(Always read these instructions before using the equipment.)
Do not attempt to install, operate, maintain or inspect the servo amplifier and servo motor until you have read
through this Instruction Manual, Installation guide, Servo motor Instruction Manual (Vol.2) and appended
documents carefully and can use the equipment correctly. Do not use the servo amplifier and servo motor until
you have a full knowledge of the equipment, safety information and instructions.
In this Instruction Manual, the safety instruction levels are classified into "WARNING" and "CAUTION".
WARNING
CAUTION
Indicates that incorrect handling may cause hazardous conditions,
resulting in death or severe injury.
Indicates that incorrect handling may cause hazardous conditions,
resulting in medium or slight injury to personnel or may cause physical
Note that the CAUTION level may lead to a serious consequence according to conditions. Please follow the
instructions of both levels because they are important to personnel safety.
What must not be done and what must be done are indicated by the following diagrammatic symbols.
: Indicates what must not be done. For example, "No Fire" is indicated by
: Indicates what must be done. For example, grounding is indicated by
In this Instruction Manual, instructions at a lower level than the above, instructions for other functions, and so
on are classified into "POINT".
After reading this installation guide, always keep it accessible to the operator.
damage.
.
.
A - 1
1. To prevent electric shock, note the following
WARNING
Before wiring or inspection, turn off the power and wait for 15 minutes or more until the charge lamp turns
off. Then, confirm that the voltage between P(
Otherwise, an electric shock may occur. In addition, always confirm from the front of the servo amplifier,
whether the charge lamp is off or not.
Connect the servo amplifier and servo motor to ground.
Any person who is involved in wiring and inspection should be fully competent to do the work.
Do not attempt to wire the servo amplifier and servo motor until they have been installed. Otherwise, you
may get an electric shock.
Operate the switches with dry hand to prevent an electric shock.
The cables should not be damaged, stressed, loaded, or pinched. Otherwise, you may get an electric
shock.
During power-on or operation, do not open the front cover of the servo amplifier. You may get an electric
shock.
Do not operate the servo amplifier with the front cover removed. High-voltage terminals and charging area
are exposed and you may get an electric shock.
Except for wiring or periodic inspection, do not remove the front cover even of the servo amplifier if the
power is off. The servo amplifier is charged and you may get an electric shock.
) and N() is safe with a voltage tester and others.
2. To prevent fire, note the following
CAUTION
Install the servo amplifier, servo motor and regenerative resistor on incombustible material. Installing them
directly or close to combustibles will lead to a fire.
Always connect a magnetic contactor (MC) between the main circuit power supply and L1, L2, and L3 of
the servo amplifier, and configure the wiring to be able to shut down the power supply on the side of the
servo amplifier’s power supply. If a magnetic contactor (MC) is not connected, continuous flow of a large
current may cause a fire when the servo amplifier malfunctions.
When a regenerative resistor is used, use an alarm signal to switch main power off. Otherwise, a
regenerative transistor fault or the like may overheat the regenerative resistor, causing a fire.
3. To prevent injury, note the follow
CAUTION
Only the voltage specified in the Instruction Manual should be applied to each terminal, Otherwise, a
burst, damage, etc. may occur.
Connect the terminals correctly to prevent a burst, damage, etc.
Ensure that polarity (, ) is correct. Otherwise, a burst, damage, etc. may occur.
Take safety measures, e.g. provide covers, to prevent accidental contact of hands and parts (cables, etc.)
with the servo amplifier heat sink, regenerative resistor, servo motor, etc. since they may be hot while
power is on or for some time after power-off. Their temperatures may be high and you may get burnt or a
parts may damaged.
During operation, never touch the rotating parts of the servo motor. Doing so can cause injury.
A - 2
4. Additional instructions
The following instructions should also be fully noted. Incorrect handling may cause a fault, injury, electric shock,
etc.
(1) Transportation and installation
CAUTION
Transport the products correctly according to their weights.
Stacking in excess of the specified number of products is not allowed.
Do not carry the servo motor by the cables, shaft or encoder.
Do not hold the front cover to transport the servo amplifier. The servo amplifier may drop.
Install the servo amplifier in a load-bearing place in accordance with the Instruction Manual.
Do not climb or stand on servo equipment. Do not put heavy objects on equipment.
The servo amplifier and servo motor must be installed in the specified direction.
Leave specified clearances between the servo amplifier and control enclosure walls or other equipment.
Do not install or operate the servo amplifier and servo motor which has been damaged or has any parts
missing.
Provide adequate protection to prevent screws and other conductive matter, oil and other combustible
matter from entering the servo amplifier and servo motor.
Do not drop or strike servo amplifier or servo motor. Isolate from all impact loads.
When you keep or use it, please fulfill the following environmental conditions.
Ambient
temperature
Ambient
humidity
Ambience Indoors (no direct sunlight) Free from corrosive gas, flammable gas, oil mist, dust and dirt
Altitude Max. 1000m (3280 ft) above sea level
(Note)
Vibration
Note. Except the servo motor with a reduction gear.
Environment
] 0 to 55 (non-freezing) 0 to 40 (non-freezing)
In operation
In storage
In operation 90%RH or less (non-condensing) 80%RH or less (non-condensing)
In storage 90%RH or less (non-condensing)
[
] 32 to 131 (non-freezing) 32 to 104 (non-freezing)
[
]
[
[
2
] 5.9 or less
[m/s
20 to 65 (non-freezing) 15 to 70 (non-freezing)
]
4 to 149 (non-freezing)
Servo amplifier Servo motor
HF-MP series HF-KP series X Y: 49
HF-SP51 81 HF-SP52 to 152
HF-SP524 to 1524 HC-RP Series
HC-UP72
HF-SP121
HF-SP2024
HF-SP301 421 HF-SP502 702
HF-SP5024
HA-LP601 to 12K1 HA-LP701M to 15K1M
HA-LP502 to 22K2 HA-LP6014 to 12K14
HA-LP701M4 to 15K1M4 HA-LP11K24 to 22K24
HA-LP15K1 to 25K1 HA-LP37K1M
HA-LP15K14 to 20K14 HA-LP22K1M4
152
201 HF-SP202 352
3524 HC-UP202 to 502
7024
Securely attach the servo motor to the machine. If attach insecurely, the servo motor may come off during
operation.
The servo motor with a reduction gear must be installed in the specified direction to prevent oil leakage.
Take safety measures, e.g. provide covers, to prevent accidental access to the rotating parts of the servo
motor during operation.
Never hit the servo motor or shaft, especially when coupling the servo motor to the machine. The encoder
may become faulty.
Do not subject the servo motor shaft to more than the permissible load. Otherwise, the shaft may break.
When the equipment has been stored for an extended period of time, consult Mitsubishi.
A - 3
Conditions
5 to 158 (non-freezing)
X
Y: 24.5
X: 24.5 Y: 49
X: 24.5 Y: 29.4
HC-LP52 to 152 X: 9.8 Y: 24.5
HC-LP202 to 302 X: 19.6 Y: 49
X: 11.7 Y: 29.4
X
Y: 9.8
(2) Wiring
CAUTION
Wire the equipment correctly and securely. Otherwise, the servo motor may operate unexpectedly.
Do not install a power capacitor, surge absorber or radio noise filter (FR-BIF-(H) option) between the
servo motor and servo amplifier.
Connect the wires to the correct phase terminals (U, V, W) of the servo amplifier and servo motor.
Not doing so may cause unexpected operation.
Connect the servo motor power terminal (U, V, W) to the servo motor power input terminal (U, V, W)
directly. Do not let a magnetic contactor, etc. intervene.
Servo amplifier
U
V
W
Servo motor
U
V
W
Servo motorServo amplifier
U
M
V
W
U
V
M
W
Do not connect AC power directly to the servo motor. Otherwise, a fault may occur.
The surge absorbing diode installed on the DC output signal relay of the servo amplifier must be wired in
the specified direction. Otherwise, the forced stop (EMG) and other protective circuits may not operate.
Servo amplifierServo amplifier
DOCOM
DICOM
Control
output
signal
24VDC
RA
DOCOM
DICOM
Control
output
signal
24VDC
RA
When the cable is not tightened enough to the terminal block (connector), the cable or terminal block
(connector) may generate heat because of the poor contact. Be sure to tighten the cable with specified
torque.
(3) Test run adjustment
CAUTION
Before operation, check the parameter settings. Improper settings may cause some machines to perform
unexpected operation.
The parameter settings must not be changed excessively. Operation will be insatiable.
A - 4
(4) Usage
CAUTION
Provide an external emergency stop circuit to ensure that operation can be stopped and power switched
off immediately.
Any person who is involved in disassembly and repair should be fully competent to do the work.
Before resetting an alarm, make sure that the run signal of the servo amplifier is off to prevent an
accident. A sudden restart is made if an alarm is reset with the run signal on.
Do not modify the equipment.
Use a noise filter, etc. to minimize the influence of electromagnetic interference, which may be caused by
electronic equipment used near the servo amplifier.
Burning or breaking a servo amplifier may cause a toxic gas. Do not burn or break a servo amplifier.
Use the servo amplifier with the specified servo motor.
The electromagnetic brake on the servo motor is designed to hold the motor shaft and should not be used
for ordinary braking.
For such reasons as service life and mechanical structure (e.g. where a ball screw and the servo motor
are coupled via a timing belt), the electromagnetic brake may not hold the motor shaft. To ensure safety,
install a stopper on the machine side.
(5) Corrective actions
CAUTION
When it is assumed that a hazardous condition may take place at the occur due to a power failure or a
product fault, use a servo motor with an electromagnetic brake or an external brake mechanism for the
purpose of prevention.
Configure the electromagnetic brake circuit so that it is activated not only by the servo amplifier signals
but also by an external forced stop (EMG).
Contacts must be open when
servo-off, when an trouble (ALM)
and when an electromagnetic brake
interlock (MBR).
SONRA
Electromagnetic brake
When any alarm has occurred, eliminate its cause, ensure safety, and deactivate the alarm before
restarting operation.
When power is restored after an instantaneous power failure, keep away from the machine because the
machine may be restarted suddenly (design the machine so that it is secured against hazard if restarted).
Circuit must be
opened during
forced stop (EMG).
EMG
24VDC
(6) Maintenance, inspection and parts replacement
CAUTION
With age, the electrolytic capacitor of the servo amplifier will deteriorate. To prevent a secondary accident
due to a fault, it is recommended to replace the electrolytic capacitor every 10 years when used in general
environment. Please consult our sales representative.
A - 5
(7) General instruction
To illustrate details, the equipment in the diagrams of this Specifications and Instruction Manual may have
been drawn without covers and safety guards. When the equipment is operated, the covers and safety
guards must be installed as specified. Operation must be performed in accordance with this
Specifications and Instruction Manual.
About processing of waste
When you discard servo amplifier, a battery (primary battery), and other option articles, please follow the law of
each country (area).
FOR MAXIMUM SAFETY
These products have been manufactured as a general-purpose part for general industries, and have not
been designed or manufactured to be incorporated in a device or system used in purposes related to
human life.
Before using the products for special purposes such as nuclear power, electric power, aerospace,
medicine, passenger movement vehicles or under water relays, contact Mitsubishi.
These products have been manufactured under strict quality control. However, when installing the product
where major accidents or losses could occur if the product fails, install appropriate backup or failsafe
functions in the system.
EEP-ROM life
The number of write times to the EEP-ROM, which stores parameter settings, etc., is limited to 100,000. If
the total number of the following operations exceeds 100,000, the servo amplifier and/or converter unit may
fail when the EEP-ROM reaches the end of its useful life.
Write to the EEP-ROM due to parameter setting changes
Home position setting in the absolute position detection system
Write to the EEP-ROM due to device changes
Write to the EEP-ROM due to point table changes
Precautions for Choosing the Products
Mitsubishi will not be held liable for damage caused by factors found not to be the cause of Mitsubishi;
machine damage or lost profits caused by faults in the Mitsubishi products; damage, secondary damage,
accident compensation caused by special factors unpredictable by Mitsubishi; damages to products other
than Mitsubishi products; and to other duties.
A - 6
COMPLIANCE WITH EC DIRECTIVES
1. WHAT ARE EC DIRECTIVES?
The EC directives were issued to standardize the regulations of the EU countries and ensure smooth
distribution of safety-guaranteed products. In the EU countries, the machinery directive (effective in January,
1995), EMC directive (effective in January, 1996) and low voltage directive (effective in January, 1997) of the
EC directives require that products to be sold should meet their fundamental safety requirements and carry the
CE marks (CE marking). CE marking applies to machines and equipment into which servo amplifiers have
been installed.
(1) EMC directive
The EMC directive applies not to the servo units alone but to servo-incorporated machines and equipment.
This requires the EMC filters to be used with the servo-incorporated machines and equipment to comply
with the EMC directive. For specific EMC directive conforming methods, refer to the EMC Installation
Guidelines (IB(NA)67310).
(2) Low voltage directive
The low voltage directive applies also to servo units alone. Hence, they are designed to comply with the low
voltage directive.
This servo is certified by TUV, third-party assessment organization, to comply with the low voltage directive.
(3) Machine directive
Not being machines, the servo amplifiers need not comply with this directive.
2. PRECAUTIONS FOR COMPLIANCE
(1) Servo amplifiers and servo motors used
Use the servo amplifiers and servo motors which comply with the standard model.
Servo amplifier :MR-J3-10T to MR-J3-22KT
MR-J3-10T1 to MR-J3-40T1
MR-J3-60T4 to MR-J3-22KT4
Servo motor :HF-MP
HF-KP
HF-SP
HF-SP
HC-RP
HC-UP
HC-LP
HA-LP
HA-LP
Note. For the latest information of compliance, contact Mitsubishi.
(Note)
4 (Note)
(Note)
4 (Note)
A - 7
(2) Configuration
The control circuit provide safe separation to the main circuit in the servo amplifier.
Control box
Reinforced
insulating type
24VDC
No-fuse
breaker
NFB
Magnetic
contactor
MC
power
supply
Servo
amplifier
Servo
motor
M
(3) Environment
Operate the servo amplifier at or above the contamination level 2 set forth in IEC60664-1. For this purpose,
install the servo amplifier in a control box which is protected against water, oil, carbon, dust, dirt, etc. (IP54).
(4) Power supply
(a) This servo amplifier can be supplied from star-connected supply with earthed neutral point of
overvoltage category III set forth in IEC60664-1. However, when using the neutral point of 400V class
for single-phase supply, a reinforced insulating transformer is required in the power input section.
(b) When supplying interface power from external, use a 24VDC power supply which has been insulation-
reinforced in I/O.
(5) Grounding
(a) To prevent an electric shock, always connect the protective earth (PE) terminals (marked
) of the
servo amplifier to the protective earth (PE) of the control box.
(b) Do not connect two ground cables to the same protective earth (PE) terminal (marked
). Always
connect the cables to the terminals one-to-one.
PE terminals
PE terminals
(c) If a leakage current breaker is used to prevent an electric shock, the protective earth (PE) terminals
(marked
) of the servo amplifier must be connected to the corresponding earth terminals.
A - 8
(6) Wiring
(a) The cables to be connected to the terminal block of the servo amplifier must have crimping terminals
provided with insulating tubes to prevent contact with adjacent terminals.
Crimping terminal
Insulating tube
Cable
(b) Use the servo motor side power connector which complies with the EN Standard. The EN Standard
compliant power connector sets are available from us as options. (Refer to section 14.1)
(7) Auxiliary equipment and options
(a) The no-fuse breaker and magnetic contactor used should be the EN or IEC standard-compliant
products of the models described in section 14.10.
Use a type B (Note) breaker. When it is not used, provide insulation between the servo amplifier and
other device by double insulation or reinforced insulation, or install a transformer between the main
power supply and servo amplifier.
Note. Type A: AC and pulse detectable
Type B: Both AC and DC detectable
(b) The sizes of the cables described in section 14.9 meet the following requirements. To meet the other
requirements, follow Table 5 and Appendix C in EN60204-1.
Ambient temperature: 40 (104) [°C (°F)]
Sheath: PVC (polyvinyl chloride)
Installed on wall surface or open table tray
(c) Use the EMC filter for noise reduction.
(8) Performing EMC tests
When EMC tests are run on a machine/device into which the servo amplifier has been installed, it must
conform to the electromagnetic compatibility (immunity/emission) standards after it has satisfied the
operating environment/electrical equipment specifications.
For the other EMC directive guidelines on the servo amplifier, refer to the EMC Installation Guidelines
(IB(NA)67310).
A - 9
CONFORMANCE WITH UL/C-UL STANDARD
(1) Servo amplifiers and servo motors used
Use the servo amplifiers and servo motors which comply with the standard model.
Servo amplifier :MR-J3-10T to MR-J3-22KT
MR-J3-10T1 to MR-J3-40T1
MR-J3-60T4 to MR-J3-22KT4
Servo motor :HF-MP
HF-KP
HF-SP
HF-SP
HC-RP
HC-UP
HC-LP
HA-LP
HA-LP
Note. For the latest information of compliance, contact Mitsubishi.
(2) Installation
Install a fan of 100CFM (2.8m
of at least equivalent capability to ensure that the ambient temperature conforms to the environment
conditions (55
or less).
(3) Short circuit rating (SCCR: Short Circuit Current Rating)
Suitable For Use In A Circuit Capable Of Delivering Not More Than 100 kA rms Symmetrical Amperes, 500
Volts Maximum.
(4) Capacitor discharge time
The capacitor discharge time is as listed below. To ensure safety, do not touch the charging section for 15
minutes after power-off.
Servo amplifier
MR-J3-10T 20T 1
MR-J3-40T 60T(4) 10T1 20T1 2
MR-J3-70T 3
MR-J3-40T1 4
MR-J3-100T(4) 5
MR-J3-200T(4) 350T 9
MR-J3-350T4 500T(4) 700T(4) 10
MR-J3-11KT(4) 4
MR-J3-15KT(4) 6
MR-J3-22KT(4) 8
(Note)
4 (Note)
(Note)
4 (Note)
3
/min) air flow 4[in] (10.16[cm]) above the servo amplifier or provide cooling
Discharge time
[min]
A - 10
(5) Options and auxiliary equipment
Use UL/C-UL standard-compliant products.
(6) Attachment of a servo motor
For the flange size of the machine side where the servo motor is installed, refer to “CONFORMANCE WITH
UL/C-UL STANDARD” in the Servo Motor Instruction Manual (Vol.2).
(7) About wiring protection
For installation in United States, branch circuit protection must be provided, in accordance with the National
Electrical Code and any applicable local codes.
For installation in Canada, branch circuit protection must be provided, in accordance with the Canada
Electrical Code and any applicable provincial codes.
<<About the manuals>>
This Instruction Manual and the MELSERVO Servo Motor Instruction Manual (Vol.2) are required if you use
the General-Purpose AC servo MR-J3-T for the first time. Always purchase them and use the MR-J3-T
safely.
Relevant manuals
Manual name Manual No.
MELSERVO-J3 Series Instructions and Cautions for Safe Use of AC Servos IB(NA)0300077
MELSERVO Servo Motor Instruction Manual (Vol.2) SH(NA)030041
EMC Installation Guidelines IB(NA)67310
<<About the wires used for wiring>>
Wiring wires mentioned in this instruction manual are selected based on the ambient temperature of 40°C
(104
1.1.1 Features of CC-Link communication functions ................................................................................ 1 - 1
1.1.2 Function block diagram ..................................................................................................................... 1 - 2
1.1.3 System configuration......................................................................................................................... 1 - 5
1.2 Servo amplifier standard specifications................................................................................................... 1 - 7
1.3 Function list ............................................................................................................................................. 1 -13
1.4 Model code definition .............................................................................................................................. 1 -15
1.5 Combination with servo motor ................................................................................................................ 1 -16
1.6.1 Parts identification ............................................................................................................................ 1 -17
1.6.2 Removal and reinstallation of the front cover.................................................................................. 1 -23
1.7 Configuration including auxiliary equipment .......................................................................................... 1 -26
1.8 Selection of operation method................................................................................................................ 1 -34
2. INSTALLATION 2 - 1 to 2 - 4
2.1 Installation direction and clearances ....................................................................................................... 2 - 1
2.2 Keep out foreign materials ....................................................................................................................... 2 - 3
2.5 Parts having service lives ........................................................................................................................ 2 - 4
3. CC-LINK COMMUNICATION FUNCTIONS 3 - 1 to 3 -60
3.1 Communication specifications ................................................................................................................. 3 - 1
3.2 System configuration ............................................................................................................................... 3 - 2
3.2.1 Configuration example ......................................................................................................................3 - 2
3.2.3 Station number setting ...................................................................................................................... 3 - 5
3.2.4 Communication baud rate setting..................................................................................................... 3 - 6
3.2.5 Occupied station count setting.......................................................................................................... 3 - 6
3.7.1 System configuration example......................................................................................................... 3 -41
3.7.2 Reading the servo amplifier status ..................................................................................................3 -44
3.7.3 Writing the operation commands..................................................................................................... 3 -45
3.7.4 Reading the data .............................................................................................................................. 3 -46
3.7.5 Writing the data ................................................................................................................................3 -49
3.8 Continuous operation program example ................................................................................................ 3 -55
3.8.1 System configuration example when 1 station is occupied ............................................................ 3 -55
3.8.2 Program example when 1 station is occupied ................................................................................3 -56
3.8.3 System configuration example when 2 stations are occupied........................................................ 3 -58
3.8.4 Program example when 2 stations are occupied ............................................................................ 3 -59
4. SIGNALS AND WIRING 4 - 1 to 4 -54
4.1 Input power supply circuit ........................................................................................................................ 4 - 2
4.2 I/O signal connection diagram ................................................................................................................ 4 -10
4.3 Explanation of power supply system ...................................................................................................... 4 -11
4.3.1 Signal explanations ..........................................................................................................................4 -11
4.5.4 Power supply.................................................................................................................................... 4 -27
4.6 Detailed description of signals (devices)................................................................................................ 4 -27
rough match in position .......................................................................... 4 -28
HF-KP series servo motor) ..................................................... 4 -52
2
5. OPERATION 5 - 1 to 5 -60
5.1 Switching power on for the first time ....................................................................................................... 5 - 1
6.2.1 Parameter list ...................................................................................................................................6 -12
6.2.2 Detail list ........................................................................................................................................... 6 -13
6.3 Extension setting parameters (No. PC
6.3.1 Parameter list ...................................................................................................................................6 -20
6.3.2 Detail list ........................................................................................................................................... 6 -21
6.4.1 Parameter list ...................................................................................................................................6 -29
6.4.2 Detail list ........................................................................................................................................... 6 -30
6.4.3 Stopping method when the forward stroke end (LSP) or reverse stroke end (LSN) is valid ......... 6 -38
6.4.4 Stopping method when a software limit is detected........................................................................ 6 -39
7.7 Test operation .........................................................................................................................................7 -13
7.7.1 Jog operation.................................................................................................................................... 7 -13
10.6 Gain changing function ........................................................................................................................10-10
14.1.3 Motor power supply cables ........................................................................................................... 14-17
14.1.4 Motor brake cables........................................................................................................................ 14-18
14.9 Selection example of wires .................................................................................................................. 14-62
14.10 No-fuse breakers, fuses, magnetic contactors ................................................................................. 14-68
14.11 Power factor improving DC reactor ...................................................................................................14-69
14.12 Power factor improving reactors........................................................................................................ 14-71
14.16 Leakage current breaker.................................................................................................................... 14-81
15.5 Detailed explanations of commands ................................................................................................... 15-17
15.5.1 Data processing ............................................................................................................................ 15-17
15.5.2 Status display ................................................................................................................................ 15-19
15.5.10 Current alarm .............................................................................................................................. 15-38
15.5.11 Point table.................................................................................................................................... 15-39
15.5.12 Servo amplifier group designation .............................................................................................. 15-45
15.5.13 Other commands......................................................................................................................... 15-46
16. INDEXER POSITIONING OPERATION 16- 1 to 16-112
16.1 Function ................................................................................................................................................. 16- 1
16.1.2 Servo amplifier standard specifications (functions only)............................................................... 16- 1
16.1.3 Function list .................................................................................................................................... 16- 2
16.2 I/O signals (I/O devices) transferred to/from the programmable controller CPU ................................ 16- 3
16.5.3 Test operation ............................................................................................................................... 16-33
16.5.5 Point table setting.......................................................................................................................... 16-35
16.5.6 Actual operation ............................................................................................................................16-35
16.8.1 Indexer JOG operation.................................................................................................................. 16-58
16.8.2 JOG operation ............................................................................................................................... 16-60
16.9 Home position return mode .................................................................................................................16-61
16.9.1 Outline of home position return..................................................................................................... 16-61
16.9.2 Torque limit changing dog type home position return.................................................................. 16-63
16.9.3 Torque limit changing data setting type home position return..................................................... 16-65
16.9.4 Home position return automatic return function ........................................................................... 16-66
16.10 Absolute position detection system ...................................................................................................16-67
16.12.1 Trouble at start-up ....................................................................................................................... 16-98
16.12.2 Operation at error occurrence..................................................................................................... 16-99
16.12.3 CC-Link communication error..................................................................................................... 16-99
16.12.4 When alarm or warning has occurred ......................................................................................16-100
16.12.5 Point table error......................................................................................................................... 16-112
The MR-J3axes of servo amplifiers can be controlled/monitored from the programmable controller side.
As the servo, it has the function to perform positioning operation by merely setting the position data (target
positions), servo motor speeds, acceleration and deceleration time constants, etc. to point tables as if setting
them in parameters. The servo amplifier is the most appropriate to configure a program-free, simple positioning
system or to simplify a system, for example.
There are 31 points of point tables to be used when 1 station is occupied and 255 points when 2 stations are
occupied.
All servo motors are equipped with an absolute position encoder as standard. An absolute position detection
system can be configured by merely adding a battery to the servo amplifier. Once the home position has been
set, home position return is not required at power on, alarm occurrence, etc.
The MR-J3-T is made easier to use and higher in function by using it with the MR Configurator.
1.1.1 Features of CC-Link communication functions
(1) Fast communication
Fast communication can be made by cyclic transmission of not only bit data but also word data.
(a) The highest communication speed is 10Mbps.
(b) The broadcast polling system ensures as high as 3.9ms to 6.7ms even at the maximum link scan
(2) Variable communication speed/distance system
Selection of speed/distance allows use in a wide range of areas from a system requiring high speed to a
system requiring long distance.
(3) System fault prevention (station separating function)
Because of connection in the bus system, any remote or local station that has become faulty due to poweroff or the like does not affect communications with normal remote and local stations.
In addition, use of the two-piece terminal block allows the unit to be changed during data link.
(4) Factory Automation compatible
As the remote device stations of CC-Link, the servo amplifiers share a link system and can be
controlled/monitored with programmable controller user programs.
From the programmable controller side, the running speed, acceleration/deceleration time constant and
other settings of servo motors can be changed/checked and the servo motors started and stopped.
T CC-Link compatible servo amplifier can support the CC-Link communication functions. Up to 42
(10Mbps).
1 - 1
1. FUNCTIONS AND CONFIGURATION
1.1.2 Function block diagram
The function block diagram of this servo is shown below.
(1) MR-J3-350T or less
MCNFB
(Note 2)
Power
supply
MR-J3-200T4 or less
Power factor
improving DC
reactor
P
1
Diode
Relay
stack
L
1
L2
L
3
Regenerative
P( )
P
2
CHARGE
option
lamp
N( )
D
C
(Note 1)
Regenerative
TR
Current
detector
Servo motorServo amplifier
U
V
W
U
V
M
W
L11
L
(Note 4) Cooling fan
Control
circuit
21
power
supply
Base
amplifier
Voltage
detection
Overcurrent
protection
Dynamic
brake
Current
detection
24VDC
CN2
RA
B1
B2
Electromagnetic
brake
Encoder
Current
control
Point table
No.
Position
data
Speed
Acceleration
time
constant
Deceleration
time
constant
Dwell Auxiliary
110001000808000
control
Model adaptive control
Position
control
Position
command
creation
Speed
(Note 3)
2
2000200010010000
3
4000200070605001
4
5002000607010001
5
6
7
8
2000808000
1000
20001000808000
10001000808000
1000100010010000
1000100010010000
255 20002000808000
USB
RS-422
MR-J3BAT
CN4
Optional battery
(for absolute position
detection system)
CN1CN6
Personal
computer
DI/O Control
Servo on
Start
Failure, etc
CC-Link
USB
Controller
RS-422
Note 1. The built-in regenerative resistor is not provided for the MR-J3-10T (1).
2. For 1-phase 200 to 230VAC, connect the power supply to L
There is no L
3 for 1-phase 100 to 120VAC power supply. Refer to section 1.2 for the power supply specification.
1, L2 and leave L3 open.
3. For the case when 2 stations are occupied. When 1 station is occupied, the point table ends at No.31.
4. Servo amplifiers MR-J3-70T or greater have a cooling fan.
1 - 2
CN3CN5
1. FUNCTIONS AND CONFIGURATION
(2) MR-J3-350T4
MR-J3-500T(4) MR-J3-700T(4)
Power factor
improving DC
reactor
Regenerative
option
(Note 1)
Power
supply
P
P
P
1
2
Diode
Relay
MCNFB
stack
L
1
L2
L
3
CHARGE
lamp
Cooling fan
L11
L
21
Control
circuit
power
supply
Base
amplifier
N
C
Regenerative
TR
Voltage
detection
Current
detector
Overcurrent
protection
Dynamic
brake
Current
detection
U
V
W
24VDC
CN2
RA
B1
B2
Servo motorServo amplifier
U
V
W
M
Electromagnetic
brake
Encoder
Current
control
Point table
No.
Position
data
Speed
Acceleration
time
constant
Deceleration
time
constant
Dwell Auxiliary
110001000808000
control
Model adaptive control
Position
control
Position
command
creation
Speed
(Note 2)
2
2000200010010000
4000200070605001
3
4
5002000607010001
5
6
7
8
2000808000
1000
20001000808000
10001000808000
1000100010010000
1000100010010000
255 20002000808000
USB
RS-422
MR-J3BAT
CN4
Optional battery
(for absolute position
detection system)
CN1CN6
Personal
computer
DI/O Control
Servo on
Start
Failure, etc
CC-Link
USB
Controller
RS-422
Note 1. Refer to section 1.2 for the power supply specification.
2. For the case when 2 stations are occupied. When 1 station is occupied, the point table ends at No.31.
1 - 3
CN3CN5
1. FUNCTIONS AND CONFIGURATION
(3) MR-J3-11KT(4) to 22KT(4)
Power factor
improving DC
reactor
Regenerative
option
(Note 1)
Power
supply
P
1
Diode
Thyristor
MCNFB
stack
L
1
P
L2
L
3
CHARGE
lamp
N
C
Regenerative
TR
Current
detector
U
V
W
Servo motorServo amplifier
U
V
M
W
Cooling fan
RA
L11
L
Control
circuit
21
power
supply
Base
amplifier
Voltage
detection
Overcurrent
protection
Current
detection
24VDC
CN2
B1
B2
Electromagnetic
brake
Encoder
Current
control
Point table
No.
Position
data
Speed
Acceleration
time
constant
Deceleration
time
constant
Dwell Auxiliary
110001000808000
control
Model adaptive control
Position
control
Position
command
creation
Speed
(Note 2)
2
2000200010010000
4000200070605001
3
4
5002000607010001
5
6
7
8
2000808000
1000
20001000808000
10001000808000
1000100010010000
1000100010010000
255 20002000808000
USB
RS-422
MR-J3BAT
CN4
Optional battery
(for absolute position
detection system)
CN1CN6
Personal
computer
DI/O Control
Servo on
Start
Failure, etc
CC-Link
USB
Controller
RS-422
Note 1. Refer to section 1.2 for the power supply specification.
2. For the case when 2 stations are occupied. When 1 station is occupied, the point table ends at No.31.
1 - 4
CN3CN5
1. FUNCTIONS AND CONFIGURATION
1.1.3 System configuration
This section provides operations using this servo.
Use of CC-Link enables you to freely configure any system from a single-axis system to an up to 42-axis
system.
Set the following values to the point table.
Name Setting range Unit
0.001[mm]
Position data 999999 to 999999
Servo motor speed 0 to max. speed [r/min]
Acceleration time constant 0 to 20000 [ms]
Deceleration time constant 0 to 20000 [ms]
Dwell 0 to 20000 [ms]
Auxiliary function
(Refer to section 4.2)
0 to 3
0.01[mm]
0.1[mm]
1[mm]
There are 31 points of point tables to be used when 1 station is occupied and 255 points when 2 stations are
occupied.
(1) Operation using CC-Link communication functions
(a) Operation
All devices can be controlled by CC-Link communication. Also, each point table setting, point table
selection, parameter value change, setting, monitor, servo motor operation and others can be
performed.
(b) Configuration
Programmable controller
CC-Link master unit
Servo amplifier
(Axis 1)
CNP3
CN2
CN1
CN6
Servo amplifier
(Axis 2)
CN1
CN6
CNP3
CN2
To the next axis
1 - 5
1. FUNCTIONS AND CONFIGURATION
(2) Operation using CC-Link communication functions and external input signals
(a) Operation
Using parameter No.PD06 to PD08 and parameter No.PD12, PD14, input devices can be assigned to
the external input devices of CN1A and CN1B. The signals assigned to the external input signals cannot
be used with the CC-Link communication functions. Output devices can be used with the CN6
connectors and CC-Link communication functions simultaneously.
(b) Configuration
Programmable controller
CC-Link master unit
Servo amplifier
(Axis 1)
CN1
CNP3CNP3
CN6
CN2
External I/O
signal
Servo amplifier
(Axis 2)
CN1
CN6
CN2
External I/O
signal
To the next axis
1 - 6
1. FUNCTIONS AND CONFIGURATION
1.2 Servo amplifier standard specifications
(1) 200V class, 100V class
Servo amplifier
MR-J3-
Item
Voltage/frequency
Permissible voltage fluctuation
Permissible frequency
fluctuation
Power supply
Power supply capacity Refer to section 13.2
Inrush current Refer to section 13.5
Voltage,
frequency
Permissible
Control circuit
power supply
Interface power
supply
Control System Sine-wave PWM control, current control system
Dynamic brake Built-in External option Built-in
Protective functions
Point table
number
input
Position
Command system
command
data input
(when 2
stations are
occupied)
Automatic
operation
mode
Manual
Operation mode
operation
mode
voltage fluctuation
Permissible
frequency
fluctuation
Input 30W 45W 30W
Inrush current Refer to section 13.5
Voltage 24VDC 10%
Power supply
capacity
Operational
specifications
Position command
input
Speed command
input
Overcurrent shut-off, regenerative overvoltage shut-off, overload shut-off (electronic thermal relay),
servo motor overheat protection, encoder error protection, regenerative brake error protection,
undervoltage, instantaneous power failure protection, overspeed protection, excessive error
protection
Positioning by specifying the point table No. (255 points)
Set in point table. 1-point feed length setting range: 1[ m] to 999.999[mm]
Set in point table. Acceleration/deceleration time is set in point table.
S-pattern acceleration/deceleration time constant is set in parameter No.PC13.
Signed absolute value command system, incremental value command system, signed absolute
value command/incremental value command specifying system
Remote register setting is used for positioning.
Remote register is used to set position command data.
Feed length input setting range:
Remote register is used to make selection from point table.
Remote register is used to set speed command data (speed).
S-pattern acceleration/deceleration time constant is set in parameter No.PC13.
Signed absolute value command system, incremental value command system, signed absolute
value command/incremental value command specifying system
Point table number input, position data input system
Positioning operation is performed once in accordance with the position and speed commands.
Varied speed operation (2 to 255 speeds), automatic continuous positioning operation (2 to 255
points)
Jog operation is performed in accordance with the parameter-set speed command by contact input
or through CC-Link communication function.
Manual feed is made by manual pulse generator.
Command pulse multiplication:
3-phase 200 to 230VAC, 50/60Hz
3-phase 170 to 253VAC
Within
5%
Within
5%
(Note 1) 150mA
1 m to 999.999m
1, 10 or 100 is selected using parameter.
1-phase 100V to
120VAC, 50/60Hz
1-phase 85 to
132VAC
1-phase 100 to
120VAC, 50/60Hz
1-phase 85 to
132VAC
1 - 7
1. FUNCTIONS AND CONFIGURATION
Servo amplifier
Item
Dog type
Count type
Data setting type
Stopper type
Home position
ignorance
(Servo-on position
as home position)
Home position return is made starting with Z-phase pulse after passage of proximity dog.
Home position address may be set. Home position shift distance may be set. Home position return
direction may be selected.
Automatic at-dog home position return return/automatic stroke return function.
Home position return is made by counting encoder pulses after contact with proximity dog.
Home position address may be set. Home position shift value may be set. Home position return
direction may be set.
Automatic at-dog home position return return/automatic stroke return function.
Home position return is made without dog.
Home position may be set at any position by manual operation, etc. Home position address may be
set.
Home position return is made by pressing machine part against stroke end.
Home position address may be set. Home position return direction may be set.
Position where servo-on (RYn0) is switched on is defined as home position.
Home position address may be set.
Home position return is made with respect to the rear end of a proximity dog.
Home position address may be set. Home position shift value may be set. Home position return
direction may be set.
Automatic at-dog home position return return/automatic stroke return function.
Home position return is made with respect to the front end of a proximity dog.
Home position address may be set. Home position shift value may be set. Home position return
direction may be set.
Automatic at-dog home position return return/automatic stroke return function.
Home position return is made with respect to the front end of a proximity dog by the first Z-phase
pulse.
Home position address may be set. Home position shift value may be set. Home position return
direction may be set.
Automatic at-dog home position return return/automatic stroke return function.
Home position return is made with respect to the front end of a proximity dog by the last Z-phase
pulse.
Home position address may be set. Home position shift value may be set. Home position return
direction may be set.
Automatic at-dog home position return return/automatic stroke return function.
Home position return is made to the dog front end with respect to the front end of a proximity dog.
Home position address may be set. Home position shift value may be set. Home position return
direction may be set.
Automatic at-dog home position return return/automatic stroke return function.
Home position return is made with respect to the first Z-phase to the Z-phase.
Home position address may be set. Home position shift value may be set. Home position return
direction may be set.
High-speed automatic return to a defined home position.
Absolute position detection, backlash function
Overtravel prevention using external limit switch
Software stroke limit
Self-cooled, open
(IP00)
Force-cooling, open (IP00)
Self-cooled, open
(IP00)
1 - 8
1. FUNCTIONS AND CONFIGURATION
Servo amplifier
MR-J3-
Item
Ambient
temperature
humidity
Environment
Ambient
Altitude Max. 1000m above sea level
Vibration 5.9 [m/s2] or less
Mass
Note 1. 150mA is the value applicable when all I/O signals are used. The current capacity can be decreased by reducing the number of
I/O points.
2. When closely mounting the servo amplifier of 3.5kW or less, operate them at the ambient temperatures of 0 to 45