
speed
control
Virtual
motor
Virtual
encoder
Position
command
input
Model speed Model torque
Model
position
control
Model
speed
control
Stepdown
circuit
Battery
(For absolute position
detection system)
I/F Control
Personal
computer
Analog monitor
(2 channels)
Digital I/O
control
Diode
stack
CN2L
External encoder
Controller or
servo amplifier
Controller or
servo amplifier
Power factor improving
DC reactor
*4
Power
supply
*1
Electromagnetic
brake
*3
Dynamic
brake
circuit
Current
detector
*1 Refer to the following for the power supply specifications.
Page 30 Servo amplifier standard specifications
*2 MR-J4 servo amplifier has P3 and P4 in the upstream of the inrush current suppression circuit. They are different from P1 and P2 of MR-
J3 servo amplifiers.
*3 This is for MR-J4-_GF-RJ servo amplifier. MR-J4-_GF servo amplifier does not have CN2L connector.
*4 The power factor improving AC reactor can also be used. In this case, the power factor improving DC reactor cannot be used. When not
using the power factor improving DC reactor, short P3 and P4.
*1 Refer to the following for the power supply specifications.
Page 30 Servo amplifier standard specifications
*2 MR-J4 servo amplifier has P3 and P4 in the upstream of the inrush current suppression circuit. They are different from P1 and P2 of MR-
J3 servo amplifiers.
*3 This is for MR-J4-_GF-RJ servo amplifier. MR-J4-_GF servo amplifier does not have CN2L connector.
*4 Use an external dynamic brake for this servo amplifier. Failure to do so will cause an accident because the servo motor does not stop
immediately but coasts at an alarm occurrence for which the servo motor does not decelerate to stop. Ensure the safety in the entire
equipment. For alarms for which the servo motor does not decelerate to stop, refer to the following.
Page 280 TROUBLESHOOTING
*5 The power factor improving AC reactor can also be used. In this case, the power factor improving DC reactor cannot be used. When not
using the power factor improving DC reactor, short P3 and P4.
*6 The external dynamic brake cannot be used for compliance with SEMI-F47 standard. Do not assign DB (Dynamic brake interlock) in [Pr.
PD07] to [Pr. PD09]. Failure to do so will cause the servo amplifier to become servo-off when an instantaneous power failure occurs.
24
1 FUNCTIONS AND CONFIGURATION
1.2 Function block diagram
400 V class
Model position
Current
control
Actual
position
control
Actual
speed
control
Virtual
motor
Virtual
encoder
L11
L21
Cooling fan
*2
Encoder
N-CD
L3
L2
L1
Dynamic
brake
circuit
Current
detection
Overcurrent
protection
Voltage
detection
Power
supply
*1
MCMCCB
Base
amplifier
STO
circuit
CN5
USB
USB
Personal
computer
CN1A
CN1B
D/A
Analog monitor
(2 channels)
Position
command
input
CN3
Servo amplifier
U
V
W
U
V
W
P3P4
*3
Diode
stack
Relay
P+
+
+
B
RA
24 V DC
B1
B2
Battery
(For absolute position
detection system)
CN4
STO
switch
Model speed Model torque
M
CN2
CN8
Control
circuit
power
supply
Model
position
control
Model
speed
control
I/F Control
Servo motor
Charge
lamp
Regenerative
TR
Current
detector
Digital I/O
control
Regenerative
option
U U
U
Stepdown
circuit
Power factor improving
DC reactor
*5
CN2L
External encoder
Controller or
servo amplifier
Controller or
servo amplifier
*4
Electromagnetic
brake
■MR-J4-350GF4(-RJ) or less
1
*1 Refer to the following for the power supply specification.
Page 30 Servo amplifier standard specifications
*2 Servo amplifiers MR-J4-200GF4(-RJ) or more have a cooling fan.
*3 MR-J4 servo amplifier has P3 and P4 in the upstream of the inrush current suppression circuit. They are different from P1 and P2 of MR-
J3 servo amplifiers.
*4 This is for MR-J4-_GF4-RJ servo amplifier. MR-J4-_GF4 servo amplifier does not have CN2L connector.
*5 The power factor improving AC reactor can also be used. In this case, the power factor improving DC reactor cannot be used. When not
using the power factor improving DC reactor, short P3 and P4.
1 FUNCTIONS AND CONFIGURATION
1.2 Function block diagram
25
■MR-J4-500GF4(-RJ)/MR-J4-700GF4(-RJ)
Dynamic
brake
circuit
Current
detector
Virtual
motor
Virtual
encoder
L11
L21
Cooling fan
Encoder
N-C
Current
detection
Overcurrent
protection
Voltage
detection
Power
supply
*1
MCMCCB
Base
amplifier
STO
circuit
CN5
USB
USB
CN1A
CN1B
D/A
Position
command
input
CN3
Servo amplifier
Diode
stack
U
V
W
U
V
W
P3P4
*2
Relay
P+
+
+
B
RA
24 V DC
B1
B2
Battery
(For absolute position
detection system)
CN4
STO
switch
M
CN2
CN8
Control
circuit
power
supply
Model
position
control
Model
speed
control
Servo motor
Regenerative
option
L3
L2
L1
U U
U
Stepdown
circuit
Power factor improving
DC reactor
*4
Charge
lamp
Regenerative
TR
Electromagnetic
brake
Model position Model speed Model torque
Current
control
Actual
position
control
Actual
speed
control
I/F Control
Personal
computer
Analog monitor
(2 channels)
Digital I/O
control
CN2L
External encoder
Controller or
servo amplifier
Controller or
servo amplifier
*3
*1 Refer to the following for the power supply specification.
Page 30 Servo amplifier standard specifications
*2 MR-J4 servo amplifier has P3 and P4 in the upstream of the inrush current suppression circuit. They are different from P1 and P2 of MR-
J3 servo amplifiers.
*3 This is for MR-J4-_GF4-RJ servo amplifier. MR-J4-_GF4 servo amplifier does not have CN2L connector.
*4 The power factor improving AC reactor can also be used. In this case, the power factor improving DC reactor cannot be used. When not
using the power factor improving DC reactor, short P3 and P4.
*1 Refer to the following for the power supply specification.
Page 30 Servo amplifier standard specifications
*2 MR-J4 servo amplifier has P3 and P4 in the upstream of the inrush current suppression circuit. They are different from P1 and P2 of MR-
J3 servo amplifiers.
*3 This is for MR-J4-_GF4-RJ servo amplifier. MR-J4-_GF4 servo amplifier does not have CN2L connector.
*4 Use an external dynamic brake for this servo amplifier. Failure to do so will cause an accident because the servo motor does not stop
immediately but coasts at an alarm occurrence for which the servo motor does not decelerate to stop. Ensure the safety in the entire
equipment. For alarms for which the servo motor does not decelerate to stop, refer to the following.
Page 280 TROUBLESHOOTING
*5 The power factor improving AC reactor can also be used. In this case, the power factor improving DC reactor cannot be used. When not
using the power factor improving DC reactor, short P3 and P4.
*6 The external dynamic brake cannot be used for compliance with SEMI-F47 standard. Do not assign DB (Dynamic brake interlock) in [Pr.
PD07] to [Pr. PD09]. Failure to do so will cause the servo amplifier to become servo-off when an instantaneous power failure occurs.
28
1 FUNCTIONS AND CONFIGURATION
1.2 Function block diagram
Loading...
+ 616 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.