(Always read these instructions before using the equipment.)
Do not attempt to install, ope rate, maint ain or inspect the servo amplif ier and servo m otor until you hav e read
through this I nstruction M anual, Insta llation guid e, Servo motor Instructio n Manual and appen ded docum ents
carefully and can us e th e equ i pment correctly. D o no t us e t he s er vo amplifier and servo motor un ti l you have a
full knowledge of the equipment, safety information and instructions.
In this Instruction Manual, the safety instruction levels are classified into "WARNING" and "CAUTION".
Indicates that incorrect handling may cause hazardous conditions,
WARNING
CAUTION
Note that the CAUTION level may lead to a serious consequence according to conditions. Please follow the
instructions of both levels because they are important to personnel safety.
What must not be done and what must be done are indicated by the following diagrammatic symbols:
resulting in death or severe injury.
Indicates that incorrect handling may cause hazardous conditions,
resulting in medium or slight injury to personnel or may cause physical
damage.
: Indicates what must not be done. For example, "No Fire" is indicated by
: Indicates what must be done . F o r exa mple , grou nd ing is in di cat ed by
In this Instruction Manual, instructions at a lower level than the above, instructions for other functions, and so
on are classified into "POINT".
After reading this installation guide, always keep it accessible to the operator.
.
.
A - 1
1. To prevent electric shock, note the following:
WARNING
Before wiring or inspection, switch power off and wait for more than 15 minutes. Then, confirm the voltage
is safe with voltage tester. Otherwise, you may get an electric shock.
Connect the serv o a mpl i fie r and se rvo mot o r to grou nd .
Any person who is involved in wiring and inspection should be fully competent to do the work.
Do not attempt to wire the servo amplifier and servo motor until they have been installed. Otherwise, you
may get an electric shock.
Operate the switches with dry hand to prevent an electric shock.
The cables should not be damaged , stressed, loaded, or pinched. Othe rwi se, you may get an ele ctric shoc k.
During power-on or operation, do not open the front cover of the servo amplifier. You may get an electric
shock.
Do not operate the servo amplifier with the front cover removed. High-voltage terminals and charging area
are exposed and you may get an electric shock.
Except for wiring or periodic inspection, do not remove the front cover even of the servo amplifier if the
power is off. The servo amplifier is charged and you may get an electric shock.
2. To prevent fire, note the following:
CAUTION
Do not install the servo amplifier, servo motor and regenerative brake resistor on or near combustibles.
Otherwise a fire may cause.
When the servo amplifier has become faulty, switch off the main servo amplifier power side. Continuous
flow of a large current may cause a fire.
When a regenerative brake resistor is used, use an alarm signal to switch main power off. Otherwise, a
regenerative brake transistor fault or the like may overheat the regenerative brake resistor, causing a fire.
3. To prevent injury, note the follow
CAUTION
Only the voltage specified in the Instruction Manual should be applied to each terminal, Otherwise, a
burst, damage, etc. may occur.
Connect the terminals correctly to prevent a burst, damage, etc.
Ensure that polarity ( , ) is correct. Otherwise, a burst, damage, etc. may occur.
Take safety measures, e.g. provide covers, to prevent accidental contact of hands and parts (cables, etc.)
with the servo amplifier heat sink, regenerative brake resistor, servo motor, etc.since they may be hot
while power is on or for some time after power-off. Their temperatures may be high and you may get burnt
or a parts may damaged.
During operation, never touch the rotating parts of the servo motor. Doing so can cause injury.
A - 2
4. Additional instructions
The following instructions should also be fully noted. Incorrect handling may cause a fault, injury, electric
shock, etc.
(1) Transportation and installation
CAUTION
Transport the products correctly according to their masses.
Stacking in excess of the specified number of products is not allowed.
Do not carry the servo motor by the cables, shaft or encoder.
Do not hold the front cover to transport the servo amplifier. The servo amplifier may drop.
Install the servo amplifier in a load-bearing place in accordance with the Instruction Manual.
Do not climb or stand on servo equipment. Do not put heavy objects on equipment.
The controller and servo motor must be installed in the specified direction.
Leave specified clearances between the servo amplifier and control enclosure walls or other equipment.
Do not install or operate the servo amplifier and servo motor which has been damaged or has any parts
missing.
Provide adequate protection to prevent screws and other conductive matter, oil and other combustible
matter from entering the servo amplifier and servo motor.
Do not drop or strike servo amplifier or servo motor. Isolate from all impact loads.
When you keep or use it, please fulfill the following environmental conditions.
Environment
During
Ambient
temperature
Ambient
humidity
AmbienceIndoors (no direct sunlight) Free from corrosive gas, flammable gas, oil mist, dust and dirt
AltitudeMax. 1000m (3280 ft) above sea level
(Note)
Vibration
Note. Except the servo motor with reduction gear.
operation
In storage
During
operation
In storage90%RH or less (non-condensing)
[ ]0 to 55 (non-freezing)0 to 40 (non-freezing)
[
] 32 to 131 (non-freezing)32 to 104 (non-freezing)
[ ]20 to 65 (non-freezing)15 to 70 (non-freezing)
[
]4 to 149 (non-freezing)5 to 158 (non-freezing)
90%RH or less (non-condensing)80%RH or less (non-condensing)
[m/s2]5.9 or less
2
]19.4 or less
[ft/s
Servo amplifierServo motor
Conditions
HC-KFS Series
HC-MFS Series
HC-UFS13 to 73
HC-SFS52 to 152
HC-SFS53 to 153
HC-RFS Series
HC-UFS 72
HC-SFS121 201
HC-SFS202
HC-SFS203
HC-UFS202 to 502
HC-SFS301
HC-SFS502 to 702
HA-LFS11K2 to 22K2
HC-KFS Series
HC-MFS Series
HC-UFS 13 to 73
HC-SFS52 to 152
HC-SFS53 to 153
HC-RFS Series
HC-UFS 72
HC-SFS121 201
HC-SFS202
HC-SFS203
HC-UFS202 to 502
HC-SFS301
HC-SFS502 to 702
HA-LFS11K2 to 22K2
HC-SFS81
HC-SFS81
152
352
353
152
352
353
X
Y : 49
Y : 24.5
X
X : 24.5
Y : 49
X : 24.5
Y : 29.4
X : 11.7
Y : 29.4
X
Y : 161
Y : 80
X
X : 80
Y : 161
X : 80
Y : 96
X : 38
Y : 96
A - 3
CAUTION
Securely attach the servo motor to the machine. If attach insecurely, the servo motor may come off during
operation.
The servo motor with reduction gear must be installed in the specified direction to prevent oil leakage.
Take safety measures, e.g. provide covers, to prevent accidental access to the rotating parts of the servo
motor during operation.
Never hit the servo motor or shaft, especially when coupling the servo motor to the machine. The encoder
may become faulty.
Do not subject the servo motor shaft to more than the permissible load. Otherwise, the shaft may break.
When the equipment has been stored for an extended period of time, consult Mitsubishi.
(2) Wiring
CAUTION
Wire the equipment correctly and securely. Otherwise, the servo motor may misoperate.
Do not install a power capacitor, surge absorber or radio noise filter (FR-BIF option) between the servo
motor and servo amplifier.
Connect the outpu t te rminal s (U, V, W) correctly. Otherwise, th e servo mot or w ill op e rate i mprop e rly .
Servo Amplifier
U
V
W
Servo Motor
U
V
W
Do not connect AC power directly to the servo motor. Otherwise, a fault may occur.
The surge absorbing diode installed on the DC output signal relay of the servo amplifier must be wired in
the specified direction. Otherwise, the emergency stop (EMG) and other protective circuits may not
operate.
Servo
Amplifier
(24VDC)
Control
output
signal
COM
RA
Servo
Amplifier
(24VDC)
Control
output
signal
COM
RA
(3) Test run adjustment
CAUTION
Before operation, check the parameter settings. Improper settings may cause some machines to perform
unexpected operation.
The parameter settings must not be changed excessively. Operation will be insatiable.
A - 4
(4) Usage
CAUTION
Provide an exter nal emergenc y stop c ircuit to ensure that oper ation c an be sto pped an d power s witched
off immediately.
Any person who is involved in disassembly and repair should be fully competent to do the work.
Before resetting an alarm, make sure that the run signal of the servo amplifier is off to prevent an
accident. A sudden restart is made if an alarm is reset with the run signal on.
Do not modify the equipment.
Use a noise filter, etc. to minim i ze the inf lue nce of electr om agne tic int erfer enc e, wh ich m ay b e ca use d b y
electronic equipment used near the servo amplifier.
Use the servo amplifier with the specified servo motor.
Burning or breaking a servo amplifier may cause a toxic gas. Do not burn or break a servo amplifier.
The electromagnetic brake on the servo motor is designed to hold the motor shaft and should not be used
for ordinary braking.
For such reas ons as servic e life and mec hanical struc ture (e.g. wher e a ballscrew and the s ervo motor
are coupled via a tim ing belt), the electrom agnetic brak e may not ho ld the m otor shaf t. To ensur e safe ty,
install a stoppe r on the machin e si de.
(5) Corrective actions
CAUTION
When it is ass umed that a hazardous c ondition m ay take place a t the occur d ue to a po wer failure or a
product fault, use a servo motor with electromagnetic brake or an external brake mechanism for the
purpose of prev en ti on .
Configure th e electromagnet ic brake circu it so that it is activated n ot only by t he servo amplifier s ignals
but also by an external emergency stop (EMG).
Contacts must be open when
servo-off, when an trouble (ALM)
and when an electromagnetic brake
interlock (MBR).
Servo motor
Electromagnetic brake
When any alarm has occurred, eliminate its cause, ensure safety, and deactivate the alarm before
restarting operation.
When power is restor ed after an inst antaneous power failu re, keep away from the machine because th e
machine may be restarted suddenly (design the machine so that it is secured against hazard if restarted).
Circuit must be
opened during
emergency stop (EMG).
EMGRA
24VDC
A - 5
(6) Maintenance, inspection and parts replacement
CAUTION
With age, the electrolytic capacitor of the servo amplifier will deteriorate. To prevent a secondary accident
due to a fault, it is recommended to replace the electrolytic capacitor every 10 years when used in general
environment.
Please consult our sales representative.
(7) General instruction
To illustrate details, the equipment in the diagrams of this Specifications and Instruction Manual may have
been drawn withou t covers and safety guards. W hen the equipment is operated, the covers and safety
guards must be installed as specified. Operation must be performed in accordance with this Specifications
and Instruction Manual.
About processing of waste
When you discard servo amplifier, a battery (primary battery), and other option articles, please follow the law of
each country (area).
FOR MAXIMUM SAFETY
These products have been manufactured as a general-purpose part for general industries, and have not
been designed or manufactured to be incorporated in a device or system used in purposes related to
human life.
Before using the products for special purposes such as nuclear power, electric power, aerospace,
medicine, passenger movement vehicles or under water relays, contact Mitsubishi.
These products have been manufactured under strict quality control. However, when installing the product
where major accidents or losses could occur if the product fails, install appropriate backup or failsafe
functions in the system.
EEP-ROM life
The number of write times to the EEP-ROM, which stores parameter settings, etc., is limited to 100,000. If
the total number of the following operations exceeds 100,000, the servo amplifier and/or converter unit may
fail when the EEP-ROM reaches the end of its useful life.
Write to the EEP-R OM du e t o par a mete r set tin g chan ge s
Home position setting in the absolute position detection system
Write to the EEP-ROM due to device changes
Precautions for Choosing the Products
Mitsubishi will not be held liable for damage caused by factors found not to be the cause of Mitsubishi;
machine damage or lost profits caused by faults in the Mitsubishi products; damage, secondary damage,
accident compensation caused by special factors unpredictable by Mitsubishi; damages to products other
than Mitsubishi products; and to other duties.
A - 6
COMPLIANCE WITH EC DIRECTIVES
1. WHAT ARE EC DIRE C TIVES ?
The EC directives were issued to standardize the regulations of the EU countries and ensure smooth
distribution of safety-guaranteed products. In the EU countries, the machinery directive (effective in
January, 1995), EMC directive (effective in January, 1996) and low voltage directive (effective in January,
1997) of the EC directives require that products to be sold should meet their fundamental safety
requirements and carry the CE marks (CE mar king). CE marking applies to machines and equipment
into which servo amplifiers have been installed.
(1) EMC directive
The EMC directive applies not to the servo units alone but to servo-incorporated machines and
equipment. This requires the EMC filters to be used with the servo-incorporated machines and
equipment to comply with the EMC directive. For specific EMC directive conforming methods, refer to
the EMC Installation Guidelines (IB(NA)67310).
(2) Low voltage di re ctiv e
The low voltage directive applies also to servo units alone. Hence, they are designed to comply with
the low voltage directive.
This servo is certified by TUV, third-party assessment orga nization, to comply with the low voltage
directive.
(3) Machine directive
Not being machines, the servo amplifiers need not comply with this directive.
2. PRECAUTIONS FOR COMPLIANCE
(1) Servo amplifiers and servo motors used
Use the servo amplifiers and servo motors which comply with the standard model.
Servo amplifier:MR-J2S-10A to MR-J2S-22KA
MR-J2S-10A1 to MR-J2S-40A1
Servo motor:HC-KFS
HC-MFS
HC-SFS
HC-RFS
HC-UFS
HA-LFS
HC-LFS
(2) Configuration
Control box
Reinforced
(Note)
Reinforced
insulating
transformer
No-fuse
breaker
NFB
Magnetic
contactor
MCM
insulating type
24VDC
power
supply
Servo
amplifier
Servo
motor
Note. The insulating transformer is not required for the 11kW or more servo amplifier.
(3) Environment
Operate the servo amplifier at or above the contaminat ion level 2 set forth in IEC60664-1. For this
purpose, install the servo amplifier in a control box which is protected against water, oil, carbon, dust,
dirt, etc. (IP54).
A - 7
(4) Power supply
(a) Operate the servo amplifier 7kW or less to meet the requirements of the overvoltage category II set
forth in IEC60664-1. For this purpose, a reinforced insulating transformer conforming to the IEC
or EN standard should be used in the power input section.
Since the 11kW or more servo amplifier can be used under the conditions of the overvoltage
category III set forth in IE60664-1, a reinforced insulating transformer is not required in the power
input section.
(b) When supplying interface power from external, use a 24VDC power supply which has been
insulation-reinforced in I/O.
(5) Grounding
(a) To prevent an electric shock, always connect the protective earth (PE) terminals (marked
servo amplifier to the protective earth (PE) of the control box.
(b) Do not co nnect two g round c ables to the same pro tective e arth (PE) terminal. Always c onnect the
cables to the terminals one-to-one.
) of the
PE terminals
PE terminals
(c) If a leakage current breaker is used to prevent an electric shock, the protective earth (PE) terminals
of the servo amplifier must be c onne ct ed t o t h e c orr es pondi n g eart h te rmi nal s.
(6) Wiring
(a) The cables to be connected to the terminal block of the servo amplifier must have crimping
terminals provided with insulating tubes to prevent contact with adjacent terminals.
Crimping terminal
Insulating tube
Cable
(b) Use the servo motor side power connector which complies with the EN Standard. The EN Standard
compliant power connector sets are available from us as options.
A - 8
(7) Auxiliary equipment and options
(a) The no-fuse breaker and magnetic contactor used should be the EN or IEC standard-compliant
products of the models described in Section 13.2.2.
(b) The sizes of the cable s described in Section 13.2. 1 meet the following req uirements. To meet t he
other requirements, follow Table 5 and Appendix C in EN60204-1.
Ambient tempera t ur e: 40 (104 ) [ ( )]
Sheath: PVC (polyvinyl chloride)
Installed on wall surface or open table tray
(c) Use the EMC filter for noise reduction.
(8) Performing EMC tests
When EMC tests are ru n on a machine/device in to which the servo amplifier has been installed, i t
must conform to the electromagnetic compatibility (immunity/emission) standards after it has
satisfied the operating environment/electrical equipment specificati ons.
For the other EMC directive guidelines on the servo amplifier, refer to the EMC Installation
Guidelines(IB(NA)67310).
A - 9
CONFORMANCE WITH UL/C-UL STANDARD
(1) Servo amplifiers and servo motors used
Use the servo amplifiers and servo motors which comply with the standard model.
Servo amplifier:MR-J2S-10A to MR-J2S-22KA
MR-J2S-10A1 to MR-J2S-40A1
Servo motor:HC-KFS
HC-MFS
HC-SFS
HC-RFS
HC-UFS
HA-LFS
HC-LFS
(2) Installation
3
Install a fan of 100CFM (2.8m
cooling of at least equivalent capability.
(3) Short circuit rating
This servo amplifier conforms to the circuit whose peak current is limited to 5000A or less. Having
been subjected to the short-circuit tests of the UL in the alternating-current circuit, the servo
amplifier conforms to the above circuit.
/min) air flow 4 in (10.16 cm) above the servo amplifier or provide
(4) Capacitor discharge time
The capacitor disc har ge tim e is a s listed belo w. To ensu re safety , do no t touch th e ch arg ing sec tion for
15 minutes after power-off.
Servo amplifier
MR-J2S-10A(1) 20A(1)1
MR-J2S-40A(1) 60A2
MR-J2S-70A to 350A3
MR-J2S-500A 700A5
MR-J2S-11KA4
MR-J2S-15KA6
MR-J2S-22KA8
(5) Options and auxiliary equipment
Use UL/C-UL standard-compliant products.
(6) Attachment of a servo motor
For the flange size of the machine side where the servo motor is installed, refer to “CONFORMANCE
WITH UL/C-UL STANDARD” in the Servo Motor Instruction Manual.
(7) About wiring protection
For installation in United States, branch circuit protection must be provided, in accordance with the
National Electrical Code and any applicable local codes.
For installation in Canada, branch circuit protection must be provided, in accordance with the Canada
Electrical Code and any applicable provincial codes.
Discharge time
[min]
A - 10
<<About the manual s>>
This Instruction Manua l and the MEL SERVO Se rvo Moto r Ins truc tion M anua l are re quired if yo u use
the General-Purpose AC servo MR-J2S-A for the first time. Always purchase them and use the MRJ2S-A safely.
Relevant manuals
Manual nameManual No.
MELSERVO-J2-Super Series To Use the AC Servo SafelyIB(NA)0300010
MELSERVO Servo Motor Instruction ManualSH(NA)3181
EMC Installation GuidelinesIB(NA)67310
1.2 Function block diagram ..........................................................................................................................1- 2
1.3 Servo amplifier standard specifications................................................................................................1- 5
1.4 Function list.............................................................................................................. ...............................1- 6
1.5 Model code definition ..............................................................................................................................1- 7
1.6 Combination with servo motor............................................................................................... ................1- 9
1.7.1 Parts identification..........................................................................................................................1-10
1.7.2 Removal and reinstallation of the front cover ..............................................................................1-15
1.8 Servo system with auxiliary equipment...............................................................................................1-19
3.1 Standard connection example ................................................................................................................3- 2
3.1.1 Position control mode .......................................................................................................................3- 2
3.1.2 Speed control mode...........................................................................................................................3- 6
3.1.3 Torque control mode.........................................................................................................................3- 8
3.2 Internal connection diagram of servo amplifier ..................................................................................3-10
3.3.1 Connectors and signal arrangements............................................................................................3-11
3.3.2 Signal explanations .........................................................................................................................3-15
3.4 Detailed description of the signals........................................................................................................3-24
3.4.1 Position control mode ......................................................................................................................3-24
3.4.2 Speed control mode..........................................................................................................................3-29
3.4.3 Torque control mode........................................................................................................................3-31
3.4.4 Position/speed control change mode ..............................................................................................3-34
3.4.5 Speed/torque control change mode.................................................................................................3-36
3.4.6 Torque/position control change mode ............................................................................................3-38
3.6.1 Common line ....................................................................................................................................3-40
3.6.2 Detailed description of the interfaces............................................................................................3-41
3.7 Input power supply circuit.....................................................................................................................3-46
4.2.1 Selection of control mode..................................................................................................................4- 2
4.2.2 Position control mode .......................................................................................................................4- 2
4.2.3 Speed control mode...........................................................................................................................4- 4
4.2.4 Torque control mode.........................................................................................................................4- 5
4.3 Multidrop communication ......................................................................................................................4- 6
5.2.2 Analog monitor.................................................................................................................................5-30
5.2.3 Using forward/reverse rotation stroke end to change the stopping pattern..............................5-33
5.2.4 Alarm history clear..........................................................................................................................5-33
5.2.5 Position smoothing ..........................................................................................................................5-34
6.2 Status display ..........................................................................................................................................6- 2
6.2.2 Status display list.............................................................................................................................6- 3
6.2.3 Changing the status display screen................................................................................................6- 4
6.6 External I/O signal display.....................................................................................................................6- 9
6.7 Output signal (DO) forced output .........................................................................................................6-12
6.8 Test operation mode...............................................................................................................................6-13
6.8.2 Jog operation....................................................................................................................................6-14
7.1 Different adjustment methods ...............................................................................................................7- 1
7.1.1 Adjustment on a single servo amplifier..........................................................................................7- 1
7.1.2 Adjustment using MR Configurator (servo configuration software)...........................................7- 2
7.2 Auto tuning ..............................................................................................................................................7- 3
7.2.1 Auto tuning mode .............................................................................................................................7- 3
7.2.2 Auto tuning mode operation............................................................................................................7- 4
7.2.3 Adjustment procedure by auto tuning............................................................................................7- 5
7.2.4 Response level setting in auto tuning mode...................................................................................7- 6
7.5.2 Auto tuning selection....................................................................................................................... 7-11
8. SPECIAL ADJUSTMENT FUNCTIONS8- 1 to 8-10
8.1 Function block diagram ..........................................................................................................................8- 1
8.5 Gain changing function...........................................................................................................................8- 5
14.4 Character codes ...................................................................................................................................14- 7
14.12 Detailed explanations of commands...............................................................................................14-14
14.12.1 Data processing..........................................................................................................................14-14
14.12.2 Status display ............................................................................................................................14-16
15.4 Standard connection diagram ............................................................................................................15- 4
15.5 Signal explanation...............................................................................................................................15- 5
15.7 Absolute position data transfer protocol ...........................................................................................15- 7
15.7.1 Data transfer procedure...............................................................................................................15- 7
15.7.2 Transfer method ...........................................................................................................................15- 8
15.7.3 Home position setting..................................................................................................................15-17
15.7.4 Use of servo motor with electromagnetic brake .......................................................................15-19
15.7.5 How to process the absolute position data at detection of stroke end....................................15-20
15.8 Examples of use..................................................................................................................................15-21
App 1. Signal arrangement recording sheets.........................................................................................App- 1
App 2. Status display block diagram ......................................................................................................App- 2
App 3. Combination of servo amplifier and servo motor ...................................................................... App- 3
5
Optional Servo Motor Instruction Manual CONTENTS
The rough table of contents of the optional MELSERVO Servo Mo tor Instruc tion Manual is introduced
here for your reference. Note that the contents of the Servo Motor Instruction Manual are not included
in the Servo Amplifier Instruction Manual.
1. INTRODUCTION
2. INSTALLATION
3. CONNECTORS USED FOR SERVO MOTOR WIRING
4. INSPECTION
5. SPECIFICATIONS
6. CHARACTERISTICS
7. OUTLINE DIMENSION DRAWINGS
8. CALCULA TI ON ME TH O DS F OR DES I G NI N G
6
1. FUNCTIONS AND CONFIGURATION
1. FUNCTIONS AND CONFIGURATION
1.1 Introduction
The Mitsubishi MELSERVO-J2-Super series general-purpose AC servo is ba sed on the MELSERVO-J2
series and has further higher performance and higher functions.
It has position control, speed control and torque control modes. Further, it can perform operation with the
control modes changed, e.g. position/speed control, speed/torque control and torque/position control.
Hence, it is applicable to a wide range of fields, not only precision positioning and smooth speed control of
machine tools and general industrial machines but also line control and tension control.
As this new series has the RS-232C or RS-422 serial communication function, a MR Conf igurator (servo
configuration software)-installed personal computer or the like can be used to perform parameter setting,
test operation, status display monitoring, gain adjustment, etc.
With real-time auto tuning, you can automatically adjust the servo gains according to the machine.
The MELSERVO-J2-Super series servo motor is equipped with an absolute position encoder which has
the resolution of 131072 pulses/rev to ensure more accurate control as compared to the MELSERVO-J2
series. Simply adding a battery to the servo amplifier makes up an abso lute position dete ction system.
This makes home position return unnecessary at power-on or alarm occurrence by setting a home position
once.
(1) Position control mode
An up to 500kpps high-speed pulse train is used to control the speed and direction of a motor and
execute precision positioning of 131072 pulses/rev resolution.
The position smoothing function provides a choice of two different modes appropriate for a machine, so
a smoother start/stop can be made in response to a sudden position command.
A torque lim it is imposed on th e se rv o amp l if ier by the clamp circuit to p ro te c t the powe r transisto r in
the main circuit from overcurrent due to sudden acceleration/deceleration or overload. This torque
limit value can be changed to any value with an external analog input or the parameter.
(2) Speed control mode
An external analog speed command (0 to
(max. 7 speeds) is used to control the speed and direction of a servo motor smoothly.
There are also the acceleration/deceleration time constant setting in response to speed command, the
servo lock function at a stop time, and automatic offset adjustment function in response to external
analog speed command.
(3) Torque control mode
An external an alog torque command (0 to
used to control the torque output by the servo motor.
To protect misoperation under no load, the speed limit function (external or internal setting) is also
available for application to tension control, etc.
10VDC) or parameter-driven internal speed command
8VDC) or parameter-driven internal torque command is
1 - 1
1. FUNCTIONS AND CONFIGURATION
1.2 Function block diagram
The function block diagram of this servo is shown below.
(1) MR-J2S-350A or less
Regenerative brake option
(Note2)
Power
NFB
supply
3-phase
200 to
230VAC,
1-phase
230VAC or
1-phase
100to120VAC
MC
Servo amplifier
1
L
2
L
L
3
(MR-J2 S-200A or more)
11
L
L
21
Regenerative
brake
Pulse
input
RADS
Control
circuit
power
supply
Model position
control
P
C
CHARGE
lamp
Regenerative
TR
Fan
Base amplifier
Model speed
control
D
(Note1)
Voltage
detection
Current
detector
Overcurrent
protection
encoder
Virtual
motor
Dynamic
Virtual
brake
Current
detection
U
V
W
CN2
Servo motor
U
V
W
B1
B2
Encoder
M
Electromagnetic
brake
Model
position
Actual position
control
Model
speed
Actual speed
control
Model
torque
Current
control
RS-232C
A/D
RS-422
D/A
I/F
CN1A CN1B
CN3
Analog monitor
(2 channels)
Controller
RS-422/RS-232C
Analog
(2 channels)
D I/O control
Servo on
Start
Failure, etc.
Note 1. The built-in regenerative brake resistor is not provided for the MR-J2S-10A(1).
2. For 1-phase 230VAC, connect the power supply to L
L
is not provided for a 1-phase 100 to120VAC power supply.
3
and leave L3 open.
1,L2
1 - 2
MR-BAT
CON1
Optional battery
(for absolute position
detection system)
1. FUNCTIONS AND CONFIGURATION
(2) MR-J2S-500A MR-J2S-700A
Regenerative brake option
Power
supply
3-phase
200 to
230VAC
NFB
Servo amplifier
MC
NCP
1
RADS
L
2
L
L
3
CHARGE
lamp
Regenerative
TR
Fan
Current
detector
Dynamic
U
V
W
Servo motor
U
V
SM
W
brake
B1
B2
Electromagnetic
brake
L
11
Control
circuit
L
21
power
supply
Regenerative
brake
Base amplifier
Voltage
detection
Overcurrent
protection
Current
detection
CN2
Encoder
Pulse
input
Model position
control
Model speed
control
Virtual
encoder
Virtual
motor
Analog
(2 channels)
Model
position
Actual position
control
A/D
CN1A CN1B
D I/O control
Servo on
Start
Failure, etc.
Model
speed
Actual speed
control
RS-232C
I/F
RS-422
CN3
Model
torque
Current
control
D/A
Analog monitor
(2 channels)
Controller
RS-422/RS-232C
MR-BAT
CON1
Optional battery
(for absolute position
detection system)
1 - 3
1. FUNCTIONS AND CONFIGURATION
(3) MR-J2S-11KA or more
Regenerative brake option
Power
supply
3-phase
200 to
230VAC,
1-phase
230VAC
NFBMC
Servo amplifier
DS
L
1
2
L
3
L
11
L
21
L
Regenerative
brake
Position
command
input
CHARGE
Control
power
supply
amplifier
Model position
control
PC
lamp
Fan
Base
Model speed
NP1
detection
control
Regenerative
TR
Voltage
Overcurrent
protection
Virtual
motor
Current
detecto r
Current
detection
Virtual
encoder
U
V
W
CN2
Servo motor
U
V
SM
W
B1
Electromagnetic
B2
brake
Encoder
Analog
(2 channels)
Model
position
Actual position
control
A/D
CN1A CN1B
D I/O control
Servo on
Start
Failure, etc.
Actual speed
control
RS-232C
I/F
Model
speed
RS-422 D/A
CN3CN4
Model
torque
Current
control
Analog monitor
(2 channels)
Controller
RS-422/RS-232C
MR-BAT
CON1
Optional battery
(for absolute position
detection system)
1 - 4
1. FUNCTIONS AND CONFIGURATION
1.3 Servo amplifier standard specifications
Servo Amplifier
MR-J2S-
Item
Voltage/frequency
Permissible voltage fluctuation
Power supply
Permissible frequency fluctuationWithin 5%
Power supply capacityRefer to Section12.2
Inrush currentRefer to Section 12.5
Control systemSine-wave PWM control, curr ent c ontr ol syste m
Dynamic brakeBuilt-inExternal optionBuilt-in
Analog speed co mma n d i nput0 to 10VDC / Rated speed
0.01% or less (load fluctuation 0 to 100%)
Speed fluctuation ratio
0.2% max.(ambient temperature 25 10 ) for external speed setting only
Speed control m ode
Torque limitSet by parameter setting or external analog input (0 to 10VDC/maximum torque)
Torque
control
mode
StructureSelf-cooled, open (I P00)Force-cooling, open (IP00 )
Mass
Note. The error excessive detection for 2.5 revolutions is available only when the servo amplifier of software version B 0 or l ater is
Analog torque command in p ut0 to 8VDC / Maximum torque (input impedance 10 to 12k )
Speed limitSet by parameter setting or external analog input (0 to
Ambient
temperature
Ambient
humidity
Ambient
Environment
AltitudeMax. 1000m (3280ft) above sea level
Vibration
used. When the software version is earlier than B0, the error excessive detection level of that servo ampli fie r is
Operation
Storage
Operation
Storage
[ ]0 to 55 (non-freezing)
[
] 32 to 131 (non-freezing)
[ ]20 to 65 (non-freezing)
[
]4 to 149 (non-freezing)
90%RH or less ( non - condensing)
Indoors (no dir ect su nl i gh t )
Free from corrosive gas, flammable gas, oil mist, dust and dirt
The following table lists the functions of this servo. For details of the functi ons, refer to the reference field.
FunctionDescription
Position control modeThis servo is used as position control servo.P
Speed control modeThis servo is used as speed control servo.S
Torque control modeThis servo is used as torque control servo.T
Position/speed control cha nge
mode
Speed/torque control change
mode
Torque/position control
change mode
High-resolut ion encoder
Absolute position detection
system
Gain changing function
Adaptive vibration
suppression control
Low-pass filter
Machine analyzer function
Machine simulation
Gain search function
Slight vibration suppression
control
Electronic gearInput pulses can be multiplied by 1/50 to 50.PParameters No. 3, 4
Auto tuning
Position smoothingSpeed can be increased smoothly in response to input pulse.PParameter No. 7
S-pattern acceleration/
deceleration time constant
Regenerative brake option
Brake unit
Using external input signal, control can be switched
between pos i tion control and speed control.
Using external input signal, control can be switched
between speed control and torque control.
Using external input signal, control can be switched
between to rque control a nd position control.
High-resolution encoder of 131072 pulses/rev is used as a
servo motor encoder.
Merely setting a home position once makes home position
return unnecessary at every power-on.
You can switch between gains during rotation and gains
during stop or use an external signal to change gains
during operation.
Servo amplifier detects mechanical resonance and sets filter
characteristics automatically to suppress mechanical
vibration.
Suppresses high-frequency resonance which occurs as servo
system response is increased.
Analyzes the frequency characteristic of the mechanical
system by simply connecting a MR Configurator (servo
configuration) software-installed personal computer and
servo amplifier.
Can simulate machine motions on a personal computer
screen on the basis of the machine analyzer results.
Personal computer changes gains automatically and
searches for overshoot-free gains in a short time.
Suppresses vibration of 1 pulse produced at a servo motor
stop.
Automatically adjusts the gain to optimum value if load
applied to the servo motor shaft varies. Higher in
performance than MR-J2 series servo amplifier.
Speed can be increased and decreased smoothly.S, TParameter No. 13
Used when the built-in regenerative brake resistor of the
servo amplifier does not have sufficient regenerative
capability for the regenerative power generated.
Used when the regenerative brake option cannot provide
enough regenerative power.
Can be used with the MR-J2S-500A to MR-J2S-22KA.
Used when the regenerative brake option cannot provide
Return conv erter
enough regenerative power.
P, S, TSection 13.1.3
Can be used with the MR-J2S-500A to MR-J2S-22KA.
Alarm history cl ea rAlarm history is cleared.P, S, TParameter No. 16
Restart after instantaneous
power failure
Command pulse selection
Input signal selection
Torque limitServo motor torque can be limited to any value.P, S
If the input power supply vol tage had reduced to cause an
alarm but has returned to normal, the servo motor can be
restarted by merely switching on the start signal.
Command pulse train form can be selected from among four
different types.
Forward rotation start, reverse rotation start, servo-on
(SON) and other input signals can be assigned to any pins.
Speed limitServo motor speed can be limited to any value.T
Parameter No. 8
to 10,72 to 75
Status display
External I/O signal display
Output signal (DO)
forced output
Servo status is shown on the 5-digit, 7-segment LED
display
ON/OFF statuses of external I/O signals are shown on the
display.
Output signal can be forced on/off independently of the
servo status.
Use this function for output signal wiring check, etc.
P, S, TSection 6.2
P, S, TSection 6.6
P, S, TSection 6.7
Voltage is automatically offset to stop the servo motor if it
Automatic VC offset
does not come to a stop at the analog speed command (VC)
S, TSection 6.3
or analog speed limit (VLA) of 0V.
Test operati on mode
JOG operation
DO forced output.
positioning operation motor-less operation
P, S, TSection 6.8
Analog monitor outputServo status is output in terms of voltage in real time.P, S, TParameter No. 17
MR Configurator
(Servo configuration software)
Alarm code output
Using a personal computer, parameter setting, test
operation, status display, etc. can be performed.
If an alarm has occurred, the corresponding alarm number
is output in 3-bit code.
P, S, TSection 13.1.9
P, S, TSection 10.2.1
Note. P: Position control mode, S: Speed control mode, T: Torque control mode
P/S: Position/speed control change mode, S/T: Speed/torque control change mode, T/P: Torque/position control change mode
1.5 Model code definition
(1) Rating plate
MITSUBISHI
MODEL
POWER
MR-J2S-60A
POWER :
INPUT :
OUTPUT :
SERIAL :
MITSUBISHI ELECTRIC CORPORATION
MADE IN JAPAN
600W
3.2A 3PH 1PH200-230V 50Hz
3PH 1PH200-230V 60Hz
5.5A 1PH 230V 50/60Hz
170V 0-360Hz 3.6A
A5
TC3 AAAAG52
AC SERVO
AC SERVO
PASSED
Model
Capacity
Applicable powe r supply
Rated output current
Serial number
1 - 7
1. FUNCTIONS AND CONFIGURATION
(2) Model
MR–J2S–
A
MR–J2S–100A or less
MR–J2S–200A 350A
Series
Symbol
SymbolMR-J2S-500A
(Note2)
Note 1. 1-phase 230V is supported
by 750W or less.
2. 1-phase 100V to 120V is
supported by 400W or less.
Rated output
Symbol
70
With no regenerative resistor
Description
Indicates a servo amplifier
of 11 to 22kw that does not
PX
use a regenerative resistor
as standard accessory.
Power Supply
Power supply
None
3-phase 200 to 230VAC
(Note1) 1-phase 230VAC
1-phase 100V to 120VAC
1
General-purpose interface
Rated
output [kW]
0.110
0.220
0.440
0.660
0.75
1100
2200
Symbol
11k
15k
22k
Rated
output [kW]
3.5350
5500
7700
11
15
22
Rating plate
Rating plateRating plate
MR-J2S-11KA 15KA
MR-J2S-22KA
Rating plate
MR-J2S-700A
1 - 8
Rating plateRating plate
1. FUNCTIONS AND CONFIGURATION
1.6 Combination with servo motor
The following table lists combina tion s of servo amplifie rs and se rvo mo tors. The same combina tions ap ply
to the models with electromagnetic brakes and the models with reduction gears.
The servo amplifier is shown without the front cover. For removal of the
front cover, refer to Section 1.7.2.
MODE UP DOWN
SET
Name/ApplicationReference
Battery connector (CON1)
Used to connect the battery for absolute position data
backup.
Battery holder
Contains the battery for absolute position data backup.
Display
The 5-digit, seven-segment LED shows the servo
status and alar m number .
Operation section
Used to perform status display, diagnostic, alarm and
parameter setting operations.
MODEUPDOWN SET
Section15.3
Section15.3
Chapter6
Fixed part
(4 places)
Used to set data.
Used to change the
display or data in each
mode.
Used to change the
mode.
I/O signal connector (C N 1A)
Used to connect digital I/O signals.
I/O signal connector (C N 1B)
Used to connect digital I/O signals.
Communication connector (CN3)
Used to connect a command device (RS-422/RS232C)
and output analog monitor data.
Encoder con n e ctor (CN2)
Used to connect the ser v o mo to r en coder.
Charge lamp
Lit to indicate that the main circuit is charged.
While this lamp is lit, do not reconnect the cables.
Control circ ui t t e rm i nal block (TE2)
Used to connect the control circuit power supply and
regenerative brake option.
Chapter6
Section3.3
Section3.3
Section3.3
Section13.1.5
Chapter14
Section3.3
Section13.1.5
Section3.7
Section11.1.1
Cooling fan
Main circuit terminal block (TE1)
Used to connect the input power supply and servo
motor.
Name plateSection1.5
Protective earth (PE) terminal ( )
Ground terminal.
Section3.7
Section11.1
Section13.1.1
Section3.10
Section11.1
1 - 12
1. FUNCTIONS AND CONFIGURATION
(4) MR-J2S-700A
POINT
The servo amplifier is shown without the front cover. For removal of the
front cover, refer to next page.
MODE UP DOWN
Name/Application
Battery connector (CON1)
Used to connect the battery for absolute position data
backup.
Battery holder
Contains the battery for absolute position data backup.
Display
The 5-digit, seven-segment LED shows the servo
status and alarm number.
Operation section
SET
Used to perform status display, diagnostic, alarm and
parameter setting operations.
MODEUPDOWNSET
Used to set data.
Used to change the
display or data in each
mode.
Used to change the
mode.
I/O signal connector (CN1A)
Used t o connect dig ital I/O signals.
Reference
Section15.3
Section15.3
Chapter6
Chapter6
Section3.3
Cooling fan
Fixed part
(4 places)
I/O signal connector (CN1B)
Used t o connect dig ital I/O signals.
Communication connector (CN3)
Used to connect a command device (RS-422/RS232C)
and output analog monitor data.
Charge lamp
Lit to indicate that the main circuit is charged.
While this lamp is lit, do not reconnect the cables.
Control circuit terminal block (TE2)
Used to connect the control circuit power supply.
Encoder connector ( C N2 )
Used to connect the servo mot or encoder.
Name plate
Main circuit terminal block (TE1)
Used to connect the input power supply, regen e rative
brake option and servo motor.
Note. The HC-SFS, HC-RFS series have cannon connectors.
Servo motor
1 - 20
1. FUNCTIONS AND CONFIGURATION
(2) MR-J2S-200A MR-J2S-350A or more
3-phase 200V
to 230VAC
power supply
No-fuse
breaker
(NFB) or
fuse
Magnetic
contactor
(MC)
Power
factor
improving
reactor
(FR-BAL)
Options and auxiliary equipment
No-fuse breaker
Magnetic contactor
MR Configurator
(Servo configuration software)
Servo amplifier
To CN2
L
11
L
21
Reference
Section 13.2.2
Section 13.2.2
Section 13.1.9
Options and auxiliary equipmentReference
Regenerative brake option
Section 13.1.1
CablesSection 13.2.1
Power factor improving reactor Section 13.2.3
Command device
To CN1A
Junction terminal
block
To CN1B
MR Configurator
(Servo
To CN3
Personal
computer
configuration
software
MRZJW3SETUP151E)
L
1
L
2
L
3
UV
PC
W
Regenerative brake option
1 - 21
1. FUNCTIONS AND CONFIGURATION
(3) MR-J2S-500A
3-phase 200V
to 230VAC
power supply
No-fuse
breaker
(NFB) or
fuse
Magnetic
contactor
(MC)
Options and auxiliary equipment
No-fuse breaker
Magnetic contactor
MR Configurator
(Servo configuration software)
Reference
Section 13.2.2
Section 13.2.2
Section 13.1.9
Options and auxiliary equipment
Regenerative brake option
Reference
Section 13.1.1
CablesSection 13.2.1
Power factor improving reactor Section 13.2.3
Power
factor
improving
reactor
(FA-BAL)
(Note)
C
Regenerative brake
option
L
11
21
L
Servo amplifier
Command device
To CN1A
1
L
L
2
L
3
To CN1B
Junction terminal
block
MR Configurator
(Servo
configuration
P
U
V
To CN3
Personal
computer
W
software
MRZJW3SETUP151E)
To CN2
Note. When using the regenerative brake option, remove the lead wires of the built-in regenerative brake resistor.
1 - 22
1. FUNCTIONS AND CONFIGURATION
r
(4) MR-J2S-700A
3-phase 200V
to 230VAC
power supply
No-fuse
breaker
(NFB) or
fuse
Magnetic
contactor
(MC)
Power
factor
improving
reactor
(FA-BAL)
Options and auxiliary equipment
No-fuse breaker
Magnetic contactor
MR Configurator
(Servo configuration software)
Servo amplifier
L
11
21
L
L
3
L
2
1
L
Reference
Section 13.2.2
Section 13.2.2
Section 13.1.9
To CN1A
To CN1B
To CN3
To CN2
U
V
W
Options and auxiliary equipment
Regenerative brake option
Reference
Section 13.1.1
CablesSection 13.2.1
Power factor improving reactor Section 13.2.3
Command device
Junction terminal
block
MR Configurato
(Servo
configuration
Personal
computer
software
MRZJW3SETUP151E)
C
P
(Note) Regenerative brake
option
Note. When using the regenerative brake option, remove the lead wires of the built-in regenerative brake resistor.
1 - 23
1. FUNCTIONS AND CONFIGURATION
(5) MR-J2S-11KA or more
3-phase 200V
to 230VAC
power supply
No-fuse
breaker
(NFB) or
fuse
Magnetic
contactor
(MC)
(Note2)
Power
factor
improving
reactor
(FA-BAL)
Options and auxiliary equipment
No-fus e breaker
Magnetic contactor
MR Configurator
(Servo configuration software)
L
21
L
11
Reference
Section 13.2.2
Section 13.2.2
Section 13.1.9
To CN3
MITSUBISH I
Options and auxiliary equipment
Regenerative brake option
Reference
Section 13.1.1
CablesSection 13.2.1
Power factor improving reactor Section 13.2.3
Power factor improving
DC reactor
Section 13.2.4
MR Configurator
(Servo
configuration
Personal
computer
software
MRZJW3-
SETUP151E)
Analog monitor
To CN4
Command device
To CN1A
L
3
L
2
L
1
To CN1B
To CN2
C
Regenerative brake
option
Junction terminal
block
P
(Note2)
Power factor
improving DC reactor
(FR-BEL)
(Note1)
BW
BV
BU
UVW
Note1. There is no BW when the HA-LFS11K2 is used.
2. Use either t h e F R - BA L or F R- B E L power factor im pr oving reactor .
Servo motor
series
1 - 24
2. INSTALLATION
2. INSTALLATION
CAUTION
Stacking in excess of the limited number of products is not allowed.
Install the equipment to incombustibles. Installing them directly or close to
combustibles will led to a fire.
Install the equipment in a load-bearing place in accordance with this Instruction
Manual.
Do not get on or put heavy load on the equipment to prevent injury.
Use the equipment within the specified environmental condition range.
Provide an adequate protection to prevent screws, metallic detritus and other
conductive matter or oil and other combustible matter from entering the servo
amplifier.
Do not block the inta ke /e xhau st po rts o f th e se rv o ampl ifier. Otherwis e, a fa ul t may
occur.
Do not subject the servo amplifier to drop impact or shock loads as they are
precision equipment.
Do not install or operate a faulty servo amplifier.
When the product has been stored for an extended period of time, consult
Mitsubishi.
When treating the servo amplifier, be careful about the edged parts such as the
corners of the servo amplifier.
Indoors (no direct sunlight)
Free from corrosive gas, flammable gas, oil mist, dust and dirt
[m/s2] 5.9 [m/s2] or less
2
] 19.4 [ft/s2] or less
[ft/s
2 - 1
2. INSTALLATION
2.2 Installation direction and clearances
The equipment mus t be installe d in the specif ied direc tion. Other wise, a fau lt ma y
CAUTION
(1) Installation of one servo amplifier
10mm
(0.4 in.)
or more
occur.
Leave specified clearances between the servo amplifier and control box inside
walls or other equipment.
Control boxControl box
40mm
(1.6 in.)
or more
Servo amplifier
10mm
(0.4 in.)
or more
Wiring clearance
70mm
(2.8 in.)
Top
40mm
(1.6 in.)
or more
Bottom
2 - 2
2. INSTALLATION
(2) Installation of two or more servo amplifiers
Leave a large clearance between the top of the servo amplifier and the internal surface of the control
box, and install a fan to prevent the internal temperature of the control box from exceeding the
environmental conditions.
Control box
100mm
(4.0 in.)
or more
Servo
amplifier
10mm
(0.4 in.)
or more
30mm
(1.2 in.)
or more
40mm
(1.6 in.)
or more
30mm
(1.2 in.)
or more
(3) Others
When using heat generating equipment such as the regenerative brake option, install them with full
consideration of heat generation so that the servo amplifier is not affected.
Install the servo amplifier on a perpendicular wall in the correct vertical direction.
2.3 Keep out foreign materials
(1) When installin g the unit in a control box, prevent drill ch ips and wire fragmen ts from entering the
servo amplifier.
(2) Prevent oil, water, metallic dust, etc. from entering the servo amplifier through openings in the control
box or a fan installed on the ceiling.
(3) When installing the control box in a place where there are much toxic gas, dirt and dust, conduct an
air purge (force clean air into the control box from outside to make the internal pressure higher than
the external pressure) to prevent such materials from entering the control box.
2 - 3
2. INSTALLATION
2.4 Cable stress
(1) The way of clamping the cable must be fully examined so that flexing stress and cable's own mass
stress are not applied to the cable connection.
(2) For use in any application where the servo motor moves, fix the cables (encoder, power supply, brake)
supplied with the servo motor, and flex the optional encoder cable or the power supply and brake
wiring cables. Use the optional encoder cable within the flexing life range. Use the power supply and
brake wiring cables within the flexing li fe of the cabl es.
(3) Avoid any probability that the cable sheath might be cut by sharp chips, rubbed by a machine corner
or stamped by workers or vehicles.
(4) For installation on a machine where the servo motor will move, the flexing radius should be made as
large as possible. Refer to section 12.4 for the flexing life.
2 - 4
3. SIGNALS AND WIRING
3. SIGNALS AND WIRING
Any person who is involved in wiring should be fully competent to do the work.
Before starting wiring, switch power off, then wait for more than 15 minutes, and
after the charge lamp has gone off, make sure that the voltage is safe in the tester
or like. Otherwise, you may get an electric shock.
WARNING
CAUTION
Ground the servo amplifier and the servo motor securely.
Do not attempt to wire the servo amplifier and servo motor until they have been
installed. Otherwise, you may get an electric shock.
The cables should not be damaged, stressed excessively, loaded heavily, or
pinched. Otherwise, you may get an electric shock.
Wire the equipment correctly and securely. Otherwise, the servo motor may
misoperate, resulting in injury.
Connect cables to correct terminals to prevent a burst, fault, etc.
Ensure that polarity ( , ) is correct. Otherwise, a burst, damage, etc. may occur.
The surge absorbing diode installed to the DC relay designed for control output
should be fitted in the specified direction. Otherwise, the signal is not output due to
a fault, disabling the emergency stop (EMG) and other protective circuits.
Servo
Amplifier
COM
(24VDC)
Control
output
signal
RA
Servo amplifier
COM
(DC24V)
Control output
signal
RA
Use a noise filter, etc. to minimize the influence of electromagnetic interference,
which may be given to electronic equipment used near the servo amplifier.
Do not install a power capacitor, surge suppressor or radio noise filter (FR-BIF
option) with the power line of the servo motor.
When using the regenerative brake resistor, switch power off with the alarm signal.
Otherwise, a transistor fault or the like may overheat the regenerative brake
resistor, causing a fire.
Do not modify the equipment.
POINT
CN1A, CN1B, CN2 and CN3 have the same shape. Wrong connection of
the connectors will lead to a failure. Connect them correctly.
3 - 1
3. SIGNALS AND WIRING
3.1 Standard connection example
POINT
Refer to Section 3.7.1 for the connection of the power supply system and to
Note 1. To prevent an electric shock, always connect the protective earth (PE) terminal (term i nal marked ) of the servo amplifier to
the protective earth (PE) of the control box.
2. Connect the diode in the correct direction. If it is connected reversely, the servo amplifier will be faulty and will not output
signals, disabling the emergency stop (EMG) and other protective circ uits.
3. The emergency stop switch (normally closed contact) must be installed.
4. CN1A, CN1B, CN2 and CN3 have the same shape. Wrong connection of the connectors will lead to a fault.
5. The sum of currents that flow in the external relays should be 80mA max. If it exceeds 80mA, externally supply 24VDC
200mA power for the interface. 200mA is a value applicable when all I/O signals are used. Reducing the number of I/O points
decreases the current capacity. Refer to the current necessary for the interf ace desc ri bed in Section 3.6.2. Connect the external
24VDC power supply if the output signals are not used.
6. When starting operation, always turn on emergency stop (EMG) and Forward/Reverse rotation stroke end (LSP/LSN).
(Normally closed contacts)
7. Trouble (ALM) turns on in normal alarm-free condition. When this signal is switched off (at occurrence of an alarm), the output
of the programmable controller should be stopped by the sequence program.
8. When connecting the personal computer together with analog monitor 1 (MO1) and analog monitor 2 (MO2) on the 7kW or less
servo amplifier, use the maintenance junction card (MR-J2CN3TM). (Refer to Secti on 13.1. 5.).
9. The pins with the same signal name are connected in the servo amplifier.
10. This length applies to the command pulse train input in the opencollector system. It is 10m (32ft) or less in the differential line
driver system.
11. Use MRZJW3-SETUP 151E.
12. When using the internal power supply (VDD), always connect VDD-COM. Do not connect them when supplying external
power. Refer to Section 3.6.2.
13. Connect to CN1A-10 when using the junction terminal block (MR-TB20).
14. For the 11kW or more servo amplifier, analog monitor 1 (MO1) and analog monitor 2 (MO2) are replaced by CN4.
(Note 8)
Analog monitor
Max. 1mA
Reading in both
directions
3 - 4
(Note 1)
3. SIGNALS AND WIRING
Note 1. To prevent an electric shock, always connect the protective earth (PE) terminal (term i nal marked ) of the servo amplifier to
the protective earth (PE) of the control box.
2. Connect the diode in the correct direction. If it is connected reversely, the servo amplifier will be faulty and will not output
signals, disabling the emergency stop (EMG) and other protective circ uits.
3. The emergency stop switch (normally closed contact) must be installed.
4. CN1A, CN1B, CN2 and CN3 have the same shape. Wrong connection of the connectors will lead to a fault.
5. The sum of currents that flow in the external relays should be 80mA max. If it exceeds 80mA, externally supply 24VDC
200mA power for the interface. 200mA is a value applicable when all I/O signals are used. Reducing the number of I/O points
decreases the current capacity. Refer to the current necessary for the interf ace des cri bed in Section 3.6.2. Connect the external
24VDC power supply if the output signals are not used.
6. When starting operation, always turn on emergency stop (EMG) and forward/reverse rotati on stroke end (LSP/LSN). (Normally
closed contacts)
7. Trouble (ALM) turns on in normal alarm-free condition. When this signal is switched off (at occurrence of an alarm), the output
of the controller should be stopped by the sequence program.
8. When connecting the personal computer together with analog monitor 1 (MO1) and analog monitor 2 (MO2) on the 7kW or less
servo amplifier, use the maintenance junction card (MR-J2CN3TM). (Refer to Secti on 13.1. 5)
9. The pins with the same signal name are connected in the servo amplifier.
10. This length applies to the command pulse train input in the differential line driver system.
It is 2m (6.5ft) or less in the opencollector system.
11. Use MRZJW3-SETUP 151E.
12. When using the internal power supply (VDD), always connect VDD-COM. Do not connect them when supplying external
power. Refer to Section 3.6.2.
13. This connection is not required for the AD75P. Depending on the used positioning module, however, it is recommended to
connect the LG and control common terminals of the servo amplifier to enhance noise immunity.
14. For the 11kW or more servo amplifier, Analog monitor 1 (MO1) and Analog monitor 2 (MO2) are replaced by CN4.
(Note 11)
MR Configurator
(Servo conf i gu r at i on
software)
10V/rated speed
Upper limit setting
(Note 10) Analog torque limit
10V/max. torque
Personal
computer
10m(32ft) max.
2m(6.5ft) max.
(Note 8)
Communication cable
Servo amplifier
(Note 4,9)
CN1A
SP1
8
10
SG
(Note 4,9) (Note 4,9)
CN1B
EMG
15
SON
5
RES
14
7SP2
ST1
8
ST2
9
LSP
16
LSN
17
SG
10
P15R
11
2
VC
LG
1
12TLA
Plate
SD
(Note 4,9)
CN3
(Note 4)
CN1B
3VDD
13
18
19 ZSP
6TLC
CN1A
9COM
18 SA
19
5
15
6
16
7
17
1
14
4
Plate
(Note 4,9,14)
CN3
4
3
14
13
Plate
COM
ALM
RD
LZ
LZR
LA
LAR
LB
LBR
LG
OP
P15R
SD
2m(6.5ft) or less
MO1
LG
MO2
LG
SD
(Note 2,5)
10m(32ft) or less
2m(6.5ft) max.
(Note 12)
RA1
RA2
RA3
RA5
RA4
Control common
Control common
Encoder Z-phase pulse
(open collector)
A
10k
A
10k
(Note 7)
Trouble
Zero speed
Limiting torque
Speed reached
Ready
Encoder Z-phase pulse
(differential line driver)
Encoder A-phase pulse
(differential line driver)
Encoder B-phase pulse
(differential line driver)
(Note 8)
Analog monitor
Max. 1mA
Reading in
both directions
3 - 6
(Note 1)
3. SIGNALS AND WIRING
Note 1. To prevent an electric shock, always connect the protective earth (PE) terminal (term i nal marked ) of the servo amplifier to
the protective earth (PE) of the control box.
2. Connect the diode in the correct direction. If it is connected reversely, the servo amplifier will be faulty and will not output
signals, disabling the emergency stop (EMG) and other protective circ uits.
3. The emergency stop switch (normally closed contact) must be installed.
4. CN1A, CN1B, CN2 and CN3 have the same shape. Wrong connection of the connectors will lead to a fault.
5. The sum of currents that flow in the external relays should be 80mA max. If it exceeds 80mA, externally supply 24VDC 10%,
200mA power for the interface. 200mA is a value applicable when all I/O signals are used. Reducing the number of I/O points
decreases the current capacity. Refer to the current necessary for the interf ace desc ri bed in Section 3.6.2. Connect the external
24VDC power supply if the output signals are not used.
6. When starting operation, always turn on emergency stop (EMG) and forward/reverse rotati on stroke end (LSP/LSN). (Normally
closed contacts)
7. Trouble (ALM) turns on in normal alarm-free condition.
8. When connecting the personal computer together with Analog monitor 1 (MO1) and analog monitor 2 (MO2) on the 7kW or less
servo amplifier, use the maintenance junction card (MR-J2CN3TM). (Refer to Secti on 13.1. 5)
9. The pins with the same signal name are connected in the servo amplifier.
10. By setting parameters No.43 to 48 to make TL available, TLA can be used.
11. Use MRZJW3-SETUP 151E.
12. When using the internal power supply (VDD), always connect VDD-COM. Do not connect them when supplying external
power. Refer to Section 3.6.2.
13. Use an external power supply when inputting a negative voltage.
14. For the 11kW or more servo amplifier, analog monitor 1 (MO1) and analog monitor 2 (MO2) are replaced by CN4.
(Note 7)
Analog monitor
Max. 1mA
Reading in both
directions
3 - 8
(Note 1)
3. SIGNALS AND WIRING
Note 1. To prevent an electric shock, always connect the protective earth (PE) terminal of the (terminal m arked ) servo amplifier to
the protective earth (PE) of the control box.
2. Connect the diode in the correct direction. If it is connected reversely, the servo amplifier will be faulty and will not output
signals, disabling the emergency stop (EMG) and other protective circ uits.
3. The emergency stop switch(normally closed contact) must be installed.
4. CN1A, CN1B, CN2 and CN3 have the same shape. Wrong connection of the connectors will lead to a fault.
5. The sum of currents that flow in the external relays should be 80mA max. If it exceeds 80mA, externally supply 24VDC 10%,
200mA power for the interface. 200mA is a value applicable when all I/O signals are used. Reducing the number of I/O points
decreases the current capacity. Refer to the current necessary for the interf ace desc ri bed in Section 3.6.2. Connect the external
24VDC power supply if the output signals are not used.
6. Trouble (ALM) turns on in normal alarm-free condition.
7. When connecting the personal computer together with analog monitor 1 (MO1) and analog monitor 2 (MO2) on the 7kW or less
servo amplifier, use the maintenance junction card (MR-J2CN3TM). (Refer to Secti on 13.1. 5)
8. The pins with the same signal name are connected in the servo amplifier.
9. Use MRZJW3-SETUP 121E.
10. When using the internal power supply (VDD), always connect VDD-COM. Do not connect them when supplying external
power. Refer to Section 3.6.2.
11. Use an external power supply when inputting a negative voltage.
12. For the 11kW or more servo amplifier, analog monitor 1 (MO1) and analog monitor 2 (MO2) are replaced by CN4.
CN4
MO1
1
MO2
2
A
A
LG
4
2m (6.5ft) or less
3 - 9
3. SIGNALS AND WIRING
3.2 Internal connection diagram of servo amplifier
The following is the internal connection diagram where the signal assignment has been made in the
initial status in each control mode.
Servo amplifier
VDD
COM
(Note1)
PS
COM COM COM9
CRSP1 SP1
SGSGSG810,20
(Note1)
PST
SON SON SON
PCST1RS2
TLST2RS1
RES
EMG
LSP
LSN
SG
(Note1)
PST
OPC
PG
PP
NG
NP
SD
(Note1)
PST
TLATC12
P15R
P15R
LG
LG
SD
SD
TCN1A
SP2 SP257
RES RES
EMG EMG
LSP
LSN
SGSG
SDSD
VCVLA2
TLA
TLA
P15R
P15R
LG
LG
SD
SD
CN1B
3
13
CN1B
8
9
14
15
16
17
10,20
CN1A
11
13
Approx. 100k
3
12
Approx. 100kApprox. 1.2k
2
Case
CN1B
11
1
Case
CN1A
4P15R
DC24V
DC 15V
Approx. 4.7k
Approx. 4.7k
Approx. 4.7k
Approx. 4.7k
Approx. 4.7k
Approx. 4.7k
Approx. 4.7k
Approx. 4.7k
Approx. 4.7k
Approx. 1.2k
(Note1)
CN1A
INPSA18
RDRDRD19
(Note1)
CN1B
TLC TLC VLC6
ALM ALM ALM18
ZSP ZSP ZSP19
DO14
CN1A
6
LAR
16
7
LBR
17
5
LZR
15
OP
14
1LG
CN3
4MO1
142MO2
RXD
TXD
12
9SDP
19SDN
5RDP
15RDN
PE
PST
PST
DO1 DO1
LA
LB
LZ
(Note2)
Note1. P: Position control mode, S: Speed control mode, T: Torque control mode
2. For the 11kW or more servo amplifier, MO1 is replaced by CN4-1 and MO2 by CN4-2.
3 - 10
3. SIGNALS AND WIRING
3.3 I/O signals
3.3.1 Connectors and signal arrangements
POINT
The pin configurations of the connectors are as viewed from the cable
connector wiring section.
Refer to the next page for CN1A and CN1B signal assignment.
(1) MR-J2S-700A or less
CN1ACN1B
1
2
3
4
5
6
7
8
9
10
CN2CN3
1
2
LG
LG
3
4
5
6
MD
7
8
MR
9
10
BAT
12
14
16
18
20
12
LG
14
16
MDR
18
P5
20
P5
11
13
15
17
19
11
LG
13
15
17
MRR
19
P5
MITSUBISHI
MELSERVO-J2
The connector frames are
connected with the PE (earth)
terminal inside the servo amplifier.
2
4
6
8
10
2
RXD
4
MO1
6
8
10
TRE
1
3
5
7
9
1
LG
3
LG
5
RDP
7
9
SDP
12
14
16
18
20
12
TXD
14
MO2
16
18
20
P5
11
13
15
17
19
11
LG
13
LG
15
RDN
17
19
SDN
3 - 11
3. SIGNALS AND WIRING
(2) MR-J2S-11KA or more
CN3
CN1A
Same as the one of the
MR-J2S-700A or less.
CN1B
Same as the one of the
MR-J2S-700A or less.
CN2
1
2
LG
LG
3
4
12
LG
14
11
LG
13
CHARGE
CN4
MITSUBISHI
1
2
1
MO1
2
MO2
4
LG
RXD
4
LG
3
5
6
7
8
9
10
SDP
TRE
12
TXD
14
16
18
20
P5
11
LG
13
15
RDNRDP
17
19
SDN
CON2
For maker adjustment.
Keep this open.
6
MD
8
10
5
7
MR
9
BAT
16
MDR
18
P5
20
P5
15
17
MRR
19
P5
The connector frames are
connected with the PE (earth)
terminal inside the servo amplifier.
3 - 12
3. SIGNALS AND WIRING
(3) CN1A and CN1B si gn al assig n men t
The signal assignment of connector changes with the control mode as indicated below;
For the pins which are given parameter No.s in the related parameter column, their signals can be
changed using those parameters.
4ODO1DO1DO1DO1DO1DO1
5ISONSONSONSONSONSONNo.43 to 48
6OTLCTLCTLCTLC/VLCVLCVLC/TLCNo.49
7ILOPSP2LOPSP2LOPNo.43 to 48
8IP CPC/ST1ST1ST1/RS2RS2RS2/PCNo.43 to 48
9ITLTL/ST2ST2ST2/RS1RS1RS1/TLNo.43 to 48
2. P : Position control mode, S: Speed control mode, T: Torque control mode, P/S: Position/speed control change mode,
S/T: Speed/torque control change mode, T/P: Torque/position control change mode
3. By setting parameters No. 43 to 48 to make TL available, TLA can be used.
4. CN1B-4 and CN1A-18 output signals are the same. However, this pin may not be used when assigning alarm codes to
CN1A-18.
I/O Signals in control modes
(Note3)
TLA
(Note3)
TLA/TC
/NP
/PP
TCTC/TLA
Related
parameter
3 - 13
3. SIGNALS AND WIRING
(4) Symbols and sig na l na mes
SymbolSignal nameSymbolSignal name
SONServo-onVLCLimiting speed
LSPForward rotation stroke endRDReady
LSNReverse rotation stroke endZSPZero speed
CRClearINPIn position
SP1Speed selection 1SASpeed reached
SP2Speed selection 2ALMTrouble
PCProportion controlWNGWarning
ST1Forward rotation startBWNGBattery warning
ST2Reverse rotation startOPEncoder Z-phase pulse (open collector)
TLTorque limit selectionMBRElectromagnetic brake interlock
RESResetLZ
EMGEmergency stopLZR
LOPControl changeLA
VCAnalog speed commandLAR
VLAAnalog speed limitLB
TLAAnalog torque limitLBR
TCAnalog torque commandVDDI/F internal power supply
RS1Forward rotati on selectionCOMDigital I/F power supply input
RS2Reverse rotation selectionOPCOpen collector power input
PPSGDigital I/F common
NPP15R15VDC power supply
PGLGControl common
NG
TLCLimiting torque
Forward/reverse rotation pulse train
SDShield
Encoder Z-phase pulse
(differential line driver)
Encoder A-phase pulse
(differential line driver)
Encoder B-phase pulse
(differential line driver)
3 - 14
3. SIGNALS AND WIRING
3.3.2 Signal explanations
For the I/O interfaces (symbols in I/O division column in the table), refer to Section 3.6.2.
In the control mode field of the table
P : Position control mode, S: Speed control mode, T: Torque control mode
: Denotes that the signal may be used in the initial setting status.
: Denotes th a t th e signal may be u se d by se t ting the corre spo n d in g pa r ameter among parameters 43 to
49.
The pin No.s in the connector pin No. column are those in the initial status.
(1) Input si gn al s
Connec-
SignalSymbol
Servo-onSONCN1B5Turn SON on to power on the base circuit and make the servo
ResetRESCN1B14Turn RES on for more than 50ms to reset the alarm.
Forward rotation
stroke end
Reverse rotation
stroke end
LSPCN1B
LSNCN1B
tor pin
No.
16
17
Functions/Applications
amplifier ready to operate (servo-on).
Turn it off to shut off the base circuit and coast the servo motor
(servo off).
Set "
1" in parameter No. 41 to swit ch thi s signa l on
(keep te rminals connected) automatically in th e servo
amplifier.
Some alarms cannot be deactivated by the reset signal. Refer to
Section 10.2.
Turning RES on in an alarm-free status shuts off the base circuit.
The base circuit is not shut off when "
No. 51.
To start operation, turn LSP/LSN on. Turn it off to bring the
motor to a sudden stop and make it servo-locked.
Set "
1" in parameter No. 22 to make a slow stop.
(Refer to Section 5.2.3.)
(Note) Input signalsOperation
LSPLSN
11
01
10
00
Note. 0: off
1: on
Set parameter No. 41 as indicated below to switch on the signals
(keep terminals connected) automatically in the servo amplifier:
TLCN1B9Turn TL off to make Internal torque limit 1 (parameter No. 28)
valid, or turn it on to make Analog torque limit (TLA) valid.
For details, refer to (5), Section 3.4.1.
TL1When using this signal, make it usable by making the setting of
parameter No. 43 to 48.
For details, refer to (5), Section 3.4.1.
ST1CN1B
ST2CN1B
RS1CN1B
RS2CN1B
Used to start the servo motor in any of the following directions:
8
9
9
8
(Note) Input signals
ST2ST1
00Stop (servo lock)
01CCW
10CW
11Stop (servo lock)
Note. 0: off
1: on
If both ST1 and ST2 are switched on or off during operation, the
servo motor will be decelerated to a stop according to the
parameter No. 12 setting and servo-locked.
Used to select any of the following servo motor torque generation
directions:
(Note) Input signals
RS2RS1
00Torque is not generated.
01
10
11Torque is not generated.
Note. 0: off
1: on
Functions/Applications
Servo motor starting direction
Torque generation direction
Forward rotation in driving mode /
reverse rotation in regenerative mode
Reverse rotation in driving mode /
forward rotation in regenerative mode
I/O
division
DI-1
DI-1
DI-1
DI-1
Control
mode
PST
3 - 16
3. SIGNALS AND WIRING
SignalSymbol
Speed selection 1SP1CN1A8<Speed control mode >
Speed selection 2SP2CN1B
Speed selection 3SP3
Connec-
tor pin
No.
7
Used to select the command sp e ed f or op era t ion.
When using SP3, make it usable by making the setting of
parameter No. 43 to 48.
Setting of
parameter
No. 43 to 48
When speed
selection
(SP3) is not
used
(initial status)
When speed
selection
(SP3) is made
valid
Note. 0: off
1: on
<Torque control mode>
Used to select the limit speed for operation.
When using SP3, make it usable by making the setting of
parameter No. 43 to 48.
Setting of
parameter
No. 43 to 48
When speed
selection
(SP3) is not
used
(initial status)
When speed
selection
(SP3) is made
valid
Note. 0: off
1: on
SP3 SP2 SP1
000Analog speed command (VC)
001
010
011
100
101
110
111
SP3 SP2 SP1
000Analog speed limit (VLA)
001
010
011
100
101
110
111
Functions/Applications
(Note) Input
signals
00Analog speed command (VC)
01
10
11
(Note) Input
signals
00Analog speed limit (VLA)
01
10
11
Speed command
Internal speed command 1
(parameter No. 8)
Internal speed command 2
(parameter No. 9)
Internal speed command 3
(parameter No. 10)
Internal speed command 1
(parameter No. 8)
Internal speed command 2
(parameter No. 9)
Internal speed command 3
(parameter No.10)
Internal speed command 4
(parameter No. 72)
Internal speed command 5
(parameter No. 73)
Internal speed command 6
(parameter No. 74)
Internal speed command 7
(parameter No. 75)
Speed limit
Internal speed command 1
(parameter No. 8)
Internal speed command 2
(parameter No. 9)
Internal speed command 3
(parameter No. 10)
Internal speed command 1
(parameter No. 8)
Internal speed command 2
(parameter No. 9)
Internal speed command 3
(parameter No.10)
Internal speed command 4
(parameter No. 72)
Internal speed command 5
(parameter No. 73)
Internal speed command 6
(parameter No. 74)
Internal speed command 7
(parameter No. 75)
I/O
division
DI-1
DI-1
DI-1
Control
mode
PST
3 - 17
3. SIGNALS AND WIRING
Connec-
SignalSymbol
Proportion
control
Emergency stopEMGCN1B15Turn EMG off (open EMG-common) to bring the motor to an
ClearCRCN1A8Turn CR on to clear the position control counter droop pulses on
Electronic gear
selection 1
Electronic gear
selection 2
Gain changingCDPWhen using this signal, make it usable by the setting of
PCCN1B8Connect PC-SG to switch the speed amplifier from the
CM1When using CM1 and CM2, make them usable by the setting of
CM2
tor pin
No.
Functions/Applications
proportional integral type to the proportional type.
If the servo motor at a stop is rotated even one pulse due to any
external factor, it generates torque to compensate for a position
shift. When the servo motor shaft is to be locked mechanically
after positioning completion (stop), switching on the proportion
control (PC) upon positioning completion will suppress the
unnecessary torque generated to compensate for a position shift.
When the shaft is to be locked for a long time, switch on the
proportion con trol (PC) and torque control (TL) at the same time
to make the torque less than the rated by the analog torque limit.
emergency stop state, in which the base circuit is shut off and the
dynamic brake is operated.
Turn EMG on (short EMG-common) in the emerge ncy stop state
to reset that state.
its leading edge. The pulse width should be 10ms or more.
When the p arameter No . 42 setti ng is "
always cleared while CR is on.
parameters No. 43 to 48.
The combination of CM1 and CM2 gives you a choice of four
different electronic gear numerators set in the parameters.
CM1 and CM2 cannot be used in the absolute position detection
system.
parameter No. 43 to 48.
Turn CDP on to change the load inertia moment ratio into the
parameter No. 61 s etting an d the gain values into the values
multiplied by the parameter No. 62 to 64 settings.
TLATo use this signal in the speed control mode, set any of
TC
VCApply 0 to 10VDC across VC-LG. Speed set in parameter No. 25
VLA
PP
NP
PG
NG
tor pin
No.
7
CN1B
12
CN1B
2
CN1A
3
CN1A
2
CN1A
13
CN1A
12
Functions/Applications
<Position/speed control change mode>
Used to select the control mode in the position/speed control
change mode.
(Note) LOPControl mode
0Position
1Speed
Note. 0: off
1: on
<Speed/torque control change mode>
Used to select the control mode in the speed/torque control change
mode.
(Note) LOPControl mode
0Speed
1Torque
Note. 0: off
1: on
<Torque/position control mode>
Used to select the control mode in the torque/position control
change mode.
(Note) LOPControl mode
0Torque
1Position
Note. 0: off
1: on
parameters No. 43 to 48 to make TL available.
When the analog torque limit (TLA) is valid, torque is limited in
the full servo motor output torque range. Apply 0 to
across TLA-LG. Connect the positive terminal of the power supply
to TLA. Maximum torque is generated at
Section 3.4.1.) Resolution:10bit
Used to control torque in the full servo motor output torque
range.
Apply 0 to
at
8V. (Refer to (1) in Section 3.4.3.)
The torque at
is provided at
Resolution:14bit or equivalent
Apply 0 to 10VDC across VLA-LG. Speed set in parameter No.
25 is provided at
Used to enter a command puls e t ra i n.
In the open collector system (max. input frequency 200kpps):
Forward rotation pulse train across PP-SG
Reverse rotation pulse train across NP-SG
In the differential receiver system (max. input frequency
500kpps):
Forward rotation pulse train across PG-PP
Reverse rotation pulse train across NG-NP
The command pulse train f o rm ca n b e cha nged using
parameter No. 21.
8VDC across TC-LG. Maximum torque is generated
8V input can be changed using parameter No. 26.
10V. (Refer to (1) in Section 3.4.2.)
10V (Refer to (3) in Section 3.4.3.).
10V. (Refer to (5) in
10VDC
I/O
division
DI-1
Analog
input
Analog
input
Analog
input
Analog
input
DI-2
Control
mode
PST
Refer to
Functions/
Appli-
cations.
3 - 19
3. SIGNALS AND WIRING
(2) Output signals
Connec-
SignalSymbol
TroubleALMCN1B18ALM turns off when power is switched off or the protective circuit
Dynamic brake
interlock
ReadyRDCN1A19RD turns on when the servo is switched on and the servo
In positionINPINP turns on when the number of droop pulses is in the preset in-
Speed reach edS A
Limiting speedVLCVLC turns on when speed reaches the value limited using any of
Limiting torqueTLC
Zero speedZSPCN1B19ZSP turns on when the servo motor speed is zero speed (50r/min)
Electromagnetic
brake interlock
WarningWNGTo use this signal, assign the connector pin for output using
Battery warningBWNGTo use this signal, assign the connector pin for output using
DBThis signal can be used with the 11kW or more servo amplifier.
MBRCN1B19Set " 1 " in parameter No. 1 to use this parameter. Note that
tor pin
No.
CN1A
18
CN1B
6
Functions/Applications
is activated to shut off the base circuit.
Without alarm occurring, ALM turns on within about 1s after
power-on.
When using this signal, set "
When the dynamic brake is operated, DB turns off. (Refer to
Section 13.1.4.)
amplifier is ready to operate.
position range. The in-position range can be changed using
parameter No. 5.
When the in-position range is increased, INP-SG may be kept
connected during low-speed rotation.
SA turns off when servo on (SON) turns off or the servomotor
speed has not reached th e preset speed with both forw ard rotation
start (ST1) and reverse rotation start (ST2) turned off. SA turns
on when the servomotor speed has nearly reached the preset
speed. When the preset spee d is 20r/min or les s, SA always turns
on.
the internal speed limits 1 to 7 (parameter No. 8 to 10, 72 to 75)
or the analog speed limit (VLA) in the torque control mode.
VLC turns off when servo on (SON) turns off.
TLC turns on when the torque generated reaches the value set to
the internal torque limit 1 (parameter No. 28) or analog torque
limit (TLA).
or less. Zero speed can be changed using parameter No. 24.
ZSP will be unusable.
MBR turns off when the servo is switched off or an alarm occurs.
parameter No.49. The old signal before assignment will be
unusable.
When warning has occurred, WNG turns on.
When there is no warning, WNG turns off within about 1s after
power-on.
parameter No.49. The old signal before assignment will be
unusable.
BWNG turns on when battery cable breakage warning (AL. 92) or
battery warning (AL. 9F) has occurred.
When there is no battery warning, BWNG turns off within about
1s after power-on.
1 " in parameter No. 1.
I/O
division
DO-1
DO-1
DO-1
DO-1
DO-1
DO-1
DO-1
DO-1
DO-1
DO-1
DO-1
Control
mode
PST
3 - 20
3. SIGNALS AND WIRING
SignalSymbol
Alarm codeACD 0
ACD 1
ACD 2
Connec-
tor pin
No.
CN1A
19
CN1A
18
CN1B
19
Functions/Applications
To use this signal, set " 1" in parameter No.49.
This signal is output when an alarm occurs. When there is no
alarm, respective ordinary signals (RD, INP, SA, ZSP) are output.
Alarm codes and alarm names are listed below:
Encoder A-phase
pulse
(Differential line
driver)
Encoder B-phase
pulse
(Differential line
driver)
Encoder Z-phase
pulse
(Differential line
driver)
Analog monitor 1MO1CN34CN41Used to output the data set in parameter No.17 to across
Analog monitor 2MO2CN314CN42Used to output the data set in parameter No.17 to across
7kW or
OPCN1A14CN1A14Outputs the zero-point sign al of the en code r. One pulse is
LA
CN1A
LB
LZ
CN1A
CN1A
CN1A
CN1A
CN1A
LAR
LBR
LZR
less
6
16
7
17
5
15
11kW or
more
CN1A
6
CN1A
16
CN1A
7
CN1A
17
CN1A
5
CN1A
15
output per servo motor revolution. OP turns on when the
zero-point position is reached. (Negative logic)
The minimum pulse width is about 400
position return using this pulse, set the creep speed to
100r/min. or less.
Outputs pulses per servo motor revolution set in
parameter No. 27 in the differential line driver system.
In CCW rotation of the servo motor, the encoder B-phase
pulse lags the encoder A-phase pulse by a phase angle of
/2.
The relationships between rotation direction and phase
difference of the A- and B-phase pulses can be changed
using parameter No. 54.
The same signal as OP is output in the differential line
driver system.
MO1-LG in terms of voltage. Resolution 10 bits
MO2-LG in terms of voltage. Resolution 10 bits
Functions/Applications
s. For home
I/O
division
DO-2
DO-2
DO-2
Analog
output
Analog
output
Control
mode
PST
(3) Communication
SignalSymbol
RS-422 I/FSDP
SDN
RDP
RDN
RS-422
termination
RS-232C I/FRXD
TRECN310Termination resistor connection terminal of RS-422 interface.
TXD
POINT
Refer to Chapter 14 for the communication function.
Connec-
tor pin
No.
CN3
9
CN3
19
CN3
5
CN3
15
CN3
2
CN3
12
RS-422 and RS-232C functions cannot be used together.
Choose either one in parameter No. 16.
When the servo amplifier is the termination axis, connect this
terminal to RDN (CN3-15).
RS-422 and RS-232C functions cannot be used together.
Choose either one in parameter No. 16.
Functions/Applications
I/O
division
Control
mode
PST
3 - 22
3. SIGNALS AND WIRING
(4) Power supply
Connector pin No.
SignalSymbol
I/F internal
power supply
Digital I/F power
supply input
Open collector
power input
Digital I/F
common
15VDC power
supply
Control commonLGCN1A
ShieldSDPlatePlateConnect the external conductor of the shield cable.
VDDCN1B3CN1B3Used to output 24V 10% to across VDD-SG.
COMCN1A
P15RCN1A
7kW or
CN1B
OPCCN1A11CN1A11When inputting a pulse train in the open collector
SGCN1A
CN1B
CN1B
CN1B
less
9
13
10
20
10
20
4
11
1
1
CN3
1, 11
3, 13
11kW or
more
CN1A
9
CN1B
13
CN1A
10
20
CN1B
10
20
CN1A
4
CN1B
11
CN1A
1
CN1B
1
CN3
1, 11
3, 13
CN4
4
When using this power supply for digital interface,
connect it with COM.
Permissible current : 80mA
Used to input 24VDC for input interface.
Connect the positive terminal of the 24VDC external
power supply.
24VDC
system, supply this terminal with the positive (
of 24VDC.
Common terminal for input signals such as SON and
EMG. Pins are connected internally.
Separated from LG.
Outputs 15VDC to across P15R-LG. Available as power
for TC, TLA, VC, VLA.
Permissible current: 30mA
Commo n te rm in al f or TL A, T C, VC, V LA, F PA, F PB, OP
,MO1, MO2 and P15R.
Pins are connecte d internally.
10%
Functions/ApplicationsI/O division
Control
mode
PST
) power
3 - 23
3. SIGNALS AND WIRING
3.4 Detailed description of the signals
3.4.1 Position control mode
(1) Pulse trai n inpu t
(a) Input pulse waveform selection
Command pulses may be input in any of three different forms, for which positive or negative logic
can be chosen. Set the command pulse train form in parameter No. 21.
Arrow
A- and B-phase pulse trains are imported after they have been multi plied b y 4.
or in the table indicates the timing of importing a pulse train.
The explanation assumes that the input waveform has b een set to the negati ve logi c and forward
and reverse rotation pulse trains (parameter No.21 has been set to 0010). The waveforms in the
table in (a), (1) of this section are voltage waveforms of PP and NP based on SG. Their
relationships with transistor ON/OFF are as follows:
Forward rotation
pulse train
(transistor)
Reverse rotation
pulse train
(transistor)
Servo amplifier
VDD
OPC
Approx.
PP
NP
SG
SD
(ON)(OFF)
Forward rotation commandReverse rotation command
(ON)(OFF)
(OFF)
1.2k
Approx.
1.2k
(OFF)
(ON) (OFF) (ON) (OFF) (ON)
3 - 25
3. SIGNALS AND WIRING
2) Differential line driver system
Connect as shown below:
The explanation assumes that the input waveform has been set t o the negative l ogic and forward
and reverse rotation pulse trains (parameter No.21 has been set t o 0010 ).
For the differential line driver, the waveforms in the table in (a), (1) of this section are as follows.
The waveforms of PP, PG, NP and NG are based on that of the ground of the differential line
driver.
Servo amplifier
PP
PG
NP
NG
SD
Forward rotation
pulse train
PP
PG
Reverse rotation
pulse train
NP
NG
Forward rotation commandReverse rotation command
3 - 26
3. SIGNALS AND WIRING
(2) In-position (INP)
PF-SG are connected when the number of droop pulses in the deviation counter falls within the preset
in-position range (parameter No. 5). INP-SG may remain connected when low-speed operation is
performed with a large value set as the in-position range.
Servo-on (SON)
ON
OFF
Alarm
Droop pulses
In position (INP)
Yes
No
In-position range
ON
OFF
(3) Ready (RD)
Servo-on (SON)
Alarm
Ready (RD)
ON
OFF
Yes
No
ON
OFF
80ms or less10ms or less10ms or less
(4) Electronic gear switching
The combination of CM1 and CM2 gives you a choice of four different electronic gear numerators set in
the parameters.
As soon as CM1/CM2 is turned ON or OFF, the molecule of the electronic gear changes. Therefore, if
any shock occurs at this change, use position smoothing (parameter No. 7) to relieve shock.
If the torque limit is canceled during servo lock, the servomotor may suddenly
rotate according to position deviation in respect to the command position.
(a) Torque limit and torque
By setting param eter No. 28 (intern al torque limit 1), to rque is always limi ted to the maximum
value during operation. A relationship between the limit value and servo motor torque is shown
below.
Max. torque
torque
0
0100
Torque limit value [%]
A relationship between the applied voltage of the analog torque limit (TLA) and the torque limit
value of the servo motor is shown below. Torque limit values will vary about 5% relative to the
voltage depending on products.
At the voltage of less than 0.05V, torque may vary as it may not be limited sufficiently. Therefore,
use this function at the voltage of 0.05V or more.
100
Servo amplifier
TL
5%
Torque limit value [%]
0
0.05
010
TLA application voltage [V]
TLA application voltage vs.
torque limit value
2k
Japan resistor
RRS10 or equivalent
2k
SG
P15R
TLA
LG
SD
(b) Torque limit value selection
Choose the torque limit made valid by the internal torque limit value 1 (parameter No. 28) using
the external torque limi t selection (T L) or the tor que limit mad e valid by the analog to rque limit
(TLA) as indicated below.
When internal torque limit selection (TL1) is made usable by parameter No. 43 to 48, internal
torque limit 2 (paramete r No. 76) can be selected. However, if the p arameter No. 28 v alue is less
than the limit value selected by TL/TL1, the parameter No. 28 value is made valid.
(Note) External input signals
TL1TL
00Internal torque limit value 1 (parameter No. 28)
01
TLC turns on when the servo motor torque reaches the torque limited using the internal torque
limit 1
2 or analog torque limit.
3 - 28
3. SIGNALS AND WIRING
3.4.2 Speed control mode
(1) Speed setting
(a) Speed command and speed
The servo motor is run at the speeds set in the parameters or at the speed set in the applied
voltage of the analog speed command (VC). A relationship between the analog speed command
(VC) applied voltage and the servo motor speed is shown below:
The maximum speed is achieved at
25.
10V. The speed at 10V can be changed u sing parame ter No.
Speed [r/min]
CW direction
Rated speed [r/min]
CCW direction
10
010
VC applied voltage [V]
Rated speed
Forward rotation (CCW)
Reverse rotation (CW)
The following ta ble indicates the rota tion direction accor ding to forward rotation start ( ST1) and
reverse rotation start (ST2) combination:
(Note 1) External input signals(Note 2) Rotation direction
ST2ST1
00
01CCWCWCCW
10CW
11
Note 1. 0: off
1: on
2. If the torque limit is canceled during servo lock, the servomotor may suddenly rotate according t o posi tion devi ation i n
respect to the command position.
Polarity0VPolarity
Stop
(Servo lock)
Stop
(Servo lock)
Analog speed command (VC)
Stop
(Servo lock)
Stop
(No servo lock)
Stop
(Servo lock)
Stop
(Servo lock)
CCWCW
Stop
(Servo lock)
Internal speed
commands
(Servo lock)
(Servo lock)
Stop
Stop
The forward rotation start (ST1) and reverse rotation start (ST2) can be assigned to any pins of
the connector CN1A, CN1B using parameters No. 43 to 48.
Generally, make connection as shown below:
Servo amplifier
ST1
ST2
SG
2k
Japan resistor
RRS10 or equivalent
2k
P15R
VC
LG
SD
3 - 29
3. SIGNALS AND WIRING
(b) Speed selection 1 (SP1), speed selection 2 (SP2) and speed command value
Choose any of the speed settings made by the internal speed commands 1 to 3 using speed selection
1 (SP1) and speed selection 2 (SP2) or the speed setting made by the analog speed command (VC).
By making speed selection 3 (SP3) usable by setting of parameter No. 43 to 48, you can choose
the speed command values of analog speed command (VC) and internal speed commands 1 to 7.
(Note) External input signals
SP3SP2SP1
000Analog spee d com mand (VC)
001Internal speed command 1 (parame t er No. 8)
010Internal speed command 2 (parame t er No. 9)
011Internal speed command 3 (parame t er No. 10)
100Internal speed command 4 (parame t er No. 72)
101Internal speed command 5 (parame t er No. 73)
110Internal speed command 6 (parame t er No. 74)
111Internal speed command 7 (parame t er No. 75)
Note. 0: off
1: on
Speed command value
Speed command value
The speed may be ch anged during rotation. In this case, the value s set in par ameters No. 11 and
12 are used for acceleration/deceleration.
When the speed has been specified under any internal speed command, it does not vary due to the
ambient temperature.
(2) Speed reached (SA)
SA turns on when the servo motor speed has nearly reached the speed set to the internal speed
command or analog speed command.
Internal speed
Set speed selection
Start (ST1,ST2)
Servo motor speed
Speed reached (SA)
Internal speed
command 1
ON
OFF
ON
OFF
command 2
(3) Torque limit
As in Section 3.4.1 (5).
3 - 30
3. SIGNALS AND WIRING
3.4.3 Torque control mode
(1) Torque control
(a) Torque command and torque
A relationship between the applied voltage of the analog torque command (TC) and the torque by
the servo motor is shown below.
The maximum torque is generated at
parameter No. 26.
8V. Note th at the to rqu e a t 8V input can be cha nge d wi th
Max. torque
Generated torque
8
0.05
CW direction
CCW direction
0.05 8
TC applied voltage [V]
Max. torque (Note)
Forward rotation (CCW)
Reverse rotation (CW)
Generated torque limit values will vary about 5% relative to the voltage depending on products.
Also the torque may vary if the voltage is low (
0.05 to 0.05V) and the actual speed is close to
the limit value. In such a case, increase the speed limit value.
The following table indicates the torque generation directions determined by the forward rotation
selection (RS1) and reverse rotation selection (RS2) when the analog torque command (TC) is used.
(Note) External input signalsRotation direction
RS2RS1
00Torque is not generated.Torque is not generated.
CCW (reverse rotation in
01
10
11Torque is not generated.
Note. 0: off
1: on
driving mode/forward
rotation in regenerative
mode)
CW (forward rotation in
driving mode/reverse
rotation in regenerative
mode)
Polarity0V Polarity
Torque control command (TC)
CW (forward rotation in
driving mode/reverse
rotation in regenerative
Torque is not
generated.
mode)
CCW (reverse rotation in
driving mode/forward
rotation in regenerative
mode)
Torque is not generated.
Generally, make connection as shown below:
8 to 8V
Servo amplifier
RS1
RS2
SG
TC
LG
SD
3 - 31
3. SIGNALS AND WIRING
e
(b) Analog torque command offset
Using parameter No. 30, the offset voltage of
voltage as shown below.
Max. torque
Generated torque
999 to 999mV can be added to the TC applied
Parameter No.30 offset rang
999 to 999mV
0
TC applied voltage [V]
8( 8)
(2) Torque limit
By setting param eter No . 28 (inte rnal torqu e limi t 1), t orque is alw ays li mite d to the max imum value
during operation. A relationship between limit value and servo motor torque is as in (5) in section
3.4.1. Note that the analog torque limit (TLA) is unavailable.
(3) Speed limit
(a) Speed limit value and speed
The speed is limite d to the values se t in p a ra m ete rs No. 8 to 10 , 72 to 75 (internal spe e d limits 1 to
7) or the value set in the applied voltage of the analog speed li mit (VLA).
A relationship between the analog speed limit (VLA) applied voltage and the servo motor speed is
shown below.
When the servo motor speed reaches the speed limit value, torque control may become unstable.
Make the set value more than 100r/min greater than the desired speed limit value.
Speed [r/min]
CW direction
Rated speed
CCW direction
10
010
VLA applied voltage [V]
Rated speed
Forward rotation (CCW)
Reverse rotation (CW)
The following table indicates the limit direction according to forward rotation selection (RS1) and
reverse rotation selection (RS2) combination:
(Note) External input signalsSpeed limit direction
Choose any of the speed settings made by the internal speed limits 1 to 7 using speed selection
1(SP1), speed selection 2(SP2) and speed selection 3(SP3) or the speed setting made by the speed
limit command (VLA), as indicated below.
Setting of parameter
No. 43 to 48
When speed selection
(SP3) is not used
(initial status)
When the internal speed limits 1 to 7 are used to command the speed, the speed does not vary
with the ambient temperature.
(c) Limiting speed (VLC)
VLC turns on when the servo motor speed reaches the speed limited using any of the internal
speed limits 1 to 7 or the analog speed li mit (VLA).
3 - 33
3. SIGNALS AND WIRING
3.4.4 Position/speed control change mode
Set "0001" in par ameter No. 0 to switch to the position/spee d control change mode. This func tion is not
available in the absolute position detection system.
(1) Control change (LOP)
Use control change (LOP) to switch between the position control mode and the speed control mode
from an external contact. Relationships between LOP and control modes are indicated below:
(Note) LOPServo control mode
0Position control mode
1Speed control mode
Note. 0: off
1: on
The control mode may be changed in the zero-speed status. To ensure safety, change control after the
servo motor has stopped. When position control mode is changed to speed control mode, droop pulses are
reset.
If the signal has been switched on-off at the speed higher than the zero speed and the speed is then
reduced to the zero speed or less, the control mode cannot be changed. A change timing chart is shown
below:
Position
contro l m ode
Speed
contro l m ode
Position
contro l m ode
Zero speed
Servo motor speed
Zero speed (ZSP)
Control change (LOP)
Note: When ZSP is not on, control cannot be changed if LOP is switched on-off.
If ZSP switches on after that, control cannot not be changed.
level
ON
OFF
ON
OFF
(2) Torque limit in position control mode
As in Section 3.4.1 (5).
(Note)
(Note)
3 - 34
3. SIGNALS AND WIRING
2
(3) Speed setting in spee d co nt rol mod e
(a) Speed command and speed
The servo motor is run at the speed set in parameter No. 8 (internal speed command 1) or at the
speed set in the applied voltage of the analog speed command (VC). A relationship between analog
speed command (VC) applied voltage and servo motor speed and the rotation directions determined
by the forward rotation start (ST1) and reverse rotation start (ST2) are as in (a), (1) in section
3.4.2.
Generally, make connection as shown below:
Servo amplif ier
SP1
SG
k
Japan resistor
RRS10 or equivalent
2k
(b) Speed selection 1 (SP1) and speed command value
Use speed selection 1 (SP1) to select between the speed set by the internal speed command 1 and
the speed set by the analog speed command (VC) as indicated in the followi ng table:
By making speed selection 2 (SP2) spee d selection 3 (SP3) usable by se tting of parame ter No. 43
to 48, you can choose the speed command values of analog speed command (VC) and internal
speed commands 1 to 7.
(Note) External input signals
SP3SP2SP1
000Analog spee d com mand (VC)
001Internal speed command 1 (parame t er No. 8)
010Internal speed command 2 (parame t er No. 9)
011Internal speed command 3 (parame t er No. 10)
100Internal speed command 4 (parame t er No. 72)
101Internal speed command 5 (parameter No. 73)
110Internal speed command 6 (parame t er No. 74)
111Internal speed command 7 (parame t er No. 75)
Note. 0: off
1: on
Speed command value
The speed may also be changed during rotation. In this case, it is increased or decreased according
to the value set in parameter No. 11 or 12.
When the internal speed command 1 is used to command the speed, the speed does not vary with
the ambient temperature.
(c) Speed reached (SA)
As in Section 3.4.2 (2).
3 - 35
3. SIGNALS AND WIRING
3.4.5 Speed/torque control change mode
Set "0003" in parameter No. 0 to switch to the speed/torque control change mode.
(1) Control change (LOP)
Use control change (LOP) to switch between the speed control mode and the torque control mode from
an external contact. Relationships between LOP and control modes are indicated below:
(Note) LOPServo control mode
0Speed control mode
1Torque con tr ol mode
Note. 0: off
1: on
The control mode may be changed at any time. A change timing chart is shown below:
Speed
control mode
Control change (LOP)
Servo motor speed
Analog torque
command (TC)
Note: When the start (ST1 ST2) is switched off as soon as the mode is changed to speed control,
the servo motor comes to a stop according to the deceleration time constant.
ON
OFF
10V
0
Torque
control mode
Load torque
Forward rotation in driving mode
Speed
control mode
(Note)
(2) Speed setting in spee d co nt rol mod e
As in Section 3.4.2 (1).
(3) Torque limit in speed control mode
As in Section 3.4.1 (5).
3 - 36
3. SIGNALS AND WIRING
r
(4) Speed limit i n to rque con t rol mod e
(a) Speed limit value and speed
The speed is limited to the limit value set in parameter No. 8 (internal speed limit 1) or the value
set in the applied voltage of the analog speed limit (VLA). A relationship between the analog speed
limit (VLA) applied voltage and the servo motor speed is as in (a), (3) in section 3.4.3.
Generally, make connection as shown below:
Servo amplifie
SP1
SG
2k
Japan resistor
RRS10 or equivalent
2k
(b) Speed selection 1 (SP1) and speed limit value
Use speed selection 1 (SP1) to select between the speed set by the internal speed command 1 and
the speed set by the analog speed limit (VLA) as indicat ed in the foll owing tabl e:
When the internal speed limit 1 is used to command the speed, the speed does not vary with the
ambient temperature.
(c) Limiting speed (VLC)
As in (c), (3) in section 3.4.3.
(5) Torque control in torque control mode
As in Section 3.4.3 (1).
(6) Torque limit in torque control mode
As in Section 3.4.3 (2).
3 - 37
3. SIGNALS AND WIRING
3.4.6 Torque/position control change mode
Set "0005" in parameter No. 0 to switch to the torque/position control change mode.
(1) Control change (LOP)
Use control change (LOP) to switch between the torque con trol mode and the position control mode
from an external contact. Relationships between LOP and control modes are indicated below:
(Note) LOPServo control mode
0Torque con tr ol mode
1Position control mode
Note. 0: off
1: on
The control mode may be changed in the zero-speed status.
To ensure safety, change control after the servo motor has stopped. When position control mode is
changed to torque control mode, droop pulses are reset.
If the signal has been switched on-off at the speed higher than the zero speed and the speed is then
reduced to the zero speed or less, the control mode cannot be changed. A change timing chart is shown
below:
Speed
control mode
Torque
control mode
Speed
control mode
Servo m o t o r speed
Analog torque
command (TLA)
Zero speed (ZSP)
Control change (LOP)
(2) Speed limit i n to rque con t rol mod e
As in Section 3.4.3 (3).
(3) Torque control in torque control mode
As in Section 3.4.3 (1).
(4) Torque limit in torque control mode
As in Section 3.4.3 (2).
(5) Torque limit in position control mode
As in Section 3.4.1 (5).
Zero speed
level
10V
0V
ON
OFF
ON
OFF
3 - 38
3. SIGNALS AND WIRING
3.5 Alarm occurrence timing chart
When an alarm has occurred, remove its cause, make sure that the operation
signal is not being input, ensure safety, and reset the alarm before restarting
CAUTION
When an alarm occurs in the servo amplifier, the base circuit is shut off and the s ervo motor is coated to a
stop. Switch off the main circuit power supply in the external sequence. To reset the alarm, switch the
control circuit power supply from off to on, press the "SET" button on the current alarm screen, or turn
the reset (RES) from off to on. However, the alarm cannot be reset unless its cause is removed.
(Note)
Main circuit
control circuit
power sup p l y
Base circuit
Dynamic brake
Invalid
Servo-on
(SON)
Ready
(RD)
Trouble
(ALM)
Reset
(RES)
operation.
As soon as an alarm occurs, turn off Servo-on (SON) and power off the main
circuit.
ON
OFF
ON
OFF
Valid
ON
OFF
ON
OFF
ON
OFF
ON
OFF
1s
about
Alarm occurs.
Brake operation
50ms or more
Remove cause of trouble.
Power off
Brake operation
60ms or more
Power on
Note. Shut off the main circuit power as soon as an alarm occurs.
(1) Overcurrent, overload 1 or overload 2
If operation is repeated by switching control circuit power off, then on to reset the overcurrent
(AL.32), overload 1 (AL.50) or overload 2 (AL.51) alarm after its occurrence, without removing
its cause, the servo amplifier and servo motor may become faulty due to temperature rise.
Securely remove the cause of the alarm and also allow about 30 minutes for cooling before
resuming operation.
(2) Regenerative alarm
If operation is repeated by switching control circuit power off, then on to reset the regenerative
(AL.30) alarm after its occurrence, the external regenerative brake resistor will gener ate heat,
resulting in an accident.
(3) Instantane ou s pow e r fa il ur e
Undervoltage (AL.10) occurs when the input power is in either of the following statuses.
A power failure of the control circuit power supply continues for 60ms or longer and the
control circuit is not completely off.
The bus voltage dropped to 200VDC or less for the MR-J2S- A, or to 158VDC or less for the
MR-J2S-
A1.
(4) In position control mode (incremental)
When an alarm occurs, the home position is lost. When resuming operation after deactivating
the alarm, make a home position return.
3 - 39
3. SIGNALS AND WIRING
3.6 Interfaces
3.6.1 Common line
The following diagram shows the power supply and its common line.
DC24V
ALM .etc
DI-1
(Note)
CN1A
CN1B
VDD
COM
SON, etc.
SG
OPC
PG NG
PP NP
CN1A
CN1B
RA
DO-1
Analog input
( 10V/max. current)
Servo motor
M
SG
15VDC 10%
30mA
P15R
TLA
VC etc.
LG
SD
Isolated
SG
OP
LG
LA etc.
LAR
etc.
LG
SD
MO1
MO2
LG
SDP
SDN
RDP
RDN
LG
SD
TXD
RXD
MR
MRR
LG
SD
CN3
Analog monitor output
RS-232C
Servo motor encoder
CN2
Differential line
driver output
35mA max.
RS-422
Ground
Note. For the open collection pulse train input. Make the following connection for the different line driver
pulse train input.
OPC
PG NG
PP NP
SG
3 - 40
3. SIGNALS AND WIRING
3.6.2 Detailed description of the interfaces
This section gives the details of the I/O signal interfaces (refer to I/O Division in the table) indicated in
Sections 3.3.2.
Refer to this section and connect the interfaces with the external equipment.
(1) Digital input interface DI-1
Give a signal with a relay or open collector transistor.
Source input is also possible. Refer to (7) in this section.
For use of internal power supplyFor use of external power supply
Servo amplifier
Do not connect
VDD-COM.
24VDC
200mA or more
Servo amplifier
VDD
COM
SON, etc.
24VDC
R: Approx. 4.7
(Note)
For a transistor
Approx. 5mA
Switch
VDD
COM
SON, etc.
24VDC
R: Approx. 4.7
SGTR
Switch
V
1.0V
CES
CEO
100 A
I
Note. This also applies to the use of the external power supply.
SG
(2) Digital output interface DO-1
A lamp, relay or photocoupler can be driven. Provide a diode (D) for an inductive load, or an inrush
current suppressing resister (R) for a lamp load. (Permissible current: 40mA or less, inrush current:
100mA or less)
(a) Inductive load
For use of internal power supplyFor use of external power supply
Servo amplifier
24VDC
VDD
COM
ALM, etc.
SG
Load
If the diode is not
connected as shown,
the servo amplifier
will be damaged.
Servo amplifier
24VDC
ALM, etc.
VDD
COM
SG
Do not connect
VDD-COM.
Load
If the diode is not
connected as shown,
the servo amplifier
will be damaged.
24VDC
10%
3 - 41
3. SIGNALS AND WIRING
R
(b) Lamp load
For use of internal power supplyFor use of external power supply
Servo amplifier
24VDC
VDD
COM
ALM, etc.
SG
(3) Pulse trai n in put int e rfa ce DI -2
Provide a pulse train signal in the open collector or differential line driver system.
(a) Open collector system
1) Interface
For use of internal power supplyFor use of external power supply
Servo amplifier
VDD
OPC
2m (78.74in) or less
PP, NP
SG
24VDC
Max. input pulse
frequency 200kpps
About 1.2k
Servo amplifier
24VDC
ALM, etc.
Do not connect
VDD-OPC.
2m (78.74in) or less
24VDC
VDD
COM
SG
Do not connect
VDD-COM.
R
Servo amplifier
VDD
OPC
PP, NP
24VDC
Max. input pulse
frequency 200kpps
About 1.2k
24VDC
10%
SD
2) Conditions of the input pulse
0.9
PP
0.1
NP
tc
tctLH
tHL
3 - 42
SG
SD
tLH tHL 0.2 s
tc 2 s
tF 3 s
tF
3. SIGNALS AND WIRING
(b) Differential line driver system
1) Interface
10m (393.70in) or less
Servo amplifier
Max. input pulse
frequency 500kpps
PP(NP)
2) Conditions of the input pulse
(4) Encoder pul se outp ut D O- 2
(a) Open collector system
Interface
Max. output current : 35mA
Servo amplifier
OP
LG
Am26LS31 or equivalent
PP PG
NP NG
0.9
0.1
tctLH
PG(NG)
SD
tHL
tc
About 100
tLH tHL 0.1 s
tc 1 s
tF 3 s
tF
Servo amplifier
OP
LG
5 to 24VDC
Photocoupler
SD
SD
3 - 43
3. SIGNALS AND WIRING
(b) Differential line driver system
1) Interface
Max. output current: 35mA
Servo amplifierServo amplifier
LA
(LB, LZ)
LAR
(LBR, LZR)
LG
SD
2) Output pulse
Servo motor CCW rotation
LA
Am26LS32 or equivalentHigh-speed photocoupler
150
LA
(LB, LZ)
LAR
(LBR, LZR)
SD
100
LAR
LB
LBR
LZ
LZR
OP
T
/2
(5) Analog input
Input impedance 10 to 12k
Upper limit setting 2k
2k
(6) Analog output
Output voltage
10V
Max.1mA
Max. output current
Resolution : 10bit
Servo amplifier
400 s or more
Servo amplifier
P15R
VC‚ etc
Approx.
LG
10k
SD
The time cycle (T) is determined by
the setting of the parameter No. 27 and 54.
15VDC
MO1
(MO2)
LG
SD
10k
Reading in one or
both directions
1mA meter
A
3 - 44
3. SIGNALS AND WIRING
(7) Source input interface
When using the input interface of source type, all Dl-1 input signals are of source type. Source output
cannot be provided.
For use of internal power supplyFor use of external power supply
Servo amplifier
Servo amplifier
SG
(Note)
For a transistor
Approx. 5mA
Switch
TR
V
1.0V
CES
100 A
I
CEO
Note. This also applies to the use of the external power supply.
COM
SON,
etc.
VDD
R: Approx. 4.7
24VDC
Switch
24VDC
200mA or more
SG
COM
SON,etc.
R: Approx. 4.7
When using the input interface o f source type, all Dl-1 input signals are of source type . Source output
cannot be provided.
For 11kW or more, the source input interface cannot be used with the internal power supply. Always use
the external power supply.
MITSUBISHI
CON2CON2
CON2
JP11
Note. The jumper, which is shown black for the convenience of explanation, is actually white.
JP11JP11
Jumper
For sink input (factory setting)For source input
(Note)(Note)
Jumper
3 - 45
3. SIGNALS AND WIRING
3.7 Input power supply circuit
When the servo amplifier has become faulty, switch power off on the servo
amplifier power side. Continuous flow of a large current may cause a fire.
CAUTION
3.7.1 Connection example
Wire the power supply and main circuit as shown below so that the servo-on (SON) turns off as soon as
alarm occurrence is detected and power is shut off.
A no-fuse breaker (NFB) must be used with the input cables of the power supply.
Use the trouble signal to switch power off. Otherwise, a regenerative brake
transistor fault or the like may o verheat the r egenerative b rake resist or, causing a
fire.
POINT
For the power line circuit of the MR-J2S-11KA to MR-J2S-22KA, refer to
Section 3.13 where the power line ci rcuit is shown together with th e servo
motor connection diagram.
(1) For 3-phase 200 to 230VAC power supply
RA
NFBMC
3-Phase
200 to 230 VAC
Emergency
stop
Servo-on
Emergency
stop
OFF
L
1
L
2
L
3
11
L
21
L
EMG
SON
SG
ON
MC
Servo amplifier
VDD
COM
ALMRA
MC
SK
Trouble
3 - 46
3. SIGNALS AND WIRING
(2) For 1-phase 100 to 120VAC or 1-phase 230VAC power supply
RA
Emergency
stop
OFF
ON
MC
MC
SK
Power supply
1-phase 100 to
120VAC or
1-phase 230VAC
NFBMC
Emergency stop
Servo-on
EMG
SON
Note. Not provided for 1-phase 100 to 120VAC.
Servo amplifier
L
1
L
2
(Note)
L
3
11
L
21
L
SG
VDD
COM
ALMRA
Trouble
3 - 47
3. SIGNALS AND WIRING
3.7.2 Terminals
The positions and signal arrangements of the terminal blocks change with the capacity of the servo
amplifier. Refer to Section 11.1.
Symbol
Connection Target
(Application)
Supply L1, L2 and L3 with the following power:
For 1-phase 230VAC, connect the power supply to L
Servo amplifier
Power supply
3-phase 200 to 230VAC,
L1, L2, L3Main circuit power supply
50/60Hz
1-phase 230VAC,
50/60Hz
1-phase 100 to 120VAC,
50/60Hz
U, V, WServo motor outputConnect to the servo motor power supply terminals (U, V, W).
Supply L11 and L12 with the following power.
Servo amplifier
Power supply
L11, L21Control circuit power supply
1-phase 200 to 230VAC,
50/60Hz
1-phase 100 to 120VAC,
50/60Hz
Description
and leave L3 open.
1/L2
MR-J2S-10A to
70A
L
1L2
L
1L2L3
MR-J2S-100A
to 22kA
MR-J2S-10A1
to 40A1
L
1L2
MR-J2S-10A to 700AMR-J2S-10A1 to 40A1
L
11L21
L
11L21
P, C, DRegenerative brake option
N
Return conv erter
Brake unit
Protective eart h (PE)
1) MR-J2S-350A or less
Wiring is factory-connected across P-D (servo amplifier built-in regenerative
brake resistor).
When using the regenerative bra ke option, alw a y s remove the wiri n g from
across P-D and connect the regenerative brake option across P-C.
2) MR-J2S-500A
700A
Wiring is factory-connected across P-C (servo amplifier built-in regenerative
brake resistor).
When using the regenerative brake option, always remove the wiring from
across P-C and connect the regene rative brake option a cross P-C.
Refer to Section 13.1.1 for details.
When using the return converter or brak e unit, conn e ct it across P-N.
Do not connect it to the servo amplifier of MR-J2S-350A or less.
Refer to Sections 13.1.2 and 13.1.3 for details.
Connect this terminal to the protective earth (PE) terminals of the servo motor
and contro l box for groundi ng.
3 - 48
3. SIGNALS AND WIRING
3.7.3 Power-on sequence
(1) Power-on procedure
1) Always wire the power supp ly as shown in above Section 3. 7.1 using the magnetic con tactor with
the main circuit power supply (three-phase 200V: L
1
L
, L2). Configure up an external sequence to switch off the magnetic contactor as soon as an alarm
occurs.
2) Switch on the control circuit power supply L
supply or before switching on the main circuit power supply. If the main circuit power supply is not
on, the display shows the corresponding warning. However, by switching on the main circuit power
supply, the warning disappears and the servo amplifier will operate properly.
3) The servo amplifier can accept the servo-on (SON) about 1 to 2s af ter the m ain cir cui t power supply
is switched on. Therefore, when SON is switched on simultaneously with the main circuit power
supply, the b ase circu it wi ll sw itch on in a bout 1 to 2s , and the ready (RD ) w ill sw it ch on in fu rthe r
about 20ms, making the servo amplifier ready to operate. (Refer to paragraph (2) in this section. )
4) When the reset (RES) is switched on, the base circuit is shut off and the servo motor shaft coasts.
(2) Timing chart
Servo-on (SON) accepted
1
, L2, L3, single-phase 230V, single-phase 100V:
11
, L21 simultaneously with the main circuit power
Main circuit
Control circuit
Power supply
Base circuit
Servo-on
(SON)
Reset
(RES)
Ready
(RD)
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
(1 to 2s)
10ms
60ms
10ms20ms
Power-on timing chart
10ms
10ms20ms
60ms
20ms10ms
(3) Emergency stop
Make up a circuit that shuts off main circuit power as soon as EMG is turned off at an emergency stop.
When EMG is turned off, the dynamic brake is operated to bring the servo motor to a sudden stop. At
this time, the display shows the servo emergency stop warning (AL.E6).
During ordinary operation, do not use the external emergency stop (EMG) to alternate stop and run.
The servo amplifier life may be shortened.
Also, if the forward rotation start (ST1) and reverse rotation start (ST2 ) are on or a pulse train is input
during an emergency stop, the servo motor will rotate as soon as the warning is reset. During an
emergency stop, always shut off the run command.
Servo amplifier
Emergency stop
VDD
COM
EMG
SG
3 - 49
3. SIGNALS AND WIRING
3.8 Connection of servo amplifier and servo motor
3.8.1 Connection instructions
WARNING
Insulate the connections of the power supply terminals to prevent an electric
shock.
Connect the wires to the corr ect phase term inals (U, V, W ) of the servo am plifier
CAUTION
and servo motor. Otherwise, the servo motor will operate improperly.
Do not connect AC power supp ly directly to the servo m otor. Otherwis e, a fault
may occur.
POINT
Do not apply the test lead bars or like of a tester directly to the pins of the
connectors supplied with the servo motor. Doing so will deform the pins,
causing poor contact.
The connection method differs according to the series and cap acity of the servo mo tor and whe ther or not
the servo motor has the electromagnetic brake. Perform wiring in accordance with this section.
(1) For grounding, connect the earth cable of the servo motor to the protective earth (PE) terminal of the
servo amplifier and connect the ground cable of the servo amplifier to the earth via the protective
earth of the control box. Do not connect them directly to the protective earth of the control panel.
Control box
Servo
amplifier
PE terminal
Servo motor
(2) Do not share the 24VDC interface power supply between the interface and electromagnetic brake.
Always use the power supply designed exclusively for the electromagnetic brake.
3.8.2 Connection diagram
The followin g table lists wiring m ethods accord ing to th e servo motor type s. Use the conn ection diag ram
which conforms to the servo motor used. For cables required for wiring, refer to Section 13.2.1. For
encoder cable connection, refer to Section 13.1.5. For the signal layouts of the connectors, refer to Section
3.8.3.
For the servo motor connector, refer to Chapter 3 of the Servo Motor Instruction Manual.
POINT
For the connection diagram of the MR-J2S-11KA to MR-J2S-22KA, refer
to Section 3.13 where the connection diagram is shown together with the
power line circuit.
3 - 50
3. SIGNALS AND WIRING
Servo motorConnection diagram
HC-KFS053 (B) to 73 (B)
HC-MFS053 (B) to 73 (B)
HC-UFS13 (B) to 73 (B)
Servo amplifier
W
CN2
U
V
(Note 1)
24VDC
EMG
To be shut off when servo-off
or Trouble (ALM)
U (Red)
V (White)
W (Black)
(Green)
B1
B2
Servo motor
Motor
(Note 2)
Electromagnetic
brake
HC-SFS121 (B) to 301 (B)
HC-SFS202 (B)
HC-SFS203 (B)
702 (B)
353 (B)
HC-UFS202 (B) to 502 (B)
HC-RFS353 (B) to 503 (B)
Encoder cable
Encoder
Note 1. To prevent an electric shock, always connect the protective earth (PE) terminal of the
servo amplifier to the protective earth (PE) of the control box.
2. This circuit applies to the servo motor with electromagnetic brake.
Servo amplifier
U
V
W
(Note 1)
24VDC
EMG
To be shut off when servo-off
Servo motor
U
V
Motor
W
B1
B2
Electromagnetic
brake
(Note 2)
or Trouble (ALM)
CN2
Encoder cable
Encoder
Note 1. To prevent an electric shock, always connect the protective earth (PE) terminal of the
servo amplifier to the protective earth (PE) of the control box.
2. This circuit applies to the servo motor with electromagnetic brake.
Servo amplifier
U
V
W
Servo motor
U
V
W
Motor
HC-SFS81 (B)
HC-SFS52 (B) to 152 (B)
HC-SFS53 (B) to 153 (B)
HC-RFS103 (B) to 203 (B)
HC-UFS72 (B)
152 (B)
EMG
24VDC
B1
B2
Electromagnetic
brake
(Note 2)
(Note 1)
To be shut off when servo-off
or Trouble (ALM)
CN2
Encoder cable
Encoder
Note 1. To prevent an electric shock, always connect the protective earth (PE) terminal of the
servo amplifier to the protective earth (PE) of the control box.
2. This circuit applies to the servo motor with electromagnetic brake.