Mitsubishi MR-J3-10B, MR-J3-60B, MR-J3-20B, MR-J3-40B, MR-J3-70B Instruction Manual

...
J3 Series MR-J3- B Servo Amplifier Instruction Manual C
General-Purpose AC Servo
J3 Series
SSCNET Compatible
MODEL
MR-J3- B
SERVO AMPLIFIER INSTRUCTION MANUAL
C
A - 1
Safety Instructions
(Always read these instructions before using the equipment.)
Do not attempt to install, operate, maintain or inspect the servo amplifier and servo motor until you have read through this Instruction Manual, Installation guide, Servo motor Instruction Manual and appended documents carefully and can use the equipment correctly. Do not use the servo amplifier and servo motor until you have a full knowledge of the equipment, safety information and instructions. In this Instruction Manual, the safety instruction levels are classified into "WARNING" and "CAUTION".
WARNING
Indicates that incorrect handling may cause hazardous conditions, resulting in death or severe injury.
CAUTION
Indicates that incorrect handling may cause hazardous conditions, resulting in medium or slight injury to personnel or may cause physical
damage.
Note that the CAUTION level may lead to a serious consequence according to conditions. Please follow the instructions of both levels because they are important to personnel safety. What must not be done and what must be done are indicated by the following diagrammatic symbols:
: Indicates what must not be done. For example, "No Fire" is indicated by
.
: Indicates what must be done. For example, grounding is indicated by
.
In this Instruction Manual, instructions at a lower level than the above, instructions for other functions, and so on are classified into "POINT". After reading this installation guide, always keep it accessible to the operator.
A - 2
1. To prevent electric shock, note the following:
WARNING
Before wiring or inspection, turn off the power and wait for 15 minutes or more (20 minutes or for drive
unit 30kW or more) until the charge lamp turns off. Then, confirm that the voltage between P(
) and
N(
) (L and L
for drive unit 30kW or more)
is safe with a voltage tester and others. Otherwise, an electric shock may occur. In addition, always confirm from the front of the servo amplifier, whether the charge lamp is off or not.
Connect the converter unit, servo amplifier (drive unit) and servo motor to ground. Any person who is involved in wiring and inspection should be fully competent to do the work. Do not attempt to wire the converter unit, servo amplifier (drive unit) and servo motor until they have been
installed. Otherwise, you may get an electric shock.
Operate the switches with dry hand to prevent an electric shock. The cables should not be damaged, stressed loaded, or pinched. Otherwise, you may get an electric
shock.
During power-on or operation, do not open the front cover. You may get an electric shock. Do not operate the converter unit and servo amplifier (drive unit) with the front cover removed. High-
voltage terminals and charging area are exposed and you may get an electric shock.
Except for wiring or periodic inspection, do not remove the front cover even if the power is off. The servo
amplifier (drive unit) is charged and you may get an electric shock.
2. To prevent fire, note the following:
CAUTION
Install the converter unit, servo amplifier (drive unit), servo motor and regenerative resistor on
incombustible material. Installing them directly or close to combustibles will lead to a fire.
Always connect a magnetic contactor (MC) between the main circuit power supply and L1, L2, and L3 of the converter unit, servo amplifier, and configure the wiring to be able to shut down the power supply on the side of the converter unit, servo amplifier’s power supply. If a magnetic contactor (MC) is not connected, continuous flow of a large current may cause a fire when the converter unit, servo amplifier (drive unit) malfunctions.
When a regenerative resistor is used, use an alarm signal to switch main power off. Otherwise, a regenerative transistor fault or the like may overheat the regenerative resistor, causing a fire.
3. To prevent injury, note the follow
CAUTION
Only the voltage specified in the instruction manual should be applied to each terminal, Otherwise, a burst, damage, etc. may occur.
Connect the terminals correctly to prevent a burst, damage, etc.
Ensure that polarity ( , ) is correct. Otherwise, a burst, damage, etc. may occur.
Take safety measures, e.g. provide covers, to prevent accidental contact of hands and parts (cables, etc.) with the converter unit and servo amplifier (drive unit) heat sink, regenerative resistor, servo motor, etc. since they may be hot while power is on or for some time after power-off. Their temperatures may be high and you may get burnt or a parts may damaged.
During operation, never touch the rotating parts of the servo motor. Doing so can cause injury.
A - 3
4. Additional instructions
The following instructions should also be fully noted. Incorrect handling may cause a fault, injury, electric shock, etc.
(1) Transportation and installation
CAUTION
Transport the products correctly according to their weights.
Stacking in excess of the specified number of products is not allowed.
Do not carry the servo motor by the cables, shaft or encoder.
Do not hold the front cover to transport the converter unit and servo amplifier (drive unit). The servo amplifier may drop.
Install the converter unit and servo amplifier (drive unit) in a load-bearing place in accordance with the Instruction Manual.
Do not climb or stand on servo equipment. Do not put heavy objects on equipment.
The converter unit, servo amplifier (drive unit), and servo motor must be installed in the specified direction.
Leave specified clearances between the converter unit, servo amplifier (drive unit), and control enclosure walls or other equipment.
Do not install or operate the converter unit, servo amplifier (drive unit), and servo motor which has been damaged or has any parts missing.
When you keep or use it, please fulfill the following environmental conditions.
Conditions
Environment
Converter unit servo amplifier (drive unit) Servo motor
[] 0 to 55 (non-freezing) 0 to 40 (non-freezing)
During operation
[
] 32 to 131 (non-freezing) 32 to 104 (non-freezing)
[] 20 to 65 (non-freezing) 15 to 70 (non-freezing)
Ambient temperature
In storage
[ ] 4 to 149 (non-freezing) 5 to 158 (non-freezing)
In operation 90%RH or less (non-condensing) 80%RH or less (non-condensing)
Ambient humidity
In storage 90%RH or less (non-condensing) Ambience Indoors (no direct sunlight) Free from corrosive gas, flammable gas, oil mist, dust and dirt Altitude Max. 1000m (3280 ft) above sea level
HF-MP series HF-KP series X, Y: 49 m/s2
HF-SP51 81 HF-SP52 to 152
HF-SP524 to 1524 HC-RP Series
HC-UP72
152
X, Y: 24.5 m/s
2
HF-SP121
201 HF-SP202 352
HF-SP2024
3524 HC-UP202 to 502
X: 24.5 m/s
2
Y: 49 m/s2
HF-SP301 421 HF-SP502 702
HF-SP5024
7024
X: 24.5 m/s
2
Y: 29.4 m/s2
HC-LP52 to 152 X: 9.8 m/s2 Y: 24.5 m/s2
HC-LP202 to 302 X: 19.6 m/s2 Y: 49 m/s2
HA-LP601 to 12K1 HA-LP701M to 15K1M
HA-LP502 to 22K2 HA-LP6014
12K14
HA-LP701M4
15K1M4 HA-LP11K24 to 22K24
X: 11.7 m/s
2
Y: 29.4 m/s2
(Note) Vibration
[m/s
2
] 5.9 or less
HA-LP15K1 to 37K1 HA-LP22K1M to 37K1M
HA-LP30K2
37K2 HA-LP15K14 to 37K14
HA-LP22K1M4 to 50K1M4 HA-LP30K24 to 55K24
X, Y: 9.8 m/s2
Note. Except the servo motor with reduction gear.
A - 4
CAUTION
Provide adequate protection to prevent screws and other conductive matter, oil and other combustible
matter from entering the converter unit, servo amplifier (drive unit), and servo motor.
Do not drop or strike converter unit, servo amplifier (drive unit), or servo motor. Isolate from all impact
loads.
Securely attach the servo motor to the machine. If attach insecurely, the servo motor may come off during
operation.
The servo motor with reduction gear must be installed in the specified direction to prevent oil leakage. Take safety measures, e.g. provide covers, to prevent accidental access to the rotating parts of the servo
motor during operation.
Never hit the servo motor or shaft, especially when coupling the servo motor to the machine. The encoder
may become faulty.
Do not subject the servo motor shaft to more than the permissible load. Otherwise, the shaft may break. When the equipment has been stored for an extended period of time, consult Mitsubishi.
(2) Wiring
CAUTION
Wire the equipment correctly and securely. Otherwise, the servo motor may misoperate. Do not install a power capacitor, surge absorber or radio noise filter (FR-BIF (-H) option) between the
servo motor and servo amplifier (drive unit).
Connect the output terminals (U, V, W) correctly. Otherwise, the servo motor will operate improperly. Connect the servo motor power terminal (U, V, W) to the servo motor power input terminal (U, V, W)
directly. Do not let a magnetic contactor, etc. intervene.
U
Servo Motor
M
V
W
U
V
W
U
M
V
W
U
V
W
Servo Amplifier
(drive unit)
Servo Motor
Servo Amplifier
(drive unit)
Do not connect AC power directly to the servo motor. Otherwise, a fault may occur.
The surge absorbing diode installed on the DC output signal relay of the servo amplifier (drive unit) must be wired in the specified direction. Otherwise, the forced stop (EM1) and other protective circuits may not operate.
Control
output
signal
Control
output
signal
RA
DOCOM
DICOM
24VDC
RA
DOCOM
DICOM
24VDC
Servo Amplifier
(drive unit)
Servo Amplifier
(drive unit)
When the cable is not tightened enough to the terminal block (connector), the cable or terminal block (connector) may generate heat because of the poor contact. Be sure to tighten the cable with specified torque.
A - 5
(3) Test run adjustment
CAUTION
Before operation, check the parameter settings. Improper settings may cause some machines to perform unexpected operation.
The parameter settings must not be changed excessively. Operation will be insatiable.
(4) Usage
CAUTION
Provide an external emergency stop circuit to ensure that operation can be stopped and power switched off immediately.
Any person who is involved in disassembly and repair should be fully competent to do the work.
Before resetting an alarm, make sure that the run signal of the servo amplifier is off to prevent an accident. A sudden restart is made if an alarm is reset with the run signal on.
Do not modify the equipment.
Use a noise filter, etc. to minimize the influence of electromagnetic interference, which may be caused by electronic equipment used near the converter unit and servo amplifier (drive unit).
Burning or breaking a converter unit and servo amplifier (drive unit) may cause a toxic gas. Do not burn or break a converter unit and servo amplifier (drive unit).
Use the converter unit and servo amplifier (drive unit) with the specified servo motor.
The electromagnetic brake on the servo motor is designed to hold the motor shaft and should not be used for ordinary braking.
For such reasons as service life and mechanical structure (e.g. where a ballscrew and the servo motor are coupled via a timing belt), the electromagnetic brake may not hold the motor shaft. To ensure safety, install a stopper on the machine side.
A - 6
(5) Corrective actions
CAUTION
When it is assumed that a hazardous condition may take place at the occur due to a power failure or a product fault, use a servo motor with electromagnetic brake or an external brake mechanism for the purpose of prevention.
Configure the electromagnetic brake circuit so that it is activated not only by the servo amplifier signals but also by an external forced stop (EM1).
EM1RA
24VDC
Contacts must be open when servo-off, when an trouble (ALM) and when an electromagnetic brake interlock (MBR).
Electromagnetic brake
Servo motor
Circuit must be opened during forced stop (EM1).
When any alarm has occurred, eliminate its cause, ensure safety, and deactivate the alarm before
restarting operation.
When power is restored after an instantaneous power failure, keep away from the machine because the machine may be restarted suddenly (design the machine so that it is secured against hazard if restarted).
(6) Maintenance, inspection and parts replacement
CAUTION
With age, the electrolytic capacitor of the servo amplifier (drive unit) will deteriorate. To prevent a secondary accident due to a fault, it is recommended to replace the electrolytic capacitor every 10 years when used in general environment.
Please consult our sales representative.
(7) General instruction
To illustrate details, the equipment in the diagrams of this Specifications and Instruction Manual may have been drawn without covers and safety guards. When the equipment is operated, the covers and safety guards must be installed as specified. Operation must be performed in accordance with this Specifications and Instruction Manual.
A - 7
About processing of waste
When you discard servo amplifier, a battery (primary battery), and other option articles, please follow the law of each country (area).
FOR MAXIMUM SAFETY
These products have been manufactured as a general-purpose part for general industries, and have not
been designed or manufactured to be incorporated in a device or system used in purposes related to
human life. Before using the products for special purposes such as nuclear power, electric power, aerospace,
medicine, passenger movement vehicles or under water relays, contact Mitsubishi. These products have been manufactured under strict quality control. However, when installing the product
where major accidents or losses could occur if the product fails, install appropriate backup or failsafe
functions in the system.
EEP-ROM life
The number of write times to the EEP-ROM, which stores parameter settings, etc., is limited to 100,000. If the total number of the following operations exceeds 100,000, the converter unit, servo amplifier (drive unit) and/or converter unit may fail when the EEP-ROM reaches the end of its useful life.
Write to the EEP-ROM due to parameter setting changes Write to the EEP-ROM due to device changes
Precautions for Choosing the Products
Mitsubishi will not be held liable for damage caused by factors found not to be the cause of Mitsubishi; machine damage or lost profits caused by faults in the Mitsubishi products; damage, secondary damage, accident compensation caused by special factors unpredictable by Mitsubishi; damages to products other than Mitsubishi products; and to other duties.
A - 8
COMPLIANCE WITH EC DIRECTIVES
1. WHAT ARE EC DIRECTIVES? The EC directives were issued to standardize the regulations of the EU countries and ensure smooth distribution of safety-guaranteed products. In the EU countries, the machinery directive (effective in January,
1995), EMC directive (effective in January, 1996) and low voltage directive (effective in January, 1997) of the EC directives require that products to be sold should meet their fundamental safety requirements and carry the CE marks (CE marking). CE marking applies to machines and equipment into which servo amplifiers have been installed.
(1) EMC directive
The EMC directive applies not to the servo units alone but to servo-incorporated machines and equipment.
This requires the EMC filters to be used with the servo-incorporated machines and equipment to comply
with the EMC directive. For specific EMC directive conforming methods, refer to the EMC Installation
Guidelines (IB(NA)67310).
(2) Low voltage directive
The low voltage directive applies also to servo units alone. Hence, they are designed to comply with the low
voltage directive.
This servo is certified by TUV, third-party assessment organization, to comply with the low voltage directive.
(3) Machine directive
Not being machines, the converter unit, servo amplifiers (drive unit) need not comply with this directive.
2. PRECAUTIONS FOR COMPLIANCE (1) Converter unit, servo amplifiers (drive unit), and servo motors used
Use the converter unit, servo amplifiers (drive unit), and servo motors which comply with the standard
model.
Converter unit series :MR-J3-CR55K MR-J3-CR55K4 Servo amplifier (drive unit) series :MR-J3-10B to MR-J3-22KB MR-J3-10B1 to MR-J3-40B1 MR-J3-60B4 to MR-J3-22KB4 MR-J3-DU30KB to MR-J3-DU37KB MR-J3-DU30KB4 to MR-J3-DU55KB4 Servo motor series :HF-MP HF-KP HF-SP
(Note)
HF-SP
4 (Note) HC-RP HC-UP HC-LP HA-LP
(Note)
HA-LP
4 (Note)
Note. For compliance conditions, refer to Section 1.1 of the Servo Motor Instruction Manual (Vol.2) (SH(NA)030041).
A - 9
(2) Configuration
The control circuit provide safe separation to the main circuit in the converter unit and servo amplifier (drive unit).
(a) MR-J3-22KB(4) or less
NFB MC
24VDC
power
supply
Servo
amplifier
Reinforced
insulating type
Control box
Serve motor
No-fuse breaker
Magnetic
contactor
M
(b) MR-J3-DU30KB(4) or more
NFB MC
24VDC
power
supply
Control box
No-fuse breaker
Magnetic contactor
Converter
unit
Servvo
motor
M
Drive
unit
Reinforced insulating type
(3) Environment
Operate the converter unit and servo amplifier (drive unit) at or above the contamination level 2 set forth in IEC60664-1. For this purpose, install the servo amplifier in a control box which is protected against water, oil, carbon, dust, dirt, etc. (IP54).
(4) Power supply
(a) This converter unit and servo amplifier (drive unit) can be supplied from star-connected supply with
earthed neutral point of overvoltage category III set forth in IEC60664-1. However, when using the neutral point of 400V system for single phase supply, a reinforced insulating transformer is required in the power input section.
(b) When supplying interface power from external, use a 24VDC power supply which has been insulation-
reinforced in I/O.
(5) Grounding
(a) To prevent an electric shock, always connect the protective earth (PE) terminals (marked
) of the
converter unit and servo amplifier (drive unit) to the protective earth (PE) of the control box.
A - 10
(b) Do not connect two ground cables to the same protective earth (PE) terminal. Always connect the
cables to the terminals one-to-one.
PE terminals
PE terminals
(c) If a leakage current breaker is used to prevent an electric shock, the protective earth (PE) terminals of
the servo amplifier must be connected to the corresponding earth terminals.
(6) Wiring
(a) The cables to be connected to the terminal block of the converter unit and servo amplifier (drive unit)
must have crimping terminals provided with insulating tubes to prevent contact with adjacent terminals.
Crimping terminal
Insulating tube
Cable
(b) Use the servo motor side power connector which complies with the EN Standard. The EN Standard
compliant power connector sets are available from us as options. (Refer to section 11.1)
(7) Auxiliary equipment and options
(a) The no-fuse breaker and magnetic contactor used should be the EN or IEC standard-compliant
products of the models described in section 11.12 (Section 13.9.5 for 30kW or more). Use a type B (Note) breaker. When it is not used, provide insulation between the converter unit, servo amplifier (drive unit) and other device by double insulation or reinforced insulation, or install a transformer between the main power supply, converter unit and servo amplifier (drive unit). Note. Type A: AC and pulse detectable
Type B: Both AC and DC detectable
(b) The sizes of the cables described in section 11.8 meet the following requirements. To meet the other
requirements, follow Table 5 and Appendix C in EN60204-1.
Ambient temperature: 40 (104) [°C (°F)] Sheath: PVC (polyvinyl chloride) Installed on wall surface or open table tray
(c) Use the EMC filter for noise reduction.
(8) Performing EMC tests
When EMC tests are run on a machine/device into which the converter unit and servo amplifier (drive unit) has been installed, it must conform to the electromagnetic compatibility (immunity/emission) standards after it has satisfied the operating environment/electrical equipment specifications. For the other EMC directive guidelines on the converter unit and servo amplifier (drive unit), refer to the EMC Installation Guidelines(IB(NA)67310).
A - 11
CONFORMANCE WITH UL/C-UL STANDARD
(1) Converter unit, servo amplifiers (drive unit) and servo motors used
Use the converter unit, servo amplifiers (drive unit) and servo motors which comply with the standard model.
Converter unit series :MR-J3-CR55K MR-J3-CR55K4 Servo amplifier (drive unit) series :MR-J3-10B to MR-J3-22KB MR-J3-10B1 to MR-J3-40B1 MR-J3-60B4 to MR-J3-22KB4 MR-J3-DU30KB to MR-J3-DU37KB MR-J3-DU30KB4 to MR-J3-DU55KB4 Servo motor series :HF-MP HF-KP HF-SP
(Note) HF-SP
4 (Note) HC-RP HC-UP HC-LP HA-LP
(Note) HA-LP
4 (Note)
Note. For compliance conditions, refer to Section 1.1 of the Servo Motor Instruction Manual (Vol.2) (SH(NA)030041).
(2) Installation
Install a cooling fan of 100CFM (2.8m
3
/min) air flow 4 in (10.16 cm) above the servo amplifier (drive unit) or
provide cooling of at least equivalent capability.
(3) Short circuit rating
This servo amplifier (drive unit) conforms to the circuit whose peak current is limited to 5000A or less. Having been subjected to the short-circuit tests of the UL in the alternating-current circuit, the servo amplifier conforms to the above circuit.
A - 12
(4) Capacitor discharge time
The capacitor discharge time is as listed below. To ensure safety, do not touch the charging section for 15 minutes (more than 20 minutes in case drive unit is 30kW or more) after power-off.
Servo amplifier Discharge time [min]
MR-J3-10B 20B 1
MR-J3-40B 60B(4) 10B1 20B1 2
MR-J3-70B 3
MR-J3-40B1 4
MR-J3-100B(4) 5
MR-J3-200B(4) 350B 9
MR-J3-350B4 500B(4) 700B(4) 10
MR-J3-11KB(4) 4 MR-J3-15KB(4) 6 MR-J3-22KB(4) 8
Converter unit Drive unit Discharge time [min]
MR-J3-DU30KB
MR-J3-CR55K
MR-J3-DU37KB
MR-J3-DU30KB4
MR-J3-DU37KB4
20
MR-J3-CR55K4
MR-J3-DU45KB4
MR-J3-DU55KB4
(5) Options and auxiliary equipment
Use UL/C-UL standard-compliant products. This servo amplifier is UL/C-UL-listed when using the fuses indicated in the following table. When the servo amplifier must comply with the UL/C-UL Standard, be sure to use these fuses.
Fuse Fuse
Servo amplifier
(drive unit)
Class Current [A]
Voltage
AC [V]
Servo amplifier
(drive unit)
Class Current [A]
Voltage
AC [V] MR-J3-10B(1) 20B 10 MR-J3-60B4 10 MR-J3-40B 20B1 15 MR-J3-100B4 15 MR-J3-60B to 100B 40B1 20 MR-J3-200B4 25 MR-J3-200B 40 MR-J3-350B4 35 MR-J3-350B 70 MR-J3-500B4 50 MR-J3-500B 125 MR-J3-700B4 65 MR-J3-700B 150 MR-J3-11KB4 T 100 600 MR-J3-11KB 200 MR-J3-15KB4 150 MR-J3-15KB 250 MR-J3-22KB4 175 MR-J3-22KB 350 MR-J3-DU30KB4 (Note) 250 MR-J3-DU30KB (Note) 500 MR-J3-DU37KB4 (Note) 300 MR-J3-DU37KB (Note)
T
600
250
MR-J3-DU45KB4 (Note) 400
MR-J3-DU55KB4 (Note) 450
Note. Prospect approved in the near future.
(6) Attachment of a servo motor
For the flange size of the machine side where the servo motor is installed, refer to “CONFORMANCE WITH UL/C-UL STANDARD” in the Servo Motor Instruction Manual (Vol.2).
A - 13
(7) About wiring protection
For installation in United States, branch circuit protection must be provided, in accordance with the National Electrical Code and any applicable local codes. For installation in Canada, branch circuit protection must be provided, in accordance with the Canada Electrical Code and any applicable provincial codes.
<<About the manuals>>
This Instruction Manual and the MELSERVO Servo Motor Instruction Manual (Vol.2) are required if you use the General-Purpose AC servo MR-J3-B for the first time. Always purchase them and use the MR-J3-B safely.
Relevant manuals
Manual name Manual No.
MELSERVO-J3 Series To Use the AC Servo Safely
Enclosed in converter unit and servo amplifier (drive unit).
IB(NA)0300077
MELSERVO Servo Motor Instruction Manual Vol.2 SH(NA)030041
EMC Installation Guidelines IB(NA)67310
Details of MR-J3-DU30KB(4) to MR-J3-DU55KB4 are described in chapter 13 of this INSTRUCTION MANUAL. For the products of 30kW or more, refer to chapter 13.
A - 14
MEMO
1
CONTENTS
1. FUNCTIONS AND CONFIGURATION 1 - 1 to 1 -28
1.1 Introduction ............................................................................................................................................... 1 - 1
1.2 Function block diagram............................................................................................................................ 1 - 2
1.3 Servo amplifier standard specifications................................................................................................... 1 - 5
1.4 Function list .............................................................................................................................................. 1 - 7
1.5 Model code definition ...............................................................................................................................1 - 8
1.6 Combination with servo motor ................................................................................................................ 1 -10
1.7 Structure .................................................................................................................................................. 1 -11
1.7.1 Parts identification ............................................................................................................................1 -11
1.7.2 Removal and reinstallation of the front cover.................................................................................. 1 -18
1.8 Configuration including auxiliary equipment........................................................................................... 1 -21
2. INSTALLATION 2 - 1 to 2 - 6
2.1 Installation direction and clearances .......................................................................................................2 - 1
2.2 Keep out foreign materials ....................................................................................................................... 2 - 3
2.3 Cable stress ............................................................................................................................................. 2 - 3
2.4 SSCNET
cable laying............................................................................................................................ 2 - 4
2.5 Inspection items .......................................................................................................................................2 - 6
2.6 Parts having service lives ........................................................................................................................ 2 - 6
3. SIGNALS AND WIRING 3 - 1 to 3 -52
3.1 Input power supply circuit ........................................................................................................................ 3 - 2
3.2 I/O signal connection example ...............................................................................................................3 -10
3.3 Explanation of power supply system ......................................................................................................3 -12
3.3.1 Signal explanations .......................................................................................................................... 3 -12
3.3.2 Power-on sequence .........................................................................................................................3 -13
3.3.3 CNP1, CNP2, CNP3 wiring method ................................................................................................3 -14
3.4 Connectors and signal arrangements ....................................................................................................3 -23
3.5 Signal (device) explanations................................................................................................................... 3 -24
3.6 Alarm occurrence timing chart ................................................................................................................ 3 -27
3.7 Interfaces .................................................................................................................................................3 -28
3.7.1 Internal connection diagram ............................................................................................................ 3 -28
3.7.2 Detailed description of interfaces..................................................................................................... 3 -29
3.7.3 Source I/O interfaces ....................................................................................................................... 3 -31
3.8 Treatment of cable shield external conductor ........................................................................................3 -32
3.9 SSCNET
cable connection .................................................................................................................. 3 -33
3.10 Connection of servo amplifier and servo motor ...................................................................................3 -35
3.10.1 Connection instructions.................................................................................................................. 3 -35
3.10.2 Power supply cable wiring diagrams ............................................................................................. 3 -36
3.11 Servo motor with electromagnetic brake.............................................................................................. 3 -46
3.11.1 Safety precautions ......................................................................................................................... 3 -46
3.11.2 Timing charts.................................................................................................................................. 3 -47
3.11.3 Wiring diagrams (HF-MP series
HF-KP series servo motor) ..................................................... 3 -49
3.12 Grounding.............................................................................................................................................. 3 -50
2
3.13 Control axis selection............................................................................................................................ 3 -51
4. STARTUP 4 - 1 to 4 -10
4.1 Switching power on for the first time ....................................................................................................... 4 - 1
4.1.1 Startup procedure.............................................................................................................................. 4 - 1
4.1.2 Wiring check ......................................................................................................................................4 - 2
4.1.3 Surrounding environment.................................................................................................................. 4 - 3
4.2 Start up .....................................................................................................................................................4 - 4
4.3 Servo amplifier display.............................................................................................................................4 - 5
4.4 Test operation ..........................................................................................................................................4 - 7
4.5 Test operation mode ................................................................................................................................ 4 - 8
4.5.1 Test operation mode in MR Configurator ......................................................................................... 4 - 8
4.5.2 Motorless operation in controller...................................................................................................... 4 -10
5. PARAMETERS 5 - 1 to 5 -26
5.1 Basic setting parameters (No.PA )..................................................................................................... 5 - 1
5.1.1 Parameter list ....................................................................................................................................5 - 1
5.1.2 Parameter write inhibit ......................................................................................................................5 - 2
5.1.3 Selection of regenerative option .......................................................................................................5 - 3
5.1.4 Using absolute position detection system ........................................................................................5 - 4
5.1.5 Forced stop input selection............................................................................................................... 5 - 4
5.1.6 Auto tuning ........................................................................................................................................ 5 - 5
5.1.7 In-position range................................................................................................................................ 5 - 6
5.1.8 Selection of servo motor rotation direction ....................................................................................... 5 - 7
5.1.9 Encoder output pulse ........................................................................................................................5 - 7
5.2 Gain/filter parameters (No. PB
) ......................................................................................................... 5 - 9
5.2.1 Parameter list ....................................................................................................................................5 - 9
5.2.2 Detail list ........................................................................................................................................... 5 -10
5.3 Extension setting parameters (No. PC
) ...........................................................................................5 -17
5.3.1 Parameter list ...................................................................................................................................5 -17
5.3.2 List of details..................................................................................................................................... 5 -18
5.3.3 Analog monitor .................................................................................................................................5 -21
5.3.4 Alarm history clear............................................................................................................................ 5 -23
5.4 I/O setting parameters (No. PD
)....................................................................................................... 5 -24
5.4.1 Parameter list ...................................................................................................................................5 -24
5.4.2 List of details..................................................................................................................................... 5 -25
6. GENERAL GAIN ADJUSTMENT 6 - 1 to 6 -12
6.1 Different adjustment methods.................................................................................................................. 6 - 1
6.1.1 Adjustment on a single servo amplifier............................................................................................. 6 - 1
6.1.2 Adjustment using MR Configurator................................................................................................... 6 - 2
6.2 Auto tuning ............................................................................................................................................... 6 - 3
6.2.1 Auto tuning mode .............................................................................................................................. 6 - 3
6.2.2 Auto tuning mode operation.............................................................................................................. 6 - 4
6.2.3 Adjustment procedure by auto tuning............................................................................................... 6 - 5
6.2.4 Response level setting in auto tuning mode .................................................................................... 6 - 6
6.3 Manual mode 1 (simple manual adjustment) .......................................................................................... 6 - 7
3
6.4 Interpolation mode ..................................................................................................................................6 -11
6.5 Differences between MELSERVO-J2-Super and MELSERVO-J3 in auto tuning ................................ 6 -12
7. SPECIAL ADJUSTMENT FUNCTIONS 7 - 1 to 7 -16
7.1 Function block diagram............................................................................................................................ 7 - 1
7.2 Adaptive filter
......................................................................................................................................... 7 - 1
7.3 Machine resonance suppression filter..................................................................................................... 7 - 4
7.4 Advanced vibration suppression control ................................................................................................. 7 - 6
7.5 Low-pass filter ......................................................................................................................................... 7 -10
7.6 Gain changing function ...........................................................................................................................7 -10
7.6.1 Applications ......................................................................................................................................7 -10
7.6.2 Function block diagram ....................................................................................................................7 -11
7.6.3 Parameters ....................................................................................................................................... 7 -12
7.6.4 Gain changing operation ..................................................................................................................7 -14
8. TROUBLESHOOTING 8 - 1 to 8 -10
8.1 Alarms and warning list............................................................................................................................ 8 - 1
8.2 Remedies for alarms................................................................................................................................ 8 - 2
8.3 Remedies for warnings ............................................................................................................................8 - 8
9. OUTLINE DRAWINGS 9 - 1 to 9 -12
9.1 Servo amplifier ......................................................................................................................................... 9 - 1
9.2 Connector ................................................................................................................................................9 -10
10. CHARACTERISTICS 10- 1 to 10-10
10.1 Overload protection characteristics ...................................................................................................... 10- 1
10.2 Power supply equipment capacity and generated loss .......................................................................10- 3
10.3 Dynamic brake characteristics.............................................................................................................. 10- 6
10.3.1 Dynamic brake operation............................................................................................................... 10- 6
10.3.2 The dynamic brake at the load inertia moment............................................................................. 10- 8
10.4 Cable flexing life .................................................................................................................................... 10- 9
10.5 Inrush currents at power-on of main circuit and control circuit ........................................................... 10-10
11. OPTIONS AND AUXILIARY EQUIPMENT 11- 1 to 11-88
11.1 Cable/connector sets ............................................................................................................................ 11- 1
11.1.1 Combinations of cable/connector sets .......................................................................................... 11- 2
11.1.2 Encoder cable/connector sets .......................................................................................................11- 8
11.1.3 Motor power supply cables ...........................................................................................................11-17
11.1.4 Motor brake cables........................................................................................................................ 11-18
11.1.5 SSCNET
cable ...........................................................................................................................11-19
11.2 Regenerative options ...........................................................................................................................11-21
11.3 FR-BU2-(H) Brake unit......................................................................................................................... 11-34
11.3.1 Selection ........................................................................................................................................ 11-35
11.3.2 Brake unit parameter setting......................................................................................................... 11-35
11.3.3 Connection example .....................................................................................................................11-36
4
11.3.4 Outline dimension drawings.......................................................................................................... 11-43
11.4 Power regeneration converter .............................................................................................................11-45
11.5 Power regeneration common converter .............................................................................................. 11-48
11.6 External dynamic brake .......................................................................................................................11-56
11.7 Junction terminal block PS7DW-20V14B-F (recommended)............................................................. 11-61
11.8 MR Configurator ...................................................................................................................................11-63
11.9 Battery MR-J3BAT ...............................................................................................................................11-64
11.10 Heat sink outside mounting attachment (MR-J3ACN)...................................................................... 11-65
11.11 Recommended wires .........................................................................................................................11-67
11.12 No-fuse breakers, fuses, magnetic contactors ................................................................................. 11-71
11.13 Power factor improving DC reactor ...................................................................................................11-71
11.14 Power factor improving AC reactors .................................................................................................11-73
11.15 Relays (recommended) .....................................................................................................................11-74
11.16 Surge absorbers (recommended) .....................................................................................................11-75
11.17 Noise reduction techniques ...............................................................................................................11-75
11.18 Leakage current breaker....................................................................................................................11-82
11.19 EMC filter (recommended) ................................................................................................................ 11-84
12. ABSOLUTE POSITION DETECTION SYSTEM 12- 1 to 12- 6
12.1 Features ................................................................................................................................................ 12- 1
12.2 Specifications ........................................................................................................................................12- 2
12.3 Battery installation procedure ............................................................................................................... 12- 3
12.4 Confirmation of absolute position detection data................................................................................. 12- 5
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW) 13- 1 to 13-100
13.1. Functions and menus........................................................................................................................... 13- 1
13.1.1 Function block diagram ..................................................................................................................13- 2
13.1.2 Packing list .....................................................................................................................................13- 4
13.1.3 Standard specifications.................................................................................................................. 13- 5
13.1.4 Model definition ..............................................................................................................................13- 8
13.1.5 Combinations of converter units, drive unit and servo motors ..................................................... 13- 9
13.1.6 Parts identification .........................................................................................................................13-10
13.1.7 Removal and reinstallation of the terminal block cover ...............................................................13-13
13.1.8 Servo system with auxiliary equipment ........................................................................................13-19
13.2 Installation ............................................................................................................................................ 13-20
13.2.1 Installation direction and clearances ............................................................................................13-21
13.2.2 Inspection ......................................................................................................................................13-22
13.3 Signals and wiring ................................................................................................................................ 13-23
13.3.1 Magnetic contactor control connector (CNP1) .............................................................................13-24
13.3.2 Input power supply circuit ............................................................................................................. 13-26
13.3.3 Terminal ......................................................................................................................................... 13-31
13.3.4 How to use the connection bars ...................................................................................................13-32
13.3.5 Connectors and signal arrangements .......................................................................................... 13-33
13.3.6 Converter unit signal (device) explanations .................................................................................13-35
13.3.7 Timing chart...................................................................................................................................13-37
13.3.8 Servo motor side details ............................................................................................................... 13-45
13.4 Display section and operation section of the converter unit ...............................................................13-47
5
13.4.1 Display flowchart ...........................................................................................................................13-47
13.4.2 Status display mode...................................................................................................................... 13-48
13.4.3 Diagnostic mode............................................................................................................................ 13-49
13.4.4 Alarm mode ...................................................................................................................................13-51
13.4.5 Parameter mode ........................................................................................................................... 13-52
13.5. Parameters for converter unit .............................................................................................................13-53
13.5.1 Parameter list ................................................................................................................................13-53
13.5.2 List of details.................................................................................................................................. 13-54
13.6 Troubleshooting ...................................................................................................................................13-55
13.6.1 Converter unit................................................................................................................................ 13-55
13.6.2 Drive unit........................................................................................................................................13-60
13.7 Outline drawings ..................................................................................................................................13-62
13.7.1 Converter unit (MR-J3-CR55K(4))................................................................................................13-62
13.7.2 Drive unit........................................................................................................................................13-63
13.8 Characteristics...................................................................................................................................... 13-65
13.8.1 Overload protection characteristics ..............................................................................................13-65
13.8.2 Power supply equipment capacity and generated loss ............................................................... 13-66
13.8.3 Dynamic brake characteristics...................................................................................................... 13-67
13.8.4 Inrush currents at power-on of main circuit and control circuit ....................................................13-69
13.9 Options .................................................................................................................................................13-70
13.9.1 Cables and connectors .................................................................................................................13-70
13.9.2 Regenerative option ......................................................................................................................13-73
13.9.3 External dynamic brake ................................................................................................................13-77
13.9.4 Recommended wires ....................................................................................................................13-80
13.9.5 No-fuse breakers, fuses, magnetic contactors............................................................................. 13-81
13.9.6 Power factor improving DC reactor ..............................................................................................13-82
13.9.7 Line noise filter (FR-BLF) ..............................................................................................................13-83
13.9.8 Leakage current breaker............................................................................................................... 13-84
13.9.9 EMC filter (recommended)............................................................................................................ 13-86
13.9.10 FR-BU2-(H) Brake Unit ............................................................................................................... 13-88
APPENDIX App- 1 to App- 4
App 1. Parameter list...................................................................................................................................App- 1
App 2. Signal layout recording paper .........................................................................................................App- 3
App 3. Twin type connector : Outline drawing for 721-2105/026-000 (WAGO)........................................App- 3
App 4. Change of connector sets to the RoHS compatible products ........................................................App- 4
6
MEMO
1 - 1
1. FUNCTIONS AND CONFIGURATION
1. FUNCTIONS AND CONFIGURATION
1.1 Introduction
The Mitsubishi MELSERVO-J3 series general-purpose AC servo has further higher performance and higher functions compared to the current MELSERVO-J2-Super series. The MR-J3-B servo amplifier connects to servo system controller and others via high speed synchronous network and operates by directly reading position data. The rotation speed/direction control of servo motor and the high accuracy positioning are executed with the data from command module. SSCNET
equipped by the MR-J3-B servo amplifier greatly improved its communication speed and noise tolerance by adopting optical communication system compared to the current SSCNET. For wiring distance, 50m of the maximum distance between electrodes is also offered. The torque limit with clamping circuit is put on the servo amplifier in order to protect the power transistor of main circuit from the overcurrent caused by rapid acceleration/deceleration or overload. In addition, torque limit value can be changed to desired value with parameter. As this new series has the USB communication function, a MR Configurator-installed personal computer or the like can be used to perform parameter setting, test operation, status display monitoring, gain adjustment, etc. With real-time auto tuning, you can automatically adjust the servo gains according to the machine. The MELSERVO-J3 series servo motor is equipped with an absolute position encoder which has the resolution of 262144 pulses/rev to ensure more accurate control as compared to the MELSERVO-J2-Super series. Simply adding a battery to the servo amplifier makes up an absolute position detection system. This makes home position return unnecessary at power-on or alarm occurrence by setting a home position once.
1 - 2
1. FUNCTIONS AND CONFIGURATION
1.2 Function block diagram
The function block diagram of this servo is shown below.
(1) MR-J3-350B or less
MR-J3-200B4 or less
Base
amplifier
CN4
N( )
DC
Encoder
Current
detection
CN5
NFB MC
L
1
L2
L
3
L
11
L21
B2
U
V
W
B1
USB
USB
Power factor improving DC reactor
Regenerative
option
MR-J3BAT
P
1
P
2
D/A
Position command input
(Note 1)
(Note 2) Power supply
CHARGE
lamp
Regene­rative TR
Current
detector
Dynamic
brake
Electro­magnetic brake
Servo motorServo amplifier
Optional battery (for absolute position detection system)
Overcurrent
protection
Voltage
detection
Virtual
encoder
Virtual
motor
Model torque
Personal computer
Actual speed
control
Actual position
control
(Note 3)Cooling fan
Control
circuit power
supply
Model position
control
Model position
Model speed
CN2
P( )
U
V
W
M
Model speed
control
Current
control
I/F Control
CN1BCN1A
Controller or
servo amplifier
Servo amplifier
or cap
Analog monitor
(2 channels)
CN3
Digital I/O
control
Diode
stack
Relay
Note 1. The built-in regenerative resistor is not provided for the MR-J3-10B (1).
2. For 1-phase 200 to 230VAC, connect the power supply to L
1, L2 and leave L3 open.
There is no L
3 for 1-phase 100 to 120VAC power supply. Refer to section 1.3 for the power supply specification.
3. Servo amplifiers MR-J3-70B or greater have a cooling fan.
1 - 3
1. FUNCTIONS AND CONFIGURATION
(2) MR-J3-350B4
MR-J3-500B(4) MR-J3-700B(4)
Base
amplifier
CN4
N
C
Encoder
Current
detection
CN5
NFB MC
L
1
L2
L
3
L
11
L21
B2
U
V
W
B1
USB
USB
Power factor improving DC reactor
Regenerative
option
MR-J3BAT
P
1
P
2
D/A
Position command input
(Note) Power supply
CHARGE
lamp
Regene­rative TR
Current
detector
Dynamic
brake
Electro­magnetic brake
Servo motorServo amplifier
Optional battery (for absolute position detection system)
Overcurrent
protection
Voltage
detection
Virtual
encoder
Virtual
motor
Model torque
Personal computer
Actual speed
control
Actual position
control
Cooling fan
Control
circuit power supply
Model position
control
Model position
Model speed
CN2
P
U
V
W
M
Model speed
control
Current
control
I/F Control
CN1BCN1A
Controller or
servo amplifier
Servo amplifier
or cap
Analog monitor
(2 channels)
CN3
Digital I/O
control
Diode
stack
Relay
Note. Refer to section 1.3 for the power supply specification.
1 - 4
1. FUNCTIONS AND CONFIGURATION
(3) MR-J3-11KB(4) to 22KB(4)
Cooling fan
Base
amplifier
CN4
N
C
Encoder
Current
detection
CN5
NFB MC
L
1
L2
L
3
L
11
L21
B2
U
V
W
B1
USB
USB
Power factor improving DC reactor
Regenerative
option
MR-J3BAT
P
1
D/A
Position command input
(Note) Power supply
CHARGE
lamp
Regene­rative TR
Current
detector
Dynamic
brake
Electro­magnetic brake
Servo motorServo amplifier
Optional battery (for absolute position detection system)
Overcurrent
protection
Voltage
detection
Virtual
encoder
Virtual
motor
Model torque
Personal computer
Actual speed
control
Actual position
control
Control
circuit power supply
Model position
control
Model position
Model speed
CN2
P
U
V
W
M
Model speed
control
Current
control
I/F Control
CN1BCN1A
Controller or
servo amplifier
Servo amplifier
or cap
Analog monitor
(2 channels)
CN3
Digital I/O
control
Diode
stack
Thyristor
Note. Refer to section 1.3 for the power supply specification.
1 - 5
1. FUNCTIONS AND CONFIGURATION
1.3 Servo amplifier standard specifications
(1) 200V class, 100V class
Servo Amplifier
MR-J3-
Item
10B 20B 40B 60B 70B 100B 200B 350B 500B 700B 11KB 15KB 22KB 10B1 20B1 40B1
Voltage/frequency
3-phase or 1-phase 200
to 230VAC, 50/60Hz
3-phase 200 to 230VAC, 50/60Hz
1-phase 100V to
120VAC, 50/60Hz
Permissible voltage fluctuation
3-phase or 1-phase 200
to 230VAC: 170 to
253VAC
3-phase 170 to 253VAC
1-phase 85 to
132VAC
Permissible frequency fluctuation Within 5% Power supply capacity Refer to section 10.2
Power supply
Inrush current Refer to section 10.5
Voltage, frequency
1-phase 200 to 230VAC, 50/60Hz
1-phase 100 to
120VAC, 50/60Hz Permissible voltage fluctuation
1-phase 170 to 253VAC
1-phase 85 to
132VAC
Permissible frequency fluctuation
Within
5%
Input 30W 45W 30W
Control circuit power supply
Inrush current Refer to section 10.5 Voltage, frequency
24VDC
10%
Interface power supply
Power supply capacity
(Note 1) 150mA or more
Control System Sine-wave PWM control, current control system Dynamic brake Built-in External option Built-in
Protective functions
Overcurrent shut-off, regenerative overvoltage shut-off, overload shut-off (electronic thermal relay), servo motor overheat protection, encoder error protection, regenerative error protection, undervoltage, instantaneous power failure protection, overspeed protection, excessive error protection.
Structure
Self-cooled, open
(IP00)
Force-cooling, open (IP00)
Self-cooled, open
(IP00)
[ ] (Note 2) 0 to 55 (non-freezing) During
operation
[
] 32 to 131 (non-freezing)
[ ] 20 to 65 (non-freezing)
Ambient temperature
In storage
[
] 4 to 149 (non-freezing)
In operation Ambient
humidity
In storage
90%RH or less (non-condensing)
Ambient
Indoors (no direct sunlight)
Free from corrosive gas, flammable gas, oil mist, dust and dirt
Altitude Max. 1000m above sea level
Environment
Vibration 5.9 [m/s2] or less
[kg] 0.8 0.8 1.0 1.0 1.4 1.4 2.3 2.3 4.6 6.2 18 18 19 0.8 0.8 1.0
Mass
[lb] 1.8 1.8 2.2 2.2 3.1 3.1 5.071 5.071 10.1 13.7 39.68 39.68 41.88 1.8 1.8 2.2
Note 1. 150mA is the value applicable when all I/O signals are used. The current capacity can be decreased by reducing the number of
I/O points.
2. When closely mounting the servo amplifier of 3.5kW or less, operate them at the ambient temperatures of 0 to 45
or at 75% or
smaller effective load ratio.
1 - 6
1. FUNCTIONS AND CONFIGURATION
(2) 400V class
Servo Amplifier
MR-J3-
Item
60B4 100B4 200B4 350B4 500B4 700B4 11KB4 15KB4 22KB4
Voltage/frequency 3-phase 380 to 480VAC, 50/60Hz Permissible voltage fluctuation 3-phase 323 to 528VAC Permissible frequency fluctuation
Within
5%
Power supply capacity Refer to section 10.2
Power supply
Inrush current Refer to section 10.5
Voltage, frequency
1-phase 380 to 480VAC, 50/60Hz
Permissible voltage fluctuation
1-phase 323 to 528VAC
Permissible frequency fluctuation
Within
5%
Input 30W 45W
Control circuit power supply
Inrush current Refer to section 10.5 Voltage,
frequency
24VDC
10%
Interface power supply
Power supply capacity
(Note1) 150mA
Control System Sine-wave PWM control, current control system Dynamic brake Built-in External option
Protective functions
Overcurrent shut-off, regenerative overvoltage shut-off, overload shut-off (electronic thermal relay), servo motor overheat protection, encoder error protection, regenerative error protection, undervoltage, instantaneous power failure protection, overspeed protection, excessive error protection.
Structure
Self-
cooled,
open
(IP00)
Force-cooling, open (IP00)
[ ]
(Note2) 0 to
55 (non-freezing) During
operation
[
]
32 to
131 (non-freezing)
[ ]
20 to 65 (non-freezing)
Ambient temperature
In storage
[
]
4 to 149 (non-freezing)
In operation Ambient
humidity
In storage
90%RH or less (non-condensing)
Ambient
Indoors (no direct sunlight)
Free from corrosive gas, flammable gas, oil mist, dust and dirt
Altitude Max. 1000m above sea level
Environment
Vibration 5.9 [m/s2] or less
[kg] 1.7 1.7 2.1 4.6 4.6 6.2 18 18 19
Mass
[lb] 3.75 3.75 4.63 10.14 10.14 13.67 39.68 39.68 41.88
Note 1. 150mA is the value applicable when all I/O signals are used. The current capacity can be decreased by reducing the number of
I/O points.
2. When closely mounting the servo amplifier of 3.5kW or less, operate them at the ambient temperatures of 0 to 45
or at 75% or
smaller effective load ratio.
1 - 7
1. FUNCTIONS AND CONFIGURATION
1.4 Function list
The following table lists the functions of this servo. For details of the functions, refer to the reference field.
Function Description Reference
High-resolution encoder
High-resolution encoder of 262144 pulses/rev is used as a servo motor
encoder. Absolute position detection system
Merely setting a home position once makes home position return
unnecessary at every power-on.
Chapter 12
Gain changing function
You can switch between gains during rotation and gains during stop or use
an external signal to change gains during operation.
Section 7.6
Advanced vibration suppression control
This function suppresses vibration at the arm end or residual vibration. Section 7.4
Adaptive filter
Servo amplifier detects mechanical resonance and sets filter characteristics
automatically to suppress mechanical vibration.
Section 7.2
Low-pass filter
Suppresses high-frequency resonance which occurs as servo system
response is increased.
Section 7.5
Machine analyzer function
Analyzes the frequency characteristic of the mechanical system by simply
connecting a servo configuration software-installed personal computer and
servo amplifier.
MR Configurator is necessary for this function.
Machine simulation
Can simulate machine motions on a personal computer screen on the basis
of the machine analyzer results.
MR Configurator is necessary for this function.
Gain search function
Personal computer changes gains automatically and searches for overshoot-
free gains in a short time.
MR Configurator is necessary for this function. Slight vibration suppression control
Suppresses vibration of
1 pulse produced at a servo motor stop. Parameters No. PB24
Auto tuning
Automatically adjusts the gain to optimum value if load applied to the servo
motor shaft varies. Higher in performance than MR-J2-Super series servo
amplifier.
Chapter 6
Brake until
Used when the regenerative option cannot provide enough regenerative
power.
Can be used the 5kW or more servo amplifier.
Section 11.3
Return converter
Used when the regenerative option cannot provide enough regenerative
power.
Can be used the 5kW or more servo amplifier.
Section 11.4
Regenerative option
Used when the built-in regenerative resistor of the servo amplifier does not
have sufficient regenerative capability for the regenerative power generated.
Section 11.2
Alarm history clear Alarm history is cleared. Parameter No. PC21 Output signal (DO) forced output
Output signal can be forced on/off independently of the servo status.
Use this function for output signal wiring check, etc.
Section 4.5.1 (1) (d)
Test operation mode
JOG operation
positioning operation DO forced output.
However, MR Configurator is necessary for positioning operation.
Section 4.5
Analog monitor output Servo status is output in terms of voltage in real time. Parameter No. PC09
MR Configurator
Using a personal computer, parameter setting, test operation, status display,
etc. can be performed.
Section 11.8
1 - 8
1. FUNCTIONS AND CONFIGURATION
1.5 Model code definition
(1) Rating plate
MR-J3-10B
AC SERVO
POWER : INPUT :
OUTPUT: SERIAL :
100W
0.9A 3PH+1PH200-230V 50Hz
1.3A 1PH 200-230V 50/60Hz 170V 0-360Hz 1.1A
3PH+1PH200-230V 60Hz
A34230001
Model Capacity
Applicable power supply
Serial number
Rated output current
1 - 9
1. FUNCTIONS AND CONFIGURATION
(2) Model
Power supply
MR J3 B
Series
Symbol Description
-PX
Indicates a servo amplifier of 11 to 22kw that does not use a regenerative resistor as standard accessory.
With no regenerative resistor
Symbol Power supply
3-phase or 1-phase 200 to 230VAC
1-phase 100 to 120VAC
(Note 1)
None
(Note 2)
1 4 3-phase 380 to 480VAC
Note 1. 1-phase 200V to 230V is supported by 750W or less.
2. 1-phase 100V to 120V is supported by 400W or less.
SSCNET compatible
Rated output
Rated output [kW]
Symbol
10 0.1 20 0.2 40 0.4 60 0.6
70 0.75 100 1 200 2 350 3.5 500 5 700 7
11K 11 15K 15 22K 22
Rating plate
MR-J3-60B4 100B4
Rating plate
MR-J3-200B4
MR-J3-11KB(4) to 22KB(4)
Rating plate
MR-J3-350B4 500B(4)
Rating plate
Rating plate
MR-J3-200B 350B
MR-J3-100B or less
Rating plate
MR-J3-700B(4)
Rating plate
1 - 10
1. FUNCTIONS AND CONFIGURATION
1.6 Combination with servo motor
The following table lists combinations of servo amplifiers and servo motors. The same combinations apply to the models with electromagnetic brakes.
Servo motors
HF-SP
Servo amplifier
HF-MP
HF-KP
1000r/min 2000r/min
HC-RP HC-UP HC-LP
MR-J3-10B (1) 053 13 053 13 MR-J3-20B (1) 23 23 MR-J3-40B (1) 43 43
MR-J3-60B 51 52 52
MR-J3-70B 73 73 72 MR-J3-100B 81 102 102 MR-J3-200B 121 201 152 202 103
153
152 152 MR-J3-350B 301 352 203 202 202 MR-J3-500B 421 502 353
503
352
502
302 MR-J3-700B 702 MR-J3-11KB MR-J3-15KB MR-J3-22KB
Servo motors HA-LP
Servo amplifier
1000r/min 1500r/min 2000r/min
MR-J3-500B 502
MR-J3-700B 601 701M 702 MR-J3-11KB 801 12K1 11K1M 11K2 MR-J3-15KB 15K1 15K1M 15K2 MR-J3-22KB 20K1 25K1 22K1M 22K2
Servo motors
HA-LP
Servo amplifier
HF-SP
1000r/min 1500r/min 2000r/min
MR-J3-60B4 524
MR-J3-100B4 1024 MR-J3-200B4 1524 2024 MR-J3-350B4 3524 MR-J3-500B4 5024 MR-J3-700B4 7024 6014 701M4 MR-J3-11KB4 8014 12K14 11K1M4 11K24 MR-J3-15KB4 15K14 15K1M4 15K24 MR-J3-22KB4 20K14 22K1M4 22K24
1 - 11
1. FUNCTIONS AND CONFIGURATION
1.7 Structure
1.7.1 Parts identification
(1) MR-J3-100B or less
7
9
6
8
5
4
3
2
1
0
F
E
D
C
B
A
ON 4F
12
SW1
SW2
Fixed part (2 places)
Used to set the axis No. of servo amplifier.
Rotary axis setting switch (SW1)
SW2
Test operation select switch (SW2-1)
Used to perform the test operation mode by using MR Configurator.
Spare (Be sure to set to the "Down" position).
Detailed
Explanation
Section 3.13
Section 3.2 Section 3.4
SW1
Section 3.13
Name/Application
12
Display The 3-digit, seven-segment LED shows the servo status and alarm number.
Main circuit power supply connector (CNP1) Connect the input power supply.
USB communication connector (CN5) Connect the personal computer.
I/O signal connector (CN3) Used to connect digital I/O signals. More over an analog monitor is output.
Control circuit connector (CNP2) Connect the control circuit power supply/regenerative option.
SSCNET cable connector (CN1A) Used to connect the servo system controller or the front axis servo amplifier.
SSCNET cable connector (CN1B) Used to connect the rear axis servo amplifier. For the final axis, puts a cap.
Servo motor power connector (CNP3) Connect the servo motor.
Encoder connector (CN2) Used to connect the servo motor encoder.
Charge lamp Lit to indicate that the main circuit is charged. While this lamp is lit, do not reconnect the cables.
Battery connector (CN4) Used to connect the battery for absolute position data backup.
Battery holder Contains the battery for absolute position data backup.
Protective earth (PE) terminal ( ) Ground terminal.
Rating plate
7
6
5
4
3
2
1
0
F
E
D
C
B
A
9
8
Chapter 4
Section 3.1 Section 3.3
Section 11.8
Section 3.2 Section 3.4
Section 3.1 Section 3.3
Section 3.2 Section 3.4
Section 3.1 Section 3.3
Section 3.4
Section 11.1
Section 11.9
Chapter 12
Section 12.3
Section 3.1 Section 3.3
Section 1.5
TEST
1 - 12
1. FUNCTIONS AND CONFIGURATION
(2) MR-J3-60B4
MR-J3-100B4
Used to set the axis No. of servo amplifier.
Rotary axis setting switch (SW1)
SW2
Test operation select switch (SW2-1)
Used to perform the test operation mode by using MR Configurator.
Spare (Be sure to set to the "Down" position).
Detailed
Explanation
Section 3.13
Section 3.2 Section 3.4
7
9
6
8
5
4
3
2
1
0
F
E
D
C
B
A
ON 4F
12
SW1
SW1
SW2
TEST
Section 3.13
Name/Application
12
Display The 3-digit, seven-segment LED shows the servo status and alarm number.
Main circuit power supply connector (CNP1) Connect the input power supply.
USB communication connector (CN5) Connect the personal computer.
I/O signal connector (CN3) Used to connect digital I/O signals. More over an analog monitor is output.
Control circuit connector (CNP2) Connect the control circuit power supply/regenerative option.
SSCNET cable connector (CN1A) Used to connect the servo system controller or the front axis servo amplifier.
SSCNET cable connector (CN1B) Used to connect the rear axis servo amplifier. For the final axis, puts a cap.
Servo motor power connector (CNP3) Connect the servo motor.
Encoder connector (CN2) Used to connect the servo motor encoder.
Charge lamp Lit to indicate that the main circuit is charged. While this lamp is lit, do not reconnect the cables.
Battery connector (CN4) Used to connect the battery for absolute position data backup.
Battery holder Contains the battery for absolute position data backup.
Protective earth (PE) terminal ( ) Ground terminal.
Rating plate
7
6
5
4
3
2
1
0
F
E
D
C
B
A
9
8
Chapter 4
Section 3.1 Section 3.3
Section 11.8
Section 3.2 Section 3.4
Section 3.1 Section 3.3
Section 3.2 Section 3.4
Section 3.1 Section 3.3
Section 3.4
Section 11.1
Section 11.9
Chapter 12
Section 12.3
Section 3.1 Section 3.3
Section 1.5
Fixed part (3 places)
1 - 13
1. FUNCTIONS AND CONFIGURATION
(3) MR-J3-200B
MR-J3-350B
7
9
6
8
5
4
3
2
1
0
F
E
D
C
B
A
12
ON 4F
SW1
SW2
TEST
Fixed part (3 places)
Cooling fan
Used to set the axis No. of servo amplifier.
Rotary axis setting switch (SW1)
SW2
Test operation select switch (SW2-1)
Used to perform the test operation mode by using MR Configurator.
Spare (Be sure to set to the "Down" position).
Detailed
Explanation
Section 3.13
Section 3.2 Section 3.4
SW1
Section 3.13
Name/Application
12
Display The 3-digit, seven-segment LED shows the servo status and alarm number.
Main circuit power supply connector (CNP1) Connect the input power supply.
USB communication connector (CN5) Connect the personal computer.
I/O signal connector (CN3) Used to connect digital I/O signals. More over an analog monitor is output.
SSCNET cable connector (CN1A) Used to connect the servo system controller or the front axis servo amplifier.
SSCNET cable connector (CN1B) Used to connect the rear axis servo amplifier. For the final axis, puts a cap.
Servo motor power connector (CNP3) Connect the servo motor.
Encoder connector (CN2) Used to connect the servo motor encoder.
Charge lamp Lit to indicate that the main circuit is charged. While this lamp is lit, do not reconnect the cables.
Battery connector (CN4) Used to connect the battery for absolute position data backup.
Battery holder Contains the battery for absolute position data backup.
Protective earth (PE) terminal ( ) Ground terminal.
Rating plate
7
6
5
4
3
2
1
0
F
E
D
C
B
A
9
8
Chapter 4
Section 3.1 Section 3.3
Section 11.8
Section 3.2 Section 3.4
Control circuit connector (CNP2) Connect the control circuit power supply/regenerative option.
Section 3.1 Section 3.3
Section 3.2 Section 3.4
Section 3.1 Section 3.3
Section 3.4
Section 11.1
Section 11.9
Chapter 12
Section 12.3
Section 3.1 Section 3.3
Section 1.5
1 - 14
1. FUNCTIONS AND CONFIGURATION
(4) MR-J3-200B4
7
9
6
8
5
4
3
2
1
0
F
E
D
C
B
A
12
ON 4F
SW1
SW2
TEST
Fixed part (3 places)
Cooling Fan
Used to set the axis No. of servo amplifier.
Rotary axis setting switch (SW1)
SW2
Test operation select switch (SW2-1)
Used to perform the test operation mode by using MR Configurator.
Spare (Be sure to set to the "Down" position).
Detailed
Explanation
Section 3.13
Section 3.2 Section 3.4
SW1
Section 3.13
Name/Application
12
Display The 3-digit, seven-segment LED shows the servo status and alarm number.
Main circuit power supply connector (CNP1) Connect the input power supply.
USB communication connector (CN5) Connect the personal computer.
I/O signal connector (CN3) Used to connect digital I/O signals. More over an analog monitor is output.
SSCNET cable connector (CN1A) Used to connect the servo system controller or the front axis servo amplifier.
SSCNET cable connector (CN1B) Used to connect the rear axis servo amplifier. For the final axis, puts a cap.
Servo motor power connector (CNP3) Connect the servo motor.
Encoder connector (CN2) Used to connect the servo motor encoder.
Charge lamp Lit to indicate that the main circuit is charged. While this lamp is lit, do not reconnect the cables.
Battery connector (CN4) Used to connect the battery for absolute position data backup.
Battery holder Contains the battery for absolute position data backup.
Protective earth (PE) terminal ( ) Ground terminal.
Rating plate
7
6
5
4
3
2
1
0
F
E
D
C
B
A
9
8
Chapter 4
Section 3.1 Section 3.3
Section 11.8
Section 3.2 Section 3.4
Control circuit connector (CNP2) Connect the control circuit power supply/regenerative option.
Section 3.1 Section 3.3
Section 3.2 Section 3.4
Section 3.1 Section 3.3
Section 3.4
Section 11.1
Section 11.9
Chapter 12
Section 12.3
Section 3.1 Section 3.3
Section 1.5
1 - 15
1. FUNCTIONS AND CONFIGURATION
(5) MR-J3-350B4
MR-J3-500B(4)
POINT The servo amplifier is shown without the front cover. For removal of the front cover, refer to section 1.7.2.
7
9
6
8
5
4
3
2
1
0
F
E
D
C
B
A
12
ON 4F
SW1
SW2
TEST
Used to set the axis No. of servo amplifier.
Rotary axis setting switch (SW1)
SW2
Test operation select switch (SW2-1)
Used to perform the test operation mode by using MR Configurator.
Spare (Be sure to set to the "Down" position).
Detailed
Explanation
Section 3.13
Section 3.2 Section 3.4
SW1
Section 3.13
Name/Application
12
Display The 3-digit, seven-segment LED shows the servo status and alarm number.
USB communication connector (CN5) Connect the personal computer.
I/O signal connector (CN3) Used to connect digital I/O signals. More over an analog monitor is output.
SSCNET cable connector (CN1A) Used to connect the servo system controller or the front axis servo amplifier.
SSCNET cable connector (CN1B) Used to connect the rear axis servo amplifier. For the final axis, puts a cap.
Encoder connector (CN2) Used to connect the servo motor encoder.
Charge lamp Lit to indicate that the main circuit is charged. While this lamp is lit, do not reconnect the cables.
Battery connector (CN4) Used to connect the battery for absolute position data backup.
Protective earth (PE) terminal ( ) Ground terminal.
Rating plate
7
6
5
4
3
2
1
0
F
E
D
C
B
A
9
8
Chapter 4
Section 11.8
Section 3.2 Section 3.4
Section 3.2 Section 3.4
Section 3.4
Section 11.1
Section 11.9
Chapter 12
Section 3.1 Section 3.3
Section 1.5
Battery holder Contains the battery for absolute position data backup.
Section 12.3
DC reactor terminal block (TE3) Used to connect the DC reactor.
Section 3.4
Section 11.1
Main circuit terminal block (TE1) Used to connect the input power supply and servo motor.
Control circuit terminal block (TE2) Used to connect the control circuit power supply.
Section 3.1 Section 3.3
Section 3.1 Section 3.3
Cooling fan
Fixed part (4 places)
1 - 16
1. FUNCTIONS AND CONFIGURATION
(6) MR-J3-700B(4)
POINT The servo amplifier is shown without the front cover. For removal of the front cover, refer to section 1.7.2.
7
9
6
8
5
4
3
2
1
0
F
E
D
C
B
A
12
ON 4F
SW1
SW2
TEST
Used to set the axis No. of servo amplifier.
Rotary axis setting switch (SW1)
SW2
Test operation select switch (SW2-1)
Used to perform the test operation mode by using MR Configurator.
Spare (Be sure to set to the "Down" position).
Detailed
Explanation
Section 3.13
Section 3.2 Section 3.4
SW1
Section 3.13
Name/Application
12
Display The 3-digit, seven-segment LED shows the servo status and alarm number.
USB communication connector (CN5) Connect the personal computer.
I/O signal connector (CN3) Used to connect digital I/O signals. More over an analog monitor is output.
SSCNET cable connector (CN1A) Used to connect the servo system controller or the front axis servo amplifier.
SSCNET cable connector (CN1B) Used to connect the rear axis servo amplifier. For the final axis, puts a cap.
Encoder connector (CN2) Used to connect the servo motor encoder.
Charge lamp Lit to indicate that the main circuit is charged. While this lamp is lit, do not reconnect the cables.
Battery connector (CN4) Used to connect the battery for absolute position data backup.
Protective earth (PE) terminal ( ) Ground terminal.
Rating plate
7
6
5
4
3
2
1
0
F
E
D
C
B
A
9
8
Chapter 4
Section 11.8
Section 3.2 Section 3.4
Section 3.2 Section 3.4
Section 3.4
Section 11.1
Section 11.9
Chapter 12
Section 3.1 Section 3.3
Section 1.5
DC reactor terminal block (TE3) Used to connect the DC reactor.
Section 3.4
Section 11.1
Main circuit terminal block (TE1) Used to connect the input power supply and servo motor.
Control circuit terminal block (TE2) Used to connect the control circuit power supply.
Section 3.1 Section 3.3
Section 3.1 Section 3.3
Battery holder Contains the battery for absolute position data backup.
Section 12.3
Cooling fan
Fixed part (4 places)
1 - 17
1. FUNCTIONS AND CONFIGURATION
(7) MR-J3-11KB(4) to MR-J3-22KB(4)
POINT The servo amplifier is shown without the front cover. For removal of the front cover, refer to section 1.7.2.
7
9
6
8
5
4
3
2
1
0
F
E
D
C
B
A
12
ON 4F
SW1
SW2
TEST
Cooling fan
Fixed part (4 places)
Used to set the axis No. of servo amplifier.
Rotary axis setting switch (SW1)
SW2
Test operation select switch (SW2-1)
Used to perform the test operation mode by using MR Configurator.
Spare (Be sure to set to the "Down" position).
Detailed
Explanation
Section 3.13
Section 3.2 Section 3.4
SW1
Section 3.13
Name/Application
12
Display The 3-digit, seven-segment LED shows the servo status and alarm number.
USB communication connector (CN5) Connect the personal computer.
I/O signal connector (CN3) Used to connect digital I/O signals. More over an analog monitor is output.
SSCNET cable connector (CN1A) Used to connect the servo system controller or the front axis servo amplifier.
SSCNET cable connector (CN1B) Used to connect the rear axis servo amplifier. For the final axis, puts a cap.
Encoder connector (CN2) Used to connect the servo motor encoder.
Charge lamp Lit to indicate that the main circuit is charged. While this lamp is lit, do not reconnect the cables.
Battery connector (CN4) Used to connect the battery for absolute position data backup.
Rating plate
7
6
5
4
3
2
1
0
F
E
D
C
B
A
9
8
Chapter 4
Section 11.8
Section 3.2 Section 3.4
Section 3.2 Section 3.4
Section 3.4
Section 11.1
Section 11.9
Chapter 12
Section 1.5
Section 3.1 Section 3.3
Battery holder Contains the battery for absolute position data backup.
Section 12.3
Main circuit terminal block control circuit protective earth (TE) Used to connect the input power supply, servo motor, regenerative option and ground.
1 - 18
1. FUNCTIONS AND CONFIGURATION
1.7.2 Removal and reinstallation of the front cover
WARNING
Before removing or installing the front cover, turn off the power and wait for 15 minutes or more until the charge lamp turns off. Then, confirm that the voltage between P(
) and N( ) is safe with a voltage tester and others. Otherwise, an electric shock may occur. In addition, always confirm from the front of the servo amplifier whether the charge lamp is off or not.
(1) For MR-J3-350B4
MR-J3-500B(4) MR-J3-700B(4)
Removal of the front cover
A)
A)
Hold the ends of lower side of the front cover with both hands.
Pull up the cover, supporting at point
A)
.
Pull out the front cover to remove.
1 - 19
1. FUNCTIONS AND CONFIGURATION
Reinstallation of the front cover
Front cover setting tab
A)
A)
Insert the front cover setting tabs into the sockets of servo amplifier (2 places).
Pull up the cover, supporting at point
A)
.
Setting tab
Push the setting tabs until they click.
1 - 20
1. FUNCTIONS AND CONFIGURATION
(2) For MR-J3-11KB(4) to MR-J3-22KB(4)
Removal of the front cover
A)
B)
C)
1) Press the removing knob on the lower side of the front cover ( A) and B) ) and release the installation hook.
2) Press the removing knob of C) and release the external hook.
3) Pull it to remove the front cover.
Reinstallation of the front cover
A)
B)
C)
D)
(Note2)
(Note1)
(Note1)
Installation hoo
k
1) Fit the front cover installation hooks on the sockets of body cover ( A) to D) ) to reinstall it.
2) Push the front cover until you hear the clicking noise of the installation hook.
Note 1. The cooling fan cover can be locked with enclosed screws (M4 40).
2. By drilling approximately
4 of a hole on the front cover, the front cover can be locked on the body with an enclosed screw (M4
14).
1 - 21
1. FUNCTIONS AND CONFIGURATION
1.8 Configuration including auxiliary equipment
POINT Equipment other than the servo amplifier and servo motor are optional or recommended products.
(1) MR-J3-100B or less
(a) For 3-phase or 1-phase 200V to 230VAC
W
CN5
PC
L11
L
21
P
1
P2
UV
Servo amplifier
L
1
L
2
L3
MR Configurator
Personal computer
Servo system controller or Front axis servo amplifier CN1B
Rear servo amplifier CN1A or Cap
CN3
CN1A
CN1B
CN2
CN4
R S T
Line noise filter (FR-BSF01)
Magnetic contactor (MC)
No-fuse breaker (NFB) or fuse
Regenerative option
Power factor improving DC reactor (FR-BEL)
(Note 2)
(Note 2)
Junction terminal block
Servo motor
(Note 1) Battery MR-J3BAT
(Note 3) Power supply
Note 1. The battery (option) is used for the absolute position detection system in the position control mode.
2. The AC reactor can also be used. In this case, the DC reactor cannot be used. When not using DC reactor, short P
1-P2.
3. A 1-phase 200V to 230VAC power supply may be used with the servo amplifier of MR-J3-70B or less. For 1-phase 200V to 230VAC, connect the power supply to L
1 L2 and leave L3 open. Refer to section 1.3 for the power supply
specification.
1 - 22
1. FUNCTIONS AND CONFIGURATION
(b) For 1-phase 100V to 120VAC
(Note 2)
W
UV
CN5
PC
CN3
CN1A
CN1B
CN2
CN4
L11
L
21
L
1
L
2
(Note 3) Power supply
R S
Power factor improving (FR-BAL)
Regenerative option
Servo amplifier
(Note 1) Battery MR-J3BAT
Line noise filter (FR-BSF01)
Magnetic contactor (MC)
No-fuse breaker (NFB) or fuse
Junction terminal block
Servo motor
Servo system controller or Front axis servo amplifier CN1B
Rear servo amplifier CN1A or Cap
MR Configurator
Personal computer
Note 1. The battery (option) is used for the absolute position detection system in the position control mode.
2. The power factor improving DC reactor cannot be used.
3. Refer to section 1.3 for the power supply specification.
1 - 23
1. FUNCTIONS AND CONFIGURATION
(2) MR-J3-60B4
MR-J3-100B4
R S T
No-fuse breaker (NFB) or fuse
Magnetic contactor (MC)
(Note 2)
Line noise filter (FR-BSF01)
L
2
L
3
(Note 2) Power factor
improving DC reactor (FR-BEL-H)
P
1
P2
Regenerative option
PC
L
11
L
21
UVW
(Note 1) Battery MR-J3BAT
CN5
CN3
CN1A
CN1B
CN2
CN4
MR Configurator
Personal computer
Junction terminal block
Servo system controller or Front axis servo amplifier CN1B
Rear servo amplifier CN1A or Cap
Servo motor
Servo amplifier
(Note 3) Power supply
L
1
Note 1. The battery (option) is used for the absolute position detection system in the position control mode.
2. The AC reactor can also be used. In this case, the DC reactor cannot be used. When not using DC reactor, short P
1-P2.
3. A 1-phase 200V to 230VAC power supply may be used with the servo amplifier of MR-J3-70B or less. For 1-phase 200V to 230VAC, connect the power supply to L
1 L2 and leave L3 open. Refer to section 1.3 for the power supply
specification.
1 - 24
1. FUNCTIONS AND CONFIGURATION
(3) MR-J3-200B
MR-J3-350B
R S T
P C
L
21
P
1
P2
UV
W
L
11
L1 L
2
L
3
CN5
CN3
CN2
CN1A
CN1B
CN4
Line noise filter (FR-BSF01)
(Note 4) Power supply
Magnetic contactor (MC)
No-fuse breaker (NFB) or fuse
Regenerative option
(Note 2) Power factor improving DC reactor (FR-BEL)
(Note 3)
(Note 2)
Servo amplifier
Junction terminal block
MR Configurator
Personal computer
(Note 1) Battery MR-J3BAT
Servo system controller or Front axis servo amplifier CN1B
Rear servo amplifier CN1A or Cap
Servo motor
Note 1. The battery (option) is used for the absolute position detection system in the position control mode.
2. The AC reactor can also be used. In this case, the DC reactor cannot be used. When not using DC reactor, short P
1-P2.
3. For MR-J3-350B, use FR-BLF.
4. Refer to section 1.3 for the power supply specification.
1 - 25
1. FUNCTIONS AND CONFIGURATION
(4) MR-J3-200B4
R S T
L
21
L
11
C
P
(Note 3) Power supply
No-fuse breaker (NFB) or fuse
Magnetic contactor (MC)
(Note 2)
Line noise filter (FR-BSF01)
(Note 2) Power factor improving DC reactor (FR-BEL-H)
L
1
L
2
L3
P1
Regenerative option
Servo amplifier
CN5
CN3
CN1A
CN1B
CN2
CN4
(Note 1) Battery MR-J3BAT
Junction terminal block
Servo system controller or Front axis servo amplifier CN1B
Rear servo amplifier CN1A or Cap
MR Configurator
Servo motor
UV W
Personal computer
P2
Note 1. The battery (option) is used for the absolute position detection system in the position control mode.
2. The AC reactor can also be used. In this case, the DC reactor cannot be used. When not using DC reactor, short P
1-P2.
3. Refer to section 1.3 for the power supply specification.
1 - 26
1. FUNCTIONS AND CONFIGURATION
(5) MR-J3-350B4
MR-J3-500B(4)
R S T
L
21
P
1
P
2
CN3
CN2
CN1A
CN1B
CN4
CN5
(Note 2)
L
11
UVW
CP
L
1
L
2
L3
Regenerative option
Line noise filter (FR-BLF)
(Note 3) Power supply
Magnetic contactor (MC)
No-fuse breaker (NFB) or fuse
MR Configurator
Personal computer
Servo amplifier
(Note 2) Power factor improving DC reactor (FR-BEL-(H))
Servo system controller or Front axis servo amplifier CN1B
Rear servo amplifier CN1A or Cap
(Note 1) Battery MR-J3BAT
Servo motor
Junction terminal block
Note 1. The battery (option) is used for the absolute position detection system in the position control mode.
2. The AC reactor can also be used. In this case, the DC reactor cannot be used. When not using DC reactor, short P
1-P2.
3. Refer to section 1.3 for the power supply specification.
1 - 27
1. FUNCTIONS AND CONFIGURATION
(6) MR-J3-700B(4)
R S T
L21L
11
UVW
CP
L
1
L
2
L
3
CN5
CN3
CN2
CN1A
CN1B
CN4
P
2
P
1
Line noise filter (FR-BLF)
(Note 3) Power supply
Magnetic contactor (MC)
No-fuse breaker (NFB) or fuse
(Note 2)
(Note 2) Power factor improving DC reactor (FR-BEL-(H))
Servo amplifier
Regenerative option
Servo motor
Junction terminal block
MR Configurator
Personal computer
Servo system controller or Front axis servo amplifier CN1B
Rear servo amplifier CN1A or Cap
(Note 1) Battery MR-J3BAT
Note 1. The battery (option) is used for the absolute position detection system in the position control mode.
2. The AC reactor can also be used. In this case, the DC reactor cannot be used. When not using DC reactor, short P
1-P2.
3. Refer to section 1.3 for the power supply specification.
1 - 28
1. FUNCTIONS AND CONFIGURATION
(7) MR-J3-11KB(4) to MR-J3-22KB(4)
Line noise filter (FR-BLF)
(Note 3) Power supply
R S T
Magnetic
contactor
(MC)
No-fuse breaker (NFB) or fuse
Regenerative option
L
21
Servo amplifier
Servo motor
(Note 2)
L
11
UVW
CP
L
1
L2
L3
CN4
MR Configurator
Personal computer
CN5
CN3
CN2
Junction terminal block
Servo system controller or Front axis servo amplifier CN1B
Rear servo amplifier CN1A or Cap
CN1A
CN1B
P
1
P
(Note 2) Power factor improving DC reactor (FR-BEL-(H))
(Note 1) Battery MR-J3BAT
Note 1. The battery (option) is used for the absolute position detection system in the position control mode.
2. The AC reactor can also be used. In this case, the DC reactor cannot be used. When not using DC reactor, short P
1-P.
3. Refer to section 1.3 for the power supply specification.
2 - 1
2. INSTALLATION
2. INSTALLATION
CAUTION
Stacking in excess of the limited number of products is not allowed. Install the equipment on incombustible material. Installing them directly or close to
combustibles will lead to a fire.
Install the equipment in a load-bearing place in accordance with this Instruction
Manual.
Do not get on or put heavy load on the equipment to prevent injury. Use the equipment within the specified environmental condition range. (For the
environmental conditions, refer to section 1.3.)
Provide an adequate protection to prevent screws, metallic detritus and other conductive matter or oil and other combustible matter from entering the servo amplifier.
Do not block the intake/exhaust ports of the servo amplifier. Otherwise, a fault may occur.
Do not subject the servo amplifier to drop impact or shock loads as they are precision equipment.
Do not install or operate a faulty servo amplifier.
When the product has been stored for an extended period of time, consult Mitsubishi.
When treating the servo amplifier, be careful about the edged parts such as the corners of the servo amplifier.
2.1 Installation direction and clearances
CAUTION
The equipment must be installed in the specified direction. Otherwise, a fault may occur.
Leave specified clearances between the servo amplifier and control box inside walls or other equipment.
(1) 7kW or less
(a) Installation of one servo amplifier
40mm or more
Servo amplifier
40mm or more
Control box
10mm or more
10mm or more
Wiring allowance
80mm
Top
Bottom
Control box
2 - 2
2. INSTALLATION
(b) Installation of two or more servo amplifiers
POINT Mounting closely is available for a combination of servo amplifiers of 3.5kW or
less in 200V or 100V class.
Leave a large clearance between the top of the servo amplifier and the internal surface of the control box, and install a cooling fan to prevent the internal temperature of the control box from exceeding the environmental conditions. When installing the servo amplifiers closely, leave a clearance of 1mm between the adjacent servo amplifiers in consideration of mounting tolerances. In this case, bring the ambient temperature within 0 to 45
, or use it at 75% or smaller effective load ratio.
40mm or more
Control box
30mm or more
30mm or more
Control box
Leaving clearance
Mounting closely
30mm or more
1mm 1mm
100mm or more
30mm or more
100mm or more
10mm or more
40mm or more
(2) 11k to 22kW
(a) Installation of one servo amplifier
40mm or more
10mm or more
120mm or more
Wiring allowance
80mm
Top
Bottom
Servo amplifier
Control box Control box
10mm or more
2 - 3
2. INSTALLATION
(b) Installation of two or more servo amplifiers
Leave a large clearance between the top of the servo amplifier and the internal surface of the control box, and install a cooling fan to prevent the internal temperature of the control box from exceeding the environmental conditions.
100mm or more
30m or more
120mm or more
30mm or more
10mm or more
Control box
(3) Others
When using heat generating equipment such as the regenerative option, install them with full consideration of heat generation so that the servo amplifier is not affected. Install the servo amplifier on a perpendicular wall in the correct vertical direction.
2.2 Keep out foreign materials
(1) When installing the unit in a control box, prevent drill chips and wire fragments from entering the servo
amplifier.
(2) Prevent oil, water, metallic dust, etc. from entering the servo amplifier through openings in the control box or
a cooling fan installed on the ceiling.
(3) When installing the control box in a place where there are much toxic gas, dirt and dust, conduct an air
purge (force clean air into the control box from outside to make the internal pressure higher than the external pressure) to prevent such materials from entering the control box.
2.3 Cable stress
(1) The way of clamping the cable must be fully examined so that flexing stress and cable's own weight stress
are not applied to the cable connection.
(2) For use in any application where the servo motor moves, fix the cables (encoder, power supply, brake)
supplied with the servo motor, and flex the optional encoder cable or the power supply and brake wiring cables. Use the optional encoder cable within the flexing life range. Use the power supply and brake wiring cables within the flexing life of the cables.
(3) Avoid any probability that the cable sheath might be cut by sharp chips, rubbed by a machine corner or
stamped by workers or vehicles.
(4) For installation on a machine where the servo motor will move, the flexing radius should be made as large
as possible. Refer to section 10.4 for the flexing life.
2 - 4
2. INSTALLATION
2.4 SSCNET
cable laying
SSCNET
cable is made from optical fiber. If optical fiber is added a power such as a major shock, lateral pressure, haul, sudden bending or twist, its inside distorts or breaks, and optical transmission will not be available. Especially, as optical fiber for MR-J3BUS
M MR-J3BUS M-A is made of synthetic resin, it melts down if being left near the fire or high temperature. Therefore, do not make it touched the part, which becomes high temperature, such as radiator or regenerative option of servo amplifier.
Read described item of this section carefully and handle it with caution.
(1) Minimum bend radius
Make sure to lay the cable with greater radius than the minimum bend radius. Do not press the cable to edges of equipment or others. For SSCNET
cable, the appropriate length should be selected with due consideration for the dimensions and arrangement of servo amplifier. When closing the door of control box, pay careful attention for avoiding the case that SSCNET
cable is hold down by the door and the cable bend becomes smaller than the minimum bend radius. For the minimum bend radius, refer to section 11.1.5.
(2) Prohibition of vinyl tape use
Migrating plasticizer is used for vinyl tape. Keep the MR-J3BUS
M, and MR-J3BUS M-A cables away
from vinyl tape because the optical characteristic may be affected.
SSCNET cable Code Cable
MR-J3BUS M MR-J3BUS M-A MR-J3BUS M-B
Optical code Cable
: Phthalate ester plasticizer such as DBP and DOP
may affect optical characteristic of cable.
: Cable is not affected by plasticizer.
(3) Precautions for migrating plasticizer added materials
Generally, soft polyvinyl chloride (PVC), polyethylene resin (PE) and Teflon (fluorine resin) contain non­migrating plasticizer and they do not affect the optical characteristic of SSCNET
cable. However, some wire sheaths and cable ties, which contain migrating plasticizer (phthalate ester), may affect MR-J3BUS
M and MR-J3BUS M-A cables.
In addition, MR-J3BUS
M-B cable is not affected by plasticizer.
2 - 5
2. INSTALLATION
(4) Bundle fixing
Fix the cable at the closest part to the connector with bundle material in order to prevent SSCNET
cable
from putting its own weight on CN1A
CN1B connector of servo amplifier. Optical cord should be given loose slack to avoid from becoming smaller than the minimum bend radius, and it should not be twisted. When bundling the cable, fix and hold it in position by using cushioning such as sponge or rubber which does not contain migratable plasticizers. If using adhesive tape for bundling the cable, fire resistant acetate cloth adhesive tape 570F (Teraoka Seisakusho Co., Ltd) is recommended.
Optical cord Loose slack
Recommended product: NK clamp SP type ( NIX, INC.)
Cable
Connector
Bundle material
(5) Tension
If tension is added on optical cable, the increase of transmission loss occurs because of external force which concentrates on the fixing part of optical fiber or the connecting part of optical connector. At worst, the breakage of optical fiber or damage of optical connector may occur. For cable laying, handle without putting forced tension. For the tension strength, refer to section 11.1.5.
(6) Lateral pressure
If lateral pressure is added on optical cable, the optical cable itself distorts, internal optical fiber gets stressed, and then transmission loss will increase. At worst, the breakage of optical cable may occur. As the same condition also occurs at cable laying, do not tighten up optical cable with a thing such as nylon band (TY-RAP). Do not trample it down or tuck it down with the door of control box or others.
(7) Twisting
If optical fiber is twisted, it will become the same stress added condition as when local lateral pressure or bend is added. Consequently, transmission loss increases, and the breakage of optical fiber may occur at worst.
(8) Disposal
When incinerating optical cable (cord) used for SSCNET
, hydrogen fluoride gas or hydrogen chloride gas which is corrosive and harmful may be generated. For disposal of optical fiber, request for specialized industrial waste disposal services who has incineration facility for disposing hydrogen fluoride gas or hydrogen chloride gas.
2 - 6
2. INSTALLATION
2.5 Inspection items
WARNING
Before starting maintenance and/or inspection, turn off the power and wait for 15 minutes or more until the charge lamp turns off. Then, confirm that the voltage between P(
) and N( ) is safe with a voltage tester and others. Otherwise, an electric shock may occur. In addition, always confirm from the front of the servo amplifier whether the charge lamp is off or not.
Any person who is involved in inspection should be fully competent to do the work. Otherwise, you may get an electric shock. For repair and parts replacement, contact your safes representative.
POINT Do not test the servo amplifier with a megger (measure insulation resistance),
or it may become faulty.
Do not disassemble and/or repair the equipment on customer side.
It is recommended to make the following checks periodically:
(1) Check for loose terminal block screws. Retighten any loose screws.
(2) Check the cables and the like for scratches and cracks. Perform periodic inspection according to operating
conditions.
2.6 Parts having service lives
The following parts must be changed periodically as listed below. If any part is found faulty, it must be changed immediately even when it has not yet reached the end of its life, which depends on the operating method and environmental conditions. For parts replacement, please contact your sales representative.
Part name Life guideline
Smoothing capacitor 10 years
Relay
Number of power-on and number of emergency stop times : 100,000 times
Cooling fan 10,000 to 30,000hours (2 to 3 years)
Servo amplifier
Absolute position battery Refer to section 12.2
(1) Smoothing capacitor
Affected by ripple currents, etc. and deteriorates in characteristic. The life of the capacitor greatly depends on ambient temperature and operating conditions. The capacitor will reach the end of its life in 10 years of continuous operation in normal air-conditioned environment.
(2) Relays
Their contacts will wear due to switching currents and contact faults occur. Relays reach the end of their life when the cumulative number of power-on and emergency stop times is 100,000, which depends on the power supply capacity.
(3) Servo amplifier cooling fan
The cooling fan bearings reach the end of their life in 10,000 to 30,000 hours. Normally, therefore, the cooling fan must be changed in a few years of continuous operation as a guideline. It must also be changed if unusual noise or vibration is found during inspection.
3 - 1
3. SIGNALS AND WIRING
3. SIGNALS AND WIRING
WARNING
Any person who is involved in wiring should be fully competent to do the work.
Before wiring, turn off the power and wait for 15 minutes or more until the charge lamp turns off. Then, confirm that the voltage between P(
) and N( ) is safe with a voltage tester and others. Otherwise, an electric shock may occur. In addition, always confirm from the front of the servo amplifier whether the charge lamp is off or not.
Ground the servo amplifier and the servo motor securely. Do not attempt to wire the servo amplifier and servo motor until they have been
installed. Otherwise, you may get an electric shock.
The cables should not be damaged, stressed excessively, loaded heavily, or
pinched. Otherwise, you may get an electric shock.
CAUTION
Wire the equipment correctly and securely. Otherwise, the servo motor may
misoperate, resulting in injury.
Connect cables to correct terminals to prevent a burst, fault, etc. Ensure that polarity ( , ) is correct. Otherwise, a burst, damage, etc. may occur.
The surge absorbing diode installed to the DC relay designed for control output should be fitted in the specified direction. Otherwise, the signal is not output due to a fault, disabling the forced stop (EM1) and other protective circuits.
RA
DOCOM
DICOM
24VDC
Servo Amplifier
Control output signal
RA
DOCOM
DICOM
24VDC
Control output signal
Servo amplifier
Use a noise filter, etc. to minimize the influence of electromagnetic interference, which may be given to electronic equipment used near the servo amplifier.
Do not install a power capacitor, surge suppressor or radio noise filter (FR-BIF (-H) option) with the power line of the servo motor.
When using the regenerative resistor, switch power off with the alarm signal. Otherwise, a transistor fault or the like may overheat the regenerative resistor, causing a fire.
Do not modify the equipment.
During power-on, do not open or close the motor power line. Otherwise, a malfunction or faulty may occur.
3 - 2
3. SIGNALS AND WIRING
3.1 Input power supply circuit
CAUTION
Always connect a magnetic contactor (MC) between the main circuit power supply and L
1, L2, and L3 of the servo amplifier, and configure the wiring to be able to shut
down the power supply on the side of the servo amplifier’s power supply. If a magnetic contactor (MC) is not connected, continuous flow of a large current may cause a fire when the servo amplifier malfunctions.
Use the trouble signal to switch main circuit power supply off. Otherwise, a regenerative transistor fault or the like may overheat the regenerative resistor, causing a fire.
POINT Even if alarm has occurred, do not switch off the control circuit power supply.
When the control circuit power supply has been switched off, optical module does not operate, and optical transmission of SSCNET
communication is interrupted. Therefore, the servo amplifier on the rear axis displays "AA" at the indicator and turns into base circuit shut-off. The servo amplifier stops with starting dynamic brake.
Wire the power supply/main circuit as shown below so that power is shut off and the servo-on command turned off as soon as an alarm occurs, a servo forced stop is made valid, or a controller forced stop is made valid. A no-fuse breaker (NFB) must be used with the input cables of the main circuit power supply.
(1) For 3-phase 200V to 230VAC power supply to MR-J3-10B to MR-J3-350B
EM1
NFB MC
L
1
L
2
L3
ALM RA1
P1
P
DICOM
DOCOM
L11
L21
N
D
C
U
V
W
(Note 1)
(Note 2)
CNP1
CNP3
PE
CNP2
U
V
W
2
3
4
1
M
Motor
Encoder
CN2
24VDC
(Note 3)
Encoder cable
(Note 6)
DOCOM
Forced stop
CN3CN3
OFF
Forced
stop
ON
MC
MC
SK
(Note 4)
Alarm
RA1
Controller
forced stop
RA2
Servo amplifier Servo motor
(Note 5)
Trouble
(Note 4)
(Note 5)
3-phase 200 to 230VAC
P
2
3 - 3
3. SIGNALS AND WIRING
Note 1. Always connect P1-P2. (Factory-wired.) When using the power factor improving DC reactor, refer to section 11.13.
2. Always connect P-D. (Factory-wired.) When using the regenerative option, refer to section 11.2.
3. For the encoder cable, use of the option cable is recommended. Refer to section 11.1 for selection of the cable.
4. If deactivating output of trouble (ALM) with parameter change, configure up the power supply circuit which switches off the magnetic contactor after detection of alarm occurrence on the controller side.
5. For the sink I/O interface. For the source I/O interface, refer to section 3.7.3.
6. Refer to section 3.10.
(2) For 1-phase 200V to 230VAC power supply to MR-J3-10B to MR-J3-70B
L
2
L3
P1
P
L
11
L21
N
D
C
P
2
EM1
NFB MC
L
1
1-phase 200 to 230VAC
ALM RA1
DICOM
DOCOM
U
V
W
(Note 1)
(Note 2)
CNP1
CNP3
PE
CNP2
U
V
W
2
3
4
1
M
Motor
Encoder
CN2
24VDC
(Note 3)
Encoder cable
(Note 6)
DOCOM
Forced stop
CN3CN3
OFF
Forced
stop
ON
MC
MC
SK
(Note 4)
Alarm
RA1
Controller
forced stop
RA2
Servo amplifier Servo motor
(Note 5)
Trouble (Note 4)
(Note 5)
Note 1. Always connect P1-P2. (Factory-wired.) When using the power factor improving DC reactor, refer to section 11.13.
2. Always connect P-D. (Factory-wired.) When using the regenerative option, refer to section 11.2.
3. For the encoder cable, use of the option cable is recommended. Refer to section 11.1 for selection of the cable.
4. If deactivating output of trouble (ALM) with parameter change, configure up the power supply circuit which switches off the magnetic contactor after detection of alarm occurrence on the controller side.
5. For the sink I/O interface. For the source I/O interface, refer to section 3.7.3.
6. Refer to section 3.10.
3 - 4
3. SIGNALS AND WIRING
(3) For MR-J3-10B1 to MR-J3-40B1
EM1
NFB MC
L
1
L2
1-phase 100 to 120VAC
ALM RA1
P1
P
DICOM
DOCOM
L11
L21
N
D
C
U
V
W
(Note 1)
(Note 2)
CNP1
CNP3
PE
CNP2
U
V
W
2
3
4
1
M
Motor
Encoder
CN2
24VDC
(Note 3)
Encoder cable
(Note 6)
DOCOM
Forced stop
CN3CN3
OFF
Forced
stop
ON
MC
MC
SK
(Note 4)
Alarm
RA1
Controller
forced stop
RA2
Servo amplifier Servo motor
(Note 5)
Trouble (Note 4)
(Note 5)
Blank
P2
Note 1. Always connect P1-P2. (Factory-wired.) The power factor improving DC reactor cannot be used.
2. Always connect P-D. (Factory-wired.) When using the regenerative option, refer to section 11.2.
3. For the encoder cable, use of the option cable is recommended. Refer to section 11.1 for selection of the cable.
4. If deactivating output of trouble (ALM) with parameter change, configure up the power supply circuit which switches off the magnetic contactor after detection of alarm occurrence on the controller side.
5. For the sink I/O interface. For the source I/O interface, refer to section 3.7.3.
6. Refer to section 3.10.
3 - 5
3. SIGNALS AND WIRING
(4) MR-J3-60B4 to MR-J3-200B4
EM1
NFB MC
L
1
L
2
L3
3-phase 200 to 230VAC
ALM RA1
P1
P
DICOM
DOCOM
L11
L21
N
D
C
U
V
W
(Note 1)
(Note 2)
CNP1
CNP3
PE
CNP2
U
V
W
2
3
4
1
M
Motor
Encoder
CN2
24VDC
(Note 3)
Encoder cable
(Note 6)
DOCOM
Forced stop
CN3CN3
OFF
Forced
stop
ON
MC
MC
SK
(Note 4)
Alarm
RA1
Controller
forced stop
RA2
Servo amplifier Servo motor
(Note 5)
Trouble (Note 4)
(Note 5)
(Note 7)
Stepdown
transformer
P2
Note 1. Always connect P1-P2. (Factory-wired.) When using the power factor improving DC reactor, refer to section 11.13.
2. Always connect P-D. (Factory-wired.) When using the regenerative option, refer to section 11.2.
3. For the encoder cable, use of the option cable is recommended. Refer to section 11.1 for selection of the cable.
4. If deactivating output of trouble (ALM) with parameter change, configure up the power supply circuit which switches off the magnetic contactor after detection of alarm occurrence on the controller side.
5. For the sink I/O interface. For the source I/O interface, refer to section 3.7.3.
6. Refer to section 3.10.
7. Stepdown transformer is required for coil voltage of magnetic contactor more than 200V class.
3 - 6
3. SIGNALS AND WIRING
(5) MR-J3-500B
MR-J3-700B
EM1
NFB MC
L
1
L
2
L
3
ALM RA1
P1
DICOM
DOCOM
N
U
V
W
(Note 2)
(Note 1)
TE1
PE
U
V
W
2
3
4
1
M
Motor
Encoder
CN2
24VDC
(Note 3)
Encoder cable
(Note 6)
DOCOM
Forced stop
CN3CN3
OFF
Forced
stop
ON
MC
MC
SK
(Note 4)
Alarm
RA1
Controller
forced stop
RA2
Servo amplifier Servo motor
(Note 5)
Trouble (Note 4)
(Note 5)
3-phase 200 to 230VAC
L11
L
21
TE2
P1
P
2
N
TE3
Built-in
regenerative
resistor
Cooling fan
(Note 7) Power supply of Cooling fan
BU
BV
Note 1. Always connect P1-P2. (Factory-wired.) When using the power factor improving DC reactor, refer to section 11.13.
2. When using the regenerative option, refer to section 11.2.
3. For the encoder cable, use of the option cable is recommended. Refer to section 11.1 for selection of the cable.
4. If deactivating output of trouble (ALM) with parameter change, configure up the power supply circuit which switches off the magnetic contactor after detection of alarm occurrence on the controller side.
5. For the sink I/O interface. For the source I/O interface, refer to section 3.7.3.
6. Refer to section 3.10.
7. A cooling fan is attached to the HA-LP601 and the HA-LP701M servo motors. For power supply specification of the cooling fan, refer to Section 3.10.2 (3) (b).
3 - 7
3. SIGNALS AND WIRING
(6) MR-J3-350B4 to MR-J3-700B4
EM1
NFB MC
L
1
L
2
L
3
ALM RA1
C
DICOM
DOCOM
P
U
V
W
(Note 2)
(Note 1)
TE1
PE
U
V
W
2
3
4
1
M
Motor
Encoder
CN2
24VDC
(Note 3)
Encoder cable
(Note 6)
DOCOM
Forced stop
CN3CN3
OFF
Forced
stop
ON
MC
MC
SK
(Note 4)
Alarm
RA1
Controller
forced stop
RA2
Servo amplifier Servo motor
(Note 5)
Trouble (Note 4)
(Note 5)
3-phase 380 to 480VAC
L11
L
21
TE2
P1
P
2
N
TE3
Built-in
regenerative
resistor
(Note 7)
Stepdown
transformer
Cooling fan
(Note 8) Power supply of Cooling fan
BU
BV
Note 1. Always connect P1-P2. (Factory-wired.) When using the power factor improving DC reactor, refer to section 11.13.
2. When using the regenerative option, refer to section 11.2.
3. For the encoder cable, use of the option cable is recommended. Refer to section 11.1 for selection of the cable.
4. If deactivating output of trouble (ALM) with parameter change, configure up the power supply circuit which switches off the magnetic contactor after detection of alarm occurrence on the controller side.
5. For the sink I/O interface. For the source I/O interface, refer to section 3.7.3.
6. Refer to section 3.10.
7. Stepdown transformer is required for coil voltage of magnetic contactor more than 200V class.
8. A cooling fan is attached to the HA-LP6014 and the HA-LP701M4 servo motors. For power supply specification of the cooling fan, refer to Section 3.10.2 (3) (b).
3 - 8
3. SIGNALS AND WIRING
(7) MR-J3-11KB to MR-J3-22KB
BW
BV
BU
Dynamic
break
(Option)
OFF
Forced
stop
ON
MC
MC
SK
(Note 4)
Alarm
RA1
Controller
forced stop
RA2
Servo amplifier
NFB MC
L
1
L
2
L
3
3-phase 200 to 230VAC
P
C
TE1
PE
L
11
L
21
U
V
W
M
Encoder
CN2
(Note 3)
Encoder cable
(Note 6)
P
1
(Note 1)
(Note 2)
Regenerative
resistor
Cooling fan
24VDC
power supply
OHS2OHS1
Servo motor thermal relay
Servo motor
thermal relay
RA3
RA3
U
V
W
Servo motor
(Note 7)
EM1
ALM
RA1
DICOM
DOCOM
24VDC
DOCOM
Forced stop
CN3CN3
(Note 5)
Trouble (Note 4)
(Note 5)
Note 1. Always connect P1-P. (Factory-wired.) When using the power factor improving DC reactor, refer to section 11.13.
2. When using the regenerative option, refer to section 11.2.
3. For the encoder cable, use of the option cable is recommended. Refer to section 11.1 for selection of the cable.
4. If deactivating output of trouble (ALM) with parameter change, configure up the power supply circuit which switches off the magnetic contactor after detection of alarm occurrence on the controller side.
5. For the sink I/O interface. For the source I/O interface, refer to section 3.7.3.
6. Refer to section 3.10.
7. Cooling fan power supply of the HA-LP11K2 servo motor is 1-phase. Power supply specification of the cooling fan is different from that of the servo amplifier. Therefore, separate power supply is required.
3 - 9
3. SIGNALS AND WIRING
(8) MR-J3-11KB4 to MR-J3-22KB4
BW
BV
BU
Cooling fan
(Note 7)
(Note 8) Cooling fan power supply
Dynamic
break
(Option)
OFF
Forced
stop
ON
MC
MC
SK
(Note 4)
Alarm
RA1
Controller
forced stop
RA2
Servo amplifier
NFB MC
L
1
L
2
L3
3-phase 380 to 480VAC
P
C
TE1
PE
L
11
L
21
U
V
W
M
Encoder
CN2
(Note 3)
Encoder cable
(Note 6)
P
1
(Note 1)
(Note 2)
Regenerative
resistor
24VDC
power supply
OHS2OHS1
Servo motor thermal relay
Servo motor
thermal relay
RA3
RA3
U
V
W
Servo motor
(Note 7)
EM1
ALM RA1
DICOM
DOCOM
24VDC
DOCOM
Forced stop
CN3CN3
(Note 5)
Trouble (Note 4)
(Note 5)
(Note 9)
Stepdown
transformer
Note 1. Always connect P1-P. (Factory-wired.) When using the power factor improving DC reactor, refer to section 11.13.
2. When using the regenerative option, refer to section 11.2.
3. For the encoder cable, use of the option cable is recommended. Refer to section 11.1 for selection of the cable.
4. If deactivating output of trouble (ALM) with parameter change, configure up the power supply circuit which switches off the magnetic contactor after detection of alarm occurrence on the controller side.
5. For the sink I/O interface. For the source I/O interface, refer to section 3.7.3.
6. Refer to section 3.10.
7. Servo amplifiers does not have BW when the cooling fan power supply is 1-phase.
8. For the cooling fan power supply, refer to section 3.10.2 (3) (b).
9. Stepdown transformer is required for coil voltage of magnetic contactor more than 200V class.
3 - 10
3. SIGNALS AND WIRING
3.2 I/O signal connection example
13
9
15
10
6
16
7
17
2 12 19
CN3
Encoder Z-phase pulse (differential line driver)
2m Max
(Note12)
(Note5) MR Configurator
Personal computer
Magnetic brake interlock
(Note2)
CN5
Servo amplifier
CN1A
Servo system
controller
USB cable
MR-J3USBCBL3M
(option)
Trouble (Note11)
In-position
CN3
(Note12)
CN1A
CN1B
MR-J3-B
(2 axis)
(Note7)
(Note9) Cap
(Note1)
CN1B
SW1
21
SW2
SW1
21
SW2
Between electrodes
Control common
(Note8)
(Note8)
CN1A
CN1B
MR-J3-B
(Note7)
SW1
21
SW2
(Note8)
CN1A
CN1B
MR-J3-B
(Note7)
SW1
21
SW2
(Note8)
(Note13,14)
24VDC
Power supply
(Note10)
(Note3,4)Forced stop
(Note14)
(3 axis)
(n axis)
(Note6) SSCNET cable (option)
(Note6) SSCNET cable (option)
Analog monitor 2 Max. 1mA meter both directions
Analog monitor 1 Max. 1mA meter both directions
10k
Encoder B-phase pulse (differential line driver)
Encoder A-phase pulse (differential line driver)
A
A
10k
(Note15)
RA3
RA2
RA1
DICOM
DOCOM
EM1
DI1 DI2 DI3
5
3 20
DICOM
MBR
INP
ALM
LA
LAR
LB
LBR
8LZ 18 LZR 11 LG
4MO1
1LG 14 MO2
Plate SD
3 - 11
3. SIGNALS AND WIRING
Note 1 To prevent an electric shock, always connect the protective earth (PE) terminal (terminal marked ) of the servo amplifier to the
protective earth (PE) of the control box.
2. Connect the diode in the correct direction. If it is connected reversely, the servo amplifier will be faulty and will not output signals, disabling the forced stop (EM1) and other protective circuits.
3. If the controller does not have an forced stop (EM1) function, always install a forced stop switch (Normally closed).
4. When starting operation, always turn on the forced stop (EM1). (Normally closed contacts) By setting "
1 " in DRU
parameter No.PA04 of the drive unit, the forced stop (EM1) can be made invalid.
5. Use MRZJW3-SETUP 221E.
6. For the distance between electrodes of SSCNET
cable, refer to the following table.
Cable Cable model name Cable length
Distance between
electrodes Standard code inside panel MR-J3BUS M 0.15m to 3m Standard cable outside panel MR-J3BUS M-A 5m to 20m
20m
Long-distance cable MR-J3BUS M-B 30m to 50m 50m
7. The wiring of the second and subsequent axes is omitted.
8. Up to eight axes (n
1 to 8) may be connected. Refer to section 3.13 for setting of axis selection.
9. Make sure to put a cap on the unused CN1A
CN1B.
10. Supply 24VDC
10% 150mA current for interfaces from the outside. 150mA is the value applicable when all I/O signals are used. The current capacity can be decreased by reducing the number of I/O points. Refer to section 3.7.2 (1) that gives the current value necessary for the interface.
11. Trouble (ALM) turns on in normal alarm-free condition. When this signal is switched off (at occurrence of an alarm), the output of the programmable controller should be stopped by the sequence program.
12. The pins with the same signal name are connected in the servo amplifier.
13. The signal can be changed by parameter No.PD07, PD08, PD09.
14. For the sink I/O interface. For the source I/O interface, refer to section 3.7.3.
15. Devices can be assigned for DI1
DI2 DI3 with controller setting. For devices that can be assigned, refer to the controller
instruction manual. The following devices can be assigned for Q172HCPU
Q173HCPU QD75MH. DI1: upper stroke limit (FLS) DI2: lower stroke limit (RLS) DI3: Proximity dog (DOG)
3 - 12
3. SIGNALS AND WIRING
3.3 Explanation of power supply system
3.3.1 Signal explanations
POINT For the layout of connector and terminal block, refer to outline drawings in chapter 9.
Abbreviation
Connection Target
(Application)
Description
Supply the following power to L1, L2, L3. For the 1-phase 200V to 230VAC power supply, connect the power supply to L
1, L2, and keep L3 open.
Servo amplifier
Power supply
MR-J3-
10B to 70B
MR-J3-
100B to
22KB
MR-J3-
10B1 to
40B1 3-phase 200V to 230VAC, 50/60Hz L1 L2 L3 1-phase 200V to 230VAC, 50/60Hz L1 L2 1-phase 100V to 120VAC, 50/60Hz L1 L2
Servo amplifier
Power supply
MR-J3-60B4 to 22KB4
3-phase 380V to 480VAC, 50/60Hz L1 L2 L3
L1 L
2
L
3
Main circuit power supply
P1 P
2
Power factor improving DC reactor
1) MR-J3-700B(4) or less When not using the power factor improving DC reactor, connect P
1-P2. (Factory-wired.)
When using the power factor improving DC reactor, disconnect the wiring across P
1-P2 and
connect the power factor improving DC reactor across P
1-P2.
2) MR-J3-11KB(4) to 22KB(4) MR-J3-11KB(4) to 22KB(4) do not have P
2 terminal.
When not using the power factor improving reactor, connect P
1-P. (Factory-wired)
When using the power factor improving reactor, connect it across P
1-P.
Refer to section 11.13.
P C D
Regenerative option
1) MR-J3-350B or less
MR-J3-200B4 or less
When using servo amplifier built-in regenerative resistor, connect between P(
)-D terminals. (Wired by default) When using regenerative option, disconnect between P(
)-D terminals and connect
regenerative option to P terminal and C terminal.
2) MR-J3-350B4
500B(4) 700B(4)
MR-J3-350B4
500B(4) and 700B(4) do not have D terminal. When using servo amplifier built-in regenerative resistor, connect P terminal and C terminal. (Wired by default) When using regenerative option, disconnect P terminal and C terminal and connect regenerative option to P terminal and C terminal.
3) MR-J3-11KB(4) to 22KB(4) MR-J3-11KB(4) to 22KB(4) do not have D terminal. When not using the power supply return converter and the brake unit, make sure to connect the regenerative option to P terminal and C terminal. Refer to section 14.2 to 14.5.
Supply the following power to L11 L21.
Servo amplifier
Power supply
MR-J3-10B to
22KB
MR-J3-10B1 to
40B1
MR-J3-60B4 to
22KB4
1-phase 200V to 230VAC, 50/60Hz L11 L21 1-phase 100V to 120VAC, 50/60Hz L11 L21 1-phase 380V to 480VAC, 50/60Hz L11 L21
L11 L
21
Control circuit power supply
U V
W
Servo motor power
Connect to the servo motor power supply terminals (U, V, W). During power-on, do not open or close the motor power line. Otherwise, a malfunction or faulty may occur.
N
Return converter Brake unit
When using return converter/brake unit, connect to P terminal and N terminal. Do not connect to servo amplifier MR-J3-350B(4) or less.
For details, refer to section 11.3 to 11.5. Protective earth (PE)
Connect to the earth terminal of the servo motor and to the protective earth (PE) of the control
box to perform grounding.
3 - 13
3. SIGNALS AND WIRING
3.3.2 Power-on sequence
(1) Power-on procedure
1) Always wire the power supply as shown in above section 3.1 using the magnetic contactor with the main circuit power supply (three-phase: L
1
, L2, L3, single-phase: L1, L2). Configure up an external sequence to
switch off the magnetic contactor as soon as an alarm occurs.
2) Switch on the control circuit power supply L
11
, L21 simultaneously with the main circuit power supply or before switching on the main circuit power supply. If the main circuit power supply is not on, the display shows the corresponding warning. However, by switching on the main circuit power supply, the warning disappears and the servo amplifier will operate properly.
3) The servo amplifier can accept the servo-on command within 3s the main circuit power supply is switched on. (Refer to paragraph (2) of this section.)
(2) Timing chart
(3s)
ON
OFF
ON
OFF
ON
OFF
10ms 95ms95ms
Base circuit
Servo-on command (from controller)
SON accepted
Main circuit Control circuit
power
(3) Forced stop
CAUTION
Install an forced stop circuit externally to ensure that operation can be stopped and
power shut off immediately.
If the controller does not have an forced stop function, make up a circuit that switches off main circuit power as soon as EM1 is turned off at a forced stop. When EM1 is turned off, the dynamic brake is operated to stop the servo motor. At this time, the display shows the servo forced stop warning (E6). During ordinary operation, do not use forced stop (EM1) to alternate stop and run. The service life of the servo amplifier may be shortened.
DICOM
DOCOM
EM1
24VDC
Servo amplifier
Forced stop
(Note)
Note. For the sink I/O interface. For the source I/O interface, refer to section 3.7.3.
3 - 14
3. SIGNALS AND WIRING
3.3.3 CNP1, CNP2, CNP3 wiring method
POINT Refer to table 11.1 in section 11.11 for the wire sizes used for wiring. MR-J3-500B or more MR-J3-350B4 or more does not have these connectors.
Use the supplied servo amplifier power supply connectors for wiring of CNP1, CNP2 and CNP3.
(1) MR-J3-10B to MR-J3-100B
(a) Servo amplifier power supply connectors
CNP2
CNP1
CNP3
Connector for CNP1
54928-0670 (Molex)
Connector for CNP2
54927-0520 (Molex)
Connector for CNP3
54928-0370 (Molex)
<Applicable cable example> Cable finish OD: to 3.8mm
(Note)Servo amplifier power supply connectors
Servo amplifier
Note. These connectors are of insert type. As the crimping type, the following connectors (Molex) are recommended.
For CNP1: 51241-0600 (connector), 56125-0128 (terminal) For CNP2: 51240-0500 (connector), 56125-0128 (terminal) For CNP3: 51241-0300 (connector), 56125-0128 (terminal) Crimping tool: CNP57349-5300 <Connector applicable cable example>
Cable finish OD: to
3.8mm
(b) Termination of the cables
Solid wire: After the sheath has been stripped, the cable can be used as it is.
8 to 9mm
Sheath
Core
Twisted wire: Use the cable after stripping the sheath and twisting the core. At this time, take care to avoid a
short caused by the loose wires of the core and the adjacent pole. Do not solder the core as it may cause a contact fault. Alternatively, a bar terminal may be used to put the wires together.
Cable size Bar terminal type
[mm2] AWG For 1 cable (Note 1) For 2 cable
Crimping tool (Note 2)
1.25/1.5 16 AI1.5-10BK AI-TWIN2 1.5-10BK
2/2.5 14 AI2.5-10BU
Variocrimp 4 206-204
Note 1. Manufacturer: Phoenix Contact
2. Manufacturer: WAGO JAPAN
3 - 15
3. SIGNALS AND WIRING
(c) The twin type connector for CNP2 (L
11 L21): 721-2105/026-000 (WAGO JAPAN)
Using this connector enables passing a wire of control circuit power supply. Refer to Appendix 3 for details of connector.
L
21
L11
L
21
L
11
Power supply or Front axis
Rear axis
CNP2
Twin type connector for CNP2
(2) MR-J3-200B
MR-J3-350B
(a) Servo amplifier power supply connectors
Servo amplifier power supply connectors
CNP3
CNP1
CNP2
Connector for CNP1
PC4/6-STF-7.62-CRWH
(Phoenix Contact)
<Applicable cable example> Cable finish OD: 5mm or less
Connector for CNP3
PC4/3-STF-7.62-CRWH
(Phoenix Contact)
Connector for CNP2(Note)
54927-0520 (Molex)
Servo amplifier
<Applicable cable example> Cable finish OD: 3.8mm or less
Note. As twin type connector for CNP2 (L11, L21) is the same as MR-J3-100B or smaller. Refer to (1) (c) of this section.
3 - 16
3. SIGNALS AND WIRING
(b) Termination of the cables
1) CNP1
CNP3
Solid wire: After the sheath has been stripped, the cable can be used as it is.
7mm
Sheath
Core
Twisted wire: Use the cable after stripping the sheath and twisting the core. At this time, take care to avoid a
short caused by the loose wires of the core and the adjacent pole. Do not solder the core as it may cause a contact fault. Alternatively, a bar terminal may be used to put the wires together.
Cable size Bar terminal type
[mm2] AWG For 1 cable For 2 cables
Crimping tool Manufacturer
1.25/1.5 16 AI1.5-8BK AI-TWIN2 1.5-8BK
2.0/2.5 14 AI2.5-8BU AI-TWIN2 2.5-10BU CRIMPFOX-ZA3 Phoenix Contact
3.5 12 AI4-10GY
2) CNP2 CNP2 is the same as MR-J3-100B or smaller capacities. Refer to (1) (b) of this section.
(3) MR-J3-60B4 to MR-J3-200B4
(a) Servo amplifier power supply connectors
<Applicable cable example> Cable finish OD: 4.1mm or less
Servo amplifier
Connector for CNP3
721-203/026-000(Plug)
(WAGO JAPAN)
Servo amplifier power supply connectors
CNP2
CNP1
CNP3
Connector for CNP1
721-207/026-000(Plug)
(WAGO JAPAN)
Connector for CNP2
721-205/026-000(Plug)
(WAGO JAPAN)
3 - 17
3. SIGNALS AND WIRING
(b) Termination of the cables
Solid wire: After the sheath has been stripped, the cable can be used as it is.
8 to 9mm
Sheath
Core
Twisted wire: Use the cable after stripping the sheath and twisting the core. At this time, take care to avoid a
short caused by the loose wires of the core and the adjacent pole. Do not solder the core as it may cause a contact fault. Alternatively, a bar terminal may be used to put the wires together.
Cable size Bar terminal type
[mm2] AWG For 1 cable (Note 1) For 2 cable
Crimping tool (Note 2)
1.25/1.5 16 AI1.5-10BK AI-TWIN2 1.5-10BK
2/2.5 14 AI2.5-10BU
Variocrimp 4 206-204
Note 1. Manufacturer: Phoenix Contact
2. Manufacturer: WAGO JAPAN
(c) The twin type connector for CNP2 (L
11 L21): 721-2205/026-000 (WAGO JAPAN)
Using this connector enables passing a wire of control circuit power supply. Refer to Appendix 3 for details of connector.
L
21
L11
L
21
L
11
Power supply or Front axis
Rear axis
CNP2
Twin type connector for CNP2
(4) Insertion of cable into Molex and WAGO JAPAN connectors
Insertion of cable into 54928-0610, 54927-0510, 54928 (Molex) connectors and 721-207/026-000, 721-205/ 026-000 and 721-203/026-000 (WAGO JAPAN) connectors are as follows. The following explains for Molex, however use the same procedures for inserting WAGO JAPAN connectors as well.
POINT It may be difficult for a cable to be inserted to the connector depending on wire size or bar terminal configuration. In this case, change the wire type or correct it in order to prevent the end of bar terminal from widening, and then insert it.
How to connect a cable to the servo amplifier power supply connector is shown below.
3 - 18
3. SIGNALS AND WIRING
(a) When using the supplied cable connection lever
1) The servo amplifier is packed with the cable connection lever.
a) 54932-0000 (Molex)
[Unit: mm]
MXJ 54932
7.7
4.7
Approx. 3 4.9
10
20.6
3.46.5 Approx. 4.9
Approx. 7.7
Approx.3.4
b) 231-131 (WAGO JAPAN)
[Unit: mm]
20.3
10
16
7.6
3
6.5
3.4
4.9
17.5
1.5
1.3
3 - 19
3. SIGNALS AND WIRING
2) Cable connection procedure
1) Attach the cable connection lever to the housing. (Detachable)
2) Push the cable connection lever in the direction of arrow.
3) Hold down the cable connection lever and insert the cable in the direction of arrow.
4) Release the cable connection lever.
Cable connection lever
3 - 20
3. SIGNALS AND WIRING
(b) Inserting the cable into the connector
1) Applicable flat-blade screwdriver dimensions Always use the screwdriver shown here to do the work.
[Unit: mm]
3
0.6
Approx. R0.3
Approx. 22
3 to 3.5
Approx. R0.3
2) When using the flat-blade screwdriver - part 1
1) Insert the screwdriver into the square hole. Insert it along the top of the square hole to insert it smoothly.
2) If inserted properly, the screwdriver is held.
3) With the screwdriver held, insert the cable in the direction
of arrow. (Insert the cable as far as it will go.)
4) Releasing the screwdriver connects the cable.
3 - 21
3. SIGNALS AND WIRING
3) When using the flat-blade screwdriver - part 2
1) Insert the screwdriver into the square window at top of the connector.
2) Push the screwdriver in the direction of arrow.
3) With the screwdriver pushed, insert the cable in the direction of arrow. (Insert the cable as far as it will go.)
4) Releasing the screwdriver connects the cable.
3 - 22
3. SIGNALS AND WIRING
(4) How to insert the cable into Phoenix Contact connector
POINT Do not use a precision driver because the cable cannot be tightened with enough torque.
Insertion of cables into Phoenix Contact connector PC4/6-STF-7.62-CRWH or PC4/3-STF-7.62-CRWH is shown as follows. Before inserting the cable into the opening, make sure that the screw of the terminal is fully loose. Insert the core of the cable into the opening and tighten the screw with a flat-blade screwdriver. When the cable is not tightened enough to the connector, the cable or connector may generate heat because of the poor contact. (When using a cable of 1.5mm
2
or less, two cables may be inserted into one opening.) Secure the connector to the servo amplifier by tightening the connector screw. For securing the cable and the connector, use a flat-blade driver with 0.6mm blade edge thickness and
3.5mm diameter (Recommended flat-blade screwdriver: Phoenix Contact SZS 0.6
3.5). Apply 0.5 to 0.6
N
m torque to screw.
[Unit: mm]
Flat-blade screwdriver
To loosen To tighten
Wire
Opening
To loosen To tighten
Flat-blade screwdriver
Connector screw
Servo amplifier power supply connector
3.5 0.6
180
100
(35)
Recommended flat-blade screwdriver dimensions
3 - 23
3. SIGNALS AND WIRING
3.4 Connectors and signal arrangements
POINT The pin configurations of the connectors are as viewed from the cable connector wiring section.
(1) Signal arrangement
The servo amplifier front view shown is that of the MR-J3-20B or less. Refer to chapter 9 Outline Drawings for the appearances and connector layouts of the other servo amplifiers.
The 3M make connector is shown. When using any other connector, refer to section 11.1.2.
9
4
MRR
2
LG
8
6
1
P5
5
10
3
MR
7
BAT
CN2
MDR
MD
CN4 CN2L CN2 CN1B CN1A CN3 CN5
CHARGE
L2
U
W
V
D
L
12
L
11
C
P
N
P
1
P
2
L
3
L1
OPEN
CN5 (USB connector) Refer to section 11.8.
CN3
The frames of the CN2 and CN3 connectors are connected to the PE (earth) terminal ( ) in the amplifier.
Connector for the front axis of CN1A SSCNET cable.
Connector for the rear axis of CN1B SSCNET cable.
2
111
12
4
313
14
6
515
16
8
717
18
10
919
20
DI1
LG LG
DI2
MO1
DOCOM
MBR
MO2
LA
DICOM
ALM
LAR
LZ
LB LBR
LZR
DICOM
INP DI1
EM1
3 - 24
3. SIGNALS AND WIRING
3.5 Signal (device) explanations
For the I/O interfaces (symbols in I/O division column in the table), refer to section 3.7.2. In the control mode field of the table The pin No.s in the connector pin No. column are those in the initial status.
(1) Connector applications
Connector Name Function/Application
CN1A Connector for bus cable
from preceding axis.
Used for connection with the controller or preceding-axis servo amplifier.
CN1B Connector for bus cable to
next axis
Used for connection with the next-axis servo amplifier or for connection of the cap.
CN2 Encoder connector Used for connection with the servo motor encoder. CN4 Battery connection
connector
When using as absolute position detection system, connect to battery (MR­J3BAT). Before installing a battery, turn off the main circuit power while keeping the control circuit power on. Wait for 15 minutes or more (20 minutes or for drive unit 30kW or more) until the charge lamp turns off. Then, confirm that the voltage between P(
)
and N(
) (L and L for drive unit 30kW or more) is safe with a voltage tester and others. Otherwise, an electric shock may occur. In addition, always confirm from the front of the servo amplifier whether the charge lamp is off or not. Replace the battery with main circuit power OFF and with control circuit power ON. Replacing the battery with the control circuit power OFF results in loosing absolute position data.
CN5 Communication connector The personal computer is connected.
(2) I/O device
(a) Input device
Device Symbol
Connector
Pin No.
Function/Application
I/O
division
Forced stop EM1 CN3-20 Turn EM1 off (open between commons) to bring the motor to an forced
stop state, in which the base circuit is shut off and the dynamic brake is operated. Turn EM1 on (short between commons) in the forced stop state to reset that state. When parameter No.PA.04 is set to "
1 ", automatically ON (always
ON) can be set inside.
DI-1
DI1 CN3-2 DI-1
DI2 CN3-12 DI-1
DI3 CN3-19
Devices can be assigned for DI1 DI2 DI3 with controller setting. For devices that can be assigned, refer to the controller instruction manual. The following devices can be assigned for Q172HCPU Q173HCPU QD75MH. DI1: upper stroke limit (FLS) DI2: lower stroke limit (RLS) DI3: near-point dog (DOG)
DI-1
3 - 25
3. SIGNALS AND WIRING
(b) Output device
Device Symbol
Connector
Pin No.
Function/Application
I/O
division
Trouble ALM CN3-15 ALM turns off when power is switched off or the protective circuit is
activated to shut off the base circuit. Without alarm occurring, ALM turns on within about 1s after power-on.
DO-1
Electromagnetic brake interlock
MBR CN3-13 When using this signal, set operation delay time of the electromagnetic
brake in parameter No.PC02. In the servo-off or alarm status, MBR turns off.
DO-1
In-position (Positioning completed)
INP CN3-9 INP turns on when the number of droop pulses is in the preset in-position
range. The in-position range can be changed using parameter No. PA10. When the in-position range is increased, INP may be on conductive status during low-speed rotation. INP turns on when servo on turns on. This signal cannot be used in the speed loop mode.
DO-1
Ready RD When using the signal, make it usable by the setting of parameter
No.PD07 to PD09. RD turns on when the servo is switched on and the servo amplifier is ready to operate.
DO-1
Dynamic brake interlock
DB When using the signal, make it usable by the setting of parameter
No.PD07 to PD09. DB turns off simultaneously when the dynamic brake is operated. When using the external dynamic brake on the servo amplifier of 11 kW or more, this device is required. (Refer to section
11.6.) For the servo amplifier of 7kW or less, it is not necessary to use this device.
DO-1
Speed reached SA When using this signal, make it usable by the setting of parameter
No.PD07 to PD09. When the servo is off, SA will be turned OFF. When servo motor rotation speed becomes approximately setting speed, SA will be turned ON. When the preset speed is 20r/min or less, SA always turns on. This signal cannot be used in position loop mode.
DO-1
Limiting torque TLC When using this signal, make it usable by the setting of parameter
No.PD07 to PD09. When torque is produced level of torque set with controller, TLC will be turned ON. When the servo is off, TLC will be turned OFF.
DO-1
Zero speed ZSP
When using this signal, make it usable by the setting of parameter No.PD07 to PD09. When the servo is off, SA will be turned OFF. ZSP turns on when the servo motor speed is zero speed (50r/min) or less. Zero speed can be changed using parameter No. PC07. Example Zero speed is 50r/min
OFF
ON
0r/min
1)
3)
2)
4)
Forward rotation direction
Servo motor speed
Reverse rotation direction
zero speed (ZSP)
ON level 50r/min
OFF level 70r/min
ON level 50r/min
OFF level 70r/min
Parameter No. PC07
20r/min (Hysteresis width)
20r/min (Hysteresis width)
Parameter No. PC07
ZPS turns on 1) when the servo motor is decelerated to 50r/min, and ZPS turns off 2) when the servo motor is accelerated to 70r/min again. ZPS turns on 3) when the servo motor is decelerated again to 50r/min, and turns off
4)
when the servo motor speed has reached -70r/min. The range from the point when the servo motor speed has reached ON level, and ZPS turns on, to the point when it is accelerated again and has reached OFF level is called hysteresis width. Hysteresis width is 20r/min for the MR-J3-B servo amplifier.
DO-1
3 - 26
3. SIGNALS AND WIRING
Device Symbol
Connector
Pin No.
Function/Application
I/O
division
Warning WNG
When using this signal, make it usable by the setting of parameter No.PD07 to PD09. When warning has occurred, WNG turns on. When there is no warning, WNG turns off within about 1.5s after power-on.
DO-1
Battery warning BWNG
When using this signal, make it usable by the setting of parameter No.PD07 to PD09. BWNG turns on when battery cable breakage warning (92) or battery warning (9F) has occurred.When there is no battery warning, BWNG turns off within about 1.5s after power-on.
DO-1
Variable gain selection
CDPS
When using this signal, make it usable by the setting of parameter No.PD07 to PD09. CDPS is on during variable gain.
DO-1
Absolute position erasing
ABSV
When using this signal, make it usable by the setting of parameter No.PD07 to PD09. ABSV turns on when the absolute position erased. This signal cannot be used in position loop mode.
DO-1
(c) Output signals
Signal name Symbol
Connector
Pin No.
Function/Application
Encoder A-phase pulse (Differential line driver)
LA
LAR
CN3-6
CN3-16
Encoder B-phase pulse (Differential line driver)
LB
LBR
CN3-7
CN3-17
Outputs pulses per servo motor revolution set in parameter No. PA15 in the differential line driver system. In CCW rotation of the servo motor, the encoder B­phase pulse lags the encoder A-phase pulse by a phase angle of
/2. The relationships between rotation direction and phase difference of the A- and B­phase pulses can be changed using parameter No. PC03. Output pulse specification and dividing ratio setting can be set. (Refer to section
5.1.9.)
Encoder Z-phase pulse (Differential line driver)
LZ
LZR
CN3-8
CN3-18
Outputs the zero-point signal in the differential line driver system of the encoder. One pulse is output per servo motor revolution. turns on when the zero-point position is reached. The minimum pulse width is about 400
s. For home position return using this pulse,
set the creep speed to 100r/min. or less.
Analog monitor 1 MO1 CN3-4 Used to output the data set in parameter No. PC09 to across MO1-LG in terms of
voltage. Resolution 10 bits
Analog monitor 2 MO2 CN3-14 Used to output the data set in parameter No. PC10 to across MO2-LG in terms of
voltage. Resolution 10 bits
(d) Power supply
Signal name Symbol
Connector
Pin No.
Function/Application
Digital I/F power supply input
DICOM CN3-5
CN3-10
Used to input 24VDC (24VDC 10% 150mA) for I/O interface of the servo amplifier. The power supply capacity changes depending on the number of I/O interface points to be used. Connect the positive terminal of the 24VDC external power supply for the sink interface.
Digital I/F common DOCOM CN3-3 Common terminal for input signals such as EM1 of the servo amplifier. Pins are
connected internally. Separated from LG. Connect the positive terminal of the 24VDC external power supply for the source interface.
Monitor common LG CN3-1
CN3-11
Common terminal of M01 M02 Pins are connected internally.
Shield SD Plate Connect the external conductor of the shield cable.
3 - 27
3. SIGNALS AND WIRING
3.6 Alarm occurrence timing chart
CAUTION
When an alarm has occurred, remove its cause, make sure that the operation signal is not being input, ensure safety, and reset the alarm before restarting operation.
As soon as an alarm occurs, make the Servo off status and interrupt the main circuit power.
When an alarm occurs in the servo amplifier, the base circuit is shut off and the servo motor is coated to a stop. Switch off the main circuit power supply in the external sequence. To deactivate the alarm, power the control circuit off, then on or give the error reset or CPU reset command from the servo system controller. However, the alarm cannot be deactivated unless its cause is removed.
ON
OFF
ON
OFF
ON
OFF
NO
YES
ON
OFF
1s
NO
YES
Main circuit Control circuit
power
Base circuit
Dynamic brake
Servo-on command (from controller)
Alarm
Reset command (from controller)
Valid
Invalid
Alarm occurs.
Remove cause of trouble.
50ms or more 60ms or more
NO
Brake operation
Brake operation
Power on
Power off
(Note)
Note. Switch off the main circuit power as soon as an alarm occurs.
(1) Overcurrent, overload 1 or overload 2
If operation is repeated by switching control circuit power off, then on to reset the overcurrent (32), overload 1 (50) or overload 2 (51) alarm after its occurrence, without removing its cause, the servo amplifier and servo motor may become faulty due to temperature rise. Securely remove the cause of the alarm and also allow about 30 minutes for cooling before resuming operation.
(2) Regenerative alarm
If operation is repeated by switching control circuit power off, then on to reset the regenerative (30) alarm after its occurrence, the external regenerative resistor will generate heat, resulting in an accident.
(3) Instantaneous power failure
Undervoltage (10) occurs when the input power is in either of the following statuses.
A power failure of the control circuit power supply continues for 60ms or longer and the control circuit is not completely off. The bus voltage dropped to 200VDC or less for the MR-J3- B, to 158VDC or less for the MR-J3- B1, or to 380VDC or less for the MR-J3-
B4.
3 - 28
3. SIGNALS AND WIRING
3.7 Interfaces
3.7.1 Internal connection diagram
3
EM1
CN3
20
DI1 2
DI2 12
DI3 19
DICOM
5
3
CN3
10
13
9
15
DICOM
(Note 2)
INP
ALM
CN3
6
16
7
17
8
18
LA
LAR
LB
LBR
LZ
LZR
RA
CN3
MO1
MO2
LG
4
14
11
RA
Differential line driver output (35mA or less)
<Isolated>
Approx
5.6k
Analog monitor
Servo amplifier
2
4
7 8
MR
MRR
MD
MDR
LG
Encoder
E
Servo motor
(Note 1)
USB
M
D
GND
VBUS
D12
3 5
CN5
LG1
MBR
DOCOM
24VDC
Forced stop
CN2
(Note 3)
(Note 3)
Approx
5.6k
10VDC
10VDC
Note 1. Signal can be assigned for these pins with host controller setting.
For contents of signals, refer to the instruction manual of host controller.
2. This signal cannot be used with speed loop mode.
3. For the sink I/O interface. For the source I/O interface, refer to section 3.7.3.
3 - 29
3. SIGNALS AND WIRING
3.7.2 Detailed description of interfaces
This section provides the details of the I/O signal interfaces (refer to the I/O division in the table) given in section 3.5. Refer to this section and make connection with the external equipment.
(1) Digital input interface DI-1
Give a signal with a relay or open collector transistor. Refer to section 3.7.3 for the source input.
DICOM
V
CES
1.0V
I
CEO
100 A
TR
24VDC 10%
5.6k
For transistor
Approx. 5mA
Switch
150mA
Servo amplifier
EM1, etc.
(2) Digital output interface DO-1
A lamp, relay or photocoupler can be driven. Install a diode (D) for an inductive load, or install an inrush current suppressing resistor (R) for a lamp load. (Permissible current: 40mA or less, inrush current: 100mA or less) A maximum of 2.6V voltage drop occurs in the servo amplifier. Refer to section 3.7.3 for the source output.
If polarity of diode is reversed, servo amplifier will fail.
Servo amplifier
ALM, etc.
Load
DOCOM
24VDC 10% 150mA
(Note)
Note. If the voltage drop (maximum of 2.6V) interferes with the relay operation, apply high voltage (up to
26.4V) from external source.
3 - 30
3. SIGNALS AND WIRING
(3) Encoder pulse output DO-2 (Differential line driver system)
(a) Interface
Max. output current: 35mA
LA (LB, LZ)
LAR (LBR, LZR)
LG
SD
LA (LB, LZ)
LAR (LBR, LZR)
SD
Servo amplifier Servo amplifier
Am26LS32 or equivalent High-speed photocoupler
150
100
b) Output pulse
Servo motor CCW rotation
LA
LAR
LB
LBR
LZ
LZR
T
/2
400 s or more
Time cycle (T) is determined by the settings of parameter No.PA15 and PC03.
(4) Analog output
LG
MO1
Servo amplifier
Output voltage 10V Max. 1mA Max. Output current Resolution: 10 bi
t
(MO2)
3 - 31
3. SIGNALS AND WIRING
3.7.3 Source I/O interfaces
In this servo amplifier, source type I/O interfaces can be used. In this case, all DI-1 input signals and DO-1 output signals are of source type. Perform wiring according to the following interfaces.
(1) Digital input interface DI-1
EM1, etc.
Servo amplifier
Switch
Approx. 5mA
DICOM
V
CES
1.0V
I
CEO
100 A
24VDC 10% 150mA
Approx. 5.6k
(2) Digital output interface DO-1
A maximum of 2.6V voltage drop occurs in the servo amplifier.
If polarity of diode is reversed, servo amplifier will fail.
Servo amplifier
ALM, etc.
Load
DOCOM
24VDC 10% 150mA
(Note)
Note. If the voltage drop (maximum of 2.6V) interferes with the relay operation, apply high voltage (up to
26.4V) from external source.
3 - 32
3. SIGNALS AND WIRING
3.8 Treatment of cable shield external conductor
In the case of the CN2 and CN3 connectors, securely connect the shielded external conductor of the cable to the ground plate as shown in this section and fix it to the connector shell.
External conductor Sheath
External conductor
Pull back the external conductor to cover the sheath
SheathCore
Strip the sheath.
(1) For CN3 connector (3M connector)
Screw
Screw
Ground plate
Cable
(2) For CN2 connector (3M or Molex connector)
Screw
Cable
Ground plate
3 - 33
3. SIGNALS AND WIRING
3.9 SSCNET
cable connection
POINT Do not see directly the light generated from CN1A CN1B connector of servo amplifier or the end of SSCNET
cable. When the light gets into eye, may feel something is wrong for eye. (The light source of SSCNET
complies with class1 defined in JIS C6802 or
IEC60825-1.)
(1) SSCNET
cable connection
For CN1A connector, connect SSCNET
cable connected to controller in host side or servo amplifier.
For CN1B, connect SSCNET
cable connected to servo amplifier in lower side.
For CN1B connector of the final axis, put a cap came with servo amplifier.
SSCNET cable
CN1B
CN1A
CN1B
CN1A
Controller
Axis No.1 servo amplifier Axis No.2 servo amplifier Final axis servo amplifier
CN1B
CN1A
Cap
SSCNET cable SSCNET cable
(2) How to connect/disconnect cable.
POINT CN1A CN1B connector is put a cap to protect light device inside connector from dust. For this reason, do not remove a cap until just before mounting SSCNET cable. Then, when removing SSCNET
cable, make sure to put a cap.
Keep the cap for CN1A CN1B connector and the tube for protecting light code end of SSCNET
cable in a plastic bag with a zipper of SSCNET
cable to prevent them from becoming dirty.
When asking repair of servo amplifier for some troubles, make sure to put a cap on CN1A
CN1B connector. When the connector is not put a cap, the light device may be damaged at the transit. In this case, exchange and repair of light device is required.
(a) Mounting
1) For SSCNET
cable in the shipping status, the tube for protect light code end is put on the end of
connector. Remove this tube.
2) Remove the CN1A
CN1B connector cap of servo amplifier.
3 - 34
3. SIGNALS AND WIRING
3) With holding a tab of SSCNET
cable connector, make sure to insert it into CN1A CN1B connector of servo amplifier until you hear the click. If the end face of optical code tip is dirty, optical transmission is interrupted and it may cause malfunctions. If it becomes dirty, wipe with a bonded textile, etc. Do not use solvent such as alcohol.
Click
Tab
(b) Removal
With holding a tab of SSCNET
cable connector, pull out the connector.
When pulling out the SSCNET
cable from servo amplifier, be sure to put the cap on the connector parts of servo amplifier to prevent it from becoming dirty. For SSCNET
cable, attach the tube for protection optical code's end face on the end of connector.
3 - 35
3. SIGNALS AND WIRING
3.10 Connection of servo amplifier and servo motor
CAUTION
During power-on, do not open or close the motor power line. Otherwise, a
malfunction or faulty may occur.
3.10.1 Connection instructions
WARNING
Insulate the connections of the power supply terminals to prevent an electric
shock.
CAUTION
Connect the wires to the correct phase terminals (U, V, W) of the servo amplifier
and servo motor. Otherwise, the servo motor will operate improperly.
Do not connect AC power supply directly to the servo motor. Otherwise, a fault
may occur.
POINT Refer to section 11.1 for the selection of the encoder cable.
This section indicates the connection of the servo motor power (U, V, W). Use of the optional cable and connector set is recommended for connection between the servo amplifier and servo motor. When the options are not available, use the recommended products. Refer to section 11.1 for details of the options.
(1) For grounding, connect the earth cable of the servo motor to the protective earth (PE) terminal (
) of the servo amplifier and connect the ground cable of the servo amplifier to the earth via the protective earth of the control box. Do not connect them directly to the protective earth of the control panel.
Servo amplifier
Servo motor
PE terminal
Control box
(2) Do not share the 24VDC interface power supply between the interface and electromagnetic brake. Always
use the power supply designed exclusively for the electromagnetic brake.
3 - 36
3. SIGNALS AND WIRING
3.10.2 Power supply cable wiring diagrams
(1) HF-MP service
HF-KP series HF-KP series servo motor
(a) When cable length is 10m or less
CNP3
AWG 19(red) AWG 19(white) AWG 19(black)
AWG 19(green/yellow)
W
V
U
Servo motorServo amplifier
10m or less
MR-PWS1CBL M-A1-L MR-PWS1CBL M-A2-L MR-PWS1CBL M-A1-H MR-PWS1CBL M-A2-H
M
U V
W
(b) When cable length exceeds 10m
When the cable length exceeds 10m, fabricate an extension cable as shown below. In this case, the motor power supply cable should be within 2m long. Refer to section 11.11 for the wire used for the extension cable.
(Note) Relay connector for extension cable
a)
(Note) Relay connector for motor power supply cable
b)
MR-PWS1CBL2M-A1-L MR-PWS1CBL2M-A2-L MR-PWS1CBL2M-A1-H MR-PWS1CBL2M-A2-H MR-PWS2CBL03M-A1-L MR-PWS2CBL03M-A2-L
CNP3
AWG 19(red) AWG 19(white) AWG 19(black)
U V
W
Servo motorServo amplifier
Extension cable
50m or less
2m or less
U V
W
M
AWG 19(green/yellow)
Note. Use of the following connectors is recommended when ingress protection (IP65) is necessary.
Relay Connector Description
Protective
Structure
a) Relay connector for
extension cable
Connector: RM15WTPZ-4P(71) Cord clamp: RM15WTP-CP(5)(71) (Hirose Electric) Numeral changes depending on the cable OD.
IP65
b) Relay connector for
motor power supply cable
Connector: RM15WTJA-4S(71) Cord clamp: RM15WTP-CP(8)(71) (Hirose Electric)
Numeral changes depending on the cable OD.
IP65
3 - 37
3. SIGNALS AND WIRING
(2) HF-SP series
HC-RP series HC-UP series HC-LP series servo motor
POINT Insert a contact in the direction shown in the figure. If inserted in the wrong direction, the contact is damaged and falls off.
Soldered part or crimping part facing up
Soldered part or crimping part facing down
Pin No.1Pin No.1
For CM10-SP2S-For CM10-SP10S-
(a) Wiring diagrams
Refer to section 11.11 for the cables used for wiring.
1) When the power supply connector and the electromagnetic brake connector are separately supplied.
Servo motor
(Note)
Servo amplifier
M
U V
W
B1 B2
U V
W
24VDC power
supply for
electromagnetic
brake
50m or less
Forced
stop
(EM1)
Trouble
(ALM)
RA1
DC24V
ALM
DOCOM
DICOM
MBR
CN3
RA1
RA2
Electromagnetic brake interlock
(MBR)
RA2
Note. There is no polarity in electromagnetic brake terminals B1 and B2.
3 - 38
3. SIGNALS AND WIRING
2) When the power supply connector and the electromagnetic brake connector are shared.
Servo motor
(Note)
Servo amplifier
M
U V
W
B1 B2
U V
W
24VDC power
supply for
electromagnetic
brake
50m or less
Forced
stop
(EM1)
Trouble
(ALM)
RA1
DC24V
ALM
DOCOM
DICOM
MBR
CN3
RA1
RA2
Electromagnetic brake interlock
(MBR)
RA2
Note. There is no polarity in electromagnetic brake terminals B1 and B2.
(b) Connector and signal allotment
The connector fitting the servomotor is prepared as optional equipment. Refer to section 11.1. For types other than those prepared as optional equipment, refer to chapter 3 in Servo Motor Instruction Manual, Vol. 2 to select.
Servo motor side connectors
Servo motor
Encoder Power supply
Electromagnetic
brake
HF-SP52(4) to 152(4)
HF-SP51 81
MS3102A18-10P
HF-SP202 352 502(4)
HF-SP121 to 301
MS3102A22-22P
HF-SP421 702(4) CE05-2A32-17RD-B
CM10-R2P
(DDK)
HC-RP103 to 203 CE05-2A22-23PD-B
HC-RP353 503 CE05-2A24-10PD-B
HC-UP72 152 CE05-2A22-23PD-B
The connector for
power is shared
HC-UP202 to 502 CE05-2A24-10PD-B MS3102A10SL-4P
HC-LP52 to 152 CE05-2A22-23PD-B
The connector for
power is shared
a
c
b
HC-LP202 302
CN10-R10P
(DDK)
CE05-2A24-10PD-B MS3102A10SL-4P
3 - 39
3. SIGNALS AND WIRING
Encoder connector signal allotment
CM10-R10P
Power supply connector signal allotment
MS3102A18-10P MS3102A22-22P
CE05-2A32-17PD-B
Power supply connector signal allotment
CE05-2A22-23PD-B
Terminal
No.
Signal
Terminal
No.
Signal
Terminal
No.
Signal
1 MR A U A U 2 MRR B V B V 3 C W C W 4 BAT 5 LG
D
(earth)
D
(earth) 6 E 7
CD
AB
View b
F 8 P5 B1 9
G
(Note)
5
6
1
4
View a
3
2
8
7
9
10
10 SHD B2
F
E
D
H
G
A
B
C
View b
H
(Note)
Note. For the motor
with electromagnetic brake, supply electromagnetic brake power (24VDC). There is no polarity.
Power supply connector signal allotment
CE05-2A24-10PD-B
Brake connector signal allotment
CM10-R2P
Brake connector signal allotment
MS3102A10SL-4P
Terminal
No.
Signal
Terminal
No.
Signal
Terminal
No.
Signal
A U B1 B1 B V
1
(Note)
A
(Note)
C W B2 B2
2
(Note)
B
(Note)
D
(earth)
B1
E
(Note)
B2
F
(Note)
F
E
DGC
B
A
View b
G
12
View c
AB
View c
Note. For the motor
with electromagnetic brake, supply electromagnetic brake power (24VDC). There is no polarity.
Note. For the motor
with electromagnetic brake, supply electromagnetic brake power (24VDC). There is no polarity.
Note. For the motor
with electromagnetic brake, supply electromagnetic brake power (24VDC). There is no polarity.
3 - 40
3. SIGNALS AND WIRING
(3) HA-LP series servo motor
(a) Wiring diagrams
Refer to section 11.11 for the cables used for wiring.
1) 200V class
Servo motor
(Note 1)
Servo amplifier
U V
W
B1 B2
U V
W
24VDC power
supply for
electromagnetic
brake
50m or less
Forced
stop
(EM1)
Trouble
(ALM)
RA1
24VDC
ALM
DOCOM
DICOM
MBR
CN3
RA1
RA2
Electromagnetic brake interlock
(MBR)
RA2
RA3
M
Cooling fan
(Note 2)
24VDC
power supply
OHS2OHS1 Servo motor
thermal relay
(Note 3)
L
1
L2 L
3
BU BV
BW
TE
MC
Note 1. When using the external dynamic brake, refer to section 11.6.
2. Cooling fan power supply of the HA-LP601, the HA-LP701M and the HA-LP11K2 servo motor is 1-phase. Power supply specification of the cooling fan is different from that of the servo amplifier. Therefore, separate power supply is required.
3. Configure the power supply circuit which turns off the magnetic contactor after detection of servo motor thermal.
3 - 41
3. SIGNALS AND WIRING
2) 400V class
Servo motor
(Note 1)
Servo amplifier
U V
W
B1 B2
U V
W
24VDC power
supply for
electromagnetic
brake
50m or less
Forced
stop
(EM1)
Trouble
(ALM)
RA1
24VDC
ALM
DOCOM
DICOM
MBR
CN3
RA1
RA2
Electromagnetic brake interlock
(MBR)
RA2
RA3
M
Cooling fan
(Note 2)
24VDC
power supply
OHS2OHS1 Servo motor
thermal relay
(Note 3)
L
1
L
2
L3
BU BV
BW
TE
MC
(Note4)
Cooling fan power supply
Note 1. When using the external dynamic brake, refer to section 11.6.
2. There is no BW when the power supply of the cooling fan is a 1-phase.
3. Configure the power supply circuit which turns off the magnetic contactor after detection of servo motor thermal.
4. For the cooling fan power supply, refer to (3) (b) of this section.
3 - 42
3. SIGNALS AND WIRING
(b) Servo motor terminals
Terminal box
Encoder connector CM10-R10P
Brake connector MS3102A10SL-4P
Terminal
No.
Signal
Terminal
No.
Signal
1 MR B1 2 MRR
1
(Note) 3 B2 4 BAT
2
(Note) 5 LG 6 7 8 P5 9
10 SHD
Encoder connector signal
allotment
CM10-R10P
5
6
1
4
3
2
8
7
9
10
Brake connector signal
allotment
MS3102A10SL-4P
1
2
Note. For the motor
with electromagnetic brake, supply electromagnetic brake power (24VDC). There is no polarity.
Terminal box inside (HA-LP601(4), 701M(4), 11K2(4) )
Terminal block signal arrangement
(U,V,W) M6 screw
Thermal sensor terminal block
(OHS1,OHS2) M4 screw
Cooling fan terminal block
(BU,BV) M4 screw
Encoder connector CM10-R10P
Earth terminal M6 screw
Motor power supply terminal block
WVU
UVW
BU BV
OHS1OHS2
3 - 43
3. SIGNALS AND WIRING
Terminal box inside (HA-LP801(4), 12K1(4), 11K1M(4), 15K1M(4), 15K2(4), 22K2(4))
Thermal sensor terminal block
(OHS1,OHS2) M4 screw
Cooling fan terminal block (BU,BV,BW) M4 screw
Encoder connector
CM10-R10P
Earth terminal M6 screw
Motor power supply terminal block
(U,V,W) M8 screw
UVW
Terminal block signal arrangement
UVW
BU BV
OHS1OHS2BW
Terminal box inside (HA-LP15K1(4), 20K1(4), 22K1M(4))
Earth terminal M6 screw
Thermal sensor terminal block
Cooling fan terminal block
Motor power supply terminal block
(OHS1,OHS2) M4 screw
(BU,BV,BW) M4 screw
(U,V,W) M8 screw
CM10-R10P
Encoder connector
U
V
W
Terminal block signal arrangement
BV
UVW
BU
BW OHS1OHS2
3 - 44
3. SIGNALS AND WIRING
Terminal box inside (HA-LP25K1)
BW
BV
BU
W
V
U
Encoder connector CM10-R10P
Earth terminal M6 screw
Thermal sensor terminal block
Cooling fan terminal block
Motor power supply terminal block
(OHS1, OHS2) M4 screw
(BU, BV, BW) M4 screw
(U, V, W) M10 screw
Terminal block signal arrangement
BV
UVW
BU
BW OHS1OHS2
3 - 45
3. SIGNALS AND WIRING
Signal Name
Abbreviation Description
Power supply
U
V W
Connect to the motor output terminals (U, V, W) of the servo amplifier. During power-on, do not open or close the motor power line. Otherwise, a malfunction or faulty may occur. Supply power which satisfies the following specifications.
Servo motor
Voltage division
Voltage/
frequency
Power
consumption
[W]
Rated
current
[A]
HA-LP601, 701M, 11K2
200V class
3-phase 200 to 220VAC
50Hz
3-phase 200 to 230VAC
60Hz
42(50Hz) 54(60Hz)
0.21(50Hz)
0.25(60Hz)
HA-LP801, 12K1, 11K1M, 15K1M, 15K2, 22K2
3-phase 200 to 230VAC
50Hz/60Hz
62(50Hz) 76(60Hz)
0.18(50Hz)
0.17(60Hz)
HA-LP15K1, 20K1, 22K1M
65(50Hz) 85(60Hz)
0.20(50Hz)
0.22(60Hz)
HA-LP25K1
120(50Hz) 175(60Hz)
0.65(50Hz)
0.80(60Hz) HA-LP6014, 701M4, 11K24
400V class
1-phase 200 to 220VAC
50Hz
3-phase 200 to 230VAC
60Hz
42(50Hz) 54(60hz)
0.21(50Hz)
0.25(60Hz)
HA-LP8014, 12K14, 11K1M4, 15K1M4, 15K24, 22K24
3-phase 380 to 440VAC
50Hz
3-phase 380 to 480VAC
60Hz
62(50Hz) 76(60Hz)
0.14(50Hz)
0.11(60Hz)
HA-LP15K14, 20K14, 22K1M4
65(50Hz)
85(60Hz)
0.12(50Hz)
0.14(60Hz) HA-LP25K14
3-phase 380 to 460VAC
50Hz
3-phase 380 to 480VAC
60Hz
110(50Hz) 150(60Hz)
0.20(50Hz)
0.22(60Hz)
Cooling fan
(Note) BU
BV BW
Motor thermal relay
OHS1
OHS2
OHS1
OHS2 are opened when heat is generated to an abnormal temperature. Maximum rating: 125V AC/DC, 3A or 250V AC/DC, 2A Minimum rating: 6V AC/DC, 0.15A
Earth terminal
For grounding, connect to the earth of the control box via the earth terminal of the servo amplifier.
Note. There is no BW when the power supply of the cooling fan is a 1-phase.
Loading...