Mitsubishi Electric MR-J4, MR-J4-03A6 Instruction Manual

General-Purpose AC Servo
General-Purpose Interface AC Servo
MODEL
SERVO AMPLIFIER INSTRUCTION MANUAL
K

Safety Instructions

Please read the instructions carefully before using the equipment.
To use the equipment correctly, do not attempt to install, operate, maintain, or inspect the equipment until you have read through this Instruction Manual, Installation guide, and appended documents carefully. Do not use the equipment until you have a full knowledge of the equipment, safety information and instructions. In this Instruction Manual, the safety instruction levels are classified into "WARNING" and "CAUTION".
WARNING
CAUTION
Note that the CAUTION level may lead to a serious consequence according to conditions. Please follow the instructions of both levels because they are important to personnel safety. What must not be done and what must be done are indicated by the following diagrammatic symbols.
Indicates that incorrect handling may cause hazardous conditions,
resulting in death or severe injury.
Indicates that incorrect handling may cause hazardous conditions,
resulting in medium or slight injury to personnel or may cause physical damage.
Indicates what must not be done. For example, "No Fire" is indicated by .
Indicates what must be done. For example, grounding is indicated by .
In this Instruction Manual, instructions at a lower level than the above, instructions for other functions, and so on are classified into "POINT". After reading this Instruction Manual, keep it accessible to the operator.
A - 1
1. To prevent electric shock, note the following
WARNING
Before wiring and inspections, turn off the power and wait for 15 minutes or more until the charge lamp turns off. Then, confirm that the voltage between P+ and N- is safe with a voltage tester and others. Otherwise, an electric shock may occur. In addition, when confirming whether the charge lamp is off or not, always confirm it from the front of the servo amplifier. Ground the servo amplifier and servo motor securely. Any person who is involved in wiring and inspection should be fully competent to do the work. Do not attempt to wire the servo amplifier and servo motor until they have been installed. Otherwise, it may cause an electric shock. Do not operate switches with wet hands. Otherwise, it may cause an electric shock. The cables should not be damaged, stressed, loaded, or pinched. Otherwise, it may cause an electric shock. During power-on or operation, do not open the front cover of the servo amplifier. Otherwise, it may cause an electric shock. Do not operate the servo amplifier with the front cover removed. High-voltage terminals and charging area are exposed and you may get an electric shock. Except for wiring and periodic inspection, do not remove the front cover of the servo amplifier even if the power is off. The servo amplifier is charged and you may get an electric shock. To prevent an electric shock, always connect the protective earth (PE) terminal (marked ) of the servo amplifier to the protective earth (PE) of the cabinet. To avoid an electric shock, insulate the connections of the power supply terminals.
2. To prevent fire, note the following
CAUTION
Install the servo amplifier, servo motor, and regenerative resistor on incombustible material. Installing them directly or close to combustibles will lead to smoke or a fire. Always connect a magnetic contactor between the power supply and the main circuit power supply (L1, L2, and L3) of the servo amplifier, in order to configure a circuit that shuts down the power supply on the side of the servo amplifier’s power supply. If a magnetic contactor is not connected, continuous flow of a large current may cause smoke or a fire when the servo amplifier malfunctions. Not doing so may cause a fire when a regenerative transistor malfunctions or the like may overheat the regenerative resistor. Always connect a molded-case circuit breaker, or a fuse to each servo amplifier between the power supply and the main circuit power supply (L1, L2, and L3) of the servo amplifier, in order to configure a circuit that shuts down the power supply on the side of the servo amplifier’s power supply. If a molded­case circuit breaker or fuse is not connected, continuous flow of a large current may cause smoke or a fire when the servo amplifier malfunctions. When using the regenerative resistor, switch power off with the alarm signal. Provide adequate protection to prevent screws and other conductive matter, oil and other combustible matter from entering the servo amplifier and servo motor.
A - 2
3. To prevent injury, note the following
CAUTION
Only the voltage specified in the Instruction Manual should be applied to each terminal. Otherwise, a burst, damage, etc. may occur. Connect cables to the correct terminals. Otherwise, a burst, damage, etc. may occur. Ensure that polarity (+/-) is correct. Otherwise, a burst, damage, etc. may occur. The servo amplifier heat sink, regenerative resistor, servo motor, etc. may be hot while power is on or for some time after power-off. Take safety measures, e.g. provide covers, to prevent accidental contact of hands and parts (cables, etc.) with them.
4. Additional instructions
The following instructions should also be fully noted. Incorrect handling may cause a fault, injury, electric shock, fire, etc.
(1) Transportation and installation
CAUTION
Transport the products correctly according to their mass. Stacking in excess of the specified number of product packages is not allowed. Do not hold the front cover when transporting the servo amplifier. Otherwise, it may drop. Install the servo amplifier and the servo motor in a load-bearing place in accordance with the Instruction Manual. Do not get on or put heavy load on the equipment. The equipment must be installed in the specified direction. Leave specified clearances between the servo amplifier and the cabinet walls or other equipment. Do not install or operate the servo amplifier and servo motor which have been damaged or have any parts missing. Do not block the intake and exhaust areas of the servo amplifier. Otherwise, it may cause a malfunction. Do not drop or strike the servo amplifier and servo motor. Isolate them from all impact loads. When you keep or use the equipment, please fulfill the following environment.
temperature
When the equipment has been stored for an extended period of time, consult your local sales office. When handling the servo amplifier, be careful about the edged parts such as corners of the servo amplifier. The servo amplifier must be installed in the metal cabinet. When fumigants that contain halogen materials such as fluorine, chlorine, bromine, and iodine are used for disinfecting and protecting wooden packaging from insects, they cause malfunction when entering our products. Please take necessary precautions to ensure that remaining materials from fumigant do not enter our products, or treat packaging with methods other than fumigation (heat method).Additionally, disinfect and protect wood from insects before packing products.
Items Environment
Ambient
Ambient humidity
Vibration resistance 5.9 m/s
Operation 0 °C to 55 °C (non-freezing)
Storage -20 °C to 65 °C (non-freezing)
Operation
Storage
Ambience Indoors (no direct sunlight), free from corrosive gas, flammable gas, oil mist, dust, and dirt
Altitude Max. 1000 m above sea level
90 %RH or less (non-condensing)
2
at 10 Hz to 55 Hz (directions of X, Y, and Z axes)
A - 3
r
(2) Wiring
CAUTION
Wire the equipment correctly and securely. Otherwise, the servo motor may operate unexpectedly. Do not install a power capacitor, surge killer, or radio noise filter (FR-BIF-(H) option) on the servo amplifier output side. To avoid a malfunction, connect the wires to the correct phase terminals (U, V, and W) of the servo amplifier and servo motor. Connect the servo amplifier power output (U, V, and W) to the servo motor power input (U, V, and W) directly. Do not let a magnetic contactor, etc. intervene. Otherwise, it may cause a malfunction.
Servo amplifier
U
V
W
Servo motor
U
V
W
Servo motorServo amplifier
U
M
V
W
U
V
W
M
The connection diagrams in this instruction manual are shown for sink interfaces, unless stated otherwise. The surge absorbing diode installed to the DC relay for control output should be fitted in the specified direction. Otherwise, the emergency stop and other protective circuits may not operate.
Servo amplifier
DOCOM
Control output signal
For sink output interface
24 V DC
RA
Servo amplifie
DOCOM
Control output signal
For source output interface
24 V DC
RA
When the cable is not tightened enough to the terminal block, the cable or terminal block may generate heat because of the poor contact. Be sure to tighten the cable with specified torque. Connecting a servo motor for different axis to the U, V, W, or CN2 may cause a malfunction.
(3) Test run and adjustment
CAUTION
Before operation, check the parameter settings. Improper settings may cause some machines to perform unexpected operation. Never adjust or change the parameter values extremely as it will make operation unstable. Do not close to moving parts at servo-on status.
(4) Usage
CAUTION
Provide an external emergency stop circuit to ensure that operation can be stopped and power switched off immediately. Do not disassemble, repair, or modify the equipment.
A - 4
CAUTION
Before resetting an alarm, make sure that the run signal of the servo amplifier is off in order to prevent a sudden restart. Otherwise, it may cause an accident. Use a noise filter, etc. to minimize the influence of electromagnetic interference. Electromagnetic interference may be given to the electronic equipment used near the servo amplifier. Burning or breaking a servo amplifier may cause a toxic gas. Do not burn or break it. Use the servo amplifier with the specified servo motor. The electromagnetic brake on the servo motor is designed to hold the motor shaft and should not be used for ordinary braking. For such reasons as service life and mechanical structure (e.g. where a ball screw and the servo motor are coupled via a timing belt), the electromagnetic brake may not hold the motor shaft. To ensure safety, install a stopper on the machine side.
(5) Corrective actions
CAUTION
When it is assumed that a hazardous condition may occur due to a power failure or product malfunction, use a servo motor with an electromagnetic brake or external brake to prevent the condition. Configure an electromagnetic brake circuit so that it is activated also by an external EMG stop switch.
Contacts must be opened when ALM (Malfunction) or MBR (Electromagnetic brake interlock) turns off.
Contacts must be opened with the EMG stop switch.
Servo motor
B
Electromagnetic brake
When any alarm has occurred, eliminate its cause, ensure safety, and deactivate the alarm before restarting operation. Provide an adequate protection to prevent unexpected restart after an instantaneous power failure.
RA
24 V DC
(6) Maintenance, inspection and parts replacement
CAUTION
With age, the electrolytic capacitor of the servo amplifier will deteriorate. To prevent a secondary accident due to a malfunction, it is recommend that the electrolytic capacitor be replaced every 10 years when it is used in general environment. Please contact your local sales office. When using a servo amplifier whose power has not been turned on for a long time, contact your local sales office.
(7) General instruction
To illustrate details, the equipment in the diagrams of this Instruction Manual may have been drawn without covers and safety guards. When the equipment is operated, the covers and safety guards must be installed as specified. Operation must be performed in accordance with this Specifications and Instruction Manual.
A - 5

DISPOSAL OF WASTE

Please dispose a servo amplifier, battery (primary battery) and other options according to your local laws and regulations.
EEP-ROM life
The number of write times to the EEP-ROM, which stores parameter settings, etc., is limited to 100,000. If the total number of the following operations exceeds 100,000, the servo amplifier may malfunction when the EEP-ROM reaches the end of its useful life.
Write to the EEP-ROM due to parameter setting changes Write to the EEP-ROM due to device changes Home position setting in the absolute position detection system

STO function of the servo amplifier

When using the STO function of the servo amplifier, refer to chapter 13. For the MR-J3-D05 safety logic unit, refer to appendix 5.

Compliance with global standards

For the compliance with global standards, refer to appendix 4.
«About the manuals»
You must have this Instruction Manual and the following manuals to use this servo. Ensure to prepare them to use the servo safely. When using the MR-J4-03A6, refer to chapter 18.
Relevant manuals
Manual name Manual No. MR-J4-_A_-RJ Servo Amplifier Instruction Manual (Positioning Mode) (Note 5) SH(NA)030143 MR-J4-DU_(-RJ)/MR-CR55K_ INSTRUCTION MANUAL (Note 6) SH(NA)030153 MR-J4 Servo Amplifier Instruction Manual (Troubleshooting) SH(NA)030109 MELSERVO Servo Motor Instruction Manual (Vol. 3) (Note 1) SH(NA)030113 MELSERVO Linear Servo Motor Instruction Manual (Note 2) SH(NA)030110 MELSERVO Direct Drive Motor Instruction Manual (Note 3) SH(NA)030112 MELSERVO Linear Encoder Instruction Manual (Note 2, 4) SH(NA)030111 EMC Installation Guidelines IB(NA)67310 PARAMETER UNIT MR-PRU03 INSTRUCTION MANUAL (MR-J4) SH(NA)030186
Note 1. It is necessary for using a rotary servo motor.
2. It is necessary for using a linear servo motor.
3. It is necessary for using a direct drive motor.
4. It is necessary for using a fully closed loop system.
5. It is necessary for using an MR-J4-_A_-RJ servo amplifier in the positioning mode.
6. It is necessary for using an MR-J4-DU_A_(-RJ) drive unit and MR-CR55K_ converter unit.
A - 6
«Wiring»
Wires mentioned in this Instruction Manual are selected based on the ambient temperature of 40 °C.
«U.S. customary units»
U.S. customary units are not shown in this manual. Convert the values if necessary according to the following table.
Quantity SI (metric) unit U.S. customary unit Mass 1 [kg] 2.2046 [lb] Length 1 [mm] 0.03937 [inch] Torque 1 [N•m] 141.6 [oz•inch] Moment of inertia 1 [(× 10-4 kg•m2)] 5.4675 [oz•inch2] Load (thrust load/axial load) 1 [N] 0.2248 [lbf] Temperature N [°C] × 9/5 + 32 N [°F]
A - 7
MEMO
A - 8

CONTENTS

1. FUNCTIONS AND CONFIGURATION 1- 1 to 1-54
1.1 Summary ........................................................................................................................................... 1- 1
1.2 Function block diagram ..................................................................................................................... 1- 3
1.3 Servo amplifier standard specifications ........................................................................................... 1-11
1.4 Combinations of servo amplifiers and servo motors ....................................................................... 1-17
1.5 Function list ...................................................................................................................................... 1-19
1.6 Model designation ............................................................................................................................ 1-22
1.7 Structure .......................................................................................................................................... 1-23
1.7.1 Parts identification ..................................................................................................................... 1-23
1.7.2 Removal and reinstallation of the front cover............................................................................ 1-38
1.8 Configuration including peripheral equipment ................................................................................. 1-40
2. INSTALLATION 2- 1 to 2- 6
2.1 Installation direction and clearances ................................................................................................ 2- 2
2.2 Keeping out of foreign materials ....................................................................................................... 2- 4
2.3 Encoder cable stress ........................................................................................................................ 2- 4
2.4 Inspection items ................................................................................................................................ 2- 5
2.5 Parts having service lives ................................................................................................................. 2- 6
3. SIGNALS AND WIRING 3- 1 to 3-76
3.1 Input power supply circuit ................................................................................................................. 3- 2
3.1.1 200 V class ................................................................................................................................. 3- 3
3.1.2 400 V class ................................................................................................................................. 3- 8
3.1.3 100 V class ................................................................................................................................ 3-11
3.2 I/O signal connection example ......................................................................................................... 3-12
3.2.1 Position control mode ................................................................................................................ 3-12
3.2.2 Speed control mode .................................................................................................................. 3-15
3.2.3 Torque control mode ................................................................................................................. 3-18
3.3 Explanation of power supply system ............................................................................................... 3-21
3.3.1 Signal explanations ................................................................................................................... 3-21
3.3.2 Power-on sequence .................................................................................................................. 3-22
3.3.3 Wiring CNP1, CNP2, and CNP3 ............................................................................................... 3-23
3.4 Connectors and pin assignment ...................................................................................................... 3-27
3.5 Signal (device) explanations ............................................................................................................ 3-30
3.6 Detailed explanation of signals ........................................................................................................ 3-40
3.6.1 Position control mode ................................................................................................................ 3-40
3.6.2 Speed control mode .................................................................................................................. 3-45
3.6.3 Torque control mode ................................................................................................................. 3-47
3.6.4 Position/speed control switching mode ..................................................................................... 3-50
3.6.5 Speed/torque control switching mode ....................................................................................... 3-52
3.6.6 Torque/position control switching mode.................................................................................... 3-54
3.7 Forced stop deceleration function ................................................................................................... 3-55
3.7.1 Forced stop deceleration function ............................................................................................. 3-55
3.7.2 Base circuit shut-off delay time function ................................................................................... 3-57
3.7.3 Vertical axis freefall prevention function ................................................................................... 3-58
1
3.7.4 Residual risks of the forced stop function (EM2) ...................................................................... 3-58
3.8 Alarm occurrence timing chart ......................................................................................................... 3-59
3.8.1 When you use the forced stop deceleration function ................................................................ 3-59
3.8.2 When you do not use the forced stop deceleration function ..................................................... 3-60
3.9 Interfaces ......................................................................................................................................... 3-61
3.9.1 Internal connection diagram ...................................................................................................... 3-61
3.9.2 Detailed explanation of interfaces ............................................................................................. 3-63
3.9.3 Source I/O interfaces ................................................................................................................ 3-67
3.10 Servo motor with an electromagnetic brake .................................................................................. 3-69
3.10.1 Safety precautions .................................................................................................................. 3-69
3.10.2 Timing chart ............................................................................................................................ 3-71
3.11 Grounding ...................................................................................................................................... 3-75
4. STARTUP 4- 1 to 4-44
4.1 Switching power on for the first time ................................................................................................. 4- 2
4.1.1 Startup procedure ...................................................................................................................... 4- 2
4.1.2 Wiring check ............................................................................................................................... 4- 3
4.1.3 Surrounding environment ........................................................................................................... 4- 6
4.2 Startup in position control mode ....................................................................................................... 4- 6
4.2.1 Power on and off procedures ..................................................................................................... 4- 6
4.2.2 Stop ............................................................................................................................................ 4- 7
4.2.3 Test operation ............................................................................................................................ 4- 8
4.2.4 Parameter setting ....................................................................................................................... 4- 9
4.2.5 Actual operation ......................................................................................................................... 4- 9
4.2.6 Trouble at start-up ...................................................................................................................... 4- 9
4.3 Startup in speed control mode ......................................................................................................... 4-12
4.3.1 Power on and off procedures .................................................................................................... 4-12
4.3.2 Stop ........................................................................................................................................... 4-13
4.3.3 Test operation ........................................................................................................................... 4-14
4.3.4 Parameter setting ...................................................................................................................... 4-15
4.3.5 Actual operation ........................................................................................................................ 4-15
4.3.6 Trouble at start-up ..................................................................................................................... 4-15
4.4 Startup in torque control mode ........................................................................................................ 4-17
4.4.1 Power on and off procedures .................................................................................................... 4-17
4.4.2 Stop ........................................................................................................................................... 4-17
4.4.3 Test operation ........................................................................................................................... 4-18
4.4.4 Parameter setting ...................................................................................................................... 4-19
4.4.5 Actual operation ........................................................................................................................ 4-19
4.4.6 Trouble at start-up ..................................................................................................................... 4-20
4.5 Display and operation sections ........................................................................................................ 4-21
4.5.1 Summary .................................................................................................................
.................. 4-21
4.5.2 Display flowchart ....................................................................................................................... 4-22
4.5.3 Status display mode .................................................................................................................. 4-23
4.5.4 Diagnostic mode ....................................................................................................................... 4-30
4.5.5 Alarm mode ............................................................................................................................... 4-32
4.5.6 Parameter mode ....................................................................................................................... 4-33
4.5.7 External I/O signal display ......................................................................................................... 4-35
4.5.8 Output signal (DO) forced output .............................................................................................. 4-38
4.5.9 Test operation mode ................................................................................................................. 4-39
2
5. PARAMETERS 5- 1 to 5-66
5.1 Parameter list .................................................................................................................................... 5- 2
5.1.1 Basic setting parameters ([Pr. PA_ _ ]) ...................................................................................... 5- 2
5.1.2 Gain/filter setting parameters ([Pr. PB_ _ ]) ............................................................................... 5- 3
5.1.3 Extension setting parameters ([Pr. PC_ _ ]) .............................................................................. 5- 5
5.1.4 I/O setting parameters ([Pr. PD_ _ ]) ......................................................................................... 5- 7
5.1.5 Extension setting 2 parameters ([Pr. PE_ _ ]) ............................................................................ 5- 8
5.1.6 Extension setting 3 parameters ([Pr. PF_ _ ]) ........................................................................... 5-10
5.1.7 Linear servo motor/DD motor setting parameters ([Pr. PL_ _ ]) ............................................... 5-11
5.2 Detailed list of parameters ............................................................................................................... 5-12
5.2.1 Basic setting parameters ([Pr. PA_ _ ]) ..................................................................................... 5-12
5.2.2 Gain/filter setting parameters ([Pr. PB_ _ ]) .............................................................................. 5-25
5.2.3 Extension setting parameters ([Pr. PC_ _ ]) ............................................................................. 5-37
5.2.4 I/O setting parameters ([Pr. PD_ _ ]) ........................................................................................ 5-51
5.2.5 Extension setting 2 parameters ([Pr. PE_ _ ]) ........................................................................... 5-59
5.2.6 Extension setting 3 parameters ([Pr. PF_ _ ]) ........................................................................... 5-62
5.2.7 Linear servo motor/DD motor setting parameters ([Pr. PL_ _ ]) ............................................... 5-64
6. NORMAL GAIN ADJUSTMENT 6- 1 to 6-24
6.1 Different adjustment methods ........................................................................................................... 6- 1
6.1.1 Adjustment on a single servo amplifier ...................................................................................... 6- 1
6.1.2 Adjustment using MR Configurator2 .......................................................................................... 6- 2
6.2 One-touch tuning .............................................................................................................................. 6- 3
6.2.1 One-touch tuning flowchart ........................................................................................................ 6- 3
6.2.2 Display transition and operation procedure of one-touch tuning ............................................... 6- 5
6.2.3 Caution for one-touch tuning ..................................................................................................... 6-13
6.3 Auto tuning ....................................................................................................................................... 6-14
6.3.1 Auto tuning mode ...................................................................................................................... 6-14
6.3.2 Auto tuning mode basis ............................................................................................................. 6-15
6.3.3 Adjustment procedure by auto tuning ....................................................................................... 6-16
6.3.4 Response level setting in auto tuning mode ............................................................................. 6-17
6.4 Manual mode ................................................................................................................................... 6-18
6.5 2 gain adjustment mode .................................................................................................................. 6-21
7. SPECIAL ADJUSTMENT FUNCTIONS 7- 1 to 7-38
7.1 Filter setting ...................................................................................................................................... 7- 1
7.1.1 Machine resonance suppression filter ....................................................................................... 7- 2
7.1.2 Adaptive filter II ........................................................................................................................... 7- 5
7.1.3 Shaft resonance suppression filter ............................................................................................. 7- 7
7.1.4 Low-pass filter ............................................................................................................................ 7- 8
7.1.5 Advanced vibration suppression control II ................................................................................. 7- 8
7.1.6 Command notch filter ................................................................................................................ 7-13
7.2 Gain switching function .................................................................................................................... 7-15
7.2.1 Applications ............................................................................................................................... 7-15
7.2.2 Function block diagram ............................................................................................................. 7-16
7.2.3 Parameter .................................................................................................................................. 7-17
7.2.4 Gain switching procedure ......................................................................................................... 7-20
7.3 Tough drive function ........................................................................................................................ 7-24
3
7.3.1 Vibration tough drive function.................................................................................................... 7-24
7.3.2 Instantaneous power failure tough drive function ..................................................................... 7-26
7.4 Compliance with SEMI-F47 standard .............................................................................................. 7-30
7.5 Model adaptive control disabled ...................................................................................................... 7-33
7.6 Lost motion compensation function ................................................................................................. 7-34
7.7 Super trace control .......................................................................................................................... 7-37
8. TROUBLESHOOTING 8- 1 to 8- 8
8.1 Explanation for the lists ..................................................................................................................... 8- 1
8.2 Alarm list ........................................................................................................................................... 8- 2
8.3 Warning list ....................................................................................................................................... 8- 7
9. OUTLINE DRAWINGS 9- 1 to 9-22
9.1 Servo amplifier .................................................................................................................................. 9- 1
9.2 Connector ........................................................................................................................................ 9-20
10. CHARACTERISTICS 10- 1 to 10-14
10.1 Overload protection characteristics .............................................................................................. 10- 1
10.2 Power supply capacity and generated loss .................................................................................. 10- 5
10.3 Dynamic brake characteristics ...................................................................................................... 10- 8
10.3.1 Dynamic brake operation ....................................................................................................... 10- 8
10.3.2 Permissible load to motor inertia when the dynamic brake is used ...................................... 10-11
10.4 Cable bending life ........................................................................................................................ 10-12
10.5 Inrush currents at power-on of main circuit and control circuit .................................................... 10-13
11. OPTIONS AND AUXILIARY EQUIPMENT 11- 1 to 11-116
11.1 Cable/connector sets .................................................................................................................... 11- 1
11.1.1 Combinations of cable/connector sets ................................................................................... 11- 2
11.1.2 MR-D05UDL3M-B STO cable ................................................................................................ 11- 6
11.1.3 Battery cable/junction battery cable ....................................................................................... 11- 7
11.2 Regenerative options .................................................................................................................... 11- 8
11.2.1 Combination and regenerative power .................................................................................... 11- 8
11.2.2 Selection of regenerative option ........................................................................................... 11-10
11.2.3 Parameter setting .................................................................................................................. 11-13
11.2.4 Connection of regenerative option ........................................................................................ 11-13
11.2.5 Dimensions ........................................................................................................................... 11-18
11.3 FR-BU2-(H) Brake unit ................................................................................................................ 11-22
11.3.1 Selection................................................................................................................................ 11-23
11.3.2 Brake unit parameter setting ................................................................................................. 11-23
11.3.3 Connection example ............................................................................................................. 11-24
11.3.4 Dimensions ........................................................................................................................... 11-34
11.4 FR-RC-(H) power regeneration converter ................................................................................... 11-36
11.5 FR-CV-(H) power regeneration common converter .................................................................... 11-42
11.5.1 Model designation ................................................................................................................. 11-42
11.5.2 Selection example ................................................................................................................. 11-43
11.6 Junction terminal block MR-TB50 ................................................................................................ 11-51
11.7 MR Configurator2 ........................................................................................................................ 11-54
4
11.7.1 Specifications ........................................................................................................................ 11-54
11.7.2 System configuration ............................................................................................................. 11-55
11.7.3 Precautions for using USB communication function ............................................................. 11-56
11.8 Battery .......................................................................................................................................... 11-57
11.8.1 Selection of battery ............................................................................................................... 11-57
11.8.2 MR-BAT6V1SET battery ....................................................................................................... 11-58
11.8.3 MR-BAT6V1BJ battery for junction battery cable ................................................................. 11-62
11.8.4 MR-BAT6V1SET-A battery ................................................................................................... 11-66
11.8.5 MR-BT6VCASE battery case ................................................................................................ 11-70
11.8.6 MR-BAT6V1 battery .............................................................................................................. 11-76
11.9 Selection example of wires .......................................................................................................... 11-77
11.10 Molded-case circuit breakers, fuses, magnetic contactors ......................................................... 11-81
11.11 Power factor improving DC reactors ........................................................................................... 11-83
11.12 Power factor improving AC reactors ........................................................................................... 11-87
11.13 Relays (recommended) .............................................................................................................. 11-90
11.14 Noise reduction techniques ........................................................................................................ 11-91
11.15 Earth-leakage current breaker .................................................................................................... 11-98
11.16 EMC filter (recommended) ........................................................................................................ 11-101
11.17 External dynamic brake ............................................................................................................ 11-105
11.18 Heat sink outside mounting attachment (MR-J4ACN15K/MR-J3ACN) .................................... 11-112
12. ABSOLUTE POSITION DETECTION SYSTEM 12- 1 to 12-30
12.1 Summary ....................................................................................................................................... 12- 1
12.1.1 Features ................................................................................................................................. 12- 1
12.1.2 Restrictions ............................................................................................................................ 12- 2
12.1.3 Structure ................................................................................................................................. 12- 2
12.1.4 Parameter setting ................................................................................................................... 12- 3
12.1.5 Confirmation of absolute position detection data ................................................................... 12- 3
12.2 Battery ........................................................................................................................................... 12- 4
12.2.1 Using MR-BAT6V1SET battery or MR-BAT6V1SET-A battery ............................................. 12- 4
12.2.2 Using MR-BAT6V1BJ battery for junction battery cable ........................................................ 12- 5
12.2.3 Using MR-BT6VCASE battery case ....................................................................................... 12- 6
12.3 Standard connection example ...................................................................................................... 12- 7
12.4 Signal explanation ........................................................................................................................ 12- 8
12.5 Startup procedure ......................................................................................................................... 12- 9
12.6 Absolute position data transfer protocol ...................................................................................... 12-10
12.6.1 Data transfer procedure ........................................................................................................ 12-10
12.6.2 Transfer method .................................................................................................................... 12-11
12.6.3 Home position setting ............................................................................................................ 12-20
12.6.4 Use of servo motor with an electromagnetic brake............................................................... 12-22
12.6.5 How to process the absolute position data at detection of stroke end ................................. 12-23
12.7 Absolute position data transfer errors .......................................................................................... 12-23
12.8 Communication-based absolute position transfer system ........................................................... 12-26
12.8.1 Serial communication command ........................................................................................... 12-26
12.8.2 Absolute position data transfer protocol ............................................................................... 12-26
13. USING STO FUNCTION 13- 1 to 13-12
13.1 Introduction ................................................................................................................................... 13- 1
13.1.1 Summary ................................................................................................................................ 13- 1
5
13.1.2 Terms related to safety .......................................................................................................... 13- 1
13.1.3 Cautions ................................................................................................................................. 13- 1
13.1.4 Residual risks of the STO function ......................................................................................... 13- 2
13.1.5 Specifications ......................................................................................................................... 13- 3
13.1.6 Maintenance ........................................................................................................................... 13- 4
13.2 STO I/O signal connector (CN8) and signal layouts ..................................................................... 13- 4
13.2.1 Signal layouts ......................................................................................................................... 13- 4
13.2.2 Signal (device) explanations .................................................................................................. 13- 5
13.2.3 How to pull out the STO cable ............................................................................................... 13- 5
13.3 Connection example ..................................................................................................................... 13- 6
13.3.1 Connection example for CN8 connector ................................................................................ 13- 6
13.3.2 External I/O signal connection example using an MR-J3-D05 safety logic unit .................... 13- 7
13.3.3 External I/O signal connection example using an external safety relay unit ......................... 13- 9
13.4 Detailed description of interfaces ................................................................................................ 13-10
13.4.1 Sink I/O interface ................................................................................................................... 13-10
13.4.2 Source I/O interface .............................................................................................................. 13-11
14. COMMUNICATION FUNCTION (MITSUBISHI GENERAL-PURPOSE AC SERVO PROTOCOL)
14- 1 to 14-38
14.1 Structure ....................................................................................................................................... 14- 1
14.1.1 Configuration diagram ............................................................................................................ 14- 1
14.1.2 Precautions for using RS-422/RS-232C/USB communication function ................................ 14- 3
14.2 Communication specifications ...................................................................................................... 14- 4
14.2.1 Outline of communication ...................................................................................................... 14- 4
14.2.2 Parameter setting ................................................................................................................... 14- 4
14.3 Protocol ......................................................................................................................................... 14- 5
14.3.1 Transmission data configuration ............................................................................................ 14- 5
14.3.2 Character codes ..................................................................................................................... 14- 6
14.3.3 Error codes ............................................................................................................................. 14- 7
14.3.4 Checksum .............................................................................................................................. 14- 7
14.3.5 Time-out processing............................................................................................................... 14- 7
14.3.6 Retry processing .................................................................................................................... 14- 8
14.3.7 Initialization ............................................................................................................................ 14- 8
14.3.8 Communication procedure example ...................................................................................... 14- 9
14.4 Command and data No. list ......................................................................................................... 14-10
14.4.1 Reading command ................................................................................................................ 14-10
14.4.2 Writing commands ................................................................................................................ 14-16
14.5 Detailed explanations of commands ............................................................................................ 14-18
14.5.1 Data processing .................................................................................................................... 14-18
14.5.2 Status display mode .............................................................................................................. 14-20
14.5.3 Parameter ............................................................................................................................. 14-21
14.5.4 External I/O signal status (DIO diagnosis) ............................................................................ 14-25
14.5.5 Input device on/off ................................................................................................................. 14-28
14.5.6 Disabling/enabling I/O devices (DIO) .................................................................................... 14-29
14.5.7 Input devices on/off (test operation) ...................................................................................... 14-30
14.5.8 Test operation mode ............................................................................................................. 14-31
14.5.9 Output signal pin on/off (output signal (DO) forced output) .................................................. 14-35
14.5.10 Alarm history ....................................................................................................................... 14-36
14.5.11 Current alarm ...................................................................................................................... 14-37
14.5.12 Other commands................................................................................................................. 14-38
6
15. USING A LINEAR SERVO MOTOR 15- 1 to 15-30
15.1 Functions and configuration ......................................................................................................... 15- 1
15.1.1 Summary ................................................................................................................................ 15- 1
15.1.2 Configuration including peripheral equipment ....................................................................... 15- 2
15.2 Signals and wiring ......................................................................................................................... 15- 6
15.3 Operation and functions ................................................................................................................ 15- 7
15.3.1 Startup .................................................................................................................................... 15- 7
15.3.2 Magnetic pole detection ........................................................................................................ 15-11
15.3.3 Home position return ............................................................................................................. 15-18
15.3.4 Test operation mode in MR Configurator2 ............................................................................ 15-22
15.3.5 Function................................................................................................................................. 15-23
15.3.6 Absolute position detection system ....................................................................................... 15-26
15.4 Characteristics ............................................................................................................................. 15-27
15.4.1 Overload protection characteristics ...................................................................................... 15-27
15.4.2 Power supply capacity and generated loss .......................................................................... 15-28
15.4.3 Dynamic brake characteristics .............................................................................................. 15-29
15.4.4 Permissible load to motor mass ratio when the dynamic brake is used ............................... 15-30
16. USING A DIRECT DRIVE MOTOR 16- 1 to 16-20
16.1 Functions and configuration ......................................................................................................... 16- 1
16.1.1 Summary ................................................................................................................................ 16- 1
16.1.2 Configuration including peripheral equipment ....................................................................... 16- 2
16.2 Signals and wiring ......................................................................................................................... 16- 3
16.3 Operation and functions ................................................................................................................ 16- 4
16.3.1 Startup procedure .................................................................................................................. 16- 5
16.3.2 Magnetic pole detection ......................................................................................................... 16- 6
16.3.3 Function................................................................................................................................. 16-12
16.4 Absolute position detection system ............................................................................................. 16-14
16.5 Characteristics ............................................................................................................................. 16-15
16.5.1 Overload protection characteristics ...................................................................................... 16-15
16.5.2 Power supply capacity and generated loss .......................................................................... 16-17
16.5.3 Dynamic brake characteristics .............................................................................................. 16-18
17. FULLY CLOSED LOOP SYSTEM 17- 1 to 17-24
17.1 Functions and configuration ......................................................................................................... 17- 2
17.1.1 Function block diagram .......................................................................................................... 17- 2
17.1.2 Selecting procedure of control mode ..................................................................................... 17- 3
17.1.3 System configuration .............................................................................................................. 17- 4
17.2 Load-side encoder ........................................................................................................................ 17- 6
17.2.1 Linear encoder ....................................................................................................................... 17- 6
17.2.2 Rotary encoder ....................................................................................................................... 17- 6
17.2.3 Configuration diagram of encoder cable ................................................................................ 17- 7
17.2.4 MR-J4FCCBL03M branch cable ............................................................................................ 17- 9
17.3 Operation and functions ............................................................................................................... 17-10
17.3.1 Startup ................................................................................................................................... 17-10
17.3.2 Home position return ............................................................................................................. 17-17
17.3.3 Fully closed loop control error detection functions................................................................ 17-19
17.3.4 Auto tuning function .............................................................................................................. 17-20
7
17.3.5 Machine analyzer function .................................................................................................... 17-20
17.3.6 Test operation mode ............................................................................................................. 17-20
17.3.7 Absolute position detection system under fully closed loop system ..................................... 17-21
17.3.8 About MR Configurator2 ....................................................................................................... 17-22
18. MR-J4-03A6 SERVO AMPLIFIER 18- 1 to 18-84
18.1 Functions and configuration ......................................................................................................... 18- 1
18.1.1 Summary ................................................................................................................................ 18- 1
18.1.2 Function block diagram .......................................................................................................... 18- 2
18.1 3 Servo amplifier standard specifications ................................................................................. 18- 3
18.1.4 Combinations of servo amplifiers and servo motors .............................................................. 18- 4
18.1.5 Function list ............................................................................................................................ 18- 5
18.1.6 Model definition ...................................................................................................................... 18- 8
18.1.7 Parts identification .................................................................................................................. 18- 9
18.1.8 Configuration including peripheral equipment ...................................................................... 18-10
18.2 Installation .................................................................................................................................... 18-11
18.2.1 Installation direction and clearances ..................................................................................... 18-12
18.2.2 Installation by DIN rail ........................................................................................................... 18-14
18.3 Signals and wiring ........................................................................................................................ 18-16
18.3.1 Input power supply circuit ..................................................................................................... 18-17
18.3.2 Explanation of power supply system ..................................................................................... 18-19
18.3.3 Selection of main circuit power supply/control circuit power supply ..................................... 18-22
18.3.4 Power-on sequence .............................................................................................................. 18-22
18.3.5 I/O signal connection example .............................................................................................. 18-23
18.3.6 Connectors and pin assignment ........................................................................................... 18-31
18.3.7 Signal (device) explanations ................................................................................................. 18-34
18.3.8 Alarm occurrence timing chart .............................................................................................. 18-38
18.3.9 Interfaces (Internal connection diagram) .............................................................................. 18-40
18.3.10 Grounding ........................................................................................................................... 18-42
18.4 Startup ......................................................................................................................................... 18-43
18.4.1 Startup procedure ................................................................................................................. 18-44
18.4.2 Troubleshooting when "24 V ERROR" lamp turns on ........................................................... 18-45
18.4.3 Wiring check .......................................................................................................................... 18-46
18.4.4 Surrounding environment ...................................................................................................... 18-47
18.5 Display and operation sections .................................................................................................... 18-47
18.5.1 Summary ............................................................................................................................... 18-47
18.5.2 Display flowchart ................................................................................................................... 18-48
18.5.3 Status display mode .............................................................................................................. 18-49
18.5.4 One-touch tuning ................................................................................................................... 18-54
18.5.5 Diagnostic mode ................................................................................................................... 18-58
18.5.6 Alarm mode ........................................................................................................................... 18-61
18.5.7 Parameter mode ................................................................................................................... 18-63
18.5.8 External I/O signal display..................................................................................................... 18-68
18.5.9 Output signal (DO) forced output .......................................................................................... 18-71
18.5.10 Test operation mode ........................................................................................................... 18-72
18.6 Dimensions .................................................................................................................................. 18-74
18.7 Characteristics ............................................................................................................................. 18-75
18.7.1 Overload protection characteristics ...................................................................................... 18-75
18.7.2 Power supply capacity and generated loss .......................................................................... 18-76
18.7.3 Dynamic brake characteristics .............................................................................................. 18-76
8
18.7.4 Inrush currents at power-on of main circuit and control circuit ............................................. 18-78
18.8 Options and peripheral equipment .............................................................................................. 18-79
18.8.1 Cable/connector sets ............................................................................................................ 18-79
18.8.2 Combinations of cable/connector sets .................................................................................. 18-80
18.8.3 Selection example of wires ................................................................................................... 18-81
18.8.4 Circuit protector ..................................................................................................................... 18-81
18.9 Mitsubishi general-purpose AC servo protocol communication function .................................... 18-82
APPENDIX App.- 1 to App.-52
App. 1 Peripheral equipment manufacturer (for reference) .............................................................. App.- 1
App. 2 Handling of AC servo amplifier batteries for the United Nations Recommendations on the
Transport of Dangerous Goods ............................................................................................ App.- 1
App. 3 Symbol for the new EU Battery Directive .............................................................................. App.- 3
App. 4 Compliance with global standards ........................................................................................ App.- 4
App. 5 MR-J3-D05 Safety logic unit ................................................................................................ App.-19
App. 6 EC declaration of conformity ................................................................................................ App.-37
App. 7 Analog monitor ..................................................................................................................... App.-39
App. 8 Two-wire type encoder cable for HG-MR/HG-KR ................................................................ App.-46
App. 9 How to replace servo amplifier without magnetic pole detection ......................................... App.-47
App. 10 Special specification ............................................................................................................. App.-49
App. 11 Driving on/off of main circuit power supply with DC power supply ....................................... App.-51
9
MEMO
10

1. FUNCTIONS AND CONFIGURATION

1. FUNCTIONS AND CONFIGURATION
POINT
In MELSERVO-J4 series, ultra-small capacity servo amplifiers compatible with 48 V DC and 24 V DC power supplies are available as MRJ4-03A6. Refer to chapter 18 for details of MR-J4-03A6 servo amplifiers.

1.1 Summary

The Mitsubishi MELSERVO-J4 series general-purpose AC servo has further higher performance and higher functions compared to the previous MELSERVO-J3 series. The MELSERVO-J4 series compatible rotary servo motor is equipped with 22-bit (4194304 pulses/rev) high­resolution absolute encoder. In addition, speed frequency response is increased to 2.5 kHz. Thus, faster and more accurate control is enabled as compared to the MELSERVO-J3 series. The servo amplifier has position, speed, and torque control modes. In the position control mode, the maximum pulse train of 4 Mpulses/s is supported. Further, it can perform operation with the control modes switched, e.g. position/speed control, speed/torque control and torque/position control. Hence, it is applicable to a wide range of fields, not only precision positioning and smooth speed control of machine tools and general industrial machines but also line control and tension control. With one-touch tuning and real-time auto tuning, you can automatically adjust the servo gains according to the machine. The tough drive function and the drive recorder function, which are well-received in the MELSERVO-JN series, have been improved. The MR-J4 servo amplifier supports the improved functions. Additionally, the preventive maintenance support function detects an error in the machine parts. This function provides strong support for the machine maintenance and inspection. The MR-J4-_A_ servo amplifier supports the Safe Torque Off (STO) function. By combining with optional MR-J3-D05, the servo amplifier supports Safe stop 1 (SS1) function. The servo amplifier has a USB communication interface. Therefore, you can connect the servo amplifier to the personal computer with MR Configurator2 installed to perform the parameter setting, test operation, gain adjustment, and others. In the MELSERVO-J4 series, servo amplifiers with the CN2L connector are also available as MR-J4-_A_-RJ. By using the CN2L connector, an A/B/Z-phase differential output method external encoder can be connected to the servo amplifier. In a fully closed loop system, a four-wire type external encoder is connectable as well. The following table indicates the communication method of the external encoder compatible with the MR-J4­_A_ and MR-J4-_A_-RJ servo amplifiers.
1 - 1
1. FUNCTIONS AND CONFIGURATION
Table 1.1 Connectors to connect from external encoders
Operation
mode
Linear servo motor system
Fully closed loop system
Note 1. The MR-J4THCBL03M branch cable is necessary.
2. The MR-J4FCCBL03M branch cable is necessary.
3. When the communication method of the servo motor encoder is four-wire type, MR-J4-_A_ cannot be used. Use an MR-J4-_A_-RJ.
4. This is used with software version A5 or later.
5. Connect a thermistor to CN2.
External encoder
communication
method
Two-wire type
Four-wire type
A/B/Z-phase
differential output
method
Two-wire type
Four-wire type
A/B/Z-phase
differential output
method
Connector
MR-J4-_A_ MR-J4-_A_-RJ
CN2
(Note 1, 4)
CN2
(Note 2, 3, 4)
CN2
(Note 1)
CN2L
(Note 5)
CN2L
1 - 2
1. FUNCTIONS AND CONFIGURATION

1.2 Function block diagram

The function block diagram of this servo is shown below.
Regenerative
option
(1) 200 V class
(a) MR-J4-500A(-RJ) or less
POINT
The diagram shows MR-J4-_A_-RJ as an example. The MR-J4-_A_ servo amplifier does not have the CN2L connector.
(Note 6)
Power factor improving
DC reactor
(Note 2) Power supply
STO
switch
Servo amplifier
MCMCCB
L1
U
L2
U U
L3
L11
L21
CN8
P3 P4
Diode
stack
Position
command
input
+
(Note 4)
Relay
Cooling fan
(Note 3)
Control
circuit
power
Model
position
control
+
CHARGE
lamp
STO
circuit
Base
amplifier
P+
(Note 1)
Regene-
rative
Model speed
control
TR
Voltage
detection
N-CD
Overcurrent
protection
Virtual
motor
detection
Virtual
encoder
Dynamic
brake circuit
Current
encoder
Current
Step­down
circuit
U
V
W
RA
24 V DC
CN2
Servo motor
U
V
W
B1
B
B2
M
Electromagnetic brake
Encoder
Model position
Actual
position
control
I/F
CN1
DI/O control
Analog
(two channel)
Servo-on Input command pulse. Start Malfunction, etc
Model speed Model torque
Actual speed
control
USB
CN5 CN3 CN6
Personal
computer
USB
Controller
RS-422/
RS-485
Current
control
RS-422/
RS-485
D/AA/D
Analog monitor
(two channel)
CN4
Battery (for absolute position detection system)
External encoder
CN2L
(Note 5)
1 - 3
1. FUNCTIONS AND CONFIGURATION
Note 1. The built-in regenerative resistor is not provided for MR-J4-10A(-RJ).
2. For 1-phase 200 V AC to 240 V AC, connect the power supply to L1 and L3. Leave L2 open. For the power supply specifications, refer to section 1.3.
3. Servo amplifiers MR-J4-70A(-RJ) or more have a cooling fan.
4. The MR-J4 servo amplifier has P3 and P4 in the upstream of the inrush current suppression circuit. They are different from P1 and P2 of the MR-J3 servo amplifiers.
5. This is for the MR-J4-_A-RJ servo amplifier. The MR-J4-_A servo amplifier does not have the CN2L connector.
6. The power factor improving AC reactor can also be used. In this case, the power factor improving DC reactor cannot be used. When not using the power factor improving DC reactor, short P3 and P4.
1 - 4
1. FUNCTIONS AND CONFIGURATION
(b) MR-J4-700A(-RJ)
(Note 4)
Power factor improving
DC reactor
Regenerative
option
(Note 1) Power supply
STO
switch
Servo amplifier
MCMCCB
L1
U
L2
U U
L3
L11
L21
CN8
P3 P4
Diode
stack
Position
command
input
+
(Note 2)
Relay
Cooling fan
Control
circuit
power
Model
position
control
+
CHARGE
lamp
STO
circuit
Base
amplifier
P+
Regene-
rative
TR
Model speed
control
Voltage
detection
N-C
Overcurrent
Virtual
motor
protection
detection
Virtual
encoder
Dynamic
brake circuit
Current
encoder
Current
Step­down
circuit
U
V
W
RA
24 V DC
CN2
Servo motor
U
V
W
B1
B
B2
M
Electromagnetic brake
Encoder
Model position Model speed Model torque
Actual
position
control
Actual speed
control
Current
control
CN4
Battery (for absolute position detection system)
External encoder
CN2L
(Note 3)
RS-422/
RS-485
Controller
RS-422/
RS-485
D/AA/D
Analog monitor
(two channel)
Analog
(two channel)
I/F
CN1
DI/O control
Servo-on Input command pulse. Start Malfunction, etc
USB
CN5 CN3 CN6
Personal computer
USB
Note 1. For the power supply specifications, refer to section 1.3.
2. The MR-J4 servo amplifier has P3 and P4 in the upstream of the inrush current suppression circuit. They are different from P1 and P2 of MR-J3 servo amplifiers.
3. This is for the MR-J4-_A-RJ servo amplifier. The MR-J4-_A servo amplifier does not have the CN2L connector.
4. The power factor improving AC reactor can also be used. In this case, the power factor improving DC reactor cannot be used. When not using the power factor improving DC reactor, short P3 and P4.
1 - 5
1. FUNCTIONS AND CONFIGURATION
(c) MR-J4-11KA(-RJ)/MR-J4-15KA(-RJ)/MR-J4-22KA(-RJ)
External regenerative
regenerative option
(Note 2)
Thyristor
+
CHARGE
lamp
STO
circuit
Base
amplifier
resistor or
Regene-
rative
TR
detection
Voltage
(Note 1) Power supply
STO
switch
Servo amplifier
MCMCCB
L1
U
L2
U U
L3
L11
L21
CN8
(Note 5)
Power factor improving
DC reactor
P3 P+
Diode
stack
P4
Cooling fan
Control
+
circuit
power
(Note 4, 6)
External dynamic
brake (optional)
RA
Servo motor
U
V
M
W
B1
Electromagnetic
B
brake
N-
C
U
Current
encoder
V
W
24 V DC
B2
Overcurrent
protection
Current
detection
CN2
Encoder
Current
control
Virtual
encoder
Step­down
circuit
CN4
Battery (for absolute position detection system)
External encoder
CN2L
Position
command
input
Model
position
control
Model position
Actual
position
control
Model speed
control
Virtual
motor
Model speed Model torque
Actual speed
control
(Note 3)
RS-422/
RS-485
Controller
RS-422/
RS-485
D/AA/D
Analog monitor
(two channel)
Analog
(two channel)
I/F
CN1
DI/O control
Servo-on Input command pulse. Start Malfunction, etc
USB
CN5 CN3 CN6
Personal
computer
USB
Note 1. For the power supply specifications, refer to section 1.3.
2. The MR-J4 servo amplifier has P3 and P4 in the upstream of the inrush current suppression circuit. They are different from P1 and P2 of the MR-J3 servo amplifiers.
3. This is for the MR-J4-_A-RJ servo amplifier. The MR-J4-_A servo amplifier does not have the CN2L connector.
4. Use an external dynamic brake for this servo amplifier. Failure to do so will cause an accident because the servo motor dose not stop immediately but coasts at an alarm occurrence for which the servo motor does not decelerate to stop. Ensure the safety in the entire equipment. For alarms for which the servo motor does not decelerate to stop, refer to chapter 8.
5. The power factor improving AC reactor can also be used. In this case, the power factor improving DC reactor cannot be used. When not using the power factor improving DC reactor, short P3 and P4.
6. The external dynamic brake cannot be used for compliance with SEMI-F47 standard. Do not assign DB (Dynamic brake interlock) in [Pr. PD23] to [Pr. PD26], [Pr. PD28], and [Pr. PD47]. Failure to do so will cause the servo amplifier to become servo-off when an instantaneous power failure occurs.
1 - 6
1. FUNCTIONS AND CONFIGURATION
(2) 400 V class
(a) MR-J4-350A4(-RJ) or less
(Note 5)
Power factor
improving
DC reactor
Regenerative
option
(Note 1) Power supply
STO
switch
Servo amplifier
MCMCCB
L1
U
L2
U U
L3
L11
L21
CN8
P3 P4 (Note 3)
Diode stack
+
Position
command
input
Relay
(Note 2)
Control
circuit power
supply
Model
position
control
+
Cooling fan
STO
circuit
Base
amplifier
P+
Regene­rative TR
Charge
lamp
Model speed control
Voltage
detection
N-CD
Overcurrent
protection
Virtual
motor
detection
Virtual
encoder
Dynamic
brake
circuit
Current
detector
Current
Step­down circuit
U
V
W
RA
24 V DC
CN2
Servo motor
U
V
W
B1
B
B2
M
Electromagnetic brake
Encoder
CN4
Battery (For absolute position detection system)
External encoder CN2L (Note 4)
Analog
(2 channels)
Model position
Actual
position
control
I/F
CN1
DI/O control
•Servo-on
•Input command pulse.
•Start
•Malfunction, etc
Model speed Model torque
Actual speed control
USB
CN5 CN3 CN6
Personal
computer
USB
Controller
RS-422/
RS-485
Current
control
RS-422/
RS-485
D/AA/D
Analog monitor
(2 channels)
Note 1. Refer to section 1.3 for the power supply specification.
2. Servo amplifiers MR-J4-200A4(-RJ) or more have a cooling fan.
3. MR-J4 servo amplifier has P3 and P4 in the upstream of the inrush current suppression circuit. They are different from P1 and P2 of MR-J3 servo amplifiers.
4. This is for MR-J4-_A4-RJ servo amplifier. MR-J4-_A4 servo amplifier does not have CN2L connector.
5. The power factor improving AC reactor can also be used. In this case, the power factor improving DC reactor cannot be used. When not using the power factor improving DC reactor, short P3 and P4.
1 - 7
1. FUNCTIONS AND CONFIGURATION
(b) MR-J4-500A4(-RJ)/MR-J4-700A4(-RJ)
(Note 4)
Power factor
improving
DC reactor
Regenerative
option
(Note 1) Power supply
STO
switch
Servo amplifier
MCMCCB
L1
U
L2
U U
L3
L11
L21
CN8
P3 P4 (Note 2)
Diode stack
+
Position
command
input
Relay
Control
circuit power
supply
Model
position
control
+
Cooling fan
STO
circuit
Base
amplifier
P+
Regene­rative TR
Charge
lamp
Model speed control
Voltage
detection
N-C
Overcurrent
Virtual
motor
protection
detection
Virtual
encoder
Dynamic
brake
circuit
Current
detector
Current
Step­down circuit
U
V
W
RA
24 V DC
CN2
Servo motor
U
V
W
B1
B
B2
M
Electromagnetic brake
Encoder
CN4
Battery (For absolute position detection system)
External encoder
CN2L
(Note 3)
Analog
(2 channels)
Model position
Actual
position
control
I/F
CN1
DI/O control
•Servo-on
•Input command pulse.
•Start
•Malfunction, etc
Model speed Model torque
Actual speed control
USB
CN5 CN3 CN6
Personal
computer
USB
Controller
RS-422/
RS-485
Current
control
RS-422/
RS-485
D/AA/D
Analog monitor
(2 channels)
Note 1. Refer to section 1.3 for the power supply specification.
2. MR-J4 servo amplifier has P3 and P4 in the upstream of the inrush current suppression circuit. They are different from P1 and P2 of MR-J3 servo amplifiers.
3. This is for MR-J4-_A4-RJ servo amplifier. MR-J4-_A4 servo amplifier does not have CN2L connector.
4. The power factor improving AC reactor can also be used. In this case, the power factor improving DC reactor cannot be used. When not using the power factor improving DC reactor, short P3 and P4.
1 - 8
1. FUNCTIONS AND CONFIGURATION
(c) MR-J4-11KA4(-RJ)/MR-J4-15KA4(-RJ)/MR-J4-22KA4(-RJ)
(Note 1) Power supply
STO
switch
Servo amplifier
MCMCCB
L1
U
L2
U U
L3
L11
L21
CN8
(Note 5)
Power factor
improving
DC reactor
P3 P4 (Note 2)
Diode
stack
Control
+
circuit power
supply
Thyristor
Cooling fan
External
regenerative resistor
or
regenerative option
P+
+
Regene­rative TR
Charge
lamp
STO
circuit
Base
amplifier
Voltage
detection
N-C
Overcurrent
protection
Current
detector
Current
detection
(Note 4, 6)
External
dynamic brake
(optional)
U
V
W
W
RA
24 V DC
CN2
Servo motor
U
V
M
B1
Electromagnetic
B
brake
B2
Encoder
Virtual
motor
Current
control
RS-422/
RS-485
Virtual
encoder
D/AA/D
Analog monitor
(2 channels)
Step­down circuit
CN4
Battery (For absolute position detection system)
CN2L (Note 3)
External encoder
Analog
(2 channels)
Position
command
input
Model
position
control
Actual
position
control
CN1
DI/O control
•Servo-on
•Input command pulse.
•Start
•Malfunction, etc
Model position
I/F
Model speed control
Model speed Model torque
Actual speed control
USB
CN5 CN3 CN6
Personal
computer
USB
Controller
RS-422/
RS-485
Note 1. Refer to section 1.3 for the power supply specification.
2. MR-J4 servo amplifier has P3 and P4 in the upstream of the inrush current suppression circuit. They are different from P1 and P2 of MR-J3 servo amplifiers.
3. This is for MR-J4-_A4-RJ servo amplifier. MR-J4-_A4 servo amplifier does not have CN2L connector.
4. Use an external dynamic brake for this servo amplifier. Failure to do so will cause an accident because the servo motor does not stop immediately but coasts at an alarm occurrence for which the servo motor does not decelerate to stop. Ensure the safety in the entire equipment. For alarms for which the servo motor does not decelerate to stop, refer to chapter 8.
5. The power factor improving AC reactor can also be used. In this case, the power factor improving DC reactor cannot be used. When not using the power factor improving DC reactor, short P3 and P4.
6. The external dynamic brake cannot be used for compliance with SEMI-F47 standard. Do not assign DB (Dynamic brake interlock) in [Pr. PD23] to [Pr. PD26], [Pr. PD28], and [Pr. PD47]. Failure to do so will cause the servo amplifier to become servo-off when an instantaneous power failure occurs.
1 - 9
1. FUNCTIONS AND CONFIGURATION
(3) 100 V class
Regenerative option
(Note 2) Power supply
STO
switch
Servo amplifier
MCMCCB
L1
L2
L11
L21
CN8
U
Relay
Position
command
input
Diode stack
+
Control
circuit power
Model
position
control
U
V
W
RA
Servo motor
M
B1
Electromagnetic
B
brake
B2
P+
(Note 1)
+
Charge
lamp
Regene-
+
rative TR
N-CD
Dynamic brake
circuit
Current
encoder
U
V
W
24 V DC
STO
circuit
Base
amplifier
Voltage
detection
Overcurrent
protection
Current
detection
CN2
Encoder
Model speed
control
Virtual
motor
Virtual
encoder
Step­down
circuit
Model position
Actual
position
control
Model speed Model torque
Actual
speed
control
Current
control
(Note 3)
RS-422/
RS-485
Controller
RS-422/
RS-485
D/AA/D
Analog monitor
(two channel)
Analog
(two channel)
I/F
CN1
DI/O control
•Servo-on
•Input command pulse.
•Start
•Malfunction, etc
Personal
computer
USB
USB
CN5 CN3 CN6
Note 1. The built-in regenerative resistor is not provided for MR-J4-10A1(-RJ).
2. Refer to section 1.3 for the power supply specifications.
3. This is for MR-J4-_A1-RJ servo amplifier. MR-J4-_A1 servo amplifier does not have CN2L connector.
CN4
Battery (For absolute position detection system)
External encoder
CN2L
1 - 10
1. FUNCTIONS AND CONFIGURATION

1.3 Servo amplifier standard specifications

(1) 200 V class
Model: MR-J4-_(-RJ) 10A 20A 40A 60A 70A 100A 200A 350A 500A 700A 11KA 15KA 22KA
Output
Main circuit power supply input
Control circuit power supply input
Interface power supply
Control method Sine-wave PWM control, current control method
Dynamic brake Built-in
Fully closed loop control Compatible (Note 9) Load-side encoder interface (Note 10) Mitsubishi high-speed serial communication
Communication function
Encoder output pulses Compatible (A/B/Z-phase pulse) Analog monitor Two channels
Position control mode
Speed control mode
Torque control mode
Positioning mode
Protective functions
Functional safety STO (IEC/EN 61800-5-2)
Safety performance
Rated voltage 3-phase 170 V AC Rated current [A] 1.1 1.5 2.8 3.2 5.8 6.0 11.0 17.0 28.0 37.0 68.0 87.0 126.0
Voltage/Frequency
Rated current (Note 11)
Permissible voltage fluctuation
Permissible frequency fluctuation
Power supply capacity
Inrush current [A] Refer to section 10.5. Voltage/Frequency 1-phase 200 V AC to 240 V AC, 50 Hz/60 Hz Rated current [A] 0.2 0.3 Permissible voltage
fluctuation Permissible frequency
fluctuation Power
consumption Inrush current [A] Refer to section 10.5. Voltage 24 V DC ± 10% Current capacity [A] (Note 1) 0.5 (including the CN8 connector signals)
Max. input pulse frequency
Positioning feedback pulse
Command pulse multiplying factor
In-position range setting 0 pulse to ±65535 pulses (command pulse unit) Error excessive ±3 revolutions Torque limit Set by parameter setting or external analog input (0 V DC to +10 V DC/maximum torque) Speed control range Analog speed command 1: 2000, Internal speed command 1: 5000 Analog speed command
input
Speed fluctuation ratio
Torque limit Set by parameter setting or external analog input (0 V DC to +10 V DC/maximum torque) Analog torque command
input Speed limit Set by parameter setting or external analog input (0 V DC to 10 V DC/rated speed)
Standards certified by CB
Response performance 8 ms or less (STO input off energy shut off) (Note 3) Test pulse input (STO) Mean time to dangerous
failure (MTTFd) Diagnosis coverage (DC) Medium (90% to 99%) Average probability of
dangerous failures per hour (PFH)
[A] 0.9 1.5 2.6
[kVA] Refer to section 10.2.
[W] 30 45
3-phase or 1-phase
200 V AC to 240 V AC,
50 Hz/60 Hz
3-phase or 1-phase
170 V AC to 264 V AC
USB: Connection to a personal computer or others (MR Configurator2-compatible)
4 Mpulses/s (for differential receiver) (Note 6), 200 kpulses/s (for open collector)
0 to ±10 V DC/rated speed (The speed at 10 V is changeable with [Pr. PC12].)
±0.01% or less (load fluctuation: 0% to 100%), 0% (power fluctuation: ±10%)
±0.2% or less (ambient temperature: 25 °C ± 10 °C) when using analog speed command
Refer to "MR-J4-_A_-RJ Servo Amplifier Instruction Manual (Positioning Mode)" section 1.1.
The positioning mode is used by MR-J4-_A_-RJ servo amplifier with software version B3 or later.
Overcurrent shut-off, regenerative overvoltage shut-off, overload shut-off (electronic thermal),
servo motor overheat protection, encoder error protection, regenerative error protection,
undervoltage protection, instantaneous power failure protection, overspeed protection,
error excessive protection, magnetic pole detection protection, and linear servo control fault protection
3.2
(Note 5)
RS-422/RS-485: 1:n communication (up to 32 axes) (Note 7, 13)
Encoder resolution (resolution per servo motor revolution): 22 bits
Electronic gear A:1 to 16777215, B:1 to 16777215, 1/10 < A/B < 4000
0 V DC to ±8 V DC/maximum torque (input impedance 10 k to 12 k )
EN ISO 13849-1 category 3 PL d, IEC 61508 SIL 2, EN 62061 SIL CL 2,
3.8 5.0 10.5 16.0 21.7 28.9 46.0 64.0 95.0
1-phase 170 V AC to 264 V AC
and EN 61800-5-2 SIL 2
Test pulse interval: 1 Hz to 25 Hz
Test pulse off time: Up to 1 ms
3-phase 200 V AC to 240 V AC, 50 Hz/60 Hz
3-phase 170 V AC to 264 V AC
Within ±5%
Within ±5%
100 years or longer
-10
1.68 × 10
[1/h]
External option
(Note 8, 12)
1 - 11
1. FUNCTIONS AND CONFIGURATION
Model: MR-J4-_(-RJ) 10A 20A 40A 60A 70A 100A 200A 350A 500A 700A 11KA 15KA 22KA
LVD: EN 61800-5-1
Compliance to global standards
Structure (IP rating) Natural cooling, open (IP20) Force cooling, open (IP20) Force cooling, open (IP20) (Note 4) Close mounting (Note 2) Possible Impossible
Environment
Mass [kg] 0.8 1.0 1.4 2.1 2.3 4.0 6.2 13.4 18.2
Note 1. 0.5 A is the value applicable when all I/O signals are used. The current capacity can be decreased by reducing the number of
2. When closely mounting the servo amplifier of 3.5 kW or less, operate them at the ambient temperatures of 0 ˚C to 45 ˚C or at
3. Test pulse is a signal which instantaneously turns off a signal to the servo amplifier at a constant period for external circuit to
4. Except for the terminal block.
5. The rated current is 2.9 A when the servo amplifier is used with a UL or CSA compliant servo motor.
6. 1 Mpulse/s or lower commands are supported in the initial setting. When inputting commands over 1 Mpulse/s and 4
7. RS-422 communication is supported by servo amplifier with software version A3.
8. Use an external dynamic brake for this servo amplifier. Failure to do so will cause an accident because the servo motor does
9. For the compatible version for the fully closed loop system, refer to table 1.1. Check the software version of the servo amplifier
10. The MR-J4-_A servo amplifier is compatible only with the two-wire type.
11. This value is applicable when a 3-phase power supply is used.
12. The external dynamic brake cannot be used for compliance with SEMI-F47 standard. Do not assign DB (Dynamic brake
13. RS-485 communication is available with servo amplifiers manufactured in November 2014 or later.
CE marking
UL standard UL 508C
Ambient temperature
Ambient humidity
Ambience
Altitude 1000 m or less above sea level Vibration resistance 5.9 m/s2, at 10 Hz to 55 Hz (directions of X, Y and Z axes)
Operation 0 ˚C to 55 ˚C (non-freezing) Storage -20 ˚C to 65 ˚C (non-freezing) Operation Storage
MD: EN ISO 13849-1, EN 61800-5-2, EN 62061
free from corrosive gas, flammable gas, oil mist, dust, and dirt
EMC: EN 61800-3
90 %RH or less (non-condensing)
Indoors (no direct sunlight),
I/O points.
75% or smaller effective load ratio.
self-diagnose.
Mpulses/s or lower, change the setting in [Pr. PA13].
not stop immediately but coasts at emergency stop. Ensure the safety in the entire equipment.
using MR Configurator2.
The MR-J4-_A-RJ servo amplifier is compatible with the two-wire type, four-wire type, and A/B/Z-phase differential output method. Refer to table 1.1 for details.
interlock) in [Pr. PD23] to [Pr. PD26], [Pr. PD28], and [Pr. PD47]. Failure to do so will cause the servo amplifier to become servo-off when an instantaneous power failure occurs.
1 - 12
1. FUNCTIONS AND CONFIGURATION
(2) 400 V class
Model: MR-J4-_(-RJ) 60A4 100A4 200A4 350A4 500A4 700A4 11KA4 15KA4 22KA4
Output
Main circuit power supply input
Voltage/Frequency 1-phase 380 V AC to 480 V AC, 50 Hz/60 Hz Rated current [A] 0.1 0.2
Control circuit power supply input
Power consumption [W] 30 45 Inrush current [A] Refer to section 10.5. Interface power
supply Control method Sine-wave PWM control, current control method Dynamic brake Built-in External option (Note 6, 7) Fully closed loop control Compatible Load-side encoder interface (Note 5) Mitsubishi high-speed serial communication
Communication function
Encoder output pulses Compatible (A/B/Z-phase pulse) Analog monitor Two channels
Position control mode
Speed control mode
Torque control mode
Positioning mode
Protective functions
Functional safety STO (IEC/EN 61800-5-2)
Standards certified by CB
Response performance 8 ms or less (STO input off energy shut off)
Safety performance
Rated voltage 3-phase 323 V AC Rated current [A] 1.5 2.8 5.4 8.6 14.0 17.0 32.0 41.0 63.0 Voltage/Frequency 3-phase 380 V AC to 480 V AC, 50 Hz/60 Hz Rated current [A] 1.4 2.5 5.1 7.9 10.8 14.4 23.1 31.8 47.6 Permissible voltage
fluctuation Permissible frequency
fluctuation Power supply
capacity Inrush current [A] Refer to section 10.5.
Permissible voltage fluctuation
Permissible frequency fluctuation
Voltage 24 V DC ± 10% Current capacity [A] (Note 1) 0.5 (including CN8 connector signals)
Max. input pulse frequency 4 Mpulses/s (for differential receiver) (Note 4), 200 kpulses/s (for open collector) Positioning feedback pulse Encoder resolution (resolution per servo motor revolution): 22 bits Command pulse multiplying
factor In-position range setting 0 pulse to ±65535 pulses (command pulse unit) Error excessive ±3 revolutions Torque limit Set by parameter setting or external analog input (0 V DC to +10 V DC/maximum torque) Speed control range Analog speed command 1: 2000, internal speed command 1: 5000 Analog speed command
input
Speed fluctuation ratio
Torque limit Set by parameter setting or external analog input (0 V DC to +10 V DC/maximum torque) Analog torque command
input Speed limit Set by parameter setting or external analog input (0 V DC to 10 V DC/rated speed)
(Note 2) Test pulse input (STO) Mean time to dangerous
failure (MTTFd) Diagnosis coverage (DC) Medium (90% to 99%) Average probability of
dangerous failures per hour (PFH)
[kVA] Refer to section 10.2.
USB: connection to a personal computer or others (MR Configurator2-compatible) RS-422/RS-485: 1 : n communication (up to 32 axes) (Note 8)
3-phase 323 V AC to 528 V AC
Within ±5%
1-phase 323 V AC to 528 V AC
Within ±5%
Electronic gear A:1 to 16777215, B:1 to 16777215, 1/10 < A/B < 4000
0 to ±10 V DC/rated speed (The speed at 10 V is changeable with [Pr. PC12].)
±0.01% or less (load fluctuation 0 % to 100%), 0% (power fluctuation ±10%), ±0.2% or less (ambient
Refer to "MR-J4-_A_-RJ Servo Amplifier Instruction Manual (Positioning Mode)" section 1.1.
The positioning mode is used by MR-J4-_A_-RJ servo amplifier with software version B3 or later.
Overcurrent shut-off, regenerative overvoltage shut-off, overload shut-off (electronic thermal),
servo motor overheat protection, encoder error protection, regenerative error protection,
undervoltage protection, instantaneous power failure protection, overspeed protection,
error excessive protection, magnetic pole detection protection, and linear servo control fault protection
100 years or longer
1.68 × 10
temperature 25 ± 10 °C) when using analog speed command
0 V DC to ±8 V DC/maximum torque (input impedance 10 k to 12 k )
EN ISO 13849-1 category 3 PL d, IEC 61508 SIL 2, EN 62061 SIL CL 2,
and EN 61800-5-2 SIL 2
Test pulse interval: 1 Hz to 25 Hz
Test pulse off time: Up to 1 ms
-10
[1/h]
1 - 13
1. FUNCTIONS AND CONFIGURATION
Model: MR-J4-_(-RJ) 60A4 100A4 200A4 350A4 500A4 700A4 11KA4 15KA4 22KA4
LVD: EN 61800-5-1
Compliance to standards
Structure (IP rating)
Close mounting Impossible
Storage -20 ˚C to 65 ˚C (non-freezing)
Environment
Altitude 1000 m or less above sea level Vibration resistance 5.9 m/s2, at 10 Hz to 55 Hz (directions of X, Y and Z axes) Mass [kg] 1.7 2.1 3.6 4.3 6.5 13.4 18.2
CE marking
MD: EN ISO 13849-1, EN 61800-5-2, EN 62061
UL standard UL 508C
Natural cooling, open
(IP20)
Ambient temperature
Ambient humidity
Ambience
Operation 0 ˚C to 55 ˚C (non-freezing)
Operation Storage
90 %RH or less (non-condensing)
Force cooling, open
(IP20)
free from corrosive gas, flammable gas, oil mist, dust, and dirt
Note 1. 0.5 A is the value applicable when all I/O signals are used. The current capacity can be decreased by reducing the number of
I/O points.
2. Test pulse is a signal which instantaneously turns off a signal to the servo amplifier at a constant period for external circuit to self-diagnose.
3. Except for the terminal block.
4. 1 Mpulse/s or lower commands are supported in the initial setting. When inputting commands over 1 Mpulse/s and 4 Mpulses/s or lower, change the setting in [Pr. PA13].
5. MR-J4-_A4 servo amplifier is compatible only with two-wire type. MR-J4-_A4-RJ servo amplifier is compatible with two-wire type, four-wire type, and A/B/Z-phase differential output method. Refer to table 1.1 for details.
6. Use an external dynamic brake for this servo amplifier. Failure to do so will cause an accident because the servo motor does not stop immediately but coasts at emergency stop. Ensure the safety in the entire equipment.
7. The external dynamic brake cannot be used for compliance with SEMI-F47 standard. Do not assign DB (Dynamic brake interlock) in [Pr. PD23] to [Pr. PD26], [Pr. PD28], and [Pr. PD47]. Failure to do so will cause the servo amplifier to become servo-off when an instantaneous power failure occurs.
8. RS-485 communication is available with servo amplifiers manufactured in November 2014 or later.
EMC: EN 61800-3
Force cooling, open (IP20) (Note 3)
Indoors (no direct sunlight),
1 - 14
1. FUNCTIONS AND CONFIGURATION
(3) 100 V class
Model: MR-J4-_(-RJ) 10A1 20A1 40A1
Output
Main circuit power supply input
Control circuit power supply input
Interface power supply
Control method Sine-wave PWM control, current control method Dynamic brake Built-in Fully closed loop control Compatible (Note 5) Load-side encoder interface (Note 6) Mitsubishi high-speed serial communication
Communication function
Encoder output pulses Compatible (A/B/Z-phase pulse) Analog monitor Two channels
Position control mode
Speed control mode
Torque control mode
Positioning mode
Protective functions
Functional safety STO (IEC/EN 61800-5-2)
Safety performance
Rated voltage 3-phase 170 V AC Rated current [A] 1.1 1.5 2.8 Voltage/Frequency 1-phase 100 V AC to 120 V AC, 50 Hz/60 Hz Rated current [A] 3.0 5.0 9.0 Permissible voltage
fluctuation Permissible frequency
fluctuation Power supply
capacity Inrush current [A] Refer to section 10.5. Voltage/Frequency 1-phase 100 V AC to 120 V AC, 50Hz/60Hz Rated current [A] 0.4 Permissible voltage
fluctuation Permissible frequency
fluctuation Power
consumption Inrush current [A] Refer to section 10.5. Voltage 24 V DC ± 10%
Current capacity [A]
Max. input pulse frequency
Positioning feedback pulse
Command pulse multiplying factor
In-position range setting 0 pulse to ±65535 pulses (command pulse unit) Error excessive ±3 revolutions Torque limit Set by parameter setting or external analog input (0 V DC to +10 V DC/maximum torque) Speed control range Analog speed command 1: 2000, Internal speed command 1: 5000 Analog speed command
input
Speed fluctuation ratio
Torque limit Set by parameter setting or external analog input (0 V DC to +10 V DC/maximum torque) Analog torque command
input Speed limit Set by parameter setting or external analog input (0 V DC to 10 V DC/rated speed)
Standards certified by CB
Response performance 8 ms or less (STO input off energy shut off) (Note 3) Test pulse input (STO) Mean time to dangerous
failure (MTTFd) Diagnosis coverage (DC) Medium (90% to 99%) Average probability of
dangerous failures per hour (PFH)
[kVA] Refer to section 10.2.
[W] 30
USB: Connection to a personal computer or others (MR Configurator2-compatible) RS-422/RS-485: 1:n communication (up to 32 axes) (Note 7)
4 Mpulses/s (for differential receiver) (Note 4), 200 kpulses/s (for open collector)
Encoder resolution (resolution per servo motor revolution): 22 bits
Electronic gear A:1 to 16777215, B:1 to 16777215, 1/10 < A/B < 4000
0 to ±10 V DC/rated speed (The speed at 10 V is changeable with [Pr. PC12].)
±0.01% or less (load fluctuation: 0% to 100%), 0% (power fluctuation: ±10%)
±0.2% or less (ambient temperature: 25 °C ± 10 °C) when using analog speed command
0 V DC to ±8 V DC/maximum torque (input impedance 10 k to 12 k )
Refer to "MR-J4-_A_-RJ Servo Amplifier Instruction Manual (Positioning Mode)" section 1.1.
The positioning mode is used by MR-J4-_A_-RJ servo amplifier with software version B3 or later.
Overcurrent shut-off, regenerative overvoltage shut-off, overload shut-off (electronic thermal), servo motor
encoder error protection, regenerative error protection, undervoltage protection, instantaneous power
error excessive protection, magnetic pole detection protection, and linear servo control fault protection
EN ISO 13849-1 category 3 PL d, IEC 61508 SIL 2, EN 62061 SIL CL 2,
1-phase 85 V AC to 132 V AC
Within ±5%
1-phase 85 V AC to 132 V AC
Within ±5%
(including the CN8 connector signals)
failure protection, overspeed protection,
Test pulse interval: 1 Hz to 25 Hz
(Note 1) 0.5
overheat protection,
and EN 61800-5-2 SIL 2
Test pulse off time: Up to 1 ms
100 years or longer
-10
1.68 × 10
[1/h]
1 - 15
1. FUNCTIONS AND CONFIGURATION
Model: MR-J4-_(-RJ) 10A1 20A1 40A1
Compliance to global standards
Structure (IP rating) Natural cooling, open (IP20) Close mounting (Note 2) Possible
Environment
Mass [kg] 0.8 1.0
CE marking
UL standard UL 508C
Ambient temperature
Ambient humidity
Ambience
Altitude 1000 m or less above sea level Vibration resistance 5.9 m/s2, at 10 Hz to 55 Hz (directions of X, Y and Z axes)
Operation 0 ˚C to 55 ˚C (non-freezing) Storage -20 ˚C to 65 ˚C (non-freezing) Operation Storage
MD: EN ISO 13849-1, EN 61800-5-2, EN 62061
free from corrosive gas, flammable gas, oil mist, dust, and dirt
Note 1. 0.5 A is the value applicable when all I/O signals are used. The current capacity can be decreased by reducing the number of
I/O points.
2. When closely mounting the servo amplifier of 3.5 kW or less, operate them at the ambient temperatures of 0 ˚C to 45 ˚C or at 75% or smaller effective load ratio.
3. Test pulse is a signal which instantaneously turns off a signal to the servo amplifier at a constant period for external circuit to self-diagnose.
4. 1 Mpulse/s or lower commands are supported in the initial setting. When inputting commands over 1 Mpulse/s and 4 Mpulses/s or lower, change the setting in [Pr. PA13].
5. For the compatible version for the fully closed loop system, refer to table 1.1. Check the software version of the servo amplifier using MR Configurator2.
6. The MR-J4-_A servo amplifier is compatible only with the two-wire type. The MR-J4-_A-RJ servo amplifier is compatible with the two-wire type, four-wire type, and A/B/Z-phase differential output method. Refer to table 1.1 for details.
7. RS-485 communication is available with servo amplifiers manufactured in November 2014 or later.
LVD: EN 61800-5-1
EMC: EN 61800-3
90 %RH or less (non-condensing)
Indoors (no direct sunlight),
1 - 16
1. FUNCTIONS AND CONFIGURATION

1.4 Combinations of servo amplifiers and servo motors

(1) 200 V class
Servo amplifier
MR-J4-10A(-RJ) 053
MR-J4-20A(-RJ)
MR-J4-40A(-RJ)
MR-J4-60A(-RJ)
MR-J4-70A(-RJ)
MR-J4-100A(-RJ)
MR-J4-200A(-RJ)
MR-J4-350A(-RJ)
MR-J4-500A(-RJ)
MR-J4-700A(-RJ)
MR-J4-11KA(-RJ)
MR-J4-15KA(-RJ)
MR-J4-22KA(-RJ)
Rotary servo motor
HG-KR HG-MR HG-SR HG-UR HG-RR HG-JR
053
13
13
23 23
43 43
73 73 72 73
702
51 52
81
102
121 201 152 202
301 352
421 502
53
103 53
103
152
202 203 353
352 502
153
153
203
353
503 353
503
601
701M
703 801
12K1
11K1M
903
15K1
15K1M
20K1 25K1
22K1M
HG-JR
(When the
maximum
torque is 400%)
73
103
153 203
503
Linear servo motor
(primary side)
LM-U2PAB-05M-0SS0 LM-U2PBB-07M-1SS0 LM-H3P2A-07P-BSS0 LM-H3P3A-12P-CSS0 LM-K2P1A-01M-2SS1 LM-U2PAD-10M-0SS0 LM-U2PAF-15M-0SS0 LM-U2PBD-15M-1SS0 TM-RFM006C20
LM-H3P3B-24P-CSS0 LM-H3P3C-36P-CSS0 LM-H3P7A-24P-ASS0 LM-K2P2A-02M-1SS1 LM-U2PBF-22M-1SS0 TM-RFM018E20
LM-H3P3D-48P-CSS0 LM-H3P7B-48P-ASS0 LM-H3P7C-72P-ASS0 LM-FP2B-06M-1SS0 LM-K2P1C-03M-2SS1 LM-U2P2B-40M-2SS0 LM-H3P7D-96P-ASS0 LM-K2P2C-07M-1SS1 LM-K2P3C-14M-1SS1 LM-U2P2C-60M-2SS0 LM-FP2D-12M-1SS0 LM-FP4B-12M-1SS0 LM-K2P2E-12M-1SS1 LM-K2P3E-24M-1SS1 LM-U2P2D-80M-2SS0 LM-FP2F-18M-1SS0 LM-FP4D-24M-1SS0
LM-FP4F-36M-1SS0
LM-FP4F-48M-1SS0
Direct
drive motor
TM-RFM002C20
TM-RFM004C20
TM-RFM006E20 TM-RFM012E20 TM-RFM012G20 TM-RFM040J10
TM-RFM048G20 TM-RFM072G20 TM-RFM120J10
TM-RFM240J10
1 - 17
1. FUNCTIONS AND CONFIGURATION
(2) 400 V class
Servo amplifier
MR-J4-60A4(-RJ) 524 534 MR-J4-100A4(-RJ)
MR-J4-200A4(-RJ) 1524
MR-J4-350A4(-RJ)
MR-J4-500A4(-RJ) 5024 5034 3534 MR-J4-700A4(-RJ)
MR-J4-11KA4(-RJ)
MR-J4-15KA4(-RJ) 15K14
MR-J4-22KA4(-RJ) 20K14
(3) 100 V class
Servo amplifier
MR-J4-10A1(-RJ) 053
MR-J4-20A1(-RJ)
MR-J4-40A1(-RJ)
Rotary servo motor
HG-SR HG-JR
1024
2024
3524 3534
7024
Rotary servo motor
HG-KR HG-MR
13
23 23
43 43
734 1034 1534 2034
6014
701M4
7034 8014
12K14
11K1M4
9034
15K1M4
25K14
22K1M4
053
13
(When the maximum
torque is 400%)
Linear servo motor
(primary side)
LM-U2PAB-05M-0SS0 LM-U2PBB-07M-1SS0 LM-H3P2A-07P-BSS0 LM-H3P3A-12P-CSS0 LM-K2P1A-01M-2SS1 LM-U2PAD-10M-0SS0 LM-U2PAF-15M-0SS0
HG-JR
534
734 1034 1534 2034
5034
Linear servo motor (primary side)
LM-FP5H-60M-1SS0
Direct drive motor
TM-RFM002C20
TM-RFM004C20
1 - 18
1. FUNCTIONS AND CONFIGURATION

1.5 Function list

The following table lists the functions of this servo. For details of the functions, refer to each section indicated in the detailed explanation field.
Function Description
This realizes a high response and stable control following the ideal model. The two­degrees-of-freedom-model model adaptive control enables you to set a response to
Model adaptive control
Position control mode This servo amplifier is used as a position control servo.
Speed control mode This servo amplifier is used as a speed control servo.
Torque control mode This servo amplifier is used as a torque control servo.
Positioning mode
Position/speed control change mode
Speed/torque control change mode
Torque/position control change mode
High-resolution encoder
Absolute position detection system
Gain switching function
Advanced vibration suppression control II
Machine resonance suppression filter
Shaft resonance suppression filter
Adaptive filter II
Low-pass filter
Machine analyzer function
Robust filter
Slight vibration suppression control
Electronic gear Input pulses can be multiplied by 1/10 to 4000.
S-pattern acceleration/ deceleration time constant
the command and response to the disturbance separately. Additionally, this function can be disabled. Refer to section 7.5 for disabling this function. This is used with servo amplifiers with software version B4 or later. Check the software version of the servo amplifier using MR Configurator2.
Used when you use an MR-J4-_A_-RJ servo amplifier in the positioning mode under the point table/program/indexer method.
Refer to "MR-J4-_A_-RJ Servo Amplifier Instruction Manual (Positioning Mode)" for details.
The positioning mode is used by MR-J4-_A_-RJ servo amplifier with software version B3 or later.
Using an input device, control can be switched between position control and speed control.
Using an input device, control can be switched between speed control and torque control.
Using an input device, control can be switched between torque control and position control.
High-resolution encoder of 4194304 pulses/rev is used as the encoder of the rotary servo motor compatible with the MELSERVO-J4 series.
Merely setting a home position once makes home position return unnecessary at every power-on.
You can switch gains during rotation and during stop, and can use an input device to switch gains during operation.
This function suppresses vibration at the arm end or residual vibration. Section 7.1.5
This is a filter function (notch filter) which decreases the gain of the specific frequency to suppress the resonance of the mechanical system.
When a load is mounted to the servo motor shaft, resonance by shaft torsion during driving may generate a mechanical vibration at high frequency. The shaft resonance suppression filter suppresses the vibration.
Servo amplifier detects mechanical resonance and sets filter characteristics automatically to suppress mechanical vibration.
Suppresses high-frequency resonance which occurs as servo system response is increased.
Analyzes the frequency characteristic of the mechanical system by simply connecting an MR Configurator2 installed personal computer and servo amplifier.
MR Configurator2 is necessary for this function. This function provides better disturbance response in case low response level that
load to motor inertia ratio is high for such as roll send axis.
Suppresses vibration of ±1 pulse produced at a servo motor stop. [Pr. PB24]
Speed can be increased and decreased smoothly. [Pr. PC03]
explanation
Section 3.2.1 Section 3.6.1 Section 4.2 Section 3.2.2 Section 3.6.2 Section 4.3 Section 3.2.3 Section 3.6.3 Section 4.4
Section 3.6.4
Section 3.6.5
Section 3.6.6
Chapter 12
Section 7.2
Section 7.1.1
Section 7.1.3
Section 7.1.2
Section 7.1.4
[Pr. PE41]
[Pr. PA06] [Pr. PA07]
Detailed
1 - 19
1. FUNCTIONS AND CONFIGURATION
Function Description
Auto tuning
Brake unit
Power regeneration converter
Regenerative option
Alarm history clear Alarm history is cleared. [Pr. PC18] Input signal selection (device
settings)
Output signal selection (device settings)
Output signal (DO) forced output
Restart after instantaneous power failure
Command pulse selection Command pulse train form can be selected from among three different types. [Pr. PA13]
Torque limit Servo motor torque can be limited to any value.
Speed limit Servo motor speed can be limited to any value.
Status display Servo status is shown on the 5-digit, 7-segment LED display Section 4.5 External I/O signal display On/off statuses of external I/O signals are shown on the display. Section 4.5.7
Automatic VC offset
Alarm code output If an alarm has occurred, the corresponding alarm number is outputted in 3-bit code. Chapter 8
Test operation mode
Analog monitor output Servo status is output in terms of voltage in real time.
MR Configurator2
Linear servo system
Direct drive servo system
Fully closed loop system
One-touch tuning
SEMI-F47 function
Tough drive function
Automatically adjusts the gain to optimum value if load applied to the servo motor shaft varies.
Used when the regenerative option cannot provide enough regenerative power. Can be used for the 5 kW or more servo amplifier. Used when the regenerative option cannot provide enough regenerative power. Can be used for the 5 kW or more servo amplifier. Used when the built-in regenerative resistor of the servo amplifier does not have
sufficient regenerative capability for the large regenerative power generated.
ST1 (Forward rotation start), ST2 (Reverse rotation start), and SON (Servo-on) and other input device can be assigned to any pins.
The output devices including MBR (Electromagnetic brake interlock) can be assigned to certain pins of the CN1 connector.
Output signal can be forced on/off independently of the servo status. Use this function for checking output signal wiring, etc. If the input power supply voltage had reduced to cause an alarm but has returned to
normal, the servo motor can be restarted by merely switching on the start signal. (available in the future)
Voltage is automatically offset to stop the servo motor if it does not come to a stop when VC (Analog speed command) or VLA (Analog speed limit is 0 V.
Jog operation, positioning operation, motor-less operation, DO forced output, and program operation
MR Configurator2 is required to perform positioning operation or program operation.
Using a personal computer, you can perform the parameter setting, test operation, monitoring, and others.
Linear servo system can be configured using a linear servo motor and liner encoder. This is used with servo amplifiers with software version A5 or later. Check the
software version of the servo amplifier using MR Configurator2. The direct drive servo system can be configured to drive a direct drive motor. This is used with servo amplifiers with software version A5 or later. Check the
software version of the servo amplifier using MR Configurator2. Fully closed loop system can be configured using the load-side encoder. This is used with servo amplifiers with software version A5 or later. Check the
software version of the servo amplifier using MR Configurator2. Gain adjustment is performed just by one click on a certain button on MR
Configurator2 or operation section. Enables to avoid triggering [AL. 10 Undervoltage] using the electrical energy charged
in the capacitor in case that an instantaneous power failure occurs during operation. Use a 3-phase for the input power supply of the servo amplifier. Using a 1-phase 100 V AC/200 V AC for the input power supply will not comply with SEMI-F47 standard.
This function makes the equipment continue operating even under the condition that an alarm occurs.
The tough drive function includes two types: the vibration tough drive and the instantaneous power failure tough drive.
Detailed
explanation
Section 6.3
Section 11.3
Section 11.4
Section 11.2
[Pr. PD03] to [Pr. PD22] [Pr. PD23] to [Pr. PD26] [Pr. PD28] [Pr. PD47]
Section 4.5.8
Section 3.6.1 (5)
[Pr. PA11] [Pr. PA12] Section 3.6.3
(3) [Pr. PC05] to
[Pr. PC11]
Section 4.5.4
Section 4.5.9
[Pr. PC14], [Pr. PC15]
Section 11.7
Chapter 15
Chapter 16
Chapter 17
Section 6.2
[Pr. PA20] [Pr. PE25] Section 7.4
Section 7.3
1 - 20
1. FUNCTIONS AND CONFIGURATION
Function Description
This function continuously monitors the servo status and records the status transition before and after an alarm for a fixed period of time. You can check the recorded data on the drive recorder window on MR Configurator2 by clicking the "Graph" button.
Drive recorder function
STO function
Servo amplifier life diagnosis function
Power monitoring function
Machine diagnosis function
Lost motion compensation function
Super trace control
High-resolution analog input (VC)
However, the drive recorder will not operate on the following conditions.
1. You are using the graph function of MR Configurator2.
2. You are using the machine analyzer function.
3. [Pr. PF21] is set to "-1". This function is a functional safety that complies with IEC/EN 61800-5-2. You can
create a safety system for the equipment easily. You can check the cumulative energization time and the number of on/off times of the
inrush relay. This function gives an indication of the replacement time for parts of the servo amplifier including a capacitor and a relay before they malfunction.
MR Configurator2 is necessary for this function. This function calculates the power running energy and the regenerative power from
the data in the servo amplifier such as speed and current. Power consumption and others are displayed on MR Configurator2.
From the data in the servo amplifier, this function estimates the friction and vibrational component of the drive system in the equipment and recognizes an error in the machine parts, including a ball screw and bearing.
MR Configurator2 is necessary for this function. This function improves the response delay occurred when the machine moving
direction is reversed.This is used with servo amplifiers with software version B4 or later. Check the software version of the servo amplifier using MR Configurator2.
This function sets constant and uniform acceleration/deceleration droop pulses to almost 0. This is used with servo amplifiers with software version B4 or later. Check the software version of the servo amplifier using MR Configurator2.
The analog input resolution can be increased to 16 bits. This function is available with MR-J4-_A_-RJ 100 W or more servo amplifiers manufactured in November 2014 or later.
Detailed
explanation
[Pr. PA23]
Chapter 13
Section 7.6
Section 7.7
[Pr. PC60]
1 - 21
1. FUNCTIONS AND CONFIGURATION

1.6 Model designation

(1) Rating plate
The following shows an example of rating plate for explanation of each item.
AC SERVO
SER.A45001001
MODEL
POWER INPUT OUTPUT STD.: IEC/EN61800-5-1 MAN.: IB(NA)0300175 Max. Surrounding Air Temp.: 55°C IP20
KCC-REI-MEK-TC300A621G51 DATE: 2014-05
TOKYO 100-8310, JAPAN MADE IN JAPAN
MR-J4-10A
: 100W : 3AC/AC200-240V 0.9A/1.5A 50/60Hz : 3PH170V 0-360Hz 1.1A
(2) Model
The following describes what each block of a model name indicates. Not all combinations of the symbols are available.
Serial number Model
Capacity Applicable power supply Rated output current Standard, Manual number Ambient temperature IP rating
KC certification number, the year and month of manufacture
Country of origin
Series
Rated output
Rated output [kW]
Symbol
10 0.1 20 0.2 40 0.4 60 0.6
70 0.75 100 1 200 2 350 3.5 500 5 700 7 11K 11 15K 15 22K 22
Special specification
Symbol Special specification
None Standard
Fully closed loop control four-wire type/
-RJ
load-side encoder A/B/Z-phase input compatible Positioning mode compatible
MR-J4-_A_ without a dynamic brake (Note 2)-ED MR-J4-_A_-RJ without a dynamic brake (Note 2)
-RU MR-J4-_A_ without regenerative resistor (Note 1)
-PX MR-J4-_A_-RJ without regenerative resistor (Note 1)
-RZ
Note 1. Indicates a servo amplifier of 11 kW to 22 kW that
does not use a regenerative resistor as standard accessory. Refer to Appendix 10.2 for details.
2. Dynamic brake which is built in 7 kw or smaller servo
amplifiers is removed. Refer to Appendix 10.1 for details.
Power supply
Symbol Power supply
3-phase or 1-phase
None
200 V AC to 240 V AC 1-phase 100 V AC to 120 V AC
1
3-phase 380 V AC to 480 V AC
4
General-purpose interface
1 - 22
1. FUNCTIONS AND CONFIGURATION
y
r
r
r

1.7 Structure

1.7.1 Parts identification

(1) 200 V class
(a) MR-J4-200A(-RJ) or less
The diagram is for MR-J4-10A-RJ.
No. Name/Application
Displa
(1)
The 5-digit, 7-segment LED shows the servo status and the alarm number.
Operation section Used to perform status display, diagnostic, alarm, and
parameter setting operations. Push the "MODE" and "SET" buttons at the same time for 3 s or more to switch to the one-touch tuning mode.
(2)
USB communication connector (CN5)
(3)
Connect with the personal computer. Analog monitor connector (CN6)
(4)
Outputs the analog monitor. RS-422/RS-485 communication connector (CN3)
(5)
Connect with the RS-422/RS-485 communication controller, parameter unit, etc.
STO input signal connector (CN8)
(6)
Used to connect the MR-J3-D05 safety logic unit and external safety relay.
I/O signal connector (CN1)
(7)
Used to connect digital I/O signals. Encoder connector (CN2)
(8)
Used to connect the servo motor encoder or external
(Note
encoder. Refer to table 1.1 for the compatible external
2)
encoders.
Battery connector (CN4)
(9)
Used to connect the battery for absolute position data backup.
Battery holde
(10)
Install the the battery for absolute position data backup. Protective earth (PE) terminal
(11)
Grounding terminal Main circuit power supply connector (CNP1)
(12)
Connect the input power supply.
(13) Rating plate Section 1.6
Control circuit power supply connector (CNP2)
(14)
Connect the control circuit power supply and regenerative option.
Servo motor power output connector (CNP3)
(15)
Connect the servo motor. Charge lamp
(16)
When the main circuit is charged, this will light up. While this lamp is lit, do not reconnect the cables.
External encoder connector (CN2L)
(17)
Refer to table 1.1 for the compatible external encoders.
(Note
1, 2)
Optional unit connecto Connect the optional unit. It is available with MR-J4-_A-RJ
(18)
servo amplifiers manufactured in November 2014 or later. The MR-J4-_A servo amplifier does not have this connector.
Optional unit connecto Connect the optional unit. It is available with MR-J4-_A-RJ
(19)
servo amplifiers manufactured in November 2014 or later. The MR-J4-_A servo amplifier does not have this connector.
(3) (4) (12) (5) (6)
(14)
(7)
(15)
(8)
(16) (17)
(9)
(13) Side
(1)
(2)
MODE UP DOWN SET
(10) (11)
Inside of the display cover
(19)
(18)
MODE UP DOWN SET
(CN7)
(CN9)
Used to set data. Push this button together with the "MODE" button for 3 s or more to switch to the one-touch tuning mode.
Used to change the display or data in each mode.
Used to change the mode. Push this button together with the "SET" button for 3 s or more to switch to the one-touch tuning mode.
explanation
Section 4.5
Section 4.5
Section
11.7
Section 3.2
Chapter 14
Chapter 13 App. 5
Section 3.2 Section 3.4 Section 3.4 "Servo Motor
Instruction Manual (Vol.
3)"
Chapter 12
Section
12.2
Section 3.1 Section 3.3
Section 3.1 Section 3.3
"Linear Encoder Instruction Manual"
Detailed
1 - 23
1. FUNCTIONS AND CONFIGURATION
Note 1. This is for the MR-J4-_A-RJ servo amplifier. The MR-J4-_A servo amplifier does not have the CN2L connector.
2. "External encoder" is a term for linear encoder used in the linear servo system and load-side encoder used in the fully closed loop system in this manual.
1 - 24
1. FUNCTIONS AND CONFIGURATION
(b) MR-J4-350A(-RJ)
No. Name/Application
Main circuit power supply connector (CNP1)
(1)
Connect the input power supply.
(2) Rating plate
Servo motor power supply connector (CNP3)
(3)
Connect the servo motor. Control circuit power supply connector (CNP2)
(4)
Connect the control circuit power supply and regenerative option.
Charge lamp
(5)
When the main circuit is charged, this will light up. While this lamp is lit, do not reconnect the cables.
Protective earth (PE) terminal
(6)
Grounding terminal Battery holder
(7)
Install the the battery for absolute position data backup.
(1)
(3)
(2) Side
(4)
(5)
The broken line area is the same as MR-J4-200A(-RJ) or less.
(7)
(6)
Detailed
explanation Section 3.1
Section 3.3 Section 1.6
Section 3.1 Section 3.3
Section 3.1 Section 3.3
Section
12.2
1 - 25
1. FUNCTIONS AND CONFIGURATION
(c) MR-J4-500A(-RJ)
No. Name/Application
Control circuit terminal block (TE2)
(1)
Used to connect the control circuit power supply. Main circuit terminal block (TE1)
(2)
Connect the input power supply. Battery holder
(3)
Install the the battery for absolute position data backup.
(4) Rating plate
Regenerative option/power factor improving reactor terminal block (TE3)
(5)
Used to connect a regenerative option or a power factor improving DC reactor.
Servo motor power supply terminal block (TE4)
(6)
Connect the servo motor. Charge lamp
(7)
When the main circuit is charged, this will light up. While this lamp is lit, do not reconnect the cables.
Protective earth (PE) terminal
(8)
Grounding terminal
(1)
(2)
(3) (Note)
(4) Side
(5)
POINT
The servo amplifier is shown with the front cover open. The front cover cannot be removed.
The broken line area is the same as MR-J4-200A(-RJ) or less.
Detailed
explanation
Section 3.1 Section 3.3
Section
12.2
Section 1.6
Section 3.1 Section 3.3
Section 3.1 Section 3.3
(6)
(7)
(8)
Note. Lines for slots around the battery holder are omitted from the illustration.
1 - 26
1. FUNCTIONS AND CONFIGURATION
(d) MR-J4-700A(-RJ)
POINT
The servo amplifier is shown without the front cover. For removal of the front cover, refer to section 1.7.2.
The broken line area is the same as MR-J4-200A(-RJ) or less.
(7)
(6)
(5) (Note)
No. Name/Application
Power factor improving reactor terminal block (TE3)
(1)
Used to connect the DC reactor. Main circuit terminal block (TE1)
(2)
Used to connect the input power supply, regenerative option, and servo motor.
Control circuit terminal block (TE2)
(3)
Used to connect the control circuit power supply. Protective earth (PE) terminal
(4)
Grounding terminal Battery holder
(5)
Install the the battery for absolute position data backup.
(6) Rating plate
Charge lamp
(7)
When the main circuit is charged, this will light up. While this lamp is lit, do not reconnect the cables.
Detailed
explanation
Section 3.1 Section 3.3
Section
12.2
Section 1.6
(1)
(2)
(4)
(3)
Note. Lines for slots around the battery holder are omitted from the illustration.
1 - 27
1. FUNCTIONS AND CONFIGURATION
(e) MR-J4-11KA(-RJ)/MR-J4-15KA(-RJ)
POINT
The servo amplifier is shown without the front cover. For removal of the front cover, refer to section 1.7.2.
The broken line area is the same as MR-J4-200A(-RJ) or less.
(7)
(6)
(5) (Note)
(2)
(3)
No. Name/Application
Power factor improving reactor terminal block (TE1-
2)
(1)
Used to connect a power factor improving DC reactor and a regenerative option.
Main circuit terminal block (TE1-1)
(2)
Used to connect the input power supply and servo motor.
Control circuit terminal block (TE2)
(3)
Used to connect the control circuit power supply. Protective earth (PE) terminal
(4)
Grounding terminal Battery holder
(5)
Install the the battery for absolute position data backup.
(6) Rating plate
Charge lamp
(7)
When the main circuit is charged, this will light up. While this lamp is lit, do not reconnect the cables.
Detailed
explanation
Section 3.1 Section 3.3
Section
12.2
Section 1.6
(4)
(1)
Note. Lines for slots around the battery holder are omitted from the illustration.
1 - 28
1. FUNCTIONS AND CONFIGURATION
(f) MR-J4-22KA(-RJ)
No. Name/Application
Power factor improving reactor terminal block (TE1-
2)
(1)
Used to connect a power factor improving DC reactor and a regenerative option.
Main circuit terminal block (TE1-1)
(2)
Used to connect the input power supply and servo motor.
Control circuit terminal block (TE2)
(3)
Used to connect the control circuit power supply. Protective earth (PE) terminal
(4)
Grounding terminal Battery holder
(5)
Install the the battery for absolute position data backup.
(6) Rating plate
Charge lamp
(7)
When the main circuit is charged, this will light up. While this lamp is lit, do not reconnect the cables.
(7)
(5) (Note)
(6)
(2)
(3)
POINT
The servo amplifier is shown without the front cover. For removal of the front cover, refer to section 1.7.2.
The broken line area is the same as MR-J4-200A(-RJ) or less.
Detailed
explanation
Section 3.1 Section 3.3
Section
12.2
Section 1.6
(1)
(4)
Note. Lines for slots around the battery holder are omitted from the illustration.
1 - 29
1. FUNCTIONS AND CONFIGURATION
y
r
r
r
(2) 400 V class
(a) For MR-J4-200A4(-RJ) or less
The diagram is for MR-J4-60A4-RJ.
No. Name/Application
(1)
(2)
MODE UP DOWN SET
(1)
Displa The 5-digit, seven-segment LED shows the servo
status and the alarm number. Operation section Used to perform status display, diagnostic, alarm,
and parameter setting operations. Push the "MODE" and "SET" buttons at the same time for 3 s or more to switch to the one-touch tuning mode.
MODE UP DOWN SET
Detailed
explanation
(3) (16) (4) (12) (5) (6)
(14)
(7) (8) (15) (17) (9) (13)
Side
(10)
(11)
Inside of the display cover
(19)
(18)
Used to set data. Push
(2)
USB communication connector (CN5)
(3)
Connect with the personal computer. Analog monitor connector (CN6)
(4)
Outputs the analog monitor. RS-422/RS-485 communication connector (CN3)
(5)
Connect with the RS-422/RS-485 communication controller, parameter unit, etc.
STO input signal connector (CN8)
(6)
Used to connect MR-J3-D05 safety logic unit and external safety relay.
I/O signal connector (CN1)
(7)
Used to connect digital I/O signals. Encoder connector (CN2) Used to connect the servo motor encoder or
(8)
external encoder. Refer to table 1.1 for the
(Note
compatible external encoders.
2)
Battery connector (CN4)
(9)
Used to connect the battery for absolute position data backup.
Battery holde
(10)
Install the battery for absolute position data backup. Protective earth (PE) terminal
(11)
Grounding terminal Main circuit power supply connector (CNP1)
(12)
Connect the input power supply.
(13) Rating plate Section 1.6
Control circuit power supply connector (CNP2)
(14)
Connect the control circuit power supply and regenerative option.
Servo motor power output connector (CNP3)
(15)
Connect the servo motor. Charge lamp
(16)
When the main circuit is charged, this will light. While this lamp is lit, do not reconnect the cables.
External encoder connector (CN2L)
(17)
Used to connect the external encoder. Refer to
(Note
table 1.1 for the compatible external encoders.
1) Optional unit connecto
Connect the optional unit. It is available with MR-J4-
(18)
_A4-RJ servo amplifiers manufactured in November 2014 or later. MR-J4-_A4 servo amplifier does not have this connector.
Optional unit connecto Connect the optional unit. It is available with MR-
(19)
J4-_A4-RJ servo amplifiers manufactured in November 2014 or later. The MR-J4-_A4 servo amplifier does not have this connector.
this button together with the "MODE" button for 3 s or more to switch to the one-touch tuning mode.
Used to change the display or data in each mode.
Used to change the mode. Push this button together wish the "SET" button for 3 s or more to switch to the one-touch tuning mode.
(CN7)
(CN9)
Section 4.5
Section 3.2
Chapter 14
Chapter 13
Section 3.2 Section 3.4 Section 3.4
"Servo Motor Instruction Manual (Vol. 3)"
Chapter 12
Section 3.1 Section 3.3
Section 3.1 Section 3.3
"Linear Encoder Instruction Manual"
Section
11.7
App. 5
Section
12.2
1 - 30
1. FUNCTIONS AND CONFIGURATION
Note 1. This is for MR-J4-_A4-RJ servo amplifier. MR-J4-_A4 servo amplifier does not have CN2L connector.
2. "External encoder" is a term for linear encoder used in the linear servo system and load-side encoder used in the fully closed loop system in this manual.
1 - 31
1. FUNCTIONS AND CONFIGURATION
(b) MR-J4-350A4(-RJ)
No. Name/Application
(1)
(2) Rating plate Section 1.6
(3)
(4)
(5)
(6)
(7)
(1)
(7)
(3)
(2) Side
(4)
(5)
The broken line area is the same as MR-J4-200A4(-RJ) or less.
Main circuit power supply connector (CNP1) Connect the input power supply.
Control circuit power supply connector (CNP2) Connect the control circuit power supply and
regenerative option. Servo motor power output connector (CNP3) Connect the servo motor. Charge lamp When the main circuit is charged, this will light.
While this lamp is lit, do not reconnect the cables. Protective earth (PE) terminal Grounding terminal Battery holder Install the battery for absolute position data
backup.
Detailed
explanation Section 3.1
Section 3.3
Section 3.1 Section 3.3
Section 3.1 Section 3.3
Section 12.2
(6)
1 - 32
1. FUNCTIONS AND CONFIGURATION
(c) MR-J4-500A4(-RJ)
No. Name/Application
(1)
(2)
(3)
(4) Rating plate Section 1.6
(5)
(6)
(7)
(6)
(3) (Note)
(4)
(5)
(1)
(2)
POINT
The servo amplifier is shown without the front cover. For removal of the front cover, refer to section 1.7.2.
The broken line area is the same as MR-J4-200A4(-RJ) or less.
Control circuit terminal block (TE2) Used to connect the control circuit power supply. Main circuit terminal block (TE1) Used to connect the input power supply and servo
motor. Battery holder Install the battery for absolute position data
backup.
Regenerative option/power factor improving reactor terminal block (TE3)
Used to connect a regenerative option and a power factor improving DC reactor.
Charge lamp When the main circuit is charged, this will light.
While this lamp is lit, do not reconnect the cables. Protective earth (PE) terminal Grounding terminal
Detailed
explanation
Section 3.1 Section 3.3
Section 12.2
Section 3.1 Section 3.3
Section 3.1 Section 3.3
(7)
Note. Lines for slots around the battery holder are omitted from the illustration.
1 - 33
1. FUNCTIONS AND CONFIGURATION
(d) MR-J4-700A4(-RJ)
No. Name/Application
(1)
(2)
(3)
(4)
(5)
(6) Rating plate Section 1.6
(7)
(7)
(6)
(5) (Note)
(1)
POINT
The servo amplifier is shown without the front cover. For removal of the front cover, refer to section 1.7.2.
The broken line area is the same as MR-J4-200A4(-RJ) or less.
Power factor improving reactor terminal block (TE3)
Used to connect the DC reactor. Main circuit terminal block (TE1) Used to connect the input power supply,
regenerative option, and servo motor. Control circuit terminal block (TE2) Used to connect the control circuit power supply. Protective earth (PE) terminal Grounding terminal Battery holder Install the battery for absolute position data
backup.
Charge lamp When the main circuit is charged, this will light.
While this lamp is lit, do not reconnect the cables.
Detailed
explanation
Section 3.1 Section 3.3
Section 12.2
(2)
(4)
(3)
Note. Lines for slots around the battery holder are omitted from the illustration.
1 - 34
1. FUNCTIONS AND CONFIGURATION
(e) MR-J4-11KA4(-RJ)/MR-J4-15KA4(-RJ)
No. Name/Application
(1)
(2)
(3)
(4)
(5)
(6) Rating plate Section 1.6
(7)
(7)
(6)
(5) (Note)
(2)
(3)
(4)
POINT
The servo amplifier is shown without the front cover. For removal of the front cover, refer to section 1.7.2.
The broken line area is the same as MR-J4-200A4(-RJ) or less.
Power factor improving reactor terminal block (TE1-2)
Used to connect a power factor improving DC reactor and a regenerative option.
Main circuit terminal block (TE1-1) Used to connect the input power supply and servo
motor. Control circuit terminal block (TE2) Used to connect the control circuit power supply. Protective earth (PE) terminal Grounding terminal Battery holder Install the battery for absolute position data
backup.
Charge lamp When the main circuit is charged, this will light.
While this lamp is lit, do not reconnect the cables.
Detailed
explanation
Section 3.1 Section 3.3
Section 12.2
(1)
Note. Lines for slots around the battery holder are omitted from the illustration.
1 - 35
1. FUNCTIONS AND CONFIGURATION
(f) MR-J4-22KA4(-RJ)
No. Name/Application
(1)
(2)
(3)
(4)
(5)
(6) Rating plate Section 1.6
(7)
(7)
(5) (Note)
(6)
(2)
(3)
(1)
POINT
The servo amplifier is shown without the front cover. For removal of the front cover, refer to section 1.7.2.
The broken line area is the same as MR-J4-200A4(-RJ) or less.
Power factor improving reactor terminal block (TE1-2)
Used to connect a power factor improving DC reactor and a regenerative option.
Main circuit terminal block (TE1-1) Used to connect the input power supply and servo
motor. Control circuit terminal block (TE2) Used to connect the control circuit power supply. Protective earth (PE) terminal Grounding terminal Battery holder Install the battery for absolute position data
backup.
Charge lamp When the main circuit is charged, this will light.
While this lamp is lit, do not reconnect the cables.
Detailed
explanation
Section 3.1 Section 3.3
Section 12.2
(4)
Note. Lines for slots around the battery holder are omitted from the illustration.
1 - 36
1. FUNCTIONS AND CONFIGURATION
y
r
r
(3) 100 V class
The diagram is for MR-J4-10A1-RJ.
No. Name/Application
Displa
(1)
(1)
(2)
MODE UP DOWN SET
The 5-digit, 7-segment LED shows the servo status and the alarm number.
Operation section Used to perform status display, diagnostic, alarm, and
parameter setting operations. Push the "MODE" and "SET" buttons at the same time for 3 s or more to switch to the one-touch tuning mode.
MODE UP DOWN SET
Used to set data. Push this button together with the "MODE" button for 3 s or more to switch to the one-touch tuning mode.
Used to change the display or data in each mode.
Used to change the mode. Push this button together with the "SET" button for 3 s or more to switch to the one-touch tuning mode.
(CN7)
(3) (4) (12) (5) (6)
(14)
(7)
(15)
(8)
(16) (17)
(9)
(13) Side
Inside of the display cover
(10) (11)
(19)
(18)
(2)
USB communication connector (CN5)
(3)
Connect with the personal computer. Analog monitor connector (CN6)
(4)
Outputs the analog monitor. RS-422/RS-485 communication connector (CN3)
(5)
Connect with the RS-422/RS-485 communication controller, parameter unit, etc.
STO input signal connector (CN8)
(6)
Used to connect the MR-J3-D05 safety logic unit and external safety relay.
I/O signal connector (CN1)
(7)
Used to connect digital I/O signals. Encoder connector (CN2) Used to connect the servo motor encoder or external
(8)
encoder. Refer to table 1.1 for the compatible external
(Note
encoders.
2)
Battery connector (CN4)
(9)
Used to connect the battery for absolute position data backup.
Battery holde
(10)
Install the the battery for absolute position data backup. Protective earth (PE) terminal
(11)
Grounding terminal Main circuit power supply connector (CNP1)
(12)
Connect the input power supply.
(13) Rating plate Section 1.6
Control circuit power supply connector (CNP2)
(14)
Connect the control circuit power supply and regenerative option.
Servo motor power output connector (CNP3)
(15)
Connect the servo motor. Charge lamp
(16)
When the main circuit is charged, this will light up. While this lamp is lit, do not reconnect the cables.
External encoder connector (CN2L)
(17)
Refer to table 1.1 for the compatible external encoders.
(Note
1, 2)
Optional unit connecto Connect the optional unit. It is available with MR-J4-_A1-RJ
(18)
servo amplifiers manufactured in November 2014 or later. The MR-J4-_A1 servo amplifier does not have this connector.
Optional unit connector (CN9) Connect the optional unit. It is available with MR-J4-_A1-RJ
(19)
servo amplifiers manufactured in November 2014 or later. The MR-J4-_A1 servo amplifier does not have this connector.
Note 1. This is for the MR-J4-_A1-RJ servo amplifier. The MR-J4-_A1 servo amplifier does not have the CN2L connector.
2. "External encoder" is a term for linear encoder used in the linear servo system and load-side encoder used in the fully closed loop system in this manual.
Detailed
explanation
Section 4.5
Section 4.5
Section
11.7
Section 3.2
Chapter 14
Chapter 13
App. 5
Section 3.2 Section 3.4 Section 3.4
"Servo Motor Instruction Manual (Vol. 3)"
Chapter 12
Section
12.2
Section 3.1 Section 3.3
Section 3.1 Section 3.3
"Linear Encoder Instruction Manual"
1 - 37
1. FUNCTIONS AND CONFIGURATION

1.7.2 Removal and reinstallation of the front cover

Before removing or installing the front cover, turn off the power and wait for 15 minutes or more until the charge lamp turns off. Then, confirm that the voltage
CAUTION
The following shows how to remove and reinstall the front cover of MR-J4-700A(-RJ) to MR-J4-22KA(-RJ) and MR-J4-500A4(-RJ) to MR-J4-22KA4(-RJ). The diagram shows MR-J4-700A.
Removal of the front cover
between P+ and N- is safe with a voltage tester and others. Otherwise, an electric shock may occur. In addition, when confirming whether the charge lamp is off or not, always confirm it from the front of the servo amplifier.
1) Hold the ends of lower side of the front cover with both hands.
A)
A)
2) Pull up the cover, supporting at point A).
3) Pull out the front cover to remove. Hold the ends of lower side of the front cover with both hands.
1 - 38
1. FUNCTIONS AND CONFIGURATION
Reinstallation of the front cover
Front cover setting tab
A)
1) Insert the front cover setting tabs into the sockets of
the servo amplifier (2 places).
2) Push down the cover, supporting at point A).
A)
Setting tab
3) Press the cover against the terminal box until the
setting tabs click.
1 - 39
1. FUNCTIONS AND CONFIGURATION

1.8 Configuration including peripheral equipment

CAUTION
(1) 200 V class
(a) MR-J4-200A(-RJ) or less
The diagram shows MR-J4-20A-RJ.
(Note 2) Power supply
Molded-case circuit breaker (MCCB)
RS T
Connecting a servo motor of the wrong axis to U, V, W, or CN2 of the servo amplifier may cause a malfunction.
POINT
Equipment other than the servo amplifier and servo motor are optional or recommended products.
CN5
MR Configurator2
Personal computer
(Note 3) Magnetic contactor (MC)
Line noise filter (FR-BSF01)
Power factor improving DC reactor (FR-HEL)
Regenerative option
(Note 1)
L1 L2 L3
P+
C
P3
P4
L11
L21
D (Note 5)
CN6
CN3
To RS-422/RS-485 communication controller, parameter unit, etc.
CN8
U V
W
CN1
CN2
CN2L (Note 4) CN4
Battery
Analog monitor
To safety relay or MR-J3-D05 safety logic unit
Junction terminal block
Servo motor
1 - 40
1. FUNCTIONS AND CONFIGURATION
A
_
A
Note 1. The power factor improving AC reactor can also be used. In this case, the power factor improving DC reactor cannot be used.
When not using the power factor improving DC reactor, short P3 and P4.
2.
3. Depending on the main circuit voltage and operation pattern, bus voltage decreases, and that may cause the forced stop
4. This is for the MR-J4-_A-RJ servo amplifier. The MR-J4-
5.
1-phase 200 V AC to 240 V AC power supply may be used with the servo amplifier of MR-J4-70A(-RJ) or less. For 1-phase 200 V AC to 240 V AC, connect the power supply to L1 and L3. Leave L2 open. For the power supply specifications, refer to section 1.3.
deceleration to shift to the dynamic brake deceleration. When dynamic brake deceleration is not required, slow the time to turn off the magnetic contactor.
A servo amplifier does not have the CN2L connector. When using an MR-J4-_A-RJ servo amplifier in the linear servo system or in the fully closed loop system, connect an external encoder to this connector. Refer to table 1.1 and "Linear Encoder Instruction Manual" for the compatible external encoders.
lways connect between P+ and D terminals. When using the regenerative option, refer to section 11.2.
1 - 41
1. FUNCTIONS AND CONFIGURATION
A
(b) MR-J4-350A(-RJ)
(Note 2) Power supply
Molded-case circuit breaker (MCCB)
(Note 3) Magnetic contactor (MC)
Line noise filter (FR-BSF01)
RS T
(Note 1)
MR Configurator2
CN5
CN6
CN3
CN8
Analog monitor
To RS-422/RS-485 communication controller, parameter unit, etc.
Personal computer
To safety relay or MR-J3-D05 safety logic unit
Power factor improving DC reactor (FR-HEL)
Regenerative option
L1 L2 L3
P+
C
P3
P4
L11
L21
U V
W
D (Note 5)
CN1
CN2
CN2L (Note 4) CN4
Servo motor
Battery
Junction terminal block
Note 1. The power factor improving AC reactor can also be used. In this case, the power factor improving DC reactor cannot be used.
When not using the power factor improving DC reactor, short P3 and P4.
2. For the power supply specifications, refer to section 1.3.
3. Depending on the main circuit voltage and operation pattern, bus voltage decreases, and that may cause the forced stop deceleration to shift to the dynamic brake deceleration. When dynamic brake deceleration is not required, slow the time to turn off the magnetic contactor.
4. This is for the MR-J4-_A-RJ servo amplifier. The MR-J4-_A servo amplifier does not have the CN2L connector. When using MR-J4-_A-RJ servo amplifier in the linear servo system or in the fully closed loop system, connect an external encoder to this connector. Refer to table 1.1 and "Linear Encoder Instruction Manual" for the compatible external encoders.
5.
lways connect between P+ and D terminals. When using the regenerative option, refer to section 11.2.
1 - 42
1. FUNCTIONS AND CONFIGURATION
A
(c) MR-J4-500A(-RJ)
(Note 2) Power supply
Molded-case circuit breaker (MCCB)
(Note 3) Magnetic contactor (MC)
(Note 1)
Line noise filter (FR-BLF)
RS T
L11
L21
MR Configurator2
CN5
CN6
CN3
CN8
Analog monitor
To RS-422/RS-485 communication controller, parameter unit, etc.
Personal computer
To safety relay or MR-J3-D05 safety logic unit
Power factor improving DC reactor (FR-HEL)
Regenerative option
L1 L2 L3
P+
C
P3
P4
D (Note 5)
U
V
W
CN1
CN2
CN2L (Note 4)
CN4
Servo motor
Junction terminal block
Battery
Note 1. The power factor improving AC reactor can also be used. In this case, the power factor improving DC reactor cannot be used.
When not using the power factor improving DC reactor, short P3 and P4.
2. For the power supply specifications, refer to section 1.3.
3. Depending on the main circuit voltage and operation pattern, bus voltage decreases, and that may cause the forced stop deceleration to shift to the dynamic brake deceleration. When dynamic brake deceleration is not required, slow the time to turn off the magnetic contactor.
4. This is for the MR-J4-_A-RJ servo amplifier. The MR-J4-_A servo amplifier does not have the CN2L connector. When using an MR-J4-_A-RJ servo amplifier in the linear servo system or in the fully closed loop system, connect an external encoder to this connector. Refer to table 1.1 and "Linear Encoder Instruction Manual" for the compatible external encoders.
5.
lways connect between P+ and D terminals. When using the regenerative option, refer to section 11.2.
1 - 43
1. FUNCTIONS AND CONFIGURATION
_
(d) MR-J4-700A(-RJ)
(Note 2) Power supply
Molded-case circuit breaker (MCCB)
(Note 3) Magnetic contactor (MC)
Line noise filter (FR-BLF)
RS T
(Note 1)
MR Configurator2
CN5
CN6
CN3
CN8
CN1
Analog monitor
To RS-422/RS-485 communication controller, parameter unit, etc.
To safety relay or MR-J3-D05 safety logic unit
Personal computer
Power factor improving DC reactor (FR-HEL)
L3 L2 L1
P3
P4
L21
L11
(Note 5)
C
P+ Regenerative option
CN2 CN2L
(Note 4)
CN4
Battery
WVU
Junction terminal block
Servo motor
Note 1. The power factor improving AC reactor can also be used. In this case, the power factor improving DC reactor cannot be used.
When not using the power factor improving DC reactor, short P3 and P4.
2. For the power supply specifications, refer to section 1.3.
3. Depending on the main circuit voltage and operation pattern, bus voltage decreases, and that may cause the forced stop deceleration to shift to the dynamic brake deceleration. When dynamic brake deceleration is not required, slow the time to turn off the magnetic contactor.
4. This is for the MR-J4-_A-RJ servo amplifier. The MR-J4­MR-J4-_A-RJ servo amplifier in the linear servo system or in the fully closed loop system, connect an external encoder to this connector. Refer to table 1.1 and "Linear Encoder Instruction Manual" for the compatible external encoders.
5. When using the regenerative option, refer to section 11.2.
A servo amplifier does not have the CN2L connector. When using an
1 - 44
1. FUNCTIONS AND CONFIGURATION
_
(e) MR-J4-11KA(-RJ)/MR-J4-15KA(-RJ)
(Note 2) Power supply
Molded-case circuit breaker (MCCB)
(Note 3) Magnetic contactor (MC)
(Note 1)
Line noise filter (FR-BLF)
RS T
L3 L2 L1
L21 L11
MR Configurator2
CN5
CN6
CN3
CN8
CN1
CN2 CN2L
(Note 4)
CN4
Battery
Analog monitor
To RS-422/RS-485 communication controller, parameter unit, etc.
To safety relay or MR-J3-D05 safety logic unit
Junction terminal block
Personal computer
WVU
Power factor improving DC reactor (FR-HEL)
P3
P4
C
P+
(Note 5)
Note 1. The power factor improving AC reactor can also be used. In this case, the power factor improving DC reactor cannot be used.
When not using the power factor improving DC reactor, short P3 and P4.
2. For the power supply specifications, refer to section 1.3.
3. Depending on the main circuit voltage and operation pattern, bus voltage decreases, and that may cause the forced stop deceleration to shift to the dynamic brake deceleration. When dynamic brake deceleration is not required, slow the time to turn off the magnetic contactor.
4. This is for the MR-J4-_A-RJ servo amplifier. The MR-J4­MR-J4-_A-RJ servo amplifier in the linear servo system or in the fully closed loop system, connect an external encoder to this connector. Refer to table 1.1 and "Linear Encoder Instruction Manual" for the compatible external encoders.
5. When using the regenerative option, refer to section 11.2.
Regenerative option
Servo motor
A servo amplifier does not have the CN2L connector. When using an
1 - 45
1. FUNCTIONS AND CONFIGURATION
_
(f) MR-J4-22KA(-RJ)
(Note 2) Power supply
Molded-case circuit breaker (MCCB)
(Note 3) Magnetic contactor (MC)
(Note 1)
RS T
MR Configurator2
CN5
CN6
CN3
To RS-422/RS-485 communication controller, parameter unit, etc.
CN8
CN1
Analog monitor
To safety relay or MR-J3-D05 safety logic unit
Personal computer
Line noise filter (FR-BLF)
L3 L2 L1
Power factor improving DC reactor (FR-HEL)
P3
P4
L21
L11
(Note 5)
C
P+ Regenerative option
CN2 CN2L
(Note 4)
CN4
Battery
Junction terminal block
VU
W
Servo motor
Note 1. The power factor improving AC reactor can also be used. In this case, the power factor improving DC reactor cannot be used.
When not using the power factor improving DC reactor, short P3 and P4.
2. For the power supply specifications, refer to section 1.3.
3. Depending on the main circuit voltage and operation pattern, bus voltage decreases, and that may cause the forced stop deceleration to shift to the dynamic brake deceleration. When dynamic brake deceleration is not required, slow the time to turn off the magnetic contactor.
4. This is for the MR-J4-_A-RJ servo amplifier. The MR-J4­MR-J4-_A-RJ servo amplifier in the linear servo system or in the fully closed loop system, connect an external encoder to this connector. Refer to table 1.1 and "Linear Encoder Instruction Manual" for the compatible external encoders.
5. When using the regenerative option, refer to section 11.2.
A servo amplifier does not have the CN2L connector. When using an
1 - 46
1. FUNCTIONS AND CONFIGURATION
A
(2) 400 V class
(a) MR-J4-200A4(-RJ) or less
The diagram is for MR-J4-60A4-RJ and MR-J4-100A4-RJ.
RST
(Note 2) Power supply
Molded-case circuit breaker (MCCB)
CN5
MR Configurator2
Personal computer
(Note 3) Magnetic contactor (MC)
(Note 1)
Line noise filter (FR-BSF01)
Power factor improving DC reactor (FR-HEL-H)
Regenerative option
L1 L2 L3
P+
C
P3
P4
L11
L21
D (Note 5)
U
V
W
CN6
CN3
To RS-422/RS-485 communication controller, parameter unit, etc.
CN8
CN1
CN2
CN2L (Note 4)
CN4
Battery
Analog monitor
To safety relay or MR-J3-D05 safety logic unit
Junction terminal block
Servo motor
Note 1. The power factor improving AC reactor can also be used. In this case, the power factor improving DC reactor cannot be used.
When not using the power factor improving DC reactor, short P3 and P4.
2. Refer to section 1.3 for the power supply specification.
3. Depending on the main circuit voltage and operation pattern, bus voltage decreases, and that may cause the forced stop deceleration to shift to the dynamic brake deceleration. When dynamic brake deceleration is not required, slow the time to turn off the magnetic contactor.
4. This is for MR-J4-_A4-RJ servo amplifier. MR-J4-_A4 servo amplifier does not have CN2L connector. When using MR-J4-_A4­RJ servo amplifier in the linear servo system or in the fully closed loop system, connect an external encoder to this connector. Refer to Table 1.1 and "Linear Encoder Instruction Manual" for the compatible external encoders.
5.
lways connect between P+ and D terminals. When using the regenerative option, refer to section 11.2.
1 - 47
1. FUNCTIONS AND CONFIGURATION
A
(b) MR-J4-350A4(-RJ)
RS T
(Note 2) Power supply
Molded-case circuit breaker (MCCB)
(Note 3) Magnetic contactor (MC)
(Note 1)
Line noise filter (FR-BSF01)
D (Note 5)
L1
Power factor improving DC reactor (FR-HEL-H)
Regenerative option
L2 L3
P3
P4
P+
C
L11
U V
W
MR Configurator2
CN5
CN6
CN3
To RS-422/RS-485 communication controller, parameter unit, etc.
CN8
CN1
CN2
CN2L (Note 4)
CN4
Analog monitor
Junction terminal block
Battery
Personal computer
To safety relay or MR-J3-D05 safety logic unit
L21
Servo motor
Note 1. The power factor improving AC reactor can also be used. In this case, the power factor improving DC reactor cannot be used.
When not using the power factor improving DC reactor, short P3 and P4.
2. Refer to section 1.3 for the power supply specification.
3. Depending on the main circuit voltage and operation pattern, bus voltage decreases, and that may cause the forced stop deceleration to shift to the dynamic brake deceleration. When dynamic brake deceleration is not required, slow the time to turn off the magnetic contactor.
4. This is for MR-J4-_A4-RJ servo amplifier. MR-J4-_A4 servo amplifier does not have CN2L connector. When using MR-J4-_A4­RJ servo amplifier in the linear servo system or in the fully closed loop system, connect an external encoder to this connector. Refer to Table 1.1 and "Linear Encoder Instruction Manual" for the compatible external encoders.
5.
lways connect between P+ and D terminals. When using the regenerative option, refer to section 11.2.
1 - 48
1. FUNCTIONS AND CONFIGURATION
(c) MR-J4-500A4(-RJ)
(Note 1)
RS T
Power factor improving DC reactor (FR-HEL-H)
P4
P3
(Note 2) Power supply
Molded-case circuit breaker (MCCB)
(Note 3) Magnetic contactor (MC)
Line noise filter (FR-BSF01)
MR Configurator2
CN5
CN6
CN3
To RS-422/RS-485 communication controller, parameter unit, etc.
CN8
CN1
Analog monitor
To safety relay or MR-J3-D05 safety logic unit
Personal computer
L3 L2
L1
L21
L11
(Note 5)
P+ C
Regenerative option
WVU
CN2
CN2L (Note 4) CN4
Battery
Junction terminal block
Servo motor
Note 1. The power factor improving AC reactor can also be used. In this case, the power factor improving DC reactor cannot be used.
When not using the power factor improving DC reactor, short P3 and P4.
2. Refer to section 1.3 for the power supply specification.
3. Depending on the main circuit voltage and operation pattern, bus voltage decreases, and that may cause the forced stop deceleration to shift to the dynamic brake deceleration. When dynamic brake deceleration is not required, slow the time to turn off the magnetic contactor.
4. This is for MR-J4-_A4-RJ servo amplifier. MR-J4-_A4 servo amplifier does not have CN2L connector. When using MR-J4-_A4­RJ servo amplifier in the linear servo system or in the fully closed loop system, connect an external encoder to this connector. Refer to Table 1.1 and "Linear Encoder Instruction Manual" for the compatible external encoders.
5. When using the regenerative option, refer to section 11.2.
1 - 49
1. FUNCTIONS AND CONFIGURATION
(d) MR-J4-700A4(-RJ)
(Note 2) Power supply
Molded-case circuit breaker (MCCB)
RS T
CN5
MR Configurator2
Personal computer
(Note 3) Magnetic contactor (MC)
(Note 1)
Line noise filter (FR-BLF)
Power factor improving DC reactor (FR-HEL-H)
L3 L2 L1
P3
P4
L21
L11
CN6
CN3
CN8
CN1
CN2
CN2L (Note 4) CN4
Analog monitor
To RS-422/RS-485 communication controller, parameter unit, etc.
Battery
To safety relay or MR-J3-D05 safety logic unit
Junction terminal block
WVU
P+ C
(Note 5)
Note 1. The power factor improving AC reactor can also be used. In this case, the power factor improving DC reactor cannot be used.
When not using the power factor improving DC reactor, short P3 and P4.
2. Refer to section 1.3 for the power supply specification.
3. Depending on the main circuit voltage and operation pattern, bus voltage decreases, and that may cause the forced stop deceleration to shift to the dynamic brake deceleration. When dynamic brake deceleration is not required, slow the time to turn off the magnetic contactor.
4. This is for MR-J4-_A4-RJ servo amplifier. MR-J4-_A4 servo amplifier does not have CN2L connector. When using MR-J4-_A4­RJ servo amplifier in the linear servo system or in the fully closed loop system, connect an external encoder to this connector. Refer to Table 1.1 and "Linear Encoder Instruction Manual" for the compatible external encoders.
5. When using the regenerative option, refer to section 11.2.
Regenerative option
Servo motor
1 - 50
1. FUNCTIONS AND CONFIGURATION
(e) MR-J4-11KA4(-RJ)/MR-J4-15KA4(-RJ)
RS T
(Note 2) Power supply
Molded-case circuit breaker (MCCB)
(Note 3) Magnetic contactor (MC)
(Note 1)
Line noise filter (FR-BLF)
L21 L11
MR Configurator2
CN5
CN6
CN3
To RS-422/RS-485 communication controller, parameter unit, etc.
CN8
CN1
CN2
CN2L (Note 4) CN4
Battery
Analog monitor
Junction terminal block
Personal computer
To safety relay or MR-J3-D05 safety logic unit
L3 L2 L1
Power factor improving DC reactor (FR-HEL-H)
P3
P4
(Note 5)
C
P+
Regenerative option
WVU
Servo motor
Note 1. The power factor improving AC reactor can also be used. In this case, the power factor improving DC reactor cannot be used.
2. Refer to section 1.3 for the power supply specification.
3. Depending on the main circuit voltage and operation pattern, bus voltage decreases, and that may cause the forced stop
4. This is for MR-J4-_A4-RJ servo amplifier. MR-J4-_A4 servo amplifier does not have CN2L connector. When using MR-J4-_A4-
5. When using the regenerative option, refer to section 11.2.
When not using the power factor improving DC reactor, short P3 and P4.
deceleration to shift to the dynamic brake deceleration. When dynamic brake deceleration is not required, slow the time to turn off the magnetic contactor.
RJ servo amplifier in the linear servo system or in the fully closed loop system, connect an external encoder to this connector. Refer to Table 1.1 and "Linear Encoder Instruction Manual" for the compatible external encoders.
1 - 51
1. FUNCTIONS AND CONFIGURATION
(f) MR-J4-22KA4(-RJ)
(Note 2) Power supply
Molded-case circuit breaker (MCCB)
(Note 3) Magnetic contactor (MC)
Line noise filter (FR-BLF)
RS T
(Note 1)
L21
L11
MR Configurator2
CN5
CN6
CN3
To RS-422/RS-485 communication controller, parameter unit, etc.
CN8
CN1
CN2
CN2L (Note 4)
CN4
Analog monitor
Junction terminal block
Battery
Personal computer
To safety relay or MR-J3-D05 safety logic unit
L3 L2 L1
Power factor improving DC reactor (FR-HEL-H)
P3
P4
(Note 5)
C
P+
Regenerative option
VU
W
Servo motor
Note 1. The power factor improving AC reactor can also be used. In this case, the power factor improving DC reactor cannot be used.
When not using the power factor improving DC reactor, short P3 and P4.
2. Refer to section 1.3 for the power supply specification.
3. Depending on the main circuit voltage and operation pattern, bus voltage decreases, and that may cause the forced stop deceleration to shift to the dynamic brake deceleration. When dynamic brake deceleration is not required, slow the time to turn off the magnetic contactor.
4. This is for MR-J4-_A4-RJ servo amplifier. MR-J4-_A4 servo amplifier does not have CN2L connector. When using MR-J4-_A4­RJ servo amplifier in the linear servo system or in the fully closed loop system, connect an external encoder to this connector. Refer to Table 1.1 and "Linear Encoder Instruction Manual" for the compatible external encoders.
5. When using the regenerative option, refer to section 11.2.
1 - 52
1. FUNCTIONS AND CONFIGURATION
A
(3) 100 V class
The diagram shows MR-J4-20A1-RJ.
RT
(Note 2) Power supply
Molded-case circuit breaker (MCCB)
RS T
CN5
MR Configurator2
Personal computer
(Note 3) Magnetic contactor (MC)
Power factor improving AC reactor (FR-HAL)
Line noise filter (FR-BSF01)
Regenerative option
(Note 1)
L1 L2
P+
C
L11
L21
(Note1)
D (Note 5)
U V
W
CN6
CN3
To RS-422/RS-485 communication controller, parameter unit, etc.
CN8
CN1
CN2
CN2L (Note 4) CN4
Battery
Analog monitor
Junction terminal block
To safety relay or MR-J3-D05 safety logic unit
Servo motor
Note 1. The power factor improving DC reactor cannot be used.
2. For power supply specifications, refer to section 1.3.
3. Depending on the main circuit voltage and operation pattern, bus voltage decreases, and that may cause the forced stop deceleration to shift to the dynamic brake deceleration. When dynamic brake deceleration is not required, slow the time to turn off the magnetic contactor.
4. This is for MR-J4-_A1-RJ servo amplifier. MR-J4-_A1 servo amplifier does not have CN2L connector. Refer to Table 1.1 and Linear Encoder Instruction Manual for the compatible external encoders.
5.
lways connect between P+ and D terminals. When using the regenerative option, refer to section 11.2.
1 - 53
1. FUNCTIONS AND CONFIGURATION
MEMO
1 - 54

2. INSTALLATION

2. INSTALLATION
WARNING
CAUTION
To prevent electric shock, ground each equipment securely.
Stacking in excess of the specified number of product packages is not allowed. Install the equipment on incombustible material. Installing it directly or close to combustibles will lead to a fire. Install the servo amplifier and the servo motor in a load-bearing place in accordance with the Instruction Manual. Do not get on or put heavy load on the equipment. Otherwise, it may cause injury. Use the equipment within the specified environment. For the environment, refer to section 1.3. Provide an adequate protection to prevent screws and other conductive matter, oil and other combustible matter from entering the servo amplifier. Do not block the intake and exhaust areas of the servo amplifier. Otherwise, it may cause a malfunction. Do not drop or strike the servo amplifier. Isolate it from all impact loads. Do not install or operate the servo amplifier which have been damaged or have any parts missing. When the equipment has been stored for an extended period of time, contact your local sales office. When handling the servo amplifier, be careful about the edged parts such as corners of the servo amplifier. The servo amplifier must be installed in the metal cabinet. When fumigants that contain halogen materials such as fluorine, chlorine, bromine, and iodine are used for disinfecting and protecting wooden packaging from insects, they cause malfunction when entering our products. Please take necessary precautions to ensure that remaining materials from fumigant do not enter our products, or treat packaging with methods other than fumigation (heat method). Additionally, disinfect and protect wood from insects before packing products.
POINT
When pulling out CNP1, CNP2, and CNP3 connectors of 100 V class/600 W or lower 200 V class servo amplifier, pull out CN3 and CN8 connectors beforehand.
2 - 1
2. INSTALLATION

2.1 Installation direction and clearances

The equipment must be installed in the specified direction. Otherwise, it may
CAUTION
(1) Installation clearances of the servo amplifier
(a) Installation of one servo amplifier
10 mm or more (Note 2)
cause a malfunction. Leave specified clearances between the servo amplifier and the cabinet walls or other equipment. Otherwise, it may cause a malfunction.
Cabinet Cabinet
40 mm or more
Servo amplifier
10 mm or more
Wiring allowance
80 mm or more
Top
40 mm or more (Note 1)
Note 1. For 11 kW to 22 kW servo amplifiers, the clearance between the bottom and ground will be 120 mm or more.
2. For the MR-J4-500A(-RJ), the clearance between the left side and wall will be 25 mm or more.
Bottom
2 - 2
2. INSTALLATION
(b) Installation of two or more servo amplifiers
POINT
Close mounting is possible depending on the capacity of the servo amplifier. Refer to section 1.3 for availability of close mounting. When mounting the servo amplifiers closely, do not install the servo amplifier whose depth is larger than that of the left side servo amplifier since CNP1, CNP2, and CNP3 connectors cannot be disconnected.
Leave a large clearance between the top of the servo amplifier and the cabinet walls, and install a cooling fan to prevent the internal temperature of the cabinet from exceeding the environment. When mounting the servo amplifiers closely, leave a clearance of 1 mm between the adjacent servo amplifiers in consideration of mounting tolerances. In this case, keep the ambient temperature within 0 °C to 45 °C or use the servo amplifier with 75% or less of the effective load ratio.
Cabinet
Cabinet
100 mm or more
30 mm or more
40 mm or more (Note 1)
Leaving clearance Mounting closely
Note 1. For 11 kW to 22 kW servo amplifiers, the clearance between the bottom and ground will be 120 mm or more.
2. When you install the MR-J4-500A(-RJ) on the right side, the clearance between the left side and wall will be 25 mm or more.
10 mm or more (Note 2)
30 mm or more
1 mm
100 mm or more
1 mm
40 mm or more
30 mm or more
Top
Bottom
(2) Others
When using heat generating equipment such as the regenerative option, install them with full consideration of heat generation so that the servo amplifier is not affected. Install the servo amplifier on a perpendicular wall in the correct vertical direction.
2 - 3
2. INSTALLATION

2.2 Keeping out of foreign materials

(1) When drilling in the cabinet, prevent drill chips and wire fragments from entering the servo amplifier.
(2) Prevent oil, water, metallic dust, etc. from entering the servo amplifier through openings in the cabinet or
a cooling fan installed on the ceiling.
(3) When installing the cabinet in a place where toxic gas, dirt and dust exist, conduct an air purge (force
clean air into the cabinet from outside to make the internal pressure higher than the external pressure) to prevent such materials from entering the cabinet.

2.3 Encoder cable stress

(1) The way of clamping the cable must be fully examined so that bending stress and cable's own weight
stress are not applied to the cable connection.
(2) For use in any application where the servo motor moves, fix the cables (encoder, power supply, and
brake) with having some slack from the connector connection part of the servo motor to avoid putting stress on the connector connection part. Use the optional encoder cable within the bending life range. Use the power supply and brake wiring cables within the bending life of the cables.
(3) Avoid any probability that the cable sheath might be cut by sharp chips, rubbed by a machine corner or
stamped by workers or vehicles.
(4) For installation on a machine where the servo motor moves, the bending radius should be made as large
as possible. Refer to section 10.4 for the bending life.
2 - 4
2. INSTALLATION

2.4 Inspection items

Before starting maintenance and/or inspection, turn off the power and wait for 15 minutes or more until the charge lamp turns off. Then, confirm that the voltage between P+ and N- is safe with a voltage tester and others. Otherwise, an electric
WARNING
CAUTION
It is recommended that the following points periodically be checked.
(1) Check for loose terminal block screws. Retighten any loose screws.
(2) Check the cables and the like for scratches or cracks. Inspect them periodically according to operating
conditions especially when the servo motor is movable.
(3) Check that the connector is securely connected to the servo amplifier.
(4) Check that the wires are not coming out from the connector.
(5) Check for dust accumulation on the servo amplifier.
(6) Check for unusual noise generated from the servo amplifier.
shock may occur. In addition, when confirming whether the charge lamp is off or not, always confirm it from the front of the servo amplifier. To avoid an electric shock, only qualified personnel should attempt inspections. For repair and parts replacement, contact your local sales office.
Do not perform insulation resistance test on the servo amplifier. Otherwise, it may cause a malfunction. Do not disassemble and/or repair the equipment on customer side.
2 - 5
2. INSTALLATION

2.5 Parts having service lives

Service lives of the following parts are listed below. However, the service life vary depending on operating methods and environment. If any fault is found in the parts, they must be replaced immediately regardless of their service lives. For parts replacement, please contact your sales representative.
(1) Smoothing capacitor
The characteristic of smoothing capacitor is deteriorated due to ripple currents, etc. The life of the capacitor greatly depends on ambient temperature and operating conditions. The capacitor will reach the end of its life in 10 years of continuous operation in normal air-conditioned environment (40 °C surrounding air temperature or less).
(2) Relays
Contact faults will occur due to contact wear arisen from switching currents. Relays reach the end of their lives when the power has been turned on and forced stop by EM1 (Forced stop 1) has occurred 100,000 times in total, or when the STO has been turned on and off 1,000,000 times while the servo motor is stopped under servo-off state. However, the lives of relays may depend on the power supply capacity.
(3) Servo amplifier cooling fan
The cooling fan bearings reach the end of their life in 10,000 hours to 30,000 hours. Normally, therefore, the cooling fan must be replaced in a few years of continuous operation as a guideline. It must also be changed if unusual noise or vibration is found during inspection. The life indicates under the yearly average ambient temperature of 40 °C, free from corrosive gas, flammable gas, oil mist, dust and dirt.
Part name Life guideline
Smoothing capacitor 10 years
Number of power-on and forced stop by EM1
Relay
Cooling fan 10,000 hours to 30,000 hours (2 years to 3 years) Absolute position battery Refer to section 12.2.
(Forced stop 1) times: 100,000 times Number of on and off for STO: 1,000,000 times
2 - 6

3. SIGNALS AND WIRING

r
3. SIGNALS AND WIRING
Any person who is involved in wiring should be fully competent to do the work. Before wiring, turn off the power and wait for 15 minutes or more until the charge lamp turns off. Then, confirm that the voltage between P+ and N- is safe with a voltage tester and others. Otherwise, an electric shock may occur. In addition, when confirming whether the charge lamp is off or not, always confirm it from the front of the servo amplifier.
WARNING
Ground the servo amplifier and servo motor securely. Do not attempt to wire the servo amplifier and servo motor until they have been installed. Otherwise, it may cause an electric shock. The cables should not be damaged, stressed, loaded, or pinched. Otherwise, it may cause an electric shock. To avoid an electric shock, insulate the connections of the power supply terminals.
Wire the equipment correctly and securely. Otherwise, the servo motor may operate unexpectedly, resulting in injury. Connect cables to the correct terminals. Otherwise, a burst, damage, etc. may occur. Ensure that polarity (+/-) is correct. Otherwise, a burst, damage, etc. may occur. The surge absorbing diode installed to the DC relay for control output should be fitted in the specified direction. Otherwise, the emergency stop and other protective circuits may not operate.
Servo amplifier
DOCOM
24 V DC
Servo amplifie
DOCOM
24 V DC
CAUTION
Control output signal
For sink output interface
RA
Control output signal
For source output interface
RA
Use a noise filter, etc. to minimize the influence of electromagnetic interference. Electromagnetic interference may be given to the electronic equipment used near the servo amplifier. Do not install a power capacitor, surge killer or radio noise filter (optional FR-BIF­(H)) with the power line of the servo motor. When using the regenerative resistor, switch power off with the alarm signal. Otherwise, a transistor fault or the like may overheat the regenerative resistor, causing a fire. Do not modify the equipment. Connect the servo amplifier power output (U, V, and W) to the servo motor power input (U, V, and W) directly. Do not let a magnetic contactor, etc. intervene. Otherwise, it may cause a malfunction.
Servo amplifier
U
V
W
Servo motor
U
V
W
Servo motorServo amplifier
U
M
V
W
U
V
W
Connecting a servo motor of the wrong axis to U, V, W, or CN2 of the servo amplifier may cause a malfunction.
M
3 - 1
3. SIGNALS AND WIRING
POINT
When you use a linear servo motor, replace the following left words to the right words. Load to motor inertia ratio Load to motor mass ratio Torque → Thrust (Servo motor) speed (Linear servo motor) speed

3.1 Input power supply circuit

Always connect a magnetic contactor between the power supply and the main circuit power supply (L1, L2, and L3) of the servo amplifier, in order to configure a circuit that shuts down the power supply on the side of the servo amplifier’s power supply. If a magnetic contactor is not connected, continuous flow of a large current may cause a fire when the servo amplifier malfunctions. Use ALM (Malfunction) to switch main circuit power supply off. Not doing so may cause a fire when a regenerative transistor malfunctions or the like may overheat the regenerative resistor. Check the servo amplifier model, and then input proper voltage to the servo
CAUTION
amplifier power supply. If input voltage exceeds the upper limit of the specification, the servo amplifier will break down. The servo amplifier has a built-in surge absorber (varistor) to reduce noise and to suppress lightning surge. The varistor can break down due to its aged deterioration. To prevent a fire, use a molded-case circuit breaker or fuse for input power supply. Connecting a servo motor of the wrong axis to U, V, W, or CN2 of the servo amplifier may cause a malfunction. The N- terminal is not a neutral point of the power supply. Incorrect wiring will cause a burst, damage, etc.
POINT
EM2 has the same function as EM1 in the torque control mode. Connect the 1-phase 200 V AC to 240 V AC power supply to L1 and L3. One of the connecting destinations is different from MR-J3 Series Servo Amplifier's. When using MR-J4 as a replacement for MR-J3, be careful not to connect the power to L2.
Configure the wirings so that the main circuit power supply is shut off and SON (Servo-on) is turned off after deceleration to a stop due to an alarm occurring, enabled servo forced stop, etc. A molded-case circuit breaker (MCCB) must be used with the input cables of the main circuit power supply.
3 - 2
3. SIGNALS AND WIRING
A

3.1.1 200 V class

(1) For 3-phase 200 V AC to 240 V AC power supply of MR-J4-10A(-RJ) to MR-J4-350A(-RJ)
3-phase 200 V AC to 240 V AC
MCCB
Malfunction
RA1
(Note 6)
EMG stop switch
MC
(Note 1)(Note 9)
(Note 2)
OFF
Servo amplifier
CNP1
L1 L2 L3 N­P3 P4
CNP2
P+ C D L11 L21
ON
MC
(Note 10)
CNP3
U V
W
(Note 10)
CN2
MC
SK
(Note 5)
(Note 3)
Encoder cable
U V
W
Servo motor
Motor
M
Encoder
(Note 7) Main circuit power supply
(Note 4)
Note 1. Between P3 and P4 is connected by default. When using the power factor improving DC reactor, remove the short bar
between P3 and P4. Refer to section 11.11 for details. Additionally, a power factor improving DC reactor and power factor improving AC reactor cannot be used simultaneously.
2.
3. For the encoder cable, use of the option cable is recommended. For selecting cables, refer to "Servo Motor Instruction Manual
4. This diagram shows sink I/O interface. For source I/O interface, refer to section 3.9.3.
5. For connecting servo motor power wires, refer to "Servo Motor Instruction Manual (Vol. 3)".
6. Use a magnetic contactor with an operation delay time (interval between current being applied to the coil until closure of
7. Configure a circuit to turn off EM2 when the main circuit power is turned off to prevent an unexpected restart of the servo
8. When not using the STO function, attach the short-circuit connector came with a servo amplifier.
9. When wires used for L11 and L21 are thinner than wires used for L1, L2, and L3, use a molded-case circuit breaker. (Refer to
10. Connecting a servo motor of the wrong axis to U, V, W, or CN2 of the servo amplifier may cause a malfunction.
11. The illustration of the 24 V DC power supply is divided between input signal and output signal for convenience. However, they
lways connect between P+ and D terminals (factory-wired). When using the regenerative option, refer to section 11.2.
(Vol. 3)".
contacts) of 80 ms or less. Depending on the main circuit voltage and operation pattern, bus voltage decreases, and that may cause the forced stop deceleration to shift to the dynamic brake deceleration. When dynamic brake deceleration is not required, slow the time to turn off the magnetic contactor.
amplifier.
section 11.10.)
can be configured by one.
Forced stop 2 Servo-on
24 V DC (Note 11)
(Note 8) Short-circuit connector (Packed with the servo amplifier)
CN1
EM2
SON
DICOM
CN8
24 V DC (Note 11)
CN1
DOCOM
ALM
RA1
Malfunction
(Note 4)
3 - 3
3. SIGNALS AND WIRING
A
(2) For 1-phase 200 V AC to 240 V AC power supply of MR-J4-10A(-RJ) to MR-J4-70A(-RJ)
POINT
Connect the 1-phase 200 V AC to 240 V AC power supply to L1 and L3. One of the connecting destinations is different from MR-J3 Series Servo Amplifier's. When using MR-J4 as a replacement for MR-J3, be careful not to connect the power to L2.
1-phase 200 V AC to 240 V AC
(Note 4)
MCCB
(Note 9)
(Note 7) Main circuit power supply
Forced stop 2 Servo-on
(Note 8) Short-circuit connector (Packed with the servo amplifier)
Malfunction
RA1
EMG stop switch
(Note 6)
MC
(Note 1)
(Note 2)
24 V DC (Note 11)
OFF
Servo amplifier
CNP1
L1 L2 L3 N­P3 P4
CNP2
P+ C D L11 L21
CN1
EM2
SON
DICOM
CN8
ON
MC
(Note 10)
CNP3
U
V
W
(Note 10)
CN2
CN1
DOCOM
ALM
MC
SK
(Note 5)
(Note 3)
Encoder cable
24 V DC (Note 11)
RA1
Malfunction
Servo motor
U V
W
Encoder
Motor
M
(Note 4)
Note 1. Between P3 and P4 is connected by default. When using the power factor improving DC reactor, remove the short bar
between P3 and P4. Refer to section 11.11 for details. Additionally, a power factor improving DC reactor and power factor improving AC reactor cannot be used simultaneously.
2.
3. For the encoder cable, use of the option cable is recommended. For selecting cables, refer to "Servo Motor Instruction Manual
4. This diagram shows sink I/O interface. For source I/O interface, refer to section 3.9.3.
5. For connecting servo motor power wires, refer to "Servo Motor Instruction Manual (Vol. 3)".
6. Use a magnetic contactor with an operation delay time (interval between current being applied to the coil until closure of
7. Configure a circuit to turn off EM2 when the main circuit power is turned off to prevent an unexpected restart of the servo
8. When not using the STO function, attach the short-circuit connector came with a servo amplifier.
9. When wires used for L11 and L21 are thinner than wires used for L1, and L3, use a molded-case circuit breaker. (Refer to
10. Connecting a servo motor of the wrong axis to U, V, W, or CN2 of the servo amplifier may cause a malfunction.
11. The illustration of the 24 V DC power supply is divided between input signal and output signal for convenience. However, they
lways connect between P+ and D terminals (factory-wired). When using the regenerative option, refer to section 11.2.
(Vol. 3)".
contacts) of 80 ms or less. Depending on the main circuit voltage and operation pattern, bus voltage decreases, and that may cause the forced stop deceleration to shift to the dynamic brake deceleration. When dynamic brake deceleration is not required, slow the time to turn off the magnetic contactor.
amplifier.
section 11.10.)
can be configured by one.
3 - 4
3. SIGNALS AND WIRING
A
(3) MR-J4-500A(-RJ)
MCCB
3-phase 200 V AC to 240 V AC
Malfunction
RA1
(Note 6)
EMG stop switch
MC
OFF
Servo amplifier
L1 L2 L3 N-
ON
MC
(Note 10)
U V
W
SK
(Note 5)
MC
Servo motor
U
Motor
V
W
M
(Note 9)
(Note 1)
(Note 2)
(Note 7) Main circuit power supply
(Note 4)
Note 1. Between P3 and P4 is connected by default. When using the power factor improving DC reactor, remove the short bar
between P3 and P4. Refer to section 11.11 for details. Additionally, a power factor improving DC reactor and power factor improving AC reactor cannot be used simultaneously.
2.
3. For the encoder cable, use of the option cable is recommended. For selecting cables, refer to "Servo Motor Instruction Manual
4. This diagram shows sink I/O interface. For source I/O interface, refer to section 3.9.3.
5. For connecting servo motor power wires, refer to "Servo Motor Instruction Manual (Vol. 3)".
6. Use a magnetic contactor with an operation delay time (interval between current being applied to the coil until closure of
7. Configure a circuit to turn off EM2 when the main circuit power is turned off to prevent an unexpected restart of the servo
8. When not using the STO function, attach the short-circuit connector came with a servo amplifier.
9. When wires used for L11 and L21 are thinner than wires used for L1, L2, and L3, use a molded-case circuit breaker. (Refer to
10. Connecting a servo motor of the wrong axis to U, V, W, or CN2 of the servo amplifier may cause a malfunction.
11. The illustration of the 24 V DC power supply is divided between input signal and output signal for convenience. However, they
lways connect between P+ and D terminals (factory-wired). When using the regenerative option, refer to section 11.2.
(Vol. 3)".
contacts) of 80 ms or less. Depending on the main circuit voltage and operation pattern, bus voltage decreases, and that may cause the forced stop deceleration to shift to the dynamic brake deceleration. When dynamic brake deceleration is not required, slow the time to turn off the magnetic contactor.
amplifier.
section 11.10.)
can be configured by one.
Forced stop 2 Servo-on
24 V DC (Note 11)
(Note 8) Short-circuit connector (Packed with the servo amplifier)
L11 L21
P3 P4 P+ C
D
CN1
EM2 SON
DICOM
CN8
(Note 10)
CN2
CN1
DOCOM
ALM
(Note 3)
Encoder cable
24 V DC (Note 11)
RA1
Encoder
Malfunction
(Note 4)
3 - 5
3. SIGNALS AND WIRING
(4) MR-J4-700A(-RJ)
MCCB
3-phase 200 V AC to 240 V AC
(Note 9)
Malfunction
RA1
(Note 6)
EMG stop switch
MC
(Note 2)
OFF
Servo amplifier
L1
Built-in
L2
regenerative resistor
L3 P+
C
L11 L21
ON
MC
(Note 10)
U V
W
(Note 5)
MC
SK
Servo motor
U
V
W
Motor
M
N-
(Note 1)
(Note 7) Main circuit power supply
(Note 4)
Note 1. Between P3 and P4 is connected by default. When using the power factor improving DC reactor, remove the short bar
between P3 and P4. Refer to section 11.11 for details. Additionally, a power factor improving DC reactor and power factor improving AC reactor cannot be used simultaneously.
2. When using the regenerative option, refer to section 11.2.
3. For the encoder cable, use of the option cable is recommended. For selecting cables, refer to "Servo Motor Instruction Manual (Vol. 3)".
4. This diagram shows sink I/O interface. For source I/O interface, refer to section 3.9.3.
5. For connecting servo motor power wires, refer to "Servo Motor Instruction Manual (Vol. 3)".
6. Use a magnetic contactor with an operation delay time (interval between current being applied to the coil until closure of contacts) of 80 ms or less. Depending on the main circuit voltage and operation pattern, bus voltage decreases, and that may cause the forced stop deceleration to shift to the dynamic brake deceleration. When dynamic brake deceleration is not required, slow the time to turn off the magnetic contactor.
7. Configure a circuit to turn off EM2 when the main circuit power is turned off to prevent an unexpected restart of the servo amplifier.
8. When not using the STO function, attach the short-circuit connector came with a servo amplifier.
9. When wires used for L11 and L21 are thinner than wires used for L1, L2, and L3, use a molded-case circuit breaker. (Refer to section 11.10.)
10. Connecting a servo motor of the wrong axis to U, V, W, or CN2 of the servo amplifier may cause a malfunction.
11. The illustration of the 24 V DC power supply is divided between input signal and output signal for convenience. However, they can be configured by one.
Forced stop 2 Servo-on
24 V DC (Note 11)
(Note 8) Short-circuit connector (Packed with the servo amplifier)
P3
P4
CN1
EM2 SON
DICOM
CN8
(Note 10)
CN2
CN1
DOCOM
ALM
(Note 3)
Encoder cable
24 V DC (Note 11)
RA1
Encoder
Malfunction
(Note 4)
3 - 6
3. SIGNALS AND WIRING
2
2
p
g
(
g
g
q
p
g
)
g
y
g
g
y
p
(5) MR-J4-11KA(-RJ)/MR-J4-15KA(-RJ)/MR-J4-22KA(-RJ)
3-phase
00 V AC to 40 V AC
MCCB
(Note 9)
Malfunction
RA1
(Note 6)
Regenerative
EMG stop switch
MC
resistor
(Note 2)
OFF
Servo amplifier
L1 L2 L3 P+
C
L11 L21
ON
MC
(Note 10)
U V
W
MC
SK
(Note 14, 15) External dynamic brake (optional)
(Note 5)
Servo motor
U V
W
Motor
M
(Note 13) Cooling fan power supply
MCCB
(Note 10)
CN2
CN1
DOCOM
ALM
(Note 3)
Encoder cable
24 V DC (Note 11)
RA1
Encoder
Cooling fan
Malfunction
BU BV
BW
(Note 12)
(Note 4)
(Note 4)
(Note 7) Main circuit power supply
Forced stop 2 Servo-on
24 V DC (Note 11)
(Note 8) Short-circuit connector (Packed with the servo amplifier)
(Note 1)
N-
P3
P4
CN1
EM2
SON
DICOM
CN8
Note 1. Between P3 and P4 is connected by default. When using the power factor improving DC reactor, remove the short bar
between P3 and P4. Refer to section 11.11 for details. Additionally, a power factor improving DC reactor and power factor
roving AC reactor cannot be used simultaneously.
2. When usin
im
the regenerative option, refer to section 11.2.
3. For the encoder cable, use of the option cable is recommended. For selecting cables, refer to "Servo Motor Instruction Manual
Vol. 3)".
4. This dia
5. For connectin
ram shows sink I/O interface. For source I/O interface, refer to section 3.9.3.
servo motor power wires, refer to "Servo Motor Instruction Manual (Vol. 3)".
6. Use a magnetic contactor with an operation delay time (interval between current being applied to the coil until closure of contacts) of 80 ms or less. Depending on the main circuit voltage and operation pattern, bus voltage decreases, and that may cause the forced stop deceleration to shift to the dynamic brake deceleration. When dynamic brake deceleration is not
uired, slow the time to turn off the magnetic contactor.
re
7. Configure a circuit to turn off EM2 when the main circuit power is turned off to prevent an unexpected restart of the servo
lifier.
8. When not usin
am
the STO function, attach the short-circuit connector came with a servo amplifier.
9. When wires used for L11 and L21 are thinner than wires used for L1, L2, and L3, use a molded-case circuit breaker. (Refer to
10. Connectin
section 11.10.
a servo motor of the wrong axis to U, V, W, or CN2 of the servo amplifier may cause a malfunction.
11. The illustration of the 24 V DC power supply is divided between input signal and output signal for convenience. However, the can be configured by one.
12. For the servo motor with a coolin
13. For the coolin
fan power supply, refer to "Servo Motor Instruction Manual (Vol. 3)".
fan.
14. Use an external dynamic brake for this servo amplifier. Failure to do so will cause an accident because the servo motor dose not stop immediately but coasts at an alarm occurrence for which the servo motor does not decelerate to stop. Ensure the safety in the entire equipment. For alarms for which the servo motor does not decelerate to stop, refer to chapter 8. For wiring of the external d
namic brake, refer to section 11.17.
15. The external dynamic brake cannot be used for compliance with SEMI-F47 standard. Do not assign DB (Dynamic brake interlock) in [Pr. PD23] to [Pr. PD26], [Pr. PD28], and [Pr. PD47]. Failure to do so will cause the servo amplifier to become servo-off when an instantaneous
ower failure occurs.
3 - 7
3. SIGNALS AND WIRING
A

3.1.2 400 V class

(1) MR-J4-60A4(-RJ) to MR-J4-350A4(-RJ)
Malfunction
RA1
(Note 11) Step-down transformer
MCCB
3-phase 380 V AC to 480 V AC
Emergency stop switch
(Note 6)
MC
(Note 1)(Note 9)
(Note 2)
CNP1
N­L1
L2 L3 P3 P4
CNP2
P+ C D L11 L21
OFF
Servo amplifier
(Note 10)
CNP3
(Note 10)
ON
MC
U
V
W
CN2
MC
SK
(Note 5)
(Note 3)
Encoder cable
Servo motor
U
V
W
Encoder
Motor
M
(Note 7) Main circuit power supply
(Note 4)
Note 1. Between P3 and P4 is connected by default. When using the power factor improving DC reactor, remove the short
2.
3. For the encoder cable, use of the option cable is recommended. For selecting cables, refer to "Servo Motor
4. This diagram is for sink I/O interface. For source I/O interface, refer to section 3.9.3.
5. For connecting servo motor power wires, refer to "Servo Motor Instruction Manual (Vol. 3)".
6. Use a magnetic contactor with an operation delay time (interval between current being applied to the coil until
7. Configure a circuit to turn off EM2 when the main circuit power is turned off to prevent an unexpected restart of the
8. When not using the STO function, attach the short-circuit connector came with a servo amplifier.
9. When wires used for L11 and L21 are thinner than wires used for L1, L2, and L3, use a molded-case circuit
10. Connecting a servo motor for different axis to U, V, W, or CN2 of the servo amplifier may cause a malfunction.
11. Stepdown transformer is required when the coil voltage of the magnetic contactor is 200 V class.
12. The illustration of the 24 V DC power supply is divided between input signal and output signal for convenience.
Forced stop 2 Servo-on
24 V DC (Note 12)
(Note 8) Short-circuit connector (Packed with the servo amplifier)
bar between P3 and P4. Refer to section 11.11 for details. Additionally, a power factor improving DC reactor and power factor improving AC reactor cannot be used simultaneously.
lways connect between P+ and D terminals. (factory-wired) When using the regenerative option, refer to section
11.2.
Instruction Manual (Vol. 3)".
closure of contacts) of 80 ms or less. Depending on the main circuit voltage and operation pattern, bus voltage decreases, and that may cause the forced stop deceleration to shift to the dynamic brake deceleration. When dynamic brake deceleration is not required, slow the time to turn off the magnetic contactor.
servo amplifier.
breaker. (Refer to section 11.10.)
However, they can be configured by one.
CN1
EM2 SON
DICOM
CN8
CN1
DOCOM
ALM
24 V DC (Note 12)
RA1
Malfunction
(Note 4)
3 - 8
3. SIGNALS AND WIRING
(2) MR-J4-500A4(-RJ)/MR-J4-700A4(-RJ)
Malfunction
RA1
(Note 11) Step-down
3-phase 380 V AC to 480 V AC
transformer
MCCB
(Note 9)
(Note 6)
OFF
Emergency stop switch
Servo amplifier Servo motor
MC
(Note 2)
L1 L2
regenerative
L3 P+
C
L11 L21
Built-in
resistor
ON
MC
(Note 10)
U
V
W
MC
SK
(Note 5)
U
Motor
V
W
M
N-
(Note 1)
(Note 7) Main circuit power supply
(Note 4)
Note 1. Between P3 and P4 is connected by default. When using the power factor improving DC reactor, remove the short
2. When using the regenerative option, refer to section 11.2.
3. For the encoder cable, use of the option cable is recommended. For selecting cables, refer to "Servo Motor
4. This diagram is for sink I/O interface. For source I/O interface, refer to section 3.9.3.
5. For connecting servo motor power wires, refer to "Servo Motor Instruction Manual (Vol. 3)".
6. Use a magnetic contactor with an operation delay time (interval between current being applied to the coil until
7. Configure a circuit to turn off EM2 when the main circuit power is turned off to prevent an unexpected restart of the
8. When not using the STO function, attach the short-circuit connector came with a servo amplifier.
9. When wires used for L11 and L21 are thinner than wires used for L1, L2, and L3, use a molded-case circuit
10. Connecting a servo motor for different axis to U, V, W, or CN2 of the servo amplifier may cause a malfunction.
11. Stepdown transformer is required when the coil voltage of the magnetic contactor is 200 V class.
12. The illustration of the 24 V DC power supply is divided between input signal and output signal for convenience.
Forced stop 2 Servo-on
24 V DC (Note 12)
(Note 8) Short-circuit connector (Packed with the servo amplifier)
bar between P3 and P4. Refer to section 11.11 for details. Additionally, a power factor improving DC reactor and power factor improving AC reactor cannot be used simultaneously.
Instruction Manual (Vol. 3)".
closure of contacts) of 80 ms or less. Depending on the main circuit voltage and operation pattern, bus voltage decreases, and that may cause the forced stop deceleration to shift to the dynamic brake deceleration. When dynamic brake deceleration is not required, slow the time to turn off the magnetic contactor.
servo amplifier.
breaker. (Refer to section 11.10.)
However, they can be configured by one.
P3
P4
CN1 EM2
SON
DICOM
CN8
(Note 10)
CN2
CN1
DOCOM
ALM
(Note 3)
Encoder cable
24 V DC (Note 12)
RA1
Encoder
Malfunction
(Note 4)
3 - 9
3. SIGNALS AND WIRING
(3) MR-J4-11KA4(-RJ) to MR-J4-22KA4(-RJ)
Malfunction
RA1
Emergency stop switch
(Note 6)
MC
Regenerative
resistor
(Note 2)
3-phase 380 V AC to 480 V AC
(Note 11) Step-down transformer
MCCB
(Note 9)
OFF
Servo amplifier Servo motor
L1 L2 L3 P+
C
L11 L21
ON
MC
(Note 10)
U V W
MC
SK
(Note 15, 16)
External
dynamic brake
(optional)
(Note 5)
U
Motor
V
M
W
(Note 13)
Cooling fan
power supply
MCCB
(Note 10)
CN2
CN1
DOCOM
ALM
(Note 3)
Encoder cable
24 V DC (Note 14)
RA1
Encoder
Cooling fan
Malfunction
BU BV
BW
(Note 12)
(Note 4)
(Note 4)
(Note 7)
Forced stop 2 Servo-on
Main circuit power supply
(Note 8) Short-circuit connector (Packed with the servo amplifier)
(Note 1)
24 V DC (Note 14)
N-
P3
P4
CN1
EM2 SON
DICOM
CN8
Note 1. Between P3 and P4 is connected by default. When using the power factor improving DC reactor, remove the short bar
between P3 and P4. Refer to section 11.11 for details. Additionally, a power factor improving DC reactor and power factor improving AC reactor cannot be used simultaneously.
2. When using the regenerative option, refer to section 11.2.
3. For the encoder cable, use of the option cable is recommended. For selecting cables, refer to "Servo Motor Instruction Manual (Vol. 3)".
4. This diagram is for sink I/O interface. For source I/O interface, refer to section 3.9.3.
5. For connecting servo motor power wires, refer to "Servo Motor Instruction Manual (Vol. 3)".
6. Use a magnetic contactor with an operation delay time (interval between current being applied to the coil until closure of contacts) of 80 ms or less. Depending on the main circuit voltage and operation pattern, bus voltage decreases, and that may cause the forced stop deceleration to shift to the dynamic brake deceleration. When dynamic brake deceleration is not required, slow the time to turn off the magnetic contactor.
7. Configure a circuit to turn off EM2 when the main circuit power is turned off to prevent an unexpected restart of the servo amplifier.
8. When not using the STO function, attach the short-circuit connector came with a servo amplifier.
9. When wires used for L11 and L21 are thinner than wires used for L1, L2, and L3, use a molded-case circuit breaker. (Refer to section 11.10.)
10. Connecting a servo motor for different axis to U, V, W, or CN2 of the servo amplifier may cause a malfunction.
11. Stepdown transformer is required when the coil voltage of the magnetic contactor is 200 V class.
12. For the servo motor with a cooling fan.
13. For the cooling fan power supply, refer to "Servo Motor Instruction Manual (Vol. 3)".
14. The illustration of the 24 V DC power supply is divided between input signal and output signal for convenience. However, they can be configured by one.
15. Use an external dynamic brake for this servo amplifier. Failure to do so will cause an accident because the servo motor does not stop immediately but coasts at an alarm occurrence for which the servo motor does not decelerate to stop. Ensure the safety in the entire equipment. For alarms for which the servo motor does not decelerate to stop, refer to chapter 8. For wiring of the external dynamic brake, refer to section 11.17.
16. The external dynamic brake cannot be used for compliance with SEMI-F47 standard. Do not assign DB (Dynamic brake interlock) in [Pr. PD23] to [Pr. PD26], [Pr. PD28], and [Pr. PD47]. Failure to do so will cause the servo amplifier to become servo-off when an instantaneous power failure occurs.
3 - 10
3. SIGNALS AND WIRING
A

3.1.3 100 V class

1-phase 100 V AC to 120 V AC
MCCB
(Note 9)
Malfunction
RA1
(Note 6)
EMG stop switch
MC
(Note 2)
OFF
Servo amplifier
CNP1
L1 Unassigned L2 N­Unassigned Unassigned
CNP2
P+ C D L11 L21
ON
MC
(Note 10)
CNP3
U V
W
(Note 10)
CN2
MC
SK
(Note 5)
(Note 3)
Encoder cable
Servo motor
U V
W
Encoder
Motor
M
(Note 7) Main circuit power supply
(Note 4)
Note 1. The power factor improving DC reactor cannot be used.
2.
3. For the encoder cable, use of the option cable is recommended. For selecting cables, refer to "Servo Motor Instruction Manual
4. This diagram shows sink I/O interface. For source I/O interface, refer to section 3.9.3.
5. For connecting servo motor power wires, refer to "Servo Motor Instruction Manual (Vol. 3)".
6. Use a magnetic contactor with an operation delay time (interval between current being applied to the coil until closure of
7. Configure a circuit to turn off EM2 when the main circuit power is turned off to prevent an unexpected restart of the servo
8. When not using the STO function, attach the short-circuit connector came with a servo amplifier.
9. When wires used for L11 and L21 are thinner than wires used for L1 and L2, use a molded-case circuit breaker. (Refer to
10. Connecting a servo motor of the wrong axis to U, V, W, or CN2 of the servo amplifier may cause a malfunction.
11. The illustration of the 24 V DC power supply is divided between input signal and output signal for convenience. However, they
lways connect between P+ and D terminals (factory-wired). When using the regenerative option, refer to section 11.2.
(Vol. 3)".
contacts) of 80 ms or less. Depending on the main circuit voltage and operation pattern, bus voltage decreases, and that may cause the forced stop deceleration to shift to the dynamic brake deceleration. When dynamic brake deceleration is not required, slow the time to turn off the magnetic contactor.
amplifier.
section 11.10.)
can be configured by one.
Forced stop 2 Servo-on
24 V DC (Note 11)
(Note 8) Short-circuit connector (Packed with the servo amplifier)
CN1
EM2 SON
DICOM
CN8
24 V DC (Note 11)
CN1
DOCOM
ALM
RA1
Malfunction
(Note 4)
3 - 11
3. SIGNALS AND WIRING
r

3.2 I/O signal connection example

3.2.1 Position control mode

(1) Sink I/O interface
(Note 4)
Positioning module
(Note 3, 5)
(Note 5)
Analog torque limit +10 V/maximum torque
(Note 9) MR Configurator2
+
RD75D
CLEARCOM
CLEAR
RDYCOM
READY PULSE F+ PULSE F-
PULSE R+
PULSE R-
PG0
PG0 COM
Forced stop 2 Servo-on Reset Proportion control
External torque limit selection Forward rotation stroke end
Reverse rotation stroke end
Upper limit setting
Personal computer
24 V DC
14 13 12 11 15 16 17 18
9
10
(Note 11)
10 m or less (Note 8)
10 m or less
(Note 13) Main circuit power supply
(Note 4) 24 V DC
2 m or less
(Note 10)
USB cable
(Note 12) Short-circuit connector
(Packed with the servo amplifier)
(option)
DICOM
DOCOM
CR
RD
PP
PG
NP
NG
LZ
LZR
LG SD
EM2 SON RES
PC
TL LSP LSN
DICOM
P15R
TLA
LG 28
SD
Servo amplifie
(Note 7)
20
CN1
47 DOCOM
48 ALM
(Note 7) CN1
46 41
23 ZSP
25 TLC
49 10
24 INP
11 35 36
8 9 3
Plate
34 LG 33
Plate
(Note 7) CN1
42 15
(Note 7)
CN6
19 17 18 43 44 21
1
27
Plate
CN5
CN8
4
LA 5 LAR 6LB 7
LBR
OP SD
2 m or less
3 MO1 1LG 2
MO2
2 m or less
(Note 1)
(Note 4)
24 V DC
(Note 2)
RA1
RA2
RA3
RA4
10 m or less
Malfunction (Note 6)
Zero speed detection
Limiting torque
In-position
Encoder A-phase pulse (differential line driver)
Encoder B-phase pulse (differential line driver)
Control common
Control common
Encoder Z-phase pulse (open collector)
Analog monitor 1
DC ± 10 V DC ± 10 V
Analog monitor 2
(Note 12)
(Note 16)
3 - 12
3. SIGNALS AND WIRING
A
r
Note 1. To prevent an electric shock, always connect the protective earth (PE) terminal (marked ) of the servo amplifier to the
protective earth (PE) of the cabinet.
2. Connect the diode in the correct direction. If it is connected reversely, the servo amplifier will malfunction and will not output signals, disabling EM2 (Forced stop 2) and other protective circuits.
3. The forced stop switch (normally closed contact) must be installed.
4. Supply 24 V DC ± 10% to interfaces from outside. The total current capacity is up to 500 mA. 500 mA is the value applicable when all I/O signals are used. The current capacity can be decreased by reducing the number of I/O points. Refer to section
3.9.2 (1) that gives the current value necessary for the interface. The illustration of the 24 V DC power supply is divided between input signal and output signal for convenience. However, they can be configured by one.
5. When starting operation, always turn on EM2 (Forced stop 2), LSP (Forward rotation stroke end) and LSN (Reverse rotation stroke end). (Normally closed contact)
6.
7. The pins with the same signal name are connected in the servo amplifier.
8. This length applies to the command pulse train input in the differential line driver type. It is 2 m or less in the open-collector
9. Use SW1DNC-MRC2-_. (Refer to section 11.7.)
10. Controller or parameter units can also be connected via the CN3 connector, enabling RS-422/RS-485 communication. Note
LM (Malfunction) turns on in normal alarm-free condition. When this signal (normally closed contact) is switched off (at
occurrence of an alarm), the output of the programmable controller should be stopped by the sequence program.
type.
that using the USB communication function (CN5 connector) prevents the RS-422/RS-485 communication function (CN3 connector) from being used, and vice versa. They cannot be used together.
RS-422/RS-485
compatible
controller
Servo amplifie
MR-PRU03
or
parameter unit
PRU03
10BASE-T cable, etc. (EIA568-compliant)
11. This connection is not required for RD75D. However, to enhance noise tolerance, it is recommended to connect LG of servo amplifier and control common depending on the positioning module.
12. When not using the STO function, attach the short-circuit connector came with a servo amplifier.
13. Configure a circuit to turn off EM2 when the main circuit power is turned off to prevent an unexpected restart of the servo amplifier.
14. Plus and minus of the power of source interface are the opposite of those of sink interface.
15. CLEAR and CLEARCOM of source interface are interchanged to sink interface.
16. When a command cable for connection with the controller side malfunctions due to disconnection or noise, a position mismatch can occur. To avoid position mismatch, it is recommended that Encoder A-phase pulse and Encoder B-phase pulse be checked.
CN3
3 - 13
3. SIGNALS AND WIRING
(2) Source I/O interface
POINT
For notes, refer to (1) in this section.
(Note 4, 14)
24 V DC
Positioning module
RD75D
(Note 15)
(Note 3, 5)
(Note 5)
Analog torque limit +10 V/maximum torque
(Note 9) MR Configurator2
+
+
CLEAR
CLEARCOM
RDYCOM
READY
PULSE F+
PULSE F­PULSE R+ PULSE R-
PG0
PG0 COM
Forced stop 2 Servo-on Reset Proportion control
External torque limit selection Forward rotation stroke end
Reverse rotation stroke end
Upper limit setting
Personal computer
13 14 12 11 15 16 17 18
9
10
(Note 11)
10 m or less (Note 8)
10 m or less
(Note 13) Main circuit power supply
(Note 4, 14) 24 V DC
2 m or less
(Note 10)
USB cable
(Note 12) Short-circuit connector
(Packed with the servo amplifier)
(option)
DICOM
DOCOM
CR
RD PP PG NP NG
LZ
LZR
LG SD
EM2 SON RES
PC
TL LSP LSN
DICOM
P15R
TLA
LG 28 SD
Servo amplifier
(Note 7)
CN1
(Note 7) CN1
20 46 41
47
48 ALM
23 ZSP
25 TLC
49 10
24 INP
11 35 36
8 9 3
4 5 LAR 6LB 7
Plate
34 LG 33
Plate
(Note 7) CN1
42 15
(Note 7)
19
CN6
17 18 43
3 MO1 1LG
2 44 21
1
27
Plate
CN5
CN8
DOCOM
LA
LBR
OP SD
2 m or less
MO2
2 m or less
(Note 1)
(Note 4, 14) 24 V DC
(Note 2)
RA1
RA1
RA2
RA2
RA3
RA3
RA4
RA4
10 m or less
Malfunction (Note 6)
Zero speed detection
Limiting torque
In-position
Encoder A-phase pulse (differential line driver)
Encoder B-phase pulse (differential line driver)
Control common Control common Encoder Z-phase pulse
(open collector)
Analog monitor 1
DC ± 10 V DC ± 10 V
Analog monitor 2
(Note 16)
3 - 14
3. SIGNALS AND WIRING

3.2.2 Speed control mode

(1) Sink I/O interface
(Note 12) Main circuit power supply
(Note 3, 5)
(Note 5)
(Note 8)
(Note 9) MR Configurator2
Forced stop 2 Servo-on Reset Speed selection 1 Speed selection 2
Forward rotation start Reverse rotation start
Forward rotation stroke end
Reverse rotation stroke end
Upper limit setting
Analog speed command ±10 V/rated speed
Upper limit setting
Analog torque limit +10 V/maximum torque
Personal computer
+
(Note 4)
24 V DC
(Note 11) Short-circuit connector
(Packed with the servo amplifier)
10 m or less
2 m or less
(Note 10)
USB cable
(option)
EM2 SON RES SP1 SP2 ST1 ST2 LSP LSN
DICOM
P15R
VC LG
TLA
SD
Servo amplifier
(Note 7)
CN1
46
47 DOCOM
(Note 7) CN1
42 15
48
23 ZSP
25 TLC
19 41 16
24 SA
49 RD
17 18 43 44 20 21DICOM
1 2
28
27
8LZ 9 LZR 4LA 5 LAR 6LB 7 LBR
34 LG 33 OP
Plate
Plate
(Note 7)
CN5
CN6
3 MO1 1LG 2 MO2
CN8
DOCOM
ALM
SD
2 m or less
2 m or less
(Note 1)
(Note 4)
24 V DC
(Note 2)
RA1
RA2
RA3
RA4
RA5
10 m or less
Encoder Z-phase pulse (open collector)
Malfunction (Note 6)
Zero speed detection
Limiting torque
Speed reached
Ready
Encoder Z-phase pulse (differential line driver)
( Encoder A-phase pulse
(differential line driver)
( Encoder B-phase pulse
(differential line driver) Control common
Analog monitor 1
DC ± 10 V DC ± 10 V
Analog monitor 2
3 - 15
3. SIGNALS AND WIRING
A
r
Note 1. To prevent an electric shock, always connect the protective earth (PE) terminal (marked ) of the servo amplifier to the
protective earth (PE) of the cabinet.
2. Connect the diode in the correct direction. If it is connected reversely, the servo amplifier will malfunction and will not output signals, disabling EM2 (Forced stop 2) and other protective circuits.
3. The forced stop switch (normally closed contact) must be installed.
4. Supply 24 V DC ± 10% to interfaces from outside. The total current capacity is up to 500 mA. 500 mA is the value applicable when all I/O signals are used. The current capacity can be decreased by reducing the number of I/O points. Refer to section
3.9.2 (1) that gives the current value necessary for the interface. The 24 V DC power supply can be used both for input signals and output signals.
5. When starting operation, always turn on EM2 (Forced stop 2), LSP (Forward rotation stroke end) and LSN (Reverse rotation stroke end). (Normally closed contact)
6.
7. The pins with the same signal name are connected in the servo amplifier.
8. TLA will be available when TL (External torque limit selection) is enabled with [Pr. PD03] to [Pr. PD22]. (Refer to section 3.6.1
9. Use SW1DNC-MRC2-_. (Refer to section 11.7.)
10. Controller or parameter units can also be connected via the CN3 connector, enabling RS-422/RS-485 communication. Note
LM (Malfunction) turns on in normal alarm-free condition. (Normally closed contact)
(5).)
that using the USB communication function (CN5 connector) prevents the RS-422/RS-485 communication function (CN3 connector) from being used, and vice versa. They cannot be used together.
RS-422/RS-485
compatible
controller
Servo amplifie
MR-PRU03
or
parameter unit
PRU03
10BASE-T cable, etc. (EIA568-compliant)
11. When not using the STO function, attach the short-circuit connector came with a servo amplifier.
12. Configure a circuit to turn off EM2 when the main circuit power is turned off to prevent an unexpected restart of the servo amplifier.
13. Plus and minus of the power of source interface are the opposite of those of sink interface.
CN3
3 - 16
3. SIGNALS AND WIRING
(2) Source I/O interface
POINT
For notes, refer to (1) in this section.
(Note 12) Main circuit power supply
(Note 3, 5)
(Note 5)
(Note 8)
(Note 9) MR Configurator2
Forced stop 2 Servo-on Reset Speed selection 1 Speed selection 2
Forward rotation start Reverse rotation start
Forward rotation stroke end
Reverse rotation stroke end
Upper limit setting
Analog speed command ±10 V/rated speed
Upper limit setting
Analog torque limit +10 V/maximum torque
Personal computer
+
+
(Note 4, 13)
24 V DC
(Note 11) Short-circuit connector
(Packed with the servo amplifier)
10 m or less
2 m or less
(Note 10)
USB cable
(option)
EM2 SON RES SP1 SP2 ST1 ST2 LSP LSN
DICOM
P15R
VC LG
TLA
SD
Servo amplifier
(Note 7)
CN1
46
47 DOCOM
(Note 7) CN1
42 15
48
23 ZSP
25 TLC
19 41 16
24 SA
49 RD
17 18 43 44 20DICOM 21
1 2
28
27
8LZ 9 LZR 4LA 5 LAR 6LB 7 LBR
34 LG 33 OP
Plate
Plate
(Note 7)
CN5
CN5
CN6
3 MO1 1LG 2 MO2
CN8
CN8
DOCOM
ALM
SD
2 m or less
2 m or less
(Note 1)
(Note 4, 13)
24 V DC
(Note 2)
RA1
RA2
RA3
RA4
RA5
10 m or less
Malfunction (Note 6)
Zero speed detection
Limiting torque
Speed reached
Ready
Encoder Z-phase pulse (differential line driver)
Encoder A-phase pulse (differential line driver)
Encoder B-phase pulse (differential line driver)
Control common
Encoder Z-phase pulse (open collector)
Analog monitor 1
DC ± 10 V
DC ± DC ± 10 V
DC ± 1
Analog monitor 2
3 - 17
3. SIGNALS AND WIRING
r

3.2.3 Torque control mode

POINT
EM2 has the same function as EM1 in the torque control mode.
(1) For sink I/O interface
(Note 10) Main circuit power supply
(Note 3)
(Note 7) MR Configurator2
Forced stop 2 Servo-on Reset Speed selection 1
Forward rotation selection Reverse rotation selection
Upper limit setting
Analog torque command ±8 V/maximum torque
Upper limit setting
Analog speed limit 0 to ±10 V/rated speed
Personal computer
+
(Note 4)
24 V DC
(Note 9) Short-circuit connector
(Packed with the servo amplifier)
10 m or less
2 m or less
(Note 8)
USB cable
(option)
EM2 SON RES SP1 SP2 RS1 RS2
DICOM
P15R
TC LG
VLA
SD
Servo amplifie
(Note 6)
CN1
46
47
(Note 6) CN1
42 15 19 41 16Speed selection 2 18 17 20 21DICOM
1 27 28
2
Plate
CN5
CN8
48 ALM
23 ZSP
25 VLC
49 RD
8LZ 9 4LA 5 LAR 6LB 7 LBR
34 LG 33 OP
Plate
(Note 6)
CN6
3 MO1 1LG 2 MO2
DOCOM
DOCOM
LZR
SD
2 m or less
2 m or less
(Note 1)
(Note 4)
24 V DC
(Note 2)
RA1
RA2
RA3
RA4
10 m or less
Encoder Z-phase pulse (open collector)
Malfunction (Note 5)
Zero speed detection
Limiting speed
Ready
Encoder Z-phase pulse (differential line driver)
Encoder A-phase pulse (differential line driver)
Encoder B-phase pulse (differential line driver)
Control common
DC ± 10 V DC ± 10 V
Analog monitor 1
Analog monitor 2
3 - 18
3. SIGNALS AND WIRING
A
r
Note 1. To prevent an electric shock, always connect the protective earth (PE) terminal (marked ) of the servo amplifier to the
protective earth (PE) of the cabinet.
2. Connect the diode in the correct direction. If it is connected reversely, the servo amplifier will malfunction and will not output signals, disabling EM2 (Forced stop 2) and other protective circuits.
3. The forced stop switch (normally closed contact) must be installed.
4. Supply 24 V DC ± 10% to interfaces from outside. The total current capacity is up to 500 mA. 500 mA is the value applicable when all I/O signals are used. The current capacity can be decreased by reducing the number of I/O points. Refer to section
3.9.2 (1) that gives the current value necessary for the interface. The 24 V DC power supply can be used both for input signals and output signals.
5.
6. The pins with the same signal name are connected in the servo amplifier.
7. Use SW1DNC-MRC2-_. (Refer to section 11.7.)
8. Controller or parameter units can also be connected via the CN3 connector, enabling RS-422/RS-485 communication. Note
LM (Malfunction) turns on in normal alarm-free condition. (Normally closed contact)
that using the USB communication function (CN5 connector) prevents the RS-422/RS-485 communication function (CN3 connector) from being used, and vice versa. They cannot be used together.
RS-422/RS-485
compatible
controller
Servo amplifie
MR-PRU03
or
parameter unit
PRU03
10BASE-T cable, etc. (EIA568-compliant)
9. When not using the STO function, attach the short-circuit connector came with a servo amplifier.
10. Configure a circuit to turn off EM2 when the main circuit power is turned off to prevent an unexpected restart of the servo amplifier.
11. Plus and minus of the power of source interface are the opposite of those of sink interface.
CN3
3 - 19
3. SIGNALS AND WIRING
r
(2) For source I/O interface
POINT
For notes, refer to (1) in this section.
Servo amplifie
(Note 6)
CN1
46 DOCOM
(Note 4, 11)
24 V DC
(Note 3)
(Note 7) MR Configurator2
Forced stop 2 Servo-on Reset Speed selection 1 Speed selection 2
Forward rotation selection Reverse rotation selection
Analog torque command ±8 V/maximum torque
Analog speed limit 0 to ±10 V/rated speed
+
+
Upper limit setting
Upper limit setting
Personal computer
(Note 9) Short-circuit connector
(Packed with the servo amplifier)
10 m or less
(Note 10) Main circuit power supply
(Note 4, 11)
24 V DC
2 m or less
(Note 8)
USB cable
(option)
EM2 SON RES SP1 SP2 RS1 RS2
DICOM DICOM
P15R
TC LG
VLA
SD
(Note 6) CN1
42 15 19 41 16 18 17 20 21
1 27 28
2
Plate
CN5
CN5
CN8
CN8
47 DOCOM
48 ALM
23 ZSP
25 VLC
49 RD
8LZ 9 4LA 5 LAR 6LB 7 LBR
34 LG 33 OP
Plate
(Note 6)
CN6
3 MO1 1LG 2 MO2
LZR
SD
2 m or less
2 m or less
(Note 1)
(Note 2)
RA1
RA2
RA3
RA4
10 m or less
Encoder Z-phase pulse (open collector)
Malfunction (Note 5)
Zero speed detection
Limiting speed
Ready
Encoder Z-phase pulse (differential line driver)
Encoder A-phase pulse (differential line driver)
Encoder B-phase pulse (differential line driver)
Control common
DC ± 10 V DC ± 10 V
Analog monitor 1
Analog monitor 2
3 - 20
3. SIGNALS AND WIRING

3.3 Explanation of power supply system

3.3.1 Signal explanations

POINT
For the layout of connector and terminal block, refer to chapter 9 DIMENSIONS.
Symbol
L1/L2/L3
P3/P4
P+/C/D Regenerative option
Connection target
(application)
Main circuit power
supply
Power factor
improving
DC reactor
Supply the following power to L1, L2, and L3. For 1-phase 200 V AC to 240 V AC, connect the power supply to L1 and L3. Leave L2 open.
Servo amplifier
Power
3-phase 200 V AC to
240 V AC, 50 Hz/60 Hz
1-phase 200 V AC to
240 V AC, 50 Hz/60 Hz
3-phase 380 V AC to
480 V AC, 50 Hz/60 Hz
1-phase 100 V AC to
120 V AC, 50 Hz/60 Hz
When not using the power factor improving DC reactor, connect P3 and P4(factory-wired). When using the power factor improving DC reactor, disconnect P3 and P4, and connect the
power factor improving DC reactor to P3 and P4. Additionally, the power factor improving DC reactor cannot be used for the 100 V class servo amplifiers.
Refer to section 11.11 for details. (1) 200 V class/100 V class
1) MR-J4-500A(-RJ) or less and MR-J4-40A1(-RJ) or less When using a servo amplifier built-in regenerative resistor, connect P+ and D (factory-
wired). When using a regenerative option, disconnect P+ and D, and connect the regenerative
option to P+ and C.
2) MR-J4-700A(-RJ) to MR-J4-22KA(-RJ) MR-J4-700A(-RJ) to MR-J4-22KA(-RJ) do not have D. When using a servo amplifier built-in regenerative resistor, connect P+ and C (factory-
wired). When using a regenerative option, disconnect wires of P+ and C for the built-in
regenerative resistor. And then connect wires of the regenerative option to P+ and C.
(2) 400 V class
1) MR-J4-350A4(-RJ) or less When using a servo amplifier built-in regenerative resistor, connect P+ and D. (factory-
wired) When using a regenerative option, disconnect P+ and D, and connect the regenerative
option to P+ and C.
2) MR-J4-500A4(-RJ) to MR-J4-22KA4(-RJ) MR-J4-500A4(-RJ) to MR-J4-22KA4(-RJ) do not have D. When using a servo amplifier built-in regenerative resistor, connect P+ and C. (factory-
wired) When using a regenerative option, disconnect wires of P+ and C for the built-in
regenerative resistor. And then connect wires of the regenerative option to P+ and C.
Refer to section 11.2 for details.
Description
MR-J4-10A
(-RJ) to
MR-J4-70A
(-RJ)
L1/L2/L3
L1/L3
L1/L2/L3
L1/L2
MR-J4-100A
(-RJ) to
MR-J4-22KA
(-RJ)
MR-J4-60A4
(-RJ) to
MR-J4-22KA4
(-RJ)
MR-J4-10A1 to
MR-J4-40A1
3 - 21
Loading...